Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:41
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940
Simulation Timestamp: 2023-10-16 08:41:06
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:06
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1524.08 | 729.12 | 729.12 |
Net Site Energy | 1524.08 | 729.12 | 729.12 |
Total Source Energy | 4826.77 | 2309.11 | 2309.11 |
Net Source Energy | 4826.77 | 2309.11 | 2309.11 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 656.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 441.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 100.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 139.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 57.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1524.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 656.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 441.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 100.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 139.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 57.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 656.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 441.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 100.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 139.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 57.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 259.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 408.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 729.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 259.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 408.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 729.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1524.083 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1524.083 | 100.00 |
Total On-Site and Utility Electric Sources | 1524.083 | 100.00 |
Total Electricity End Uses | 1524.083 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 12.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1050.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:06
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:41 |
RunPeriod | RUNPERIOD 1 |
Weather File | Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Latitude [deg] | 25.25 |
Longitude [deg] | 55.33 |
Elevation [m] | 5.00 |
Time Zone | 4.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.77 | 20.77 | 17.8770 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.38 | 10.38 | 19.3382 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 17.3739 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 17.3739 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 17.3739 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.72 | 20.72 | 13.1675 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.3365 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.3365 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.3365 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.36 | 10.36 | 13.3365 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 15.5746 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 15.5746 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 17.8770 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 19.3382 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 17.3739 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 17.3739 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 17.3739 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 13.1675 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 13.3365 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 13.3365 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 13.3365 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 13.3365 | 6.19 | 4.3000 | |
Total | 2090.32 | 15.5746 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 15.5746 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 15.5746 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:06
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-15:50 | - | - | - | - | - | - | - | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 106233.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 27522.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 14787.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3318.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 159951.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 106233.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 27522.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 14787.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 3318.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:06
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2079.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1398.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 316.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 407.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 442.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 182.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4826.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 994.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 668.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 151.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 211.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 87.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2309.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 994.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 668.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 151.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 211.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 87.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2309.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:06
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 2.96 |
SMSTORE1 DIRECT AIR | 1.49 |
SMSTORE2 DIRECT AIR | 1.48 |
SMSTORE3 DIRECT AIR | 1.49 |
SMSTORE4 DIRECT AIR | 1.49 |
LGSTORE2 DIRECT AIR | 2.73 |
SMSTORE5 DIRECT AIR | 1.45 |
SMSTORE6 DIRECT AIR | 1.44 |
SMSTORE7 DIRECT AIR | 1.45 |
SMSTORE8 DIRECT AIR | 1.66 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.96 | 2.96 | 2.96 | 2.96 | 2.96 | 2.96 | 1.00 | 1.00 | 2.96 |
PSZ-AC_2:2 | 1.49 | 1.49 | 1.49 | 1.49 | 1.49 | 1.49 | 1.00 | 1.00 | 1.49 |
PSZ-AC_3:3 | 1.48 | 1.48 | 1.48 | 1.48 | 1.48 | 1.48 | 1.00 | 1.000000 | 1.48 |
PSZ-AC_4:4 | 1.49 | 1.49 | 1.49 | 1.49 | 1.49 | 1.49 | 1.00 | 1.00 | 1.49 |
PSZ-AC_5:5 | 1.49 | 1.49 | 1.49 | 1.49 | 1.49 | 1.49 | 1.00 | 1.00 | 1.49 |
PSZ-AC_6:6 | 2.73 | 2.73 | 2.73 | 2.73 | 2.73 | 2.73 | 1.00 | 1.00 | 2.73 |
PSZ-AC_7:7 | 1.45 | 1.45 | 1.45 | 1.45 | 1.45 | 1.45 | 1.00 | 1.00 | 1.45 |
PSZ-AC_8:8 | 1.44 | 1.44 | 1.44 | 1.44 | 1.44 | 1.44 | 1.00 | 1.00 | 1.44 |
PSZ-AC_9:9 | 1.45 | 1.45 | 1.45 | 1.45 | 1.45 | 1.45 | 1.00 | 1.00 | 1.45 |
PSZ-AC_10:10 | 1.66 | 1.66 | 1.66 | 1.66 | 1.66 | 1.66 | 1.00 | 1.000000 | 1.66 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.96 | 0.411479 |
PSZ-AC_2:2_OA_CONTROLLER | 1.49 | 0.205739 |
PSZ-AC_3:3_OA_CONTROLLER | 1.48 | 0.205739 |
PSZ-AC_4:4_OA_CONTROLLER | 1.49 | 0.205739 |
PSZ-AC_5:5_OA_CONTROLLER | 1.49 | 0.205739 |
PSZ-AC_6:6_OA_CONTROLLER | 2.73 | 0.411479 |
PSZ-AC_7:7_OA_CONTROLLER | 1.45 | 0.205739 |
PSZ-AC_8:8_OA_CONTROLLER | 1.44 | 0.205739 |
PSZ-AC_9:9_OA_CONTROLLER | 1.45 | 0.205739 |
PSZ-AC_10:10_OA_CONTROLLER | 1.66 | 0.205739 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.96 | 3162.58 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.49 | 1595.77 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.48 | 1588.79 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.49 | 1592.06 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.49 | 1589.05 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 2.73 | 2922.91 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 1.45 | 1546.96 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 1.44 | 1541.79 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 1.45 | 1548.20 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.66 | 1779.79 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.96 | 2.96 | 2.96 | 1.95 | 73163.28 | 72888.52 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.49 | 1.49 | 1.49 | 0.984264 | 36952.12 | 36162.77 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.48 | 1.48 | 1.48 | 0.979959 | 36827.09 | 36013.73 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.49 | 1.49 | 1.49 | 0.981975 | 36886.44 | 36083.49 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.49 | 1.49 | 1.49 | 0.980120 | 36832.27 | 36019.31 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 2.73 | 2.73 | 2.73 | 1.80 | 67831.39 | 67718.69 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 1.45 | 1.45 | 1.45 | 0.954158 | 35900.01 | 35632.15 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 1.44 | 1.44 | 1.44 | 0.950968 | 35779.98 | 35520.11 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 1.45 | 1.45 | 1.45 | 0.954925 | 35928.90 | 35682.06 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.66 | 1.66 | 1.66 | 1.10 | 40144.92 | 40720.54 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 2.96 | 1.48 | 1.97 | 73163.28 | 36581.64 | 0.702850 | 0.702850 |
PSZ-AC_2:2 COOLING COIL | 1.49 | 0.745655 | 0.994207 | 36952.12 | 18476.06 | 0.702620 | 0.702620 |
PSZ-AC_3:3 COOLING COIL | 1.48 | 0.742393 | 0.989860 | 36827.09 | 18413.54 | 0.701370 | 0.701370 |
PSZ-AC_4:4 COOLING COIL | 1.49 | 0.743920 | 0.991893 | 36886.44 | 18443.22 | 0.701480 | 0.701480 |
PSZ-AC_5:5 COOLING COIL | 1.49 | 0.742515 | 0.990020 | 36832.27 | 18416.13 | 0.701380 | 0.701380 |
PSZ-AC_6:6 COOLING COIL | 2.73 | 1.37 | 1.82 | 67831.39 | 33915.69 | 0.701080 | 0.701080 |
PSZ-AC_7:7 COOLING COIL | 1.45 | 0.722847 | 0.963793 | 35900.01 | 17950.01 | 0.701080 | 0.701080 |
PSZ-AC_8:8 COOLING COIL | 1.44 | 0.720430 | 0.960573 | 35779.98 | 17889.99 | 0.701080 | 0.701080 |
PSZ-AC_9:9 COOLING COIL | 1.45 | 0.723428 | 0.964573 | 35928.90 | 17964.45 | 0.701080 | 0.701080 |
PSZ-AC_10:10 COOLING COIL | 1.66 | 0.831640 | 1.11 | 40144.92 | 20072.46 | 0.710150 | 0.710150 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 72888.52 |
PSZ-AC_2:2 HEATING COIL | 36162.77 |
PSZ-AC_3:3 HEATING COIL | 36013.73 |
PSZ-AC_4:4 HEATING COIL | 36083.49 |
PSZ-AC_5:5 HEATING COIL | 36019.31 |
PSZ-AC_6:6 HEATING COIL | 67718.69 |
PSZ-AC_7:7 HEATING COIL | 35632.15 |
PSZ-AC_8:8 HEATING COIL | 35520.11 |
PSZ-AC_9:9 HEATING COIL | 35682.06 |
PSZ-AC_10:10 HEATING COIL | 40720.54 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:06
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:06
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:06
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 29.50 | 25.50 | 21.10 | 19.20 | 20.80 | 23.10 | 26.50 | 31.40 | 33.00 | 35.10 | 35.30 | 32.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Dubai Intl AP - ARE IWEC2 WMO#=411940 | 25.25 | 55.33 | 4.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.75 | 16.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.74 | 20.77 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.66 | 10.38 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.41 | 20.72 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.12 | 10.36 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 17.877 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.177 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 19.338 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 23.638 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 17.374 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.674 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 17.374 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.674 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 17.374 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.674 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 13.168 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.468 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 13.336 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.636 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 13.336 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.636 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 13.336 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.636 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 13.336 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.636 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 4596.695 | 13.194 | 81.718 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4596.695 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 1631.408 | 4.683 | 29.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1631.408 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 2327.780 | 13.363 | 82.767 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2327.780 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1040.795 | 5.975 | 37.007 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1040.795 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 2323.122 | 13.336 | 82.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2323.122 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 703.295 | 4.037 | 25.007 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 703.295 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 2323.122 | 13.336 | 82.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2323.122 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 703.295 | 4.037 | 25.007 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 703.295 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 2323.122 | 13.336 | 82.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2323.122 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 703.295 | 4.037 | 25.007 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 703.295 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 4587.379 | 13.168 | 81.553 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4587.379 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 2323.122 | 13.336 | 82.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2323.122 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 2323.122 | 13.336 | 82.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2323.122 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 2323.122 | 13.336 | 82.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2323.122 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 2323.122 | 13.336 | 82.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2323.122 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.7544 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1995 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2888 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.092 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.937 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.386 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
19 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
20 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
21 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
22 | 7 | -0.31526305E-12 | 0.65421067E-14 | -0.96995935E-13 | 0.16372101E-15 |
23 | 6 | 0.28934589E-07 | 0.21281465E-09 | 0.66261080E-08 | -0.13661131E-12 |
24 | 5 | -0.19144321E-03 | 0.18179002E-05 | -0.98452505E-04 | 0.65494719E-08 |
25 | 4 | 0.29370911 | 0.88327295E-03 | 0.10024532 | -0.33791493E-04 |
26 | 3 | -7.2972687 | 0.27321832E-01 | -2.3480939 | 0.29160644E-01 |
27 | 2 | 40.973187 | 0.96992104E-01 | 15.302757 | -0.33447687 |
28 | 1 | -80.623988 | 0.43709902E-01 | -29.175449 | 1.0802857 |
29 | 0 | 46.824338 | 0.87814252E-03 | 16.290426 | |
30 | 7 | -0.21163652E-08 | -0.68723841E-15 | 0.43910983E-14 | -0.57684426E-16 |
31 | 6 | 0.56109385E-05 | 0.38186281E-08 | 0.31898696E-02 | -0.26759299E-04 |
32 | 5 | -0.40164657E-03 | 0.22608617E-05 | -0.22372456 | 0.19561502E-02 |
33 | 4 | 0.92272104E-02 | 0.10289840E-03 | 4.8295456 | -0.45264980E-01 |
34 | 3 | -0.80993241E-01 | 0.81813938E-03 | -38.021416 | 0.39865375 |
35 | 2 | 0.28754352 | 0.13608947E-02 | 116.48395 | -1.4179393 |
36 | 1 | -0.41499682 | 0.41453381E-03 | -143.90731 | 2.0490399 |
37 | 0 | 0.20232414 | 0.10048102E-04 | 60.838472 | |
38 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
39 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
40 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
41 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
42 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
43 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
44 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
45 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
46 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
47 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
48 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
49 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
50 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
51 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
52 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
53 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
54 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
55 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
56 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
57 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
58 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
59 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
60 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
61 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
62 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
63 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
64 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
65 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
66 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
67 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
68 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
69 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
70 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
71 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
72 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
73 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
74 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
75 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
76 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
77 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
78 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
79 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
80 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
81 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
82 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
83 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
84 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
85 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
86 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
87 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
88 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
89 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
90 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
91 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
92 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
93 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
94 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479936E-14 | -0.41635794E-16 |
95 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
96 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
97 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
98 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
99 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
100 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
101 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
102 | 7 | -0.14484255E-08 | -0.22640907E-15 | 0.11860658E-13 | -0.17473455E-15 |
103 | 6 | 0.80640390E-05 | 0.55493782E-08 | 0.31828288E-02 | -0.26700235E-04 |
104 | 5 | -0.58275339E-03 | 0.32892043E-05 | -0.22332434 | 0.19526176E-02 |
105 | 4 | 0.13421983E-01 | 0.14977251E-03 | 4.8228790 | -0.45200897E-01 |
106 | 3 | -0.11791368 | 0.11914425E-02 | -37.983753 | 0.39823745 |
107 | 2 | 0.41875064 | 0.19825898E-02 | 116.41064 | -1.4169588 |
108 | 1 | -0.60444169 | 0.60433957E-03 | -143.86415 | 2.0483306 |
109 | 0 | 0.29470347 | 0.14596444E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 35 | 1 | VerySmooth | 2.861 | 2.861 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 1.93170E-002 | 0.16139 | 0.61074 | 0.61074 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10774 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 0.157 | 4.517E-004 | 2.488E-004 | 0.314 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.389 | 1.116E-003 | 6.149E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.648E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 8.993E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.389 | 1.116E-003 | 7.565E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 0.112 | 6.453E-004 | 2.994E-004 | 0.448 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 5.921E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 33447.80091 | 40137.36109 | 2.46296 | 2.95555 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 42.80000 | 1.07818E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 8842.69304 | 10611.23164 | 0.36637 | 0.43965 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 12.70000 | 9.15345E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 16877.06200 | 20252.47440 | 1.24276 | 1.49131 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 42.80000 | 1.07818E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 4231.62970 | 5077.95565 | 0.18253 | 0.21903 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 12.70000 | 9.15345E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 16803.26046 | 20163.91255 | 1.23732 | 1.48479 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 42.71917 | 1.07817E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 4267.66093 | 5121.19311 | 0.18408 | 0.22090 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 12.70000 | 9.15345E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 16837.81832 | 20205.38198 | 1.23987 | 1.48784 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 42.71917 | 1.07817E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 4310.85479 | 5173.02574 | 0.18595 | 0.22314 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 12.70000 | 9.15345E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 16806.02554 | 20167.23064 | 1.23753 | 1.48503 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 42.71917 | 1.07817E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 4432.45036 | 5318.94043 | 0.19119 | 0.22943 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 12.70000 | 9.15345E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 30913.39039 | 37096.06847 | 2.27631 | 2.73157 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 42.71917 | 1.07817E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 9120.68490 | 10944.82188 | 0.37686 | 0.45224 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 12.70000 | 9.15345E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 16360.89212 | 19633.07054 | 1.20474 | 1.44569 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 42.63833 | 1.07815E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 4778.17080 | 5733.80496 | 0.19833 | 0.23800 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 12.70000 | 9.15345E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 16306.19137 | 19567.42964 | 1.20072 | 1.44086 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 42.63833 | 1.07815E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 4785.62839 | 5742.75407 | 0.19864 | 0.23837 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 12.70000 | 9.15345E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 16374.06007 | 19648.87208 | 1.20571 | 1.44686 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 42.63833 | 1.07815E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 5046.10111 | 6055.32133 | 0.20928 | 0.25113 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 12.70000 | 9.15345E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 18824.40186 | 22589.28224 | 1.38607 | 1.66328 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 42.31500 | 1.07810E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 5667.60510 | 6801.12613 | 0.23618 | 0.28341 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 12.70000 | 9.15345E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 49038.08 | 2.95555 | 2.95555 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 14242.77 | 0.43965 | 0.43965 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 24700.49 | 1.49131 | 1.49131 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 7096.80 | 0.21903 | 0.21903 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 24611.28 | 1.48479 | 1.48479 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 7139.41 | 0.22090 | 0.22090 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 24651.46 | 1.48784 | 1.48784 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 7190.48 | 0.22314 | 0.22314 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 24613.57 | 1.48503 | 1.48503 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 7334.27 | 0.22943 | 0.22943 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 46024.57 | 2.73157 | 2.73157 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 14537.10 | 0.45224 | 0.45224 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 24081.68 | 1.44569 | 1.44569 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 7543.34 | 0.23800 | 0.23800 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 24016.64 | 1.44086 | 1.44086 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 7551.97 | 0.23837 | 0.23837 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 24095.15 | 1.44686 | 1.44686 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 7849.70 | 0.25113 | 0.25113 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 26895.97 | 1.66328 | 1.66328 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 8601.07 | 0.28341 | 0.28341 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.95555 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.49131 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.48479 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.48784 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.48503 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.73157 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.44569 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.44086 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.44686 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.66328 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.95555 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.95555 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.95555 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.95555 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.95555 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.95555 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.49131 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.49131 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.49131 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.49131 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.49131 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.49131 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.48479 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.48479 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.48479 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.48479 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.48479 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.48479 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.48784 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.48784 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.48784 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.48784 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.48784 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.48784 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.48503 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.48503 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.48503 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.48503 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.48503 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.48503 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.73157 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.73157 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.73157 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.73157 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.73157 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 2.73157 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.44569 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.44569 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.44569 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.44569 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.44569 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 1.44569 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 1.00000 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.44086 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.44086 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.44086 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.44086 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.44086 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 1.44086 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 1.00000 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.44686 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.44686 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.44686 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.44686 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.44686 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 1.44686 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 1.00000 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.66328 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.66328 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.66328 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.66328 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.66328 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.66328 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.95555 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.49131 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.48479 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.48784 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.48503 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 2.73157 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 1.44569 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 1.44086 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 1.44686 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.66328 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.95555 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.95555 |
104 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 3162.57931 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.95555 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.95555 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.95555 |
108 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.95066 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.95555 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.47778 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.97037 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 73163.28000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 36581.64000 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70285 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70285 |
116 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 73163.28000 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 72888.52490 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
120 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 72888.52490 |
121 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.49131 |
122 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
123 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.49131 |
124 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1595.77129 |
125 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.49131 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.49131 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.49131 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.98426 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.49131 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.74565 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.99421 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 36952.12000 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 18476.06000 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70262 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70262 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 36952.12000 |
137 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 36162.76611 |
138 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
139 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
140 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 36162.76611 |
141 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.48479 |
142 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
143 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.48479 |
144 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1588.79210 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.48479 |
146 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.48479 |
147 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.48479 |
148 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.97996 |
149 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.48479 |
150 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.74239 |
151 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.98986 |
152 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 36827.09000 |
153 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 18413.54500 |
154 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70137 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70137 |
156 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 36827.09000 |
157 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 36013.73466 |
158 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
159 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
160 | Coil:Heating:Fuel | PSZ-AC_3:3 HEATING COIL | Design Size Nominal Capacity [W] | 36013.73466 |
161 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.48784 |
162 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
163 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.48784 |
164 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1592.05959 |
165 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.48784 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.48784 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.48784 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.98197 |
169 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.48784 |
170 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.74392 |
171 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.99189 |
172 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 36886.44000 |
173 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 18443.22000 |
174 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70148 |
175 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70148 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 36886.44000 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 36083.49486 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
179 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
180 | Coil:Heating:Fuel | PSZ-AC_4:4 HEATING COIL | Design Size Nominal Capacity [W] | 36083.49486 |
181 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.48503 |
182 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
183 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.48503 |
184 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1589.05320 |
185 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.48503 |
186 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.48503 |
187 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.48503 |
188 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.98012 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.48503 |
190 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.74252 |
191 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.99002 |
192 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 36832.27000 |
193 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 18416.13500 |
194 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70138 |
195 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70138 |
196 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 36832.27000 |
197 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 36019.31092 |
198 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
200 | Coil:Heating:Fuel | PSZ-AC_5:5 HEATING COIL | Design Size Nominal Capacity [W] | 36019.31092 |
201 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.73157 |
202 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
203 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.73157 |
204 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2922.90929 |
205 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.73157 |
206 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.73157 |
207 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.73157 |
208 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.80284 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.73157 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.36579 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.82105 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 67831.39000 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 33915.69500 |
214 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
215 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 67831.39000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 67718.68590 |
218 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
219 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
220 | Coil:Heating:Fuel | PSZ-AC_6:6 HEATING COIL | Design Size Nominal Capacity [W] | 67718.68590 |
221 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.44569 |
222 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
223 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.44569 |
224 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1546.96025 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.44569 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.44569 |
227 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.44569 |
228 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.95416 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.44569 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.72285 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.96379 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 35900.01000 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 17950.00500 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
236 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 35900.01000 |
237 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 35632.15267 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
240 | Coil:Heating:Fuel | PSZ-AC_7:7 HEATING COIL | Design Size Nominal Capacity [W] | 35632.15267 |
241 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.44086 |
242 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
243 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.44086 |
244 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1541.78818 |
245 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.44086 |
246 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.44086 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.44086 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.95097 |
249 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.44086 |
250 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.72043 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.96057 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 35779.98000 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 17889.99000 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
256 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 35779.98000 |
257 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 35520.11044 |
258 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
259 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
260 | Coil:Heating:Fuel | PSZ-AC_8:8 HEATING COIL | Design Size Nominal Capacity [W] | 35520.11044 |
261 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.44686 |
262 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
263 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.44686 |
264 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1548.20497 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.44686 |
266 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.44686 |
267 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.44686 |
268 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.95493 |
269 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.44686 |
270 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.72343 |
271 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.96457 |
272 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 35928.90000 |
273 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 17964.45000 |
274 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 35928.90000 |
277 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 35682.05604 |
278 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
279 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
280 | Coil:Heating:Fuel | PSZ-AC_9:9 HEATING COIL | Design Size Nominal Capacity [W] | 35682.05604 |
281 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.66328 |
282 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
283 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.66328 |
284 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1779.78735 |
285 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.66328 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.66328 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.66328 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.09776 |
289 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.66328 |
290 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.83164 |
291 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.10885 |
292 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 40144.92000 |
293 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 20072.46000 |
294 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.71015 |
295 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.71015 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 40144.92000 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 40720.53970 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
299 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
300 | Coil:Heating:Fuel | PSZ-AC_10:10 HEATING COIL | Design Size Nominal Capacity [W] | 40720.53970 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 70831.8 | 10.85 | 10.85 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 35775.7 | 11.94 | 11.94 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | 35655.7 | 11.95 | 11.95 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | 35712.7 | 11.95 | 11.95 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | 35660.7 | 11.95 | 11.95 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | 65676.4 | 11.77 | 11.77 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | 34759.5 | 11.95 | 11.95 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | 34643.3 | 11.95 | 11.95 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | 34787.5 | 11.95 | 11.95 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | 38833.5 | 11.72 | 11.72 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 58.18 | 78.94 | 58.18 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.199 | 0.190 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 29.09 | 39.47 | 29.09 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 58.22 | 78.94 | 58.22 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.289 | 0.270 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 2.9777011220E-002 | 6.7120576014E-002 | Pass | Pass | 3.4033526090E-002 | 9.7481111292E-002 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 2.7595329370E-002 | 6.9678528442E-002 | Pass | Pass | 3.3597132035E-002 | 9.4576256689E-002 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 3.7389300330E-002 | 7.6192383462E-002 | Pass | Pass | 0.1367205352 | 1.1842302960 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 3.7833298902E-002 | 7.4537812339E-002 | Pass | Pass | 0.1471207847 | 1.2786912820 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 3.8238076034E-002 | 7.2124502123E-002 | Pass | Pass | 0.1628586457 | 1.4186198216 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 3.3091206654E-002 | 5.2181325283E-002 | Pass | Pass | 0.1436642741 | 1.2496358378 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 3.2622593791E-002 | 5.0281561043E-002 | Pass | Pass | 0.1972279567 | 1.7677975626 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 3.2850806328E-002 | 4.9780574565E-002 | Pass | Pass | 0.2045195737 | 1.8357029253 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 3.4057991895E-002 | 4.9200623049E-002 | Pass | Pass | 0.2608890362 | 2.2794771591 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 3.9853611368E-002 | 5.0635880565E-002 | Pass | Pass | 5.2265925700 | 61.6909257840 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:06
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2271.32 | -416.9 | 0.00 | -969.8 | 3024.64 | 3909.34 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:06
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 12.70 | 0.00 | 12.70 | Wetbulb [C] | 2.00 | 170.00 |
DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 42.80 | 9.70 | 23.80 | Wetbulb [C] | 5.00 | 80.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.40 | 26 | |||
Feb | 9.60 | 38 | |||
Mar | 3.60 | 37 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 1.20 | 13 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 18.00 | 37 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:06
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 78.94 | 58.18 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.193 | 0.199 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 29.09 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 78.94 | 58.22 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.276 | 0.289 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.861 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.861 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.861 | 0.251 | 0.251 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 124.40 | 2.861 | 0.251 | 0.251 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 124.40 | 2.861 | 0.251 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:06
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:06
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 13.1942 | 348.39 | 4596.69 | LightsWired | LTG_SCH_BASE_LPD1 | 84.21 | 168.00 | 84.19 | 0.0000 | Y | 72.65 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 4.6828 | 348.39 | 1631.41 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 168.00 | 97.48 | 0.0000 | Y | 29.85 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 13.3632 | 174.19 | 2327.78 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 85.70 | 168.00 | 85.69 | 0.0000 | Y | 37.44 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 5.9749 | 174.19 | 1040.80 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 168.00 | 97.48 | 0.0000 | Y | 19.04 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 13.3365 | 174.19 | 2323.12 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 29.75 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 4.0374 | 174.19 | 703.30 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 10.29 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 13.3365 | 174.19 | 2323.12 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 29.75 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 4.0374 | 174.19 | 703.30 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 10.29 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 13.3365 | 174.19 | 2323.12 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 29.75 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 4.0374 | 174.19 | 703.30 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 10.29 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 13.1675 | 348.39 | 4587.38 | LightsWired | LTG_SCH_BASE_LPD2 | 62.11 | 168.00 | 61.60 | 0.0000 | Y | 53.05 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 13.3365 | 174.19 | 2323.12 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 27.34 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 13.3365 | 174.19 | 2323.12 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 27.34 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 13.3365 | 174.19 | 2323.12 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 27.34 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 13.3365 | 174.19 | 2323.12 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 27.34 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 7.7873 | 4180.64 | 32555.80 | 441.52 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 345.19 | AstronomicalClock | - | 41.85 | 41.85 | 2.71 | |
EXTERIOR_LIGHTS_B | 7274.32 | AstronomicalClock | - | 83.85 | 71.25 | 97.29 | |
Exterior Lighting Total | 7619.51 | 100.00 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:06
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 73163.28 | 51422.81 | 21740.47 | 0.70 | 3.40 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 36952.12 | 25963.30 | 10988.82 | 0.70 | 3.80 | |||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 36827.09 | 25829.42 | 10997.67 | 0.70 | 3.80 | |||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 36886.44 | 25875.10 | 11011.34 | 0.70 | 3.80 | |||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 36832.27 | 25833.42 | 10998.85 | 0.70 | 3.80 | |||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 67831.39 | 47555.23 | 20276.16 | 0.70 | 3.73 | |||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 35900.01 | 25168.78 | 10731.23 | 0.70 | 3.80 | |||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 35779.98 | 25084.63 | 10695.35 | 0.70 | 3.80 | |||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 35928.90 | 25189.03 | 10739.87 | 0.70 | 3.80 | |||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 40144.92 | 28508.91 | 11636.01 | 0.71 | 3.73 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 70831.8 | 10.85 | 10.85 | ||||
PSZ-AC_2:2 COOLING COIL | 35775.7 | 11.94 | 11.94 | ||||
PSZ-AC_3:3 COOLING COIL | 35655.7 | 11.95 | 11.95 | ||||
PSZ-AC_4:4 COOLING COIL | 35712.7 | 11.95 | 11.95 | ||||
PSZ-AC_5:5 COOLING COIL | 35660.7 | 11.95 | 11.95 | ||||
PSZ-AC_6:6 COOLING COIL | 65676.4 | 11.77 | 11.77 | ||||
PSZ-AC_7:7 COOLING COIL | 34759.5 | 11.95 | 11.95 | ||||
PSZ-AC_8:8 COOLING COIL | 34643.3 | 11.95 | 11.95 | ||||
PSZ-AC_9:9 COOLING COIL | 34787.5 | 11.95 | 11.95 | ||||
PSZ-AC_10:10 COOLING COIL | 38833.5 | 11.72 | 11.72 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 72888.52 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 36162.77 | 0.80 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | 36013.73 | 0.80 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | 36083.49 | 0.80 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | 36019.31 | 0.80 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | 67718.69 | 0.80 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | 35632.15 | 0.80 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | 35520.11 | 0.80 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | 35682.06 | 0.80 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | 40720.54 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.96 | 3162.58 | 1070.05 | 1.00 | 1.27 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.49 | 1595.77 | 1070.05 | 1.00 | 1.36 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.48 | 1588.79 | 1070.05 | 1.00 | 1.36 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.49 | 1592.06 | 1070.05 | 1.00 | 1.36 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.49 | 1589.05 | 1070.05 | 1.00 | 1.36 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.73 | 2922.91 | 1070.05 | 1.00 | 1.27 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.45 | 1546.96 | 1070.05 | 1.00 | 1.37 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.44 | 1541.79 | 1070.05 | 1.00 | 1.37 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.45 | 1548.20 | 1070.05 | 1.00 | 1.37 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.66 | 1779.79 | 1070.05 | 1.00 | 1.34 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:06
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 33447.80 | 40137.36 | 115.21 | 2.463 | 2.956 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 23.89 | 23.89 | 0.00785 | 42.80 | 0.01078 | 0.411 | 0.00 |
SMSTORE1 | 16877.06 | 20252.47 | 116.26 | 1.243 | 1.491 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 23.89 | 23.89 | 0.00787 | 42.80 | 0.01078 | 0.206 | 0.00 |
SMSTORE2 | 16803.26 | 20163.91 | 115.76 | 1.237 | 1.485 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.89 | 0.00788 | 42.72 | 0.01078 | 0.206 | 0.00 |
SMSTORE3 | 16837.82 | 20205.38 | 115.99 | 1.240 | 1.488 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.89 | 0.00788 | 42.72 | 0.01078 | 0.206 | 0.00 |
SMSTORE4 | 16806.03 | 20167.23 | 115.78 | 1.238 | 1.485 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.89 | 0.00788 | 42.72 | 0.01078 | 0.206 | 0.00 |
LGSTORE2 | 30913.39 | 37096.07 | 106.48 | 2.276 | 2.732 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.89 | 0.00789 | 42.72 | 0.01078 | 0.411 | 0.00 |
SMSTORE5 | 16360.89 | 19633.07 | 112.71 | 1.205 | 1.446 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 23.89 | 23.89 | 0.00790 | 42.64 | 0.01078 | 0.206 | 0.00 |
SMSTORE6 | 16306.19 | 19567.43 | 112.33 | 1.201 | 1.441 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 23.89 | 23.89 | 0.00790 | 42.64 | 0.01078 | 0.206 | 0.00 |
SMSTORE7 | 16374.06 | 19648.87 | 112.80 | 1.206 | 1.447 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 23.89 | 23.89 | 0.00790 | 42.64 | 0.01078 | 0.206 | 0.00 |
SMSTORE8 | 18824.40 | 22589.28 | 129.68 | 1.386 | 1.663 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 23.89 | 23.89 | 0.00783 | 42.31 | 0.01078 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 8842.69 | 10611.23 | 30.46 | 0.366 | 0.440 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 21.11 | 21.11 | 0.00837 | 12.70 | 0.00915 | 0.411 | 0.00 |
SMSTORE1 | 4231.63 | 5077.96 | 29.15 | 0.183 | 0.219 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00855 | 12.70 | 0.00915 | 0.206 | 0.00 |
SMSTORE2 | 4267.66 | 5121.19 | 29.40 | 0.184 | 0.221 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00855 | 12.70 | 0.00915 | 0.206 | 0.00 |
SMSTORE3 | 4310.85 | 5173.03 | 29.70 | 0.186 | 0.223 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00855 | 12.70 | 0.00915 | 0.206 | 0.00 |
SMSTORE4 | 4432.45 | 5318.94 | 30.53 | 0.191 | 0.229 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00854 | 12.70 | 0.00915 | 0.206 | 0.00 |
LGSTORE2 | 9120.68 | 10944.82 | 31.42 | 0.377 | 0.452 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 21.11 | 21.11 | 0.00841 | 12.70 | 0.00915 | 0.411 | 0.00 |
SMSTORE5 | 4778.17 | 5733.80 | 32.92 | 0.198 | 0.238 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 21.11 | 21.11 | 0.00841 | 12.70 | 0.00915 | 0.206 | 0.00 |
SMSTORE6 | 4785.63 | 5742.75 | 32.97 | 0.199 | 0.238 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 21.11 | 21.11 | 0.00841 | 12.70 | 0.00915 | 0.206 | 0.00 |
SMSTORE7 | 5046.10 | 6055.32 | 34.76 | 0.209 | 0.251 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 21.11 | 21.11 | 0.00839 | 12.70 | 0.00915 | 0.206 | 0.00 |
SMSTORE8 | 5667.61 | 6801.13 | 39.04 | 0.236 | 0.283 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 21.11 | 21.11 | 0.00845 | 12.70 | 0.00915 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.96 | 2.96 | 0.44 | 0.44 | 2.9556 | 2.9556 | 2.9556 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.49 | 1.49 | 0.22 | 0.22 | 1.4913 | 1.4913 | 1.4913 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 1.48 | 1.48 | 0.22 | 0.22 | 1.4848 | 1.4848 | 1.4848 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 1.49 | 1.49 | 0.22 | 0.22 | 1.4878 | 1.4878 | 1.4878 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.49 | 1.49 | 0.23 | 0.23 | 1.4850 | 1.4850 | 1.4850 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 2.73 | 2.73 | 0.45 | 0.45 | 2.7316 | 2.7316 | 2.7316 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 1.45 | 1.45 | 0.24 | 0.24 | 1.4457 | 1.4457 | 1.4457 | 1.0000 | 1.0000 |
PSZ-AC_8:8 | 1.44 | 1.44 | 0.24 | 0.24 | 1.4409 | 1.4409 | 1.4409 | 1.0000 | 1.0000 |
PSZ-AC_9:9 | 1.45 | 1.45 | 0.25 | 0.25 | 1.4469 | 1.4469 | 1.4469 | 1.0000 | 1.0000 |
