Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:41
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Simulation Timestamp: 2023-10-16 08:41:05
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:05
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1593.43 | 762.29 | 762.29 |
Net Site Energy | 1593.43 | 762.29 | 762.29 |
Total Source Energy | 3622.35 | 1732.92 | 1732.92 |
Net Source Energy | 3622.35 | 1732.92 | 1732.92 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 683.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 71.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 441.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 99.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 103.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 65.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 909.78 | 683.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 683.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 71.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 441.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 99.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 103.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 65.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 683.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 71.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 441.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 99.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 103.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 65.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 259.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 114.63 | 327.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 435.24 | 327.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 259.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 114.63 | 327.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 435.24 | 327.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 909.781 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 909.781 | 100.00 |
Total On-Site and Utility Electric Sources | 909.781 | 100.00 |
Total Electricity End Uses | 909.781 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2604.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:05
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:41 |
RunPeriod | RUNPERIOD 1 |
Weather File | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Latitude [deg] | 42.93 |
Longitude [deg] | -78.7 |
Elevation [m] | 215.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.77 | 20.77 | 17.8770 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.38 | 10.38 | 19.3382 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 17.3739 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 17.3739 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 17.3739 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.72 | 20.72 | 13.1675 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.3365 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.3365 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.3365 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.36 | 10.36 | 13.3365 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 15.5746 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 15.5746 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 17.8770 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 19.3382 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 17.3739 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 17.3739 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 17.3739 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 13.1675 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 13.3365 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 13.3365 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 13.3365 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 13.3365 | 6.19 | 4.3000 | |
Total | 2090.32 | 15.5746 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 15.5746 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 15.5746 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:05
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 15-JUL-14:50 | 06-FEB-09:09 | - | - | - | - | - | - | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 287737.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 38277.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 27522.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6737.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 7256.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 87883.82 | 287737.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 287737.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 38277.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 27522.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 6737.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 7256.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:05
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 741.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 224.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1398.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 316.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 407.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 326.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 206.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2881.28 | 741.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 354.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 107.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 668.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 151.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 156.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 98.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1378.39 | 354.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 354.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 107.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 668.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 151.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 156.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 98.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1378.39 | 354.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:05
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 1.98 |
SMSTORE1 DIRECT AIR | 1.02 |
SMSTORE2 DIRECT AIR | 1.02 |
SMSTORE3 DIRECT AIR | 1.05 |
SMSTORE4 DIRECT AIR | 1.02 |
LGSTORE2 DIRECT AIR | 1.92 |
SMSTORE5 DIRECT AIR | 1.00 |
SMSTORE6 DIRECT AIR | 0.996468 |
SMSTORE7 DIRECT AIR | 0.988874 |
SMSTORE8 DIRECT AIR | 1.05 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 1.98 | 1.98 | 1.98 | 1.98 | 1.98 | 1.98 | 1.00 | 1.00 | 1.98 |
PSZ-AC_2:2 | 1.02 | 1.02 | 1.02 | 1.02 | 1.04 | 1.04 | 1.00 | 0.979310 | 1.04 |
PSZ-AC_3:3 | 1.02 | 1.02 | 1.02 | 1.02 | 1.04 | 1.04 | 1.00 | 0.975948 | 1.04 |
PSZ-AC_4:4 | 1.05 | 1.05 | 1.05 | 1.05 | 1.05 | 1.05 | 1.00 | 1.00 | 1.05 |
PSZ-AC_5:5 | 1.02 | 1.02 | 1.02 | 1.02 | 1.04 | 1.04 | 1.00 | 0.976824 | 1.04 |
PSZ-AC_6:6 | 1.92 | 1.92 | 1.92 | 1.92 | 1.92 | 1.92 | 1.00 | 1.00 | 1.92 |
PSZ-AC_7:7 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.998823 | 1.00 |
PSZ-AC_8:8 | 0.996468 | 0.996468 | 0.996468 | 0.996468 | 0.997976 | 0.997976 | 1.00 | 0.998489 | 0.997976 |
PSZ-AC_9:9 | 0.988874 | 0.988874 | 0.988874 | 0.988874 | 0.991621 | 0.991621 | 1.00 | 0.997229 | 0.991621 |
PSZ-AC_10:10 | 1.05 | 1.05 | 1.05 | 1.05 | 1.07 | 1.07 | 1.00 | 0.986224 | 1.07 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 1.98 | 0.411479 |
PSZ-AC_2:2_OA_CONTROLLER | 1.04 | 0.205739 |
PSZ-AC_3:3_OA_CONTROLLER | 1.04 | 0.205739 |
PSZ-AC_4:4_OA_CONTROLLER | 1.05 | 0.205739 |
PSZ-AC_5:5_OA_CONTROLLER | 1.04 | 0.205739 |
PSZ-AC_6:6_OA_CONTROLLER | 1.92 | 0.411479 |
PSZ-AC_7:7_OA_CONTROLLER | 1.00 | 0.205739 |
PSZ-AC_8:8_OA_CONTROLLER | 0.997976 | 0.205739 |
PSZ-AC_9:9_OA_CONTROLLER | 0.991621 | 0.205739 |
PSZ-AC_10:10_OA_CONTROLLER | 1.07 | 0.205739 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 1.98 | 2116.16 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.04 | 1155.65 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.04 | 1153.56 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.05 | 1157.23 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.04 | 1152.53 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 1.92 | 2055.05 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 1.00 | 1110.41 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 0.997976 | 1104.92 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 0.991621 | 1097.88 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.07 | 1181.18 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 1.98 | 1.98 | 1.98 | 1.31 | 42030.65 | 62235.38 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.04 | 1.04 | 1.04 | 0.688905 | 21914.60 | 31861.38 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.04 | 1.04 | 1.04 | 0.687660 | 21887.12 | 31742.12 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.05 | 1.05 | 1.05 | 0.689850 | 21940.99 | 32374.64 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.04 | 1.04 | 1.04 | 0.687045 | 21872.75 | 31742.16 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 1.92 | 1.92 | 1.92 | 1.27 | 40951.58 | 60961.15 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 1.00 | 1.00 | 1.00 | 0.661937 | 21299.25 | 31405.66 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 0.997976 | 0.997976 | 0.997976 | 0.658664 | 21223.12 | 31287.82 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 0.991621 | 0.991621 | 0.991621 | 0.654470 | 21106.66 | 31118.56 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.07 | 1.07 | 1.07 | 0.704124 | 22292.63 | 32530.29 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 1.98 | 0.988816 | 1.32 | 42030.65 | 21015.33 | 0.753360 | 0.753360 |
PSZ-AC_2:2 COOLING COIL | 1.04 | 0.521898 | 0.695867 | 21914.60 | 10957.30 | 0.757880 | 0.757880 |
PSZ-AC_3:3 COOLING COIL | 1.04 | 0.520955 | 0.694607 | 21887.12 | 10943.56 | 0.757720 | 0.757720 |
PSZ-AC_4:4 COOLING COIL | 1.05 | 0.522614 | 0.696820 | 21940.99 | 10970.50 | 0.757930 | 0.757930 |
PSZ-AC_5:5 COOLING COIL | 1.04 | 0.520488 | 0.693987 | 21872.75 | 10936.38 | 0.757650 | 0.757650 |
PSZ-AC_6:6 COOLING COIL | 1.92 | 0.960259 | 1.28 | 40951.58 | 20475.79 | 0.751420 | 0.751420 |
PSZ-AC_7:7 COOLING COIL | 1.00 | 0.501468 | 0.668627 | 21299.25 | 10649.62 | 0.753580 | 0.753580 |
PSZ-AC_8:8 COOLING COIL | 0.997980 | 0.498988 | 0.665320 | 21223.12 | 10611.56 | 0.753180 | 0.753180 |
PSZ-AC_9:9 COOLING COIL | 0.991620 | 0.495811 | 0.661080 | 21106.66 | 10553.33 | 0.752930 | 0.752930 |
PSZ-AC_10:10 COOLING COIL | 1.07 | 0.533427 | 0.711233 | 22292.63 | 11146.32 | 0.759260 | 0.759260 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 62235.38 |
PSZ-AC_2:2 HEATING COIL | 31861.38 |
PSZ-AC_3:3 HEATING COIL | 31742.12 |
PSZ-AC_4:4 HEATING COIL | 32374.64 |
PSZ-AC_5:5 HEATING COIL | 31742.16 |
PSZ-AC_6:6 HEATING COIL | 60961.15 |
PSZ-AC_7:7 HEATING COIL | 31405.66 |
PSZ-AC_8:8 HEATING COIL | 31287.82 |
PSZ-AC_9:9 HEATING COIL | 31118.56 |
PSZ-AC_10:10 HEATING COIL | 32530.29 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:05
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:05
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:05
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.70 | 6.00 | -2.20 | -3.40 | -4.20 | 2.70 | 7.50 | 13.70 | 18.60 | 22.00 | 20.70 | 16.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 | 42.93 | -78.73 | -5.00 | 215.00 | 98769 | 1.1739 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 8.97 | 26.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.74 | 20.77 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.66 | 10.38 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.41 | 20.72 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.12 | 10.36 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 17.877 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.177 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 19.338 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 23.638 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 17.374 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.674 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 17.374 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.674 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 17.374 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.674 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 13.168 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.468 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 13.336 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.636 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 13.336 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.636 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 13.336 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.636 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 13.336 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.636 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 4596.695 | 13.194 | 81.718 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4596.695 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 1631.408 | 4.683 | 29.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1631.408 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 2327.780 | 13.363 | 82.767 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2327.780 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1040.795 | 5.975 | 37.007 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1040.795 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 2323.122 | 13.336 | 82.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2323.122 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 703.295 | 4.037 | 25.007 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 703.295 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 2323.122 | 13.336 | 82.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2323.122 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 703.295 | 4.037 | 25.007 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 703.295 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 2323.122 | 13.336 | 82.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2323.122 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 703.295 | 4.037 | 25.007 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 703.295 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 4587.379 | 13.168 | 81.553 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4587.379 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 2323.122 | 13.336 | 82.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2323.122 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 2323.122 | 13.336 | 82.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2323.122 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 2323.122 | 13.336 | 82.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2323.122 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 2323.122 | 13.336 | 82.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2323.122 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.6641 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1464 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2111 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.272 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.756 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.659 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
19 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
20 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
21 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
22 | 7 | -0.32972738E-12 | 0.11763143E-14 | -0.10490290E-12 | 0.10060316E-15 |
23 | 6 | 0.30001920E-07 | 0.18927851E-09 | 0.68616814E-08 | -0.14235861E-12 |
24 | 5 | -0.19683904E-03 | 0.16062604E-05 | -0.10115234E-03 | 0.67789156E-08 |
25 | 4 | 0.29998857 | 0.77587294E-03 | 0.10250533 | -0.34681058E-04 |
26 | 3 | -7.4215481 | 0.23875067E-01 | -2.3849775 | 0.29769922E-01 |
27 | 2 | 41.382972 | 0.84366340E-01 | 15.453844 | -0.33904133 |
28 | 1 | -80.937908 | 0.37867119E-01 | -29.310851 | 1.0869756 |
29 | 0 | 46.824336 | 0.75775345E-03 | 16.287225 | |
30 | 7 | -0.28997596E-08 | -0.17578320E-14 | 0.22751757E-14 | -0.53829073E-16 |
31 | 6 | 0.41991781E-05 | 0.27986603E-08 | 0.31940183E-02 | -0.26794102E-04 |
32 | 5 | -0.29588474E-03 | 0.16552611E-05 | -0.22396035 | 0.19582313E-02 |
33 | 4 | 0.67666006E-02 | 0.75295852E-04 | 4.8334724 | -0.45302727E-01 |
34 | 3 | -0.59297736E-01 | 0.59838054E-03 | -38.043598 | 0.39889893 |
35 | 2 | 0.21038411 | 0.99492606E-03 | 116.52712 | -1.4185167 |
36 | 1 | -0.30354941 | 0.30287292E-03 | -143.93272 | 2.0494576 |
37 | 0 | 0.14796861 | 0.73483799E-05 | 60.838472 | |
38 | 7 | -0.51571905E-08 | -0.97500959E-14 | 0.15789915E-14 | -0.32998988E-16 |
39 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
40 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
41 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
42 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
43 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
44 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
45 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
46 | 7 | -0.51571905E-08 | -0.97500958E-14 | 0.15789913E-14 | -0.32998984E-16 |
47 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
48 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
49 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
50 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
51 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
52 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
53 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
54 | 7 | -0.51571905E-08 | -0.97500959E-14 | 0.15789911E-14 | -0.32998980E-16 |
55 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
56 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
57 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
58 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
59 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
60 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
61 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
62 | 7 | -0.51571905E-08 | -0.97500959E-14 | 0.15789915E-14 | -0.32998988E-16 |
63 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
64 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
65 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
66 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
67 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
68 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
69 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
70 | 7 | -0.51571905E-08 | -0.97500958E-14 | 0.15789913E-14 | -0.32998984E-16 |
71 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
72 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
73 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
74 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
75 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
76 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
77 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
78 | 7 | -0.51571905E-08 | -0.97500957E-14 | 0.15789917E-14 | -0.32998991E-16 |
79 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
80 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
81 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
82 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
83 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
84 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
85 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
86 | 7 | -0.51571905E-08 | -0.97500959E-14 | 0.15789915E-14 | -0.32998988E-16 |
87 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
88 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
89 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
90 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
91 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
92 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
93 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
94 | 7 | -0.51571905E-08 | -0.97500958E-14 | 0.15789913E-14 | -0.32998984E-16 |
95 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
96 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
97 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
98 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
99 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
100 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
101 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
102 | 7 | -0.19967951E-08 | -0.58252365E-15 | 0.72897552E-14 | -0.10630581E-15 |
103 | 6 | 0.59274927E-05 | 0.40433693E-08 | 0.31889525E-02 | -0.26751606E-04 |
104 | 5 | -0.42514865E-03 | 0.23948505E-05 | -0.22367243 | 0.19556901E-02 |
105 | 4 | 0.97725356E-02 | 0.10900143E-03 | 4.8286774 | -0.45256634E-01 |
106 | 3 | -0.85796444E-01 | 0.86675557E-03 | -38.016512 | 0.39859954 |
107 | 2 | 0.30461848 | 0.14417950E-02 | 116.47440 | -1.4178116 |
108 | 1 | -0.43965446 | 0.43929230E-03 | -143.90169 | 2.0489476 |
109 | 0 | 0.21434897 | 0.10616597E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 35 | 1 | VerySmooth | 2.168 | 2.168 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 3.44376E-002 | 0.31435 | 0.47922 | 0.47922 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11914 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 0.157 | 4.517E-004 | 2.488E-004 | 0.314 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 3.813E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 8.993E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 4.692E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 0.112 | 6.453E-004 | 2.994E-004 | 0.448 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 3.583E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 21889.12516 | 26266.95019 | 1.64803 | 1.97763 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.30000 | 1.33670E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 28758.43324 | 34510.11989 | 1.27147 | 1.52576 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -16.30000 | 9.24091E-004 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 11645.61650 | 13974.73980 | 0.85183 | 1.02220 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 26.76600 | 1.33607E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 13426.62225 | 16111.94670 | 0.59363 | 0.71236 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -16.30000 | 9.24091E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 11589.32567 | 13907.19080 | 0.84737 | 1.01685 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.18500 | 1.33579E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 13565.41193 | 16278.49431 | 0.59977 | 0.71972 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -16.30000 | 9.24091E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 11569.20191 | 13883.04230 | 0.87102 | 1.04523 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 30.14500 | 1.33667E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 13637.43861 | 16364.92633 | 0.60295 | 0.72354 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -16.30000 | 9.24091E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 11589.43230 | 13907.31876 | 0.84738 | 1.01685 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.18500 | 1.33579E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 13777.18124 | 16532.61749 | 0.60913 | 0.73096 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -16.30000 | 9.24091E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 21257.74816 | 25509.29780 | 1.60043 | 1.92052 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.06750 | 1.33665E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 26389.29507 | 31667.15409 | 1.16676 | 1.40012 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -16.30000 | 9.24091E-004 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 11417.92930 | 13701.51516 | 0.83480 | 1.00175 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 26.76600 | 1.33607E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 14107.71429 | 16929.25715 | 0.62374 | 0.74849 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -16.30000 | 9.24091E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 11359.11349 | 13630.93619 | 0.83039 | 0.99647 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 26.76600 | 1.33607E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 14095.76755 | 16914.92106 | 0.62322 | 0.74786 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -16.30000 | 9.24091E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 11274.46746 | 13529.36095 | 0.82406 | 0.98887 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 26.76600 | 1.33607E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 14322.89900 | 17187.47880 | 0.63326 | 0.75991 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -16.30000 | 9.24091E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 11975.59779 | 14370.71734 | 0.87680 | 1.05216 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 26.76600 | 1.33607E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 17871.49251 | 21445.79101 | 0.79010 | 0.94812 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -16.30000 | 9.24091E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 28974.38 | 1.97763 | 1.97763 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 52163.64 | 1.52576 | 1.52576 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 15199.87 | 1.04380 | 1.04380 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 24955.46 | 0.71236 | 0.71236 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 15167.80 | 1.04191 | 1.04191 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 25119.58 | 0.71972 | 0.71972 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 15209.74 | 1.04523 | 1.04523 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 25204.76 | 0.72354 | 0.72354 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 15154.01 | 1.04098 | 1.04098 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 25370.01 | 0.73096 | 0.73096 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 28190.15 | 1.92052 | 1.92052 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 49362.43 | 1.40012 | 1.40012 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 14556.01 | 1.00294 | 1.00294 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 25760.88 | 0.74849 | 0.74849 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 14481.42 | 0.99798 | 0.99798 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 25746.75 | 0.74786 | 0.74786 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 14433.75 | 0.99162 | 0.99162 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 26015.34 | 0.75991 | 0.75991 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 15395.57 | 1.06685 | 1.06685 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 30211.32 | 0.94812 | 0.94812 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.97763 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.02220 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.01685 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.04523 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.01685 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.92052 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.00175 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.99647 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.98887 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.05216 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.97763 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.97763 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.97763 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.97763 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.97763 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.97763 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.02220 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.02220 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.02220 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.02220 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.04380 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.04380 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 0.97931 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.01685 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.01685 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.01685 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.01685 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.04191 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.04191 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 0.97595 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.04523 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.04523 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.04523 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.04523 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.04523 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.04523 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.01685 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.01685 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.01685 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.01685 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.04098 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.04098 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 0.97682 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.92052 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.92052 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.92052 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.92052 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.92052 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 1.92052 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.00175 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.00175 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.00175 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.00175 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.00294 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 1.00294 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 0.99882 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.99647 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.99647 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.99647 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.99647 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.99798 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 0.99798 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 0.99849 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.98887 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.98887 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.98887 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.98887 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.99162 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 0.99162 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 0.99723 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.05216 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.05216 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.05216 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.05216 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.06685 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.06685 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 0.98622 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 1.97763 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.04380 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.04191 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.04523 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.04098 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 1.92052 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 1.00294 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 0.99798 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 0.99162 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.06685 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.97763 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.97763 |
104 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2116.15900 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.97763 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.97763 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.97763 |
108 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.30524 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.97763 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.98882 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.31842 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 42030.65000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 21015.32500 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.75336 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.75336 |
116 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 42030.65000 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 62235.38237 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
120 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 62235.38237 |
121 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.04380 |
122 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
123 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.04380 |
124 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1155.64750 |
125 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.04380 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.04380 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.04380 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.68891 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.04380 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52190 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.69587 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 21914.60000 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10957.30000 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.75788 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.75788 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21914.60000 |
137 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31861.37834 |
138 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
139 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
140 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 31861.37834 |
141 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.04191 |
142 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
143 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.04191 |
144 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1153.55876 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.04191 |
146 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.04191 |
147 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.04191 |
148 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.68766 |
149 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.04191 |
150 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52095 |
151 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.69461 |
152 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 21887.12000 |
153 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10943.56000 |
154 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.75772 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.75772 |
156 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21887.12000 |
157 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31742.11718 |
158 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
159 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
160 | Coil:Heating:Fuel | PSZ-AC_3:3 HEATING COIL | Design Size Nominal Capacity [W] | 31742.11718 |
161 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.04523 |
162 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
163 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.04523 |
164 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1157.23315 |
165 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.04523 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.04523 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.04523 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.68985 |
169 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.04523 |
170 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52261 |
171 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.69682 |
172 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 21940.99000 |
173 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10970.49500 |
174 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.75793 |
175 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.75793 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21940.99000 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32374.63770 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
179 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
180 | Coil:Heating:Fuel | PSZ-AC_4:4 HEATING COIL | Design Size Nominal Capacity [W] | 32374.63770 |
181 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.04098 |
182 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
183 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.04098 |
184 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1152.52672 |
185 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.04098 |
186 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.04098 |
187 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.04098 |
188 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.68704 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.04098 |
190 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52049 |
191 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.69399 |
192 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 21872.75000 |
193 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10936.37500 |
194 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.75765 |
195 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.75765 |
196 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21872.75000 |
197 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31742.16253 |
198 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
200 | Coil:Heating:Fuel | PSZ-AC_5:5 HEATING COIL | Design Size Nominal Capacity [W] | 31742.16253 |
201 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.92052 |
202 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
203 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.92052 |
204 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2055.04551 |
205 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.92052 |
206 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.92052 |
207 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.92052 |
208 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.26754 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.92052 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.96026 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.28035 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 40951.58000 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 20475.79000 |
214 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.75142 |
215 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.75142 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 40951.58000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 60961.15203 |
218 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
219 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
220 | Coil:Heating:Fuel | PSZ-AC_6:6 HEATING COIL | Design Size Nominal Capacity [W] | 60961.15203 |
221 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.00294 |
222 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
223 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.00294 |
224 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1110.40836 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.00294 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.00294 |
227 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.00294 |
228 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.66194 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.00294 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.50147 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.66863 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 21299.25000 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10649.62500 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.75358 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.75358 |
236 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21299.25000 |
237 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31405.66064 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
240 | Coil:Heating:Fuel | PSZ-AC_7:7 HEATING COIL | Design Size Nominal Capacity [W] | 31405.66064 |
241 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.99798 |
242 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
243 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.99798 |
244 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1104.91773 |
245 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.99798 |
246 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.99798 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.99798 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.65866 |
249 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.99798 |
250 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.49899 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.66532 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 21223.12000 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10611.56000 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.75318 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.75318 |
256 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21223.12000 |
257 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31287.81837 |
258 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
259 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
260 | Coil:Heating:Fuel | PSZ-AC_8:8 HEATING COIL | Design Size Nominal Capacity [W] | 31287.81837 |
261 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.99162 |
262 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
263 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.99162 |
264 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1097.88205 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.99162 |
266 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.99162 |
267 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.99162 |
268 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.65447 |
269 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.99162 |
270 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.49581 |
271 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.66108 |
272 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 21106.66000 |
273 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10553.33000 |
274 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.75293 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.75293 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21106.66000 |
277 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31118.56234 |
278 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
279 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
280 | Coil:Heating:Fuel | PSZ-AC_9:9 HEATING COIL | Design Size Nominal Capacity [W] | 31118.56234 |
281 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.06685 |
282 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
283 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.06685 |
284 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1181.17657 |
285 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.06685 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.06685 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.06685 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.70412 |
289 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.06685 |
290 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.53343 |
291 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.71123 |
292 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 22292.63000 |
293 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11146.31500 |
294 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.75926 |
295 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.75926 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22292.63000 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32530.29077 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
299 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
300 | Coil:Heating:Fuel | PSZ-AC_10:10 HEATING COIL | Design Size Nominal Capacity [W] | 32530.29077 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 40474.9 | 11.48 | 11.48 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 21093.7 | 11.63 | 11.63 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | 21067.6 | 11.63 | 11.63 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | 21118.9 | 11.63 | 11.63 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | 21054.0 | 11.63 | 11.63 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | 39440.7 | 11.49 | 11.49 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | 20510.3 | 11.65 | 11.65 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | 20438.0 | 11.66 | 11.66 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | 20326.6 | 11.66 | 11.66 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | 21453.6 | 11.62 | 11.62 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 58.18 | 78.94 | 58.18 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.146 | 0.141 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.09 | 39.47 | 29.09 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 58.22 | 78.94 | 58.22 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.211 | 0.201 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 4.8063651737E-002 | 0.2257147648 | Pass | Pass | 0.2806336029 | 1.5296019619 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 4.6522740670E-002 | 0.1776993689 | Pass | Pass | 0.1219834048 | 0.6366125534 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 5.0786766564E-002 | 0.2261440910 | Pass | Pass | 0.1072241760 | 0.6432526465 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 5.7971823507E-002 | 0.2436940992 | Pass | Pass | 7.0942808956E-002 | 0.2813295875 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 6.2931063380E-002 | 0.2576256604 | Pass | Pass | 6.3769844002E-002 | 0.2417061646 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 7.0218491341E-002 | 0.2784670065 | Pass | Pass | 9.9907975191E-002 | 0.5293761268 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 6.9220890836E-002 | 0.2751701060 | Pass | Pass | 9.4524481735E-002 | 0.5412877194 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 7.0258099049E-002 | 0.2795098632 | Pass | Pass | 9.1254737404E-002 | 0.5148679194 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 7.5326724646E-002 | 0.3043315545 | Pass | Pass | 9.5324359980E-002 | 0.5861611139 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 0.1445900055 | 0.3463239636 | Pass | Pass | 0.3043523595 | 2.3309876584 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:05
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3993.01 | 261.77 | 0.00 | 585.90 | 497.23 | 5337.93 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:05
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00 | -16.30 | Wetbulb [C] | 5.10 | 270.00 |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30 | 9.30 | 21.80 | Wetbulb [C] | 5.70 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 44.00 | 33 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 67.00 | 33 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:05
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 78.94 | 58.18 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.143 | 0.146 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.09 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.082 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.082 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.082 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.082 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 78.94 | 58.22 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.082 | 0.083 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.082 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.082 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.082 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.204 | 0.211 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.168 | 0.401 | 0.402 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.168 | 0.401 | 0.402 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.168 | 0.401 | 0.402 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.168 | 0.401 | 0.402 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.168 | 0.401 | 0.402 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.168 | 0.401 | 0.402 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.168 | 0.401 | 0.402 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.168 | 0.401 | 0.402 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.168 | 0.401 | 0.402 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.168 | 0.401 | 0.402 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.168 | 0.401 | 0.402 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.168 | 0.401 | 0.402 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 124.40 | 2.168 | 0.401 | 0.402 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 124.40 | 2.168 | 0.401 | 0.402 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:05
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:05
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 13.1942 | 348.39 | 4596.69 | LightsWired | LTG_SCH_BASE_LPD1 | 84.21 | 168.00 | 84.19 | 0.0000 | Y | 72.65 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 4.6828 | 348.39 | 1631.41 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 168.00 | 97.48 | 0.0000 | Y | 29.85 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 13.3632 | 174.19 | 2327.78 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 85.70 | 168.00 | 85.69 | 0.0000 | Y | 37.44 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 5.9749 | 174.19 | 1040.80 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 168.00 | 97.48 | 0.0000 | Y | 19.04 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 13.3365 | 174.19 | 2323.12 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 29.75 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 4.0374 | 174.19 | 703.30 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 10.29 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 13.3365 | 174.19 | 2323.12 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 29.75 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 4.0374 | 174.19 | 703.30 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 10.29 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 13.3365 | 174.19 | 2323.12 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 29.75 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 4.0374 | 174.19 | 703.30 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 10.29 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 13.1675 | 348.39 | 4587.38 | LightsWired | LTG_SCH_BASE_LPD2 | 62.11 | 168.00 | 61.60 | 0.0000 | Y | 53.05 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 13.3365 | 174.19 | 2323.12 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 27.34 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 13.3365 | 174.19 | 2323.12 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 27.34 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 13.3365 | 174.19 | 2323.12 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 27.34 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 13.3365 | 174.19 | 2323.12 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 27.34 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 7.7873 | 4180.64 | 32555.80 | 441.52 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 345.19 | AstronomicalClock | - | 42.04 | 42.04 | 2.72 | |
EXTERIOR_LIGHTS_B | 7274.32 | AstronomicalClock | - | 83.67 | 71.18 | 97.20 | |
Exterior Lighting Total | 7619.51 | 99.92 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:05
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 42030.65 | 31664.21 | 10366.44 | 0.75 | 3.73 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 21914.60 | 16608.64 | 5305.96 | 0.76 | 3.80 | |||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 21887.12 | 16584.31 | 5302.81 | 0.76 | 3.80 | |||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 21940.99 | 16629.73 | 5311.26 | 0.76 | 3.80 | |||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 21872.75 | 16571.89 | 5300.86 | 0.76 | 3.80 | |||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 40951.58 | 30771.84 | 10179.74 | 0.75 | 3.73 | |||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 21299.25 | 16050.69 | 5248.56 | 0.75 | 3.80 | |||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 21223.12 | 15984.83 | 5238.29 | 0.75 | 3.80 | |||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 21106.66 | 15891.84 | 5214.82 | 0.75 | 3.80 | |||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 22292.63 | 16925.90 | 5366.73 | 0.76 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 40474.9 | 11.48 | 11.48 | ||||
PSZ-AC_2:2 COOLING COIL | 21093.7 | 11.63 | 11.63 | ||||
PSZ-AC_3:3 COOLING COIL | 21067.6 | 11.63 | 11.63 | ||||
PSZ-AC_4:4 COOLING COIL | 21118.9 | 11.63 | 11.63 | ||||
PSZ-AC_5:5 COOLING COIL | 21054.0 | 11.63 | 11.63 | ||||
PSZ-AC_6:6 COOLING COIL | 39440.7 | 11.49 | 11.49 | ||||
PSZ-AC_7:7 COOLING COIL | 20510.3 | 11.65 | 11.65 | ||||
PSZ-AC_8:8 COOLING COIL | 20438.0 | 11.66 | 11.66 | ||||
PSZ-AC_9:9 COOLING COIL | 20326.6 | 11.66 | 11.66 | ||||
PSZ-AC_10:10 COOLING COIL | 21453.6 | 11.62 | 11.62 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 62235.38 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 31861.38 | 0.80 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | 31742.12 | 0.80 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | 32374.64 | 0.80 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | 31742.16 | 0.80 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | 60961.15 | 0.80 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | 31405.66 | 0.80 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | 31287.82 | 0.80 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | 31118.56 | 0.80 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | 32530.29 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.98 | 2116.16 | 1070.05 | 1.00 | 1.32 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.04 | 1155.65 | 1107.16 | 1.00 | 1.39 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.04 | 1153.56 | 1107.16 | 1.00 | 1.39 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.05 | 1157.23 | 1107.16 | 1.00 | 1.39 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.04 | 1152.53 | 1107.16 | 1.00 | 1.39 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.92 | 2055.05 | 1070.05 | 1.00 | 1.32 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.00 | 1110.41 | 1107.16 | 1.00 | 1.40 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.00 | 1104.92 | 1107.16 | 1.00 | 1.40 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.99 | 1097.88 | 1107.16 | 1.00 | 1.40 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.07 | 1181.18 | 1107.16 | 1.00 | 1.39 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:05
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 21889.13 | 26266.95 | 75.40 | 1.648 | 1.978 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 23.89 | 23.89 | 0.00970 | 30.30 | 0.01337 | 0.411 | 0.00 |
SMSTORE1 | 11645.62 | 13974.74 | 80.23 | 0.852 | 1.022 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00938 | 26.77 | 0.01336 | 0.206 | 0.00 |
SMSTORE2 | 11589.33 | 13907.19 | 79.84 | 0.847 | 1.017 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00957 | 25.18 | 0.01336 | 0.206 | 0.00 |
SMSTORE3 | 11569.20 | 13883.04 | 79.70 | 0.871 | 1.045 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.89 | 0.00965 | 30.14 | 0.01337 | 0.206 | 0.00 |
SMSTORE4 | 11589.43 | 13907.32 | 79.84 | 0.847 | 1.017 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00957 | 25.18 | 0.01336 | 0.206 | 0.00 |
LGSTORE2 | 21257.75 | 25509.30 | 73.22 | 1.600 | 1.921 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 23.89 | 23.89 | 0.00968 | 30.07 | 0.01337 | 0.411 | 0.00 |
SMSTORE5 | 11417.93 | 13701.52 | 78.66 | 0.835 | 1.002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00944 | 26.77 | 0.01336 | 0.206 | 0.00 |
SMSTORE6 | 11359.11 | 13630.94 | 78.25 | 0.830 | 0.996 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00946 | 26.77 | 0.01336 | 0.206 | 0.00 |
SMSTORE7 | 11274.47 | 13529.36 | 77.67 | 0.824 | 0.989 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00948 | 26.77 | 0.01336 | 0.206 | 0.00 |
SMSTORE8 | 11975.60 | 14370.72 | 82.50 | 0.877 | 1.052 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.88 | 0.00950 | 26.77 | 0.01336 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 28758.43 | 34510.12 | 99.06 | 1.271 | 1.526 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00658 | -16.30 | 0.00092 | 0.411 | 0.00 |
SMSTORE1 | 13426.62 | 16111.95 | 92.49 | 0.594 | 0.712 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00650 | -16.30 | 0.00092 | 0.206 | 0.00 |
SMSTORE2 | 13565.41 | 16278.49 | 93.45 | 0.600 | 0.720 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00651 | -16.30 | 0.00092 | 0.206 | 0.00 |
SMSTORE3 | 13637.44 | 16364.93 | 93.95 | 0.603 | 0.724 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00652 | -16.30 | 0.00092 | 0.206 | 0.00 |
SMSTORE4 | 13777.18 | 16532.62 | 94.91 | 0.609 | 0.731 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00653 | -16.30 | 0.00092 | 0.206 | 0.00 |
LGSTORE2 | 26389.30 | 31667.15 | 90.90 | 1.167 | 1.400 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00660 | -16.30 | 0.00092 | 0.411 | 0.00 |
SMSTORE5 | 14107.71 | 16929.26 | 97.19 | 0.624 | 0.748 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00655 | -16.30 | 0.00092 | 0.206 | 0.00 |
SMSTORE6 | 14095.77 | 16914.92 | 97.10 | 0.623 | 0.748 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00655 | -16.30 | 0.00092 | 0.206 | 0.00 |
