Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:41
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880
Simulation Timestamp: 2023-10-16 08:41:13
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1223.12 | 585.14 | 585.14 |
Net Site Energy | 1223.12 | 585.14 | 585.14 |
Total Source Energy | 3844.04 | 1838.97 | 1838.97 |
Net Source Energy | 3844.04 | 1838.97 | 1838.97 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 14.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 371.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 441.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 99.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 107.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 60.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1208.91 | 14.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 14.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 371.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 441.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 99.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 107.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 60.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 14.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 371.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 441.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 99.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 107.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 60.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 258.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 257.78 | 6.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 578.34 | 6.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 258.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 257.78 | 6.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 578.34 | 6.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1208.915 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1208.915 | 100.00 |
Total On-Site and Utility Electric Sources | 1208.915 | 100.00 |
Total Electricity End Uses | 1208.915 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 9.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1692.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:41 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Latitude [deg] | 27.85 |
Longitude [deg] | -82.5 |
Elevation [m] | 8.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.77 | 20.77 | 17.8770 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.38 | 10.38 | 19.3382 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 17.3739 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 17.3739 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 17.3739 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.72 | 20.72 | 13.1675 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.3365 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.3365 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.3365 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.36 | 10.36 | 13.3365 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 15.5746 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 15.5746 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 17.8770 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 19.3382 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 17.3739 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 17.3739 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 17.3739 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 13.1675 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 13.3365 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 13.3365 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 13.3365 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 13.3365 | 6.19 | 4.3000 | |
Total | 2090.32 | 15.5746 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 15.5746 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 15.5746 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-SEP-14:20 | 05-FEB-10:09 | - | - | - | - | - | - | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 96522.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 74165.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 27522.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 11589.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 5419.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 126786.86 | 96522.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 96522.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 74165.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 27522.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 11589.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 5419.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 15.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1175.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1398.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 316.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 407.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 341.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 190.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3828.63 | 15.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 7.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 562.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 668.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 151.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 163.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1831.60 | 7.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 7.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 562.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 668.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 151.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 163.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1831.60 | 7.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 2.25 |
SMSTORE1 DIRECT AIR | 1.16 |
SMSTORE2 DIRECT AIR | 1.16 |
SMSTORE3 DIRECT AIR | 1.16 |
SMSTORE4 DIRECT AIR | 1.16 |
LGSTORE2 DIRECT AIR | 2.12 |
SMSTORE5 DIRECT AIR | 1.12 |
SMSTORE6 DIRECT AIR | 1.11 |
SMSTORE7 DIRECT AIR | 1.11 |
SMSTORE8 DIRECT AIR | 1.27 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.25 | 2.25 | 2.25 | 2.25 | 2.25 | 2.25 | 1.00 | 1.00 | 2.25 |
PSZ-AC_2:2 | 1.16 | 1.16 | 1.16 | 1.16 | 1.16 | 1.16 | 1.00 | 1.00 | 1.16 |
PSZ-AC_3:3 | 1.16 | 1.16 | 1.16 | 1.16 | 1.16 | 1.16 | 1.00 | 1.00 | 1.16 |
PSZ-AC_4:4 | 1.16 | 1.16 | 1.16 | 1.16 | 1.16 | 1.16 | 1.00 | 1.00 | 1.16 |
PSZ-AC_5:5 | 1.16 | 1.16 | 1.16 | 1.16 | 1.16 | 1.16 | 1.00 | 1.00 | 1.16 |
PSZ-AC_6:6 | 2.12 | 2.12 | 2.12 | 2.12 | 2.12 | 2.12 | 1.00 | 1.00 | 2.12 |
PSZ-AC_7:7 | 1.12 | 1.12 | 1.12 | 1.12 | 1.12 | 1.12 | 1.00 | 1.00 | 1.12 |
PSZ-AC_8:8 | 1.11 | 1.11 | 1.11 | 1.11 | 1.11 | 1.11 | 1.00 | 1.00 | 1.11 |
PSZ-AC_9:9 | 1.11 | 1.11 | 1.11 | 1.11 | 1.11 | 1.11 | 1.00 | 1.00 | 1.11 |
PSZ-AC_10:10 | 1.27 | 1.27 | 1.27 | 1.27 | 1.27 | 1.27 | 1.00 | 1.00 | 1.27 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.25 | 0.411479 |
PSZ-AC_2:2_OA_CONTROLLER | 1.16 | 0.205739 |
PSZ-AC_3:3_OA_CONTROLLER | 1.16 | 0.205739 |
PSZ-AC_4:4_OA_CONTROLLER | 1.16 | 0.205739 |
PSZ-AC_5:5_OA_CONTROLLER | 1.16 | 0.205739 |
PSZ-AC_6:6_OA_CONTROLLER | 2.12 | 0.411479 |
PSZ-AC_7:7_OA_CONTROLLER | 1.12 | 0.205739 |
PSZ-AC_8:8_OA_CONTROLLER | 1.11 | 0.205739 |
PSZ-AC_9:9_OA_CONTROLLER | 1.11 | 0.205739 |
PSZ-AC_10:10_OA_CONTROLLER | 1.27 | 0.205739 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.25 | 2410.03 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.16 | 1289.15 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.16 | 1284.24 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.16 | 1287.69 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.16 | 1283.20 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 2.12 | 2271.11 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 1.12 | 1235.21 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 1.11 | 1230.03 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 1.11 | 1233.48 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.27 | 1410.66 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.25 | 2.25 | 2.25 | 1.49 | 55929.16 | 59655.32 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.16 | 1.16 | 1.16 | 0.768491 | 28914.33 | 30701.28 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.16 | 1.16 | 1.16 | 0.765562 | 28804.15 | 30599.95 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.16 | 1.16 | 1.16 | 0.767621 | 28881.59 | 30671.17 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.16 | 1.16 | 1.16 | 0.764941 | 28780.75 | 30578.42 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 2.12 | 2.12 | 2.12 | 1.40 | 52705.10 | 56689.66 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 1.12 | 1.12 | 1.12 | 0.736332 | 27704.38 | 29588.39 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 1.11 | 1.11 | 1.11 | 0.733246 | 27588.25 | 29481.58 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 1.11 | 1.11 | 1.11 | 0.735303 | 27665.64 | 29552.75 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.27 | 1.27 | 1.27 | 0.840920 | 30995.66 | 33208.12 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 2.25 | 1.13 | 1.50 | 55929.16 | 27964.58 | 0.701080 | 0.701080 |
PSZ-AC_2:2 COOLING COIL | 1.16 | 0.582190 | 0.776253 | 28914.33 | 14457.17 | 0.701080 | 0.701080 |
PSZ-AC_3:3 COOLING COIL | 1.16 | 0.579972 | 0.773293 | 28804.15 | 14402.08 | 0.701080 | 0.701080 |
PSZ-AC_4:4 COOLING COIL | 1.16 | 0.581531 | 0.775373 | 28881.59 | 14440.80 | 0.701080 | 0.701080 |
PSZ-AC_5:5 COOLING COIL | 1.16 | 0.579500 | 0.772667 | 28780.75 | 14390.38 | 0.701080 | 0.701080 |
PSZ-AC_6:6 COOLING COIL | 2.12 | 1.06 | 1.41 | 52705.10 | 26352.55 | 0.701080 | 0.701080 |
PSZ-AC_7:7 COOLING COIL | 1.12 | 0.557828 | 0.743773 | 27704.38 | 13852.19 | 0.701080 | 0.701080 |
PSZ-AC_8:8 COOLING COIL | 1.11 | 0.555489 | 0.740653 | 27588.25 | 13794.12 | 0.701080 | 0.701080 |
PSZ-AC_9:9 COOLING COIL | 1.11 | 0.557048 | 0.742733 | 27665.64 | 13832.82 | 0.701080 | 0.701080 |
PSZ-AC_10:10 COOLING COIL | 1.27 | 0.637061 | 0.849413 | 30995.66 | 15497.83 | 0.708170 | 0.708170 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 59655.32 |
PSZ-AC_2:2 HEATING COIL | 30701.28 |
PSZ-AC_3:3 HEATING COIL | 30599.95 |
PSZ-AC_4:4 HEATING COIL | 30671.17 |
PSZ-AC_5:5 HEATING COIL | 30578.42 |
PSZ-AC_6:6 HEATING COIL | 56689.66 |
PSZ-AC_7:7 HEATING COIL | 29588.39 |
PSZ-AC_8:8 HEATING COIL | 29481.58 |
PSZ-AC_9:9 HEATING COIL | 29552.75 |
PSZ-AC_10:10 HEATING COIL | 33208.12 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 24.20 | 18.90 | 15.70 | 13.60 | 15.50 | 17.10 | 21.20 | 26.90 | 27.60 | 27.90 | 27.40 | 26.20 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 | 27.85 | -82.52 | -5.00 | 8.00 | 101229 | 1.2032 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.85 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.74 | 20.77 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.66 | 10.38 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.41 | 20.72 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.12 | 10.36 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 17.877 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.177 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 19.338 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 23.638 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 17.374 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.674 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 17.374 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.674 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 17.374 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.674 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 13.168 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.468 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 13.336 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.636 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 13.336 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.636 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 13.336 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.636 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 13.336 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.636 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 4596.695 | 13.194 | 81.718 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4596.695 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 1631.408 | 4.683 | 29.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1631.408 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 2327.780 | 13.363 | 82.767 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2327.780 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1040.795 | 5.975 | 37.007 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1040.795 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 2323.122 | 13.336 | 82.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2323.122 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 703.295 | 4.037 | 25.007 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 703.295 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 2323.122 | 13.336 | 82.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2323.122 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 703.295 | 4.037 | 25.007 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 703.295 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 2323.122 | 13.336 | 82.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2323.122 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 703.295 | 4.037 | 25.007 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 703.295 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 4587.379 | 13.168 | 81.553 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4587.379 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 2323.122 | 13.336 | 82.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2323.122 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 2323.122 | 13.336 | 82.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2323.122 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 2323.122 | 13.336 | 82.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2323.122 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 2323.122 | 13.336 | 82.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2323.122 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.7544 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1995 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2888 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.092 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.937 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.386 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
19 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
20 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
21 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
22 | 7 | -0.31526305E-12 | 0.65421067E-14 | -0.96995935E-13 | 0.16372101E-15 |
23 | 6 | 0.28934589E-07 | 0.21281465E-09 | 0.66261080E-08 | -0.13661131E-12 |
24 | 5 | -0.19144321E-03 | 0.18179002E-05 | -0.98452505E-04 | 0.65494719E-08 |
25 | 4 | 0.29370911 | 0.88327295E-03 | 0.10024532 | -0.33791493E-04 |
26 | 3 | -7.2972687 | 0.27321832E-01 | -2.3480939 | 0.29160644E-01 |
27 | 2 | 40.973187 | 0.96992104E-01 | 15.302757 | -0.33447687 |
28 | 1 | -80.623988 | 0.43709902E-01 | -29.175449 | 1.0802857 |
29 | 0 | 46.824338 | 0.87814252E-03 | 16.290426 | |
30 | 7 | -0.21163652E-08 | -0.68723841E-15 | 0.43910983E-14 | -0.57684426E-16 |
31 | 6 | 0.56109385E-05 | 0.38186281E-08 | 0.31898696E-02 | -0.26759299E-04 |
32 | 5 | -0.40164657E-03 | 0.22608617E-05 | -0.22372456 | 0.19561502E-02 |
33 | 4 | 0.92272104E-02 | 0.10289840E-03 | 4.8295456 | -0.45264980E-01 |
34 | 3 | -0.80993241E-01 | 0.81813938E-03 | -38.021416 | 0.39865375 |
35 | 2 | 0.28754352 | 0.13608947E-02 | 116.48395 | -1.4179393 |
36 | 1 | -0.41499682 | 0.41453381E-03 | -143.90731 | 2.0490399 |
37 | 0 | 0.20232414 | 0.10048102E-04 | 60.838472 | |
38 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
39 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
40 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
41 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
42 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
43 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
44 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
45 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
46 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
47 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
48 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
49 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
50 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
51 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
52 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
53 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
54 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
55 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
56 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
57 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
58 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
59 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
60 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
61 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
62 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
63 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
64 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
65 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
66 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
67 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
68 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
69 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
70 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
71 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
72 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
73 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
74 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
75 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
76 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
77 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
78 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
79 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
80 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
81 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
82 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
83 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
84 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
85 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
86 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
87 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
88 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
89 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
90 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
91 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
92 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
93 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
94 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479936E-14 | -0.41635794E-16 |
95 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
96 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
97 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
98 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
99 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
100 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
101 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
102 | 7 | -0.14484255E-08 | -0.22640907E-15 | 0.11860658E-13 | -0.17473455E-15 |
103 | 6 | 0.80640390E-05 | 0.55493782E-08 | 0.31828288E-02 | -0.26700235E-04 |
104 | 5 | -0.58275339E-03 | 0.32892043E-05 | -0.22332434 | 0.19526176E-02 |
105 | 4 | 0.13421983E-01 | 0.14977251E-03 | 4.8228790 | -0.45200897E-01 |
106 | 3 | -0.11791368 | 0.11914425E-02 | -37.983753 | 0.39823745 |
107 | 2 | 0.41875064 | 0.19825898E-02 | 116.41064 | -1.4169588 |
108 | 1 | -0.60444169 | 0.60433957E-03 | -143.86415 | 2.0483306 |
109 | 0 | 0.29470347 | 0.14596444E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 35 | 1 | VerySmooth | 2.861 | 2.861 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 1.93170E-002 | 0.16139 | 0.61074 | 0.61074 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10774 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 0.157 | 4.517E-004 | 2.488E-004 | 0.314 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.389 | 1.116E-003 | 6.149E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.648E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 8.993E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.389 | 1.116E-003 | 7.565E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 0.112 | 6.453E-004 | 2.994E-004 | 0.448 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 5.921E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 25542.59843 | 30651.11811 | 1.87689 | 2.25227 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 33.90000 | 1.65364E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 16172.48931 | 19406.98718 | 0.69775 | 0.83730 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 13204.86608 | 15845.83929 | 0.97032 | 1.16438 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 33.90000 | 1.65364E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 8003.06076 | 9603.67291 | 0.34529 | 0.41434 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 13154.60060 | 15785.52072 | 0.96662 | 1.15994 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 33.83417 | 1.65363E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 8073.83121 | 9688.59745 | 0.34834 | 0.41801 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 13189.96591 | 15827.95909 | 0.96922 | 1.16306 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 33.83417 | 1.65363E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 8142.65083 | 9771.18100 | 0.35131 | 0.42157 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 13143.92009 | 15772.70410 | 0.96583 | 1.15900 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 33.83417 | 1.65363E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 8287.87593 | 9945.45112 | 0.35757 | 0.42909 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 24070.75853 | 28884.91023 | 1.76870 | 2.12243 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 33.83417 | 1.65363E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 15615.06964 | 18738.08357 | 0.67370 | 0.80845 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 12652.51511 | 15183.01813 | 0.92971 | 1.11566 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 33.76833 | 1.65361E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 8491.08129 | 10189.29755 | 0.36634 | 0.43961 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 12599.48451 | 15119.38142 | 0.92582 | 1.11098 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 33.76833 | 1.65361E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 8496.25716 | 10195.50859 | 0.36656 | 0.43988 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 12634.83023 | 15161.79628 | 0.92841 | 1.11410 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 33.76833 | 1.65361E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 8742.91455 | 10491.49745 | 0.37721 | 0.45265 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 14452.08348 | 17342.50017 | 1.06177 | 1.27412 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 33.50500 | 1.65356E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 10297.07721 | 12356.49265 | 0.44425 | 0.53310 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 35160.82 | 2.25227 | 2.25227 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 27336.85 | 0.83730 | 0.83730 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 18092.68 | 1.16438 | 1.16438 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 13570.05 | 0.41434 | 0.41434 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 18031.15 | 1.15994 | 1.15994 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 13653.73 | 0.41801 | 0.41801 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 18072.17 | 1.16306 | 1.16306 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 13735.11 | 0.42157 | 0.42157 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 18017.69 | 1.15900 | 1.15900 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 13906.85 | 0.42909 | 0.42909 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 33412.78 | 2.12243 | 2.12243 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 26677.75 | 0.80845 | 0.80845 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 17433.33 | 1.11566 | 1.11566 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 14147.14 | 0.43961 | 0.43961 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 17370.48 | 1.11098 | 1.11098 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 14153.26 | 0.43988 | 0.43988 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 17409.70 | 1.11410 | 1.11410 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 14444.94 | 0.45265 | 0.45265 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 19467.43 | 1.27412 | 1.27412 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 16282.72 | 0.53310 | 0.53310 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.25227 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.16438 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.15994 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.16306 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.15900 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.12243 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.11566 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.11098 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.11410 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.27412 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.25227 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.25227 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.25227 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.25227 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.25227 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.25227 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.16438 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.16438 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.16438 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.16438 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.16438 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.16438 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.15994 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.15994 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.15994 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.15994 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.15994 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.15994 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.16306 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.16306 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.16306 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.16306 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.16306 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.16306 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.15900 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.15900 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.15900 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.15900 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.15900 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.15900 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.12243 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.12243 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.12243 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.12243 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.12243 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 2.12243 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.11566 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.11566 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.11566 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.11566 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.11566 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 1.11566 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 1.00000 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.11098 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.11098 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.11098 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.11098 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.11098 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 1.11098 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 1.00000 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.11410 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.11410 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.11410 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.11410 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.11410 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 1.11410 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 1.00000 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.27412 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.27412 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.27412 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.27412 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.27412 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.27412 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.25227 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.16438 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.15994 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.16306 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.15900 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 2.12243 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 1.11566 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 1.11098 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 1.11410 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.27412 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.25227 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.25227 |
104 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2410.03238 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.25227 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.25227 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.25227 |
108 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.48650 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.25227 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.12613 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.50151 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 55929.16000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 27964.58000 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
116 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 55929.16000 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 59655.32255 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
120 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 59655.32255 |
121 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.16438 |
122 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
123 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.16438 |
124 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1289.15347 |
125 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.16438 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.16438 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.16438 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.76849 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.16438 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.58219 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.77625 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 28914.33000 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 14457.16500 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28914.33000 |
137 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30701.28285 |
138 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
139 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
140 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 30701.28285 |
141 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.15994 |
142 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
143 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.15994 |
144 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1284.24119 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.15994 |
146 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.15994 |
147 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.15994 |
148 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.76556 |
149 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.15994 |
150 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.57997 |
151 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.77329 |
152 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 28804.15000 |
153 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 14402.07500 |
154 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
156 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28804.15000 |
157 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30599.94524 |
158 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
159 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
160 | Coil:Heating:Fuel | PSZ-AC_3:3 HEATING COIL | Design Size Nominal Capacity [W] | 30599.94524 |
161 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.16306 |
162 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
163 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.16306 |
164 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1287.69390 |
165 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.16306 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.16306 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.16306 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.76762 |
169 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.16306 |
170 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.58153 |
171 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.77537 |
172 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 28881.59000 |
173 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 14440.79500 |
174 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
175 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28881.59000 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30671.17349 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
179 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
180 | Coil:Heating:Fuel | PSZ-AC_4:4 HEATING COIL | Design Size Nominal Capacity [W] | 30671.17349 |
181 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.15900 |
182 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
183 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.15900 |
184 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1283.19794 |
185 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.15900 |
186 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.15900 |
187 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.15900 |
188 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.76494 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.15900 |
190 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.57950 |
191 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.77267 |
192 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 28780.75000 |
193 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 14390.37500 |
194 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
195 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
196 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28780.75000 |
197 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30578.41593 |
198 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
200 | Coil:Heating:Fuel | PSZ-AC_5:5 HEATING COIL | Design Size Nominal Capacity [W] | 30578.41593 |
201 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.12243 |
202 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
203 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.12243 |
204 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2271.10502 |
205 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.12243 |
206 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.12243 |
207 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.12243 |
208 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.40081 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.12243 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.06122 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.41495 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 52705.10000 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 26352.55000 |
214 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
215 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 52705.10000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 56689.65833 |
218 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
219 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
220 | Coil:Heating:Fuel | PSZ-AC_6:6 HEATING COIL | Design Size Nominal Capacity [W] | 56689.65833 |
221 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.11566 |
222 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
223 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.11566 |
224 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1235.20740 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.11566 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.11566 |
227 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.11566 |
228 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.73633 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.11566 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.55783 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.74377 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 27704.38000 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 13852.19000 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
236 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 27704.38000 |
237 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29588.38953 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
240 | Coil:Heating:Fuel | PSZ-AC_7:7 HEATING COIL | Design Size Nominal Capacity [W] | 29588.38953 |
241 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.11098 |
242 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
243 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.11098 |
244 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1230.02997 |
245 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.11098 |
246 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.11098 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.11098 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.73325 |
249 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.11098 |
250 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.55549 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.74065 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 27588.25000 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 13794.12500 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
256 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 27588.25000 |
257 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29481.57862 |
258 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
259 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
260 | Coil:Heating:Fuel | PSZ-AC_8:8 HEATING COIL | Design Size Nominal Capacity [W] | 29481.57862 |
261 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.11410 |
262 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
263 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.11410 |
264 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1233.48031 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.11410 |
266 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.11410 |
267 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.11410 |
268 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.73530 |
269 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.11410 |
270 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.55705 |
271 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.74273 |
272 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 27665.64000 |
273 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 13832.82000 |
274 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 27665.64000 |
277 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29552.75147 |
278 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
279 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
280 | Coil:Heating:Fuel | PSZ-AC_9:9 HEATING COIL | Design Size Nominal Capacity [W] | 29552.75147 |
281 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.27412 |
282 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
283 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.27412 |
284 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1410.65509 |
285 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.27412 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.27412 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.27412 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.84092 |
289 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.27412 |
290 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.63706 |
291 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.84941 |
292 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 30995.66000 |
293 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 15497.83000 |
294 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70817 |
295 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70817 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 30995.66000 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 33208.11582 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
299 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
300 | Coil:Heating:Fuel | PSZ-AC_10:10 HEATING COIL | Design Size Nominal Capacity [W] | 33208.11582 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 54152.3 | 11.77 | 11.77 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 27995.7 | 11.95 | 11.95 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | 27889.1 | 11.95 | 11.95 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | 27964.0 | 11.95 | 11.95 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | 27866.4 | 11.95 | 11.95 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | 51030.7 | 11.77 | 11.77 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | 26824.2 | 11.95 | 11.95 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | 26711.8 | 11.95 | 11.95 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | 26786.7 | 11.95 | 11.95 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | 29990.9 | 11.91 | 11.91 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 58.18 | 78.94 | 58.18 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.199 | 0.190 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 29.09 | 39.47 | 29.09 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 58.22 | 78.94 | 58.22 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.289 | 0.270 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 1.8627020292E-002 | 8.0574328996E-002 | Pass | Pass | 3.4181201241E-002 | 8.8105355084E-002 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 2.4499898146E-002 | 0.1134127481 | Pass | Pass | 3.5735151429E-002 | 9.6243017269E-002 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 5.0411068397E-002 | 0.1812744773 | Pass | Pass | 0.1692201405 | 1.5175275069 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 5.0492118510E-002 | 0.1825397986 | Pass | Pass | 0.1706180170 | 1.5339823727 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 5.0503654722E-002 | 0.1813682868 | Pass | Pass | 0.1717309222 | 1.5599624681 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 5.0075882139E-002 | 0.1657735336 | Pass | Pass | 0.1703033734 | 1.2937215015 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 4.9952180757E-002 | 0.1670949748 | Pass | Pass | 0.1783046815 | 1.5893566315 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 4.9905337221E-002 | 0.1656373017 | Pass | Pass | 0.1774959081 | 1.5979578429 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 5.0675034032E-002 | 0.1656347109 | Pass | Pass | 0.1833623050 | 1.6499905018 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 5.4841720556E-002 | 0.1587309247 | Pass | Pass | 0.2281451906 | 2.0746552546 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3152.21 | -213.5 | 0.00 | -322.1 | 1902.47 | 4519.09 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60 | 0.00 | 4.60 | Wetbulb [C] | 2.50 | 10.00 |
TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 7.90 | 25.10 | Wetbulb [C] | 3.10 | 270.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 66.00 | 12 | |||
Feb | 66.00 | 22 | |||
Mar | 126.00 | 32 | |||
Apr | 206.00 | 19 | |||
May | 144.00 | 46 | |||
Jun | 99.00 | 30 | |||
Jul | 192.00 | 52 | |||
Aug | 240.00 | 34 | |||
Sep | 310.00 | 44 | |||
Oct | 34.00 | 10 | |||
Nov | 63.00 | 12 | |||
Dec | 35.00 | 24 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 78.94 | 58.18 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.193 | 0.199 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 29.09 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 78.94 | 58.22 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.276 | 0.289 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.861 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.861 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.861 | 0.251 | 0.251 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 124.40 | 2.861 | 0.251 | 0.251 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 124.40 | 2.861 | 0.251 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 13.1942 | 348.39 | 4596.69 | LightsWired | LTG_SCH_BASE_LPD1 | 84.21 | 168.00 | 84.19 | 0.0000 | Y | 72.65 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 4.6828 | 348.39 | 1631.41 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 168.00 | 97.48 | 0.0000 | Y | 29.85 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 13.3632 | 174.19 | 2327.78 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 85.70 | 168.00 | 85.69 | 0.0000 | Y | 37.44 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 5.9749 | 174.19 | 1040.80 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 168.00 | 97.48 | 0.0000 | Y | 19.04 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 13.3365 | 174.19 | 2323.12 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 29.75 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 4.0374 | 174.19 | 703.30 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 10.29 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 13.3365 | 174.19 | 2323.12 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 29.75 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 4.0374 | 174.19 | 703.30 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 10.29 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 13.3365 | 174.19 | 2323.12 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 29.75 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 4.0374 | 174.19 | 703.30 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 10.29 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 13.1675 | 348.39 | 4587.38 | LightsWired | LTG_SCH_BASE_LPD2 | 62.11 | 168.00 | 61.60 | 0.0000 | Y | 53.05 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 13.3365 | 174.19 | 2323.12 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 27.34 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 13.3365 | 174.19 | 2323.12 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 27.34 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 13.3365 | 174.19 | 2323.12 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 27.34 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 13.3365 | 174.19 | 2323.12 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 27.34 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 7.7873 | 4180.64 | 32555.80 | 441.52 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 345.19 | AstronomicalClock | - | 41.73 | 41.73 | 2.70 | |
EXTERIOR_LIGHTS_B | 7274.32 | AstronomicalClock | - | 83.73 | 71.13 | 97.12 | |
Exterior Lighting Total | 7619.51 | 99.82 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 55929.16 | 39210.82 | 16718.34 | 0.70 | 3.73 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 28914.33 | 20271.26 | 8643.07 | 0.70 | 3.80 | |||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 28804.15 | 20194.01 | 8610.14 | 0.70 | 3.80 | |||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 28881.59 | 20248.31 | 8633.28 | 0.70 | 3.80 | |||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 28780.75 | 20177.61 | 8603.14 | 0.70 | 3.80 | |||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 52705.10 | 36950.49 | 15754.61 | 0.70 | 3.73 | |||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 27704.38 | 19422.99 | 8281.39 | 0.70 | 3.80 | |||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 27588.25 | 19341.57 | 8246.68 | 0.70 | 3.80 | |||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 27665.64 | 19395.83 | 8269.81 | 0.70 | 3.80 | |||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 30995.66 | 21950.20 | 9045.46 | 0.71 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 54152.3 | 11.77 | 11.77 | ||||
PSZ-AC_2:2 COOLING COIL | 27995.7 | 11.95 | 11.95 | ||||
PSZ-AC_3:3 COOLING COIL | 27889.1 | 11.95 | 11.95 | ||||
PSZ-AC_4:4 COOLING COIL | 27964.0 | 11.95 | 11.95 | ||||
PSZ-AC_5:5 COOLING COIL | 27866.4 | 11.95 | 11.95 | ||||
PSZ-AC_6:6 COOLING COIL | 51030.7 | 11.77 | 11.77 | ||||
PSZ-AC_7:7 COOLING COIL | 26824.2 | 11.95 | 11.95 | ||||
PSZ-AC_8:8 COOLING COIL | 26711.8 | 11.95 | 11.95 | ||||
PSZ-AC_9:9 COOLING COIL | 26786.7 | 11.95 | 11.95 | ||||
PSZ-AC_10:10 COOLING COIL | 29990.9 | 11.91 | 11.91 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 59655.32 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 30701.28 | 0.80 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | 30599.95 | 0.80 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | 30671.17 | 0.80 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | 30578.42 | 0.80 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | 56689.66 | 0.80 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | 29588.39 | 0.80 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | 29481.58 | 0.80 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | 29552.75 | 0.80 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | 33208.12 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.25 | 2410.03 | 1070.05 | 1.00 | 1.30 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.16 | 1289.15 | 1107.16 | 1.00 | 1.37 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.16 | 1284.24 | 1107.16 | 1.00 | 1.37 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.16 | 1287.69 | 1107.16 | 1.00 | 1.37 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.16 | 1283.20 | 1107.16 | 1.00 | 1.37 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.12 | 2271.11 | 1070.05 | 1.00 | 1.31 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.12 | 1235.21 | 1107.16 | 1.00 | 1.38 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.11 | 1230.03 | 1107.16 | 1.00 | 1.38 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.11 | 1233.48 | 1107.16 | 1.00 | 1.38 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.27 | 1410.66 | 1107.16 | 1.00 | 1.35 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 25542.60 | 30651.12 | 87.98 | 1.877 | 2.252 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 23.89 | 23.88 | 0.01029 | 33.90 | 0.01654 | 0.411 | 0.00 |
SMSTORE1 | 13204.87 | 15845.84 | 90.97 | 0.970 | 1.164 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 23.89 | 23.88 | 0.01034 | 33.90 | 0.01654 | 0.206 | 0.00 |
SMSTORE2 | 13154.60 | 15785.52 | 90.62 | 0.967 | 1.160 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.88 | 0.01035 | 33.83 | 0.01654 | 0.206 | 0.00 |
SMSTORE3 | 13189.97 | 15827.96 | 90.86 | 0.969 | 1.163 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.88 | 0.01035 | 33.83 | 0.01654 | 0.206 | 0.00 |
SMSTORE4 | 13143.92 | 15772.70 | 90.55 | 0.966 | 1.159 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.88 | 0.01035 | 33.83 | 0.01654 | 0.206 | 0.00 |
LGSTORE2 | 24070.76 | 28884.91 | 82.91 | 1.769 | 2.122 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.88 | 0.01034 | 33.83 | 0.01654 | 0.411 | 0.00 |
SMSTORE5 | 12652.52 | 15183.02 | 87.16 | 0.930 | 1.116 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 23.89 | 23.88 | 0.01041 | 33.77 | 0.01654 | 0.206 | 0.00 |
SMSTORE6 | 12599.48 | 15119.38 | 86.80 | 0.926 | 1.111 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 23.89 | 23.88 | 0.01041 | 33.77 | 0.01654 | 0.206 | 0.00 |
SMSTORE7 | 12634.83 | 15161.80 | 87.04 | 0.928 | 1.114 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 23.89 | 23.88 | 0.01041 | 33.77 | 0.01654 | 0.206 | 0.00 |
SMSTORE8 | 14452.08 | 17342.50 | 99.56 | 1.062 | 1.274 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 23.89 | 23.88 | 0.01027 | 33.50 | 0.01654 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 16172.49 | 19406.99 | 55.71 | 0.698 | 0.837 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00704 | 4.60 | 0.00526 | 0.411 | 0.00 |
SMSTORE1 | 8003.06 | 9603.67 | 55.13 | 0.345 | 0.414 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00697 | 4.60 | 0.00526 | 0.206 | 0.00 |
SMSTORE2 | 8073.83 | 9688.60 | 55.62 | 0.348 | 0.418 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00698 | 4.60 | 0.00526 | 0.206 | 0.00 |
SMSTORE3 | 8142.65 | 9771.18 | 56.09 | 0.351 | 0.422 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00698 | 4.60 | 0.00526 | 0.206 | 0.00 |
SMSTORE4 | 8287.88 | 9945.45 | 57.09 | 0.358 | 0.429 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00699 | 4.60 | 0.00526 | 0.206 | 0.00 |
LGSTORE2 | 15615.07 | 18738.08 | 53.79 | 0.674 | 0.808 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00705 | 4.60 | 0.00526 | 0.411 | 0.00 |
SMSTORE5 | 8491.08 | 10189.30 | 58.49 | 0.366 | 0.440 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00700 | 4.60 | 0.00526 | 0.206 | 0.00 |
SMSTORE6 | 8496.26 | 10195.51 | 58.53 | 0.367 | 0.440 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00700 | 4.60 | 0.00526 | 0.206 | 0.00 |
SMSTORE7 | 8742.91 | 10491.50 | 60.23 | 0.377 | 0.453 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00702 | 4.60 | 0.00526 | 0.206 | 0.00 |
SMSTORE8 | 10297.08 | 12356.49 | 70.94 | 0.444 | 0.533 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00707 | 4.60 | 0.00526 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.25 | 2.25 | 0.84 | 0.84 | 2.2523 | 2.2523 | 2.2523 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.16 | 1.16 | 0.41 | 0.41 | 1.1644 | 1.1644 | 1.1644 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 1.16 | 1.16 | 0.42 | 0.42 | 1.1599 | 1.1599 | 1.1599 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 1.16 | 1.16 | 0.42 | 0.42 | 1.1631 | 1.1631 | 1.1631 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.16 | 1.16 | 0.43 | 0.43 | 1.1590 | 1.1590 | 1.1590 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 2.12 | 2.12 | 0.81 | 0.81 | 2.1224 | 2.1224 | 2.1224 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 1.12 | 1.12 | 0.44 | 0.44 | 1.1157 | 1.1157 | 1.1157 | 1.0000 | 1.0000 |
PSZ-AC_8:8 | 1.11 | 1.11 | 0.44 | 0.44 | 1.1110 | 1.1110 | 1.1110 | 1.0000 | 1.0000 |
PSZ-AC_9:9 | 1.11 | 1.11 | 0.45 | 0.45 | 1.1141 | 1.1141 | 1.1141 | 1.0000 | 1.0000 |