PSZ-AC_10:10 | 1.66 | 1.66 | 0.28 | 0.28 | 1.6633 | 1.6633 | 1.6633 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 73163.280 | 51422.811 | 2.955550 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 36581.64 | 31295.18 | 1.970367 | 27.39 | 17.36 | 0.00825758 | 12.80 | 10.55 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 20.8834 | 23.89 | 0.00784931 | 42.5696 | 33447.80 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 72888.525 | 72888.525 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 72888.52 | 72888.52 | 2.955551 | 19.61 | 14.76 | 0.00847857 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 13.9222 | 21.11 | 0.00836942 | 53.6826 | 8842.69 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 36952.120 | 25963.299 | 1.491310 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 18476.06 | 15771.03 | 0.994207 | 27.37 | 17.37 | 0.00827530 | 12.80 | 10.55 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 20.6938 | 23.89 | 0.00787416 | 42.7027 | 16877.06 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 36162.766 | 36162.766 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 36162.77 | 36162.77 | 1.491309 | 19.95 | 15.03 | 0.00863499 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 13.7959 | 21.11 | 0.00855202 | 54.8368 | 4231.63 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 36827.090 | 25829.416 | 1.484790 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 18413.54 | 15710.56 | 0.989860 | 27.38 | 17.37 | 0.00828002 | 12.80 | 10.55 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 20.7847 | 23.89 | 0.00787756 | 42.7209 | 16801.76 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 36013.735 | 36013.735 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 36013.73 | 36013.73 | 1.484787 | 19.95 | 15.03 | 0.00863695 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 13.8565 | 21.11 | 0.00855387 | 54.8485 | 4267.66 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 36886.440 | 25875.100 | 1.487840 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 18443.22 | 15739.02 | 0.991893 | 27.37 | 17.37 | 0.00827793 | 12.80 | 10.55 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 20.7421 | 23.89 | 0.00787607 | 42.7130 | 16835.68 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 36083.495 | 36083.495 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 36083.49 | 36083.49 | 1.487840 | 19.95 | 15.03 | 0.00863455 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 13.8281 | 21.11 | 0.00855128 | 54.8321 | 4310.85 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 36832.270 | 25833.418 | 1.485030 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 18416.13 | 15712.93 | 0.990020 | 27.38 | 17.37 | 0.00827992 | 12.80 | 10.55 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 20.7813 | 23.89 | 0.00787749 | 42.7206 | 16803.69 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 36019.311 | 36019.311 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 36019.31 | 36019.31 | 1.485031 | 19.95 | 15.02 | 0.00862751 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 13.8542 | 21.11 | 0.00854293 | 54.7792 | 4432.45 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 67831.390 | 47555.231 | 2.731570 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 33915.69 | 28844.67 | 1.821047 | 27.61 | 17.49 | 0.00832381 | 12.80 | 10.55 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 22.5957 | 23.89 | 0.00788772 | 42.7750 | 30904.12 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 67718.686 | 67718.686 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 67718.69 | 67718.69 | 2.731570 | 19.50 | 14.76 | 0.00851967 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 15.0638 | 21.11 | 0.00840727 | 53.9220 | 9120.68 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 35900.010 | 25168.779 | 1.445690 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 17950.01 | 15273.77 | 0.963793 | 27.45 | 17.42 | 0.00830854 | 12.80 | 10.55 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 21.3468 | 23.89 | 0.00789798 | 42.8303 | 16354.72 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 35632.153 | 35632.153 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 35632.15 | 35632.15 | 1.445693 | 19.62 | 14.80 | 0.00851431 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 14.2312 | 21.11 | 0.00840826 | 53.9282 | 4778.17 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 35779.980 | 25084.628 | 1.440860 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 17889.99 | 15217.58 | 0.960573 | 27.46 | 17.43 | 0.00831212 | 12.80 | 10.55 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 21.4184 | 23.89 | 0.00790055 | 42.8440 | 16299.82 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 35520.110 | 35520.110 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 35520.11 | 35520.11 | 1.440860 | 19.62 | 14.79 | 0.00851460 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 14.2789 | 21.11 | 0.00840818 | 53.9277 | 4785.63 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 35928.900 | 25189.033 | 1.446860 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 17964.45 | 15287.09 | 0.964573 | 27.45 | 17.42 | 0.00830782 | 12.80 | 10.55 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 21.3296 | 23.89 | 0.00789747 | 42.8276 | 16366.09 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 35682.056 | 35682.056 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 35682.06 | 35682.06 | 1.446857 | 19.61 | 14.78 | 0.00849982 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 14.2198 | 21.11 | 0.00839146 | 53.8219 | 5046.10 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 40144.920 | 28508.915 | 1.663280 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 20072.46 | 17248.55 | 1.108853 | 27.06 | 17.20 | 0.00819755 | 12.80 | 10.55 | 0.00700000 | 42.48 | 0.01078126 | 23.77 | 18.5542 | 23.89 | 0.00783229 | 42.4790 | 18824.40 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 40720.540 | 40720.540 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 40720.54 | 40720.54 | 1.663279 | 19.76 | 14.87 | 0.00853490 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 12.3695 | 21.11 | 0.00844759 | 54.1763 | 5667.61 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:41:06
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 73163.280 | 51422.811 | 2.955550 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.1904 | 1004.8586 | 1.2036 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.955551 | 3.55728639 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | Sensible | 36581.64 | 31295.18 | 1.0000 | 2.37152343 | 1.970367 | 27.39 | 17.36 | 0.00825758 | 48594.8 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 36581.64 | 42.80 | 0.01078182 | 23.86 | 0.41147883 | 20.8834 | 23.89 | 0.00784931 | 23.89 | 0.00784931 | 42.5696 | 33447.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 72888.525 | 72888.525 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.955551 | 3.55728639 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | Sensible | 72888.52 | 72888.52 | 1.0000 | 3.55728639 | 2.955551 | 19.61 | 14.76 | 0.00847857 | 41217.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 72888.52 | 12.70 | 0.00915345 | 12.70 | 0.41147883 | 13.9222 | 20.73 | 0.00836942 | 21.11 | 0.00836942 | 53.6826 | 8842.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 36952.120 | 25963.299 | 1.491310 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2234 | 1004.8586 | 1.2036 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.491309 | 1.79493221 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | Sensible | 18476.06 | 15771.03 | 1.0000 | 1.19662215 | 0.994207 | 27.37 | 17.37 | 0.00827530 | 48615.6 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18476.06 | 42.80 | 0.01078182 | 23.86 | 0.20573941 | 20.6938 | 23.89 | 0.00787416 | 23.89 | 0.00787416 | 42.7027 | 16877.06 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 36162.766 | 36162.766 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.491309 | 1.79493221 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 36162.77 | 36162.77 | 1.0000 | 1.79493221 | 1.491309 | 19.95 | 15.03 | 0.00863499 | 41962.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 36162.77 | 12.70 | 0.00915345 | 12.70 | 0.20573941 | 13.7959 | 21.11 | 0.00855202 | 21.11 | 0.00855202 | 54.8368 | 4231.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 36827.090 | 25829.416 | 1.484790 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2322 | 1004.8586 | 1.2036 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.484787 | 1.78708198 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 18413.54 | 15710.56 | 1.0000 | 1.19139053 | 0.989860 | 27.38 | 17.37 | 0.00828002 | 48639.6 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18413.54 | 42.80 | 0.01078182 | 23.86 | 0.20573941 | 20.7847 | 23.89 | 0.00787756 | 23.89 | 0.00787756 | 42.7209 | 16801.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 36013.735 | 36013.735 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.484787 | 1.78708198 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 36013.73 | 36013.73 | 1.0000 | 1.78708198 | 1.484787 | 19.95 | 15.03 | 0.00863695 | 41962.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 36013.73 | 12.70 | 0.00915345 | 12.70 | 0.20573941 | 13.8565 | 21.11 | 0.00855387 | 21.11 | 0.00855387 | 54.8485 | 4267.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 36886.440 | 25875.100 | 1.487840 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2283 | 1004.8586 | 1.2036 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.487840 | 1.79075727 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 18443.22 | 15739.02 | 1.0000 | 1.19383784 | 0.991893 | 27.37 | 17.37 | 0.00827793 | 48628.8 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18443.22 | 42.80 | 0.01078182 | 23.86 | 0.20573941 | 20.7421 | 23.89 | 0.00787607 | 23.89 | 0.00787607 | 42.7130 | 16835.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 36083.495 | 36083.495 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.487840 | 1.79075727 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 36083.49 | 36083.49 | 1.0000 | 1.79075727 | 1.487840 | 19.95 | 15.03 | 0.00863455 | 41958.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 36083.49 | 12.70 | 0.00915345 | 12.70 | 0.20573941 | 13.8281 | 21.11 | 0.00855128 | 21.11 | 0.00855128 | 54.8321 | 4310.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 36832.270 | 25833.418 | 1.485030 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2320 | 1004.8586 | 1.2036 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.485031 | 1.78737567 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 18416.13 | 15712.93 | 1.0000 | 1.19158310 | 0.990020 | 27.38 | 17.37 | 0.00827992 | 48639.0 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18416.13 | 42.80 | 0.01078182 | 23.86 | 0.20573941 | 20.7813 | 23.89 | 0.00787749 | 23.89 | 0.00787749 | 42.7206 | 16803.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 36019.311 | 36019.311 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.485031 | 1.78737567 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 36019.31 | 36019.31 | 1.0000 | 1.78737567 | 1.485031 | 19.95 | 15.02 | 0.00862751 | 41938.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 36019.31 | 12.70 | 0.00915345 | 12.70 | 0.20573941 | 13.8542 | 21.11 | 0.00854293 | 21.11 | 0.00854293 | 54.7792 | 4432.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 67831.390 | 47555.231 | 2.731570 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.3135 | 1004.8586 | 1.2036 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.731570 | 3.28770424 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 33915.69 | 28844.67 | 1.0000 | 2.19180263 | 1.821047 | 27.61 | 17.49 | 0.00832381 | 48985.0 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33915.69 | 42.80 | 0.01078182 | 23.86 | 0.41147883 | 22.5957 | 23.89 | 0.00788772 | 23.89 | 0.00788772 | 42.7750 | 30904.12 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 67718.686 | 67718.686 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.731570 | 3.28770424 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | Sensible | 67718.69 | 67718.69 | 1.0000 | 3.28770424 | 2.731570 | 19.50 | 14.76 | 0.00851967 | 41212.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 67718.69 | 12.70 | 0.00915345 | 12.70 | 0.41147883 | 15.0638 | 20.71 | 0.00840727 | 21.11 | 0.00840727 | 53.9220 | 9120.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 35900.010 | 25168.779 | 1.445690 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2852 | 1004.8586 | 1.2036 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.445693 | 1.74002929 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | Sensible | 17950.01 | 15273.77 | 1.0000 | 1.16001682 | 0.963793 | 27.45 | 17.42 | 0.00830854 | 48785.4 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17950.01 | 42.80 | 0.01078182 | 23.86 | 0.20573941 | 21.3468 | 23.89 | 0.00789798 | 23.89 | 0.00789798 | 42.8303 | 16354.72 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 35632.153 | 35632.153 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.445693 | 1.74002929 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | Sensible | 35632.15 | 35632.15 | 1.0000 | 1.74002929 | 1.445693 | 19.62 | 14.80 | 0.00851431 | 41320.4 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 35632.15 | 12.70 | 0.00915345 | 12.70 | 0.20573941 | 14.2312 | 20.77 | 0.00840826 | 21.11 | 0.00840826 | 53.9282 | 4778.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 35779.980 | 25084.628 | 1.440860 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2918 | 1004.8586 | 1.2036 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.440860 | 1.73421172 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | Sensible | 17889.99 | 15217.58 | 1.0000 | 1.15614124 | 0.960573 | 27.46 | 17.43 | 0.00831212 | 48803.8 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17889.99 | 42.80 | 0.01078182 | 23.86 | 0.20573941 | 21.4184 | 23.89 | 0.00790055 | 23.89 | 0.00790055 | 42.8440 | 16299.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 35520.110 | 35520.110 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.440860 | 1.73421172 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | Sensible | 35520.11 | 35520.11 | 1.0000 | 1.73421172 | 1.440860 | 19.62 | 14.79 | 0.00851460 | 41317.0 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 35520.11 | 12.70 | 0.00915345 | 12.70 | 0.20573941 | 14.2789 | 20.77 | 0.00840818 | 21.11 | 0.00840818 | 53.9277 | 4785.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 35928.900 | 25189.033 | 1.446860 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2838 | 1004.8586 | 1.2036 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.446857 | 1.74142936 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | Sensible | 17964.45 | 15287.09 | 1.0000 | 1.16095562 | 0.964573 | 27.45 | 17.42 | 0.00830782 | 48781.6 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17964.45 | 42.80 | 0.01078182 | 23.86 | 0.20573941 | 21.3296 | 23.89 | 0.00789747 | 23.89 | 0.00789747 | 42.8276 | 16366.09 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 35682.056 | 35682.056 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.446857 | 1.74142936 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | Sensible | 35682.06 | 35682.06 | 1.0000 | 1.74142936 | 1.446857 | 19.61 | 14.78 | 0.00849982 | 41271.3 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 35682.06 | 12.70 | 0.00915345 | 12.70 | 0.20573941 | 14.2198 | 20.75 | 0.00839146 | 21.11 | 0.00839146 | 53.8219 | 5046.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 40144.920 | 28508.915 | 1.663280 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0788 | 1004.8586 | 1.2036 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.663279 | 2.00191448 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | Sensible | 20072.46 | 17248.55 | 1.0000 | 1.33461031 | 1.108853 | 27.06 | 17.20 | 0.00819755 | 48104.5 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20072.46 | 42.48 | 0.01078126 | 23.77 | 0.20573941 | 18.5542 | 23.89 | 0.00783229 | 23.89 | 0.00783229 | 42.4790 | 18824.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 40720.540 | 40720.540 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.663279 | 2.00191448 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | Sensible | 40720.54 | 40720.54 | 1.0000 | 2.00191448 | 1.663279 | 19.76 | 14.87 | 0.00853490 | 41511.9 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 40720.54 | 12.70 | 0.00915345 | 12.70 | 0.20573941 | 12.3695 | 20.75 | 0.00844759 | 21.11 | 0.00844759 | 54.1763 | 5667.61 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:06
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 5365.83 | 811.17 | 753.00 |
SMSTORE1 | 5131.50 | 608.00 | 563.67 |
SMSTORE2 | 4042.50 | 728.50 | 690.67 |
SMSTORE3 | 4035.83 | 722.17 | 680.50 |
SMSTORE4 | 4011.00 | 738.83 | 689.67 |
LGSTORE2 | 3672.83 | 668.50 | 641.17 |
SMSTORE5 | 3584.67 | 665.17 | 633.83 |
SMSTORE6 | 3570.00 | 672.67 | 638.83 |
SMSTORE7 | 3559.50 | 673.67 | 632.50 |
SMSTORE8 | 3632.83 | 595.67 | 540.50 |
Facility | 5486.17 | 1160.67 | 1050.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 0.00 | 3.67 | 0.00 | 3.67 |
SMSTORE1 | 0.00 | 0.33 | 0.00 | 0.33 |
SMSTORE2 | 0.00 | 4.33 | 0.00 | 4.33 |
SMSTORE3 | 0.00 | 4.67 | 0.00 | 4.67 |
SMSTORE4 | 0.00 | 4.67 | 0.00 | 4.67 |
LGSTORE2 | 0.00 | 6.17 | 0.00 | 6.17 |
SMSTORE5 | 0.00 | 4.33 | 0.00 | 4.33 |
SMSTORE6 | 0.00 | 4.33 | 0.00 | 4.33 |
SMSTORE7 | 0.00 | 4.33 | 0.00 | 4.33 |
SMSTORE8 | 0.00 | 3.67 | 0.00 | 3.17 |
Facility | 0.00 | 12.67 | 0.00 | 12.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:06
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.92 | 56.25 | 1805.20 | 0.848 | 0.341 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.688 | 0.378 | 0.000 | 0.000 |
SMSTORE2 | 7.10 | 28.12 | 902.60 | 0.848 | 0.497 | 0.000 | 0.000 |
SMSTORE3 | 7.10 | 28.12 | 902.60 | 0.848 | 0.497 | 0.000 | 0.000 |
SMSTORE4 | 7.10 | 28.12 | 902.60 | 0.848 | 0.497 | 0.000 | 0.000 |
LGSTORE2 | 24.82 | 56.25 | 1805.20 | 0.848 | 0.465 | 0.000 | 0.000 |
SMSTORE5 | 12.41 | 28.12 | 902.60 | 0.848 | 0.530 | 0.000 | 0.000 |
SMSTORE6 | 12.41 | 28.12 | 902.60 | 0.848 | 0.530 | 0.000 | 0.000 |
SMSTORE7 | 12.41 | 28.12 | 902.60 | 0.848 | 0.530 | 0.000 | 0.000 |
SMSTORE8 | 12.41 | 28.12 | 902.60 | 0.848 | 0.549 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.92 | 56.25 | 1805.20 | 0.826 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.041 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.10 | 28.12 | 902.60 | 0.825 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.10 | 28.12 | 902.60 | 0.825 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.10 | 28.12 | 902.60 | 0.824 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.82 | 56.25 | 1805.20 | 0.828 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.41 | 28.12 | 902.60 | 0.828 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.41 | 28.12 | 902.60 | 0.828 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.41 | 28.12 | 902.60 | 0.828 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.41 | 28.12 | 902.60 | 0.828 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:41:06
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 16.92 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE1 | PSZ-AC_2:2 | 8.46 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE2 | PSZ-AC_3:3 | 7.10 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE3 | PSZ-AC_4:4 | 7.10 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE4 | PSZ-AC_5:5 | 7.10 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
LGSTORE2 | PSZ-AC_6:6 | 24.82 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE5 | PSZ-AC_7:7 | 12.41 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE6 | PSZ-AC_8:8 | 12.41 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE7 | PSZ-AC_9:9 | 12.41 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE8 | PSZ-AC_10:10 | 12.41 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
Total Facility | 121.13 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 2.469 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 8803571.45 | 0.00 | 8803571.45 | 3720417.12 | 12523988.57 | 12976396.34 | 2817.00 | 5943.00 | 0.00 | 103.00 |
SMSTORE1 | 3586380.67 | 0.00 | 3586380.67 | 2005460.50 | 5591841.18 | 6488198.17 | 4303.00 | 4457.00 | 0.00 | 103.00 |
SMSTORE2 | 3525580.21 | 0.00 | 3525580.21 | 2030324.42 | 5555904.63 | 6488198.17 | 4000.00 | 4760.00 | 0.00 | 365.00 |
SMSTORE3 | 3525579.41 | 0.00 | 3525579.41 | 2030324.42 | 5555903.83 | 6488198.17 | 4000.00 | 4760.00 | 0.00 | 365.00 |
SMSTORE4 | 3525579.92 | 0.00 | 3525579.92 | 2030324.42 | 5555904.35 | 6488198.17 | 4000.00 | 4760.00 | 0.00 | 365.00 |
LGSTORE2 | 6510484.66 | 0.00 | 6510484.66 | 3601646.44 | 10112131.10 | 12976396.34 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE5 | 3255235.88 | 0.00 | 3255235.88 | 2036872.93 | 5292108.80 | 6488198.17 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE6 | 3255236.11 | 0.00 | 3255236.11 | 2036872.93 | 5292109.03 | 6488198.17 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE7 | 3255235.37 | 0.00 | 3255235.37 | 2036872.93 | 5292108.29 | 6488198.17 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE8 | 3255298.72 | 0.00 | 3255298.72 | 2265587.09 | 5520885.81 | 6488198.17 | 4365.00 | 4395.00 | 0.00 | 366.19 |
Total Facility | 42498182.40 | 0.00 | 42498182.40 | 23794703.20 | 66292885.60 | 77858378.04 | 4365.00 | 6246.00 | 0.00 | 731.19 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.4115 | 0.0000 | 0.4115 | 0.1654 | 0.5768 | 0.4115 | 0.00 | 5840.00 | 0.00 |
SMSTORE1 | 0.1670 | 0.0000 | 0.1670 | 0.0918 | 0.2588 | 0.2057 | 1486.00 | 4354.00 | 0.00 |
SMSTORE2 | 0.2057 | 0.0000 | 0.2057 | 0.1205 | 0.3262 | 0.2057 | 0.00 | 4395.00 | 0.00 |
SMSTORE3 | 0.2057 | 0.0000 | 0.2057 | 0.1205 | 0.3262 | 0.2057 | 0.00 | 4395.00 | 0.00 |
SMSTORE4 | 0.2057 | 0.0000 | 0.2057 | 0.1205 | 0.3262 | 0.2057 | 0.00 | 4395.00 | 0.00 |
LGSTORE2 | 0.4115 | 0.0000 | 0.4115 | 0.2254 | 0.6369 | 0.4115 | 0.00 | 4030.00 | 0.00 |
SMSTORE5 | 0.2057 | 0.0000 | 0.2057 | 0.1284 | 0.3342 | 0.2057 | 0.00 | 4030.00 | 0.00 |
SMSTORE6 | 0.2057 | 0.0000 | 0.2057 | 0.1284 | 0.3342 | 0.2057 | 0.00 | 4030.00 | 0.00 |
SMSTORE7 | 0.2057 | 0.0000 | 0.2057 | 0.1284 | 0.3342 | 0.2057 | 0.00 | 4030.00 | 0.00 |
SMSTORE8 | 0.2057 | 0.0000 | 0.2057 | 0.1330 | 0.3388 | 0.2057 | 0.00 | 4030.00 | 0.00 |
Total Facility | 2.4301 | 0.0000 | 2.4301 | 1.3622 | 3.7923 | 2.4689 | 1486.00 | 5943.00 | 0.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 12753120.48 | 0.00 | 12753120.48 | 12976396.34 | 2817.00 | 0.00 | 5943.00 | 103.00 |
PSZ-AC_2:2 | 5195313.75 | 0.00 | 5195313.75 | 6488198.17 | 4302.67 | 0.17 | 4457.17 | 103.00 |
PSZ-AC_3:3 | 5107256.73 | 0.00 | 5107256.73 | 6488198.17 | 4000.00 | 0.00 | 4760.00 | 365.00 |
PSZ-AC_4:4 | 5107256.73 | 0.00 | 5107256.73 | 6488198.17 | 4000.00 | 0.00 | 4760.00 | 365.00 |
PSZ-AC_5:5 | 5107256.73 | 0.00 | 5107256.73 | 6488198.17 | 4000.00 | 0.00 | 4760.00 | 365.00 |
PSZ-AC_6:6 | 9431257.70 | 0.00 | 9431257.70 | 12976396.34 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_7:7 | 4715628.85 | 0.00 | 4715628.85 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_8:8 | 4715628.85 | 0.00 | 4715628.85 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_9:9 | 4715628.85 | 0.00 | 4715628.85 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_10:10 | 4715734.88 | 0.00 | 4715734.88 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 366.19 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.5961 | 0.0000 | 0.5961 | 0.4115 | 0.00 | 0.00 | 5840.00 |
PSZ-AC_2:2 | 0.2419 | 0.0000 | 0.2419 | 0.2057 | 1485.67 | 0.17 | 4354.17 |
PSZ-AC_3:3 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_4:4 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_5:5 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_6:6 | 0.5961 | 0.0000 | 0.5961 | 0.4115 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_7:7 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_8:8 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_9:9 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_10:10 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 5943.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 5943.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 4760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 4760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 4760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 4396.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.5961 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.2419 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 0.5962 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:06
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 759 |
Defaulted Fields | 823 |
Fields with Defaults | 2681 |
Autosized Fields | 184 |
Autosizable Fields | 458 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:41:06
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1524.08 | 3115.94 | 01-JAN-07:10 | 159951.58 | 10-AUG-15:50 |
Electricity:Building | 570.24 | 1897.94 | 01-JAN-00:10 | 35612.10 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 128.86 | 354.96 | 01-JAN-00:10 | 6669.68 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 570.24 | 1897.94 | 01-JAN-00:10 | 35612.10 | 01-JAN-11:10 |
InteriorLights:Electricity | 441.52 | 1448.52 | 01-JAN-00:10 | 27522.57 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 102.50 | 280.06 | 01-JAN-00:10 | 5321.43 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 441.52 | 1448.52 | 01-JAN-00:10 | 27522.57 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 441.52 | 1448.52 | 01-JAN-00:10 | 27522.57 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 102.50 | 280.06 | 01-JAN-00:10 | 5321.43 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 441.52 | 1448.52 | 01-JAN-00:10 | 27522.57 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 69.66 | 191.80 | 01-JAN-00:10 | 3606.70 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 56.49 | 154.35 | 01-JAN-00:10 | 2932.57 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 56.49 | 154.35 | 01-JAN-00:10 | 2932.57 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 50.51 | 174.25 | 01-JAN-00:10 | 3273.35 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 40.04 | 136.80 | 01-JAN-00:10 | 2599.23 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 40.04 | 136.80 | 01-JAN-00:10 | 2599.23 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 50.51 | 174.25 | 01-JAN-00:10 | 3273.35 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 40.04 | 136.80 | 01-JAN-00:10 | 2599.23 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 40.04 | 136.80 | 01-JAN-00:10 | 2599.23 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 50.51 | 174.25 | 01-JAN-00:10 | 3273.35 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 40.04 | 136.80 | 01-JAN-00:10 | 2599.23 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 40.04 | 136.80 | 01-JAN-00:10 | 2599.23 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 72.31 | 272.07 | 01-JAN-00:10 | 5094.77 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 53.05 | 197.17 | 01-JAN-00:10 | 3746.51 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 53.05 | 197.17 | 01-JAN-00:10 | 3746.51 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 36.97 | 139.09 | 01-JAN-00:10 | 2605.22 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 36.97 | 139.09 | 01-JAN-00:10 | 2605.22 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 36.97 | 139.09 | 01-JAN-00:10 | 2605.22 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 36.97 | 139.09 | 01-JAN-00:10 | 2605.22 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.36 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.36 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.18 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.18 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.26 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.26 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
ElectricityPurchased:Facility | 1524.08 | 3115.94 | 01-JAN-07:10 | 159951.58 | 10-AUG-15:50 |
ElectricityPurchased:Plant | 1524.08 | 3115.94 | 01-JAN-07:10 | 159951.58 | 10-AUG-15:50 |
Cogeneration:ElectricityPurchased | 1524.08 | 3115.94 | 01-JAN-07:10 | 159951.58 | 10-AUG-15:50 |
General:Cogeneration:ElectricityPurchased | 1524.08 | 3115.94 | 01-JAN-07:10 | 159951.58 | 10-AUG-15:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1524.08 | 3115.94 | 01-JAN-07:10 | 159951.58 | 10-AUG-15:50 |
ElectricityNet:Plant | 1524.08 | 3115.94 | 01-JAN-07:10 | 159951.58 | 10-AUG-15:50 |
Cogeneration:ElectricityNet | 1524.08 | 3115.94 | 01-JAN-07:10 | 159951.58 | 10-AUG-15:50 |
General:Cogeneration:ElectricityNet | 1524.08 | 3115.94 | 01-JAN-07:10 | 159951.58 | 10-AUG-15:50 |
Electricity:HVAC | 796.17 | 0.00 | 01-JAN-00:10 | 122783.55 | 10-AUG-16:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 656.57 | 0.00 | 01-JAN-00:10 | 107664.98 | 10-AUG-16:10 |
General:Cooling:Electricity | 656.57 | 0.00 | 01-JAN-00:10 | 107664.98 | 10-AUG-16:10 |
Fans:Electricity | 139.60 | 0.00 | 01-JAN-00:10 | 15118.57 | 10-AUG-16:10 |
General:Fans:Electricity | 139.60 | 0.00 | 01-JAN-00:10 | 15118.57 | 10-AUG-16:10 |
ExteriorLights:Electricity | 100.00 | 0.00 | 01-JAN-07:10 | 7619.51 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 100.00 | 0.00 | 01-JAN-07:10 | 7619.51 | 01-JAN-06:10 |
Electricity:Plant | 57.66 | 1218.00 | 01-MAR-09:10 | 12949.94 | 01-JAN-08:10 |
WaterSystems:Electricity | 57.66 | 1218.00 | 01-MAR-09:10 | 12949.94 | 01-JAN-08:10 |
Water Heater:WaterSystems:Electricity | 57.66 | 1218.00 | 01-MAR-09:10 | 12949.94 | 01-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
NaturalGas:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 3587.12 | 0.00 | 01-JAN-00:10 | 517476.14 | 10-AUG-16:10 |
EnergyTransfer:Building | 1219.05 | 0.00 | 01-JAN-00:10 | 163397.76 | 16-AUG-12:10 |
EnergyTransfer:Zone:LGSTORE1 | 244.65 | 0.00 | 01-JAN-00:10 | 26593.28 | 04-AUG-13:00 |
Heating:EnergyTransfer | 9.75 | 0.00 | 01-JAN-00:10 | 35009.79 | 05-AUG-17:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 0.44 | 0.00 | 01-JAN-00:10 | 3906.66 | 27-MAR-08:20 |
General:Heating:EnergyTransfer | 9.75 | 0.00 | 01-JAN-00:10 | 35009.79 | 05-AUG-17:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 0.44 | 0.00 | 01-JAN-00:10 | 3906.66 | 27-MAR-08:20 |
Cooling:EnergyTransfer | 1209.30 | 0.00 | 01-JAN-00:10 | 163397.76 | 16-AUG-12:10 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 244.21 | 0.00 | 01-JAN-00:10 | 26593.28 | 04-AUG-13:00 |
General:Cooling:EnergyTransfer | 1209.30 | 0.00 | 01-JAN-00:10 | 163397.76 | 16-AUG-12:10 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 244.21 | 0.00 | 01-JAN-00:10 | 26593.28 | 04-AUG-13:00 |
EnergyTransfer:Zone:SMSTORE1 | 125.20 | 0.00 | 01-JAN-00:10 | 13577.09 | 16-AUG-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 0.21 | 0.00 | 01-JAN-00:10 | 1529.73 | 27-MAR-08:20 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 0.21 | 0.00 | 01-JAN-00:10 | 1529.73 | 27-MAR-08:20 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 124.99 | 0.00 | 01-JAN-00:10 | 13577.09 | 16-AUG-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 124.99 | 0.00 | 01-JAN-00:10 | 13577.09 | 16-AUG-12:10 |
EnergyTransfer:Zone:SMSTORE2 | 98.47 | 0.00 | 01-JAN-00:10 | 13628.05 | 16-AUG-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 1.67 | 0.00 | 01-JAN-00:10 | 4150.93 | 31-MAY-19:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 1.67 | 0.00 | 01-JAN-00:10 | 4150.93 | 31-MAY-19:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 96.80 | 0.00 | 01-JAN-00:10 | 13628.05 | 16-AUG-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 96.80 | 0.00 | 01-JAN-00:10 | 13628.05 | 16-AUG-12:10 |
EnergyTransfer:Zone:SMSTORE3 | 99.08 | 0.00 | 01-JAN-00:10 | 13703.85 | 16-AUG-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 1.66 | 0.00 | 01-JAN-00:10 | 4148.11 | 31-MAY-19:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 1.66 | 0.00 | 01-JAN-00:10 | 4148.11 | 31-MAY-19:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 97.42 | 0.00 | 01-JAN-00:10 | 13703.85 | 16-AUG-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 97.42 | 0.00 | 01-JAN-00:10 | 13703.85 | 16-AUG-12:10 |
EnergyTransfer:Zone:SMSTORE4 | 97.76 | 0.00 | 01-JAN-00:10 | 13631.37 | 16-AUG-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 1.68 | 0.00 | 01-JAN-00:10 | 4153.49 | 31-MAY-19:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 1.68 | 0.00 | 01-JAN-00:10 | 4153.49 | 31-MAY-19:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 96.08 | 0.00 | 01-JAN-00:10 | 13631.37 | 16-AUG-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 96.08 | 0.00 | 01-JAN-00:10 | 13631.37 | 16-AUG-12:10 |
EnergyTransfer:Zone:LGSTORE2 | 174.36 | 0.00 | 01-JAN-00:10 | 25364.23 | 16-AUG-12:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 1.33 | 0.00 | 01-JAN-00:10 | 7813.54 | 05-AUG-17:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 1.33 | 0.00 | 01-JAN-00:10 | 7813.54 | 05-AUG-17:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 173.03 | 0.00 | 01-JAN-00:10 | 25364.23 | 16-AUG-12:10 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 173.03 | 0.00 | 01-JAN-00:10 | 25364.23 | 16-AUG-12:10 |
EnergyTransfer:Zone:SMSTORE5 | 91.79 | 0.00 | 01-JAN-00:10 | 13574.70 | 16-AUG-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 0.70 | 0.00 | 01-JAN-00:10 | 3917.42 | 05-AUG-17:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 0.70 | 0.00 | 01-JAN-00:10 | 3917.42 | 05-AUG-17:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 91.08 | 0.00 | 01-JAN-00:10 | 13574.70 | 16-AUG-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 91.08 | 0.00 | 01-JAN-00:10 | 13574.70 | 16-AUG-12:10 |
EnergyTransfer:Zone:SMSTORE6 | 91.27 | 0.00 | 01-JAN-00:10 | 13539.77 | 16-AUG-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 0.70 | 0.00 | 01-JAN-00:10 | 3920.01 | 05-AUG-17:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 0.70 | 0.00 | 01-JAN-00:10 | 3920.01 | 05-AUG-17:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 90.57 | 0.00 | 01-JAN-00:10 | 13539.77 | 16-AUG-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 90.57 | 0.00 | 01-JAN-00:10 | 13539.77 | 16-AUG-12:10 |
EnergyTransfer:Zone:SMSTORE7 | 91.38 | 0.00 | 01-JAN-00:10 | 13670.24 | 16-AUG-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 0.71 | 0.00 | 01-JAN-00:10 | 3913.12 | 05-AUG-17:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 0.71 | 0.00 | 01-JAN-00:10 | 3913.12 | 05-AUG-17:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 90.67 | 0.00 | 01-JAN-00:10 | 13670.24 | 16-AUG-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 90.67 | 0.00 | 01-JAN-00:10 | 13670.24 | 16-AUG-12:10 |
EnergyTransfer:Zone:SMSTORE8 | 105.09 | 0.00 | 01-JAN-00:10 | 16168.42 | 16-AUG-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 0.64 | 0.00 | 01-JAN-00:10 | 3770.80 | 05-AUG-17:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 0.64 | 0.00 | 01-JAN-00:10 | 3770.80 | 05-AUG-17:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 104.45 | 0.00 | 01-JAN-00:10 | 16168.42 | 16-AUG-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 104.45 | 0.00 | 01-JAN-00:10 | 16168.42 | 16-AUG-12:10 |
EnergyTransfer:HVAC | 2368.07 | 0.00 | 01-JAN-00:10 | 379222.48 | 20-JUL-13:00 |
HeatingCoils:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
CoolingCoils:EnergyTransfer | 2368.07 | 0.00 | 01-JAN-00:10 | 379222.48 | 20-JUL-13:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:06
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 0.438 | -244.208 | 0.000 | 0.000 | 23.198 | 102.498 | 26.357 | 20.580 | 0.000 | 32.724 | 43.457 | 0.000 | -2.686 | 0.000 | -2.359 | -0.001 |
SMSTORE1 | 0.000 | 0.000 | 0.209 | -124.993 | 0.000 | 0.000 | 11.598 | 56.486 | 13.179 | 10.356 | 0.000 | 18.088 | 17.545 | 0.000 | -1.347 | 0.000 | -1.120 | -0.000 |
SMSTORE2 | 0.000 | 0.000 | 1.671 | -96.800 | 0.000 | 0.000 | 6.964 | 40.039 | 10.467 | 10.129 | 0.000 | 17.927 | 12.243 | 0.000 | -1.445 | 0.000 | -1.195 | -0.000 |
SMSTORE3 | 0.000 | 0.000 | 1.664 | -97.414 | 0.000 | 0.000 | 6.964 | 40.039 | 10.467 | 10.108 | 0.000 | 17.916 | 12.903 | 0.000 | -1.452 | 0.000 | -1.195 | -0.001 |
SMSTORE4 | 0.000 | 0.000 | 1.682 | -96.076 | 0.000 | 0.000 | 6.965 | 40.039 | 10.467 | 10.121 | 0.000 | 17.922 | 11.498 | 0.000 | -1.433 | 0.000 | -1.185 | -0.000 |
LGSTORE2 | 0.000 | 0.000 | 1.330 | -173.030 | 0.000 | 0.000 | 23.910 | 53.048 | 19.261 | 20.251 | 0.000 | 31.455 | 28.734 | 0.000 | -2.775 | 0.000 | -2.185 | -0.000 |
SMSTORE5 | 0.000 | 0.000 | 0.702 | -91.083 | 0.000 | 0.000 | 11.955 | 27.343 | 9.631 | 10.166 | 0.000 | 17.890 | 15.967 | 0.000 | -1.369 | 0.000 | -1.202 | -0.000 |
SMSTORE6 | 0.000 | 0.000 | 0.703 | -90.564 | 0.000 | 0.000 | 11.955 | 27.343 | 9.631 | 10.172 | 0.000 | 17.892 | 15.430 | 0.000 | -1.363 | 0.000 | -1.199 | -0.001 |
SMSTORE7 | 0.000 | 0.000 | 0.711 | -90.669 | 0.000 | 0.000 | 11.955 | 27.343 | 9.631 | 10.161 | 0.000 | 17.890 | 15.526 | 0.000 | -1.357 | 0.000 | -1.190 | -0.000 |
SMSTORE8 | 0.000 | 0.000 | 0.640 | -104.448 | 0.000 | 0.000 | 11.955 | 27.343 | 9.631 | 10.019 | 0.000 | 18.838 | 28.987 | 0.000 | -1.356 | 0.000 | -1.607 | -0.000 |
Total Facility | 0.000 | 0.000 | 9.749 | -1209.284 | 0.000 | 0.000 | 127.420 | 441.522 | 128.721 | 122.062 | 0.000 | 208.542 | 202.290 | 0.000 | -16.582 | 0.000 | -14.439 | -0.004 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 28-MAR-08:61 | 0.00 | 0.00 | 0.00 | -62692.08 | 0.00 | 0.00 | 165.41 | 2800.74 | 749.03 | 458.37 | 0.00 | 87.76 | 58430.76 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 28-MAR-08:61 | 0.00 | 0.00 | 0.00 | -31733.82 | 0.00 | 0.00 | 82.24 | 1543.46 | 374.52 | 227.52 | 0.00 | 45.13 | 29460.96 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 28-MAR-07:02 | 0.00 | 0.00 | 0.00 | -31842.53 | 0.00 | 0.00 | 83.99 | 1368.01 | 374.52 | 25.84 | 0.00 | 0.00 | 29994.80 | 0.00 | -0.00 | 0.00 | -4.64 | 0.00 |
SMSTORE3 | 28-MAR-07:02 | 0.00 | 0.00 | 0.00 | -31908.90 | 0.00 | 0.00 | 83.69 | 1368.01 | 374.52 | 24.72 | 0.00 | 0.00 | 30064.12 | 0.00 | -0.00 | 0.00 | -6.16 | 0.00 |
SMSTORE4 | 28-MAR-07:02 | 0.00 | 0.00 | 0.00 | -31819.46 | 0.00 | 0.00 | 84.35 | 1368.01 | 374.52 | 26.42 | 0.00 | 0.00 | 29968.82 | 0.00 | -0.00 | 0.00 | -2.65 | 0.00 |
LGSTORE2 | 28-MAR-08:61 | 0.00 | 0.00 | 0.00 | -58447.58 | 0.00 | 0.00 | 364.81 | 1971.84 | 749.03 | 452.71 | 0.00 | 79.03 | 54830.17 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 28-MAR-08:61 | 0.00 | 0.00 | 0.00 | -30799.10 | 0.00 | 0.00 | 183.10 | 1016.37 | 374.52 | 227.31 | 0.00 | 48.96 | 28948.85 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 28-MAR-08:61 | 0.00 | 0.00 | 0.00 | -30691.31 | 0.00 | 0.00 | 183.45 | 1016.37 | 374.52 | 227.87 | 0.00 | 49.67 | 28839.43 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 28-MAR-08:61 | 0.00 | 0.00 | 0.00 | -30781.63 | 0.00 | 0.00 | 184.23 | 1016.37 | 374.52 | 228.56 | 0.00 | 51.86 | 28926.10 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 28-MAR-08:61 | 0.00 | 0.00 | 0.00 | -34087.83 | 0.00 | 0.00 | 184.12 | 1016.37 | 374.52 | 228.94 | 0.00 | 62.36 | 32221.52 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 28-MAR-08:61 | 0.00 | 0.00 | 0.00 | -290602.44 | 0.00 | 0.00 | 1938.40 | 18179.18 | 5393.02 | 2797.44 | 0.00 | 682.63 | 261611.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 10-MAY-08:04 | 0.00 | 0.00 | 9607.90 | 0.00 | 0.00 | 0.00 | 158.15 | 2800.74 | 749.03 | 1050.16 | 0.00 | 1035.22 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -15401.19 |
SMSTORE1 | 10-MAY-08:04 | 0.00 | 0.00 | 4787.93 | 0.00 | 0.00 | 0.00 | 79.07 | 1543.46 | 374.52 | 527.55 | 0.00 | 559.75 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7872.28 |
SMSTORE2 | 31-MAY-19:02 | 0.00 | 0.00 | 4600.20 | 0.00 | 0.00 | 0.00 | 98.50 | 1368.01 | 374.52 | 347.32 | 0.00 | 63.47 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6852.02 |
SMSTORE3 | 31-MAY-19:02 | 0.00 | 0.00 | 4598.53 | 0.00 | 0.00 | 0.00 | 98.50 | 1368.01 | 374.52 | 347.06 | 0.00 | 63.46 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6850.08 |
SMSTORE4 | 31-MAY-19:02 | 0.00 | 0.00 | 4601.56 | 0.00 | 0.00 | 0.00 | 98.50 | 1368.01 | 374.52 | 347.18 | 0.00 | 63.47 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6853.24 |
LGSTORE2 | 10-MAY-08:04 | 0.00 | 0.00 | 9095.83 | 0.00 | 0.00 | 0.00 | 347.92 | 1971.84 | 749.03 | 1045.07 | 0.00 | 970.20 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -14179.90 |
SMSTORE5 | 10-MAY-08:04 | 0.00 | 0.00 | 4690.17 | 0.00 | 0.00 | 0.00 | 173.96 | 1016.37 | 374.52 | 525.03 | 0.00 | 554.83 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7334.87 |
SMSTORE6 | 10-MAY-08:04 | 0.00 | 0.00 | 4680.39 | 0.00 | 0.00 | 0.00 | 173.96 | 1016.37 | 374.52 | 525.32 | 0.00 | 554.36 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7324.90 |
SMSTORE7 | 10-MAY-08:04 | 0.00 | 0.00 | 4696.66 | 0.00 | 0.00 | 0.00 | 173.96 | 1016.37 | 374.52 | 524.87 | 0.00 | 555.18 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7341.54 |
SMSTORE8 | 10-MAY-08:04 | 0.00 | 0.00 | 4963.54 | 0.00 | 0.00 | 0.00 | 173.96 | 1016.37 | 374.52 | 519.95 | 0.00 | 611.97 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7660.30 |
Total Facility | 10-MAY-08:04 | -17116.30 | 17116.30 | 42522.42 | -17116.30 | 0.00 | 0.00 | 1871.99 | 18179.18 | 5393.02 | 6394.69 | 0.00 | 6494.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -63739.22 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:06
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.9556 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.9556 | 0.1392 | 1.0000 | Not calculated | 0.4115 | 0.1392 | ||
PSZ-AC_2:2 | 1.4913 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4913 | 0.1380 | 1.0000 | Not calculated | 0.2057 | 0.1380 | ||
PSZ-AC_3:3 | 1.4848 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4848 | 0.1386 | 1.0000 | Not calculated | 0.2057 | 0.1386 | ||
PSZ-AC_4:4 | 1.4878 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4878 | 0.1383 | 1.0000 | Not calculated | 0.2057 | 0.1383 | ||
PSZ-AC_5:5 | 1.4850 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4850 | 0.1385 | 1.0000 | Not calculated | 0.2057 | 0.1385 | ||
PSZ-AC_6:6 | 2.7316 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.7316 | 0.1506 | 1.0000 | Not calculated | 0.4115 | 0.1506 | ||
PSZ-AC_7:7 | 1.4457 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4457 | 0.1423 | 1.0000 | Not calculated | 0.2057 | 0.1423 | ||
PSZ-AC_8:8 | 1.4409 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4409 | 0.1428 | 1.0000 | Not calculated | 0.2057 | 0.1428 | ||
PSZ-AC_9:9 | 1.4469 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4469 | 0.1422 | 1.0000 | Not calculated | 0.2057 | 0.1422 | ||
PSZ-AC_10:10 | 1.6633 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.6633 | 0.1237 | 1.0000 | Not calculated | 0.2057 | 0.1237 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.9556 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.9556 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.1392 | ||
PSZ-AC_2:2 | 1.4913 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4913 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1380 | ||
PSZ-AC_3:3 | 1.4848 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4848 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1386 | ||
PSZ-AC_4:4 | 1.4878 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4878 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1383 | ||
PSZ-AC_5:5 | 1.4850 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4850 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1385 | ||
PSZ-AC_6:6 | 2.7316 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.7316 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.1506 | ||
PSZ-AC_7:7 | 1.4457 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4457 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1423 | ||
PSZ-AC_8:8 | 1.4409 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4409 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1428 | ||
PSZ-AC_9:9 | 1.4469 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4469 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1422 | ||
PSZ-AC_10:10 | 1.6633 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.6633 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1237 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.9556 | 2.9556 | 2.9556 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4913 | 1.4913 | 1.4913 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4848 | 1.4848 | 1.4848 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4878 | 1.4878 | 1.4878 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4850 | 1.4850 | 1.4850 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.7316 | 2.7316 | 2.7316 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4457 | 1.4457 | 1.4457 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4409 | 1.4409 | 1.4409 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4469 | 1.4469 | 1.4469 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6633 | 1.6633 | 1.6633 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.9556 | 2.9556 | 2.9556 | 2.9556 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.4913 | 1.4913 | 1.4913 | 1.4913 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.4848 | 1.4848 | 1.4848 | 1.4848 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.4878 | 1.4878 | 1.4878 | 1.4878 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.4850 | 1.4850 | 1.4850 | 1.4850 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.7316 | 2.7316 | 2.7316 | 2.7316 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.4457 | 1.4457 | 1.4457 | 1.4457 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.4409 | 1.4409 | 1.4409 | 1.4409 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.4469 | 1.4469 | 1.4469 | 1.4469 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.6633 | 1.6633 | 1.6633 | 1.6633 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.9556 | 2.9556 | 2.9556 | No | 0.4115 | 0.9359 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4913 | 1.4913 | 1.4913 | No | 0.2057 | 0.9393 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4848 | 1.4848 | 1.4848 | No | 0.2057 | 0.9314 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4878 | 1.4878 | 1.4878 | No | 0.2057 | 0.9220 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4850 | 1.4850 | 1.4850 | No | 0.2057 | 0.8967 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.7316 | 2.7316 | 2.7316 | No | 0.4115 | 0.9099 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4457 | 1.4457 | 1.4457 | No | 0.2057 | 0.8645 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4409 | 1.4409 | 1.4409 | No | 0.2057 | 0.8631 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4469 | 1.4469 | 1.4469 | No | 0.2057 | 0.8192 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6633 | 1.6633 | 1.6633 | No | 0.2057 | 0.7259 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.9556 | 2.9556 | 2.9556 | 2.9556 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.4913 | 1.4913 | 1.4913 | 1.4913 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.4848 | 1.4848 | 1.4848 | 1.4848 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.4878 | 1.4878 | 1.4878 | 1.4878 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.4850 | 1.4850 | 1.4850 | 1.4850 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.7316 | 2.7316 | 2.7316 | 2.7316 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.4457 | 1.4457 | 1.4457 | 1.4457 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.4409 | 1.4409 | 1.4409 | 1.4409 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.4469 | 1.4469 | 1.4469 | 1.4469 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.6633 | 1.6633 | 1.6633 | 1.6633 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:06
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Total gross floor area [m2] | 2090.32 |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 12.17 |
Number of hours not met | 12.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 656.57 | 107664.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 441.52 | 27522.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 100.00 | 7619.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.72 | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 139.60 | 15118.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 57.66 | 12949.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.72 | 1524.08 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 128.72 | 1524.08 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 211.22 |
Space Heating | 0.00 |
Space Cooling | 314.10 |
Fans (All) | 66.78 |
Service Water Heating | 27.59 |
Receptacle Equipment | 61.58 |
Miscellaneous (All) | 729.12 |
Subtotal | 729.12 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.00 |
Subtotal | 0.00 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 28.97 |
Space Heating | 0.00 |
Space Cooling | 43.08 |
Fans (All) | 9.16 |
Service Water Heating | 3.78 |
Receptacle Equipment | 8.45 |
Miscellaneous | 6.56 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3238. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3296. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 4469. | 8760. |
LTG_SCH_BASE_LPD1 | 4391. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 3584. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4888. | 8760. |
TYPE2_EQUIP_SCH | 3911. | 8760. |
TYPE3_EQUIP_SCH | 3600. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2505. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:06
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 7828.33 | 931.67 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8129.00 | 631.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 6557.33 | 2156.83 | 45.83 | 0.00 | 0.00 |
SMSTORE3 | 6493.17 | 2218.50 | 48.33 | 0.00 | 0.00 |
SMSTORE4 | 6571.00 | 2141.33 | 47.67 | 0.00 | 0.00 |
LGSTORE2 | 6899.67 | 1809.67 | 50.67 | 0.00 | 0.00 |
SMSTORE5 | 7026.17 | 1683.33 | 50.50 | 0.00 | 0.00 |
SMSTORE6 | 7045.67 | 1664.17 | 50.17 | 0.00 | 0.00 |
SMSTORE7 | 7044.50 | 1663.50 | 52.00 | 0.00 | 0.00 |
SMSTORE8 | 6687.17 | 1889.50 | 183.33 | 0.00 | 0.00 |
Min | 6493.17 | 631.00 | 0.00 | 0.00 | 0.00 |
Max | 8129.00 | 2218.50 | 183.33 | 0.00 | 0.00 |
Average | 7028.20 | 1678.95 | 52.85 | 0.00 | 0.00 |
Sum | 70282.00 | 16789.50 | 528.50 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 88868.67 | 172.33 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43704.17 | 72.83 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25321.83 | 150.50 | 2.67 | 0.00 | 0.00 |
SMSTORE3 | 25321.17 | 151.00 | 2.83 | 0.00 | 0.00 |
SMSTORE4 | 25323.67 | 148.50 | 2.83 | 0.00 | 0.00 |
LGSTORE2 | 92877.00 | 317.00 | 17.00 | 0.00 | 0.00 |
SMSTORE5 | 45744.50 | 159.00 | 8.50 | 0.00 | 0.00 |
SMSTORE6 | 45745.00 | 159.50 | 7.50 | 0.00 | 0.00 |
SMSTORE7 | 45745.50 | 158.50 | 8.00 | 0.00 | 0.00 |
SMSTORE8 | 45731.50 | 170.00 | 10.50 | 0.00 | 0.00 |
Min | 25321.17 | 72.83 | 0.00 | 0.00 | 0.00 |
Max | 92877.00 | 317.00 | 17.00 | 0.00 | 0.00 |
Average | 48438.30 | 165.92 | 5.98 | 0.00 | 0.00 |
Sum | 484383.00 | 1659.17 | 59.83 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 6343.33 | 2416.67 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 7271.83 | 1488.17 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 4917.17 | 3804.17 | 38.67 | 0.00 | 0.00 |
SMSTORE3 | 4926.33 | 3794.83 | 38.83 | 0.00 | 0.00 |
SMSTORE4 | 4950.50 | 3770.67 | 38.83 | 0.00 | 0.00 |
LGSTORE2 | 5119.83 | 3598.33 | 41.83 | 0.00 | 0.00 |
SMSTORE5 | 5186.83 | 3530.33 | 42.83 | 0.00 | 0.00 |
SMSTORE6 | 5188.67 | 3528.50 | 42.83 | 0.00 | 0.00 |
SMSTORE7 | 5226.50 | 3490.33 | 43.17 | 0.00 | 0.00 |
SMSTORE8 | 5167.50 | 3484.83 | 107.67 | 0.00 | 0.00 |
Min | 4917.17 | 1488.17 | 0.00 | 0.00 | 0.00 |
Max | 7271.83 | 3804.17 | 107.67 | 0.00 | 0.00 |
Average | 5429.85 | 3290.68 | 39.47 | 0.00 | 0.00 |
Sum | 54298.50 | 32906.83 | 394.67 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 80030.67 | 9010.33 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 39485.67 | 4291.33 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 22221.67 | 3252.83 | 0.50 | 0.00 | 0.00 |
SMSTORE3 | 22262.00 | 3212.50 | 0.50 | 0.00 | 0.00 |
SMSTORE4 | 22208.50 | 3266.00 | 0.50 | 0.00 | 0.00 |
LGSTORE2 | 80128.83 | 13079.17 | 3.00 | 0.00 | 0.00 |
SMSTORE5 | 39439.83 | 6469.67 | 2.50 | 0.00 | 0.00 |
SMSTORE6 | 39385.67 | 6523.83 | 2.50 | 0.00 | 0.00 |
SMSTORE7 | 39491.67 | 6418.33 | 2.00 | 0.00 | 0.00 |
SMSTORE8 | 40604.17 | 5306.33 | 1.50 | 0.00 | 0.00 |
Min | 22208.50 | 3212.50 | 0.00 | 0.00 | 0.00 |
Max | 80128.83 | 13079.17 | 3.00 | 0.00 | 0.00 |
Average | 42525.87 | 6083.03 | 1.30 | 0.00 | 0.00 |
Sum | 425258.67 | 60830.33 | 13.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:06
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:06
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Environment
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
For: Environment
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
For: Environment
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.113576E+11 | 26078.51 | 29-JAN-08:62 | 22.17 | 18.26 | 0.140842E+10 | 1685.99 | 22-JAN-13:00 | 22.17 | 18.26 |
February | 0.114960E+11 | 36774.21 | 09-FEB-09:02 | 23.12 | 19.10 | 0.127233E+10 | 1686.04 | 05-FEB-13:09 | 23.12 | 19.10 |
March | 0.146812E+11 | 62691.86 | 28-MAR-08:61 | 26.03 | 13.62 | 0.139803E+10 | 1686.05 | 25-MAR-12:00 | 26.03 | 13.62 |
April | 0.175580E+11 | 61781.34 | 27-APR-08:61 | 29.83 | 15.29 | 0.136286E+10 | 1686.08 | 22-APR-12:00 | 29.83 | 15.29 |
May | 0.236400E+11 | 58825.99 | 11-MAY-08:61 | 33.67 | 17.81 | 0.140438E+10 | 1686.05 | 14-MAY-17:00 | 33.00 | 21.47 |
June | 0.249846E+11 | 55808.19 | 02-JUN-08:61 | 33.67 | 17.87 | 0.135751E+10 | 1686.13 | 02-JUN-12:00 | 38.60 | 24.59 |
July | 0.284110E+11 | 57161.01 | 04-JUL-07:01 | 31.33 | 17.56 | 0.141569E+10 | 1686.18 | 04-JUL-12:20 | 39.90 | 23.87 |
August | 0.295504E+11 | 51724.65 | 06-AUG-07:01 | 35.08 | 22.69 | 0.139745E+10 | 1686.07 | 06-AUG-17:30 | 39.50 | 26.07 |
September | 0.261082E+11 | 52124.46 | 26-SEP-08:61 | 29.83 | 18.30 | 0.136790E+10 | 1686.14 | 24-SEP-12:00 | 29.83 | 18.30 |
October | 0.239949E+11 | 58596.14 | 21-OCT-08:62 | 24.83 | 14.71 | 0.141245E+10 | 1686.08 | 08-OCT-16:10 | 24.83 | 14.71 |
November | 0.186427E+11 | 55040.72 | 05-NOV-07:02 | 21.17 | 15.81 | 0.136494E+10 | 1686.06 | 17-NOV-13:00 | 29.00 | 19.29 |
December | 0.137842E+11 | 49439.29 | 12-DEC-09:02 | 24.07 | 17.73 | 0.141697E+10 | 1686.06 | 03-DEC-13:39 | 24.07 | 17.73 |
Annual Sum or Average | 0.244209E+12 | 0.165789E+11 | ||||||||
Minimum of Months | 0.113576E+11 | 26078.51 | 21.17 | 13.62 | 0.127233E+10 | 1685.99 | 22.17 | 13.62 | ||
Maximum of Months | 0.295504E+11 | 62691.86 | 35.08 | 22.69 | 0.141697E+10 | 1686.18 | 39.90 | 26.07 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.613355E+10 | 15306.54 | 29-JAN-08:62 | 22.17 | 18.26 | 0.704465E+09 | 843.21 | 01-JAN-18:49 | 22.17 | 18.26 |
February | 0.618548E+10 | 19544.87 | 09-FEB-09:02 | 23.12 | 19.10 | 0.636316E+09 | 843.26 | 05-FEB-18:19 | 23.12 | 19.10 |
March | 0.782245E+10 | 31733.74 | 28-MAR-08:61 | 26.03 | 13.62 | 0.699139E+09 | 843.04 | 05-MAR-18:49 | 26.03 | 13.62 |
April | 0.921555E+10 | 31068.38 | 27-APR-08:61 | 29.83 | 15.29 | 0.681501E+09 | 843.08 | 09-APR-17:49 | 29.83 | 15.29 |
May | 0.120974E+11 | 30464.55 | 08-MAY-08:61 | 31.67 | 17.07 | 0.702196E+09 | 843.03 | 14-MAY-17:30 | 33.50 | 21.38 |
June | 0.126380E+11 | 29458.43 | 02-JUN-08:61 | 33.67 | 17.87 | 0.678735E+09 | 843.06 | 02-JUN-12:00 | 38.60 | 24.59 |
July | 0.142482E+11 | 29881.06 | 04-JUL-07:01 | 31.33 | 17.56 | 0.707807E+09 | 843.08 | 23-JUL-17:00 | 38.00 | 24.94 |
August | 0.146556E+11 | 27570.38 | 06-AUG-07:01 | 35.08 | 22.69 | 0.698680E+09 | 843.00 | 13-AUG-17:30 | 37.50 | 25.83 |
September | 0.130551E+11 | 28116.18 | 26-SEP-08:61 | 29.83 | 18.30 | 0.683918E+09 | 843.04 | 24-SEP-12:50 | 29.83 | 18.30 |
October | 0.121176E+11 | 30304.13 | 21-OCT-08:62 | 24.83 | 14.71 | 0.706196E+09 | 843.11 | 15-OCT-17:49 | 24.83 | 14.71 |
November | 0.954055E+10 | 28837.02 | 12-NOV-08:62 | 23.17 | 15.91 | 0.682468E+09 | 843.25 | 23-NOV-18:30 | 25.85 | 19.58 |
December | 0.728539E+10 | 26366.53 | 12-DEC-09:02 | 24.07 | 17.73 | 0.708564E+09 | 843.25 | 25-DEC-18:19 | 22.83 | 19.46 |
Annual Sum or Average | 0.124995E+12 | 0.828999E+10 | ||||||||
Minimum of Months | 0.613355E+10 | 15306.54 | 22.17 | 13.62 | 0.636316E+09 | 843.00 | 22.17 | 13.62 | ||
Maximum of Months | 0.146556E+11 | 31733.74 | 35.08 | 22.69 | 0.708564E+09 | 843.26 | 38.60 | 25.83 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.423899E+10 | 16525.75 | 29-JAN-09:02 | 23.22 | 19.02 | 0.419298E+09 | 842.92 | 21-JAN-13:00 | 23.22 | 19.02 |
February | 0.442253E+10 | 18857.66 | 09-FEB-08:62 | 22.17 | 19.26 | 0.381366E+09 | 842.91 | 04-FEB-13:00 | 22.17 | 19.26 |
March | 0.581710E+10 | 31843.04 | 28-MAR-07:02 | 24.33 | 12.69 | 0.431480E+09 | 843.00 | 25-MAR-12:50 | 24.33 | 12.69 |
April | 0.695733E+10 | 30039.26 | 25-APR-07:02 | 25.33 | 14.26 | 0.411373E+09 | 843.02 | 08-APR-12:50 | 25.33 | 14.26 |
May | 0.958087E+10 | 30878.29 | 10-MAY-07:01 | 30.52 | 16.02 | 0.427512E+09 | 842.93 | 27-MAY-12:00 | 34.50 | 22.36 |
June | 0.101545E+11 | 26055.89 | 02-JUN-07:01 | 29.67 | 18.04 | 0.418500E+09 | 843.02 | 03-JUN-12:00 | 39.80 | 23.10 |
July | 0.113433E+11 | 28674.61 | 04-JUL-08:61 | 32.82 | 19.26 | 0.421979E+09 | 843.04 | 29-JUL-12:09 | 39.77 | 23.68 |
August | 0.119623E+11 | 23084.62 | 06-AUG-07:01 | 35.08 | 22.69 | 0.433596E+09 | 842.90 | 26-AUG-12:09 | 37.05 | 27.29 |
September | 0.103891E+11 | 24092.12 | 26-SEP-07:01 | 27.00 | 17.98 | 0.412459E+09 | 843.05 | 30-SEP-12:00 | 36.20 | 24.62 |
October | 0.946723E+10 | 28913.23 | 20-OCT-07:02 | 23.25 | 15.43 | 0.421823E+09 | 842.93 | 28-OCT-12:00 | 33.40 | 20.86 |
November | 0.727149E+10 | 28378.87 | 19-NOV-09:02 | 25.40 | 16.09 | 0.406801E+09 | 842.98 | 04-NOV-12:09 | 25.40 | 16.09 |
December | 0.519666E+10 | 24472.91 | 12-DEC-08:62 | 23.17 | 17.37 | 0.419614E+09 | 842.96 | 30-DEC-13:50 | 25.08 | 14.90 |
Annual Sum or Average | 0.968013E+11 | 0.500580E+10 | ||||||||
Minimum of Months | 0.423899E+10 | 16525.75 | 22.17 | 12.69 | 0.381366E+09 | 842.90 | 22.17 | 12.69 | ||
Maximum of Months | 0.119623E+11 | 31843.04 | 35.08 | 22.69 | 0.433596E+09 | 843.05 | 39.80 | 27.29 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.417324E+10 | 16282.64 | 29-JAN-09:02 | 23.22 | 19.02 | 0.419224E+09 | 842.92 | 21-JAN-13:00 | 23.22 | 19.02 |
February | 0.438403E+10 | 18887.84 | 09-FEB-08:62 | 22.17 | 19.26 | 0.381337E+09 | 842.91 | 04-FEB-13:00 | 22.17 | 19.26 |
March | 0.579872E+10 | 31909.42 | 28-MAR-07:02 | 24.33 | 12.69 | 0.431467E+09 | 843.00 | 25-MAR-12:50 | 24.33 | 12.69 |
April | 0.697975E+10 | 30132.78 | 25-APR-07:02 | 25.33 | 14.26 | 0.411376E+09 | 843.02 | 08-APR-12:50 | 25.33 | 14.26 |
May | 0.967336E+10 | 30931.38 | 10-MAY-07:01 | 30.52 | 16.02 | 0.427522E+09 | 842.93 | 27-MAY-12:00 | 34.50 | 22.36 |
June | 0.102631E+11 | 26131.34 | 02-JUN-07:01 | 29.67 | 18.04 | 0.418509E+09 | 843.03 | 03-JUN-12:00 | 39.80 | 23.10 |
July | 0.114908E+11 | 28757.94 | 04-JUL-08:61 | 32.82 | 19.26 | 0.421991E+09 | 842.90 | 01-JUL-12:09 | 32.82 | 19.26 |
August | 0.121050E+11 | 23351.17 | 06-AUG-07:01 | 35.08 | 22.69 | 0.433608E+09 | 842.90 | 26-AUG-12:09 | 37.05 | 27.29 |
September | 0.105090E+11 | 24177.17 | 26-SEP-07:01 | 27.00 | 17.98 | 0.412469E+09 | 843.05 | 30-SEP-12:00 | 36.20 | 24.62 |
October | 0.956545E+10 | 29027.51 | 20-OCT-07:02 | 23.25 | 15.43 | 0.421836E+09 | 842.93 | 28-OCT-12:00 | 33.40 | 20.86 |
November | 0.730331E+10 | 28461.83 | 19-NOV-09:02 | 25.40 | 16.09 | 0.406807E+09 | 842.98 | 04-NOV-12:09 | 25.40 | 16.09 |
December | 0.516997E+10 | 24518.69 | 12-DEC-08:62 | 23.17 | 17.37 | 0.419597E+09 | 842.96 | 30-DEC-13:50 | 25.08 | 14.90 |
Annual Sum or Average | 0.974158E+11 | 0.500574E+10 | ||||||||
Minimum of Months | 0.417324E+10 | 16282.64 | 22.17 | 12.69 | 0.381337E+09 | 842.90 | 22.17 | 12.69 | ||
Maximum of Months | 0.121050E+11 | 31909.42 | 35.08 | 22.69 | 0.433608E+09 | 843.05 | 39.80 | 27.29 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.400968E+10 | 15231.23 | 29-JAN-09:02 | 23.22 | 19.02 | 0.419077E+09 | 842.92 | 21-JAN-13:00 | 23.22 | 19.02 |
February | 0.424509E+10 | 17802.75 | 09-FEB-08:62 | 22.17 | 19.26 | 0.381264E+09 | 842.91 | 04-FEB-13:00 | 22.17 | 19.26 |
March | 0.564646E+10 | 31819.97 | 28-MAR-07:02 | 24.33 | 12.69 | 0.431406E+09 | 843.00 | 25-MAR-12:50 | 24.33 | 12.69 |
April | 0.685210E+10 | 29984.12 | 25-APR-07:02 | 25.33 | 14.26 | 0.411342E+09 | 843.02 | 08-APR-12:39 | 25.33 | 14.26 |
May | 0.957663E+10 | 30878.31 | 10-MAY-07:01 | 30.52 | 16.02 | 0.427498E+09 | 842.93 | 27-MAY-12:00 | 34.50 | 22.36 |
June | 0.101698E+11 | 26051.51 | 02-JUN-07:01 | 29.67 | 18.04 | 0.418487E+09 | 843.02 | 03-JUN-12:00 | 39.80 | 23.10 |
July | 0.114218E+11 | 28701.30 | 04-JUL-08:61 | 32.82 | 19.26 | 0.421971E+09 | 843.03 | 29-JUL-12:09 | 39.77 | 23.68 |
August | 0.120310E+11 | 23245.01 | 06-AUG-07:01 | 35.08 | 22.69 | 0.433587E+09 | 842.90 | 26-AUG-12:09 | 37.05 | 27.29 |