SMSTORE7 | 14322.90 | 17187.48 | 98.67 | 0.633 | 0.760 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00657 | -16.30 | 0.00092 | 0.206 | 0.00 |
SMSTORE8 | 17871.49 | 21445.79 | 123.11 | 0.790 | 0.948 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00662 | -16.30 | 0.00092 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 1.98 | 1.98 | 1.53 | 1.53 | 1.9776 | 1.9776 | 1.9776 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.04 | 1.04 | 0.71 | 0.71 | 1.0438 | 1.0222 | 1.0438 | 0.9793 | 1.0000 |
PSZ-AC_3:3 | 1.04 | 1.04 | 0.72 | 0.72 | 1.0419 | 1.0168 | 1.0419 | 0.9759 | 1.0000 |
PSZ-AC_4:4 | 1.05 | 1.05 | 0.72 | 0.72 | 1.0452 | 1.0452 | 1.0452 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.04 | 1.04 | 0.73 | 0.73 | 1.0410 | 1.0169 | 1.0410 | 0.9768 | 1.0000 |
PSZ-AC_6:6 | 1.92 | 1.92 | 1.40 | 1.40 | 1.9205 | 1.9205 | 1.9205 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 1.00 | 1.00 | 0.75 | 0.75 | 1.0029 | 1.0018 | 1.0029 | 0.9988 | 1.0000 |
PSZ-AC_8:8 | 1.00 | 1.00 | 0.75 | 0.75 | 0.9980 | 0.9965 | 0.9980 | 0.9985 | 1.0000 |
PSZ-AC_9:9 | 0.99 | 0.99 | 0.76 | 0.76 | 0.9916 | 0.9889 | 0.9916 | 0.9972 | 1.0000 |
PSZ-AC_10:10 | 1.07 | 1.07 | 0.95 | 0.95 | 1.0669 | 1.0522 | 1.0669 | 0.9862 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 42030.650 | 31664.210 | 1.977630 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 21015.33 | 15812.17 | 1.318420 | 26.11 | 18.44 | 0.01046222 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 31.2100 | 23.89 | 0.00969906 | 51.1541 | 21889.13 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 62235.382 | 62235.382 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 62235.38 | 62235.38 | 1.977631 | 13.32 | 8.85 | 0.00540565 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 20.8067 | 21.10 | 0.00658310 | 41.3195 | 28758.43 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 21914.600 | 16608.637 | 1.043800 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 10957.30 | 8321.98 | 0.695867 | 26.07 | 18.37 | 0.01038351 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 29.5659 | 23.89 | 0.00965065 | 50.9023 | 11547.82 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 31861.378 | 31861.378 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31861.38 | 31861.38 | 1.043796 | 13.73 | 9.03 | 0.00540041 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 19.7107 | 21.10 | 0.00649933 | 40.7985 | 13426.62 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 21887.120 | 16584.309 | 1.041910 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 10943.56 | 8308.11 | 0.694607 | 26.07 | 18.37 | 0.01038711 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 29.6196 | 23.89 | 0.00965299 | 50.9144 | 11520.68 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 31742.117 | 31742.117 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31742.12 | 31742.12 | 1.041909 | 13.72 | 9.03 | 0.00540704 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 19.7464 | 21.10 | 0.00651006 | 40.8652 | 13565.41 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 21940.990 | 16629.735 | 1.045230 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 10970.50 | 8333.03 | 0.696820 | 26.07 | 18.37 | 0.01038242 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 29.5255 | 23.89 | 0.00964996 | 50.8987 | 11556.18 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 32374.638 | 32374.638 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32374.64 | 32374.64 | 1.045228 | 13.74 | 9.05 | 0.00541491 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 19.6837 | 21.10 | 0.00651550 | 40.8990 | 13637.44 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 21872.750 | 16571.889 | 1.040980 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 10936.38 | 8301.19 | 0.693987 | 26.08 | 18.38 | 0.01038866 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 29.6460 | 23.89 | 0.00965400 | 50.9196 | 11509.01 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 31742.163 | 31742.163 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31742.16 | 31742.16 | 1.040977 | 13.71 | 9.04 | 0.00541893 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 19.7641 | 21.10 | 0.00652611 | 40.9650 | 13777.18 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 40951.580 | 30771.836 | 1.920520 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 20475.79 | 15392.01 | 1.280347 | 26.15 | 18.47 | 0.01047502 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 32.1381 | 23.89 | 0.00968495 | 51.0803 | 21225.42 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 60961.152 | 60961.152 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 60961.15 | 60961.15 | 1.920518 | 13.09 | 8.72 | 0.00538419 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 21.4254 | 21.10 | 0.00660036 | 41.4251 | 26389.30 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 21299.250 | 16050.689 | 1.002940 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 10649.62 | 8020.06 | 0.668627 | 26.13 | 18.45 | 0.01045826 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 30.7704 | 23.89 | 0.00969915 | 51.1541 | 11002.85 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 31405.661 | 31405.661 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31405.66 | 31405.66 | 1.002935 | 13.43 | 8.89 | 0.00539640 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 20.5137 | 21.10 | 0.00655061 | 41.1171 | 14107.71 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 21223.120 | 15984.830 | 0.997980 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 10611.56 | 7983.30 | 0.665320 | 26.14 | 18.46 | 0.01046730 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 30.9234 | 23.89 | 0.00970502 | 51.1846 | 10939.72 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 31287.818 | 31287.818 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31287.82 | 31287.82 | 0.997976 | 13.39 | 8.86 | 0.00538999 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 20.6157 | 21.10 | 0.00654976 | 41.1119 | 14095.77 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 21106.660 | 15891.838 | 0.991620 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 10553.33 | 7934.32 | 0.661080 | 26.15 | 18.46 | 0.01047312 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 31.1217 | 23.89 | 0.00970881 | 51.2043 | 10899.36 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 31118.562 | 31118.562 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31118.56 | 31118.56 | 0.991621 | 13.34 | 8.85 | 0.00539535 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 20.7478 | 21.10 | 0.00656590 | 41.2121 | 14322.90 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 22292.630 | 16925.902 | 1.066850 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 11146.32 | 8420.24 | 0.711233 | 25.95 | 18.35 | 0.01041061 | 12.80 | 11.87 | 0.00850000 | 29.84 | 0.01336614 | 21.70 | 28.9271 | 23.89 | 0.00970447 | 51.1823 | 11809.11 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 32530.291 | 32530.291 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32530.29 | 32530.29 | 1.066854 | 13.89 | 9.23 | 0.00552159 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 19.2847 | 21.10 | 0.00662004 | 41.5515 | 17871.49 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:41:05
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 42030.650 | 31664.210 | 1.977630 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.2888 | 1004.8586 | 1.1739 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.977631 | 2.32159147 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | Sensible | 21015.33 | 15812.17 | 1.0000 | 1.54772661 | 1.318420 | 26.11 | 18.44 | 0.01046222 | 52909.5 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21015.33 | 30.30 | 0.01336696 | 21.83 | 0.41147883 | 31.2100 | 23.89 | 0.00969906 | 23.89 | 0.00969906 | 51.1541 | 21889.13 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 62235.382 | 62235.382 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.977631 | 2.32159147 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 62235.38 | 62235.38 | 1.0000 | 2.32159147 | 1.977631 | 13.32 | 8.85 | 0.00540565 | 27040.0 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 62235.38 | -16.30 | 0.00092409 | -16.30 | 0.41147883 | 20.8067 | 21.11 | 0.00658310 | 21.10 | 0.00658310 | 41.3195 | 28758.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21914.600 | 16608.637 | 1.043800 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.1424 | 1004.8586 | 1.1739 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.043796 | 1.22533816 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 10957.30 | 8321.98 | 1.0000 | 0.81689549 | 0.695867 | 26.07 | 18.37 | 0.01038351 | 52669.3 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10957.30 | 30.30 | 0.01336696 | 21.83 | 0.20573941 | 29.5659 | 23.89 | 0.00965065 | 23.89 | 0.00965065 | 50.9023 | 11547.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31861.378 | 31861.378 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.043796 | 1.22533816 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 31861.38 | 31861.38 | 1.0000 | 1.22533816 | 1.043796 | 13.73 | 9.03 | 0.00540041 | 27443.1 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31861.38 | -16.30 | 0.00092409 | -16.30 | 0.20573941 | 19.7107 | 21.11 | 0.00649933 | 21.10 | 0.00649933 | 40.7985 | 13426.62 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21887.120 | 16584.309 | 1.041910 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.1491 | 1004.8586 | 1.1739 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.041909 | 1.22312346 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 10943.56 | 8308.11 | 1.0000 | 0.81541635 | 0.694607 | 26.07 | 18.37 | 0.01038711 | 52681.6 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10943.56 | 30.30 | 0.01336696 | 21.83 | 0.20573941 | 29.6196 | 23.89 | 0.00965299 | 23.89 | 0.00965299 | 50.9144 | 11520.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31742.117 | 31742.117 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.041909 | 1.22312346 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 31742.12 | 31742.12 | 1.0000 | 1.22312346 | 1.041909 | 13.72 | 9.03 | 0.00540704 | 27446.3 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31742.12 | -16.30 | 0.00092409 | -16.30 | 0.20573941 | 19.7464 | 21.11 | 0.00651006 | 21.10 | 0.00651006 | 40.8652 | 13565.41 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21940.990 | 16629.735 | 1.045230 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.1404 | 1004.8586 | 1.1739 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.045228 | 1.22701943 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 10970.50 | 8333.03 | 1.0000 | 0.81801464 | 0.696820 | 26.07 | 18.37 | 0.01038242 | 52665.6 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10970.50 | 30.30 | 0.01336696 | 21.83 | 0.20573941 | 29.5255 | 23.89 | 0.00964996 | 23.89 | 0.00964996 | 50.8987 | 11556.18 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32374.638 | 32374.638 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.045228 | 1.22701943 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 32374.64 | 32374.64 | 1.0000 | 1.22701943 | 1.045228 | 13.74 | 9.05 | 0.00541491 | 27490.0 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32374.64 | -16.30 | 0.00092409 | -16.30 | 0.20573941 | 19.6837 | 21.11 | 0.00651550 | 21.10 | 0.00651550 | 40.8990 | 13637.44 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21872.750 | 16571.889 | 1.040980 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.1520 | 1004.8586 | 1.1739 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.040977 | 1.22202919 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 10936.38 | 8301.19 | 1.0000 | 0.81468852 | 0.693987 | 26.08 | 18.38 | 0.01038866 | 52686.8 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10936.38 | 30.30 | 0.01336696 | 21.83 | 0.20573941 | 29.6460 | 23.89 | 0.00965400 | 23.89 | 0.00965400 | 50.9196 | 11509.01 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31742.163 | 31742.163 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.040977 | 1.22202919 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 31742.16 | 31742.16 | 1.0000 | 1.22202919 | 1.040977 | 13.71 | 9.04 | 0.00541893 | 27469.6 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31742.16 | -16.30 | 0.00092409 | -16.30 | 0.20573941 | 19.7641 | 21.11 | 0.00652611 | 21.10 | 0.00652611 | 40.9650 | 13777.18 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 40951.580 | 30771.836 | 1.920520 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.3125 | 1004.8586 | 1.1739 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.920518 | 2.25454520 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | Sensible | 20475.79 | 15392.01 | 1.0000 | 1.50303136 | 1.280347 | 26.15 | 18.47 | 0.01047502 | 52985.1 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20475.79 | 30.30 | 0.01336696 | 21.83 | 0.41147883 | 32.1381 | 23.89 | 0.00968495 | 23.89 | 0.00968495 | 51.0803 | 21225.42 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 60961.152 | 60961.152 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.920518 | 2.25454520 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 60961.15 | 60961.15 | 1.0000 | 2.25454520 | 1.920518 | 13.09 | 8.72 | 0.00538419 | 26751.5 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 60961.15 | -16.30 | 0.00092409 | -16.30 | 0.41147883 | 21.4254 | 21.11 | 0.00660036 | 21.10 | 0.00660036 | 41.4251 | 26389.30 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21299.250 | 16050.689 | 1.002940 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.2814 | 1004.8586 | 1.1739 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.002935 | 1.17737091 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | Sensible | 10649.62 | 8020.06 | 1.0000 | 0.78491777 | 0.668627 | 26.13 | 18.45 | 0.01045826 | 52924.0 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10649.62 | 30.30 | 0.01336696 | 21.83 | 0.20573941 | 30.7704 | 23.89 | 0.00969915 | 23.89 | 0.00969915 | 51.1541 | 11002.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31405.661 | 31405.661 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.002935 | 1.17737091 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 31405.66 | 31405.66 | 1.0000 | 1.17737091 | 1.002935 | 13.43 | 8.89 | 0.00539640 | 27128.2 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31405.66 | -16.30 | 0.00092409 | -16.30 | 0.20573941 | 20.5137 | 21.11 | 0.00655061 | 21.10 | 0.00655061 | 41.1171 | 14107.71 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21223.120 | 15984.830 | 0.997980 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.2982 | 1004.8586 | 1.1739 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.997976 | 1.17154916 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | Sensible | 10611.56 | 7983.30 | 1.0000 | 0.78103599 | 0.665320 | 26.14 | 18.46 | 0.01046730 | 52954.8 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10611.56 | 30.30 | 0.01336696 | 21.83 | 0.20573941 | 30.9234 | 23.89 | 0.00970502 | 23.89 | 0.00970502 | 51.1846 | 10939.72 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31287.818 | 31287.818 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.997976 | 1.17154916 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 31287.82 | 31287.82 | 1.0000 | 1.17154916 | 0.997976 | 13.39 | 8.86 | 0.00538999 | 27073.3 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31287.82 | -16.30 | 0.00092409 | -16.30 | 0.20573941 | 20.6157 | 21.11 | 0.00654976 | 21.10 | 0.00654976 | 41.1119 | 14095.77 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21106.660 | 15891.838 | 0.991620 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.3090 | 1004.8586 | 1.1739 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.991621 | 1.16408920 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | Sensible | 10553.33 | 7934.32 | 1.0000 | 0.77605855 | 0.661080 | 26.15 | 18.46 | 0.01047312 | 52974.7 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10553.33 | 30.30 | 0.01336696 | 21.83 | 0.20573941 | 31.1217 | 23.89 | 0.00970881 | 23.89 | 0.00970881 | 51.2043 | 10899.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31118.562 | 31118.562 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.991621 | 1.16408920 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 31118.56 | 31118.56 | 1.0000 | 1.16408920 | 0.991621 | 13.34 | 8.85 | 0.00539535 | 27036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31118.56 | -16.30 | 0.00092409 | -16.30 | 0.20573941 | 20.7478 | 21.11 | 0.00656590 | 21.10 | 0.00656590 | 41.2121 | 14322.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22292.630 | 16925.902 | 1.066850 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.1928 | 1004.8586 | 1.1739 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.066854 | 1.25240675 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | Sensible | 11146.32 | 8420.24 | 1.0000 | 0.83493481 | 0.711233 | 25.95 | 18.35 | 0.01041061 | 52618.4 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11146.32 | 29.84 | 0.01336614 | 21.70 | 0.20573941 | 28.9271 | 23.89 | 0.00970447 | 23.89 | 0.00970447 | 51.1823 | 11809.11 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32530.291 | 32530.291 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.066854 | 1.25240675 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 32530.29 | 32530.29 | 1.0000 | 1.25240675 | 1.066854 | 13.89 | 9.23 | 0.00552159 | 27910.0 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32530.29 | -16.30 | 0.00092409 | -16.30 | 0.20573941 | 19.2847 | 21.10 | 0.00662004 | 21.10 | 0.00662004 | 41.5515 | 17871.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:05
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 1.98 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.04 | - | |||
PSZ-AC_3:3_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.04 | - | |||
PSZ-AC_4:4_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.05 | - | |||
PSZ-AC_5:5_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.04 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 1.92 | - | |||
PSZ-AC_7:7_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.00 | - | |||
PSZ-AC_8:8_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.00 | - | |||
PSZ-AC_9:9_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.99 | - | |||
PSZ-AC_10:10_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.07 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 3272.67 | 4009.50 | 1970.67 |
SMSTORE1 | 2587.83 | 3677.50 | 1199.33 |
SMSTORE2 | 2238.17 | 2939.17 | 1213.50 |
SMSTORE3 | 2297.00 | 2964.50 | 1284.67 |
SMSTORE4 | 2349.67 | 3006.67 | 1370.67 |
LGSTORE2 | 2267.17 | 2799.17 | 1407.50 |
SMSTORE5 | 2220.50 | 2823.17 | 1415.33 |
SMSTORE6 | 2236.67 | 2849.17 | 1447.67 |
SMSTORE7 | 2287.67 | 2924.17 | 1542.67 |
SMSTORE8 | 2525.83 | 3032.00 | 1845.00 |
Facility | 3925.50 | 4442.17 | 2604.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 7.67 | 0.17 | 0.00 | 0.17 |
SMSTORE1 | 3.50 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 0.00 | 0.17 | 0.00 | 0.17 |
SMSTORE3 | 0.00 | 0.17 | 0.00 | 0.17 |
SMSTORE4 | 0.00 | 0.17 | 0.00 | 0.17 |
LGSTORE2 | 0.00 | 0.33 | 0.00 | 0.33 |
SMSTORE5 | 0.00 | 0.17 | 0.00 | 0.17 |
SMSTORE6 | 0.00 | 0.17 | 0.00 | 0.17 |
SMSTORE7 | 0.17 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 32.17 | 0.00 | 0.00 | 0.00 |
Facility | 41.50 | 0.50 | 0.00 | 0.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:05
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.92 | 56.25 | 1805.20 | 0.998 | 0.241 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.851 | 0.252 | 0.000 | 0.000 |
SMSTORE2 | 7.09 | 28.12 | 902.60 | 1.041 | 0.328 | 0.000 | 0.000 |
SMSTORE3 | 7.09 | 28.12 | 902.60 | 1.038 | 0.328 | 0.000 | 0.000 |
SMSTORE4 | 7.09 | 28.12 | 902.60 | 1.030 | 0.328 | 0.000 | 0.000 |
LGSTORE2 | 24.79 | 56.25 | 1805.20 | 1.010 | 0.316 | 0.000 | 0.000 |
SMSTORE5 | 12.40 | 28.12 | 902.60 | 1.023 | 0.350 | 0.000 | 0.000 |
SMSTORE6 | 12.40 | 28.12 | 902.60 | 1.018 | 0.350 | 0.000 | 0.000 |
SMSTORE7 | 12.40 | 28.12 | 902.60 | 1.006 | 0.350 | 0.000 | 0.000 |
SMSTORE8 | 12.40 | 28.12 | 902.60 | 1.012 | 0.377 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.92 | 56.25 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.09 | 28.12 | 902.60 | 0.792 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.09 | 28.12 | 902.60 | 0.792 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.09 | 28.12 | 902.60 | 0.792 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.79 | 56.25 | 1805.20 | 0.792 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.40 | 28.12 | 902.60 | 0.792 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.40 | 28.12 | 902.60 | 0.792 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.40 | 28.12 | 902.60 | 0.792 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.40 | 28.12 | 902.60 | 0.792 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:41:05
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 16.92 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE1 | PSZ-AC_2:2 | 8.46 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE2 | PSZ-AC_3:3 | 7.09 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE3 | PSZ-AC_4:4 | 7.09 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE4 | PSZ-AC_5:5 | 7.09 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
LGSTORE2 | PSZ-AC_6:6 | 24.79 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE5 | PSZ-AC_7:7 | 12.40 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE6 | PSZ-AC_8:8 | 12.40 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE7 | PSZ-AC_9:9 | 12.40 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE8 | PSZ-AC_10:10 | 12.40 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
Total Facility | 121.02 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 2.469 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 10357338.38 | 0.00 | 10357338.38 | 2994054.69 | 13351393.07 | 12976396.34 | 3175.30 | 4213.10 | 1371.60 | 0.00 |
SMSTORE1 | 4408448.48 | 0.00 | 4408448.48 | 1454945.90 | 5863394.38 | 6488198.17 | 4372.91 | 3061.98 | 1325.11 | 0.00 |
SMSTORE2 | 4061171.39 | 0.00 | 4061171.39 | 1502359.59 | 5563530.98 | 6488198.17 | 4365.00 | 3452.98 | 942.02 | 0.00 |
SMSTORE3 | 4052608.73 | 0.00 | 4052608.73 | 1502359.59 | 5554968.33 | 6488198.17 | 4365.00 | 3471.29 | 923.71 | 0.00 |
SMSTORE4 | 4022340.44 | 0.00 | 4022340.44 | 1502359.59 | 5524700.03 | 6488198.17 | 4365.00 | 3499.15 | 895.85 | 0.00 |
LGSTORE2 | 7227533.74 | 0.00 | 7227533.74 | 2777691.18 | 10005224.92 | 12976396.34 | 4730.00 | 3187.82 | 842.18 | 0.00 |
SMSTORE5 | 3659719.58 | 0.00 | 3659719.58 | 1516077.97 | 5175797.55 | 6488198.17 | 4730.00 | 3191.02 | 838.98 | 0.00 |
SMSTORE6 | 3641765.92 | 0.00 | 3641765.92 | 1516077.97 | 5157843.89 | 6488198.17 | 4730.00 | 3206.55 | 823.45 | 0.00 |
SMSTORE7 | 3600883.58 | 0.00 | 3600883.58 | 1516077.97 | 5116961.55 | 6488198.17 | 4730.00 | 3248.72 | 781.28 | 0.00 |
SMSTORE8 | 3623020.17 | 0.00 | 3623020.17 | 1946403.69 | 5569423.86 | 6488198.17 | 4730.00 | 3310.76 | 719.24 | 0.00 |
Total Facility | 48654830.42 | 0.00 | 48654830.42 | 18228408.14 | 66883238.56 | 77858378.04 | 4730.00 | 4718.38 | 1603.04 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.4926 | 0.0000 | 0.4926 | 0.1189 | 0.6116 | 0.4115 | 255.30 | 4213.10 | 1371.60 |
SMSTORE1 | 0.2097 | 0.0000 | 0.2097 | 0.0623 | 0.2720 | 0.2057 | 1452.91 | 3061.98 | 1325.11 |
SMSTORE2 | 0.2567 | 0.0000 | 0.2567 | 0.0811 | 0.3378 | 0.2057 | 0.00 | 3452.98 | 942.02 |
SMSTORE3 | 0.2561 | 0.0000 | 0.2561 | 0.0811 | 0.3372 | 0.2057 | 0.00 | 3471.29 | 923.71 |
SMSTORE4 | 0.2542 | 0.0000 | 0.2542 | 0.0811 | 0.3353 | 0.2057 | 0.00 | 3499.15 | 895.85 |
LGSTORE2 | 0.4982 | 0.0000 | 0.4982 | 0.1559 | 0.6541 | 0.4115 | 0.00 | 3187.82 | 842.18 |
SMSTORE5 | 0.2523 | 0.0000 | 0.2523 | 0.0864 | 0.3387 | 0.2057 | 0.00 | 3191.02 | 838.98 |
SMSTORE6 | 0.2510 | 0.0000 | 0.2510 | 0.0864 | 0.3374 | 0.2057 | 0.00 | 3206.55 | 823.45 |
SMSTORE7 | 0.2482 | 0.0000 | 0.2482 | 0.0864 | 0.3346 | 0.2057 | 0.00 | 3248.72 | 781.28 |
SMSTORE8 | 0.2497 | 0.0000 | 0.2497 | 0.0931 | 0.3428 | 0.2057 | 0.00 | 3310.76 | 719.24 |
Total Facility | 2.9687 | 0.0000 | 2.9687 | 0.9328 | 3.9015 | 2.4689 | 1557.20 | 4718.38 | 1603.04 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 14273897.84 | 0.00 | 14273897.84 | 12976396.34 | 3174.55 | 0.00 | 5585.45 | 0.00 |
PSZ-AC_2:2 | 6075440.36 | 0.00 | 6075440.36 | 6488198.17 | 4323.47 | 2.00 | 4434.53 | 0.00 |
PSZ-AC_3:3 | 5596876.66 | 0.00 | 5596876.66 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 0.00 |
PSZ-AC_4:4 | 5585076.79 | 0.00 | 5585076.79 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 0.00 |
PSZ-AC_5:5 | 5543356.79 | 0.00 | 5543356.79 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 0.00 |
PSZ-AC_6:6 | 9960613.09 | 0.00 | 9960613.09 | 12976396.34 | 4730.00 | 0.00 | 4030.00 | 0.00 |
PSZ-AC_7:7 | 5043615.91 | 0.00 | 5043615.91 | 6488198.17 | 4730.00 | 0.00 | 4030.00 | 0.00 |
PSZ-AC_8:8 | 5018871.28 | 0.00 | 5018871.28 | 6488198.17 | 4730.00 | 0.00 | 4030.00 | 0.00 |
PSZ-AC_9:9 | 4962515.64 | 0.00 | 4962515.64 | 6488198.17 | 4730.00 | 0.00 | 4030.00 | 0.00 |
PSZ-AC_10:10 | 4992955.56 | 0.00 | 4992955.56 | 6488198.17 | 4730.00 | 0.00 | 4030.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.6789 | 0.0000 | 0.6789 | 0.4115 | 254.55 | 0.00 | 5585.45 |
PSZ-AC_2:2 | 0.2890 | 0.0000 | 0.2890 | 0.2057 | 1403.47 | 2.00 | 4434.53 |
PSZ-AC_3:3 | 0.3537 | 0.0000 | 0.3537 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_4:4 | 0.3530 | 0.0000 | 0.3530 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_5:5 | 0.3504 | 0.0000 | 0.3504 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_6:6 | 0.6866 | 0.0000 | 0.6866 | 0.4115 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_7:7 | 0.3476 | 0.0000 | 0.3476 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_8:8 | 0.3459 | 0.0000 | 0.3459 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_9:9 | 0.3421 | 0.0000 | 0.3421 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_10:10 | 0.3442 | 0.0000 | 0.3442 | 0.2057 | 0.00 | 0.00 | 4030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 5161.40 | 428.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 4149.56 | 681.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 4129.60 | 265.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 4137.68 | 257.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 4145.57 | 249.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 3812.82 | 217.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 3807.63 | 222.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 3814.29 | 215.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 3826.69 | 203.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 3833.15 | 196.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.6950 | 0.8839 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.3468 | 0.3655 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 0.3462 | 0.4720 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 0.3455 | 0.4746 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 0.3431 | 0.4733 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 0.6754 | 0.8858 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.3414 | 0.4561 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.3399 | 0.4540 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.3364 | 0.4505 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.3377 | 0.4728 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:05
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 759 |
Defaulted Fields | 823 |
Fields with Defaults | 2681 |
Autosized Fields | 184 |
Autosizable Fields | 458 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:41:05
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 909.78 | 3115.94 | 01-JAN-08:00 | 87883.82 | 15-JUL-14:50 |
Electricity:Building | 570.24 | 1897.94 | 01-JAN-00:10 | 35612.10 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 128.86 | 354.96 | 01-JAN-00:10 | 6669.68 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 570.24 | 1897.94 | 01-JAN-00:10 | 35612.10 | 01-JAN-11:10 |
InteriorLights:Electricity | 441.52 | 1448.52 | 01-JAN-00:10 | 27522.57 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 102.50 | 280.06 | 01-JAN-00:10 | 5321.43 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 441.52 | 1448.52 | 01-JAN-00:10 | 27522.57 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 441.52 | 1448.52 | 01-JAN-00:10 | 27522.57 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 102.50 | 280.06 | 01-JAN-00:10 | 5321.43 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 441.52 | 1448.52 | 01-JAN-00:10 | 27522.57 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 69.66 | 191.80 | 01-JAN-00:10 | 3606.70 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 56.49 | 154.35 | 01-JAN-00:10 | 2932.57 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 56.49 | 154.35 | 01-JAN-00:10 | 2932.57 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 50.51 | 174.25 | 01-JAN-00:10 | 3273.35 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 40.04 | 136.80 | 01-JAN-00:10 | 2599.23 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 40.04 | 136.80 | 01-JAN-00:10 | 2599.23 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 50.51 | 174.25 | 01-JAN-00:10 | 3273.35 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 40.04 | 136.80 | 01-JAN-00:10 | 2599.23 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 40.04 | 136.80 | 01-JAN-00:10 | 2599.23 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 50.51 | 174.25 | 01-JAN-00:10 | 3273.35 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 40.04 | 136.80 | 01-JAN-00:10 | 2599.23 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 40.04 | 136.80 | 01-JAN-00:10 | 2599.23 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 72.31 | 272.07 | 01-JAN-00:10 | 5094.77 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 53.05 | 197.17 | 01-JAN-00:10 | 3746.51 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 53.05 | 197.17 | 01-JAN-00:10 | 3746.51 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 36.97 | 139.09 | 01-JAN-00:10 | 2605.22 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 36.97 | 139.09 | 01-JAN-00:10 | 2605.22 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 36.97 | 139.09 | 01-JAN-00:10 | 2605.22 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 36.97 | 139.09 | 01-JAN-00:10 | 2605.22 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.36 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.36 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.18 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.18 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.26 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.26 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
ElectricityPurchased:Facility | 909.78 | 3115.94 | 01-JAN-08:00 | 87883.82 | 15-JUL-14:50 |
ElectricityPurchased:Plant | 909.78 | 3115.94 | 01-JAN-08:00 | 87883.82 | 15-JUL-14:50 |
Cogeneration:ElectricityPurchased | 909.78 | 3115.94 | 01-JAN-08:00 | 87883.82 | 15-JUL-14:50 |
General:Cogeneration:ElectricityPurchased | 909.78 | 3115.94 | 01-JAN-08:00 | 87883.82 | 15-JUL-14:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 909.78 | 3115.94 | 01-JAN-08:00 | 87883.82 | 15-JUL-14:50 |
ElectricityNet:Plant | 909.78 | 3115.94 | 01-JAN-08:00 | 87883.82 | 15-JUL-14:50 |
Cogeneration:ElectricityNet | 909.78 | 3115.94 | 01-JAN-08:00 | 87883.82 | 15-JUL-14:50 |
General:Cogeneration:ElectricityNet | 909.78 | 3115.94 | 01-JAN-08:00 | 87883.82 | 15-JUL-14:50 |
Electricity:HVAC | 174.29 | 0.00 | 01-JAN-00:10 | 46190.62 | 20-JUL-13:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 71.04 | 0.00 | 01-JAN-00:10 | 39114.50 | 20-JUL-13:00 |
General:Cooling:Electricity | 71.04 | 0.00 | 01-JAN-00:10 | 39114.50 | 20-JUL-13:00 |
Fans:Electricity | 103.25 | 0.00 | 01-JAN-00:10 | 10167.02 | 06-FEB-09:10 |
General:Fans:Electricity | 103.25 | 0.00 | 01-JAN-00:10 | 10167.02 | 06-FEB-09:10 |
ExteriorLights:Electricity | 99.92 | 0.00 | 01-JAN-08:00 | 7619.51 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 99.92 | 0.00 | 01-JAN-08:00 | 7619.51 | 01-JAN-06:10 |
Electricity:Plant | 65.33 | 1218.00 | 02-JAN-08:10 | 11871.16 | 07-JAN-14:20 |
WaterSystems:Electricity | 65.33 | 1218.00 | 02-JAN-08:10 | 11871.16 | 07-JAN-14:20 |
Water Heater:WaterSystems:Electricity | 65.33 | 1218.00 | 02-JAN-08:10 | 11871.16 | 07-JAN-14:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 683.65 | 0.00 | 01-JAN-00:10 | 287737.42 | 06-FEB-09:10 |
NaturalGas:HVAC | 683.65 | 0.00 | 01-JAN-00:10 | 287737.42 | 06-FEB-09:10 |
Heating:NaturalGas | 683.65 | 0.00 | 01-JAN-00:10 | 287737.42 | 06-FEB-09:10 |
General:Heating:NaturalGas | 683.65 | 0.00 | 01-JAN-00:10 | 287737.42 | 06-FEB-09:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1345.40 | 0.00 | 01-JAN-00:10 | 367418.72 | 06-FEB-09:10 |
EnergyTransfer:Building | 509.03 | 0.00 | 01-JAN-00:10 | 137228.78 | 06-FEB-09:10 |
EnergyTransfer:Zone:LGSTORE1 | 101.69 | 0.00 | 01-JAN-00:10 | 24906.45 | 06-FEB-09:10 |
Heating:EnergyTransfer | 186.36 | 0.00 | 01-JAN-00:10 | 135130.20 | 06-FEB-09:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 30.06 | 0.00 | 01-JAN-00:10 | 24315.57 | 06-FEB-09:10 |
General:Heating:EnergyTransfer | 186.36 | 0.00 | 01-JAN-00:10 | 135130.20 | 06-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 30.06 | 0.00 | 01-JAN-00:10 | 24315.57 | 06-FEB-09:10 |
Cooling:EnergyTransfer | 322.67 | 0.00 | 01-JAN-00:10 | 88461.62 | 21-JUL-13:00 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 71.63 | 0.00 | 01-JAN-00:10 | 14703.05 | 21-JUL-13:00 |
General:Cooling:EnergyTransfer | 322.67 | 0.00 | 01-JAN-00:10 | 88461.62 | 21-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 71.63 | 0.00 | 01-JAN-00:10 | 14703.05 | 21-JUL-13:00 |
EnergyTransfer:Zone:SMSTORE1 | 48.49 | 0.00 | 01-JAN-00:10 | 10331.37 | 06-FEB-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 9.59 | 0.00 | 01-JAN-00:10 | 10291.25 | 06-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 9.59 | 0.00 | 01-JAN-00:10 | 10291.25 | 06-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 38.90 | 0.00 | 01-JAN-00:10 | 9015.96 | 03-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 38.90 | 0.00 | 01-JAN-00:10 | 9015.96 | 03-JUN-18:20 |
EnergyTransfer:Zone:SMSTORE2 | 40.10 | 0.00 | 01-JAN-00:10 | 13014.85 | 07-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 12.15 | 0.00 | 01-JAN-00:10 | 12342.48 | 07-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 12.15 | 0.00 | 01-JAN-00:10 | 12342.48 | 07-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 27.95 | 0.00 | 01-JAN-00:10 | 7453.14 | 21-JUL-13:40 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 27.95 | 0.00 | 01-JAN-00:10 | 7453.14 | 21-JUL-13:40 |
EnergyTransfer:Zone:SMSTORE3 | 40.37 | 0.00 | 01-JAN-00:10 | 13243.46 | 07-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 13.11 | 0.00 | 01-JAN-00:10 | 12661.49 | 07-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 13.11 | 0.00 | 01-JAN-00:10 | 12661.49 | 07-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 27.27 | 0.00 | 01-JAN-00:10 | 7467.25 | 21-JUL-13:40 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 27.27 | 0.00 | 01-JAN-00:10 | 7467.25 | 21-JUL-13:40 |
EnergyTransfer:Zone:SMSTORE4 | 40.40 | 0.00 | 01-JAN-00:10 | 13135.30 | 11-DEC-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 14.47 | 0.00 | 01-JAN-00:10 | 12789.51 | 06-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 14.47 | 0.00 | 01-JAN-00:10 | 12789.51 | 06-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 25.92 | 0.00 | 01-JAN-00:10 | 7373.20 | 21-JUL-13:40 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 25.92 | 0.00 | 01-JAN-00:10 | 7373.20 | 21-JUL-13:40 |
EnergyTransfer:Zone:LGSTORE2 | 72.36 | 0.00 | 01-JAN-00:10 | 25840.37 | 06-FEB-09:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 26.82 | 0.00 | 01-JAN-00:10 | 25009.97 | 06-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 26.82 | 0.00 | 01-JAN-00:10 | 25009.97 | 06-FEB-09:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 45.54 | 0.00 | 01-JAN-00:10 | 13994.71 | 21-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 45.54 | 0.00 | 01-JAN-00:10 | 13994.71 | 21-JUL-13:00 |
EnergyTransfer:Zone:SMSTORE5 | 38.17 | 0.00 | 01-JAN-00:10 | 13519.41 | 06-FEB-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 15.13 | 0.00 | 01-JAN-00:10 | 13290.15 | 06-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 15.13 | 0.00 | 01-JAN-00:10 | 13290.15 | 06-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 23.04 | 0.00 | 01-JAN-00:10 | 7278.32 | 21-JUL-14:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 23.04 | 0.00 | 01-JAN-00:10 | 7278.32 | 21-JUL-14:10 |
EnergyTransfer:Zone:SMSTORE6 | 38.01 | 0.00 | 01-JAN-00:10 | 13638.37 | 06-FEB-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 15.54 | 0.00 | 01-JAN-00:10 | 13384.23 | 06-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 15.54 | 0.00 | 01-JAN-00:10 | 13384.23 | 06-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 22.46 | 0.00 | 01-JAN-00:10 | 7224.49 | 21-JUL-14:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 22.46 | 0.00 | 01-JAN-00:10 | 7224.49 | 21-JUL-14:10 |
EnergyTransfer:Zone:SMSTORE7 | 38.65 | 0.00 | 01-JAN-00:10 | 13871.89 | 06-FEB-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 17.75 | 0.00 | 01-JAN-00:10 | 13718.11 | 06-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 17.75 | 0.00 | 01-JAN-00:10 | 13718.11 | 06-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 20.90 | 0.00 | 01-JAN-00:10 | 7182.13 | 21-JUL-14:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 20.90 | 0.00 | 01-JAN-00:10 | 7182.13 | 21-JUL-14:10 |
EnergyTransfer:Zone:SMSTORE8 | 50.79 | 0.00 | 01-JAN-00:10 | 16893.17 | 06-FEB-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 31.74 | 0.00 | 01-JAN-00:10 | 16893.17 | 06-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 31.74 | 0.00 | 01-JAN-00:10 | 16893.17 | 06-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 19.05 | 0.00 | 01-JAN-00:10 | 8004.73 | 21-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 19.05 | 0.00 | 01-JAN-00:10 | 8004.73 | 21-JUL-13:00 |
EnergyTransfer:HVAC | 836.37 | 0.00 | 01-JAN-00:10 | 230189.93 | 06-FEB-09:10 |
HeatingCoils:EnergyTransfer | 546.92 | 0.00 | 01-JAN-00:10 | 230189.93 | 06-FEB-09:10 |
CoolingCoils:EnergyTransfer | 289.45 | 0.00 | 01-JAN-00:10 | 166098.33 | 20-JUL-14:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:05
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 30.062 | -71.630 | 0.000 | 0.000 | 25.459 | 102.498 | 26.357 | 20.266 | 0.000 | 1.056 | 0.004 | 0.000 | -10.685 | 0.000 | -44.112 | -79.272 |
SMSTORE1 | 0.000 | 0.000 | 9.585 | -38.901 | 0.000 | 0.000 | 12.566 | 56.486 | 13.179 | 10.020 | 0.000 | 0.565 | 0.003 | 0.000 | -5.625 | 0.000 | -21.268 | -36.607 |
SMSTORE2 | 0.000 | 0.000 | 12.152 | -27.950 | 0.000 | 0.000 | 7.639 | 40.039 | 10.467 | 10.008 | 0.000 | 0.552 | 0.001 | 0.000 | -5.524 | 0.000 | -21.944 | -25.439 |
SMSTORE3 | 0.000 | 0.000 | 13.108 | -27.267 | 0.000 | 0.000 | 7.648 | 40.039 | 10.467 | 10.022 | 0.000 | 0.551 | 0.000 | 0.000 | -5.465 | 0.000 | -21.867 | -27.237 |
SMSTORE4 | 0.000 | 0.000 | 14.472 | -25.925 | 0.000 | 0.000 | 7.658 | 40.039 | 10.467 | 10.041 | 0.000 | 0.552 | 0.002 | 0.000 | -5.412 | 0.000 | -21.787 | -30.105 |
LGSTORE2 | 0.000 | 0.000 | 26.822 | -45.540 | 0.000 | 0.000 | 26.286 | 53.048 | 19.261 | 20.208 | 0.000 | 0.994 | 0.001 | 0.000 | -10.551 | 0.000 | -40.225 | -50.303 |
SMSTORE5 | 0.000 | 0.000 | 15.129 | -23.043 | 0.000 | 0.000 | 13.146 | 27.343 | 9.631 | 10.081 | 0.000 | 0.552 | 0.002 | 0.000 | -5.294 | 0.000 | -21.875 | -25.669 |
SMSTORE6 | 0.000 | 0.000 | 15.542 | -22.463 | 0.000 | 0.000 | 13.156 | 27.343 | 9.631 | 10.092 | 0.000 | 0.552 | 0.001 | 0.000 | -5.270 | 0.000 | -21.835 | -26.747 |
SMSTORE7 | 0.000 | 0.000 | 17.746 | -20.901 | 0.000 | 0.000 | 13.182 | 27.343 | 9.631 | 10.127 | 0.000 | 0.552 | 0.001 | 0.000 | -5.180 | 0.000 | -21.699 | -30.801 |
SMSTORE8 | 0.000 | 0.000 | 31.745 | -19.046 | 0.000 | 0.000 | 13.228 | 27.343 | 9.631 | 10.223 | 0.000 | 0.588 | 0.001 | 0.000 | -4.831 | 0.000 | -27.912 | -40.969 |
Total Facility | 0.000 | 0.000 | 186.363 | -322.667 | 0.000 | 0.000 | 139.968 | 441.522 | 128.721 | 121.086 | 0.000 | 6.515 | 0.017 | 0.000 | -63.835 | 0.000 | -264.524 | -373.150 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 06-AUG-07:02 | 0.00 | 0.00 | 0.00 | -35208.57 | 0.00 | 0.00 | 180.71 | 280.06 | 74.90 | 303.95 | 0.00 | 0.00 | 34549.87 | 0.00 | -0.00 | 0.00 | -180.92 | 0.00 |
SMSTORE1 | 12-JUL-08:62 | 0.00 | 0.00 | 0.00 | -21204.34 | 0.00 | 0.00 | 88.61 | 1543.46 | 374.52 | 243.81 | 0.00 | 0.00 | 19083.98 | 0.00 | -0.00 | 0.00 | -130.02 | 0.00 |
SMSTORE2 | 12-JUL-07:02 | 0.00 | 0.00 | 0.00 | -21189.62 | 0.00 | 0.00 | 88.66 | 1368.01 | 374.52 | 106.51 | 0.00 | 0.00 | 19404.59 | 0.00 | -0.00 | 0.00 | -152.66 | 0.00 |
SMSTORE3 | 12-JUL-07:02 | 0.00 | 0.00 | 0.00 | -21265.37 | 0.00 | 0.00 | 88.51 | 1368.01 | 374.52 | 106.13 | 0.00 | 0.00 | 19481.21 | 0.00 | -0.00 | 0.00 | -153.02 | 0.00 |
SMSTORE4 | 12-JUL-07:02 | 0.00 | 0.00 | 0.00 | -21064.22 | 0.00 | 0.00 | 89.36 | 1368.01 | 374.52 | 107.82 | 0.00 | 0.00 | 19275.11 | 0.00 | -0.00 | 0.00 | -150.61 | 0.00 |
LGSTORE2 | 12-JUL-08:62 | 0.00 | 0.00 | 0.00 | -38170.78 | 0.00 | 0.00 | 397.15 | 1971.84 | 749.03 | 489.22 | 0.00 | 0.00 | 34794.44 | 0.00 | -0.00 | 0.00 | -230.90 | 0.00 |
SMSTORE5 | 20-AUG-09:02 | 0.00 | 0.00 | 0.00 | -19193.97 | 0.00 | 0.00 | 193.63 | 1016.37 | 374.52 | 774.66 | 0.00 | 0.00 | 16954.83 | 0.00 | -0.00 | 0.00 | -120.05 | 0.00 |
SMSTORE6 | 20-AUG-09:02 | 0.00 | 0.00 | 0.00 | -19068.70 | 0.00 | 0.00 | 194.43 | 1016.37 | 374.52 | 775.66 | 0.00 | 0.00 | 16826.65 | 0.00 | -0.00 | 0.00 | -118.93 | 0.00 |
SMSTORE7 | 20-AUG-09:02 | 0.00 | 0.00 | 0.00 | -18779.43 | 0.00 | 0.00 | 197.30 | 1016.37 | 374.52 | 778.51 | 0.00 | 0.00 | 16527.30 | 0.00 | -0.00 | 0.00 | -114.56 | 0.00 |
SMSTORE8 | 11-AUG-08:62 | 0.00 | 0.00 | 0.00 | -18094.41 | 0.00 | 0.00 | 196.87 | 1016.37 | 374.52 | 383.86 | 0.00 | 0.00 | 16286.17 | 0.00 | -0.00 | 0.00 | -163.38 | 0.00 |
Total Facility | 11-AUG-08:62 | 0.00 | 0.00 | 0.00 | -168084.94 | 0.00 | 0.00 | 1998.67 | 18179.18 | 5393.02 | 4596.37 | 0.00 | 0.00 | 139569.99 | 0.00 | 0.00 | 0.00 | -1652.30 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 06-FEB-08:61 | 0.00 | 0.00 | 62235.39 | 0.00 | 0.00 | 0.00 | 289.54 | 280.06 | 74.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1022.10 | 0.00 | -2173.77 | -59684.02 |
SMSTORE1 | 06-FEB-08:61 | 0.00 | 0.00 | 31879.58 | 0.00 | 0.00 | 0.00 | 139.57 | 154.35 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -539.05 | 0.00 | -1018.22 | -30653.68 |
SMSTORE2 | 07-FEB-07:01 | 0.00 | 0.00 | 31642.32 | 0.00 | 0.00 | 0.00 | 0.00 | 136.80 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -642.44 | 0.00 | -217.37 | -30956.76 |
SMSTORE3 | 07-FEB-07:01 | 0.00 | 0.00 | 32251.83 | 0.00 | 0.00 | 0.00 | 0.00 | 136.80 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -636.29 | 0.00 | -215.53 | -31574.27 |
SMSTORE4 | 06-FEB-07:01 | 0.00 | 0.00 | 31658.96 | 0.00 | 0.00 | 0.00 | 0.00 | 136.80 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -578.04 | 0.00 | -242.44 | -31012.73 |
LGSTORE2 | 06-FEB-08:61 | 0.00 | 0.00 | 61130.09 | 0.00 | 0.00 | 0.00 | 0.00 | 197.17 | 74.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1015.76 | 0.00 | -1828.08 | -58558.32 |
SMSTORE5 | 06-FEB-08:61 | 0.00 | 0.00 | 31500.87 | 0.00 | 0.00 | 0.00 | 0.00 | 101.64 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -511.65 | 0.00 | -992.35 | -30135.96 |
SMSTORE6 | 06-FEB-08:61 | 0.00 | 0.00 | 31340.24 | 0.00 | 0.00 | 0.00 | 0.00 | 101.64 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -506.99 | 0.00 | -982.60 | -29989.74 |
SMSTORE7 | 06-FEB-08:61 | 0.00 | 0.00 | 31216.09 | 0.00 | 0.00 | 0.00 | 0.00 | 101.64 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -509.06 | 0.00 | -991.59 | -29854.53 |
SMSTORE8 | 11-DEC-08:61 | 0.00 | 0.00 | 32643.28 | 0.00 | 0.00 | 0.00 | 0.00 | 101.64 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -154.08 | 0.00 | -968.90 | -31659.38 |
Total Facility | 13-FEB-08:61 | 0.00 | 0.00 | 357972.35 | 0.00 | 0.00 | 0.00 | 817.93 | 5142.15 | 1460.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4941.15 | 0.00 | -11641.14 | -348810.76 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:05
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.9776 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.9776 | 0.2081 | 1.0000 | Not calculated | 0.4115 | 0.2081 | ||
PSZ-AC_2:2 | 1.0222 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0438 | 0.1971 | 1.0000 | Not calculated | 0.2057 | 0.1971 | ||
PSZ-AC_3:3 | 1.0168 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0419 | 0.1975 | 1.0000 | Not calculated | 0.2057 | 0.1975 | ||
PSZ-AC_4:4 | 1.0452 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0452 | 0.1968 | 1.0000 | Not calculated | 0.2057 | 0.1968 | ||
PSZ-AC_5:5 | 1.0169 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0410 | 0.1976 | 1.0000 | Not calculated | 0.2057 | 0.1976 | ||
PSZ-AC_6:6 | 1.9205 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.9205 | 0.2143 | 1.0000 | Not calculated | 0.4115 | 0.2143 | ||
PSZ-AC_7:7 | 1.0018 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0029 | 0.2051 | 1.0000 | Not calculated | 0.2057 | 0.2051 | ||
PSZ-AC_8:8 | 0.9965 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9980 | 0.2062 | 1.0000 | Not calculated | 0.2057 | 0.2062 | ||
PSZ-AC_9:9 | 0.9889 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9916 | 0.2075 | 1.0000 | Not calculated | 0.2057 | 0.2075 | ||
PSZ-AC_10:10 | 1.0522 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0669 | 0.1928 | 1.0000 | Not calculated | 0.2057 | 0.1928 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.9776 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.9776 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2081 | ||
PSZ-AC_2:2 | 1.0222 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0222 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2013 | ||
PSZ-AC_3:3 | 1.0168 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0168 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2023 | ||
PSZ-AC_4:4 | 1.0452 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0452 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1968 | ||
PSZ-AC_5:5 | 1.0169 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0169 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2023 | ||
PSZ-AC_6:6 | 1.9205 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.9205 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2143 | ||
PSZ-AC_7:7 | 1.0018 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0018 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2054 | ||
PSZ-AC_8:8 | 0.9965 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9965 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2065 | ||
PSZ-AC_9:9 | 0.9889 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9889 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2081 | ||
PSZ-AC_10:10 | 1.0522 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0522 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1955 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9776 | 1.9776 | 1.9776 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0222 | 1.0222 | 1.0222 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0168 | 1.0168 | 1.0168 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0452 | 1.0452 | 1.0452 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0169 | 1.0169 | 1.0169 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9205 | 1.9205 | 1.9205 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0018 | 1.0018 | 1.0018 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9965 | 0.9965 | 0.9965 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9889 | 0.9889 | 0.9889 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0522 | 1.0522 | 1.0522 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.9776 | 1.9776 | 1.9776 | 1.9776 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.0222 | 1.0438 | 1.0222 | 1.0222 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.0168 | 1.0419 | 1.0168 | 1.0168 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.0452 | 1.0452 | 1.0452 | 1.0452 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.0169 | 1.0410 | 1.0169 | 1.0169 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.9205 | 1.9205 | 1.9205 | 1.9205 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.0018 | 1.0029 | 1.0018 | 1.0018 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9965 | 0.9980 | 0.9965 | 0.9965 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.9889 | 0.9916 | 0.9889 | 0.9889 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.0522 | 1.0669 | 1.0522 | 1.0522 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9776 | 1.9776 | 1.9776 | No | 0.4115 | 0.2697 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0222 | 1.0222 | 1.0222 | No | 0.2057 | 0.2888 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0168 | 1.0168 | 1.0168 | No | 0.2057 | 0.2859 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0452 | 1.0452 | 1.0452 | No | 0.2057 | 0.2844 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0169 | 1.0169 | 1.0169 | No | 0.2057 | 0.2815 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9205 | 1.9205 | 1.9205 | No | 0.4115 | 0.2939 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0018 | 1.0018 | 1.0018 | No | 0.2057 | 0.2749 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9965 | 0.9965 | 0.9965 | No | 0.2057 | 0.2751 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9889 | 0.9889 | 0.9889 | No | 0.2057 | 0.2707 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0522 | 1.0522 | 1.0522 | No | 0.2057 | 0.2170 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.9776 | 1.9776 | 1.9776 | 1.9776 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.0222 | 1.0222 | 1.0222 | 1.0222 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.0168 | 1.0168 | 1.0168 | 1.0168 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.0452 | 1.0452 | 1.0452 | 1.0452 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.0169 | 1.0169 | 1.0169 | 1.0169 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.9205 | 1.9205 | 1.9205 | 1.9205 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.0018 | 1.0018 | 1.0018 | 1.0018 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9965 | 0.9965 | 0.9965 | 0.9965 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.9889 | 0.9889 | 0.9889 | 0.9889 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.0522 | 1.0522 | 1.0522 | 1.0522 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:05
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.50 |
Number of hours not met | 0.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 683.65 | 287737.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 71.04 | 39114.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 441.52 | 27522.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 99.92 | 7619.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.72 | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 103.25 | 10167.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 65.33 | 11871.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.72 | 909.78 |
Natural Gas | 0.00 | 683.65 |
Additional | 0.00 | 0.00 |
Total | 128.72 | 1593.43 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 211.22 |
Space Heating | 0.00 |
Space Cooling | 33.99 |
Fans (All) | 49.39 |
Service Water Heating | 31.25 |
Receptacle Equipment | 61.58 |
Miscellaneous (All) | 435.24 |
Subtotal | 435.24 |
Natural Gas [MJ/m2] | |
Space Heating | 327.05 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 327.05 |
Subtotal | 327.05 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 27.71 |
Space Heating | 42.90 |
Space Cooling | 4.46 |
Fans (All) | 6.48 |
Service Water Heating | 4.10 |
Receptacle Equipment | 8.08 |
Miscellaneous | 6.27 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3238. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3296. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 4469. | 8760. |
LTG_SCH_BASE_LPD1 | 4391. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 3584. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4888. | 8760. |
TYPE2_EQUIP_SCH | 3911. | 8760. |
TYPE3_EQUIP_SCH | 3600. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:05
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 8759.00 | 1.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8759.50 | 0.50 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8734.50 | 25.50 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8730.83 | 29.17 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8737.67 | 22.33 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8745.50 | 14.50 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8748.00 | 12.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8749.00 | 11.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8751.67 | 8.33 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8750.50 | 9.50 | 0.00 | 0.00 | 0.00 |
Min | 8730.83 | 0.50 | 0.00 | 0.00 | 0.00 |
Max | 8759.50 | 29.17 | 0.00 | 0.00 | 0.00 |
Average | 8746.62 | 13.38 | 0.00 | 0.00 | 0.00 |
Sum | 87466.17 | 133.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 89040.67 | 0.33 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25470.67 | 4.33 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25470.67 | 4.33 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25471.00 | 4.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93192.00 | 19.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45903.00 | 9.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45903.00 | 9.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45904.50 | 7.50 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45903.50 | 8.50 | 0.00 | 0.00 | 0.00 |
Min | 25470.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 93192.00 | 19.00 | 0.00 | 0.00 | 0.00 |
Average | 48603.60 | 6.60 | 0.00 | 0.00 | 0.00 |
Sum | 486036.00 | 66.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 8234.50 | 525.50 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8532.67 | 227.33 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8062.83 | 697.17 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8061.50 | 698.50 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8058.67 | 701.33 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8060.17 | 699.83 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8067.67 | 692.33 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8069.00 | 691.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8075.17 | 684.83 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8100.67 | 659.33 | 0.00 | 0.00 | 0.00 |
Min | 8058.67 | 227.33 | 0.00 | 0.00 | 0.00 |
Max | 8532.67 | 701.33 | 0.00 | 0.00 | 0.00 |
Average | 8132.28 | 627.72 | 0.00 | 0.00 | 0.00 |
Sum | 81322.83 | 6277.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 86717.83 | 2323.17 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43033.00 | 744.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 24792.00 | 683.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 24780.83 | 694.17 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 24722.17 | 752.83 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 89906.83 | 3304.17 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 44263.33 | 1648.67 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 44230.00 | 1682.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 44158.67 | 1753.33 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 43950.17 | 1961.83 | 0.00 | 0.00 | 0.00 |
Min | 24722.17 | 683.00 | 0.00 | 0.00 | 0.00 |
Max | 89906.83 | 3304.17 | 0.00 | 0.00 | 0.00 |
Average | 47055.48 | 1554.72 | 0.00 | 0.00 | 0.00 |
Sum | 470554.83 | 15547.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:05
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:05
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Environment
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
For: Environment
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
For: Environment
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.406906E+09 | 13628.99 | 06-JAN-00:02 | -10.0 | -10.7 | 0.106236E+10 | 1275.40 | 29-JAN-18:00 | -6.7 | -7.2 |
February | 0.399368E+09 | 13642.23 | 11-FEB-00:02 | -10.0 | -10.7 | 0.958958E+09 | 1275.40 | 26-FEB-18:00 | -3.3 | -4.2 |
March | 0.198733E+10 | 13377.83 | 04-MAR-00:02 | -9.4 | -10.8 | 0.108233E+10 | 1435.47 | 12-MAR-17:00 | 13.30 | 11.37 |
April | 0.363049E+10 | 10395.03 | 17-APR-08:04 | -0.8 | -2.8 | 0.108792E+10 | 1685.83 | 08-APR-12:00 | -0.8 | -2.8 |
May | 0.647563E+10 | 7741.26 | 14-MAY-15:00 | 26.10 | 17.84 | 0.130409E+10 | 1685.89 | 13-MAY-12:00 | 26.10 | 17.84 |
June | 0.107748E+11 | 32039.49 | 28-JUN-08:62 | 19.18 | 16.35 | 0.134866E+10 | 1686.00 | 02-JUN-12:50 | 19.18 | 16.35 |
July | 0.143655E+11 | 33010.96 | 12-JUL-08:62 | 18.48 | 12.94 | 0.141369E+10 | 1685.99 | 29-JUL-12:09 | 25.68 | 21.35 |
August | 0.139522E+11 | 35217.07 | 06-AUG-07:02 | 20.28 | 15.40 | 0.139448E+10 | 1686.01 | 13-AUG-12:39 | 29.63 | 22.57 |
September | 0.102237E+11 | 29622.98 | 15-SEP-08:62 | 19.27 | 17.62 | 0.135101E+10 | 1685.97 | 09-SEP-12:00 | 19.27 | 17.62 |
October | 0.597187E+10 | 8497.46 | 16-OCT-08:02 | 3.17 | 2.53 | 0.119256E+10 | 1685.93 | 22-OCT-12:00 | 21.70 | 14.82 |
November | 0.279984E+10 | 10738.71 | 24-NOV-09:04 | -1.5 | -2.5 | 0.105403E+10 | 1685.80 | 05-NOV-12:00 | -1.5 | -2.5 |
December | 0.642888E+09 | 15088.38 | 10-DEC-09:04 | -11.4 | -11.8 | 0.106796E+10 | 1275.40 | 10-DEC-18:00 | -13.3 | -13.7 |
Annual Sum or Average | 0.716305E+11 | 0.143180E+11 | ||||||||
Minimum of Months | 0.399368E+09 | 7741.26 | -11.4 | -11.8 | 0.958958E+09 | 1275.40 | -13.3 | -13.7 | ||
Maximum of Months | 0.143655E+11 | 35217.07 | 26.10 | 17.84 | 0.141369E+10 | 1686.01 | 29.63 | 22.57 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.162903E+09 | 6623.45 | 23-JAN-09:04 | -6.8 | -8.7 | 0.539130E+09 | 732.14 | 15-JAN-18:00 | -6.8 | -8.7 |
February | 0.159615E+09 | 6652.51 | 28-FEB-09:04 | -7.2 | -8.1 | 0.485433E+09 | 712.48 | 19-FEB-18:00 | -7.2 | -8.1 |
March | 0.103626E+10 | 13036.55 | 15-MAR-20:47 | 19.27 | 13.89 | 0.560403E+09 | 842.90 | 12-MAR-17:00 | 19.27 | 13.89 |
April | 0.185505E+10 | 5494.48 | 16-APR-08:03 | -2.9 | -4.2 | 0.578116E+09 | 842.91 | 08-APR-12:00 | -2.9 | -4.2 |
May | 0.360164E+10 | 16103.33 | 21-MAY-17:08 | 17.62 | 10.45 | 0.676774E+09 | 842.94 | 13-MAY-12:00 | 17.62 | 10.45 |
June | 0.609955E+10 | 18990.52 | 30-JUN-08:62 | 19.08 | 14.57 | 0.674147E+09 | 842.97 | 02-JUN-12:50 | 19.08 | 14.57 |
