Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:41
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885
Simulation Timestamp: 2023-10-16 08:41:10
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:10
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1263.92 | 604.66 | 604.66 |
Net Site Energy | 1263.92 | 604.66 | 604.66 |
Total Source Energy | 3290.00 | 1573.92 | 1573.92 |
Net Source Energy | 3290.00 | 1573.92 | 1573.92 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 342.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 12.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 441.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 100.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 174.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 65.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 921.70 | 342.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 342.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 12.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 441.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 100.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 174.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 65.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 342.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 12.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 441.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 100.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 174.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 65.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 259.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 120.29 | 163.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 440.94 | 163.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 259.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 120.29 | 163.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 440.94 | 163.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 921.703 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 921.703 | 100.00 |
Total On-Site and Utility Electric Sources | 921.703 | 100.00 |
Total Electricity End Uses | 921.703 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1504.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:10
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:41 |
RunPeriod | RUNPERIOD 1 |
Weather File | William R Fairchild WA USA TMY3 WMO#=727885 |
Latitude [deg] | 48.12 |
Longitude [deg] | -123.5 |
Elevation [m] | 91.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.77 | 20.77 | 17.8770 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.38 | 10.38 | 19.3382 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 17.3739 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 17.3739 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 17.3739 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.72 | 20.72 | 13.1675 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.3365 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.3365 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.3365 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.36 | 10.36 | 13.3365 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 15.5746 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 15.5746 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 17.8770 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 19.3382 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 17.3739 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 17.3739 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 17.3739 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 13.1675 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 13.3365 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 13.3365 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 13.3365 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 13.3365 | 6.19 | 4.3000 | |
Total | 2090.32 | 15.5746 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 15.5746 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 15.5746 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:10
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 22-JUL-12:00 | 10-JAN-09:09 | - | - | - | - | - | - | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 173467.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 21307.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 27522.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 10218.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 7028.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 74166.76 | 173467.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 173467.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 21307.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 27522.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 10218.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 7028.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:10
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 370.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 38.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1398.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 316.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 407.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 551.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 206.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2919.03 | 370.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 177.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 18.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 668.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 151.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 263.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 98.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1396.45 | 177.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 177.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 18.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 668.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 151.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 263.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 98.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1396.45 | 177.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:10
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 1.83 |
SMSTORE1 DIRECT AIR | 0.978667 |
SMSTORE2 DIRECT AIR | 0.957583 |
SMSTORE3 DIRECT AIR | 0.951958 |
SMSTORE4 DIRECT AIR | 0.957036 |
LGSTORE2 DIRECT AIR | 1.77 |
SMSTORE5 DIRECT AIR | 0.957474 |
SMSTORE6 DIRECT AIR | 0.951874 |
SMSTORE7 DIRECT AIR | 0.940951 |
SMSTORE8 DIRECT AIR | 0.972876 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 1.83 | 1.83 | 1.83 | 1.83 | 1.83 | 1.83 | 1.00 | 1.000000 | 1.83 |
PSZ-AC_2:2 | 0.978667 | 0.978667 | 0.978667 | 0.978667 | 0.990701 | 0.990701 | 1.00 | 0.987854 | 0.990701 |
PSZ-AC_3:3 | 0.957583 | 0.957583 | 0.957583 | 0.957583 | 0.976051 | 0.976051 | 1.00 | 0.981079 | 0.976051 |
PSZ-AC_4:4 | 0.951958 | 0.951958 | 0.951958 | 0.951958 | 0.979189 | 0.979189 | 1.00 | 0.972190 | 0.979189 |
PSZ-AC_5:5 | 0.957036 | 0.957036 | 0.957036 | 0.957036 | 0.974832 | 0.974832 | 1.00 | 0.981745 | 0.974832 |
PSZ-AC_6:6 | 1.77 | 1.77 | 1.77 | 1.77 | 1.81 | 1.81 | 1.00 | 0.977562 | 1.81 |
PSZ-AC_7:7 | 0.957474 | 0.957474 | 0.957474 | 0.957474 | 0.965498 | 0.965498 | 1.00 | 0.991690 | 0.965498 |
PSZ-AC_8:8 | 0.951874 | 0.951874 | 0.951874 | 0.951874 | 0.960267 | 0.960267 | 1.00 | 0.991259 | 0.960267 |
PSZ-AC_9:9 | 0.940951 | 0.940951 | 0.940951 | 0.940951 | 0.950845 | 0.950845 | 1.00 | 0.989595 | 0.950845 |
PSZ-AC_10:10 | 0.972876 | 0.972876 | 0.972876 | 0.972876 | 0.992648 | 0.992648 | 1.00 | 0.980082 | 0.992648 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 1.83 | 0.411479 |
PSZ-AC_2:2_OA_CONTROLLER | 0.990701 | 0.205739 |
PSZ-AC_3:3_OA_CONTROLLER | 0.976051 | 0.205739 |
PSZ-AC_4:4_OA_CONTROLLER | 0.979189 | 0.205739 |
PSZ-AC_5:5_OA_CONTROLLER | 0.974832 | 0.205739 |
PSZ-AC_6:6_OA_CONTROLLER | 1.81 | 0.411479 |
PSZ-AC_7:7_OA_CONTROLLER | 0.965498 | 0.205739 |
PSZ-AC_8:8_OA_CONTROLLER | 0.960267 | 0.205739 |
PSZ-AC_9:9_OA_CONTROLLER | 0.950845 | 0.205739 |
PSZ-AC_10:10_OA_CONTROLLER | 0.992648 | 0.205739 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 1.83 | 1953.47 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 0.990701 | 1096.86 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 0.976051 | 1080.64 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 0.979189 | 1084.12 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 0.974832 | 1079.29 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 1.81 | 1933.76 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 0.965498 | 1068.96 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 0.960267 | 1063.17 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 0.950845 | 1052.74 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 0.992648 | 1099.02 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 1.83 | 1.83 | 1.83 | 1.20 | 30219.97 | 53805.54 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 0.990701 | 0.990701 | 0.990701 | 0.990701 | 16399.62 | 28392.67 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 0.976051 | 0.976051 | 0.976051 | 0.976051 | 16157.11 | 27915.81 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 0.979189 | 0.979189 | 0.979189 | 0.979189 | 16209.06 | 27788.59 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 0.974832 | 0.974832 | 0.974832 | 0.974832 | 16136.92 | 27903.42 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 1.81 | 1.81 | 1.81 | 1.19 | 29915.06 | 52471.63 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 0.965498 | 0.965498 | 0.965498 | 0.965498 | 15982.41 | 27913.33 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 0.960267 | 0.960267 | 0.960267 | 0.960267 | 15895.83 | 27786.67 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 0.950845 | 0.950845 | 0.950845 | 0.950845 | 15739.86 | 27539.63 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 0.992648 | 0.992648 | 0.992648 | 0.992648 | 16431.85 | 28261.94 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 1.83 | 0.912794 | 1.22 | 30219.97 | 15109.99 | 0.800660 | 0.800660 |
PSZ-AC_2:2 COOLING COIL | 0.990700 | 0.495350 | 0.660467 | 16399.62 | 8199.81 | 0.800660 | 0.800660 |
PSZ-AC_3:3 COOLING COIL | 0.976050 | 0.488026 | 0.650700 | 16157.11 | 8078.56 | 0.800660 | 0.800660 |
PSZ-AC_4:4 COOLING COIL | 0.979190 | 0.489595 | 0.652793 | 16209.06 | 8104.53 | 0.800660 | 0.800660 |
PSZ-AC_5:5 COOLING COIL | 0.974830 | 0.487416 | 0.649887 | 16136.92 | 8068.46 | 0.800660 | 0.800660 |
PSZ-AC_6:6 COOLING COIL | 1.81 | 0.903584 | 1.20 | 29915.06 | 14957.53 | 0.800660 | 0.800660 |
PSZ-AC_7:7 COOLING COIL | 0.965500 | 0.482749 | 0.643667 | 15982.41 | 7991.20 | 0.800660 | 0.800660 |
PSZ-AC_8:8 COOLING COIL | 0.960270 | 0.480134 | 0.640180 | 15895.83 | 7947.91 | 0.800660 | 0.800660 |
PSZ-AC_9:9 COOLING COIL | 0.950840 | 0.475422 | 0.633893 | 15739.86 | 7869.93 | 0.800660 | 0.800660 |
PSZ-AC_10:10 COOLING COIL | 0.992650 | 0.496324 | 0.661767 | 16431.85 | 8215.92 | 0.800660 | 0.800660 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 53805.54 |
PSZ-AC_2:2 HEATING COIL | 28392.67 |
PSZ-AC_3:3 HEATING COIL | 27915.81 |
PSZ-AC_4:4 HEATING COIL | 27788.59 |
PSZ-AC_5:5 HEATING COIL | 27903.42 |
PSZ-AC_6:6 HEATING COIL | 52471.63 |
PSZ-AC_7:7 HEATING COIL | 27913.33 |
PSZ-AC_8:8 HEATING COIL | 27786.67 |
PSZ-AC_9:9 HEATING COIL | 27539.63 |
PSZ-AC_10:10 HEATING COIL | 28261.94 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:10
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:10
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:10
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.30 | 6.70 | 4.10 | 4.20 | 4.20 | 5.90 | 9.00 | 10.00 | 13.30 | 15.00 | 15.70 | 13.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | William R Fairchild WA USA TMY3 WMO#=727885 | 48.12 | -123.50 | -8.00 | 91.00 | 100237 | 1.1914 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.23 | 11.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.74 | 20.77 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.66 | 10.38 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.41 | 20.72 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.12 | 10.36 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 17.877 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.177 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 19.338 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 23.638 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 17.374 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.674 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 17.374 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.674 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 17.374 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.674 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 13.168 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.468 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 13.336 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.636 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 13.336 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.636 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 13.336 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.636 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 13.336 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.636 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 4596.695 | 13.194 | 81.718 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4596.695 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 1631.408 | 4.683 | 29.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1631.408 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 2327.780 | 13.363 | 82.767 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2327.780 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1040.795 | 5.975 | 37.007 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1040.795 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 2323.122 | 13.336 | 82.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2323.122 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 703.295 | 4.037 | 25.007 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 703.295 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 2323.122 | 13.336 | 82.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2323.122 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 703.295 | 4.037 | 25.007 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 703.295 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 2323.122 | 13.336 | 82.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2323.122 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 703.295 | 4.037 | 25.007 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 703.295 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 4587.379 | 13.168 | 81.553 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4587.379 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 2323.122 | 13.336 | 82.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2323.122 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 2323.122 | 13.336 | 82.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2323.122 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 2323.122 | 13.336 | 82.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2323.122 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 2323.122 | 13.336 | 82.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2323.122 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.6641 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1464 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2111 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.272 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.756 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.659 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
19 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
20 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
21 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
22 | 7 | -0.32972738E-12 | 0.11763143E-14 | -0.10490290E-12 | 0.10060316E-15 |
23 | 6 | 0.30001920E-07 | 0.18927851E-09 | 0.68616814E-08 | -0.14235861E-12 |
24 | 5 | -0.19683904E-03 | 0.16062604E-05 | -0.10115234E-03 | 0.67789156E-08 |
25 | 4 | 0.29998857 | 0.77587294E-03 | 0.10250533 | -0.34681058E-04 |
26 | 3 | -7.4215481 | 0.23875067E-01 | -2.3849775 | 0.29769922E-01 |
27 | 2 | 41.382972 | 0.84366340E-01 | 15.453844 | -0.33904133 |
28 | 1 | -80.937908 | 0.37867119E-01 | -29.310851 | 1.0869756 |
29 | 0 | 46.824336 | 0.75775345E-03 | 16.287225 | |
30 | 7 | -0.28997596E-08 | -0.17578320E-14 | 0.22751757E-14 | -0.53829073E-16 |
31 | 6 | 0.41991781E-05 | 0.27986603E-08 | 0.31940183E-02 | -0.26794102E-04 |
32 | 5 | -0.29588474E-03 | 0.16552611E-05 | -0.22396035 | 0.19582313E-02 |
33 | 4 | 0.67666006E-02 | 0.75295852E-04 | 4.8334724 | -0.45302727E-01 |
34 | 3 | -0.59297736E-01 | 0.59838054E-03 | -38.043598 | 0.39889893 |
35 | 2 | 0.21038411 | 0.99492606E-03 | 116.52712 | -1.4185167 |
36 | 1 | -0.30354941 | 0.30287292E-03 | -143.93272 | 2.0494576 |
37 | 0 | 0.14796861 | 0.73483799E-05 | 60.838472 | |
38 | 7 | -0.51571905E-08 | -0.97500959E-14 | 0.15789915E-14 | -0.32998988E-16 |
39 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
40 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
41 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
42 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
43 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
44 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
45 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
46 | 7 | -0.51571905E-08 | -0.97500958E-14 | 0.15789913E-14 | -0.32998984E-16 |
47 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
48 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
49 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
50 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
51 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
52 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
53 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
54 | 7 | -0.51571905E-08 | -0.97500959E-14 | 0.15789911E-14 | -0.32998980E-16 |
55 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
56 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
57 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
58 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
59 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
60 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
61 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
62 | 7 | -0.51571905E-08 | -0.97500959E-14 | 0.15789915E-14 | -0.32998988E-16 |
63 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
64 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
65 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
66 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
67 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
68 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
69 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
70 | 7 | -0.51571905E-08 | -0.97500958E-14 | 0.15789913E-14 | -0.32998984E-16 |
71 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
72 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
73 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
74 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
75 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
76 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
77 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
78 | 7 | -0.51571905E-08 | -0.97500957E-14 | 0.15789917E-14 | -0.32998991E-16 |
79 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
80 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
81 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
82 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
83 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
84 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
85 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
86 | 7 | -0.51571905E-08 | -0.97500959E-14 | 0.15789915E-14 | -0.32998988E-16 |
87 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
88 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
89 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
90 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
91 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
92 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
93 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
94 | 7 | -0.51571905E-08 | -0.97500958E-14 | 0.15789913E-14 | -0.32998984E-16 |
95 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
96 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
97 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
98 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
99 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
100 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
101 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
102 | 7 | -0.19967951E-08 | -0.58252365E-15 | 0.72897552E-14 | -0.10630581E-15 |
103 | 6 | 0.59274927E-05 | 0.40433693E-08 | 0.31889525E-02 | -0.26751606E-04 |
104 | 5 | -0.42514865E-03 | 0.23948505E-05 | -0.22367243 | 0.19556901E-02 |
105 | 4 | 0.97725356E-02 | 0.10900143E-03 | 4.8286774 | -0.45256634E-01 |
106 | 3 | -0.85796444E-01 | 0.86675557E-03 | -38.016512 | 0.39859954 |
107 | 2 | 0.30461848 | 0.14417950E-02 | 116.47440 | -1.4178116 |
108 | 1 | -0.43965446 | 0.43929230E-03 | -143.90169 | 2.0489476 |
109 | 0 | 0.21434897 | 0.10616597E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 35 | 1 | VerySmooth | 2.168 | 2.168 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 3.44376E-002 | 0.31435 | 0.47922 | 0.47922 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11914 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 0.157 | 4.517E-004 | 2.488E-004 | 0.314 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 3.813E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 8.993E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 4.692E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 0.112 | 6.453E-004 | 2.994E-004 | 0.448 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 3.583E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 20511.71641 | 24614.05970 | 1.52132 | 1.82559 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 26.40000 | 8.40708E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 18937.20245 | 22724.64294 | 0.82510 | 0.99012 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 11327.97667 | 13593.57201 | 0.81556 | 0.97867 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 22.94200 | 8.40167E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 8889.65010 | 10667.58012 | 0.38732 | 0.46479 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 11090.81693 | 13308.98032 | 0.79799 | 0.95758 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 21.39500 | 8.39928E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 8982.53319 | 10779.03982 | 0.39137 | 0.46964 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 11027.91792 | 13233.50150 | 0.79330 | 0.95196 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 21.39500 | 8.39928E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 9077.23107 | 10892.67729 | 0.39550 | 0.47460 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 11084.74305 | 13301.69166 | 0.79753 | 0.95704 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 21.39500 | 8.39928E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 9250.87284 | 11101.04741 | 0.40306 | 0.48367 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 20509.89449 | 24611.87339 | 1.47218 | 1.76662 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 22.94200 | 8.40167E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 17920.04457 | 21504.05349 | 0.78079 | 0.93694 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 11088.17386 | 13305.80863 | 0.79789 | 0.95747 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 22.94200 | 8.40167E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 9550.66823 | 11460.80188 | 0.41612 | 0.49935 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 11025.00036 | 13230.00044 | 0.79323 | 0.95187 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 22.94200 | 8.40167E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 9555.52689 | 11466.63227 | 0.41634 | 0.49960 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 10902.22573 | 13082.67087 | 0.78413 | 0.94095 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 22.94200 | 8.40167E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 9862.48907 | 11834.98689 | 0.42971 | 0.51565 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 11261.26559 | 13513.51870 | 0.81073 | 0.97288 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 22.94200 | 8.40167E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 12005.72146 | 14406.86575 | 0.52308 | 0.62770 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 25470.79 | 1.82559 | 1.82559 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 34909.63 | 0.99012 | 0.99012 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 13599.95 | 0.99070 | 0.99070 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 16770.18 | 0.46479 | 0.46479 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 13574.80 | 0.97605 | 0.97605 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 16880.02 | 0.46964 | 0.46964 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 13615.72 | 0.97919 | 0.97919 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 16992.00 | 0.47460 | 0.47460 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 13557.84 | 0.97483 | 0.97483 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 17197.34 | 0.48367 | 0.48367 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 25080.83 | 1.80717 | 1.80717 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 33706.88 | 0.93694 | 0.93694 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 12955.69 | 0.96550 | 0.96550 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 17551.85 | 0.49935 | 0.49935 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 12876.82 | 0.96027 | 0.96027 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 17557.60 | 0.49960 | 0.49960 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 12793.76 | 0.95084 | 0.95084 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 17920.59 | 0.51565 | 0.51565 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 13189.38 | 0.99265 | 0.99265 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 20454.94 | 0.62770 | 0.62770 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.82559 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.97867 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.95758 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.95196 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.95704 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.76662 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.95747 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.95187 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.94095 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.97288 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.82559 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.82559 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.82559 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.82559 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.82559 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.82559 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.97867 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.97867 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.97867 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.97867 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.99070 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.99070 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 0.98785 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.95758 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.95758 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.95758 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.95758 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.97605 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 0.97605 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 0.98108 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.95196 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.95196 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.95196 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.95196 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.97919 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 0.97919 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 0.97219 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.95704 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.95704 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.95704 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.95704 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.97483 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 0.97483 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 0.98174 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.76662 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.76662 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.76662 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.76662 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.80717 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 1.80717 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 0.97756 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.95747 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.95747 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.95747 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.95747 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.96550 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 0.96550 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 0.99169 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.95187 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.95187 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.95187 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.95187 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.96027 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 0.96027 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 0.99126 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.94095 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.94095 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.94095 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.94095 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.95084 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 0.95084 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 0.98959 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.97288 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.97288 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.97288 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.97288 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.99265 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 0.99265 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 0.98008 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 1.82559 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 0.99070 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 0.97605 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 0.97919 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 0.97483 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 1.80717 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 0.96550 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 0.96027 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 0.95084 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 0.99265 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.82559 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.82559 |
104 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1953.46583 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.82559 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.82559 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.82559 |
108 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.20489 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.82559 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.91279 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.21706 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 30219.97000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 15109.98500 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
116 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 30219.97000 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 53805.54429 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
120 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 53805.54429 |
121 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.99070 |
122 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
123 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.99070 |
124 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1096.86301 |
125 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.99070 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.99070 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.99070 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.99070 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.99070 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.49535 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.66047 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 16399.62000 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 8199.81000 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16399.62000 |
137 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28392.66801 |
138 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
139 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
140 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 28392.66801 |
141 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.97605 |
142 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
143 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.97605 |
144 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1080.64351 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.97605 |
146 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.97605 |
147 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.97605 |
148 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.97605 |
149 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.97605 |
150 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.48803 |
151 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.65070 |
152 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 16157.11000 |
153 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 8078.55500 |
154 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
156 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16157.11000 |
157 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27915.80584 |
158 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
159 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
160 | Coil:Heating:Fuel | PSZ-AC_3:3 HEATING COIL | Design Size Nominal Capacity [W] | 27915.80584 |
161 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.97919 |
162 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
163 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.97919 |
164 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1084.11790 |
165 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.97919 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.97919 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.97919 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.97919 |
169 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.97919 |
170 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.48959 |
171 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.65279 |
172 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 16209.06000 |
173 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 8104.53000 |
174 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
175 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16209.06000 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27788.58566 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
179 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
180 | Coil:Heating:Fuel | PSZ-AC_4:4 HEATING COIL | Design Size Nominal Capacity [W] | 27788.58566 |
181 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.97483 |
182 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
183 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.97483 |
184 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1079.29332 |
185 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.97483 |
186 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.97483 |
187 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.97483 |
188 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.97483 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.97483 |
190 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.48742 |
191 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.64989 |
192 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 16136.92000 |
193 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 8068.46000 |
194 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
195 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
196 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16136.92000 |
197 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27903.42168 |
198 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
200 | Coil:Heating:Fuel | PSZ-AC_5:5 HEATING COIL | Design Size Nominal Capacity [W] | 27903.42168 |
201 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.80717 |
202 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
203 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.80717 |
204 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1933.75598 |
205 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.80717 |
206 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.80717 |
207 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.80717 |
208 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.19273 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.80717 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.90358 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.20478 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 29915.06000 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 14957.53000 |
214 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
215 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 29915.06000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 52471.62537 |
218 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
219 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
220 | Coil:Heating:Fuel | PSZ-AC_6:6 HEATING COIL | Design Size Nominal Capacity [W] | 52471.62537 |
221 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.96550 |
222 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
223 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.96550 |
224 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1068.95906 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.96550 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.96550 |
227 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.96550 |
228 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.96550 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.96550 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.48275 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.64367 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 15982.41000 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 7991.20500 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