September | 0.104305E+11 | 24073.28 | 26-SEP-07:01 | 27.00 | 17.98 | 0.412448E+09 | 843.04 | 30-SEP-12:00 | 36.20 | 24.62 |
October | 0.947640E+10 | 28889.02 | 20-OCT-07:02 | 23.25 | 15.43 | 0.421809E+09 | 842.94 | 28-OCT-12:00 | 33.40 | 20.86 |
November | 0.719275E+10 | 28333.63 | 19-NOV-09:02 | 25.40 | 16.09 | 0.406775E+09 | 842.99 | 04-NOV-12:09 | 25.40 | 16.09 |
December | 0.502520E+10 | 24386.94 | 12-DEC-08:62 | 23.17 | 17.37 | 0.419540E+09 | 842.96 | 30-DEC-13:50 | 25.08 | 14.90 |
Annual Sum or Average | 0.960774E+11 | 0.500520E+10 | ||||||||
Minimum of Months | 0.400968E+10 | 15231.23 | 22.17 | 12.69 | 0.381264E+09 | 842.90 | 22.17 | 12.69 | ||
Maximum of Months | 0.120310E+11 | 31819.97 | 35.08 | 22.69 | 0.433587E+09 | 843.04 | 39.80 | 27.29 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.705036E+10 | 43311.08 | 29-JAN-10:02 | 24.58 | 19.01 | 0.143255E+10 | 2247.99 | 28-JAN-15:09 | 24.58 | 19.01 |
February | 0.754299E+10 | 49407.12 | 05-FEB-10:02 | 27.58 | 18.59 | 0.130564E+10 | 2247.97 | 04-FEB-15:00 | 27.58 | 18.59 |
March | 0.101527E+11 | 58447.13 | 28-MAR-08:61 | 26.03 | 13.62 | 0.147968E+10 | 2247.80 | 11-MAR-15:00 | 26.03 | 13.62 |
April | 0.123189E+11 | 56917.03 | 27-APR-08:61 | 29.83 | 15.29 | 0.141168E+10 | 2248.10 | 22-APR-14:09 | 29.83 | 15.29 |
May | 0.172674E+11 | 54595.77 | 11-MAY-08:61 | 33.67 | 17.81 | 0.146114E+10 | 2247.88 | 27-MAY-14:00 | 35.00 | 21.99 |
June | 0.183801E+11 | 51460.26 | 02-JUN-08:61 | 33.67 | 17.87 | 0.143313E+10 | 2247.81 | 24-JUN-14:09 | 36.00 | 27.04 |
July | 0.206381E+11 | 50416.84 | 04-JUL-09:01 | 34.72 | 21.09 | 0.144261E+10 | 2247.81 | 08-JUL-14:00 | 35.00 | 26.74 |
August | 0.218149E+11 | 44394.15 | 16-AUG-07:01 | 33.67 | 25.11 | 0.148372E+10 | 2247.81 | 26-AUG-14:00 | 36.00 | 27.58 |
September | 0.188499E+11 | 48127.90 | 26-SEP-08:61 | 29.83 | 18.30 | 0.141389E+10 | 2247.88 | 16-SEP-14:09 | 29.83 | 18.30 |
October | 0.171465E+11 | 53890.99 | 20-OCT-08:61 | 25.67 | 16.61 | 0.143876E+10 | 2247.96 | 28-OCT-14:00 | 32.00 | 20.74 |
November | 0.129397E+11 | 55982.58 | 19-NOV-10:01 | 27.67 | 16.16 | 0.138418E+10 | 2247.98 | 04-NOV-14:09 | 27.67 | 16.16 |
December | 0.893010E+10 | 46595.76 | 12-DEC-09:02 | 24.07 | 17.73 | 0.143732E+10 | 2247.93 | 30-DEC-15:09 | 24.83 | 13.98 |
Annual Sum or Average | 0.173032E+12 | 0.171243E+11 | ||||||||
Minimum of Months | 0.705036E+10 | 43311.08 | 24.07 | 13.62 | 0.130564E+10 | 2247.80 | 24.58 | 13.62 | ||
Maximum of Months | 0.218149E+11 | 58447.13 | 34.72 | 25.11 | 0.148372E+10 | 2248.10 | 36.00 | 27.58 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.362025E+10 | 22786.39 | 29-JAN-10:02 | 24.58 | 19.01 | 0.716290E+09 | 1123.96 | 28-JAN-15:09 | 24.58 | 19.01 |
February | 0.390085E+10 | 25996.75 | 05-FEB-10:02 | 27.58 | 18.59 | 0.652817E+09 | 1123.96 | 04-FEB-15:00 | 27.58 | 18.59 |
March | 0.529133E+10 | 30798.87 | 28-MAR-08:61 | 26.03 | 13.62 | 0.739826E+09 | 1123.87 | 11-MAR-15:00 | 26.03 | 13.62 |
April | 0.648505E+10 | 29933.99 | 27-APR-08:61 | 29.83 | 15.29 | 0.705808E+09 | 1124.02 | 22-APR-14:00 | 29.83 | 15.29 |
May | 0.914205E+10 | 28876.05 | 11-MAY-08:61 | 33.67 | 17.81 | 0.730531E+09 | 1123.91 | 27-MAY-14:00 | 35.00 | 21.99 |
June | 0.972674E+10 | 27162.04 | 02-JUN-08:61 | 33.67 | 17.87 | 0.716526E+09 | 1123.87 | 24-JUN-14:00 | 36.00 | 27.58 |
July | 0.109292E+11 | 26690.08 | 04-JUL-09:01 | 34.72 | 21.09 | 0.721262E+09 | 1123.87 | 08-JUL-14:00 | 35.00 | 26.74 |
August | 0.115329E+11 | 23401.86 | 16-AUG-07:01 | 33.67 | 25.11 | 0.741819E+09 | 1123.87 | 26-AUG-14:00 | 36.00 | 27.58 |
September | 0.996666E+10 | 25404.00 | 26-SEP-08:61 | 29.83 | 18.30 | 0.706900E+09 | 1124.07 | 16-SEP-14:20 | 29.83 | 18.30 |
October | 0.905244E+10 | 28388.79 | 20-OCT-08:61 | 25.67 | 16.61 | 0.719340E+09 | 1123.95 | 28-OCT-14:00 | 32.00 | 20.74 |
November | 0.680073E+10 | 29475.12 | 19-NOV-10:01 | 27.67 | 16.16 | 0.692056E+09 | 1123.96 | 04-NOV-14:09 | 27.67 | 16.16 |
December | 0.463545E+10 | 24568.45 | 12-DEC-09:02 | 24.07 | 17.73 | 0.718648E+09 | 1123.93 | 30-DEC-15:09 | 24.83 | 13.98 |
Annual Sum or Average | 0.910837E+11 | 0.856182E+10 | ||||||||
Minimum of Months | 0.362025E+10 | 22786.39 | 24.07 | 13.62 | 0.652817E+09 | 1123.87 | 24.58 | 13.62 | ||
Maximum of Months | 0.115329E+11 | 30798.87 | 34.72 | 25.11 | 0.741819E+09 | 1124.07 | 36.00 | 27.58 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.357017E+10 | 22687.14 | 29-JAN-10:02 | 24.58 | 19.01 | 0.716238E+09 | 1123.96 | 28-JAN-15:09 | 24.58 | 19.01 |
February | 0.385355E+10 | 25881.50 | 05-FEB-10:02 | 27.58 | 18.59 | 0.652788E+09 | 1123.96 | 04-FEB-15:00 | 27.58 | 18.59 |
March | 0.523775E+10 | 30691.08 | 28-MAR-08:61 | 26.03 | 13.62 | 0.739806E+09 | 1123.87 | 11-MAR-15:00 | 26.03 | 13.62 |
April | 0.643841E+10 | 29809.65 | 27-APR-08:61 | 29.83 | 15.29 | 0.705796E+09 | 1124.02 | 22-APR-14:00 | 29.83 | 15.29 |
May | 0.909925E+10 | 28782.22 | 11-MAY-08:61 | 33.67 | 17.81 | 0.730524E+09 | 1123.91 | 27-MAY-14:00 | 35.00 | 21.99 |
June | 0.968478E+10 | 27069.99 | 02-JUN-08:61 | 33.67 | 17.87 | 0.716518E+09 | 1123.87 | 24-JUN-14:09 | 36.00 | 27.04 |
July | 0.108907E+11 | 26598.80 | 04-JUL-09:01 | 34.72 | 21.09 | 0.721257E+09 | 1123.87 | 08-JUL-14:00 | 35.00 | 26.74 |
August | 0.114944E+11 | 23305.54 | 16-AUG-07:01 | 33.67 | 25.11 | 0.741816E+09 | 1123.87 | 26-AUG-14:00 | 36.00 | 27.58 |
September | 0.992860E+10 | 25320.39 | 26-SEP-08:61 | 29.83 | 18.30 | 0.706892E+09 | 1124.05 | 16-SEP-14:09 | 29.83 | 18.30 |
October | 0.901553E+10 | 28281.91 | 20-OCT-08:61 | 25.67 | 16.61 | 0.719332E+09 | 1123.95 | 28-OCT-14:00 | 32.00 | 20.74 |
November | 0.676199E+10 | 29379.67 | 19-NOV-10:01 | 27.67 | 16.16 | 0.692049E+09 | 1123.96 | 04-NOV-14:09 | 27.67 | 16.16 |
December | 0.458996E+10 | 24477.65 | 12-DEC-09:02 | 24.07 | 17.73 | 0.718629E+09 | 1123.93 | 30-DEC-15:09 | 24.83 | 13.98 |
Annual Sum or Average | 0.905651E+11 | 0.856164E+10 | ||||||||
Minimum of Months | 0.357017E+10 | 22687.14 | 24.07 | 13.62 | 0.652788E+09 | 1123.87 | 24.58 | 13.62 | ||
Maximum of Months | 0.114944E+11 | 30691.08 | 34.72 | 25.11 | 0.741816E+09 | 1124.05 | 36.00 | 27.58 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.345366E+10 | 22672.68 | 29-JAN-10:02 | 24.58 | 19.01 | 0.716052E+09 | 1123.96 | 28-JAN-15:09 | 24.58 | 19.01 |
February | 0.374871E+10 | 25871.63 | 05-FEB-10:02 | 27.58 | 18.59 | 0.652685E+09 | 1123.96 | 04-FEB-15:00 | 27.58 | 18.59 |
March | 0.513436E+10 | 30781.41 | 28-MAR-08:61 | 26.03 | 13.62 | 0.739739E+09 | 1123.87 | 11-MAR-15:00 | 26.03 | 13.62 |
April | 0.638783E+10 | 29869.12 | 27-APR-08:61 | 29.83 | 15.29 | 0.705772E+09 | 1123.93 | 29-APR-14:00 | 34.00 | 22.91 |
May | 0.913408E+10 | 28896.36 | 11-MAY-08:61 | 33.67 | 17.81 | 0.730525E+09 | 1123.91 | 27-MAY-14:00 | 35.00 | 21.99 |
June | 0.975266E+10 | 27173.19 | 02-JUN-08:61 | 33.67 | 17.87 | 0.716525E+09 | 1123.87 | 24-JUN-14:00 | 36.00 | 27.58 |
July | 0.110081E+11 | 26720.74 | 04-JUL-09:01 | 34.72 | 21.09 | 0.721265E+09 | 1123.87 | 08-JUL-14:00 | 35.00 | 26.74 |
August | 0.116452E+11 | 23489.15 | 16-AUG-07:01 | 33.67 | 25.11 | 0.741822E+09 | 1123.87 | 26-AUG-14:00 | 36.00 | 27.58 |
September | 0.100368E+11 | 25424.80 | 26-SEP-08:61 | 29.83 | 18.30 | 0.706903E+09 | 1124.06 | 16-SEP-14:09 | 29.83 | 18.30 |
October | 0.908689E+10 | 28379.72 | 20-OCT-08:61 | 25.67 | 16.61 | 0.719337E+09 | 1123.95 | 28-OCT-14:00 | 32.00 | 20.74 |
November | 0.676848E+10 | 29487.49 | 19-NOV-10:01 | 27.67 | 16.16 | 0.692039E+09 | 1123.96 | 04-NOV-14:09 | 27.67 | 16.16 |
December | 0.451341E+10 | 24489.19 | 12-DEC-09:02 | 24.07 | 17.73 | 0.718576E+09 | 1123.93 | 30-DEC-15:09 | 24.83 | 13.98 |
Annual Sum or Average | 0.906701E+11 | 0.856124E+10 | ||||||||
Minimum of Months | 0.345366E+10 | 22672.68 | 24.07 | 13.62 | 0.652685E+09 | 1123.87 | 24.58 | 13.62 | ||
Maximum of Months | 0.116452E+11 | 30781.41 | 34.72 | 25.11 | 0.741822E+09 | 1124.06 | 36.00 | 27.58 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.361458E+10 | 25212.94 | 29-JAN-10:02 | 24.58 | 19.01 | 0.715791E+09 | 1123.95 | 28-JAN-15:09 | 24.58 | 19.01 |
February | 0.393356E+10 | 28933.65 | 05-FEB-10:02 | 27.58 | 18.59 | 0.652508E+09 | 1123.96 | 04-FEB-15:00 | 27.58 | 18.59 |
March | 0.547900E+10 | 34087.62 | 28-MAR-08:61 | 26.03 | 13.62 | 0.739612E+09 | 1123.87 | 04-MAR-15:09 | 26.03 | 13.62 |
April | 0.711849E+10 | 33538.58 | 27-APR-08:61 | 29.83 | 15.29 | 0.705854E+09 | 1123.94 | 29-APR-14:00 | 34.00 | 22.91 |
May | 0.105774E+11 | 32208.37 | 11-MAY-08:61 | 33.67 | 17.81 | 0.730656E+09 | 1123.93 | 27-MAY-14:00 | 35.00 | 21.99 |
June | 0.114279E+11 | 30324.85 | 02-JUN-08:61 | 33.67 | 17.87 | 0.716653E+09 | 1123.87 | 03-JUN-14:09 | 38.67 | 24.77 |
July | 0.130259E+11 | 32356.14 | 04-JUL-08:61 | 32.82 | 19.26 | 0.721405E+09 | 1123.87 | 08-JUL-14:00 | 35.00 | 26.74 |
August | 0.139865E+11 | 26683.87 | 06-AUG-08:61 | 36.17 | 23.08 | 0.741930E+09 | 1123.87 | 26-AUG-14:00 | 36.00 | 27.58 |
September | 0.119368E+11 | 28423.69 | 26-SEP-08:61 | 29.83 | 18.30 | 0.707074E+09 | 1124.09 | 16-SEP-14:39 | 29.83 | 18.30 |
October | 0.106819E+11 | 31709.88 | 20-OCT-08:61 | 25.67 | 16.61 | 0.719525E+09 | 1123.96 | 28-OCT-14:00 | 32.00 | 20.74 |
November | 0.778088E+10 | 32540.70 | 19-NOV-10:01 | 27.67 | 16.16 | 0.692192E+09 | 1123.97 | 04-NOV-14:09 | 27.67 | 16.16 |
December | 0.488733E+10 | 26938.55 | 12-DEC-09:02 | 24.07 | 17.73 | 0.718586E+09 | 1123.93 | 30-DEC-15:09 | 24.83 | 13.98 |
Annual Sum or Average | 0.104450E+12 | 0.856179E+10 | ||||||||
Minimum of Months | 0.361458E+10 | 25212.94 | 24.07 | 13.62 | 0.652508E+09 | 1123.87 | 24.58 | 13.62 | ||
Maximum of Months | 0.139865E+11 | 34087.62 | 36.17 | 23.08 | 0.741930E+09 | 1124.09 | 38.67 | 27.58 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1298514.13 | 1404.97 | 29-JAN-08:05 | 22.17 |
February | 6138723.35 | 2846.60 | 07-FEB-09:05 | 24.33 |
March | 35646048.50 | 4907.42 | 27-MAR-08:04 | 29.17 |
April | 82469847.96 | 6931.46 | 28-APR-08:04 | 32.67 |
May | 87306773.21 | 9607.42 | 10-MAY-08:04 | 38.25 |
June | 33203762.17 | 7462.68 | 02-JUN-08:04 | 33.67 |
July | 31667006.23 | 7440.92 | 19-JUL-08:06 | 36.50 |
August | 35030195.73 | 8040.95 | 02-AUG-08:05 | 36.73 |
September | 34004885.11 | 7302.85 | 30-SEP-08:05 | 35.47 |
October | 42709438.59 | 5657.22 | 06-OCT-08:06 | 31.75 |
November | 42032841.94 | 4010.71 | 20-NOV-09:04 | 27.02 |
December | 6102362.27 | 2556.97 | 01-DEC-09:05 | 24.23 |
Annual Sum or Average | 0.437610E+09 | |||
Minimum of Months | 1298514.13 | 1404.97 | 22.17 | |
Maximum of Months | 87306773.21 | 9607.42 | 38.25 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 634555.06 | 816.74 | 29-JAN-08:05 | 22.17 |
February | 2962415.36 | 1492.06 | 07-FEB-09:05 | 24.33 |
March | 16830613.35 | 2499.75 | 27-MAR-08:04 | 29.17 |
April | 37943628.03 | 3458.21 | 28-APR-08:04 | 32.67 |
May | 38943974.42 | 4787.63 | 10-MAY-08:04 | 38.25 |
June | 16290820.22 | 3744.97 | 02-JUN-08:04 | 33.67 |
July | 16873219.72 | 4176.32 | 21-JUL-08:04 | 36.33 |
August | 16649154.23 | 3669.30 | 10-AUG-08:06 | 35.33 |
September | 14747987.62 | 2809.99 | 04-SEP-07:04 | 31.55 |
October | 22821289.85 | 2552.33 | 04-OCT-08:04 | 29.33 |
November | 21168563.00 | 2070.57 | 09-NOV-09:04 | 27.48 |
December | 3311961.94 | 1338.89 | 01-DEC-09:05 | 24.23 |
Annual Sum or Average | 0.209178E+09 | |||
Minimum of Months | 634555.06 | 816.74 | 22.17 | |
Maximum of Months | 38943974.42 | 4787.63 | 38.25 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1526880.10 | 1071.15 | 29-JAN-09:05 | 23.22 |
February | 9828896.04 | 1933.78 | 05-FEB-17:12 | 31.00 |
March | 38428638.13 | 2189.20 | 27-MAR-19:12 | 31.67 |
April | 0.107072E+09 | 2590.02 | 29-APR-17:02 | 33.67 |
May | 0.226787E+09 | 4600.20 | 31-MAY-19:02 | 41.85 |
June | 0.232418E+09 | 3787.86 | 09-JUN-19:02 | 38.25 |
July | 0.284197E+09 | 4388.20 | 21-JUL-19:02 | 41.00 |
August | 0.298101E+09 | 4405.01 | 10-AUG-19:02 | 40.92 |
September | 0.216408E+09 | 4285.00 | 04-SEP-16:01 | 40.58 |
October | 0.170517E+09 | 3307.40 | 09-OCT-16:01 | 36.67 |
November | 75204979.31 | 2009.90 | 05-NOV-16:02 | 31.33 |
December | 10330049.48 | 1265.15 | 10-DEC-09:05 | 23.60 |
Annual Sum or Average | 0.167082E+10 | |||
Minimum of Months | 1526880.10 | 1071.15 | 23.22 | |
Maximum of Months | 0.298101E+09 | 4600.20 | 41.85 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1557171.38 | 1061.04 | 29-JAN-09:05 | 23.22 |
February | 9911986.29 | 1936.01 | 05-FEB-17:12 | 31.00 |
March | 38536702.69 | 2189.95 | 27-MAR-19:12 | 31.67 |
April | 0.106637E+09 | 2589.31 | 29-APR-17:02 | 33.67 |
May | 0.224294E+09 | 4598.53 | 31-MAY-19:02 | 41.85 |
June | 0.231179E+09 | 3787.33 | 09-JUN-19:02 | 38.25 |
July | 0.284304E+09 | 4386.72 | 21-JUL-19:02 | 41.00 |
August | 0.298186E+09 | 4404.25 | 10-AUG-19:02 | 40.92 |
September | 0.215258E+09 | 4280.38 | 04-SEP-16:01 | 40.58 |
October | 0.168278E+09 | 3303.58 | 09-OCT-16:01 | 36.67 |
November | 74701917.28 | 2008.33 | 05-NOV-16:02 | 31.33 |
December | 10398233.25 | 1259.00 | 10-DEC-09:05 | 23.60 |
Annual Sum or Average | 0.166324E+10 | |||
Minimum of Months | 1557171.38 | 1061.04 | 23.22 | |
Maximum of Months | 0.298186E+09 | 4598.53 | 41.85 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1636829.88 | 1011.49 | 29-JAN-09:05 | 23.22 |
February | 10171210.20 | 1939.81 | 05-FEB-17:12 | 31.00 |
March | 40324718.41 | 2192.91 | 27-MAR-19:12 | 31.67 |
April | 0.108520E+09 | 2594.43 | 29-APR-17:02 | 33.67 |
May | 0.229401E+09 | 4601.56 | 31-MAY-19:02 | 41.85 |
June | 0.232852E+09 | 3791.32 | 09-JUN-19:02 | 38.25 |
July | 0.283966E+09 | 4390.50 | 21-JUL-19:02 | 41.00 |
August | 0.298663E+09 | 4407.94 | 10-AUG-19:02 | 40.92 |
September | 0.216859E+09 | 4280.82 | 04-SEP-16:01 | 40.58 |
October | 0.172187E+09 | 3304.57 | 09-OCT-16:01 | 36.67 |
November | 76382312.55 | 2011.64 | 05-NOV-16:02 | 31.33 |
December | 10802797.19 | 1213.21 | 10-DEC-09:05 | 23.60 |
Annual Sum or Average | 0.168177E+10 | |||
Minimum of Months | 1636829.88 | 1011.49 | 23.22 | |
Maximum of Months | 0.298663E+09 | 4601.56 | 41.85 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4502445.39 | 2664.46 | 29-JAN-10:04 | 24.58 |
February | 25381050.88 | 3887.47 | 05-FEB-17:02 | 31.00 |
March | 57886645.19 | 5051.57 | 27-MAR-08:04 | 29.17 |
April | 0.175055E+09 | 6665.07 | 28-APR-08:04 | 32.67 |
May | 0.186409E+09 | 9095.51 | 10-MAY-08:04 | 38.25 |
June | 0.144294E+09 | 7257.84 | 18-JUN-09:05 | 35.27 |
July | 0.187949E+09 | 8427.79 | 29-JUL-17:01 | 40.00 |
August | 0.136528E+09 | 8836.21 | 05-AUG-17:01 | 40.83 |
September | 0.152960E+09 | 8608.88 | 04-SEP-16:01 | 40.58 |
October | 0.148565E+09 | 6649.98 | 09-OCT-16:01 | 36.67 |
November | 90002191.58 | 4294.11 | 19-NOV-10:04 | 27.67 |
December | 20405973.96 | 3719.51 | 10-DEC-10:04 | 27.00 |
Annual Sum or Average | 0.132994E+10 | |||
Minimum of Months | 4502445.39 | 2664.46 | 24.58 | |
Maximum of Months | 0.187949E+09 | 9095.51 | 40.83 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2644637.24 | 1443.42 | 29-JAN-10:04 | 24.58 |
February | 13088298.79 | 1931.66 | 05-FEB-17:02 | 31.00 |
March | 29771667.03 | 2514.16 | 27-MAR-08:04 | 29.17 |
April | 90154586.28 | 3434.44 | 28-APR-08:04 | 32.67 |
May | 0.101462E+09 | 4690.01 | 10-MAY-08:04 | 38.25 |
June | 78435247.38 | 3641.41 | 02-JUN-08:04 | 33.67 |
July | 96587604.71 | 4212.38 | 29-JUL-17:01 | 40.00 |
August | 69777067.16 | 4414.84 | 05-AUG-17:01 | 40.83 |
September | 82289895.23 | 4283.14 | 04-SEP-16:01 | 40.58 |
October | 78582435.49 | 3308.01 | 09-OCT-16:01 | 36.67 |
November | 48194424.31 | 2262.59 | 19-NOV-10:04 | 27.67 |
December | 10834999.30 | 1847.35 | 10-DEC-10:04 | 27.00 |
Annual Sum or Average | 0.701823E+09 | |||
Minimum of Months | 2644637.24 | 1443.42 | 24.58 | |
Maximum of Months | 0.101462E+09 | 4690.01 | 40.83 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2684198.62 | 1439.74 | 29-JAN-10:04 | 24.58 |
February | 13148019.83 | 1933.64 | 05-FEB-17:02 | 31.00 |
March | 29956368.05 | 2502.36 | 27-MAR-08:04 | 29.17 |
April | 90975260.32 | 3432.29 | 28-APR-08:04 | 32.67 |
May | 0.102558E+09 | 4680.22 | 10-MAY-08:04 | 38.25 |
June | 78336567.69 | 3631.65 | 18-JUN-09:05 | 35.27 |
July | 96058378.78 | 4213.64 | 29-JUL-17:01 | 40.00 |
August | 69719687.00 | 4416.15 | 05-AUG-17:01 | 40.83 |
September | 80023471.64 | 4283.87 | 04-SEP-16:01 | 40.58 |
October | 78913886.52 | 3308.80 | 09-OCT-16:01 | 36.67 |
November | 49356300.10 | 2260.16 | 19-NOV-10:04 | 27.67 |
December | 10899789.54 | 1834.72 | 10-DEC-10:04 | 27.00 |
Annual Sum or Average | 0.702630E+09 | |||
Minimum of Months | 2684198.62 | 1439.74 | 24.58 | |
Maximum of Months | 0.102558E+09 | 4680.22 | 40.83 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2870223.41 | 1468.93 | 29-JAN-10:04 | 24.58 |
February | 13547964.65 | 2064.30 | 05-FEB-10:03 | 27.58 |
March | 30666964.50 | 2470.50 | 27-MAR-08:04 | 29.17 |
April | 92931057.09 | 3433.85 | 28-APR-08:04 | 32.67 |
May | 0.104481E+09 | 4696.49 | 10-MAY-08:04 | 38.25 |
June | 78091266.76 | 3658.25 | 02-JUN-08:04 | 33.67 |
July | 95661800.13 | 4211.17 | 29-JUL-17:01 | 40.00 |
August | 70406534.99 | 4412.07 | 05-AUG-17:01 | 40.83 |
September | 82501141.78 | 4279.89 | 04-SEP-16:01 | 40.58 |
October | 78713928.51 | 3305.87 | 09-OCT-16:01 | 36.67 |
November | 49484915.31 | 2262.64 | 19-NOV-10:04 | 27.67 |
December | 11198407.03 | 1808.79 | 10-DEC-10:04 | 27.00 |
Annual Sum or Average | 0.710556E+09 | |||
Minimum of Months | 2870223.41 | 1468.93 | 24.58 | |
Maximum of Months | 0.104481E+09 | 4696.49 | 40.83 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3381780.96 | 1733.89 | 29-JAN-10:04 | 24.58 |
February | 15118141.25 | 2395.79 | 05-FEB-10:03 | 27.58 |
March | 34222569.56 | 2457.86 | 27-MAR-08:04 | 29.17 |
April | 96359630.46 | 3505.82 | 28-APR-08:04 | 32.67 |
May | 93297893.85 | 4963.28 | 10-MAY-08:04 | 38.25 |
June | 67683606.03 | 3838.58 | 02-JUN-08:04 | 33.67 |
July | 81940068.17 | 4152.16 | 29-JUL-17:01 | 40.00 |
August | 56212710.14 | 4332.36 | 05-AUG-17:01 | 40.83 |
September | 66491722.89 | 4211.08 | 04-SEP-16:01 | 40.58 |
October | 65928218.31 | 3248.63 | 09-OCT-16:01 | 36.67 |
November | 47284504.34 | 2496.55 | 11-NOV-10:04 | 28.25 |
December | 11755963.58 | 1912.03 | 10-DEC-10:04 | 27.00 |
Annual Sum or Average | 0.639677E+09 | |||
Minimum of Months | 3381780.96 | 1733.89 | 24.58 | |
Maximum of Months | 96359630.46 | 4963.28 | 40.83 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.869933E+10 | 5321.43 | 01-JAN-10:09 | 0.223514E+10 | 1348.26 | 01-JAN-10:09 |
February | 0.786449E+10 | 5321.43 | 01-FEB-10:09 | 0.202238E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.870841E+10 | 5321.43 | 01-MAR-10:09 | 0.224215E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.843013E+10 | 5321.43 | 01-APR-09:09 | 0.216638E+10 | 1348.26 | 01-APR-09:09 |
May | 0.869933E+10 | 5321.43 | 01-MAY-09:09 | 0.223514E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.843013E+10 | 5321.43 | 01-JUN-09:09 | 0.217123E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.870841E+10 | 5321.43 | 01-JUL-09:09 | 0.223729E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.869933E+10 | 5321.43 | 01-AUG-09:09 | 0.223756E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.843920E+10 | 5321.43 | 01-SEP-09:09 | 0.217096E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.869933E+10 | 5321.43 | 01-OCT-09:09 | 0.223514E+10 | 1348.26 | 01-OCT-09:09 |
November | 0.840290E+10 | 5321.43 | 01-NOV-09:09 | 0.215964E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.871748E+10 | 5321.43 | 01-DEC-10:09 | 0.224431E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.102498E+12 | 0.263573E+11 | ||||
Minimum of Months | 0.786449E+10 | 5321.43 | 0.202238E+10 | 1348.26 | ||
Maximum of Months | 0.871748E+10 | 5321.43 | 0.224431E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.479410E+10 | 2932.57 | 01-JAN-10:09 | 0.111757E+10 | 674.13 | 01-JAN-10:09 |
February | 0.433403E+10 | 2932.57 | 01-FEB-10:09 | 0.101119E+10 | 674.13 | 01-FEB-10:09 |
March | 0.479910E+10 | 2932.57 | 01-MAR-10:09 | 0.112107E+10 | 674.13 | 01-MAR-10:09 |
April | 0.464574E+10 | 2932.57 | 01-APR-09:09 | 0.108319E+10 | 674.13 | 01-APR-09:09 |
May | 0.479410E+10 | 2932.57 | 01-MAY-09:09 | 0.111757E+10 | 674.13 | 01-MAY-09:09 |
June | 0.464574E+10 | 2932.57 | 01-JUN-09:09 | 0.108562E+10 | 674.13 | 01-JUN-09:09 |
July | 0.479910E+10 | 2932.57 | 01-JUL-09:09 | 0.111865E+10 | 674.13 | 01-JUL-09:09 |
August | 0.479410E+10 | 2932.57 | 01-AUG-09:09 | 0.111878E+10 | 674.13 | 01-AUG-09:09 |
September | 0.465074E+10 | 2932.57 | 01-SEP-09:09 | 0.108548E+10 | 674.13 | 01-SEP-09:09 |
October | 0.479410E+10 | 2932.57 | 01-OCT-09:09 | 0.111757E+10 | 674.13 | 01-OCT-09:09 |
November | 0.463074E+10 | 2932.57 | 01-NOV-09:09 | 0.107982E+10 | 674.13 | 01-NOV-09:09 |
December | 0.480410E+10 | 2932.57 | 01-DEC-10:09 | 0.112215E+10 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.564857E+11 | 0.131787E+11 | ||||
Minimum of Months | 0.433403E+10 | 2932.57 | 0.101119E+10 | 674.13 | ||
Maximum of Months | 0.480410E+10 | 2932.57 | 0.112215E+10 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.338042E+10 | 2599.23 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.306129E+10 | 2599.23 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.345133E+10 | 2599.23 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.327995E+10 | 2599.23 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.341588E+10 | 2599.23 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.333314E+10 | 2599.23 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.336269E+10 | 2599.23 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.345133E+10 | 2599.23 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.327995E+10 | 2599.23 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.338042E+10 | 2599.23 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.327995E+10 | 2599.23 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.336269E+10 | 2599.23 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.400390E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.306129E+10 | 2599.23 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.345133E+10 | 2599.23 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.338042E+10 | 2599.23 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.306129E+10 | 2599.23 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.345133E+10 | 2599.23 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.327995E+10 | 2599.23 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.341588E+10 | 2599.23 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.333314E+10 | 2599.23 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.336269E+10 | 2599.23 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.345133E+10 | 2599.23 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.327995E+10 | 2599.23 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.338042E+10 | 2599.23 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.327995E+10 | 2599.23 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.336269E+10 | 2599.23 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.400390E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.306129E+10 | 2599.23 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.345133E+10 | 2599.23 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.338042E+10 | 2599.23 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.306129E+10 | 2599.23 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.345133E+10 | 2599.23 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.327995E+10 | 2599.23 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.341588E+10 | 2599.23 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.333314E+10 | 2599.23 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.336269E+10 | 2599.23 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.345133E+10 | 2599.23 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.327995E+10 | 2599.23 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.338042E+10 | 2599.23 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.327995E+10 | 2599.23 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.336269E+10 | 2599.23 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.400390E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.306129E+10 | 2599.23 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.345133E+10 | 2599.23 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.447638E+10 | 3746.51 | 01-JAN-11:09 | 0.162546E+10 | 1348.26 | 01-JAN-11:09 |
February | 0.405472E+10 | 3746.51 | 01-FEB-10:09 | 0.147229E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.457860E+10 | 3746.51 | 01-MAR-10:09 | 0.166213E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.434435E+10 | 3746.51 | 01-APR-09:09 | 0.157746E+10 | 1348.26 | 01-APR-09:09 |
May | 0.452749E+10 | 3746.51 | 01-MAY-09:09 | 0.164379E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.442101E+10 | 3746.51 | 01-JUN-09:09 | 0.160496E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.445083E+10 | 3746.51 | 01-JUL-09:09 | 0.161629E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.457860E+10 | 3746.51 | 01-AUG-09:09 | 0.166213E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.434435E+10 | 3746.51 | 01-SEP-09:09 | 0.157746E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.447638E+10 | 3746.51 | 01-OCT-10:09 | 0.162546E+10 | 1348.26 | 01-OCT-10:09 |
November | 0.434435E+10 | 3746.51 | 01-NOV-09:09 | 0.157746E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.445083E+10 | 3746.51 | 01-DEC-10:09 | 0.161629E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.530479E+11 | 0.192612E+11 | ||||
Minimum of Months | 0.405472E+10 | 3746.51 | 0.147229E+10 | 1348.26 | ||
Maximum of Months | 0.457860E+10 | 3746.51 | 0.166213E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.230731E+10 | 1931.10 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.208997E+10 | 1931.10 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.236000E+10 | 1931.10 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.223926E+10 | 1931.10 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.233366E+10 | 1931.10 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.227877E+10 | 1931.10 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.229414E+10 | 1931.10 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.236000E+10 | 1931.10 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.223926E+10 | 1931.10 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.230731E+10 | 1931.10 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.223926E+10 | 1931.10 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.229414E+10 | 1931.10 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.273431E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.208997E+10 | 1931.10 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.236000E+10 | 1931.10 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.230731E+10 | 1931.10 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.208997E+10 | 1931.10 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.236000E+10 | 1931.10 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.223926E+10 | 1931.10 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.233366E+10 | 1931.10 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.227877E+10 | 1931.10 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.229414E+10 | 1931.10 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.236000E+10 | 1931.10 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.223926E+10 | 1931.10 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.230731E+10 | 1931.10 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.223926E+10 | 1931.10 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.229414E+10 | 1931.10 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.273431E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.208997E+10 | 1931.10 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.236000E+10 | 1931.10 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.230731E+10 | 1931.10 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.208997E+10 | 1931.10 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.236000E+10 | 1931.10 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.223926E+10 | 1931.10 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.233366E+10 | 1931.10 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.227877E+10 | 1931.10 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.229414E+10 | 1931.10 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.236000E+10 | 1931.10 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.223926E+10 | 1931.10 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.230731E+10 | 1931.10 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.223926E+10 | 1931.10 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.229414E+10 | 1931.10 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.273431E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.208997E+10 | 1931.10 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.236000E+10 | 1931.10 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.230731E+10 | 1931.10 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.208997E+10 | 1931.10 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.236000E+10 | 1931.10 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.223926E+10 | 1931.10 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.233366E+10 | 1931.10 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.227877E+10 | 1931.10 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.229414E+10 | 1931.10 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.236000E+10 | 1931.10 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.223926E+10 | 1931.10 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.230731E+10 | 1931.10 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.223926E+10 | 1931.10 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.229414E+10 | 1931.10 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.273431E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.208997E+10 | 1931.10 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.236000E+10 | 1931.10 | 0.831065E+09 | 674.13 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.869933E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75447505.49 | 0.836679E+09 |
February | 0.305697E+10 | 0.786449E+10 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402061E+09 | 0.603628E+09 |
March | 0.335708E+10 | 0.870841E+10 | 0.224215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104470E+10 | 0.263750E+09 |
April | 0.327081E+10 | 0.843013E+10 | 0.216638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230830E+10 | 78908692.07 |
May | 0.336680E+10 | 0.869933E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.408894E+10 | 10096532.27 |
June | 0.325380E+10 | 0.843013E+10 | 0.217123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.449280E+10 | 3135164.75 |
July | 0.339353E+10 | 0.870841E+10 | 0.223729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.523288E+10 | 0.00 |
August | 0.334857E+10 | 0.869933E+10 | 0.223756E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.527007E+10 | 0.00 |
September | 0.327932E+10 | 0.843920E+10 | 0.217096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.429164E+10 | 2634332.17 |
October | 0.338624E+10 | 0.869933E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335042E+10 | 23178475.07 |
November | 0.327446E+10 | 0.840290E+10 | 0.215964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177064E+10 | 86904736.64 |
December | 0.340325E+10 | 0.871748E+10 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.396517E+09 | 0.450425E+09 |
Annual Sum or Average | 0.397770E+11 | 0.102498E+12 | 0.263573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327244E+11 | 0.235934E+10 |
Minimum of Months | 0.305697E+10 | 0.786449E+10 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75447505.49 | 0.00 |
Maximum of Months | 0.340325E+10 | 0.871748E+10 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.527007E+10 | 0.836679E+09 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.479410E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42462742.70 | 0.421388E+09 |
February | 0.152844E+10 | 0.433403E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225302E+09 | 0.292165E+09 |
March | 0.167849E+10 | 0.479910E+10 | 0.112107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.581867E+09 | 0.121399E+09 |
April | 0.163536E+10 | 0.464574E+10 | 0.108319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128750E+10 | 28754441.20 |
May | 0.168335E+10 | 0.479410E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226758E+10 | 3583128.51 |
June | 0.162685E+10 | 0.464574E+10 | 0.108562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247357E+10 | 1249533.56 |
July | 0.169671E+10 | 0.479910E+10 | 0.111865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286896E+10 | 0.00 |
August | 0.167424E+10 | 0.479410E+10 | 0.111878E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288834E+10 | 0.00 |
September | 0.163961E+10 | 0.465074E+10 | 0.108548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237118E+10 | 834572.46 |
October | 0.169307E+10 | 0.479410E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186729E+10 | 8030793.36 |
November | 0.163718E+10 | 0.463074E+10 | 0.107982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.990698E+09 | 29807723.64 |
December | 0.170157E+10 | 0.480410E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223066E+09 | 0.213073E+09 |
Annual Sum or Average | 0.198880E+11 | 0.564857E+11 | 0.131787E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180878E+11 | 0.112028E+10 |
Minimum of Months | 0.152844E+10 | 0.433403E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42462742.70 | 0.00 |
Maximum of Months | 0.170157E+10 | 0.480410E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288834E+10 | 0.421388E+09 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.338042E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41990859.78 | 0.443914E+09 |
February | 0.914877E+09 | 0.306129E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221140E+09 | 0.312836E+09 |
March | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.575909E+09 | 0.132914E+09 |
April | 0.984131E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126663E+10 | 29714255.26 |
May | 0.102058E+10 | 0.341588E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225036E+10 | 3220656.68 |
June | 0.998711E+09 | 0.333314E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246149E+10 | 893648.98 |
July | 0.100600E+10 | 0.336269E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284917E+10 | 0.00 |
August | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287953E+10 | 0.00 |
September | 0.984131E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235176E+10 | 819803.36 |
October | 0.100722E+10 | 0.338042E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184023E+10 | 6357298.66 |
November | 0.973196E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.969840E+09 | 31954965.16 |
December | 0.100600E+10 | 0.336269E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218592E+09 | 0.232651E+09 |
Annual Sum or Average | 0.119700E+11 | 0.400390E+11 | 0.104672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179266E+11 | 0.119528E+10 |
Minimum of Months | 0.914877E+09 | 0.306129E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41990859.78 | 0.00 |
Maximum of Months | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287953E+10 | 0.443914E+09 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.338042E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41991637.26 | 0.442880E+09 |
February | 0.914877E+09 | 0.306129E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221132E+09 | 0.312312E+09 |
March | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.575861E+09 | 0.132738E+09 |
April | 0.984131E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126637E+10 | 29976130.06 |
May | 0.102058E+10 | 0.341588E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224920E+10 | 3434510.69 |
June | 0.998711E+09 | 0.333314E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245983E+10 | 957988.00 |
July | 0.100600E+10 | 0.336269E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284676E+10 | 0.00 |
August | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287748E+10 | 0.00 |
September | 0.984131E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235000E+10 | 893571.28 |
October | 0.100722E+10 | 0.338042E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183917E+10 | 6790867.96 |
November | 0.973196E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.969630E+09 | 32389164.30 |
December | 0.100600E+10 | 0.336269E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218595E+09 | 0.232372E+09 |
Annual Sum or Average | 0.119700E+11 | 0.400390E+11 | 0.104672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179160E+11 | 0.119474E+10 |
Minimum of Months | 0.914877E+09 | 0.306129E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41991637.26 | 0.00 |
Maximum of Months | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287748E+10 | 0.442880E+09 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.338042E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41993120.02 | 0.440772E+09 |
February | 0.914877E+09 | 0.306129E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221186E+09 | 0.310505E+09 |
March | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.576067E+09 | 0.131301E+09 |
April | 0.984131E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126679E+10 | 29107618.36 |
May | 0.102058E+10 | 0.341588E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224989E+10 | 3220447.09 |
June | 0.998711E+09 | 0.333314E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246088E+10 | 881538.14 |
July | 0.100600E+10 | 0.336269E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284779E+10 | 0.00 |
August | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287850E+10 | 0.00 |
September | 0.984131E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235089E+10 | 830997.92 |
October | 0.100722E+10 | 0.338042E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183986E+10 | 6420726.86 |
November | 0.973196E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.969961E+09 | 31443606.07 |
December | 0.100600E+10 | 0.336269E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218615E+09 | 0.230782E+09 |
Annual Sum or Average | 0.119700E+11 | 0.400390E+11 | 0.104672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179224E+11 | 0.118527E+10 |
Minimum of Months | 0.914877E+09 | 0.306129E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41993120.02 | 0.00 |
Maximum of Months | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287850E+10 | 0.440772E+09 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.447638E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73613658.93 | 0.790993E+09 |
February | 0.313522E+10 | 0.405472E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.387954E+09 | 0.564038E+09 |
March | 0.355148E+10 | 0.457860E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101087E+10 | 0.241980E+09 |
April | 0.338259E+10 | 0.434435E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222115E+10 | 61496406.67 |
May | 0.349753E+10 | 0.452749E+10 | 0.164379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394256E+10 | 7738039.26 |
June | 0.343071E+10 | 0.442101E+10 | 0.160496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.432236E+10 | 2745872.48 |
July | 0.344942E+10 | 0.445083E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.500708E+10 | 0.00 |
August | 0.355148E+10 | 0.457860E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.506265E+10 | 0.00 |
September | 0.338259E+10 | 0.434435E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412250E+10 | 2183988.94 |
October | 0.344359E+10 | 0.447638E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322172E+10 | 18955386.15 |
November | 0.331698E+10 | 0.434435E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169910E+10 | 70770709.50 |
December | 0.344942E+10 | 0.445083E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383150E+09 | 0.424132E+09 |
Annual Sum or Average | 0.410346E+11 | 0.530479E+11 | 0.192612E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314547E+11 | 0.218503E+10 |
Minimum of Months | 0.313522E+10 | 0.405472E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73613658.93 | 0.00 |
Maximum of Months | 0.355148E+10 | 0.457860E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.506265E+10 | 0.790993E+09 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41983882.47 | 0.441208E+09 |
February | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221160E+09 | 0.311498E+09 |
March | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.575778E+09 | 0.132069E+09 |
April | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126551E+10 | 31714357.21 |
May | 0.174872E+10 | 0.233366E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224348E+10 | 3883627.18 |
June | 0.171530E+10 | 0.227877E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245686E+10 | 1395787.76 |
July | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284360E+10 | 0.00 |
August | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287516E+10 | 0.00 |
September | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234466E+10 | 1079212.34 |
October | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183514E+10 | 9608027.25 |
November | 0.165844E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.968529E+09 | 36288108.73 |
December | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218515E+09 | 0.233417E+09 |
Annual Sum or Average | 0.205167E+11 | 0.273431E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178904E+11 | 0.120216E+10 |
Minimum of Months | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41983882.47 | 0.00 |
Maximum of Months | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287516E+10 | 0.441208E+09 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41985605.28 | 0.440499E+09 |
February | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221182E+09 | 0.310858E+09 |
March | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.575849E+09 | 0.131577E+09 |
April | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126568E+10 | 31433234.97 |
May | 0.174872E+10 | 0.233366E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224371E+10 | 3831463.05 |
June | 0.171530E+10 | 0.227877E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245714E+10 | 1371974.85 |
July | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284385E+10 | 0.00 |
August | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287537E+10 | 0.00 |
September | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234490E+10 | 1064748.99 |
October | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183532E+10 | 9514337.82 |
November | 0.165844E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.968633E+09 | 36033355.68 |
December | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218524E+09 | 0.232908E+09 |
Annual Sum or Average | 0.205167E+11 | 0.273431E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178921E+11 | 0.119909E+10 |
Minimum of Months | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41985605.28 | 0.00 |
Maximum of Months | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287537E+10 | 0.440499E+09 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41990667.02 | 0.438092E+09 |
February | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221220E+09 | 0.308678E+09 |
March | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.576006E+09 | 0.129922E+09 |
April | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126589E+10 | 30587990.58 |
May | 0.174872E+10 | 0.233366E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224370E+10 | 3726104.81 |
June | 0.171530E+10 | 0.227877E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245693E+10 | 1342062.76 |
July | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284309E+10 | 0.00 |
August | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287454E+10 | 0.00 |
September | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234431E+10 | 1076308.22 |
October | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183506E+10 | 9528038.16 |
November | 0.165844E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.968660E+09 | 35618653.97 |
December | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218536E+09 | 0.231440E+09 |
Annual Sum or Average | 0.205167E+11 | 0.273431E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178899E+11 | 0.119001E+10 |
Minimum of Months | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41990667.02 | 0.00 |
Maximum of Months | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287454E+10 | 0.438092E+09 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42968921.52 | 0.540338E+09 |
February | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227520E+09 | 0.404852E+09 |
March | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.598792E+09 | 0.180820E+09 |
April | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131174E+10 | 56951937.13 |
May | 0.174872E+10 | 0.233366E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235297E+10 | 7950758.55 |
June | 0.171530E+10 | 0.227877E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260473E+10 | 2528042.03 |
July | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303550E+10 | 0.00 |
August | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306998E+10 | 0.00 |
September | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246785E+10 | 2804827.76 |
October | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190406E+10 | 21775839.58 |
November | 0.165844E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.998101E+09 | 74320401.94 |
December | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223514E+09 | 0.315035E+09 |
Annual Sum or Average | 0.205167E+11 | 0.273431E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188377E+11 | 0.160738E+10 |
Minimum of Months | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42968921.52 | 0.00 |
Maximum of Months | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306998E+10 | 0.540338E+09 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 5321.43 | 01-JAN-10:09 | 1348.26 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1938.28 | 23-JAN-14:00 | 2423.03 | 18-JAN-17:00 |
February | 4050.04 | 03-FEB-13:09 | 5321.43 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4040.62 | 06-FEB-15:00 | 2980.52 | 20-FEB-16:00 |
March | 4050.04 | 03-MAR-13:09 | 5321.43 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6493.18 | 27-MAR-11:10 | 2863.31 | 05-MAR-18:00 |
April | 4050.04 | 01-APR-12:09 | 5321.43 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8033.99 | 28-APR-12:00 | 477.63 | 01-APR-07:10 |
May | 4050.04 | 05-MAY-12:09 | 5321.43 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7779.71 | 09-MAY-13:00 | 317.26 | 01-MAY-07:02 |
June | 4050.04 | 02-JUN-12:09 | 5321.43 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8427.20 | 12-JUN-12:00 | 376.30 | 22-JUN-08:00 |
July | 4050.04 | 01-JUL-12:09 | 5321.43 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9608.25 | 21-JUL-12:00 | 0.00 | 01-JUL-00:03 |
August | 4050.04 | 04-AUG-12:09 | 5321.43 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9880.30 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 4050.04 | 01-SEP-12:09 | 5321.43 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7772.78 | 26-SEP-13:00 | 120.54 | 25-SEP-07:10 |
October | 4050.04 | 01-OCT-12:09 | 5321.43 | 01-OCT-09:09 | 1348.26 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6298.27 | 09-OCT-12:00 | 266.64 | 21-OCT-07:02 |
November | 4050.04 | 03-NOV-12:09 | 5321.43 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4618.20 | 05-NOV-12:00 | 498.32 | 22-NOV-08:65 |
December | 4050.04 | 01-DEC-13:09 | 5321.43 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2845.57 | 10-DEC-12:10 | 2919.28 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 5321.43 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 1938.28 | 0.00 | |||||
Maximum of Months | 4050.04 | 5321.43 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 9880.30 | 2980.52 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 2932.57 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.83 | 23-JAN-14:00 | 1358.14 | 18-JAN-17:00 |
February | 2024.96 | 03-FEB-13:09 | 2932.57 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2264.84 | 06-FEB-15:00 | 1684.17 | 20-FEB-16:00 |
March | 2024.96 | 03-MAR-13:09 | 2932.57 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3623.86 | 27-MAR-11:10 | 1615.40 | 05-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 2932.57 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4553.97 | 28-APR-12:00 | 274.82 | 01-APR-07:10 |
May | 2024.96 | 05-MAY-12:09 | 2932.57 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4367.31 | 09-MAY-13:00 | 180.24 | 01-MAY-07:02 |
June | 2024.96 | 02-JUN-12:09 | 2932.57 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4761.86 | 12-JUN-12:00 | 207.38 | 22-JUN-08:00 |
July | 2024.96 | 01-JUL-12:09 | 2932.57 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5429.22 | 21-JUL-12:00 | 0.00 | 01-JUL-00:03 |
August | 2024.96 | 04-AUG-12:09 | 2932.57 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.19 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 2024.96 | 01-SEP-12:09 | 2932.57 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4385.15 | 26-SEP-13:00 | 69.08 | 25-SEP-07:10 |
October | 2024.96 | 01-OCT-12:09 | 2932.57 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3582.71 | 09-OCT-12:00 | 142.22 | 21-OCT-07:02 |
November | 2024.96 | 03-NOV-12:09 | 2932.57 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2621.98 | 05-NOV-12:00 | 276.56 | 22-NOV-08:65 |
December | 2024.96 | 01-DEC-13:09 | 2932.57 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1604.86 | 10-DEC-12:10 | 1622.74 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2932.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.83 | 0.00 | |||||
Maximum of Months | 2024.96 | 2932.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.19 | 1684.17 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2599.23 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.83 | 23-JAN-14:00 | 1358.13 | 18-JAN-17:00 |
February | 2024.96 | 04-FEB-13:09 | 2599.23 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2264.84 | 06-FEB-15:00 | 1684.17 | 20-FEB-16:00 |
March | 2024.96 | 04-MAR-13:09 | 2599.23 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3623.86 | 27-MAR-11:10 | 1629.73 | 05-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 2599.23 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4553.96 | 28-APR-12:00 | 253.03 | 01-APR-07:10 |
May | 2024.96 | 06-MAY-12:09 | 2599.23 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4367.30 | 09-MAY-13:00 | 140.23 | 01-MAY-07:02 |
June | 2024.96 | 03-JUN-12:09 | 2599.23 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4761.86 | 12-JUN-12:00 | 114.16 | 22-JUN-08:00 |
July | 2024.96 | 01-JUL-12:09 | 2599.23 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5429.21 | 21-JUL-12:00 | 0.00 | 01-JUL-00:03 |
August | 2024.96 | 05-AUG-12:09 | 2599.23 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.19 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 2024.96 | 02-SEP-12:09 | 2599.23 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4385.12 | 26-SEP-13:00 | 70.89 | 24-SEP-07:10 |
October | 2024.96 | 07-OCT-12:09 | 2599.23 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3582.71 | 09-OCT-12:00 | 196.79 | 29-OCT-07:02 |
November | 2024.96 | 04-NOV-12:09 | 2599.23 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2621.98 | 05-NOV-12:00 | 243.09 | 26-NOV-08:62 |
December | 2024.96 | 02-DEC-13:09 | 2599.23 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1605.14 | 10-DEC-12:10 | 1622.74 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2599.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.83 | 0.00 | |||||
Maximum of Months | 2024.96 | 2599.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.19 | 1684.17 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2599.23 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.83 | 23-JAN-14:00 | 1358.13 | 18-JAN-17:00 |
February | 2024.96 | 04-FEB-13:09 | 2599.23 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2264.84 | 06-FEB-15:00 | 1684.17 | 20-FEB-16:00 |
March | 2024.96 | 04-MAR-13:09 | 2599.23 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3623.86 | 27-MAR-11:10 | 1622.35 | 05-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 2599.23 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4553.96 | 28-APR-12:00 | 253.08 | 01-APR-07:10 |
May | 2024.96 | 06-MAY-12:09 | 2599.23 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4367.30 | 09-MAY-13:00 | 143.81 | 01-MAY-07:02 |
June | 2024.96 | 03-JUN-12:09 | 2599.23 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4761.86 | 12-JUN-12:00 | 114.16 | 22-JUN-08:00 |
July | 2024.96 | 01-JUL-12:09 | 2599.23 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5429.21 | 21-JUL-12:00 | 0.00 | 01-JUL-00:03 |
August | 2024.96 | 05-AUG-12:09 | 2599.23 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.19 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 2024.96 | 02-SEP-12:09 | 2599.23 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4385.11 | 26-SEP-13:00 | 71.00 | 24-SEP-07:01 |
October | 2024.96 | 07-OCT-12:09 | 2599.23 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3582.72 | 09-OCT-12:00 | 199.57 | 29-OCT-07:02 |
November | 2024.96 | 04-NOV-12:09 | 2599.23 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2621.98 | 05-NOV-12:00 | 243.89 | 26-NOV-08:62 |
December | 2024.96 | 02-DEC-13:09 | 2599.23 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1605.14 | 10-DEC-12:10 | 1622.74 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2599.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.83 | 0.00 | |||||
Maximum of Months | 2024.96 | 2599.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.19 | 1684.17 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2599.23 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.82 | 23-JAN-14:00 | 1358.13 | 18-JAN-17:00 |
February | 2024.96 | 04-FEB-13:09 | 2599.23 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2264.84 | 06-FEB-15:00 | 1684.17 | 20-FEB-16:00 |
March | 2024.96 | 04-MAR-13:09 | 2599.23 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3623.86 | 27-MAR-11:10 | 1608.78 | 05-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 2599.23 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4553.97 | 28-APR-12:00 | 252.30 | 01-APR-07:10 |
May | 2024.96 | 06-MAY-12:09 | 2599.23 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4367.30 | 09-MAY-13:00 | 142.12 | 01-MAY-07:02 |
June | 2024.96 | 03-JUN-12:09 | 2599.23 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4761.86 | 12-JUN-12:00 | 114.16 | 22-JUN-08:00 |
July | 2024.96 | 01-JUL-12:09 | 2599.23 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5429.21 | 21-JUL-12:00 | 0.00 | 01-JUL-00:03 |
August | 2024.96 | 05-AUG-12:09 | 2599.23 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.19 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 2024.96 | 02-SEP-12:09 | 2599.23 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4385.12 | 26-SEP-13:00 | 70.89 | 24-SEP-07:10 |
October | 2024.96 | 07-OCT-12:09 | 2599.23 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3582.72 | 09-OCT-12:00 | 196.39 | 29-OCT-07:02 |
November | 2024.96 | 04-NOV-12:09 | 2599.23 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2621.98 | 05-NOV-12:00 | 240.55 | 26-NOV-08:62 |
December | 2024.96 | 02-DEC-13:09 | 2599.23 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1605.14 | 10-DEC-12:10 | 1622.74 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2599.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.82 | 0.00 | |||||
Maximum of Months | 2024.96 | 2599.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.19 | 1684.17 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 3746.51 | 01-JAN-11:09 | 1348.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1914.11 | 23-JAN-14:00 | 2382.79 | 18-JAN-17:00 |
February | 5400.05 | 04-FEB-15:09 | 3746.51 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3973.45 | 06-FEB-15:00 | 2951.28 | 20-FEB-16:00 |
March | 5400.05 | 04-MAR-15:09 | 3746.51 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6361.78 | 27-MAR-11:10 | 2763.44 | 05-MAR-18:00 |
April | 5400.05 | 01-APR-14:09 | 3746.51 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7976.58 | 28-APR-12:00 | 467.25 | 01-APR-07:10 |
May | 5400.05 | 06-MAY-14:09 | 3746.51 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7660.32 | 09-MAY-13:00 | 342.81 | 01-MAY-07:02 |
June | 5400.05 | 03-JUN-14:09 | 3746.51 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8344.54 | 12-JUN-12:00 | 358.71 | 22-JUN-08:00 |
July | 5400.05 | 01-JUL-14:09 | 3746.51 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9514.00 | 21-JUL-12:00 | 0.00 | 01-JUL-00:03 |
August | 5400.05 | 05-AUG-14:09 | 3746.51 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9690.80 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 5400.05 | 02-SEP-14:09 | 3746.51 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7686.73 | 26-SEP-13:00 | 147.83 | 25-SEP-07:01 |
October | 5400.05 | 07-OCT-14:09 | 3746.51 | 01-OCT-10:09 | 1348.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6272.21 | 09-OCT-12:00 | 364.04 | 29-OCT-07:02 |
November | 5400.05 | 04-NOV-14:09 | 3746.51 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4591.53 | 05-NOV-12:00 | 488.65 | 26-NOV-08:62 |
December | 5400.05 | 02-DEC-15:09 | 3746.51 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2813.51 | 10-DEC-12:10 | 2850.43 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 3746.51 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 1914.11 | 0.00 | |||||
Maximum of Months | 5400.05 | 3746.51 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 9690.80 | 2951.28 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1931.10 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.80 | 23-JAN-14:00 | 1358.16 | 18-JAN-17:00 |
February | 2699.95 | 04-FEB-15:09 | 1931.10 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2264.82 | 06-FEB-15:00 | 1684.17 | 20-FEB-16:00 |
March | 2699.95 | 04-MAR-15:09 | 1931.10 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3623.86 | 27-MAR-11:10 | 1571.40 | 05-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1931.10 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4553.96 | 28-APR-12:00 | 264.74 | 01-APR-07:10 |
May | 2699.95 | 06-MAY-14:09 | 1931.10 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4367.27 | 09-MAY-13:00 | 193.66 | 01-MAY-07:02 |
June | 2699.95 | 03-JUN-14:09 | 1931.10 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4761.86 | 12-JUN-12:00 | 203.37 | 22-JUN-08:00 |
July | 2699.95 | 01-JUL-14:09 | 1931.10 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5429.22 | 21-JUL-12:00 | 0.00 | 01-JUL-00:03 |
August | 2699.95 | 05-AUG-14:09 | 1931.10 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.19 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 2699.95 | 02-SEP-14:09 | 1931.10 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4385.48 | 26-SEP-13:00 | 84.29 | 25-SEP-07:01 |
October | 2699.95 | 07-OCT-14:09 | 1931.10 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3582.72 | 09-OCT-12:00 | 203.87 | 29-OCT-07:02 |
November | 2699.95 | 04-NOV-14:09 | 1931.10 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2621.98 | 05-NOV-12:00 | 271.51 | 26-NOV-08:62 |