July | 0.790181E+10 | 21209.08 | 12-JUL-08:62 | 18.48 | 12.94 | 0.705202E+09 | 842.98 | 23-JUL-12:50 | 23.22 | 18.27 |
August | 0.763492E+10 | 18969.99 | 06-AUG-07:02 | 20.28 | 15.40 | 0.695396E+09 | 843.00 | 13-AUG-12:39 | 29.63 | 22.57 |
September | 0.572755E+10 | 17396.75 | 09-SEP-08:62 | 18.40 | 15.05 | 0.678816E+09 | 842.96 | 09-SEP-12:00 | 21.10 | 14.78 |
October | 0.304154E+10 | 13107.00 | 22-OCT-17:50 | 19.18 | 14.09 | 0.629494E+09 | 842.94 | 22-OCT-12:00 | 19.18 | 14.09 |
November | 0.143615E+10 | 4801.04 | 23-NOV-09:03 | 0.68 | 0.19 | 0.553734E+09 | 842.90 | 05-NOV-17:00 | 0.68 | 0.19 |
December | 0.244256E+09 | 7496.75 | 10-DEC-09:04 | -11.4 | -11.8 | 0.544817E+09 | 736.38 | 24-DEC-18:00 | 5.00 | 2.82 |
Annual Sum or Average | 0.389012E+11 | 0.732146E+10 | ||||||||
Minimum of Months | 0.159615E+09 | 4801.04 | -11.4 | -11.8 | 0.485433E+09 | 712.48 | -7.2 | -8.7 | ||
Maximum of Months | 0.790181E+10 | 21209.08 | 20.28 | 15.40 | 0.705202E+09 | 843.00 | 29.63 | 22.57 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 44890482.33 | 6393.01 | 23-JAN-08:04 | -6.2 | -8.2 | 0.316929E+09 | 637.68 | 21-JAN-13:50 | -6.2 | -8.2 |
February | 51725521.39 | 6968.98 | 13-FEB-08:04 | -9.3 | -9.7 | 0.287872E+09 | 637.68 | 04-FEB-13:09 | -9.3 | -9.7 |
March | 0.708778E+09 | 7080.95 | 04-MAR-08:04 | -9.1 | -10.3 | 0.335665E+09 | 702.46 | 15-MAR-17:00 | 23.90 | 15.62 |
April | 0.139924E+10 | 5698.27 | 16-APR-08:03 | -2.9 | -4.2 | 0.329748E+09 | 842.91 | 08-APR-12:00 | -2.9 | -4.2 |
May | 0.260399E+10 | 8648.04 | 24-MAY-07:03 | 16.52 | 15.53 | 0.399506E+09 | 842.93 | 13-MAY-12:00 | 16.52 | 15.53 |
June | 0.435028E+10 | 17918.46 | 30-JUN-07:02 | 18.40 | 15.33 | 0.414822E+09 | 842.97 | 17-JUN-12:09 | 18.40 | 15.33 |
July | 0.567076E+10 | 21199.90 | 12-JUL-07:02 | 16.97 | 12.15 | 0.420115E+09 | 842.96 | 15-JUL-12:20 | 23.70 | 21.93 |
August | 0.565054E+10 | 20508.89 | 21-AUG-07:02 | 15.78 | 13.76 | 0.431452E+09 | 842.97 | 12-AUG-12:09 | 15.78 | 13.76 |
September | 0.406664E+10 | 17711.92 | 09-SEP-07:03 | 16.47 | 15.12 | 0.406634E+09 | 842.96 | 09-SEP-12:00 | 21.10 | 14.78 |
October | 0.229401E+10 | 4744.25 | 30-OCT-07:03 | 0.87 | -0.3 | 0.357488E+09 | 842.88 | 21-OCT-12:00 | 0.87 | -0.3 |
November | 0.100401E+10 | 5459.74 | 24-NOV-08:04 | -2.6 | -3.4 | 0.313720E+09 | 734.87 | 04-NOV-12:00 | -2.6 | -3.4 |
December | 0.105555E+09 | 7502.88 | 10-DEC-09:04 | -11.4 | -11.8 | 0.316579E+09 | 637.68 | 02-DEC-13:50 | -11.4 | -11.8 |
Annual Sum or Average | 0.279504E+11 | 0.433053E+10 | ||||||||
Minimum of Months | 44890482.33 | 4744.25 | -11.4 | -11.8 | 0.287872E+09 | 637.68 | -11.4 | -11.8 | ||
Maximum of Months | 0.567076E+10 | 21199.90 | 18.40 | 15.53 | 0.431452E+09 | 842.97 | 23.90 | 21.93 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 38248730.21 | 6273.46 | 12-JAN-18:52 | -7.8 | -9.7 | 0.316922E+09 | 637.68 | 21-JAN-13:39 | -0.6 | -3.1 |
February | 43048210.19 | 6438.84 | 10-FEB-18:02 | -8.5 | -9.1 | 0.287866E+09 | 637.68 | 04-FEB-13:09 | -8.5 | -9.1 |
March | 0.638858E+09 | 6471.53 | 01-MAR-08:04 | -6.4 | -7.3 | 0.335244E+09 | 702.46 | 15-MAR-17:00 | 23.90 | 15.62 |
April | 0.127968E+10 | 5727.94 | 17-APR-07:04 | -2.9 | -4.4 | 0.327835E+09 | 842.91 | 08-APR-12:00 | -2.9 | -4.4 |
May | 0.247982E+10 | 7920.81 | 24-MAY-07:03 | 16.52 | 15.53 | 0.396825E+09 | 842.93 | 13-MAY-12:00 | 16.52 | 15.53 |
June | 0.431410E+10 | 17979.72 | 30-JUN-07:02 | 18.40 | 15.33 | 0.414745E+09 | 842.97 | 17-JUN-12:09 | 18.40 | 15.33 |
July | 0.568564E+10 | 21275.71 | 12-JUL-07:02 | 16.97 | 12.15 | 0.420116E+09 | 842.96 | 15-JUL-12:20 | 23.70 | 21.93 |
August | 0.566071E+10 | 20584.82 | 21-AUG-07:02 | 15.78 | 13.76 | 0.431447E+09 | 842.97 | 12-AUG-12:09 | 15.78 | 13.76 |
September | 0.402056E+10 | 17509.12 | 09-SEP-07:03 | 16.47 | 15.12 | 0.406325E+09 | 842.96 | 09-SEP-12:00 | 21.10 | 14.78 |
October | 0.213779E+10 | 5340.47 | 17-OCT-07:05 | -2.4 | -2.9 | 0.355327E+09 | 842.88 | 21-OCT-12:00 | 19.40 | 12.11 |
November | 0.884277E+09 | 5569.72 | 24-NOV-08:04 | -2.6 | -3.4 | 0.312864E+09 | 728.41 | 04-NOV-12:00 | -2.6 | -3.4 |
December | 84564994.40 | 7481.34 | 10-DEC-09:04 | -11.4 | -11.8 | 0.316566E+09 | 637.68 | 02-DEC-13:20 | -11.4 | -11.8 |
Annual Sum or Average | 0.272673E+11 | 0.432208E+10 | ||||||||
Minimum of Months | 38248730.21 | 5340.47 | -11.4 | -11.8 | 0.287866E+09 | 637.68 | -11.4 | -11.8 | ||
Maximum of Months | 0.568564E+10 | 21275.71 | 18.40 | 15.53 | 0.431447E+09 | 842.97 | 23.90 | 21.93 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 26485055.02 | 5715.19 | 21-JAN-08:04 | -3.1 | -4.8 | 0.316916E+09 | 637.68 | 07-JAN-13:30 | -3.1 | -4.8 |
February | 27977546.47 | 6976.99 | 13-FEB-08:04 | -9.3 | -9.7 | 0.287861E+09 | 637.68 | 04-FEB-13:39 | -9.3 | -9.7 |
March | 0.545898E+09 | 6267.63 | 24-MAR-07:03 | -5.4 | -6.3 | 0.334718E+09 | 702.45 | 15-MAR-17:00 | -5.4 | -6.3 |
April | 0.112723E+10 | 5649.19 | 17-APR-07:04 | -2.9 | -4.4 | 0.325682E+09 | 842.90 | 08-APR-12:00 | -2.9 | -4.4 |
May | 0.231864E+10 | 6148.72 | 24-MAY-07:03 | 16.52 | 15.53 | 0.393346E+09 | 842.92 | 13-MAY-12:00 | 16.52 | 15.53 |
June | 0.416247E+10 | 17793.43 | 30-JUN-07:02 | 18.40 | 15.33 | 0.414447E+09 | 842.97 | 17-JUN-12:00 | 18.40 | 15.33 |
July | 0.555006E+10 | 21074.48 | 12-JUL-07:02 | 16.97 | 12.15 | 0.420072E+09 | 842.96 | 15-JUL-12:20 | 23.70 | 21.93 |
August | 0.551926E+10 | 20415.08 | 21-AUG-07:02 | 15.78 | 13.76 | 0.431372E+09 | 842.97 | 12-AUG-12:09 | 15.78 | 13.76 |
September | 0.388065E+10 | 16142.87 | 15-SEP-07:02 | 18.40 | 16.97 | 0.405720E+09 | 842.96 | 09-SEP-12:00 | 18.40 | 16.97 |
October | 0.196480E+10 | 5408.37 | 17-OCT-07:05 | -2.4 | -2.9 | 0.352923E+09 | 842.87 | 21-OCT-12:00 | 19.40 | 12.11 |
November | 0.742201E+09 | 5643.75 | 24-NOV-08:04 | -2.6 | -3.4 | 0.312022E+09 | 720.15 | 04-NOV-12:00 | -2.6 | -3.4 |
December | 59274479.48 | 7511.06 | 10-DEC-09:04 | -11.4 | -11.8 | 0.316553E+09 | 637.68 | 02-DEC-13:20 | -11.4 | -11.8 |
Annual Sum or Average | 0.259249E+11 | 0.431163E+10 | ||||||||
Minimum of Months | 26485055.02 | 5408.37 | -11.4 | -11.8 | 0.287861E+09 | 637.68 | -11.4 | -11.8 | ||
Maximum of Months | 0.555006E+10 | 21074.48 | 18.40 | 16.97 | 0.431372E+09 | 842.97 | 23.70 | 21.93 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 25536826.12 | 10867.31 | 21-JAN-09:04 | -2.0 | -3.9 | 0.108321E+10 | 1700.53 | 07-JAN-15:00 | -2.0 | -3.9 |
February | 31236823.75 | 10933.26 | 12-FEB-10:04 | -3.0 | -3.4 | 0.986206E+09 | 1700.53 | 04-FEB-15:09 | -3.0 | -3.4 |
March | 0.847851E+09 | 11743.98 | 03-MAR-09:04 | -3.7 | -5.7 | 0.114905E+10 | 1995.03 | 15-MAR-16:30 | 25.00 | 15.96 |
April | 0.195509E+10 | 11551.02 | 16-APR-09:04 | -3.3 | -4.3 | 0.111476E+10 | 2247.81 | 08-APR-14:09 | -3.3 | -4.3 |
May | 0.406324E+10 | 6935.90 | 27-MAY-14:30 | 21.70 | 12.26 | 0.133695E+10 | 2247.90 | 13-MAY-14:50 | 21.70 | 12.26 |
June | 0.737355E+10 | 34401.14 | 30-JUN-08:62 | 19.08 | 14.57 | 0.142172E+10 | 2247.99 | 17-JUN-14:09 | 19.08 | 14.57 |
July | 0.994439E+10 | 38184.53 | 12-JUL-08:62 | 18.48 | 12.94 | 0.143851E+10 | 2247.99 | 01-JUL-14:09 | 18.48 | 12.94 |
August | 0.988103E+10 | 37018.97 | 20-AUG-09:02 | 19.60 | 14.41 | 0.147974E+10 | 2247.95 | 26-AUG-14:09 | 25.37 | 21.59 |
September | 0.682328E+10 | 28627.26 | 15-SEP-08:62 | 19.27 | 17.62 | 0.139288E+10 | 2247.97 | 09-SEP-14:20 | 19.27 | 17.62 |
October | 0.338554E+10 | 9531.48 | 17-OCT-08:04 | -0.0 | -1.3 | 0.119826E+10 | 2247.75 | 21-OCT-14:09 | 19.40 | 12.06 |
November | 0.113725E+10 | 10700.52 | 24-NOV-09:04 | -1.5 | -2.5 | 0.106234E+10 | 2089.10 | 04-NOV-14:00 | -1.5 | -2.5 |
December | 72899116.70 | 10740.47 | 09-DEC-09:04 | -1.7 | -2.2 | 0.108509E+10 | 1700.53 | 02-DEC-15:20 | -1.7 | -2.2 |
Annual Sum or Average | 0.455409E+11 | 0.147487E+11 | ||||||||
Minimum of Months | 25536826.12 | 6935.90 | -3.7 | -5.7 | 0.986206E+09 | 1700.53 | -3.3 | -4.3 | ||
Maximum of Months | 0.994439E+10 | 38184.53 | 21.70 | 17.62 | 0.147974E+10 | 2247.99 | 25.37 | 21.59 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11028212.26 | 5430.71 | 21-JAN-09:04 | -2.0 | -3.9 | 0.541588E+09 | 850.24 | 07-JAN-15:30 | -2.0 | -3.9 |
February | 11572520.52 | 5652.98 | 12-FEB-10:04 | -3.0 | -3.4 | 0.493094E+09 | 850.24 | 04-FEB-15:00 | -3.0 | -3.4 |
March | 0.410870E+09 | 5972.98 | 24-MAR-08:04 | -4.3 | -5.8 | 0.574425E+09 | 997.49 | 15-MAR-16:40 | -4.3 | -5.8 |
April | 0.924872E+09 | 5781.01 | 16-APR-09:04 | -3.3 | -4.3 | 0.556468E+09 | 1123.87 | 08-APR-14:09 | -3.3 | -4.3 |
May | 0.198366E+10 | 3524.06 | 27-MAY-14:30 | 21.70 | 12.26 | 0.666933E+09 | 1123.91 | 13-MAY-14:50 | 21.70 | 12.26 |
June | 0.376345E+10 | 17820.32 | 30-JUN-08:62 | 19.08 | 14.57 | 0.710772E+09 | 1123.96 | 17-JUN-14:39 | 19.08 | 14.57 |
July | 0.513920E+10 | 18260.09 | 12-JUL-08:62 | 18.48 | 12.94 | 0.719224E+09 | 1123.96 | 01-JUL-14:09 | 18.48 | 12.94 |
August | 0.509972E+10 | 19198.18 | 20-AUG-09:02 | 19.60 | 14.41 | 0.739856E+09 | 1123.95 | 26-AUG-14:09 | 25.37 | 21.59 |
September | 0.348243E+10 | 14823.75 | 15-SEP-08:62 | 19.27 | 17.62 | 0.696435E+09 | 1123.95 | 09-SEP-14:20 | 19.27 | 17.62 |
October | 0.164862E+10 | 4590.94 | 17-OCT-08:04 | -0.0 | -1.3 | 0.598704E+09 | 1123.85 | 21-OCT-14:09 | 19.40 | 12.06 |
November | 0.536398E+09 | 5348.87 | 24-NOV-09:04 | -1.5 | -2.5 | 0.530839E+09 | 1037.30 | 04-NOV-14:00 | -1.5 | -2.5 |
December | 31696267.70 | 5725.68 | 25-DEC-10:04 | -3.3 | -4.0 | 0.542519E+09 | 850.24 | 09-DEC-15:20 | -3.3 | -4.0 |
Annual Sum or Average | 0.230435E+11 | 0.737086E+10 | ||||||||
Minimum of Months | 11028212.26 | 3524.06 | -4.3 | -5.8 | 0.493094E+09 | 850.24 | -4.3 | -5.8 | ||
Maximum of Months | 0.513920E+10 | 19198.18 | 21.70 | 17.62 | 0.739856E+09 | 1123.96 | 25.37 | 21.59 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9365159.76 | 5416.56 | 21-JAN-09:04 | -2.0 | -3.9 | 0.541588E+09 | 850.24 | 14-JAN-15:09 | -2.0 | -3.9 |
February | 11326632.30 | 5393.46 | 12-FEB-10:04 | -3.0 | -3.4 | 0.493089E+09 | 850.24 | 04-FEB-15:39 | -3.0 | -3.4 |
March | 0.385720E+09 | 5967.28 | 24-MAR-08:04 | -4.3 | -5.8 | 0.574080E+09 | 997.49 | 15-MAR-16:30 | -4.3 | -5.8 |
April | 0.870609E+09 | 5780.00 | 16-APR-09:04 | -3.3 | -4.3 | 0.554874E+09 | 1123.85 | 08-APR-14:20 | -3.3 | -4.3 |
May | 0.189715E+10 | 3391.35 | 27-MAY-14:30 | 21.70 | 12.26 | 0.662997E+09 | 1123.91 | 13-MAY-14:00 | 21.70 | 12.26 |
June | 0.367410E+10 | 17694.50 | 30-JUN-08:62 | 19.08 | 14.57 | 0.710365E+09 | 1123.96 | 17-JUN-14:00 | 19.08 | 14.57 |
July | 0.506652E+10 | 17452.67 | 12-JUL-08:62 | 18.48 | 12.94 | 0.719197E+09 | 1123.96 | 01-JUL-14:09 | 18.48 | 12.94 |
August | 0.502780E+10 | 19072.89 | 20-AUG-09:02 | 19.60 | 14.41 | 0.739792E+09 | 1123.95 | 26-AUG-14:09 | 25.37 | 21.59 |
September | 0.341245E+10 | 14712.72 | 15-SEP-08:62 | 19.27 | 17.62 | 0.695761E+09 | 1123.95 | 09-SEP-14:20 | 19.27 | 17.62 |
October | 0.158250E+10 | 4767.26 | 17-OCT-08:04 | -0.0 | -1.3 | 0.596585E+09 | 1123.85 | 21-OCT-14:09 | 19.40 | 12.06 |
November | 0.495809E+09 | 5329.10 | 24-NOV-09:04 | -1.5 | -2.5 | 0.530346E+09 | 1031.57 | 04-NOV-14:00 | -1.5 | -2.5 |
December | 30177459.14 | 5435.52 | 04-DEC-09:04 | -2.1 | -3.8 | 0.542514E+09 | 850.24 | 02-DEC-15:20 | -2.1 | -3.8 |
Annual Sum or Average | 0.224635E+11 | 0.736119E+10 | ||||||||
Minimum of Months | 9365159.76 | 3391.35 | -4.3 | -5.8 | 0.493089E+09 | 850.24 | -4.3 | -5.8 | ||
Maximum of Months | 0.506652E+10 | 19072.89 | 21.70 | 17.62 | 0.739792E+09 | 1123.96 | 25.37 | 21.59 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4944228.09 | 4866.74 | 22-JAN-10:04 | 0.18 | -1.7 | 0.541588E+09 | 850.24 | 07-JAN-15:20 | 0.18 | -1.7 |
February | 5563946.69 | 5178.57 | 18-FEB-09:04 | -1.0 | -1.7 | 0.493094E+09 | 850.24 | 04-FEB-15:09 | -1.0 | -1.7 |
March | 0.299275E+09 | 5825.78 | 03-MAR-09:04 | -3.7 | -5.7 | 0.573047E+09 | 997.48 | 15-MAR-12:00 | 25.00 | 15.61 |
April | 0.701665E+09 | 4906.65 | 03-APR-08:04 | 0.55 | -0.1 | 0.550768E+09 | 1123.85 | 08-APR-14:20 | 20.20 | 13.55 |
May | 0.167507E+10 | 3270.05 | 08-MAY-08:03 | 7.38 | 1.78 | 0.652320E+09 | 1123.91 | 13-MAY-14:00 | 22.80 | 14.76 |
June | 0.343913E+10 | 15965.81 | 28-JUN-08:62 | 19.18 | 16.35 | 0.708974E+09 | 1123.91 | 10-JUN-14:20 | 19.18 | 16.35 |
July | 0.490715E+10 | 16146.80 | 04-JUL-09:02 | 21.28 | 17.22 | 0.719113E+09 | 1123.96 | 01-JUL-14:30 | 21.28 | 17.22 |
August | 0.486757E+10 | 18783.57 | 20-AUG-09:02 | 19.60 | 14.41 | 0.739527E+09 | 1123.95 | 26-AUG-14:09 | 25.37 | 21.59 |
September | 0.321945E+10 | 14438.91 | 15-SEP-08:62 | 19.27 | 17.62 | 0.693639E+09 | 1123.95 | 09-SEP-14:09 | 19.27 | 17.62 |
October | 0.138121E+10 | 4927.00 | 17-OCT-08:04 | -0.0 | -1.3 | 0.591285E+09 | 1123.85 | 21-OCT-14:09 | 19.40 | 12.06 |
November | 0.382052E+09 | 4788.66 | 22-NOV-09:04 | 1.10 | -1.3 | 0.528905E+09 | 1013.18 | 04-NOV-14:00 | 1.10 | -1.3 |
December | 18031044.55 | 4882.50 | 21-DEC-09:04 | 0.60 | 0.33 | 0.542514E+09 | 850.24 | 02-DEC-15:50 | 0.60 | 0.33 |
Annual Sum or Average | 0.209011E+11 | 0.733478E+10 | ||||||||
Minimum of Months | 4944228.09 | 3270.05 | -3.7 | -5.7 | 0.493094E+09 | 850.24 | -1.0 | -1.7 | ||
Maximum of Months | 0.490715E+10 | 18783.57 | 21.28 | 17.62 | 0.739527E+09 | 1123.96 | 25.37 | 21.59 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1454766.47 | 4350.83 | 15-JAN-10:04 | 2.30 | 1.13 | 0.541588E+09 | 850.24 | 07-JAN-15:50 | 2.30 | 1.13 |
February | 1153576.29 | 3913.32 | 19-FEB-10:04 | 3.98 | -0.3 | 0.493094E+09 | 850.24 | 04-FEB-15:00 | 3.98 | -0.3 |
March | 0.152356E+09 | 4974.75 | 23-MAR-08:04 | -0.2 | -1.0 | 0.571274E+09 | 997.43 | 14-MAR-16:10 | -0.2 | -1.0 |
April | 0.389238E+09 | 4278.63 | 14-APR-08:04 | 2.80 | 1.87 | 0.545084E+09 | 1123.86 | 08-APR-14:20 | 2.80 | 1.87 |
May | 0.125130E+10 | 3066.20 | 08-MAY-08:04 | 7.38 | 1.78 | 0.633747E+09 | 1123.90 | 13-MAY-14:00 | 22.80 | 14.76 |
June | 0.320700E+10 | 15132.67 | 12-JUN-08:62 | 25.28 | 18.91 | 0.705318E+09 | 1123.90 | 10-JUN-14:20 | 25.28 | 18.91 |
July | 0.498952E+10 | 17010.30 | 04-JUL-09:02 | 21.28 | 17.22 | 0.719019E+09 | 1123.97 | 01-JUL-14:50 | 21.28 | 17.22 |
August | 0.492093E+10 | 18100.86 | 11-AUG-08:62 | 19.08 | 15.81 | 0.738720E+09 | 1123.97 | 26-AUG-14:09 | 25.37 | 21.59 |
September | 0.300767E+10 | 14390.14 | 16-SEP-08:62 | 22.98 | 18.69 | 0.688280E+09 | 1123.96 | 09-SEP-14:09 | 22.98 | 18.69 |
October | 0.962961E+09 | 4999.36 | 17-OCT-08:04 | -0.0 | -1.3 | 0.583360E+09 | 1123.86 | 21-OCT-14:09 | 19.40 | 12.06 |
November | 0.158705E+09 | 4684.76 | 22-NOV-09:04 | 1.10 | -1.3 | 0.526598E+09 | 975.10 | 04-NOV-14:00 | 1.10 | -1.3 |
December | 4378732.79 | 4756.00 | 16-DEC-09:04 | 0.68 | -0.3 | 0.542507E+09 | 850.24 | 09-DEC-15:09 | 0.68 | -0.3 |
Annual Sum or Average | 0.190467E+11 | 0.728859E+10 | ||||||||
Minimum of Months | 1153576.29 | 3066.20 | -0.2 | -1.3 | 0.493094E+09 | 850.24 | -0.2 | -1.3 | ||
Maximum of Months | 0.498952E+10 | 18100.86 | 25.28 | 18.91 | 0.738720E+09 | 1123.97 | 25.37 | 21.59 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.841922E+10 | 62049.69 | 30-JAN-08:61 | -10.5 |
February | 0.815745E+10 | 62235.36 | 06-FEB-08:61 | -15.0 |
March | 0.351303E+10 | 62075.09 | 07-MAR-08:61 | -10.8 |
April | 0.888252E+09 | 56503.01 | 12-APR-08:61 | 9.08 |
May | 90084719.84 | 31679.53 | 01-MAY-08:61 | 8.77 |
June | 75843706.27 | 2066.98 | 12-JUN-08:05 | 25.28 |
July | 73671915.50 | 2145.37 | 20-JUL-08:06 | 26.28 |
August | 77979908.80 | 1689.34 | 06-AUG-07:04 | 20.28 |
September | 74997196.11 | 1097.11 | 17-SEP-07:06 | 22.12 |
October | 0.177219E+09 | 55054.43 | 18-OCT-08:61 | 5.78 |
November | 0.120527E+10 | 55308.09 | 30-NOV-09:01 | 5.68 |
December | 0.730889E+10 | 62065.75 | 11-DEC-08:61 | -14.8 |
Annual Sum or Average | 0.300619E+11 | |||
Minimum of Months | 73671915.50 | 1097.11 | -15.0 | |
Maximum of Months | 0.841922E+10 | 62235.36 | 26.28 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.279108E+10 | 31773.31 | 10-JAN-08:61 | -9.9 |
February | 0.272413E+10 | 31879.61 | 06-FEB-08:61 | -15.0 |
March | 0.934618E+09 | 27722.68 | 02-MAR-09:01 | 2.88 |
April | 0.180495E+09 | 27759.71 | 05-APR-08:61 | 3.58 |
May | 42664114.14 | 953.75 | 01-MAY-08:06 | 8.77 |
June | 40476209.18 | 1135.31 | 12-JUN-08:05 | 25.28 |
July | 40779698.26 | 1288.01 | 21-JUL-08:06 | 26.78 |
August | 42819610.83 | 956.01 | 06-AUG-07:04 | 20.28 |
September | 39335680.33 | 649.85 | 17-SEP-07:06 | 22.12 |
October | 51061004.33 | 14760.06 | 17-OCT-08:61 | -0.0 |
November | 0.263895E+09 | 27423.87 | 25-NOV-09:01 | 2.15 |
December | 0.243401E+10 | 31780.13 | 11-DEC-08:61 | -14.8 |
Annual Sum or Average | 0.958537E+10 | |||
Minimum of Months | 39335680.33 | 649.85 | -15.0 | |
Maximum of Months | 0.279108E+10 | 31879.61 | 26.78 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.346358E+10 | 31327.39 | 29-JAN-08:61 | -8.1 |
February | 0.328634E+10 | 31642.32 | 07-FEB-07:01 | -16.5 |
March | 0.126995E+10 | 28233.49 | 06-MAR-07:02 | -10.8 |
April | 0.291443E+09 | 27865.97 | 18-APR-07:01 | 5.18 |
May | 44199836.43 | 991.45 | 08-MAY-07:10 | 5.87 |
June | 49529226.24 | 1397.22 | 17-JUN-17:03 | 28.80 |
July | 59830826.87 | 1653.24 | 16-JUL-16:02 | 30.03 |
August | 55019144.81 | 1429.07 | 13-AUG-16:02 | 29.03 |
September | 43820863.74 | 625.77 | 16-SEP-17:12 | 25.73 |
October | 71610611.88 | 21827.04 | 30-OCT-07:02 | 0.87 |
November | 0.486267E+09 | 26712.00 | 25-NOV-08:61 | -0.2 |
December | 0.303066E+10 | 31508.99 | 11-DEC-07:01 | -16.4 |
Annual Sum or Average | 0.121522E+11 | |||
Minimum of Months | 43820863.74 | 625.77 | -16.5 | |
Maximum of Months | 0.346358E+10 | 31642.32 | 30.03 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.371002E+10 | 31928.90 | 29-JAN-08:61 | -8.1 |
February | 0.349033E+10 | 32251.83 | 07-FEB-07:01 | -16.5 |
March | 0.140151E+10 | 31691.49 | 06-MAR-07:02 | -10.8 |
April | 0.345863E+09 | 28525.48 | 18-APR-07:01 | 5.18 |
May | 46623216.52 | 3106.38 | 01-MAY-07:05 | 6.05 |
June | 49710690.11 | 1400.12 | 17-JUN-17:03 | 28.80 |
July | 59756644.84 | 1653.80 | 16-JUL-16:02 | 30.03 |
August | 55106958.75 | 1429.90 | 13-AUG-16:02 | 29.03 |
September | 43920722.97 | 628.25 | 16-SEP-17:12 | 25.73 |
October | 85035627.92 | 27333.83 | 30-OCT-07:02 | 0.87 |
November | 0.581798E+09 | 27371.13 | 25-NOV-08:61 | -0.2 |
December | 0.323793E+10 | 32115.61 | 11-DEC-07:01 | -16.4 |
Annual Sum or Average | 0.131076E+11 | |||
Minimum of Months | 43920722.97 | 628.25 | -16.5 | |
Maximum of Months | 0.371002E+10 | 32251.83 | 30.03 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.405738E+10 | 31329.57 | 29-JAN-08:61 | -8.1 |
February | 0.379672E+10 | 31658.96 | 06-FEB-07:01 | -14.1 |
March | 0.160088E+10 | 31097.60 | 06-MAR-07:02 | -10.8 |
April | 0.417610E+09 | 27982.03 | 18-APR-07:01 | 5.18 |
May | 48566982.39 | 4784.57 | 01-MAY-07:05 | 6.05 |
June | 50002168.79 | 1405.49 | 17-JUN-17:03 | 28.80 |
July | 60432879.55 | 1657.00 | 16-JUL-16:02 | 30.03 |
August | 55351122.82 | 1433.13 | 13-AUG-16:02 | 29.03 |
September | 43883591.94 | 631.73 | 16-SEP-17:12 | 25.73 |
October | 0.100061E+09 | 26789.13 | 30-OCT-07:02 | 0.87 |
November | 0.693102E+09 | 27105.86 | 19-NOV-09:02 | 2.38 |
December | 0.354773E+10 | 31511.88 | 11-DEC-07:01 | -16.4 |
Annual Sum or Average | 0.144717E+11 | |||
Minimum of Months | 43883591.94 | 631.73 | -16.4 | |
Maximum of Months | 0.405738E+10 | 31658.96 | 30.03 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.761458E+10 | 60838.23 | 10-JAN-08:61 | -9.9 |
February | 0.710299E+10 | 61130.10 | 06-FEB-08:61 | -15.0 |
March | 0.285204E+10 | 60860.32 | 07-MAR-08:61 | -10.8 |
April | 0.728281E+09 | 59179.65 | 16-APR-08:61 | -2.9 |
May | 95795200.05 | 52541.86 | 01-MAY-08:61 | 8.77 |
June | 95297211.05 | 2800.46 | 17-JUN-17:03 | 28.80 |
July | 95769843.90 | 3306.14 | 16-JUL-16:02 | 30.03 |
August | 96503072.48 | 2856.39 | 13-AUG-16:02 | 29.03 |
September | 80800013.89 | 1259.98 | 16-SEP-17:03 | 25.92 |
October | 0.198956E+09 | 53829.63 | 18-OCT-08:61 | 5.78 |
November | 0.121871E+10 | 55579.32 | 14-NOV-09:01 | 9.50 |
December | 0.664239E+10 | 60983.19 | 10-DEC-09:01 | -11.4 |
Annual Sum or Average | 0.268221E+11 | |||
Minimum of Months | 80800013.89 | 1259.98 | -15.0 | |
Maximum of Months | 0.761458E+10 | 61130.10 | 30.03 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.423202E+10 | 31350.01 | 10-JAN-08:61 | -9.9 |
February | 0.394697E+10 | 31500.87 | 06-FEB-08:61 | -15.0 |
March | 0.168059E+10 | 31361.87 | 07-MAR-08:61 | -10.8 |
April | 0.447504E+09 | 29115.24 | 16-APR-08:61 | -2.9 |
May | 53531941.05 | 27494.00 | 01-MAY-08:61 | 8.77 |
June | 51500773.68 | 1417.28 | 17-JUN-17:03 | 28.80 |
July | 51991467.50 | 1664.40 | 16-JUL-16:02 | 30.03 |
August | 52091415.62 | 1440.75 | 13-AUG-16:02 | 29.03 |
September | 44004778.19 | 642.42 | 16-SEP-17:03 | 25.92 |
October | 0.121931E+09 | 27842.65 | 18-OCT-08:61 | 5.78 |
November | 0.734770E+09 | 28709.73 | 14-NOV-09:01 | 9.50 |
December | 0.371173E+10 | 31425.68 | 10-DEC-09:01 | -11.4 |
Annual Sum or Average | 0.151286E+11 | |||
Minimum of Months | 44004778.19 | 642.42 | -15.0 | |
Maximum of Months | 0.423202E+10 | 31500.87 | 30.03 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.431443E+10 | 31236.69 | 10-JAN-08:61 | -9.9 |
February | 0.401489E+10 | 31340.25 | 06-FEB-08:61 | -15.0 |
March | 0.175749E+10 | 31248.52 | 07-MAR-08:61 | -10.8 |
April | 0.489758E+09 | 31180.61 | 16-APR-08:61 | -2.9 |
May | 56454089.91 | 28428.66 | 01-MAY-08:61 | 8.77 |
June | 51479681.45 | 1420.01 | 17-JUN-17:03 | 28.80 |
July | 52064610.77 | 1665.98 | 16-JUL-16:02 | 30.03 |
August | 52042474.94 | 1442.32 | 13-AUG-16:02 | 29.03 |
September | 43855642.79 | 644.78 | 16-SEP-17:03 | 25.92 |
October | 0.134650E+09 | 27751.90 | 18-OCT-08:61 | 5.78 |
November | 0.781673E+09 | 28622.06 | 14-NOV-09:01 | 9.50 |
December | 0.379306E+10 | 31311.77 | 10-DEC-09:01 | -11.4 |
Annual Sum or Average | 0.155418E+11 | |||
Minimum of Months | 43855642.79 | 644.78 | -15.0 | |
Maximum of Months | 0.431443E+10 | 31340.25 | 30.03 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.479846E+10 | 31073.56 | 10-JAN-08:61 | -9.9 |
February | 0.445184E+10 | 31216.10 | 06-FEB-08:61 | -15.0 |
March | 0.211977E+10 | 31086.39 | 07-MAR-08:61 | -10.8 |
April | 0.670018E+09 | 31019.31 | 16-APR-08:61 | -2.9 |
May | 74739372.50 | 28769.36 | 02-MAY-08:61 | 11.65 |
June | 51345376.39 | 1428.03 | 17-JUN-17:03 | 28.80 |
July | 52175200.80 | 1668.62 | 16-JUL-16:02 | 30.03 |
August | 52110633.36 | 1446.13 | 13-AUG-16:02 | 29.03 |
September | 43873290.48 | 648.93 | 16-SEP-17:03 | 25.92 |
October | 0.185830E+09 | 27683.72 | 18-OCT-08:61 | 5.78 |
November | 0.100094E+10 | 30919.28 | 24-NOV-08:61 | -2.6 |
December | 0.424459E+10 | 31149.73 | 10-DEC-09:01 | -11.4 |
Annual Sum or Average | 0.177457E+11 | |||
Minimum of Months | 43873290.48 | 648.93 | -15.0 | |
Maximum of Months | 0.479846E+10 | 31216.10 | 30.03 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.808896E+10 | 32587.93 | 24-JAN-08:61 | -12.1 |
February | 0.768476E+10 | 32573.79 | 07-FEB-08:61 | -15.6 |
March | 0.422378E+10 | 32455.14 | 07-MAR-08:61 | -10.8 |
April | 0.161936E+10 | 32373.20 | 16-APR-08:61 | -2.9 |
May | 0.183841E+09 | 30388.99 | 02-MAY-08:61 | 11.65 |
June | 51071487.59 | 1448.25 | 17-JUN-17:03 | 28.80 |
July | 52891058.44 | 1665.10 | 16-JUL-16:02 | 30.03 |
August | 53464028.22 | 1447.56 | 13-AUG-16:02 | 29.03 |
September | 48427169.01 | 8858.99 | 30-SEP-08:63 | 10.28 |
October | 0.469017E+09 | 31827.59 | 30-OCT-07:02 | 0.87 |
November | 0.208947E+10 | 32264.23 | 24-NOV-08:61 | -2.6 |
December | 0.717986E+10 | 32643.28 | 11-DEC-08:61 | -14.8 |
Annual Sum or Average | 0.317449E+11 | |||
Minimum of Months | 48427169.01 | 1447.56 | -15.6 | |
Maximum of Months | 0.808896E+10 | 32643.28 | 30.03 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.869933E+10 | 5321.43 | 01-JAN-10:09 | 0.223514E+10 | 1348.26 | 01-JAN-10:09 |
February | 0.786449E+10 | 5321.43 | 01-FEB-10:09 | 0.202238E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.870841E+10 | 5321.43 | 01-MAR-10:09 | 0.224215E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.843013E+10 | 5321.43 | 01-APR-09:09 | 0.216638E+10 | 1348.26 | 01-APR-09:09 |
May | 0.869933E+10 | 5321.43 | 01-MAY-09:09 | 0.223514E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.843013E+10 | 5321.43 | 01-JUN-09:09 | 0.217123E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.870841E+10 | 5321.43 | 01-JUL-09:09 | 0.223729E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.869933E+10 | 5321.43 | 01-AUG-09:09 | 0.223756E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.843920E+10 | 5321.43 | 01-SEP-09:09 | 0.217096E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.869933E+10 | 5321.43 | 01-OCT-09:09 | 0.223514E+10 | 1348.26 | 01-OCT-09:09 |
November | 0.840290E+10 | 5321.43 | 01-NOV-09:09 | 0.215964E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.871748E+10 | 5321.43 | 01-DEC-10:09 | 0.224431E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.102498E+12 | 0.263573E+11 | ||||
Minimum of Months | 0.786449E+10 | 5321.43 | 0.202238E+10 | 1348.26 | ||
Maximum of Months | 0.871748E+10 | 5321.43 | 0.224431E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.479410E+10 | 2932.57 | 01-JAN-10:09 | 0.111757E+10 | 674.13 | 01-JAN-10:09 |
February | 0.433403E+10 | 2932.57 | 01-FEB-10:09 | 0.101119E+10 | 674.13 | 01-FEB-10:09 |
March | 0.479910E+10 | 2932.57 | 01-MAR-10:09 | 0.112107E+10 | 674.13 | 01-MAR-10:09 |
April | 0.464574E+10 | 2932.57 | 01-APR-09:09 | 0.108319E+10 | 674.13 | 01-APR-09:09 |
May | 0.479410E+10 | 2932.57 | 01-MAY-09:09 | 0.111757E+10 | 674.13 | 01-MAY-09:09 |
June | 0.464574E+10 | 2932.57 | 01-JUN-09:09 | 0.108562E+10 | 674.13 | 01-JUN-09:09 |
July | 0.479910E+10 | 2932.57 | 01-JUL-09:09 | 0.111865E+10 | 674.13 | 01-JUL-09:09 |
August | 0.479410E+10 | 2932.57 | 01-AUG-09:09 | 0.111878E+10 | 674.13 | 01-AUG-09:09 |
September | 0.465074E+10 | 2932.57 | 01-SEP-09:09 | 0.108548E+10 | 674.13 | 01-SEP-09:09 |
October | 0.479410E+10 | 2932.57 | 01-OCT-09:09 | 0.111757E+10 | 674.13 | 01-OCT-09:09 |
November | 0.463074E+10 | 2932.57 | 01-NOV-09:09 | 0.107982E+10 | 674.13 | 01-NOV-09:09 |
December | 0.480410E+10 | 2932.57 | 01-DEC-10:09 | 0.112215E+10 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.564857E+11 | 0.131787E+11 | ||||
Minimum of Months | 0.433403E+10 | 2932.57 | 0.101119E+10 | 674.13 | ||
Maximum of Months | 0.480410E+10 | 2932.57 | 0.112215E+10 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.338042E+10 | 2599.23 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.306129E+10 | 2599.23 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.345133E+10 | 2599.23 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.327995E+10 | 2599.23 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.341588E+10 | 2599.23 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.333314E+10 | 2599.23 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.336269E+10 | 2599.23 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.345133E+10 | 2599.23 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.327995E+10 | 2599.23 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.338042E+10 | 2599.23 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.327995E+10 | 2599.23 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.336269E+10 | 2599.23 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.400390E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.306129E+10 | 2599.23 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.345133E+10 | 2599.23 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.338042E+10 | 2599.23 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.306129E+10 | 2599.23 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.345133E+10 | 2599.23 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.327995E+10 | 2599.23 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.341588E+10 | 2599.23 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.333314E+10 | 2599.23 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.336269E+10 | 2599.23 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.345133E+10 | 2599.23 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.327995E+10 | 2599.23 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.338042E+10 | 2599.23 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.327995E+10 | 2599.23 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.336269E+10 | 2599.23 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.400390E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.306129E+10 | 2599.23 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.345133E+10 | 2599.23 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.338042E+10 | 2599.23 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.306129E+10 | 2599.23 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.345133E+10 | 2599.23 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.327995E+10 | 2599.23 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.341588E+10 | 2599.23 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.333314E+10 | 2599.23 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.336269E+10 | 2599.23 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.345133E+10 | 2599.23 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.327995E+10 | 2599.23 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.338042E+10 | 2599.23 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.327995E+10 | 2599.23 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.336269E+10 | 2599.23 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.400390E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.306129E+10 | 2599.23 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.345133E+10 | 2599.23 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.447638E+10 | 3746.51 | 01-JAN-11:09 | 0.162546E+10 | 1348.26 | 01-JAN-11:09 |
February | 0.405472E+10 | 3746.51 | 01-FEB-10:09 | 0.147229E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.457860E+10 | 3746.51 | 01-MAR-10:09 | 0.166213E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.434435E+10 | 3746.51 | 01-APR-09:09 | 0.157746E+10 | 1348.26 | 01-APR-09:09 |
May | 0.452749E+10 | 3746.51 | 01-MAY-09:09 | 0.164379E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.442101E+10 | 3746.51 | 01-JUN-09:09 | 0.160496E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.445083E+10 | 3746.51 | 01-JUL-09:09 | 0.161629E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.457860E+10 | 3746.51 | 01-AUG-09:09 | 0.166213E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.434435E+10 | 3746.51 | 01-SEP-09:09 | 0.157746E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.447638E+10 | 3746.51 | 01-OCT-10:09 | 0.162546E+10 | 1348.26 | 01-OCT-10:09 |
November | 0.434435E+10 | 3746.51 | 01-NOV-09:09 | 0.157746E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.445083E+10 | 3746.51 | 01-DEC-10:09 | 0.161629E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.530479E+11 | 0.192612E+11 | ||||
Minimum of Months | 0.405472E+10 | 3746.51 | 0.147229E+10 | 1348.26 | ||
Maximum of Months | 0.457860E+10 | 3746.51 | 0.166213E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.230731E+10 | 1931.10 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.208997E+10 | 1931.10 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.236000E+10 | 1931.10 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.223926E+10 | 1931.10 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.233366E+10 | 1931.10 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.227877E+10 | 1931.10 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.229414E+10 | 1931.10 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.236000E+10 | 1931.10 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.223926E+10 | 1931.10 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.230731E+10 | 1931.10 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.223926E+10 | 1931.10 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.229414E+10 | 1931.10 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.273431E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.208997E+10 | 1931.10 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.236000E+10 | 1931.10 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.230731E+10 | 1931.10 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.208997E+10 | 1931.10 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.236000E+10 | 1931.10 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.223926E+10 | 1931.10 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.233366E+10 | 1931.10 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.227877E+10 | 1931.10 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.229414E+10 | 1931.10 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.236000E+10 | 1931.10 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.223926E+10 | 1931.10 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.230731E+10 | 1931.10 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.223926E+10 | 1931.10 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.229414E+10 | 1931.10 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.273431E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.208997E+10 | 1931.10 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.236000E+10 | 1931.10 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.230731E+10 | 1931.10 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.208997E+10 | 1931.10 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.236000E+10 | 1931.10 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.223926E+10 | 1931.10 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.233366E+10 | 1931.10 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.227877E+10 | 1931.10 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.229414E+10 | 1931.10 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.236000E+10 | 1931.10 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.223926E+10 | 1931.10 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.230731E+10 | 1931.10 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.223926E+10 | 1931.10 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.229414E+10 | 1931.10 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.273431E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.208997E+10 | 1931.10 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.236000E+10 | 1931.10 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.230731E+10 | 1931.10 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.208997E+10 | 1931.10 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.236000E+10 | 1931.10 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.223926E+10 | 1931.10 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.233366E+10 | 1931.10 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.227877E+10 | 1931.10 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.229414E+10 | 1931.10 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.236000E+10 | 1931.10 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.223926E+10 | 1931.10 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.230731E+10 | 1931.10 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.223926E+10 | 1931.10 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.229414E+10 | 1931.10 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.273431E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.208997E+10 | 1931.10 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.236000E+10 | 1931.10 | 0.831065E+09 | 674.13 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.869933E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.767285E+10 |
February | 0.305697E+10 | 0.786449E+10 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.744094E+10 |
March | 0.335708E+10 | 0.870841E+10 | 0.224215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11413926.00 | 0.526062E+10 |
April | 0.327081E+10 | 0.843013E+10 | 0.216638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350249E+10 |
May | 0.336680E+10 | 0.869933E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10366662.57 | 0.199928E+10 |
June | 0.325380E+10 | 0.843013E+10 | 0.217123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183921E+09 | 0.104832E+10 |
July | 0.339353E+10 | 0.870841E+10 | 0.223729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.442547E+09 | 0.374914E+09 |
August | 0.334857E+10 | 0.869933E+10 | 0.223756E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372427E+09 | 0.552667E+09 |
September | 0.327932E+10 | 0.843920E+10 | 0.217096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35643561.20 | 0.133733E+10 |
October | 0.338624E+10 | 0.869933E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313173E+10 |
November | 0.327446E+10 | 0.840290E+10 | 0.215964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426231E+10 |
December | 0.340325E+10 | 0.871748E+10 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.752889E+10 |
Annual Sum or Average | 0.397770E+11 | 0.102498E+12 | 0.263573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105632E+10 | 0.441123E+11 |
Minimum of Months | 0.305697E+10 | 0.786449E+10 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374914E+09 |
Maximum of Months | 0.340325E+10 | 0.871748E+10 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.442547E+09 | 0.767285E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.479410E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370428E+10 |
February | 0.152844E+10 | 0.433403E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353708E+10 |
March | 0.167849E+10 | 0.479910E+10 | 0.112107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6181540.85 | 0.257394E+10 |
April | 0.163536E+10 | 0.464574E+10 | 0.108319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171429E+10 |
May | 0.168335E+10 | 0.479410E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5593237.74 | 0.100382E+10 |
June | 0.162685E+10 | 0.464574E+10 | 0.108562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97728762.30 | 0.478177E+09 |
July | 0.169671E+10 | 0.479910E+10 | 0.111865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236322E+09 | 0.149979E+09 |
August | 0.167424E+10 | 0.479410E+10 | 0.111878E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200302E+09 | 0.234224E+09 |
September | 0.163961E+10 | 0.465074E+10 | 0.108548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19255772.40 | 0.641605E+09 |
October | 0.169307E+10 | 0.479410E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155106E+10 |
November | 0.163718E+10 | 0.463074E+10 | 0.107982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207258E+10 |
December | 0.170157E+10 | 0.480410E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360740E+10 |
Annual Sum or Average | 0.198880E+11 | 0.564857E+11 | 0.131787E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.565383E+09 | 0.212684E+11 |
Minimum of Months | 0.152844E+10 | 0.433403E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149979E+09 |
Maximum of Months | 0.170157E+10 | 0.480410E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236322E+09 | 0.370428E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.338042E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381851E+10 |
February | 0.914877E+09 | 0.306129E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365225E+10 |
March | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6181637.13 | 0.264182E+10 |
April | 0.984131E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176471E+10 |
May | 0.102058E+10 | 0.341588E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5593737.23 | 0.102573E+10 |
June | 0.998711E+09 | 0.333314E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 94551754.03 | 0.502817E+09 |
July | 0.100600E+10 | 0.336269E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230577E+09 | 0.173475E+09 |
August | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195553E+09 | 0.257655E+09 |
September | 0.984131E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19084696.86 | 0.668526E+09 |
October | 0.100722E+10 | 0.338042E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157982E+10 |
November | 0.973196E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212044E+10 |
December | 0.100600E+10 | 0.336269E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373841E+10 |
Annual Sum or Average | 0.119700E+11 | 0.400390E+11 | 0.104672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551541E+09 | 0.219442E+11 |
Minimum of Months | 0.914877E+09 | 0.306129E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173475E+09 |
Maximum of Months | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230577E+09 | 0.381851E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.338042E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381116E+10 |
February | 0.914877E+09 | 0.306129E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364475E+10 |
March | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6181651.69 | 0.263517E+10 |
April | 0.984131E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175250E+10 |
May | 0.102058E+10 | 0.341588E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5593736.92 | 0.101302E+10 |
June | 0.998711E+09 | 0.333314E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 94558500.83 | 0.502120E+09 |
July | 0.100600E+10 | 0.336269E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230534E+09 | 0.173884E+09 |
August | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195546E+09 | 0.257984E+09 |
September | 0.984131E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19084812.97 | 0.666739E+09 |
October | 0.100722E+10 | 0.338042E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156778E+10 |
November | 0.973196E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211104E+10 |
December | 0.100600E+10 | 0.336269E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373043E+10 |
Annual Sum or Average | 0.119700E+11 | 0.400390E+11 | 0.104672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551498E+09 | 0.218666E+11 |
Minimum of Months | 0.914877E+09 | 0.306129E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173884E+09 |
Maximum of Months | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230534E+09 | 0.381116E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.338042E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.380561E+10 |
February | 0.914877E+09 | 0.306129E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363940E+10 |
March | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6181744.26 | 0.262927E+10 |
April | 0.984131E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174075E+10 |
May | 0.102058E+10 | 0.341588E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5593736.63 | 0.997759E+09 |
June | 0.998711E+09 | 0.333314E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 94606607.93 | 0.499162E+09 |
July | 0.100600E+10 | 0.336269E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230652E+09 | 0.171999E+09 |
August | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195588E+09 | 0.256191E+09 |
September | 0.984131E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19085706.87 | 0.663058E+09 |
October | 0.100722E+10 | 0.338042E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155601E+10 |
November | 0.973196E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210332E+10 |
December | 0.100600E+10 | 0.336269E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372438E+10 |
Annual Sum or Average | 0.119700E+11 | 0.400390E+11 | 0.104672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551708E+09 | 0.217869E+11 |
Minimum of Months | 0.914877E+09 | 0.306129E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171999E+09 |
Maximum of Months | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230652E+09 | 0.380561E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.447638E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.700987E+10 |
February | 0.313522E+10 | 0.405472E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.672905E+10 |
March | 0.355148E+10 | 0.457860E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11124200.54 | 0.483585E+10 |
April | 0.338259E+10 | 0.434435E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320959E+10 |
May | 0.349753E+10 | 0.452749E+10 | 0.164379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10070362.51 | 0.183006E+10 |
June | 0.343071E+10 | 0.442101E+10 | 0.160496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170427E+09 | 0.936515E+09 |
July | 0.344942E+10 | 0.445083E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.415613E+09 | 0.334304E+09 |
August | 0.355148E+10 | 0.457860E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352446E+09 | 0.491574E+09 |
September | 0.338259E+10 | 0.434435E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34352333.50 | 0.123360E+10 |
October | 0.344359E+10 | 0.447638E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286228E+10 |
November | 0.331698E+10 | 0.434435E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.387796E+10 |
December | 0.344942E+10 | 0.445083E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.687427E+10 |
Annual Sum or Average | 0.410346E+11 | 0.530479E+11 | 0.192612E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.994032E+09 | 0.402249E+11 |
Minimum of Months | 0.313522E+10 | 0.405472E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334304E+09 |
Maximum of Months | 0.355148E+10 | 0.457860E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.415613E+09 | 0.700987E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382258E+10 |
February | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366073E+10 |
March | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6181914.49 | 0.263899E+10 |
April | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174240E+10 |
May | 0.174872E+10 | 0.233366E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5593735.69 | 0.990422E+09 |
June | 0.171530E+10 | 0.227877E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 94541218.92 | 0.503440E+09 |
July | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230732E+09 | 0.175026E+09 |
August | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195807E+09 | 0.260605E+09 |
September | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19088078.10 | 0.668929E+09 |
October | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155793E+10 |
November | 0.165844E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211135E+10 |
December | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374213E+10 |
Annual Sum or Average | 0.205167E+11 | 0.273431E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551944E+09 | 0.218745E+11 |
Minimum of Months | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175026E+09 |
Maximum of Months | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230732E+09 | 0.382258E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382100E+10 |
February | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365938E+10 |
March | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6182128.83 | 0.263648E+10 |
April | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173653E+10 |
May | 0.174872E+10 | 0.233366E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5593735.48 | 0.979938E+09 |
June | 0.171530E+10 | 0.227877E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 94572761.68 | 0.501400E+09 |
July | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230786E+09 | 0.174136E+09 |
August | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195837E+09 | 0.259736E+09 |
September | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19088547.17 | 0.666679E+09 |
October | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155171E+10 |
November | 0.165844E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210802E+10 |
December | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374029E+10 |
Annual Sum or Average | 0.205167E+11 | 0.273431E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552061E+09 | 0.218353E+11 |
Minimum of Months | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174136E+09 |
Maximum of Months | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230786E+09 | 0.382100E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381128E+10 |
February | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365095E+10 |
March | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6184511.63 | 0.262594E+10 |
April | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171828E+10 |
May | 0.174872E+10 | 0.233366E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5593735.05 | 0.950454E+09 |
June | 0.171530E+10 | 0.227877E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 94660505.57 | 0.494322E+09 |
July | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230925E+09 | 0.171183E+09 |
August | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195903E+09 | 0.256784E+09 |
September | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19089877.87 | 0.659181E+09 |
October | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153438E+10 |
November | 0.165844E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209595E+10 |
December | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373000E+10 |
Annual Sum or Average | 0.205167E+11 | 0.273431E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552356E+09 | 0.216987E+11 |
Minimum of Months | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171183E+09 |
Maximum of Months | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230925E+09 | 0.381128E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.486537E+10 |
February | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.479022E+10 |
March | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6522977.26 | 0.328387E+10 |
April | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219486E+10 |
May | 0.174872E+10 | 0.233366E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5905361.15 | 0.116774E+10 |
June | 0.171530E+10 | 0.227877E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102060E+09 | 0.672842E+09 |
July | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246945E+09 | 0.277844E+09 |
August | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206644E+09 | 0.393222E+09 |
September | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20010650.97 | 0.852133E+09 |
October | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192638E+10 |
November | 0.165844E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265829E+10 |
December | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482914E+10 |
Annual Sum or Average | 0.205167E+11 | 0.273431E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.588087E+09 | 0.279119E+11 |
Minimum of Months | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277844E+09 |
Maximum of Months | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246945E+09 | 0.486537E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 5321.43 | 01-JAN-10:09 | 1348.26 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 11393.74 | 31-JAN-18:00 |
February | 4050.04 | 03-FEB-13:09 | 5321.43 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 12700.39 | 06-FEB-17:00 |
March | 4050.04 | 03-MAR-13:09 | 5321.43 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 659.70 | 15-MAR-14:00 | 10040.83 | 06-MAR-18:00 |
April | 4050.04 | 01-APR-12:09 | 5321.43 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 8058.18 | 16-APR-11:10 |
May | 4050.04 | 05-MAY-12:09 | 5321.43 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 675.88 | 14-MAY-15:00 | 3955.51 | 11-MAY-15:00 |
June | 4050.04 | 02-JUN-12:09 | 5321.43 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2026.26 | 27-JUN-13:00 | 3966.22 | 13-JUN-11:10 |
July | 4050.04 | 01-JUL-12:09 | 5321.43 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2263.15 | 21-JUL-14:00 | 1647.43 | 02-JUL-11:10 |
August | 4050.04 | 04-AUG-12:09 | 5321.43 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1957.97 | 10-AUG-14:00 | 2777.59 | 30-AUG-17:00 |
September | 4050.04 | 01-SEP-12:09 | 5321.43 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1007.76 | 16-SEP-13:00 | 3507.32 | 28-SEP-16:40 |
October | 4050.04 | 01-OCT-12:09 | 5321.43 | 01-OCT-09:09 | 1348.26 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 5309.52 | 23-OCT-17:00 |
November | 4050.04 | 03-NOV-12:09 | 5321.43 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6512.23 | 22-NOV-18:00 |
December | 4050.04 | 01-DEC-13:09 | 5321.43 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 11348.04 | 10-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 5321.43 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1647.43 | |||||
Maximum of Months | 4050.04 | 5321.43 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 2263.15 | 12700.39 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 2932.57 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6179.73 | 31-JAN-18:00 |
February | 2024.96 | 03-FEB-13:09 | 2932.57 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 6778.27 | 06-FEB-18:00 |
March | 2024.96 | 03-MAR-13:09 | 2932.57 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 356.16 | 15-MAR-14:00 | 5458.76 | 06-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 2932.57 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 4348.64 | 16-APR-11:10 |
May | 2024.96 | 05-MAY-12:09 | 2932.57 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 358.89 | 14-MAY-15:00 | 2125.25 | 11-MAY-15:00 |
June | 2024.96 | 02-JUN-12:09 | 2932.57 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.11 | 27-JUN-13:00 | 2234.79 | 13-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 2932.57 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 21-JUL-14:00 | 894.60 | 02-JUL-11:10 |
August | 2024.96 | 04-AUG-12:09 | 2932.57 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1061.95 | 10-AUG-14:00 | 1534.43 | 31-AUG-11:10 |
September | 2024.96 | 01-SEP-12:09 | 2932.57 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 538.90 | 16-SEP-13:00 | 1999.81 | 28-SEP-16:30 |
October | 2024.96 | 01-OCT-12:09 | 2932.57 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2894.78 | 23-OCT-17:00 |
November | 2024.96 | 03-NOV-12:09 | 2932.57 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3585.02 | 22-NOV-18:00 |
December | 2024.96 | 01-DEC-13:09 | 2932.57 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6247.17 | 10-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2932.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 894.60 | |||||
Maximum of Months | 2024.96 | 2932.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 6778.27 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2599.23 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6179.73 | 31-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2599.23 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 6778.27 | 06-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2599.23 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 356.16 | 15-MAR-14:00 | 5458.76 | 06-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 2599.23 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 4348.64 | 16-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 2599.23 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 359.03 | 14-MAY-15:00 | 2105.79 | 11-MAY-15:00 |
June | 2024.96 | 03-JUN-12:09 | 2599.23 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.11 | 27-JUN-13:00 | 2235.41 | 13-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 2599.23 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 21-JUL-14:00 | 894.60 | 02-JUL-11:10 |
August | 2024.96 | 05-AUG-12:09 | 2599.23 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1062.01 | 10-AUG-14:00 | 1531.54 | 31-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 2599.23 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 538.89 | 16-SEP-13:00 | 1980.97 | 28-SEP-16:30 |
October | 2024.96 | 07-OCT-12:09 | 2599.23 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2894.78 | 23-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2599.23 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3585.02 | 22-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2599.23 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6247.17 | 10-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2599.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 894.60 | |||||
Maximum of Months | 2024.96 | 2599.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 6778.27 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2599.23 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6179.73 | 31-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2599.23 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 6778.27 | 06-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2599.23 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 356.16 | 15-MAR-14:00 | 5458.76 | 06-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 2599.23 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 4348.64 | 16-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 2599.23 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 359.03 | 14-MAY-15:00 | 2105.78 | 11-MAY-15:00 |
June | 2024.96 | 03-JUN-12:09 | 2599.23 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.11 | 27-JUN-13:00 | 2233.97 | 13-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 2599.23 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 21-JUL-14:00 | 894.60 | 02-JUL-11:10 |
August | 2024.96 | 05-AUG-12:09 | 2599.23 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1062.01 | 10-AUG-14:00 | 1530.32 | 31-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 2599.23 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 538.89 | 16-SEP-13:00 | 1972.94 | 28-SEP-16:30 |
October | 2024.96 | 07-OCT-12:09 | 2599.23 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2894.78 | 23-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2599.23 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3585.02 | 22-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2599.23 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6247.17 | 10-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2599.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 894.60 | |||||
Maximum of Months | 2024.96 | 2599.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 6778.27 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2599.23 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6179.73 | 31-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2599.23 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 6778.27 | 06-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2599.23 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 356.16 | 15-MAR-14:00 | 5458.76 | 06-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 2599.23 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 4348.64 | 16-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 2599.23 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 359.03 | 14-MAY-15:00 | 2105.78 | 11-MAY-15:00 |