236 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 15982.41000 |
237 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27913.33425 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
240 | Coil:Heating:Fuel | PSZ-AC_7:7 HEATING COIL | Design Size Nominal Capacity [W] | 27913.33425 |
241 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.96027 |
242 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
243 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.96027 |
244 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1063.16835 |
245 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.96027 |
246 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.96027 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.96027 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.96027 |
249 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.96027 |
250 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.48013 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.64018 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 15895.83000 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 7947.91500 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
256 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 15895.83000 |
257 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27786.67046 |
258 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
259 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
260 | Coil:Heating:Fuel | PSZ-AC_8:8 HEATING COIL | Design Size Nominal Capacity [W] | 27786.67046 |
261 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.95084 |
262 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
263 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.95084 |
264 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1052.73624 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.95084 |
266 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.95084 |
267 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.95084 |
268 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.95084 |
269 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.95084 |
270 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.47542 |
271 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.63389 |
272 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 15739.86000 |
273 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 7869.93000 |
274 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 15739.86000 |
277 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27539.63143 |
278 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
279 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
280 | Coil:Heating:Fuel | PSZ-AC_9:9 HEATING COIL | Design Size Nominal Capacity [W] | 27539.63143 |
281 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.99265 |
282 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
283 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.99265 |
284 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1099.01877 |
285 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.99265 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.99265 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.99265 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.99265 |
289 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.99265 |
290 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.49632 |
291 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.66177 |
292 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 16431.85000 |
293 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 8215.92500 |
294 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
295 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16431.85000 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28261.93878 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
299 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
300 | Coil:Heating:Fuel | PSZ-AC_10:10 HEATING COIL | Design Size Nominal Capacity [W] | 28261.93878 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 28789.2 | 11.11 | 11.11 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 15623.2 | 11.83 | 11.83 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | 15392.2 | 11.83 | 11.83 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | 15441.7 | 11.83 | 11.83 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | 15372.9 | 11.83 | 11.83 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | 28498.8 | 11.11 | 11.11 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | 15225.7 | 11.83 | 11.83 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | 15143.3 | 11.83 | 11.83 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | 14994.7 | 11.83 | 11.83 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | 15653.9 | 11.83 | 11.83 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 58.18 | 78.94 | 58.18 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.146 | 0.141 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.09 | 39.47 | 29.09 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 58.22 | 78.94 | 58.22 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.211 | 0.201 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 2.2883960613E-002 | 0.1093073593 | Pass | Pass | 0.1177340295 | 0.3470665731 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 4.1206518488E-002 | 8.6890352687E-002 | Pass | Pass | 0.2424562768 | 1.3346115181 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 2.5236045474E-002 | 7.0782478007E-002 | Pass | Pass | 6.8865532411E-002 | 0.2522328238 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 3.1454946360E-002 | 0.1120519936 | Pass | Pass | 0.4593989341 | 4.0567309091 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 3.4454519037E-002 | 0.1289090654 | Pass | Pass | 0.1519044846 | 0.6129998066 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 4.2866795819E-002 | 0.1790169158 | Pass | Pass | 7.3138743503E-002 | 0.2186892235 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 4.2994949060E-002 | 0.1466103444 | Pass | Pass | 7.5684699692E-002 | 0.2431633946 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 4.4683471043E-002 | 0.1574351069 | Pass | Pass | 7.6539671616E-002 | 0.2710558609 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 5.1508365823E-002 | 0.2240075242 | Pass | Pass | 8.2760259940E-002 | 0.3052638828 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 7.3418404969E-002 | 0.2875191014 | Pass | Pass | 9.9538144240E-002 | 0.4508150076 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:10
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3507.33 | 227.27 | 0.00 | 723.96 | 133.25 | 4591.84 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:10
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | -4.30 | 0.00 | -4.30 | Wetbulb [C] | 1.20 | 110.00 |
WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 26.40 | 9.10 | 17.00 | Wetbulb [C] | 2.10 | 90.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 42.00 | 35 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 40.00 | 22 | |||
Jun | 4.00 | 8 | |||
Jul | 5.00 | 4 | |||
Aug | 7.00 | 8 | |||
Sep | 17.00 | 10 | |||
Oct | 50.00 | 49 | |||
Nov | 69.00 | 59 | |||
Dec | 95.00 | 53 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:10
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 78.94 | 58.18 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.143 | 0.146 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.09 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.082 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.082 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.082 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.082 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 78.94 | 58.22 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.082 | 0.083 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.082 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.082 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.082 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.204 | 0.211 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.168 | 0.401 | 0.402 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.168 | 0.401 | 0.402 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.168 | 0.401 | 0.402 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.168 | 0.401 | 0.402 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.168 | 0.401 | 0.402 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.168 | 0.401 | 0.402 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.168 | 0.401 | 0.402 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.168 | 0.401 | 0.402 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.168 | 0.401 | 0.402 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.168 | 0.401 | 0.402 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.168 | 0.401 | 0.402 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.168 | 0.401 | 0.402 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 124.40 | 2.168 | 0.401 | 0.402 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 124.40 | 2.168 | 0.401 | 0.402 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:10
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:10
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 13.1942 | 348.39 | 4596.69 | LightsWired | LTG_SCH_BASE_LPD1 | 84.21 | 168.00 | 84.19 | 0.0000 | Y | 72.65 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 4.6828 | 348.39 | 1631.41 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 168.00 | 97.48 | 0.0000 | Y | 29.85 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 13.3632 | 174.19 | 2327.78 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 85.70 | 168.00 | 85.69 | 0.0000 | Y | 37.44 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 5.9749 | 174.19 | 1040.80 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 168.00 | 97.48 | 0.0000 | Y | 19.04 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 13.3365 | 174.19 | 2323.12 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 29.75 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 4.0374 | 174.19 | 703.30 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 10.29 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 13.3365 | 174.19 | 2323.12 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 29.75 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 4.0374 | 174.19 | 703.30 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 10.29 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 13.3365 | 174.19 | 2323.12 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 29.75 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 4.0374 | 174.19 | 703.30 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 10.29 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 13.1675 | 348.39 | 4587.38 | LightsWired | LTG_SCH_BASE_LPD2 | 62.11 | 168.00 | 61.60 | 0.0000 | Y | 53.05 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 13.3365 | 174.19 | 2323.12 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 27.34 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 13.3365 | 174.19 | 2323.12 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 27.34 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 13.3365 | 174.19 | 2323.12 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 27.34 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 13.3365 | 174.19 | 2323.12 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 27.34 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 7.7873 | 4180.64 | 32555.80 | 441.52 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 345.19 | AstronomicalClock | - | 42.50 | 42.50 | 2.75 | |
EXTERIOR_LIGHTS_B | 7274.32 | AstronomicalClock | - | 83.54 | 71.23 | 97.26 | |
Exterior Lighting Total | 7619.51 | 100.01 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:10
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 30219.97 | 24195.92 | 6024.05 | 0.80 | 3.80 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 16399.62 | 13130.52 | 3269.10 | 0.80 | 4.12 | |||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 16157.11 | 12936.35 | 3220.76 | 0.80 | 4.12 | |||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 16209.06 | 12977.95 | 3231.11 | 0.80 | 4.12 | |||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 16136.92 | 12920.19 | 3216.73 | 0.80 | 4.12 | |||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 29915.06 | 23951.79 | 5963.27 | 0.80 | 3.80 | |||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 15982.41 | 12796.48 | 3185.93 | 0.80 | 4.12 | |||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 15895.83 | 12727.16 | 3168.67 | 0.80 | 4.12 | |||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 15739.86 | 12602.28 | 3137.58 | 0.80 | 4.12 | |||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 16431.85 | 13156.33 | 3275.52 | 0.80 | 4.12 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 28789.2 | 11.11 | 11.11 | ||||
PSZ-AC_2:2 COOLING COIL | 15623.2 | 11.83 | 11.83 | ||||
PSZ-AC_3:3 COOLING COIL | 15392.2 | 11.83 | 11.83 | ||||
PSZ-AC_4:4 COOLING COIL | 15441.7 | 11.83 | 11.83 | ||||
PSZ-AC_5:5 COOLING COIL | 15372.9 | 11.83 | 11.83 | ||||
PSZ-AC_6:6 COOLING COIL | 28498.8 | 11.11 | 11.11 | ||||
PSZ-AC_7:7 COOLING COIL | 15225.7 | 11.83 | 11.83 | ||||
PSZ-AC_8:8 COOLING COIL | 15143.3 | 11.83 | 11.83 | ||||
PSZ-AC_9:9 COOLING COIL | 14994.7 | 11.83 | 11.83 | ||||
PSZ-AC_10:10 COOLING COIL | 15653.9 | 11.83 | 11.83 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 53805.54 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 28392.67 | 0.80 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | 27915.81 | 0.80 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | 27788.59 | 0.80 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | 27903.42 | 0.80 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | 52471.63 | 0.80 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | 27913.33 | 0.80 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | 27786.67 | 0.80 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | 27539.63 | 0.80 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | 28261.94 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.83 | 1953.47 | 1070.05 | 1.00 | 1.33 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.99 | 1096.86 | 1107.16 | 1.00 | 1.40 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.98 | 1080.64 | 1107.16 | 1.00 | 1.41 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.98 | 1084.12 | 1107.16 | 1.00 | 1.41 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.97 | 1079.29 | 1107.16 | 1.00 | 1.41 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.81 | 1933.76 | 1070.05 | 1.00 | 1.33 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.97 | 1068.96 | 1107.16 | 1.00 | 1.41 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.96 | 1063.17 | 1107.16 | 1.00 | 1.41 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.95 | 1052.74 | 1107.16 | 1.00 | 1.42 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.99 | 1099.02 | 1107.16 | 1.00 | 1.40 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:10
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 20511.72 | 24614.06 | 70.65 | 1.521 | 1.826 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 23.89 | 23.89 | 0.00901 | 26.40 | 0.00841 | 0.411 | 0.00 |
SMSTORE1 | 11327.98 | 13593.57 | 78.04 | 0.816 | 0.979 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00929 | 22.94 | 0.00840 | 0.206 | 0.00 |
SMSTORE2 | 11090.82 | 13308.98 | 76.40 | 0.798 | 0.958 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.89 | 23.88 | 0.00975 | 21.39 | 0.00840 | 0.206 | 0.00 |
SMSTORE3 | 11027.92 | 13233.50 | 75.97 | 0.793 | 0.952 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.89 | 23.88 | 0.00970 | 21.39 | 0.00840 | 0.206 | 0.00 |
SMSTORE4 | 11084.74 | 13301.69 | 76.36 | 0.798 | 0.957 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.89 | 23.88 | 0.00973 | 21.39 | 0.00840 | 0.206 | 0.00 |
LGSTORE2 | 20509.89 | 24611.87 | 70.65 | 1.472 | 1.767 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00951 | 22.94 | 0.00840 | 0.411 | 0.00 |
SMSTORE5 | 11088.17 | 13305.81 | 76.39 | 0.798 | 0.957 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00940 | 22.94 | 0.00840 | 0.206 | 0.00 |
SMSTORE6 | 11025.00 | 13230.00 | 75.95 | 0.793 | 0.952 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00942 | 22.94 | 0.00840 | 0.206 | 0.00 |
SMSTORE7 | 10902.23 | 13082.67 | 75.10 | 0.784 | 0.941 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00943 | 22.94 | 0.00840 | 0.206 | 0.00 |
SMSTORE8 | 11261.27 | 13513.52 | 77.58 | 0.811 | 0.973 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00935 | 22.94 | 0.00840 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 18937.20 | 22724.64 | 65.23 | 0.825 | 0.990 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00683 | -4.30 | 0.00266 | 0.411 | 0.00 |
SMSTORE1 | 8889.65 | 10667.58 | 61.24 | 0.387 | 0.465 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00670 | -4.30 | 0.00266 | 0.206 | 0.00 |
SMSTORE2 | 8982.53 | 10779.04 | 61.88 | 0.391 | 0.470 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00671 | -4.30 | 0.00266 | 0.206 | 0.00 |
SMSTORE3 | 9077.23 | 10892.68 | 62.53 | 0.395 | 0.475 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00671 | -4.30 | 0.00266 | 0.206 | 0.00 |
SMSTORE4 | 9250.87 | 11101.05 | 63.73 | 0.403 | 0.484 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00673 | -4.30 | 0.00266 | 0.206 | 0.00 |
LGSTORE2 | 17920.04 | 21504.05 | 61.72 | 0.781 | 0.937 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00681 | -4.30 | 0.00266 | 0.411 | 0.00 |
SMSTORE5 | 9550.67 | 11460.80 | 65.79 | 0.416 | 0.499 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00675 | -4.30 | 0.00266 | 0.206 | 0.00 |
SMSTORE6 | 9555.53 | 11466.63 | 65.83 | 0.416 | 0.500 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00675 | -4.30 | 0.00266 | 0.206 | 0.00 |
SMSTORE7 | 9862.49 | 11834.99 | 67.94 | 0.430 | 0.516 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00678 | -4.30 | 0.00266 | 0.206 | 0.00 |
SMSTORE8 | 12005.72 | 14406.87 | 82.71 | 0.523 | 0.628 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00687 | -4.30 | 0.00266 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 1.83 | 1.83 | 0.99 | 0.99 | 1.8256 | 1.8256 | 1.8256 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 0.99 | 0.99 | 0.46 | 0.46 | 0.9907 | 0.9787 | 0.9907 | 0.9879 | 1.0000 |
PSZ-AC_3:3 | 0.98 | 0.98 | 0.47 | 0.47 | 0.9761 | 0.9576 | 0.9761 | 0.9811 | 1.0000 |
PSZ-AC_4:4 | 0.98 | 0.98 | 0.47 | 0.47 | 0.9792 | 0.9520 | 0.9792 | 0.9722 | 1.0000 |
PSZ-AC_5:5 | 0.97 | 0.97 | 0.48 | 0.48 | 0.9748 | 0.9570 | 0.9748 | 0.9817 | 1.0000 |
PSZ-AC_6:6 | 1.81 | 1.81 | 0.94 | 0.94 | 1.8072 | 1.7666 | 1.8072 | 0.9776 | 1.0000 |
PSZ-AC_7:7 | 0.97 | 0.97 | 0.50 | 0.50 | 0.9655 | 0.9575 | 0.9655 | 0.9917 | 1.0000 |
PSZ-AC_8:8 | 0.96 | 0.96 | 0.50 | 0.50 | 0.9603 | 0.9519 | 0.9603 | 0.9913 | 1.0000 |
PSZ-AC_9:9 | 0.95 | 0.95 | 0.52 | 0.52 | 0.9508 | 0.9410 | 0.9508 | 0.9896 | 1.0000 |
PSZ-AC_10:10 | 0.99 | 0.99 | 0.63 | 0.63 | 0.9926 | 0.9729 | 0.9926 | 0.9801 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 30219.970 | 24195.921 | 1.825590 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 15109.99 | 14160.78 | 1.217060 | 25.33 | 17.06 | 0.00887312 | 12.80 | 12.00 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 33.8092 | 23.89 | 0.00900873 | 48.2641 | 20511.72 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 53805.544 | 53805.544 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 53805.54 | 53805.54 | 1.825588 | 15.38 | 10.41 | 0.00588608 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 22.5395 | 21.11 | 0.00682551 | 43.4525 | 18937.20 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 16399.620 | 13130.520 | 0.990700 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 8199.81 | 7708.39 | 0.660467 | 25.33 | 17.04 | 0.00885469 | 12.80 | 12.00 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 31.1506 | 23.89 | 0.00897395 | 48.0802 | 10987.65 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 28392.668 | 28392.668 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28392.67 | 28392.67 | 0.990701 | 15.83 | 10.57 | 0.00585865 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 20.7671 | 21.11 | 0.00669765 | 42.6474 | 8889.65 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 16157.110 | 12936.352 | 0.976050 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 8078.56 | 7593.93 | 0.650700 | 25.33 | 17.04 | 0.00885508 | 12.80 | 12.00 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 31.6182 | 23.89 | 0.00897474 | 48.0843 | 11090.82 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 27915.806 | 27915.806 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 27915.81 | 27915.81 | 0.976051 | 15.75 | 10.53 | 0.00585222 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 21.0788 | 21.11 | 0.00670546 | 42.6967 | 8982.53 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 16209.060 | 12977.946 | 0.979190 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 8104.53 | 7619.12 | 0.652793 | 25.33 | 17.04 | 0.00885444 | 12.80 | 12.00 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 31.5168 | 23.89 | 0.00897345 | 48.0775 | 11027.92 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 27788.586 | 27788.586 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 27788.59 | 27788.59 | 0.979189 | 15.77 | 10.55 | 0.00586121 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 21.0112 | 21.11 | 0.00671338 | 42.7466 | 9077.23 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 16136.920 | 12920.186 | 0.974830 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 8068.46 | 7584.13 | 0.649887 | 25.33 | 17.04 | 0.00885534 | 12.80 | 12.00 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 31.6577 | 23.89 | 0.00897527 | 48.0871 | 11084.74 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 27903.422 | 27903.422 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 27903.42 | 27903.42 | 0.974832 | 15.75 | 10.55 | 0.00586908 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 21.1051 | 21.11 | 0.00672818 | 42.8398 | 9250.87 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 29915.060 | 23951.792 | 1.807170 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 14957.53 | 14005.06 | 1.204780 | 25.34 | 17.07 | 0.00887882 | 12.80 | 12.00 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 34.1539 | 23.89 | 0.00901900 | 48.3183 | 20181.64 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 52471.625 | 52471.625 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 52471.63 | 52471.63 | 1.807169 | 15.32 | 10.36 | 0.00586778 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 22.7693 | 21.11 | 0.00681421 | 43.3810 | 17920.04 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 15982.410 | 12796.476 | 0.965500 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 7991.20 | 7500.27 | 0.643667 | 25.35 | 17.06 | 0.00886488 | 12.80 | 12.00 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 31.9637 | 23.89 | 0.00899504 | 48.1915 | 11088.17 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 27913.334 | 27913.334 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 27913.33 | 27913.33 | 0.965498 | 15.69 | 10.53 | 0.00587931 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 21.3092 | 21.11 | 0.00675174 | 42.9883 | 9550.67 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 15895.830 | 12727.155 | 0.960270 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 7947.91 | 7458.16 | 0.640180 | 25.36 | 17.06 | 0.00886616 | 12.80 | 12.00 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 32.1377 | 23.89 | 0.00899776 | 48.2059 | 11025.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 27786.670 | 27786.670 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 27786.67 | 27786.67 | 0.960267 | 15.66 | 10.52 | 0.00587491 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 21.4252 | 21.11 | 0.00675219 | 42.9911 | 9555.53 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 15739.860 | 12602.276 | 0.950840 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 7869.93 | 7383.44 | 0.633893 | 25.36 | 17.07 | 0.00886750 | 12.80 | 12.00 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 32.4565 | 23.89 | 0.00900065 | 48.2211 | 10902.23 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 27539.631 | 27539.631 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 27539.63 | 27539.63 | 0.950845 | 15.61 | 10.50 | 0.00588464 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 21.6375 | 21.11 | 0.00677570 | 43.1393 | 9862.49 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 16431.850 | 13156.325 | 0.992650 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 8215.92 | 7717.33 | 0.661767 | 25.24 | 17.02 | 0.00885726 | 12.80 | 12.00 | 0.00850000 | 25.95 | 0.00840636 | 16.88 | 31.0894 | 23.89 | 0.00898100 | 48.1174 | 11261.27 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 28261.939 | 28261.939 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28261.94 | 28261.94 | 0.992648 | 15.84 | 10.72 | 0.00599895 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 20.7263 | 21.11 | 0.00687256 | 43.7502 | 12005.72 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:41:10
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 30219.970 | 24195.921 | 1.825590 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3347 | 1004.8586 | 1.1914 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.825588 | 2.17495487 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | Sensible | 15109.99 | 14160.78 | 1.0000 | 1.44997122 | 1.217060 | 25.33 | 17.06 | 0.00887312 | 48065.4 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15109.99 | 26.40 | 0.00840708 | 17.04 | 0.41147883 | 33.8092 | 23.89 | 0.00900873 | 23.89 | 0.00900873 | 48.2641 | 20511.72 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 53805.544 | 53805.544 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.825588 | 2.17495487 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 53805.54 | 53805.54 | 1.0000 | 2.17495487 | 1.825588 | 15.38 | 10.41 | 0.00588608 | 30344.4 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 53805.54 | -4.30 | 0.00265759 | -4.30 | 0.41147883 | 22.5395 | 21.11 | 0.00682551 | 21.11 | 0.00682551 | 43.4525 | 18937.20 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 16399.620 | 13130.520 | 0.990700 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3004 | 1004.8586 | 1.1914 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.990701 | 1.18029316 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | Sensible | 8199.81 | 7708.39 | 1.0000 | 0.78686150 | 0.660467 | 25.33 | 17.04 | 0.00885469 | 48011.1 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8199.81 | 26.40 | 0.00840708 | 17.04 | 0.20573941 | 31.1506 | 23.89 | 0.00897395 | 23.89 | 0.00897395 | 48.0802 | 10987.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28392.668 | 28392.668 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.990701 | 1.18029316 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 28392.67 | 28392.67 | 1.0000 | 1.18029316 | 0.990701 | 15.83 | 10.57 | 0.00585865 | 30732.4 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28392.67 | -4.30 | 0.00265759 | -4.30 | 0.20573941 | 20.7671 | 21.11 | 0.00669765 | 21.11 | 0.00669765 | 42.6474 | 8889.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 16157.110 | 12936.352 | 0.976050 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3012 | 1004.8586 | 1.1914 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.976051 | 1.16283997 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 8078.56 | 7593.93 | 1.0000 | 0.77522577 | 0.650700 | 25.33 | 17.04 | 0.00885508 | 48013.2 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8078.56 | 26.40 | 0.00840708 | 17.04 | 0.20573941 | 31.6182 | 23.89 | 0.00897474 | 23.89 | 0.00897474 | 48.0843 | 11090.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27915.806 | 27915.806 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.976051 | 1.16283997 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 27915.81 | 27915.81 | 1.0000 | 1.16283997 | 0.976051 | 15.75 | 10.53 | 0.00585222 | 30635.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27915.81 | -4.30 | 0.00265759 | -4.30 | 0.20573941 | 21.0788 | 21.11 | 0.00670546 | 21.11 | 0.00670546 | 42.6967 | 8982.53 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 16209.060 | 12977.946 | 0.979190 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3000 | 1004.8586 | 1.1914 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.979189 | 1.16657863 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 8104.53 | 7619.12 | 1.0000 | 0.77771971 | 0.652793 | 25.33 | 17.04 | 0.00885444 | 48009.8 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8104.53 | 26.40 | 0.00840708 | 17.04 | 0.20573941 | 31.5168 | 23.89 | 0.00897345 | 23.89 | 0.00897345 | 48.0775 | 11027.92 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27788.586 | 27788.586 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.979189 | 1.16657863 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 27788.59 | 27788.59 | 1.0000 | 1.16657863 | 0.979189 | 15.77 | 10.55 | 0.00586121 | 30675.9 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27788.59 | -4.30 | 0.00265759 | -4.30 | 0.20573941 | 21.0112 | 21.11 | 0.00671338 | 21.11 | 0.00671338 | 42.7466 | 9077.23 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 16136.920 | 12920.186 | 0.974830 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3016 | 1004.8586 | 1.1914 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.974832 | 1.16138708 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 8068.46 | 7584.13 | 1.0000 | 0.77425679 | 0.649887 | 25.33 | 17.04 | 0.00885534 | 48014.6 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8068.46 | 26.40 | 0.00840708 | 17.04 | 0.20573941 | 31.6577 | 23.89 | 0.00897527 | 23.89 | 0.00897527 | 48.0871 | 11084.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27903.422 | 27903.422 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.974832 | 1.16138708 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 27903.42 | 27903.42 | 1.0000 | 1.16138708 | 0.974832 | 15.75 | 10.55 | 0.00586908 | 30671.5 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27903.42 | -4.30 | 0.00265759 | -4.30 | 0.20573941 | 21.1051 | 21.11 | 0.00672818 | 21.11 | 0.00672818 | 42.8398 | 9250.87 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 29915.060 | 23951.792 | 1.807170 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3453 | 1004.8586 | 1.1914 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.807169 | 2.15301026 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | Sensible | 14957.53 | 14005.06 | 1.0000 | 1.43534117 | 1.204780 | 25.34 | 17.07 | 0.00887882 | 48089.3 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14957.53 | 26.40 | 0.00840708 | 17.04 | 0.41147883 | 34.1539 | 23.89 | 0.00901900 | 23.89 | 0.00901900 | 48.3183 | 20181.64 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 52471.625 | 52471.625 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.807169 | 2.15301026 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 52471.63 | 52471.63 | 1.0000 | 2.15301026 | 1.807169 | 15.32 | 10.36 | 0.00586778 | 30238.9 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 52471.63 | -4.30 | 0.00265759 | -4.30 | 0.41147883 | 22.7693 | 21.11 | 0.00681421 | 21.11 | 0.00681421 | 43.3810 | 17920.04 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 15982.410 | 12796.476 | 0.965500 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3194 | 1004.8586 | 1.1914 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.965498 | 1.15026677 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | Sensible | 7991.20 | 7500.27 | 1.0000 | 0.76684645 | 0.643667 | 25.35 | 17.06 | 0.00886488 | 48065.3 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7991.20 | 26.40 | 0.00840708 | 17.04 | 0.20573941 | 31.9637 | 23.89 | 0.00899504 | 23.89 | 0.00899504 | 48.1915 | 11088.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27913.334 | 27913.334 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.965498 | 1.15026677 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 27913.33 | 27913.33 | 1.0000 | 1.15026677 | 0.965498 | 15.69 | 10.53 | 0.00587931 | 30644.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27913.33 | -4.30 | 0.00265759 | -4.30 | 0.20573941 | 21.3092 | 21.11 | 0.00675174 | 21.11 | 0.00675174 | 42.9883 | 9550.67 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 15895.830 | 12727.155 | 0.960270 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3217 | 1004.8586 | 1.1914 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.960267 | 1.14403561 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | Sensible | 7947.91 | 7458.16 | 1.0000 | 0.76269253 | 0.640180 | 25.36 | 17.06 | 0.00886616 | 48072.2 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7947.91 | 26.40 | 0.00840708 | 17.04 | 0.20573941 | 32.1377 | 23.89 | 0.00899776 | 23.89 | 0.00899776 | 48.2059 | 11025.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27786.670 | 27786.670 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.960267 | 1.14403561 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 27786.67 | 27786.67 | 1.0000 | 1.14403561 | 0.960267 | 15.66 | 10.52 | 0.00587491 | 30603.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27786.67 | -4.30 | 0.00265759 | -4.30 | 0.20573941 | 21.4252 | 21.11 | 0.00675219 | 21.11 | 0.00675219 | 42.9911 | 9555.53 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 15739.860 | 12602.276 | 0.950840 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3242 | 1004.8586 | 1.1914 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.950845 | 1.13281000 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | Sensible | 7869.93 | 7383.44 | 1.0000 | 0.75520278 | 0.633893 | 25.36 | 17.07 | 0.00886750 | 48079.5 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7869.93 | 26.40 | 0.00840708 | 17.04 | 0.20573941 | 32.4565 | 23.89 | 0.00900065 | 23.89 | 0.00900065 | 48.2211 | 10902.23 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27539.631 | 27539.631 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.950845 | 1.13281000 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 27539.63 | 27539.63 | 1.0000 | 1.13281000 | 0.950845 | 15.61 | 10.50 | 0.00588464 | 30573.5 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27539.63 | -4.30 | 0.00265759 | -4.30 | 0.20573941 | 21.6375 | 21.11 | 0.00677570 | 21.11 | 0.00677570 | 43.1393 | 9862.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 16431.850 | 13156.325 | 0.992650 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3052 | 1004.8586 | 1.1914 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.992648 | 1.18261290 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | Sensible | 8215.92 | 7717.33 | 1.0000 | 0.78841028 | 0.661767 | 25.24 | 17.02 | 0.00885726 | 47930.2 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8215.92 | 25.95 | 0.00840636 | 16.88 | 0.20573941 | 31.0894 | 23.89 | 0.00898100 | 23.89 | 0.00898100 | 48.1174 | 11261.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28261.939 | 28261.939 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.992648 | 1.18261290 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 28261.94 | 28261.94 | 1.0000 | 1.18261290 | 0.992648 | 15.84 | 10.72 | 0.00599895 | 31097.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28261.94 | -4.30 | 0.00265759 | -4.30 | 0.20573941 | 20.7263 | 21.11 | 0.00687256 | 21.11 | 0.00687256 | 43.7502 | 12005.72 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:10
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 1.83 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.99 | - | |||
PSZ-AC_3:3_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.98 | - | |||
PSZ-AC_4:4_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.98 | - | |||
PSZ-AC_5:5_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.97 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 1.81 | - | |||
PSZ-AC_7:7_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.97 | - | |||
PSZ-AC_8:8_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.96 | - | |||
PSZ-AC_10:10_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.99 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 1433.83 | 4361.67 | 568.83 |
SMSTORE1 | 1190.50 | 3716.83 | 83.17 |
SMSTORE2 | 1054.33 | 2890.00 | 188.83 |
SMSTORE3 | 1075.00 | 2929.17 | 242.33 |
SMSTORE4 | 1079.33 | 3013.83 | 305.50 |
LGSTORE2 | 1036.83 | 2942.83 | 414.83 |
SMSTORE5 | 999.67 | 2817.00 | 403.00 |
SMSTORE6 | 1016.67 | 2852.33 | 444.00 |
SMSTORE7 | 1093.67 | 2994.83 | 609.50 |
SMSTORE8 | 1597.67 | 3161.33 | 1204.17 |
Facility | 2658.33 | 4707.67 | 1504.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 4.67 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 0.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 4.67 | 0.00 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:10
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 0.915 | 0.223 | 0.000 | 0.000 |
SMSTORE1 | 8.47 | 28.12 | 902.60 | 0.968 | 0.242 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 1.146 | 0.317 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 1.140 | 0.317 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 1.119 | 0.317 | 0.000 | 0.000 |
LGSTORE2 | 24.76 | 56.25 | 1805.20 | 0.964 | 0.305 | 0.000 | 0.000 |
SMSTORE5 | 12.38 | 28.12 | 902.60 | 1.114 | 0.339 | 0.000 | 0.000 |
SMSTORE6 | 12.38 | 28.12 | 902.60 | 1.105 | 0.339 | 0.000 | 0.000 |
SMSTORE7 | 12.38 | 28.12 | 902.60 | 0.831 | 0.339 | 0.000 | 0.000 |
SMSTORE8 | 12.38 | 28.12 | 902.60 | 1.058 | 0.350 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.47 | 28.12 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 0.807 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 0.807 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 0.807 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.76 | 56.25 | 1805.20 | 0.804 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.38 | 28.12 | 902.60 | 0.805 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.38 | 28.12 | 902.60 | 0.805 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.38 | 28.12 | 902.60 | 0.802 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.38 | 28.12 | 902.60 | 0.802 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:41:10
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 16.93 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE1 | PSZ-AC_2:2 | 8.47 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE2 | PSZ-AC_3:3 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE3 | PSZ-AC_4:4 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE4 | PSZ-AC_5:5 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
LGSTORE2 | PSZ-AC_6:6 | 24.76 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE5 | PSZ-AC_7:7 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE6 | PSZ-AC_8:8 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE7 | PSZ-AC_9:9 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE8 | PSZ-AC_10:10 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
Total Facility | 120.91 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 2.469 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 9513038.33 | 0.00 | 9513038.33 | 2543830.37 | 12056868.70 | 12976396.34 | 3181.44 | 4452.60 | 1125.95 | 0.00 |
SMSTORE1 | 5015070.43 | 0.00 | 5015070.43 | 1325765.83 | 6340836.25 | 6488198.17 | 4253.80 | 2746.83 | 1759.37 | 0.00 |
SMSTORE2 | 4476217.19 | 0.00 | 4476217.19 | 1348098.60 | 5824315.79 | 6488198.17 | 4365.00 | 3175.28 | 1219.72 | 0.00 |
SMSTORE3 | 4451305.32 | 0.00 | 4451305.32 | 1348098.60 | 5799403.92 | 6488198.17 | 4365.00 | 3210.35 | 1184.65 | 0.00 |