December | 2699.95 | 02-DEC-15:09 | 1931.10 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1605.14 | 10-DEC-12:10 | 1622.74 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.80 | 0.00 | |||||
Maximum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.19 | 1684.17 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1931.10 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.80 | 23-JAN-14:00 | 1358.16 | 18-JAN-17:00 |
February | 2699.95 | 04-FEB-15:09 | 1931.10 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2264.82 | 06-FEB-15:00 | 1684.17 | 20-FEB-16:00 |
March | 2699.95 | 04-MAR-15:09 | 1931.10 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3623.86 | 27-MAR-11:10 | 1565.97 | 05-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1931.10 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4553.96 | 28-APR-12:00 | 263.47 | 01-APR-07:10 |
May | 2699.95 | 06-MAY-14:09 | 1931.10 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4367.27 | 09-MAY-13:00 | 192.91 | 01-MAY-07:02 |
June | 2699.95 | 03-JUN-14:09 | 1931.10 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4761.86 | 12-JUN-12:00 | 202.82 | 22-JUN-08:00 |
July | 2699.95 | 01-JUL-14:09 | 1931.10 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5429.22 | 21-JUL-12:00 | 0.00 | 01-JUL-00:03 |
August | 2699.95 | 05-AUG-14:09 | 1931.10 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.19 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 2699.95 | 02-SEP-14:09 | 1931.10 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4385.48 | 26-SEP-13:00 | 84.28 | 25-SEP-07:01 |
October | 2699.95 | 07-OCT-14:09 | 1931.10 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3582.72 | 09-OCT-12:00 | 203.22 | 29-OCT-07:02 |
November | 2699.95 | 04-NOV-14:09 | 1931.10 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2621.98 | 05-NOV-12:00 | 270.59 | 26-NOV-08:62 |
December | 2699.95 | 02-DEC-15:09 | 1931.10 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1605.14 | 10-DEC-12:10 | 1622.74 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.80 | 0.00 | |||||
Maximum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.19 | 1684.17 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1931.10 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.80 | 23-JAN-14:00 | 1358.15 | 18-JAN-17:00 |
February | 2699.95 | 04-FEB-15:09 | 1931.10 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2264.82 | 06-FEB-15:00 | 1684.17 | 20-FEB-16:00 |
March | 2699.95 | 04-MAR-15:09 | 1931.10 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3623.86 | 27-MAR-11:10 | 1553.14 | 05-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1931.10 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4553.96 | 28-APR-12:00 | 259.26 | 01-APR-07:10 |
May | 2699.95 | 06-MAY-14:09 | 1931.10 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4367.27 | 09-MAY-13:00 | 190.90 | 01-MAY-07:02 |
June | 2699.95 | 03-JUN-14:09 | 1931.10 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4761.86 | 12-JUN-12:00 | 202.54 | 22-JUN-08:00 |
July | 2699.95 | 01-JUL-14:09 | 1931.10 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5429.22 | 21-JUL-12:00 | 0.00 | 01-JUL-00:03 |
August | 2699.95 | 05-AUG-14:09 | 1931.10 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.19 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 2699.95 | 02-SEP-14:09 | 1931.10 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4385.48 | 26-SEP-13:00 | 84.34 | 25-SEP-07:01 |
October | 2699.95 | 07-OCT-14:09 | 1931.10 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3582.72 | 09-OCT-12:00 | 203.03 | 29-OCT-07:02 |
November | 2699.95 | 04-NOV-14:09 | 1931.10 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2621.98 | 05-NOV-12:00 | 267.89 | 26-NOV-08:62 |
December | 2699.95 | 02-DEC-15:09 | 1931.10 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1605.14 | 10-DEC-12:10 | 1622.74 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.80 | 0.00 | |||||
Maximum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.19 | 1684.17 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1931.10 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1115.94 | 23-JAN-14:00 | 1398.41 | 18-JAN-17:00 |
February | 2699.95 | 04-FEB-15:09 | 1931.10 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2331.98 | 06-FEB-15:00 | 1713.41 | 20-FEB-16:00 |
March | 2699.95 | 04-MAR-15:09 | 1931.10 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3755.26 | 27-MAR-11:10 | 1576.64 | 05-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1931.10 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4611.23 | 28-APR-12:00 | 255.66 | 01-APR-07:10 |
May | 2699.95 | 06-MAY-14:09 | 1931.10 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4486.50 | 09-MAY-13:00 | 200.20 | 01-MAY-07:02 |
June | 2699.95 | 03-JUN-14:09 | 1931.10 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4844.53 | 12-JUN-12:00 | 223.04 | 22-JUN-08:00 |
July | 2699.95 | 01-JUL-14:09 | 1931.10 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5523.42 | 21-JUL-12:00 | 0.00 | 01-JUL-00:03 |
August | 2699.95 | 05-AUG-14:09 | 1931.10 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5710.69 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 2699.95 | 02-SEP-14:09 | 1931.10 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4472.02 | 26-SEP-13:00 | 86.78 | 25-SEP-07:01 |
October | 2699.95 | 07-OCT-14:09 | 1931.10 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3608.81 | 09-OCT-12:00 | 234.46 | 29-OCT-07:02 |
November | 2699.95 | 04-NOV-14:09 | 1931.10 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2648.66 | 05-NOV-12:00 | 329.82 | 23-NOV-08:62 |
December | 2699.95 | 02-DEC-15:09 | 1931.10 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1637.21 | 10-DEC-12:10 | 1691.59 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1115.94 | 0.00 | |||||
Maximum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 5710.69 | 1713.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 26078.51 | 29-JAN-08:62 | 1350.01 | 1120.22 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.94 |
February | 36774.21 | 09-FEB-09:02 | 1350.01 | 11202.96 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.24 |
March | 62691.86 | 28-MAR-08:61 | 2362.52 | 19605.18 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 87.76 | 0.00 |
April | 61781.34 | 27-APR-08:61 | 2700.03 | 22405.92 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 292.79 | 0.00 |
May | 58825.99 | 11-MAY-08:61 | 2700.03 | 22405.92 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 592.69 | 0.00 |
June | 55808.19 | 02-JUN-08:61 | 2700.03 | 22405.92 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 583.09 | 0.00 |
July | 57161.01 | 04-JUL-07:01 | 2700.03 | 2240.45 | 599.22 | 0.00 | 0.00 | 0.00 | 0.00 | 371.68 | 0.00 |
August | 51724.65 | 06-AUG-07:01 | 3375.03 | 2800.56 | 749.03 | 0.00 | 0.00 | 0.00 | 0.00 | 518.86 | 0.00 |
September | 52124.46 | 26-SEP-08:61 | 2700.03 | 22405.92 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 299.86 | 0.00 |
October | 58596.14 | 21-OCT-08:62 | 2025.02 | 16804.44 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 32.83 | 0.00 |
November | 55040.72 | 05-NOV-07:02 | 1687.52 | 1400.28 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.88 |
December | 49439.29 | 12-DEC-09:02 | 2025.02 | 16804.44 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 26078.51 | 1350.01 | 1120.22 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 62691.86 | 3375.03 | 22405.92 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 592.69 | 198.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15306.54 | 29-JAN-08:62 | 674.99 | 617.38 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.58 |
February | 19544.87 | 09-FEB-09:02 | 674.99 | 6173.83 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.00 |
March | 31733.74 | 28-MAR-08:61 | 1181.23 | 10804.20 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 45.13 | 0.00 |
April | 31068.38 | 27-APR-08:61 | 1349.97 | 12347.66 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 164.37 | 0.00 |
May | 30464.55 | 08-MAY-08:61 | 1349.97 | 12347.66 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 233.96 | 0.00 |
June | 29458.43 | 02-JUN-08:61 | 1349.97 | 12347.66 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 315.34 | 0.00 |
July | 29881.06 | 04-JUL-07:01 | 1349.97 | 1234.77 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 211.08 | 0.00 |
August | 27570.38 | 06-AUG-07:01 | 1687.47 | 1543.46 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 302.73 | 0.00 |
September | 28116.18 | 26-SEP-08:61 | 1349.97 | 12347.66 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 165.33 | 0.00 |
October | 30304.13 | 21-OCT-08:62 | 1012.48 | 9260.74 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.52 | 0.00 |
November | 28837.02 | 12-NOV-08:62 | 843.73 | 771.73 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.09 |
December | 26366.53 | 12-DEC-09:02 | 1012.48 | 9260.74 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 15306.54 | 674.99 | 617.38 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31733.74 | 1687.47 | 12347.66 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 315.34 | 83.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16525.75 | 29-JAN-09:02 | 674.99 | 5472.06 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.00 |
February | 18857.66 | 09-FEB-08:62 | 674.99 | 5472.06 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.60 |
March | 31843.04 | 28-MAR-07:02 | 1012.48 | 8208.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.64 |
April | 30039.26 | 25-APR-07:02 | 1012.48 | 8208.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 38.49 | 0.00 |
May | 30878.29 | 10-MAY-07:01 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 193.37 | 0.00 |
June | 26055.89 | 02-JUN-07:01 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 150.93 | 0.00 |
July | 28674.61 | 04-JUL-08:61 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 272.54 | 0.00 |
August | 23084.62 | 06-AUG-07:01 | 0.00 | 1368.01 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 279.01 | 0.00 |
September | 24092.12 | 26-SEP-07:01 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 44.71 | 0.00 |
October | 28913.23 | 20-OCT-07:02 | 1012.48 | 8208.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.27 |
November | 28378.87 | 19-NOV-09:02 | 1012.48 | 8208.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 26.95 | 0.00 |
December | 24472.91 | 12-DEC-08:62 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16525.75 | 0.00 | 1368.01 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31843.04 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 279.01 | 80.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16282.64 | 29-JAN-09:02 | 674.99 | 5472.06 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.86 |
February | 18887.84 | 09-FEB-08:62 | 674.99 | 5472.06 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.63 |
March | 31909.42 | 28-MAR-07:02 | 1012.48 | 8208.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.16 |
April | 30132.78 | 25-APR-07:02 | 1012.48 | 8208.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 37.03 | 0.00 |
May | 30931.38 | 10-MAY-07:01 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 193.55 | 0.00 |
June | 26131.34 | 02-JUN-07:01 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 150.83 | 0.00 |
July | 28757.94 | 04-JUL-08:61 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 272.19 | 0.00 |
August | 23351.17 | 06-AUG-07:01 | 0.00 | 1368.01 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 273.03 | 0.00 |
September | 24177.17 | 26-SEP-07:01 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 45.85 | 0.00 |
October | 29027.51 | 20-OCT-07:02 | 1012.48 | 8208.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.42 |
November | 28461.83 | 19-NOV-09:02 | 1012.48 | 8208.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.68 | 0.00 |
December | 24518.69 | 12-DEC-08:62 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16282.64 | 0.00 | 1368.01 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31909.42 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 273.03 | 80.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15231.23 | 29-JAN-09:02 | 674.99 | 5472.06 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.25 |
February | 17802.75 | 09-FEB-08:62 | 674.99 | 5472.06 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.00 |
March | 31819.97 | 28-MAR-07:02 | 1012.48 | 8208.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.65 |
April | 29984.12 | 25-APR-07:02 | 1012.48 | 8208.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 40.32 | 0.00 |
May | 30878.31 | 10-MAY-07:01 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 193.45 | 0.00 |
June | 26051.51 | 02-JUN-07:01 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 150.94 | 0.00 |
July | 28701.30 | 04-JUL-08:61 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 272.22 | 0.00 |
August | 23245.01 | 06-AUG-07:01 | 0.00 | 1368.01 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 274.67 | 0.00 |
September | 24073.28 | 26-SEP-07:01 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 45.79 | 0.00 |
October | 28889.02 | 20-OCT-07:02 | 1012.48 | 8208.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.27 |
November | 28333.63 | 19-NOV-09:02 | 1012.48 | 8208.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.61 | 0.00 |
December | 24386.94 | 12-DEC-08:62 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 15231.23 | 0.00 | 1368.01 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31819.97 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 274.67 | 80.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 43311.08 | 29-JAN-10:02 | 3712.53 | 9859.20 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 25.95 | 0.00 |
February | 49407.12 | 05-FEB-10:02 | 4455.04 | 11831.03 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 224.34 | 0.00 |
March | 58447.13 | 28-MAR-08:61 | 5197.55 | 13802.87 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 79.03 | 0.00 |
April | 56917.03 | 27-APR-08:61 | 5940.06 | 15774.71 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 288.43 | 0.00 |
May | 54595.77 | 11-MAY-08:61 | 5940.06 | 15774.71 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 555.79 | 0.00 |
June | 51460.26 | 02-JUN-08:61 | 5940.06 | 15774.71 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 547.38 | 0.00 |
July | 50416.84 | 04-JUL-09:01 | 5940.06 | 15774.71 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 597.55 | 0.00 |
August | 44394.15 | 16-AUG-07:01 | 0.00 | 1577.32 | 599.22 | 0.00 | 0.00 | 0.00 | 0.00 | 500.48 | 0.00 |
September | 48127.90 | 26-SEP-08:61 | 5940.06 | 15774.71 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 281.38 | 0.00 |
October | 53890.99 | 20-OCT-08:61 | 5197.55 | 13802.87 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 40.60 | 0.00 |
November | 55982.58 | 19-NOV-10:01 | 5940.06 | 15774.71 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 143.41 | 0.00 |
December | 46595.76 | 12-DEC-09:02 | 4455.04 | 11831.03 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.21 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 43311.08 | 0.00 | 1577.32 | 599.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 58447.13 | 5940.06 | 15774.71 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 597.55 | 40.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 22786.39 | 29-JAN-10:02 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 17.90 | 0.00 |
February | 25996.75 | 05-FEB-10:02 | 2227.46 | 6098.20 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 130.90 | 0.00 |
March | 30798.87 | 28-MAR-08:61 | 2598.70 | 7114.56 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 48.96 | 0.00 |
April | 29933.99 | 27-APR-08:61 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 169.90 | 0.00 |
May | 28876.05 | 11-MAY-08:61 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 316.84 | 0.00 |
June | 27162.04 | 02-JUN-08:61 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 312.01 | 0.00 |
July | 26690.08 | 04-JUL-09:01 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 341.34 | 0.00 |
August | 23401.86 | 16-AUG-07:01 | 0.00 | 813.09 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 287.97 | 0.00 |
September | 25404.00 | 26-SEP-08:61 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 161.08 | 0.00 |
October | 28388.79 | 20-OCT-08:61 | 2598.70 | 7114.56 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 26.73 | 0.00 |
November | 29475.12 | 19-NOV-10:01 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 84.78 | 0.00 |
December | 24568.45 | 12-DEC-09:02 | 2227.46 | 6098.20 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.29 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 22786.39 | 0.00 | 813.09 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30798.87 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 341.34 | 20.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 22687.14 | 29-JAN-10:02 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 18.82 | 0.00 |
February | 25881.50 | 05-FEB-10:02 | 2227.46 | 6098.20 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 131.96 | 0.00 |
March | 30691.08 | 28-MAR-08:61 | 2598.70 | 7114.56 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 49.67 | 0.00 |
April | 29809.65 | 27-APR-08:61 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 170.64 | 0.00 |
May | 28782.22 | 11-MAY-08:61 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 316.69 | 0.00 |
June | 27069.99 | 02-JUN-08:61 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 311.84 | 0.00 |
July | 26598.80 | 04-JUL-09:01 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 341.23 | 0.00 |
August | 23305.54 | 16-AUG-07:01 | 0.00 | 813.09 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 288.29 | 0.00 |
September | 25320.39 | 26-SEP-08:61 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 161.36 | 0.00 |
October | 28281.91 | 20-OCT-08:61 | 2598.70 | 7114.56 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 27.18 | 0.00 |
November | 29379.67 | 19-NOV-10:01 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 84.70 | 0.00 |
December | 24477.65 | 12-DEC-09:02 | 2227.46 | 6098.20 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.94 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 22687.14 | 0.00 | 813.09 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30691.08 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 341.23 | 19.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 22672.68 | 29-JAN-10:02 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 22.89 | 0.00 |
February | 25871.63 | 05-FEB-10:02 | 2227.46 | 6098.20 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 136.29 | 0.00 |
March | 30781.41 | 28-MAR-08:61 | 2598.70 | 7114.56 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 51.86 | 0.00 |
April | 29869.12 | 27-APR-08:61 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 172.49 | 0.00 |
May | 28896.36 | 11-MAY-08:61 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 316.94 | 0.00 |
June | 27173.19 | 02-JUN-08:61 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 312.15 | 0.00 |
July | 26720.74 | 04-JUL-09:01 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 341.26 | 0.00 |
August | 23489.15 | 16-AUG-07:01 | 0.00 | 813.09 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 285.84 | 0.00 |
September | 25424.80 | 26-SEP-08:61 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 161.26 | 0.00 |
October | 28379.72 | 20-OCT-08:61 | 2598.70 | 7114.56 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 27.75 | 0.00 |
November | 29487.49 | 19-NOV-10:01 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 84.97 | 0.00 |
December | 24489.19 | 12-DEC-09:02 | 2227.46 | 6098.20 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 22672.68 | 0.00 | 813.09 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30781.41 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 341.26 | 17.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 25212.94 | 29-JAN-10:02 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 29.76 | 0.00 |
February | 28933.65 | 05-FEB-10:02 | 2227.46 | 6098.20 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 174.64 | 0.00 |
March | 34087.62 | 28-MAR-08:61 | 2598.70 | 7114.56 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 62.36 | 0.00 |
April | 33538.58 | 27-APR-08:61 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 180.36 | 0.00 |
May | 32208.37 | 11-MAY-08:61 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 353.01 | 0.00 |
June | 30324.85 | 02-JUN-08:61 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 346.15 | 0.00 |
July | 32356.14 | 04-JUL-08:61 | 0.00 | 813.09 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 243.91 | 0.00 |
August | 26683.87 | 06-AUG-08:61 | 0.00 | 813.09 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 297.44 | 0.00 |
September | 28423.69 | 26-SEP-08:61 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 178.39 | 0.00 |
October | 31709.88 | 20-OCT-08:61 | 2598.70 | 7114.56 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 24.34 | 0.00 |
November | 32540.70 | 19-NOV-10:01 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 98.79 | 0.00 |
December | 26938.55 | 12-DEC-09:02 | 2227.46 | 6098.20 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 25212.94 | 0.00 | 813.09 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34087.62 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 353.01 | 21.13 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.917739E+11 | 79557.05 | 29-JAN-15:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 0.876514E+11 | 91151.38 | 07-FEB-13:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 0.104161E+12 | 99171.95 | 27-MAR-11:30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 0.112306E+12 | 110511.45 | 28-APR-12:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.136887E+12 | 131605.13 | 31-MAY-12:20 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.147675E+12 | 140611.93 | 09-JUN-12:20 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.166190E+12 | 156540.70 | 20-JUL-12:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.174552E+12 | 159951.58 | 10-AUG-15:50 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.151602E+12 | 149350.57 | 07-SEP-13:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.135960E+12 | 133126.73 | 07-OCT-12:39 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.115035E+12 | 113680.08 | 01-NOV-12:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.100289E+12 | 89421.44 | 05-DEC-17:30 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.152408E+13 | 0.00 | ||||
Minimum of Months | 0.876514E+11 | 79557.05 | 0.00 | 0.00 | ||
Maximum of Months | 0.174552E+12 | 159951.58 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.373403E+11 | 0.966828E+10 | 0.108804E+11 | 0.00 | 0.109822E+11 | 0.00 | 0.00 | 0.178099E+11 | 0.00 | 0.00 | 0.00 | 0.509276E+10 | 0.00 |
February | 0.337970E+11 | 0.832797E+10 | 0.985143E+10 | 0.00 | 0.995180E+10 | 0.00 | 0.00 | 0.211433E+11 | 0.00 | 0.00 | 0.00 | 0.457985E+10 | 0.00 |
March | 0.378801E+11 | 0.863051E+10 | 0.110560E+11 | 0.00 | 0.111841E+11 | 0.00 | 0.00 | 0.303887E+11 | 0.00 | 0.00 | 0.00 | 0.502201E+10 | 0.00 |
April | 0.362171E+11 | 0.772504E+10 | 0.105544E+11 | 0.00 | 0.107059E+11 | 0.00 | 0.00 | 0.423657E+11 | 0.00 | 0.00 | 0.00 | 0.473753E+10 | 0.00 |
May | 0.376032E+11 | 0.747844E+10 | 0.109629E+11 | 0.00 | 0.113731E+11 | 0.00 | 0.00 | 0.646742E+11 | 0.00 | 0.00 | 0.00 | 0.479491E+10 | 0.00 |
June | 0.366114E+11 | 0.700271E+10 | 0.106855E+11 | 0.00 | 0.120069E+11 | 0.00 | 0.00 | 0.767880E+11 | 0.00 | 0.00 | 0.00 | 0.458077E+10 | 0.00 |
July | 0.372230E+11 | 0.732300E+10 | 0.108424E+11 | 0.00 | 0.136216E+11 | 0.00 | 0.00 | 0.924997E+11 | 0.00 | 0.00 | 0.00 | 0.468056E+10 | 0.00 |
August | 0.378660E+11 | 0.775731E+10 | 0.110491E+11 | 0.00 | 0.143719E+11 | 0.00 | 0.00 | 0.987735E+11 | 0.00 | 0.00 | 0.00 | 0.473390E+10 | 0.00 |
September | 0.362312E+11 | 0.807706E+10 | 0.105613E+11 | 0.00 | 0.123669E+11 | 0.00 | 0.00 | 0.797174E+11 | 0.00 | 0.00 | 0.00 | 0.464827E+10 | 0.00 |
October | 0.373403E+11 | 0.896881E+10 | 0.108804E+11 | 0.00 | 0.113446E+11 | 0.00 | 0.00 | 0.625340E+11 | 0.00 | 0.00 | 0.00 | 0.489211E+10 | 0.00 |
November | 0.361749E+11 | 0.921542E+10 | 0.105443E+11 | 0.00 | 0.107280E+11 | 0.00 | 0.00 | 0.435389E+11 | 0.00 | 0.00 | 0.00 | 0.483354E+10 | 0.00 |
December | 0.372370E+11 | 0.982829E+10 | 0.108529E+11 | 0.00 | 0.109647E+11 | 0.00 | 0.00 | 0.263374E+11 | 0.00 | 0.00 | 0.00 | 0.506831E+10 | 0.00 |
Annual Sum or Average | 0.441522E+12 | 0.100003E+12 | 0.128721E+12 | 0.00 | 0.139602E+12 | 0.00 | 0.00 | 0.656571E+12 | 0.00 | 0.00 | 0.00 | 0.576645E+11 | 0.00 |
Minimum of Months | 0.337970E+11 | 0.700271E+10 | 0.985143E+10 | 0.00 | 0.995180E+10 | 0.00 | 0.00 | 0.178099E+11 | 0.00 | 0.00 | 0.00 | 0.457985E+10 | 0.00 |
Maximum of Months | 0.378801E+11 | 0.982829E+10 | 0.110560E+11 | 0.00 | 0.143719E+11 | 0.00 | 0.00 | 0.987735E+11 | 0.00 | 0.00 | 0.00 | 0.509276E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 27522.57 | 01-JAN-11:09 | 7619.51 | 01-JAN-06:10 | 8089.53 | 01-JAN-11:09 | 0.00 | 8667.92 | 29-JAN-10:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 27522.57 | 01-FEB-10:09 | 7619.51 | 01-FEB-06:10 | 8089.53 | 01-FEB-10:09 | 0.00 | 8908.97 | 07-FEB-09:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 27522.57 | 01-MAR-10:09 | 7619.51 | 01-MAR-06:10 | 8089.53 | 01-MAR-10:09 | 0.00 | 9570.79 | 02-MAR-09:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 27522.57 | 01-APR-09:09 | 7619.51 | 01-APR-05:10 | 8089.53 | 01-APR-09:09 | 0.00 | 9696.65 | 03-APR-08:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 27522.57 | 01-MAY-09:09 | 7619.51 | 01-MAY-05:10 | 8089.53 | 01-MAY-09:09 | 0.00 | 10809.62 | 30-MAY-08:09 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 27522.57 | 01-JUN-09:09 | 7619.51 | 01-JUN-05:10 | 8089.53 | 01-JUN-09:09 | 0.00 | 12157.36 | 09-JUN-12:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 27522.57 | 01-JUL-09:09 | 7619.51 | 01-JUL-05:10 | 8089.53 | 01-JUL-09:09 | 0.00 | 14841.92 | 20-JUL-12:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 27522.57 | 01-AUG-09:09 | 7619.51 | 01-AUG-05:10 | 8089.53 | 01-AUG-09:09 | 0.00 | 15118.57 | 10-AUG-16:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 27522.57 | 01-SEP-09:09 | 7619.51 | 01-SEP-05:10 | 8089.53 | 01-SEP-09:09 | 0.00 | 13514.90 | 07-SEP-13:39 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 27522.57 | 01-OCT-10:09 | 7619.51 | 01-OCT-05:10 | 8089.53 | 01-OCT-10:09 | 0.00 | 11761.75 | 07-OCT-12:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 27522.57 | 01-NOV-09:09 | 7619.51 | 01-NOV-05:10 | 8089.53 | 01-NOV-09:09 | 0.00 | 9963.96 | 08-NOV-09:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 27522.57 | 01-DEC-10:09 | 7619.51 | 01-DEC-06:10 | 8089.53 | 01-DEC-10:09 | 0.00 | 9150.41 | 11-DEC-09:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 27522.57 | 7619.51 | 8089.53 | 0.00 | 8667.92 | 0.00 | 0.00 | |||||
Maximum of Months | 27522.57 | 7619.51 | 8089.53 | 0.00 | 15118.57 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 30973.58 | 29-JAN-15:00 | 0.00 | 0.00 | 0.00 | 12949.94 | 01-JAN-08:09 | 0.00 |
February | 42502.99 | 07-FEB-13:39 | 0.00 | 0.00 | 0.00 | 9564.28 | 28-FEB-13:00 | 0.00 |
March | 50722.26 | 27-MAR-12:09 | 0.00 | 0.00 | 0.00 | 7555.88 | 11-MAR-14:50 | 0.00 |
April | 65152.23 | 28-APR-11:00 | 0.00 | 0.00 | 0.00 | 7544.55 | 22-APR-13:00 | 0.00 |
May | 79921.35 | 31-MAY-12:09 | 0.00 | 0.00 | 0.00 | 7887.21 | 22-MAY-12:30 | 0.00 |
June | 89528.09 | 09-JUN-12:00 | 0.00 | 0.00 | 0.00 | 7533.55 | 24-JUN-12:30 | 0.00 |
July | 102763.80 | 20-JUL-12:00 | 0.00 | 0.00 | 0.00 | 7518.41 | 07-JUL-17:30 | 0.00 |
August | 107664.98 | 10-AUG-16:10 | 0.00 | 0.00 | 0.00 | 8983.73 | 28-AUG-15:09 | 0.00 |
September | 93303.11 | 07-SEP-13:30 | 0.00 | 0.00 | 0.00 | 7543.39 | 30-SEP-13:50 | 0.00 |
October | 81160.64 | 07-OCT-12:00 | 0.00 | 0.00 | 0.00 | 7552.73 | 20-OCT-12:30 | 0.00 |
November | 63007.81 | 01-NOV-13:00 | 0.00 | 0.00 | 0.00 | 8712.64 | 18-NOV-18:49 | 0.00 |
December | 38358.64 | 04-DEC-13:09 | 0.00 | 0.00 | 0.00 | 9526.65 | 14-DEC-13:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 30973.58 | 0.00 | 0.00 | 0.00 | 7518.41 | 0.00 | ||
Maximum of Months | 107664.98 | 0.00 | 0.00 | 0.00 | 12949.94 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 79557.05 | 29-JAN-15:00 | 27522.57 | 8089.53 | 0.00 | 0.00 | 7547.16 | 0.00 | 0.00 | 30973.58 | 0.00 |
February | 91151.38 | 07-FEB-13:30 | 27522.57 | 8089.53 | 0.00 | 0.00 | 7547.16 | 0.00 | 0.00 | 42499.12 | 0.00 |
March | 99171.95 | 27-MAR-11:30 | 27522.57 | 8089.53 | 0.00 | 0.00 | 7547.16 | 0.00 | 0.00 | 50581.60 | 0.00 |
April | 110511.45 | 28-APR-12:09 | 27522.57 | 8089.53 | 0.00 | 0.00 | 7878.59 | 0.00 | 0.00 | 63693.68 | 0.00 |
May | 131605.13 | 31-MAY-12:20 | 27522.57 | 8089.53 | 0.00 | 0.00 | 10686.69 | 0.00 | 0.00 | 79875.60 | 0.00 |
June | 140611.93 | 09-JUN-12:20 | 27522.57 | 8089.53 | 0.00 | 0.00 | 11905.79 | 0.00 | 0.00 | 87664.36 | 0.00 |
July | 156540.70 | 20-JUL-12:00 | 27522.57 | 8089.53 | 0.00 | 0.00 | 14841.92 | 0.00 | 0.00 | 102763.80 | 0.00 |
August | 159951.58 | 10-AUG-15:50 | 27522.57 | 8089.53 | 0.00 | 0.00 | 14787.47 | 0.00 | 0.00 | 106233.95 | 0.00 |
September | 149350.57 | 07-SEP-13:00 | 27522.57 | 8089.53 | 0.00 | 0.00 | 13485.22 | 0.00 | 0.00 | 92714.97 | 0.00 |
October | 133126.73 | 07-OCT-12:39 | 27522.57 | 8089.53 | 0.00 | 0.00 | 11661.65 | 0.00 | 0.00 | 80416.33 | 0.00 |
November | 113680.08 | 01-NOV-12:00 | 27522.57 | 8089.53 | 0.00 | 0.00 | 8484.90 | 0.00 | 0.00 | 62028.37 | 0.00 |
December | 89421.44 | 05-DEC-17:30 | 27522.57 | 8089.53 | 7619.51 | 0.00 | 7547.16 | 0.00 | 0.00 | 35135.48 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 79557.05 | 27522.57 | 8089.53 | 0.00 | 0.00 | 7547.16 | 0.00 | 0.00 | 30973.58 | 0.00 | |
Maximum of Months | 159951.58 | 27522.57 | 8089.53 | 7619.51 | 0.00 | 14841.92 | 0.00 | 0.00 | 106233.95 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.50 | 1.50 | 24.50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.51 | 1.67 | 24.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.49 | 0.50 | 24.49 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.67 | 24.50 | 3.67 | 24.50 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.51 | 1.67 | 24.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.47 | 0.17 | 24.47 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.49 | 0.17 | 24.49 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.33 | 24.48 | 0.33 | 24.48 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.49 | 0.17 | 24.49 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.49 | 1.67 | 24.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.52 | 1.50 | 24.52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.53 | 0.67 | 24.53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.48 | 0.50 | 24.48 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.33 | 24.51 | 4.33 | 24.51 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.53 | 1.67 | 24.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.45 | 0.17 | 24.45 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.49 | 1.83 | 24.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.52 | 1.50 | 24.52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.53 | 0.67 | 24.53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.49 | 0.50 | 24.49 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.67 | 24.50 | 4.67 | 24.50 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.53 | 1.83 | 24.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.45 | 0.17 | 24.45 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.49 | 1.83 | 24.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.52 | 1.50 | 24.52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.53 | 0.67 | 24.53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.49 | 0.50 | 24.49 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.67 | 24.50 | 4.67 | 24.50 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.53 | 1.83 | 24.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.51 | 0.50 | 24.51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.51 | 2.17 | 24.51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.51 | 2.17 | 24.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.56 | 0.83 | 24.56 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.55 | 0.50 | 24.55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 6.17 | 24.52 | 6.17 | 24.52 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.56 | 2.17 | 24.56 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.50 | 0.33 | 24.50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.49 | 1.50 | 24.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.50 | 1.33 | 24.50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.55 | 0.67 | 24.55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.52 | 0.50 | 24.52 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.33 | 24.51 | 4.33 | 24.51 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.55 | 1.50 | 24.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.50 | 0.33 | 24.50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.49 | 1.50 | 24.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.50 | 1.33 | 24.50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.55 | 0.67 | 24.55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.52 | 0.50 | 24.52 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.33 | 24.51 | 4.33 | 24.51 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.55 | 1.50 | 24.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.50 | 0.33 | 24.50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.49 | 1.50 | 24.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.50 | 1.33 | 24.50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.55 | 0.67 | 24.55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.52 | 0.50 | 24.52 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.33 | 24.51 | 4.33 | 24.51 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.55 | 1.50 | 24.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.48 | 0.17 | 24.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.47 | 1.17 | 24.47 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 26.10 | 0.83 | 25.44 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.92 | 0.50 | 25.32 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.48 | 0.50 | 24.48 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.67 | 25.25 | 3.17 | 24.90 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 26.10 | 1.17 | 25.44 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 30.50 | 23.16 | 293.33 | 23.83 | 0.50 | 23.83 |
February | 13.67 | 23.39 | 367.00 | 23.89 | 1.17 | 23.89 |
March | 13.50 | 23.62 | 404.17 | 23.91 | 3.50 | 23.91 |
April | 9.17 | 24.44 | 455.00 | 23.95 | 9.17 | 23.96 |
May | 26.33 | 24.75 | 495.83 | 24.02 | 26.33 | 24.06 |
June | 120.33 | 24.24 | 481.00 | 24.04 | 120.33 | 24.08 |
July | 194.00 | 24.12 | 495.00 | 24.02 | 194.00 | 24.04 |
August | 187.67 | 24.18 | 497.00 | 24.05 | 187.67 | 24.08 |
September | 125.50 | 24.21 | 479.00 | 24.03 | 125.50 | 24.06 |
October | 64.33 | 24.38 | 495.67 | 24.03 | 64.33 | 24.07 |
November | 15.50 | 24.56 | 477.00 | 23.97 | 15.50 | 23.99 |
December | 10.67 | 23.75 | 425.83 | 23.90 | 5.00 | 23.91 |
Annual Sum or Average | 811.17 | 24.16 | 5365.83 | 23.98 | 753.00 | 24.01 |
Minimum of Months | 9.17 | 23.16 | 293.33 | 23.83 | 0.50 | 23.83 |
Maximum of Months | 194.00 | 24.75 | 497.00 | 24.05 | 194.00 | 24.08 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 25.33 | 23.31 | 255.67 | 23.84 | 0.83 | 23.84 |
February | 9.50 | 23.39 | 322.33 | 23.89 | 0.00 | 23.89 |
March | 6.50 | 23.62 | 357.83 | 23.93 | 0.00 | 23.93 |
April | 2.33 | 23.89 | 422.83 | 23.95 | 2.33 | 23.95 |
May | 15.17 | 24.17 | 492.67 | 23.99 | 15.17 | 24.00 |
June | 82.33 | 24.22 | 481.00 | 24.02 | 82.33 | 24.05 |
July | 146.17 | 24.15 | 495.00 | 24.02 | 146.17 | 24.05 |
August | 165.17 | 24.16 | 497.00 | 24.04 | 165.17 | 24.07 |
September | 95.17 | 24.13 | 479.00 | 24.01 | 95.17 | 24.02 |
October | 44.83 | 24.25 | 488.33 | 24.01 | 44.83 | 24.02 |
November | 8.17 | 24.19 | 455.50 | 23.96 | 8.17 | 23.97 |
December | 7.33 | 23.72 | 384.33 | 23.91 | 3.50 | 23.91 |
Annual Sum or Average | 608.00 | 24.11 | 5131.50 | 23.98 | 563.67 | 24.00 |
Minimum of Months | 2.33 | 23.31 | 255.67 | 23.84 | 0.00 | 23.84 |
Maximum of Months | 165.17 | 24.25 | 497.00 | 24.04 | 165.17 | 24.07 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 25.50 | 23.24 | 223.17 | 23.94 | 1.17 | 23.94 |
February | 7.33 | 23.37 | 279.50 | 24.00 | 0.50 | 24.00 |
March | 5.83 | 24.50 | 309.33 | 24.06 | 2.67 | 24.08 |
April | 9.83 | 25.77 | 327.00 | 24.15 | 9.83 | 24.20 |
May | 37.00 | 25.77 | 375.00 | 24.31 | 37.00 | 24.43 |
June | 98.67 | 24.81 | 366.00 | 24.31 | 98.67 | 24.40 |
July | 156.00 | 24.63 | 369.00 | 24.34 | 156.00 | 24.41 |
August | 174.17 | 24.57 | 379.00 | 24.33 | 174.17 | 24.38 |
September | 119.50 | 24.76 | 360.00 | 24.33 | 119.50 | 24.42 |
October | 61.00 | 25.00 | 367.00 | 24.28 | 61.00 | 24.37 |
November | 18.00 | 24.80 | 358.67 | 24.12 | 18.00 | 24.15 |
December | 15.67 | 24.23 | 328.83 | 24.03 | 12.17 | 24.04 |
Annual Sum or Average | 728.50 | 24.70 | 4042.50 | 24.21 | 690.67 | 24.28 |
Minimum of Months | 5.83 | 23.24 | 223.17 | 23.94 | 0.50 | 23.94 |
Maximum of Months | 174.17 | 25.77 | 379.00 | 24.34 | 174.17 | 24.43 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 27.17 | 23.21 | 219.50 | 23.93 | 1.17 | 23.93 |
February | 8.50 | 23.34 | 277.67 | 23.99 | 0.50 | 23.99 |
March | 6.50 | 24.39 | 307.33 | 24.06 | 2.67 | 24.08 |
April | 9.83 | 25.84 | 327.83 | 24.16 | 9.83 | 24.20 |
May | 36.50 | 25.81 | 375.00 | 24.31 | 36.50 | 24.43 |
June | 96.83 | 24.83 | 366.00 | 24.31 | 96.83 | 24.40 |
July | 154.83 | 24.64 | 369.00 | 24.35 | 154.83 | 24.41 |
August | 171.17 | 24.58 | 379.00 | 24.33 | 171.17 | 24.39 |
September | 116.83 | 24.79 | 360.00 | 24.34 | 116.83 | 24.43 |
October | 59.33 | 25.04 | 368.00 | 24.28 | 59.33 | 24.37 |
November | 18.17 | 24.90 | 358.67 | 24.12 | 18.17 | 24.16 |
December | 16.50 | 24.19 | 327.83 | 24.03 | 12.67 | 24.04 |
Annual Sum or Average | 722.17 | 24.71 | 4035.83 | 24.22 | 680.50 | 24.29 |
Minimum of Months | 6.50 | 23.21 | 219.50 | 23.93 | 0.50 | 23.93 |
Maximum of Months | 171.17 | 25.84 | 379.00 | 24.35 | 171.17 | 24.43 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 31.33 | 23.20 | 213.83 | 23.91 | 1.33 | 23.91 |
February | 10.00 | 23.29 | 274.17 | 23.98 | 0.50 | 23.99 |
March | 7.67 | 24.14 | 301.00 | 24.06 | 2.83 | 24.07 |
April | 9.67 | 25.78 | 325.17 | 24.15 | 9.67 | 24.20 |
May | 36.33 | 25.76 | 375.00 | 24.30 | 36.33 | 24.42 |
June | 98.33 | 24.81 | 366.00 | 24.31 | 98.33 | 24.40 |
July | 155.67 | 24.63 | 369.00 | 24.34 | 155.67 | 24.41 |
August | 173.33 | 24.57 | 379.00 | 24.33 | 173.33 | 24.38 |
September | 118.83 | 24.77 | 360.00 | 24.33 | 118.83 | 24.42 |
October | 60.33 | 25.02 | 366.67 | 24.28 | 60.33 | 24.37 |
November | 18.83 | 24.79 | 358.50 | 24.11 | 18.83 | 24.15 |
December | 18.50 | 24.12 | 322.67 | 24.02 | 13.67 | 24.03 |
Annual Sum or Average | 738.83 | 24.67 | 4011.00 | 24.21 | 689.67 | 24.28 |
Minimum of Months | 7.67 | 23.20 | 213.83 | 23.91 | 0.50 | 23.91 |
Maximum of Months | 173.33 | 25.78 | 379.00 | 24.34 | 173.33 | 24.42 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 21.00 | 23.29 | 189.50 | 23.87 | 2.17 | 23.87 |
February | 4.67 | 23.45 | 251.83 | 23.92 | 0.17 | 23.92 |
March | 5.50 | 24.04 | 269.67 | 23.94 | 3.17 | 23.94 |
April | 7.83 | 25.84 | 303.67 | 24.03 | 7.83 | 24.07 |
May | 26.67 | 25.00 | 344.00 | 24.07 | 26.67 | 24.13 |
June | 93.83 | 24.25 | 336.00 | 24.05 | 93.83 | 24.09 |
July | 150.33 | 24.22 | 338.00 | 24.10 | 150.33 | 24.13 |
August | 165.00 | 24.12 | 348.00 | 24.04 | 165.00 | 24.06 |
September | 110.00 | 24.28 | 330.00 | 24.09 | 110.00 | 24.13 |
October | 50.00 | 24.54 | 338.50 | 24.07 | 50.00 | 24.13 |
November | 15.33 | 24.25 | 329.50 | 23.98 | 15.33 | 23.99 |
December | 18.33 | 24.15 | 294.17 | 23.95 | 16.67 | 23.97 |
Annual Sum or Average | 668.50 | 24.25 | 3672.83 | 24.02 | 641.17 | 24.06 |
Minimum of Months | 4.67 | 23.29 | 189.50 | 23.87 | 0.17 | 23.87 |
Maximum of Months | 165.00 | 25.84 | 348.00 | 24.10 | 165.00 | 24.13 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 23.33 | 23.36 | 181.17 | 23.87 | 2.33 | 23.87 |
February | 5.33 | 23.51 | 235.33 | 23.92 | 0.17 | 23.93 |
March | 5.67 | 24.03 | 246.33 | 23.94 | 2.67 | 23.95 |
April | 7.50 | 25.75 | 290.83 | 24.03 | 7.50 | 24.07 |
May | 25.83 | 24.99 | 342.33 | 24.07 | 25.83 | 24.13 |
June | 92.33 | 24.25 | 336.00 | 24.05 | 92.33 | 24.08 |
July | 148.67 | 24.22 | 338.00 | 24.10 | 148.67 | 24.12 |
August | 163.67 | 24.12 | 348.00 | 24.04 | 163.67 | 24.06 |
September | 109.67 | 24.28 | 330.00 | 24.08 | 109.67 | 24.12 |
October | 49.33 | 24.50 | 333.67 | 24.07 | 49.33 | 24.12 |
November | 14.33 | 24.14 | 327.33 | 23.97 | 14.33 | 23.98 |
December | 19.50 | 24.16 | 275.67 | 23.96 | 17.33 | 23.97 |
Annual Sum or Average | 665.17 | 24.24 | 3584.67 | 24.02 | 633.83 | 24.06 |
Minimum of Months | 5.33 | 23.36 | 181.17 | 23.87 | 0.17 | 23.87 |
Maximum of Months | 163.67 | 25.75 | 348.00 | 24.10 | 163.67 | 24.13 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 24.67 | 23.36 | 179.33 | 23.87 | 2.33 | 23.87 |
February | 5.67 | 23.35 | 232.17 | 23.92 | 0.00 | 23.92 |
March | 6.50 | 23.99 | 241.00 | 23.94 | 3.00 | 23.95 |
April | 7.67 | 25.70 | 289.50 | 24.03 | 7.67 | 24.07 |
May | 25.83 | 24.98 | 342.00 | 24.07 | 25.83 | 24.13 |
June | 93.00 | 24.24 | 336.00 | 24.05 | 93.00 | 24.08 |
July | 149.67 | 24.22 | 338.00 | 24.09 | 149.67 | 24.12 |
August | 164.83 | 24.12 | 348.00 | 24.04 | 164.83 | 24.06 |
September | 110.33 | 24.27 | 330.00 | 24.08 | 110.33 | 24.12 |
October | 49.83 | 24.49 | 333.50 | 24.07 | 49.83 | 24.12 |
November | 14.50 | 24.13 | 327.33 | 23.97 | 14.50 | 23.98 |
December | 20.17 | 24.15 | 273.17 | 23.96 | 17.83 | 23.97 |
Annual Sum or Average | 672.67 | 24.23 | 3570.00 | 24.02 | 638.83 | 24.06 |
Minimum of Months | 5.67 | 23.35 | 179.33 | 23.87 | 0.00 | 23.87 |
Maximum of Months | 164.83 | 25.70 | 348.00 | 24.09 | 164.83 | 24.13 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 28.17 | 23.33 | 177.33 | 23.85 | 2.50 | 23.85 |
February | 7.67 | 23.32 | 229.00 | 23.91 | 0.00 | 23.91 |
March | 8.17 | 23.91 | 237.50 | 23.94 | 3.50 | 23.95 |
April | 7.83 | 25.66 | 289.67 | 24.03 | 7.83 | 24.07 |
May | 26.00 | 24.98 | 342.17 | 24.07 | 26.00 | 24.13 |
June | 92.33 | 24.25 | 336.00 | 24.05 | 92.33 | 24.08 |
July | 146.67 | 24.23 | 338.00 | 24.10 | 146.67 | 24.13 |
August | 162.33 | 24.12 | 348.00 | 24.04 | 162.33 | 24.06 |
September | 108.67 | 24.28 | 330.00 | 24.09 | 108.67 | 24.13 |
October | 49.17 | 24.50 | 333.67 | 24.07 | 49.17 | 24.12 |
November | 14.83 | 24.13 | 327.17 | 23.97 | 14.83 | 23.98 |
December | 21.83 | 24.11 | 271.00 | 23.96 | 18.67 | 23.97 |
Annual Sum or Average | 673.67 | 24.22 | 3559.50 | 24.02 | 632.50 | 24.06 |
Minimum of Months | 7.67 | 23.32 | 177.33 | 23.85 | 0.00 | 23.85 |
Maximum of Months | 162.33 | 25.66 | 348.00 | 24.10 | 162.33 | 24.13 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 31.00 | 23.22 | 180.83 | 23.83 | 2.00 | 23.83 |
February | 12.17 | 23.33 | 237.67 | 23.90 | 0.50 | 23.91 |
March | 14.50 | 23.79 | 252.33 | 23.93 | 4.67 | 23.94 |
April | 10.50 | 25.58 | 307.33 | 24.04 | 10.50 | 24.09 |
May | 23.83 | 25.30 | 344.00 | 24.09 | 23.83 | 24.16 |
June | 75.00 | 24.37 | 336.00 | 24.07 | 75.00 | 24.11 |
July | 130.00 | 24.29 | 338.00 | 24.12 | 130.00 | 24.15 |
August | 135.33 | 24.19 | 348.00 | 24.06 | 135.33 | 24.08 |
September | 85.50 | 24.42 | 330.00 | 24.11 | 85.50 | 24.16 |
October | 40.00 | 24.77 | 340.00 | 24.09 | 40.00 | 24.16 |
November | 14.83 | 24.56 | 330.00 | 23.99 | 14.83 | 24.02 |
December | 23.00 | 24.06 | 288.67 | 23.95 | 18.33 | 23.97 |
Annual Sum or Average | 595.67 | 24.30 | 3632.83 | 24.03 | 540.50 | 24.08 |
Minimum of Months | 10.50 | 23.22 | 180.83 | 23.83 | 0.50 | 23.83 |
Maximum of Months | 135.33 | 25.58 | 348.00 | 24.12 | 135.33 | 24.16 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 23.84517 | 45.15765 | 0.44144 | 9.25508 |
February | 448.00000 | 23.87950 | 48.21439 | 0.48447 | 10.03041 |
March | 497.00000 | 23.90946 | 46.02275 | 0.49187 | 10.19721 |
April | 479.00000 | 23.93518 | 49.27154 | 0.55180 | 11.48574 |
May | 496.00000 | 23.98369 | 51.05267 | -0.1964 | 6.07711 |
June | 481.00000 | 23.99140 | 58.16939 | -0.1139 | 5.60792 |
July | 495.00000 | 23.98532 | 60.36496 | -0.0626 | 5.46854 |
August | 497.00000 | 24.00196 | 61.67630 | -0.0307 | 5.41840 |
September | 479.00000 | 23.98103 | 60.55200 | -0.0774 | 5.42645 |
October | 496.00000 | 23.98292 | 53.94476 | 0.66020 | 14.37599 |
November | 480.00000 | 23.95234 | 50.95461 | 0.58913 | 12.41925 |
December | 496.00000 | 23.89774 | 49.40397 | 0.51016 | 10.57338 |
Annual Sum or Average | 5840.00000 | 23.94580 | 52.91637 | 0.26927 | 8.85287 |
Minimum of Months | 448.00000 | 23.84517 | 45.15765 | -0.1964 | 5.41840 |
Maximum of Months | 497.00000 | 24.00196 | 61.67630 | 0.66020 | 14.37599 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 23.86490 | 43.47190 | 0.43014 | 9.00821 |
February | 448.00000 | 23.89265 | 45.95829 | 0.46595 | 9.64333 |
March | 497.00000 | 23.91938 | 44.09015 | 0.47175 | 9.77056 |
April | 479.00000 | 23.94053 | 46.73595 | 0.52021 | 10.77916 |
May | 496.00000 | 23.98508 | 48.86513 | -0.2494 | 6.56740 |
June | 481.00000 | 23.99105 | 55.59071 | -0.1782 | 6.00535 |
July | 495.00000 | 23.98450 | 58.25945 | -0.1314 | 5.73733 |
August | 497.00000 | 24.00096 | 59.76828 | -0.1049 | 5.62258 |
September | 479.00000 | 23.98048 | 58.03817 | -0.1478 | 5.76506 |
October | 496.00000 | 23.98202 | 51.52517 | 0.61203 | 13.07937 |
November | 480.00000 | 23.95325 | 48.92146 | 0.55287 | 11.55112 |
December | 496.00000 | 23.90444 | 47.11909 | 0.48587 | 10.05509 |
Annual Sum or Average | 5840.00000 | 23.95023 | 50.71581 | 0.22573 | 8.62475 |
Minimum of Months | 448.00000 | 23.86490 | 43.47190 | -0.2494 | 5.62258 |
Maximum of Months | 497.00000 | 24.00096 | 59.76828 | 0.61203 | 13.07937 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 23.92605 | 44.62076 | 0.44567 | 9.36608 |
February | 336.00000 | 23.97343 | 47.49851 | 0.49117 | 10.20153 |
March | 379.00000 | 24.01951 | 45.17134 | 0.49941 | 10.43695 |
April | 360.00000 | 24.08536 | 47.83909 | 0.55943 | 11.89926 |
May | 375.00000 | 24.16167 | 49.76047 | -0.1832 | 6.62291 |
June | 366.00000 | 24.17792 | 56.91906 | -0.1038 | 6.29047 |
July | 369.00000 | 24.22265 | 60.11442 | -0.0377 | 6.33135 |
August | 379.00000 | 24.21475 | 61.70131 | -0.0175 | 6.24686 |
September | 360.00000 | 24.18865 | 60.11449 | -0.0601 | 6.20988 |
October | 371.00000 | 24.15480 | 53.15086 | 0.66856 | 14.88520 |
November | 360.00000 | 24.08080 | 51.12858 | 0.60055 | 12.81903 |
December | 369.00000 | 23.99985 | 49.11760 | 0.51856 | 10.80912 |
Annual Sum or Average | 4395.00000 | 24.10135 | 52.28811 | 0.27935 | 9.32719 |
Minimum of Months | 336.00000 | 23.92605 | 44.62076 | -0.1832 | 6.20988 |
Maximum of Months | 379.00000 | 24.22265 | 61.70131 | 0.66856 | 14.88520 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 23.91963 | 44.69005 | 0.44218 | 9.31099 |
February | 336.00000 | 23.97036 | 47.54932 | 0.48924 | 10.16460 |
March | 379.00000 | 24.01820 | 45.18736 | 0.49854 | 10.42015 |
April | 360.00000 | 24.08545 | 47.82067 | 0.56012 | 11.91542 |
May | 375.00000 | 24.16266 | 49.68407 | -0.1795 | 6.60472 |
June | 366.00000 | 24.17912 | 56.80203 | -0.0999 | 6.28666 |
July | 369.00000 | 24.22404 | 59.96553 | -0.0328 | 6.33918 |
August | 379.00000 | 24.21608 | 61.55503 | -0.0130 | 6.25950 |
September | 360.00000 | 24.18991 | 59.97186 | -0.0560 | 6.21400 |
October | 371.00000 | 24.15603 | 53.04050 | 0.67097 | 14.95760 |
November | 360.00000 | 24.08104 | 51.09656 | 0.60145 | 12.84263 |
December | 369.00000 | 23.99810 | 49.15041 | 0.51740 | 10.78512 |
Annual Sum or Average | 4395.00000 | 24.10096 | 52.23547 | 0.28084 | 9.32583 |
Minimum of Months | 336.00000 | 23.91963 | 44.69005 | -0.1795 | 6.21400 |
Maximum of Months | 379.00000 | 24.22404 | 61.55503 | 0.67097 | 14.95760 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 23.90701 | 44.86795 | 0.43639 | 9.21838 |
February | 336.00000 | 23.96285 | 47.73262 | 0.48514 | 10.08419 |
March | 379.00000 | 24.01231 | 45.32877 | 0.49472 | 10.34062 |
April | 360.00000 | 24.08248 | 47.94338 | 0.55754 | 11.84906 |
May | 375.00000 | 24.16012 | 49.75600 | -0.1816 | 6.60531 |
June | 366.00000 | 24.17650 | 56.89762 | -0.1015 | 6.27261 |
July | 369.00000 | 24.22186 | 60.03595 | -0.0333 | 6.31677 |
August | 379.00000 | 24.21382 | 61.63284 | -0.0136 | 6.23439 |
September | 360.00000 | 24.18749 | 60.07217 | -0.0569 | 6.19480 |
October | 371.00000 | 24.15331 | 53.13454 | 0.66994 | 14.92151 |
November | 360.00000 | 24.07806 | 51.22427 | 0.59963 | 12.79007 |
December | 369.00000 | 23.99241 | 49.33386 | 0.51410 | 10.71439 |
Annual Sum or Average | 4395.00000 | 24.09661 | 52.35549 | 0.27851 | 9.27954 |
Minimum of Months | 336.00000 | 23.90701 | 44.86795 | -0.1816 | 6.19480 |
Maximum of Months | 379.00000 | 24.22186 | 61.63284 | 0.66994 | 14.92151 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.87805 | 46.15667 | 0.43433 | 9.12294 |
February | 308.00000 | 23.91098 | 48.86811 | 0.48014 | 9.92398 |
March | 348.00000 | 23.92332 | 46.55941 | 0.48545 | 10.07084 |
April | 330.00000 | 23.97388 | 49.09348 | 0.54790 | 11.51968 |
May | 344.00000 | 23.99662 | 50.97064 | -0.2039 | 6.40431 |
June | 336.00000 | 23.99541 | 58.01146 | -0.1277 | 5.95269 |
July | 338.00000 | 24.04106 | 61.15376 | -0.0546 | 5.84474 |
August | 348.00000 | 24.00190 | 62.80548 | -0.0419 | 5.62479 |
September | 330.00000 | 24.02263 | 61.03210 | -0.0770 | 5.80910 |
October | 340.00000 | 24.00318 | 53.88163 | 0.65615 | 14.37139 |
November | 330.00000 | 23.96406 | 52.28342 | 0.58929 | 12.42885 |
December | 338.00000 | 23.93226 | 50.54986 | 0.50860 | 10.55094 |
Annual Sum or Average | 4030.00000 | 23.97058 | 53.47393 | 0.26383 | 8.95079 |
Minimum of Months | 308.00000 | 23.87805 | 46.15667 | -0.2039 | 5.62479 |
Maximum of Months | 348.00000 | 24.04106 | 62.80548 | 0.65615 | 14.37139 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.87940 | 46.07950 | 0.42391 | 8.93069 |
February | 308.00000 | 23.91146 | 48.80586 | 0.46808 | 9.68036 |
March | 348.00000 | 23.92348 | 46.49185 | 0.47165 | 9.78726 |
April | 330.00000 | 23.97309 | 49.01893 | 0.53123 | 11.13686 |
May | 344.00000 | 23.99552 | 50.84829 | -0.2326 | 6.65775 |
June | 336.00000 | 23.99412 | 57.91043 | -0.1585 | 6.13312 |
July | 338.00000 | 24.03984 | 61.05847 | -0.0877 | 5.94432 |
August | 348.00000 | 24.00052 | 62.73459 | -0.0761 | 5.70597 |
September | 330.00000 | 24.02101 | 60.98365 | -0.1088 | 5.92399 |
October | 340.00000 | 24.00185 | 53.77601 | 0.63534 | 13.80392 |
November | 330.00000 | 23.96299 | 52.21763 | 0.57226 | 12.00845 |
December | 338.00000 | 23.93236 | 50.49779 | 0.49618 | 10.28571 |
Annual Sum or Average | 4030.00000 | 23.96993 | 53.39511 | 0.24193 | 8.81701 |
Minimum of Months | 308.00000 | 23.87940 | 46.07950 | -0.2326 | 5.70597 |
Maximum of Months | 348.00000 | 24.03984 | 62.73459 | 0.63534 | 13.80392 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.87682 | 46.13895 | 0.42158 | 8.89316 |
February | 308.00000 | 23.91001 | 48.87226 | 0.46603 | 9.64169 |
March | 348.00000 | 23.92279 | 46.54387 | 0.46972 | 9.74999 |
April | 330.00000 | 23.97275 | 49.06684 | 0.52960 | 11.09976 |
May | 344.00000 | 23.99530 | 50.88562 | -0.2345 | 6.67526 |
June | 336.00000 | 23.99385 | 57.95632 | -0.1603 | 6.14250 |
July | 338.00000 | 24.03967 | 61.10184 | -0.0893 | 5.94823 |
August | 348.00000 | 24.00041 | 62.77901 | -0.0776 | 5.70929 |
September | 330.00000 | 24.02076 | 61.02965 | -0.1103 | 5.92881 |
October | 340.00000 | 24.00154 | 53.81490 | 0.63422 | 13.77363 |
November | 330.00000 | 23.96280 | 52.26503 | 0.57101 | 11.97769 |
December | 338.00000 | 23.93162 | 50.55961 | 0.49460 | 10.25293 |
Annual Sum or Average | 4030.00000 | 23.96933 | 53.44421 | 0.24026 | 8.80010 |
Minimum of Months | 308.00000 | 23.87682 | 46.13895 | -0.2345 | 5.70929 |
Maximum of Months | 348.00000 | 24.03967 | 62.77901 | 0.63422 | 13.77363 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.86768 | 46.27894 | 0.41763 | 8.84174 |
February | 308.00000 | 23.90499 | 49.02512 | 0.46323 | 9.59522 |
March | 348.00000 | 23.92046 | 46.64665 | 0.46784 | 9.71889 |
April | 330.00000 | 23.97236 | 49.12688 | 0.52987 | 11.10739 |
May | 344.00000 | 23.99538 | 50.86039 | -0.2303 | 6.63844 |
June | 336.00000 | 23.99409 | 57.88602 | -0.1548 | 6.11034 |
July | 338.00000 | 24.04006 | 60.98052 | -0.0823 | 5.92843 |
August | 348.00000 | 24.00076 | 62.62017 | -0.0698 | 5.69054 |
September | 330.00000 | 24.02121 | 60.90515 | -0.1035 | 5.90519 |
October | 340.00000 | 24.00181 | 53.74277 | 0.63809 | 13.87942 |
November | 330.00000 | 23.96251 | 52.26115 | 0.57315 | 12.03047 |
December | 338.00000 | 23.92971 | 50.66727 | 0.49390 | 10.24200 |
Annual Sum or Average | 4030.00000 | 23.96791 | 53.44202 | 0.24263 | 8.79144 |
Minimum of Months | 308.00000 | 23.86768 | 46.27894 | -0.2303 | 5.69054 |
Maximum of Months | 348.00000 | 24.04006 | 62.62017 | 0.63809 | 13.87942 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.85606 | 46.25995 | 0.42158 | 8.97081 |
February | 308.00000 | 23.89690 | 49.11870 | 0.46964 | 9.76032 |
March | 348.00000 | 23.91645 | 46.73296 | 0.47881 | 9.98322 |
April | 330.00000 | 23.97843 | 49.07767 | 0.55643 | 11.74505 |
May | 344.00000 | 24.00126 | 50.51094 | -0.1673 | 6.17330 |
June | 336.00000 | 24.00003 | 57.16019 | -0.0851 | 5.81655 |
July | 338.00000 | 24.04708 | 59.96695 | -0.0030 | 5.85127 |
August | 348.00000 | 24.00577 | 61.31187 | 0.01604 | 5.65148 |
September | 330.00000 | 24.02971 | 59.76196 | -0.0258 | 5.78444 |
October | 340.00000 | 24.01024 | 53.04286 | 0.68533 | 15.22670 |
November | 330.00000 | 23.96893 | 51.78900 | 0.60708 | 12.90082 |
December | 338.00000 | 23.93137 | 50.51855 | 0.50774 | 10.55862 |
Annual Sum or Average | 4030.00000 | 23.97055 | 52.95887 | 0.28613 | 9.01755 |
Minimum of Months | 308.00000 | 23.85606 | 46.25995 | -0.1673 | 5.65148 |
Maximum of Months | 348.00000 | 24.04708 | 61.31187 | 0.68533 | 15.22670 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.141381E+11 | 0.418098E+10 | 452.10 | 0.108546E+11 | 0.328345E+10 | 0.00 | 1.00 | 29-JAN-08:62 | 0.00 | 01-JAN-00:10 | 38766.45 | 29-JAN-08:62 | 28202.90 | 29-JAN-08:62 | 13303.00 | 30-JAN-09:03 | 9311.19 | 29-JAN-08:62 | 0.00 | 01-JAN-00:10 |
February | 0.162142E+11 | 0.480893E+10 | 419.89 | 0.122063E+11 | 0.400783E+10 | 0.00 | 1.00 | 06-FEB-09:02 | 0.00 | 01-FEB-00:05 | 68677.23 | 09-FEB-09:02 | 42400.86 | 09-FEB-09:02 | 26276.38 | 09-FEB-09:02 | 16336.43 | 09-FEB-09:02 | 0.00 | 01-FEB-00:05 |
March | 0.223431E+11 | 0.673790E+10 | 470.65 | 0.175521E+11 | 0.479096E+10 | 0.00 | 1.00 | 01-MAR-09:01 | 0.00 | 01-MAR-00:05 | 78065.18 | 01-MAR-09:01 | 70551.97 | 28-MAR-08:61 | 24422.29 | 01-MAR-09:01 | 19705.10 | 01-MAR-09:01 | 0.00 | 01-MAR-00:05 |
April | 0.310991E+11 | 0.946535E+10 | 459.75 | 0.236564E+11 | 0.744273E+10 | 0.00 | 1.00 | 03-APR-08:61 | 0.00 | 01-APR-00:05 | 79821.78 | 30-APR-07:02 | 70732.33 | 27-APR-08:61 | 34231.54 | 30-APR-07:02 | 20407.11 | 28-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.456752E+11 | 0.142054E+11 | 493.22 | 0.345022E+11 | 0.111730E+11 | 0.00 | 1.00 | 01-MAY-08:62 | 0.00 | 01-MAY-00:10 | 82754.99 | 30-MAY-08:61 | 69403.41 | 11-MAY-08:61 | 41105.32 | 30-MAY-08:03 | 22119.92 | 10-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.553848E+11 | 0.167632E+11 | 485.97 | 0.369940E+11 | 0.183909E+11 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 84373.72 | 08-JUN-08:61 | 66122.09 | 02-JUN-08:61 | 47533.83 | 08-JUN-08:03 | 21893.76 | 05-JUN-08:03 | 0.00 | 01-JUN-00:10 |
July | 0.663582E+11 | 0.202416E+11 | 502.60 | 0.427746E+11 | 0.235836E+11 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:03 | 83284.11 | 18-JUL-08:03 | 66322.06 | 04-JUL-07:01 | 48102.19 | 26-JUL-08:04 | 22140.78 | 19-JUL-08:03 | 0.00 | 01-JUL-00:03 |
August | 0.701147E+11 | 0.212496E+11 | 503.41 | 0.441031E+11 | 0.260116E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 83630.81 | 08-AUG-07:01 | 61140.13 | 06-AUG-07:01 | 51631.59 | 08-AUG-08:06 | 22373.05 | 05-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.598185E+11 | 0.175812E+11 | 485.22 | 0.376298E+11 | 0.221887E+11 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 | 84156.58 | 23-SEP-08:61 | 60165.12 | 26-SEP-08:61 | 49566.90 | 11-SEP-08:04 | 21855.35 | 30-SEP-08:61 | 0.00 | 01-SEP-00:03 |
October | 0.472029E+11 | 0.139102E+11 | 489.03 | 0.329318E+11 | 0.142711E+11 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 84335.74 | 07-OCT-08:61 | 66263.45 | 21-OCT-08:62 | 47771.38 | 07-OCT-08:03 | 20780.44 | 06-OCT-08:03 | 0.00 | 01-OCT-00:10 |
November | 0.328935E+11 | 0.963393E+10 | 459.55 | 0.237574E+11 | 0.913607E+10 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-00:10 | 81536.85 | 03-NOV-08:61 | 62045.18 | 18-NOV-09:02 | 37319.26 | 03-NOV-08:03 | 19692.03 | 09-NOV-09:01 | 0.00 | 01-NOV-00:10 |
December | 0.206296E+11 | 0.602221E+10 | 471.51 | 0.148992E+11 | 0.573036E+10 | 0.00 | 1.00 | 01-DEC-09:02 | 0.00 | 01-DEC-01:05 | 77266.28 | 12-DEC-09:02 | 55805.87 | 12-DEC-09:02 | 21460.41 | 12-DEC-09:02 | 18793.27 | 12-DEC-09:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.481872E+12 | 0.144800E+12 | 5692.90 | 0.331862E+12 | 0.150010E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.141381E+11 | 0.418098E+10 | 419.89 | 0.108546E+11 | 0.328345E+10 | 0.00 | 1.00 | 0.00 | 38766.45 | 28202.90 | 13303.00 | 9311.19 | 0.00 | |||||||
Maximum of Months | 0.701147E+11 | 0.212496E+11 | 503.41 | 0.441031E+11 | 0.260116E+11 | 0.00 | 1.00 | 0.00 | 84373.72 | 70732.33 | 51631.59 | 22373.05 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.782833E+10 | 0.206441E+10 | 460.43 | 0.612209E+10 | 0.170624E+10 | 0.00 | 1.00 | 29-JAN-08:62 | 0.00 | 01-JAN-00:10 | 21353.50 | 29-JAN-08:62 | 16725.12 | 29-JAN-08:62 | 5675.87 | 30-JAN-09:03 | 4602.30 | 29-JAN-08:62 | 0.00 | 01-JAN-00:10 |
February | 0.867765E+10 | 0.229683E+10 | 423.72 | 0.666474E+10 | 0.201291E+10 | 0.00 | 1.00 | 06-FEB-09:02 | 0.00 | 01-FEB-00:05 | 33700.65 | 09-FEB-09:02 | 22771.13 | 07-FEB-09:02 | 11230.93 | 09-FEB-09:02 | 7319.47 | 07-FEB-09:02 | 0.00 | 01-FEB-00:05 |
March | 0.115144E+11 | 0.310430E+10 | 473.56 | 0.919242E+10 | 0.232201E+10 | 0.00 | 1.00 | 01-MAR-09:01 | 0.00 | 01-MAR-00:05 | 38983.71 | 01-MAR-09:01 | 35700.72 | 28-MAR-08:61 | 10693.64 | 01-MAR-09:01 | 8877.62 | 01-MAR-09:01 | 0.00 | 01-MAR-00:05 |
April | 0.152956E+11 | 0.418439E+10 | 459.80 | 0.118926E+11 | 0.340293E+10 | 0.00 | 1.00 | 02-APR-07:03 | 0.00 | 01-APR-00:05 | 39784.68 | 18-APR-08:62 | 35606.08 | 29-APR-08:61 | 14378.42 | 18-APR-08:62 | 9219.95 | 28-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.218059E+11 | 0.613464E+10 | 493.69 | 0.168074E+11 | 0.499853E+10 | 0.00 | 1.00 | 01-MAY-08:62 | 0.00 | 01-MAY-00:10 | 40848.74 | 30-MAY-08:61 | 35342.84 | 08-MAY-08:61 | 17556.42 | 30-MAY-08:03 | 9996.80 | 10-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.261181E+11 | 0.719099E+10 | 485.67 | 0.179083E+11 | 0.820980E+10 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 41863.01 | 08-JUN-08:61 | 34772.14 | 02-JUN-08:61 | 21023.57 | 08-JUN-08:03 | 9892.83 | 05-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.312308E+11 | 0.867201E+10 | 502.41 | 0.205291E+11 | 0.107017E+11 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:03 | 42063.78 | 26-JUL-08:61 | 34627.44 | 04-JUL-07:01 | 22386.36 | 26-JUL-08:04 | 10016.01 | 19-JUL-08:03 | 0.00 | 01-JUL-00:03 |