PSZ-AC_10:10 | 1.27 | 1.27 | 0.53 | 0.53 | 1.2741 | 1.2741 | 1.2741 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 55929.160 | 39210.815 | 2.252270 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 27964.58 | 18788.02 | 1.501513 | 26.58 | 19.61 | 0.01143069 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 27.4043 | 23.88 | 0.01028939 | 55.5780 | 25542.60 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 59655.323 | 59655.323 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 59655.32 | 59655.32 | 2.252267 | 18.09 | 12.49 | 0.00671836 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 18.2695 | 21.11 | 0.00704499 | 45.2751 | 16172.49 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 28914.330 | 20271.258 | 1.164380 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 14457.17 | 9697.84 | 0.776253 | 26.55 | 19.60 | 0.01143883 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 26.5042 | 23.88 | 0.01034481 | 55.8730 | 13204.87 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 30701.283 | 30701.283 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 30701.28 | 30701.28 | 1.164380 | 18.19 | 12.48 | 0.00666876 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 17.6694 | 21.11 | 0.00697171 | 44.8097 | 8003.06 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 28804.150 | 20194.013 | 1.159940 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 14402.08 | 9652.29 | 0.773293 | 26.56 | 19.61 | 0.01144814 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 26.6056 | 23.88 | 0.01035087 | 55.9052 | 13152.79 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 30599.945 | 30599.945 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 30599.95 | 30599.95 | 1.159943 | 18.18 | 12.48 | 0.00667155 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 17.7370 | 21.11 | 0.00697651 | 44.8402 | 8073.83 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 28881.590 | 20248.305 | 1.163060 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 14440.80 | 9683.92 | 0.775373 | 26.55 | 19.61 | 0.01144200 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 26.5342 | 23.88 | 0.01034691 | 55.8841 | 13187.51 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 30671.173 | 30671.173 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 30671.17 | 30671.17 | 1.163062 | 18.19 | 12.48 | 0.00667628 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 17.6895 | 21.11 | 0.00698127 | 44.8705 | 8142.65 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 28780.750 | 20177.608 | 1.159000 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 14390.38 | 9642.56 | 0.772667 | 26.56 | 19.61 | 0.01145019 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 26.6272 | 23.88 | 0.01035220 | 55.9123 | 13141.39 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 30578.416 | 30578.416 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 30578.42 | 30578.42 | 1.159001 | 18.18 | 12.49 | 0.00668380 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 17.7514 | 21.11 | 0.00699172 | 44.9369 | 8287.88 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 52705.100 | 36950.492 | 2.122430 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 26352.55 | 17525.73 | 1.414953 | 26.69 | 19.73 | 0.01154446 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 29.0807 | 23.88 | 0.01034346 | 55.8646 | 24063.11 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 56689.658 | 56689.658 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 56689.66 | 56689.66 | 2.122434 | 17.91 | 12.40 | 0.00670324 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 19.3871 | 21.11 | 0.00705102 | 45.3130 | 15615.07 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 27704.380 | 19422.987 | 1.115660 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 13852.19 | 9202.69 | 0.743773 | 26.63 | 19.71 | 0.01154109 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 27.6616 | 23.88 | 0.01041100 | 56.2245 | 12646.78 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 29588.390 | 29588.390 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 29588.39 | 29588.39 | 1.115655 | 18.06 | 12.44 | 0.00668191 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 18.4411 | 21.11 | 0.00700407 | 45.0154 | 8491.08 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 27588.250 | 19341.570 | 1.110980 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 13794.12 | 9155.49 | 0.740653 | 26.63 | 19.72 | 0.01155119 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 27.7781 | 23.88 | 0.01041754 | 56.2592 | 12593.59 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 29481.579 | 29481.579 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 29481.58 | 29481.58 | 1.110979 | 18.05 | 12.43 | 0.00668091 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 18.5188 | 21.11 | 0.00700450 | 45.0182 | 8496.26 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 27665.640 | 19395.827 | 1.114100 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 13832.82 | 9186.54 | 0.742733 | 26.63 | 19.71 | 0.01154490 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 27.7003 | 23.88 | 0.01041349 | 56.2377 | 12626.78 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 29552.751 | 29552.751 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 29552.75 | 29552.75 | 1.114095 | 18.06 | 12.45 | 0.00669500 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 18.4669 | 21.11 | 0.00702066 | 45.1209 | 8742.91 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 30995.660 | 21950.197 | 1.274120 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 15497.83 | 10530.73 | 0.849413 | 26.33 | 19.42 | 0.01128453 | 12.80 | 12.09 | 0.00850000 | 33.50 | 0.01653563 | 25.03 | 24.2214 | 23.88 | 0.01027332 | 55.4935 | 14452.08 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 33208.116 | 33208.116 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 33208.12 | 33208.12 | 1.274122 | 18.44 | 12.69 | 0.00677602 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 16.1475 | 21.11 | 0.00706851 | 45.4257 | 10297.08 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 55929.160 | 39210.815 | 2.252270 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.0891 | 1004.8586 | 1.2032 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.252267 | 2.70985335 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | Sensible | 27964.58 | 18788.02 | 1.0000 | 1.80657114 | 1.501513 | 26.58 | 19.61 | 0.01143069 | 55860.1 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27964.58 | 33.90 | 0.01653638 | 25.13 | 0.41147883 | 27.4043 | 23.88 | 0.01028939 | 23.88 | 0.01028939 | 55.5780 | 25542.60 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 59655.323 | 59655.323 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.252267 | 2.70985335 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 59655.32 | 59655.32 | 1.0000 | 2.70985335 | 2.252267 | 18.09 | 12.49 | 0.00671836 | 35208.0 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 59655.32 | 4.60 | 0.00525715 | 4.60 | 0.41147883 | 18.2695 | 21.11 | 0.00704499 | 21.11 | 0.00704499 | 45.2751 | 16172.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28914.330 | 20271.258 | 1.164380 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.1042 | 1004.8586 | 1.2032 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.164380 | 1.40094345 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | Sensible | 14457.17 | 9697.84 | 1.0000 | 0.93396231 | 0.776253 | 26.55 | 19.60 | 0.01143883 | 55849.9 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14457.17 | 33.90 | 0.01653638 | 25.13 | 0.20573941 | 26.5042 | 23.88 | 0.01034481 | 23.88 | 0.01034481 | 55.8730 | 13204.87 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30701.283 | 30701.283 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.164380 | 1.40094345 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 30701.28 | 30701.28 | 1.0000 | 1.40094345 | 1.164380 | 18.19 | 12.48 | 0.00666876 | 35183.0 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30701.28 | 4.60 | 0.00525715 | 4.60 | 0.20573941 | 17.6694 | 21.11 | 0.00697171 | 21.11 | 0.00697171 | 44.8097 | 8003.06 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28804.150 | 20194.013 | 1.159940 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.1215 | 1004.8586 | 1.2032 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.159943 | 1.39560520 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 14402.08 | 9652.29 | 1.0000 | 0.93040094 | 0.773293 | 26.56 | 19.61 | 0.01144814 | 55880.8 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14402.08 | 33.90 | 0.01653638 | 25.13 | 0.20573941 | 26.6056 | 23.88 | 0.01035087 | 23.88 | 0.01035087 | 55.9052 | 13152.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30599.945 | 30599.945 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.159943 | 1.39560520 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 30599.95 | 30599.95 | 1.0000 | 1.39560520 | 1.159943 | 18.18 | 12.48 | 0.00667155 | 35178.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30599.95 | 4.60 | 0.00525715 | 4.60 | 0.20573941 | 17.7370 | 21.11 | 0.00697651 | 21.11 | 0.00697651 | 44.8402 | 8073.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28881.590 | 20248.305 | 1.163060 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.1101 | 1004.8586 | 1.2032 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.163062 | 1.39935731 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 14440.80 | 9683.92 | 1.0000 | 0.93290353 | 0.775373 | 26.55 | 19.61 | 0.01144200 | 55860.3 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14440.80 | 33.90 | 0.01653638 | 25.13 | 0.20573941 | 26.5342 | 23.88 | 0.01034691 | 23.88 | 0.01034691 | 55.8841 | 13187.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30671.173 | 30671.173 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.163062 | 1.39935731 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 30671.17 | 30671.17 | 1.0000 | 1.39935731 | 1.163062 | 18.19 | 12.48 | 0.00667628 | 35198.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30671.17 | 4.60 | 0.00525715 | 4.60 | 0.20573941 | 17.6895 | 21.11 | 0.00698127 | 21.11 | 0.00698127 | 44.8705 | 8142.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28780.750 | 20177.608 | 1.159000 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.1253 | 1004.8586 | 1.2032 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.159001 | 1.39447148 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 14390.38 | 9642.56 | 1.0000 | 0.92964696 | 0.772667 | 26.56 | 19.61 | 0.01145019 | 55887.6 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14390.38 | 33.90 | 0.01653638 | 25.13 | 0.20573941 | 26.6272 | 23.88 | 0.01035220 | 23.88 | 0.01035220 | 55.9123 | 13141.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30578.416 | 30578.416 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.159001 | 1.39447148 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 30578.42 | 30578.42 | 1.0000 | 1.39447148 | 1.159001 | 18.18 | 12.49 | 0.00668380 | 35207.3 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30578.42 | 4.60 | 0.00525715 | 4.60 | 0.20573941 | 17.7514 | 21.11 | 0.00699172 | 21.11 | 0.00699172 | 44.9369 | 8287.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 52705.100 | 36950.492 | 2.122430 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.3006 | 1004.8586 | 1.2032 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.122434 | 2.55364268 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 26352.55 | 17525.73 | 1.0000 | 1.70242501 | 1.414953 | 26.69 | 19.73 | 0.01154446 | 56265.8 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26352.55 | 33.90 | 0.01653638 | 25.13 | 0.41147883 | 29.0807 | 23.88 | 0.01034346 | 23.88 | 0.01034346 | 55.8646 | 24063.11 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 56689.658 | 56689.658 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.122434 | 2.55364268 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 56689.66 | 56689.66 | 1.0000 | 2.55364268 | 2.122434 | 17.91 | 12.40 | 0.00670324 | 34982.0 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 56689.66 | 4.60 | 0.00525715 | 4.60 | 0.41147883 | 19.3871 | 21.11 | 0.00705102 | 21.11 | 0.00705102 | 45.3130 | 15615.07 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 27704.380 | 19422.987 | 1.115660 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.2943 | 1004.8586 | 1.2032 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.115655 | 1.34231940 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | Sensible | 13852.19 | 9202.69 | 1.0000 | 0.89488345 | 0.743773 | 26.63 | 19.71 | 0.01154109 | 56190.7 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13852.19 | 33.90 | 0.01653638 | 25.13 | 0.20573941 | 27.6616 | 23.88 | 0.01041100 | 23.88 | 0.01041100 | 56.2245 | 12646.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29588.390 | 29588.390 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.115655 | 1.34231940 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 29588.39 | 29588.39 | 1.0000 | 1.34231940 | 1.115655 | 18.06 | 12.44 | 0.00668191 | 35086.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29588.39 | 4.60 | 0.00525715 | 4.60 | 0.20573941 | 18.4411 | 21.11 | 0.00700407 | 21.11 | 0.00700407 | 45.0154 | 8491.08 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 27588.250 | 19341.570 | 1.110980 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.3131 | 1004.8586 | 1.2032 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.110979 | 1.33669301 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | Sensible | 13794.12 | 9155.49 | 1.0000 | 0.89112957 | 0.740653 | 26.63 | 19.72 | 0.01155119 | 56224.4 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13794.12 | 33.90 | 0.01653638 | 25.13 | 0.20573941 | 27.7781 | 23.88 | 0.01041754 | 23.88 | 0.01041754 | 56.2592 | 12593.59 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29481.579 | 29481.579 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.110979 | 1.33669301 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 29481.58 | 29481.58 | 1.0000 | 1.33669301 | 1.110979 | 18.05 | 12.43 | 0.00668091 | 35071.1 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29481.58 | 4.60 | 0.00525715 | 4.60 | 0.20573941 | 18.5188 | 21.11 | 0.00700450 | 21.11 | 0.00700450 | 45.0182 | 8496.26 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 27665.640 | 19395.827 | 1.114100 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.3014 | 1004.8586 | 1.2032 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.114095 | 1.34044254 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | Sensible | 13832.82 | 9186.54 | 1.0000 | 0.89363216 | 0.742733 | 26.63 | 19.71 | 0.01154490 | 56203.4 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13832.82 | 33.90 | 0.01653638 | 25.13 | 0.20573941 | 27.7003 | 23.88 | 0.01041349 | 23.88 | 0.01041349 | 56.2377 | 12626.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29552.751 | 29552.751 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.114095 | 1.34044254 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 29552.75 | 29552.75 | 1.0000 | 1.34044254 | 1.114095 | 18.06 | 12.45 | 0.00669500 | 35115.5 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29552.75 | 4.60 | 0.00525715 | 4.60 | 0.20573941 | 18.4669 | 21.11 | 0.00702066 | 21.11 | 0.00702066 | 45.1209 | 8742.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 30995.660 | 21950.197 | 1.274120 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.8174 | 1004.8586 | 1.2032 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.274122 | 1.53298118 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | Sensible | 15497.83 | 10530.73 | 1.0000 | 1.02198600 | 0.849413 | 26.33 | 19.42 | 0.01128453 | 55236.5 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15497.83 | 33.50 | 0.01653563 | 25.03 | 0.20573941 | 24.2214 | 23.88 | 0.01027332 | 23.88 | 0.01027332 | 55.4935 | 14452.08 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 33208.116 | 33208.116 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.274122 | 1.53298118 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 33208.12 | 33208.12 | 1.0000 | 1.53298118 | 1.274122 | 18.44 | 12.69 | 0.00677602 | 35710.3 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33208.12 | 4.60 | 0.00525715 | 4.60 | 0.20573941 | 16.1475 | 21.11 | 0.00706851 | 21.11 | 0.00706851 | 45.4257 | 10297.08 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialEnthalpy | 0.41 | 2.25 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.16 | - | |||
PSZ-AC_3:3_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.16 | - | |||
PSZ-AC_4:4_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.16 | - | |||
PSZ-AC_5:5_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.16 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialEnthalpy | 0.41 | 2.12 | - | |||
PSZ-AC_7:7_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.12 | - | |||
PSZ-AC_8:8_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.11 | - | |||
PSZ-AC_9:9_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.11 | - | |||
PSZ-AC_10:10_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.27 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 4456.67 | 1975.17 | 1066.83 |
SMSTORE1 | 4352.83 | 1406.67 | 628.00 |
SMSTORE2 | 3336.83 | 1727.00 | 1050.00 |
SMSTORE3 | 3316.83 | 1750.17 | 1042.50 |
SMSTORE4 | 3295.83 | 1836.50 | 1096.17 |
LGSTORE2 | 3002.83 | 1853.00 | 1148.33 |
SMSTORE5 | 2976.67 | 1893.17 | 1160.17 |
SMSTORE6 | 2968.33 | 1932.83 | 1183.33 |
SMSTORE7 | 2952.50 | 1988.83 | 1208.83 |
SMSTORE8 | 2972.33 | 1896.83 | 1095.17 |
Facility | 4604.83 | 2848.83 | 1692.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 0.00 | 0.50 | 0.00 | 0.50 |
SMSTORE1 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 0.00 | 2.33 | 0.00 | 2.33 |
SMSTORE3 | 0.00 | 2.33 | 0.00 | 2.33 |
SMSTORE4 | 0.00 | 2.17 | 0.00 | 2.17 |
LGSTORE2 | 0.00 | 6.00 | 0.00 | 6.00 |
SMSTORE5 | 0.00 | 5.00 | 0.00 | 5.00 |
SMSTORE6 | 0.00 | 5.00 | 0.00 | 5.00 |
SMSTORE7 | 0.00 | 4.50 | 0.00 | 4.50 |
SMSTORE8 | 0.00 | 3.00 | 0.00 | 3.00 |
Facility | 0.00 | 9.00 | 0.00 | 9.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.92 | 56.25 | 1805.20 | 0.943 | 0.345 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.817 | 0.384 | 0.000 | 0.000 |
SMSTORE2 | 7.10 | 28.12 | 902.60 | 0.980 | 0.504 | 0.000 | 0.000 |
SMSTORE3 | 7.10 | 28.12 | 902.60 | 0.978 | 0.504 | 0.000 | 0.000 |
SMSTORE4 | 7.10 | 28.12 | 902.60 | 0.973 | 0.504 | 0.000 | 0.000 |
LGSTORE2 | 24.82 | 56.25 | 1805.20 | 0.962 | 0.471 | 0.000 | 0.000 |
SMSTORE5 | 12.41 | 28.12 | 902.60 | 0.970 | 0.538 | 0.000 | 0.000 |
SMSTORE6 | 12.41 | 28.12 | 902.60 | 0.967 | 0.538 | 0.000 | 0.000 |
SMSTORE7 | 12.41 | 28.12 | 902.60 | 0.963 | 0.538 | 0.000 | 0.000 |
SMSTORE8 | 12.41 | 28.12 | 902.60 | 0.982 | 0.553 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.92 | 56.25 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.10 | 28.12 | 902.60 | 0.804 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.10 | 28.12 | 902.60 | 0.804 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.10 | 28.12 | 902.60 | 0.804 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.82 | 56.25 | 1805.20 | 0.803 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.41 | 28.12 | 902.60 | 0.803 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.41 | 28.12 | 902.60 | 0.803 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.41 | 28.12 | 902.60 | 0.802 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.41 | 28.12 | 902.60 | 0.800 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 16.92 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE1 | PSZ-AC_2:2 | 8.46 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE2 | PSZ-AC_3:3 | 7.10 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE3 | PSZ-AC_4:4 | 7.10 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE4 | PSZ-AC_5:5 | 7.10 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
LGSTORE2 | PSZ-AC_6:6 | 24.82 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE5 | PSZ-AC_7:7 | 12.41 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE6 | PSZ-AC_8:8 | 12.41 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE7 | PSZ-AC_9:9 | 12.41 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE8 | PSZ-AC_10:10 | 12.41 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
Total Facility | 121.13 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 2.469 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 9723941.56 | 0.00 | 9723941.56 | 3838649.30 | 13562590.86 | 12976396.34 | 3178.72 | 4686.43 | 894.85 | 0.00 |
SMSTORE1 | 4215940.72 | 0.00 | 4215940.72 | 2068521.06 | 6284461.77 | 6488198.17 | 4422.59 | 3450.74 | 886.67 | 0.00 |
SMSTORE2 | 3804567.24 | 0.00 | 3804567.24 | 2094113.03 | 5898680.27 | 6488198.17 | 4364.83 | 3792.79 | 602.38 | 1.33 |
SMSTORE3 | 3794057.41 | 0.00 | 3794057.41 | 2094113.03 | 5888170.44 | 6488198.17 | 4364.83 | 3811.09 | 584.08 | 2.00 |
SMSTORE4 | 3774858.07 | 0.00 | 3774858.07 | 2094113.03 | 5868971.10 | 6488198.17 | 4364.83 | 3829.07 | 566.09 | 1.67 |
LGSTORE2 | 6845748.45 | 0.00 | 6845748.45 | 3717029.21 | 10562777.65 | 12976396.34 | 4729.71 | 3492.80 | 537.49 | 0.62 |
SMSTORE5 | 3451478.38 | 0.00 | 3451478.38 | 2101897.61 | 5553375.99 | 6488198.17 | 4729.73 | 3498.62 | 531.65 | 0.44 |
SMSTORE6 | 3440833.06 | 0.00 | 3440833.06 | 2101897.61 | 5542730.67 | 6488198.17 | 4729.75 | 3509.24 | 521.01 | 0.44 |
SMSTORE7 | 3425066.07 | 0.00 | 3425066.07 | 2101897.61 | 5526963.68 | 6488198.17 | 4729.83 | 3530.11 | 500.06 | 0.25 |
SMSTORE8 | 3494804.73 | 0.00 | 3494804.73 | 2340335.64 | 5835140.37 | 6488198.17 | 4729.58 | 3542.60 | 487.82 | 0.58 |
Total Facility | 45971295.66 | 0.00 | 45971295.66 | 24552567.14 | 70523862.80 | 77858378.04 | 4729.83 | 5195.80 | 1131.45 | 2.96 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.4625 | 0.0000 | 0.4625 | 0.1689 | 0.6314 | 0.4115 | 258.72 | 4686.43 | 894.85 |
SMSTORE1 | 0.2005 | 0.0000 | 0.2005 | 0.0942 | 0.2947 | 0.2057 | 1502.59 | 3450.74 | 886.67 |
SMSTORE2 | 0.2404 | 0.0000 | 0.2404 | 0.1236 | 0.3640 | 0.2057 | 0.00 | 3792.62 | 602.38 |
SMSTORE3 | 0.2398 | 0.0000 | 0.2398 | 0.1236 | 0.3633 | 0.2057 | 0.00 | 3811.09 | 583.91 |
SMSTORE4 | 0.2385 | 0.0000 | 0.2385 | 0.1236 | 0.3621 | 0.2057 | 0.00 | 3829.07 | 565.93 |
LGSTORE2 | 0.4718 | 0.0000 | 0.4718 | 0.2310 | 0.7028 | 0.4115 | 0.00 | 3492.80 | 537.20 |
SMSTORE5 | 0.2379 | 0.0000 | 0.2379 | 0.1317 | 0.3696 | 0.2057 | 0.00 | 3498.62 | 531.38 |
SMSTORE6 | 0.2371 | 0.0000 | 0.2371 | 0.1317 | 0.3688 | 0.2057 | 0.00 | 3509.24 | 520.76 |
SMSTORE7 | 0.2361 | 0.0000 | 0.2361 | 0.1317 | 0.3678 | 0.2057 | 0.00 | 3530.11 | 499.89 |
SMSTORE8 | 0.2408 | 0.0000 | 0.2408 | 0.1354 | 0.3762 | 0.2057 | 0.00 | 3542.60 | 487.40 |
Total Facility | 2.8055 | 0.0000 | 2.8055 | 1.3954 | 4.2008 | 2.4689 | 1606.84 | 5195.63 | 1130.82 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 14076439.46 | 0.00 | 14076439.46 | 12976396.34 | 3176.72 | 0.17 | 5583.11 | 0.00 |
PSZ-AC_2:2 | 6103012.83 | 0.00 | 6103012.83 | 6488198.17 | 4363.30 | 2.58 | 4394.12 | 0.00 |
PSZ-AC_3:3 | 5507511.34 | 0.00 | 5507511.34 | 6488198.17 | 4364.83 | 0.00 | 4395.17 | 1.33 |
PSZ-AC_4:4 | 5492297.67 | 0.00 | 5492297.67 | 6488198.17 | 4364.50 | 0.00 | 4395.50 | 2.00 |
PSZ-AC_5:5 | 5464503.28 | 0.00 | 5464503.28 | 6488198.17 | 4364.50 | 0.00 | 4395.50 | 1.67 |
PSZ-AC_6:6 | 9909937.71 | 0.00 | 9909937.71 | 12976396.34 | 4729.71 | 0.00 | 4030.29 | 0.62 |
PSZ-AC_7:7 | 4996380.89 | 0.00 | 4996380.89 | 6488198.17 | 4729.73 | 0.00 | 4030.27 | 0.44 |
PSZ-AC_8:8 | 4980969.85 | 0.00 | 4980969.85 | 6488198.17 | 4729.75 | 0.00 | 4030.25 | 0.44 |
PSZ-AC_9:9 | 4958141.18 | 0.00 | 4958141.18 | 6488198.17 | 4729.75 | 0.00 | 4030.25 | 0.25 |
PSZ-AC_10:10 | 5059090.19 | 0.00 | 5059090.19 | 6488198.17 | 4729.58 | 0.00 | 4030.42 | 0.58 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.6695 | 0.0000 | 0.6695 | 0.4115 | 256.72 | 0.17 | 5583.11 |
PSZ-AC_2:2 | 0.2903 | 0.0000 | 0.2903 | 0.2057 | 1443.30 | 2.58 | 4394.12 |
PSZ-AC_3:3 | 0.3481 | 0.0000 | 0.3481 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_4:4 | 0.3471 | 0.0000 | 0.3471 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_5:5 | 0.3453 | 0.0000 | 0.3453 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_6:6 | 0.6830 | 0.0000 | 0.6830 | 0.4115 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_7:7 | 0.3443 | 0.0000 | 0.3443 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_8:8 | 0.3433 | 0.0000 | 0.3433 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_9:9 | 0.3417 | 0.0000 | 0.3417 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_10:10 | 0.3486 | 0.0000 | 0.3486 | 0.2057 | 0.00 | 0.00 | 4030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 5101.91 | 489.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 4828.01 | 684.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 4131.43 | 264.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 4140.81 | 256.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 4154.12 | 242.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 3816.14 | 214.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 3813.54 | 216.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 3819.55 | 210.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 3827.42 | 202.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 3814.12 | 216.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.6708 | 0.9984 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.2925 | 0.4138 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 0.3373 | 0.5178 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 0.3366 | 0.5192 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 0.3355 | 0.5169 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 0.6663 | 0.9831 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.3351 | 0.5097 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.3342 | 0.5095 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.3328 | 0.5115 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.3374 | 0.5476 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 759 |
Defaulted Fields | 823 |
Fields with Defaults | 2681 |
Autosized Fields | 184 |
Autosizable Fields | 458 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1208.91 | 3115.94 | 01-JAN-07:30 | 126786.86 | 10-SEP-14:20 |
Electricity:Building | 570.24 | 1897.94 | 01-JAN-00:10 | 35612.10 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 128.86 | 354.96 | 01-JAN-00:10 | 6669.68 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 570.24 | 1897.94 | 01-JAN-00:10 | 35612.10 | 01-JAN-11:10 |
InteriorLights:Electricity | 441.52 | 1448.52 | 01-JAN-00:10 | 27522.57 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 102.50 | 280.06 | 01-JAN-00:10 | 5321.43 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 441.52 | 1448.52 | 01-JAN-00:10 | 27522.57 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 441.52 | 1448.52 | 01-JAN-00:10 | 27522.57 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 102.50 | 280.06 | 01-JAN-00:10 | 5321.43 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 441.52 | 1448.52 | 01-JAN-00:10 | 27522.57 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 69.66 | 191.80 | 01-JAN-00:10 | 3606.70 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 56.49 | 154.35 | 01-JAN-00:10 | 2932.57 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 56.49 | 154.35 | 01-JAN-00:10 | 2932.57 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 50.51 | 174.25 | 01-JAN-00:10 | 3273.35 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 40.04 | 136.80 | 01-JAN-00:10 | 2599.23 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 40.04 | 136.80 | 01-JAN-00:10 | 2599.23 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 50.51 | 174.25 | 01-JAN-00:10 | 3273.35 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 40.04 | 136.80 | 01-JAN-00:10 | 2599.23 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 40.04 | 136.80 | 01-JAN-00:10 | 2599.23 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 50.51 | 174.25 | 01-JAN-00:10 | 3273.35 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 40.04 | 136.80 | 01-JAN-00:10 | 2599.23 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 40.04 | 136.80 | 01-JAN-00:10 | 2599.23 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 72.31 | 272.07 | 01-JAN-00:10 | 5094.77 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 53.05 | 197.17 | 01-JAN-00:10 | 3746.51 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 53.05 | 197.17 | 01-JAN-00:10 | 3746.51 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 36.97 | 139.09 | 01-JAN-00:10 | 2605.22 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 36.97 | 139.09 | 01-JAN-00:10 | 2605.22 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 36.97 | 139.09 | 01-JAN-00:10 | 2605.22 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 36.97 | 139.09 | 01-JAN-00:10 | 2605.22 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.36 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.36 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.18 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.18 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.26 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.26 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
ElectricityPurchased:Facility | 1208.91 | 3115.94 | 01-JAN-07:30 | 126786.86 | 10-SEP-14:20 |
ElectricityPurchased:Plant | 1208.91 | 3115.94 | 01-JAN-07:30 | 126786.86 | 10-SEP-14:20 |
Cogeneration:ElectricityPurchased | 1208.91 | 3115.94 | 01-JAN-07:30 | 126786.86 | 10-SEP-14:20 |
General:Cogeneration:ElectricityPurchased | 1208.91 | 3115.94 | 01-JAN-07:30 | 126786.86 | 10-SEP-14:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1208.91 | 3115.94 | 01-JAN-07:30 | 126786.86 | 10-SEP-14:20 |
ElectricityNet:Plant | 1208.91 | 3115.94 | 01-JAN-07:30 | 126786.86 | 10-SEP-14:20 |
Cogeneration:ElectricityNet | 1208.91 | 3115.94 | 01-JAN-07:30 | 126786.86 | 10-SEP-14:20 |
General:Cogeneration:ElectricityNet | 1208.91 | 3115.94 | 01-JAN-07:30 | 126786.86 | 10-SEP-14:20 |
Electricity:HVAC | 478.84 | 0.00 | 01-JAN-00:10 | 86283.45 | 10-SEP-12:50 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 371.07 | 0.00 | 01-JAN-00:10 | 74511.00 | 10-SEP-13:30 |
General:Cooling:Electricity | 371.07 | 0.00 | 01-JAN-00:10 | 74511.00 | 10-SEP-13:30 |
Fans:Electricity | 107.77 | 0.00 | 01-JAN-00:10 | 11796.00 | 10-SEP-13:00 |
General:Fans:Electricity | 107.77 | 0.00 | 01-JAN-00:10 | 11796.00 | 10-SEP-13:00 |
ExteriorLights:Electricity | 99.82 | 0.00 | 01-JAN-07:30 | 7619.51 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 99.82 | 0.00 | 01-JAN-07:30 | 7619.51 | 01-JAN-06:10 |
Electricity:Plant | 60.01 | 1218.00 | 10-JAN-09:10 | 11817.66 | 04-JAN-15:00 |
WaterSystems:Electricity | 60.01 | 1218.00 | 10-JAN-09:10 | 11817.66 | 04-JAN-15:00 |
Water Heater:WaterSystems:Electricity | 60.01 | 1218.00 | 10-JAN-09:10 | 11817.66 | 04-JAN-15:00 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 14.21 | 0.00 | 01-JAN-00:10 | 96522.95 | 05-FEB-10:10 |
NaturalGas:HVAC | 14.21 | 0.00 | 01-JAN-00:10 | 96522.95 | 05-FEB-10:10 |
Heating:NaturalGas | 14.21 | 0.00 | 01-JAN-00:10 | 96522.95 | 05-FEB-10:10 |
General:Heating:NaturalGas | 14.21 | 0.00 | 01-JAN-00:10 | 96522.95 | 05-FEB-10:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2372.08 | 0.00 | 01-JAN-00:10 | 420567.26 | 10-SEP-13:00 |
EnergyTransfer:Building | 832.15 | 0.00 | 01-JAN-00:10 | 125586.58 | 10-SEP-14:10 |
EnergyTransfer:Zone:LGSTORE1 | 172.91 | 0.00 | 01-JAN-00:10 | 20444.75 | 10-SEP-15:00 |
Heating:EnergyTransfer | 10.74 | 0.00 | 01-JAN-00:10 | 40319.00 | 21-DEC-09:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 1.25 | 0.00 | 01-JAN-00:10 | 12131.85 | 05-FEB-09:10 |
General:Heating:EnergyTransfer | 10.74 | 0.00 | 01-JAN-00:10 | 40319.00 | 21-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 1.25 | 0.00 | 01-JAN-00:10 | 12131.85 | 05-FEB-09:10 |
Cooling:EnergyTransfer | 821.40 | 0.00 | 01-JAN-00:10 | 125586.58 | 10-SEP-14:10 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 171.66 | 0.00 | 01-JAN-00:10 | 20444.75 | 10-SEP-15:00 |
General:Cooling:EnergyTransfer | 821.40 | 0.00 | 01-JAN-00:10 | 125586.58 | 10-SEP-14:10 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 171.66 | 0.00 | 01-JAN-00:10 | 20444.75 | 10-SEP-15:00 |
EnergyTransfer:Zone:SMSTORE1 | 90.14 | 0.00 | 01-JAN-00:10 | 10480.53 | 10-SEP-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 0.60 | 0.00 | 01-JAN-00:10 | 2238.80 | 05-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 0.60 | 0.00 | 01-JAN-00:10 | 2238.80 | 05-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 89.54 | 0.00 | 01-JAN-00:10 | 10480.53 | 10-SEP-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 89.54 | 0.00 | 01-JAN-00:10 | 10480.53 | 10-SEP-13:00 |
EnergyTransfer:Zone:SMSTORE2 | 68.21 | 0.00 | 01-JAN-00:10 | 10414.16 | 10-SEP-14:00 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 1.07 | 0.00 | 01-JAN-00:10 | 4014.43 | 05-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 1.07 | 0.00 | 01-JAN-00:10 | 4014.43 | 05-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 67.13 | 0.00 | 01-JAN-00:10 | 10414.16 | 10-SEP-14:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 67.13 | 0.00 | 01-JAN-00:10 | 10414.16 | 10-SEP-14:00 |
EnergyTransfer:Zone:SMSTORE3 | 67.96 | 0.00 | 01-JAN-00:10 | 10481.01 | 10-SEP-14:00 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 1.07 | 0.00 | 01-JAN-00:10 | 4830.97 | 05-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 1.07 | 0.00 | 01-JAN-00:10 | 4830.97 | 05-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 66.89 | 0.00 | 01-JAN-00:10 | 10481.01 | 10-SEP-14:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 66.89 | 0.00 | 01-JAN-00:10 | 10481.01 | 10-SEP-14:00 |
EnergyTransfer:Zone:SMSTORE4 | 66.43 | 0.00 | 01-JAN-00:10 | 10422.15 | 10-SEP-14:00 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 1.12 | 0.00 | 01-JAN-00:10 | 5521.86 | 05-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 1.12 | 0.00 | 01-JAN-00:10 | 5521.86 | 05-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 65.32 | 0.00 | 01-JAN-00:10 | 10422.15 | 10-SEP-14:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 65.32 | 0.00 | 01-JAN-00:10 | 10422.15 | 10-SEP-14:00 |
EnergyTransfer:Zone:LGSTORE2 | 118.32 | 0.00 | 01-JAN-00:10 | 19887.62 | 10-SEP-14:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 1.62 | 0.00 | 01-JAN-00:10 | 8044.79 | 13-MAR-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 1.62 | 0.00 | 01-JAN-00:10 | 8044.79 | 13-MAR-08:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 116.70 | 0.00 | 01-JAN-00:10 | 19887.62 | 10-SEP-14:10 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 116.70 | 0.00 | 01-JAN-00:10 | 19887.62 | 10-SEP-14:10 |
EnergyTransfer:Zone:SMSTORE5 | 61.59 | 0.00 | 01-JAN-00:10 | 10589.15 | 10-SEP-14:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 0.89 | 0.00 | 01-JAN-00:10 | 4284.78 | 06-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 0.89 | 0.00 | 01-JAN-00:10 | 4284.78 | 06-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 60.70 | 0.00 | 01-JAN-00:10 | 10589.15 | 10-SEP-14:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 60.70 | 0.00 | 01-JAN-00:10 | 10589.15 | 10-SEP-14:10 |
EnergyTransfer:Zone:SMSTORE6 | 60.96 | 0.00 | 01-JAN-00:10 | 10556.18 | 10-SEP-14:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 0.90 | 0.00 | 01-JAN-00:10 | 4355.77 | 13-MAR-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 0.90 | 0.00 | 01-JAN-00:10 | 4355.77 | 13-MAR-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 60.06 | 0.00 | 01-JAN-00:10 | 10556.18 | 10-SEP-14:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 60.06 | 0.00 | 01-JAN-00:10 | 10556.18 | 10-SEP-14:10 |
EnergyTransfer:Zone:SMSTORE7 | 60.01 | 0.00 | 01-JAN-00:10 | 10639.86 | 10-SEP-14:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 0.96 | 0.00 | 01-JAN-00:10 | 5798.64 | 06-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 0.96 | 0.00 | 01-JAN-00:10 | 5798.64 | 06-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 59.05 | 0.00 | 01-JAN-00:10 | 10639.86 | 10-SEP-14:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 59.05 | 0.00 | 01-JAN-00:10 | 10639.86 | 10-SEP-14:10 |
EnergyTransfer:Zone:SMSTORE8 | 65.61 | 0.00 | 01-JAN-00:10 | 12295.67 | 10-SEP-14:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 1.26 | 0.00 | 01-JAN-00:10 | 9128.11 | 21-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 1.26 | 0.00 | 01-JAN-00:10 | 9128.11 | 21-DEC-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 64.35 | 0.00 | 01-JAN-00:10 | 12295.67 | 10-SEP-14:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 64.35 | 0.00 | 01-JAN-00:10 | 12295.67 | 10-SEP-14:10 |
EnergyTransfer:HVAC | 1539.93 | 0.00 | 01-JAN-00:10 | 297297.92 | 10-SEP-13:00 |
HeatingCoils:EnergyTransfer | 11.37 | 0.00 | 01-JAN-00:10 | 77218.36 | 05-FEB-10:10 |
CoolingCoils:EnergyTransfer | 1528.57 | 0.00 | 01-JAN-00:10 | 297297.92 | 10-SEP-13:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 1.254 | -171.654 | 0.000 | 0.000 | 23.527 | 102.498 | 26.357 | 19.375 | 0.000 | 14.094 | 0.548 | 0.000 | -5.216 | 0.000 | -10.784 | -0.001 |
SMSTORE1 | 0.000 | 0.000 | 0.600 | -89.538 | 0.000 | 0.000 | 11.707 | 56.486 | 13.179 | 9.658 | 0.000 | 7.913 | 0.001 | 0.000 | -2.689 | 0.000 | -5.587 | -1.729 |
SMSTORE2 | 0.000 | 0.000 | 1.074 | -67.131 | 0.000 | 0.000 | 7.070 | 40.039 | 10.467 | 9.609 | 0.000 | 7.790 | 0.000 | 0.000 | -2.777 | 0.000 | -5.673 | -0.467 |
SMSTORE3 | 0.000 | 0.000 | 1.072 | -66.885 | 0.000 | 0.000 | 7.075 | 40.039 | 10.467 | 9.614 | 0.000 | 7.788 | 0.001 | 0.000 | -2.765 | 0.000 | -5.639 | -0.766 |
SMSTORE4 | 0.000 | 0.000 | 1.116 | -65.314 | 0.000 | 0.000 | 7.082 | 40.039 | 10.467 | 9.628 | 0.000 | 7.791 | 0.000 | 0.000 | -2.729 | 0.000 | -5.586 | -2.493 |
LGSTORE2 | 0.000 | 0.000 | 1.616 | -116.702 | 0.000 | 0.000 | 24.300 | 53.048 | 19.261 | 19.290 | 0.000 | 13.600 | 0.942 | 0.000 | -5.293 | 0.000 | -10.062 | -0.000 |
SMSTORE5 | 0.000 | 0.000 | 0.885 | -60.702 | 0.000 | 0.000 | 12.154 | 27.343 | 9.631 | 9.646 | 0.000 | 7.758 | 1.504 | 0.000 | -2.625 | 0.000 | -5.594 | -0.000 |
SMSTORE6 | 0.000 | 0.000 | 0.900 | -60.061 | 0.000 | 0.000 | 12.160 | 27.343 | 9.631 | 9.655 | 0.000 | 7.759 | 0.791 | 0.000 | -2.609 | 0.000 | -5.568 | -0.000 |
SMSTORE7 | 0.000 | 0.000 | 0.965 | -59.047 | 0.000 | 0.000 | 12.174 | 27.343 | 9.631 | 9.670 | 0.000 | 7.761 | 0.002 | 0.000 | -2.574 | 0.000 | -5.497 | -0.425 |
SMSTORE8 | 0.000 | 0.000 | 1.262 | -64.344 | 0.000 | 0.000 | 12.190 | 27.343 | 9.631 | 9.656 | 0.000 | 7.953 | 5.409 | 0.000 | -2.468 | 0.000 | -6.632 | -0.001 |
Total Facility | 0.000 | 0.000 | 10.745 | -821.379 | 0.000 | 0.000 | 129.438 | 441.522 | 128.721 | 115.800 | 0.000 | 90.207 | 9.199 | 0.000 | -31.745 | 0.000 | -66.622 | -5.882 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | -51528.24 | 0.00 | 0.00 | 165.01 | 2800.74 | 749.03 | 399.88 | 0.00 | 0.00 | 47743.89 | 0.00 | -0.00 | 0.00 | -330.32 | 0.00 |
SMSTORE1 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | -27200.61 | 0.00 | 0.00 | 81.97 | 1543.46 | 374.52 | 198.03 | 0.00 | 0.00 | 25174.69 | 0.00 | -0.00 | 0.00 | -172.06 | 0.00 |
SMSTORE2 | 17-OCT-07:02 | 0.00 | 0.00 | 0.00 | -28883.93 | 0.00 | 0.00 | 85.73 | 1368.01 | 374.52 | 0.00 | 0.00 | 0.00 | 27601.50 | 0.00 | -151.12 | 0.00 | -394.71 | 0.00 |
SMSTORE3 | 17-OCT-07:02 | 0.00 | 0.00 | 0.00 | -29005.72 | 0.00 | 0.00 | 85.43 | 1368.01 | 374.52 | 0.00 | 0.00 | 0.00 | 27726.11 | 0.00 | -152.13 | 0.00 | -396.23 | 0.00 |
SMSTORE4 | 17-OCT-07:02 | 0.00 | 0.00 | 0.00 | -28809.99 | 0.00 | 0.00 | 86.03 | 1368.01 | 374.52 | 0.00 | 0.00 | 0.00 | 27525.10 | 0.00 | -150.65 | 0.00 | -393.02 | 0.00 |
LGSTORE2 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | -48043.10 | 0.00 | 0.00 | 366.96 | 1971.84 | 749.03 | 399.89 | 0.00 | 0.00 | 44855.64 | 0.00 | -0.00 | 0.00 | -300.27 | 0.00 |
SMSTORE5 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | -25133.70 | 0.00 | 0.00 | 184.44 | 1016.37 | 374.52 | 200.21 | 0.00 | 0.00 | 23522.84 | 0.00 | -0.00 | 0.00 | -164.67 | 0.00 |
SMSTORE6 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | -24999.86 | 0.00 | 0.00 | 184.86 | 1016.37 | 374.52 | 200.81 | 0.00 | 0.00 | 23387.07 | 0.00 | -0.00 | 0.00 | -163.78 | 0.00 |
SMSTORE7 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | -25003.88 | 0.00 | 0.00 | 185.67 | 1016.37 | 374.52 | 201.27 | 0.00 | 0.00 | 23387.51 | 0.00 | -0.00 | 0.00 | -161.47 | 0.00 |
SMSTORE8 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | -28434.90 | 0.00 | 0.00 | 185.77 | 1016.37 | 374.52 | 201.42 | 0.00 | 0.00 | 26835.70 | 0.00 | -0.00 | 0.00 | -178.87 | 0.00 |
Total Facility | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | -241521.74 | 0.00 | 0.00 | 1945.70 | 18179.18 | 5393.02 | 2460.95 | 0.00 | 0.00 | 215367.55 | 0.00 | 0.00 | 0.00 | -1824.66 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 06-FEB-09:01 | 0.00 | 0.00 | 53218.73 | 0.00 | 0.00 | 0.00 | 243.54 | 2800.74 | 749.03 | 1304.51 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1161.93 | -57154.62 |
SMSTORE1 | 21-DEC-09:01 | 0.00 | 0.00 | 9232.83 | 0.00 | 0.00 | 0.00 | 117.55 | 1543.46 | 374.52 | 15.32 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -651.93 | -10631.74 |
SMSTORE2 | 05-FEB-09:02 | 0.00 | 0.00 | 16342.43 | 0.00 | 0.00 | 0.00 | 120.96 | 1368.01 | 374.52 | 595.83 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1017.42 | -17784.34 |
SMSTORE3 | 05-FEB-09:02 | 0.00 | 0.00 | 19284.23 | 0.00 | 0.00 | 0.00 | 121.91 | 1368.01 | 374.52 | 599.89 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1016.75 | -20731.81 |
SMSTORE4 | 05-FEB-09:02 | 0.00 | 0.00 | 21767.09 | 0.00 | 0.00 | 0.00 | 122.69 | 1368.01 | 374.52 | 602.95 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1016.18 | -23219.09 |
LGSTORE2 | 12-MAR-09:01 | 0.00 | 0.00 | 51287.73 | 0.00 | 0.00 | 0.00 | 536.08 | 1971.84 | 749.03 | 912.83 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -729.54 | -54727.98 |
SMSTORE5 | 13-MAR-08:61 | 0.00 | 0.00 | 26490.42 | 0.00 | 0.00 | 0.00 | 268.35 | 1016.37 | 374.52 | 128.21 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -437.28 | -27840.58 |
SMSTORE6 | 12-MAR-09:01 | 0.00 | 0.00 | 27108.12 | 0.00 | 0.00 | 0.00 | 269.46 | 1016.37 | 374.52 | 457.97 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -410.31 | -28816.11 |
SMSTORE7 | 12-MAR-09:01 | 0.00 | 0.00 | 27266.58 | 0.00 | 0.00 | 0.00 | 273.71 | 1016.37 | 374.52 | 466.01 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -394.73 | -29002.45 |
SMSTORE8 | 12-MAR-09:01 | 0.00 | 0.00 | 30862.42 | 0.00 | 0.00 | 0.00 | 283.58 | 1016.37 | 374.52 | 485.62 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -399.06 | -32623.44 |
Total Facility | 21-DEC-09:01 | -61.40 | 61.40 | 220350.07 | -61.40 | 0.00 | 0.00 | 2688.74 | 18179.18 | 5393.02 | 384.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7483.31 | -239450.66 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.2523 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.2523 | 0.1827 | 1.0000 | Not calculated | 0.4115 | 0.1827 | ||
PSZ-AC_2:2 | 1.1644 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1644 | 0.1767 | 1.0000 | Not calculated | 0.2057 | 0.1767 | ||
PSZ-AC_3:3 | 1.1599 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1599 | 0.1774 | 1.0000 | Not calculated | 0.2057 | 0.1774 | ||
PSZ-AC_4:4 | 1.1631 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1631 | 0.1769 | 1.0000 | Not calculated | 0.2057 | 0.1769 | ||
PSZ-AC_5:5 | 1.1590 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1590 | 0.1775 | 1.0000 | Not calculated | 0.2057 | 0.1775 | ||
PSZ-AC_6:6 | 2.1224 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.1224 | 0.1939 | 1.0000 | Not calculated | 0.4115 | 0.1939 | ||
PSZ-AC_7:7 | 1.1157 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1157 | 0.1844 | 1.0000 | Not calculated | 0.2057 | 0.1844 | ||
PSZ-AC_8:8 | 1.1110 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1110 | 0.1852 | 1.0000 | Not calculated | 0.2057 | 0.1852 | ||
PSZ-AC_9:9 | 1.1141 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1141 | 0.1847 | 1.0000 | Not calculated | 0.2057 | 0.1847 | ||
PSZ-AC_10:10 | 1.2741 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2741 | 0.1615 | 1.0000 | Not calculated | 0.2057 | 0.1615 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.2523 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.2523 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.1827 | ||
PSZ-AC_2:2 | 1.1644 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1644 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1767 | ||
PSZ-AC_3:3 | 1.1599 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1599 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1774 | ||
PSZ-AC_4:4 | 1.1631 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1631 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1769 | ||
PSZ-AC_5:5 | 1.1590 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1590 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1775 | ||
PSZ-AC_6:6 | 2.1224 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.1224 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.1939 | ||
PSZ-AC_7:7 | 1.1157 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1157 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1844 | ||
PSZ-AC_8:8 | 1.1110 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1110 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1852 | ||
PSZ-AC_9:9 | 1.1141 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1141 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1847 | ||
PSZ-AC_10:10 | 1.2741 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2741 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1615 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.2523 | 2.2523 | 2.2523 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1644 | 1.1644 | 1.1644 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1599 | 1.1599 | 1.1599 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1631 | 1.1631 | 1.1631 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1590 | 1.1590 | 1.1590 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.1224 | 2.1224 | 2.1224 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1157 | 1.1157 | 1.1157 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1110 | 1.1110 | 1.1110 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1141 | 1.1141 | 1.1141 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2741 | 1.2741 | 1.2741 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.2523 | 2.2523 | 2.2523 | 2.2523 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.1644 | 1.1644 | 1.1644 | 1.1644 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.1599 | 1.1599 | 1.1599 | 1.1599 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.1631 | 1.1631 | 1.1631 | 1.1631 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.1590 | 1.1590 | 1.1590 | 1.1590 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.1224 | 2.1224 | 2.1224 | 2.1224 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.1157 | 1.1157 | 1.1157 | 1.1157 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.1110 | 1.1110 | 1.1110 | 1.1110 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.1141 | 1.1141 | 1.1141 | 1.1141 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.2741 | 1.2741 | 1.2741 | 1.2741 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.2523 | 2.2523 | 2.2523 | No | 0.4115 | 0.4914 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1644 | 1.1644 | 1.1644 | No | 0.2057 | 0.4965 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1599 | 1.1599 | 1.1599 | No | 0.2057 | 0.4922 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1631 | 1.1631 | 1.1631 | No | 0.2057 | 0.4880 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1590 | 1.1590 | 1.1590 | No | 0.2057 | 0.4795 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.1224 | 2.1224 | 2.1224 | No | 0.4115 | 0.5090 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1157 | 1.1157 | 1.1157 | No | 0.2057 | 0.4680 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1110 | 1.1110 | 1.1110 | No | 0.2057 | 0.4677 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1141 | 1.1141 | 1.1141 | No | 0.2057 | 0.4545 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2741 | 1.2741 | 1.2741 | No | 0.2057 | 0.3859 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.2523 | 2.2523 | 2.2523 | 2.2523 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.1644 | 1.1644 | 1.1644 | 1.1644 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.1599 | 1.1599 | 1.1599 | 1.1599 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.1631 | 1.1631 | 1.1631 | 1.1631 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.1590 | 1.1590 | 1.1590 | 1.1590 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.1224 | 2.1224 | 2.1224 | 2.1224 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.1157 | 1.1157 | 1.1157 | 1.1157 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.1110 | 1.1110 | 1.1110 | 1.1110 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.1141 | 1.1141 | 1.1141 | 1.1141 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.2741 | 1.2741 | 1.2741 | 1.2741 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 9.00 |
Number of hours not met | 9.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 14.21 | 96522.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 371.07 | 74511.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 441.52 | 27522.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 99.82 | 7619.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.72 | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 107.77 | 11796.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 60.01 | 11817.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.72 | 1208.91 |
Natural Gas | 0.00 | 14.21 |
Additional | 0.00 | 0.00 |
Total | 128.72 | 1223.12 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 211.22 |
Space Heating | 0.00 |
Space Cooling | 177.52 |
Fans (All) | 51.56 |
Service Water Heating | 28.71 |
Receptacle Equipment | 61.58 |
Miscellaneous (All) | 578.34 |
Subtotal | 578.34 |
Natural Gas [MJ/m2] | |
Space Heating | 6.80 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 6.80 |
Subtotal | 6.80 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 36.10 |
Space Heating | 1.16 |
Space Cooling | 30.34 |
Fans (All) | 8.81 |
Service Water Heating | 4.91 |
Receptacle Equipment | 10.52 |
Miscellaneous | 8.16 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3238. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3296. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 4469. | 8760. |
LTG_SCH_BASE_LPD1 | 4391. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 3584. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4888. | 8760. |
TYPE2_EQUIP_SCH | 3911. | 8760. |
TYPE3_EQUIP_SCH | 3600. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2505. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 8704.00 | 56.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8739.33 | 20.67 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 7681.67 | 1078.17 | 0.17 | 0.00 | 0.00 |
SMSTORE3 | 7563.17 | 1196.67 | 0.17 | 0.00 | 0.00 |
SMSTORE4 | 7777.83 | 982.00 | 0.17 | 0.00 | 0.00 |
LGSTORE2 | 8145.50 | 614.33 | 0.17 | 0.00 | 0.00 |
SMSTORE5 | 8168.33 | 591.50 | 0.17 | 0.00 | 0.00 |
SMSTORE6 | 8179.33 | 580.50 | 0.17 | 0.00 | 0.00 |
SMSTORE7 | 8209.33 | 550.50 | 0.17 | 0.00 | 0.00 |
SMSTORE8 | 8118.50 | 641.17 | 0.33 | 0.00 | 0.00 |
Min | 7563.17 | 20.67 | 0.00 | 0.00 | 0.00 |
Max | 8739.33 | 1196.67 | 0.33 | 0.00 | 0.00 |
Average | 8128.70 | 631.15 | 0.15 | 0.00 | 0.00 |
Sum | 81287.00 | 6311.50 | 1.50 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 88971.67 | 69.33 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43764.67 | 12.33 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25399.67 | 75.17 | 0.17 | 0.00 | 0.00 |
SMSTORE3 | 25399.33 | 75.50 | 0.17 | 0.00 | 0.00 |
SMSTORE4 | 25403.33 | 71.50 | 0.17 | 0.00 | 0.00 |
LGSTORE2 | 93008.00 | 202.00 | 1.00 | 0.00 | 0.00 |
SMSTORE5 | 45809.50 | 102.00 | 0.50 | 0.00 | 0.00 |
SMSTORE6 | 45810.50 | 101.00 | 0.50 | 0.00 | 0.00 |
SMSTORE7 | 45811.00 | 100.50 | 0.50 | 0.00 | 0.00 |
SMSTORE8 | 45801.00 | 110.50 | 0.50 | 0.00 | 0.00 |
Min | 25399.33 | 12.33 | 0.00 | 0.00 | 0.00 |
Max | 93008.00 | 202.00 | 1.00 | 0.00 | 0.00 |
Average | 48517.87 | 91.98 | 0.35 | 0.00 | 0.00 |
Sum | 485178.67 | 919.83 | 3.50 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 5681.33 | 3078.67 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 7332.00 | 1428.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 4596.17 | 4163.83 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 4626.17 | 4133.83 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 4599.00 | 4161.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 4473.50 | 4286.50 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 4495.50 | 4264.50 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 4482.50 | 4277.50 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 4475.50 | 4284.50 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 4691.00 | 4069.00 | 0.00 | 0.00 | 0.00 |
Min | 4473.50 | 1428.00 | 0.00 | 0.00 | 0.00 |
Max | 7332.00 | 4286.50 | 0.00 | 0.00 | 0.00 |
Average | 4945.27 | 3814.73 | 0.00 | 0.00 | 0.00 |
Sum | 49452.67 | 38147.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 73757.17 | 15283.83 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 36704.83 | 7072.17 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 19256.17 | 6218.83 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 19337.00 | 6138.00 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 19077.83 | 6397.17 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 64388.33 | 28822.67 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 31465.50 | 14446.50 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 31237.83 | 14674.17 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 31025.67 | 14886.33 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 33334.67 | 12577.33 | 0.00 | 0.00 | 0.00 |
Min | 19077.83 | 6138.00 | 0.00 | 0.00 | 0.00 |
Max | 73757.17 | 28822.67 | 0.00 | 0.00 | 0.00 |
Average | 35958.50 | 12651.70 | 0.00 | 0.00 | 0.00 |
Sum | 359585.00 | 126517.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Environment
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
For: Environment
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
For: Environment
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.816062E+10 | 31169.26 | 19-JAN-09:02 | 21.33 | 20.42 | 0.128831E+10 | 1685.94 | 15-JAN-17:19 | 21.33 | 20.42 |
February | 0.778141E+10 | 36177.31 | 28-FEB-09:02 | 20.08 | 18.60 | 0.120341E+10 | 1685.91 | 19-FEB-13:30 | 20.08 | 18.60 |
March | 0.900050E+10 | 34524.52 | 30-MAR-08:62 | 21.78 | 19.48 | 0.133894E+10 | 1686.03 | 05-MAR-13:00 | 21.78 | 19.48 |
April | 0.119261E+11 | 34977.23 | 25-APR-08:62 | 22.07 | 18.96 | 0.136103E+10 | 1686.04 | 22-APR-12:30 | 22.07 | 18.96 |
May | 0.178080E+11 | 36058.76 | 07-MAY-07:02 | 24.60 | 22.15 | 0.140373E+10 | 1686.08 | 19-MAY-12:39 | 32.60 | 23.69 |
June | 0.185789E+11 | 36648.36 | 11-JUN-07:02 | 23.58 | 20.40 | 0.135685E+10 | 1686.04 | 25-JUN-12:20 | 30.73 | 24.69 |
July | 0.196405E+11 | 36332.95 | 09-JUL-07:01 | 28.48 | 25.79 | 0.141520E+10 | 1686.07 | 08-JUL-12:09 | 28.48 | 25.79 |
August | 0.204815E+11 | 37959.62 | 20-AUG-07:02 | 24.17 | 22.66 | 0.139687E+10 | 1686.07 | 25-AUG-12:30 | 29.10 | 24.37 |
September | 0.184195E+11 | 35202.28 | 22-SEP-08:62 | 23.58 | 20.80 | 0.136734E+10 | 1686.05 | 23-SEP-12:20 | 30.70 | 24.24 |
October | 0.182524E+11 | 51551.80 | 26-OCT-08:61 | 21.18 | 12.94 | 0.141126E+10 | 1686.09 | 09-OCT-12:20 | 21.18 | 12.94 |
November | 0.118818E+11 | 38491.33 | 06-NOV-09:02 | 22.47 | 19.37 | 0.135868E+10 | 1686.06 | 03-NOV-12:00 | 22.47 | 19.37 |
December | 0.972544E+10 | 40653.78 | 17-DEC-08:62 | 19.83 | 15.88 | 0.134846E+10 | 1686.03 | 10-DEC-13:30 | 19.83 | 15.88 |
Annual Sum or Average | 0.171657E+12 | 0.162501E+11 | ||||||||
Minimum of Months | 0.778141E+10 | 31169.26 | 19.83 | 12.94 | 0.120341E+10 | 1685.91 | 19.83 | 12.94 | ||
Maximum of Months | 0.204815E+11 | 51551.80 | 28.48 | 25.79 | 0.141520E+10 | 1686.09 | 32.60 | 25.79 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.398536E+10 | 17394.03 | 02-JAN-09:02 | 18.33 | 16.37 | 0.667268E+09 | 843.05 | 01-JAN-18:00 | 18.33 | 16.37 |
February | 0.409074E+10 | 20934.51 | 28-FEB-09:02 | 20.08 | 18.60 | 0.614131E+09 | 842.99 | 24-FEB-13:39 | 20.08 | 18.60 |
March | 0.482697E+10 | 20778.75 | 30-MAR-08:62 | 21.78 | 19.48 | 0.679795E+09 | 843.00 | 05-MAR-18:19 | 21.78 | 19.48 |
April | 0.651186E+10 | 20568.95 | 24-APR-08:62 | 19.50 | 19.50 | 0.679742E+09 | 843.14 | 23-APR-17:19 | 19.50 | 19.50 |
May | 0.942109E+10 | 21600.92 | 07-MAY-07:02 | 24.60 | 22.15 | 0.701954E+09 | 843.12 | 21-MAY-17:30 | 27.50 | 22.92 |
June | 0.969317E+10 | 21221.77 | 11-JUN-07:02 | 23.58 | 20.40 | 0.678484E+09 | 843.04 | 04-JUN-17:40 | 23.58 | 20.40 |
July | 0.101970E+11 | 21812.43 | 09-JUL-07:01 | 28.48 | 25.79 | 0.707625E+09 | 843.02 | 08-JUL-12:09 | 28.48 | 25.79 |
August | 0.104481E+11 | 22120.32 | 20-AUG-07:02 | 24.17 | 22.66 | 0.698441E+09 | 843.05 | 06-AUG-17:30 | 24.17 | 22.66 |
September | 0.947684E+10 | 20953.21 | 03-SEP-07:02 | 26.78 | 24.09 | 0.683689E+09 | 842.99 | 08-SEP-12:00 | 28.30 | 25.04 |
October | 0.943922E+10 | 27209.94 | 26-OCT-08:61 | 21.18 | 12.94 | 0.705289E+09 | 843.07 | 01-OCT-17:49 | 21.18 | 12.94 |
November | 0.637525E+10 | 22248.82 | 06-NOV-09:02 | 22.47 | 19.37 | 0.679959E+09 | 843.09 | 05-NOV-17:40 | 22.47 | 19.37 |
December | 0.507415E+10 | 22118.95 | 17-DEC-08:62 | 19.83 | 15.88 | 0.684274E+09 | 843.17 | 10-DEC-18:19 | 19.83 | 15.88 |
Annual Sum or Average | 0.895398E+11 | 0.818065E+10 | ||||||||
Minimum of Months | 0.398536E+10 | 17394.03 | 18.33 | 12.94 | 0.614131E+09 | 842.99 | 18.33 | 12.94 | ||
Maximum of Months | 0.104481E+11 | 27209.94 | 28.48 | 25.79 | 0.707625E+09 | 843.17 | 28.48 | 25.79 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.298393E+10 | 22878.87 | 02-JAN-08:62 | 15.50 | 14.72 | 0.384144E+09 | 842.94 | 28-JAN-13:00 | 22.00 | 13.62 |
February | 0.295190E+10 | 19027.03 | 28-FEB-08:62 | 19.50 | 18.32 | 0.361674E+09 | 842.90 | 25-FEB-13:09 | 19.50 | 18.32 |
March | 0.350191E+10 | 18225.26 | 27-MAR-07:02 | 20.18 | 18.99 | 0.412977E+09 | 842.93 | 04-MAR-13:09 | 20.18 | 18.99 |
April | 0.465553E+10 | 19189.95 | 25-APR-07:02 | 20.27 | 17.95 | 0.410162E+09 | 842.99 | 22-APR-12:30 | 20.27 | 17.95 |
May | 0.718334E+10 | 18843.78 | 12-MAY-07:01 | 23.98 | 20.89 | 0.426685E+09 | 842.97 | 27-MAY-12:00 | 26.70 | 23.11 |
June | 0.749686E+10 | 18618.58 | 12-JUN-07:01 | 25.18 | 21.23 | 0.417685E+09 | 842.97 | 03-JUN-12:00 | 25.18 | 21.23 |
July | 0.771558E+10 | 16363.17 | 19-JUL-07:01 | 28.07 | 25.39 | 0.420852E+09 | 843.01 | 01-JUL-12:39 | 28.07 | 25.39 |
August | 0.811367E+10 | 18474.10 | 31-AUG-07:01 | 25.45 | 23.81 | 0.432391E+09 | 843.01 | 12-AUG-12:39 | 25.45 | 23.81 |
September | 0.714421E+10 | 18328.68 | 23-SEP-07:01 | 23.08 | 21.03 | 0.411465E+09 | 843.00 | 09-SEP-12:09 | 23.08 | 21.03 |
October | 0.710397E+10 | 28900.84 | 17-OCT-07:02 | 15.17 | 9.88 | 0.420802E+09 | 842.98 | 21-OCT-12:09 | 28.03 | 25.07 |
November | 0.461033E+10 | 19594.51 | 06-NOV-08:62 | 20.78 | 18.75 | 0.404310E+09 | 842.95 | 25-NOV-13:09 | 20.42 | 14.33 |
December | 0.367216E+10 | 23504.41 | 17-DEC-09:02 | 19.00 | 14.29 | 0.396944E+09 | 842.99 | 02-DEC-13:30 | 19.00 | 14.29 |
Annual Sum or Average | 0.671334E+11 | 0.490009E+10 | ||||||||
Minimum of Months | 0.295190E+10 | 16363.17 | 15.17 | 9.88 | 0.361674E+09 | 842.90 | 19.00 | 13.62 | ||
Maximum of Months | 0.811367E+10 | 28900.84 | 28.07 | 25.39 | 0.432391E+09 | 843.01 | 28.07 | 25.39 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.286550E+10 | 22936.18 | 02-JAN-08:62 | 15.50 | 14.72 | 0.381953E+09 | 842.94 | 28-JAN-13:00 | 22.00 | 13.62 |
February | 0.285546E+10 | 19037.83 | 28-FEB-08:62 | 19.50 | 18.32 | 0.360573E+09 | 842.90 | 25-FEB-13:09 | 19.50 | 18.32 |
March | 0.341460E+10 | 18244.53 | 27-MAR-07:02 | 20.18 | 18.99 | 0.412221E+09 | 842.93 | 04-MAR-13:09 | 20.18 | 18.99 |
April | 0.461737E+10 | 19248.03 | 25-APR-07:02 | 20.27 | 17.95 | 0.410119E+09 | 842.99 | 22-APR-12:30 | 20.27 | 17.95 |
May | 0.721005E+10 | 18941.29 | 12-MAY-07:01 | 23.98 | 20.89 | 0.426689E+09 | 842.97 | 27-MAY-12:00 | 26.70 | 23.11 |
June | 0.753389E+10 | 18714.67 | 12-JUN-07:01 | 25.18 | 21.23 | 0.417691E+09 | 842.97 | 03-JUN-12:00 | 25.18 | 21.23 |
July | 0.776833E+10 | 16440.64 | 19-JUL-07:01 | 28.07 | 25.39 | 0.420857E+09 | 843.00 | 01-JUL-12:39 | 28.07 | 25.39 |
August | 0.815665E+10 | 18542.49 | 31-AUG-07:01 | 25.45 | 23.81 | 0.432396E+09 | 843.00 | 12-AUG-12:39 | 25.45 | 23.81 |
September | 0.718665E+10 | 18413.01 | 23-SEP-07:01 | 23.08 | 21.03 | 0.411470E+09 | 843.00 | 09-SEP-12:09 | 23.08 | 21.03 |
October | 0.713327E+10 | 29022.72 | 17-OCT-07:02 | 15.17 | 9.88 | 0.420803E+09 | 842.98 | 21-OCT-12:09 | 28.03 | 25.07 |
November | 0.456012E+10 | 19693.65 | 06-NOV-08:62 | 20.78 | 18.75 | 0.404187E+09 | 842.95 | 25-NOV-13:00 | 20.00 | 14.21 |
December | 0.358575E+10 | 23580.44 | 17-DEC-09:02 | 19.00 | 14.29 | 0.396034E+09 | 842.95 | 16-DEC-13:09 | 19.00 | 14.29 |
Annual Sum or Average | 0.668876E+11 | 0.489499E+10 | ||||||||
Minimum of Months | 0.285546E+10 | 16440.64 | 15.17 | 9.88 | 0.360573E+09 | 842.90 | 19.00 | 13.62 | ||
Maximum of Months | 0.815665E+10 | 29022.72 | 28.07 | 25.39 | 0.432396E+09 | 843.00 | 28.07 | 25.39 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.271441E+10 | 22753.17 | 02-JAN-08:62 | 15.50 | 14.72 | 0.379605E+09 | 842.93 | 28-JAN-13:00 | 22.00 | 13.62 |
February | 0.271171E+10 | 18827.62 | 28-FEB-08:62 | 19.50 | 18.32 | 0.359130E+09 | 842.90 | 25-FEB-13:09 | 19.50 | 18.32 |
March | 0.325764E+10 | 18029.88 | 27-MAR-07:02 | 20.18 | 18.99 | 0.411015E+09 | 842.93 | 04-MAR-13:00 | 20.18 | 18.99 |
April | 0.445945E+10 | 19044.62 | 25-APR-07:02 | 20.27 | 17.95 | 0.409994E+09 | 842.99 | 22-APR-12:30 | 20.27 | 17.95 |
May | 0.708544E+10 | 18748.96 | 12-MAY-07:01 | 23.98 | 20.89 | 0.426651E+09 | 842.99 | 27-MAY-12:20 | 30.37 | 24.49 |
June | 0.741765E+10 | 18623.57 | 12-JUN-07:01 | 25.18 | 21.23 | 0.417655E+09 | 842.99 | 17-JUN-12:50 | 27.80 | 24.92 |
July | 0.766796E+10 | 16305.27 | 19-JUL-07:01 | 28.07 | 25.39 | 0.420829E+09 | 843.01 | 01-JUL-12:50 | 28.07 | 25.39 |
August | 0.804850E+10 | 18419.68 | 31-AUG-07:01 | 25.45 | 23.81 | 0.432367E+09 | 843.01 | 26-AUG-12:09 | 25.45 | 23.81 |
September | 0.708280E+10 | 18228.27 | 23-SEP-07:01 | 23.08 | 21.03 | 0.411439E+09 | 842.99 | 09-SEP-12:09 | 23.08 | 21.03 |
October | 0.701916E+10 | 28826.87 | 17-OCT-07:02 | 15.17 | 9.88 | 0.420754E+09 | 842.97 | 21-OCT-12:09 | 28.03 | 25.07 |
November | 0.441483E+10 | 19521.30 | 06-NOV-08:62 | 20.78 | 18.75 | 0.403925E+09 | 842.95 | 25-NOV-13:50 | 20.08 | 14.24 |
December | 0.343715E+10 | 23385.85 | 17-DEC-09:02 | 19.00 | 14.29 | 0.394898E+09 | 842.95 | 16-DEC-13:09 | 19.00 | 14.29 |
