Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:41
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
Simulation Timestamp: 2023-10-16 08:41:11
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:11
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1368.83 | 654.84 | 654.84 |
Net Site Energy | 1368.83 | 654.84 | 654.84 |
Total Source Energy | 4329.10 | 2071.02 | 2071.02 |
Net Source Energy | 4329.10 | 2071.02 | 2071.02 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 2.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 502.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 441.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 99.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 134.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 58.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1365.96 | 2.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 2.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 502.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 441.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 99.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 134.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 58.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 2.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 502.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 441.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 99.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 134.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 58.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 259.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 332.89 | 1.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 653.47 | 1.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 259.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 332.89 | 1.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 653.47 | 1.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1365.957 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1365.957 | 100.00 |
Total On-Site and Utility Electric Sources | 1365.957 | 100.00 |
Total Electricity End Uses | 1365.957 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 12.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1420.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:11
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:41 |
RunPeriod | RUNPERIOD 1 |
Weather File | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Latitude [deg] | 28.58 |
Longitude [deg] | 77.20 |
Elevation [m] | 216.00 |
Time Zone | 5.50 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.77 | 20.77 | 17.8770 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.38 | 10.38 | 19.3382 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 17.3739 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 17.3739 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 17.3739 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.72 | 20.72 | 13.1675 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.3365 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.3365 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.3365 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.36 | 10.36 | 13.3365 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 15.5746 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 15.5746 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 17.8770 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 19.3382 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 17.3739 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 17.3739 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 17.3739 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 13.1675 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 13.3365 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 13.3365 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 13.3365 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 13.3365 | 6.19 | 4.3000 | |
Total | 2090.32 | 15.5746 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 15.5746 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 15.5746 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:11
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 22-JUN-16:40 | 02-JAN-09:09 | - | - | - | - | - | - | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 109100.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 85851.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 27522.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 13388.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4741.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 139593.76 | 109100.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 109100.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 85851.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 27522.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 13388.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 4741.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:11
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 3.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1592.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1398.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 316.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 407.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 425.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 186.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4325.99 | 3.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 761.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 668.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 151.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 203.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 89.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2069.53 | 1.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 761.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 668.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 151.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 203.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 89.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2069.53 | 1.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:11
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 2.81 |
SMSTORE1 DIRECT AIR | 1.44 |
SMSTORE2 DIRECT AIR | 1.44 |
SMSTORE3 DIRECT AIR | 1.44 |
SMSTORE4 DIRECT AIR | 1.44 |
LGSTORE2 DIRECT AIR | 2.63 |
SMSTORE5 DIRECT AIR | 1.39 |
SMSTORE6 DIRECT AIR | 1.39 |
SMSTORE7 DIRECT AIR | 1.39 |
SMSTORE8 DIRECT AIR | 1.57 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.81 | 2.81 | 2.81 | 2.81 | 2.81 | 2.81 | 1.00 | 1.00 | 2.81 |
PSZ-AC_2:2 | 1.44 | 1.44 | 1.44 | 1.44 | 1.44 | 1.44 | 1.00 | 1.00 | 1.44 |
PSZ-AC_3:3 | 1.44 | 1.44 | 1.44 | 1.44 | 1.44 | 1.44 | 1.00 | 1.00 | 1.44 |
PSZ-AC_4:4 | 1.44 | 1.44 | 1.44 | 1.44 | 1.44 | 1.44 | 1.00 | 1.00 | 1.44 |
PSZ-AC_5:5 | 1.44 | 1.44 | 1.44 | 1.44 | 1.44 | 1.44 | 1.00 | 1.00 | 1.44 |
PSZ-AC_6:6 | 2.63 | 2.63 | 2.63 | 2.63 | 2.63 | 2.63 | 1.00 | 0.999999 | 2.63 |
PSZ-AC_7:7 | 1.39 | 1.39 | 1.39 | 1.39 | 1.39 | 1.39 | 1.00 | 1.00 | 1.39 |
PSZ-AC_8:8 | 1.39 | 1.39 | 1.39 | 1.39 | 1.39 | 1.39 | 1.00 | 1.000000 | 1.39 |
PSZ-AC_9:9 | 1.39 | 1.39 | 1.39 | 1.39 | 1.39 | 1.39 | 1.00 | 1.00 | 1.39 |
PSZ-AC_10:10 | 1.57 | 1.57 | 1.57 | 1.57 | 1.57 | 1.57 | 1.00 | 1.00 | 1.57 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.81 | 0.411479 |
PSZ-AC_2:2_OA_CONTROLLER | 1.44 | 0.205739 |
PSZ-AC_3:3_OA_CONTROLLER | 1.44 | 0.205739 |
PSZ-AC_4:4_OA_CONTROLLER | 1.44 | 0.205739 |
PSZ-AC_5:5_OA_CONTROLLER | 1.44 | 0.205739 |
PSZ-AC_6:6_OA_CONTROLLER | 2.63 | 0.411479 |
PSZ-AC_7:7_OA_CONTROLLER | 1.39 | 0.205739 |
PSZ-AC_8:8_OA_CONTROLLER | 1.39 | 0.205739 |
PSZ-AC_9:9_OA_CONTROLLER | 1.39 | 0.205739 |
PSZ-AC_10:10_OA_CONTROLLER | 1.57 | 0.205739 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.81 | 3012.03 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.44 | 1542.78 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.44 | 1536.34 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.44 | 1539.72 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.44 | 1536.18 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 2.63 | 2815.57 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 1.39 | 1543.22 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 1.39 | 1537.75 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 1.39 | 1542.10 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.57 | 1677.69 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.81 | 2.81 | 2.81 | 1.86 | 64960.70 | 69907.26 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.44 | 1.44 | 1.44 | 0.951581 | 33185.01 | 35719.39 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.44 | 1.44 | 1.44 | 0.947609 | 33074.15 | 35585.32 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.44 | 1.44 | 1.44 | 0.949693 | 33132.96 | 35655.68 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.44 | 1.44 | 1.44 | 0.947508 | 33071.71 | 35581.92 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 2.63 | 2.63 | 2.63 | 1.74 | 61513.13 | 65816.25 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 1.39 | 1.39 | 1.39 | 0.919946 | 32298.85 | 34651.42 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 1.39 | 1.39 | 1.39 | 0.916682 | 32207.07 | 34541.22 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 1.39 | 1.39 | 1.39 | 0.919278 | 32280.50 | 34628.84 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.57 | 1.57 | 1.57 | 1.03 | 35327.26 | 38528.73 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 2.81 | 1.41 | 1.88 | 64960.70 | 32480.35 | 0.724720 | 0.724720 |
PSZ-AC_2:2 COOLING COIL | 1.44 | 0.720895 | 0.961193 | 33185.01 | 16592.51 | 0.725420 | 0.725420 |
PSZ-AC_3:3 COOLING COIL | 1.44 | 0.717886 | 0.957180 | 33074.15 | 16537.08 | 0.725200 | 0.725200 |
PSZ-AC_4:4 COOLING COIL | 1.44 | 0.719465 | 0.959287 | 33132.96 | 16566.48 | 0.725310 | 0.725310 |
PSZ-AC_5:5 COOLING COIL | 1.44 | 0.717809 | 0.957080 | 33071.71 | 16535.85 | 0.725190 | 0.725190 |
PSZ-AC_6:6 COOLING COIL | 2.63 | 1.32 | 1.75 | 61513.13 | 30756.56 | 0.720330 | 0.720330 |
PSZ-AC_7:7 COOLING COIL | 1.39 | 0.696929 | 0.929240 | 32298.85 | 16149.42 | 0.722640 | 0.722640 |
PSZ-AC_8:8 COOLING COIL | 1.39 | 0.694456 | 0.925940 | 32207.07 | 16103.53 | 0.722460 | 0.722460 |
PSZ-AC_9:9 COOLING COIL | 1.39 | 0.696422 | 0.928560 | 32280.50 | 16140.25 | 0.722600 | 0.722600 |
PSZ-AC_10:10 COOLING COIL | 1.57 | 0.783933 | 1.05 | 35327.26 | 17663.63 | 0.732100 | 0.732100 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 69907.26 |
PSZ-AC_2:2 HEATING COIL | 35719.39 |
PSZ-AC_3:3 HEATING COIL | 35585.32 |
PSZ-AC_4:4 HEATING COIL | 35655.68 |
PSZ-AC_5:5 HEATING COIL | 35581.92 |
PSZ-AC_6:6 HEATING COIL | 65816.25 |
PSZ-AC_7:7 HEATING COIL | 34651.42 |
PSZ-AC_8:8 HEATING COIL | 34541.22 |
PSZ-AC_9:9 HEATING COIL | 34628.84 |
PSZ-AC_10:10 HEATING COIL | 38528.73 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:11
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:11
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:11
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 25.10 | 19.60 | 14.50 | 13.40 | 17.00 | 22.40 | 29.10 | 33.00 | 33.60 | 31.70 | 30.00 | 28.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 | 28.58 | 77.20 | 5.50 | 216.00 | 98757 | 1.1738 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.84 | 20.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.74 | 20.77 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.66 | 10.38 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.41 | 20.72 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.12 | 10.36 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 17.877 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.177 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 19.338 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 23.638 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 17.374 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.674 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 17.374 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.674 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 17.374 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.674 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 13.168 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.468 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 13.336 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.636 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 13.336 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.636 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 13.336 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.636 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 13.336 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.636 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 4596.695 | 13.194 | 81.718 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4596.695 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 1631.408 | 4.683 | 29.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1631.408 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 2327.780 | 13.363 | 82.767 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2327.780 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1040.795 | 5.975 | 37.007 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1040.795 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 2323.122 | 13.336 | 82.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2323.122 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 703.295 | 4.037 | 25.007 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 703.295 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 2323.122 | 13.336 | 82.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2323.122 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 703.295 | 4.037 | 25.007 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 703.295 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 2323.122 | 13.336 | 82.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2323.122 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 703.295 | 4.037 | 25.007 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 703.295 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 4587.379 | 13.168 | 81.553 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4587.379 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 2323.122 | 13.336 | 82.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2323.122 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 2323.122 | 13.336 | 82.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2323.122 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 2323.122 | 13.336 | 82.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2323.122 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 2323.122 | 13.336 | 82.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2323.122 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.7544 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1995 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2888 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.092 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.937 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.386 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
19 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
20 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
21 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
22 | 7 | -0.31526305E-12 | 0.65421067E-14 | -0.96995935E-13 | 0.16372101E-15 |
23 | 6 | 0.28934589E-07 | 0.21281465E-09 | 0.66261080E-08 | -0.13661131E-12 |
24 | 5 | -0.19144321E-03 | 0.18179002E-05 | -0.98452505E-04 | 0.65494719E-08 |
25 | 4 | 0.29370911 | 0.88327295E-03 | 0.10024532 | -0.33791493E-04 |
26 | 3 | -7.2972687 | 0.27321832E-01 | -2.3480939 | 0.29160644E-01 |
27 | 2 | 40.973187 | 0.96992104E-01 | 15.302757 | -0.33447687 |
28 | 1 | -80.623988 | 0.43709902E-01 | -29.175449 | 1.0802857 |
29 | 0 | 46.824338 | 0.87814252E-03 | 16.290426 | |
30 | 7 | -0.21163652E-08 | -0.68723841E-15 | 0.43910983E-14 | -0.57684426E-16 |
31 | 6 | 0.56109385E-05 | 0.38186281E-08 | 0.31898696E-02 | -0.26759299E-04 |
32 | 5 | -0.40164657E-03 | 0.22608617E-05 | -0.22372456 | 0.19561502E-02 |
33 | 4 | 0.92272104E-02 | 0.10289840E-03 | 4.8295456 | -0.45264980E-01 |
34 | 3 | -0.80993241E-01 | 0.81813938E-03 | -38.021416 | 0.39865375 |
35 | 2 | 0.28754352 | 0.13608947E-02 | 116.48395 | -1.4179393 |
36 | 1 | -0.41499682 | 0.41453381E-03 | -143.90731 | 2.0490399 |
37 | 0 | 0.20232414 | 0.10048102E-04 | 60.838472 | |
38 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
39 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
40 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
41 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
42 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
43 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
44 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
45 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
46 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
47 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
48 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
49 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
50 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
51 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
52 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
53 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
54 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
55 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
56 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
57 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
58 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
59 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
60 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
61 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
62 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
63 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
64 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
65 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
66 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
67 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
68 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
69 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
70 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
71 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
72 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
73 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
74 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
75 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
76 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
77 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
78 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
79 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
80 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
81 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
82 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
83 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
84 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
85 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
86 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
87 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
88 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
89 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
90 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
91 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
92 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
93 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
94 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479936E-14 | -0.41635794E-16 |
95 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
96 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
97 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
98 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
99 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
100 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
101 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
102 | 7 | -0.14484255E-08 | -0.22640907E-15 | 0.11860658E-13 | -0.17473455E-15 |
103 | 6 | 0.80640390E-05 | 0.55493782E-08 | 0.31828288E-02 | -0.26700235E-04 |
104 | 5 | -0.58275339E-03 | 0.32892043E-05 | -0.22332434 | 0.19526176E-02 |
105 | 4 | 0.13421983E-01 | 0.14977251E-03 | 4.8228790 | -0.45200897E-01 |
106 | 3 | -0.11791368 | 0.11914425E-02 | -37.983753 | 0.39823745 |
107 | 2 | 0.41875064 | 0.19825898E-02 | 116.41064 | -1.4169588 |
108 | 1 | -0.60444169 | 0.60433957E-03 | -143.86415 | 2.0483306 |
109 | 0 | 0.29470347 | 0.14596444E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 35 | 1 | VerySmooth | 2.861 | 2.861 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 1.93170E-002 | 0.16139 | 0.61074 | 0.61074 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10774 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 0.157 | 4.517E-004 | 2.488E-004 | 0.314 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.389 | 1.116E-003 | 6.149E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.648E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 8.993E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.389 | 1.116E-003 | 7.565E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 0.112 | 6.453E-004 | 2.994E-004 | 0.448 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 5.921E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 31070.23523 | 37284.28228 | 2.34571 | 2.81486 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:50:00 | 42.00000 | 9.15790E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 14378.72040 | 17254.46448 | 0.63591 | 0.76310 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 15914.41934 | 19097.30320 | 1.20149 | 1.44179 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 42.00000 | 9.15790E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 7228.84614 | 8674.61537 | 0.31970 | 0.38364 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 15847.99570 | 19017.59483 | 1.19648 | 1.43577 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 41.91917 | 9.15777E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 7312.04750 | 8774.45700 | 0.32338 | 0.38806 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 15882.85344 | 19059.42413 | 1.19911 | 1.43893 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 41.91917 | 9.15777E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 7380.88163 | 8857.05795 | 0.32643 | 0.39171 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 15846.31749 | 19015.58099 | 1.19635 | 1.43562 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 41.91917 | 9.15777E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 7523.09314 | 9027.71177 | 0.33271 | 0.39926 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 29043.78239 | 34852.53886 | 2.19271 | 2.63125 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 | 41.83833 | 9.15763E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 14211.73006 | 17054.07608 | 0.62853 | 0.75423 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 15385.37808 | 18462.45370 | 1.16155 | 1.39386 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 | 41.83833 | 9.15763E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 7714.47166 | 9257.36599 | 0.34118 | 0.40941 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 15330.78903 | 18396.94684 | 1.15743 | 1.38891 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 | 41.83833 | 9.15763E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 7714.94160 | 9257.92992 | 0.34120 | 0.40944 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 15374.19779 | 18449.03735 | 1.16070 | 1.39284 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 | 41.83833 | 9.15763E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 7929.66108 | 9515.59330 | 0.35070 | 0.42083 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 17306.57184 | 20767.88620 | 1.30656 | 1.56787 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:00:00 | 41.51500 | 9.15709E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 9096.76500 | 10916.11800 | 0.40231 | 0.48277 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 45599.39 | 2.81486 | 2.81486 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 24190.44 | 0.76310 | 0.76310 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 23249.04 | 1.44179 | 1.44179 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 12141.89 | 0.38364 | 0.38364 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 23169.00 | 1.43577 | 1.43577 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 12240.27 | 0.38806 | 0.38806 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 23209.54 | 1.43893 | 1.43893 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 12321.67 | 0.39171 | 0.39171 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 23166.05 | 1.43562 | 1.43562 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 12489.84 | 0.39926 | 0.39926 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 43189.63 | 2.63126 | 2.63126 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 23992.97 | 0.75423 | 0.75423 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 22615.41 | 1.39386 | 1.39386 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 12716.15 | 0.40941 | 0.40941 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 22550.58 | 1.38891 | 1.38891 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 12716.70 | 0.40944 | 0.40944 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 22600.97 | 1.39284 | 1.39284 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 12970.61 | 0.42083 | 0.42083 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 24796.62 | 1.56787 | 1.56787 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 14350.73 | 0.48277 | 0.48277 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.81486 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.44179 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.43577 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.43893 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.43562 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.63125 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.39386 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.38891 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.39284 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.56787 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.81486 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.81486 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.81486 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.81486 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.81486 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.81486 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.44179 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.44179 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.44179 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.44179 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.44179 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.44179 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.43577 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.43577 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.43577 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.43577 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.43577 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.43577 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.43893 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.43893 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.43893 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.43893 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.43893 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.43893 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.43562 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.43562 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.43562 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.43562 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.43562 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.43562 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.63125 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.63125 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.63125 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.63125 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.63126 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 2.63126 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.39386 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.39386 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.39386 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.39386 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.39386 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 1.39386 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 1.00000 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.38891 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.38891 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.38891 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.38891 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.38891 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 1.38891 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 1.00000 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.39284 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.39284 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.39284 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.39284 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.39284 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 1.39284 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 1.00000 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.56787 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.56787 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.56787 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.56787 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.56787 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.56787 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.81486 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.44179 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.43577 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.43893 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.43562 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 2.63126 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 1.39386 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 1.38891 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 1.39284 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.56787 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.81486 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.81486 |
104 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 3012.02925 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.81486 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.81486 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.81486 |
108 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.85781 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.81486 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.40743 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.87657 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 64960.70000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 32480.35000 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72472 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72472 |
116 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 64960.70000 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 69907.25751 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
120 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 69907.25751 |
121 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.44179 |
122 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
123 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.44179 |
124 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1542.78275 |
125 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.44179 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.44179 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.44179 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.95158 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.44179 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.72089 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.96119 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 33185.01000 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 16592.50500 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72542 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72542 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 33185.01000 |
137 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 35719.39354 |
138 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
139 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
140 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 35719.39354 |
141 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.43577 |
142 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
143 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.43577 |
144 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1536.34297 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.43577 |
146 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.43577 |
147 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.43577 |
148 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.94761 |
149 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.43577 |
150 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.71789 |
151 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.95718 |
152 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 33074.15000 |
153 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 16537.07500 |
154 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72520 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72520 |
156 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 33074.15000 |
157 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 35585.31524 |
158 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
159 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
160 | Coil:Heating:Fuel | PSZ-AC_3:3 HEATING COIL | Design Size Nominal Capacity [W] | 35585.31524 |
161 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.43893 |
162 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
163 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.43893 |
164 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1539.72212 |
165 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.43893 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.43893 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.43893 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.94969 |
169 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.43893 |
170 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.71946 |
171 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.95929 |
172 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 33132.96000 |
173 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 16566.48000 |
174 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72531 |
175 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72531 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 33132.96000 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 35655.68143 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
179 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
180 | Coil:Heating:Fuel | PSZ-AC_4:4 HEATING COIL | Design Size Nominal Capacity [W] | 35655.68143 |
181 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.43562 |
182 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
183 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.43562 |
184 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1536.18002 |
185 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.43562 |
186 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.43562 |
187 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.43562 |
188 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.94751 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.43562 |
190 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.71781 |
191 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.95708 |
192 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 33071.71000 |
193 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 16535.85500 |
194 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72519 |
195 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72519 |
196 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 33071.71000 |
197 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 35581.92161 |
198 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
200 | Coil:Heating:Fuel | PSZ-AC_5:5 HEATING COIL | Design Size Nominal Capacity [W] | 35581.92161 |
201 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.63126 |
202 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
203 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.63126 |
204 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2815.56734 |
205 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.63126 |
206 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.63126 |
207 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.63126 |
208 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.73663 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.63126 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.31563 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.75417 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 61513.13000 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 30756.56500 |
214 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72033 |
215 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72033 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 61513.13000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 65816.24671 |
218 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
219 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
220 | Coil:Heating:Fuel | PSZ-AC_6:6 HEATING COIL | Design Size Nominal Capacity [W] | 65816.24671 |
221 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.39386 |
222 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
223 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.39386 |
224 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1543.22205 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.39386 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.39386 |
227 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.39386 |
228 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.91995 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.39386 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.69693 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.92924 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 32298.85000 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 16149.42500 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72264 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72264 |
236 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 32298.85000 |
237 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 34651.41575 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
240 | Coil:Heating:Fuel | PSZ-AC_7:7 HEATING COIL | Design Size Nominal Capacity [W] | 34651.41575 |
241 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.38891 |
242 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
243 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.38891 |
244 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1537.74656 |
245 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.38891 |
246 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.38891 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.38891 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.91668 |
249 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.38891 |
250 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.69446 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.92594 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 32207.07000 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 16103.53500 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72246 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72246 |
256 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 32207.07000 |
257 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 34541.21905 |
258 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
259 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
260 | Coil:Heating:Fuel | PSZ-AC_8:8 HEATING COIL | Design Size Nominal Capacity [W] | 34541.21905 |
261 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.39284 |
262 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
263 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.39284 |
264 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1542.10039 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.39284 |
266 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.39284 |
267 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.39284 |
268 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.91928 |
269 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.39284 |
270 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.69642 |
271 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.92856 |
272 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 32280.50000 |
273 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 16140.25000 |
274 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72260 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72260 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 32280.50000 |
277 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 34628.84138 |
278 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
279 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
280 | Coil:Heating:Fuel | PSZ-AC_9:9 HEATING COIL | Design Size Nominal Capacity [W] | 34628.84138 |
281 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.56787 |
282 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
283 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.56787 |
284 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1677.69152 |
285 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.56787 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.56787 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.56787 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.03479 |
289 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.56787 |
290 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.78393 |
291 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.04525 |
292 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 35327.26000 |
293 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 17663.63000 |
294 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73210 |
295 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73210 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 35327.26000 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 38528.73172 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
299 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
300 | Coil:Heating:Fuel | PSZ-AC_10:10 HEATING COIL | Design Size Nominal Capacity [W] | 38528.73172 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 62743.1 | 11.64 | 11.64 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 32049.2 | 11.81 | 11.81 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | 31943.1 | 11.81 | 11.81 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | 31999.4 | 11.81 | 11.81 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | 31940.8 | 11.81 | 11.81 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | 59439.7 | 11.66 | 11.66 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | 31200.7 | 11.82 | 11.82 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | 31112.8 | 11.82 | 11.82 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | 31183.1 | 11.82 | 11.82 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | 34092.6 | 11.77 | 11.77 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 58.18 | 78.94 | 58.18 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.199 | 0.190 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 29.09 | 39.47 | 29.09 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 58.22 | 78.94 | 58.22 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.289 | 0.270 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 6.5102488819E-002 | 0.1968380670 | Pass | Pass | 0.1447500438 | 0.7110390299 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 7.9233819906E-002 | 0.1802271762 | Pass | Pass | 0.1216474601 | 0.4138617388 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 5.5082555776E-002 | 0.2040265202 | Pass | Pass | 0.9596834858 | 10.0276112815 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 5.0331861558E-002 | 0.2288396586 | Pass | Pass | 0.1744071574 | 0.7178191250 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 4.5705784736E-002 | 0.2269624341 | Pass | Pass | 0.2757604703 | 1.1992652480 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 4.6572862584E-002 | 0.2256407844 | Pass | Pass | 0.2002889282 | 0.7763258021 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 4.5442417844E-002 | 0.2235271083 | Pass | Pass | 0.4115728821 | 2.5313248319 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 4.4864231542E-002 | 0.2234228291 | Pass | Pass | 0.2750309281 | 0.8374086054 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 4.3246941804E-002 | 0.2227595619 | Pass | Pass | 0.6867095895 | 4.0603192945 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 5.3326231532E-002 | 0.2454256714 | Pass | Pass | 0.2554558253 | 0.7710262750 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:11
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2615.21 | -285.4 | 0.00 | -604.1 | 2402.51 | 4128.20 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:11
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30 | 0.00 | 6.30 | Wetbulb [C] | 0.50 | 270.00 |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00 | 9.70 | 22.20 | Wetbulb [C] | 3.20 | 320.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.60 | 4 | |||
Feb | 21.40 | 43 | |||
Mar | 12.00 | 35 | |||
Apr | 29.10 | 12 | |||
May | 29.10 | 57 | |||
Jun | 197.10 | 59 | |||
Jul | 47.90 | 83 | |||
Aug | 0.00 | 0 | |||
Sep | 171.60 | 106 | |||
Oct | 4.80 | 31 | |||
Nov | 1.20 | 7 | |||
Dec | 33.00 | 13 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:11
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 78.94 | 58.18 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.193 | 0.199 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 29.09 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 78.94 | 58.22 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.276 | 0.289 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.861 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.861 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.861 | 0.251 | 0.251 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 124.40 | 2.861 | 0.251 | 0.251 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 124.40 | 2.861 | 0.251 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:11
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:11
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 13.1942 | 348.39 | 4596.69 | LightsWired | LTG_SCH_BASE_LPD1 | 84.21 | 168.00 | 84.19 | 0.0000 | Y | 72.65 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 4.6828 | 348.39 | 1631.41 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 168.00 | 97.48 | 0.0000 | Y | 29.85 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 13.3632 | 174.19 | 2327.78 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 85.70 | 168.00 | 85.69 | 0.0000 | Y | 37.44 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 5.9749 | 174.19 | 1040.80 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 168.00 | 97.48 | 0.0000 | Y | 19.04 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 13.3365 | 174.19 | 2323.12 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 29.75 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 4.0374 | 174.19 | 703.30 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 10.29 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 13.3365 | 174.19 | 2323.12 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 29.75 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 4.0374 | 174.19 | 703.30 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 10.29 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 13.3365 | 174.19 | 2323.12 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 29.75 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 4.0374 | 174.19 | 703.30 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 10.29 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 13.1675 | 348.39 | 4587.38 | LightsWired | LTG_SCH_BASE_LPD2 | 62.11 | 168.00 | 61.60 | 0.0000 | Y | 53.05 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 13.3365 | 174.19 | 2323.12 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 27.34 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 13.3365 | 174.19 | 2323.12 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 27.34 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 13.3365 | 174.19 | 2323.12 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 27.34 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 13.3365 | 174.19 | 2323.12 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 27.34 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 7.7873 | 4180.64 | 32555.80 | 441.52 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 345.19 | AstronomicalClock | - | 41.75 | 41.75 | 2.71 | |
EXTERIOR_LIGHTS_B | 7274.32 | AstronomicalClock | - | 83.75 | 71.15 | 97.16 | |
Exterior Lighting Total | 7619.51 | 99.87 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:11
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 64960.70 | 47078.32 | 17882.38 | 0.72 | 3.73 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 33185.01 | 24073.07 | 9111.94 | 0.73 | 3.80 | |||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 33074.15 | 23985.37 | 9088.78 | 0.73 | 3.80 | |||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 33132.96 | 24031.67 | 9101.29 | 0.73 | 3.80 | |||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 33071.71 | 23983.27 | 9088.44 | 0.73 | 3.80 | |||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 61513.13 | 44309.75 | 17203.38 | 0.72 | 3.73 | |||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 32298.85 | 23340.44 | 8958.41 | 0.72 | 3.80 | |||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 32207.07 | 23268.32 | 8938.75 | 0.72 | 3.80 | |||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 32280.50 | 23325.89 | 8954.61 | 0.72 | 3.80 | |||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 35327.26 | 25863.09 | 9464.17 | 0.73 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 62743.1 | 11.64 | 11.64 | ||||
PSZ-AC_2:2 COOLING COIL | 32049.2 | 11.81 | 11.81 | ||||
PSZ-AC_3:3 COOLING COIL | 31943.1 | 11.81 | 11.81 | ||||
PSZ-AC_4:4 COOLING COIL | 31999.4 | 11.81 | 11.81 | ||||
PSZ-AC_5:5 COOLING COIL | 31940.8 | 11.81 | 11.81 | ||||
PSZ-AC_6:6 COOLING COIL | 59439.7 | 11.66 | 11.66 | ||||
PSZ-AC_7:7 COOLING COIL | 31200.7 | 11.82 | 11.82 | ||||
PSZ-AC_8:8 COOLING COIL | 31112.8 | 11.82 | 11.82 | ||||
PSZ-AC_9:9 COOLING COIL | 31183.1 | 11.82 | 11.82 | ||||
PSZ-AC_10:10 COOLING COIL | 34092.6 | 11.77 | 11.77 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 69907.26 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 35719.39 | 0.80 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | 35585.32 | 0.80 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | 35655.68 | 0.80 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | 35581.92 | 0.80 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | 65816.25 | 0.80 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | 34651.42 | 0.80 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | 34541.22 | 0.80 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | 34628.84 | 0.80 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | 38528.73 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.81 | 3012.03 | 1070.05 | 1.00 | 1.27 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.44 | 1542.78 | 1070.05 | 1.00 | 1.37 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.44 | 1536.34 | 1070.05 | 1.00 | 1.37 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.44 | 1539.72 | 1070.05 | 1.00 | 1.37 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.44 | 1536.18 | 1070.05 | 1.00 | 1.37 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.63 | 2815.57 | 1070.05 | 1.00 | 1.28 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.39 | 1543.22 | 1107.16 | 1.00 | 1.33 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.39 | 1537.75 | 1107.16 | 1.00 | 1.33 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.39 | 1542.10 | 1107.16 | 1.00 | 1.33 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.57 | 1677.69 | 1070.05 | 1.00 | 1.35 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:11
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 31070.24 | 37284.28 | 107.02 | 2.346 | 2.815 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:50:00 | 23.89 | 23.89 | 0.00765 | 42.00 | 0.00916 | 0.411 | 0.00 |
SMSTORE1 | 15914.42 | 19097.30 | 109.63 | 1.201 | 1.442 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 23.89 | 23.89 | 0.00766 | 42.00 | 0.00916 | 0.206 | 0.00 |
SMSTORE2 | 15848.00 | 19017.59 | 109.18 | 1.196 | 1.436 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 23.89 | 23.89 | 0.00766 | 41.92 | 0.00916 | 0.206 | 0.00 |
SMSTORE3 | 15882.85 | 19059.42 | 109.42 | 1.199 | 1.439 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 23.89 | 23.89 | 0.00766 | 41.92 | 0.00916 | 0.206 | 0.00 |
SMSTORE4 | 15846.32 | 19015.58 | 109.16 | 1.196 | 1.436 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 23.89 | 23.89 | 0.00766 | 41.92 | 0.00916 | 0.206 | 0.00 |
LGSTORE2 | 29043.78 | 34852.54 | 100.04 | 2.193 | 2.631 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 | 23.89 | 23.89 | 0.00768 | 41.84 | 0.00916 | 0.411 | 0.00 |
SMSTORE5 | 15385.38 | 18462.45 | 105.99 | 1.162 | 1.394 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 | 23.89 | 23.89 | 0.00768 | 41.84 | 0.00916 | 0.206 | 0.00 |
SMSTORE6 | 15330.79 | 18396.95 | 105.61 | 1.157 | 1.389 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 | 23.89 | 23.89 | 0.00768 | 41.84 | 0.00916 | 0.206 | 0.00 |
SMSTORE7 | 15374.20 | 18449.04 | 105.91 | 1.161 | 1.393 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 | 23.89 | 23.89 | 0.00768 | 41.84 | 0.00916 | 0.206 | 0.00 |
SMSTORE8 | 17306.57 | 20767.89 | 119.22 | 1.307 | 1.568 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:00:00 | 23.89 | 23.89 | 0.00762 | 41.52 | 0.00916 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 14378.72 | 17254.46 | 49.53 | 0.636 | 0.763 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00734 | 6.30 | 0.00607 | 0.411 | 0.00 |
SMSTORE1 | 7228.85 | 8674.62 | 49.80 | 0.320 | 0.384 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00728 | 6.30 | 0.00607 | 0.206 | 0.00 |
SMSTORE2 | 7312.05 | 8774.46 | 50.37 | 0.323 | 0.388 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00728 | 6.30 | 0.00607 | 0.206 | 0.00 |
SMSTORE3 | 7380.88 | 8857.06 | 50.85 | 0.326 | 0.392 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00728 | 6.30 | 0.00607 | 0.206 | 0.00 |
SMSTORE4 | 7523.09 | 9027.71 | 51.83 | 0.333 | 0.399 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00729 | 6.30 | 0.00607 | 0.206 | 0.00 |
LGSTORE2 | 14211.73 | 17054.08 | 48.95 | 0.629 | 0.754 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00734 | 6.30 | 0.00607 | 0.411 | 0.00 |
SMSTORE5 | 7714.47 | 9257.37 | 53.14 | 0.341 | 0.409 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00730 | 6.30 | 0.00607 | 0.206 | 0.00 |
SMSTORE6 | 7714.94 | 9257.93 | 53.15 | 0.341 | 0.409 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00730 | 6.30 | 0.00607 | 0.206 | 0.00 |
SMSTORE7 | 7929.66 | 9515.59 | 54.63 | 0.351 | 0.421 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00731 | 6.30 | 0.00607 | 0.206 | 0.00 |
SMSTORE8 | 9096.76 | 10916.12 | 62.67 | 0.402 | 0.483 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00735 | 6.30 | 0.00607 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.81 | 2.81 | 0.76 | 0.76 | 2.8149 | 2.8149 | 2.8149 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.44 | 1.44 | 0.38 | 0.38 | 1.4418 | 1.4418 | 1.4418 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 1.44 | 1.44 | 0.39 | 0.39 | 1.4358 | 1.4358 | 1.4358 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 1.44 | 1.44 | 0.39 | 0.39 | 1.4389 | 1.4389 | 1.4389 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.44 | 1.44 | 0.40 | 0.40 | 1.4356 | 1.4356 | 1.4356 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 2.63 | 2.63 | 0.75 | 0.75 | 2.6313 | 2.6313 | 2.6313 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 1.39 | 1.39 | 0.41 | 0.41 | 1.3939 | 1.3939 | 1.3939 | 1.0000 | 1.0000 |
PSZ-AC_8:8 | 1.39 | 1.39 | 0.41 | 0.41 | 1.3889 | 1.3889 | 1.3889 | 1.0000 | 1.0000 |
PSZ-AC_9:9 | 1.39 | 1.39 | 0.42 | 0.42 | 1.3928 | 1.3928 | 1.3928 | 1.0000 | 1.0000 |