August | 0.329878E+11 | 0.909423E+10 | 503.41 | 0.211022E+11 | 0.118856E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 42088.88 | 21-AUG-08:61 | 32511.20 | 06-AUG-07:01 | 24567.63 | 08-AUG-08:04 | 10090.34 | 05-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.280427E+11 | 0.750181E+10 | 485.31 | 0.181017E+11 | 0.994093E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:03 | 42290.50 | 11-SEP-08:61 | 32324.90 | 26-SEP-08:61 | 22878.73 | 11-SEP-08:04 | 9850.10 | 30-SEP-08:61 | 0.00 | 01-SEP-00:03 |
October | 0.223729E+11 | 0.597081E+10 | 488.04 | 0.159837E+11 | 0.638924E+10 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 41858.24 | 07-OCT-08:61 | 34288.57 | 21-OCT-08:62 | 20854.84 | 07-OCT-08:03 | 9409.38 | 06-OCT-08:03 | 0.00 | 01-OCT-00:10 |
November | 0.160856E+11 | 0.423312E+10 | 459.71 | 0.118083E+11 | 0.427722E+10 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-00:10 | 40466.98 | 01-NOV-08:61 | 32793.85 | 12-NOV-08:62 | 16185.26 | 01-NOV-08:03 | 8864.65 | 09-NOV-09:01 | 0.00 | 01-NOV-00:10 |
December | 0.107458E+11 | 0.280544E+10 | 473.51 | 0.794775E+10 | 0.279801E+10 | 0.00 | 1.00 | 01-DEC-09:02 | 0.00 | 01-DEC-01:05 | 38486.47 | 12-DEC-09:02 | 29735.39 | 12-DEC-09:02 | 8751.08 | 12-DEC-09:02 | 8432.99 | 12-DEC-09:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.232705E+12 | 0.632530E+11 | 5709.27 | 0.164060E+12 | 0.686451E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.782833E+10 | 0.206441E+10 | 423.72 | 0.612209E+10 | 0.170624E+10 | 0.00 | 1.00 | 0.00 | 21353.50 | 16725.12 | 5675.87 | 4602.30 | 0.00 | |||||||
Maximum of Months | 0.329878E+11 | 0.909423E+10 | 503.41 | 0.211022E+11 | 0.118856E+11 | 0.00 | 1.00 | 0.00 | 42290.50 | 35700.72 | 24567.63 | 10090.34 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.522735E+10 | 0.138478E+10 | 310.26 | 0.404787E+10 | 0.117948E+10 | 0.00 | 1.00 | 29-JAN-09:02 | 0.00 | 01-JAN-00:10 | 27672.69 | 29-JAN-09:02 | 18708.14 | 29-JAN-09:02 | 8964.55 | 29-JAN-09:02 | 5967.45 | 29-JAN-09:02 | 0.00 | 01-JAN-00:10 |
February | 0.621219E+10 | 0.165143E+10 | 293.54 | 0.474749E+10 | 0.146471E+10 | 0.00 | 1.00 | 06-FEB-08:62 | 0.00 | 01-FEB-00:05 | 36322.38 | 09-FEB-08:62 | 21584.47 | 09-FEB-08:62 | 14737.91 | 09-FEB-08:62 | 7632.42 | 09-FEB-08:62 | 0.00 | 01-FEB-00:05 |
March | 0.873155E+10 | 0.236483E+10 | 338.01 | 0.698123E+10 | 0.175032E+10 | 0.00 | 1.00 | 01-MAR-08:62 | 0.00 | 01-MAR-00:05 | 39396.13 | 01-MAR-08:62 | 35824.27 | 28-MAR-07:02 | 13302.34 | 01-MAR-08:62 | 8651.44 | 02-MAR-08:61 | 0.00 | 01-MAR-00:05 |
April | 0.119201E+11 | 0.326343E+10 | 325.07 | 0.931222E+10 | 0.260793E+10 | 0.00 | 1.00 | 02-APR-08:62 | 0.00 | 01-APR-00:05 | 40847.82 | 30-APR-08:62 | 34128.75 | 25-APR-07:02 | 19161.33 | 30-APR-08:62 | 8632.74 | 03-APR-07:02 | 0.00 | 01-APR-00:05 |
May | 0.177979E+11 | 0.495689E+10 | 361.16 | 0.137086E+11 | 0.408923E+10 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 41919.64 | 30-MAY-07:01 | 35485.62 | 10-MAY-07:01 | 22882.23 | 01-MAY-07:02 | 9518.17 | 28-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.216282E+11 | 0.589044E+10 | 363.73 | 0.147679E+11 | 0.686022E+10 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 42502.04 | 08-JUN-07:01 | 30053.59 | 02-JUN-07:01 | 25723.81 | 25-JUN-08:04 | 9709.85 | 05-JUN-07:04 | 0.00 | 01-JUN-00:10 |
July | 0.259209E+11 | 0.708375E+10 | 371.15 | 0.167311E+11 | 0.918983E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 42095.95 | 26-JUL-07:03 | 33645.76 | 04-JUL-08:61 | 27213.13 | 31-JUL-06:03 | 9849.88 | 23-JUL-08:03 | 0.00 | 01-JUL-00:03 |
August | 0.279574E+11 | 0.759117E+10 | 380.30 | 0.175586E+11 | 0.103988E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 42095.95 | 08-AUG-07:01 | 28130.55 | 06-AUG-08:61 | 25735.80 | 08-AUG-07:06 | 9919.65 | 06-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.230199E+11 | 0.607845E+10 | 357.40 | 0.147279E+11 | 0.829192E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 | 42505.51 | 25-SEP-07:01 | 27220.03 | 26-SEP-07:01 | 26919.97 | 11-SEP-07:04 | 9615.68 | 04-SEP-08:61 | 0.00 | 01-SEP-00:03 |
October | 0.181595E+11 | 0.477430E+10 | 354.40 | 0.127958E+11 | 0.536367E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 42506.45 | 07-OCT-07:01 | 32222.26 | 20-OCT-07:02 | 25871.57 | 08-OCT-08:04 | 9024.13 | 08-OCT-08:13 | 0.00 | 01-OCT-00:10 |
November | 0.128473E+11 | 0.335616E+10 | 327.38 | 0.925523E+10 | 0.359202E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 41233.97 | 03-NOV-07:02 | 32232.76 | 19-NOV-09:02 | 19801.45 | 03-NOV-07:02 | 8693.31 | 20-NOV-08:61 | 0.00 | 01-NOV-00:10 |
December | 0.778009E+10 | 0.203532E+10 | 327.71 | 0.567785E+10 | 0.210224E+10 | 0.00 | 1.00 | 10-DEC-09:02 | 0.00 | 01-DEC-00:10 | 38845.78 | 12-DEC-08:62 | 27851.56 | 12-DEC-08:62 | 11501.87 | 11-DEC-08:62 | 8370.56 | 12-DEC-08:62 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.187202E+12 | 0.504310E+11 | 4110.10 | 0.130312E+12 | 0.568904E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.522735E+10 | 0.138478E+10 | 293.54 | 0.404787E+10 | 0.117948E+10 | 0.00 | 1.00 | 0.00 | 27672.69 | 18708.14 | 8964.55 | 5967.45 | 0.00 | |||||||
Maximum of Months | 0.279574E+11 | 0.759117E+10 | 380.30 | 0.175586E+11 | 0.103988E+11 | 0.00 | 1.00 | 0.00 | 42506.45 | 35824.27 | 27213.13 | 9919.65 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.515307E+10 | 0.136651E+10 | 308.93 | 0.398694E+10 | 0.116613E+10 | 0.00 | 1.00 | 29-JAN-09:02 | 0.00 | 01-JAN-00:10 | 27270.24 | 29-JAN-09:02 | 18412.81 | 29-JAN-09:02 | 8857.42 | 29-JAN-09:02 | 5881.23 | 29-JAN-09:02 | 0.00 | 01-JAN-00:10 |
February | 0.616709E+10 | 0.164067E+10 | 293.21 | 0.471198E+10 | 0.145511E+10 | 0.00 | 1.00 | 06-FEB-08:62 | 0.00 | 01-FEB-00:05 | 36384.40 | 09-FEB-08:62 | 21625.50 | 09-FEB-08:62 | 14758.89 | 09-FEB-08:62 | 7645.29 | 09-FEB-08:62 | 0.00 | 01-FEB-00:05 |
March | 0.871195E+10 | 0.236058E+10 | 337.65 | 0.696522E+10 | 0.174673E+10 | 0.00 | 1.00 | 01-MAR-08:62 | 0.00 | 01-MAR-00:05 | 39456.08 | 01-MAR-08:62 | 35896.14 | 28-MAR-07:02 | 13340.63 | 01-MAR-08:62 | 8665.53 | 02-MAR-08:61 | 0.00 | 01-MAR-00:05 |
April | 0.119476E+11 | 0.327093E+10 | 325.35 | 0.933625E+10 | 0.261137E+10 | 0.00 | 1.00 | 02-APR-08:62 | 0.00 | 01-APR-00:05 | 40926.73 | 30-APR-08:62 | 34452.12 | 26-APR-07:02 | 19122.53 | 30-APR-08:62 | 8647.30 | 03-APR-07:02 | 0.00 | 01-APR-00:05 |
May | 0.179126E+11 | 0.498635E+10 | 362.04 | 0.138057E+11 | 0.410685E+10 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 41911.19 | 30-MAY-07:01 | 35554.86 | 10-MAY-07:01 | 22827.62 | 01-MAY-07:02 | 9533.35 | 28-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.217717E+11 | 0.592781E+10 | 364.30 | 0.148822E+11 | 0.688954E+10 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 42570.56 | 08-JUN-07:01 | 30132.29 | 02-JUN-07:01 | 25564.58 | 25-JUN-08:04 | 9727.58 | 05-JUN-07:04 | 0.00 | 01-JUN-00:10 |
July | 0.261113E+11 | 0.713442E+10 | 371.21 | 0.168847E+11 | 0.922659E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 42174.39 | 02-JUL-07:01 | 33719.74 | 04-JUL-08:61 | 26962.21 | 31-JUL-06:03 | 9866.05 | 23-JUL-08:03 | 0.00 | 01-JUL-00:03 |
August | 0.281429E+11 | 0.764049E+10 | 380.61 | 0.177073E+11 | 0.104356E+11 | 0.00 | 1.00 | 01-AUG-06:03 | 0.00 | 01-AUG-00:10 | 42174.39 | 21-AUG-06:03 | 28273.61 | 06-AUG-08:61 | 25573.02 | 08-AUG-07:06 | 9934.09 | 06-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.231797E+11 | 0.611965E+10 | 358.72 | 0.148538E+11 | 0.832594E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 | 42574.04 | 25-SEP-07:01 | 27324.42 | 26-SEP-07:01 | 26606.79 | 11-SEP-07:04 | 9629.75 | 04-SEP-08:61 | 0.00 | 01-SEP-00:03 |
October | 0.182879E+11 | 0.480530E+10 | 355.42 | 0.128981E+11 | 0.538983E+10 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 42574.98 | 07-OCT-07:03 | 32335.30 | 20-OCT-07:02 | 25718.51 | 08-OCT-08:04 | 9042.82 | 08-OCT-08:13 | 0.00 | 01-OCT-00:10 |
November | 0.128865E+11 | 0.336601E+10 | 327.58 | 0.928847E+10 | 0.359806E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 41309.53 | 03-NOV-07:02 | 32325.54 | 19-NOV-09:02 | 19781.24 | 03-NOV-07:02 | 8706.81 | 20-NOV-08:61 | 0.00 | 01-NOV-00:10 |
December | 0.774896E+10 | 0.202823E+10 | 327.29 | 0.565382E+10 | 0.209515E+10 | 0.00 | 1.00 | 10-DEC-09:02 | 0.00 | 01-DEC-00:10 | 38910.87 | 12-DEC-08:62 | 27909.00 | 12-DEC-08:62 | 11593.15 | 11-DEC-08:62 | 8384.33 | 12-DEC-08:62 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.188021E+12 | 0.506469E+11 | 4112.31 | 0.130974E+12 | 0.570469E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.515307E+10 | 0.136651E+10 | 293.21 | 0.398694E+10 | 0.116613E+10 | 0.00 | 1.00 | 0.00 | 27270.24 | 18412.81 | 8857.42 | 5881.23 | 0.00 | |||||||
Maximum of Months | 0.281429E+11 | 0.764049E+10 | 380.61 | 0.177073E+11 | 0.104356E+11 | 0.00 | 1.00 | 0.00 | 42574.98 | 35896.14 | 26962.21 | 9934.09 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.495856E+10 | 0.131783E+10 | 307.10 | 0.382777E+10 | 0.113078E+10 | 0.00 | 1.00 | 29-JAN-09:02 | 0.00 | 01-JAN-00:10 | 25534.96 | 29-JAN-09:02 | 17132.98 | 29-JAN-09:02 | 8401.99 | 29-JAN-09:02 | 5509.13 | 29-JAN-09:02 | 0.00 | 01-JAN-00:10 |
February | 0.599580E+10 | 0.159842E+10 | 291.71 | 0.457525E+10 | 0.142055E+10 | 0.00 | 1.00 | 06-FEB-08:62 | 0.00 | 01-FEB-00:05 | 34319.37 | 09-FEB-08:62 | 20263.22 | 09-FEB-08:62 | 14056.15 | 09-FEB-08:62 | 7214.40 | 09-FEB-08:62 | 0.00 | 01-FEB-00:05 |
March | 0.852953E+10 | 0.231580E+10 | 335.78 | 0.681350E+10 | 0.171604E+10 | 0.00 | 1.00 | 01-MAR-08:62 | 0.00 | 01-MAR-00:05 | 39381.84 | 01-MAR-08:62 | 35814.48 | 28-MAR-07:02 | 13419.09 | 01-MAR-08:62 | 8654.09 | 02-MAR-08:61 | 0.00 | 01-MAR-00:05 |
April | 0.117941E+11 | 0.323408E+10 | 325.15 | 0.920813E+10 | 0.258601E+10 | 0.00 | 1.00 | 02-APR-08:62 | 0.00 | 01-APR-00:05 | 40856.54 | 30-APR-08:62 | 34090.01 | 25-APR-07:02 | 19158.13 | 30-APR-08:62 | 8633.75 | 03-APR-07:02 | 0.00 | 01-APR-00:05 |
May | 0.177940E+11 | 0.495637E+10 | 360.85 | 0.137032E+11 | 0.409085E+10 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 41862.52 | 30-MAY-07:01 | 35489.15 | 10-MAY-07:01 | 22844.00 | 01-MAY-07:02 | 9519.49 | 28-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.216503E+11 | 0.589567E+10 | 363.64 | 0.147838E+11 | 0.686649E+10 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 42508.04 | 08-JUN-07:01 | 30050.03 | 02-JUN-07:01 | 25653.90 | 25-JUN-08:04 | 9712.83 | 05-JUN-07:04 | 0.00 | 01-JUN-00:10 |
July | 0.260229E+11 | 0.710968E+10 | 371.11 | 0.168127E+11 | 0.921021E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 42112.45 | 02-JUL-07:01 | 33657.63 | 04-JUL-08:61 | 26969.21 | 31-JUL-06:03 | 9851.51 | 23-JUL-08:03 | 0.00 | 01-JUL-00:03 |
August | 0.280463E+11 | 0.761329E+10 | 380.34 | 0.176292E+11 | 0.104172E+11 | 0.00 | 1.00 | 01-AUG-06:03 | 0.00 | 01-AUG-00:10 | 42112.45 | 21-AUG-06:03 | 28216.26 | 06-AUG-08:61 | 25609.90 | 08-AUG-07:06 | 9919.75 | 06-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.230732E+11 | 0.609152E+10 | 358.10 | 0.147704E+11 | 0.830281E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 | 42511.52 | 25-SEP-07:01 | 27213.00 | 26-SEP-07:01 | 26602.22 | 11-SEP-07:04 | 9615.66 | 04-SEP-08:61 | 0.00 | 01-SEP-00:03 |
October | 0.181727E+11 | 0.477731E+10 | 353.75 | 0.128044E+11 | 0.536832E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 42512.45 | 07-OCT-07:01 | 32197.41 | 20-OCT-07:02 | 25779.56 | 08-OCT-08:04 | 9027.69 | 08-OCT-08:13 | 0.00 | 01-OCT-00:10 |
November | 0.127495E+11 | 0.333443E+10 | 327.43 | 0.917748E+10 | 0.357201E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 41237.79 | 03-NOV-07:02 | 32197.89 | 19-NOV-09:02 | 19849.01 | 03-NOV-07:02 | 8694.55 | 20-NOV-08:61 | 0.00 | 01-NOV-00:10 |
December | 0.756752E+10 | 0.198441E+10 | 326.34 | 0.551083E+10 | 0.205668E+10 | 0.00 | 1.00 | 10-DEC-09:02 | 0.00 | 01-DEC-00:10 | 38838.41 | 12-DEC-08:62 | 27772.83 | 12-DEC-08:62 | 11125.95 | 11-DEC-08:62 | 8370.26 | 12-DEC-08:62 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.186355E+12 | 0.502288E+11 | 4101.29 | 0.129617E+12 | 0.567379E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.495856E+10 | 0.131783E+10 | 291.71 | 0.382777E+10 | 0.113078E+10 | 0.00 | 1.00 | 0.00 | 25534.96 | 17132.98 | 8401.99 | 5509.13 | 0.00 | |||||||
Maximum of Months | 0.280463E+11 | 0.761329E+10 | 380.34 | 0.176292E+11 | 0.104172E+11 | 0.00 | 1.00 | 0.00 | 42512.45 | 35814.48 | 26969.21 | 9919.75 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.912903E+10 | 0.246540E+10 | 309.16 | 0.692398E+10 | 0.220505E+10 | 0.00 | 1.00 | 29-JAN-10:02 | 0.00 | 01-JAN-00:10 | 71777.01 | 29-JAN-10:02 | 49740.99 | 29-JAN-10:02 | 22036.02 | 29-JAN-10:02 | 15982.75 | 29-JAN-10:02 | 0.00 | 01-JAN-00:10 |
February | 0.110900E+11 | 0.299970E+10 | 288.50 | 0.832869E+10 | 0.276133E+10 | 0.00 | 1.00 | 05-FEB-10:02 | 0.00 | 01-FEB-00:05 | 69219.04 | 05-FEB-10:02 | 57064.46 | 05-FEB-10:02 | 24894.46 | 07-FEB-09:02 | 16372.43 | 05-FEB-10:02 | 0.00 | 01-FEB-00:05 |
March | 0.159954E+11 | 0.440354E+10 | 334.70 | 0.125878E+11 | 0.340760E+10 | 0.00 | 1.00 | 01-MAR-09:01 | 0.00 | 01-MAR-00:05 | 72086.99 | 01-MAR-09:01 | 65593.86 | 27-MAR-08:61 | 22374.23 | 01-MAR-09:01 | 16622.12 | 01-MAR-09:01 | 0.00 | 01-MAR-00:05 |
April | 0.220385E+11 | 0.611466E+10 | 318.74 | 0.170146E+11 | 0.502394E+10 | 0.00 | 1.00 | 02-APR-09:01 | 0.00 | 01-APR-00:05 | 75543.27 | 30-APR-09:02 | 65122.01 | 26-APR-08:61 | 35017.22 | 30-APR-09:03 | 17234.02 | 28-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.334154E+11 | 0.943152E+10 | 357.38 | 0.255332E+11 | 0.788221E+10 | 0.00 | 1.00 | 01-MAY-08:62 | 0.00 | 01-MAY-00:10 | 76964.66 | 01-MAY-08:62 | 64371.21 | 11-MAY-08:61 | 42996.11 | 01-MAY-08:62 | 18718.65 | 10-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.406543E+11 | 0.112437E+11 | 355.28 | 0.275985E+11 | 0.130558E+11 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 78195.41 | 08-JUN-08:61 | 60969.91 | 02-JUN-08:61 | 45509.57 | 25-JUN-09:04 | 18671.42 | 11-JUN-09:04 | 0.00 | 01-JUN-00:10 |
July | 0.485826E+11 | 0.135014E+11 | 359.77 | 0.312955E+11 | 0.172871E+11 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:03 | 77476.26 | 18-JUL-07:01 | 60308.74 | 04-JUL-09:01 | 48108.33 | 31-JUL-07:01 | 19259.95 | 30-JUL-09:01 | 0.00 | 01-JUL-00:03 |
August | 0.526775E+11 | 0.145451E+11 | 372.22 | 0.329710E+11 | 0.197065E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 77536.08 | 08-AUG-07:01 | 53001.68 | 16-AUG-07:01 | 46051.93 | 08-AUG-08:06 | 18899.59 | 05-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.432811E+11 | 0.116065E+11 | 348.71 | 0.274909E+11 | 0.157902E+11 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 | 78224.85 | 25-SEP-08:03 | 55418.44 | 26-SEP-08:61 | 51459.07 | 11-SEP-07:01 | 18608.78 | 04-SEP-09:01 | 0.00 | 01-SEP-00:03 |
October | 0.338922E+11 | 0.903965E+10 | 346.22 | 0.238143E+11 | 0.100780E+11 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 78189.63 | 07-OCT-08:61 | 60211.02 | 20-OCT-08:61 | 45060.76 | 09-OCT-09:04 | 17552.54 | 06-OCT-08:03 | 0.00 | 01-OCT-00:10 |
November | 0.237738E+11 | 0.629247E+10 | 321.19 | 0.169167E+11 | 0.685710E+10 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-00:10 | 75715.63 | 03-NOV-08:61 | 62698.14 | 19-NOV-10:01 | 35268.76 | 03-NOV-08:03 | 16703.24 | 11-NOV-10:01 | 0.00 | 01-NOV-00:10 |
December | 0.140080E+11 | 0.372464E+10 | 322.06 | 0.100403E+11 | 0.396762E+10 | 0.00 | 1.00 | 01-DEC-09:02 | 0.00 | 01-DEC-00:10 | 72036.31 | 10-DEC-10:01 | 52305.24 | 12-DEC-09:02 | 26164.71 | 03-DEC-10:02 | 16494.50 | 10-DEC-10:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.348538E+12 | 0.953683E+11 | 4033.93 | 0.240516E+12 | 0.108022E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.912903E+10 | 0.246540E+10 | 288.50 | 0.692398E+10 | 0.220505E+10 | 0.00 | 1.00 | 0.00 | 69219.04 | 49740.99 | 22036.02 | 15982.75 | 0.00 | |||||||
Maximum of Months | 0.526775E+11 | 0.145451E+11 | 372.22 | 0.329710E+11 | 0.197065E+11 | 0.00 | 1.00 | 0.00 | 78224.85 | 65593.86 | 51459.07 | 19259.95 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.474079E+10 | 0.125987E+10 | 308.62 | 0.360050E+10 | 0.114030E+10 | 0.00 | 1.00 | 29-JAN-10:02 | 0.00 | 01-JAN-00:10 | 37989.79 | 29-JAN-10:02 | 26311.00 | 29-JAN-10:02 | 11678.79 | 29-JAN-10:02 | 8310.80 | 29-JAN-10:02 | 0.00 | 01-JAN-00:10 |
February | 0.576269E+10 | 0.153447E+10 | 288.62 | 0.433377E+10 | 0.142893E+10 | 0.00 | 1.00 | 05-FEB-10:02 | 0.00 | 01-FEB-00:05 | 36612.70 | 05-FEB-10:02 | 30135.70 | 05-FEB-10:02 | 12290.73 | 07-FEB-09:02 | 8510.89 | 05-FEB-10:02 | 0.00 | 01-FEB-00:05 |
March | 0.831988E+10 | 0.225580E+10 | 334.86 | 0.655429E+10 | 0.176559E+10 | 0.00 | 1.00 | 01-MAR-09:01 | 0.00 | 01-MAR-00:05 | 38126.87 | 01-MAR-09:01 | 34688.60 | 27-MAR-08:61 | 11885.39 | 01-MAR-09:01 | 8641.55 | 01-MAR-09:01 | 0.00 | 01-MAR-00:05 |
April | 0.114936E+11 | 0.314166E+10 | 318.65 | 0.887444E+10 | 0.261916E+10 | 0.00 | 1.00 | 02-APR-09:01 | 0.00 | 01-APR-00:05 | 39990.61 | 30-APR-09:02 | 34413.56 | 26-APR-08:61 | 18386.13 | 30-APR-09:02 | 8960.22 | 28-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.174327E+11 | 0.484960E+10 | 356.54 | 0.133125E+11 | 0.412021E+10 | 0.00 | 1.00 | 01-MAY-08:62 | 0.00 | 01-MAY-00:10 | 40765.05 | 01-MAY-08:62 | 34042.13 | 11-MAY-08:61 | 22801.75 | 01-MAY-08:62 | 9727.20 | 10-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.211835E+11 | 0.577757E+10 | 354.60 | 0.143760E+11 | 0.680747E+10 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 41355.36 | 08-JUN-08:61 | 32181.12 | 02-JUN-08:61 | 24179.77 | 25-JUN-09:04 | 9709.19 | 11-JUN-09:04 | 0.00 | 01-JUN-00:10 |
July | 0.253211E+11 | 0.694090E+10 | 359.85 | 0.163055E+11 | 0.901569E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:03 | 40960.56 | 05-JUL-07:01 | 31895.83 | 04-JUL-09:01 | 25826.87 | 31-JUL-07:01 | 10012.80 | 30-JUL-09:01 | 0.00 | 01-JUL-00:03 |
August | 0.274309E+11 | 0.747121E+10 | 372.06 | 0.171611E+11 | 0.102698E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 41036.27 | 08-AUG-07:01 | 27973.20 | 16-AUG-07:01 | 24411.79 | 27-AUG-08:61 | 9826.02 | 05-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.225514E+11 | 0.596368E+10 | 347.62 | 0.143273E+11 | 0.822407E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:03 | 41400.80 | 25-SEP-08:03 | 29294.69 | 26-SEP-08:61 | 27548.60 | 11-SEP-07:01 | 9675.40 | 04-SEP-09:01 | 0.00 | 01-SEP-00:03 |
October | 0.176732E+11 | 0.464696E+10 | 344.76 | 0.124271E+11 | 0.524610E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 41382.17 | 07-OCT-08:61 | 31850.34 | 20-OCT-08:61 | 23915.85 | 09-OCT-09:04 | 9128.52 | 06-OCT-08:03 | 0.00 | 01-OCT-00:10 |
November | 0.123988E+11 | 0.323322E+10 | 321.04 | 0.883043E+10 | 0.356841E+10 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-00:10 | 40048.62 | 03-NOV-08:61 | 33127.69 | 19-NOV-10:01 | 18626.26 | 03-NOV-08:03 | 8685.55 | 11-NOV-10:01 | 0.00 | 01-NOV-00:10 |
December | 0.729361E+10 | 0.190913E+10 | 322.31 | 0.523457E+10 | 0.205905E+10 | 0.00 | 1.00 | 01-DEC-09:02 | 0.00 | 01-DEC-00:10 | 38118.15 | 10-DEC-10:01 | 27712.00 | 12-DEC-09:02 | 13036.20 | 03-DEC-10:02 | 8576.25 | 10-DEC-10:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.181602E+12 | 0.489841E+11 | 4029.53 | 0.125337E+12 | 0.562648E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.474079E+10 | 0.125987E+10 | 288.62 | 0.360050E+10 | 0.114030E+10 | 0.00 | 1.00 | 0.00 | 36612.70 | 26311.00 | 11678.79 | 8310.80 | 0.00 | |||||||
Maximum of Months | 0.274309E+11 | 0.747121E+10 | 372.06 | 0.171611E+11 | 0.102698E+11 | 0.00 | 1.00 | 0.00 | 41400.80 | 34688.60 | 27548.60 | 10012.80 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.467668E+10 | 0.124352E+10 | 307.79 | 0.354889E+10 | 0.112779E+10 | 0.00 | 1.00 | 29-JAN-10:02 | 0.00 | 01-JAN-00:10 | 37858.34 | 29-JAN-10:02 | 26194.75 | 29-JAN-10:02 | 11663.59 | 29-JAN-10:02 | 8282.59 | 29-JAN-10:02 | 0.00 | 01-JAN-00:10 |
February | 0.570053E+10 | 0.151870E+10 | 287.96 | 0.428481E+10 | 0.141572E+10 | 0.00 | 1.00 | 05-FEB-10:02 | 0.00 | 01-FEB-00:05 | 36484.59 | 05-FEB-10:02 | 30005.41 | 05-FEB-10:02 | 12144.96 | 07-FEB-09:02 | 8481.81 | 05-FEB-10:02 | 0.00 | 01-FEB-00:05 |
March | 0.825192E+10 | 0.223834E+10 | 334.69 | 0.649847E+10 | 0.175345E+10 | 0.00 | 1.00 | 01-MAR-09:01 | 0.00 | 01-MAR-00:05 | 37996.23 | 01-MAR-09:01 | 34565.91 | 27-MAR-08:61 | 11876.22 | 01-MAR-09:01 | 8612.46 | 01-MAR-09:01 | 0.00 | 01-MAR-00:05 |
April | 0.114334E+11 | 0.312577E+10 | 318.83 | 0.882496E+10 | 0.260844E+10 | 0.00 | 1.00 | 02-APR-09:01 | 0.00 | 01-APR-00:05 | 39854.75 | 30-APR-09:02 | 34290.74 | 26-APR-08:61 | 18345.77 | 30-APR-09:02 | 8930.60 | 28-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.173772E+11 | 0.483348E+10 | 355.93 | 0.132661E+11 | 0.411105E+10 | 0.00 | 1.00 | 01-MAY-08:62 | 0.00 | 01-MAY-00:10 | 40626.45 | 01-MAY-08:62 | 33930.26 | 11-MAY-08:61 | 22745.15 | 01-MAY-08:62 | 9695.17 | 10-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.211275E+11 | 0.576100E+10 | 354.60 | 0.143318E+11 | 0.679572E+10 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 41218.30 | 08-JUN-08:61 | 32070.73 | 02-JUN-08:61 | 24120.32 | 25-JUN-09:04 | 9676.68 | 11-JUN-09:04 | 0.00 | 01-JUN-00:10 |
July | 0.252694E+11 | 0.692488E+10 | 359.94 | 0.162651E+11 | 0.900434E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:03 | 40823.59 | 05-JUL-07:01 | 31789.16 | 04-JUL-09:01 | 25744.48 | 31-JUL-07:01 | 9979.55 | 30-JUL-09:01 | 0.00 | 01-JUL-00:03 |
August | 0.273781E+11 | 0.745468E+10 | 372.06 | 0.171202E+11 | 0.102578E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 40899.05 | 08-AUG-07:01 | 27863.00 | 16-AUG-07:01 | 24342.66 | 27-AUG-08:61 | 9793.38 | 05-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.225023E+11 | 0.594939E+10 | 348.48 | 0.142894E+11 | 0.821288E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:03 | 41262.36 | 25-SEP-08:61 | 29198.28 | 26-SEP-08:61 | 27464.57 | 11-SEP-07:01 | 9643.06 | 04-SEP-09:01 | 0.00 | 01-SEP-00:03 |
October | 0.176241E+11 | 0.463304E+10 | 344.70 | 0.123874E+11 | 0.523668E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 41243.79 | 07-OCT-08:61 | 31726.93 | 20-OCT-08:61 | 23843.60 | 09-OCT-09:04 | 9097.68 | 06-OCT-08:03 | 0.00 | 01-OCT-00:10 |
November | 0.123460E+11 | 0.321940E+10 | 320.66 | 0.878829E+10 | 0.355774E+10 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-00:10 | 39915.44 | 03-NOV-08:61 | 33015.92 | 19-NOV-10:01 | 18589.80 | 03-NOV-08:03 | 8656.83 | 11-NOV-10:01 | 0.00 | 01-NOV-00:10 |
December | 0.723249E+10 | 0.189379E+10 | 322.20 | 0.518697E+10 | 0.204552E+10 | 0.00 | 1.00 | 01-DEC-09:02 | 0.00 | 01-DEC-00:10 | 37987.05 | 10-DEC-10:01 | 27599.59 | 12-DEC-09:02 | 12885.97 | 03-DEC-10:02 | 8547.33 | 10-DEC-10:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.180920E+12 | 0.487960E+11 | 4027.83 | 0.124792E+12 | 0.561272E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.467668E+10 | 0.124352E+10 | 287.96 | 0.354889E+10 | 0.112779E+10 | 0.00 | 1.00 | 0.00 | 36484.59 | 26194.75 | 11663.59 | 8282.59 | 0.00 | |||||||
Maximum of Months | 0.273781E+11 | 0.745468E+10 | 372.06 | 0.171202E+11 | 0.102578E+11 | 0.00 | 1.00 | 0.00 | 41262.36 | 34565.91 | 27464.57 | 9979.55 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.454082E+10 | 0.120964E+10 | 305.68 | 0.343978E+10 | 0.110104E+10 | 0.00 | 1.00 | 29-JAN-10:02 | 0.00 | 01-JAN-00:10 | 37998.28 | 29-JAN-10:02 | 26219.65 | 29-JAN-10:02 | 11778.63 | 29-JAN-10:02 | 8315.37 | 29-JAN-10:02 | 0.00 | 01-JAN-00:10 |
February | 0.557332E+10 | 0.148776E+10 | 286.72 | 0.418550E+10 | 0.138782E+10 | 0.00 | 1.00 | 05-FEB-10:02 | 0.00 | 01-FEB-00:05 | 36613.58 | 05-FEB-10:02 | 30036.10 | 05-FEB-10:02 | 11652.43 | 07-FEB-09:02 | 8514.59 | 05-FEB-10:02 | 0.00 | 01-FEB-00:05 |
March | 0.813175E+10 | 0.220984E+10 | 333.41 | 0.640014E+10 | 0.173162E+10 | 0.00 | 1.00 | 01-MAR-09:01 | 0.00 | 01-MAR-00:05 | 38141.03 | 01-MAR-09:01 | 34689.33 | 27-MAR-08:61 | 12005.92 | 01-MAR-09:01 | 8647.48 | 01-MAR-09:01 | 0.00 | 01-MAR-00:05 |
April | 0.113743E+11 | 0.311390E+10 | 318.80 | 0.877715E+10 | 0.259717E+10 | 0.00 | 1.00 | 02-APR-09:01 | 0.00 | 01-APR-00:05 | 40010.32 | 30-APR-09:02 | 34415.50 | 26-APR-08:61 | 18457.43 | 30-APR-09:02 | 8968.01 | 28-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.174204E+11 | 0.484732E+10 | 355.75 | 0.133024E+11 | 0.411797E+10 | 0.00 | 1.00 | 01-MAY-08:62 | 0.00 | 01-MAY-00:10 | 40789.57 | 01-MAY-08:62 | 34069.57 | 11-MAY-08:61 | 22867.74 | 01-MAY-08:62 | 9735.05 | 10-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.212172E+11 | 0.578694E+10 | 354.52 | 0.144036E+11 | 0.681366E+10 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 41381.48 | 08-JUN-08:61 | 32201.15 | 02-JUN-08:61 | 24197.71 | 25-JUN-09:04 | 9717.04 | 11-JUN-09:04 | 0.00 | 01-JUN-00:10 |
July | 0.254247E+11 | 0.696943E+10 | 359.89 | 0.163888E+11 | 0.903591E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:03 | 40993.48 | 05-JUL-07:01 | 31925.43 | 04-JUL-09:01 | 25769.42 | 31-JUL-07:01 | 10020.29 | 30-JUL-09:01 | 0.00 | 01-JUL-00:03 |
August | 0.275769E+11 | 0.751082E+10 | 371.91 | 0.172777E+11 | 0.102992E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 41069.26 | 08-AUG-07:01 | 28060.11 | 16-AUG-07:01 | 24376.02 | 27-AUG-08:61 | 9833.47 | 05-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.226429E+11 | 0.598776E+10 | 347.48 | 0.144001E+11 | 0.824281E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:03 | 41434.08 | 25-SEP-08:03 | 29326.68 | 26-SEP-08:61 | 27490.72 | 11-SEP-07:01 | 9682.32 | 04-SEP-09:01 | 0.00 | 01-SEP-00:03 |
October | 0.177167E+11 | 0.465769E+10 | 344.65 | 0.124626E+11 | 0.525410E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 41415.43 | 07-OCT-08:61 | 31854.39 | 20-OCT-08:61 | 23869.99 | 09-OCT-09:04 | 9135.91 | 06-OCT-08:03 | 0.00 | 01-OCT-00:10 |
November | 0.123582E+11 | 0.322429E+10 | 320.96 | 0.879846E+10 | 0.355977E+10 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-00:10 | 40076.48 | 03-NOV-08:61 | 33147.61 | 19-NOV-10:01 | 18664.10 | 03-NOV-08:03 | 8692.92 | 11-NOV-10:01 | 0.00 | 01-NOV-00:10 |
December | 0.713946E+10 | 0.187199E+10 | 321.55 | 0.511526E+10 | 0.202420E+10 | 0.00 | 1.00 | 01-DEC-09:02 | 0.00 | 01-DEC-00:10 | 38133.14 | 10-DEC-10:01 | 27658.00 | 12-DEC-09:02 | 12518.21 | 03-DEC-10:02 | 8582.09 | 10-DEC-10:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.181117E+12 | 0.488774E+11 | 4021.32 | 0.124952E+12 | 0.561652E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.454082E+10 | 0.120964E+10 | 286.72 | 0.343978E+10 | 0.110104E+10 | 0.00 | 1.00 | 0.00 | 36613.58 | 26219.65 | 11652.43 | 8315.37 | 0.00 | |||||||
Maximum of Months | 0.275769E+11 | 0.751082E+10 | 371.91 | 0.172777E+11 | 0.102992E+11 | 0.00 | 1.00 | 0.00 | 41434.08 | 34689.33 | 27490.72 | 10020.29 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.484230E+10 | 0.131698E+10 | 303.34 | 0.372456E+10 | 0.111774E+10 | 0.00 | 1.00 | 29-JAN-10:02 | 0.00 | 01-JAN-00:10 | 42567.55 | 29-JAN-10:02 | 29582.00 | 29-JAN-10:02 | 12985.55 | 29-JAN-10:02 | 9467.54 | 29-JAN-10:02 | 0.00 | 01-JAN-00:10 |
February | 0.588084E+10 | 0.160640E+10 | 284.37 | 0.448164E+10 | 0.139920E+10 | 0.00 | 1.00 | 05-FEB-10:02 | 0.00 | 01-FEB-00:05 | 40873.16 | 05-FEB-10:02 | 33978.87 | 05-FEB-10:02 | 11549.96 | 07-FEB-09:02 | 9679.29 | 05-FEB-10:02 | 0.00 | 01-FEB-00:05 |
March | 0.861385E+10 | 0.239781E+10 | 330.36 | 0.686841E+10 | 0.174544E+10 | 0.00 | 1.00 | 01-MAR-09:01 | 0.00 | 01-MAR-00:05 | 42837.51 | 01-MAR-09:01 | 38780.34 | 27-MAR-08:61 | 14060.98 | 01-MAR-09:01 | 9847.86 | 01-MAR-09:01 | 0.00 | 01-MAR-00:05 |
April | 0.123043E+11 | 0.345153E+10 | 319.10 | 0.962053E+10 | 0.268373E+10 | 0.00 | 1.00 | 02-APR-09:01 | 0.00 | 01-APR-00:05 | 45028.46 | 30-APR-09:02 | 38716.68 | 27-APR-08:61 | 21433.47 | 30-APR-09:02 | 10212.73 | 28-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.192128E+11 | 0.547263E+10 | 357.84 | 0.148790E+11 | 0.433371E+10 | 0.00 | 1.00 | 01-MAY-08:62 | 0.00 | 01-MAY-00:10 | 45573.65 | 01-MAY-08:62 | 38119.06 | 11-MAY-08:61 | 25301.59 | 01-MAY-08:62 | 11056.52 | 10-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.234606E+11 | 0.655061E+10 | 356.51 | 0.162149E+11 | 0.724571E+10 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 46296.11 | 08-JUN-08:03 | 36043.69 | 02-JUN-08:61 | 27900.64 | 19-JUN-07:01 | 11049.22 | 11-JUN-09:03 | 0.00 | 01-JUN-00:10 |
July | 0.282016E+11 | 0.792174E+10 | 361.36 | 0.185676E+11 | 0.963403E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:03 | 45888.48 | 26-JUL-07:01 | 37812.71 | 04-JUL-08:61 | 29981.84 | 05-JUL-07:03 | 11410.24 | 30-JUL-09:01 | 0.00 | 01-JUL-00:03 |
August | 0.308142E+11 | 0.860294E+10 | 374.67 | 0.198001E+11 | 0.110141E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 45888.48 | 08-AUG-07:01 | 32068.97 | 06-AUG-08:61 | 29152.60 | 21-AUG-07:03 | 11183.52 | 05-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.252454E+11 | 0.683744E+10 | 351.66 | 0.164514E+11 | 0.879399E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 | 46296.11 | 25-SEP-08:03 | 32978.96 | 26-SEP-08:61 | 31168.85 | 11-SEP-07:03 | 11004.50 | 04-SEP-09:01 | 0.00 | 01-SEP-00:03 |
October | 0.197956E+11 | 0.531878E+10 | 350.74 | 0.141914E+11 | 0.560416E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 46275.27 | 07-OCT-08:61 | 36062.54 | 21-OCT-08:62 | 29230.19 | 08-OCT-08:61 | 10388.98 | 22-OCT-09:01 | 0.00 | 01-OCT-00:10 |
November | 0.136762E+11 | 0.364584E+10 | 322.44 | 0.992568E+10 | 0.375056E+10 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-00:10 | 45099.73 | 03-NOV-08:61 | 36907.24 | 19-NOV-10:01 | 21431.32 | 03-NOV-08:03 | 9893.50 | 11-NOV-10:01 | 0.00 | 01-NOV-00:10 |
December | 0.769361E+10 | 0.206221E+10 | 320.80 | 0.560832E+10 | 0.208530E+10 | 0.00 | 1.00 | 01-DEC-09:02 | 0.00 | 01-DEC-00:10 | 42605.90 | 10-DEC-10:01 | 30830.16 | 12-DEC-09:02 | 12961.66 | 03-DEC-10:02 | 9760.10 | 10-DEC-10:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.199741E+12 | 0.551849E+11 | 4033.19 | 0.140334E+12 | 0.594077E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.484230E+10 | 0.131698E+10 | 284.37 | 0.372456E+10 | 0.111774E+10 | 0.00 | 1.00 | 0.00 | 40873.16 | 29582.00 | 11549.96 | 9467.54 | 0.00 | |||||||
Maximum of Months | 0.308142E+11 | 0.860294E+10 | 374.67 | 0.198001E+11 | 0.110141E+11 | 0.00 | 1.00 | 0.00 | 46296.11 | 38780.34 | 31168.85 | 11410.24 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.78 | 29.51 | 33.26 | 95.05 | 35.69 | 0.00 | 0.00 | 0.00 |
February | 58.95 | 24.11 | 34.84 | 94.30 | 30.03 | 0.00 | 0.00 | 0.00 |
March | 48.52 | 13.17 | 35.35 | 85.88 | 22.94 | 0.00 | 0.00 | 0.00 |
April | 38.14 | 4.04 | 34.10 | 79.10 | 13.87 | 0.00 | 0.00 | 0.00 |
May | 32.31 | 0.49 | 31.81 | 87.00 | 3.46 | 0.00 | 0.00 | 0.00 |
June | 30.43 | 0.04 | 30.39 | 90.47 | 0.93 | 0.00 | 0.00 | 0.00 |
July | 30.42 | 0.26 | 30.17 | 105.54 | 0.02 | 0.00 | 0.00 | 0.00 |
August | 35.29 | 2.50 | 32.79 | 117.20 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 46.53 | 10.66 | 35.87 | 120.83 | 1.68 | 0.00 | 0.00 | 0.00 |
October | 60.92 | 24.22 | 36.70 | 128.70 | 6.19 | 0.00 | 0.00 | 0.00 |
November | 67.21 | 32.40 | 34.81 | 121.06 | 16.26 | 0.00 | 0.00 | 0.00 |
December | 62.39 | 30.82 | 31.57 | 99.57 | 29.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.76 | 14.30 | 33.46 | 102.11 | 13.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.42 | 0.04 | 30.17 | 79.10 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.21 | 32.40 | 36.70 | 128.70 | 35.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.78 | 29.51 | 33.26 | 95.05 | 35.69 | 0.00 | 0.00 | 0.00 |
February | 58.95 | 24.11 | 34.84 | 94.30 | 30.03 | 0.00 | 0.00 | 0.00 |
March | 48.52 | 13.17 | 35.35 | 85.88 | 22.94 | 0.00 | 0.00 | 0.00 |
April | 38.14 | 4.04 | 34.10 | 79.10 | 13.87 | 0.00 | 0.00 | 0.00 |
May | 32.31 | 0.49 | 31.81 | 87.00 | 3.46 | 0.00 | 0.00 | 0.00 |
June | 30.43 | 0.04 | 30.39 | 90.47 | 0.93 | 0.00 | 0.00 | 0.00 |
July | 30.42 | 0.26 | 30.17 | 105.54 | 0.02 | 0.00 | 0.00 | 0.00 |
August | 35.29 | 2.50 | 32.79 | 117.20 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 46.53 | 10.66 | 35.87 | 120.83 | 1.68 | 0.00 | 0.00 | 0.00 |
October | 60.92 | 24.22 | 36.70 | 128.70 | 6.19 | 0.00 | 0.00 | 0.00 |
November | 67.21 | 32.40 | 34.81 | 121.06 | 16.26 | 0.00 | 0.00 | 0.00 |
December | 62.39 | 30.82 | 31.57 | 99.57 | 29.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.76 | 14.30 | 33.46 | 102.11 | 13.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.42 | 0.04 | 30.17 | 79.10 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.21 | 32.40 | 36.70 | 128.70 | 35.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.78 | 29.51 | 33.26 | 95.05 | 35.69 | 0.00 | 0.00 | 0.00 |
February | 58.95 | 24.11 | 34.84 | 94.30 | 30.03 | 0.00 | 0.00 | 0.00 |
March | 48.52 | 13.17 | 35.35 | 85.88 | 22.94 | 0.00 | 0.00 | 0.00 |
April | 38.14 | 4.04 | 34.10 | 79.10 | 13.87 | 0.00 | 0.00 | 0.00 |
May | 32.31 | 0.49 | 31.81 | 87.00 | 3.46 | 0.00 | 0.00 | 0.00 |
June | 30.43 | 0.04 | 30.39 | 90.47 | 0.93 | 0.00 | 0.00 | 0.00 |
July | 30.42 | 0.26 | 30.17 | 105.54 | 0.02 | 0.00 | 0.00 | 0.00 |
August | 35.29 | 2.50 | 32.79 | 117.20 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 46.53 | 10.66 | 35.87 | 120.83 | 1.68 | 0.00 | 0.00 | 0.00 |
October | 60.92 | 24.22 | 36.70 | 128.70 | 6.19 | 0.00 | 0.00 | 0.00 |
November | 67.21 | 32.40 | 34.81 | 121.06 | 16.26 | 0.00 | 0.00 | 0.00 |
December | 62.39 | 30.82 | 31.57 | 99.57 | 29.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.76 | 14.30 | 33.46 | 102.11 | 13.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.42 | 0.04 | 30.17 | 79.10 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.21 | 32.40 | 36.70 | 128.70 | 35.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.78 | 29.51 | 33.26 | 95.05 | 35.69 | 0.00 | 0.00 | 0.00 |
February | 58.95 | 24.11 | 34.84 | 94.30 | 30.03 | 0.00 | 0.00 | 0.00 |
March | 48.52 | 13.17 | 35.35 | 85.88 | 22.94 | 0.00 | 0.00 | 0.00 |
April | 38.14 | 4.04 | 34.10 | 79.10 | 13.87 | 0.00 | 0.00 | 0.00 |
May | 32.31 | 0.49 | 31.81 | 87.00 | 3.46 | 0.00 | 0.00 | 0.00 |
June | 30.43 | 0.04 | 30.39 | 90.47 | 0.93 | 0.00 | 0.00 | 0.00 |
July | 30.42 | 0.26 | 30.17 | 105.54 | 0.02 | 0.00 | 0.00 | 0.00 |
August | 35.29 | 2.50 | 32.79 | 117.20 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 46.53 | 10.66 | 35.87 | 120.83 | 1.68 | 0.00 | 0.00 | 0.00 |
October | 60.92 | 24.22 | 36.70 | 128.70 | 6.19 | 0.00 | 0.00 | 0.00 |
November | 67.21 | 32.40 | 34.81 | 121.06 | 16.26 | 0.00 | 0.00 | 0.00 |
December | 62.39 | 30.82 | 31.57 | 99.57 | 29.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.76 | 14.30 | 33.46 | 102.11 | 13.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.42 | 0.04 | 30.17 | 79.10 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.21 | 32.40 | 36.70 | 128.70 | 35.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.47 | 35.48 | 39.99 | 114.36 | 42.57 | 0.00 | 0.00 | 0.00 |
February | 70.87 | 28.99 | 41.88 | 113.39 | 35.84 | 0.00 | 0.00 | 0.00 |
March | 58.33 | 15.84 | 42.49 | 103.08 | 27.46 | 0.00 | 0.00 | 0.00 |
April | 45.85 | 4.86 | 40.99 | 94.65 | 16.67 | 0.00 | 0.00 | 0.00 |
May | 38.84 | 0.59 | 38.24 | 103.54 | 4.20 | 0.00 | 0.00 | 0.00 |
June | 36.58 | 0.05 | 36.53 | 107.42 | 1.17 | 0.00 | 0.00 | 0.00 |
July | 36.58 | 0.31 | 36.26 | 125.36 | 0.03 | 0.00 | 0.00 | 0.00 |
August | 42.42 | 3.01 | 39.42 | 139.34 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 55.94 | 12.82 | 43.12 | 144.11 | 2.06 | 0.00 | 0.00 | 0.00 |
October | 73.23 | 29.11 | 44.12 | 153.94 | 7.50 | 0.00 | 0.00 | 0.00 |
November | 80.79 | 38.95 | 41.84 | 145.21 | 19.57 | 0.00 | 0.00 | 0.00 |
December | 75.00 | 37.05 | 37.95 | 119.67 | 35.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.41 | 17.19 | 40.22 | 122.07 | 15.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.58 | 0.05 | 36.26 | 94.65 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 80.79 | 38.95 | 44.12 | 153.94 | 42.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.47 | 35.48 | 39.99 | 114.36 | 42.57 | 0.00 | 0.00 | 0.00 |
February | 70.87 | 28.99 | 41.88 | 113.39 | 35.84 | 0.00 | 0.00 | 0.00 |
March | 58.33 | 15.84 | 42.49 | 103.08 | 27.46 | 0.00 | 0.00 | 0.00 |
April | 45.85 | 4.86 | 40.99 | 94.65 | 16.67 | 0.00 | 0.00 | 0.00 |
May | 38.84 | 0.59 | 38.24 | 103.54 | 4.20 | 0.00 | 0.00 | 0.00 |
June | 36.58 | 0.05 | 36.53 | 107.42 | 1.17 | 0.00 | 0.00 | 0.00 |
July | 36.58 | 0.31 | 36.26 | 125.36 | 0.03 | 0.00 | 0.00 | 0.00 |
August | 42.42 | 3.01 | 39.42 | 139.34 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 55.94 | 12.82 | 43.12 | 144.11 | 2.06 | 0.00 | 0.00 | 0.00 |
October | 73.23 | 29.11 | 44.12 | 153.94 | 7.50 | 0.00 | 0.00 | 0.00 |
November | 80.79 | 38.95 | 41.84 | 145.21 | 19.57 | 0.00 | 0.00 | 0.00 |
December | 75.00 | 37.05 | 37.95 | 119.67 | 35.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.41 | 17.19 | 40.22 | 122.07 | 15.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.58 | 0.05 | 36.26 | 94.65 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 80.79 | 38.95 | 44.12 | 153.94 | 42.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.78 | 29.51 | 33.26 | 94.65 | 36.11 | 0.00 | 0.00 | 0.00 |
February | 58.95 | 24.11 | 34.84 | 93.98 | 30.42 | 0.00 | 0.00 | 0.00 |
March | 48.52 | 13.17 | 35.35 | 85.77 | 23.22 | 0.00 | 0.00 | 0.00 |
April | 38.14 | 4.04 | 34.10 | 79.30 | 14.00 | 0.00 | 0.00 | 0.00 |
May | 32.31 | 0.49 | 31.81 | 87.92 | 3.41 | 0.00 | 0.00 | 0.00 |
June | 30.43 | 0.04 | 30.39 | 91.84 | 0.84 | 0.00 | 0.00 | 0.00 |
July | 30.42 | 0.26 | 30.17 | 107.33 | 0.02 | 0.00 | 0.00 | 0.00 |
August | 35.29 | 2.50 | 32.79 | 119.26 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 46.53 | 10.66 | 35.87 | 122.24 | 1.52 | 0.00 | 0.00 | 0.00 |
October | 60.92 | 24.22 | 36.70 | 129.51 | 5.89 | 0.00 | 0.00 | 0.00 |
November | 67.21 | 32.40 | 34.81 | 121.31 | 16.01 | 0.00 | 0.00 | 0.00 |
December | 62.39 | 30.82 | 31.57 | 99.38 | 29.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.76 | 14.30 | 33.46 | 102.77 | 13.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.42 | 0.04 | 30.17 | 79.30 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.21 | 32.40 | 36.70 | 129.51 | 36.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.78 | 29.51 | 33.26 | 94.65 | 36.11 | 0.00 | 0.00 | 0.00 |
February | 58.95 | 24.11 | 34.84 | 93.98 | 30.42 | 0.00 | 0.00 | 0.00 |
March | 48.52 | 13.17 | 35.35 | 85.77 | 23.22 | 0.00 | 0.00 | 0.00 |
April | 38.14 | 4.04 | 34.10 | 79.30 | 14.00 | 0.00 | 0.00 | 0.00 |
May | 32.31 | 0.49 | 31.81 | 87.92 | 3.41 | 0.00 | 0.00 | 0.00 |
June | 30.43 | 0.04 | 30.39 | 91.84 | 0.84 | 0.00 | 0.00 | 0.00 |
July | 30.42 | 0.26 | 30.17 | 107.33 | 0.02 | 0.00 | 0.00 | 0.00 |
August | 35.29 | 2.50 | 32.79 | 119.26 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 46.53 | 10.66 | 35.87 | 122.24 | 1.52 | 0.00 | 0.00 | 0.00 |
October | 60.92 | 24.22 | 36.70 | 129.51 | 5.89 | 0.00 | 0.00 | 0.00 |
November | 67.21 | 32.40 | 34.81 | 121.31 | 16.01 | 0.00 | 0.00 | 0.00 |
December | 62.39 | 30.82 | 31.57 | 99.38 | 29.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.76 | 14.30 | 33.46 | 102.77 | 13.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.42 | 0.04 | 30.17 | 79.30 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.21 | 32.40 | 36.70 | 129.51 | 36.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.47 | 35.48 | 39.99 | 113.92 | 43.05 | 0.00 | 0.00 | 0.00 |
February | 70.87 | 28.99 | 41.88 | 113.05 | 36.30 | 0.00 | 0.00 | 0.00 |
March | 58.33 | 15.84 | 42.49 | 102.97 | 27.80 | 0.00 | 0.00 | 0.00 |
April | 45.85 | 4.86 | 40.99 | 94.89 | 16.83 | 0.00 | 0.00 | 0.00 |
May | 38.84 | 0.59 | 38.24 | 104.62 | 4.14 | 0.00 | 0.00 | 0.00 |
June | 36.58 | 0.05 | 36.53 | 109.01 | 1.06 | 0.00 | 0.00 | 0.00 |
July | 36.58 | 0.31 | 36.26 | 127.45 | 0.02 | 0.00 | 0.00 | 0.00 |
August | 42.42 | 3.01 | 39.42 | 141.76 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 55.94 | 12.82 | 43.12 | 145.77 | 1.87 | 0.00 | 0.00 | 0.00 |
October | 73.23 | 29.11 | 44.12 | 154.92 | 7.15 | 0.00 | 0.00 | 0.00 |
November | 80.79 | 38.95 | 41.84 | 145.53 | 19.27 | 0.00 | 0.00 | 0.00 |
December | 75.00 | 37.05 | 37.95 | 119.47 | 35.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.41 | 17.19 | 40.22 | 122.85 | 16.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.58 | 0.05 | 36.26 | 94.89 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 80.79 | 38.95 | 44.12 | 154.92 | 43.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.78 | 29.51 | 33.26 | 94.77 | 36.97 | 0.00 | 0.00 | 0.00 |
February | 58.95 | 24.11 | 34.84 | 94.03 | 31.55 | 0.00 | 0.00 | 0.00 |
March | 48.52 | 13.17 | 35.35 | 85.62 | 24.61 | 0.00 | 0.00 | 0.00 |
April | 38.14 | 4.04 | 34.10 | 78.54 | 15.74 | 0.00 | 0.00 | 0.00 |
May | 32.31 | 0.49 | 31.81 | 84.80 | 4.25 | 0.00 | 0.00 | 0.00 |
June | 30.43 | 0.04 | 30.39 | 87.91 | 1.22 | 0.00 | 0.00 | 0.00 |
July | 30.42 | 0.26 | 30.17 | 102.10 | 0.06 | 0.00 | 0.00 | 0.00 |
August | 35.29 | 2.50 | 32.79 | 114.30 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 46.53 | 10.66 | 35.87 | 118.13 | 2.00 | 0.00 | 0.00 | 0.00 |
October | 60.92 | 24.22 | 36.70 | 127.23 | 7.52 | 0.00 | 0.00 | 0.00 |
November | 67.21 | 32.40 | 34.81 | 120.98 | 18.20 | 0.00 | 0.00 | 0.00 |
December | 62.39 | 30.82 | 31.57 | 99.44 | 31.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.76 | 14.30 | 33.46 | 100.70 | 14.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.42 | 0.04 | 30.17 | 78.54 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.21 | 32.40 | 36.70 | 127.23 | 36.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.78 | 29.51 | 33.26 | 94.77 | 36.97 | 0.00 | 0.00 | 0.00 |
February | 58.95 | 24.11 | 34.84 | 94.03 | 31.55 | 0.00 | 0.00 | 0.00 |
March | 48.52 | 13.17 | 35.35 | 85.62 | 24.61 | 0.00 | 0.00 | 0.00 |
April | 38.14 | 4.04 | 34.10 | 78.54 | 15.74 | 0.00 | 0.00 | 0.00 |
May | 32.31 | 0.49 | 31.81 | 84.80 | 4.25 | 0.00 | 0.00 | 0.00 |
June | 30.43 | 0.04 | 30.39 | 87.91 | 1.22 | 0.00 | 0.00 | 0.00 |
July | 30.42 | 0.26 | 30.17 | 102.10 | 0.06 | 0.00 | 0.00 | 0.00 |
August | 35.29 | 2.50 | 32.79 | 114.30 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 46.53 | 10.66 | 35.87 | 118.13 | 2.00 | 0.00 | 0.00 | 0.00 |
October | 60.92 | 24.22 | 36.70 | 127.23 | 7.52 | 0.00 | 0.00 | 0.00 |
November | 67.21 | 32.40 | 34.81 | 120.98 | 18.20 | 0.00 | 0.00 | 0.00 |
December | 62.39 | 30.82 | 31.57 | 99.44 | 31.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.76 | 14.30 | 33.46 | 100.70 | 14.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.42 | 0.04 | 30.17 | 78.54 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.21 | 32.40 | 36.70 | 127.23 | 36.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.05 | 35.29 | 39.77 | 113.45 | 43.80 | 0.00 | 0.00 | 0.00 |
February | 70.48 | 28.83 | 41.65 | 112.48 | 37.39 | 0.00 | 0.00 | 0.00 |
March | 58.01 | 15.75 | 42.26 | 102.23 | 29.25 | 0.00 | 0.00 | 0.00 |
April | 45.60 | 4.83 | 40.76 | 93.50 | 18.78 | 0.00 | 0.00 | 0.00 |
May | 38.63 | 0.59 | 38.03 | 100.44 | 5.13 | 0.00 | 0.00 | 0.00 |
June | 36.38 | 0.05 | 36.33 | 103.87 | 1.53 | 0.00 | 0.00 | 0.00 |
July | 36.38 | 0.31 | 36.07 | 120.68 | 0.08 | 0.00 | 0.00 | 0.00 |
August | 42.19 | 2.99 | 39.20 | 135.21 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 55.63 | 12.75 | 42.88 | 140.23 | 2.45 | 0.00 | 0.00 | 0.00 |
October | 72.83 | 28.96 | 43.88 | 151.47 | 9.06 | 0.00 | 0.00 | 0.00 |
November | 80.35 | 38.73 | 41.61 | 144.36 | 21.72 | 0.00 | 0.00 | 0.00 |
December | 74.59 | 36.84 | 37.74 | 118.89 | 37.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.10 | 17.10 | 40.00 | 119.79 | 17.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.38 | 0.05 | 36.07 | 93.50 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 80.35 | 38.73 | 43.88 | 151.47 | 43.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.78 | 29.51 | 33.26 | 94.85 | 36.77 | 0.00 | 0.00 | 0.00 |
February | 58.95 | 24.11 | 34.84 | 94.07 | 31.43 | 0.00 | 0.00 | 0.00 |
March | 48.52 | 13.17 | 35.35 | 85.64 | 24.59 | 0.00 | 0.00 | 0.00 |
April | 38.14 | 4.04 | 34.10 | 78.50 | 15.88 | 0.00 | 0.00 | 0.00 |
May | 32.31 | 0.49 | 31.81 | 84.53 | 4.45 | 0.00 | 0.00 | 0.00 |
June | 30.43 | 0.04 | 30.39 | 87.50 | 1.36 | 0.00 | 0.00 | 0.00 |
July | 30.42 | 0.26 | 30.17 | 101.43 | 0.08 | 0.00 | 0.00 | 0.00 |
August | 35.29 | 2.50 | 32.79 | 113.64 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 46.53 | 10.66 | 35.87 | 117.70 | 2.16 | 0.00 | 0.00 | 0.00 |
October | 60.92 | 24.22 | 36.70 | 127.07 | 7.84 | 0.00 | 0.00 | 0.00 |
November | 67.21 | 32.40 | 34.81 | 120.93 | 18.36 | 0.00 | 0.00 | 0.00 |
December | 62.39 | 30.82 | 31.57 | 99.46 | 31.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.76 | 14.30 | 33.46 | 100.49 | 14.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.42 | 0.04 | 30.17 | 78.50 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.21 | 32.40 | 36.70 | 127.07 | 36.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.78 | 29.51 | 33.26 | 94.85 | 36.77 | 0.00 | 0.00 | 0.00 |
February | 58.95 | 24.11 | 34.84 | 94.07 | 31.43 | 0.00 | 0.00 | 0.00 |
March | 48.52 | 13.17 | 35.35 | 85.64 | 24.59 | 0.00 | 0.00 | 0.00 |
April | 38.14 | 4.04 | 34.10 | 78.50 | 15.88 | 0.00 | 0.00 | 0.00 |
May | 32.31 | 0.49 | 31.81 | 84.53 | 4.45 | 0.00 | 0.00 | 0.00 |
June | 30.43 | 0.04 | 30.39 | 87.50 | 1.36 | 0.00 | 0.00 | 0.00 |
July | 30.42 | 0.26 | 30.17 | 101.43 | 0.08 | 0.00 | 0.00 | 0.00 |
August | 35.29 | 2.50 | 32.79 | 113.64 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 46.53 | 10.66 | 35.87 | 117.70 | 2.16 | 0.00 | 0.00 | 0.00 |
October | 60.92 | 24.22 | 36.70 | 127.07 | 7.84 | 0.00 | 0.00 | 0.00 |
November | 67.21 | 32.40 | 34.81 | 120.93 | 18.36 | 0.00 | 0.00 | 0.00 |
December | 62.39 | 30.82 | 31.57 | 99.46 | 31.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.76 | 14.30 | 33.46 | 100.49 | 14.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.42 | 0.04 | 30.17 | 78.50 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.21 | 32.40 | 36.70 | 127.07 | 36.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.05 | 35.29 | 39.77 | 113.55 | 43.56 | 0.00 | 0.00 | 0.00 |
February | 70.48 | 28.83 | 41.65 | 112.54 | 37.25 | 0.00 | 0.00 | 0.00 |
March | 58.01 | 15.75 | 42.26 | 102.25 | 29.23 | 0.00 | 0.00 | 0.00 |
April | 45.60 | 4.83 | 40.76 | 93.46 | 18.95 | 0.00 | 0.00 | 0.00 |
May | 38.63 | 0.59 | 38.03 | 100.12 | 5.37 | 0.00 | 0.00 | 0.00 |
June | 36.38 | 0.05 | 36.33 | 103.39 | 1.69 | 0.00 | 0.00 | 0.00 |
July | 36.38 | 0.31 | 36.07 | 119.88 | 0.10 | 0.00 | 0.00 | 0.00 |
August | 42.19 | 2.99 | 39.20 | 134.43 | 0.04 | 0.00 | 0.00 | 0.00 |
September | 55.63 | 12.75 | 42.88 | 139.72 | 2.64 | 0.00 | 0.00 | 0.00 |
October | 72.83 | 28.96 | 43.88 | 151.28 | 9.45 | 0.00 | 0.00 | 0.00 |
November | 80.35 | 38.73 | 41.61 | 144.31 | 21.92 | 0.00 | 0.00 | 0.00 |
December | 74.59 | 36.84 | 37.74 | 118.92 | 37.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.10 | 17.10 | 40.00 | 119.54 | 17.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.38 | 0.05 | 36.07 | 93.46 | 0.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 80.35 | 38.73 | 43.88 | 151.28 | 43.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.78 | 29.51 | 33.26 | 94.99 | 36.42 | 0.00 | 0.00 | 0.00 |
February | 58.95 | 24.11 | 34.84 | 94.18 | 31.11 | 0.00 | 0.00 | 0.00 |
March | 48.52 | 13.17 | 35.35 | 85.74 | 24.28 | 0.00 | 0.00 | 0.00 |
April | 38.14 | 4.04 | 34.10 | 78.59 | 15.61 | 0.00 | 0.00 | 0.00 |
May | 32.31 | 0.49 | 31.81 | 84.67 | 4.33 | 0.00 | 0.00 | 0.00 |
June | 30.43 | 0.04 | 30.39 | 87.69 | 1.29 | 0.00 | 0.00 | 0.00 |
July | 30.42 | 0.26 | 30.17 | 101.61 | 0.07 | 0.00 | 0.00 | 0.00 |
August | 35.29 | 2.50 | 32.79 | 113.85 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 46.53 | 10.66 | 35.87 | 117.84 | 2.09 | 0.00 | 0.00 | 0.00 |
October | 60.92 | 24.22 | 36.70 | 127.14 | 7.67 | 0.00 | 0.00 | 0.00 |
November | 67.21 | 32.40 | 34.81 | 121.01 | 18.13 | 0.00 | 0.00 | 0.00 |
December | 62.39 | 30.82 | 31.57 | 99.56 | 30.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.76 | 14.30 | 33.46 | 100.62 | 14.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.42 | 0.04 | 30.17 | 78.59 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.21 | 32.40 | 36.70 | 127.14 | 36.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.78 | 29.51 | 33.26 | 94.99 | 36.42 | 0.00 | 0.00 | 0.00 |
February | 58.95 | 24.11 | 34.84 | 94.18 | 31.11 | 0.00 | 0.00 | 0.00 |
March | 48.52 | 13.17 | 35.35 | 85.74 | 24.28 | 0.00 | 0.00 | 0.00 |
April | 38.14 | 4.04 | 34.10 | 78.59 | 15.61 | 0.00 | 0.00 | 0.00 |
May | 32.31 | 0.49 | 31.81 | 84.67 | 4.33 | 0.00 | 0.00 | 0.00 |
June | 30.43 | 0.04 | 30.39 | 87.69 | 1.29 | 0.00 | 0.00 | 0.00 |
July | 30.42 | 0.26 | 30.17 | 101.61 | 0.07 | 0.00 | 0.00 | 0.00 |
August | 35.29 | 2.50 | 32.79 | 113.85 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 46.53 | 10.66 | 35.87 | 117.84 | 2.09 | 0.00 | 0.00 | 0.00 |
October | 60.92 | 24.22 | 36.70 | 127.14 | 7.67 | 0.00 | 0.00 | 0.00 |
November | 67.21 | 32.40 | 34.81 | 121.01 | 18.13 | 0.00 | 0.00 | 0.00 |
December | 62.39 | 30.82 | 31.57 | 99.56 | 30.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.76 | 14.30 | 33.46 | 100.62 | 14.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.42 | 0.04 | 30.17 | 78.59 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.21 | 32.40 | 36.70 | 127.14 | 36.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.05 | 35.29 | 39.77 | 113.71 | 43.15 | 0.00 | 0.00 | 0.00 |
February | 70.48 | 28.83 | 41.65 | 112.67 | 36.89 | 0.00 | 0.00 | 0.00 |
March | 58.01 | 15.75 | 42.26 | 102.37 | 28.86 | 0.00 | 0.00 | 0.00 |
April | 45.60 | 4.83 | 40.76 | 93.56 | 18.64 | 0.00 | 0.00 | 0.00 |
May | 38.63 | 0.59 | 38.03 | 100.28 | 5.23 | 0.00 | 0.00 | 0.00 |
June | 36.38 | 0.05 | 36.33 | 103.61 | 1.61 | 0.00 | 0.00 | 0.00 |
July | 36.38 | 0.31 | 36.07 | 120.09 | 0.10 | 0.00 | 0.00 | 0.00 |
August | 42.19 | 2.99 | 39.20 | 134.67 | 0.04 | 0.00 | 0.00 | 0.00 |
September | 55.63 | 12.75 | 42.88 | 139.88 | 2.55 | 0.00 | 0.00 | 0.00 |
October | 72.83 | 28.96 | 43.88 | 151.36 | 9.25 | 0.00 | 0.00 | 0.00 |
November | 80.35 | 38.73 | 41.61 | 144.40 | 21.64 | 0.00 | 0.00 | 0.00 |
December | 74.59 | 36.84 | 37.74 | 119.04 | 36.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.10 | 17.10 | 40.00 | 119.69 | 16.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.38 | 0.05 | 36.07 | 93.56 | 0.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 80.35 | 38.73 | 43.88 | 151.36 | 43.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.78 | 29.51 | 33.26 | 95.37 | 35.62 | 0.00 | 0.00 | 0.00 |
February | 58.95 | 24.11 | 34.84 | 94.46 | 30.34 | 0.00 | 0.00 | 0.00 |
March | 48.52 | 13.17 | 35.35 | 85.93 | 23.49 | 0.00 | 0.00 | 0.00 |
April | 38.14 | 4.04 | 34.10 | 78.56 | 14.91 | 0.00 | 0.00 | 0.00 |
May | 32.31 | 0.49 | 31.81 | 84.66 | 4.04 | 0.00 | 0.00 | 0.00 |
June | 30.43 | 0.04 | 30.39 | 87.71 | 1.14 | 0.00 | 0.00 | 0.00 |
July | 30.42 | 0.26 | 30.17 | 101.47 | 0.06 | 0.00 | 0.00 | 0.00 |
August | 35.29 | 2.50 | 32.79 | 113.85 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 46.53 | 10.66 | 35.87 | 117.78 | 1.92 | 0.00 | 0.00 | 0.00 |
October | 60.92 | 24.22 | 36.70 | 127.03 | 7.25 | 0.00 | 0.00 | 0.00 |
November | 67.21 | 32.40 | 34.81 | 120.88 | 17.45 | 0.00 | 0.00 | 0.00 |
December | 62.39 | 30.82 | 31.57 | 99.75 | 30.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.76 | 14.30 | 33.46 | 100.66 | 13.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.42 | 0.04 | 30.17 | 78.56 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.21 | 32.40 | 36.70 | 127.03 | 35.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.78 | 29.51 | 33.26 | 95.37 | 35.62 | 0.00 | 0.00 | 0.00 |
February | 58.95 | 24.11 | 34.84 | 94.46 | 30.34 | 0.00 | 0.00 | 0.00 |
March | 48.52 | 13.17 | 35.35 | 85.93 | 23.49 | 0.00 | 0.00 | 0.00 |
April | 38.14 | 4.04 | 34.10 | 78.56 | 14.91 | 0.00 | 0.00 | 0.00 |
May | 32.31 | 0.49 | 31.81 | 84.66 | 4.04 | 0.00 | 0.00 | 0.00 |
June | 30.43 | 0.04 | 30.39 | 87.71 | 1.14 | 0.00 | 0.00 | 0.00 |
July | 30.42 | 0.26 | 30.17 | 101.47 | 0.06 | 0.00 | 0.00 | 0.00 |
August | 35.29 | 2.50 | 32.79 | 113.85 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 46.53 | 10.66 | 35.87 | 117.78 | 1.92 | 0.00 | 0.00 | 0.00 |
October | 60.92 | 24.22 | 36.70 | 127.03 | 7.25 | 0.00 | 0.00 | 0.00 |
November | 67.21 | 32.40 | 34.81 | 120.88 | 17.45 | 0.00 | 0.00 | 0.00 |
December | 62.39 | 30.82 | 31.57 | 99.75 | 30.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.76 | 14.30 | 33.46 | 100.66 | 13.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.42 | 0.04 | 30.17 | 78.56 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.21 | 32.40 | 36.70 | 127.03 | 35.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.78 | 29.51 | 33.26 | 95.37 | 35.62 | 0.00 | 0.00 | 0.00 |
February | 58.95 | 24.11 | 34.84 | 94.46 | 30.34 | 0.00 | 0.00 | 0.00 |
March | 48.52 | 13.17 | 35.35 | 85.93 | 23.49 | 0.00 | 0.00 | 0.00 |
April | 38.14 | 4.04 | 34.10 | 78.56 | 14.91 | 0.00 | 0.00 | 0.00 |
May | 32.31 | 0.49 | 31.81 | 84.66 | 4.04 | 0.00 | 0.00 | 0.00 |
June | 30.43 | 0.04 | 30.39 | 87.71 | 1.14 | 0.00 | 0.00 | 0.00 |
July | 30.42 | 0.26 | 30.17 | 101.47 | 0.06 | 0.00 | 0.00 | 0.00 |
August | 35.29 | 2.50 | 32.79 | 113.85 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 46.53 | 10.66 | 35.87 | 117.78 | 1.92 | 0.00 | 0.00 | 0.00 |
October | 60.92 | 24.22 | 36.70 | 127.03 | 7.25 | 0.00 | 0.00 | 0.00 |
November | 67.21 | 32.40 | 34.81 | 120.88 | 17.45 | 0.00 | 0.00 | 0.00 |
December | 62.39 | 30.82 | 31.57 | 99.75 | 30.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.76 | 14.30 | 33.46 | 100.66 | 13.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.42 | 0.04 | 30.17 | 78.56 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.21 | 32.40 | 36.70 | 127.03 | 35.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.78 | 29.51 | 33.26 | 95.37 | 35.62 | 0.00 | 0.00 | 0.00 |
February | 58.95 | 24.11 | 34.84 | 94.46 | 30.34 | 0.00 | 0.00 | 0.00 |
March | 48.52 | 13.17 | 35.35 | 85.93 | 23.49 | 0.00 | 0.00 | 0.00 |
April | 38.14 | 4.04 | 34.10 | 78.56 | 14.91 | 0.00 | 0.00 | 0.00 |
May | 32.31 | 0.49 | 31.81 | 84.66 | 4.04 | 0.00 | 0.00 | 0.00 |
June | 30.43 | 0.04 | 30.39 | 87.71 | 1.14 | 0.00 | 0.00 | 0.00 |
July | 30.42 | 0.26 | 30.17 | 101.47 | 0.06 | 0.00 | 0.00 | 0.00 |
August | 35.29 | 2.50 | 32.79 | 113.85 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 46.53 | 10.66 | 35.87 | 117.78 | 1.92 | 0.00 | 0.00 | 0.00 |
October | 60.92 | 24.22 | 36.70 | 127.03 | 7.25 | 0.00 | 0.00 | 0.00 |
November | 67.21 | 32.40 | 34.81 | 120.88 | 17.45 | 0.00 | 0.00 | 0.00 |
December | 62.39 | 30.82 | 31.57 | 99.75 | 30.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.76 | 14.30 | 33.46 | 100.66 | 13.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.42 | 0.04 | 30.17 | 78.56 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.21 | 32.40 | 36.70 | 127.03 | 35.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.05 | 35.29 | 39.77 | 114.13 | 42.22 | 0.00 | 0.00 | 0.00 |
February | 70.48 | 28.83 | 41.65 | 112.97 | 35.98 | 0.00 | 0.00 | 0.00 |
March | 58.01 | 15.75 | 42.26 | 102.59 | 27.93 | 0.00 | 0.00 | 0.00 |
April | 45.60 | 4.83 | 40.76 | 93.52 | 17.79 | 0.00 | 0.00 | 0.00 |
May | 38.63 | 0.59 | 38.03 | 100.30 | 4.88 | 0.00 | 0.00 | 0.00 |
June | 36.38 | 0.05 | 36.33 | 103.67 | 1.42 | 0.00 | 0.00 | 0.00 |
July | 36.38 | 0.31 | 36.07 | 119.98 | 0.08 | 0.00 | 0.00 | 0.00 |
August | 42.19 | 2.99 | 39.20 | 134.74 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 55.63 | 12.75 | 42.88 | 139.83 | 2.34 | 0.00 | 0.00 | 0.00 |
October | 72.83 | 28.96 | 43.88 | 151.23 | 8.73 | 0.00 | 0.00 | 0.00 |
November | 80.35 | 38.73 | 41.61 | 144.24 | 20.84 | 0.00 | 0.00 | 0.00 |
December | 74.59 | 36.84 | 37.74 | 119.24 | 35.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.10 | 17.10 | 40.00 | 119.75 | 16.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.38 | 0.05 | 36.07 | 93.52 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 80.35 | 38.73 | 43.88 | 151.23 | 42.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.05 | 35.29 | 39.77 | 114.13 | 42.22 | 0.00 | 0.00 | 0.00 |
February | 70.48 | 28.83 | 41.65 | 112.97 | 35.98 | 0.00 | 0.00 | 0.00 |
March | 58.01 | 15.75 | 42.26 | 102.59 | 27.93 | 0.00 | 0.00 | 0.00 |
April | 45.60 | 4.83 | 40.76 | 93.52 | 17.79 | 0.00 | 0.00 | 0.00 |
May | 38.63 | 0.59 | 38.03 | 100.30 | 4.88 | 0.00 | 0.00 | 0.00 |
June | 36.38 | 0.05 | 36.33 | 103.67 | 1.42 | 0.00 | 0.00 | 0.00 |
July | 36.38 | 0.31 | 36.07 | 119.98 | 0.08 | 0.00 | 0.00 | 0.00 |
August | 42.19 | 2.99 | 39.20 | 134.74 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 55.63 | 12.75 | 42.88 | 139.83 | 2.34 | 0.00 | 0.00 | 0.00 |
October | 72.83 | 28.96 | 43.88 | 151.23 | 8.73 | 0.00 | 0.00 | 0.00 |
November | 80.35 | 38.73 | 41.61 | 144.24 | 20.84 | 0.00 | 0.00 | 0.00 |
December | 74.59 | 36.84 | 37.74 | 119.24 | 35.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.10 | 17.10 | 40.00 | 119.75 | 16.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.38 | 0.05 | 36.07 | 93.52 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 80.35 | 38.73 | 43.88 | 151.23 | 42.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.78 | 29.51 | 33.26 | 95.19 | 35.52 | 0.00 | 0.00 | 0.00 |
February | 58.95 | 24.11 | 34.84 | 94.32 | 30.17 | 0.00 | 0.00 | 0.00 |
March | 48.52 | 13.17 | 35.35 | 85.92 | 23.24 | 0.00 | 0.00 | 0.00 |
April | 38.14 | 4.04 | 34.10 | 78.73 | 14.59 | 0.00 | 0.00 | 0.00 |
May | 32.31 | 0.49 | 31.81 | 85.33 | 3.84 | 0.00 | 0.00 | 0.00 |
June | 30.43 | 0.04 | 30.39 | 88.66 | 1.01 | 0.00 | 0.00 | 0.00 |
July | 30.42 | 0.26 | 30.17 | 102.58 | 0.05 | 0.00 | 0.00 | 0.00 |
August | 35.29 | 2.50 | 32.79 | 115.02 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 46.53 | 10.66 | 35.87 | 118.53 | 1.77 | 0.00 | 0.00 | 0.00 |
October | 60.92 | 24.22 | 36.70 | 127.37 | 6.91 | 0.00 | 0.00 | 0.00 |
November | 67.21 | 32.40 | 34.81 | 120.93 | 17.10 | 0.00 | 0.00 | 0.00 |
December | 62.39 | 30.82 | 31.57 | 99.63 | 30.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.76 | 14.30 | 33.46 | 101.06 | 13.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.42 | 0.04 | 30.17 | 78.73 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.21 | 32.40 | 36.70 | 127.37 | 35.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.78 | 29.51 | 33.26 | 95.19 | 35.52 | 0.00 | 0.00 | 0.00 |
February | 58.95 | 24.11 | 34.84 | 94.32 | 30.17 | 0.00 | 0.00 | 0.00 |
March | 48.52 | 13.17 | 35.35 | 85.92 | 23.24 | 0.00 | 0.00 | 0.00 |
April | 38.14 | 4.04 | 34.10 | 78.73 | 14.59 | 0.00 | 0.00 | 0.00 |
May | 32.31 | 0.49 | 31.81 | 85.33 | 3.84 | 0.00 | 0.00 | 0.00 |
June | 30.43 | 0.04 | 30.39 | 88.66 | 1.01 | 0.00 | 0.00 | 0.00 |
July | 30.42 | 0.26 | 30.17 | 102.58 | 0.05 | 0.00 | 0.00 | 0.00 |
August | 35.29 | 2.50 | 32.79 | 115.02 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 46.53 | 10.66 | 35.87 | 118.53 | 1.77 | 0.00 | 0.00 | 0.00 |
October | 60.92 | 24.22 | 36.70 | 127.37 | 6.91 | 0.00 | 0.00 | 0.00 |
November | 67.21 | 32.40 | 34.81 | 120.93 | 17.10 | 0.00 | 0.00 | 0.00 |
December | 62.39 | 30.82 | 31.57 | 99.63 | 30.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.76 | 14.30 | 33.46 | 101.06 | 13.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.42 | 0.04 | 30.17 | 78.73 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.21 | 32.40 | 36.70 | 127.37 | 35.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.05 | 35.29 | 39.77 | 113.95 | 42.09 | 0.00 | 0.00 | 0.00 |
February | 70.48 | 28.83 | 41.65 | 112.84 | 35.78 | 0.00 | 0.00 | 0.00 |