Annual Sum or Average | 0.653167E+11 | 0.488826E+10 | ||||||||
Minimum of Months | 0.271171E+10 | 16305.27 | 15.17 | 9.88 | 0.359130E+09 | 842.90 | 19.00 | 13.62 | ||
Maximum of Months | 0.804850E+10 | 28826.87 | 28.07 | 25.39 | 0.432367E+09 | 843.01 | 30.37 | 25.39 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.480338E+10 | 39609.48 | 01-JAN-10:02 | 20.33 | 16.41 | 0.129811E+10 | 2247.91 | 28-JAN-15:39 | 23.00 | 14.05 |
February | 0.477862E+10 | 34026.40 | 28-FEB-09:02 | 20.08 | 18.60 | 0.122791E+10 | 2247.80 | 11-FEB-15:00 | 20.08 | 18.60 |
March | 0.572079E+10 | 32852.29 | 30-MAR-08:62 | 21.78 | 19.48 | 0.140898E+10 | 2247.88 | 04-MAR-15:00 | 21.78 | 19.48 |
April | 0.789353E+10 | 33158.99 | 25-APR-08:62 | 22.07 | 18.96 | 0.140824E+10 | 2248.00 | 15-APR-14:09 | 22.07 | 18.96 |
May | 0.126911E+11 | 34333.81 | 12-MAY-08:61 | 24.78 | 21.42 | 0.145963E+10 | 2248.06 | 06-MAY-14:30 | 24.78 | 21.42 |
June | 0.133301E+11 | 33944.14 | 14-JUN-08:61 | 28.07 | 23.96 | 0.143184E+10 | 2248.10 | 03-JUN-14:39 | 28.07 | 23.96 |
July | 0.137428E+11 | 31065.55 | 18-JUL-08:61 | 28.58 | 24.22 | 0.144063E+10 | 2248.06 | 29-JUL-14:09 | 27.20 | 24.88 |
August | 0.145311E+11 | 34427.61 | 31-AUG-08:61 | 27.88 | 24.10 | 0.148203E+10 | 2248.06 | 26-AUG-14:30 | 27.88 | 24.10 |
September | 0.127169E+11 | 33052.17 | 22-SEP-08:62 | 23.58 | 20.80 | 0.141235E+10 | 2248.06 | 23-SEP-14:00 | 28.80 | 24.09 |
October | 0.126394E+11 | 48066.02 | 26-OCT-08:61 | 21.18 | 12.94 | 0.143654E+10 | 2248.03 | 21-OCT-14:09 | 21.18 | 12.94 |
November | 0.778334E+10 | 37021.03 | 05-NOV-09:02 | 20.78 | 17.18 | 0.137653E+10 | 2248.05 | 04-NOV-14:00 | 20.78 | 17.18 |
December | 0.607391E+10 | 43577.82 | 17-DEC-10:02 | 19.17 | 14.29 | 0.135219E+10 | 2248.05 | 09-DEC-15:50 | 19.17 | 14.29 |
Annual Sum or Average | 0.116705E+12 | 0.167350E+11 | ||||||||
Minimum of Months | 0.477862E+10 | 31065.55 | 19.17 | 12.94 | 0.122791E+10 | 2247.80 | 19.17 | 12.94 | ||
Maximum of Months | 0.145311E+11 | 48066.02 | 28.58 | 24.22 | 0.148203E+10 | 2248.10 | 28.80 | 24.88 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.238252E+10 | 20695.35 | 01-JAN-10:02 | 20.33 | 16.41 | 0.647390E+09 | 1123.92 | 28-JAN-15:39 | 23.00 | 14.05 |
February | 0.239782E+10 | 17768.70 | 28-FEB-09:02 | 20.08 | 18.60 | 0.612763E+09 | 1123.87 | 11-FEB-15:00 | 20.08 | 18.60 |
March | 0.290033E+10 | 17206.56 | 30-MAR-08:62 | 21.78 | 19.48 | 0.703524E+09 | 1123.91 | 04-MAR-15:00 | 21.78 | 19.48 |
April | 0.409209E+10 | 17337.21 | 25-APR-08:62 | 22.07 | 18.96 | 0.704084E+09 | 1124.01 | 29-APR-14:09 | 30.00 | 24.56 |
May | 0.668134E+10 | 17947.45 | 12-MAY-08:61 | 24.78 | 21.42 | 0.729773E+09 | 1124.00 | 06-MAY-14:30 | 24.78 | 21.42 |
June | 0.701923E+10 | 17769.27 | 14-JUN-08:61 | 28.07 | 23.96 | 0.715874E+09 | 1124.02 | 03-JUN-14:30 | 28.07 | 23.96 |
July | 0.723526E+10 | 16277.31 | 18-JUL-08:61 | 28.58 | 24.22 | 0.720275E+09 | 1124.00 | 29-JUL-14:20 | 27.20 | 25.03 |
August | 0.763891E+10 | 18028.60 | 31-AUG-08:61 | 27.88 | 24.10 | 0.740974E+09 | 1124.02 | 26-AUG-14:39 | 27.88 | 24.10 |
September | 0.667127E+10 | 17291.09 | 23-SEP-08:61 | 25.27 | 21.98 | 0.706133E+09 | 1124.00 | 23-SEP-14:00 | 28.80 | 24.09 |
October | 0.660975E+10 | 25146.11 | 26-OCT-08:61 | 21.18 | 12.94 | 0.718242E+09 | 1123.98 | 21-OCT-14:09 | 21.18 | 12.94 |
November | 0.400749E+10 | 19346.87 | 05-NOV-09:02 | 20.78 | 17.18 | 0.688145E+09 | 1123.99 | 04-NOV-14:50 | 20.78 | 17.18 |
December | 0.306741E+10 | 22800.45 | 17-DEC-10:02 | 19.17 | 14.29 | 0.675556E+09 | 1123.99 | 09-DEC-15:50 | 19.17 | 14.29 |
Annual Sum or Average | 0.607034E+11 | 0.836273E+10 | ||||||||
Minimum of Months | 0.238252E+10 | 16277.31 | 19.17 | 12.94 | 0.612763E+09 | 1123.87 | 19.17 | 12.94 | ||
Maximum of Months | 0.763891E+10 | 25146.11 | 28.58 | 24.22 | 0.740974E+09 | 1124.02 | 30.00 | 25.03 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.232343E+10 | 20557.88 | 01-JAN-10:02 | 20.33 | 16.41 | 0.645611E+09 | 1123.92 | 28-JAN-15:39 | 23.00 | 14.05 |
February | 0.234070E+10 | 17635.81 | 28-FEB-09:02 | 20.08 | 18.60 | 0.611423E+09 | 1123.87 | 11-FEB-15:00 | 20.08 | 18.60 |
March | 0.284021E+10 | 17075.75 | 30-MAR-08:62 | 21.78 | 19.48 | 0.702386E+09 | 1123.91 | 04-MAR-15:00 | 21.78 | 19.48 |
April | 0.403170E+10 | 17218.92 | 25-APR-08:62 | 22.07 | 18.96 | 0.704005E+09 | 1124.01 | 29-APR-14:09 | 30.00 | 24.56 |
May | 0.662848E+10 | 17834.67 | 12-MAY-08:61 | 24.78 | 21.42 | 0.729757E+09 | 1124.00 | 06-MAY-14:30 | 24.78 | 21.42 |
June | 0.696969E+10 | 17658.56 | 14-JUN-08:61 | 28.07 | 23.96 | 0.715861E+09 | 1124.02 | 03-JUN-14:30 | 28.07 | 23.96 |
July | 0.719095E+10 | 16174.95 | 18-JUL-08:61 | 28.58 | 24.22 | 0.720264E+09 | 1123.99 | 29-JUL-14:09 | 27.20 | 24.88 |
August | 0.759504E+10 | 17914.56 | 31-AUG-08:61 | 27.88 | 24.10 | 0.740963E+09 | 1123.99 | 26-AUG-14:30 | 27.88 | 24.10 |
September | 0.662836E+10 | 17186.98 | 23-SEP-08:61 | 25.27 | 21.98 | 0.706122E+09 | 1124.00 | 23-SEP-14:00 | 28.80 | 24.09 |
October | 0.655796E+10 | 25012.19 | 26-OCT-08:61 | 21.18 | 12.94 | 0.718216E+09 | 1123.98 | 21-OCT-14:09 | 21.18 | 12.94 |
November | 0.394970E+10 | 19232.74 | 05-NOV-09:02 | 20.78 | 17.18 | 0.687943E+09 | 1123.99 | 04-NOV-14:50 | 20.78 | 17.18 |
December | 0.300666E+10 | 22667.82 | 17-DEC-10:02 | 19.17 | 14.29 | 0.674616E+09 | 1123.99 | 09-DEC-15:50 | 19.17 | 14.29 |
Annual Sum or Average | 0.600629E+11 | 0.835717E+10 | ||||||||
Minimum of Months | 0.232343E+10 | 16174.95 | 19.17 | 12.94 | 0.611423E+09 | 1123.87 | 19.17 | 12.94 | ||
Maximum of Months | 0.759504E+10 | 25012.19 | 28.58 | 24.22 | 0.740963E+09 | 1124.02 | 30.00 | 24.88 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.217201E+10 | 20408.41 | 01-JAN-10:02 | 20.33 | 16.41 | 0.641335E+09 | 1123.92 | 28-JAN-15:39 | 23.00 | 14.05 |
February | 0.219941E+10 | 16144.12 | 28-FEB-09:02 | 20.08 | 18.60 | 0.608035E+09 | 1123.87 | 11-FEB-15:00 | 20.08 | 18.60 |
March | 0.268366E+10 | 14879.17 | 30-MAR-08:62 | 21.78 | 19.48 | 0.699249E+09 | 1123.91 | 04-MAR-15:00 | 21.78 | 19.48 |
April | 0.388349E+10 | 17003.84 | 22-APR-08:62 | 22.57 | 19.97 | 0.703702E+09 | 1124.00 | 29-APR-14:00 | 30.00 | 23.99 |
May | 0.656782E+10 | 17800.73 | 12-MAY-08:61 | 24.78 | 21.42 | 0.729722E+09 | 1124.01 | 06-MAY-14:39 | 24.78 | 21.42 |
June | 0.693690E+10 | 17657.69 | 14-JUN-08:61 | 28.07 | 23.96 | 0.715837E+09 | 1124.02 | 03-JUN-14:50 | 28.07 | 23.96 |
July | 0.718815E+10 | 16178.27 | 18-JUL-08:61 | 28.58 | 24.22 | 0.720253E+09 | 1124.00 | 29-JUL-14:20 | 27.20 | 25.03 |
August | 0.760426E+10 | 17947.59 | 31-AUG-08:61 | 27.88 | 24.10 | 0.740955E+09 | 1124.02 | 26-AUG-14:39 | 27.88 | 24.10 |
September | 0.661721E+10 | 17181.12 | 23-SEP-08:61 | 25.27 | 21.98 | 0.706108E+09 | 1123.99 | 23-SEP-14:00 | 28.80 | 24.09 |
October | 0.651387E+10 | 25016.26 | 26-OCT-08:61 | 21.18 | 12.94 | 0.718141E+09 | 1123.97 | 21-OCT-14:09 | 21.18 | 12.94 |
November | 0.382510E+10 | 19138.80 | 05-NOV-09:02 | 20.78 | 17.18 | 0.687360E+09 | 1123.99 | 04-NOV-14:30 | 20.78 | 17.18 |
December | 0.285695E+10 | 22583.80 | 17-DEC-10:02 | 19.17 | 14.29 | 0.671989E+09 | 1123.98 | 16-DEC-15:00 | 19.17 | 14.29 |
Annual Sum or Average | 0.590488E+11 | 0.834269E+10 | ||||||||
Minimum of Months | 0.217201E+10 | 14879.17 | 19.17 | 12.94 | 0.608035E+09 | 1123.87 | 19.17 | 12.94 | ||
Maximum of Months | 0.760426E+10 | 25016.26 | 28.58 | 24.22 | 0.740955E+09 | 1124.02 | 30.00 | 25.03 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.198960E+10 | 19815.71 | 01-JAN-10:02 | 20.33 | 16.41 | 0.637785E+09 | 1123.91 | 28-JAN-15:39 | 23.00 | 14.05 |
February | 0.207478E+10 | 10223.15 | 28-FEB-09:02 | 20.08 | 18.60 | 0.603810E+09 | 1123.87 | 11-FEB-15:50 | 20.08 | 18.60 |
March | 0.264127E+10 | 12669.92 | 07-MAR-09:02 | 23.67 | 21.83 | 0.695281E+09 | 1123.91 | 04-MAR-15:00 | 23.67 | 21.83 |
April | 0.404307E+10 | 18405.04 | 23-APR-09:02 | 24.68 | 20.67 | 0.703145E+09 | 1123.96 | 22-APR-14:00 | 24.68 | 20.67 |
May | 0.727820E+10 | 18841.78 | 12-MAY-08:61 | 24.78 | 21.42 | 0.729773E+09 | 1124.01 | 27-MAY-14:00 | 32.20 | 25.37 |
June | 0.783767E+10 | 19475.07 | 11-JUN-09:01 | 28.07 | 20.81 | 0.715925E+09 | 1123.96 | 03-JUN-14:00 | 28.07 | 20.81 |
July | 0.822661E+10 | 17650.27 | 19-JUL-08:61 | 29.68 | 25.89 | 0.720404E+09 | 1124.00 | 29-JUL-14:00 | 27.20 | 25.59 |
August | 0.875825E+10 | 20607.59 | 31-AUG-08:61 | 27.88 | 24.10 | 0.741088E+09 | 1124.04 | 26-AUG-14:00 | 27.88 | 24.10 |
September | 0.751162E+10 | 18580.72 | 02-SEP-08:61 | 28.58 | 24.62 | 0.706252E+09 | 1124.03 | 23-SEP-14:20 | 29.93 | 24.10 |
October | 0.728369E+10 | 28448.35 | 26-OCT-08:61 | 21.18 | 12.94 | 0.718074E+09 | 1123.97 | 21-OCT-14:00 | 21.18 | 12.94 |
November | 0.396982E+10 | 20078.94 | 06-NOV-09:02 | 22.47 | 19.37 | 0.686708E+09 | 1123.91 | 25-NOV-15:09 | 19.80 | 14.72 |
December | 0.273230E+10 | 25407.48 | 17-DEC-10:02 | 19.17 | 14.29 | 0.668248E+09 | 1124.00 | 16-DEC-15:39 | 19.17 | 14.29 |
Annual Sum or Average | 0.643469E+11 | 0.832649E+10 | ||||||||
Minimum of Months | 0.198960E+10 | 10223.15 | 19.17 | 12.94 | 0.603810E+09 | 1123.87 | 19.17 | 12.94 | ||
Maximum of Months | 0.875825E+10 | 28448.35 | 29.68 | 25.89 | 0.741088E+09 | 1124.04 | 32.20 | 25.59 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.106061E+09 | 34700.68 | 10-JAN-09:01 | 5.33 |
February | 0.124524E+09 | 53219.20 | 06-FEB-09:01 | 7.47 |
March | 0.182526E+09 | 40738.96 | 11-MAR-09:01 | 6.52 |
April | 89477654.68 | 2561.92 | 29-APR-08:05 | 25.78 |
May | 0.101285E+09 | 3446.78 | 27-MAY-08:06 | 27.98 |
June | 96208020.46 | 3970.48 | 16-JUN-08:05 | 29.08 |
July | 85647651.77 | 3423.84 | 05-JUL-08:17 | 28.50 |
August | 89132519.44 | 3513.16 | 31-AUG-08:05 | 27.88 |
September | 90608274.74 | 3732.66 | 02-SEP-08:05 | 28.58 |
October | 90923811.57 | 3864.64 | 07-OCT-08:06 | 29.17 |
November | 87352835.86 | 1768.22 | 11-NOV-08:05 | 20.73 |
December | 0.110574E+09 | 52731.85 | 21-DEC-09:01 | 6.33 |
Annual Sum or Average | 0.125432E+10 | |||
Minimum of Months | 85647651.77 | 1768.22 | 5.33 | |
Maximum of Months | 0.182526E+09 | 53219.20 | 29.17 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 49476866.61 | 1206.71 | 05-JAN-09:03 | 6.50 |
February | 50631048.28 | 8468.62 | 05-FEB-09:02 | -0.3 |
March | 66946826.11 | 2095.92 | 11-MAR-12:10 | 6.28 |
April | 47904846.82 | 1314.18 | 29-APR-08:05 | 25.78 |
May | 52752626.15 | 1856.76 | 16-MAY-08:04 | 27.98 |
June | 49661647.92 | 2281.34 | 17-JUN-08:05 | 30.00 |
July | 45212899.22 | 2252.20 | 19-JUL-08:05 | 29.68 |
August | 46992222.06 | 2091.69 | 22-AUG-08:05 | 29.00 |
September | 47671923.44 | 1817.81 | 02-SEP-08:05 | 28.58 |
October | 46918528.49 | 1572.19 | 14-OCT-08:05 | 27.17 |
November | 44433452.35 | 1026.97 | 11-NOV-08:05 | 20.73 |
December | 51256904.04 | 9233.00 | 21-DEC-09:01 | 6.33 |
Annual Sum or Average | 0.599860E+09 | |||
Minimum of Months | 44433452.35 | 1026.97 | -0.3 | |
Maximum of Months | 66946826.11 | 9233.00 | 30.00 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 52521726.45 | 1287.54 | 04-JAN-08:10 | 2.33 |
February | 61538454.43 | 16342.57 | 05-FEB-09:02 | -0.3 |
March | 78496925.11 | 9137.81 | 12-MAR-08:62 | 9.18 |
April | 58927072.81 | 1713.01 | 22-APR-17:03 | 30.13 |
May | 0.128048E+09 | 2525.33 | 28-MAY-16:02 | 33.43 |
June | 0.141572E+09 | 2345.41 | 25-JUN-16:02 | 32.70 |
July | 0.135930E+09 | 2897.82 | 22-JUL-17:02 | 34.63 |
August | 0.122681E+09 | 2563.82 | 27-AUG-16:02 | 33.67 |
September | 96940994.09 | 3273.76 | 09-SEP-17:02 | 36.18 |
October | 88434147.86 | 1846.92 | 08-OCT-16:02 | 30.67 |
November | 52437767.69 | 983.39 | 11-NOV-09:05 | 24.40 |
December | 56004750.44 | 2450.32 | 21-DEC-08:65 | 3.50 |
Annual Sum or Average | 0.107353E+10 | |||
Minimum of Months | 52437767.69 | 983.39 | -0.3 | |
Maximum of Months | 0.141572E+09 | 16342.57 | 36.18 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 55775240.35 | 1842.40 | 10-JAN-08:65 | 4.17 |
February | 67542801.92 | 19284.39 | 05-FEB-09:02 | -0.3 |
March | 83615744.27 | 12136.81 | 12-MAR-08:62 | 9.18 |
April | 59040155.52 | 1714.68 | 22-APR-17:03 | 30.13 |
May | 0.126785E+09 | 2525.80 | 28-MAY-16:02 | 33.43 |
June | 0.139231E+09 | 2344.98 | 25-JUN-16:02 | 32.70 |
July | 0.130959E+09 | 2898.06 | 22-JUL-17:02 | 34.63 |
August | 0.118159E+09 | 2562.75 | 27-AUG-16:02 | 33.67 |
September | 94298229.05 | 3274.41 | 09-SEP-17:02 | 36.18 |
October | 85797958.47 | 1845.83 | 08-OCT-16:02 | 30.67 |
November | 52538419.23 | 982.64 | 11-NOV-09:05 | 24.40 |
December | 58348764.80 | 3295.74 | 21-DEC-08:65 | 3.50 |
Annual Sum or Average | 0.107209E+10 | |||
Minimum of Months | 52538419.23 | 982.64 | -0.3 | |
Maximum of Months | 0.139231E+09 | 19284.39 | 36.18 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 58124480.37 | 3228.16 | 10-JAN-08:65 | 4.17 |
February | 75091993.63 | 21767.28 | 05-FEB-09:02 | -0.3 |
March | 90311533.35 | 14613.73 | 12-MAR-08:62 | 9.18 |
April | 59277765.83 | 1719.91 | 22-APR-17:03 | 30.13 |
May | 0.129048E+09 | 2528.70 | 28-MAY-16:02 | 33.43 |
June | 0.142101E+09 | 2347.67 | 25-JUN-16:02 | 32.70 |
July | 0.137229E+09 | 2900.93 | 22-JUL-17:02 | 34.63 |
August | 0.124926E+09 | 2565.19 | 27-AUG-16:02 | 33.67 |
September | 96864928.83 | 3277.26 | 09-SEP-17:02 | 36.18 |
October | 89163468.34 | 1847.86 | 08-OCT-16:02 | 30.67 |
November | 52647376.20 | 939.50 | 11-NOV-09:05 | 24.40 |
December | 61025191.37 | 4279.26 | 21-DEC-08:65 | 3.50 |
Annual Sum or Average | 0.111581E+10 | |||
Minimum of Months | 52647376.20 | 939.50 | -0.3 | |
Maximum of Months | 0.142101E+09 | 21767.28 | 36.18 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.103553E+09 | 42442.59 | 10-JAN-09:01 | 5.33 |
February | 0.126837E+09 | 50481.36 | 06-FEB-09:01 | 7.47 |
March | 0.157570E+09 | 51289.30 | 12-MAR-09:01 | 11.47 |
April | 0.111147E+09 | 3439.80 | 22-APR-17:03 | 30.13 |
May | 0.166144E+09 | 5062.23 | 28-MAY-16:02 | 33.43 |
June | 0.164644E+09 | 4698.62 | 25-JUN-16:02 | 32.70 |
July | 0.162582E+09 | 5784.01 | 22-JUL-17:02 | 34.63 |
August | 0.140064E+09 | 5137.91 | 27-AUG-16:02 | 33.67 |
September | 0.153883E+09 | 6539.57 | 09-SEP-17:02 | 36.18 |
October | 0.129218E+09 | 3690.53 | 08-OCT-16:02 | 30.67 |
November | 92436712.14 | 1841.68 | 05-NOV-16:03 | 27.02 |
December | 0.107966E+09 | 49815.05 | 21-DEC-09:01 | 6.33 |
Annual Sum or Average | 0.161605E+10 | |||
Minimum of Months | 92436712.14 | 1841.68 | 5.33 | |
Maximum of Months | 0.166144E+09 | 51289.30 | 36.18 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 59264632.70 | 22695.35 | 10-JAN-09:01 | 5.33 |
February | 78076619.46 | 26483.70 | 06-FEB-09:01 | 7.47 |
March | 94161184.94 | 26489.51 | 13-MAR-08:61 | 10.55 |
April | 60364588.73 | 1734.50 | 22-APR-17:03 | 30.13 |
May | 85926548.71 | 2535.58 | 28-MAY-16:02 | 33.43 |
June | 86176903.08 | 2354.54 | 25-JUN-16:02 | 32.70 |
July | 85496493.12 | 2908.35 | 22-JUL-17:02 | 34.63 |
August | 72158326.16 | 2571.72 | 27-AUG-16:02 | 33.67 |
September | 81186992.72 | 3284.90 | 09-SEP-17:02 | 36.18 |
October | 68753556.59 | 1852.76 | 08-OCT-16:02 | 30.67 |
November | 50618090.22 | 963.74 | 11-NOV-10:04 | 24.68 |
December | 63143485.78 | 26147.19 | 21-DEC-09:01 | 6.33 |
Annual Sum or Average | 0.885327E+09 | |||
Minimum of Months | 50618090.22 | 963.74 | 5.33 | |
Maximum of Months | 94161184.94 | 26489.51 | 36.18 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 62751979.27 | 24596.13 | 10-JAN-09:01 | 5.33 |
February | 80670835.04 | 26402.52 | 06-FEB-09:01 | 7.47 |
March | 97897117.17 | 27108.92 | 12-MAR-09:01 | 11.47 |
April | 60261384.88 | 1736.29 | 22-APR-17:03 | 30.13 |
May | 86297949.27 | 2536.74 | 28-MAY-16:02 | 33.43 |
June | 86692646.11 | 2355.68 | 25-JUN-16:02 | 32.70 |
July | 86279627.52 | 2909.15 | 22-JUL-17:02 | 34.63 |
August | 73363140.91 | 2572.82 | 27-AUG-16:02 | 33.67 |
September | 81747981.20 | 3285.86 | 09-SEP-17:02 | 36.18 |
October | 68662269.08 | 1853.86 | 08-OCT-16:02 | 30.67 |
November | 50456394.26 | 963.75 | 11-NOV-10:04 | 24.68 |
December | 64802447.42 | 26061.79 | 21-DEC-09:01 | 6.33 |
Annual Sum or Average | 0.899884E+09 | |||
Minimum of Months | 50456394.26 | 963.75 | 5.33 | |
Maximum of Months | 97897117.17 | 27108.92 | 36.18 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 76364762.61 | 25779.34 | 10-JAN-09:01 | 5.33 |
February | 0.100978E+09 | 26567.95 | 06-FEB-09:01 | 7.47 |
March | 0.112478E+09 | 27267.39 | 12-MAR-09:01 | 11.47 |
April | 60632795.74 | 1739.88 | 22-APR-17:03 | 30.13 |
May | 87373646.28 | 2538.31 | 28-MAY-16:02 | 33.43 |
June | 87843978.62 | 2356.66 | 25-JUN-16:02 | 32.70 |
July | 87842337.02 | 2909.04 | 22-JUL-17:02 | 34.63 |
August | 73246056.01 | 2572.23 | 27-AUG-16:02 | 33.67 |
September | 81837211.69 | 3285.99 | 09-SEP-17:02 | 36.18 |
October | 69303715.50 | 1853.53 | 08-OCT-16:02 | 30.67 |
November | 50690999.97 | 990.08 | 11-NOV-10:04 | 24.68 |
December | 76353802.21 | 26209.23 | 21-DEC-09:01 | 6.33 |
Annual Sum or Average | 0.964945E+09 | |||
Minimum of Months | 50690999.97 | 990.08 | 5.33 | |
Maximum of Months | 0.112478E+09 | 27267.39 | 36.18 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.149518E+09 | 29466.04 | 10-JAN-09:01 | 5.33 |
February | 0.175422E+09 | 30253.88 | 06-FEB-09:01 | 7.47 |
March | 0.190260E+09 | 30862.81 | 12-MAR-09:01 | 11.47 |
April | 64900246.90 | 1734.81 | 22-APR-17:03 | 30.13 |
May | 89519042.03 | 2523.14 | 28-MAY-16:02 | 33.43 |
June | 88351268.02 | 2357.26 | 17-JUN-08:05 | 30.00 |
July | 86563444.10 | 2885.59 | 22-JUL-17:02 | 34.63 |
August | 70545213.33 | 2537.70 | 27-AUG-16:02 | 33.67 |
September | 82306015.93 | 3259.11 | 09-SEP-17:02 | 36.18 |
October | 72771713.01 | 1827.56 | 08-OCT-16:02 | 30.67 |
November | 54606789.08 | 1098.69 | 11-NOV-10:04 | 24.68 |
December | 0.137394E+09 | 29970.18 | 21-DEC-09:01 | 6.33 |
Annual Sum or Average | 0.126216E+10 | |||
Minimum of Months | 54606789.08 | 1098.69 | 5.33 | |
Maximum of Months | 0.190260E+09 | 30862.81 | 36.18 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.869933E+10 | 5321.43 | 01-JAN-10:09 | 0.223514E+10 | 1348.26 | 01-JAN-10:09 |
February | 0.786449E+10 | 5321.43 | 01-FEB-10:09 | 0.202238E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.870841E+10 | 5321.43 | 01-MAR-10:09 | 0.224215E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.843013E+10 | 5321.43 | 01-APR-09:09 | 0.216638E+10 | 1348.26 | 01-APR-09:09 |
May | 0.869933E+10 | 5321.43 | 01-MAY-09:09 | 0.223514E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.843013E+10 | 5321.43 | 01-JUN-09:09 | 0.217123E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.870841E+10 | 5321.43 | 01-JUL-09:09 | 0.223729E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.869933E+10 | 5321.43 | 01-AUG-09:09 | 0.223756E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.843920E+10 | 5321.43 | 01-SEP-09:09 | 0.217096E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.869933E+10 | 5321.43 | 01-OCT-09:09 | 0.223514E+10 | 1348.26 | 01-OCT-09:09 |
November | 0.840290E+10 | 5321.43 | 01-NOV-09:09 | 0.215964E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.871748E+10 | 5321.43 | 01-DEC-10:09 | 0.224431E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.102498E+12 | 0.263573E+11 | ||||
Minimum of Months | 0.786449E+10 | 5321.43 | 0.202238E+10 | 1348.26 | ||
Maximum of Months | 0.871748E+10 | 5321.43 | 0.224431E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.479410E+10 | 2932.57 | 01-JAN-10:09 | 0.111757E+10 | 674.13 | 01-JAN-10:09 |
February | 0.433403E+10 | 2932.57 | 01-FEB-10:09 | 0.101119E+10 | 674.13 | 01-FEB-10:09 |
March | 0.479910E+10 | 2932.57 | 01-MAR-10:09 | 0.112107E+10 | 674.13 | 01-MAR-10:09 |
April | 0.464574E+10 | 2932.57 | 01-APR-09:09 | 0.108319E+10 | 674.13 | 01-APR-09:09 |
May | 0.479410E+10 | 2932.57 | 01-MAY-09:09 | 0.111757E+10 | 674.13 | 01-MAY-09:09 |
June | 0.464574E+10 | 2932.57 | 01-JUN-09:09 | 0.108562E+10 | 674.13 | 01-JUN-09:09 |
July | 0.479910E+10 | 2932.57 | 01-JUL-09:09 | 0.111865E+10 | 674.13 | 01-JUL-09:09 |
August | 0.479410E+10 | 2932.57 | 01-AUG-09:09 | 0.111878E+10 | 674.13 | 01-AUG-09:09 |
September | 0.465074E+10 | 2932.57 | 01-SEP-09:09 | 0.108548E+10 | 674.13 | 01-SEP-09:09 |
October | 0.479410E+10 | 2932.57 | 01-OCT-09:09 | 0.111757E+10 | 674.13 | 01-OCT-09:09 |
November | 0.463074E+10 | 2932.57 | 01-NOV-09:09 | 0.107982E+10 | 674.13 | 01-NOV-09:09 |
December | 0.480410E+10 | 2932.57 | 01-DEC-10:09 | 0.112215E+10 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.564857E+11 | 0.131787E+11 | ||||
Minimum of Months | 0.433403E+10 | 2932.57 | 0.101119E+10 | 674.13 | ||
Maximum of Months | 0.480410E+10 | 2932.57 | 0.112215E+10 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.338042E+10 | 2599.23 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.306129E+10 | 2599.23 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.345133E+10 | 2599.23 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.327995E+10 | 2599.23 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.341588E+10 | 2599.23 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.333314E+10 | 2599.23 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.336269E+10 | 2599.23 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.345133E+10 | 2599.23 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.327995E+10 | 2599.23 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.338042E+10 | 2599.23 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.327995E+10 | 2599.23 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.336269E+10 | 2599.23 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.400390E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.306129E+10 | 2599.23 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.345133E+10 | 2599.23 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.338042E+10 | 2599.23 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.306129E+10 | 2599.23 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.345133E+10 | 2599.23 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.327995E+10 | 2599.23 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.341588E+10 | 2599.23 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.333314E+10 | 2599.23 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.336269E+10 | 2599.23 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.345133E+10 | 2599.23 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.327995E+10 | 2599.23 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.338042E+10 | 2599.23 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.327995E+10 | 2599.23 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.336269E+10 | 2599.23 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.400390E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.306129E+10 | 2599.23 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.345133E+10 | 2599.23 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.338042E+10 | 2599.23 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.306129E+10 | 2599.23 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.345133E+10 | 2599.23 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.327995E+10 | 2599.23 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.341588E+10 | 2599.23 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.333314E+10 | 2599.23 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.336269E+10 | 2599.23 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.345133E+10 | 2599.23 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.327995E+10 | 2599.23 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.338042E+10 | 2599.23 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.327995E+10 | 2599.23 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.336269E+10 | 2599.23 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.400390E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.306129E+10 | 2599.23 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.345133E+10 | 2599.23 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.447638E+10 | 3746.51 | 01-JAN-11:09 | 0.162546E+10 | 1348.26 | 01-JAN-11:09 |
February | 0.405472E+10 | 3746.51 | 01-FEB-10:09 | 0.147229E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.457860E+10 | 3746.51 | 01-MAR-10:09 | 0.166213E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.434435E+10 | 3746.51 | 01-APR-09:09 | 0.157746E+10 | 1348.26 | 01-APR-09:09 |
May | 0.452749E+10 | 3746.51 | 01-MAY-09:09 | 0.164379E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.442101E+10 | 3746.51 | 01-JUN-09:09 | 0.160496E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.445083E+10 | 3746.51 | 01-JUL-09:09 | 0.161629E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.457860E+10 | 3746.51 | 01-AUG-09:09 | 0.166213E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.434435E+10 | 3746.51 | 01-SEP-09:09 | 0.157746E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.447638E+10 | 3746.51 | 01-OCT-10:09 | 0.162546E+10 | 1348.26 | 01-OCT-10:09 |
November | 0.434435E+10 | 3746.51 | 01-NOV-09:09 | 0.157746E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.445083E+10 | 3746.51 | 01-DEC-10:09 | 0.161629E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.530479E+11 | 0.192612E+11 | ||||
Minimum of Months | 0.405472E+10 | 3746.51 | 0.147229E+10 | 1348.26 | ||
Maximum of Months | 0.457860E+10 | 3746.51 | 0.166213E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.230731E+10 | 1931.10 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.208997E+10 | 1931.10 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.236000E+10 | 1931.10 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.223926E+10 | 1931.10 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.233366E+10 | 1931.10 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.227877E+10 | 1931.10 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.229414E+10 | 1931.10 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.236000E+10 | 1931.10 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.223926E+10 | 1931.10 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.230731E+10 | 1931.10 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.223926E+10 | 1931.10 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.229414E+10 | 1931.10 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.273431E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.208997E+10 | 1931.10 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.236000E+10 | 1931.10 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.230731E+10 | 1931.10 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.208997E+10 | 1931.10 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.236000E+10 | 1931.10 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.223926E+10 | 1931.10 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.233366E+10 | 1931.10 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.227877E+10 | 1931.10 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.229414E+10 | 1931.10 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.236000E+10 | 1931.10 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.223926E+10 | 1931.10 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.230731E+10 | 1931.10 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.223926E+10 | 1931.10 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.229414E+10 | 1931.10 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.273431E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.208997E+10 | 1931.10 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.236000E+10 | 1931.10 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.230731E+10 | 1931.10 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.208997E+10 | 1931.10 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.236000E+10 | 1931.10 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.223926E+10 | 1931.10 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.233366E+10 | 1931.10 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.227877E+10 | 1931.10 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.229414E+10 | 1931.10 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.236000E+10 | 1931.10 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.223926E+10 | 1931.10 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.230731E+10 | 1931.10 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.223926E+10 | 1931.10 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.229414E+10 | 1931.10 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.273431E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.208997E+10 | 1931.10 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.236000E+10 | 1931.10 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.230731E+10 | 1931.10 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.208997E+10 | 1931.10 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.236000E+10 | 1931.10 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.223926E+10 | 1931.10 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.233366E+10 | 1931.10 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.227877E+10 | 1931.10 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.229414E+10 | 1931.10 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.236000E+10 | 1931.10 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.223926E+10 | 1931.10 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.230731E+10 | 1931.10 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.223926E+10 | 1931.10 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.229414E+10 | 1931.10 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.273431E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.208997E+10 | 1931.10 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.236000E+10 | 1931.10 | 0.831065E+09 | 674.13 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.869933E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70559402.60 | 0.261454E+10 |
February | 0.305697E+10 | 0.786449E+10 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122072E+09 | 0.190027E+10 |
March | 0.335708E+10 | 0.870841E+10 | 0.224215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266933E+09 | 0.167001E+10 |
April | 0.327081E+10 | 0.843013E+10 | 0.216638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.755687E+09 | 0.591727E+09 |
May | 0.336680E+10 | 0.869933E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215810E+10 | 32595287.30 |
June | 0.325380E+10 | 0.843013E+10 | 0.217123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233393E+10 | 25583620.55 |
July | 0.339353E+10 | 0.870841E+10 | 0.223729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226468E+10 | 17343138.31 |
August | 0.334857E+10 | 0.869933E+10 | 0.223756E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232170E+10 | 41039201.98 |
September | 0.327932E+10 | 0.843920E+10 | 0.217096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165340E+10 | 79698357.58 |
October | 0.338624E+10 | 0.869933E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153119E+10 | 0.381423E+09 |
November | 0.327446E+10 | 0.840290E+10 | 0.215964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373076E+09 | 0.118725E+10 |
December | 0.340325E+10 | 0.871748E+10 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242259E+09 | 0.224215E+10 |
Annual Sum or Average | 0.397770E+11 | 0.102498E+12 | 0.263573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140936E+11 | 0.107836E+11 |
Minimum of Months | 0.305697E+10 | 0.786449E+10 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70559402.60 | 17343138.31 |
Maximum of Months | 0.340325E+10 | 0.871748E+10 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233393E+10 | 0.261454E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.479410E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39886318.00 | 0.139803E+10 |
February | 0.152844E+10 | 0.433403E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68878488.96 | 0.100949E+10 |
March | 0.167849E+10 | 0.479910E+10 | 0.112107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150066E+09 | 0.868158E+09 |
April | 0.163536E+10 | 0.464574E+10 | 0.108319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426378E+09 | 0.294609E+09 |
May | 0.168335E+10 | 0.479410E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121248E+10 | 11987997.50 |
June | 0.162685E+10 | 0.464574E+10 | 0.108562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131362E+10 | 8787280.18 |
July | 0.169671E+10 | 0.479910E+10 | 0.111865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127014E+10 | 7393783.84 |
August | 0.167424E+10 | 0.479410E+10 | 0.111878E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130183E+10 | 14000618.87 |
September | 0.163961E+10 | 0.465074E+10 | 0.108548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.924872E+09 | 32109823.48 |
October | 0.169307E+10 | 0.479410E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.856828E+09 | 0.167261E+09 |
November | 0.163718E+10 | 0.463074E+10 | 0.107982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210863E+09 | 0.604118E+09 |
December | 0.170157E+10 | 0.480410E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137007E+09 | 0.117102E+10 |
Annual Sum or Average | 0.198880E+11 | 0.564857E+11 | 0.131787E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.791285E+10 | 0.558697E+10 |
Minimum of Months | 0.152844E+10 | 0.433403E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39886318.00 | 7393783.84 |
Maximum of Months | 0.170157E+10 | 0.480410E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131362E+10 | 0.139803E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.338042E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887275.20 | 0.139066E+10 |
February | 0.914877E+09 | 0.306129E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68805974.46 | 0.101483E+10 |
March | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147660E+09 | 0.880678E+09 |
April | 0.984131E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421280E+09 | 0.308737E+09 |
May | 0.102058E+10 | 0.341588E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119330E+10 | 15016665.07 |
June | 0.998711E+09 | 0.333314E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129948E+10 | 11667301.35 |
July | 0.100600E+10 | 0.336269E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124634E+10 | 8840424.93 |
August | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128980E+10 | 21214616.31 |
September | 0.984131E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.902037E+09 | 39111000.05 |
October | 0.100722E+10 | 0.338042E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.837072E+09 | 0.181547E+09 |
November | 0.973196E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207863E+09 | 0.617608E+09 |
December | 0.100600E+10 | 0.336269E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136536E+09 | 0.118282E+10 |
Annual Sum or Average | 0.119700E+11 | 0.400390E+11 | 0.104672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.779007E+10 | 0.567273E+10 |
Minimum of Months | 0.914877E+09 | 0.306129E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887275.20 | 8840424.93 |
Maximum of Months | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129948E+10 | 0.139066E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.338042E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887464.96 | 0.137584E+10 |
February | 0.914877E+09 | 0.306129E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68805969.24 | 0.100676E+10 |
March | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147665E+09 | 0.874683E+09 |
April | 0.984131E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421278E+09 | 0.308214E+09 |
May | 0.102058E+10 | 0.341588E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119307E+10 | 15509776.10 |
June | 0.998711E+09 | 0.333314E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129920E+10 | 12097419.68 |
July | 0.100600E+10 | 0.336269E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124575E+10 | 9280935.59 |
August | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128943E+10 | 21861393.45 |
September | 0.984131E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.901615E+09 | 39840562.49 |
October | 0.100722E+10 | 0.338042E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.836968E+09 | 0.182414E+09 |
November | 0.973196E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207864E+09 | 0.616437E+09 |
December | 0.100600E+10 | 0.336269E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136537E+09 | 0.117612E+10 |
Annual Sum or Average | 0.119700E+11 | 0.400390E+11 | 0.104672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.778807E+10 | 0.563907E+10 |
Minimum of Months | 0.914877E+09 | 0.306129E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887464.96 | 9280935.59 |
Maximum of Months | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129920E+10 | 0.137584E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.338042E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887460.25 | 0.136061E+10 |
February | 0.914877E+09 | 0.306129E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68805962.61 | 0.997083E+09 |
March | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147676E+09 | 0.865734E+09 |
April | 0.984131E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421334E+09 | 0.306412E+09 |
May | 0.102058E+10 | 0.341588E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119348E+10 | 14257513.79 |
June | 0.998711E+09 | 0.333314E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129960E+10 | 11266225.23 |
July | 0.100600E+10 | 0.336269E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124637E+10 | 8660393.87 |
August | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128983E+10 | 20717147.09 |
September | 0.984131E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.901936E+09 | 38631371.67 |
October | 0.100722E+10 | 0.338042E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.837174E+09 | 0.180635E+09 |
November | 0.973196E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207875E+09 | 0.613758E+09 |
December | 0.100600E+10 | 0.336269E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136539E+09 | 0.116815E+10 |
Annual Sum or Average | 0.119700E+11 | 0.400390E+11 | 0.104672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.779051E+10 | 0.558591E+10 |
Minimum of Months | 0.914877E+09 | 0.306129E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887460.25 | 8660393.87 |
Maximum of Months | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129960E+10 | 0.136061E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.447638E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69893212.59 | 0.243204E+10 |
February | 0.313522E+10 | 0.405472E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120599E+09 | 0.177955E+10 |
March | 0.355148E+10 | 0.457860E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259051E+09 | 0.155673E+10 |
April | 0.338259E+10 | 0.434435E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.738260E+09 | 0.557671E+09 |
May | 0.349753E+10 | 0.452749E+10 | 0.164379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208186E+10 | 28618923.69 |
June | 0.343071E+10 | 0.442101E+10 | 0.160496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226643E+10 | 22752266.19 |
July | 0.344942E+10 | 0.445083E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217095E+10 | 16482255.79 |
August | 0.355148E+10 | 0.457860E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225003E+10 | 40774898.12 |
September | 0.338259E+10 | 0.434435E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157422E+10 | 78829023.50 |
October | 0.344359E+10 | 0.447638E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146548E+10 | 0.347106E+09 |
November | 0.331698E+10 | 0.434435E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364261E+09 | 0.110979E+10 |
December | 0.344942E+10 | 0.445083E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239242E+09 | 0.209207E+10 |
Annual Sum or Average | 0.410346E+11 | 0.530479E+11 | 0.192612E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136003E+11 | 0.100624E+11 |
Minimum of Months | 0.313522E+10 | 0.405472E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69893212.59 | 16482255.79 |
Maximum of Months | 0.355148E+10 | 0.457860E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226643E+10 | 0.243204E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887461.26 | 0.135701E+10 |
February | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68805992.79 | 0.993650E+09 |
March | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147710E+09 | 0.864347E+09 |
April | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421326E+09 | 0.309267E+09 |
May | 0.174872E+10 | 0.233366E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118776E+10 | 14023736.99 |
June | 0.171530E+10 | 0.227877E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129331E+10 | 11128521.46 |
July | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123852E+10 | 8406427.30 |
August | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128312E+10 | 20228081.77 |
September | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.897556E+09 | 40813644.15 |
October | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.835556E+09 | 0.187171E+09 |
November | 0.165844E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207872E+09 | 0.618884E+09 |
December | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136539E+09 | 0.116909E+10 |
Annual Sum or Average | 0.205167E+11 | 0.273431E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.775796E+10 | 0.559402E+10 |
Minimum of Months | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887461.26 | 8406427.30 |
Maximum of Months | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129331E+10 | 0.135701E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887459.60 | 0.134984E+10 |
February | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68806009.10 | 0.988328E+09 |
March | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147718E+09 | 0.859601E+09 |
April | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421353E+09 | 0.308351E+09 |
May | 0.174872E+10 | 0.233366E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118804E+10 | 13681767.43 |
June | 0.171530E+10 | 0.227877E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129356E+10 | 10914894.54 |
July | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123882E+10 | 8268044.51 |
August | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128329E+10 | 19956193.00 |
September | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.897714E+09 | 40493481.24 |
October | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.835659E+09 | 0.186512E+09 |
November | 0.165844E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207879E+09 | 0.617485E+09 |
December | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136540E+09 | 0.116493E+10 |
Annual Sum or Average | 0.205167E+11 | 0.273431E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.775926E+10 | 0.556836E+10 |
Minimum of Months | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887459.60 | 8268044.51 |
Maximum of Months | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129356E+10 | 0.134984E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887453.51 | 0.133174E+10 |
February | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68806504.73 | 0.973921E+09 |
March | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147736E+09 | 0.845744E+09 |
April | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421402E+09 | 0.304960E+09 |
May | 0.174872E+10 | 0.233366E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118877E+10 | 12610606.46 |
June | 0.171530E+10 | 0.227877E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129405E+10 | 10308457.70 |
July | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123921E+10 | 7923616.61 |
August | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128343E+10 | 19484834.48 |
September | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.897771E+09 | 39778981.11 |
October | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.835734E+09 | 0.184823E+09 |
November | 0.165844E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207892E+09 | 0.613240E+09 |
December | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136542E+09 | 0.115294E+10 |
Annual Sum or Average | 0.205167E+11 | 0.273431E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.776123E+10 | 0.549748E+10 |
Minimum of Months | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887453.51 | 7923616.61 |
Maximum of Months | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129405E+10 | 0.133174E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40553958.60 | 0.155566E+10 |
February | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 70149812.99 | 0.112380E+10 |
March | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151408E+09 | 0.101761E+10 |
April | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.428920E+09 | 0.377350E+09 |
May | 0.174872E+10 | 0.233366E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121837E+10 | 24190266.15 |
June | 0.171530E+10 | 0.227877E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132251E+10 | 21798935.28 |
July | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127047E+10 | 14055775.53 |
August | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131733E+10 | 42829940.67 |
September | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.923714E+09 | 73306572.02 |
October | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.859344E+09 | 0.280220E+09 |
November | 0.165844E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211327E+09 | 0.743862E+09 |
December | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138730E+09 | 0.135688E+10 |
Annual Sum or Average | 0.205167E+11 | 0.273431E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.795283E+10 | 0.663157E+10 |
Minimum of Months | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40553958.60 | 14055775.53 |
Maximum of Months | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132251E+10 | 0.155566E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 5321.43 | 01-JAN-10:09 | 1348.26 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1459.20 | 16-JAN-15:00 | 7668.65 | 04-JAN-18:00 |
February | 4050.04 | 03-FEB-13:09 | 5321.43 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2107.21 | 02-FEB-13:00 | 8462.73 | 04-FEB-18:00 |
March | 4050.04 | 03-MAR-13:09 | 5321.43 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2854.25 | 26-MAR-14:00 | 7632.19 | 11-MAR-12:10 |
April | 4050.04 | 01-APR-12:09 | 5321.43 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4371.41 | 28-APR-15:00 | 3445.20 | 02-APR-11:10 |
May | 4050.04 | 05-MAY-12:09 | 5321.43 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4660.63 | 07-MAY-14:00 | 524.52 | 31-MAY-13:00 |
June | 4050.04 | 02-JUN-12:09 | 5321.43 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5074.35 | 14-JUN-14:00 | 534.24 | 01-JUN-13:00 |
July | 4050.04 | 01-JUL-12:09 | 5321.43 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5552.73 | 22-JUL-16:00 | 529.81 | 12-JUL-15:00 |
August | 4050.04 | 04-AUG-12:09 | 5321.43 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5648.88 | 30-AUG-16:00 | 1008.29 | 16-AUG-17:00 |
September | 4050.04 | 01-SEP-12:09 | 5321.43 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5771.84 | 09-SEP-17:00 | 1979.94 | 07-SEP-17:00 |
October | 4050.04 | 01-OCT-12:09 | 5321.43 | 01-OCT-09:09 | 1348.26 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4643.30 | 05-OCT-15:00 | 3395.48 | 27-OCT-16:00 |
November | 4050.04 | 03-NOV-12:09 | 5321.43 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2838.18 | 01-NOV-14:00 | 6140.96 | 15-NOV-18:00 |
December | 4050.04 | 01-DEC-13:09 | 5321.43 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2866.45 | 13-DEC-15:00 | 8685.40 | 20-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 5321.43 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 1459.20 | 524.52 | |||||
Maximum of Months | 4050.04 | 5321.43 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 5771.84 | 8685.40 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 2932.57 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 16-JAN-15:00 | 4346.94 | 04-JAN-18:00 |
February | 2024.96 | 03-FEB-13:09 | 2932.57 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1179.68 | 02-FEB-13:00 | 4744.95 | 04-FEB-18:00 |
March | 2024.96 | 03-MAR-13:09 | 2932.57 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1615.89 | 26-MAR-14:00 | 4292.50 | 11-MAR-12:10 |
April | 2024.96 | 01-APR-12:09 | 2932.57 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2466.22 | 28-APR-15:00 | 1970.35 | 02-APR-11:10 |
May | 2024.96 | 05-MAY-12:09 | 2932.57 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2629.46 | 07-MAY-14:00 | 296.85 | 31-MAY-13:00 |
June | 2024.96 | 02-JUN-12:09 | 2932.57 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2880.95 | 14-JUN-14:00 | 299.45 | 01-JUN-13:00 |
July | 2024.96 | 01-JUL-12:09 | 2932.57 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3158.61 | 22-JUL-16:00 | 298.90 | 12-JUL-15:00 |
August | 2024.96 | 04-AUG-12:09 | 2932.57 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3204.08 | 30-AUG-16:00 | 570.82 | 16-AUG-17:00 |
September | 2024.96 | 01-SEP-12:09 | 2932.57 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 09-SEP-17:00 | 1121.25 | 07-SEP-17:00 |
October | 2024.96 | 01-OCT-12:09 | 2932.57 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2632.03 | 05-OCT-15:00 | 1915.64 | 27-OCT-16:00 |
November | 2024.96 | 03-NOV-12:09 | 2932.57 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1611.84 | 01-NOV-14:00 | 3509.24 | 15-NOV-18:00 |
December | 2024.96 | 01-DEC-13:09 | 2932.57 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1622.28 | 13-DEC-15:00 | 4940.59 | 20-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2932.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 296.85 | |||||
Maximum of Months | 2024.96 | 2932.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 4940.59 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2599.23 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 16-JAN-15:00 | 4346.94 | 04-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2599.23 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1179.68 | 02-FEB-13:00 | 4744.95 | 04-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2599.23 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1615.86 | 26-MAR-14:00 | 4292.50 | 11-MAR-12:10 |
April | 2024.96 | 01-APR-12:09 | 2599.23 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2466.29 | 28-APR-15:00 | 1958.14 | 02-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 2599.23 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2629.40 | 07-MAY-14:00 | 296.85 | 31-MAY-13:00 |
June | 2024.96 | 03-JUN-12:09 | 2599.23 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2880.95 | 14-JUN-14:00 | 299.45 | 01-JUN-13:00 |
July | 2024.96 | 01-JUL-12:09 | 2599.23 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3158.61 | 22-JUL-16:00 | 298.90 | 12-JUL-15:00 |
August | 2024.96 | 05-AUG-12:09 | 2599.23 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3204.08 | 30-AUG-16:00 | 570.82 | 16-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 2599.23 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 09-SEP-17:00 | 1121.25 | 07-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2599.23 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2632.03 | 05-OCT-15:00 | 1915.65 | 27-OCT-16:00 |
November | 2024.96 | 04-NOV-12:09 | 2599.23 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1611.98 | 01-NOV-14:00 | 3460.25 | 15-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2599.23 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1622.23 | 13-DEC-15:00 | 4940.59 | 20-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2599.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 296.85 | |||||
Maximum of Months | 2024.96 | 2599.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 4940.59 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2599.23 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 16-JAN-15:00 | 4346.94 | 04-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2599.23 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1179.68 | 02-FEB-13:00 | 4744.95 | 04-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2599.23 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1615.85 | 26-MAR-14:00 | 4292.50 | 11-MAR-12:10 |
April | 2024.96 | 01-APR-12:09 | 2599.23 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2466.30 | 28-APR-15:00 | 1953.88 | 02-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 2599.23 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2629.40 | 07-MAY-14:00 | 296.85 | 31-MAY-13:00 |
June | 2024.96 | 03-JUN-12:09 | 2599.23 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2880.95 | 14-JUN-14:00 | 299.45 | 01-JUN-13:00 |
July | 2024.96 | 01-JUL-12:09 | 2599.23 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3158.61 | 22-JUL-16:00 | 298.90 | 12-JUL-15:00 |
August | 2024.96 | 05-AUG-12:09 | 2599.23 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3204.08 | 30-AUG-16:00 | 570.82 | 16-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 2599.23 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 09-SEP-17:00 | 1121.25 | 07-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2599.23 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2632.03 | 05-OCT-15:00 | 1915.65 | 27-OCT-16:00 |
November | 2024.96 | 04-NOV-12:09 | 2599.23 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1612.00 | 01-NOV-14:00 | 3444.54 | 15-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2599.23 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1622.22 | 13-DEC-15:00 | 4940.59 | 20-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2599.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 296.85 | |||||
Maximum of Months | 2024.96 | 2599.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 4940.59 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2599.23 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 16-JAN-15:00 | 4346.94 | 04-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2599.23 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1179.68 | 02-FEB-13:00 | 4744.95 | 04-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2599.23 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1615.85 | 26-MAR-14:00 | 4292.50 | 11-MAR-12:10 |
April | 2024.96 | 01-APR-12:09 | 2599.23 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2466.33 | 28-APR-15:00 | 1944.55 | 02-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 2599.23 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2629.40 | 07-MAY-14:00 | 296.85 | 31-MAY-13:00 |
June | 2024.96 | 03-JUN-12:09 | 2599.23 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2880.95 | 14-JUN-14:00 | 299.45 | 01-JUN-13:00 |
July | 2024.96 | 01-JUL-12:09 | 2599.23 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3158.61 | 22-JUL-16:00 | 298.90 | 12-JUL-15:00 |
August | 2024.96 | 05-AUG-12:09 | 2599.23 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3204.08 | 30-AUG-16:00 | 570.82 | 16-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 2599.23 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 09-SEP-17:00 | 1121.25 | 07-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2599.23 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2632.03 | 05-OCT-15:00 | 1915.65 | 27-OCT-16:00 |
November | 2024.96 | 04-NOV-12:09 | 2599.23 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1612.04 | 01-NOV-14:00 | 3422.73 | 15-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2599.23 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1622.21 | 13-DEC-15:00 | 4940.59 | 20-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2599.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 296.85 | |||||
Maximum of Months | 2024.96 | 2599.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 4940.59 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 3746.51 | 01-JAN-11:09 | 1348.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1448.80 | 16-JAN-15:00 | 7613.97 | 04-JAN-18:00 |
February | 5400.05 | 04-FEB-15:09 | 3746.51 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2070.02 | 02-FEB-13:00 | 8324.27 | 04-FEB-18:00 |
March | 5400.05 | 04-MAR-15:09 | 3746.51 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2830.80 | 26-MAR-14:00 | 7527.14 | 11-MAR-12:10 |
April | 5400.05 | 01-APR-14:09 | 3746.51 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4322.47 | 28-APR-15:00 | 3316.03 | 02-APR-11:10 |
May | 5400.05 | 06-MAY-14:09 | 3746.51 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4608.83 | 07-MAY-14:00 | 520.08 | 31-MAY-13:00 |
June | 5400.05 | 03-JUN-14:09 | 3746.51 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5045.04 | 14-JUN-14:00 | 525.36 | 01-JUN-13:00 |
July | 5400.05 | 01-JUL-14:09 | 3746.51 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5529.73 | 22-JUL-16:00 | 523.91 | 12-JUL-15:00 |
August | 5400.05 | 05-AUG-14:09 | 3746.51 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5611.65 | 30-AUG-16:00 | 1000.01 | 16-AUG-17:00 |
September | 5400.05 | 02-SEP-14:09 | 3746.51 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5702.99 | 09-SEP-17:00 | 1964.22 | 07-SEP-17:00 |
October | 5400.05 | 07-OCT-14:09 | 3746.51 | 01-OCT-10:09 | 1348.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4610.19 | 05-OCT-15:00 | 3357.62 | 27-OCT-16:00 |
November | 5400.05 | 04-NOV-14:09 | 3746.51 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2822.70 | 01-NOV-14:00 | 5959.78 | 15-NOV-18:00 |
December | 5400.05 | 02-DEC-15:09 | 3746.51 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2842.11 | 13-DEC-15:00 | 8649.42 | 20-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 3746.51 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 1448.80 | 520.08 | |||||
Maximum of Months | 5400.05 | 3746.51 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 5702.99 | 8649.42 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1931.10 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 16-JAN-15:00 | 4346.94 | 04-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1931.10 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1179.68 | 02-FEB-13:00 | 4744.95 | 04-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1931.10 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1615.85 | 26-MAR-14:00 | 4292.50 | 11-MAR-12:10 |
April | 2699.95 | 01-APR-14:09 | 1931.10 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2466.07 | 28-APR-15:00 | 1880.50 | 02-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1931.10 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2629.46 | 07-MAY-14:00 | 296.85 | 31-MAY-13:00 |
June | 2699.95 | 03-JUN-14:09 | 1931.10 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2880.95 | 14-JUN-14:00 | 299.45 | 01-JUN-13:00 |
July | 2699.95 | 01-JUL-14:09 | 1931.10 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3158.61 | 22-JUL-16:00 | 298.90 | 12-JUL-15:00 |
August | 2699.95 | 05-AUG-14:09 | 1931.10 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3204.08 | 30-AUG-16:00 | 570.82 | 16-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1931.10 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 09-SEP-17:00 | 1121.25 | 07-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1931.10 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2632.03 | 05-OCT-15:00 | 1915.62 | 27-OCT-16:00 |
November | 2699.95 | 04-NOV-14:09 | 1931.10 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1611.95 | 01-NOV-14:00 | 3394.84 | 15-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1931.10 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1622.24 | 13-DEC-15:00 | 4940.59 | 20-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 296.85 | |||||