SMSTORE4 | 4372142.43 | 0.00 | 4372142.43 | 1348098.60 | 5720241.03 | 6488198.17 | 4365.00 | 3284.19 | 1110.81 | 0.00 |
LGSTORE2 | 6912427.91 | 0.00 | 6912427.91 | 2452721.70 | 9365149.61 | 12976396.34 | 4730.00 | 3216.01 | 813.99 | 0.00 |
SMSTORE5 | 3990831.83 | 0.00 | 3990831.83 | 1353477.65 | 5344309.48 | 6488198.17 | 4730.00 | 2993.24 | 1036.76 | 0.00 |
SMSTORE6 | 3956781.06 | 0.00 | 3956781.06 | 1353477.65 | 5310258.71 | 6488198.17 | 4730.00 | 3020.83 | 1009.17 | 0.00 |
SMSTORE7 | 3255209.01 | 0.00 | 3255209.01 | 1353477.65 | 4608686.67 | 6488198.17 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE8 | 3792174.88 | 0.00 | 3792174.88 | 1541577.72 | 5333752.60 | 6488198.17 | 4730.00 | 3239.51 | 790.49 | 0.00 |
Total Facility | 49735198.40 | 0.00 | 49735198.40 | 15968624.37 | 65703822.77 | 77858378.04 | 4730.00 | 5657.83 | 1832.31 | 365.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.4525 | 0.0000 | 0.4525 | 0.1105 | 0.5630 | 0.4115 | 261.44 | 4452.60 | 1125.95 |
SMSTORE1 | 0.2385 | 0.0000 | 0.2385 | 0.0599 | 0.2984 | 0.2057 | 1333.80 | 2746.83 | 1759.37 |
SMSTORE2 | 0.2829 | 0.0000 | 0.2829 | 0.0785 | 0.3614 | 0.2057 | 0.00 | 3175.28 | 1219.72 |
SMSTORE3 | 0.2813 | 0.0000 | 0.2813 | 0.0785 | 0.3598 | 0.2057 | 0.00 | 3210.35 | 1184.65 |
SMSTORE4 | 0.2763 | 0.0000 | 0.2763 | 0.0785 | 0.3548 | 0.2057 | 0.00 | 3284.19 | 1110.81 |
LGSTORE2 | 0.4765 | 0.0000 | 0.4765 | 0.1507 | 0.6271 | 0.4115 | 0.00 | 3216.01 | 813.99 |
SMSTORE5 | 0.2751 | 0.0000 | 0.2751 | 0.0838 | 0.3589 | 0.2057 | 0.00 | 2993.24 | 1036.76 |
SMSTORE6 | 0.2727 | 0.0000 | 0.2727 | 0.0838 | 0.3565 | 0.2057 | 0.00 | 3020.83 | 1009.17 |
SMSTORE7 | 0.2057 | 0.0000 | 0.2057 | 0.0838 | 0.2896 | 0.2057 | 0.00 | 4030.00 | 0.00 |
SMSTORE8 | 0.2614 | 0.0000 | 0.2614 | 0.0866 | 0.3480 | 0.2057 | 0.00 | 3239.51 | 790.49 |
Total Facility | 3.0230 | 0.0000 | 3.0230 | 0.8946 | 3.9176 | 2.4689 | 1437.30 | 5634.80 | 1832.31 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 13503094.58 | 0.00 | 13503094.58 | 12976396.34 | 3181.28 | 0.00 | 5578.72 | 0.00 |
PSZ-AC_2:2 | 7118226.83 | 0.00 | 7118226.83 | 6488198.17 | 4225.35 | 5.64 | 4529.01 | 0.00 |
PSZ-AC_3:3 | 6353396.18 | 0.00 | 6353396.18 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 0.00 |
PSZ-AC_4:4 | 6318037.08 | 0.00 | 6318037.08 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 0.00 |
PSZ-AC_5:5 | 6205675.86 | 0.00 | 6205675.86 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 0.00 |
PSZ-AC_6:6 | 9811661.31 | 0.00 | 9811661.31 | 12976396.34 | 4730.00 | 0.00 | 4030.00 | 0.00 |
PSZ-AC_7:7 | 5664456.08 | 0.00 | 5664456.08 | 6488198.17 | 4730.00 | 0.00 | 4030.00 | 0.00 |
PSZ-AC_8:8 | 5616125.53 | 0.00 | 5616125.53 | 6488198.17 | 4730.00 | 0.00 | 4030.00 | 0.00 |
PSZ-AC_9:9 | 4620337.13 | 0.00 | 4620337.13 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_10:10 | 5382488.90 | 0.00 | 5382488.90 | 6488198.17 | 4730.00 | 0.00 | 4030.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.6423 | 0.0000 | 0.6423 | 0.4115 | 261.28 | 0.00 | 5578.72 |
PSZ-AC_2:2 | 0.3386 | 0.0000 | 0.3386 | 0.2057 | 1305.35 | 5.64 | 4529.01 |
PSZ-AC_3:3 | 0.4016 | 0.0000 | 0.4016 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_4:4 | 0.3993 | 0.0000 | 0.3993 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_5:5 | 0.3922 | 0.0000 | 0.3922 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_6:6 | 0.6763 | 0.0000 | 0.6763 | 0.4115 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_7:7 | 0.3904 | 0.0000 | 0.3904 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_8:8 | 0.3871 | 0.0000 | 0.3871 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_9:9 | 0.2920 | 0.0000 | 0.2920 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_10:10 | 0.3710 | 0.0000 | 0.3710 | 0.2057 | 0.00 | 0.00 | 4030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 5003.26 | 579.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 3219.90 | 1645.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 3530.35 | 864.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 3554.26 | 840.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 3608.03 | 786.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 3654.10 | 375.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 3287.55 | 742.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 3307.22 | 722.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 3469.82 | 560.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.6526 | 0.8392 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.3757 | 0.4667 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 0.3602 | 0.5709 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 0.3579 | 0.5749 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 0.3527 | 0.5739 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 0.6567 | 0.8687 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.3519 | 0.5615 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.3495 | 0.5600 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.2921 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.3382 | 0.5750 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:10
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 759 |
Defaulted Fields | 823 |
Fields with Defaults | 2681 |
Autosized Fields | 184 |
Autosizable Fields | 458 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:41:10
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 921.70 | 3115.94 | 29-JAN-08:00 | 74166.76 | 22-JUL-13:00 |
Electricity:Building | 570.24 | 1897.94 | 01-JAN-00:10 | 35612.10 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 128.86 | 354.96 | 01-JAN-00:10 | 6669.68 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 570.24 | 1897.94 | 01-JAN-00:10 | 35612.10 | 01-JAN-11:10 |
InteriorLights:Electricity | 441.52 | 1448.52 | 01-JAN-00:10 | 27522.57 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 102.50 | 280.06 | 01-JAN-00:10 | 5321.43 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 441.52 | 1448.52 | 01-JAN-00:10 | 27522.57 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 441.52 | 1448.52 | 01-JAN-00:10 | 27522.57 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 102.50 | 280.06 | 01-JAN-00:10 | 5321.43 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 441.52 | 1448.52 | 01-JAN-00:10 | 27522.57 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 69.66 | 191.80 | 01-JAN-00:10 | 3606.70 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 56.49 | 154.35 | 01-JAN-00:10 | 2932.57 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 56.49 | 154.35 | 01-JAN-00:10 | 2932.57 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 50.51 | 174.25 | 01-JAN-00:10 | 3273.35 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 40.04 | 136.80 | 01-JAN-00:10 | 2599.23 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 40.04 | 136.80 | 01-JAN-00:10 | 2599.23 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 50.51 | 174.25 | 01-JAN-00:10 | 3273.35 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 40.04 | 136.80 | 01-JAN-00:10 | 2599.23 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 40.04 | 136.80 | 01-JAN-00:10 | 2599.23 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 50.51 | 174.25 | 01-JAN-00:10 | 3273.35 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 40.04 | 136.80 | 01-JAN-00:10 | 2599.23 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 40.04 | 136.80 | 01-JAN-00:10 | 2599.23 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 72.31 | 272.07 | 01-JAN-00:10 | 5094.77 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 53.05 | 197.17 | 01-JAN-00:10 | 3746.51 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 53.05 | 197.17 | 01-JAN-00:10 | 3746.51 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 36.97 | 139.09 | 01-JAN-00:10 | 2605.22 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 36.97 | 139.09 | 01-JAN-00:10 | 2605.22 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 36.97 | 139.09 | 01-JAN-00:10 | 2605.22 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 36.97 | 139.09 | 01-JAN-00:10 | 2605.22 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.36 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.36 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.18 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.18 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.26 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.26 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
ElectricityPurchased:Facility | 921.70 | 3115.94 | 29-JAN-08:00 | 74166.76 | 22-JUL-13:00 |
ElectricityPurchased:Plant | 921.70 | 3115.94 | 29-JAN-08:00 | 74166.76 | 22-JUL-13:00 |
Cogeneration:ElectricityPurchased | 921.70 | 3115.94 | 29-JAN-08:00 | 74166.76 | 22-JUL-13:00 |
General:Cogeneration:ElectricityPurchased | 921.70 | 3115.94 | 29-JAN-08:00 | 74166.76 | 22-JUL-13:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 921.70 | 3115.94 | 29-JAN-08:00 | 74166.76 | 22-JUL-13:00 |
ElectricityNet:Plant | 921.70 | 3115.94 | 29-JAN-08:00 | 74166.76 | 22-JUL-13:00 |
Cogeneration:ElectricityNet | 921.70 | 3115.94 | 29-JAN-08:00 | 74166.76 | 22-JUL-13:00 |
General:Cogeneration:ElectricityNet | 921.70 | 3115.94 | 29-JAN-08:00 | 74166.76 | 22-JUL-13:00 |
Electricity:HVAC | 186.23 | 0.00 | 01-JAN-00:10 | 32841.14 | 22-JUL-15:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 12.09 | 0.00 | 01-JAN-00:10 | 22497.23 | 22-JUL-15:00 |
General:Cooling:Electricity | 12.09 | 0.00 | 01-JAN-00:10 | 22497.23 | 22-JUL-15:00 |
Fans:Electricity | 174.14 | 0.00 | 01-JAN-00:10 | 11328.76 | 10-JAN-09:10 |
General:Fans:Electricity | 174.14 | 0.00 | 01-JAN-00:10 | 11328.76 | 10-JAN-09:10 |
ExteriorLights:Electricity | 100.01 | 0.00 | 01-JAN-08:20 | 7619.51 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 100.01 | 0.00 | 01-JAN-08:20 | 7619.51 | 01-JAN-06:10 |
Electricity:Plant | 65.22 | 1218.00 | 12-JAN-08:10 | 11859.11 | 07-JAN-14:40 |
WaterSystems:Electricity | 65.22 | 1218.00 | 12-JAN-08:10 | 11859.11 | 07-JAN-14:40 |
Water Heater:WaterSystems:Electricity | 65.22 | 1218.00 | 12-JAN-08:10 | 11859.11 | 07-JAN-14:40 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 342.22 | 0.00 | 01-JAN-00:10 | 173467.85 | 10-JAN-09:10 |
NaturalGas:HVAC | 342.22 | 0.00 | 01-JAN-00:10 | 173467.85 | 10-JAN-09:10 |
Heating:NaturalGas | 342.22 | 0.00 | 01-JAN-00:10 | 173467.85 | 10-JAN-09:10 |
General:Heating:NaturalGas | 342.22 | 0.00 | 01-JAN-00:10 | 173467.85 | 10-JAN-09:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 663.27 | 0.00 | 01-JAN-00:10 | 219446.38 | 10-JAN-09:10 |
EnergyTransfer:Building | 336.78 | 0.00 | 01-JAN-00:10 | 80672.10 | 10-JAN-09:10 |
EnergyTransfer:Zone:LGSTORE1 | 73.86 | 0.00 | 01-JAN-00:10 | 17098.59 | 10-JAN-09:10 |
Heating:EnergyTransfer | 68.66 | 0.00 | 01-JAN-00:10 | 77511.46 | 10-JAN-09:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 8.77 | 0.00 | 01-JAN-00:10 | 16229.89 | 10-JAN-09:10 |
General:Heating:EnergyTransfer | 68.66 | 0.00 | 01-JAN-00:10 | 77511.46 | 10-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 8.77 | 0.00 | 01-JAN-00:10 | 16229.89 | 10-JAN-09:10 |
Cooling:EnergyTransfer | 268.12 | 0.00 | 01-JAN-00:10 | 75859.99 | 22-JUL-15:00 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 65.09 | 0.00 | 01-JAN-00:10 | 12927.18 | 22-JUL-16:20 |
General:Cooling:EnergyTransfer | 268.12 | 0.00 | 01-JAN-00:10 | 75859.99 | 22-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 65.09 | 0.00 | 01-JAN-00:10 | 12927.18 | 22-JUL-16:20 |
EnergyTransfer:Zone:SMSTORE1 | 36.58 | 0.00 | 01-JAN-00:10 | 9677.34 | 06-AUG-17:20 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 2.60 | 0.00 | 01-JAN-00:10 | 4459.92 | 30-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 2.60 | 0.00 | 01-JAN-00:10 | 4459.92 | 30-DEC-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 33.97 | 0.00 | 01-JAN-00:10 | 9677.34 | 06-AUG-17:20 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 33.97 | 0.00 | 01-JAN-00:10 | 9677.34 | 06-AUG-17:20 |
EnergyTransfer:Zone:SMSTORE2 | 28.11 | 0.00 | 01-JAN-00:10 | 6913.62 | 10-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 3.90 | 0.00 | 01-JAN-00:10 | 6230.84 | 10-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 3.90 | 0.00 | 01-JAN-00:10 | 6230.84 | 10-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 24.21 | 0.00 | 01-JAN-00:10 | 6627.98 | 22-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 24.21 | 0.00 | 01-JAN-00:10 | 6627.98 | 22-JUL-13:00 |
EnergyTransfer:Zone:SMSTORE3 | 27.46 | 0.00 | 01-JAN-00:10 | 7729.09 | 10-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 4.48 | 0.00 | 01-JAN-00:10 | 7014.57 | 10-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 4.48 | 0.00 | 01-JAN-00:10 | 7014.57 | 10-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 22.98 | 0.00 | 01-JAN-00:10 | 6606.35 | 22-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 22.98 | 0.00 | 01-JAN-00:10 | 6606.35 | 22-JUL-13:00 |
EnergyTransfer:Zone:SMSTORE4 | 26.39 | 0.00 | 01-JAN-00:10 | 8550.84 | 31-DEC-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 5.36 | 0.00 | 01-JAN-00:10 | 7757.52 | 10-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 5.36 | 0.00 | 01-JAN-00:10 | 7757.52 | 10-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 21.03 | 0.00 | 01-JAN-00:10 | 6481.84 | 22-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 21.03 | 0.00 | 01-JAN-00:10 | 6481.84 | 22-JUL-13:00 |
EnergyTransfer:Zone:LGSTORE2 | 47.14 | 0.00 | 01-JAN-00:10 | 16686.31 | 10-JAN-09:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 8.79 | 0.00 | 01-JAN-00:10 | 15676.79 | 27-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 8.79 | 0.00 | 01-JAN-00:10 | 15676.79 | 27-DEC-09:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 38.35 | 0.00 | 01-JAN-00:10 | 12393.43 | 22-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 38.35 | 0.00 | 01-JAN-00:10 | 12393.43 | 22-JUL-15:00 |
EnergyTransfer:Zone:SMSTORE5 | 23.49 | 0.00 | 01-JAN-00:10 | 8709.23 | 02-JAN-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 5.79 | 0.00 | 01-JAN-00:10 | 7882.39 | 30-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 5.79 | 0.00 | 01-JAN-00:10 | 7882.39 | 30-DEC-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 17.70 | 0.00 | 01-JAN-00:10 | 6477.71 | 22-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 17.70 | 0.00 | 01-JAN-00:10 | 6477.71 | 22-JUL-15:00 |
EnergyTransfer:Zone:SMSTORE6 | 23.24 | 0.00 | 01-JAN-00:10 | 8738.28 | 13-FEB-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 6.17 | 0.00 | 01-JAN-00:10 | 7949.48 | 30-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 6.17 | 0.00 | 01-JAN-00:10 | 7949.48 | 30-DEC-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 17.07 | 0.00 | 01-JAN-00:10 | 6413.89 | 22-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 17.07 | 0.00 | 01-JAN-00:10 | 6413.89 | 22-JUL-15:00 |
EnergyTransfer:Zone:SMSTORE7 | 23.07 | 0.00 | 01-JAN-00:10 | 9220.81 | 10-JAN-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 7.25 | 0.00 | 01-JAN-00:10 | 8909.50 | 10-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 7.25 | 0.00 | 01-JAN-00:10 | 8909.50 | 10-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 15.82 | 0.00 | 01-JAN-00:10 | 6277.90 | 22-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 15.82 | 0.00 | 01-JAN-00:10 | 6277.90 | 22-JUL-15:00 |
EnergyTransfer:Zone:SMSTORE8 | 27.45 | 0.00 | 01-JAN-00:10 | 12251.25 | 10-JAN-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 15.55 | 0.00 | 01-JAN-00:10 | 11975.35 | 10-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 15.55 | 0.00 | 01-JAN-00:10 | 11975.35 | 10-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 11.90 | 0.00 | 01-JAN-00:10 | 6462.82 | 22-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 11.90 | 0.00 | 01-JAN-00:10 | 6462.82 | 22-JUL-15:00 |
EnergyTransfer:HVAC | 326.49 | 0.00 | 01-JAN-00:10 | 138774.28 | 10-JAN-09:10 |
HeatingCoils:EnergyTransfer | 273.78 | 0.00 | 01-JAN-00:10 | 138774.28 | 10-JAN-09:10 |
CoolingCoils:EnergyTransfer | 52.71 | 0.00 | 01-JAN-00:10 | 101499.92 | 22-JUL-15:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:10
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 8.767 | -65.090 | 0.000 | 0.000 | 25.747 | 102.498 | 26.357 | 21.453 | 0.000 | 0.065 | 0.000 | 0.000 | -10.469 | 0.000 | -33.107 | -76.222 |
SMSTORE1 | 0.000 | 0.000 | 2.604 | -33.972 | 0.000 | 0.000 | 12.521 | 56.486 | 13.179 | 10.582 | 0.000 | 0.035 | 0.000 | 0.000 | -5.576 | 0.000 | -17.569 | -38.290 |
SMSTORE2 | 0.000 | 0.000 | 3.897 | -24.209 | 0.000 | 0.000 | 7.659 | 40.039 | 10.467 | 10.577 | 0.000 | 0.035 | 0.000 | 0.000 | -5.473 | 0.000 | -17.812 | -25.181 |
SMSTORE3 | 0.000 | 0.000 | 4.477 | -22.985 | 0.000 | 0.000 | 7.671 | 40.039 | 10.467 | 10.595 | 0.000 | 0.035 | 0.001 | 0.000 | -5.407 | 0.000 | -17.750 | -27.142 |
SMSTORE4 | 0.000 | 0.000 | 5.360 | -21.031 | 0.000 | 0.000 | 7.689 | 40.039 | 10.467 | 10.621 | 0.000 | 0.035 | 0.001 | 0.000 | -5.344 | 0.000 | -17.665 | -30.170 |
LGSTORE2 | 0.000 | 0.000 | 8.793 | -38.348 | 0.000 | 0.000 | 26.566 | 53.048 | 19.261 | 21.392 | 0.000 | 0.063 | 0.000 | 0.000 | -10.402 | 0.000 | -31.736 | -48.635 |
SMSTORE5 | 0.000 | 0.000 | 5.790 | -17.695 | 0.000 | 0.000 | 13.205 | 27.343 | 9.631 | 10.660 | 0.000 | 0.035 | 0.000 | 0.000 | -5.228 | 0.000 | -17.644 | -26.096 |
SMSTORE6 | 0.000 | 0.000 | 6.172 | -17.070 | 0.000 | 0.000 | 13.216 | 27.343 | 9.631 | 10.672 | 0.000 | 0.035 | 0.001 | 0.000 | -5.203 | 0.000 | -17.612 | -27.183 |
SMSTORE7 | 0.000 | 0.000 | 7.250 | -15.819 | 0.000 | 0.000 | 13.267 | 27.343 | 9.631 | 10.731 | 0.000 | 0.035 | 0.001 | 0.000 | -5.092 | 0.000 | -17.434 | -29.910 |
SMSTORE8 | 0.000 | 0.000 | 15.551 | -11.903 | 0.000 | 0.000 | 13.316 | 27.343 | 9.631 | 10.824 | 0.000 | 0.036 | 0.000 | 0.000 | -4.744 | 0.000 | -19.804 | -40.251 |
Total Facility | 0.000 | 0.000 | 68.661 | -268.121 | 0.000 | 0.000 | 140.856 | 441.522 | 128.721 | 128.108 | 0.000 | 0.409 | 0.006 | 0.000 | -62.939 | 0.000 | -208.134 | -369.081 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 18-JUL-08:62 | 0.00 | 0.00 | 0.00 | -27488.98 | 0.00 | 0.00 | 183.84 | 2800.74 | 749.03 | 711.23 | 0.00 | 0.00 | 23285.42 | 0.00 | -0.00 | 0.00 | -241.29 | 0.00 |
SMSTORE1 | 29-APR-18:44 | 0.00 | 0.00 | 0.00 | -18331.19 | 0.00 | 0.00 | 1055.96 | 2932.57 | 674.13 | 0.00 | 0.00 | 0.00 | 13830.02 | 0.00 | -52.52 | 0.00 | -108.96 | 0.00 |
SMSTORE2 | 15-AUG-07:02 | 0.00 | 0.00 | 0.00 | -18029.88 | 0.00 | 0.00 | 87.74 | 1368.01 | 374.52 | 30.03 | 0.00 | 0.00 | 16335.98 | 0.00 | -0.00 | 0.00 | -166.39 | 0.00 |
SMSTORE3 | 15-AUG-07:02 | 0.00 | 0.00 | 0.00 | -18075.61 | 0.00 | 0.00 | 87.80 | 1368.01 | 374.52 | 30.18 | 0.00 | 0.00 | 16381.22 | 0.00 | -0.00 | 0.00 | -166.12 | 0.00 |
SMSTORE4 | 15-AUG-07:02 | 0.00 | 0.00 | 0.00 | -17872.40 | 0.00 | 0.00 | 88.76 | 1368.01 | 374.52 | 32.28 | 0.00 | 0.00 | 16172.10 | 0.00 | -0.00 | 0.00 | -163.26 | 0.00 |
LGSTORE2 | 24-JUL-08:62 | 0.00 | 0.00 | 0.00 | -30853.81 | 0.00 | 0.00 | 399.46 | 1971.84 | 749.03 | 656.53 | 0.00 | 0.00 | 27493.15 | 0.00 | -0.00 | 0.00 | -416.19 | 0.00 |
SMSTORE5 | 25-JUL-08:62 | 0.00 | 0.00 | 0.00 | -16993.64 | 0.00 | 0.00 | 197.76 | 1016.37 | 374.52 | 205.79 | 0.00 | 0.00 | 15451.74 | 0.00 | -0.00 | 0.00 | -252.52 | 0.00 |
SMSTORE6 | 25-JUL-08:62 | 0.00 | 0.00 | 0.00 | -16836.71 | 0.00 | 0.00 | 198.90 | 1016.37 | 374.52 | 207.22 | 0.00 | 0.00 | 15290.71 | 0.00 | -0.00 | 0.00 | -251.01 | 0.00 |
SMSTORE7 | 23-JUL-09:01 | 0.00 | 0.00 | 0.00 | -13690.93 | 0.00 | 0.00 | 202.57 | 1016.37 | 374.52 | 834.06 | 0.00 | 0.00 | 11361.74 | 0.00 | -0.00 | 0.00 | -98.31 | 0.00 |
SMSTORE8 | 23-JUL-09:01 | 0.00 | 0.00 | 0.00 | -16345.22 | 0.00 | 0.00 | 183.43 | 1016.37 | 374.52 | 823.80 | 0.00 | 0.00 | 14090.96 | 0.00 | -0.00 | 0.00 | -143.84 | 0.00 |
Total Facility | 22-JUL-08:62 | 0.00 | 0.00 | 0.00 | -131711.76 | 0.00 | 0.00 | 2029.06 | 18179.18 | 5393.02 | 5050.02 | 0.00 | 7.83 | 101205.97 | 0.00 | 0.00 | 0.00 | -153.31 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 09-MAR-09:01 | 0.00 | 0.00 | 49378.11 | 0.00 | 0.00 | 0.00 | 245.45 | 2800.74 | 749.03 | 858.46 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -510.64 | -53521.15 |
SMSTORE1 | 29-DEC-09:01 | 0.00 | 0.00 | 23998.04 | 0.00 | 0.00 | 0.00 | 121.16 | 1543.46 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -103.35 | 0.00 | -496.27 | -25437.55 |
SMSTORE2 | 25-DEC-09:01 | 0.00 | 0.00 | 23924.80 | 0.00 | 0.00 | 0.00 | 121.87 | 1368.01 | 374.52 | 290.58 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -454.40 | -25625.38 |
SMSTORE3 | 25-DEC-09:01 | 0.00 | 0.00 | 23883.85 | 0.00 | 0.00 | 0.00 | 123.62 | 1368.01 | 374.52 | 297.11 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -445.45 | -25601.66 |
SMSTORE4 | 06-MAR-08:62 | 0.00 | 0.00 | 24280.78 | 0.00 | 0.00 | 0.00 | 123.11 | 1368.01 | 374.52 | 41.91 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -368.91 | -25819.42 |
LGSTORE2 | 29-JAN-10:01 | 0.00 | 0.00 | 48178.31 | 0.00 | 0.00 | 0.00 | 541.46 | 1971.84 | 749.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -84.70 | 0.00 | -430.27 | -50925.67 |
SMSTORE5 | 04-DEC-09:01 | 0.00 | 0.00 | 25269.88 | 0.00 | 0.00 | 0.00 | 279.76 | 1016.37 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -157.89 | 0.00 | -287.35 | -26495.27 |
SMSTORE6 | 29-JAN-10:01 | 0.00 | 0.00 | 25553.04 | 0.00 | 0.00 | 0.00 | 266.05 | 1016.37 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -44.41 | 0.00 | -246.97 | -26918.58 |
SMSTORE7 | 29-JAN-10:01 | 0.00 | 0.00 | 25694.60 | 0.00 | 0.00 | 0.00 | 286.81 | 1016.37 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -27.44 | 0.00 | -202.87 | -27141.98 |
SMSTORE8 | 10-JAN-08:61 | 0.00 | 0.00 | 28183.86 | 0.00 | 0.00 | 0.00 | 0.00 | 101.64 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -46.18 | 0.00 | -533.94 | -27742.83 |
Total Facility | 31-DEC-09:01 | 0.00 | 0.00 | 260615.76 | 0.00 | 0.00 | 0.00 | 759.54 | 9051.95 | 2471.80 | 4894.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5259.20 | -272534.25 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:10
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.8256 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.8256 | 0.2254 | 1.0000 | Not calculated | 0.4115 | 0.2254 | ||
PSZ-AC_2:2 | 0.9787 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9907 | 0.2077 | 1.0000 | Not calculated | 0.2057 | 0.2077 | ||
PSZ-AC_3:3 | 0.9576 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9761 | 0.2108 | 1.0000 | Not calculated | 0.2057 | 0.2108 | ||
PSZ-AC_4:4 | 0.9520 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9792 | 0.2101 | 1.0000 | Not calculated | 0.2057 | 0.2101 | ||
PSZ-AC_5:5 | 0.9570 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9748 | 0.2111 | 1.0000 | Not calculated | 0.2057 | 0.2111 | ||
PSZ-AC_6:6 | 1.7666 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.8072 | 0.2277 | 1.0000 | Not calculated | 0.4115 | 0.2277 | ||
PSZ-AC_7:7 | 0.9575 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9655 | 0.2131 | 1.0000 | Not calculated | 0.2057 | 0.2131 | ||
PSZ-AC_8:8 | 0.9519 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9603 | 0.2143 | 1.0000 | Not calculated | 0.2057 | 0.2143 | ||
PSZ-AC_9:9 | 0.9410 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9508 | 0.2164 | 1.0000 | Not calculated | 0.2057 | 0.2164 | ||
PSZ-AC_10:10 | 0.9729 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9926 | 0.2073 | 1.0000 | Not calculated | 0.2057 | 0.2073 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.8256 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.8256 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2254 | ||
PSZ-AC_2:2 | 0.9787 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9787 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2102 | ||
PSZ-AC_3:3 | 0.9576 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9576 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2149 | ||
PSZ-AC_4:4 | 0.9520 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9520 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2161 | ||
PSZ-AC_5:5 | 0.9570 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9570 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2150 | ||
PSZ-AC_6:6 | 1.7666 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.7666 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2329 | ||
PSZ-AC_7:7 | 0.9575 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9575 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2149 | ||
PSZ-AC_8:8 | 0.9519 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9519 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2161 | ||
PSZ-AC_9:9 | 0.9410 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9410 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2187 | ||
PSZ-AC_10:10 | 0.9729 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9729 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2115 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8256 | 1.8256 | 1.8256 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9787 | 0.9787 | 0.9787 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9576 | 0.9576 | 0.9576 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9520 | 0.9520 | 0.9520 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9570 | 0.9570 | 0.9570 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.7666 | 1.7666 | 1.7666 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9575 | 0.9575 | 0.9575 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9519 | 0.9519 | 0.9519 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9410 | 0.9410 | 0.9410 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9729 | 0.9729 | 0.9729 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.8256 | 1.8256 | 1.8256 | 1.8256 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 0.9787 | 0.9907 | 0.9787 | 0.9787 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 0.9576 | 0.9761 | 0.9576 | 0.9576 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 0.9520 | 0.9792 | 0.9520 | 0.9520 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 0.9570 | 0.9748 | 0.9570 | 0.9570 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.7666 | 1.8072 | 1.7666 | 1.7666 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.9575 | 0.9655 | 0.9575 | 0.9575 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9519 | 0.9603 | 0.9519 | 0.9519 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.9410 | 0.9508 | 0.9410 | 0.9410 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 0.9729 | 0.9926 | 0.9729 | 0.9729 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8256 | 1.8256 | 1.8256 | No | 0.4115 | 0.4156 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9787 | 0.9787 | 0.9787 | No | 0.2057 | 0.4427 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9576 | 0.9576 | 0.9576 | No | 0.2057 | 0.4381 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9520 | 0.9520 | 0.9520 | No | 0.2057 | 0.4335 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9570 | 0.9570 | 0.9570 | No | 0.2057 | 0.4254 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.7666 | 1.7666 | 1.7666 | No | 0.4115 | 0.4392 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9575 | 0.9575 | 0.9575 | No | 0.2057 | 0.4120 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9519 | 0.9519 | 0.9519 | No | 0.2057 | 0.4118 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9410 | 0.9410 | 0.9410 | No | 0.2057 | 0.3990 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9729 | 0.9729 | 0.9729 | No | 0.2057 | 0.3278 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.8256 | 1.8256 | 1.8256 | 1.8256 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 0.9787 | 0.9787 | 0.9787 | 0.9787 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 0.9576 | 0.9576 | 0.9576 | 0.9576 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 0.9520 | 0.9520 | 0.9520 | 0.9520 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 0.9570 | 0.9570 | 0.9570 | 0.9570 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.7666 | 1.7666 | 1.7666 | 1.7666 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.9575 | 0.9575 | 0.9575 | 0.9575 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9519 | 0.9519 | 0.9519 | 0.9519 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.9410 | 0.9410 | 0.9410 | 0.9410 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 0.9729 | 0.9729 | 0.9729 | 0.9729 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:10
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 342.22 | 173467.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 12.09 | 22497.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 441.52 | 27522.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 100.01 | 7619.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.72 | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 174.14 | 11328.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 65.22 | 11859.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.72 | 921.70 |
Natural Gas | 0.00 | 342.22 |
Additional | 0.00 | 0.00 |
Total | 128.72 | 1263.92 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 211.22 |
Space Heating | 0.00 |
Space Cooling | 5.79 |
Fans (All) | 83.31 |
Service Water Heating | 31.20 |
Receptacle Equipment | 61.58 |
Miscellaneous (All) | 440.94 |
Subtotal | 440.94 |
Natural Gas [MJ/m2] | |
Space Heating | 163.72 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 163.72 |
Subtotal | 163.72 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 34.93 |
Space Heating | 27.08 |
Space Cooling | 0.96 |
Fans (All) | 13.78 |
Service Water Heating | 5.16 |
Receptacle Equipment | 10.18 |
Miscellaneous | 7.91 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3238. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3296. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 4469. | 8760. |
LTG_SCH_BASE_LPD1 | 4391. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 3584. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4888. | 8760. |
TYPE2_EQUIP_SCH | 3911. | 8760. |
TYPE3_EQUIP_SCH | 3600. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:10
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8759.67 | 0.33 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8759.50 | 0.50 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8759.50 | 0.50 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8759.50 | 0.50 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8759.50 | 0.50 | 0.00 | 0.00 | 0.00 |
Min | 8759.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 0.67 | 0.00 | 0.00 | 0.00 |
Average | 8759.57 | 0.43 | 0.00 | 0.00 | 0.00 |
Sum | 87595.67 | 4.33 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25474.67 | 0.33 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25474.67 | 0.33 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25474.67 | 0.33 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93210.00 | 1.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45911.00 | 1.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45911.00 | 1.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45911.00 | 1.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45911.00 | 1.00 | 0.00 | 0.00 | 0.00 |
Min | 25474.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 93210.00 | 1.00 | 0.00 | 0.00 | 0.00 |
Average | 48609.60 | 0.60 | 0.00 | 0.00 | 0.00 |
Sum | 486096.00 | 6.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8753.67 | 6.33 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8754.17 | 5.83 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8755.00 | 5.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8757.67 | 2.33 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8757.00 | 3.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8757.33 | 2.67 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8759.50 | 0.50 | 0.00 | 0.00 | 0.00 |
Min | 8753.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 6.33 | 0.00 | 0.00 | 0.00 |
Average | 8757.37 | 2.63 | 0.00 | 0.00 | 0.00 |
Sum | 87573.67 | 26.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43776.33 | 0.67 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25474.33 | 0.67 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25474.50 | 0.50 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25474.50 | 0.50 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93211.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45912.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45912.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45912.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45912.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 25474.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 93211.00 | 0.67 | 0.00 | 0.00 | 0.00 |
Average | 48609.97 | 0.23 | 0.00 | 0.00 | 0.00 |
Sum | 486099.67 | 2.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:10
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:10
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Environment
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
For: Environment
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
For: Environment
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.183641E+10 | 9557.54 | 04-JAN-09:04 | 1.17 | 0.69 | 0.106381E+10 | 1275.40 | 16-JAN-18:00 | 4.00 | 3.53 |
February | 0.174878E+10 | 9722.10 | 18-FEB-00:03 | -1.2 | -1.5 | 0.960262E+09 | 1275.40 | 19-FEB-18:00 | 1.00 | 1.00 |
March | 0.235659E+10 | 9098.42 | 15-MAR-08:04 | 2.00 | 1.57 | 0.105490E+10 | 1288.43 | 19-MAR-17:30 | 11.50 | 10.70 |
April | 0.636519E+10 | 10485.13 | 30-APR-16:07 | 24.00 | 13.04 | 0.111990E+10 | 1685.87 | 29-APR-12:00 | 24.00 | 13.04 |
May | 0.697103E+10 | 8183.37 | 23-MAY-17:10 | 18.00 | 13.65 | 0.118323E+10 | 1685.86 | 21-MAY-17:40 | 18.00 | 13.65 |
June | 0.819541E+10 | 27191.27 | 13-JUN-08:62 | 21.10 | 15.99 | 0.129397E+10 | 1685.91 | 25-JUN-17:30 | 21.50 | 17.05 |
July | 0.971533E+10 | 27494.79 | 18-JUL-08:62 | 18.00 | 15.37 | 0.139206E+10 | 1685.94 | 16-JUL-12:00 | 18.00 | 15.37 |
August | 0.988034E+10 | 20810.08 | 15-AUG-08:62 | 17.67 | 13.87 | 0.139166E+10 | 1685.95 | 18-AUG-12:20 | 21.00 | 16.54 |
September | 0.844068E+10 | 10210.83 | 13-SEP-16:10 | 23.00 | 16.14 | 0.133404E+10 | 1685.95 | 10-SEP-16:49 | 23.00 | 16.14 |
October | 0.563606E+10 | 7557.52 | 05-OCT-20:03 | 5.17 | 4.18 | 0.113747E+10 | 1682.04 | 07-OCT-12:00 | 17.00 | 9.21 |
November | 0.263841E+10 | 9539.52 | 29-NOV-09:04 | 1.17 | -0.2 | 0.102973E+10 | 1304.79 | 10-NOV-13:00 | 1.17 | -0.2 |
December | 0.130535E+10 | 10550.55 | 30-DEC-00:02 | -2.8 | -4.3 | 0.106883E+10 | 1275.40 | 03-DEC-13:09 | -2.8 | -4.3 |
Annual Sum or Average | 0.650896E+11 | 0.140299E+11 | ||||||||
Minimum of Months | 0.130535E+10 | 7557.52 | -2.8 | -4.3 | 0.960262E+09 | 1275.40 | -2.8 | -4.3 | ||
Maximum of Months | 0.988034E+10 | 27494.79 | 24.00 | 16.14 | 0.139206E+10 | 1685.95 | 24.00 | 17.05 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.980116E+09 | 4905.12 | 09-JAN-09:03 | -1.8 | -3.0 | 0.555898E+09 | 789.28 | 29-JAN-18:00 | 9.00 | 8.43 |
February | 0.978481E+09 | 4187.27 | 17-FEB-09:03 | 1.33 | 0.86 | 0.501160E+09 | 787.60 | 05-FEB-18:00 | 1.33 | 0.86 |
March | 0.123474E+10 | 3707.09 | 15-MAR-08:02 | 2.00 | 1.57 | 0.554906E+09 | 821.77 | 19-MAR-17:00 | 11.00 | 10.48 |
April | 0.281491E+10 | 18331.39 | 29-APR-18:44 | 18.33 | 11.61 | 0.619163E+09 | 842.91 | 30-APR-17:00 | 24.00 | 13.13 |
May | 0.313818E+10 | 17371.05 | 21-MAY-17:07 | 20.00 | 12.86 | 0.649089E+09 | 842.90 | 29-MAY-17:00 | 11.00 | 7.55 |
June | 0.430773E+10 | 17056.68 | 26-JUN-08:62 | 18.17 | 13.96 | 0.672878E+09 | 842.91 | 25-JUN-17:10 | 18.17 | 13.96 |
July | 0.545615E+10 | 17675.02 | 25-JUL-08:62 | 13.17 | 13.07 | 0.705004E+09 | 842.94 | 23-JUL-17:10 | 13.17 | 13.07 |
August | 0.579425E+10 | 18246.29 | 14-AUG-21:16 | 17.47 | 11.81 | 0.696287E+09 | 842.94 | 18-AUG-12:39 | 21.00 | 16.54 |
September | 0.476414E+10 | 17429.79 | 14-SEP-08:62 | 17.00 | 12.99 | 0.681173E+09 | 842.94 | 10-SEP-16:10 | 17.00 | 12.99 |
October | 0.248662E+10 | 3980.26 | 05-OCT-20:10 | 5.17 | 4.18 | 0.631013E+09 | 842.90 | 09-OCT-17:00 | 11.00 | 11.00 |
November | 0.138421E+10 | 4124.71 | 29-NOV-09:03 | 1.17 | -0.2 | 0.546032E+09 | 827.15 | 05-NOV-17:00 | 1.17 | -0.2 |
December | 0.632273E+09 | 4631.16 | 27-DEC-09:03 | -0.7 | -0.8 | 0.554654E+09 | 757.63 | 24-DEC-18:00 | -0.7 | -0.8 |
Annual Sum or Average | 0.339718E+11 | 0.736726E+10 | ||||||||
Minimum of Months | 0.632273E+09 | 3707.09 | -1.8 | -3.0 | 0.501160E+09 | 757.63 | -0.7 | -0.8 | ||
Maximum of Months | 0.579425E+10 | 18331.39 | 20.00 | 13.96 | 0.705004E+09 | 842.94 | 24.00 | 16.54 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.590886E+09 | 5462.24 | 10-JAN-08:04 | -5.7 | -6.7 | 0.317187E+09 | 637.68 | 07-JAN-13:09 | -5.7 | -6.7 |
February | 0.573600E+09 | 5012.14 | 17-FEB-08:03 | -2.3 | -2.4 | 0.288070E+09 | 641.69 | 04-FEB-13:00 | -2.3 | -2.4 |
March | 0.820038E+09 | 3662.43 | 16-MAR-07:04 | 2.33 | 1.90 | 0.326464E+09 | 701.42 | 25-MAR-12:00 | 14.00 | 11.22 |
April | 0.222550E+10 | 10470.04 | 30-APR-08:63 | 17.50 | 12.51 | 0.354312E+09 | 842.90 | 29-APR-12:00 | 17.50 | 12.51 |
May | 0.250390E+10 | 6608.58 | 01-MAY-07:03 | 7.17 | 5.31 | 0.375786E+09 | 842.89 | 27-MAY-12:09 | 15.83 | 10.60 |
June | 0.303145E+10 | 18034.42 | 14-JUN-07:03 | 12.00 | 12.00 | 0.410509E+09 | 842.89 | 24-JUN-12:20 | 16.67 | 12.61 |
July | 0.374708E+10 | 17882.93 | 13-JUL-07:03 | 13.17 | 12.51 | 0.418180E+09 | 842.90 | 22-JUL-12:09 | 27.17 | 17.06 |
August | 0.411031E+10 | 18028.26 | 15-AUG-07:02 | 17.17 | 13.06 | 0.430865E+09 | 842.93 | 19-AUG-12:00 | 21.00 | 15.44 |
September | 0.334061E+10 | 17146.80 | 02-SEP-07:03 | 13.83 | 12.78 | 0.408107E+09 | 842.92 | 23-SEP-12:00 | 19.00 | 14.78 |
October | 0.197801E+10 | 3371.41 | 06-OCT-07:03 | 3.83 | 3.69 | 0.357218E+09 | 842.89 | 07-OCT-12:20 | 16.33 | 10.17 |
November | 0.939144E+09 | 4484.96 | 29-NOV-08:03 | -0.7 | -1.6 | 0.307694E+09 | 652.73 | 25-NOV-13:50 | -0.7 | -1.6 |
December | 0.347964E+09 | 4681.61 | 27-DEC-08:03 | -1.0 | -1.4 | 0.316717E+09 | 637.68 | 02-DEC-13:09 | -1.0 | -1.4 |
Annual Sum or Average | 0.242085E+11 | 0.431111E+10 | ||||||||
Minimum of Months | 0.347964E+09 | 3371.41 | -5.7 | -6.7 | 0.288070E+09 | 637.68 | -5.7 | -6.7 | ||
Maximum of Months | 0.411031E+10 | 18034.42 | 17.50 | 13.06 | 0.430865E+09 | 842.93 | 27.17 | 17.06 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.480776E+09 | 5716.19 | 10-JAN-08:04 | -5.7 | -6.7 | 0.317082E+09 | 637.68 | 21-JAN-13:09 | 7.83 | 6.08 |
February | 0.480248E+09 | 4392.13 | 18-FEB-08:03 | 0.17 | -0.4 | 0.288036E+09 | 638.14 | 04-FEB-13:00 | 0.17 | -0.4 |
March | 0.701680E+09 | 3952.00 | 13-MAR-07:04 | 1.33 | 0.37 | 0.326225E+09 | 695.17 | 25-MAR-12:00 | 14.00 | 11.22 |
April | 0.208929E+10 | 9741.10 | 30-APR-08:63 | 17.50 | 12.51 | 0.350929E+09 | 842.90 | 29-APR-12:00 | 17.50 | 12.51 |
May | 0.238547E+10 | 6330.17 | 01-MAY-07:03 | 7.17 | 5.31 | 0.372428E+09 | 842.89 | 27-MAY-12:09 | 15.83 | 10.60 |
June | 0.294358E+10 | 17648.71 | 14-JUN-07:03 | 12.00 | 12.00 | 0.409480E+09 | 842.89 | 24-JUN-12:20 | 16.67 | 12.61 |
July | 0.368198E+10 | 17874.62 | 13-JUL-07:03 | 13.17 | 12.51 | 0.417892E+09 | 842.90 | 22-JUL-12:09 | 27.17 | 17.06 |
August | 0.405727E+10 | 18073.98 | 15-AUG-07:02 | 17.17 | 13.06 | 0.430837E+09 | 842.93 | 19-AUG-12:00 | 21.00 | 15.44 |
September | 0.325950E+10 | 16580.12 | 02-SEP-07:03 | 13.83 | 12.78 | 0.407876E+09 | 842.92 | 23-SEP-12:00 | 19.00 | 14.78 |
October | 0.181943E+10 | 3341.08 | 06-OCT-07:03 | 3.83 | 3.69 | 0.354509E+09 | 842.90 | 07-OCT-12:20 | 16.33 | 10.17 |
November | 0.800532E+09 | 4595.77 | 29-NOV-08:03 | -0.7 | -1.6 | 0.307309E+09 | 644.15 | 25-NOV-13:50 | -0.7 | -1.6 |
December | 0.284944E+09 | 4345.35 | 31-DEC-09:04 | 0.33 | -0.2 | 0.316691E+09 | 637.68 | 02-DEC-13:30 | 0.33 | -0.2 |
Annual Sum or Average | 0.229847E+11 | 0.429929E+10 | ||||||||
Minimum of Months | 0.284944E+09 | 3341.08 | -5.7 | -6.7 | 0.288036E+09 | 637.68 | -0.7 | -1.6 | ||