June | 2024.96 | 03-JUN-12:09 | 2599.23 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.11 | 27-JUN-13:00 | 2218.34 | 13-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 2599.23 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 21-JUL-14:00 | 894.60 | 02-JUL-11:10 |
August | 2024.96 | 05-AUG-12:09 | 2599.23 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1062.03 | 10-AUG-14:00 | 1524.69 | 31-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 2599.23 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 538.88 | 16-SEP-13:00 | 1957.36 | 28-SEP-16:30 |
October | 2024.96 | 07-OCT-12:09 | 2599.23 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2894.78 | 23-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2599.23 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3585.02 | 22-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2599.23 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6247.17 | 10-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2599.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 894.60 | |||||
Maximum of Months | 2024.96 | 2599.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 6778.27 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 3746.51 | 01-JAN-11:09 | 1348.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 11118.18 | 31-JAN-18:00 |
February | 5400.05 | 04-FEB-15:09 | 3746.51 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 12216.69 | 06-FEB-18:00 |
March | 5400.05 | 04-MAR-15:09 | 3746.51 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 641.12 | 15-MAR-14:00 | 9818.19 | 06-MAR-18:00 |
April | 5400.05 | 01-APR-14:09 | 3746.51 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 7828.71 | 16-APR-11:10 |
May | 5400.05 | 06-MAY-14:09 | 3746.51 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 647.63 | 14-MAY-15:00 | 3797.45 | 11-MAY-15:00 |
June | 5400.05 | 03-JUN-14:09 | 3746.51 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1949.06 | 27-JUN-13:00 | 3961.97 | 13-JUN-11:10 |
July | 5400.05 | 01-JUL-14:09 | 3746.51 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2212.96 | 21-JUL-14:00 | 1609.19 | 02-JUL-11:10 |
August | 5400.05 | 05-AUG-14:09 | 3746.51 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1910.70 | 10-AUG-14:00 | 2720.92 | 31-AUG-11:10 |
September | 5400.05 | 02-SEP-14:09 | 3746.51 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 971.24 | 16-SEP-13:00 | 3476.54 | 28-SEP-16:30 |
October | 5400.05 | 07-OCT-14:09 | 3746.51 | 01-OCT-10:09 | 1348.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 5204.75 | 23-OCT-17:00 |
November | 5400.05 | 04-NOV-14:09 | 3746.51 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6438.11 | 22-NOV-18:00 |
December | 5400.05 | 02-DEC-15:09 | 3746.51 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 11218.88 | 10-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 3746.51 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1609.19 | |||||
Maximum of Months | 5400.05 | 3746.51 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 2212.96 | 12216.69 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1931.10 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6179.73 | 31-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1931.10 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 6778.27 | 06-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1931.10 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 356.14 | 15-MAR-14:00 | 5458.76 | 06-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1931.10 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 4348.64 | 16-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1931.10 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 359.03 | 14-MAY-15:00 | 2105.78 | 11-MAY-15:00 |
June | 2699.95 | 03-JUN-14:09 | 1931.10 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.11 | 27-JUN-13:00 | 2202.32 | 13-JUN-11:10 |
July | 2699.95 | 01-JUL-14:09 | 1931.10 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 21-JUL-14:00 | 894.54 | 02-JUL-11:10 |
August | 2699.95 | 05-AUG-14:09 | 1931.10 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1062.02 | 10-AUG-14:00 | 1513.62 | 31-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1931.10 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 538.88 | 16-SEP-13:00 | 1939.31 | 28-SEP-16:20 |
October | 2699.95 | 07-OCT-14:09 | 1931.10 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2894.78 | 23-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1931.10 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3585.02 | 22-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1931.10 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6247.17 | 10-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 894.54 | |||||
Maximum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 6778.27 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1931.10 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6179.73 | 31-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1931.10 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 6778.27 | 06-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1931.10 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 356.14 | 15-MAR-14:00 | 5458.76 | 06-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1931.10 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 4348.64 | 16-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1931.10 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 359.03 | 14-MAY-15:00 | 2105.78 | 11-MAY-15:00 |
June | 2699.95 | 03-JUN-14:09 | 1931.10 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.11 | 27-JUN-13:00 | 2191.83 | 13-JUN-11:10 |
July | 2699.95 | 01-JUL-14:09 | 1931.10 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 21-JUL-14:00 | 894.52 | 02-JUL-11:10 |
August | 2699.95 | 05-AUG-14:09 | 1931.10 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1062.03 | 10-AUG-14:00 | 1505.46 | 31-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1931.10 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 538.87 | 16-SEP-13:00 | 1929.44 | 28-SEP-16:20 |
October | 2699.95 | 07-OCT-14:09 | 1931.10 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2894.78 | 23-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1931.10 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3585.02 | 22-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1931.10 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6247.17 | 10-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 894.52 | |||||
Maximum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 6778.27 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1931.10 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6179.73 | 31-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1931.10 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 6778.27 | 06-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1931.10 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 356.14 | 15-MAR-14:00 | 5458.76 | 06-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1931.10 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 4348.64 | 16-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1931.10 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 359.03 | 14-MAY-15:00 | 2105.78 | 11-MAY-15:00 |
June | 2699.95 | 03-JUN-14:09 | 1931.10 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.11 | 27-JUN-13:00 | 2156.28 | 13-JUN-11:10 |
July | 2699.95 | 01-JUL-14:09 | 1931.10 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 21-JUL-14:00 | 894.51 | 02-JUL-11:10 |
August | 2699.95 | 05-AUG-14:09 | 1931.10 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1062.03 | 10-AUG-14:00 | 1496.07 | 30-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1931.10 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 538.87 | 16-SEP-13:00 | 1895.43 | 28-SEP-16:20 |
October | 2699.95 | 07-OCT-14:09 | 1931.10 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2894.78 | 23-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1931.10 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3585.02 | 22-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1931.10 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6247.17 | 10-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 894.51 | |||||
Maximum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 6778.27 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1931.10 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6455.29 | 31-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1931.10 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 7285.77 | 06-FEB-17:00 |
March | 2699.95 | 04-MAR-15:09 | 1931.10 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 374.72 | 15-MAR-14:00 | 5681.40 | 06-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1931.10 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 4578.11 | 16-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1931.10 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 387.28 | 14-MAY-15:00 | 2263.84 | 11-MAY-15:00 |
June | 2699.95 | 03-JUN-14:09 | 1931.10 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1158.31 | 27-JUN-13:00 | 2146.24 | 13-JUN-11:10 |
July | 2699.95 | 01-JUL-14:09 | 1931.10 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1284.48 | 15-JUL-15:00 | 932.71 | 02-JUL-11:10 |
August | 2699.95 | 05-AUG-14:09 | 1931.10 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1109.35 | 10-AUG-14:00 | 1577.82 | 30-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1931.10 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 575.38 | 16-SEP-13:00 | 1850.69 | 28-SEP-16:30 |
October | 2699.95 | 07-OCT-14:09 | 1931.10 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3011.82 | 23-OCT-15:00 |
November | 2699.95 | 04-NOV-14:09 | 1931.10 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3659.14 | 22-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1931.10 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6376.32 | 10-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 932.71 | |||||
Maximum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1284.48 | 7285.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13628.99 | 06-JAN-00:02 | 2025.02 | 1680.33 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 301.34 |
February | 13642.23 | 11-FEB-00:02 | 2025.02 | 16804.44 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.96 |
March | 13377.83 | 04-MAR-00:02 | 2025.02 | 16804.44 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 404.02 |
April | 10395.03 | 17-APR-08:04 | 2700.03 | 22405.92 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1177.13 |
May | 7741.26 | 14-MAY-15:00 | 2700.03 | 5321.43 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 675.88 | 0.00 |
June | 32039.49 | 28-JUN-08:62 | 1687.52 | 14003.70 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 276.60 |
July | 33010.96 | 12-JUL-08:62 | 1687.52 | 14003.70 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.53 |
August | 35217.07 | 06-AUG-07:02 | 1687.52 | 1400.28 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.92 |
September | 29622.98 | 15-SEP-08:62 | 1687.52 | 14003.70 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.41 |
October | 8497.46 | 16-OCT-08:02 | 2700.03 | 22405.92 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 925.38 |
November | 10738.71 | 24-NOV-09:04 | 2700.03 | 22405.92 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1035.85 |
December | 15088.38 | 10-DEC-09:04 | 3375.03 | 28007.41 | 7490.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2018.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7741.26 | 1687.52 | 1400.28 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35217.07 | 3375.03 | 28007.41 | 7490.31 | 0.00 | 0.00 | 0.00 | 0.00 | 675.88 | 2018.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6623.45 | 23-JAN-09:04 | 1349.97 | 12347.66 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 816.34 |
February | 6652.51 | 28-FEB-09:04 | 1349.97 | 12347.66 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 740.37 |
March | 13036.55 | 15-MAR-20:47 | 4049.92 | 11730.27 | 2696.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.27 |
April | 5494.48 | 16-APR-08:03 | 1518.72 | 13891.11 | 3370.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 707.00 |
May | 16103.33 | 21-MAY-17:08 | 12149.77 | 17595.41 | 4044.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.89 |
June | 18990.52 | 30-JUN-08:62 | 843.73 | 7717.28 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.71 |
July | 21209.08 | 12-JUL-08:62 | 843.73 | 7717.28 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.02 |
August | 18969.99 | 06-AUG-07:02 | 843.73 | 771.73 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.02 |
September | 17396.75 | 09-SEP-08:62 | 674.99 | 6173.83 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.53 |
October | 13107.00 | 22-OCT-17:50 | 12149.77 | 17595.41 | 4044.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.15 |
November | 4801.04 | 23-NOV-09:03 | 1012.48 | 9260.74 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 472.44 |
December | 7496.75 | 10-DEC-09:04 | 1687.47 | 15434.57 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 952.39 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4801.04 | 674.99 | 771.73 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 21209.08 | 12149.77 | 17595.41 | 4044.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 952.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6393.01 | 23-JAN-08:04 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 794.14 |
February | 6968.98 | 13-FEB-08:04 | 1687.47 | 13680.14 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1059.17 |
March | 7080.95 | 04-MAR-08:04 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 792.25 |
April | 5698.27 | 16-APR-08:03 | 1518.72 | 12312.12 | 3370.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 712.82 |
May | 8648.04 | 24-MAY-07:03 | 506.24 | 4104.04 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.13 |
June | 17918.46 | 30-JUN-07:02 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.52 |
July | 21199.90 | 12-JUL-07:02 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.66 |
August | 20508.89 | 21-AUG-07:02 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.41 |
September | 17711.92 | 09-SEP-07:03 | 674.99 | 5472.06 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.70 |
October | 4744.25 | 30-OCT-07:03 | 1012.48 | 8208.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 548.02 |
November | 5459.74 | 24-NOV-08:04 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 576.31 |
December | 7502.88 | 10-DEC-09:04 | 1687.47 | 13680.14 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 952.69 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4744.25 | 506.24 | 4104.04 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.52 | |
Maximum of Months | 21199.90 | 1687.47 | 13680.14 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1059.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6273.46 | 12-JAN-18:52 | 8437.34 | 12996.13 | 3370.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 908.88 |
February | 6438.84 | 10-FEB-18:02 | 8437.34 | 12996.13 | 3370.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 758.74 |
March | 6471.53 | 01-MAR-08:04 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 833.14 |
April | 5727.94 | 17-APR-07:04 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 621.16 |
May | 7920.81 | 24-MAY-07:03 | 506.24 | 4104.04 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.00 |
June | 17979.72 | 30-JUN-07:02 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.84 |
July | 21275.71 | 12-JUL-07:02 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.02 |
August | 20584.82 | 21-AUG-07:02 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.79 |
September | 17509.12 | 09-SEP-07:03 | 674.99 | 5472.06 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.65 |
October | 5340.47 | 17-OCT-07:05 | 674.99 | 5472.06 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 587.27 |
November | 5569.72 | 24-NOV-08:04 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 579.34 |
December | 7481.34 | 10-DEC-09:04 | 1687.47 | 13680.14 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 951.99 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5340.47 | 506.24 | 4104.04 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.84 | |
Maximum of Months | 21275.71 | 8437.34 | 13680.14 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 951.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5715.19 | 21-JAN-08:04 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 695.62 |
February | 6976.99 | 13-FEB-08:04 | 1687.47 | 13680.14 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1059.41 |
March | 6267.63 | 24-MAR-07:03 | 1518.72 | 12312.12 | 3370.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 685.89 |
April | 5649.19 | 17-APR-07:04 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 614.14 |
May | 6148.72 | 24-MAY-07:03 | 506.24 | 4104.04 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.66 |
June | 17793.43 | 30-JUN-07:02 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.14 |
July | 21074.48 | 12-JUL-07:02 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.61 |
August | 20415.08 | 21-AUG-07:02 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.87 |
September | 16142.87 | 15-SEP-07:02 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.56 |
October | 5408.37 | 17-OCT-07:05 | 674.99 | 5472.06 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 589.02 |
November | 5643.75 | 24-NOV-08:04 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 580.20 |
December | 7511.06 | 10-DEC-09:04 | 1687.47 | 13680.14 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 952.92 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5408.37 | 506.24 | 4104.04 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.56 | |
Maximum of Months | 21074.48 | 1687.47 | 13680.14 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1059.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10867.31 | 21-JAN-09:04 | 5940.06 | 15774.71 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1247.99 |
February | 10933.26 | 12-FEB-10:04 | 5940.06 | 15774.71 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1316.67 |
March | 11743.98 | 03-MAR-09:04 | 5940.06 | 15774.71 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1209.07 |
April | 11551.02 | 16-APR-09:04 | 5940.06 | 15774.71 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1335.25 |
May | 6935.90 | 27-MAY-14:30 | 5400.05 | 3746.51 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 649.10 |
June | 34401.14 | 30-JUN-08:62 | 3712.53 | 9859.20 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.80 |
July | 38184.53 | 12-JUL-08:62 | 3712.53 | 9859.20 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 230.90 |
August | 37018.97 | 20-AUG-09:02 | 3712.53 | 9859.20 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.85 |
September | 28627.26 | 15-SEP-08:62 | 3712.53 | 9859.20 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.32 |
October | 9531.48 | 17-OCT-08:04 | 5940.06 | 15774.71 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 949.49 |
November | 10700.52 | 24-NOV-09:04 | 5940.06 | 15774.71 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 984.78 |
December | 10740.47 | 09-DEC-09:04 | 5940.06 | 15774.71 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1314.30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6935.90 | 3712.53 | 3746.51 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.32 | |
Maximum of Months | 38184.53 | 5940.06 | 15774.71 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1335.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5430.71 | 21-JAN-09:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 679.92 |
February | 5652.98 | 12-FEB-10:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 715.07 |
March | 5972.98 | 24-MAR-08:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 638.25 |
April | 5781.01 | 16-APR-09:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 727.28 |
May | 3524.06 | 27-MAY-14:30 | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.90 |
June | 17820.32 | 30-JUN-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.17 |
July | 18260.09 | 12-JUL-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.23 |
August | 19198.18 | 20-AUG-09:02 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.05 |
September | 14823.75 | 15-SEP-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.39 |
October | 4590.94 | 17-OCT-08:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 524.40 |
November | 5348.87 | 24-NOV-09:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 547.16 |
December | 5725.68 | 25-DEC-10:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 715.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3524.06 | 1856.21 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.39 | |
Maximum of Months | 19198.18 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 727.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5416.56 | 21-JAN-09:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 678.93 |
February | 5393.46 | 12-FEB-10:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 714.21 |
March | 5967.28 | 24-MAR-08:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 637.78 |
April | 5780.00 | 16-APR-09:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 727.00 |
May | 3391.35 | 27-MAY-14:30 | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.90 |
June | 17694.50 | 30-JUN-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.01 |
July | 17452.67 | 12-JUL-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.11 |
August | 19072.89 | 20-AUG-09:02 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.93 |
September | 14712.72 | 15-SEP-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.36 |
October | 4767.26 | 17-OCT-08:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 525.51 |
November | 5329.10 | 24-NOV-09:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 546.09 |
December | 5435.52 | 04-DEC-09:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 688.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3391.35 | 1856.21 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.36 | |
Maximum of Months | 19072.89 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 727.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4866.74 | 22-JAN-10:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 597.04 |
February | 5178.57 | 18-FEB-09:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 569.82 |
March | 5825.78 | 03-MAR-09:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 661.32 |
April | 4906.65 | 03-APR-08:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 539.50 |
May | 3270.05 | 08-MAY-08:03 | 2598.70 | 7114.56 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 376.16 |
June | 15965.81 | 28-JUN-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.26 |
July | 16146.80 | 04-JUL-09:02 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.40 |
August | 18783.57 | 20-AUG-09:02 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.56 |
September | 14438.91 | 15-SEP-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.44 |
October | 4927.00 | 17-OCT-08:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 530.22 |
November | 4788.66 | 22-NOV-09:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 491.33 |
December | 4882.50 | 21-DEC-09:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 533.39 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3270.05 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.40 | |
Maximum of Months | 18783.57 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 661.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4350.83 | 15-JAN-10:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 610.42 |
February | 3913.32 | 19-FEB-10:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 570.99 |
March | 4974.75 | 23-MAR-08:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 954.24 |
April | 4278.63 | 14-APR-08:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 767.68 |
May | 3066.20 | 08-MAY-08:04 | 2598.70 | 7114.56 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 464.61 |
June | 15132.67 | 12-JUN-08:62 | 2227.46 | 6098.20 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 48.36 | 0.00 |
July | 17010.30 | 04-JUL-09:02 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.80 |
August | 18100.86 | 11-AUG-08:62 | 2227.46 | 6098.20 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.38 |
September | 14390.14 | 16-SEP-08:62 | 2227.46 | 6098.20 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.22 |
October | 4999.36 | 17-OCT-08:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 594.12 |
November | 4684.76 | 22-NOV-09:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 530.45 |
December | 4756.00 | 16-DEC-09:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 601.39 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3066.20 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18100.86 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 48.36 | 954.24 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.753308E+11 | 60921.69 | 12-JAN-17:40 | 0.166875E+12 | 247196.16 | 31-JAN-09:09 |
February | 0.674192E+11 | 59676.34 | 13-FEB-17:00 | 0.155868E+12 | 287737.42 | 06-FEB-09:09 |
March | 0.733379E+11 | 60610.67 | 15-MAR-13:00 | 0.935197E+11 | 222648.12 | 06-MAR-09:09 |
April | 0.675913E+11 | 57509.13 | 11-APR-18:49 | 0.376476E+11 | 170047.21 | 17-APR-08:09 |
May | 0.700204E+11 | 62245.71 | 10-MAY-14:20 | 0.218388E+10 | 64209.68 | 01-MAY-08:09 |
June | 0.787626E+11 | 85087.61 | 27-JUN-12:30 | 1645265.40 | 949.27 | 14-JUN-08:20 |
July | 0.935287E+11 | 87883.82 | 15-JUL-14:50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.907005E+11 | 83629.25 | 13-AUG-13:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.758348E+11 | 75637.75 | 16-SEP-12:20 | 42776604.66 | 6543.66 | 30-SEP-08:09 |
October | 0.714059E+11 | 58883.00 | 11-OCT-13:20 | 0.174579E+11 | 122750.67 | 17-OCT-08:09 |
November | 0.706974E+11 | 56790.78 | 29-NOV-19:30 | 0.570496E+11 | 169041.33 | 24-NOV-09:09 |
December | 0.751513E+11 | 58755.34 | 09-DEC-17:00 | 0.152999E+12 | 269834.76 | 11-DEC-09:09 |
Annual Sum or Average | 0.909781E+12 | 0.683645E+12 | ||||
Minimum of Months | 0.674192E+11 | 56790.78 | 0.00 | 0.00 | ||
Maximum of Months | 0.935287E+11 | 87883.82 | 0.166875E+12 | 287737.42 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.373403E+11 | 0.108752E+11 | 0.108804E+11 | 0.00 | 0.105017E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.573312E+10 | 0.00 |
February | 0.337970E+11 | 0.895887E+10 | 0.985143E+10 | 0.00 | 0.959818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521376E+10 | 0.00 |
March | 0.378801E+11 | 0.872651E+10 | 0.110560E+11 | 0.00 | 0.939358E+10 | 0.00 | 0.00 | 0.507203E+09 | 0.00 | 0.00 | 0.00 | 0.577448E+10 | 0.00 |
April | 0.362171E+11 | 0.724044E+10 | 0.105544E+11 | 0.00 | 0.809815E+10 | 0.00 | 0.00 | 6494113.11 | 0.00 | 0.00 | 0.00 | 0.547469E+10 | 0.00 |
May | 0.376032E+11 | 0.646332E+10 | 0.109629E+11 | 0.00 | 0.788208E+10 | 0.00 | 0.00 | 0.156745E+10 | 0.00 | 0.00 | 0.00 | 0.554138E+10 | 0.00 |
June | 0.366114E+11 | 0.579534E+10 | 0.106855E+11 | 0.00 | 0.768420E+10 | 0.00 | 0.00 | 0.127200E+11 | 0.00 | 0.00 | 0.00 | 0.526620E+10 | 0.00 |
July | 0.372230E+11 | 0.614328E+10 | 0.108424E+11 | 0.00 | 0.786722E+10 | 0.00 | 0.00 | 0.261338E+11 | 0.00 | 0.00 | 0.00 | 0.531901E+10 | 0.00 |
August | 0.378660E+11 | 0.700755E+10 | 0.110491E+11 | 0.00 | 0.795760E+10 | 0.00 | 0.00 | 0.214771E+11 | 0.00 | 0.00 | 0.00 | 0.534309E+10 | 0.00 |
September | 0.362312E+11 | 0.792620E+10 | 0.105613E+11 | 0.00 | 0.760101E+10 | 0.00 | 0.00 | 0.834290E+10 | 0.00 | 0.00 | 0.00 | 0.517220E+10 | 0.00 |
October | 0.373403E+11 | 0.942598E+10 | 0.108804E+11 | 0.00 | 0.802424E+10 | 0.00 | 0.00 | 0.288035E+09 | 0.00 | 0.00 | 0.00 | 0.544686E+10 | 0.00 |
November | 0.361749E+11 | 0.101938E+11 | 0.105443E+11 | 0.00 | 0.840373E+10 | 0.00 | 0.00 | 511937.76 | 0.00 | 0.00 | 0.00 | 0.538019E+10 | 0.00 |
December | 0.372370E+11 | 0.111632E+11 | 0.108529E+11 | 0.00 | 0.102374E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.566066E+10 | 0.00 |
Annual Sum or Average | 0.441522E+12 | 0.999197E+11 | 0.128721E+12 | 0.00 | 0.103249E+12 | 0.00 | 0.00 | 0.710435E+11 | 0.00 | 0.00 | 0.00 | 0.653257E+11 | 0.00 |
Minimum of Months | 0.337970E+11 | 0.579534E+10 | 0.985143E+10 | 0.00 | 0.760101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.517220E+10 | 0.00 |
Maximum of Months | 0.378801E+11 | 0.111632E+11 | 0.110560E+11 | 0.00 | 0.105017E+11 | 0.00 | 0.00 | 0.261338E+11 | 0.00 | 0.00 | 0.00 | 0.577448E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.166875E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.155868E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.935197E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.376476E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.218388E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 1645265.40 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 42776604.66 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.174579E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.570496E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.152999E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.683645E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.166875E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 27522.57 | 01-JAN-11:09 | 7619.51 | 01-JAN-06:10 | 8089.53 | 01-JAN-11:09 | 0.00 | 9481.79 | 31-JAN-09:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 27522.57 | 01-FEB-10:09 | 7619.51 | 01-FEB-06:10 | 8089.53 | 01-FEB-10:09 | 0.00 | 10167.02 | 06-FEB-09:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 27522.57 | 01-MAR-10:09 | 7619.51 | 01-MAR-06:10 | 8089.53 | 01-MAR-10:09 | 0.00 | 9067.19 | 06-MAR-09:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 27522.57 | 01-APR-09:09 | 7619.51 | 01-APR-05:10 | 8089.53 | 01-APR-09:09 | 0.00 | 8178.33 | 17-APR-08:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 27522.57 | 01-MAY-09:09 | 7619.51 | 01-MAY-05:10 | 8089.53 | 01-MAY-09:09 | 0.00 | 6395.21 | 01-MAY-08:09 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 27522.57 | 01-JUN-09:09 | 7619.51 | 01-JUN-19:49 | 8089.53 | 01-JUN-09:09 | 0.00 | 7114.56 | 27-JUN-08:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 27522.57 | 01-JUL-09:09 | 7619.51 | 01-JUL-19:00 | 8089.53 | 01-JUL-09:09 | 0.00 | 8262.10 | 21-JUL-08:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 27522.57 | 01-AUG-09:09 | 7619.51 | 01-AUG-19:40 | 8089.53 | 01-AUG-09:09 | 0.00 | 7783.90 | 14-AUG-08:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 27522.57 | 01-SEP-09:09 | 7619.51 | 01-SEP-05:10 | 8089.53 | 01-SEP-09:09 | 0.00 | 6754.05 | 16-SEP-08:09 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 27522.57 | 01-OCT-10:09 | 7619.51 | 01-OCT-05:10 | 8089.53 | 01-OCT-10:09 | 0.00 | 7381.77 | 17-OCT-08:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 27522.57 | 01-NOV-09:09 | 7619.51 | 01-NOV-05:10 | 8089.53 | 01-NOV-09:09 | 0.00 | 8160.60 | 24-NOV-09:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 27522.57 | 01-DEC-10:09 | 7619.51 | 01-DEC-06:10 | 8089.53 | 01-DEC-10:09 | 0.00 | 9864.36 | 11-DEC-09:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 27522.57 | 7619.51 | 8089.53 | 0.00 | 6395.21 | 0.00 | 0.00 | |||||
Maximum of Months | 27522.57 | 7619.51 | 8089.53 | 0.00 | 10167.02 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 11871.16 | 07-JAN-14:20 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 10895.22 | 16-FEB-12:09 | 0.00 |
March | 14276.11 | 15-MAR-14:09 | 0.00 | 0.00 | 0.00 | 10198.03 | 27-MAR-14:09 | 0.00 |
April | 1365.28 | 08-APR-12:00 | 0.00 | 0.00 | 0.00 | 9737.52 | 04-APR-13:09 | 0.00 |
May | 17634.65 | 14-MAY-14:00 | 0.00 | 0.00 | 0.00 | 9318.31 | 24-MAY-17:19 | 0.00 |
June | 38580.62 | 27-JUN-12:00 | 0.00 | 0.00 | 0.00 | 7591.66 | 19-JUN-12:00 | 0.00 |
July | 39114.50 | 20-JUL-12:00 | 0.00 | 0.00 | 0.00 | 9433.58 | 24-JUL-11:39 | 0.00 |
August | 37390.11 | 13-AUG-14:00 | 0.00 | 0.00 | 0.00 | 9707.18 | 28-AUG-12:00 | 0.00 |
September | 28453.12 | 16-SEP-13:00 | 0.00 | 0.00 | 0.00 | 9687.84 | 18-SEP-11:00 | 0.00 |
October | 9620.93 | 11-OCT-14:00 | 0.00 | 0.00 | 0.00 | 11836.86 | 10-OCT-13:30 | 0.00 |
November | 172.01 | 04-NOV-18:10 | 0.00 | 0.00 | 0.00 | 7605.92 | 30-NOV-13:20 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 10208.91 | 23-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7591.66 | 0.00 | ||
Maximum of Months | 39114.50 | 0.00 | 0.00 | 0.00 | 11871.16 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 60921.69 | 12-JAN-17:40 | 27522.57 | 8089.53 | 7619.51 | 0.00 | 8047.20 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 59676.34 | 13-FEB-17:00 | 27522.57 | 8089.53 | 7619.51 | 0.00 | 8257.56 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 60610.67 | 15-MAR-13:00 | 27522.57 | 8089.53 | 0.00 | 0.00 | 5313.82 | 0.00 | 0.00 | 14204.75 | 0.00 |
April | 57509.13 | 11-APR-18:49 | 27522.57 | 8089.53 | 7619.51 | 0.00 | 5761.83 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 62245.71 | 10-MAY-14:20 | 27522.57 | 8089.53 | 0.00 | 0.00 | 5313.82 | 0.00 | 0.00 | 16050.96 | 0.00 |
June | 85087.61 | 27-JUN-12:30 | 27522.57 | 8089.53 | 0.00 | 0.00 | 6423.97 | 0.00 | 0.00 | 36637.62 | 0.00 |
July | 87883.82 | 15-JUL-14:50 | 27522.57 | 8089.53 | 0.00 | 0.00 | 6737.15 | 0.00 | 0.00 | 38277.76 | 0.00 |
August | 83629.25 | 13-AUG-13:09 | 27522.57 | 8089.53 | 0.00 | 0.00 | 6061.99 | 0.00 | 0.00 | 35006.43 | 0.00 |
September | 75637.75 | 16-SEP-12:20 | 27522.57 | 8089.53 | 0.00 | 0.00 | 5313.82 | 0.00 | 0.00 | 27126.90 | 0.00 |
October | 58883.00 | 11-OCT-13:20 | 27522.57 | 8089.53 | 0.00 | 0.00 | 5313.82 | 0.00 | 0.00 | 8244.79 | 0.00 |
November | 56790.78 | 29-NOV-19:30 | 27522.57 | 8089.53 | 7619.51 | 0.00 | 6264.57 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 58755.34 | 09-DEC-17:00 | 27522.57 | 8089.53 | 7619.51 | 0.00 | 8234.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 56790.78 | 27522.57 | 8089.53 | 0.00 | 0.00 | 5313.82 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 87883.82 | 27522.57 | 8089.53 | 7619.51 | 0.00 | 8257.56 | 0.00 | 0.00 | 38277.76 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 247196.16 | 31-JAN-09:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 287737.42 | 06-FEB-09:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 222648.12 | 06-MAR-09:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 170047.21 | 17-APR-08:09 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 64209.68 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 949.27 | 14-JUN-08:20 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 6543.66 | 30-SEP-08:09 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 122750.67 | 17-OCT-08:09 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 169041.33 | 24-NOV-09:09 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 269834.76 | 11-DEC-09:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 287737.42 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 |
February | 1.83 | 20.21 | 0.00 | 20.21 | 0.00 | 20.21 | 0.00 | 20.21 |
March | 1.00 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
April | 0.83 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.54 | 0.17 | 24.54 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 |
November | 0.33 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
December | 1.17 | 20.28 | 0.00 | 20.28 | 0.00 | 20.28 | 0.00 | 20.28 |
Annual Sum or Average | 7.67 | 20.36 | 0.00 | 20.36 | 0.17 | 20.45 | 0.17 | 20.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.33 | 20.55 | 0.00 | 20.55 | 0.17 | 24.54 | 0.17 | 24.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
February | 1.33 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
March | 0.50 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.17 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
Annual Sum or Average | 3.50 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.33 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.55 | 0.17 | 24.55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 24.55 | 0.17 | 24.55 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.55 | 0.17 | 24.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.55 | 0.17 | 24.55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 24.55 | 0.17 | 24.55 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.55 | 0.17 | 24.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.54 | 0.17 | 24.54 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 24.54 | 0.17 | 24.54 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.54 | 0.17 | 24.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.50 | 0.33 | 24.50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.33 | 24.50 | 0.33 | 24.50 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.50 | 0.33 | 24.50 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.48 | 0.17 | 24.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 24.48 | 0.17 | 24.48 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.48 | 0.17 | 24.48 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.46 | 0.17 | 24.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 24.46 | 0.17 | 24.46 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.46 | 0.17 | 24.46 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.17 | 15.00 | 0.00 | 15.00 | 0.00 | 15.00 | 0.00 | 15.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 15.00 | 0.00 | 15.00 | 0.00 | 15.00 | 0.00 | 15.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 15.00 | 0.00 | 15.00 | 0.00 | 15.00 | 0.00 | 15.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.50 | 14.92 | 0.00 | 14.92 | 0.00 | 14.92 | 0.00 | 14.92 |
February | 13.83 | 14.77 | 0.00 | 14.77 | 0.00 | 14.77 | 0.00 | 14.77 |
March | 3.17 | 14.95 | 0.00 | 14.95 | 0.00 | 14.95 | 0.00 | 14.95 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6.67 | 14.89 | 0.00 | 14.89 | 0.00 | 14.89 | 0.00 | 14.89 |
Annual Sum or Average | 32.17 | 14.85 | 0.00 | 14.85 | 0.00 | 14.85 | 0.00 | 14.85 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 13.83 | 14.95 | 0.00 | 14.95 | 0.00 | 14.95 | 0.00 | 14.95 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 20.93 | 464.67 | 20.92 | 464.67 | 20.92 |
February | 448.00 | 20.92 | 427.50 | 20.92 | 427.50 | 20.92 |
March | 476.33 | 21.06 | 247.33 | 20.98 | 247.33 | 20.94 |
April | 473.67 | 21.37 | 69.00 | 21.27 | 69.00 | 21.19 |
May | 329.67 | 22.38 | 44.50 | 22.51 | 5.50 | 22.48 |
June | 114.83 | 23.51 | 294.33 | 23.81 | 53.17 | 23.82 |
July | 100.50 | 24.00 | 473.50 | 23.94 | 100.17 | 23.95 |
August | 67.83 | 23.98 | 448.00 | 23.93 | 61.83 | 23.95 |
September | 110.33 | 23.21 | 280.67 | 23.71 | 33.00 | 23.72 |
October | 418.67 | 21.68 | 32.00 | 21.71 | 17.33 | 21.66 |
November | 477.67 | 21.19 | 86.50 | 21.11 | 86.50 | 21.05 |
December | 496.00 | 20.94 | 404.67 | 20.92 | 404.67 | 20.91 |
Annual Sum or Average | 4009.50 | 21.49 | 3272.67 | 21.86 | 1970.67 | 21.73 |
Minimum of Months | 67.83 | 20.92 | 32.00 | 20.92 | 5.50 | 20.91 |
Maximum of Months | 496.00 | 24.00 | 473.50 | 23.94 | 464.67 | 23.95 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.11 | 349.00 | 21.05 | 349.00 | 21.02 |
February | 448.00 | 21.09 | 316.00 | 21.03 | 316.00 | 21.01 |
March | 467.00 | 21.45 | 108.50 | 21.35 | 106.00 | 21.26 |
April | 457.00 | 22.00 | 17.17 | 21.95 | 17.17 | 21.90 |
May | 257.17 | 23.02 | 54.17 | 23.17 | 0.00 | 23.17 |
June | 72.67 | 23.62 | 280.17 | 23.86 | 32.33 | 23.86 |
July | 52.33 | 23.89 | 455.50 | 23.91 | 52.00 | 23.91 |
August | 29.00 | 23.89 | 421.00 | 23.93 | 27.33 | 23.93 |
September | 62.67 | 23.46 | 283.00 | 23.82 | 19.67 | 23.82 |
October | 368.67 | 22.25 | 26.17 | 22.34 | 2.67 | 22.33 |
November | 471.00 | 21.73 | 16.33 | 21.69 | 16.33 | 21.66 |
December | 496.00 | 21.19 | 260.83 | 21.10 | 260.83 | 21.06 |
Annual Sum or Average | 3677.50 | 21.75 | 2587.83 | 22.14 | 1199.33 | 21.99 |
Minimum of Months | 29.00 | 21.09 | 16.33 | 21.03 | 0.00 | 21.01 |
Maximum of Months | 496.00 | 23.89 | 455.50 | 23.93 | 349.00 | 23.93 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 318.50 | 21.11 | 318.50 | 21.11 |
February | 336.00 | 21.11 | 284.50 | 21.11 | 284.50 | 21.11 |
March | 359.17 | 21.22 | 131.83 | 21.20 | 130.67 | 21.18 |
April | 354.50 | 21.53 | 24.33 | 21.50 | 24.33 | 21.48 |
May | 222.50 | 22.51 | 40.00 | 22.73 | 0.00 | 22.73 |
June | 73.17 | 23.61 | 232.83 | 23.93 | 35.83 | 23.94 |
July | 73.50 | 24.13 | 353.50 | 24.06 | 73.00 | 24.07 |
August | 39.50 | 24.18 | 345.83 | 24.04 | 37.33 | 24.06 |
September | 73.83 | 23.33 | 213.50 | 23.81 | 25.33 | 23.83 |
October | 307.67 | 21.77 | 13.50 | 21.83 | 4.17 | 21.82 |
November | 359.33 | 21.28 | 29.67 | 21.27 | 29.67 | 21.26 |
December | 369.00 | 21.11 | 250.17 | 21.11 | 250.17 | 21.11 |
Annual Sum or Average | 2939.17 | 21.60 | 2238.17 | 22.06 | 1213.50 | 21.96 |
Minimum of Months | 39.50 | 21.11 | 13.50 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 371.00 | 24.18 | 353.50 | 24.06 | 318.50 | 24.07 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 328.50 | 21.11 | 328.50 | 21.11 |
February | 336.00 | 21.11 | 298.33 | 21.11 | 298.33 | 21.11 |
March | 360.33 | 21.22 | 144.83 | 21.18 | 144.83 | 21.17 |
April | 356.67 | 21.49 | 29.50 | 21.46 | 29.50 | 21.44 |
May | 231.83 | 22.45 | 34.17 | 22.63 | 0.17 | 22.63 |
June | 75.83 | 23.60 | 231.33 | 23.92 | 36.67 | 23.93 |
July | 73.17 | 24.13 | 354.17 | 24.06 | 72.67 | 24.07 |
August | 39.50 | 24.18 | 346.33 | 24.04 | 37.33 | 24.06 |
September | 76.50 | 23.30 | 209.83 | 23.80 | 25.50 | 23.82 |
October | 314.67 | 21.74 | 14.67 | 21.79 | 5.83 | 21.78 |
November | 360.00 | 21.26 | 37.33 | 21.25 | 37.33 | 21.24 |
December | 369.00 | 21.11 | 268.00 | 21.11 | 268.00 | 21.11 |
Annual Sum or Average | 2964.50 | 21.59 | 2297.00 | 22.04 | 1284.67 | 21.93 |
Minimum of Months | 39.50 | 21.11 | 14.67 | 21.11 | 0.17 | 21.11 |
Maximum of Months | 371.00 | 24.18 | 354.17 | 24.06 | 328.50 | 24.07 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 338.17 | 21.11 | 338.17 | 21.11 |
February | 336.00 | 21.11 | 310.67 | 21.11 | 310.67 | 21.11 |
March | 361.67 | 21.21 | 160.33 | 21.18 | 160.33 | 21.16 |
April | 357.83 | 21.45 | 35.50 | 21.42 | 35.50 | 21.39 |
May | 244.33 | 22.36 | 27.00 | 22.50 | 1.50 | 22.49 |
June | 82.00 | 23.57 | 226.33 | 23.90 | 38.50 | 23.92 |
July | 76.83 | 24.11 | 352.33 | 24.05 | 76.33 | 24.06 |
August | 41.83 | 24.14 | 343.00 | 24.03 | 38.33 | 24.05 |
September | 82.67 | 23.25 | 203.17 | 23.76 | 26.17 | 23.79 |
October | 323.50 | 21.72 | 15.67 | 21.75 | 7.67 | 21.74 |
November | 360.00 | 21.24 | 47.33 | 21.23 | 47.33 | 21.21 |
December | 369.00 | 21.11 | 290.17 | 21.11 | 290.17 | 21.11 |
Annual Sum or Average | 3006.67 | 21.59 | 2349.67 | 22.01 | 1370.67 | 21.90 |
Minimum of Months | 41.83 | 21.11 | 15.67 | 21.11 | 1.50 | 21.11 |
Maximum of Months | 371.00 | 24.14 | 352.33 | 24.05 | 338.17 | 24.06 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 321.50 | 21.11 | 321.50 | 21.11 |
February | 308.00 | 21.11 | 302.83 | 21.11 | 302.83 | 21.10 |
March | 337.67 | 21.25 | 172.67 | 21.20 | 172.67 | 21.18 |
April | 330.00 | 21.44 | 38.83 | 21.40 | 38.83 | 21.37 |
May | 241.83 | 22.38 | 18.00 | 22.46 | 4.00 | 22.47 |
June | 83.17 | 23.57 | 200.83 | 23.83 | 41.67 | 23.85 |
July | 70.83 | 24.01 | 321.83 | 23.96 | 70.67 | 23.97 |
August | 42.00 | 23.96 | 309.83 | 23.94 | 39.33 | 23.95 |
September | 77.17 | 23.22 | 187.83 | 23.71 | 29.50 | 23.73 |
October | 300.50 | 21.69 | 13.17 | 21.72 | 6.67 | 21.71 |
November | 330.00 | 21.23 | 76.67 | 21.21 | 76.67 | 21.19 |
December | 338.00 | 21.11 | 303.17 | 21.11 | 303.17 | 21.11 |
Annual Sum or Average | 2799.17 | 21.60 | 2267.17 | 21.96 | 1407.50 | 21.86 |
Minimum of Months | 42.00 | 21.11 | 13.17 | 21.11 | 4.00 | 21.10 |
Maximum of Months | 340.00 | 24.01 | 321.83 | 23.96 | 321.50 | 23.97 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 319.83 | 21.11 | 319.83 | 21.11 |
February | 308.00 | 21.11 | 302.83 | 21.11 | 302.83 | 21.11 |
March | 338.50 | 21.25 | 175.17 | 21.20 | 175.17 | 21.18 |
April | 330.00 | 21.43 | 42.17 | 21.39 | 42.17 | 21.36 |
May | 251.33 | 22.41 | 14.50 | 22.46 | 4.83 | 22.46 |
June | 89.83 | 23.59 | 185.50 | 23.83 | 42.17 | 23.84 |
July | 71.33 | 24.00 | 318.00 | 23.96 | 71.00 | 23.97 |
August | 43.17 | 23.96 | 294.83 | 23.94 | 40.00 | 23.95 |
September | 79.67 | 23.25 | 174.00 | 23.71 | 29.83 | 23.72 |
October | 303.33 | 21.71 | 14.00 | 21.73 | 7.83 | 21.72 |
November | 330.00 | 21.23 | 78.17 | 21.21 | 78.17 | 21.19 |
December | 338.00 | 21.11 | 301.50 | 21.11 | 301.50 | 21.11 |
Annual Sum or Average | 2823.17 | 21.61 | 2220.50 | 21.95 | 1415.33 | 21.84 |
Minimum of Months | 43.17 | 21.11 | 14.00 | 21.11 | 4.83 | 21.11 |
Maximum of Months | 340.00 | 24.00 | 319.83 | 23.96 | 319.83 | 23.97 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 321.33 | 21.11 | 321.33 | 21.11 |
February | 308.00 | 21.11 | 303.00 | 21.11 | 303.00 | 21.11 |
March | 340.33 | 21.26 | 181.83 | 21.21 | 181.83 | 21.18 |
April | 330.00 | 21.40 | 49.67 | 21.36 | 49.67 | 21.33 |
May | 263.33 | 22.39 | 13.83 | 22.43 | 6.00 | 22.42 |
June | 93.50 | 23.57 | 181.50 | 23.82 | 43.00 | 23.83 |
July | 72.33 | 24.00 | 317.33 | 23.96 | 71.83 | 23.97 |
August | 45.00 | 23.94 | 292.33 | 23.94 | 41.50 | 23.94 |
September | 82.67 | 23.22 | 170.83 | 23.69 | 30.17 | 23.71 |
October | 306.00 | 21.69 | 14.67 | 21.71 | 9.00 | 21.69 |
November | 330.00 | 21.22 | 86.67 | 21.20 | 86.67 | 21.18 |
December | 338.00 | 21.11 | 303.67 | 21.11 | 303.67 | 21.11 |
Annual Sum or Average | 2849.17 | 21.61 | 2236.67 | 21.93 | 1447.67 | 21.83 |
Minimum of Months | 45.00 | 21.11 | 13.83 | 21.11 | 6.00 | 21.11 |
Maximum of Months | 340.33 | 24.00 | 321.33 | 23.96 | 321.33 | 23.97 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 326.17 | 21.11 | 326.17 | 21.11 |
February | 308.00 | 21.11 | 304.00 | 21.10 | 304.00 | 21.10 |
March | 342.83 | 21.26 | 201.67 | 21.21 | 201.67 | 21.18 |
April | 330.00 | 21.34 | 66.33 | 21.30 | 66.33 | 21.28 |
May | 299.17 | 22.35 | 11.17 | 22.35 | 9.17 | 22.33 |
June | 104.00 | 23.49 | 173.50 | 23.77 | 46.83 | 23.80 |
July | 74.17 | 23.99 | 315.67 | 23.96 | 73.67 | 23.96 |
August | 51.83 | 23.89 | 287.00 | 23.93 | 44.83 | 23.94 |
September | 91.50 | 23.12 | 160.00 | 23.63 | 32.17 | 23.65 |
October | 314.67 | 21.65 | 16.67 | 21.66 | 12.33 | 21.64 |
November | 330.00 | 21.20 | 111.50 | 21.18 | 111.50 | 21.16 |
December | 338.00 | 21.11 | 314.00 | 21.11 | 314.00 | 21.11 |
Annual Sum or Average | 2924.17 | 21.62 | 2287.67 | 21.91 | 1542.67 | 21.81 |
Minimum of Months | 51.83 | 21.11 | 11.17 | 21.10 | 9.17 | 21.10 |
Maximum of Months | 342.83 | 23.99 | 326.17 | 23.96 | 326.17 | 23.96 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.10 | 335.67 | 21.10 | 335.67 | 21.10 |
February | 308.00 | 21.10 | 308.00 | 21.10 | 308.00 | 21.10 |
March | 348.00 | 21.27 | 270.33 | 21.20 | 270.33 | 21.17 |
April | 330.00 | 21.26 | 130.67 | 21.22 | 130.67 | 21.19 |
May | 329.00 | 22.17 | 19.83 | 22.12 | 19.83 | 22.07 |
June | 126.50 | 23.33 | 159.17 | 23.66 | 53.50 | 23.70 |
July | 80.00 | 23.99 | 314.50 | 23.96 | 79.00 | 23.96 |
August | 69.50 | 23.81 | 279.17 | 23.91 | 55.67 | 23.92 |
September | 110.17 | 22.90 | 146.50 | 23.48 | 32.67 | 23.52 |
October | 322.83 | 21.57 | 37.17 | 21.54 | 34.83 | 21.50 |
November | 330.00 | 21.17 | 194.83 | 21.15 | 194.83 | 21.14 |
December | 338.00 | 21.11 | 330.00 | 21.11 | 330.00 | 21.11 |
Annual Sum or Average | 3032.00 | 21.61 | 2525.83 | 21.84 | 1845.00 | 21.74 |
Minimum of Months | 69.50 | 21.10 | 19.83 | 21.10 | 19.83 | 21.10 |
Maximum of Months | 348.00 | 23.99 | 335.67 | 23.96 | 335.67 | 23.96 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 20.92838 | 16.79866 | -0.7040 | 16.01279 |
February | 448.00000 | 20.92309 | 16.74101 | -0.7085 | 16.14277 |
March | 497.00000 | 21.18032 | 25.90074 | -0.4996 | 12.05880 |
April | 479.00000 | 21.40057 | 31.72689 | -0.3539 | 8.79756 |
May | 496.00000 | 22.87653 | 36.54031 | -0.9234 | 25.46379 |
June | 481.00000 | 23.80634 | 46.42046 | -0.4499 | 10.05666 |
July | 495.00000 | 23.92466 | 55.35130 | -0.2944 | 6.98685 |
August | 497.00000 | 23.91535 | 50.36058 | -0.3392 | 7.64039 |
September | 479.00000 | 23.72678 | 46.60870 | -0.4807 | 10.79753 |
October | 496.00000 | 22.01899 | 36.68520 | -0.1214 | 7.40475 |
November | 480.00000 | 21.19840 | 29.54622 | -0.4261 | 9.59036 |
December | 496.00000 | 20.93756 | 20.32074 | -0.6603 | 14.73407 |
Annual Sum or Average | 5840.00000 | 22.24393 | 34.51455 | -0.4958 | 12.13371 |
Minimum of Months | 448.00000 | 20.92309 | 16.74101 | -0.9234 | 6.98685 |
Maximum of Months | 497.00000 | 23.92466 | 55.35130 | -0.1214 | 25.46379 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.11283 | 19.21748 | -0.5871 | 12.78301 |
February | 448.00000 | 21.09023 | 18.91200 | -0.5956 | 12.94476 |
March | 497.00000 | 21.59647 | 27.43323 | -0.3551 | 9.45156 |
April | 479.00000 | 22.08958 | 32.81226 | -0.1743 | 6.97826 |
May | 496.00000 | 23.43099 | 35.85566 | -0.7369 | 17.87085 |
June | 481.00000 | 23.85181 | 45.07080 | -0.4386 | 9.49048 |
July | 495.00000 | 23.89455 | 52.88613 | -0.3249 | 7.41762 |
August | 497.00000 | 23.89795 | 48.69051 | -0.3612 | 7.94682 |
September | 479.00000 | 23.83072 | 45.54309 | -0.4505 | 9.66777 |
October | 496.00000 | 22.66334 | 37.08562 | 0.02803 | 6.77350 |
November | 480.00000 | 21.76604 | 31.02567 | -0.2715 | 7.57172 |
December | 496.00000 | 21.18869 | 22.48262 | -0.5378 | 11.65138 |
Annual Sum or Average | 5840.00000 | 22.54239 | 34.83740 | -0.3996 | 10.04004 |
Minimum of Months | 448.00000 | 21.09023 | 18.91200 | -0.7369 | 6.77350 |
Maximum of Months | 497.00000 | 23.89795 | 52.88613 | 0.02803 | 17.87085 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.10653 | 15.93783 | -0.6330 | 13.59956 |
February | 336.00000 | 21.10625 | 15.89838 | -0.6329 | 13.59106 |
March | 379.00000 | 21.36068 | 24.91169 | -0.4264 | 10.25088 |
April | 360.00000 | 21.56481 | 30.65057 | -0.2966 | 7.74487 |
May | 375.00000 | 23.07925 | 35.32649 | -0.8445 | 22.26260 |
June | 366.00000 | 23.90618 | 45.49207 | -0.4200 | 9.40734 |
July | 369.00000 | 24.03596 | 54.37020 | -0.2699 | 6.86863 |
August | 379.00000 | 24.00380 | 49.38148 | -0.3207 | 7.48136 |
September | 360.00000 | 23.80876 | 45.72294 | -0.4542 | 10.11715 |
October | 371.00000 | 22.12618 | 35.79568 | -0.0888 | 7.05881 |
November | 360.00000 | 21.28908 | 29.22053 | -0.3851 | 8.67579 |
December | 369.00000 | 21.10754 | 19.69454 | -0.5937 | 12.60893 |
Annual Sum or Average | 4395.00000 | 22.38568 | 33.65947 | -0.4463 | 10.80404 |
Minimum of Months | 336.00000 | 21.10625 | 15.89838 | -0.8445 | 6.86863 |
Maximum of Months | 379.00000 | 24.03596 | 54.37020 | -0.0888 | 22.26260 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.10630 | 15.93815 | -0.6443 | 13.90286 |
February | 336.00000 | 21.10615 | 15.89850 | -0.6433 | 13.87348 |
March | 379.00000 | 21.34803 | 24.94986 | -0.4392 | 10.45299 |
April | 360.00000 | 21.51637 | 30.73433 | -0.3166 | 7.93204 |
May | 375.00000 | 23.00005 | 35.48703 | -0.8785 | 23.63683 |
June | 366.00000 | 23.90182 | 45.52852 | -0.4232 | 9.48154 |
July | 369.00000 | 24.03590 | 54.36582 | -0.2693 | 6.85953 |
August | 379.00000 | 24.00343 | 49.38603 | -0.3203 | 7.47652 |
September | 360.00000 | 23.79745 | 45.78418 | -0.4602 | 10.28278 |
October | 371.00000 | 22.06295 | 35.95225 | -0.1107 | 7.09428 |
November | 360.00000 | 21.26440 | 29.27582 | -0.4015 | 8.89629 |
December | 369.00000 | 21.10731 | 19.69490 | -0.6049 | 12.89404 |
Annual Sum or Average | 4395.00000 | 22.36513 | 33.70921 | -0.4585 | 11.06481 |
Minimum of Months | 336.00000 | 21.10615 | 15.89850 | -0.8785 | 6.85953 |
Maximum of Months | 379.00000 | 24.03590 | 54.36582 | -0.1107 | 23.63683 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.10599 | 15.93853 | -0.6569 | 14.25406 |
February | 336.00000 | 21.10587 | 15.89875 | -0.6555 | 14.21369 |
March | 379.00000 | 21.33220 | 24.99836 | -0.4541 | 10.69890 |
April | 360.00000 | 21.46293 | 30.82711 | -0.3376 | 8.14775 |
May | 375.00000 | 22.89559 | 35.71182 | -0.9197 | 25.29269 |
June | 366.00000 | 23.88569 | 45.66546 | -0.4329 | 9.70560 |
July | 369.00000 | 24.03178 | 54.52230 | -0.2735 | 6.90171 |
August | 379.00000 | 23.99788 | 49.50198 | -0.3254 | 7.54744 |
September | 360.00000 | 23.77288 | 45.93335 | -0.4721 | 10.60271 |
October | 371.00000 | 21.99228 | 36.12930 | -0.1327 | 7.13191 |
November | 360.00000 | 21.24172 | 29.32857 | -0.4171 | 9.12253 |
December | 369.00000 | 21.10675 | 19.69554 | -0.6176 | 13.22624 |
Annual Sum or Average | 4395.00000 | 22.33838 | 33.80630 | -0.4738 | 11.40474 |
Minimum of Months | 336.00000 | 21.10587 | 15.89875 | -0.9197 | 6.90171 |
Maximum of Months | 379.00000 | 24.03178 | 54.52230 | -0.1327 | 25.29269 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10534 | 17.39104 | -0.6861 | 15.06928 |
February | 308.00000 | 21.10505 | 17.30541 | -0.6839 | 15.00009 |
March | 348.00000 | 21.32533 | 26.53194 | -0.4762 | 11.12744 |
April | 330.00000 | 21.43506 | 32.36754 | -0.3563 | 8.37596 |
May | 344.00000 | 22.81863 | 37.11550 | -0.9547 | 26.61960 |
June | 336.00000 | 23.83425 | 46.72415 | -0.4460 | 9.87448 |
July | 338.00000 | 23.94744 | 55.33204 | -0.2896 | 7.00231 |
August | 348.00000 | 23.91944 | 50.39792 | -0.3406 | 7.69677 |
September | 330.00000 | 23.73838 | 47.03848 | -0.4808 | 10.74750 |
October | 340.00000 | 21.94079 | 37.67318 | -0.1497 | 7.16359 |
November | 330.00000 | 21.23197 | 30.77036 | -0.4393 | 9.51523 |
December | 338.00000 | 21.10611 | 21.07402 | -0.6468 | 13.99774 |
Annual Sum or Average | 4030.00000 | 22.30298 | 35.10521 | -0.4950 | 11.84957 |
Minimum of Months | 308.00000 | 21.10505 | 17.30541 | -0.9547 | 7.00231 |
Maximum of Months | 348.00000 | 23.94744 | 55.33204 | -0.1497 | 26.61960 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10546 | 17.29413 | -0.6799 | 14.89210 |
February | 308.00000 | 21.10547 | 17.20787 | -0.6783 | 14.83842 |
March | 348.00000 | 21.32493 | 26.43912 | -0.4784 | 11.15287 |
April | 330.00000 | 21.42599 | 32.29045 | -0.3653 | 8.48488 |
May | 344.00000 | 22.80233 | 37.05928 | -0.9751 | 27.41185 |
June | 336.00000 | 23.83447 | 46.69660 | -0.4649 | 10.22451 |
July | 338.00000 | 23.94705 | 55.35144 | -0.3113 | 7.26458 |
August | 348.00000 | 23.92024 | 50.38241 | -0.3614 | 7.98912 |
September | 330.00000 | 23.74282 | 46.98551 | -0.4966 | 11.04180 |
October | 340.00000 | 21.94014 | 37.58006 | -0.1586 | 7.19983 |
November | 330.00000 | 21.22859 | 30.68266 | -0.4434 | 9.57473 |
December | 338.00000 | 21.10613 | 20.97697 | -0.6421 | 13.86467 |
Annual Sum or Average | 4030.00000 | 22.30094 | 35.04093 | -0.5039 | 11.99830 |
Minimum of Months | 308.00000 | 21.10546 | 17.20787 | -0.9751 | 7.19983 |
Maximum of Months | 348.00000 | 23.94705 | 55.35144 | -0.1586 | 27.41185 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10542 | 17.29437 | -0.6832 | 14.98718 |
February | 308.00000 | 21.10517 | 17.20844 | -0.6814 | 14.92717 |
March | 348.00000 | 21.31955 | 26.45829 | -0.4849 | 11.27061 |
April | 330.00000 | 21.40300 | 32.32952 | -0.3766 | 8.62645 |
May | 344.00000 | 22.73483 | 37.21889 | -1.0044 | 28.61809 |
June | 336.00000 | 23.82424 | 46.78910 | -0.4733 | 10.43452 |
July | 338.00000 | 23.94622 | 55.43690 | -0.3150 | 7.31346 |
August | 348.00000 | 23.91875 | 50.44463 | -0.3654 | 8.05316 |
September | 330.00000 | 23.72917 | 47.06990 | -0.5050 | 11.28050 |
October | 340.00000 | 21.90551 | 37.67190 | -0.1708 | 7.23948 |
November | 330.00000 | 21.22165 | 30.69927 | -0.4506 | 9.69365 |
December | 338.00000 | 21.10588 | 20.97750 | -0.6457 | 13.96226 |
Annual Sum or Average | 4030.00000 | 22.28713 | 35.09579 | -0.5124 | 12.20579 |
Minimum of Months | 308.00000 | 21.10517 | 17.20844 | -1.0044 | 7.23948 |
Maximum of Months | 348.00000 | 23.94622 | 55.43690 | -0.1708 | 28.61809 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10514 | 17.29470 | -0.6990 | 15.45064 |
February | 308.00000 | 21.10502 | 17.20873 | -0.6962 | 15.35989 |
March | 348.00000 | 21.30314 | 26.51612 | -0.5075 | 11.71904 |
April | 330.00000 | 21.34374 | 32.43126 | -0.4084 | 9.08164 |
May | 344.00000 | 22.55281 | 37.65365 | -1.0798 | 31.84017 |
June | 336.00000 | 23.78846 | 47.07598 | -0.4952 | 11.05055 |
July | 338.00000 | 23.94402 | 55.65235 | -0.3203 | 7.38666 |
August | 348.00000 | 23.91275 | 50.61666 | -0.3722 | 8.17739 |
September | 330.00000 | 23.68338 | 47.33039 | -0.5278 | 11.99276 |
October | 340.00000 | 21.81932 | 37.89949 | -0.2017 | 7.39765 |
November | 330.00000 | 21.20159 | 30.74730 | -0.4726 | 10.08627 |
December | 338.00000 | 21.10556 | 20.97778 | -0.6615 | 14.40009 |
Annual Sum or Average | 4030.00000 | 22.24891 | 35.24760 | -0.5363 | 12.83776 |
Minimum of Months | 308.00000 | 21.10502 | 17.20873 | -1.0798 | 7.38666 |
Maximum of Months | 348.00000 | 23.94402 | 55.65235 | -0.2017 | 31.84017 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10470 | 17.07986 | -0.7769 | 17.91830 |
February | 308.00000 | 21.10464 | 17.03124 | -0.7717 | 17.73468 |
March | 348.00000 | 21.27456 | 26.41561 | -0.5882 | 13.65776 |
April | 330.00000 | 21.26307 | 32.34717 | -0.4887 | 10.57344 |
May | 344.00000 | 22.24312 | 38.30615 | -1.2287 | 38.65023 |
June | 336.00000 | 23.69713 | 47.58999 | -0.5443 | 12.65624 |
July | 338.00000 | 23.94368 | 56.11539 | -0.3157 | 7.34813 |
August | 348.00000 | 23.89462 | 50.96887 | -0.3753 | 8.36070 |
September | 330.00000 | 23.56269 | 47.78625 | -0.5803 | 13.91375 |
October | 340.00000 | 21.68651 | 38.06438 | -0.2685 | 8.08671 |
November | 330.00000 | 21.17114 | 30.64523 | -0.5408 | 11.54431 |
December | 338.00000 | 21.10516 | 20.81084 | -0.7364 | 16.65109 |
Annual Sum or Average | 4030.00000 | 22.18051 | 35.39703 | -0.6007 | 14.76842 |
Minimum of Months | 308.00000 | 21.10464 | 17.03124 | -1.2287 | 7.34813 |
Maximum of Months | 348.00000 | 23.94368 | 56.11539 | -0.2685 | 38.65023 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.344057E+09 | 94737227.88 | 17.50 | 0.293035E+09 | 51022456.86 | 0.00 | 0.53 | 15-MAR-14:00 | 0.00 | 01-MAR-00:05 | 9344.84 | 15-MAR-14:00 | 8633.63 | 15-MAR-14:00 | 1692.51 | 14-MAR-13:30 | 2544.25 | 15-MAR-14:00 | 0.00 | 01-MAR-00:05 |
April | 1616808.76 | 463957.36 | 1.33 | 1439939.13 | 176869.63 | 0.00 | 0.05 | 08-APR-13:00 | 0.00 | 01-APR-00:05 | 831.84 | 08-APR-13:00 | 753.14 | 08-APR-13:00 | 78.69 | 08-APR-13:00 | 237.17 | 08-APR-13:00 | 0.00 | 01-APR-00:05 |