Maximum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 4940.59 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1931.10 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 16-JAN-15:00 | 4346.94 | 04-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1931.10 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1179.68 | 02-FEB-13:00 | 4744.95 | 04-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1931.10 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1615.85 | 26-MAR-14:00 | 4292.50 | 11-MAR-12:10 |
April | 2699.95 | 01-APR-14:09 | 1931.10 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2466.07 | 28-APR-15:00 | 1867.55 | 02-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1931.10 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2629.46 | 07-MAY-14:00 | 296.85 | 31-MAY-13:00 |
June | 2699.95 | 03-JUN-14:09 | 1931.10 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2880.95 | 14-JUN-14:00 | 299.45 | 01-JUN-13:00 |
July | 2699.95 | 01-JUL-14:09 | 1931.10 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3158.61 | 22-JUL-16:00 | 298.90 | 12-JUL-15:00 |
August | 2699.95 | 05-AUG-14:09 | 1931.10 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3204.08 | 30-AUG-16:00 | 570.82 | 16-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1931.10 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 09-SEP-17:00 | 1121.25 | 07-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1931.10 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2632.03 | 05-OCT-15:00 | 1915.62 | 27-OCT-16:00 |
November | 2699.95 | 04-NOV-14:09 | 1931.10 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1611.96 | 01-NOV-14:00 | 3381.17 | 15-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1931.10 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1622.24 | 13-DEC-15:00 | 4940.59 | 20-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 296.85 | |||||
Maximum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 4940.59 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1931.10 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 16-JAN-15:00 | 4346.94 | 04-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1931.10 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1179.68 | 02-FEB-13:00 | 4744.95 | 04-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1931.10 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1615.84 | 26-MAR-14:00 | 4292.50 | 11-MAR-12:10 |
April | 2699.95 | 01-APR-14:09 | 1931.10 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2466.09 | 28-APR-15:00 | 1864.25 | 01-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 1931.10 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2629.46 | 07-MAY-14:00 | 296.85 | 31-MAY-13:00 |
June | 2699.95 | 03-JUN-14:09 | 1931.10 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2880.95 | 14-JUN-14:00 | 299.45 | 01-JUN-13:00 |
July | 2699.95 | 01-JUL-14:09 | 1931.10 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3158.61 | 22-JUL-16:00 | 298.90 | 12-JUL-15:00 |
August | 2699.95 | 05-AUG-14:09 | 1931.10 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3204.08 | 30-AUG-16:00 | 570.82 | 16-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1931.10 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 09-SEP-17:00 | 1121.25 | 07-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1931.10 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2632.03 | 05-OCT-15:00 | 1915.63 | 27-OCT-16:00 |
November | 2699.95 | 04-NOV-14:09 | 1931.10 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1612.00 | 01-NOV-14:00 | 3348.94 | 15-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1931.10 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1622.22 | 13-DEC-15:00 | 4940.59 | 20-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 296.85 | |||||
Maximum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 4940.59 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1931.10 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 837.55 | 16-JAN-15:00 | 4401.62 | 04-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1931.10 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1216.86 | 02-FEB-13:00 | 4883.41 | 04-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1931.10 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1639.23 | 26-MAR-14:00 | 4397.55 | 11-MAR-12:10 |
April | 2699.95 | 01-APR-14:09 | 1931.10 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2515.01 | 28-APR-15:00 | 1932.58 | 01-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 1931.10 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2680.96 | 07-MAY-14:00 | 301.30 | 31-MAY-13:00 |
June | 2699.95 | 03-JUN-14:09 | 1931.10 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2910.27 | 14-JUN-14:00 | 308.33 | 01-JUN-13:00 |
July | 2699.95 | 01-JUL-14:09 | 1931.10 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3181.61 | 22-JUL-16:00 | 304.80 | 12-JUL-15:00 |
August | 2699.95 | 05-AUG-14:09 | 1931.10 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3241.30 | 30-AUG-16:00 | 579.09 | 16-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1931.10 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3322.12 | 09-SEP-17:00 | 1136.97 | 07-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1931.10 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2665.14 | 05-OCT-15:00 | 1953.44 | 27-OCT-16:00 |
November | 2699.95 | 04-NOV-14:09 | 1931.10 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.72 | 01-NOV-14:00 | 3311.03 | 15-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1931.10 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1646.39 | 13-DEC-15:00 | 4976.57 | 20-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 837.55 | 301.30 | |||||
Maximum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3322.12 | 4976.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 31169.26 | 19-JAN-09:02 | 1687.52 | 14003.70 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.35 |
February | 36177.31 | 28-FEB-09:02 | 1687.52 | 14003.70 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 298.27 |
March | 34524.52 | 30-MAR-08:62 | 1687.52 | 14003.70 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.70 |
April | 34977.23 | 25-APR-08:62 | 1687.52 | 14003.70 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.62 |
May | 36058.76 | 07-MAY-07:02 | 1687.52 | 1400.28 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 28.78 | 0.00 |
June | 36648.36 | 11-JUN-07:02 | 1687.52 | 1400.28 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.73 |
July | 36332.95 | 09-JUL-07:01 | 2362.52 | 1960.39 | 524.32 | 0.00 | 0.00 | 0.00 | 0.00 | 211.53 | 0.00 |
August | 37959.62 | 20-AUG-07:02 | 2025.02 | 1680.33 | 449.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.17 |
September | 35202.28 | 22-SEP-08:62 | 2025.02 | 16804.44 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.62 |
October | 51551.80 | 26-OCT-08:61 | 2362.52 | 19605.18 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330.32 |
November | 38491.33 | 06-NOV-09:02 | 2025.02 | 16804.44 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.91 |
December | 40653.78 | 17-DEC-08:62 | 1687.52 | 1400.28 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 371.80 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 31169.26 | 1687.52 | 1400.28 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 51551.80 | 2362.52 | 19605.18 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 211.53 | 371.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17394.03 | 02-JAN-09:02 | 674.99 | 6173.83 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.89 |
February | 20934.51 | 28-FEB-09:02 | 843.73 | 7717.28 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.76 |
March | 20778.75 | 30-MAR-08:62 | 843.73 | 7717.28 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.78 |
April | 20568.95 | 24-APR-08:62 | 843.73 | 7717.28 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.94 |
May | 21600.92 | 07-MAY-07:02 | 843.73 | 771.73 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 14.78 | 0.00 |
June | 21221.77 | 11-JUN-07:02 | 843.73 | 771.73 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.49 |
July | 21812.43 | 09-JUL-07:01 | 1181.23 | 1080.42 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 121.91 | 0.00 |
August | 22120.32 | 20-AUG-07:02 | 1012.48 | 926.07 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.67 |
September | 20953.21 | 03-SEP-07:02 | 1012.48 | 926.07 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 69.96 | 0.00 |
October | 27209.94 | 26-OCT-08:61 | 1181.23 | 10804.20 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.06 |
November | 22248.82 | 06-NOV-09:02 | 1012.48 | 9260.74 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.93 |
December | 22118.95 | 17-DEC-08:62 | 843.73 | 771.73 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17394.03 | 674.99 | 771.73 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27209.94 | 1181.23 | 10804.20 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 121.91 | 240.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 22878.87 | 02-JAN-08:62 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 367.97 |
February | 19027.03 | 28-FEB-08:62 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.24 |
March | 18225.26 | 27-MAR-07:02 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.94 |
April | 19189.95 | 25-APR-07:02 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.66 |
May | 18843.78 | 12-MAY-07:01 | 1181.23 | 9576.10 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.45 |
June | 18618.58 | 12-JUN-07:01 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.61 |
July | 16363.17 | 19-JUL-07:01 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 79.87 | 0.00 |
August | 18474.10 | 31-AUG-07:01 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.26 |
September | 18328.68 | 23-SEP-07:01 | 1181.23 | 9576.10 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.23 |
October | 28900.84 | 17-OCT-07:02 | 1012.48 | 8208.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 394.71 |
November | 19594.51 | 06-NOV-08:62 | 1012.48 | 8208.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.73 |
December | 23504.41 | 17-DEC-09:02 | 1012.48 | 8208.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16363.17 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28900.84 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 79.87 | 394.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 22936.18 | 02-JAN-08:62 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 367.86 |
February | 19037.83 | 28-FEB-08:62 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.10 |
March | 18244.53 | 27-MAR-07:02 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.00 |
April | 19248.03 | 25-APR-07:02 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.89 |
May | 18941.29 | 12-MAY-07:01 | 1181.23 | 9576.10 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.35 |
June | 18714.67 | 12-JUN-07:01 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.92 |
July | 16440.64 | 19-JUL-07:01 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 79.97 | 0.00 |
August | 18542.49 | 31-AUG-07:01 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.27 |
September | 18413.01 | 23-SEP-07:01 | 1181.23 | 9576.10 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.71 |
October | 29022.72 | 17-OCT-07:02 | 1012.48 | 8208.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 396.23 |
November | 19693.65 | 06-NOV-08:62 | 1012.48 | 8208.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.32 |
December | 23580.44 | 17-DEC-09:02 | 1012.48 | 8208.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16440.64 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29022.72 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 79.97 | 396.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 22753.17 | 02-JAN-08:62 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 364.35 |
February | 18827.62 | 28-FEB-08:62 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.86 |
March | 18029.88 | 27-MAR-07:02 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.03 |
April | 19044.62 | 25-APR-07:02 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.81 |
May | 18748.96 | 12-MAY-07:01 | 1181.23 | 9576.10 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.67 |
June | 18623.57 | 12-JUN-07:01 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.91 |
July | 16305.27 | 19-JUL-07:01 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 79.86 | 0.00 |
August | 18419.68 | 31-AUG-07:01 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.83 |
September | 18228.27 | 23-SEP-07:01 | 1181.23 | 9576.10 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.16 |
October | 28826.87 | 17-OCT-07:02 | 1012.48 | 8208.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 393.02 |
November | 19521.30 | 06-NOV-08:62 | 1012.48 | 8208.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.85 |
December | 23385.85 | 17-DEC-09:02 | 1012.48 | 8208.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16305.27 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28826.87 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 79.86 | 393.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 39609.48 | 01-JAN-10:02 | 3712.53 | 9859.20 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 311.05 |
February | 34026.40 | 28-FEB-09:02 | 3712.53 | 9859.20 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.25 |
March | 32852.29 | 30-MAR-08:62 | 3712.53 | 9859.20 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.89 |
April | 33158.99 | 25-APR-08:62 | 3712.53 | 9859.20 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.67 |
May | 34333.81 | 12-MAY-08:61 | 5197.55 | 13802.87 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.81 |
June | 33944.14 | 14-JUN-08:61 | 5940.06 | 15774.71 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 142.70 | 0.00 |
July | 31065.55 | 18-JUL-08:61 | 5940.06 | 15774.71 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 174.48 | 0.00 |
August | 34427.61 | 31-AUG-08:61 | 5940.06 | 15774.71 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 133.24 | 0.00 |
September | 33052.17 | 22-SEP-08:62 | 4455.04 | 11831.03 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.26 |
October | 48066.02 | 26-OCT-08:61 | 5197.55 | 13802.87 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 300.27 |
November | 37021.03 | 05-NOV-09:02 | 3712.53 | 9859.20 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 273.29 |
December | 43577.82 | 17-DEC-10:02 | 4455.04 | 11831.03 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 457.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 31065.55 | 3712.53 | 9859.20 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 48066.02 | 5940.06 | 15774.71 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 174.48 | 457.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20695.35 | 01-JAN-10:02 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.17 |
February | 17768.70 | 28-FEB-09:02 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.47 |
March | 17206.56 | 30-MAR-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.07 |
April | 17337.21 | 25-APR-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.56 |
May | 17947.45 | 12-MAY-08:61 | 2598.70 | 7114.56 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.07 |
June | 17769.27 | 14-JUN-08:61 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 85.31 | 0.00 |
July | 16277.31 | 18-JUL-08:61 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 102.82 | 0.00 |
August | 18028.60 | 31-AUG-08:61 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 80.19 | 0.00 |
September | 17291.09 | 23-SEP-08:61 | 2598.70 | 7114.56 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.82 | 0.00 |
October | 25146.11 | 26-OCT-08:61 | 2598.70 | 7114.56 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.67 |
November | 19346.87 | 05-NOV-09:02 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.37 |
December | 22800.45 | 17-DEC-10:02 | 2227.46 | 6098.20 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 252.83 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16277.31 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25146.11 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 102.82 | 252.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20557.88 | 01-JAN-10:02 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.36 |
February | 17635.81 | 28-FEB-09:02 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.85 |
March | 17075.75 | 30-MAR-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.48 |
April | 17218.92 | 25-APR-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.20 |
May | 17834.67 | 12-MAY-08:61 | 2598.70 | 7114.56 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.84 |
June | 17658.56 | 14-JUN-08:61 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 86.29 | 0.00 |
July | 16174.95 | 18-JUL-08:61 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 103.62 | 0.00 |
August | 17914.56 | 31-AUG-08:61 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 81.08 | 0.00 |
September | 17186.98 | 23-SEP-08:61 | 2598.70 | 7114.56 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 1.80 | 0.00 |
October | 25012.19 | 26-OCT-08:61 | 2598.70 | 7114.56 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.78 |
November | 19232.74 | 05-NOV-09:02 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.19 |
December | 22667.82 | 17-DEC-10:02 | 2227.46 | 6098.20 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16174.95 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25012.19 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 103.62 | 251.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20408.41 | 01-JAN-10:02 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.08 |
February | 16144.12 | 28-FEB-09:02 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.12 |
March | 14879.17 | 30-MAR-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.05 |
April | 17003.84 | 22-APR-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.22 |
May | 17800.73 | 12-MAY-08:61 | 2598.70 | 7114.56 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.35 |
June | 17657.69 | 14-JUN-08:61 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 88.50 | 0.00 |
July | 16178.27 | 18-JUL-08:61 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 105.50 | 0.00 |
August | 17947.59 | 31-AUG-08:61 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 82.15 | 0.00 |
September | 17181.12 | 23-SEP-08:61 | 2598.70 | 7114.56 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 4.15 | 0.00 |
October | 25016.26 | 26-OCT-08:61 | 2598.70 | 7114.56 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.47 |
November | 19138.80 | 05-NOV-09:02 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.90 |
December | 22583.80 | 17-DEC-10:02 | 2227.46 | 6098.20 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14879.17 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25016.26 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 105.50 | 246.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19815.71 | 01-JAN-10:02 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.21 |
February | 10223.15 | 28-FEB-09:02 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.23 |
March | 12669.92 | 07-MAR-09:02 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.74 |
April | 18405.04 | 23-APR-09:02 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 3.24 | 0.00 |
May | 18841.78 | 12-MAY-08:61 | 2598.70 | 7114.56 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.61 |
June | 19475.07 | 11-JUN-09:01 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 101.47 | 0.00 |
July | 17650.27 | 19-JUL-08:61 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 156.98 | 0.00 |
August | 20607.59 | 31-AUG-08:61 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 85.23 | 0.00 |
September | 18580.72 | 02-SEP-08:61 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 119.08 | 0.00 |
October | 28448.35 | 26-OCT-08:61 | 2598.70 | 7114.56 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.87 |
November | 20078.94 | 06-NOV-09:02 | 2227.46 | 6098.20 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.47 |
December | 25407.48 | 17-DEC-10:02 | 2227.46 | 6098.20 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10223.15 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28448.35 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 156.98 | 281.76 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.782513E+11 | 80077.89 | 19-JAN-14:30 | 0.354415E+10 | 81424.60 | 10-JAN-09:09 |
February | 0.733023E+11 | 81507.49 | 02-FEB-13:20 | 0.420140E+10 | 96522.95 | 05-FEB-10:09 |
March | 0.838680E+11 | 83731.75 | 30-MAR-12:50 | 0.297581E+10 | 84073.90 | 11-MAR-12:09 |
April | 0.900250E+11 | 100209.91 | 28-APR-16:19 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.116653E+12 | 103218.19 | 30-MAY-12:50 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.117775E+12 | 109297.70 | 28-JUN-13:50 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.124390E+12 | 117646.54 | 22-JUL-16:49 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.126219E+12 | 108886.02 | 03-AUG-14:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.115976E+12 | 126786.86 | 10-SEP-14:20 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.112639E+12 | 117766.09 | 07-OCT-12:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.867777E+11 | 94544.32 | 02-NOV-13:39 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.830374E+11 | 86498.24 | 15-DEC-17:40 | 0.348777E+10 | 89438.01 | 21-DEC-09:09 |
Annual Sum or Average | 0.120891E+13 | 0.142091E+11 | ||||
Minimum of Months | 0.733023E+11 | 80077.89 | 0.00 | 0.00 | ||
Maximum of Months | 0.126219E+12 | 126786.86 | 0.420140E+10 | 96522.95 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.373403E+11 | 0.981001E+10 | 0.108804E+11 | 0.00 | 0.879000E+10 | 0.00 | 0.00 | 0.617133E+10 | 0.00 | 0.00 | 0.00 | 0.525920E+10 | 0.00 |
February | 0.337970E+11 | 0.840569E+10 | 0.985143E+10 | 0.00 | 0.800227E+10 | 0.00 | 0.00 | 0.850092E+10 | 0.00 | 0.00 | 0.00 | 0.474497E+10 | 0.00 |
March | 0.378801E+11 | 0.862136E+10 | 0.110560E+11 | 0.00 | 0.894623E+10 | 0.00 | 0.00 | 0.121336E+11 | 0.00 | 0.00 | 0.00 | 0.523071E+10 | 0.00 |
April | 0.362171E+11 | 0.767933E+10 | 0.105544E+11 | 0.00 | 0.851820E+10 | 0.00 | 0.00 | 0.221024E+11 | 0.00 | 0.00 | 0.00 | 0.495362E+10 | 0.00 |
May | 0.376032E+11 | 0.733671E+10 | 0.109629E+11 | 0.00 | 0.904913E+10 | 0.00 | 0.00 | 0.466659E+11 | 0.00 | 0.00 | 0.00 | 0.503509E+10 | 0.00 |
June | 0.366114E+11 | 0.677413E+10 | 0.106855E+11 | 0.00 | 0.911403E+10 | 0.00 | 0.00 | 0.497668E+11 | 0.00 | 0.00 | 0.00 | 0.482314E+10 | 0.00 |
July | 0.372230E+11 | 0.717213E+10 | 0.108424E+11 | 0.00 | 0.974434E+10 | 0.00 | 0.00 | 0.544868E+11 | 0.00 | 0.00 | 0.00 | 0.492136E+10 | 0.00 |
August | 0.378660E+11 | 0.765673E+10 | 0.110491E+11 | 0.00 | 0.985764E+10 | 0.00 | 0.00 | 0.548278E+11 | 0.00 | 0.00 | 0.00 | 0.496215E+10 | 0.00 |
September | 0.362312E+11 | 0.806335E+10 | 0.105613E+11 | 0.00 | 0.912676E+10 | 0.00 | 0.00 | 0.471653E+11 | 0.00 | 0.00 | 0.00 | 0.482844E+10 | 0.00 |
October | 0.373403E+11 | 0.902825E+10 | 0.108804E+11 | 0.00 | 0.926485E+10 | 0.00 | 0.00 | 0.410687E+11 | 0.00 | 0.00 | 0.00 | 0.505694E+10 | 0.00 |
November | 0.361749E+11 | 0.931600E+10 | 0.105443E+11 | 0.00 | 0.855100E+10 | 0.00 | 0.00 | 0.172146E+11 | 0.00 | 0.00 | 0.00 | 0.497686E+10 | 0.00 |
December | 0.372370E+11 | 0.996087E+10 | 0.108529E+11 | 0.00 | 0.880859E+10 | 0.00 | 0.00 | 0.109611E+11 | 0.00 | 0.00 | 0.00 | 0.521689E+10 | 0.00 |
Annual Sum or Average | 0.441522E+12 | 0.998246E+11 | 0.128721E+12 | 0.00 | 0.107773E+12 | 0.00 | 0.00 | 0.371065E+12 | 0.00 | 0.00 | 0.00 | 0.600094E+11 | 0.00 |
Minimum of Months | 0.337970E+11 | 0.677413E+10 | 0.985143E+10 | 0.00 | 0.800227E+10 | 0.00 | 0.00 | 0.617133E+10 | 0.00 | 0.00 | 0.00 | 0.474497E+10 | 0.00 |
Maximum of Months | 0.378801E+11 | 0.996087E+10 | 0.110560E+11 | 0.00 | 0.985764E+10 | 0.00 | 0.00 | 0.548278E+11 | 0.00 | 0.00 | 0.00 | 0.525920E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.354415E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.420140E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.297581E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.348777E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.142091E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.420140E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 27522.57 | 01-JAN-11:09 | 7619.51 | 01-JAN-06:10 | 8089.53 | 01-JAN-11:09 | 0.00 | 7590.83 | 10-JAN-09:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 27522.57 | 01-FEB-10:09 | 7619.51 | 01-FEB-06:10 | 8089.53 | 01-FEB-10:09 | 0.00 | 7892.89 | 05-FEB-10:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 27522.57 | 01-MAR-10:09 | 7619.51 | 01-MAR-06:10 | 8089.53 | 01-MAR-10:09 | 0.00 | 7644.57 | 11-MAR-12:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 27522.57 | 01-APR-09:09 | 7619.51 | 01-APR-05:10 | 8089.53 | 01-APR-09:09 | 0.00 | 7889.78 | 29-APR-08:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 27522.57 | 01-MAY-09:09 | 7619.51 | 01-MAY-05:10 | 8089.53 | 01-MAY-09:09 | 0.00 | 8647.65 | 22-MAY-08:09 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 27522.57 | 01-JUN-09:09 | 7619.51 | 01-JUN-05:10 | 8089.53 | 01-JUN-09:09 | 0.00 | 9176.77 | 19-JUN-08:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 27522.57 | 01-JUL-09:09 | 7619.51 | 01-JUL-05:10 | 8089.53 | 01-JUL-09:09 | 0.00 | 10238.81 | 22-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 27522.57 | 01-AUG-09:09 | 7619.51 | 01-AUG-05:10 | 8089.53 | 01-AUG-09:09 | 0.00 | 9160.77 | 14-AUG-08:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 27522.57 | 01-SEP-09:09 | 7619.51 | 01-SEP-05:10 | 8089.53 | 01-SEP-09:09 | 0.00 | 11796.00 | 10-SEP-12:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 27522.57 | 01-OCT-10:09 | 7619.51 | 01-OCT-05:10 | 8089.53 | 01-OCT-10:09 | 0.00 | 10503.67 | 07-OCT-12:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 27522.57 | 01-NOV-09:09 | 7619.51 | 01-NOV-05:10 | 8089.53 | 01-NOV-09:09 | 0.00 | 7873.29 | 02-NOV-08:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 27522.57 | 01-DEC-10:09 | 7619.51 | 01-DEC-06:10 | 8089.53 | 01-DEC-10:09 | 0.00 | 7749.40 | 21-DEC-09:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 27522.57 | 7619.51 | 8089.53 | 0.00 | 7590.83 | 0.00 | 0.00 | |||||
Maximum of Months | 27522.57 | 7619.51 | 8089.53 | 0.00 | 11796.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 31491.93 | 19-JAN-13:00 | 0.00 | 0.00 | 0.00 | 11817.66 | 04-JAN-14:00 | 0.00 |
February | 33666.94 | 24-FEB-13:30 | 0.00 | 0.00 | 0.00 | 8459.10 | 07-FEB-13:09 | 0.00 |
March | 37118.25 | 30-MAR-12:00 | 0.00 | 0.00 | 0.00 | 9693.06 | 13-MAR-12:30 | 0.00 |
April | 49982.10 | 28-APR-16:10 | 0.00 | 0.00 | 0.00 | 7568.36 | 10-APR-12:09 | 0.00 |
May | 53602.81 | 30-MAY-12:00 | 0.00 | 0.00 | 0.00 | 7563.77 | 01-MAY-12:09 | 0.00 |
June | 59818.55 | 28-JUN-13:00 | 0.00 | 0.00 | 0.00 | 7540.26 | 16-JUN-13:39 | 0.00 |
July | 67622.41 | 22-JUL-15:00 | 0.00 | 0.00 | 0.00 | 9661.69 | 26-JUL-13:20 | 0.00 |
August | 60148.29 | 03-AUG-14:00 | 0.00 | 0.00 | 0.00 | 8318.64 | 01-AUG-17:19 | 0.00 |
September | 74511.00 | 10-SEP-13:30 | 0.00 | 0.00 | 0.00 | 7557.76 | 18-SEP-12:00 | 0.00 |
October | 66203.16 | 07-OCT-12:00 | 0.00 | 0.00 | 0.00 | 9682.86 | 30-OCT-12:20 | 0.00 |
November | 47839.35 | 02-NOV-12:00 | 0.00 | 0.00 | 0.00 | 8457.07 | 10-NOV-20:40 | 0.00 |
December | 40284.45 | 15-DEC-13:00 | 0.00 | 0.00 | 0.00 | 8509.63 | 28-DEC-14:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 31491.93 | 0.00 | 0.00 | 0.00 | 7540.26 | 0.00 | ||
Maximum of Months | 74511.00 | 0.00 | 0.00 | 0.00 | 11817.66 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 80077.89 | 19-JAN-14:30 | 27522.57 | 8089.53 | 0.00 | 0.00 | 5973.92 | 0.00 | 0.00 | 30917.31 | 0.00 |
February | 81507.49 | 02-FEB-13:20 | 27522.57 | 8089.53 | 0.00 | 0.00 | 5973.92 | 0.00 | 0.00 | 32721.81 | 0.00 |
March | 83731.75 | 30-MAR-12:50 | 27522.57 | 8089.53 | 0.00 | 0.00 | 5973.92 | 0.00 | 0.00 | 36683.33 | 0.00 |
April | 100209.91 | 28-APR-16:19 | 27522.57 | 8089.53 | 0.00 | 0.00 | 7307.66 | 0.00 | 0.00 | 49747.04 | 0.00 |
May | 103218.19 | 30-MAY-12:50 | 27522.57 | 8089.53 | 0.00 | 0.00 | 7816.36 | 0.00 | 0.00 | 52231.92 | 0.00 |
June | 109297.70 | 28-JUN-13:50 | 27522.57 | 8089.53 | 0.00 | 0.00 | 8978.21 | 0.00 | 0.00 | 59266.50 | 0.00 |
July | 117646.54 | 22-JUL-16:49 | 27522.57 | 8089.53 | 0.00 | 0.00 | 9816.15 | 0.00 | 0.00 | 64683.49 | 0.00 |
August | 108886.02 | 03-AUG-14:09 | 27522.57 | 8089.53 | 0.00 | 0.00 | 8880.70 | 0.00 | 0.00 | 58960.23 | 0.00 |
September | 126786.86 | 10-SEP-14:20 | 27522.57 | 8089.53 | 0.00 | 0.00 | 11589.45 | 0.00 | 0.00 | 74165.86 | 0.00 |
October | 117766.09 | 07-OCT-12:00 | 27522.57 | 8089.53 | 0.00 | 0.00 | 10503.67 | 0.00 | 0.00 | 66203.16 | 0.00 |
November | 94544.32 | 02-NOV-13:39 | 27522.57 | 8089.53 | 0.00 | 0.00 | 6929.32 | 0.00 | 0.00 | 46553.91 | 0.00 |
December | 86498.24 | 15-DEC-17:40 | 27522.57 | 8089.53 | 7619.51 | 0.00 | 5973.92 | 0.00 | 0.00 | 31851.62 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 80077.89 | 27522.57 | 8089.53 | 0.00 | 0.00 | 5973.92 | 0.00 | 0.00 | 30917.31 | 0.00 | |
Maximum of Months | 126786.86 | 27522.57 | 8089.53 | 7619.51 | 0.00 | 11589.45 | 0.00 | 0.00 | 74165.86 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 81424.60 | 10-JAN-09:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 96522.95 | 05-FEB-10:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 84073.90 | 11-MAR-12:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 89438.01 | 21-DEC-09:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 96522.95 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.55 | 0.17 | 24.55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.47 | 0.33 | 24.47 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.50 | 24.50 | 0.50 | 24.50 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.55 | 0.33 | 24.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.47 | 0.17 | 24.47 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.49 | 1.00 | 24.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.49 | 0.67 | 24.49 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.50 | 0.33 | 24.50 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.45 | 0.17 | 24.45 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.33 | 24.49 | 2.33 | 24.49 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.50 | 1.00 | 24.50 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.47 | 0.33 | 24.47 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.48 | 1.00 | 24.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.50 | 0.67 | 24.50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.52 | 0.33 | 24.52 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.33 | 24.49 | 2.33 | 24.49 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.52 | 1.00 | 24.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.47 | 0.17 | 24.47 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.50 | 0.83 | 24.50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.49 | 0.67 | 24.49 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.52 | 0.33 | 24.52 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.45 | 0.17 | 24.45 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.17 | 24.49 | 2.17 | 24.49 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.52 | 0.83 | 24.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.45 | 0.33 | 24.45 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.51 | 0.67 | 24.51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.55 | 2.00 | 24.55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.57 | 0.83 | 24.57 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.54 | 1.50 | 24.54 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.50 | 0.67 | 24.50 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 6.00 | 24.54 | 6.00 | 24.54 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.57 | 2.00 | 24.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.50 | 0.50 | 24.50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.53 | 1.83 | 24.53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.55 | 0.83 | 24.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.51 | 1.50 | 24.51 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.52 | 0.33 | 24.52 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 5.00 | 24.52 | 5.00 | 24.52 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.55 | 1.83 | 24.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.50 | 0.50 | 24.50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.54 | 1.83 | 24.54 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.55 | 0.83 | 24.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.51 | 1.50 | 24.51 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.51 | 0.33 | 24.51 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 5.00 | 24.53 | 5.00 | 24.53 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.55 | 1.83 | 24.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.49 | 0.33 | 24.49 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.53 | 1.83 | 24.53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.55 | 0.83 | 24.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.52 | 1.17 | 24.52 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.51 | 0.33 | 24.51 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.50 | 24.53 | 4.50 | 24.53 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.55 | 1.83 | 24.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.48 | 0.17 | 24.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.49 | 1.33 | 24.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.50 | 0.67 | 24.50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.50 | 0.67 | 24.50 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.53 | 0.17 | 24.53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.00 | 24.50 | 3.00 | 24.50 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.53 | 1.33 | 24.53 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 322.50 | 22.18 | 162.83 | 22.72 | 33.83 | 22.76 |
February | 243.00 | 22.61 | 227.17 | 23.18 | 66.17 | 23.23 |
March | 216.50 | 22.56 | 231.00 | 23.22 | 39.17 | 23.24 |
April | 75.17 | 23.75 | 374.67 | 23.88 | 49.83 | 23.89 |
May | 110.00 | 24.15 | 496.00 | 24.00 | 110.00 | 24.02 |
June | 97.67 | 24.19 | 481.00 | 24.01 | 97.67 | 24.04 |
July | 205.50 | 24.10 | 495.00 | 24.01 | 205.50 | 24.03 |
August | 133.00 | 24.24 | 497.00 | 24.04 | 133.00 | 24.08 |
September | 154.17 | 24.13 | 479.00 | 24.01 | 154.17 | 24.03 |
October | 107.17 | 24.02 | 454.17 | 23.97 | 99.00 | 23.99 |
November | 94.17 | 23.61 | 327.50 | 23.86 | 41.50 | 23.88 |
December | 216.33 | 22.43 | 231.33 | 23.17 | 37.00 | 23.21 |
Annual Sum or Average | 1975.17 | 23.23 | 4456.67 | 23.72 | 1066.83 | 23.76 |
Minimum of Months | 75.17 | 22.18 | 162.83 | 22.72 | 33.83 | 22.76 |
Maximum of Months | 322.50 | 24.24 | 497.00 | 24.04 | 205.50 | 24.08 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 271.33 | 22.74 | 155.50 | 23.17 | 15.00 | 23.19 |
February | 180.00 | 22.91 | 214.67 | 23.44 | 32.67 | 23.47 |
March | 167.00 | 22.89 | 216.33 | 23.47 | 11.17 | 23.48 |
April | 33.00 | 23.75 | 345.17 | 23.90 | 13.83 | 23.90 |
May | 57.33 | 23.95 | 493.17 | 23.97 | 57.33 | 23.97 |
June | 54.33 | 23.89 | 479.33 | 23.97 | 54.33 | 23.96 |
July | 136.17 | 23.92 | 494.83 | 23.96 | 136.17 | 23.96 |
August | 83.17 | 23.96 | 496.00 | 23.99 | 83.17 | 23.98 |
September | 107.50 | 23.94 | 476.83 | 23.96 | 107.50 | 23.96 |
October | 77.83 | 23.86 | 440.67 | 23.95 | 70.33 | 23.94 |
November | 60.67 | 23.70 | 313.50 | 23.90 | 24.50 | 23.90 |
December | 178.33 | 22.77 | 226.83 | 23.40 | 22.00 | 23.42 |
Annual Sum or Average | 1406.67 | 23.28 | 4352.83 | 23.79 | 628.00 | 23.80 |
Minimum of Months | 33.00 | 22.74 | 155.50 | 23.17 | 11.17 | 23.19 |
Maximum of Months | 271.33 | 23.96 | 496.00 | 23.99 | 136.17 | 23.98 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 238.33 | 22.25 | 118.50 | 22.80 | 21.67 | 22.85 |
February | 165.33 | 22.61 | 168.67 | 23.26 | 35.00 | 23.30 |
March | 156.17 | 22.62 | 168.67 | 23.33 | 22.00 | 23.37 |
April | 63.33 | 23.91 | 278.33 | 23.99 | 44.00 | 24.01 |
May | 108.50 | 24.31 | 375.00 | 24.13 | 108.50 | 24.17 |
June | 114.00 | 24.40 | 366.00 | 24.17 | 114.00 | 24.21 |
July | 208.67 | 24.24 | 369.00 | 24.16 | 208.67 | 24.18 |
August | 143.67 | 24.30 | 379.00 | 24.15 | 143.67 | 24.18 |
September | 169.17 | 24.24 | 360.00 | 24.13 | 169.17 | 24.16 |
October | 107.33 | 24.20 | 336.83 | 24.11 | 101.83 | 24.13 |
November | 76.17 | 23.75 | 247.83 | 23.93 | 43.83 | 23.96 |
December | 176.33 | 22.55 | 169.00 | 23.23 | 37.67 | 23.30 |
Annual Sum or Average | 1727.00 | 23.47 | 3336.83 | 23.85 | 1050.00 | 23.92 |
Minimum of Months | 63.33 | 22.25 | 118.50 | 22.80 | 21.67 | 22.85 |
Maximum of Months | 238.33 | 24.40 | 379.00 | 24.17 | 208.67 | 24.21 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 247.00 | 22.22 | 117.50 | 22.75 | 25.00 | 22.81 |
February | 174.67 | 22.60 | 165.67 | 23.22 | 37.00 | 23.27 |
March | 166.67 | 22.64 | 164.67 | 23.31 | 23.83 | 23.36 |
April | 65.00 | 23.90 | 276.00 | 23.99 | 44.33 | 24.01 |
May | 106.50 | 24.32 | 375.00 | 24.14 | 106.50 | 24.17 |
June | 111.83 | 24.42 | 366.00 | 24.17 | 111.83 | 24.22 |
July | 204.83 | 24.25 | 369.00 | 24.16 | 204.83 | 24.18 |
August | 141.17 | 24.31 | 379.00 | 24.15 | 141.17 | 24.19 |
September | 166.00 | 24.24 | 360.00 | 24.13 | 166.00 | 24.16 |
October | 106.00 | 24.20 | 336.67 | 24.11 | 100.50 | 24.13 |
November | 78.50 | 23.73 | 244.17 | 23.93 | 43.83 | 23.95 |
December | 182.00 | 22.53 | 163.17 | 23.20 | 37.67 | 23.27 |
Annual Sum or Average | 1750.17 | 23.45 | 3316.83 | 23.84 | 1042.50 | 23.90 |
Minimum of Months | 65.00 | 22.22 | 117.50 | 22.75 | 23.83 | 22.81 |
Maximum of Months | 247.00 | 24.42 | 379.00 | 24.17 | 204.83 | 24.22 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 255.17 | 22.18 | 116.50 | 22.70 | 29.50 | 22.77 |
February | 185.17 | 22.58 | 165.17 | 23.18 | 41.00 | 23.23 |
March | 178.67 | 22.65 | 160.33 | 23.27 | 28.67 | 23.32 |
April | 70.67 | 23.87 | 273.17 | 23.98 | 48.00 | 24.00 |
May | 112.17 | 24.30 | 375.00 | 24.13 | 112.17 | 24.16 |
June | 118.33 | 24.37 | 366.00 | 24.16 | 118.33 | 24.20 |
July | 213.50 | 24.23 | 369.00 | 24.15 | 213.50 | 24.17 |
August | 144.83 | 24.29 | 379.00 | 24.15 | 144.83 | 24.18 |
September | 171.67 | 24.23 | 360.00 | 24.13 | 171.67 | 24.15 |
October | 109.17 | 24.19 | 335.33 | 24.11 | 103.17 | 24.13 |
November | 84.17 | 23.69 | 236.17 | 23.91 | 45.33 | 23.94 |
December | 193.00 | 22.53 | 160.17 | 23.17 | 40.00 | 23.25 |
Annual Sum or Average | 1836.50 | 23.42 | 3295.83 | 23.82 | 1096.17 | 23.89 |
Minimum of Months | 70.67 | 22.18 | 116.50 | 22.70 | 28.67 | 22.77 |
Maximum of Months | 255.17 | 24.37 | 379.00 | 24.16 | 213.50 | 24.20 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 249.33 | 22.24 | 104.00 | 22.70 | 37.83 | 22.78 |
February | 172.67 | 22.56 | 150.67 | 23.15 | 38.67 | 23.19 |
March | 179.67 | 22.73 | 141.50 | 23.25 | 33.50 | 23.31 |
April | 69.50 | 23.86 | 246.00 | 23.92 | 44.00 | 23.93 |
May | 108.17 | 24.09 | 344.00 | 24.00 | 108.17 | 24.02 |
June | 122.50 | 24.08 | 336.00 | 24.00 | 122.50 | 24.01 |
July | 220.67 | 24.05 | 338.00 | 24.02 | 220.67 | 24.03 |
August | 156.50 | 24.03 | 348.00 | 23.98 | 156.50 | 23.99 |
September | 191.83 | 24.05 | 330.00 | 24.01 | 191.83 | 24.02 |
October | 110.00 | 24.05 | 309.67 | 23.99 | 104.50 | 24.01 |
November | 86.50 | 23.65 | 212.50 | 23.84 | 48.83 | 23.86 |
December | 185.67 | 22.55 | 142.50 | 23.13 | 41.33 | 23.21 |
Annual Sum or Average | 1853.00 | 23.37 | 3002.83 | 23.73 | 1148.33 | 23.78 |
Minimum of Months | 69.50 | 22.24 | 104.00 | 22.70 | 33.50 | 22.78 |
Maximum of Months | 249.33 | 24.09 | 348.00 | 24.02 | 220.67 | 24.03 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 251.83 | 22.24 | 102.17 | 22.68 | 37.83 | 22.77 |
February | 178.33 | 22.58 | 150.67 | 23.14 | 40.17 | 23.18 |
March | 188.17 | 22.76 | 136.50 | 23.24 | 34.50 | 23.30 |
April | 76.50 | 23.86 | 242.50 | 23.92 | 45.67 | 23.93 |
May | 107.83 | 24.09 | 344.00 | 24.00 | 107.83 | 24.01 |
June | 123.50 | 24.07 | 336.00 | 23.99 | 123.50 | 24.01 |
July | 219.50 | 24.05 | 338.00 | 24.02 | 219.50 | 24.02 |
August | 158.83 | 24.02 | 348.00 | 23.98 | 158.83 | 23.99 |
September | 194.33 | 24.05 | 330.00 | 24.01 | 194.33 | 24.02 |
October | 112.17 | 24.04 | 305.83 | 23.99 | 105.50 | 24.01 |
November | 94.17 | 23.67 | 202.17 | 23.84 | 51.00 | 23.86 |
December | 188.00 | 22.56 | 140.83 | 23.13 | 41.50 | 23.20 |
Annual Sum or Average | 1893.17 | 23.37 | 2976.67 | 23.72 | 1160.17 | 23.77 |
Minimum of Months | 76.50 | 22.24 | 102.17 | 22.68 | 34.50 | 22.77 |
Maximum of Months | 251.83 | 24.09 | 348.00 | 24.02 | 219.50 | 24.02 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 255.17 | 22.22 | 100.83 | 22.66 | 38.50 | 22.74 |
February | 181.83 | 22.56 | 150.50 | 23.11 | 41.33 | 23.15 |
March | 193.67 | 22.76 | 135.83 | 23.23 | 35.67 | 23.28 |
April | 79.67 | 23.85 | 241.33 | 23.91 | 47.33 | 23.93 |
May | 110.17 | 24.09 | 344.00 | 23.99 | 110.17 | 24.01 |
June | 125.17 | 24.07 | 336.00 | 23.99 | 125.17 | 24.01 |
July | 222.17 | 24.05 | 338.00 | 24.01 | 222.17 | 24.02 |
August | 162.33 | 24.02 | 348.00 | 23.98 | 162.33 | 23.99 |
September | 198.33 | 24.05 | 330.00 | 24.01 | 198.33 | 24.02 |
October | 113.33 | 24.03 | 304.33 | 23.99 | 106.67 | 24.00 |
November | 99.17 | 23.66 | 199.17 | 23.84 | 53.50 | 23.85 |
December | 191.83 | 22.55 | 140.33 | 23.11 | 42.17 | 23.19 |
Annual Sum or Average | 1932.83 | 23.36 | 2968.33 | 23.71 | 1183.33 | 23.77 |
Minimum of Months | 79.67 | 22.22 | 100.83 | 22.66 | 35.67 | 22.74 |
Maximum of Months | 255.17 | 24.09 | 348.00 | 24.01 | 222.17 | 24.02 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 263.00 | 22.19 | 97.83 | 22.61 | 41.17 | 22.69 |
February | 187.50 | 22.49 | 150.50 | 23.05 | 44.50 | 23.08 |
March | 204.17 | 22.72 | 133.33 | 23.17 | 40.00 | 23.23 |
April | 89.83 | 23.81 | 237.50 | 23.90 | 52.17 | 23.91 |
May | 112.50 | 24.08 | 344.00 | 23.99 | 112.50 | 24.01 |
June | 128.17 | 24.06 | 336.00 | 23.99 | 128.17 | 24.01 |
July | 222.67 | 24.05 | 338.00 | 24.01 | 222.67 | 24.02 |
August | 161.50 | 24.02 | 348.00 | 23.98 | 161.50 | 23.99 |
September | 200.17 | 24.04 | 330.00 | 24.01 | 200.17 | 24.02 |
October | 114.67 | 24.03 | 304.00 | 23.99 | 107.33 | 24.00 |
November | 104.67 | 23.62 | 194.50 | 23.82 | 54.50 | 23.84 |
December | 200.00 | 22.52 | 138.83 | 23.07 | 44.17 | 23.15 |
Annual Sum or Average | 1988.83 | 23.33 | 2952.50 | 23.69 | 1208.83 | 23.75 |
Minimum of Months | 89.83 | 22.19 | 97.83 | 22.61 | 40.00 | 22.69 |
Maximum of Months | 263.00 | 24.08 | 348.00 | 24.01 | 222.67 | 24.02 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 267.83 | 22.13 | 103.17 | 22.54 | 48.50 | 22.62 |
February | 198.33 | 22.41 | 154.33 | 22.94 | 56.17 | 22.96 |
March | 215.67 | 22.64 | 139.83 | 23.07 | 50.50 | 23.10 |
April | 98.83 | 23.74 | 234.17 | 23.87 | 55.17 | 23.89 |
May | 111.50 | 24.10 | 344.00 | 24.00 | 111.50 | 24.02 |
June | 101.00 | 24.13 | 336.00 | 24.00 | 101.00 | 24.03 |
July | 183.83 | 24.09 | 338.00 | 24.03 | 183.83 | 24.05 |
August | 132.00 | 24.07 | 348.00 | 23.99 | 132.00 | 24.01 |
September | 158.50 | 24.10 | 330.00 | 24.03 | 158.50 | 24.04 |
October | 107.17 | 24.04 | 305.00 | 23.99 | 97.67 | 24.02 |
November | 106.33 | 23.55 | 198.83 | 23.80 | 50.33 | 23.82 |
December | 215.83 | 22.48 | 141.00 | 22.99 | 50.00 | 23.06 |
Annual Sum or Average | 1896.83 | 23.24 | 2972.33 | 23.65 | 1095.17 | 23.71 |
Minimum of Months | 98.83 | 22.13 | 103.17 | 22.54 | 48.50 | 22.62 |
Maximum of Months | 267.83 | 24.13 | 348.00 | 24.03 | 183.83 | 24.05 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 22.77229 | 43.60900 | 0.13926 | 8.02358 |
February | 448.00000 | 23.18809 | 47.39617 | 0.26704 | 9.21495 |
March | 497.00000 | 23.30730 | 45.89768 | 0.28244 | 8.94528 |
April | 479.00000 | 23.87317 | 52.68250 | 0.50237 | 10.59940 |
May | 496.00000 | 23.96547 | 60.71867 | -0.2141 | 6.09479 |
June | 481.00000 | 23.97254 | 60.53928 | -0.1909 | 5.94513 |
July | 495.00000 | 23.97553 | 64.19157 | -0.1523 | 5.69758 |
August | 497.00000 | 23.99014 | 62.16998 | -0.1484 | 5.70360 |
September | 479.00000 | 23.96628 | 62.97639 | -0.1661 | 5.79247 |
October | 496.00000 | 23.94711 | 55.63322 | 0.61069 | 13.17087 |
November | 480.00000 | 23.84210 | 47.69937 | 0.47075 | 10.20691 |
December | 496.00000 | 23.24168 | 45.60576 | 0.28434 | 9.02391 |
Annual Sum or Average | 5840.00000 | 23.67134 | 54.12580 | 0.13919 | 8.19367 |
Minimum of Months | 448.00000 | 22.77229 | 43.60900 | -0.2141 | 5.69758 |
Maximum of Months | 497.00000 | 23.99014 | 64.19157 | 0.61069 | 13.17087 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 23.26137 | 42.41049 | 0.23643 | 7.77087 |
February | 448.00000 | 23.48701 | 45.94970 | 0.32386 | 8.88533 |
March | 497.00000 | 23.55323 | 44.09689 | 0.32726 | 8.57482 |
April | 479.00000 | 23.89005 | 49.76148 | 0.48361 | 10.12496 |
May | 496.00000 | 23.97190 | 57.04284 | -0.2567 | 6.55286 |
June | 481.00000 | 23.97712 | 57.18911 | -0.2384 | 6.40179 |
July | 495.00000 | 23.97690 | 60.72388 | -0.2040 | 6.10508 |
August | 497.00000 | 23.99088 | 59.13596 | -0.2045 | 6.13291 |
September | 479.00000 | 23.96803 | 59.60529 | -0.2188 | 6.24483 |
October | 496.00000 | 23.94963 | 52.87357 | 0.57331 | 12.20146 |
November | 480.00000 | 23.88717 | 45.93643 | 0.46343 | 9.86068 |
December | 496.00000 | 23.49340 | 44.35596 | 0.32865 | 8.75360 |
Annual Sum or Average | 5840.00000 | 23.78467 | 51.61804 | 0.13306 | 8.12743 |
Minimum of Months | 448.00000 | 23.26137 | 42.41049 | -0.2567 | 6.10508 |
Maximum of Months | 497.00000 | 23.99088 | 60.72388 | 0.57331 | 12.20146 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 22.84713 | 41.93871 | 0.15035 | 7.85912 |
February | 336.00000 | 23.26948 | 46.56340 | 0.28563 | 9.13653 |
March | 379.00000 | 23.38514 | 44.90273 | 0.29707 | 8.91529 |
April | 360.00000 | 23.95960 | 52.21504 | 0.51397 | 10.93653 |
May | 375.00000 | 24.08246 | 61.07192 | -0.1924 | 6.19694 |
June | 366.00000 | 24.09744 | 61.28637 | -0.1692 | 6.11024 |
July | 369.00000 | 24.10950 | 65.35925 | -0.1264 | 5.90095 |
August | 379.00000 | 24.09348 | 63.48203 | -0.1371 | 5.86514 |
September | 360.00000 | 24.08425 | 64.23544 | -0.1468 | 5.95831 |
October | 371.00000 | 24.05509 | 56.03388 | 0.62370 | 13.67858 |
November | 360.00000 | 23.89383 | 47.33341 | 0.47787 | 10.35487 |
December | 369.00000 | 23.26370 | 45.10113 | 0.28884 | 9.03334 |
Annual Sum or Average | 4395.00000 | 23.76394 | 54.18107 | 0.15332 | 8.31467 |
Minimum of Months | 336.00000 | 22.84713 | 41.93871 | -0.1924 | 5.86514 |
Maximum of Months | 379.00000 | 24.10950 | 65.35925 | 0.62370 | 13.67858 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 22.78527 | 42.15654 | 0.13133 | 7.84494 |
February | 336.00000 | 23.23069 | 46.73212 | 0.27226 | 9.06917 |
March | 379.00000 | 23.35945 | 45.00841 | 0.28752 | 8.88570 |
April | 360.00000 | 23.95621 | 52.24670 | 0.51187 | 10.90197 |
May | 375.00000 | 24.08270 | 61.02073 | -0.1914 | 6.19086 |
June | 366.00000 | 24.09785 | 61.21589 | -0.1677 | 6.10335 |
July | 369.00000 | 24.11003 | 65.24757 | -0.1244 | 5.89651 |
August | 379.00000 | 24.09392 | 63.39563 | -0.1356 | 5.86008 |
September | 360.00000 | 24.08469 | 64.14518 | -0.1453 | 5.95459 |
October | 371.00000 | 24.05514 | 55.97971 | 0.62434 | 13.69915 |
November | 360.00000 | 23.88739 | 47.38406 | 0.47473 | 10.31173 |
December | 369.00000 | 23.23197 | 45.19408 | 0.27801 | 8.99541 |
Annual Sum or Average | 4395.00000 | 23.75025 | 54.19699 | 0.14922 | 8.29576 |
Minimum of Months | 336.00000 | 22.78527 | 42.15654 | -0.1914 | 5.86008 |
Maximum of Months | 379.00000 | 24.11003 | 65.24757 | 0.62434 | 13.69915 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 22.71811 | 42.44752 | 0.11248 | 7.83582 |
February | 336.00000 | 23.17971 | 47.01781 | 0.25684 | 8.98649 |
March | 379.00000 | 23.31839 | 45.27265 | 0.27476 | 8.83420 |
April | 360.00000 | 23.94665 | 52.50498 | 0.50731 | 10.82202 |
May | 375.00000 | 24.07920 | 61.24223 | -0.1943 | 6.20033 |
June | 366.00000 | 24.09445 | 61.42117 | -0.1704 | 6.10634 |
July | 369.00000 | 24.10710 | 65.45274 | -0.1262 | 5.88999 |
August | 379.00000 | 24.09089 | 63.59974 | -0.1376 | 5.85618 |
September | 360.00000 | 24.08163 | 64.35982 | -0.1472 | 5.95490 |
October | 371.00000 | 24.05084 | 56.14997 | 0.62246 | 13.65177 |
November | 360.00000 | 23.87344 | 47.57168 | 0.46925 | 10.23307 |
December | 369.00000 | 23.19110 | 45.38216 | 0.26548 | 8.94454 |
Annual Sum or Average | 4395.00000 | 23.73008 | 54.42127 | 0.14236 | 8.26316 |
Minimum of Months | 336.00000 | 22.71811 | 42.44752 | -0.1943 | 5.85618 |
Maximum of Months | 379.00000 | 24.10710 | 65.45274 | 0.62246 | 13.65177 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.68369 | 43.73540 | 0.10293 | 7.76467 |
February | 308.00000 | 23.14545 | 48.11683 | 0.24661 | 8.81471 |
March | 348.00000 | 23.28987 | 46.42805 | 0.26623 | 8.70487 |
April | 330.00000 | 23.89306 | 53.20080 | 0.49654 | 10.54555 |
May | 344.00000 | 23.96576 | 62.19504 | -0.2165 | 6.22613 |
June | 336.00000 | 23.96657 | 62.29470 | -0.1946 | 6.07420 |
July | 338.00000 | 23.99485 | 66.36743 | -0.1447 | 5.82953 |
August | 348.00000 | 23.96067 | 64.48637 | -0.1597 | 5.78141 |
September | 330.00000 | 23.98642 | 65.38565 | -0.1608 | 5.96475 |
October | 340.00000 | 23.95559 | 57.10299 | 0.61429 | 13.35591 |
November | 330.00000 | 23.83305 | 48.50570 | 0.46364 | 10.05717 |
December | 338.00000 | 23.15201 | 46.47611 | 0.25697 | 8.86049 |
Annual Sum or Average | 4030.00000 | 23.65437 | 55.41213 | 0.12872 | 8.15195 |
Minimum of Months | 308.00000 | 22.68369 | 43.73540 | -0.2165 | 5.78141 |
Maximum of Months | 348.00000 | 23.99485 | 66.36743 | 0.61429 | 13.35591 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.66833 | 43.69494 | 0.08984 | 7.72003 |
February | 308.00000 | 23.13283 | 48.09656 | 0.23371 | 8.69688 |
March | 348.00000 | 23.28258 | 46.38907 | 0.25458 | 8.58054 |
April | 330.00000 | 23.89347 | 53.17070 | 0.48465 | 10.29111 |
May | 344.00000 | 23.96485 | 62.17768 | -0.2384 | 6.43255 |
June | 336.00000 | 23.96539 | 62.29726 | -0.2182 | 6.27251 |
July | 338.00000 | 23.99354 | 66.42673 | -0.1684 | 5.97828 |
August | 348.00000 | 23.95969 | 64.53137 | -0.1842 | 5.95458 |
September | 330.00000 | 23.98517 | 65.45934 | -0.1838 | 6.12028 |
October | 340.00000 | 23.95555 | 57.12492 | 0.59792 | 12.92532 |
November | 330.00000 | 23.83385 | 48.47449 | 0.45183 | 9.81856 |
December | 338.00000 | 23.15024 | 46.40734 | 0.24569 | 8.72522 |
Annual Sum or Average | 4030.00000 | 23.65095 | 55.40849 | 0.11153 | 8.11472 |
Minimum of Months | 308.00000 | 22.66833 | 43.69494 | -0.2384 | 5.95458 |
Maximum of Months | 348.00000 | 23.99354 | 66.42673 | 0.59792 | 12.92532 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.64038 | 43.80261 | 0.08043 | 7.72571 |
February | 308.00000 | 23.10712 | 48.22295 | 0.22477 | 8.66133 |
March | 348.00000 | 23.26280 | 46.49257 | 0.24719 | 8.55316 |
April | 330.00000 | 23.89048 | 53.26581 | 0.48187 | 10.24373 |
May | 344.00000 | 23.96440 | 62.27414 | -0.2407 | 6.45346 |
June | 336.00000 | 23.96500 | 62.38616 | -0.2204 | 6.29041 |
July | 338.00000 | 23.99316 | 66.51524 | -0.1702 | 5.98867 |
August | 348.00000 | 23.95940 | 64.61174 | -0.1861 | 5.96686 |
September | 330.00000 | 23.98481 | 65.55139 | -0.1856 | 6.13201 |
October | 340.00000 | 23.95462 | 57.20244 | 0.59630 | 12.88649 |
November | 330.00000 | 23.82856 | 48.54945 | 0.44855 | 9.77229 |
December | 338.00000 | 23.13120 | 46.50144 | 0.23868 | 8.69704 |
Annual Sum or Average | 4030.00000 | 23.64241 | 55.50208 | 0.10736 | 8.10298 |
Minimum of Months | 308.00000 | 22.64038 | 43.80261 | -0.2407 | 5.96686 |
Maximum of Months | 348.00000 | 23.99316 | 66.51524 | 0.59630 | 12.88649 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.57242 | 44.06357 | 0.05932 | 7.77920 |
February | 308.00000 | 23.03972 | 48.54906 | 0.20360 | 8.62357 |
March | 348.00000 | 23.20738 | 46.78714 | 0.22923 | 8.53149 |
April | 330.00000 | 23.87904 | 53.54580 | 0.47635 | 10.17275 |
May | 344.00000 | 23.96347 | 62.40440 | -0.2405 | 6.44861 |
June | 336.00000 | 23.96433 | 62.45857 | -0.2190 | 6.27758 |
July | 338.00000 | 23.99284 | 66.54209 | -0.1675 | 5.97094 |
August | 348.00000 | 23.95923 | 64.60749 | -0.1828 | 5.94362 |
September | 330.00000 | 23.98451 | 65.59307 | -0.1832 | 6.11753 |
October | 340.00000 | 23.95200 | 57.26856 | 0.59640 | 12.90494 |
November | 330.00000 | 23.81241 | 48.71302 | 0.44239 | 9.71250 |
December | 338.00000 | 23.07699 | 46.73505 | 0.22157 | 8.67434 |
Annual Sum or Average | 4030.00000 | 23.61951 | 55.65840 | 0.10086 | 8.08551 |
Minimum of Months | 308.00000 | 22.57242 | 44.06357 | -0.2405 | 5.94362 |
Maximum of Months | 348.00000 | 23.99284 | 66.54209 | 0.59640 | 12.90494 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.50871 | 44.10605 | 0.03122 | 8.04334 |
February | 308.00000 | 22.94579 | 48.81153 | 0.16978 | 8.74819 |
March | 348.00000 | 23.12797 | 46.88003 | 0.20099 | 8.70954 |
April | 330.00000 | 23.85397 | 53.74383 | 0.47416 | 10.26001 |
May | 344.00000 | 23.96642 | 62.14924 | -0.2075 | 6.17077 |
June | 336.00000 | 23.96850 | 61.83772 | -0.1780 | 5.97964 |
July | 338.00000 | 24.00004 | 65.64903 | -0.1214 | 5.77096 |
August | 348.00000 | 23.96529 | 63.75693 | -0.1329 | 5.67391 |
September | 330.00000 | 23.99160 | 64.79426 | -0.1421 | 5.93464 |
October | 340.00000 | 23.95027 | 56.81460 | 0.61897 | 13.60101 |
November | 330.00000 | 23.79037 | 48.63166 | 0.44142 | 9.85691 |
December | 338.00000 | 22.99359 | 46.92090 | 0.19321 | 8.86583 |
Annual Sum or Average | 4030.00000 | 23.59141 | 55.38960 | 0.11052 | 8.12286 |
Minimum of Months | 308.00000 | 22.50871 | 44.10605 | -0.2075 | 5.67391 |
Maximum of Months | 348.00000 | 24.00004 | 65.64903 | 0.61897 | 13.60101 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.497072E+10 | 0.126459E+10 | 133.90 | 0.314604E+10 | 0.182468E+10 | 0.00 | 1.00 | 02-JAN-09:02 | 0.00 | 01-JAN-00:05 | 61142.61 | 19-JAN-09:02 | 33862.13 | 19-JAN-09:02 | 27280.48 | 19-JAN-09:02 | 12919.79 | 19-JAN-09:02 | 0.00 | 01-JAN-00:05 |
February | 0.647390E+10 | 0.164210E+10 | 165.96 | 0.408529E+10 | 0.238861E+10 | 0.00 | 1.00 | 27-FEB-09:02 | 0.00 | 01-FEB-00:05 | 59432.74 | 28-FEB-09:02 | 31166.21 | 28-FEB-09:02 | 28266.53 | 28-FEB-09:02 | 12711.72 | 28-FEB-09:02 | 0.00 | 01-FEB-00:05 |
March | 0.939166E+10 | 0.240259E+10 | 235.67 | 0.611992E+10 | 0.327175E+10 | 0.00 | 1.00 | 06-MAR-09:02 | 0.00 | 01-MAR-00:05 | 61442.57 | 07-MAR-09:02 | 37797.85 | 30-MAR-08:62 | 27176.33 | 07-MAR-09:02 | 13217.00 | 07-MAR-09:02 | 0.00 | 01-MAR-00:05 |
April | 0.173268E+11 | 0.442424E+10 | 372.29 | 0.114015E+11 | 0.592533E+10 | 0.00 | 1.00 | 01-APR-08:62 | 0.00 | 01-APR-00:05 | 62143.81 | 29-APR-08:62 | 37695.28 | 22-APR-08:62 | 32692.53 | 24-APR-08:62 | 13525.81 | 29-APR-08:62 | 0.00 | 01-APR-00:05 |
May | 0.380513E+11 | 0.946263E+10 | 475.72 | 0.232631E+11 | 0.147881E+11 | 0.00 | 1.00 | 01-MAY-08:62 | 0.00 | 01-MAY-00:10 | 63275.46 | 24-MAY-08:61 | 41167.54 | 07-MAY-07:02 | 31958.82 | 24-MAY-08:03 | 13850.65 | 27-MAY-08:04 | 0.00 | 01-MAY-00:10 |
June | 0.405312E+11 | 0.100182E+11 | 463.37 | 0.245781E+11 | 0.159531E+11 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 63122.86 | 19-JUN-08:61 | 41821.52 | 11-JUN-07:02 | 31039.41 | 19-JUN-08:04 | 14184.16 | 17-JUN-08:02 | 0.00 | 01-JUN-00:10 |
July | 0.460469E+11 | 0.111748E+11 | 481.99 | 0.259346E+11 | 0.201123E+11 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 63412.52 | 03-JUL-08:61 | 40687.61 | 09-JUL-07:01 | 32028.06 | 31-JUL-08:04 | 14129.75 | 19-JUL-08:02 | 0.00 | 01-JUL-00:05 |
August | 0.454217E+11 | 0.110451E+11 | 482.32 | 0.264869E+11 | 0.189348E+11 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 63453.58 | 07-AUG-08:61 | 42759.95 | 20-AUG-07:02 | 31720.44 | 07-AUG-08:13 | 14014.99 | 22-AUG-08:02 | 0.00 | 01-AUG-00:10 |
September | 0.403692E+11 | 0.972952E+10 | 463.01 | 0.228691E+11 | 0.175001E+11 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:05 | 63892.70 | 05-SEP-08:61 | 39198.34 | 03-SEP-07:02 | 34572.53 | 05-SEP-08:04 | 14461.16 | 10-SEP-07:13 | 0.00 | 01-SEP-00:05 |
October | 0.344510E+11 | 0.838584E+10 | 444.18 | 0.210009E+11 | 0.134501E+11 | 0.00 | 1.00 | 01-OCT-07:03 | 0.00 | 01-OCT-00:10 | 63904.39 | 06-OCT-08:61 | 46866.07 | 26-OCT-08:61 | 33600.19 | 06-OCT-08:05 | 14057.76 | 07-OCT-08:13 | 0.00 | 01-OCT-00:10 |
November | 0.137385E+11 | 0.341760E+10 | 298.95 | 0.869693E+10 | 0.504160E+10 | 0.00 | 1.00 | 01-NOV-08:62 | 0.00 | 01-NOV-00:10 | 61918.95 | 02-NOV-08:61 | 41584.00 | 06-NOV-09:02 | 30109.96 | 04-NOV-08:62 | 13302.43 | 02-NOV-08:61 | 0.00 | 01-NOV-00:10 |
December | 0.883462E+10 | 0.220390E+10 | 193.89 | 0.555492E+10 | 0.327970E+10 | 0.00 | 1.00 | 09-DEC-09:02 | 0.00 | 01-DEC-00:10 | 61735.76 | 15-DEC-09:02 | 36194.16 | 11-DEC-09:02 | 28068.72 | 15-DEC-09:02 | 13071.95 | 15-DEC-09:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.305608E+12 | 0.751711E+11 | 4211.25 | 0.183137E+12 | 0.122470E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.497072E+10 | 0.126459E+10 | 133.90 | 0.314604E+10 | 0.182468E+10 | 0.00 | 1.00 | 0.00 | 59432.74 | 31166.21 | 27176.33 | 12711.72 | 0.00 | |||||||
Maximum of Months | 0.460469E+11 | 0.111748E+11 | 482.32 | 0.264869E+11 | 0.201123E+11 | 0.00 | 1.00 | 0.00 | 63904.39 | 46866.07 | 34572.53 | 14461.16 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.291507E+10 | 0.723852E+09 | 140.64 | 0.189583E+10 | 0.101923E+10 | 0.00 | 1.00 | 01-JAN-18:02 | 0.00 | 01-JAN-00:05 | 31452.27 | 19-JAN-09:02 | 19627.44 | 29-JAN-18:07 | 13851.83 | 01-JAN-18:02 | 6548.67 | 19-JAN-09:02 | 0.00 | 01-JAN-00:05 |
February | 0.384954E+10 | 0.956022E+09 | 184.57 | 0.248165E+10 | 0.136788E+10 | 0.00 | 1.00 | 02-FEB-09:03 | 0.00 | 01-FEB-00:05 | 30553.12 | 28-FEB-21:20 | 22502.16 | 28-FEB-09:02 | 15911.57 | 28-FEB-21:20 | 6433.95 | 28-FEB-21:20 | 0.00 | 01-FEB-00:05 |
March | 0.541684E+10 | 0.135291E+10 | 243.61 | 0.363487E+10 | 0.178197E+10 | 0.00 | 1.00 | 04-MAR-19:01 | 0.00 | 01-MAR-00:05 | 30898.58 | 07-MAR-09:02 | 24337.36 | 04-MAR-19:01 | 15488.09 | 27-MAR-20:50 | 6650.77 | 07-MAR-09:02 | 0.00 | 01-MAR-00:05 |
April | 0.949752E+10 | 0.237718E+10 | 378.26 | 0.644483E+10 | 0.305269E+10 | 0.00 | 1.00 | 01-APR-08:62 | 0.00 | 01-APR-00:05 | 30983.08 | 29-APR-08:62 | 25211.70 | 17-APR-20:01 | 15779.12 | 15-APR-18:10 | 6822.73 | 29-APR-08:62 | 0.00 | 01-APR-00:05 |
May | 0.189045E+11 | 0.465790E+10 | 476.05 | 0.119481E+11 | 0.695637E+10 | 0.00 | 1.00 | 01-MAY-08:62 | 0.00 | 01-MAY-00:10 | 31661.92 | 24-MAY-08:61 | 24623.35 | 07-MAY-07:02 | 12666.03 | 22-MAY-08:04 | 7025.96 | 27-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.199432E+11 | 0.489313E+10 | 464.35 | 0.124633E+11 | 0.747986E+10 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 31395.73 | 19-JUN-08:61 | 24214.56 | 11-JUN-07:02 | 11859.41 | 19-JUN-08:04 | 7181.03 | 17-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.224306E+11 | 0.541747E+10 | 482.60 | 0.130651E+11 | 0.936548E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 31793.07 | 03-JUL-08:61 | 24351.75 | 09-JUL-07:01 | 13033.38 | 03-JUL-08:04 | 7163.36 | 19-JUL-08:61 | 0.00 | 01-JUL-00:05 |
August | 0.220811E+11 | 0.533817E+10 | 482.25 | 0.132428E+11 | 0.883828E+10 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 31906.29 | 16-AUG-08:61 | 24905.69 | 20-AUG-07:02 | 13377.24 | 16-AUG-08:03 | 7104.03 | 22-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.197428E+11 | 0.472407E+10 | 463.53 | 0.115487E+11 | 0.819408E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:05 | 32175.26 | 05-SEP-08:61 | 23634.88 | 03-SEP-07:02 | 14677.64 | 05-SEP-08:04 | 7329.09 | 10-SEP-07:01 | 0.00 | 01-SEP-00:05 |