PSZ-AC_10:10 | 1.57 | 1.57 | 0.48 | 0.48 | 1.5679 | 1.5679 | 1.5679 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 64960.700 | 47078.319 | 2.814860 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:50:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:50:00 | 32480.35 | 29147.95 | 1.876573 | 27.43 | 16.79 | 0.00786974 | 12.80 | 10.34 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 21.9271 | 23.89 | 0.00764919 | 40.4666 | 31070.24 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 69907.258 | 69907.258 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 69907.26 | 69907.26 | 2.814856 | 18.94 | 13.03 | 0.00715483 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 14.6181 | 21.11 | 0.00734016 | 45.9956 | 14378.72 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 33185.010 | 24073.070 | 1.441790 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 16592.51 | 14883.40 | 0.961193 | 27.37 | 16.77 | 0.00787074 | 12.80 | 10.34 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 21.4046 | 23.89 | 0.00765649 | 40.5047 | 15914.42 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 35719.394 | 35719.394 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 35719.39 | 35719.39 | 1.441789 | 19.00 | 13.00 | 0.00710553 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 14.2697 | 21.11 | 0.00727750 | 45.6079 | 7228.85 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 33074.150 | 23985.374 | 1.435770 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 16537.08 | 14829.30 | 0.957180 | 27.38 | 16.77 | 0.00787373 | 12.80 | 10.34 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 21.4943 | 23.89 | 0.00765892 | 40.5174 | 15846.86 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 35585.315 | 35585.315 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 35585.32 | 35585.32 | 1.435771 | 18.99 | 13.00 | 0.00710732 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 14.3295 | 21.11 | 0.00728043 | 45.6261 | 7312.05 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 33132.960 | 24031.667 | 1.438930 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 16566.48 | 14857.84 | 0.959287 | 27.37 | 16.77 | 0.00787224 | 12.80 | 10.34 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 21.4471 | 23.89 | 0.00765772 | 40.5111 | 15881.07 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 35655.681 | 35655.681 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 35655.68 | 35655.68 | 1.438929 | 18.99 | 13.00 | 0.00711065 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 14.2981 | 21.11 | 0.00728387 | 45.6474 | 7380.88 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 33071.710 | 23983.273 | 1.435620 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 16535.85 | 14828.03 | 0.957080 | 27.38 | 16.77 | 0.00787385 | 12.80 | 10.34 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 21.4966 | 23.89 | 0.00765902 | 40.5179 | 15844.37 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 35581.922 | 35581.922 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 35581.92 | 35581.92 | 1.435619 | 18.99 | 13.01 | 0.00711656 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 14.3311 | 21.11 | 0.00729124 | 45.6931 | 7523.09 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 61513.130 | 44309.753 | 2.631260 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 30756.56 | 27492.95 | 1.754173 | 27.61 | 16.89 | 0.00791172 | 12.80 | 10.34 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 23.4571 | 23.89 | 0.00768064 | 40.6308 | 29036.15 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 65816.247 | 65816.247 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 65816.25 | 65816.25 | 2.631255 | 18.79 | 12.95 | 0.00714073 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 15.6381 | 21.11 | 0.00733878 | 45.9870 | 14211.73 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 32298.850 | 23340.441 | 1.393860 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 | 16149.42 | 14454.46 | 0.929240 | 27.49 | 16.83 | 0.00789473 | 12.80 | 10.34 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 22.1406 | 23.89 | 0.00767590 | 40.6061 | 15379.56 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 34651.416 | 34651.416 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 34651.42 | 34651.42 | 1.393858 | 18.92 | 12.98 | 0.00711887 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 14.7604 | 21.11 | 0.00730009 | 45.7479 | 7714.47 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 32207.070 | 23268.320 | 1.388910 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 | 16103.53 | 14409.87 | 0.925940 | 27.50 | 16.83 | 0.00789725 | 12.80 | 10.34 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 22.2195 | 23.89 | 0.00767794 | 40.6168 | 15324.84 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 34541.219 | 34541.219 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 34541.22 | 34541.22 | 1.388912 | 18.92 | 12.98 | 0.00711829 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 14.8130 | 21.11 | 0.00730016 | 45.7484 | 7714.94 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 32280.500 | 23325.889 | 1.392840 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 | 16140.25 | 14445.45 | 0.928560 | 27.49 | 16.83 | 0.00789530 | 12.80 | 10.34 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 22.1568 | 23.89 | 0.00767636 | 40.6085 | 15367.37 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 34628.841 | 34628.841 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 34628.84 | 34628.84 | 1.392845 | 18.92 | 12.99 | 0.00712746 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 14.7712 | 21.11 | 0.00731032 | 45.8113 | 7929.66 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 35327.260 | 25863.087 | 1.567870 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:00:00 | 17663.63 | 15908.98 | 1.045247 | 27.12 | 16.64 | 0.00782557 | 12.80 | 10.34 | 0.00700000 | 41.68 | 0.00915736 | 22.17 | 19.6833 | 23.89 | 0.00762416 | 40.3359 | 17286.98 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 38528.732 | 38528.732 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 38528.73 | 38528.73 | 1.567867 | 19.17 | 13.14 | 0.00718424 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 13.1223 | 21.11 | 0.00735218 | 46.0709 | 9096.76 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:41:11
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 64960.700 | 47078.319 | 2.814860 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.4695 | 1004.8586 | 1.1738 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.814856 | 3.30403734 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:50:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:50:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:50:00 | Sensible | 32480.35 | 29147.95 | 1.0000 | 2.20269449 | 1.876573 | 27.43 | 16.79 | 0.00786974 | 47644.4 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32480.35 | 42.00 | 0.00915790 | 22.26 | 0.41147883 | 21.9271 | 23.89 | 0.00764919 | 23.89 | 0.00764919 | 40.4666 | 31070.24 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 69907.258 | 69907.258 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.814856 | 3.30403734 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 69907.26 | 69907.26 | 1.0000 | 3.30403734 | 2.814856 | 18.94 | 13.03 | 0.00715483 | 37181.6 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 69907.26 | 6.30 | 0.00607234 | 6.30 | 0.41147883 | 14.6181 | 21.11 | 0.00734016 | 21.11 | 0.00734016 | 45.9956 | 14378.72 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 33185.010 | 24073.070 | 1.441790 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.4713 | 1004.8586 | 1.1738 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.441789 | 1.69235137 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | Sensible | 16592.51 | 14883.40 | 1.0000 | 1.12823476 | 0.961193 | 27.37 | 16.77 | 0.00787074 | 47582.6 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16592.51 | 42.00 | 0.00915790 | 22.26 | 0.20573941 | 21.4046 | 23.89 | 0.00765649 | 23.89 | 0.00765649 | 40.5047 | 15914.42 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 35719.394 | 35719.394 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.441789 | 1.69235137 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 35719.39 | 35719.39 | 1.0000 | 1.69235137 | 1.441789 | 19.00 | 13.00 | 0.00710553 | 37109.0 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 35719.39 | 6.30 | 0.00607234 | 6.30 | 0.20573941 | 14.2697 | 21.11 | 0.00727750 | 21.11 | 0.00727750 | 45.6079 | 7228.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 33074.150 | 23985.374 | 1.435770 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.4769 | 1004.8586 | 1.1738 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.435771 | 1.68528726 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | Sensible | 16537.08 | 14829.30 | 1.0000 | 1.12352397 | 0.957180 | 27.38 | 16.77 | 0.00787373 | 47601.5 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16537.08 | 42.00 | 0.00915790 | 22.26 | 0.20573941 | 21.4943 | 23.89 | 0.00765892 | 23.89 | 0.00765892 | 40.5174 | 15846.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 35585.315 | 35585.315 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.435771 | 1.68528726 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 35585.32 | 35585.32 | 1.0000 | 1.68528726 | 1.435771 | 18.99 | 13.00 | 0.00710732 | 37104.5 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 35585.32 | 6.30 | 0.00607234 | 6.30 | 0.20573941 | 14.3295 | 21.11 | 0.00728043 | 21.11 | 0.00728043 | 45.6261 | 7312.05 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 33132.960 | 24031.667 | 1.438930 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.4741 | 1004.8586 | 1.1738 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.438929 | 1.68899402 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | Sensible | 16566.48 | 14857.84 | 1.0000 | 1.12599674 | 0.959287 | 27.37 | 16.77 | 0.00787224 | 47592.0 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16566.48 | 42.00 | 0.00915790 | 22.26 | 0.20573941 | 21.4471 | 23.89 | 0.00765772 | 23.89 | 0.00765772 | 40.5111 | 15881.07 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 35655.681 | 35655.681 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.438929 | 1.68899402 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 35655.68 | 35655.68 | 1.0000 | 1.68899402 | 1.438929 | 18.99 | 13.00 | 0.00711065 | 37117.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 35655.68 | 6.30 | 0.00607234 | 6.30 | 0.20573941 | 14.2981 | 21.11 | 0.00728387 | 21.11 | 0.00728387 | 45.6474 | 7380.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 33071.710 | 23983.273 | 1.435620 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.4771 | 1004.8586 | 1.1738 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.435619 | 1.68510852 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | Sensible | 16535.85 | 14828.03 | 1.0000 | 1.12340659 | 0.957080 | 27.38 | 16.77 | 0.00787385 | 47602.2 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16535.85 | 42.00 | 0.00915790 | 22.26 | 0.20573941 | 21.4966 | 23.89 | 0.00765902 | 23.89 | 0.00765902 | 40.5179 | 15844.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 35581.922 | 35581.922 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.435619 | 1.68510852 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 35581.92 | 35581.92 | 1.0000 | 1.68510852 | 1.435619 | 18.99 | 13.01 | 0.00711656 | 37127.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 35581.92 | 6.30 | 0.00607234 | 6.30 | 0.20573941 | 14.3311 | 21.11 | 0.00729124 | 21.11 | 0.00729124 | 45.6931 | 7523.09 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 61513.130 | 44309.753 | 2.631260 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.5475 | 1004.8586 | 1.1738 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.631255 | 3.08852898 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | Sensible | 30756.56 | 27492.95 | 1.0000 | 2.05902315 | 1.754173 | 27.61 | 16.89 | 0.00791172 | 47940.6 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30756.56 | 42.00 | 0.00915790 | 22.26 | 0.41147883 | 23.4571 | 23.89 | 0.00768064 | 23.89 | 0.00768064 | 40.6308 | 29036.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 65816.247 | 65816.247 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.631255 | 3.08852898 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 65816.25 | 65816.25 | 1.0000 | 3.08852898 | 2.631255 | 18.79 | 12.95 | 0.00714073 | 36992.1 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 65816.25 | 6.30 | 0.00607234 | 6.30 | 0.41147883 | 15.6381 | 21.11 | 0.00733878 | 21.11 | 0.00733878 | 45.9870 | 14211.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 32298.850 | 23340.441 | 1.393860 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.5159 | 1004.8586 | 1.1738 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.393858 | 1.63609025 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 | Sensible | 16149.42 | 14454.46 | 1.0000 | 1.09072840 | 0.929240 | 27.49 | 16.83 | 0.00789473 | 47767.0 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16149.42 | 42.00 | 0.00915790 | 22.26 | 0.20573941 | 22.1406 | 23.89 | 0.00767590 | 23.89 | 0.00767590 | 40.6061 | 15379.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 34651.416 | 34651.416 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.393858 | 1.63609025 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 34651.42 | 34651.42 | 1.0000 | 1.63609025 | 1.393858 | 18.92 | 12.98 | 0.00711887 | 37068.9 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34651.42 | 6.30 | 0.00607234 | 6.30 | 0.20573941 | 14.7604 | 21.11 | 0.00730009 | 21.11 | 0.00730009 | 45.7479 | 7714.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 32207.070 | 23268.320 | 1.388910 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.5206 | 1004.8586 | 1.1738 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.388912 | 1.63028524 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 | Sensible | 16103.53 | 14409.87 | 1.0000 | 1.08685491 | 0.925940 | 27.50 | 16.83 | 0.00789725 | 47783.2 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16103.53 | 42.00 | 0.00915790 | 22.26 | 0.20573941 | 22.2195 | 23.89 | 0.00767794 | 23.89 | 0.00767794 | 40.6168 | 15324.84 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 34541.219 | 34541.219 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.388912 | 1.63028524 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 34541.22 | 34541.22 | 1.0000 | 1.63028524 | 1.388912 | 18.92 | 12.98 | 0.00711829 | 37059.5 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34541.22 | 6.30 | 0.00607234 | 6.30 | 0.20573941 | 14.8130 | 21.11 | 0.00730016 | 21.11 | 0.00730016 | 45.7484 | 7714.94 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 32280.500 | 23325.889 | 1.392840 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.5170 | 1004.8586 | 1.1738 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.392845 | 1.63490108 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 | Sensible | 16140.25 | 14445.45 | 1.0000 | 1.08993023 | 0.928560 | 27.49 | 16.83 | 0.00789530 | 47770.7 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16140.25 | 42.00 | 0.00915790 | 22.26 | 0.20573941 | 22.1568 | 23.89 | 0.00767636 | 23.89 | 0.00767636 | 40.6085 | 15367.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 34628.841 | 34628.841 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.392845 | 1.63490108 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 34628.84 | 34628.84 | 1.0000 | 1.63490108 | 1.392845 | 18.92 | 12.99 | 0.00712746 | 37089.0 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34628.84 | 6.30 | 0.00607234 | 6.30 | 0.20573941 | 14.7712 | 21.11 | 0.00731032 | 21.11 | 0.00731032 | 45.8113 | 7929.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 35327.260 | 25863.087 | 1.567870 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.3873 | 1004.8586 | 1.1738 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.567867 | 1.84033917 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:00:00 | Sensible | 17663.63 | 15908.98 | 1.0000 | 1.22689534 | 1.045247 | 27.12 | 16.64 | 0.00782557 | 47215.0 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17663.63 | 41.68 | 0.00915736 | 22.17 | 0.20573941 | 19.6833 | 23.89 | 0.00762416 | 23.89 | 0.00762416 | 40.3359 | 17286.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 38528.732 | 38528.732 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.567867 | 1.84033917 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 38528.73 | 38528.73 | 1.0000 | 1.84033917 | 1.567867 | 19.17 | 13.14 | 0.00718424 | 37481.6 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 38528.73 | 6.30 | 0.00607234 | 6.30 | 0.20573941 | 13.1223 | 21.11 | 0.00735218 | 21.11 | 0.00735218 | 46.0709 | 9096.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:11
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 4310.83 | 1798.00 | 1217.00 |
SMSTORE1 | 4143.67 | 1382.83 | 949.00 |
SMSTORE2 | 3197.33 | 1460.00 | 1043.17 |
SMSTORE3 | 3174.83 | 1488.67 | 1035.67 |
SMSTORE4 | 3145.50 | 1548.33 | 1043.50 |
LGSTORE2 | 2864.83 | 1445.00 | 953.50 |
SMSTORE5 | 2779.33 | 1467.33 | 950.83 |
SMSTORE6 | 2766.83 | 1484.67 | 953.50 |
SMSTORE7 | 2749.50 | 1517.67 | 951.17 |
SMSTORE8 | 2794.00 | 1486.83 | 880.67 |
Facility | 4440.67 | 2335.67 | 1420.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 0.00 | 1.67 | 0.00 | 1.67 |
SMSTORE1 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 0.00 | 5.50 | 0.00 | 5.50 |
SMSTORE3 | 0.00 | 5.83 | 0.00 | 5.83 |
SMSTORE4 | 0.00 | 6.00 | 0.00 | 6.00 |
LGSTORE2 | 0.00 | 6.00 | 0.00 | 6.00 |
SMSTORE5 | 0.00 | 4.67 | 0.00 | 4.67 |
SMSTORE6 | 0.00 | 4.50 | 0.00 | 4.50 |
SMSTORE7 | 0.00 | 4.50 | 0.00 | 4.50 |
SMSTORE8 | 0.00 | 3.50 | 0.00 | 3.50 |
Facility | 0.00 | 12.83 | 0.00 | 12.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:11
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 0.848 | 0.333 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.684 | 0.375 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 0.848 | 0.494 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 0.848 | 0.494 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 0.848 | 0.494 | 0.000 | 0.000 |
LGSTORE2 | 24.77 | 56.25 | 1805.20 | 0.848 | 0.462 | 0.000 | 0.000 |
SMSTORE5 | 12.39 | 28.12 | 902.60 | 0.848 | 0.527 | 0.000 | 0.000 |
SMSTORE6 | 12.39 | 28.12 | 902.60 | 0.848 | 0.527 | 0.000 | 0.000 |
SMSTORE7 | 12.39 | 28.12 | 902.60 | 0.848 | 0.527 | 0.000 | 0.000 |
SMSTORE8 | 12.39 | 28.12 | 902.60 | 0.848 | 0.536 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 0.779 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 0.778 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 0.778 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 0.777 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.77 | 56.25 | 1805.20 | 0.779 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.39 | 28.12 | 902.60 | 0.779 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.39 | 28.12 | 902.60 | 0.778 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.39 | 28.12 | 902.60 | 0.778 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.39 | 28.12 | 902.60 | 0.777 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:41:11
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 16.93 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE1 | PSZ-AC_2:2 | 8.46 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE2 | PSZ-AC_3:3 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE3 | PSZ-AC_4:4 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE4 | PSZ-AC_5:5 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
LGSTORE2 | PSZ-AC_6:6 | 24.77 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE5 | PSZ-AC_7:7 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE6 | PSZ-AC_8:8 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE7 | PSZ-AC_9:9 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE8 | PSZ-AC_10:10 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
Total Facility | 120.95 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 2.469 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 8803562.65 | 0.00 | 8803562.65 | 3505960.47 | 12309523.12 | 12976396.34 | 2817.00 | 5943.00 | 0.00 | 103.00 |
SMSTORE1 | 3565881.24 | 0.00 | 3565881.24 | 1952020.86 | 5517902.10 | 6488198.17 | 4303.00 | 4457.00 | 0.00 | 103.00 |
SMSTORE2 | 3525574.68 | 0.00 | 3525574.68 | 1960785.24 | 5486359.92 | 6488198.17 | 4000.00 | 4760.00 | 0.00 | 365.00 |
SMSTORE3 | 3525574.80 | 0.00 | 3525574.80 | 1960785.24 | 5486360.04 | 6488198.17 | 4000.00 | 4760.00 | 0.00 | 365.00 |
SMSTORE4 | 3525576.24 | 0.00 | 3525576.24 | 1960785.24 | 5486361.48 | 6488198.17 | 4000.00 | 4760.00 | 0.00 | 365.00 |
LGSTORE2 | 6510476.25 | 0.00 | 6510476.25 | 3452391.79 | 9962868.04 | 12976396.34 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE5 | 3255231.31 | 0.00 | 3255231.31 | 1964207.59 | 5219438.90 | 6488198.17 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE6 | 3255231.88 | 0.00 | 3255231.88 | 1964207.59 | 5219439.47 | 6488198.17 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE7 | 3255232.51 | 0.00 | 3255232.51 | 1964207.59 | 5219440.10 | 6488198.17 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE8 | 3255281.89 | 0.00 | 3255281.89 | 2060429.81 | 5315711.69 | 6488198.17 | 4365.00 | 4395.00 | 0.00 | 365.83 |
Total Facility | 42477623.45 | 0.00 | 42477623.45 | 22745781.39 | 65223404.84 | 77858378.04 | 4365.00 | 6246.00 | 0.00 | 730.83 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.4115 | 0.0000 | 0.4115 | 0.1614 | 0.5729 | 0.4115 | 0.00 | 5840.00 | 0.00 |
SMSTORE1 | 0.1660 | 0.0000 | 0.1660 | 0.0910 | 0.2570 | 0.2057 | 1486.00 | 4354.00 | 0.00 |
SMSTORE2 | 0.2057 | 0.0000 | 0.2057 | 0.1198 | 0.3256 | 0.2057 | 0.00 | 4395.00 | 0.00 |
SMSTORE3 | 0.2057 | 0.0000 | 0.2057 | 0.1198 | 0.3256 | 0.2057 | 0.00 | 4395.00 | 0.00 |
SMSTORE4 | 0.2057 | 0.0000 | 0.2057 | 0.1198 | 0.3256 | 0.2057 | 0.00 | 4395.00 | 0.00 |
LGSTORE2 | 0.4115 | 0.0000 | 0.4115 | 0.2239 | 0.6354 | 0.4115 | 0.00 | 4030.00 | 0.00 |
SMSTORE5 | 0.2057 | 0.0000 | 0.2057 | 0.1278 | 0.3335 | 0.2057 | 0.00 | 4030.00 | 0.00 |
SMSTORE6 | 0.2057 | 0.0000 | 0.2057 | 0.1278 | 0.3335 | 0.2057 | 0.00 | 4030.00 | 0.00 |
SMSTORE7 | 0.2057 | 0.0000 | 0.2057 | 0.1278 | 0.3335 | 0.2057 | 0.00 | 4030.00 | 0.00 |
SMSTORE8 | 0.2057 | 0.0000 | 0.2057 | 0.1299 | 0.3356 | 0.2057 | 0.00 | 4030.00 | 0.00 |
Total Facility | 2.4291 | 0.0000 | 2.4291 | 1.3490 | 3.7781 | 2.4689 | 1486.00 | 5943.00 | 0.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 12129228.48 | 0.00 | 12129228.48 | 12976396.34 | 2817.00 | 0.00 | 5943.00 | 103.00 |
PSZ-AC_2:2 | 4912928.82 | 0.00 | 4912928.82 | 6488198.17 | 4303.00 | 0.00 | 4457.00 | 103.00 |
PSZ-AC_3:3 | 4857405.99 | 0.00 | 4857405.99 | 6488198.17 | 4000.00 | 0.00 | 4760.00 | 365.00 |
PSZ-AC_4:4 | 4857405.99 | 0.00 | 4857405.99 | 6488198.17 | 4000.00 | 0.00 | 4760.00 | 365.00 |
PSZ-AC_5:5 | 4857405.99 | 0.00 | 4857405.99 | 6488198.17 | 4000.00 | 0.00 | 4760.00 | 365.00 |
PSZ-AC_6:6 | 8969873.66 | 0.00 | 8969873.66 | 12976396.34 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_7:7 | 4484936.83 | 0.00 | 4484936.83 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_8:8 | 4484936.83 | 0.00 | 4484936.83 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_9:9 | 4484936.83 | 0.00 | 4484936.83 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_10:10 | 4485015.11 | 0.00 | 4485015.11 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 365.83 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.5669 | 0.0000 | 0.5669 | 0.4115 | 0.00 | 0.00 | 5840.00 |
PSZ-AC_2:2 | 0.2287 | 0.0000 | 0.2287 | 0.2057 | 1486.00 | 0.00 | 4354.00 |
PSZ-AC_3:3 | 0.2835 | 0.0000 | 0.2835 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_4:4 | 0.2835 | 0.0000 | 0.2835 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_5:5 | 0.2835 | 0.0000 | 0.2835 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_6:6 | 0.5669 | 0.0000 | 0.5669 | 0.4115 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_7:7 | 0.2835 | 0.0000 | 0.2835 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_8:8 | 0.2835 | 0.0000 | 0.2835 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_9:9 | 0.2835 | 0.0000 | 0.2835 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_10:10 | 0.2835 | 0.0000 | 0.2835 | 0.2057 | 0.00 | 0.00 | 4030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 5943.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 5933.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 4760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 4760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 4760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 4395.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.5669 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.2291 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 0.2835 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 0.2835 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 0.2835 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 0.5671 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.2835 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.2835 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.2835 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.2835 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:11
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 759 |
Defaulted Fields | 823 |
Fields with Defaults | 2681 |
Autosized Fields | 184 |
Autosizable Fields | 458 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:41:11
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1365.96 | 3115.94 | 01-JAN-08:00 | 139593.76 | 22-JUN-16:40 |
Electricity:Building | 570.24 | 1897.94 | 01-JAN-00:10 | 35612.10 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 128.86 | 354.96 | 01-JAN-00:10 | 6669.68 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 570.24 | 1897.94 | 01-JAN-00:10 | 35612.10 | 01-JAN-11:10 |
InteriorLights:Electricity | 441.52 | 1448.52 | 01-JAN-00:10 | 27522.57 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 102.50 | 280.06 | 01-JAN-00:10 | 5321.43 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 441.52 | 1448.52 | 01-JAN-00:10 | 27522.57 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 441.52 | 1448.52 | 01-JAN-00:10 | 27522.57 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 102.50 | 280.06 | 01-JAN-00:10 | 5321.43 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 441.52 | 1448.52 | 01-JAN-00:10 | 27522.57 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 69.66 | 191.80 | 01-JAN-00:10 | 3606.70 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 56.49 | 154.35 | 01-JAN-00:10 | 2932.57 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 56.49 | 154.35 | 01-JAN-00:10 | 2932.57 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 50.51 | 174.25 | 01-JAN-00:10 | 3273.35 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 40.04 | 136.80 | 01-JAN-00:10 | 2599.23 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 40.04 | 136.80 | 01-JAN-00:10 | 2599.23 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 50.51 | 174.25 | 01-JAN-00:10 | 3273.35 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 40.04 | 136.80 | 01-JAN-00:10 | 2599.23 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 40.04 | 136.80 | 01-JAN-00:10 | 2599.23 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 50.51 | 174.25 | 01-JAN-00:10 | 3273.35 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 40.04 | 136.80 | 01-JAN-00:10 | 2599.23 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 40.04 | 136.80 | 01-JAN-00:10 | 2599.23 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 72.31 | 272.07 | 01-JAN-00:10 | 5094.77 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 53.05 | 197.17 | 01-JAN-00:10 | 3746.51 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 53.05 | 197.17 | 01-JAN-00:10 | 3746.51 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 36.97 | 139.09 | 01-JAN-00:10 | 2605.22 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 36.97 | 139.09 | 01-JAN-00:10 | 2605.22 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 36.97 | 139.09 | 01-JAN-00:10 | 2605.22 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 36.97 | 139.09 | 01-JAN-00:10 | 2605.22 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.36 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.36 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.18 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.18 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.26 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.26 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
ElectricityPurchased:Facility | 1365.96 | 3115.94 | 01-JAN-08:00 | 139593.76 | 22-JUN-16:40 |
ElectricityPurchased:Plant | 1365.96 | 3115.94 | 01-JAN-08:00 | 139593.76 | 22-JUN-16:40 |
Cogeneration:ElectricityPurchased | 1365.96 | 3115.94 | 01-JAN-08:00 | 139593.76 | 22-JUN-16:40 |
General:Cogeneration:ElectricityPurchased | 1365.96 | 3115.94 | 01-JAN-08:00 | 139593.76 | 22-JUN-16:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1365.96 | 3115.94 | 01-JAN-08:00 | 139593.76 | 22-JUN-16:40 |
ElectricityNet:Plant | 1365.96 | 3115.94 | 01-JAN-08:00 | 139593.76 | 22-JUN-16:40 |
Cogeneration:ElectricityNet | 1365.96 | 3115.94 | 01-JAN-08:00 | 139593.76 | 22-JUN-16:40 |
General:Cogeneration:ElectricityNet | 1365.96 | 3115.94 | 01-JAN-08:00 | 139593.76 | 22-JUN-16:40 |
Electricity:HVAC | 637.02 | 0.00 | 01-JAN-00:10 | 100135.11 | 22-JUN-16:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 502.75 | 0.00 | 01-JAN-00:10 | 86891.90 | 10-JUN-16:00 |
General:Cooling:Electricity | 502.75 | 0.00 | 01-JAN-00:10 | 86891.90 | 10-JUN-16:00 |
Fans:Electricity | 134.27 | 0.00 | 01-JAN-00:10 | 13662.04 | 01-JUL-15:00 |
General:Fans:Electricity | 134.27 | 0.00 | 01-JAN-00:10 | 13662.04 | 01-JUL-15:00 |
ExteriorLights:Electricity | 99.87 | 0.00 | 01-JAN-07:20 | 7619.51 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 99.87 | 0.00 | 01-JAN-07:20 | 7619.51 | 01-JAN-06:10 |
Electricity:Plant | 58.83 | 1218.00 | 06-JAN-09:10 | 10225.93 | 05-JAN-13:00 |
WaterSystems:Electricity | 58.83 | 1218.00 | 06-JAN-09:10 | 10225.93 | 05-JAN-13:00 |
Water Heater:WaterSystems:Electricity | 58.83 | 1218.00 | 06-JAN-09:10 | 10225.93 | 05-JAN-13:00 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 2.87 | 0.00 | 01-JAN-00:10 | 109100.01 | 02-JAN-09:10 |
NaturalGas:HVAC | 2.87 | 0.00 | 01-JAN-00:10 | 109100.01 | 02-JAN-09:10 |
Heating:NaturalGas | 2.87 | 0.00 | 01-JAN-00:10 | 109100.01 | 02-JAN-09:10 |
General:Heating:NaturalGas | 2.87 | 0.00 | 01-JAN-00:10 | 109100.01 | 02-JAN-09:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2946.71 | 0.00 | 01-JAN-00:10 | 451060.92 | 01-JUL-14:00 |
EnergyTransfer:Building | 1045.22 | 0.00 | 01-JAN-00:10 | 158274.65 | 12-JUN-16:10 |
EnergyTransfer:Zone:LGSTORE1 | 211.63 | 0.00 | 01-JAN-00:10 | 26198.65 | 08-JUN-16:10 |
Heating:EnergyTransfer | 8.82 | 0.00 | 01-JAN-00:10 | 64009.70 | 02-JAN-09:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 0.44 | 0.00 | 01-JAN-00:10 | 11043.25 | 02-JAN-09:10 |
General:Heating:EnergyTransfer | 8.82 | 0.00 | 01-JAN-00:10 | 64009.70 | 02-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 0.44 | 0.00 | 01-JAN-00:10 | 11043.25 | 02-JAN-09:10 |
Cooling:EnergyTransfer | 1036.41 | 0.00 | 01-JAN-00:10 | 158274.65 | 12-JUN-16:10 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 211.19 | 0.00 | 01-JAN-00:10 | 26198.65 | 08-JUN-16:10 |
General:Cooling:EnergyTransfer | 1036.41 | 0.00 | 01-JAN-00:10 | 158274.65 | 12-JUN-16:10 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 211.19 | 0.00 | 01-JAN-00:10 | 26198.65 | 08-JUN-16:10 |
EnergyTransfer:Zone:SMSTORE1 | 109.08 | 0.00 | 01-JAN-00:10 | 12972.92 | 08-JUN-16:10 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 0.19 | 0.00 | 01-JAN-00:10 | 4287.83 | 02-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 0.19 | 0.00 | 01-JAN-00:10 | 4287.83 | 02-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 108.89 | 0.00 | 01-JAN-00:10 | 12972.92 | 08-JUN-16:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 108.89 | 0.00 | 01-JAN-00:10 | 12972.92 | 08-JUN-16:10 |
EnergyTransfer:Zone:SMSTORE2 | 85.13 | 0.00 | 01-JAN-00:10 | 13108.47 | 12-JUN-16:10 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 1.36 | 0.00 | 01-JAN-00:10 | 6593.43 | 02-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 1.36 | 0.00 | 01-JAN-00:10 | 6593.43 | 02-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 83.77 | 0.00 | 01-JAN-00:10 | 13108.47 | 12-JUN-16:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 83.77 | 0.00 | 01-JAN-00:10 | 13108.47 | 12-JUN-16:10 |
EnergyTransfer:Zone:SMSTORE3 | 85.32 | 0.00 | 01-JAN-00:10 | 13240.97 | 12-JUN-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 1.37 | 0.00 | 01-JAN-00:10 | 7630.46 | 02-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 1.37 | 0.00 | 01-JAN-00:10 | 7630.46 | 02-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 83.95 | 0.00 | 01-JAN-00:10 | 13240.97 | 12-JUN-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 83.95 | 0.00 | 01-JAN-00:10 | 13240.97 | 12-JUN-13:00 |
EnergyTransfer:Zone:SMSTORE4 | 83.90 | 0.00 | 01-JAN-00:10 | 13241.47 | 12-JUN-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 1.41 | 0.00 | 01-JAN-00:10 | 7872.85 | 02-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 1.41 | 0.00 | 01-JAN-00:10 | 7872.85 | 02-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 82.50 | 0.00 | 01-JAN-00:10 | 13241.47 | 12-JUN-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 82.50 | 0.00 | 01-JAN-00:10 | 13241.47 | 12-JUN-13:00 |
EnergyTransfer:Zone:LGSTORE2 | 149.47 | 0.00 | 01-JAN-00:10 | 25302.94 | 12-JUN-14:20 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 1.25 | 0.00 | 01-JAN-00:10 | 15401.45 | 02-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 1.25 | 0.00 | 01-JAN-00:10 | 15401.45 | 02-JAN-09:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 148.22 | 0.00 | 01-JAN-00:10 | 25302.94 | 12-JUN-14:20 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 148.22 | 0.00 | 01-JAN-00:10 | 25302.94 | 12-JUN-14:20 |
EnergyTransfer:Zone:SMSTORE5 | 78.35 | 0.00 | 01-JAN-00:10 | 13546.00 | 12-JUN-14:20 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 0.67 | 0.00 | 01-JAN-00:10 | 7846.43 | 02-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 0.67 | 0.00 | 01-JAN-00:10 | 7846.43 | 02-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 77.68 | 0.00 | 01-JAN-00:10 | 13546.00 | 12-JUN-14:20 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 77.68 | 0.00 | 01-JAN-00:10 | 13546.00 | 12-JUN-14:20 |
EnergyTransfer:Zone:SMSTORE6 | 77.79 | 0.00 | 01-JAN-00:10 | 13515.86 | 12-JUN-14:20 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 0.68 | 0.00 | 01-JAN-00:10 | 7867.05 | 02-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 0.68 | 0.00 | 01-JAN-00:10 | 7867.05 | 02-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 77.11 | 0.00 | 01-JAN-00:10 | 13515.86 | 12-JUN-14:20 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 77.11 | 0.00 | 01-JAN-00:10 | 13515.86 | 12-JUN-14:20 |
EnergyTransfer:Zone:SMSTORE7 | 77.43 | 0.00 | 01-JAN-00:10 | 13636.13 | 12-JUN-14:20 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 0.71 | 0.00 | 01-JAN-00:10 | 7996.78 | 02-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 0.71 | 0.00 | 01-JAN-00:10 | 7996.78 | 02-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 76.71 | 0.00 | 01-JAN-00:10 | 13636.13 | 12-JUN-14:20 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 76.71 | 0.00 | 01-JAN-00:10 | 13636.13 | 12-JUN-14:20 |
EnergyTransfer:Zone:SMSTORE8 | 87.12 | 0.00 | 01-JAN-00:10 | 15862.47 | 12-JUN-12:30 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 0.74 | 0.00 | 01-JAN-00:10 | 8363.35 | 01-JAN-10:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 0.74 | 0.00 | 01-JAN-00:10 | 8363.35 | 01-JAN-10:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 86.39 | 0.00 | 01-JAN-00:10 | 15862.47 | 12-JUN-12:30 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 86.39 | 0.00 | 01-JAN-00:10 | 15862.47 | 12-JUN-12:30 |
EnergyTransfer:HVAC | 1901.48 | 0.00 | 01-JAN-00:10 | 324615.74 | 01-JUL-15:00 |
HeatingCoils:EnergyTransfer | 2.30 | 0.00 | 01-JAN-00:10 | 87280.01 | 02-JAN-09:10 |
CoolingCoils:EnergyTransfer | 1899.19 | 0.00 | 01-JAN-00:10 | 324615.74 | 01-JUL-15:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:11
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 0.445 | -211.186 | 0.000 | 0.000 | 23.294 | 102.498 | 26.357 | 21.997 | 0.000 | 25.189 | 20.956 | 0.000 | -4.507 | 0.000 | -5.045 | -0.001 |
SMSTORE1 | 0.000 | 0.000 | 0.187 | -108.889 | 0.000 | 0.000 | 11.623 | 56.486 | 13.179 | 11.022 | 0.000 | 14.176 | 7.300 | 0.000 | -2.297 | 0.000 | -2.786 | -0.000 |
SMSTORE2 | 0.000 | 0.000 | 1.361 | -83.765 | 0.000 | 0.000 | 6.995 | 40.039 | 10.467 | 10.853 | 0.000 | 14.016 | 5.180 | 0.000 | -2.359 | 0.000 | -2.788 | -0.000 |
SMSTORE3 | 0.000 | 0.000 | 1.367 | -83.950 | 0.000 | 0.000 | 6.999 | 40.039 | 10.467 | 10.843 | 0.000 | 14.011 | 5.344 | 0.000 | -2.352 | 0.000 | -2.769 | -0.000 |
SMSTORE4 | 0.000 | 0.000 | 1.408 | -82.494 | 0.000 | 0.000 | 7.003 | 40.039 | 10.467 | 10.859 | 0.000 | 14.015 | 3.771 | 0.000 | -2.325 | 0.000 | -2.743 | -0.001 |
LGSTORE2 | 0.000 | 0.000 | 1.250 | -148.212 | 0.000 | 0.000 | 24.031 | 53.048 | 19.261 | 21.756 | 0.000 | 24.494 | 13.736 | 0.000 | -4.532 | 0.000 | -4.833 | -0.001 |
SMSTORE5 | 0.000 | 0.000 | 0.669 | -77.675 | 0.000 | 0.000 | 12.016 | 27.343 | 9.631 | 10.903 | 0.000 | 13.971 | 8.123 | 0.000 | -2.251 | 0.000 | -2.730 | -0.001 |
SMSTORE6 | 0.000 | 0.000 | 0.681 | -77.111 | 0.000 | 0.000 | 12.019 | 27.343 | 9.631 | 10.912 | 0.000 | 13.972 | 7.513 | 0.000 | -2.241 | 0.000 | -2.720 | -0.001 |
SMSTORE7 | 0.000 | 0.000 | 0.713 | -76.713 | 0.000 | 0.000 | 12.027 | 27.343 | 9.631 | 10.913 | 0.000 | 13.972 | 7.022 | 0.000 | -2.221 | 0.000 | -2.689 | -0.000 |
SMSTORE8 | 0.000 | 0.000 | 0.737 | -86.384 | 0.000 | 0.000 | 12.035 | 27.343 | 9.631 | 10.832 | 0.000 | 14.304 | 16.567 | 0.000 | -2.170 | 0.000 | -2.894 | -0.001 |
Total Facility | 0.000 | 0.000 | 8.818 | -1036.378 | 0.000 | 0.000 | 128.042 | 441.522 | 128.721 | 130.891 | 0.000 | 162.120 | 95.513 | 0.000 | -27.253 | 0.000 | -31.996 | -0.005 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 08-APR-08:62 | 0.00 | 0.00 | 0.00 | -55458.75 | 0.00 | 0.00 | 169.25 | 2800.74 | 749.03 | 502.00 | 0.00 | 101.41 | 51136.31 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 08-APR-08:62 | 0.00 | 0.00 | 0.00 | -28435.87 | 0.00 | 0.00 | 83.70 | 1543.46 | 374.52 | 247.73 | 0.00 | 52.61 | 26133.86 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 30-APR-08:61 | 0.00 | 0.00 | 0.00 | -28921.62 | 0.00 | 0.00 | 80.41 | 1368.01 | 374.52 | 219.59 | 0.00 | 34.00 | 26845.09 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 30-APR-08:61 | 0.00 | 0.00 | 0.00 | -29010.26 | 0.00 | 0.00 | 79.66 | 1368.01 | 374.52 | 216.76 | 0.00 | 30.37 | 26940.95 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 30-APR-08:61 | 0.00 | 0.00 | 0.00 | -28928.65 | 0.00 | 0.00 | 80.16 | 1368.01 | 374.52 | 217.75 | 0.00 | 32.87 | 26855.34 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 09-APR-09:01 | 0.00 | 0.00 | 0.00 | -53158.32 | 0.00 | 0.00 | 347.96 | 1971.84 | 749.03 | 920.28 | 0.00 | 132.71 | 49036.49 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 09-APR-09:01 | 0.00 | 0.00 | 0.00 | -27792.87 | 0.00 | 0.00 | 173.98 | 1016.37 | 374.52 | 460.26 | 0.00 | 76.56 | 25691.19 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 09-APR-09:01 | 0.00 | 0.00 | 0.00 | -27719.12 | 0.00 | 0.00 | 173.99 | 1016.37 | 374.52 | 460.73 | 0.00 | 76.46 | 25617.06 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 09-APR-09:01 | 0.00 | 0.00 | 0.00 | -27772.81 | 0.00 | 0.00 | 174.04 | 1016.37 | 374.52 | 461.43 | 0.00 | 76.77 | 25669.69 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 09-APR-09:01 | 0.00 | 0.00 | 0.00 | -30292.05 | 0.00 | 0.00 | 174.11 | 1016.37 | 374.52 | 461.20 | 0.00 | 92.00 | 28173.86 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 12-JUN-07:01 | 0.00 | 0.00 | 0.00 | -292992.30 | 0.00 | 0.00 | 452.03 | 5142.15 | 1460.61 | 3832.06 | 0.00 | 4027.60 | 278077.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 01-JAN-09:01 | 0.00 | 0.00 | 64041.56 | 0.00 | 0.00 | 0.00 | 256.17 | 2800.74 | 749.03 | 673.94 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -760.14 | -67761.29 |
SMSTORE1 | 01-JAN-09:01 | 0.00 | 0.00 | 32572.48 | 0.00 | 0.00 | 0.00 | 124.33 | 1543.46 | 374.52 | 319.41 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -461.86 | -34472.33 |
SMSTORE2 | 01-JAN-09:01 | 0.00 | 0.00 | 32650.76 | 0.00 | 0.00 | 0.00 | 128.71 | 1368.01 | 374.52 | 338.44 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -427.61 | -34432.83 |
SMSTORE3 | 01-JAN-09:01 | 0.00 | 0.00 | 32806.70 | 0.00 | 0.00 | 0.00 | 130.38 | 1368.01 | 374.52 | 348.15 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -414.08 | -34613.68 |
SMSTORE4 | 01-JAN-09:01 | 0.00 | 0.00 | 32758.99 | 0.00 | 0.00 | 0.00 | 130.38 | 1368.01 | 374.52 | 351.75 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -413.50 | -34570.14 |
LGSTORE2 | 01-JAN-10:01 | 0.00 | 0.00 | 61100.26 | 0.00 | 0.00 | 0.00 | 573.67 | 1971.84 | 749.03 | 1453.43 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -634.94 | -65213.30 |
SMSTORE5 | 01-JAN-10:01 | 0.00 | 0.00 | 32228.77 | 0.00 | 0.00 | 0.00 | 286.83 | 1016.37 | 374.52 | 725.88 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -364.48 | -34267.88 |
SMSTORE6 | 01-JAN-10:01 | 0.00 | 0.00 | 32129.64 | 0.00 | 0.00 | 0.00 | 286.83 | 1016.37 | 374.52 | 726.71 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -364.25 | -34169.81 |
SMSTORE7 | 01-JAN-10:01 | 0.00 | 0.00 | 32222.14 | 0.00 | 0.00 | 0.00 | 286.83 | 1016.37 | 374.52 | 729.27 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -364.10 | -34265.01 |
SMSTORE8 | 01-JAN-10:01 | 0.00 | 0.00 | 35800.55 | 0.00 | 0.00 | 0.00 | 289.42 | 1016.37 | 374.52 | 737.79 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -366.67 | -37851.96 |
Total Facility | 02-JAN-09:01 | 0.00 | 0.00 | 288646.15 | 0.00 | 0.00 | 0.00 | 2796.16 | 18179.18 | 5393.02 | 5277.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5279.92 | -315012.02 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:11
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.8149 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.8149 | 0.1462 | 1.0000 | Not calculated | 0.4115 | 0.1462 | ||
PSZ-AC_2:2 | 1.4418 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4418 | 0.1427 | 1.0000 | Not calculated | 0.2057 | 0.1427 | ||
PSZ-AC_3:3 | 1.4358 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4358 | 0.1433 | 1.0000 | Not calculated | 0.2057 | 0.1433 | ||
PSZ-AC_4:4 | 1.4389 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4389 | 0.1430 | 1.0000 | Not calculated | 0.2057 | 0.1430 | ||
PSZ-AC_5:5 | 1.4356 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4356 | 0.1433 | 1.0000 | Not calculated | 0.2057 | 0.1433 | ||
PSZ-AC_6:6 | 2.6313 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.6313 | 0.1564 | 1.0000 | Not calculated | 0.4115 | 0.1564 | ||
PSZ-AC_7:7 | 1.3939 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3939 | 0.1476 | 1.0000 | Not calculated | 0.2057 | 0.1476 | ||
PSZ-AC_8:8 | 1.3889 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3889 | 0.1481 | 1.0000 | Not calculated | 0.2057 | 0.1481 | ||
PSZ-AC_9:9 | 1.3928 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3928 | 0.1477 | 1.0000 | Not calculated | 0.2057 | 0.1477 | ||
PSZ-AC_10:10 | 1.5679 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.5679 | 0.1312 | 1.0000 | Not calculated | 0.2057 | 0.1312 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.8149 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.8149 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.1462 | ||
PSZ-AC_2:2 | 1.4418 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4418 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1427 | ||
PSZ-AC_3:3 | 1.4358 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4358 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1433 | ||
PSZ-AC_4:4 | 1.4389 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4389 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1430 | ||
PSZ-AC_5:5 | 1.4356 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4356 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1433 | ||
PSZ-AC_6:6 | 2.6313 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.6313 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.1564 | ||
PSZ-AC_7:7 | 1.3939 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3939 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1476 | ||
PSZ-AC_8:8 | 1.3889 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3889 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1481 | ||
PSZ-AC_9:9 | 1.3928 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3928 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1477 | ||
PSZ-AC_10:10 | 1.5679 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.5679 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1312 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.8149 | 2.8149 | 2.8149 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4418 | 1.4418 | 1.4418 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4358 | 1.4358 | 1.4358 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4389 | 1.4389 | 1.4389 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4356 | 1.4356 | 1.4356 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.6313 | 2.6313 | 2.6313 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3939 | 1.3939 | 1.3939 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3889 | 1.3889 | 1.3889 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3928 | 1.3928 | 1.3928 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5679 | 1.5679 | 1.5679 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.8149 | 2.8149 | 2.8149 | 2.8149 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.4418 | 1.4418 | 1.4418 | 1.4418 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.4358 | 1.4358 | 1.4358 | 1.4358 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.4389 | 1.4389 | 1.4389 | 1.4389 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.4356 | 1.4356 | 1.4356 | 1.4356 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.6313 | 2.6313 | 2.6313 | 2.6313 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.3939 | 1.3939 | 1.3939 | 1.3939 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.3889 | 1.3889 | 1.3889 | 1.3889 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.3928 | 1.3928 | 1.3928 | 1.3928 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.5679 | 1.5679 | 1.5679 | 1.5679 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.8149 | 2.8149 | 2.8149 | No | 0.4115 | 0.5392 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4418 | 1.4418 | 1.4418 | No | 0.2057 | 0.5363 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4358 | 1.4358 | 1.4358 | No | 0.2057 | 0.5302 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4389 | 1.4389 | 1.4389 | No | 0.2057 | 0.5252 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4356 | 1.4356 | 1.4356 | No | 0.2057 | 0.5153 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.6313 | 2.6313 | 2.6313 | No | 0.4115 | 0.5456 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3939 | 1.3939 | 1.3939 | No | 0.2057 | 0.5025 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3889 | 1.3889 | 1.3889 | No | 0.2057 | 0.5025 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3928 | 1.3928 | 1.3928 | No | 0.2057 | 0.4889 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5679 | 1.5679 | 1.5679 | No | 0.2057 | 0.4262 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.8149 | 2.8149 | 2.8149 | 2.8149 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.4418 | 1.4418 | 1.4418 | 1.4418 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.4358 | 1.4358 | 1.4358 | 1.4358 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.4389 | 1.4389 | 1.4389 | 1.4389 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.4356 | 1.4356 | 1.4356 | 1.4356 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.6313 | 2.6313 | 2.6313 | 2.6313 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.3939 | 1.3939 | 1.3939 | 1.3939 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.3889 | 1.3889 | 1.3889 | 1.3889 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.3928 | 1.3928 | 1.3928 | 1.3928 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.5679 | 1.5679 | 1.5679 | 1.5679 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:11
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 12.83 |
Number of hours not met | 12.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 2.87 | 109100.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 502.75 | 86891.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 441.52 | 27522.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 99.87 | 7619.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.72 | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 134.27 | 13662.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 58.83 | 10225.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.72 | 1365.96 |
Natural Gas | 0.00 | 2.87 |
Additional | 0.00 | 0.00 |
Total | 128.72 | 1368.83 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 211.22 |
Space Heating | 0.00 |
Space Cooling | 240.51 |
Fans (All) | 64.23 |
Service Water Heating | 28.14 |
Receptacle Equipment | 61.58 |
Miscellaneous (All) | 653.47 |
Subtotal | 653.47 |
Natural Gas [MJ/m2] | |
Space Heating | 1.37 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 1.37 |
Subtotal | 1.37 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 32.26 |
Space Heating | 0.21 |
Space Cooling | 36.73 |
Fans (All) | 9.81 |
Service Water Heating | 4.30 |
Receptacle Equipment | 9.40 |
Miscellaneous | 7.30 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3238. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3296. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 4469. | 8760. |
LTG_SCH_BASE_LPD1 | 4391. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 3584. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4888. | 8760. |
TYPE2_EQUIP_SCH | 3911. | 8760. |
TYPE3_EQUIP_SCH | 3600. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2505. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:11
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 8147.33 | 612.67 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8408.33 | 351.67 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 6891.50 | 1864.33 | 4.17 | 0.00 | 0.00 |
SMSTORE3 | 6824.83 | 1928.17 | 7.00 | 0.00 | 0.00 |
SMSTORE4 | 6897.17 | 1856.50 | 6.33 | 0.00 | 0.00 |
LGSTORE2 | 7365.83 | 1388.83 | 5.33 | 0.00 | 0.00 |
SMSTORE5 | 7494.50 | 1259.50 | 6.00 | 0.00 | 0.00 |
SMSTORE6 | 7519.33 | 1234.83 | 5.83 | 0.00 | 0.00 |
SMSTORE7 | 7527.50 | 1225.83 | 6.67 | 0.00 | 0.00 |
SMSTORE8 | 7176.00 | 1548.83 | 35.17 | 0.00 | 0.00 |
Min | 6824.83 | 351.67 | 0.00 | 0.00 | 0.00 |
Max | 8408.33 | 1928.17 | 35.17 | 0.00 | 0.00 |
Average | 7425.23 | 1327.12 | 7.65 | 0.00 | 0.00 |
Sum | 74252.33 | 13271.17 | 76.50 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 88892.33 | 148.67 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43717.83 | 59.17 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25342.67 | 131.17 | 1.17 | 0.00 | 0.00 |
SMSTORE3 | 25342.17 | 131.67 | 1.17 | 0.00 | 0.00 |
SMSTORE4 | 25344.00 | 129.83 | 1.17 | 0.00 | 0.00 |
LGSTORE2 | 92914.00 | 290.00 | 7.00 | 0.00 | 0.00 |
SMSTORE5 | 45763.50 | 144.50 | 4.00 | 0.00 | 0.00 |
SMSTORE6 | 45763.50 | 144.50 | 4.00 | 0.00 | 0.00 |
SMSTORE7 | 45763.50 | 144.50 | 4.00 | 0.00 | 0.00 |
SMSTORE8 | 45754.00 | 154.00 | 4.00 | 0.00 | 0.00 |
Min | 25342.17 | 59.17 | 0.00 | 0.00 | 0.00 |
Max | 92914.00 | 290.00 | 7.00 | 0.00 | 0.00 |
Average | 48459.75 | 147.80 | 2.65 | 0.00 | 0.00 |
Sum | 484597.50 | 1478.00 | 26.50 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 6555.33 | 2204.67 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 7229.50 | 1530.50 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 5729.67 | 3029.50 | 0.83 | 0.00 | 0.00 |
SMSTORE3 | 5726.17 | 3031.83 | 2.00 | 0.00 | 0.00 |
SMSTORE4 | 5737.50 | 3020.83 | 1.67 | 0.00 | 0.00 |
LGSTORE2 | 5826.17 | 2933.50 | 0.33 | 0.00 | 0.00 |
SMSTORE5 | 5861.67 | 2896.33 | 2.00 | 0.00 | 0.00 |
SMSTORE6 | 5865.67 | 2892.33 | 2.00 | 0.00 | 0.00 |
SMSTORE7 | 5883.00 | 2874.83 | 2.17 | 0.00 | 0.00 |
SMSTORE8 | 5906.17 | 2839.50 | 14.33 | 0.00 | 0.00 |
Min | 5726.17 | 1530.50 | 0.00 | 0.00 | 0.00 |
Max | 7229.50 | 3031.83 | 14.33 | 0.00 | 0.00 |
Average | 6032.08 | 2725.38 | 2.53 | 0.00 | 0.00 |
Sum | 60320.83 | 27253.83 | 25.33 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 75093.50 | 13947.50 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 37426.83 | 6350.17 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 20507.00 | 4967.83 | 0.17 | 0.00 | 0.00 |
SMSTORE3 | 20551.17 | 4923.67 | 0.17 | 0.00 | 0.00 |
SMSTORE4 | 20509.17 | 4965.67 | 0.17 | 0.00 | 0.00 |
LGSTORE2 | 74108.83 | 19101.17 | 1.00 | 0.00 | 0.00 |
SMSTORE5 | 36460.67 | 9450.83 | 0.50 | 0.00 | 0.00 |
SMSTORE6 | 36432.17 | 9479.33 | 0.50 | 0.00 | 0.00 |
SMSTORE7 | 36479.33 | 9432.17 | 0.50 | 0.00 | 0.00 |
SMSTORE8 | 37341.33 | 8570.17 | 0.50 | 0.00 | 0.00 |
Min | 20507.00 | 4923.67 | 0.00 | 0.00 | 0.00 |
Max | 75093.50 | 19101.17 | 1.00 | 0.00 | 0.00 |
Average | 39491.00 | 9118.85 | 0.35 | 0.00 | 0.00 |
Sum | 394910.00 | 91188.50 | 3.50 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:11
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:11
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Environment
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
For: Environment
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
For: Environment
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.658452E+10 | 7755.87 | 12-JAN-15:00 | 23.60 | 14.20 | 0.135528E+10 | 1685.93 | 08-JAN-18:00 | 23.60 | 14.20 |
February | 0.845679E+10 | 11674.32 | 22-FEB-15:00 | 27.10 | 16.20 | 0.125989E+10 | 1685.97 | 20-FEB-18:00 | 27.10 | 16.20 |
March | 0.142843E+11 | 46854.19 | 11-MAR-09:02 | 25.87 | 17.88 | 0.139700E+10 | 1686.04 | 12-MAR-17:49 | 29.35 | 19.37 |
April | 0.203201E+11 | 55458.43 | 08-APR-08:62 | 26.02 | 15.27 | 0.136328E+10 | 1686.13 | 16-APR-12:00 | 39.10 | 21.92 |
May | 0.250601E+11 | 53843.62 | 06-MAY-08:61 | 31.42 | 18.17 | 0.140462E+10 | 1686.18 | 07-MAY-12:50 | 40.73 | 21.37 |
June | 0.250774E+11 | 49228.85 | 07-JUN-08:61 | 36.23 | 19.97 | 0.135755E+10 | 1686.17 | 04-JUN-12:39 | 36.23 | 19.97 |
July | 0.245548E+11 | 40821.48 | 05-JUL-07:01 | 33.75 | 24.52 | 0.141563E+10 | 1686.10 | 04-JUL-17:40 | 33.75 | 24.52 |
August | 0.234895E+11 | 39413.60 | 06-AUG-07:01 | 29.23 | 23.54 | 0.139729E+10 | 1686.05 | 11-AUG-12:30 | 28.05 | 27.10 |
September | 0.214456E+11 | 44209.26 | 26-SEP-08:61 | 26.97 | 20.03 | 0.136775E+10 | 1686.14 | 30-SEP-12:50 | 34.07 | 23.68 |
October | 0.199188E+11 | 49049.70 | 16-OCT-08:62 | 24.53 | 16.49 | 0.141109E+10 | 1686.06 | 09-OCT-17:00 | 24.53 | 16.49 |
November | 0.138092E+11 | 20183.76 | 09-NOV-09:03 | 22.33 | 17.31 | 0.136234E+10 | 1686.03 | 05-NOV-17:10 | 22.33 | 17.31 |
December | 0.818755E+10 | 9728.69 | 03-DEC-14:00 | 24.50 | 14.17 | 0.139133E+10 | 1685.94 | 08-DEC-13:00 | 20.20 | 13.18 |
Annual Sum or Average | 0.211189E+12 | 0.164831E+11 | ||||||||
Minimum of Months | 0.658452E+10 | 7755.87 | 22.33 | 14.17 | 0.125989E+10 | 1685.93 | 20.20 | 13.18 | ||
Maximum of Months | 0.250774E+11 | 55458.43 | 36.23 | 24.52 | 0.141563E+10 | 1686.18 | 40.73 | 27.10 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.333745E+10 | 4302.42 | 12-JAN-15:00 | 23.60 | 14.20 | 0.691191E+09 | 843.15 | 15-JAN-18:49 | 13.63 | 12.95 |
February | 0.467439E+10 | 6213.41 | 22-FEB-15:00 | 27.10 | 16.20 | 0.633092E+09 | 843.24 | 19-FEB-18:19 | 27.10 | 16.20 |
March | 0.777046E+10 | 25043.09 | 11-MAR-09:02 | 25.87 | 17.88 | 0.698790E+09 | 843.25 | 19-MAR-17:30 | 23.90 | 15.01 |
April | 0.105963E+11 | 28435.77 | 08-APR-08:62 | 26.02 | 15.27 | 0.681705E+09 | 843.12 | 16-APR-17:49 | 36.38 | 22.46 |
May | 0.128499E+11 | 27517.85 | 06-MAY-08:61 | 31.42 | 18.17 | 0.702303E+09 | 843.22 | 28-MAY-17:30 | 40.70 | 19.77 |
June | 0.127009E+11 | 25598.86 | 07-JUN-08:61 | 36.23 | 19.97 | 0.678744E+09 | 843.05 | 04-JUN-12:20 | 36.23 | 19.97 |
July | 0.124151E+11 | 23015.84 | 05-JUL-07:01 | 33.75 | 24.52 | 0.707783E+09 | 843.01 | 28-JUL-12:00 | 30.00 | 26.28 |
August | 0.118176E+11 | 22770.06 | 06-AUG-07:01 | 29.23 | 23.54 | 0.698608E+09 | 842.99 | 11-AUG-12:20 | 28.03 | 27.08 |
September | 0.108593E+11 | 24046.29 | 26-SEP-08:61 | 26.97 | 20.03 | 0.683843E+09 | 843.05 | 29-SEP-12:00 | 36.10 | 22.70 |
October | 0.102435E+11 | 26418.02 | 16-OCT-08:62 | 24.53 | 16.49 | 0.705565E+09 | 843.22 | 15-OCT-17:19 | 24.53 | 16.49 |
November | 0.730602E+10 | 11209.43 | 09-NOV-09:03 | 22.33 | 17.31 | 0.681392E+09 | 843.24 | 26-NOV-18:19 | 22.27 | 15.07 |
December | 0.432081E+10 | 5360.07 | 03-DEC-14:00 | 24.50 | 14.17 | 0.702087E+09 | 843.09 | 17-DEC-18:00 | 16.20 | 13.65 |
Annual Sum or Average | 0.108892E+12 | 0.826510E+10 | ||||||||
Minimum of Months | 0.333745E+10 | 4302.42 | 22.33 | 14.17 | 0.633092E+09 | 842.99 | 13.63 | 12.95 | ||
Maximum of Months | 0.128499E+11 | 28435.77 | 36.23 | 24.52 | 0.707783E+09 | 843.25 | 40.70 | 27.08 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.232279E+10 | 3783.22 | 12-JAN-15:00 | 23.60 | 14.20 | 0.403230E+09 | 842.94 | 07-JAN-13:00 | 23.60 | 14.20 |
February | 0.328863E+10 | 5885.65 | 22-FEB-14:00 | 27.00 | 16.33 | 0.377084E+09 | 842.91 | 18-FEB-13:09 | 27.00 | 16.33 |
March | 0.581444E+10 | 22464.52 | 11-MAR-08:62 | 24.43 | 17.41 | 0.431343E+09 | 842.97 | 11-MAR-13:09 | 30.42 | 19.03 |
April | 0.821738E+10 | 28921.91 | 30-APR-08:61 | 26.15 | 14.14 | 0.411964E+09 | 842.96 | 01-APR-12:09 | 26.15 | 14.14 |
May | 0.102877E+11 | 28000.89 | 06-MAY-07:01 | 30.00 | 17.75 | 0.427792E+09 | 843.00 | 27-MAY-12:50 | 40.70 | 20.30 |
June | 0.102034E+11 | 25106.20 | 07-JUN-07:01 | 34.92 | 19.62 | 0.418675E+09 | 842.90 | 17-JUN-12:09 | 37.17 | 26.31 |
July | 0.963721E+10 | 19825.62 | 05-JUL-06:02 | 33.02 | 24.50 | 0.421564E+09 | 842.90 | 29-JUL-12:00 | 32.10 | 26.85 |
August | 0.932088E+10 | 18080.50 | 03-AUG-07:01 | 28.70 | 23.41 | 0.432921E+09 | 842.90 | 26-AUG-12:09 | 32.65 | 28.45 |
September | 0.837151E+10 | 21192.84 | 26-SEP-07:01 | 25.87 | 19.87 | 0.411976E+09 | 843.04 | 30-SEP-12:30 | 33.80 | 23.68 |
October | 0.782923E+10 | 24947.79 | 16-OCT-07:02 | 22.70 | 15.66 | 0.421105E+09 | 842.99 | 14-OCT-12:09 | 22.70 | 15.66 |
November | 0.546602E+10 | 7862.66 | 04-NOV-13:00 | 30.10 | 17.26 | 0.405471E+09 | 842.99 | 18-NOV-13:39 | 26.47 | 17.14 |
December | 0.300846E+10 | 5105.38 | 02-DEC-14:00 | 24.10 | 13.15 | 0.411501E+09 | 842.94 | 09-DEC-13:00 | 19.70 | 12.78 |
Annual Sum or Average | 0.837676E+11 | 0.497463E+10 | ||||||||
Minimum of Months | 0.232279E+10 | 3783.22 | 22.70 | 13.15 | 0.377084E+09 | 842.90 | 19.70 | 12.78 | ||
Maximum of Months | 0.102877E+11 | 28921.91 | 34.92 | 24.50 | 0.432921E+09 | 843.04 | 40.70 | 28.45 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.217617E+10 | 3759.66 | 05-JAN-08:04 | 6.10 | 5.59 | 0.400994E+09 | 842.94 | 07-JAN-13:00 | 20.90 | 13.29 |
February | 0.319570E+10 | 5821.42 | 22-FEB-14:00 | 27.00 | 16.33 | 0.376745E+09 | 842.91 | 18-FEB-13:09 | 27.00 | 16.33 |
March | 0.579164E+10 | 22507.65 | 11-MAR-08:62 | 24.43 | 17.41 | 0.431319E+09 | 842.97 | 11-MAR-13:09 | 30.42 | 19.03 |
April | 0.826826E+10 | 29010.55 | 30-APR-08:61 | 26.15 | 14.14 | 0.411973E+09 | 842.96 | 01-APR-12:09 | 26.15 | 14.14 |
May | 0.104040E+11 | 28067.39 | 06-MAY-07:01 | 30.00 | 17.75 | 0.427801E+09 | 843.00 | 27-MAY-12:50 | 40.70 | 20.30 |
June | 0.103145E+11 | 25172.53 | 07-JUN-07:01 | 34.92 | 19.62 | 0.418684E+09 | 842.90 | 17-JUN-12:09 | 37.17 | 26.31 |
July | 0.975786E+10 | 20157.00 | 05-JUL-06:02 | 33.02 | 24.50 | 0.421573E+09 | 842.90 | 29-JUL-12:00 | 32.10 | 26.85 |
August | 0.940814E+10 | 18170.05 | 03-AUG-07:01 | 28.70 | 23.41 | 0.432928E+09 | 842.90 | 26-AUG-12:09 | 32.65 | 28.45 |
September | 0.844377E+10 | 21294.52 | 26-SEP-07:01 | 25.87 | 19.87 | 0.411983E+09 | 843.03 | 23-SEP-12:09 | 25.87 | 19.87 |
October | 0.787631E+10 | 25070.42 | 16-OCT-07:02 | 22.70 | 15.66 | 0.421114E+09 | 842.99 | 14-OCT-12:09 | 22.70 | 15.66 |
November | 0.542451E+10 | 7849.31 | 04-NOV-13:00 | 30.10 | 17.26 | 0.405430E+09 | 842.99 | 18-NOV-13:39 | 26.47 | 17.14 |
December | 0.289156E+10 | 5036.57 | 02-DEC-14:00 | 24.10 | 13.15 | 0.410848E+09 | 842.94 | 09-DEC-13:00 | 19.70 | 12.78 |
Annual Sum or Average | 0.839525E+11 | 0.497139E+10 | ||||||||
Minimum of Months | 0.217617E+10 | 3759.66 | 6.10 | 5.59 | 0.376745E+09 | 842.90 | 19.70 | 12.78 | ||
Maximum of Months | 0.104040E+11 | 29010.55 | 34.92 | 24.50 | 0.432928E+09 | 843.03 | 40.70 | 28.45 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.201366E+10 | 3860.76 | 05-JAN-08:04 | 6.10 | 5.59 | 0.398385E+09 | 842.93 | 07-JAN-13:00 | 20.90 | 13.29 |
February | 0.304428E+10 | 5690.17 | 22-FEB-14:00 | 27.00 | 16.33 | 0.376160E+09 | 842.91 | 18-FEB-13:09 | 27.00 | 16.33 |
March | 0.563209E+10 | 22338.71 | 11-MAR-08:62 | 24.43 | 17.41 | 0.431229E+09 | 842.97 | 11-MAR-13:09 | 30.42 | 19.03 |
April | 0.814879E+10 | 28928.94 | 30-APR-08:61 | 26.15 | 14.14 | 0.411938E+09 | 842.97 | 01-APR-12:09 | 26.15 | 14.14 |
May | 0.103114E+11 | 28001.36 | 06-MAY-07:01 | 30.00 | 17.75 | 0.427778E+09 | 842.99 | 27-MAY-12:50 | 40.70 | 20.30 |
June | 0.102226E+11 | 25107.15 | 07-JUN-07:01 | 34.92 | 19.62 | 0.418661E+09 | 842.90 | 17-JUN-12:09 | 37.17 | 26.31 |
July | 0.968339E+10 | 20084.45 | 05-JUL-06:02 | 33.02 | 24.50 | 0.421553E+09 | 842.90 | 29-JUL-12:50 | 32.07 | 26.85 |
August | 0.931481E+10 | 18052.17 | 03-AUG-07:01 | 28.70 | 23.41 | 0.432905E+09 | 842.90 | 26-AUG-12:09 | 32.65 | 28.45 |
September | 0.834900E+10 | 21199.64 | 26-SEP-07:01 | 25.87 | 19.87 | 0.411958E+09 | 843.04 | 30-SEP-12:30 | 33.80 | 23.68 |
October | 0.776287E+10 | 24971.38 | 16-OCT-07:02 | 22.70 | 15.66 | 0.421081E+09 | 842.99 | 14-OCT-12:09 | 22.70 | 15.66 |
November | 0.528180E+10 | 7729.56 | 04-NOV-13:00 | 30.10 | 17.26 | 0.405343E+09 | 842.99 | 18-NOV-13:39 | 26.47 | 17.14 |