March | 58.01 | 15.75 | 42.26 | 102.59 | 27.63 | 0.00 | 0.00 | 0.00 |
April | 45.60 | 4.83 | 40.76 | 93.73 | 17.43 | 0.00 | 0.00 | 0.00 |
May | 38.63 | 0.59 | 38.03 | 101.06 | 4.64 | 0.00 | 0.00 | 0.00 |
June | 36.38 | 0.05 | 36.33 | 104.75 | 1.26 | 0.00 | 0.00 | 0.00 |
July | 36.38 | 0.31 | 36.07 | 121.25 | 0.07 | 0.00 | 0.00 | 0.00 |
August | 42.19 | 2.99 | 39.20 | 136.07 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 55.63 | 12.75 | 42.88 | 140.69 | 2.16 | 0.00 | 0.00 | 0.00 |
October | 72.83 | 28.96 | 43.88 | 151.63 | 8.33 | 0.00 | 0.00 | 0.00 |
November | 80.35 | 38.73 | 41.61 | 144.32 | 20.43 | 0.00 | 0.00 | 0.00 |
December | 74.59 | 36.84 | 37.74 | 119.14 | 35.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.10 | 17.10 | 40.00 | 120.22 | 16.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.38 | 0.05 | 36.07 | 93.73 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 80.35 | 38.73 | 43.88 | 151.63 | 42.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.78 | 29.51 | 33.26 | 95.25 | 35.41 | 0.00 | 0.00 | 0.00 |
February | 58.95 | 24.11 | 34.84 | 94.38 | 30.06 | 0.00 | 0.00 | 0.00 |
March | 48.52 | 13.17 | 35.35 | 85.98 | 23.13 | 0.00 | 0.00 | 0.00 |
April | 38.14 | 4.04 | 34.10 | 78.79 | 14.51 | 0.00 | 0.00 | 0.00 |
May | 32.31 | 0.49 | 31.81 | 85.40 | 3.80 | 0.00 | 0.00 | 0.00 |
June | 30.43 | 0.04 | 30.39 | 88.75 | 0.99 | 0.00 | 0.00 | 0.00 |
July | 30.42 | 0.26 | 30.17 | 102.67 | 0.05 | 0.00 | 0.00 | 0.00 |
August | 35.29 | 2.50 | 32.79 | 115.10 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 46.53 | 10.66 | 35.87 | 118.60 | 1.75 | 0.00 | 0.00 | 0.00 |
October | 60.92 | 24.22 | 36.70 | 127.42 | 6.87 | 0.00 | 0.00 | 0.00 |
November | 67.21 | 32.40 | 34.81 | 120.98 | 17.04 | 0.00 | 0.00 | 0.00 |
December | 62.39 | 30.82 | 31.57 | 99.68 | 29.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.76 | 14.30 | 33.46 | 101.13 | 13.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.42 | 0.04 | 30.17 | 78.79 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.21 | 32.40 | 36.70 | 127.42 | 35.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.78 | 29.51 | 33.26 | 95.25 | 35.41 | 0.00 | 0.00 | 0.00 |
February | 58.95 | 24.11 | 34.84 | 94.38 | 30.06 | 0.00 | 0.00 | 0.00 |
March | 48.52 | 13.17 | 35.35 | 85.98 | 23.13 | 0.00 | 0.00 | 0.00 |
April | 38.14 | 4.04 | 34.10 | 78.79 | 14.51 | 0.00 | 0.00 | 0.00 |
May | 32.31 | 0.49 | 31.81 | 85.40 | 3.80 | 0.00 | 0.00 | 0.00 |
June | 30.43 | 0.04 | 30.39 | 88.75 | 0.99 | 0.00 | 0.00 | 0.00 |
July | 30.42 | 0.26 | 30.17 | 102.67 | 0.05 | 0.00 | 0.00 | 0.00 |
August | 35.29 | 2.50 | 32.79 | 115.10 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 46.53 | 10.66 | 35.87 | 118.60 | 1.75 | 0.00 | 0.00 | 0.00 |
October | 60.92 | 24.22 | 36.70 | 127.42 | 6.87 | 0.00 | 0.00 | 0.00 |
November | 67.21 | 32.40 | 34.81 | 120.98 | 17.04 | 0.00 | 0.00 | 0.00 |
December | 62.39 | 30.82 | 31.57 | 99.68 | 29.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.76 | 14.30 | 33.46 | 101.13 | 13.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.42 | 0.04 | 30.17 | 78.79 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.21 | 32.40 | 36.70 | 127.42 | 35.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.05 | 35.29 | 39.77 | 114.03 | 41.96 | 0.00 | 0.00 | 0.00 |
February | 70.48 | 28.83 | 41.65 | 112.91 | 35.65 | 0.00 | 0.00 | 0.00 |
March | 58.01 | 15.75 | 42.26 | 102.66 | 27.51 | 0.00 | 0.00 | 0.00 |
April | 45.60 | 4.83 | 40.76 | 93.80 | 17.33 | 0.00 | 0.00 | 0.00 |
May | 38.63 | 0.59 | 38.03 | 101.15 | 4.60 | 0.00 | 0.00 | 0.00 |
June | 36.38 | 0.05 | 36.33 | 104.85 | 1.24 | 0.00 | 0.00 | 0.00 |
July | 36.38 | 0.31 | 36.07 | 121.35 | 0.07 | 0.00 | 0.00 | 0.00 |
August | 42.19 | 2.99 | 39.20 | 136.16 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 55.63 | 12.75 | 42.88 | 140.77 | 2.14 | 0.00 | 0.00 | 0.00 |
October | 72.83 | 28.96 | 43.88 | 151.69 | 8.28 | 0.00 | 0.00 | 0.00 |
November | 80.35 | 38.73 | 41.61 | 144.37 | 20.35 | 0.00 | 0.00 | 0.00 |
December | 74.59 | 36.84 | 37.74 | 119.20 | 35.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.10 | 17.10 | 40.00 | 120.30 | 16.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.38 | 0.05 | 36.07 | 93.80 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 80.35 | 38.73 | 43.88 | 151.69 | 41.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.78 | 29.51 | 33.26 | 95.39 | 35.12 | 0.00 | 0.00 | 0.00 |
February | 58.95 | 24.11 | 34.84 | 94.50 | 29.78 | 0.00 | 0.00 | 0.00 |
March | 48.52 | 13.17 | 35.35 | 86.06 | 22.90 | 0.00 | 0.00 | 0.00 |
April | 38.14 | 4.04 | 34.10 | 78.81 | 14.40 | 0.00 | 0.00 | 0.00 |
May | 32.31 | 0.49 | 31.81 | 85.27 | 3.83 | 0.00 | 0.00 | 0.00 |
June | 30.43 | 0.04 | 30.39 | 88.51 | 1.03 | 0.00 | 0.00 | 0.00 |
July | 30.42 | 0.26 | 30.17 | 102.25 | 0.06 | 0.00 | 0.00 | 0.00 |
August | 35.29 | 2.50 | 32.79 | 114.62 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 46.53 | 10.66 | 35.87 | 118.27 | 1.82 | 0.00 | 0.00 | 0.00 |
October | 60.92 | 24.22 | 36.70 | 127.26 | 7.00 | 0.00 | 0.00 | 0.00 |
November | 67.21 | 32.40 | 34.81 | 120.94 | 17.06 | 0.00 | 0.00 | 0.00 |
December | 62.39 | 30.82 | 31.57 | 99.75 | 29.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.76 | 14.30 | 33.46 | 101.02 | 13.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.42 | 0.04 | 30.17 | 78.81 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.21 | 32.40 | 36.70 | 127.26 | 35.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.78 | 29.51 | 33.26 | 95.39 | 35.12 | 0.00 | 0.00 | 0.00 |
February | 58.95 | 24.11 | 34.84 | 94.50 | 29.78 | 0.00 | 0.00 | 0.00 |
March | 48.52 | 13.17 | 35.35 | 86.06 | 22.90 | 0.00 | 0.00 | 0.00 |
April | 38.14 | 4.04 | 34.10 | 78.81 | 14.40 | 0.00 | 0.00 | 0.00 |
May | 32.31 | 0.49 | 31.81 | 85.27 | 3.83 | 0.00 | 0.00 | 0.00 |
June | 30.43 | 0.04 | 30.39 | 88.51 | 1.03 | 0.00 | 0.00 | 0.00 |
July | 30.42 | 0.26 | 30.17 | 102.25 | 0.06 | 0.00 | 0.00 | 0.00 |
August | 35.29 | 2.50 | 32.79 | 114.62 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 46.53 | 10.66 | 35.87 | 118.27 | 1.82 | 0.00 | 0.00 | 0.00 |
October | 60.92 | 24.22 | 36.70 | 127.26 | 7.00 | 0.00 | 0.00 | 0.00 |
November | 67.21 | 32.40 | 34.81 | 120.94 | 17.06 | 0.00 | 0.00 | 0.00 |
December | 62.39 | 30.82 | 31.57 | 99.75 | 29.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.76 | 14.30 | 33.46 | 101.02 | 13.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.42 | 0.04 | 30.17 | 78.81 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.21 | 32.40 | 36.70 | 127.26 | 35.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.05 | 35.29 | 39.77 | 114.20 | 41.63 | 0.00 | 0.00 | 0.00 |
February | 70.48 | 28.83 | 41.65 | 113.06 | 35.32 | 0.00 | 0.00 | 0.00 |
March | 58.01 | 15.75 | 42.26 | 102.77 | 27.23 | 0.00 | 0.00 | 0.00 |
April | 45.60 | 4.83 | 40.76 | 93.83 | 17.20 | 0.00 | 0.00 | 0.00 |
May | 38.63 | 0.59 | 38.03 | 100.99 | 4.63 | 0.00 | 0.00 | 0.00 |
June | 36.38 | 0.05 | 36.33 | 104.57 | 1.29 | 0.00 | 0.00 | 0.00 |
July | 36.38 | 0.31 | 36.07 | 120.85 | 0.08 | 0.00 | 0.00 | 0.00 |
August | 42.19 | 2.99 | 39.20 | 135.58 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 55.63 | 12.75 | 42.88 | 140.39 | 2.23 | 0.00 | 0.00 | 0.00 |
October | 72.83 | 28.96 | 43.88 | 151.50 | 8.44 | 0.00 | 0.00 | 0.00 |
November | 80.35 | 38.73 | 41.61 | 144.32 | 20.39 | 0.00 | 0.00 | 0.00 |
December | 74.59 | 36.84 | 37.74 | 119.28 | 35.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.10 | 17.10 | 40.00 | 120.16 | 16.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.38 | 0.05 | 36.07 | 93.83 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 80.35 | 38.73 | 43.88 | 151.50 | 41.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.78 | 29.51 | 33.26 | 95.49 | 34.27 | 0.00 | 0.00 | 0.00 |
February | 58.95 | 24.11 | 34.84 | 94.55 | 28.87 | 0.00 | 0.00 | 0.00 |
March | 48.52 | 13.17 | 35.35 | 85.94 | 22.17 | 0.00 | 0.00 | 0.00 |
April | 38.14 | 4.04 | 34.10 | 78.28 | 14.21 | 0.00 | 0.00 | 0.00 |
May | 32.31 | 0.49 | 31.81 | 83.62 | 4.09 | 0.00 | 0.00 | 0.00 |
June | 30.43 | 0.04 | 30.39 | 86.22 | 1.29 | 0.00 | 0.00 | 0.00 |
July | 30.42 | 0.26 | 30.17 | 98.90 | 0.12 | 0.00 | 0.00 | 0.00 |
August | 35.29 | 2.50 | 32.79 | 110.81 | 0.06 | 0.00 | 0.00 | 0.00 |
September | 46.53 | 10.66 | 35.87 | 115.63 | 2.36 | 0.00 | 0.00 | 0.00 |
October | 60.92 | 24.22 | 36.70 | 125.69 | 7.99 | 0.00 | 0.00 | 0.00 |
November | 67.21 | 32.40 | 34.81 | 120.13 | 17.68 | 0.00 | 0.00 | 0.00 |
December | 62.39 | 30.82 | 31.57 | 99.60 | 29.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.76 | 14.30 | 33.46 | 99.61 | 13.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.42 | 0.04 | 30.17 | 78.28 | 0.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.21 | 32.40 | 36.70 | 125.69 | 34.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.78 | 29.51 | 33.26 | 95.49 | 34.27 | 0.00 | 0.00 | 0.00 |
February | 58.95 | 24.11 | 34.84 | 94.55 | 28.87 | 0.00 | 0.00 | 0.00 |
March | 48.52 | 13.17 | 35.35 | 85.94 | 22.17 | 0.00 | 0.00 | 0.00 |
April | 38.14 | 4.04 | 34.10 | 78.28 | 14.21 | 0.00 | 0.00 | 0.00 |
May | 32.31 | 0.49 | 31.81 | 83.62 | 4.09 | 0.00 | 0.00 | 0.00 |
June | 30.43 | 0.04 | 30.39 | 86.22 | 1.29 | 0.00 | 0.00 | 0.00 |
July | 30.42 | 0.26 | 30.17 | 98.90 | 0.12 | 0.00 | 0.00 | 0.00 |
August | 35.29 | 2.50 | 32.79 | 110.81 | 0.06 | 0.00 | 0.00 | 0.00 |
September | 46.53 | 10.66 | 35.87 | 115.63 | 2.36 | 0.00 | 0.00 | 0.00 |
October | 60.92 | 24.22 | 36.70 | 125.69 | 7.99 | 0.00 | 0.00 | 0.00 |
November | 67.21 | 32.40 | 34.81 | 120.13 | 17.68 | 0.00 | 0.00 | 0.00 |
December | 62.39 | 30.82 | 31.57 | 99.60 | 29.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.76 | 14.30 | 33.46 | 99.61 | 13.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.42 | 0.04 | 30.17 | 78.28 | 0.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.21 | 32.40 | 36.70 | 125.69 | 34.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.05 | 35.29 | 39.77 | 114.31 | 40.63 | 0.00 | 0.00 | 0.00 |
February | 70.48 | 28.83 | 41.65 | 113.11 | 34.25 | 0.00 | 0.00 | 0.00 |
March | 58.01 | 15.75 | 42.26 | 102.61 | 26.38 | 0.00 | 0.00 | 0.00 |
April | 45.60 | 4.83 | 40.76 | 93.19 | 16.99 | 0.00 | 0.00 | 0.00 |
May | 38.63 | 0.59 | 38.03 | 99.03 | 4.95 | 0.00 | 0.00 | 0.00 |
June | 36.38 | 0.05 | 36.33 | 101.85 | 1.61 | 0.00 | 0.00 | 0.00 |
July | 36.38 | 0.31 | 36.07 | 116.87 | 0.15 | 0.00 | 0.00 | 0.00 |
August | 42.19 | 2.99 | 39.20 | 131.05 | 0.08 | 0.00 | 0.00 | 0.00 |
September | 55.63 | 12.75 | 42.88 | 137.26 | 2.89 | 0.00 | 0.00 | 0.00 |
October | 72.83 | 28.96 | 43.88 | 149.63 | 9.63 | 0.00 | 0.00 | 0.00 |
November | 80.35 | 38.73 | 41.61 | 143.36 | 21.12 | 0.00 | 0.00 | 0.00 |
December | 74.59 | 36.84 | 37.74 | 119.10 | 34.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.10 | 17.10 | 40.00 | 118.48 | 16.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.38 | 0.05 | 36.07 | 93.19 | 0.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 80.35 | 38.73 | 43.88 | 149.63 | 40.63 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168140E+09 | 79050247.79 | 89089825.42 | 0.254572E+09 | 95604380.93 |
February | 0.142611E+09 | 58334110.25 | 84276813.20 | 0.228120E+09 | 72649766.21 |
March | 0.129951E+09 | 35281028.83 | 94670103.70 | 0.230022E+09 | 61452773.81 |
April | 98856132.43 | 10480621.16 | 88375511.27 | 0.205030E+09 | 35943786.29 |
May | 86531017.69 | 1325136.47 | 85205881.22 | 0.233019E+09 | 9257495.71 |
June | 78863524.57 | 97596.59 | 78765927.99 | 0.234493E+09 | 2417084.79 |
July | 81490104.20 | 692417.37 | 80797686.83 | 0.282672E+09 | 63138.54 |
August | 94522041.84 | 6697269.10 | 87824772.74 | 0.313908E+09 | 45158.70 |
September | 0.120608E+09 | 27640881.62 | 92967288.71 | 0.313181E+09 | 4356141.29 |
October | 0.163163E+09 | 64866492.43 | 98296522.40 | 0.344701E+09 | 16567566.37 |
November | 0.174195E+09 | 83975166.54 | 90220290.42 | 0.313797E+09 | 42157194.66 |
December | 0.167096E+09 | 82540540.50 | 84555830.53 | 0.266693E+09 | 79517216.23 |
Annual Sum or Average | 0.150603E+10 | 0.450982E+09 | 0.105505E+10 | 0.322021E+10 | 0.420032E+09 |
Minimum of Months | 78863524.57 | 97596.59 | 78765927.99 | 0.205030E+09 | 45158.70 |
Maximum of Months | 0.174195E+09 | 83975166.54 | 98296522.40 | 0.344701E+09 | 95604380.93 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168140E+09 | 79050247.79 | 89089825.42 | 0.254572E+09 | 95604380.93 |
February | 0.142611E+09 | 58334110.25 | 84276813.20 | 0.228120E+09 | 72649766.21 |
March | 0.129951E+09 | 35281028.83 | 94670103.70 | 0.230022E+09 | 61452773.81 |
April | 98856132.43 | 10480621.16 | 88375511.27 | 0.205030E+09 | 35943786.29 |
May | 86531017.69 | 1325136.47 | 85205881.22 | 0.233019E+09 | 9257495.71 |
June | 78863524.57 | 97596.59 | 78765927.99 | 0.234493E+09 | 2417084.79 |
July | 81490104.20 | 692417.37 | 80797686.83 | 0.282672E+09 | 63138.54 |
August | 94522041.84 | 6697269.10 | 87824772.74 | 0.313908E+09 | 45158.70 |
September | 0.120608E+09 | 27640881.62 | 92967288.71 | 0.313181E+09 | 4356141.29 |
October | 0.163163E+09 | 64866492.43 | 98296522.40 | 0.344701E+09 | 16567566.37 |
November | 0.174195E+09 | 83975166.54 | 90220290.42 | 0.313797E+09 | 42157194.66 |
December | 0.167096E+09 | 82540540.50 | 84555830.53 | 0.266693E+09 | 79517216.23 |
Annual Sum or Average | 0.150603E+10 | 0.450982E+09 | 0.105505E+10 | 0.322021E+10 | 0.420032E+09 |
Minimum of Months | 78863524.57 | 97596.59 | 78765927.99 | 0.205030E+09 | 45158.70 |
Maximum of Months | 0.174195E+09 | 83975166.54 | 98296522.40 | 0.344701E+09 | 95604380.93 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168140E+09 | 79050247.79 | 89089825.42 | 0.254572E+09 | 95604380.93 |
February | 0.142611E+09 | 58334110.25 | 84276813.20 | 0.228120E+09 | 72649766.21 |
March | 0.129951E+09 | 35281028.83 | 94670103.70 | 0.230022E+09 | 61452773.81 |
April | 98856132.43 | 10480621.16 | 88375511.27 | 0.205030E+09 | 35943786.29 |
May | 86531017.69 | 1325136.47 | 85205881.22 | 0.233019E+09 | 9257495.71 |
June | 78863524.57 | 97596.59 | 78765927.99 | 0.234493E+09 | 2417084.79 |
July | 81490104.20 | 692417.37 | 80797686.83 | 0.282672E+09 | 63138.54 |
August | 94522041.84 | 6697269.10 | 87824772.74 | 0.313908E+09 | 45158.70 |
September | 0.120608E+09 | 27640881.62 | 92967288.71 | 0.313181E+09 | 4356141.29 |
October | 0.163163E+09 | 64866492.43 | 98296522.40 | 0.344701E+09 | 16567566.37 |
November | 0.174195E+09 | 83975166.54 | 90220290.42 | 0.313797E+09 | 42157194.66 |
December | 0.167096E+09 | 82540540.50 | 84555830.53 | 0.266693E+09 | 79517216.23 |
Annual Sum or Average | 0.150603E+10 | 0.450982E+09 | 0.105505E+10 | 0.322021E+10 | 0.420032E+09 |
Minimum of Months | 78863524.57 | 97596.59 | 78765927.99 | 0.205030E+09 | 45158.70 |
Maximum of Months | 0.174195E+09 | 83975166.54 | 98296522.40 | 0.344701E+09 | 95604380.93 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168140E+09 | 79050247.79 | 89089825.42 | 0.254572E+09 | 95604380.93 |
February | 0.142611E+09 | 58334110.25 | 84276813.20 | 0.228120E+09 | 72649766.21 |
March | 0.129951E+09 | 35281028.83 | 94670103.70 | 0.230022E+09 | 61452773.81 |
April | 98856132.43 | 10480621.16 | 88375511.27 | 0.205030E+09 | 35943786.29 |
May | 86531017.69 | 1325136.47 | 85205881.22 | 0.233019E+09 | 9257495.71 |
June | 78863524.57 | 97596.59 | 78765927.99 | 0.234493E+09 | 2417084.79 |
July | 81490104.20 | 692417.37 | 80797686.83 | 0.282672E+09 | 63138.54 |
August | 94522041.84 | 6697269.10 | 87824772.74 | 0.313908E+09 | 45158.70 |
September | 0.120608E+09 | 27640881.62 | 92967288.71 | 0.313181E+09 | 4356141.29 |
October | 0.163163E+09 | 64866492.43 | 98296522.40 | 0.344701E+09 | 16567566.37 |
November | 0.174195E+09 | 83975166.54 | 90220290.42 | 0.313797E+09 | 42157194.66 |
December | 0.167096E+09 | 82540540.50 | 84555830.53 | 0.266693E+09 | 79517216.23 |
Annual Sum or Average | 0.150603E+10 | 0.450982E+09 | 0.105505E+10 | 0.322021E+10 | 0.420032E+09 |
Minimum of Months | 78863524.57 | 97596.59 | 78765927.99 | 0.205030E+09 | 45158.70 |
Maximum of Months | 0.174195E+09 | 83975166.54 | 98296522.40 | 0.344701E+09 | 95604380.93 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.202130E+09 | 95030567.71 | 0.107100E+09 | 0.306296E+09 | 0.114014E+09 |
February | 0.171440E+09 | 70126581.11 | 0.101314E+09 | 0.274302E+09 | 86704081.15 |
March | 0.156221E+09 | 42413228.20 | 0.113808E+09 | 0.276076E+09 | 73560334.16 |
April | 0.118840E+09 | 12599320.14 | 0.106241E+09 | 0.245324E+09 | 43215564.88 |
May | 0.104024E+09 | 1593018.04 | 0.102431E+09 | 0.277334E+09 | 11243553.35 |
June | 94806097.65 | 117326.12 | 94688771.53 | 0.278441E+09 | 3028231.81 |
July | 97963650.72 | 832392.27 | 97131258.45 | 0.335769E+09 | 87233.40 |
August | 0.113630E+09 | 8051148.50 | 0.105579E+09 | 0.373217E+09 | 60195.47 |
September | 0.144990E+09 | 33228595.05 | 0.111761E+09 | 0.373533E+09 | 5334737.15 |
October | 0.196147E+09 | 77979510.16 | 0.118168E+09 | 0.412309E+09 | 20085051.81 |
November | 0.209410E+09 | 0.100951E+09 | 0.108459E+09 | 0.376396E+09 | 50724005.78 |
December | 0.200876E+09 | 99226436.87 | 0.101649E+09 | 0.320529E+09 | 95010871.94 |
Annual Sum or Average | 0.181048E+10 | 0.542149E+09 | 0.126833E+10 | 0.384953E+10 | 0.503068E+09 |
Minimum of Months | 94806097.65 | 117326.12 | 94688771.53 | 0.245324E+09 | 60195.47 |
Maximum of Months | 0.209410E+09 | 0.100951E+09 | 0.118168E+09 | 0.412309E+09 | 0.114014E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.202130E+09 | 95030567.71 | 0.107100E+09 | 0.306296E+09 | 0.114014E+09 |
February | 0.171440E+09 | 70126581.11 | 0.101314E+09 | 0.274302E+09 | 86704081.15 |
March | 0.156221E+09 | 42413228.20 | 0.113808E+09 | 0.276076E+09 | 73560334.16 |
April | 0.118840E+09 | 12599320.14 | 0.106241E+09 | 0.245324E+09 | 43215564.88 |
May | 0.104024E+09 | 1593018.04 | 0.102431E+09 | 0.277334E+09 | 11243553.35 |
June | 94806097.65 | 117326.12 | 94688771.53 | 0.278441E+09 | 3028231.81 |
July | 97963650.72 | 832392.27 | 97131258.45 | 0.335769E+09 | 87233.40 |
August | 0.113630E+09 | 8051148.50 | 0.105579E+09 | 0.373217E+09 | 60195.47 |
September | 0.144990E+09 | 33228595.05 | 0.111761E+09 | 0.373533E+09 | 5334737.15 |
October | 0.196147E+09 | 77979510.16 | 0.118168E+09 | 0.412309E+09 | 20085051.81 |
November | 0.209410E+09 | 0.100951E+09 | 0.108459E+09 | 0.376396E+09 | 50724005.78 |
December | 0.200876E+09 | 99226436.87 | 0.101649E+09 | 0.320529E+09 | 95010871.94 |
Annual Sum or Average | 0.181048E+10 | 0.542149E+09 | 0.126833E+10 | 0.384953E+10 | 0.503068E+09 |
Minimum of Months | 94806097.65 | 117326.12 | 94688771.53 | 0.245324E+09 | 60195.47 |
Maximum of Months | 0.209410E+09 | 0.100951E+09 | 0.118168E+09 | 0.412309E+09 | 0.114014E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168140E+09 | 79050247.79 | 89089825.42 | 0.253499E+09 | 96712685.40 |
February | 0.142611E+09 | 58334110.25 | 84276813.20 | 0.227368E+09 | 73599660.95 |
March | 0.129951E+09 | 35281028.83 | 94670103.70 | 0.229738E+09 | 62205074.24 |
April | 98856132.43 | 10480621.16 | 88375511.27 | 0.205557E+09 | 36277050.28 |
May | 86531017.69 | 1325136.47 | 85205881.22 | 0.235490E+09 | 9123276.05 |
June | 78863524.57 | 97596.59 | 78765927.99 | 0.238043E+09 | 2183538.33 |
July | 81490104.20 | 692417.37 | 80797686.83 | 0.287473E+09 | 43824.88 |
August | 94522041.84 | 6697269.10 | 87824772.74 | 0.319436E+09 | 22820.56 |
September | 0.120608E+09 | 27640881.62 | 92967288.71 | 0.316834E+09 | 3951287.51 |
October | 0.163163E+09 | 64866492.43 | 98296522.40 | 0.346890E+09 | 15776955.26 |
November | 0.174195E+09 | 83975166.54 | 90220290.42 | 0.314441E+09 | 41505905.11 |
December | 0.167096E+09 | 82540540.50 | 84555830.53 | 0.266171E+09 | 79849946.02 |
Annual Sum or Average | 0.150603E+10 | 0.450982E+09 | 0.105505E+10 | 0.324094E+10 | 0.421252E+09 |
Minimum of Months | 78863524.57 | 97596.59 | 78765927.99 | 0.205557E+09 | 22820.56 |
Maximum of Months | 0.174195E+09 | 83975166.54 | 98296522.40 | 0.346890E+09 | 96712685.40 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168140E+09 | 79050247.79 | 89089825.42 | 0.253499E+09 | 96712685.40 |
February | 0.142611E+09 | 58334110.25 | 84276813.20 | 0.227368E+09 | 73599660.95 |
March | 0.129951E+09 | 35281028.83 | 94670103.70 | 0.229738E+09 | 62205074.24 |
April | 98856132.43 | 10480621.16 | 88375511.27 | 0.205557E+09 | 36277050.28 |
May | 86531017.69 | 1325136.47 | 85205881.22 | 0.235490E+09 | 9123276.05 |
June | 78863524.57 | 97596.59 | 78765927.99 | 0.238043E+09 | 2183538.33 |
July | 81490104.20 | 692417.37 | 80797686.83 | 0.287473E+09 | 43824.88 |
August | 94522041.84 | 6697269.10 | 87824772.74 | 0.319436E+09 | 22820.56 |
September | 0.120608E+09 | 27640881.62 | 92967288.71 | 0.316834E+09 | 3951287.51 |
October | 0.163163E+09 | 64866492.43 | 98296522.40 | 0.346890E+09 | 15776955.26 |
November | 0.174195E+09 | 83975166.54 | 90220290.42 | 0.314441E+09 | 41505905.11 |
December | 0.167096E+09 | 82540540.50 | 84555830.53 | 0.266171E+09 | 79849946.02 |
Annual Sum or Average | 0.150603E+10 | 0.450982E+09 | 0.105505E+10 | 0.324094E+10 | 0.421252E+09 |
Minimum of Months | 78863524.57 | 97596.59 | 78765927.99 | 0.205557E+09 | 22820.56 |
Maximum of Months | 0.174195E+09 | 83975166.54 | 98296522.40 | 0.346890E+09 | 96712685.40 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.202130E+09 | 95030567.71 | 0.107100E+09 | 0.305119E+09 | 0.115295E+09 |
February | 0.171440E+09 | 70126581.11 | 0.101314E+09 | 0.273489E+09 | 87807907.11 |
March | 0.156221E+09 | 42413228.20 | 0.113808E+09 | 0.275794E+09 | 74448496.61 |
April | 0.118840E+09 | 12599320.14 | 0.106241E+09 | 0.245961E+09 | 43620954.75 |
May | 0.104024E+09 | 1593018.04 | 0.102431E+09 | 0.280208E+09 | 11095195.24 |
June | 94806097.65 | 117326.12 | 94688771.53 | 0.282552E+09 | 2750653.25 |
July | 97963650.72 | 832392.27 | 97131258.45 | 0.341373E+09 | 62105.79 |
August | 0.113630E+09 | 8051148.50 | 0.105579E+09 | 0.379698E+09 | 33847.59 |
September | 0.144990E+09 | 33228595.05 | 0.111761E+09 | 0.377844E+09 | 4848705.32 |
October | 0.196147E+09 | 77979510.16 | 0.118168E+09 | 0.414949E+09 | 19157955.60 |
November | 0.209410E+09 | 0.100951E+09 | 0.108459E+09 | 0.377223E+09 | 49941497.65 |
December | 0.200876E+09 | 99226436.87 | 0.101649E+09 | 0.320000E+09 | 95385376.81 |
Annual Sum or Average | 0.181048E+10 | 0.542149E+09 | 0.126833E+10 | 0.387421E+10 | 0.504447E+09 |
Minimum of Months | 94806097.65 | 117326.12 | 94688771.53 | 0.245961E+09 | 33847.59 |
Maximum of Months | 0.209410E+09 | 0.100951E+09 | 0.118168E+09 | 0.414949E+09 | 0.115295E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168140E+09 | 79050247.79 | 89089825.42 | 0.253837E+09 | 99025538.57 |
February | 0.142611E+09 | 58334110.25 | 84276813.20 | 0.227474E+09 | 76316976.32 |
March | 0.129951E+09 | 35281028.83 | 94670103.70 | 0.229329E+09 | 65916442.07 |
April | 98856132.43 | 10480621.16 | 88375511.27 | 0.203568E+09 | 40797435.27 |
May | 86531017.69 | 1325136.47 | 85205881.22 | 0.227126E+09 | 11378640.45 |
June | 78863524.57 | 97596.59 | 78765927.99 | 0.227866E+09 | 3173715.76 |
July | 81490104.20 | 692417.37 | 80797686.83 | 0.273473E+09 | 156849.08 |
August | 94522041.84 | 6697269.10 | 87824772.74 | 0.306144E+09 | 62552.80 |
September | 0.120608E+09 | 27640881.62 | 92967288.71 | 0.306205E+09 | 5193981.24 |
October | 0.163163E+09 | 64866492.43 | 98296522.40 | 0.340775E+09 | 20130113.46 |
November | 0.174195E+09 | 83975166.54 | 90220290.42 | 0.313573E+09 | 47161466.29 |
December | 0.167096E+09 | 82540540.50 | 84555830.53 | 0.266334E+09 | 83763158.06 |
Annual Sum or Average | 0.150603E+10 | 0.450982E+09 | 0.105505E+10 | 0.317570E+10 | 0.453077E+09 |
Minimum of Months | 78863524.57 | 97596.59 | 78765927.99 | 0.203568E+09 | 62552.80 |
Maximum of Months | 0.174195E+09 | 83975166.54 | 98296522.40 | 0.340775E+09 | 99025538.57 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168140E+09 | 79050247.79 | 89089825.42 | 0.253837E+09 | 99025538.57 |
February | 0.142611E+09 | 58334110.25 | 84276813.20 | 0.227474E+09 | 76316976.32 |
March | 0.129951E+09 | 35281028.83 | 94670103.70 | 0.229329E+09 | 65916442.07 |
April | 98856132.43 | 10480621.16 | 88375511.27 | 0.203568E+09 | 40797435.27 |
May | 86531017.69 | 1325136.47 | 85205881.22 | 0.227126E+09 | 11378640.45 |
June | 78863524.57 | 97596.59 | 78765927.99 | 0.227866E+09 | 3173715.76 |
July | 81490104.20 | 692417.37 | 80797686.83 | 0.273473E+09 | 156849.08 |
August | 94522041.84 | 6697269.10 | 87824772.74 | 0.306144E+09 | 62552.80 |
September | 0.120608E+09 | 27640881.62 | 92967288.71 | 0.306205E+09 | 5193981.24 |
October | 0.163163E+09 | 64866492.43 | 98296522.40 | 0.340775E+09 | 20130113.46 |
November | 0.174195E+09 | 83975166.54 | 90220290.42 | 0.313573E+09 | 47161466.29 |
December | 0.167096E+09 | 82540540.50 | 84555830.53 | 0.266334E+09 | 83763158.06 |
Annual Sum or Average | 0.150603E+10 | 0.450982E+09 | 0.105505E+10 | 0.317570E+10 | 0.453077E+09 |
Minimum of Months | 78863524.57 | 97596.59 | 78765927.99 | 0.203568E+09 | 62552.80 |
Maximum of Months | 0.174195E+09 | 83975166.54 | 98296522.40 | 0.340775E+09 | 99025538.57 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201026E+09 | 94511274.99 | 0.106514E+09 | 0.303860E+09 | 0.117322E+09 |
February | 0.170503E+09 | 69743375.75 | 0.100760E+09 | 0.272123E+09 | 90465492.11 |
March | 0.155368E+09 | 42181461.93 | 0.113186E+09 | 0.273818E+09 | 78349061.24 |
April | 0.118191E+09 | 12530471.39 | 0.105660E+09 | 0.242347E+09 | 48688048.32 |
May | 0.103455E+09 | 1584313.03 | 0.101871E+09 | 0.269016E+09 | 13740699.13 |
June | 94288031.54 | 116684.99 | 94171346.55 | 0.269237E+09 | 3956645.80 |
July | 97428330.23 | 827843.68 | 96600486.54 | 0.323225E+09 | 207582.54 |
August | 0.113009E+09 | 8007153.16 | 0.105002E+09 | 0.362150E+09 | 84360.29 |
September | 0.144197E+09 | 33047018.03 | 0.111150E+09 | 0.363469E+09 | 6344996.35 |
October | 0.195075E+09 | 77553392.62 | 0.117522E+09 | 0.405696E+09 | 24270770.32 |
November | 0.208265E+09 | 0.100399E+09 | 0.107866E+09 | 0.374186E+09 | 56294175.62 |
December | 0.199778E+09 | 98684215.90 | 0.101094E+09 | 0.318439E+09 | 99385668.56 |
Annual Sum or Average | 0.180058E+10 | 0.539187E+09 | 0.126140E+10 | 0.377757E+10 | 0.539110E+09 |
Minimum of Months | 94288031.54 | 116684.99 | 94171346.55 | 0.242347E+09 | 84360.29 |
Maximum of Months | 0.208265E+09 | 0.100399E+09 | 0.117522E+09 | 0.405696E+09 | 0.117322E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168140E+09 | 79050247.79 | 89089825.42 | 0.254055E+09 | 98472370.96 |
February | 0.142611E+09 | 58334110.25 | 84276813.20 | 0.227580E+09 | 76027248.49 |
March | 0.129951E+09 | 35281028.83 | 94670103.70 | 0.229369E+09 | 65856149.88 |
April | 98856132.43 | 10480621.16 | 88375511.27 | 0.203478E+09 | 41159765.65 |
May | 86531017.69 | 1325136.47 | 85205881.22 | 0.226393E+09 | 11921373.66 |
June | 78863524.57 | 97596.59 | 78765927.99 | 0.226810E+09 | 3518598.36 |
July | 81490104.20 | 692417.37 | 80797686.83 | 0.271672E+09 | 210231.38 |
August | 94522041.84 | 6697269.10 | 87824772.74 | 0.304378E+09 | 84813.52 |
September | 0.120608E+09 | 27640881.62 | 92967288.71 | 0.305088E+09 | 5599036.75 |
October | 0.163163E+09 | 64866492.43 | 98296522.40 | 0.340340E+09 | 21004712.60 |
November | 0.174195E+09 | 83975166.54 | 90220290.42 | 0.313452E+09 | 47595086.39 |
December | 0.167096E+09 | 82540540.50 | 84555830.53 | 0.266401E+09 | 83606267.52 |
Annual Sum or Average | 0.150603E+10 | 0.450982E+09 | 0.105505E+10 | 0.316902E+10 | 0.455056E+09 |
Minimum of Months | 78863524.57 | 97596.59 | 78765927.99 | 0.203478E+09 | 84813.52 |
Maximum of Months | 0.174195E+09 | 83975166.54 | 98296522.40 | 0.340340E+09 | 98472370.96 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168140E+09 | 79050247.79 | 89089825.42 | 0.254055E+09 | 98472370.96 |
February | 0.142611E+09 | 58334110.25 | 84276813.20 | 0.227580E+09 | 76027248.49 |
March | 0.129951E+09 | 35281028.83 | 94670103.70 | 0.229369E+09 | 65856149.88 |
April | 98856132.43 | 10480621.16 | 88375511.27 | 0.203478E+09 | 41159765.65 |
May | 86531017.69 | 1325136.47 | 85205881.22 | 0.226393E+09 | 11921373.66 |
June | 78863524.57 | 97596.59 | 78765927.99 | 0.226810E+09 | 3518598.36 |
July | 81490104.20 | 692417.37 | 80797686.83 | 0.271672E+09 | 210231.38 |
August | 94522041.84 | 6697269.10 | 87824772.74 | 0.304378E+09 | 84813.52 |
September | 0.120608E+09 | 27640881.62 | 92967288.71 | 0.305088E+09 | 5599036.75 |
October | 0.163163E+09 | 64866492.43 | 98296522.40 | 0.340340E+09 | 21004712.60 |
November | 0.174195E+09 | 83975166.54 | 90220290.42 | 0.313452E+09 | 47595086.39 |
December | 0.167096E+09 | 82540540.50 | 84555830.53 | 0.266401E+09 | 83606267.52 |
Annual Sum or Average | 0.150603E+10 | 0.450982E+09 | 0.105505E+10 | 0.316902E+10 | 0.455056E+09 |
Minimum of Months | 78863524.57 | 97596.59 | 78765927.99 | 0.203478E+09 | 84813.52 |
Maximum of Months | 0.174195E+09 | 83975166.54 | 98296522.40 | 0.340340E+09 | 98472370.96 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201026E+09 | 94511274.99 | 0.106514E+09 | 0.304120E+09 | 0.116670E+09 |
February | 0.170503E+09 | 69743375.75 | 0.100760E+09 | 0.272250E+09 | 90124702.12 |
March | 0.155368E+09 | 42181461.93 | 0.113186E+09 | 0.273866E+09 | 78278208.21 |
April | 0.118191E+09 | 12530471.39 | 0.105660E+09 | 0.242239E+09 | 49116271.80 |
May | 0.103455E+09 | 1584313.03 | 0.101871E+09 | 0.268153E+09 | 14389261.51 |
June | 94288031.54 | 116684.99 | 94171346.55 | 0.268000E+09 | 4376968.95 |
July | 97428330.23 | 827843.68 | 96600486.54 | 0.321094E+09 | 273293.21 |
August | 0.113009E+09 | 8007153.16 | 0.105002E+09 | 0.360066E+09 | 117841.85 |
September | 0.144197E+09 | 33047018.03 | 0.111150E+09 | 0.362160E+09 | 6840130.25 |
October | 0.195075E+09 | 77553392.62 | 0.117522E+09 | 0.405181E+09 | 25308495.83 |
November | 0.208265E+09 | 0.100399E+09 | 0.107866E+09 | 0.374042E+09 | 56806593.79 |
December | 0.199778E+09 | 98684215.90 | 0.101094E+09 | 0.318518E+09 | 99200363.88 |
Annual Sum or Average | 0.180058E+10 | 0.539187E+09 | 0.126140E+10 | 0.376969E+10 | 0.541502E+09 |
Minimum of Months | 94288031.54 | 116684.99 | 94171346.55 | 0.242239E+09 | 117841.85 |
Maximum of Months | 0.208265E+09 | 0.100399E+09 | 0.117522E+09 | 0.405181E+09 | 0.116670E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168140E+09 | 79050247.79 | 89089825.42 | 0.254433E+09 | 97542536.00 |
February | 0.142611E+09 | 58334110.25 | 84276813.20 | 0.227846E+09 | 75267976.61 |
March | 0.129951E+09 | 35281028.83 | 94670103.70 | 0.229635E+09 | 65025730.39 |
April | 98856132.43 | 10480621.16 | 88375511.27 | 0.203703E+09 | 40469582.00 |
May | 86531017.69 | 1325136.47 | 85205881.22 | 0.226774E+09 | 11598764.27 |
June | 78863524.57 | 97596.59 | 78765927.99 | 0.227289E+09 | 3345314.51 |
July | 81490104.20 | 692417.37 | 80797686.83 | 0.272155E+09 | 197601.88 |
August | 94522041.84 | 6697269.10 | 87824772.74 | 0.304925E+09 | 74623.91 |
September | 0.120608E+09 | 27640881.62 | 92967288.71 | 0.305433E+09 | 5409706.75 |
October | 0.163163E+09 | 64866492.43 | 98296522.40 | 0.340530E+09 | 20548956.71 |
November | 0.174195E+09 | 83975166.54 | 90220290.42 | 0.313650E+09 | 46993682.32 |
December | 0.167096E+09 | 82540540.50 | 84555830.53 | 0.266667E+09 | 82838509.19 |
Annual Sum or Average | 0.150603E+10 | 0.450982E+09 | 0.105505E+10 | 0.317304E+10 | 0.449313E+09 |
Minimum of Months | 78863524.57 | 97596.59 | 78765927.99 | 0.203703E+09 | 74623.91 |
Maximum of Months | 0.174195E+09 | 83975166.54 | 98296522.40 | 0.340530E+09 | 97542536.00 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168140E+09 | 79050247.79 | 89089825.42 | 0.254433E+09 | 97542536.00 |
February | 0.142611E+09 | 58334110.25 | 84276813.20 | 0.227846E+09 | 75267976.61 |
March | 0.129951E+09 | 35281028.83 | 94670103.70 | 0.229635E+09 | 65025730.39 |
April | 98856132.43 | 10480621.16 | 88375511.27 | 0.203703E+09 | 40469582.00 |
May | 86531017.69 | 1325136.47 | 85205881.22 | 0.226774E+09 | 11598764.27 |
June | 78863524.57 | 97596.59 | 78765927.99 | 0.227289E+09 | 3345314.51 |
July | 81490104.20 | 692417.37 | 80797686.83 | 0.272155E+09 | 197601.88 |
August | 94522041.84 | 6697269.10 | 87824772.74 | 0.304925E+09 | 74623.91 |
September | 0.120608E+09 | 27640881.62 | 92967288.71 | 0.305433E+09 | 5409706.75 |
October | 0.163163E+09 | 64866492.43 | 98296522.40 | 0.340530E+09 | 20548956.71 |
November | 0.174195E+09 | 83975166.54 | 90220290.42 | 0.313650E+09 | 46993682.32 |
December | 0.167096E+09 | 82540540.50 | 84555830.53 | 0.266667E+09 | 82838509.19 |
Annual Sum or Average | 0.150603E+10 | 0.450982E+09 | 0.105505E+10 | 0.317304E+10 | 0.449313E+09 |
Minimum of Months | 78863524.57 | 97596.59 | 78765927.99 | 0.203703E+09 | 74623.91 |
Maximum of Months | 0.174195E+09 | 83975166.54 | 98296522.40 | 0.340530E+09 | 97542536.00 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201026E+09 | 94511274.99 | 0.106514E+09 | 0.304574E+09 | 0.115581E+09 |
February | 0.170503E+09 | 69743375.75 | 0.100760E+09 | 0.272569E+09 | 89236185.30 |
March | 0.155368E+09 | 42181461.93 | 0.113186E+09 | 0.274185E+09 | 77306166.41 |
April | 0.118191E+09 | 12530471.39 | 0.105660E+09 | 0.242508E+09 | 48308025.52 |
May | 0.103455E+09 | 1584313.03 | 0.101871E+09 | 0.268598E+09 | 14008591.24 |
June | 94288031.54 | 116684.99 | 94171346.55 | 0.268559E+09 | 4169696.98 |
July | 97428330.23 | 827843.68 | 96600486.54 | 0.321658E+09 | 257354.15 |
August | 0.113009E+09 | 8007153.16 | 0.105002E+09 | 0.360705E+09 | 105005.84 |
September | 0.144197E+09 | 33047018.03 | 0.111150E+09 | 0.362559E+09 | 6612602.02 |
October | 0.195075E+09 | 77553392.62 | 0.117522E+09 | 0.405403E+09 | 24772532.89 |
November | 0.208265E+09 | 0.100399E+09 | 0.107866E+09 | 0.374277E+09 | 56102455.14 |
December | 0.199778E+09 | 98684215.90 | 0.101094E+09 | 0.318838E+09 | 98302335.13 |
Annual Sum or Average | 0.180058E+10 | 0.539187E+09 | 0.126140E+10 | 0.377443E+10 | 0.534762E+09 |
Minimum of Months | 94288031.54 | 116684.99 | 94171346.55 | 0.242508E+09 | 105005.84 |
Maximum of Months | 0.208265E+09 | 0.100399E+09 | 0.117522E+09 | 0.405403E+09 | 0.115581E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168140E+09 | 79050247.79 | 89089825.42 | 0.255445E+09 | 95401619.44 |
February | 0.142611E+09 | 58334110.25 | 84276813.20 | 0.228507E+09 | 73396816.10 |
March | 0.129951E+09 | 35281028.83 | 94670103.70 | 0.230161E+09 | 62919411.91 |
April | 98856132.43 | 10480621.16 | 88375511.27 | 0.203616E+09 | 38639819.62 |
May | 86531017.69 | 1325136.47 | 85205881.22 | 0.226747E+09 | 10829014.94 |
June | 78863524.57 | 97596.59 | 78765927.99 | 0.227332E+09 | 2955057.53 |
July | 81490104.20 | 692417.37 | 80797686.83 | 0.271765E+09 | 173600.73 |
August | 94522041.84 | 6697269.10 | 87824772.74 | 0.304944E+09 | 53196.19 |
September | 0.120608E+09 | 27640881.62 | 92967288.71 | 0.305282E+09 | 4969862.19 |
October | 0.163163E+09 | 64866492.43 | 98296522.40 | 0.340247E+09 | 19416503.24 |
November | 0.174195E+09 | 83975166.54 | 90220290.42 | 0.313331E+09 | 45238052.11 |
December | 0.167096E+09 | 82540540.50 | 84555830.53 | 0.267159E+09 | 80872903.86 |
Annual Sum or Average | 0.150603E+10 | 0.450982E+09 | 0.105505E+10 | 0.317454E+10 | 0.434866E+09 |
Minimum of Months | 78863524.57 | 97596.59 | 78765927.99 | 0.203616E+09 | 53196.19 |
Maximum of Months | 0.174195E+09 | 83975166.54 | 98296522.40 | 0.340247E+09 | 95401619.44 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168140E+09 | 79050247.79 | 89089825.42 | 0.255445E+09 | 95401619.44 |
February | 0.142611E+09 | 58334110.25 | 84276813.20 | 0.228507E+09 | 73396816.10 |
March | 0.129951E+09 | 35281028.83 | 94670103.70 | 0.230161E+09 | 62919411.91 |
April | 98856132.43 | 10480621.16 | 88375511.27 | 0.203616E+09 | 38639819.62 |
May | 86531017.69 | 1325136.47 | 85205881.22 | 0.226747E+09 | 10829014.94 |
June | 78863524.57 | 97596.59 | 78765927.99 | 0.227332E+09 | 2955057.53 |
July | 81490104.20 | 692417.37 | 80797686.83 | 0.271765E+09 | 173600.73 |
August | 94522041.84 | 6697269.10 | 87824772.74 | 0.304944E+09 | 53196.19 |
September | 0.120608E+09 | 27640881.62 | 92967288.71 | 0.305282E+09 | 4969862.19 |
October | 0.163163E+09 | 64866492.43 | 98296522.40 | 0.340247E+09 | 19416503.24 |
November | 0.174195E+09 | 83975166.54 | 90220290.42 | 0.313331E+09 | 45238052.11 |
December | 0.167096E+09 | 82540540.50 | 84555830.53 | 0.267159E+09 | 80872903.86 |
Annual Sum or Average | 0.150603E+10 | 0.450982E+09 | 0.105505E+10 | 0.317454E+10 | 0.434866E+09 |
Minimum of Months | 78863524.57 | 97596.59 | 78765927.99 | 0.203616E+09 | 53196.19 |
Maximum of Months | 0.174195E+09 | 83975166.54 | 98296522.40 | 0.340247E+09 | 95401619.44 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168140E+09 | 79050247.79 | 89089825.42 | 0.255445E+09 | 95401619.44 |
February | 0.142611E+09 | 58334110.25 | 84276813.20 | 0.228507E+09 | 73396816.10 |
March | 0.129951E+09 | 35281028.83 | 94670103.70 | 0.230161E+09 | 62919411.91 |
April | 98856132.43 | 10480621.16 | 88375511.27 | 0.203616E+09 | 38639819.62 |
May | 86531017.69 | 1325136.47 | 85205881.22 | 0.226747E+09 | 10829014.94 |
June | 78863524.57 | 97596.59 | 78765927.99 | 0.227332E+09 | 2955057.53 |
July | 81490104.20 | 692417.37 | 80797686.83 | 0.271765E+09 | 173600.73 |
August | 94522041.84 | 6697269.10 | 87824772.74 | 0.304944E+09 | 53196.19 |
September | 0.120608E+09 | 27640881.62 | 92967288.71 | 0.305282E+09 | 4969862.19 |
October | 0.163163E+09 | 64866492.43 | 98296522.40 | 0.340247E+09 | 19416503.24 |
November | 0.174195E+09 | 83975166.54 | 90220290.42 | 0.313331E+09 | 45238052.11 |
December | 0.167096E+09 | 82540540.50 | 84555830.53 | 0.267159E+09 | 80872903.86 |
Annual Sum or Average | 0.150603E+10 | 0.450982E+09 | 0.105505E+10 | 0.317454E+10 | 0.434866E+09 |
Minimum of Months | 78863524.57 | 97596.59 | 78765927.99 | 0.203616E+09 | 53196.19 |
Maximum of Months | 0.174195E+09 | 83975166.54 | 98296522.40 | 0.340247E+09 | 95401619.44 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168140E+09 | 79050247.79 | 89089825.42 | 0.255445E+09 | 95401619.44 |
February | 0.142611E+09 | 58334110.25 | 84276813.20 | 0.228507E+09 | 73396816.10 |
March | 0.129951E+09 | 35281028.83 | 94670103.70 | 0.230161E+09 | 62919411.91 |
April | 98856132.43 | 10480621.16 | 88375511.27 | 0.203616E+09 | 38639819.62 |
May | 86531017.69 | 1325136.47 | 85205881.22 | 0.226747E+09 | 10829014.94 |
June | 78863524.57 | 97596.59 | 78765927.99 | 0.227332E+09 | 2955057.53 |
July | 81490104.20 | 692417.37 | 80797686.83 | 0.271765E+09 | 173600.73 |
August | 94522041.84 | 6697269.10 | 87824772.74 | 0.304944E+09 | 53196.19 |
September | 0.120608E+09 | 27640881.62 | 92967288.71 | 0.305282E+09 | 4969862.19 |
October | 0.163163E+09 | 64866492.43 | 98296522.40 | 0.340247E+09 | 19416503.24 |
November | 0.174195E+09 | 83975166.54 | 90220290.42 | 0.313331E+09 | 45238052.11 |
December | 0.167096E+09 | 82540540.50 | 84555830.53 | 0.267159E+09 | 80872903.86 |
Annual Sum or Average | 0.150603E+10 | 0.450982E+09 | 0.105505E+10 | 0.317454E+10 | 0.434866E+09 |
Minimum of Months | 78863524.57 | 97596.59 | 78765927.99 | 0.203616E+09 | 53196.19 |
Maximum of Months | 0.174195E+09 | 83975166.54 | 98296522.40 | 0.340247E+09 | 95401619.44 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201026E+09 | 94511274.99 | 0.106514E+09 | 0.305690E+09 | 0.113078E+09 |
February | 0.170503E+09 | 69743375.75 | 0.100760E+09 | 0.273291E+09 | 87046633.27 |
March | 0.155368E+09 | 42181461.93 | 0.113186E+09 | 0.274770E+09 | 74815009.44 |
April | 0.118191E+09 | 12530471.39 | 0.105660E+09 | 0.242412E+09 | 46123735.89 |
May | 0.103455E+09 | 1584313.03 | 0.101871E+09 | 0.268652E+09 | 13063988.31 |
June | 94288031.54 | 116684.99 | 94171346.55 | 0.268725E+09 | 3674422.90 |
July | 97428330.23 | 827843.68 | 96600486.54 | 0.321351E+09 | 223857.14 |
August | 0.113009E+09 | 8007153.16 | 0.105002E+09 | 0.360875E+09 | 74583.79 |
September | 0.144197E+09 | 33047018.03 | 0.111150E+09 | 0.362435E+09 | 6059998.81 |
October | 0.195075E+09 | 77553392.62 | 0.117522E+09 | 0.405048E+09 | 23382605.30 |
November | 0.208265E+09 | 0.100399E+09 | 0.107866E+09 | 0.373869E+09 | 54012360.18 |
December | 0.199778E+09 | 98684215.90 | 0.101094E+09 | 0.319362E+09 | 95996683.49 |
Annual Sum or Average | 0.180058E+10 | 0.539187E+09 | 0.126140E+10 | 0.377648E+10 | 0.517552E+09 |
Minimum of Months | 94288031.54 | 116684.99 | 94171346.55 | 0.242412E+09 | 74583.79 |
Maximum of Months | 0.208265E+09 | 0.100399E+09 | 0.117522E+09 | 0.405048E+09 | 0.113078E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201026E+09 | 94511274.99 | 0.106514E+09 | 0.305690E+09 | 0.113078E+09 |
February | 0.170503E+09 | 69743375.75 | 0.100760E+09 | 0.273291E+09 | 87046633.27 |
March | 0.155368E+09 | 42181461.93 | 0.113186E+09 | 0.274770E+09 | 74815009.44 |
April | 0.118191E+09 | 12530471.39 | 0.105660E+09 | 0.242412E+09 | 46123735.89 |
May | 0.103455E+09 | 1584313.03 | 0.101871E+09 | 0.268652E+09 | 13063988.31 |
June | 94288031.54 | 116684.99 | 94171346.55 | 0.268725E+09 | 3674422.90 |
July | 97428330.23 | 827843.68 | 96600486.54 | 0.321351E+09 | 223857.14 |
August | 0.113009E+09 | 8007153.16 | 0.105002E+09 | 0.360875E+09 | 74583.79 |
September | 0.144197E+09 | 33047018.03 | 0.111150E+09 | 0.362435E+09 | 6059998.81 |
October | 0.195075E+09 | 77553392.62 | 0.117522E+09 | 0.405048E+09 | 23382605.30 |
November | 0.208265E+09 | 0.100399E+09 | 0.107866E+09 | 0.373869E+09 | 54012360.18 |
December | 0.199778E+09 | 98684215.90 | 0.101094E+09 | 0.319362E+09 | 95996683.49 |
Annual Sum or Average | 0.180058E+10 | 0.539187E+09 | 0.126140E+10 | 0.377648E+10 | 0.517552E+09 |
Minimum of Months | 94288031.54 | 116684.99 | 94171346.55 | 0.242412E+09 | 74583.79 |
Maximum of Months | 0.208265E+09 | 0.100399E+09 | 0.117522E+09 | 0.405048E+09 | 0.113078E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168140E+09 | 79050247.79 | 89089825.42 | 0.254945E+09 | 95130638.48 |
February | 0.142611E+09 | 58334110.25 | 84276813.20 | 0.228174E+09 | 72997717.26 |
March | 0.129951E+09 | 35281028.83 | 94670103.70 | 0.230123E+09 | 62233701.44 |
April | 98856132.43 | 10480621.16 | 88375511.27 | 0.204068E+09 | 37825005.43 |
May | 86531017.69 | 1325136.47 | 85205881.22 | 0.228538E+09 | 10279720.51 |
June | 78863524.57 | 97596.59 | 78765927.99 | 0.229801E+09 | 2610789.70 |
July | 81490104.20 | 692417.37 | 80797686.83 | 0.274762E+09 | 144908.47 |
August | 94522041.84 | 6697269.10 | 87824772.74 | 0.308079E+09 | 31643.44 |
September | 0.120608E+09 | 27640881.62 | 92967288.71 | 0.307227E+09 | 4576321.52 |
October | 0.163163E+09 | 64866492.43 | 98296522.40 | 0.341143E+09 | 18500009.96 |
November | 0.174195E+09 | 83975166.54 | 90220290.42 | 0.313452E+09 | 44323835.21 |
December | 0.167096E+09 | 82540540.50 | 84555830.53 | 0.266853E+09 | 80339921.75 |
Annual Sum or Average | 0.150603E+10 | 0.450982E+09 | 0.105505E+10 | 0.318717E+10 | 0.428994E+09 |
Minimum of Months | 78863524.57 | 97596.59 | 78765927.99 | 0.204068E+09 | 31643.44 |
Maximum of Months | 0.174195E+09 | 83975166.54 | 98296522.40 | 0.341143E+09 | 95130638.48 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168140E+09 | 79050247.79 | 89089825.42 | 0.254945E+09 | 95130638.48 |
February | 0.142611E+09 | 58334110.25 | 84276813.20 | 0.228174E+09 | 72997717.26 |
March | 0.129951E+09 | 35281028.83 | 94670103.70 | 0.230123E+09 | 62233701.44 |
April | 98856132.43 | 10480621.16 | 88375511.27 | 0.204068E+09 | 37825005.43 |
May | 86531017.69 | 1325136.47 | 85205881.22 | 0.228538E+09 | 10279720.51 |
June | 78863524.57 | 97596.59 | 78765927.99 | 0.229801E+09 | 2610789.70 |
July | 81490104.20 | 692417.37 | 80797686.83 | 0.274762E+09 | 144908.47 |
August | 94522041.84 | 6697269.10 | 87824772.74 | 0.308079E+09 | 31643.44 |
September | 0.120608E+09 | 27640881.62 | 92967288.71 | 0.307227E+09 | 4576321.52 |
October | 0.163163E+09 | 64866492.43 | 98296522.40 | 0.341143E+09 | 18500009.96 |
November | 0.174195E+09 | 83975166.54 | 90220290.42 | 0.313452E+09 | 44323835.21 |
December | 0.167096E+09 | 82540540.50 | 84555830.53 | 0.266853E+09 | 80339921.75 |
Annual Sum or Average | 0.150603E+10 | 0.450982E+09 | 0.105505E+10 | 0.318717E+10 | 0.428994E+09 |
Minimum of Months | 78863524.57 | 97596.59 | 78765927.99 | 0.204068E+09 | 31643.44 |
Maximum of Months | 0.174195E+09 | 83975166.54 | 98296522.40 | 0.341143E+09 | 95130638.48 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201026E+09 | 94511274.99 | 0.106514E+09 | 0.305208E+09 | 0.112737E+09 |
February | 0.170503E+09 | 69743375.75 | 0.100760E+09 | 0.272983E+09 | 86562609.09 |
March | 0.155368E+09 | 42181461.93 | 0.113186E+09 | 0.274787E+09 | 74011535.96 |
April | 0.118191E+09 | 12530471.39 | 0.105660E+09 | 0.242958E+09 | 45181456.59 |
May | 0.103455E+09 | 1584313.03 | 0.101871E+09 | 0.270687E+09 | 12429099.93 |
June | 94288031.54 | 116684.99 | 94171346.55 | 0.271506E+09 | 3269114.50 |
July | 97428330.23 | 827843.68 | 96600486.54 | 0.324754E+09 | 188376.31 |
August | 0.113009E+09 | 8007153.16 | 0.105002E+09 | 0.364443E+09 | 46780.07 |
September | 0.144197E+09 | 33047018.03 | 0.111150E+09 | 0.364674E+09 | 5597456.93 |
October | 0.195075E+09 | 77553392.62 | 0.117522E+09 | 0.406125E+09 | 22323488.33 |
November | 0.208265E+09 | 0.100399E+09 | 0.107866E+09 | 0.374075E+09 | 52949136.66 |
December | 0.199778E+09 | 98684215.90 | 0.101094E+09 | 0.319093E+09 | 95360301.64 |
Annual Sum or Average | 0.180058E+10 | 0.539187E+09 | 0.126140E+10 | 0.379129E+10 | 0.510656E+09 |
Minimum of Months | 94288031.54 | 116684.99 | 94171346.55 | 0.242958E+09 | 46780.07 |
Maximum of Months | 0.208265E+09 | 0.100399E+09 | 0.117522E+09 | 0.406125E+09 | 0.112737E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168140E+09 | 79050247.79 | 89089825.42 | 0.255120E+09 | 94833282.83 |
February | 0.142611E+09 | 58334110.25 | 84276813.20 | 0.228323E+09 | 72728696.97 |
March | 0.129951E+09 | 35281028.83 | 94670103.70 | 0.230278E+09 | 61950047.48 |
April | 98856132.43 | 10480621.16 | 88375511.27 | 0.204216E+09 | 37604791.39 |
May | 86531017.69 | 1325136.47 | 85205881.22 | 0.228738E+09 | 10185705.31 |
June | 78863524.57 | 97596.59 | 78765927.99 | 0.230027E+09 | 2567108.36 |
July | 81490104.20 | 692417.37 | 80797686.83 | 0.274989E+09 | 143443.19 |
August | 94522041.84 | 6697269.10 | 87824772.74 | 0.308297E+09 | 29932.45 |
September | 0.120608E+09 | 27640881.62 | 92967288.71 | 0.307403E+09 | 4534953.20 |
October | 0.163163E+09 | 64866492.43 | 98296522.40 | 0.341270E+09 | 18388575.13 |
November | 0.174195E+09 | 83975166.54 | 90220290.42 | 0.313568E+09 | 44157008.56 |
December | 0.167096E+09 | 82540540.50 | 84555830.53 | 0.266987E+09 | 80098216.02 |
Annual Sum or Average | 0.150603E+10 | 0.450982E+09 | 0.105505E+10 | 0.318922E+10 | 0.427222E+09 |
Minimum of Months | 78863524.57 | 97596.59 | 78765927.99 | 0.204216E+09 | 29932.45 |
Maximum of Months | 0.174195E+09 | 83975166.54 | 98296522.40 | 0.341270E+09 | 94833282.83 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168140E+09 | 79050247.79 | 89089825.42 | 0.255120E+09 | 94833282.83 |
February | 0.142611E+09 | 58334110.25 | 84276813.20 | 0.228323E+09 | 72728696.97 |
March | 0.129951E+09 | 35281028.83 | 94670103.70 | 0.230278E+09 | 61950047.48 |
April | 98856132.43 | 10480621.16 | 88375511.27 | 0.204216E+09 | 37604791.39 |
May | 86531017.69 | 1325136.47 | 85205881.22 | 0.228738E+09 | 10185705.31 |
June | 78863524.57 | 97596.59 | 78765927.99 | 0.230027E+09 | 2567108.36 |
July | 81490104.20 | 692417.37 | 80797686.83 | 0.274989E+09 | 143443.19 |
August | 94522041.84 | 6697269.10 | 87824772.74 | 0.308297E+09 | 29932.45 |
September | 0.120608E+09 | 27640881.62 | 92967288.71 | 0.307403E+09 | 4534953.20 |
October | 0.163163E+09 | 64866492.43 | 98296522.40 | 0.341270E+09 | 18388575.13 |
November | 0.174195E+09 | 83975166.54 | 90220290.42 | 0.313568E+09 | 44157008.56 |
December | 0.167096E+09 | 82540540.50 | 84555830.53 | 0.266987E+09 | 80098216.02 |
Annual Sum or Average | 0.150603E+10 | 0.450982E+09 | 0.105505E+10 | 0.318922E+10 | 0.427222E+09 |
Minimum of Months | 78863524.57 | 97596.59 | 78765927.99 | 0.204216E+09 | 29932.45 |
Maximum of Months | 0.174195E+09 | 83975166.54 | 98296522.40 | 0.341270E+09 | 94833282.83 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201026E+09 | 94511274.99 | 0.106514E+09 | 0.305418E+09 | 0.112387E+09 |
February | 0.170503E+09 | 69743375.75 | 0.100760E+09 | 0.273161E+09 | 86245223.72 |
March | 0.155368E+09 | 42181461.93 | 0.113186E+09 | 0.274973E+09 | 73676682.50 |
April | 0.118191E+09 | 12530471.39 | 0.105660E+09 | 0.243134E+09 | 44920855.45 |
May | 0.103455E+09 | 1584313.03 | 0.101871E+09 | 0.270925E+09 | 12317126.79 |
June | 94288031.54 | 116684.99 | 94171346.55 | 0.271774E+09 | 3215925.63 |
July | 97428330.23 | 827843.68 | 96600486.54 | 0.325024E+09 | 186462.58 |
August | 0.113009E+09 | 8007153.16 | 0.105002E+09 | 0.364703E+09 | 44659.16 |
September | 0.144197E+09 | 33047018.03 | 0.111150E+09 | 0.364882E+09 | 5546447.55 |
October | 0.195075E+09 | 77553392.62 | 0.117522E+09 | 0.406276E+09 | 22190201.13 |
November | 0.208265E+09 | 0.100399E+09 | 0.107866E+09 | 0.374213E+09 | 52751506.28 |
December | 0.199778E+09 | 98684215.90 | 0.101094E+09 | 0.319253E+09 | 95074342.38 |
Annual Sum or Average | 0.180058E+10 | 0.539187E+09 | 0.126140E+10 | 0.379374E+10 | 0.508556E+09 |
Minimum of Months | 94288031.54 | 116684.99 | 94171346.55 | 0.243134E+09 | 44659.16 |
Maximum of Months | 0.208265E+09 | 0.100399E+09 | 0.117522E+09 | 0.406276E+09 | 0.112387E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168140E+09 | 79050247.79 | 89089825.42 | 0.255505E+09 | 94067082.28 |
February | 0.142611E+09 | 58334110.25 | 84276813.20 | 0.228621E+09 | 72055379.03 |
March | 0.129951E+09 | 35281028.83 | 94670103.70 | 0.230507E+09 | 61324463.71 |
April | 98856132.43 | 10480621.16 | 88375511.27 | 0.204281E+09 | 37314119.05 |
May | 86531017.69 | 1325136.47 | 85205881.22 | 0.228380E+09 | 10247287.79 |
June | 78863524.57 | 97596.59 | 78765927.99 | 0.229413E+09 | 2662787.21 |
July | 81490104.20 | 692417.37 | 80797686.83 | 0.273874E+09 | 163251.59 |
August | 94522041.84 | 6697269.10 | 87824772.74 | 0.306991E+09 | 42029.78 |
September | 0.120608E+09 | 27640881.62 | 92967288.71 | 0.306566E+09 | 4718615.50 |
October | 0.163163E+09 | 64866492.43 | 98296522.40 | 0.340852E+09 | 18738669.96 |
November | 0.174195E+09 | 83975166.54 | 90220290.42 | 0.313465E+09 | 44231191.18 |
December | 0.167096E+09 | 82540540.50 | 84555830.53 | 0.267169E+09 | 79680767.19 |
Annual Sum or Average | 0.150603E+10 | 0.450982E+09 | 0.105505E+10 | 0.318562E+10 | 0.425246E+09 |
Minimum of Months | 78863524.57 | 97596.59 | 78765927.99 | 0.204281E+09 | 42029.78 |
Maximum of Months | 0.174195E+09 | 83975166.54 | 98296522.40 | 0.340852E+09 | 94067082.28 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168140E+09 | 79050247.79 | 89089825.42 | 0.255505E+09 | 94067082.28 |
February | 0.142611E+09 | 58334110.25 | 84276813.20 | 0.228621E+09 | 72055379.03 |
March | 0.129951E+09 | 35281028.83 | 94670103.70 | 0.230507E+09 | 61324463.71 |
April | 98856132.43 | 10480621.16 | 88375511.27 | 0.204281E+09 | 37314119.05 |
May | 86531017.69 | 1325136.47 | 85205881.22 | 0.228380E+09 | 10247287.79 |
June | 78863524.57 | 97596.59 | 78765927.99 | 0.229413E+09 | 2662787.21 |
July | 81490104.20 | 692417.37 | 80797686.83 | 0.273874E+09 | 163251.59 |
August | 94522041.84 | 6697269.10 | 87824772.74 | 0.306991E+09 | 42029.78 |
September | 0.120608E+09 | 27640881.62 | 92967288.71 | 0.306566E+09 | 4718615.50 |
October | 0.163163E+09 | 64866492.43 | 98296522.40 | 0.340852E+09 | 18738669.96 |
November | 0.174195E+09 | 83975166.54 | 90220290.42 | 0.313465E+09 | 44231191.18 |
December | 0.167096E+09 | 82540540.50 | 84555830.53 | 0.267169E+09 | 79680767.19 |
Annual Sum or Average | 0.150603E+10 | 0.450982E+09 | 0.105505E+10 | 0.318562E+10 | 0.425246E+09 |
Minimum of Months | 78863524.57 | 97596.59 | 78765927.99 | 0.204281E+09 | 42029.78 |
Maximum of Months | 0.174195E+09 | 83975166.54 | 98296522.40 | 0.340852E+09 | 94067082.28 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201026E+09 | 94511274.99 | 0.106514E+09 | 0.305877E+09 | 0.111491E+09 |
February | 0.170503E+09 | 69743375.75 | 0.100760E+09 | 0.273518E+09 | 85457346.60 |
March | 0.155368E+09 | 42181461.93 | 0.113186E+09 | 0.275247E+09 | 72946152.51 |
April | 0.118191E+09 | 12530471.39 | 0.105660E+09 | 0.243210E+09 | 44585150.59 |
May | 0.103455E+09 | 1584313.03 | 0.101871E+09 | 0.270495E+09 | 12395409.07 |
June | 94288031.54 | 116684.99 | 94171346.55 | 0.271041E+09 | 3334776.18 |
July | 97428330.23 | 827843.68 | 96600486.54 | 0.323691E+09 | 211414.38 |
August | 0.113009E+09 | 8007153.16 | 0.105002E+09 | 0.363144E+09 | 60663.22 |
September | 0.144197E+09 | 33047018.03 | 0.111150E+09 | 0.363887E+09 | 5773070.88 |
October | 0.195075E+09 | 77553392.62 | 0.117522E+09 | 0.405777E+09 | 22612625.68 |
November | 0.208265E+09 | 0.100399E+09 | 0.107866E+09 | 0.374088E+09 | 52847426.47 |
December | 0.199778E+09 | 98684215.90 | 0.101094E+09 | 0.319470E+09 | 94589036.04 |
Annual Sum or Average | 0.180058E+10 | 0.539187E+09 | 0.126140E+10 | 0.378944E+10 | 0.506304E+09 |
Minimum of Months | 94288031.54 | 116684.99 | 94171346.55 | 0.243210E+09 | 60663.22 |
Maximum of Months | 0.208265E+09 | 0.100399E+09 | 0.117522E+09 | 0.405777E+09 | 0.111491E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168140E+09 | 79050247.79 | 89089825.42 | 0.255748E+09 | 91789768.42 |
February | 0.142611E+09 | 58334110.25 | 84276813.20 | 0.228733E+09 | 69842921.41 |
March | 0.129951E+09 | 35281028.83 | 94670103.70 | 0.230176E+09 | 59380404.71 |
April | 98856132.43 | 10480621.16 | 88375511.27 | 0.202892E+09 | 36836659.50 |
May | 86531017.69 | 1325136.47 | 85205881.22 | 0.223973E+09 | 10959646.47 |
June | 78863524.57 | 97596.59 | 78765927.99 | 0.223478E+09 | 3354091.46 |
July | 81490104.20 | 692417.37 | 80797686.83 | 0.264892E+09 | 320842.19 |
August | 94522041.84 | 6697269.10 | 87824772.74 | 0.296785E+09 | 154943.31 |
September | 0.120608E+09 | 27640881.62 | 92967288.71 | 0.299718E+09 | 6118717.54 |
October | 0.163163E+09 | 64866492.43 | 98296522.40 | 0.336651E+09 | 21408216.05 |
November | 0.174195E+09 | 83975166.54 | 90220290.42 | 0.311364E+09 | 45818683.43 |
December | 0.167096E+09 | 82540540.50 | 84555830.53 | 0.266778E+09 | 78907547.17 |
Annual Sum or Average | 0.150603E+10 | 0.450982E+09 | 0.105505E+10 | 0.314119E+10 | 0.424892E+09 |
Minimum of Months | 78863524.57 | 97596.59 | 78765927.99 | 0.202892E+09 | 154943.31 |
Maximum of Months | 0.174195E+09 | 83975166.54 | 98296522.40 | 0.336651E+09 | 91789768.42 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168140E+09 | 79050247.79 | 89089825.42 | 0.255748E+09 | 91789768.42 |
February | 0.142611E+09 | 58334110.25 | 84276813.20 | 0.228733E+09 | 69842921.41 |
March | 0.129951E+09 | 35281028.83 | 94670103.70 | 0.230176E+09 | 59380404.71 |
April | 98856132.43 | 10480621.16 | 88375511.27 | 0.202892E+09 | 36836659.50 |
May | 86531017.69 | 1325136.47 | 85205881.22 | 0.223973E+09 | 10959646.47 |
June | 78863524.57 | 97596.59 | 78765927.99 | 0.223478E+09 | 3354091.46 |
July | 81490104.20 | 692417.37 | 80797686.83 | 0.264892E+09 | 320842.19 |
August | 94522041.84 | 6697269.10 | 87824772.74 | 0.296785E+09 | 154943.31 |
September | 0.120608E+09 | 27640881.62 | 92967288.71 | 0.299718E+09 | 6118717.54 |
October | 0.163163E+09 | 64866492.43 | 98296522.40 | 0.336651E+09 | 21408216.05 |
November | 0.174195E+09 | 83975166.54 | 90220290.42 | 0.311364E+09 | 45818683.43 |
December | 0.167096E+09 | 82540540.50 | 84555830.53 | 0.266778E+09 | 78907547.17 |
Annual Sum or Average | 0.150603E+10 | 0.450982E+09 | 0.105505E+10 | 0.314119E+10 | 0.424892E+09 |
Minimum of Months | 78863524.57 | 97596.59 | 78765927.99 | 0.202892E+09 | 154943.31 |
Maximum of Months | 0.174195E+09 | 83975166.54 | 98296522.40 | 0.336651E+09 | 91789768.42 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201026E+09 | 94511274.99 | 0.106514E+09 | 0.306155E+09 | 0.108820E+09 |
February | 0.170503E+09 | 69743375.75 | 0.100760E+09 | 0.273645E+09 | 82868588.28 |
March | 0.155368E+09 | 42181461.93 | 0.113186E+09 | 0.274843E+09 | 70663718.17 |
April | 0.118191E+09 | 12530471.39 | 0.105660E+09 | 0.241542E+09 | 44032267.70 |
May | 0.103455E+09 | 1584313.03 | 0.101871E+09 | 0.265235E+09 | 13251783.40 |
June | 94288031.54 | 116684.99 | 94171346.55 | 0.263994E+09 | 4183569.95 |
July | 97428330.23 | 827843.68 | 96600486.54 | 0.313017E+09 | 413002.87 |
August | 0.113009E+09 | 8007153.16 | 0.105002E+09 | 0.351010E+09 | 206737.80 |
September | 0.144197E+09 | 33047018.03 | 0.111150E+09 | 0.355768E+09 | 7482791.59 |
October | 0.195075E+09 | 77553392.62 | 0.117522E+09 | 0.400756E+09 | 25787517.21 |
November | 0.208265E+09 | 0.100399E+09 | 0.107866E+09 | 0.371577E+09 | 54746385.60 |
December | 0.199778E+09 | 98684215.90 | 0.101094E+09 | 0.318990E+09 | 93687928.26 |
Annual Sum or Average | 0.180058E+10 | 0.539187E+09 | 0.126140E+10 | 0.373653E+10 | 0.506144E+09 |
Minimum of Months | 94288031.54 | 116684.99 | 94171346.55 | 0.241542E+09 | 206737.80 |
Maximum of Months | 0.208265E+09 | 0.100399E+09 | 0.117522E+09 | 0.400756E+09 | 0.108820E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 608.90 | 227.91 | 402.04 | 189.02 | 213.02 | 0.00 | 0.00 |
February | 603.95 | 191.80 | 377.53 | 154.43 | 223.10 | 0.00 | 0.00 |
March | 549.67 | 146.70 | 310.73 | 84.36 | 226.37 | 0.00 | 0.00 |
April | 505.70 | 88.81 | 244.25 | 25.90 | 218.36 | 0.00 | 0.00 |
May | 555.09 | 22.22 | 206.90 | 3.17 | 203.74 | 0.00 | 0.00 |
June | 576.72 | 6.06 | 194.86 | 0.24 | 194.61 | 0.00 | 0.00 |
July | 672.87 | 0.16 | 194.85 | 1.66 | 193.19 | 0.00 | 0.00 |
August | 747.49 | 0.11 | 226.01 | 16.01 | 210.00 | 0.00 | 0.00 |
September | 771.52 | 10.84 | 298.00 | 68.30 | 229.70 | 0.00 | 0.00 |
October | 822.66 | 39.74 | 390.14 | 155.10 | 235.04 | 0.00 | 0.00 |
November | 774.68 | 104.19 | 430.40 | 207.49 | 222.92 | 0.00 | 0.00 |
December | 637.63 | 189.70 | 399.54 | 197.36 | 202.18 | 0.00 | 0.00 |
Annual Sum or Average | 652.58 | 85.18 | 305.84 | 91.58 | 214.26 | 0.00 | 0.00 |
Minimum of Months | 505.70 | 0.11 | 194.85 | 0.24 | 193.19 | 0.00 | 0.00 |
Maximum of Months | 822.66 | 227.91 | 430.40 | 207.49 | 235.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 303.21 | 115.26 | 201.02 | 94.51 | 106.51 | 0.00 | 0.00 |
February | 301.02 | 97.14 | 188.77 | 77.21 | 111.55 | 0.00 | 0.00 |
March | 274.52 | 74.24 | 155.36 | 42.18 | 113.18 | 0.00 | 0.00 |
April | 253.50 | 44.82 | 122.13 | 12.95 | 109.18 | 0.00 | 0.00 |
May | 280.46 | 10.95 | 103.45 | 1.58 | 101.87 | 0.00 | 0.00 |
June | 292.68 | 2.75 | 97.43 | 0.12 | 97.31 | 0.00 | 0.00 |
July | 342.11 | 0.06 | 97.43 | 0.83 | 96.60 | 0.00 | 0.00 |
August | 380.29 | 0.03 | 113.01 | 8.01 | 105.00 | 0.00 | 0.00 |
September | 390.24 | 4.92 | 149.00 | 34.15 | 114.85 | 0.00 | 0.00 |
October | 413.95 | 18.93 | 195.07 | 77.55 | 117.52 | 0.00 | 0.00 |
November | 388.16 | 51.29 | 215.20 | 103.74 | 111.46 | 0.00 | 0.00 |
December | 318.23 | 95.24 | 199.77 | 98.68 | 101.09 | 0.00 | 0.00 |
Annual Sum or Average | 328.39 | 42.71 | 152.92 | 45.79 | 107.13 | 0.00 | 0.00 |
Minimum of Months | 253.50 | 0.03 | 97.43 | 0.12 | 96.60 | 0.00 | 0.00 |
Maximum of Months | 413.95 | 115.26 | 215.20 | 103.74 | 117.52 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 302.99 | 117.75 | 200.61 | 94.31 | 106.29 | 0.00 | 0.00 |
February | 300.54 | 100.49 | 188.38 | 77.06 | 111.32 | 0.00 | 0.00 |
March | 273.48 | 78.47 | 155.04 | 42.09 | 112.95 | 0.00 | 0.00 |
April | 250.57 | 50.26 | 121.88 | 12.92 | 108.96 | 0.00 | 0.00 |
May | 270.04 | 13.63 | 103.24 | 1.58 | 101.66 | 0.00 | 0.00 |
June | 279.69 | 3.97 | 97.23 | 0.12 | 97.11 | 0.00 | 0.00 |
July | 324.88 | 0.19 | 97.23 | 0.83 | 96.40 | 0.00 | 0.00 |
August | 363.81 | 0.08 | 112.77 | 7.99 | 104.78 | 0.00 | 0.00 |
September | 376.50 | 6.45 | 148.69 | 34.08 | 114.62 | 0.00 | 0.00 |
October | 405.93 | 24.09 | 194.67 | 77.39 | 117.28 | 0.00 | 0.00 |
November | 386.32 | 58.11 | 214.76 | 103.53 | 111.23 | 0.00 | 0.00 |