May | 0.110689E+10 | 0.298030E+09 | 78.86 | 0.984753E+09 | 0.122133E+09 | 0.00 | 0.64 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 | 12191.69 | 14-MAY-15:00 | 9669.38 | 14-MAY-15:00 | 2860.72 | 14-MAY-16:10 | 3170.16 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.101657E+11 | 0.254693E+10 | 315.09 | 0.736500E+10 | 0.280074E+10 | 0.00 | 1.00 | 02-JUN-08:62 | 0.00 | 01-JUN-00:10 | 46360.91 | 18-JUN-07:03 | 32598.21 | 12-JUN-08:62 | 23128.41 | 18-JUN-07:03 | 10096.71 | 27-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.216192E+11 | 0.527946E+10 | 462.53 | 0.144627E+11 | 0.715648E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-00:05 | 47557.86 | 21-JUL-08:61 | 29173.50 | 15-JUL-08:62 | 24331.22 | 22-JUL-08:03 | 10281.84 | 21-JUL-08:13 | 0.00 | 01-JUL-00:05 |
August | 0.169854E+11 | 0.423455E+10 | 427.36 | 0.126910E+11 | 0.429435E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 46730.88 | 14-AUG-08:61 | 33928.98 | 18-AUG-08:62 | 23395.21 | 26-AUG-08:62 | 10025.49 | 14-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.655267E+10 | 0.165440E+10 | 258.02 | 0.457591E+10 | 0.197675E+10 | 0.00 | 1.00 | 08-SEP-08:62 | 0.00 | 01-SEP-00:10 | 45108.69 | 17-SEP-07:02 | 27426.01 | 16-SEP-08:62 | 21685.88 | 14-SEP-08:62 | 9774.81 | 16-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.240971E+09 | 65157798.53 | 24.47 | 0.208712E+09 | 32259336.60 | 0.00 | 0.41 | 11-OCT-16:10 | 0.00 | 01-OCT-00:10 | 7010.40 | 11-OCT-16:10 | 6042.23 | 11-OCT-16:10 | 1002.86 | 11-OCT-17:10 | 1837.95 | 11-OCT-16:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.570165E+11 | 0.141737E+11 | 1585.17 | 0.405826E+11 | 0.164339E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.216192E+11 | 0.527946E+10 | 462.53 | 0.144627E+11 | 0.715648E+10 | 0.00 | 1.00 | 0.00 | 47557.86 | 33928.98 | 24331.22 | 10281.84 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.241666E+09 | 63422305.48 | 20.72 | 0.205650E+09 | 36015826.68 | 0.00 | 1.00 | 15-MAR-20:01 | 0.00 | 01-MAR-00:05 | 21564.89 | 15-MAR-20:01 | 17961.88 | 15-MAR-20:09 | 4233.47 | 15-MAR-20:47 | 4592.02 | 15-MAR-20:01 | 0.00 | 01-MAR-00:05 |
April | 11895037.75 | 3268924.67 | 5.00 | 10915151.80 | 979885.95 | 0.00 | 0.29 | 23-APR-17:10 | 0.00 | 01-APR-00:05 | 2460.43 | 23-APR-17:10 | 2460.43 | 23-APR-17:10 | 157.19 | 09-APR-17:05 | 644.80 | 23-APR-17:10 | 0.00 | 01-APR-00:05 |
May | 0.909619E+09 | 0.230023E+09 | 92.01 | 0.813449E+09 | 96169748.67 | 0.00 | 1.00 | 13-MAY-18:01 | 0.00 | 01-MAY-00:10 | 22181.75 | 14-MAY-17:43 | 20674.67 | 23-MAY-23:00 | 8018.73 | 14-MAY-17:43 | 4717.97 | 14-MAY-17:43 | 0.00 | 01-MAY-00:10 |
June | 0.637922E+10 | 0.153011E+10 | 311.97 | 0.469845E+10 | 0.168077E+10 | 0.00 | 1.00 | 01-JUN-20:02 | 0.00 | 01-JUN-00:10 | 24032.28 | 18-JUN-07:03 | 20948.51 | 10-JUN-18:01 | 12520.99 | 07-JUN-20:10 | 5144.49 | 27-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.126861E+11 | 0.298163E+10 | 425.37 | 0.865136E+10 | 0.403476E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-00:05 | 24203.14 | 21-JUL-08:61 | 18924.63 | 06-JUL-20:01 | 12452.39 | 28-JUL-20:03 | 5260.70 | 21-JUL-08:61 | 0.00 | 01-JUL-00:05 |
August | 0.100896E+11 | 0.241800E+10 | 397.54 | 0.758919E+10 | 0.250039E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 23824.20 | 14-AUG-08:61 | 20163.28 | 03-AUG-20:02 | 12716.97 | 28-AUG-20:03 | 5112.16 | 14-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.417195E+10 | 0.100866E+10 | 259.37 | 0.294573E+10 | 0.122622E+10 | 0.00 | 1.00 | 02-SEP-18:02 | 0.00 | 01-SEP-00:10 | 23825.50 | 15-SEP-20:03 | 18809.75 | 07-SEP-20:01 | 12421.66 | 15-SEP-20:03 | 4997.01 | 15-SEP-20:03 | 0.00 | 01-SEP-00:10 |
October | 0.220800E+09 | 56411233.88 | 34.80 | 0.187604E+09 | 33196176.24 | 0.00 | 1.00 | 22-OCT-17:01 | 0.00 | 01-OCT-00:10 | 21551.76 | 22-OCT-17:07 | 17628.69 | 22-OCT-17:01 | 5382.90 | 22-OCT-18:40 | 4589.14 | 22-OCT-17:07 | 0.00 | 01-OCT-00:10 |
November | 1840525.41 | 511937.76 | 1.08 | 1614407.00 | 226118.41 | 0.00 | 0.15 | 04-NOV-18:10 | 0.00 | 01-NOV-00:10 | 1256.59 | 04-NOV-18:10 | 1000.94 | 04-NOV-18:10 | 255.65 | 04-NOV-18:10 | 344.02 | 04-NOV-18:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.347127E+11 | 0.829204E+10 | 1547.86 | 0.251040E+11 | 0.960872E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.126861E+11 | 0.298163E+10 | 425.37 | 0.865136E+10 | 0.403476E+10 | 0.00 | 1.00 | 0.00 | 24203.14 | 20948.51 | 12716.97 | 5260.70 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.179790E+09 | 48548964.21 | 16.67 | 0.154493E+09 | 25296721.19 | 0.00 | 0.53 | 15-MAR-14:00 | 0.00 | 01-MAR-00:05 | 4883.31 | 15-MAR-14:00 | 4556.64 | 15-MAR-14:00 | 923.89 | 14-MAR-13:00 | 1305.87 | 15-MAR-14:00 | 0.00 | 01-MAR-00:05 |
April | 3740684.03 | 1040757.60 | 2.00 | 3340100.14 | 400583.89 | 0.00 | 0.12 | 08-APR-13:00 | 0.00 | 01-APR-00:05 | 967.79 | 08-APR-13:00 | 881.92 | 08-APR-13:00 | 85.87 | 08-APR-13:00 | 266.66 | 08-APR-13:00 | 0.00 | 01-APR-00:05 |
May | 0.566852E+09 | 0.149549E+09 | 71.33 | 0.508618E+09 | 58233865.90 | 0.00 | 0.80 | 24-MAY-07:03 | 0.00 | 01-MAY-00:10 | 8143.51 | 24-MAY-07:03 | 5031.87 | 24-MAY-07:03 | 3111.64 | 24-MAY-07:03 | 1853.20 | 24-MAY-07:03 | 0.00 | 01-MAY-00:10 |
June | 0.424004E+10 | 0.104426E+10 | 241.63 | 0.312942E+10 | 0.111062E+10 | 0.00 | 1.00 | 02-JUN-07:02 | 0.00 | 01-JUN-00:10 | 24306.86 | 18-JUN-08:62 | 16424.82 | 12-JUN-07:02 | 11250.81 | 27-JUN-07:03 | 5133.41 | 18-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.869657E+10 | 0.208393E+10 | 329.21 | 0.594145E+10 | 0.275513E+10 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:05 | 24677.46 | 21-JUL-07:01 | 16496.56 | 12-JUL-07:02 | 13361.98 | 29-JUL-07:03 | 5227.38 | 21-JUL-07:13 | 0.00 | 01-JUL-00:05 |
August | 0.705472E+10 | 0.172845E+10 | 318.06 | 0.540342E+10 | 0.165130E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 24583.87 | 14-AUG-07:01 | 17580.65 | 06-AUG-08:61 | 12763.41 | 26-AUG-07:02 | 5091.87 | 14-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.284514E+10 | 0.704137E+09 | 212.18 | 0.203009E+10 | 0.815047E+09 | 0.00 | 1.00 | 08-SEP-07:03 | 0.00 | 01-SEP-00:10 | 23584.19 | 16-SEP-07:02 | 14499.96 | 13-SEP-07:03 | 11210.55 | 14-SEP-07:02 | 4960.68 | 16-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 0.101943E+09 | 27179414.68 | 20.33 | 90102979.55 | 11840174.84 | 0.00 | 0.38 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 3332.81 | 11-OCT-15:00 | 3008.11 | 11-OCT-13:00 | 438.61 | 11-OCT-16:10 | 872.80 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.236888E+11 | 0.578709E+10 | 1211.41 | 0.172609E+11 | 0.642786E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.869657E+10 | 0.208393E+10 | 329.21 | 0.594145E+10 | 0.275513E+10 | 0.00 | 1.00 | 0.00 | 24677.46 | 17580.65 | 13361.98 | 5227.38 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.167629E+09 | 45499050.74 | 16.17 | 0.144270E+09 | 23358749.86 | 0.00 | 0.51 | 15-MAR-14:00 | 0.00 | 01-MAR-00:05 | 4700.11 | 15-MAR-14:00 | 4384.68 | 15-MAR-14:00 | 865.32 | 14-MAR-13:00 | 1263.50 | 15-MAR-14:00 | 0.00 | 01-MAR-00:05 |
April | 2372620.40 | 663736.00 | 1.67 | 2123141.72 | 249478.68 | 0.00 | 0.09 | 08-APR-13:00 | 0.00 | 01-APR-00:05 | 750.76 | 08-APR-13:00 | 684.24 | 08-APR-13:00 | 66.52 | 08-APR-13:00 | 208.26 | 08-APR-13:00 | 0.00 | 01-APR-00:05 |
May | 0.528840E+09 | 0.140099E+09 | 69.11 | 0.474754E+09 | 54085363.09 | 0.00 | 0.70 | 24-MAY-07:03 | 0.00 | 01-MAY-00:10 | 6930.68 | 24-MAY-07:03 | 4475.30 | 14-MAY-15:00 | 2651.30 | 24-MAY-07:03 | 1626.16 | 24-MAY-07:03 | 0.00 | 01-MAY-00:10 |
June | 0.420798E+10 | 0.103719E+10 | 238.79 | 0.310491E+10 | 0.110306E+10 | 0.00 | 1.00 | 02-JUN-07:02 | 0.00 | 01-JUN-00:10 | 24367.06 | 18-JUN-08:62 | 16467.22 | 12-JUN-07:02 | 11275.94 | 27-JUN-07:03 | 5146.05 | 18-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.871505E+10 | 0.208879E+10 | 329.58 | 0.595519E+10 | 0.275986E+10 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:05 | 24731.27 | 21-JUL-07:01 | 16544.57 | 12-JUL-07:02 | 13394.75 | 29-JUL-07:03 | 5240.14 | 21-JUL-07:13 | 0.00 | 01-JUL-00:05 |
August | 0.706502E+10 | 0.173134E+10 | 318.12 | 0.541332E+10 | 0.165171E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 24649.81 | 14-AUG-07:01 | 17640.95 | 06-AUG-08:61 | 12798.37 | 26-AUG-07:02 | 5104.49 | 14-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.280191E+10 | 0.694028E+09 | 210.68 | 0.199797E+10 | 0.803933E+09 | 0.00 | 1.00 | 08-SEP-07:03 | 0.00 | 01-SEP-00:10 | 23643.03 | 16-SEP-07:02 | 14088.42 | 13-SEP-07:03 | 11242.61 | 14-SEP-07:02 | 4972.97 | 16-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 86624321.98 | 23221141.83 | 17.00 | 76746685.79 | 9877636.19 | 0.00 | 0.35 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 3037.51 | 11-OCT-15:00 | 2720.56 | 11-OCT-13:00 | 400.86 | 11-OCT-16:10 | 802.32 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.235754E+11 | 0.576083E+10 | 1201.12 | 0.171693E+11 | 0.640613E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.871505E+10 | 0.208879E+10 | 329.58 | 0.595519E+10 | 0.275986E+10 | 0.00 | 1.00 | 0.00 | 24731.27 | 17640.95 | 13394.75 | 5240.14 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.153387E+09 | 41875437.59 | 15.58 | 0.132067E+09 | 21319679.95 | 0.00 | 0.49 | 15-MAR-14:00 | 0.00 | 01-MAR-00:05 | 4460.54 | 15-MAR-14:00 | 4155.38 | 15-MAR-14:00 | 810.13 | 14-MAR-13:00 | 1206.43 | 15-MAR-14:00 | 0.00 | 01-MAR-00:05 |
April | 929832.72 | 261980.47 | 1.33 | 833884.27 | 95948.45 | 0.00 | 0.06 | 08-APR-13:00 | 0.00 | 01-APR-00:05 | 467.31 | 08-APR-13:00 | 425.34 | 08-APR-13:00 | 41.97 | 08-APR-13:00 | 130.77 | 08-APR-13:00 | 0.00 | 01-APR-00:05 |
May | 0.478910E+09 | 0.127510E+09 | 64.39 | 0.429613E+09 | 49296733.42 | 0.00 | 0.55 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 | 5352.71 | 14-MAY-15:00 | 4278.45 | 14-MAY-15:00 | 1552.60 | 24-MAY-07:03 | 1402.86 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.407337E+10 | 0.100614E+10 | 232.53 | 0.300117E+10 | 0.107220E+10 | 0.00 | 1.00 | 02-JUN-07:02 | 0.00 | 01-JUN-00:10 | 24279.90 | 18-JUN-08:62 | 16380.88 | 12-JUN-07:02 | 11271.77 | 27-JUN-07:03 | 5129.74 | 18-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.853475E+10 | 0.204964E+10 | 328.23 | 0.582582E+10 | 0.270893E+10 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:05 | 24668.78 | 21-JUL-07:01 | 16456.86 | 12-JUL-07:02 | 13384.38 | 29-JUL-07:03 | 5224.07 | 21-JUL-07:13 | 0.00 | 01-JUL-00:05 |
August | 0.690690E+10 | 0.169599E+10 | 316.64 | 0.529100E+10 | 0.161590E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 24565.03 | 14-AUG-07:01 | 17555.32 | 06-AUG-08:61 | 12793.86 | 26-AUG-07:02 | 5088.47 | 14-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.268293E+10 | 0.666097E+09 | 204.79 | 0.190980E+10 | 0.773129E+09 | 0.00 | 1.00 | 08-SEP-07:03 | 0.00 | 01-SEP-00:10 | 23566.69 | 16-SEP-07:02 | 13218.14 | 17-SEP-08:61 | 11241.76 | 14-SEP-07:02 | 4957.23 | 16-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 74521525.94 | 20093199.60 | 13.17 | 66014925.48 | 8506600.46 | 0.00 | 0.32 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 2760.96 | 11-OCT-15:00 | 2453.18 | 11-OCT-15:00 | 368.08 | 11-OCT-16:10 | 734.87 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.229057E+11 | 0.560761E+10 | 1176.66 | 0.166563E+11 | 0.624938E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.853475E+10 | 0.204964E+10 | 328.23 | 0.582582E+10 | 0.270893E+10 | 0.00 | 1.00 | 0.00 | 24668.78 | 17555.32 | 13384.38 | 5224.07 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.278699E+09 | 77371068.39 | 14.92 | 0.233996E+09 | 44703675.94 | 0.00 | 0.50 | 15-MAR-14:10 | 0.00 | 01-MAR-00:05 | 8582.68 | 15-MAR-14:10 | 7799.86 | 15-MAR-14:10 | 1721.25 | 14-MAR-13:00 | 2349.79 | 15-MAR-14:10 | 0.00 | 01-MAR-00:05 |
April | 2326281.07 | 666779.76 | 1.33 | 2039312.88 | 286968.19 | 0.00 | 0.04 | 08-APR-13:30 | 0.00 | 01-APR-00:05 | 596.88 | 08-APR-13:30 | 523.91 | 08-APR-13:30 | 72.97 | 08-APR-13:30 | 170.86 | 08-APR-13:30 | 0.00 | 01-APR-00:05 |
May | 0.877641E+09 | 0.237932E+09 | 61.44 | 0.779683E+09 | 97958320.52 | 0.00 | 0.60 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 | 11020.23 | 14-MAY-15:00 | 8560.17 | 14-MAY-15:00 | 2636.36 | 14-MAY-14:20 | 2895.48 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.758151E+10 | 0.190105E+10 | 224.56 | 0.550622E+10 | 0.207530E+10 | 0.00 | 1.00 | 02-JUN-08:62 | 0.00 | 01-JUN-00:10 | 45432.64 | 18-JUN-09:02 | 31951.64 | 12-JUN-08:62 | 20937.10 | 18-JUN-09:03 | 9823.43 | 18-JUN-09:02 | 0.00 | 01-JUN-00:10 |
July | 0.159601E+11 | 0.389160E+10 | 318.45 | 0.107837E+11 | 0.517648E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-00:05 | 45921.87 | 21-JUL-08:61 | 32018.42 | 12-JUL-08:62 | 23634.63 | 29-JUL-08:62 | 10013.76 | 21-JUL-08:13 | 0.00 | 01-JUL-00:05 |
August | 0.129609E+11 | 0.323284E+10 | 308.99 | 0.982598E+10 | 0.313494E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 46022.42 | 14-AUG-08:61 | 34066.20 | 06-AUG-09:01 | 22945.80 | 26-AUG-08:62 | 9776.83 | 14-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.495013E+10 | 0.124910E+10 | 199.37 | 0.348858E+10 | 0.146154E+10 | 0.00 | 1.00 | 08-SEP-08:62 | 0.00 | 01-SEP-00:10 | 44227.61 | 17-SEP-09:02 | 26823.21 | 16-SEP-08:62 | 21291.41 | 14-SEP-08:62 | 9519.38 | 16-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.130009E+09 | 35682408.65 | 12.00 | 0.113879E+09 | 16129439.82 | 0.00 | 0.35 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 5712.03 | 11-OCT-15:00 | 4991.71 | 11-OCT-15:00 | 720.31 | 11-OCT-15:00 | 1534.83 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.427414E+11 | 0.106262E+11 | 1141.06 | 0.307340E+11 | 0.120073E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.159601E+11 | 0.389160E+10 | 318.45 | 0.107837E+11 | 0.517648E+10 | 0.00 | 1.00 | 0.00 | 46022.42 | 34066.20 | 23634.63 | 10013.76 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.140003E+09 | 38252726.73 | 14.75 | 0.118110E+09 | 21892571.07 | 0.00 | 0.49 | 15-MAR-14:10 | 0.00 | 01-MAR-00:05 | 4414.83 | 15-MAR-14:10 | 4023.36 | 15-MAR-14:10 | 839.94 | 14-MAR-13:00 | 1189.19 | 15-MAR-14:10 | 0.00 | 01-MAR-00:05 |
April | 418067.18 | 118317.02 | 1.17 | 368664.63 | 49402.55 | 0.00 | 0.02 | 08-APR-13:30 | 0.00 | 01-APR-00:05 | 143.35 | 08-APR-13:30 | 126.22 | 08-APR-13:30 | 17.13 | 08-APR-13:30 | 40.53 | 08-APR-13:30 | 0.00 | 01-APR-00:05 |
May | 0.436222E+09 | 0.116405E+09 | 59.50 | 0.388313E+09 | 47909078.25 | 0.00 | 0.59 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 | 5664.07 | 14-MAY-15:00 | 4407.96 | 14-MAY-15:00 | 1339.66 | 14-MAY-14:20 | 1464.73 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.388840E+10 | 0.959137E+09 | 222.02 | 0.283290E+10 | 0.105550E+10 | 0.00 | 1.00 | 02-JUN-08:62 | 0.00 | 01-JUN-00:10 | 23631.93 | 18-JUN-09:02 | 16681.91 | 12-JUN-08:62 | 10857.02 | 18-JUN-09:03 | 5019.73 | 18-JUN-09:02 | 0.00 | 01-JUN-00:10 |
July | 0.822637E+10 | 0.197369E+10 | 318.42 | 0.557724E+10 | 0.264913E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-00:05 | 23872.26 | 21-JUL-08:61 | 15258.82 | 04-JUL-09:02 | 12272.73 | 29-JUL-08:62 | 5116.67 | 21-JUL-08:13 | 0.00 | 01-JUL-00:05 |
August | 0.668158E+10 | 0.163949E+10 | 309.02 | 0.508109E+10 | 0.160049E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 23941.53 | 14-AUG-08:61 | 17785.44 | 06-AUG-09:01 | 11912.12 | 26-AUG-08:62 | 4995.91 | 14-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.253953E+10 | 0.629870E+09 | 197.45 | 0.179340E+10 | 0.746129E+09 | 0.00 | 1.00 | 08-SEP-08:62 | 0.00 | 01-SEP-00:10 | 23006.58 | 17-SEP-09:02 | 13995.24 | 16-SEP-08:62 | 11045.77 | 14-SEP-08:62 | 4864.53 | 16-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 64708260.58 | 17464052.42 | 11.00 | 56855295.71 | 7852964.88 | 0.00 | 0.34 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 2945.46 | 11-OCT-15:00 | 2582.48 | 11-OCT-15:00 | 362.98 | 11-OCT-15:00 | 778.16 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.219772E+11 | 0.537443E+10 | 1133.33 | 0.158483E+11 | 0.612896E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.822637E+10 | 0.197369E+10 | 318.42 | 0.557724E+10 | 0.264913E+10 | 0.00 | 1.00 | 0.00 | 23941.53 | 17785.44 | 12272.73 | 5116.67 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.134985E+09 | 36958572.77 | 14.50 | 0.113842E+09 | 21142403.10 | 0.00 | 0.49 | 15-MAR-14:10 | 0.00 | 01-MAR-00:05 | 4318.12 | 15-MAR-14:10 | 3932.44 | 15-MAR-14:10 | 817.80 | 14-MAR-13:00 | 1165.75 | 15-MAR-14:10 | 0.00 | 01-MAR-00:05 |
April | 34032.31 | 9660.24 | 0.50 | 29977.50 | 4054.81 | 0.00 | 0.00 | 08-APR-13:30 | 0.00 | 01-APR-00:05 | 28.86 | 08-APR-13:30 | 25.39 | 08-APR-13:30 | 3.47 | 08-APR-13:30 | 8.19 | 08-APR-13:30 | 0.00 | 01-APR-00:05 |
May | 0.406690E+09 | 0.108858E+09 | 57.50 | 0.361479E+09 | 45210935.91 | 0.00 | 0.58 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 | 5527.57 | 14-MAY-15:00 | 4294.13 | 14-MAY-15:00 | 1312.18 | 14-MAY-14:20 | 1433.66 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.380911E+10 | 0.940697E+09 | 218.94 | 0.277141E+10 | 0.103770E+10 | 0.00 | 1.00 | 02-JUN-08:62 | 0.00 | 01-JUN-00:10 | 23545.06 | 18-JUN-09:02 | 16594.33 | 12-JUN-08:62 | 10839.47 | 18-JUN-09:03 | 5001.73 | 18-JUN-09:02 | 0.00 | 01-JUN-00:10 |
July | 0.812853E+10 | 0.195202E+10 | 318.08 | 0.550596E+10 | 0.262257E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-00:05 | 23785.09 | 21-JUL-08:61 | 15181.99 | 04-JUL-09:02 | 12246.95 | 29-JUL-08:62 | 5098.43 | 21-JUL-08:13 | 0.00 | 01-JUL-00:05 |
August | 0.659837E+10 | 0.162054E+10 | 308.23 | 0.501598E+10 | 0.158239E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 23851.39 | 14-AUG-08:61 | 17700.38 | 06-AUG-09:01 | 11890.14 | 26-AUG-08:62 | 4978.02 | 14-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.248081E+10 | 0.615808E+09 | 194.90 | 0.174973E+10 | 0.731075E+09 | 0.00 | 1.00 | 09-SEP-08:62 | 0.00 | 01-SEP-00:10 | 22922.78 | 17-SEP-09:02 | 13924.11 | 16-SEP-08:62 | 11024.55 | 14-SEP-08:62 | 4847.09 | 16-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 60565477.45 | 16388673.85 | 10.67 | 53193032.71 | 7372444.74 | 0.00 | 0.33 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 2828.88 | 11-OCT-15:00 | 2478.84 | 11-OCT-15:00 | 350.04 | 11-OCT-15:00 | 749.69 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.216191E+11 | 0.529128E+10 | 1123.32 | 0.155716E+11 | 0.604746E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.812853E+10 | 0.195202E+10 | 318.08 | 0.550596E+10 | 0.262257E+10 | 0.00 | 1.00 | 0.00 | 23851.39 | 17700.38 | 12246.95 | 5098.43 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.119047E+09 | 32812702.55 | 14.00 | 0.100495E+09 | 18552048.64 | 0.00 | 0.46 | 15-MAR-14:10 | 0.00 | 01-MAR-00:05 | 4033.72 | 15-MAR-14:10 | 3668.29 | 15-MAR-14:10 | 726.74 | 14-MAR-13:00 | 1096.98 | 15-MAR-14:10 | 0.00 | 01-MAR-00:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 |
May | 0.337084E+09 | 90960914.23 | 50.50 | 0.298586E+09 | 38497525.37 | 0.00 | 0.55 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 | 5156.30 | 14-MAY-15:00 | 3987.97 | 14-MAY-15:00 | 1231.39 | 14-MAY-14:30 | 1349.15 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.360672E+10 | 0.893657E+09 | 212.17 | 0.261666E+10 | 0.990058E+09 | 0.00 | 1.00 | 02-JUN-08:62 | 0.00 | 01-JUN-00:10 | 23408.30 | 18-JUN-09:02 | 16877.74 | 12-JUN-08:62 | 10789.37 | 18-JUN-09:02 | 4974.10 | 18-JUN-09:02 | 0.00 | 01-JUN-00:10 |
July | 0.791099E+10 | 0.190409E+10 | 316.98 | 0.535276E+10 | 0.255823E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-00:05 | 23648.03 | 21-JUL-08:61 | 15048.36 | 04-JUL-09:02 | 12233.81 | 29-JUL-08:62 | 5070.50 | 21-JUL-08:13 | 0.00 | 01-JUL-00:05 |
August | 0.641252E+10 | 0.157799E+10 | 304.05 | 0.487642E+10 | 0.153610E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 23705.93 | 14-AUG-08:61 | 17563.01 | 06-AUG-09:01 | 11889.26 | 26-AUG-08:62 | 4950.57 | 14-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.232917E+10 | 0.579369E+09 | 184.75 | 0.163800E+10 | 0.691165E+09 | 0.00 | 1.00 | 09-SEP-08:62 | 0.00 | 01-SEP-00:10 | 22792.26 | 17-SEP-09:02 | 13796.15 | 16-SEP-08:62 | 11014.50 | 14-SEP-08:62 | 4820.25 | 16-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 51171629.26 | 13928731.23 | 10.33 | 44942044.79 | 6229584.47 | 0.00 | 0.31 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 2565.68 | 11-OCT-15:00 | 2246.74 | 11-OCT-15:00 | 318.94 | 11-OCT-15:00 | 684.96 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.207667E+11 | 0.509280E+10 | 1092.79 | 0.149279E+11 | 0.583884E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.791099E+10 | 0.190409E+10 | 316.98 | 0.535276E+10 | 0.255823E+10 | 0.00 | 1.00 | 0.00 | 23705.93 | 17563.01 | 12233.81 | 5070.50 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 99366575.48 | 27725073.28 | 12.67 | 84658219.26 | 14708356.21 | 0.00 | 0.41 | 15-MAR-14:10 | 0.00 | 01-MAR-00:05 | 3744.36 | 15-MAR-14:10 | 3421.65 | 15-MAR-14:10 | 598.48 | 14-MAR-13:00 | 1032.59 | 15-MAR-14:10 | 0.00 | 01-MAR-00:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 |
May | 0.248348E+09 | 68082872.05 | 42.50 | 0.219154E+09 | 29193716.78 | 0.00 | 0.48 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 | 4641.43 | 14-MAY-15:00 | 3582.75 | 14-MAY-15:00 | 1100.00 | 14-MAY-14:30 | 1239.11 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.345112E+10 | 0.860868E+09 | 198.92 | 0.251695E+10 | 0.934168E+09 | 0.00 | 1.00 | 12-JUN-08:62 | 0.00 | 01-JUN-00:10 | 24743.79 | 18-JUN-09:02 | 17294.37 | 12-JUN-08:62 | 11499.36 | 18-JUN-09:02 | 5256.80 | 27-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.796793E+10 | 0.192896E+10 | 315.24 | 0.544816E+10 | 0.251977E+10 | 0.00 | 1.00 | 02-JUL-09:02 | 0.00 | 01-JUL-00:05 | 25384.91 | 21-JUL-08:61 | 15810.63 | 04-JUL-09:02 | 12968.50 | 21-JUL-08:05 | 5357.93 | 21-JUL-08:13 | 0.00 | 01-JUL-00:05 |
August | 0.646973E+10 | 0.159792E+10 | 293.51 | 0.498108E+10 | 0.148866E+10 | 0.00 | 1.00 | 05-AUG-08:62 | 0.00 | 01-AUG-00:10 | 25131.24 | 14-AUG-08:61 | 18606.66 | 06-AUG-09:01 | 12629.50 | 14-AUG-08:03 | 5229.36 | 14-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.216824E+10 | 0.541431E+09 | 165.37 | 0.153360E+10 | 0.634636E+09 | 0.00 | 1.00 | 14-SEP-08:62 | 0.00 | 01-SEP-00:10 | 24107.48 | 17-SEP-09:02 | 14523.20 | 16-SEP-08:62 | 11337.17 | 17-SEP-09:02 | 5092.25 | 16-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 45684023.41 | 12508585.04 | 9.67 | 40577295.83 | 5106727.58 | 0.00 | 0.27 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 2394.60 | 11-OCT-15:00 | 2113.70 | 11-OCT-15:00 | 280.90 | 11-OCT-15:00 | 645.02 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.204504E+11 | 0.503750E+10 | 1037.88 | 0.148242E+11 | 0.562624E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.796793E+10 | 0.192896E+10 | 315.24 | 0.544816E+10 | 0.251977E+10 | 0.00 | 1.00 | 0.00 | 25384.91 | 18606.66 | 12968.50 | 5357.93 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.02 | 48.46 | 34.56 | 70.46 | 94.34 | 0.00 | 0.00 | 0.00 |
February | 94.78 | 45.70 | 49.08 | 79.96 | 91.33 | 0.00 | 0.00 | 0.00 |
March | 115.69 | 65.00 | 50.68 | 119.74 | 65.95 | 0.00 | 0.00 | 0.00 |
April | 95.81 | 38.29 | 57.52 | 104.30 | 50.44 | 0.00 | 0.00 | 0.00 |
May | 83.84 | 24.35 | 59.49 | 97.73 | 34.97 | 0.00 | 0.00 | 0.00 |
June | 81.47 | 17.26 | 64.20 | 103.26 | 23.78 | 0.00 | 0.00 | 0.00 |
July | 83.16 | 20.18 | 62.99 | 115.86 | 16.13 | 0.00 | 0.00 | 0.00 |
August | 93.37 | 30.27 | 63.09 | 127.37 | 21.58 | 0.00 | 0.00 | 0.00 |
September | 108.56 | 52.87 | 55.68 | 137.02 | 34.81 | 0.00 | 0.00 | 0.00 |
October | 103.87 | 59.33 | 44.54 | 116.15 | 50.58 | 0.00 | 0.00 | 0.00 |
November | 74.39 | 42.00 | 32.39 | 73.69 | 63.86 | 0.00 | 0.00 | 0.00 |
December | 69.42 | 35.93 | 33.49 | 55.79 | 92.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90.59 | 39.95 | 50.64 | 100.23 | 53.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.42 | 17.26 | 32.39 | 55.79 | 16.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.69 | 65.00 | 64.20 | 137.02 | 94.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.02 | 48.46 | 34.56 | 70.46 | 94.34 | 0.00 | 0.00 | 0.00 |
February | 94.78 | 45.70 | 49.08 | 79.96 | 91.33 | 0.00 | 0.00 | 0.00 |
March | 115.69 | 65.00 | 50.68 | 119.74 | 65.95 | 0.00 | 0.00 | 0.00 |
April | 95.81 | 38.29 | 57.52 | 104.30 | 50.44 | 0.00 | 0.00 | 0.00 |
May | 83.84 | 24.35 | 59.49 | 97.73 | 34.97 | 0.00 | 0.00 | 0.00 |
June | 81.47 | 17.26 | 64.20 | 103.26 | 23.78 | 0.00 | 0.00 | 0.00 |
July | 83.16 | 20.18 | 62.99 | 115.86 | 16.13 | 0.00 | 0.00 | 0.00 |
August | 93.37 | 30.27 | 63.09 | 127.37 | 21.58 | 0.00 | 0.00 | 0.00 |
September | 108.56 | 52.87 | 55.68 | 137.02 | 34.81 | 0.00 | 0.00 | 0.00 |
October | 103.87 | 59.33 | 44.54 | 116.15 | 50.58 | 0.00 | 0.00 | 0.00 |
November | 74.39 | 42.00 | 32.39 | 73.69 | 63.86 | 0.00 | 0.00 | 0.00 |
December | 69.42 | 35.93 | 33.49 | 55.79 | 92.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90.59 | 39.95 | 50.64 | 100.23 | 53.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.42 | 17.26 | 32.39 | 55.79 | 16.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.69 | 65.00 | 64.20 | 137.02 | 94.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.02 | 48.46 | 34.56 | 70.46 | 94.34 | 0.00 | 0.00 | 0.00 |
February | 94.78 | 45.70 | 49.08 | 79.96 | 91.33 | 0.00 | 0.00 | 0.00 |
March | 115.69 | 65.00 | 50.68 | 119.74 | 65.95 | 0.00 | 0.00 | 0.00 |
April | 95.81 | 38.29 | 57.52 | 104.30 | 50.44 | 0.00 | 0.00 | 0.00 |
May | 83.84 | 24.35 | 59.49 | 97.73 | 34.97 | 0.00 | 0.00 | 0.00 |
June | 81.47 | 17.26 | 64.20 | 103.26 | 23.78 | 0.00 | 0.00 | 0.00 |
July | 83.16 | 20.18 | 62.99 | 115.86 | 16.13 | 0.00 | 0.00 | 0.00 |
August | 93.37 | 30.27 | 63.09 | 127.37 | 21.58 | 0.00 | 0.00 | 0.00 |
September | 108.56 | 52.87 | 55.68 | 137.02 | 34.81 | 0.00 | 0.00 | 0.00 |
October | 103.87 | 59.33 | 44.54 | 116.15 | 50.58 | 0.00 | 0.00 | 0.00 |
November | 74.39 | 42.00 | 32.39 | 73.69 | 63.86 | 0.00 | 0.00 | 0.00 |
December | 69.42 | 35.93 | 33.49 | 55.79 | 92.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90.59 | 39.95 | 50.64 | 100.23 | 53.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.42 | 17.26 | 32.39 | 55.79 | 16.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.69 | 65.00 | 64.20 | 137.02 | 94.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.02 | 48.46 | 34.56 | 70.46 | 94.34 | 0.00 | 0.00 | 0.00 |
February | 94.78 | 45.70 | 49.08 | 79.96 | 91.33 | 0.00 | 0.00 | 0.00 |
March | 115.69 | 65.00 | 50.68 | 119.74 | 65.95 | 0.00 | 0.00 | 0.00 |
April | 95.81 | 38.29 | 57.52 | 104.30 | 50.44 | 0.00 | 0.00 | 0.00 |
May | 83.84 | 24.35 | 59.49 | 97.73 | 34.97 | 0.00 | 0.00 | 0.00 |
June | 81.47 | 17.26 | 64.20 | 103.26 | 23.78 | 0.00 | 0.00 | 0.00 |
July | 83.16 | 20.18 | 62.99 | 115.86 | 16.13 | 0.00 | 0.00 | 0.00 |
August | 93.37 | 30.27 | 63.09 | 127.37 | 21.58 | 0.00 | 0.00 | 0.00 |
September | 108.56 | 52.87 | 55.68 | 137.02 | 34.81 | 0.00 | 0.00 | 0.00 |
October | 103.87 | 59.33 | 44.54 | 116.15 | 50.58 | 0.00 | 0.00 | 0.00 |
November | 74.39 | 42.00 | 32.39 | 73.69 | 63.86 | 0.00 | 0.00 | 0.00 |
December | 69.42 | 35.93 | 33.49 | 55.79 | 92.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90.59 | 39.95 | 50.64 | 100.23 | 53.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.42 | 17.26 | 32.39 | 55.79 | 16.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.69 | 65.00 | 64.20 | 137.02 | 94.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 99.80 | 58.25 | 41.54 | 85.28 | 111.70 | 0.00 | 0.00 | 0.00 |
February | 113.94 | 54.94 | 59.00 | 96.97 | 108.02 | 0.00 | 0.00 | 0.00 |
March | 139.08 | 78.15 | 60.93 | 144.61 | 78.26 | 0.00 | 0.00 | 0.00 |
April | 115.18 | 46.02 | 69.15 | 125.84 | 59.88 | 0.00 | 0.00 | 0.00 |
May | 100.79 | 29.27 | 71.52 | 117.79 | 41.61 | 0.00 | 0.00 | 0.00 |
June | 97.94 | 20.75 | 77.18 | 124.28 | 28.37 | 0.00 | 0.00 | 0.00 |
July | 99.98 | 24.26 | 75.72 | 139.27 | 19.30 | 0.00 | 0.00 | 0.00 |
August | 112.24 | 36.39 | 75.85 | 153.13 | 25.78 | 0.00 | 0.00 | 0.00 |
September | 130.50 | 63.56 | 66.94 | 164.86 | 41.51 | 0.00 | 0.00 | 0.00 |
October | 124.87 | 71.33 | 53.54 | 140.02 | 60.16 | 0.00 | 0.00 | 0.00 |
November | 89.43 | 50.49 | 38.94 | 88.98 | 75.74 | 0.00 | 0.00 | 0.00 |
December | 83.45 | 43.19 | 40.26 | 67.62 | 109.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 108.90 | 48.03 | 60.87 | 120.86 | 63.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 83.45 | 20.75 | 38.94 | 67.62 | 19.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.08 | 78.15 | 77.18 | 164.86 | 111.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 99.80 | 58.25 | 41.54 | 85.28 | 111.70 | 0.00 | 0.00 | 0.00 |
February | 113.94 | 54.94 | 59.00 | 96.97 | 108.02 | 0.00 | 0.00 | 0.00 |
March | 139.08 | 78.15 | 60.93 | 144.61 | 78.26 | 0.00 | 0.00 | 0.00 |
April | 115.18 | 46.02 | 69.15 | 125.84 | 59.88 | 0.00 | 0.00 | 0.00 |
May | 100.79 | 29.27 | 71.52 | 117.79 | 41.61 | 0.00 | 0.00 | 0.00 |
June | 97.94 | 20.75 | 77.18 | 124.28 | 28.37 | 0.00 | 0.00 | 0.00 |
July | 99.98 | 24.26 | 75.72 | 139.27 | 19.30 | 0.00 | 0.00 | 0.00 |
August | 112.24 | 36.39 | 75.85 | 153.13 | 25.78 | 0.00 | 0.00 | 0.00 |
September | 130.50 | 63.56 | 66.94 | 164.86 | 41.51 | 0.00 | 0.00 | 0.00 |
October | 124.87 | 71.33 | 53.54 | 140.02 | 60.16 | 0.00 | 0.00 | 0.00 |
November | 89.43 | 50.49 | 38.94 | 88.98 | 75.74 | 0.00 | 0.00 | 0.00 |
December | 83.45 | 43.19 | 40.26 | 67.62 | 109.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 108.90 | 48.03 | 60.87 | 120.86 | 63.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 83.45 | 20.75 | 38.94 | 67.62 | 19.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.08 | 78.15 | 77.18 | 164.86 | 111.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.02 | 48.46 | 34.56 | 69.31 | 98.72 | 0.00 | 0.00 | 0.00 |
February | 94.78 | 45.70 | 49.08 | 78.46 | 95.68 | 0.00 | 0.00 | 0.00 |
March | 115.69 | 65.00 | 50.68 | 118.01 | 70.01 | 0.00 | 0.00 | 0.00 |
April | 95.81 | 38.29 | 57.52 | 102.47 | 54.62 | 0.00 | 0.00 | 0.00 |
May | 83.84 | 24.35 | 59.49 | 95.88 | 37.79 | 0.00 | 0.00 | 0.00 |
June | 81.47 | 17.26 | 64.20 | 102.51 | 24.49 | 0.00 | 0.00 | 0.00 |
July | 83.16 | 20.18 | 62.99 | 115.53 | 16.40 | 0.00 | 0.00 | 0.00 |
August | 93.37 | 30.27 | 63.09 | 127.05 | 21.88 | 0.00 | 0.00 | 0.00 |
September | 108.56 | 52.87 | 55.68 | 136.35 | 35.77 | 0.00 | 0.00 | 0.00 |
October | 103.87 | 59.33 | 44.54 | 114.79 | 53.88 | 0.00 | 0.00 | 0.00 |
November | 74.39 | 42.00 | 32.39 | 72.57 | 67.95 | 0.00 | 0.00 | 0.00 |
December | 69.42 | 35.93 | 33.49 | 54.79 | 97.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90.59 | 39.95 | 50.64 | 99.10 | 55.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.42 | 17.26 | 32.39 | 54.79 | 16.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.69 | 65.00 | 64.20 | 136.35 | 98.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.02 | 48.46 | 34.56 | 69.31 | 98.72 | 0.00 | 0.00 | 0.00 |
February | 94.78 | 45.70 | 49.08 | 78.46 | 95.68 | 0.00 | 0.00 | 0.00 |
March | 115.69 | 65.00 | 50.68 | 118.01 | 70.01 | 0.00 | 0.00 | 0.00 |
April | 95.81 | 38.29 | 57.52 | 102.47 | 54.62 | 0.00 | 0.00 | 0.00 |
May | 83.84 | 24.35 | 59.49 | 95.88 | 37.79 | 0.00 | 0.00 | 0.00 |
June | 81.47 | 17.26 | 64.20 | 102.51 | 24.49 | 0.00 | 0.00 | 0.00 |
July | 83.16 | 20.18 | 62.99 | 115.53 | 16.40 | 0.00 | 0.00 | 0.00 |
August | 93.37 | 30.27 | 63.09 | 127.05 | 21.88 | 0.00 | 0.00 | 0.00 |
September | 108.56 | 52.87 | 55.68 | 136.35 | 35.77 | 0.00 | 0.00 | 0.00 |
October | 103.87 | 59.33 | 44.54 | 114.79 | 53.88 | 0.00 | 0.00 | 0.00 |
November | 74.39 | 42.00 | 32.39 | 72.57 | 67.95 | 0.00 | 0.00 | 0.00 |
December | 69.42 | 35.93 | 33.49 | 54.79 | 97.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90.59 | 39.95 | 50.64 | 99.10 | 55.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.42 | 17.26 | 32.39 | 54.79 | 16.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.69 | 65.00 | 64.20 | 136.35 | 98.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 99.80 | 58.25 | 41.54 | 83.93 | 116.84 | 0.00 | 0.00 | 0.00 |
February | 113.94 | 54.94 | 59.00 | 95.21 | 113.11 | 0.00 | 0.00 | 0.00 |
March | 139.08 | 78.15 | 60.93 | 142.57 | 83.02 | 0.00 | 0.00 | 0.00 |
April | 115.18 | 46.02 | 69.15 | 123.69 | 64.76 | 0.00 | 0.00 | 0.00 |
May | 100.79 | 29.27 | 71.52 | 115.61 | 44.93 | 0.00 | 0.00 | 0.00 |
June | 97.94 | 20.75 | 77.18 | 123.41 | 29.21 | 0.00 | 0.00 | 0.00 |
July | 99.98 | 24.26 | 75.72 | 138.89 | 19.61 | 0.00 | 0.00 | 0.00 |
August | 112.24 | 36.39 | 75.85 | 152.77 | 26.13 | 0.00 | 0.00 | 0.00 |
September | 130.50 | 63.56 | 66.94 | 164.09 | 42.64 | 0.00 | 0.00 | 0.00 |
October | 124.87 | 71.33 | 53.54 | 138.43 | 64.01 | 0.00 | 0.00 | 0.00 |
November | 89.43 | 50.49 | 38.94 | 87.67 | 80.53 | 0.00 | 0.00 | 0.00 |
December | 83.45 | 43.19 | 40.26 | 66.43 | 114.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 108.90 | 48.03 | 60.87 | 119.53 | 66.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 83.45 | 20.75 | 38.94 | 66.43 | 19.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.08 | 78.15 | 77.18 | 164.09 | 116.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.02 | 48.46 | 34.56 | 69.37 | 96.19 | 0.00 | 0.00 | 0.00 |
February | 94.78 | 45.70 | 49.08 | 78.53 | 93.18 | 0.00 | 0.00 | 0.00 |
March | 115.69 | 65.00 | 50.68 | 118.16 | 68.08 | 0.00 | 0.00 | 0.00 |
April | 95.81 | 38.29 | 57.52 | 102.84 | 52.73 | 0.00 | 0.00 | 0.00 |
May | 83.84 | 24.35 | 59.49 | 96.30 | 37.10 | 0.00 | 0.00 | 0.00 |
June | 81.47 | 17.26 | 64.20 | 102.33 | 25.49 | 0.00 | 0.00 | 0.00 |
July | 83.16 | 20.18 | 62.99 | 115.03 | 17.90 | 0.00 | 0.00 | 0.00 |
August | 93.37 | 30.27 | 63.09 | 126.77 | 23.39 | 0.00 | 0.00 | 0.00 |
September | 108.56 | 52.87 | 55.68 | 136.36 | 36.60 | 0.00 | 0.00 | 0.00 |
October | 103.87 | 59.33 | 44.54 | 115.24 | 52.33 | 0.00 | 0.00 | 0.00 |
November | 74.39 | 42.00 | 32.39 | 72.89 | 65.81 | 0.00 | 0.00 | 0.00 |
December | 69.42 | 35.93 | 33.49 | 54.90 | 94.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90.59 | 39.95 | 50.64 | 99.18 | 55.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.42 | 17.26 | 32.39 | 54.90 | 17.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.69 | 65.00 | 64.20 | 136.36 | 96.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.02 | 48.46 | 34.56 | 69.37 | 96.19 | 0.00 | 0.00 | 0.00 |
February | 94.78 | 45.70 | 49.08 | 78.53 | 93.18 | 0.00 | 0.00 | 0.00 |
March | 115.69 | 65.00 | 50.68 | 118.16 | 68.08 | 0.00 | 0.00 | 0.00 |
April | 95.81 | 38.29 | 57.52 | 102.84 | 52.73 | 0.00 | 0.00 | 0.00 |
May | 83.84 | 24.35 | 59.49 | 96.30 | 37.10 | 0.00 | 0.00 | 0.00 |
June | 81.47 | 17.26 | 64.20 | 102.33 | 25.49 | 0.00 | 0.00 | 0.00 |
July | 83.16 | 20.18 | 62.99 | 115.03 | 17.90 | 0.00 | 0.00 | 0.00 |
August | 93.37 | 30.27 | 63.09 | 126.77 | 23.39 | 0.00 | 0.00 | 0.00 |
September | 108.56 | 52.87 | 55.68 | 136.36 | 36.60 | 0.00 | 0.00 | 0.00 |
October | 103.87 | 59.33 | 44.54 | 115.24 | 52.33 | 0.00 | 0.00 | 0.00 |
November | 74.39 | 42.00 | 32.39 | 72.89 | 65.81 | 0.00 | 0.00 | 0.00 |
December | 69.42 | 35.93 | 33.49 | 54.90 | 94.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90.59 | 39.95 | 50.64 | 99.18 | 55.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.42 | 17.26 | 32.39 | 54.90 | 17.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.69 | 65.00 | 64.20 | 136.36 | 96.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 99.25 | 57.94 | 41.32 | 83.54 | 113.24 | 0.00 | 0.00 | 0.00 |
February | 113.32 | 54.64 | 58.68 | 94.77 | 109.57 | 0.00 | 0.00 | 0.00 |
March | 138.32 | 77.72 | 60.60 | 141.98 | 80.32 | 0.00 | 0.00 | 0.00 |
April | 114.55 | 45.77 | 68.77 | 123.45 | 62.21 | 0.00 | 0.00 | 0.00 |
May | 100.24 | 29.11 | 71.13 | 115.47 | 43.87 | 0.00 | 0.00 | 0.00 |
June | 97.40 | 20.64 | 76.76 | 122.52 | 30.22 | 0.00 | 0.00 | 0.00 |
July | 99.43 | 24.12 | 75.30 | 137.55 | 21.25 | 0.00 | 0.00 | 0.00 |
August | 111.63 | 36.19 | 75.43 | 151.62 | 27.74 | 0.00 | 0.00 | 0.00 |
September | 129.79 | 63.22 | 66.57 | 163.21 | 43.37 | 0.00 | 0.00 | 0.00 |
October | 124.19 | 70.94 | 53.25 | 138.21 | 61.85 | 0.00 | 0.00 | 0.00 |
November | 88.94 | 50.21 | 38.73 | 87.57 | 77.59 | 0.00 | 0.00 | 0.00 |
December | 82.99 | 42.95 | 40.04 | 66.20 | 111.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 108.30 | 47.76 | 60.54 | 118.98 | 64.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.99 | 20.64 | 38.73 | 66.20 | 21.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.32 | 77.72 | 76.76 | 163.21 | 113.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.02 | 48.46 | 34.56 | 69.49 | 95.21 | 0.00 | 0.00 | 0.00 |
February | 94.78 | 45.70 | 49.08 | 78.67 | 92.26 | 0.00 | 0.00 | 0.00 |
March | 115.69 | 65.00 | 50.68 | 118.36 | 67.28 | 0.00 | 0.00 | 0.00 |
April | 95.81 | 38.29 | 57.52 | 103.12 | 51.86 | 0.00 | 0.00 | 0.00 |
May | 83.84 | 24.35 | 59.49 | 96.63 | 36.42 | 0.00 | 0.00 | 0.00 |
June | 81.47 | 17.26 | 64.20 | 102.37 | 25.41 | 0.00 | 0.00 | 0.00 |
July | 83.16 | 20.18 | 62.99 | 115.00 | 17.97 | 0.00 | 0.00 | 0.00 |
August | 93.37 | 30.27 | 63.09 | 126.76 | 23.44 | 0.00 | 0.00 | 0.00 |
September | 108.56 | 52.87 | 55.68 | 136.42 | 36.43 | 0.00 | 0.00 | 0.00 |
October | 103.87 | 59.33 | 44.54 | 115.52 | 51.53 | 0.00 | 0.00 | 0.00 |
November | 74.39 | 42.00 | 32.39 | 73.09 | 64.89 | 0.00 | 0.00 | 0.00 |
December | 69.42 | 35.93 | 33.49 | 55.01 | 93.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90.59 | 39.95 | 50.64 | 99.32 | 54.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.42 | 17.26 | 32.39 | 55.01 | 17.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.69 | 65.00 | 64.20 | 136.42 | 95.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.02 | 48.46 | 34.56 | 69.49 | 95.21 | 0.00 | 0.00 | 0.00 |
February | 94.78 | 45.70 | 49.08 | 78.67 | 92.26 | 0.00 | 0.00 | 0.00 |
March | 115.69 | 65.00 | 50.68 | 118.36 | 67.28 | 0.00 | 0.00 | 0.00 |
April | 95.81 | 38.29 | 57.52 | 103.12 | 51.86 | 0.00 | 0.00 | 0.00 |
May | 83.84 | 24.35 | 59.49 | 96.63 | 36.42 | 0.00 | 0.00 | 0.00 |
June | 81.47 | 17.26 | 64.20 | 102.37 | 25.41 | 0.00 | 0.00 | 0.00 |
July | 83.16 | 20.18 | 62.99 | 115.00 | 17.97 | 0.00 | 0.00 | 0.00 |
August | 93.37 | 30.27 | 63.09 | 126.76 | 23.44 | 0.00 | 0.00 | 0.00 |
September | 108.56 | 52.87 | 55.68 | 136.42 | 36.43 | 0.00 | 0.00 | 0.00 |
October | 103.87 | 59.33 | 44.54 | 115.52 | 51.53 | 0.00 | 0.00 | 0.00 |
November | 74.39 | 42.00 | 32.39 | 73.09 | 64.89 | 0.00 | 0.00 | 0.00 |
December | 69.42 | 35.93 | 33.49 | 55.01 | 93.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90.59 | 39.95 | 50.64 | 99.32 | 54.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.42 | 17.26 | 32.39 | 55.01 | 17.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.69 | 65.00 | 64.20 | 136.42 | 95.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 99.25 | 57.94 | 41.32 | 83.69 | 112.07 | 0.00 | 0.00 | 0.00 |
February | 113.32 | 54.64 | 58.68 | 94.95 | 108.48 | 0.00 | 0.00 | 0.00 |
March | 138.32 | 77.72 | 60.60 | 142.22 | 79.36 | 0.00 | 0.00 | 0.00 |
April | 114.55 | 45.77 | 68.77 | 123.78 | 61.18 | 0.00 | 0.00 | 0.00 |
May | 100.24 | 29.11 | 71.13 | 115.87 | 43.06 | 0.00 | 0.00 | 0.00 |
June | 97.40 | 20.64 | 76.76 | 122.57 | 30.12 | 0.00 | 0.00 | 0.00 |
July | 99.43 | 24.12 | 75.30 | 137.52 | 21.33 | 0.00 | 0.00 | 0.00 |
August | 111.63 | 36.19 | 75.43 | 151.60 | 27.80 | 0.00 | 0.00 | 0.00 |
September | 129.79 | 63.22 | 66.57 | 163.28 | 43.17 | 0.00 | 0.00 | 0.00 |
October | 124.19 | 70.94 | 53.25 | 138.53 | 60.90 | 0.00 | 0.00 | 0.00 |
November | 88.94 | 50.21 | 38.73 | 87.81 | 76.50 | 0.00 | 0.00 | 0.00 |
December | 82.99 | 42.95 | 40.04 | 66.34 | 110.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 108.30 | 47.76 | 60.54 | 119.15 | 64.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.99 | 20.64 | 38.73 | 66.34 | 21.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.32 | 77.72 | 76.76 | 163.28 | 112.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.02 | 48.46 | 34.56 | 69.64 | 94.48 | 0.00 | 0.00 | 0.00 |
February | 94.78 | 45.70 | 49.08 | 78.85 | 91.59 | 0.00 | 0.00 | 0.00 |
March | 115.69 | 65.00 | 50.68 | 118.60 | 66.65 | 0.00 | 0.00 | 0.00 |
April | 95.81 | 38.29 | 57.52 | 103.41 | 51.20 | 0.00 | 0.00 | 0.00 |
May | 83.84 | 24.35 | 59.49 | 97.02 | 35.77 | 0.00 | 0.00 | 0.00 |
June | 81.47 | 17.26 | 64.20 | 102.51 | 25.16 | 0.00 | 0.00 | 0.00 |
July | 83.16 | 20.18 | 62.99 | 115.10 | 17.77 | 0.00 | 0.00 | 0.00 |
August | 93.37 | 30.27 | 63.09 | 126.84 | 23.22 | 0.00 | 0.00 | 0.00 |
September | 108.56 | 52.87 | 55.68 | 136.54 | 36.13 | 0.00 | 0.00 | 0.00 |
October | 103.87 | 59.33 | 44.54 | 115.78 | 50.93 | 0.00 | 0.00 | 0.00 |
November | 74.39 | 42.00 | 32.39 | 73.28 | 64.23 | 0.00 | 0.00 | 0.00 |
December | 69.42 | 35.93 | 33.49 | 55.14 | 92.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90.59 | 39.95 | 50.64 | 99.51 | 53.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.42 | 17.26 | 32.39 | 55.14 | 17.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.69 | 65.00 | 64.20 | 136.54 | 94.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.02 | 48.46 | 34.56 | 69.64 | 94.48 | 0.00 | 0.00 | 0.00 |
February | 94.78 | 45.70 | 49.08 | 78.85 | 91.59 | 0.00 | 0.00 | 0.00 |
March | 115.69 | 65.00 | 50.68 | 118.60 | 66.65 | 0.00 | 0.00 | 0.00 |
April | 95.81 | 38.29 | 57.52 | 103.41 | 51.20 | 0.00 | 0.00 | 0.00 |
May | 83.84 | 24.35 | 59.49 | 97.02 | 35.77 | 0.00 | 0.00 | 0.00 |
June | 81.47 | 17.26 | 64.20 | 102.51 | 25.16 | 0.00 | 0.00 | 0.00 |
July | 83.16 | 20.18 | 62.99 | 115.10 | 17.77 | 0.00 | 0.00 | 0.00 |
August | 93.37 | 30.27 | 63.09 | 126.84 | 23.22 | 0.00 | 0.00 | 0.00 |
September | 108.56 | 52.87 | 55.68 | 136.54 | 36.13 | 0.00 | 0.00 | 0.00 |
October | 103.87 | 59.33 | 44.54 | 115.78 | 50.93 | 0.00 | 0.00 | 0.00 |
November | 74.39 | 42.00 | 32.39 | 73.28 | 64.23 | 0.00 | 0.00 | 0.00 |
December | 69.42 | 35.93 | 33.49 | 55.14 | 92.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90.59 | 39.95 | 50.64 | 99.51 | 53.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.42 | 17.26 | 32.39 | 55.14 | 17.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.69 | 65.00 | 64.20 | 136.54 | 94.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 99.25 | 57.94 | 41.32 | 83.87 | 111.22 | 0.00 | 0.00 | 0.00 |
February | 113.32 | 54.64 | 58.68 | 95.16 | 107.69 | 0.00 | 0.00 | 0.00 |
March | 138.32 | 77.72 | 60.60 | 142.50 | 78.63 | 0.00 | 0.00 | 0.00 |
April | 114.55 | 45.77 | 68.77 | 124.13 | 60.41 | 0.00 | 0.00 | 0.00 |
May | 100.24 | 29.11 | 71.13 | 116.33 | 42.31 | 0.00 | 0.00 | 0.00 |
June | 97.40 | 20.64 | 76.76 | 122.75 | 29.83 | 0.00 | 0.00 | 0.00 |
July | 99.43 | 24.12 | 75.30 | 137.63 | 21.10 | 0.00 | 0.00 | 0.00 |
August | 111.63 | 36.19 | 75.43 | 151.70 | 27.55 | 0.00 | 0.00 | 0.00 |
September | 129.79 | 63.22 | 66.57 | 163.42 | 42.82 | 0.00 | 0.00 | 0.00 |
October | 124.19 | 70.94 | 53.25 | 138.85 | 60.20 | 0.00 | 0.00 | 0.00 |
November | 88.94 | 50.21 | 38.73 | 88.04 | 75.73 | 0.00 | 0.00 | 0.00 |
December | 82.99 | 42.95 | 40.04 | 66.50 | 109.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 108.30 | 47.76 | 60.54 | 119.38 | 63.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.99 | 20.64 | 38.73 | 66.50 | 21.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.32 | 77.72 | 76.76 | 163.42 | 111.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.02 | 48.46 | 34.56 | 70.52 | 92.04 | 0.00 | 0.00 | 0.00 |
February | 94.78 | 45.70 | 49.08 | 80.02 | 89.26 | 0.00 | 0.00 | 0.00 |
March | 115.69 | 65.00 | 50.68 | 119.73 | 65.00 | 0.00 | 0.00 | 0.00 |
April | 95.81 | 38.29 | 57.52 | 104.31 | 49.82 | 0.00 | 0.00 | 0.00 |
May | 83.84 | 24.35 | 59.49 | 97.76 | 34.65 | 0.00 | 0.00 | 0.00 |
June | 81.47 | 17.26 | 64.20 | 102.79 | 24.53 | 0.00 | 0.00 | 0.00 |
July | 83.16 | 20.18 | 62.99 | 115.18 | 17.21 | 0.00 | 0.00 | 0.00 |
August | 93.37 | 30.27 | 63.09 | 126.93 | 22.59 | 0.00 | 0.00 | 0.00 |
September | 108.56 | 52.87 | 55.68 | 136.80 | 35.47 | 0.00 | 0.00 | 0.00 |
October | 103.87 | 59.33 | 44.54 | 116.45 | 49.86 | 0.00 | 0.00 | 0.00 |
November | 74.39 | 42.00 | 32.39 | 73.96 | 62.64 | 0.00 | 0.00 | 0.00 |
December | 69.42 | 35.93 | 33.49 | 55.90 | 90.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90.59 | 39.95 | 50.64 | 100.14 | 52.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.42 | 17.26 | 32.39 | 55.90 | 17.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.69 | 65.00 | 64.20 | 136.80 | 92.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.02 | 48.46 | 34.56 | 70.52 | 92.04 | 0.00 | 0.00 | 0.00 |
February | 94.78 | 45.70 | 49.08 | 80.02 | 89.26 | 0.00 | 0.00 | 0.00 |
March | 115.69 | 65.00 | 50.68 | 119.73 | 65.00 | 0.00 | 0.00 | 0.00 |
April | 95.81 | 38.29 | 57.52 | 104.31 | 49.82 | 0.00 | 0.00 | 0.00 |
May | 83.84 | 24.35 | 59.49 | 97.76 | 34.65 | 0.00 | 0.00 | 0.00 |
June | 81.47 | 17.26 | 64.20 | 102.79 | 24.53 | 0.00 | 0.00 | 0.00 |
July | 83.16 | 20.18 | 62.99 | 115.18 | 17.21 | 0.00 | 0.00 | 0.00 |
August | 93.37 | 30.27 | 63.09 | 126.93 | 22.59 | 0.00 | 0.00 | 0.00 |
September | 108.56 | 52.87 | 55.68 | 136.80 | 35.47 | 0.00 | 0.00 | 0.00 |
October | 103.87 | 59.33 | 44.54 | 116.45 | 49.86 | 0.00 | 0.00 | 0.00 |
November | 74.39 | 42.00 | 32.39 | 73.96 | 62.64 | 0.00 | 0.00 | 0.00 |
December | 69.42 | 35.93 | 33.49 | 55.90 | 90.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90.59 | 39.95 | 50.64 | 100.14 | 52.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.42 | 17.26 | 32.39 | 55.90 | 17.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.69 | 65.00 | 64.20 | 136.80 | 92.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.02 | 48.46 | 34.56 | 70.52 | 92.04 | 0.00 | 0.00 | 0.00 |
February | 94.78 | 45.70 | 49.08 | 80.02 | 89.26 | 0.00 | 0.00 | 0.00 |
March | 115.69 | 65.00 | 50.68 | 119.73 | 65.00 | 0.00 | 0.00 | 0.00 |
April | 95.81 | 38.29 | 57.52 | 104.31 | 49.82 | 0.00 | 0.00 | 0.00 |
May | 83.84 | 24.35 | 59.49 | 97.76 | 34.65 | 0.00 | 0.00 | 0.00 |
June | 81.47 | 17.26 | 64.20 | 102.79 | 24.53 | 0.00 | 0.00 | 0.00 |
July | 83.16 | 20.18 | 62.99 | 115.18 | 17.21 | 0.00 | 0.00 | 0.00 |
August | 93.37 | 30.27 | 63.09 | 126.93 | 22.59 | 0.00 | 0.00 | 0.00 |
September | 108.56 | 52.87 | 55.68 | 136.80 | 35.47 | 0.00 | 0.00 | 0.00 |
October | 103.87 | 59.33 | 44.54 | 116.45 | 49.86 | 0.00 | 0.00 | 0.00 |
November | 74.39 | 42.00 | 32.39 | 73.96 | 62.64 | 0.00 | 0.00 | 0.00 |
December | 69.42 | 35.93 | 33.49 | 55.90 | 90.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90.59 | 39.95 | 50.64 | 100.14 | 52.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.42 | 17.26 | 32.39 | 55.90 | 17.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.69 | 65.00 | 64.20 | 136.80 | 92.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.02 | 48.46 | 34.56 | 70.52 | 92.04 | 0.00 | 0.00 | 0.00 |
February | 94.78 | 45.70 | 49.08 | 80.02 | 89.26 | 0.00 | 0.00 | 0.00 |
March | 115.69 | 65.00 | 50.68 | 119.73 | 65.00 | 0.00 | 0.00 | 0.00 |
April | 95.81 | 38.29 | 57.52 | 104.31 | 49.82 | 0.00 | 0.00 | 0.00 |
May | 83.84 | 24.35 | 59.49 | 97.76 | 34.65 | 0.00 | 0.00 | 0.00 |
June | 81.47 | 17.26 | 64.20 | 102.79 | 24.53 | 0.00 | 0.00 | 0.00 |
July | 83.16 | 20.18 | 62.99 | 115.18 | 17.21 | 0.00 | 0.00 | 0.00 |
August | 93.37 | 30.27 | 63.09 | 126.93 | 22.59 | 0.00 | 0.00 | 0.00 |
September | 108.56 | 52.87 | 55.68 | 136.80 | 35.47 | 0.00 | 0.00 | 0.00 |
October | 103.87 | 59.33 | 44.54 | 116.45 | 49.86 | 0.00 | 0.00 | 0.00 |
November | 74.39 | 42.00 | 32.39 | 73.96 | 62.64 | 0.00 | 0.00 | 0.00 |
December | 69.42 | 35.93 | 33.49 | 55.90 | 90.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90.59 | 39.95 | 50.64 | 100.14 | 52.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.42 | 17.26 | 32.39 | 55.90 | 17.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.69 | 65.00 | 64.20 | 136.80 | 92.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 99.25 | 57.94 | 41.32 | 84.89 | 108.41 | 0.00 | 0.00 | 0.00 |
February | 113.32 | 54.64 | 58.68 | 96.51 | 105.02 | 0.00 | 0.00 | 0.00 |
March | 138.32 | 77.72 | 60.60 | 143.80 | 76.72 | 0.00 | 0.00 | 0.00 |
April | 114.55 | 45.77 | 68.77 | 125.17 | 58.82 | 0.00 | 0.00 | 0.00 |
May | 100.24 | 29.11 | 71.13 | 117.18 | 41.00 | 0.00 | 0.00 | 0.00 |
June | 97.40 | 20.64 | 76.76 | 123.06 | 29.09 | 0.00 | 0.00 | 0.00 |
July | 99.43 | 24.12 | 75.30 | 137.72 | 20.44 | 0.00 | 0.00 | 0.00 |
August | 111.63 | 36.19 | 75.43 | 151.79 | 26.81 | 0.00 | 0.00 | 0.00 |
September | 129.79 | 63.22 | 66.57 | 163.71 | 42.05 | 0.00 | 0.00 | 0.00 |
October | 124.19 | 70.94 | 53.25 | 139.61 | 58.96 | 0.00 | 0.00 | 0.00 |
November | 88.94 | 50.21 | 38.73 | 88.82 | 73.90 | 0.00 | 0.00 | 0.00 |
December | 82.99 | 42.95 | 40.04 | 67.38 | 106.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 108.30 | 47.76 | 60.54 | 120.11 | 62.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.99 | 20.64 | 38.73 | 67.38 | 20.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.32 | 77.72 | 76.76 | 163.71 | 108.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 99.25 | 57.94 | 41.32 | 84.89 | 108.41 | 0.00 | 0.00 | 0.00 |
February | 113.32 | 54.64 | 58.68 | 96.51 | 105.02 | 0.00 | 0.00 | 0.00 |
March | 138.32 | 77.72 | 60.60 | 143.80 | 76.72 | 0.00 | 0.00 | 0.00 |
April | 114.55 | 45.77 | 68.77 | 125.17 | 58.82 | 0.00 | 0.00 | 0.00 |
May | 100.24 | 29.11 | 71.13 | 117.18 | 41.00 | 0.00 | 0.00 | 0.00 |
June | 97.40 | 20.64 | 76.76 | 123.06 | 29.09 | 0.00 | 0.00 | 0.00 |
July | 99.43 | 24.12 | 75.30 | 137.72 | 20.44 | 0.00 | 0.00 | 0.00 |
August | 111.63 | 36.19 | 75.43 | 151.79 | 26.81 | 0.00 | 0.00 | 0.00 |
September | 129.79 | 63.22 | 66.57 | 163.71 | 42.05 | 0.00 | 0.00 | 0.00 |
October | 124.19 | 70.94 | 53.25 | 139.61 | 58.96 | 0.00 | 0.00 | 0.00 |
November | 88.94 | 50.21 | 38.73 | 88.82 | 73.90 | 0.00 | 0.00 | 0.00 |
December | 82.99 | 42.95 | 40.04 | 67.38 | 106.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 108.30 | 47.76 | 60.54 | 120.11 | 62.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.99 | 20.64 | 38.73 | 67.38 | 20.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.32 | 77.72 | 76.76 | 163.71 | 108.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.02 | 48.46 | 34.56 | 70.13 | 92.83 | 0.00 | 0.00 | 0.00 |
February | 94.78 | 45.70 | 49.08 | 79.48 | 90.06 | 0.00 | 0.00 | 0.00 |
March | 115.69 | 65.00 | 50.68 | 119.28 | 65.31 | 0.00 | 0.00 | 0.00 |
April | 95.81 | 38.29 | 57.52 | 104.03 | 49.93 | 0.00 | 0.00 | 0.00 |
May | 83.84 | 24.35 | 59.49 | 97.64 | 34.55 | 0.00 | 0.00 | 0.00 |
June | 81.47 | 17.26 | 64.20 | 102.71 | 24.39 | 0.00 | 0.00 | 0.00 |
July | 83.16 | 20.18 | 62.99 | 115.17 | 17.01 | 0.00 | 0.00 | 0.00 |
August | 93.37 | 30.27 | 63.09 | 126.87 | 22.39 | 0.00 | 0.00 | 0.00 |
September | 108.56 | 52.87 | 55.68 | 136.63 | 35.36 | 0.00 | 0.00 | 0.00 |
October | 103.87 | 59.33 | 44.54 | 116.20 | 49.90 | 0.00 | 0.00 | 0.00 |
November | 74.39 | 42.00 | 32.39 | 73.71 | 62.93 | 0.00 | 0.00 | 0.00 |
December | 69.42 | 35.93 | 33.49 | 55.55 | 91.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90.59 | 39.95 | 50.64 | 99.90 | 52.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.42 | 17.26 | 32.39 | 55.55 | 17.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.69 | 65.00 | 64.20 | 136.63 | 92.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.02 | 48.46 | 34.56 | 70.13 | 92.83 | 0.00 | 0.00 | 0.00 |
February | 94.78 | 45.70 | 49.08 | 79.48 | 90.06 | 0.00 | 0.00 | 0.00 |
March | 115.69 | 65.00 | 50.68 | 119.28 | 65.31 | 0.00 | 0.00 | 0.00 |
April | 95.81 | 38.29 | 57.52 | 104.03 | 49.93 | 0.00 | 0.00 | 0.00 |
May | 83.84 | 24.35 | 59.49 | 97.64 | 34.55 | 0.00 | 0.00 | 0.00 |
June | 81.47 | 17.26 | 64.20 | 102.71 | 24.39 | 0.00 | 0.00 | 0.00 |
July | 83.16 | 20.18 | 62.99 | 115.17 | 17.01 | 0.00 | 0.00 | 0.00 |
August | 93.37 | 30.27 | 63.09 | 126.87 | 22.39 | 0.00 | 0.00 | 0.00 |
September | 108.56 | 52.87 | 55.68 | 136.63 | 35.36 | 0.00 | 0.00 | 0.00 |
October | 103.87 | 59.33 | 44.54 | 116.20 | 49.90 | 0.00 | 0.00 | 0.00 |
November | 74.39 | 42.00 | 32.39 | 73.71 | 62.93 | 0.00 | 0.00 | 0.00 |
December | 69.42 | 35.93 | 33.49 | 55.55 | 91.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90.59 | 39.95 | 50.64 | 99.90 | 52.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.42 | 17.26 | 32.39 | 55.55 | 17.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.69 | 65.00 | 64.20 | 136.63 | 92.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 99.25 | 57.94 | 41.32 | 84.46 | 109.27 | 0.00 | 0.00 | 0.00 |
February | 113.32 | 54.64 | 58.68 | 95.93 | 105.89 | 0.00 | 0.00 | 0.00 |
March | 138.32 | 77.72 | 60.60 | 143.32 | 77.04 | 0.00 | 0.00 | 0.00 |
April | 114.55 | 45.77 | 68.77 | 124.88 | 58.92 | 0.00 | 0.00 | 0.00 |
May | 100.24 | 29.11 | 71.13 | 117.07 | 40.86 | 0.00 | 0.00 | 0.00 |
June | 97.40 | 20.64 | 76.76 | 122.98 | 28.92 | 0.00 | 0.00 | 0.00 |
July | 99.43 | 24.12 | 75.30 | 137.73 | 20.20 | 0.00 | 0.00 | 0.00 |
August | 111.63 | 36.19 | 75.43 | 151.74 | 26.57 | 0.00 | 0.00 | 0.00 |
September | 129.79 | 63.22 | 66.57 | 163.54 | 41.91 | 0.00 | 0.00 | 0.00 |
October | 124.19 | 70.94 | 53.25 | 139.35 | 58.98 | 0.00 | 0.00 | 0.00 |
November | 88.94 | 50.21 | 38.73 | 88.56 | 74.20 | 0.00 | 0.00 | 0.00 |
December | 82.99 | 42.95 | 40.04 | 66.99 | 107.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 108.30 | 47.76 | 60.54 | 119.85 | 62.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.99 | 20.64 | 38.73 | 66.99 | 20.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.32 | 77.72 | 76.76 | 163.54 | 109.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.02 | 48.46 | 34.56 | 70.17 | 92.62 | 0.00 | 0.00 | 0.00 |
February | 94.78 | 45.70 | 49.08 | 79.53 | 89.88 | 0.00 | 0.00 | 0.00 |
March | 115.69 | 65.00 | 50.68 | 119.39 | 65.03 | 0.00 | 0.00 | 0.00 |
April | 95.81 | 38.29 | 57.52 | 104.20 | 49.58 | 0.00 | 0.00 | 0.00 |
May | 83.84 | 24.35 | 59.49 | 97.95 | 34.11 | 0.00 | 0.00 | 0.00 |
June | 81.47 | 17.26 | 64.20 | 102.85 | 24.22 | 0.00 | 0.00 | 0.00 |
July | 83.16 | 20.18 | 62.99 | 115.26 | 16.91 | 0.00 | 0.00 | 0.00 |
August | 93.37 | 30.27 | 63.09 | 126.94 | 22.28 | 0.00 | 0.00 | 0.00 |
September | 108.56 | 52.87 | 55.68 | 136.73 | 35.18 | 0.00 | 0.00 | 0.00 |
October | 103.87 | 59.33 | 44.54 | 116.36 | 49.57 | 0.00 | 0.00 | 0.00 |
November | 74.39 | 42.00 | 32.39 | 73.81 | 62.63 | 0.00 | 0.00 | 0.00 |
December | 69.42 | 35.93 | 33.49 | 55.59 | 91.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90.59 | 39.95 | 50.64 | 100.02 | 52.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.42 | 17.26 | 32.39 | 55.59 | 16.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.69 | 65.00 | 64.20 | 136.73 | 92.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.02 | 48.46 | 34.56 | 70.17 | 92.62 | 0.00 | 0.00 | 0.00 |
February | 94.78 | 45.70 | 49.08 | 79.53 | 89.88 | 0.00 | 0.00 | 0.00 |
March | 115.69 | 65.00 | 50.68 | 119.39 | 65.03 | 0.00 | 0.00 | 0.00 |
April | 95.81 | 38.29 | 57.52 | 104.20 | 49.58 | 0.00 | 0.00 | 0.00 |
May | 83.84 | 24.35 | 59.49 | 97.95 | 34.11 | 0.00 | 0.00 | 0.00 |
June | 81.47 | 17.26 | 64.20 | 102.85 | 24.22 | 0.00 | 0.00 | 0.00 |
July | 83.16 | 20.18 | 62.99 | 115.26 | 16.91 | 0.00 | 0.00 | 0.00 |
August | 93.37 | 30.27 | 63.09 | 126.94 | 22.28 | 0.00 | 0.00 | 0.00 |
September | 108.56 | 52.87 | 55.68 | 136.73 | 35.18 | 0.00 | 0.00 | 0.00 |
October | 103.87 | 59.33 | 44.54 | 116.36 | 49.57 | 0.00 | 0.00 | 0.00 |
November | 74.39 | 42.00 | 32.39 | 73.81 | 62.63 | 0.00 | 0.00 | 0.00 |
December | 69.42 | 35.93 | 33.49 | 55.59 | 91.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90.59 | 39.95 | 50.64 | 100.02 | 52.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.42 | 17.26 | 32.39 | 55.59 | 16.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.69 | 65.00 | 64.20 | 136.73 | 92.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 99.25 | 57.94 | 41.32 | 84.51 | 109.03 | 0.00 | 0.00 | 0.00 |
February | 113.32 | 54.64 | 58.68 | 95.99 | 105.68 | 0.00 | 0.00 | 0.00 |
March | 138.32 | 77.72 | 60.60 | 143.45 | 76.71 | 0.00 | 0.00 | 0.00 |
April | 114.55 | 45.77 | 68.77 | 125.09 | 58.50 | 0.00 | 0.00 | 0.00 |
May | 100.24 | 29.11 | 71.13 | 117.44 | 40.35 | 0.00 | 0.00 | 0.00 |
June | 97.40 | 20.64 | 76.76 | 123.15 | 28.72 | 0.00 | 0.00 | 0.00 |
July | 99.43 | 24.12 | 75.30 | 137.83 | 20.08 | 0.00 | 0.00 | 0.00 |
August | 111.63 | 36.19 | 75.43 | 151.83 | 26.44 | 0.00 | 0.00 | 0.00 |
September | 129.79 | 63.22 | 66.57 | 163.66 | 41.70 | 0.00 | 0.00 | 0.00 |
October | 124.19 | 70.94 | 53.25 | 139.54 | 58.60 | 0.00 | 0.00 | 0.00 |
November | 88.94 | 50.21 | 38.73 | 88.68 | 73.83 | 0.00 | 0.00 | 0.00 |
December | 82.99 | 42.95 | 40.04 | 67.04 | 107.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 108.30 | 47.76 | 60.54 | 119.99 | 61.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.99 | 20.64 | 38.73 | 67.04 | 20.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.32 | 77.72 | 76.76 | 163.66 | 109.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.02 | 48.46 | 34.56 | 70.37 | 91.44 | 0.00 | 0.00 | 0.00 |
February | 94.78 | 45.70 | 49.08 | 79.77 | 88.82 | 0.00 | 0.00 | 0.00 |
March | 115.69 | 65.00 | 50.68 | 119.78 | 63.81 | 0.00 | 0.00 | 0.00 |
April | 95.81 | 38.29 | 57.52 | 104.73 | 48.33 | 0.00 | 0.00 | 0.00 |
May | 83.84 | 24.35 | 59.49 | 98.76 | 32.88 | 0.00 | 0.00 | 0.00 |
June | 81.47 | 17.26 | 64.20 | 103.24 | 23.70 | 0.00 | 0.00 | 0.00 |
July | 83.16 | 20.18 | 62.99 | 115.43 | 16.64 | 0.00 | 0.00 | 0.00 |
August | 93.37 | 30.27 | 63.09 | 127.10 | 22.00 | 0.00 | 0.00 | 0.00 |
September | 108.56 | 52.87 | 55.68 | 137.00 | 34.62 | 0.00 | 0.00 | 0.00 |
October | 103.87 | 59.33 | 44.54 | 116.79 | 48.59 | 0.00 | 0.00 | 0.00 |
November | 74.39 | 42.00 | 32.39 | 74.13 | 61.50 | 0.00 | 0.00 | 0.00 |
December | 69.42 | 35.93 | 33.49 | 55.77 | 89.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90.59 | 39.95 | 50.64 | 100.36 | 51.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.42 | 17.26 | 32.39 | 55.77 | 16.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.69 | 65.00 | 64.20 | 137.00 | 91.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.02 | 48.46 | 34.56 | 70.37 | 91.44 | 0.00 | 0.00 | 0.00 |
February | 94.78 | 45.70 | 49.08 | 79.77 | 88.82 | 0.00 | 0.00 | 0.00 |
March | 115.69 | 65.00 | 50.68 | 119.78 | 63.81 | 0.00 | 0.00 | 0.00 |
April | 95.81 | 38.29 | 57.52 | 104.73 | 48.33 | 0.00 | 0.00 | 0.00 |
May | 83.84 | 24.35 | 59.49 | 98.76 | 32.88 | 0.00 | 0.00 | 0.00 |
June | 81.47 | 17.26 | 64.20 | 103.24 | 23.70 | 0.00 | 0.00 | 0.00 |
July | 83.16 | 20.18 | 62.99 | 115.43 | 16.64 | 0.00 | 0.00 | 0.00 |
August | 93.37 | 30.27 | 63.09 | 127.10 | 22.00 | 0.00 | 0.00 | 0.00 |
September | 108.56 | 52.87 | 55.68 | 137.00 | 34.62 | 0.00 | 0.00 | 0.00 |
October | 103.87 | 59.33 | 44.54 | 116.79 | 48.59 | 0.00 | 0.00 | 0.00 |
November | 74.39 | 42.00 | 32.39 | 74.13 | 61.50 | 0.00 | 0.00 | 0.00 |
December | 69.42 | 35.93 | 33.49 | 55.77 | 89.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90.59 | 39.95 | 50.64 | 100.36 | 51.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.42 | 17.26 | 32.39 | 55.77 | 16.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.69 | 65.00 | 64.20 | 137.00 | 91.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 99.25 | 57.94 | 41.32 | 84.76 | 107.63 | 0.00 | 0.00 | 0.00 |