December | 0.273242E+10 | 4910.43 | 02-DEC-14:00 | 24.10 | 13.15 | 0.409954E+09 | 842.93 | 09-DEC-13:00 | 19.70 | 12.78 |
Annual Sum or Average | 0.824971E+11 | 0.496694E+10 | ||||||||
Minimum of Months | 0.201366E+10 | 3860.76 | 6.10 | 5.59 | 0.376160E+09 | 842.90 | 19.70 | 12.78 | ||
Maximum of Months | 0.103114E+11 | 28928.94 | 34.92 | 24.50 | 0.432905E+09 | 843.04 | 40.70 | 28.45 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.352476E+10 | 6611.17 | 12-JAN-15:10 | 23.55 | 14.25 | 0.136217E+10 | 2247.84 | 28-JAN-15:20 | 18.33 | 11.46 |
February | 0.531693E+10 | 10726.26 | 22-FEB-14:00 | 27.00 | 16.33 | 0.129019E+10 | 2247.85 | 18-FEB-15:00 | 27.00 | 16.33 |
March | 0.101204E+11 | 43438.48 | 11-MAR-09:02 | 25.87 | 17.88 | 0.147933E+10 | 2248.01 | 11-MAR-15:00 | 30.20 | 19.50 |
April | 0.146575E+11 | 53157.82 | 09-APR-09:01 | 27.52 | 15.34 | 0.141274E+10 | 2248.06 | 15-APR-14:20 | 40.23 | 20.63 |
May | 0.186065E+11 | 51810.90 | 29-MAY-08:61 | 32.12 | 19.78 | 0.146165E+10 | 2248.17 | 27-MAY-14:20 | 32.12 | 19.78 |
June | 0.184701E+11 | 47353.64 | 12-JUN-07:01 | 35.90 | 20.13 | 0.143311E+10 | 2247.81 | 17-JUN-14:09 | 38.42 | 25.70 |
July | 0.174533E+11 | 41367.68 | 07-JUL-07:01 | 33.33 | 24.39 | 0.144206E+10 | 2247.81 | 29-JUL-14:09 | 32.40 | 26.64 |
August | 0.168535E+11 | 35087.81 | 03-AUG-08:61 | 29.35 | 23.64 | 0.148288E+10 | 2248.02 | 19-AUG-14:30 | 27.65 | 26.22 |
September | 0.150476E+11 | 41967.82 | 26-SEP-08:61 | 26.97 | 20.03 | 0.141291E+10 | 2247.81 | 02-SEP-14:09 | 26.97 | 20.03 |
October | 0.140452E+11 | 47704.34 | 15-OCT-09:01 | 26.53 | 16.19 | 0.143751E+10 | 2247.98 | 28-OCT-14:00 | 29.30 | 18.44 |
November | 0.938591E+10 | 21562.52 | 11-NOV-10:03 | 23.18 | 16.68 | 0.138126E+10 | 2247.91 | 04-NOV-14:00 | 23.18 | 16.68 |
December | 0.473415E+10 | 8988.01 | 02-DEC-14:20 | 24.03 | 13.16 | 0.140798E+10 | 2247.87 | 23-DEC-15:20 | 20.03 | 12.37 |
Annual Sum or Average | 0.148216E+12 | 0.170038E+11 | ||||||||
Minimum of Months | 0.352476E+10 | 6611.17 | 23.18 | 13.16 | 0.129019E+10 | 2247.81 | 18.33 | 11.46 | ||
Maximum of Months | 0.186065E+11 | 53157.82 | 35.90 | 24.39 | 0.148288E+10 | 2248.17 | 40.23 | 26.64 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.169422E+10 | 3421.24 | 12-JAN-15:10 | 23.55 | 14.25 | 0.679934E+09 | 1123.88 | 28-JAN-15:20 | 18.33 | 11.46 |
February | 0.269712E+10 | 5634.83 | 22-FEB-15:10 | 27.00 | 16.16 | 0.644984E+09 | 1123.89 | 18-FEB-15:00 | 27.00 | 16.16 |
March | 0.528110E+10 | 22711.91 | 11-MAR-09:02 | 25.87 | 17.88 | 0.739663E+09 | 1123.97 | 11-MAR-15:00 | 30.20 | 19.50 |
April | 0.774414E+10 | 27792.61 | 09-APR-09:01 | 27.52 | 15.34 | 0.706331E+09 | 1124.00 | 15-APR-14:30 | 40.25 | 20.64 |
May | 0.986425E+10 | 26865.36 | 06-MAY-08:61 | 31.42 | 18.17 | 0.730788E+09 | 1124.07 | 06-MAY-14:00 | 41.70 | 19.97 |
June | 0.976654E+10 | 24772.58 | 12-JUN-07:01 | 35.90 | 20.13 | 0.716519E+09 | 1123.87 | 10-JUN-14:30 | 35.90 | 20.13 |
July | 0.920978E+10 | 20122.30 | 05-JUL-07:01 | 33.75 | 24.52 | 0.720992E+09 | 1123.87 | 29-JUL-14:09 | 32.40 | 26.64 |
August | 0.887411E+10 | 18403.84 | 03-AUG-08:61 | 29.35 | 23.64 | 0.741406E+09 | 1123.97 | 19-AUG-14:30 | 27.65 | 26.22 |
September | 0.792950E+10 | 22021.55 | 26-SEP-08:61 | 26.97 | 20.03 | 0.706414E+09 | 1123.87 | 02-SEP-14:09 | 26.97 | 20.03 |
October | 0.738323E+10 | 24976.73 | 15-OCT-09:01 | 26.53 | 16.19 | 0.718731E+09 | 1123.96 | 28-OCT-14:00 | 29.30 | 18.44 |
November | 0.488346E+10 | 10559.29 | 11-NOV-10:03 | 23.18 | 16.68 | 0.690637E+09 | 1123.92 | 04-NOV-14:00 | 23.18 | 16.68 |
December | 0.235012E+10 | 4686.38 | 02-DEC-14:30 | 24.00 | 13.17 | 0.703886E+09 | 1123.90 | 23-DEC-15:20 | 20.03 | 12.37 |
Annual Sum or Average | 0.776776E+11 | 0.850029E+10 | ||||||||
Minimum of Months | 0.169422E+10 | 3421.24 | 23.18 | 13.17 | 0.644984E+09 | 1123.87 | 18.33 | 11.46 | ||
Maximum of Months | 0.986425E+10 | 27792.61 | 35.90 | 24.52 | 0.741406E+09 | 1124.07 | 41.70 | 26.64 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.165061E+10 | 3354.16 | 12-JAN-15:10 | 23.55 | 14.25 | 0.678355E+09 | 1123.88 | 28-JAN-15:20 | 18.33 | 11.46 |
February | 0.264190E+10 | 5578.59 | 22-FEB-15:10 | 27.00 | 16.16 | 0.644547E+09 | 1123.89 | 18-FEB-15:00 | 27.00 | 16.16 |
March | 0.521888E+10 | 22607.26 | 11-MAR-09:02 | 25.87 | 17.88 | 0.739621E+09 | 1123.97 | 11-MAR-15:00 | 30.20 | 19.50 |
April | 0.769285E+10 | 27718.86 | 09-APR-09:01 | 27.52 | 15.34 | 0.706319E+09 | 1124.00 | 15-APR-14:30 | 40.25 | 20.64 |
May | 0.981787E+10 | 26780.74 | 06-MAY-08:61 | 31.42 | 18.17 | 0.730783E+09 | 1124.07 | 06-MAY-14:00 | 41.70 | 19.97 |
June | 0.972007E+10 | 24695.16 | 12-JUN-07:01 | 35.90 | 20.13 | 0.716513E+09 | 1123.87 | 17-JUN-14:09 | 38.42 | 25.70 |
July | 0.916996E+10 | 20063.91 | 05-JUL-07:01 | 33.75 | 24.52 | 0.720984E+09 | 1123.87 | 29-JUL-14:09 | 32.40 | 26.64 |
August | 0.883494E+10 | 18333.77 | 03-AUG-08:61 | 29.35 | 23.64 | 0.741402E+09 | 1123.97 | 19-AUG-14:30 | 27.65 | 26.22 |
September | 0.789309E+10 | 21948.21 | 26-SEP-08:61 | 26.97 | 20.03 | 0.706406E+09 | 1123.87 | 02-SEP-14:09 | 26.97 | 20.03 |
October | 0.733902E+10 | 24884.35 | 15-OCT-09:01 | 26.53 | 16.19 | 0.718720E+09 | 1123.96 | 28-OCT-14:00 | 29.30 | 18.44 |
November | 0.483242E+10 | 10274.01 | 11-NOV-10:03 | 23.18 | 16.68 | 0.690607E+09 | 1123.92 | 04-NOV-14:00 | 23.18 | 16.68 |
December | 0.230112E+10 | 4635.09 | 02-DEC-14:30 | 24.00 | 13.17 | 0.703259E+09 | 1123.90 | 23-DEC-15:20 | 20.03 | 12.37 |
Annual Sum or Average | 0.771127E+11 | 0.849752E+10 | ||||||||
Minimum of Months | 0.165061E+10 | 3354.16 | 23.18 | 13.17 | 0.644547E+09 | 1123.87 | 18.33 | 11.46 | ||
Maximum of Months | 0.981787E+10 | 27718.86 | 35.90 | 24.52 | 0.741402E+09 | 1124.07 | 41.70 | 26.64 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.153284E+10 | 3190.01 | 12-JAN-15:10 | 23.55 | 14.25 | 0.674182E+09 | 1123.88 | 28-JAN-15:30 | 18.30 | 11.46 |
February | 0.249083E+10 | 5460.82 | 22-FEB-15:10 | 27.00 | 16.16 | 0.643090E+09 | 1123.89 | 18-FEB-15:00 | 27.00 | 16.16 |
March | 0.507689E+10 | 22544.62 | 11-MAR-09:02 | 25.87 | 17.88 | 0.739458E+09 | 1123.97 | 11-MAR-15:00 | 30.20 | 19.50 |
April | 0.765699E+10 | 27772.55 | 09-APR-09:01 | 27.52 | 15.34 | 0.706298E+09 | 1124.00 | 15-APR-14:30 | 40.25 | 20.64 |
May | 0.985296E+10 | 26850.79 | 06-MAY-08:61 | 31.42 | 18.17 | 0.730785E+09 | 1124.08 | 06-MAY-14:00 | 41.70 | 19.97 |
June | 0.977544E+10 | 24817.19 | 12-JUN-07:01 | 35.90 | 20.13 | 0.716515E+09 | 1123.87 | 17-JUN-14:09 | 38.42 | 25.70 |
July | 0.924653E+10 | 20214.54 | 05-JUL-07:01 | 33.75 | 24.52 | 0.720990E+09 | 1123.87 | 29-JUL-14:09 | 32.40 | 26.64 |
August | 0.890783E+10 | 18406.76 | 03-AUG-08:61 | 29.35 | 23.64 | 0.741406E+09 | 1123.97 | 19-AUG-14:30 | 27.65 | 26.22 |
September | 0.793845E+10 | 22008.18 | 26-SEP-08:61 | 26.97 | 20.03 | 0.706409E+09 | 1123.87 | 02-SEP-14:09 | 26.97 | 20.03 |
October | 0.733525E+10 | 24891.39 | 15-OCT-09:01 | 26.53 | 16.19 | 0.718709E+09 | 1123.96 | 28-OCT-14:00 | 29.30 | 18.44 |
November | 0.473597E+10 | 9509.88 | 11-NOV-10:03 | 23.18 | 16.68 | 0.690501E+09 | 1123.92 | 04-NOV-14:00 | 23.18 | 16.68 |
December | 0.216487E+10 | 4508.18 | 02-DEC-14:30 | 24.00 | 13.17 | 0.701285E+09 | 1123.90 | 23-DEC-15:20 | 20.03 | 12.37 |
Annual Sum or Average | 0.767148E+11 | 0.848963E+10 | ||||||||
Minimum of Months | 0.153284E+10 | 3190.01 | 23.18 | 13.17 | 0.643090E+09 | 1123.87 | 18.30 | 11.46 | ||
Maximum of Months | 0.985296E+10 | 27772.55 | 35.90 | 24.52 | 0.741406E+09 | 1124.08 | 41.70 | 26.64 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.140532E+10 | 3275.88 | 12-JAN-15:10 | 23.55 | 14.25 | 0.671342E+09 | 1123.90 | 07-JAN-15:00 | 23.55 | 14.25 |
February | 0.245061E+10 | 5889.11 | 22-FEB-14:00 | 27.00 | 16.33 | 0.640372E+09 | 1123.88 | 18-FEB-15:00 | 27.00 | 16.33 |
March | 0.532609E+10 | 24629.94 | 11-MAR-09:02 | 25.87 | 17.88 | 0.739033E+09 | 1123.98 | 11-MAR-15:00 | 30.20 | 19.50 |
April | 0.860040E+10 | 30291.78 | 09-APR-09:01 | 27.52 | 15.34 | 0.706352E+09 | 1124.01 | 15-APR-14:30 | 40.25 | 20.64 |
May | 0.113162E+11 | 30042.79 | 29-MAY-08:61 | 32.12 | 19.78 | 0.730867E+09 | 1124.11 | 06-MAY-14:00 | 32.12 | 19.78 |
June | 0.112799E+11 | 28220.41 | 12-JUN-07:01 | 35.90 | 20.13 | 0.716593E+09 | 1123.87 | 17-JUN-14:00 | 38.50 | 25.76 |
July | 0.107526E+11 | 24317.64 | 07-JUL-07:01 | 33.33 | 24.39 | 0.721135E+09 | 1124.01 | 22-JUL-14:30 | 29.55 | 26.95 |
August | 0.104333E+11 | 21150.10 | 08-AUG-07:01 | 30.50 | 24.42 | 0.741530E+09 | 1123.99 | 19-AUG-14:30 | 27.65 | 26.22 |
September | 0.920749E+10 | 24264.46 | 26-SEP-08:61 | 26.97 | 20.03 | 0.706559E+09 | 1123.87 | 02-SEP-14:09 | 26.97 | 20.03 |
October | 0.837983E+10 | 27511.63 | 15-OCT-09:01 | 26.53 | 16.19 | 0.718839E+09 | 1123.96 | 28-OCT-14:00 | 29.30 | 18.44 |
November | 0.512613E+10 | 9744.11 | 11-NOV-10:03 | 23.18 | 16.68 | 0.690347E+09 | 1123.99 | 18-NOV-15:09 | 26.30 | 17.22 |
December | 0.210932E+10 | 4690.49 | 01-DEC-14:00 | 23.50 | 13.07 | 0.699077E+09 | 1123.91 | 09-DEC-15:09 | 19.72 | 13.10 |
Annual Sum or Average | 0.863871E+11 | 0.848205E+10 | ||||||||
Minimum of Months | 0.140532E+10 | 3275.88 | 23.18 | 13.07 | 0.640372E+09 | 1123.87 | 19.72 | 13.10 | ||
Maximum of Months | 0.113162E+11 | 30291.78 | 35.90 | 24.42 | 0.741530E+09 | 1124.11 | 40.25 | 26.95 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 79077573.33 | 64041.56 | 01-JAN-09:01 | 9.20 |
February | 6055863.55 | 19762.19 | 02-FEB-09:02 | 10.37 |
March | 6839612.40 | 2525.50 | 11-MAR-09:05 | 25.87 |
April | 0.106303E+09 | 5985.82 | 28-APR-08:04 | 31.13 |
May | 50951565.44 | 7245.80 | 01-MAY-08:04 | 34.38 |
June | 39940286.35 | 6578.21 | 12-JUN-07:02 | 35.90 |
July | 27483300.48 | 6850.74 | 07-JUL-08:05 | 34.70 |
August | 32904937.86 | 5183.74 | 07-AUG-08:05 | 31.17 |
September | 56065455.94 | 4557.32 | 22-SEP-08:05 | 29.38 |
October | 30925276.02 | 3836.42 | 02-OCT-08:04 | 27.45 |
November | 247805.61 | 1058.10 | 09-NOV-09:07 | 22.33 |
December | 8043112.01 | 37815.16 | 23-DEC-09:02 | 10.55 |
Annual Sum or Average | 0.444838E+09 | |||
Minimum of Months | 247805.61 | 1058.10 | 9.20 | |
Maximum of Months | 0.106303E+09 | 64041.56 | 35.90 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 14831183.36 | 32572.88 | 01-JAN-09:01 | 9.20 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 9.73 |
March | 3340386.30 | 1270.38 | 11-MAR-09:05 | 25.87 |
April | 48485297.48 | 3018.80 | 28-APR-08:04 | 31.13 |
May | 22789453.07 | 3668.47 | 01-MAY-08:04 | 34.38 |
June | 16433747.06 | 3264.28 | 12-JUN-07:02 | 35.90 |
July | 15565444.60 | 3403.18 | 05-JUL-08:05 | 34.65 |
August | 18317241.28 | 2601.13 | 08-AUG-08:05 | 31.15 |
September | 31509141.09 | 2127.81 | 22-SEP-08:05 | 29.38 |
October | 14541944.47 | 2006.17 | 02-OCT-08:04 | 27.45 |
November | 151568.95 | 587.03 | 09-NOV-09:07 | 22.33 |
December | 676777.99 | 3652.73 | 23-DEC-09:02 | 10.55 |
Annual Sum or Average | 0.186642E+09 | |||
Minimum of Months | 0.00 | 0.00 | 9.20 | |
Maximum of Months | 48485297.48 | 32572.88 | 35.90 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 38254195.49 | 32650.83 | 01-JAN-09:01 | 9.20 |
February | 780767.40 | 1572.38 | 02-FEB-08:63 | 8.07 |
March | 36340980.13 | 1869.00 | 12-MAR-16:02 | 31.18 |
April | 0.201980E+09 | 3822.77 | 16-APR-16:01 | 39.13 |
May | 0.242135E+09 | 4546.91 | 07-MAY-16:01 | 42.17 |
June | 0.258233E+09 | 4869.86 | 11-JUN-16:01 | 43.35 |
July | 0.193972E+09 | 4176.74 | 02-JUL-16:01 | 40.38 |
August | 0.162991E+09 | 3184.29 | 06-AUG-16:01 | 36.25 |
September | 0.144905E+09 | 2770.27 | 24-SEP-16:01 | 34.68 |
October | 73070745.52 | 2879.54 | 01-OCT-16:01 | 35.32 |
November | 6356358.35 | 1133.74 | 04-NOV-17:03 | 27.72 |
December | 1562548.39 | 8524.74 | 23-DEC-08:62 | 7.55 |
Annual Sum or Average | 0.136058E+10 | |||
Minimum of Months | 780767.40 | 1133.74 | 7.55 | |
Maximum of Months | 0.258233E+09 | 32650.83 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 55260377.92 | 32806.77 | 01-JAN-09:01 | 9.20 |
February | 1094315.52 | 2978.44 | 02-FEB-08:63 | 8.07 |
March | 36457533.04 | 1869.74 | 12-MAR-16:02 | 31.18 |
April | 0.199637E+09 | 3820.94 | 16-APR-16:01 | 39.13 |
May | 0.240181E+09 | 4544.17 | 07-MAY-16:01 | 42.17 |
June | 0.255862E+09 | 4866.91 | 11-JUN-16:01 | 43.35 |
July | 0.192859E+09 | 4174.11 | 02-JUL-16:01 | 40.38 |
August | 0.161428E+09 | 3181.82 | 06-AUG-16:01 | 36.25 |
September | 0.142755E+09 | 2767.99 | 24-SEP-16:01 | 34.68 |
October | 72169889.90 | 2877.57 | 01-OCT-16:01 | 35.32 |
November | 6398224.31 | 1135.88 | 04-NOV-17:03 | 27.72 |
December | 2407971.62 | 10871.53 | 23-DEC-08:62 | 7.55 |
Annual Sum or Average | 0.136651E+10 | |||
Minimum of Months | 1094315.52 | 1135.88 | 7.55 | |
Maximum of Months | 0.255862E+09 | 32806.77 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 69558986.00 | 32759.06 | 01-JAN-09:01 | 9.20 |
February | 2150265.23 | 4444.68 | 02-FEB-08:63 | 8.07 |
March | 37402415.93 | 1874.61 | 12-MAR-16:02 | 31.18 |
April | 0.204716E+09 | 3823.26 | 16-APR-16:01 | 39.13 |
May | 0.245156E+09 | 4545.75 | 07-MAY-16:01 | 42.17 |
June | 0.258995E+09 | 4867.98 | 11-JUN-16:01 | 43.35 |
July | 0.194724E+09 | 4175.45 | 02-JUL-16:01 | 40.38 |
August | 0.164258E+09 | 3183.38 | 06-AUG-16:01 | 36.25 |
September | 0.146974E+09 | 2770.22 | 24-SEP-16:01 | 34.68 |
October | 73948829.62 | 2880.05 | 01-OCT-16:01 | 35.32 |
November | 6583510.42 | 1142.38 | 04-NOV-17:03 | 27.72 |
December | 3309220.59 | 12981.04 | 23-DEC-08:62 | 7.55 |
Annual Sum or Average | 0.140778E+10 | |||
Minimum of Months | 2150265.23 | 1142.38 | 7.55 | |
Maximum of Months | 0.258995E+09 | 32759.06 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.140152E+09 | 61100.28 | 01-JAN-10:01 | 10.43 |
February | 10538403.23 | 26049.18 | 02-FEB-09:02 | 10.37 |
March | 39148445.77 | 3807.22 | 12-MAR-16:02 | 31.18 |
April | 0.212797E+09 | 7700.85 | 16-APR-16:01 | 39.13 |
May | 0.159830E+09 | 9144.50 | 07-MAY-16:01 | 42.17 |
June | 0.140567E+09 | 9782.14 | 11-JUN-16:01 | 43.35 |
July | 0.152680E+09 | 8394.83 | 02-JUL-16:01 | 40.38 |
August | 0.112138E+09 | 6402.88 | 06-AUG-16:01 | 36.25 |
September | 0.150210E+09 | 5584.37 | 24-SEP-16:01 | 34.68 |
October | 0.107065E+09 | 5810.33 | 01-OCT-16:01 | 35.32 |
November | 13514055.60 | 2316.42 | 04-NOV-17:03 | 27.72 |
December | 11370356.01 | 43860.14 | 23-DEC-09:02 | 10.55 |
Annual Sum or Average | 0.125001E+10 | |||
Minimum of Months | 10538403.23 | 2316.42 | 10.37 | |
Maximum of Months | 0.212797E+09 | 61100.28 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 73546624.28 | 32228.77 | 01-JAN-10:01 | 10.43 |
February | 4268227.64 | 11285.25 | 02-FEB-09:02 | 10.37 |
March | 21104250.91 | 1908.58 | 12-MAR-16:02 | 31.18 |
April | 0.113012E+09 | 3851.61 | 16-APR-16:01 | 39.13 |
May | 88126695.90 | 4572.27 | 07-MAY-16:01 | 42.17 |
June | 74577221.90 | 4892.31 | 11-JUN-16:01 | 43.35 |
July | 79658060.59 | 4199.91 | 02-JUL-16:01 | 40.38 |
August | 61239690.51 | 3207.90 | 06-AUG-16:01 | 36.25 |
September | 83687509.47 | 2797.24 | 24-SEP-16:01 | 34.68 |
October | 57493145.55 | 2908.14 | 01-OCT-16:01 | 35.32 |
November | 7595309.91 | 1179.15 | 04-NOV-17:03 | 27.72 |
December | 4714580.84 | 20198.72 | 23-DEC-09:02 | 10.55 |
Annual Sum or Average | 0.669023E+09 | |||
Minimum of Months | 4268227.64 | 1179.15 | 10.37 | |
Maximum of Months | 0.113012E+09 | 32228.77 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 77965536.27 | 32129.65 | 01-JAN-10:01 | 10.43 |
February | 5088936.94 | 12273.60 | 02-FEB-09:02 | 10.37 |
March | 21166911.51 | 1910.70 | 12-MAR-16:02 | 31.18 |
April | 0.114418E+09 | 3852.76 | 16-APR-16:01 | 39.13 |
May | 89741960.75 | 4573.17 | 07-MAY-16:01 | 42.17 |
June | 75221172.15 | 4893.08 | 11-JUN-16:01 | 43.35 |
July | 79337296.28 | 4200.73 | 02-JUL-16:01 | 40.38 |
August | 62092028.12 | 3208.58 | 06-AUG-16:01 | 36.25 |
September | 85377917.78 | 2798.28 | 24-SEP-16:01 | 34.68 |
October | 57858474.12 | 2909.23 | 01-OCT-16:01 | 35.32 |
November | 7615050.36 | 1181.28 | 04-NOV-17:03 | 27.72 |
December | 5281286.87 | 21559.30 | 23-DEC-09:02 | 10.55 |
Annual Sum or Average | 0.681165E+09 | |||
Minimum of Months | 5088936.94 | 1181.28 | 10.37 | |
Maximum of Months | 0.114418E+09 | 32129.65 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 96652871.33 | 32222.15 | 01-JAN-10:01 | 10.43 |
February | 8401115.00 | 16095.04 | 02-FEB-09:02 | 10.37 |
March | 21588261.29 | 1914.09 | 12-MAR-16:02 | 31.18 |
April | 0.118777E+09 | 3852.16 | 16-APR-16:01 | 39.13 |
May | 91003712.80 | 4571.42 | 07-MAY-16:01 | 42.17 |
June | 75990145.55 | 4890.60 | 11-JUN-16:01 | 43.35 |
July | 80912125.88 | 4197.78 | 02-JUL-16:01 | 40.38 |
August | 61669285.55 | 3205.52 | 06-AUG-16:01 | 36.25 |
September | 84194688.58 | 2795.76 | 24-SEP-16:01 | 34.68 |
October | 58718157.74 | 2907.13 | 01-OCT-16:01 | 35.32 |
November | 7649635.01 | 1184.84 | 04-NOV-17:03 | 27.72 |
December | 7598157.23 | 26199.80 | 23-DEC-09:02 | 10.55 |
Annual Sum or Average | 0.713156E+09 | |||
Minimum of Months | 7598157.23 | 1184.84 | 10.37 | |
Maximum of Months | 0.118777E+09 | 32222.15 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.151679E+09 | 35800.58 | 01-JAN-10:01 | 10.43 |
February | 24184873.66 | 27019.48 | 02-FEB-09:02 | 10.37 |
March | 22451771.56 | 1901.50 | 12-MAR-16:12 | 31.07 |
April | 0.119932E+09 | 3793.38 | 16-APR-16:01 | 39.13 |
May | 80314535.62 | 4506.55 | 07-MAY-16:01 | 42.17 |
June | 68319356.58 | 4824.31 | 11-JUN-16:01 | 43.35 |
July | 69680305.94 | 4123.79 | 02-JUL-16:01 | 40.38 |
August | 52663082.71 | 3131.01 | 06-AUG-16:01 | 36.25 |
September | 68615241.30 | 2722.12 | 24-SEP-16:01 | 34.68 |
October | 55335719.48 | 2834.60 | 01-OCT-16:01 | 35.32 |
November | 7380308.99 | 1152.65 | 04-NOV-17:03 | 27.72 |
December | 16659179.09 | 34857.97 | 23-DEC-09:02 | 10.55 |
Annual Sum or Average | 0.737215E+09 | |||
Minimum of Months | 7380308.99 | 1152.65 | 10.37 | |
Maximum of Months | 0.151679E+09 | 35800.58 | 43.35 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.869933E+10 | 5321.43 | 01-JAN-10:09 | 0.223514E+10 | 1348.26 | 01-JAN-10:09 |
February | 0.786449E+10 | 5321.43 | 01-FEB-10:09 | 0.202238E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.870841E+10 | 5321.43 | 01-MAR-10:09 | 0.224215E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.843013E+10 | 5321.43 | 01-APR-09:09 | 0.216638E+10 | 1348.26 | 01-APR-09:09 |
May | 0.869933E+10 | 5321.43 | 01-MAY-09:09 | 0.223514E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.843013E+10 | 5321.43 | 01-JUN-09:09 | 0.217123E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.870841E+10 | 5321.43 | 01-JUL-09:09 | 0.223729E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.869933E+10 | 5321.43 | 01-AUG-09:09 | 0.223756E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.843920E+10 | 5321.43 | 01-SEP-09:09 | 0.217096E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.869933E+10 | 5321.43 | 01-OCT-09:09 | 0.223514E+10 | 1348.26 | 01-OCT-09:09 |
November | 0.840290E+10 | 5321.43 | 01-NOV-09:09 | 0.215964E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.871748E+10 | 5321.43 | 01-DEC-10:09 | 0.224431E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.102498E+12 | 0.263573E+11 | ||||
Minimum of Months | 0.786449E+10 | 5321.43 | 0.202238E+10 | 1348.26 | ||
Maximum of Months | 0.871748E+10 | 5321.43 | 0.224431E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.479410E+10 | 2932.57 | 01-JAN-10:09 | 0.111757E+10 | 674.13 | 01-JAN-10:09 |
February | 0.433403E+10 | 2932.57 | 01-FEB-10:09 | 0.101119E+10 | 674.13 | 01-FEB-10:09 |
March | 0.479910E+10 | 2932.57 | 01-MAR-10:09 | 0.112107E+10 | 674.13 | 01-MAR-10:09 |
April | 0.464574E+10 | 2932.57 | 01-APR-09:09 | 0.108319E+10 | 674.13 | 01-APR-09:09 |
May | 0.479410E+10 | 2932.57 | 01-MAY-09:09 | 0.111757E+10 | 674.13 | 01-MAY-09:09 |
June | 0.464574E+10 | 2932.57 | 01-JUN-09:09 | 0.108562E+10 | 674.13 | 01-JUN-09:09 |
July | 0.479910E+10 | 2932.57 | 01-JUL-09:09 | 0.111865E+10 | 674.13 | 01-JUL-09:09 |
August | 0.479410E+10 | 2932.57 | 01-AUG-09:09 | 0.111878E+10 | 674.13 | 01-AUG-09:09 |
September | 0.465074E+10 | 2932.57 | 01-SEP-09:09 | 0.108548E+10 | 674.13 | 01-SEP-09:09 |
October | 0.479410E+10 | 2932.57 | 01-OCT-09:09 | 0.111757E+10 | 674.13 | 01-OCT-09:09 |
November | 0.463074E+10 | 2932.57 | 01-NOV-09:09 | 0.107982E+10 | 674.13 | 01-NOV-09:09 |
December | 0.480410E+10 | 2932.57 | 01-DEC-10:09 | 0.112215E+10 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.564857E+11 | 0.131787E+11 | ||||
Minimum of Months | 0.433403E+10 | 2932.57 | 0.101119E+10 | 674.13 | ||
Maximum of Months | 0.480410E+10 | 2932.57 | 0.112215E+10 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.338042E+10 | 2599.23 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.306129E+10 | 2599.23 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.345133E+10 | 2599.23 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.327995E+10 | 2599.23 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.341588E+10 | 2599.23 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.333314E+10 | 2599.23 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.336269E+10 | 2599.23 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.345133E+10 | 2599.23 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.327995E+10 | 2599.23 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.338042E+10 | 2599.23 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.327995E+10 | 2599.23 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.336269E+10 | 2599.23 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.400390E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.306129E+10 | 2599.23 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.345133E+10 | 2599.23 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.338042E+10 | 2599.23 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.306129E+10 | 2599.23 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.345133E+10 | 2599.23 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.327995E+10 | 2599.23 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.341588E+10 | 2599.23 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.333314E+10 | 2599.23 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.336269E+10 | 2599.23 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.345133E+10 | 2599.23 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.327995E+10 | 2599.23 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.338042E+10 | 2599.23 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.327995E+10 | 2599.23 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.336269E+10 | 2599.23 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.400390E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.306129E+10 | 2599.23 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.345133E+10 | 2599.23 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.338042E+10 | 2599.23 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.306129E+10 | 2599.23 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.345133E+10 | 2599.23 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.327995E+10 | 2599.23 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.341588E+10 | 2599.23 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.333314E+10 | 2599.23 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.336269E+10 | 2599.23 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.345133E+10 | 2599.23 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.327995E+10 | 2599.23 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.338042E+10 | 2599.23 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.327995E+10 | 2599.23 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.336269E+10 | 2599.23 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.400390E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.306129E+10 | 2599.23 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.345133E+10 | 2599.23 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.447638E+10 | 3746.51 | 01-JAN-11:09 | 0.162546E+10 | 1348.26 | 01-JAN-11:09 |
February | 0.405472E+10 | 3746.51 | 01-FEB-10:09 | 0.147229E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.457860E+10 | 3746.51 | 01-MAR-10:09 | 0.166213E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.434435E+10 | 3746.51 | 01-APR-09:09 | 0.157746E+10 | 1348.26 | 01-APR-09:09 |
May | 0.452749E+10 | 3746.51 | 01-MAY-09:09 | 0.164379E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.442101E+10 | 3746.51 | 01-JUN-09:09 | 0.160496E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.445083E+10 | 3746.51 | 01-JUL-09:09 | 0.161629E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.457860E+10 | 3746.51 | 01-AUG-09:09 | 0.166213E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.434435E+10 | 3746.51 | 01-SEP-09:09 | 0.157746E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.447638E+10 | 3746.51 | 01-OCT-10:09 | 0.162546E+10 | 1348.26 | 01-OCT-10:09 |
November | 0.434435E+10 | 3746.51 | 01-NOV-09:09 | 0.157746E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.445083E+10 | 3746.51 | 01-DEC-10:09 | 0.161629E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.530479E+11 | 0.192612E+11 | ||||
Minimum of Months | 0.405472E+10 | 3746.51 | 0.147229E+10 | 1348.26 | ||
Maximum of Months | 0.457860E+10 | 3746.51 | 0.166213E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.230731E+10 | 1931.10 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.208997E+10 | 1931.10 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.236000E+10 | 1931.10 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.223926E+10 | 1931.10 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.233366E+10 | 1931.10 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.227877E+10 | 1931.10 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.229414E+10 | 1931.10 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.236000E+10 | 1931.10 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.223926E+10 | 1931.10 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.230731E+10 | 1931.10 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.223926E+10 | 1931.10 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.229414E+10 | 1931.10 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.273431E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.208997E+10 | 1931.10 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.236000E+10 | 1931.10 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.230731E+10 | 1931.10 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.208997E+10 | 1931.10 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.236000E+10 | 1931.10 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.223926E+10 | 1931.10 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.233366E+10 | 1931.10 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.227877E+10 | 1931.10 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.229414E+10 | 1931.10 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.236000E+10 | 1931.10 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.223926E+10 | 1931.10 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.230731E+10 | 1931.10 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.223926E+10 | 1931.10 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.229414E+10 | 1931.10 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.273431E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.208997E+10 | 1931.10 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.236000E+10 | 1931.10 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.230731E+10 | 1931.10 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.208997E+10 | 1931.10 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.236000E+10 | 1931.10 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.223926E+10 | 1931.10 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.233366E+10 | 1931.10 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.227877E+10 | 1931.10 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.229414E+10 | 1931.10 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.236000E+10 | 1931.10 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.223926E+10 | 1931.10 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.230731E+10 | 1931.10 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.223926E+10 | 1931.10 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.229414E+10 | 1931.10 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.273431E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.208997E+10 | 1931.10 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.236000E+10 | 1931.10 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.230731E+10 | 1931.10 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.208997E+10 | 1931.10 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.236000E+10 | 1931.10 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.223926E+10 | 1931.10 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.233366E+10 | 1931.10 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.227877E+10 | 1931.10 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.229414E+10 | 1931.10 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.236000E+10 | 1931.10 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.223926E+10 | 1931.10 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.230731E+10 | 1931.10 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.223926E+10 | 1931.10 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.229414E+10 | 1931.10 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.273431E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.208997E+10 | 1931.10 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.236000E+10 | 1931.10 | 0.831065E+09 | 674.13 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.869933E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197782E+10 |
February | 0.305697E+10 | 0.786449E+10 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120651E+09 | 0.833518E+09 |
March | 0.335708E+10 | 0.870841E+10 | 0.224215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122829E+10 | 0.205149E+09 |
April | 0.327081E+10 | 0.843013E+10 | 0.216638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328622E+10 | 13957184.12 |
May | 0.336680E+10 | 0.869933E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.464322E+10 | 4312571.22 |
June | 0.325380E+10 | 0.843013E+10 | 0.217123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421133E+10 | 1967908.92 |
July | 0.339353E+10 | 0.870841E+10 | 0.223729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339036E+10 | 1080964.42 |
August | 0.334857E+10 | 0.869933E+10 | 0.223756E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287042E+10 | 2011988.47 |
September | 0.327932E+10 | 0.843920E+10 | 0.217096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250961E+10 | 5402730.81 |
October | 0.338624E+10 | 0.869933E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218018E+10 | 44337777.68 |
November | 0.327446E+10 | 0.840290E+10 | 0.215964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.743415E+09 | 0.255806E+09 |
December | 0.340325E+10 | 0.871748E+10 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5212665.75 | 0.169938E+10 |
Annual Sum or Average | 0.397770E+11 | 0.102498E+12 | 0.263573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251889E+11 | 0.504474E+10 |
Minimum of Months | 0.305697E+10 | 0.786449E+10 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1080964.42 |
Maximum of Months | 0.340325E+10 | 0.871748E+10 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.464322E+10 | 0.197782E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.479410E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111832E+10 |
February | 0.152844E+10 | 0.433403E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68407430.48 | 0.449070E+09 |
March | 0.167849E+10 | 0.479910E+10 | 0.112107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.695106E+09 | 96011461.06 |
April | 0.163536E+10 | 0.464574E+10 | 0.108319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185205E+10 | 6269441.66 |
May | 0.168335E+10 | 0.479410E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260118E+10 | 1620588.55 |
June | 0.162685E+10 | 0.464574E+10 | 0.108562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236913E+10 | 647223.36 |
July | 0.169671E+10 | 0.479910E+10 | 0.111865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189372E+10 | 320748.65 |
August | 0.167424E+10 | 0.479410E+10 | 0.111878E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161410E+10 | 708257.97 |
September | 0.163961E+10 | 0.465074E+10 | 0.108548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141845E+10 | 2027724.63 |
October | 0.169307E+10 | 0.479410E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123810E+10 | 22908708.83 |
November | 0.163718E+10 | 0.463074E+10 | 0.107982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422970E+09 | 0.137660E+09 |
December | 0.170157E+10 | 0.480410E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2960843.40 | 0.950353E+09 |
Annual Sum or Average | 0.198880E+11 | 0.564857E+11 | 0.131787E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141762E+11 | 0.278591E+10 |
Minimum of Months | 0.152844E+10 | 0.433403E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 320748.65 |
Maximum of Months | 0.170157E+10 | 0.480410E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260118E+10 | 0.111832E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.338042E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109520E+10 |
February | 0.914877E+09 | 0.306129E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68318992.42 | 0.460552E+09 |
March | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.683574E+09 | 0.104806E+09 |
April | 0.984131E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183109E+10 | 6198676.99 |
May | 0.102058E+10 | 0.341588E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257906E+10 | 1390347.24 |
June | 0.998711E+09 | 0.333314E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235526E+10 | 807170.55 |
July | 0.100600E+10 | 0.336269E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186717E+10 | 358516.30 |
August | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159969E+10 | 1156032.09 |
September | 0.984131E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139966E+10 | 2060462.53 |
October | 0.100722E+10 | 0.338042E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121102E+10 | 21110513.92 |
November | 0.973196E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418357E+09 | 0.145822E+09 |
December | 0.100600E+10 | 0.336269E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2961099.56 | 0.948174E+09 |
Annual Sum or Average | 0.119700E+11 | 0.400390E+11 | 0.104672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140162E+11 | 0.278764E+10 |
Minimum of Months | 0.914877E+09 | 0.306129E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 358516.30 |
Maximum of Months | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257906E+10 | 0.109520E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.338042E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108250E+10 |
February | 0.914877E+09 | 0.306129E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68319432.40 | 0.458352E+09 |
March | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.683547E+09 | 0.104667E+09 |
April | 0.984131E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183073E+10 | 6316026.71 |
May | 0.102058E+10 | 0.341588E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257797E+10 | 1496280.19 |
June | 0.998711E+09 | 0.333314E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235451E+10 | 865258.39 |
July | 0.100600E+10 | 0.336269E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186592E+10 | 404827.99 |
August | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159908E+10 | 1247687.80 |
September | 0.984131E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139930E+10 | 2230673.24 |
October | 0.100722E+10 | 0.338042E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121078E+10 | 21210313.88 |
November | 0.973196E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418365E+09 | 0.145512E+09 |
December | 0.100600E+10 | 0.336269E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2961114.34 | 0.944036E+09 |
Annual Sum or Average | 0.119700E+11 | 0.400390E+11 | 0.104672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140115E+11 | 0.276884E+10 |
Minimum of Months | 0.914877E+09 | 0.306129E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 404827.99 |
Maximum of Months | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257797E+10 | 0.108250E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.338042E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106858E+10 |
February | 0.914877E+09 | 0.306129E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68320207.04 | 0.454771E+09 |
March | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.683708E+09 | 0.103570E+09 |
April | 0.984131E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183109E+10 | 6093938.17 |
May | 0.102058E+10 | 0.341588E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257860E+10 | 1389966.80 |
June | 0.998711E+09 | 0.333314E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235499E+10 | 830285.35 |
July | 0.100600E+10 | 0.336269E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186665E+10 | 360234.99 |
August | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159957E+10 | 1135250.69 |
September | 0.984131E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139958E+10 | 2030831.80 |
October | 0.100722E+10 | 0.338042E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121103E+10 | 21042641.70 |
November | 0.973196E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418399E+09 | 0.144744E+09 |
December | 0.100600E+10 | 0.336269E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2961130.75 | 0.938876E+09 |
Annual Sum or Average | 0.119700E+11 | 0.400390E+11 | 0.104672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140149E+11 | 0.274343E+10 |
Minimum of Months | 0.914877E+09 | 0.306129E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360234.99 |
Maximum of Months | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257860E+10 | 0.106858E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.447638E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186108E+10 |
February | 0.313522E+10 | 0.405472E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119663E+09 | 0.803857E+09 |
March | 0.355148E+10 | 0.457860E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119837E+10 | 0.190049E+09 |
April | 0.338259E+10 | 0.434435E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320112E+10 | 14143647.27 |
May | 0.349753E+10 | 0.452749E+10 | 0.164379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451235E+10 | 3774009.27 |
June | 0.343071E+10 | 0.442101E+10 | 0.160496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411642E+10 | 1936739.23 |
July | 0.344942E+10 | 0.445083E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326274E+10 | 706683.46 |
August | 0.355148E+10 | 0.457860E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278942E+10 | 2591784.22 |
September | 0.338259E+10 | 0.434435E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243718E+10 | 6020919.48 |
October | 0.344359E+10 | 0.447638E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211874E+10 | 46165308.92 |
November | 0.331698E+10 | 0.434435E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.732639E+09 | 0.257052E+09 |
December | 0.344942E+10 | 0.445083E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5185075.60 | 0.164552E+10 |
Annual Sum or Average | 0.410346E+11 | 0.530479E+11 | 0.192612E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244938E+11 | 0.483290E+10 |
Minimum of Months | 0.313522E+10 | 0.405472E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 706683.46 |
Maximum of Months | 0.355148E+10 | 0.457860E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451235E+10 | 0.186108E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105369E+10 |
February | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68319335.45 | 0.452336E+09 |
March | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.684131E+09 | 0.103884E+09 |
April | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182626E+10 | 7470744.39 |
May | 0.174872E+10 | 0.233366E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257185E+10 | 1885303.95 |
June | 0.171530E+10 | 0.227877E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234744E+10 | 967592.50 |
July | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185900E+10 | 323233.21 |
August | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159104E+10 | 1284126.28 |
September | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139121E+10 | 2994097.58 |
October | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121017E+10 | 25708592.85 |
November | 0.165844E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418471E+09 | 0.145218E+09 |
December | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2960935.51 | 0.934416E+09 |
Annual Sum or Average | 0.205167E+11 | 0.273431E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139709E+11 | 0.273018E+10 |
Minimum of Months | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 323233.21 |
Maximum of Months | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257185E+10 | 0.105369E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104842E+10 |
February | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68319542.10 | 0.450606E+09 |
March | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.684196E+09 | 0.103372E+09 |
April | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182645E+10 | 7352090.10 |
May | 0.174872E+10 | 0.233366E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257205E+10 | 1851553.52 |
June | 0.171530E+10 | 0.227877E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234761E+10 | 956995.50 |
July | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185921E+10 | 315323.30 |
August | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159118E+10 | 1261414.73 |
September | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139131E+10 | 2932964.23 |
October | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121028E+10 | 25583148.04 |
November | 0.165844E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418484E+09 | 0.144862E+09 |
December | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2960939.34 | 0.932103E+09 |
Annual Sum or Average | 0.205167E+11 | 0.273431E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139720E+11 | 0.271962E+10 |
Minimum of Months | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 315323.30 |
Maximum of Months | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257205E+10 | 0.104842E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103427E+10 |
February | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68320626.31 | 0.444766E+09 |
March | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.684327E+09 | 0.101481E+09 |
April | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182674E+10 | 6999125.03 |
May | 0.174872E+10 | 0.233366E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257209E+10 | 1764422.34 |
June | 0.171530E+10 | 0.227877E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234759E+10 | 946896.99 |
July | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185895E+10 | 306105.36 |
August | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159103E+10 | 1261467.48 |
September | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139127E+10 | 2876828.93 |
October | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121027E+10 | 25336466.72 |
November | 0.165844E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418502E+09 | 0.143758E+09 |
December | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2961333.27 | 0.924869E+09 |
Annual Sum or Average | 0.205167E+11 | 0.273431E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139720E+11 | 0.268864E+10 |
Minimum of Months | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 306105.36 |
Maximum of Months | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257209E+10 | 0.103427E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107546E+10 |
February | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69154794.01 | 0.496596E+09 |
March | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.694217E+09 | 0.137955E+09 |
April | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186733E+10 | 9973928.82 |
May | 0.174872E+10 | 0.233366E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265399E+10 | 3542166.82 |
June | 0.171530E+10 | 0.227877E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240894E+10 | 2029363.47 |
July | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192475E+10 | 919592.26 |
August | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162824E+10 | 2728668.41 |
September | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141274E+10 | 6350451.20 |
October | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122003E+10 | 30522497.66 |
November | 0.165844E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421285E+09 | 0.158381E+09 |
December | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2989426.35 | 0.969604E+09 |
Annual Sum or Average | 0.205167E+11 | 0.273431E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143037E+11 | 0.289406E+10 |
Minimum of Months | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 919592.26 |
Maximum of Months | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265399E+10 | 0.107546E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 5321.43 | 01-JAN-10:09 | 1348.26 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4238.78 | 15-JAN-18:00 |
February | 4050.04 | 03-FEB-13:09 | 5321.43 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1446.90 | 22-FEB-15:00 | 3769.09 | 10-FEB-18:00 |
March | 4050.04 | 03-MAR-13:09 | 5321.43 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5081.39 | 28-MAR-15:00 | 1577.45 | 18-MAR-17:00 |
April | 4050.04 | 01-APR-12:09 | 5321.43 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7286.17 | 15-APR-15:00 | 319.92 | 10-APR-07:05 |
May | 4050.04 | 05-MAY-12:09 | 5321.43 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8780.03 | 03-MAY-15:00 | 128.03 | 13-MAY-07:10 |
June | 4050.04 | 02-JUN-12:09 | 5321.43 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8804.15 | 06-JUN-15:00 | 95.65 | 24-JUN-08:00 |
July | 4050.04 | 01-JUL-12:09 | 5321.43 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7081.27 | 07-JUL-15:00 | 75.24 | 19-JUL-03:00 |
August | 4050.04 | 04-AUG-12:09 | 5321.43 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5868.59 | 07-AUG-15:00 | 146.36 | 16-AUG-07:10 |
September | 4050.04 | 01-SEP-12:09 | 5321.43 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5404.33 | 29-SEP-13:00 | 138.44 | 07-SEP-08:00 |
October | 4050.04 | 01-OCT-12:09 | 5321.43 | 01-OCT-09:09 | 1348.26 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5498.45 | 02-OCT-14:00 | 505.76 | 11-OCT-17:00 |
November | 4050.04 | 03-NOV-12:09 | 5321.43 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2857.79 | 04-NOV-14:00 | 2233.32 | 30-NOV-18:00 |
December | 4050.04 | 01-DEC-13:09 | 5321.43 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 323.63 | 28-DEC-14:00 | 4989.62 | 31-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 5321.43 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.24 | |||||
Maximum of Months | 4050.04 | 5321.43 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 8804.15 | 4989.62 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 2932.57 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2447.56 | 15-JAN-18:00 |
February | 2024.96 | 03-FEB-13:09 | 2932.57 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 823.06 | 22-FEB-15:00 | 2226.11 | 10-FEB-18:00 |
March | 2024.96 | 03-MAR-13:09 | 2932.57 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.53 | 28-MAR-15:00 | 894.17 | 18-MAR-17:00 |
April | 2024.96 | 01-APR-12:09 | 2932.57 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4077.76 | 15-APR-15:00 | 189.86 | 10-APR-07:05 |
May | 2024.96 | 05-MAY-12:09 | 2932.57 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4973.50 | 03-MAY-15:00 | 76.46 | 13-MAY-07:10 |
June | 2024.96 | 02-JUN-12:09 | 2932.57 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4981.85 | 07-JUN-16:00 | 48.99 | 24-JUN-08:00 |
July | 2024.96 | 01-JUL-12:09 | 2932.57 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4019.10 | 07-JUL-15:00 | 21.67 | 19-JUL-03:00 |
August | 2024.96 | 04-AUG-12:09 | 2932.57 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3322.37 | 07-AUG-15:00 | 79.72 | 16-AUG-07:10 |
September | 2024.96 | 01-SEP-12:09 | 2932.57 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3057.04 | 29-SEP-13:00 | 77.40 | 07-SEP-08:00 |
October | 2024.96 | 01-OCT-12:09 | 2932.57 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3124.71 | 02-OCT-14:00 | 294.61 | 31-OCT-07:05 |
November | 2024.96 | 03-NOV-12:09 | 2932.57 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.72 | 04-NOV-14:00 | 1272.85 | 30-NOV-18:00 |
December | 2024.96 | 01-DEC-13:09 | 2932.57 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 183.34 | 28-DEC-14:00 | 2847.00 | 31-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2932.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.67 | |||||
Maximum of Months | 2024.96 | 2932.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 4981.85 | 2847.00 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2599.23 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2294.97 | 15-JAN-17:00 |
February | 2024.96 | 04-FEB-13:09 | 2599.23 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 823.06 | 22-FEB-15:00 | 2184.92 | 10-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2599.23 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.53 | 28-MAR-15:00 | 894.17 | 18-MAR-17:00 |
April | 2024.96 | 01-APR-12:09 | 2599.23 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4077.30 | 15-APR-15:00 | 176.69 | 22-APR-19:00 |
May | 2024.96 | 06-MAY-12:09 | 2599.23 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4973.44 | 03-MAY-15:00 | 45.11 | 13-MAY-07:02 |
June | 2024.96 | 03-JUN-12:09 | 2599.23 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4981.85 | 07-JUN-16:00 | 65.20 | 18-JUN-07:10 |
July | 2024.96 | 01-JUL-12:09 | 2599.23 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4019.10 | 07-JUL-15:00 | 23.52 | 19-JUL-03:00 |
August | 2024.96 | 05-AUG-12:09 | 2599.23 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3322.37 | 07-AUG-15:00 | 187.51 | 20-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 2599.23 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3056.72 | 29-SEP-13:00 | 81.97 | 03-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2599.23 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3124.70 | 02-OCT-14:00 | 286.69 | 11-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2599.23 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.71 | 04-NOV-14:00 | 1272.84 | 30-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2599.23 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 183.34 | 28-DEC-14:00 | 2767.94 | 21-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2599.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.52 | |||||
Maximum of Months | 2024.96 | 2599.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 4981.85 | 2767.94 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2599.23 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2270.71 | 15-JAN-17:00 |
February | 2024.96 | 04-FEB-13:09 | 2599.23 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 823.06 | 22-FEB-15:00 | 2167.10 | 10-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2599.23 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.53 | 28-MAR-15:00 | 894.17 | 18-MAR-17:00 |
April | 2024.96 | 01-APR-12:09 | 2599.23 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4077.30 | 15-APR-15:00 | 177.43 | 22-APR-19:00 |
May | 2024.96 | 06-MAY-12:09 | 2599.23 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4973.44 | 03-MAY-15:00 | 46.69 | 13-MAY-07:02 |
June | 2024.96 | 03-JUN-12:09 | 2599.23 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4981.85 | 07-JUN-16:00 | 65.35 | 18-JUN-07:02 |
July | 2024.96 | 01-JUL-12:09 | 2599.23 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4019.10 | 07-JUL-15:00 | 24.07 | 19-JUL-03:00 |
August | 2024.96 | 05-AUG-12:09 | 2599.23 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3322.37 | 07-AUG-15:00 | 193.64 | 20-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 2599.23 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3056.71 | 29-SEP-13:00 | 89.62 | 03-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2599.23 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3124.67 | 02-OCT-14:00 | 286.69 | 11-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2599.23 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.71 | 04-NOV-14:00 | 1272.84 | 30-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2599.23 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 183.34 | 28-DEC-14:00 | 2747.95 | 21-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2599.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.07 | |||||
Maximum of Months | 2024.96 | 2599.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 4981.85 | 2747.95 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2599.23 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2240.69 | 15-JAN-17:00 |
February | 2024.96 | 04-FEB-13:09 | 2599.23 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 823.06 | 22-FEB-15:00 | 2138.83 | 10-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2599.23 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.53 | 28-MAR-15:00 | 894.17 | 18-MAR-17:00 |
April | 2024.96 | 01-APR-12:09 | 2599.23 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4077.31 | 15-APR-15:00 | 173.54 | 22-APR-19:00 |
May | 2024.96 | 06-MAY-12:09 | 2599.23 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4973.44 | 03-MAY-15:00 | 43.27 | 13-MAY-07:02 |
June | 2024.96 | 03-JUN-12:09 | 2599.23 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4981.85 | 07-JUN-16:00 | 65.21 | 18-JUN-07:02 |
July | 2024.96 | 01-JUL-12:09 | 2599.23 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4019.10 | 07-JUL-15:00 | 23.31 | 19-JUL-03:00 |
August | 2024.96 | 05-AUG-12:09 | 2599.23 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3322.37 | 07-AUG-15:00 | 185.41 | 20-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 2599.23 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3056.74 | 29-SEP-13:00 | 82.07 | 03-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2599.23 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3124.68 | 02-OCT-14:00 | 286.69 | 11-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2599.23 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.71 | 04-NOV-14:00 | 1272.84 | 30-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2599.23 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 183.34 | 28-DEC-14:00 | 2716.54 | 21-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2599.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.31 | |||||
Maximum of Months | 2024.96 | 2599.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 4981.85 | 2716.54 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 3746.51 | 01-JAN-11:09 | 1348.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3904.41 | 15-JAN-16:00 |
February | 5400.05 | 04-FEB-15:09 | 3746.51 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1440.87 | 22-FEB-15:00 | 3714.81 | 10-FEB-18:00 |
March | 5400.05 | 04-MAR-15:09 | 3746.51 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5081.39 | 28-MAR-15:00 | 1566.21 | 18-MAR-17:00 |
April | 5400.05 | 01-APR-14:09 | 3746.51 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7155.27 | 15-APR-15:00 | 342.68 | 10-APR-07:05 |
May | 5400.05 | 06-MAY-14:09 | 3746.51 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8712.13 | 03-MAY-15:00 | 129.21 | 13-MAY-07:10 |
June | 5400.05 | 03-JUN-14:09 | 3746.51 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8728.03 | 07-JUN-16:00 | 131.05 | 18-JUN-07:02 |
July | 5400.05 | 01-JUL-14:09 | 3746.51 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7038.45 | 07-JUL-15:00 | 44.11 | 19-JUL-03:00 |
August | 5400.05 | 05-AUG-14:09 | 3746.51 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5820.44 | 07-AUG-15:00 | 333.10 | 20-AUG-17:00 |
September | 5400.05 | 02-SEP-14:09 | 3746.51 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5356.34 | 29-SEP-13:00 | 146.45 | 03-SEP-17:00 |
October | 5400.05 | 07-OCT-14:09 | 3746.51 | 01-OCT-10:09 | 1348.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5470.93 | 02-OCT-14:00 | 513.13 | 29-OCT-07:03 |
November | 5400.05 | 04-NOV-14:09 | 3746.51 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2849.05 | 04-NOV-14:00 | 2227.76 | 30-NOV-18:00 |
December | 5400.05 | 02-DEC-15:09 | 3746.51 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 321.09 | 28-DEC-14:00 | 4743.49 | 21-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 3746.51 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.11 | |||||
Maximum of Months | 5400.05 | 3746.51 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 8728.03 | 4743.49 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1931.10 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2216.88 | 15-JAN-16:00 |
February | 2699.95 | 04-FEB-15:09 | 1931.10 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 823.04 | 22-FEB-15:00 | 2110.26 | 10-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1931.10 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.53 | 28-MAR-15:00 | 894.17 | 18-MAR-17:00 |
April | 2699.95 | 01-APR-14:09 | 1931.10 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4077.51 | 15-APR-15:00 | 194.26 | 10-APR-07:05 |
May | 2699.95 | 06-MAY-14:09 | 1931.10 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4973.43 | 03-MAY-15:00 | 71.88 | 13-MAY-07:10 |
June | 2699.95 | 03-JUN-14:09 | 1931.10 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4981.82 | 07-JUN-16:00 | 70.42 | 18-JUN-07:02 |
July | 2699.95 | 01-JUL-14:09 | 1931.10 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4019.10 | 07-JUL-15:00 | 21.51 | 19-JUL-03:00 |
August | 2699.95 | 05-AUG-14:09 | 1931.10 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3322.38 | 07-AUG-15:00 | 171.20 | 20-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1931.10 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3057.11 | 29-SEP-13:00 | 75.76 | 19-SEP-07:10 |
October | 2699.95 | 07-OCT-14:09 | 1931.10 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3124.56 | 02-OCT-14:00 | 292.07 | 30-OCT-07:05 |
November | 2699.95 | 04-NOV-14:09 | 1931.10 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.69 | 04-NOV-14:00 | 1272.85 | 30-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1931.10 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 183.31 | 28-DEC-14:00 | 2703.43 | 21-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.51 | |||||
Maximum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 4981.82 | 2703.43 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1931.10 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2204.91 | 15-JAN-16:00 |
February | 2699.95 | 04-FEB-15:09 | 1931.10 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 823.04 | 22-FEB-15:00 | 2094.56 | 10-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1931.10 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.53 | 28-MAR-15:00 | 894.17 | 18-MAR-17:00 |
April | 2699.95 | 01-APR-14:09 | 1931.10 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4077.51 | 15-APR-15:00 | 192.99 | 10-APR-07:05 |
May | 2699.95 | 06-MAY-14:09 | 1931.10 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4973.43 | 03-MAY-15:00 | 70.80 | 13-MAY-07:10 |
June | 2699.95 | 03-JUN-14:09 | 1931.10 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4981.82 | 07-JUN-16:00 | 69.64 | 18-JUN-07:02 |
July | 2699.95 | 01-JUL-14:09 | 1931.10 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4019.10 | 07-JUL-15:00 | 21.36 | 19-JUL-03:00 |