Maximum of Months | 0.405727E+10 | 18073.98 | 17.50 | 13.06 | 0.430837E+09 | 842.93 | 27.17 | 17.06 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.363021E+09 | 5792.29 | 10-JAN-08:04 | -5.7 | -6.7 | 0.317066E+09 | 637.68 | 07-JAN-13:09 | -5.7 | -6.7 |
February | 0.371589E+09 | 4462.53 | 18-FEB-08:03 | 0.17 | -0.4 | 0.288007E+09 | 637.68 | 04-FEB-13:20 | 0.17 | -0.4 |
March | 0.562370E+09 | 4095.57 | 13-MAR-07:04 | 1.33 | 0.37 | 0.325966E+09 | 685.29 | 25-MAR-12:00 | 14.00 | 11.22 |
April | 0.190276E+10 | 7823.97 | 30-APR-08:63 | 17.50 | 12.51 | 0.346470E+09 | 842.90 | 29-APR-12:00 | 17.50 | 12.51 |
May | 0.220139E+10 | 4738.28 | 01-MAY-07:03 | 7.17 | 5.31 | 0.367764E+09 | 842.90 | 27-MAY-12:09 | 15.83 | 10.60 |
June | 0.273931E+10 | 16121.08 | 26-JUN-07:02 | 19.67 | 14.49 | 0.406665E+09 | 842.89 | 24-JUN-12:20 | 19.67 | 14.49 |
July | 0.348595E+10 | 17491.16 | 25-JUL-07:02 | 13.00 | 13.00 | 0.417040E+09 | 842.90 | 22-JUL-12:09 | 13.00 | 13.00 |
August | 0.387041E+10 | 17870.81 | 15-AUG-07:02 | 17.17 | 13.06 | 0.430728E+09 | 842.93 | 19-AUG-12:00 | 21.00 | 15.44 |
September | 0.305748E+10 | 14853.32 | 02-SEP-07:03 | 13.83 | 12.78 | 0.407114E+09 | 842.92 | 23-SEP-12:00 | 19.00 | 14.78 |
October | 0.161853E+10 | 3286.95 | 06-OCT-07:03 | 3.83 | 3.69 | 0.350792E+09 | 842.90 | 07-OCT-12:20 | 16.33 | 10.17 |
November | 0.646954E+09 | 4612.87 | 29-NOV-08:03 | -0.7 | -1.6 | 0.306963E+09 | 637.68 | 25-NOV-13:09 | -0.7 | -1.6 |
December | 0.210979E+09 | 4501.40 | 31-DEC-09:04 | 0.33 | -0.2 | 0.316666E+09 | 637.68 | 02-DEC-13:09 | 0.33 | -0.2 |
Annual Sum or Average | 0.210307E+11 | 0.428124E+10 | ||||||||
Minimum of Months | 0.210979E+09 | 3286.95 | -5.7 | -6.7 | 0.288007E+09 | 637.68 | -5.7 | -6.7 | ||
Maximum of Months | 0.387041E+10 | 17870.81 | 19.67 | 14.49 | 0.430728E+09 | 842.93 | 21.00 | 15.44 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.490680E+09 | 9497.09 | 10-JAN-09:05 | -3.8 | -5.4 | 0.108352E+10 | 1700.53 | 14-JAN-15:39 | 7.00 | 5.29 |
February | 0.508379E+09 | 9400.09 | 18-FEB-09:04 | 1.67 | 0.83 | 0.986534E+09 | 1700.53 | 04-FEB-15:00 | 1.67 | 0.83 |
March | 0.849452E+09 | 9218.69 | 15-MAR-08:04 | 2.00 | 1.57 | 0.111775E+10 | 1700.99 | 25-MAR-14:09 | 11.83 | 9.32 |
April | 0.375025E+10 | 9441.52 | 30-APR-09:03 | 18.33 | 12.10 | 0.115035E+10 | 2247.81 | 29-APR-14:00 | 18.33 | 12.10 |
May | 0.437211E+10 | 6633.75 | 22-MAY-15:00 | 24.00 | 16.08 | 0.121711E+10 | 2240.31 | 27-MAY-14:09 | 15.67 | 10.94 |
June | 0.535580E+10 | 30048.56 | 26-JUN-08:62 | 18.17 | 13.96 | 0.135105E+10 | 2247.86 | 24-JUN-14:20 | 18.17 | 13.96 |
July | 0.626826E+10 | 30861.64 | 24-JUL-08:62 | 14.17 | 13.49 | 0.141485E+10 | 2247.84 | 15-JUL-14:20 | 14.17 | 13.49 |
August | 0.678319E+10 | 23781.47 | 18-AUG-08:62 | 19.00 | 15.28 | 0.147718E+10 | 2247.91 | 19-AUG-14:30 | 19.50 | 14.96 |
September | 0.559047E+10 | 12541.68 | 14-SEP-08:62 | 17.00 | 12.99 | 0.137971E+10 | 2247.90 | 23-SEP-14:39 | 19.00 | 14.78 |
October | 0.318587E+10 | 7166.83 | 05-OCT-20:00 | 5.00 | 4.09 | 0.116180E+10 | 2247.80 | 07-OCT-14:00 | 19.00 | 10.10 |
November | 0.977571E+09 | 9151.91 | 28-NOV-09:04 | 2.17 | 0.49 | 0.104397E+10 | 1700.53 | 04-NOV-14:09 | 2.17 | 0.49 |
December | 0.216134E+09 | 9497.98 | 08-DEC-09:04 | 1.50 | 1.37 | 0.108524E+10 | 1700.53 | 02-DEC-15:09 | 1.50 | 1.37 |
Annual Sum or Average | 0.383482E+11 | 0.144691E+11 | ||||||||
Minimum of Months | 0.216134E+09 | 6633.75 | -3.8 | -5.4 | 0.986534E+09 | 1700.53 | 1.50 | 0.49 | ||
Maximum of Months | 0.678319E+10 | 30861.64 | 24.00 | 16.08 | 0.147718E+10 | 2247.91 | 19.50 | 14.96 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.219085E+09 | 5017.48 | 11-JAN-09:04 | -3.8 | -5.2 | 0.541839E+09 | 850.24 | 07-JAN-15:50 | -3.8 | -5.2 |
February | 0.226820E+09 | 4276.44 | 17-FEB-20:37 | -2.3 | -2.5 | 0.493340E+09 | 850.24 | 04-FEB-15:20 | -2.3 | -2.5 |
March | 0.386539E+09 | 3742.29 | 15-MAR-08:04 | 2.00 | 1.57 | 0.559307E+09 | 884.81 | 25-MAR-14:09 | 11.83 | 9.32 |
April | 0.160805E+10 | 9210.39 | 30-APR-09:03 | 18.33 | 12.10 | 0.588511E+09 | 1123.87 | 29-APR-14:09 | 18.33 | 12.10 |
May | 0.186309E+10 | 3504.16 | 22-MAY-15:00 | 24.00 | 16.08 | 0.623676E+09 | 1123.86 | 27-MAY-14:00 | 14.00 | 10.25 |
June | 0.236531E+10 | 16427.98 | 26-JUN-08:62 | 18.17 | 13.96 | 0.692588E+09 | 1123.87 | 24-JUN-14:20 | 18.17 | 13.96 |
July | 0.307745E+10 | 16998.09 | 25-JUL-08:62 | 13.17 | 13.07 | 0.713578E+09 | 1123.87 | 22-JUL-14:00 | 13.17 | 13.07 |
August | 0.345421E+10 | 16848.49 | 15-AUG-08:62 | 17.67 | 13.87 | 0.739441E+09 | 1123.90 | 19-AUG-14:00 | 20.00 | 15.13 |
September | 0.264752E+10 | 11675.03 | 14-SEP-08:62 | 17.00 | 12.99 | 0.698969E+09 | 1123.89 | 23-SEP-14:39 | 19.00 | 14.78 |
October | 0.131399E+10 | 3055.49 | 07-OCT-15:00 | 19.00 | 10.10 | 0.594885E+09 | 1123.84 | 07-OCT-14:20 | 19.00 | 10.10 |
November | 0.444507E+09 | 4176.98 | 29-NOV-09:04 | 1.17 | -0.2 | 0.522557E+09 | 850.24 | 04-NOV-14:09 | 1.17 | -0.2 |
December | 88765728.26 | 4683.24 | 27-DEC-09:04 | -0.7 | -0.8 | 0.542705E+09 | 850.24 | 09-DEC-15:00 | -0.7 | -0.8 |
Annual Sum or Average | 0.176953E+11 | 0.731140E+10 | ||||||||
Minimum of Months | 88765728.26 | 3055.49 | -3.8 | -5.2 | 0.493340E+09 | 850.24 | -3.8 | -5.2 | ||
Maximum of Months | 0.345421E+10 | 16998.09 | 24.00 | 16.08 | 0.739441E+09 | 1123.90 | 20.00 | 15.13 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.192439E+09 | 4747.87 | 12-JAN-09:04 | -1.0 | -2.8 | 0.541794E+09 | 850.24 | 07-JAN-15:09 | -1.0 | -2.8 |
February | 0.204900E+09 | 4257.97 | 13-FEB-09:04 | 1.33 | 0.56 | 0.493269E+09 | 850.24 | 04-FEB-15:50 | 1.33 | 0.56 |
March | 0.350549E+09 | 3816.17 | 15-MAR-08:04 | 2.00 | 1.57 | 0.559172E+09 | 879.68 | 25-MAR-14:09 | 11.83 | 9.32 |
April | 0.154998E+10 | 8275.18 | 30-APR-09:03 | 18.33 | 12.10 | 0.586551E+09 | 1123.87 | 29-APR-14:09 | 18.33 | 12.10 |
May | 0.180173E+10 | 3418.41 | 22-MAY-15:00 | 24.00 | 16.08 | 0.621283E+09 | 1123.85 | 27-MAY-14:50 | 14.33 | 10.40 |
June | 0.230321E+10 | 16265.53 | 26-JUN-08:62 | 18.17 | 13.96 | 0.690655E+09 | 1123.87 | 24-JUN-14:20 | 18.17 | 13.96 |
July | 0.299412E+10 | 16841.10 | 25-JUL-08:62 | 13.17 | 13.07 | 0.712957E+09 | 1123.87 | 22-JUL-14:00 | 13.17 | 13.07 |
August | 0.335831E+10 | 16693.50 | 15-AUG-08:62 | 17.67 | 13.87 | 0.739365E+09 | 1123.90 | 19-AUG-14:00 | 20.00 | 15.13 |
September | 0.257052E+10 | 10672.13 | 14-SEP-08:62 | 17.00 | 12.99 | 0.698286E+09 | 1123.89 | 23-SEP-14:39 | 19.00 | 14.78 |
October | 0.126319E+10 | 3031.40 | 05-OCT-20:00 | 5.00 | 4.09 | 0.592765E+09 | 1123.84 | 07-OCT-14:20 | 17.67 | 9.98 |
November | 0.402481E+09 | 4247.10 | 29-NOV-09:04 | 1.17 | -0.2 | 0.522406E+09 | 850.24 | 04-NOV-14:30 | 1.17 | -0.2 |
December | 78391789.92 | 4659.15 | 27-DEC-09:04 | -0.7 | -0.8 | 0.542683E+09 | 850.24 | 09-DEC-15:30 | -0.7 | -0.8 |
Annual Sum or Average | 0.170698E+11 | 0.730119E+10 | ||||||||
Minimum of Months | 78391789.92 | 3031.40 | -1.0 | -2.8 | 0.493269E+09 | 850.24 | -1.0 | -2.8 | ||
Maximum of Months | 0.335831E+10 | 16841.10 | 24.00 | 16.08 | 0.739365E+09 | 1123.90 | 20.00 | 15.13 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.151206E+09 | 4756.95 | 11-JAN-08:02 | -4.0 | -4.9 | 0.541567E+09 | 850.24 | 21-JAN-15:30 | 7.05 | 5.83 |
February | 0.142514E+09 | 4119.87 | 17-FEB-08:03 | -2.3 | -2.4 | 0.493091E+09 | 850.24 | 18-FEB-15:09 | 6.00 | 4.15 |
March | 0.281806E+09 | 3595.04 | 31-MAR-08:04 | 3.33 | 2.68 | 0.558688E+09 | 860.21 | 25-MAR-14:09 | 3.33 | 2.68 |
April | 0.147412E+10 | 4531.31 | 30-APR-15:00 | 24.00 | 13.13 | 0.578531E+09 | 1123.87 | 29-APR-14:09 | 24.00 | 13.13 |
May | 0.169270E+10 | 3132.04 | 22-MAY-15:00 | 24.00 | 16.08 | 0.611492E+09 | 1123.87 | 27-MAY-14:30 | 15.00 | 10.68 |
June | 0.216777E+10 | 4902.46 | 13-JUN-15:00 | 26.00 | 17.83 | 0.679164E+09 | 1123.89 | 24-JUN-14:30 | 18.50 | 13.33 |
July | 0.278008E+10 | 13691.54 | 23-JUL-09:01 | 20.17 | 15.71 | 0.708543E+09 | 1123.89 | 15-JUL-14:09 | 20.17 | 15.71 |
August | 0.308747E+10 | 4978.23 | 14-AUG-16:10 | 26.17 | 15.64 | 0.738094E+09 | 1123.90 | 26-AUG-14:20 | 17.67 | 14.64 |
September | 0.239481E+10 | 4728.70 | 13-SEP-14:30 | 23.00 | 16.22 | 0.692495E+09 | 1123.90 | 23-SEP-14:50 | 19.00 | 14.78 |
October | 0.121714E+10 | 2963.55 | 06-OCT-07:03 | 3.83 | 3.69 | 0.583394E+09 | 1123.87 | 07-OCT-14:00 | 19.00 | 10.10 |
November | 0.371050E+09 | 3756.42 | 17-NOV-09:04 | 3.50 | 2.12 | 0.521718E+09 | 850.24 | 18-NOV-15:20 | 8.67 | 6.28 |
December | 58703962.40 | 3903.99 | 27-DEC-08:03 | -1.0 | -1.4 | 0.542504E+09 | 850.24 | 02-DEC-15:30 | -1.0 | -1.4 |
Annual Sum or Average | 0.158194E+11 | 0.724928E+10 | ||||||||
Minimum of Months | 58703962.40 | 2963.55 | -4.0 | -4.9 | 0.493091E+09 | 850.24 | -1.0 | -1.4 | ||
Maximum of Months | 0.308747E+10 | 13691.54 | 26.17 | 17.83 | 0.738094E+09 | 1123.90 | 24.00 | 15.71 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 10926705.64 | 3173.89 | 16-JAN-10:04 | 5.75 | 4.80 | 0.541599E+09 | 850.24 | 07-JAN-15:09 | 5.75 | 4.80 |
February | 9224975.08 | 3296.78 | 23-FEB-09:04 | 5.33 | 3.83 | 0.493093E+09 | 850.24 | 18-FEB-15:09 | 5.33 | 3.83 |
March | 35649722.99 | 3326.59 | 12-MAR-09:04 | 5.17 | 2.49 | 0.558624E+09 | 850.31 | 25-MAR-14:09 | 11.83 | 9.32 |
April | 0.987381E+09 | 4294.07 | 30-APR-15:00 | 24.00 | 13.13 | 0.573563E+09 | 1123.87 | 29-APR-14:09 | 24.00 | 13.13 |
May | 0.113514E+10 | 2982.90 | 22-MAY-15:00 | 24.00 | 16.08 | 0.602719E+09 | 1103.29 | 27-MAY-14:09 | 15.67 | 10.94 |
June | 0.183926E+10 | 9112.37 | 26-JUN-08:62 | 18.17 | 13.96 | 0.664362E+09 | 1123.85 | 17-JUN-14:00 | 18.17 | 13.96 |
July | 0.244310E+10 | 16345.13 | 23-JUL-09:01 | 20.17 | 15.71 | 0.704886E+09 | 1123.87 | 22-JUL-14:09 | 20.17 | 15.71 |
August | 0.272756E+10 | 6241.92 | 20-AUG-09:02 | 16.83 | 13.42 | 0.737633E+09 | 1123.90 | 12-AUG-14:09 | 16.83 | 13.42 |
September | 0.200127E+10 | 4633.06 | 13-SEP-14:20 | 23.00 | 16.22 | 0.685232E+09 | 1123.88 | 09-SEP-14:30 | 23.00 | 16.22 |
October | 0.656799E+09 | 2920.33 | 30-OCT-08:04 | 7.17 | 6.56 | 0.574271E+09 | 1123.85 | 07-OCT-14:20 | 7.17 | 6.56 |
November | 54741004.46 | 3451.80 | 16-NOV-09:04 | 4.83 | 4.15 | 0.521748E+09 | 850.24 | 04-NOV-14:30 | 4.83 | 4.15 |
December | 1733644.54 | 2888.11 | 02-DEC-09:04 | 7.00 | 6.47 | 0.542506E+09 | 850.24 | 02-DEC-15:30 | 8.50 | 7.70 |
Annual Sum or Average | 0.119028E+11 | 0.720024E+10 | ||||||||
Minimum of Months | 1733644.54 | 2888.11 | 4.83 | 2.49 | 0.493093E+09 | 850.24 | 4.83 | 3.83 | ||
Maximum of Months | 0.272756E+10 | 16345.13 | 24.00 | 16.22 | 0.737633E+09 | 1123.90 | 24.00 | 16.22 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.202637E+10 | 47982.66 | 17-JAN-09:01 | 8.25 |
February | 0.128316E+10 | 47801.83 | 22-FEB-09:01 | 8.00 |
March | 0.117473E+10 | 49378.63 | 09-MAR-09:01 | 11.00 |
April | 0.193125E+09 | 46935.06 | 11-APR-08:61 | 7.17 |
May | 0.112611E+09 | 45785.75 | 06-MAY-08:61 | 8.17 |
June | 72827281.06 | 1156.03 | 08-JUN-08:10 | 11.00 |
July | 74077547.09 | 1190.19 | 23-JUL-07:07 | 18.17 |
August | 72452620.15 | 766.63 | 04-AUG-07:13 | 13.33 |
September | 74323761.35 | 769.78 | 08-SEP-07:13 | 10.67 |
October | 0.192175E+09 | 48025.82 | 21-OCT-08:61 | 8.50 |
November | 0.868475E+09 | 47465.66 | 18-NOV-09:01 | 7.00 |
December | 0.262303E+10 | 48389.27 | 04-DEC-09:01 | 8.17 |
Annual Sum or Average | 0.876736E+10 | |||
Minimum of Months | 72452620.15 | 766.63 | 7.00 | |
Maximum of Months | 0.262303E+10 | 49378.63 | 18.17 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.538992E+09 | 23803.95 | 13-JAN-09:01 | 1.17 |
February | 0.265178E+09 | 23819.59 | 17-FEB-09:01 | 1.33 |
March | 0.227290E+09 | 15253.61 | 16-MAR-08:61 | 4.00 |
April | 0.101405E+09 | 4251.11 | 01-APR-08:06 | 5.50 |
May | 0.105047E+09 | 1100.06 | 19-MAY-07:35 | 9.00 |
June | 91182272.61 | 1054.81 | 14-JUN-07:13 | 12.00 |
July | 91327149.14 | 1529.11 | 23-JUL-07:07 | 18.17 |
August | 93780590.32 | 1202.43 | 06-AUG-07:10 | 13.17 |
September | 92145890.45 | 1080.80 | 21-SEP-07:25 | 10.00 |
October | 0.107240E+09 | 1097.83 | 28-OCT-08:06 | 8.17 |
November | 0.197489E+09 | 20283.41 | 29-NOV-09:01 | 1.17 |
December | 0.692990E+09 | 23998.62 | 29-DEC-09:01 | 2.00 |
Annual Sum or Average | 0.260407E+10 | |||
Minimum of Months | 91182272.61 | 1054.81 | 1.17 | |
Maximum of Months | 0.692990E+09 | 23998.62 | 18.17 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.851848E+09 | 22675.50 | 09-JAN-08:61 | -2.0 |
February | 0.479824E+09 | 23171.79 | 13-FEB-08:61 | 1.00 |
March | 0.412569E+09 | 17120.59 | 05-MAR-09:02 | 5.17 |
April | 0.110840E+09 | 2069.42 | 08-APR-07:07 | 2.50 |
May | 98619172.74 | 1053.33 | 28-MAY-08:00 | 9.00 |
June | 96009267.19 | 998.84 | 28-JUN-07:00 | 11.00 |
July | 0.104315E+09 | 2028.84 | 22-JUL-17:12 | 29.33 |
August | 0.100231E+09 | 1001.07 | 08-AUG-07:00 | 16.00 |
September | 97025250.66 | 1010.94 | 21-SEP-07:00 | 7.00 |
October | 0.108560E+09 | 3258.70 | 23-OCT-08:61 | 7.33 |
November | 0.355487E+09 | 16896.08 | 29-NOV-08:62 | -0.7 |
December | 0.108187E+10 | 23925.05 | 25-DEC-09:01 | 4.17 |
Annual Sum or Average | 0.389720E+10 | |||
Minimum of Months | 96009267.19 | 998.84 | -2.0 | |
Maximum of Months | 0.108187E+10 | 23925.05 | 29.33 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.977648E+09 | 23604.30 | 01-JAN-09:02 | 4.00 |
February | 0.585552E+09 | 23680.93 | 26-FEB-09:02 | 4.33 |
March | 0.505670E+09 | 22022.81 | 05-MAR-09:02 | 5.17 |
April | 0.121139E+09 | 4116.58 | 08-APR-08:61 | 5.33 |
May | 99120382.23 | 1219.75 | 06-MAY-07:10 | 6.33 |
June | 96276637.38 | 1000.03 | 28-JUN-07:00 | 11.00 |
July | 0.104565E+09 | 2033.38 | 22-JUL-17:12 | 29.33 |
August | 0.100479E+09 | 1002.11 | 08-AUG-07:00 | 16.00 |
September | 97278070.24 | 1012.62 | 21-SEP-07:00 | 7.00 |
October | 0.114579E+09 | 2047.28 | 23-OCT-07:03 | 4.50 |
November | 0.442209E+09 | 20954.58 | 29-NOV-08:62 | -0.7 |
December | 0.123237E+10 | 23884.10 | 25-DEC-09:01 | 4.17 |
Annual Sum or Average | 0.447689E+10 | |||
Minimum of Months | 96276637.38 | 1000.03 | -0.7 | |
Maximum of Months | 0.123237E+10 | 23884.10 | 29.33 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.116416E+10 | 24041.29 | 15-JAN-09:02 | 5.17 |
February | 0.742756E+09 | 23844.62 | 26-FEB-09:02 | 4.33 |
March | 0.656586E+09 | 24280.62 | 06-MAR-08:62 | 6.17 |
April | 0.136357E+09 | 3723.10 | 02-APR-08:63 | 7.33 |
May | 0.100374E+09 | 1191.74 | 17-MAY-07:10 | 7.17 |
June | 96179941.88 | 997.75 | 28-JUN-07:00 | 11.00 |
July | 0.104333E+09 | 2034.23 | 22-JUL-17:12 | 29.33 |
August | 0.100256E+09 | 999.20 | 08-AUG-07:00 | 16.00 |
September | 97095294.77 | 1010.74 | 27-SEP-07:00 | 10.00 |
October | 0.136621E+09 | 4678.67 | 23-OCT-07:03 | 4.50 |
November | 0.559921E+09 | 23111.92 | 28-NOV-08:62 | 1.17 |
December | 0.146507E+10 | 24061.63 | 25-DEC-09:01 | 4.17 |
Annual Sum or Average | 0.535971E+10 | |||
Minimum of Months | 96179941.88 | 997.75 | 1.17 | |
Maximum of Months | 0.146507E+10 | 24280.62 | 29.33 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.206767E+10 | 48178.30 | 29-JAN-10:01 | 11.17 |
February | 0.126533E+10 | 46729.39 | 22-FEB-09:01 | 8.00 |
March | 0.109716E+10 | 48148.44 | 09-MAR-09:01 | 11.00 |
April | 0.179617E+09 | 47029.32 | 02-APR-09:01 | 9.17 |
May | 99423718.96 | 33221.60 | 17-MAY-08:61 | 8.17 |
June | 74294865.75 | 758.36 | 14-JUN-07:13 | 12.00 |
July | 85140003.04 | 2889.61 | 22-JUL-17:03 | 29.17 |
August | 76473530.53 | 758.80 | 04-AUG-07:13 | 13.33 |
September | 73774508.01 | 761.62 | 08-SEP-07:13 | 10.67 |
October | 0.212267E+09 | 47080.19 | 25-OCT-08:61 | 9.33 |
November | 0.948646E+09 | 48047.06 | 24-NOV-09:01 | 11.17 |
December | 0.261285E+10 | 47415.37 | 04-DEC-09:01 | 8.17 |
Annual Sum or Average | 0.879266E+10 | |||
Minimum of Months | 73774508.01 | 758.36 | 8.00 | |
Maximum of Months | 0.261285E+10 | 48178.30 | 29.17 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.125500E+10 | 25100.92 | 17-JAN-09:01 | 8.25 |
February | 0.807124E+09 | 24920.98 | 22-FEB-09:01 | 8.00 |
March | 0.721367E+09 | 25126.03 | 20-MAR-08:61 | 8.50 |
April | 0.153082E+09 | 23046.42 | 01-APR-08:61 | 5.50 |
May | 0.107998E+09 | 3146.79 | 17-MAY-08:61 | 8.17 |
June | 0.101455E+09 | 1031.17 | 14-JUN-07:13 | 12.00 |
July | 0.111420E+09 | 2043.40 | 22-JUL-17:12 | 29.33 |
August | 0.104807E+09 | 1030.65 | 04-AUG-07:13 | 13.33 |
September | 0.100369E+09 | 1053.25 | 21-SEP-07:25 | 10.00 |
October | 0.162392E+09 | 22841.69 | 23-OCT-08:61 | 7.33 |
November | 0.612692E+09 | 24932.83 | 13-NOV-09:01 | 8.00 |
December | 0.155202E+10 | 25270.44 | 04-DEC-09:01 | 8.17 |
Annual Sum or Average | 0.578973E+10 | |||
Minimum of Months | 0.100369E+09 | 1030.65 | 5.50 | |
Maximum of Months | 0.155202E+10 | 25270.44 | 29.33 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.133132E+10 | 25553.03 | 29-JAN-10:01 | 11.17 |
February | 0.882490E+09 | 24829.17 | 22-FEB-09:01 | 8.00 |
March | 0.786373E+09 | 25537.16 | 09-MAR-09:01 | 11.00 |
April | 0.162664E+09 | 24205.01 | 01-APR-08:61 | 5.50 |
May | 0.110098E+09 | 6222.93 | 17-MAY-08:61 | 8.17 |
June | 0.101280E+09 | 1026.07 | 14-JUN-07:13 | 12.00 |
July | 0.111211E+09 | 2041.70 | 22-JUL-17:12 | 29.33 |
August | 0.104547E+09 | 1025.97 | 04-AUG-07:13 | 13.33 |
September | 0.100173E+09 | 1048.73 | 21-SEP-07:25 | 10.00 |
October | 0.183370E+09 | 24641.96 | 23-OCT-08:61 | 7.33 |
November | 0.668744E+09 | 24842.25 | 13-NOV-09:01 | 8.00 |
December | 0.162984E+10 | 25172.95 | 04-DEC-09:01 | 8.17 |
Annual Sum or Average | 0.617211E+10 | |||
Minimum of Months | 0.100173E+09 | 1025.97 | 5.50 | |
Maximum of Months | 0.162984E+10 | 25553.03 | 29.33 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.164333E+10 | 25694.54 | 29-JAN-10:01 | 11.17 |
February | 0.113977E+10 | 24925.71 | 22-FEB-09:01 | 8.00 |
March | 0.103377E+10 | 25663.40 | 09-MAR-09:01 | 11.00 |
April | 0.203796E+09 | 25198.85 | 02-APR-09:01 | 9.17 |
May | 0.104748E+09 | 25175.05 | 18-MAY-08:62 | 11.03 |
June | 5049010.97 | 14009.10 | 08-JUN-08:62 | 11.00 |
July | 12108004.40 | 2038.41 | 22-JUL-17:12 | 29.33 |
August | 1047237.55 | 616.81 | 20-AUG-16:03 | 23.67 |
September | 291518.71 | 268.11 | 24-SEP-16:03 | 21.83 |
October | 0.246877E+09 | 25306.43 | 20-OCT-08:62 | 11.83 |
November | 0.888599E+09 | 25656.04 | 24-NOV-09:01 | 11.17 |
December | 0.197051E+10 | 25052.15 | 04-DEC-09:01 | 8.17 |
Annual Sum or Average | 0.724989E+10 | |||
Minimum of Months | 291518.71 | 268.11 | 8.00 | |
Maximum of Months | 0.197051E+10 | 25694.54 | 29.33 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.324039E+10 | 28183.91 | 10-JAN-08:61 | -5.7 |
February | 0.253553E+10 | 28003.64 | 13-FEB-08:61 | 1.00 |
March | 0.232781E+10 | 27792.78 | 05-MAR-09:02 | 5.17 |
April | 0.435906E+09 | 25795.10 | 02-APR-09:01 | 9.17 |
May | 0.278162E+09 | 25581.61 | 19-MAY-08:61 | 9.12 |
June | 0.102223E+09 | 3119.28 | 08-JUN-08:62 | 11.00 |
July | 0.109722E+09 | 2069.51 | 22-JUL-17:12 | 29.33 |
August | 0.104213E+09 | 1060.65 | 04-AUG-07:13 | 13.33 |
September | 0.100642E+09 | 1079.07 | 21-SEP-07:25 | 10.00 |
October | 0.641138E+09 | 25938.72 | 20-OCT-08:62 | 11.83 |
November | 0.193043E+10 | 27828.52 | 29-NOV-08:62 | -0.7 |
December | 0.374491E+10 | 28167.52 | 26-DEC-08:61 | 1.17 |
Annual Sum or Average | 0.155511E+11 | |||
Minimum of Months | 0.100642E+09 | 1060.65 | -5.7 | |
Maximum of Months | 0.374491E+10 | 28183.91 | 29.33 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.869933E+10 | 5321.43 | 01-JAN-10:09 | 0.223514E+10 | 1348.26 | 01-JAN-10:09 |
February | 0.786449E+10 | 5321.43 | 01-FEB-10:09 | 0.202238E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.870841E+10 | 5321.43 | 01-MAR-10:09 | 0.224215E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.843013E+10 | 5321.43 | 01-APR-09:09 | 0.216638E+10 | 1348.26 | 01-APR-09:09 |
May | 0.869933E+10 | 5321.43 | 01-MAY-09:09 | 0.223514E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.843013E+10 | 5321.43 | 01-JUN-09:09 | 0.217123E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.870841E+10 | 5321.43 | 01-JUL-09:09 | 0.223729E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.869933E+10 | 5321.43 | 01-AUG-09:09 | 0.223756E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.843920E+10 | 5321.43 | 01-SEP-09:09 | 0.217096E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.869933E+10 | 5321.43 | 01-OCT-09:09 | 0.223514E+10 | 1348.26 | 01-OCT-09:09 |
November | 0.840290E+10 | 5321.43 | 01-NOV-09:09 | 0.215964E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.871748E+10 | 5321.43 | 01-DEC-10:09 | 0.224431E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.102498E+12 | 0.263573E+11 | ||||
Minimum of Months | 0.786449E+10 | 5321.43 | 0.202238E+10 | 1348.26 | ||
Maximum of Months | 0.871748E+10 | 5321.43 | 0.224431E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.479410E+10 | 2932.57 | 01-JAN-10:09 | 0.111757E+10 | 674.13 | 01-JAN-10:09 |
February | 0.433403E+10 | 2932.57 | 01-FEB-10:09 | 0.101119E+10 | 674.13 | 01-FEB-10:09 |
March | 0.479910E+10 | 2932.57 | 01-MAR-10:09 | 0.112107E+10 | 674.13 | 01-MAR-10:09 |
April | 0.464574E+10 | 2932.57 | 01-APR-09:09 | 0.108319E+10 | 674.13 | 01-APR-09:09 |
May | 0.479410E+10 | 2932.57 | 01-MAY-09:09 | 0.111757E+10 | 674.13 | 01-MAY-09:09 |
June | 0.464574E+10 | 2932.57 | 01-JUN-09:09 | 0.108562E+10 | 674.13 | 01-JUN-09:09 |
July | 0.479910E+10 | 2932.57 | 01-JUL-09:09 | 0.111865E+10 | 674.13 | 01-JUL-09:09 |
August | 0.479410E+10 | 2932.57 | 01-AUG-09:09 | 0.111878E+10 | 674.13 | 01-AUG-09:09 |
September | 0.465074E+10 | 2932.57 | 01-SEP-09:09 | 0.108548E+10 | 674.13 | 01-SEP-09:09 |
October | 0.479410E+10 | 2932.57 | 01-OCT-09:09 | 0.111757E+10 | 674.13 | 01-OCT-09:09 |
November | 0.463074E+10 | 2932.57 | 01-NOV-09:09 | 0.107982E+10 | 674.13 | 01-NOV-09:09 |
December | 0.480410E+10 | 2932.57 | 01-DEC-10:09 | 0.112215E+10 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.564857E+11 | 0.131787E+11 | ||||
Minimum of Months | 0.433403E+10 | 2932.57 | 0.101119E+10 | 674.13 | ||
Maximum of Months | 0.480410E+10 | 2932.57 | 0.112215E+10 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.338042E+10 | 2599.23 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.306129E+10 | 2599.23 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.345133E+10 | 2599.23 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.327995E+10 | 2599.23 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.341588E+10 | 2599.23 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.333314E+10 | 2599.23 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.336269E+10 | 2599.23 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.345133E+10 | 2599.23 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.327995E+10 | 2599.23 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.338042E+10 | 2599.23 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.327995E+10 | 2599.23 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.336269E+10 | 2599.23 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.400390E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.306129E+10 | 2599.23 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.345133E+10 | 2599.23 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.338042E+10 | 2599.23 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.306129E+10 | 2599.23 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.345133E+10 | 2599.23 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.327995E+10 | 2599.23 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.341588E+10 | 2599.23 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.333314E+10 | 2599.23 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.336269E+10 | 2599.23 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.345133E+10 | 2599.23 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.327995E+10 | 2599.23 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.338042E+10 | 2599.23 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.327995E+10 | 2599.23 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.336269E+10 | 2599.23 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.400390E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.306129E+10 | 2599.23 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.345133E+10 | 2599.23 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.338042E+10 | 2599.23 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.306129E+10 | 2599.23 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.345133E+10 | 2599.23 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.327995E+10 | 2599.23 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.341588E+10 | 2599.23 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.333314E+10 | 2599.23 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.336269E+10 | 2599.23 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.345133E+10 | 2599.23 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.327995E+10 | 2599.23 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.338042E+10 | 2599.23 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.327995E+10 | 2599.23 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.336269E+10 | 2599.23 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.400390E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.306129E+10 | 2599.23 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.345133E+10 | 2599.23 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.447638E+10 | 3746.51 | 01-JAN-11:09 | 0.162546E+10 | 1348.26 | 01-JAN-11:09 |
February | 0.405472E+10 | 3746.51 | 01-FEB-10:09 | 0.147229E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.457860E+10 | 3746.51 | 01-MAR-10:09 | 0.166213E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.434435E+10 | 3746.51 | 01-APR-09:09 | 0.157746E+10 | 1348.26 | 01-APR-09:09 |
May | 0.452749E+10 | 3746.51 | 01-MAY-09:09 | 0.164379E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.442101E+10 | 3746.51 | 01-JUN-09:09 | 0.160496E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.445083E+10 | 3746.51 | 01-JUL-09:09 | 0.161629E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.457860E+10 | 3746.51 | 01-AUG-09:09 | 0.166213E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.434435E+10 | 3746.51 | 01-SEP-09:09 | 0.157746E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.447638E+10 | 3746.51 | 01-OCT-10:09 | 0.162546E+10 | 1348.26 | 01-OCT-10:09 |
November | 0.434435E+10 | 3746.51 | 01-NOV-09:09 | 0.157746E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.445083E+10 | 3746.51 | 01-DEC-10:09 | 0.161629E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.530479E+11 | 0.192612E+11 | ||||
Minimum of Months | 0.405472E+10 | 3746.51 | 0.147229E+10 | 1348.26 | ||
Maximum of Months | 0.457860E+10 | 3746.51 | 0.166213E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.230731E+10 | 1931.10 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.208997E+10 | 1931.10 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.236000E+10 | 1931.10 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.223926E+10 | 1931.10 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.233366E+10 | 1931.10 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.227877E+10 | 1931.10 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.229414E+10 | 1931.10 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.236000E+10 | 1931.10 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.223926E+10 | 1931.10 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.230731E+10 | 1931.10 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.223926E+10 | 1931.10 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.229414E+10 | 1931.10 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.273431E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.208997E+10 | 1931.10 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.236000E+10 | 1931.10 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.230731E+10 | 1931.10 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.208997E+10 | 1931.10 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.236000E+10 | 1931.10 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.223926E+10 | 1931.10 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.233366E+10 | 1931.10 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.227877E+10 | 1931.10 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.229414E+10 | 1931.10 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.236000E+10 | 1931.10 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.223926E+10 | 1931.10 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.230731E+10 | 1931.10 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.223926E+10 | 1931.10 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.229414E+10 | 1931.10 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.273431E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.208997E+10 | 1931.10 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.236000E+10 | 1931.10 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.230731E+10 | 1931.10 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.208997E+10 | 1931.10 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.236000E+10 | 1931.10 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.223926E+10 | 1931.10 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.233366E+10 | 1931.10 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.227877E+10 | 1931.10 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.229414E+10 | 1931.10 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.236000E+10 | 1931.10 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.223926E+10 | 1931.10 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.230731E+10 | 1931.10 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.223926E+10 | 1931.10 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.229414E+10 | 1931.10 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.273431E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.208997E+10 | 1931.10 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.236000E+10 | 1931.10 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.230731E+10 | 1931.10 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.208997E+10 | 1931.10 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.236000E+10 | 1931.10 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.223926E+10 | 1931.10 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.233366E+10 | 1931.10 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.227877E+10 | 1931.10 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.229414E+10 | 1931.10 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.236000E+10 | 1931.10 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.223926E+10 | 1931.10 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.230731E+10 | 1931.10 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.223926E+10 | 1931.10 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.229414E+10 | 1931.10 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.273431E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.208997E+10 | 1931.10 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.236000E+10 | 1931.10 | 0.831065E+09 | 674.13 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.869933E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377953E+10 |
February | 0.305697E+10 | 0.786449E+10 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340581E+10 |
March | 0.335708E+10 | 0.870841E+10 | 0.224215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322587E+10 |
April | 0.327081E+10 | 0.843013E+10 | 0.216638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 262347.78 | 0.234250E+10 |
May | 0.336680E+10 | 0.869933E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18090.24 | 0.283190E+10 |
June | 0.325380E+10 | 0.843013E+10 | 0.217123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10780955.57 | 0.211261E+10 |
July | 0.339353E+10 | 0.870841E+10 | 0.223729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47464682.74 | 0.182149E+10 |
August | 0.334857E+10 | 0.869933E+10 | 0.223756E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6334934.45 | 0.148312E+10 |
September | 0.327932E+10 | 0.843920E+10 | 0.217096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186181E+10 |
October | 0.338624E+10 | 0.869933E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261112E+10 |
November | 0.327446E+10 | 0.840290E+10 | 0.215964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339937E+10 |
December | 0.340325E+10 | 0.871748E+10 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423220E+10 |
Annual Sum or Average | 0.397770E+11 | 0.102498E+12 | 0.263573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64861010.78 | 0.331073E+11 |
Minimum of Months | 0.305697E+10 | 0.786449E+10 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148312E+10 |
Maximum of Months | 0.340325E+10 | 0.871748E+10 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47464682.74 | 0.423220E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.479410E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204903E+10 |
February | 0.152844E+10 | 0.433403E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180678E+10 |
March | 0.167849E+10 | 0.479910E+10 | 0.112107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175197E+10 |
April | 0.163536E+10 | 0.464574E+10 | 0.108319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 144863.35 | 0.133439E+10 |
May | 0.168335E+10 | 0.479410E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9971.60 | 0.150677E+10 |
June | 0.162685E+10 | 0.464574E+10 | 0.108562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5884587.97 | 0.110528E+10 |
July | 0.169671E+10 | 0.479910E+10 | 0.111865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25990922.91 | 0.908926E+09 |
August | 0.167424E+10 | 0.479410E+10 | 0.111878E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3452551.33 | 0.729089E+09 |
September | 0.163961E+10 | 0.465074E+10 | 0.108548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.958341E+09 |
October | 0.169307E+10 | 0.479410E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144224E+10 |
November | 0.163718E+10 | 0.463074E+10 | 0.107982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178317E+10 |
December | 0.170157E+10 | 0.480410E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219295E+10 |
Annual Sum or Average | 0.198880E+11 | 0.564857E+11 | 0.131787E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35482897.16 | 0.175689E+11 |
Minimum of Months | 0.152844E+10 | 0.433403E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.729089E+09 |
Maximum of Months | 0.170157E+10 | 0.480410E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25990922.91 | 0.219295E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.338042E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205739E+10 |
February | 0.914877E+09 | 0.306129E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182442E+10 |
March | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175649E+10 |
April | 0.984131E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69104.31 | 0.132222E+10 |
May | 0.102058E+10 | 0.341588E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9971.20 | 0.152124E+10 |
June | 0.998711E+09 | 0.333314E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5843750.95 | 0.114630E+10 |
July | 0.100600E+10 | 0.336269E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25540694.55 | 0.954063E+09 |
August | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3452542.81 | 0.766684E+09 |
September | 0.984131E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.989044E+09 |
October | 0.100722E+10 | 0.338042E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144238E+10 |
November | 0.973196E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180044E+10 |
December | 0.100600E+10 | 0.336269E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223152E+10 |
Annual Sum or Average | 0.119700E+11 | 0.400390E+11 | 0.104672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34916063.82 | 0.178122E+11 |
Minimum of Months | 0.914877E+09 | 0.306129E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.766684E+09 |
Maximum of Months | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25540694.55 | 0.223152E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.338042E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205572E+10 |
February | 0.914877E+09 | 0.306129E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182260E+10 |
March | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175511E+10 |
April | 0.984131E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69104.31 | 0.130916E+10 |
May | 0.102058E+10 | 0.341588E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9970.77 | 0.150599E+10 |
June | 0.998711E+09 | 0.333314E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5843883.05 | 0.114099E+10 |
July | 0.100600E+10 | 0.336269E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25536953.67 | 0.951804E+09 |
August | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3452535.70 | 0.766021E+09 |
September | 0.984131E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.987198E+09 |
October | 0.100722E+10 | 0.338042E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143110E+10 |
November | 0.973196E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179654E+10 |
December | 0.100600E+10 | 0.336269E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222802E+10 |
Annual Sum or Average | 0.119700E+11 | 0.400390E+11 | 0.104672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34912447.51 | 0.177503E+11 |
Minimum of Months | 0.914877E+09 | 0.306129E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.766021E+09 |
Maximum of Months | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25536953.67 | 0.222802E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.338042E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205473E+10 |
February | 0.914877E+09 | 0.306129E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182114E+10 |
March | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175386E+10 |
April | 0.984131E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69104.31 | 0.129255E+10 |
May | 0.102058E+10 | 0.341588E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9970.42 | 0.148595E+10 |
June | 0.998711E+09 | 0.333314E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5844176.04 | 0.112833E+10 |
July | 0.100600E+10 | 0.336269E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25548537.21 | 0.946309E+09 |
August | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3452525.96 | 0.764294E+09 |
September | 0.984131E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.982866E+09 |
October | 0.100722E+10 | 0.338042E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141648E+10 |
November | 0.973196E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179352E+10 |
December | 0.100600E+10 | 0.336269E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222511E+10 |
Annual Sum or Average | 0.119700E+11 | 0.400390E+11 | 0.104672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34924313.95 | 0.176651E+11 |
Minimum of Months | 0.914877E+09 | 0.306129E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.764294E+09 |
Maximum of Months | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25548537.21 | 0.222511E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.447638E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.369673E+10 |
February | 0.313522E+10 | 0.405472E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329049E+10 |
March | 0.355148E+10 | 0.457860E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315500E+10 |
April | 0.338259E+10 | 0.434435E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 123960.25 | 0.227057E+10 |
May | 0.349753E+10 | 0.452749E+10 | 0.164379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17874.56 | 0.264719E+10 |
June | 0.343071E+10 | 0.442101E+10 | 0.160496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10510377.66 | 0.199335E+10 |
July | 0.344942E+10 | 0.445083E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45993863.36 | 0.171256E+10 |
August | 0.355148E+10 | 0.457860E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6207463.64 | 0.140351E+10 |