December | 317.77 | 99.65 | 199.36 | 98.48 | 100.88 | 0.00 | 0.00 |
Annual Sum or Average | 321.19 | 45.83 | 152.61 | 45.70 | 106.91 | 0.00 | 0.00 |
Minimum of Months | 250.57 | 0.08 | 97.23 | 0.12 | 96.40 | 0.00 | 0.00 |
Maximum of Months | 405.93 | 117.75 | 214.76 | 103.53 | 117.28 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 303.25 | 117.09 | 200.61 | 94.31 | 106.29 | 0.00 | 0.00 |
February | 300.68 | 100.11 | 188.38 | 77.06 | 111.32 | 0.00 | 0.00 |
March | 273.52 | 78.40 | 155.04 | 42.09 | 112.95 | 0.00 | 0.00 |
April | 250.46 | 50.71 | 121.88 | 12.92 | 108.96 | 0.00 | 0.00 |
May | 269.17 | 14.27 | 103.24 | 1.58 | 101.66 | 0.00 | 0.00 |
June | 278.40 | 4.40 | 97.23 | 0.12 | 97.11 | 0.00 | 0.00 |
July | 322.74 | 0.26 | 97.23 | 0.83 | 96.40 | 0.00 | 0.00 |
August | 361.72 | 0.11 | 112.77 | 7.99 | 104.78 | 0.00 | 0.00 |
September | 375.13 | 6.96 | 148.69 | 34.08 | 114.62 | 0.00 | 0.00 |
October | 405.41 | 25.13 | 194.67 | 77.39 | 117.28 | 0.00 | 0.00 |
November | 386.17 | 58.64 | 214.76 | 103.53 | 111.23 | 0.00 | 0.00 |
December | 317.85 | 99.47 | 199.36 | 98.48 | 100.88 | 0.00 | 0.00 |
Annual Sum or Average | 320.51 | 46.03 | 152.61 | 45.70 | 106.91 | 0.00 | 0.00 |
Minimum of Months | 250.46 | 0.11 | 97.23 | 0.12 | 96.40 | 0.00 | 0.00 |
Maximum of Months | 405.41 | 117.09 | 214.76 | 103.53 | 117.28 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 303.70 | 115.99 | 200.61 | 94.31 | 106.29 | 0.00 | 0.00 |
February | 301.03 | 99.11 | 188.38 | 77.06 | 111.32 | 0.00 | 0.00 |
March | 273.84 | 77.42 | 155.04 | 42.09 | 112.95 | 0.00 | 0.00 |
April | 250.74 | 49.86 | 121.88 | 12.92 | 108.96 | 0.00 | 0.00 |
May | 269.62 | 13.89 | 103.24 | 1.58 | 101.66 | 0.00 | 0.00 |
June | 278.99 | 4.19 | 97.23 | 0.12 | 97.11 | 0.00 | 0.00 |
July | 323.32 | 0.24 | 97.23 | 0.83 | 96.40 | 0.00 | 0.00 |
August | 362.36 | 0.09 | 112.77 | 7.99 | 104.78 | 0.00 | 0.00 |
September | 375.55 | 6.72 | 148.69 | 34.08 | 114.62 | 0.00 | 0.00 |
October | 405.64 | 24.59 | 194.67 | 77.39 | 117.28 | 0.00 | 0.00 |
November | 386.41 | 57.90 | 214.76 | 103.53 | 111.23 | 0.00 | 0.00 |
December | 318.16 | 98.56 | 199.36 | 98.48 | 100.88 | 0.00 | 0.00 |
Annual Sum or Average | 320.92 | 45.45 | 152.61 | 45.70 | 106.91 | 0.00 | 0.00 |
Minimum of Months | 250.74 | 0.09 | 97.23 | 0.12 | 96.40 | 0.00 | 0.00 |
Maximum of Months | 405.64 | 115.99 | 214.76 | 103.53 | 117.28 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 609.75 | 226.91 | 401.21 | 188.63 | 212.59 | 0.00 | 0.00 |
February | 603.76 | 193.32 | 376.76 | 154.11 | 222.65 | 0.00 | 0.00 |
March | 548.90 | 149.83 | 310.09 | 84.19 | 225.90 | 0.00 | 0.00 |
April | 501.27 | 95.22 | 243.75 | 25.84 | 217.91 | 0.00 | 0.00 |
May | 539.24 | 25.93 | 206.48 | 3.16 | 203.32 | 0.00 | 0.00 |
June | 558.17 | 7.39 | 194.46 | 0.24 | 194.22 | 0.00 | 0.00 |
July | 645.82 | 0.43 | 194.45 | 1.65 | 192.80 | 0.00 | 0.00 |
August | 724.88 | 0.13 | 225.55 | 15.98 | 209.57 | 0.00 | 0.00 |
September | 750.77 | 12.34 | 297.39 | 68.15 | 229.23 | 0.00 | 0.00 |
October | 810.59 | 46.46 | 389.34 | 154.78 | 234.55 | 0.00 | 0.00 |
November | 772.01 | 111.49 | 429.52 | 207.06 | 222.46 | 0.00 | 0.00 |
December | 637.46 | 192.46 | 398.72 | 196.96 | 201.77 | 0.00 | 0.00 |
Annual Sum or Average | 642.16 | 87.98 | 305.22 | 91.40 | 213.82 | 0.00 | 0.00 |
Minimum of Months | 501.27 | 0.13 | 194.45 | 0.24 | 192.80 | 0.00 | 0.00 |
Maximum of Months | 810.59 | 226.91 | 429.52 | 207.06 | 234.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 304.32 | 113.13 | 200.61 | 94.31 | 106.29 | 0.00 | 0.00 |
February | 301.48 | 96.13 | 188.38 | 77.06 | 111.32 | 0.00 | 0.00 |
March | 274.43 | 74.10 | 155.04 | 42.09 | 112.95 | 0.00 | 0.00 |
April | 251.19 | 46.62 | 121.88 | 12.92 | 108.96 | 0.00 | 0.00 |
May | 271.72 | 12.32 | 103.24 | 1.58 | 101.66 | 0.00 | 0.00 |
June | 282.06 | 3.27 | 97.23 | 0.12 | 97.11 | 0.00 | 0.00 |
July | 326.42 | 0.18 | 97.23 | 0.83 | 96.40 | 0.00 | 0.00 |
August | 366.11 | 0.04 | 112.77 | 7.99 | 104.78 | 0.00 | 0.00 |
September | 377.75 | 5.69 | 148.69 | 34.08 | 114.62 | 0.00 | 0.00 |
October | 406.37 | 22.15 | 194.67 | 77.39 | 117.28 | 0.00 | 0.00 |
November | 386.18 | 54.63 | 214.76 | 103.53 | 111.23 | 0.00 | 0.00 |
December | 318.40 | 95.59 | 199.36 | 98.48 | 100.88 | 0.00 | 0.00 |
Annual Sum or Average | 322.35 | 43.40 | 152.61 | 45.70 | 106.91 | 0.00 | 0.00 |
Minimum of Months | 251.19 | 0.04 | 97.23 | 0.12 | 96.40 | 0.00 | 0.00 |
Maximum of Months | 406.37 | 113.13 | 214.76 | 103.53 | 117.28 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 304.53 | 112.77 | 200.61 | 94.31 | 106.29 | 0.00 | 0.00 |
February | 301.67 | 95.78 | 188.38 | 77.06 | 111.32 | 0.00 | 0.00 |
March | 274.61 | 73.77 | 155.04 | 42.09 | 112.95 | 0.00 | 0.00 |
April | 251.38 | 46.35 | 121.88 | 12.92 | 108.96 | 0.00 | 0.00 |
May | 271.95 | 12.20 | 103.24 | 1.58 | 101.66 | 0.00 | 0.00 |
June | 282.34 | 3.22 | 97.23 | 0.12 | 97.11 | 0.00 | 0.00 |
July | 326.69 | 0.18 | 97.23 | 0.83 | 96.40 | 0.00 | 0.00 |
August | 366.37 | 0.04 | 112.77 | 7.99 | 104.78 | 0.00 | 0.00 |
September | 377.97 | 5.64 | 148.69 | 34.08 | 114.62 | 0.00 | 0.00 |
October | 406.52 | 22.02 | 194.67 | 77.39 | 117.28 | 0.00 | 0.00 |
November | 386.32 | 54.42 | 214.76 | 103.53 | 111.23 | 0.00 | 0.00 |
December | 318.56 | 95.31 | 199.36 | 98.48 | 100.88 | 0.00 | 0.00 |
Annual Sum or Average | 322.56 | 43.22 | 152.61 | 45.70 | 106.91 | 0.00 | 0.00 |
Minimum of Months | 251.38 | 0.04 | 97.23 | 0.12 | 96.40 | 0.00 | 0.00 |
Maximum of Months | 406.52 | 112.77 | 214.76 | 103.53 | 117.28 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 304.99 | 111.87 | 200.61 | 94.31 | 106.29 | 0.00 | 0.00 |
February | 302.07 | 94.89 | 188.38 | 77.06 | 111.32 | 0.00 | 0.00 |
March | 274.89 | 73.03 | 155.04 | 42.09 | 112.95 | 0.00 | 0.00 |
April | 251.45 | 45.99 | 121.88 | 12.92 | 108.96 | 0.00 | 0.00 |
May | 271.53 | 12.28 | 103.24 | 1.58 | 101.66 | 0.00 | 0.00 |
June | 281.58 | 3.34 | 97.23 | 0.12 | 97.11 | 0.00 | 0.00 |
July | 325.36 | 0.20 | 97.23 | 0.83 | 96.40 | 0.00 | 0.00 |
August | 364.82 | 0.05 | 112.77 | 7.99 | 104.78 | 0.00 | 0.00 |
September | 376.94 | 5.87 | 148.69 | 34.08 | 114.62 | 0.00 | 0.00 |
October | 406.02 | 22.43 | 194.67 | 77.39 | 117.28 | 0.00 | 0.00 |
November | 386.19 | 54.52 | 214.76 | 103.53 | 111.23 | 0.00 | 0.00 |
December | 318.78 | 94.81 | 199.36 | 98.48 | 100.88 | 0.00 | 0.00 |
Annual Sum or Average | 322.19 | 43.02 | 152.61 | 45.70 | 106.91 | 0.00 | 0.00 |
Minimum of Months | 251.45 | 0.05 | 97.23 | 0.12 | 96.40 | 0.00 | 0.00 |
Maximum of Months | 406.02 | 111.87 | 214.76 | 103.53 | 117.28 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 305.28 | 109.17 | 200.61 | 94.31 | 106.29 | 0.00 | 0.00 |
February | 302.21 | 91.99 | 188.38 | 77.06 | 111.32 | 0.00 | 0.00 |
March | 274.49 | 70.72 | 155.04 | 42.09 | 112.95 | 0.00 | 0.00 |
April | 249.74 | 45.41 | 121.88 | 12.92 | 108.96 | 0.00 | 0.00 |
May | 266.27 | 13.13 | 103.24 | 1.58 | 101.66 | 0.00 | 0.00 |
June | 274.28 | 4.20 | 97.23 | 0.12 | 97.11 | 0.00 | 0.00 |
July | 314.67 | 0.39 | 97.23 | 0.83 | 96.40 | 0.00 | 0.00 |
August | 352.67 | 0.19 | 112.77 | 7.99 | 104.78 | 0.00 | 0.00 |
September | 368.52 | 7.61 | 148.69 | 34.08 | 114.62 | 0.00 | 0.00 |
October | 401.01 | 25.61 | 194.67 | 77.39 | 117.28 | 0.00 | 0.00 |
November | 383.60 | 56.47 | 214.76 | 103.53 | 111.23 | 0.00 | 0.00 |
December | 318.30 | 93.90 | 199.36 | 98.48 | 100.88 | 0.00 | 0.00 |
Annual Sum or Average | 317.70 | 43.00 | 152.61 | 45.70 | 106.91 | 0.00 | 0.00 |
Minimum of Months | 249.74 | 0.19 | 97.23 | 0.12 | 96.40 | 0.00 | 0.00 |
Maximum of Months | 401.01 | 109.17 | 214.76 | 103.53 | 117.28 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.163088E+10 | 0.610446E+09 | 0.107682E+10 | 0.506262E+09 | 0.570559E+09 | 0.00 | 0.00 |
February | 0.146108E+10 | 0.464006E+09 | 0.913324E+09 | 0.373590E+09 | 0.539735E+09 | 0.00 | 0.00 |
March | 0.147224E+10 | 0.392929E+09 | 0.832247E+09 | 0.225951E+09 | 0.606296E+09 | 0.00 | 0.00 |
April | 0.131076E+10 | 0.230204E+09 | 0.633105E+09 | 67121124.92 | 0.565984E+09 | 0.00 | 0.00 |
May | 0.148674E+10 | 59515665.84 | 0.554171E+09 | 8486581.97 | 0.545685E+09 | 0.00 | 0.00 |
June | 0.149485E+10 | 15717211.21 | 0.505066E+09 | 625038.59 | 0.504441E+09 | 0.00 | 0.00 |
July | 0.180223E+10 | 426600.48 | 0.521888E+09 | 4434454.02 | 0.517453E+09 | 0.00 | 0.00 |
August | 0.200207E+10 | 301025.73 | 0.605348E+09 | 42891373.39 | 0.562457E+09 | 0.00 | 0.00 |
September | 0.199979E+10 | 28091371.72 | 0.772412E+09 | 0.177021E+09 | 0.595391E+09 | 0.00 | 0.00 |
October | 0.220342E+10 | 0.106436E+09 | 0.104495E+10 | 0.415425E+09 | 0.629521E+09 | 0.00 | 0.00 |
November | 0.200797E+10 | 0.270069E+09 | 0.111560E+10 | 0.537803E+09 | 0.577799E+09 | 0.00 | 0.00 |
December | 0.170783E+10 | 0.508089E+09 | 0.107014E+10 | 0.528615E+09 | 0.541522E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.205799E+11 | 0.268623E+10 | 0.964507E+10 | 0.288822E+10 | 0.675684E+10 | 0.00 | 0.00 |
Minimum of Months | 0.131076E+10 | 301025.73 | 0.505066E+09 | 625038.59 | 0.504441E+09 | 0.00 | 0.00 |
Maximum of Months | 0.220342E+10 | 0.610446E+09 | 0.111560E+10 | 0.537803E+09 | 0.629521E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.812116E+09 | 0.308720E+09 | 0.538410E+09 | 0.253131E+09 | 0.285279E+09 | 0.00 | 0.00 |
February | 0.728225E+09 | 0.235006E+09 | 0.456662E+09 | 0.186795E+09 | 0.269867E+09 | 0.00 | 0.00 |
March | 0.735268E+09 | 0.198857E+09 | 0.416124E+09 | 0.112975E+09 | 0.303148E+09 | 0.00 | 0.00 |
April | 0.657074E+09 | 0.116173E+09 | 0.316553E+09 | 33560562.46 | 0.282992E+09 | 0.00 | 0.00 |
May | 0.751187E+09 | 29339900.09 | 0.277086E+09 | 4243290.99 | 0.272842E+09 | 0.00 | 0.00 |
June | 0.758635E+09 | 7115504.84 | 0.252533E+09 | 312519.29 | 0.252221E+09 | 0.00 | 0.00 |
July | 0.916317E+09 | 149078.37 | 0.260944E+09 | 2217227.01 | 0.258727E+09 | 0.00 | 0.00 |
August | 0.101857E+10 | 79291.99 | 0.302674E+09 | 21445686.70 | 0.281228E+09 | 0.00 | 0.00 |
September | 0.101151E+10 | 12748981.32 | 0.386206E+09 | 88510358.30 | 0.297696E+09 | 0.00 | 0.00 |
October | 0.110873E+10 | 50710180.95 | 0.522473E+09 | 0.207712E+09 | 0.314761E+09 | 0.00 | 0.00 |
November | 0.100610E+10 | 0.132952E+09 | 0.557801E+09 | 0.268901E+09 | 0.288899E+09 | 0.00 | 0.00 |
December | 0.852341E+09 | 0.255085E+09 | 0.535068E+09 | 0.264308E+09 | 0.270761E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.103561E+11 | 0.134694E+10 | 0.482253E+10 | 0.144411E+10 | 0.337842E+10 | 0.00 | 0.00 |
Minimum of Months | 0.657074E+09 | 79291.99 | 0.252533E+09 | 312519.29 | 0.252221E+09 | 0.00 | 0.00 |
Maximum of Months | 0.110873E+10 | 0.308720E+09 | 0.557801E+09 | 0.268901E+09 | 0.314761E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.811534E+09 | 0.315373E+09 | 0.537306E+09 | 0.252612E+09 | 0.284694E+09 | 0.00 | 0.00 |
February | 0.727071E+09 | 0.243099E+09 | 0.455725E+09 | 0.186412E+09 | 0.269314E+09 | 0.00 | 0.00 |
March | 0.732476E+09 | 0.210182E+09 | 0.415270E+09 | 0.112744E+09 | 0.302526E+09 | 0.00 | 0.00 |
April | 0.649482E+09 | 0.130282E+09 | 0.315903E+09 | 33491713.71 | 0.282411E+09 | 0.00 | 0.00 |
May | 0.723267E+09 | 36497010.48 | 0.276517E+09 | 4234585.97 | 0.272283E+09 | 0.00 | 0.00 |
June | 0.724964E+09 | 10300027.27 | 0.252015E+09 | 311878.17 | 0.251703E+09 | 0.00 | 0.00 |
July | 0.870171E+09 | 520931.89 | 0.260409E+09 | 2212678.42 | 0.258196E+09 | 0.00 | 0.00 |
August | 0.974436E+09 | 208735.81 | 0.302053E+09 | 21401691.35 | 0.280652E+09 | 0.00 | 0.00 |
September | 0.975877E+09 | 16730316.11 | 0.385414E+09 | 88328781.27 | 0.297085E+09 | 0.00 | 0.00 |
October | 0.108725E+10 | 64529573.55 | 0.521401E+09 | 0.207286E+09 | 0.314115E+09 | 0.00 | 0.00 |
November | 0.100133E+10 | 0.150616E+09 | 0.556656E+09 | 0.268350E+09 | 0.288307E+09 | 0.00 | 0.00 |
December | 0.851107E+09 | 0.266912E+09 | 0.533971E+09 | 0.263765E+09 | 0.270205E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.101290E+11 | 0.144525E+10 | 0.481264E+10 | 0.144115E+10 | 0.337149E+10 | 0.00 | 0.00 |
Minimum of Months | 0.649482E+09 | 208735.81 | 0.252015E+09 | 311878.17 | 0.251703E+09 | 0.00 | 0.00 |
Maximum of Months | 0.108725E+10 | 0.315373E+09 | 0.556656E+09 | 0.268350E+09 | 0.314115E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.812228E+09 | 0.313615E+09 | 0.537306E+09 | 0.252612E+09 | 0.284694E+09 | 0.00 | 0.00 |
February | 0.727410E+09 | 0.242179E+09 | 0.455725E+09 | 0.186412E+09 | 0.269314E+09 | 0.00 | 0.00 |
March | 0.732604E+09 | 0.209990E+09 | 0.415270E+09 | 0.112744E+09 | 0.302526E+09 | 0.00 | 0.00 |
April | 0.649193E+09 | 0.131435E+09 | 0.315903E+09 | 33491713.71 | 0.282411E+09 | 0.00 | 0.00 |
May | 0.720937E+09 | 38230885.85 | 0.276517E+09 | 4234585.97 | 0.272283E+09 | 0.00 | 0.00 |
June | 0.721617E+09 | 11412017.79 | 0.252015E+09 | 311878.17 | 0.251703E+09 | 0.00 | 0.00 |
July | 0.864438E+09 | 693226.01 | 0.260409E+09 | 2212678.42 | 0.258196E+09 | 0.00 | 0.00 |
August | 0.968823E+09 | 286747.67 | 0.302053E+09 | 21401691.35 | 0.280652E+09 | 0.00 | 0.00 |
September | 0.972334E+09 | 18036086.11 | 0.385414E+09 | 88328781.27 | 0.297085E+09 | 0.00 | 0.00 |
October | 0.108586E+10 | 67317408.12 | 0.521401E+09 | 0.207286E+09 | 0.314115E+09 | 0.00 | 0.00 |
November | 0.100094E+10 | 0.151995E+09 | 0.556656E+09 | 0.268350E+09 | 0.288307E+09 | 0.00 | 0.00 |
December | 0.851319E+09 | 0.266413E+09 | 0.533971E+09 | 0.263765E+09 | 0.270205E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.101077E+11 | 0.145160E+10 | 0.481264E+10 | 0.144115E+10 | 0.337149E+10 | 0.00 | 0.00 |
Minimum of Months | 0.649193E+09 | 286747.67 | 0.252015E+09 | 311878.17 | 0.251703E+09 | 0.00 | 0.00 |
Maximum of Months | 0.108586E+10 | 0.313615E+09 | 0.556656E+09 | 0.268350E+09 | 0.314115E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.813439E+09 | 0.310665E+09 | 0.537306E+09 | 0.252612E+09 | 0.284694E+09 | 0.00 | 0.00 |
February | 0.728259E+09 | 0.239772E+09 | 0.455725E+09 | 0.186412E+09 | 0.269314E+09 | 0.00 | 0.00 |
March | 0.733455E+09 | 0.207357E+09 | 0.415270E+09 | 0.112744E+09 | 0.302526E+09 | 0.00 | 0.00 |
April | 0.649913E+09 | 0.129247E+09 | 0.315903E+09 | 33491713.71 | 0.282411E+09 | 0.00 | 0.00 |
May | 0.722144E+09 | 37204919.67 | 0.276517E+09 | 4234585.97 | 0.272283E+09 | 0.00 | 0.00 |
June | 0.723134E+09 | 10857828.93 | 0.252015E+09 | 311878.17 | 0.251703E+09 | 0.00 | 0.00 |
July | 0.865969E+09 | 652189.31 | 0.260409E+09 | 2212678.42 | 0.258196E+09 | 0.00 | 0.00 |
August | 0.970555E+09 | 253989.63 | 0.302053E+09 | 21401691.35 | 0.280652E+09 | 0.00 | 0.00 |
September | 0.973423E+09 | 17429469.89 | 0.385414E+09 | 88328781.27 | 0.297085E+09 | 0.00 | 0.00 |
October | 0.108646E+10 | 65869890.06 | 0.521401E+09 | 0.207286E+09 | 0.314115E+09 | 0.00 | 0.00 |
November | 0.100158E+10 | 0.150089E+09 | 0.556656E+09 | 0.268350E+09 | 0.288307E+09 | 0.00 | 0.00 |
December | 0.852171E+09 | 0.263979E+09 | 0.533971E+09 | 0.263765E+09 | 0.270205E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.101205E+11 | 0.143338E+10 | 0.481264E+10 | 0.144115E+10 | 0.337149E+10 | 0.00 | 0.00 |
Minimum of Months | 0.649913E+09 | 253989.63 | 0.252015E+09 | 311878.17 | 0.251703E+09 | 0.00 | 0.00 |
Maximum of Months | 0.108646E+10 | 0.310665E+09 | 0.556656E+09 | 0.268350E+09 | 0.314115E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.163316E+10 | 0.607761E+09 | 0.107461E+10 | 0.505224E+09 | 0.569388E+09 | 0.00 | 0.00 |
February | 0.146061E+10 | 0.467679E+09 | 0.911451E+09 | 0.372823E+09 | 0.538627E+09 | 0.00 | 0.00 |
March | 0.147018E+10 | 0.401306E+09 | 0.830540E+09 | 0.225487E+09 | 0.605053E+09 | 0.00 | 0.00 |
April | 0.129928E+10 | 0.246805E+09 | 0.631806E+09 | 66983427.43 | 0.564823E+09 | 0.00 | 0.00 |
May | 0.144429E+10 | 69442307.48 | 0.553034E+09 | 8469171.94 | 0.544565E+09 | 0.00 | 0.00 |
June | 0.144677E+10 | 19163729.75 | 0.504030E+09 | 623756.33 | 0.503406E+09 | 0.00 | 0.00 |
July | 0.172976E+10 | 1141088.43 | 0.520817E+09 | 4425356.84 | 0.516392E+09 | 0.00 | 0.00 |
August | 0.194152E+10 | 360674.82 | 0.604106E+09 | 42803382.70 | 0.561303E+09 | 0.00 | 0.00 |
September | 0.194599E+10 | 31996324.87 | 0.770827E+09 | 0.176658E+09 | 0.594170E+09 | 0.00 | 0.00 |
October | 0.217108E+10 | 0.124430E+09 | 0.104280E+10 | 0.414573E+09 | 0.628230E+09 | 0.00 | 0.00 |
November | 0.200106E+10 | 0.288972E+09 | 0.111331E+10 | 0.536700E+09 | 0.576613E+09 | 0.00 | 0.00 |
December | 0.170736E+10 | 0.515485E+09 | 0.106794E+10 | 0.527531E+09 | 0.540411E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.202511E+11 | 0.277454E+10 | 0.962528E+10 | 0.288230E+10 | 0.674298E+10 | 0.00 | 0.00 |
Minimum of Months | 0.129928E+10 | 360674.82 | 0.504030E+09 | 623756.33 | 0.503406E+09 | 0.00 | 0.00 |
Maximum of Months | 0.217108E+10 | 0.607761E+09 | 0.111331E+10 | 0.536700E+09 | 0.628230E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.815098E+09 | 0.302998E+09 | 0.537306E+09 | 0.252612E+09 | 0.284694E+09 | 0.00 | 0.00 |
February | 0.729330E+09 | 0.232558E+09 | 0.455725E+09 | 0.186412E+09 | 0.269314E+09 | 0.00 | 0.00 |
March | 0.735031E+09 | 0.198478E+09 | 0.415270E+09 | 0.112744E+09 | 0.302526E+09 | 0.00 | 0.00 |
April | 0.651094E+09 | 0.120831E+09 | 0.315903E+09 | 33491713.71 | 0.282411E+09 | 0.00 | 0.00 |
May | 0.727763E+09 | 32987676.68 | 0.276517E+09 | 4234585.97 | 0.272283E+09 | 0.00 | 0.00 |
June | 0.731106E+09 | 8488777.97 | 0.252015E+09 | 311878.17 | 0.251703E+09 | 0.00 | 0.00 |
July | 0.874278E+09 | 477817.35 | 0.260409E+09 | 2212678.42 | 0.258196E+09 | 0.00 | 0.00 |
August | 0.980602E+09 | 109712.27 | 0.302053E+09 | 21401691.35 | 0.280652E+09 | 0.00 | 0.00 |
September | 0.979124E+09 | 14747311.04 | 0.385414E+09 | 88328781.27 | 0.297085E+09 | 0.00 | 0.00 |
October | 0.108841E+10 | 59321960.89 | 0.521401E+09 | 0.207286E+09 | 0.314115E+09 | 0.00 | 0.00 |
November | 0.100098E+10 | 0.141595E+09 | 0.556656E+09 | 0.268350E+09 | 0.288307E+09 | 0.00 | 0.00 |
December | 0.852798E+09 | 0.256040E+09 | 0.533971E+09 | 0.263765E+09 | 0.270205E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.101656E+11 | 0.136863E+10 | 0.481264E+10 | 0.144115E+10 | 0.337149E+10 | 0.00 | 0.00 |
Minimum of Months | 0.651094E+09 | 109712.27 | 0.252015E+09 | 311878.17 | 0.251703E+09 | 0.00 | 0.00 |
Maximum of Months | 0.108841E+10 | 0.302998E+09 | 0.556656E+09 | 0.268350E+09 | 0.314115E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.815658E+09 | 0.302053E+09 | 0.537306E+09 | 0.252612E+09 | 0.284694E+09 | 0.00 | 0.00 |
February | 0.729807E+09 | 0.231702E+09 | 0.455725E+09 | 0.186412E+09 | 0.269314E+09 | 0.00 | 0.00 |
March | 0.735529E+09 | 0.197576E+09 | 0.415270E+09 | 0.112744E+09 | 0.302526E+09 | 0.00 | 0.00 |
April | 0.651566E+09 | 0.120130E+09 | 0.315903E+09 | 33491713.71 | 0.282411E+09 | 0.00 | 0.00 |
May | 0.728401E+09 | 32687596.51 | 0.276517E+09 | 4234585.97 | 0.272283E+09 | 0.00 | 0.00 |
June | 0.731827E+09 | 8348387.41 | 0.252015E+09 | 311878.17 | 0.251703E+09 | 0.00 | 0.00 |
July | 0.875002E+09 | 472728.85 | 0.260409E+09 | 2212678.42 | 0.258196E+09 | 0.00 | 0.00 |
August | 0.981297E+09 | 104285.65 | 0.302053E+09 | 21401691.35 | 0.280652E+09 | 0.00 | 0.00 |
September | 0.979686E+09 | 14613676.62 | 0.385414E+09 | 88328781.27 | 0.297085E+09 | 0.00 | 0.00 |
October | 0.108881E+10 | 58965824.09 | 0.521401E+09 | 0.207286E+09 | 0.314115E+09 | 0.00 | 0.00 |
November | 0.100135E+10 | 0.141064E+09 | 0.556656E+09 | 0.268350E+09 | 0.288307E+09 | 0.00 | 0.00 |
December | 0.853226E+09 | 0.255271E+09 | 0.533971E+09 | 0.263765E+09 | 0.270205E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.101722E+11 | 0.136299E+10 | 0.481264E+10 | 0.144115E+10 | 0.337149E+10 | 0.00 | 0.00 |
Minimum of Months | 0.651566E+09 | 104285.65 | 0.252015E+09 | 311878.17 | 0.251703E+09 | 0.00 | 0.00 |
Maximum of Months | 0.108881E+10 | 0.302053E+09 | 0.556656E+09 | 0.268350E+09 | 0.314115E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.816887E+09 | 0.299625E+09 | 0.537306E+09 | 0.252612E+09 | 0.284694E+09 | 0.00 | 0.00 |
February | 0.730760E+09 | 0.229568E+09 | 0.455725E+09 | 0.186412E+09 | 0.269314E+09 | 0.00 | 0.00 |
March | 0.736260E+09 | 0.195594E+09 | 0.415270E+09 | 0.112744E+09 | 0.302526E+09 | 0.00 | 0.00 |
April | 0.651770E+09 | 0.119213E+09 | 0.315903E+09 | 33491713.71 | 0.282411E+09 | 0.00 | 0.00 |
May | 0.727254E+09 | 32889131.57 | 0.276517E+09 | 4234585.97 | 0.272283E+09 | 0.00 | 0.00 |
June | 0.729866E+09 | 8658500.21 | 0.252015E+09 | 311878.17 | 0.251703E+09 | 0.00 | 0.00 |
July | 0.871438E+09 | 537322.83 | 0.260409E+09 | 2212678.42 | 0.258196E+09 | 0.00 | 0.00 |
August | 0.977126E+09 | 144227.49 | 0.302053E+09 | 21401691.35 | 0.280652E+09 | 0.00 | 0.00 |
September | 0.977017E+09 | 15208915.82 | 0.385414E+09 | 88328781.27 | 0.297085E+09 | 0.00 | 0.00 |
October | 0.108748E+10 | 60089104.04 | 0.521401E+09 | 0.207286E+09 | 0.314115E+09 | 0.00 | 0.00 |
November | 0.100102E+10 | 0.141308E+09 | 0.556656E+09 | 0.268350E+09 | 0.288307E+09 | 0.00 | 0.00 |
December | 0.853808E+09 | 0.253951E+09 | 0.533971E+09 | 0.263765E+09 | 0.270205E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.101607E+11 | 0.135679E+10 | 0.481264E+10 | 0.144115E+10 | 0.337149E+10 | 0.00 | 0.00 |
Minimum of Months | 0.651770E+09 | 144227.49 | 0.252015E+09 | 311878.17 | 0.251703E+09 | 0.00 | 0.00 |
Maximum of Months | 0.108748E+10 | 0.299625E+09 | 0.556656E+09 | 0.268350E+09 | 0.314115E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.817651E+09 | 0.292400E+09 | 0.537306E+09 | 0.252612E+09 | 0.284694E+09 | 0.00 | 0.00 |
February | 0.731109E+09 | 0.222553E+09 | 0.455725E+09 | 0.186412E+09 | 0.269314E+09 | 0.00 | 0.00 |
March | 0.735196E+09 | 0.189424E+09 | 0.415270E+09 | 0.112744E+09 | 0.302526E+09 | 0.00 | 0.00 |
April | 0.647325E+09 | 0.117705E+09 | 0.315903E+09 | 33491713.71 | 0.282411E+09 | 0.00 | 0.00 |
May | 0.713180E+09 | 35170412.97 | 0.276517E+09 | 4234585.97 | 0.272283E+09 | 0.00 | 0.00 |
June | 0.710946E+09 | 10888588.68 | 0.252015E+09 | 311878.17 | 0.251703E+09 | 0.00 | 0.00 |
July | 0.842800E+09 | 1054255.03 | 0.260409E+09 | 2212678.42 | 0.258196E+09 | 0.00 | 0.00 |
August | 0.944579E+09 | 516154.66 | 0.302053E+09 | 21401691.35 | 0.280652E+09 | 0.00 | 0.00 |
September | 0.955202E+09 | 19718146.98 | 0.385414E+09 | 88328781.27 | 0.297085E+09 | 0.00 | 0.00 |
October | 0.107406E+10 | 68603232.41 | 0.521401E+09 | 0.207286E+09 | 0.314115E+09 | 0.00 | 0.00 |
November | 0.994302E+09 | 0.146380E+09 | 0.556656E+09 | 0.268350E+09 | 0.288307E+09 | 0.00 | 0.00 |
December | 0.852546E+09 | 0.251503E+09 | 0.533971E+09 | 0.263765E+09 | 0.270205E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.100189E+11 | 0.135592E+10 | 0.481264E+10 | 0.144115E+10 | 0.337149E+10 | 0.00 | 0.00 |
Minimum of Months | 0.647325E+09 | 516154.66 | 0.252015E+09 | 311878.17 | 0.251703E+09 | 0.00 | 0.00 |
Maximum of Months | 0.107406E+10 | 0.292400E+09 | 0.556656E+09 | 0.268350E+09 | 0.314115E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.24 | 14.74 | 11.63 | 2.95 | 7.91 | 83.00 | 101.34 | 0.00 |
February | 20.75 | 16.26 | 13.46 | 3.66 | 9.80 | 96.50 | 106.33 | 0.00 |
March | 23.12 | 16.75 | 12.67 | 3.48 | 11.63 | 114.51 | 110.36 | 0.00 |
April | 26.49 | 19.17 | 14.91 | 3.36 | 14.65 | 129.52 | 127.73 | 0.00 |
May | 31.37 | 21.91 | 17.14 | 3.30 | 19.37 | 135.62 | 152.47 | 0.00 |
June | 32.97 | 24.78 | 21.39 | 3.95 | 20.59 | 135.23 | 162.31 | 0.00 |
July | 35.08 | 26.48 | 23.16 | 3.85 | 24.14 | 131.49 | 150.69 | 0.00 |
August | 35.31 | 27.02 | 24.10 | 3.89 | 24.33 | 129.32 | 147.63 | 0.00 |
September | 32.49 | 25.68 | 23.13 | 3.64 | 20.59 | 118.70 | 140.92 | 0.00 |
October | 29.53 | 22.66 | 19.34 | 3.16 | 16.84 | 101.82 | 135.23 | 0.00 |
November | 25.53 | 19.62 | 16.50 | 2.98 | 12.88 | 85.82 | 121.41 | 0.00 |
December | 21.13 | 16.84 | 14.23 | 2.84 | 10.14 | 76.46 | 98.30 | 0.00 |
Annual Sum or Average | 27.79 | 21.02 | 17.66 | 3.42 | 16.11 | 111.56 | 129.66 | 0.00 |
Minimum of Months | 19.24 | 14.74 | 11.63 | 2.84 | 7.91 | 76.46 | 98.30 | 0.00 |
Maximum of Months | 35.31 | 27.02 | 24.10 | 3.95 | 24.33 | 135.62 | 162.31 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.00 | 23-JAN-13:00 | 16.55 | 9.00 | 4.60 | 16.85 | 268.00 | 249.50 |
February | 32.50 | 06-FEB-14:00 | 17.28 | 6.50 | 6.20 | 21.27 | 242.00 | 327.50 |
March | 38.00 | 27-MAR-10:00 | 18.84 | 6.00 | 7.70 | 21.44 | 329.50 | 440.00 |
April | 42.00 | 28-APR-11:00 | 19.18 | 2.00 | 2.60 | 24.16 | 371.50 | 432.50 |
May | 42.10 | 31-MAY-18:00 | 20.76 | 8.00 | 5.10 | 30.18 | 0.00 | 0.00 |
June | 43.00 | 12-JUN-11:00 | 24.56 | 17.00 | 3.60 | 28.91 | 372.00 | 427.00 |
July | 46.00 | 21-JUL-11:00 | 22.01 | 9.00 | 3.60 | 32.99 | 306.00 | 562.50 |
August | 46.00 | 16-AUG-11:00 | 25.38 | 17.00 | 7.20 | 31.75 | 273.00 | 629.50 |
September | 41.20 | 26-SEP-12:00 | 22.43 | 13.00 | 4.10 | 26.15 | 325.00 | 455.00 |
October | 38.00 | 04-OCT-11:00 | 19.81 | 9.00 | 1.00 | 22.13 | 338.00 | 421.50 |
November | 34.00 | 05-NOV-11:00 | 17.15 | 5.00 | 2.10 | 17.39 | 294.00 | 427.50 |
December | 30.00 | 10-DEC-11:00 | 19.04 | 13.00 | 4.10 | 21.27 | 305.00 | 214.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.00 | 16.55 | 2.00 | 1.00 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 46.00 | 25.38 | 17.00 | 7.70 | 32.99 | 372.00 | 629.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 09-JAN-07:00 | 12.00 | 12.00 | 1.00 | -1.9 | 54.50 | 10.00 |
February | 13.00 | 01-FEB-04:00 | 12.45 | 12.00 | 1.00 | -0.8 | 0.00 | 0.00 |
March | 14.00 | 07-MAR-05:00 | 11.74 | 10.00 | 0.50 | 2.64 | 0.00 | 0.00 |
April | 17.00 | 01-APR-05:00 | 15.74 | 15.00 | 0.50 | 3.69 | 0.00 | 0.00 |
May | 20.40 | 01-MAY-05:00 | 20.40 | 20.40 | 2.10 | 9.33 | 28.50 | 50.50 |
June | 21.00 | 22-JUN-07:00 | 19.59 | 19.00 | 1.50 | 8.35 | 206.50 | 266.00 |
July | 28.00 | 03-JUL-05:00 | 16.06 | 8.00 | 1.00 | 12.41 | 32.50 | 30.50 |
August | 28.80 | 31-AUG-03:00 | 25.95 | 25.00 | 1.50 | 17.03 | 0.00 | 0.00 |
September | 23.00 | 25-SEP-04:00 | 22.27 | 22.00 | 2.10 | 10.88 | 0.00 | 0.00 |
October | 20.60 | 29-OCT-06:00 | 17.24 | 15.40 | 0.50 | 7.15 | 49.50 | 123.00 |
November | 16.90 | 22-NOV-06:00 | 14.44 | 12.90 | 3.10 | 3.06 | 31.00 | 106.50 |
December | 13.00 | 18-DEC-04:00 | 10.82 | 9.00 | 1.80 | -1.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.00 | 10.82 | 8.00 | 0.50 | -1.9 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 25.95 | 25.00 | 3.10 | 17.03 | 206.50 | 266.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.89 | 30-JAN-13:00 | 23.00 | 20.00 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 23.21 | 07-FEB-15:00 | 28.00 | 21.30 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 23.05 | 28-MAR-10:00 | 28.00 | 21.00 | 7.20 | 23.82 | 374.50 | 58.00 |
April | 26.40 | 30-APR-14:00 | 31.00 | 25.00 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 29.11 | 29-MAY-12:00 | 33.40 | 27.90 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 29.09 | 04-JUN-18:00 | 33.20 | 28.00 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.86 | 18-JUL-20:00 | 34.00 | 30.00 | 3.60 | 26.32 | 0.00 | 0.00 |
August | 31.14 | 22-AUG-16:00 | 36.00 | 30.00 | 9.30 | 25.16 | 159.00 | 168.50 |
September | 30.39 | 09-SEP-13:00 | 36.00 | 29.00 | 5.70 | 28.11 | 339.50 | 377.00 |
October | 30.18 | 07-OCT-09:00 | 30.60 | 30.10 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 26.24 | 01-NOV-13:00 | 33.00 | 24.00 | 6.20 | 20.92 | 269.00 | 349.50 |
December | 23.18 | 05-DEC-14:00 | 26.00 | 22.00 | 4.60 | 16.85 | 185.00 | 295.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.89 | 23.00 | 20.00 | 3.60 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 31.14 | 36.00 | 30.10 | 9.30 | 28.11 | 421.00 | 377.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.00 | 30-JAN-13:00 | 23.00 | 20.89 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 21.30 | 07-FEB-15:00 | 28.00 | 23.21 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 22.00 | 31-MAR-09:00 | 23.00 | 22.27 | 0.50 | 10.88 | 323.50 | 305.50 |
April | 25.00 | 30-APR-14:00 | 31.00 | 26.40 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 27.90 | 29-MAY-12:00 | 33.40 | 29.11 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 28.00 | 04-JUN-18:00 | 33.20 | 29.09 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.00 | 19-JUL-23:19 | 34.00 | 30.86 | 0.83 | 25.33 | 0.00 | 0.00 |
August | 30.00 | 07-AUG-23:19 | 33.00 | 30.56 | 3.43 | 22.30 | 0.00 | 0.00 |
September | 29.00 | 08-SEP-07:00 | 31.00 | 29.41 | 1.50 | 24.33 | 179.00 | 151.00 |
October | 30.10 | 07-OCT-09:00 | 30.60 | 30.18 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 24.00 | 01-NOV-10:00 | 32.00 | 26.10 | 3.10 | 20.05 | 300.50 | 377.00 |
December | 23.00 | 25-DEC-10:00 | 23.00 | 23.00 | 0.80 | 14.10 | 245.00 | 376.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 23.00 | 20.89 | 0.50 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 30.10 | 34.00 | 30.86 | 8.70 | 25.33 | 421.00 | 377.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.90 | 26.90 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.87 | 32.18 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 28.18 | 38.22 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 31.32 | 44.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 34.39 | 50.41 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 36.58 | 52.39 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 37.28 | 50.68 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 36.29 | 48.56 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 33.90 | 43.99 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.75 | 37.43 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 27.69 | 30.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.55 | 25.09 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 31.09 | 40.13 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.90 | 25.09 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 37.28 | 52.39 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.280373E+09 | -167381658.3 | 0.00 | 0.00 | 744.00 | 0.00 | -112990990.2 | 58.99 | 0.00 | 0.00 |
February | 0.249480E+09 | -147671533.9 | 0.00 | 0.00 | 672.00 | 0.00 | -101808156.0 | 58.99 | 0.00 | 0.00 |
March | 0.266911E+09 | -154558883.6 | 0.00 | 0.00 | 744.00 | 0.00 | -112351936.4 | 58.99 | 0.00 | 0.00 |
April | 0.240888E+09 | -132638564.1 | 0.00 | 0.00 | 720.00 | 0.00 | -108249260.2 | 58.99 | 0.00 | 0.00 |
May | 0.232935E+09 | -122089813.8 | 0.00 | 0.00 | 744.00 | 0.00 | -110845571.5 | 58.99 | 0.00 | 0.00 |
June | 0.215507E+09 | -108670302.2 | 0.00 | 0.00 | 720.00 | 0.00 | -106836875.0 | 58.99 | 0.00 | 0.00 |
July | 0.216457E+09 | -106567766.7 | 0.00 | 0.00 | 744.00 | 0.00 | -109889211.9 | 58.99 | 0.00 | 0.00 |
August | 0.223453E+09 | -113799358.7 | 0.00 | 0.00 | 744.00 | 0.00 | -109653857.2 | 58.99 | 0.00 | 0.00 |
September | 0.227058E+09 | -120418601.8 | 0.00 | 0.00 | 720.00 | 0.00 | -106639386.8 | 58.99 | 0.00 | 0.00 |
October | 0.249370E+09 | -138692829.7 | 0.00 | 0.00 | 744.00 | 0.00 | -110676704.9 | 58.99 | 0.00 | 0.00 |
November | 0.256144E+09 | -148305854.2 | 0.00 | 0.00 | 720.00 | 0.00 | -107837651.4 | 58.99 | 0.00 | 0.00 |
December | 0.276771E+09 | -164402967.6 | 0.00 | 0.00 | 744.00 | 0.00 | -112367570.8 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.293535E+10 | -0.162520E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.131015E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.215507E+09 | -167381658.3 | 0.00 | 0.00 | 672.00 | 0.00 | -112990990.2 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.280373E+09 | -106567766.7 | 0.00 | 0.00 | 744.00 | 0.00 | -101808156.0 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.280101E+09 | -167381606.7 | 0.00 | 0.00 | 744.00 | 0.00 | -112719113.2 | 58.99 | 0.00 | 0.00 |
February | 0.249249E+09 | -147695542.8 | 0.00 | 0.00 | 672.00 | 0.00 | -101553572.0 | 58.99 | 0.00 | 0.00 |
March | 0.266704E+09 | -154568574.8 | 0.00 | 0.00 | 744.00 | 0.00 | -112135683.2 | 58.99 | 0.00 | 0.00 |
April | 0.240727E+09 | -132625789.6 | 0.00 | 0.00 | 720.00 | 0.00 | -108101533.4 | 58.99 | 0.00 | 0.00 |
May | 0.232928E+09 | -122090360.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110837617.6 | 58.99 | 0.00 | 0.00 |
June | 0.215605E+09 | -108685938.6 | 0.00 | 0.00 | 720.00 | 0.00 | -106919533.5 | 58.99 | 0.00 | 0.00 |
July | 0.216637E+09 | -106572987.7 | 0.00 | 0.00 | 744.00 | 0.00 | -110064378.2 | 58.99 | 0.00 | 0.00 |
August | 0.223693E+09 | -113791979.2 | 0.00 | 0.00 | 744.00 | 0.00 | -109901501.3 | 58.99 | 0.00 | 0.00 |
September | 0.227194E+09 | -120412879.8 | 0.00 | 0.00 | 720.00 | 0.00 | -106781396.0 | 58.99 | 0.00 | 0.00 |
October | 0.249458E+09 | -138697962.6 | 0.00 | 0.00 | 744.00 | 0.00 | -110759770.2 | 58.99 | 0.00 | 0.00 |
November | 0.256136E+09 | -148303387.4 | 0.00 | 0.00 | 720.00 | 0.00 | -107832286.5 | 58.99 | 0.00 | 0.00 |
December | 0.276606E+09 | -164406487.4 | 0.00 | 0.00 | 744.00 | 0.00 | -112199328.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.293504E+10 | -0.162523E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.130981E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.215605E+09 | -167381606.7 | 0.00 | 0.00 | 672.00 | 0.00 | -112719113.2 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.280101E+09 | -106572987.7 | 0.00 | 0.00 | 744.00 | 0.00 | -101553572.0 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.259265E+09 | -147196088.0 | 0.00 | 0.00 | 744.00 | 0.00 | -112069384.8 | 58.99 | 0.00 | 0.00 |
February | 0.230775E+09 | -130001419.3 | 0.00 | 0.00 | 672.00 | 0.00 | -100774036.6 | 58.99 | 0.00 | 0.00 |
March | 0.248890E+09 | -137934769.4 | 0.00 | 0.00 | 744.00 | 0.00 | -110955694.2 | 58.99 | 0.00 | 0.00 |
April | 0.222983E+09 | -116666059.8 | 0.00 | 0.00 | 720.00 | 0.00 | -106317425.1 | 58.99 | 0.00 | 0.00 |
May | 0.216578E+09 | -108306287.8 | 0.00 | 0.00 | 744.00 | 0.00 | -108271256.6 | 58.99 | 0.00 | 0.00 |
June | 0.201065E+09 | -96758666.8 | 0.00 | 0.00 | 720.00 | 0.00 | -104306421.3 | 58.99 | 0.00 | 0.00 |
July | 0.200014E+09 | -93158384.2 | 0.00 | 0.00 | 744.00 | 0.00 | -106856013.9 | 58.99 | 0.00 | 0.00 |
August | 0.208487E+09 | -101611771.8 | 0.00 | 0.00 | 744.00 | 0.00 | -106875069.1 | 58.99 | 0.00 | 0.00 |
September | 0.209828E+09 | -105867080.6 | 0.00 | 0.00 | 720.00 | 0.00 | -103960811.5 | 58.99 | 0.00 | 0.00 |
October | 0.230148E+09 | -121990093.3 | 0.00 | 0.00 | 744.00 | 0.00 | -108157759.5 | 58.99 | 0.00 | 0.00 |
November | 0.236994E+09 | -130918426.7 | 0.00 | 0.00 | 720.00 | 0.00 | -106075551.9 | 58.99 | 0.00 | 0.00 |
December | 0.254652E+09 | -143548361.1 | 0.00 | 0.00 | 744.00 | 0.00 | -111104094.6 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.271968E+10 | -0.143396E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.128572E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.200014E+09 | -147196088.0 | 0.00 | 0.00 | 672.00 | 0.00 | -112069384.8 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.259265E+09 | -93158384.2 | 0.00 | 0.00 | 744.00 | 0.00 | -100774036.6 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.259361E+09 | -147197297.7 | 0.00 | 0.00 | 744.00 | 0.00 | -112163868.1 | 58.99 | 0.00 | 0.00 |
February | 0.230823E+09 | -130009558.4 | 0.00 | 0.00 | 672.00 | 0.00 | -100813464.2 | 58.98 | 0.00 | 0.00 |
March | 0.248903E+09 | -137931811.3 | 0.00 | 0.00 | 744.00 | 0.00 | -110971217.7 | 58.99 | 0.00 | 0.00 |
April | 0.222916E+09 | -116667127.6 | 0.00 | 0.00 | 720.00 | 0.00 | -106248536.3 | 58.99 | 0.00 | 0.00 |
May | 0.216395E+09 | -108297935.7 | 0.00 | 0.00 | 744.00 | 0.00 | -108096982.6 | 58.99 | 0.00 | 0.00 |
June | 0.200874E+09 | -96779876.8 | 0.00 | 0.00 | 720.00 | 0.00 | -104094031.6 | 58.99 | 0.00 | 0.00 |
July | 0.199767E+09 | -93186344.7 | 0.00 | 0.00 | 744.00 | 0.00 | -106580226.7 | 58.98 | 0.00 | 0.00 |
August | 0.208263E+09 | -101671200.2 | 0.00 | 0.00 | 744.00 | 0.00 | -106591430.2 | 58.98 | 0.00 | 0.00 |
September | 0.209619E+09 | -105836553.0 | 0.00 | 0.00 | 720.00 | 0.00 | -103781981.4 | 59.00 | 0.00 | 0.00 |
October | 0.229958E+09 | -121984044.8 | 0.00 | 0.00 | 744.00 | 0.00 | -107974215.3 | 58.99 | 0.00 | 0.00 |
November | 0.236917E+09 | -130922271.4 | 0.00 | 0.00 | 720.00 | 0.00 | -105994686.8 | 58.99 | 0.00 | 0.00 |
December | 0.254679E+09 | -143548373.8 | 0.00 | 0.00 | 744.00 | 0.00 | -111130533.3 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.271847E+10 | -0.143403E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.128444E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.199767E+09 | -147197297.7 | 0.00 | 0.00 | 672.00 | 0.00 | -112163868.1 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.259361E+09 | -93186344.7 | 0.00 | 0.00 | 744.00 | 0.00 | -100813464.2 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.251847E+09 | -139118119.9 | 0.00 | 0.00 | 744.00 | 0.00 | -112729296.4 | 58.99 | 0.00 | 0.00 |
February | 0.224238E+09 | -122925432.7 | 0.00 | 0.00 | 672.00 | 0.00 | -101312765.9 | 58.99 | 0.00 | 0.00 |
March | 0.242090E+09 | -130511189.5 | 0.00 | 0.00 | 744.00 | 0.00 | -111579266.5 | 58.99 | 0.00 | 0.00 |
April | 0.217182E+09 | -110378348.1 | 0.00 | 0.00 | 720.00 | 0.00 | -106803983.3 | 58.99 | 0.00 | 0.00 |
May | 0.211052E+09 | -102455581.7 | 0.00 | 0.00 | 744.00 | 0.00 | -108596372.8 | 58.98 | 0.00 | 0.00 |
June | 0.196200E+09 | -91607330.4 | 0.00 | 0.00 | 720.00 | 0.00 | -104592770.5 | 58.98 | 0.00 | 0.00 |
July | 0.195075E+09 | -88138743.2 | 0.00 | 0.00 | 744.00 | 0.00 | -106936341.8 | 58.99 | 0.00 | 0.00 |
August | 0.203233E+09 | -96145329.8 | 0.00 | 0.00 | 744.00 | 0.00 | -107088060.9 | 58.99 | 0.00 | 0.00 |
September | 0.204333E+09 | -100178022.3 | 0.00 | 0.00 | 720.00 | 0.00 | -104155366.6 | 59.00 | 0.00 | 0.00 |
October | 0.223723E+09 | -115284772.2 | 0.00 | 0.00 | 744.00 | 0.00 | -108438022.0 | 58.99 | 0.00 | 0.00 |
November | 0.230097E+09 | -123661700.1 | 0.00 | 0.00 | 720.00 | 0.00 | -106434891.0 | 58.99 | 0.00 | 0.00 |
December | 0.247366E+09 | -135732421.1 | 0.00 | 0.00 | 744.00 | 0.00 | -111633405.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.264644E+10 | -0.135614E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.129030E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.195075E+09 | -139118119.9 | 0.00 | 0.00 | 672.00 | 0.00 | -112729296.4 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.251847E+09 | -88138743.2 | 0.00 | 0.00 | 744.00 | 0.00 | -101312765.9 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.251872E+09 | -139117733.6 | 0.00 | 0.00 | 744.00 | 0.00 | -112753789.3 | 58.99 | 0.00 | 0.00 |
February | 0.224278E+09 | -122927737.5 | 0.00 | 0.00 | 672.00 | 0.00 | -101349867.5 | 58.99 | 0.00 | 0.00 |
March | 0.242154E+09 | -130513546.3 | 0.00 | 0.00 | 744.00 | 0.00 | -111640629.3 | 58.99 | 0.00 | 0.00 |
April | 0.217279E+09 | -110391262.3 | 0.00 | 0.00 | 720.00 | 0.00 | -106888014.0 | 58.99 | 0.00 | 0.00 |
May | 0.211193E+09 | -102432083.4 | 0.00 | 0.00 | 744.00 | 0.00 | -108761341.4 | 58.99 | 0.00 | 0.00 |
June | 0.196349E+09 | -91575913.7 | 0.00 | 0.00 | 720.00 | 0.00 | -104773198.1 | 58.99 | 0.00 | 0.00 |
July | 0.195242E+09 | -88099390.0 | 0.00 | 0.00 | 744.00 | 0.00 | -107142956.8 | 58.99 | 0.00 | 0.00 |
August | 0.203455E+09 | -96175116.7 | 0.00 | 0.00 | 744.00 | 0.00 | -107279803.3 | 58.99 | 0.00 | 0.00 |
September | 0.204499E+09 | -100220283.4 | 0.00 | 0.00 | 720.00 | 0.00 | -104278574.8 | 58.98 | 0.00 | 0.00 |
October | 0.223867E+09 | -115281345.7 | 0.00 | 0.00 | 744.00 | 0.00 | -108585799.7 | 59.00 | 0.00 | 0.00 |
November | 0.230195E+09 | -123662073.3 | 0.00 | 0.00 | 720.00 | 0.00 | -106532642.5 | 58.99 | 0.00 | 0.00 |
December | 0.247421E+09 | -135734027.3 | 0.00 | 0.00 | 744.00 | 0.00 | -111687200.8 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.264780E+10 | -0.135613E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.129167E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.195242E+09 | -139117733.6 | 0.00 | 0.00 | 672.00 | 0.00 | -112753789.3 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.251872E+09 | -88099390.0 | 0.00 | 0.00 | 744.00 | 0.00 | -101349867.5 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.251924E+09 | -139113609.7 | 0.00 | 0.00 | 744.00 | 0.00 | -112810077.4 | 58.99 | 0.00 | 0.00 |
February | 0.224323E+09 | -122929011.6 | 0.00 | 0.00 | 672.00 | 0.00 | -101394375.4 | 58.99 | 0.00 | 0.00 |
March | 0.242201E+09 | -130522700.2 | 0.00 | 0.00 | 744.00 | 0.00 | -111678131.1 | 58.99 | 0.00 | 0.00 |
April | 0.217327E+09 | -110408585.4 | 0.00 | 0.00 | 720.00 | 0.00 | -106917999.5 | 58.99 | 0.00 | 0.00 |
May | 0.211225E+09 | -102428223.1 | 0.00 | 0.00 | 744.00 | 0.00 | -108796539.4 | 58.99 | 0.00 | 0.00 |
June | 0.196372E+09 | -91559830.7 | 0.00 | 0.00 | 720.00 | 0.00 | -104812547.4 | 58.99 | 0.00 | 0.00 |
July | 0.195269E+09 | -88109596.7 | 0.00 | 0.00 | 744.00 | 0.00 | -107159438.2 | 58.99 | 0.00 | 0.00 |
August | 0.203469E+09 | -96147043.6 | 0.00 | 0.00 | 744.00 | 0.00 | -107322412.1 | 59.00 | 0.00 | 0.00 |
September | 0.204520E+09 | -100161959.5 | 0.00 | 0.00 | 720.00 | 0.00 | -104357685.6 | 59.00 | 0.00 | 0.00 |
October | 0.223899E+09 | -115296710.7 | 0.00 | 0.00 | 744.00 | 0.00 | -108602421.6 | 58.99 | 0.00 | 0.00 |
November | 0.230216E+09 | -123656483.0 | 0.00 | 0.00 | 720.00 | 0.00 | -106559179.8 | 58.99 | 0.00 | 0.00 |
December | 0.247473E+09 | -135705833.3 | 0.00 | 0.00 | 744.00 | 0.00 | -111767321.4 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.264822E+10 | -0.135604E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.129218E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.195269E+09 | -139113609.7 | 0.00 | 0.00 | 672.00 | 0.00 | -112810077.4 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.251924E+09 | -88109596.7 | 0.00 | 0.00 | 744.00 | 0.00 | -101394375.4 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 325.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 308.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 357.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 375.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 405.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 403.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 405.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 395.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 358.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 351.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 318.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 319.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4323.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 308.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 405.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.141381E+11 | 0.108546E+11 | 38766.45 | 29-JAN-08:62 | 28202.90 | 0.00 |
February | 0.00 | 0.00 | 0.162142E+11 | 0.122063E+11 | 68677.23 | 09-FEB-09:02 | 42400.86 | 0.00 |
March | 0.00 | 0.00 | 0.223431E+11 | 0.175521E+11 | 78065.18 | 01-MAR-09:01 | 53642.89 | 0.00 |
April | 0.00 | 0.00 | 0.310991E+11 | 0.236564E+11 | 79821.78 | 30-APR-07:02 | 45590.24 | 0.00 |
May | 0.00 | 0.00 | 0.456752E+11 | 0.345022E+11 | 82754.99 | 30-MAY-08:61 | 41936.21 | 0.00 |
June | 0.00 | 0.00 | 0.553848E+11 | 0.369940E+11 | 84373.72 | 08-JUN-08:61 | 37009.46 | 0.00 |
July | 0.00 | 0.00 | 0.663582E+11 | 0.427746E+11 | 83284.11 | 18-JUL-08:03 | 36312.56 | 0.00 |
August | 0.00 | 0.00 | 0.701147E+11 | 0.441031E+11 | 83630.81 | 08-AUG-07:01 | 34266.58 | 0.00 |
September | 0.00 | 0.00 | 0.598185E+11 | 0.376298E+11 | 84156.58 | 23-SEP-08:61 | 38253.81 | 0.00 |
October | 0.00 | 0.00 | 0.472029E+11 | 0.329318E+11 | 84335.74 | 07-OCT-08:61 | 36859.34 | 0.00 |
November | 0.00 | 0.00 | 0.328935E+11 | 0.237574E+11 | 81536.85 | 03-NOV-08:61 | 44630.64 | 0.00 |
December | 0.00 | 0.00 | 0.206296E+11 | 0.148992E+11 | 77266.28 | 12-DEC-09:02 | 55805.87 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.481872E+12 | 0.331862E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.141381E+11 | 0.108546E+11 | 38766.45 | 28202.90 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.701147E+11 | 0.441031E+11 | 84373.72 | 55805.87 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.782833E+10 | 0.612209E+10 | 21353.50 | 29-JAN-08:62 | 16725.12 | 0.00 |
February | 0.00 | 0.00 | 0.867765E+10 | 0.666474E+10 | 33700.65 | 09-FEB-09:02 | 22469.72 | 0.00 |
March | 0.00 | 0.00 | 0.115144E+11 | 0.919242E+10 | 38983.71 | 01-MAR-09:01 | 28290.07 | 0.00 |
April | 0.00 | 0.00 | 0.152956E+11 | 0.118926E+11 | 39784.68 | 18-APR-08:62 | 25406.26 | 0.00 |
May | 0.00 | 0.00 | 0.218059E+11 | 0.168074E+11 | 40848.74 | 30-MAY-08:61 | 23573.59 | 0.00 |
June | 0.00 | 0.00 | 0.261181E+11 | 0.179083E+11 | 41863.01 | 08-JUN-08:61 | 21009.79 | 0.00 |
July | 0.00 | 0.00 | 0.312308E+11 | 0.205291E+11 | 42063.78 | 26-JUL-08:61 | 20043.37 | 0.00 |
August | 0.00 | 0.00 | 0.329878E+11 | 0.211022E+11 | 42088.88 | 21-AUG-08:61 | 20194.00 | 0.00 |
September | 0.00 | 0.00 | 0.280427E+11 | 0.181017E+11 | 42290.50 | 11-SEP-08:61 | 19758.96 | 0.00 |
October | 0.00 | 0.00 | 0.223729E+11 | 0.159837E+11 | 41858.24 | 07-OCT-08:61 | 21184.73 | 0.00 |
November | 0.00 | 0.00 | 0.160856E+11 | 0.118083E+11 | 40466.98 | 01-NOV-08:61 | 24616.34 | 0.00 |
December | 0.00 | 0.00 | 0.107458E+11 | 0.794775E+10 | 38486.47 | 12-DEC-09:02 | 29735.39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.232705E+12 | 0.164060E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.782833E+10 | 0.612209E+10 | 21353.50 | 16725.12 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.329878E+11 | 0.211022E+11 | 42290.50 | 29735.39 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.522735E+10 | 0.404787E+10 | 27672.69 | 29-JAN-09:02 | 18708.14 | 0.00 |
February | 0.00 | 0.00 | 0.621219E+10 | 0.474749E+10 | 36322.38 | 09-FEB-08:62 | 21584.47 | 0.00 |
March | 0.00 | 0.00 | 0.873155E+10 | 0.698123E+10 | 39396.13 | 01-MAR-08:62 | 26093.80 | 0.00 |
April | 0.00 | 0.00 | 0.119201E+11 | 0.931222E+10 | 40847.82 | 30-APR-08:62 | 21686.48 | 0.00 |
May | 0.00 | 0.00 | 0.177979E+11 | 0.137086E+11 | 41919.64 | 30-MAY-07:01 | 20525.49 | 0.00 |
June | 0.00 | 0.00 | 0.216282E+11 | 0.147679E+11 | 42502.04 | 08-JUN-07:01 | 17854.62 | 0.00 |
July | 0.00 | 0.00 | 0.259209E+11 | 0.167311E+11 | 42095.95 | 26-JUL-07:03 | 17949.48 | 0.00 |
August | 0.00 | 0.00 | 0.279574E+11 | 0.175586E+11 | 42095.95 | 08-AUG-07:01 | 16704.91 | 0.00 |
September | 0.00 | 0.00 | 0.230199E+11 | 0.147279E+11 | 42505.51 | 25-SEP-07:01 | 18143.63 | 0.00 |
October | 0.00 | 0.00 | 0.181595E+11 | 0.127958E+11 | 42506.45 | 07-OCT-07:01 | 17567.31 | 0.00 |
November | 0.00 | 0.00 | 0.128473E+11 | 0.925523E+10 | 41233.97 | 03-NOV-07:02 | 21432.52 | 0.00 |
December | 0.00 | 0.00 | 0.778009E+10 | 0.567785E+10 | 38845.78 | 12-DEC-08:62 | 27851.56 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.187202E+12 | 0.130312E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.522735E+10 | 0.404787E+10 | 27672.69 | 16704.91 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.279574E+11 | 0.175586E+11 | 42506.45 | 27851.56 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.515307E+10 | 0.398694E+10 | 27270.24 | 29-JAN-09:02 | 18412.81 | 0.00 |
February | 0.00 | 0.00 | 0.616709E+10 | 0.471198E+10 | 36384.40 | 09-FEB-08:62 | 21625.50 | 0.00 |
March | 0.00 | 0.00 | 0.871195E+10 | 0.696522E+10 | 39456.08 | 01-MAR-08:62 | 26115.45 | 0.00 |
April | 0.00 | 0.00 | 0.119476E+11 | 0.933625E+10 | 40926.73 | 30-APR-08:62 | 21804.20 | 0.00 |
May | 0.00 | 0.00 | 0.179126E+11 | 0.138057E+11 | 41911.19 | 30-MAY-07:01 | 20763.54 | 0.00 |
June | 0.00 | 0.00 | 0.217717E+11 | 0.148822E+11 | 42570.56 | 08-JUN-07:01 | 17941.01 | 0.00 |
July | 0.00 | 0.00 | 0.261113E+11 | 0.168847E+11 | 42174.39 | 02-JUL-07:01 | 19420.13 | 0.00 |
August | 0.00 | 0.00 | 0.281429E+11 | 0.177073E+11 | 42174.39 | 21-AUG-06:03 | 17418.01 | 0.00 |
September | 0.00 | 0.00 | 0.231797E+11 | 0.148538E+11 | 42574.04 | 25-SEP-07:01 | 18379.66 | 0.00 |
October | 0.00 | 0.00 | 0.182879E+11 | 0.128981E+11 | 42574.98 | 07-OCT-07:03 | 17557.49 | 0.00 |
November | 0.00 | 0.00 | 0.128865E+11 | 0.928847E+10 | 41309.53 | 03-NOV-07:02 | 21528.28 | 0.00 |
December | 0.00 | 0.00 | 0.774896E+10 | 0.565382E+10 | 38910.87 | 12-DEC-08:62 | 27909.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.188021E+12 | 0.130974E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.515307E+10 | 0.398694E+10 | 27270.24 | 17418.01 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.281429E+11 | 0.177073E+11 | 42574.98 | 27909.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.495856E+10 | 0.382777E+10 | 25534.96 | 29-JAN-09:02 | 17132.98 | 0.00 |
February | 0.00 | 0.00 | 0.599580E+10 | 0.457525E+10 | 34319.37 | 09-FEB-08:62 | 20263.22 | 0.00 |
March | 0.00 | 0.00 | 0.852953E+10 | 0.681350E+10 | 39381.84 | 01-MAR-08:62 | 25962.75 | 0.00 |
April | 0.00 | 0.00 | 0.117941E+11 | 0.920813E+10 | 40856.54 | 30-APR-08:62 | 21698.41 | 0.00 |
May | 0.00 | 0.00 | 0.177940E+11 | 0.137032E+11 | 41862.52 | 30-MAY-07:01 | 20696.86 | 0.00 |
June | 0.00 | 0.00 | 0.216503E+11 | 0.147838E+11 | 42508.04 | 08-JUN-07:01 | 17800.22 | 0.00 |
July | 0.00 | 0.00 | 0.260229E+11 | 0.168127E+11 | 42112.45 | 02-JUL-07:01 | 19304.94 | 0.00 |
August | 0.00 | 0.00 | 0.280463E+11 | 0.176292E+11 | 42112.45 | 21-AUG-06:03 | 17361.48 | 0.00 |
September | 0.00 | 0.00 | 0.230732E+11 | 0.147704E+11 | 42511.52 | 25-SEP-07:01 | 18281.11 | 0.00 |
October | 0.00 | 0.00 | 0.181727E+11 | 0.128044E+11 | 42512.45 | 07-OCT-07:01 | 17519.31 | 0.00 |
November | 0.00 | 0.00 | 0.127495E+11 | 0.917748E+10 | 41237.79 | 03-NOV-07:02 | 21388.77 | 0.00 |
December | 0.00 | 0.00 | 0.756752E+10 | 0.551083E+10 | 38838.41 | 12-DEC-08:62 | 27772.83 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.186355E+12 | 0.129617E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.495856E+10 | 0.382777E+10 | 25534.96 | 17132.98 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.280463E+11 | 0.176292E+11 | 42512.45 | 27772.83 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.912903E+10 | 0.692398E+10 | 71777.01 | 29-JAN-10:02 | 49740.99 | 0.00 |
February | 0.00 | 0.00 | 0.110900E+11 | 0.832869E+10 | 69219.04 | 05-FEB-10:02 | 57064.46 | 0.00 |
March | 0.00 | 0.00 | 0.159954E+11 | 0.125878E+11 | 72086.99 | 01-MAR-09:01 | 49712.77 | 0.00 |
April | 0.00 | 0.00 | 0.220385E+11 | 0.170146E+11 | 75543.27 | 30-APR-09:02 | 40895.14 | 0.00 |
May | 0.00 | 0.00 | 0.334154E+11 | 0.255332E+11 | 76964.66 | 01-MAY-08:62 | 33968.55 | 0.00 |
June | 0.00 | 0.00 | 0.406543E+11 | 0.275985E+11 | 78195.41 | 08-JUN-08:61 | 34368.73 | 0.00 |
July | 0.00 | 0.00 | 0.485826E+11 | 0.312955E+11 | 77476.26 | 18-JUL-07:01 | 39212.04 | 0.00 |
August | 0.00 | 0.00 | 0.526775E+11 | 0.329710E+11 | 77536.08 | 08-AUG-07:01 | 37294.34 | 0.00 |
September | 0.00 | 0.00 | 0.432811E+11 | 0.274909E+11 | 78224.85 | 25-SEP-08:03 | 31005.85 | 0.00 |
October | 0.00 | 0.00 | 0.338922E+11 | 0.238143E+11 | 78189.63 | 07-OCT-08:61 | 34259.46 | 0.00 |
November | 0.00 | 0.00 | 0.237738E+11 | 0.169167E+11 | 75715.63 | 03-NOV-08:61 | 40767.17 | 0.00 |
December | 0.00 | 0.00 | 0.140080E+11 | 0.100403E+11 | 72036.31 | 10-DEC-10:01 | 50596.49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.348538E+12 | 0.240516E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.912903E+10 | 0.692398E+10 | 69219.04 | 31005.85 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.526775E+11 | 0.329710E+11 | 78224.85 | 57064.46 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.474079E+10 | 0.360050E+10 | 37989.79 | 29-JAN-10:02 | 26311.00 | 0.00 |
February | 0.00 | 0.00 | 0.576269E+10 | 0.433377E+10 | 36612.70 | 05-FEB-10:02 | 30135.70 | 0.00 |
March | 0.00 | 0.00 | 0.831988E+10 | 0.655429E+10 | 38126.87 | 01-MAR-09:01 | 26241.48 | 0.00 |
April | 0.00 | 0.00 | 0.114936E+11 | 0.887444E+10 | 39990.61 | 30-APR-09:02 | 21604.49 | 0.00 |
May | 0.00 | 0.00 | 0.174327E+11 | 0.133125E+11 | 40765.05 | 01-MAY-08:62 | 17963.29 | 0.00 |
June | 0.00 | 0.00 | 0.211835E+11 | 0.143760E+11 | 41355.36 | 08-JUN-08:61 | 18210.89 | 0.00 |
July | 0.00 | 0.00 | 0.253211E+11 | 0.163055E+11 | 40960.56 | 05-JUL-07:01 | 15873.58 | 0.00 |
August | 0.00 | 0.00 | 0.274309E+11 | 0.171611E+11 | 41036.27 | 08-AUG-07:01 | 19770.78 | 0.00 |
September | 0.00 | 0.00 | 0.225514E+11 | 0.143273E+11 | 41400.80 | 25-SEP-08:03 | 16309.97 | 0.00 |
October | 0.00 | 0.00 | 0.176732E+11 | 0.124271E+11 | 41382.17 | 07-OCT-08:61 | 18180.16 | 0.00 |
November | 0.00 | 0.00 | 0.123988E+11 | 0.883043E+10 | 40048.62 | 03-NOV-08:61 | 21601.94 | 0.00 |
December | 0.00 | 0.00 | 0.729361E+10 | 0.523457E+10 | 38118.15 | 10-DEC-10:01 | 26722.32 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.181602E+12 | 0.125337E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.474079E+10 | 0.360050E+10 | 36612.70 | 15873.58 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.274309E+11 | 0.171611E+11 | 41400.80 | 30135.70 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.467668E+10 | 0.354889E+10 | 37858.34 | 29-JAN-10:02 | 26194.75 | 0.00 |
February | 0.00 | 0.00 | 0.570053E+10 | 0.428481E+10 | 36484.59 | 05-FEB-10:02 | 30005.41 | 0.00 |
March | 0.00 | 0.00 | 0.825192E+10 | 0.649847E+10 | 37996.23 | 01-MAR-09:01 | 26120.02 | 0.00 |
April | 0.00 | 0.00 | 0.114334E+11 | 0.882496E+10 | 39854.75 | 30-APR-09:02 | 21508.98 | 0.00 |
May | 0.00 | 0.00 | 0.173772E+11 | 0.132661E+11 | 40626.45 | 01-MAY-08:62 | 17881.30 | 0.00 |
June | 0.00 | 0.00 | 0.211275E+11 | 0.143318E+11 | 41218.30 | 08-JUN-08:61 | 18117.01 | 0.00 |
July | 0.00 | 0.00 | 0.252694E+11 | 0.162651E+11 | 40823.59 | 05-JUL-07:01 | 15812.03 | 0.00 |
August | 0.00 | 0.00 | 0.273781E+11 | 0.171202E+11 | 40899.05 | 08-AUG-07:01 | 19683.17 | 0.00 |
September | 0.00 | 0.00 | 0.225023E+11 | 0.142894E+11 | 41262.36 | 25-SEP-08:61 | 16347.90 | 0.00 |
October | 0.00 | 0.00 | 0.176241E+11 | 0.123874E+11 | 41243.79 | 07-OCT-08:61 | 18089.65 | 0.00 |
November | 0.00 | 0.00 | 0.123460E+11 | 0.878829E+10 | 39915.44 | 03-NOV-08:61 | 21501.98 | 0.00 |
December | 0.00 | 0.00 | 0.723249E+10 | 0.518697E+10 | 37987.05 | 10-DEC-10:01 | 26608.18 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.180920E+12 | 0.124792E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.467668E+10 | 0.354889E+10 | 36484.59 | 15812.03 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.273781E+11 | 0.171202E+11 | 41262.36 | 30005.41 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.454082E+10 | 0.343978E+10 | 37998.28 | 29-JAN-10:02 | 26219.65 | 0.00 |
February | 0.00 | 0.00 | 0.557332E+10 | 0.418550E+10 | 36613.58 | 05-FEB-10:02 | 30036.10 | 0.00 |
March | 0.00 | 0.00 | 0.813175E+10 | 0.640014E+10 | 38141.03 | 01-MAR-09:01 | 26135.11 | 0.00 |
April | 0.00 | 0.00 | 0.113743E+11 | 0.877715E+10 | 40010.32 | 30-APR-09:02 | 21552.90 | 0.00 |
May | 0.00 | 0.00 | 0.174204E+11 | 0.133024E+11 | 40789.57 | 01-MAY-08:62 | 17921.82 | 0.00 |
June | 0.00 | 0.00 | 0.212172E+11 | 0.144036E+11 | 41381.48 | 08-JUN-08:61 | 18175.46 | 0.00 |
July | 0.00 | 0.00 | 0.254247E+11 | 0.163888E+11 | 40993.48 | 05-JUL-07:01 | 15939.28 | 0.00 |
August | 0.00 | 0.00 | 0.275769E+11 | 0.172777E+11 | 41069.26 | 08-AUG-07:01 | 19852.49 | 0.00 |
September | 0.00 | 0.00 | 0.226429E+11 | 0.144001E+11 | 41434.08 | 25-SEP-08:03 | 16367.05 | 0.00 |
October | 0.00 | 0.00 | 0.177167E+11 | 0.124626E+11 | 41415.43 | 07-OCT-08:61 | 18194.44 | 0.00 |
November | 0.00 | 0.00 | 0.123582E+11 | 0.879846E+10 | 40076.48 | 03-NOV-08:61 | 21591.32 | 0.00 |
December | 0.00 | 0.00 | 0.713946E+10 | 0.511526E+10 | 38133.14 | 10-DEC-10:01 | 26660.59 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.181117E+12 | 0.124952E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.454082E+10 | 0.343978E+10 | 36613.58 | 15939.28 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.275769E+11 | 0.172777E+11 | 41434.08 | 30036.10 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.484230E+10 | 0.372456E+10 | 42567.55 | 29-JAN-10:02 | 29582.00 | 0.00 |
February | 0.00 | 0.00 | 0.588084E+10 | 0.448164E+10 | 40873.16 | 05-FEB-10:02 | 33978.87 | 0.00 |
March | 0.00 | 0.00 | 0.861385E+10 | 0.686841E+10 | 42837.51 | 01-MAR-09:01 | 28776.53 | 0.00 |
April | 0.00 | 0.00 | 0.123043E+11 | 0.962053E+10 | 45028.46 | 30-APR-09:02 | 23594.99 | 0.00 |
May | 0.00 | 0.00 | 0.192128E+11 | 0.148790E+11 | 45573.65 | 01-MAY-08:62 | 20272.07 | 0.00 |
June | 0.00 | 0.00 | 0.234606E+11 | 0.162149E+11 | 46296.11 | 08-JUN-08:03 | 18938.85 | 0.00 |
July | 0.00 | 0.00 | 0.282016E+11 | 0.185676E+11 | 45888.48 | 26-JUL-07:01 | 20302.74 | 0.00 |
August | 0.00 | 0.00 | 0.308142E+11 | 0.198001E+11 | 45888.48 | 08-AUG-07:01 | 17379.74 | 0.00 |
September | 0.00 | 0.00 | 0.252454E+11 | 0.164514E+11 | 46296.11 | 25-SEP-08:03 | 18821.13 | 0.00 |
October | 0.00 | 0.00 | 0.197956E+11 | 0.141914E+11 | 46275.27 | 07-OCT-08:61 | 19667.04 | 0.00 |
November | 0.00 | 0.00 | 0.136762E+11 | 0.992568E+10 | 45099.73 | 03-NOV-08:61 | 23900.68 | 0.00 |
December | 0.00 | 0.00 | 0.769361E+10 | 0.560832E+10 | 42605.90 | 10-DEC-10:01 | 30330.66 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.199741E+12 | 0.140334E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.484230E+10 | 0.372456E+10 | 40873.16 | 17379.74 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.308142E+11 | 0.198001E+11 | 46296.11 | 33978.87 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.229528E+10 | 0.36 | 1318.44 | 29-JAN-08:62 | 0.54 |
February | 0.207736E+10 | 0.36 | 2671.26 | 09-FEB-09:02 | 0.80 |
March | 0.230559E+10 | 0.36 | 3162.58 | 01-MAR-09:01 | 0.87 |
April | 0.222601E+10 | 0.36 | 3162.58 | 03-APR-08:61 | 0.86 |
May | 0.232543E+10 | 0.36 | 3162.58 | 01-MAY-08:62 | 0.86 |
June | 0.239443E+10 | 0.37 | 3162.58 | 01-JUN-08:61 | 0.87 |
July | 0.269127E+10 | 0.39 | 3162.58 | 01-JUL-08:61 | 0.86 |
August | 0.279191E+10 | 0.40 | 3162.58 | 01-AUG-08:61 | 0.86 |
September | 0.247127E+10 | 0.38 | 3162.58 | 01-SEP-08:61 | 0.86 |
October | 0.233630E+10 | 0.36 | 3162.58 | 01-OCT-07:01 | 0.86 |
November | 0.222581E+10 | 0.36 | 3162.58 | 01-NOV-08:61 | 0.86 |
December | 0.230497E+10 | 0.36 | 3162.58 | 12-DEC-09:02 | 0.87 |
Annual Sum or Average | 0.284456E+11 | 0.37 | |||
Minimum of Months | 0.207736E+10 | 0.36 | 1318.44 | 0.54 | |
Maximum of Months | 0.279191E+10 | 0.40 | 3162.58 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.935307E+09 | 0.37 | 766.86 | 29-JAN-08:62 | 0.59 |
February | 0.852389E+09 | 0.37 | 1321.80 | 07-FEB-09:02 | 0.80 |
March | 0.959564E+09 | 0.37 | 1595.77 | 01-MAR-09:01 | 0.87 |
April | 0.940652E+09 | 0.37 | 1595.77 | 03-APR-08:61 | 0.87 |
May | 0.102085E+10 | 0.37 | 1595.77 | 01-MAY-08:62 | 0.86 |
June | 0.108573E+10 | 0.38 | 1595.77 | 01-JUN-08:61 | 0.87 |
July | 0.124498E+10 | 0.39 | 1595.77 | 01-JUL-08:61 | 0.86 |
August | 0.129971E+10 | 0.40 | 1595.77 | 01-AUG-08:61 | 0.86 |
September | 0.112482E+10 | 0.38 | 1595.77 | 01-SEP-08:61 | 0.86 |
October | 0.102358E+10 | 0.37 | 1595.77 | 01-OCT-07:01 | 0.86 |
November | 0.944142E+09 | 0.37 | 1595.77 | 01-NOV-08:61 | 0.86 |
December | 0.945813E+09 | 0.37 | 1595.77 | 12-DEC-09:02 | 0.87 |
Annual Sum or Average | 0.123775E+11 | 0.37 | |||
Minimum of Months | 0.852389E+09 | 0.37 | 766.86 | 0.59 | |
Maximum of Months | 0.129971E+10 | 0.40 | 1595.77 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.919781E+09 | 0.29 | 1040.49 | 29-JAN-09:02 | 0.71 |
February | 0.833049E+09 | 0.29 | 1415.93 | 09-FEB-08:62 | 0.82 |
March | 0.938610E+09 | 0.29 | 1588.79 | 01-MAR-08:62 | 0.87 |
April | 0.894042E+09 | 0.29 | 1588.79 | 03-APR-07:02 | 0.87 |
May | 0.946381E+09 | 0.29 | 1588.79 | 01-MAY-07:02 | 0.86 |
June | 0.992780E+09 | 0.30 | 1588.79 | 01-JUN-07:01 | 0.87 |
July | 0.111648E+10 | 0.32 | 1588.79 | 01-JUL-07:01 | 0.86 |
August | 0.118188E+10 | 0.33 | 1588.79 | 01-AUG-07:01 | 0.86 |
September | 0.101551E+10 | 0.31 | 1588.79 | 01-SEP-07:01 | 0.86 |
October | 0.941513E+09 | 0.29 | 1588.79 | 01-OCT-08:61 | 0.86 |
November | 0.895503E+09 | 0.29 | 1588.79 | 01-NOV-07:02 | 0.86 |
December | 0.915452E+09 | 0.28 | 1588.79 | 12-DEC-08:62 | 0.87 |
Annual Sum or Average | 0.115910E+11 | 0.30 | |||
Minimum of Months | 0.833049E+09 | 0.28 | 1040.49 | 0.71 | |