August | 2699.95 | 05-AUG-14:09 | 1931.10 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3322.38 | 07-AUG-15:00 | 167.87 | 20-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1931.10 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3057.11 | 29-SEP-13:00 | 75.36 | 19-SEP-07:10 |
October | 2699.95 | 07-OCT-14:09 | 1931.10 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3124.56 | 02-OCT-14:00 | 291.13 | 30-OCT-07:05 |
November | 2699.95 | 04-NOV-14:09 | 1931.10 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.69 | 04-NOV-14:00 | 1272.85 | 30-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1931.10 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 183.31 | 28-DEC-14:00 | 2691.92 | 21-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.36 | |||||
Maximum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 4981.82 | 2691.92 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1931.10 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2178.04 | 01-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1931.10 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 823.04 | 22-FEB-15:00 | 2048.11 | 10-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1931.10 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.53 | 28-MAR-15:00 | 894.17 | 18-MAR-17:00 |
April | 2699.95 | 01-APR-14:09 | 1931.10 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4077.51 | 15-APR-15:00 | 188.12 | 10-APR-07:05 |
May | 2699.95 | 06-MAY-14:09 | 1931.10 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4973.43 | 03-MAY-15:00 | 67.38 | 13-MAY-07:10 |
June | 2699.95 | 03-JUN-14:09 | 1931.10 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4981.82 | 07-JUN-16:00 | 68.37 | 18-JUN-07:02 |
July | 2699.95 | 01-JUL-14:09 | 1931.10 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4019.10 | 07-JUL-15:00 | 21.10 | 19-JUL-03:00 |
August | 2699.95 | 05-AUG-14:09 | 1931.10 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3322.38 | 07-AUG-15:00 | 169.79 | 20-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1931.10 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3057.11 | 29-SEP-13:00 | 75.19 | 19-SEP-07:10 |
October | 2699.95 | 07-OCT-14:09 | 1931.10 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3124.55 | 02-OCT-14:00 | 288.53 | 30-OCT-07:05 |
November | 2699.95 | 04-NOV-14:09 | 1931.10 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.69 | 04-NOV-14:00 | 1272.85 | 30-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1931.10 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 183.31 | 28-DEC-14:00 | 2654.51 | 21-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.10 | |||||
Maximum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 4981.82 | 2654.51 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1931.10 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2182.29 | 01-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1931.10 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 829.04 | 22-FEB-15:00 | 1953.73 | 10-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1931.10 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.53 | 28-MAR-15:00 | 905.42 | 18-MAR-17:00 |
April | 2699.95 | 01-APR-14:09 | 1931.10 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4207.95 | 15-APR-15:00 | 215.55 | 22-APR-18:10 |
May | 2699.95 | 06-MAY-14:09 | 1931.10 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5040.74 | 03-MAY-15:00 | 67.87 | 15-MAY-07:10 |
June | 2699.95 | 03-JUN-14:09 | 1931.10 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5080.09 | 06-JUN-15:00 | 84.45 | 18-JUN-07:02 |
July | 2699.95 | 01-JUL-14:09 | 1931.10 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4061.93 | 07-JUL-15:00 | 54.16 | 19-JUL-03:00 |
August | 2699.95 | 05-AUG-14:09 | 1931.10 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3370.53 | 07-AUG-15:00 | 257.22 | 20-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1931.10 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3105.82 | 29-SEP-13:00 | 145.16 | 03-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1931.10 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3151.76 | 02-OCT-14:00 | 295.23 | 29-OCT-07:03 |
November | 2699.95 | 04-NOV-14:09 | 1931.10 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1636.40 | 04-NOV-14:00 | 1278.41 | 30-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1931.10 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 185.80 | 28-DEC-14:00 | 2625.49 | 21-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.16 | |||||
Maximum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 5080.09 | 2625.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7755.87 | 12-JAN-15:00 | 2700.03 | 5321.43 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.42 |
February | 11674.32 | 22-FEB-15:00 | 2700.03 | 5321.43 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 1446.90 | 0.00 |
March | 46854.19 | 11-MAR-09:02 | 2025.02 | 16804.44 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 72.65 | 0.00 |
April | 55458.43 | 08-APR-08:62 | 2025.02 | 16804.44 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 101.41 | 0.00 |
May | 53843.62 | 06-MAY-08:61 | 2700.03 | 22405.92 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 388.14 | 0.00 |
June | 49228.85 | 07-JUN-08:61 | 2700.03 | 22405.92 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 806.12 | 0.00 |
July | 40821.48 | 05-JUL-07:01 | 2700.03 | 2240.45 | 599.22 | 0.00 | 0.00 | 0.00 | 0.00 | 467.21 | 0.00 |
August | 39413.60 | 06-AUG-07:01 | 2700.03 | 2240.45 | 599.22 | 0.00 | 0.00 | 0.00 | 0.00 | 221.61 | 0.00 |
September | 44209.26 | 26-SEP-08:61 | 2700.03 | 22405.92 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 76.87 | 0.00 |
October | 49049.70 | 16-OCT-08:62 | 2025.02 | 16804.44 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 11.68 | 0.00 |
November | 20183.76 | 09-NOV-09:03 | 1012.51 | 8402.22 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.43 |
December | 9728.69 | 03-DEC-14:00 | 4050.04 | 5321.43 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 275.07 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7755.87 | 1012.51 | 2240.45 | 599.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 55458.43 | 4050.04 | 22405.92 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1446.90 | 138.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4302.42 | 12-JAN-15:00 | 1349.97 | 2932.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.16 |
February | 6213.41 | 22-FEB-15:00 | 1349.97 | 2932.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 823.06 | 0.00 |
March | 25043.09 | 11-MAR-09:02 | 1012.48 | 9260.74 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 38.90 | 0.00 |
April | 28435.77 | 08-APR-08:62 | 1012.48 | 9260.74 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 52.61 | 0.00 |
May | 27517.85 | 06-MAY-08:61 | 1349.97 | 12347.66 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 215.62 | 0.00 |
June | 25598.86 | 07-JUN-08:61 | 1349.97 | 12347.66 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 416.42 | 0.00 |
July | 23015.84 | 05-JUL-07:01 | 1349.97 | 1234.77 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 264.44 | 0.00 |
August | 22770.06 | 06-AUG-07:01 | 1349.97 | 1234.77 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 126.84 | 0.00 |
September | 24046.29 | 26-SEP-08:61 | 1349.97 | 12347.66 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 45.27 | 0.00 |
October | 26418.02 | 16-OCT-08:62 | 1012.48 | 9260.74 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.24 | 0.00 |
November | 11209.43 | 09-NOV-09:03 | 506.24 | 4630.37 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.45 |
December | 5360.07 | 03-DEC-14:00 | 2024.96 | 2932.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 157.04 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4302.42 | 506.24 | 1234.77 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28435.77 | 2024.96 | 12347.66 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 823.06 | 78.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3783.22 | 12-JAN-15:00 | 1012.48 | 2599.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.15 |
February | 5885.65 | 22-FEB-14:00 | 1349.97 | 2599.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 797.44 | 0.00 |
March | 22464.52 | 11-MAR-08:62 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 0.00 |
April | 28921.91 | 30-APR-08:61 | 1181.23 | 9576.10 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 34.00 | 0.00 |
May | 28000.89 | 06-MAY-07:01 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 163.49 | 0.00 |
June | 25106.20 | 07-JUN-07:01 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 356.33 | 0.00 |
July | 19825.62 | 05-JUL-06:02 | 0.00 | 684.01 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 12.66 | 0.00 |
August | 18080.50 | 03-AUG-07:01 | 1181.23 | 9576.10 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 107.42 | 0.00 |
September | 21192.84 | 26-SEP-07:01 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
October | 24947.79 | 16-OCT-07:02 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.13 |
November | 7862.66 | 04-NOV-13:00 | 2024.96 | 2599.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1578.98 | 0.00 |
December | 5105.38 | 02-DEC-14:00 | 2024.96 | 2599.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 52.91 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3783.22 | 0.00 | 684.01 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28921.91 | 2024.96 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 1578.98 | 78.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3759.66 | 05-JAN-08:04 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 620.97 |
February | 5821.42 | 22-FEB-14:00 | 1349.97 | 2599.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 797.44 | 0.00 |
March | 22507.65 | 11-MAR-08:62 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 | 0.00 |
April | 29010.55 | 30-APR-08:61 | 1181.23 | 9576.10 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 30.37 | 0.00 |
May | 28067.39 | 06-MAY-07:01 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 163.27 | 0.00 |
June | 25172.53 | 07-JUN-07:01 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 356.21 | 0.00 |
July | 20157.00 | 05-JUL-06:02 | 0.00 | 684.01 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 12.18 | 0.00 |
August | 18170.05 | 03-AUG-07:01 | 1181.23 | 9576.10 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 107.39 | 0.00 |
September | 21294.52 | 26-SEP-07:01 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.01 |
October | 25070.42 | 16-OCT-07:02 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.77 |
November | 7849.31 | 04-NOV-13:00 | 2024.96 | 2599.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1578.98 | 0.00 |
December | 5036.57 | 02-DEC-14:00 | 2024.96 | 2599.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 52.91 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3759.66 | 0.00 | 684.01 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29010.55 | 2024.96 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 1578.98 | 620.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3860.76 | 05-JAN-08:04 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 623.83 |
February | 5690.17 | 22-FEB-14:00 | 1349.97 | 2599.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 797.43 | 0.00 |
March | 22338.71 | 11-MAR-08:62 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 3.90 | 0.00 |
April | 28928.94 | 30-APR-08:61 | 1181.23 | 9576.10 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 32.87 | 0.00 |
May | 28001.36 | 06-MAY-07:01 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 163.43 | 0.00 |
June | 25107.15 | 07-JUN-07:01 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 356.27 | 0.00 |
July | 20084.45 | 05-JUL-06:02 | 0.00 | 684.01 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 12.22 | 0.00 |
August | 18052.17 | 03-AUG-07:01 | 1181.23 | 9576.10 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 107.40 | 0.00 |
September | 21199.64 | 26-SEP-07:01 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
October | 24971.38 | 16-OCT-07:02 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.99 |
November | 7729.56 | 04-NOV-13:00 | 2024.96 | 2599.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1578.97 | 0.00 |
December | 4910.43 | 02-DEC-14:00 | 2024.96 | 2599.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 52.91 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3860.76 | 0.00 | 684.01 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28928.94 | 2024.96 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 1578.97 | 623.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6611.17 | 12-JAN-15:10 | 4657.54 | 3746.51 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.00 |
February | 10726.26 | 22-FEB-14:00 | 4792.55 | 3746.51 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 1395.74 | 0.00 |
March | 43438.48 | 11-MAR-09:02 | 4455.04 | 11831.03 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 68.60 | 0.00 |
April | 53157.82 | 09-APR-09:01 | 5940.06 | 15774.71 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 132.71 | 0.00 |
May | 51810.90 | 29-MAY-08:61 | 0.00 | 1577.32 | 599.22 | 0.00 | 0.00 | 0.00 | 0.00 | 416.47 | 0.00 |
June | 47353.64 | 12-JUN-07:01 | 0.00 | 1577.32 | 599.22 | 0.00 | 0.00 | 0.00 | 0.00 | 562.28 | 0.00 |
July | 41367.68 | 07-JUL-07:01 | 0.00 | 1577.32 | 599.22 | 0.00 | 0.00 | 0.00 | 0.00 | 446.06 | 0.00 |
August | 35087.81 | 03-AUG-08:61 | 5940.06 | 15774.71 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 231.12 | 0.00 |
September | 41967.82 | 26-SEP-08:61 | 5940.06 | 15774.71 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 71.98 | 0.00 |
October | 47704.34 | 15-OCT-09:01 | 5197.55 | 13802.87 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 90.29 | 0.00 |
November | 21562.52 | 11-NOV-10:03 | 2227.52 | 5915.52 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.19 |
December | 8988.01 | 02-DEC-14:20 | 5197.55 | 3746.51 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 62.14 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6611.17 | 0.00 | 1577.32 | 599.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 53157.82 | 5940.06 | 15774.71 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1395.74 | 160.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3421.24 | 12-JAN-15:10 | 2328.71 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.30 |
February | 5634.83 | 22-FEB-15:10 | 2328.71 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 798.03 | 0.00 |
March | 22711.91 | 11-MAR-09:02 | 2227.46 | 6098.20 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 42.62 | 0.00 |
April | 27792.61 | 09-APR-09:01 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 76.56 | 0.00 |
May | 26865.36 | 06-MAY-08:61 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 214.48 | 0.00 |
June | 24772.58 | 12-JUN-07:01 | 0.00 | 813.09 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 321.49 | 0.00 |
July | 20122.30 | 05-JUL-07:01 | 0.00 | 813.09 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 227.73 | 0.00 |
August | 18403.84 | 03-AUG-08:61 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 132.00 | 0.00 |
September | 22021.55 | 26-SEP-08:61 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 42.32 | 0.00 |
October | 24976.73 | 15-OCT-09:01 | 2598.70 | 7114.56 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 53.57 | 0.00 |
November | 10559.29 | 11-NOV-10:03 | 1113.73 | 3049.10 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.55 |
December | 4686.38 | 02-DEC-14:30 | 2598.70 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 26.83 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3421.24 | 0.00 | 813.09 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27792.61 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 798.03 | 91.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3354.16 | 12-JAN-15:10 | 2328.71 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.30 |
February | 5578.59 | 22-FEB-15:10 | 2328.71 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 798.03 | 0.00 |
March | 22607.26 | 11-MAR-09:02 | 2227.46 | 6098.20 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 43.66 | 0.00 |
April | 27718.86 | 09-APR-09:01 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 76.46 | 0.00 |
May | 26780.74 | 06-MAY-08:61 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 214.45 | 0.00 |
June | 24695.16 | 12-JUN-07:01 | 0.00 | 813.09 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 321.49 | 0.00 |
July | 20063.91 | 05-JUL-07:01 | 0.00 | 813.09 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 227.50 | 0.00 |
August | 18333.77 | 03-AUG-08:61 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 131.95 | 0.00 |
September | 21948.21 | 26-SEP-08:61 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 42.22 | 0.00 |
October | 24884.35 | 15-OCT-09:01 | 2598.70 | 7114.56 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 54.20 | 0.00 |
November | 10274.01 | 11-NOV-10:03 | 1113.73 | 3049.10 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.44 |
December | 4635.09 | 02-DEC-14:30 | 2598.70 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 26.82 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3354.16 | 0.00 | 813.09 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27718.86 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 798.03 | 91.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3190.01 | 12-JAN-15:10 | 2328.71 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.29 |
February | 5460.82 | 22-FEB-15:10 | 2328.71 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 798.03 | 0.00 |
March | 22544.62 | 11-MAR-09:02 | 2227.46 | 6098.20 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.10 | 0.00 |
April | 27772.55 | 09-APR-09:01 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 76.77 | 0.00 |
May | 26850.79 | 06-MAY-08:61 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 214.42 | 0.00 |
June | 24817.19 | 12-JUN-07:01 | 0.00 | 813.09 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 319.55 | 0.00 |
July | 20214.54 | 05-JUL-07:01 | 0.00 | 813.09 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 224.60 | 0.00 |
August | 18406.76 | 03-AUG-08:61 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 131.89 | 0.00 |
September | 22008.18 | 26-SEP-08:61 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 42.39 | 0.00 |
October | 24891.39 | 15-OCT-09:01 | 2598.70 | 7114.56 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 55.93 | 0.00 |
November | 9509.88 | 11-NOV-10:03 | 1113.73 | 3049.10 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.16 |
December | 4508.18 | 02-DEC-14:30 | 2598.70 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 26.83 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3190.01 | 0.00 | 813.09 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27772.55 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 798.03 | 91.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3275.88 | 12-JAN-15:10 | 2328.71 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.90 |
February | 5889.11 | 22-FEB-14:00 | 2396.20 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 801.68 | 0.00 |
March | 24629.94 | 11-MAR-09:02 | 2227.46 | 6098.20 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 55.18 | 0.00 |
April | 30291.78 | 09-APR-09:01 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 92.00 | 0.00 |
May | 30042.79 | 29-MAY-08:61 | 0.00 | 813.09 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 279.96 | 0.00 |
June | 28220.41 | 12-JUN-07:01 | 0.00 | 813.09 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 338.92 | 0.00 |
July | 24317.64 | 07-JUL-07:01 | 0.00 | 813.09 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 264.26 | 0.00 |
August | 21150.10 | 08-AUG-07:01 | 0.00 | 711.46 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 147.96 | 0.00 |
September | 24264.46 | 26-SEP-08:61 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 47.51 | 0.00 |
October | 27511.63 | 15-OCT-09:01 | 2598.70 | 7114.56 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 61.83 | 0.00 |
November | 9744.11 | 11-NOV-10:03 | 1113.73 | 3049.10 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.64 |
December | 4690.49 | 01-DEC-14:00 | 2396.20 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.80 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3275.88 | 0.00 | 711.46 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30291.78 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 801.68 | 103.80 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.767018E+11 | 65252.43 | 13-JAN-18:10 | 0.250446E+10 | 109100.01 | 02-JAN-09:09 |
February | 0.767525E+11 | 74376.65 | 22-FEB-18:30 | 0.142941E+09 | 33746.39 | 02-FEB-09:09 |
March | 0.100515E+12 | 94548.66 | 28-MAR-16:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 0.115416E+12 | 112186.82 | 16-APR-13:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.140325E+12 | 128335.14 | 03-MAY-14:50 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.144183E+12 | 139593.76 | 22-JUN-16:40 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.146997E+12 | 137881.91 | 10-JUL-12:50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.146311E+12 | 134920.21 | 27-AUG-14:30 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.130006E+12 | 121235.06 | 14-SEP-16:49 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.114739E+12 | 105314.74 | 03-OCT-14:50 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.938859E+11 | 82469.40 | 04-NOV-13:30 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.801245E+11 | 66149.51 | 28-DEC-17:40 | 0.224612E+09 | 45484.03 | 23-DEC-09:09 |
Annual Sum or Average | 0.136596E+13 | 0.287201E+10 | ||||
Minimum of Months | 0.767018E+11 | 65252.43 | 0.00 | 0.00 | ||
Maximum of Months | 0.146997E+12 | 139593.76 | 0.250446E+10 | 109100.01 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.373403E+11 | 0.981915E+10 | 0.108804E+11 | 0.00 | 0.106509E+11 | 0.00 | 0.00 | 0.276473E+10 | 0.00 | 0.00 | 0.00 | 0.524622E+10 | 0.00 |
February | 0.337970E+11 | 0.843312E+10 | 0.985143E+10 | 0.00 | 0.961644E+10 | 0.00 | 0.00 | 0.103480E+11 | 0.00 | 0.00 | 0.00 | 0.470655E+10 | 0.00 |
March | 0.378801E+11 | 0.863051E+10 | 0.110560E+11 | 0.00 | 0.108229E+11 | 0.00 | 0.00 | 0.269753E+11 | 0.00 | 0.00 | 0.00 | 0.515025E+10 | 0.00 |
April | 0.362171E+11 | 0.766104E+10 | 0.105544E+11 | 0.00 | 0.104823E+11 | 0.00 | 0.00 | 0.456615E+11 | 0.00 | 0.00 | 0.00 | 0.483974E+10 | 0.00 |
May | 0.376032E+11 | 0.730928E+10 | 0.109629E+11 | 0.00 | 0.119201E+11 | 0.00 | 0.00 | 0.676451E+11 | 0.00 | 0.00 | 0.00 | 0.488432E+10 | 0.00 |
June | 0.366114E+11 | 0.674670E+10 | 0.106855E+11 | 0.00 | 0.123781E+11 | 0.00 | 0.00 | 0.731136E+11 | 0.00 | 0.00 | 0.00 | 0.464827E+10 | 0.00 |
July | 0.372230E+11 | 0.714927E+10 | 0.108424E+11 | 0.00 | 0.127855E+11 | 0.00 | 0.00 | 0.742542E+11 | 0.00 | 0.00 | 0.00 | 0.474287E+10 | 0.00 |
August | 0.378660E+11 | 0.763845E+10 | 0.110491E+11 | 0.00 | 0.128040E+11 | 0.00 | 0.00 | 0.721555E+11 | 0.00 | 0.00 | 0.00 | 0.479743E+10 | 0.00 |
September | 0.362312E+11 | 0.805421E+10 | 0.105613E+11 | 0.00 | 0.111942E+11 | 0.00 | 0.00 | 0.592592E+11 | 0.00 | 0.00 | 0.00 | 0.470575E+10 | 0.00 |
October | 0.373403E+11 | 0.904196E+10 | 0.108804E+11 | 0.00 | 0.107243E+11 | 0.00 | 0.00 | 0.417771E+11 | 0.00 | 0.00 | 0.00 | 0.497496E+10 | 0.00 |
November | 0.361749E+11 | 0.934800E+10 | 0.105443E+11 | 0.00 | 0.103116E+11 | 0.00 | 0.00 | 0.225713E+11 | 0.00 | 0.00 | 0.00 | 0.493583E+10 | 0.00 |
December | 0.372370E+11 | 0.100340E+11 | 0.108529E+11 | 0.00 | 0.105801E+11 | 0.00 | 0.00 | 0.622280E+10 | 0.00 | 0.00 | 0.00 | 0.519763E+10 | 0.00 |
Annual Sum or Average | 0.441522E+12 | 0.998657E+11 | 0.128721E+12 | 0.00 | 0.134271E+12 | 0.00 | 0.00 | 0.502748E+12 | 0.00 | 0.00 | 0.00 | 0.588298E+11 | 0.00 |
Minimum of Months | 0.337970E+11 | 0.674670E+10 | 0.985143E+10 | 0.00 | 0.961644E+10 | 0.00 | 0.00 | 0.276473E+10 | 0.00 | 0.00 | 0.00 | 0.464827E+10 | 0.00 |
Maximum of Months | 0.378801E+11 | 0.100340E+11 | 0.110560E+11 | 0.00 | 0.128040E+11 | 0.00 | 0.00 | 0.742542E+11 | 0.00 | 0.00 | 0.00 | 0.524622E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.250446E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.142941E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.224612E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.287201E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.250446E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 27522.57 | 01-JAN-11:09 | 7619.51 | 01-JAN-06:10 | 8089.53 | 01-JAN-11:09 | 0.00 | 9595.08 | 02-JAN-09:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 27522.57 | 01-FEB-10:09 | 7619.51 | 01-FEB-06:10 | 8089.53 | 01-FEB-10:09 | 0.00 | 8020.02 | 02-FEB-09:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 27522.57 | 01-MAR-10:09 | 7619.51 | 01-MAR-06:10 | 8089.53 | 01-MAR-10:09 | 0.00 | 8680.47 | 11-MAR-09:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 27522.57 | 01-APR-09:09 | 7619.51 | 01-APR-05:10 | 8089.53 | 01-APR-09:09 | 0.00 | 9364.02 | 17-APR-08:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 27522.57 | 01-MAY-09:09 | 7619.51 | 01-MAY-05:10 | 8089.53 | 01-MAY-09:09 | 0.00 | 11273.38 | 17-MAY-16:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 27522.57 | 01-JUN-09:09 | 7619.51 | 01-JUN-05:10 | 8089.53 | 01-JUN-09:09 | 0.00 | 13500.41 | 22-JUN-16:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 27522.57 | 01-JUL-09:09 | 7619.51 | 01-JUL-05:10 | 8089.53 | 01-JUL-09:09 | 0.00 | 13662.04 | 01-JUL-14:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 27522.57 | 01-AUG-09:09 | 7619.51 | 01-AUG-05:10 | 8089.53 | 01-AUG-09:09 | 0.00 | 13192.93 | 27-AUG-14:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 27522.57 | 01-SEP-09:09 | 7619.51 | 01-SEP-05:10 | 8089.53 | 01-SEP-09:09 | 0.00 | 11198.81 | 14-SEP-16:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 27522.57 | 01-OCT-10:09 | 7619.51 | 01-OCT-05:10 | 8089.53 | 01-OCT-10:09 | 0.00 | 9458.30 | 03-OCT-08:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 27522.57 | 01-NOV-09:09 | 7619.51 | 01-NOV-05:10 | 8089.53 | 01-NOV-09:09 | 0.00 | 7313.35 | 01-NOV-07:40 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 27522.57 | 01-DEC-10:09 | 7619.51 | 01-DEC-06:10 | 8089.53 | 01-DEC-10:09 | 0.00 | 8265.51 | 23-DEC-09:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 27522.57 | 7619.51 | 8089.53 | 0.00 | 7313.35 | 0.00 | 0.00 | |||||
Maximum of Months | 27522.57 | 7619.51 | 8089.53 | 0.00 | 13662.04 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 14043.87 | 12-JAN-15:09 | 0.00 | 0.00 | 0.00 | 10225.93 | 05-JAN-12:00 | 0.00 |
February | 25156.75 | 22-FEB-13:00 | 0.00 | 0.00 | 0.00 | 9692.15 | 21-FEB-13:30 | 0.00 |
March | 44295.51 | 28-MAR-14:00 | 0.00 | 0.00 | 0.00 | 8829.36 | 25-MAR-11:00 | 0.00 |
April | 63239.44 | 16-APR-14:00 | 0.00 | 0.00 | 0.00 | 9668.41 | 17-APR-13:20 | 0.00 |
May | 76824.51 | 03-MAY-14:00 | 0.00 | 0.00 | 0.00 | 8974.13 | 09-MAY-13:09 | 0.00 |
June | 86891.90 | 10-JUN-15:00 | 0.00 | 0.00 | 0.00 | 9625.48 | 09-JUN-15:39 | 0.00 |
July | 85239.02 | 01-JUL-14:00 | 0.00 | 0.00 | 0.00 | 9642.32 | 20-JUL-13:39 | 0.00 |
August | 80806.53 | 27-AUG-14:09 | 0.00 | 0.00 | 0.00 | 7542.73 | 31-AUG-12:20 | 0.00 |
September | 69674.14 | 14-SEP-16:10 | 0.00 | 0.00 | 0.00 | 7542.67 | 09-SEP-13:39 | 0.00 |
October | 56290.74 | 04-OCT-12:00 | 0.00 | 0.00 | 0.00 | 7539.50 | 04-OCT-11:00 | 0.00 |
November | 34640.78 | 09-NOV-13:50 | 0.00 | 0.00 | 0.00 | 8148.03 | 16-NOV-12:30 | 0.00 |
December | 18301.84 | 28-DEC-13:00 | 0.00 | 0.00 | 0.00 | 7575.76 | 27-DEC-13:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 14043.87 | 0.00 | 0.00 | 0.00 | 7539.50 | 0.00 | ||
Maximum of Months | 86891.90 | 0.00 | 0.00 | 0.00 | 10225.93 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 65252.43 | 13-JAN-18:10 | 27522.57 | 8089.53 | 7619.51 | 0.00 | 7313.35 | 0.00 | 0.00 | 7843.68 | 0.00 |
February | 74376.65 | 22-FEB-18:30 | 27522.57 | 8089.53 | 7619.51 | 0.00 | 7313.35 | 0.00 | 0.00 | 16282.93 | 0.00 |
March | 94548.66 | 28-MAR-16:10 | 27522.57 | 8089.53 | 0.00 | 0.00 | 7313.35 | 0.00 | 0.00 | 44104.47 | 0.00 |
April | 112186.82 | 16-APR-13:09 | 27522.57 | 8089.53 | 0.00 | 0.00 | 8714.96 | 0.00 | 0.00 | 60932.75 | 0.00 |
May | 128335.14 | 03-MAY-14:50 | 27522.57 | 8089.53 | 0.00 | 0.00 | 11055.26 | 0.00 | 0.00 | 76232.69 | 0.00 |
June | 139593.76 | 22-JUN-16:40 | 27522.57 | 8089.53 | 0.00 | 0.00 | 13388.86 | 0.00 | 0.00 | 85851.09 | 0.00 |
July | 137881.91 | 10-JUL-12:50 | 27522.57 | 8089.53 | 0.00 | 0.00 | 13063.69 | 0.00 | 0.00 | 83774.94 | 0.00 |
August | 134920.21 | 27-AUG-14:30 | 27522.57 | 8089.53 | 0.00 | 0.00 | 13180.64 | 0.00 | 0.00 | 80712.31 | 0.00 |
September | 121235.06 | 14-SEP-16:49 | 27522.57 | 8089.53 | 0.00 | 0.00 | 11102.94 | 0.00 | 0.00 | 69095.54 | 0.00 |
October | 105314.74 | 03-OCT-14:50 | 27522.57 | 8089.53 | 0.00 | 0.00 | 8128.92 | 0.00 | 0.00 | 55714.33 | 0.00 |
November | 82469.40 | 04-NOV-13:30 | 27522.57 | 8089.53 | 0.00 | 0.00 | 7313.35 | 0.00 | 0.00 | 34370.31 | 0.00 |
December | 66149.51 | 28-DEC-17:40 | 27522.57 | 8089.53 | 7619.51 | 0.00 | 7313.35 | 0.00 | 0.00 | 12276.07 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 65252.43 | 27522.57 | 8089.53 | 0.00 | 0.00 | 7313.35 | 0.00 | 0.00 | 7843.68 | 0.00 | |
Maximum of Months | 139593.76 | 27522.57 | 8089.53 | 7619.51 | 0.00 | 13388.86 | 0.00 | 0.00 | 85851.09 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 109100.01 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 33746.39 | 02-FEB-09:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 45484.03 | 23-DEC-09:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 109100.01 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.47 | 1.17 | 24.47 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.47 | 0.50 | 24.47 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.67 | 24.47 | 1.67 | 24.47 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.47 | 1.17 | 24.47 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.47 | 0.50 | 24.47 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.48 | 2.00 | 24.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.50 | 2.00 | 24.50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.48 | 1.00 | 24.48 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 5.50 | 24.49 | 5.50 | 24.49 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.50 | 2.00 | 24.50 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.47 | 0.50 | 24.47 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.48 | 2.17 | 24.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.50 | 2.00 | 24.50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.47 | 1.17 | 24.47 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 5.83 | 24.49 | 5.83 | 24.49 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.50 | 2.17 | 24.50 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.47 | 0.50 | 24.47 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 24.48 | 2.33 | 24.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.51 | 2.00 | 24.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.47 | 1.17 | 24.47 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 6.00 | 24.49 | 6.00 | 24.49 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 24.51 | 2.33 | 24.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.53 | 0.33 | 24.53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 24.50 | 3.00 | 24.50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.56 | 1.67 | 24.56 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.52 | 1.00 | 24.52 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 6.00 | 24.52 | 6.00 | 24.52 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 24.56 | 3.00 | 24.56 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.54 | 0.33 | 24.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.50 | 2.00 | 24.50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.55 | 1.50 | 24.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.51 | 0.83 | 24.51 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.67 | 24.52 | 4.67 | 24.52 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.55 | 2.00 | 24.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.49 | 0.33 | 24.49 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.51 | 1.83 | 24.51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.55 | 1.50 | 24.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.51 | 0.83 | 24.51 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.50 | 24.52 | 4.50 | 24.52 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.55 | 1.83 | 24.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.49 | 0.33 | 24.49 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.51 | 1.83 | 24.51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.55 | 1.50 | 24.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.51 | 0.83 | 24.51 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.50 | 24.52 | 4.50 | 24.52 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.55 | 1.83 | 24.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.49 | 0.17 | 24.49 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.48 | 1.50 | 24.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.52 | 1.17 | 24.52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.47 | 0.67 | 24.47 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.50 | 24.49 | 3.50 | 24.49 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.52 | 1.50 | 24.52 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 267.67 | 22.49 | 28.50 | 22.56 | 4.00 | 22.52 |
February | 105.50 | 22.70 | 132.67 | 23.36 | 0.00 | 23.36 |
March | 23.50 | 23.31 | 336.00 | 23.86 | 0.00 | 23.86 |
April | 0.00 | 0.00 | 439.50 | 23.95 | 0.00 | 23.95 |
May | 28.67 | 24.54 | 496.00 | 24.02 | 28.67 | 24.05 |
June | 143.50 | 24.14 | 481.00 | 24.03 | 143.50 | 24.05 |
July | 366.50 | 24.02 | 495.00 | 24.00 | 366.50 | 24.01 |
August | 407.33 | 24.03 | 497.00 | 24.01 | 407.33 | 24.02 |
September | 259.50 | 24.04 | 479.00 | 24.00 | 259.50 | 24.01 |
October | 7.50 | 24.49 | 488.83 | 23.95 | 7.50 | 23.96 |
November | 21.83 | 23.22 | 349.67 | 23.85 | 0.00 | 23.85 |
December | 166.50 | 22.71 | 87.67 | 23.12 | 0.00 | 23.12 |
Annual Sum or Average | 1798.00 | 23.60 | 4310.83 | 23.85 | 1217.00 | 23.88 |
Minimum of Months | 0.00 | 0.00 | 28.50 | 22.56 | 0.00 | 22.52 |
Maximum of Months | 407.33 | 24.54 | 497.00 | 24.03 | 407.33 | 24.05 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 202.67 | 22.86 | 29.83 | 22.98 | 0.17 | 22.98 |
February | 71.17 | 22.93 | 115.00 | 23.52 | 0.00 | 23.52 |
March | 16.17 | 23.52 | 299.17 | 23.89 | 0.00 | 23.89 |
April | 0.00 | 0.00 | 416.33 | 23.96 | 0.00 | 23.96 |
May | 17.67 | 24.30 | 496.00 | 24.00 | 17.67 | 24.01 |
June | 111.33 | 24.07 | 481.00 | 24.01 | 111.33 | 24.02 |
July | 292.83 | 24.03 | 495.00 | 24.00 | 292.83 | 24.01 |
August | 329.17 | 24.02 | 497.00 | 24.01 | 329.17 | 24.01 |
September | 195.50 | 23.99 | 479.00 | 23.98 | 195.50 | 23.98 |
October | 2.33 | 24.12 | 468.83 | 23.94 | 2.33 | 23.95 |
November | 16.00 | 23.38 | 295.67 | 23.87 | 0.00 | 23.87 |
December | 128.00 | 23.08 | 70.83 | 23.37 | 0.00 | 23.37 |
Annual Sum or Average | 1382.83 | 23.70 | 4143.67 | 23.90 | 949.00 | 23.92 |
Minimum of Months | 0.00 | 0.00 | 29.83 | 22.98 | 0.00 | 22.98 |
Maximum of Months | 329.17 | 24.30 | 497.00 | 24.01 | 329.17 | 24.02 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 206.50 | 22.62 | 10.67 | 22.69 | 0.00 | 22.69 |
February | 70.00 | 22.72 | 87.00 | 23.45 | 0.00 | 23.45 |
March | 13.33 | 23.60 | 267.00 | 24.06 | 0.50 | 24.07 |
April | 7.50 | 28.32 | 327.00 | 24.26 | 7.50 | 24.35 |
May | 40.50 | 26.08 | 375.00 | 24.37 | 40.50 | 24.53 |
June | 135.50 | 24.64 | 366.00 | 24.32 | 135.50 | 24.39 |
July | 297.17 | 24.25 | 369.00 | 24.21 | 297.17 | 24.23 |
August | 335.00 | 24.18 | 379.00 | 24.16 | 335.00 | 24.17 |
September | 215.17 | 24.27 | 360.00 | 24.19 | 215.17 | 24.21 |
October | 11.83 | 25.86 | 366.33 | 24.15 | 11.83 | 24.20 |
November | 13.00 | 23.19 | 250.50 | 23.98 | 0.00 | 23.98 |
December | 114.50 | 22.78 | 39.83 | 23.08 | 0.00 | 23.08 |
Annual Sum or Average | 1460.00 | 23.92 | 3197.33 | 24.07 | 1043.17 | 24.13 |
Minimum of Months | 7.50 | 22.62 | 10.67 | 22.69 | 0.00 | 22.69 |
Maximum of Months | 335.00 | 28.32 | 379.00 | 24.37 | 335.00 | 24.53 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 230.33 | 22.64 | 9.67 | 22.69 | 0.50 | 22.68 |
February | 73.50 | 22.69 | 76.50 | 23.39 | 0.00 | 23.39 |
March | 13.50 | 23.57 | 263.50 | 24.06 | 0.50 | 24.07 |
April | 7.67 | 28.32 | 328.00 | 24.26 | 7.67 | 24.35 |
May | 40.17 | 26.12 | 375.00 | 24.38 | 40.17 | 24.53 |
June | 133.67 | 24.65 | 366.00 | 24.32 | 133.67 | 24.39 |
July | 294.17 | 24.26 | 369.00 | 24.22 | 294.17 | 24.23 |
August | 333.17 | 24.19 | 379.00 | 24.17 | 333.17 | 24.17 |
September | 213.67 | 24.28 | 360.00 | 24.19 | 213.67 | 24.21 |
October | 12.17 | 25.90 | 367.33 | 24.15 | 12.17 | 24.21 |
November | 14.33 | 23.18 | 246.67 | 23.97 | 0.00 | 23.97 |
December | 122.33 | 22.76 | 34.17 | 23.02 | 0.00 | 23.02 |
Annual Sum or Average | 1488.67 | 23.90 | 3174.83 | 24.06 | 1035.67 | 24.12 |
Minimum of Months | 7.67 | 22.64 | 9.67 | 22.69 | 0.00 | 22.68 |
Maximum of Months | 333.17 | 28.32 | 379.00 | 24.38 | 333.17 | 24.53 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 261.50 | 22.65 | 9.00 | 22.69 | 0.83 | 22.68 |
February | 79.33 | 22.66 | 69.50 | 23.31 | 0.00 | 23.31 |
March | 16.00 | 23.52 | 256.00 | 24.05 | 0.50 | 24.06 |
April | 7.17 | 28.33 | 326.50 | 24.25 | 7.17 | 24.34 |
May | 40.83 | 26.06 | 375.00 | 24.37 | 40.83 | 24.52 |
June | 135.50 | 24.63 | 366.00 | 24.31 | 135.50 | 24.38 |
July | 295.83 | 24.25 | 369.00 | 24.21 | 295.83 | 24.22 |
August | 335.17 | 24.18 | 379.00 | 24.16 | 335.17 | 24.17 |
September | 215.50 | 24.27 | 360.00 | 24.19 | 215.50 | 24.21 |
October | 12.17 | 25.79 | 367.00 | 24.15 | 12.17 | 24.20 |
November | 16.17 | 23.16 | 240.33 | 23.96 | 0.00 | 23.96 |
December | 133.17 | 22.74 | 28.17 | 22.95 | 0.00 | 22.95 |
Annual Sum or Average | 1548.33 | 23.85 | 3145.50 | 24.04 | 1043.50 | 24.11 |
Minimum of Months | 7.17 | 22.65 | 9.00 | 22.69 | 0.00 | 22.68 |
Maximum of Months | 335.17 | 28.33 | 379.00 | 24.37 | 335.17 | 24.52 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 273.17 | 22.81 | 8.00 | 22.84 | 0.67 | 22.83 |
February | 74.00 | 22.86 | 58.50 | 23.35 | 0.00 | 23.35 |
March | 12.00 | 23.59 | 225.83 | 23.94 | 0.50 | 23.95 |
April | 4.33 | 28.59 | 299.33 | 24.07 | 4.33 | 24.13 |
May | 26.33 | 25.23 | 344.00 | 24.10 | 26.33 | 24.17 |
June | 121.17 | 24.16 | 336.00 | 24.04 | 121.17 | 24.07 |
July | 276.17 | 24.06 | 338.00 | 24.04 | 276.17 | 24.05 |
August | 319.17 | 23.99 | 348.00 | 23.98 | 319.17 | 23.99 |
September | 195.00 | 24.07 | 330.00 | 24.02 | 195.00 | 24.04 |
October | 10.17 | 25.61 | 336.33 | 24.03 | 10.17 | 24.08 |
November | 7.83 | 23.25 | 219.67 | 23.92 | 0.00 | 23.92 |
December | 125.67 | 22.87 | 21.17 | 23.02 | 0.00 | 23.02 |
Annual Sum or Average | 1445.00 | 23.69 | 2864.83 | 23.89 | 953.50 | 23.93 |
Minimum of Months | 4.33 | 22.81 | 8.00 | 22.84 | 0.00 | 22.83 |
Maximum of Months | 319.17 | 28.59 | 348.00 | 24.10 | 319.17 | 24.17 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 282.67 | 22.84 | 4.17 | 22.85 | 0.67 | 22.85 |
February | 79.83 | 22.95 | 48.33 | 23.34 | 0.00 | 23.34 |
March | 13.50 | 23.64 | 196.67 | 23.95 | 0.50 | 23.96 |
April | 4.17 | 28.56 | 285.00 | 24.08 | 4.17 | 24.14 |
May | 25.83 | 25.23 | 344.00 | 24.10 | 25.83 | 24.17 |
June | 120.17 | 24.16 | 336.00 | 24.04 | 120.17 | 24.07 |
July | 276.17 | 24.06 | 338.00 | 24.04 | 276.17 | 24.05 |
August | 317.50 | 23.99 | 348.00 | 23.98 | 317.50 | 23.99 |
September | 196.33 | 24.06 | 330.00 | 24.02 | 196.33 | 24.03 |
October | 9.50 | 25.34 | 333.50 | 24.02 | 9.50 | 24.06 |
November | 9.50 | 23.38 | 200.83 | 23.92 | 0.00 | 23.92 |
December | 132.17 | 22.94 | 14.83 | 23.04 | 0.00 | 23.04 |
Annual Sum or Average | 1467.33 | 23.69 | 2779.33 | 23.89 | 950.83 | 23.93 |
Minimum of Months | 4.17 | 22.84 | 4.17 | 22.85 | 0.00 | 22.85 |
Maximum of Months | 317.50 | 28.56 | 348.00 | 24.10 | 317.50 | 24.17 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 284.83 | 22.81 | 3.83 | 22.82 | 0.83 | 22.82 |
February | 84.67 | 22.96 | 46.17 | 23.32 | 0.00 | 23.32 |
March | 14.83 | 23.62 | 194.50 | 23.95 | 0.50 | 23.96 |
April | 4.17 | 28.55 | 283.33 | 24.08 | 4.17 | 24.14 |
May | 26.50 | 25.19 | 344.00 | 24.09 | 26.50 | 24.17 |
June | 120.83 | 24.16 | 336.00 | 24.04 | 120.83 | 24.06 |
July | 276.33 | 24.06 | 338.00 | 24.04 | 276.33 | 24.05 |
August | 317.83 | 23.99 | 348.00 | 23.98 | 317.83 | 23.99 |
September | 196.67 | 24.06 | 330.00 | 24.02 | 196.67 | 24.03 |
October | 9.83 | 25.28 | 333.17 | 24.02 | 9.83 | 24.06 |
November | 10.17 | 23.38 | 198.00 | 23.92 | 0.00 | 23.92 |
December | 138.00 | 22.94 | 11.83 | 23.02 | 0.00 | 23.02 |
Annual Sum or Average | 1484.67 | 23.68 | 2766.83 | 23.88 | 953.50 | 23.93 |
Minimum of Months | 4.17 | 22.81 | 3.83 | 22.82 | 0.00 | 22.82 |
Maximum of Months | 317.83 | 28.55 | 348.00 | 24.09 | 317.83 | 24.17 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 291.50 | 22.75 | 1.50 | 22.74 | 1.33 | 22.74 |
February | 96.50 | 22.94 | 40.67 | 23.25 | 0.00 | 23.25 |
March | 17.83 | 23.54 | 191.17 | 23.94 | 0.50 | 23.95 |
April | 4.17 | 28.54 | 283.00 | 24.08 | 4.17 | 24.14 |
May | 26.67 | 25.19 | 344.00 | 24.09 | 26.67 | 24.17 |
June | 120.33 | 24.16 | 336.00 | 24.04 | 120.33 | 24.06 |
July | 275.17 | 24.06 | 338.00 | 24.04 | 275.17 | 24.05 |
August | 316.83 | 23.99 | 348.00 | 23.98 | 316.83 | 23.99 |
September | 196.00 | 24.06 | 330.00 | 24.02 | 196.00 | 24.03 |
October | 10.17 | 25.24 | 333.17 | 24.02 | 10.17 | 24.06 |
November | 12.17 | 23.36 | 194.50 | 23.92 | 0.00 | 23.92 |
December | 150.33 | 22.92 | 9.50 | 22.97 | 0.00 | 22.97 |
Annual Sum or Average | 1517.67 | 23.65 | 2749.50 | 23.87 | 951.17 | 23.91 |
Minimum of Months | 4.17 | 22.75 | 1.50 | 22.74 | 0.00 | 22.74 |
Maximum of Months | 316.83 | 28.54 | 348.00 | 24.09 | 316.83 | 24.17 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 297.83 | 22.70 | 2.83 | 22.68 | 2.83 | 22.67 |
February | 113.00 | 22.87 | 39.83 | 23.15 | 0.00 | 23.15 |
March | 24.50 | 23.35 | 201.00 | 23.91 | 0.50 | 23.91 |
April | 5.17 | 28.29 | 299.50 | 24.08 | 4.83 | 24.15 |
May | 28.67 | 25.23 | 344.00 | 24.11 | 28.67 | 24.19 |
June | 108.33 | 24.22 | 336.00 | 24.05 | 108.33 | 24.08 |
July | 258.00 | 24.08 | 338.00 | 24.06 | 258.00 | 24.06 |
August | 286.00 | 24.01 | 348.00 | 23.99 | 286.00 | 24.00 |
September | 181.33 | 24.09 | 330.00 | 24.03 | 181.33 | 24.05 |
October | 10.17 | 25.93 | 334.83 | 24.05 | 10.17 | 24.10 |
November | 15.00 | 23.26 | 213.83 | 23.90 | 0.00 | 23.90 |
December | 158.83 | 22.83 | 6.17 | 22.87 | 0.00 | 22.87 |
Annual Sum or Average | 1486.83 | 23.60 | 2794.00 | 23.86 | 880.67 | 23.91 |
Minimum of Months | 5.17 | 22.70 | 2.83 | 22.68 | 0.00 | 22.67 |
Maximum of Months | 297.83 | 28.29 | 348.00 | 24.11 | 286.00 | 24.19 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 23.11611 | 40.96151 | 0.17102 | 6.80224 |
February | 448.00000 | 23.60279 | 42.17063 | 0.32939 | 7.83317 |
March | 497.00000 | 23.87101 | 42.35472 | 0.44824 | 9.35971 |
April | 479.00000 | 23.94736 | 42.19862 | 0.53130 | 11.05625 |
May | 496.00000 | 23.99180 | 51.33496 | -0.1752 | 5.91806 |
June | 481.00000 | 23.99236 | 57.79902 | -0.1108 | 5.56185 |
July | 495.00000 | 23.98566 | 64.76321 | -0.0716 | 5.42204 |
August | 497.00000 | 24.00077 | 66.45007 | -0.0671 | 5.42445 |
September | 479.00000 | 23.97860 | 63.21230 | -0.1178 | 5.53249 |
October | 496.00000 | 23.93791 | 48.56811 | 0.57279 | 11.98316 |
November | 480.00000 | 23.85846 | 42.24349 | 0.45007 | 9.36788 |
December | 496.00000 | 23.48554 | 39.65638 | 0.27789 | 7.35897 |
Annual Sum or Average | 5840.00000 | 23.81433 | 50.19429 | 0.18532 | 7.63043 |
Minimum of Months | 448.00000 | 23.11611 | 39.65638 | -0.1752 | 5.42204 |
Maximum of Months | 497.00000 | 24.00077 | 66.45007 | 0.57279 | 11.98316 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 23.45579 | 40.44630 | 0.24582 | 6.99756 |
February | 448.00000 | 23.73281 | 40.71434 | 0.35266 | 7.91857 |
March | 497.00000 | 23.89287 | 40.89727 | 0.43898 | 9.13564 |
April | 479.00000 | 23.95285 | 41.24459 | 0.50652 | 10.49502 |
May | 496.00000 | 23.99224 | 49.77203 | -0.2261 | 6.34275 |
June | 481.00000 | 23.99195 | 55.89265 | -0.1708 | 5.91411 |
July | 495.00000 | 23.98464 | 62.47169 | -0.1329 | 5.68546 |
August | 497.00000 | 23.99978 | 64.03285 | -0.1296 | 5.69322 |
September | 479.00000 | 23.97742 | 60.44688 | -0.1780 | 5.92305 |
October | 496.00000 | 23.94052 | 46.42315 | 0.53661 | 11.14314 |
November | 480.00000 | 23.87761 | 40.59330 | 0.43355 | 9.02344 |
December | 496.00000 | 23.67833 | 38.61717 | 0.31410 | 7.48065 |
Annual Sum or Average | 5840.00000 | 23.87337 | 48.51394 | 0.16456 | 7.64146 |
Minimum of Months | 448.00000 | 23.45579 | 38.61717 | -0.2261 | 5.68546 |
Maximum of Months | 497.00000 | 23.99978 | 64.03285 | 0.53661 | 11.14314 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 23.16673 | 39.52730 | 0.16964 | 6.64787 |
February | 336.00000 | 23.68911 | 40.71516 | 0.33737 | 7.91167 |
March | 379.00000 | 24.01170 | 41.13547 | 0.46434 | 9.74669 |
April | 360.00000 | 24.13885 | 41.21053 | 0.54892 | 11.72485 |
May | 375.00000 | 24.19060 | 50.87692 | -0.1507 | 6.43888 |
June | 366.00000 | 24.19818 | 57.68092 | -0.0891 | 6.22697 |
July | 369.00000 | 24.18327 | 65.50604 | -0.0455 | 6.07299 |
August | 379.00000 | 24.14883 | 67.68663 | -0.0522 | 5.88128 |
September | 360.00000 | 24.13888 | 63.99704 | -0.0980 | 5.93544 |
October | 371.00000 | 24.09078 | 47.90149 | 0.58510 | 12.45955 |
November | 360.00000 | 23.95430 | 40.81051 | 0.45335 | 9.45838 |
December | 369.00000 | 23.54685 | 37.88435 | 0.27845 | 7.26954 |
Annual Sum or Average | 4395.00000 | 23.95651 | 49.66270 | 0.19838 | 7.97496 |
Minimum of Months | 336.00000 | 23.16673 | 37.88435 | -0.1507 | 5.88128 |
Maximum of Months | 379.00000 | 24.19818 | 67.68663 | 0.58510 | 12.45955 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 23.09726 | 39.73519 | 0.14617 | 6.56118 |
February | 336.00000 | 23.66814 | 40.81548 | 0.32875 | 7.83231 |
March | 379.00000 | 24.00955 | 41.14872 | 0.46309 | 9.72591 |
April | 360.00000 | 24.13966 | 41.18597 | 0.55072 | 11.76894 |
May | 375.00000 | 24.19172 | 50.80386 | -0.1462 | 6.42111 |
June | 366.00000 | 24.19927 | 57.57598 | -0.0851 | 6.22449 |
July | 369.00000 | 24.18449 | 65.34575 | -0.0416 | 6.08097 |
August | 379.00000 | 24.14976 | 67.55211 | -0.0495 | 5.88583 |
September | 360.00000 | 24.13969 | 63.88018 | -0.0954 | 5.93328 |
October | 371.00000 | 24.09136 | 47.86189 | 0.58651 | 12.49590 |
November | 360.00000 | 23.95037 | 40.83987 | 0.45108 | 9.42176 |
December | 369.00000 | 23.51654 | 38.00227 | 0.26706 | 7.19404 |
Annual Sum or Average | 4395.00000 | 23.94654 | 49.64641 | 0.19625 | 7.95629 |
Minimum of Months | 336.00000 | 23.09726 | 38.00227 | -0.1462 | 5.88583 |
Maximum of Months | 379.00000 | 24.19927 | 67.55211 | 0.58651 | 12.49590 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 23.01575 | 39.97237 | 0.12175 | 6.47229 |
February | 336.00000 | 23.63505 | 40.98440 | 0.31717 | 7.72293 |
March | 379.00000 | 24.00168 | 41.25180 | 0.45821 | 9.63649 |
April | 360.00000 | 24.13624 | 41.23506 | 0.54791 | 11.69762 |
May | 375.00000 | 24.18917 | 50.87343 | -0.1481 | 6.41168 |
June | 366.00000 | 24.19676 | 57.67749 | -0.0866 | 6.20607 |
July | 369.00000 | 24.18218 | 65.46096 | -0.0422 | 6.06254 |
August | 379.00000 | 24.14709 | 67.70642 | -0.0506 | 5.86741 |
September | 360.00000 | 24.13692 | 64.03863 | -0.0971 | 5.92158 |
October | 371.00000 | 24.08829 | 47.96142 | 0.58449 | 12.44092 |
November | 360.00000 | 23.94204 | 40.93899 | 0.44652 | 9.34193 |
December | 369.00000 | 23.47673 | 38.16324 | 0.25409 | 7.11062 |
Annual Sum or Average | 4395.00000 | 23.93081 | 49.77264 | 0.19045 | 7.90225 |
Minimum of Months | 336.00000 | 23.01575 | 38.16324 | -0.1481 | 5.86741 |
Maximum of Months | 379.00000 | 24.19676 | 67.70642 | 0.58449 | 12.44092 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.02299 | 41.31869 | 0.11589 | 6.33090 |
February | 308.00000 | 23.65354 | 41.91787 | 0.31897 | 7.62060 |
March | 348.00000 | 23.92038 | 42.07825 | 0.44783 | 9.37715 |
April | 330.00000 | 23.99453 | 42.20364 | 0.53456 | 11.26954 |
May | 344.00000 | 24.01096 | 51.95547 | -0.1734 | 6.16129 |
June | 336.00000 | 23.99645 | 58.71018 | -0.1177 | 5.78193 |
July | 338.00000 | 24.03062 | 66.29990 | -0.0638 | 5.77735 |
August | 348.00000 | 23.98084 | 68.54007 | -0.0778 | 5.56126 |
September | 330.00000 | 23.99735 | 64.76303 | -0.1196 | 5.75659 |
October | 340.00000 | 23.98384 | 48.66899 | 0.57665 | 12.17649 |
November | 330.00000 | 23.91261 | 41.60476 | 0.44592 | 9.27452 |
December | 338.00000 | 23.50665 | 39.51350 | 0.25971 | 7.07041 |
Annual Sum or Average | 4030.00000 | 23.83521 | 50.71824 | 0.17707 | 7.67300 |
Minimum of Months | 308.00000 | 23.02299 | 39.51350 | -0.1734 | 5.56126 |
Maximum of Months | 348.00000 | 24.03062 | 68.54007 | 0.57665 | 12.17649 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.01802 | 41.20411 | 0.10678 | 6.28627 |
February | 308.00000 | 23.65651 | 41.82850 | 0.30955 | 7.48832 |
March | 348.00000 | 23.92107 | 42.01810 | 0.43427 | 9.11708 |
April | 330.00000 | 23.99368 | 42.10659 | 0.51551 | 10.83982 |
May | 344.00000 | 24.01015 | 51.87755 | -0.2032 | 6.38620 |
June | 336.00000 | 23.99550 | 58.69527 | -0.1481 | 5.94437 |
July | 338.00000 | 24.02940 | 66.39791 | -0.0920 | 5.86037 |
August | 348.00000 | 23.97995 | 68.69572 | -0.1046 | 5.66062 |
September | 330.00000 | 23.99616 | 64.85521 | -0.1454 | 5.89220 |
October | 340.00000 | 23.98353 | 48.64783 | 0.55893 | 11.74644 |
November | 330.00000 | 23.91363 | 41.55053 | 0.43287 | 9.02669 |
December | 338.00000 | 23.51496 | 39.39514 | 0.25268 | 6.99069 |
Annual Sum or Average | 4030.00000 | 23.83534 | 50.69376 | 0.15783 | 7.59761 |
Minimum of Months | 308.00000 | 23.01802 | 39.39514 | -0.2032 | 5.66062 |
Maximum of Months | 348.00000 | 24.02940 | 68.69572 | 0.55893 | 11.74644 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.98947 | 41.28467 | 0.09740 | 6.25628 |
February | 308.00000 | 23.64436 | 41.89481 | 0.30394 | 7.43663 |
March | 348.00000 | 23.91923 | 42.05490 | 0.43158 | 9.07087 |
April | 330.00000 | 23.99334 | 42.12468 | 0.51356 | 10.79673 |
May | 344.00000 | 24.00997 | 51.90784 | -0.2052 | 6.40247 |
June | 336.00000 | 23.99523 | 58.73879 | -0.1500 | 5.95465 |
July | 338.00000 | 24.02912 | 66.45056 | -0.0936 | 5.86417 |
August | 348.00000 | 23.97978 | 68.75355 | -0.1062 | 5.66565 |
September | 330.00000 | 23.99584 | 64.91130 | -0.1471 | 5.90016 |
October | 340.00000 | 23.98318 | 48.68200 | 0.55744 | 11.71049 |
November | 330.00000 | 23.91223 | 41.58311 | 0.43063 | 8.98763 |
December | 338.00000 | 23.50004 | 39.45452 | 0.24692 | 6.95293 |
Annual Sum or Average | 4030.00000 | 23.83031 | 50.74103 | 0.15468 | 7.57786 |
Minimum of Months | 308.00000 | 22.98947 | 39.45452 | -0.2052 | 5.66565 |
Maximum of Months | 348.00000 | 24.02912 | 68.75355 | 0.55744 | 11.71049 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.91334 | 41.49722 | 0.07495 | 6.21630 |
February | 308.00000 | 23.60284 | 42.09846 | 0.28905 | 7.33033 |
March | 348.00000 | 23.91206 | 42.15860 | 0.42688 | 9.00287 |
April | 330.00000 | 23.99293 | 42.14759 | 0.51406 | 10.81029 |
May | 344.00000 | 24.01007 | 51.90413 | -0.2009 | 6.36820 |
June | 336.00000 | 23.99532 | 58.70817 | -0.1451 | 5.92653 |
July | 338.00000 | 24.02942 | 66.36270 | -0.0881 | 5.85034 |
August | 348.00000 | 23.97998 | 68.64973 | -0.1009 | 5.64697 |
September | 330.00000 | 23.99596 | 64.85560 | -0.1424 | 5.87562 |
October | 340.00000 | 23.98317 | 48.69917 | 0.55931 | 11.75684 |
November | 330.00000 | 23.90743 | 41.66034 | 0.42813 | 8.95270 |
December | 338.00000 | 23.45133 | 39.63387 | 0.23169 | 6.87913 |
Annual Sum or Average | 4030.00000 | 23.81565 | 50.78441 | 0.15204 | 7.54641 |
Minimum of Months | 308.00000 | 22.91334 | 39.63387 | -0.2009 | 5.64697 |
Maximum of Months | 348.00000 | 24.02942 | 68.64973 | 0.55931 | 11.75684 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.84445 | 41.68367 | 0.04965 | 6.26943 |
February | 308.00000 | 23.52917 | 42.39071 | 0.26745 | 7.29091 |
March | 348.00000 | 23.89332 | 42.37541 | 0.43077 | 9.16619 |
April | 330.00000 | 23.99657 | 42.14278 | 0.54671 | 11.58181 |
May | 344.00000 | 24.01373 | 51.64206 | -0.1377 | 5.97695 |
June | 336.00000 | 23.99876 | 58.09795 | -0.0813 | 5.67689 |
July | 338.00000 | 24.03631 | 65.24261 | -0.0275 | 5.80952 |
August | 348.00000 | 23.98564 | 67.20207 | -0.0423 | 5.54816 |
September | 330.00000 | 24.00302 | 63.72609 | -0.0873 | 5.68995 |
October | 340.00000 | 23.98980 | 48.38978 | 0.59448 | 12.65711 |
November | 330.00000 | 23.90112 | 41.71888 | 0.44216 | 9.26396 |
December | 338.00000 | 23.38563 | 39.79103 | 0.21308 | 6.88670 |
Annual Sum or Average | 4030.00000 | 23.79967 | 50.44799 | 0.17920 | 7.64586 |
Minimum of Months | 308.00000 | 22.84445 | 39.79103 | -0.1377 | 5.54816 |
Maximum of Months | 348.00000 | 24.03631 | 67.20207 | 0.59448 | 12.65711 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.219419E+10 | 0.608086E+09 | 194.17 | 0.195761E+10 | 0.236581E+09 | 0.00 | 0.36 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 | 9407.13 | 12-JAN-15:00 | 8815.87 | 12-JAN-15:00 | 1640.80 | 14-JAN-14:00 | 2576.57 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.781313E+10 | 0.213611E+10 | 324.17 | 0.677519E+10 | 0.103794E+10 | 0.00 | 0.57 | 22-FEB-15:00 | 0.00 | 01-FEB-00:05 | 15779.03 | 22-FEB-15:00 | 14451.76 | 22-FEB-15:00 | 4118.22 | 25-FEB-18:05 | 4326.18 | 22-FEB-15:00 | 0.00 | 01-FEB-00:05 |
March | 0.196667E+11 | 0.542692E+10 | 460.18 | 0.169364E+11 | 0.273031E+10 | 0.00 | 1.00 | 11-MAR-09:02 | 0.00 | 01-MAR-00:10 | 67238.93 | 11-MAR-09:02 | 53604.79 | 11-MAR-09:02 | 13634.14 | 11-MAR-09:02 | 15403.92 | 11-MAR-09:02 | 0.00 | 01-MAR-00:10 |
April | 0.320043E+11 | 0.930093E+10 | 464.13 | 0.286976E+11 | 0.330665E+10 | 0.00 | 1.00 | 01-APR-08:62 | 0.00 | 01-APR-00:05 | 69270.24 | 26-APR-08:61 | 63196.87 | 08-APR-08:62 | 21012.45 | 26-APR-08:02 | 16476.74 | 27-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.464863E+11 | 0.135223E+11 | 497.81 | 0.371787E+11 | 0.930764E+10 | 0.00 | 1.00 | 01-MAY-08:61 | 0.00 | 01-MAY-00:10 | 73073.29 | 24-MAY-08:61 | 62593.69 | 06-MAY-08:61 | 35098.41 | 24-MAY-08:03 | 17649.25 | 04-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.527270E+11 | 0.147391E+11 | 487.46 | 0.371935E+11 | 0.155334E+11 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 74449.65 | 26-JUN-08:61 | 59862.11 | 07-JUN-08:61 | 40485.35 | 26-JUN-08:04 | 17870.82 | 12-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.596715E+11 | 0.152726E+11 | 502.15 | 0.348255E+11 | 0.248460E+11 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:03 | 74544.78 | 18-JUL-08:61 | 49292.10 | 05-JUL-07:01 | 42174.75 | 25-JUL-08:04 | 17488.47 | 07-JUL-08:61 | 0.00 | 01-JUL-00:03 |
August | 0.591073E+11 | 0.145870E+11 | 500.55 | 0.322316E+11 | 0.268757E+11 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 74630.39 | 11-AUG-08:61 | 45880.48 | 06-AUG-07:01 | 45533.97 | 12-AUG-08:13 | 16714.62 | 07-AUG-08:02 | 0.00 | 01-AUG-00:10 |
September | 0.488762E+11 | 0.122343E+11 | 476.84 | 0.288023E+11 | 0.200739E+11 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:03 | 74377.30 | 06-SEP-08:61 | 49999.76 | 26-SEP-08:61 | 40176.08 | 09-SEP-08:03 | 16352.31 | 22-SEP-08:02 | 0.00 | 01-SEP-00:03 |
October | 0.316842E+11 | 0.850440E+10 | 474.99 | 0.249466E+11 | 0.673764E+10 | 0.00 | 1.00 | 01-OCT-07:02 | 0.00 | 01-OCT-00:10 | 71420.03 | 12-OCT-08:62 | 55531.71 | 16-OCT-08:62 | 31872.77 | 12-OCT-08:62 | 15954.17 | 04-OCT-08:61 | 0.00 | 01-OCT-00:10 |
November | 0.166291E+11 | 0.450598E+10 | 439.42 | 0.142545E+11 | 0.237464E+10 | 0.00 | 0.95 | 09-NOV-09:03 | 0.00 | 01-NOV-00:10 | 31351.61 | 09-NOV-09:03 | 22064.68 | 09-NOV-09:03 | 9286.93 | 09-NOV-09:03 | 6979.22 | 09-NOV-09:03 | 0.00 | 01-NOV-00:10 |
December | 0.470759E+10 | 0.129372E+10 | 297.25 | 0.407390E+10 | 0.633695E+09 | 0.00 | 0.45 | 03-DEC-14:00 | 0.00 | 01-DEC-00:10 | 12027.41 | 28-DEC-15:00 | 11227.75 | 03-DEC-14:00 | 1864.45 | 16-DEC-14:00 | 3261.64 | 28-DEC-15:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.381568E+12 | 0.102132E+12 | 5119.12 | 0.267873E+12 | 0.113694E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.219419E+10 | 0.608086E+09 | 194.17 | 0.195761E+10 | 0.236581E+09 | 0.00 | 0.36 | 0.00 | 9407.13 | 8815.87 | 1640.80 | 2576.57 | 0.00 | |||||||
Maximum of Months | 0.596715E+11 | 0.152726E+11 | 502.15 | 0.371935E+11 | 0.268757E+11 | 0.00 | 1.00 | 0.00 | 74630.39 | 63196.87 | 45533.97 | 17870.82 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.211463E+10 | 0.573529E+09 | 319.53 | 0.183890E+10 | 0.275725E+09 | 0.00 | 0.39 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 | 5158.51 | 12-JAN-15:00 | 4847.05 | 12-JAN-15:00 | 1409.01 | 16-JAN-18:20 | 1378.90 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.498943E+10 | 0.133255E+10 | 377.33 | 0.432324E+10 | 0.666185E+09 | 0.00 | 0.59 | 22-FEB-15:00 | 0.00 | 01-FEB-00:05 | 8305.84 | 22-FEB-14:50 | 7616.68 | 22-FEB-15:00 | 2158.05 | 25-FEB-18:05 | 2227.32 | 22-FEB-15:00 | 0.00 | 01-FEB-00:05 |
March | 0.105088E+11 | 0.284038E+10 | 468.04 | 0.914164E+10 | 0.136720E+10 | 0.00 | 1.00 | 11-MAR-09:02 | 0.00 | 01-MAR-00:10 | 33976.62 | 11-MAR-09:02 | 28619.90 | 11-MAR-09:02 | 5663.41 | 29-MAR-08:62 | 7687.79 | 11-MAR-09:02 | 0.00 | 01-MAR-00:10 |
April | 0.157934E+11 | 0.453184E+10 | 464.27 | 0.142597E+11 | 0.153363E+10 | 0.00 | 1.00 | 01-APR-08:62 | 0.00 | 01-APR-00:05 | 34879.55 | 26-APR-08:61 | 32412.54 | 08-APR-08:62 | 8924.46 | 26-APR-08:02 | 8239.77 | 27-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.224898E+11 | 0.649939E+10 | 498.35 | 0.181879E+11 | 0.430189E+10 | 0.00 | 1.00 | 01-MAY-08:61 | 0.00 | 01-MAY-00:10 | 36736.89 | 24-MAY-08:61 | 32019.21 | 06-MAY-08:61 | 15612.19 | 24-MAY-08:03 | 8846.15 | 04-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.251954E+11 | 0.701466E+10 | 487.99 | 0.180270E+11 | 0.716842E+10 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 37349.04 | 24-JUN-08:61 | 31079.59 | 07-JUN-08:61 | 17814.87 | 26-JUN-08:03 | 8934.63 | 12-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.283989E+11 | 0.724473E+10 | 501.80 | 0.169247E+11 | 0.114742E+11 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:03 | 37713.92 | 18-JUL-08:61 | 27583.00 | 05-JUL-07:01 | 19480.99 | 18-JUL-08:04 | 8771.51 | 05-JUL-08:61 | 0.00 | 01-JUL-00:03 |
August | 0.281766E+11 | 0.692134E+10 | 500.25 | 0.157146E+11 | 0.124620E+11 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 38022.48 | 12-AUG-08:61 | 26351.22 | 06-AUG-07:01 | 21205.16 | 12-AUG-08:13 | 8386.90 | 07-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.233225E+11 | 0.580636E+10 | 476.20 | 0.141026E+11 | 0.921991E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:03 | 37282.16 | 06-SEP-08:61 | 27156.05 | 26-SEP-08:61 | 17815.60 | 06-SEP-08:04 | 8199.03 | 22-SEP-08:61 | 0.00 | 01-SEP-00:03 |
October | 0.157529E+11 | 0.417341E+10 | 475.66 | 0.126182E+11 | 0.313471E+10 | 0.00 | 1.00 | 01-OCT-07:02 | 0.00 | 01-OCT-00:10 | 35933.08 | 12-OCT-08:62 | 29907.07 | 16-OCT-08:62 | 13898.44 | 12-OCT-08:62 | 7977.50 | 04-OCT-08:61 | 0.00 | 01-OCT-00:10 |
November | 0.918339E+10 | 0.243752E+10 | 451.92 | 0.794232E+10 | 0.124107E+10 | 0.00 | 0.96 | 09-NOV-09:03 | 0.00 | 01-NOV-00:10 | 16181.10 | 09-NOV-09:03 | 12280.38 | 09-NOV-09:03 | 3900.72 | 09-NOV-09:03 | 3533.43 | 09-NOV-09:03 | 0.00 | 01-NOV-00:10 |
December | 0.366932E+10 | 0.986580E+09 | 395.83 | 0.314529E+10 | 0.524029E+09 | 0.00 | 0.47 | 03-DEC-14:00 | 0.00 | 01-DEC-01:05 | 6448.94 | 03-DEC-14:00 | 6124.25 | 03-DEC-14:00 | 1334.32 | 10-DEC-18:05 | 1709.39 | 03-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.189595E+12 | 0.503623E+11 | 5417.17 | 0.136226E+12 | 0.533689E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.211463E+10 | 0.573529E+09 | 319.53 | 0.183890E+10 | 0.275725E+09 | 0.00 | 0.39 | 0.00 | 5158.51 | 4847.05 | 1334.32 | 1378.90 | 0.00 | |||||||