September | 0.338259E+10 | 0.434435E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176724E+10 |
October | 0.344359E+10 | 0.447638E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250754E+10 |
November | 0.331698E+10 | 0.434435E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325346E+10 |
December | 0.344942E+10 | 0.445083E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403859E+10 |
Annual Sum or Average | 0.410346E+11 | 0.530479E+11 | 0.192612E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 62853539.48 | 0.317362E+11 |
Minimum of Months | 0.313522E+10 | 0.405472E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140351E+10 |
Maximum of Months | 0.355148E+10 | 0.457860E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45993863.36 | 0.403859E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205244E+10 |
February | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182051E+10 |
March | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175219E+10 |
April | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69104.31 | 0.128271E+10 |
May | 0.174872E+10 | 0.233366E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9967.20 | 0.148074E+10 |
June | 0.171530E+10 | 0.227877E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5844946.33 | 0.112274E+10 |
July | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25577081.43 | 0.947085E+09 |
August | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3452457.97 | 0.768086E+09 |
September | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.985783E+09 |
October | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141011E+10 |
November | 0.165844E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179567E+10 |
December | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222587E+10 |
Annual Sum or Average | 0.205167E+11 | 0.273431E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34953557.25 | 0.176439E+11 |
Minimum of Months | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.768086E+09 |
Maximum of Months | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25577081.43 | 0.222587E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205169E+10 |
February | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181952E+10 |
March | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175138E+10 |
April | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69104.31 | 0.127828E+10 |
May | 0.174872E+10 | 0.233366E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9967.17 | 0.147437E+10 |
June | 0.171530E+10 | 0.227877E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5845117.20 | 0.111794E+10 |
July | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25581951.14 | 0.944708E+09 |
August | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3452452.44 | 0.767116E+09 |
September | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.983682E+09 |
October | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140488E+10 |
November | 0.165844E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179421E+10 |
December | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222472E+10 |
Annual Sum or Average | 0.205167E+11 | 0.273431E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34958592.27 | 0.176125E+11 |
Minimum of Months | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.767116E+09 |
Maximum of Months | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25581951.14 | 0.222472E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204747E+10 |
February | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181455E+10 |
March | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174633E+10 |
April | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69104.31 | 0.125719E+10 |
May | 0.174872E+10 | 0.233366E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9964.90 | 0.144420E+10 |
June | 0.171530E+10 | 0.227877E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5845681.27 | 0.108794E+10 |
July | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25594464.73 | 0.928403E+09 |
August | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3452413.67 | 0.759107E+09 |
September | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.966409E+09 |
October | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137880E+10 |
November | 0.165844E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178559E+10 |
December | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221822E+10 |
Annual Sum or Average | 0.205167E+11 | 0.273431E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34971628.88 | 0.174342E+11 |
Minimum of Months | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.759107E+09 |
Maximum of Months | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25594464.73 | 0.221822E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216482E+10 |
February | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198952E+10 |
March | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184947E+10 |
April | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69520.41 | 0.136365E+10 |
May | 0.174872E+10 | 0.233366E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10172.49 | 0.174174E+10 |
June | 0.171530E+10 | 0.227877E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6047548.85 | 0.131555E+10 |
July | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26361250.85 | 0.117031E+10 |
August | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3579714.57 | 0.954065E+09 |
September | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115524E+10 |
October | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154805E+10 |
November | 0.165844E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201847E+10 |
December | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253286E+10 |
Annual Sum or Average | 0.205167E+11 | 0.273431E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36068207.17 | 0.198037E+11 |
Minimum of Months | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.954065E+09 |
Maximum of Months | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26361250.85 | 0.253286E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 5321.43 | 01-JAN-10:09 | 1348.26 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 8006.93 | 11-JAN-18:00 |
February | 4050.04 | 03-FEB-13:09 | 5321.43 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 6020.31 | 24-FEB-18:00 |
March | 4050.04 | 03-MAR-13:09 | 5321.43 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6220.37 | 15-MAR-12:00 |
April | 4050.04 | 01-APR-12:09 | 5321.43 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 29.89 | 30-APR-17:00 | 4388.34 | 10-APR-11:10 |
May | 4050.04 | 05-MAY-12:09 | 5321.43 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.15 | 22-MAY-15:00 | 4531.09 | 01-MAY-15:00 |
June | 4050.04 | 02-JUN-12:09 | 5321.43 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 905.87 | 13-JUN-17:00 | 3677.58 | 07-JUN-11:10 |
July | 4050.04 | 01-JUL-12:09 | 5321.43 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1477.90 | 22-JUL-15:00 | 3232.15 | 04-JUL-14:00 |
August | 4050.04 | 04-AUG-12:09 | 5321.43 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 903.22 | 14-AUG-17:00 | 2483.37 | 30-AUG-17:00 |
September | 4050.04 | 01-SEP-12:09 | 5321.43 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 3448.94 | 29-SEP-17:00 |
October | 4050.04 | 01-OCT-12:09 | 5321.43 | 01-OCT-09:09 | 1348.26 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3955.48 | 27-OCT-17:00 |
November | 4050.04 | 03-NOV-12:09 | 5321.43 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6537.86 | 28-NOV-18:00 |
December | 4050.04 | 01-DEC-13:09 | 5321.43 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 7437.13 | 29-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 5321.43 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2483.37 | |||||
Maximum of Months | 4050.04 | 5321.43 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 1477.90 | 8006.93 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 2932.57 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4431.96 | 11-JAN-18:00 |
February | 2024.96 | 03-FEB-13:09 | 2932.57 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3322.40 | 24-FEB-18:00 |
March | 2024.96 | 03-MAR-13:09 | 2932.57 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3469.29 | 15-MAR-12:00 |
April | 2024.96 | 01-APR-12:09 | 2932.57 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.54 | 30-APR-17:00 | 2416.01 | 10-APR-11:10 |
May | 2024.96 | 05-MAY-12:09 | 2932.57 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.62 | 22-MAY-15:00 | 2610.10 | 01-MAY-15:00 |
June | 2024.96 | 02-JUN-12:09 | 2932.57 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.48 | 13-JUN-17:00 | 2200.05 | 07-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 2932.57 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 22-JUL-15:00 | 1973.77 | 04-JUL-14:00 |
August | 2024.96 | 04-AUG-12:09 | 2932.57 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.23 | 14-AUG-17:00 | 1343.79 | 30-AUG-17:00 |
September | 2024.96 | 01-SEP-12:09 | 2932.57 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 1981.36 | 30-SEP-11:10 |
October | 2024.96 | 01-OCT-12:09 | 2932.57 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2189.42 | 27-OCT-17:00 |
November | 2024.96 | 03-NOV-12:09 | 2932.57 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3590.34 | 28-NOV-18:00 |
December | 2024.96 | 01-DEC-13:09 | 2932.57 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4094.19 | 29-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2932.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1343.79 | |||||
Maximum of Months | 2024.96 | 2932.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 4431.96 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2599.23 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4431.96 | 11-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2599.23 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3322.40 | 24-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2599.23 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3469.29 | 15-MAR-12:00 |
April | 2024.96 | 01-APR-12:09 | 2599.23 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.51 | 30-APR-15:00 | 2416.01 | 10-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 2599.23 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.62 | 22-MAY-15:00 | 2601.43 | 01-MAY-15:00 |
June | 2024.96 | 03-JUN-12:09 | 2599.23 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.48 | 13-JUN-17:00 | 2187.45 | 07-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 2599.23 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 22-JUL-15:00 | 1939.41 | 04-JUL-14:00 |
August | 2024.96 | 05-AUG-12:09 | 2599.23 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.23 | 14-AUG-17:00 | 1343.79 | 30-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 2599.23 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 1986.53 | 30-SEP-11:10 |
October | 2024.96 | 07-OCT-12:09 | 2599.23 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2189.42 | 27-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2599.23 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3590.34 | 28-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2599.23 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4094.19 | 29-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2599.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1343.79 | |||||
Maximum of Months | 2024.96 | 2599.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 4431.96 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2599.23 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4431.96 | 11-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2599.23 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3322.40 | 24-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2599.23 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3469.29 | 15-MAR-12:00 |
April | 2024.96 | 01-APR-12:09 | 2599.23 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.51 | 30-APR-15:00 | 2416.01 | 10-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 2599.23 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.62 | 22-MAY-15:00 | 2595.56 | 01-MAY-15:00 |
June | 2024.96 | 03-JUN-12:09 | 2599.23 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.47 | 13-JUN-17:00 | 2163.28 | 07-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 2599.23 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 22-JUL-15:00 | 1920.83 | 04-JUL-14:00 |
August | 2024.96 | 05-AUG-12:09 | 2599.23 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.23 | 14-AUG-17:00 | 1343.80 | 30-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 2599.23 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 1984.99 | 30-SEP-11:10 |
October | 2024.96 | 07-OCT-12:09 | 2599.23 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2189.42 | 27-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2599.23 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3590.34 | 28-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2599.23 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4094.19 | 29-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2599.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1343.80 | |||||
Maximum of Months | 2024.96 | 2599.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 4431.96 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2599.23 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4431.96 | 11-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2599.23 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3322.40 | 24-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2599.23 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3469.29 | 15-MAR-12:00 |
April | 2024.96 | 01-APR-12:09 | 2599.23 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.51 | 30-APR-15:00 | 2416.01 | 10-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 2599.23 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.62 | 22-MAY-15:00 | 2571.05 | 01-MAY-15:00 |
June | 2024.96 | 03-JUN-12:09 | 2599.23 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.47 | 13-JUN-17:00 | 2109.85 | 07-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 2599.23 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 22-JUL-15:00 | 1878.94 | 04-JUL-14:00 |
August | 2024.96 | 05-AUG-12:09 | 2599.23 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.23 | 14-AUG-17:00 | 1343.80 | 30-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 2599.23 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 1978.49 | 30-SEP-11:10 |
October | 2024.96 | 07-OCT-12:09 | 2599.23 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2189.42 | 27-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2599.23 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3590.34 | 28-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2599.23 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4094.19 | 29-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2599.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1343.80 | |||||
Maximum of Months | 2024.96 | 2599.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 4431.96 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 3746.51 | 01-JAN-11:09 | 1348.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 7953.76 | 11-JAN-18:00 |
February | 5400.05 | 04-FEB-15:09 | 3746.51 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5964.69 | 24-FEB-18:00 |
March | 5400.05 | 04-MAR-15:09 | 3746.51 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6220.37 | 15-MAR-12:00 |
April | 5400.05 | 01-APR-14:09 | 3746.51 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 29.63 | 30-APR-15:00 | 4338.71 | 10-APR-11:10 |
May | 5400.05 | 06-MAY-14:09 | 3746.51 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 29.79 | 22-MAY-15:00 | 4512.29 | 01-MAY-15:00 |
June | 5400.05 | 03-JUN-14:09 | 3746.51 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 893.64 | 13-JUN-17:00 | 3607.99 | 07-JUN-11:10 |
July | 5400.05 | 01-JUL-14:09 | 3746.51 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1457.94 | 22-JUL-15:00 | 3124.34 | 04-JUL-14:00 |
August | 5400.05 | 05-AUG-14:09 | 3746.51 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 892.94 | 14-AUG-17:00 | 2418.33 | 30-AUG-17:00 |
September | 5400.05 | 02-SEP-14:09 | 3746.51 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 3490.00 | 30-SEP-11:10 |
October | 5400.05 | 07-OCT-14:09 | 3746.51 | 01-OCT-10:09 | 1348.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3929.21 | 27-OCT-17:00 |
November | 5400.05 | 04-NOV-14:09 | 3746.51 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6449.59 | 28-NOV-18:00 |
December | 5400.05 | 02-DEC-15:09 | 3746.51 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 7352.49 | 29-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 3746.51 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2418.33 | |||||
Maximum of Months | 5400.05 | 3746.51 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 1457.94 | 7953.76 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1931.10 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4431.96 | 11-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1931.10 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3322.40 | 24-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1931.10 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3469.29 | 15-MAR-12:00 |
April | 2699.95 | 01-APR-14:09 | 1931.10 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.51 | 30-APR-15:00 | 2416.01 | 10-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1931.10 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.61 | 22-MAY-15:00 | 2580.02 | 01-MAY-15:00 |
June | 2699.95 | 03-JUN-14:09 | 1931.10 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.47 | 13-JUN-17:00 | 2081.91 | 07-JUN-15:00 |
July | 2699.95 | 01-JUL-14:09 | 1931.10 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 22-JUL-15:00 | 1823.63 | 04-JUL-14:00 |
August | 2699.95 | 05-AUG-14:09 | 1931.10 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.23 | 14-AUG-17:00 | 1343.78 | 30-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1931.10 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 1973.36 | 30-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 1931.10 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2189.42 | 27-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1931.10 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3590.34 | 28-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1931.10 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4094.19 | 29-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1343.78 | |||||
Maximum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 4431.96 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1931.10 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4431.96 | 11-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1931.10 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3322.40 | 24-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1931.10 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3469.29 | 15-MAR-12:00 |
April | 2699.95 | 01-APR-14:09 | 1931.10 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.51 | 30-APR-15:00 | 2416.01 | 10-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1931.10 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.61 | 22-MAY-15:00 | 2568.19 | 01-MAY-15:00 |
June | 2699.95 | 03-JUN-14:09 | 1931.10 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.47 | 13-JUN-17:00 | 2069.75 | 07-JUN-15:00 |
July | 2699.95 | 01-JUL-14:09 | 1931.10 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 22-JUL-15:00 | 1812.53 | 04-JUL-14:00 |
August | 2699.95 | 05-AUG-14:09 | 1931.10 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.23 | 14-AUG-17:00 | 1343.79 | 30-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1931.10 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 1970.07 | 30-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 1931.10 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2189.42 | 27-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1931.10 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3590.34 | 28-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1931.10 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4094.19 | 29-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1343.79 | |||||
Maximum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 4431.96 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1931.10 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4431.96 | 11-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1931.10 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3322.40 | 24-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1931.10 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3469.29 | 15-MAR-12:00 |
April | 2699.95 | 01-APR-14:09 | 1931.10 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.51 | 30-APR-15:00 | 2416.01 | 10-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1931.10 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.61 | 22-MAY-15:00 | 2514.96 | 01-MAY-15:00 |
June | 2699.95 | 03-JUN-14:09 | 1931.10 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.47 | 13-JUN-17:00 | 2013.59 | 07-JUN-15:00 |
July | 2699.95 | 01-JUL-14:09 | 1931.10 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 22-JUL-15:00 | 1757.60 | 04-JUL-14:00 |
August | 2699.95 | 05-AUG-14:09 | 1931.10 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.23 | 14-AUG-17:00 | 1343.87 | 30-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1931.10 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 1953.00 | 30-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 1931.10 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2189.42 | 27-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1931.10 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3590.34 | 28-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1931.10 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4094.19 | 29-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1343.87 | |||||
Maximum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 4431.96 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1931.10 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4485.13 | 11-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1931.10 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3378.03 | 24-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1931.10 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3469.29 | 15-MAR-12:00 |
April | 2699.95 | 01-APR-14:09 | 1931.10 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.71 | 30-APR-15:00 | 2465.64 | 10-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1931.10 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.95 | 22-MAY-15:00 | 2543.92 | 01-MAY-15:00 |
June | 2699.95 | 03-JUN-14:09 | 1931.10 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 509.69 | 13-JUN-17:00 | 2076.78 | 07-JUN-11:10 |
July | 2699.95 | 01-JUL-14:09 | 1931.10 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 831.59 | 22-JUL-15:00 | 1737.89 | 01-JUL-11:10 |
August | 2699.95 | 05-AUG-14:09 | 1931.10 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 507.51 | 14-AUG-17:00 | 1408.80 | 30-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1931.10 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 1964.48 | 30-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 1931.10 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2215.69 | 27-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1931.10 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3678.60 | 28-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1931.10 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4178.83 | 29-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1408.80 | |||||
Maximum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 831.59 | 4485.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9557.54 | 04-JAN-09:04 | 2700.03 | 22405.92 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 821.01 |
February | 9722.10 | 18-FEB-00:03 | 1350.01 | 11202.96 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.39 |
March | 9098.42 | 15-MAR-08:04 | 2700.03 | 22405.92 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 883.59 |
April | 10485.13 | 30-APR-16:07 | 12150.11 | 15964.28 | 4044.77 | 0.00 | 0.00 | 0.00 | 0.00 | 29.48 | 0.00 |
May | 8183.37 | 23-MAY-17:10 | 3375.03 | 5321.43 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 284.83 |
June | 27191.27 | 13-JUN-08:62 | 1687.52 | 14003.70 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.23 |
July | 27494.79 | 18-JUL-08:62 | 1687.52 | 14003.70 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.29 |
August | 20810.08 | 15-AUG-08:62 | 1687.52 | 14003.70 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 250.39 |
September | 10210.83 | 13-SEP-16:10 | 3375.03 | 5321.43 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.02 |
October | 7557.52 | 05-OCT-20:03 | 6075.06 | 15964.28 | 4044.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.09 |
November | 9539.52 | 29-NOV-09:04 | 2700.03 | 22405.92 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 854.60 |
December | 10550.55 | 30-DEC-00:02 | 1687.52 | 14003.70 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 254.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7557.52 | 1350.01 | 5321.43 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27494.79 | 12150.11 | 22405.92 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 29.48 | 883.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4905.12 | 09-JAN-09:03 | 1349.97 | 12347.66 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 531.42 |
February | 4187.27 | 17-FEB-09:03 | 1349.97 | 12347.66 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 455.86 |
March | 3707.09 | 15-MAR-08:02 | 1349.97 | 12347.66 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 462.01 |
April | 18331.39 | 29-APR-18:44 | 11812.27 | 20527.98 | 4718.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.96 |
May | 17371.05 | 21-MAY-17:07 | 18224.65 | 26393.11 | 6067.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.30 |
June | 17056.68 | 26-JUN-08:62 | 843.73 | 7717.28 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.97 |
July | 17675.02 | 25-JUL-08:62 | 843.73 | 7717.28 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.55 |
August | 18246.29 | 14-AUG-21:16 | 7087.36 | 20527.98 | 4718.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.42 |
September | 17429.79 | 14-SEP-08:62 | 674.99 | 6173.83 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.93 |
October | 3980.26 | 05-OCT-20:10 | 3037.44 | 8797.70 | 2022.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.84 |
November | 4124.71 | 29-NOV-09:03 | 1349.97 | 12347.66 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 470.00 |
December | 4631.16 | 27-DEC-09:03 | 1349.97 | 12347.66 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 509.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3707.09 | 674.99 | 6173.83 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.42 | |
Maximum of Months | 18331.39 | 18224.65 | 26393.11 | 6067.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 531.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5462.24 | 10-JAN-08:04 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 628.92 |
February | 5012.14 | 17-FEB-08:03 | 1012.48 | 8208.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 543.96 |
March | 3662.43 | 16-MAR-07:04 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 426.04 |
April | 10470.04 | 30-APR-08:63 | 506.24 | 4104.04 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.65 |
May | 6608.58 | 01-MAY-07:03 | 506.24 | 4104.04 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 451.27 |
June | 18034.42 | 14-JUN-07:03 | 674.99 | 5472.06 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 309.84 |
July | 17882.93 | 13-JUL-07:03 | 674.99 | 5472.06 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.54 |
August | 18028.26 | 15-AUG-07:02 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.39 |
September | 17146.80 | 02-SEP-07:03 | 674.99 | 5472.06 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.87 |
October | 3371.41 | 06-OCT-07:03 | 506.24 | 4104.04 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 435.78 |
November | 4484.96 | 29-NOV-08:03 | 1012.48 | 8208.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 558.43 |
December | 4681.61 | 27-DEC-08:03 | 1181.23 | 9576.10 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 545.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3371.41 | 506.24 | 4104.04 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.65 | |
Maximum of Months | 18034.42 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 628.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5716.19 | 10-JAN-08:04 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 631.75 |
February | 4392.13 | 18-FEB-08:03 | 1012.48 | 8208.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 516.35 |
March | 3952.00 | 13-MAR-07:04 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 447.92 |
April | 9741.10 | 30-APR-08:63 | 506.24 | 4104.04 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.49 |
May | 6330.17 | 01-MAY-07:03 | 506.24 | 4104.04 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 451.21 |
June | 17648.71 | 14-JUN-07:03 | 674.99 | 5472.06 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 309.69 |
July | 17874.62 | 13-JUL-07:03 | 674.99 | 5472.06 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.74 |
August | 18073.98 | 15-AUG-07:02 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.12 |
September | 16580.12 | 02-SEP-07:03 | 674.99 | 5472.06 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.80 |
October | 3341.08 | 06-OCT-07:03 | 506.24 | 4104.04 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 433.18 |
November | 4595.77 | 29-NOV-08:03 | 1012.48 | 8208.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 560.67 |
December | 4345.35 | 31-DEC-09:04 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 502.80 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3341.08 | 506.24 | 4104.04 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.49 | |
Maximum of Months | 18073.98 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 631.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5792.29 | 10-JAN-08:04 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 631.33 |
February | 4462.53 | 18-FEB-08:03 | 1012.48 | 8208.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 516.31 |
March | 4095.57 | 13-MAR-07:04 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 450.31 |
April | 7823.97 | 30-APR-08:63 | 506.24 | 4104.04 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.03 |
May | 4738.28 | 01-MAY-07:03 | 506.24 | 4104.04 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 450.77 |
June | 16121.08 | 26-JUN-07:02 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.17 |
July | 17491.16 | 25-JUL-07:02 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 252.03 |
August | 17870.81 | 15-AUG-07:02 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.26 |
September | 14853.32 | 02-SEP-07:03 | 674.99 | 5472.06 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.57 |
October | 3286.95 | 06-OCT-07:03 | 506.24 | 4104.04 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 427.19 |
November | 4612.87 | 29-NOV-08:03 | 1012.48 | 8208.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 557.98 |
December | 4501.40 | 31-DEC-09:04 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 505.72 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3286.95 | 506.24 | 4104.04 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.17 | |
Maximum of Months | 17870.81 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 631.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9497.09 | 10-JAN-09:05 | 5940.06 | 15774.71 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1144.08 |
February | 9400.09 | 18-FEB-09:04 | 5940.06 | 15774.71 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 874.72 |
March | 9218.69 | 15-MAR-08:04 | 5940.06 | 15774.71 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 846.29 |
April | 9441.52 | 30-APR-09:03 | 2227.52 | 5915.52 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 250.69 |
May | 6633.75 | 22-MAY-15:00 | 4657.54 | 3746.51 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 29.79 | 0.00 |
June | 30048.56 | 26-JUN-08:62 | 3712.53 | 9859.20 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.72 |
July | 30861.64 | 24-JUL-08:62 | 3712.53 | 9859.20 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 416.19 |
August | 23781.47 | 18-AUG-08:62 | 3712.53 | 9859.20 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.35 |
September | 12541.68 | 14-SEP-08:62 | 2970.03 | 7887.36 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 269.31 |
October | 7166.83 | 05-OCT-20:00 | 742.51 | 1971.84 | 749.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.76 |
November | 9151.91 | 28-NOV-09:04 | 5940.06 | 15774.71 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 922.82 |
December | 9497.98 | 08-DEC-09:04 | 5940.06 | 15774.71 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 928.85 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6633.75 | 742.51 | 1971.84 | 749.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30861.64 | 5940.06 | 15774.71 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 29.79 | 1144.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5017.48 | 11-JAN-09:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 605.86 |
February | 4276.44 | 17-FEB-20:37 | 1113.73 | 3049.10 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.80 |
March | 3742.29 | 15-MAR-08:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 461.98 |
April | 9210.39 | 30-APR-09:03 | 1113.73 | 3049.10 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.20 |
May | 3504.16 | 22-MAY-15:00 | 2328.71 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 16.61 | 0.00 |
June | 16427.98 | 26-JUN-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.85 |
July | 16998.09 | 25-JUL-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 252.52 |
August | 16848.49 | 15-AUG-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.91 |
September | 11675.03 | 14-SEP-08:62 | 1484.97 | 4065.46 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.99 |
October | 3055.49 | 07-OCT-15:00 | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 799.72 |
November | 4176.98 | 29-NOV-09:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 470.41 |
December | 4683.24 | 27-DEC-09:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 506.18 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3055.49 | 1113.73 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16998.09 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 16.61 | 799.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4747.87 | 12-JAN-09:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 537.03 |
February | 4257.97 | 13-FEB-09:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 471.44 |
March | 3816.17 | 15-MAR-08:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 463.32 |
April | 8275.18 | 30-APR-09:03 | 1113.73 | 3049.10 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.95 |
May | 3418.41 | 22-MAY-15:00 | 2328.71 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 16.61 | 0.00 |
June | 16265.53 | 26-JUN-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.09 |
July | 16841.10 | 25-JUL-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.01 |
August | 16693.50 | 15-AUG-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.47 |
September | 10672.13 | 14-SEP-08:62 | 1484.97 | 4065.46 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.85 |
October | 3031.40 | 05-OCT-20:00 | 371.24 | 1016.37 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.36 |
November | 4247.10 | 29-NOV-09:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 471.66 |
December | 4659.15 | 27-DEC-09:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 503.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3031.40 | 371.24 | 1016.37 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16841.10 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 16.61 | 537.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4756.95 | 11-JAN-08:02 | 0.00 | 813.09 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 548.00 |
February | 4119.87 | 17-FEB-08:03 | 0.00 | 609.82 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 477.84 |
March | 3595.04 | 31-MAR-08:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 493.30 |
April | 4531.31 | 30-APR-15:00 | 2328.71 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 16.51 | 0.00 |
May | 3132.04 | 22-MAY-15:00 | 2328.71 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 16.61 | 0.00 |
June | 4902.46 | 13-JUN-15:00 | 2328.71 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 341.90 | 0.00 |
July | 13691.54 | 23-JUL-09:01 | 2598.70 | 7114.56 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.31 |
August | 4978.23 | 14-AUG-16:10 | 2396.20 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 366.76 | 0.00 |
September | 4728.70 | 13-SEP-14:30 | 2328.71 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.34 |
October | 2963.55 | 06-OCT-07:03 | 0.00 | 304.91 | 112.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 388.18 |
November | 3756.42 | 17-NOV-09:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 446.65 |
December | 3903.99 | 27-DEC-08:03 | 0.00 | 711.46 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 476.78 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2963.55 | 0.00 | 304.91 | 112.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13691.54 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 366.76 | 548.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3173.89 | 16-JAN-10:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 347.70 |
February | 3296.78 | 23-FEB-09:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 439.16 |
March | 3326.59 | 12-MAR-09:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 434.24 |
April | 4294.07 | 30-APR-15:00 | 2328.71 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 16.71 | 0.00 |
May | 2982.90 | 22-MAY-15:00 | 2328.71 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 16.95 | 0.00 |
June | 9112.37 | 26-JUN-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.70 |
July | 16345.13 | 23-JUL-09:01 | 2598.70 | 7114.56 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.84 |
August | 6241.92 | 20-AUG-09:02 | 1484.97 | 4065.46 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.33 |
September | 4633.06 | 13-SEP-14:20 | 2328.71 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.51 |
October | 2920.33 | 30-OCT-08:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 327.23 |
November | 3451.80 | 16-NOV-09:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 371.20 |
December | 2888.11 | 02-DEC-09:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 325.91 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2888.11 | 1484.97 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16345.13 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 16.95 | 439.16 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.800536E+11 | 65695.18 | 07-JAN-17:40 | 0.735397E+11 | 173467.85 | 10-JAN-09:09 |
February | 0.713676E+11 | 62748.81 | 07-FEB-17:19 | 0.589631E+11 | 141472.80 | 13-FEB-09:09 |
March | 0.783662E+11 | 62962.38 | 29-MAR-18:49 | 0.531932E+11 | 124535.84 | 15-MAR-08:09 |
April | 0.737140E+11 | 63470.79 | 30-APR-15:09 | 0.105330E+11 | 88629.36 | 01-APR-08:09 |
May | 0.751736E+11 | 65703.53 | 22-MAY-15:09 | 0.601962E+10 | 54729.46 | 17-MAY-08:09 |
June | 0.744341E+11 | 73089.72 | 13-JUN-14:30 | 0.127631E+09 | 10418.86 | 08-JUN-08:09 |
July | 0.774220E+11 | 74166.76 | 22-JUL-12:00 | 966811.71 | 1011.12 | 05-JUL-08:09 |