February | 113.32 | 54.64 | 58.68 | 96.28 | 104.43 | 0.00 | 0.00 | 0.00 |
March | 138.32 | 77.72 | 60.60 | 143.93 | 75.28 | 0.00 | 0.00 | 0.00 |
April | 114.55 | 45.77 | 68.77 | 125.73 | 57.03 | 0.00 | 0.00 | 0.00 |
May | 100.24 | 29.11 | 71.13 | 118.41 | 38.90 | 0.00 | 0.00 | 0.00 |
June | 97.40 | 20.64 | 76.76 | 123.62 | 28.11 | 0.00 | 0.00 | 0.00 |
July | 99.43 | 24.12 | 75.30 | 138.05 | 19.77 | 0.00 | 0.00 | 0.00 |
August | 111.63 | 36.19 | 75.43 | 152.01 | 26.11 | 0.00 | 0.00 | 0.00 |
September | 129.79 | 63.22 | 66.57 | 163.98 | 41.04 | 0.00 | 0.00 | 0.00 |
October | 124.19 | 70.94 | 53.25 | 140.06 | 57.44 | 0.00 | 0.00 | 0.00 |
November | 88.94 | 50.21 | 38.73 | 89.06 | 72.50 | 0.00 | 0.00 | 0.00 |
December | 82.99 | 42.95 | 40.04 | 67.26 | 105.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 108.30 | 47.76 | 60.54 | 120.40 | 60.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.99 | 20.64 | 38.73 | 67.26 | 19.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.32 | 77.72 | 76.76 | 163.98 | 107.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.02 | 48.46 | 34.56 | 71.26 | 86.31 | 0.00 | 0.00 | 0.00 |
February | 94.78 | 45.70 | 49.08 | 80.84 | 83.97 | 0.00 | 0.00 | 0.00 |
March | 115.69 | 65.00 | 50.68 | 121.15 | 58.88 | 0.00 | 0.00 | 0.00 |
April | 95.81 | 38.29 | 57.52 | 106.16 | 43.75 | 0.00 | 0.00 | 0.00 |
May | 83.84 | 24.35 | 59.49 | 100.60 | 29.20 | 0.00 | 0.00 | 0.00 |
June | 81.47 | 17.26 | 64.20 | 104.19 | 21.74 | 0.00 | 0.00 | 0.00 |
July | 83.16 | 20.18 | 62.99 | 115.72 | 15.61 | 0.00 | 0.00 | 0.00 |
August | 93.37 | 30.27 | 63.09 | 127.34 | 20.87 | 0.00 | 0.00 | 0.00 |
September | 108.56 | 52.87 | 55.68 | 137.62 | 32.58 | 0.00 | 0.00 | 0.00 |
October | 103.87 | 59.33 | 44.54 | 117.82 | 45.40 | 0.00 | 0.00 | 0.00 |
November | 74.39 | 42.00 | 32.39 | 75.07 | 57.37 | 0.00 | 0.00 | 0.00 |
December | 69.42 | 35.93 | 33.49 | 56.54 | 84.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90.59 | 39.95 | 50.64 | 101.31 | 48.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.42 | 17.26 | 32.39 | 56.54 | 15.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.69 | 65.00 | 64.20 | 137.62 | 86.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.02 | 48.46 | 34.56 | 71.26 | 86.31 | 0.00 | 0.00 | 0.00 |
February | 94.78 | 45.70 | 49.08 | 80.84 | 83.97 | 0.00 | 0.00 | 0.00 |
March | 115.69 | 65.00 | 50.68 | 121.15 | 58.88 | 0.00 | 0.00 | 0.00 |
April | 95.81 | 38.29 | 57.52 | 106.16 | 43.75 | 0.00 | 0.00 | 0.00 |
May | 83.84 | 24.35 | 59.49 | 100.60 | 29.20 | 0.00 | 0.00 | 0.00 |
June | 81.47 | 17.26 | 64.20 | 104.19 | 21.74 | 0.00 | 0.00 | 0.00 |
July | 83.16 | 20.18 | 62.99 | 115.72 | 15.61 | 0.00 | 0.00 | 0.00 |
August | 93.37 | 30.27 | 63.09 | 127.34 | 20.87 | 0.00 | 0.00 | 0.00 |
September | 108.56 | 52.87 | 55.68 | 137.62 | 32.58 | 0.00 | 0.00 | 0.00 |
October | 103.87 | 59.33 | 44.54 | 117.82 | 45.40 | 0.00 | 0.00 | 0.00 |
November | 74.39 | 42.00 | 32.39 | 75.07 | 57.37 | 0.00 | 0.00 | 0.00 |
December | 69.42 | 35.93 | 33.49 | 56.54 | 84.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90.59 | 39.95 | 50.64 | 101.31 | 48.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.42 | 17.26 | 32.39 | 56.54 | 15.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.69 | 65.00 | 64.20 | 137.62 | 86.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 99.25 | 57.94 | 41.32 | 85.84 | 101.55 | 0.00 | 0.00 | 0.00 |
February | 113.32 | 54.64 | 58.68 | 97.58 | 98.70 | 0.00 | 0.00 | 0.00 |
March | 138.32 | 77.72 | 60.60 | 145.58 | 69.46 | 0.00 | 0.00 | 0.00 |
April | 114.55 | 45.77 | 68.77 | 127.44 | 51.63 | 0.00 | 0.00 | 0.00 |
May | 100.24 | 29.11 | 71.13 | 120.60 | 34.58 | 0.00 | 0.00 | 0.00 |
June | 97.40 | 20.64 | 76.76 | 124.75 | 25.80 | 0.00 | 0.00 | 0.00 |
July | 99.43 | 24.12 | 75.30 | 138.38 | 18.55 | 0.00 | 0.00 | 0.00 |
August | 111.63 | 36.19 | 75.43 | 152.31 | 24.79 | 0.00 | 0.00 | 0.00 |
September | 129.79 | 63.22 | 66.57 | 164.72 | 38.63 | 0.00 | 0.00 | 0.00 |
October | 124.19 | 70.94 | 53.25 | 141.29 | 53.69 | 0.00 | 0.00 | 0.00 |
November | 88.94 | 50.21 | 38.73 | 90.20 | 67.64 | 0.00 | 0.00 | 0.00 |
December | 82.99 | 42.95 | 40.04 | 68.21 | 99.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 108.30 | 47.76 | 60.54 | 121.55 | 56.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.99 | 20.64 | 38.73 | 68.21 | 18.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.32 | 77.72 | 76.76 | 164.72 | 101.55 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222349E+09 | 0.129792E+09 | 92557189.18 | 0.188725E+09 | 0.252669E+09 |
February | 0.229299E+09 | 0.110566E+09 | 0.118733E+09 | 0.193429E+09 | 0.220952E+09 |
March | 0.309861E+09 | 0.174109E+09 | 0.135752E+09 | 0.320719E+09 | 0.176639E+09 |
April | 0.248336E+09 | 99235703.68 | 0.149100E+09 | 0.270336E+09 | 0.130747E+09 |
May | 0.224560E+09 | 65221588.97 | 0.159338E+09 | 0.261767E+09 | 93660264.55 |
June | 0.211161E+09 | 44746050.03 | 0.166415E+09 | 0.267638E+09 | 61630089.94 |
July | 0.222746E+09 | 54045571.25 | 0.168701E+09 | 0.310317E+09 | 43215183.71 |
August | 0.250070E+09 | 81078819.00 | 0.168991E+09 | 0.341141E+09 | 57797223.28 |
September | 0.281377E+09 | 0.137052E+09 | 0.144326E+09 | 0.355158E+09 | 90220998.56 |
October | 0.278211E+09 | 0.158919E+09 | 0.119291E+09 | 0.311101E+09 | 0.135486E+09 |
November | 0.192821E+09 | 0.108854E+09 | 83967293.25 | 0.191004E+09 | 0.165518E+09 |
December | 0.185928E+09 | 96225999.83 | 89701650.75 | 0.149434E+09 | 0.247976E+09 |
Annual Sum or Average | 0.285672E+10 | 0.125985E+10 | 0.159687E+10 | 0.316077E+10 | 0.167651E+10 |
Minimum of Months | 0.185928E+09 | 44746050.03 | 83967293.25 | 0.149434E+09 | 43215183.71 |
Maximum of Months | 0.309861E+09 | 0.174109E+09 | 0.168991E+09 | 0.355158E+09 | 0.252669E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222349E+09 | 0.129792E+09 | 92557189.18 | 0.188725E+09 | 0.252669E+09 |
February | 0.229299E+09 | 0.110566E+09 | 0.118733E+09 | 0.193429E+09 | 0.220952E+09 |
March | 0.309861E+09 | 0.174109E+09 | 0.135752E+09 | 0.320719E+09 | 0.176639E+09 |
April | 0.248336E+09 | 99235703.68 | 0.149100E+09 | 0.270336E+09 | 0.130747E+09 |
May | 0.224560E+09 | 65221588.97 | 0.159338E+09 | 0.261767E+09 | 93660264.55 |
June | 0.211161E+09 | 44746050.03 | 0.166415E+09 | 0.267638E+09 | 61630089.94 |
July | 0.222746E+09 | 54045571.25 | 0.168701E+09 | 0.310317E+09 | 43215183.71 |
August | 0.250070E+09 | 81078819.00 | 0.168991E+09 | 0.341141E+09 | 57797223.28 |
September | 0.281377E+09 | 0.137052E+09 | 0.144326E+09 | 0.355158E+09 | 90220998.56 |
October | 0.278211E+09 | 0.158919E+09 | 0.119291E+09 | 0.311101E+09 | 0.135486E+09 |
November | 0.192821E+09 | 0.108854E+09 | 83967293.25 | 0.191004E+09 | 0.165518E+09 |
December | 0.185928E+09 | 96225999.83 | 89701650.75 | 0.149434E+09 | 0.247976E+09 |
Annual Sum or Average | 0.285672E+10 | 0.125985E+10 | 0.159687E+10 | 0.316077E+10 | 0.167651E+10 |
Minimum of Months | 0.185928E+09 | 44746050.03 | 83967293.25 | 0.149434E+09 | 43215183.71 |
Maximum of Months | 0.309861E+09 | 0.174109E+09 | 0.168991E+09 | 0.355158E+09 | 0.252669E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222349E+09 | 0.129792E+09 | 92557189.18 | 0.188725E+09 | 0.252669E+09 |
February | 0.229299E+09 | 0.110566E+09 | 0.118733E+09 | 0.193429E+09 | 0.220952E+09 |
March | 0.309861E+09 | 0.174109E+09 | 0.135752E+09 | 0.320719E+09 | 0.176639E+09 |
April | 0.248336E+09 | 99235703.68 | 0.149100E+09 | 0.270336E+09 | 0.130747E+09 |
May | 0.224560E+09 | 65221588.97 | 0.159338E+09 | 0.261767E+09 | 93660264.55 |
June | 0.211161E+09 | 44746050.03 | 0.166415E+09 | 0.267638E+09 | 61630089.94 |
July | 0.222746E+09 | 54045571.25 | 0.168701E+09 | 0.310317E+09 | 43215183.71 |
August | 0.250070E+09 | 81078819.00 | 0.168991E+09 | 0.341141E+09 | 57797223.28 |
September | 0.281377E+09 | 0.137052E+09 | 0.144326E+09 | 0.355158E+09 | 90220998.56 |
October | 0.278211E+09 | 0.158919E+09 | 0.119291E+09 | 0.311101E+09 | 0.135486E+09 |
November | 0.192821E+09 | 0.108854E+09 | 83967293.25 | 0.191004E+09 | 0.165518E+09 |
December | 0.185928E+09 | 96225999.83 | 89701650.75 | 0.149434E+09 | 0.247976E+09 |
Annual Sum or Average | 0.285672E+10 | 0.125985E+10 | 0.159687E+10 | 0.316077E+10 | 0.167651E+10 |
Minimum of Months | 0.185928E+09 | 44746050.03 | 83967293.25 | 0.149434E+09 | 43215183.71 |
Maximum of Months | 0.309861E+09 | 0.174109E+09 | 0.168991E+09 | 0.355158E+09 | 0.252669E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222349E+09 | 0.129792E+09 | 92557189.18 | 0.188725E+09 | 0.252669E+09 |
February | 0.229299E+09 | 0.110566E+09 | 0.118733E+09 | 0.193429E+09 | 0.220952E+09 |
March | 0.309861E+09 | 0.174109E+09 | 0.135752E+09 | 0.320719E+09 | 0.176639E+09 |
April | 0.248336E+09 | 99235703.68 | 0.149100E+09 | 0.270336E+09 | 0.130747E+09 |
May | 0.224560E+09 | 65221588.97 | 0.159338E+09 | 0.261767E+09 | 93660264.55 |
June | 0.211161E+09 | 44746050.03 | 0.166415E+09 | 0.267638E+09 | 61630089.94 |
July | 0.222746E+09 | 54045571.25 | 0.168701E+09 | 0.310317E+09 | 43215183.71 |
August | 0.250070E+09 | 81078819.00 | 0.168991E+09 | 0.341141E+09 | 57797223.28 |
September | 0.281377E+09 | 0.137052E+09 | 0.144326E+09 | 0.355158E+09 | 90220998.56 |
October | 0.278211E+09 | 0.158919E+09 | 0.119291E+09 | 0.311101E+09 | 0.135486E+09 |
November | 0.192821E+09 | 0.108854E+09 | 83967293.25 | 0.191004E+09 | 0.165518E+09 |
December | 0.185928E+09 | 96225999.83 | 89701650.75 | 0.149434E+09 | 0.247976E+09 |
Annual Sum or Average | 0.285672E+10 | 0.125985E+10 | 0.159687E+10 | 0.316077E+10 | 0.167651E+10 |
Minimum of Months | 0.185928E+09 | 44746050.03 | 83967293.25 | 0.149434E+09 | 43215183.71 |
Maximum of Months | 0.309861E+09 | 0.174109E+09 | 0.168991E+09 | 0.355158E+09 | 0.252669E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.267297E+09 | 0.156029E+09 | 0.111268E+09 | 0.228426E+09 | 0.299170E+09 |
February | 0.275652E+09 | 0.132917E+09 | 0.142735E+09 | 0.234585E+09 | 0.261315E+09 |
March | 0.372500E+09 | 0.209306E+09 | 0.163195E+09 | 0.387319E+09 | 0.209603E+09 |
April | 0.298538E+09 | 0.119297E+09 | 0.179241E+09 | 0.326180E+09 | 0.155196E+09 |
May | 0.269955E+09 | 78406390.86 | 0.191549E+09 | 0.315478E+09 | 0.111453E+09 |
June | 0.253848E+09 | 53791640.83 | 0.200056E+09 | 0.322128E+09 | 73540178.49 |
July | 0.267775E+09 | 64971097.01 | 0.202804E+09 | 0.373016E+09 | 51681274.65 |
August | 0.300622E+09 | 97469222.59 | 0.203153E+09 | 0.410143E+09 | 69043372.67 |
September | 0.338259E+09 | 0.164757E+09 | 0.173502E+09 | 0.427321E+09 | 0.107604E+09 |
October | 0.334452E+09 | 0.191046E+09 | 0.143407E+09 | 0.375018E+09 | 0.161119E+09 |
November | 0.231801E+09 | 0.130860E+09 | 0.100942E+09 | 0.230646E+09 | 0.196325E+09 |
December | 0.223514E+09 | 0.115678E+09 | 0.107835E+09 | 0.181122E+09 | 0.293317E+09 |
Annual Sum or Average | 0.343421E+10 | 0.151453E+10 | 0.191969E+10 | 0.381138E+10 | 0.198937E+10 |
Minimum of Months | 0.223514E+09 | 53791640.83 | 0.100942E+09 | 0.181122E+09 | 51681274.65 |
Maximum of Months | 0.372500E+09 | 0.209306E+09 | 0.203153E+09 | 0.427321E+09 | 0.299170E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.267297E+09 | 0.156029E+09 | 0.111268E+09 | 0.228426E+09 | 0.299170E+09 |
February | 0.275652E+09 | 0.132917E+09 | 0.142735E+09 | 0.234585E+09 | 0.261315E+09 |
March | 0.372500E+09 | 0.209306E+09 | 0.163195E+09 | 0.387319E+09 | 0.209603E+09 |
April | 0.298538E+09 | 0.119297E+09 | 0.179241E+09 | 0.326180E+09 | 0.155196E+09 |
May | 0.269955E+09 | 78406390.86 | 0.191549E+09 | 0.315478E+09 | 0.111453E+09 |
June | 0.253848E+09 | 53791640.83 | 0.200056E+09 | 0.322128E+09 | 73540178.49 |
July | 0.267775E+09 | 64971097.01 | 0.202804E+09 | 0.373016E+09 | 51681274.65 |
August | 0.300622E+09 | 97469222.59 | 0.203153E+09 | 0.410143E+09 | 69043372.67 |
September | 0.338259E+09 | 0.164757E+09 | 0.173502E+09 | 0.427321E+09 | 0.107604E+09 |
October | 0.334452E+09 | 0.191046E+09 | 0.143407E+09 | 0.375018E+09 | 0.161119E+09 |
November | 0.231801E+09 | 0.130860E+09 | 0.100942E+09 | 0.230646E+09 | 0.196325E+09 |
December | 0.223514E+09 | 0.115678E+09 | 0.107835E+09 | 0.181122E+09 | 0.293317E+09 |
Annual Sum or Average | 0.343421E+10 | 0.151453E+10 | 0.191969E+10 | 0.381138E+10 | 0.198937E+10 |
Minimum of Months | 0.223514E+09 | 53791640.83 | 0.100942E+09 | 0.181122E+09 | 51681274.65 |
Maximum of Months | 0.372500E+09 | 0.209306E+09 | 0.203153E+09 | 0.427321E+09 | 0.299170E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222349E+09 | 0.129792E+09 | 92557189.18 | 0.185652E+09 | 0.264406E+09 |
February | 0.229299E+09 | 0.110566E+09 | 0.118733E+09 | 0.189818E+09 | 0.231477E+09 |
March | 0.309861E+09 | 0.174109E+09 | 0.135752E+09 | 0.316082E+09 | 0.187523E+09 |
April | 0.248336E+09 | 99235703.68 | 0.149100E+09 | 0.265610E+09 | 0.141563E+09 |
May | 0.224560E+09 | 65221588.97 | 0.159338E+09 | 0.256816E+09 | 0.101214E+09 |
June | 0.211161E+09 | 44746050.03 | 0.166415E+09 | 0.265700E+09 | 63482599.84 |
July | 0.222746E+09 | 54045571.25 | 0.168701E+09 | 0.309429E+09 | 43932834.41 |
August | 0.250070E+09 | 81078819.00 | 0.168991E+09 | 0.340283E+09 | 58604414.51 |
September | 0.281377E+09 | 0.137052E+09 | 0.144326E+09 | 0.353413E+09 | 92709680.02 |
October | 0.278211E+09 | 0.158919E+09 | 0.119291E+09 | 0.307465E+09 | 0.144303E+09 |
November | 0.192821E+09 | 0.108854E+09 | 83967293.25 | 0.188112E+09 | 0.176137E+09 |
December | 0.185928E+09 | 96225999.83 | 89701650.75 | 0.146752E+09 | 0.260162E+09 |
Annual Sum or Average | 0.285672E+10 | 0.125985E+10 | 0.159687E+10 | 0.312513E+10 | 0.176552E+10 |
Minimum of Months | 0.185928E+09 | 44746050.03 | 83967293.25 | 0.146752E+09 | 43932834.41 |
Maximum of Months | 0.309861E+09 | 0.174109E+09 | 0.168991E+09 | 0.353413E+09 | 0.264406E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222349E+09 | 0.129792E+09 | 92557189.18 | 0.185652E+09 | 0.264406E+09 |
February | 0.229299E+09 | 0.110566E+09 | 0.118733E+09 | 0.189818E+09 | 0.231477E+09 |
March | 0.309861E+09 | 0.174109E+09 | 0.135752E+09 | 0.316082E+09 | 0.187523E+09 |
April | 0.248336E+09 | 99235703.68 | 0.149100E+09 | 0.265610E+09 | 0.141563E+09 |
May | 0.224560E+09 | 65221588.97 | 0.159338E+09 | 0.256816E+09 | 0.101214E+09 |
June | 0.211161E+09 | 44746050.03 | 0.166415E+09 | 0.265700E+09 | 63482599.84 |
July | 0.222746E+09 | 54045571.25 | 0.168701E+09 | 0.309429E+09 | 43932834.41 |
August | 0.250070E+09 | 81078819.00 | 0.168991E+09 | 0.340283E+09 | 58604414.51 |
September | 0.281377E+09 | 0.137052E+09 | 0.144326E+09 | 0.353413E+09 | 92709680.02 |
October | 0.278211E+09 | 0.158919E+09 | 0.119291E+09 | 0.307465E+09 | 0.144303E+09 |
November | 0.192821E+09 | 0.108854E+09 | 83967293.25 | 0.188112E+09 | 0.176137E+09 |
December | 0.185928E+09 | 96225999.83 | 89701650.75 | 0.146752E+09 | 0.260162E+09 |
Annual Sum or Average | 0.285672E+10 | 0.125985E+10 | 0.159687E+10 | 0.312513E+10 | 0.176552E+10 |
Minimum of Months | 0.185928E+09 | 44746050.03 | 83967293.25 | 0.146752E+09 | 43932834.41 |
Maximum of Months | 0.309861E+09 | 0.174109E+09 | 0.168991E+09 | 0.353413E+09 | 0.264406E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.267297E+09 | 0.156029E+09 | 0.111268E+09 | 0.224785E+09 | 0.312938E+09 |
February | 0.275652E+09 | 0.132917E+09 | 0.142735E+09 | 0.230322E+09 | 0.273628E+09 |
March | 0.372500E+09 | 0.209306E+09 | 0.163195E+09 | 0.381856E+09 | 0.222369E+09 |
April | 0.298538E+09 | 0.119297E+09 | 0.179241E+09 | 0.320602E+09 | 0.167869E+09 |
May | 0.269955E+09 | 78406390.86 | 0.191549E+09 | 0.309640E+09 | 0.120330E+09 |
June | 0.253848E+09 | 53791640.83 | 0.200056E+09 | 0.319878E+09 | 75716605.35 |
July | 0.267775E+09 | 64971097.01 | 0.202804E+09 | 0.372014E+09 | 52523795.03 |
August | 0.300622E+09 | 97469222.59 | 0.203153E+09 | 0.409188E+09 | 69985361.16 |
September | 0.338259E+09 | 0.164757E+09 | 0.173502E+09 | 0.425314E+09 | 0.110521E+09 |
October | 0.334452E+09 | 0.191046E+09 | 0.143407E+09 | 0.370766E+09 | 0.171435E+09 |
November | 0.231801E+09 | 0.130860E+09 | 0.100942E+09 | 0.227231E+09 | 0.208740E+09 |
December | 0.223514E+09 | 0.115678E+09 | 0.107835E+09 | 0.177939E+09 | 0.307575E+09 |
Annual Sum or Average | 0.343421E+10 | 0.151453E+10 | 0.191969E+10 | 0.376954E+10 | 0.209363E+10 |
Minimum of Months | 0.223514E+09 | 53791640.83 | 0.100942E+09 | 0.177939E+09 | 52523795.03 |
Maximum of Months | 0.372500E+09 | 0.209306E+09 | 0.203153E+09 | 0.425314E+09 | 0.312938E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222349E+09 | 0.129792E+09 | 92557189.18 | 0.185808E+09 | 0.257648E+09 |
February | 0.229299E+09 | 0.110566E+09 | 0.118733E+09 | 0.189978E+09 | 0.225424E+09 |
March | 0.309861E+09 | 0.174109E+09 | 0.135752E+09 | 0.316487E+09 | 0.182354E+09 |
April | 0.248336E+09 | 99235703.68 | 0.149100E+09 | 0.266554E+09 | 0.136666E+09 |
May | 0.224560E+09 | 65221588.97 | 0.159338E+09 | 0.257929E+09 | 99365993.11 |
June | 0.211161E+09 | 44746050.03 | 0.166415E+09 | 0.265227E+09 | 66080969.59 |
July | 0.222746E+09 | 54045571.25 | 0.168701E+09 | 0.308088E+09 | 47950796.61 |
August | 0.250070E+09 | 81078819.00 | 0.168991E+09 | 0.339551E+09 | 62645090.78 |
September | 0.281377E+09 | 0.137052E+09 | 0.144326E+09 | 0.353452E+09 | 94873411.31 |
October | 0.278211E+09 | 0.158919E+09 | 0.119291E+09 | 0.308672E+09 | 0.140171E+09 |
November | 0.192821E+09 | 0.108854E+09 | 83967293.25 | 0.188934E+09 | 0.170571E+09 |
December | 0.185928E+09 | 96225999.83 | 89701650.75 | 0.147035E+09 | 0.253592E+09 |
Annual Sum or Average | 0.285672E+10 | 0.125985E+10 | 0.159687E+10 | 0.312771E+10 | 0.173734E+10 |
Minimum of Months | 0.185928E+09 | 44746050.03 | 83967293.25 | 0.147035E+09 | 47950796.61 |
Maximum of Months | 0.309861E+09 | 0.174109E+09 | 0.168991E+09 | 0.353452E+09 | 0.257648E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222349E+09 | 0.129792E+09 | 92557189.18 | 0.185808E+09 | 0.257648E+09 |
February | 0.229299E+09 | 0.110566E+09 | 0.118733E+09 | 0.189978E+09 | 0.225424E+09 |
March | 0.309861E+09 | 0.174109E+09 | 0.135752E+09 | 0.316487E+09 | 0.182354E+09 |
April | 0.248336E+09 | 99235703.68 | 0.149100E+09 | 0.266554E+09 | 0.136666E+09 |
May | 0.224560E+09 | 65221588.97 | 0.159338E+09 | 0.257929E+09 | 99365993.11 |
June | 0.211161E+09 | 44746050.03 | 0.166415E+09 | 0.265227E+09 | 66080969.59 |
July | 0.222746E+09 | 54045571.25 | 0.168701E+09 | 0.308088E+09 | 47950796.61 |
August | 0.250070E+09 | 81078819.00 | 0.168991E+09 | 0.339551E+09 | 62645090.78 |
September | 0.281377E+09 | 0.137052E+09 | 0.144326E+09 | 0.353452E+09 | 94873411.31 |
October | 0.278211E+09 | 0.158919E+09 | 0.119291E+09 | 0.308672E+09 | 0.140171E+09 |
November | 0.192821E+09 | 0.108854E+09 | 83967293.25 | 0.188934E+09 | 0.170571E+09 |
December | 0.185928E+09 | 96225999.83 | 89701650.75 | 0.147035E+09 | 0.253592E+09 |
Annual Sum or Average | 0.285672E+10 | 0.125985E+10 | 0.159687E+10 | 0.312771E+10 | 0.173734E+10 |
Minimum of Months | 0.185928E+09 | 44746050.03 | 83967293.25 | 0.147035E+09 | 47950796.61 |
Maximum of Months | 0.309861E+09 | 0.174109E+09 | 0.168991E+09 | 0.353452E+09 | 0.257648E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.265837E+09 | 0.155177E+09 | 0.110660E+09 | 0.223761E+09 | 0.303304E+09 |
February | 0.274146E+09 | 0.132191E+09 | 0.141955E+09 | 0.229278E+09 | 0.265063E+09 |
March | 0.370465E+09 | 0.208162E+09 | 0.162303E+09 | 0.380273E+09 | 0.215116E+09 |
April | 0.296906E+09 | 0.118645E+09 | 0.178262E+09 | 0.319983E+09 | 0.161236E+09 |
May | 0.268480E+09 | 77977940.64 | 0.190502E+09 | 0.309269E+09 | 0.117496E+09 |
June | 0.252461E+09 | 53497697.44 | 0.198963E+09 | 0.317574E+09 | 78318408.84 |
July | 0.266312E+09 | 64616063.69 | 0.201696E+09 | 0.368413E+09 | 56921685.01 |
August | 0.298979E+09 | 96936603.89 | 0.202043E+09 | 0.406088E+09 | 74307039.17 |
September | 0.336410E+09 | 0.163857E+09 | 0.172553E+09 | 0.423036E+09 | 0.112422E+09 |
October | 0.332625E+09 | 0.190002E+09 | 0.142623E+09 | 0.370176E+09 | 0.165660E+09 |
November | 0.230534E+09 | 0.130144E+09 | 0.100390E+09 | 0.226981E+09 | 0.201104E+09 |
December | 0.222292E+09 | 0.115046E+09 | 0.107246E+09 | 0.177320E+09 | 0.298205E+09 |
Annual Sum or Average | 0.341545E+10 | 0.150625E+10 | 0.190920E+10 | 0.375215E+10 | 0.204915E+10 |
Minimum of Months | 0.222292E+09 | 53497697.44 | 0.100390E+09 | 0.177320E+09 | 56921685.01 |
Maximum of Months | 0.370465E+09 | 0.208162E+09 | 0.202043E+09 | 0.423036E+09 | 0.303304E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222349E+09 | 0.129792E+09 | 92557189.18 | 0.186132E+09 | 0.255001E+09 |
February | 0.229299E+09 | 0.110566E+09 | 0.118733E+09 | 0.190329E+09 | 0.223190E+09 |
March | 0.309861E+09 | 0.174109E+09 | 0.135752E+09 | 0.317026E+09 | 0.180198E+09 |
April | 0.248336E+09 | 99235703.68 | 0.149100E+09 | 0.267276E+09 | 0.134417E+09 |
May | 0.224560E+09 | 65221588.97 | 0.159338E+09 | 0.258824E+09 | 97535528.05 |
June | 0.211161E+09 | 44746050.03 | 0.166415E+09 | 0.265342E+09 | 65871886.72 |
July | 0.222746E+09 | 54045571.25 | 0.168701E+09 | 0.308024E+09 | 48117722.18 |
August | 0.250070E+09 | 81078819.00 | 0.168991E+09 | 0.339512E+09 | 62771372.72 |
September | 0.281377E+09 | 0.137052E+09 | 0.144326E+09 | 0.353598E+09 | 94434167.76 |
October | 0.278211E+09 | 0.158919E+09 | 0.119291E+09 | 0.309404E+09 | 0.138014E+09 |
November | 0.192821E+09 | 0.108854E+09 | 83967293.25 | 0.189453E+09 | 0.168190E+09 |
December | 0.185928E+09 | 96225999.83 | 89701650.75 | 0.147337E+09 | 0.250979E+09 |
Annual Sum or Average | 0.285672E+10 | 0.125985E+10 | 0.159687E+10 | 0.313226E+10 | 0.171872E+10 |
Minimum of Months | 0.185928E+09 | 44746050.03 | 83967293.25 | 0.147337E+09 | 48117722.18 |
Maximum of Months | 0.309861E+09 | 0.174109E+09 | 0.168991E+09 | 0.353598E+09 | 0.255001E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222349E+09 | 0.129792E+09 | 92557189.18 | 0.186132E+09 | 0.255001E+09 |
February | 0.229299E+09 | 0.110566E+09 | 0.118733E+09 | 0.190329E+09 | 0.223190E+09 |
March | 0.309861E+09 | 0.174109E+09 | 0.135752E+09 | 0.317026E+09 | 0.180198E+09 |
April | 0.248336E+09 | 99235703.68 | 0.149100E+09 | 0.267276E+09 | 0.134417E+09 |
May | 0.224560E+09 | 65221588.97 | 0.159338E+09 | 0.258824E+09 | 97535528.05 |
June | 0.211161E+09 | 44746050.03 | 0.166415E+09 | 0.265342E+09 | 65871886.72 |
July | 0.222746E+09 | 54045571.25 | 0.168701E+09 | 0.308024E+09 | 48117722.18 |
August | 0.250070E+09 | 81078819.00 | 0.168991E+09 | 0.339512E+09 | 62771372.72 |
September | 0.281377E+09 | 0.137052E+09 | 0.144326E+09 | 0.353598E+09 | 94434167.76 |
October | 0.278211E+09 | 0.158919E+09 | 0.119291E+09 | 0.309404E+09 | 0.138014E+09 |
November | 0.192821E+09 | 0.108854E+09 | 83967293.25 | 0.189453E+09 | 0.168190E+09 |
December | 0.185928E+09 | 96225999.83 | 89701650.75 | 0.147337E+09 | 0.250979E+09 |
Annual Sum or Average | 0.285672E+10 | 0.125985E+10 | 0.159687E+10 | 0.313226E+10 | 0.171872E+10 |
Minimum of Months | 0.185928E+09 | 44746050.03 | 83967293.25 | 0.147337E+09 | 48117722.18 |
Maximum of Months | 0.309861E+09 | 0.174109E+09 | 0.168991E+09 | 0.353598E+09 | 0.255001E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.265837E+09 | 0.155177E+09 | 0.110660E+09 | 0.224158E+09 | 0.300172E+09 |
February | 0.274146E+09 | 0.132191E+09 | 0.141955E+09 | 0.229706E+09 | 0.262426E+09 |
March | 0.370465E+09 | 0.208162E+09 | 0.162303E+09 | 0.380925E+09 | 0.212571E+09 |
April | 0.296906E+09 | 0.118645E+09 | 0.178262E+09 | 0.320849E+09 | 0.158583E+09 |
May | 0.268480E+09 | 77977940.64 | 0.190502E+09 | 0.310337E+09 | 0.115340E+09 |
June | 0.252461E+09 | 53497697.44 | 0.198963E+09 | 0.317712E+09 | 78071700.89 |
July | 0.266312E+09 | 64616063.69 | 0.201696E+09 | 0.368336E+09 | 57119164.39 |
August | 0.298979E+09 | 96936603.89 | 0.202043E+09 | 0.406040E+09 | 74455887.43 |
September | 0.336410E+09 | 0.163857E+09 | 0.172553E+09 | 0.423212E+09 | 0.111903E+09 |
October | 0.332625E+09 | 0.190002E+09 | 0.142623E+09 | 0.371052E+09 | 0.163117E+09 |
November | 0.230534E+09 | 0.130144E+09 | 0.100390E+09 | 0.227606E+09 | 0.198296E+09 |
December | 0.222292E+09 | 0.115046E+09 | 0.107246E+09 | 0.177688E+09 | 0.295115E+09 |
Annual Sum or Average | 0.341545E+10 | 0.150625E+10 | 0.190920E+10 | 0.375762E+10 | 0.202717E+10 |
Minimum of Months | 0.222292E+09 | 53497697.44 | 0.100390E+09 | 0.177688E+09 | 57119164.39 |
Maximum of Months | 0.370465E+09 | 0.208162E+09 | 0.202043E+09 | 0.423212E+09 | 0.300172E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222349E+09 | 0.129792E+09 | 92557189.18 | 0.186517E+09 | 0.253060E+09 |
February | 0.229299E+09 | 0.110566E+09 | 0.118733E+09 | 0.190748E+09 | 0.221574E+09 |
March | 0.309861E+09 | 0.174109E+09 | 0.135752E+09 | 0.317648E+09 | 0.178518E+09 |
April | 0.248336E+09 | 99235703.68 | 0.149100E+09 | 0.268028E+09 | 0.132720E+09 |
May | 0.224560E+09 | 65221588.97 | 0.159338E+09 | 0.259867E+09 | 95817442.69 |
June | 0.211161E+09 | 44746050.03 | 0.166415E+09 | 0.265717E+09 | 65220716.70 |
July | 0.222746E+09 | 54045571.25 | 0.168701E+09 | 0.308274E+09 | 47596488.26 |
August | 0.250070E+09 | 81078819.00 | 0.168991E+09 | 0.339728E+09 | 62204397.75 |
September | 0.281377E+09 | 0.137052E+09 | 0.144326E+09 | 0.353906E+09 | 93655609.58 |
October | 0.278211E+09 | 0.158919E+09 | 0.119291E+09 | 0.310111E+09 | 0.136410E+09 |
November | 0.192821E+09 | 0.108854E+09 | 83967293.25 | 0.189947E+09 | 0.166485E+09 |
December | 0.185928E+09 | 96225999.83 | 89701650.75 | 0.147681E+09 | 0.249004E+09 |
Annual Sum or Average | 0.285672E+10 | 0.125985E+10 | 0.159687E+10 | 0.313817E+10 | 0.170226E+10 |
Minimum of Months | 0.185928E+09 | 44746050.03 | 83967293.25 | 0.147681E+09 | 47596488.26 |
Maximum of Months | 0.309861E+09 | 0.174109E+09 | 0.168991E+09 | 0.353906E+09 | 0.253060E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222349E+09 | 0.129792E+09 | 92557189.18 | 0.186517E+09 | 0.253060E+09 |
February | 0.229299E+09 | 0.110566E+09 | 0.118733E+09 | 0.190748E+09 | 0.221574E+09 |
March | 0.309861E+09 | 0.174109E+09 | 0.135752E+09 | 0.317648E+09 | 0.178518E+09 |
April | 0.248336E+09 | 99235703.68 | 0.149100E+09 | 0.268028E+09 | 0.132720E+09 |
May | 0.224560E+09 | 65221588.97 | 0.159338E+09 | 0.259867E+09 | 95817442.69 |
June | 0.211161E+09 | 44746050.03 | 0.166415E+09 | 0.265717E+09 | 65220716.70 |
July | 0.222746E+09 | 54045571.25 | 0.168701E+09 | 0.308274E+09 | 47596488.26 |
August | 0.250070E+09 | 81078819.00 | 0.168991E+09 | 0.339728E+09 | 62204397.75 |
September | 0.281377E+09 | 0.137052E+09 | 0.144326E+09 | 0.353906E+09 | 93655609.58 |
October | 0.278211E+09 | 0.158919E+09 | 0.119291E+09 | 0.310111E+09 | 0.136410E+09 |
November | 0.192821E+09 | 0.108854E+09 | 83967293.25 | 0.189947E+09 | 0.166485E+09 |
December | 0.185928E+09 | 96225999.83 | 89701650.75 | 0.147681E+09 | 0.249004E+09 |
Annual Sum or Average | 0.285672E+10 | 0.125985E+10 | 0.159687E+10 | 0.313817E+10 | 0.170226E+10 |
Minimum of Months | 0.185928E+09 | 44746050.03 | 83967293.25 | 0.147681E+09 | 47596488.26 |
Maximum of Months | 0.309861E+09 | 0.174109E+09 | 0.168991E+09 | 0.353906E+09 | 0.253060E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.265837E+09 | 0.155177E+09 | 0.110660E+09 | 0.224628E+09 | 0.297879E+09 |
February | 0.274146E+09 | 0.132191E+09 | 0.141955E+09 | 0.230215E+09 | 0.260518E+09 |
March | 0.370465E+09 | 0.208162E+09 | 0.162303E+09 | 0.381678E+09 | 0.210592E+09 |
April | 0.296906E+09 | 0.118645E+09 | 0.178262E+09 | 0.321749E+09 | 0.156585E+09 |
May | 0.268480E+09 | 77977940.64 | 0.190502E+09 | 0.311578E+09 | 0.113320E+09 |
June | 0.252461E+09 | 53497697.44 | 0.198963E+09 | 0.318161E+09 | 77309787.89 |
July | 0.266312E+09 | 64616063.69 | 0.201696E+09 | 0.368636E+09 | 56510135.06 |
August | 0.298979E+09 | 96936603.89 | 0.202043E+09 | 0.406300E+09 | 73791491.92 |
September | 0.336410E+09 | 0.163857E+09 | 0.172553E+09 | 0.423580E+09 | 0.110989E+09 |
October | 0.332625E+09 | 0.190002E+09 | 0.142623E+09 | 0.371894E+09 | 0.161230E+09 |
November | 0.230534E+09 | 0.130144E+09 | 0.100390E+09 | 0.228202E+09 | 0.196289E+09 |
December | 0.222292E+09 | 0.115046E+09 | 0.107246E+09 | 0.178109E+09 | 0.292783E+09 |
Annual Sum or Average | 0.341545E+10 | 0.150625E+10 | 0.190920E+10 | 0.376473E+10 | 0.200780E+10 |
Minimum of Months | 0.222292E+09 | 53497697.44 | 0.100390E+09 | 0.178109E+09 | 56510135.06 |
Maximum of Months | 0.370465E+09 | 0.208162E+09 | 0.202043E+09 | 0.423580E+09 | 0.297879E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222349E+09 | 0.129792E+09 | 92557189.18 | 0.188869E+09 | 0.246530E+09 |
February | 0.229299E+09 | 0.110566E+09 | 0.118733E+09 | 0.193574E+09 | 0.215939E+09 |
March | 0.309861E+09 | 0.174109E+09 | 0.135752E+09 | 0.320684E+09 | 0.174093E+09 |
April | 0.248336E+09 | 99235703.68 | 0.149100E+09 | 0.270363E+09 | 0.129145E+09 |
May | 0.224560E+09 | 65221588.97 | 0.159338E+09 | 0.261837E+09 | 92812777.86 |
June | 0.211161E+09 | 44746050.03 | 0.166415E+09 | 0.266441E+09 | 63575844.29 |
July | 0.222746E+09 | 54045571.25 | 0.168701E+09 | 0.308500E+09 | 46095107.66 |
August | 0.250070E+09 | 81078819.00 | 0.168991E+09 | 0.339982E+09 | 60509458.79 |
September | 0.281377E+09 | 0.137052E+09 | 0.144326E+09 | 0.354594E+09 | 91941853.71 |
October | 0.278211E+09 | 0.158919E+09 | 0.119291E+09 | 0.311900E+09 | 0.133551E+09 |
November | 0.192821E+09 | 0.108854E+09 | 83967293.25 | 0.191707E+09 | 0.162373E+09 |
December | 0.185928E+09 | 96225999.83 | 89701650.75 | 0.149712E+09 | 0.242324E+09 |
Annual Sum or Average | 0.285672E+10 | 0.125985E+10 | 0.159687E+10 | 0.315816E+10 | 0.165889E+10 |
Minimum of Months | 0.185928E+09 | 44746050.03 | 83967293.25 | 0.149712E+09 | 46095107.66 |
Maximum of Months | 0.309861E+09 | 0.174109E+09 | 0.168991E+09 | 0.354594E+09 | 0.246530E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222349E+09 | 0.129792E+09 | 92557189.18 | 0.188869E+09 | 0.246530E+09 |
February | 0.229299E+09 | 0.110566E+09 | 0.118733E+09 | 0.193574E+09 | 0.215939E+09 |
March | 0.309861E+09 | 0.174109E+09 | 0.135752E+09 | 0.320684E+09 | 0.174093E+09 |
April | 0.248336E+09 | 99235703.68 | 0.149100E+09 | 0.270363E+09 | 0.129145E+09 |
May | 0.224560E+09 | 65221588.97 | 0.159338E+09 | 0.261837E+09 | 92812777.86 |
June | 0.211161E+09 | 44746050.03 | 0.166415E+09 | 0.266441E+09 | 63575844.29 |
July | 0.222746E+09 | 54045571.25 | 0.168701E+09 | 0.308500E+09 | 46095107.66 |
August | 0.250070E+09 | 81078819.00 | 0.168991E+09 | 0.339982E+09 | 60509458.79 |
September | 0.281377E+09 | 0.137052E+09 | 0.144326E+09 | 0.354594E+09 | 91941853.71 |
October | 0.278211E+09 | 0.158919E+09 | 0.119291E+09 | 0.311900E+09 | 0.133551E+09 |
November | 0.192821E+09 | 0.108854E+09 | 83967293.25 | 0.191707E+09 | 0.162373E+09 |
December | 0.185928E+09 | 96225999.83 | 89701650.75 | 0.149712E+09 | 0.242324E+09 |
Annual Sum or Average | 0.285672E+10 | 0.125985E+10 | 0.159687E+10 | 0.315816E+10 | 0.165889E+10 |
Minimum of Months | 0.185928E+09 | 44746050.03 | 83967293.25 | 0.149712E+09 | 46095107.66 |
Maximum of Months | 0.309861E+09 | 0.174109E+09 | 0.168991E+09 | 0.354594E+09 | 0.246530E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222349E+09 | 0.129792E+09 | 92557189.18 | 0.188869E+09 | 0.246530E+09 |
February | 0.229299E+09 | 0.110566E+09 | 0.118733E+09 | 0.193574E+09 | 0.215939E+09 |
March | 0.309861E+09 | 0.174109E+09 | 0.135752E+09 | 0.320684E+09 | 0.174093E+09 |
April | 0.248336E+09 | 99235703.68 | 0.149100E+09 | 0.270363E+09 | 0.129145E+09 |
May | 0.224560E+09 | 65221588.97 | 0.159338E+09 | 0.261837E+09 | 92812777.86 |
June | 0.211161E+09 | 44746050.03 | 0.166415E+09 | 0.266441E+09 | 63575844.29 |
July | 0.222746E+09 | 54045571.25 | 0.168701E+09 | 0.308500E+09 | 46095107.66 |
August | 0.250070E+09 | 81078819.00 | 0.168991E+09 | 0.339982E+09 | 60509458.79 |
September | 0.281377E+09 | 0.137052E+09 | 0.144326E+09 | 0.354594E+09 | 91941853.71 |
October | 0.278211E+09 | 0.158919E+09 | 0.119291E+09 | 0.311900E+09 | 0.133551E+09 |
November | 0.192821E+09 | 0.108854E+09 | 83967293.25 | 0.191707E+09 | 0.162373E+09 |
December | 0.185928E+09 | 96225999.83 | 89701650.75 | 0.149712E+09 | 0.242324E+09 |
Annual Sum or Average | 0.285672E+10 | 0.125985E+10 | 0.159687E+10 | 0.315816E+10 | 0.165889E+10 |
Minimum of Months | 0.185928E+09 | 44746050.03 | 83967293.25 | 0.149712E+09 | 46095107.66 |
Maximum of Months | 0.309861E+09 | 0.174109E+09 | 0.168991E+09 | 0.354594E+09 | 0.246530E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222349E+09 | 0.129792E+09 | 92557189.18 | 0.188869E+09 | 0.246530E+09 |
February | 0.229299E+09 | 0.110566E+09 | 0.118733E+09 | 0.193574E+09 | 0.215939E+09 |
March | 0.309861E+09 | 0.174109E+09 | 0.135752E+09 | 0.320684E+09 | 0.174093E+09 |
April | 0.248336E+09 | 99235703.68 | 0.149100E+09 | 0.270363E+09 | 0.129145E+09 |
May | 0.224560E+09 | 65221588.97 | 0.159338E+09 | 0.261837E+09 | 92812777.86 |
June | 0.211161E+09 | 44746050.03 | 0.166415E+09 | 0.266441E+09 | 63575844.29 |
July | 0.222746E+09 | 54045571.25 | 0.168701E+09 | 0.308500E+09 | 46095107.66 |
August | 0.250070E+09 | 81078819.00 | 0.168991E+09 | 0.339982E+09 | 60509458.79 |
September | 0.281377E+09 | 0.137052E+09 | 0.144326E+09 | 0.354594E+09 | 91941853.71 |
October | 0.278211E+09 | 0.158919E+09 | 0.119291E+09 | 0.311900E+09 | 0.133551E+09 |
November | 0.192821E+09 | 0.108854E+09 | 83967293.25 | 0.191707E+09 | 0.162373E+09 |
December | 0.185928E+09 | 96225999.83 | 89701650.75 | 0.149712E+09 | 0.242324E+09 |
Annual Sum or Average | 0.285672E+10 | 0.125985E+10 | 0.159687E+10 | 0.315816E+10 | 0.165889E+10 |
Minimum of Months | 0.185928E+09 | 44746050.03 | 83967293.25 | 0.149712E+09 | 46095107.66 |
Maximum of Months | 0.309861E+09 | 0.174109E+09 | 0.168991E+09 | 0.354594E+09 | 0.246530E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.265837E+09 | 0.155177E+09 | 0.110660E+09 | 0.227359E+09 | 0.290364E+09 |
February | 0.274146E+09 | 0.132191E+09 | 0.141955E+09 | 0.233478E+09 | 0.254057E+09 |
March | 0.370465E+09 | 0.208162E+09 | 0.162303E+09 | 0.385164E+09 | 0.205478E+09 |
April | 0.296906E+09 | 0.118645E+09 | 0.178262E+09 | 0.324438E+09 | 0.152457E+09 |
May | 0.268480E+09 | 77977940.64 | 0.190502E+09 | 0.313848E+09 | 0.109820E+09 |
June | 0.252461E+09 | 53497697.44 | 0.198963E+09 | 0.318968E+09 | 75390970.42 |
July | 0.266312E+09 | 64616063.69 | 0.201696E+09 | 0.368862E+09 | 54751479.54 |
August | 0.298979E+09 | 96936603.89 | 0.202043E+09 | 0.406556E+09 | 71813653.27 |
September | 0.336410E+09 | 0.163857E+09 | 0.172553E+09 | 0.424331E+09 | 0.108993E+09 |
October | 0.332625E+09 | 0.190002E+09 | 0.142623E+09 | 0.373930E+09 | 0.157924E+09 |
November | 0.230534E+09 | 0.130144E+09 | 0.100390E+09 | 0.230234E+09 | 0.191537E+09 |
December | 0.222292E+09 | 0.115046E+09 | 0.107246E+09 | 0.180470E+09 | 0.285109E+09 |
Annual Sum or Average | 0.341545E+10 | 0.150625E+10 | 0.190920E+10 | 0.378764E+10 | 0.195770E+10 |
Minimum of Months | 0.222292E+09 | 53497697.44 | 0.100390E+09 | 0.180470E+09 | 54751479.54 |
Maximum of Months | 0.370465E+09 | 0.208162E+09 | 0.202043E+09 | 0.424331E+09 | 0.290364E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.265837E+09 | 0.155177E+09 | 0.110660E+09 | 0.227359E+09 | 0.290364E+09 |
February | 0.274146E+09 | 0.132191E+09 | 0.141955E+09 | 0.233478E+09 | 0.254057E+09 |
March | 0.370465E+09 | 0.208162E+09 | 0.162303E+09 | 0.385164E+09 | 0.205478E+09 |
April | 0.296906E+09 | 0.118645E+09 | 0.178262E+09 | 0.324438E+09 | 0.152457E+09 |
May | 0.268480E+09 | 77977940.64 | 0.190502E+09 | 0.313848E+09 | 0.109820E+09 |
June | 0.252461E+09 | 53497697.44 | 0.198963E+09 | 0.318968E+09 | 75390970.42 |
July | 0.266312E+09 | 64616063.69 | 0.201696E+09 | 0.368862E+09 | 54751479.54 |
August | 0.298979E+09 | 96936603.89 | 0.202043E+09 | 0.406556E+09 | 71813653.27 |
September | 0.336410E+09 | 0.163857E+09 | 0.172553E+09 | 0.424331E+09 | 0.108993E+09 |
October | 0.332625E+09 | 0.190002E+09 | 0.142623E+09 | 0.373930E+09 | 0.157924E+09 |
November | 0.230534E+09 | 0.130144E+09 | 0.100390E+09 | 0.230234E+09 | 0.191537E+09 |
December | 0.222292E+09 | 0.115046E+09 | 0.107246E+09 | 0.180470E+09 | 0.285109E+09 |
Annual Sum or Average | 0.341545E+10 | 0.150625E+10 | 0.190920E+10 | 0.378764E+10 | 0.195770E+10 |
Minimum of Months | 0.222292E+09 | 53497697.44 | 0.100390E+09 | 0.180470E+09 | 54751479.54 |
Maximum of Months | 0.370465E+09 | 0.208162E+09 | 0.202043E+09 | 0.424331E+09 | 0.290364E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222349E+09 | 0.129792E+09 | 92557189.18 | 0.187838E+09 | 0.248637E+09 |
February | 0.229299E+09 | 0.110566E+09 | 0.118733E+09 | 0.192286E+09 | 0.217867E+09 |
March | 0.309861E+09 | 0.174109E+09 | 0.135752E+09 | 0.319478E+09 | 0.174926E+09 |
April | 0.248336E+09 | 99235703.68 | 0.149100E+09 | 0.269634E+09 | 0.129425E+09 |
May | 0.224560E+09 | 65221588.97 | 0.159338E+09 | 0.261519E+09 | 92525967.48 |
June | 0.211161E+09 | 44746050.03 | 0.166415E+09 | 0.266215E+09 | 63217165.30 |
July | 0.222746E+09 | 54045571.25 | 0.168701E+09 | 0.308470E+09 | 45558698.65 |
August | 0.250070E+09 | 81078819.00 | 0.168991E+09 | 0.339808E+09 | 59979535.71 |
September | 0.281377E+09 | 0.137052E+09 | 0.144326E+09 | 0.354157E+09 | 91653988.65 |
October | 0.278211E+09 | 0.158919E+09 | 0.119291E+09 | 0.311220E+09 | 0.133641E+09 |
November | 0.192821E+09 | 0.108854E+09 | 83967293.25 | 0.191069E+09 | 0.163121E+09 |
December | 0.185928E+09 | 96225999.83 | 89701650.75 | 0.148772E+09 | 0.244466E+09 |
Annual Sum or Average | 0.285672E+10 | 0.125985E+10 | 0.159687E+10 | 0.315047E+10 | 0.166502E+10 |
Minimum of Months | 0.185928E+09 | 44746050.03 | 83967293.25 | 0.148772E+09 | 45558698.65 |
Maximum of Months | 0.309861E+09 | 0.174109E+09 | 0.168991E+09 | 0.354157E+09 | 0.248637E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222349E+09 | 0.129792E+09 | 92557189.18 | 0.187838E+09 | 0.248637E+09 |
February | 0.229299E+09 | 0.110566E+09 | 0.118733E+09 | 0.192286E+09 | 0.217867E+09 |
March | 0.309861E+09 | 0.174109E+09 | 0.135752E+09 | 0.319478E+09 | 0.174926E+09 |
April | 0.248336E+09 | 99235703.68 | 0.149100E+09 | 0.269634E+09 | 0.129425E+09 |
May | 0.224560E+09 | 65221588.97 | 0.159338E+09 | 0.261519E+09 | 92525967.48 |
June | 0.211161E+09 | 44746050.03 | 0.166415E+09 | 0.266215E+09 | 63217165.30 |
July | 0.222746E+09 | 54045571.25 | 0.168701E+09 | 0.308470E+09 | 45558698.65 |
August | 0.250070E+09 | 81078819.00 | 0.168991E+09 | 0.339808E+09 | 59979535.71 |
September | 0.281377E+09 | 0.137052E+09 | 0.144326E+09 | 0.354157E+09 | 91653988.65 |
October | 0.278211E+09 | 0.158919E+09 | 0.119291E+09 | 0.311220E+09 | 0.133641E+09 |
November | 0.192821E+09 | 0.108854E+09 | 83967293.25 | 0.191069E+09 | 0.163121E+09 |
December | 0.185928E+09 | 96225999.83 | 89701650.75 | 0.148772E+09 | 0.244466E+09 |
Annual Sum or Average | 0.285672E+10 | 0.125985E+10 | 0.159687E+10 | 0.315047E+10 | 0.166502E+10 |
Minimum of Months | 0.185928E+09 | 44746050.03 | 83967293.25 | 0.148772E+09 | 45558698.65 |
Maximum of Months | 0.309861E+09 | 0.174109E+09 | 0.168991E+09 | 0.354157E+09 | 0.248637E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.265837E+09 | 0.155177E+09 | 0.110660E+09 | 0.226223E+09 | 0.292673E+09 |
February | 0.274146E+09 | 0.132191E+09 | 0.141955E+09 | 0.232067E+09 | 0.256167E+09 |
March | 0.370465E+09 | 0.208162E+09 | 0.162303E+09 | 0.383872E+09 | 0.206357E+09 |
April | 0.296906E+09 | 0.118645E+09 | 0.178262E+09 | 0.323681E+09 | 0.152708E+09 |
May | 0.268480E+09 | 77977940.64 | 0.190502E+09 | 0.313561E+09 | 0.109442E+09 |
June | 0.252461E+09 | 53497697.44 | 0.198963E+09 | 0.318774E+09 | 74952778.49 |
July | 0.266312E+09 | 64616063.69 | 0.201696E+09 | 0.368894E+09 | 54113328.87 |
August | 0.298979E+09 | 96936603.89 | 0.202043E+09 | 0.406425E+09 | 71175424.02 |
September | 0.336410E+09 | 0.163857E+09 | 0.172553E+09 | 0.423902E+09 | 0.108626E+09 |
October | 0.332625E+09 | 0.190002E+09 | 0.142623E+09 | 0.373230E+09 | 0.157963E+09 |
November | 0.230534E+09 | 0.130144E+09 | 0.100390E+09 | 0.229552E+09 | 0.192316E+09 |
December | 0.222292E+09 | 0.115046E+09 | 0.107246E+09 | 0.179438E+09 | 0.287450E+09 |
Annual Sum or Average | 0.341545E+10 | 0.150625E+10 | 0.190920E+10 | 0.377962E+10 | 0.196394E+10 |
Minimum of Months | 0.222292E+09 | 53497697.44 | 0.100390E+09 | 0.179438E+09 | 54113328.87 |
Maximum of Months | 0.370465E+09 | 0.208162E+09 | 0.202043E+09 | 0.423902E+09 | 0.292673E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222349E+09 | 0.129792E+09 | 92557189.18 | 0.187950E+09 | 0.248084E+09 |
February | 0.229299E+09 | 0.110566E+09 | 0.118733E+09 | 0.192405E+09 | 0.217437E+09 |
March | 0.309861E+09 | 0.174109E+09 | 0.135752E+09 | 0.319770E+09 | 0.174173E+09 |
April | 0.248336E+09 | 99235703.68 | 0.149100E+09 | 0.270095E+09 | 0.128507E+09 |
May | 0.224560E+09 | 65221588.97 | 0.159338E+09 | 0.262345E+09 | 91363599.77 |
June | 0.211161E+09 | 44746050.03 | 0.166415E+09 | 0.266581E+09 | 62782609.30 |
July | 0.222746E+09 | 54045571.25 | 0.168701E+09 | 0.308706E+09 | 45282230.87 |
August | 0.250070E+09 | 81078819.00 | 0.168991E+09 | 0.340007E+09 | 59684020.74 |
September | 0.281377E+09 | 0.137052E+09 | 0.144326E+09 | 0.354410E+09 | 91189700.22 |
October | 0.278211E+09 | 0.158919E+09 | 0.119291E+09 | 0.311653E+09 | 0.132778E+09 |
November | 0.192821E+09 | 0.108854E+09 | 83967293.25 | 0.191324E+09 | 0.162324E+09 |
December | 0.185928E+09 | 96225999.83 | 89701650.75 | 0.148880E+09 | 0.243872E+09 |
Annual Sum or Average | 0.285672E+10 | 0.125985E+10 | 0.159687E+10 | 0.315413E+10 | 0.165748E+10 |
Minimum of Months | 0.185928E+09 | 44746050.03 | 83967293.25 | 0.148880E+09 | 45282230.87 |
Maximum of Months | 0.309861E+09 | 0.174109E+09 | 0.168991E+09 | 0.354410E+09 | 0.248084E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222349E+09 | 0.129792E+09 | 92557189.18 | 0.187950E+09 | 0.248084E+09 |
February | 0.229299E+09 | 0.110566E+09 | 0.118733E+09 | 0.192405E+09 | 0.217437E+09 |
March | 0.309861E+09 | 0.174109E+09 | 0.135752E+09 | 0.319770E+09 | 0.174173E+09 |
April | 0.248336E+09 | 99235703.68 | 0.149100E+09 | 0.270095E+09 | 0.128507E+09 |
May | 0.224560E+09 | 65221588.97 | 0.159338E+09 | 0.262345E+09 | 91363599.77 |
June | 0.211161E+09 | 44746050.03 | 0.166415E+09 | 0.266581E+09 | 62782609.30 |
July | 0.222746E+09 | 54045571.25 | 0.168701E+09 | 0.308706E+09 | 45282230.87 |
August | 0.250070E+09 | 81078819.00 | 0.168991E+09 | 0.340007E+09 | 59684020.74 |
September | 0.281377E+09 | 0.137052E+09 | 0.144326E+09 | 0.354410E+09 | 91189700.22 |
October | 0.278211E+09 | 0.158919E+09 | 0.119291E+09 | 0.311653E+09 | 0.132778E+09 |
November | 0.192821E+09 | 0.108854E+09 | 83967293.25 | 0.191324E+09 | 0.162324E+09 |
December | 0.185928E+09 | 96225999.83 | 89701650.75 | 0.148880E+09 | 0.243872E+09 |
Annual Sum or Average | 0.285672E+10 | 0.125985E+10 | 0.159687E+10 | 0.315413E+10 | 0.165748E+10 |
Minimum of Months | 0.185928E+09 | 44746050.03 | 83967293.25 | 0.148880E+09 | 45282230.87 |
Maximum of Months | 0.309861E+09 | 0.174109E+09 | 0.168991E+09 | 0.354410E+09 | 0.248084E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.265837E+09 | 0.155177E+09 | 0.110660E+09 | 0.226360E+09 | 0.292019E+09 |
February | 0.274146E+09 | 0.132191E+09 | 0.141955E+09 | 0.232212E+09 | 0.255659E+09 |
March | 0.370465E+09 | 0.208162E+09 | 0.162303E+09 | 0.384226E+09 | 0.205468E+09 |
April | 0.296906E+09 | 0.118645E+09 | 0.178262E+09 | 0.324235E+09 | 0.151626E+09 |
May | 0.268480E+09 | 77977940.64 | 0.190502E+09 | 0.314547E+09 | 0.108074E+09 |
June | 0.252461E+09 | 53497697.44 | 0.198963E+09 | 0.319212E+09 | 74439865.72 |
July | 0.266312E+09 | 64616063.69 | 0.201696E+09 | 0.369176E+09 | 53787003.21 |
August | 0.298979E+09 | 96936603.89 | 0.202043E+09 | 0.406664E+09 | 70826812.97 |
September | 0.336410E+09 | 0.163857E+09 | 0.172553E+09 | 0.424205E+09 | 0.108078E+09 |
October | 0.332625E+09 | 0.190002E+09 | 0.142623E+09 | 0.373747E+09 | 0.156945E+09 |
November | 0.230534E+09 | 0.130144E+09 | 0.100390E+09 | 0.229859E+09 | 0.191377E+09 |
December | 0.222292E+09 | 0.115046E+09 | 0.107246E+09 | 0.179569E+09 | 0.286747E+09 |
Annual Sum or Average | 0.341545E+10 | 0.150625E+10 | 0.190920E+10 | 0.378401E+10 | 0.195505E+10 |
Minimum of Months | 0.222292E+09 | 53497697.44 | 0.100390E+09 | 0.179569E+09 | 53787003.21 |
Maximum of Months | 0.370465E+09 | 0.208162E+09 | 0.202043E+09 | 0.424205E+09 | 0.292019E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222349E+09 | 0.129792E+09 | 92557189.18 | 0.188486E+09 | 0.244925E+09 |
February | 0.229299E+09 | 0.110566E+09 | 0.118733E+09 | 0.192985E+09 | 0.214876E+09 |
March | 0.309861E+09 | 0.174109E+09 | 0.135752E+09 | 0.320828E+09 | 0.170920E+09 |
April | 0.248336E+09 | 99235703.68 | 0.149100E+09 | 0.271472E+09 | 0.125272E+09 |
May | 0.224560E+09 | 65221588.97 | 0.159338E+09 | 0.264527E+09 | 88066148.04 |
June | 0.211161E+09 | 44746050.03 | 0.166415E+09 | 0.267587E+09 | 61430369.00 |
July | 0.222746E+09 | 54045571.25 | 0.168701E+09 | 0.309181E+09 | 44571784.14 |
August | 0.250070E+09 | 81078819.00 | 0.168991E+09 | 0.340416E+09 | 58929256.64 |
September | 0.281377E+09 | 0.137052E+09 | 0.144326E+09 | 0.355103E+09 | 89737562.41 |
October | 0.278211E+09 | 0.158919E+09 | 0.119291E+09 | 0.312813E+09 | 0.130156E+09 |
November | 0.192821E+09 | 0.108854E+09 | 83967293.25 | 0.192147E+09 | 0.159400E+09 |
December | 0.185928E+09 | 96225999.83 | 89701650.75 | 0.149363E+09 | 0.240732E+09 |
Annual Sum or Average | 0.285672E+10 | 0.125985E+10 | 0.159687E+10 | 0.316491E+10 | 0.162902E+10 |
Minimum of Months | 0.185928E+09 | 44746050.03 | 83967293.25 | 0.149363E+09 | 44571784.14 |
Maximum of Months | 0.309861E+09 | 0.174109E+09 | 0.168991E+09 | 0.355103E+09 | 0.244925E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222349E+09 | 0.129792E+09 | 92557189.18 | 0.188486E+09 | 0.244925E+09 |
February | 0.229299E+09 | 0.110566E+09 | 0.118733E+09 | 0.192985E+09 | 0.214876E+09 |
March | 0.309861E+09 | 0.174109E+09 | 0.135752E+09 | 0.320828E+09 | 0.170920E+09 |
April | 0.248336E+09 | 99235703.68 | 0.149100E+09 | 0.271472E+09 | 0.125272E+09 |
May | 0.224560E+09 | 65221588.97 | 0.159338E+09 | 0.264527E+09 | 88066148.04 |
June | 0.211161E+09 | 44746050.03 | 0.166415E+09 | 0.267587E+09 | 61430369.00 |
July | 0.222746E+09 | 54045571.25 | 0.168701E+09 | 0.309181E+09 | 44571784.14 |
August | 0.250070E+09 | 81078819.00 | 0.168991E+09 | 0.340416E+09 | 58929256.64 |
September | 0.281377E+09 | 0.137052E+09 | 0.144326E+09 | 0.355103E+09 | 89737562.41 |
October | 0.278211E+09 | 0.158919E+09 | 0.119291E+09 | 0.312813E+09 | 0.130156E+09 |
November | 0.192821E+09 | 0.108854E+09 | 83967293.25 | 0.192147E+09 | 0.159400E+09 |
December | 0.185928E+09 | 96225999.83 | 89701650.75 | 0.149363E+09 | 0.240732E+09 |
Annual Sum or Average | 0.285672E+10 | 0.125985E+10 | 0.159687E+10 | 0.316491E+10 | 0.162902E+10 |
Minimum of Months | 0.185928E+09 | 44746050.03 | 83967293.25 | 0.149363E+09 | 44571784.14 |
Maximum of Months | 0.309861E+09 | 0.174109E+09 | 0.168991E+09 | 0.355103E+09 | 0.244925E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.265837E+09 | 0.155177E+09 | 0.110660E+09 | 0.227015E+09 | 0.288289E+09 |
February | 0.274146E+09 | 0.132191E+09 | 0.141955E+09 | 0.232919E+09 | 0.252639E+09 |
March | 0.370465E+09 | 0.208162E+09 | 0.162303E+09 | 0.385501E+09 | 0.201629E+09 |
April | 0.296906E+09 | 0.118645E+09 | 0.178262E+09 | 0.325886E+09 | 0.147814E+09 |
May | 0.268480E+09 | 77977940.64 | 0.190502E+09 | 0.317145E+09 | 0.104198E+09 |
June | 0.252461E+09 | 53497697.44 | 0.198963E+09 | 0.320411E+09 | 72849337.66 |
July | 0.266312E+09 | 64616063.69 | 0.201696E+09 | 0.369741E+09 | 52953900.40 |
August | 0.298979E+09 | 96936603.89 | 0.202043E+09 | 0.407153E+09 | 69940458.43 |
September | 0.336410E+09 | 0.163857E+09 | 0.172553E+09 | 0.425032E+09 | 0.106367E+09 |
October | 0.332625E+09 | 0.190002E+09 | 0.142623E+09 | 0.375132E+09 | 0.153857E+09 |
November | 0.230534E+09 | 0.130144E+09 | 0.100390E+09 | 0.230852E+09 | 0.187929E+09 |
December | 0.222292E+09 | 0.115046E+09 | 0.107246E+09 | 0.180156E+09 | 0.283036E+09 |
Annual Sum or Average | 0.341545E+10 | 0.150625E+10 | 0.190920E+10 | 0.379695E+10 | 0.192150E+10 |
Minimum of Months | 0.222292E+09 | 53497697.44 | 0.100390E+09 | 0.180156E+09 | 52953900.40 |
Maximum of Months | 0.370465E+09 | 0.208162E+09 | 0.202043E+09 | 0.425032E+09 | 0.288289E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222349E+09 | 0.129792E+09 | 92557189.18 | 0.190857E+09 | 0.231164E+09 |
February | 0.229299E+09 | 0.110566E+09 | 0.118733E+09 | 0.195572E+09 | 0.203144E+09 |
March | 0.309861E+09 | 0.174109E+09 | 0.135752E+09 | 0.324482E+09 | 0.157701E+09 |
April | 0.248336E+09 | 99235703.68 | 0.149100E+09 | 0.275159E+09 | 0.113392E+09 |
May | 0.224560E+09 | 65221588.97 | 0.159338E+09 | 0.269447E+09 | 78221513.92 |
June | 0.211161E+09 | 44746050.03 | 0.166415E+09 | 0.270066E+09 | 56347425.23 |
July | 0.222746E+09 | 54045571.25 | 0.168701E+09 | 0.309939E+09 | 41797638.75 |
August | 0.250070E+09 | 81078819.00 | 0.168991E+09 | 0.341078E+09 | 55911297.64 |
September | 0.281377E+09 | 0.137052E+09 | 0.144326E+09 | 0.356720E+09 | 84438763.32 |
October | 0.278211E+09 | 0.158919E+09 | 0.119291E+09 | 0.315566E+09 | 0.121603E+09 |
November | 0.192821E+09 | 0.108854E+09 | 83967293.25 | 0.194589E+09 | 0.148703E+09 |
December | 0.185928E+09 | 96225999.83 | 89701650.75 | 0.151426E+09 | 0.226959E+09 |
Annual Sum or Average | 0.285672E+10 | 0.125985E+10 | 0.159687E+10 | 0.319490E+10 | 0.151938E+10 |
Minimum of Months | 0.185928E+09 | 44746050.03 | 83967293.25 | 0.151426E+09 | 41797638.75 |
Maximum of Months | 0.309861E+09 | 0.174109E+09 | 0.168991E+09 | 0.356720E+09 | 0.231164E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222349E+09 | 0.129792E+09 | 92557189.18 | 0.190857E+09 | 0.231164E+09 |
February | 0.229299E+09 | 0.110566E+09 | 0.118733E+09 | 0.195572E+09 | 0.203144E+09 |
March | 0.309861E+09 | 0.174109E+09 | 0.135752E+09 | 0.324482E+09 | 0.157701E+09 |
April | 0.248336E+09 | 99235703.68 | 0.149100E+09 | 0.275159E+09 | 0.113392E+09 |
May | 0.224560E+09 | 65221588.97 | 0.159338E+09 | 0.269447E+09 | 78221513.92 |
June | 0.211161E+09 | 44746050.03 | 0.166415E+09 | 0.270066E+09 | 56347425.23 |
July | 0.222746E+09 | 54045571.25 | 0.168701E+09 | 0.309939E+09 | 41797638.75 |
August | 0.250070E+09 | 81078819.00 | 0.168991E+09 | 0.341078E+09 | 55911297.64 |
September | 0.281377E+09 | 0.137052E+09 | 0.144326E+09 | 0.356720E+09 | 84438763.32 |
October | 0.278211E+09 | 0.158919E+09 | 0.119291E+09 | 0.315566E+09 | 0.121603E+09 |
November | 0.192821E+09 | 0.108854E+09 | 83967293.25 | 0.194589E+09 | 0.148703E+09 |
December | 0.185928E+09 | 96225999.83 | 89701650.75 | 0.151426E+09 | 0.226959E+09 |
Annual Sum or Average | 0.285672E+10 | 0.125985E+10 | 0.159687E+10 | 0.319490E+10 | 0.151938E+10 |
Minimum of Months | 0.185928E+09 | 44746050.03 | 83967293.25 | 0.151426E+09 | 41797638.75 |
Maximum of Months | 0.309861E+09 | 0.174109E+09 | 0.168991E+09 | 0.356720E+09 | 0.231164E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.265837E+09 | 0.155177E+09 | 0.110660E+09 | 0.229901E+09 | 0.272005E+09 |
February | 0.274146E+09 | 0.132191E+09 | 0.141955E+09 | 0.236074E+09 | 0.238777E+09 |
March | 0.370465E+09 | 0.208162E+09 | 0.162303E+09 | 0.389926E+09 | 0.186040E+09 |
April | 0.296906E+09 | 0.118645E+09 | 0.178262E+09 | 0.330327E+09 | 0.133835E+09 |
May | 0.268480E+09 | 77977940.64 | 0.190502E+09 | 0.323014E+09 | 92622438.41 |
June | 0.252461E+09 | 53497697.44 | 0.198963E+09 | 0.323361E+09 | 66873649.65 |
July | 0.266312E+09 | 64616063.69 | 0.201696E+09 | 0.370637E+09 | 49692519.23 |
August | 0.298979E+09 | 96936603.89 | 0.202043E+09 | 0.407936E+09 | 66391791.83 |
September | 0.336410E+09 | 0.163857E+09 | 0.172553E+09 | 0.426958E+09 | 0.100125E+09 |
October | 0.332625E+09 | 0.190002E+09 | 0.142623E+09 | 0.378431E+09 | 0.143795E+09 |
November | 0.230534E+09 | 0.130144E+09 | 0.100390E+09 | 0.233799E+09 | 0.175333E+09 |
December | 0.222292E+09 | 0.115046E+09 | 0.107246E+09 | 0.182685E+09 | 0.266784E+09 |
Annual Sum or Average | 0.341545E+10 | 0.150625E+10 | 0.190920E+10 | 0.383305E+10 | 0.179227E+10 |
Minimum of Months | 0.222292E+09 | 53497697.44 | 0.100390E+09 | 0.182685E+09 | 49692519.23 |
Maximum of Months | 0.370465E+09 | 0.208162E+09 | 0.202043E+09 | 0.426958E+09 | 0.272005E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 452.41 | 600.73 | 531.66 | 310.34 | 221.31 | 0.00 | 0.00 |
February | 513.75 | 581.36 | 607.02 | 292.70 | 314.32 | 0.00 | 0.00 |
March | 768.19 | 420.31 | 740.91 | 416.31 | 324.60 | 0.00 | 0.00 |
April | 668.87 | 321.52 | 613.59 | 245.19 | 368.40 | 0.00 | 0.00 |
May | 626.50 | 223.10 | 536.94 | 155.95 | 380.99 | 0.00 | 0.00 |
June | 661.58 | 151.85 | 521.74 | 110.56 | 411.18 | 0.00 | 0.00 |
July | 741.97 | 103.13 | 532.61 | 129.23 | 403.38 | 0.00 | 0.00 |
August | 815.73 | 137.87 | 597.94 | 193.87 | 404.07 | 0.00 | 0.00 |
September | 877.81 | 222.26 | 695.23 | 338.63 | 356.60 | 0.00 | 0.00 |
October | 744.64 | 322.65 | 665.23 | 379.99 | 285.24 | 0.00 | 0.00 |
November | 472.73 | 406.91 | 476.42 | 268.96 | 207.47 | 0.00 | 0.00 |
December | 358.41 | 589.35 | 444.57 | 230.09 | 214.49 | 0.00 | 0.00 |
Annual Sum or Average | 642.62 | 338.81 | 580.14 | 255.85 | 324.29 | 0.00 | 0.00 |
Minimum of Months | 358.41 | 103.13 | 444.57 | 110.56 | 207.47 | 0.00 | 0.00 |
Maximum of Months | 877.81 | 600.73 | 740.91 | 416.31 | 411.18 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 222.55 | 314.27 | 265.83 | 155.17 | 110.66 | 0.00 | 0.00 |
February | 252.13 | 304.47 | 303.51 | 146.35 | 157.16 | 0.00 | 0.00 |
March | 378.59 | 223.05 | 370.45 | 208.16 | 162.30 | 0.00 | 0.00 |
April | 328.63 | 173.99 | 306.79 | 122.60 | 184.20 | 0.00 | 0.00 |
May | 307.37 | 120.50 | 268.47 | 77.98 | 190.50 | 0.00 | 0.00 |
June | 328.42 | 78.19 | 260.87 | 55.28 | 205.59 | 0.00 | 0.00 |
July | 369.95 | 52.42 | 266.30 | 64.61 | 201.69 | 0.00 | 0.00 |
August | 406.87 | 69.89 | 298.97 | 96.93 | 202.04 | 0.00 | 0.00 |
September | 436.78 | 114.17 | 347.61 | 169.31 | 178.30 | 0.00 | 0.00 |
October | 368.02 | 171.76 | 332.61 | 190.00 | 142.62 | 0.00 | 0.00 |
November | 232.81 | 216.44 | 238.21 | 134.48 | 103.73 | 0.00 | 0.00 |
December | 176.01 | 309.10 | 222.29 | 115.04 | 107.24 | 0.00 | 0.00 |
Annual Sum or Average | 317.72 | 178.36 | 290.07 | 127.92 | 162.15 | 0.00 | 0.00 |
Minimum of Months | 176.01 | 52.42 | 222.29 | 55.28 | 103.73 | 0.00 | 0.00 |
Maximum of Months | 436.78 | 314.27 | 370.45 | 208.16 | 205.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 222.29 | 305.63 | 265.28 | 154.85 | 110.43 | 0.00 | 0.00 |
February | 251.83 | 295.93 | 302.89 | 146.05 | 156.84 | 0.00 | 0.00 |
March | 378.30 | 216.48 | 369.69 | 207.73 | 161.96 | 0.00 | 0.00 |
April | 329.12 | 167.66 | 306.16 | 122.34 | 183.82 | 0.00 | 0.00 |
May | 308.07 | 118.07 | 267.92 | 77.82 | 190.11 | 0.00 | 0.00 |
June | 327.17 | 81.20 | 260.33 | 55.17 | 205.17 | 0.00 | 0.00 |
July | 367.60 | 57.06 | 265.76 | 64.48 | 201.28 | 0.00 | 0.00 |
August | 405.16 | 74.52 | 298.36 | 96.73 | 201.62 | 0.00 | 0.00 |
September | 435.93 | 116.58 | 346.90 | 168.97 | 177.93 | 0.00 | 0.00 |
October | 368.70 | 166.52 | 331.93 | 189.61 | 142.33 | 0.00 | 0.00 |
November | 233.35 | 209.20 | 237.72 | 134.20 | 103.52 | 0.00 | 0.00 |
December | 175.99 | 300.70 | 221.83 | 114.81 | 107.02 | 0.00 | 0.00 |
Annual Sum or Average | 317.34 | 175.16 | 289.48 | 127.66 | 161.81 | 0.00 | 0.00 |
Minimum of Months | 175.99 | 57.06 | 221.83 | 55.17 | 103.52 | 0.00 | 0.00 |
Maximum of Months | 435.93 | 305.63 | 369.69 | 207.73 | 205.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 222.68 | 302.48 | 265.28 | 154.85 | 110.43 | 0.00 | 0.00 |
February | 252.30 | 292.99 | 302.89 | 146.05 | 156.84 | 0.00 | 0.00 |
March | 378.95 | 213.92 | 369.69 | 207.73 | 161.96 | 0.00 | 0.00 |
April | 330.02 | 164.90 | 306.16 | 122.34 | 183.82 | 0.00 | 0.00 |
May | 309.13 | 115.89 | 267.92 | 77.82 | 190.11 | 0.00 | 0.00 |
June | 327.31 | 80.95 | 260.33 | 55.17 | 205.17 | 0.00 | 0.00 |
July | 367.53 | 57.26 | 265.76 | 64.48 | 201.28 | 0.00 | 0.00 |
August | 405.12 | 74.67 | 298.36 | 96.73 | 201.62 | 0.00 | 0.00 |
September | 436.11 | 116.04 | 346.90 | 168.97 | 177.93 | 0.00 | 0.00 |
October | 369.57 | 163.96 | 331.93 | 189.61 | 142.33 | 0.00 | 0.00 |
November | 233.99 | 206.28 | 237.72 | 134.20 | 103.52 | 0.00 | 0.00 |
December | 176.36 | 297.59 | 221.83 | 114.81 | 107.02 | 0.00 | 0.00 |
Annual Sum or Average | 317.80 | 173.28 | 289.48 | 127.66 | 161.81 | 0.00 | 0.00 |
Minimum of Months | 176.36 | 57.26 | 221.83 | 55.17 | 103.52 | 0.00 | 0.00 |
Maximum of Months | 436.11 | 302.48 | 369.69 | 207.73 | 205.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 223.14 | 300.18 | 265.28 | 154.85 | 110.43 | 0.00 | 0.00 |
February | 252.86 | 290.87 | 302.89 | 146.05 | 156.84 | 0.00 | 0.00 |
March | 379.69 | 211.93 | 369.69 | 207.73 | 161.96 | 0.00 | 0.00 |
April | 330.94 | 162.82 | 306.16 | 122.34 | 183.82 | 0.00 | 0.00 |
May | 310.38 | 113.86 | 267.92 | 77.82 | 190.11 | 0.00 | 0.00 |
June | 327.78 | 80.15 | 260.33 | 55.17 | 205.17 | 0.00 | 0.00 |
July | 367.83 | 56.64 | 265.76 | 64.48 | 201.28 | 0.00 | 0.00 |
August | 405.38 | 74.00 | 298.36 | 96.73 | 201.62 | 0.00 | 0.00 |
September | 436.49 | 115.08 | 346.90 | 168.97 | 177.93 | 0.00 | 0.00 |
October | 370.41 | 162.06 | 331.93 | 189.61 | 142.33 | 0.00 | 0.00 |
November | 234.60 | 204.19 | 237.72 | 134.20 | 103.52 | 0.00 | 0.00 |
December | 176.77 | 295.24 | 221.83 | 114.81 | 107.02 | 0.00 | 0.00 |
Annual Sum or Average | 318.40 | 171.62 | 289.48 | 127.66 | 161.81 | 0.00 | 0.00 |
Minimum of Months | 176.77 | 56.64 | 221.83 | 55.17 | 103.52 | 0.00 | 0.00 |
Maximum of Months | 436.49 | 300.18 | 369.69 | 207.73 | 205.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 451.83 | 584.99 | 530.57 | 309.71 | 220.86 | 0.00 | 0.00 |
February | 513.08 | 567.07 | 605.77 | 292.10 | 313.67 | 0.00 | 0.00 |
March | 766.52 | 413.43 | 739.39 | 415.46 | 323.93 | 0.00 | 0.00 |
April | 667.56 | 316.93 | 612.33 | 244.69 | 367.64 | 0.00 | 0.00 |
May | 625.39 | 220.61 | 535.84 | 155.63 | 380.21 | 0.00 | 0.00 |
June | 657.29 | 156.28 | 520.67 | 110.33 | 410.33 | 0.00 | 0.00 |
July | 736.16 | 109.72 | 531.52 | 128.96 | 402.55 | 0.00 | 0.00 |
August | 811.32 | 143.99 | 596.71 | 193.47 | 403.24 | 0.00 | 0.00 |
September | 874.63 | 225.98 | 693.80 | 337.93 | 355.87 | 0.00 | 0.00 |
October | 745.02 | 317.37 | 663.86 | 379.21 | 284.65 | 0.00 | 0.00 |
November | 473.49 | 398.36 | 475.45 | 268.40 | 207.04 | 0.00 | 0.00 |
December | 358.34 | 574.78 | 443.66 | 229.61 | 214.05 | 0.00 | 0.00 |
Annual Sum or Average | 640.79 | 334.57 | 578.95 | 255.32 | 323.63 | 0.00 | 0.00 |
Minimum of Months | 358.34 | 109.72 | 443.66 | 110.33 | 207.04 | 0.00 | 0.00 |
Maximum of Months | 874.63 | 584.99 | 739.39 | 415.46 | 410.33 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 224.72 | 294.93 | 265.28 | 154.85 | 110.43 | 0.00 | 0.00 |
February | 254.89 | 286.00 | 302.89 | 146.05 | 156.84 | 0.00 | 0.00 |
March | 381.88 | 207.66 | 369.69 | 207.73 | 161.96 | 0.00 | 0.00 |
April | 332.93 | 158.78 | 306.16 | 122.34 | 183.82 | 0.00 | 0.00 |
May | 312.35 | 109.95 | 267.92 | 77.82 | 190.11 | 0.00 | 0.00 |
June | 328.40 | 77.70 | 260.33 | 55.17 | 205.17 | 0.00 | 0.00 |