Maximum of Months | 0.283989E+11 | 0.724473E+10 | 501.80 | 0.181879E+11 | 0.124620E+11 | 0.00 | 1.00 | 0.00 | 38022.48 | 32412.54 | 21205.16 | 8934.63 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.879478E+09 | 0.239537E+09 | 146.25 | 0.798950E+09 | 80527876.22 | 0.00 | 0.35 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 | 4593.19 | 12-JAN-15:00 | 4325.60 | 12-JAN-15:00 | 852.27 | 14-JAN-14:00 | 1240.60 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.317559E+10 | 0.854673E+09 | 233.33 | 0.280840E+10 | 0.367194E+09 | 0.00 | 0.57 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 | 7905.87 | 22-FEB-14:00 | 7262.99 | 22-FEB-14:00 | 1776.11 | 25-FEB-16:30 | 2130.91 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 |
March | 0.794985E+10 | 0.216146E+10 | 332.60 | 0.696161E+10 | 0.988238E+09 | 0.00 | 1.00 | 11-MAR-08:62 | 0.00 | 01-MAR-00:10 | 34680.63 | 11-MAR-08:62 | 25859.42 | 11-MAR-08:62 | 8821.21 | 11-MAR-08:62 | 7609.89 | 11-MAR-08:62 | 0.00 | 01-MAR-00:10 |
April | 0.126298E+11 | 0.360250E+10 | 333.25 | 0.114149E+11 | 0.121490E+10 | 0.00 | 1.00 | 01-APR-07:03 | 0.00 | 01-APR-00:05 | 35360.26 | 26-APR-07:01 | 32511.96 | 30-APR-08:61 | 11193.79 | 26-APR-07:03 | 8218.79 | 16-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.186358E+11 | 0.533159E+10 | 372.96 | 0.149788E+11 | 0.365695E+10 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 37157.47 | 24-MAY-07:01 | 32156.07 | 06-MAY-07:01 | 17514.76 | 24-MAY-07:02 | 8648.84 | 04-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.210087E+11 | 0.574980E+10 | 366.91 | 0.147933E+11 | 0.621541E+10 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 38015.85 | 25-JUN-08:61 | 30187.94 | 07-JUN-07:01 | 22569.32 | 26-JUN-07:04 | 8753.19 | 12-JUN-07:01 | 0.00 | 01-JUN-00:10 |
July | 0.232944E+11 | 0.581316E+10 | 369.95 | 0.134206E+11 | 0.987377E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 38060.61 | 28-JUL-07:01 | 24574.71 | 05-JUL-06:02 | 22498.23 | 23-JUL-08:04 | 8668.22 | 02-JUL-08:04 | 0.00 | 01-JUL-00:03 |
August | 0.235762E+11 | 0.568451E+10 | 377.04 | 0.126921E+11 | 0.108841E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 38127.72 | 21-AUG-07:03 | 21293.11 | 03-AUG-07:01 | 24086.71 | 21-AUG-07:04 | 8289.11 | 08-AUG-07:03 | 0.00 | 01-AUG-00:10 |
September | 0.190452E+11 | 0.465317E+10 | 347.84 | 0.111572E+11 | 0.788801E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 | 38162.24 | 09-SEP-07:01 | 23791.06 | 26-SEP-07:01 | 23954.93 | 11-SEP-07:04 | 8085.20 | 24-SEP-08:04 | 0.00 | 01-SEP-00:03 |
October | 0.124231E+11 | 0.328634E+10 | 336.64 | 0.991347E+10 | 0.250962E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 36398.96 | 12-OCT-07:02 | 28213.89 | 16-OCT-07:02 | 16424.47 | 12-OCT-07:02 | 7880.97 | 04-OCT-07:01 | 0.00 | 01-OCT-00:10 |
November | 0.678828E+10 | 0.181590E+10 | 311.67 | 0.595976E+10 | 0.828515E+09 | 0.00 | 0.74 | 04-NOV-13:00 | 0.00 | 01-NOV-00:10 | 10898.92 | 09-NOV-13:40 | 9998.90 | 04-NOV-13:00 | 2344.15 | 09-NOV-08:65 | 2925.35 | 04-NOV-13:00 | 0.00 | 01-NOV-00:10 |
December | 0.198253E+10 | 0.536143E+09 | 234.00 | 0.175228E+10 | 0.230258E+09 | 0.00 | 0.44 | 02-DEC-14:00 | 0.00 | 01-DEC-00:10 | 5880.20 | 28-DEC-14:00 | 5769.89 | 02-DEC-14:00 | 958.07 | 16-DEC-14:00 | 1576.68 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.151389E+12 | 0.397288E+11 | 3762.42 | 0.106651E+12 | 0.447375E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.879478E+09 | 0.239537E+09 | 146.25 | 0.798950E+09 | 80527876.22 | 0.00 | 0.35 | 0.00 | 4593.19 | 4325.60 | 852.27 | 1240.60 | 0.00 | |||||||
Maximum of Months | 0.235762E+11 | 0.581316E+10 | 377.04 | 0.149788E+11 | 0.108841E+11 | 0.00 | 1.00 | 0.00 | 38162.24 | 32511.96 | 24086.71 | 8753.19 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.784225E+09 | 0.213989E+09 | 136.00 | 0.711790E+09 | 72435003.36 | 0.00 | 0.34 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 | 4449.80 | 12-JAN-15:00 | 4189.48 | 12-JAN-15:00 | 832.84 | 14-JAN-14:00 | 1205.36 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.308462E+10 | 0.831633E+09 | 231.75 | 0.272825E+10 | 0.356375E+09 | 0.00 | 0.56 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 | 7838.33 | 22-FEB-14:00 | 7200.14 | 22-FEB-14:00 | 1761.60 | 25-FEB-16:30 | 2115.78 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 |
March | 0.792739E+10 | 0.215651E+10 | 331.43 | 0.694151E+10 | 0.985878E+09 | 0.00 | 1.00 | 11-MAR-08:62 | 0.00 | 01-MAR-00:10 | 34745.00 | 11-MAR-08:62 | 25913.38 | 11-MAR-08:62 | 8831.62 | 11-MAR-08:62 | 7623.72 | 11-MAR-08:62 | 0.00 | 01-MAR-00:10 |
April | 0.126890E+11 | 0.361796E+10 | 333.92 | 0.114693E+11 | 0.121974E+10 | 0.00 | 1.00 | 01-APR-07:03 | 0.00 | 01-APR-00:05 | 35428.92 | 26-APR-07:01 | 32592.06 | 30-APR-08:61 | 11180.55 | 26-APR-07:03 | 8232.77 | 16-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.187752E+11 | 0.536885E+10 | 373.64 | 0.151012E+11 | 0.367399E+10 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 37217.19 | 24-MAY-07:01 | 32220.01 | 06-MAY-07:01 | 17495.03 | 24-MAY-07:02 | 8663.72 | 04-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.211521E+11 | 0.578724E+10 | 368.04 | 0.149113E+11 | 0.624082E+10 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 38083.44 | 25-JUN-08:61 | 30255.58 | 07-JUN-07:01 | 22458.56 | 26-JUN-07:04 | 8767.79 | 12-JUN-07:01 | 0.00 | 01-JUN-00:10 |
July | 0.234615E+11 | 0.585453E+10 | 370.09 | 0.135477E+11 | 0.991383E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 38128.27 | 28-JUL-07:01 | 24888.79 | 05-JUL-06:02 | 22393.16 | 23-JUL-08:04 | 8684.44 | 02-JUL-08:04 | 0.00 | 01-JUL-00:03 |
August | 0.237035E+11 | 0.571550E+10 | 376.96 | 0.127852E+11 | 0.109183E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 38195.50 | 21-AUG-07:04 | 21387.96 | 03-AUG-07:01 | 24020.44 | 21-AUG-07:04 | 8304.37 | 08-AUG-07:03 | 0.00 | 01-AUG-00:10 |
September | 0.191497E+11 | 0.467808E+10 | 347.72 | 0.112342E+11 | 0.791548E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 | 38230.09 | 09-SEP-07:01 | 23897.68 | 26-SEP-07:01 | 23924.84 | 11-SEP-07:04 | 8100.03 | 24-SEP-08:04 | 0.00 | 01-SEP-00:03 |
October | 0.124801E+11 | 0.330047E+10 | 336.85 | 0.996234E+10 | 0.251773E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 36466.27 | 12-OCT-07:02 | 28337.23 | 16-OCT-07:02 | 16422.50 | 12-OCT-07:02 | 7894.61 | 04-OCT-07:01 | 0.00 | 01-OCT-00:10 |
November | 0.674584E+10 | 0.180603E+10 | 311.17 | 0.592186E+10 | 0.823976E+09 | 0.00 | 0.74 | 04-NOV-13:00 | 0.00 | 01-NOV-00:10 | 10869.97 | 09-NOV-13:40 | 9986.93 | 04-NOV-13:00 | 2292.49 | 09-NOV-08:65 | 2923.47 | 04-NOV-13:00 | 0.00 | 01-NOV-00:10 |
December | 0.186978E+10 | 0.506652E+09 | 229.50 | 0.165311E+10 | 0.216668E+09 | 0.00 | 0.43 | 02-DEC-14:00 | 0.00 | 01-DEC-00:10 | 5746.56 | 28-DEC-14:00 | 5702.45 | 02-DEC-14:00 | 940.71 | 16-DEC-14:00 | 1544.94 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.151823E+12 | 0.398374E+11 | 3747.05 | 0.106968E+12 | 0.448552E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.784225E+09 | 0.213989E+09 | 136.00 | 0.711790E+09 | 72435003.36 | 0.00 | 0.34 | 0.00 | 4449.80 | 4189.48 | 832.84 | 1205.36 | 0.00 | |||||||
Maximum of Months | 0.237035E+11 | 0.585453E+10 | 376.96 | 0.151012E+11 | 0.109183E+11 | 0.00 | 1.00 | 0.00 | 38230.09 | 32592.06 | 24020.44 | 8767.79 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.673483E+09 | 0.184229E+09 | 123.50 | 0.610206E+09 | 63276752.42 | 0.00 | 0.33 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 | 4248.69 | 12-JAN-15:00 | 3997.54 | 12-JAN-15:00 | 800.38 | 14-JAN-14:00 | 1155.14 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.292797E+10 | 0.791535E+09 | 225.92 | 0.259056E+10 | 0.337414E+09 | 0.00 | 0.55 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 | 7698.00 | 22-FEB-14:00 | 7067.52 | 22-FEB-14:00 | 1713.46 | 25-FEB-16:30 | 2082.57 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 |
March | 0.774957E+10 | 0.211269E+10 | 329.27 | 0.678351E+10 | 0.966069E+09 | 0.00 | 1.00 | 11-MAR-08:62 | 0.00 | 01-MAR-00:10 | 34664.60 | 11-MAR-08:62 | 25748.63 | 11-MAR-08:62 | 8915.97 | 11-MAR-08:62 | 7607.86 | 11-MAR-08:62 | 0.00 | 01-MAR-00:10 |
April | 0.125553E+11 | 0.358435E+10 | 332.78 | 0.113449E+11 | 0.121047E+10 | 0.00 | 1.00 | 01-APR-07:03 | 0.00 | 01-APR-00:05 | 35348.12 | 26-APR-07:01 | 32517.19 | 30-APR-08:61 | 11244.99 | 26-APR-07:03 | 8218.10 | 16-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.186583E+11 | 0.533712E+10 | 372.14 | 0.150002E+11 | 0.365807E+10 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 37150.62 | 24-MAY-07:01 | 32153.20 | 06-MAY-07:01 | 17543.27 | 24-MAY-07:02 | 8648.39 | 04-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.210296E+11 | 0.575492E+10 | 367.22 | 0.148123E+11 | 0.621728E+10 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 38013.03 | 25-JUN-08:61 | 30185.95 | 07-JUN-07:01 | 22494.30 | 26-JUN-07:04 | 8751.63 | 12-JUN-07:01 | 0.00 | 01-JUN-00:10 |
July | 0.233536E+11 | 0.582739E+10 | 370.10 | 0.134678E+11 | 0.988584E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 38057.79 | 28-JUL-07:01 | 24813.22 | 05-JUL-06:02 | 22467.09 | 23-JUL-08:04 | 8668.09 | 02-JUL-08:04 | 0.00 | 01-JUL-00:03 |
August | 0.235639E+11 | 0.568147E+10 | 376.72 | 0.126850E+11 | 0.108789E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 38124.89 | 21-AUG-07:04 | 21263.33 | 03-AUG-07:01 | 24048.44 | 21-AUG-07:04 | 8288.73 | 08-AUG-07:03 | 0.00 | 01-AUG-00:10 |
September | 0.190115E+11 | 0.464510E+10 | 346.82 | 0.111326E+11 | 0.787889E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 | 38159.42 | 09-SEP-07:01 | 23800.71 | 26-SEP-07:01 | 23965.77 | 11-SEP-07:04 | 8084.69 | 24-SEP-08:04 | 0.00 | 01-SEP-00:03 |
October | 0.123450E+11 | 0.326892E+10 | 336.26 | 0.984785E+10 | 0.249714E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 36391.40 | 12-OCT-07:02 | 28229.57 | 16-OCT-07:02 | 16478.86 | 12-OCT-07:02 | 7880.54 | 04-OCT-07:01 | 0.00 | 01-OCT-00:10 |
November | 0.658829E+10 | 0.176743E+10 | 308.92 | 0.578131E+10 | 0.806982E+09 | 0.00 | 0.73 | 04-NOV-13:00 | 0.00 | 01-NOV-00:10 | 10753.21 | 09-NOV-13:40 | 9869.97 | 04-NOV-14:00 | 2076.87 | 08-NOV-18:00 | 2894.56 | 04-NOV-13:00 | 0.00 | 01-NOV-00:10 |
December | 0.170903E+10 | 0.464222E+09 | 221.58 | 0.151168E+10 | 0.197345E+09 | 0.00 | 0.42 | 02-DEC-14:00 | 0.00 | 01-DEC-00:10 | 5574.92 | 02-DEC-14:00 | 5574.92 | 02-DEC-14:00 | 913.31 | 16-DEC-14:00 | 1499.66 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.150165E+12 | 0.394193E+11 | 3711.23 | 0.105568E+12 | 0.445977E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.673483E+09 | 0.184229E+09 | 123.50 | 0.610206E+09 | 63276752.42 | 0.00 | 0.33 | 0.00 | 4248.69 | 3997.54 | 800.38 | 1155.14 | 0.00 | |||||||
Maximum of Months | 0.235639E+11 | 0.582739E+10 | 376.72 | 0.150002E+11 | 0.108789E+11 | 0.00 | 1.00 | 0.00 | 38159.42 | 32517.19 | 24048.44 | 8751.63 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.122581E+10 | 0.340847E+09 | 116.33 | 0.109116E+10 | 0.134655E+09 | 0.00 | 0.34 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 | 8229.33 | 12-JAN-15:10 | 7567.61 | 12-JAN-15:10 | 1649.96 | 14-JAN-15:10 | 2267.81 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 |
February | 0.539843E+10 | 0.148421E+10 | 226.92 | 0.469735E+10 | 0.701081E+09 | 0.00 | 0.57 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 | 14873.70 | 22-FEB-14:00 | 13375.75 | 22-FEB-14:00 | 3858.19 | 25-FEB-16:00 | 4070.96 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 |
March | 0.145666E+11 | 0.403465E+10 | 326.46 | 0.125781E+11 | 0.198850E+10 | 0.00 | 1.00 | 11-MAR-09:02 | 0.00 | 01-MAR-00:10 | 63965.98 | 11-MAR-09:02 | 49477.33 | 11-MAR-09:02 | 14488.65 | 11-MAR-09:02 | 14618.69 | 11-MAR-09:02 | 0.00 | 01-MAR-00:10 |
April | 0.234206E+11 | 0.680408E+10 | 325.89 | 0.210757E+11 | 0.234486E+10 | 0.00 | 1.00 | 01-APR-08:62 | 0.00 | 01-APR-00:05 | 65167.47 | 26-APR-08:61 | 59795.66 | 08-APR-08:62 | 18657.47 | 24-APR-08:62 | 16081.07 | 16-APR-09:01 | 0.00 | 01-APR-00:05 |
May | 0.349445E+11 | 0.101761E+11 | 363.72 | 0.279357E+11 | 0.700884E+10 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 68824.35 | 24-MAY-08:61 | 59985.28 | 29-MAY-08:61 | 31987.17 | 24-MAY-08:03 | 16731.90 | 04-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.393709E+11 | 0.109801E+11 | 358.02 | 0.276066E+11 | 0.117642E+11 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 70528.48 | 25-JUN-09:03 | 56806.85 | 07-JUN-08:61 | 41479.54 | 26-JUN-08:04 | 16897.22 | 12-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.434279E+11 | 0.110231E+11 | 358.20 | 0.248308E+11 | 0.185972E+11 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:03 | 70600.95 | 28-JUL-08:61 | 49513.14 | 07-JUL-07:01 | 41162.39 | 23-JUL-09:04 | 16558.99 | 05-JUL-08:61 | 0.00 | 01-JUL-00:03 |
August | 0.441233E+11 | 0.108100E+11 | 367.35 | 0.234806E+11 | 0.206427E+11 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 70834.86 | 21-AUG-08:04 | 41611.08 | 08-AUG-08:61 | 44505.60 | 21-AUG-08:05 | 15835.61 | 06-AUG-09:04 | 0.00 | 01-AUG-00:10 |
September | 0.353562E+11 | 0.877720E+10 | 336.99 | 0.205215E+11 | 0.148347E+11 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:03 | 70906.51 | 04-SEP-09:01 | 47250.62 | 26-SEP-08:61 | 44026.47 | 11-SEP-08:05 | 15559.39 | 24-SEP-09:04 | 0.00 | 01-SEP-00:03 |
October | 0.231285E+11 | 0.620950E+10 | 329.09 | 0.182345E+11 | 0.489393E+10 | 0.00 | 1.00 | 01-OCT-09:01 | 0.00 | 01-OCT-00:10 | 67550.67 | 12-OCT-08:62 | 53802.43 | 15-OCT-09:01 | 30425.36 | 12-OCT-08:62 | 15097.43 | 04-OCT-08:61 | 0.00 | 01-OCT-00:10 |
November | 0.122664E+11 | 0.334193E+10 | 311.06 | 0.105878E+11 | 0.167857E+10 | 0.00 | 0.99 | 11-NOV-10:03 | 0.00 | 01-NOV-00:10 | 30794.07 | 11-NOV-10:03 | 23772.70 | 11-NOV-10:03 | 7938.67 | 09-NOV-09:03 | 6877.75 | 11-NOV-10:03 | 0.00 | 01-NOV-00:10 |
December | 0.303298E+10 | 0.836959E+09 | 205.83 | 0.263465E+10 | 0.398332E+09 | 0.00 | 0.42 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 | 10702.98 | 28-DEC-14:00 | 10185.70 | 02-DEC-14:10 | 1849.92 | 16-DEC-15:10 | 2926.87 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.280262E+12 | 0.748187E+11 | 3625.85 | 0.195275E+12 | 0.849875E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.122581E+10 | 0.340847E+09 | 116.33 | 0.109116E+10 | 0.134655E+09 | 0.00 | 0.34 | 0.00 | 8229.33 | 7567.61 | 1649.96 | 2267.81 | 0.00 | |||||||
Maximum of Months | 0.441233E+11 | 0.110231E+11 | 367.35 | 0.279357E+11 | 0.206427E+11 | 0.00 | 1.00 | 0.00 | 70906.51 | 59985.28 | 44505.60 | 16897.22 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.611341E+09 | 0.167158E+09 | 112.67 | 0.545966E+09 | 65375383.95 | 0.00 | 0.33 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 | 4278.55 | 12-JAN-15:10 | 3953.71 | 12-JAN-15:10 | 832.88 | 14-JAN-15:10 | 1159.36 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 |
February | 0.280166E+10 | 0.757383E+09 | 227.08 | 0.244844E+10 | 0.353221E+09 | 0.00 | 0.57 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 | 7766.56 | 22-FEB-14:00 | 7013.29 | 22-FEB-15:10 | 1969.11 | 25-FEB-16:00 | 2090.23 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 |
March | 0.759688E+10 | 0.206926E+10 | 326.72 | 0.658119E+10 | 0.101570E+10 | 0.00 | 1.00 | 11-MAR-09:02 | 0.00 | 01-MAR-00:10 | 33581.27 | 11-MAR-09:02 | 26049.91 | 11-MAR-09:02 | 7531.36 | 11-MAR-09:02 | 7540.74 | 11-MAR-09:02 | 0.00 | 01-MAR-00:10 |
April | 0.122272E+11 | 0.349508E+10 | 325.06 | 0.110188E+11 | 0.120847E+10 | 0.00 | 1.00 | 01-APR-08:62 | 0.00 | 01-APR-00:05 | 34192.15 | 26-APR-08:61 | 31400.39 | 08-APR-08:62 | 9731.16 | 24-APR-08:62 | 8295.32 | 16-APR-09:01 | 0.00 | 01-APR-00:05 |
May | 0.182401E+11 | 0.523173E+10 | 363.21 | 0.146046E+11 | 0.363544E+10 | 0.00 | 1.00 | 01-MAY-08:61 | 0.00 | 01-MAY-00:10 | 36123.00 | 24-MAY-08:61 | 31259.80 | 06-MAY-08:61 | 16705.51 | 24-MAY-08:03 | 8629.95 | 04-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.205193E+11 | 0.563902E+10 | 357.29 | 0.144165E+11 | 0.610280E+10 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 37032.57 | 25-JUN-09:03 | 29878.45 | 07-JUN-08:61 | 21785.34 | 26-JUN-08:04 | 8715.17 | 12-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.226348E+11 | 0.565925E+10 | 357.67 | 0.129819E+11 | 0.965291E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:03 | 37072.05 | 28-JUL-08:61 | 24499.95 | 07-JUL-08:61 | 21620.12 | 23-JUL-09:04 | 8542.16 | 05-JUL-08:61 | 0.00 | 01-JUL-00:03 |
August | 0.229793E+11 | 0.554533E+10 | 367.04 | 0.122692E+11 | 0.107100E+11 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 37193.44 | 21-AUG-08:05 | 21931.15 | 08-AUG-08:61 | 23378.62 | 21-AUG-08:05 | 8169.30 | 06-AUG-09:04 | 0.00 | 01-AUG-00:10 |
September | 0.184341E+11 | 0.450535E+10 | 335.78 | 0.107335E+11 | 0.770058E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:03 | 37231.06 | 04-SEP-09:03 | 24929.82 | 26-SEP-08:61 | 23168.15 | 11-SEP-08:05 | 8026.90 | 24-SEP-09:04 | 0.00 | 01-SEP-00:03 |
October | 0.120715E+11 | 0.318849E+10 | 329.23 | 0.954637E+10 | 0.252515E+10 | 0.00 | 1.00 | 01-OCT-09:01 | 0.00 | 01-OCT-00:10 | 35463.56 | 12-OCT-08:62 | 28327.77 | 15-OCT-09:01 | 15815.14 | 12-OCT-08:62 | 7788.12 | 04-OCT-08:61 | 0.00 | 01-OCT-00:10 |
November | 0.640893E+10 | 0.171675E+10 | 311.06 | 0.555234E+10 | 0.856586E+09 | 0.00 | 0.94 | 11-NOV-10:03 | 0.00 | 01-NOV-00:10 | 15169.53 | 11-NOV-10:03 | 11764.98 | 11-NOV-10:03 | 3897.65 | 09-NOV-09:03 | 3380.19 | 11-NOV-10:03 | 0.00 | 01-NOV-00:10 |
December | 0.156481E+10 | 0.424540E+09 | 205.33 | 0.136538E+10 | 0.199431E+09 | 0.00 | 0.42 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 | 5568.22 | 28-DEC-14:00 | 5335.56 | 02-DEC-14:20 | 942.35 | 16-DEC-15:10 | 1497.48 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.146090E+12 | 0.383993E+11 | 3618.13 | 0.102064E+12 | 0.440257E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.611341E+09 | 0.167158E+09 | 112.67 | 0.545966E+09 | 65375383.95 | 0.00 | 0.33 | 0.00 | 4278.55 | 3953.71 | 832.88 | 1159.36 | 0.00 | |||||||
Maximum of Months | 0.229793E+11 | 0.565925E+10 | 367.04 | 0.146046E+11 | 0.107100E+11 | 0.00 | 1.00 | 0.00 | 37231.06 | 31400.39 | 23378.62 | 8715.17 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.578855E+09 | 0.158409E+09 | 109.67 | 0.516449E+09 | 62406567.12 | 0.00 | 0.33 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 | 4205.34 | 12-JAN-15:10 | 3884.46 | 12-JAN-15:10 | 820.16 | 14-JAN-15:10 | 1140.89 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 |
February | 0.274129E+10 | 0.741768E+09 | 224.58 | 0.239566E+10 | 0.345630E+09 | 0.00 | 0.56 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 | 7701.59 | 22-FEB-14:00 | 6954.89 | 22-FEB-15:10 | 1948.07 | 25-FEB-16:00 | 2074.35 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 |
March | 0.752527E+10 | 0.205109E+10 | 326.31 | 0.651710E+10 | 0.100817E+10 | 0.00 | 1.00 | 11-MAR-09:02 | 0.00 | 01-MAR-00:10 | 33482.10 | 11-MAR-09:02 | 25932.14 | 11-MAR-09:02 | 7549.96 | 11-MAR-09:02 | 7518.92 | 11-MAR-09:02 | 0.00 | 01-MAR-00:10 |
April | 0.121683E+11 | 0.347906E+10 | 324.87 | 0.109637E+11 | 0.120459E+10 | 0.00 | 1.00 | 01-APR-08:62 | 0.00 | 01-APR-00:05 | 34092.62 | 26-APR-08:61 | 31302.52 | 08-APR-08:62 | 9738.20 | 24-APR-08:62 | 8271.98 | 16-APR-09:01 | 0.00 | 01-APR-00:05 |
May | 0.181813E+11 | 0.521461E+10 | 363.02 | 0.145535E+11 | 0.362783E+10 | 0.00 | 1.00 | 01-MAY-08:61 | 0.00 | 01-MAY-00:10 | 36018.99 | 24-MAY-08:61 | 31162.22 | 06-MAY-08:61 | 16689.45 | 24-MAY-08:03 | 8605.71 | 04-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.204580E+11 | 0.562158E+10 | 357.47 | 0.143663E+11 | 0.609171E+10 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 36927.36 | 25-JUN-09:03 | 29786.63 | 07-JUN-08:61 | 21733.37 | 26-JUN-08:04 | 8690.55 | 12-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.225788E+11 | 0.564431E+10 | 357.87 | 0.129394E+11 | 0.963941E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:03 | 36979.40 | 28-JUL-08:61 | 24415.75 | 07-JUL-08:61 | 21577.97 | 23-JUL-09:04 | 8517.90 | 05-JUL-08:61 | 0.00 | 01-JUL-00:03 |
August | 0.229212E+11 | 0.553006E+10 | 366.81 | 0.122261E+11 | 0.106951E+11 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 37087.77 | 21-AUG-08:61 | 21853.24 | 08-AUG-08:61 | 23327.22 | 21-AUG-08:05 | 8146.04 | 06-AUG-09:04 | 0.00 | 01-AUG-00:10 |
September | 0.183801E+11 | 0.449139E+10 | 335.44 | 0.106925E+11 | 0.768754E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:03 | 37125.29 | 04-SEP-09:01 | 24841.26 | 26-SEP-08:61 | 23122.52 | 11-SEP-08:05 | 8003.94 | 24-SEP-09:04 | 0.00 | 01-SEP-00:03 |
October | 0.120169E+11 | 0.317465E+10 | 329.34 | 0.949938E+10 | 0.251752E+10 | 0.00 | 1.00 | 01-OCT-09:01 | 0.00 | 01-OCT-00:10 | 35362.92 | 12-OCT-08:62 | 28221.54 | 15-OCT-09:01 | 15806.19 | 12-OCT-08:62 | 7766.26 | 04-OCT-08:61 | 0.00 | 01-OCT-00:10 |
November | 0.634966E+10 | 0.170181E+10 | 311.17 | 0.549934E+10 | 0.850325E+09 | 0.00 | 0.92 | 11-NOV-10:03 | 0.00 | 01-NOV-00:10 | 14786.69 | 11-NOV-10:03 | 11453.38 | 11-NOV-10:03 | 3798.36 | 09-NOV-09:03 | 3312.38 | 11-NOV-10:03 | 0.00 | 01-NOV-00:10 |
December | 0.151277E+10 | 0.410727E+09 | 201.08 | 0.132018E+10 | 0.192588E+09 | 0.00 | 0.42 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 | 5501.07 | 28-DEC-14:00 | 5281.73 | 02-DEC-14:20 | 932.04 | 16-DEC-15:10 | 1480.85 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.145412E+12 | 0.382195E+11 | 3607.63 | 0.101490E+12 | 0.439229E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.578855E+09 | 0.158409E+09 | 109.67 | 0.516449E+09 | 62406567.12 | 0.00 | 0.33 | 0.00 | 4205.34 | 3884.46 | 820.16 | 1140.89 | 0.00 | |||||||
Maximum of Months | 0.229212E+11 | 0.564431E+10 | 366.81 | 0.145535E+11 | 0.106951E+11 | 0.00 | 1.00 | 0.00 | 37125.29 | 31302.52 | 23327.22 | 8690.55 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.505872E+09 | 0.138763E+09 | 101.00 | 0.450525E+09 | 55347332.25 | 0.00 | 0.32 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 | 4031.34 | 12-JAN-15:10 | 3722.12 | 12-JAN-15:10 | 786.25 | 14-JAN-15:10 | 1097.62 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 |
February | 0.258944E+10 | 0.702788E+09 | 219.00 | 0.226458E+10 | 0.324858E+09 | 0.00 | 0.56 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 | 7571.20 | 22-FEB-14:00 | 6838.95 | 22-FEB-15:10 | 1897.73 | 25-FEB-16:00 | 2044.72 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 |
March | 0.737006E+10 | 0.201354E+10 | 324.01 | 0.638124E+10 | 0.988815E+09 | 0.00 | 1.00 | 11-MAR-09:02 | 0.00 | 01-MAR-00:10 | 33546.42 | 11-MAR-09:02 | 25898.37 | 11-MAR-09:02 | 7648.04 | 11-MAR-09:02 | 7534.80 | 11-MAR-09:02 | 0.00 | 01-MAR-00:10 |
April | 0.121276E+11 | 0.347046E+10 | 324.00 | 0.109270E+11 | 0.120057E+10 | 0.00 | 1.00 | 01-APR-08:62 | 0.00 | 01-APR-00:05 | 34158.31 | 26-APR-08:61 | 31354.28 | 08-APR-08:62 | 9832.16 | 24-APR-08:62 | 8290.97 | 16-APR-09:01 | 0.00 | 01-APR-00:05 |
May | 0.182193E+11 | 0.522699E+10 | 362.31 | 0.145904E+11 | 0.362882E+10 | 0.00 | 1.00 | 01-MAY-08:61 | 0.00 | 01-MAY-00:10 | 36093.44 | 24-MAY-08:61 | 31239.84 | 06-MAY-08:61 | 16756.18 | 24-MAY-08:03 | 8625.10 | 04-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.205238E+11 | 0.564111E+10 | 357.27 | 0.144247E+11 | 0.609911E+10 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 37011.57 | 25-JUN-09:01 | 29862.79 | 07-JUN-08:61 | 21821.59 | 26-JUN-08:04 | 8709.88 | 12-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.226804E+11 | 0.567125E+10 | 357.39 | 0.130193E+11 | 0.966110E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:03 | 37065.75 | 28-JUL-08:61 | 24506.00 | 07-JUL-08:61 | 21646.30 | 23-JUL-09:04 | 8537.21 | 05-JUL-08:61 | 0.00 | 01-JUL-00:03 |
August | 0.230249E+11 | 0.555625E+10 | 366.72 | 0.123039E+11 | 0.107210E+11 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 37172.34 | 21-AUG-08:61 | 21956.19 | 08-AUG-08:61 | 23393.18 | 21-AUG-08:05 | 8164.78 | 06-AUG-09:04 | 0.00 | 01-AUG-00:10 |
September | 0.184429E+11 | 0.450773E+10 | 335.36 | 0.107424E+11 | 0.770050E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:03 | 37209.94 | 04-SEP-09:01 | 24917.05 | 26-SEP-08:61 | 23199.22 | 11-SEP-08:05 | 8022.34 | 24-SEP-09:04 | 0.00 | 01-SEP-00:03 |
October | 0.120127E+11 | 0.317475E+10 | 329.21 | 0.949787E+10 | 0.251488E+10 | 0.00 | 1.00 | 01-OCT-09:01 | 0.00 | 01-OCT-00:10 | 35437.52 | 12-OCT-08:62 | 28252.13 | 15-OCT-09:01 | 15876.03 | 12-OCT-08:62 | 7783.87 | 04-OCT-08:61 | 0.00 | 01-OCT-00:10 |
November | 0.624460E+10 | 0.167639E+10 | 308.92 | 0.540780E+10 | 0.836799E+09 | 0.00 | 0.87 | 11-NOV-10:03 | 0.00 | 01-NOV-00:10 | 13762.41 | 11-NOV-10:03 | 10635.93 | 11-NOV-10:03 | 3493.19 | 09-NOV-09:03 | 3134.67 | 11-NOV-10:03 | 0.00 | 01-NOV-00:10 |
December | 0.138307E+10 | 0.376359E+09 | 190.92 | 0.120876E+10 | 0.174309E+09 | 0.00 | 0.41 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 | 5347.44 | 28-DEC-14:00 | 5155.44 | 02-DEC-14:20 | 903.11 | 16-DEC-15:10 | 1444.02 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.145125E+12 | 0.381564E+11 | 3576.11 | 0.101219E+12 | 0.439062E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.505872E+09 | 0.138763E+09 | 101.00 | 0.450525E+09 | 55347332.25 | 0.00 | 0.32 | 0.00 | 4031.34 | 3722.12 | 786.25 | 1097.62 | 0.00 | |||||||
Maximum of Months | 0.230249E+11 | 0.567125E+10 | 366.72 | 0.145904E+11 | 0.107210E+11 | 0.00 | 1.00 | 0.00 | 37209.94 | 31354.28 | 23393.18 | 8709.88 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.509716E+09 | 0.140177E+09 | 98.67 | 0.459627E+09 | 50088384.56 | 0.00 | 0.30 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 | 4132.86 | 12-JAN-15:10 | 3862.39 | 12-JAN-15:10 | 751.79 | 14-JAN-15:10 | 1130.92 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 |
February | 0.262334E+10 | 0.715357E+09 | 214.08 | 0.232412E+10 | 0.299220E+09 | 0.00 | 0.54 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 | 8032.08 | 22-FEB-14:00 | 7322.23 | 22-FEB-14:00 | 1829.32 | 25-FEB-16:00 | 2178.66 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 |
March | 0.767216E+10 | 0.210882E+10 | 320.19 | 0.671075E+10 | 0.961410E+09 | 0.00 | 1.00 | 11-MAR-09:02 | 0.00 | 01-MAR-00:10 | 36721.99 | 11-MAR-09:02 | 28552.69 | 11-MAR-09:02 | 8169.31 | 11-MAR-09:02 | 8246.95 | 11-MAR-09:02 | 0.00 | 01-MAR-00:10 |
April | 0.131574E+11 | 0.377521E+10 | 324.48 | 0.119387E+11 | 0.121874E+10 | 0.00 | 1.00 | 01-APR-08:62 | 0.00 | 01-APR-00:05 | 37349.96 | 17-APR-08:61 | 34384.97 | 30-APR-09:01 | 10566.76 | 24-APR-08:62 | 9068.96 | 16-APR-09:01 | 0.00 | 01-APR-00:05 |
May | 0.199192E+11 | 0.573641E+10 | 363.12 | 0.161455E+11 | 0.377370E+10 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 39946.64 | 24-MAY-08:61 | 34890.33 | 29-MAY-08:61 | 19915.58 | 24-MAY-08:03 | 9436.27 | 04-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.223708E+11 | 0.618602E+10 | 358.42 | 0.160227E+11 | 0.634812E+10 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 40613.90 | 24-JUN-08:61 | 33609.26 | 12-JUN-07:01 | 24128.86 | 26-JUN-08:04 | 9523.89 | 12-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.247941E+11 | 0.624383E+10 | 359.45 | 0.146266E+11 | 0.101674E+11 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 40686.86 | 26-JUL-08:61 | 29039.81 | 07-JUL-07:01 | 23683.34 | 23-JUL-09:04 | 9342.85 | 05-JUL-08:61 | 0.00 | 01-JUL-00:03 |
August | 0.252032E+11 | 0.612402E+10 | 368.78 | 0.139261E+11 | 0.112771E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 40680.77 | 21-AUG-08:61 | 25130.01 | 08-AUG-07:01 | 25155.34 | 21-AUG-08:04 | 8936.05 | 06-AUG-09:04 | 0.00 | 01-AUG-00:10 |
September | 0.201693E+11 | 0.496050E+10 | 340.28 | 0.121017E+11 | 0.806760E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:03 | 40753.17 | 09-SEP-08:61 | 27629.53 | 26-SEP-08:61 | 25131.40 | 10-SEP-09:04 | 8783.24 | 24-SEP-09:04 | 0.00 | 01-SEP-00:03 |
October | 0.132222E+11 | 0.349618E+10 | 330.19 | 0.106150E+11 | 0.260715E+10 | 0.00 | 1.00 | 01-OCT-09:01 | 0.00 | 01-OCT-00:10 | 38946.91 | 12-OCT-08:62 | 31434.85 | 15-OCT-09:01 | 17794.48 | 12-OCT-08:62 | 8515.26 | 04-OCT-08:61 | 0.00 | 01-OCT-00:10 |
November | 0.669646E+10 | 0.180158E+10 | 306.50 | 0.586936E+10 | 0.827103E+09 | 0.00 | 0.83 | 11-NOV-10:03 | 0.00 | 01-NOV-00:10 | 14113.37 | 11-NOV-10:03 | 11055.04 | 11-NOV-10:03 | 3117.62 | 09-NOV-09:03 | 3259.22 | 11-NOV-10:03 | 0.00 | 01-NOV-00:10 |
December | 0.141878E+10 | 0.386896E+09 | 184.08 | 0.125960E+10 | 0.159179E+09 | 0.00 | 0.39 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 | 5567.83 | 28-DEC-14:00 | 5374.08 | 02-DEC-14:10 | 894.87 | 16-DEC-14:30 | 1511.00 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.157757E+12 | 0.416750E+11 | 3568.25 | 0.112000E+12 | 0.457568E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.509716E+09 | 0.140177E+09 | 98.67 | 0.459627E+09 | 50088384.56 | 0.00 | 0.30 | 0.00 | 4132.86 | 3862.39 | 751.79 | 1130.92 | 0.00 | |||||||
Maximum of Months | 0.252032E+11 | 0.624383E+10 | 368.78 | 0.161455E+11 | 0.112771E+11 | 0.00 | 1.00 | 0.00 | 40753.17 | 34890.33 | 25155.34 | 9523.89 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.32 | 46.98 | 30.34 | 111.05 | 57.51 | 0.00 | 0.00 | 0.00 |
February | 73.52 | 40.83 | 32.68 | 114.08 | 45.80 | 0.00 | 0.00 | 0.00 |
March | 62.86 | 27.77 | 35.10 | 112.96 | 27.25 | 0.00 | 0.00 | 0.00 |
April | 44.15 | 12.46 | 31.69 | 104.98 | 9.28 | 0.00 | 0.00 | 0.00 |
May | 31.75 | 2.35 | 29.40 | 95.68 | 1.56 | 0.00 | 0.00 | 0.00 |
June | 29.05 | 0.50 | 28.55 | 92.85 | 1.21 | 0.00 | 0.00 | 0.00 |
July | 30.30 | 0.42 | 29.88 | 86.86 | 0.38 | 0.00 | 0.00 | 0.00 |
August | 32.14 | 1.72 | 30.42 | 81.56 | 1.17 | 0.00 | 0.00 | 0.00 |
September | 43.08 | 11.18 | 31.90 | 93.57 | 4.51 | 0.00 | 0.00 | 0.00 |
October | 74.12 | 41.39 | 32.73 | 140.06 | 21.87 | 0.00 | 0.00 | 0.00 |
November | 92.58 | 61.19 | 31.39 | 153.86 | 41.76 | 0.00 | 0.00 | 0.00 |
December | 82.63 | 51.78 | 30.85 | 122.18 | 57.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.02 | 24.79 | 31.24 | 109.08 | 22.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.05 | 0.42 | 28.55 | 81.56 | 0.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.58 | 61.19 | 35.10 | 153.86 | 57.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.32 | 46.98 | 30.34 | 111.05 | 57.51 | 0.00 | 0.00 | 0.00 |
February | 73.52 | 40.83 | 32.68 | 114.08 | 45.80 | 0.00 | 0.00 | 0.00 |
March | 62.86 | 27.77 | 35.10 | 112.96 | 27.25 | 0.00 | 0.00 | 0.00 |
April | 44.15 | 12.46 | 31.69 | 104.98 | 9.28 | 0.00 | 0.00 | 0.00 |
May | 31.75 | 2.35 | 29.40 | 95.68 | 1.56 | 0.00 | 0.00 | 0.00 |
June | 29.05 | 0.50 | 28.55 | 92.85 | 1.21 | 0.00 | 0.00 | 0.00 |
July | 30.30 | 0.42 | 29.88 | 86.86 | 0.38 | 0.00 | 0.00 | 0.00 |
August | 32.14 | 1.72 | 30.42 | 81.56 | 1.17 | 0.00 | 0.00 | 0.00 |
September | 43.08 | 11.18 | 31.90 | 93.57 | 4.51 | 0.00 | 0.00 | 0.00 |
October | 74.12 | 41.39 | 32.73 | 140.06 | 21.87 | 0.00 | 0.00 | 0.00 |
November | 92.58 | 61.19 | 31.39 | 153.86 | 41.76 | 0.00 | 0.00 | 0.00 |
December | 82.63 | 51.78 | 30.85 | 122.18 | 57.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.02 | 24.79 | 31.24 | 109.08 | 22.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.05 | 0.42 | 28.55 | 81.56 | 0.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.58 | 61.19 | 35.10 | 153.86 | 57.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.32 | 46.98 | 30.34 | 111.05 | 57.51 | 0.00 | 0.00 | 0.00 |
February | 73.52 | 40.83 | 32.68 | 114.08 | 45.80 | 0.00 | 0.00 | 0.00 |
March | 62.86 | 27.77 | 35.10 | 112.96 | 27.25 | 0.00 | 0.00 | 0.00 |
April | 44.15 | 12.46 | 31.69 | 104.98 | 9.28 | 0.00 | 0.00 | 0.00 |
May | 31.75 | 2.35 | 29.40 | 95.68 | 1.56 | 0.00 | 0.00 | 0.00 |
June | 29.05 | 0.50 | 28.55 | 92.85 | 1.21 | 0.00 | 0.00 | 0.00 |
July | 30.30 | 0.42 | 29.88 | 86.86 | 0.38 | 0.00 | 0.00 | 0.00 |
August | 32.14 | 1.72 | 30.42 | 81.56 | 1.17 | 0.00 | 0.00 | 0.00 |
September | 43.08 | 11.18 | 31.90 | 93.57 | 4.51 | 0.00 | 0.00 | 0.00 |
October | 74.12 | 41.39 | 32.73 | 140.06 | 21.87 | 0.00 | 0.00 | 0.00 |
November | 92.58 | 61.19 | 31.39 | 153.86 | 41.76 | 0.00 | 0.00 | 0.00 |
December | 82.63 | 51.78 | 30.85 | 122.18 | 57.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.02 | 24.79 | 31.24 | 109.08 | 22.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.05 | 0.42 | 28.55 | 81.56 | 0.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.58 | 61.19 | 35.10 | 153.86 | 57.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.32 | 46.98 | 30.34 | 111.05 | 57.51 | 0.00 | 0.00 | 0.00 |
February | 73.52 | 40.83 | 32.68 | 114.08 | 45.80 | 0.00 | 0.00 | 0.00 |
March | 62.86 | 27.77 | 35.10 | 112.96 | 27.25 | 0.00 | 0.00 | 0.00 |
April | 44.15 | 12.46 | 31.69 | 104.98 | 9.28 | 0.00 | 0.00 | 0.00 |
May | 31.75 | 2.35 | 29.40 | 95.68 | 1.56 | 0.00 | 0.00 | 0.00 |
June | 29.05 | 0.50 | 28.55 | 92.85 | 1.21 | 0.00 | 0.00 | 0.00 |
July | 30.30 | 0.42 | 29.88 | 86.86 | 0.38 | 0.00 | 0.00 | 0.00 |
August | 32.14 | 1.72 | 30.42 | 81.56 | 1.17 | 0.00 | 0.00 | 0.00 |
September | 43.08 | 11.18 | 31.90 | 93.57 | 4.51 | 0.00 | 0.00 | 0.00 |
October | 74.12 | 41.39 | 32.73 | 140.06 | 21.87 | 0.00 | 0.00 | 0.00 |
November | 92.58 | 61.19 | 31.39 | 153.86 | 41.76 | 0.00 | 0.00 | 0.00 |
December | 82.63 | 51.78 | 30.85 | 122.18 | 57.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.02 | 24.79 | 31.24 | 109.08 | 22.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.05 | 0.42 | 28.55 | 81.56 | 0.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.58 | 61.19 | 35.10 | 153.86 | 57.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.95 | 56.48 | 36.47 | 133.54 | 68.54 | 0.00 | 0.00 | 0.00 |
February | 88.38 | 49.09 | 39.29 | 137.14 | 54.59 | 0.00 | 0.00 | 0.00 |
March | 75.57 | 33.38 | 42.19 | 135.54 | 32.57 | 0.00 | 0.00 | 0.00 |
April | 53.08 | 14.98 | 38.10 | 125.53 | 11.11 | 0.00 | 0.00 | 0.00 |
May | 38.17 | 2.83 | 35.35 | 113.90 | 1.90 | 0.00 | 0.00 | 0.00 |
June | 34.92 | 0.60 | 34.32 | 110.55 | 1.45 | 0.00 | 0.00 | 0.00 |
July | 36.42 | 0.50 | 35.92 | 103.49 | 0.47 | 0.00 | 0.00 | 0.00 |
August | 38.64 | 2.06 | 36.57 | 97.38 | 1.42 | 0.00 | 0.00 | 0.00 |
September | 51.79 | 13.44 | 38.35 | 111.93 | 5.41 | 0.00 | 0.00 | 0.00 |
October | 89.11 | 49.76 | 39.35 | 167.86 | 26.16 | 0.00 | 0.00 | 0.00 |
November | 111.30 | 73.57 | 37.73 | 184.66 | 49.87 | 0.00 | 0.00 | 0.00 |
December | 99.33 | 62.24 | 37.09 | 146.84 | 68.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 67.35 | 29.80 | 37.55 | 130.62 | 26.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.92 | 0.50 | 34.32 | 97.38 | 0.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 111.30 | 73.57 | 42.19 | 184.66 | 68.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.95 | 56.48 | 36.47 | 133.54 | 68.54 | 0.00 | 0.00 | 0.00 |
February | 88.38 | 49.09 | 39.29 | 137.14 | 54.59 | 0.00 | 0.00 | 0.00 |
March | 75.57 | 33.38 | 42.19 | 135.54 | 32.57 | 0.00 | 0.00 | 0.00 |
April | 53.08 | 14.98 | 38.10 | 125.53 | 11.11 | 0.00 | 0.00 | 0.00 |
May | 38.17 | 2.83 | 35.35 | 113.90 | 1.90 | 0.00 | 0.00 | 0.00 |
June | 34.92 | 0.60 | 34.32 | 110.55 | 1.45 | 0.00 | 0.00 | 0.00 |
July | 36.42 | 0.50 | 35.92 | 103.49 | 0.47 | 0.00 | 0.00 | 0.00 |
August | 38.64 | 2.06 | 36.57 | 97.38 | 1.42 | 0.00 | 0.00 | 0.00 |
September | 51.79 | 13.44 | 38.35 | 111.93 | 5.41 | 0.00 | 0.00 | 0.00 |
October | 89.11 | 49.76 | 39.35 | 167.86 | 26.16 | 0.00 | 0.00 | 0.00 |
November | 111.30 | 73.57 | 37.73 | 184.66 | 49.87 | 0.00 | 0.00 | 0.00 |
December | 99.33 | 62.24 | 37.09 | 146.84 | 68.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 67.35 | 29.80 | 37.55 | 130.62 | 26.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.92 | 0.50 | 34.32 | 97.38 | 0.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 111.30 | 73.57 | 42.19 | 184.66 | 68.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.32 | 46.98 | 30.34 | 109.94 | 59.71 | 0.00 | 0.00 | 0.00 |
February | 73.52 | 40.83 | 32.68 | 113.26 | 47.11 | 0.00 | 0.00 | 0.00 |
March | 62.86 | 27.77 | 35.10 | 112.65 | 27.79 | 0.00 | 0.00 | 0.00 |
April | 44.15 | 12.46 | 31.69 | 105.35 | 9.43 | 0.00 | 0.00 | 0.00 |
May | 31.75 | 2.35 | 29.40 | 96.65 | 1.54 | 0.00 | 0.00 | 0.00 |
June | 29.05 | 0.50 | 28.55 | 94.12 | 1.20 | 0.00 | 0.00 | 0.00 |
July | 30.30 | 0.42 | 29.88 | 88.15 | 0.34 | 0.00 | 0.00 | 0.00 |
August | 32.14 | 1.72 | 30.42 | 82.66 | 1.05 | 0.00 | 0.00 | 0.00 |
September | 43.08 | 11.18 | 31.90 | 94.28 | 4.24 | 0.00 | 0.00 | 0.00 |
October | 74.12 | 41.39 | 32.73 | 140.30 | 21.74 | 0.00 | 0.00 | 0.00 |
November | 92.58 | 61.19 | 31.39 | 153.61 | 42.05 | 0.00 | 0.00 | 0.00 |
December | 82.63 | 51.78 | 30.85 | 121.37 | 58.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.02 | 24.79 | 31.24 | 109.30 | 22.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.05 | 0.42 | 28.55 | 82.66 | 0.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.58 | 61.19 | 35.10 | 153.61 | 59.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.32 | 46.98 | 30.34 | 109.94 | 59.71 | 0.00 | 0.00 | 0.00 |
February | 73.52 | 40.83 | 32.68 | 113.26 | 47.11 | 0.00 | 0.00 | 0.00 |
March | 62.86 | 27.77 | 35.10 | 112.65 | 27.79 | 0.00 | 0.00 | 0.00 |
April | 44.15 | 12.46 | 31.69 | 105.35 | 9.43 | 0.00 | 0.00 | 0.00 |
May | 31.75 | 2.35 | 29.40 | 96.65 | 1.54 | 0.00 | 0.00 | 0.00 |
June | 29.05 | 0.50 | 28.55 | 94.12 | 1.20 | 0.00 | 0.00 | 0.00 |
July | 30.30 | 0.42 | 29.88 | 88.15 | 0.34 | 0.00 | 0.00 | 0.00 |
August | 32.14 | 1.72 | 30.42 | 82.66 | 1.05 | 0.00 | 0.00 | 0.00 |
September | 43.08 | 11.18 | 31.90 | 94.28 | 4.24 | 0.00 | 0.00 | 0.00 |
October | 74.12 | 41.39 | 32.73 | 140.30 | 21.74 | 0.00 | 0.00 | 0.00 |
November | 92.58 | 61.19 | 31.39 | 153.61 | 42.05 | 0.00 | 0.00 | 0.00 |
December | 82.63 | 51.78 | 30.85 | 121.37 | 58.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.02 | 24.79 | 31.24 | 109.30 | 22.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.05 | 0.42 | 28.55 | 82.66 | 0.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.58 | 61.19 | 35.10 | 153.61 | 59.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.95 | 56.48 | 36.47 | 132.26 | 71.13 | 0.00 | 0.00 | 0.00 |
February | 88.38 | 49.09 | 39.29 | 136.20 | 56.13 | 0.00 | 0.00 | 0.00 |
March | 75.57 | 33.38 | 42.19 | 135.19 | 33.21 | 0.00 | 0.00 | 0.00 |
April | 53.08 | 14.98 | 38.10 | 125.97 | 11.29 | 0.00 | 0.00 | 0.00 |
May | 38.17 | 2.83 | 35.35 | 115.05 | 1.87 | 0.00 | 0.00 | 0.00 |
June | 34.92 | 0.60 | 34.32 | 112.05 | 1.44 | 0.00 | 0.00 | 0.00 |
July | 36.42 | 0.50 | 35.92 | 105.01 | 0.42 | 0.00 | 0.00 | 0.00 |
August | 38.64 | 2.06 | 36.57 | 98.70 | 1.27 | 0.00 | 0.00 | 0.00 |
September | 51.79 | 13.44 | 38.35 | 112.80 | 5.08 | 0.00 | 0.00 | 0.00 |
October | 89.11 | 49.76 | 39.35 | 168.17 | 26.00 | 0.00 | 0.00 | 0.00 |
November | 111.30 | 73.57 | 37.73 | 184.40 | 50.20 | 0.00 | 0.00 | 0.00 |
December | 99.33 | 62.24 | 37.09 | 145.90 | 70.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 67.35 | 29.80 | 37.55 | 130.90 | 27.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.92 | 0.50 | 34.32 | 98.70 | 0.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 111.30 | 73.57 | 42.19 | 184.40 | 71.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.32 | 46.98 | 30.34 | 110.59 | 58.17 | 0.00 | 0.00 | 0.00 |
February | 73.52 | 40.83 | 32.68 | 113.51 | 47.14 | 0.00 | 0.00 | 0.00 |
March | 62.86 | 27.77 | 35.10 | 112.48 | 29.11 | 0.00 | 0.00 | 0.00 |
April | 44.15 | 12.46 | 31.69 | 103.54 | 10.86 | 0.00 | 0.00 | 0.00 |
May | 31.75 | 2.35 | 29.40 | 92.95 | 2.17 | 0.00 | 0.00 | 0.00 |
June | 29.05 | 0.50 | 28.55 | 90.22 | 1.73 | 0.00 | 0.00 | 0.00 |
July | 30.30 | 0.42 | 29.88 | 83.83 | 0.57 | 0.00 | 0.00 | 0.00 |
August | 32.14 | 1.72 | 30.42 | 79.79 | 1.78 | 0.00 | 0.00 | 0.00 |
September | 43.08 | 11.18 | 31.90 | 92.58 | 5.98 | 0.00 | 0.00 | 0.00 |
October | 74.12 | 41.39 | 32.73 | 139.84 | 24.04 | 0.00 | 0.00 | 0.00 |
November | 92.58 | 61.19 | 31.39 | 153.67 | 43.17 | 0.00 | 0.00 | 0.00 |
December | 82.63 | 51.78 | 30.85 | 121.79 | 58.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.02 | 24.79 | 31.24 | 107.83 | 23.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.05 | 0.42 | 28.55 | 79.79 | 0.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.58 | 61.19 | 35.10 | 153.67 | 58.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.32 | 46.98 | 30.34 | 110.59 | 58.17 | 0.00 | 0.00 | 0.00 |
February | 73.52 | 40.83 | 32.68 | 113.51 | 47.14 | 0.00 | 0.00 | 0.00 |
March | 62.86 | 27.77 | 35.10 | 112.48 | 29.11 | 0.00 | 0.00 | 0.00 |
April | 44.15 | 12.46 | 31.69 | 103.54 | 10.86 | 0.00 | 0.00 | 0.00 |
May | 31.75 | 2.35 | 29.40 | 92.95 | 2.17 | 0.00 | 0.00 | 0.00 |
June | 29.05 | 0.50 | 28.55 | 90.22 | 1.73 | 0.00 | 0.00 | 0.00 |
July | 30.30 | 0.42 | 29.88 | 83.83 | 0.57 | 0.00 | 0.00 | 0.00 |
August | 32.14 | 1.72 | 30.42 | 79.79 | 1.78 | 0.00 | 0.00 | 0.00 |
September | 43.08 | 11.18 | 31.90 | 92.58 | 5.98 | 0.00 | 0.00 | 0.00 |
October | 74.12 | 41.39 | 32.73 | 139.84 | 24.04 | 0.00 | 0.00 | 0.00 |
November | 92.58 | 61.19 | 31.39 | 153.67 | 43.17 | 0.00 | 0.00 | 0.00 |
December | 82.63 | 51.78 | 30.85 | 121.79 | 58.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.02 | 24.79 | 31.24 | 107.83 | 23.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.05 | 0.42 | 28.55 | 79.79 | 0.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.58 | 61.19 | 35.10 | 153.67 | 58.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.44 | 56.17 | 36.27 | 132.31 | 68.91 | 0.00 | 0.00 | 0.00 |
February | 87.90 | 48.82 | 39.08 | 135.76 | 55.84 | 0.00 | 0.00 | 0.00 |
March | 75.16 | 33.20 | 41.96 | 134.25 | 34.56 | 0.00 | 0.00 | 0.00 |
April | 52.79 | 14.90 | 37.89 | 123.18 | 12.92 | 0.00 | 0.00 | 0.00 |
May | 37.96 | 2.81 | 35.15 | 110.12 | 2.62 | 0.00 | 0.00 | 0.00 |
June | 34.73 | 0.59 | 34.13 | 106.90 | 2.06 | 0.00 | 0.00 | 0.00 |
July | 36.22 | 0.50 | 35.72 | 99.42 | 0.69 | 0.00 | 0.00 | 0.00 |
August | 38.42 | 2.05 | 36.37 | 94.82 | 2.13 | 0.00 | 0.00 | 0.00 |
September | 51.51 | 13.37 | 38.14 | 110.22 | 7.12 | 0.00 | 0.00 | 0.00 |
October | 88.62 | 49.48 | 39.13 | 166.71 | 28.55 | 0.00 | 0.00 | 0.00 |
November | 110.69 | 73.16 | 37.53 | 183.47 | 51.22 | 0.00 | 0.00 | 0.00 |
December | 98.79 | 61.90 | 36.88 | 145.60 | 69.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.98 | 29.64 | 37.35 | 128.48 | 27.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.73 | 0.50 | 34.13 | 94.82 | 0.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 110.69 | 73.16 | 41.96 | 183.47 | 69.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.32 | 46.98 | 30.34 | 110.96 | 57.21 | 0.00 | 0.00 | 0.00 |
February | 73.52 | 40.83 | 32.68 | 113.67 | 46.72 | 0.00 | 0.00 | 0.00 |
March | 62.86 | 27.77 | 35.10 | 112.50 | 29.07 | 0.00 | 0.00 | 0.00 |
April | 44.15 | 12.46 | 31.69 | 103.42 | 11.06 | 0.00 | 0.00 | 0.00 |
May | 31.75 | 2.35 | 29.40 | 92.57 | 2.34 | 0.00 | 0.00 | 0.00 |
June | 29.05 | 0.50 | 28.55 | 89.77 | 1.85 | 0.00 | 0.00 | 0.00 |
July | 30.30 | 0.42 | 29.88 | 83.32 | 0.63 | 0.00 | 0.00 | 0.00 |
August | 32.14 | 1.72 | 30.42 | 79.49 | 1.91 | 0.00 | 0.00 | 0.00 |
September | 43.08 | 11.18 | 31.90 | 92.47 | 6.28 | 0.00 | 0.00 | 0.00 |
October | 74.12 | 41.39 | 32.73 | 139.79 | 24.24 | 0.00 | 0.00 | 0.00 |
November | 92.58 | 61.19 | 31.39 | 153.72 | 43.05 | 0.00 | 0.00 | 0.00 |
December | 82.63 | 51.78 | 30.85 | 122.00 | 57.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.02 | 24.79 | 31.24 | 107.74 | 23.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.05 | 0.42 | 28.55 | 79.49 | 0.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.58 | 61.19 | 35.10 | 153.72 | 57.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.32 | 46.98 | 30.34 | 110.96 | 57.21 | 0.00 | 0.00 | 0.00 |
February | 73.52 | 40.83 | 32.68 | 113.67 | 46.72 | 0.00 | 0.00 | 0.00 |
March | 62.86 | 27.77 | 35.10 | 112.50 | 29.07 | 0.00 | 0.00 | 0.00 |
April | 44.15 | 12.46 | 31.69 | 103.42 | 11.06 | 0.00 | 0.00 | 0.00 |
May | 31.75 | 2.35 | 29.40 | 92.57 | 2.34 | 0.00 | 0.00 | 0.00 |
June | 29.05 | 0.50 | 28.55 | 89.77 | 1.85 | 0.00 | 0.00 | 0.00 |
July | 30.30 | 0.42 | 29.88 | 83.32 | 0.63 | 0.00 | 0.00 | 0.00 |
August | 32.14 | 1.72 | 30.42 | 79.49 | 1.91 | 0.00 | 0.00 | 0.00 |
September | 43.08 | 11.18 | 31.90 | 92.47 | 6.28 | 0.00 | 0.00 | 0.00 |
October | 74.12 | 41.39 | 32.73 | 139.79 | 24.24 | 0.00 | 0.00 | 0.00 |
November | 92.58 | 61.19 | 31.39 | 153.72 | 43.05 | 0.00 | 0.00 | 0.00 |
December | 82.63 | 51.78 | 30.85 | 122.00 | 57.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.02 | 24.79 | 31.24 | 107.74 | 23.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.05 | 0.42 | 28.55 | 79.49 | 0.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.58 | 61.19 | 35.10 | 153.72 | 57.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.44 | 56.17 | 36.27 | 132.75 | 67.78 | 0.00 | 0.00 | 0.00 |
February | 87.90 | 48.82 | 39.08 | 135.95 | 55.34 | 0.00 | 0.00 | 0.00 |
March | 75.16 | 33.20 | 41.96 | 134.28 | 34.51 | 0.00 | 0.00 | 0.00 |
April | 52.79 | 14.90 | 37.89 | 123.03 | 13.15 | 0.00 | 0.00 | 0.00 |
May | 37.96 | 2.81 | 35.15 | 109.67 | 2.83 | 0.00 | 0.00 | 0.00 |
June | 34.73 | 0.59 | 34.13 | 106.36 | 2.19 | 0.00 | 0.00 | 0.00 |
July | 36.22 | 0.50 | 35.72 | 98.81 | 0.77 | 0.00 | 0.00 | 0.00 |
August | 38.42 | 2.05 | 36.37 | 94.46 | 2.29 | 0.00 | 0.00 | 0.00 |
September | 51.51 | 13.37 | 38.14 | 110.09 | 7.46 | 0.00 | 0.00 | 0.00 |
October | 88.62 | 49.48 | 39.13 | 166.65 | 28.79 | 0.00 | 0.00 | 0.00 |
November | 110.69 | 73.16 | 37.53 | 183.53 | 51.08 | 0.00 | 0.00 | 0.00 |
December | 98.79 | 61.90 | 36.88 | 145.86 | 68.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.98 | 29.64 | 37.35 | 128.37 | 27.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.73 | 0.50 | 34.13 | 94.46 | 0.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 110.69 | 73.16 | 41.96 | 183.53 | 68.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.32 | 46.98 | 30.34 | 111.31 | 56.43 | 0.00 | 0.00 | 0.00 |
February | 73.52 | 40.83 | 32.68 | 113.88 | 46.25 | 0.00 | 0.00 | 0.00 |
March | 62.86 | 27.77 | 35.10 | 112.62 | 28.75 | 0.00 | 0.00 | 0.00 |
April | 44.15 | 12.46 | 31.69 | 103.54 | 10.84 | 0.00 | 0.00 | 0.00 |
May | 31.75 | 2.35 | 29.40 | 92.73 | 2.25 | 0.00 | 0.00 | 0.00 |
June | 29.05 | 0.50 | 28.55 | 89.98 | 1.80 | 0.00 | 0.00 | 0.00 |
July | 30.30 | 0.42 | 29.88 | 83.47 | 0.59 | 0.00 | 0.00 | 0.00 |
August | 32.14 | 1.72 | 30.42 | 79.63 | 1.82 | 0.00 | 0.00 | 0.00 |
September | 43.08 | 11.18 | 31.90 | 92.53 | 6.08 | 0.00 | 0.00 | 0.00 |
October | 74.12 | 41.39 | 32.73 | 139.84 | 24.02 | 0.00 | 0.00 | 0.00 |
November | 92.58 | 61.19 | 31.39 | 153.82 | 42.76 | 0.00 | 0.00 | 0.00 |
December | 82.63 | 51.78 | 30.85 | 122.23 | 57.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.02 | 24.79 | 31.24 | 107.89 | 23.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.05 | 0.42 | 28.55 | 79.63 | 0.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.58 | 61.19 | 35.10 | 153.82 | 57.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.32 | 46.98 | 30.34 | 111.31 | 56.43 | 0.00 | 0.00 | 0.00 |
February | 73.52 | 40.83 | 32.68 | 113.88 | 46.25 | 0.00 | 0.00 | 0.00 |
March | 62.86 | 27.77 | 35.10 | 112.62 | 28.75 | 0.00 | 0.00 | 0.00 |
April | 44.15 | 12.46 | 31.69 | 103.54 | 10.84 | 0.00 | 0.00 | 0.00 |
May | 31.75 | 2.35 | 29.40 | 92.73 | 2.25 | 0.00 | 0.00 | 0.00 |
June | 29.05 | 0.50 | 28.55 | 89.98 | 1.80 | 0.00 | 0.00 | 0.00 |
July | 30.30 | 0.42 | 29.88 | 83.47 | 0.59 | 0.00 | 0.00 | 0.00 |
August | 32.14 | 1.72 | 30.42 | 79.63 | 1.82 | 0.00 | 0.00 | 0.00 |
September | 43.08 | 11.18 | 31.90 | 92.53 | 6.08 | 0.00 | 0.00 | 0.00 |
October | 74.12 | 41.39 | 32.73 | 139.84 | 24.02 | 0.00 | 0.00 | 0.00 |
November | 92.58 | 61.19 | 31.39 | 153.82 | 42.76 | 0.00 | 0.00 | 0.00 |
December | 82.63 | 51.78 | 30.85 | 122.23 | 57.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.02 | 24.79 | 31.24 | 107.89 | 23.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.05 | 0.42 | 28.55 | 79.63 | 0.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.58 | 61.19 | 35.10 | 153.82 | 57.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.44 | 56.17 | 36.27 | 133.17 | 66.86 | 0.00 | 0.00 | 0.00 |
February | 87.90 | 48.82 | 39.08 | 136.20 | 54.79 | 0.00 | 0.00 | 0.00 |
March | 75.16 | 33.20 | 41.96 | 134.41 | 34.14 | 0.00 | 0.00 | 0.00 |
April | 52.79 | 14.90 | 37.89 | 123.18 | 12.90 | 0.00 | 0.00 | 0.00 |
May | 37.96 | 2.81 | 35.15 | 109.86 | 2.73 | 0.00 | 0.00 | 0.00 |
June | 34.73 | 0.59 | 34.13 | 106.61 | 2.13 | 0.00 | 0.00 | 0.00 |
July | 36.22 | 0.50 | 35.72 | 98.99 | 0.72 | 0.00 | 0.00 | 0.00 |
August | 38.42 | 2.05 | 36.37 | 94.63 | 2.18 | 0.00 | 0.00 | 0.00 |
September | 51.51 | 13.37 | 38.14 | 110.16 | 7.23 | 0.00 | 0.00 | 0.00 |
October | 88.62 | 49.48 | 39.13 | 166.72 | 28.52 | 0.00 | 0.00 | 0.00 |
November | 110.69 | 73.16 | 37.53 | 183.65 | 50.74 | 0.00 | 0.00 | 0.00 |
December | 98.79 | 61.90 | 36.88 | 146.13 | 67.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.98 | 29.64 | 37.35 | 128.56 | 27.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.73 | 0.50 | 34.13 | 94.63 | 0.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 110.69 | 73.16 | 41.96 | 183.65 | 67.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.32 | 46.98 | 30.34 | 112.04 | 55.17 | 0.00 | 0.00 | 0.00 |
February | 73.52 | 40.83 | 32.68 | 114.38 | 45.35 | 0.00 | 0.00 | 0.00 |
March | 62.86 | 27.77 | 35.10 | 112.88 | 27.93 | 0.00 | 0.00 | 0.00 |
April | 44.15 | 12.46 | 31.69 | 103.65 | 10.23 | 0.00 | 0.00 | 0.00 |
May | 31.75 | 2.35 | 29.40 | 92.82 | 2.04 | 0.00 | 0.00 | 0.00 |
June | 29.05 | 0.50 | 28.55 | 90.26 | 1.68 | 0.00 | 0.00 | 0.00 |
July | 30.30 | 0.42 | 29.88 | 83.39 | 0.48 | 0.00 | 0.00 | 0.00 |
August | 32.14 | 1.72 | 30.42 | 79.65 | 1.56 | 0.00 | 0.00 | 0.00 |
September | 43.08 | 11.18 | 31.90 | 92.37 | 5.52 | 0.00 | 0.00 | 0.00 |
October | 74.12 | 41.39 | 32.73 | 139.70 | 23.33 | 0.00 | 0.00 | 0.00 |
November | 92.58 | 61.19 | 31.39 | 154.00 | 42.14 | 0.00 | 0.00 | 0.00 |
December | 82.63 | 51.78 | 30.85 | 122.71 | 56.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.02 | 24.79 | 31.24 | 108.08 | 22.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.05 | 0.42 | 28.55 | 79.65 | 0.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.58 | 61.19 | 35.10 | 154.00 | 56.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.32 | 46.98 | 30.34 | 112.04 | 55.17 | 0.00 | 0.00 | 0.00 |
February | 73.52 | 40.83 | 32.68 | 114.38 | 45.35 | 0.00 | 0.00 | 0.00 |
March | 62.86 | 27.77 | 35.10 | 112.88 | 27.93 | 0.00 | 0.00 | 0.00 |
April | 44.15 | 12.46 | 31.69 | 103.65 | 10.23 | 0.00 | 0.00 | 0.00 |
May | 31.75 | 2.35 | 29.40 | 92.82 | 2.04 | 0.00 | 0.00 | 0.00 |
June | 29.05 | 0.50 | 28.55 | 90.26 | 1.68 | 0.00 | 0.00 | 0.00 |
July | 30.30 | 0.42 | 29.88 | 83.39 | 0.48 | 0.00 | 0.00 | 0.00 |
August | 32.14 | 1.72 | 30.42 | 79.65 | 1.56 | 0.00 | 0.00 | 0.00 |
September | 43.08 | 11.18 | 31.90 | 92.37 | 5.52 | 0.00 | 0.00 | 0.00 |
October | 74.12 | 41.39 | 32.73 | 139.70 | 23.33 | 0.00 | 0.00 | 0.00 |
November | 92.58 | 61.19 | 31.39 | 154.00 | 42.14 | 0.00 | 0.00 | 0.00 |
December | 82.63 | 51.78 | 30.85 | 122.71 | 56.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.02 | 24.79 | 31.24 | 108.08 | 22.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.05 | 0.42 | 28.55 | 79.65 | 0.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.58 | 61.19 | 35.10 | 154.00 | 56.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.32 | 46.98 | 30.34 | 112.04 | 55.17 | 0.00 | 0.00 | 0.00 |
February | 73.52 | 40.83 | 32.68 | 114.38 | 45.35 | 0.00 | 0.00 | 0.00 |
March | 62.86 | 27.77 | 35.10 | 112.88 | 27.93 | 0.00 | 0.00 | 0.00 |
April | 44.15 | 12.46 | 31.69 | 103.65 | 10.23 | 0.00 | 0.00 | 0.00 |
May | 31.75 | 2.35 | 29.40 | 92.82 | 2.04 | 0.00 | 0.00 | 0.00 |
June | 29.05 | 0.50 | 28.55 | 90.26 | 1.68 | 0.00 | 0.00 | 0.00 |
July | 30.30 | 0.42 | 29.88 | 83.39 | 0.48 | 0.00 | 0.00 | 0.00 |
August | 32.14 | 1.72 | 30.42 | 79.65 | 1.56 | 0.00 | 0.00 | 0.00 |
September | 43.08 | 11.18 | 31.90 | 92.37 | 5.52 | 0.00 | 0.00 | 0.00 |
October | 74.12 | 41.39 | 32.73 | 139.70 | 23.33 | 0.00 | 0.00 | 0.00 |
November | 92.58 | 61.19 | 31.39 | 154.00 | 42.14 | 0.00 | 0.00 | 0.00 |
December | 82.63 | 51.78 | 30.85 | 122.71 | 56.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.02 | 24.79 | 31.24 | 108.08 | 22.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.05 | 0.42 | 28.55 | 79.65 | 0.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.58 | 61.19 | 35.10 | 154.00 | 56.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.32 | 46.98 | 30.34 | 112.04 | 55.17 | 0.00 | 0.00 | 0.00 |
February | 73.52 | 40.83 | 32.68 | 114.38 | 45.35 | 0.00 | 0.00 | 0.00 |
March | 62.86 | 27.77 | 35.10 | 112.88 | 27.93 | 0.00 | 0.00 | 0.00 |
April | 44.15 | 12.46 | 31.69 | 103.65 | 10.23 | 0.00 | 0.00 | 0.00 |
May | 31.75 | 2.35 | 29.40 | 92.82 | 2.04 | 0.00 | 0.00 | 0.00 |
June | 29.05 | 0.50 | 28.55 | 90.26 | 1.68 | 0.00 | 0.00 | 0.00 |
July | 30.30 | 0.42 | 29.88 | 83.39 | 0.48 | 0.00 | 0.00 | 0.00 |
August | 32.14 | 1.72 | 30.42 | 79.65 | 1.56 | 0.00 | 0.00 | 0.00 |
September | 43.08 | 11.18 | 31.90 | 92.37 | 5.52 | 0.00 | 0.00 | 0.00 |
October | 74.12 | 41.39 | 32.73 | 139.70 | 23.33 | 0.00 | 0.00 | 0.00 |
November | 92.58 | 61.19 | 31.39 | 154.00 | 42.14 | 0.00 | 0.00 | 0.00 |
December | 82.63 | 51.78 | 30.85 | 122.71 | 56.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.02 | 24.79 | 31.24 | 108.08 | 22.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.05 | 0.42 | 28.55 | 79.65 | 0.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.58 | 61.19 | 35.10 | 154.00 | 56.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.44 | 56.17 | 36.27 | 134.01 | 65.37 | 0.00 | 0.00 | 0.00 |
February | 87.90 | 48.82 | 39.08 | 136.77 | 53.74 | 0.00 | 0.00 | 0.00 |
March | 75.16 | 33.20 | 41.96 | 134.71 | 33.17 | 0.00 | 0.00 | 0.00 |
April | 52.79 | 14.90 | 37.89 | 123.32 | 12.16 | 0.00 | 0.00 | 0.00 |
May | 37.96 | 2.81 | 35.15 | 109.99 | 2.46 | 0.00 | 0.00 | 0.00 |
June | 34.73 | 0.59 | 34.13 | 106.97 | 1.99 | 0.00 | 0.00 | 0.00 |
July | 36.22 | 0.50 | 35.72 | 98.92 | 0.59 | 0.00 | 0.00 | 0.00 |
August | 38.42 | 2.05 | 36.37 | 94.67 | 1.86 | 0.00 | 0.00 | 0.00 |
September | 51.51 | 13.37 | 38.14 | 109.97 | 6.56 | 0.00 | 0.00 | 0.00 |
October | 88.62 | 49.48 | 39.13 | 166.54 | 27.71 | 0.00 | 0.00 | 0.00 |
November | 110.69 | 73.16 | 37.53 | 183.84 | 50.00 | 0.00 | 0.00 | 0.00 |
December | 98.79 | 61.90 | 36.88 | 146.67 | 66.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.98 | 29.64 | 37.35 | 128.78 | 26.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.73 | 0.50 | 34.13 | 94.67 | 0.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 110.69 | 73.16 | 41.96 | 183.84 | 66.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.44 | 56.17 | 36.27 | 134.01 | 65.37 | 0.00 | 0.00 | 0.00 |
February | 87.90 | 48.82 | 39.08 | 136.77 | 53.74 | 0.00 | 0.00 | 0.00 |
March | 75.16 | 33.20 | 41.96 | 134.71 | 33.17 | 0.00 | 0.00 | 0.00 |
April | 52.79 | 14.90 | 37.89 | 123.32 | 12.16 | 0.00 | 0.00 | 0.00 |
May | 37.96 | 2.81 | 35.15 | 109.99 | 2.46 | 0.00 | 0.00 | 0.00 |
June | 34.73 | 0.59 | 34.13 | 106.97 | 1.99 | 0.00 | 0.00 | 0.00 |
July | 36.22 | 0.50 | 35.72 | 98.92 | 0.59 | 0.00 | 0.00 | 0.00 |
August | 38.42 | 2.05 | 36.37 | 94.67 | 1.86 | 0.00 | 0.00 | 0.00 |
September | 51.51 | 13.37 | 38.14 | 109.97 | 6.56 | 0.00 | 0.00 | 0.00 |
October | 88.62 | 49.48 | 39.13 | 166.54 | 27.71 | 0.00 | 0.00 | 0.00 |
November | 110.69 | 73.16 | 37.53 | 183.84 | 50.00 | 0.00 | 0.00 | 0.00 |
December | 98.79 | 61.90 | 36.88 | 146.67 | 66.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.98 | 29.64 | 37.35 | 128.78 | 26.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.73 | 0.50 | 34.13 | 94.67 | 0.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 110.69 | 73.16 | 41.96 | 183.84 | 66.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.32 | 46.98 | 30.34 | 111.87 | 55.16 | 0.00 | 0.00 | 0.00 |
February | 73.52 | 40.83 | 32.68 | 114.20 | 45.31 | 0.00 | 0.00 | 0.00 |
March | 62.86 | 27.77 | 35.10 | 112.84 | 27.72 | 0.00 | 0.00 | 0.00 |
April | 44.15 | 12.46 | 31.69 | 103.97 | 9.98 | 0.00 | 0.00 | 0.00 |
May | 31.75 | 2.35 | 29.40 | 93.57 | 1.89 | 0.00 | 0.00 | 0.00 |
June | 29.05 | 0.50 | 28.55 | 91.11 | 1.59 | 0.00 | 0.00 | 0.00 |
July | 30.30 | 0.42 | 29.88 | 84.17 | 0.41 | 0.00 | 0.00 | 0.00 |
August | 32.14 | 1.72 | 30.42 | 80.21 | 1.40 | 0.00 | 0.00 | 0.00 |
September | 43.08 | 11.18 | 31.90 | 92.65 | 5.20 | 0.00 | 0.00 | 0.00 |
October | 74.12 | 41.39 | 32.73 | 139.77 | 23.01 | 0.00 | 0.00 | 0.00 |
November | 92.58 | 61.19 | 31.39 | 153.90 | 41.95 | 0.00 | 0.00 | 0.00 |
December | 82.63 | 51.78 | 30.85 | 122.52 | 56.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.02 | 24.79 | 31.24 | 108.33 | 22.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.05 | 0.42 | 28.55 | 80.21 | 0.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.58 | 61.19 | 35.10 | 153.90 | 56.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.32 | 46.98 | 30.34 | 111.87 | 55.16 | 0.00 | 0.00 | 0.00 |
February | 73.52 | 40.83 | 32.68 | 114.20 | 45.31 | 0.00 | 0.00 | 0.00 |
March | 62.86 | 27.77 | 35.10 | 112.84 | 27.72 | 0.00 | 0.00 | 0.00 |
April | 44.15 | 12.46 | 31.69 | 103.97 | 9.98 | 0.00 | 0.00 | 0.00 |
May | 31.75 | 2.35 | 29.40 | 93.57 | 1.89 | 0.00 | 0.00 | 0.00 |
June | 29.05 | 0.50 | 28.55 | 91.11 | 1.59 | 0.00 | 0.00 | 0.00 |
July | 30.30 | 0.42 | 29.88 | 84.17 | 0.41 | 0.00 | 0.00 | 0.00 |
August | 32.14 | 1.72 | 30.42 | 80.21 | 1.40 | 0.00 | 0.00 | 0.00 |
September | 43.08 | 11.18 | 31.90 | 92.65 | 5.20 | 0.00 | 0.00 | 0.00 |
October | 74.12 | 41.39 | 32.73 | 139.77 | 23.01 | 0.00 | 0.00 | 0.00 |
November | 92.58 | 61.19 | 31.39 | 153.90 | 41.95 | 0.00 | 0.00 | 0.00 |
December | 82.63 | 51.78 | 30.85 | 122.52 | 56.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.02 | 24.79 | 31.24 | 108.33 | 22.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.05 | 0.42 | 28.55 | 80.21 | 0.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.58 | 61.19 | 35.10 | 153.90 | 56.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.44 | 56.17 | 36.27 | 133.84 | 65.35 | 0.00 | 0.00 | 0.00 |
February | 87.90 | 48.82 | 39.08 | 136.58 | 53.67 | 0.00 | 0.00 | 0.00 |
March | 75.16 | 33.20 | 41.96 | 134.70 | 32.91 | 0.00 | 0.00 | 0.00 |
April | 52.79 | 14.90 | 37.89 | 123.70 | 11.87 | 0.00 | 0.00 | 0.00 |
May | 37.96 | 2.81 | 35.15 | 110.85 | 2.29 | 0.00 | 0.00 | 0.00 |
June | 34.73 | 0.59 | 34.13 | 107.96 | 1.89 | 0.00 | 0.00 | 0.00 |
July | 36.22 | 0.50 | 35.72 | 99.82 | 0.51 | 0.00 | 0.00 | 0.00 |
August | 38.42 | 2.05 | 36.37 | 95.32 | 1.68 | 0.00 | 0.00 | 0.00 |
September | 51.51 | 13.37 | 38.14 | 110.31 | 6.18 | 0.00 | 0.00 | 0.00 |
October | 88.62 | 49.48 | 39.13 | 166.65 | 27.32 | 0.00 | 0.00 | 0.00 |
November | 110.69 | 73.16 | 37.53 | 183.76 | 49.78 | 0.00 | 0.00 | 0.00 |
December | 98.79 | 61.90 | 36.88 | 146.49 | 66.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.98 | 29.64 | 37.35 | 129.08 | 26.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.73 | 0.50 | 34.13 | 95.32 | 0.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 110.69 | 73.16 | 41.96 | 183.76 | 66.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.32 | 46.98 | 30.34 | 112.01 | 54.89 | 0.00 | 0.00 | 0.00 |
February | 73.52 | 40.83 | 32.68 | 114.31 | 45.10 | 0.00 | 0.00 | 0.00 |
March | 62.86 | 27.77 | 35.10 | 112.92 | 27.59 | 0.00 | 0.00 | 0.00 |
April | 44.15 | 12.46 | 31.69 | 104.05 | 9.90 | 0.00 | 0.00 | 0.00 |
May | 31.75 | 2.35 | 29.40 | 93.66 | 1.86 | 0.00 | 0.00 | 0.00 |
June | 29.05 | 0.50 | 28.55 | 91.21 | 1.57 | 0.00 | 0.00 | 0.00 |
July | 30.30 | 0.42 | 29.88 | 84.25 | 0.40 | 0.00 | 0.00 | 0.00 |
August | 32.14 | 1.72 | 30.42 | 80.28 | 1.38 | 0.00 | 0.00 | 0.00 |
September | 43.08 | 11.18 | 31.90 | 92.70 | 5.14 | 0.00 | 0.00 | 0.00 |
October | 74.12 | 41.39 | 32.73 | 139.81 | 22.93 | 0.00 | 0.00 | 0.00 |
November | 92.58 | 61.19 | 31.39 | 153.96 | 41.85 | 0.00 | 0.00 | 0.00 |
December | 82.63 | 51.78 | 30.85 | 122.63 | 56.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.02 | 24.79 | 31.24 | 108.41 | 22.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.05 | 0.42 | 28.55 | 80.28 | 0.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.58 | 61.19 | 35.10 | 153.96 | 56.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.32 | 46.98 | 30.34 | 112.01 | 54.89 | 0.00 | 0.00 | 0.00 |
February | 73.52 | 40.83 | 32.68 | 114.31 | 45.10 | 0.00 | 0.00 | 0.00 |