August | 0.798575E+11 | 70561.27 | 14-AUG-14:30 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.762866E+11 | 66511.24 | 13-SEP-14:09 | 6023430.19 | 2068.37 | 08-SEP-08:00 |
October | 0.778539E+11 | 61161.81 | 30-OCT-16:00 | 0.132979E+11 | 75720.54 | 23-OCT-08:09 |
November | 0.769400E+11 | 61489.29 | 27-NOV-16:00 | 0.461036E+11 | 139164.59 | 29-NOV-09:09 |
December | 0.802341E+11 | 61995.94 | 05-DEC-17:00 | 0.804349E+11 | 158275.95 | 30-DEC-09:09 |
Annual Sum or Average | 0.921703E+12 | 0.342220E+12 | ||||
Minimum of Months | 0.713676E+11 | 61161.81 | 0.00 | 0.00 | ||
Maximum of Months | 0.802341E+11 | 74166.76 | 0.804349E+11 | 173467.85 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.373403E+11 | 0.113690E+11 | 0.108804E+11 | 0.00 | 0.148443E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.561968E+10 | 0.00 |
February | 0.337970E+11 | 0.921946E+10 | 0.985143E+10 | 0.00 | 0.133981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.510161E+10 | 0.00 |
March | 0.378801E+11 | 0.876766E+10 | 0.110560E+11 | 0.00 | 0.149915E+11 | 0.00 | 0.00 | 10513.37 | 0.00 | 0.00 | 0.00 | 0.567099E+10 | 0.00 |
April | 0.362171E+11 | 0.703014E+10 | 0.105544E+11 | 0.00 | 0.141030E+11 | 0.00 | 0.00 | 0.408198E+09 | 0.00 | 0.00 | 0.00 | 0.540114E+10 | 0.00 |
May | 0.376032E+11 | 0.609877E+10 | 0.109629E+11 | 0.00 | 0.146830E+11 | 0.00 | 0.00 | 0.281909E+09 | 0.00 | 0.00 | 0.00 | 0.554372E+10 | 0.00 |
June | 0.366114E+11 | 0.531478E+10 | 0.106855E+11 | 0.00 | 0.144641E+11 | 0.00 | 0.00 | 0.204207E+10 | 0.00 | 0.00 | 0.00 | 0.531629E+10 | 0.00 |
July | 0.372230E+11 | 0.572072E+10 | 0.108424E+11 | 0.00 | 0.147116E+11 | 0.00 | 0.00 | 0.351663E+10 | 0.00 | 0.00 | 0.00 | 0.540770E+10 | 0.00 |
August | 0.378660E+11 | 0.670426E+10 | 0.110491E+11 | 0.00 | 0.150440E+11 | 0.00 | 0.00 | 0.375165E+10 | 0.00 | 0.00 | 0.00 | 0.544248E+10 | 0.00 |
September | 0.362312E+11 | 0.785305E+10 | 0.105613E+11 | 0.00 | 0.143016E+11 | 0.00 | 0.00 | 0.208362E+10 | 0.00 | 0.00 | 0.00 | 0.525590E+10 | 0.00 |
October | 0.373403E+11 | 0.960885E+10 | 0.108804E+11 | 0.00 | 0.145233E+11 | 0.00 | 0.00 | 10276065.22 | 0.00 | 0.00 | 0.00 | 0.549072E+10 | 0.00 |
November | 0.361749E+11 | 0.106052E+11 | 0.105443E+11 | 0.00 | 0.142457E+11 | 0.00 | 0.00 | 28448.42 | 0.00 | 0.00 | 0.00 | 0.536989E+10 | 0.00 |
December | 0.372370E+11 | 0.117210E+11 | 0.108529E+11 | 0.00 | 0.148257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.559742E+10 | 0.00 |
Annual Sum or Average | 0.441522E+12 | 0.100013E+12 | 0.128721E+12 | 0.00 | 0.174136E+12 | 0.00 | 0.00 | 0.120944E+11 | 0.00 | 0.00 | 0.00 | 0.652175E+11 | 0.00 |
Minimum of Months | 0.337970E+11 | 0.531478E+10 | 0.985143E+10 | 0.00 | 0.133981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.510161E+10 | 0.00 |
Maximum of Months | 0.378801E+11 | 0.117210E+11 | 0.110560E+11 | 0.00 | 0.150440E+11 | 0.00 | 0.00 | 0.375165E+10 | 0.00 | 0.00 | 0.00 | 0.567099E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.735397E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.589631E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.531932E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.105330E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.601962E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.127631E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 966811.71 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 6023430.19 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.132979E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.461036E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.804349E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.342220E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.804349E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 27522.57 | 01-JAN-11:09 | 7619.51 | 01-JAN-06:10 | 8089.53 | 01-JAN-11:09 | 0.00 | 11328.76 | 10-JAN-09:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 27522.57 | 01-FEB-10:09 | 7619.51 | 01-FEB-06:10 | 8089.53 | 01-FEB-10:09 | 0.00 | 11151.15 | 17-FEB-09:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 27522.57 | 01-MAR-10:09 | 7619.51 | 01-MAR-06:10 | 8089.53 | 01-MAR-10:09 | 0.00 | 11032.59 | 15-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 27522.57 | 01-APR-09:09 | 7619.51 | 01-APR-05:10 | 8089.53 | 01-APR-09:09 | 0.00 | 10796.11 | 01-APR-08:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 27522.57 | 01-MAY-09:09 | 7619.51 | 01-MAY-19:19 | 8089.53 | 01-MAY-09:09 | 0.00 | 10570.17 | 06-MAY-08:09 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 27522.57 | 01-JUN-09:09 | 7619.51 | 01-JUN-19:00 | 8089.53 | 01-JUN-09:09 | 0.00 | 10638.23 | 13-JUN-08:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 27522.57 | 01-JUL-09:09 | 7619.51 | 01-JUL-20:19 | 8089.53 | 01-JUL-09:09 | 0.00 | 10646.16 | 18-JUL-08:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 27522.57 | 01-AUG-09:09 | 7619.51 | 01-AUG-19:49 | 8089.53 | 01-AUG-09:09 | 0.00 | 10405.53 | 17-AUG-08:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 27522.57 | 01-SEP-09:09 | 7619.51 | 01-SEP-05:10 | 8089.53 | 01-SEP-09:09 | 0.00 | 10194.02 | 08-SEP-08:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 27522.57 | 01-OCT-10:09 | 7619.51 | 01-OCT-05:10 | 8089.53 | 01-OCT-10:09 | 0.00 | 10689.81 | 23-OCT-08:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 27522.57 | 01-NOV-09:09 | 7619.51 | 01-NOV-05:10 | 8089.53 | 01-NOV-09:09 | 0.00 | 11134.88 | 29-NOV-09:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 27522.57 | 01-DEC-10:09 | 7619.51 | 01-DEC-06:10 | 8089.53 | 01-DEC-10:09 | 0.00 | 11241.84 | 30-DEC-09:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 27522.57 | 7619.51 | 8089.53 | 0.00 | 10194.02 | 0.00 | 0.00 | |||||
Maximum of Months | 27522.57 | 7619.51 | 8089.53 | 0.00 | 11328.76 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 11859.11 | 07-JAN-14:39 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 9734.79 | 01-FEB-14:20 | 0.00 |
March | 9.68 | 25-MAR-19:00 | 0.00 | 0.00 | 0.00 | 9727.41 | 13-MAR-12:39 | 0.00 |
April | 15099.52 | 30-APR-14:00 | 0.00 | 0.00 | 0.00 | 9735.58 | 01-APR-12:09 | 0.00 |
May | 12956.75 | 22-MAY-14:00 | 0.00 | 0.00 | 0.00 | 9687.15 | 15-MAY-17:19 | 0.00 |
June | 19648.61 | 13-JUN-16:00 | 0.00 | 0.00 | 0.00 | 9681.19 | 21-JUN-17:19 | 0.00 |
July | 22497.23 | 22-JUL-14:00 | 0.00 | 0.00 | 0.00 | 9625.41 | 01-JUL-09:20 | 0.00 |
August | 18449.43 | 14-AUG-16:00 | 0.00 | 0.00 | 0.00 | 11805.95 | 04-AUG-11:20 | 0.00 |
September | 15295.59 | 13-SEP-14:20 | 0.00 | 0.00 | 0.00 | 9718.77 | 18-SEP-12:39 | 0.00 |
October | 1181.79 | 07-OCT-14:00 | 0.00 | 0.00 | 0.00 | 8877.44 | 24-OCT-13:20 | 0.00 |
November | 23.40 | 05-NOV-19:19 | 0.00 | 0.00 | 0.00 | 9700.64 | 20-NOV-15:30 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 9696.39 | 05-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8877.44 | 0.00 | ||
Maximum of Months | 22497.23 | 0.00 | 0.00 | 0.00 | 11859.11 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 65695.18 | 07-JAN-17:40 | 27522.57 | 8089.53 | 7619.51 | 0.00 | 10648.21 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 62748.81 | 07-FEB-17:19 | 27522.57 | 8089.53 | 7619.51 | 0.00 | 10411.51 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 62962.38 | 29-MAR-18:49 | 27522.57 | 8089.53 | 7619.51 | 0.00 | 10336.79 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 63470.79 | 30-APR-15:09 | 27522.57 | 8089.53 | 0.00 | 0.00 | 10179.69 | 0.00 | 0.00 | 14351.72 | 0.00 |
May | 65703.53 | 22-MAY-15:09 | 27522.57 | 8089.53 | 0.00 | 0.00 | 10179.69 | 0.00 | 0.00 | 12347.27 | 0.00 |
June | 73089.72 | 13-JUN-14:30 | 27522.57 | 8089.53 | 0.00 | 0.00 | 10179.69 | 0.00 | 0.00 | 18630.91 | 0.00 |
July | 74166.76 | 22-JUL-12:00 | 27522.57 | 8089.53 | 0.00 | 0.00 | 10218.49 | 0.00 | 0.00 | 21307.92 | 0.00 |
August | 70561.27 | 14-AUG-14:30 | 27522.57 | 8089.53 | 0.00 | 0.00 | 10179.69 | 0.00 | 0.00 | 17196.85 | 0.00 |
September | 66511.24 | 13-SEP-14:09 | 27522.57 | 8089.53 | 0.00 | 0.00 | 10179.69 | 0.00 | 0.00 | 15266.75 | 0.00 |
October | 61161.81 | 30-OCT-16:00 | 27522.57 | 8089.53 | 7619.51 | 0.00 | 10360.07 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 61489.29 | 27-NOV-16:00 | 27522.57 | 8089.53 | 7619.51 | 0.00 | 10689.91 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 61995.94 | 05-DEC-17:00 | 27522.57 | 8089.53 | 7619.51 | 0.00 | 10499.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 61161.81 | 27522.57 | 8089.53 | 0.00 | 0.00 | 10179.69 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 74166.76 | 27522.57 | 8089.53 | 7619.51 | 0.00 | 10689.91 | 0.00 | 0.00 | 21307.92 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 173467.85 | 10-JAN-09:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 141472.80 | 13-FEB-09:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 124535.84 | 15-MAR-08:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 88629.36 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 54729.46 | 17-MAY-08:09 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 10418.86 | 08-JUN-08:09 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 1011.12 | 05-JUL-08:09 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 2068.37 | 08-SEP-08:00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 75720.54 | 23-OCT-08:09 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 139164.59 | 29-NOV-09:09 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 158275.95 | 30-DEC-09:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 173467.85 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
February | 1.17 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
March | 1.50 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.67 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
December | 0.83 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
Annual Sum or Average | 4.67 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.50 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 20.99 | 147.17 | 20.93 | 147.17 | 20.89 |
February | 448.00 | 20.99 | 81.50 | 20.90 | 81.50 | 20.84 |
March | 497.00 | 21.00 | 84.50 | 20.92 | 84.50 | 20.87 |
April | 432.83 | 21.47 | 21.83 | 21.43 | 20.17 | 21.38 |
May | 433.17 | 21.68 | 34.33 | 21.78 | 7.17 | 21.76 |
June | 232.33 | 22.61 | 114.50 | 23.03 | 0.00 | 23.03 |
July | 116.83 | 22.94 | 261.67 | 23.60 | 0.00 | 23.60 |
August | 66.67 | 23.45 | 309.00 | 23.81 | 0.00 | 23.81 |
September | 173.67 | 22.90 | 151.00 | 23.36 | 0.00 | 23.36 |
October | 489.17 | 21.53 | 13.33 | 21.50 | 13.33 | 21.47 |
November | 480.00 | 21.03 | 51.50 | 20.98 | 51.50 | 20.93 |
December | 496.00 | 20.98 | 163.50 | 20.91 | 163.50 | 20.87 |
Annual Sum or Average | 4361.67 | 21.42 | 1433.83 | 21.71 | 568.83 | 21.61 |
Minimum of Months | 66.67 | 20.98 | 13.33 | 20.90 | 0.00 | 20.84 |
Maximum of Months | 497.00 | 23.45 | 309.00 | 23.81 | 163.50 | 23.81 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.51 | 28.50 | 21.47 | 28.50 | 21.43 |
February | 448.00 | 21.50 | 10.83 | 21.48 | 10.83 | 21.46 |
March | 497.00 | 21.58 | 6.83 | 21.57 | 6.83 | 21.56 |
April | 393.00 | 22.59 | 6.67 | 22.61 | 0.00 | 22.61 |
May | 370.17 | 22.75 | 41.17 | 22.86 | 0.00 | 22.86 |
June | 71.33 | 23.34 | 212.00 | 23.77 | 0.00 | 23.77 |
July | 20.17 | 23.65 | 302.17 | 23.91 | 0.00 | 23.91 |
August | 6.17 | 23.72 | 340.33 | 23.91 | 0.00 | 23.91 |
September | 43.83 | 23.59 | 205.00 | 23.84 | 0.00 | 23.84 |
October | 395.17 | 22.41 | 0.00 | 22.41 | 0.00 | 22.41 |
November | 480.00 | 21.68 | 6.17 | 21.67 | 6.17 | 21.65 |
December | 496.00 | 21.43 | 30.83 | 21.39 | 30.83 | 21.35 |
Annual Sum or Average | 3716.83 | 21.94 | 1190.50 | 22.36 | 83.17 | 22.33 |
Minimum of Months | 6.17 | 21.43 | 0.00 | 21.39 | 0.00 | 21.35 |
Maximum of Months | 497.00 | 23.72 | 340.33 | 23.91 | 30.83 | 23.91 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 60.17 | 21.11 | 60.17 | 21.11 |
February | 336.00 | 21.11 | 26.83 | 21.11 | 26.83 | 21.11 |
March | 379.00 | 21.12 | 23.83 | 21.12 | 23.83 | 21.12 |
April | 304.17 | 21.93 | 7.50 | 21.98 | 0.83 | 21.98 |
May | 295.50 | 22.15 | 37.17 | 22.34 | 0.00 | 22.34 |
June | 76.50 | 23.11 | 158.33 | 23.67 | 0.00 | 23.67 |
July | 28.17 | 23.38 | 237.67 | 23.91 | 0.00 | 23.91 |
August | 12.50 | 23.57 | 271.33 | 23.96 | 0.00 | 23.96 |
September | 47.00 | 23.26 | 154.33 | 23.78 | 0.00 | 23.78 |
October | 311.17 | 21.76 | 0.00 | 21.76 | 0.00 | 21.76 |
November | 360.00 | 21.14 | 13.50 | 21.14 | 13.50 | 21.14 |
December | 369.00 | 21.11 | 63.67 | 21.11 | 63.67 | 21.11 |
Annual Sum or Average | 2890.00 | 21.50 | 1054.33 | 22.02 | 188.83 | 21.98 |
Minimum of Months | 12.50 | 21.11 | 0.00 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 379.00 | 23.57 | 271.33 | 23.96 | 63.67 | 23.96 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 78.67 | 21.11 | 78.67 | 21.11 |
February | 336.00 | 21.11 | 33.33 | 21.11 | 33.33 | 21.11 |
March | 379.00 | 21.12 | 32.67 | 21.12 | 32.67 | 21.12 |
April | 308.83 | 21.85 | 7.17 | 21.89 | 2.00 | 21.88 |
May | 302.83 | 22.07 | 32.33 | 22.25 | 0.00 | 22.25 |
June | 86.00 | 23.06 | 143.00 | 23.61 | 0.00 | 23.61 |
July | 33.83 | 23.35 | 232.67 | 23.90 | 0.00 | 23.90 |
August | 14.33 | 23.58 | 269.33 | 23.95 | 0.00 | 23.95 |
September | 51.00 | 23.24 | 150.17 | 23.76 | 0.00 | 23.76 |
October | 317.33 | 21.71 | 0.00 | 21.71 | 0.00 | 21.71 |
November | 360.00 | 21.13 | 18.33 | 21.13 | 18.33 | 21.13 |
December | 369.00 | 21.11 | 77.33 | 21.11 | 77.33 | 21.11 |
Annual Sum or Average | 2929.17 | 21.49 | 1075.00 | 21.98 | 242.33 | 21.93 |
Minimum of Months | 14.33 | 21.11 | 0.00 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 379.00 | 23.58 | 269.33 | 23.95 | 78.67 | 23.95 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 94.50 | 21.11 | 94.50 | 21.11 |
February | 336.00 | 21.11 | 43.17 | 21.11 | 43.17 | 21.11 |
March | 379.00 | 21.12 | 45.17 | 21.11 | 45.17 | 21.11 |
April | 318.67 | 21.76 | 7.33 | 21.79 | 4.00 | 21.78 |
May | 308.50 | 21.94 | 27.00 | 22.10 | 0.00 | 22.10 |
June | 112.67 | 22.98 | 120.33 | 23.48 | 0.00 | 23.48 |
July | 48.50 | 23.27 | 223.33 | 23.85 | 0.00 | 23.85 |
August | 20.17 | 23.57 | 260.17 | 23.94 | 0.00 | 23.94 |
September | 63.00 | 23.19 | 139.67 | 23.70 | 0.00 | 23.70 |
October | 327.33 | 21.66 | 0.00 | 21.66 | 0.00 | 21.66 |
November | 360.00 | 21.12 | 23.67 | 21.12 | 23.67 | 21.12 |
December | 369.00 | 21.11 | 95.00 | 21.11 | 95.00 | 21.11 |
Annual Sum or Average | 3013.83 | 21.49 | 1079.33 | 21.93 | 305.50 | 21.87 |
Minimum of Months | 20.17 | 21.11 | 0.00 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 379.00 | 23.57 | 260.17 | 23.94 | 95.00 | 23.94 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 122.50 | 21.11 | 122.50 | 21.11 |
February | 308.00 | 21.11 | 52.50 | 21.11 | 52.50 | 21.11 |
March | 348.00 | 21.11 | 57.33 | 21.11 | 57.33 | 21.11 |
April | 299.67 | 21.49 | 6.33 | 21.50 | 4.50 | 21.50 |
May | 294.50 | 21.62 | 16.83 | 21.74 | 0.00 | 21.74 |
June | 159.67 | 22.56 | 79.83 | 23.00 | 0.00 | 23.00 |
July | 68.17 | 22.91 | 186.50 | 23.65 | 0.00 | 23.65 |
August | 25.33 | 23.44 | 226.17 | 23.87 | 0.00 | 23.87 |
September | 97.67 | 22.95 | 110.83 | 23.46 | 0.00 | 23.46 |
October | 333.83 | 21.59 | 0.50 | 21.59 | 0.50 | 21.59 |
November | 330.00 | 21.11 | 33.33 | 21.11 | 33.33 | 21.11 |
December | 338.00 | 21.11 | 144.17 | 21.11 | 144.17 | 21.11 |
Annual Sum or Average | 2942.83 | 21.45 | 1036.83 | 21.80 | 414.83 | 21.74 |
Minimum of Months | 25.33 | 21.11 | 0.50 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 348.00 | 23.44 | 226.17 | 23.87 | 144.17 | 23.87 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 119.83 | 21.11 | 119.83 | 21.11 |
February | 308.00 | 21.11 | 53.17 | 21.11 | 53.17 | 21.11 |
March | 348.00 | 21.11 | 56.50 | 21.11 | 56.50 | 21.11 |
April | 299.17 | 21.72 | 6.83 | 21.73 | 5.00 | 21.72 |
May | 286.17 | 21.86 | 14.67 | 21.96 | 0.00 | 21.96 |
June | 121.67 | 22.90 | 76.50 | 23.29 | 0.00 | 23.29 |
July | 51.00 | 23.26 | 179.17 | 23.78 | 0.00 | 23.78 |
August | 17.83 | 23.71 | 213.50 | 23.91 | 0.00 | 23.91 |
September | 62.67 | 23.26 | 111.00 | 23.68 | 0.00 | 23.68 |
October | 314.50 | 21.70 | 0.50 | 21.70 | 0.50 | 21.70 |
November | 330.00 | 21.12 | 32.17 | 21.12 | 32.17 | 21.12 |
December | 338.00 | 21.11 | 135.83 | 21.11 | 135.83 | 21.11 |
Annual Sum or Average | 2817.00 | 21.50 | 999.67 | 21.84 | 403.00 | 21.77 |
Minimum of Months | 17.83 | 21.11 | 0.50 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 348.00 | 23.71 | 213.50 | 23.91 | 135.83 | 23.91 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 128.33 | 21.11 | 128.33 | 21.11 |
February | 308.00 | 21.11 | 58.17 | 21.11 | 58.17 | 21.11 |
March | 348.00 | 21.11 | 65.17 | 21.11 | 65.17 | 21.11 |
April | 301.67 | 21.70 | 8.83 | 21.71 | 7.00 | 21.70 |
May | 288.67 | 21.83 | 13.00 | 21.92 | 0.00 | 21.92 |
June | 130.33 | 22.87 | 71.00 | 23.24 | 0.00 | 23.24 |
July | 56.00 | 23.23 | 173.83 | 23.76 | 0.00 | 23.76 |
August | 22.00 | 23.70 | 209.17 | 23.90 | 0.00 | 23.90 |
September | 69.00 | 23.25 | 103.83 | 23.65 | 0.00 | 23.65 |
October | 320.67 | 21.70 | 1.17 | 21.70 | 1.17 | 21.70 |
November | 330.00 | 21.11 | 37.50 | 21.11 | 37.50 | 21.11 |
December | 338.00 | 21.11 | 146.67 | 21.11 | 146.67 | 21.11 |
Annual Sum or Average | 2852.33 | 21.51 | 1016.67 | 21.82 | 444.00 | 21.75 |
Minimum of Months | 22.00 | 21.11 | 1.17 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 348.00 | 23.70 | 209.17 | 23.90 | 146.67 | 23.90 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.10 | 152.67 | 21.10 | 152.67 | 21.10 |
February | 308.00 | 21.10 | 84.83 | 21.10 | 84.83 | 21.10 |
March | 348.00 | 21.11 | 96.17 | 21.10 | 96.17 | 21.10 |
April | 307.17 | 21.61 | 19.00 | 21.60 | 17.33 | 21.57 |
May | 297.33 | 21.69 | 7.83 | 21.72 | 2.67 | 21.72 |
June | 169.17 | 22.65 | 53.33 | 22.96 | 0.00 | 22.96 |
July | 77.50 | 22.95 | 152.50 | 23.60 | 0.00 | 23.60 |
August | 37.67 | 23.33 | 190.33 | 23.83 | 0.00 | 23.83 |
September | 105.33 | 23.04 | 81.17 | 23.42 | 0.00 | 23.42 |
October | 336.67 | 21.65 | 8.67 | 21.63 | 8.67 | 21.62 |
November | 330.00 | 21.11 | 60.50 | 21.10 | 60.50 | 21.10 |
December | 338.00 | 21.10 | 186.67 | 21.10 | 186.67 | 21.10 |
Annual Sum or Average | 2994.83 | 21.51 | 1093.67 | 21.73 | 609.50 | 21.65 |
Minimum of Months | 37.67 | 21.10 | 7.83 | 21.10 | 0.00 | 21.10 |
Maximum of Months | 348.00 | 23.33 | 190.33 | 23.83 | 186.67 | 23.83 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 237.33 | 21.10 | 237.33 | 21.10 |
February | 308.00 | 21.10 | 205.67 | 21.10 | 205.67 | 21.10 |
March | 348.00 | 21.11 | 231.83 | 21.10 | 231.83 | 21.10 |
April | 309.83 | 21.54 | 36.83 | 21.50 | 36.00 | 21.47 |
May | 310.50 | 21.63 | 17.33 | 21.64 | 12.67 | 21.62 |
June | 221.00 | 22.55 | 37.33 | 22.75 | 0.00 | 22.75 |
July | 105.33 | 22.98 | 125.33 | 23.50 | 0.00 | 23.50 |
August | 55.33 | 23.38 | 164.83 | 23.79 | 0.00 | 23.79 |
September | 155.33 | 22.97 | 60.50 | 23.24 | 0.00 | 23.24 |
October | 340.00 | 21.52 | 27.50 | 21.49 | 27.50 | 21.46 |
November | 330.00 | 21.11 | 142.33 | 21.11 | 142.33 | 21.10 |
December | 338.00 | 21.10 | 310.83 | 21.10 | 310.83 | 21.10 |
Annual Sum or Average | 3161.33 | 21.54 | 1597.67 | 21.63 | 1204.17 | 21.52 |
Minimum of Months | 55.33 | 21.10 | 17.33 | 21.10 | 0.00 | 21.10 |
Maximum of Months | 348.00 | 23.38 | 310.83 | 23.79 | 310.83 | 23.79 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 20.99301 | 32.54669 | -0.4981 | 10.60466 |
February | 448.00000 | 20.98623 | 33.56686 | -0.4818 | 10.19572 |
March | 497.00000 | 21.00115 | 33.63066 | -0.4705 | 9.92953 |
April | 479.00000 | 21.69973 | 33.56724 | -0.2127 | 7.38587 |
May | 496.00000 | 21.95356 | 39.43958 | -1.1877 | 36.80525 |
June | 481.00000 | 23.21962 | 45.52846 | -0.6916 | 16.67123 |
July | 495.00000 | 23.64750 | 45.91774 | -0.5220 | 11.62058 |
August | 497.00000 | 23.81744 | 45.85488 | -0.4661 | 9.89236 |
September | 479.00000 | 23.48767 | 43.88626 | -0.6108 | 13.94335 |
October | 496.00000 | 21.56400 | 42.56177 | -0.2106 | 6.84747 |
November | 480.00000 | 21.03423 | 37.80087 | -0.4223 | 8.98038 |
December | 496.00000 | 20.97579 | 31.69242 | -0.5310 | 11.23503 |
Annual Sum or Average | 5840.00000 | 22.03651 | 38.86141 | -0.5263 | 12.87701 |
Minimum of Months | 448.00000 | 20.97579 | 31.69242 | -1.1877 | 6.84747 |
Maximum of Months | 497.00000 | 23.81744 | 45.91774 | -0.2106 | 36.80525 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.50774 | 35.27535 | -0.3319 | 7.87013 |
February | 448.00000 | 21.50070 | 36.03537 | -0.3194 | 7.53014 |
March | 497.00000 | 21.58034 | 35.85010 | -0.2992 | 7.42271 |
April | 479.00000 | 22.82049 | 33.56632 | 0.03693 | 6.18469 |
May | 496.00000 | 23.03599 | 38.31427 | -0.8605 | 22.35709 |
June | 481.00000 | 23.81077 | 43.92426 | -0.5107 | 10.87196 |
July | 495.00000 | 23.89303 | 45.14828 | -0.4433 | 9.32435 |
August | 497.00000 | 23.91145 | 45.46116 | -0.4283 | 8.97243 |
September | 479.00000 | 23.86691 | 42.75591 | -0.4872 | 10.23407 |
October | 496.00000 | 22.70020 | 42.08515 | 0.04586 | 6.18042 |
November | 480.00000 | 21.67898 | 39.59474 | -0.2464 | 6.87996 |
December | 496.00000 | 21.43244 | 34.10225 | -0.3734 | 8.30111 |
Annual Sum or Average | 5840.00000 | 22.64973 | 39.36382 | -0.3523 | 9.36804 |
Minimum of Months | 448.00000 | 21.43244 | 33.56632 | -0.8605 | 6.18042 |
Maximum of Months | 497.00000 | 23.91145 | 45.46116 | 0.04586 | 22.35709 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.11068 | 32.01627 | -0.4414 | 9.23886 |
February | 336.00000 | 21.11016 | 33.23371 | -0.4207 | 8.78534 |
March | 379.00000 | 21.12345 | 32.58255 | -0.4160 | 8.71515 |
April | 360.00000 | 22.24435 | 31.57205 | -0.0865 | 6.69204 |
May | 375.00000 | 22.51700 | 37.58695 | -1.0014 | 28.47428 |
June | 366.00000 | 23.72349 | 43.63582 | -0.5327 | 11.62330 |
July | 369.00000 | 23.89842 | 44.99070 | -0.4384 | 9.38462 |
August | 379.00000 | 23.94096 | 45.34790 | -0.4161 | 8.83019 |
September | 360.00000 | 23.82322 | 42.56253 | -0.4947 | 10.57812 |
October | 371.00000 | 22.09873 | 40.78538 | -0.0807 | 6.49286 |
November | 360.00000 | 21.14099 | 37.12498 | -0.3751 | 8.07229 |
December | 369.00000 | 21.10925 | 31.00563 | -0.4697 | 9.70360 |
Annual Sum or Average | 4395.00000 | 22.32826 | 37.74141 | -0.4324 | 10.58859 |
Minimum of Months | 336.00000 | 21.10925 | 31.00563 | -1.0014 | 6.49286 |
Maximum of Months | 379.00000 | 23.94096 | 45.34790 | -0.0807 | 28.47428 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.10929 | 32.01873 | -0.4544 | 9.48541 |
February | 336.00000 | 21.10956 | 33.23416 | -0.4321 | 8.99278 |
March | 379.00000 | 21.11963 | 32.58841 | -0.4277 | 8.92206 |
April | 360.00000 | 22.14695 | 31.75016 | -0.1159 | 6.82154 |
May | 375.00000 | 22.42096 | 37.79689 | -1.0401 | 30.19826 |
June | 366.00000 | 23.68981 | 43.73758 | -0.5487 | 12.08266 |
July | 369.00000 | 23.88729 | 45.03189 | -0.4455 | 9.55643 |
August | 379.00000 | 23.93858 | 45.36722 | -0.4195 | 8.88933 |
September | 360.00000 | 23.81151 | 42.60981 | -0.5029 | 10.77962 |
October | 371.00000 | 22.02474 | 40.97655 | -0.1051 | 6.59602 |
November | 360.00000 | 21.13120 | 37.14732 | -0.3888 | 8.28667 |
December | 369.00000 | 21.10906 | 31.00499 | -0.4820 | 9.95261 |
Annual Sum or Average | 4395.00000 | 22.29963 | 37.81004 | -0.4482 | 10.92226 |
Minimum of Months | 336.00000 | 21.10906 | 31.00499 | -1.0401 | 6.59602 |
Maximum of Months | 379.00000 | 23.93858 | 45.36722 | -0.1051 | 30.19826 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.10915 | 32.01959 | -0.4675 | 9.74798 |
February | 336.00000 | 21.10910 | 33.23589 | -0.4444 | 9.22601 |
March | 379.00000 | 21.11559 | 32.59693 | -0.4404 | 9.15800 |
April | 360.00000 | 22.01733 | 31.99989 | -0.1528 | 6.96663 |
May | 375.00000 | 22.28652 | 38.09825 | -1.0920 | 32.49487 |
June | 366.00000 | 23.59926 | 44.01283 | -0.5867 | 13.22021 |
July | 369.00000 | 23.85389 | 45.15506 | -0.4638 | 10.01190 |
August | 379.00000 | 23.92976 | 45.42583 | -0.4288 | 9.06842 |
September | 360.00000 | 23.77546 | 42.74432 | -0.5226 | 11.29790 |
October | 371.00000 | 21.91945 | 41.25193 | -0.1370 | 6.69274 |
November | 360.00000 | 21.12267 | 37.16916 | -0.4019 | 8.50306 |
December | 369.00000 | 21.10861 | 31.00704 | -0.4957 | 10.24200 |
Annual Sum or Average | 4395.00000 | 22.25346 | 37.93169 | -0.4708 | 11.43150 |
Minimum of Months | 336.00000 | 21.10861 | 31.00704 | -1.0920 | 6.69274 |
Maximum of Months | 379.00000 | 23.92976 | 45.42583 | -0.1370 | 32.49487 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10737 | 33.64551 | -0.4933 | 10.27642 |
February | 308.00000 | 21.10803 | 34.78374 | -0.4677 | 9.66891 |
March | 348.00000 | 21.10934 | 34.12982 | -0.4639 | 9.59971 |
April | 330.00000 | 21.71394 | 34.09959 | -0.2160 | 7.28100 |
May | 344.00000 | 21.94027 | 40.39446 | -1.1933 | 37.05582 |
June | 336.00000 | 23.19704 | 46.50810 | -0.6999 | 16.87067 |
July | 338.00000 | 23.67685 | 46.76304 | -0.5136 | 11.37797 |
August | 348.00000 | 23.85800 | 46.52421 | -0.4498 | 9.45996 |
September | 330.00000 | 23.56695 | 44.70811 | -0.5798 | 12.90936 |
October | 340.00000 | 21.62948 | 43.52462 | -0.2026 | 6.83521 |
November | 330.00000 | 21.10934 | 38.78779 | -0.4257 | 8.90733 |
December | 338.00000 | 21.10688 | 32.58143 | -0.5255 | 10.87877 |
Annual Sum or Average | 4030.00000 | 22.10119 | 39.74347 | -0.5207 | 12.64752 |
Minimum of Months | 308.00000 | 21.10688 | 32.58143 | -1.1933 | 6.83521 |
Maximum of Months | 348.00000 | 23.85800 | 46.76304 | -0.2026 | 37.05582 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10847 | 33.53787 | -0.4924 | 10.25222 |
February | 308.00000 | 21.10846 | 34.67439 | -0.4683 | 9.68042 |
March | 348.00000 | 21.11304 | 34.02058 | -0.4648 | 9.61820 |
April | 330.00000 | 21.93120 | 33.51092 | -0.1864 | 7.14071 |
May | 344.00000 | 22.19516 | 39.65131 | -1.1424 | 34.74616 |
June | 336.00000 | 23.50304 | 45.53017 | -0.6364 | 14.64156 |
July | 338.00000 | 23.80734 | 46.26143 | -0.4961 | 10.67988 |
August | 348.00000 | 23.89896 | 46.26225 | -0.4555 | 9.51189 |
September | 330.00000 | 23.76629 | 43.91527 | -0.5433 | 11.68777 |
October | 340.00000 | 21.85561 | 42.86375 | -0.1672 | 6.83158 |
November | 330.00000 | 21.11636 | 38.65361 | -0.4260 | 8.91403 |
December | 338.00000 | 21.10790 | 32.46119 | -0.5229 | 10.81977 |
Annual Sum or Average | 4030.00000 | 22.21723 | 39.31699 | -0.5016 | 12.09466 |
Minimum of Months | 308.00000 | 21.10790 | 32.46119 | -1.1424 | 6.83158 |
Maximum of Months | 348.00000 | 23.89896 | 46.26225 | -0.1672 | 34.74616 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10782 | 33.53910 | -0.4984 | 10.37835 |
February | 308.00000 | 21.10729 | 34.67665 | -0.4749 | 9.81138 |
March | 348.00000 | 21.11156 | 34.02343 | -0.4711 | 9.74404 |
April | 330.00000 | 21.90003 | 33.57170 | -0.1975 | 7.22989 |
May | 344.00000 | 22.15516 | 39.74600 | -1.1603 | 35.56791 |
June | 336.00000 | 23.46865 | 45.64556 | -0.6518 | 15.13644 |
July | 338.00000 | 23.79349 | 46.32667 | -0.5057 | 10.92467 |
August | 348.00000 | 23.89604 | 46.30103 | -0.4619 | 9.64320 |
September | 330.00000 | 23.74951 | 43.98879 | -0.5536 | 11.96521 |
October | 340.00000 | 21.82112 | 42.94983 | -0.1793 | 6.88750 |
November | 330.00000 | 21.11463 | 38.65762 | -0.4327 | 9.03549 |
December | 338.00000 | 21.10753 | 32.46221 | -0.5279 | 10.93140 |
Annual Sum or Average | 4030.00000 | 22.20226 | 39.36271 | -0.5111 | 12.32350 |
Minimum of Months | 308.00000 | 21.10729 | 32.46221 | -1.1603 | 6.88750 |
Maximum of Months | 348.00000 | 23.89604 | 46.32667 | -0.1793 | 35.56791 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10437 | 33.37974 | -0.5210 | 10.87660 |
February | 308.00000 | 21.10474 | 34.59863 | -0.4980 | 10.30276 |
March | 348.00000 | 21.10628 | 33.83441 | -0.4953 | 10.25123 |
April | 330.00000 | 21.77230 | 33.85616 | -0.2410 | 7.65418 |
May | 344.00000 | 21.98737 | 40.17121 | -1.2324 | 38.94649 |
June | 336.00000 | 23.24569 | 46.32834 | -0.7345 | 18.04536 |
July | 338.00000 | 23.68365 | 46.66644 | -0.5537 | 12.38356 |
August | 348.00000 | 23.84616 | 46.65208 | -0.4906 | 10.36070 |
September | 330.00000 | 23.60193 | 44.57363 | -0.6133 | 13.85275 |
October | 340.00000 | 21.66751 | 43.20851 | -0.2312 | 7.16979 |
November | 330.00000 | 21.10664 | 38.52767 | -0.4574 | 9.51219 |
December | 338.00000 | 21.10487 | 32.32287 | -0.5483 | 11.40795 |
Annual Sum or Average | 4030.00000 | 22.11850 | 39.54969 | -0.5529 | 13.45425 |
Minimum of Months | 308.00000 | 21.10437 | 32.32287 | -1.2324 | 7.16979 |
Maximum of Months | 348.00000 | 23.84616 | 46.66644 | -0.2312 | 38.94649 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10512 | 33.48372 | -0.5912 | 12.55935 |
February | 308.00000 | 21.10482 | 34.55044 | -0.5706 | 11.96309 |
March | 348.00000 | 21.10592 | 33.94023 | -0.5629 | 11.78373 |
April | 330.00000 | 21.68868 | 33.85183 | -0.2954 | 8.30274 |
May | 344.00000 | 21.84472 | 40.29287 | -1.3264 | 43.52227 |
June | 336.00000 | 23.00236 | 46.81008 | -0.8405 | 22.02517 |
July | 338.00000 | 23.61501 | 46.85161 | -0.6001 | 13.80721 |
August | 348.00000 | 23.82307 | 46.58153 | -0.5238 | 11.19794 |
September | 330.00000 | 23.45651 | 44.69981 | -0.6886 | 16.31383 |
October | 340.00000 | 21.51984 | 43.44293 | -0.3101 | 7.92730 |
November | 330.00000 | 21.10646 | 38.48924 | -0.5206 | 10.84009 |
December | 338.00000 | 21.10470 | 32.27336 | -0.6179 | 13.14587 |
Annual Sum or Average | 4030.00000 | 22.04708 | 39.64636 | -0.6221 | 15.34260 |
Minimum of Months | 308.00000 | 21.10470 | 32.27336 | -1.3264 | 7.92730 |
Maximum of Months | 348.00000 | 23.82307 | 46.85161 | -0.2954 | 43.52227 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.403401E+09 | 0.100521E+09 | 24.50 | 0.399666E+09 | 3735030.50 | 0.00 | 0.83 | 30-APR-16:03 | 0.00 | 01-APR-00:05 | 11317.60 | 30-APR-16:03 | 11317.60 | 30-APR-16:03 | 336.97 | 30-APR-19:50 | 2679.54 | 30-APR-16:10 | 0.00 | 01-APR-00:05 |
May | 0.260421E+09 | 67725267.74 | 24.17 | 0.220324E+09 | 40096704.74 | 0.00 | 0.67 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 9103.42 | 22-MAY-15:00 | 8264.61 | 22-MAY-15:00 | 949.71 | 22-MAY-17:10 | 2246.13 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.170446E+10 | 0.413373E+09 | 77.72 | 0.140119E+10 | 0.303267E+09 | 0.00 | 1.00 | 13-JUN-08:62 | 0.00 | 01-JUN-00:10 | 30424.26 | 13-JUN-08:62 | 25185.14 | 13-JUN-08:62 | 9220.19 | 27-JUN-08:62 | 6474.53 | 13-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.316561E+10 | 0.787756E+09 | 171.77 | 0.265539E+10 | 0.510218E+09 | 0.00 | 1.00 | 10-JUL-08:62 | 0.00 | 01-JUL-00:10 | 30581.87 | 18-JUL-08:62 | 27985.88 | 22-JUL-08:62 | 10108.93 | 18-JUL-08:62 | 6753.32 | 22-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.314642E+10 | 0.795134E+09 | 230.77 | 0.255829E+10 | 0.588134E+09 | 0.00 | 1.00 | 15-AUG-08:62 | 0.00 | 01-AUG-00:10 | 19999.86 | 17-AUG-08:62 | 14920.70 | 15-AUG-08:62 | 8458.67 | 17-AUG-08:62 | 4256.40 | 17-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.164188E+10 | 0.409430E+09 | 104.71 | 0.136596E+10 | 0.275914E+09 | 0.00 | 0.82 | 13-SEP-16:10 | 0.00 | 01-SEP-00:05 | 11771.93 | 13-SEP-16:10 | 10073.06 | 13-SEP-16:10 | 2684.05 | 12-SEP-14:00 | 2727.67 | 13-SEP-16:10 | 0.00 | 01-SEP-00:05 |
October | 6505.57 | 1838.46 | 0.17 | 6505.57 | -0.0 | 0.00 | 0.00 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 | 10.84 | 07-OCT-15:00 | 10.84 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 | 3.06 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.103222E+11 | 0.257394E+10 | 633.80 | 0.860083E+10 | 0.172136E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.316561E+10 | 0.795134E+09 | 230.77 | 0.265539E+10 | 0.588134E+09 | 0.00 | 1.00 | 0.00 | 30581.87 | 27985.88 | 10108.93 | 6753.32 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 42502.68 | 10513.37 | 0.33 | 33968.26 | 8534.42 | 0.00 | 0.01 | 25-MAR-20:00 | 0.00 | 01-MAR-00:10 | 39.11 | 25-MAR-20:00 | 33.00 | 25-MAR-20:00 | 8.11 | 19-MAR-19:30 | 9.68 | 25-MAR-20:00 | 0.00 | 01-MAR-00:10 |
April | 0.256369E+09 | 55304296.77 | 28.25 | 0.255633E+09 | 736119.17 | 0.00 | 1.00 | 29-APR-18:01 | 0.00 | 01-APR-00:05 | 15843.46 | 30-APR-19:07 | 15843.46 | 30-APR-19:07 | 803.95 | 30-APR-19:40 | 3198.91 | 30-APR-19:07 | 0.00 | 01-APR-00:05 |
May | 0.166609E+09 | 36586446.66 | 26.48 | 0.152731E+09 | 13877819.98 | 0.00 | 1.00 | 21-MAY-17:01 | 0.00 | 01-MAY-00:10 | 15848.43 | 21-MAY-19:00 | 15656.71 | 21-MAY-17:01 | 1729.31 | 23-MAY-08:63 | 3109.88 | 21-MAY-19:00 | 0.00 | 01-MAY-00:10 |
June | 0.963523E+09 | 0.203944E+09 | 76.37 | 0.830701E+09 | 0.132822E+09 | 0.00 | 1.00 | 12-JUN-08:62 | 0.00 | 01-JUN-00:10 | 17464.33 | 25-JUN-18:00 | 14321.36 | 25-JUN-17:02 | 7231.95 | 27-JUN-08:62 | 3413.22 | 25-JUN-18:00 | 0.00 | 01-JUN-00:10 |
July | 0.159301E+10 | 0.342114E+09 | 137.14 | 0.140366E+10 | 0.189344E+09 | 0.00 | 1.00 | 07-JUL-08:62 | 0.00 | 01-JUL-00:10 | 16802.89 | 23-JUL-17:02 | 15390.55 | 22-JUL-08:62 | 6511.26 | 25-JUL-08:62 | 3386.29 | 22-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.151830E+10 | 0.329490E+09 | 188.90 | 0.130418E+10 | 0.214112E+09 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 16676.21 | 17-AUG-08:62 | 15615.05 | 14-AUG-20:08 | 6705.24 | 17-AUG-08:62 | 3270.87 | 17-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.896889E+09 | 0.194364E+09 | 107.18 | 0.780181E+09 | 0.116708E+09 | 0.00 | 1.00 | 02-SEP-08:62 | 0.00 | 01-SEP-00:05 | 16691.92 | 10-SEP-17:02 | 13739.24 | 24-SEP-17:08 | 5927.28 | 16-SEP-08:62 | 3273.52 | 10-SEP-17:02 | 0.00 | 01-SEP-00:05 |
October | 10714559.63 | 2530982.77 | 7.28 | 10026421.49 | 688138.14 | 0.00 | 0.38 | 03-OCT-20:10 | 0.00 | 01-OCT-00:10 | 2639.40 | 03-OCT-20:10 | 2639.40 | 03-OCT-20:10 | 227.48 | 17-OCT-20:30 | 590.26 | 03-OCT-20:10 | 0.00 | 01-OCT-00:10 |
November | 115176.38 | 28448.42 | 0.83 | 99683.97 | 15492.41 | 0.00 | 0.01 | 05-NOV-19:20 | 0.00 | 01-NOV-00:10 | 94.81 | 05-NOV-19:20 | 87.38 | 05-NOV-19:20 | 14.10 | 08-NOV-22:30 | 23.40 | 05-NOV-19:20 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.540556E+10 | 0.116437E+10 | 572.76 | 0.473725E+10 | 0.668311E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.159301E+10 | 0.342114E+09 | 188.90 | 0.140366E+10 | 0.214112E+09 | 0.00 | 1.00 | 0.00 | 17464.33 | 15843.46 | 7231.95 | 3413.22 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.131766E+09 | 29004441.11 | 16.06 | 0.131349E+09 | 417077.96 | 0.00 | 0.87 | 30-APR-08:63 | 0.00 | 01-APR-00:05 | 7030.22 | 30-APR-08:63 | 6530.14 | 30-APR-08:63 | 500.08 | 30-APR-08:63 | 1359.52 | 30-APR-08:63 | 0.00 | 01-APR-00:05 |
May | 89581997.95 | 20150136.39 | 17.47 | 81627887.56 | 7954110.39 | 0.00 | 0.67 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 5286.83 | 22-MAY-15:00 | 5016.52 | 22-MAY-15:00 | 329.98 | 22-MAY-14:00 | 1138.30 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.757012E+09 | 0.161580E+09 | 65.91 | 0.658996E+09 | 98015572.16 | 0.00 | 1.00 | 13-JUN-07:02 | 0.00 | 01-JUN-00:10 | 16341.75 | 27-JUN-07:02 | 13639.23 | 26-JUN-07:02 | 7268.57 | 27-JUN-07:02 | 3207.37 | 27-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.114407E+10 | 0.248720E+09 | 117.80 | 0.102241E+10 | 0.121655E+09 | 0.00 | 1.00 | 07-JUL-07:03 | 0.00 | 01-JUL-00:10 | 16339.98 | 18-JUL-07:02 | 14664.87 | 22-JUL-07:02 | 6406.23 | 25-JUL-07:02 | 3297.10 | 22-JUL-07:02 | 0.00 | 01-JUL-00:10 |
August | 0.116225E+10 | 0.255281E+09 | 164.88 | 0.100050E+10 | 0.161747E+09 | 0.00 | 1.00 | 03-AUG-07:03 | 0.00 | 01-AUG-00:10 | 16237.30 | 17-AUG-07:02 | 13513.08 | 15-AUG-07:02 | 6681.34 | 17-AUG-07:02 | 3188.74 | 17-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.719243E+09 | 0.157288E+09 | 93.96 | 0.632302E+09 | 86941253.90 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:05 | 16036.16 | 16-SEP-07:03 | 10205.07 | 02-SEP-07:03 | 6444.20 | 16-SEP-07:03 | 3150.95 | 16-SEP-07:03 | 0.00 | 01-SEP-00:05 |
October | 358844.26 | 87820.10 | 1.83 | 356941.86 | 1902.40 | 0.00 | 0.05 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 | 317.33 | 07-OCT-15:00 | 317.33 | 07-OCT-15:00 | 2.06 | 11-OCT-17:30 | 77.22 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.400427E+10 | 0.872112E+09 | 477.91 | 0.352754E+10 | 0.476732E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.116225E+10 | 0.255281E+09 | 164.88 | 0.102241E+10 | 0.161747E+09 | 0.00 | 1.00 | 0.00 | 16341.75 | 14664.87 | 7268.57 | 3297.10 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.125641E+09 | 27718280.37 | 15.47 | 0.125273E+09 | 368538.58 | 0.00 | 0.79 | 30-APR-08:63 | 0.00 | 01-APR-00:05 | 6216.69 | 30-APR-08:63 | 6078.16 | 30-APR-15:00 | 446.85 | 30-APR-08:63 | 1278.71 | 30-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 78944714.37 | 17812087.41 | 15.50 | 72349132.37 | 6595582.00 | 0.00 | 0.64 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 5062.97 | 22-MAY-15:00 | 4802.29 | 22-MAY-15:00 | 312.67 | 22-MAY-14:00 | 1098.39 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.738281E+09 | 0.157907E+09 | 65.30 | 0.642818E+09 | 95463378.36 | 0.00 | 1.00 | 13-JUN-07:02 | 0.00 | 01-JUN-00:10 | 16393.61 | 27-JUN-07:02 | 13678.04 | 26-JUN-07:02 | 7296.76 | 27-JUN-07:02 | 3217.56 | 27-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.112243E+10 | 0.244154E+09 | 116.92 | 0.100395E+10 | 0.118471E+09 | 0.00 | 1.00 | 07-JUL-07:03 | 0.00 | 01-JUL-00:10 | 16391.39 | 18-JUL-07:02 | 14710.41 | 22-JUL-07:02 | 6426.83 | 25-JUL-07:02 | 3307.67 | 22-JUL-07:02 | 0.00 | 01-JUL-00:10 |
August | 0.113187E+10 | 0.248856E+09 | 160.57 | 0.975381E+09 | 0.156494E+09 | 0.00 | 1.00 | 03-AUG-07:03 | 0.00 | 01-AUG-00:10 | 16288.86 | 17-AUG-07:02 | 13554.74 | 15-AUG-07:02 | 6706.62 | 17-AUG-07:02 | 3198.87 | 17-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.695411E+09 | 0.152371E+09 | 90.63 | 0.612071E+09 | 83339871.76 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:05 | 15371.75 | 16-SEP-07:03 | 9607.71 | 02-SEP-07:03 | 6177.91 | 16-SEP-07:03 | 3011.34 | 16-SEP-07:03 | 0.00 | 01-SEP-00:05 |
October | 316205.64 | 77761.68 | 1.92 | 315851.89 | 353.75 | 0.00 | 0.03 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 | 187.43 | 07-OCT-15:00 | 187.43 | 07-OCT-15:00 | 0.59 | 02-OCT-13:20 | 45.85 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.389289E+10 | 0.848897E+09 | 466.31 | 0.343216E+10 | 0.460732E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.113187E+10 | 0.248856E+09 | 160.57 | 0.100395E+10 | 0.156494E+09 | 0.00 | 1.00 | 0.00 | 16393.61 | 14710.41 | 7296.76 | 3307.67 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.113533E+09 | 25128870.45 | 14.97 | 0.113259E+09 | 274609.50 | 0.00 | 0.75 | 30-APR-15:00 | 0.00 | 01-APR-00:05 | 5891.51 | 30-APR-15:00 | 5891.51 | 30-APR-15:00 | 304.80 | 30-APR-08:63 | 1245.73 | 30-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 66033176.56 | 14939613.37 | 12.50 | 61023229.43 | 5009947.13 | 0.00 | 0.61 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 4760.61 | 22-MAY-15:00 | 4513.30 | 22-MAY-15:00 | 289.94 | 22-MAY-14:00 | 1042.04 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.696259E+09 | 0.149419E+09 | 59.64 | 0.606643E+09 | 89616380.92 | 0.00 | 1.00 | 13-JUN-07:02 | 0.00 | 01-JUN-00:10 | 16316.70 | 27-JUN-07:02 | 13591.30 | 26-JUN-07:02 | 7285.26 | 27-JUN-07:02 | 3202.55 | 27-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.105838E+10 | 0.230657E+09 | 110.10 | 0.949690E+09 | 0.108689E+09 | 0.00 | 1.00 | 07-JUL-07:03 | 0.00 | 01-JUL-00:10 | 16314.28 | 18-JUL-07:02 | 14619.49 | 22-JUL-07:02 | 6414.68 | 25-JUL-07:02 | 3292.31 | 22-JUL-07:02 | 0.00 | 01-JUL-00:10 |
August | 0.105493E+10 | 0.232386E+09 | 148.15 | 0.911878E+09 | 0.143047E+09 | 0.00 | 1.00 | 06-AUG-08:62 | 0.00 | 01-AUG-00:10 | 16212.30 | 17-AUG-07:02 | 13470.46 | 15-AUG-07:02 | 6698.11 | 17-AUG-07:02 | 3183.90 | 17-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.643008E+09 | 0.141336E+09 | 82.88 | 0.567474E+09 | 75534366.13 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:05 | 12511.82 | 16-SEP-07:03 | 7885.90 | 02-SEP-07:03 | 5019.05 | 16-SEP-07:03 | 2414.09 | 16-SEP-07:03 | 0.00 | 01-SEP-00:05 |