October | 0.171778E+11 | 0.414364E+10 | 445.96 | 0.108168E+11 | 0.636104E+10 | 0.00 | 1.00 | 01-OCT-07:03 | 0.00 | 01-OCT-00:10 | 31881.28 | 06-OCT-08:61 | 25248.06 | 26-OCT-20:01 | 13477.85 | 24-OCT-08:04 | 7132.20 | 07-OCT-08:61 | 0.00 | 01-OCT-00:10 |
November | 0.747997E+10 | 0.182644E+10 | 306.66 | 0.487329E+10 | 0.260668E+10 | 0.00 | 1.00 | 01-NOV-08:62 | 0.00 | 01-NOV-00:10 | 31065.65 | 02-NOV-08:61 | 24110.69 | 06-NOV-09:02 | 15705.32 | 29-NOV-21:02 | 6702.22 | 02-NOV-08:61 | 0.00 | 01-NOV-00:10 |
December | 0.473571E+10 | 0.116144E+10 | 203.11 | 0.307396E+10 | 0.166175E+10 | 0.00 | 1.00 | 08-DEC-21:02 | 0.00 | 01-DEC-00:10 | 30934.70 | 13-DEC-09:02 | 21593.29 | 11-DEC-09:02 | 14348.04 | 08-DEC-21:40 | 6547.73 | 15-DEC-09:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.154175E+12 | 0.375722E+11 | 4271.59 | 0.954892E+11 | 0.586853E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.291507E+10 | 0.723852E+09 | 140.64 | 0.189583E+10 | 0.101923E+10 | 0.00 | 1.00 | 0.00 | 30553.12 | 19627.44 | 11859.41 | 6433.95 | 0.00 | |||||||
Maximum of Months | 0.224306E+11 | 0.541747E+10 | 482.60 | 0.132428E+11 | 0.936548E+10 | 0.00 | 1.00 | 0.00 | 32175.26 | 25248.06 | 15911.57 | 7329.09 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.213275E+10 | 0.535064E+09 | 105.75 | 0.137028E+10 | 0.762467E+09 | 0.00 | 1.00 | 01-JAN-09:02 | 0.00 | 01-JAN-00:05 | 30414.82 | 19-JAN-08:62 | 18408.07 | 01-JAN-09:02 | 16382.60 | 19-JAN-08:62 | 6372.48 | 20-JAN-08:62 | 0.00 | 01-JAN-00:05 |
February | 0.292265E+10 | 0.729190E+09 | 142.09 | 0.185485E+10 | 0.106780E+10 | 0.00 | 1.00 | 01-FEB-08:62 | 0.00 | 01-FEB-00:05 | 30553.00 | 28-FEB-08:62 | 15755.03 | 28-FEB-08:62 | 14797.97 | 28-FEB-08:62 | 6424.80 | 28-FEB-08:62 | 0.00 | 01-FEB-00:05 |
March | 0.406676E+10 | 0.102175E+10 | 183.22 | 0.267187E+10 | 0.139489E+10 | 0.00 | 1.00 | 01-MAR-08:62 | 0.00 | 01-MAR-00:05 | 31322.10 | 07-MAR-08:62 | 17324.88 | 18-MAR-07:03 | 16055.14 | 07-MAR-08:62 | 6530.32 | 07-MAR-08:62 | 0.00 | 01-MAR-00:05 |
April | 0.717841E+10 | 0.180287E+10 | 286.63 | 0.479399E+10 | 0.238442E+10 | 0.00 | 1.00 | 01-APR-07:02 | 0.00 | 01-APR-00:05 | 32039.12 | 29-APR-07:02 | 18944.09 | 27-APR-07:02 | 17820.29 | 24-APR-07:02 | 6730.20 | 29-APR-07:02 | 0.00 | 01-APR-00:05 |
May | 0.154029E+11 | 0.374571E+10 | 343.59 | 0.944693E+10 | 0.595595E+10 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 32831.31 | 24-MAY-07:01 | 20581.41 | 12-MAY-07:01 | 17360.75 | 24-MAY-07:04 | 6968.78 | 28-MAY-08:04 | 0.00 | 01-MAY-00:10 |
June | 0.164932E+11 | 0.398708E+10 | 337.90 | 0.998196E+10 | 0.651120E+10 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 33139.15 | 19-JUN-07:01 | 20815.46 | 14-JUN-07:01 | 18682.59 | 19-JUN-07:04 | 7056.86 | 17-JUN-07:04 | 0.00 | 01-JUN-00:10 |
July | 0.182607E+11 | 0.433327E+10 | 350.38 | 0.102228E+11 | 0.803792E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:05 | 33226.69 | 03-JUL-07:01 | 18760.28 | 19-JUL-07:01 | 19063.13 | 02-JUL-08:04 | 7138.17 | 09-JUL-08:04 | 0.00 | 01-JUL-00:05 |
August | 0.183657E+11 | 0.437337E+10 | 359.46 | 0.106180E+11 | 0.774777E+10 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 33191.06 | 14-AUG-07:02 | 20337.10 | 31-AUG-07:01 | 19089.69 | 14-AUG-07:04 | 7020.23 | 06-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.159698E+11 | 0.375509E+10 | 335.79 | 0.894110E+10 | 0.702871E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:05 | 33212.74 | 05-SEP-07:01 | 19799.29 | 23-SEP-07:01 | 18823.09 | 05-SEP-07:02 | 7408.87 | 10-SEP-08:13 | 0.00 | 01-SEP-00:05 |
October | 0.136724E+11 | 0.325666E+10 | 321.06 | 0.831173E+10 | 0.536064E+10 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 | 33147.36 | 25-OCT-07:01 | 23649.30 | 26-OCT-07:01 | 18380.70 | 25-OCT-07:04 | 6932.85 | 14-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.581513E+10 | 0.142233E+10 | 245.79 | 0.371685E+10 | 0.209828E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 32137.26 | 02-NOV-07:01 | 19948.46 | 07-NOV-08:61 | 16730.27 | 04-NOV-07:02 | 6712.87 | 11-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 0.371310E+10 | 0.909512E+09 | 155.56 | 0.234875E+10 | 0.136436E+10 | 0.00 | 1.00 | 09-DEC-08:62 | 0.00 | 01-DEC-00:10 | 31782.62 | 16-DEC-08:62 | 19169.35 | 17-DEC-09:02 | 17616.22 | 14-DEC-08:62 | 6592.55 | 15-DEC-08:62 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.123994E+12 | 0.298719E+11 | 3167.24 | 0.742791E+11 | 0.497144E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.213275E+10 | 0.535064E+09 | 105.75 | 0.137028E+10 | 0.762467E+09 | 0.00 | 1.00 | 0.00 | 30414.82 | 15755.03 | 14797.97 | 6372.48 | 0.00 | |||||||
Maximum of Months | 0.183657E+11 | 0.437337E+10 | 359.46 | 0.106180E+11 | 0.803792E+10 | 0.00 | 1.00 | 0.00 | 33226.69 | 23649.30 | 19089.69 | 7408.87 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.206553E+10 | 0.519249E+09 | 102.70 | 0.132276E+10 | 0.742772E+09 | 0.00 | 1.00 | 01-JAN-09:02 | 0.00 | 01-JAN-00:05 | 30255.63 | 20-JAN-08:62 | 18457.54 | 01-JAN-09:02 | 16146.53 | 20-JAN-08:62 | 6389.68 | 20-JAN-08:62 | 0.00 | 01-JAN-00:05 |
February | 0.285297E+10 | 0.713078E+09 | 140.26 | 0.180664E+10 | 0.104633E+10 | 0.00 | 1.00 | 01-FEB-08:62 | 0.00 | 01-FEB-00:05 | 30634.95 | 28-FEB-08:62 | 15785.77 | 28-FEB-08:62 | 14849.19 | 28-FEB-08:62 | 6442.05 | 28-FEB-08:62 | 0.00 | 01-FEB-00:05 |
March | 0.400417E+10 | 0.100736E+10 | 181.89 | 0.262419E+10 | 0.137997E+10 | 0.00 | 1.00 | 01-MAR-08:62 | 0.00 | 01-MAR-00:05 | 31405.77 | 07-MAR-08:62 | 16286.25 | 18-MAR-07:03 | 16114.23 | 07-MAR-08:62 | 6547.83 | 07-MAR-08:62 | 0.00 | 01-MAR-00:05 |
April | 0.714186E+10 | 0.179507E+10 | 285.43 | 0.476543E+10 | 0.237643E+10 | 0.00 | 1.00 | 01-APR-07:02 | 0.00 | 01-APR-00:05 | 32127.58 | 29-APR-07:02 | 18988.54 | 27-APR-07:02 | 17860.26 | 24-APR-07:02 | 6748.36 | 29-APR-07:02 | 0.00 | 01-APR-00:05 |
May | 0.154440E+11 | 0.375623E+10 | 344.59 | 0.947682E+10 | 0.596717E+10 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 32921.99 | 24-MAY-07:01 | 20678.24 | 12-MAY-07:01 | 17400.83 | 24-MAY-07:04 | 6987.48 | 28-MAY-08:04 | 0.00 | 01-MAY-00:10 |
June | 0.165496E+11 | 0.400112E+10 | 339.25 | 0.100234E+11 | 0.652622E+10 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 33228.24 | 19-JUN-07:03 | 20894.46 | 14-JUN-07:01 | 18685.71 | 19-JUN-07:04 | 7075.83 | 17-JUN-07:04 | 0.00 | 01-JUN-00:10 |
July | 0.183452E+11 | 0.435394E+10 | 353.44 | 0.102834E+11 | 0.806177E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:05 | 33309.13 | 31-JUL-07:01 | 18846.91 | 19-JUL-07:01 | 19049.86 | 02-JUL-08:04 | 7157.91 | 09-JUL-08:04 | 0.00 | 01-JUL-00:05 |
August | 0.184346E+11 | 0.439043E+10 | 362.03 | 0.106680E+11 | 0.776658E+10 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 33280.28 | 14-AUG-07:01 | 20412.90 | 31-AUG-07:01 | 18999.57 | 14-AUG-07:04 | 7039.78 | 06-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.160373E+11 | 0.377150E+10 | 337.31 | 0.898874E+10 | 0.704857E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:05 | 33259.38 | 05-SEP-07:01 | 19885.09 | 23-SEP-07:01 | 18715.95 | 05-SEP-07:04 | 7430.40 | 10-SEP-08:13 | 0.00 | 01-SEP-00:05 |
October | 0.137149E+11 | 0.326711E+10 | 322.79 | 0.834332E+10 | 0.537156E+10 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 | 33223.94 | 25-OCT-07:01 | 23720.33 | 26-OCT-07:01 | 18383.09 | 25-OCT-07:04 | 6951.53 | 14-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.576603E+10 | 0.141097E+10 | 244.57 | 0.367992E+10 | 0.208611E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 32226.02 | 02-NOV-07:01 | 20019.80 | 07-NOV-08:61 | 16772.33 | 04-NOV-07:02 | 6730.92 | 11-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 0.367313E+10 | 0.900179E+09 | 153.22 | 0.231856E+10 | 0.135458E+10 | 0.00 | 1.00 | 09-DEC-08:62 | 0.00 | 01-DEC-00:10 | 31856.22 | 16-DEC-08:62 | 19224.31 | 17-DEC-09:02 | 17896.66 | 16-DEC-08:62 | 6610.42 | 15-DEC-08:62 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.124029E+12 | 0.298862E+11 | 3167.48 | 0.743013E+11 | 0.497281E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.206553E+10 | 0.519249E+09 | 102.70 | 0.132276E+10 | 0.742772E+09 | 0.00 | 1.00 | 0.00 | 30255.63 | 15785.77 | 14849.19 | 6389.68 | 0.00 | |||||||
Maximum of Months | 0.184346E+11 | 0.439043E+10 | 362.03 | 0.106680E+11 | 0.806177E+10 | 0.00 | 1.00 | 0.00 | 33309.13 | 23720.33 | 19049.86 | 7430.40 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.196277E+10 | 0.494759E+09 | 99.56 | 0.125159E+10 | 0.711173E+09 | 0.00 | 1.00 | 01-JAN-09:02 | 0.00 | 01-JAN-00:05 | 30146.42 | 20-JAN-08:62 | 18366.60 | 01-JAN-09:02 | 16129.83 | 20-JAN-08:62 | 6366.84 | 20-JAN-08:62 | 0.00 | 01-JAN-00:05 |
February | 0.273013E+10 | 0.683992E+09 | 136.62 | 0.172238E+10 | 0.100775E+10 | 0.00 | 1.00 | 01-FEB-08:62 | 0.00 | 01-FEB-00:05 | 30525.45 | 28-FEB-08:62 | 15688.09 | 28-FEB-08:62 | 14837.36 | 28-FEB-08:62 | 6419.23 | 28-FEB-08:62 | 0.00 | 01-FEB-00:05 |
March | 0.385247E+10 | 0.971400E+09 | 179.71 | 0.251499E+10 | 0.133748E+10 | 0.00 | 1.00 | 01-MAR-08:62 | 0.00 | 01-MAR-00:05 | 31292.99 | 07-MAR-08:62 | 15968.15 | 30-MAR-07:02 | 16101.68 | 07-MAR-08:62 | 6524.69 | 07-MAR-08:62 | 0.00 | 01-MAR-00:05 |
April | 0.694487E+10 | 0.174848E+10 | 282.28 | 0.462494E+10 | 0.231992E+10 | 0.00 | 1.00 | 01-APR-07:02 | 0.00 | 01-APR-00:05 | 32008.78 | 29-APR-07:02 | 18803.32 | 27-APR-07:02 | 17822.64 | 24-APR-07:02 | 6724.61 | 29-APR-07:02 | 0.00 | 01-APR-00:05 |
May | 0.152640E+11 | 0.371577E+10 | 343.82 | 0.934713E+10 | 0.591689E+10 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 32800.43 | 24-MAY-07:01 | 20497.83 | 12-MAY-07:01 | 17429.83 | 24-MAY-07:04 | 6963.15 | 28-MAY-08:04 | 0.00 | 01-MAY-00:10 |
June | 0.163820E+11 | 0.396248E+10 | 337.28 | 0.990073E+10 | 0.648123E+10 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 33112.22 | 19-JUN-07:01 | 20773.07 | 14-JUN-07:01 | 18676.03 | 19-JUN-07:04 | 7051.13 | 17-JUN-07:04 | 0.00 | 01-JUN-00:10 |
July | 0.181882E+11 | 0.431693E+10 | 349.86 | 0.101726E+11 | 0.801559E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:05 | 33192.83 | 31-JUL-07:01 | 18699.52 | 19-JUL-07:01 | 19085.26 | 02-JUL-08:04 | 7132.42 | 09-JUL-08:04 | 0.00 | 01-JUL-00:05 |
August | 0.182682E+11 | 0.435116E+10 | 357.27 | 0.105485E+11 | 0.771963E+10 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 33164.08 | 14-AUG-07:01 | 20286.03 | 31-AUG-07:01 | 19049.55 | 14-AUG-07:04 | 7014.10 | 06-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.158801E+11 | 0.373616E+10 | 335.69 | 0.887925E+10 | 0.700083E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:05 | 33160.45 | 05-SEP-07:01 | 19711.24 | 23-SEP-07:01 | 18718.23 | 05-SEP-07:04 | 7403.36 | 10-SEP-08:13 | 0.00 | 01-SEP-00:05 |
October | 0.135679E+11 | 0.323320E+10 | 320.28 | 0.823500E+10 | 0.533288E+10 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 | 33146.50 | 25-OCT-07:01 | 23601.49 | 26-OCT-07:01 | 18462.29 | 25-OCT-07:04 | 6927.18 | 14-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.561348E+10 | 0.137493E+10 | 241.21 | 0.356816E+10 | 0.204532E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 32105.01 | 02-NOV-07:01 | 19858.04 | 07-NOV-08:61 | 16755.00 | 04-NOV-07:02 | 6706.74 | 11-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 0.357441E+10 | 0.877106E+09 | 149.39 | 0.224759E+10 | 0.132682E+10 | 0.00 | 1.00 | 09-DEC-08:62 | 0.00 | 01-DEC-00:10 | 31752.99 | 16-DEC-08:62 | 19129.84 | 17-DEC-09:02 | 17645.30 | 14-DEC-08:62 | 6587.00 | 15-DEC-08:62 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.122228E+12 | 0.294664E+11 | 3132.96 | 0.730129E+11 | 0.492155E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.196277E+10 | 0.494759E+09 | 99.56 | 0.125159E+10 | 0.711173E+09 | 0.00 | 1.00 | 0.00 | 30146.42 | 15688.09 | 14837.36 | 6366.84 | 0.00 | |||||||
Maximum of Months | 0.182682E+11 | 0.435116E+10 | 357.27 | 0.105485E+11 | 0.801559E+10 | 0.00 | 1.00 | 0.00 | 33192.83 | 23601.49 | 19085.26 | 7403.36 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.347172E+10 | 0.887078E+09 | 97.24 | 0.218109E+10 | 0.129063E+10 | 0.00 | 1.00 | 01-JAN-10:02 | 0.00 | 01-JAN-00:05 | 57584.60 | 19-JAN-09:02 | 35007.16 | 01-JAN-10:02 | 26271.05 | 19-JAN-09:02 | 12172.21 | 19-JAN-09:02 | 0.00 | 01-JAN-00:05 |
February | 0.500269E+10 | 0.127016E+10 | 128.30 | 0.311327E+10 | 0.188942E+10 | 0.00 | 1.00 | 26-FEB-10:03 | 0.00 | 01-FEB-00:05 | 55977.41 | 28-FEB-09:02 | 29362.40 | 28-FEB-09:02 | 26615.01 | 28-FEB-09:02 | 11975.15 | 28-FEB-09:02 | 0.00 | 01-FEB-00:05 |
March | 0.701294E+10 | 0.178980E+10 | 173.07 | 0.451880E+10 | 0.249414E+10 | 0.00 | 1.00 | 06-MAR-09:02 | 0.00 | 01-MAR-00:05 | 57715.14 | 07-MAR-09:02 | 35752.43 | 30-MAR-08:62 | 28388.97 | 27-MAR-08:62 | 12444.88 | 07-MAR-09:02 | 0.00 | 01-MAR-00:05 |
April | 0.128914E+11 | 0.328895E+10 | 274.34 | 0.849613E+10 | 0.439529E+10 | 0.00 | 1.00 | 01-APR-08:62 | 0.00 | 01-APR-00:05 | 58220.34 | 29-APR-08:62 | 36137.00 | 22-APR-08:62 | 33250.03 | 30-APR-09:03 | 12739.46 | 29-APR-08:62 | 0.00 | 01-APR-00:05 |
May | 0.280594E+11 | 0.691640E+10 | 335.26 | 0.170433E+11 | 0.110161E+11 | 0.00 | 1.00 | 01-MAY-08:62 | 0.00 | 01-MAY-00:10 | 60074.15 | 21-MAY-09:01 | 37690.82 | 12-MAY-08:61 | 31492.46 | 21-MAY-09:04 | 13214.35 | 28-MAY-09:05 | 0.00 | 01-MAY-00:10 |
June | 0.302183E+11 | 0.741009E+10 | 330.59 | 0.181371E+11 | 0.120813E+11 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 60502.10 | 19-JUN-08:04 | 38561.85 | 10-JUN-08:61 | 34282.99 | 19-JUN-08:04 | 13366.51 | 17-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.333789E+11 | 0.803267E+10 | 338.54 | 0.185155E+11 | 0.148634E+11 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 60773.68 | 31-JUL-08:61 | 35898.92 | 19-JUL-08:61 | 34484.38 | 31-JUL-08:03 | 13485.12 | 09-JUL-09:13 | 0.00 | 01-JUL-00:05 |
August | 0.337851E+11 | 0.816459E+10 | 347.03 | 0.193733E+11 | 0.144118E+11 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 60585.97 | 07-AUG-08:61 | 38912.55 | 31-AUG-08:61 | 34819.35 | 14-AUG-08:05 | 13241.89 | 13-AUG-09:13 | 0.00 | 01-AUG-00:10 |
September | 0.290896E+11 | 0.692669E+10 | 324.77 | 0.160750E+11 | 0.130146E+11 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:05 | 60835.64 | 05-SEP-08:61 | 36581.03 | 23-SEP-08:61 | 34716.15 | 05-SEP-08:04 | 13996.25 | 10-SEP-09:13 | 0.00 | 01-SEP-00:05 |
October | 0.251805E+11 | 0.608482E+10 | 311.60 | 0.151607E+11 | 0.100198E+11 | 0.00 | 1.00 | 01-OCT-09:02 | 0.00 | 01-OCT-00:10 | 60647.78 | 08-OCT-09:01 | 43639.27 | 26-OCT-08:61 | 33189.57 | 22-OCT-09:04 | 13246.20 | 07-OCT-08:13 | 0.00 | 01-OCT-00:10 |
November | 0.103489E+11 | 0.256417E+10 | 228.78 | 0.650986E+10 | 0.383909E+10 | 0.00 | 1.00 | 01-NOV-08:62 | 0.00 | 01-NOV-00:10 | 58232.89 | 02-NOV-08:61 | 36931.66 | 07-NOV-09:01 | 28606.28 | 04-NOV-08:62 | 12541.29 | 11-NOV-10:01 | 0.00 | 01-NOV-00:10 |
December | 0.655834E+10 | 0.162602E+10 | 139.83 | 0.408061E+10 | 0.247773E+10 | 0.00 | 1.00 | 09-DEC-09:02 | 0.00 | 01-DEC-00:10 | 57986.37 | 15-DEC-09:02 | 37617.94 | 10-DEC-10:02 | 25917.99 | 15-DEC-09:02 | 12441.00 | 10-DEC-10:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.224998E+12 | 0.549614E+11 | 3029.35 | 0.133205E+12 | 0.917933E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.347172E+10 | 0.887078E+09 | 97.24 | 0.218109E+10 | 0.129063E+10 | 0.00 | 1.00 | 0.00 | 55977.41 | 29362.40 | 25917.99 | 11975.15 | 0.00 | |||||||
Maximum of Months | 0.337851E+11 | 0.816459E+10 | 347.03 | 0.193733E+11 | 0.148634E+11 | 0.00 | 1.00 | 0.00 | 60835.64 | 43639.27 | 34819.35 | 13996.25 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.179150E+10 | 0.450264E+09 | 95.79 | 0.112687E+10 | 0.664635E+09 | 0.00 | 1.00 | 01-JAN-10:02 | 0.00 | 01-JAN-00:05 | 30273.06 | 19-JAN-09:02 | 18416.73 | 01-JAN-10:02 | 13781.90 | 19-JAN-09:02 | 6286.47 | 19-JAN-09:02 | 0.00 | 01-JAN-00:05 |
February | 0.258332E+10 | 0.645202E+09 | 126.99 | 0.160957E+10 | 0.973745E+09 | 0.00 | 1.00 | 26-FEB-10:03 | 0.00 | 01-FEB-00:05 | 29420.26 | 28-FEB-09:02 | 15465.42 | 28-FEB-09:02 | 13954.84 | 28-FEB-09:02 | 6183.85 | 28-FEB-09:02 | 0.00 | 01-FEB-00:05 |
March | 0.363279E+10 | 0.912105E+09 | 172.02 | 0.234239E+10 | 0.129040E+10 | 0.00 | 1.00 | 06-MAR-09:02 | 0.00 | 01-MAR-00:05 | 30314.38 | 07-MAR-09:02 | 18881.92 | 30-MAR-08:62 | 14926.98 | 27-MAR-08:62 | 6425.63 | 07-MAR-09:02 | 0.00 | 01-MAR-00:05 |
April | 0.670109E+10 | 0.168195E+10 | 273.52 | 0.442327E+10 | 0.227783E+10 | 0.00 | 1.00 | 01-APR-08:62 | 0.00 | 01-APR-00:05 | 30581.67 | 29-APR-08:62 | 19044.15 | 22-APR-08:62 | 17445.92 | 30-APR-09:02 | 6578.57 | 29-APR-08:62 | 0.00 | 01-APR-00:05 |
May | 0.146398E+11 | 0.355337E+10 | 335.29 | 0.890913E+10 | 0.573064E+10 | 0.00 | 1.00 | 01-MAY-08:62 | 0.00 | 01-MAY-00:10 | 31583.22 | 21-MAY-09:01 | 19828.54 | 12-MAY-08:61 | 16588.17 | 21-MAY-09:04 | 6819.74 | 28-MAY-09:04 | 0.00 | 01-MAY-00:10 |
June | 0.157565E+11 | 0.380513E+10 | 329.37 | 0.947368E+10 | 0.628284E+10 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 31802.82 | 19-JUN-08:61 | 20253.65 | 10-JUN-08:61 | 18105.77 | 19-JUN-08:04 | 6902.91 | 17-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.174048E+11 | 0.412563E+10 | 337.04 | 0.967559E+10 | 0.772917E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 31945.58 | 31-JUL-08:61 | 18909.65 | 19-JUL-08:61 | 18200.43 | 31-JUL-08:03 | 6964.13 | 09-JUL-09:13 | 0.00 | 01-JUL-00:05 |
August | 0.176080E+11 | 0.419145E+10 | 345.87 | 0.101166E+11 | 0.749139E+10 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 31846.91 | 07-AUG-08:61 | 20467.10 | 31-AUG-08:61 | 18390.28 | 14-AUG-08:05 | 6838.69 | 13-AUG-09:13 | 0.00 | 01-AUG-00:10 |
September | 0.151621E+11 | 0.355469E+10 | 324.42 | 0.839877E+10 | 0.676334E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:05 | 31978.15 | 05-SEP-08:61 | 19254.65 | 23-SEP-08:61 | 18254.29 | 05-SEP-08:02 | 7229.67 | 10-SEP-09:13 | 0.00 | 01-SEP-00:05 |
October | 0.131174E+11 | 0.312022E+10 | 311.14 | 0.791106E+10 | 0.520633E+10 | 0.00 | 1.00 | 01-OCT-09:02 | 0.00 | 01-OCT-00:10 | 31879.40 | 08-OCT-09:01 | 22980.10 | 26-OCT-08:61 | 17499.28 | 22-OCT-09:04 | 6841.56 | 07-OCT-08:13 | 0.00 | 01-OCT-00:10 |
November | 0.536704E+10 | 0.130805E+10 | 226.87 | 0.337921E+10 | 0.198783E+10 | 0.00 | 1.00 | 01-NOV-08:62 | 0.00 | 01-NOV-00:10 | 30588.21 | 02-NOV-08:61 | 19449.49 | 07-NOV-09:01 | 15009.87 | 04-NOV-08:62 | 6476.47 | 11-NOV-10:01 | 0.00 | 01-NOV-00:10 |
December | 0.340590E+10 | 0.830476E+09 | 138.06 | 0.212131E+10 | 0.128460E+10 | 0.00 | 1.00 | 09-DEC-09:02 | 0.00 | 01-DEC-00:10 | 30465.52 | 15-DEC-09:02 | 19774.51 | 10-DEC-10:02 | 13551.49 | 15-DEC-09:02 | 6425.09 | 10-DEC-10:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.117170E+12 | 0.281785E+11 | 3016.37 | 0.694875E+11 | 0.476828E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.179150E+10 | 0.450264E+09 | 95.79 | 0.112687E+10 | 0.664635E+09 | 0.00 | 1.00 | 0.00 | 29420.26 | 15465.42 | 13551.49 | 6183.85 | 0.00 | |||||||
Maximum of Months | 0.176080E+11 | 0.419145E+10 | 345.87 | 0.101166E+11 | 0.772917E+10 | 0.00 | 1.00 | 0.00 | 31978.15 | 22980.10 | 18390.28 | 7229.67 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.175341E+10 | 0.441080E+09 | 94.90 | 0.110128E+10 | 0.652134E+09 | 0.00 | 1.00 | 01-JAN-10:02 | 0.00 | 01-JAN-00:05 | 30141.54 | 19-JAN-09:02 | 18325.92 | 01-JAN-10:02 | 13763.68 | 19-JAN-09:02 | 6259.73 | 19-JAN-09:02 | 0.00 | 01-JAN-00:05 |
February | 0.253466E+10 | 0.633550E+09 | 125.66 | 0.157655E+10 | 0.958113E+09 | 0.00 | 1.00 | 26-FEB-10:03 | 0.00 | 01-FEB-00:05 | 29298.14 | 28-FEB-09:02 | 15376.99 | 28-FEB-09:02 | 13921.15 | 28-FEB-09:02 | 6158.08 | 28-FEB-09:02 | 0.00 | 01-FEB-00:05 |
March | 0.357630E+10 | 0.898509E+09 | 171.27 | 0.230086E+10 | 0.127544E+10 | 0.00 | 1.00 | 06-MAR-09:02 | 0.00 | 01-MAR-00:05 | 30190.07 | 07-MAR-09:02 | 18741.26 | 30-MAR-08:62 | 14877.64 | 27-MAR-08:62 | 6398.85 | 07-MAR-09:02 | 0.00 | 01-MAR-00:05 |
April | 0.662727E+10 | 0.166401E+10 | 272.61 | 0.436954E+10 | 0.225772E+10 | 0.00 | 1.00 | 01-APR-08:62 | 0.00 | 01-APR-00:05 | 30455.63 | 29-APR-08:62 | 18922.29 | 22-APR-08:62 | 17382.99 | 30-APR-09:02 | 6551.05 | 29-APR-08:62 | 0.00 | 01-APR-00:05 |
May | 0.145615E+11 | 0.353429E+10 | 335.26 | 0.885306E+10 | 0.570842E+10 | 0.00 | 1.00 | 01-MAY-08:62 | 0.00 | 01-MAY-00:10 | 31447.29 | 21-MAY-09:01 | 19708.71 | 12-MAY-08:61 | 16541.57 | 21-MAY-09:04 | 6791.18 | 28-MAY-09:04 | 0.00 | 01-MAY-00:10 |
June | 0.156839E+11 | 0.378703E+10 | 329.23 | 0.942081E+10 | 0.626308E+10 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 31669.53 | 19-JUN-08:61 | 20137.75 | 10-JUN-08:61 | 18053.62 | 19-JUN-08:04 | 6873.98 | 17-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.173367E+11 | 0.410850E+10 | 336.16 | 0.962774E+10 | 0.770896E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 31811.69 | 31-JUL-08:61 | 18807.32 | 19-JUL-08:61 | 18144.08 | 31-JUL-08:03 | 6934.72 | 09-JUL-09:13 | 0.00 | 01-JUL-00:05 |
August | 0.175413E+11 | 0.417461E+10 | 345.05 | 0.100688E+11 | 0.747255E+10 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 31713.44 | 07-AUG-08:61 | 20345.22 | 31-AUG-08:61 | 18339.85 | 14-AUG-08:05 | 6809.74 | 13-AUG-09:13 | 0.00 | 01-AUG-00:10 |
September | 0.150945E+11 | 0.353826E+10 | 323.86 | 0.835187E+10 | 0.674259E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:05 | 31844.13 | 05-SEP-08:61 | 19142.37 | 23-SEP-08:61 | 18196.20 | 05-SEP-08:02 | 7198.93 | 10-SEP-09:13 | 0.00 | 01-SEP-00:05 |
October | 0.130485E+11 | 0.310348E+10 | 310.87 | 0.786033E+10 | 0.518815E+10 | 0.00 | 1.00 | 01-OCT-09:02 | 0.00 | 01-OCT-00:10 | 31745.79 | 08-OCT-09:01 | 22872.22 | 26-OCT-08:61 | 17448.80 | 22-OCT-09:04 | 6812.61 | 07-OCT-08:13 | 0.00 | 01-OCT-00:10 |
November | 0.530796E+10 | 0.129372E+10 | 225.07 | 0.333548E+10 | 0.197248E+10 | 0.00 | 1.00 | 01-NOV-08:62 | 0.00 | 01-NOV-00:10 | 30462.75 | 02-NOV-08:61 | 19327.89 | 07-NOV-09:01 | 14965.19 | 04-NOV-08:62 | 6449.30 | 11-NOV-10:01 | 0.00 | 01-NOV-00:10 |
December | 0.336421E+10 | 0.820502E+09 | 136.94 | 0.209105E+10 | 0.127315E+10 | 0.00 | 1.00 | 09-DEC-09:02 | 0.00 | 01-DEC-00:10 | 30339.70 | 15-DEC-09:02 | 19648.61 | 10-DEC-10:02 | 13548.92 | 15-DEC-09:02 | 6397.73 | 10-DEC-10:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.116430E+12 | 0.279975E+11 | 3006.89 | 0.689574E+11 | 0.474728E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.175341E+10 | 0.441080E+09 | 94.90 | 0.110128E+10 | 0.652134E+09 | 0.00 | 1.00 | 0.00 | 29298.14 | 15376.99 | 13548.92 | 6158.08 | 0.00 | |||||||
Maximum of Months | 0.175413E+11 | 0.417461E+10 | 345.05 | 0.100688E+11 | 0.770896E+10 | 0.00 | 1.00 | 0.00 | 31844.13 | 22872.22 | 18339.85 | 7198.93 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.167017E+10 | 0.421373E+09 | 91.40 | 0.104622E+10 | 0.623955E+09 | 0.00 | 1.00 | 01-JAN-10:02 | 0.00 | 01-JAN-00:05 | 28561.38 | 01-JAN-10:02 | 18331.71 | 01-JAN-10:02 | 12558.07 | 19-JAN-09:02 | 6055.08 | 01-JAN-10:02 | 0.00 | 01-JAN-00:05 |
February | 0.242425E+10 | 0.607922E+09 | 122.58 | 0.150275E+10 | 0.921500E+09 | 0.00 | 1.00 | 27-FEB-09:02 | 0.00 | 01-FEB-00:05 | 26887.09 | 28-FEB-09:02 | 14011.21 | 28-FEB-09:02 | 12875.88 | 28-FEB-09:02 | 5652.59 | 28-FEB-09:02 | 0.00 | 01-FEB-00:05 |
March | 0.343963E+10 | 0.866703E+09 | 168.71 | 0.220232E+10 | 0.123732E+10 | 0.00 | 1.00 | 07-MAR-09:02 | 0.00 | 01-MAR-00:05 | 30272.91 | 07-MAR-09:02 | 16767.40 | 07-MAR-09:02 | 13505.52 | 07-MAR-09:02 | 6416.69 | 07-MAR-09:02 | 0.00 | 01-MAR-00:05 |
April | 0.644589E+10 | 0.162202E+10 | 269.08 | 0.424022E+10 | 0.220567E+10 | 0.00 | 1.00 | 01-APR-08:62 | 0.00 | 01-APR-00:05 | 30532.49 | 29-APR-08:62 | 18860.72 | 22-APR-08:62 | 17462.37 | 30-APR-09:02 | 6569.21 | 29-APR-08:62 | 0.00 | 01-APR-00:05 |
May | 0.144717E+11 | 0.351653E+10 | 334.66 | 0.879117E+10 | 0.568058E+10 | 0.00 | 1.00 | 01-MAY-08:62 | 0.00 | 01-MAY-00:10 | 31522.44 | 21-MAY-09:01 | 19701.19 | 12-MAY-08:61 | 16651.79 | 21-MAY-09:04 | 6810.56 | 28-MAY-09:04 | 0.00 | 01-MAY-00:10 |
June | 0.156355E+11 | 0.377789E+10 | 328.26 | 0.938679E+10 | 0.624875E+10 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 31758.35 | 19-JUN-08:61 | 20134.88 | 10-JUN-08:61 | 18167.67 | 19-JUN-08:04 | 6893.25 | 17-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.173281E+11 | 0.410831E+10 | 334.90 | 0.962415E+10 | 0.770395E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 31900.91 | 31-JUL-08:61 | 18859.13 | 19-JUL-08:61 | 18231.09 | 31-JUL-08:03 | 6954.10 | 09-JUL-09:13 | 0.00 | 01-JUL-00:05 |
August | 0.175538E+11 | 0.417899E+10 | 344.59 | 0.100792E+11 | 0.747462E+10 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 31802.38 | 07-AUG-08:02 | 20393.00 | 31-AUG-08:61 | 18406.53 | 14-AUG-08:05 | 6828.63 | 13-AUG-09:13 | 0.00 | 01-AUG-00:10 |
September | 0.150767E+11 | 0.353614E+10 | 323.63 | 0.834164E+10 | 0.673507E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:05 | 31933.43 | 05-SEP-08:61 | 19157.12 | 23-SEP-08:61 | 18278.34 | 05-SEP-08:02 | 7219.86 | 10-SEP-09:13 | 0.00 | 01-SEP-00:05 |
October | 0.129977E+11 | 0.309315E+10 | 309.65 | 0.782403E+10 | 0.517368E+10 | 0.00 | 1.00 | 01-OCT-09:02 | 0.00 | 01-OCT-00:10 | 31834.82 | 08-OCT-09:01 | 22921.94 | 26-OCT-08:61 | 17535.06 | 22-OCT-09:04 | 6831.73 | 07-OCT-08:13 | 0.00 | 01-OCT-00:10 |
November | 0.518813E+10 | 0.126584E+10 | 220.55 | 0.324680E+10 | 0.194133E+10 | 0.00 | 1.00 | 01-NOV-08:62 | 0.00 | 01-NOV-00:10 | 30545.37 | 02-NOV-08:61 | 19297.19 | 07-NOV-09:01 | 15037.27 | 04-NOV-08:62 | 6466.94 | 11-NOV-10:01 | 0.00 | 01-NOV-00:10 |
December | 0.327599E+10 | 0.800573E+09 | 132.76 | 0.202741E+10 | 0.124857E+10 | 0.00 | 1.00 | 09-DEC-09:02 | 0.00 | 01-DEC-00:10 | 30419.50 | 15-DEC-09:02 | 19586.92 | 10-DEC-10:02 | 13700.80 | 15-DEC-09:02 | 6413.95 | 10-DEC-10:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.115508E+12 | 0.277954E+11 | 2980.76 | 0.683127E+11 | 0.471950E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.167017E+10 | 0.421373E+09 | 91.40 | 0.104622E+10 | 0.623955E+09 | 0.00 | 1.00 | 0.00 | 26887.09 | 14011.21 | 12558.07 | 5652.59 | 0.00 | |||||||
Maximum of Months | 0.175538E+11 | 0.417899E+10 | 344.59 | 0.100792E+11 | 0.770395E+10 | 0.00 | 1.00 | 0.00 | 31933.43 | 22921.94 | 18406.53 | 7219.86 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.170508E+10 | 0.434017E+09 | 87.36 | 0.108305E+10 | 0.622035E+09 | 0.00 | 1.00 | 01-JAN-10:02 | 0.00 | 01-JAN-00:05 | 27346.16 | 01-JAN-10:02 | 17744.50 | 01-JAN-10:02 | 9601.66 | 01-JAN-10:02 | 5802.02 | 01-JAN-10:02 | 0.00 | 01-JAN-00:05 |
February | 0.244559E+10 | 0.619715E+09 | 118.10 | 0.153587E+10 | 0.909719E+09 | 0.00 | 0.99 | 28-FEB-09:02 | 0.00 | 01-FEB-00:05 | 16109.56 | 28-FEB-09:02 | 8137.66 | 28-FEB-09:02 | 7971.90 | 28-FEB-09:02 | 3407.51 | 28-FEB-09:02 | 0.00 | 01-FEB-00:05 |
March | 0.358071E+10 | 0.910434E+09 | 167.84 | 0.232108E+10 | 0.125963E+10 | 0.00 | 1.00 | 07-MAR-09:02 | 0.00 | 01-MAR-00:05 | 27869.50 | 07-MAR-09:02 | 14418.56 | 07-MAR-09:02 | 13450.94 | 07-MAR-09:02 | 5879.80 | 07-MAR-09:02 | 0.00 | 01-MAR-00:05 |
April | 0.668151E+10 | 0.169759E+10 | 261.51 | 0.446194E+10 | 0.221957E+10 | 0.00 | 1.00 | 22-APR-08:62 | 0.00 | 01-APR-00:05 | 34501.07 | 29-APR-08:62 | 21088.49 | 23-APR-09:02 | 19616.82 | 30-APR-09:02 | 7365.35 | 29-APR-08:62 | 0.00 | 01-APR-00:05 |
May | 0.155249E+11 | 0.380705E+10 | 335.39 | 0.958349E+10 | 0.594144E+10 | 0.00 | 1.00 | 01-MAY-08:62 | 0.00 | 01-MAY-00:10 | 35449.13 | 24-MAY-08:61 | 21617.94 | 31-MAY-08:61 | 19596.04 | 23-MAY-08:03 | 7622.32 | 28-MAY-09:04 | 0.00 | 01-MAY-00:10 |
June | 0.169416E+11 | 0.412466E+10 | 329.50 | 0.103699E+11 | 0.657174E+10 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 35593.34 | 05-JUN-08:61 | 22211.04 | 11-JUN-09:01 | 20618.55 | 19-JUN-08:04 | 7722.90 | 17-JUN-08:02 | 0.00 | 01-JUN-00:10 |
July | 0.188936E+11 | 0.451526E+10 | 336.96 | 0.107552E+11 | 0.813838E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 35740.76 | 31-JUL-08:61 | 20722.24 | 19-JUL-08:61 | 20824.52 | 02-JUL-09:04 | 7792.37 | 09-JUL-09:13 | 0.00 | 01-JUL-00:05 |
August | 0.192848E+11 | 0.461991E+10 | 348.54 | 0.113307E+11 | 0.795411E+10 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 35630.36 | 07-AUG-08:61 | 23484.25 | 31-AUG-08:61 | 20553.62 | 14-AUG-08:04 | 7651.71 | 13-AUG-09:13 | 0.00 | 01-AUG-00:10 |
September | 0.164752E+11 | 0.389320E+10 | 325.61 | 0.934294E+10 | 0.713226E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:05 | 35777.20 | 05-SEP-08:02 | 21591.82 | 01-SEP-08:61 | 20644.06 | 05-SEP-08:04 | 8094.80 | 10-SEP-09:13 | 0.00 | 01-SEP-00:05 |
October | 0.141232E+11 | 0.338058E+10 | 306.79 | 0.866556E+10 | 0.545762E+10 | 0.00 | 1.00 | 01-OCT-09:02 | 0.00 | 01-OCT-00:10 | 35732.33 | 22-OCT-09:01 | 26322.43 | 26-OCT-08:61 | 20159.56 | 22-OCT-09:03 | 7641.66 | 07-OCT-08:13 | 0.00 | 01-OCT-00:10 |
November | 0.541079E+10 | 0.133061E+10 | 210.42 | 0.343096E+10 | 0.197984E+10 | 0.00 | 1.00 | 01-NOV-08:62 | 0.00 | 01-NOV-00:10 | 34531.88 | 02-NOV-08:61 | 20966.81 | 11-NOV-10:01 | 17051.08 | 04-NOV-08:62 | 7260.71 | 11-NOV-10:01 | 0.00 | 01-NOV-00:10 |
December | 0.335948E+10 | 0.831351E+09 | 129.11 | 0.210292E+10 | 0.125656E+10 | 0.00 | 1.00 | 10-DEC-10:02 | 0.00 | 01-DEC-00:10 | 34350.25 | 15-DEC-09:02 | 21992.82 | 10-DEC-10:02 | 18513.30 | 11-DEC-09:02 | 7188.63 | 10-DEC-10:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.124426E+12 | 0.301644E+11 | 2957.13 | 0.749836E+11 | 0.494429E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.170508E+10 | 0.434017E+09 | 87.36 | 0.108305E+10 | 0.622035E+09 | 0.00 | 0.99 | 0.00 | 16109.56 | 8137.66 | 7971.90 | 3407.51 | 0.00 | |||||||
Maximum of Months | 0.192848E+11 | 0.461991E+10 | 348.54 | 0.113307E+11 | 0.813838E+10 | 0.00 | 1.00 | 0.00 | 35777.20 | 26322.43 | 20824.52 | 8094.80 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 133.50 | 54.82 | 0.00 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 122.98 | 47.74 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 80.91 | 42.33 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 65.88 | 27.87 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.70 | 7.20 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 63.50 | 6.32 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 66.44 | 4.20 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 77.87 | 6.82 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 86.56 | 9.67 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 123.45 | 17.67 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.03 | 38.11 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 134.46 | 49.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 95.98 | 25.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.70 | 4.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.03 | 54.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 133.50 | 54.82 | 0.00 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 122.98 | 47.74 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 80.91 | 42.33 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 65.88 | 27.87 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.70 | 7.20 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 63.50 | 6.32 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 66.44 | 4.20 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 77.87 | 6.82 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 86.56 | 9.67 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 123.45 | 17.67 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.03 | 38.11 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 134.46 | 49.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 95.98 | 25.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.70 | 4.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.03 | 54.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 133.50 | 54.82 | 0.00 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 122.98 | 47.74 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 80.91 | 42.33 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 65.88 | 27.87 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.70 | 7.20 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 63.50 | 6.32 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 66.44 | 4.20 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 77.87 | 6.82 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 86.56 | 9.67 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 123.45 | 17.67 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.03 | 38.11 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 134.46 | 49.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 95.98 | 25.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.70 | 4.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.03 | 54.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 133.50 | 54.82 | 0.00 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 122.98 | 47.74 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 80.91 | 42.33 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 65.88 | 27.87 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.70 | 7.20 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 63.50 | 6.32 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 66.44 | 4.20 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 77.87 | 6.82 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 86.56 | 9.67 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 123.45 | 17.67 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.03 | 38.11 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 134.46 | 49.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 95.98 | 25.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.70 | 4.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.03 | 54.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 108.04 | 77.05 | 30.99 | 160.72 | 65.18 | 0.00 | 0.00 | 0.00 |
February | 97.98 | 63.42 | 34.56 | 148.04 | 56.81 | 0.00 | 0.00 | 0.00 |
March | 62.56 | 28.23 | 34.32 | 97.41 | 50.34 | 0.00 | 0.00 | 0.00 |
April | 46.36 | 10.86 | 35.50 | 79.15 | 33.25 | 0.00 | 0.00 | 0.00 |
May | 35.43 | 1.51 | 33.92 | 75.01 | 8.67 | 0.00 | 0.00 | 0.00 |
June | 35.00 | 0.33 | 34.67 | 75.89 | 7.60 | 0.00 | 0.00 | 0.00 |
July | 36.63 | 0.67 | 35.96 | 79.39 | 5.09 | 0.00 | 0.00 | 0.00 |
August | 43.10 | 5.17 | 37.93 | 93.18 | 8.20 | 0.00 | 0.00 | 0.00 |
September | 51.71 | 13.63 | 38.08 | 103.74 | 11.62 | 0.00 | 0.00 | 0.00 |
October | 80.23 | 41.79 | 38.44 | 148.18 | 21.13 | 0.00 | 0.00 | 0.00 |
November | 102.10 | 70.29 | 31.80 | 162.30 | 45.44 | 0.00 | 0.00 | 0.00 |
December | 105.57 | 75.81 | 29.75 | 161.74 | 59.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.89 | 32.24 | 34.66 | 115.24 | 30.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 35.00 | 0.33 | 29.75 | 75.01 | 5.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 108.04 | 77.05 | 38.44 | 162.30 | 65.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 108.04 | 77.05 | 30.99 | 160.72 | 65.18 | 0.00 | 0.00 | 0.00 |
February | 97.98 | 63.42 | 34.56 | 148.04 | 56.81 | 0.00 | 0.00 | 0.00 |
March | 62.56 | 28.23 | 34.32 | 97.41 | 50.34 | 0.00 | 0.00 | 0.00 |
April | 46.36 | 10.86 | 35.50 | 79.15 | 33.25 | 0.00 | 0.00 | 0.00 |
May | 35.43 | 1.51 | 33.92 | 75.01 | 8.67 | 0.00 | 0.00 | 0.00 |
June | 35.00 | 0.33 | 34.67 | 75.89 | 7.60 | 0.00 | 0.00 | 0.00 |
July | 36.63 | 0.67 | 35.96 | 79.39 | 5.09 | 0.00 | 0.00 | 0.00 |
August | 43.10 | 5.17 | 37.93 | 93.18 | 8.20 | 0.00 | 0.00 | 0.00 |
September | 51.71 | 13.63 | 38.08 | 103.74 | 11.62 | 0.00 | 0.00 | 0.00 |
October | 80.23 | 41.79 | 38.44 | 148.18 | 21.13 | 0.00 | 0.00 | 0.00 |
November | 102.10 | 70.29 | 31.80 | 162.30 | 45.44 | 0.00 | 0.00 | 0.00 |
December | 105.57 | 75.81 | 29.75 | 161.74 | 59.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.89 | 32.24 | 34.66 | 115.24 | 30.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 35.00 | 0.33 | 29.75 | 75.01 | 5.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 108.04 | 77.05 | 38.44 | 162.30 | 65.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 132.00 | 57.71 | 0.00 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 121.79 | 49.87 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 80.01 | 44.36 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 65.54 | 28.47 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.83 | 7.32 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 63.80 | 6.35 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 66.86 | 4.17 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 78.36 | 6.63 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 86.85 | 9.51 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 123.52 | 17.65 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 134.50 | 38.66 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 133.54 | 51.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 95.68 | 26.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.83 | 4.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 134.50 | 57.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 132.00 | 57.71 | 0.00 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 121.79 | 49.87 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 80.01 | 44.36 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 65.54 | 28.47 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.83 | 7.32 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 63.80 | 6.35 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 66.86 | 4.17 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 78.36 | 6.63 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 86.85 | 9.51 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 123.52 | 17.65 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 134.50 | 38.66 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 133.54 | 51.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 95.68 | 26.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.83 | 4.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 134.50 | 57.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 108.04 | 77.05 | 30.99 | 159.00 | 68.55 | 0.00 | 0.00 | 0.00 |
February | 97.98 | 63.42 | 34.56 | 146.67 | 59.29 | 0.00 | 0.00 | 0.00 |
March | 62.56 | 28.23 | 34.32 | 96.37 | 52.73 | 0.00 | 0.00 | 0.00 |
April | 46.36 | 10.86 | 35.50 | 78.76 | 33.95 | 0.00 | 0.00 | 0.00 |
May | 35.43 | 1.51 | 33.92 | 75.17 | 8.81 | 0.00 | 0.00 | 0.00 |
June | 35.00 | 0.33 | 34.67 | 76.26 | 7.65 | 0.00 | 0.00 | 0.00 |
July | 36.63 | 0.67 | 35.96 | 79.90 | 5.05 | 0.00 | 0.00 | 0.00 |
August | 43.10 | 5.17 | 37.93 | 93.78 | 7.98 | 0.00 | 0.00 | 0.00 |
September | 51.71 | 13.63 | 38.08 | 104.11 | 11.44 | 0.00 | 0.00 | 0.00 |
October | 80.23 | 41.79 | 38.44 | 148.29 | 21.10 | 0.00 | 0.00 | 0.00 |
November | 102.10 | 70.29 | 31.80 | 161.72 | 46.08 | 0.00 | 0.00 | 0.00 |
December | 105.57 | 75.81 | 29.75 | 160.70 | 61.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.89 | 32.24 | 34.66 | 114.91 | 31.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 35.00 | 0.33 | 29.75 | 75.17 | 5.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 108.04 | 77.05 | 38.44 | 161.72 | 68.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 132.58 | 56.54 | 1.33 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 122.19 | 49.26 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 80.20 | 44.16 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 65.43 | 29.57 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.14 | 9.08 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 63.05 | 8.28 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 65.30 | 5.75 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 77.38 | 8.46 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 86.19 | 11.63 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 123.13 | 19.77 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 134.60 | 39.60 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 133.86 | 51.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 95.37 | 27.66 | 1.33 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.14 | 5.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 134.60 | 56.54 | 1.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 132.58 | 56.54 | 1.33 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 122.19 | 49.26 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 80.20 | 44.16 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 65.43 | 29.57 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.14 | 9.08 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 63.05 | 8.28 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 65.30 | 5.75 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 77.38 | 8.46 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 86.19 | 11.63 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 123.13 | 19.77 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 134.60 | 39.60 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 133.86 | 51.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 95.37 | 27.66 | 1.33 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.14 | 5.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 134.60 | 56.54 | 1.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.45 | 76.63 | 30.82 | 158.82 | 66.80 | 1.33 | 0.00 | 0.00 |
February | 97.45 | 63.08 | 34.37 | 146.35 | 58.25 | 0.00 | 0.00 | 0.00 |
March | 62.21 | 28.08 | 34.14 | 96.07 | 52.19 | 0.00 | 0.00 | 0.00 |
April | 46.11 | 10.81 | 35.31 | 78.21 | 35.03 | 0.00 | 0.00 | 0.00 |
May | 35.23 | 1.50 | 33.74 | 73.95 | 10.82 | 0.00 | 0.00 | 0.00 |
June | 34.80 | 0.32 | 34.48 | 74.97 | 9.87 | 0.00 | 0.00 | 0.00 |
July | 36.43 | 0.67 | 35.76 | 77.67 | 6.89 | 0.00 | 0.00 | 0.00 |
August | 42.86 | 5.14 | 37.72 | 92.14 | 10.09 | 0.00 | 0.00 | 0.00 |
September | 51.43 | 13.55 | 37.87 | 102.77 | 13.86 | 0.00 | 0.00 | 0.00 |
October | 79.79 | 41.56 | 38.23 | 147.03 | 23.46 | 0.00 | 0.00 | 0.00 |
November | 101.54 | 69.91 | 31.63 | 160.95 | 46.90 | 0.00 | 0.00 | 0.00 |
December | 104.99 | 75.40 | 29.59 | 160.20 | 60.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.53 | 32.06 | 34.47 | 113.94 | 32.75 | 1.33 | 0.00 | 0.00 |
Minimum of Months | 34.80 | 0.32 | 29.59 | 73.95 | 6.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.45 | 76.63 | 38.23 | 160.95 | 66.80 | 1.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 132.89 | 55.76 | 1.33 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 122.44 | 48.65 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 80.36 | 43.69 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 65.47 | 29.44 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.09 | 9.23 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 62.99 | 8.47 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 65.20 | 5.97 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 77.31 | 8.68 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 86.12 | 11.83 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 123.09 | 19.93 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 134.66 | 39.43 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 134.03 | 50.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 95.42 | 27.53 | 1.33 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.09 | 5.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 134.66 | 55.76 | 1.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 132.89 | 55.76 | 1.33 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 122.44 | 48.65 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 80.36 | 43.69 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 65.47 | 29.44 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.09 | 9.23 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 62.99 | 8.47 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 65.20 | 5.97 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 77.31 | 8.68 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 86.12 | 11.83 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 123.09 | 19.93 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 134.66 | 39.43 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 134.03 | 50.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 95.42 | 27.53 | 1.33 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.09 | 5.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 134.66 | 55.76 | 1.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.45 | 76.63 | 30.82 | 159.19 | 65.87 | 1.50 | 0.00 | 0.00 |
February | 97.45 | 63.08 | 34.37 | 146.64 | 57.52 | 0.00 | 0.00 | 0.00 |
March | 62.21 | 28.08 | 34.14 | 96.26 | 51.64 | 0.00 | 0.00 | 0.00 |
April | 46.11 | 10.81 | 35.31 | 78.25 | 34.89 | 0.00 | 0.00 | 0.00 |
May | 35.23 | 1.50 | 33.74 | 73.90 | 10.99 | 0.00 | 0.00 | 0.00 |
June | 34.80 | 0.32 | 34.48 | 74.90 | 10.09 | 0.00 | 0.00 | 0.00 |
July | 36.43 | 0.67 | 35.76 | 77.55 | 7.15 | 0.00 | 0.00 | 0.00 |
August | 42.86 | 5.14 | 37.72 | 92.06 | 10.34 | 0.00 | 0.00 | 0.00 |
September | 51.43 | 13.55 | 37.87 | 102.69 | 14.09 | 0.00 | 0.00 | 0.00 |
October | 79.79 | 41.56 | 38.23 | 146.99 | 23.65 | 0.00 | 0.00 | 0.00 |
November | 101.54 | 69.91 | 31.63 | 161.03 | 46.70 | 0.00 | 0.00 | 0.00 |
December | 104.99 | 75.40 | 29.59 | 160.40 | 59.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.53 | 32.06 | 34.47 | 114.00 | 32.60 | 1.50 | 0.00 | 0.00 |
Minimum of Months | 34.80 | 0.32 | 29.59 | 73.90 | 7.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.45 | 76.63 | 38.23 | 161.03 | 65.87 | 1.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 133.19 | 55.11 | 1.50 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 122.71 | 48.08 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 80.57 | 43.17 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 65.59 | 29.09 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.18 | 8.98 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 63.07 | 8.24 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 65.28 | 5.78 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 77.39 | 8.45 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 86.18 | 11.62 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 123.15 | 19.69 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 134.80 | 39.10 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 134.23 | 50.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 95.56 | 27.18 | 1.50 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.18 | 5.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 134.80 | 55.11 | 1.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 133.19 | 55.11 | 1.50 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 122.71 | 48.08 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 80.57 | 43.17 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 65.59 | 29.09 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.18 | 8.98 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 63.07 | 8.24 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 65.28 | 5.78 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 77.39 | 8.45 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 86.18 | 11.62 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 123.15 | 19.69 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 134.80 | 39.10 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 134.23 | 50.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 95.56 | 27.18 | 1.50 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.18 | 5.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 134.80 | 55.11 | 1.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.45 | 76.63 | 30.82 | 159.55 | 65.11 | 1.50 | 0.00 | 0.00 |
February | 97.45 | 63.08 | 34.37 | 146.96 | 56.85 | 0.00 | 0.00 | 0.00 |
March | 62.21 | 28.08 | 34.14 | 96.51 | 51.02 | 0.00 | 0.00 | 0.00 |
April | 46.11 | 10.81 | 35.31 | 78.39 | 34.48 | 0.00 | 0.00 | 0.00 |
May | 35.23 | 1.50 | 33.74 | 74.01 | 10.71 | 0.00 | 0.00 | 0.00 |
June | 34.80 | 0.32 | 34.48 | 75.00 | 9.82 | 0.00 | 0.00 | 0.00 |
July | 36.43 | 0.67 | 35.76 | 77.65 | 6.92 | 0.00 | 0.00 | 0.00 |
August | 42.86 | 5.14 | 37.72 | 92.15 | 10.08 | 0.00 | 0.00 | 0.00 |
September | 51.43 | 13.55 | 37.87 | 102.76 | 13.84 | 0.00 | 0.00 | 0.00 |
October | 79.79 | 41.56 | 38.23 | 147.06 | 23.36 | 0.00 | 0.00 | 0.00 |
November | 101.54 | 69.91 | 31.63 | 161.19 | 46.32 | 0.00 | 0.00 | 0.00 |
December | 104.99 | 75.40 | 29.59 | 160.64 | 59.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.53 | 32.06 | 34.47 | 114.16 | 32.18 | 1.50 | 0.00 | 0.00 |
Minimum of Months | 34.80 | 0.32 | 29.59 | 74.01 | 6.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.45 | 76.63 | 38.23 | 161.19 | 65.11 | 1.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 133.92 | 53.94 | 1.50 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 123.43 | 46.98 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 81.11 | 42.06 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 65.88 | 28.24 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.08 | 8.31 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 62.88 | 7.51 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 65.10 | 5.27 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 77.22 | 7.78 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 85.94 | 10.95 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 123.14 | 19.00 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.11 | 38.34 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 134.73 | 49.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 95.74 | 26.35 | 1.50 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.08 | 5.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.11 | 53.94 | 1.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 133.92 | 53.94 | 1.50 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 123.43 | 46.98 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 81.11 | 42.06 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 65.88 | 28.24 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.08 | 8.31 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 62.88 | 7.51 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 65.10 | 5.27 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 77.22 | 7.78 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 85.94 | 10.95 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 123.14 | 19.00 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.11 | 38.34 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 134.73 | 49.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 95.74 | 26.35 | 1.50 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.08 | 5.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.11 | 53.94 | 1.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 133.92 | 53.94 | 1.50 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 123.43 | 46.98 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 81.11 | 42.06 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 65.88 | 28.24 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.08 | 8.31 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 62.88 | 7.51 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 65.10 | 5.27 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 77.22 | 7.78 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 85.94 | 10.95 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 123.14 | 19.00 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.11 | 38.34 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 134.73 | 49.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 95.74 | 26.35 | 1.50 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.08 | 5.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.11 | 53.94 | 1.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 133.92 | 53.94 | 1.50 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 123.43 | 46.98 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 81.11 | 42.06 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 65.88 | 28.24 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.08 | 8.31 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 62.88 | 7.51 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 65.10 | 5.27 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 77.22 | 7.78 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 85.94 | 10.95 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 123.14 | 19.00 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.11 | 38.34 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 134.73 | 49.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 95.74 | 26.35 | 1.50 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.08 | 5.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.11 | 53.94 | 1.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.45 | 76.63 | 30.82 | 160.35 | 63.76 | 1.50 | 0.00 | 0.00 |
February | 97.45 | 63.08 | 34.37 | 147.77 | 55.58 | 0.00 | 0.00 | 0.00 |
March | 62.21 | 28.08 | 34.14 | 97.12 | 49.73 | 0.00 | 0.00 | 0.00 |
April | 46.11 | 10.81 | 35.31 | 78.72 | 33.47 | 0.00 | 0.00 | 0.00 |
May | 35.23 | 1.50 | 33.74 | 73.89 | 9.91 | 0.00 | 0.00 | 0.00 |
June | 34.80 | 0.32 | 34.48 | 74.79 | 8.95 | 0.00 | 0.00 | 0.00 |
July | 36.43 | 0.67 | 35.76 | 77.45 | 6.32 | 0.00 | 0.00 | 0.00 |
August | 42.86 | 5.14 | 37.72 | 91.95 | 9.28 | 0.00 | 0.00 | 0.00 |
September | 51.43 | 13.55 | 37.87 | 102.47 | 13.05 | 0.00 | 0.00 | 0.00 |
October | 79.79 | 41.56 | 38.23 | 147.02 | 22.56 | 0.00 | 0.00 | 0.00 |
November | 101.54 | 69.91 | 31.63 | 161.52 | 45.43 | 0.00 | 0.00 | 0.00 |
December | 104.99 | 75.40 | 29.59 | 161.19 | 58.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.53 | 32.06 | 34.47 | 114.36 | 31.22 | 1.50 | 0.00 | 0.00 |
Minimum of Months | 34.80 | 0.32 | 29.59 | 73.89 | 6.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.45 | 76.63 | 38.23 | 161.52 | 63.76 | 1.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.45 | 76.63 | 30.82 | 160.35 | 63.76 | 1.50 | 0.00 | 0.00 |
February | 97.45 | 63.08 | 34.37 | 147.77 | 55.58 | 0.00 | 0.00 | 0.00 |
March | 62.21 | 28.08 | 34.14 | 97.12 | 49.73 | 0.00 | 0.00 | 0.00 |
April | 46.11 | 10.81 | 35.31 | 78.72 | 33.47 | 0.00 | 0.00 | 0.00 |
May | 35.23 | 1.50 | 33.74 | 73.89 | 9.91 | 0.00 | 0.00 | 0.00 |
June | 34.80 | 0.32 | 34.48 | 74.79 | 8.95 | 0.00 | 0.00 | 0.00 |
July | 36.43 | 0.67 | 35.76 | 77.45 | 6.32 | 0.00 | 0.00 | 0.00 |
August | 42.86 | 5.14 | 37.72 | 91.95 | 9.28 | 0.00 | 0.00 | 0.00 |
September | 51.43 | 13.55 | 37.87 | 102.47 | 13.05 | 0.00 | 0.00 | 0.00 |
October | 79.79 | 41.56 | 38.23 | 147.02 | 22.56 | 0.00 | 0.00 | 0.00 |
November | 101.54 | 69.91 | 31.63 | 161.52 | 45.43 | 0.00 | 0.00 | 0.00 |
December | 104.99 | 75.40 | 29.59 | 161.19 | 58.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.53 | 32.06 | 34.47 | 114.36 | 31.22 | 1.50 | 0.00 | 0.00 |
Minimum of Months | 34.80 | 0.32 | 29.59 | 73.89 | 6.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.45 | 76.63 | 38.23 | 161.52 | 63.76 | 1.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 133.65 | 53.88 | 1.50 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 123.20 | 46.88 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 80.95 | 41.98 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 65.83 | 28.05 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.27 | 8.01 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 63.14 | 7.20 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 65.41 | 4.97 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 77.44 | 7.43 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 86.04 | 10.60 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 123.11 | 18.69 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 134.93 | 38.18 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 134.49 | 49.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 95.74 | 26.14 | 1.50 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.27 | 4.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 134.93 | 53.88 | 1.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 133.65 | 53.88 | 1.50 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 123.20 | 46.88 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 80.95 | 41.98 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 65.83 | 28.05 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.27 | 8.01 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 63.14 | 7.20 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 65.41 | 4.97 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 77.44 | 7.43 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 86.04 | 10.60 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 123.11 | 18.69 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 134.93 | 38.18 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 134.49 | 49.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 95.74 | 26.14 | 1.50 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.27 | 4.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 134.93 | 53.88 | 1.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.45 | 76.63 | 30.82 | 160.10 | 63.66 | 1.50 | 0.00 | 0.00 |
February | 97.45 | 63.08 | 34.37 | 147.55 | 55.44 | 0.00 | 0.00 | 0.00 |
March | 62.21 | 28.08 | 34.14 | 96.97 | 49.62 | 0.00 | 0.00 | 0.00 |
April | 46.11 | 10.81 | 35.31 | 78.69 | 33.25 | 0.00 | 0.00 | 0.00 |
May | 35.23 | 1.50 | 33.74 | 74.13 | 9.56 | 0.00 | 0.00 | 0.00 |
June | 34.80 | 0.32 | 34.48 | 75.09 | 8.59 | 0.00 | 0.00 | 0.00 |
July | 36.43 | 0.67 | 35.76 | 77.81 | 5.97 | 0.00 | 0.00 | 0.00 |
August | 42.86 | 5.14 | 37.72 | 92.22 | 8.87 | 0.00 | 0.00 | 0.00 |
September | 51.43 | 13.55 | 37.87 | 102.61 | 12.64 | 0.00 | 0.00 | 0.00 |
October | 79.79 | 41.56 | 38.23 | 147.03 | 22.19 | 0.00 | 0.00 | 0.00 |
November | 101.54 | 69.91 | 31.63 | 161.36 | 45.23 | 0.00 | 0.00 | 0.00 |
December | 104.99 | 75.40 | 29.59 | 160.96 | 58.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.53 | 32.06 | 34.47 | 114.38 | 30.96 | 1.50 | 0.00 | 0.00 |
Minimum of Months | 34.80 | 0.32 | 29.59 | 74.13 | 5.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.45 | 76.63 | 38.23 | 161.36 | 63.66 | 1.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 133.82 | 53.58 | 1.50 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 123.37 | 46.59 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 81.08 | 41.72 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 65.91 | 27.90 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.34 | 7.93 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 63.20 | 7.12 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 65.47 | 4.91 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 77.49 | 7.37 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 86.09 | 10.52 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 123.17 | 18.60 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.02 | 38.03 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 134.61 | 48.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 95.83 | 25.98 | 1.50 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.34 | 4.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.02 | 53.58 | 1.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 133.82 | 53.58 | 1.50 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 123.37 | 46.59 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 81.08 | 41.72 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 65.91 | 27.90 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.34 | 7.93 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 63.20 | 7.12 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 65.47 | 4.91 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 77.49 | 7.37 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 86.09 | 10.52 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 123.17 | 18.60 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.02 | 38.03 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 134.61 | 48.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 95.83 | 25.98 | 1.50 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.34 | 4.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.02 | 53.58 | 1.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.45 | 76.63 | 30.82 | 160.30 | 63.30 | 1.50 | 0.00 | 0.00 |