Maximum of Months | 0.118188E+10 | 0.33 | 1588.79 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.921669E+09 | 0.29 | 1020.93 | 29-JAN-09:02 | 0.70 |
February | 0.834767E+09 | 0.29 | 1418.94 | 09-FEB-08:62 | 0.82 |
March | 0.940544E+09 | 0.29 | 1592.06 | 01-MAR-08:62 | 0.87 |
April | 0.895932E+09 | 0.29 | 1592.06 | 03-APR-07:02 | 0.87 |
May | 0.949009E+09 | 0.29 | 1592.06 | 01-MAY-07:02 | 0.86 |
June | 0.996618E+09 | 0.30 | 1592.06 | 01-JUN-07:01 | 0.87 |
July | 0.112239E+10 | 0.32 | 1592.06 | 01-JUL-07:01 | 0.86 |
August | 0.118790E+10 | 0.33 | 1592.06 | 01-AUG-07:01 | 0.86 |
September | 0.101997E+10 | 0.31 | 1592.06 | 01-SEP-07:01 | 0.86 |
October | 0.944037E+09 | 0.29 | 1592.06 | 01-OCT-08:61 | 0.86 |
November | 0.897397E+09 | 0.29 | 1592.06 | 01-NOV-07:02 | 0.86 |
December | 0.917338E+09 | 0.28 | 1592.06 | 12-DEC-08:62 | 0.87 |
Annual Sum or Average | 0.116276E+11 | 0.30 | |||
Minimum of Months | 0.834767E+09 | 0.28 | 1020.93 | 0.70 | |
Maximum of Months | 0.118790E+10 | 0.33 | 1592.06 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.919916E+09 | 0.29 | 936.72 | 29-JAN-09:02 | 0.67 |
February | 0.833139E+09 | 0.29 | 1321.39 | 09-FEB-08:62 | 0.79 |
March | 0.938748E+09 | 0.29 | 1589.05 | 01-MAR-08:62 | 0.87 |
April | 0.894087E+09 | 0.29 | 1589.05 | 03-APR-07:02 | 0.87 |
May | 0.946893E+09 | 0.29 | 1589.05 | 01-MAY-07:02 | 0.86 |
June | 0.993043E+09 | 0.30 | 1589.05 | 01-JUN-07:01 | 0.87 |
July | 0.111873E+10 | 0.32 | 1589.05 | 01-JUL-07:01 | 0.86 |
August | 0.118366E+10 | 0.33 | 1589.05 | 01-AUG-07:01 | 0.86 |
September | 0.101637E+10 | 0.31 | 1589.05 | 01-SEP-07:01 | 0.86 |
October | 0.941711E+09 | 0.29 | 1589.05 | 01-OCT-08:61 | 0.86 |
November | 0.895502E+09 | 0.29 | 1589.05 | 01-NOV-07:02 | 0.86 |
December | 0.915584E+09 | 0.28 | 1589.05 | 12-DEC-08:62 | 0.87 |
Annual Sum or Average | 0.115974E+11 | 0.30 | |||
Minimum of Months | 0.833139E+09 | 0.28 | 936.72 | 0.67 | |
Maximum of Months | 0.118366E+10 | 0.33 | 1589.05 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.156175E+10 | 0.26 | 2922.91 | 29-JAN-10:02 | 0.87 |
February | 0.141506E+10 | 0.26 | 2922.91 | 05-FEB-10:02 | 0.87 |
March | 0.159657E+10 | 0.27 | 2922.91 | 01-MAR-09:01 | 0.87 |
April | 0.151998E+10 | 0.26 | 2922.91 | 02-APR-09:01 | 0.87 |
May | 0.162536E+10 | 0.27 | 2922.91 | 01-MAY-08:62 | 0.86 |
June | 0.174272E+10 | 0.29 | 2922.91 | 01-JUN-08:61 | 0.87 |
July | 0.198968E+10 | 0.30 | 2922.91 | 01-JUL-08:61 | 0.86 |
August | 0.211379E+10 | 0.31 | 2922.91 | 01-AUG-08:61 | 0.86 |
September | 0.179666E+10 | 0.29 | 2922.91 | 01-SEP-08:61 | 0.86 |
October | 0.161681E+10 | 0.27 | 2922.91 | 01-OCT-09:01 | 0.86 |
November | 0.152463E+10 | 0.26 | 2922.91 | 01-NOV-08:61 | 0.86 |
December | 0.155413E+10 | 0.26 | 2922.91 | 10-DEC-10:01 | 0.87 |
Annual Sum or Average | 0.200571E+11 | 0.28 | |||
Minimum of Months | 0.141506E+10 | 0.26 | 2922.91 | 0.86 | |
Maximum of Months | 0.211379E+10 | 0.31 | 2922.91 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.826559E+09 | 0.26 | 1546.96 | 29-JAN-10:02 | 0.87 |
February | 0.748873E+09 | 0.26 | 1546.96 | 05-FEB-10:02 | 0.87 |
March | 0.844925E+09 | 0.27 | 1546.96 | 01-MAR-09:01 | 0.87 |
April | 0.804266E+09 | 0.26 | 1546.96 | 02-APR-09:01 | 0.87 |
May | 0.858976E+09 | 0.27 | 1546.96 | 01-MAY-08:62 | 0.86 |
June | 0.918578E+09 | 0.29 | 1546.96 | 01-JUN-08:61 | 0.87 |
July | 0.104663E+10 | 0.30 | 1546.96 | 01-JUL-08:61 | 0.86 |
August | 0.111025E+10 | 0.31 | 1546.96 | 01-AUG-08:61 | 0.86 |
September | 0.945517E+09 | 0.29 | 1546.96 | 01-SEP-08:61 | 0.86 |
October | 0.853823E+09 | 0.27 | 1546.96 | 01-OCT-09:01 | 0.86 |
November | 0.806598E+09 | 0.26 | 1546.96 | 01-NOV-08:61 | 0.86 |
December | 0.822469E+09 | 0.26 | 1546.96 | 10-DEC-10:01 | 0.87 |
Annual Sum or Average | 0.105875E+11 | 0.28 | |||
Minimum of Months | 0.748873E+09 | 0.26 | 1546.96 | 0.86 | |
Maximum of Months | 0.111025E+10 | 0.31 | 1546.96 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.823796E+09 | 0.26 | 1541.79 | 29-JAN-10:02 | 0.87 |
February | 0.746357E+09 | 0.26 | 1541.79 | 05-FEB-10:02 | 0.87 |
March | 0.842091E+09 | 0.27 | 1541.79 | 01-MAR-09:01 | 0.87 |
April | 0.801552E+09 | 0.26 | 1541.79 | 02-APR-09:01 | 0.87 |
May | 0.856270E+09 | 0.27 | 1541.79 | 01-MAY-08:62 | 0.86 |
June | 0.916079E+09 | 0.29 | 1541.79 | 01-JUN-08:61 | 0.87 |
July | 0.104429E+10 | 0.30 | 1541.79 | 01-JUL-08:61 | 0.86 |
August | 0.110786E+10 | 0.31 | 1541.79 | 01-AUG-08:61 | 0.86 |
September | 0.943216E+09 | 0.29 | 1541.79 | 01-SEP-08:61 | 0.86 |
October | 0.851172E+09 | 0.27 | 1541.79 | 01-OCT-09:01 | 0.86 |
November | 0.803897E+09 | 0.26 | 1541.79 | 01-NOV-08:61 | 0.86 |
December | 0.819709E+09 | 0.26 | 1541.79 | 10-DEC-10:01 | 0.87 |
Annual Sum or Average | 0.105563E+11 | 0.28 | |||
Minimum of Months | 0.746357E+09 | 0.26 | 1541.79 | 0.86 | |
Maximum of Months | 0.110786E+10 | 0.31 | 1541.79 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.827224E+09 | 0.26 | 1548.20 | 29-JAN-10:02 | 0.87 |
February | 0.749417E+09 | 0.26 | 1548.20 | 05-FEB-10:02 | 0.87 |
March | 0.845548E+09 | 0.27 | 1548.20 | 01-MAR-09:01 | 0.87 |
April | 0.804752E+09 | 0.26 | 1548.20 | 02-APR-09:01 | 0.87 |
May | 0.859695E+09 | 0.27 | 1548.20 | 01-MAY-08:62 | 0.86 |
June | 0.920010E+09 | 0.29 | 1548.20 | 01-JUN-08:61 | 0.87 |
July | 0.105024E+10 | 0.30 | 1548.20 | 01-JUL-08:61 | 0.86 |
August | 0.111521E+10 | 0.31 | 1548.20 | 01-AUG-08:61 | 0.86 |
September | 0.948590E+09 | 0.29 | 1548.20 | 01-SEP-08:61 | 0.86 |
October | 0.854971E+09 | 0.27 | 1548.20 | 01-OCT-09:01 | 0.86 |
November | 0.807168E+09 | 0.26 | 1548.20 | 01-NOV-08:61 | 0.86 |
December | 0.823076E+09 | 0.26 | 1548.20 | 10-DEC-10:01 | 0.87 |
Annual Sum or Average | 0.106059E+11 | 0.28 | |||
Minimum of Months | 0.749417E+09 | 0.26 | 1548.20 | 0.86 | |
Maximum of Months | 0.111521E+10 | 0.31 | 1548.20 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.950962E+09 | 0.26 | 1779.79 | 29-JAN-10:02 | 0.87 |
February | 0.861391E+09 | 0.26 | 1779.79 | 05-FEB-10:02 | 0.87 |
March | 0.971859E+09 | 0.27 | 1779.79 | 01-MAR-09:01 | 0.87 |
April | 0.924628E+09 | 0.26 | 1779.79 | 02-APR-09:01 | 0.87 |
May | 0.984260E+09 | 0.27 | 1779.79 | 01-MAY-08:62 | 0.86 |
June | 0.104695E+10 | 0.28 | 1779.79 | 01-JUN-08:61 | 0.87 |
July | 0.119696E+10 | 0.30 | 1779.79 | 01-JUL-08:61 | 0.86 |
August | 0.127974E+10 | 0.31 | 1779.79 | 01-AUG-07:01 | 0.86 |
September | 0.108501E+10 | 0.29 | 1779.79 | 01-SEP-08:61 | 0.86 |
October | 0.980687E+09 | 0.27 | 1779.79 | 01-OCT-08:61 | 0.85 |
November | 0.927400E+09 | 0.26 | 1779.79 | 01-NOV-08:61 | 0.86 |
December | 0.946116E+09 | 0.26 | 1779.79 | 10-DEC-10:01 | 0.87 |
Annual Sum or Average | 0.121560E+11 | 0.28 | |||
Minimum of Months | 0.861391E+09 | 0.26 | 1779.79 | 0.85 | |
Maximum of Months | 0.127974E+10 | 0.31 | 1779.79 | 0.87 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.647627E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.688629E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.904349E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.116914E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.165308E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.191576E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.229328E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.240415E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.200525E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.162465E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.118597E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.832718E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.173246E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.647627E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.240415E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.299972E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.314922E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.406387E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.512504E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.715549E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.827673E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.991699E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.103939E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.862663E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.699439E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.517726E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.375125E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.756305E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.299972E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.103939E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.230457E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.248448E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.330344E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.415747E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.590327E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.688322E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.820022E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.877304E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.709395E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.571582E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.425167E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.295078E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.620219E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.230457E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.877304E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.228818E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.247543E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.330112E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.416686E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.593536E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.692443E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.825682E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.882838E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.713962E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.574934E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.426341E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.294557E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.622745E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.228818E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.882838E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.223775E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.243156E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.325455E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.412816E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.590327E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.688871E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.822841E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.879695E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.710789E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.571902E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.422993E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.289999E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.618262E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.223775E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.879695E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.402715E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.441476E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.600011E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.763463E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.110569E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.129865E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.154911E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.166589E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.134032E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.106565E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.781710E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.527877E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.115425E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.402715E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.166589E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.208643E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.228334E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.310072E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.394593E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.570858E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.669615E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.798752E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.858145E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.690919E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.550078E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.403982E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.273159E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.595715E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.208643E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.858145E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.206732E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.226506E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.308044E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.392732E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.568975E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.667708E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.796917E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.856254E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.689260E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.548421E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.402330E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.271350E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.593523E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.206732E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.856254E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.203686E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.223717E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.305539E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.391866E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.570701E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.670695E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.801968E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.862602E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.693635E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.551266E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.403146E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.269507E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.594833E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.203686E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.862602E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.226794E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.246779E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.336967E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.437616E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.645689E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.759756E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.911870E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.988268E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.792246E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.629947E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.457324E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.300832E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.673409E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.226794E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.988268E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.229528E+10 | 0.141381E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.207736E+10 | 0.162142E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.230559E+10 | 0.223431E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.222601E+10 | 0.310991E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.232543E+10 | 0.456752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.239443E+10 | 0.553848E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.269127E+10 | 0.663582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.279191E+10 | 0.701147E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.247127E+10 | 0.598185E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.233630E+10 | 0.472029E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.222581E+10 | 0.328935E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.230497E+10 | 0.206296E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.284456E+11 | 0.481872E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.207736E+10 | 0.141381E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.279191E+10 | 0.701147E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.935307E+09 | 0.782833E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.852389E+09 | 0.867765E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.959564E+09 | 0.115144E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.940652E+09 | 0.152956E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.102085E+10 | 0.218059E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.108573E+10 | 0.261181E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.124498E+10 | 0.312308E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.129971E+10 | 0.329878E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.112482E+10 | 0.280427E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.102358E+10 | 0.223729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.944142E+09 | 0.160856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.945813E+09 | 0.107458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.123775E+11 | 0.232705E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.852389E+09 | 0.782833E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.129971E+10 | 0.329878E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.919781E+09 | 0.522735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.833049E+09 | 0.621219E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.938610E+09 | 0.873155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.894042E+09 | 0.119201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.946381E+09 | 0.177979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.992780E+09 | 0.216282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.111648E+10 | 0.259209E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.118188E+10 | 0.279574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.101551E+10 | 0.230199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.941513E+09 | 0.181595E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.895503E+09 | 0.128473E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.915452E+09 | 0.778009E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.115910E+11 | 0.187202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.833049E+09 | 0.522735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.118188E+10 | 0.279574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.921669E+09 | 0.515307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.834767E+09 | 0.616709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.940544E+09 | 0.871195E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.895932E+09 | 0.119476E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.949009E+09 | 0.179126E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.996618E+09 | 0.217717E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.112239E+10 | 0.261113E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.118790E+10 | 0.281429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.101997E+10 | 0.231797E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.944037E+09 | 0.182879E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.897397E+09 | 0.128865E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.917338E+09 | 0.774896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.116276E+11 | 0.188021E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.834767E+09 | 0.515307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.118790E+10 | 0.281429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.919916E+09 | 0.495856E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.833139E+09 | 0.599580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.938748E+09 | 0.852953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.894087E+09 | 0.117941E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.946893E+09 | 0.177940E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.993043E+09 | 0.216503E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.111873E+10 | 0.260229E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.118366E+10 | 0.280463E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.101637E+10 | 0.230732E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.941711E+09 | 0.181727E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.895502E+09 | 0.127495E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.915584E+09 | 0.756752E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.115974E+11 | 0.186355E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.833139E+09 | 0.495856E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.118366E+10 | 0.280463E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.156175E+10 | 0.912903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.141506E+10 | 0.110900E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159657E+10 | 0.159954E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.151998E+10 | 0.220385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.162536E+10 | 0.334154E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.174272E+10 | 0.406543E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.198968E+10 | 0.485826E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.211379E+10 | 0.526775E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.179666E+10 | 0.432811E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.161681E+10 | 0.338922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152463E+10 | 0.237738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.155413E+10 | 0.140080E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.200571E+11 | 0.348538E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.141506E+10 | 0.912903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.211379E+10 | 0.526775E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.826559E+09 | 0.474079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.748873E+09 | 0.576269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.844925E+09 | 0.831988E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.804266E+09 | 0.114936E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.858976E+09 | 0.174327E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.918578E+09 | 0.211835E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.104663E+10 | 0.253211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.111025E+10 | 0.274309E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.945517E+09 | 0.225514E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.853823E+09 | 0.176732E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.806598E+09 | 0.123988E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.822469E+09 | 0.729361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105875E+11 | 0.181602E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.748873E+09 | 0.474079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.111025E+10 | 0.274309E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.823796E+09 | 0.467668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.746357E+09 | 0.570053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.842091E+09 | 0.825192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.801552E+09 | 0.114334E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.856270E+09 | 0.173772E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.916079E+09 | 0.211275E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.104429E+10 | 0.252694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.110786E+10 | 0.273781E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.943216E+09 | 0.225023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.851172E+09 | 0.176241E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.803897E+09 | 0.123460E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.819709E+09 | 0.723249E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105563E+11 | 0.180920E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.746357E+09 | 0.467668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.110786E+10 | 0.273781E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.827224E+09 | 0.454082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.749417E+09 | 0.557332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.845548E+09 | 0.813175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.804752E+09 | 0.113743E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.859695E+09 | 0.174204E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.920010E+09 | 0.212172E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.105024E+10 | 0.254247E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.111521E+10 | 0.275769E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.948590E+09 | 0.226429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.854971E+09 | 0.177167E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.807168E+09 | 0.123582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.823076E+09 | 0.713946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.106059E+11 | 0.181117E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.749417E+09 | 0.454082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.111521E+10 | 0.275769E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.950962E+09 | 0.484230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.861391E+09 | 0.588084E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.971859E+09 | 0.861385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.924628E+09 | 0.123043E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.984260E+09 | 0.192128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.104695E+10 | 0.234606E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.119696E+10 | 0.282016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.127974E+10 | 0.308142E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.108501E+10 | 0.252454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.980687E+09 | 0.197956E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.927400E+09 | 0.136762E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.946116E+09 | 0.769361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.121560E+11 | 0.199741E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.861391E+09 | 0.484230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.127974E+10 | 0.308142E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.229528E+10 | 0.00 | 0.00 | 0.00 | 0.418098E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.207736E+10 | 0.00 | 0.00 | 0.00 | 0.480893E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.230559E+10 | 0.00 | 0.00 | 0.00 | 0.673790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.222601E+10 | 0.00 | 0.00 | 0.00 | 0.946535E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.232543E+10 | 0.00 | 0.00 | 0.00 | 0.142054E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.239443E+10 | 0.00 | 0.00 | 0.00 | 0.167632E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.269127E+10 | 0.00 | 0.00 | 0.00 | 0.202416E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.279191E+10 | 0.00 | 0.00 | 0.00 | 0.212496E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.247127E+10 | 0.00 | 0.00 | 0.00 | 0.175812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.233630E+10 | 0.00 | 0.00 | 0.00 | 0.139102E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.222581E+10 | 0.00 | 0.00 | 0.00 | 0.963393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.230497E+10 | 0.00 | 0.00 | 0.00 | 0.602221E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.284456E+11 | 0.00 | 0.00 | 0.00 | 0.144800E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.207736E+10 | 0.00 | 0.00 | 0.00 | 0.418098E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.279191E+10 | 0.00 | 0.00 | 0.00 | 0.212496E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.935307E+09 | 0.00 | 0.00 | 0.00 | 0.206441E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.852389E+09 | 0.00 | 0.00 | 0.00 | 0.229683E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.959564E+09 | 0.00 | 0.00 | 0.00 | 0.310430E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.940652E+09 | 0.00 | 0.00 | 0.00 | 0.418439E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.102085E+10 | 0.00 | 0.00 | 0.00 | 0.613464E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.108573E+10 | 0.00 | 0.00 | 0.00 | 0.719099E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.124498E+10 | 0.00 | 0.00 | 0.00 | 0.867201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.129971E+10 | 0.00 | 0.00 | 0.00 | 0.909423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.112482E+10 | 0.00 | 0.00 | 0.00 | 0.750181E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.102358E+10 | 0.00 | 0.00 | 0.00 | 0.597081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.944142E+09 | 0.00 | 0.00 | 0.00 | 0.423312E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.945813E+09 | 0.00 | 0.00 | 0.00 | 0.280544E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.123775E+11 | 0.00 | 0.00 | 0.00 | 0.632530E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.852389E+09 | 0.00 | 0.00 | 0.00 | 0.206441E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.129971E+10 | 0.00 | 0.00 | 0.00 | 0.909423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.919781E+09 | 0.00 | 0.00 | 0.00 | 0.138478E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.833049E+09 | 0.00 | 0.00 | 0.00 | 0.165143E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.938610E+09 | 0.00 | 0.00 | 0.00 | 0.236483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.894042E+09 | 0.00 | 0.00 | 0.00 | 0.326343E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.946381E+09 | 0.00 | 0.00 | 0.00 | 0.495689E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.992780E+09 | 0.00 | 0.00 | 0.00 | 0.589044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.111648E+10 | 0.00 | 0.00 | 0.00 | 0.708375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.118188E+10 | 0.00 | 0.00 | 0.00 | 0.759117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.101551E+10 | 0.00 | 0.00 | 0.00 | 0.607845E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.941513E+09 | 0.00 | 0.00 | 0.00 | 0.477430E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.895503E+09 | 0.00 | 0.00 | 0.00 | 0.335616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.915452E+09 | 0.00 | 0.00 | 0.00 | 0.203532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.115910E+11 | 0.00 | 0.00 | 0.00 | 0.504310E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.833049E+09 | 0.00 | 0.00 | 0.00 | 0.138478E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.118188E+10 | 0.00 | 0.00 | 0.00 | 0.759117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.921669E+09 | 0.00 | 0.00 | 0.00 | 0.136651E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.834767E+09 | 0.00 | 0.00 | 0.00 | 0.164067E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.940544E+09 | 0.00 | 0.00 | 0.00 | 0.236058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.895932E+09 | 0.00 | 0.00 | 0.00 | 0.327093E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.949009E+09 | 0.00 | 0.00 | 0.00 | 0.498635E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.996618E+09 | 0.00 | 0.00 | 0.00 | 0.592781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.112239E+10 | 0.00 | 0.00 | 0.00 | 0.713442E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.118790E+10 | 0.00 | 0.00 | 0.00 | 0.764049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.101997E+10 | 0.00 | 0.00 | 0.00 | 0.611965E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.944037E+09 | 0.00 | 0.00 | 0.00 | 0.480530E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.897397E+09 | 0.00 | 0.00 | 0.00 | 0.336601E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.917338E+09 | 0.00 | 0.00 | 0.00 | 0.202823E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.116276E+11 | 0.00 | 0.00 | 0.00 | 0.506469E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.834767E+09 | 0.00 | 0.00 | 0.00 | 0.136651E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.118790E+10 | 0.00 | 0.00 | 0.00 | 0.764049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.919916E+09 | 0.00 | 0.00 | 0.00 | 0.131783E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.833139E+09 | 0.00 | 0.00 | 0.00 | 0.159842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.938748E+09 | 0.00 | 0.00 | 0.00 | 0.231580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.894087E+09 | 0.00 | 0.00 | 0.00 | 0.323408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.946893E+09 | 0.00 | 0.00 | 0.00 | 0.495637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.993043E+09 | 0.00 | 0.00 | 0.00 | 0.589567E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.111873E+10 | 0.00 | 0.00 | 0.00 | 0.710968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.118366E+10 | 0.00 | 0.00 | 0.00 | 0.761329E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.101637E+10 | 0.00 | 0.00 | 0.00 | 0.609152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.941711E+09 | 0.00 | 0.00 | 0.00 | 0.477731E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.895502E+09 | 0.00 | 0.00 | 0.00 | 0.333443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.915584E+09 | 0.00 | 0.00 | 0.00 | 0.198441E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.115974E+11 | 0.00 | 0.00 | 0.00 | 0.502288E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.833139E+09 | 0.00 | 0.00 | 0.00 | 0.131783E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.118366E+10 | 0.00 | 0.00 | 0.00 | 0.761329E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.156175E+10 | 0.00 | 0.00 | 0.00 | 0.246540E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.141506E+10 | 0.00 | 0.00 | 0.00 | 0.299970E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159657E+10 | 0.00 | 0.00 | 0.00 | 0.440354E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.151998E+10 | 0.00 | 0.00 | 0.00 | 0.611466E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.162536E+10 | 0.00 | 0.00 | 0.00 | 0.943152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.174272E+10 | 0.00 | 0.00 | 0.00 | 0.112437E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.198968E+10 | 0.00 | 0.00 | 0.00 | 0.135014E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.211379E+10 | 0.00 | 0.00 | 0.00 | 0.145451E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.179666E+10 | 0.00 | 0.00 | 0.00 | 0.116065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.161681E+10 | 0.00 | 0.00 | 0.00 | 0.903965E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152463E+10 | 0.00 | 0.00 | 0.00 | 0.629247E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.155413E+10 | 0.00 | 0.00 | 0.00 | 0.372464E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.200571E+11 | 0.00 | 0.00 | 0.00 | 0.953683E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.141506E+10 | 0.00 | 0.00 | 0.00 | 0.246540E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.211379E+10 | 0.00 | 0.00 | 0.00 | 0.145451E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.826559E+09 | 0.00 | 0.00 | 0.00 | 0.125987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.748873E+09 | 0.00 | 0.00 | 0.00 | 0.153447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.844925E+09 | 0.00 | 0.00 | 0.00 | 0.225580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.804266E+09 | 0.00 | 0.00 | 0.00 | 0.314166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.858976E+09 | 0.00 | 0.00 | 0.00 | 0.484960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.918578E+09 | 0.00 | 0.00 | 0.00 | 0.577757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.104663E+10 | 0.00 | 0.00 | 0.00 | 0.694090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.111025E+10 | 0.00 | 0.00 | 0.00 | 0.747121E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.945517E+09 | 0.00 | 0.00 | 0.00 | 0.596368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.853823E+09 | 0.00 | 0.00 | 0.00 | 0.464696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.806598E+09 | 0.00 | 0.00 | 0.00 | 0.323322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.822469E+09 | 0.00 | 0.00 | 0.00 | 0.190913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105875E+11 | 0.00 | 0.00 | 0.00 | 0.489841E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.748873E+09 | 0.00 | 0.00 | 0.00 | 0.125987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.111025E+10 | 0.00 | 0.00 | 0.00 | 0.747121E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.823796E+09 | 0.00 | 0.00 | 0.00 | 0.124352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.746357E+09 | 0.00 | 0.00 | 0.00 | 0.151870E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.842091E+09 | 0.00 | 0.00 | 0.00 | 0.223834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.801552E+09 | 0.00 | 0.00 | 0.00 | 0.312577E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.856270E+09 | 0.00 | 0.00 | 0.00 | 0.483348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.916079E+09 | 0.00 | 0.00 | 0.00 | 0.576100E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.104429E+10 | 0.00 | 0.00 | 0.00 | 0.692488E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.110786E+10 | 0.00 | 0.00 | 0.00 | 0.745468E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.943216E+09 | 0.00 | 0.00 | 0.00 | 0.594939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.851172E+09 | 0.00 | 0.00 | 0.00 | 0.463304E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.803897E+09 | 0.00 | 0.00 | 0.00 | 0.321940E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.819709E+09 | 0.00 | 0.00 | 0.00 | 0.189379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105563E+11 | 0.00 | 0.00 | 0.00 | 0.487960E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.746357E+09 | 0.00 | 0.00 | 0.00 | 0.124352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.110786E+10 | 0.00 | 0.00 | 0.00 | 0.745468E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.827224E+09 | 0.00 | 0.00 | 0.00 | 0.120964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.749417E+09 | 0.00 | 0.00 | 0.00 | 0.148776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.845548E+09 | 0.00 | 0.00 | 0.00 | 0.220984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.804752E+09 | 0.00 | 0.00 | 0.00 | 0.311390E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.859695E+09 | 0.00 | 0.00 | 0.00 | 0.484732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.920010E+09 | 0.00 | 0.00 | 0.00 | 0.578694E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.105024E+10 | 0.00 | 0.00 | 0.00 | 0.696943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.111521E+10 | 0.00 | 0.00 | 0.00 | 0.751082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.948590E+09 | 0.00 | 0.00 | 0.00 | 0.598776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.854971E+09 | 0.00 | 0.00 | 0.00 | 0.465769E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.807168E+09 | 0.00 | 0.00 | 0.00 | 0.322429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.823076E+09 | 0.00 | 0.00 | 0.00 | 0.187199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.106059E+11 | 0.00 | 0.00 | 0.00 | 0.488774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.749417E+09 | 0.00 | 0.00 | 0.00 | 0.120964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.111521E+10 | 0.00 | 0.00 | 0.00 | 0.751082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.950962E+09 | 0.00 | 0.00 | 0.00 | 0.131698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.861391E+09 | 0.00 | 0.00 | 0.00 | 0.160640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.971859E+09 | 0.00 | 0.00 | 0.00 | 0.239781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.924628E+09 | 0.00 | 0.00 | 0.00 | 0.345153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.984260E+09 | 0.00 | 0.00 | 0.00 | 0.547263E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.104695E+10 | 0.00 | 0.00 | 0.00 | 0.655061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.119696E+10 | 0.00 | 0.00 | 0.00 | 0.792174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.127974E+10 | 0.00 | 0.00 | 0.00 | 0.860294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.108501E+10 | 0.00 | 0.00 | 0.00 | 0.683744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.980687E+09 | 0.00 | 0.00 | 0.00 | 0.531878E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.927400E+09 | 0.00 | 0.00 | 0.00 | 0.364584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.946116E+09 | 0.00 | 0.00 | 0.00 | 0.206221E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.121560E+11 | 0.00 | 0.00 | 0.00 | 0.551849E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.861391E+09 | 0.00 | 0.00 | 0.00 | 0.131698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.127974E+10 | 0.00 | 0.00 | 0.00 | 0.860294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.556938E+09 | 0.712531E+09 | 0.00 | 10951778.34 | 4916212.50 | 0.00 | 0.158999E+10 | 0.00 | 0.57 |
February | 0.294795E+09 | 0.177471E+10 | 0.00 | 6819861.41 | 6126596.27 | 0.00 | 0.861204E+09 | 0.00 | 0.57 |
March | 0.252452E+09 | 0.370464E+10 | 0.00 | 3971677.20 | 13942419.23 | 0.00 | 0.388289E+09 | 0.00 | 0.57 |
April | 0.131478E+09 | 0.846639E+10 | 0.00 | 887790.34 | 81714899.43 | 0.00 | 53538768.50 | 0.00 | 0.57 |
May | 28490962.69 | 0.156063E+11 | 0.00 | 360518.93 | 0.136745E+09 | 0.00 | 6405569.69 | 0.00 | 0.58 |
June | 6719439.86 | 0.219389E+11 | 0.00 | 185636.37 | 0.112095E+09 | 0.00 | 9677288.68 | 0.00 | 0.58 |
July | 140530.93 | 0.273694E+11 | 0.00 | 54939.90 | 0.124432E+09 | 0.00 | 1201519.75 | 0.00 | 0.58 |
August | 0.00 | 0.291852E+11 | 0.00 | 0.00 | 0.148364E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
September | 2269470.84 | 0.240588E+11 | 0.00 | 80112.28 | 0.146323E+09 | 0.00 | 6180196.35 | 0.00 | 0.58 |
October | 24535252.20 | 0.159247E+11 | 0.00 | 573353.12 | 0.276680E+09 | 0.00 | 8694177.40 | 0.00 | 0.57 |
November | 29562341.61 | 0.836461E+10 | 0.00 | 672107.77 | 0.171726E+09 | 0.00 | 5250319.87 | 0.00 | 0.57 |
December | 0.238468E+09 | 0.283108E+10 | 0.00 | 6549906.13 | 11942330.34 | 0.00 | 0.698568E+09 | 0.00 | 0.57 |
Annual Sum or Average | 0.156585E+10 | 0.159937E+12 | 0.00 | 31107681.80 | 0.123501E+10 | 0.00 | 0.362900E+10 | 0.00 | 0.58 |
Minimum of Months | 0.00 | 0.712531E+09 | 0.00 | 0.00 | 4916212.50 | 0.00 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 0.556938E+09 | 0.291852E+11 | 0.00 | 10951778.34 | 0.276680E+09 | 0.00 | 0.158999E+10 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.194999E+09 | 0.360622E+09 | 0.00 | 5337939.33 | 9616820.10 | 0.00 | 0.431993E+09 | 0.00 | 0.44 |
February | 73320932.53 | 0.818117E+09 | 0.00 | 2968722.94 | 17364550.36 | 0.00 | 0.197366E+09 | 0.00 | 0.45 |
March | 63446171.72 | 0.164078E+10 | 0.00 | 1763657.33 | 24529828.49 | 0.00 | 77469061.85 | 0.00 | 0.46 |
April | 24023523.41 | 0.350648E+10 | 0.00 | 230278.89 | 95945039.84 | 0.00 | 5157755.19 | 0.00 | 0.46 |
May | 785393.47 | 0.645195E+10 | 0.00 | 0.00 | 0.126005E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
June | 316261.64 | 0.918086E+10 | 0.00 | 933.06 | 82692865.61 | 0.00 | 79817.78 | 0.00 | 0.49 |
July | 0.00 | 0.116426E+11 | 0.00 | 0.00 | 60775527.22 | 0.00 | 0.00 | 0.00 | 0.49 |
August | 0.00 | 0.125662E+11 | 0.00 | 0.00 | 79848553.68 | 0.00 | 0.00 | 0.00 | 0.50 |
September | 0.00 | 0.100760E+11 | 0.00 | 0.00 | 0.113626E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
October | 3351696.22 | 0.657338E+10 | 0.00 | 64910.20 | 0.226840E+09 | 0.00 | 336382.17 | 0.00 | 0.47 |
November | 2943775.09 | 0.358246E+10 | 0.00 | 64859.82 | 0.172088E+09 | 0.00 | 140631.97 | 0.00 | 0.46 |
December | 58140717.52 | 0.129372E+10 | 0.00 | 2971518.82 | 32429110.78 | 0.00 | 0.141030E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.421328E+09 | 0.676932E+11 | 0.00 | 13402820.38 | 0.104176E+10 | 0.00 | 0.853572E+09 | 0.00 | 0.47 |
Minimum of Months | 0.00 | 0.360622E+09 | 0.00 | 0.00 | 9616820.10 | 0.00 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 0.194999E+09 | 0.125662E+11 | 0.00 | 5337939.33 | 0.226840E+09 | 0.00 | 0.431993E+09 | 0.00 | 0.50 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.509075E+09 | 0.305378E+09 | 0.00 | 3200332.81 | 8385777.34 | 0.00 | 0.441922E+09 | 0.00 | 0.45 |
February | 0.301203E+09 | 0.687721E+09 | 0.00 | 2021595.27 | 33504682.21 | 0.00 | 0.240861E+09 | 0.00 | 0.46 |
March | 0.241826E+09 | 0.140535E+10 | 0.00 | 1323812.71 | 82087034.24 | 0.00 | 0.148651E+09 | 0.00 | 0.47 |
April | 0.155092E+09 | 0.290049E+10 | 0.00 | 776340.15 | 0.222025E+09 | 0.00 | 45198894.30 | 0.00 | 0.46 |
May | 61440701.32 | 0.532372E+10 | 0.00 | 979931.63 | 0.410751E+09 | 0.00 | 6210951.99 | 0.00 | 0.46 |
June | 8632366.40 | 0.741695E+10 | 0.00 | 241378.44 | 0.621766E+09 | 0.00 | 12067926.21 | 0.00 | 0.47 |
July | 3425122.95 | 0.945788E+10 | 0.00 | 94503.92 | 0.733197E+09 | 0.00 | 5572571.33 | 0.00 | 0.46 |
August | 887285.84 | 0.103525E+11 | 0.00 | 24725.43 | 0.818627E+09 | 0.00 | 1723293.04 | 0.00 | 0.47 |
September | 17490733.23 | 0.796893E+10 | 0.00 | 420788.38 | 0.666386E+09 | 0.00 | 8940769.37 | 0.00 | 0.46 |
October | 29945599.75 | 0.538797E+10 | 0.00 | 619066.35 | 0.480850E+09 | 0.00 | 11670846.47 | 0.00 | 0.46 |
November | 69632021.58 | 0.312409E+10 | 0.00 | 487877.77 | 0.199616E+09 | 0.00 | 7520691.41 | 0.00 | 0.46 |
December | 0.277541E+09 | 0.104135E+10 | 0.00 | 1917676.15 | 59657488.08 | 0.00 | 0.200747E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.167619E+10 | 0.553723E+11 | 0.00 | 12108029.01 | 0.433685E+10 | 0.00 | 0.113109E+10 | 0.00 | 0.46 |
Minimum of Months | 887285.84 | 0.305378E+09 | 0.00 | 24725.43 | 8385777.34 | 0.00 | 1723293.04 | 0.00 | 0.45 |
Maximum of Months | 0.509075E+09 | 0.103525E+11 | 0.00 | 3200332.81 | 0.818627E+09 | 0.00 | 0.441922E+09 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.515616E+09 | 0.301895E+09 | 0.00 | 3162600.00 | 8339900.55 | 0.00 | 0.436657E+09 | 0.00 | 0.45 |
February | 0.303015E+09 | 0.684847E+09 | 0.00 | 2007727.55 | 33390132.23 | 0.00 | 0.240525E+09 | 0.00 | 0.46 |
March | 0.244167E+09 | 0.140438E+10 | 0.00 | 1320944.02 | 82016389.55 | 0.00 | 0.146751E+09 | 0.00 | 0.47 |
April | 0.155747E+09 | 0.290323E+10 | 0.00 | 789766.67 | 0.221873E+09 | 0.00 | 45110575.37 | 0.00 | 0.46 |
May | 54974100.09 | 0.533744E+10 | 0.00 | 980508.81 | 0.409481E+09 | 0.00 | 12974550.24 | 0.00 | 0.46 |
June | 4643682.25 | 0.744677E+10 | 0.00 | 243508.72 | 0.613288E+09 | 0.00 | 15974790.79 | 0.00 | 0.47 |
July | 3374617.05 | 0.948846E+10 | 0.00 | 105428.69 | 0.731530E+09 | 0.00 | 5474608.94 | 0.00 | 0.46 |
August | 821174.46 | 0.103883E+11 | 0.00 | 23733.98 | 0.812024E+09 | 0.00 | 1578516.25 | 0.00 | 0.47 |
September | 6992515.59 | 0.799588E+10 | 0.00 | 422320.22 | 0.665064E+09 | 0.00 | 18612217.15 | 0.00 | 0.46 |
October | 29478663.18 | 0.542224E+10 | 0.00 | 638698.45 | 0.465099E+09 | 0.00 | 12352565.56 | 0.00 | 0.46 |
November | 70261558.67 | 0.312887E+10 | 0.00 | 496883.79 | 0.199256E+09 | 0.00 | 7508389.76 | 0.00 | 0.46 |
December | 0.278082E+09 | 0.103890E+10 | 0.00 | 1907958.27 | 59501389.88 | 0.00 | 0.201186E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.166717E+10 | 0.555412E+11 | 0.00 | 12100079.16 | 0.430086E+10 | 0.00 | 0.114471E+10 | 0.00 | 0.46 |
Minimum of Months | 821174.46 | 0.301895E+09 | 0.00 | 23733.98 | 8339900.55 | 0.00 | 1578516.25 | 0.00 | 0.45 |
Maximum of Months | 0.515616E+09 | 0.103883E+11 | 0.00 | 3162600.00 | 0.812024E+09 | 0.00 | 0.436657E+09 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.524410E+09 | 0.291622E+09 | 0.00 | 3044185.10 | 8263890.49 | 0.00 | 0.433286E+09 | 0.00 | 0.45 |
February | 0.306842E+09 | 0.671943E+09 | 0.00 | 1964149.64 | 32961951.61 | 0.00 | 0.242007E+09 | 0.00 | 0.46 |
March | 0.250266E+09 | 0.138962E+10 | 0.00 | 1273862.65 | 81764888.61 | 0.00 | 0.141652E+09 | 0.00 | 0.47 |
April | 0.154130E+09 | 0.288849E+10 | 0.00 | 749983.31 | 0.221526E+09 | 0.00 | 46484834.91 | 0.00 | 0.46 |
May | 60738977.64 | 0.532619E+10 | 0.00 | 974591.77 | 0.410617E+09 | 0.00 | 6708393.53 | 0.00 | 0.46 |
June | 10721640.49 | 0.742582E+10 | 0.00 | 241519.50 | 0.618563E+09 | 0.00 | 9984461.95 | 0.00 | 0.47 |
July | 3405946.90 | 0.947595E+10 | 0.00 | 100767.83 | 0.731100E+09 | 0.00 | 5553761.53 | 0.00 | 0.46 |
August | 886106.13 | 0.103739E+11 | 0.00 | 26481.62 | 0.811789E+09 | 0.00 | 1744544.19 | 0.00 | 0.47 |
September | 10070644.80 | 0.797732E+10 | 0.00 | 438460.69 | 0.666876E+09 | 0.00 | 16195115.39 | 0.00 | 0.46 |
October | 29924811.41 | 0.539703E+10 | 0.00 | 622853.23 | 0.476475E+09 | 0.00 | 11715939.06 | 0.00 | 0.46 |
November | 68918180.67 | 0.311222E+10 | 0.00 | 473552.78 | 0.199195E+09 | 0.00 | 7964948.43 | 0.00 | 0.46 |
December | 0.283587E+09 | 0.102162E+10 | 0.00 | 1863503.56 | 58952984.58 | 0.00 | 0.200210E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.170390E+10 | 0.553517E+11 | 0.00 | 11773911.67 | 0.431808E+10 | 0.00 | 0.112351E+10 | 0.00 | 0.46 |
Minimum of Months | 886106.13 | 0.291622E+09 | 0.00 | 26481.62 | 8263890.49 | 0.00 | 1744544.19 | 0.00 | 0.45 |
Maximum of Months | 0.524410E+09 | 0.103739E+11 | 0.00 | 3044185.10 | 0.811789E+09 | 0.00 | 0.433286E+09 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.591088E+09 | 0.425174E+09 | 0.00 | 6705632.35 | 13750451.85 | 0.00 | 0.100460E+10 | 0.00 | 0.42 |
February | 0.355156E+09 | 0.117217E+10 | 0.00 | 4466581.46 | 32520133.75 | 0.00 | 0.502963E+09 | 0.00 | 0.42 |
March | 0.276873E+09 | 0.261873E+10 | 0.00 | 2650016.45 | 46095027.98 | 0.00 | 0.214457E+09 | 0.00 | 0.43 |
April | 0.155811E+09 | 0.562330E+10 | 0.00 | 824648.90 | 0.225384E+09 | 0.00 | 32279402.98 | 0.00 | 0.42 |
May | 32393293.13 | 0.105891E+11 | 0.00 | 399034.33 | 0.315235E+09 | 0.00 | 24927621.44 | 0.00 | 0.43 |
June | 3867031.78 | 0.148093E+11 | 0.00 | 140094.68 | 0.373899E+09 | 0.00 | 10050187.08 | 0.00 | 0.44 |
July | 2497258.93 | 0.185646E+11 | 0.00 | 125370.70 | 0.479215E+09 | 0.00 | 1458192.76 | 0.00 | 0.43 |
August | 0.00 | 0.206197E+11 | 0.00 | 44797.24 | 0.394959E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 6544650.07 | 0.159335E+11 | 0.00 | 275684.48 | 0.461638E+09 | 0.00 | 8780984.12 | 0.00 | 0.43 |
October | 41817578.73 | 0.104997E+11 | 0.00 | 769742.23 | 0.496399E+09 | 0.00 | 15378345.55 | 0.00 | 0.42 |
November | 45676803.89 | 0.598194E+10 | 0.00 | 504299.85 | 0.234228E+09 | 0.00 | 3186863.65 | 0.00 | 0.42 |
December | 0.306108E+09 | 0.184111E+10 | 0.00 | 4046033.40 | 52494810.05 | 0.00 | 0.376189E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.181783E+10 | 0.108678E+12 | 0.00 | 20951936.07 | 0.312582E+10 | 0.00 | 0.219427E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.425174E+09 | 0.00 | 44797.24 | 13750451.85 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.591088E+09 | 0.206197E+11 | 0.00 | 6705632.35 | 0.496399E+09 | 0.00 | 0.100460E+10 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.296719E+09 | 0.213280E+09 | 0.00 | 3418783.08 | 6396817.19 | 0.00 | 0.491385E+09 | 0.00 | 0.42 |
February | 0.176715E+09 | 0.590106E+09 | 0.00 | 2261637.87 | 16374820.56 | 0.00 | 0.248152E+09 | 0.00 | 0.42 |
March | 0.136825E+09 | 0.131674E+10 | 0.00 | 1326849.46 | 23131086.94 | 0.00 | 0.105652E+09 | 0.00 | 0.43 |
April | 76663101.36 | 0.282373E+10 | 0.00 | 399099.07 | 0.111440E+09 | 0.00 | 15949574.01 | 0.00 | 0.42 |
May | 16740158.46 | 0.531289E+10 | 0.00 | 197294.69 | 0.158227E+09 | 0.00 | 11724360.64 | 0.00 | 0.43 |
June | 2383598.28 | 0.740962E+10 | 0.00 | 67328.78 | 0.196476E+09 | 0.00 | 4458501.85 | 0.00 | 0.44 |
July | 1151508.42 | 0.930518E+10 | 0.00 | 67505.24 | 0.230386E+09 | 0.00 | 882924.59 | 0.00 | 0.43 |
August | 0.00 | 0.103185E+11 | 0.00 | 26092.66 | 0.199835E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 4892752.76 | 0.797039E+10 | 0.00 | 142817.76 | 0.234033E+09 | 0.00 | 3030477.71 | 0.00 | 0.43 |
October | 21152184.04 | 0.526287E+10 | 0.00 | 387133.18 | 0.250844E+09 | 0.00 | 7160779.72 | 0.00 | 0.42 |
November | 23013333.65 | 0.300567E+10 | 0.00 | 245651.02 | 0.113170E+09 | 0.00 | 903053.82 | 0.00 | 0.42 |
December | 0.151171E+09 | 0.924202E+09 | 0.00 | 2052205.14 | 25466345.81 | 0.00 | 0.184818E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.907427E+09 | 0.544532E+11 | 0.00 | 10592397.94 | 0.156578E+10 | 0.00 | 0.107412E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.213280E+09 | 0.00 | 26092.66 | 6396817.19 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.296719E+09 | 0.103185E+11 | 0.00 | 3418783.08 | 0.250844E+09 | 0.00 | 0.491385E+09 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.300967E+09 | 0.210410E+09 | 0.00 | 3381666.18 | 6399000.98 | 0.00 | 0.490370E+09 | 0.00 | 0.42 |
February | 0.176744E+09 | 0.585773E+09 | 0.00 | 2246124.60 | 16367338.84 | 0.00 | 0.250988E+09 | 0.00 | 0.42 |
March | 0.138543E+09 | 0.131094E+10 | 0.00 | 1309645.32 | 23111923.08 | 0.00 | 0.104758E+09 | 0.00 | 0.43 |
April | 76286365.30 | 0.281758E+10 | 0.00 | 391877.73 | 0.111415E+09 | 0.00 | 16372900.06 | 0.00 | 0.42 |
May | 16791574.50 | 0.530662E+10 | 0.00 | 197175.60 | 0.158890E+09 | 0.00 | 11771527.72 | 0.00 | 0.43 |
June | 2399669.94 | 0.739303E+10 | 0.00 | 67246.32 | 0.205893E+09 | 0.00 | 4506355.78 | 0.00 | 0.44 |
July | 1152576.26 | 0.929844E+10 | 0.00 | 67825.08 | 0.230222E+09 | 0.00 | 885295.78 | 0.00 | 0.43 |
August | 0.00 | 0.103110E+11 | 0.00 | 26360.45 | 0.199958E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 4315570.97 | 0.796177E+10 | 0.00 | 141338.25 | 0.235898E+09 | 0.00 | 3591184.36 | 0.00 | 0.43 |
October | 21136019.87 | 0.525003E+10 | 0.00 | 385963.21 | 0.257964E+09 | 0.00 | 7176292.45 | 0.00 | 0.42 |
November | 22946145.53 | 0.299806E+10 | 0.00 | 243295.69 | 0.114283E+09 | 0.00 | 913153.27 | 0.00 | 0.42 |
December | 0.152374E+09 | 0.918508E+09 | 0.00 | 2041532.86 | 25392257.36 | 0.00 | 0.185820E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.913656E+09 | 0.543622E+11 | 0.00 | 10500051.30 | 0.158579E+10 | 0.00 | 0.107715E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.210410E+09 | 0.00 | 26360.45 | 6399000.98 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.300967E+09 | 0.103110E+11 | 0.00 | 3381666.18 | 0.257964E+09 | 0.00 | 0.490370E+09 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.307163E+09 | 0.204726E+09 | 0.00 | 3285584.27 | 6493495.03 | 0.00 | 0.489314E+09 | 0.00 | 0.42 |
February | 0.182723E+09 | 0.577206E+09 | 0.00 | 2199733.07 | 16446856.20 | 0.00 | 0.250605E+09 | 0.00 | 0.42 |
March | 0.140026E+09 | 0.130096E+10 | 0.00 | 1269755.22 | 23142512.46 | 0.00 | 0.104160E+09 | 0.00 | 0.43 |
April | 75162034.83 | 0.281036E+10 | 0.00 | 371549.19 | 0.111589E+09 | 0.00 | 16902615.14 | 0.00 | 0.42 |
May | 20105274.56 | 0.531077E+10 | 0.00 | 196764.98 | 0.158696E+09 | 0.00 | 8225097.59 | 0.00 | 0.43 |
June | 2436987.06 | 0.740811E+10 | 0.00 | 67053.85 | 0.201796E+09 | 0.00 | 4408108.80 | 0.00 | 0.44 |
July | 1147877.44 | 0.931838E+10 | 0.00 | 71084.41 | 0.230210E+09 | 0.00 | 875693.34 | 0.00 | 0.43 |
August | 0.00 | 0.103454E+11 | 0.00 | 27420.52 | 0.192595E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 4849426.34 | 0.798118E+10 | 0.00 | 146898.33 | 0.235637E+09 | 0.00 | 2967846.88 | 0.00 | 0.43 |
October | 21197485.72 | 0.526488E+10 | 0.00 | 384739.71 | 0.254372E+09 | 0.00 | 7034798.66 | 0.00 | 0.42 |
November | 22591104.77 | 0.299822E+10 | 0.00 | 237026.13 | 0.115416E+09 | 0.00 | 924852.93 | 0.00 | 0.42 |
December | 0.152331E+09 | 0.909745E+09 | 0.00 | 1990746.19 | 25435084.56 | 0.00 | 0.189274E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.929734E+09 | 0.544299E+11 | 0.00 | 10248355.88 | 0.157183E+10 | 0.00 | 0.107469E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.204726E+09 | 0.00 | 27420.52 | 6493495.03 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.307163E+09 | 0.103454E+11 | 0.00 | 3285584.27 | 0.254372E+09 | 0.00 | 0.489314E+09 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.301907E+09 | 0.211991E+09 | 0.00 | 3346411.57 | 6034152.11 | 0.00 | 0.478425E+09 | 0.00 | 0.42 |
February | 0.188614E+09 | 0.575617E+09 | 0.00 | 2237485.73 | 14462287.21 | 0.00 | 0.245416E+09 | 0.00 | 0.42 |
March | 0.146257E+09 | 0.129818E+10 | 0.00 | 1221965.64 | 22529162.14 | 0.00 | 0.101366E+09 | 0.00 | 0.43 |
April | 82530271.99 | 0.281813E+10 | 0.00 | 371805.80 | 98312622.09 | 0.00 | 18238276.65 | 0.00 | 0.42 |
May | 19626196.46 | 0.535613E+10 | 0.00 | 331647.41 | 0.131331E+09 | 0.00 | 16455787.16 | 0.00 | 0.43 |
June | 3086298.99 | 0.749116E+10 | 0.00 | 217965.80 | 0.158425E+09 | 0.00 | 7580298.86 | 0.00 | 0.44 |
July | 1040537.57 | 0.941403E+10 | 0.00 | 247296.44 | 0.203158E+09 | 0.00 | 673931.16 | 0.00 | 0.43 |
August | 75077.73 | 0.104964E+11 | 0.00 | 138031.55 | 0.163711E+09 | 0.00 | 138198.21 | 0.00 | 0.44 |
September | 1353681.41 | 0.813372E+10 | 0.00 | 316192.30 | 0.185876E+09 | 0.00 | 8001481.96 | 0.00 | 0.43 |
October | 21500438.07 | 0.539301E+10 | 0.00 | 484075.14 | 0.172272E+09 | 0.00 | 12377176.16 | 0.00 | 0.42 |
November | 26057718.33 | 0.306440E+10 | 0.00 | 307725.99 | 86624786.19 | 0.00 | 2938297.16 | 0.00 | 0.42 |
December | 0.153642E+09 | 0.930632E+09 | 0.00 | 2075858.93 | 25512580.62 | 0.00 | 0.186330E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.945691E+09 | 0.551834E+11 | 0.00 | 11296462.29 | 0.126825E+10 | 0.00 | 0.107794E+10 | 0.00 | 0.43 |
Minimum of Months | 75077.73 | 0.211991E+09 | 0.00 | 138031.55 | 6034152.11 | 0.00 | 138198.21 | 0.00 | 0.42 |
Maximum of Months | 0.301907E+09 | 0.104964E+11 | 0.00 | 3346411.57 | 0.203158E+09 | 0.00 | 0.478425E+09 | 0.00 | 0.44 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:41:06
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.134385E+12 | 0.180999E+10 | 0.00 | 0.352289E+11 | 0.830449E+11 |
February | 0.156888E+12 | -0.324245E+10 | 0.00 | 0.150223E+11 | 0.984176E+11 |
March | 0.203294E+12 | -0.104214E+11 | 0.00 | -0.269095E+10 | 0.139532E+12 |
April | 0.224379E+12 | -0.244182E+11 | 0.00 | -0.410317E+11 | 0.193066E+12 |
May | 0.245649E+12 | -0.423231E+11 | 0.00 | -0.103044E+12 | 0.290518E+12 |
June | 0.239802E+12 | -0.566545E+11 | 0.00 | -0.151561E+12 | 0.350984E+12 |
July | 0.242575E+12 | -0.712150E+11 | 0.00 | -0.199624E+12 | 0.420943E+12 |
August | 0.232358E+12 | -0.763327E+11 | 0.00 | -0.213767E+12 | 0.451900E+12 |
September | 0.196526E+12 | -0.615764E+11 | 0.00 | -0.162100E+12 | 0.373074E+12 |
October | 0.159423E+12 | -0.410749E+11 | 0.00 | -0.110298E+12 | 0.293432E+12 |
November | 0.120242E+12 | -0.243366E+11 | 0.00 | -0.463385E+11 | 0.205554E+12 |
December | 0.115802E+12 | -0.709407E+10 | 0.00 | 0.104108E+11 | 0.124176E+12 |
Annual Sum or Average | 0.227132E+13 | -0.416879E+12 | 0.00 | -0.969793E+12 | 0.302464E+13 |
Minimum of Months | 0.115802E+12 | -0.763327E+11 | 0.00 | -0.213767E+12 | 0.830449E+11 |
Maximum of Months | 0.245649E+12 | 0.180999E+10 | 0.00 | 0.352289E+11 | 0.451900E+12 |