October | 83604.57 | 20665.95 | 1.17 | 83574.70 | 29.87 | 0.00 | 0.01 | 11-OCT-15:20 | 0.00 | 01-OCT-00:10 | 37.01 | 11-OCT-15:20 | 37.01 | 11-OCT-15:20 | 0.04 | 02-OCT-12:40 | 9.14 | 11-OCT-15:20 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.363222E+10 | 0.793887E+09 | 429.40 | 0.321005E+10 | 0.422171E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.105838E+10 | 0.232386E+09 | 148.15 | 0.949690E+09 | 0.143047E+09 | 0.00 | 1.00 | 0.00 | 16316.70 | 14619.49 | 7285.26 | 3292.31 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.217909E+09 | 55393926.13 | 14.72 | 0.214584E+09 | 3324886.05 | 0.00 | 0.76 | 30-APR-15:00 | 0.00 | 01-APR-00:05 | 10168.83 | 30-APR-15:00 | 10168.83 | 30-APR-15:00 | 335.49 | 28-APR-15:00 | 2455.27 | 30-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 0.136000E+09 | 35539220.51 | 14.83 | 0.116410E+09 | 19589905.04 | 0.00 | 0.63 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 8367.49 | 22-MAY-15:00 | 7457.47 | 22-MAY-15:00 | 910.02 | 22-MAY-15:00 | 2088.87 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.128862E+10 | 0.317493E+09 | 61.72 | 0.106860E+10 | 0.220015E+09 | 0.00 | 1.00 | 13-JUN-08:62 | 0.00 | 01-JUN-00:10 | 29769.95 | 13-JUN-08:62 | 23802.27 | 13-JUN-08:62 | 10991.97 | 27-JUN-08:62 | 6331.90 | 13-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.223968E+10 | 0.559911E+09 | 129.89 | 0.188747E+10 | 0.352214E+09 | 0.00 | 1.00 | 10-JUL-08:62 | 0.00 | 01-JUL-00:10 | 30289.85 | 18-JUL-08:62 | 27604.41 | 22-JUL-08:62 | 11541.85 | 24-JUL-08:62 | 6692.65 | 22-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.258112E+10 | 0.651786E+09 | 187.06 | 0.209881E+10 | 0.482314E+09 | 0.00 | 1.00 | 06-AUG-09:02 | 0.00 | 01-AUG-00:10 | 25719.87 | 18-AUG-08:62 | 18907.02 | 18-AUG-08:62 | 10432.71 | 17-AUG-08:62 | 5475.44 | 18-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.137887E+10 | 0.345833E+09 | 89.44 | 0.115784E+10 | 0.221035E+09 | 0.00 | 0.80 | 13-SEP-14:20 | 0.00 | 01-SEP-00:05 | 11362.16 | 13-SEP-14:20 | 9547.77 | 13-SEP-14:20 | 2567.79 | 12-SEP-14:10 | 2646.25 | 13-SEP-14:20 | 0.00 | 01-SEP-00:05 |
October | 3322516.03 | 918918.05 | 1.33 | 3322516.03 | 0.00 | 0.00 | 0.13 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 | 1414.99 | 07-OCT-15:00 | 1414.99 | 07-OCT-15:00 | 0.00 | 07-OCT-15:20 | 386.98 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.784553E+10 | 0.196688E+10 | 499.01 | 0.654703E+10 | 0.129849E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.258112E+10 | 0.651786E+09 | 187.06 | 0.209881E+10 | 0.482314E+09 | 0.00 | 1.00 | 0.00 | 30289.85 | 27604.41 | 11541.85 | 6692.65 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.102641E+09 | 22729177.82 | 12.56 | 0.102418E+09 | 222605.22 | 0.00 | 0.78 | 30-APR-09:03 | 0.00 | 01-APR-00:05 | 6018.90 | 30-APR-09:03 | 6006.10 | 30-APR-15:00 | 71.52 | 28-APR-15:00 | 1263.43 | 30-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 57947410.30 | 13066957.15 | 8.89 | 53701520.11 | 4245890.20 | 0.00 | 0.63 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 4932.95 | 22-MAY-15:00 | 4599.26 | 22-MAY-15:00 | 333.69 | 22-MAY-15:00 | 1071.83 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.651513E+09 | 0.140330E+09 | 52.55 | 0.564685E+09 | 86827771.30 | 0.00 | 1.00 | 13-JUN-08:62 | 0.00 | 01-JUN-00:10 | 16207.70 | 13-JUN-08:62 | 13026.64 | 13-JUN-08:62 | 7162.73 | 27-JUN-08:62 | 3180.10 | 13-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.964650E+09 | 0.210348E+09 | 96.38 | 0.864487E+09 | 0.100164E+09 | 0.00 | 1.00 | 10-JUL-08:62 | 0.00 | 01-JUL-00:10 | 16199.28 | 18-JUL-08:62 | 14832.37 | 22-JUL-08:62 | 6349.80 | 25-JUL-08:62 | 3302.50 | 22-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.986646E+09 | 0.217418E+09 | 127.75 | 0.853353E+09 | 0.133292E+09 | 0.00 | 1.00 | 06-AUG-09:02 | 0.00 | 01-AUG-00:10 | 16228.21 | 17-AUG-08:62 | 13052.64 | 15-AUG-08:62 | 6557.93 | 17-AUG-08:62 | 3183.62 | 17-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.594499E+09 | 0.130829E+09 | 67.65 | 0.525043E+09 | 69455938.45 | 0.00 | 1.00 | 13-SEP-08:62 | 0.00 | 01-SEP-00:05 | 9568.57 | 13-SEP-08:62 | 7313.78 | 14-SEP-08:62 | 3071.62 | 13-SEP-08:62 | 1799.42 | 13-SEP-08:62 | 0.00 | 01-SEP-00:05 |
October | 80706.33 | 19782.85 | 0.17 | 80706.33 | -0.0 | 0.00 | 0.02 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 | 134.51 | 07-OCT-15:00 | 134.51 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 | 32.97 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.335798E+10 | 0.734741E+09 | 365.94 | 0.296377E+10 | 0.394208E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.986646E+09 | 0.217418E+09 | 127.75 | 0.864487E+09 | 0.133292E+09 | 0.00 | 1.00 | 0.00 | 16228.21 | 14832.37 | 7162.73 | 3302.50 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 98852842.76 | 21929495.65 | 12.14 | 98649552.71 | 203290.05 | 0.00 | 0.76 | 30-APR-15:00 | 0.00 | 01-APR-00:05 | 5908.91 | 30-APR-15:00 | 5908.91 | 30-APR-15:00 | 67.07 | 28-APR-15:00 | 1245.57 | 30-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 55034815.06 | 12417869.73 | 8.33 | 51102925.61 | 3931889.46 | 0.00 | 0.62 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 4835.77 | 22-MAY-15:00 | 4507.74 | 22-MAY-15:00 | 328.03 | 22-MAY-15:00 | 1053.10 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.632864E+09 | 0.136547E+09 | 52.44 | 0.548706E+09 | 84157559.58 | 0.00 | 1.00 | 13-JUN-08:62 | 0.00 | 01-JUN-00:10 | 16117.22 | 13-JUN-08:62 | 12936.77 | 13-JUN-08:62 | 7137.81 | 27-JUN-08:62 | 3162.41 | 13-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.936246E+09 | 0.204326E+09 | 92.73 | 0.840418E+09 | 95827603.50 | 0.00 | 1.00 | 10-JUL-08:62 | 0.00 | 01-JUL-00:10 | 16109.10 | 18-JUL-08:62 | 14739.19 | 22-JUL-08:62 | 6327.16 | 25-JUL-08:62 | 3284.32 | 22-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.948844E+09 | 0.209360E+09 | 124.17 | 0.822012E+09 | 0.126833E+09 | 0.00 | 1.00 | 06-AUG-09:02 | 0.00 | 01-AUG-00:10 | 16138.10 | 17-AUG-08:62 | 12968.46 | 15-AUG-08:62 | 6535.18 | 17-AUG-08:62 | 3165.99 | 17-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.572917E+09 | 0.126343E+09 | 65.32 | 0.506495E+09 | 66421591.18 | 0.00 | 0.95 | 13-SEP-08:62 | 0.00 | 01-SEP-00:05 | 8016.69 | 13-SEP-08:62 | 6317.34 | 14-SEP-08:62 | 2562.25 | 13-SEP-08:62 | 1517.66 | 13-SEP-08:62 | 0.00 | 01-SEP-00:05 |
October | 27792.77 | 6836.90 | 0.17 | 27792.77 | -0.0 | 0.00 | 0.01 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 | 46.32 | 07-OCT-15:00 | 46.32 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 | 11.39 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.324479E+10 | 0.710931E+09 | 355.31 | 0.286741E+10 | 0.377375E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.948844E+09 | 0.209360E+09 | 124.17 | 0.840418E+09 | 0.126833E+09 | 0.00 | 1.00 | 0.00 | 16138.10 | 14739.19 | 7137.81 | 3284.32 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.237015E+09 | 53140802.85 | 32.50 | 0.236998E+09 | 16592.93 | 0.00 | 0.73 | 30-APR-15:00 | 0.00 | 01-APR-00:05 | 5609.40 | 30-APR-15:00 | 5609.40 | 30-APR-15:00 | 9.21 | 28-APR-15:20 | 1192.23 | 30-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 0.229711E+09 | 52670499.49 | 46.17 | 0.204695E+09 | 25015955.50 | 0.00 | 0.60 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 4561.58 | 22-MAY-15:00 | 4210.78 | 22-MAY-15:00 | 488.04 | 23-MAY-14:10 | 1000.53 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.108436E+10 | 0.238351E+09 | 121.37 | 0.959449E+09 | 0.124907E+09 | 0.00 | 0.88 | 13-JUN-15:00 | 0.00 | 01-JUN-00:10 | 7353.88 | 13-JUN-15:00 | 6628.71 | 13-JUN-17:00 | 1342.37 | 26-JUN-17:00 | 1530.48 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.231275E+10 | 0.508864E+09 | 236.23 | 0.203565E+10 | 0.277105E+09 | 0.00 | 1.00 | 22-JUL-08:62 | 0.00 | 01-JUL-00:10 | 16003.76 | 23-JUL-09:01 | 15008.83 | 22-JUL-08:62 | 1817.70 | 23-JUL-09:01 | 3252.69 | 22-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.292192E+10 | 0.643457E+09 | 298.20 | 0.255808E+10 | 0.363837E+09 | 0.00 | 0.84 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 | 6768.71 | 14-AUG-14:50 | 6703.87 | 14-AUG-17:00 | 1154.90 | 17-AUG-13:00 | 1448.09 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 |
September | 0.147908E+10 | 0.326333E+09 | 182.83 | 0.132252E+10 | 0.156557E+09 | 0.00 | 0.77 | 13-SEP-14:40 | 0.00 | 01-SEP-00:05 | 6273.55 | 13-SEP-14:40 | 5555.86 | 13-SEP-14:30 | 1074.14 | 12-SEP-14:10 | 1283.89 | 13-SEP-14:40 | 0.00 | 01-SEP-00:05 |
October | 28270758.26 | 6609508.81 | 9.50 | 28270758.26 | 0.00 | 0.00 | 0.34 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 | 2338.51 | 07-OCT-15:00 | 2338.51 | 07-OCT-15:00 | 0.00 | 07-OCT-14:50 | 528.00 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.829311E+10 | 0.182943E+10 | 926.80 | 0.734567E+10 | 0.947439E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.292192E+10 | 0.643457E+09 | 298.20 | 0.255808E+10 | 0.363837E+09 | 0.00 | 1.00 | 0.00 | 16003.76 | 15008.83 | 1817.70 | 3252.69 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 77404207.28 | 17327469.54 | 11.72 | 77331491.36 | 72715.92 | 0.00 | 0.69 | 30-APR-15:00 | 0.00 | 01-APR-00:05 | 5419.73 | 30-APR-15:00 | 5419.73 | 30-APR-15:00 | 31.80 | 28-APR-15:00 | 1167.42 | 30-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 48039066.62 | 11000985.70 | 8.50 | 44634479.34 | 3404587.28 | 0.00 | 0.56 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 4409.35 | 22-MAY-15:00 | 4108.32 | 22-MAY-15:00 | 301.03 | 22-MAY-15:00 | 978.22 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.563384E+09 | 0.123128E+09 | 46.15 | 0.490082E+09 | 73302653.18 | 0.00 | 0.85 | 13-JUN-15:00 | 0.00 | 01-JUN-00:10 | 7354.69 | 13-JUN-15:00 | 6561.59 | 13-JUN-17:00 | 1259.26 | 26-JUN-08:62 | 1533.94 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.824063E+09 | 0.179778E+09 | 73.11 | 0.752798E+09 | 71264658.17 | 0.00 | 1.00 | 22-JUL-08:62 | 0.00 | 01-JUL-00:10 | 16589.40 | 22-JUL-08:62 | 15199.84 | 22-JUL-08:62 | 3398.47 | 23-JUL-09:03 | 3389.20 | 22-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.754924E+09 | 0.168484E+09 | 96.36 | 0.660144E+09 | 94779586.76 | 0.00 | 0.80 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 | 6735.39 | 14-AUG-13:00 | 6573.01 | 14-AUG-17:00 | 1162.26 | 17-AUG-14:10 | 1438.08 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 |
September | 0.444062E+09 | 99495160.89 | 56.00 | 0.393716E+09 | 50345956.08 | 0.00 | 0.69 | 13-SEP-14:20 | 0.00 | 01-SEP-00:05 | 5668.34 | 13-SEP-14:20 | 4977.12 | 13-SEP-14:20 | 967.01 | 12-SEP-14:10 | 1191.42 | 13-SEP-14:20 | 0.00 | 01-SEP-00:05 |
October | 7914.70 | 1949.67 | 0.17 | 7914.70 | 0.00 | 0.00 | 0.00 | 07-OCT-16:30 | 0.00 | 01-OCT-00:10 | 13.19 | 07-OCT-16:30 | 13.19 | 07-OCT-16:30 | 0.00 | 01-OCT-00:10 | 3.25 | 07-OCT-16:30 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.271188E+10 | 0.599216E+09 | 292.01 | 0.241871E+10 | 0.293170E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.824063E+09 | 0.179778E+09 | 96.36 | 0.752798E+09 | 94779586.76 | 0.00 | 1.00 | 0.00 | 16589.40 | 15199.84 | 3398.47 | 3389.20 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 50.59 | 27.56 | 80.53 | 69.32 | 0.00 | 0.00 | 0.00 |
February | 95.45 | 58.25 | 37.21 | 101.05 | 66.70 | 0.00 | 0.00 | 0.00 |
March | 59.01 | 17.18 | 41.83 | 52.12 | 55.59 | 0.00 | 0.00 | 0.00 |
April | 122.55 | 55.39 | 67.16 | 145.34 | 47.75 | 0.00 | 0.00 | 0.00 |
May | 101.36 | 33.00 | 68.36 | 112.29 | 41.78 | 0.00 | 0.00 | 0.00 |
June | 93.37 | 22.60 | 70.77 | 105.29 | 34.24 | 0.00 | 0.00 | 0.00 |
July | 101.17 | 31.68 | 69.49 | 121.19 | 32.52 | 0.00 | 0.00 | 0.00 |
August | 118.55 | 53.33 | 65.22 | 149.14 | 35.84 | 0.00 | 0.00 | 0.00 |
September | 140.09 | 82.07 | 58.02 | 174.84 | 45.08 | 0.00 | 0.00 | 0.00 |
October | 96.25 | 56.25 | 40.00 | 109.52 | 54.02 | 0.00 | 0.00 | 0.00 |
November | 68.24 | 41.51 | 26.73 | 70.77 | 63.87 | 0.00 | 0.00 | 0.00 |
December | 54.09 | 34.65 | 19.43 | 53.84 | 78.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93.88 | 44.54 | 49.34 | 106.18 | 52.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.09 | 17.18 | 19.43 | 52.12 | 32.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.09 | 82.07 | 70.77 | 174.84 | 78.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 50.59 | 27.56 | 80.53 | 69.32 | 0.00 | 0.00 | 0.00 |
February | 95.45 | 58.25 | 37.21 | 101.05 | 66.70 | 0.00 | 0.00 | 0.00 |
March | 59.01 | 17.18 | 41.83 | 52.12 | 55.59 | 0.00 | 0.00 | 0.00 |
April | 122.55 | 55.39 | 67.16 | 145.34 | 47.75 | 0.00 | 0.00 | 0.00 |
May | 101.36 | 33.00 | 68.36 | 112.29 | 41.78 | 0.00 | 0.00 | 0.00 |
June | 93.37 | 22.60 | 70.77 | 105.29 | 34.24 | 0.00 | 0.00 | 0.00 |
July | 101.17 | 31.68 | 69.49 | 121.19 | 32.52 | 0.00 | 0.00 | 0.00 |
August | 118.55 | 53.33 | 65.22 | 149.14 | 35.84 | 0.00 | 0.00 | 0.00 |
September | 140.09 | 82.07 | 58.02 | 174.84 | 45.08 | 0.00 | 0.00 | 0.00 |
October | 96.25 | 56.25 | 40.00 | 109.52 | 54.02 | 0.00 | 0.00 | 0.00 |
November | 68.24 | 41.51 | 26.73 | 70.77 | 63.87 | 0.00 | 0.00 | 0.00 |
December | 54.09 | 34.65 | 19.43 | 53.84 | 78.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93.88 | 44.54 | 49.34 | 106.18 | 52.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.09 | 17.18 | 19.43 | 52.12 | 32.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.09 | 82.07 | 70.77 | 174.84 | 78.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 50.59 | 27.56 | 80.53 | 69.32 | 0.00 | 0.00 | 0.00 |
February | 95.45 | 58.25 | 37.21 | 101.05 | 66.70 | 0.00 | 0.00 | 0.00 |
March | 59.01 | 17.18 | 41.83 | 52.12 | 55.59 | 0.00 | 0.00 | 0.00 |
April | 122.55 | 55.39 | 67.16 | 145.34 | 47.75 | 0.00 | 0.00 | 0.00 |
May | 101.36 | 33.00 | 68.36 | 112.29 | 41.78 | 0.00 | 0.00 | 0.00 |
June | 93.37 | 22.60 | 70.77 | 105.29 | 34.24 | 0.00 | 0.00 | 0.00 |
July | 101.17 | 31.68 | 69.49 | 121.19 | 32.52 | 0.00 | 0.00 | 0.00 |
August | 118.55 | 53.33 | 65.22 | 149.14 | 35.84 | 0.00 | 0.00 | 0.00 |
September | 140.09 | 82.07 | 58.02 | 174.84 | 45.08 | 0.00 | 0.00 | 0.00 |
October | 96.25 | 56.25 | 40.00 | 109.52 | 54.02 | 0.00 | 0.00 | 0.00 |
November | 68.24 | 41.51 | 26.73 | 70.77 | 63.87 | 0.00 | 0.00 | 0.00 |
December | 54.09 | 34.65 | 19.43 | 53.84 | 78.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93.88 | 44.54 | 49.34 | 106.18 | 52.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.09 | 17.18 | 19.43 | 52.12 | 32.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.09 | 82.07 | 70.77 | 174.84 | 78.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 50.59 | 27.56 | 80.53 | 69.32 | 0.00 | 0.00 | 0.00 |
February | 95.45 | 58.25 | 37.21 | 101.05 | 66.70 | 0.00 | 0.00 | 0.00 |
March | 59.01 | 17.18 | 41.83 | 52.12 | 55.59 | 0.00 | 0.00 | 0.00 |
April | 122.55 | 55.39 | 67.16 | 145.34 | 47.75 | 0.00 | 0.00 | 0.00 |
May | 101.36 | 33.00 | 68.36 | 112.29 | 41.78 | 0.00 | 0.00 | 0.00 |
June | 93.37 | 22.60 | 70.77 | 105.29 | 34.24 | 0.00 | 0.00 | 0.00 |
July | 101.17 | 31.68 | 69.49 | 121.19 | 32.52 | 0.00 | 0.00 | 0.00 |
August | 118.55 | 53.33 | 65.22 | 149.14 | 35.84 | 0.00 | 0.00 | 0.00 |
September | 140.09 | 82.07 | 58.02 | 174.84 | 45.08 | 0.00 | 0.00 | 0.00 |
October | 96.25 | 56.25 | 40.00 | 109.52 | 54.02 | 0.00 | 0.00 | 0.00 |
November | 68.24 | 41.51 | 26.73 | 70.77 | 63.87 | 0.00 | 0.00 | 0.00 |
December | 54.09 | 34.65 | 19.43 | 53.84 | 78.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93.88 | 44.54 | 49.34 | 106.18 | 52.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.09 | 17.18 | 19.43 | 52.12 | 32.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.09 | 82.07 | 70.77 | 174.84 | 78.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 93.95 | 60.82 | 33.13 | 96.98 | 82.58 | 0.00 | 0.00 | 0.00 |
February | 114.75 | 70.02 | 44.73 | 121.70 | 79.35 | 0.00 | 0.00 | 0.00 |
March | 70.94 | 20.66 | 50.29 | 62.89 | 66.24 | 0.00 | 0.00 | 0.00 |
April | 147.32 | 66.59 | 80.73 | 174.84 | 56.93 | 0.00 | 0.00 | 0.00 |
May | 121.85 | 39.67 | 82.18 | 135.23 | 49.69 | 0.00 | 0.00 | 0.00 |
June | 112.25 | 27.17 | 85.08 | 126.75 | 40.76 | 0.00 | 0.00 | 0.00 |
July | 121.62 | 38.09 | 83.53 | 145.79 | 38.73 | 0.00 | 0.00 | 0.00 |
August | 142.51 | 64.11 | 78.41 | 179.31 | 42.75 | 0.00 | 0.00 | 0.00 |
September | 168.41 | 98.66 | 69.75 | 210.26 | 53.75 | 0.00 | 0.00 | 0.00 |
October | 115.71 | 67.63 | 48.08 | 131.77 | 64.35 | 0.00 | 0.00 | 0.00 |
November | 82.04 | 49.90 | 32.13 | 85.23 | 76.01 | 0.00 | 0.00 | 0.00 |
December | 65.02 | 41.66 | 23.36 | 64.87 | 93.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.86 | 53.54 | 59.32 | 127.79 | 61.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 65.02 | 20.66 | 23.36 | 62.89 | 38.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 168.41 | 98.66 | 85.08 | 210.26 | 93.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 93.95 | 60.82 | 33.13 | 96.98 | 82.58 | 0.00 | 0.00 | 0.00 |
February | 114.75 | 70.02 | 44.73 | 121.70 | 79.35 | 0.00 | 0.00 | 0.00 |
March | 70.94 | 20.66 | 50.29 | 62.89 | 66.24 | 0.00 | 0.00 | 0.00 |
April | 147.32 | 66.59 | 80.73 | 174.84 | 56.93 | 0.00 | 0.00 | 0.00 |
May | 121.85 | 39.67 | 82.18 | 135.23 | 49.69 | 0.00 | 0.00 | 0.00 |
June | 112.25 | 27.17 | 85.08 | 126.75 | 40.76 | 0.00 | 0.00 | 0.00 |
July | 121.62 | 38.09 | 83.53 | 145.79 | 38.73 | 0.00 | 0.00 | 0.00 |
August | 142.51 | 64.11 | 78.41 | 179.31 | 42.75 | 0.00 | 0.00 | 0.00 |
September | 168.41 | 98.66 | 69.75 | 210.26 | 53.75 | 0.00 | 0.00 | 0.00 |
October | 115.71 | 67.63 | 48.08 | 131.77 | 64.35 | 0.00 | 0.00 | 0.00 |
November | 82.04 | 49.90 | 32.13 | 85.23 | 76.01 | 0.00 | 0.00 | 0.00 |
December | 65.02 | 41.66 | 23.36 | 64.87 | 93.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.86 | 53.54 | 59.32 | 127.79 | 61.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 65.02 | 20.66 | 23.36 | 62.89 | 38.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 168.41 | 98.66 | 85.08 | 210.26 | 93.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 50.59 | 27.56 | 79.52 | 73.42 | 0.00 | 0.00 | 0.00 |
February | 95.45 | 58.25 | 37.21 | 99.85 | 70.83 | 0.00 | 0.00 | 0.00 |
March | 59.01 | 17.18 | 41.83 | 50.88 | 59.53 | 0.00 | 0.00 | 0.00 |
April | 122.55 | 55.39 | 67.16 | 142.90 | 52.04 | 0.00 | 0.00 | 0.00 |
May | 101.36 | 33.00 | 68.36 | 109.67 | 45.77 | 0.00 | 0.00 | 0.00 |
June | 93.37 | 22.60 | 70.77 | 103.27 | 36.40 | 0.00 | 0.00 | 0.00 |
July | 101.17 | 31.68 | 69.49 | 119.99 | 33.85 | 0.00 | 0.00 | 0.00 |
August | 118.55 | 53.33 | 65.22 | 148.36 | 36.86 | 0.00 | 0.00 | 0.00 |
September | 140.09 | 82.07 | 58.02 | 173.51 | 47.07 | 0.00 | 0.00 | 0.00 |
October | 96.25 | 56.25 | 40.00 | 107.70 | 59.02 | 0.00 | 0.00 | 0.00 |
November | 68.24 | 41.51 | 26.73 | 69.87 | 68.19 | 0.00 | 0.00 | 0.00 |
December | 54.09 | 34.65 | 19.43 | 53.12 | 83.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93.88 | 44.54 | 49.34 | 104.74 | 55.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.09 | 17.18 | 19.43 | 50.88 | 33.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.09 | 82.07 | 70.77 | 173.51 | 83.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 50.59 | 27.56 | 79.52 | 73.42 | 0.00 | 0.00 | 0.00 |
February | 95.45 | 58.25 | 37.21 | 99.85 | 70.83 | 0.00 | 0.00 | 0.00 |
March | 59.01 | 17.18 | 41.83 | 50.88 | 59.53 | 0.00 | 0.00 | 0.00 |
April | 122.55 | 55.39 | 67.16 | 142.90 | 52.04 | 0.00 | 0.00 | 0.00 |
May | 101.36 | 33.00 | 68.36 | 109.67 | 45.77 | 0.00 | 0.00 | 0.00 |
June | 93.37 | 22.60 | 70.77 | 103.27 | 36.40 | 0.00 | 0.00 | 0.00 |
July | 101.17 | 31.68 | 69.49 | 119.99 | 33.85 | 0.00 | 0.00 | 0.00 |
August | 118.55 | 53.33 | 65.22 | 148.36 | 36.86 | 0.00 | 0.00 | 0.00 |
September | 140.09 | 82.07 | 58.02 | 173.51 | 47.07 | 0.00 | 0.00 | 0.00 |
October | 96.25 | 56.25 | 40.00 | 107.70 | 59.02 | 0.00 | 0.00 | 0.00 |
November | 68.24 | 41.51 | 26.73 | 69.87 | 68.19 | 0.00 | 0.00 | 0.00 |
December | 54.09 | 34.65 | 19.43 | 53.12 | 83.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93.88 | 44.54 | 49.34 | 104.74 | 55.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.09 | 17.18 | 19.43 | 50.88 | 33.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.09 | 82.07 | 70.77 | 173.51 | 83.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 93.95 | 60.82 | 33.13 | 95.77 | 87.43 | 0.00 | 0.00 | 0.00 |
February | 114.75 | 70.02 | 44.73 | 120.27 | 84.22 | 0.00 | 0.00 | 0.00 |
March | 70.94 | 20.66 | 50.29 | 61.40 | 70.91 | 0.00 | 0.00 | 0.00 |
April | 147.32 | 66.59 | 80.73 | 171.96 | 62.00 | 0.00 | 0.00 | 0.00 |
May | 121.85 | 39.67 | 82.18 | 132.13 | 54.37 | 0.00 | 0.00 | 0.00 |
June | 112.25 | 27.17 | 85.08 | 124.37 | 43.29 | 0.00 | 0.00 | 0.00 |
July | 121.62 | 38.09 | 83.53 | 144.38 | 40.29 | 0.00 | 0.00 | 0.00 |
August | 142.51 | 64.11 | 78.41 | 178.41 | 43.96 | 0.00 | 0.00 | 0.00 |
September | 168.41 | 98.66 | 69.75 | 208.70 | 56.09 | 0.00 | 0.00 | 0.00 |
October | 115.71 | 67.63 | 48.08 | 129.62 | 70.25 | 0.00 | 0.00 | 0.00 |
November | 82.04 | 49.90 | 32.13 | 84.16 | 81.11 | 0.00 | 0.00 | 0.00 |
December | 65.02 | 41.66 | 23.36 | 64.02 | 98.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.86 | 53.54 | 59.32 | 126.08 | 65.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 65.02 | 20.66 | 23.36 | 61.40 | 40.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 168.41 | 98.66 | 85.08 | 208.70 | 98.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 50.59 | 27.56 | 79.74 | 71.38 | 0.00 | 0.00 | 0.00 |
February | 95.45 | 58.25 | 37.21 | 100.07 | 68.92 | 0.00 | 0.00 | 0.00 |
March | 59.01 | 17.18 | 41.83 | 51.10 | 57.76 | 0.00 | 0.00 | 0.00 |
April | 122.55 | 55.39 | 67.16 | 143.33 | 50.90 | 0.00 | 0.00 | 0.00 |
May | 101.36 | 33.00 | 68.36 | 110.09 | 44.85 | 0.00 | 0.00 | 0.00 |
June | 93.37 | 22.60 | 70.77 | 103.26 | 36.78 | 0.00 | 0.00 | 0.00 |
July | 101.17 | 31.68 | 69.49 | 119.85 | 34.57 | 0.00 | 0.00 | 0.00 |
August | 118.55 | 53.33 | 65.22 | 148.29 | 37.73 | 0.00 | 0.00 | 0.00 |
September | 140.09 | 82.07 | 58.02 | 173.54 | 47.61 | 0.00 | 0.00 | 0.00 |
October | 96.25 | 56.25 | 40.00 | 108.02 | 57.53 | 0.00 | 0.00 | 0.00 |
November | 68.24 | 41.51 | 26.73 | 70.11 | 66.01 | 0.00 | 0.00 | 0.00 |
December | 54.09 | 34.65 | 19.43 | 53.27 | 80.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93.88 | 44.54 | 49.34 | 104.90 | 54.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.09 | 17.18 | 19.43 | 51.10 | 34.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.09 | 82.07 | 70.77 | 173.54 | 80.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 50.59 | 27.56 | 79.74 | 71.38 | 0.00 | 0.00 | 0.00 |
February | 95.45 | 58.25 | 37.21 | 100.07 | 68.92 | 0.00 | 0.00 | 0.00 |
March | 59.01 | 17.18 | 41.83 | 51.10 | 57.76 | 0.00 | 0.00 | 0.00 |
April | 122.55 | 55.39 | 67.16 | 143.33 | 50.90 | 0.00 | 0.00 | 0.00 |
May | 101.36 | 33.00 | 68.36 | 110.09 | 44.85 | 0.00 | 0.00 | 0.00 |
June | 93.37 | 22.60 | 70.77 | 103.26 | 36.78 | 0.00 | 0.00 | 0.00 |
July | 101.17 | 31.68 | 69.49 | 119.85 | 34.57 | 0.00 | 0.00 | 0.00 |
August | 118.55 | 53.33 | 65.22 | 148.29 | 37.73 | 0.00 | 0.00 | 0.00 |
September | 140.09 | 82.07 | 58.02 | 173.54 | 47.61 | 0.00 | 0.00 | 0.00 |
October | 96.25 | 56.25 | 40.00 | 108.02 | 57.53 | 0.00 | 0.00 | 0.00 |
November | 68.24 | 41.51 | 26.73 | 70.11 | 66.01 | 0.00 | 0.00 | 0.00 |
December | 54.09 | 34.65 | 19.43 | 53.27 | 80.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93.88 | 44.54 | 49.34 | 104.90 | 54.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.09 | 17.18 | 19.43 | 51.10 | 34.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.09 | 82.07 | 70.77 | 173.54 | 80.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 93.44 | 60.49 | 32.95 | 95.52 | 84.55 | 0.00 | 0.00 | 0.00 |
February | 114.12 | 69.64 | 44.48 | 119.88 | 81.51 | 0.00 | 0.00 | 0.00 |
March | 70.56 | 20.54 | 50.01 | 61.34 | 68.44 | 0.00 | 0.00 | 0.00 |
April | 146.52 | 66.22 | 80.29 | 171.53 | 60.31 | 0.00 | 0.00 | 0.00 |
May | 121.18 | 39.45 | 81.73 | 131.91 | 53.00 | 0.00 | 0.00 | 0.00 |
June | 111.64 | 27.02 | 84.61 | 123.68 | 43.49 | 0.00 | 0.00 | 0.00 |
July | 120.96 | 37.88 | 83.08 | 143.43 | 40.89 | 0.00 | 0.00 | 0.00 |
August | 141.73 | 63.76 | 77.98 | 177.34 | 44.73 | 0.00 | 0.00 | 0.00 |
September | 167.49 | 98.12 | 69.37 | 207.59 | 56.41 | 0.00 | 0.00 | 0.00 |
October | 115.07 | 67.26 | 47.82 | 129.28 | 68.12 | 0.00 | 0.00 | 0.00 |
November | 81.59 | 49.63 | 31.96 | 83.99 | 78.10 | 0.00 | 0.00 | 0.00 |
December | 64.67 | 41.43 | 23.23 | 63.85 | 95.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.24 | 53.25 | 59.00 | 125.60 | 64.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.67 | 20.54 | 23.23 | 61.34 | 40.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 167.49 | 98.12 | 84.61 | 207.59 | 95.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 50.59 | 27.56 | 79.90 | 70.45 | 0.00 | 0.00 | 0.00 |
February | 95.45 | 58.25 | 37.21 | 100.24 | 68.08 | 0.00 | 0.00 | 0.00 |
March | 59.01 | 17.18 | 41.83 | 51.28 | 56.98 | 0.00 | 0.00 | 0.00 |
April | 122.55 | 55.39 | 67.16 | 143.70 | 50.06 | 0.00 | 0.00 | 0.00 |
May | 101.36 | 33.00 | 68.36 | 110.48 | 44.12 | 0.00 | 0.00 | 0.00 |
June | 93.37 | 22.60 | 70.77 | 103.45 | 36.45 | 0.00 | 0.00 | 0.00 |
July | 101.17 | 31.68 | 69.49 | 119.95 | 34.36 | 0.00 | 0.00 | 0.00 |
August | 118.55 | 53.33 | 65.22 | 148.33 | 37.59 | 0.00 | 0.00 | 0.00 |
September | 140.09 | 82.07 | 58.02 | 173.63 | 47.33 | 0.00 | 0.00 | 0.00 |
October | 96.25 | 56.25 | 40.00 | 108.25 | 56.63 | 0.00 | 0.00 | 0.00 |
November | 68.24 | 41.51 | 26.73 | 70.25 | 65.09 | 0.00 | 0.00 | 0.00 |
December | 54.09 | 34.65 | 19.43 | 53.38 | 79.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93.88 | 44.54 | 49.34 | 105.08 | 53.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.09 | 17.18 | 19.43 | 51.28 | 34.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.09 | 82.07 | 70.77 | 173.63 | 79.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 50.59 | 27.56 | 79.90 | 70.45 | 0.00 | 0.00 | 0.00 |
February | 95.45 | 58.25 | 37.21 | 100.24 | 68.08 | 0.00 | 0.00 | 0.00 |
March | 59.01 | 17.18 | 41.83 | 51.28 | 56.98 | 0.00 | 0.00 | 0.00 |
April | 122.55 | 55.39 | 67.16 | 143.70 | 50.06 | 0.00 | 0.00 | 0.00 |
May | 101.36 | 33.00 | 68.36 | 110.48 | 44.12 | 0.00 | 0.00 | 0.00 |
June | 93.37 | 22.60 | 70.77 | 103.45 | 36.45 | 0.00 | 0.00 | 0.00 |
July | 101.17 | 31.68 | 69.49 | 119.95 | 34.36 | 0.00 | 0.00 | 0.00 |
August | 118.55 | 53.33 | 65.22 | 148.33 | 37.59 | 0.00 | 0.00 | 0.00 |
September | 140.09 | 82.07 | 58.02 | 173.63 | 47.33 | 0.00 | 0.00 | 0.00 |
October | 96.25 | 56.25 | 40.00 | 108.25 | 56.63 | 0.00 | 0.00 | 0.00 |
November | 68.24 | 41.51 | 26.73 | 70.25 | 65.09 | 0.00 | 0.00 | 0.00 |
December | 54.09 | 34.65 | 19.43 | 53.38 | 79.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93.88 | 44.54 | 49.34 | 105.08 | 53.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.09 | 17.18 | 19.43 | 51.28 | 34.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.09 | 82.07 | 70.77 | 173.63 | 79.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 93.44 | 60.49 | 32.95 | 95.71 | 83.44 | 0.00 | 0.00 | 0.00 |
February | 114.12 | 69.64 | 44.48 | 120.08 | 80.52 | 0.00 | 0.00 | 0.00 |
March | 70.56 | 20.54 | 50.01 | 61.55 | 67.51 | 0.00 | 0.00 | 0.00 |
April | 146.52 | 66.22 | 80.29 | 171.97 | 59.32 | 0.00 | 0.00 | 0.00 |
May | 121.18 | 39.45 | 81.73 | 132.36 | 52.13 | 0.00 | 0.00 | 0.00 |
June | 111.64 | 27.02 | 84.61 | 123.90 | 43.09 | 0.00 | 0.00 | 0.00 |
July | 120.96 | 37.88 | 83.08 | 143.54 | 40.65 | 0.00 | 0.00 | 0.00 |
August | 141.73 | 63.76 | 77.98 | 177.40 | 44.56 | 0.00 | 0.00 | 0.00 |
September | 167.49 | 98.12 | 69.37 | 207.69 | 56.08 | 0.00 | 0.00 | 0.00 |
October | 115.07 | 67.26 | 47.82 | 129.56 | 67.04 | 0.00 | 0.00 | 0.00 |
November | 81.59 | 49.63 | 31.96 | 84.16 | 77.01 | 0.00 | 0.00 | 0.00 |
December | 64.67 | 41.43 | 23.23 | 63.98 | 94.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.24 | 53.25 | 59.00 | 125.81 | 63.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.67 | 20.54 | 23.23 | 61.55 | 40.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 167.49 | 98.12 | 84.61 | 207.69 | 94.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 50.59 | 27.56 | 80.06 | 69.75 | 0.00 | 0.00 | 0.00 |
February | 95.45 | 58.25 | 37.21 | 100.41 | 67.44 | 0.00 | 0.00 | 0.00 |
March | 59.01 | 17.18 | 41.83 | 51.47 | 56.38 | 0.00 | 0.00 | 0.00 |
April | 122.55 | 55.39 | 67.16 | 144.16 | 49.26 | 0.00 | 0.00 | 0.00 |
May | 101.36 | 33.00 | 68.36 | 110.97 | 43.37 | 0.00 | 0.00 | 0.00 |
June | 93.37 | 22.60 | 70.77 | 103.87 | 35.89 | 0.00 | 0.00 | 0.00 |
July | 101.17 | 31.68 | 69.49 | 120.18 | 33.99 | 0.00 | 0.00 | 0.00 |
August | 118.55 | 53.33 | 65.22 | 148.46 | 37.31 | 0.00 | 0.00 | 0.00 |
September | 140.09 | 82.07 | 58.02 | 173.83 | 46.90 | 0.00 | 0.00 | 0.00 |
October | 96.25 | 56.25 | 40.00 | 108.56 | 55.76 | 0.00 | 0.00 | 0.00 |
November | 68.24 | 41.51 | 26.73 | 70.38 | 64.43 | 0.00 | 0.00 | 0.00 |
December | 54.09 | 34.65 | 19.43 | 53.49 | 79.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93.88 | 44.54 | 49.34 | 105.34 | 53.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.09 | 17.18 | 19.43 | 51.47 | 33.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.09 | 82.07 | 70.77 | 173.83 | 79.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 50.59 | 27.56 | 80.06 | 69.75 | 0.00 | 0.00 | 0.00 |
February | 95.45 | 58.25 | 37.21 | 100.41 | 67.44 | 0.00 | 0.00 | 0.00 |
March | 59.01 | 17.18 | 41.83 | 51.47 | 56.38 | 0.00 | 0.00 | 0.00 |
April | 122.55 | 55.39 | 67.16 | 144.16 | 49.26 | 0.00 | 0.00 | 0.00 |
May | 101.36 | 33.00 | 68.36 | 110.97 | 43.37 | 0.00 | 0.00 | 0.00 |
June | 93.37 | 22.60 | 70.77 | 103.87 | 35.89 | 0.00 | 0.00 | 0.00 |
July | 101.17 | 31.68 | 69.49 | 120.18 | 33.99 | 0.00 | 0.00 | 0.00 |
August | 118.55 | 53.33 | 65.22 | 148.46 | 37.31 | 0.00 | 0.00 | 0.00 |
September | 140.09 | 82.07 | 58.02 | 173.83 | 46.90 | 0.00 | 0.00 | 0.00 |
October | 96.25 | 56.25 | 40.00 | 108.56 | 55.76 | 0.00 | 0.00 | 0.00 |
November | 68.24 | 41.51 | 26.73 | 70.38 | 64.43 | 0.00 | 0.00 | 0.00 |
December | 54.09 | 34.65 | 19.43 | 53.49 | 79.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93.88 | 44.54 | 49.34 | 105.34 | 53.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.09 | 17.18 | 19.43 | 51.47 | 33.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.09 | 82.07 | 70.77 | 173.83 | 79.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 93.44 | 60.49 | 32.95 | 95.91 | 82.61 | 0.00 | 0.00 | 0.00 |
February | 114.12 | 69.64 | 44.48 | 120.29 | 79.77 | 0.00 | 0.00 | 0.00 |
March | 70.56 | 20.54 | 50.01 | 61.79 | 66.80 | 0.00 | 0.00 | 0.00 |
April | 146.52 | 66.22 | 80.29 | 172.52 | 58.38 | 0.00 | 0.00 | 0.00 |
May | 121.18 | 39.45 | 81.73 | 132.96 | 51.25 | 0.00 | 0.00 | 0.00 |
June | 111.64 | 27.02 | 84.61 | 124.41 | 42.44 | 0.00 | 0.00 | 0.00 |
July | 120.96 | 37.88 | 83.08 | 143.83 | 40.21 | 0.00 | 0.00 | 0.00 |
August | 141.73 | 63.76 | 77.98 | 177.54 | 44.23 | 0.00 | 0.00 | 0.00 |
September | 167.49 | 98.12 | 69.37 | 207.93 | 55.57 | 0.00 | 0.00 | 0.00 |
October | 115.07 | 67.26 | 47.82 | 129.93 | 66.02 | 0.00 | 0.00 | 0.00 |
November | 81.59 | 49.63 | 31.96 | 84.32 | 76.22 | 0.00 | 0.00 | 0.00 |
December | 64.67 | 41.43 | 23.23 | 64.12 | 93.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.24 | 53.25 | 59.00 | 126.12 | 63.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.67 | 20.54 | 23.23 | 61.79 | 40.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 167.49 | 98.12 | 84.61 | 207.93 | 93.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 50.59 | 27.56 | 80.70 | 68.09 | 0.00 | 0.00 | 0.00 |
February | 95.45 | 58.25 | 37.21 | 101.13 | 65.85 | 0.00 | 0.00 | 0.00 |
March | 59.01 | 17.18 | 41.83 | 52.18 | 54.98 | 0.00 | 0.00 | 0.00 |
April | 122.55 | 55.39 | 67.16 | 145.22 | 47.77 | 0.00 | 0.00 | 0.00 |
May | 101.36 | 33.00 | 68.36 | 112.15 | 41.92 | 0.00 | 0.00 | 0.00 |
June | 93.37 | 22.60 | 70.77 | 105.06 | 34.57 | 0.00 | 0.00 | 0.00 |
July | 101.17 | 31.68 | 69.49 | 120.87 | 33.06 | 0.00 | 0.00 | 0.00 |
August | 118.55 | 53.33 | 65.22 | 148.83 | 36.56 | 0.00 | 0.00 | 0.00 |
September | 140.09 | 82.07 | 58.02 | 174.51 | 45.77 | 0.00 | 0.00 | 0.00 |
October | 96.25 | 56.25 | 40.00 | 109.39 | 54.01 | 0.00 | 0.00 | 0.00 |
November | 68.24 | 41.51 | 26.73 | 70.88 | 62.86 | 0.00 | 0.00 | 0.00 |
December | 54.09 | 34.65 | 19.43 | 53.98 | 77.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93.88 | 44.54 | 49.34 | 106.09 | 51.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.09 | 17.18 | 19.43 | 52.18 | 33.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.09 | 82.07 | 70.77 | 174.51 | 77.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 50.59 | 27.56 | 80.70 | 68.09 | 0.00 | 0.00 | 0.00 |
February | 95.45 | 58.25 | 37.21 | 101.13 | 65.85 | 0.00 | 0.00 | 0.00 |
March | 59.01 | 17.18 | 41.83 | 52.18 | 54.98 | 0.00 | 0.00 | 0.00 |
April | 122.55 | 55.39 | 67.16 | 145.22 | 47.77 | 0.00 | 0.00 | 0.00 |
May | 101.36 | 33.00 | 68.36 | 112.15 | 41.92 | 0.00 | 0.00 | 0.00 |
June | 93.37 | 22.60 | 70.77 | 105.06 | 34.57 | 0.00 | 0.00 | 0.00 |
July | 101.17 | 31.68 | 69.49 | 120.87 | 33.06 | 0.00 | 0.00 | 0.00 |
August | 118.55 | 53.33 | 65.22 | 148.83 | 36.56 | 0.00 | 0.00 | 0.00 |
September | 140.09 | 82.07 | 58.02 | 174.51 | 45.77 | 0.00 | 0.00 | 0.00 |
October | 96.25 | 56.25 | 40.00 | 109.39 | 54.01 | 0.00 | 0.00 | 0.00 |
November | 68.24 | 41.51 | 26.73 | 70.88 | 62.86 | 0.00 | 0.00 | 0.00 |
December | 54.09 | 34.65 | 19.43 | 53.98 | 77.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93.88 | 44.54 | 49.34 | 106.09 | 51.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.09 | 17.18 | 19.43 | 52.18 | 33.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.09 | 82.07 | 70.77 | 174.51 | 77.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 50.59 | 27.56 | 80.70 | 68.09 | 0.00 | 0.00 | 0.00 |
February | 95.45 | 58.25 | 37.21 | 101.13 | 65.85 | 0.00 | 0.00 | 0.00 |
March | 59.01 | 17.18 | 41.83 | 52.18 | 54.98 | 0.00 | 0.00 | 0.00 |
April | 122.55 | 55.39 | 67.16 | 145.22 | 47.77 | 0.00 | 0.00 | 0.00 |
May | 101.36 | 33.00 | 68.36 | 112.15 | 41.92 | 0.00 | 0.00 | 0.00 |
June | 93.37 | 22.60 | 70.77 | 105.06 | 34.57 | 0.00 | 0.00 | 0.00 |
July | 101.17 | 31.68 | 69.49 | 120.87 | 33.06 | 0.00 | 0.00 | 0.00 |
August | 118.55 | 53.33 | 65.22 | 148.83 | 36.56 | 0.00 | 0.00 | 0.00 |
September | 140.09 | 82.07 | 58.02 | 174.51 | 45.77 | 0.00 | 0.00 | 0.00 |
October | 96.25 | 56.25 | 40.00 | 109.39 | 54.01 | 0.00 | 0.00 | 0.00 |
November | 68.24 | 41.51 | 26.73 | 70.88 | 62.86 | 0.00 | 0.00 | 0.00 |
December | 54.09 | 34.65 | 19.43 | 53.98 | 77.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93.88 | 44.54 | 49.34 | 106.09 | 51.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.09 | 17.18 | 19.43 | 52.18 | 33.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.09 | 82.07 | 70.77 | 174.51 | 77.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 50.59 | 27.56 | 80.70 | 68.09 | 0.00 | 0.00 | 0.00 |
February | 95.45 | 58.25 | 37.21 | 101.13 | 65.85 | 0.00 | 0.00 | 0.00 |
March | 59.01 | 17.18 | 41.83 | 52.18 | 54.98 | 0.00 | 0.00 | 0.00 |
April | 122.55 | 55.39 | 67.16 | 145.22 | 47.77 | 0.00 | 0.00 | 0.00 |
May | 101.36 | 33.00 | 68.36 | 112.15 | 41.92 | 0.00 | 0.00 | 0.00 |
June | 93.37 | 22.60 | 70.77 | 105.06 | 34.57 | 0.00 | 0.00 | 0.00 |
July | 101.17 | 31.68 | 69.49 | 120.87 | 33.06 | 0.00 | 0.00 | 0.00 |
August | 118.55 | 53.33 | 65.22 | 148.83 | 36.56 | 0.00 | 0.00 | 0.00 |
September | 140.09 | 82.07 | 58.02 | 174.51 | 45.77 | 0.00 | 0.00 | 0.00 |
October | 96.25 | 56.25 | 40.00 | 109.39 | 54.01 | 0.00 | 0.00 | 0.00 |
November | 68.24 | 41.51 | 26.73 | 70.88 | 62.86 | 0.00 | 0.00 | 0.00 |
December | 54.09 | 34.65 | 19.43 | 53.98 | 77.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93.88 | 44.54 | 49.34 | 106.09 | 51.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.09 | 17.18 | 19.43 | 52.18 | 33.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.09 | 82.07 | 70.77 | 174.51 | 77.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 93.44 | 60.49 | 32.95 | 96.66 | 80.66 | 0.00 | 0.00 | 0.00 |
February | 114.12 | 69.64 | 44.48 | 121.13 | 77.89 | 0.00 | 0.00 | 0.00 |
March | 70.56 | 20.54 | 50.01 | 62.62 | 65.15 | 0.00 | 0.00 | 0.00 |
April | 146.52 | 66.22 | 80.29 | 173.74 | 56.62 | 0.00 | 0.00 | 0.00 |
May | 121.18 | 39.45 | 81.73 | 134.33 | 49.56 | 0.00 | 0.00 | 0.00 |
June | 111.64 | 27.02 | 84.61 | 125.79 | 40.90 | 0.00 | 0.00 | 0.00 |
July | 120.96 | 37.88 | 83.08 | 144.62 | 39.14 | 0.00 | 0.00 | 0.00 |
August | 141.73 | 63.76 | 77.98 | 177.96 | 43.35 | 0.00 | 0.00 | 0.00 |
September | 167.49 | 98.12 | 69.37 | 208.72 | 54.25 | 0.00 | 0.00 | 0.00 |
October | 115.07 | 67.26 | 47.82 | 130.90 | 63.96 | 0.00 | 0.00 | 0.00 |
November | 81.59 | 49.63 | 31.96 | 84.90 | 74.39 | 0.00 | 0.00 | 0.00 |
December | 64.67 | 41.43 | 23.23 | 64.69 | 91.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.24 | 53.25 | 59.00 | 126.99 | 61.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.67 | 20.54 | 23.23 | 62.62 | 39.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 167.49 | 98.12 | 84.61 | 208.72 | 91.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 93.44 | 60.49 | 32.95 | 96.66 | 80.66 | 0.00 | 0.00 | 0.00 |
February | 114.12 | 69.64 | 44.48 | 121.13 | 77.89 | 0.00 | 0.00 | 0.00 |
March | 70.56 | 20.54 | 50.01 | 62.62 | 65.15 | 0.00 | 0.00 | 0.00 |
April | 146.52 | 66.22 | 80.29 | 173.74 | 56.62 | 0.00 | 0.00 | 0.00 |
May | 121.18 | 39.45 | 81.73 | 134.33 | 49.56 | 0.00 | 0.00 | 0.00 |
June | 111.64 | 27.02 | 84.61 | 125.79 | 40.90 | 0.00 | 0.00 | 0.00 |
July | 120.96 | 37.88 | 83.08 | 144.62 | 39.14 | 0.00 | 0.00 | 0.00 |
August | 141.73 | 63.76 | 77.98 | 177.96 | 43.35 | 0.00 | 0.00 | 0.00 |
September | 167.49 | 98.12 | 69.37 | 208.72 | 54.25 | 0.00 | 0.00 | 0.00 |
October | 115.07 | 67.26 | 47.82 | 130.90 | 63.96 | 0.00 | 0.00 | 0.00 |
November | 81.59 | 49.63 | 31.96 | 84.90 | 74.39 | 0.00 | 0.00 | 0.00 |
December | 64.67 | 41.43 | 23.23 | 64.69 | 91.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.24 | 53.25 | 59.00 | 126.99 | 61.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.67 | 20.54 | 23.23 | 62.62 | 39.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 167.49 | 98.12 | 84.61 | 208.72 | 91.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 50.59 | 27.56 | 80.50 | 68.34 | 0.00 | 0.00 | 0.00 |
February | 95.45 | 58.25 | 37.21 | 100.89 | 66.10 | 0.00 | 0.00 | 0.00 |
March | 59.01 | 17.18 | 41.83 | 51.96 | 55.14 | 0.00 | 0.00 | 0.00 |
April | 122.55 | 55.39 | 67.16 | 144.70 | 48.05 | 0.00 | 0.00 | 0.00 |
May | 101.36 | 33.00 | 68.36 | 111.53 | 42.29 | 0.00 | 0.00 | 0.00 |
June | 93.37 | 22.60 | 70.77 | 104.38 | 34.95 | 0.00 | 0.00 | 0.00 |
July | 101.17 | 31.68 | 69.49 | 120.47 | 33.19 | 0.00 | 0.00 | 0.00 |
August | 118.55 | 53.33 | 65.22 | 148.60 | 36.54 | 0.00 | 0.00 | 0.00 |
September | 140.09 | 82.07 | 58.02 | 174.02 | 46.08 | 0.00 | 0.00 | 0.00 |
October | 96.25 | 56.25 | 40.00 | 108.92 | 54.48 | 0.00 | 0.00 | 0.00 |
November | 68.24 | 41.51 | 26.73 | 70.70 | 63.11 | 0.00 | 0.00 | 0.00 |
December | 54.09 | 34.65 | 19.43 | 53.83 | 77.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93.88 | 44.54 | 49.34 | 105.72 | 52.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.09 | 17.18 | 19.43 | 51.96 | 33.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.09 | 82.07 | 70.77 | 174.02 | 77.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 50.59 | 27.56 | 80.50 | 68.34 | 0.00 | 0.00 | 0.00 |
February | 95.45 | 58.25 | 37.21 | 100.89 | 66.10 | 0.00 | 0.00 | 0.00 |
March | 59.01 | 17.18 | 41.83 | 51.96 | 55.14 | 0.00 | 0.00 | 0.00 |
April | 122.55 | 55.39 | 67.16 | 144.70 | 48.05 | 0.00 | 0.00 | 0.00 |
May | 101.36 | 33.00 | 68.36 | 111.53 | 42.29 | 0.00 | 0.00 | 0.00 |
June | 93.37 | 22.60 | 70.77 | 104.38 | 34.95 | 0.00 | 0.00 | 0.00 |
July | 101.17 | 31.68 | 69.49 | 120.47 | 33.19 | 0.00 | 0.00 | 0.00 |
August | 118.55 | 53.33 | 65.22 | 148.60 | 36.54 | 0.00 | 0.00 | 0.00 |
September | 140.09 | 82.07 | 58.02 | 174.02 | 46.08 | 0.00 | 0.00 | 0.00 |
October | 96.25 | 56.25 | 40.00 | 108.92 | 54.48 | 0.00 | 0.00 | 0.00 |
November | 68.24 | 41.51 | 26.73 | 70.70 | 63.11 | 0.00 | 0.00 | 0.00 |