March | 62.86 | 27.77 | 35.10 | 112.92 | 27.59 | 0.00 | 0.00 | 0.00 |
April | 44.15 | 12.46 | 31.69 | 104.05 | 9.90 | 0.00 | 0.00 | 0.00 |
May | 31.75 | 2.35 | 29.40 | 93.66 | 1.86 | 0.00 | 0.00 | 0.00 |
June | 29.05 | 0.50 | 28.55 | 91.21 | 1.57 | 0.00 | 0.00 | 0.00 |
July | 30.30 | 0.42 | 29.88 | 84.25 | 0.40 | 0.00 | 0.00 | 0.00 |
August | 32.14 | 1.72 | 30.42 | 80.28 | 1.38 | 0.00 | 0.00 | 0.00 |
September | 43.08 | 11.18 | 31.90 | 92.70 | 5.14 | 0.00 | 0.00 | 0.00 |
October | 74.12 | 41.39 | 32.73 | 139.81 | 22.93 | 0.00 | 0.00 | 0.00 |
November | 92.58 | 61.19 | 31.39 | 153.96 | 41.85 | 0.00 | 0.00 | 0.00 |
December | 82.63 | 51.78 | 30.85 | 122.63 | 56.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.02 | 24.79 | 31.24 | 108.41 | 22.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.05 | 0.42 | 28.55 | 80.28 | 0.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.58 | 61.19 | 35.10 | 153.96 | 56.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.44 | 56.17 | 36.27 | 134.02 | 65.02 | 0.00 | 0.00 | 0.00 |
February | 87.90 | 48.82 | 39.08 | 136.72 | 53.43 | 0.00 | 0.00 | 0.00 |
March | 75.16 | 33.20 | 41.96 | 134.79 | 32.76 | 0.00 | 0.00 | 0.00 |
April | 52.79 | 14.90 | 37.89 | 123.79 | 11.78 | 0.00 | 0.00 | 0.00 |
May | 37.96 | 2.81 | 35.15 | 110.96 | 2.25 | 0.00 | 0.00 | 0.00 |
June | 34.73 | 0.59 | 34.13 | 108.07 | 1.87 | 0.00 | 0.00 | 0.00 |
July | 36.22 | 0.50 | 35.72 | 99.92 | 0.50 | 0.00 | 0.00 | 0.00 |
August | 38.42 | 2.05 | 36.37 | 95.41 | 1.65 | 0.00 | 0.00 | 0.00 |
September | 51.51 | 13.37 | 38.14 | 110.37 | 6.12 | 0.00 | 0.00 | 0.00 |
October | 88.62 | 49.48 | 39.13 | 166.70 | 27.23 | 0.00 | 0.00 | 0.00 |
November | 110.69 | 73.16 | 37.53 | 183.83 | 49.66 | 0.00 | 0.00 | 0.00 |
December | 98.79 | 61.90 | 36.88 | 146.62 | 66.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.98 | 29.64 | 37.35 | 129.18 | 26.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.73 | 0.50 | 34.13 | 95.41 | 0.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 110.69 | 73.16 | 41.96 | 183.83 | 66.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.32 | 46.98 | 30.34 | 112.38 | 54.11 | 0.00 | 0.00 | 0.00 |
February | 73.52 | 40.83 | 32.68 | 114.63 | 44.46 | 0.00 | 0.00 | 0.00 |
March | 62.86 | 27.77 | 35.10 | 113.07 | 27.25 | 0.00 | 0.00 | 0.00 |
April | 44.15 | 12.46 | 31.69 | 104.06 | 9.80 | 0.00 | 0.00 | 0.00 |
May | 31.75 | 2.35 | 29.40 | 93.52 | 1.88 | 0.00 | 0.00 | 0.00 |
June | 29.05 | 0.50 | 28.55 | 91.00 | 1.59 | 0.00 | 0.00 | 0.00 |
July | 30.30 | 0.42 | 29.88 | 83.95 | 0.42 | 0.00 | 0.00 | 0.00 |
August | 32.14 | 1.72 | 30.42 | 80.04 | 1.43 | 0.00 | 0.00 | 0.00 |
September | 43.08 | 11.18 | 31.90 | 92.58 | 5.24 | 0.00 | 0.00 | 0.00 |
October | 74.12 | 41.39 | 32.73 | 139.78 | 22.94 | 0.00 | 0.00 | 0.00 |
November | 92.58 | 61.19 | 31.39 | 154.07 | 41.62 | 0.00 | 0.00 | 0.00 |
December | 82.63 | 51.78 | 30.85 | 122.95 | 55.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.02 | 24.79 | 31.24 | 108.43 | 22.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.05 | 0.42 | 28.55 | 80.04 | 0.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.58 | 61.19 | 35.10 | 154.07 | 55.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.32 | 46.98 | 30.34 | 112.38 | 54.11 | 0.00 | 0.00 | 0.00 |
February | 73.52 | 40.83 | 32.68 | 114.63 | 44.46 | 0.00 | 0.00 | 0.00 |
March | 62.86 | 27.77 | 35.10 | 113.07 | 27.25 | 0.00 | 0.00 | 0.00 |
April | 44.15 | 12.46 | 31.69 | 104.06 | 9.80 | 0.00 | 0.00 | 0.00 |
May | 31.75 | 2.35 | 29.40 | 93.52 | 1.88 | 0.00 | 0.00 | 0.00 |
June | 29.05 | 0.50 | 28.55 | 91.00 | 1.59 | 0.00 | 0.00 | 0.00 |
July | 30.30 | 0.42 | 29.88 | 83.95 | 0.42 | 0.00 | 0.00 | 0.00 |
August | 32.14 | 1.72 | 30.42 | 80.04 | 1.43 | 0.00 | 0.00 | 0.00 |
September | 43.08 | 11.18 | 31.90 | 92.58 | 5.24 | 0.00 | 0.00 | 0.00 |
October | 74.12 | 41.39 | 32.73 | 139.78 | 22.94 | 0.00 | 0.00 | 0.00 |
November | 92.58 | 61.19 | 31.39 | 154.07 | 41.62 | 0.00 | 0.00 | 0.00 |
December | 82.63 | 51.78 | 30.85 | 122.95 | 55.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.02 | 24.79 | 31.24 | 108.43 | 22.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.05 | 0.42 | 28.55 | 80.04 | 0.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.58 | 61.19 | 35.10 | 154.07 | 55.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.44 | 56.17 | 36.27 | 134.46 | 64.11 | 0.00 | 0.00 | 0.00 |
February | 87.90 | 48.82 | 39.08 | 137.10 | 52.68 | 0.00 | 0.00 | 0.00 |
March | 75.16 | 33.20 | 41.96 | 134.97 | 32.36 | 0.00 | 0.00 | 0.00 |
April | 52.79 | 14.90 | 37.89 | 123.80 | 11.66 | 0.00 | 0.00 | 0.00 |
May | 37.96 | 2.81 | 35.15 | 110.79 | 2.27 | 0.00 | 0.00 | 0.00 |
June | 34.73 | 0.59 | 34.13 | 107.81 | 1.88 | 0.00 | 0.00 | 0.00 |
July | 36.22 | 0.50 | 35.72 | 99.56 | 0.51 | 0.00 | 0.00 | 0.00 |
August | 38.42 | 2.05 | 36.37 | 95.12 | 1.72 | 0.00 | 0.00 | 0.00 |
September | 51.51 | 13.37 | 38.14 | 110.22 | 6.24 | 0.00 | 0.00 | 0.00 |
October | 88.62 | 49.48 | 39.13 | 166.66 | 27.24 | 0.00 | 0.00 | 0.00 |
November | 110.69 | 73.16 | 37.53 | 183.95 | 49.38 | 0.00 | 0.00 | 0.00 |
December | 98.79 | 61.90 | 36.88 | 147.00 | 65.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.98 | 29.64 | 37.35 | 129.20 | 26.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.73 | 0.50 | 34.13 | 95.12 | 0.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 110.69 | 73.16 | 41.96 | 183.95 | 65.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.32 | 46.98 | 30.34 | 112.99 | 51.87 | 0.00 | 0.00 | 0.00 |
February | 73.52 | 40.83 | 32.68 | 115.20 | 42.31 | 0.00 | 0.00 | 0.00 |
March | 62.86 | 27.77 | 35.10 | 113.17 | 25.97 | 0.00 | 0.00 | 0.00 |
April | 44.15 | 12.46 | 31.69 | 103.28 | 9.57 | 0.00 | 0.00 | 0.00 |
May | 31.75 | 2.35 | 29.40 | 91.79 | 2.04 | 0.00 | 0.00 | 0.00 |
June | 29.05 | 0.50 | 28.55 | 88.80 | 1.71 | 0.00 | 0.00 | 0.00 |
July | 30.30 | 0.42 | 29.88 | 81.40 | 0.57 | 0.00 | 0.00 | 0.00 |
August | 32.14 | 1.72 | 30.42 | 77.94 | 1.90 | 0.00 | 0.00 | 0.00 |
September | 43.08 | 11.18 | 31.90 | 91.29 | 6.16 | 0.00 | 0.00 | 0.00 |
October | 74.12 | 41.39 | 32.73 | 139.05 | 23.38 | 0.00 | 0.00 | 0.00 |
November | 92.58 | 61.19 | 31.39 | 154.00 | 40.92 | 0.00 | 0.00 | 0.00 |
December | 82.63 | 51.78 | 30.85 | 123.49 | 53.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.02 | 24.79 | 31.24 | 107.62 | 21.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.05 | 0.42 | 28.55 | 77.94 | 0.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.58 | 61.19 | 35.10 | 154.00 | 53.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.32 | 46.98 | 30.34 | 112.99 | 51.87 | 0.00 | 0.00 | 0.00 |
February | 73.52 | 40.83 | 32.68 | 115.20 | 42.31 | 0.00 | 0.00 | 0.00 |
March | 62.86 | 27.77 | 35.10 | 113.17 | 25.97 | 0.00 | 0.00 | 0.00 |
April | 44.15 | 12.46 | 31.69 | 103.28 | 9.57 | 0.00 | 0.00 | 0.00 |
May | 31.75 | 2.35 | 29.40 | 91.79 | 2.04 | 0.00 | 0.00 | 0.00 |
June | 29.05 | 0.50 | 28.55 | 88.80 | 1.71 | 0.00 | 0.00 | 0.00 |
July | 30.30 | 0.42 | 29.88 | 81.40 | 0.57 | 0.00 | 0.00 | 0.00 |
August | 32.14 | 1.72 | 30.42 | 77.94 | 1.90 | 0.00 | 0.00 | 0.00 |
September | 43.08 | 11.18 | 31.90 | 91.29 | 6.16 | 0.00 | 0.00 | 0.00 |
October | 74.12 | 41.39 | 32.73 | 139.05 | 23.38 | 0.00 | 0.00 | 0.00 |
November | 92.58 | 61.19 | 31.39 | 154.00 | 40.92 | 0.00 | 0.00 | 0.00 |
December | 82.63 | 51.78 | 30.85 | 123.49 | 53.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.02 | 24.79 | 31.24 | 107.62 | 21.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.05 | 0.42 | 28.55 | 77.94 | 0.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.58 | 61.19 | 35.10 | 154.00 | 53.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.44 | 56.17 | 36.27 | 135.19 | 61.46 | 0.00 | 0.00 | 0.00 |
February | 87.90 | 48.82 | 39.08 | 137.78 | 50.15 | 0.00 | 0.00 | 0.00 |
March | 75.16 | 33.20 | 41.96 | 135.09 | 30.86 | 0.00 | 0.00 | 0.00 |
April | 52.79 | 14.90 | 37.89 | 122.87 | 11.38 | 0.00 | 0.00 | 0.00 |
May | 37.96 | 2.81 | 35.15 | 108.73 | 2.47 | 0.00 | 0.00 | 0.00 |
June | 34.73 | 0.59 | 34.13 | 105.19 | 2.03 | 0.00 | 0.00 | 0.00 |
July | 36.22 | 0.50 | 35.72 | 96.53 | 0.70 | 0.00 | 0.00 | 0.00 |
August | 38.42 | 2.05 | 36.37 | 92.61 | 2.27 | 0.00 | 0.00 | 0.00 |
September | 51.51 | 13.37 | 38.14 | 108.67 | 7.33 | 0.00 | 0.00 | 0.00 |
October | 88.62 | 49.48 | 39.13 | 165.78 | 27.77 | 0.00 | 0.00 | 0.00 |
November | 110.69 | 73.16 | 37.53 | 183.87 | 48.56 | 0.00 | 0.00 | 0.00 |
December | 98.79 | 61.90 | 36.88 | 147.64 | 63.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.98 | 29.64 | 37.35 | 128.23 | 25.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.73 | 0.50 | 34.13 | 92.61 | 0.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 110.69 | 73.16 | 41.96 | 183.87 | 63.73 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207091E+09 | 0.125834E+09 | 81257288.09 | 0.297426E+09 | 0.154036E+09 |
February | 0.177858E+09 | 98787087.29 | 79070412.96 | 0.275976E+09 | 0.110808E+09 |
March | 0.168366E+09 | 74365858.93 | 94000120.98 | 0.302564E+09 | 72986813.73 |
April | 0.114446E+09 | 32300174.04 | 82145771.14 | 0.272115E+09 | 24050277.95 |
May | 85045136.14 | 6295651.56 | 78749484.58 | 0.256261E+09 | 4183719.61 |
June | 75284903.70 | 1284716.20 | 74000187.51 | 0.240656E+09 | 3145087.29 |
July | 81146974.60 | 1116110.20 | 80030864.39 | 0.232644E+09 | 1019824.85 |
August | 86079759.40 | 4597308.19 | 81482451.22 | 0.218449E+09 | 3139085.05 |
September | 0.111674E+09 | 28985325.40 | 82689055.74 | 0.242528E+09 | 11695833.01 |
October | 0.198528E+09 | 0.110857E+09 | 87670930.57 | 0.375135E+09 | 58589930.10 |
November | 0.239973E+09 | 0.158617E+09 | 81356023.64 | 0.398794E+09 | 0.108235E+09 |
December | 0.221309E+09 | 0.138678E+09 | 82630682.34 | 0.327252E+09 | 0.153675E+09 |
Annual Sum or Average | 0.176680E+10 | 0.781719E+09 | 0.985083E+09 | 0.343980E+10 | 0.705565E+09 |
Minimum of Months | 75284903.70 | 1116110.20 | 74000187.51 | 0.218449E+09 | 1019824.85 |
Maximum of Months | 0.239973E+09 | 0.158617E+09 | 94000120.98 | 0.398794E+09 | 0.154036E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207091E+09 | 0.125834E+09 | 81257288.09 | 0.297426E+09 | 0.154036E+09 |
February | 0.177858E+09 | 98787087.29 | 79070412.96 | 0.275976E+09 | 0.110808E+09 |
March | 0.168366E+09 | 74365858.93 | 94000120.98 | 0.302564E+09 | 72986813.73 |
April | 0.114446E+09 | 32300174.04 | 82145771.14 | 0.272115E+09 | 24050277.95 |
May | 85045136.14 | 6295651.56 | 78749484.58 | 0.256261E+09 | 4183719.61 |
June | 75284903.70 | 1284716.20 | 74000187.51 | 0.240656E+09 | 3145087.29 |
July | 81146974.60 | 1116110.20 | 80030864.39 | 0.232644E+09 | 1019824.85 |
August | 86079759.40 | 4597308.19 | 81482451.22 | 0.218449E+09 | 3139085.05 |
September | 0.111674E+09 | 28985325.40 | 82689055.74 | 0.242528E+09 | 11695833.01 |
October | 0.198528E+09 | 0.110857E+09 | 87670930.57 | 0.375135E+09 | 58589930.10 |
November | 0.239973E+09 | 0.158617E+09 | 81356023.64 | 0.398794E+09 | 0.108235E+09 |
December | 0.221309E+09 | 0.138678E+09 | 82630682.34 | 0.327252E+09 | 0.153675E+09 |
Annual Sum or Average | 0.176680E+10 | 0.781719E+09 | 0.985083E+09 | 0.343980E+10 | 0.705565E+09 |
Minimum of Months | 75284903.70 | 1116110.20 | 74000187.51 | 0.218449E+09 | 1019824.85 |
Maximum of Months | 0.239973E+09 | 0.158617E+09 | 94000120.98 | 0.398794E+09 | 0.154036E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207091E+09 | 0.125834E+09 | 81257288.09 | 0.297426E+09 | 0.154036E+09 |
February | 0.177858E+09 | 98787087.29 | 79070412.96 | 0.275976E+09 | 0.110808E+09 |
March | 0.168366E+09 | 74365858.93 | 94000120.98 | 0.302564E+09 | 72986813.73 |
April | 0.114446E+09 | 32300174.04 | 82145771.14 | 0.272115E+09 | 24050277.95 |
May | 85045136.14 | 6295651.56 | 78749484.58 | 0.256261E+09 | 4183719.61 |
June | 75284903.70 | 1284716.20 | 74000187.51 | 0.240656E+09 | 3145087.29 |
July | 81146974.60 | 1116110.20 | 80030864.39 | 0.232644E+09 | 1019824.85 |
August | 86079759.40 | 4597308.19 | 81482451.22 | 0.218449E+09 | 3139085.05 |
September | 0.111674E+09 | 28985325.40 | 82689055.74 | 0.242528E+09 | 11695833.01 |
October | 0.198528E+09 | 0.110857E+09 | 87670930.57 | 0.375135E+09 | 58589930.10 |
November | 0.239973E+09 | 0.158617E+09 | 81356023.64 | 0.398794E+09 | 0.108235E+09 |
December | 0.221309E+09 | 0.138678E+09 | 82630682.34 | 0.327252E+09 | 0.153675E+09 |
Annual Sum or Average | 0.176680E+10 | 0.781719E+09 | 0.985083E+09 | 0.343980E+10 | 0.705565E+09 |
Minimum of Months | 75284903.70 | 1116110.20 | 74000187.51 | 0.218449E+09 | 1019824.85 |
Maximum of Months | 0.239973E+09 | 0.158617E+09 | 94000120.98 | 0.398794E+09 | 0.154036E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207091E+09 | 0.125834E+09 | 81257288.09 | 0.297426E+09 | 0.154036E+09 |
February | 0.177858E+09 | 98787087.29 | 79070412.96 | 0.275976E+09 | 0.110808E+09 |
March | 0.168366E+09 | 74365858.93 | 94000120.98 | 0.302564E+09 | 72986813.73 |
April | 0.114446E+09 | 32300174.04 | 82145771.14 | 0.272115E+09 | 24050277.95 |
May | 85045136.14 | 6295651.56 | 78749484.58 | 0.256261E+09 | 4183719.61 |
June | 75284903.70 | 1284716.20 | 74000187.51 | 0.240656E+09 | 3145087.29 |
July | 81146974.60 | 1116110.20 | 80030864.39 | 0.232644E+09 | 1019824.85 |
August | 86079759.40 | 4597308.19 | 81482451.22 | 0.218449E+09 | 3139085.05 |
September | 0.111674E+09 | 28985325.40 | 82689055.74 | 0.242528E+09 | 11695833.01 |
October | 0.198528E+09 | 0.110857E+09 | 87670930.57 | 0.375135E+09 | 58589930.10 |
November | 0.239973E+09 | 0.158617E+09 | 81356023.64 | 0.398794E+09 | 0.108235E+09 |
December | 0.221309E+09 | 0.138678E+09 | 82630682.34 | 0.327252E+09 | 0.153675E+09 |
Annual Sum or Average | 0.176680E+10 | 0.781719E+09 | 0.985083E+09 | 0.343980E+10 | 0.705565E+09 |
Minimum of Months | 75284903.70 | 1116110.20 | 74000187.51 | 0.218449E+09 | 1019824.85 |
Maximum of Months | 0.239973E+09 | 0.158617E+09 | 94000120.98 | 0.398794E+09 | 0.154036E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.248956E+09 | 0.151272E+09 | 97683769.91 | 0.357683E+09 | 0.183572E+09 |
February | 0.213812E+09 | 0.118757E+09 | 95054809.34 | 0.331768E+09 | 0.132074E+09 |
March | 0.202402E+09 | 89399211.13 | 0.113003E+09 | 0.363025E+09 | 87240911.74 |
April | 0.137582E+09 | 38829781.84 | 98751863.32 | 0.325366E+09 | 28797307.88 |
May | 0.102237E+09 | 7568342.39 | 94669004.02 | 0.305081E+09 | 5087031.62 |
June | 90504044.43 | 1544426.65 | 88959617.78 | 0.286544E+09 | 3765660.54 |
July | 97551156.12 | 1341736.29 | 96209419.82 | 0.277176E+09 | 1247402.96 |
August | 0.103481E+09 | 5526672.20 | 97954450.66 | 0.260817E+09 | 3792191.82 |
September | 0.134250E+09 | 34844823.45 | 99404975.05 | 0.290120E+09 | 14016394.13 |
October | 0.238662E+09 | 0.133268E+09 | 0.105394E+09 | 0.449585E+09 | 70077260.73 |
November | 0.288485E+09 | 0.190682E+09 | 97802465.24 | 0.478642E+09 | 0.129254E+09 |
December | 0.266048E+09 | 0.166713E+09 | 99334801.24 | 0.393289E+09 | 0.183245E+09 |
Annual Sum or Average | 0.212397E+10 | 0.939747E+09 | 0.118422E+10 | 0.411910E+10 | 0.842169E+09 |
Minimum of Months | 90504044.43 | 1341736.29 | 88959617.78 | 0.260817E+09 | 1247402.96 |
Maximum of Months | 0.288485E+09 | 0.190682E+09 | 0.113003E+09 | 0.478642E+09 | 0.183572E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.248956E+09 | 0.151272E+09 | 97683769.91 | 0.357683E+09 | 0.183572E+09 |
February | 0.213812E+09 | 0.118757E+09 | 95054809.34 | 0.331768E+09 | 0.132074E+09 |
March | 0.202402E+09 | 89399211.13 | 0.113003E+09 | 0.363025E+09 | 87240911.74 |
April | 0.137582E+09 | 38829781.84 | 98751863.32 | 0.325366E+09 | 28797307.88 |
May | 0.102237E+09 | 7568342.39 | 94669004.02 | 0.305081E+09 | 5087031.62 |
June | 90504044.43 | 1544426.65 | 88959617.78 | 0.286544E+09 | 3765660.54 |
July | 97551156.12 | 1341736.29 | 96209419.82 | 0.277176E+09 | 1247402.96 |
August | 0.103481E+09 | 5526672.20 | 97954450.66 | 0.260817E+09 | 3792191.82 |
September | 0.134250E+09 | 34844823.45 | 99404975.05 | 0.290120E+09 | 14016394.13 |
October | 0.238662E+09 | 0.133268E+09 | 0.105394E+09 | 0.449585E+09 | 70077260.73 |
November | 0.288485E+09 | 0.190682E+09 | 97802465.24 | 0.478642E+09 | 0.129254E+09 |
December | 0.266048E+09 | 0.166713E+09 | 99334801.24 | 0.393289E+09 | 0.183245E+09 |
Annual Sum or Average | 0.212397E+10 | 0.939747E+09 | 0.118422E+10 | 0.411910E+10 | 0.842169E+09 |
Minimum of Months | 90504044.43 | 1341736.29 | 88959617.78 | 0.260817E+09 | 1247402.96 |
Maximum of Months | 0.288485E+09 | 0.190682E+09 | 0.113003E+09 | 0.478642E+09 | 0.183572E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207091E+09 | 0.125834E+09 | 81257288.09 | 0.294467E+09 | 0.159921E+09 |
February | 0.177858E+09 | 98787087.29 | 79070412.96 | 0.273999E+09 | 0.113973E+09 |
March | 0.168366E+09 | 74365858.93 | 94000120.98 | 0.301735E+09 | 74433596.56 |
April | 0.114446E+09 | 32300174.04 | 82145771.14 | 0.273056E+09 | 24445779.88 |
May | 85045136.14 | 6295651.56 | 78749484.58 | 0.258879E+09 | 4116203.84 |
June | 75284903.70 | 1284716.20 | 74000187.51 | 0.243954E+09 | 3114061.21 |
July | 81146974.60 | 1116110.20 | 80030864.39 | 0.236089E+09 | 922290.22 |
August | 86079759.40 | 4597308.19 | 81482451.22 | 0.221398E+09 | 2819854.33 |
September | 0.111674E+09 | 28985325.40 | 82689055.74 | 0.244378E+09 | 10991005.23 |
October | 0.198528E+09 | 0.110857E+09 | 87670930.57 | 0.375782E+09 | 58240106.37 |
November | 0.239973E+09 | 0.158617E+09 | 81356023.64 | 0.398154E+09 | 0.108991E+09 |
December | 0.221309E+09 | 0.138678E+09 | 82630682.34 | 0.325085E+09 | 0.157431E+09 |
Annual Sum or Average | 0.176680E+10 | 0.781719E+09 | 0.985083E+09 | 0.344698E+10 | 0.719399E+09 |
Minimum of Months | 75284903.70 | 1116110.20 | 74000187.51 | 0.221398E+09 | 922290.22 |
Maximum of Months | 0.239973E+09 | 0.158617E+09 | 94000120.98 | 0.398154E+09 | 0.159921E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207091E+09 | 0.125834E+09 | 81257288.09 | 0.294467E+09 | 0.159921E+09 |
February | 0.177858E+09 | 98787087.29 | 79070412.96 | 0.273999E+09 | 0.113973E+09 |
March | 0.168366E+09 | 74365858.93 | 94000120.98 | 0.301735E+09 | 74433596.56 |
April | 0.114446E+09 | 32300174.04 | 82145771.14 | 0.273056E+09 | 24445779.88 |
May | 85045136.14 | 6295651.56 | 78749484.58 | 0.258879E+09 | 4116203.84 |
June | 75284903.70 | 1284716.20 | 74000187.51 | 0.243954E+09 | 3114061.21 |
July | 81146974.60 | 1116110.20 | 80030864.39 | 0.236089E+09 | 922290.22 |
August | 86079759.40 | 4597308.19 | 81482451.22 | 0.221398E+09 | 2819854.33 |
September | 0.111674E+09 | 28985325.40 | 82689055.74 | 0.244378E+09 | 10991005.23 |
October | 0.198528E+09 | 0.110857E+09 | 87670930.57 | 0.375782E+09 | 58240106.37 |
November | 0.239973E+09 | 0.158617E+09 | 81356023.64 | 0.398154E+09 | 0.108991E+09 |
December | 0.221309E+09 | 0.138678E+09 | 82630682.34 | 0.325085E+09 | 0.157431E+09 |
Annual Sum or Average | 0.176680E+10 | 0.781719E+09 | 0.985083E+09 | 0.344698E+10 | 0.719399E+09 |
Minimum of Months | 75284903.70 | 1116110.20 | 74000187.51 | 0.221398E+09 | 922290.22 |
Maximum of Months | 0.239973E+09 | 0.158617E+09 | 94000120.98 | 0.398154E+09 | 0.159921E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.248956E+09 | 0.151272E+09 | 97683769.91 | 0.354239E+09 | 0.190507E+09 |
February | 0.213812E+09 | 0.118757E+09 | 95054809.34 | 0.329497E+09 | 0.135800E+09 |
March | 0.202402E+09 | 89399211.13 | 0.113003E+09 | 0.362094E+09 | 88948551.57 |
April | 0.137582E+09 | 38829781.84 | 98751863.32 | 0.326502E+09 | 29271653.28 |
May | 0.102237E+09 | 7568342.39 | 94669004.02 | 0.308144E+09 | 5011052.23 |
June | 90504044.43 | 1544426.65 | 88959617.78 | 0.290438E+09 | 3727427.48 |
July | 97551156.12 | 1341736.29 | 96209419.82 | 0.281247E+09 | 1129216.25 |
August | 0.103481E+09 | 5526672.20 | 97954450.66 | 0.264348E+09 | 3409217.83 |
September | 0.134250E+09 | 34844823.45 | 99404975.05 | 0.292379E+09 | 13176965.21 |
October | 0.238662E+09 | 0.133268E+09 | 0.105394E+09 | 0.450427E+09 | 69647569.87 |
November | 0.288485E+09 | 0.190682E+09 | 97802465.24 | 0.477967E+09 | 0.130131E+09 |
December | 0.266048E+09 | 0.166713E+09 | 99334801.24 | 0.390786E+09 | 0.187667E+09 |
Annual Sum or Average | 0.212397E+10 | 0.939747E+09 | 0.118422E+10 | 0.412807E+10 | 0.858428E+09 |
Minimum of Months | 90504044.43 | 1341736.29 | 88959617.78 | 0.264348E+09 | 1129216.25 |
Maximum of Months | 0.288485E+09 | 0.190682E+09 | 0.113003E+09 | 0.477967E+09 | 0.190507E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207091E+09 | 0.125834E+09 | 81257288.09 | 0.296211E+09 | 0.155796E+09 |
February | 0.177858E+09 | 98787087.29 | 79070412.96 | 0.274612E+09 | 0.114051E+09 |
March | 0.168366E+09 | 74365858.93 | 94000120.98 | 0.301269E+09 | 77972251.58 |
April | 0.114446E+09 | 32300174.04 | 82145771.14 | 0.268368E+09 | 28157759.12 |
May | 85045136.14 | 6295651.56 | 78749484.58 | 0.248952E+09 | 5799751.24 |
June | 75284903.70 | 1284716.20 | 74000187.51 | 0.233856E+09 | 4495801.52 |
July | 81146974.60 | 1116110.20 | 80030864.39 | 0.224539E+09 | 1516645.24 |
August | 86079759.40 | 4597308.19 | 81482451.22 | 0.213701E+09 | 4773280.57 |
September | 0.111674E+09 | 28985325.40 | 82689055.74 | 0.239975E+09 | 15512500.07 |
October | 0.198528E+09 | 0.110857E+09 | 87670930.57 | 0.374545E+09 | 64389163.61 |
November | 0.239973E+09 | 0.158617E+09 | 81356023.64 | 0.398325E+09 | 0.111889E+09 |
December | 0.221309E+09 | 0.138678E+09 | 82630682.34 | 0.326201E+09 | 0.156089E+09 |
Annual Sum or Average | 0.176680E+10 | 0.781719E+09 | 0.985083E+09 | 0.340055E+10 | 0.740443E+09 |
Minimum of Months | 75284903.70 | 1116110.20 | 74000187.51 | 0.213701E+09 | 1516645.24 |
Maximum of Months | 0.239973E+09 | 0.158617E+09 | 94000120.98 | 0.398325E+09 | 0.156089E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207091E+09 | 0.125834E+09 | 81257288.09 | 0.296211E+09 | 0.155796E+09 |
February | 0.177858E+09 | 98787087.29 | 79070412.96 | 0.274612E+09 | 0.114051E+09 |
March | 0.168366E+09 | 74365858.93 | 94000120.98 | 0.301269E+09 | 77972251.58 |
April | 0.114446E+09 | 32300174.04 | 82145771.14 | 0.268368E+09 | 28157759.12 |
May | 85045136.14 | 6295651.56 | 78749484.58 | 0.248952E+09 | 5799751.24 |
June | 75284903.70 | 1284716.20 | 74000187.51 | 0.233856E+09 | 4495801.52 |
July | 81146974.60 | 1116110.20 | 80030864.39 | 0.224539E+09 | 1516645.24 |
August | 86079759.40 | 4597308.19 | 81482451.22 | 0.213701E+09 | 4773280.57 |
September | 0.111674E+09 | 28985325.40 | 82689055.74 | 0.239975E+09 | 15512500.07 |
October | 0.198528E+09 | 0.110857E+09 | 87670930.57 | 0.374545E+09 | 64389163.61 |
November | 0.239973E+09 | 0.158617E+09 | 81356023.64 | 0.398325E+09 | 0.111889E+09 |
December | 0.221309E+09 | 0.138678E+09 | 82630682.34 | 0.326201E+09 | 0.156089E+09 |
Annual Sum or Average | 0.176680E+10 | 0.781719E+09 | 0.985083E+09 | 0.340055E+10 | 0.740443E+09 |
Minimum of Months | 75284903.70 | 1116110.20 | 74000187.51 | 0.213701E+09 | 1516645.24 |
Maximum of Months | 0.239973E+09 | 0.158617E+09 | 94000120.98 | 0.398325E+09 | 0.156089E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.247595E+09 | 0.150445E+09 | 97149978.82 | 0.354390E+09 | 0.184571E+09 |
February | 0.212644E+09 | 0.118108E+09 | 94535384.15 | 0.328431E+09 | 0.135100E+09 |
March | 0.201296E+09 | 88910690.85 | 0.112385E+09 | 0.359580E+09 | 92570649.10 |
April | 0.136830E+09 | 38617597.24 | 98212235.66 | 0.319270E+09 | 33481504.72 |
May | 0.101679E+09 | 7526985.33 | 94151687.06 | 0.294947E+09 | 7015944.97 |
June | 90009486.81 | 1535987.16 | 88473499.65 | 0.277078E+09 | 5337320.41 |
July | 97018089.69 | 1334404.40 | 95683685.29 | 0.266295E+09 | 1854693.71 |
August | 0.102916E+09 | 5496471.81 | 97419180.44 | 0.253959E+09 | 5708574.00 |
September | 0.133516E+09 | 34654414.58 | 98861778.46 | 0.285689E+09 | 18444857.38 |
October | 0.237357E+09 | 0.132539E+09 | 0.104818E+09 | 0.446523E+09 | 76460343.31 |
November | 0.286908E+09 | 0.189640E+09 | 97268025.54 | 0.475559E+09 | 0.132764E+09 |
December | 0.264594E+09 | 0.165802E+09 | 98791988.12 | 0.389986E+09 | 0.185007E+09 |
Annual Sum or Average | 0.211236E+10 | 0.934612E+09 | 0.117775E+10 | 0.405171E+10 | 0.878316E+09 |
Minimum of Months | 90009486.81 | 1334404.40 | 88473499.65 | 0.253959E+09 | 1854693.71 |
Maximum of Months | 0.286908E+09 | 0.189640E+09 | 0.112385E+09 | 0.475559E+09 | 0.185007E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207091E+09 | 0.125834E+09 | 81257288.09 | 0.297183E+09 | 0.153238E+09 |
February | 0.177858E+09 | 98787087.29 | 79070412.96 | 0.275000E+09 | 0.113028E+09 |
March | 0.168366E+09 | 74365858.93 | 94000120.98 | 0.301330E+09 | 77851319.33 |
April | 0.114446E+09 | 32300174.04 | 82145771.14 | 0.268064E+09 | 28661474.44 |
May | 85045136.14 | 6295651.56 | 78749484.58 | 0.247933E+09 | 6264391.15 |
June | 75284903.70 | 1284716.20 | 74000187.51 | 0.232690E+09 | 4785495.92 |
July | 81146974.60 | 1116110.20 | 80030864.39 | 0.223157E+09 | 1681460.40 |
August | 86079759.40 | 4597308.19 | 81482451.22 | 0.212901E+09 | 5127456.41 |
September | 0.111674E+09 | 28985325.40 | 82689055.74 | 0.239686E+09 | 16265604.59 |
October | 0.198528E+09 | 0.110857E+09 | 87670930.57 | 0.374415E+09 | 64936310.55 |
November | 0.239973E+09 | 0.158617E+09 | 81356023.64 | 0.398441E+09 | 0.111574E+09 |
December | 0.221309E+09 | 0.138678E+09 | 82630682.34 | 0.326766E+09 | 0.154639E+09 |
Annual Sum or Average | 0.176680E+10 | 0.781719E+09 | 0.985083E+09 | 0.339756E+10 | 0.738052E+09 |
Minimum of Months | 75284903.70 | 1116110.20 | 74000187.51 | 0.212901E+09 | 1681460.40 |
Maximum of Months | 0.239973E+09 | 0.158617E+09 | 94000120.98 | 0.398441E+09 | 0.154639E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207091E+09 | 0.125834E+09 | 81257288.09 | 0.297183E+09 | 0.153238E+09 |
February | 0.177858E+09 | 98787087.29 | 79070412.96 | 0.275000E+09 | 0.113028E+09 |
March | 0.168366E+09 | 74365858.93 | 94000120.98 | 0.301330E+09 | 77851319.33 |
April | 0.114446E+09 | 32300174.04 | 82145771.14 | 0.268064E+09 | 28661474.44 |
May | 85045136.14 | 6295651.56 | 78749484.58 | 0.247933E+09 | 6264391.15 |
June | 75284903.70 | 1284716.20 | 74000187.51 | 0.232690E+09 | 4785495.92 |
July | 81146974.60 | 1116110.20 | 80030864.39 | 0.223157E+09 | 1681460.40 |
August | 86079759.40 | 4597308.19 | 81482451.22 | 0.212901E+09 | 5127456.41 |
September | 0.111674E+09 | 28985325.40 | 82689055.74 | 0.239686E+09 | 16265604.59 |
October | 0.198528E+09 | 0.110857E+09 | 87670930.57 | 0.374415E+09 | 64936310.55 |
November | 0.239973E+09 | 0.158617E+09 | 81356023.64 | 0.398441E+09 | 0.111574E+09 |
December | 0.221309E+09 | 0.138678E+09 | 82630682.34 | 0.326766E+09 | 0.154639E+09 |
Annual Sum or Average | 0.176680E+10 | 0.781719E+09 | 0.985083E+09 | 0.339756E+10 | 0.738052E+09 |
Minimum of Months | 75284903.70 | 1116110.20 | 74000187.51 | 0.212901E+09 | 1681460.40 |
Maximum of Months | 0.239973E+09 | 0.158617E+09 | 94000120.98 | 0.398441E+09 | 0.154639E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.247595E+09 | 0.150445E+09 | 97149978.82 | 0.355554E+09 | 0.181542E+09 |
February | 0.212644E+09 | 0.118108E+09 | 94535384.15 | 0.328894E+09 | 0.133889E+09 |
March | 0.201296E+09 | 88910690.85 | 0.112385E+09 | 0.359654E+09 | 92427711.21 |
April | 0.136830E+09 | 38617597.24 | 98212235.66 | 0.318906E+09 | 34079400.05 |
May | 0.101679E+09 | 7526985.33 | 94151687.06 | 0.293750E+09 | 7579434.49 |
June | 90009486.81 | 1535987.16 | 88473499.65 | 0.275693E+09 | 5682604.99 |
July | 97018089.69 | 1334404.40 | 95683685.29 | 0.264664E+09 | 2055572.87 |
August | 0.102916E+09 | 5496471.81 | 97419180.44 | 0.253014E+09 | 6133458.25 |
September | 0.133516E+09 | 34654414.58 | 98861778.46 | 0.285344E+09 | 19338422.49 |
October | 0.237357E+09 | 0.132539E+09 | 0.104818E+09 | 0.446366E+09 | 77109794.58 |
November | 0.286908E+09 | 0.189640E+09 | 97268025.54 | 0.475699E+09 | 0.132390E+09 |
December | 0.264594E+09 | 0.165802E+09 | 98791988.12 | 0.390663E+09 | 0.183288E+09 |
Annual Sum or Average | 0.211236E+10 | 0.934612E+09 | 0.117775E+10 | 0.404820E+10 | 0.875516E+09 |
Minimum of Months | 90009486.81 | 1334404.40 | 88473499.65 | 0.253014E+09 | 2055572.87 |
Maximum of Months | 0.286908E+09 | 0.189640E+09 | 0.112385E+09 | 0.475699E+09 | 0.183288E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207091E+09 | 0.125834E+09 | 81257288.09 | 0.298135E+09 | 0.151147E+09 |
February | 0.177858E+09 | 98787087.29 | 79070412.96 | 0.275495E+09 | 0.111896E+09 |
March | 0.168366E+09 | 74365858.93 | 94000120.98 | 0.301632E+09 | 77001532.35 |
April | 0.114446E+09 | 32300174.04 | 82145771.14 | 0.268375E+09 | 28105070.53 |
May | 85045136.14 | 6295651.56 | 78749484.58 | 0.248365E+09 | 6033471.53 |
June | 75284903.70 | 1284716.20 | 74000187.51 | 0.233233E+09 | 4658536.07 |
July | 81146974.60 | 1116110.20 | 80030864.39 | 0.223555E+09 | 1567245.98 |
August | 86079759.40 | 4597308.19 | 81482451.22 | 0.213269E+09 | 4876346.60 |
September | 0.111674E+09 | 28985325.40 | 82689055.74 | 0.239850E+09 | 15758393.79 |
October | 0.198528E+09 | 0.110857E+09 | 87670930.57 | 0.374559E+09 | 64333397.09 |
November | 0.239973E+09 | 0.158617E+09 | 81356023.64 | 0.398705E+09 | 0.110837E+09 |
December | 0.221309E+09 | 0.138678E+09 | 82630682.34 | 0.327380E+09 | 0.153356E+09 |
Annual Sum or Average | 0.176680E+10 | 0.781719E+09 | 0.985083E+09 | 0.340255E+10 | 0.729570E+09 |
Minimum of Months | 75284903.70 | 1116110.20 | 74000187.51 | 0.213269E+09 | 1567245.98 |
Maximum of Months | 0.239973E+09 | 0.158617E+09 | 94000120.98 | 0.398705E+09 | 0.153356E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207091E+09 | 0.125834E+09 | 81257288.09 | 0.298135E+09 | 0.151147E+09 |
February | 0.177858E+09 | 98787087.29 | 79070412.96 | 0.275495E+09 | 0.111896E+09 |
March | 0.168366E+09 | 74365858.93 | 94000120.98 | 0.301632E+09 | 77001532.35 |
April | 0.114446E+09 | 32300174.04 | 82145771.14 | 0.268375E+09 | 28105070.53 |
May | 85045136.14 | 6295651.56 | 78749484.58 | 0.248365E+09 | 6033471.53 |
June | 75284903.70 | 1284716.20 | 74000187.51 | 0.233233E+09 | 4658536.07 |
July | 81146974.60 | 1116110.20 | 80030864.39 | 0.223555E+09 | 1567245.98 |
August | 86079759.40 | 4597308.19 | 81482451.22 | 0.213269E+09 | 4876346.60 |
September | 0.111674E+09 | 28985325.40 | 82689055.74 | 0.239850E+09 | 15758393.79 |
October | 0.198528E+09 | 0.110857E+09 | 87670930.57 | 0.374559E+09 | 64333397.09 |
November | 0.239973E+09 | 0.158617E+09 | 81356023.64 | 0.398705E+09 | 0.110837E+09 |
December | 0.221309E+09 | 0.138678E+09 | 82630682.34 | 0.327380E+09 | 0.153356E+09 |
Annual Sum or Average | 0.176680E+10 | 0.781719E+09 | 0.985083E+09 | 0.340255E+10 | 0.729570E+09 |
Minimum of Months | 75284903.70 | 1116110.20 | 74000187.51 | 0.213269E+09 | 1567245.98 |
Maximum of Months | 0.239973E+09 | 0.158617E+09 | 94000120.98 | 0.398705E+09 | 0.153356E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.247595E+09 | 0.150445E+09 | 97149978.82 | 0.356692E+09 | 0.179075E+09 |
February | 0.212644E+09 | 0.118108E+09 | 94535384.15 | 0.329487E+09 | 0.132559E+09 |
March | 0.201296E+09 | 88910690.85 | 0.112385E+09 | 0.360017E+09 | 91429258.85 |
April | 0.136830E+09 | 38617597.24 | 98212235.66 | 0.319278E+09 | 33425258.48 |
May | 0.101679E+09 | 7526985.33 | 94151687.06 | 0.294252E+09 | 7301244.67 |
June | 90009486.81 | 1535987.16 | 88473499.65 | 0.276333E+09 | 5532132.09 |
July | 97018089.69 | 1334404.40 | 95683685.29 | 0.265125E+09 | 1917533.19 |
August | 0.102916E+09 | 5496471.81 | 97419180.44 | 0.253444E+09 | 5835238.42 |
September | 0.133516E+09 | 34654414.58 | 98861778.46 | 0.285540E+09 | 18743416.76 |
October | 0.237357E+09 | 0.132539E+09 | 0.104818E+09 | 0.446539E+09 | 76401185.85 |
November | 0.286908E+09 | 0.189640E+09 | 97268025.54 | 0.476016E+09 | 0.131524E+09 |
December | 0.264594E+09 | 0.165802E+09 | 98791988.12 | 0.391395E+09 | 0.181775E+09 |
Annual Sum or Average | 0.211236E+10 | 0.934612E+09 | 0.117775E+10 | 0.405412E+10 | 0.865517E+09 |
Minimum of Months | 90009486.81 | 1334404.40 | 88473499.65 | 0.253444E+09 | 1917533.19 |
Maximum of Months | 0.286908E+09 | 0.189640E+09 | 0.112385E+09 | 0.476016E+09 | 0.181775E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207091E+09 | 0.125834E+09 | 81257288.09 | 0.300081E+09 | 0.147761E+09 |
February | 0.177858E+09 | 98787087.29 | 79070412.96 | 0.276717E+09 | 0.109714E+09 |
March | 0.168366E+09 | 74365858.93 | 94000120.98 | 0.302336E+09 | 74802319.13 |
April | 0.114446E+09 | 32300174.04 | 82145771.14 | 0.268669E+09 | 26505321.81 |
May | 85045136.14 | 6295651.56 | 78749484.58 | 0.248602E+09 | 5452564.93 |
June | 75284903.70 | 1284716.20 | 74000187.51 | 0.233956E+09 | 4346462.67 |
July | 81146974.60 | 1116110.20 | 80030864.39 | 0.223347E+09 | 1286276.88 |
August | 86079759.40 | 4597308.19 | 81482451.22 | 0.213345E+09 | 4169571.11 |
September | 0.111674E+09 | 28985325.40 | 82689055.74 | 0.239427E+09 | 14297597.73 |
October | 0.198528E+09 | 0.110857E+09 | 87670930.57 | 0.374172E+09 | 62481989.16 |
November | 0.239973E+09 | 0.158617E+09 | 81356023.64 | 0.399167E+09 | 0.109215E+09 |
December | 0.221309E+09 | 0.138678E+09 | 82630682.34 | 0.328659E+09 | 0.151068E+09 |
Annual Sum or Average | 0.176680E+10 | 0.781719E+09 | 0.985083E+09 | 0.340848E+10 | 0.711100E+09 |
Minimum of Months | 75284903.70 | 1116110.20 | 74000187.51 | 0.213345E+09 | 1286276.88 |
Maximum of Months | 0.239973E+09 | 0.158617E+09 | 94000120.98 | 0.399167E+09 | 0.151068E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207091E+09 | 0.125834E+09 | 81257288.09 | 0.300081E+09 | 0.147761E+09 |
February | 0.177858E+09 | 98787087.29 | 79070412.96 | 0.276717E+09 | 0.109714E+09 |
March | 0.168366E+09 | 74365858.93 | 94000120.98 | 0.302336E+09 | 74802319.13 |
April | 0.114446E+09 | 32300174.04 | 82145771.14 | 0.268669E+09 | 26505321.81 |
May | 85045136.14 | 6295651.56 | 78749484.58 | 0.248602E+09 | 5452564.93 |
June | 75284903.70 | 1284716.20 | 74000187.51 | 0.233956E+09 | 4346462.67 |
July | 81146974.60 | 1116110.20 | 80030864.39 | 0.223347E+09 | 1286276.88 |
August | 86079759.40 | 4597308.19 | 81482451.22 | 0.213345E+09 | 4169571.11 |
September | 0.111674E+09 | 28985325.40 | 82689055.74 | 0.239427E+09 | 14297597.73 |
October | 0.198528E+09 | 0.110857E+09 | 87670930.57 | 0.374172E+09 | 62481989.16 |
November | 0.239973E+09 | 0.158617E+09 | 81356023.64 | 0.399167E+09 | 0.109215E+09 |
December | 0.221309E+09 | 0.138678E+09 | 82630682.34 | 0.328659E+09 | 0.151068E+09 |
Annual Sum or Average | 0.176680E+10 | 0.781719E+09 | 0.985083E+09 | 0.340848E+10 | 0.711100E+09 |
Minimum of Months | 75284903.70 | 1116110.20 | 74000187.51 | 0.213345E+09 | 1286276.88 |
Maximum of Months | 0.239973E+09 | 0.158617E+09 | 94000120.98 | 0.399167E+09 | 0.151068E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207091E+09 | 0.125834E+09 | 81257288.09 | 0.300081E+09 | 0.147761E+09 |
February | 0.177858E+09 | 98787087.29 | 79070412.96 | 0.276717E+09 | 0.109714E+09 |
March | 0.168366E+09 | 74365858.93 | 94000120.98 | 0.302336E+09 | 74802319.13 |
April | 0.114446E+09 | 32300174.04 | 82145771.14 | 0.268669E+09 | 26505321.81 |
May | 85045136.14 | 6295651.56 | 78749484.58 | 0.248602E+09 | 5452564.93 |
June | 75284903.70 | 1284716.20 | 74000187.51 | 0.233956E+09 | 4346462.67 |
July | 81146974.60 | 1116110.20 | 80030864.39 | 0.223347E+09 | 1286276.88 |
August | 86079759.40 | 4597308.19 | 81482451.22 | 0.213345E+09 | 4169571.11 |
September | 0.111674E+09 | 28985325.40 | 82689055.74 | 0.239427E+09 | 14297597.73 |
October | 0.198528E+09 | 0.110857E+09 | 87670930.57 | 0.374172E+09 | 62481989.16 |
November | 0.239973E+09 | 0.158617E+09 | 81356023.64 | 0.399167E+09 | 0.109215E+09 |
December | 0.221309E+09 | 0.138678E+09 | 82630682.34 | 0.328659E+09 | 0.151068E+09 |
Annual Sum or Average | 0.176680E+10 | 0.781719E+09 | 0.985083E+09 | 0.340848E+10 | 0.711100E+09 |
Minimum of Months | 75284903.70 | 1116110.20 | 74000187.51 | 0.213345E+09 | 1286276.88 |
Maximum of Months | 0.239973E+09 | 0.158617E+09 | 94000120.98 | 0.399167E+09 | 0.151068E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207091E+09 | 0.125834E+09 | 81257288.09 | 0.300081E+09 | 0.147761E+09 |
February | 0.177858E+09 | 98787087.29 | 79070412.96 | 0.276717E+09 | 0.109714E+09 |
March | 0.168366E+09 | 74365858.93 | 94000120.98 | 0.302336E+09 | 74802319.13 |
April | 0.114446E+09 | 32300174.04 | 82145771.14 | 0.268669E+09 | 26505321.81 |
May | 85045136.14 | 6295651.56 | 78749484.58 | 0.248602E+09 | 5452564.93 |
June | 75284903.70 | 1284716.20 | 74000187.51 | 0.233956E+09 | 4346462.67 |
July | 81146974.60 | 1116110.20 | 80030864.39 | 0.223347E+09 | 1286276.88 |
August | 86079759.40 | 4597308.19 | 81482451.22 | 0.213345E+09 | 4169571.11 |
September | 0.111674E+09 | 28985325.40 | 82689055.74 | 0.239427E+09 | 14297597.73 |
October | 0.198528E+09 | 0.110857E+09 | 87670930.57 | 0.374172E+09 | 62481989.16 |
November | 0.239973E+09 | 0.158617E+09 | 81356023.64 | 0.399167E+09 | 0.109215E+09 |
December | 0.221309E+09 | 0.138678E+09 | 82630682.34 | 0.328659E+09 | 0.151068E+09 |
Annual Sum or Average | 0.176680E+10 | 0.781719E+09 | 0.985083E+09 | 0.340848E+10 | 0.711100E+09 |
Minimum of Months | 75284903.70 | 1116110.20 | 74000187.51 | 0.213345E+09 | 1286276.88 |
Maximum of Months | 0.239973E+09 | 0.158617E+09 | 94000120.98 | 0.399167E+09 | 0.151068E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.247595E+09 | 0.150445E+09 | 97149978.82 | 0.358923E+09 | 0.175082E+09 |
February | 0.212644E+09 | 0.118108E+09 | 94535384.15 | 0.330862E+09 | 0.129996E+09 |
March | 0.201296E+09 | 88910690.85 | 0.112385E+09 | 0.360811E+09 | 88831447.34 |
April | 0.136830E+09 | 38617597.24 | 98212235.66 | 0.319648E+09 | 31515928.32 |
May | 0.101679E+09 | 7526985.33 | 94151687.06 | 0.294610E+09 | 6584888.53 |
June | 90009486.81 | 1535987.16 | 88473499.65 | 0.277267E+09 | 5152987.28 |
July | 97018089.69 | 1334404.40 | 95683685.29 | 0.264943E+09 | 1571404.88 |
August | 0.102916E+09 | 5496471.81 | 97419180.44 | 0.253556E+09 | 4985185.55 |
September | 0.133516E+09 | 34654414.58 | 98861778.46 | 0.285039E+09 | 16997174.05 |
October | 0.237357E+09 | 0.132539E+09 | 0.104818E+09 | 0.446061E+09 | 74207538.34 |
November | 0.286908E+09 | 0.189640E+09 | 97268025.54 | 0.476505E+09 | 0.129604E+09 |
December | 0.264594E+09 | 0.165802E+09 | 98791988.12 | 0.392843E+09 | 0.179077E+09 |
Annual Sum or Average | 0.211236E+10 | 0.934612E+09 | 0.117775E+10 | 0.406107E+10 | 0.843606E+09 |
Minimum of Months | 90009486.81 | 1334404.40 | 88473499.65 | 0.253556E+09 | 1571404.88 |
Maximum of Months | 0.286908E+09 | 0.189640E+09 | 0.112385E+09 | 0.476505E+09 | 0.179077E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.247595E+09 | 0.150445E+09 | 97149978.82 | 0.358923E+09 | 0.175082E+09 |
February | 0.212644E+09 | 0.118108E+09 | 94535384.15 | 0.330862E+09 | 0.129996E+09 |
March | 0.201296E+09 | 88910690.85 | 0.112385E+09 | 0.360811E+09 | 88831447.34 |
April | 0.136830E+09 | 38617597.24 | 98212235.66 | 0.319648E+09 | 31515928.32 |
May | 0.101679E+09 | 7526985.33 | 94151687.06 | 0.294610E+09 | 6584888.53 |
June | 90009486.81 | 1535987.16 | 88473499.65 | 0.277267E+09 | 5152987.28 |
July | 97018089.69 | 1334404.40 | 95683685.29 | 0.264943E+09 | 1571404.88 |
August | 0.102916E+09 | 5496471.81 | 97419180.44 | 0.253556E+09 | 4985185.55 |
September | 0.133516E+09 | 34654414.58 | 98861778.46 | 0.285039E+09 | 16997174.05 |
October | 0.237357E+09 | 0.132539E+09 | 0.104818E+09 | 0.446061E+09 | 74207538.34 |
November | 0.286908E+09 | 0.189640E+09 | 97268025.54 | 0.476505E+09 | 0.129604E+09 |
December | 0.264594E+09 | 0.165802E+09 | 98791988.12 | 0.392843E+09 | 0.179077E+09 |
Annual Sum or Average | 0.211236E+10 | 0.934612E+09 | 0.117775E+10 | 0.406107E+10 | 0.843606E+09 |
Minimum of Months | 90009486.81 | 1334404.40 | 88473499.65 | 0.253556E+09 | 1571404.88 |
Maximum of Months | 0.286908E+09 | 0.189640E+09 | 0.112385E+09 | 0.476505E+09 | 0.179077E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207091E+09 | 0.125834E+09 | 81257288.09 | 0.299620E+09 | 0.147736E+09 |
February | 0.177858E+09 | 98787087.29 | 79070412.96 | 0.276262E+09 | 0.109608E+09 |
March | 0.168366E+09 | 74365858.93 | 94000120.98 | 0.302242E+09 | 74233021.94 |
April | 0.114446E+09 | 32300174.04 | 82145771.14 | 0.269488E+09 | 25857067.29 |
May | 85045136.14 | 6295651.56 | 78749484.58 | 0.250611E+09 | 5057571.28 |
June | 75284903.70 | 1284716.20 | 74000187.51 | 0.236169E+09 | 4125464.59 |
July | 81146974.60 | 1116110.20 | 80030864.39 | 0.225435E+09 | 1109456.66 |
August | 86079759.40 | 4597308.19 | 81482451.22 | 0.214839E+09 | 3759392.06 |
September | 0.111674E+09 | 28985325.40 | 82689055.74 | 0.240152E+09 | 13467597.50 |
October | 0.198528E+09 | 0.110857E+09 | 87670930.57 | 0.374362E+09 | 61617783.10 |
November | 0.239973E+09 | 0.158617E+09 | 81356023.64 | 0.398914E+09 | 0.108741E+09 |
December | 0.221309E+09 | 0.138678E+09 | 82630682.34 | 0.328170E+09 | 0.151084E+09 |
Annual Sum or Average | 0.176680E+10 | 0.781719E+09 | 0.985083E+09 | 0.341626E+10 | 0.706396E+09 |
Minimum of Months | 75284903.70 | 1116110.20 | 74000187.51 | 0.214839E+09 | 1109456.66 |
Maximum of Months | 0.239973E+09 | 0.158617E+09 | 94000120.98 | 0.398914E+09 | 0.151084E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207091E+09 | 0.125834E+09 | 81257288.09 | 0.299620E+09 | 0.147736E+09 |
February | 0.177858E+09 | 98787087.29 | 79070412.96 | 0.276262E+09 | 0.109608E+09 |
March | 0.168366E+09 | 74365858.93 | 94000120.98 | 0.302242E+09 | 74233021.94 |
April | 0.114446E+09 | 32300174.04 | 82145771.14 | 0.269488E+09 | 25857067.29 |
May | 85045136.14 | 6295651.56 | 78749484.58 | 0.250611E+09 | 5057571.28 |
June | 75284903.70 | 1284716.20 | 74000187.51 | 0.236169E+09 | 4125464.59 |
July | 81146974.60 | 1116110.20 | 80030864.39 | 0.225435E+09 | 1109456.66 |
August | 86079759.40 | 4597308.19 | 81482451.22 | 0.214839E+09 | 3759392.06 |
September | 0.111674E+09 | 28985325.40 | 82689055.74 | 0.240152E+09 | 13467597.50 |
October | 0.198528E+09 | 0.110857E+09 | 87670930.57 | 0.374362E+09 | 61617783.10 |
November | 0.239973E+09 | 0.158617E+09 | 81356023.64 | 0.398914E+09 | 0.108741E+09 |
December | 0.221309E+09 | 0.138678E+09 | 82630682.34 | 0.328170E+09 | 0.151084E+09 |
Annual Sum or Average | 0.176680E+10 | 0.781719E+09 | 0.985083E+09 | 0.341626E+10 | 0.706396E+09 |
Minimum of Months | 75284903.70 | 1116110.20 | 74000187.51 | 0.214839E+09 | 1109456.66 |
Maximum of Months | 0.239973E+09 | 0.158617E+09 | 94000120.98 | 0.398914E+09 | 0.151084E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.247595E+09 | 0.150445E+09 | 97149978.82 | 0.358481E+09 | 0.175021E+09 |
February | 0.212644E+09 | 0.118108E+09 | 94535384.15 | 0.330421E+09 | 0.129846E+09 |
March | 0.201296E+09 | 88910690.85 | 0.112385E+09 | 0.360773E+09 | 88155144.07 |
April | 0.136830E+09 | 38617597.24 | 98212235.66 | 0.320627E+09 | 30754228.79 |
May | 0.101679E+09 | 7526985.33 | 94151687.06 | 0.296908E+09 | 6120511.30 |
June | 90009486.81 | 1535987.16 | 88473499.65 | 0.279823E+09 | 4889206.02 |
July | 97018089.69 | 1334404.40 | 95683685.29 | 0.267353E+09 | 1358788.60 |
August | 0.102916E+09 | 5496471.81 | 97419180.44 | 0.255316E+09 | 4501170.12 |
September | 0.133516E+09 | 34654414.58 | 98861778.46 | 0.285927E+09 | 16018266.43 |
October | 0.237357E+09 | 0.132539E+09 | 0.104818E+09 | 0.446349E+09 | 73179807.08 |
November | 0.286908E+09 | 0.189640E+09 | 97268025.54 | 0.476298E+09 | 0.129032E+09 |
December | 0.264594E+09 | 0.165802E+09 | 98791988.12 | 0.392358E+09 | 0.179068E+09 |
Annual Sum or Average | 0.211236E+10 | 0.934612E+09 | 0.117775E+10 | 0.407063E+10 | 0.837944E+09 |
Minimum of Months | 90009486.81 | 1334404.40 | 88473499.65 | 0.255316E+09 | 1358788.60 |
Maximum of Months | 0.286908E+09 | 0.189640E+09 | 0.112385E+09 | 0.476298E+09 | 0.179068E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207091E+09 | 0.125834E+09 | 81257288.09 | 0.300014E+09 | 0.147006E+09 |
February | 0.177858E+09 | 98787087.29 | 79070412.96 | 0.276536E+09 | 0.109117E+09 |
March | 0.168366E+09 | 74365858.93 | 94000120.98 | 0.302439E+09 | 73896055.46 |
April | 0.114446E+09 | 32300174.04 | 82145771.14 | 0.269686E+09 | 25663765.92 |
May | 85045136.14 | 6295651.56 | 78749484.58 | 0.250850E+09 | 4985073.51 |
June | 75284903.70 | 1284716.20 | 74000187.51 | 0.236427E+09 | 4080163.11 |
July | 81146974.60 | 1116110.20 | 80030864.39 | 0.225662E+09 | 1083823.86 |
August | 86079759.40 | 4597308.19 | 81482451.22 | 0.215027E+09 | 3699578.62 |
September | 0.111674E+09 | 28985325.40 | 82689055.74 | 0.240278E+09 | 13333213.93 |
October | 0.198528E+09 | 0.110857E+09 | 87670930.57 | 0.374474E+09 | 61417402.63 |
November | 0.239973E+09 | 0.158617E+09 | 81356023.64 | 0.399064E+09 | 0.108467E+09 |
December | 0.221309E+09 | 0.138678E+09 | 82630682.34 | 0.328464E+09 | 0.150587E+09 |
Annual Sum or Average | 0.176680E+10 | 0.781719E+09 | 0.985083E+09 | 0.341892E+10 | 0.703337E+09 |
Minimum of Months | 75284903.70 | 1116110.20 | 74000187.51 | 0.215027E+09 | 1083823.86 |
Maximum of Months | 0.239973E+09 | 0.158617E+09 | 94000120.98 | 0.399064E+09 | 0.150587E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207091E+09 | 0.125834E+09 | 81257288.09 | 0.300014E+09 | 0.147006E+09 |
February | 0.177858E+09 | 98787087.29 | 79070412.96 | 0.276536E+09 | 0.109117E+09 |
March | 0.168366E+09 | 74365858.93 | 94000120.98 | 0.302439E+09 | 73896055.46 |
April | 0.114446E+09 | 32300174.04 | 82145771.14 | 0.269686E+09 | 25663765.92 |
May | 85045136.14 | 6295651.56 | 78749484.58 | 0.250850E+09 | 4985073.51 |
June | 75284903.70 | 1284716.20 | 74000187.51 | 0.236427E+09 | 4080163.11 |
July | 81146974.60 | 1116110.20 | 80030864.39 | 0.225662E+09 | 1083823.86 |
August | 86079759.40 | 4597308.19 | 81482451.22 | 0.215027E+09 | 3699578.62 |
September | 0.111674E+09 | 28985325.40 | 82689055.74 | 0.240278E+09 | 13333213.93 |
October | 0.198528E+09 | 0.110857E+09 | 87670930.57 | 0.374474E+09 | 61417402.63 |
November | 0.239973E+09 | 0.158617E+09 | 81356023.64 | 0.399064E+09 | 0.108467E+09 |
December | 0.221309E+09 | 0.138678E+09 | 82630682.34 | 0.328464E+09 | 0.150587E+09 |
Annual Sum or Average | 0.176680E+10 | 0.781719E+09 | 0.985083E+09 | 0.341892E+10 | 0.703337E+09 |
Minimum of Months | 75284903.70 | 1116110.20 | 74000187.51 | 0.215027E+09 | 1083823.86 |
Maximum of Months | 0.239973E+09 | 0.158617E+09 | 94000120.98 | 0.399064E+09 | 0.150587E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.247595E+09 | 0.150445E+09 | 97149978.82 | 0.358951E+09 | 0.174158E+09 |
February | 0.212644E+09 | 0.118108E+09 | 94535384.15 | 0.330750E+09 | 0.129266E+09 |
March | 0.201296E+09 | 88910690.85 | 0.112385E+09 | 0.361010E+09 | 87756220.31 |
April | 0.136830E+09 | 38617597.24 | 98212235.66 | 0.320865E+09 | 30524805.28 |
May | 0.101679E+09 | 7526985.33 | 94151687.06 | 0.297192E+09 | 6032980.12 |
June | 90009486.81 | 1535987.16 | 88473499.65 | 0.280130E+09 | 4834659.60 |
July | 97018089.69 | 1334404.40 | 95683685.29 | 0.267622E+09 | 1327469.83 |
August | 0.102916E+09 | 5496471.81 | 97419180.44 | 0.255541E+09 | 4429753.63 |
September | 0.133516E+09 | 34654414.58 | 98861778.46 | 0.286078E+09 | 15859405.73 |
October | 0.237357E+09 | 0.132539E+09 | 0.104818E+09 | 0.446485E+09 | 72940863.26 |
November | 0.286908E+09 | 0.189640E+09 | 97268025.54 | 0.476478E+09 | 0.128706E+09 |
December | 0.264594E+09 | 0.165802E+09 | 98791988.12 | 0.392711E+09 | 0.178481E+09 |
Annual Sum or Average | 0.211236E+10 | 0.934612E+09 | 0.117775E+10 | 0.407381E+10 | 0.834317E+09 |
Minimum of Months | 90009486.81 | 1334404.40 | 88473499.65 | 0.255541E+09 | 1327469.83 |
Maximum of Months | 0.286908E+09 | 0.189640E+09 | 0.112385E+09 | 0.476478E+09 | 0.178481E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207091E+09 | 0.125834E+09 | 81257288.09 | 0.301011E+09 | 0.144925E+09 |
February | 0.177858E+09 | 98787087.29 | 79070412.96 | 0.277301E+09 | 0.107568E+09 |
March | 0.168366E+09 | 74365858.93 | 94000120.98 | 0.302852E+09 | 72974885.05 |
April | 0.114446E+09 | 32300174.04 | 82145771.14 | 0.269718E+09 | 25411445.07 |
May | 85045136.14 | 6295651.56 | 78749484.58 | 0.250474E+09 | 5023339.88 |
June | 75284903.70 | 1284716.20 | 74000187.51 | 0.235867E+09 | 4109007.38 |
July | 81146974.60 | 1116110.20 | 80030864.39 | 0.224850E+09 | 1122807.68 |
August | 86079759.40 | 4597308.19 | 81482451.22 | 0.214381E+09 | 3835287.77 |
September | 0.111674E+09 | 28985325.40 | 82689055.74 | 0.239966E+09 | 13593042.45 |
October | 0.198528E+09 | 0.110857E+09 | 87670930.57 | 0.374399E+09 | 61432410.06 |
November | 0.239973E+09 | 0.158617E+09 | 81356023.64 | 0.399339E+09 | 0.107871E+09 |
December | 0.221309E+09 | 0.138678E+09 | 82630682.34 | 0.329306E+09 | 0.149022E+09 |
Annual Sum or Average | 0.176680E+10 | 0.781719E+09 | 0.985083E+09 | 0.341946E+10 | 0.696888E+09 |
Minimum of Months | 75284903.70 | 1116110.20 | 74000187.51 | 0.214381E+09 | 1122807.68 |
Maximum of Months | 0.239973E+09 | 0.158617E+09 | 94000120.98 | 0.399339E+09 | 0.149022E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207091E+09 | 0.125834E+09 | 81257288.09 | 0.301011E+09 | 0.144925E+09 |
February | 0.177858E+09 | 98787087.29 | 79070412.96 | 0.277301E+09 | 0.107568E+09 |
March | 0.168366E+09 | 74365858.93 | 94000120.98 | 0.302852E+09 | 72974885.05 |
April | 0.114446E+09 | 32300174.04 | 82145771.14 | 0.269718E+09 | 25411445.07 |
May | 85045136.14 | 6295651.56 | 78749484.58 | 0.250474E+09 | 5023339.88 |
June | 75284903.70 | 1284716.20 | 74000187.51 | 0.235867E+09 | 4109007.38 |
July | 81146974.60 | 1116110.20 | 80030864.39 | 0.224850E+09 | 1122807.68 |
August | 86079759.40 | 4597308.19 | 81482451.22 | 0.214381E+09 | 3835287.77 |
September | 0.111674E+09 | 28985325.40 | 82689055.74 | 0.239966E+09 | 13593042.45 |
October | 0.198528E+09 | 0.110857E+09 | 87670930.57 | 0.374399E+09 | 61432410.06 |
November | 0.239973E+09 | 0.158617E+09 | 81356023.64 | 0.399339E+09 | 0.107871E+09 |
December | 0.221309E+09 | 0.138678E+09 | 82630682.34 | 0.329306E+09 | 0.149022E+09 |
Annual Sum or Average | 0.176680E+10 | 0.781719E+09 | 0.985083E+09 | 0.341946E+10 | 0.696888E+09 |
Minimum of Months | 75284903.70 | 1116110.20 | 74000187.51 | 0.214381E+09 | 1122807.68 |
Maximum of Months | 0.239973E+09 | 0.158617E+09 | 94000120.98 | 0.399339E+09 | 0.149022E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.247595E+09 | 0.150445E+09 | 97149978.82 | 0.360140E+09 | 0.171702E+09 |
February | 0.212644E+09 | 0.118108E+09 | 94535384.15 | 0.331662E+09 | 0.127440E+09 |
March | 0.201296E+09 | 88910690.85 | 0.112385E+09 | 0.361505E+09 | 86673787.19 |
April | 0.136830E+09 | 38617597.24 | 98212235.66 | 0.320900E+09 | 30231122.23 |
May | 0.101679E+09 | 7526985.33 | 94151687.06 | 0.296739E+09 | 6083080.54 |
June | 90009486.81 | 1535987.16 | 88473499.65 | 0.279455E+09 | 4870585.76 |
July | 97018089.69 | 1334404.40 | 95683685.29 | 0.266651E+09 | 1376095.88 |
August | 0.102916E+09 | 5496471.81 | 97419180.44 | 0.254768E+09 | 4594575.65 |
September | 0.133516E+09 | 34654414.58 | 98861778.46 | 0.285702E+09 | 16173553.62 |
October | 0.237357E+09 | 0.132539E+09 | 0.104818E+09 | 0.446393E+09 | 72966439.15 |
November | 0.286908E+09 | 0.189640E+09 | 97268025.54 | 0.476805E+09 | 0.128004E+09 |
December | 0.264594E+09 | 0.165802E+09 | 98791988.12 | 0.393713E+09 | 0.176633E+09 |
Annual Sum or Average | 0.211236E+10 | 0.934612E+09 | 0.117775E+10 | 0.407443E+10 | 0.826748E+09 |
Minimum of Months | 90009486.81 | 1334404.40 | 88473499.65 | 0.254768E+09 | 1376095.88 |
Maximum of Months | 0.286908E+09 | 0.189640E+09 | 0.112385E+09 | 0.476805E+09 | 0.176633E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207091E+09 | 0.125834E+09 | 81257288.09 | 0.302632E+09 | 0.138937E+09 |
February | 0.177858E+09 | 98787087.29 | 79070412.96 | 0.278694E+09 | 0.102367E+09 |
March | 0.168366E+09 | 74365858.93 | 94000120.98 | 0.303125E+09 | 69561292.22 |
April | 0.114446E+09 | 32300174.04 | 82145771.14 | 0.267701E+09 | 24798448.44 |
May | 85045136.14 | 6295651.56 | 78749484.58 | 0.245862E+09 | 5467722.80 |
June | 75284903.70 | 1284716.20 | 74000187.51 | 0.230177E+09 | 4435250.91 |
July | 81146974.60 | 1116110.20 | 80030864.39 | 0.218019E+09 | 1529583.65 |
August | 86079759.40 | 4597308.19 | 81482451.22 | 0.208747E+09 | 5079694.71 |
September | 0.111674E+09 | 28985325.40 | 82689055.74 | 0.236614E+09 | 15972811.50 |
October | 0.198528E+09 | 0.110857E+09 | 87670930.57 | 0.372445E+09 | 62620022.91 |
November | 0.239973E+09 | 0.158617E+09 | 81356023.64 | 0.399165E+09 | 0.106064E+09 |
December | 0.221309E+09 | 0.138678E+09 | 82630682.34 | 0.330757E+09 | 0.143996E+09 |
Annual Sum or Average | 0.176680E+10 | 0.781719E+09 | 0.985083E+09 | 0.339394E+10 | 0.680829E+09 |
Minimum of Months | 75284903.70 | 1116110.20 | 74000187.51 | 0.208747E+09 | 1529583.65 |
Maximum of Months | 0.239973E+09 | 0.158617E+09 | 94000120.98 | 0.399165E+09 | 0.143996E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207091E+09 | 0.125834E+09 | 81257288.09 | 0.302632E+09 | 0.138937E+09 |
February | 0.177858E+09 | 98787087.29 | 79070412.96 | 0.278694E+09 | 0.102367E+09 |
March | 0.168366E+09 | 74365858.93 | 94000120.98 | 0.303125E+09 | 69561292.22 |
April | 0.114446E+09 | 32300174.04 | 82145771.14 | 0.267701E+09 | 24798448.44 |
May | 85045136.14 | 6295651.56 | 78749484.58 | 0.245862E+09 | 5467722.80 |
June | 75284903.70 | 1284716.20 | 74000187.51 | 0.230177E+09 | 4435250.91 |
July | 81146974.60 | 1116110.20 | 80030864.39 | 0.218019E+09 | 1529583.65 |
August | 86079759.40 | 4597308.19 | 81482451.22 | 0.208747E+09 | 5079694.71 |
September | 0.111674E+09 | 28985325.40 | 82689055.74 | 0.236614E+09 | 15972811.50 |
October | 0.198528E+09 | 0.110857E+09 | 87670930.57 | 0.372445E+09 | 62620022.91 |
November | 0.239973E+09 | 0.158617E+09 | 81356023.64 | 0.399165E+09 | 0.106064E+09 |
December | 0.221309E+09 | 0.138678E+09 | 82630682.34 | 0.330757E+09 | 0.143996E+09 |
Annual Sum or Average | 0.176680E+10 | 0.781719E+09 | 0.985083E+09 | 0.339394E+10 | 0.680829E+09 |
Minimum of Months | 75284903.70 | 1116110.20 | 74000187.51 | 0.208747E+09 | 1529583.65 |
Maximum of Months | 0.239973E+09 | 0.158617E+09 | 94000120.98 | 0.399165E+09 | 0.143996E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.247595E+09 | 0.150445E+09 | 97149978.82 | 0.362083E+09 | 0.164624E+09 |
February | 0.212644E+09 | 0.118108E+09 | 94535384.15 | 0.333325E+09 | 0.121311E+09 |
March | 0.201296E+09 | 88910690.85 | 0.112385E+09 | 0.361820E+09 | 82645623.00 |
April | 0.136830E+09 | 38617597.24 | 98212235.66 | 0.318468E+09 | 29506212.26 |
May | 0.101679E+09 | 7526985.33 | 94151687.06 | 0.291228E+09 | 6622466.80 |
June | 90009486.81 | 1535987.16 | 88473499.65 | 0.272658E+09 | 5264499.94 |
July | 97018089.69 | 1334404.40 | 95683685.29 | 0.258535E+09 | 1876750.98 |
August | 0.102916E+09 | 5496471.81 | 97419180.44 | 0.248042E+09 | 6083105.70 |
September | 0.133516E+09 | 34654414.58 | 98861778.46 | 0.281674E+09 | 19002526.43 |
October | 0.237357E+09 | 0.132539E+09 | 0.104818E+09 | 0.444030E+09 | 74382952.92 |
November | 0.286908E+09 | 0.189640E+09 | 97268025.54 | 0.476582E+09 | 0.125868E+09 |
December | 0.264594E+09 | 0.165802E+09 | 98791988.12 | 0.395436E+09 | 0.170685E+09 |
Annual Sum or Average | 0.211236E+10 | 0.934612E+09 | 0.117775E+10 | 0.404388E+10 | 0.807873E+09 |
Minimum of Months | 90009486.81 | 1334404.40 | 88473499.65 | 0.248042E+09 | 1876750.98 |
Maximum of Months | 0.286908E+09 | 0.189640E+09 | 0.112385E+09 | 0.476582E+09 | 0.170685E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 711.27 | 367.12 | 495.17 | 300.88 | 194.29 | 0.00 | 0.00 |
February | 730.59 | 292.40 | 470.84 | 261.52 | 209.32 | 0.00 | 0.00 |
March | 722.93 | 174.14 | 402.58 | 177.82 | 224.76 | 0.00 | 0.00 |
April | 670.98 | 59.33 | 282.77 | 79.81 | 202.97 | 0.00 | 0.00 |
May | 610.52 | 10.05 | 203.35 | 15.05 | 188.30 | 0.00 | 0.00 |
June | 592.48 | 7.76 | 186.01 | 3.17 | 182.84 | 0.00 | 0.00 |
July | 554.41 | 2.45 | 194.03 | 2.67 | 191.36 | 0.00 | 0.00 |
August | 520.99 | 7.52 | 205.82 | 10.99 | 194.83 | 0.00 | 0.00 |
September | 598.13 | 28.86 | 275.92 | 71.62 | 204.31 | 0.00 | 0.00 |
October | 895.95 | 139.83 | 474.70 | 265.07 | 209.63 | 0.00 | 0.00 |
November | 984.74 | 266.76 | 592.93 | 391.91 | 201.01 | 0.00 | 0.00 |
December | 782.40 | 366.33 | 529.17 | 331.59 | 197.58 | 0.00 | 0.00 |
Annual Sum or Average | 697.53 | 142.90 | 358.80 | 158.75 | 200.05 | 0.00 | 0.00 |
Minimum of Months | 520.99 | 2.45 | 186.01 | 2.67 | 182.84 | 0.00 | 0.00 |
Maximum of Months | 984.74 | 367.12 | 592.93 | 391.91 | 224.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 352.14 | 190.54 | 247.59 | 150.44 | 97.15 | 0.00 | 0.00 |
February | 362.72 | 150.36 | 235.42 | 130.76 | 104.66 | 0.00 | 0.00 |
March | 360.50 | 88.79 | 201.29 | 88.91 | 112.38 | 0.00 | 0.00 |
April | 336.66 | 30.16 | 141.39 | 39.90 | 101.48 | 0.00 | 0.00 |
May | 308.36 | 4.94 | 101.68 | 7.53 | 94.15 | 0.00 | 0.00 |
June | 300.29 | 3.84 | 93.01 | 1.59 | 91.42 | 0.00 | 0.00 |
July | 281.30 | 1.11 | 97.02 | 1.33 | 95.68 | 0.00 | 0.00 |
August | 264.02 | 3.38 | 102.91 | 5.50 | 97.42 | 0.00 | 0.00 |
September | 301.36 | 13.56 | 137.96 | 35.81 | 102.15 | 0.00 | 0.00 |
October | 448.77 | 69.49 | 237.35 | 132.54 | 104.81 | 0.00 | 0.00 |
November | 491.62 | 134.30 | 296.46 | 195.96 | 100.51 | 0.00 | 0.00 |
December | 388.65 | 187.62 | 264.59 | 165.80 | 98.79 | 0.00 | 0.00 |
Annual Sum or Average | 349.51 | 72.84 | 179.40 | 79.38 | 100.02 | 0.00 | 0.00 |
Minimum of Months | 264.02 | 1.11 | 93.01 | 1.33 | 91.42 | 0.00 | 0.00 |
Maximum of Months | 491.62 | 190.54 | 296.46 | 195.96 | 112.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 353.50 | 185.25 | 247.08 | 150.13 | 96.95 | 0.00 | 0.00 |
February | 362.79 | 150.13 | 234.94 | 130.49 | 104.45 | 0.00 | 0.00 |
March | 359.21 | 92.78 | 200.88 | 88.73 | 112.15 | 0.00 | 0.00 |
April | 330.25 | 34.64 | 141.10 | 39.82 | 101.27 | 0.00 | 0.00 |
May | 296.02 | 6.95 | 101.47 | 7.51 | 93.96 | 0.00 | 0.00 |
June | 287.34 | 5.53 | 92.82 | 1.58 | 91.23 | 0.00 | 0.00 |
July | 267.09 | 1.82 | 96.82 | 1.33 | 95.48 | 0.00 | 0.00 |
August | 254.39 | 5.70 | 102.70 | 5.49 | 97.22 | 0.00 | 0.00 |
September | 295.39 | 19.09 | 137.68 | 35.73 | 101.94 | 0.00 | 0.00 |
October | 446.39 | 76.63 | 236.86 | 132.26 | 104.60 | 0.00 | 0.00 |
November | 490.82 | 137.56 | 295.85 | 195.55 | 100.30 | 0.00 | 0.00 |
December | 389.18 | 185.63 | 264.04 | 165.46 | 98.59 | 0.00 | 0.00 |
Annual Sum or Average | 344.14 | 74.81 | 179.03 | 79.21 | 99.82 | 0.00 | 0.00 |
Minimum of Months | 254.39 | 1.82 | 92.82 | 1.33 | 91.23 | 0.00 | 0.00 |
Maximum of Months | 490.82 | 185.63 | 295.85 | 195.55 | 112.15 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 354.66 | 182.20 | 247.08 | 150.13 | 96.95 | 0.00 | 0.00 |
February | 363.30 | 148.79 | 234.94 | 130.49 | 104.45 | 0.00 | 0.00 |
March | 359.29 | 92.64 | 200.88 | 88.73 | 112.15 | 0.00 | 0.00 |
April | 329.87 | 35.26 | 141.10 | 39.82 | 101.27 | 0.00 | 0.00 |
May | 294.81 | 7.51 | 101.47 | 7.51 | 93.96 | 0.00 | 0.00 |
June | 285.91 | 5.88 | 92.82 | 1.58 | 91.23 | 0.00 | 0.00 |
July | 265.45 | 2.02 | 96.82 | 1.33 | 95.48 | 0.00 | 0.00 |
August | 253.44 | 6.12 | 102.70 | 5.49 | 97.22 | 0.00 | 0.00 |
September | 295.03 | 20.01 | 137.68 | 35.73 | 101.94 | 0.00 | 0.00 |
October | 446.23 | 77.28 | 236.86 | 132.26 | 104.60 | 0.00 | 0.00 |
November | 490.97 | 137.17 | 295.85 | 195.55 | 100.30 | 0.00 | 0.00 |
December | 389.86 | 183.90 | 264.04 | 165.46 | 98.59 | 0.00 | 0.00 |
Annual Sum or Average | 343.84 | 74.57 | 179.03 | 79.21 | 99.82 | 0.00 | 0.00 |
Minimum of Months | 253.44 | 2.02 | 92.82 | 1.33 | 91.23 | 0.00 | 0.00 |
Maximum of Months | 490.97 | 183.90 | 295.85 | 195.55 | 112.15 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 355.79 | 179.72 | 247.08 | 150.13 | 96.95 | 0.00 | 0.00 |
February | 363.95 | 147.30 | 234.94 | 130.49 | 104.45 | 0.00 | 0.00 |
March | 359.65 | 91.63 | 200.88 | 88.73 | 112.15 | 0.00 | 0.00 |
April | 330.26 | 34.58 | 141.10 | 39.82 | 101.27 | 0.00 | 0.00 |
May | 295.32 | 7.23 | 101.47 | 7.51 | 93.96 | 0.00 | 0.00 |
June | 286.57 | 5.73 | 92.82 | 1.58 | 91.23 | 0.00 | 0.00 |
July | 265.92 | 1.89 | 96.82 | 1.33 | 95.48 | 0.00 | 0.00 |
August | 253.88 | 5.82 | 102.70 | 5.49 | 97.22 | 0.00 | 0.00 |
September | 295.23 | 19.39 | 137.68 | 35.73 | 101.94 | 0.00 | 0.00 |
October | 446.41 | 76.56 | 236.86 | 132.26 | 104.60 | 0.00 | 0.00 |
November | 491.29 | 136.26 | 295.85 | 195.55 | 100.30 | 0.00 | 0.00 |
December | 390.59 | 182.38 | 264.04 | 165.46 | 98.59 | 0.00 | 0.00 |
Annual Sum or Average | 344.34 | 73.71 | 179.03 | 79.21 | 99.82 | 0.00 | 0.00 |
Minimum of Months | 253.88 | 1.89 | 92.82 | 1.33 | 91.23 | 0.00 | 0.00 |