February | 97.45 | 63.08 | 34.37 | 147.75 | 55.10 | 0.00 | 0.00 | 0.00 |
March | 62.21 | 28.08 | 34.14 | 97.13 | 49.31 | 0.00 | 0.00 | 0.00 |
April | 46.11 | 10.81 | 35.31 | 78.79 | 33.07 | 0.00 | 0.00 | 0.00 |
May | 35.23 | 1.50 | 33.74 | 74.21 | 9.46 | 0.00 | 0.00 | 0.00 |
June | 34.80 | 0.32 | 34.48 | 75.17 | 8.49 | 0.00 | 0.00 | 0.00 |
July | 36.43 | 0.67 | 35.76 | 77.89 | 5.90 | 0.00 | 0.00 | 0.00 |
August | 42.86 | 5.14 | 37.72 | 92.28 | 8.80 | 0.00 | 0.00 | 0.00 |
September | 51.43 | 13.55 | 37.87 | 102.67 | 12.55 | 0.00 | 0.00 | 0.00 |
October | 79.79 | 41.56 | 38.23 | 147.10 | 22.07 | 0.00 | 0.00 | 0.00 |
November | 101.54 | 69.91 | 31.63 | 161.46 | 45.06 | 0.00 | 0.00 | 0.00 |
December | 104.99 | 75.40 | 29.59 | 161.11 | 57.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.53 | 32.06 | 34.47 | 114.49 | 30.77 | 1.50 | 0.00 | 0.00 |
Minimum of Months | 34.80 | 0.32 | 29.59 | 74.21 | 5.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.45 | 76.63 | 38.23 | 161.46 | 63.30 | 1.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 134.22 | 52.77 | 1.67 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 123.80 | 45.76 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 81.40 | 40.92 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 66.09 | 27.45 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.40 | 7.80 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 63.22 | 7.04 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 65.44 | 4.90 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 77.43 | 7.39 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 86.05 | 10.51 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 123.19 | 18.49 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.21 | 37.65 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 134.92 | 48.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 95.98 | 25.63 | 1.67 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.40 | 4.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.21 | 52.77 | 1.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 134.22 | 52.77 | 1.67 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 123.80 | 45.76 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 81.40 | 40.92 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 66.09 | 27.45 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.40 | 7.80 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 63.22 | 7.04 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 65.44 | 4.90 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 77.43 | 7.39 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 86.05 | 10.51 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 123.19 | 18.49 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.21 | 37.65 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 134.92 | 48.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 95.98 | 25.63 | 1.67 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.40 | 4.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.21 | 52.77 | 1.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.45 | 76.63 | 30.82 | 160.78 | 62.35 | 1.67 | 0.00 | 0.00 |
February | 97.45 | 63.08 | 34.37 | 148.27 | 54.12 | 0.00 | 0.00 | 0.00 |
March | 62.21 | 28.08 | 34.14 | 97.51 | 48.37 | 0.00 | 0.00 | 0.00 |
April | 46.11 | 10.81 | 35.31 | 79.00 | 32.54 | 0.00 | 0.00 | 0.00 |
May | 35.23 | 1.50 | 33.74 | 74.28 | 9.31 | 0.00 | 0.00 | 0.00 |
June | 34.80 | 0.32 | 34.48 | 75.19 | 8.41 | 0.00 | 0.00 | 0.00 |
July | 36.43 | 0.67 | 35.76 | 77.84 | 5.89 | 0.00 | 0.00 | 0.00 |
August | 42.86 | 5.14 | 37.72 | 92.21 | 8.83 | 0.00 | 0.00 | 0.00 |
September | 51.43 | 13.55 | 37.87 | 102.63 | 12.53 | 0.00 | 0.00 | 0.00 |
October | 79.79 | 41.56 | 38.23 | 147.12 | 21.95 | 0.00 | 0.00 | 0.00 |
November | 101.54 | 69.91 | 31.63 | 161.69 | 44.61 | 0.00 | 0.00 | 0.00 |
December | 104.99 | 75.40 | 29.59 | 161.48 | 56.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.53 | 32.06 | 34.47 | 114.67 | 30.36 | 1.67 | 0.00 | 0.00 |
Minimum of Months | 34.80 | 0.32 | 29.59 | 74.28 | 5.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.45 | 76.63 | 38.23 | 161.69 | 62.35 | 1.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 134.94 | 50.14 | 0.00 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 124.61 | 43.02 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 81.87 | 38.16 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 66.25 | 25.77 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 61.94 | 7.53 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 62.53 | 7.00 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 64.46 | 5.16 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 76.41 | 7.88 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 85.25 | 10.83 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 122.66 | 18.37 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.41 | 36.40 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 135.51 | 45.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 95.85 | 24.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 61.94 | 5.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.51 | 50.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 134.94 | 50.14 | 0.00 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 124.61 | 43.02 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 81.87 | 38.16 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 66.25 | 25.77 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 61.94 | 7.53 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 62.53 | 7.00 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 64.46 | 5.16 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 76.41 | 7.88 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 85.25 | 10.83 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 122.66 | 18.37 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.41 | 36.40 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 135.51 | 45.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 95.85 | 24.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 61.94 | 5.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.51 | 50.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.45 | 76.63 | 30.82 | 161.63 | 59.25 | 0.00 | 0.00 | 0.00 |
February | 97.45 | 63.08 | 34.37 | 149.24 | 50.90 | 0.00 | 0.00 | 0.00 |
March | 62.21 | 28.08 | 34.14 | 98.06 | 45.13 | 0.00 | 0.00 | 0.00 |
April | 46.11 | 10.81 | 35.31 | 79.20 | 30.57 | 0.00 | 0.00 | 0.00 |
May | 35.23 | 1.50 | 33.74 | 73.72 | 8.99 | 0.00 | 0.00 | 0.00 |
June | 34.80 | 0.32 | 34.48 | 74.36 | 8.36 | 0.00 | 0.00 | 0.00 |
July | 36.43 | 0.67 | 35.76 | 76.68 | 6.19 | 0.00 | 0.00 | 0.00 |
August | 42.86 | 5.14 | 37.72 | 90.99 | 9.41 | 0.00 | 0.00 | 0.00 |
September | 51.43 | 13.55 | 37.87 | 101.66 | 12.92 | 0.00 | 0.00 | 0.00 |
October | 79.79 | 41.56 | 38.23 | 146.48 | 21.82 | 0.00 | 0.00 | 0.00 |
November | 101.54 | 69.91 | 31.63 | 161.93 | 43.14 | 0.00 | 0.00 | 0.00 |
December | 104.99 | 75.40 | 29.59 | 162.18 | 54.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.53 | 32.06 | 34.47 | 114.51 | 29.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.80 | 0.32 | 29.59 | 73.72 | 6.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.45 | 76.63 | 38.23 | 162.18 | 59.25 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.357553E+09 | 0.146827E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.297508E+09 | 0.115498E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.216704E+09 | 0.113364E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.170765E+09 | 72230419.53 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.167943E+09 | 19291061.02 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.164587E+09 | 16369319.15 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.177941E+09 | 11261294.38 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.208556E+09 | 18259750.54 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.224359E+09 | 25054524.90 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.330659E+09 | 47326612.88 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.349989E+09 | 98774214.79 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.360139E+09 | 0.132820E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.302670E+10 | 0.817076E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.164587E+09 | 11261294.38 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.360139E+09 | 0.146827E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.357553E+09 | 0.146827E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.297508E+09 | 0.115498E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.216704E+09 | 0.113364E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.170765E+09 | 72230419.53 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.167943E+09 | 19291061.02 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.164587E+09 | 16369319.15 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.177941E+09 | 11261294.38 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.208556E+09 | 18259750.54 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.224359E+09 | 25054524.90 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.330659E+09 | 47326612.88 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.349989E+09 | 98774214.79 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.360139E+09 | 0.132820E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.302670E+10 | 0.817076E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.164587E+09 | 11261294.38 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.360139E+09 | 0.146827E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.357553E+09 | 0.146827E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.297508E+09 | 0.115498E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.216704E+09 | 0.113364E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.170765E+09 | 72230419.53 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.167943E+09 | 19291061.02 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.164587E+09 | 16369319.15 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.177941E+09 | 11261294.38 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.208556E+09 | 18259750.54 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.224359E+09 | 25054524.90 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.330659E+09 | 47326612.88 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.349989E+09 | 98774214.79 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.360139E+09 | 0.132820E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.302670E+10 | 0.817076E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.164587E+09 | 11261294.38 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.360139E+09 | 0.146827E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.357553E+09 | 0.146827E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.297508E+09 | 0.115498E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.216704E+09 | 0.113364E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.170765E+09 | 72230419.53 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.167943E+09 | 19291061.02 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.164587E+09 | 16369319.15 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.177941E+09 | 11261294.38 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.208556E+09 | 18259750.54 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.224359E+09 | 25054524.90 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.330659E+09 | 47326612.88 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.349989E+09 | 98774214.79 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.360139E+09 | 0.132820E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.302670E+10 | 0.817076E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.164587E+09 | 11261294.38 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.360139E+09 | 0.146827E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.289368E+09 | 0.206369E+09 | 82998250.47 | 0.430473E+09 | 0.174566E+09 |
February | 0.237043E+09 | 0.153434E+09 | 83608932.79 | 0.358132E+09 | 0.137431E+09 |
March | 0.167547E+09 | 75614314.65 | 91933022.62 | 0.260892E+09 | 0.134836E+09 |
April | 0.120178E+09 | 28160696.70 | 92017377.45 | 0.205156E+09 | 86179317.52 |
May | 94885545.44 | 4032502.60 | 90853042.84 | 0.200900E+09 | 23214033.89 |
June | 90707111.54 | 845477.76 | 89861633.79 | 0.196717E+09 | 19708711.45 |
July | 98120832.69 | 1803450.40 | 96317382.29 | 0.212633E+09 | 13629668.08 |
August | 0.115434E+09 | 13855553.09 | 0.101578E+09 | 0.249568E+09 | 21972421.95 |
September | 0.134034E+09 | 35323541.73 | 98710078.52 | 0.268886E+09 | 30131396.09 |
October | 0.214886E+09 | 0.111935E+09 | 0.102951E+09 | 0.396885E+09 | 56596868.81 |
November | 0.264635E+09 | 0.182204E+09 | 82431092.21 | 0.420678E+09 | 0.117775E+09 |
December | 0.282747E+09 | 0.203054E+09 | 79693274.94 | 0.433212E+09 | 0.158026E+09 |
Annual Sum or Average | 0.210959E+10 | 0.101663E+10 | 0.109295E+10 | 0.363413E+10 | 0.974067E+09 |
Minimum of Months | 90707111.54 | 845477.76 | 79693274.94 | 0.196717E+09 | 13629668.08 |
Maximum of Months | 0.289368E+09 | 0.206369E+09 | 0.102951E+09 | 0.433212E+09 | 0.174566E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.289368E+09 | 0.206369E+09 | 82998250.47 | 0.430473E+09 | 0.174566E+09 |
February | 0.237043E+09 | 0.153434E+09 | 83608932.79 | 0.358132E+09 | 0.137431E+09 |
March | 0.167547E+09 | 75614314.65 | 91933022.62 | 0.260892E+09 | 0.134836E+09 |
April | 0.120178E+09 | 28160696.70 | 92017377.45 | 0.205156E+09 | 86179317.52 |
May | 94885545.44 | 4032502.60 | 90853042.84 | 0.200900E+09 | 23214033.89 |
June | 90707111.54 | 845477.76 | 89861633.79 | 0.196717E+09 | 19708711.45 |
July | 98120832.69 | 1803450.40 | 96317382.29 | 0.212633E+09 | 13629668.08 |
August | 0.115434E+09 | 13855553.09 | 0.101578E+09 | 0.249568E+09 | 21972421.95 |
September | 0.134034E+09 | 35323541.73 | 98710078.52 | 0.268886E+09 | 30131396.09 |
October | 0.214886E+09 | 0.111935E+09 | 0.102951E+09 | 0.396885E+09 | 56596868.81 |
November | 0.264635E+09 | 0.182204E+09 | 82431092.21 | 0.420678E+09 | 0.117775E+09 |
December | 0.282747E+09 | 0.203054E+09 | 79693274.94 | 0.433212E+09 | 0.158026E+09 |
Annual Sum or Average | 0.210959E+10 | 0.101663E+10 | 0.109295E+10 | 0.363413E+10 | 0.974067E+09 |
Minimum of Months | 90707111.54 | 845477.76 | 79693274.94 | 0.196717E+09 | 13629668.08 |
Maximum of Months | 0.289368E+09 | 0.206369E+09 | 0.102951E+09 | 0.433212E+09 | 0.174566E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.353555E+09 | 0.154576E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.294624E+09 | 0.120644E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.214299E+09 | 0.118814E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.169879E+09 | 73794082.57 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.168294E+09 | 19611330.35 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.165373E+09 | 16469196.86 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.179084E+09 | 11162480.03 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.209877E+09 | 17768281.08 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.225125E+09 | 24646840.67 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.330829E+09 | 47283849.37 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.348628E+09 | 0.100205E+09 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.357685E+09 | 0.137676E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.301725E+10 | 0.842652E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.165373E+09 | 11162480.03 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.357685E+09 | 0.154576E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.353555E+09 | 0.154576E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.294624E+09 | 0.120644E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.214299E+09 | 0.118814E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.169879E+09 | 73794082.57 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.168294E+09 | 19611330.35 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.165373E+09 | 16469196.86 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.179084E+09 | 11162480.03 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.209877E+09 | 17768281.08 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.225125E+09 | 24646840.67 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.330829E+09 | 47283849.37 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.348628E+09 | 0.100205E+09 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.357685E+09 | 0.137676E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.301725E+10 | 0.842652E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.165373E+09 | 11162480.03 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.357685E+09 | 0.154576E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.289368E+09 | 0.206369E+09 | 82998250.47 | 0.425872E+09 | 0.183616E+09 |
February | 0.237043E+09 | 0.153434E+09 | 83608932.79 | 0.354815E+09 | 0.143444E+09 |
March | 0.167547E+09 | 75614314.65 | 91933022.62 | 0.258112E+09 | 0.141219E+09 |
April | 0.120178E+09 | 28160696.70 | 92017377.45 | 0.204152E+09 | 88010023.42 |
May | 94885545.44 | 4032502.60 | 90853042.84 | 0.201331E+09 | 23598184.06 |
June | 90707111.54 | 845477.76 | 89861633.79 | 0.197656E+09 | 19829430.51 |
July | 98120832.69 | 1803450.40 | 96317382.29 | 0.214000E+09 | 13514077.35 |
August | 0.115434E+09 | 13855553.09 | 0.101578E+09 | 0.251175E+09 | 21383991.19 |
September | 0.134034E+09 | 35323541.73 | 98710078.52 | 0.269857E+09 | 29645326.61 |
October | 0.214886E+09 | 0.111935E+09 | 0.102951E+09 | 0.397191E+09 | 56522867.26 |
November | 0.264635E+09 | 0.182204E+09 | 82431092.21 | 0.419177E+09 | 0.119435E+09 |
December | 0.282747E+09 | 0.203054E+09 | 79693274.94 | 0.430426E+09 | 0.163687E+09 |
Annual Sum or Average | 0.210959E+10 | 0.101663E+10 | 0.109295E+10 | 0.362376E+10 | 0.100390E+10 |
Minimum of Months | 90707111.54 | 845477.76 | 79693274.94 | 0.197656E+09 | 13514077.35 |
Maximum of Months | 0.289368E+09 | 0.206369E+09 | 0.102951E+09 | 0.430426E+09 | 0.183616E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.355101E+09 | 0.151444E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.295610E+09 | 0.119175E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.214818E+09 | 0.118286E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.169597E+09 | 76636682.34 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.166426E+09 | 24318929.75 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.163416E+09 | 21464072.01 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.174909E+09 | 15395004.69 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.207256E+09 | 22671122.14 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.223398E+09 | 30155028.22 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.329780E+09 | 52961435.38 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.348882E+09 | 0.102634E+09 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.358536E+09 | 0.137073E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.300773E+10 | 0.872214E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.163416E+09 | 15395004.69 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.358536E+09 | 0.151444E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.355101E+09 | 0.151444E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.295610E+09 | 0.119175E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.214818E+09 | 0.118286E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.169597E+09 | 76636682.34 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.166426E+09 | 24318929.75 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.163416E+09 | 21464072.01 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.174909E+09 | 15395004.69 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.207256E+09 | 22671122.14 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.223398E+09 | 30155028.22 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.329780E+09 | 52961435.38 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.348882E+09 | 0.102634E+09 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.358536E+09 | 0.137073E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.300773E+10 | 0.872214E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.163416E+09 | 15395004.69 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.358536E+09 | 0.151444E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287786E+09 | 0.205242E+09 | 82544708.12 | 0.425377E+09 | 0.178912E+09 |
February | 0.235747E+09 | 0.152595E+09 | 83152053.37 | 0.354046E+09 | 0.140907E+09 |
March | 0.166632E+09 | 75201121.67 | 91430656.38 | 0.257320E+09 | 0.139783E+09 |
April | 0.119521E+09 | 28006813.11 | 91514550.25 | 0.202710E+09 | 90805199.32 |
May | 94367045.19 | 4010467.07 | 90356578.12 | 0.198075E+09 | 28978099.61 |
June | 90211444.27 | 840857.66 | 89370586.61 | 0.194320E+09 | 25573290.96 |
July | 97584653.27 | 1793595.48 | 95791057.80 | 0.208039E+09 | 18450031.90 |
August | 0.114803E+09 | 13779839.69 | 0.101023E+09 | 0.246792E+09 | 27025090.97 |
September | 0.133301E+09 | 35130516.91 | 98170679.18 | 0.266386E+09 | 35914162.67 |
October | 0.213712E+09 | 0.111324E+09 | 0.102388E+09 | 0.393809E+09 | 62832644.28 |
November | 0.263189E+09 | 0.181208E+09 | 81980649.09 | 0.417184E+09 | 0.121573E+09 |
December | 0.281202E+09 | 0.201944E+09 | 79257792.56 | 0.429081E+09 | 0.162043E+09 |
Annual Sum or Average | 0.209806E+10 | 0.101108E+10 | 0.108698E+10 | 0.359314E+10 | 0.103280E+10 |
Minimum of Months | 90211444.27 | 840857.66 | 79257792.56 | 0.194320E+09 | 18450031.90 |
Maximum of Months | 0.287786E+09 | 0.205242E+09 | 0.102388E+09 | 0.429081E+09 | 0.178912E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.355928E+09 | 0.149339E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.296195E+09 | 0.117694E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.215231E+09 | 0.117033E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.169695E+09 | 76318536.11 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.166308E+09 | 24713301.88 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.163260E+09 | 21952563.30 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.174626E+09 | 15980196.26 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.207079E+09 | 23245260.86 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.223228E+09 | 30673231.39 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.329688E+09 | 53386116.46 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.349048E+09 | 0.102190E+09 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.358985E+09 | 0.135736E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.300927E+10 | 0.868261E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.163260E+09 | 15980196.26 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.358985E+09 | 0.149339E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.355928E+09 | 0.149339E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.296195E+09 | 0.117694E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.215231E+09 | 0.117033E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.169695E+09 | 76318536.11 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.166308E+09 | 24713301.88 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.163260E+09 | 21952563.30 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.174626E+09 | 15980196.26 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.207079E+09 | 23245260.86 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.223228E+09 | 30673231.39 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.329688E+09 | 53386116.46 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.349048E+09 | 0.102190E+09 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.358985E+09 | 0.135736E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.300927E+10 | 0.868261E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.163260E+09 | 15980196.26 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.358985E+09 | 0.149339E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287786E+09 | 0.205242E+09 | 82544708.12 | 0.426362E+09 | 0.176432E+09 |
February | 0.235747E+09 | 0.152595E+09 | 83152053.37 | 0.354744E+09 | 0.139161E+09 |
March | 0.166632E+09 | 75201121.67 | 91430656.38 | 0.257814E+09 | 0.138305E+09 |
April | 0.119521E+09 | 28006813.11 | 91514550.25 | 0.202828E+09 | 90429216.88 |
May | 94367045.19 | 4010467.07 | 90356578.12 | 0.197933E+09 | 29443063.45 |
June | 90211444.27 | 840857.66 | 89370586.61 | 0.194131E+09 | 26151140.07 |
July | 97584653.27 | 1793595.48 | 95791057.80 | 0.207703E+09 | 19143405.63 |
August | 0.114803E+09 | 13779839.69 | 0.101023E+09 | 0.246581E+09 | 27702497.93 |
September | 0.133301E+09 | 35130516.91 | 98170679.18 | 0.266183E+09 | 36526470.99 |
October | 0.213712E+09 | 0.111324E+09 | 0.102388E+09 | 0.393700E+09 | 63332640.08 |
November | 0.263189E+09 | 0.181208E+09 | 81980649.09 | 0.417383E+09 | 0.121049E+09 |
December | 0.281202E+09 | 0.201944E+09 | 79257792.56 | 0.429618E+09 | 0.160465E+09 |
Annual Sum or Average | 0.209806E+10 | 0.101108E+10 | 0.108698E+10 | 0.359498E+10 | 0.102814E+10 |
Minimum of Months | 90211444.27 | 840857.66 | 79257792.56 | 0.194131E+09 | 19143405.63 |
Maximum of Months | 0.287786E+09 | 0.205242E+09 | 0.102388E+09 | 0.429618E+09 | 0.176432E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.356740E+09 | 0.147599E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.296859E+09 | 0.116306E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.215795E+09 | 0.115617E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.170001E+09 | 75409141.00 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.166554E+09 | 24063867.71 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.163488E+09 | 21345392.04 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.174858E+09 | 15471507.76 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.207271E+09 | 22642698.57 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.223376E+09 | 30107115.87 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.329852E+09 | 52735980.97 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.349389E+09 | 0.101341E+09 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.359516E+09 | 0.134396E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.301370E+10 | 0.857036E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.163488E+09 | 15471507.76 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.359516E+09 | 0.147599E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.356740E+09 | 0.147599E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.296859E+09 | 0.116306E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.215795E+09 | 0.115617E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.170001E+09 | 75409141.00 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.166554E+09 | 24063867.71 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.163488E+09 | 21345392.04 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.174858E+09 | 15471507.76 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.207271E+09 | 22642698.57 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.223376E+09 | 30107115.87 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.329852E+09 | 52735980.97 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.349389E+09 | 0.101341E+09 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.359516E+09 | 0.134396E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.301370E+10 | 0.857036E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.163488E+09 | 15471507.76 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.359516E+09 | 0.147599E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287786E+09 | 0.205242E+09 | 82544708.12 | 0.427327E+09 | 0.174385E+09 |
February | 0.235747E+09 | 0.152595E+09 | 83152053.37 | 0.355535E+09 | 0.137531E+09 |
March | 0.166632E+09 | 75201121.67 | 91430656.38 | 0.258487E+09 | 0.136642E+09 |
April | 0.119521E+09 | 28006813.11 | 91514550.25 | 0.203196E+09 | 89364227.21 |
May | 94367045.19 | 4010467.07 | 90356578.12 | 0.198228E+09 | 28684468.37 |
June | 90211444.27 | 840857.66 | 89370586.61 | 0.194404E+09 | 25440698.75 |
July | 97584653.27 | 1793595.48 | 95791057.80 | 0.207977E+09 | 18547314.03 |
August | 0.114803E+09 | 13779839.69 | 0.101023E+09 | 0.246809E+09 | 26998621.73 |
September | 0.133301E+09 | 35130516.91 | 98170679.18 | 0.266360E+09 | 35864668.61 |
October | 0.213712E+09 | 0.111324E+09 | 0.102388E+09 | 0.393896E+09 | 62573709.20 |
November | 0.263189E+09 | 0.181208E+09 | 81980649.09 | 0.417792E+09 | 0.120052E+09 |
December | 0.281202E+09 | 0.201944E+09 | 79257792.56 | 0.430251E+09 | 0.158891E+09 |
Annual Sum or Average | 0.209806E+10 | 0.101108E+10 | 0.108698E+10 | 0.360026E+10 | 0.101498E+10 |
Minimum of Months | 90211444.27 | 840857.66 | 79257792.56 | 0.194404E+09 | 18547314.03 |
Maximum of Months | 0.287786E+09 | 0.205242E+09 | 0.102388E+09 | 0.430251E+09 | 0.174385E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.358679E+09 | 0.144471E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.298596E+09 | 0.113653E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.217249E+09 | 0.112661E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.170753E+09 | 73192647.41 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.166270E+09 | 22258030.54 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.162995E+09 | 19467863.35 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.174375E+09 | 14115420.42 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.206822E+09 | 20824566.09 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.222748E+09 | 28390010.59 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.329820E+09 | 50899880.63 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.350207E+09 | 99365911.23 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.360855E+09 | 0.131712E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.301937E+10 | 0.831011E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.162995E+09 | 14115420.42 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.360855E+09 | 0.144471E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.358679E+09 | 0.144471E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.298596E+09 | 0.113653E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.217249E+09 | 0.112661E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.170753E+09 | 73192647.41 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.166270E+09 | 22258030.54 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.162995E+09 | 19467863.35 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.174375E+09 | 14115420.42 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.206822E+09 | 20824566.09 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.222748E+09 | 28390010.59 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.329820E+09 | 50899880.63 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.350207E+09 | 99365911.23 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.360855E+09 | 0.131712E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.301937E+10 | 0.831011E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.162995E+09 | 14115420.42 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.360855E+09 | 0.144471E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.358679E+09 | 0.144471E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.298596E+09 | 0.113653E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.217249E+09 | 0.112661E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.170753E+09 | 73192647.41 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.166270E+09 | 22258030.54 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.162995E+09 | 19467863.35 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.174375E+09 | 14115420.42 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.206822E+09 | 20824566.09 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.222748E+09 | 28390010.59 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.329820E+09 | 50899880.63 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.350207E+09 | 99365911.23 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.360855E+09 | 0.131712E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.301937E+10 | 0.831011E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.162995E+09 | 14115420.42 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.360855E+09 | 0.144471E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.358679E+09 | 0.144471E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.298596E+09 | 0.113653E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.217249E+09 | 0.112661E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.170753E+09 | 73192647.41 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.166270E+09 | 22258030.54 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.162995E+09 | 19467863.35 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.174375E+09 | 14115420.42 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.206822E+09 | 20824566.09 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.222748E+09 | 28390010.59 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.329820E+09 | 50899880.63 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.350207E+09 | 99365911.23 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.360855E+09 | 0.131712E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.301937E+10 | 0.831011E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.162995E+09 | 14115420.42 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.360855E+09 | 0.144471E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287786E+09 | 0.205242E+09 | 82544708.12 | 0.429485E+09 | 0.170764E+09 |
February | 0.235747E+09 | 0.152595E+09 | 83152053.37 | 0.357487E+09 | 0.134449E+09 |
March | 0.166632E+09 | 75201121.67 | 91430656.38 | 0.260134E+09 | 0.133204E+09 |
April | 0.119521E+09 | 28006813.11 | 91514550.25 | 0.204051E+09 | 86766553.27 |
May | 94367045.19 | 4010467.07 | 90356578.12 | 0.197912E+09 | 26540378.74 |
June | 90211444.27 | 840857.66 | 89370586.61 | 0.193854E+09 | 23210301.56 |
July | 97584653.27 | 1793595.48 | 95791057.80 | 0.207436E+09 | 16924367.66 |
August | 0.114803E+09 | 13779839.69 | 0.101023E+09 | 0.246282E+09 | 24843743.52 |
September | 0.133301E+09 | 35130516.91 | 98170679.18 | 0.265610E+09 | 33836530.44 |
October | 0.213712E+09 | 0.111324E+09 | 0.102388E+09 | 0.393787E+09 | 60416012.15 |
November | 0.263189E+09 | 0.181208E+09 | 81980649.09 | 0.418671E+09 | 0.117747E+09 |
December | 0.281202E+09 | 0.201944E+09 | 79257792.56 | 0.431720E+09 | 0.155780E+09 |
Annual Sum or Average | 0.209806E+10 | 0.101108E+10 | 0.108698E+10 | 0.360643E+10 | 0.984482E+09 |
Minimum of Months | 90211444.27 | 840857.66 | 79257792.56 | 0.193854E+09 | 16924367.66 |
Maximum of Months | 0.287786E+09 | 0.205242E+09 | 0.102388E+09 | 0.431720E+09 | 0.170764E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287786E+09 | 0.205242E+09 | 82544708.12 | 0.429485E+09 | 0.170764E+09 |
February | 0.235747E+09 | 0.152595E+09 | 83152053.37 | 0.357487E+09 | 0.134449E+09 |
March | 0.166632E+09 | 75201121.67 | 91430656.38 | 0.260134E+09 | 0.133204E+09 |
April | 0.119521E+09 | 28006813.11 | 91514550.25 | 0.204051E+09 | 86766553.27 |
May | 94367045.19 | 4010467.07 | 90356578.12 | 0.197912E+09 | 26540378.74 |
June | 90211444.27 | 840857.66 | 89370586.61 | 0.193854E+09 | 23210301.56 |
July | 97584653.27 | 1793595.48 | 95791057.80 | 0.207436E+09 | 16924367.66 |
August | 0.114803E+09 | 13779839.69 | 0.101023E+09 | 0.246282E+09 | 24843743.52 |
September | 0.133301E+09 | 35130516.91 | 98170679.18 | 0.265610E+09 | 33836530.44 |
October | 0.213712E+09 | 0.111324E+09 | 0.102388E+09 | 0.393787E+09 | 60416012.15 |
November | 0.263189E+09 | 0.181208E+09 | 81980649.09 | 0.418671E+09 | 0.117747E+09 |
December | 0.281202E+09 | 0.201944E+09 | 79257792.56 | 0.431720E+09 | 0.155780E+09 |
Annual Sum or Average | 0.209806E+10 | 0.101108E+10 | 0.108698E+10 | 0.360643E+10 | 0.984482E+09 |
Minimum of Months | 90211444.27 | 840857.66 | 79257792.56 | 0.193854E+09 | 16924367.66 |
Maximum of Months | 0.287786E+09 | 0.205242E+09 | 0.102388E+09 | 0.431720E+09 | 0.170764E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.357965E+09 | 0.144301E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.298036E+09 | 0.113412E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.216816E+09 | 0.112440E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.170632E+09 | 72714419.76 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.166794E+09 | 21458799.12 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.163648E+09 | 18654756.08 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.175185E+09 | 13319646.87 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.207405E+09 | 19908057.13 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.223008E+09 | 27475323.67 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.329746E+09 | 50065967.38 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.349744E+09 | 98954976.04 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.360222E+09 | 0.131497E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.301920E+10 | 0.824201E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.163648E+09 | 13319646.87 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.360222E+09 | 0.144301E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.357965E+09 | 0.144301E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.298036E+09 | 0.113412E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.216816E+09 | 0.112440E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.170632E+09 | 72714419.76 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.166794E+09 | 21458799.12 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.163648E+09 | 18654756.08 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.175185E+09 | 13319646.87 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.207405E+09 | 19908057.13 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.223008E+09 | 27475323.67 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.329746E+09 | 50065967.38 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.349744E+09 | 98954976.04 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.360222E+09 | 0.131497E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.301920E+10 | 0.824201E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.163648E+09 | 13319646.87 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.360222E+09 | 0.144301E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287786E+09 | 0.205242E+09 | 82544708.12 | 0.428806E+09 | 0.170494E+09 |
February | 0.235747E+09 | 0.152595E+09 | 83152053.37 | 0.356959E+09 | 0.134118E+09 |
March | 0.166632E+09 | 75201121.67 | 91430656.38 | 0.259727E+09 | 0.132894E+09 |
April | 0.119521E+09 | 28006813.11 | 91514550.25 | 0.203971E+09 | 86189317.94 |
May | 94367045.19 | 4010467.07 | 90356578.12 | 0.198542E+09 | 25605781.65 |
June | 90211444.27 | 840857.66 | 89370586.61 | 0.194628E+09 | 22256970.66 |
July | 97584653.27 | 1793595.48 | 95791057.80 | 0.208396E+09 | 15995888.59 |
August | 0.114803E+09 | 13779839.69 | 0.101023E+09 | 0.247000E+09 | 23770578.00 |
September | 0.133301E+09 | 35130516.91 | 98170679.18 | 0.265969E+09 | 32765257.89 |
October | 0.213712E+09 | 0.111324E+09 | 0.102388E+09 | 0.393801E+09 | 59425759.99 |
November | 0.263189E+09 | 0.181208E+09 | 81980649.09 | 0.418249E+09 | 0.117234E+09 |
December | 0.281202E+09 | 0.201944E+09 | 79257792.56 | 0.431118E+09 | 0.155466E+09 |
Annual Sum or Average | 0.209806E+10 | 0.101108E+10 | 0.108698E+10 | 0.360717E+10 | 0.976215E+09 |
Minimum of Months | 90211444.27 | 840857.66 | 79257792.56 | 0.194628E+09 | 15995888.59 |
Maximum of Months | 0.287786E+09 | 0.205242E+09 | 0.102388E+09 | 0.431118E+09 | 0.170494E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.358411E+09 | 0.143502E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.298446E+09 | 0.112712E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.217165E+09 | 0.111731E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.170836E+09 | 72322497.97 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.166983E+09 | 21227209.91 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.163823E+09 | 18452656.67 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.175364E+09 | 13153896.57 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.207551E+09 | 19731937.26 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.223135E+09 | 27279923.15 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.329894E+09 | 49806320.89 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.349965E+09 | 98575547.00 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.360548E+09 | 0.130831E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.302212E+10 | 0.819326E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.163823E+09 | 13153896.57 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.360548E+09 | 0.143502E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.358411E+09 | 0.143502E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.298446E+09 | 0.112712E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.217165E+09 | 0.111731E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.170836E+09 | 72322497.97 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.166983E+09 | 21227209.91 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.163823E+09 | 18452656.67 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.175364E+09 | 13153896.57 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.207551E+09 | 19731937.26 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.223135E+09 | 27279923.15 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.329894E+09 | 49806320.89 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.349965E+09 | 98575547.00 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.360548E+09 | 0.130831E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.302212E+10 | 0.819326E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.163823E+09 | 13153896.57 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.360548E+09 | 0.143502E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287786E+09 | 0.205242E+09 | 82544708.12 | 0.429338E+09 | 0.169552E+09 |
February | 0.235747E+09 | 0.152595E+09 | 83152053.37 | 0.357449E+09 | 0.133292E+09 |
March | 0.166632E+09 | 75201121.67 | 91430656.38 | 0.260143E+09 | 0.132059E+09 |
April | 0.119521E+09 | 28006813.11 | 91514550.25 | 0.204217E+09 | 85727088.78 |
May | 94367045.19 | 4010467.07 | 90356578.12 | 0.198769E+09 | 25332258.75 |
June | 90211444.27 | 840857.66 | 89370586.61 | 0.194837E+09 | 22017509.90 |
July | 97584653.27 | 1793595.48 | 95791057.80 | 0.208607E+09 | 15798283.46 |
August | 0.114803E+09 | 13779839.69 | 0.101023E+09 | 0.247174E+09 | 23562041.55 |
September | 0.133301E+09 | 35130516.91 | 98170679.18 | 0.266121E+09 | 32533909.56 |
October | 0.213712E+09 | 0.111324E+09 | 0.102388E+09 | 0.393979E+09 | 59119873.05 |
November | 0.263189E+09 | 0.181208E+09 | 81980649.09 | 0.418513E+09 | 0.116785E+09 |
December | 0.281202E+09 | 0.201944E+09 | 79257792.56 | 0.431506E+09 | 0.154680E+09 |
Annual Sum or Average | 0.209806E+10 | 0.101108E+10 | 0.108698E+10 | 0.361065E+10 | 0.970458E+09 |
Minimum of Months | 90211444.27 | 840857.66 | 79257792.56 | 0.194837E+09 | 15798283.46 |
Maximum of Months | 0.287786E+09 | 0.205242E+09 | 0.102388E+09 | 0.431506E+09 | 0.169552E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.359508E+09 | 0.141330E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.299489E+09 | 0.110705E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.218023E+09 | 0.109598E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.171293E+09 | 71150366.41 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.167133E+09 | 20879055.57 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.163865E+09 | 18254675.63 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.175263E+09 | 13125253.41 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.207396E+09 | 19792157.82 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.223049E+09 | 27234568.99 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.329944E+09 | 49515796.87 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.350466E+09 | 97600486.60 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.361380E+09 | 0.128942E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.302681E+10 | 0.808128E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.163865E+09 | 13125253.41 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.361380E+09 | 0.141330E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.359508E+09 | 0.141330E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.299489E+09 | 0.110705E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.218023E+09 | 0.109598E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.171293E+09 | 71150366.41 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.167133E+09 | 20879055.57 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.163865E+09 | 18254675.63 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.175263E+09 | 13125253.41 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.207396E+09 | 19792157.82 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.223049E+09 | 27234568.99 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.329944E+09 | 49515796.87 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.350466E+09 | 97600486.60 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.361380E+09 | 0.128942E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.302681E+10 | 0.808128E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.163865E+09 | 13125253.41 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.361380E+09 | 0.141330E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287786E+09 | 0.205242E+09 | 82544708.12 | 0.430643E+09 | 0.166997E+09 |
February | 0.235747E+09 | 0.152595E+09 | 83152053.37 | 0.358688E+09 | 0.130932E+09 |
March | 0.166632E+09 | 75201121.67 | 91430656.38 | 0.261168E+09 | 0.129550E+09 |
April | 0.119521E+09 | 28006813.11 | 91514550.25 | 0.204764E+09 | 84353797.99 |
May | 94367045.19 | 4010467.07 | 90356578.12 | 0.198943E+09 | 24929263.32 |
June | 90211444.27 | 840857.66 | 89370586.61 | 0.194885E+09 | 21790244.31 |
July | 97584653.27 | 1793595.48 | 95791057.80 | 0.208484E+09 | 15771953.99 |
August | 0.114803E+09 | 13779839.69 | 0.101023E+09 | 0.246988E+09 | 23641398.64 |
September | 0.133301E+09 | 35130516.91 | 98170679.18 | 0.266016E+09 | 32489059.26 |
October | 0.213712E+09 | 0.111324E+09 | 0.102388E+09 | 0.394038E+09 | 58785132.07 |
November | 0.263189E+09 | 0.181208E+09 | 81980649.09 | 0.419109E+09 | 0.115640E+09 |
December | 0.281202E+09 | 0.201944E+09 | 79257792.56 | 0.432497E+09 | 0.152456E+09 |
Annual Sum or Average | 0.209806E+10 | 0.101108E+10 | 0.108698E+10 | 0.361622E+10 | 0.957336E+09 |
Minimum of Months | 90211444.27 | 840857.66 | 79257792.56 | 0.194885E+09 | 15771953.99 |
Maximum of Months | 0.287786E+09 | 0.205242E+09 | 0.102388E+09 | 0.432497E+09 | 0.166997E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.361420E+09 | 0.134284E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.301465E+09 | 0.104081E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.219269E+09 | 0.102219E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.171729E+09 | 66796130.01 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.165889E+09 | 20158227.32 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.162076E+09 | 18156234.19 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.172663E+09 | 13808032.55 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.204665E+09 | 21117166.59 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.220957E+09 | 28064856.30 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.328534E+09 | 49214501.35 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.350982E+09 | 94345848.60 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.362963E+09 | 0.122691E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.302261E+10 | 0.774936E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.162076E+09 | 13808032.55 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.362963E+09 | 0.134284E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.361420E+09 | 0.134284E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.301465E+09 | 0.104081E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.219269E+09 | 0.102219E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.171729E+09 | 66796130.01 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.165889E+09 | 20158227.32 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.162076E+09 | 18156234.19 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.172663E+09 | 13808032.55 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.204665E+09 | 21117166.59 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.220957E+09 | 28064856.30 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.328534E+09 | 49214501.35 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.350982E+09 | 94345848.60 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.362963E+09 | 0.122691E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.302261E+10 | 0.774936E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.162076E+09 | 13808032.55 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.362963E+09 | 0.134284E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287786E+09 | 0.205242E+09 | 82544708.12 | 0.432921E+09 | 0.158704E+09 |
February | 0.235747E+09 | 0.152595E+09 | 83152053.37 | 0.361045E+09 | 0.123141E+09 |
March | 0.166632E+09 | 75201121.67 | 91430656.38 | 0.262657E+09 | 0.120869E+09 |
April | 0.119521E+09 | 28006813.11 | 91514550.25 | 0.205279E+09 | 79227186.06 |
May | 94367045.19 | 4010467.07 | 90356578.12 | 0.197442E+09 | 24081790.26 |
June | 90211444.27 | 840857.66 | 89370586.61 | 0.192730E+09 | 21679378.84 |
July | 97584653.27 | 1793595.48 | 95791057.80 | 0.205372E+09 | 16586831.16 |
August | 0.114803E+09 | 13779839.69 | 0.101023E+09 | 0.243709E+09 | 25213138.54 |
September | 0.133301E+09 | 35130516.91 | 98170679.18 | 0.263504E+09 | 33478484.78 |
October | 0.213712E+09 | 0.111324E+09 | 0.102388E+09 | 0.392338E+09 | 58444242.15 |
November | 0.263189E+09 | 0.181208E+09 | 81980649.09 | 0.419710E+09 | 0.111810E+09 |
December | 0.281202E+09 | 0.201944E+09 | 79257792.56 | 0.434380E+09 | 0.145097E+09 |
Annual Sum or Average | 0.209806E+10 | 0.101108E+10 | 0.108698E+10 | 0.361109E+10 | 0.918332E+09 |
Minimum of Months | 90211444.27 | 840857.66 | 79257792.56 | 0.192730E+09 | 16586831.16 |
Maximum of Months | 0.287786E+09 | 0.205242E+09 | 0.102388E+09 | 0.434380E+09 | 0.158704E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 855.42 | 349.63 | 575.55 | 410.47 | 165.08 | 0.00 | 0.00 |
February | 787.99 | 304.59 | 522.00 | 337.88 | 184.12 | 0.00 | 0.00 |
March | 518.44 | 269.98 | 333.25 | 150.40 | 182.86 | 0.00 | 0.00 |
April | 421.83 | 177.96 | 247.00 | 57.88 | 189.12 | 0.00 | 0.00 |
May | 400.83 | 46.14 | 188.73 | 8.02 | 180.71 | 0.00 | 0.00 |
June | 405.78 | 40.47 | 186.43 | 1.74 | 184.69 | 0.00 | 0.00 |
July | 424.52 | 26.99 | 195.16 | 3.59 | 191.58 | 0.00 | 0.00 |
August | 497.82 | 43.68 | 229.60 | 27.56 | 202.04 | 0.00 | 0.00 |
September | 553.71 | 61.91 | 275.48 | 72.60 | 202.88 | 0.00 | 0.00 |
October | 790.18 | 112.94 | 427.41 | 222.64 | 204.77 | 0.00 | 0.00 |
November | 864.70 | 243.31 | 543.91 | 374.49 | 169.42 | 0.00 | 0.00 |
December | 861.33 | 316.36 | 562.39 | 403.88 | 158.51 | 0.00 | 0.00 |
Annual Sum or Average | 614.38 | 165.41 | 356.37 | 171.74 | 184.63 | 0.00 | 0.00 |
Minimum of Months | 400.83 | 26.99 | 186.43 | 1.74 | 158.51 | 0.00 | 0.00 |
Maximum of Months | 864.70 | 349.63 | 575.55 | 410.47 | 204.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 423.01 | 183.98 | 287.78 | 205.24 | 82.54 | 0.00 | 0.00 |
February | 390.24 | 159.03 | 261.00 | 168.94 | 92.06 | 0.00 | 0.00 |
March | 256.39 | 141.45 | 166.63 | 75.20 | 91.43 | 0.00 | 0.00 |
April | 209.84 | 90.89 | 123.50 | 28.94 | 94.56 | 0.00 | 0.00 |
May | 200.84 | 23.45 | 94.36 | 4.01 | 90.35 | 0.00 | 0.00 |
June | 203.86 | 20.36 | 93.22 | 0.87 | 92.35 | 0.00 | 0.00 |
July | 213.62 | 13.38 | 97.58 | 1.79 | 95.79 | 0.00 | 0.00 |
August | 250.50 | 21.25 | 114.80 | 13.78 | 101.02 | 0.00 | 0.00 |
September | 277.82 | 30.45 | 137.74 | 36.30 | 101.44 | 0.00 | 0.00 |
October | 395.33 | 56.41 | 213.71 | 111.32 | 102.39 | 0.00 | 0.00 |
November | 430.72 | 123.40 | 271.95 | 187.24 | 84.71 | 0.00 | 0.00 |
December | 427.79 | 163.92 | 281.19 | 201.94 | 79.26 | 0.00 | 0.00 |
Annual Sum or Average | 306.26 | 85.27 | 178.19 | 85.87 | 92.32 | 0.00 | 0.00 |
Minimum of Months | 200.84 | 13.38 | 93.22 | 0.87 | 79.26 | 0.00 | 0.00 |
Maximum of Months | 430.72 | 183.98 | 287.78 | 205.24 | 102.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 423.98 | 179.88 | 287.19 | 204.81 | 82.37 | 0.00 | 0.00 |
February | 390.73 | 156.77 | 260.46 | 168.59 | 91.87 | 0.00 | 0.00 |
March | 256.48 | 140.51 | 166.28 | 75.04 | 91.24 | 0.00 | 0.00 |
April | 209.07 | 94.17 | 123.25 | 28.88 | 94.37 | 0.00 | 0.00 |
May | 198.23 | 28.98 | 94.17 | 4.00 | 90.17 | 0.00 | 0.00 |
June | 201.06 | 26.43 | 93.02 | 0.87 | 92.16 | 0.00 | 0.00 |
July | 208.28 | 18.38 | 97.38 | 1.79 | 95.59 | 0.00 | 0.00 |
August | 246.90 | 27.02 | 114.56 | 13.75 | 100.81 | 0.00 | 0.00 |
September | 275.15 | 37.12 | 137.46 | 36.23 | 101.23 | 0.00 | 0.00 |
October | 393.28 | 63.01 | 213.27 | 111.09 | 102.17 | 0.00 | 0.00 |
November | 430.15 | 126.10 | 271.40 | 186.86 | 84.54 | 0.00 | 0.00 |
December | 427.92 | 162.85 | 280.62 | 201.52 | 79.09 | 0.00 | 0.00 |
Annual Sum or Average | 304.69 | 88.07 | 177.82 | 85.69 | 92.13 | 0.00 | 0.00 |
Minimum of Months | 198.23 | 18.38 | 93.02 | 0.87 | 79.09 | 0.00 | 0.00 |
Maximum of Months | 430.15 | 179.88 | 287.19 | 204.81 | 102.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 424.96 | 177.39 | 287.19 | 204.81 | 82.37 | 0.00 | 0.00 |
February | 391.51 | 154.82 | 260.46 | 168.59 | 91.87 | 0.00 | 0.00 |
March | 256.97 | 139.03 | 166.28 | 75.04 | 91.24 | 0.00 | 0.00 |
April | 209.19 | 93.78 | 123.25 | 28.88 | 94.37 | 0.00 | 0.00 |
May | 198.08 | 29.45 | 94.17 | 4.00 | 90.17 | 0.00 | 0.00 |
June | 200.87 | 27.03 | 93.02 | 0.87 | 92.16 | 0.00 | 0.00 |
July | 207.94 | 19.08 | 97.38 | 1.79 | 95.59 | 0.00 | 0.00 |
August | 246.69 | 27.70 | 114.56 | 13.75 | 100.81 | 0.00 | 0.00 |
September | 274.94 | 37.76 | 137.46 | 36.23 | 101.23 | 0.00 | 0.00 |
October | 393.17 | 63.51 | 213.27 | 111.09 | 102.17 | 0.00 | 0.00 |
November | 430.35 | 125.55 | 271.40 | 186.86 | 84.54 | 0.00 | 0.00 |
December | 428.46 | 161.27 | 280.62 | 201.52 | 79.09 | 0.00 | 0.00 |
Annual Sum or Average | 304.84 | 87.67 | 177.82 | 85.69 | 92.13 | 0.00 | 0.00 |
Minimum of Months | 198.08 | 19.08 | 93.02 | 0.87 | 79.09 | 0.00 | 0.00 |
Maximum of Months | 430.35 | 177.39 | 287.19 | 204.81 | 102.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 425.93 | 175.32 | 287.19 | 204.81 | 82.37 | 0.00 | 0.00 |
February | 392.38 | 153.00 | 260.46 | 168.59 | 91.87 | 0.00 | 0.00 |
March | 257.64 | 137.35 | 166.28 | 75.04 | 91.24 | 0.00 | 0.00 |
April | 209.57 | 92.66 | 123.25 | 28.88 | 94.37 | 0.00 | 0.00 |
May | 198.38 | 28.68 | 94.17 | 4.00 | 90.17 | 0.00 | 0.00 |
June | 201.15 | 26.29 | 93.02 | 0.87 | 92.16 | 0.00 | 0.00 |
July | 208.22 | 18.48 | 97.38 | 1.79 | 95.59 | 0.00 | 0.00 |
August | 246.92 | 26.99 | 114.56 | 13.75 | 100.81 | 0.00 | 0.00 |
September | 275.12 | 37.07 | 137.46 | 36.23 | 101.23 | 0.00 | 0.00 |
October | 393.37 | 62.74 | 213.27 | 111.09 | 102.17 | 0.00 | 0.00 |
November | 430.78 | 124.51 | 271.40 | 186.86 | 84.54 | 0.00 | 0.00 |
December | 429.09 | 159.68 | 280.62 | 201.52 | 79.09 | 0.00 | 0.00 |
Annual Sum or Average | 305.29 | 86.54 | 177.82 | 85.69 | 92.13 | 0.00 | 0.00 |
Minimum of Months | 198.38 | 18.48 | 93.02 | 0.87 | 79.09 | 0.00 | 0.00 |
Maximum of Months | 430.78 | 175.32 | 287.19 | 204.81 | 102.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 856.36 | 343.27 | 574.37 | 409.63 | 164.75 | 0.00 | 0.00 |
February | 789.25 | 299.07 | 520.92 | 337.19 | 183.74 | 0.00 | 0.00 |
March | 518.69 | 267.72 | 332.57 | 150.09 | 182.48 | 0.00 | 0.00 |
April | 420.95 | 179.90 | 246.50 | 57.76 | 188.74 | 0.00 | 0.00 |
May | 396.10 | 53.06 | 188.34 | 8.00 | 180.34 | 0.00 | 0.00 |
June | 401.11 | 47.95 | 186.05 | 1.73 | 184.31 | 0.00 | 0.00 |
July | 415.31 | 33.72 | 194.76 | 3.58 | 191.18 | 0.00 | 0.00 |
August | 492.78 | 49.65 | 229.13 | 27.50 | 201.63 | 0.00 | 0.00 |
September | 548.69 | 69.92 | 274.92 | 72.45 | 202.46 | 0.00 | 0.00 |
October | 786.61 | 121.13 | 426.53 | 222.18 | 204.35 | 0.00 | 0.00 |
November | 863.49 | 244.20 | 542.79 | 373.72 | 169.07 | 0.00 | 0.00 |
December | 861.28 | 313.03 | 561.23 | 403.05 | 158.19 | 0.00 | 0.00 |
Annual Sum or Average | 611.69 | 167.84 | 355.64 | 171.39 | 184.25 | 0.00 | 0.00 |
Minimum of Months | 396.10 | 33.72 | 186.05 | 1.73 | 158.19 | 0.00 | 0.00 |
Maximum of Months | 863.49 | 343.27 | 574.37 | 409.63 | 204.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 427.40 | 171.41 | 287.19 | 204.81 | 82.37 | 0.00 | 0.00 |
February | 393.94 | 149.20 | 260.46 | 168.59 | 91.87 | 0.00 | 0.00 |
March | 258.87 | 133.58 | 166.28 | 75.04 | 91.24 | 0.00 | 0.00 |
April | 210.35 | 89.36 | 123.25 | 28.88 | 94.37 | 0.00 | 0.00 |
May | 198.67 | 25.58 | 94.17 | 4.00 | 90.17 | 0.00 | 0.00 |
June | 201.36 | 22.98 | 93.02 | 0.87 | 92.16 | 0.00 | 0.00 |
July | 208.62 | 15.92 | 97.38 | 1.79 | 95.59 | 0.00 | 0.00 |
August | 247.09 | 23.74 | 114.56 | 13.75 | 100.81 | 0.00 | 0.00 |
September | 274.69 | 33.84 | 137.46 | 36.23 | 101.23 | 0.00 | 0.00 |
October | 393.25 | 59.57 | 213.27 | 111.09 | 102.17 | 0.00 | 0.00 |
November | 431.23 | 121.58 | 271.40 | 186.86 | 84.54 | 0.00 | 0.00 |
December | 429.94 | 156.23 | 280.62 | 201.52 | 79.09 | 0.00 | 0.00 |
Annual Sum or Average | 305.86 | 83.23 | 177.82 | 85.69 | 92.13 | 0.00 | 0.00 |
Minimum of Months | 198.67 | 15.92 | 93.02 | 0.87 | 79.09 | 0.00 | 0.00 |
Maximum of Months | 431.23 | 171.41 | 287.19 | 204.81 | 102.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 427.93 | 170.46 | 287.19 | 204.81 | 82.37 | 0.00 | 0.00 |
February | 394.49 | 148.28 | 260.46 | 168.59 | 91.87 | 0.00 | 0.00 |
March | 259.29 | 132.74 | 166.28 | 75.04 | 91.24 | 0.00 | 0.00 |
April | 210.61 | 88.88 | 123.25 | 28.88 | 94.37 | 0.00 | 0.00 |
May | 198.90 | 25.31 | 94.17 | 4.00 | 90.17 | 0.00 | 0.00 |
June | 201.57 | 22.73 | 93.02 | 0.87 | 92.16 | 0.00 | 0.00 |
July | 208.83 | 15.72 | 97.38 | 1.79 | 95.59 | 0.00 | 0.00 |
August | 247.26 | 23.53 | 114.56 | 13.75 | 100.81 | 0.00 | 0.00 |
September | 274.84 | 33.60 | 137.46 | 36.23 | 101.23 | 0.00 | 0.00 |
October | 393.43 | 59.26 | 213.27 | 111.09 | 102.17 | 0.00 | 0.00 |
November | 431.50 | 121.12 | 271.40 | 186.86 | 84.54 | 0.00 | 0.00 |
December | 430.33 | 155.44 | 280.62 | 201.52 | 79.09 | 0.00 | 0.00 |
Annual Sum or Average | 306.15 | 82.73 | 177.82 | 85.69 | 92.13 | 0.00 | 0.00 |
Minimum of Months | 198.90 | 15.72 | 93.02 | 0.87 | 79.09 | 0.00 | 0.00 |
Maximum of Months | 431.50 | 170.46 | 287.19 | 204.81 | 102.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 429.23 | 167.88 | 287.19 | 204.81 | 82.37 | 0.00 | 0.00 |