July | 368.07 | 54.22 | 265.76 | 64.48 | 201.28 | 0.00 | 0.00 |
August | 405.48 | 71.36 | 298.36 | 96.73 | 201.62 | 0.00 | 0.00 |
September | 436.81 | 112.63 | 346.90 | 168.97 | 177.93 | 0.00 | 0.00 |
October | 371.74 | 158.77 | 331.93 | 189.61 | 142.33 | 0.00 | 0.00 |
November | 235.99 | 200.06 | 237.72 | 134.20 | 103.52 | 0.00 | 0.00 |
December | 178.08 | 289.87 | 221.83 | 114.81 | 107.02 | 0.00 | 0.00 |
Annual Sum or Average | 319.65 | 167.87 | 289.48 | 127.66 | 161.81 | 0.00 | 0.00 |
Minimum of Months | 178.08 | 54.22 | 221.83 | 55.17 | 103.52 | 0.00 | 0.00 |
Maximum of Months | 436.81 | 294.93 | 369.69 | 207.73 | 205.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 224.86 | 294.27 | 265.28 | 154.85 | 110.43 | 0.00 | 0.00 |
February | 255.05 | 285.44 | 302.89 | 146.05 | 156.84 | 0.00 | 0.00 |
March | 382.23 | 206.77 | 369.69 | 207.73 | 161.96 | 0.00 | 0.00 |
April | 333.50 | 157.65 | 306.16 | 122.34 | 183.82 | 0.00 | 0.00 |
May | 313.33 | 108.57 | 267.92 | 77.82 | 190.11 | 0.00 | 0.00 |
June | 328.85 | 77.16 | 260.33 | 55.17 | 205.17 | 0.00 | 0.00 |
July | 368.35 | 53.89 | 265.76 | 64.48 | 201.28 | 0.00 | 0.00 |
August | 405.72 | 71.01 | 298.36 | 96.73 | 201.62 | 0.00 | 0.00 |
September | 437.12 | 112.06 | 346.90 | 168.97 | 177.93 | 0.00 | 0.00 |
October | 372.26 | 157.74 | 331.93 | 189.61 | 142.33 | 0.00 | 0.00 |
November | 236.31 | 199.08 | 237.72 | 134.20 | 103.52 | 0.00 | 0.00 |
December | 178.21 | 289.16 | 221.83 | 114.81 | 107.02 | 0.00 | 0.00 |
Annual Sum or Average | 320.02 | 167.11 | 289.48 | 127.66 | 161.81 | 0.00 | 0.00 |
Minimum of Months | 178.21 | 53.89 | 221.83 | 55.17 | 103.52 | 0.00 | 0.00 |
Maximum of Months | 437.12 | 294.27 | 369.69 | 207.73 | 205.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 225.50 | 290.52 | 265.28 | 154.85 | 110.43 | 0.00 | 0.00 |
February | 255.82 | 282.07 | 302.89 | 146.05 | 156.84 | 0.00 | 0.00 |
March | 383.50 | 202.91 | 369.69 | 207.73 | 161.96 | 0.00 | 0.00 |
April | 335.20 | 153.69 | 306.16 | 122.34 | 183.82 | 0.00 | 0.00 |
May | 315.93 | 104.66 | 267.92 | 77.82 | 190.11 | 0.00 | 0.00 |
June | 330.09 | 75.51 | 260.33 | 55.17 | 205.17 | 0.00 | 0.00 |
July | 368.92 | 53.05 | 265.76 | 64.48 | 201.28 | 0.00 | 0.00 |
August | 406.21 | 70.12 | 298.36 | 96.73 | 201.62 | 0.00 | 0.00 |
September | 437.98 | 110.28 | 346.90 | 168.97 | 177.93 | 0.00 | 0.00 |
October | 373.64 | 154.63 | 331.93 | 189.61 | 142.33 | 0.00 | 0.00 |
November | 237.32 | 195.50 | 237.72 | 134.20 | 103.52 | 0.00 | 0.00 |
December | 178.79 | 285.43 | 221.83 | 114.81 | 107.02 | 0.00 | 0.00 |
Annual Sum or Average | 321.12 | 164.24 | 289.48 | 127.66 | 161.81 | 0.00 | 0.00 |
Minimum of Months | 178.79 | 53.05 | 221.83 | 55.17 | 103.52 | 0.00 | 0.00 |
Maximum of Months | 437.98 | 290.52 | 369.69 | 207.73 | 205.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 228.35 | 274.17 | 265.28 | 154.85 | 110.43 | 0.00 | 0.00 |
February | 259.27 | 266.64 | 302.89 | 146.05 | 156.84 | 0.00 | 0.00 |
March | 387.88 | 187.22 | 369.69 | 207.73 | 161.96 | 0.00 | 0.00 |
April | 339.75 | 139.13 | 306.16 | 122.34 | 183.82 | 0.00 | 0.00 |
May | 321.80 | 92.99 | 267.92 | 77.82 | 190.11 | 0.00 | 0.00 |
June | 333.14 | 69.28 | 260.33 | 55.17 | 205.17 | 0.00 | 0.00 |
July | 369.82 | 49.76 | 265.76 | 64.48 | 201.28 | 0.00 | 0.00 |
August | 406.99 | 66.54 | 298.36 | 96.73 | 201.62 | 0.00 | 0.00 |
September | 439.97 | 103.78 | 346.90 | 168.97 | 177.93 | 0.00 | 0.00 |
October | 376.93 | 144.49 | 331.93 | 189.61 | 142.33 | 0.00 | 0.00 |
November | 240.34 | 182.38 | 237.72 | 134.20 | 103.52 | 0.00 | 0.00 |
December | 181.28 | 269.08 | 221.83 | 114.81 | 107.02 | 0.00 | 0.00 |
Annual Sum or Average | 324.16 | 153.19 | 289.48 | 127.66 | 161.81 | 0.00 | 0.00 |
Minimum of Months | 181.28 | 49.76 | 221.83 | 55.17 | 103.52 | 0.00 | 0.00 |
Maximum of Months | 439.97 | 274.17 | 369.69 | 207.73 | 205.17 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.121174E+10 | 0.160900E+10 | 0.142399E+10 | 0.831225E+09 | 0.592765E+09 | 0.00 | 0.00 |
February | 0.124288E+10 | 0.140643E+10 | 0.146850E+10 | 0.708098E+09 | 0.760402E+09 | 0.00 | 0.00 |
March | 0.205751E+10 | 0.112575E+10 | 0.198444E+10 | 0.111505E+10 | 0.869398E+09 | 0.00 | 0.00 |
April | 0.173370E+10 | 0.833377E+09 | 0.159042E+10 | 0.635536E+09 | 0.954882E+09 | 0.00 | 0.00 |
May | 0.167802E+10 | 0.597545E+09 | 0.143815E+10 | 0.417699E+09 | 0.102045E+10 | 0.00 | 0.00 |
June | 0.171481E+10 | 0.393600E+09 | 0.135234E+10 | 0.286567E+09 | 0.106577E+10 | 0.00 | 0.00 |
July | 0.198730E+10 | 0.276223E+09 | 0.142654E+10 | 0.346124E+09 | 0.108041E+10 | 0.00 | 0.00 |
August | 0.218485E+10 | 0.369275E+09 | 0.160152E+10 | 0.519254E+09 | 0.108227E+10 | 0.00 | 0.00 |
September | 0.227528E+10 | 0.576091E+09 | 0.180203E+10 | 0.877721E+09 | 0.924306E+09 | 0.00 | 0.00 |
October | 0.199444E+10 | 0.864180E+09 | 0.178175E+10 | 0.101777E+10 | 0.763979E+09 | 0.00 | 0.00 |
November | 0.122531E+10 | 0.105472E+10 | 0.123489E+10 | 0.697136E+09 | 0.537752E+09 | 0.00 | 0.00 |
December | 0.959965E+09 | 0.157852E+10 | 0.119074E+10 | 0.616261E+09 | 0.574477E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.202658E+11 | 0.106847E+11 | 0.182953E+11 | 0.806844E+10 | 0.102269E+11 | 0.00 | 0.00 |
Minimum of Months | 0.959965E+09 | 0.276223E+09 | 0.119074E+10 | 0.286567E+09 | 0.537752E+09 | 0.00 | 0.00 |
Maximum of Months | 0.227528E+10 | 0.160900E+10 | 0.198444E+10 | 0.111505E+10 | 0.108227E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.596081E+09 | 0.841743E+09 | 0.711995E+09 | 0.415612E+09 | 0.296382E+09 | 0.00 | 0.00 |
February | 0.609955E+09 | 0.736579E+09 | 0.734250E+09 | 0.354049E+09 | 0.380201E+09 | 0.00 | 0.00 |
March | 0.101402E+10 | 0.597414E+09 | 0.992222E+09 | 0.557523E+09 | 0.434699E+09 | 0.00 | 0.00 |
April | 0.851821E+09 | 0.450995E+09 | 0.795209E+09 | 0.317768E+09 | 0.477441E+09 | 0.00 | 0.00 |
May | 0.823270E+09 | 0.322757E+09 | 0.719075E+09 | 0.208850E+09 | 0.510225E+09 | 0.00 | 0.00 |
June | 0.851277E+09 | 0.202681E+09 | 0.676170E+09 | 0.143284E+09 | 0.532886E+09 | 0.00 | 0.00 |
July | 0.990871E+09 | 0.140389E+09 | 0.713268E+09 | 0.173062E+09 | 0.540206E+09 | 0.00 | 0.00 |
August | 0.108975E+10 | 0.187194E+09 | 0.800761E+09 | 0.259627E+09 | 0.541134E+09 | 0.00 | 0.00 |
September | 0.113214E+10 | 0.295940E+09 | 0.901013E+09 | 0.438860E+09 | 0.462153E+09 | 0.00 | 0.00 |
October | 0.985695E+09 | 0.460041E+09 | 0.890874E+09 | 0.508884E+09 | 0.381990E+09 | 0.00 | 0.00 |
November | 0.603451E+09 | 0.561010E+09 | 0.617444E+09 | 0.348568E+09 | 0.268876E+09 | 0.00 | 0.00 |
December | 0.471438E+09 | 0.827894E+09 | 0.595369E+09 | 0.308130E+09 | 0.287238E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.100198E+11 | 0.562463E+10 | 0.914765E+10 | 0.403422E+10 | 0.511343E+10 | 0.00 | 0.00 |
Minimum of Months | 0.471438E+09 | 0.140389E+09 | 0.595369E+09 | 0.143284E+09 | 0.268876E+09 | 0.00 | 0.00 |
Maximum of Months | 0.113214E+10 | 0.841743E+09 | 0.992222E+09 | 0.557523E+09 | 0.541134E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.595371E+09 | 0.818594E+09 | 0.710534E+09 | 0.414760E+09 | 0.295774E+09 | 0.00 | 0.00 |
February | 0.609228E+09 | 0.715906E+09 | 0.732744E+09 | 0.353323E+09 | 0.379421E+09 | 0.00 | 0.00 |
March | 0.101324E+10 | 0.579822E+09 | 0.990187E+09 | 0.556380E+09 | 0.433807E+09 | 0.00 | 0.00 |
April | 0.853089E+09 | 0.434567E+09 | 0.793578E+09 | 0.317116E+09 | 0.476462E+09 | 0.00 | 0.00 |
May | 0.825126E+09 | 0.316227E+09 | 0.717599E+09 | 0.208421E+09 | 0.509178E+09 | 0.00 | 0.00 |
June | 0.848027E+09 | 0.210480E+09 | 0.674783E+09 | 0.142990E+09 | 0.531793E+09 | 0.00 | 0.00 |
July | 0.984589E+09 | 0.152823E+09 | 0.711805E+09 | 0.172707E+09 | 0.539098E+09 | 0.00 | 0.00 |
August | 0.108519E+10 | 0.199597E+09 | 0.799118E+09 | 0.259094E+09 | 0.540024E+09 | 0.00 | 0.00 |
September | 0.112994E+10 | 0.302169E+09 | 0.899165E+09 | 0.437960E+09 | 0.461205E+09 | 0.00 | 0.00 |
October | 0.987517E+09 | 0.445999E+09 | 0.889046E+09 | 0.507840E+09 | 0.381206E+09 | 0.00 | 0.00 |
November | 0.604846E+09 | 0.542242E+09 | 0.616177E+09 | 0.347853E+09 | 0.268325E+09 | 0.00 | 0.00 |
December | 0.471384E+09 | 0.805382E+09 | 0.594148E+09 | 0.307498E+09 | 0.286649E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.100075E+11 | 0.552381E+10 | 0.912888E+10 | 0.402594E+10 | 0.510294E+10 | 0.00 | 0.00 |
Minimum of Months | 0.471384E+09 | 0.152823E+09 | 0.594148E+09 | 0.142990E+09 | 0.268325E+09 | 0.00 | 0.00 |
Maximum of Months | 0.112994E+10 | 0.818594E+09 | 0.990187E+09 | 0.556380E+09 | 0.540024E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.596415E+09 | 0.810167E+09 | 0.710534E+09 | 0.414760E+09 | 0.295774E+09 | 0.00 | 0.00 |
February | 0.610359E+09 | 0.708800E+09 | 0.732744E+09 | 0.353323E+09 | 0.379421E+09 | 0.00 | 0.00 |
March | 0.101497E+10 | 0.572964E+09 | 0.990187E+09 | 0.556380E+09 | 0.433807E+09 | 0.00 | 0.00 |
April | 0.855399E+09 | 0.427415E+09 | 0.793578E+09 | 0.317116E+09 | 0.476462E+09 | 0.00 | 0.00 |
May | 0.827985E+09 | 0.310411E+09 | 0.717599E+09 | 0.208421E+09 | 0.509178E+09 | 0.00 | 0.00 |
June | 0.848395E+09 | 0.209814E+09 | 0.674783E+09 | 0.142990E+09 | 0.531793E+09 | 0.00 | 0.00 |
July | 0.984384E+09 | 0.153354E+09 | 0.711805E+09 | 0.172707E+09 | 0.539098E+09 | 0.00 | 0.00 |
August | 0.108506E+10 | 0.199999E+09 | 0.799118E+09 | 0.259094E+09 | 0.540024E+09 | 0.00 | 0.00 |
September | 0.113041E+10 | 0.300771E+09 | 0.899165E+09 | 0.437960E+09 | 0.461205E+09 | 0.00 | 0.00 |
October | 0.989859E+09 | 0.439143E+09 | 0.889046E+09 | 0.507840E+09 | 0.381206E+09 | 0.00 | 0.00 |
November | 0.606506E+09 | 0.534671E+09 | 0.616177E+09 | 0.347853E+09 | 0.268325E+09 | 0.00 | 0.00 |
December | 0.472357E+09 | 0.797068E+09 | 0.594148E+09 | 0.307498E+09 | 0.286649E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.100221E+11 | 0.546458E+10 | 0.912888E+10 | 0.402594E+10 | 0.510294E+10 | 0.00 | 0.00 |
Minimum of Months | 0.472357E+09 | 0.153354E+09 | 0.594148E+09 | 0.142990E+09 | 0.268325E+09 | 0.00 | 0.00 |
Maximum of Months | 0.113041E+10 | 0.810167E+09 | 0.990187E+09 | 0.556380E+09 | 0.540024E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.597656E+09 | 0.803993E+09 | 0.710534E+09 | 0.414760E+09 | 0.295774E+09 | 0.00 | 0.00 |
February | 0.611707E+09 | 0.703662E+09 | 0.732744E+09 | 0.353323E+09 | 0.379421E+09 | 0.00 | 0.00 |
March | 0.101697E+10 | 0.567624E+09 | 0.990187E+09 | 0.556380E+09 | 0.433807E+09 | 0.00 | 0.00 |
April | 0.857804E+09 | 0.422022E+09 | 0.793578E+09 | 0.317116E+09 | 0.476462E+09 | 0.00 | 0.00 |
May | 0.831311E+09 | 0.304954E+09 | 0.717599E+09 | 0.208421E+09 | 0.509178E+09 | 0.00 | 0.00 |
June | 0.849595E+09 | 0.207750E+09 | 0.674783E+09 | 0.142990E+09 | 0.531793E+09 | 0.00 | 0.00 |
July | 0.985184E+09 | 0.151703E+09 | 0.711805E+09 | 0.172707E+09 | 0.539098E+09 | 0.00 | 0.00 |
August | 0.108576E+10 | 0.198200E+09 | 0.799118E+09 | 0.259094E+09 | 0.540024E+09 | 0.00 | 0.00 |
September | 0.113139E+10 | 0.298300E+09 | 0.899165E+09 | 0.437960E+09 | 0.461205E+09 | 0.00 | 0.00 |
October | 0.992116E+09 | 0.434049E+09 | 0.889046E+09 | 0.507840E+09 | 0.381206E+09 | 0.00 | 0.00 |
November | 0.608092E+09 | 0.529257E+09 | 0.616177E+09 | 0.347853E+09 | 0.268325E+09 | 0.00 | 0.00 |
December | 0.473464E+09 | 0.790783E+09 | 0.594148E+09 | 0.307498E+09 | 0.286649E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.100410E+11 | 0.541230E+10 | 0.912888E+10 | 0.402594E+10 | 0.510294E+10 | 0.00 | 0.00 |
Minimum of Months | 0.473464E+09 | 0.151703E+09 | 0.594148E+09 | 0.142990E+09 | 0.268325E+09 | 0.00 | 0.00 |
Maximum of Months | 0.113139E+10 | 0.803993E+09 | 0.990187E+09 | 0.556380E+09 | 0.540024E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.121018E+10 | 0.156684E+10 | 0.142107E+10 | 0.829520E+09 | 0.591549E+09 | 0.00 | 0.00 |
February | 0.124124E+10 | 0.137186E+10 | 0.146549E+10 | 0.706645E+09 | 0.758842E+09 | 0.00 | 0.00 |
March | 0.205306E+10 | 0.110732E+10 | 0.198037E+10 | 0.111276E+10 | 0.867614E+09 | 0.00 | 0.00 |
April | 0.173032E+10 | 0.821491E+09 | 0.158716E+10 | 0.634232E+09 | 0.952924E+09 | 0.00 | 0.00 |
May | 0.167505E+10 | 0.590890E+09 | 0.143520E+10 | 0.416842E+09 | 0.101836E+10 | 0.00 | 0.00 |
June | 0.170370E+10 | 0.405085E+09 | 0.134957E+10 | 0.285980E+09 | 0.106359E+10 | 0.00 | 0.00 |
July | 0.197173E+10 | 0.293883E+09 | 0.142361E+10 | 0.345414E+09 | 0.107820E+10 | 0.00 | 0.00 |
August | 0.217304E+10 | 0.385665E+09 | 0.159824E+10 | 0.518188E+09 | 0.108005E+10 | 0.00 | 0.00 |
September | 0.226704E+10 | 0.585752E+09 | 0.179833E+10 | 0.875920E+09 | 0.922409E+09 | 0.00 | 0.00 |
October | 0.199546E+10 | 0.850050E+09 | 0.177809E+10 | 0.101568E+10 | 0.762412E+09 | 0.00 | 0.00 |
November | 0.122729E+10 | 0.103256E+10 | 0.123235E+10 | 0.695706E+09 | 0.536649E+09 | 0.00 | 0.00 |
December | 0.959777E+09 | 0.153950E+10 | 0.118830E+10 | 0.614997E+09 | 0.573298E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.202079E+11 | 0.105509E+11 | 0.182578E+11 | 0.805188E+10 | 0.102059E+11 | 0.00 | 0.00 |
Minimum of Months | 0.959777E+09 | 0.293883E+09 | 0.118830E+10 | 0.285980E+09 | 0.536649E+09 | 0.00 | 0.00 |
Maximum of Months | 0.226704E+10 | 0.156684E+10 | 0.198037E+10 | 0.111276E+10 | 0.108005E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.601895E+09 | 0.789942E+09 | 0.710534E+09 | 0.414760E+09 | 0.295774E+09 | 0.00 | 0.00 |
February | 0.616636E+09 | 0.691899E+09 | 0.732744E+09 | 0.353323E+09 | 0.379421E+09 | 0.00 | 0.00 |
March | 0.102283E+10 | 0.556207E+09 | 0.990187E+09 | 0.556380E+09 | 0.433807E+09 | 0.00 | 0.00 |
April | 0.862947E+09 | 0.411556E+09 | 0.793578E+09 | 0.317116E+09 | 0.476462E+09 | 0.00 | 0.00 |
May | 0.836598E+09 | 0.294493E+09 | 0.717599E+09 | 0.208421E+09 | 0.509178E+09 | 0.00 | 0.00 |
June | 0.851204E+09 | 0.201387E+09 | 0.674783E+09 | 0.142990E+09 | 0.531793E+09 | 0.00 | 0.00 |
July | 0.985834E+09 | 0.145231E+09 | 0.711805E+09 | 0.172707E+09 | 0.539098E+09 | 0.00 | 0.00 |
August | 0.108604E+10 | 0.191134E+09 | 0.799118E+09 | 0.259094E+09 | 0.540024E+09 | 0.00 | 0.00 |
September | 0.113222E+10 | 0.291934E+09 | 0.899165E+09 | 0.437960E+09 | 0.461205E+09 | 0.00 | 0.00 |
October | 0.995669E+09 | 0.425243E+09 | 0.889046E+09 | 0.507840E+09 | 0.381206E+09 | 0.00 | 0.00 |
November | 0.611686E+09 | 0.518555E+09 | 0.616177E+09 | 0.347853E+09 | 0.268325E+09 | 0.00 | 0.00 |
December | 0.476978E+09 | 0.776378E+09 | 0.594148E+09 | 0.307498E+09 | 0.286649E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.100805E+11 | 0.529396E+10 | 0.912888E+10 | 0.402594E+10 | 0.510294E+10 | 0.00 | 0.00 |
Minimum of Months | 0.476978E+09 | 0.145231E+09 | 0.594148E+09 | 0.142990E+09 | 0.268325E+09 | 0.00 | 0.00 |
Maximum of Months | 0.113222E+10 | 0.789942E+09 | 0.990187E+09 | 0.556380E+09 | 0.540024E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.602255E+09 | 0.788181E+09 | 0.710534E+09 | 0.414760E+09 | 0.295774E+09 | 0.00 | 0.00 |
February | 0.617020E+09 | 0.690529E+09 | 0.732744E+09 | 0.353323E+09 | 0.379421E+09 | 0.00 | 0.00 |
March | 0.102376E+10 | 0.553812E+09 | 0.990187E+09 | 0.556380E+09 | 0.433807E+09 | 0.00 | 0.00 |
April | 0.864423E+09 | 0.408638E+09 | 0.793578E+09 | 0.317116E+09 | 0.476462E+09 | 0.00 | 0.00 |
May | 0.839235E+09 | 0.290799E+09 | 0.717599E+09 | 0.208421E+09 | 0.509178E+09 | 0.00 | 0.00 |
June | 0.852375E+09 | 0.200005E+09 | 0.674783E+09 | 0.142990E+09 | 0.531793E+09 | 0.00 | 0.00 |
July | 0.986588E+09 | 0.144351E+09 | 0.711805E+09 | 0.172707E+09 | 0.539098E+09 | 0.00 | 0.00 |
August | 0.108668E+10 | 0.190195E+09 | 0.799118E+09 | 0.259094E+09 | 0.540024E+09 | 0.00 | 0.00 |
September | 0.113303E+10 | 0.290457E+09 | 0.899165E+09 | 0.437960E+09 | 0.461205E+09 | 0.00 | 0.00 |
October | 0.997053E+09 | 0.422499E+09 | 0.889046E+09 | 0.507840E+09 | 0.381206E+09 | 0.00 | 0.00 |
November | 0.612504E+09 | 0.516022E+09 | 0.616177E+09 | 0.347853E+09 | 0.268325E+09 | 0.00 | 0.00 |
December | 0.477326E+09 | 0.774487E+09 | 0.594148E+09 | 0.307498E+09 | 0.286649E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.100922E+11 | 0.526998E+10 | 0.912888E+10 | 0.402594E+10 | 0.510294E+10 | 0.00 | 0.00 |
Minimum of Months | 0.477326E+09 | 0.144351E+09 | 0.594148E+09 | 0.142990E+09 | 0.268325E+09 | 0.00 | 0.00 |
Maximum of Months | 0.113303E+10 | 0.788181E+09 | 0.990187E+09 | 0.556380E+09 | 0.540024E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.603980E+09 | 0.778132E+09 | 0.710534E+09 | 0.414760E+09 | 0.295774E+09 | 0.00 | 0.00 |
February | 0.618884E+09 | 0.682386E+09 | 0.732744E+09 | 0.353323E+09 | 0.379421E+09 | 0.00 | 0.00 |
March | 0.102716E+10 | 0.543467E+09 | 0.990187E+09 | 0.556380E+09 | 0.433807E+09 | 0.00 | 0.00 |
April | 0.868828E+09 | 0.398355E+09 | 0.793578E+09 | 0.317116E+09 | 0.476462E+09 | 0.00 | 0.00 |
May | 0.846198E+09 | 0.280328E+09 | 0.717599E+09 | 0.208421E+09 | 0.509178E+09 | 0.00 | 0.00 |
June | 0.855584E+09 | 0.195709E+09 | 0.674783E+09 | 0.142990E+09 | 0.531793E+09 | 0.00 | 0.00 |
July | 0.988103E+09 | 0.142097E+09 | 0.711805E+09 | 0.172707E+09 | 0.539098E+09 | 0.00 | 0.00 |
August | 0.108799E+10 | 0.187799E+09 | 0.799118E+09 | 0.259094E+09 | 0.540024E+09 | 0.00 | 0.00 |
September | 0.113524E+10 | 0.285842E+09 | 0.899165E+09 | 0.437960E+09 | 0.461205E+09 | 0.00 | 0.00 |
October | 0.100076E+10 | 0.414169E+09 | 0.889046E+09 | 0.507840E+09 | 0.381206E+09 | 0.00 | 0.00 |
November | 0.615143E+09 | 0.506725E+09 | 0.616177E+09 | 0.347853E+09 | 0.268325E+09 | 0.00 | 0.00 |
December | 0.478880E+09 | 0.764497E+09 | 0.594148E+09 | 0.307498E+09 | 0.286649E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.101267E+11 | 0.517951E+10 | 0.912888E+10 | 0.402594E+10 | 0.510294E+10 | 0.00 | 0.00 |
Minimum of Months | 0.478880E+09 | 0.142097E+09 | 0.594148E+09 | 0.142990E+09 | 0.268325E+09 | 0.00 | 0.00 |
Maximum of Months | 0.113524E+10 | 0.778132E+09 | 0.990187E+09 | 0.556380E+09 | 0.540024E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.611613E+09 | 0.734331E+09 | 0.710534E+09 | 0.414760E+09 | 0.295774E+09 | 0.00 | 0.00 |
February | 0.627216E+09 | 0.645063E+09 | 0.732744E+09 | 0.353323E+09 | 0.379421E+09 | 0.00 | 0.00 |
March | 0.103889E+10 | 0.501441E+09 | 0.990187E+09 | 0.556380E+09 | 0.433807E+09 | 0.00 | 0.00 |
April | 0.880642E+09 | 0.360618E+09 | 0.793578E+09 | 0.317116E+09 | 0.476462E+09 | 0.00 | 0.00 |
May | 0.861908E+09 | 0.249065E+09 | 0.717599E+09 | 0.208421E+09 | 0.509178E+09 | 0.00 | 0.00 |
June | 0.863493E+09 | 0.179568E+09 | 0.674783E+09 | 0.142990E+09 | 0.531793E+09 | 0.00 | 0.00 |
July | 0.990514E+09 | 0.133288E+09 | 0.711805E+09 | 0.172707E+09 | 0.539098E+09 | 0.00 | 0.00 |
August | 0.109009E+10 | 0.178214E+09 | 0.799118E+09 | 0.259094E+09 | 0.540024E+09 | 0.00 | 0.00 |
September | 0.114040E+10 | 0.269002E+09 | 0.899165E+09 | 0.437960E+09 | 0.461205E+09 | 0.00 | 0.00 |
October | 0.100956E+10 | 0.387002E+09 | 0.889046E+09 | 0.507840E+09 | 0.381206E+09 | 0.00 | 0.00 |
November | 0.622973E+09 | 0.472735E+09 | 0.616177E+09 | 0.347853E+09 | 0.268325E+09 | 0.00 | 0.00 |
December | 0.485531E+09 | 0.720697E+09 | 0.594148E+09 | 0.307498E+09 | 0.286649E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.102228E+11 | 0.483102E+10 | 0.912888E+10 | 0.402594E+10 | 0.510294E+10 | 0.00 | 0.00 |
Minimum of Months | 0.485531E+09 | 0.133288E+09 | 0.594148E+09 | 0.142990E+09 | 0.268325E+09 | 0.00 | 0.00 |
Maximum of Months | 0.114040E+10 | 0.734331E+09 | 0.990187E+09 | 0.556380E+09 | 0.540024E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -3.4 | -4.9 | -8.7 | 5.96 | -14.4 | 41.15 | 62.17 | 0.00 |
February | -4.2 | -5.4 | -8.1 | 6.66 | -15.1 | 65.72 | 71.39 | 0.00 |
March | 2.67 | 0.66 | -2.8 | 5.20 | -8.9 | 69.76 | 141.76 | 0.00 |
April | 7.47 | 4.95 | 1.92 | 5.29 | -2.7 | 89.32 | 159.79 | 0.00 |
May | 13.73 | 9.66 | 5.81 | 4.79 | 3.34 | 93.75 | 203.34 | 0.03 |
June | 18.63 | 14.47 | 11.49 | 5.10 | 8.69 | 105.42 | 236.95 | 0.00 |
July | 22.03 | 18.19 | 16.11 | 4.43 | 13.39 | 102.98 | 214.28 | 0.00 |
August | 20.69 | 16.39 | 13.72 | 4.23 | 11.88 | 99.24 | 178.64 | 0.00 |
September | 16.55 | 13.42 | 11.22 | 4.10 | 7.08 | 75.66 | 154.97 | 0.03 |
October | 9.73 | 7.36 | 4.97 | 4.79 | 0.13 | 58.70 | 104.01 | 0.00 |
November | 6.03 | 3.70 | 0.77 | 5.87 | -3.2 | 41.19 | 58.47 | 0.00 |
December | -2.2 | -3.2 | -5.3 | 6.59 | -12.0 | 40.52 | 44.30 | 0.00 |
Annual Sum or Average | 9.05 | 6.33 | 3.49 | 5.24 | -0.9 | 73.64 | 136.19 | 0.01 |
Minimum of Months | -4.2 | -5.4 | -8.7 | 4.10 | -15.1 | 40.52 | 44.30 | 0.00 |
Maximum of Months | 22.03 | 18.19 | 16.11 | 6.66 | 13.39 | 105.42 | 236.95 | 0.03 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 11-JAN-15:00 | 10.14 | 8.90 | 13.40 | 7.15 | 65.50 | 1.00 |
February | 12.80 | 22-FEB-17:00 | 6.18 | -2.2 | 14.90 | 3.48 | 0.00 | 0.00 |
March | 26.10 | 15-MAR-13:00 | 16.06 | 9.40 | 6.70 | 14.65 | 249.50 | 400.00 |
April | 21.10 | 08-APR-12:00 | 13.43 | 7.80 | 8.20 | 11.46 | 330.00 | 283.50 |
May | 26.10 | 10-MAY-13:00 | 17.84 | 13.30 | 5.20 | 13.35 | 258.50 | 457.00 |
June | 30.60 | 12-JUN-13:00 | 20.23 | 15.00 | 8.20 | 17.93 | 252.00 | 572.00 |
July | 31.70 | 21-JUL-13:00 | 21.73 | 17.20 | 5.20 | 22.47 | 330.00 | 231.00 |
August | 30.60 | 10-AUG-13:00 | 20.24 | 15.00 | 5.70 | 19.70 | 220.50 | 635.00 |
September | 27.20 | 16-SEP-13:09 | 19.53 | 15.68 | 8.80 | 17.30 | 207.00 | 564.67 |
October | 22.20 | 11-OCT-12:00 | 14.14 | 8.30 | 6.20 | 6.95 | 121.00 | 665.00 |
November | 19.40 | 05-NOV-13:00 | 13.85 | 10.00 | 12.40 | 14.84 | 133.00 | 3.50 |
December | 15.00 | 01-DEC-10:00 | 12.41 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.70 | 6.18 | -2.2 | 5.20 | 3.48 | 0.00 | 0.00 | |
Maximum of Months | 31.70 | 21.73 | 17.20 | 14.90 | 22.47 | 330.00 | 665.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -13.9 | 31-JAN-01:00 | -14.5 | -17.2 | 1.50 | -25.9 | 0.00 | 0.00 |
February | -16.7 | 07-FEB-06:00 | -17.3 | -20.6 | 6.20 | -35.1 | 0.00 | 0.00 |
March | -13.3 | 07-MAR-05:19 | -13.9 | -16.7 | 2.43 | -32.2 | 0.00 | 0.00 |
April | -4.4 | 17-APR-05:00 | -5.4 | -7.8 | 2.10 | -20.5 | 35.00 | 151.50 |
May | 1.70 | 01-MAY-04:00 | 0.96 | 0.00 | 0.00 | -14.2 | 0.00 | 0.00 |
June | 6.70 | 04-JUN-04:00 | 5.40 | 3.90 | 2.10 | -7.3 | 20.00 | 104.00 |
July | 11.70 | 03-JUL-03:00 | 11.07 | 10.60 | 2.10 | -1.2 | 0.00 | 0.00 |
August | 11.10 | 01-AUG-04:00 | 10.75 | 10.60 | 2.10 | -0.8 | 0.00 | 0.00 |
September | 6.10 | 05-SEP-05:00 | 5.59 | 5.00 | 2.10 | -6.2 | 24.50 | 41.00 |
October | -2.8 | 17-OCT-04:10 | -3.2 | -4.0 | 2.18 | -19.4 | 0.00 | 0.00 |
November | -3.9 | 24-NOV-05:00 | -4.5 | -5.6 | 2.10 | -18.1 | 0.00 | 0.00 |
December | -18.9 | 11-DEC-05:00 | -19.4 | -23.3 | 2.10 | -35.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -18.9 | -19.4 | -23.3 | 0.00 | -35.1 | 0.00 | 0.00 | |
Maximum of Months | 11.70 | 11.07 | 10.60 | 6.20 | -0.8 | 35.00 | 151.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.21 | 11-JAN-17:00 | 11.10 | 9.40 | 10.30 | 6.55 | 0.00 | 0.00 |
February | 6.89 | 01-FEB-03:00 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 |
March | 17.83 | 14-MAR-12:00 | 25.00 | 13.90 | 6.20 | 14.10 | 197.00 | 562.50 |
April | 13.78 | 08-APR-13:00 | 20.60 | 8.90 | 10.30 | 9.72 | 268.50 | 325.50 |
May | 18.19 | 10-MAY-14:00 | 26.10 | 13.90 | 5.20 | 16.85 | 273.00 | 238.00 |
June | 23.75 | 27-JUN-12:00 | 30.60 | 21.10 | 9.30 | 21.09 | 304.00 | 606.00 |
July | 24.79 | 21-JUL-01:00 | 28.90 | 23.30 | 8.80 | 27.46 | 0.00 | 0.00 |
August | 23.42 | 13-AUG-15:00 | 29.40 | 21.10 | 9.80 | 19.87 | 212.00 | 276.00 |
September | 21.17 | 15-SEP-11:00 | 26.10 | 18.90 | 3.60 | 16.30 | 204.00 | 464.50 |
October | 15.23 | 12-OCT-14:00 | 18.30 | 13.30 | 10.30 | 9.13 | 148.00 | 367.50 |
November | 13.96 | 05-NOV-14:00 | 18.30 | 11.10 | 11.30 | 14.10 | 72.00 | 6.00 |
December | 12.41 | 01-DEC-10:00 | 15.00 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.89 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 24.79 | 30.60 | 23.30 | 12.90 | 27.46 | 304.00 | 606.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 11-JAN-13:00 | 10.00 | 9.66 | 12.90 | 5.54 | 95.50 | 2.00 |
February | 6.70 | 01-FEB-04:10 | 7.20 | 6.89 | 3.52 | 2.22 | 0.00 | 0.00 |
March | 15.00 | 14-MAR-10:20 | 20.33 | 16.97 | 4.80 | 10.50 | 159.17 | 592.83 |
April | 11.10 | 08-APR-21:00 | 13.90 | 12.23 | 12.90 | 9.72 | 0.00 | 0.00 |
May | 15.60 | 17-MAY-12:00 | 16.70 | 15.97 | 6.70 | 13.54 | 184.00 | 0.00 |
June | 21.70 | 27-JUN-14:00 | 25.60 | 22.78 | 8.20 | 16.85 | 255.50 | 530.00 |
July | 23.30 | 20-JUL-20:00 | 25.60 | 24.03 | 4.60 | 24.16 | 0.00 | 0.00 |
August | 21.70 | 14-AUG-03:20 | 23.70 | 22.19 | 5.00 | 21.90 | 0.00 | 0.00 |
September | 20.00 | 15-SEP-18:00 | 21.70 | 20.51 | 0.00 | 19.52 | 0.00 | 0.00 |
October | 14.40 | 01-OCT-07:19 | 14.60 | 14.50 | 3.77 | 10.56 | 67.50 | 30.17 |
November | 11.70 | 05-NOV-15:00 | 12.80 | 12.14 | 7.20 | 8.74 | 28.00 | 4.50 |
December | 11.10 | 01-DEC-12:00 | 13.90 | 12.22 | 10.30 | 6.35 | 158.00 | 84.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.70 | 7.20 | 6.89 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 23.30 | 25.60 | 24.03 | 12.90 | 24.16 | 255.50 | 592.83 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 7.32 | 12.49 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 6.57 | 19.26 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 7.29 | 28.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 9.34 | 37.44 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.19 | 46.60 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 15.07 | 54.01 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.20 | 50.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.01 | 43.20 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.27 | 32.93 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.18 | 21.28 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.32 | 12.54 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 9.45 | 10.96 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.30 | 30.86 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 6.57 | 10.96 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.01 | 54.01 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.379875E+09 | -253684923.9 | 0.00 | 0.00 | 744.00 | 0.00 | -126190469.3 | 58.99 | 0.00 | 0.00 |
February | 0.347998E+09 | -233692597.7 | 0.00 | 0.00 | 672.00 | 0.00 | -114305716.2 | 59.00 | 0.00 | 0.00 |
March | 0.383724E+09 | -259383235.6 | 0.00 | 0.00 | 744.00 | 0.00 | -124340550.7 | 59.00 | 0.00 | 0.00 |
April | 0.356890E+09 | -237979286.8 | 0.00 | 0.00 | 720.00 | 0.00 | -118910242.9 | 58.99 | 0.00 | 0.00 |
May | 0.349617E+09 | -232229671.5 | 0.00 | 0.00 | 744.00 | 0.00 | -117387021.0 | 58.99 | 0.00 | 0.00 |
June | 0.322759E+09 | -213018351.9 | 0.00 | 0.00 | 720.00 | 0.00 | -109741065.9 | 58.99 | 0.00 | 0.00 |
July | 0.317452E+09 | -205142453.7 | 0.00 | 0.00 | 744.00 | 0.00 | -112309846.6 | 58.99 | 0.00 | 0.00 |
August | 0.317854E+09 | -205437200.1 | 0.00 | 0.00 | 744.00 | 0.00 | -112417261.8 | 58.99 | 0.00 | 0.00 |
September | 0.310035E+09 | -200161420.7 | 0.00 | 0.00 | 720.00 | 0.00 | -109873770.2 | 58.99 | 0.00 | 0.00 |
October | 0.334977E+09 | -215156166.7 | 0.00 | 0.00 | 744.00 | 0.00 | -119820496.5 | 58.99 | 0.00 | 0.00 |
November | 0.340419E+09 | -221151500.8 | 0.00 | 0.00 | 720.00 | 0.00 | -119267668.0 | 58.99 | 0.00 | 0.00 |
December | 0.369359E+09 | -243519150.6 | 0.00 | 0.00 | 744.00 | 0.00 | -125840189.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.413096E+10 | -0.272056E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.141040E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.310035E+09 | -259383235.6 | 0.00 | 0.00 | 672.00 | 0.00 | -126190469.3 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.383724E+09 | -200161420.7 | 0.00 | 0.00 | 744.00 | 0.00 | -109741065.9 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.378222E+09 | -253702963.8 | 0.00 | 0.00 | 744.00 | 0.00 | -124519345.7 | 58.99 | 0.00 | 0.00 |
February | 0.346464E+09 | -233695850.7 | 0.00 | 0.00 | 672.00 | 0.00 | -112767867.2 | 58.99 | 0.00 | 0.00 |
March | 0.381539E+09 | -259393088.2 | 0.00 | 0.00 | 744.00 | 0.00 | -122145859.8 | 58.99 | 0.00 | 0.00 |
April | 0.354143E+09 | -237982888.3 | 0.00 | 0.00 | 720.00 | 0.00 | -116160321.1 | 58.99 | 0.00 | 0.00 |
May | 0.347310E+09 | -232225120.3 | 0.00 | 0.00 | 744.00 | 0.00 | -115085045.9 | 58.99 | 0.00 | 0.00 |
June | 0.322220E+09 | -213016962.4 | 0.00 | 0.00 | 720.00 | 0.00 | -109202780.8 | 58.99 | 0.00 | 0.00 |
July | 0.317299E+09 | -205145913.3 | 0.00 | 0.00 | 744.00 | 0.00 | -112153576.5 | 58.99 | 0.00 | 0.00 |
August | 0.317658E+09 | -205435840.6 | 0.00 | 0.00 | 744.00 | 0.00 | -112222567.4 | 58.99 | 0.00 | 0.00 |
September | 0.309383E+09 | -200152995.3 | 0.00 | 0.00 | 720.00 | 0.00 | -109230257.7 | 58.99 | 0.00 | 0.00 |
October | 0.332559E+09 | -215142428.0 | 0.00 | 0.00 | 744.00 | 0.00 | -117416145.7 | 58.99 | 0.00 | 0.00 |
November | 0.338105E+09 | -221151624.0 | 0.00 | 0.00 | 720.00 | 0.00 | -116953538.8 | 58.99 | 0.00 | 0.00 |
December | 0.367582E+09 | -243522532.5 | 0.00 | 0.00 | 744.00 | 0.00 | -124059004.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.411248E+10 | -0.272057E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.139192E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.309383E+09 | -259393088.2 | 0.00 | 0.00 | 672.00 | 0.00 | -124519345.7 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.381539E+09 | -200152995.3 | 0.00 | 0.00 | 744.00 | 0.00 | -109202780.8 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.349432E+09 | -223086228.1 | 0.00 | 0.00 | 744.00 | 0.00 | -126345515.6 | 58.99 | 0.00 | 0.00 |
February | 0.320060E+09 | -205667709.2 | 0.00 | 0.00 | 672.00 | 0.00 | -114392016.7 | 58.99 | 0.00 | 0.00 |
March | 0.355196E+09 | -231506660.1 | 0.00 | 0.00 | 744.00 | 0.00 | -123689003.8 | 58.99 | 0.00 | 0.00 |
April | 0.327155E+09 | -209312086.4 | 0.00 | 0.00 | 720.00 | 0.00 | -117842471.3 | 58.99 | 0.00 | 0.00 |
May | 0.321892E+09 | -205966616.3 | 0.00 | 0.00 | 744.00 | 0.00 | -115925851.2 | 59.00 | 0.00 | 0.00 |
June | 0.297987E+09 | -189704439.7 | 0.00 | 0.00 | 720.00 | 0.00 | -108282063.9 | 58.99 | 0.00 | 0.00 |
July | 0.289814E+09 | -179338419.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110475428.2 | 58.99 | 0.00 | 0.00 |
August | 0.294317E+09 | -183514769.3 | 0.00 | 0.00 | 744.00 | 0.00 | -110802580.1 | 58.99 | 0.00 | 0.00 |
September | 0.284572E+09 | -175894257.9 | 0.00 | 0.00 | 720.00 | 0.00 | -108677634.7 | 59.00 | 0.00 | 0.00 |
October | 0.308124E+09 | -189215161.2 | 0.00 | 0.00 | 744.00 | 0.00 | -118908954.1 | 58.99 | 0.00 | 0.00 |
November | 0.313958E+09 | -195253789.0 | 0.00 | 0.00 | 720.00 | 0.00 | -118704030.6 | 58.99 | 0.00 | 0.00 |
December | 0.338431E+09 | -212557060.1 | 0.00 | 0.00 | 744.00 | 0.00 | -125874028.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.380094E+10 | -0.240102E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.139992E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.284572E+09 | -231506660.1 | 0.00 | 0.00 | 672.00 | 0.00 | -126345515.6 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.355196E+09 | -175894257.9 | 0.00 | 0.00 | 744.00 | 0.00 | -108282063.9 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.349849E+09 | -223086081.9 | 0.00 | 0.00 | 744.00 | 0.00 | -126762838.8 | 58.99 | 0.00 | 0.00 |
February | 0.320430E+09 | -205669006.3 | 0.00 | 0.00 | 672.00 | 0.00 | -114760692.5 | 58.99 | 0.00 | 0.00 |
March | 0.355592E+09 | -231511569.3 | 0.00 | 0.00 | 744.00 | 0.00 | -124079990.9 | 58.99 | 0.00 | 0.00 |
April | 0.327638E+09 | -209291405.0 | 0.00 | 0.00 | 720.00 | 0.00 | -118347079.1 | 59.00 | 0.00 | 0.00 |
May | 0.322360E+09 | -206006159.3 | 0.00 | 0.00 | 744.00 | 0.00 | -116354047.4 | 58.98 | 0.00 | 0.00 |
June | 0.298030E+09 | -189705950.3 | 0.00 | 0.00 | 720.00 | 0.00 | -108323598.9 | 58.99 | 0.00 | 0.00 |
July | 0.289778E+09 | -179341299.8 | 0.00 | 0.00 | 744.00 | 0.00 | -110436897.8 | 58.99 | 0.00 | 0.00 |
August | 0.294297E+09 | -183474983.5 | 0.00 | 0.00 | 744.00 | 0.00 | -110821564.2 | 59.00 | 0.00 | 0.00 |
September | 0.284667E+09 | -175902415.2 | 0.00 | 0.00 | 720.00 | 0.00 | -108764880.2 | 59.00 | 0.00 | 0.00 |
October | 0.308603E+09 | -189220395.6 | 0.00 | 0.00 | 744.00 | 0.00 | -119382522.9 | 58.99 | 0.00 | 0.00 |
November | 0.314387E+09 | -195279732.6 | 0.00 | 0.00 | 720.00 | 0.00 | -119107746.0 | 58.98 | 0.00 | 0.00 |
December | 0.338850E+09 | -212563614.8 | 0.00 | 0.00 | 744.00 | 0.00 | -126286815.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.380448E+10 | -0.240105E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.140343E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.284667E+09 | -231511569.3 | 0.00 | 0.00 | 672.00 | 0.00 | -126762838.8 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.355592E+09 | -175902415.2 | 0.00 | 0.00 | 744.00 | 0.00 | -108323598.9 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.339154E+09 | -210850094.9 | 0.00 | 0.00 | 744.00 | 0.00 | -128303865.9 | 58.99 | 0.00 | 0.00 |
February | 0.310626E+09 | -194485187.2 | 0.00 | 0.00 | 672.00 | 0.00 | -116140599.0 | 59.00 | 0.00 | 0.00 |
March | 0.344471E+09 | -219054133.2 | 0.00 | 0.00 | 744.00 | 0.00 | -125417286.1 | 58.99 | 0.00 | 0.00 |
April | 0.317637E+09 | -198049798.2 | 0.00 | 0.00 | 720.00 | 0.00 | -119587015.4 | 59.00 | 0.00 | 0.00 |
May | 0.312457E+09 | -194801536.5 | 0.00 | 0.00 | 744.00 | 0.00 | -117655243.4 | 58.99 | 0.00 | 0.00 |
June | 0.288411E+09 | -179521569.4 | 0.00 | 0.00 | 720.00 | 0.00 | -108889796.9 | 58.98 | 0.00 | 0.00 |
July | 0.280552E+09 | -169593309.3 | 0.00 | 0.00 | 744.00 | 0.00 | -110958791.0 | 58.99 | 0.00 | 0.00 |
August | 0.284942E+09 | -173631455.1 | 0.00 | 0.00 | 744.00 | 0.00 | -111311008.8 | 58.99 | 0.00 | 0.00 |
September | 0.275769E+09 | -166463378.8 | 0.00 | 0.00 | 720.00 | 0.00 | -109305672.7 | 59.00 | 0.00 | 0.00 |
October | 0.299283E+09 | -178841085.1 | 0.00 | 0.00 | 744.00 | 0.00 | -120441835.5 | 58.99 | 0.00 | 0.00 |
November | 0.304648E+09 | -184410267.6 | 0.00 | 0.00 | 720.00 | 0.00 | -120237745.8 | 58.99 | 0.00 | 0.00 |
December | 0.328788E+09 | -201033163.1 | 0.00 | 0.00 | 744.00 | 0.00 | -127754823.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.368674E+10 | -0.227073E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.141600E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.275769E+09 | -219054133.2 | 0.00 | 0.00 | 672.00 | 0.00 | -128303865.9 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.344471E+09 | -166463378.8 | 0.00 | 0.00 | 744.00 | 0.00 | -108889796.9 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.339004E+09 | -210855403.9 | 0.00 | 0.00 | 744.00 | 0.00 | -128148956.8 | 58.99 | 0.00 | 0.00 |
February | 0.310487E+09 | -194500812.1 | 0.00 | 0.00 | 672.00 | 0.00 | -115986274.3 | 58.99 | 0.00 | 0.00 |
March | 0.344416E+09 | -219042006.5 | 0.00 | 0.00 | 744.00 | 0.00 | -125373640.0 | 59.00 | 0.00 | 0.00 |
April | 0.317653E+09 | -198074847.5 | 0.00 | 0.00 | 720.00 | 0.00 | -119577993.5 | 58.99 | 0.00 | 0.00 |
May | 0.312560E+09 | -194794846.2 | 0.00 | 0.00 | 744.00 | 0.00 | -117765576.6 | 58.99 | 0.00 | 0.00 |
June | 0.288472E+09 | -179526842.9 | 0.00 | 0.00 | 720.00 | 0.00 | -108945623.0 | 58.98 | 0.00 | 0.00 |
July | 0.280643E+09 | -169612612.3 | 0.00 | 0.00 | 744.00 | 0.00 | -111030863.5 | 58.99 | 0.00 | 0.00 |
August | 0.285036E+09 | -173629956.2 | 0.00 | 0.00 | 744.00 | 0.00 | -111405996.9 | 58.99 | 0.00 | 0.00 |
September | 0.275816E+09 | -166463077.3 | 0.00 | 0.00 | 720.00 | 0.00 | -109353108.7 | 59.00 | 0.00 | 0.00 |
October | 0.299320E+09 | -178829092.2 | 0.00 | 0.00 | 744.00 | 0.00 | -120490562.3 | 59.00 | 0.00 | 0.00 |
November | 0.304636E+09 | -184415059.4 | 0.00 | 0.00 | 720.00 | 0.00 | -120220652.0 | 58.99 | 0.00 | 0.00 |
December | 0.328654E+09 | -201032075.1 | 0.00 | 0.00 | 744.00 | 0.00 | -127622072.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.368670E+10 | -0.227078E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.141592E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.275816E+09 | -219042006.5 | 0.00 | 0.00 | 672.00 | 0.00 | -128148956.8 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.344416E+09 | -166463077.3 | 0.00 | 0.00 | 744.00 | 0.00 | -108945623.0 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.339091E+09 | -210852877.0 | 0.00 | 0.00 | 744.00 | 0.00 | -128237874.7 | 58.99 | 0.00 | 0.00 |
February | 0.310558E+09 | -194492156.7 | 0.00 | 0.00 | 672.00 | 0.00 | -116065697.3 | 58.99 | 0.00 | 0.00 |
March | 0.344554E+09 | -219047415.9 | 0.00 | 0.00 | 744.00 | 0.00 | -125506751.8 | 58.99 | 0.00 | 0.00 |
April | 0.317861E+09 | -198054934.5 | 0.00 | 0.00 | 720.00 | 0.00 | -119806012.9 | 59.00 | 0.00 | 0.00 |
May | 0.312893E+09 | -194794062.0 | 0.00 | 0.00 | 744.00 | 0.00 | -118099026.4 | 58.99 | 0.00 | 0.00 |
June | 0.288601E+09 | -179487922.4 | 0.00 | 0.00 | 720.00 | 0.00 | -109112702.9 | 59.00 | 0.00 | 0.00 |
July | 0.280712E+09 | -169631374.8 | 0.00 | 0.00 | 744.00 | 0.00 | -111080378.4 | 58.98 | 0.00 | 0.00 |
August | 0.285099E+09 | -173619833.5 | 0.00 | 0.00 | 744.00 | 0.00 | -111479475.3 | 59.00 | 0.00 | 0.00 |
September | 0.275926E+09 | -166473959.8 | 0.00 | 0.00 | 720.00 | 0.00 | -109452277.0 | 58.99 | 0.00 | 0.00 |
October | 0.299522E+09 | -178838543.8 | 0.00 | 0.00 | 744.00 | 0.00 | -120683770.5 | 58.99 | 0.00 | 0.00 |
November | 0.304778E+09 | -184419539.2 | 0.00 | 0.00 | 720.00 | 0.00 | -120358820.5 | 58.99 | 0.00 | 0.00 |
December | 0.328738E+09 | -201026856.0 | 0.00 | 0.00 | 744.00 | 0.00 | -127711436.6 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.368833E+10 | -0.227074E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.141759E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.275926E+09 | -219047415.9 | 0.00 | 0.00 | 672.00 | 0.00 | -128237874.7 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.344554E+09 | -166473959.8 | 0.00 | 0.00 | 744.00 | 0.00 | -109112702.9 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 255.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 262.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 339.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 371.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 332.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 430.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 439.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 406.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 289.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 314.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 258.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 230.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3928.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 230.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 439.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.258194E+11 | 62235.38 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.243599E+11 | 62235.38 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146348E+11 | 62235.38 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.583726E+10 | 62235.38 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.247675E+09 | 36990.26 | 01-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1425398.05 | 1058.28 | 30-SEP-08:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.260388E+10 | 62235.38 | 17-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.855355E+10 | 62235.38 | 03-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.237882E+11 | 62235.38 | 02-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105846E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.258194E+11 | 62235.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.904986E+10 | 31861.38 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.851419E+10 | 31861.38 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.469456E+10 | 31861.38 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.147298E+10 | 31861.38 | 05-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 8880431.97 | 3431.25 | 01-MAY-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.499913E+09 | 19467.41 | 17-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.248200E+10 | 31861.38 | 24-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.827316E+10 | 31861.38 | 03-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.349955E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.904986E+10 | 31861.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.103336E+11 | 31742.12 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.964515E+10 | 31742.12 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.566110E+10 | 31742.12 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.211137E+10 | 31742.12 | 03-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 62892002.47 | 4109.33 | 08-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 194496.32 | 324.16 | 30-SEP-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.909243E+09 | 26658.88 | 30-OCT-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.332296E+10 | 31742.12 | 23-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.945643E+10 | 31742.12 | 03-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.415030E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.103336E+11 | 31742.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.105840E+11 | 32374.64 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.985561E+10 | 32374.64 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.584298E+10 | 32374.64 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.226258E+10 | 32374.64 | 03-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 89217837.87 | 6430.47 | 01-MAY-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 557284.41 | 901.98 | 30-SEP-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.101635E+10 | 32374.64 | 30-OCT-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.352614E+10 | 32374.64 | 23-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.968175E+10 | 32374.64 | 02-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.428592E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.105840E+11 | 32374.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.109356E+11 | 31742.16 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.101700E+11 | 31742.16 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.611131E+10 | 31742.16 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.246393E+10 | 31742.16 | 03-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.124213E+09 | 8222.59 | 01-MAY-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1629840.41 | 1478.65 | 30-SEP-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.114290E+10 | 31742.16 | 30-OCT-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.376925E+10 | 31742.16 | 19-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.100097E+11 | 31742.16 | 02-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.447286E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.109356E+11 | 31742.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.203062E+11 | 60961.15 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.188560E+11 | 60961.15 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.112481E+11 | 60961.15 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.451307E+10 | 60961.15 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.224082E+09 | 58248.20 | 01-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 55443.46 | 55.21 | 30-SEP-08:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.218545E+10 | 60961.15 | 16-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.713700E+10 | 60961.15 | 03-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.186131E+11 | 60961.15 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.830830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.203062E+11 | 60961.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.105181E+11 | 31405.66 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.977124E+10 | 31405.66 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.583798E+10 | 31405.66 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.234210E+10 | 31405.66 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.117542E+09 | 30353.48 | 01-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.111515E+10 | 31405.66 | 16-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.367638E+10 | 31405.66 | 03-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.964189E+10 | 31405.66 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.430203E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.105181E+11 | 31405.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.106037E+11 | 31287.82 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.984098E+10 | 31287.82 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.593446E+10 | 31287.82 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.243162E+10 | 31287.82 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139456E+09 | 31287.82 | 01-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 229091.69 | 381.82 | 30-SEP-08:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.117055E+10 | 31287.82 | 16-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.376304E+10 | 31287.82 | 03-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.972607E+10 | 31287.82 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.436101E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.106037E+11 | 31287.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.110872E+11 | 31118.56 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.102787E+11 | 31118.56 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.635890E+10 | 31118.56 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.275729E+10 | 31118.56 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.219649E+09 | 31118.56 | 01-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3967527.10 | 2322.25 | 30-SEP-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.136655E+10 | 31118.56 | 16-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.408758E+10 | 31118.56 | 03-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.101847E+11 | 31118.56 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.463446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.110872E+11 | 31118.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.142624E+11 | 32530.29 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134023E+11 | 32530.29 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.849152E+10 | 32530.29 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.392587E+10 | 32530.29 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.513497E+09 | 32530.29 | 01-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1316212.32 | 1060.24 | 14-JUN-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 26162202.27 | 11402.41 | 30-SEP-08:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195633E+10 | 32530.29 | 08-OCT-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.532181E+10 | 32530.29 | 01-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.130244E+11 | 32530.29 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.609256E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.142624E+11 | 32530.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.344057E+09 | 0.293035E+09 | 9344.84 | 15-MAR-14:00 | 8633.63 | 0.00 |
April | 0.00 | 0.00 | 1616808.76 | 1439939.13 | 831.84 | 08-APR-13:00 | 753.14 | 0.00 |
May | 0.00 | 0.00 | 0.110689E+10 | 0.984753E+09 | 12191.69 | 14-MAY-15:00 | 9669.38 | 0.00 |
June | 0.00 | 0.00 | 0.101657E+11 | 0.736500E+10 | 46360.91 | 18-JUN-07:03 | 23232.50 | 0.00 |
July | 0.00 | 0.00 | 0.216192E+11 | 0.144627E+11 | 47557.86 | 21-JUL-08:61 | 25063.62 | 0.00 |
August | 0.00 | 0.00 | 0.169854E+11 | 0.126910E+11 | 46730.88 | 14-AUG-08:61 | 26304.58 | 0.00 |
September | 0.00 | 0.00 | 0.655267E+10 | 0.457591E+10 | 45108.69 | 17-SEP-07:02 | 25591.16 | 0.00 |
October | 0.00 | 0.00 | 0.240971E+09 | 0.208712E+09 | 7010.40 | 11-OCT-16:10 | 6042.23 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.570165E+11 | 0.405826E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.216192E+11 | 0.144627E+11 | 47557.86 | 26304.58 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.241666E+09 | 0.205650E+09 | 21564.89 | 15-MAR-20:01 | 17952.73 | 0.00 |
April | 0.00 | 0.00 | 11895037.75 | 10915151.80 | 2460.43 | 23-APR-17:10 | 2460.43 | 0.00 |
May | 0.00 | 0.00 | 0.909619E+09 | 0.813449E+09 | 22181.75 | 14-MAY-17:43 | 14163.02 | 0.00 |
June | 0.00 | 0.00 | 0.637922E+10 | 0.469845E+10 | 24032.28 | 18-JUN-07:03 | 12789.70 | 0.00 |
July | 0.00 | 0.00 | 0.126861E+11 | 0.865136E+10 | 24203.14 | 21-JUL-08:61 | 15088.09 | 0.00 |
August | 0.00 | 0.00 | 0.100896E+11 | 0.758919E+10 | 23824.20 | 14-AUG-08:61 | 15772.46 | 0.00 |
September | 0.00 | 0.00 | 0.417195E+10 | 0.294573E+10 | 23825.50 | 15-SEP-20:03 | 11403.85 | 0.00 |
October | 0.00 | 0.00 | 0.220800E+09 | 0.187604E+09 | 21551.76 | 22-OCT-17:07 | 17628.00 | 0.00 |
November | 0.00 | 0.00 | 1840525.41 | 1614407.00 | 1256.59 | 04-NOV-18:10 | 1000.94 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.347127E+11 | 0.251040E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.126861E+11 | 0.865136E+10 | 24203.14 | 17952.73 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.179790E+09 | 0.154493E+09 | 4883.31 | 15-MAR-14:00 | 4556.64 | 0.00 |
April | 0.00 | 0.00 | 3740684.03 | 3340100.14 | 967.79 | 08-APR-13:00 | 881.92 | 0.00 |
May | 0.00 | 0.00 | 0.566852E+09 | 0.508618E+09 | 8143.51 | 24-MAY-07:03 | 5031.87 | 0.00 |
June | 0.00 | 0.00 | 0.424004E+10 | 0.312942E+10 | 24306.86 | 18-JUN-08:62 | 13777.44 | 0.00 |
July | 0.00 | 0.00 | 0.869657E+10 | 0.594145E+10 | 24677.46 | 21-JUL-07:01 | 13497.27 | 0.00 |
August | 0.00 | 0.00 | 0.705472E+10 | 0.540342E+10 | 24583.87 | 14-AUG-07:01 | 13107.78 | 0.00 |
September | 0.00 | 0.00 | 0.284514E+10 | 0.203009E+10 | 23584.19 | 16-SEP-07:02 | 13069.33 | 0.00 |
October | 0.00 | 0.00 | 0.101943E+09 | 90102979.55 | 3332.81 | 11-OCT-15:00 | 2963.56 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.236888E+11 | 0.172609E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.869657E+10 | 0.594145E+10 | 24677.46 | 13777.44 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.167629E+09 | 0.144270E+09 | 4700.11 | 15-MAR-14:00 | 4384.68 | 0.00 |
April | 0.00 | 0.00 | 2372620.40 | 2123141.72 | 750.76 | 08-APR-13:00 | 684.24 | 0.00 |
May | 0.00 | 0.00 | 0.528840E+09 | 0.474754E+09 | 6930.68 | 24-MAY-07:03 | 4279.39 | 0.00 |
June | 0.00 | 0.00 | 0.420798E+10 | 0.310491E+10 | 24367.06 | 18-JUN-08:62 | 13811.11 | 0.00 |
July | 0.00 | 0.00 | 0.871505E+10 | 0.595519E+10 | 24731.27 | 21-JUL-07:01 | 13556.26 | 0.00 |
August | 0.00 | 0.00 | 0.706502E+10 | 0.541332E+10 | 24649.81 | 14-AUG-07:01 | 13181.95 | 0.00 |
September | 0.00 | 0.00 | 0.280191E+10 | 0.199797E+10 | 23643.03 | 16-SEP-07:02 | 13101.21 | 0.00 |
October | 0.00 | 0.00 | 86624321.98 | 76746685.79 | 3037.51 | 11-OCT-15:00 | 2701.45 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.235754E+11 | 0.171693E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.871505E+10 | 0.595519E+10 | 24731.27 | 13811.11 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.153387E+09 | 0.132067E+09 | 4460.54 | 15-MAR-14:00 | 4155.38 | 0.00 |
April | 0.00 | 0.00 | 929832.72 | 833884.27 | 467.31 | 08-APR-13:00 | 425.34 | 0.00 |
May | 0.00 | 0.00 | 0.478910E+09 | 0.429613E+09 | 5352.71 | 14-MAY-15:00 | 4278.45 | 0.00 |
June | 0.00 | 0.00 | 0.407337E+10 | 0.300117E+10 | 24279.90 | 18-JUN-08:62 | 13667.52 | 0.00 |
July | 0.00 | 0.00 | 0.853475E+10 | 0.582582E+10 | 24668.78 | 21-JUL-07:01 | 13452.32 | 0.00 |
August | 0.00 | 0.00 | 0.690690E+10 | 0.529100E+10 | 24565.03 | 14-AUG-07:01 | 13069.43 | 0.00 |
September | 0.00 | 0.00 | 0.268293E+10 | 0.190980E+10 | 23566.69 | 16-SEP-07:02 | 13020.84 | 0.00 |
October | 0.00 | 0.00 | 74521525.94 | 66014925.48 | 2760.96 | 11-OCT-15:00 | 2453.18 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.229057E+11 | 0.166563E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.853475E+10 | 0.582582E+10 | 24668.78 | 13667.52 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.278699E+09 | 0.233996E+09 | 8582.68 | 15-MAR-14:10 | 7799.86 | 0.00 |
April | 0.00 | 0.00 | 2326281.07 | 2039312.88 | 596.88 | 08-APR-13:30 | 523.91 | 0.00 |
May | 0.00 | 0.00 | 0.877641E+09 | 0.779683E+09 | 11020.23 | 14-MAY-15:00 | 8560.17 | 0.00 |
June | 0.00 | 0.00 | 0.758151E+10 | 0.550622E+10 | 45432.64 | 18-JUN-09:02 | 24585.59 | 0.00 |
July | 0.00 | 0.00 | 0.159601E+11 | 0.107837E+11 | 45921.87 | 21-JUL-08:61 | 25727.42 | 0.00 |
August | 0.00 | 0.00 | 0.129609E+11 | 0.982598E+10 | 46022.42 | 14-AUG-08:61 | 24314.92 | 0.00 |
September | 0.00 | 0.00 | 0.495013E+10 | 0.348858E+10 | 44227.61 | 17-SEP-09:02 | 23792.53 | 0.00 |
October | 0.00 | 0.00 | 0.130009E+09 | 0.113879E+09 | 5712.03 | 11-OCT-15:00 | 4991.71 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.427414E+11 | 0.307340E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.159601E+11 | 0.107837E+11 | 46022.42 | 25727.42 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.140003E+09 | 0.118110E+09 | 4414.83 | 15-MAR-14:10 | 4023.36 | 0.00 |
April | 0.00 | 0.00 | 418067.18 | 368664.63 | 143.35 | 08-APR-13:30 | 126.22 | 0.00 |
May | 0.00 | 0.00 | 0.436222E+09 | 0.388313E+09 | 5664.07 | 14-MAY-15:00 | 4407.96 | 0.00 |
June | 0.00 | 0.00 | 0.388840E+10 | 0.283290E+10 | 23631.93 | 18-JUN-09:02 | 12823.26 | 0.00 |
July | 0.00 | 0.00 | 0.822637E+10 | 0.557724E+10 | 23872.26 | 21-JUL-08:61 | 13395.53 | 0.00 |
August | 0.00 | 0.00 | 0.668158E+10 | 0.508109E+10 | 23941.53 | 14-AUG-08:61 | 12671.01 | 0.00 |
September | 0.00 | 0.00 | 0.253953E+10 | 0.179340E+10 | 23006.58 | 17-SEP-09:02 | 12409.11 | 0.00 |
October | 0.00 | 0.00 | 64708260.58 | 56855295.71 | 2945.46 | 11-OCT-15:00 | 2582.48 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.219772E+11 | 0.158483E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.822637E+10 | 0.557724E+10 | 23941.53 | 13395.53 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.134985E+09 | 0.113842E+09 | 4318.12 | 15-MAR-14:10 | 3932.44 | 0.00 |
April | 0.00 | 0.00 | 34032.31 | 29977.50 | 28.86 | 08-APR-13:30 | 25.39 | 0.00 |
May | 0.00 | 0.00 | 0.406690E+09 | 0.361479E+09 | 5527.57 | 14-MAY-15:00 | 4294.13 | 0.00 |
June | 0.00 | 0.00 | 0.380911E+10 | 0.277141E+10 | 23545.06 | 18-JUN-09:02 | 12752.28 | 0.00 |
July | 0.00 | 0.00 | 0.812853E+10 | 0.550596E+10 | 23785.09 | 21-JUL-08:61 | 13305.80 | 0.00 |
August | 0.00 | 0.00 | 0.659837E+10 | 0.501598E+10 | 23851.39 | 14-AUG-08:61 | 12581.28 | 0.00 |
September | 0.00 | 0.00 | 0.248081E+10 | 0.174973E+10 | 22922.78 | 17-SEP-09:02 | 12348.79 | 0.00 |
October | 0.00 | 0.00 | 60565477.45 | 53193032.71 | 2828.88 | 11-OCT-15:00 | 2478.84 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.216191E+11 | 0.155716E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.812853E+10 | 0.550596E+10 | 23851.39 | 13305.80 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.119047E+09 | 0.100495E+09 | 4033.72 | 15-MAR-14:10 | 3668.29 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.337084E+09 | 0.298586E+09 | 5156.30 | 14-MAY-15:00 | 3987.97 | 0.00 |
June | 0.00 | 0.00 | 0.360672E+10 | 0.261666E+10 | 23408.30 | 18-JUN-09:02 | 12618.93 | 0.00 |
July | 0.00 | 0.00 | 0.791099E+10 | 0.535276E+10 | 23648.03 | 21-JUL-08:61 | 13152.58 | 0.00 |
August | 0.00 | 0.00 | 0.641252E+10 | 0.487642E+10 | 23705.93 | 14-AUG-08:61 | 12394.51 | 0.00 |
September | 0.00 | 0.00 | 0.232917E+10 | 0.163800E+10 | 22792.26 | 17-SEP-09:02 | 12245.38 | 0.00 |
October | 0.00 | 0.00 | 51171629.26 | 44942044.79 | 2565.68 | 11-OCT-15:00 | 2246.74 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.207667E+11 | 0.149279E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.791099E+10 | 0.535276E+10 | 23705.93 | 13152.58 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 99366575.48 | 84658219.26 | 3744.36 | 15-MAR-14:10 | 3421.65 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.248348E+09 | 0.219154E+09 | 4641.43 | 14-MAY-15:00 | 3582.75 | 0.00 |
June | 0.00 | 0.00 | 0.345112E+10 | 0.251695E+10 | 24743.79 | 18-JUN-09:02 | 13244.43 | 0.00 |
July | 0.00 | 0.00 | 0.796793E+10 | 0.544816E+10 | 25384.91 | 21-JUL-08:61 | 12579.38 | 0.00 |
August | 0.00 | 0.00 | 0.646973E+10 | 0.498108E+10 | 25131.24 | 14-AUG-08:61 | 12578.12 | 0.00 |
September | 0.00 | 0.00 | 0.216824E+10 | 0.153360E+10 | 24107.48 | 17-SEP-09:02 | 12770.31 | 0.00 |
October | 0.00 | 0.00 | 45684023.41 | 40577295.83 | 2394.60 | 11-OCT-15:00 | 2113.70 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.204504E+11 | 0.148242E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.796793E+10 | 0.544816E+10 | 25384.91 | 13244.43 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.206681E+10 | 0.45 | 2116.16 | 01-JAN-09:01 | 0.90 |
February | 0.189159E+10 | 0.46 | 2116.16 | 01-FEB-09:01 | 0.90 |
March | 0.184289E+10 | 0.42 | 2116.16 | 01-MAR-08:61 | 0.90 |
April | 0.160685E+10 | 0.39 | 2116.16 | 01-APR-08:61 | 0.90 |
May | 0.154088E+10 | 0.37 | 1601.12 | 01-MAY-08:61 | 0.79 |
June | 0.149641E+10 | 0.37 | 2116.16 | 02-JUN-08:62 | 0.89 |
July | 0.155391E+10 | 0.37 | 2116.16 | 05-JUL-08:62 | 0.89 |
August | 0.154663E+10 | 0.37 | 2116.16 | 05-AUG-08:62 | 0.89 |
September | 0.149103E+10 | 0.37 | 2116.16 | 14-SEP-08:62 | 0.89 |
October | 0.158901E+10 | 0.38 | 2116.16 | 17-OCT-08:61 | 0.90 |
November | 0.165893E+10 | 0.40 | 2116.16 | 03-NOV-08:61 | 0.90 |
December | 0.203061E+10 | 0.45 | 2116.16 | 02-DEC-09:01 | 0.90 |
Annual Sum or Average | 0.203156E+11 | 0.40 | |||
Minimum of Months | 0.149103E+10 | 0.37 | 1601.12 | 0.79 | |
Maximum of Months | 0.206681E+10 | 0.46 | 2116.16 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.826180E+09 | 0.38 | 1155.65 | 01-JAN-09:01 | 0.93 |
February | 0.755181E+09 | 0.39 | 1155.65 | 01-FEB-09:01 | 0.93 |
March | 0.749109E+09 | 0.34 | 1155.65 | 01-MAR-09:01 | 0.93 |
April | 0.666147E+09 | 0.33 | 1155.65 | 05-APR-08:61 | 0.93 |
May | 0.747912E+09 | 0.37 | 536.93 | 01-MAY-08:06 | 0.62 |
June | 0.745483E+09 | 0.37 | 1155.65 | 02-JUN-08:62 | 0.92 |
July | 0.750801E+09 | 0.36 | 1155.65 | 05-JUL-08:62 | 0.92 |
August | 0.758839E+09 | 0.37 | 1155.65 | 05-AUG-08:62 | 0.92 |
September | 0.764428E+09 | 0.37 | 1155.65 | 13-SEP-08:62 | 0.92 |
October | 0.700681E+09 | 0.35 | 885.92 | 17-OCT-08:61 | 0.82 |
November | 0.669832E+09 | 0.32 | 1155.65 | 24-NOV-09:01 | 0.93 |
December | 0.805503E+09 | 0.36 | 1155.65 | 03-DEC-09:01 | 0.93 |
Annual Sum or Average | 0.894010E+10 | 0.36 | |||
Minimum of Months | 0.666147E+09 | 0.32 | 536.93 | 0.62 | |
Maximum of Months | 0.826180E+09 | 0.39 | 1155.65 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.893097E+09 | 0.37 | 1153.56 | 01-JAN-09:01 | 0.93 |
February | 0.814961E+09 | 0.37 | 1153.56 | 01-FEB-08:61 | 0.93 |
March | 0.804501E+09 | 0.34 | 1153.56 | 01-MAR-08:61 | 0.93 |
April | 0.693877E+09 | 0.32 | 1153.56 | 03-APR-07:01 | 0.93 |
May | 0.675788E+09 | 0.31 | 551.03 | 08-MAY-07:10 | 0.63 |
June | 0.659750E+09 | 0.31 | 1153.56 | 02-JUN-07:02 | 0.92 |
July | 0.673958E+09 | 0.30 | 1153.56 | 02-JUL-08:62 | 0.92 |
August | 0.684935E+09 | 0.31 | 1153.56 | 01-AUG-07:02 | 0.92 |
September | 0.648571E+09 | 0.30 | 1153.56 | 14-SEP-07:02 | 0.92 |