Maximum of Months | 491.29 | 182.38 | 295.85 | 195.55 | 112.15 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 716.16 | 351.41 | 494.16 | 300.26 | 193.90 | 0.00 | 0.00 |
February | 731.07 | 288.88 | 469.87 | 260.98 | 208.89 | 0.00 | 0.00 |
March | 720.94 | 178.04 | 401.75 | 177.45 | 224.30 | 0.00 | 0.00 |
April | 661.26 | 65.22 | 282.19 | 79.64 | 202.55 | 0.00 | 0.00 |
May | 591.26 | 13.06 | 202.93 | 15.02 | 187.91 | 0.00 | 0.00 |
June | 574.98 | 10.68 | 185.63 | 3.17 | 182.46 | 0.00 | 0.00 |
July | 531.39 | 3.09 | 193.63 | 2.66 | 190.97 | 0.00 | 0.00 |
August | 507.95 | 9.95 | 205.40 | 10.97 | 194.43 | 0.00 | 0.00 |
September | 589.42 | 35.18 | 275.36 | 71.47 | 203.89 | 0.00 | 0.00 |
October | 891.88 | 148.72 | 473.73 | 264.53 | 209.20 | 0.00 | 0.00 |
November | 983.67 | 268.54 | 591.71 | 391.11 | 200.60 | 0.00 | 0.00 |
December | 784.17 | 359.33 | 528.09 | 330.91 | 197.17 | 0.00 | 0.00 |
Annual Sum or Average | 689.88 | 143.70 | 358.06 | 158.43 | 199.64 | 0.00 | 0.00 |
Minimum of Months | 507.95 | 3.09 | 185.63 | 2.66 | 182.46 | 0.00 | 0.00 |
Maximum of Months | 983.67 | 359.33 | 591.71 | 391.11 | 224.30 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 357.57 | 175.66 | 247.08 | 150.13 | 96.95 | 0.00 | 0.00 |
February | 364.97 | 144.29 | 234.94 | 130.49 | 104.45 | 0.00 | 0.00 |
March | 360.39 | 88.34 | 200.88 | 88.73 | 112.15 | 0.00 | 0.00 |
April | 331.64 | 31.82 | 141.10 | 39.82 | 101.27 | 0.00 | 0.00 |
May | 297.99 | 6.06 | 101.47 | 7.51 | 93.96 | 0.00 | 0.00 |
June | 290.19 | 5.07 | 92.82 | 1.58 | 91.23 | 0.00 | 0.00 |
July | 268.15 | 1.34 | 96.82 | 1.33 | 95.48 | 0.00 | 0.00 |
August | 255.75 | 4.49 | 102.70 | 5.49 | 97.22 | 0.00 | 0.00 |
September | 295.61 | 16.57 | 137.68 | 35.73 | 101.94 | 0.00 | 0.00 |
October | 446.19 | 73.33 | 236.86 | 132.26 | 104.60 | 0.00 | 0.00 |
November | 491.56 | 133.69 | 295.85 | 195.55 | 100.30 | 0.00 | 0.00 |
December | 391.54 | 179.67 | 264.04 | 165.46 | 98.59 | 0.00 | 0.00 |
Annual Sum or Average | 345.74 | 71.37 | 179.03 | 79.21 | 99.82 | 0.00 | 0.00 |
Minimum of Months | 255.75 | 1.34 | 92.82 | 1.33 | 91.23 | 0.00 | 0.00 |
Maximum of Months | 491.56 | 179.67 | 295.85 | 195.55 | 112.15 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 358.04 | 174.79 | 247.08 | 150.13 | 96.95 | 0.00 | 0.00 |
February | 365.34 | 143.64 | 234.94 | 130.49 | 104.45 | 0.00 | 0.00 |
March | 360.62 | 87.94 | 200.88 | 88.73 | 112.15 | 0.00 | 0.00 |
April | 331.88 | 31.58 | 141.10 | 39.82 | 101.27 | 0.00 | 0.00 |
May | 298.27 | 5.97 | 101.47 | 7.51 | 93.96 | 0.00 | 0.00 |
June | 290.50 | 5.01 | 92.82 | 1.58 | 91.23 | 0.00 | 0.00 |
July | 268.42 | 1.30 | 96.82 | 1.33 | 95.48 | 0.00 | 0.00 |
August | 255.97 | 4.42 | 102.70 | 5.49 | 97.22 | 0.00 | 0.00 |
September | 295.77 | 16.41 | 137.68 | 35.73 | 101.94 | 0.00 | 0.00 |
October | 446.32 | 73.09 | 236.86 | 132.26 | 104.60 | 0.00 | 0.00 |
November | 491.75 | 133.35 | 295.85 | 195.55 | 100.30 | 0.00 | 0.00 |
December | 391.89 | 179.08 | 264.04 | 165.46 | 98.59 | 0.00 | 0.00 |
Annual Sum or Average | 346.01 | 71.06 | 179.03 | 79.21 | 99.82 | 0.00 | 0.00 |
Minimum of Months | 255.97 | 1.30 | 92.82 | 1.33 | 91.23 | 0.00 | 0.00 |
Maximum of Months | 491.75 | 179.08 | 295.85 | 195.55 | 112.15 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 359.23 | 172.32 | 247.08 | 150.13 | 96.95 | 0.00 | 0.00 |
February | 366.35 | 141.61 | 234.94 | 130.49 | 104.45 | 0.00 | 0.00 |
March | 361.11 | 86.85 | 200.88 | 88.73 | 112.15 | 0.00 | 0.00 |
April | 331.92 | 31.27 | 141.10 | 39.82 | 101.27 | 0.00 | 0.00 |
May | 297.82 | 6.02 | 101.47 | 7.51 | 93.96 | 0.00 | 0.00 |
June | 289.81 | 5.05 | 92.82 | 1.58 | 91.23 | 0.00 | 0.00 |
July | 267.45 | 1.35 | 96.82 | 1.33 | 95.48 | 0.00 | 0.00 |
August | 255.20 | 4.58 | 102.70 | 5.49 | 97.22 | 0.00 | 0.00 |
September | 295.38 | 16.73 | 137.68 | 35.73 | 101.94 | 0.00 | 0.00 |
October | 446.23 | 73.11 | 236.86 | 132.26 | 104.60 | 0.00 | 0.00 |
November | 492.08 | 132.62 | 295.85 | 195.55 | 100.30 | 0.00 | 0.00 |
December | 392.89 | 177.22 | 264.04 | 165.46 | 98.59 | 0.00 | 0.00 |
Annual Sum or Average | 346.06 | 70.41 | 179.03 | 79.21 | 99.82 | 0.00 | 0.00 |
Minimum of Months | 255.20 | 1.35 | 92.82 | 1.33 | 91.23 | 0.00 | 0.00 |
Maximum of Months | 492.08 | 177.22 | 295.85 | 195.55 | 112.15 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 361.17 | 165.21 | 247.08 | 150.13 | 96.95 | 0.00 | 0.00 |
February | 368.18 | 134.77 | 234.94 | 130.49 | 104.45 | 0.00 | 0.00 |
March | 361.44 | 82.80 | 200.88 | 88.73 | 112.15 | 0.00 | 0.00 |
April | 329.42 | 30.52 | 141.10 | 39.82 | 101.27 | 0.00 | 0.00 |
May | 292.32 | 6.55 | 101.47 | 7.51 | 93.96 | 0.00 | 0.00 |
June | 282.80 | 5.45 | 92.82 | 1.58 | 91.23 | 0.00 | 0.00 |
July | 259.32 | 1.84 | 96.82 | 1.33 | 95.48 | 0.00 | 0.00 |
August | 248.48 | 6.06 | 102.70 | 5.49 | 97.22 | 0.00 | 0.00 |
September | 291.24 | 19.66 | 137.68 | 35.73 | 101.94 | 0.00 | 0.00 |
October | 443.89 | 74.53 | 236.86 | 132.26 | 104.60 | 0.00 | 0.00 |
November | 491.86 | 130.40 | 295.85 | 195.55 | 100.30 | 0.00 | 0.00 |
December | 394.62 | 171.25 | 264.04 | 165.46 | 98.59 | 0.00 | 0.00 |
Annual Sum or Average | 343.47 | 68.80 | 179.03 | 79.21 | 99.82 | 0.00 | 0.00 |
Minimum of Months | 248.48 | 1.84 | 92.82 | 1.33 | 91.23 | 0.00 | 0.00 |
Maximum of Months | 491.86 | 171.25 | 295.85 | 195.55 | 112.15 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.190507E+10 | 0.983284E+09 | 0.132628E+10 | 0.805880E+09 | 0.520397E+09 | 0.00 | 0.00 |
February | 0.176744E+10 | 0.707379E+09 | 0.113905E+10 | 0.632663E+09 | 0.506391E+09 | 0.00 | 0.00 |
March | 0.193631E+10 | 0.466428E+09 | 0.107827E+10 | 0.476262E+09 | 0.602006E+09 | 0.00 | 0.00 |
April | 0.173919E+10 | 0.153795E+09 | 0.732947E+09 | 0.206860E+09 | 0.526087E+09 | 0.00 | 0.00 |
May | 0.163520E+10 | 26906415.03 | 0.544655E+09 | 40319291.00 | 0.504336E+09 | 0.00 | 0.00 |
June | 0.153571E+10 | 20110692.65 | 0.482148E+09 | 8227718.08 | 0.473920E+09 | 0.00 | 0.00 |
July | 0.148493E+10 | 6572451.49 | 0.519690E+09 | 7147913.40 | 0.512542E+09 | 0.00 | 0.00 |
August | 0.139543E+10 | 20140023.49 | 0.551281E+09 | 29442577.15 | 0.521839E+09 | 0.00 | 0.00 |
September | 0.155035E+10 | 74815756.64 | 0.715197E+09 | 0.185631E+09 | 0.529566E+09 | 0.00 | 0.00 |
October | 0.239971E+10 | 0.374514E+09 | 0.127144E+10 | 0.709965E+09 | 0.561472E+09 | 0.00 | 0.00 |
November | 0.255246E+10 | 0.691450E+09 | 0.153686E+10 | 0.101583E+10 | 0.521029E+09 | 0.00 | 0.00 |
December | 0.209559E+10 | 0.981190E+09 | 0.141733E+10 | 0.888139E+09 | 0.529192E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.219974E+11 | 0.450659E+10 | 0.113151E+11 | 0.500637E+10 | 0.630878E+10 | 0.00 | 0.00 |
Minimum of Months | 0.139543E+10 | 6572451.49 | 0.482148E+09 | 7147913.40 | 0.473920E+09 | 0.00 | 0.00 |
Maximum of Months | 0.255246E+10 | 0.983284E+09 | 0.153686E+10 | 0.101583E+10 | 0.602006E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.943172E+09 | 0.510348E+09 | 0.663138E+09 | 0.402940E+09 | 0.260198E+09 | 0.00 | 0.00 |
February | 0.877494E+09 | 0.363746E+09 | 0.569527E+09 | 0.316331E+09 | 0.253196E+09 | 0.00 | 0.00 |
March | 0.965563E+09 | 0.237816E+09 | 0.539134E+09 | 0.238131E+09 | 0.301003E+09 | 0.00 | 0.00 |
April | 0.872614E+09 | 78162963.29 | 0.366474E+09 | 0.103430E+09 | 0.263043E+09 | 0.00 | 0.00 |
May | 0.825901E+09 | 13241724.08 | 0.272328E+09 | 20159645.50 | 0.252168E+09 | 0.00 | 0.00 |
June | 0.778345E+09 | 9954745.58 | 0.241074E+09 | 4113859.04 | 0.236960E+09 | 0.00 | 0.00 |
July | 0.753424E+09 | 2973383.30 | 0.259845E+09 | 3573956.70 | 0.256271E+09 | 0.00 | 0.00 |
August | 0.707144E+09 | 9047985.15 | 0.275641E+09 | 14721288.57 | 0.260919E+09 | 0.00 | 0.00 |
September | 0.781133E+09 | 35158408.27 | 0.357599E+09 | 92815474.26 | 0.264783E+09 | 0.00 | 0.00 |
October | 0.120199E+10 | 0.186127E+09 | 0.635718E+09 | 0.354982E+09 | 0.280736E+09 | 0.00 | 0.00 |
November | 0.127427E+10 | 0.348112E+09 | 0.768431E+09 | 0.507917E+09 | 0.260515E+09 | 0.00 | 0.00 |
December | 0.104096E+10 | 0.502529E+09 | 0.708666E+09 | 0.444070E+09 | 0.264596E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.110220E+11 | 0.229722E+10 | 0.565757E+10 | 0.250319E+10 | 0.315439E+10 | 0.00 | 0.00 |
Minimum of Months | 0.707144E+09 | 2973383.30 | 0.241074E+09 | 3573956.70 | 0.236960E+09 | 0.00 | 0.00 |
Maximum of Months | 0.127427E+10 | 0.510348E+09 | 0.768431E+09 | 0.507917E+09 | 0.301003E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.946811E+09 | 0.496163E+09 | 0.661778E+09 | 0.402113E+09 | 0.259665E+09 | 0.00 | 0.00 |
February | 0.877656E+09 | 0.363202E+09 | 0.568359E+09 | 0.315683E+09 | 0.252676E+09 | 0.00 | 0.00 |
March | 0.962117E+09 | 0.248515E+09 | 0.538028E+09 | 0.237642E+09 | 0.300385E+09 | 0.00 | 0.00 |
April | 0.856007E+09 | 89796933.79 | 0.365722E+09 | 0.103218E+09 | 0.262504E+09 | 0.00 | 0.00 |
May | 0.792848E+09 | 18612497.88 | 0.271769E+09 | 20118288.44 | 0.251651E+09 | 0.00 | 0.00 |
June | 0.744789E+09 | 14328588.85 | 0.240579E+09 | 4105419.55 | 0.236474E+09 | 0.00 | 0.00 |
July | 0.715372E+09 | 4887049.71 | 0.259312E+09 | 3566624.81 | 0.255745E+09 | 0.00 | 0.00 |
August | 0.681359E+09 | 15254330.03 | 0.275075E+09 | 14691088.18 | 0.260384E+09 | 0.00 | 0.00 |
September | 0.765639E+09 | 49469516.88 | 0.356865E+09 | 92625065.38 | 0.264240E+09 | 0.00 | 0.00 |
October | 0.119561E+10 | 0.205238E+09 | 0.634414E+09 | 0.354254E+09 | 0.280160E+09 | 0.00 | 0.00 |
November | 0.127221E+10 | 0.356543E+09 | 0.766855E+09 | 0.506875E+09 | 0.259980E+09 | 0.00 | 0.00 |
December | 0.104239E+10 | 0.497186E+09 | 0.707212E+09 | 0.443159E+09 | 0.264053E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.108528E+11 | 0.235920E+10 | 0.564597E+10 | 0.249805E+10 | 0.314792E+10 | 0.00 | 0.00 |
Minimum of Months | 0.681359E+09 | 4887049.71 | 0.240579E+09 | 3566624.81 | 0.236474E+09 | 0.00 | 0.00 |
Maximum of Months | 0.127221E+10 | 0.497186E+09 | 0.766855E+09 | 0.506875E+09 | 0.300385E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.949918E+09 | 0.488017E+09 | 0.661778E+09 | 0.402113E+09 | 0.259665E+09 | 0.00 | 0.00 |
February | 0.878893E+09 | 0.359944E+09 | 0.568359E+09 | 0.315683E+09 | 0.252676E+09 | 0.00 | 0.00 |
March | 0.962313E+09 | 0.248130E+09 | 0.538028E+09 | 0.237642E+09 | 0.300385E+09 | 0.00 | 0.00 |
April | 0.855033E+09 | 91402297.14 | 0.365722E+09 | 0.103218E+09 | 0.262504E+09 | 0.00 | 0.00 |
May | 0.789612E+09 | 20105453.31 | 0.271769E+09 | 20118288.44 | 0.251651E+09 | 0.00 | 0.00 |
June | 0.741072E+09 | 15253230.36 | 0.240579E+09 | 4105419.55 | 0.236474E+09 | 0.00 | 0.00 |
July | 0.710977E+09 | 5417650.28 | 0.259312E+09 | 3566624.81 | 0.255745E+09 | 0.00 | 0.00 |
August | 0.678815E+09 | 16387752.81 | 0.275075E+09 | 14691088.18 | 0.260384E+09 | 0.00 | 0.00 |
September | 0.764716E+09 | 51869591.31 | 0.356865E+09 | 92625065.38 | 0.264240E+09 | 0.00 | 0.00 |
October | 0.119520E+10 | 0.206982E+09 | 0.634414E+09 | 0.354254E+09 | 0.280160E+09 | 0.00 | 0.00 |
November | 0.127258E+10 | 0.355537E+09 | 0.766855E+09 | 0.506875E+09 | 0.259980E+09 | 0.00 | 0.00 |
December | 0.104420E+10 | 0.492567E+09 | 0.707212E+09 | 0.443159E+09 | 0.264053E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.108433E+11 | 0.235161E+10 | 0.564597E+10 | 0.249805E+10 | 0.314792E+10 | 0.00 | 0.00 |
Minimum of Months | 0.678815E+09 | 5417650.28 | 0.240579E+09 | 3566624.81 | 0.236474E+09 | 0.00 | 0.00 |
Maximum of Months | 0.127258E+10 | 0.492567E+09 | 0.766855E+09 | 0.506875E+09 | 0.300385E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.952961E+09 | 0.481368E+09 | 0.661778E+09 | 0.402113E+09 | 0.259665E+09 | 0.00 | 0.00 |
February | 0.880475E+09 | 0.356350E+09 | 0.568359E+09 | 0.315683E+09 | 0.252676E+09 | 0.00 | 0.00 |
March | 0.963280E+09 | 0.245432E+09 | 0.538028E+09 | 0.237642E+09 | 0.300385E+09 | 0.00 | 0.00 |
April | 0.856029E+09 | 89635208.26 | 0.365722E+09 | 0.103218E+09 | 0.262504E+09 | 0.00 | 0.00 |
May | 0.790980E+09 | 19365564.80 | 0.271769E+09 | 20118288.44 | 0.251651E+09 | 0.00 | 0.00 |
June | 0.742799E+09 | 14848768.75 | 0.240579E+09 | 4105419.55 | 0.236474E+09 | 0.00 | 0.00 |
July | 0.712234E+09 | 5051028.00 | 0.259312E+09 | 3566624.81 | 0.255745E+09 | 0.00 | 0.00 |
August | 0.679982E+09 | 15587242.32 | 0.275075E+09 | 14691088.18 | 0.260384E+09 | 0.00 | 0.00 |
September | 0.765239E+09 | 50260066.01 | 0.356865E+09 | 92625065.38 | 0.264240E+09 | 0.00 | 0.00 |
October | 0.119566E+10 | 0.205068E+09 | 0.634414E+09 | 0.354254E+09 | 0.280160E+09 | 0.00 | 0.00 |
November | 0.127343E+10 | 0.353198E+09 | 0.766855E+09 | 0.506875E+09 | 0.259980E+09 | 0.00 | 0.00 |
December | 0.104615E+10 | 0.488486E+09 | 0.707212E+09 | 0.443159E+09 | 0.264053E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.108592E+11 | 0.232465E+10 | 0.564597E+10 | 0.249805E+10 | 0.314792E+10 | 0.00 | 0.00 |
Minimum of Months | 0.679982E+09 | 5051028.00 | 0.240579E+09 | 3566624.81 | 0.236474E+09 | 0.00 | 0.00 |
Maximum of Months | 0.127343E+10 | 0.488486E+09 | 0.766855E+09 | 0.506875E+09 | 0.300385E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.191817E+10 | 0.941208E+09 | 0.132356E+10 | 0.804226E+09 | 0.519329E+09 | 0.00 | 0.00 |
February | 0.176859E+10 | 0.698849E+09 | 0.113672E+10 | 0.631365E+09 | 0.505352E+09 | 0.00 | 0.00 |
March | 0.193096E+10 | 0.476872E+09 | 0.107606E+10 | 0.475285E+09 | 0.600771E+09 | 0.00 | 0.00 |
April | 0.171397E+10 | 0.169053E+09 | 0.731443E+09 | 0.206436E+09 | 0.525008E+09 | 0.00 | 0.00 |
May | 0.158363E+10 | 34977916.07 | 0.543538E+09 | 40236576.88 | 0.503301E+09 | 0.00 | 0.00 |
June | 0.149036E+10 | 27690602.49 | 0.481159E+09 | 8210839.10 | 0.472948E+09 | 0.00 | 0.00 |
July | 0.142327E+10 | 8285229.87 | 0.518624E+09 | 7133249.62 | 0.511491E+09 | 0.00 | 0.00 |
August | 0.136049E+10 | 26647593.85 | 0.550150E+09 | 29382176.36 | 0.520768E+09 | 0.00 | 0.00 |
September | 0.152779E+10 | 91183920.85 | 0.713730E+09 | 0.185250E+09 | 0.528480E+09 | 0.00 | 0.00 |
October | 0.238881E+10 | 0.398343E+09 | 0.126883E+10 | 0.708508E+09 | 0.560320E+09 | 0.00 | 0.00 |
November | 0.254968E+10 | 0.696066E+09 | 0.153371E+10 | 0.101375E+10 | 0.519960E+09 | 0.00 | 0.00 |
December | 0.210032E+10 | 0.962424E+09 | 0.141442E+10 | 0.886317E+09 | 0.528107E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.217560E+11 | 0.453160E+10 | 0.112919E+11 | 0.499610E+10 | 0.629583E+10 | 0.00 | 0.00 |
Minimum of Months | 0.136049E+10 | 8285229.87 | 0.481159E+09 | 7133249.62 | 0.472948E+09 | 0.00 | 0.00 |
Maximum of Months | 0.254968E+10 | 0.962424E+09 | 0.153371E+10 | 0.101375E+10 | 0.600771E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.957722E+09 | 0.470492E+09 | 0.661778E+09 | 0.402113E+09 | 0.259665E+09 | 0.00 | 0.00 |
February | 0.882944E+09 | 0.349062E+09 | 0.568359E+09 | 0.315683E+09 | 0.252676E+09 | 0.00 | 0.00 |
March | 0.965257E+09 | 0.236621E+09 | 0.538028E+09 | 0.237642E+09 | 0.300385E+09 | 0.00 | 0.00 |
April | 0.859602E+09 | 82467908.42 | 0.365722E+09 | 0.103218E+09 | 0.262504E+09 | 0.00 | 0.00 |
May | 0.798129E+09 | 16234352.59 | 0.271769E+09 | 20118288.44 | 0.251651E+09 | 0.00 | 0.00 |
June | 0.752160E+09 | 13139299.11 | 0.240579E+09 | 4105419.55 | 0.236474E+09 | 0.00 | 0.00 |
July | 0.718222E+09 | 3576667.84 | 0.259312E+09 | 3566624.81 | 0.255745E+09 | 0.00 | 0.00 |
August | 0.684995E+09 | 12019531.77 | 0.275075E+09 | 14691088.18 | 0.260384E+09 | 0.00 | 0.00 |
September | 0.766231E+09 | 42953088.25 | 0.356865E+09 | 92625065.38 | 0.264240E+09 | 0.00 | 0.00 |
October | 0.119507E+10 | 0.196415E+09 | 0.634414E+09 | 0.354254E+09 | 0.280160E+09 | 0.00 | 0.00 |
November | 0.127413E+10 | 0.346514E+09 | 0.766855E+09 | 0.506875E+09 | 0.259980E+09 | 0.00 | 0.00 |
December | 0.104870E+10 | 0.481235E+09 | 0.707212E+09 | 0.443159E+09 | 0.264053E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.109032E+11 | 0.225073E+10 | 0.564597E+10 | 0.249805E+10 | 0.314792E+10 | 0.00 | 0.00 |
Minimum of Months | 0.684995E+09 | 3576667.84 | 0.240579E+09 | 3566624.81 | 0.236474E+09 | 0.00 | 0.00 |
Maximum of Months | 0.127413E+10 | 0.481235E+09 | 0.766855E+09 | 0.506875E+09 | 0.300385E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.958979E+09 | 0.468171E+09 | 0.661778E+09 | 0.402113E+09 | 0.259665E+09 | 0.00 | 0.00 |
February | 0.883822E+09 | 0.347500E+09 | 0.568359E+09 | 0.315683E+09 | 0.252676E+09 | 0.00 | 0.00 |
March | 0.965887E+09 | 0.235548E+09 | 0.538028E+09 | 0.237642E+09 | 0.300385E+09 | 0.00 | 0.00 |
April | 0.860238E+09 | 81851913.23 | 0.365722E+09 | 0.103218E+09 | 0.262504E+09 | 0.00 | 0.00 |
May | 0.798892E+09 | 16001742.31 | 0.271769E+09 | 20118288.44 | 0.251651E+09 | 0.00 | 0.00 |
June | 0.752984E+09 | 12994347.66 | 0.240579E+09 | 4105419.55 | 0.236474E+09 | 0.00 | 0.00 |
July | 0.718946E+09 | 3494435.19 | 0.259312E+09 | 3566624.81 | 0.255745E+09 | 0.00 | 0.00 |
August | 0.685593E+09 | 11828551.51 | 0.275075E+09 | 14691088.18 | 0.260384E+09 | 0.00 | 0.00 |
September | 0.766635E+09 | 42525460.35 | 0.356865E+09 | 92625065.38 | 0.264240E+09 | 0.00 | 0.00 |
October | 0.119543E+10 | 0.195775E+09 | 0.634414E+09 | 0.354254E+09 | 0.280160E+09 | 0.00 | 0.00 |
November | 0.127461E+10 | 0.345640E+09 | 0.766855E+09 | 0.506875E+09 | 0.259980E+09 | 0.00 | 0.00 |
December | 0.104964E+10 | 0.479655E+09 | 0.707212E+09 | 0.443159E+09 | 0.264053E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.109117E+11 | 0.224099E+10 | 0.564597E+10 | 0.249805E+10 | 0.314792E+10 | 0.00 | 0.00 |
Minimum of Months | 0.685593E+09 | 3494435.19 | 0.240579E+09 | 3566624.81 | 0.236474E+09 | 0.00 | 0.00 |
Maximum of Months | 0.127461E+10 | 0.479655E+09 | 0.766855E+09 | 0.506875E+09 | 0.300385E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.962163E+09 | 0.461552E+09 | 0.661778E+09 | 0.402113E+09 | 0.259665E+09 | 0.00 | 0.00 |
February | 0.886265E+09 | 0.342576E+09 | 0.568359E+09 | 0.315683E+09 | 0.252676E+09 | 0.00 | 0.00 |
March | 0.967209E+09 | 0.232623E+09 | 0.538028E+09 | 0.237642E+09 | 0.300385E+09 | 0.00 | 0.00 |
April | 0.860335E+09 | 81053446.15 | 0.365722E+09 | 0.103218E+09 | 0.262504E+09 | 0.00 | 0.00 |
May | 0.797685E+09 | 16128583.31 | 0.271769E+09 | 20118288.44 | 0.251651E+09 | 0.00 | 0.00 |
June | 0.751189E+09 | 13087902.52 | 0.240579E+09 | 4105419.55 | 0.236474E+09 | 0.00 | 0.00 |
July | 0.716349E+09 | 3620869.40 | 0.259312E+09 | 3566624.81 | 0.255745E+09 | 0.00 | 0.00 |
August | 0.683530E+09 | 12264509.63 | 0.275075E+09 | 14691088.18 | 0.260384E+09 | 0.00 | 0.00 |
September | 0.765633E+09 | 43359273.37 | 0.356865E+09 | 92625065.38 | 0.264240E+09 | 0.00 | 0.00 |
October | 0.119519E+10 | 0.195831E+09 | 0.634414E+09 | 0.354254E+09 | 0.280160E+09 | 0.00 | 0.00 |
November | 0.127548E+10 | 0.343746E+09 | 0.766855E+09 | 0.506875E+09 | 0.259980E+09 | 0.00 | 0.00 |
December | 0.105232E+10 | 0.474677E+09 | 0.707212E+09 | 0.443159E+09 | 0.264053E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.109134E+11 | 0.222052E+10 | 0.564597E+10 | 0.249805E+10 | 0.314792E+10 | 0.00 | 0.00 |
Minimum of Months | 0.683530E+09 | 3620869.40 | 0.240579E+09 | 3566624.81 | 0.236474E+09 | 0.00 | 0.00 |
Maximum of Months | 0.127548E+10 | 0.474677E+09 | 0.766855E+09 | 0.506875E+09 | 0.300385E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.967347E+09 | 0.442498E+09 | 0.661778E+09 | 0.402113E+09 | 0.259665E+09 | 0.00 | 0.00 |
February | 0.890711E+09 | 0.326045E+09 | 0.568359E+09 | 0.315683E+09 | 0.252676E+09 | 0.00 | 0.00 |
March | 0.968069E+09 | 0.221768E+09 | 0.538028E+09 | 0.237642E+09 | 0.300385E+09 | 0.00 | 0.00 |
April | 0.853869E+09 | 79102816.96 | 0.365722E+09 | 0.103218E+09 | 0.262504E+09 | 0.00 | 0.00 |
May | 0.782951E+09 | 17556534.29 | 0.271769E+09 | 20118288.44 | 0.251651E+09 | 0.00 | 0.00 |
June | 0.733012E+09 | 14134448.42 | 0.240579E+09 | 4105419.55 | 0.236474E+09 | 0.00 | 0.00 |
July | 0.694571E+09 | 4934649.16 | 0.259312E+09 | 3566624.81 | 0.255745E+09 | 0.00 | 0.00 |
August | 0.665536E+09 | 16241793.35 | 0.275075E+09 | 14691088.18 | 0.260384E+09 | 0.00 | 0.00 |
September | 0.754902E+09 | 50947815.50 | 0.356865E+09 | 92625065.38 | 0.264240E+09 | 0.00 | 0.00 |
October | 0.118892E+10 | 0.199623E+09 | 0.634414E+09 | 0.354254E+09 | 0.280160E+09 | 0.00 | 0.00 |
November | 0.127491E+10 | 0.337996E+09 | 0.766855E+09 | 0.506875E+09 | 0.259980E+09 | 0.00 | 0.00 |
December | 0.105695E+10 | 0.458677E+09 | 0.707212E+09 | 0.443159E+09 | 0.264053E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.108318E+11 | 0.216952E+10 | 0.564597E+10 | 0.249805E+10 | 0.314792E+10 | 0.00 | 0.00 |
Minimum of Months | 0.665536E+09 | 4934649.16 | 0.240579E+09 | 3566624.81 | 0.236474E+09 | 0.00 | 0.00 |
Maximum of Months | 0.127491E+10 | 0.458677E+09 | 0.766855E+09 | 0.506875E+09 | 0.300385E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.39 | 10.38 | 7.87 | 1.20 | 0.38 | 63.33 | 149.51 | 0.00 |
February | 16.97 | 12.78 | 9.69 | 1.81 | 4.63 | 75.94 | 163.32 | 0.01 |
March | 22.37 | 15.60 | 11.23 | 1.86 | 10.07 | 92.70 | 193.23 | 0.00 |
April | 29.13 | 18.33 | 11.93 | 1.64 | 16.17 | 89.20 | 259.84 | 0.01 |
May | 32.98 | 21.97 | 16.72 | 2.17 | 21.14 | 97.31 | 248.85 | 0.02 |
June | 33.59 | 24.39 | 20.62 | 1.55 | 23.45 | 107.22 | 203.36 | 0.06 |
July | 31.67 | 26.29 | 24.51 | 2.27 | 24.88 | 132.35 | 83.14 | 0.02 |
August | 30.03 | 26.31 | 25.11 | 1.75 | 23.81 | 127.44 | 60.46 | 0.00 |
September | 28.75 | 24.70 | 23.21 | 1.33 | 20.22 | 105.62 | 105.60 | 0.08 |
October | 25.09 | 18.74 | 15.36 | 0.77 | 12.83 | 75.09 | 190.08 | 0.00 |
November | 19.63 | 14.46 | 10.99 | 0.66 | 5.78 | 58.54 | 201.10 | 0.00 |
December | 14.52 | 10.88 | 7.89 | 0.97 | 0.94 | 60.91 | 153.60 | 0.01 |
Annual Sum or Average | 24.88 | 18.77 | 15.46 | 1.50 | 13.74 | 90.59 | 167.44 | 0.02 |
Minimum of Months | 13.39 | 10.38 | 7.87 | 0.66 | 0.38 | 58.54 | 60.46 | 0.00 |
Maximum of Months | 33.59 | 26.31 | 25.11 | 2.27 | 24.88 | 132.35 | 259.84 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.60 | 12-JAN-14:00 | 14.20 | 7.40 | 3.80 | 8.15 | 163.00 | 476.00 |
February | 27.10 | 22-FEB-14:00 | 16.20 | 9.10 | 1.50 | 15.39 | 225.00 | 451.00 |
March | 35.60 | 28-MAR-14:00 | 18.50 | 7.70 | 0.00 | 19.52 | 182.00 | 699.00 |
April | 40.30 | 15-APR-14:00 | 20.67 | 10.00 | 6.70 | 28.43 | 201.00 | 649.50 |
May | 44.50 | 03-MAY-14:00 | 20.64 | 5.30 | 2.80 | 28.91 | 150.00 | 809.00 |
June | 44.60 | 07-JUN-15:00 | 21.53 | 9.10 | 3.10 | 28.43 | 167.00 | 640.50 |
July | 40.40 | 02-JUL-15:00 | 26.36 | 21.60 | 2.10 | 29.87 | 200.00 | 545.50 |
August | 37.30 | 07-AUG-14:00 | 26.58 | 22.90 | 3.00 | 29.87 | 311.00 | 370.00 |
September | 37.50 | 17-SEP-19:00 | 27.68 | 24.60 | 0.20 | 28.59 | 0.00 | 0.00 |
October | 36.40 | 02-OCT-14:20 | 21.05 | 13.00 | 1.80 | 21.61 | 187.33 | 678.83 |
November | 30.30 | 04-NOV-13:00 | 17.17 | 8.90 | 1.10 | 14.84 | 155.00 | 710.00 |
December | 24.60 | 28-DEC-13:00 | 15.30 | 8.90 | 2.80 | 10.88 | 181.50 | 535.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.60 | 14.20 | 5.30 | 0.00 | 8.15 | 0.00 | 0.00 | |
Maximum of Months | 44.60 | 27.68 | 24.60 | 6.70 | 29.87 | 311.00 | 809.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 4.80 | 05-JAN-06:00 | 4.73 | 4.60 | 0.00 | -10.2 | 0.00 | 0.00 |
February | 6.90 | 02-FEB-05:00 | 6.67 | 6.50 | 0.00 | -7.8 | 0.00 | 0.00 |
March | 13.30 | 01-MAR-03:00 | 10.56 | 8.30 | 0.80 | -1.4 | 0.00 | 0.00 |
April | 17.40 | 11-APR-04:00 | 13.58 | 10.90 | 0.00 | 3.06 | 0.00 | 0.00 |
May | 22.70 | 13-MAY-04:00 | 20.32 | 19.30 | 2.10 | 20.40 | 0.00 | 0.00 |
June | 23.30 | 18-JUN-04:00 | 21.80 | 21.20 | 2.70 | 17.75 | 0.00 | 0.00 |
July | 23.20 | 19-JUL-02:00 | 23.20 | 23.20 | 2.30 | 15.39 | 0.00 | 0.00 |
August | 23.40 | 15-AUG-23:00 | 22.91 | 22.80 | 2.40 | 21.78 | 0.00 | 0.00 |
September | 23.00 | 27-SEP-04:00 | 20.74 | 19.70 | 0.00 | 10.30 | 0.00 | 0.00 |
October | 15.50 | 31-OCT-04:00 | 14.07 | 13.20 | 0.00 | 1.80 | 0.00 | 0.00 |
November | 9.50 | 27-NOV-05:00 | 8.75 | 8.10 | 0.00 | -5.0 | 0.00 | 0.00 |
December | 5.00 | 21-DEC-04:00 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.80 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 | |
Maximum of Months | 23.40 | 23.20 | 23.20 | 2.70 | 21.78 | 0.00 | 0.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.62 | 17-JAN-14:00 | 18.20 | 14.10 | 1.00 | 11.07 | 198.00 | 56.50 |
February | 18.14 | 25-FEB-16:00 | 21.20 | 16.60 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 21.38 | 10-MAR-18:49 | 29.25 | 17.73 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 23.42 | 18-APR-13:00 | 37.10 | 17.80 | 5.70 | 23.49 | 233.50 | 671.50 |
May | 27.40 | 22-MAY-22:00 | 29.40 | 26.80 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 28.92 | 28-JUN-12:00 | 34.40 | 27.50 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 29.18 | 01-JUL-16:00 | 37.20 | 26.80 | 2.30 | 25.66 | 196.00 | 196.00 |
August | 29.17 | 27-AUG-15:00 | 35.10 | 27.40 | 1.30 | 29.55 | 256.00 | 129.00 |
September | 28.10 | 14-SEP-16:00 | 33.70 | 26.40 | 1.40 | 26.48 | 122.50 | 108.50 |
October | 23.06 | 06-OCT-10:00 | 28.60 | 20.80 | 1.30 | 20.22 | 327.00 | 348.50 |
November | 18.93 | 08-NOV-17:10 | 27.55 | 14.47 | 0.17 | 16.67 | 28.00 | 65.33 |
December | 15.64 | 29-DEC-19:00 | 16.80 | 14.90 | 4.80 | 13.54 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.62 | 16.80 | 14.10 | 0.00 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 29.18 | 37.20 | 27.50 | 5.90 | 29.55 | 332.50 | 671.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.10 | 17-JAN-13:00 | 17.80 | 15.48 | 0.90 | 9.72 | 260.50 | 81.50 |
February | 16.60 | 25-FEB-16:00 | 21.20 | 18.14 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 18.30 | 10-MAR-19:00 | 27.70 | 21.26 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 19.30 | 26-APR-23:10 | 28.53 | 22.04 | 0.00 | 15.61 | 0.00 | 0.00 |
May | 26.80 | 22-MAY-22:00 | 29.40 | 27.40 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 27.50 | 28-JUN-12:00 | 34.40 | 28.92 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 27.30 | 18-JUL-06:19 | 29.10 | 27.70 | 1.17 | 26.48 | 20.00 | 0.00 |
August | 28.80 | 12-AUG-07:00 | 29.10 | 28.83 | 2.90 | 26.81 | 113.00 | 6.50 |
September | 26.50 | 12-SEP-14:00 | 30.50 | 27.38 | 0.90 | 25.99 | 260.00 | 20.00 |
October | 21.10 | 06-OCT-08:00 | 25.50 | 22.41 | 0.30 | 17.21 | 239.00 | 159.00 |
November | 16.30 | 08-NOV-21:19 | 20.10 | 17.59 | 0.00 | 10.95 | 0.00 | 0.00 |
December | 14.90 | 29-DEC-20:10 | 16.72 | 15.59 | 4.73 | 13.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 14.10 | 16.72 | 15.48 | 0.00 | 9.72 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 34.40 | 28.92 | 5.90 | 26.81 | 332.50 | 501.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.92 | 27.26 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 21.74 | 33.91 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 24.21 | 44.04 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.79 | 55.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.48 | 58.43 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 34.27 | 54.82 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 35.42 | 39.75 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 34.60 | 34.68 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 32.04 | 35.55 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 28.44 | 39.44 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 24.77 | 33.85 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 22.02 | 26.79 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 28.18 | 40.37 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.92 | 26.79 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 35.42 | 58.43 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.303412E+09 | -186933305.7 | 0.00 | 0.00 | 744.00 | 0.00 | -116479101.3 | 58.99 | 0.00 | 0.00 |
February | 0.269509E+09 | -166086457.5 | 0.00 | 0.00 | 672.00 | 0.00 | -103422553.5 | 58.99 | 0.00 | 0.00 |
March | 0.287314E+09 | -174468457.6 | 0.00 | 0.00 | 744.00 | 0.00 | -112845207.6 | 58.99 | 0.00 | 0.00 |
April | 0.257487E+09 | -149514639.1 | 0.00 | 0.00 | 720.00 | 0.00 | -107972728.3 | 58.99 | 0.00 | 0.00 |
May | 0.247217E+09 | -136558251.5 | 0.00 | 0.00 | 744.00 | 0.00 | -110659145.9 | 58.99 | 0.00 | 0.00 |
June | 0.226640E+09 | -119849311.3 | 0.00 | 0.00 | 720.00 | 0.00 | -106790652.5 | 58.99 | 0.00 | 0.00 |
July | 0.225858E+09 | -115658333.7 | 0.00 | 0.00 | 744.00 | 0.00 | -110199959.5 | 58.99 | 0.00 | 0.00 |
August | 0.232606E+09 | -122271758.7 | 0.00 | 0.00 | 744.00 | 0.00 | -110334627.4 | 58.99 | 0.00 | 0.00 |
September | 0.236479E+09 | -129352318.1 | 0.00 | 0.00 | 720.00 | 0.00 | -107126575.0 | 58.99 | 0.00 | 0.00 |
October | 0.261677E+09 | -150064548.7 | 0.00 | 0.00 | 744.00 | 0.00 | -111612290.8 | 58.99 | 0.00 | 0.00 |
November | 0.271395E+09 | -162153429.8 | 0.00 | 0.00 | 720.00 | 0.00 | -109241646.5 | 58.99 | 0.00 | 0.00 |
December | 0.296721E+09 | -181760985.7 | 0.00 | 0.00 | 744.00 | 0.00 | -114960511.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.311632E+10 | -0.179467E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.132165E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.225858E+09 | -186933305.7 | 0.00 | 0.00 | 672.00 | 0.00 | -116479101.3 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.303412E+09 | -115658333.7 | 0.00 | 0.00 | 744.00 | 0.00 | -103422553.5 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.302025E+09 | -186922837.8 | 0.00 | 0.00 | 744.00 | 0.00 | -115102643.9 | 58.99 | 0.00 | 0.00 |
February | 0.268825E+09 | -166091193.4 | 0.00 | 0.00 | 672.00 | 0.00 | -102734029.6 | 58.99 | 0.00 | 0.00 |
March | 0.286968E+09 | -174465888.2 | 0.00 | 0.00 | 744.00 | 0.00 | -112501635.9 | 58.99 | 0.00 | 0.00 |
April | 0.257360E+09 | -149513580.6 | 0.00 | 0.00 | 720.00 | 0.00 | -107846904.7 | 58.99 | 0.00 | 0.00 |
May | 0.247230E+09 | -136557123.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110672700.8 | 58.99 | 0.00 | 0.00 |
June | 0.226721E+09 | -119848455.3 | 0.00 | 0.00 | 720.00 | 0.00 | -106873017.5 | 58.99 | 0.00 | 0.00 |
July | 0.225989E+09 | -115659798.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110329378.7 | 58.99 | 0.00 | 0.00 |
August | 0.232737E+09 | -122284354.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110452763.1 | 58.99 | 0.00 | 0.00 |
September | 0.236567E+09 | -129345931.1 | 0.00 | 0.00 | 720.00 | 0.00 | -107220584.4 | 58.99 | 0.00 | 0.00 |
October | 0.261627E+09 | -150050922.9 | 0.00 | 0.00 | 744.00 | 0.00 | -111575826.8 | 58.99 | 0.00 | 0.00 |
November | 0.271170E+09 | -162147036.9 | 0.00 | 0.00 | 720.00 | 0.00 | -109022936.3 | 58.99 | 0.00 | 0.00 |
December | 0.295835E+09 | -181758751.4 | 0.00 | 0.00 | 744.00 | 0.00 | -114076056.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.311305E+10 | -0.179465E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.131841E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.225989E+09 | -186922837.8 | 0.00 | 0.00 | 672.00 | 0.00 | -115102643.9 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.302025E+09 | -115659798.9 | 0.00 | 0.00 | 744.00 | 0.00 | -102734029.6 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.280578E+09 | -164348938.9 | 0.00 | 0.00 | 744.00 | 0.00 | -116228849.7 | 59.00 | 0.00 | 0.00 |
February | 0.248898E+09 | -146175059.2 | 0.00 | 0.00 | 672.00 | 0.00 | -102723262.4 | 59.00 | 0.00 | 0.00 |
March | 0.267062E+09 | -155709508.4 | 0.00 | 0.00 | 744.00 | 0.00 | -111352584.4 | 58.98 | 0.00 | 0.00 |
April | 0.237179E+09 | -131517022.9 | 0.00 | 0.00 | 720.00 | 0.00 | -105661937.9 | 58.99 | 0.00 | 0.00 |
May | 0.229061E+09 | -121187421.2 | 0.00 | 0.00 | 744.00 | 0.00 | -107873416.8 | 58.98 | 0.00 | 0.00 |
June | 0.210895E+09 | -106761142.9 | 0.00 | 0.00 | 720.00 | 0.00 | -104133612.4 | 58.98 | 0.00 | 0.00 |
July | 0.208560E+09 | -101101975.5 | 0.00 | 0.00 | 744.00 | 0.00 | -107458074.2 | 59.00 | 0.00 | 0.00 |
August | 0.217253E+09 | -109218494.3 | 0.00 | 0.00 | 744.00 | 0.00 | -108034446.9 | 58.99 | 0.00 | 0.00 |
September | 0.218627E+09 | -113724958.3 | 0.00 | 0.00 | 720.00 | 0.00 | -104902164.3 | 58.99 | 0.00 | 0.00 |
October | 0.241625E+09 | -132003615.3 | 0.00 | 0.00 | 744.00 | 0.00 | -109621584.3 | 58.99 | 0.00 | 0.00 |
November | 0.251438E+09 | -143186416.8 | 0.00 | 0.00 | 720.00 | 0.00 | -108251854.9 | 58.98 | 0.00 | 0.00 |
December | 0.273152E+09 | -158636536.4 | 0.00 | 0.00 | 744.00 | 0.00 | -114515274.6 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.288433E+10 | -0.158357E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.130076E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.208560E+09 | -164348938.9 | 0.00 | 0.00 | 672.00 | 0.00 | -116228849.7 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.280578E+09 | -101101975.5 | 0.00 | 0.00 | 744.00 | 0.00 | -102723262.4 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.281063E+09 | -164376263.4 | 0.00 | 0.00 | 744.00 | 0.00 | -116687224.0 | 58.99 | 0.00 | 0.00 |
February | 0.249071E+09 | -146205121.2 | 0.00 | 0.00 | 672.00 | 0.00 | -102866364.7 | 58.98 | 0.00 | 0.00 |
March | 0.267097E+09 | -155696785.4 | 0.00 | 0.00 | 744.00 | 0.00 | -111400061.7 | 58.99 | 0.00 | 0.00 |
April | 0.237052E+09 | -131495079.2 | 0.00 | 0.00 | 720.00 | 0.00 | -105557357.3 | 58.99 | 0.00 | 0.00 |
May | 0.228855E+09 | -121150661.6 | 0.00 | 0.00 | 744.00 | 0.00 | -107704602.8 | 58.99 | 0.00 | 0.00 |
June | 0.210690E+09 | -106744295.8 | 0.00 | 0.00 | 720.00 | 0.00 | -103945887.3 | 58.98 | 0.00 | 0.00 |
July | 0.208344E+09 | -101107691.1 | 0.00 | 0.00 | 744.00 | 0.00 | -107236601.2 | 58.99 | 0.00 | 0.00 |
August | 0.217086E+09 | -109234566.2 | 0.00 | 0.00 | 744.00 | 0.00 | -107851703.5 | 58.99 | 0.00 | 0.00 |
September | 0.218475E+09 | -113740466.3 | 0.00 | 0.00 | 720.00 | 0.00 | -104734409.2 | 58.99 | 0.00 | 0.00 |
October | 0.241540E+09 | -132000241.7 | 0.00 | 0.00 | 744.00 | 0.00 | -109539611.8 | 58.99 | 0.00 | 0.00 |
November | 0.251479E+09 | -143136506.7 | 0.00 | 0.00 | 720.00 | 0.00 | -108342039.0 | 59.00 | 0.00 | 0.00 |
December | 0.273432E+09 | -158641620.0 | 0.00 | 0.00 | 744.00 | 0.00 | -114790012.3 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.288419E+10 | -0.158353E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.130066E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.208344E+09 | -164376263.4 | 0.00 | 0.00 | 672.00 | 0.00 | -116687224.0 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.281063E+09 | -101107691.1 | 0.00 | 0.00 | 744.00 | 0.00 | -102866364.7 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.273149E+09 | -155349558.6 | 0.00 | 0.00 | 744.00 | 0.00 | -117799891.7 | 58.99 | 0.00 | 0.00 |
February | 0.241760E+09 | -138245578.8 | 0.00 | 0.00 | 672.00 | 0.00 | -103514393.3 | 58.99 | 0.00 | 0.00 |
March | 0.259384E+09 | -147287318.1 | 0.00 | 0.00 | 744.00 | 0.00 | -112097154.4 | 59.00 | 0.00 | 0.00 |
April | 0.230610E+09 | -124451591.8 | 0.00 | 0.00 | 720.00 | 0.00 | -106158666.8 | 58.99 | 0.00 | 0.00 |
May | 0.222817E+09 | -114576497.6 | 0.00 | 0.00 | 744.00 | 0.00 | -108240722.3 | 58.99 | 0.00 | 0.00 |
June | 0.205501E+09 | -100967715.5 | 0.00 | 0.00 | 720.00 | 0.00 | -104533593.5 | 58.99 | 0.00 | 0.00 |
July | 0.203172E+09 | -95608186.4 | 0.00 | 0.00 | 744.00 | 0.00 | -107564240.6 | 59.00 | 0.00 | 0.00 |
August | 0.211646E+09 | -103336287.8 | 0.00 | 0.00 | 744.00 | 0.00 | -108309289.6 | 58.99 | 0.00 | 0.00 |
September | 0.212798E+09 | -107626570.9 | 0.00 | 0.00 | 720.00 | 0.00 | -105171189.8 | 58.99 | 0.00 | 0.00 |
October | 0.234746E+09 | -124752944.2 | 0.00 | 0.00 | 744.00 | 0.00 | -109993496.4 | 58.99 | 0.00 | 0.00 |
November | 0.243962E+09 | -135236573.7 | 0.00 | 0.00 | 720.00 | 0.00 | -108725438.4 | 58.98 | 0.00 | 0.00 |
December | 0.265491E+09 | -150052674.9 | 0.00 | 0.00 | 744.00 | 0.00 | -115438161.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.280504E+10 | -0.149749E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.130755E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.203172E+09 | -155349558.6 | 0.00 | 0.00 | 672.00 | 0.00 | -117799891.7 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.273149E+09 | -95608186.4 | 0.00 | 0.00 | 744.00 | 0.00 | -103514393.3 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.273163E+09 | -155349946.3 | 0.00 | 0.00 | 744.00 | 0.00 | -117812621.2 | 58.99 | 0.00 | 0.00 |
February | 0.241763E+09 | -138245003.0 | 0.00 | 0.00 | 672.00 | 0.00 | -103517696.5 | 58.99 | 0.00 | 0.00 |
March | 0.259442E+09 | -147295314.7 | 0.00 | 0.00 | 744.00 | 0.00 | -112146550.0 | 59.00 | 0.00 | 0.00 |
April | 0.230729E+09 | -124437981.2 | 0.00 | 0.00 | 720.00 | 0.00 | -106291514.4 | 58.99 | 0.00 | 0.00 |
May | 0.222964E+09 | -114566174.3 | 0.00 | 0.00 | 744.00 | 0.00 | -108398111.0 | 58.99 | 0.00 | 0.00 |
June | 0.205695E+09 | -101015407.2 | 0.00 | 0.00 | 720.00 | 0.00 | -104679253.7 | 58.98 | 0.00 | 0.00 |
July | 0.203341E+09 | -95658004.0 | 0.00 | 0.00 | 744.00 | 0.00 | -107682758.4 | 58.98 | 0.00 | 0.00 |
August | 0.211823E+09 | -103367647.7 | 0.00 | 0.00 | 744.00 | 0.00 | -108455204.2 | 58.98 | 0.00 | 0.00 |
September | 0.212942E+09 | -107635854.7 | 0.00 | 0.00 | 720.00 | 0.00 | -105305811.7 | 58.99 | 0.00 | 0.00 |
October | 0.234857E+09 | -124748070.8 | 0.00 | 0.00 | 744.00 | 0.00 | -110108966.3 | 58.99 | 0.00 | 0.00 |
November | 0.244021E+09 | -135219435.7 | 0.00 | 0.00 | 720.00 | 0.00 | -108801141.7 | 58.99 | 0.00 | 0.00 |
December | 0.265467E+09 | -150047166.8 | 0.00 | 0.00 | 744.00 | 0.00 | -115420254.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.280621E+10 | -0.149759E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.130862E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.203341E+09 | -155349946.3 | 0.00 | 0.00 | 672.00 | 0.00 | -117812621.2 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.273163E+09 | -95658004.0 | 0.00 | 0.00 | 744.00 | 0.00 | -103517696.5 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.273313E+09 | -155352763.2 | 0.00 | 0.00 | 744.00 | 0.00 | -117960509.9 | 58.99 | 0.00 | 0.00 |
February | 0.241859E+09 | -138246526.3 | 0.00 | 0.00 | 672.00 | 0.00 | -103612607.2 | 58.99 | 0.00 | 0.00 |
March | 0.259497E+09 | -147324887.7 | 0.00 | 0.00 | 744.00 | 0.00 | -112172522.1 | 58.99 | 0.00 | 0.00 |
April | 0.230772E+09 | -124442556.6 | 0.00 | 0.00 | 720.00 | 0.00 | -106329561.7 | 58.99 | 0.00 | 0.00 |
May | 0.223005E+09 | -114591967.1 | 0.00 | 0.00 | 744.00 | 0.00 | -108412542.2 | 58.99 | 0.00 | 0.00 |
June | 0.205723E+09 | -100992282.4 | 0.00 | 0.00 | 720.00 | 0.00 | -104730867.9 | 58.99 | 0.00 | 0.00 |
July | 0.203366E+09 | -95624842.5 | 0.00 | 0.00 | 744.00 | 0.00 | -107740794.8 | 58.99 | 0.00 | 0.00 |
August | 0.211840E+09 | -103360340.2 | 0.00 | 0.00 | 744.00 | 0.00 | -108479807.5 | 58.98 | 0.00 | 0.00 |
September | 0.212964E+09 | -107626593.2 | 0.00 | 0.00 | 720.00 | 0.00 | -105337479.9 | 58.99 | 0.00 | 0.00 |
October | 0.234904E+09 | -124766231.7 | 0.00 | 0.00 | 744.00 | 0.00 | -110137531.9 | 58.99 | 0.00 | 0.00 |
November | 0.244057E+09 | -135232117.2 | 0.00 | 0.00 | 720.00 | 0.00 | -108825041.2 | 58.98 | 0.00 | 0.00 |
December | 0.265585E+09 | -150037012.8 | 0.00 | 0.00 | 744.00 | 0.00 | -115548101.8 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.280689E+10 | -0.149760E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.130929E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.203366E+09 | -155352763.2 | 0.00 | 0.00 | 672.00 | 0.00 | -117960509.9 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.273313E+09 | -95624842.5 | 0.00 | 0.00 | 744.00 | 0.00 | -103612607.2 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 319.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 303.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 364.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 379.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 406.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 386.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 379.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 372.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 344.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 347.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 317.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 315.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4237.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 303.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 406.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.202435E+09 | 69907.26 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10178088.89 | 24676.26 | 02-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 21905223.83 | 43094.18 | 23-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.234518E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.202435E+09 | 69907.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 37744673.27 | 35719.39 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 130615.71 | 1088.46 | 02-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1354854.00 | 5759.68 | 23-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39230142.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37744673.27 | 35719.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.136145E+09 | 35585.32 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3636090.41 | 4389.95 | 02-FEB-08:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 9632561.07 | 11728.24 | 23-DEC-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.149413E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.136145E+09 | 35585.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.181575E+09 | 35655.68 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6928163.38 | 5882.01 | 02-FEB-08:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13808567.55 | 14213.38 | 23-DEC-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.202311E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.181575E+09 | 35655.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.226443E+09 | 35581.92 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11103645.96 | 7446.16 | 02-FEB-08:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 18442397.34 | 16457.29 | 23-DEC-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.255989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.226443E+09 | 35581.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.338634E+09 | 65816.25 | 01-JAN-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 15809375.61 | 31225.97 | 02-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 28247660.22 | 49351.47 | 23-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.382691E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.338634E+09 | 65816.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.171048E+09 | 34651.42 | 01-JAN-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6169941.31 | 13767.36 | 02-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 12326231.15 | 22842.47 | 23-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189545E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.171048E+09 | 34651.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.181789E+09 | 34541.22 | 01-JAN-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7660995.86 | 14799.15 | 02-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13929673.89 | 24265.29 | 23-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.203379E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.181789E+09 | 34541.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.220637E+09 | 34628.84 | 01-JAN-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 13966795.23 | 18809.17 | 02-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 20397015.97 | 29146.83 | 23-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.255000E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.220637E+09 | 34628.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.307119E+09 | 38528.73 | 01-JAN-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 38769127.52 | 30619.19 | 02-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 39645677.68 | 38528.73 | 23-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.385534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.307119E+09 | 38528.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.219419E+10 | 0.195761E+10 | 9407.13 | 12-JAN-15:00 | 8815.87 | 0.00 |
February | 0.00 | 0.00 | 0.781313E+10 | 0.677519E+10 | 15779.03 | 22-FEB-15:00 | 14451.76 | 0.00 |
March | 0.00 | 0.00 | 0.196667E+11 | 0.169364E+11 | 67238.93 | 11-MAR-09:02 | 53604.79 | 0.00 |
April | 0.00 | 0.00 | 0.320043E+11 | 0.286976E+11 | 69270.24 | 26-APR-08:61 | 49048.71 | 0.00 |
May | 0.00 | 0.00 | 0.464863E+11 | 0.371787E+11 | 73073.29 | 24-MAY-08:61 | 38349.60 | 0.00 |
June | 0.00 | 0.00 | 0.527270E+11 | 0.371935E+11 | 74449.65 | 26-JUN-08:61 | 34550.69 | 0.00 |
July | 0.00 | 0.00 | 0.596715E+11 | 0.348255E+11 | 74544.78 | 18-JUL-08:61 | 33764.45 | 0.00 |
August | 0.00 | 0.00 | 0.591073E+11 | 0.322316E+11 | 74630.39 | 11-AUG-08:61 | 34553.68 | 0.00 |
September | 0.00 | 0.00 | 0.488762E+11 | 0.288023E+11 | 74377.30 | 06-SEP-08:61 | 35141.32 | 0.00 |
October | 0.00 | 0.00 | 0.316842E+11 | 0.249466E+11 | 71420.03 | 12-OCT-08:62 | 39547.26 | 0.00 |
November | 0.00 | 0.00 | 0.166291E+11 | 0.142545E+11 | 31351.61 | 09-NOV-09:03 | 22064.68 | 0.00 |
December | 0.00 | 0.00 | 0.470759E+10 | 0.407390E+10 | 12027.41 | 28-DEC-15:00 | 10767.38 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.381568E+12 | 0.267873E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.219419E+10 | 0.195761E+10 | 9407.13 | 8815.87 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.596715E+11 | 0.371935E+11 | 74630.39 | 53604.79 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.211463E+10 | 0.183890E+10 | 5158.51 | 12-JAN-15:00 | 4847.05 | 0.00 |
February | 0.00 | 0.00 | 0.498943E+10 | 0.432324E+10 | 8305.84 | 22-FEB-14:50 | 7612.01 | 0.00 |
March | 0.00 | 0.00 | 0.105088E+11 | 0.914164E+10 | 33976.62 | 11-MAR-09:02 | 28619.90 | 0.00 |
April | 0.00 | 0.00 | 0.157934E+11 | 0.142597E+11 | 34879.55 | 26-APR-08:61 | 26437.16 | 0.00 |
May | 0.00 | 0.00 | 0.224898E+11 | 0.181879E+11 | 36736.89 | 24-MAY-08:61 | 21424.06 | 0.00 |
June | 0.00 | 0.00 | 0.251954E+11 | 0.180270E+11 | 37349.04 | 24-JUN-08:61 | 19784.08 | 0.00 |
July | 0.00 | 0.00 | 0.283989E+11 | 0.169247E+11 | 37713.92 | 18-JUL-08:61 | 18753.02 | 0.00 |
August | 0.00 | 0.00 | 0.281766E+11 | 0.157146E+11 | 38022.48 | 12-AUG-08:61 | 17507.91 | 0.00 |
September | 0.00 | 0.00 | 0.233225E+11 | 0.141026E+11 | 37282.16 | 06-SEP-08:61 | 20048.14 | 0.00 |
October | 0.00 | 0.00 | 0.157529E+11 | 0.126182E+11 | 35933.08 | 12-OCT-08:62 | 22034.65 | 0.00 |
November | 0.00 | 0.00 | 0.918339E+10 | 0.794232E+10 | 16181.10 | 09-NOV-09:03 | 12280.38 | 0.00 |
December | 0.00 | 0.00 | 0.366932E+10 | 0.314529E+10 | 6448.94 | 03-DEC-14:00 | 6124.25 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.189595E+12 | 0.136226E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.211463E+10 | 0.183890E+10 | 5158.51 | 4847.05 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.283989E+11 | 0.181879E+11 | 38022.48 | 28619.90 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.879478E+09 | 0.798950E+09 | 4593.19 | 12-JAN-15:00 | 4325.60 | 0.00 |
February | 0.00 | 0.00 | 0.317559E+10 | 0.280840E+10 | 7905.87 | 22-FEB-14:00 | 7262.99 | 0.00 |
March | 0.00 | 0.00 | 0.794985E+10 | 0.696161E+10 | 34680.63 | 11-MAR-08:62 | 25859.42 | 0.00 |
April | 0.00 | 0.00 | 0.126298E+11 | 0.114149E+11 | 35360.26 | 26-APR-07:01 | 24622.00 | 0.00 |
May | 0.00 | 0.00 | 0.186358E+11 | 0.149788E+11 | 37157.47 | 24-MAY-07:01 | 19840.85 | 0.00 |
June | 0.00 | 0.00 | 0.210087E+11 | 0.147933E+11 | 38015.85 | 25-JUN-08:61 | 16041.23 | 0.00 |
July | 0.00 | 0.00 | 0.232944E+11 | 0.134206E+11 | 38060.61 | 28-JUL-07:01 | 16546.84 | 0.00 |
August | 0.00 | 0.00 | 0.235762E+11 | 0.126921E+11 | 38127.72 | 21-AUG-07:03 | 14138.48 | 0.00 |
September | 0.00 | 0.00 | 0.190452E+11 | 0.111572E+11 | 38162.24 | 09-SEP-07:01 | 16420.57 | 0.00 |
October | 0.00 | 0.00 | 0.124231E+11 | 0.991347E+10 | 36398.96 | 12-OCT-07:02 | 19974.49 | 0.00 |
November | 0.00 | 0.00 | 0.678828E+10 | 0.595976E+10 | 10898.92 | 09-NOV-13:40 | 9521.50 | 0.00 |
December | 0.00 | 0.00 | 0.198253E+10 | 0.175228E+10 | 5880.20 | 28-DEC-14:00 | 5340.65 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.151389E+12 | 0.106651E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.879478E+09 | 0.798950E+09 | 4593.19 | 4325.60 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.235762E+11 | 0.149788E+11 | 38162.24 | 25859.42 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.784225E+09 | 0.711790E+09 | 4449.80 | 12-JAN-15:00 | 4189.48 | 0.00 |
February | 0.00 | 0.00 | 0.308462E+10 | 0.272825E+10 | 7838.33 | 22-FEB-14:00 | 7200.14 | 0.00 |
March | 0.00 | 0.00 | 0.792739E+10 | 0.694151E+10 | 34745.00 | 11-MAR-08:62 | 25913.38 | 0.00 |
April | 0.00 | 0.00 | 0.126890E+11 | 0.114693E+11 | 35428.92 | 26-APR-07:01 | 24708.86 | 0.00 |
May | 0.00 | 0.00 | 0.187752E+11 | 0.151012E+11 | 37217.19 | 24-MAY-07:01 | 19923.87 | 0.00 |
June | 0.00 | 0.00 | 0.211521E+11 | 0.149113E+11 | 38083.44 | 25-JUN-08:61 | 16175.43 | 0.00 |
July | 0.00 | 0.00 | 0.234615E+11 | 0.135477E+11 | 38128.27 | 28-JUL-07:01 | 16653.67 | 0.00 |
August | 0.00 | 0.00 | 0.237035E+11 | 0.127852E+11 | 38195.50 | 21-AUG-07:04 | 14175.07 | 0.00 |
September | 0.00 | 0.00 | 0.191497E+11 | 0.112342E+11 | 38230.09 | 09-SEP-07:01 | 16485.45 | 0.00 |
October | 0.00 | 0.00 | 0.124801E+11 | 0.996234E+10 | 36466.27 | 12-OCT-07:02 | 20043.77 | 0.00 |
November | 0.00 | 0.00 | 0.674584E+10 | 0.592186E+10 | 10869.97 | 09-NOV-13:40 | 9495.40 | 0.00 |
December | 0.00 | 0.00 | 0.186978E+10 | 0.165311E+10 | 5746.56 | 28-DEC-14:00 | 5217.33 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.151823E+12 | 0.106968E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.784225E+09 | 0.711790E+09 | 4449.80 | 4189.48 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.237035E+11 | 0.151012E+11 | 38230.09 | 25913.38 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.673483E+09 | 0.610206E+09 | 4248.69 | 12-JAN-15:00 | 3997.54 | 0.00 |
February | 0.00 | 0.00 | 0.292797E+10 | 0.259056E+10 | 7698.00 | 22-FEB-14:00 | 7067.52 | 0.00 |
March | 0.00 | 0.00 | 0.774957E+10 | 0.678351E+10 | 34664.60 | 11-MAR-08:62 | 25748.63 | 0.00 |
April | 0.00 | 0.00 | 0.125553E+11 | 0.113449E+11 | 35348.12 | 26-APR-07:01 | 24554.65 | 0.00 |
May | 0.00 | 0.00 | 0.186583E+11 | 0.150002E+11 | 37150.62 | 24-MAY-07:01 | 19804.11 | 0.00 |
June | 0.00 | 0.00 | 0.210296E+11 | 0.148123E+11 | 38013.03 | 25-JUN-08:61 | 16041.47 | 0.00 |
July | 0.00 | 0.00 | 0.233536E+11 | 0.134678E+11 | 38057.79 | 28-JUL-07:01 | 16502.12 | 0.00 |
August | 0.00 | 0.00 | 0.235639E+11 | 0.126850E+11 | 38124.89 | 21-AUG-07:04 | 14076.46 | 0.00 |
September | 0.00 | 0.00 | 0.190115E+11 | 0.111326E+11 | 38159.42 | 09-SEP-07:01 | 16342.53 | 0.00 |
October | 0.00 | 0.00 | 0.123450E+11 | 0.984785E+10 | 36391.40 | 12-OCT-07:02 | 19912.55 | 0.00 |
November | 0.00 | 0.00 | 0.658829E+10 | 0.578131E+10 | 10753.21 | 09-NOV-13:40 | 9386.93 | 0.00 |
December | 0.00 | 0.00 | 0.170903E+10 | 0.151168E+10 | 5574.92 | 02-DEC-14:00 | 5574.92 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.150165E+12 | 0.105568E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.673483E+09 | 0.610206E+09 | 4248.69 | 3997.54 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.235639E+11 | 0.150002E+11 | 38159.42 | 25748.63 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.122581E+10 | 0.109116E+10 | 8229.33 | 12-JAN-15:10 | 7567.61 | 0.00 |
February | 0.00 | 0.00 | 0.539843E+10 | 0.469735E+10 | 14873.70 | 22-FEB-14:00 | 13375.75 | 0.00 |
March | 0.00 | 0.00 | 0.145666E+11 | 0.125781E+11 | 63965.98 | 11-MAR-09:02 | 49477.33 | 0.00 |
April | 0.00 | 0.00 | 0.234206E+11 | 0.210757E+11 | 65167.47 | 26-APR-08:61 | 47326.89 | 0.00 |
May | 0.00 | 0.00 | 0.349445E+11 | 0.279357E+11 | 68824.35 | 24-MAY-08:61 | 37210.73 | 0.00 |
June | 0.00 | 0.00 | 0.393709E+11 | 0.276066E+11 | 70528.48 | 25-JUN-09:03 | 30385.82 | 0.00 |
July | 0.00 | 0.00 | 0.434279E+11 | 0.248308E+11 | 70600.95 | 28-JUL-08:61 | 32837.18 | 0.00 |
August | 0.00 | 0.00 | 0.441233E+11 | 0.234806E+11 | 70834.86 | 21-AUG-08:04 | 26476.25 | 0.00 |
September | 0.00 | 0.00 | 0.353562E+11 | 0.205215E+11 | 70906.51 | 04-SEP-09:01 | 28683.64 | 0.00 |
October | 0.00 | 0.00 | 0.231285E+11 | 0.182345E+11 | 67550.67 | 12-OCT-08:62 | 37125.31 | 0.00 |
November | 0.00 | 0.00 | 0.122664E+11 | 0.105878E+11 | 30794.07 | 11-NOV-10:03 | 23772.70 | 0.00 |
December | 0.00 | 0.00 | 0.303298E+10 | 0.263465E+10 | 10702.98 | 28-DEC-14:00 | 9485.41 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.280262E+12 | 0.195275E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.122581E+10 | 0.109116E+10 | 8229.33 | 7567.61 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.441233E+11 | 0.279357E+11 | 70906.51 | 49477.33 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.611341E+09 | 0.545966E+09 | 4278.55 | 12-JAN-15:10 | 3953.71 | 0.00 |
February | 0.00 | 0.00 | 0.280166E+10 | 0.244844E+10 | 7766.56 | 22-FEB-14:00 | 7008.14 | 0.00 |
March | 0.00 | 0.00 | 0.759688E+10 | 0.658119E+10 | 33581.27 | 11-MAR-09:02 | 26049.91 | 0.00 |
April | 0.00 | 0.00 | 0.122272E+11 | 0.110188E+11 | 34192.15 | 26-APR-08:61 | 24914.12 | 0.00 |
May | 0.00 | 0.00 | 0.182401E+11 | 0.146046E+11 | 36123.00 | 24-MAY-08:61 | 19628.53 | 0.00 |
June | 0.00 | 0.00 | 0.205193E+11 | 0.144165E+11 | 37032.57 | 25-JUN-09:03 | 15945.53 | 0.00 |
July | 0.00 | 0.00 | 0.226348E+11 | 0.129819E+11 | 37072.05 | 28-JUL-08:61 | 17308.30 | 0.00 |
August | 0.00 | 0.00 | 0.229793E+11 | 0.122692E+11 | 37193.44 | 21-AUG-08:05 | 13814.82 | 0.00 |
September | 0.00 | 0.00 | 0.184341E+11 | 0.107335E+11 | 37231.06 | 04-SEP-09:03 | 14924.26 | 0.00 |
October | 0.00 | 0.00 | 0.120715E+11 | 0.954637E+10 | 35463.56 | 12-OCT-08:62 | 19648.41 | 0.00 |
November | 0.00 | 0.00 | 0.640893E+10 | 0.555234E+10 | 15169.53 | 11-NOV-10:03 | 11764.98 | 0.00 |
December | 0.00 | 0.00 | 0.156481E+10 | 0.136538E+10 | 5568.22 | 28-DEC-14:00 | 4954.94 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.146090E+12 | 0.102064E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.611341E+09 | 0.545966E+09 | 4278.55 | 3953.71 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.229793E+11 | 0.146046E+11 | 37231.06 | 26049.91 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.578855E+09 | 0.516449E+09 | 4205.34 | 12-JAN-15:10 | 3884.46 | 0.00 |
February | 0.00 | 0.00 | 0.274129E+10 | 0.239566E+10 | 7701.59 | 22-FEB-14:00 | 6947.06 | 0.00 |
March | 0.00 | 0.00 | 0.752527E+10 | 0.651710E+10 | 33482.10 | 11-MAR-09:02 | 25932.14 | 0.00 |
April | 0.00 | 0.00 | 0.121683E+11 | 0.109637E+11 | 34092.62 | 26-APR-08:61 | 24800.09 | 0.00 |
May | 0.00 | 0.00 | 0.181813E+11 | 0.145535E+11 | 36018.99 | 24-MAY-08:61 | 19536.64 | 0.00 |
June | 0.00 | 0.00 | 0.204580E+11 | 0.143663E+11 | 36927.36 | 25-JUN-09:03 | 15824.79 | 0.00 |
July | 0.00 | 0.00 | 0.225788E+11 | 0.129394E+11 | 36979.40 | 28-JUL-08:61 | 17221.21 | 0.00 |
August | 0.00 | 0.00 | 0.229212E+11 | 0.122261E+11 | 37087.77 | 21-AUG-08:61 | 14002.14 | 0.00 |
September | 0.00 | 0.00 | 0.183801E+11 | 0.106925E+11 | 37125.29 | 04-SEP-09:01 | 14997.76 | 0.00 |
October | 0.00 | 0.00 | 0.120169E+11 | 0.949938E+10 | 35362.92 | 12-OCT-08:62 | 19556.74 | 0.00 |
November | 0.00 | 0.00 | 0.634966E+10 | 0.549934E+10 | 14786.69 | 11-NOV-10:03 | 11453.38 | 0.00 |
December | 0.00 | 0.00 | 0.151277E+10 | 0.132018E+10 | 5501.07 | 28-DEC-14:00 | 4892.94 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.145412E+12 | 0.101490E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.578855E+09 | 0.516449E+09 | 4205.34 | 3884.46 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.229212E+11 | 0.145535E+11 | 37125.29 | 25932.14 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.505872E+09 | 0.450525E+09 | 4031.34 | 12-JAN-15:10 | 3722.12 | 0.00 |
February | 0.00 | 0.00 | 0.258944E+10 | 0.226458E+10 | 7571.20 | 22-FEB-14:00 | 6826.67 | 0.00 |
March | 0.00 | 0.00 | 0.737006E+10 | 0.638124E+10 | 33546.42 | 11-MAR-09:02 | 25898.37 | 0.00 |
April | 0.00 | 0.00 | 0.121276E+11 | 0.109270E+11 | 34158.31 | 26-APR-08:61 | 24803.16 | 0.00 |
May | 0.00 | 0.00 | 0.182193E+11 | 0.145904E+11 | 36093.44 | 24-MAY-08:61 | 19543.76 | 0.00 |
June | 0.00 | 0.00 | 0.205238E+11 | 0.144247E+11 | 37011.57 | 25-JUN-09:01 | 15947.35 | 0.00 |
July | 0.00 | 0.00 | 0.226804E+11 | 0.130193E+11 | 37065.75 | 28-JUL-08:61 | 17256.39 | 0.00 |
August | 0.00 | 0.00 | 0.230249E+11 | 0.123039E+11 | 37172.34 | 21-AUG-08:61 | 14032.54 | 0.00 |
September | 0.00 | 0.00 | 0.184429E+11 | 0.107424E+11 | 37209.94 | 04-SEP-09:01 | 15031.87 | 0.00 |
October | 0.00 | 0.00 | 0.120127E+11 | 0.949787E+10 | 35437.52 | 12-OCT-08:62 | 19561.48 | 0.00 |
November | 0.00 | 0.00 | 0.624460E+10 | 0.540780E+10 | 13762.41 | 11-NOV-10:03 | 10635.93 | 0.00 |
December | 0.00 | 0.00 | 0.138307E+10 | 0.120876E+10 | 5347.44 | 28-DEC-14:00 | 4753.55 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.145125E+12 | 0.101219E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.505872E+09 | 0.450525E+09 | 4031.34 | 3722.12 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.230249E+11 | 0.145904E+11 | 37209.94 | 25898.37 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.509716E+09 | 0.459627E+09 | 4132.86 | 12-JAN-15:10 | 3862.39 | 0.00 |
February | 0.00 | 0.00 | 0.262334E+10 | 0.232412E+10 | 8032.08 | 22-FEB-14:00 | 7322.23 | 0.00 |
March | 0.00 | 0.00 | 0.767216E+10 | 0.671075E+10 | 36721.99 | 11-MAR-09:02 | 28552.69 | 0.00 |
April | 0.00 | 0.00 | 0.131574E+11 | 0.119387E+11 | 37349.96 | 17-APR-08:61 | 27787.40 | 0.00 |
May | 0.00 | 0.00 | 0.199192E+11 | 0.161455E+11 | 39946.64 | 24-MAY-08:61 | 20228.05 | 0.00 |
June | 0.00 | 0.00 | 0.223708E+11 | 0.160227E+11 | 40613.90 | 24-JUN-08:61 | 18668.33 | 0.00 |
July | 0.00 | 0.00 | 0.247941E+11 | 0.146266E+11 | 40686.86 | 26-JUL-08:61 | 18140.68 | 0.00 |
August | 0.00 | 0.00 | 0.252032E+11 | 0.139261E+11 | 40680.77 | 21-AUG-08:61 | 15791.36 | 0.00 |
September | 0.00 | 0.00 | 0.201693E+11 | 0.121017E+11 | 40753.17 | 09-SEP-08:61 | 17587.65 | 0.00 |
October | 0.00 | 0.00 | 0.132222E+11 | 0.106150E+11 | 38946.91 | 12-OCT-08:62 | 21152.43 | 0.00 |
November | 0.00 | 0.00 | 0.669646E+10 | 0.586936E+10 | 14113.37 | 11-NOV-10:03 | 11055.04 | 0.00 |
December | 0.00 | 0.00 | 0.141878E+10 | 0.125960E+10 | 5567.83 | 28-DEC-14:00 | 5008.58 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.157757E+12 | 0.112000E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.509716E+09 | 0.459627E+09 | 4132.86 | 3862.39 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.252032E+11 | 0.161455E+11 | 40753.17 | 28552.69 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.219124E+10 | 0.37 | 3012.03 | 01-JAN-09:01 | 0.90 |
February | 0.197808E+10 | 0.37 | 1842.73 | 02-FEB-09:02 | 0.70 |
March | 0.219502E+10 | 0.37 | 3012.03 | 11-MAR-09:02 | 0.89 |
April | 0.213544E+10 | 0.37 | 3012.03 | 03-APR-08:62 | 0.89 |
May | 0.235130E+10 | 0.38 | 3012.03 | 01-MAY-08:61 | 0.89 |
June | 0.241767E+10 | 0.39 | 3012.03 | 01-JUN-08:61 | 0.89 |
July | 0.251734E+10 | 0.39 | 3012.03 | 01-JUL-08:61 | 0.88 |
August | 0.249649E+10 | 0.39 | 3012.03 | 01-AUG-08:61 | 0.88 |
September | 0.224380E+10 | 0.38 | 3012.03 | 01-SEP-08:61 | 0.88 |
October | 0.219278E+10 | 0.37 | 3012.03 | 01-OCT-07:02 | 0.89 |
November | 0.211228E+10 | 0.37 | 1204.81 | 24-NOV-10:30 | 0.54 |
December | 0.219525E+10 | 0.37 | 2318.87 | 23-DEC-09:02 | 0.79 |
Annual Sum or Average | 0.270267E+11 | 0.38 | |||
Minimum of Months | 0.197808E+10 | 0.37 | 1204.81 | 0.54 | |
Maximum of Months | 0.251734E+10 | 0.39 | 3012.03 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.873327E+09 | 0.37 | 1542.78 | 01-JAN-09:01 | 0.89 |
February | 0.807233E+09 | 0.38 | 645.32 | 02-FEB-09:02 | 0.56 |
March | 0.927676E+09 | 0.38 | 1542.78 | 11-MAR-09:02 | 0.89 |
April | 0.929865E+09 | 0.38 | 1542.78 | 01-APR-08:62 | 0.89 |
May | 0.107317E+10 | 0.39 | 1542.78 | 01-MAY-08:61 | 0.89 |
June | 0.112330E+10 | 0.40 | 1542.78 | 01-JUN-08:61 | 0.89 |
July | 0.117729E+10 | 0.40 | 1542.78 | 01-JUL-08:61 | 0.88 |
August | 0.116013E+10 | 0.40 | 1542.78 | 01-AUG-08:61 | 0.88 |
September | 0.101701E+10 | 0.38 | 1542.78 | 01-SEP-08:61 | 0.88 |
October | 0.948474E+09 | 0.37 | 1542.78 | 01-OCT-07:02 | 0.89 |
November | 0.883182E+09 | 0.38 | 617.11 | 11-NOV-09:30 | 0.54 |
December | 0.880057E+09 | 0.38 | 766.38 | 23-DEC-09:02 | 0.62 |
Annual Sum or Average | 0.118007E+11 | 0.38 | |||
Minimum of Months | 0.807233E+09 | 0.37 | 617.11 | 0.54 | |
Maximum of Months | 0.117729E+10 | 0.40 | 1542.78 | 0.89 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.892885E+09 | 0.29 | 1536.34 | 01-JAN-09:01 | 0.90 |