February | 395.86 | 145.64 | 260.46 | 168.59 | 91.87 | 0.00 | 0.00 |
March | 260.31 | 130.21 | 166.28 | 75.04 | 91.24 | 0.00 | 0.00 |
April | 211.17 | 87.44 | 123.25 | 28.88 | 94.37 | 0.00 | 0.00 |
May | 199.08 | 24.90 | 94.17 | 4.00 | 90.17 | 0.00 | 0.00 |
June | 201.63 | 22.49 | 93.02 | 0.87 | 92.16 | 0.00 | 0.00 |
July | 208.71 | 15.69 | 97.38 | 1.79 | 95.59 | 0.00 | 0.00 |
August | 247.08 | 23.61 | 114.56 | 13.75 | 100.81 | 0.00 | 0.00 |
September | 274.74 | 33.55 | 137.46 | 36.23 | 101.23 | 0.00 | 0.00 |
October | 393.49 | 58.92 | 213.27 | 111.09 | 102.17 | 0.00 | 0.00 |
November | 432.11 | 119.92 | 271.40 | 186.86 | 84.54 | 0.00 | 0.00 |
December | 431.32 | 153.20 | 280.62 | 201.52 | 79.09 | 0.00 | 0.00 |
Annual Sum or Average | 306.63 | 81.61 | 177.82 | 85.69 | 92.13 | 0.00 | 0.00 |
Minimum of Months | 199.08 | 15.69 | 93.02 | 0.87 | 79.09 | 0.00 | 0.00 |
Maximum of Months | 432.11 | 167.88 | 287.19 | 204.81 | 102.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 431.51 | 159.53 | 287.19 | 204.81 | 82.37 | 0.00 | 0.00 |
February | 398.47 | 136.95 | 260.46 | 168.59 | 91.87 | 0.00 | 0.00 |
March | 261.80 | 121.46 | 166.28 | 75.04 | 91.24 | 0.00 | 0.00 |
April | 211.70 | 82.11 | 123.25 | 28.88 | 94.37 | 0.00 | 0.00 |
May | 197.59 | 24.04 | 94.17 | 4.00 | 90.17 | 0.00 | 0.00 |
June | 199.41 | 22.37 | 93.02 | 0.87 | 92.16 | 0.00 | 0.00 |
July | 205.61 | 16.50 | 97.38 | 1.79 | 95.59 | 0.00 | 0.00 |
August | 243.82 | 25.18 | 114.56 | 13.75 | 100.81 | 0.00 | 0.00 |
September | 272.15 | 34.57 | 137.46 | 36.23 | 101.23 | 0.00 | 0.00 |
October | 391.80 | 58.57 | 213.27 | 111.09 | 102.17 | 0.00 | 0.00 |
November | 432.74 | 115.93 | 271.40 | 186.86 | 84.54 | 0.00 | 0.00 |
December | 433.21 | 145.79 | 280.62 | 201.52 | 79.09 | 0.00 | 0.00 |
Annual Sum or Average | 306.20 | 78.27 | 177.82 | 85.69 | 92.13 | 0.00 | 0.00 |
Minimum of Months | 197.59 | 16.50 | 93.02 | 0.87 | 79.09 | 0.00 | 0.00 |
Maximum of Months | 433.21 | 159.53 | 287.19 | 204.81 | 102.17 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.229116E+10 | 0.936439E+09 | 0.154157E+10 | 0.109940E+10 | 0.442162E+09 | 0.00 | 0.00 |
February | 0.190630E+10 | 0.736854E+09 | 0.126281E+10 | 0.817396E+09 | 0.445415E+09 | 0.00 | 0.00 |
March | 0.138860E+10 | 0.723127E+09 | 0.892585E+09 | 0.402825E+09 | 0.489760E+09 | 0.00 | 0.00 |
April | 0.109337E+10 | 0.461280E+09 | 0.640232E+09 | 0.150022E+09 | 0.490210E+09 | 0.00 | 0.00 |
May | 0.107357E+10 | 0.123591E+09 | 0.505490E+09 | 21482596.50 | 0.484007E+09 | 0.00 | 0.00 |
June | 0.105178E+10 | 0.104893E+09 | 0.483230E+09 | 4504165.10 | 0.478725E+09 | 0.00 | 0.00 |
July | 0.113702E+10 | 72298846.18 | 0.522725E+09 | 9607631.05 | 0.513117E+09 | 0.00 | 0.00 |
August | 0.133335E+10 | 0.116980E+09 | 0.614958E+09 | 73813531.21 | 0.541145E+09 | 0.00 | 0.00 |
September | 0.143521E+10 | 0.160480E+09 | 0.714045E+09 | 0.188181E+09 | 0.525864E+09 | 0.00 | 0.00 |
October | 0.211641E+10 | 0.302498E+09 | 0.114478E+10 | 0.596320E+09 | 0.548456E+09 | 0.00 | 0.00 |
November | 0.224131E+10 | 0.630647E+09 | 0.140981E+10 | 0.970667E+09 | 0.439140E+09 | 0.00 | 0.00 |
December | 0.230698E+10 | 0.847332E+09 | 0.150630E+10 | 0.108174E+10 | 0.424555E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.193751E+11 | 0.521642E+10 | 0.112385E+11 | 0.541597E+10 | 0.582256E+10 | 0.00 | 0.00 |
Minimum of Months | 0.105178E+10 | 72298846.18 | 0.483230E+09 | 4504165.10 | 0.424555E+09 | 0.00 | 0.00 |
Maximum of Months | 0.230698E+10 | 0.936439E+09 | 0.154157E+10 | 0.109940E+10 | 0.548456E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.113298E+10 | 0.492768E+09 | 0.770783E+09 | 0.549702E+09 | 0.221081E+09 | 0.00 | 0.00 |
February | 0.944064E+09 | 0.384732E+09 | 0.631406E+09 | 0.408698E+09 | 0.222707E+09 | 0.00 | 0.00 |
March | 0.686709E+09 | 0.378848E+09 | 0.446293E+09 | 0.201412E+09 | 0.244880E+09 | 0.00 | 0.00 |
April | 0.543910E+09 | 0.235598E+09 | 0.320116E+09 | 75011096.64 | 0.245105E+09 | 0.00 | 0.00 |
May | 0.537918E+09 | 62820400.43 | 0.252745E+09 | 10741298.25 | 0.242003E+09 | 0.00 | 0.00 |
June | 0.528402E+09 | 52766998.84 | 0.241615E+09 | 2252082.55 | 0.239363E+09 | 0.00 | 0.00 |
July | 0.572166E+09 | 35838044.49 | 0.261363E+09 | 4803815.53 | 0.256559E+09 | 0.00 | 0.00 |
August | 0.670928E+09 | 56919344.26 | 0.307479E+09 | 36906765.60 | 0.270572E+09 | 0.00 | 0.00 |
September | 0.720105E+09 | 78938288.35 | 0.357023E+09 | 94090626.76 | 0.262932E+09 | 0.00 | 0.00 |
October | 0.105885E+10 | 0.151090E+09 | 0.572388E+09 | 0.298160E+09 | 0.274228E+09 | 0.00 | 0.00 |
November | 0.111643E+10 | 0.319844E+09 | 0.704904E+09 | 0.485334E+09 | 0.219570E+09 | 0.00 | 0.00 |
December | 0.114580E+10 | 0.439038E+09 | 0.753148E+09 | 0.540871E+09 | 0.212277E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.965826E+10 | 0.268920E+10 | 0.561926E+10 | 0.270798E+10 | 0.291128E+10 | 0.00 | 0.00 |
Minimum of Months | 0.528402E+09 | 35838044.49 | 0.241615E+09 | 2252082.55 | 0.212277E+09 | 0.00 | 0.00 |
Maximum of Months | 0.114580E+10 | 0.492768E+09 | 0.770783E+09 | 0.549702E+09 | 0.274228E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.113558E+10 | 0.481799E+09 | 0.769201E+09 | 0.548574E+09 | 0.220627E+09 | 0.00 | 0.00 |
February | 0.945266E+09 | 0.379256E+09 | 0.630110E+09 | 0.407860E+09 | 0.222251E+09 | 0.00 | 0.00 |
March | 0.686954E+09 | 0.376354E+09 | 0.445377E+09 | 0.200999E+09 | 0.244378E+09 | 0.00 | 0.00 |
April | 0.541904E+09 | 0.244078E+09 | 0.319459E+09 | 74857213.05 | 0.244602E+09 | 0.00 | 0.00 |
May | 0.530927E+09 | 77615706.67 | 0.252226E+09 | 10719262.72 | 0.241507E+09 | 0.00 | 0.00 |
June | 0.521152E+09 | 68501045.01 | 0.241119E+09 | 2247462.45 | 0.238872E+09 | 0.00 | 0.00 |
July | 0.557856E+09 | 49239586.52 | 0.260826E+09 | 4793960.61 | 0.256032E+09 | 0.00 | 0.00 |
August | 0.661303E+09 | 72367279.41 | 0.306848E+09 | 36831052.20 | 0.270017E+09 | 0.00 | 0.00 |
September | 0.713182E+09 | 96223859.27 | 0.356290E+09 | 93897601.94 | 0.262393E+09 | 0.00 | 0.00 |
October | 0.105337E+10 | 0.168755E+09 | 0.571214E+09 | 0.297548E+09 | 0.273665E+09 | 0.00 | 0.00 |
November | 0.111495E+10 | 0.326841E+09 | 0.703458E+09 | 0.484338E+09 | 0.219120E+09 | 0.00 | 0.00 |
December | 0.114615E+10 | 0.436189E+09 | 0.751603E+09 | 0.539761E+09 | 0.211842E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.960859E+10 | 0.277722E+10 | 0.560773E+10 | 0.270243E+10 | 0.290531E+10 | 0.00 | 0.00 |
Minimum of Months | 0.521152E+09 | 49239586.52 | 0.241119E+09 | 2247462.45 | 0.211842E+09 | 0.00 | 0.00 |
Maximum of Months | 0.114615E+10 | 0.481799E+09 | 0.769201E+09 | 0.548574E+09 | 0.273665E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.113822E+10 | 0.475110E+09 | 0.769201E+09 | 0.548574E+09 | 0.220627E+09 | 0.00 | 0.00 |
February | 0.947134E+09 | 0.374549E+09 | 0.630110E+09 | 0.407860E+09 | 0.222251E+09 | 0.00 | 0.00 |
March | 0.688277E+09 | 0.372370E+09 | 0.445377E+09 | 0.200999E+09 | 0.244378E+09 | 0.00 | 0.00 |
April | 0.542217E+09 | 0.243066E+09 | 0.319459E+09 | 74857213.05 | 0.244602E+09 | 0.00 | 0.00 |
May | 0.530549E+09 | 78869621.01 | 0.252226E+09 | 10719262.72 | 0.241507E+09 | 0.00 | 0.00 |
June | 0.520650E+09 | 70056047.76 | 0.241119E+09 | 2247462.45 | 0.238872E+09 | 0.00 | 0.00 |
July | 0.556955E+09 | 51102881.81 | 0.260826E+09 | 4793960.61 | 0.256032E+09 | 0.00 | 0.00 |
August | 0.660739E+09 | 74192850.13 | 0.306848E+09 | 36831052.20 | 0.270017E+09 | 0.00 | 0.00 |
September | 0.712639E+09 | 97872442.36 | 0.356290E+09 | 93897601.94 | 0.262393E+09 | 0.00 | 0.00 |
October | 0.105308E+10 | 0.170104E+09 | 0.571214E+09 | 0.297548E+09 | 0.273665E+09 | 0.00 | 0.00 |
November | 0.111548E+10 | 0.325429E+09 | 0.703458E+09 | 0.484338E+09 | 0.219120E+09 | 0.00 | 0.00 |
December | 0.114759E+10 | 0.431936E+09 | 0.751603E+09 | 0.539761E+09 | 0.211842E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.961352E+10 | 0.276466E+10 | 0.560773E+10 | 0.270243E+10 | 0.290531E+10 | 0.00 | 0.00 |
Minimum of Months | 0.520650E+09 | 51102881.81 | 0.241119E+09 | 2247462.45 | 0.211842E+09 | 0.00 | 0.00 |
Maximum of Months | 0.114759E+10 | 0.475110E+09 | 0.769201E+09 | 0.548574E+09 | 0.273665E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.114081E+10 | 0.469583E+09 | 0.769201E+09 | 0.548574E+09 | 0.220627E+09 | 0.00 | 0.00 |
February | 0.949252E+09 | 0.370143E+09 | 0.630110E+09 | 0.407860E+09 | 0.222251E+09 | 0.00 | 0.00 |
March | 0.690076E+09 | 0.367875E+09 | 0.445377E+09 | 0.200999E+09 | 0.244378E+09 | 0.00 | 0.00 |
April | 0.543199E+09 | 0.240182E+09 | 0.319459E+09 | 74857213.05 | 0.244602E+09 | 0.00 | 0.00 |
May | 0.531336E+09 | 76812102.22 | 0.252226E+09 | 10719262.72 | 0.241507E+09 | 0.00 | 0.00 |
June | 0.521380E+09 | 68131392.83 | 0.241119E+09 | 2247462.45 | 0.238872E+09 | 0.00 | 0.00 |
July | 0.557693E+09 | 49489696.96 | 0.260826E+09 | 4793960.61 | 0.256032E+09 | 0.00 | 0.00 |
August | 0.661351E+09 | 72283909.67 | 0.306848E+09 | 36831052.20 | 0.270017E+09 | 0.00 | 0.00 |
September | 0.713110E+09 | 96078420.01 | 0.356290E+09 | 93897601.94 | 0.262393E+09 | 0.00 | 0.00 |
October | 0.105360E+10 | 0.168045E+09 | 0.571214E+09 | 0.297548E+09 | 0.273665E+09 | 0.00 | 0.00 |
November | 0.111657E+10 | 0.322735E+09 | 0.703458E+09 | 0.484338E+09 | 0.219120E+09 | 0.00 | 0.00 |
December | 0.114928E+10 | 0.427683E+09 | 0.751603E+09 | 0.539761E+09 | 0.211842E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.962765E+10 | 0.272904E+10 | 0.560773E+10 | 0.270243E+10 | 0.290531E+10 | 0.00 | 0.00 |
Minimum of Months | 0.521380E+09 | 49489696.96 | 0.241119E+09 | 2247462.45 | 0.211842E+09 | 0.00 | 0.00 |
Maximum of Months | 0.114928E+10 | 0.469583E+09 | 0.769201E+09 | 0.548574E+09 | 0.273665E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.229369E+10 | 0.919411E+09 | 0.153840E+10 | 0.109715E+10 | 0.441255E+09 | 0.00 | 0.00 |
February | 0.190936E+10 | 0.723510E+09 | 0.126022E+10 | 0.815720E+09 | 0.444501E+09 | 0.00 | 0.00 |
March | 0.138926E+10 | 0.717049E+09 | 0.890754E+09 | 0.401998E+09 | 0.488756E+09 | 0.00 | 0.00 |
April | 0.109111E+10 | 0.466303E+09 | 0.638919E+09 | 0.149714E+09 | 0.489204E+09 | 0.00 | 0.00 |
May | 0.106090E+10 | 0.142113E+09 | 0.504453E+09 | 21438525.43 | 0.483014E+09 | 0.00 | 0.00 |
June | 0.103969E+10 | 0.124292E+09 | 0.482238E+09 | 4494924.91 | 0.477743E+09 | 0.00 | 0.00 |
July | 0.111237E+10 | 90308467.94 | 0.521653E+09 | 9587921.21 | 0.512065E+09 | 0.00 | 0.00 |
August | 0.131985E+10 | 0.132985E+09 | 0.613697E+09 | 73662104.40 | 0.540035E+09 | 0.00 | 0.00 |
September | 0.142221E+10 | 0.181233E+09 | 0.712581E+09 | 0.187795E+09 | 0.524785E+09 | 0.00 | 0.00 |
October | 0.210686E+10 | 0.324431E+09 | 0.114243E+10 | 0.595097E+09 | 0.547331E+09 | 0.00 | 0.00 |
November | 0.223817E+10 | 0.632958E+09 | 0.140692E+10 | 0.968676E+09 | 0.438239E+09 | 0.00 | 0.00 |
December | 0.230686E+10 | 0.838407E+09 | 0.150321E+10 | 0.107952E+10 | 0.423684E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.192903E+11 | 0.529300E+10 | 0.112155E+11 | 0.540485E+10 | 0.581061E+10 | 0.00 | 0.00 |
Minimum of Months | 0.103969E+10 | 90308467.94 | 0.482238E+09 | 4494924.91 | 0.423684E+09 | 0.00 | 0.00 |
Maximum of Months | 0.230686E+10 | 0.919411E+09 | 0.153840E+10 | 0.109715E+10 | 0.547331E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.114474E+10 | 0.459095E+09 | 0.769201E+09 | 0.548574E+09 | 0.220627E+09 | 0.00 | 0.00 |
February | 0.953030E+09 | 0.360941E+09 | 0.630110E+09 | 0.407860E+09 | 0.222251E+09 | 0.00 | 0.00 |
March | 0.693358E+09 | 0.357773E+09 | 0.445377E+09 | 0.200999E+09 | 0.244378E+09 | 0.00 | 0.00 |
April | 0.545235E+09 | 0.231618E+09 | 0.319459E+09 | 74857213.05 | 0.244602E+09 | 0.00 | 0.00 |
May | 0.532129E+09 | 68523161.41 | 0.252226E+09 | 10719262.72 | 0.241507E+09 | 0.00 | 0.00 |
June | 0.521923E+09 | 59566323.28 | 0.241119E+09 | 2247462.45 | 0.238872E+09 | 0.00 | 0.00 |
July | 0.558765E+09 | 42634032.25 | 0.260826E+09 | 4793960.61 | 0.256032E+09 | 0.00 | 0.00 |
August | 0.661809E+09 | 63586236.68 | 0.306848E+09 | 36831052.20 | 0.270017E+09 | 0.00 | 0.00 |
September | 0.711985E+09 | 87715636.02 | 0.356290E+09 | 93897601.94 | 0.262393E+09 | 0.00 | 0.00 |
October | 0.105329E+10 | 0.159557E+09 | 0.571214E+09 | 0.297548E+09 | 0.273665E+09 | 0.00 | 0.00 |
November | 0.111774E+10 | 0.315144E+09 | 0.703458E+09 | 0.484338E+09 | 0.219120E+09 | 0.00 | 0.00 |
December | 0.115156E+10 | 0.418459E+09 | 0.751603E+09 | 0.539761E+09 | 0.211842E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.964556E+10 | 0.262461E+10 | 0.560773E+10 | 0.270243E+10 | 0.290531E+10 | 0.00 | 0.00 |
Minimum of Months | 0.521923E+09 | 42634032.25 | 0.241119E+09 | 2247462.45 | 0.211842E+09 | 0.00 | 0.00 |
Maximum of Months | 0.115156E+10 | 0.459095E+09 | 0.769201E+09 | 0.548574E+09 | 0.273665E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.114616E+10 | 0.456555E+09 | 0.769201E+09 | 0.548574E+09 | 0.220627E+09 | 0.00 | 0.00 |
February | 0.954342E+09 | 0.358715E+09 | 0.630110E+09 | 0.407860E+09 | 0.222251E+09 | 0.00 | 0.00 |
March | 0.694472E+09 | 0.355521E+09 | 0.445377E+09 | 0.200999E+09 | 0.244378E+09 | 0.00 | 0.00 |
April | 0.545889E+09 | 0.230372E+09 | 0.319459E+09 | 74857213.05 | 0.244602E+09 | 0.00 | 0.00 |
May | 0.532735E+09 | 67786645.04 | 0.252226E+09 | 10719262.72 | 0.241507E+09 | 0.00 | 0.00 |
June | 0.522482E+09 | 58922553.05 | 0.241119E+09 | 2247462.45 | 0.238872E+09 | 0.00 | 0.00 |
July | 0.559335E+09 | 42104621.75 | 0.260826E+09 | 4793960.61 | 0.256032E+09 | 0.00 | 0.00 |
August | 0.662275E+09 | 63025463.80 | 0.306848E+09 | 36831052.20 | 0.270017E+09 | 0.00 | 0.00 |
September | 0.712391E+09 | 87093631.86 | 0.356290E+09 | 93897601.94 | 0.262393E+09 | 0.00 | 0.00 |
October | 0.105377E+10 | 0.158732E+09 | 0.571214E+09 | 0.297548E+09 | 0.273665E+09 | 0.00 | 0.00 |
November | 0.111844E+10 | 0.313936E+09 | 0.703458E+09 | 0.484338E+09 | 0.219120E+09 | 0.00 | 0.00 |
December | 0.115260E+10 | 0.416341E+09 | 0.751603E+09 | 0.539761E+09 | 0.211842E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.965489E+10 | 0.260910E+10 | 0.560773E+10 | 0.270243E+10 | 0.290531E+10 | 0.00 | 0.00 |
Minimum of Months | 0.522482E+09 | 42104621.75 | 0.241119E+09 | 2247462.45 | 0.211842E+09 | 0.00 | 0.00 |
Maximum of Months | 0.115260E+10 | 0.456555E+09 | 0.769201E+09 | 0.548574E+09 | 0.273665E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.114966E+10 | 0.449657E+09 | 0.769201E+09 | 0.548574E+09 | 0.220627E+09 | 0.00 | 0.00 |
February | 0.957665E+09 | 0.352343E+09 | 0.630110E+09 | 0.407860E+09 | 0.222251E+09 | 0.00 | 0.00 |
March | 0.697213E+09 | 0.348744E+09 | 0.445377E+09 | 0.200999E+09 | 0.244378E+09 | 0.00 | 0.00 |
April | 0.547350E+09 | 0.226654E+09 | 0.319459E+09 | 74857213.05 | 0.244602E+09 | 0.00 | 0.00 |
May | 0.533209E+09 | 66687353.44 | 0.252226E+09 | 10719262.72 | 0.241507E+09 | 0.00 | 0.00 |
June | 0.522615E+09 | 58299348.44 | 0.241119E+09 | 2247462.45 | 0.238872E+09 | 0.00 | 0.00 |
July | 0.559008E+09 | 42021342.02 | 0.260826E+09 | 4793960.61 | 0.256032E+09 | 0.00 | 0.00 |
August | 0.661779E+09 | 63225102.50 | 0.306848E+09 | 36831052.20 | 0.270017E+09 | 0.00 | 0.00 |
September | 0.712114E+09 | 86957903.75 | 0.356290E+09 | 93897601.94 | 0.262393E+09 | 0.00 | 0.00 |
October | 0.105393E+10 | 0.157817E+09 | 0.571214E+09 | 0.297548E+09 | 0.273665E+09 | 0.00 | 0.00 |
November | 0.112004E+10 | 0.310841E+09 | 0.703458E+09 | 0.484338E+09 | 0.219120E+09 | 0.00 | 0.00 |
December | 0.115526E+10 | 0.410339E+09 | 0.751603E+09 | 0.539761E+09 | 0.211842E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.966983E+10 | 0.257359E+10 | 0.560773E+10 | 0.270243E+10 | 0.290531E+10 | 0.00 | 0.00 |
Minimum of Months | 0.522615E+09 | 42021342.02 | 0.241119E+09 | 2247462.45 | 0.211842E+09 | 0.00 | 0.00 |
Maximum of Months | 0.115526E+10 | 0.449657E+09 | 0.769201E+09 | 0.548574E+09 | 0.273665E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.115576E+10 | 0.427272E+09 | 0.769201E+09 | 0.548574E+09 | 0.220627E+09 | 0.00 | 0.00 |
February | 0.963975E+09 | 0.331302E+09 | 0.630110E+09 | 0.407860E+09 | 0.222251E+09 | 0.00 | 0.00 |
March | 0.701194E+09 | 0.325307E+09 | 0.445377E+09 | 0.200999E+09 | 0.244378E+09 | 0.00 | 0.00 |
April | 0.548736E+09 | 0.212819E+09 | 0.319459E+09 | 74857213.05 | 0.244602E+09 | 0.00 | 0.00 |
May | 0.529220E+09 | 64397850.48 | 0.252226E+09 | 10719262.72 | 0.241507E+09 | 0.00 | 0.00 |
June | 0.516883E+09 | 57991766.51 | 0.241119E+09 | 2247462.45 | 0.238872E+09 | 0.00 | 0.00 |
July | 0.550697E+09 | 44202315.00 | 0.260826E+09 | 4793960.61 | 0.256032E+09 | 0.00 | 0.00 |
August | 0.653038E+09 | 67447154.42 | 0.306848E+09 | 36831052.20 | 0.270017E+09 | 0.00 | 0.00 |
September | 0.705417E+09 | 89608138.50 | 0.356290E+09 | 93897601.94 | 0.262393E+09 | 0.00 | 0.00 |
October | 0.104941E+10 | 0.156873E+09 | 0.571214E+09 | 0.297548E+09 | 0.273665E+09 | 0.00 | 0.00 |
November | 0.112167E+10 | 0.300502E+09 | 0.703458E+09 | 0.484338E+09 | 0.219120E+09 | 0.00 | 0.00 |
December | 0.116031E+10 | 0.390479E+09 | 0.751603E+09 | 0.539761E+09 | 0.211842E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.965631E+10 | 0.246820E+10 | 0.560773E+10 | 0.270243E+10 | 0.290531E+10 | 0.00 | 0.00 |
Minimum of Months | 0.516883E+09 | 44202315.00 | 0.241119E+09 | 2247462.45 | 0.211842E+09 | 0.00 | 0.00 |
Maximum of Months | 0.116031E+10 | 0.427272E+09 | 0.769201E+09 | 0.548574E+09 | 0.273665E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.57 | 11.02 | 8.64 | 3.24 | 3.13 | 48.31 | 209.17 | 0.01 |
February | 15.49 | 12.82 | 10.40 | 2.82 | 4.36 | 58.07 | 218.23 | 0.02 |
March | 17.07 | 13.58 | 10.72 | 3.68 | 7.24 | 76.61 | 186.08 | 0.03 |
April | 21.23 | 17.54 | 15.23 | 2.65 | 11.47 | 90.28 | 216.86 | 0.02 |
May | 26.90 | 22.82 | 21.10 | 3.11 | 19.64 | 106.10 | 173.47 | 0.04 |
June | 27.61 | 23.37 | 21.62 | 2.44 | 19.77 | 115.40 | 187.69 | 0.03 |
July | 27.94 | 24.58 | 23.34 | 2.53 | 20.70 | 123.49 | 154.05 | 0.05 |
August | 27.43 | 23.90 | 22.52 | 3.20 | 20.40 | 118.51 | 145.78 | 0.03 |
September | 26.23 | 23.37 | 22.24 | 3.39 | 19.02 | 101.73 | 135.58 | 0.05 |
October | 24.23 | 20.47 | 18.40 | 4.11 | 16.60 | 78.24 | 178.15 | 0.01 |
November | 18.91 | 15.31 | 12.62 | 2.63 | 7.99 | 49.56 | 205.43 | 0.01 |
December | 15.68 | 12.88 | 10.53 | 3.17 | 6.01 | 45.08 | 191.18 | 0.02 |
Annual Sum or Average | 21.89 | 18.50 | 16.48 | 3.09 | 13.08 | 84.44 | 183.16 | 0.03 |
Minimum of Months | 13.57 | 11.02 | 8.64 | 2.44 | 3.13 | 45.08 | 135.58 | 0.01 |
Maximum of Months | 27.94 | 24.58 | 23.34 | 4.11 | 20.70 | 123.49 | 218.23 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 27.00 | 02-JAN-14:00 | 18.67 | 14.00 | 1.50 | 17.75 | 146.50 | 0.00 |
February | 28.30 | 02-FEB-12:00 | 20.78 | 17.20 | 6.60 | 17.93 | 127.50 | 748.50 |
March | 30.00 | 26-MAR-13:00 | 19.88 | 14.40 | 3.00 | 19.52 | 288.50 | 548.00 |
April | 33.30 | 28-APR-14:00 | 23.06 | 18.80 | 4.10 | 23.15 | 150.50 | 762.50 |
May | 33.90 | 07-MAY-13:00 | 23.76 | 19.40 | 4.10 | 23.15 | 287.50 | 507.50 |
June | 35.00 | 14-JUN-13:00 | 23.95 | 19.40 | 2.10 | 24.16 | 194.50 | 712.50 |
July | 36.10 | 21-JUL-15:00 | 25.96 | 22.20 | 1.50 | 26.65 | 216.00 | 245.00 |
August | 36.30 | 30-AUG-15:00 | 23.74 | 18.50 | 2.40 | 25.33 | 116.00 | 698.50 |
September | 36.40 | 09-SEP-16:00 | 26.65 | 23.40 | 4.40 | 26.48 | 114.00 | 401.50 |
October | 34.00 | 05-OCT-14:00 | 24.05 | 20.00 | 2.60 | 29.55 | 169.50 | 606.00 |
November | 30.00 | 01-NOV-13:00 | 25.01 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 30.00 | 13-DEC-14:00 | 21.84 | 18.00 | 3.10 | 20.92 | 101.50 | 682.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 27.00 | 18.67 | 14.00 | 1.50 | 17.75 | 101.50 | 0.00 | |
Maximum of Months | 36.40 | 26.65 | 23.40 | 6.60 | 29.55 | 288.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.00 | 05-JAN-05:00 | -0.0 | -0.0 | 2.10 | -16.0 | 0.00 | 0.00 |
February | -3.4 | 05-FEB-07:10 | -5.4 | -9.4 | 4.68 | -21.3 | 0.00 | 0.00 |
March | 1.10 | 09-MAR-05:00 | -2.1 | -7.3 | 3.60 | -14.4 | 0.00 | 0.00 |
April | 8.30 | 11-APR-05:00 | 6.95 | 5.50 | 0.00 | -6.9 | 0.00 | 0.00 |
May | 21.10 | 07-MAY-00:00 | 19.58 | 18.90 | 0.00 | 11.46 | 0.00 | 0.00 |
June | 20.60 | 07-JUN-01:00 | 18.00 | 16.70 | 3.60 | 10.50 | 0.00 | 0.00 |
July | 22.20 | 11-JUL-19:00 | 21.37 | 21.10 | 2.10 | 20.22 | 0.00 | 0.00 |
August | 20.20 | 25-AUG-23:00 | 20.20 | 20.20 | 5.30 | 11.84 | 0.00 | 0.00 |
September | 19.20 | 07-SEP-17:00 | 19.20 | 19.20 | 2.50 | 16.85 | 35.00 | 7.00 |
October | 10.00 | 28-OCT-04:00 | 5.56 | 0.00 | 3.60 | -0.1 | 0.00 | 0.00 |
November | 7.20 | 12-NOV-07:49 | 4.12 | 0.18 | 4.60 | -9.0 | 36.00 | 517.00 |
December | 0.00 | 21-DEC-04:00 | -0.9 | -2.0 | 2.10 | -16.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.4 | -5.4 | -9.4 | 0.00 | -21.3 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 21.37 | 21.10 | 5.30 | 20.22 | 36.00 | 517.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 22.11 | 31-JAN-12:00 | 25.00 | 21.00 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 21.49 | 24-FEB-12:00 | 27.70 | 18.80 | 4.10 | 17.75 | 165.00 | 746.50 |
March | 22.77 | 30-MAR-12:00 | 29.40 | 20.00 | 2.50 | 27.14 | 340.00 | 0.00 |
April | 25.55 | 28-APR-15:00 | 32.20 | 23.30 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 25.84 | 27-MAY-13:00 | 31.70 | 23.90 | 3.10 | 22.13 | 168.50 | 735.50 |
June | 26.52 | 29-JUN-16:00 | 29.40 | 25.60 | 1.50 | 26.32 | 164.00 | 36.00 |
July | 27.17 | 22-JUL-10:00 | 32.20 | 25.60 | 2.10 | 21.96 | 191.00 | 719.50 |
August | 27.24 | 07-AUG-12:00 | 31.00 | 26.00 | 3.10 | 27.95 | 473.00 | 200.00 |
September | 27.79 | 10-SEP-12:00 | 35.00 | 25.50 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.18 | 07-OCT-07:00 | 29.00 | 28.00 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 25.01 | 01-NOV-13:00 | 30.00 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 24.12 | 12-DEC-13:00 | 27.00 | 23.00 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.49 | 25.00 | 18.80 | 1.50 | 17.75 | 95.00 | 0.00 | |
Maximum of Months | 28.18 | 35.00 | 28.00 | 5.70 | 27.95 | 473.00 | 746.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 31-JAN-12:00 | 25.00 | 22.11 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 20.20 | 02-FEB-22:00 | 21.50 | 20.56 | 4.80 | 14.65 | 0.00 | 0.00 |
March | 21.10 | 07-MAR-08:00 | 23.30 | 21.69 | 2.00 | 13.91 | 126.00 | 566.50 |
April | 23.30 | 28-APR-15:00 | 32.20 | 25.55 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 24.40 | 26-MAY-08:20 | 27.07 | 25.09 | 3.10 | 23.71 | 252.67 | 47.33 |
June | 25.60 | 29-JUN-14:00 | 27.20 | 26.00 | 5.10 | 24.16 | 335.00 | 238.00 |
July | 25.60 | 02-JUL-05:00 | 26.10 | 25.71 | 2.60 | 19.52 | 30.50 | 8.50 |
August | 26.60 | 09-AUG-18:00 | 26.60 | 26.60 | 1.90 | 19.52 | 26.00 | 23.00 |
September | 25.50 | 10-SEP-12:00 | 35.00 | 27.79 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.00 | 07-OCT-07:00 | 29.00 | 28.18 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 23.80 | 01-NOV-10:00 | 26.10 | 24.39 | 2.00 | 22.64 | 228.50 | 113.00 |
December | 23.00 | 12-DEC-13:00 | 27.00 | 24.12 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.20 | 21.50 | 20.56 | 1.90 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 28.00 | 35.00 | 28.18 | 5.70 | 24.66 | 336.50 | 662.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.46 | 29.60 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 20.78 | 36.65 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 22.23 | 38.94 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.49 | 49.11 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 26.95 | 46.95 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 28.93 | 51.71 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 29.89 | 48.43 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 29.58 | 45.50 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.08 | 39.22 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.80 | 37.51 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 23.35 | 31.26 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 21.40 | 27.18 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 25.18 | 40.17 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.46 | 27.18 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 29.89 | 51.71 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.306398E+09 | -189183906.4 | 0.00 | 0.00 | 744.00 | 0.00 | -117213650.8 | 58.99 | 0.00 | 0.00 |
February | 0.274938E+09 | -170364364.0 | 0.00 | 0.00 | 672.00 | 0.00 | -104573812.9 | 58.99 | 0.00 | 0.00 |
March | 0.299690E+09 | -184422964.1 | 0.00 | 0.00 | 744.00 | 0.00 | -115267366.6 | 58.99 | 0.00 | 0.00 |
April | 0.274528E+09 | -165334782.9 | 0.00 | 0.00 | 720.00 | 0.00 | -109192733.1 | 58.99 | 0.00 | 0.00 |
May | 0.270532E+09 | -158994544.6 | 0.00 | 0.00 | 744.00 | 0.00 | -111537066.7 | 58.99 | 0.00 | 0.00 |
June | 0.253585E+09 | -145802854.8 | 0.00 | 0.00 | 720.00 | 0.00 | -107782456.3 | 58.99 | 0.00 | 0.00 |
July | 0.253922E+09 | -142825189.9 | 0.00 | 0.00 | 744.00 | 0.00 | -111096488.3 | 58.99 | 0.00 | 0.00 |
August | 0.258454E+09 | -147445818.5 | 0.00 | 0.00 | 744.00 | 0.00 | -111008196.0 | 58.99 | 0.00 | 0.00 |
September | 0.255910E+09 | -148310209.0 | 0.00 | 0.00 | 720.00 | 0.00 | -107599673.9 | 58.99 | 0.00 | 0.00 |
October | 0.274596E+09 | -163009411.9 | 0.00 | 0.00 | 744.00 | 0.00 | -111586209.1 | 58.99 | 0.00 | 0.00 |
November | 0.278142E+09 | -168886555.6 | 0.00 | 0.00 | 720.00 | 0.00 | -109255845.3 | 58.99 | 0.00 | 0.00 |
December | 0.300102E+09 | -184813488.0 | 0.00 | 0.00 | 744.00 | 0.00 | -115288523.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.330080E+10 | -0.196939E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.133140E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.253585E+09 | -189183906.4 | 0.00 | 0.00 | 672.00 | 0.00 | -117213650.8 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.306398E+09 | -142825189.9 | 0.00 | 0.00 | 744.00 | 0.00 | -104573812.9 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.304537E+09 | -189189997.5 | 0.00 | 0.00 | 744.00 | 0.00 | -115346738.5 | 58.99 | 0.00 | 0.00 |
February | 0.273765E+09 | -170363436.6 | 0.00 | 0.00 | 672.00 | 0.00 | -103401958.7 | 58.99 | 0.00 | 0.00 |
March | 0.298559E+09 | -184435325.5 | 0.00 | 0.00 | 744.00 | 0.00 | -114123629.8 | 58.99 | 0.00 | 0.00 |
April | 0.274177E+09 | -165326911.5 | 0.00 | 0.00 | 720.00 | 0.00 | -108850445.7 | 58.99 | 0.00 | 0.00 |
May | 0.270385E+09 | -159016923.9 | 0.00 | 0.00 | 744.00 | 0.00 | -111368467.6 | 58.99 | 0.00 | 0.00 |
June | 0.253470E+09 | -145795380.6 | 0.00 | 0.00 | 720.00 | 0.00 | -107674448.6 | 58.99 | 0.00 | 0.00 |
July | 0.253875E+09 | -142825087.8 | 0.00 | 0.00 | 744.00 | 0.00 | -111050075.6 | 58.99 | 0.00 | 0.00 |
August | 0.258446E+09 | -147440183.3 | 0.00 | 0.00 | 744.00 | 0.00 | -111005825.4 | 58.99 | 0.00 | 0.00 |
September | 0.255877E+09 | -148293436.3 | 0.00 | 0.00 | 720.00 | 0.00 | -107583088.0 | 59.00 | 0.00 | 0.00 |
October | 0.274489E+09 | -163011346.7 | 0.00 | 0.00 | 744.00 | 0.00 | -111478099.5 | 58.99 | 0.00 | 0.00 |
November | 0.277765E+09 | -168885052.0 | 0.00 | 0.00 | 720.00 | 0.00 | -108879501.6 | 58.99 | 0.00 | 0.00 |
December | 0.298998E+09 | -184815231.4 | 0.00 | 0.00 | 744.00 | 0.00 | -114183115.8 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.329434E+10 | -0.196940E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.132495E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.253470E+09 | -189189997.5 | 0.00 | 0.00 | 672.00 | 0.00 | -115346738.5 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.304537E+09 | -142825087.8 | 0.00 | 0.00 | 744.00 | 0.00 | -103401958.7 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.282587E+09 | -166358546.2 | 0.00 | 0.00 | 744.00 | 0.00 | -116228839.7 | 58.99 | 0.00 | 0.00 |
February | 0.253735E+09 | -149937328.6 | 0.00 | 0.00 | 672.00 | 0.00 | -103798023.0 | 59.00 | 0.00 | 0.00 |
March | 0.278806E+09 | -164590989.9 | 0.00 | 0.00 | 744.00 | 0.00 | -114215089.1 | 58.99 | 0.00 | 0.00 |
April | 0.253363E+09 | -145410838.7 | 0.00 | 0.00 | 720.00 | 0.00 | -107952420.2 | 58.99 | 0.00 | 0.00 |
May | 0.250618E+09 | -141010802.6 | 0.00 | 0.00 | 744.00 | 0.00 | -109606780.8 | 59.00 | 0.00 | 0.00 |
June | 0.235637E+09 | -129836983.9 | 0.00 | 0.00 | 720.00 | 0.00 | -105800340.6 | 58.99 | 0.00 | 0.00 |
July | 0.233704E+09 | -124875849.8 | 0.00 | 0.00 | 744.00 | 0.00 | -108827728.5 | 58.99 | 0.00 | 0.00 |
August | 0.240705E+09 | -131667021.0 | 0.00 | 0.00 | 744.00 | 0.00 | -109037683.9 | 59.00 | 0.00 | 0.00 |
September | 0.236040E+09 | -130367410.6 | 0.00 | 0.00 | 720.00 | 0.00 | -105672862.7 | 58.99 | 0.00 | 0.00 |
October | 0.253072E+09 | -143398188.1 | 0.00 | 0.00 | 744.00 | 0.00 | -109673691.7 | 58.98 | 0.00 | 0.00 |
November | 0.257335E+09 | -149117186.7 | 0.00 | 0.00 | 720.00 | 0.00 | -108218045.0 | 58.99 | 0.00 | 0.00 |
December | 0.275678E+09 | -161327013.7 | 0.00 | 0.00 | 744.00 | 0.00 | -114350604.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.305128E+10 | -0.173790E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.131338E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.233704E+09 | -166358546.2 | 0.00 | 0.00 | 672.00 | 0.00 | -116228839.7 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.282587E+09 | -124875849.8 | 0.00 | 0.00 | 744.00 | 0.00 | -103798023.0 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.282988E+09 | -166346827.3 | 0.00 | 0.00 | 744.00 | 0.00 | -116641366.9 | 59.00 | 0.00 | 0.00 |
February | 0.254014E+09 | -149959519.5 | 0.00 | 0.00 | 672.00 | 0.00 | -104053987.9 | 58.99 | 0.00 | 0.00 |
March | 0.279023E+09 | -164590900.1 | 0.00 | 0.00 | 744.00 | 0.00 | -114432010.1 | 58.99 | 0.00 | 0.00 |
April | 0.253412E+09 | -145423874.2 | 0.00 | 0.00 | 720.00 | 0.00 | -107988287.7 | 58.99 | 0.00 | 0.00 |
May | 0.250536E+09 | -141050645.1 | 0.00 | 0.00 | 744.00 | 0.00 | -109485397.5 | 58.98 | 0.00 | 0.00 |
June | 0.235542E+09 | -129846207.2 | 0.00 | 0.00 | 720.00 | 0.00 | -105695434.1 | 58.99 | 0.00 | 0.00 |
July | 0.233597E+09 | -124879420.3 | 0.00 | 0.00 | 744.00 | 0.00 | -108717090.0 | 58.99 | 0.00 | 0.00 |
August | 0.240595E+09 | -131692367.3 | 0.00 | 0.00 | 744.00 | 0.00 | -108902915.8 | 58.99 | 0.00 | 0.00 |
September | 0.235937E+09 | -130377558.2 | 0.00 | 0.00 | 720.00 | 0.00 | -105559114.3 | 58.99 | 0.00 | 0.00 |
October | 0.253004E+09 | -143392413.9 | 0.00 | 0.00 | 744.00 | 0.00 | -109611145.1 | 58.99 | 0.00 | 0.00 |
November | 0.257414E+09 | -149104255.1 | 0.00 | 0.00 | 720.00 | 0.00 | -108309675.1 | 58.99 | 0.00 | 0.00 |
December | 0.275903E+09 | -161332036.6 | 0.00 | 0.00 | 744.00 | 0.00 | -114571139.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.305196E+10 | -0.173800E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.131397E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.233597E+09 | -166346827.3 | 0.00 | 0.00 | 672.00 | 0.00 | -116641366.9 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.282988E+09 | -124879420.3 | 0.00 | 0.00 | 744.00 | 0.00 | -104053987.9 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.274782E+09 | -157239053.4 | 0.00 | 0.00 | 744.00 | 0.00 | -117542733.2 | 58.99 | 0.00 | 0.00 |
February | 0.246641E+09 | -141815486.9 | 0.00 | 0.00 | 672.00 | 0.00 | -104825790.5 | 58.98 | 0.00 | 0.00 |
March | 0.270970E+09 | -155728216.6 | 0.00 | 0.00 | 744.00 | 0.00 | -115242178.3 | 59.00 | 0.00 | 0.00 |
April | 0.246195E+09 | -137617040.0 | 0.00 | 0.00 | 720.00 | 0.00 | -108577707.7 | 58.98 | 0.00 | 0.00 |
May | 0.243383E+09 | -133384331.9 | 0.00 | 0.00 | 744.00 | 0.00 | -109998622.1 | 58.99 | 0.00 | 0.00 |
June | 0.229088E+09 | -122865991.7 | 0.00 | 0.00 | 720.00 | 0.00 | -106221558.0 | 58.99 | 0.00 | 0.00 |
July | 0.227208E+09 | -118090160.3 | 0.00 | 0.00 | 744.00 | 0.00 | -109117776.3 | 58.99 | 0.00 | 0.00 |
August | 0.233991E+09 | -124607480.2 | 0.00 | 0.00 | 744.00 | 0.00 | -109383045.8 | 58.99 | 0.00 | 0.00 |
September | 0.229278E+09 | -123362438.0 | 0.00 | 0.00 | 720.00 | 0.00 | -105915519.4 | 59.00 | 0.00 | 0.00 |
October | 0.245579E+09 | -135529896.2 | 0.00 | 0.00 | 744.00 | 0.00 | -110049123.4 | 58.99 | 0.00 | 0.00 |
November | 0.249637E+09 | -140829718.9 | 0.00 | 0.00 | 720.00 | 0.00 | -108806872.4 | 58.99 | 0.00 | 0.00 |
December | 0.267860E+09 | -152571934.9 | 0.00 | 0.00 | 744.00 | 0.00 | -115288029.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.296461E+10 | -0.164364E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.132097E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.227208E+09 | -157239053.4 | 0.00 | 0.00 | 672.00 | 0.00 | -117542733.2 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.274782E+09 | -118090160.3 | 0.00 | 0.00 | 744.00 | 0.00 | -104825790.5 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.274859E+09 | -157241301.8 | 0.00 | 0.00 | 744.00 | 0.00 | -117617874.4 | 58.99 | 0.00 | 0.00 |
February | 0.246709E+09 | -141811772.1 | 0.00 | 0.00 | 672.00 | 0.00 | -104896771.8 | 58.99 | 0.00 | 0.00 |
March | 0.271014E+09 | -155732006.1 | 0.00 | 0.00 | 744.00 | 0.00 | -115282434.0 | 59.00 | 0.00 | 0.00 |
April | 0.246247E+09 | -137621481.5 | 0.00 | 0.00 | 720.00 | 0.00 | -108625774.9 | 58.98 | 0.00 | 0.00 |
May | 0.243495E+09 | -133398608.1 | 0.00 | 0.00 | 744.00 | 0.00 | -110096014.6 | 58.99 | 0.00 | 0.00 |
June | 0.229197E+09 | -122880243.9 | 0.00 | 0.00 | 720.00 | 0.00 | -106316601.9 | 58.99 | 0.00 | 0.00 |
July | 0.227337E+09 | -118104154.2 | 0.00 | 0.00 | 744.00 | 0.00 | -109232717.3 | 58.99 | 0.00 | 0.00 |
August | 0.234129E+09 | -124615836.9 | 0.00 | 0.00 | 744.00 | 0.00 | -109512695.1 | 58.99 | 0.00 | 0.00 |
September | 0.229388E+09 | -123380230.6 | 0.00 | 0.00 | 720.00 | 0.00 | -106008203.4 | 58.99 | 0.00 | 0.00 |
October | 0.245683E+09 | -135493628.1 | 0.00 | 0.00 | 744.00 | 0.00 | -110189238.1 | 59.00 | 0.00 | 0.00 |
November | 0.249694E+09 | -140803519.4 | 0.00 | 0.00 | 720.00 | 0.00 | -108890054.0 | 59.00 | 0.00 | 0.00 |
December | 0.267915E+09 | -152570104.8 | 0.00 | 0.00 | 744.00 | 0.00 | -115345179.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.296567E+10 | -0.164365E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.132201E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.227337E+09 | -157241301.8 | 0.00 | 0.00 | 672.00 | 0.00 | -117617874.4 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.274859E+09 | -118104154.2 | 0.00 | 0.00 | 744.00 | 0.00 | -104896771.8 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.275017E+09 | -157241253.6 | 0.00 | 0.00 | 744.00 | 0.00 | -117775646.3 | 58.99 | 0.00 | 0.00 |
February | 0.246859E+09 | -141801399.7 | 0.00 | 0.00 | 672.00 | 0.00 | -105057802.1 | 58.99 | 0.00 | 0.00 |
March | 0.271139E+09 | -155760535.2 | 0.00 | 0.00 | 744.00 | 0.00 | -115378168.2 | 58.98 | 0.00 | 0.00 |
April | 0.246322E+09 | -137579331.3 | 0.00 | 0.00 | 720.00 | 0.00 | -108742503.0 | 59.00 | 0.00 | 0.00 |
May | 0.243534E+09 | -133368774.1 | 0.00 | 0.00 | 744.00 | 0.00 | -110165564.0 | 58.99 | 0.00 | 0.00 |
June | 0.229239E+09 | -122848786.2 | 0.00 | 0.00 | 720.00 | 0.00 | -106389929.8 | 59.00 | 0.00 | 0.00 |
July | 0.227372E+09 | -118094368.5 | 0.00 | 0.00 | 744.00 | 0.00 | -109278032.3 | 58.99 | 0.00 | 0.00 |
August | 0.234158E+09 | -124600904.8 | 0.00 | 0.00 | 744.00 | 0.00 | -109557132.2 | 58.99 | 0.00 | 0.00 |
September | 0.229426E+09 | -123391106.7 | 0.00 | 0.00 | 720.00 | 0.00 | -106034839.4 | 58.99 | 0.00 | 0.00 |
October | 0.245726E+09 | -135509663.6 | 0.00 | 0.00 | 744.00 | 0.00 | -110216478.0 | 58.99 | 0.00 | 0.00 |
November | 0.249762E+09 | -140839862.3 | 0.00 | 0.00 | 720.00 | 0.00 | -108922612.6 | 58.99 | 0.00 | 0.00 |
December | 0.268044E+09 | -152566292.5 | 0.00 | 0.00 | 744.00 | 0.00 | -115477989.8 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.296660E+10 | -0.164360E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.132300E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.227372E+09 | -157241253.6 | 0.00 | 0.00 | 672.00 | 0.00 | -117775646.3 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.275017E+09 | -118094368.5 | 0.00 | 0.00 | 744.00 | 0.00 | -105057802.1 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 307.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 295.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 296.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 347.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 353.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 394.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 390.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 380.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 342.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 330.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 308.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 282.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4027.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 282.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 394.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.411446E+09 | 41956.86 | 10-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.629502E+09 | 59655.32 | 05-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.410742E+09 | 47637.01 | 11-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.450815E+09 | 59655.32 | 21-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.190251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.629502E+09 | 59655.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 42361135.75 | 4246.50 | 05-JAN-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126369E+09 | 13366.48 | 05-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.111514E+09 | 5175.08 | 11-MAR-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.104374E+09 | 12385.58 | 21-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.384618E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.126369E+09 | 13366.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.166185E+09 | 5279.48 | 04-JAN-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.227715E+09 | 21528.15 | 05-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.165535E+09 | 11843.09 | 12-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.183938E+09 | 6649.02 | 20-DEC-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.743372E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.227715E+09 | 21528.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.206225E+09 | 5702.44 | 04-JAN-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.252956E+09 | 24603.58 | 05-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.182757E+09 | 14978.89 | 12-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.203761E+09 | 7264.11 | 21-DEC-08:65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.845698E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.252956E+09 | 24603.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.254412E+09 | 7023.17 | 10-JAN-08:65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.284639E+09 | 27207.80 | 05-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.206050E+09 | 17581.53 | 12-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.234199E+09 | 8326.78 | 21-DEC-08:65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.979300E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.284639E+09 | 27207.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.434074E+09 | 49894.83 | 10-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.491110E+09 | 56689.66 | 05-FEB-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.339094E+09 | 56232.05 | 13-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.417614E+09 | 56689.66 | 21-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168189E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.491110E+09 | 56689.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.226250E+09 | 26433.63 | 10-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.265696E+09 | 29588.39 | 05-FEB-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.179348E+09 | 29120.15 | 13-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.223984E+09 | 29588.39 | 21-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.895278E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.265696E+09 | 29588.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.250712E+09 | 28395.09 | 10-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.280438E+09 | 29481.58 | 05-FEB-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189360E+09 | 29481.58 | 12-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.239016E+09 | 29481.58 | 21-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.959527E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.280438E+09 | 29481.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.325900E+09 | 29552.75 | 10-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.331396E+09 | 29552.75 | 05-FEB-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.228443E+09 | 29552.75 | 11-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.289370E+09 | 29552.75 | 21-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.117511E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.331396E+09 | 29552.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.517758E+09 | 33208.12 | 05-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.471298E+09 | 33208.12 | 05-FEB-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.367800E+09 | 33208.12 | 10-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.443144E+09 | 33208.12 | 20-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.180000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.517758E+09 | 33208.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.497072E+10 | 0.314604E+10 | 61142.61 | 19-JAN-09:02 | 33862.13 | 0.00 |
February | 0.00 | 0.00 | 0.647390E+10 | 0.408529E+10 | 59432.74 | 28-FEB-09:02 | 31166.21 | 0.00 |
March | 0.00 | 0.00 | 0.939166E+10 | 0.611992E+10 | 61442.57 | 07-MAR-09:02 | 34266.24 | 0.00 |
April | 0.00 | 0.00 | 0.173268E+11 | 0.114015E+11 | 62143.81 | 29-APR-08:62 | 33498.58 | 0.00 |
May | 0.00 | 0.00 | 0.380513E+11 | 0.232631E+11 | 63275.46 | 24-MAY-08:61 | 31501.53 | 0.00 |
June | 0.00 | 0.00 | 0.405312E+11 | 0.245781E+11 | 63122.86 | 19-JUN-08:61 | 32640.95 | 0.00 |
July | 0.00 | 0.00 | 0.460469E+11 | 0.259346E+11 | 63412.52 | 03-JUL-08:61 | 32209.12 | 0.00 |
August | 0.00 | 0.00 | 0.454217E+11 | 0.264869E+11 | 63453.58 | 07-AUG-08:61 | 32431.01 | 0.00 |
September | 0.00 | 0.00 | 0.403692E+11 | 0.228691E+11 | 63892.70 | 05-SEP-08:61 | 29555.63 | 0.00 |
October | 0.00 | 0.00 | 0.344510E+11 | 0.210009E+11 | 63904.39 | 06-OCT-08:61 | 30838.84 | 0.00 |
November | 0.00 | 0.00 | 0.137385E+11 | 0.869693E+10 | 61918.95 | 02-NOV-08:61 | 34682.40 | 0.00 |
December | 0.00 | 0.00 | 0.883462E+10 | 0.555492E+10 | 61735.76 | 15-DEC-09:02 | 33667.04 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.305608E+12 | 0.183137E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.497072E+10 | 0.314604E+10 | 59432.74 | 29555.63 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.460469E+11 | 0.264869E+11 | 63904.39 | 34682.40 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.291507E+10 | 0.189583E+10 | 31452.27 | 19-JAN-09:02 | 18350.72 | 0.00 |
February | 0.00 | 0.00 | 0.384954E+10 | 0.248165E+10 | 30553.12 | 28-FEB-21:20 | 14641.55 | 0.00 |
March | 0.00 | 0.00 | 0.541684E+10 | 0.363487E+10 | 30898.58 | 07-MAR-09:02 | 20542.14 | 0.00 |
April | 0.00 | 0.00 | 0.949752E+10 | 0.644483E+10 | 30983.08 | 29-APR-08:62 | 20741.53 | 0.00 |
May | 0.00 | 0.00 | 0.189045E+11 | 0.119481E+11 | 31661.92 | 24-MAY-08:61 | 19357.29 | 0.00 |
June | 0.00 | 0.00 | 0.199432E+11 | 0.124633E+11 | 31395.73 | 19-JUN-08:61 | 20273.25 | 0.00 |
July | 0.00 | 0.00 | 0.224306E+11 | 0.130651E+11 | 31793.07 | 03-JUL-08:61 | 19346.63 | 0.00 |
August | 0.00 | 0.00 | 0.220811E+11 | 0.132428E+11 | 31906.29 | 16-AUG-08:61 | 18754.10 | 0.00 |
September | 0.00 | 0.00 | 0.197428E+11 | 0.115487E+11 | 32175.26 | 05-SEP-08:61 | 17949.26 | 0.00 |
October | 0.00 | 0.00 | 0.171778E+11 | 0.108168E+11 | 31881.28 | 06-OCT-08:61 | 19139.55 | 0.00 |
November | 0.00 | 0.00 | 0.747997E+10 | 0.487329E+10 | 31065.65 | 02-NOV-08:61 | 20786.58 | 0.00 |
December | 0.00 | 0.00 | 0.473571E+10 | 0.307396E+10 | 30934.70 | 13-DEC-09:02 | 20280.91 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.154175E+12 | 0.954892E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.291507E+10 | 0.189583E+10 | 30553.12 | 14641.55 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.224306E+11 | 0.132428E+11 | 32175.26 | 20786.58 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.213275E+10 | 0.137028E+10 | 30414.82 | 19-JAN-08:62 | 14032.22 | 0.00 |
February | 0.00 | 0.00 | 0.292265E+10 | 0.185485E+10 | 30553.00 | 28-FEB-08:62 | 15755.03 | 0.00 |
March | 0.00 | 0.00 | 0.406676E+10 | 0.267187E+10 | 31322.10 | 07-MAR-08:62 | 15266.97 | 0.00 |
April | 0.00 | 0.00 | 0.717841E+10 | 0.479399E+10 | 32039.12 | 29-APR-07:02 | 17303.98 | 0.00 |
May | 0.00 | 0.00 | 0.154029E+11 | 0.944693E+10 | 32831.31 | 24-MAY-07:01 | 15625.36 | 0.00 |
June | 0.00 | 0.00 | 0.164932E+11 | 0.998196E+10 | 33139.15 | 19-JUN-07:01 | 14601.72 | 0.00 |
July | 0.00 | 0.00 | 0.182607E+11 | 0.102228E+11 | 33226.69 | 03-JUL-07:01 | 14764.09 | 0.00 |
August | 0.00 | 0.00 | 0.183657E+11 | 0.106180E+11 | 33191.06 | 14-AUG-07:02 | 14176.68 | 0.00 |
September | 0.00 | 0.00 | 0.159698E+11 | 0.894110E+10 | 33212.74 | 05-SEP-07:01 | 14413.53 | 0.00 |
October | 0.00 | 0.00 | 0.136724E+11 | 0.831173E+10 | 33147.36 | 25-OCT-07:01 | 14873.30 | 0.00 |
November | 0.00 | 0.00 | 0.581513E+10 | 0.371685E+10 | 32137.26 | 02-NOV-07:01 | 17051.39 | 0.00 |
December | 0.00 | 0.00 | 0.371310E+10 | 0.234875E+10 | 31782.62 | 16-DEC-08:62 | 17443.95 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.123994E+12 | 0.742791E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.213275E+10 | 0.137028E+10 | 30414.82 | 14032.22 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.183657E+11 | 0.106180E+11 | 33226.69 | 17443.95 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.206553E+10 | 0.132276E+10 | 30255.63 | 20-JAN-08:62 | 14109.11 | 0.00 |
February | 0.00 | 0.00 | 0.285297E+10 | 0.180664E+10 | 30634.95 | 28-FEB-08:62 | 15785.77 | 0.00 |
March | 0.00 | 0.00 | 0.400417E+10 | 0.262419E+10 | 31405.77 | 07-MAR-08:62 | 15291.54 | 0.00 |
April | 0.00 | 0.00 | 0.714186E+10 | 0.476543E+10 | 32127.58 | 29-APR-07:02 | 17354.51 | 0.00 |
May | 0.00 | 0.00 | 0.154440E+11 | 0.947682E+10 | 32921.99 | 24-MAY-07:01 | 15677.94 | 0.00 |
June | 0.00 | 0.00 | 0.165496E+11 | 0.100234E+11 | 33228.24 | 19-JUN-07:03 | 14568.85 | 0.00 |
July | 0.00 | 0.00 | 0.183452E+11 | 0.102834E+11 | 33309.13 | 31-JUL-07:01 | 14668.88 | 0.00 |
August | 0.00 | 0.00 | 0.184346E+11 | 0.106680E+11 | 33280.28 | 14-AUG-07:01 | 14478.86 | 0.00 |
September | 0.00 | 0.00 | 0.160373E+11 | 0.898874E+10 | 33259.38 | 05-SEP-07:01 | 14583.70 | 0.00 |
October | 0.00 | 0.00 | 0.137149E+11 | 0.834332E+10 | 33223.94 | 25-OCT-07:01 | 14951.84 | 0.00 |
November | 0.00 | 0.00 | 0.576603E+10 | 0.367992E+10 | 32226.02 | 02-NOV-07:01 | 17095.29 | 0.00 |
December | 0.00 | 0.00 | 0.367313E+10 | 0.231856E+10 | 31856.22 | 16-DEC-08:62 | 13959.57 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.124029E+12 | 0.743013E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.206553E+10 | 0.132276E+10 | 30255.63 | 13959.57 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.184346E+11 | 0.106680E+11 | 33309.13 | 17354.51 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.196277E+10 | 0.125159E+10 | 30146.42 | 20-JAN-08:62 | 14016.59 | 0.00 |
February | 0.00 | 0.00 | 0.273013E+10 | 0.172238E+10 | 30525.45 | 28-FEB-08:62 | 15688.09 | 0.00 |
March | 0.00 | 0.00 | 0.385247E+10 | 0.251499E+10 | 31292.99 | 07-MAR-08:62 | 15191.32 | 0.00 |
April | 0.00 | 0.00 | 0.694487E+10 | 0.462494E+10 | 32008.78 | 29-APR-07:02 | 17174.13 | 0.00 |
May | 0.00 | 0.00 | 0.152640E+11 | 0.934713E+10 | 32800.43 | 24-MAY-07:01 | 15511.43 | 0.00 |
June | 0.00 | 0.00 | 0.163820E+11 | 0.990073E+10 | 33112.22 | 19-JUN-07:01 | 14582.37 | 0.00 |
July | 0.00 | 0.00 | 0.181882E+11 | 0.101726E+11 | 33192.83 | 31-JUL-07:01 | 14562.17 | 0.00 |
August | 0.00 | 0.00 | 0.182682E+11 | 0.105485E+11 | 33164.08 | 14-AUG-07:01 | 14299.76 | 0.00 |
September | 0.00 | 0.00 | 0.158801E+11 | 0.887925E+10 | 33160.45 | 05-SEP-07:01 | 14477.58 | 0.00 |
October | 0.00 | 0.00 | 0.135679E+11 | 0.823500E+10 | 33146.50 | 25-OCT-07:01 | 14783.34 | 0.00 |
November | 0.00 | 0.00 | 0.561348E+10 | 0.356816E+10 | 32105.01 | 02-NOV-07:01 | 16910.42 | 0.00 |
December | 0.00 | 0.00 | 0.357441E+10 | 0.224759E+10 | 31752.99 | 16-DEC-08:62 | 17316.81 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.122228E+12 | 0.730129E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.196277E+10 | 0.125159E+10 | 30146.42 | 14016.59 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.182682E+11 | 0.105485E+11 | 33192.83 | 17316.81 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.347172E+10 | 0.218109E+10 | 57584.60 | 19-JAN-09:02 | 31313.55 | 0.00 |
February | 0.00 | 0.00 | 0.500269E+10 | 0.311327E+10 | 55977.41 | 28-FEB-09:02 | 29362.40 | 0.00 |
March | 0.00 | 0.00 | 0.701294E+10 | 0.451880E+10 | 57715.14 | 07-MAR-09:02 | 32339.60 | 0.00 |
April | 0.00 | 0.00 | 0.128914E+11 | 0.849613E+10 | 58220.34 | 29-APR-08:62 | 32518.25 | 0.00 |
May | 0.00 | 0.00 | 0.280594E+11 | 0.170433E+11 | 60074.15 | 21-MAY-09:01 | 28723.28 | 0.00 |
June | 0.00 | 0.00 | 0.302183E+11 | 0.181371E+11 | 60502.10 | 19-JUN-08:04 | 26219.11 | 0.00 |
July | 0.00 | 0.00 | 0.333789E+11 | 0.185155E+11 | 60773.68 | 31-JUL-08:61 | 26451.04 | 0.00 |
August | 0.00 | 0.00 | 0.337851E+11 | 0.193733E+11 | 60585.97 | 07-AUG-08:61 | 27927.51 | 0.00 |
September | 0.00 | 0.00 | 0.290896E+11 | 0.160750E+11 | 60835.64 | 05-SEP-08:61 | 26239.85 | 0.00 |
October | 0.00 | 0.00 | 0.251805E+11 | 0.151607E+11 | 60647.78 | 08-OCT-09:01 | 28088.48 | 0.00 |
November | 0.00 | 0.00 | 0.103489E+11 | 0.650986E+10 | 58232.89 | 02-NOV-08:61 | 32469.82 | 0.00 |
December | 0.00 | 0.00 | 0.655834E+10 | 0.408061E+10 | 57986.37 | 15-DEC-09:02 | 32068.38 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.224998E+12 | 0.133205E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.347172E+10 | 0.218109E+10 | 55977.41 | 26219.11 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.337851E+11 | 0.193733E+11 | 60835.64 | 32518.25 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.179150E+10 | 0.112687E+10 | 30273.06 | 19-JAN-09:02 | 16491.16 | 0.00 |
February | 0.00 | 0.00 | 0.258332E+10 | 0.160957E+10 | 29420.26 | 28-FEB-09:02 | 15465.42 | 0.00 |
March | 0.00 | 0.00 | 0.363279E+10 | 0.234239E+10 | 30314.38 | 07-MAR-09:02 | 17063.22 | 0.00 |
April | 0.00 | 0.00 | 0.670109E+10 | 0.442327E+10 | 30581.67 | 29-APR-08:62 | 17124.02 | 0.00 |
May | 0.00 | 0.00 | 0.146398E+11 | 0.890913E+10 | 31583.22 | 21-MAY-09:01 | 15057.62 | 0.00 |
June | 0.00 | 0.00 | 0.157565E+11 | 0.947368E+10 | 31802.82 | 19-JUN-08:61 | 13931.85 | 0.00 |
July | 0.00 | 0.00 | 0.174048E+11 | 0.967559E+10 | 31945.58 | 31-JUL-08:61 | 13841.74 | 0.00 |
August | 0.00 | 0.00 | 0.176080E+11 | 0.101166E+11 | 31846.91 | 07-AUG-08:61 | 14610.30 | 0.00 |
September | 0.00 | 0.00 | 0.151621E+11 | 0.839877E+10 | 31978.15 | 05-SEP-08:61 | 13793.22 | 0.00 |
October | 0.00 | 0.00 | 0.131174E+11 | 0.791106E+10 | 31879.40 | 08-OCT-09:01 | 14729.35 | 0.00 |
November | 0.00 | 0.00 | 0.536704E+10 | 0.337921E+10 | 30588.21 | 02-NOV-08:61 | 17135.41 | 0.00 |
December | 0.00 | 0.00 | 0.340590E+10 | 0.212131E+10 | 30465.52 | 15-DEC-09:02 | 16914.02 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.117170E+12 | 0.694875E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.179150E+10 | 0.112687E+10 | 29420.26 | 13793.22 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.176080E+11 | 0.101166E+11 | 31978.15 | 17135.41 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.175341E+10 | 0.110128E+10 | 30141.54 | 19-JAN-09:02 | 16377.87 | 0.00 |
February | 0.00 | 0.00 | 0.253466E+10 | 0.157655E+10 | 29298.14 | 28-FEB-09:02 | 15376.99 | 0.00 |
March | 0.00 | 0.00 | 0.357630E+10 | 0.230086E+10 | 30190.07 | 07-MAR-09:02 | 16919.95 | 0.00 |
April | 0.00 | 0.00 | 0.662727E+10 | 0.436954E+10 | 30455.63 | 29-APR-08:62 | 17002.04 | 0.00 |
May | 0.00 | 0.00 | 0.145615E+11 | 0.885306E+10 | 31447.29 | 21-MAY-09:01 | 14963.33 | 0.00 |
June | 0.00 | 0.00 | 0.156839E+11 | 0.942081E+10 | 31669.53 | 19-JUN-08:61 | 13845.97 | 0.00 |
July | 0.00 | 0.00 | 0.173367E+11 | 0.962774E+10 | 31811.69 | 31-JUL-08:61 | 13760.90 | 0.00 |
August | 0.00 | 0.00 | 0.175413E+11 | 0.100688E+11 | 31713.44 | 07-AUG-08:61 | 14530.69 | 0.00 |
September | 0.00 | 0.00 | 0.150945E+11 | 0.835187E+10 | 31844.13 | 05-SEP-08:61 | 13719.03 | 0.00 |
October | 0.00 | 0.00 | 0.130485E+11 | 0.786033E+10 | 31745.79 | 08-OCT-09:01 | 14651.32 | 0.00 |
November | 0.00 | 0.00 | 0.530796E+10 | 0.333548E+10 | 30462.75 | 02-NOV-08:61 | 17015.59 | 0.00 |
December | 0.00 | 0.00 | 0.336421E+10 | 0.209105E+10 | 30339.70 | 15-DEC-09:02 | 16790.78 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.116430E+12 | 0.689574E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.175341E+10 | 0.110128E+10 | 29298.14 | 13719.03 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.175413E+11 | 0.100688E+11 | 31844.13 | 17015.59 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.167017E+10 | 0.104622E+10 | 28561.38 | 01-JAN-10:02 | 18331.71 | 0.00 |
February | 0.00 | 0.00 | 0.242425E+10 | 0.150275E+10 | 26887.09 | 28-FEB-09:02 | 14011.21 | 0.00 |
March | 0.00 | 0.00 | 0.343963E+10 | 0.220232E+10 | 30272.91 | 07-MAR-09:02 | 16767.40 | 0.00 |
April | 0.00 | 0.00 | 0.644589E+10 | 0.424022E+10 | 30532.49 | 29-APR-08:62 | 16931.17 | 0.00 |
May | 0.00 | 0.00 | 0.144717E+11 | 0.879117E+10 | 31522.44 | 21-MAY-09:01 | 14916.98 | 0.00 |
June | 0.00 | 0.00 | 0.156355E+11 | 0.938679E+10 | 31758.35 | 19-JUN-08:61 | 13812.91 | 0.00 |
July | 0.00 | 0.00 | 0.173281E+11 | 0.962415E+10 | 31900.91 | 31-JUL-08:61 | 13755.99 | 0.00 |
August | 0.00 | 0.00 | 0.175538E+11 | 0.100792E+11 | 31802.38 | 07-AUG-08:02 | 14423.17 | 0.00 |
September | 0.00 | 0.00 | 0.150767E+11 | 0.834164E+10 | 31933.43 | 05-SEP-08:61 | 13731.34 | 0.00 |
October | 0.00 | 0.00 | 0.129977E+11 | 0.782403E+10 | 31834.82 | 08-OCT-09:01 | 14666.94 | 0.00 |
November | 0.00 | 0.00 | 0.518813E+10 | 0.324680E+10 | 30545.37 | 02-NOV-08:61 | 16980.97 | 0.00 |
December | 0.00 | 0.00 | 0.327599E+10 | 0.202741E+10 | 30419.50 | 15-DEC-09:02 | 16718.71 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.115508E+12 | 0.683127E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.167017E+10 | 0.104622E+10 | 26887.09 | 13731.34 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.175538E+11 | 0.100792E+11 | 31933.43 | 18331.71 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.170508E+10 | 0.108305E+10 | 27346.16 | 01-JAN-10:02 | 17744.50 | 0.00 |
February | 0.00 | 0.00 | 0.244559E+10 | 0.153587E+10 | 16109.56 | 28-FEB-09:02 | 8137.66 | 0.00 |
March | 0.00 | 0.00 | 0.358071E+10 | 0.232108E+10 | 27869.50 | 07-MAR-09:02 | 14418.56 | 0.00 |
April | 0.00 | 0.00 | 0.668151E+10 | 0.446194E+10 | 34501.07 | 29-APR-08:62 | 17888.53 | 0.00 |
May | 0.00 | 0.00 | 0.155249E+11 | 0.958349E+10 | 35449.13 | 24-MAY-08:61 | 15953.56 | 0.00 |
June | 0.00 | 0.00 | 0.169416E+11 | 0.103699E+11 | 35593.34 | 05-JUN-08:61 | 16377.74 | 0.00 |
July | 0.00 | 0.00 | 0.188936E+11 | 0.107552E+11 | 35740.76 | 31-JUL-08:61 | 15284.18 | 0.00 |
August | 0.00 | 0.00 | 0.192848E+11 | 0.113307E+11 | 35630.36 | 07-AUG-08:61 | 15862.83 | 0.00 |
September | 0.00 | 0.00 | 0.164752E+11 | 0.934294E+10 | 35777.20 | 05-SEP-08:02 | 15136.29 | 0.00 |
October | 0.00 | 0.00 | 0.141232E+11 | 0.866556E+10 | 35732.33 | 22-OCT-09:01 | 15632.97 | 0.00 |
November | 0.00 | 0.00 | 0.541079E+10 | 0.343096E+10 | 34531.88 | 02-NOV-08:61 | 18287.40 | 0.00 |
December | 0.00 | 0.00 | 0.335948E+10 | 0.210292E+10 | 34350.25 | 15-DEC-09:02 | 17872.51 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.124426E+12 | 0.749836E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.170508E+10 | 0.108305E+10 | 16109.56 | 8137.66 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.192848E+11 | 0.113307E+11 | 35777.20 | 18287.40 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.175957E+10 | 0.36 | 2410.03 | 19-JAN-09:02 | 0.86 |
February | 0.159808E+10 | 0.36 | 2410.03 | 05-FEB-09:02 | 0.88 |
March | 0.176681E+10 | 0.36 | 2410.03 | 07-MAR-09:02 | 0.86 |
April | 0.169788E+10 | 0.36 | 2410.03 | 22-APR-08:62 | 0.87 |
May | 0.178265E+10 | 0.36 | 2410.03 | 01-MAY-08:62 | 0.86 |
June | 0.177661E+10 | 0.37 | 2410.03 | 01-JUN-08:61 | 0.86 |
July | 0.190432E+10 | 0.37 | 2410.03 | 01-JUL-08:61 | 0.86 |
August | 0.190460E+10 | 0.37 | 2410.03 | 01-AUG-08:61 | 0.86 |
September | 0.179847E+10 | 0.37 | 2410.03 | 01-SEP-08:61 | 0.86 |
October | 0.182963E+10 | 0.37 | 2410.03 | 02-OCT-08:62 | 0.87 |
November | 0.169591E+10 | 0.36 | 2410.03 | 01-NOV-08:62 | 0.86 |
December | 0.176848E+10 | 0.36 | 2410.03 | 11-DEC-09:02 | 0.86 |
Annual Sum or Average | 0.212830E+11 | 0.36 | |||
Minimum of Months | 0.159808E+10 | 0.36 | 2410.03 | 0.86 | |
Maximum of Months | 0.190460E+10 | 0.37 | 2410.03 | 0.88 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.793666E+09 | 0.36 | 1289.15 | 19-JAN-09:02 | 0.89 |
February | 0.745857E+09 | 0.36 | 1289.15 | 28-FEB-09:02 | 0.90 |
March | 0.825562E+09 | 0.37 | 1289.15 | 07-MAR-09:02 | 0.90 |
April | 0.807816E+09 | 0.37 | 1289.15 | 22-APR-08:62 | 0.90 |
May | 0.840579E+09 | 0.38 | 1289.15 | 01-MAY-08:62 | 0.90 |
June | 0.845517E+09 | 0.39 | 1289.15 | 01-JUN-08:61 | 0.90 |
July | 0.917743E+09 | 0.39 | 1289.15 | 01-JUL-08:61 | 0.90 |
August | 0.914179E+09 | 0.39 | 1289.15 | 01-AUG-08:61 | 0.90 |
September | 0.853289E+09 | 0.39 | 1289.15 | 01-SEP-08:61 | 0.90 |
October | 0.867457E+09 | 0.38 | 1289.15 | 02-OCT-08:62 | 0.90 |
November | 0.837092E+09 | 0.37 | 1289.15 | 01-NOV-08:62 | 0.90 |
December | 0.834630E+09 | 0.37 | 1289.15 | 11-DEC-09:02 | 0.90 |
Annual Sum or Average | 0.100834E+11 | 0.38 | |||
Minimum of Months | 0.745857E+09 | 0.36 | 1289.15 | 0.89 | |
Maximum of Months | 0.917743E+09 | 0.39 | 1289.15 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.748142E+09 | 0.30 | 1284.24 | 01-JAN-09:02 | 0.90 |
February | 0.679232E+09 | 0.30 | 1284.24 | 28-FEB-08:62 | 0.90 |
March | 0.763016E+09 | 0.30 | 1284.24 | 07-MAR-08:62 | 0.89 |
April | 0.723733E+09 | 0.30 | 1284.24 | 01-APR-07:02 | 0.89 |
May | 0.768049E+09 | 0.30 | 1284.24 | 01-MAY-07:02 | 0.89 |
June | 0.771711E+09 | 0.31 | 1284.24 | 01-JUN-07:02 | 0.89 |
July | 0.818010E+09 | 0.31 | 1284.24 | 01-JUL-07:01 | 0.89 |
August | 0.831260E+09 | 0.32 | 1284.24 | 01-AUG-07:01 | 0.89 |
September | 0.768669E+09 | 0.30 | 1284.24 | 01-SEP-07:01 | 0.89 |
October | 0.782016E+09 | 0.30 | 1284.24 | 01-OCT-08:62 | 0.90 |
November | 0.724056E+09 | 0.30 | 1284.24 | 01-NOV-07:02 | 0.89 |
December | 0.745346E+09 | 0.30 | 1284.24 | 10-DEC-09:02 | 0.90 |
Annual Sum or Average | 0.912324E+10 | 0.30 | |||
Minimum of Months | 0.679232E+09 | 0.30 | 1284.24 | 0.89 | |
Maximum of Months | 0.831260E+09 | 0.32 | 1284.24 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.751110E+09 | 0.30 | 1287.69 | 01-JAN-09:02 | 0.90 |
February | 0.681657E+09 | 0.30 | 1287.69 | 28-FEB-08:62 | 0.90 |
March | 0.765452E+09 | 0.30 | 1287.69 | 07-MAR-08:62 | 0.89 |
April | 0.725589E+09 | 0.30 | 1287.69 | 01-APR-07:02 | 0.89 |
May | 0.769951E+09 | 0.30 | 1287.69 | 01-MAY-07:02 | 0.89 |
June | 0.773712E+09 | 0.31 | 1287.69 | 01-JUN-07:02 | 0.89 |
July | 0.820463E+09 | 0.31 | 1287.69 | 01-JUL-07:01 | 0.89 |
August | 0.833373E+09 | 0.32 | 1287.69 | 01-AUG-07:01 | 0.89 |
September | 0.771021E+09 | 0.30 | 1287.69 | 01-SEP-07:01 | 0.89 |
October | 0.784060E+09 | 0.30 | 1287.69 | 01-OCT-08:62 | 0.90 |
November | 0.725886E+09 | 0.30 | 1287.69 | 01-NOV-07:02 | 0.89 |
December | 0.747826E+09 | 0.30 | 1287.69 | 10-DEC-09:02 | 0.90 |
Annual Sum or Average | 0.915010E+10 | 0.30 | |||
Minimum of Months | 0.681657E+09 | 0.30 | 1287.69 | 0.89 | |