October | 0.687598E+09 | 0.31 | 1042.72 | 30-OCT-07:02 | 0.89 |
November | 0.720296E+09 | 0.33 | 1153.56 | 23-NOV-09:02 | 0.93 |
December | 0.870647E+09 | 0.36 | 1153.56 | 03-DEC-09:01 | 0.93 |
Annual Sum or Average | 0.882798E+10 | 0.33 | |||
Minimum of Months | 0.648571E+09 | 0.30 | 551.03 | 0.63 | |
Maximum of Months | 0.893097E+09 | 0.37 | 1153.56 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.896894E+09 | 0.37 | 1157.23 | 01-JAN-09:01 | 0.93 |
February | 0.817949E+09 | 0.37 | 1157.23 | 01-FEB-08:61 | 0.93 |
March | 0.808545E+09 | 0.35 | 1157.23 | 01-MAR-08:61 | 0.93 |
April | 0.698428E+09 | 0.32 | 1157.23 | 03-APR-07:01 | 0.93 |
May | 0.678478E+09 | 0.31 | 600.81 | 01-MAY-07:05 | 0.66 |
June | 0.661809E+09 | 0.31 | 1157.23 | 02-JUN-07:02 | 0.92 |
July | 0.676054E+09 | 0.30 | 1157.23 | 02-JUL-08:62 | 0.92 |
August | 0.687099E+09 | 0.31 | 1157.23 | 01-AUG-07:02 | 0.92 |
September | 0.650625E+09 | 0.30 | 1157.23 | 14-SEP-07:02 | 0.92 |
October | 0.691697E+09 | 0.31 | 1157.23 | 30-OCT-07:02 | 0.93 |
November | 0.725527E+09 | 0.33 | 1157.23 | 23-NOV-09:02 | 0.93 |
December | 0.874211E+09 | 0.36 | 1157.23 | 02-DEC-08:61 | 0.93 |
Annual Sum or Average | 0.886732E+10 | 0.33 | |||
Minimum of Months | 0.650625E+09 | 0.30 | 600.81 | 0.66 | |
Maximum of Months | 0.896894E+09 | 0.37 | 1157.23 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.905412E+09 | 0.37 | 1152.53 | 01-JAN-09:01 | 0.93 |
February | 0.825740E+09 | 0.37 | 1152.53 | 01-FEB-08:61 | 0.93 |
March | 0.813589E+09 | 0.35 | 1152.53 | 01-MAR-08:61 | 0.93 |
April | 0.700937E+09 | 0.32 | 1152.53 | 03-APR-07:01 | 0.93 |
May | 0.676519E+09 | 0.31 | 640.14 | 01-MAY-07:05 | 0.69 |
June | 0.658933E+09 | 0.31 | 1152.53 | 02-JUN-07:02 | 0.92 |
July | 0.672562E+09 | 0.30 | 1152.53 | 02-JUL-08:62 | 0.92 |
August | 0.683977E+09 | 0.31 | 1152.53 | 01-AUG-07:02 | 0.92 |
September | 0.647870E+09 | 0.30 | 1152.53 | 14-SEP-07:02 | 0.92 |
October | 0.692073E+09 | 0.31 | 1152.53 | 30-OCT-07:02 | 0.93 |
November | 0.729374E+09 | 0.33 | 1152.53 | 19-NOV-09:02 | 0.93 |
December | 0.881920E+09 | 0.36 | 1152.53 | 02-DEC-08:61 | 0.93 |
Annual Sum or Average | 0.888891E+10 | 0.33 | |||
Minimum of Months | 0.647870E+09 | 0.30 | 640.14 | 0.69 | |
Maximum of Months | 0.905412E+09 | 0.37 | 1152.53 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.150861E+10 | 0.33 | 2055.05 | 01-JAN-09:01 | 0.90 |
February | 0.137672E+10 | 0.34 | 2055.05 | 01-FEB-09:01 | 0.90 |
March | 0.134907E+10 | 0.31 | 2055.05 | 01-MAR-08:61 | 0.90 |
April | 0.115662E+10 | 0.29 | 2055.05 | 01-APR-08:61 | 0.90 |
May | 0.111426E+10 | 0.27 | 2000.17 | 01-MAY-08:61 | 0.89 |
June | 0.108701E+10 | 0.28 | 2055.05 | 02-JUN-08:62 | 0.89 |
July | 0.111271E+10 | 0.27 | 2055.05 | 02-JUL-09:02 | 0.89 |
August | 0.112958E+10 | 0.28 | 2055.05 | 05-AUG-08:62 | 0.89 |
September | 0.106637E+10 | 0.27 | 2055.05 | 14-SEP-08:62 | 0.89 |
October | 0.114209E+10 | 0.28 | 2055.05 | 16-OCT-08:61 | 0.90 |
November | 0.120969E+10 | 0.30 | 2055.05 | 03-NOV-08:61 | 0.90 |
December | 0.146851E+10 | 0.32 | 2055.05 | 01-DEC-09:01 | 0.90 |
Annual Sum or Average | 0.147213E+11 | 0.29 | |||
Minimum of Months | 0.106637E+10 | 0.27 | 2000.17 | 0.89 | |
Maximum of Months | 0.150861E+10 | 0.34 | 2055.05 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.816357E+09 | 0.34 | 1110.41 | 01-JAN-09:01 | 0.93 |
February | 0.744968E+09 | 0.35 | 1110.41 | 01-FEB-09:01 | 0.93 |
March | 0.729864E+09 | 0.32 | 1110.41 | 01-MAR-08:61 | 0.93 |
April | 0.625321E+09 | 0.30 | 1110.41 | 01-APR-08:61 | 0.93 |
May | 0.602114E+09 | 0.28 | 1088.09 | 01-MAY-08:61 | 0.92 |
June | 0.587145E+09 | 0.28 | 1110.41 | 02-JUN-08:62 | 0.92 |
July | 0.600524E+09 | 0.28 | 1110.41 | 02-JUL-09:02 | 0.92 |
August | 0.610000E+09 | 0.29 | 1110.41 | 05-AUG-08:62 | 0.92 |
September | 0.576131E+09 | 0.28 | 1110.41 | 14-SEP-08:62 | 0.92 |
October | 0.616882E+09 | 0.29 | 1110.41 | 16-OCT-08:61 | 0.93 |
November | 0.653627E+09 | 0.31 | 1110.41 | 03-NOV-08:61 | 0.93 |
December | 0.794571E+09 | 0.34 | 1110.41 | 01-DEC-09:01 | 0.93 |
Annual Sum or Average | 0.795750E+10 | 0.30 | |||
Minimum of Months | 0.576131E+09 | 0.28 | 1088.09 | 0.92 | |
Maximum of Months | 0.816357E+09 | 0.35 | 1110.41 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.814971E+09 | 0.34 | 1104.92 | 01-JAN-09:01 | 0.93 |
February | 0.743536E+09 | 0.35 | 1104.92 | 01-FEB-09:01 | 0.93 |
March | 0.728764E+09 | 0.32 | 1104.92 | 01-MAR-08:61 | 0.93 |
April | 0.624312E+09 | 0.30 | 1104.92 | 01-APR-08:61 | 0.93 |
May | 0.599610E+09 | 0.28 | 1104.92 | 01-MAY-08:61 | 0.93 |
June | 0.584104E+09 | 0.28 | 1104.92 | 02-JUN-08:62 | 0.92 |
July | 0.597259E+09 | 0.28 | 1104.92 | 02-JUL-09:02 | 0.92 |
August | 0.606814E+09 | 0.29 | 1104.92 | 05-AUG-08:62 | 0.92 |
September | 0.573255E+09 | 0.28 | 1104.92 | 14-SEP-08:62 | 0.92 |
October | 0.615094E+09 | 0.29 | 1104.92 | 16-OCT-08:61 | 0.93 |
November | 0.652524E+09 | 0.31 | 1104.92 | 03-NOV-08:61 | 0.93 |
December | 0.793209E+09 | 0.34 | 1104.92 | 01-DEC-09:01 | 0.93 |
Annual Sum or Average | 0.793345E+10 | 0.30 | |||
Minimum of Months | 0.573255E+09 | 0.28 | 1104.92 | 0.92 | |
Maximum of Months | 0.814971E+09 | 0.35 | 1104.92 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.821230E+09 | 0.35 | 1097.88 | 01-JAN-09:01 | 0.93 |
February | 0.749599E+09 | 0.36 | 1097.88 | 01-FEB-08:61 | 0.93 |
March | 0.733788E+09 | 0.33 | 1097.88 | 01-MAR-08:61 | 0.93 |
April | 0.627509E+09 | 0.30 | 1097.88 | 01-APR-08:61 | 0.93 |
May | 0.597506E+09 | 0.28 | 1097.88 | 01-MAY-08:61 | 0.93 |
June | 0.579978E+09 | 0.28 | 1097.88 | 12-JUN-08:62 | 0.92 |
July | 0.592863E+09 | 0.28 | 1097.88 | 02-JUL-09:02 | 0.92 |
August | 0.602498E+09 | 0.29 | 1097.88 | 05-AUG-08:62 | 0.92 |
September | 0.569592E+09 | 0.28 | 1097.88 | 14-SEP-08:62 | 0.92 |
October | 0.615460E+09 | 0.29 | 1097.88 | 16-OCT-08:61 | 0.93 |
November | 0.655669E+09 | 0.31 | 1097.88 | 03-NOV-08:61 | 0.93 |
December | 0.799129E+09 | 0.34 | 1097.88 | 01-DEC-09:01 | 0.93 |
Annual Sum or Average | 0.794482E+10 | 0.31 | |||
Minimum of Months | 0.569592E+09 | 0.28 | 1097.88 | 0.92 | |
Maximum of Months | 0.821230E+09 | 0.36 | 1097.88 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.952142E+09 | 0.45 | 1181.18 | 01-JAN-09:01 | 0.93 |
February | 0.877929E+09 | 0.48 | 1181.18 | 01-FEB-08:61 | 0.93 |
March | 0.833461E+09 | 0.37 | 1181.18 | 01-MAR-08:61 | 0.94 |
April | 0.698149E+09 | 0.31 | 1181.18 | 01-APR-08:61 | 0.93 |
May | 0.649022E+09 | 0.29 | 1181.18 | 01-MAY-08:61 | 0.93 |
June | 0.623577E+09 | 0.28 | 1181.18 | 12-JUN-08:62 | 0.92 |
July | 0.636578E+09 | 0.28 | 1181.18 | 04-JUL-09:02 | 0.92 |
August | 0.647225E+09 | 0.29 | 1181.18 | 06-AUG-09:01 | 0.92 |
September | 0.613133E+09 | 0.28 | 1181.18 | 16-SEP-08:62 | 0.92 |
October | 0.673652E+09 | 0.29 | 1181.18 | 08-OCT-09:02 | 0.93 |
November | 0.728263E+09 | 0.31 | 1181.18 | 01-NOV-08:62 | 0.93 |
December | 0.919134E+09 | 0.41 | 1181.18 | 01-DEC-09:01 | 0.93 |
Annual Sum or Average | 0.885227E+10 | 0.34 | |||
Minimum of Months | 0.613133E+09 | 0.28 | 1181.18 | 0.92 | |
Maximum of Months | 0.952142E+09 | 0.48 | 1181.18 | 0.94 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.206681E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.189159E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.193763E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.160732E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.183891E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.404334E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.683337E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.578118E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.314543E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.165417E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.165893E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.203061E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.344893E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.160732E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.683337E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.826180E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.755181E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.812531E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.669416E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.977935E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.227560E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.373243E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.317684E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.177309E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.757092E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.670344E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.805503E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.172321E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.669416E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.373243E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.893097E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.814961E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.853050E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.694918E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.825337E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.170401E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.275788E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.241338E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.135271E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.714778E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.720296E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.870647E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.146151E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.694918E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.275788E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.896894E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.817949E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.854044E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.699092E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.818577E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.169900E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.276485E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.241844E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.134465E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.714918E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.725527E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.874211E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.146282E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.699092E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.276485E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.905412E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.825740E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.855465E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.701199E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.804029E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.166507E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.272220E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.237996E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.131397E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.712166E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.729374E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.881920E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.144965E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.701199E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.272220E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.150861E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.137672E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.142644E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.115729E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.135219E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.298806E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.500430E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.436242E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.231547E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.117777E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.120969E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.146851E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.253475E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.115729E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.500430E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.816357E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.744968E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.768117E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.625440E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.718519E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.154628E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.257422E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.224949E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.120600E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.634346E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.653627E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.794571E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.133319E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.625440E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.257422E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.814971E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.743536E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.765723E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.624322E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.708468E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.152480E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.254928E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.222736E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.118906E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.631482E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.652524E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.793209E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.132247E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.624322E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.254928E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.821230E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.749599E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.766600E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.627509E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.688467E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.147363E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.249695E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.218048E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.114896E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.629389E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.655669E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.799129E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.130376E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.627509E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.249695E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.952142E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.877929E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.861186E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.698149E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.717105E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.148445E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.256554E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.224514E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.115456E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.686161E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.728263E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.919134E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.138898E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.686161E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.256554E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.206681E+10 | 0.00 | 0.258194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.189159E+10 | 0.00 | 0.243599E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.184289E+10 | 0.344057E+09 | 0.146348E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.160685E+10 | 1616808.76 | 0.583726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.154088E+10 | 0.110689E+10 | 0.247675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.149641E+10 | 0.101657E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.155391E+10 | 0.216192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.154663E+10 | 0.169854E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.149103E+10 | 0.655267E+10 | 1425398.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.158901E+10 | 0.240971E+09 | 0.260388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.165893E+10 | 0.00 | 0.855355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.203061E+10 | 0.00 | 0.237882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.203156E+11 | 0.570165E+11 | 0.105846E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.149103E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.206681E+10 | 0.216192E+11 | 0.258194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.826180E+09 | 0.00 | 0.904986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.755181E+09 | 0.00 | 0.851419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.749109E+09 | 0.235663E+09 | 0.469456E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.666147E+09 | 11895037.75 | 0.147298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.747912E+09 | 0.864493E+09 | 8880431.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.745483E+09 | 0.602441E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.750801E+09 | 0.119759E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.758839E+09 | 0.959281E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.764428E+09 | 0.399906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.700681E+09 | 0.212817E+09 | 0.499913E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.669832E+09 | 1840525.41 | 0.248200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.805503E+09 | 0.00 | 0.827316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.894010E+10 | 0.329189E+11 | 0.349955E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.666147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.826180E+09 | 0.119759E+11 | 0.904986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.893097E+09 | 0.00 | 0.103336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.814961E+09 | 0.00 | 0.964515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.804501E+09 | 0.179790E+09 | 0.566110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.693877E+09 | 3740684.03 | 0.211137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.675788E+09 | 0.566852E+09 | 62892002.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.659750E+09 | 0.424004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.673958E+09 | 0.869657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.684935E+09 | 0.705472E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.648571E+09 | 0.284514E+10 | 194496.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.687598E+09 | 0.101943E+09 | 0.909243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.720296E+09 | 0.00 | 0.332296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.870647E+09 | 0.00 | 0.945643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.882798E+10 | 0.236888E+11 | 0.415030E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.648571E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.893097E+09 | 0.869657E+10 | 0.103336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.896894E+09 | 0.00 | 0.105840E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.817949E+09 | 0.00 | 0.985561E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.808545E+09 | 0.167629E+09 | 0.584298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.698428E+09 | 2372620.40 | 0.226258E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.678478E+09 | 0.528840E+09 | 89217837.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.661809E+09 | 0.420798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.676054E+09 | 0.871505E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.687099E+09 | 0.706502E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.650625E+09 | 0.280191E+10 | 557284.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.691697E+09 | 86624321.98 | 0.101635E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.725527E+09 | 0.00 | 0.352614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.874211E+09 | 0.00 | 0.968175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.886732E+10 | 0.235754E+11 | 0.428592E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.650625E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.896894E+09 | 0.871505E+10 | 0.105840E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.905412E+09 | 0.00 | 0.109356E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.825740E+09 | 0.00 | 0.101700E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.813589E+09 | 0.153387E+09 | 0.611131E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.700937E+09 | 929832.72 | 0.246393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.676519E+09 | 0.478910E+09 | 0.124213E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.658933E+09 | 0.407337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.672562E+09 | 0.853475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.683977E+09 | 0.690690E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.647870E+09 | 0.268293E+10 | 1629840.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.692073E+09 | 74521525.94 | 0.114290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.729374E+09 | 0.00 | 0.376925E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.881920E+09 | 0.00 | 0.100097E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.888891E+10 | 0.229057E+11 | 0.447286E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.647870E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.905412E+09 | 0.853475E+10 | 0.109356E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.150861E+10 | 0.00 | 0.203062E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137672E+10 | 0.00 | 0.188560E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.134907E+10 | 0.278699E+09 | 0.112481E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115662E+10 | 2326281.07 | 0.451307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.111426E+10 | 0.877641E+09 | 0.224082E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.108701E+10 | 0.758151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.111271E+10 | 0.159601E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.112958E+10 | 0.129609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.106637E+10 | 0.495013E+10 | 55443.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.114209E+10 | 0.130009E+09 | 0.218545E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.120969E+10 | 0.00 | 0.713700E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.146851E+10 | 0.00 | 0.186131E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.147213E+11 | 0.427414E+11 | 0.830830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.106637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.150861E+10 | 0.159601E+11 | 0.203062E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.816357E+09 | 0.00 | 0.105181E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.744968E+09 | 0.00 | 0.977124E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.729864E+09 | 0.140003E+09 | 0.583798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.625321E+09 | 418067.18 | 0.234210E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.602114E+09 | 0.436222E+09 | 0.117542E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.587145E+09 | 0.388840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.600524E+09 | 0.822637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.610000E+09 | 0.668158E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.576131E+09 | 0.253953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.616882E+09 | 64708260.58 | 0.111515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.653627E+09 | 0.00 | 0.367638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.794571E+09 | 0.00 | 0.964189E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.795750E+10 | 0.219772E+11 | 0.430203E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.576131E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.816357E+09 | 0.822637E+10 | 0.105181E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.814971E+09 | 0.00 | 0.106037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.743536E+09 | 0.00 | 0.984098E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.728764E+09 | 0.134985E+09 | 0.593446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.624312E+09 | 34032.31 | 0.243162E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.599610E+09 | 0.406690E+09 | 0.139456E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.584104E+09 | 0.380911E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.597259E+09 | 0.812853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.606814E+09 | 0.659837E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.573255E+09 | 0.248081E+10 | 229091.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.615094E+09 | 60565477.45 | 0.117055E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.652524E+09 | 0.00 | 0.376304E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.793209E+09 | 0.00 | 0.972607E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.793345E+10 | 0.216191E+11 | 0.436101E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.573255E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.814971E+09 | 0.812853E+10 | 0.106037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.821230E+09 | 0.00 | 0.110872E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.749599E+09 | 0.00 | 0.102787E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.733788E+09 | 0.119047E+09 | 0.635890E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.627509E+09 | 0.00 | 0.275729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.597506E+09 | 0.337084E+09 | 0.219649E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.579978E+09 | 0.360672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.592863E+09 | 0.791099E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.602498E+09 | 0.641252E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.569592E+09 | 0.232917E+10 | 3967527.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.615460E+09 | 51171629.26 | 0.136655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.655669E+09 | 0.00 | 0.408758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.799129E+09 | 0.00 | 0.101847E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.794482E+10 | 0.207667E+11 | 0.463446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.569592E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.821230E+09 | 0.791099E+10 | 0.110872E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.952142E+09 | 0.00 | 0.142624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.877929E+09 | 0.00 | 0.134023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.833461E+09 | 99366575.48 | 0.849152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.698149E+09 | 0.00 | 0.392587E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.649022E+09 | 0.248348E+09 | 0.513497E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.623577E+09 | 0.345112E+10 | 1316212.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.636578E+09 | 0.796793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.647225E+09 | 0.646973E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.613133E+09 | 0.216824E+10 | 26162202.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.673652E+09 | 45684023.41 | 0.195633E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.728263E+09 | 0.00 | 0.532181E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.919134E+09 | 0.00 | 0.130244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.885227E+10 | 0.204504E+11 | 0.609256E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.613133E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.952142E+09 | 0.796793E+10 | 0.142624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.206681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.189159E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.184289E+10 | 0.00 | 0.00 | 0.00 | 94737227.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.160685E+10 | 0.00 | 0.00 | 0.00 | 463957.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.154088E+10 | 0.00 | 0.00 | 0.00 | 0.298030E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.149641E+10 | 0.00 | 0.00 | 0.00 | 0.254693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.155391E+10 | 0.00 | 0.00 | 0.00 | 0.527946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.154663E+10 | 0.00 | 0.00 | 0.00 | 0.423455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.149103E+10 | 0.00 | 0.00 | 0.00 | 0.165440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.158901E+10 | 0.00 | 0.00 | 0.00 | 65157798.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.165893E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.203061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.203156E+11 | 0.00 | 0.00 | 0.00 | 0.141737E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.149103E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.206681E+10 | 0.00 | 0.00 | 0.00 | 0.527946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.826180E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.755181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.749109E+09 | 0.00 | 0.00 | 0.00 | 63422305.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.666147E+09 | 0.00 | 0.00 | 0.00 | 3268924.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.747912E+09 | 0.00 | 0.00 | 0.00 | 0.230023E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.745483E+09 | 0.00 | 0.00 | 0.00 | 0.153011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.750801E+09 | 0.00 | 0.00 | 0.00 | 0.298163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.758839E+09 | 0.00 | 0.00 | 0.00 | 0.241800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.764428E+09 | 0.00 | 0.00 | 0.00 | 0.100866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.700681E+09 | 0.00 | 0.00 | 0.00 | 56411233.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.669832E+09 | 0.00 | 0.00 | 0.00 | 511937.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.805503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.894010E+10 | 0.00 | 0.00 | 0.00 | 0.829204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.666147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.826180E+09 | 0.00 | 0.00 | 0.00 | 0.298163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.893097E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.814961E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.804501E+09 | 0.00 | 0.00 | 0.00 | 48548964.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.693877E+09 | 0.00 | 0.00 | 0.00 | 1040757.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.675788E+09 | 0.00 | 0.00 | 0.00 | 0.149549E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.659750E+09 | 0.00 | 0.00 | 0.00 | 0.104426E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.673958E+09 | 0.00 | 0.00 | 0.00 | 0.208393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.684935E+09 | 0.00 | 0.00 | 0.00 | 0.172845E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.648571E+09 | 0.00 | 0.00 | 0.00 | 0.704137E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.687598E+09 | 0.00 | 0.00 | 0.00 | 27179414.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.720296E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.870647E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.882798E+10 | 0.00 | 0.00 | 0.00 | 0.578709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.648571E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.893097E+09 | 0.00 | 0.00 | 0.00 | 0.208393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.896894E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.817949E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.808545E+09 | 0.00 | 0.00 | 0.00 | 45499050.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.698428E+09 | 0.00 | 0.00 | 0.00 | 663736.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.678478E+09 | 0.00 | 0.00 | 0.00 | 0.140099E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.661809E+09 | 0.00 | 0.00 | 0.00 | 0.103719E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.676054E+09 | 0.00 | 0.00 | 0.00 | 0.208879E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.687099E+09 | 0.00 | 0.00 | 0.00 | 0.173134E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.650625E+09 | 0.00 | 0.00 | 0.00 | 0.694028E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.691697E+09 | 0.00 | 0.00 | 0.00 | 23221141.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.725527E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.874211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.886732E+10 | 0.00 | 0.00 | 0.00 | 0.576083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.650625E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.896894E+09 | 0.00 | 0.00 | 0.00 | 0.208879E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.905412E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.825740E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.813589E+09 | 0.00 | 0.00 | 0.00 | 41875437.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.700937E+09 | 0.00 | 0.00 | 0.00 | 261980.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.676519E+09 | 0.00 | 0.00 | 0.00 | 0.127510E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.658933E+09 | 0.00 | 0.00 | 0.00 | 0.100614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.672562E+09 | 0.00 | 0.00 | 0.00 | 0.204964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.683977E+09 | 0.00 | 0.00 | 0.00 | 0.169599E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.647870E+09 | 0.00 | 0.00 | 0.00 | 0.666097E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.692073E+09 | 0.00 | 0.00 | 0.00 | 20093199.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.729374E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.881920E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.888891E+10 | 0.00 | 0.00 | 0.00 | 0.560761E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.647870E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.905412E+09 | 0.00 | 0.00 | 0.00 | 0.204964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.150861E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.134907E+10 | 0.00 | 0.00 | 0.00 | 77371068.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115662E+10 | 0.00 | 0.00 | 0.00 | 666779.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.111426E+10 | 0.00 | 0.00 | 0.00 | 0.237932E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.108701E+10 | 0.00 | 0.00 | 0.00 | 0.190105E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.111271E+10 | 0.00 | 0.00 | 0.00 | 0.389160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.112958E+10 | 0.00 | 0.00 | 0.00 | 0.323284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.106637E+10 | 0.00 | 0.00 | 0.00 | 0.124910E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.114209E+10 | 0.00 | 0.00 | 0.00 | 35682408.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.120969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.146851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.147213E+11 | 0.00 | 0.00 | 0.00 | 0.106262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.106637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.150861E+10 | 0.00 | 0.00 | 0.00 | 0.389160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.816357E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.744968E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.729864E+09 | 0.00 | 0.00 | 0.00 | 38252726.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.625321E+09 | 0.00 | 0.00 | 0.00 | 118317.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.602114E+09 | 0.00 | 0.00 | 0.00 | 0.116405E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.587145E+09 | 0.00 | 0.00 | 0.00 | 0.959137E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.600524E+09 | 0.00 | 0.00 | 0.00 | 0.197369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.610000E+09 | 0.00 | 0.00 | 0.00 | 0.163949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.576131E+09 | 0.00 | 0.00 | 0.00 | 0.629870E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.616882E+09 | 0.00 | 0.00 | 0.00 | 17464052.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.653627E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.794571E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.795750E+10 | 0.00 | 0.00 | 0.00 | 0.537443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.576131E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.816357E+09 | 0.00 | 0.00 | 0.00 | 0.197369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.814971E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.743536E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.728764E+09 | 0.00 | 0.00 | 0.00 | 36958572.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.624312E+09 | 0.00 | 0.00 | 0.00 | 9660.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.599610E+09 | 0.00 | 0.00 | 0.00 | 0.108858E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.584104E+09 | 0.00 | 0.00 | 0.00 | 0.940697E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.597259E+09 | 0.00 | 0.00 | 0.00 | 0.195202E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.606814E+09 | 0.00 | 0.00 | 0.00 | 0.162054E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.573255E+09 | 0.00 | 0.00 | 0.00 | 0.615808E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.615094E+09 | 0.00 | 0.00 | 0.00 | 16388673.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.652524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.793209E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.793345E+10 | 0.00 | 0.00 | 0.00 | 0.529128E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.573255E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.814971E+09 | 0.00 | 0.00 | 0.00 | 0.195202E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.821230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.749599E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.733788E+09 | 0.00 | 0.00 | 0.00 | 32812702.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.627509E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.597506E+09 | 0.00 | 0.00 | 0.00 | 90960914.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.579978E+09 | 0.00 | 0.00 | 0.00 | 0.893657E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.592863E+09 | 0.00 | 0.00 | 0.00 | 0.190409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.602498E+09 | 0.00 | 0.00 | 0.00 | 0.157799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.569592E+09 | 0.00 | 0.00 | 0.00 | 0.579369E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.615460E+09 | 0.00 | 0.00 | 0.00 | 13928731.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.655669E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.799129E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.794482E+10 | 0.00 | 0.00 | 0.00 | 0.509280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.569592E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.821230E+09 | 0.00 | 0.00 | 0.00 | 0.190409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.952142E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.877929E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.833461E+09 | 0.00 | 0.00 | 0.00 | 27725073.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.698149E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.649022E+09 | 0.00 | 0.00 | 0.00 | 68082872.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.623577E+09 | 0.00 | 0.00 | 0.00 | 0.860868E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.636578E+09 | 0.00 | 0.00 | 0.00 | 0.192896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.647225E+09 | 0.00 | 0.00 | 0.00 | 0.159792E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.613133E+09 | 0.00 | 0.00 | 0.00 | 0.541431E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.673652E+09 | 0.00 | 0.00 | 0.00 | 12508585.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.728263E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.919134E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.885227E+10 | 0.00 | 0.00 | 0.00 | 0.503750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.613133E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.952142E+09 | 0.00 | 0.00 | 0.00 | 0.192896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.189720E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187797E+11 | 0.00 | 0.00 | 0.52 |
February | 0.182474E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173782E+11 | 0.00 | 0.00 | 0.53 |
March | 0.576695E+10 | 13895518.12 | 0.00 | 349157.14 | 163324.29 | 0.949979E+10 | 0.154262E+09 | 0.00 | 0.54 |
April | 0.818208E+10 | 0.00 | 0.00 | 117064.39 | 0.00 | 0.265991E+10 | 0.175164E+09 | 0.00 | 0.53 |
May | 0.495530E+10 | 38563920.21 | 0.00 | 5425184.46 | 0.00 | 25465886.77 | 0.319077E+10 | 0.00 | 0.66 |
June | 0.788638E+09 | 0.162442E+10 | 0.00 | 13687551.75 | 11845423.28 | 0.00 | 0.446461E+10 | 0.00 | 0.89 |
July | 20538051.86 | 0.460638E+10 | 0.00 | 10029220.21 | 12694785.96 | 0.00 | 0.121665E+10 | 0.00 | 0.88 |
August | 0.133500E+09 | 0.265491E+10 | 0.00 | 15504073.97 | 6083652.99 | 0.00 | 0.284250E+10 | 0.00 | 0.88 |
September | 0.119866E+10 | 0.659283E+09 | 0.00 | 14495394.80 | 866778.44 | 0.00 | 0.596761E+10 | 0.00 | 0.92 |
October | 0.869278E+10 | 0.00 | 0.00 | 2351898.23 | 0.00 | 0.374497E+09 | 0.162646E+10 | 0.00 | 0.59 |
November | 0.834042E+10 | 0.00 | 0.00 | 28526.40 | 0.00 | 0.424775E+10 | 34248679.00 | 0.00 | 0.53 |
December | 0.347887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164870E+11 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 0.452797E+11 | 0.959745E+10 | 0.00 | 61988071.35 | 31653964.96 | 0.694523E+11 | 0.196723E+11 | 0.00 | 0.67 |
Minimum of Months | 20538051.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.869278E+10 | 0.460638E+10 | 0.00 | 15504073.97 | 12694785.96 | 0.187797E+11 | 0.596761E+10 | 0.00 | 0.92 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.158332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.601883E+10 | 0.00 | 0.00 | 0.38 |
February | 0.137558E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.562814E+10 | 0.00 | 0.00 | 0.39 |
March | 0.263864E+10 | 8498652.70 | 0.00 | 244222.72 | 0.00 | 0.293421E+10 | 0.120069E+09 | 0.00 | 0.41 |
April | 0.312091E+10 | 0.00 | 0.00 | 458809.88 | 0.00 | 0.667464E+09 | 0.404853E+09 | 0.00 | 0.42 |
May | 0.138748E+10 | 22161830.93 | 0.00 | 4174024.09 | 0.00 | 424389.48 | 0.263825E+10 | 0.00 | 0.66 |
June | 0.219880E+09 | 0.867151E+09 | 0.00 | 6083731.03 | 10938224.87 | 0.00 | 0.230511E+10 | 0.00 | 0.83 |
July | 3964012.18 | 0.240499E+10 | 0.00 | 2730792.29 | 14388636.96 | 0.00 | 0.363321E+09 | 0.00 | 0.73 |
August | 19230796.21 | 0.135256E+10 | 0.00 | 5911452.43 | 6548910.03 | 0.00 | 0.111444E+10 | 0.00 | 0.77 |
September | 0.263008E+09 | 0.381249E+09 | 0.00 | 7224025.66 | 1766974.80 | 0.00 | 0.332096E+10 | 0.00 | 0.92 |
October | 0.299974E+10 | 0.00 | 0.00 | 1995894.82 | 0.00 | 25832598.57 | 0.141236E+10 | 0.00 | 0.51 |
November | 0.337819E+10 | 0.00 | 0.00 | 135602.66 | 0.00 | 0.117699E+10 | 0.136472E+09 | 0.00 | 0.40 |
December | 0.167809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.555100E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.186680E+11 | 0.503661E+10 | 0.00 | 28958555.58 | 33642746.65 | 0.220029E+11 | 0.118158E+11 | 0.00 | 0.57 |
Minimum of Months | 3964012.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.337819E+10 | 0.240499E+10 | 0.00 | 7224025.66 | 14388636.96 | 0.601883E+10 | 0.332096E+10 | 0.00 | 0.92 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.480904E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.752819E+10 | 0.00 | 0.00 | 0.41 |
February | 0.522541E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.687472E+10 | 0.00 | 0.00 | 0.41 |
March | 0.210557E+10 | 8116206.46 | 0.00 | 91815.13 | 17116.71 | 0.380870E+10 | 32133017.58 | 0.00 | 0.43 |
April | 0.305860E+10 | 0.00 | 0.00 | 57272.21 | 0.00 | 0.991738E+09 | 66272326.61 | 0.00 | 0.42 |
May | 0.184380E+10 | 20360532.24 | 0.00 | 1890444.28 | 697894.40 | 14612699.82 | 0.119841E+10 | 0.00 | 0.54 |
June | 0.414465E+09 | 0.688140E+09 | 0.00 | 3645119.05 | 32937580.65 | 0.00 | 0.161074E+10 | 0.00 | 0.69 |
July | 34147066.18 | 0.180853E+10 | 0.00 | 2445329.89 | 90071463.66 | 0.00 | 0.375873E+09 | 0.00 | 0.64 |
August | 0.101722E+09 | 0.107558E+10 | 0.00 | 4120133.85 | 39788095.23 | 0.00 | 0.933694E+09 | 0.00 | 0.68 |
September | 0.591568E+09 | 0.294641E+09 | 0.00 | 4279252.71 | 6469938.68 | 0.00 | 0.200141E+10 | 0.00 | 0.74 |
October | 0.325826E+10 | 0.00 | 0.00 | 759735.68 | 0.00 | 0.157409E+09 | 0.546038E+09 | 0.00 | 0.47 |
November | 0.293225E+10 | 0.00 | 0.00 | 6457.16 | 0.00 | 0.181130E+10 | 12694690.39 | 0.00 | 0.42 |
December | 0.792605E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.680771E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.161364E+11 | 0.389536E+10 | 0.00 | 17295559.97 | 0.169982E+09 | 0.279944E+11 | 0.677727E+10 | 0.00 | 0.52 |
Minimum of Months | 34147066.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.325826E+10 | 0.180853E+10 | 0.00 | 4279252.71 | 90071463.66 | 0.752819E+10 | 0.200141E+10 | 0.00 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.395135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.761383E+10 | 0.00 | 0.00 | 0.41 |
February | 0.391710E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.700547E+10 | 0.00 | 0.00 | 0.41 |
March | 0.185846E+10 | 7630487.61 | 0.00 | 84888.83 | 71832.09 | 0.405299E+10 | 29569513.40 | 0.00 | 0.43 |
April | 0.295594E+10 | 0.00 | 0.00 | 40278.76 | 0.00 | 0.109999E+10 | 41685697.72 | 0.00 | 0.42 |
May | 0.187661E+10 | 19485072.80 | 0.00 | 1696753.68 | 670253.78 | 26107846.73 | 0.108952E+10 | 0.00 | 0.53 |
June | 0.425253E+09 | 0.686183E+09 | 0.00 | 3596617.67 | 32591898.64 | 0.00 | 0.159324E+10 | 0.00 | 0.69 |
July | 33809605.63 | 0.181110E+10 | 0.00 | 2460894.08 | 90384852.82 | 0.00 | 0.377117E+09 | 0.00 | 0.64 |
August | 0.101783E+09 | 0.107627E+10 | 0.00 | 4155404.39 | 39706067.46 | 0.00 | 0.935494E+09 | 0.00 | 0.68 |
September | 0.611322E+09 | 0.291346E+09 | 0.00 | 4202059.16 | 6407726.20 | 0.00 | 0.197514E+10 | 0.00 | 0.74 |
October | 0.320949E+10 | 0.00 | 0.00 | 642939.56 | 0.00 | 0.226894E+09 | 0.478556E+09 | 0.00 | 0.46 |
November | 0.281706E+10 | 0.00 | 0.00 | 21.20 | 0.00 | 0.192970E+10 | 703192.03 | 0.00 | 0.42 |
December | 0.664098E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.693603E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.153407E+11 | 0.389202E+10 | 0.00 | 16879857.33 | 0.169833E+09 | 0.288910E+11 | 0.652102E+10 | 0.00 | 0.52 |
Minimum of Months | 33809605.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.320949E+10 | 0.181110E+10 | 0.00 | 4202059.16 | 90384852.82 | 0.761383E+10 | 0.197514E+10 | 0.00 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.242012E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.776676E+10 | 0.00 | 0.00 | 0.41 |
February | 0.280447E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.711656E+10 | 0.00 | 0.00 | 0.41 |
March | 0.158366E+10 | 7134305.82 | 0.00 | 72784.31 | 239906.10 | 0.432516E+10 | 25480773.59 | 0.00 | 0.43 |
April | 0.273363E+10 | 0.00 | 0.00 | 28455.55 | 0.00 | 0.131393E+10 | 29362736.40 | 0.00 | 0.42 |
May | 0.196095E+10 | 18436937.06 | 0.00 | 1436379.56 | 707120.66 | 30395703.25 | 0.914490E+09 | 0.00 | 0.52 |
June | 0.449105E+09 | 0.671735E+09 | 0.00 | 3392418.17 | 35437202.77 | 0.00 | 0.153087E+10 | 0.00 | 0.68 |
July | 35275851.41 | 0.178141E+10 | 0.00 | 2375955.70 | 89811749.26 | 0.00 | 0.378086E+09 | 0.00 | 0.64 |
August | 0.108259E+09 | 0.106236E+10 | 0.00 | 3952550.63 | 39553501.17 | 0.00 | 0.923107E+09 | 0.00 | 0.67 |
September | 0.657503E+09 | 0.280024E+09 | 0.00 | 3956250.60 | 6286370.28 | 0.00 | 0.188950E+10 | 0.00 | 0.73 |
October | 0.312217E+10 | 0.00 | 0.00 | 528587.65 | 0.00 | 0.343443E+09 | 0.396823E+09 | 0.00 | 0.45 |
November | 0.253762E+10 | 0.00 | 0.00 | 0.00 | 706.76 | 0.220177E+10 | 0.00 | 0.00 | 0.42 |
December | 0.470302E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.712950E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.141809E+11 | 0.382110E+10 | 0.00 | 15743382.17 | 0.172037E+09 | 0.302275E+11 | 0.608773E+10 | 0.00 | 0.52 |
Minimum of Months | 35275851.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.312217E+10 | 0.178141E+10 | 0.00 | 3956250.60 | 89811749.26 | 0.776676E+10 | 0.188950E+10 | 0.00 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.146791E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147651E+11 | 0.00 | 0.00 | 0.38 |
February | 0.156785E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136086E+11 | 0.00 | 0.00 | 0.38 |
March | 0.270067E+10 | 4137080.11 | 0.00 | 235286.90 | 601590.71 | 0.827402E+10 | 74916137.87 | 0.00 | 0.39 |
April | 0.519630E+10 | 0.00 | 0.00 | 59504.40 | 0.00 | 0.233237E+10 | 69832741.78 | 0.00 | 0.38 |
May | 0.369838E+10 | 24757609.01 | 0.00 | 2433475.06 | 5570922.47 | 35744905.15 | 0.170749E+10 | 0.00 | 0.47 |
June | 0.640675E+09 | 0.120254E+10 | 0.00 | 6213040.76 | 43184278.58 | 0.00 | 0.298532E+10 | 0.00 | 0.61 |
July | 26043142.24 | 0.328786E+10 | 0.00 | 3791633.15 | 63565299.37 | 0.00 | 0.602127E+09 | 0.00 | 0.56 |
August | 0.104246E+09 | 0.190764E+10 | 0.00 | 6826480.38 | 42614741.00 | 0.00 | 0.162792E+10 | 0.00 | 0.59 |
September | 0.946517E+09 | 0.427735E+09 | 0.00 | 7320228.77 | 8342212.28 | 0.00 | 0.369896E+10 | 0.00 | 0.65 |
October | 0.588133E+10 | 0.00 | 0.00 | 902967.47 | 0.00 | 0.536943E+09 | 0.769925E+09 | 0.00 | 0.41 |
November | 0.457268E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436883E+10 | 0.00 | 0.00 | 0.38 |
December | 0.448472E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137483E+11 | 0.00 | 2555.71 | 0.38 |
Annual Sum or Average | 0.245189E+11 | 0.685467E+10 | 0.00 | 27782616.87 | 0.163879E+09 | 0.576699E+11 | 0.115365E+11 | 2555.71 | 0.46 |
Minimum of Months | 26043142.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.588133E+10 | 0.328786E+10 | 0.00 | 7320228.77 | 63565299.37 | 0.147651E+11 | 0.369896E+10 | 2555.71 | 0.65 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 51801976.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.739268E+10 | 0.00 | 0.00 | 0.38 |
February | 63632987.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.680879E+10 | 0.00 | 0.00 | 0.38 |
March | 0.121882E+10 | 2200773.53 | 0.00 | 112002.96 | 334420.50 | 0.425798E+10 | 37040174.36 | 0.00 | 0.39 |
April | 0.242051E+10 | 0.00 | 0.00 | 25797.24 | 0.00 | 0.133254E+10 | 31586310.49 | 0.00 | 0.38 |
May | 0.185384E+10 | 12257440.00 | 0.00 | 1167328.55 | 2956785.12 | 26984783.02 | 0.825339E+09 | 0.00 | 0.47 |
June | 0.325450E+09 | 0.605000E+09 | 0.00 | 3136370.34 | 20323420.67 | 0.00 | 0.151963E+10 | 0.00 | 0.62 |
July | 11892628.27 | 0.165324E+10 | 0.00 | 1920601.50 | 31664323.54 | 0.00 | 0.314941E+09 | 0.00 | 0.57 |
August | 50576940.49 | 0.962025E+09 | 0.00 | 3467510.18 | 20921225.62 | 0.00 | 0.841938E+09 | 0.00 | 0.61 |
September | 0.478377E+09 | 0.216389E+09 | 0.00 | 3731672.14 | 4295583.22 | 0.00 | 0.189480E+10 | 0.00 | 0.67 |
October | 0.285330E+10 | 0.00 | 0.00 | 438195.87 | 0.00 | 0.351148E+09 | 0.378151E+09 | 0.00 | 0.41 |
November | 0.212632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233202E+10 | 0.00 | 0.00 | 0.38 |
December | 0.185043E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.690179E+10 | 0.00 | 1006.94 | 0.38 |
Annual Sum or Average | 0.116396E+11 | 0.345111E+10 | 0.00 | 13999478.77 | 80495758.66 | 0.294039E+11 | 0.584342E+10 | 1006.94 | 0.47 |
Minimum of Months | 11892628.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.285330E+10 | 0.165324E+10 | 0.00 | 3731672.14 | 31664323.54 | 0.739268E+10 | 0.189480E+10 | 1006.94 | 0.67 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 44773495.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.739972E+10 | 0.00 | 0.00 | 0.38 |
February | 60649305.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.681167E+10 | 0.00 | 0.00 | 0.38 |
March | 0.114411E+10 | 2140785.64 | 0.00 | 105809.18 | 365545.03 | 0.433253E+10 | 34884436.47 | 0.00 | 0.39 |
April | 0.232321E+10 | 0.00 | 0.00 | 22695.26 | 0.00 | 0.142340E+10 | 29251886.79 | 0.00 | 0.38 |
May | 0.190889E+10 | 11681684.73 | 0.00 | 1039668.78 | 3346855.90 | 30297250.97 | 0.720946E+09 | 0.00 | 0.47 |
June | 0.341525E+09 | 0.597599E+09 | 0.00 | 3008321.44 | 20224099.53 | 0.00 | 0.147790E+10 | 0.00 | 0.61 |
July | 12325767.18 | 0.163750E+10 | 0.00 | 1877920.03 | 31449634.80 | 0.00 | 0.315243E+09 | 0.00 | 0.57 |
August | 53849319.32 | 0.953984E+09 | 0.00 | 3395621.62 | 20762203.43 | 0.00 | 0.835338E+09 | 0.00 | 0.61 |
September | 0.509251E+09 | 0.211057E+09 | 0.00 | 3617849.69 | 4267402.69 | 0.00 | 0.184110E+10 | 0.00 | 0.67 |
October | 0.282728E+10 | 0.00 | 0.00 | 396830.57 | 0.00 | 0.387772E+09 | 0.344093E+09 | 0.00 | 0.41 |
November | 0.202940E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242657E+10 | 0.00 | 1927.33 | 0.38 |
December | 0.166481E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.692029E+10 | 0.00 | 2660.38 | 0.38 |
Annual Sum or Average | 0.114217E+11 | 0.341396E+10 | 0.00 | 13464716.58 | 80415741.38 | 0.297323E+11 | 0.559875E+10 | 4587.71 | 0.47 |
Minimum of Months | 12325767.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.282728E+10 | 0.163750E+10 | 0.00 | 3617849.69 | 31449634.80 | 0.739972E+10 | 0.184110E+10 | 2660.38 | 0.67 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 10556934.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.743384E+10 | 0.00 | 0.00 | 0.38 |
February | 24430176.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.684788E+10 | 0.00 | 0.00 | 0.38 |
March | 0.831013E+09 | 1959246.18 | 0.00 | 86859.00 | 562953.59 | 0.464753E+10 | 27035316.35 | 0.00 | 0.39 |
April | 0.201611E+10 | 0.00 | 0.00 | 14675.98 | 0.00 | 0.171541E+10 | 20801680.26 | 0.00 | 0.38 |
May | 0.191911E+10 | 10308704.64 | 0.00 | 777127.57 | 4409284.52 | 61573506.95 | 0.572541E+09 | 0.00 | 0.45 |
June | 0.405777E+09 | 0.578082E+09 | 0.00 | 2689789.24 | 19681100.88 | 0.00 | 0.134260E+10 | 0.00 | 0.60 |
July | 13660522.34 | 0.159780E+10 | 0.00 | 1748897.55 | 32332561.47 | 0.00 | 0.317662E+09 | 0.00 | 0.57 |
August | 68286903.17 | 0.934457E+09 | 0.00 | 3168878.26 | 20784199.82 | 0.00 | 0.813696E+09 | 0.00 | 0.60 |
September | 0.551502E+09 | 0.197370E+09 | 0.00 | 3328596.99 | 4193324.54 | 498922.95 | 0.173235E+10 | 0.00 | 0.65 |
October | 0.270748E+10 | 0.00 | 0.00 | 311019.35 | 0.00 | 0.521498E+09 | 0.277437E+09 | 0.00 | 0.40 |
November | 0.156934E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287961E+10 | 0.00 | 11336.83 | 0.38 |
December | 82582395.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.700407E+10 | 0.00 | 9840.06 | 0.38 |
Annual Sum or Average | 0.101999E+11 | 0.331997E+10 | 0.00 | 12125843.95 | 81963424.82 | 0.311119E+11 | 0.510412E+10 | 21176.89 | 0.46 |
Minimum of Months | 10556934.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.270748E+10 | 0.159780E+10 | 0.00 | 3328596.99 | 32332561.47 | 0.743384E+10 | 0.173235E+10 | 11336.83 | 0.65 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 1787170.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.741537E+10 | 0.00 | 0.00 | 0.38 |
February | 1451995.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.685071E+10 | 0.00 | 0.00 | 0.38 |
March | 0.274427E+09 | 1739190.08 | 47662.62 | 64654.36 | 854983.29 | 0.517559E+10 | 20037865.86 | 57.62 | 0.39 |
April | 0.103079E+10 | 0.00 | 0.00 | 3800.42 | 0.00 | 0.265206E+10 | 9289938.57 | 0.00 | 0.38 |
May | 0.177970E+10 | 8497403.55 | 721074.75 | 502064.15 | 2698730.23 | 0.269099E+09 | 0.369292E+09 | 21097.59 | 0.45 |
June | 0.471077E+09 | 0.548825E+09 | 0.00 | 2310591.84 | 15395744.82 | 0.00 | 0.119752E+10 | 0.00 | 0.59 |
July | 16050205.47 | 0.152261E+10 | 0.00 | 1871059.79 | 26746404.47 | 0.00 | 0.358615E+09 | 0.00 | 0.59 |
August | 0.122067E+09 | 0.903198E+09 | 0.00 | 2991621.51 | 19133394.69 | 0.00 | 0.777119E+09 | 0.00 | 0.61 |
September | 0.604572E+09 | 0.179075E+09 | 0.00 | 3012237.03 | 3615160.88 | 7847179.65 | 0.163002E+10 | 0.00 | 0.66 |
October | 0.195751E+10 | 0.00 | 0.00 | 233016.59 | 0.00 | 0.125712E+10 | 0.207132E+09 | 0.00 | 0.40 |
November | 0.685128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373108E+10 | 0.00 | 22603.19 | 0.38 |
December | 7813783.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.705783E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.695237E+10 | 0.316394E+10 | 768737.36 | 10989045.68 | 68444418.37 | 0.344167E+11 | 0.456902E+10 | 43758.41 | 0.47 |
Minimum of Months | 1451995.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.195751E+10 | 0.152261E+10 | 721074.75 | 3012237.03 | 26746404.47 | 0.741537E+10 | 0.163002E+10 | 22603.19 | 0.66 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:41:05
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.112430E+12 | 0.481726E+11 | 0.00 | 0.995784E+11 | 0.333750E+11 |
February | 0.203795E+12 | 0.462088E+11 | 0.00 | 0.918169E+11 | 0.311735E+11 |
March | 0.335808E+12 | 0.335419E+11 | 0.00 | 0.742984E+11 | 0.210698E+11 |
April | 0.422089E+12 | 0.229070E+11 | 0.00 | 0.517114E+11 | 0.755935E+10 |
May | 0.539953E+12 | 0.135010E+11 | 0.00 | 0.369040E+11 | 0.790132E+10 |
June | 0.596650E+12 | 0.333782E+10 | 0.00 | 0.162341E+11 | 0.641236E+11 |
July | 0.557823E+12 | -0.688405E+10 | 0.00 | -0.178575E+11 | 0.134579E+12 |
August | 0.468897E+12 | -0.195026E+10 | 0.00 | -593610092.0 | 0.108702E+12 |
September | 0.344782E+12 | 0.747359E+10 | 0.00 | 0.292483E+11 | 0.418739E+11 |
October | 0.215658E+12 | 0.207439E+11 | 0.00 | 0.490108E+11 | 0.485661E+10 |
November | 0.975253E+11 | 0.274701E+11 | 0.00 | 0.603066E+11 | 0.114123E+11 |
December | 0.976034E+11 | 0.472453E+11 | 0.00 | 0.952381E+11 | 0.305998E+11 |
Annual Sum or Average | 0.399301E+13 | 0.261768E+12 | 0.00 | 0.585896E+12 | 0.497226E+12 |
Minimum of Months | 0.975253E+11 | -0.688405E+10 | 0.00 | -0.178575E+11 | 0.485661E+10 |