February | 0.805384E+09 | 0.29 | 728.26 | 02-FEB-08:63 | 0.61 |
March | 0.907272E+09 | 0.30 | 1536.34 | 11-MAR-08:62 | 0.89 |
April | 0.872258E+09 | 0.30 | 1536.34 | 02-APR-08:61 | 0.89 |
May | 0.984601E+09 | 0.31 | 1536.34 | 01-MAY-07:01 | 0.89 |
June | 0.101956E+10 | 0.32 | 1536.34 | 01-JUN-07:01 | 0.89 |
July | 0.104349E+10 | 0.32 | 1536.34 | 01-JUL-07:01 | 0.88 |
August | 0.105290E+10 | 0.32 | 1536.34 | 01-AUG-07:01 | 0.88 |
September | 0.922053E+09 | 0.30 | 1536.34 | 01-SEP-07:01 | 0.88 |
October | 0.892977E+09 | 0.29 | 1536.34 | 01-OCT-08:61 | 0.89 |
November | 0.862810E+09 | 0.29 | 614.54 | 03-NOV-07:40 | 0.54 |
December | 0.885183E+09 | 0.29 | 918.35 | 23-DEC-08:62 | 0.69 |
Annual Sum or Average | 0.111414E+11 | 0.30 | |||
Minimum of Months | 0.805384E+09 | 0.29 | 614.54 | 0.54 | |
Maximum of Months | 0.105290E+10 | 0.32 | 1536.34 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.896019E+09 | 0.29 | 1539.72 | 01-JAN-09:01 | 0.90 |
February | 0.807240E+09 | 0.29 | 768.29 | 02-FEB-08:63 | 0.62 |
March | 0.909272E+09 | 0.30 | 1539.72 | 11-MAR-08:62 | 0.89 |
April | 0.874379E+09 | 0.30 | 1539.72 | 02-APR-08:61 | 0.89 |
May | 0.988626E+09 | 0.31 | 1539.72 | 01-MAY-07:01 | 0.89 |
June | 0.102368E+10 | 0.32 | 1539.72 | 01-JUN-07:01 | 0.89 |
July | 0.104868E+10 | 0.32 | 1539.72 | 01-JUL-07:01 | 0.88 |
August | 0.105690E+10 | 0.32 | 1539.72 | 01-AUG-07:01 | 0.88 |
September | 0.924865E+09 | 0.30 | 1539.72 | 01-SEP-07:01 | 0.88 |
October | 0.895120E+09 | 0.29 | 1539.72 | 01-OCT-08:61 | 0.89 |
November | 0.864708E+09 | 0.29 | 615.89 | 01-NOV-09:40 | 0.54 |
December | 0.887238E+09 | 0.29 | 984.16 | 23-DEC-08:62 | 0.72 |
Annual Sum or Average | 0.111767E+11 | 0.30 | |||
Minimum of Months | 0.807240E+09 | 0.29 | 615.89 | 0.54 | |
Maximum of Months | 0.105690E+10 | 0.32 | 1539.72 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.895130E+09 | 0.29 | 1536.18 | 01-JAN-09:01 | 0.90 |
February | 0.805492E+09 | 0.29 | 807.36 | 02-FEB-08:63 | 0.64 |
March | 0.907153E+09 | 0.30 | 1536.18 | 11-MAR-08:62 | 0.89 |
April | 0.871784E+09 | 0.30 | 1536.18 | 02-APR-08:61 | 0.89 |
May | 0.984672E+09 | 0.31 | 1536.18 | 01-MAY-07:01 | 0.89 |
June | 0.101951E+10 | 0.32 | 1536.18 | 01-JUN-07:01 | 0.89 |
July | 0.104473E+10 | 0.32 | 1536.18 | 01-JUL-07:01 | 0.88 |
August | 0.105228E+10 | 0.32 | 1536.18 | 01-AUG-07:01 | 0.88 |
September | 0.920824E+09 | 0.30 | 1536.18 | 01-SEP-07:01 | 0.88 |
October | 0.892883E+09 | 0.29 | 1536.18 | 01-OCT-08:61 | 0.89 |
November | 0.862719E+09 | 0.29 | 614.47 | 02-NOV-07:10 | 0.54 |
December | 0.885317E+09 | 0.29 | 1040.78 | 23-DEC-08:62 | 0.74 |
Annual Sum or Average | 0.111425E+11 | 0.30 | |||
Minimum of Months | 0.805492E+09 | 0.29 | 614.47 | 0.54 | |
Maximum of Months | 0.105228E+10 | 0.32 | 1536.18 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.151288E+10 | 0.27 | 2815.57 | 01-JAN-10:01 | 0.89 |
February | 0.136269E+10 | 0.27 | 1927.72 | 02-FEB-09:02 | 0.75 |
March | 0.153708E+10 | 0.28 | 2815.57 | 11-MAR-09:02 | 0.89 |
April | 0.148206E+10 | 0.27 | 2815.57 | 01-APR-08:62 | 0.89 |
May | 0.170745E+10 | 0.29 | 2815.57 | 01-MAY-08:61 | 0.89 |
June | 0.178139E+10 | 0.30 | 2815.57 | 01-JUN-08:61 | 0.89 |
July | 0.183707E+10 | 0.30 | 2815.57 | 01-JUL-08:61 | 0.88 |
August | 0.184795E+10 | 0.30 | 2815.57 | 01-AUG-08:61 | 0.88 |
September | 0.159483E+10 | 0.28 | 2815.57 | 01-SEP-08:61 | 0.88 |
October | 0.151396E+10 | 0.27 | 2815.57 | 01-OCT-09:01 | 0.89 |
November | 0.145959E+10 | 0.27 | 1126.23 | 02-NOV-19:00 | 0.54 |
December | 0.149680E+10 | 0.27 | 2392.96 | 23-DEC-09:02 | 0.83 |
Annual Sum or Average | 0.191337E+11 | 0.28 | |||
Minimum of Months | 0.136269E+10 | 0.27 | 1126.23 | 0.54 | |
Maximum of Months | 0.184795E+10 | 0.30 | 2815.57 | 0.89 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.829022E+09 | 0.28 | 1543.22 | 01-JAN-10:01 | 0.93 |
February | 0.746837E+09 | 0.28 | 985.17 | 02-FEB-09:02 | 0.74 |
March | 0.842446E+09 | 0.29 | 1543.22 | 11-MAR-09:02 | 0.92 |
April | 0.812723E+09 | 0.28 | 1543.22 | 02-APR-09:01 | 0.92 |
May | 0.938053E+09 | 0.30 | 1543.22 | 01-MAY-08:61 | 0.92 |
June | 0.977480E+09 | 0.31 | 1543.22 | 01-JUN-08:61 | 0.92 |
July | 0.100643E+10 | 0.31 | 1543.22 | 01-JUL-08:61 | 0.91 |
August | 0.101214E+10 | 0.31 | 1543.22 | 01-AUG-08:61 | 0.91 |
September | 0.873757E+09 | 0.29 | 1543.22 | 01-SEP-08:61 | 0.91 |
October | 0.829724E+09 | 0.28 | 1543.22 | 01-OCT-09:01 | 0.92 |
November | 0.800006E+09 | 0.28 | 617.29 | 03-NOV-09:20 | 0.56 |
December | 0.820336E+09 | 0.28 | 1227.67 | 23-DEC-09:02 | 0.84 |
Annual Sum or Average | 0.104890E+11 | 0.29 | |||
Minimum of Months | 0.746837E+09 | 0.28 | 617.29 | 0.56 | |
Maximum of Months | 0.101214E+10 | 0.31 | 1543.22 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.826382E+09 | 0.28 | 1537.75 | 01-JAN-10:01 | 0.93 |
February | 0.744228E+09 | 0.28 | 1010.41 | 02-FEB-09:02 | 0.76 |
March | 0.839446E+09 | 0.29 | 1537.75 | 11-MAR-09:02 | 0.92 |
April | 0.809759E+09 | 0.28 | 1537.75 | 02-APR-09:01 | 0.92 |
May | 0.934817E+09 | 0.30 | 1537.75 | 01-MAY-08:61 | 0.92 |
June | 0.974191E+09 | 0.31 | 1537.75 | 01-JUN-08:61 | 0.92 |
July | 0.100329E+10 | 0.31 | 1537.75 | 01-JUL-08:61 | 0.91 |
August | 0.100896E+10 | 0.31 | 1537.75 | 01-AUG-08:61 | 0.91 |
September | 0.870788E+09 | 0.29 | 1537.75 | 01-SEP-08:61 | 0.91 |
October | 0.826768E+09 | 0.28 | 1537.75 | 01-OCT-09:01 | 0.92 |
November | 0.797168E+09 | 0.28 | 615.10 | 09-NOV-15:10 | 0.56 |
December | 0.817469E+09 | 0.28 | 1263.26 | 23-DEC-09:02 | 0.85 |
Annual Sum or Average | 0.104533E+11 | 0.29 | |||
Minimum of Months | 0.744228E+09 | 0.28 | 615.10 | 0.56 | |
Maximum of Months | 0.100896E+10 | 0.31 | 1537.75 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.829747E+09 | 0.28 | 1542.10 | 01-JAN-10:01 | 0.93 |
February | 0.746503E+09 | 0.28 | 1119.41 | 02-FEB-09:02 | 0.80 |
March | 0.841782E+09 | 0.29 | 1542.10 | 11-MAR-09:02 | 0.92 |
April | 0.811842E+09 | 0.28 | 1542.10 | 02-APR-09:01 | 0.92 |
May | 0.937962E+09 | 0.30 | 1542.10 | 01-MAY-08:61 | 0.92 |
June | 0.978085E+09 | 0.31 | 1542.10 | 01-JUN-08:61 | 0.92 |
July | 0.100839E+10 | 0.31 | 1542.10 | 01-JUL-08:61 | 0.91 |
August | 0.101360E+10 | 0.31 | 1542.10 | 01-AUG-08:61 | 0.91 |
September | 0.874158E+09 | 0.29 | 1542.10 | 01-SEP-08:61 | 0.91 |
October | 0.829142E+09 | 0.28 | 1542.10 | 01-OCT-09:01 | 0.92 |
November | 0.799425E+09 | 0.28 | 616.84 | 01-NOV-19:03 | 0.56 |
December | 0.819955E+09 | 0.28 | 1395.62 | 23-DEC-09:02 | 0.89 |
Annual Sum or Average | 0.104906E+11 | 0.29 | |||
Minimum of Months | 0.746503E+09 | 0.28 | 616.84 | 0.56 | |
Maximum of Months | 0.101360E+10 | 0.31 | 1542.10 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.904314E+09 | 0.27 | 1677.69 | 01-JAN-10:01 | 0.89 |
February | 0.812747E+09 | 0.27 | 1471.04 | 02-FEB-09:02 | 0.84 |
March | 0.915729E+09 | 0.28 | 1677.69 | 11-MAR-09:02 | 0.89 |
April | 0.882179E+09 | 0.27 | 1677.69 | 02-APR-09:01 | 0.89 |
May | 0.101944E+10 | 0.29 | 1677.69 | 01-MAY-08:61 | 0.89 |
June | 0.106320E+10 | 0.30 | 1677.69 | 01-JUN-08:61 | 0.89 |
July | 0.109878E+10 | 0.30 | 1677.69 | 01-JUL-08:61 | 0.88 |
August | 0.110269E+10 | 0.30 | 1677.69 | 01-AUG-08:61 | 0.88 |
September | 0.952155E+09 | 0.28 | 1677.69 | 01-SEP-08:61 | 0.88 |
October | 0.902513E+09 | 0.27 | 1677.69 | 01-OCT-09:01 | 0.89 |
November | 0.869715E+09 | 0.27 | 671.08 | 01-NOV-13:00 | 0.54 |
December | 0.892494E+09 | 0.27 | 1677.69 | 23-DEC-09:02 | 0.90 |
Annual Sum or Average | 0.114159E+11 | 0.28 | |||
Minimum of Months | 0.812747E+09 | 0.27 | 671.08 | 0.54 | |
Maximum of Months | 0.110269E+10 | 0.30 | 1677.69 | 0.90 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.279933E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.411420E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.762194E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.114364E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.158736E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.171568E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.177900E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.170835E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.144781E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.106972E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.661825E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.348897E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.129158E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.279933E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.177900E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.144686E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.213978E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.376805E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.546170E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.757257E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.813796E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.842202E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.808147E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.682337E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.512189E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.332070E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.186664E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.621630E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.144686E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.842202E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.113242E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.166006E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.306873E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.447475E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.631619E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.676936E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.685664E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.673741E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.557523E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.417931E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.267871E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.142133E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.508701E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.113242E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.685664E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.111001E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.163887E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.306579E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.449234E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.635747E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.681092E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.690322E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.677240E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.560294E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.419559E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.267074E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.139389E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.510142E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.111001E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.690322E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.107936E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.159703E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.301984E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.445613E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.632179E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.677443E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.687212E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.673375E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.556592E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.416180E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.263014E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.134954E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.505618E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.107936E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.687212E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.185373E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.284690E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.557172E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.828614E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.118836E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.127615E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.128602E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.126580E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.103720E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.772346E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.480152E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.233376E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.939525E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.185373E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.128602E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.996180E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.150422E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.291171E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.430780E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.616978E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.661650E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.666567E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.655747E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.537910E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.401821E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.251676E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.124488E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.488883E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.996180E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.666567E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.984791E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.148600E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.289054E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.428882E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.614942E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.659578E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.664760E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.653902E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.536218E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.400141E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.249898E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.122820E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.486727E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.984791E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.664760E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.968510E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.144929E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.285532E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.428230E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.616495E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.661920E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.667964E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.656985E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.538188E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.400389E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.247581E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.119631E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.486470E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.968510E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.667964E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.104449E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.152810E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.302455E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.465739E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.675585E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.724922E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.734261E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.722671E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.591265E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.439869E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.267129E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.127939E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.530909E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.104449E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.734261E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.219124E+10 | 0.219419E+10 | 0.202435E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.197808E+10 | 0.781313E+10 | 10178088.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.219502E+10 | 0.196667E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.213544E+10 | 0.320043E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.235130E+10 | 0.464863E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.241767E+10 | 0.527270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.251734E+10 | 0.596715E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.249649E+10 | 0.591073E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.224380E+10 | 0.488762E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.219278E+10 | 0.316842E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.211228E+10 | 0.166291E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.219525E+10 | 0.470759E+10 | 21905223.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.270267E+11 | 0.381568E+12 | 0.234518E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.197808E+10 | 0.219419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.251734E+10 | 0.596715E+11 | 0.202435E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.873327E+09 | 0.211463E+10 | 37744673.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.807233E+09 | 0.498943E+10 | 130615.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.927676E+09 | 0.105088E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.929865E+09 | 0.157934E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.107317E+10 | 0.224898E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.112330E+10 | 0.251954E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.117729E+10 | 0.283989E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.116013E+10 | 0.281766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.101701E+10 | 0.233225E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.948474E+09 | 0.157529E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.883182E+09 | 0.918339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.880057E+09 | 0.366932E+10 | 1354854.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.118007E+11 | 0.189595E+12 | 39230142.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.807233E+09 | 0.211463E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.117729E+10 | 0.283989E+11 | 37744673.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.892885E+09 | 0.879478E+09 | 0.136145E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.805384E+09 | 0.317559E+10 | 3636090.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.907272E+09 | 0.794985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.872258E+09 | 0.126298E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.984601E+09 | 0.186358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.101956E+10 | 0.210087E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.104349E+10 | 0.232944E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.105290E+10 | 0.235762E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.922053E+09 | 0.190452E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.892977E+09 | 0.124231E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.862810E+09 | 0.678828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.885183E+09 | 0.198253E+10 | 9632561.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111414E+11 | 0.151389E+12 | 0.149413E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.805384E+09 | 0.879478E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.105290E+10 | 0.235762E+11 | 0.136145E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.896019E+09 | 0.784225E+09 | 0.181575E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.807240E+09 | 0.308462E+10 | 6928163.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.909272E+09 | 0.792739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.874379E+09 | 0.126890E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.988626E+09 | 0.187752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.102368E+10 | 0.211521E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.104868E+10 | 0.234615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.105690E+10 | 0.237035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.924865E+09 | 0.191497E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.895120E+09 | 0.124801E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.864708E+09 | 0.674584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.887238E+09 | 0.186978E+10 | 13808567.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111767E+11 | 0.151823E+12 | 0.202311E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.807240E+09 | 0.784225E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.105690E+10 | 0.237035E+11 | 0.181575E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.895130E+09 | 0.673483E+09 | 0.226443E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.805492E+09 | 0.292797E+10 | 11103645.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.907153E+09 | 0.774957E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.871784E+09 | 0.125553E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.984672E+09 | 0.186583E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.101951E+10 | 0.210296E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.104473E+10 | 0.233536E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.105228E+10 | 0.235639E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.920824E+09 | 0.190115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.892883E+09 | 0.123450E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.862719E+09 | 0.658829E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.885317E+09 | 0.170903E+10 | 18442397.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111425E+11 | 0.150165E+12 | 0.255989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.805492E+09 | 0.673483E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.105228E+10 | 0.235639E+11 | 0.226443E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.151288E+10 | 0.122581E+10 | 0.338634E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136269E+10 | 0.539843E+10 | 15809375.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153708E+10 | 0.145666E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.148206E+10 | 0.234206E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.170745E+10 | 0.349445E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.178139E+10 | 0.393709E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.183707E+10 | 0.434279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.184795E+10 | 0.441233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.159483E+10 | 0.353562E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.151396E+10 | 0.231285E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145959E+10 | 0.122664E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149680E+10 | 0.303298E+10 | 28247660.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.191337E+11 | 0.280262E+12 | 0.382691E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.136269E+10 | 0.122581E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.184795E+10 | 0.441233E+11 | 0.338634E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.829022E+09 | 0.611341E+09 | 0.171048E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.746837E+09 | 0.280166E+10 | 6169941.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.842446E+09 | 0.759688E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.812723E+09 | 0.122272E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.938053E+09 | 0.182401E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.977480E+09 | 0.205193E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.100643E+10 | 0.226348E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.101214E+10 | 0.229793E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.873757E+09 | 0.184341E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.829724E+09 | 0.120715E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.800006E+09 | 0.640893E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.820336E+09 | 0.156481E+10 | 12326231.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104890E+11 | 0.146090E+12 | 0.189545E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.746837E+09 | 0.611341E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.101214E+10 | 0.229793E+11 | 0.171048E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.826382E+09 | 0.578855E+09 | 0.181789E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.744228E+09 | 0.274129E+10 | 7660995.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.839446E+09 | 0.752527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.809759E+09 | 0.121683E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.934817E+09 | 0.181813E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.974191E+09 | 0.204580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.100329E+10 | 0.225788E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.100896E+10 | 0.229212E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.870788E+09 | 0.183801E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.826768E+09 | 0.120169E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.797168E+09 | 0.634966E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.817469E+09 | 0.151277E+10 | 13929673.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104533E+11 | 0.145412E+12 | 0.203379E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.744228E+09 | 0.578855E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.100896E+10 | 0.229212E+11 | 0.181789E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.829747E+09 | 0.505872E+09 | 0.220637E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.746503E+09 | 0.258944E+10 | 13966795.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.841782E+09 | 0.737006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.811842E+09 | 0.121276E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.937962E+09 | 0.182193E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.978085E+09 | 0.205238E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.100839E+10 | 0.226804E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.101360E+10 | 0.230249E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.874158E+09 | 0.184429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.829142E+09 | 0.120127E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.799425E+09 | 0.624460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.819955E+09 | 0.138307E+10 | 20397015.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104906E+11 | 0.145125E+12 | 0.255000E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.746503E+09 | 0.505872E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.101360E+10 | 0.230249E+11 | 0.220637E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.904314E+09 | 0.509716E+09 | 0.307119E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.812747E+09 | 0.262334E+10 | 38769127.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.915729E+09 | 0.767216E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.882179E+09 | 0.131574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.101944E+10 | 0.199192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.106320E+10 | 0.223708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.109878E+10 | 0.247941E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.110269E+10 | 0.252032E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.952155E+09 | 0.201693E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.902513E+09 | 0.132222E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.869715E+09 | 0.669646E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.892494E+09 | 0.141878E+10 | 39645677.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114159E+11 | 0.157757E+12 | 0.385534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.812747E+09 | 0.509716E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.110269E+10 | 0.252032E+11 | 0.307119E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.219124E+10 | 0.00 | 0.00 | 0.00 | 0.608086E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.197808E+10 | 0.00 | 0.00 | 0.00 | 0.213611E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.219502E+10 | 0.00 | 0.00 | 0.00 | 0.542692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.213544E+10 | 0.00 | 0.00 | 0.00 | 0.930093E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.235130E+10 | 0.00 | 0.00 | 0.00 | 0.135223E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.241767E+10 | 0.00 | 0.00 | 0.00 | 0.147391E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.251734E+10 | 0.00 | 0.00 | 0.00 | 0.152726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.249649E+10 | 0.00 | 0.00 | 0.00 | 0.145870E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.224380E+10 | 0.00 | 0.00 | 0.00 | 0.122343E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.219278E+10 | 0.00 | 0.00 | 0.00 | 0.850440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.211228E+10 | 0.00 | 0.00 | 0.00 | 0.450598E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.219525E+10 | 0.00 | 0.00 | 0.00 | 0.129372E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.270267E+11 | 0.00 | 0.00 | 0.00 | 0.102132E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.197808E+10 | 0.00 | 0.00 | 0.00 | 0.608086E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.251734E+10 | 0.00 | 0.00 | 0.00 | 0.152726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.873327E+09 | 0.00 | 0.00 | 0.00 | 0.573529E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.807233E+09 | 0.00 | 0.00 | 0.00 | 0.133255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.927676E+09 | 0.00 | 0.00 | 0.00 | 0.284038E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.929865E+09 | 0.00 | 0.00 | 0.00 | 0.453184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.107317E+10 | 0.00 | 0.00 | 0.00 | 0.649939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.112330E+10 | 0.00 | 0.00 | 0.00 | 0.701466E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.724473E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.116013E+10 | 0.00 | 0.00 | 0.00 | 0.692134E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.101701E+10 | 0.00 | 0.00 | 0.00 | 0.580636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.948474E+09 | 0.00 | 0.00 | 0.00 | 0.417341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.883182E+09 | 0.00 | 0.00 | 0.00 | 0.243752E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.880057E+09 | 0.00 | 0.00 | 0.00 | 0.986580E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.118007E+11 | 0.00 | 0.00 | 0.00 | 0.503623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.807233E+09 | 0.00 | 0.00 | 0.00 | 0.573529E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.724473E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.892885E+09 | 0.00 | 0.00 | 0.00 | 0.239537E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.805384E+09 | 0.00 | 0.00 | 0.00 | 0.854673E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.907272E+09 | 0.00 | 0.00 | 0.00 | 0.216146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.872258E+09 | 0.00 | 0.00 | 0.00 | 0.360250E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.984601E+09 | 0.00 | 0.00 | 0.00 | 0.533159E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.101956E+10 | 0.00 | 0.00 | 0.00 | 0.574980E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.104349E+10 | 0.00 | 0.00 | 0.00 | 0.581316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.105290E+10 | 0.00 | 0.00 | 0.00 | 0.568451E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.922053E+09 | 0.00 | 0.00 | 0.00 | 0.465317E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.892977E+09 | 0.00 | 0.00 | 0.00 | 0.328634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.862810E+09 | 0.00 | 0.00 | 0.00 | 0.181590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.885183E+09 | 0.00 | 0.00 | 0.00 | 0.536143E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111414E+11 | 0.00 | 0.00 | 0.00 | 0.397288E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.805384E+09 | 0.00 | 0.00 | 0.00 | 0.239537E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.105290E+10 | 0.00 | 0.00 | 0.00 | 0.581316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.896019E+09 | 0.00 | 0.00 | 0.00 | 0.213989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.807240E+09 | 0.00 | 0.00 | 0.00 | 0.831633E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.909272E+09 | 0.00 | 0.00 | 0.00 | 0.215651E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.874379E+09 | 0.00 | 0.00 | 0.00 | 0.361796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.988626E+09 | 0.00 | 0.00 | 0.00 | 0.536885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.102368E+10 | 0.00 | 0.00 | 0.00 | 0.578724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.104868E+10 | 0.00 | 0.00 | 0.00 | 0.585453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.105690E+10 | 0.00 | 0.00 | 0.00 | 0.571550E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.924865E+09 | 0.00 | 0.00 | 0.00 | 0.467808E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.895120E+09 | 0.00 | 0.00 | 0.00 | 0.330047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.864708E+09 | 0.00 | 0.00 | 0.00 | 0.180603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.887238E+09 | 0.00 | 0.00 | 0.00 | 0.506652E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111767E+11 | 0.00 | 0.00 | 0.00 | 0.398374E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.807240E+09 | 0.00 | 0.00 | 0.00 | 0.213989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.105690E+10 | 0.00 | 0.00 | 0.00 | 0.585453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.895130E+09 | 0.00 | 0.00 | 0.00 | 0.184229E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.805492E+09 | 0.00 | 0.00 | 0.00 | 0.791535E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.907153E+09 | 0.00 | 0.00 | 0.00 | 0.211269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.871784E+09 | 0.00 | 0.00 | 0.00 | 0.358435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.984672E+09 | 0.00 | 0.00 | 0.00 | 0.533712E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.101951E+10 | 0.00 | 0.00 | 0.00 | 0.575492E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.104473E+10 | 0.00 | 0.00 | 0.00 | 0.582739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.105228E+10 | 0.00 | 0.00 | 0.00 | 0.568147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.920824E+09 | 0.00 | 0.00 | 0.00 | 0.464510E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.892883E+09 | 0.00 | 0.00 | 0.00 | 0.326892E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.862719E+09 | 0.00 | 0.00 | 0.00 | 0.176743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.885317E+09 | 0.00 | 0.00 | 0.00 | 0.464222E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111425E+11 | 0.00 | 0.00 | 0.00 | 0.394193E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.805492E+09 | 0.00 | 0.00 | 0.00 | 0.184229E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.105228E+10 | 0.00 | 0.00 | 0.00 | 0.582739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.151288E+10 | 0.00 | 0.00 | 0.00 | 0.340847E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136269E+10 | 0.00 | 0.00 | 0.00 | 0.148421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153708E+10 | 0.00 | 0.00 | 0.00 | 0.403465E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.148206E+10 | 0.00 | 0.00 | 0.00 | 0.680408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.170745E+10 | 0.00 | 0.00 | 0.00 | 0.101761E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.178139E+10 | 0.00 | 0.00 | 0.00 | 0.109801E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.183707E+10 | 0.00 | 0.00 | 0.00 | 0.110231E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.184795E+10 | 0.00 | 0.00 | 0.00 | 0.108100E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.159483E+10 | 0.00 | 0.00 | 0.00 | 0.877720E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.151396E+10 | 0.00 | 0.00 | 0.00 | 0.620950E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145959E+10 | 0.00 | 0.00 | 0.00 | 0.334193E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149680E+10 | 0.00 | 0.00 | 0.00 | 0.836959E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.191337E+11 | 0.00 | 0.00 | 0.00 | 0.748187E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.136269E+10 | 0.00 | 0.00 | 0.00 | 0.340847E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.184795E+10 | 0.00 | 0.00 | 0.00 | 0.110231E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.829022E+09 | 0.00 | 0.00 | 0.00 | 0.167158E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.746837E+09 | 0.00 | 0.00 | 0.00 | 0.757383E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.842446E+09 | 0.00 | 0.00 | 0.00 | 0.206926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.812723E+09 | 0.00 | 0.00 | 0.00 | 0.349508E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.938053E+09 | 0.00 | 0.00 | 0.00 | 0.523173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.977480E+09 | 0.00 | 0.00 | 0.00 | 0.563902E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.100643E+10 | 0.00 | 0.00 | 0.00 | 0.565925E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.101214E+10 | 0.00 | 0.00 | 0.00 | 0.554533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.873757E+09 | 0.00 | 0.00 | 0.00 | 0.450535E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.829724E+09 | 0.00 | 0.00 | 0.00 | 0.318849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.800006E+09 | 0.00 | 0.00 | 0.00 | 0.171675E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.820336E+09 | 0.00 | 0.00 | 0.00 | 0.424540E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104890E+11 | 0.00 | 0.00 | 0.00 | 0.383993E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.746837E+09 | 0.00 | 0.00 | 0.00 | 0.167158E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.101214E+10 | 0.00 | 0.00 | 0.00 | 0.565925E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.826382E+09 | 0.00 | 0.00 | 0.00 | 0.158409E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.744228E+09 | 0.00 | 0.00 | 0.00 | 0.741768E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.839446E+09 | 0.00 | 0.00 | 0.00 | 0.205109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.809759E+09 | 0.00 | 0.00 | 0.00 | 0.347906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.934817E+09 | 0.00 | 0.00 | 0.00 | 0.521461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.974191E+09 | 0.00 | 0.00 | 0.00 | 0.562158E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.100329E+10 | 0.00 | 0.00 | 0.00 | 0.564431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.100896E+10 | 0.00 | 0.00 | 0.00 | 0.553006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.870788E+09 | 0.00 | 0.00 | 0.00 | 0.449139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.826768E+09 | 0.00 | 0.00 | 0.00 | 0.317465E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.797168E+09 | 0.00 | 0.00 | 0.00 | 0.170181E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.817469E+09 | 0.00 | 0.00 | 0.00 | 0.410727E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104533E+11 | 0.00 | 0.00 | 0.00 | 0.382195E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.744228E+09 | 0.00 | 0.00 | 0.00 | 0.158409E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.100896E+10 | 0.00 | 0.00 | 0.00 | 0.564431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.829747E+09 | 0.00 | 0.00 | 0.00 | 0.138763E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.746503E+09 | 0.00 | 0.00 | 0.00 | 0.702788E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.841782E+09 | 0.00 | 0.00 | 0.00 | 0.201354E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.811842E+09 | 0.00 | 0.00 | 0.00 | 0.347046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.937962E+09 | 0.00 | 0.00 | 0.00 | 0.522699E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.978085E+09 | 0.00 | 0.00 | 0.00 | 0.564111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.100839E+10 | 0.00 | 0.00 | 0.00 | 0.567125E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.101360E+10 | 0.00 | 0.00 | 0.00 | 0.555625E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.874158E+09 | 0.00 | 0.00 | 0.00 | 0.450773E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.829142E+09 | 0.00 | 0.00 | 0.00 | 0.317475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.799425E+09 | 0.00 | 0.00 | 0.00 | 0.167639E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.819955E+09 | 0.00 | 0.00 | 0.00 | 0.376359E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104906E+11 | 0.00 | 0.00 | 0.00 | 0.381564E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.746503E+09 | 0.00 | 0.00 | 0.00 | 0.138763E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.101360E+10 | 0.00 | 0.00 | 0.00 | 0.567125E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.904314E+09 | 0.00 | 0.00 | 0.00 | 0.140177E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.812747E+09 | 0.00 | 0.00 | 0.00 | 0.715357E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.915729E+09 | 0.00 | 0.00 | 0.00 | 0.210882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.882179E+09 | 0.00 | 0.00 | 0.00 | 0.377521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.101944E+10 | 0.00 | 0.00 | 0.00 | 0.573641E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.106320E+10 | 0.00 | 0.00 | 0.00 | 0.618602E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.109878E+10 | 0.00 | 0.00 | 0.00 | 0.624383E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.110269E+10 | 0.00 | 0.00 | 0.00 | 0.612402E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.952155E+09 | 0.00 | 0.00 | 0.00 | 0.496050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.902513E+09 | 0.00 | 0.00 | 0.00 | 0.349618E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.869715E+09 | 0.00 | 0.00 | 0.00 | 0.180158E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.892494E+09 | 0.00 | 0.00 | 0.00 | 0.386896E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114159E+11 | 0.00 | 0.00 | 0.00 | 0.416750E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.812747E+09 | 0.00 | 0.00 | 0.00 | 0.140177E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.110269E+10 | 0.00 | 0.00 | 0.00 | 0.624383E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.449354E+10 | 0.00 | 0.00 | 5542523.42 | 0.00 | 73766068.86 | 0.323902E+10 | 0.00 | 0.57 |
February | 0.165496E+10 | 0.154946E+09 | 0.00 | 9087477.01 | 0.00 | 3144117.60 | 0.227450E+10 | 0.00 | 0.57 |
March | 0.330009E+09 | 0.257065E+10 | 0.00 | 5935811.83 | 5140849.59 | 0.00 | 0.693325E+09 | 0.00 | 0.57 |
April | 14699077.20 | 0.782686E+10 | 0.00 | 465411.20 | 0.195675E+09 | 0.00 | 20025375.61 | 0.00 | 0.57 |
May | 66177.90 | 0.156255E+11 | 0.00 | 8690.83 | 0.194890E+09 | 0.00 | 637971.12 | 0.00 | 0.58 |
June | 0.00 | 0.201651E+11 | 0.00 | 0.00 | 0.214155E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
July | 0.00 | 0.246507E+11 | 0.00 | 0.00 | 0.188637E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
August | 0.00 | 0.245464E+11 | 0.00 | 0.00 | 0.293632E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
September | 0.00 | 0.185269E+11 | 0.00 | 0.00 | 0.437142E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
October | 91242288.01 | 0.703043E+10 | 0.00 | 1089074.57 | 0.123649E+09 | 0.00 | 66829059.90 | 0.00 | 0.57 |
November | 0.488020E+09 | 0.129251E+10 | 0.00 | 8942015.17 | 0.00 | 0.00 | 0.169290E+10 | 0.00 | 0.57 |
December | 0.295844E+10 | 5719068.41 | 0.00 | 9830983.07 | 0.00 | 6683031.31 | 0.398920E+10 | 0.00 | 0.57 |
Annual Sum or Average | 0.100310E+11 | 0.122396E+12 | 0.00 | 40901987.10 | 0.165292E+10 | 83593217.76 | 0.119764E+11 | 0.00 | 0.58 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 0.449354E+10 | 0.246507E+11 | 0.00 | 9830983.07 | 0.437142E+09 | 73766068.86 | 0.398920E+10 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.126229E+10 | 0.00 | 0.00 | 4175258.03 | 0.00 | 15252202.34 | 0.139497E+10 | 0.00 | 0.43 |
February | 0.472852E+09 | 82854083.58 | 0.00 | 5409713.03 | 50914.35 | 0.00 | 0.701651E+09 | 0.00 | 0.44 |
March | 93892683.34 | 0.119439E+10 | 0.00 | 2895093.99 | 18863932.47 | 0.00 | 0.163922E+09 | 0.00 | 0.46 |
April | 4253139.55 | 0.333189E+10 | 0.00 | 266536.01 | 0.130855E+09 | 0.00 | 3593471.15 | 0.00 | 0.47 |
May | 0.00 | 0.671522E+10 | 0.00 | 0.00 | 0.129306E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
June | 0.00 | 0.866824E+10 | 0.00 | 0.00 | 0.117866E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
July | 0.00 | 0.105774E+11 | 0.00 | 0.00 | 0.117217E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
August | 0.00 | 0.105632E+11 | 0.00 | 0.00 | 0.212817E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
September | 0.00 | 0.776071E+10 | 0.00 | 0.00 | 0.365293E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
October | 10751353.69 | 0.308998E+10 | 0.00 | 149501.65 | 0.126381E+09 | 0.00 | 3210853.05 | 0.00 | 0.46 |
November | 0.139310E+09 | 0.661710E+09 | 0.00 | 4491423.02 | 2395358.88 | 0.00 | 0.334952E+09 | 0.00 | 0.45 |
December | 0.863052E+09 | 3206526.95 | 0.00 | 6137767.01 | 0.00 | 761206.52 | 0.129488E+10 | 0.00 | 0.44 |
Annual Sum or Average | 0.284640E+10 | 0.526488E+11 | 0.00 | 23525292.75 | 0.122104E+10 | 16013408.86 | 0.389717E+10 | 0.00 | 0.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.126229E+10 | 0.105774E+11 | 0.00 | 6137767.01 | 0.365293E+09 | 15252202.34 | 0.139497E+10 | 0.00 | 0.49 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.182716E+10 | 17880.44 | 0.00 | 1837788.66 | 0.00 | 57189176.84 | 0.844950E+09 | 0.00 | 0.45 |
February | 0.822251E+09 | 83553596.07 | 0.00 | 2873463.55 | 340354.23 | 618659.61 | 0.527275E+09 | 0.00 | 0.45 |
March | 0.235762E+09 | 0.105185E+10 | 0.00 | 1787108.50 | 56121667.58 | 0.00 | 0.192863E+09 | 0.00 | 0.46 |
April | 12724565.34 | 0.292319E+10 | 0.00 | 238829.24 | 0.261993E+09 | 0.00 | 3820908.46 | 0.00 | 0.46 |
May | 1823381.55 | 0.574861E+10 | 0.00 | 50788.15 | 0.457889E+09 | 0.00 | 1674118.35 | 0.00 | 0.47 |
June | 25644.62 | 0.716575E+10 | 0.00 | 0.00 | 0.594011E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
July | 0.00 | 0.846807E+10 | 0.00 | 0.00 | 0.674316E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.862141E+10 | 0.00 | 0.00 | 0.690142E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 1262851.77 | 0.631439E+10 | 0.00 | 40424.23 | 0.573597E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
October | 77589230.93 | 0.263454E+10 | 0.00 | 592903.55 | 0.191274E+09 | 0.00 | 42034404.23 | 0.00 | 0.46 |
November | 0.396113E+09 | 0.622255E+09 | 0.00 | 2184255.34 | 11645317.96 | 0.00 | 0.328033E+09 | 0.00 | 0.46 |
December | 0.135594E+10 | 3496592.02 | 0.00 | 3372821.62 | 0.00 | 2211929.78 | 0.933855E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.473066E+10 | 0.436371E+11 | 0.00 | 12978382.85 | 0.351133E+10 | 60019766.23 | 0.287451E+10 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 17880.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.182716E+10 | 0.862141E+10 | 0.00 | 3372821.62 | 0.690142E+09 | 57189176.84 | 0.933855E+09 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.186322E+10 | 10893.17 | 0.00 | 1615871.97 | 0.00 | 77593553.78 | 0.764117E+09 | 0.00 | 0.45 |
February | 0.847591E+09 | 82574922.53 | 0.00 | 2767205.80 | 336874.73 | 2257655.71 | 0.497185E+09 | 0.00 | 0.45 |
March | 0.236567E+09 | 0.105128E+10 | 0.00 | 1778448.49 | 56105072.69 | 0.00 | 0.191714E+09 | 0.00 | 0.46 |
April | 13141173.25 | 0.292824E+10 | 0.00 | 249571.99 | 0.259652E+09 | 0.00 | 3761354.09 | 0.00 | 0.46 |
May | 1900814.67 | 0.576560E+10 | 0.00 | 54848.82 | 0.452805E+09 | 0.00 | 1677618.37 | 0.00 | 0.47 |
June | 1676.23 | 0.718850E+10 | 0.00 | 1493.48 | 0.589831E+09 | 0.00 | 1807.26 | 0.00 | 0.47 |
July | 0.00 | 0.851115E+10 | 0.00 | 0.00 | 0.661369E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.865652E+10 | 0.00 | 0.00 | 0.680931E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 777206.78 | 0.634844E+10 | 0.00 | 40223.90 | 0.559003E+09 | 0.00 | 495389.00 | 0.00 | 0.46 |
October | 78172526.49 | 0.264124E+10 | 0.00 | 610494.12 | 0.189693E+09 | 0.00 | 41822847.29 | 0.00 | 0.46 |
November | 0.401532E+09 | 0.621095E+09 | 0.00 | 2158884.99 | 11635931.07 | 0.00 | 0.322521E+09 | 0.00 | 0.46 |
December | 0.136569E+10 | 3387139.99 | 0.00 | 3195505.06 | 0.00 | 2894062.76 | 0.918443E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.480859E+10 | 0.437980E+11 | 0.00 | 12472548.62 | 0.346136E+10 | 82745272.24 | 0.274174E+10 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 10893.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.186322E+10 | 0.865652E+10 | 0.00 | 3195505.06 | 0.680931E+09 | 77593553.78 | 0.918443E+09 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.190428E+10 | 5668.02 | 0.00 | 1368725.21 | 0.00 | 94597385.63 | 0.678503E+09 | 0.00 | 0.45 |
February | 0.865353E+09 | 80727324.01 | 0.00 | 2570739.95 | 323778.34 | 4037236.08 | 0.474394E+09 | 0.00 | 0.45 |
March | 0.240918E+09 | 0.104315E+10 | 0.00 | 1687400.95 | 56291677.75 | 0.00 | 0.187803E+09 | 0.00 | 0.46 |
April | 12238323.85 | 0.291895E+10 | 0.00 | 230234.80 | 0.264545E+09 | 0.00 | 3823611.75 | 0.00 | 0.46 |
May | 1811833.50 | 0.574702E+10 | 0.00 | 49536.53 | 0.461071E+09 | 0.00 | 1678109.77 | 0.00 | 0.47 |
June | 12620.93 | 0.716202E+10 | 0.00 | 41.14 | 0.599568E+09 | 0.00 | 4057.24 | 0.00 | 0.47 |
July | 0.00 | 0.847027E+10 | 0.00 | 0.00 | 0.681916E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.862327E+10 | 0.00 | 0.00 | 0.686728E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 1252386.57 | 0.630301E+10 | 0.00 | 41108.21 | 0.580406E+09 | 0.00 | 6049.24 | 0.00 | 0.46 |
October | 77169318.87 | 0.262784E+10 | 0.00 | 586063.85 | 0.191363E+09 | 0.00 | 43042731.24 | 0.00 | 0.46 |
November | 0.409630E+09 | 0.615227E+09 | 0.00 | 2071091.97 | 11632739.57 | 0.00 | 0.315694E+09 | 0.00 | 0.46 |
December | 0.138199E+10 | 3261777.41 | 0.00 | 2932036.73 | 0.00 | 4378262.81 | 0.895717E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.489466E+10 | 0.435947E+11 | 0.00 | 11536979.36 | 0.353384E+10 | 0.103013E+09 | 0.260067E+10 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 5668.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.190428E+10 | 0.862327E+10 | 0.00 | 2932036.73 | 0.686728E+09 | 94597385.63 | 0.895717E+09 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.340084E+10 | 0.00 | 0.00 | 2462820.91 | 0.00 | 0.134355E+09 | 0.137545E+10 | 0.00 | 0.42 |
February | 0.126047E+10 | 0.100019E+09 | 0.00 | 5387260.99 | 211316.15 | 3652894.48 | 0.111464E+10 | 0.00 | 0.42 |
March | 0.296722E+09 | 0.196725E+10 | 0.00 | 3827644.80 | 47556916.79 | 0.00 | 0.321377E+09 | 0.00 | 0.43 |
April | 10460429.67 | 0.563167E+10 | 0.00 | 173974.78 | 0.334296E+09 | 0.00 | 5180923.54 | 0.00 | 0.42 |
May | 203193.64 | 0.113320E+11 | 0.00 | 27331.72 | 0.349482E+09 | 0.00 | 481639.42 | 0.00 | 0.43 |
June | 0.00 | 0.141927E+11 | 0.00 | 0.00 | 0.394335E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.164974E+11 | 0.00 | 0.00 | 0.563758E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.170947E+11 | 0.00 | 0.00 | 0.560762E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 1785.30 | 0.122825E+11 | 0.00 | 15374.03 | 0.711922E+09 | 0.00 | 13799.72 | 0.00 | 0.43 |
October | 85422776.64 | 0.507982E+10 | 0.00 | 681559.85 | 0.257549E+09 | 0.00 | 29428415.38 | 0.00 | 0.42 |
November | 0.440749E+09 | 0.105117E+10 | 0.00 | 4141339.98 | 17613695.94 | 0.00 | 0.630759E+09 | 0.00 | 0.42 |
December | 0.222302E+10 | 1795891.10 | 0.00 | 5357891.31 | 0.00 | 6996435.21 | 0.203172E+10 | 0.00 | 0.41 |
Annual Sum or Average | 0.771788E+10 | 0.852311E+11 | 0.00 | 22075198.36 | 0.323749E+10 | 0.145004E+09 | 0.550906E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.340084E+10 | 0.170947E+11 | 0.00 | 5387260.99 | 0.711922E+09 | 0.134355E+09 | 0.203172E+10 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.170489E+10 | 0.00 | 0.00 | 1182469.77 | 0.00 | 78015983.62 | 0.653369E+09 | 0.00 | 0.42 |
February | 0.634955E+09 | 51376413.98 | 0.00 | 2692295.11 | 105161.03 | 1845947.01 | 0.544854E+09 | 0.00 | 0.42 |
March | 0.149481E+09 | 0.988887E+09 | 0.00 | 1917457.15 | 23926113.79 | 0.00 | 0.156426E+09 | 0.00 | 0.43 |
April | 5861968.29 | 0.282943E+10 | 0.00 | 85683.63 | 0.168281E+09 | 0.00 | 1867327.10 | 0.00 | 0.42 |
May | 83290.77 | 0.566762E+10 | 0.00 | 8690.36 | 0.184800E+09 | 0.00 | 232689.79 | 0.00 | 0.43 |
June | 0.00 | 0.709622E+10 | 0.00 | 0.00 | 0.198688E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.822951E+10 | 0.00 | 0.00 | 0.284638E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.850814E+10 | 0.00 | 0.00 | 0.294017E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 28903.73 | 0.612410E+10 | 0.00 | 8291.08 | 0.359437E+09 | 0.00 | 41195.41 | 0.00 | 0.43 |
October | 42512774.73 | 0.255021E+10 | 0.00 | 340811.27 | 0.121640E+09 | 0.00 | 14629888.23 | 0.00 | 0.42 |
November | 0.219926E+09 | 0.528988E+09 | 0.00 | 2120726.06 | 8683346.00 | 0.00 | 0.311878E+09 | 0.00 | 0.42 |
December | 0.109737E+10 | 988247.92 | 0.00 | 2687898.51 | 0.00 | 3509414.38 | 0.102003E+10 | 0.00 | 0.41 |
Annual Sum or Average | 0.385510E+10 | 0.425755E+11 | 0.00 | 11044322.94 | 0.164422E+10 | 83371345.01 | 0.270332E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.170489E+10 | 0.850814E+10 | 0.00 | 2692295.11 | 0.359437E+09 | 78015983.62 | 0.102003E+10 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.172107E+10 | 0.00 | 0.00 | 1113231.45 | 0.00 | 81378769.98 | 0.624417E+09 | 0.00 | 0.42 |
February | 0.642592E+09 | 50880631.22 | 0.00 | 2618072.96 | 106078.18 | 1832480.68 | 0.536441E+09 | 0.00 | 0.42 |
March | 0.152112E+09 | 0.985775E+09 | 0.00 | 1893398.77 | 24049634.94 | 0.00 | 0.154145E+09 | 0.00 | 0.43 |
April | 6270802.88 | 0.282496E+10 | 0.00 | 84948.26 | 0.170871E+09 | 0.00 | 1429245.81 | 0.00 | 0.42 |
May | 53545.24 | 0.565932E+10 | 0.00 | 7711.14 | 0.188290E+09 | 0.00 | 263918.95 | 0.00 | 0.43 |
June | 0.00 | 0.708787E+10 | 0.00 | 0.00 | 0.200211E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.822287E+10 | 0.00 | 0.00 | 0.282825E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.849644E+10 | 0.00 | 0.00 | 0.296134E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 31005.15 | 0.610856E+10 | 0.00 | 8190.53 | 0.366573E+09 | 0.00 | 43594.86 | 0.00 | 0.43 |
October | 42375308.39 | 0.254456E+10 | 0.00 | 338426.44 | 0.122813E+09 | 0.00 | 14790358.85 | 0.00 | 0.42 |
November | 0.221601E+09 | 0.526870E+09 | 0.00 | 2091794.86 | 8693030.36 | 0.00 | 0.311223E+09 | 0.00 | 0.42 |
December | 0.111585E+10 | 957843.19 | 0.00 | 2595000.49 | 0.00 | 3500599.48 | 0.999508E+09 | 0.00 | 0.41 |
Annual Sum or Average | 0.390195E+10 | 0.425091E+11 | 0.00 | 10750774.91 | 0.166057E+10 | 86711850.14 | 0.264226E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.172107E+10 | 0.849644E+10 | 0.00 | 2618072.96 | 0.366573E+09 | 81378769.98 | 0.999508E+09 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.174387E+10 | 0.00 | 0.00 | 954754.39 | 0.00 | 0.108320E+09 | 0.547847E+09 | 0.00 | 0.42 |
February | 0.657752E+09 | 49596855.43 | 0.00 | 2423042.07 | 108220.77 | 4687303.74 | 0.512354E+09 | 0.00 | 0.42 |
March | 0.154264E+09 | 0.978168E+09 | 0.00 | 1818370.92 | 24509456.49 | 0.00 | 0.151547E+09 | 0.00 | 0.43 |
April | 6127423.61 | 0.282167E+10 | 0.00 | 82673.83 | 0.172963E+09 | 0.00 | 1483169.89 | 0.00 | 0.42 |
May | 39854.78 | 0.565911E+10 | 0.00 | 5953.13 | 0.189143E+09 | 0.00 | 260568.32 | 0.00 | 0.43 |
June | 0.00 | 0.708981E+10 | 0.00 | 0.00 | 0.202757E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.823256E+10 | 0.00 | 0.00 | 0.287071E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.851705E+10 | 0.00 | 0.00 | 0.292697E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 22744.88 | 0.612326E+10 | 0.00 | 8982.95 | 0.360786E+09 | 0.00 | 34290.90 | 0.00 | 0.43 |
October | 41762898.64 | 0.254257E+10 | 0.00 | 330655.27 | 0.123193E+09 | 0.00 | 15121532.46 | 0.00 | 0.42 |
November | 0.225725E+09 | 0.522561E+09 | 0.00 | 2017998.85 | 8708768.27 | 0.00 | 0.307963E+09 | 0.00 | 0.42 |
December | 0.116795E+10 | 880799.09 | 0.00 | 2350892.71 | 0.00 | 4623984.92 | 0.936306E+09 | 0.00 | 0.41 |
Annual Sum or Average | 0.399751E+10 | 0.425372E+11 | 0.00 | 9993324.11 | 0.166194E+10 | 0.117632E+09 | 0.247292E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.174387E+10 | 0.851705E+10 | 0.00 | 2423042.07 | 0.360786E+09 | 0.108320E+09 | 0.936306E+09 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.168127E+10 | 0.00 | 0.00 | 911812.52 | 0.00 | 0.164240E+09 | 0.516058E+09 | 0.00 | 0.42 |
February | 0.654290E+09 | 47947569.86 | 0.00 | 2424815.72 | 100933.91 | 13979015.07 | 0.476183E+09 | 0.00 | 0.42 |
March | 0.159683E+09 | 0.964827E+09 | 0.00 | 1858831.31 | 23222760.30 | 0.00 | 0.143018E+09 | 0.00 | 0.43 |
April | 4099748.18 | 0.282694E+10 | 0.00 | 83677.23 | 0.163918E+09 | 0.00 | 3556155.97 | 0.00 | 0.42 |
May | 467776.11 | 0.570626E+10 | 0.00 | 30641.91 | 0.148023E+09 | 0.00 | 152323.68 | 0.00 | 0.43 |
June | 235385.98 | 0.717026E+10 | 0.00 | 1471.85 | 0.179863E+09 | 0.00 | 431226.80 | 0.00 | 0.44 |
July | 0.00 | 0.839116E+10 | 0.00 | 0.00 | 0.234874E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.875983E+10 | 0.00 | 0.00 | 0.228995E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 56911.87 | 0.634160E+10 | 0.00 | 17308.59 | 0.281439E+09 | 0.00 | 65229.14 | 0.00 | 0.43 |
October | 38578405.12 | 0.258885E+10 | 0.00 | 314850.38 | 0.115033E+09 | 0.00 | 16508868.46 | 0.00 | 0.42 |
November | 0.230110E+09 | 0.521273E+09 | 0.00 | 2101599.18 | 8299812.74 | 0.00 | 0.296712E+09 | 0.00 | 0.42 |
December | 0.117966E+10 | 765816.00 | 0.00 | 2311651.18 | 0.00 | 10471930.69 | 0.877292E+09 | 0.00 | 0.41 |
Annual Sum or Average | 0.394845E+10 | 0.433197E+11 | 0.00 | 10056659.86 | 0.138377E+10 | 0.188691E+09 | 0.232998E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.168127E+10 | 0.875983E+10 | 0.00 | 2424815.72 | 0.281439E+09 | 0.164240E+09 | 0.877292E+09 | 0.00 | 0.44 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:41:11
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.148814E+12 | 0.147077E+11 | 0.00 | 0.824715E+11 | 0.133432E+11 |
February | 0.175244E+12 | 0.537038E+10 | 0.00 | 0.472021E+11 | 0.485215E+11 |
March | 0.247646E+12 | -0.793246E+10 | 0.00 | 0.347445E+10 | 0.125509E+12 |
April | 0.286500E+12 | -0.228709E+11 | 0.00 | -0.547435E+11 | 0.204434E+12 |
May | 0.310248E+12 | -0.417822E+11 | 0.00 | -0.112842E+12 | 0.302195E+12 |
June | 0.289769E+12 | -0.495539E+11 | 0.00 | -0.150714E+12 | 0.337469E+12 |
July | 0.237936E+12 | -0.609899E+11 | 0.00 | -0.177711E+12 | 0.368550E+12 |
August | 0.202469E+12 | -0.619958E+11 | 0.00 | -0.176218E+12 | 0.368535E+12 |
September | 0.211290E+12 | -0.470950E+11 | 0.00 | -0.133074E+12 | 0.299447E+12 |
October | 0.204029E+12 | -0.213328E+11 | 0.00 | -0.398104E+11 | 0.198914E+12 |
November | 0.168536E+12 | -0.416561E+10 | 0.00 | 0.287487E+11 | 0.106472E+12 |
December | 0.132731E+12 | 0.121969E+11 | 0.00 | 0.790970E+11 | 0.291184E+11 |
Annual Sum or Average | 0.261521E+13 | -0.285444E+12 | 0.00 | -0.604118E+12 | 0.240251E+13 |
Minimum of Months | 0.132731E+12 | -0.619958E+11 | 0.00 | -0.177711E+12 | 0.133432E+11 |
Maximum of Months | 0.310248E+12 | 0.147077E+11 | 0.00 | 0.824715E+11 | 0.368550E+12 |