Maximum of Months | 0.833373E+09 | 0.32 | 1287.69 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.749636E+09 | 0.30 | 1283.20 | 01-JAN-09:02 | 0.90 |
February | 0.680013E+09 | 0.30 | 1283.20 | 28-FEB-08:62 | 0.90 |
March | 0.763275E+09 | 0.30 | 1283.20 | 07-MAR-08:62 | 0.89 |
April | 0.722768E+09 | 0.30 | 1283.20 | 01-APR-07:02 | 0.89 |
May | 0.765994E+09 | 0.30 | 1283.20 | 01-MAY-07:02 | 0.89 |
June | 0.769298E+09 | 0.31 | 1283.20 | 01-JUN-07:02 | 0.89 |
July | 0.816107E+09 | 0.31 | 1283.20 | 01-JUL-07:01 | 0.89 |
August | 0.828595E+09 | 0.31 | 1283.20 | 01-AUG-07:01 | 0.89 |
September | 0.767155E+09 | 0.30 | 1283.20 | 01-SEP-07:01 | 0.89 |
October | 0.780233E+09 | 0.30 | 1283.20 | 01-OCT-08:62 | 0.90 |
November | 0.723017E+09 | 0.30 | 1283.20 | 01-NOV-07:02 | 0.89 |
December | 0.745907E+09 | 0.30 | 1283.20 | 10-DEC-09:02 | 0.90 |
Annual Sum or Average | 0.911200E+10 | 0.30 | |||
Minimum of Months | 0.680013E+09 | 0.30 | 1283.20 | 0.89 | |
Maximum of Months | 0.828595E+09 | 0.31 | 1283.20 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.122425E+10 | 0.27 | 2271.11 | 01-JAN-10:02 | 0.87 |
February | 0.111098E+10 | 0.27 | 2271.11 | 05-FEB-10:01 | 0.88 |
March | 0.124835E+10 | 0.27 | 2271.11 | 07-MAR-09:02 | 0.86 |
April | 0.118279E+10 | 0.26 | 2271.11 | 22-APR-08:62 | 0.87 |
May | 0.127310E+10 | 0.27 | 2271.11 | 01-MAY-08:62 | 0.86 |
June | 0.129112E+10 | 0.28 | 2271.11 | 01-JUN-08:61 | 0.86 |
July | 0.137926E+10 | 0.28 | 2271.11 | 01-JUL-08:61 | 0.86 |
August | 0.140348E+10 | 0.29 | 2271.11 | 01-AUG-08:61 | 0.86 |
September | 0.128633E+10 | 0.28 | 2271.11 | 01-SEP-08:61 | 0.86 |
October | 0.130389E+10 | 0.27 | 2271.11 | 01-OCT-09:02 | 0.87 |
November | 0.118420E+10 | 0.26 | 2271.11 | 01-NOV-08:62 | 0.86 |
December | 0.121845E+10 | 0.26 | 2271.11 | 10-DEC-10:02 | 0.87 |
Annual Sum or Average | 0.151062E+11 | 0.27 | |||
Minimum of Months | 0.111098E+10 | 0.26 | 2271.11 | 0.86 | |
Maximum of Months | 0.140348E+10 | 0.29 | 2271.11 | 0.88 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.665796E+09 | 0.27 | 1235.21 | 01-JAN-10:02 | 0.90 |
February | 0.604444E+09 | 0.28 | 1235.21 | 05-FEB-10:01 | 0.91 |
March | 0.678964E+09 | 0.28 | 1235.21 | 07-MAR-09:02 | 0.89 |
April | 0.643135E+09 | 0.27 | 1235.21 | 22-APR-08:62 | 0.90 |
May | 0.692123E+09 | 0.28 | 1235.21 | 01-MAY-08:62 | 0.89 |
June | 0.701646E+09 | 0.29 | 1235.21 | 01-JUN-08:61 | 0.89 |
July | 0.749522E+09 | 0.29 | 1235.21 | 01-JUL-08:61 | 0.89 |
August | 0.762230E+09 | 0.30 | 1235.21 | 01-AUG-08:61 | 0.89 |
September | 0.698638E+09 | 0.28 | 1235.21 | 01-SEP-08:61 | 0.89 |
October | 0.707813E+09 | 0.28 | 1235.21 | 01-OCT-09:02 | 0.90 |
November | 0.643819E+09 | 0.27 | 1235.21 | 01-NOV-08:62 | 0.89 |
December | 0.662741E+09 | 0.27 | 1235.21 | 10-DEC-10:02 | 0.90 |
Annual Sum or Average | 0.821087E+10 | 0.28 | |||
Minimum of Months | 0.604444E+09 | 0.27 | 1235.21 | 0.89 | |
Maximum of Months | 0.762230E+09 | 0.30 | 1235.21 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.663626E+09 | 0.27 | 1230.03 | 01-JAN-10:02 | 0.90 |
February | 0.602286E+09 | 0.28 | 1230.03 | 05-FEB-10:01 | 0.91 |
March | 0.676348E+09 | 0.28 | 1230.03 | 07-MAR-09:02 | 0.89 |
April | 0.640383E+09 | 0.27 | 1230.03 | 22-APR-08:62 | 0.90 |
May | 0.689140E+09 | 0.28 | 1230.03 | 01-MAY-08:62 | 0.89 |
June | 0.698761E+09 | 0.29 | 1230.03 | 01-JUN-08:61 | 0.89 |
July | 0.746756E+09 | 0.29 | 1230.03 | 01-JUL-08:61 | 0.89 |
August | 0.759445E+09 | 0.30 | 1230.03 | 01-AUG-08:61 | 0.89 |
September | 0.695948E+09 | 0.28 | 1230.03 | 01-SEP-08:61 | 0.89 |
October | 0.704919E+09 | 0.28 | 1230.03 | 01-OCT-09:02 | 0.90 |
November | 0.641069E+09 | 0.27 | 1230.03 | 01-NOV-08:62 | 0.89 |
December | 0.660330E+09 | 0.27 | 1230.03 | 10-DEC-10:02 | 0.90 |
Annual Sum or Average | 0.817901E+10 | 0.28 | |||
Minimum of Months | 0.602286E+09 | 0.27 | 1230.03 | 0.89 | |
Maximum of Months | 0.759445E+09 | 0.30 | 1230.03 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.667309E+09 | 0.28 | 1233.48 | 01-JAN-10:02 | 0.90 |
February | 0.605182E+09 | 0.28 | 1233.48 | 05-FEB-10:01 | 0.91 |
March | 0.679135E+09 | 0.28 | 1233.48 | 07-MAR-09:02 | 0.89 |
April | 0.641823E+09 | 0.27 | 1233.48 | 22-APR-08:62 | 0.90 |
May | 0.689335E+09 | 0.28 | 1233.48 | 01-MAY-08:62 | 0.89 |
June | 0.699177E+09 | 0.29 | 1233.48 | 01-JUN-08:61 | 0.89 |
July | 0.748117E+09 | 0.29 | 1233.48 | 01-JUL-08:61 | 0.89 |
August | 0.760984E+09 | 0.30 | 1233.48 | 01-AUG-08:61 | 0.89 |
September | 0.697335E+09 | 0.28 | 1233.48 | 01-SEP-08:61 | 0.89 |
October | 0.706029E+09 | 0.28 | 1233.48 | 01-OCT-09:02 | 0.90 |
November | 0.642521E+09 | 0.27 | 1233.48 | 01-NOV-08:62 | 0.89 |
December | 0.663325E+09 | 0.27 | 1233.48 | 10-DEC-10:02 | 0.90 |
Annual Sum or Average | 0.820027E+10 | 0.28 | |||
Minimum of Months | 0.605182E+09 | 0.27 | 1233.48 | 0.89 | |
Maximum of Months | 0.760984E+09 | 0.30 | 1233.48 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.766897E+09 | 0.28 | 1410.66 | 05-JAN-09:02 | 0.91 |
February | 0.694544E+09 | 0.28 | 1410.66 | 05-FEB-10:01 | 0.91 |
March | 0.779318E+09 | 0.28 | 1410.66 | 10-MAR-09:02 | 0.91 |
April | 0.732287E+09 | 0.27 | 1410.66 | 23-APR-09:02 | 0.90 |
May | 0.778204E+09 | 0.28 | 1410.66 | 01-MAY-08:62 | 0.89 |
June | 0.786475E+09 | 0.28 | 1410.66 | 01-JUN-08:61 | 0.89 |
July | 0.844047E+09 | 0.29 | 1410.66 | 01-JUL-08:61 | 0.89 |
August | 0.859494E+09 | 0.29 | 1410.66 | 01-AUG-08:61 | 0.89 |
September | 0.789908E+09 | 0.28 | 1410.66 | 01-SEP-08:61 | 0.89 |
October | 0.798808E+09 | 0.28 | 1410.66 | 01-OCT-09:02 | 0.90 |
November | 0.733426E+09 | 0.27 | 1410.66 | 01-NOV-08:62 | 0.89 |
December | 0.761559E+09 | 0.27 | 1410.66 | 10-DEC-10:02 | 0.90 |
Annual Sum or Average | 0.932497E+10 | 0.28 | |||
Minimum of Months | 0.694544E+09 | 0.27 | 1410.66 | 0.89 | |
Maximum of Months | 0.859494E+09 | 0.29 | 1410.66 | 0.91 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.302417E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.324018E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.416940E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.612213E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.112453E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.117948E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.130791E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.129497E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.115280E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.102155E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.511351E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.397237E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.964542E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.302417E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.130791E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.151752E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.170188E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.217847E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.318500E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.549848E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.573864E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.633521E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.625235E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.557736E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.501110E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.266354E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.199607E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.476556E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.151752E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.633521E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.128321E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.140842E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.178477E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.252660E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.451376E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.475880E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.515128E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.520463E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.452376E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.403867E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.214638E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.165486E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.389951E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.128321E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.520463E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.127036E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.139473E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.177281E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.252066E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.452618E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.477484E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.517440E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.522380E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.454252E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.405117E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.213685E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.164801E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.390363E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.127036E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.522380E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.124440E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.136401E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.173467E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.247124E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.448176E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.473178E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.513304E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.517975E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.450331E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.401344E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.209795E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.162301E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.385784E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.124440E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.517975E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.211133E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.238113E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.303814E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.447173E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.818950E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.870121E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.941193E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.956807E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.821302E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.738871E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.374837E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.284447E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.700676E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.211133E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.956807E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.111606E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.124965E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.159107E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.232508E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.424550E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.450677E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.487516E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.495368E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.425333E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.382803E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.195187E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.149322E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.363894E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.111606E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.495368E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.110471E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.123584E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.157486E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.230439E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.422343E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.448579E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.485526E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.493406E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.423421E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.380840E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.193478E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.148083E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.361766E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.110471E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.493406E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.108868E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.121310E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.154584E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.226385E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.420587E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.447706E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.485643E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.493997E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.423348E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.379918E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.190836E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.146390E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.359957E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.108868E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.493997E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.120091E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.131426E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.168975E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.242988E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.458526E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.491114E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.535930E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.547941E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.468311E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.417938E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.206403E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.159291E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.394893E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.120091E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.547941E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.175957E+10 | 0.497072E+10 | 0.411446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.159808E+10 | 0.647390E+10 | 0.629502E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.176681E+10 | 0.939166E+10 | 0.410742E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.169788E+10 | 0.173268E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.178265E+10 | 0.380513E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.177661E+10 | 0.405312E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.190432E+10 | 0.460469E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.190460E+10 | 0.454217E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.179847E+10 | 0.403692E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.182963E+10 | 0.344510E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.169591E+10 | 0.137385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.176848E+10 | 0.883462E+10 | 0.450815E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.212830E+11 | 0.305608E+12 | 0.190251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.159808E+10 | 0.497072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.190460E+10 | 0.460469E+11 | 0.629502E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.793666E+09 | 0.289550E+10 | 42361135.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.745857E+09 | 0.382907E+10 | 0.126369E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.825562E+09 | 0.537870E+10 | 0.111514E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.807816E+09 | 0.942154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.840579E+09 | 0.189045E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.845517E+09 | 0.199432E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.917743E+09 | 0.224306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.914179E+09 | 0.220811E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.853289E+09 | 0.197428E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.867457E+09 | 0.171420E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.837092E+09 | 0.739978E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.834630E+09 | 0.472082E+10 | 0.104374E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100834E+11 | 0.153889E+12 | 0.384618E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.745857E+09 | 0.289550E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.917743E+09 | 0.224306E+11 | 0.126369E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.748142E+09 | 0.213275E+10 | 0.166185E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.679232E+09 | 0.292265E+10 | 0.227715E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.763016E+09 | 0.406676E+10 | 0.165535E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.723733E+09 | 0.717841E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.768049E+09 | 0.154029E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.771711E+09 | 0.164932E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.818010E+09 | 0.182607E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.831260E+09 | 0.183657E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.768669E+09 | 0.159698E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.782016E+09 | 0.136724E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.724056E+09 | 0.581513E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.745346E+09 | 0.371310E+10 | 0.183938E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.912324E+10 | 0.123994E+12 | 0.743372E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.679232E+09 | 0.213275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.831260E+09 | 0.183657E+11 | 0.227715E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.751110E+09 | 0.206553E+10 | 0.206225E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.681657E+09 | 0.285297E+10 | 0.252956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.765452E+09 | 0.400417E+10 | 0.182757E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.725589E+09 | 0.714186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.769951E+09 | 0.154440E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.773712E+09 | 0.165496E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.820463E+09 | 0.183452E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.833373E+09 | 0.184346E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.771021E+09 | 0.160373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.784060E+09 | 0.137149E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.725886E+09 | 0.576603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.747826E+09 | 0.367313E+10 | 0.203761E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.915010E+10 | 0.124029E+12 | 0.845698E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.681657E+09 | 0.206553E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.833373E+09 | 0.184346E+11 | 0.252956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.749636E+09 | 0.196277E+10 | 0.254412E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.680013E+09 | 0.273013E+10 | 0.284639E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.763275E+09 | 0.385247E+10 | 0.206050E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.722768E+09 | 0.694487E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.765994E+09 | 0.152640E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.769298E+09 | 0.163820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.816107E+09 | 0.181882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.828595E+09 | 0.182682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.767155E+09 | 0.158801E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.780233E+09 | 0.135679E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.723017E+09 | 0.561348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.745907E+09 | 0.357441E+10 | 0.234199E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.911200E+10 | 0.122228E+12 | 0.979300E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.680013E+09 | 0.196277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.828595E+09 | 0.182682E+11 | 0.284639E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.122425E+10 | 0.347172E+10 | 0.434074E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.111098E+10 | 0.500269E+10 | 0.491110E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.124835E+10 | 0.701294E+10 | 0.339094E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.118279E+10 | 0.128914E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.127310E+10 | 0.280594E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.129112E+10 | 0.302183E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137926E+10 | 0.333789E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140348E+10 | 0.337851E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128633E+10 | 0.290896E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.130389E+10 | 0.251805E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.118420E+10 | 0.103489E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.121845E+10 | 0.655834E+10 | 0.417614E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.151062E+11 | 0.224998E+12 | 0.168189E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.111098E+10 | 0.347172E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140348E+10 | 0.337851E+11 | 0.491110E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.665796E+09 | 0.179150E+10 | 0.226250E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.604444E+09 | 0.258332E+10 | 0.265696E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.678964E+09 | 0.363279E+10 | 0.179348E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.643135E+09 | 0.670109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.692123E+09 | 0.146398E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.701646E+09 | 0.157565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.749522E+09 | 0.174048E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.762230E+09 | 0.176080E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.698638E+09 | 0.151621E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.707813E+09 | 0.131174E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.643819E+09 | 0.536704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.662741E+09 | 0.340590E+10 | 0.223984E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.821087E+10 | 0.117170E+12 | 0.895278E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.604444E+09 | 0.179150E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.762230E+09 | 0.176080E+11 | 0.265696E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.663626E+09 | 0.175341E+10 | 0.250712E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.602286E+09 | 0.253466E+10 | 0.280438E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.676348E+09 | 0.357630E+10 | 0.189360E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.640383E+09 | 0.662727E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.689140E+09 | 0.145615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.698761E+09 | 0.156839E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.746756E+09 | 0.173367E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.759445E+09 | 0.175413E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.695948E+09 | 0.150945E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.704919E+09 | 0.130485E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.641069E+09 | 0.530796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.660330E+09 | 0.336421E+10 | 0.239016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.817901E+10 | 0.116430E+12 | 0.959527E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.602286E+09 | 0.175341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.759445E+09 | 0.175413E+11 | 0.280438E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.667309E+09 | 0.167017E+10 | 0.325900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.605182E+09 | 0.242425E+10 | 0.331396E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.679135E+09 | 0.343963E+10 | 0.228443E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.641823E+09 | 0.644589E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.689335E+09 | 0.144717E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.699177E+09 | 0.156355E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.748117E+09 | 0.173281E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.760984E+09 | 0.175538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.697335E+09 | 0.150767E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.706029E+09 | 0.129977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.642521E+09 | 0.518813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.663325E+09 | 0.327599E+10 | 0.289370E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.820027E+10 | 0.115508E+12 | 0.117511E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.605182E+09 | 0.167017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.760984E+09 | 0.175538E+11 | 0.331396E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.766897E+09 | 0.170508E+10 | 0.517758E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.694544E+09 | 0.244559E+10 | 0.471298E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.779318E+09 | 0.358071E+10 | 0.367800E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.732287E+09 | 0.668151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.778204E+09 | 0.155249E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.786475E+09 | 0.169416E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.844047E+09 | 0.188936E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.859494E+09 | 0.192848E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.789908E+09 | 0.164752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.798808E+09 | 0.141232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.733426E+09 | 0.541079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.761559E+09 | 0.335948E+10 | 0.443144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.932497E+10 | 0.124426E+12 | 0.180000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.694544E+09 | 0.170508E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.859494E+09 | 0.192848E+11 | 0.517758E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.175957E+10 | 0.00 | 0.00 | 0.00 | 0.126459E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.159808E+10 | 0.00 | 0.00 | 0.00 | 0.164210E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.176681E+10 | 0.00 | 0.00 | 0.00 | 0.240259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.169788E+10 | 0.00 | 0.00 | 0.00 | 0.442424E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.178265E+10 | 0.00 | 0.00 | 0.00 | 0.946263E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.177661E+10 | 0.00 | 0.00 | 0.00 | 0.100182E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.190432E+10 | 0.00 | 0.00 | 0.00 | 0.111748E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.190460E+10 | 0.00 | 0.00 | 0.00 | 0.110451E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.179847E+10 | 0.00 | 0.00 | 0.00 | 0.972952E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.182963E+10 | 0.00 | 0.00 | 0.00 | 0.838584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.169591E+10 | 0.00 | 0.00 | 0.00 | 0.341760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.176848E+10 | 0.00 | 0.00 | 0.00 | 0.220390E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.212830E+11 | 0.00 | 0.00 | 0.00 | 0.751711E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.159808E+10 | 0.00 | 0.00 | 0.00 | 0.126459E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.190460E+10 | 0.00 | 0.00 | 0.00 | 0.111748E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.793666E+09 | 0.00 | 0.00 | 0.00 | 0.723852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.745857E+09 | 0.00 | 0.00 | 0.00 | 0.956022E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.825562E+09 | 0.00 | 0.00 | 0.00 | 0.135291E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.807816E+09 | 0.00 | 0.00 | 0.00 | 0.237718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.840579E+09 | 0.00 | 0.00 | 0.00 | 0.465790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.845517E+09 | 0.00 | 0.00 | 0.00 | 0.489313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.917743E+09 | 0.00 | 0.00 | 0.00 | 0.541747E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.914179E+09 | 0.00 | 0.00 | 0.00 | 0.533817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.853289E+09 | 0.00 | 0.00 | 0.00 | 0.472407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.867457E+09 | 0.00 | 0.00 | 0.00 | 0.414364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.837092E+09 | 0.00 | 0.00 | 0.00 | 0.182644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.834630E+09 | 0.00 | 0.00 | 0.00 | 0.116144E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100834E+11 | 0.00 | 0.00 | 0.00 | 0.375722E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.745857E+09 | 0.00 | 0.00 | 0.00 | 0.723852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.917743E+09 | 0.00 | 0.00 | 0.00 | 0.541747E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.748142E+09 | 0.00 | 0.00 | 0.00 | 0.535064E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.679232E+09 | 0.00 | 0.00 | 0.00 | 0.729190E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.763016E+09 | 0.00 | 0.00 | 0.00 | 0.102175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.723733E+09 | 0.00 | 0.00 | 0.00 | 0.180287E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.768049E+09 | 0.00 | 0.00 | 0.00 | 0.374571E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.771711E+09 | 0.00 | 0.00 | 0.00 | 0.398708E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.818010E+09 | 0.00 | 0.00 | 0.00 | 0.433327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.831260E+09 | 0.00 | 0.00 | 0.00 | 0.437337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.768669E+09 | 0.00 | 0.00 | 0.00 | 0.375509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.782016E+09 | 0.00 | 0.00 | 0.00 | 0.325666E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.724056E+09 | 0.00 | 0.00 | 0.00 | 0.142233E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.745346E+09 | 0.00 | 0.00 | 0.00 | 0.909512E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.912324E+10 | 0.00 | 0.00 | 0.00 | 0.298719E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.679232E+09 | 0.00 | 0.00 | 0.00 | 0.535064E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.831260E+09 | 0.00 | 0.00 | 0.00 | 0.437337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.751110E+09 | 0.00 | 0.00 | 0.00 | 0.519249E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.681657E+09 | 0.00 | 0.00 | 0.00 | 0.713078E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.765452E+09 | 0.00 | 0.00 | 0.00 | 0.100736E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.725589E+09 | 0.00 | 0.00 | 0.00 | 0.179507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.769951E+09 | 0.00 | 0.00 | 0.00 | 0.375623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.773712E+09 | 0.00 | 0.00 | 0.00 | 0.400112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.820463E+09 | 0.00 | 0.00 | 0.00 | 0.435394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.833373E+09 | 0.00 | 0.00 | 0.00 | 0.439043E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.771021E+09 | 0.00 | 0.00 | 0.00 | 0.377150E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.784060E+09 | 0.00 | 0.00 | 0.00 | 0.326711E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.725886E+09 | 0.00 | 0.00 | 0.00 | 0.141097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.747826E+09 | 0.00 | 0.00 | 0.00 | 0.900179E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.915010E+10 | 0.00 | 0.00 | 0.00 | 0.298862E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.681657E+09 | 0.00 | 0.00 | 0.00 | 0.519249E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.833373E+09 | 0.00 | 0.00 | 0.00 | 0.439043E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.749636E+09 | 0.00 | 0.00 | 0.00 | 0.494759E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.680013E+09 | 0.00 | 0.00 | 0.00 | 0.683992E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.763275E+09 | 0.00 | 0.00 | 0.00 | 0.971400E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.722768E+09 | 0.00 | 0.00 | 0.00 | 0.174848E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.765994E+09 | 0.00 | 0.00 | 0.00 | 0.371577E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.769298E+09 | 0.00 | 0.00 | 0.00 | 0.396248E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.816107E+09 | 0.00 | 0.00 | 0.00 | 0.431693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.828595E+09 | 0.00 | 0.00 | 0.00 | 0.435116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.767155E+09 | 0.00 | 0.00 | 0.00 | 0.373616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.780233E+09 | 0.00 | 0.00 | 0.00 | 0.323320E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.723017E+09 | 0.00 | 0.00 | 0.00 | 0.137493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.745907E+09 | 0.00 | 0.00 | 0.00 | 0.877106E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.911200E+10 | 0.00 | 0.00 | 0.00 | 0.294664E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.680013E+09 | 0.00 | 0.00 | 0.00 | 0.494759E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.828595E+09 | 0.00 | 0.00 | 0.00 | 0.435116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.122425E+10 | 0.00 | 0.00 | 0.00 | 0.887078E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.111098E+10 | 0.00 | 0.00 | 0.00 | 0.127016E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.124835E+10 | 0.00 | 0.00 | 0.00 | 0.178980E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.118279E+10 | 0.00 | 0.00 | 0.00 | 0.328895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.127310E+10 | 0.00 | 0.00 | 0.00 | 0.691640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.129112E+10 | 0.00 | 0.00 | 0.00 | 0.741009E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137926E+10 | 0.00 | 0.00 | 0.00 | 0.803267E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140348E+10 | 0.00 | 0.00 | 0.00 | 0.816459E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128633E+10 | 0.00 | 0.00 | 0.00 | 0.692669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.130389E+10 | 0.00 | 0.00 | 0.00 | 0.608482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.118420E+10 | 0.00 | 0.00 | 0.00 | 0.256417E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.121845E+10 | 0.00 | 0.00 | 0.00 | 0.162602E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.151062E+11 | 0.00 | 0.00 | 0.00 | 0.549614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.111098E+10 | 0.00 | 0.00 | 0.00 | 0.887078E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140348E+10 | 0.00 | 0.00 | 0.00 | 0.816459E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.665796E+09 | 0.00 | 0.00 | 0.00 | 0.450264E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.604444E+09 | 0.00 | 0.00 | 0.00 | 0.645202E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.678964E+09 | 0.00 | 0.00 | 0.00 | 0.912105E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.643135E+09 | 0.00 | 0.00 | 0.00 | 0.168195E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.692123E+09 | 0.00 | 0.00 | 0.00 | 0.355337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.701646E+09 | 0.00 | 0.00 | 0.00 | 0.380513E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.749522E+09 | 0.00 | 0.00 | 0.00 | 0.412563E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.762230E+09 | 0.00 | 0.00 | 0.00 | 0.419145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.698638E+09 | 0.00 | 0.00 | 0.00 | 0.355469E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.707813E+09 | 0.00 | 0.00 | 0.00 | 0.312022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.643819E+09 | 0.00 | 0.00 | 0.00 | 0.130805E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.662741E+09 | 0.00 | 0.00 | 0.00 | 0.830476E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.821087E+10 | 0.00 | 0.00 | 0.00 | 0.281785E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.604444E+09 | 0.00 | 0.00 | 0.00 | 0.450264E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.762230E+09 | 0.00 | 0.00 | 0.00 | 0.419145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.663626E+09 | 0.00 | 0.00 | 0.00 | 0.441080E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.602286E+09 | 0.00 | 0.00 | 0.00 | 0.633550E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.676348E+09 | 0.00 | 0.00 | 0.00 | 0.898509E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.640383E+09 | 0.00 | 0.00 | 0.00 | 0.166401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.689140E+09 | 0.00 | 0.00 | 0.00 | 0.353429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.698761E+09 | 0.00 | 0.00 | 0.00 | 0.378703E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.746756E+09 | 0.00 | 0.00 | 0.00 | 0.410850E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.759445E+09 | 0.00 | 0.00 | 0.00 | 0.417461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.695948E+09 | 0.00 | 0.00 | 0.00 | 0.353826E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.704919E+09 | 0.00 | 0.00 | 0.00 | 0.310348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.641069E+09 | 0.00 | 0.00 | 0.00 | 0.129372E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.660330E+09 | 0.00 | 0.00 | 0.00 | 0.820502E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.817901E+10 | 0.00 | 0.00 | 0.00 | 0.279975E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.602286E+09 | 0.00 | 0.00 | 0.00 | 0.441080E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.759445E+09 | 0.00 | 0.00 | 0.00 | 0.417461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.667309E+09 | 0.00 | 0.00 | 0.00 | 0.421373E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.605182E+09 | 0.00 | 0.00 | 0.00 | 0.607922E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.679135E+09 | 0.00 | 0.00 | 0.00 | 0.866703E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.641823E+09 | 0.00 | 0.00 | 0.00 | 0.162202E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.689335E+09 | 0.00 | 0.00 | 0.00 | 0.351653E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.699177E+09 | 0.00 | 0.00 | 0.00 | 0.377789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.748117E+09 | 0.00 | 0.00 | 0.00 | 0.410831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.760984E+09 | 0.00 | 0.00 | 0.00 | 0.417899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.697335E+09 | 0.00 | 0.00 | 0.00 | 0.353614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.706029E+09 | 0.00 | 0.00 | 0.00 | 0.309315E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.642521E+09 | 0.00 | 0.00 | 0.00 | 0.126584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.663325E+09 | 0.00 | 0.00 | 0.00 | 0.800573E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.820027E+10 | 0.00 | 0.00 | 0.00 | 0.277954E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.605182E+09 | 0.00 | 0.00 | 0.00 | 0.421373E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.760984E+09 | 0.00 | 0.00 | 0.00 | 0.417899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.766897E+09 | 0.00 | 0.00 | 0.00 | 0.434017E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.694544E+09 | 0.00 | 0.00 | 0.00 | 0.619715E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.779318E+09 | 0.00 | 0.00 | 0.00 | 0.910434E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.732287E+09 | 0.00 | 0.00 | 0.00 | 0.169759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.778204E+09 | 0.00 | 0.00 | 0.00 | 0.380705E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.786475E+09 | 0.00 | 0.00 | 0.00 | 0.412466E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.844047E+09 | 0.00 | 0.00 | 0.00 | 0.451526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.859494E+09 | 0.00 | 0.00 | 0.00 | 0.461991E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.789908E+09 | 0.00 | 0.00 | 0.00 | 0.389320E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.798808E+09 | 0.00 | 0.00 | 0.00 | 0.338058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.733426E+09 | 0.00 | 0.00 | 0.00 | 0.133061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.761559E+09 | 0.00 | 0.00 | 0.00 | 0.831351E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.932497E+10 | 0.00 | 0.00 | 0.00 | 0.301644E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.694544E+09 | 0.00 | 0.00 | 0.00 | 0.434017E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.859494E+09 | 0.00 | 0.00 | 0.00 | 0.461991E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.567589E+10 | 0.728574E+09 | 0.00 | 3733679.05 | 6295642.79 | 45300818.28 | 0.172090E+10 | 0.00 | 0.63 |
February | 0.335676E+10 | 0.941865E+09 | 0.00 | 4512500.23 | 1755684.82 | 0.153139E+09 | 0.247711E+10 | 0.00 | 0.69 |
March | 0.257180E+10 | 0.170432E+10 | 0.00 | 5189220.41 | 14564789.33 | 0.214579E+09 | 0.247680E+10 | 0.00 | 0.69 |
April | 0.193201E+09 | 0.401378E+10 | 0.00 | 6644288.12 | 26440017.67 | 0.00 | 0.275160E+10 | 0.00 | 0.74 |
May | 0.00 | 0.131947E+11 | 0.00 | 0.00 | 80897282.94 | 0.00 | 0.00 | 0.00 | 0.54 |
June | 0.00 | 0.147243E+11 | 0.00 | 0.00 | 84054841.11 | 0.00 | 0.00 | 0.00 | 0.54 |
July | 0.00 | 0.176559E+11 | 0.00 | 0.00 | 80107610.81 | 0.00 | 0.00 | 0.00 | 0.54 |
August | 0.00 | 0.164323E+11 | 0.00 | 0.00 | 82301022.45 | 0.00 | 0.00 | 0.00 | 0.54 |
September | 0.00 | 0.138579E+11 | 0.00 | 0.00 | 66718254.18 | 0.00 | 0.00 | 0.00 | 0.54 |
October | 66152891.84 | 0.106061E+11 | 0.00 | 4054422.17 | 47508077.10 | 0.00 | 0.124063E+10 | 0.00 | 0.62 |
November | 0.711302E+09 | 0.311956E+10 | 0.00 | 9535896.97 | 24710017.80 | 0.00 | 0.471105E+10 | 0.00 | 0.82 |
December | 0.318438E+10 | 0.187922E+10 | 0.00 | 5391962.28 | 23035541.93 | 0.100582E+09 | 0.361456E+10 | 0.00 | 0.68 |
Annual Sum or Average | 0.157595E+11 | 0.988584E+11 | 0.00 | 39061969.23 | 0.538389E+09 | 0.513600E+09 | 0.189926E+11 | 0.00 | 0.63 |
Minimum of Months | 0.00 | 0.728574E+09 | 0.00 | 0.00 | 1755684.82 | 0.00 | 0.00 | 0.00 | 0.54 |
Maximum of Months | 0.567589E+10 | 0.176559E+11 | 0.00 | 9535896.97 | 84054841.11 | 0.214579E+09 | 0.471105E+10 | 0.00 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.181072E+10 | 0.379605E+09 | 0.00 | 2204014.05 | 5057033.88 | 787510.22 | 0.122383E+10 | 0.00 | 0.54 |
February | 0.987770E+09 | 0.512325E+09 | 0.00 | 2561345.72 | 4614996.56 | 33889849.51 | 0.146010E+10 | 0.00 | 0.62 |
March | 0.790805E+09 | 0.892120E+09 | 0.00 | 2758820.95 | 15669723.32 | 63399382.49 | 0.144086E+10 | 0.00 | 0.61 |
April | 50743966.29 | 0.189069E+10 | 0.00 | 2862537.46 | 36238065.76 | 0.00 | 0.122432E+10 | 0.00 | 0.64 |
May | 0.00 | 0.577619E+10 | 0.00 | 0.00 | 58120554.04 | 0.00 | 0.00 | 0.00 | 0.44 |
June | 0.00 | 0.643261E+10 | 0.00 | 0.00 | 62194257.12 | 0.00 | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.761802E+10 | 0.00 | 0.00 | 56816845.84 | 0.00 | 0.00 | 0.00 | 0.44 |
August | 0.00 | 0.716771E+10 | 0.00 | 0.00 | 56900506.60 | 0.00 | 0.00 | 0.00 | 0.45 |
September | 0.00 | 0.603114E+10 | 0.00 | 0.00 | 51206088.11 | 0.00 | 0.00 | 0.00 | 0.44 |
October | 25183873.12 | 0.465765E+10 | 0.00 | 1664716.62 | 34493483.12 | 0.00 | 0.528488E+09 | 0.00 | 0.52 |
November | 0.162555E+09 | 0.144386E+10 | 0.00 | 4903280.32 | 19309291.71 | 0.00 | 0.243598E+10 | 0.00 | 0.77 |
December | 0.107381E+10 | 0.895658E+09 | 0.00 | 3365617.54 | 14533572.46 | 15102448.74 | 0.212713E+10 | 0.00 | 0.64 |
Annual Sum or Average | 0.490159E+10 | 0.436976E+11 | 0.00 | 20320332.67 | 0.415154E+09 | 0.113179E+09 | 0.104407E+11 | 0.00 | 0.54 |
Minimum of Months | 0.00 | 0.379605E+09 | 0.00 | 0.00 | 4614996.56 | 0.00 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 0.181072E+10 | 0.761802E+10 | 0.00 | 4903280.32 | 62194257.12 | 63399382.49 | 0.243598E+10 | 0.00 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.210313E+10 | 0.311810E+09 | 0.00 | 884917.44 | 9714784.94 | 39526781.28 | 0.413204E+09 | 0.00 | 0.48 |
February | 0.121361E+10 | 0.420963E+09 | 0.00 | 1307330.28 | 6461373.07 | 85257352.64 | 0.640288E+09 | 0.00 | 0.53 |
March | 0.103265E+10 | 0.759354E+09 | 0.00 | 1461367.17 | 18691883.99 | 93257332.73 | 0.715167E+09 | 0.00 | 0.54 |
April | 0.156181E+09 | 0.153135E+10 | 0.00 | 1982078.84 | 84442307.44 | 0.00 | 0.715726E+09 | 0.00 | 0.57 |
May | 0.00 | 0.484560E+10 | 0.00 | 4447.44 | 0.339298E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
June | 0.00 | 0.544591E+10 | 0.00 | 107703.84 | 0.391696E+09 | 0.00 | 247467.42 | 0.00 | 0.43 |
July | 0.00 | 0.627139E+10 | 0.00 | 51607.16 | 0.443141E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
August | 0.00 | 0.608694E+10 | 0.00 | 0.00 | 0.388632E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
September | 677203.94 | 0.497687E+10 | 0.00 | 204123.76 | 0.307260E+09 | 0.00 | 66539.78 | 0.00 | 0.42 |
October | 72449523.55 | 0.388808E+10 | 0.00 | 1938790.70 | 0.239470E+09 | 0.00 | 0.446843E+09 | 0.00 | 0.49 |
November | 0.393347E+09 | 0.121085E+10 | 0.00 | 3106756.46 | 70830835.06 | 0.00 | 0.138788E+10 | 0.00 | 0.64 |
December | 0.136862E+10 | 0.763672E+09 | 0.00 | 1746998.54 | 34636111.31 | 50078852.18 | 0.958739E+09 | 0.00 | 0.53 |
Annual Sum or Average | 0.634067E+10 | 0.365128E+11 | 0.00 | 12796121.63 | 0.233427E+10 | 0.268120E+09 | 0.527816E+10 | 0.00 | 0.49 |
Minimum of Months | 0.00 | 0.311810E+09 | 0.00 | 0.00 | 6461373.07 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.210313E+10 | 0.627139E+10 | 0.00 | 3106756.46 | 0.443141E+09 | 93257332.73 | 0.138788E+10 | 0.00 | 0.64 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.209736E+10 | 0.303256E+09 | 0.00 | 834718.45 | 9800828.06 | 49527768.99 | 0.378473E+09 | 0.00 | 0.48 |
February | 0.123890E+10 | 0.414611E+09 | 0.00 | 1217868.80 | 6362813.03 | 97609229.31 | 0.582771E+09 | 0.00 | 0.52 |
March | 0.103354E+10 | 0.753930E+09 | 0.00 | 1370296.95 | 18381233.09 | 0.103359E+09 | 0.682236E+09 | 0.00 | 0.53 |
April | 0.158684E+09 | 0.152903E+10 | 0.00 | 1946373.33 | 84219748.43 | 0.00 | 0.707353E+09 | 0.00 | 0.57 |
May | 0.00 | 0.485399E+10 | 0.00 | 1314.92 | 0.339008E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
June | 0.00 | 0.545763E+10 | 0.00 | 110624.95 | 0.390830E+09 | 0.00 | 253123.90 | 0.00 | 0.43 |
July | 0.00 | 0.629180E+10 | 0.00 | 38660.74 | 0.440388E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
August | 0.00 | 0.610207E+10 | 0.00 | 0.00 | 0.387457E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
September | 675561.77 | 0.499207E+10 | 0.00 | 185229.44 | 0.305908E+09 | 0.00 | 69624.60 | 0.00 | 0.42 |
October | 72057805.15 | 0.389871E+10 | 0.00 | 1950904.57 | 0.237056E+09 | 0.00 | 0.449812E+09 | 0.00 | 0.49 |
November | 0.400934E+09 | 0.120790E+10 | 0.00 | 3036144.77 | 71043818.94 | 0.00 | 0.137440E+10 | 0.00 | 0.64 |
December | 0.137052E+10 | 0.761427E+09 | 0.00 | 1632682.77 | 34963808.96 | 66629481.79 | 0.907004E+09 | 0.00 | 0.53 |
Annual Sum or Average | 0.637267E+10 | 0.365664E+11 | 0.00 | 12324819.69 | 0.232542E+10 | 0.317125E+09 | 0.508237E+10 | 0.00 | 0.49 |
Minimum of Months | 0.00 | 0.303256E+09 | 0.00 | 0.00 | 6362813.03 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.209736E+10 | 0.629180E+10 | 0.00 | 3036144.77 | 0.440388E+09 | 0.103359E+09 | 0.137440E+10 | 0.00 | 0.64 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.208377E+10 | 0.289718E+09 | 0.00 | 764008.49 | 10061862.23 | 64161499.66 | 0.346458E+09 | 0.00 | 0.48 |
February | 0.124458E+10 | 0.399414E+09 | 0.00 | 1096817.35 | 6115399.95 | 0.122163E+09 | 0.523874E+09 | 0.00 | 0.52 |
March | 0.107330E+10 | 0.737172E+09 | 0.00 | 1225904.47 | 17610366.43 | 0.104520E+09 | 0.614671E+09 | 0.00 | 0.53 |
April | 0.173013E+09 | 0.150540E+10 | 0.00 | 1822170.22 | 83520219.45 | 0.00 | 0.691448E+09 | 0.00 | 0.57 |
May | 0.00 | 0.481849E+10 | 0.00 | 3775.70 | 0.341795E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.542782E+10 | 0.00 | 96631.84 | 0.391077E+09 | 0.00 | 236891.29 | 0.00 | 0.43 |
July | 0.00 | 0.626170E+10 | 0.00 | 48315.81 | 0.440106E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
August | 0.00 | 0.607045E+10 | 0.00 | 0.00 | 0.388185E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
September | 695222.96 | 0.496106E+10 | 0.00 | 190184.58 | 0.306120E+09 | 0.00 | 66231.19 | 0.00 | 0.42 |
October | 75505245.69 | 0.387558E+10 | 0.00 | 1878510.10 | 0.237446E+09 | 0.00 | 0.436258E+09 | 0.00 | 0.49 |
November | 0.427404E+09 | 0.119246E+10 | 0.00 | 2845099.39 | 70591071.46 | 0.00 | 0.132452E+10 | 0.00 | 0.63 |
December | 0.138218E+10 | 0.749800E+09 | 0.00 | 1456288.19 | 34881428.92 | 79767790.93 | 0.836611E+09 | 0.00 | 0.52 |
Annual Sum or Average | 0.646045E+10 | 0.362891E+11 | 0.00 | 11427706.14 | 0.232751E+10 | 0.370612E+09 | 0.477414E+10 | 0.00 | 0.49 |
Minimum of Months | 0.00 | 0.289718E+09 | 0.00 | 0.00 | 6115399.95 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.208377E+10 | 0.626170E+10 | 0.00 | 2845099.39 | 0.440106E+09 | 0.122163E+09 | 0.132452E+10 | 0.00 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.387888E+10 | 0.497419E+09 | 0.00 | 1410694.18 | 15952129.37 | 48803811.89 | 0.718606E+09 | 0.00 | 0.44 |
February | 0.232193E+10 | 0.723508E+09 | 0.00 | 1786302.42 | 12134933.27 | 0.169144E+09 | 0.944822E+09 | 0.00 | 0.47 |
March | 0.187550E+10 | 0.131610E+10 | 0.00 | 1982690.30 | 32334358.75 | 0.204747E+09 | 0.116485E+10 | 0.00 | 0.48 |
April | 0.249888E+09 | 0.283176E+10 | 0.00 | 2784751.22 | 93421761.77 | 0.00 | 0.119969E+10 | 0.00 | 0.50 |
May | 0.00 | 0.915723E+10 | 0.00 | 0.00 | 0.253028E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
June | 0.00 | 0.104257E+11 | 0.00 | 0.00 | 0.254712E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
July | 0.00 | 0.118637E+11 | 0.00 | 0.00 | 0.364453E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.116248E+11 | 0.00 | 0.00 | 0.247210E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
September | 0.00 | 0.932801E+10 | 0.00 | 172575.34 | 0.276482E+09 | 0.00 | 25202653.72 | 0.00 | 0.39 |
October | 72052352.63 | 0.742322E+10 | 0.00 | 2748653.29 | 0.169975E+09 | 0.00 | 0.745598E+09 | 0.00 | 0.45 |
November | 0.578534E+09 | 0.227506E+10 | 0.00 | 5001350.21 | 56344665.35 | 0.00 | 0.253967E+10 | 0.00 | 0.56 |
December | 0.254616E+10 | 0.137301E+10 | 0.00 | 2316267.52 | 48261071.39 | 0.104109E+09 | 0.153263E+10 | 0.00 | 0.46 |
Annual Sum or Average | 0.115229E+11 | 0.688396E+11 | 0.00 | 18203284.50 | 0.182431E+10 | 0.526803E+09 | 0.887107E+10 | 0.00 | 0.44 |
Minimum of Months | 0.00 | 0.497419E+09 | 0.00 | 0.00 | 12134933.27 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.387888E+10 | 0.118637E+11 | 0.00 | 5001350.21 | 0.364453E+09 | 0.204747E+09 | 0.253967E+10 | 0.00 | 0.56 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.191980E+10 | 0.247124E+09 | 0.00 | 692898.88 | 7784403.78 | 36664912.34 | 0.352091E+09 | 0.00 | 0.45 |
February | 0.114640E+10 | 0.359423E+09 | 0.00 | 875818.88 | 5809922.97 | 0.103479E+09 | 0.468175E+09 | 0.00 | 0.47 |
March | 0.944123E+09 | 0.657271E+09 | 0.00 | 970927.37 | 15019549.86 | 0.110711E+09 | 0.561212E+09 | 0.00 | 0.48 |
April | 0.124563E+09 | 0.141829E+10 | 0.00 | 1386291.26 | 46787197.37 | 0.00 | 0.615572E+09 | 0.00 | 0.51 |
May | 0.00 | 0.458531E+10 | 0.00 | 0.00 | 0.122659E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
June | 0.00 | 0.521223E+10 | 0.00 | 0.00 | 0.128137E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
July | 0.00 | 0.592936E+10 | 0.00 | 0.00 | 0.176723E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.581371E+10 | 0.00 | 0.00 | 0.116036E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
September | 0.00 | 0.465555E+10 | 0.00 | 95703.79 | 0.137238E+09 | 0.00 | 14065696.64 | 0.00 | 0.39 |
October | 35156708.25 | 0.370837E+10 | 0.00 | 1376114.09 | 83419550.60 | 0.00 | 0.381961E+09 | 0.00 | 0.45 |
November | 0.296593E+09 | 0.113641E+10 | 0.00 | 2523591.48 | 27702828.41 | 0.00 | 0.129572E+10 | 0.00 | 0.58 |
December | 0.126811E+10 | 0.687489E+09 | 0.00 | 1129563.48 | 23087291.95 | 64722985.19 | 0.756962E+09 | 0.00 | 0.47 |
Annual Sum or Average | 0.573475E+10 | 0.344105E+11 | 0.00 | 9050909.23 | 0.890403E+09 | 0.315578E+09 | 0.444576E+10 | 0.00 | 0.45 |
Minimum of Months | 0.00 | 0.247124E+09 | 0.00 | 0.00 | 5809922.97 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.191980E+10 | 0.592936E+10 | 0.00 | 2523591.48 | 0.176723E+09 | 0.110711E+09 | 0.129572E+10 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.190347E+10 | 0.241799E+09 | 0.00 | 660512.50 | 9178680.85 | 48760282.59 | 0.344157E+09 | 0.00 | 0.45 |
February | 0.116388E+10 | 0.353662E+09 | 0.00 | 833054.36 | 6203482.70 | 0.115890E+09 | 0.428241E+09 | 0.00 | 0.47 |
March | 0.959659E+09 | 0.650325E+09 | 0.00 | 907629.48 | 14897876.29 | 0.114511E+09 | 0.528341E+09 | 0.00 | 0.48 |
April | 0.128734E+09 | 0.140852E+10 | 0.00 | 1344376.92 | 46512616.84 | 0.00 | 0.605177E+09 | 0.00 | 0.51 |
May | 0.00 | 0.457199E+10 | 0.00 | 0.00 | 0.122171E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
June | 0.00 | 0.519993E+10 | 0.00 | 0.00 | 0.127957E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
July | 0.00 | 0.591660E+10 | 0.00 | 0.00 | 0.176917E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.580187E+10 | 0.00 | 0.00 | 0.116142E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
September | 0.00 | 0.464378E+10 | 0.00 | 96709.32 | 0.136853E+09 | 0.00 | 15515771.79 | 0.00 | 0.39 |
October | 35929900.39 | 0.369895E+10 | 0.00 | 1356391.71 | 82687838.28 | 0.00 | 0.378116E+09 | 0.00 | 0.45 |
November | 0.306547E+09 | 0.112979E+10 | 0.00 | 2453832.66 | 28009013.56 | 0.00 | 0.127266E+10 | 0.00 | 0.57 |
December | 0.127512E+10 | 0.682122E+09 | 0.00 | 1072131.79 | 23396792.40 | 74635184.31 | 0.721595E+09 | 0.00 | 0.46 |
Annual Sum or Average | 0.577334E+10 | 0.342993E+11 | 0.00 | 8724638.74 | 0.890927E+09 | 0.353797E+09 | 0.429381E+10 | 0.00 | 0.44 |
Minimum of Months | 0.00 | 0.241799E+09 | 0.00 | 0.00 | 6203482.70 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.190347E+10 | 0.591660E+10 | 0.00 | 2453832.66 | 0.176917E+09 | 0.115890E+09 | 0.127266E+10 | 0.00 | 0.57 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.186907E+10 | 0.231128E+09 | 0.00 | 587217.85 | 11573740.39 | 91395030.92 | 0.309590E+09 | 0.00 | 0.44 |
February | 0.114174E+10 | 0.339769E+09 | 0.00 | 742204.79 | 6673107.25 | 0.158079E+09 | 0.382697E+09 | 0.00 | 0.47 |
March | 0.995779E+09 | 0.631362E+09 | 0.00 | 779105.74 | 14696071.04 | 0.120096E+09 | 0.458681E+09 | 0.00 | 0.48 |
April | 0.138792E+09 | 0.138158E+10 | 0.00 | 1234160.91 | 46513949.19 | 0.00 | 0.584582E+09 | 0.00 | 0.50 |
May | 0.00 | 0.455079E+10 | 0.00 | 0.00 | 0.124897E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
June | 0.00 | 0.518929E+10 | 0.00 | 0.00 | 0.128651E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
July | 0.00 | 0.591281E+10 | 0.00 | 0.00 | 0.176934E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.580205E+10 | 0.00 | 0.00 | 0.116622E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
September | 0.00 | 0.463913E+10 | 0.00 | 94028.53 | 0.135900E+09 | 0.00 | 15767653.11 | 0.00 | 0.39 |
October | 37907888.24 | 0.369058E+10 | 0.00 | 1295650.56 | 83873716.12 | 0.00 | 0.370886E+09 | 0.00 | 0.45 |
November | 0.327175E+09 | 0.111697E+10 | 0.00 | 2286100.84 | 29392364.86 | 0.00 | 0.122598E+10 | 0.00 | 0.57 |
December | 0.128932E+10 | 0.670775E+09 | 0.00 | 936424.17 | 24636287.48 | 0.107620E+09 | 0.632458E+09 | 0.00 | 0.46 |
Annual Sum or Average | 0.579979E+10 | 0.341562E+11 | 0.00 | 7954893.39 | 0.900363E+09 | 0.477190E+09 | 0.398064E+10 | 0.00 | 0.44 |
Minimum of Months | 0.00 | 0.231128E+09 | 0.00 | 0.00 | 6673107.25 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.186907E+10 | 0.591281E+10 | 0.00 | 2286100.84 | 0.176934E+09 | 0.158079E+09 | 0.122598E+10 | 0.00 | 0.57 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.174297E+10 | 0.227403E+09 | 0.00 | 541359.16 | 11821776.85 | 0.197773E+09 | 0.303263E+09 | 0.00 | 0.45 |
February | 0.103321E+10 | 0.332611E+09 | 0.00 | 693416.71 | 6496764.42 | 0.259762E+09 | 0.371353E+09 | 0.00 | 0.48 |
March | 0.931305E+09 | 0.628005E+09 | 0.00 | 749834.38 | 10827120.73 | 0.204261E+09 | 0.412889E+09 | 0.00 | 0.49 |
April | 0.151384E+09 | 0.136982E+10 | 0.00 | 1141564.26 | 41731247.08 | 0.00 | 0.602451E+09 | 0.00 | 0.52 |
May | 0.00 | 0.458975E+10 | 0.00 | 0.00 | 0.112519E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
June | 0.00 | 0.527773E+10 | 0.00 | 146.83 | 0.118610E+09 | 0.00 | 57134.48 | 0.00 | 0.39 |
July | 0.00 | 0.603701E+10 | 0.00 | 0.00 | 0.167657E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.592112E+10 | 0.00 | 0.00 | 0.107770E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
September | 0.00 | 0.473717E+10 | 0.00 | 52991.11 | 0.130344E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
October | 48180380.80 | 0.374779E+10 | 0.00 | 1296185.27 | 77871504.09 | 0.00 | 0.366420E+09 | 0.00 | 0.46 |
November | 0.331717E+09 | 0.112482E+10 | 0.00 | 2263400.24 | 24844164.50 | 0.00 | 0.124914E+10 | 0.00 | 0.60 |
December | 0.119557E+10 | 0.657513E+09 | 0.00 | 895132.70 | 20191379.82 | 0.228346E+09 | 0.570124E+09 | 0.00 | 0.47 |
Annual Sum or Average | 0.543434E+10 | 0.346507E+11 | 0.00 | 7634030.67 | 0.830684E+09 | 0.890143E+09 | 0.387569E+10 | 0.00 | 0.45 |
Minimum of Months | 0.00 | 0.227403E+09 | 0.00 | 0.00 | 6496764.42 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.174297E+10 | 0.603701E+10 | 0.00 | 2263400.24 | 0.167657E+09 | 0.259762E+09 | 0.124914E+10 | 0.00 | 0.60 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.206134E+12 | 0.149102E+11 | 0.00 | 0.285829E+11 | 0.313189E+11 |
February | 0.229930E+12 | 0.850400E+10 | 0.00 | 0.198604E+11 | 0.431609E+11 |
March | 0.262997E+12 | 0.495075E+10 | 0.00 | 0.139323E+11 | 0.607030E+11 |
April | 0.308515E+12 | -0.932348E+10 | 0.00 | -0.820779E+10 | 0.109539E+12 |
May | 0.314900E+12 | -0.370625E+11 | 0.00 | -0.628384E+11 | 0.236990E+12 |
June | 0.317177E+12 | -0.402489E+11 | 0.00 | -0.708700E+11 | 0.253902E+12 |
July | 0.326230E+12 | -0.471586E+11 | 0.00 | -0.822814E+11 | 0.282100E+12 |
August | 0.302103E+12 | -0.461621E+11 | 0.00 | -0.788302E+11 | 0.283172E+12 |
September | 0.253899E+12 | -0.393605E+11 | 0.00 | -0.646028E+11 | 0.246063E+12 |
October | 0.255783E+12 | -0.292464E+11 | 0.00 | -0.445713E+11 | 0.212120E+12 |
November | 0.187966E+12 | -0.192912E+10 | 0.00 | 0.742246E+10 | 0.872507E+11 |
December | 0.186571E+12 | 0.862336E+10 | 0.00 | 0.203022E+11 | 0.561535E+11 |
Annual Sum or Average | 0.315221E+13 | -0.213503E+12 | 0.00 | -0.322102E+12 | 0.190247E+13 |
Minimum of Months | 0.186571E+12 | -0.471586E+11 | 0.00 | -0.822814E+11 | 0.313189E+11 |
Maximum of Months | 0.326230E+12 | 0.149102E+11 | 0.00 | 0.285829E+11 | 0.283172E+12 |