December | 54.09 | 34.65 | 19.43 | 53.83 | 77.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93.88 | 44.54 | 49.34 | 105.72 | 52.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.09 | 17.18 | 19.43 | 51.96 | 33.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.09 | 82.07 | 70.77 | 174.02 | 77.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 93.44 | 60.49 | 32.95 | 96.44 | 80.93 | 0.00 | 0.00 | 0.00 |
February | 114.12 | 69.64 | 44.48 | 120.86 | 78.17 | 0.00 | 0.00 | 0.00 |
March | 70.56 | 20.54 | 50.01 | 62.38 | 65.32 | 0.00 | 0.00 | 0.00 |
April | 146.52 | 66.22 | 80.29 | 173.17 | 56.94 | 0.00 | 0.00 | 0.00 |
May | 121.18 | 39.45 | 81.73 | 133.63 | 49.98 | 0.00 | 0.00 | 0.00 |
June | 111.64 | 27.02 | 84.61 | 125.02 | 41.34 | 0.00 | 0.00 | 0.00 |
July | 120.96 | 37.88 | 83.08 | 144.18 | 39.27 | 0.00 | 0.00 | 0.00 |
August | 141.73 | 63.76 | 77.98 | 177.73 | 43.32 | 0.00 | 0.00 | 0.00 |
September | 167.49 | 98.12 | 69.37 | 208.17 | 54.61 | 0.00 | 0.00 | 0.00 |
October | 115.07 | 67.26 | 47.82 | 130.37 | 64.50 | 0.00 | 0.00 | 0.00 |
November | 81.59 | 49.63 | 31.96 | 84.70 | 74.66 | 0.00 | 0.00 | 0.00 |
December | 64.67 | 41.43 | 23.23 | 64.52 | 91.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.24 | 53.25 | 59.00 | 126.58 | 61.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.67 | 20.54 | 23.23 | 62.38 | 39.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 167.49 | 98.12 | 84.61 | 208.17 | 91.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 50.59 | 27.56 | 80.58 | 68.04 | 0.00 | 0.00 | 0.00 |
February | 95.45 | 58.25 | 37.21 | 100.99 | 65.79 | 0.00 | 0.00 | 0.00 |
March | 59.01 | 17.18 | 41.83 | 52.06 | 54.86 | 0.00 | 0.00 | 0.00 |
April | 122.55 | 55.39 | 67.16 | 144.87 | 47.80 | 0.00 | 0.00 | 0.00 |
May | 101.36 | 33.00 | 68.36 | 111.73 | 42.03 | 0.00 | 0.00 | 0.00 |
June | 93.37 | 22.60 | 70.77 | 104.57 | 34.75 | 0.00 | 0.00 | 0.00 |
July | 101.17 | 31.68 | 69.49 | 120.61 | 33.02 | 0.00 | 0.00 | 0.00 |
August | 118.55 | 53.33 | 65.22 | 148.70 | 36.38 | 0.00 | 0.00 | 0.00 |
September | 140.09 | 82.07 | 58.02 | 174.14 | 45.89 | 0.00 | 0.00 | 0.00 |
October | 96.25 | 56.25 | 40.00 | 109.06 | 54.16 | 0.00 | 0.00 | 0.00 |
November | 68.24 | 41.51 | 26.73 | 70.78 | 62.79 | 0.00 | 0.00 | 0.00 |
December | 54.09 | 34.65 | 19.43 | 53.88 | 77.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93.88 | 44.54 | 49.34 | 105.84 | 51.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.09 | 17.18 | 19.43 | 52.06 | 33.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.09 | 82.07 | 70.77 | 174.14 | 77.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 50.59 | 27.56 | 80.58 | 68.04 | 0.00 | 0.00 | 0.00 |
February | 95.45 | 58.25 | 37.21 | 100.99 | 65.79 | 0.00 | 0.00 | 0.00 |
March | 59.01 | 17.18 | 41.83 | 52.06 | 54.86 | 0.00 | 0.00 | 0.00 |
April | 122.55 | 55.39 | 67.16 | 144.87 | 47.80 | 0.00 | 0.00 | 0.00 |
May | 101.36 | 33.00 | 68.36 | 111.73 | 42.03 | 0.00 | 0.00 | 0.00 |
June | 93.37 | 22.60 | 70.77 | 104.57 | 34.75 | 0.00 | 0.00 | 0.00 |
July | 101.17 | 31.68 | 69.49 | 120.61 | 33.02 | 0.00 | 0.00 | 0.00 |
August | 118.55 | 53.33 | 65.22 | 148.70 | 36.38 | 0.00 | 0.00 | 0.00 |
September | 140.09 | 82.07 | 58.02 | 174.14 | 45.89 | 0.00 | 0.00 | 0.00 |
October | 96.25 | 56.25 | 40.00 | 109.06 | 54.16 | 0.00 | 0.00 | 0.00 |
November | 68.24 | 41.51 | 26.73 | 70.78 | 62.79 | 0.00 | 0.00 | 0.00 |
December | 54.09 | 34.65 | 19.43 | 53.88 | 77.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93.88 | 44.54 | 49.34 | 105.84 | 51.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.09 | 17.18 | 19.43 | 52.06 | 33.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.09 | 82.07 | 70.77 | 174.14 | 77.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 93.44 | 60.49 | 32.95 | 96.53 | 80.58 | 0.00 | 0.00 | 0.00 |
February | 114.12 | 69.64 | 44.48 | 120.99 | 77.80 | 0.00 | 0.00 | 0.00 |
March | 70.56 | 20.54 | 50.01 | 62.50 | 64.99 | 0.00 | 0.00 | 0.00 |
April | 146.52 | 66.22 | 80.29 | 173.37 | 56.63 | 0.00 | 0.00 | 0.00 |
May | 121.18 | 39.45 | 81.73 | 133.87 | 49.68 | 0.00 | 0.00 | 0.00 |
June | 111.64 | 27.02 | 84.61 | 125.25 | 41.10 | 0.00 | 0.00 | 0.00 |
July | 120.96 | 37.88 | 83.08 | 144.35 | 39.07 | 0.00 | 0.00 | 0.00 |
August | 141.73 | 63.76 | 77.98 | 177.85 | 43.14 | 0.00 | 0.00 | 0.00 |
September | 167.49 | 98.12 | 69.37 | 208.32 | 54.38 | 0.00 | 0.00 | 0.00 |
October | 115.07 | 67.26 | 47.82 | 130.53 | 64.12 | 0.00 | 0.00 | 0.00 |
November | 81.59 | 49.63 | 31.96 | 84.80 | 74.27 | 0.00 | 0.00 | 0.00 |
December | 64.67 | 41.43 | 23.23 | 64.58 | 91.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.24 | 53.25 | 59.00 | 126.73 | 61.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.67 | 20.54 | 23.23 | 62.50 | 39.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 167.49 | 98.12 | 84.61 | 208.32 | 91.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 50.59 | 27.56 | 80.89 | 66.80 | 0.00 | 0.00 | 0.00 |
February | 95.45 | 58.25 | 37.21 | 101.39 | 64.52 | 0.00 | 0.00 | 0.00 |
March | 59.01 | 17.18 | 41.83 | 52.48 | 53.68 | 0.00 | 0.00 | 0.00 |
April | 122.55 | 55.39 | 67.16 | 145.63 | 46.68 | 0.00 | 0.00 | 0.00 |
May | 101.36 | 33.00 | 68.36 | 112.66 | 40.91 | 0.00 | 0.00 | 0.00 |
June | 93.37 | 22.60 | 70.77 | 105.57 | 33.77 | 0.00 | 0.00 | 0.00 |
July | 101.17 | 31.68 | 69.49 | 121.32 | 32.31 | 0.00 | 0.00 | 0.00 |
August | 118.55 | 53.33 | 65.22 | 149.18 | 35.78 | 0.00 | 0.00 | 0.00 |
September | 140.09 | 82.07 | 58.02 | 174.84 | 44.95 | 0.00 | 0.00 | 0.00 |
October | 96.25 | 56.25 | 40.00 | 109.72 | 52.70 | 0.00 | 0.00 | 0.00 |
November | 68.24 | 41.51 | 26.73 | 71.12 | 61.47 | 0.00 | 0.00 | 0.00 |
December | 54.09 | 34.65 | 19.43 | 54.09 | 75.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93.88 | 44.54 | 49.34 | 106.42 | 50.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.09 | 17.18 | 19.43 | 52.48 | 32.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.09 | 82.07 | 70.77 | 174.84 | 75.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 50.59 | 27.56 | 80.89 | 66.80 | 0.00 | 0.00 | 0.00 |
February | 95.45 | 58.25 | 37.21 | 101.39 | 64.52 | 0.00 | 0.00 | 0.00 |
March | 59.01 | 17.18 | 41.83 | 52.48 | 53.68 | 0.00 | 0.00 | 0.00 |
April | 122.55 | 55.39 | 67.16 | 145.63 | 46.68 | 0.00 | 0.00 | 0.00 |
May | 101.36 | 33.00 | 68.36 | 112.66 | 40.91 | 0.00 | 0.00 | 0.00 |
June | 93.37 | 22.60 | 70.77 | 105.57 | 33.77 | 0.00 | 0.00 | 0.00 |
July | 101.17 | 31.68 | 69.49 | 121.32 | 32.31 | 0.00 | 0.00 | 0.00 |
August | 118.55 | 53.33 | 65.22 | 149.18 | 35.78 | 0.00 | 0.00 | 0.00 |
September | 140.09 | 82.07 | 58.02 | 174.84 | 44.95 | 0.00 | 0.00 | 0.00 |
October | 96.25 | 56.25 | 40.00 | 109.72 | 52.70 | 0.00 | 0.00 | 0.00 |
November | 68.24 | 41.51 | 26.73 | 71.12 | 61.47 | 0.00 | 0.00 | 0.00 |
December | 54.09 | 34.65 | 19.43 | 54.09 | 75.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93.88 | 44.54 | 49.34 | 106.42 | 50.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.09 | 17.18 | 19.43 | 52.48 | 32.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.09 | 82.07 | 70.77 | 174.84 | 75.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 93.44 | 60.49 | 32.95 | 96.91 | 79.10 | 0.00 | 0.00 | 0.00 |
February | 114.12 | 69.64 | 44.48 | 121.47 | 76.30 | 0.00 | 0.00 | 0.00 |
March | 70.56 | 20.54 | 50.01 | 63.01 | 63.59 | 0.00 | 0.00 | 0.00 |
April | 146.52 | 66.22 | 80.29 | 174.27 | 55.32 | 0.00 | 0.00 | 0.00 |
May | 121.18 | 39.45 | 81.73 | 134.98 | 48.35 | 0.00 | 0.00 | 0.00 |
June | 111.64 | 27.02 | 84.61 | 126.44 | 39.94 | 0.00 | 0.00 | 0.00 |
July | 120.96 | 37.88 | 83.08 | 145.19 | 38.23 | 0.00 | 0.00 | 0.00 |
August | 141.73 | 63.76 | 77.98 | 178.42 | 42.43 | 0.00 | 0.00 | 0.00 |
September | 167.49 | 98.12 | 69.37 | 209.15 | 53.27 | 0.00 | 0.00 | 0.00 |
October | 115.07 | 67.26 | 47.82 | 131.32 | 62.39 | 0.00 | 0.00 | 0.00 |
November | 81.59 | 49.63 | 31.96 | 85.20 | 72.71 | 0.00 | 0.00 | 0.00 |
December | 64.67 | 41.43 | 23.23 | 64.84 | 89.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.24 | 53.25 | 59.00 | 127.42 | 60.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.67 | 20.54 | 23.23 | 63.01 | 38.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 167.49 | 98.12 | 84.61 | 209.15 | 89.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 50.59 | 27.56 | 81.75 | 62.50 | 0.00 | 0.00 | 0.00 |
February | 95.45 | 58.25 | 37.21 | 102.47 | 60.05 | 0.00 | 0.00 | 0.00 |
March | 59.01 | 17.18 | 41.83 | 53.56 | 49.79 | 0.00 | 0.00 | 0.00 |
April | 122.55 | 55.39 | 67.16 | 146.57 | 43.46 | 0.00 | 0.00 | 0.00 |
May | 101.36 | 33.00 | 68.36 | 113.94 | 37.56 | 0.00 | 0.00 | 0.00 |
June | 93.37 | 22.60 | 70.77 | 106.92 | 30.98 | 0.00 | 0.00 | 0.00 |
July | 101.17 | 31.68 | 69.49 | 122.18 | 30.05 | 0.00 | 0.00 | 0.00 |
August | 118.55 | 53.33 | 65.22 | 149.78 | 33.60 | 0.00 | 0.00 | 0.00 |
September | 140.09 | 82.07 | 58.02 | 175.63 | 42.10 | 0.00 | 0.00 | 0.00 |
October | 96.25 | 56.25 | 40.00 | 110.66 | 49.00 | 0.00 | 0.00 | 0.00 |
November | 68.24 | 41.51 | 26.73 | 71.82 | 57.47 | 0.00 | 0.00 | 0.00 |
December | 54.09 | 34.65 | 19.43 | 54.68 | 71.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93.88 | 44.54 | 49.34 | 107.34 | 47.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.09 | 17.18 | 19.43 | 53.56 | 30.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.09 | 82.07 | 70.77 | 175.63 | 71.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 50.59 | 27.56 | 81.75 | 62.50 | 0.00 | 0.00 | 0.00 |
February | 95.45 | 58.25 | 37.21 | 102.47 | 60.05 | 0.00 | 0.00 | 0.00 |
March | 59.01 | 17.18 | 41.83 | 53.56 | 49.79 | 0.00 | 0.00 | 0.00 |
April | 122.55 | 55.39 | 67.16 | 146.57 | 43.46 | 0.00 | 0.00 | 0.00 |
May | 101.36 | 33.00 | 68.36 | 113.94 | 37.56 | 0.00 | 0.00 | 0.00 |
June | 93.37 | 22.60 | 70.77 | 106.92 | 30.98 | 0.00 | 0.00 | 0.00 |
July | 101.17 | 31.68 | 69.49 | 122.18 | 30.05 | 0.00 | 0.00 | 0.00 |
August | 118.55 | 53.33 | 65.22 | 149.78 | 33.60 | 0.00 | 0.00 | 0.00 |
September | 140.09 | 82.07 | 58.02 | 175.63 | 42.10 | 0.00 | 0.00 | 0.00 |
October | 96.25 | 56.25 | 40.00 | 110.66 | 49.00 | 0.00 | 0.00 | 0.00 |
November | 68.24 | 41.51 | 26.73 | 71.82 | 57.47 | 0.00 | 0.00 | 0.00 |
December | 54.09 | 34.65 | 19.43 | 54.68 | 71.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93.88 | 44.54 | 49.34 | 107.34 | 47.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.09 | 17.18 | 19.43 | 53.56 | 30.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.09 | 82.07 | 70.77 | 175.63 | 71.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 93.44 | 60.49 | 32.95 | 97.96 | 73.99 | 0.00 | 0.00 | 0.00 |
February | 114.12 | 69.64 | 44.48 | 122.78 | 70.99 | 0.00 | 0.00 | 0.00 |
March | 70.56 | 20.54 | 50.01 | 64.32 | 58.98 | 0.00 | 0.00 | 0.00 |
April | 146.52 | 66.22 | 80.29 | 175.42 | 51.51 | 0.00 | 0.00 | 0.00 |
May | 121.18 | 39.45 | 81.73 | 136.52 | 44.42 | 0.00 | 0.00 | 0.00 |
June | 111.64 | 27.02 | 84.61 | 128.05 | 36.65 | 0.00 | 0.00 | 0.00 |
July | 120.96 | 37.88 | 83.08 | 146.23 | 35.58 | 0.00 | 0.00 | 0.00 |
August | 141.73 | 63.76 | 77.98 | 179.14 | 39.86 | 0.00 | 0.00 | 0.00 |
September | 167.49 | 98.12 | 69.37 | 210.09 | 49.91 | 0.00 | 0.00 | 0.00 |
October | 115.07 | 67.26 | 47.82 | 132.46 | 58.02 | 0.00 | 0.00 | 0.00 |
November | 81.59 | 49.63 | 31.96 | 86.05 | 67.96 | 0.00 | 0.00 | 0.00 |
December | 64.67 | 41.43 | 23.23 | 65.55 | 84.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.24 | 53.25 | 59.00 | 128.53 | 55.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.67 | 20.54 | 23.23 | 64.32 | 35.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 167.49 | 98.12 | 84.61 | 210.09 | 84.10 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209331E+09 | 0.135509E+09 | 73822427.99 | 0.215690E+09 | 0.185672E+09 |
February | 0.230918E+09 | 0.140909E+09 | 90008705.79 | 0.244471E+09 | 0.161364E+09 |
March | 0.158065E+09 | 46021543.82 | 0.112044E+09 | 0.139597E+09 | 0.148887E+09 |
April | 0.317647E+09 | 0.143573E+09 | 0.174075E+09 | 0.376715E+09 | 0.123773E+09 |
May | 0.271481E+09 | 88385508.69 | 0.183096E+09 | 0.300765E+09 | 0.111911E+09 |
June | 0.242025E+09 | 58584113.08 | 0.183441E+09 | 0.272902E+09 | 88758308.03 |
July | 0.270970E+09 | 84857401.35 | 0.186113E+09 | 0.324603E+09 | 87107770.22 |
August | 0.317518E+09 | 0.142831E+09 | 0.174687E+09 | 0.399455E+09 | 95980742.12 |
September | 0.363119E+09 | 0.212721E+09 | 0.150398E+09 | 0.453195E+09 | 0.116852E+09 |
October | 0.257794E+09 | 0.150669E+09 | 0.107125E+09 | 0.293334E+09 | 0.144689E+09 |
November | 0.176880E+09 | 0.107600E+09 | 69279279.99 | 0.183437E+09 | 0.165554E+09 |
December | 0.144867E+09 | 92816685.57 | 52049860.74 | 0.144200E+09 | 0.210078E+09 |
Annual Sum or Average | 0.296062E+10 | 0.140448E+10 | 0.155614E+10 | 0.334836E+10 | 0.164063E+10 |
Minimum of Months | 0.144867E+09 | 46021543.82 | 52049860.74 | 0.139597E+09 | 87107770.22 |
Maximum of Months | 0.363119E+09 | 0.212721E+09 | 0.186113E+09 | 0.453195E+09 | 0.210078E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209331E+09 | 0.135509E+09 | 73822427.99 | 0.215690E+09 | 0.185672E+09 |
February | 0.230918E+09 | 0.140909E+09 | 90008705.79 | 0.244471E+09 | 0.161364E+09 |
March | 0.158065E+09 | 46021543.82 | 0.112044E+09 | 0.139597E+09 | 0.148887E+09 |
April | 0.317647E+09 | 0.143573E+09 | 0.174075E+09 | 0.376715E+09 | 0.123773E+09 |
May | 0.271481E+09 | 88385508.69 | 0.183096E+09 | 0.300765E+09 | 0.111911E+09 |
June | 0.242025E+09 | 58584113.08 | 0.183441E+09 | 0.272902E+09 | 88758308.03 |
July | 0.270970E+09 | 84857401.35 | 0.186113E+09 | 0.324603E+09 | 87107770.22 |
August | 0.317518E+09 | 0.142831E+09 | 0.174687E+09 | 0.399455E+09 | 95980742.12 |
September | 0.363119E+09 | 0.212721E+09 | 0.150398E+09 | 0.453195E+09 | 0.116852E+09 |
October | 0.257794E+09 | 0.150669E+09 | 0.107125E+09 | 0.293334E+09 | 0.144689E+09 |
November | 0.176880E+09 | 0.107600E+09 | 69279279.99 | 0.183437E+09 | 0.165554E+09 |
December | 0.144867E+09 | 92816685.57 | 52049860.74 | 0.144200E+09 | 0.210078E+09 |
Annual Sum or Average | 0.296062E+10 | 0.140448E+10 | 0.155614E+10 | 0.334836E+10 | 0.164063E+10 |
Minimum of Months | 0.144867E+09 | 46021543.82 | 52049860.74 | 0.139597E+09 | 87107770.22 |
Maximum of Months | 0.363119E+09 | 0.212721E+09 | 0.186113E+09 | 0.453195E+09 | 0.210078E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209331E+09 | 0.135509E+09 | 73822427.99 | 0.215690E+09 | 0.185672E+09 |
February | 0.230918E+09 | 0.140909E+09 | 90008705.79 | 0.244471E+09 | 0.161364E+09 |
March | 0.158065E+09 | 46021543.82 | 0.112044E+09 | 0.139597E+09 | 0.148887E+09 |
April | 0.317647E+09 | 0.143573E+09 | 0.174075E+09 | 0.376715E+09 | 0.123773E+09 |
May | 0.271481E+09 | 88385508.69 | 0.183096E+09 | 0.300765E+09 | 0.111911E+09 |
June | 0.242025E+09 | 58584113.08 | 0.183441E+09 | 0.272902E+09 | 88758308.03 |
July | 0.270970E+09 | 84857401.35 | 0.186113E+09 | 0.324603E+09 | 87107770.22 |
August | 0.317518E+09 | 0.142831E+09 | 0.174687E+09 | 0.399455E+09 | 95980742.12 |
September | 0.363119E+09 | 0.212721E+09 | 0.150398E+09 | 0.453195E+09 | 0.116852E+09 |
October | 0.257794E+09 | 0.150669E+09 | 0.107125E+09 | 0.293334E+09 | 0.144689E+09 |
November | 0.176880E+09 | 0.107600E+09 | 69279279.99 | 0.183437E+09 | 0.165554E+09 |
December | 0.144867E+09 | 92816685.57 | 52049860.74 | 0.144200E+09 | 0.210078E+09 |
Annual Sum or Average | 0.296062E+10 | 0.140448E+10 | 0.155614E+10 | 0.334836E+10 | 0.164063E+10 |
Minimum of Months | 0.144867E+09 | 46021543.82 | 52049860.74 | 0.139597E+09 | 87107770.22 |
Maximum of Months | 0.363119E+09 | 0.212721E+09 | 0.186113E+09 | 0.453195E+09 | 0.210078E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209331E+09 | 0.135509E+09 | 73822427.99 | 0.215690E+09 | 0.185672E+09 |
February | 0.230918E+09 | 0.140909E+09 | 90008705.79 | 0.244471E+09 | 0.161364E+09 |
March | 0.158065E+09 | 46021543.82 | 0.112044E+09 | 0.139597E+09 | 0.148887E+09 |
April | 0.317647E+09 | 0.143573E+09 | 0.174075E+09 | 0.376715E+09 | 0.123773E+09 |
May | 0.271481E+09 | 88385508.69 | 0.183096E+09 | 0.300765E+09 | 0.111911E+09 |
June | 0.242025E+09 | 58584113.08 | 0.183441E+09 | 0.272902E+09 | 88758308.03 |
July | 0.270970E+09 | 84857401.35 | 0.186113E+09 | 0.324603E+09 | 87107770.22 |
August | 0.317518E+09 | 0.142831E+09 | 0.174687E+09 | 0.399455E+09 | 95980742.12 |
September | 0.363119E+09 | 0.212721E+09 | 0.150398E+09 | 0.453195E+09 | 0.116852E+09 |
October | 0.257794E+09 | 0.150669E+09 | 0.107125E+09 | 0.293334E+09 | 0.144689E+09 |
November | 0.176880E+09 | 0.107600E+09 | 69279279.99 | 0.183437E+09 | 0.165554E+09 |
December | 0.144867E+09 | 92816685.57 | 52049860.74 | 0.144200E+09 | 0.210078E+09 |
Annual Sum or Average | 0.296062E+10 | 0.140448E+10 | 0.155614E+10 | 0.334836E+10 | 0.164063E+10 |
Minimum of Months | 0.144867E+09 | 46021543.82 | 52049860.74 | 0.139597E+09 | 87107770.22 |
Maximum of Months | 0.363119E+09 | 0.212721E+09 | 0.186113E+09 | 0.453195E+09 | 0.210078E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.251648E+09 | 0.162902E+09 | 88745923.47 | 0.259754E+09 | 0.221172E+09 |
February | 0.277599E+09 | 0.169395E+09 | 0.108204E+09 | 0.294413E+09 | 0.191956E+09 |
March | 0.190019E+09 | 55324980.73 | 0.134694E+09 | 0.168445E+09 | 0.177426E+09 |
April | 0.381861E+09 | 0.172597E+09 | 0.209264E+09 | 0.453173E+09 | 0.147565E+09 |
May | 0.326362E+09 | 0.106253E+09 | 0.220109E+09 | 0.362193E+09 | 0.133099E+09 |
June | 0.290951E+09 | 70427123.00 | 0.220524E+09 | 0.328530E+09 | 0.105637E+09 |
July | 0.325748E+09 | 0.102012E+09 | 0.223736E+09 | 0.390489E+09 | 0.103735E+09 |
August | 0.381705E+09 | 0.171705E+09 | 0.210000E+09 | 0.480267E+09 | 0.114509E+09 |
September | 0.436525E+09 | 0.255724E+09 | 0.180801E+09 | 0.544982E+09 | 0.139330E+09 |
October | 0.309908E+09 | 0.181127E+09 | 0.128781E+09 | 0.352923E+09 | 0.172355E+09 |
November | 0.212637E+09 | 0.129352E+09 | 83284360.16 | 0.220918E+09 | 0.197012E+09 |
December | 0.174152E+09 | 0.111580E+09 | 62571945.73 | 0.173751E+09 | 0.249606E+09 |
Annual Sum or Average | 0.355912E+10 | 0.168840E+10 | 0.187072E+10 | 0.402984E+10 | 0.195340E+10 |
Minimum of Months | 0.174152E+09 | 55324980.73 | 62571945.73 | 0.168445E+09 | 0.103735E+09 |
Maximum of Months | 0.436525E+09 | 0.255724E+09 | 0.223736E+09 | 0.544982E+09 | 0.249606E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.251648E+09 | 0.162902E+09 | 88745923.47 | 0.259754E+09 | 0.221172E+09 |
February | 0.277599E+09 | 0.169395E+09 | 0.108204E+09 | 0.294413E+09 | 0.191956E+09 |
March | 0.190019E+09 | 55324980.73 | 0.134694E+09 | 0.168445E+09 | 0.177426E+09 |
April | 0.381861E+09 | 0.172597E+09 | 0.209264E+09 | 0.453173E+09 | 0.147565E+09 |
May | 0.326362E+09 | 0.106253E+09 | 0.220109E+09 | 0.362193E+09 | 0.133099E+09 |
June | 0.290951E+09 | 70427123.00 | 0.220524E+09 | 0.328530E+09 | 0.105637E+09 |
July | 0.325748E+09 | 0.102012E+09 | 0.223736E+09 | 0.390489E+09 | 0.103735E+09 |
August | 0.381705E+09 | 0.171705E+09 | 0.210000E+09 | 0.480267E+09 | 0.114509E+09 |
September | 0.436525E+09 | 0.255724E+09 | 0.180801E+09 | 0.544982E+09 | 0.139330E+09 |
October | 0.309908E+09 | 0.181127E+09 | 0.128781E+09 | 0.352923E+09 | 0.172355E+09 |
November | 0.212637E+09 | 0.129352E+09 | 83284360.16 | 0.220918E+09 | 0.197012E+09 |
December | 0.174152E+09 | 0.111580E+09 | 62571945.73 | 0.173751E+09 | 0.249606E+09 |
Annual Sum or Average | 0.355912E+10 | 0.168840E+10 | 0.187072E+10 | 0.402984E+10 | 0.195340E+10 |
Minimum of Months | 0.174152E+09 | 55324980.73 | 62571945.73 | 0.168445E+09 | 0.103735E+09 |
Maximum of Months | 0.436525E+09 | 0.255724E+09 | 0.223736E+09 | 0.544982E+09 | 0.249606E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209331E+09 | 0.135509E+09 | 73822427.99 | 0.212975E+09 | 0.196635E+09 |
February | 0.230918E+09 | 0.140909E+09 | 90008705.79 | 0.241563E+09 | 0.171359E+09 |
March | 0.158065E+09 | 46021543.82 | 0.112044E+09 | 0.136268E+09 | 0.159445E+09 |
April | 0.317647E+09 | 0.143573E+09 | 0.174075E+09 | 0.370403E+09 | 0.134897E+09 |
May | 0.271481E+09 | 88385508.69 | 0.183096E+09 | 0.293730E+09 | 0.122586E+09 |
June | 0.242025E+09 | 58584113.08 | 0.183441E+09 | 0.267680E+09 | 94358617.97 |
July | 0.270970E+09 | 84857401.35 | 0.186113E+09 | 0.321385E+09 | 90665850.62 |
August | 0.317518E+09 | 0.142831E+09 | 0.174687E+09 | 0.397381E+09 | 98733124.68 |
September | 0.363119E+09 | 0.212721E+09 | 0.150398E+09 | 0.449750E+09 | 0.121995E+09 |
October | 0.257794E+09 | 0.150669E+09 | 0.107125E+09 | 0.288471E+09 | 0.158074E+09 |
November | 0.176880E+09 | 0.107600E+09 | 69279279.99 | 0.181096E+09 | 0.176757E+09 |
December | 0.144867E+09 | 92816685.57 | 52049860.74 | 0.142283E+09 | 0.222548E+09 |
Annual Sum or Average | 0.296062E+10 | 0.140448E+10 | 0.155614E+10 | 0.330299E+10 | 0.174805E+10 |
Minimum of Months | 0.144867E+09 | 46021543.82 | 52049860.74 | 0.136268E+09 | 90665850.62 |
Maximum of Months | 0.363119E+09 | 0.212721E+09 | 0.186113E+09 | 0.449750E+09 | 0.222548E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209331E+09 | 0.135509E+09 | 73822427.99 | 0.212975E+09 | 0.196635E+09 |
February | 0.230918E+09 | 0.140909E+09 | 90008705.79 | 0.241563E+09 | 0.171359E+09 |
March | 0.158065E+09 | 46021543.82 | 0.112044E+09 | 0.136268E+09 | 0.159445E+09 |
April | 0.317647E+09 | 0.143573E+09 | 0.174075E+09 | 0.370403E+09 | 0.134897E+09 |
May | 0.271481E+09 | 88385508.69 | 0.183096E+09 | 0.293730E+09 | 0.122586E+09 |
June | 0.242025E+09 | 58584113.08 | 0.183441E+09 | 0.267680E+09 | 94358617.97 |
July | 0.270970E+09 | 84857401.35 | 0.186113E+09 | 0.321385E+09 | 90665850.62 |
August | 0.317518E+09 | 0.142831E+09 | 0.174687E+09 | 0.397381E+09 | 98733124.68 |
September | 0.363119E+09 | 0.212721E+09 | 0.150398E+09 | 0.449750E+09 | 0.121995E+09 |
October | 0.257794E+09 | 0.150669E+09 | 0.107125E+09 | 0.288471E+09 | 0.158074E+09 |
November | 0.176880E+09 | 0.107600E+09 | 69279279.99 | 0.181096E+09 | 0.176757E+09 |
December | 0.144867E+09 | 92816685.57 | 52049860.74 | 0.142283E+09 | 0.222548E+09 |
Annual Sum or Average | 0.296062E+10 | 0.140448E+10 | 0.155614E+10 | 0.330299E+10 | 0.174805E+10 |
Minimum of Months | 0.144867E+09 | 46021543.82 | 52049860.74 | 0.136268E+09 | 90665850.62 |
Maximum of Months | 0.363119E+09 | 0.212721E+09 | 0.186113E+09 | 0.449750E+09 | 0.222548E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.251648E+09 | 0.162902E+09 | 88745923.47 | 0.256517E+09 | 0.234178E+09 |
February | 0.277599E+09 | 0.169395E+09 | 0.108204E+09 | 0.290951E+09 | 0.203755E+09 |
March | 0.190019E+09 | 55324980.73 | 0.134694E+09 | 0.164459E+09 | 0.189935E+09 |
April | 0.381861E+09 | 0.172597E+09 | 0.209264E+09 | 0.445712E+09 | 0.160713E+09 |
May | 0.326362E+09 | 0.106253E+09 | 0.220109E+09 | 0.353885E+09 | 0.145625E+09 |
June | 0.290951E+09 | 70427123.00 | 0.220524E+09 | 0.322380E+09 | 0.112215E+09 |
July | 0.325748E+09 | 0.102012E+09 | 0.223736E+09 | 0.386718E+09 | 0.107903E+09 |
August | 0.381705E+09 | 0.171705E+09 | 0.210000E+09 | 0.477851E+09 | 0.117742E+09 |
September | 0.436525E+09 | 0.255724E+09 | 0.180801E+09 | 0.540953E+09 | 0.145387E+09 |
October | 0.309908E+09 | 0.181127E+09 | 0.128781E+09 | 0.347169E+09 | 0.188147E+09 |
November | 0.212637E+09 | 0.129352E+09 | 83284360.16 | 0.218144E+09 | 0.210233E+09 |
December | 0.174152E+09 | 0.111580E+09 | 62571945.73 | 0.171474E+09 | 0.264342E+09 |
Annual Sum or Average | 0.355912E+10 | 0.168840E+10 | 0.187072E+10 | 0.397621E+10 | 0.208017E+10 |
Minimum of Months | 0.174152E+09 | 55324980.73 | 62571945.73 | 0.164459E+09 | 0.107903E+09 |
Maximum of Months | 0.436525E+09 | 0.255724E+09 | 0.223736E+09 | 0.540953E+09 | 0.264342E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209331E+09 | 0.135509E+09 | 73822427.99 | 0.213572E+09 | 0.191178E+09 |
February | 0.230918E+09 | 0.140909E+09 | 90008705.79 | 0.242094E+09 | 0.166729E+09 |
March | 0.158065E+09 | 46021543.82 | 0.112044E+09 | 0.136872E+09 | 0.154709E+09 |
April | 0.317647E+09 | 0.143573E+09 | 0.174075E+09 | 0.371517E+09 | 0.131921E+09 |
May | 0.271481E+09 | 88385508.69 | 0.183096E+09 | 0.294872E+09 | 0.120136E+09 |
June | 0.242025E+09 | 58584113.08 | 0.183441E+09 | 0.267641E+09 | 95333313.64 |
July | 0.270970E+09 | 84857401.35 | 0.186113E+09 | 0.321010E+09 | 92581701.60 |
August | 0.317518E+09 | 0.142831E+09 | 0.174687E+09 | 0.397176E+09 | 0.101065E+09 |
September | 0.363119E+09 | 0.212721E+09 | 0.150398E+09 | 0.449813E+09 | 0.123408E+09 |
October | 0.257794E+09 | 0.150669E+09 | 0.107125E+09 | 0.289312E+09 | 0.154094E+09 |
November | 0.176880E+09 | 0.107600E+09 | 69279279.99 | 0.181714E+09 | 0.171099E+09 |
December | 0.144867E+09 | 92816685.57 | 52049860.74 | 0.142674E+09 | 0.216799E+09 |
Annual Sum or Average | 0.296062E+10 | 0.140448E+10 | 0.155614E+10 | 0.330827E+10 | 0.171905E+10 |
Minimum of Months | 0.144867E+09 | 46021543.82 | 52049860.74 | 0.136872E+09 | 92581701.60 |
Maximum of Months | 0.363119E+09 | 0.212721E+09 | 0.186113E+09 | 0.449813E+09 | 0.216799E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209331E+09 | 0.135509E+09 | 73822427.99 | 0.213572E+09 | 0.191178E+09 |
February | 0.230918E+09 | 0.140909E+09 | 90008705.79 | 0.242094E+09 | 0.166729E+09 |
March | 0.158065E+09 | 46021543.82 | 0.112044E+09 | 0.136872E+09 | 0.154709E+09 |
April | 0.317647E+09 | 0.143573E+09 | 0.174075E+09 | 0.371517E+09 | 0.131921E+09 |
May | 0.271481E+09 | 88385508.69 | 0.183096E+09 | 0.294872E+09 | 0.120136E+09 |
June | 0.242025E+09 | 58584113.08 | 0.183441E+09 | 0.267641E+09 | 95333313.64 |
July | 0.270970E+09 | 84857401.35 | 0.186113E+09 | 0.321010E+09 | 92581701.60 |
August | 0.317518E+09 | 0.142831E+09 | 0.174687E+09 | 0.397176E+09 | 0.101065E+09 |
September | 0.363119E+09 | 0.212721E+09 | 0.150398E+09 | 0.449813E+09 | 0.123408E+09 |
October | 0.257794E+09 | 0.150669E+09 | 0.107125E+09 | 0.289312E+09 | 0.154094E+09 |
November | 0.176880E+09 | 0.107600E+09 | 69279279.99 | 0.181714E+09 | 0.171099E+09 |
December | 0.144867E+09 | 92816685.57 | 52049860.74 | 0.142674E+09 | 0.216799E+09 |
Annual Sum or Average | 0.296062E+10 | 0.140448E+10 | 0.155614E+10 | 0.330827E+10 | 0.171905E+10 |
Minimum of Months | 0.144867E+09 | 46021543.82 | 52049860.74 | 0.136872E+09 | 92581701.60 |
Maximum of Months | 0.363119E+09 | 0.212721E+09 | 0.186113E+09 | 0.449813E+09 | 0.216799E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.250273E+09 | 0.162012E+09 | 88260973.07 | 0.255842E+09 | 0.226454E+09 |
February | 0.276082E+09 | 0.168469E+09 | 0.107613E+09 | 0.290010E+09 | 0.197196E+09 |
March | 0.188981E+09 | 55022658.43 | 0.133958E+09 | 0.164296E+09 | 0.183312E+09 |
April | 0.379775E+09 | 0.171654E+09 | 0.208121E+09 | 0.444600E+09 | 0.156318E+09 |
May | 0.324579E+09 | 0.105672E+09 | 0.218907E+09 | 0.353302E+09 | 0.141954E+09 |
June | 0.289361E+09 | 70042275.33 | 0.219319E+09 | 0.320572E+09 | 0.112719E+09 |
July | 0.323968E+09 | 0.101454E+09 | 0.222514E+09 | 0.384162E+09 | 0.109526E+09 |
August | 0.379619E+09 | 0.170767E+09 | 0.208853E+09 | 0.474995E+09 | 0.119796E+09 |
September | 0.434140E+09 | 0.254326E+09 | 0.179813E+09 | 0.538068E+09 | 0.146218E+09 |
October | 0.308214E+09 | 0.180137E+09 | 0.128077E+09 | 0.346271E+09 | 0.182442E+09 |
November | 0.211475E+09 | 0.128645E+09 | 82829254.37 | 0.217696E+09 | 0.202434E+09 |
December | 0.173200E+09 | 0.110970E+09 | 62230022.53 | 0.171015E+09 | 0.256142E+09 |
Annual Sum or Average | 0.353967E+10 | 0.167917E+10 | 0.186049E+10 | 0.396083E+10 | 0.203451E+10 |
Minimum of Months | 0.173200E+09 | 55022658.43 | 62230022.53 | 0.164296E+09 | 0.109526E+09 |
Maximum of Months | 0.434140E+09 | 0.254326E+09 | 0.222514E+09 | 0.538068E+09 | 0.256142E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209331E+09 | 0.135509E+09 | 73822427.99 | 0.214001E+09 | 0.188691E+09 |
February | 0.230918E+09 | 0.140909E+09 | 90008705.79 | 0.242496E+09 | 0.164708E+09 |
March | 0.158065E+09 | 46021543.82 | 0.112044E+09 | 0.137339E+09 | 0.152621E+09 |
April | 0.317647E+09 | 0.143573E+09 | 0.174075E+09 | 0.372482E+09 | 0.129760E+09 |
May | 0.271481E+09 | 88385508.69 | 0.183096E+09 | 0.295897E+09 | 0.118172E+09 |
June | 0.242025E+09 | 58584113.08 | 0.183441E+09 | 0.268132E+09 | 94466642.40 |
July | 0.270970E+09 | 84857401.35 | 0.186113E+09 | 0.321263E+09 | 92041274.29 |
August | 0.317518E+09 | 0.142831E+09 | 0.174687E+09 | 0.397294E+09 | 0.100693E+09 |
September | 0.363119E+09 | 0.212721E+09 | 0.150398E+09 | 0.450042E+09 | 0.122685E+09 |
October | 0.257794E+09 | 0.150669E+09 | 0.107125E+09 | 0.289937E+09 | 0.151671E+09 |
November | 0.176880E+09 | 0.107600E+09 | 69279279.99 | 0.182078E+09 | 0.168717E+09 |
December | 0.144867E+09 | 92816685.57 | 52049860.74 | 0.142962E+09 | 0.214178E+09 |
Annual Sum or Average | 0.296062E+10 | 0.140448E+10 | 0.155614E+10 | 0.331392E+10 | 0.169840E+10 |
Minimum of Months | 0.144867E+09 | 46021543.82 | 52049860.74 | 0.137339E+09 | 92041274.29 |
Maximum of Months | 0.363119E+09 | 0.212721E+09 | 0.186113E+09 | 0.450042E+09 | 0.214178E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209331E+09 | 0.135509E+09 | 73822427.99 | 0.214001E+09 | 0.188691E+09 |
February | 0.230918E+09 | 0.140909E+09 | 90008705.79 | 0.242496E+09 | 0.164708E+09 |
March | 0.158065E+09 | 46021543.82 | 0.112044E+09 | 0.137339E+09 | 0.152621E+09 |
April | 0.317647E+09 | 0.143573E+09 | 0.174075E+09 | 0.372482E+09 | 0.129760E+09 |
May | 0.271481E+09 | 88385508.69 | 0.183096E+09 | 0.295897E+09 | 0.118172E+09 |
June | 0.242025E+09 | 58584113.08 | 0.183441E+09 | 0.268132E+09 | 94466642.40 |
July | 0.270970E+09 | 84857401.35 | 0.186113E+09 | 0.321263E+09 | 92041274.29 |
August | 0.317518E+09 | 0.142831E+09 | 0.174687E+09 | 0.397294E+09 | 0.100693E+09 |
September | 0.363119E+09 | 0.212721E+09 | 0.150398E+09 | 0.450042E+09 | 0.122685E+09 |
October | 0.257794E+09 | 0.150669E+09 | 0.107125E+09 | 0.289937E+09 | 0.151671E+09 |
November | 0.176880E+09 | 0.107600E+09 | 69279279.99 | 0.182078E+09 | 0.168717E+09 |
December | 0.144867E+09 | 92816685.57 | 52049860.74 | 0.142962E+09 | 0.214178E+09 |
Annual Sum or Average | 0.296062E+10 | 0.140448E+10 | 0.155614E+10 | 0.331392E+10 | 0.169840E+10 |
Minimum of Months | 0.144867E+09 | 46021543.82 | 52049860.74 | 0.137339E+09 | 92041274.29 |
Maximum of Months | 0.363119E+09 | 0.212721E+09 | 0.186113E+09 | 0.450042E+09 | 0.214178E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.250273E+09 | 0.162012E+09 | 88260973.07 | 0.256362E+09 | 0.223497E+09 |
February | 0.276082E+09 | 0.168469E+09 | 0.107613E+09 | 0.290497E+09 | 0.194798E+09 |
March | 0.188981E+09 | 55022658.43 | 0.133958E+09 | 0.164863E+09 | 0.180831E+09 |
April | 0.379775E+09 | 0.171654E+09 | 0.208121E+09 | 0.445752E+09 | 0.153756E+09 |
May | 0.324579E+09 | 0.105672E+09 | 0.218907E+09 | 0.354525E+09 | 0.139637E+09 |
June | 0.289361E+09 | 70042275.33 | 0.219319E+09 | 0.321159E+09 | 0.111696E+09 |
July | 0.323968E+09 | 0.101454E+09 | 0.222514E+09 | 0.384466E+09 | 0.108889E+09 |
August | 0.379619E+09 | 0.170767E+09 | 0.208853E+09 | 0.475139E+09 | 0.119356E+09 |
September | 0.434140E+09 | 0.254326E+09 | 0.179813E+09 | 0.538344E+09 | 0.145363E+09 |
October | 0.308214E+09 | 0.180137E+09 | 0.128077E+09 | 0.347017E+09 | 0.179571E+09 |
November | 0.211475E+09 | 0.128645E+09 | 82829254.37 | 0.218134E+09 | 0.199607E+09 |
December | 0.173200E+09 | 0.110970E+09 | 62230022.53 | 0.171363E+09 | 0.253034E+09 |
Annual Sum or Average | 0.353967E+10 | 0.167917E+10 | 0.186049E+10 | 0.396762E+10 | 0.201004E+10 |
Minimum of Months | 0.173200E+09 | 55022658.43 | 62230022.53 | 0.164863E+09 | 0.108889E+09 |
Maximum of Months | 0.434140E+09 | 0.254326E+09 | 0.222514E+09 | 0.538344E+09 | 0.253034E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209331E+09 | 0.135509E+09 | 73822427.99 | 0.214427E+09 | 0.186816E+09 |
February | 0.230918E+09 | 0.140909E+09 | 90008705.79 | 0.242919E+09 | 0.163163E+09 |
March | 0.158065E+09 | 46021543.82 | 0.112044E+09 | 0.137854E+09 | 0.151010E+09 |
April | 0.317647E+09 | 0.143573E+09 | 0.174075E+09 | 0.373674E+09 | 0.127691E+09 |
May | 0.271481E+09 | 88385508.69 | 0.183096E+09 | 0.297235E+09 | 0.116164E+09 |
June | 0.242025E+09 | 58584113.08 | 0.183441E+09 | 0.269225E+09 | 93035931.34 |
July | 0.270970E+09 | 84857401.35 | 0.186113E+09 | 0.321897E+09 | 91029773.18 |
August | 0.317518E+09 | 0.142831E+09 | 0.174687E+09 | 0.397622E+09 | 99930565.79 |
September | 0.363119E+09 | 0.212721E+09 | 0.150398E+09 | 0.450560E+09 | 0.121553E+09 |
October | 0.257794E+09 | 0.150669E+09 | 0.107125E+09 | 0.290761E+09 | 0.149349E+09 |
November | 0.176880E+09 | 0.107600E+09 | 69279279.99 | 0.182429E+09 | 0.166992E+09 |
December | 0.144867E+09 | 92816685.57 | 52049860.74 | 0.143277E+09 | 0.212036E+09 |
Annual Sum or Average | 0.296062E+10 | 0.140448E+10 | 0.155614E+10 | 0.332188E+10 | 0.167877E+10 |
Minimum of Months | 0.144867E+09 | 46021543.82 | 52049860.74 | 0.137854E+09 | 91029773.18 |
Maximum of Months | 0.363119E+09 | 0.212721E+09 | 0.186113E+09 | 0.450560E+09 | 0.212036E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209331E+09 | 0.135509E+09 | 73822427.99 | 0.214427E+09 | 0.186816E+09 |
February | 0.230918E+09 | 0.140909E+09 | 90008705.79 | 0.242919E+09 | 0.163163E+09 |
March | 0.158065E+09 | 46021543.82 | 0.112044E+09 | 0.137854E+09 | 0.151010E+09 |
April | 0.317647E+09 | 0.143573E+09 | 0.174075E+09 | 0.373674E+09 | 0.127691E+09 |
May | 0.271481E+09 | 88385508.69 | 0.183096E+09 | 0.297235E+09 | 0.116164E+09 |
June | 0.242025E+09 | 58584113.08 | 0.183441E+09 | 0.269225E+09 | 93035931.34 |
July | 0.270970E+09 | 84857401.35 | 0.186113E+09 | 0.321897E+09 | 91029773.18 |
August | 0.317518E+09 | 0.142831E+09 | 0.174687E+09 | 0.397622E+09 | 99930565.79 |
September | 0.363119E+09 | 0.212721E+09 | 0.150398E+09 | 0.450560E+09 | 0.121553E+09 |
October | 0.257794E+09 | 0.150669E+09 | 0.107125E+09 | 0.290761E+09 | 0.149349E+09 |
November | 0.176880E+09 | 0.107600E+09 | 69279279.99 | 0.182429E+09 | 0.166992E+09 |
December | 0.144867E+09 | 92816685.57 | 52049860.74 | 0.143277E+09 | 0.212036E+09 |
Annual Sum or Average | 0.296062E+10 | 0.140448E+10 | 0.155614E+10 | 0.332188E+10 | 0.167877E+10 |
Minimum of Months | 0.144867E+09 | 46021543.82 | 52049860.74 | 0.137854E+09 | 91029773.18 |
Maximum of Months | 0.363119E+09 | 0.212721E+09 | 0.186113E+09 | 0.450560E+09 | 0.212036E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.250273E+09 | 0.162012E+09 | 88260973.07 | 0.256878E+09 | 0.221268E+09 |
February | 0.276082E+09 | 0.168469E+09 | 0.107613E+09 | 0.291012E+09 | 0.192969E+09 |
March | 0.188981E+09 | 55022658.43 | 0.133958E+09 | 0.165486E+09 | 0.178920E+09 |
April | 0.379775E+09 | 0.171654E+09 | 0.208121E+09 | 0.447174E+09 | 0.151309E+09 |
May | 0.324579E+09 | 0.105672E+09 | 0.218907E+09 | 0.356123E+09 | 0.137276E+09 |
June | 0.289361E+09 | 70042275.33 | 0.219319E+09 | 0.322463E+09 | 0.110013E+09 |
July | 0.323968E+09 | 0.101454E+09 | 0.222514E+09 | 0.385228E+09 | 0.107703E+09 |
August | 0.379619E+09 | 0.170767E+09 | 0.208853E+09 | 0.475536E+09 | 0.118463E+09 |
September | 0.434140E+09 | 0.254326E+09 | 0.179813E+09 | 0.538964E+09 | 0.144030E+09 |
October | 0.308214E+09 | 0.180137E+09 | 0.128077E+09 | 0.348002E+09 | 0.176826E+09 |
November | 0.211475E+09 | 0.128645E+09 | 82829254.37 | 0.218558E+09 | 0.197562E+09 |
December | 0.173200E+09 | 0.110970E+09 | 62230022.53 | 0.171743E+09 | 0.250492E+09 |
Annual Sum or Average | 0.353967E+10 | 0.167917E+10 | 0.186049E+10 | 0.397717E+10 | 0.198683E+10 |
Minimum of Months | 0.173200E+09 | 55022658.43 | 62230022.53 | 0.165486E+09 | 0.107703E+09 |
Maximum of Months | 0.434140E+09 | 0.254326E+09 | 0.222514E+09 | 0.538964E+09 | 0.250492E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209331E+09 | 0.135509E+09 | 73822427.99 | 0.216146E+09 | 0.182385E+09 |
February | 0.230918E+09 | 0.140909E+09 | 90008705.79 | 0.244655E+09 | 0.159294E+09 |
March | 0.158065E+09 | 46021543.82 | 0.112044E+09 | 0.139752E+09 | 0.147265E+09 |
April | 0.317647E+09 | 0.143573E+09 | 0.174075E+09 | 0.376406E+09 | 0.123816E+09 |
May | 0.271481E+09 | 88385508.69 | 0.183096E+09 | 0.300388E+09 | 0.112275E+09 |
June | 0.242025E+09 | 58584113.08 | 0.183441E+09 | 0.272306E+09 | 89616251.56 |
July | 0.270970E+09 | 84857401.35 | 0.186113E+09 | 0.323729E+09 | 88551899.81 |
August | 0.317518E+09 | 0.142831E+09 | 0.174687E+09 | 0.398617E+09 | 97917437.51 |
September | 0.363119E+09 | 0.212721E+09 | 0.150398E+09 | 0.452334E+09 | 0.118628E+09 |
October | 0.257794E+09 | 0.150669E+09 | 0.107125E+09 | 0.292994E+09 | 0.144654E+09 |
November | 0.176880E+09 | 0.107600E+09 | 69279279.99 | 0.183716E+09 | 0.162945E+09 |
December | 0.144867E+09 | 92816685.57 | 52049860.74 | 0.144592E+09 | 0.206272E+09 |
Annual Sum or Average | 0.296062E+10 | 0.140448E+10 | 0.155614E+10 | 0.334563E+10 | 0.163362E+10 |
Minimum of Months | 0.144867E+09 | 46021543.82 | 52049860.74 | 0.139752E+09 | 88551899.81 |
Maximum of Months | 0.363119E+09 | 0.212721E+09 | 0.186113E+09 | 0.452334E+09 | 0.206272E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209331E+09 | 0.135509E+09 | 73822427.99 | 0.216146E+09 | 0.182385E+09 |
February | 0.230918E+09 | 0.140909E+09 | 90008705.79 | 0.244655E+09 | 0.159294E+09 |
March | 0.158065E+09 | 46021543.82 | 0.112044E+09 | 0.139752E+09 | 0.147265E+09 |
April | 0.317647E+09 | 0.143573E+09 | 0.174075E+09 | 0.376406E+09 | 0.123816E+09 |
May | 0.271481E+09 | 88385508.69 | 0.183096E+09 | 0.300388E+09 | 0.112275E+09 |
June | 0.242025E+09 | 58584113.08 | 0.183441E+09 | 0.272306E+09 | 89616251.56 |
July | 0.270970E+09 | 84857401.35 | 0.186113E+09 | 0.323729E+09 | 88551899.81 |
August | 0.317518E+09 | 0.142831E+09 | 0.174687E+09 | 0.398617E+09 | 97917437.51 |
September | 0.363119E+09 | 0.212721E+09 | 0.150398E+09 | 0.452334E+09 | 0.118628E+09 |
October | 0.257794E+09 | 0.150669E+09 | 0.107125E+09 | 0.292994E+09 | 0.144654E+09 |
November | 0.176880E+09 | 0.107600E+09 | 69279279.99 | 0.183716E+09 | 0.162945E+09 |
December | 0.144867E+09 | 92816685.57 | 52049860.74 | 0.144592E+09 | 0.206272E+09 |
Annual Sum or Average | 0.296062E+10 | 0.140448E+10 | 0.155614E+10 | 0.334563E+10 | 0.163362E+10 |
Minimum of Months | 0.144867E+09 | 46021543.82 | 52049860.74 | 0.139752E+09 | 88551899.81 |
Maximum of Months | 0.363119E+09 | 0.212721E+09 | 0.186113E+09 | 0.452334E+09 | 0.206272E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209331E+09 | 0.135509E+09 | 73822427.99 | 0.216146E+09 | 0.182385E+09 |
February | 0.230918E+09 | 0.140909E+09 | 90008705.79 | 0.244655E+09 | 0.159294E+09 |
March | 0.158065E+09 | 46021543.82 | 0.112044E+09 | 0.139752E+09 | 0.147265E+09 |
April | 0.317647E+09 | 0.143573E+09 | 0.174075E+09 | 0.376406E+09 | 0.123816E+09 |
May | 0.271481E+09 | 88385508.69 | 0.183096E+09 | 0.300388E+09 | 0.112275E+09 |
June | 0.242025E+09 | 58584113.08 | 0.183441E+09 | 0.272306E+09 | 89616251.56 |
July | 0.270970E+09 | 84857401.35 | 0.186113E+09 | 0.323729E+09 | 88551899.81 |
August | 0.317518E+09 | 0.142831E+09 | 0.174687E+09 | 0.398617E+09 | 97917437.51 |
September | 0.363119E+09 | 0.212721E+09 | 0.150398E+09 | 0.452334E+09 | 0.118628E+09 |
October | 0.257794E+09 | 0.150669E+09 | 0.107125E+09 | 0.292994E+09 | 0.144654E+09 |
November | 0.176880E+09 | 0.107600E+09 | 69279279.99 | 0.183716E+09 | 0.162945E+09 |
December | 0.144867E+09 | 92816685.57 | 52049860.74 | 0.144592E+09 | 0.206272E+09 |
Annual Sum or Average | 0.296062E+10 | 0.140448E+10 | 0.155614E+10 | 0.334563E+10 | 0.163362E+10 |
Minimum of Months | 0.144867E+09 | 46021543.82 | 52049860.74 | 0.139752E+09 | 88551899.81 |
Maximum of Months | 0.363119E+09 | 0.212721E+09 | 0.186113E+09 | 0.452334E+09 | 0.206272E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209331E+09 | 0.135509E+09 | 73822427.99 | 0.216146E+09 | 0.182385E+09 |
February | 0.230918E+09 | 0.140909E+09 | 90008705.79 | 0.244655E+09 | 0.159294E+09 |
March | 0.158065E+09 | 46021543.82 | 0.112044E+09 | 0.139752E+09 | 0.147265E+09 |
April | 0.317647E+09 | 0.143573E+09 | 0.174075E+09 | 0.376406E+09 | 0.123816E+09 |
May | 0.271481E+09 | 88385508.69 | 0.183096E+09 | 0.300388E+09 | 0.112275E+09 |
June | 0.242025E+09 | 58584113.08 | 0.183441E+09 | 0.272306E+09 | 89616251.56 |
July | 0.270970E+09 | 84857401.35 | 0.186113E+09 | 0.323729E+09 | 88551899.81 |
August | 0.317518E+09 | 0.142831E+09 | 0.174687E+09 | 0.398617E+09 | 97917437.51 |
September | 0.363119E+09 | 0.212721E+09 | 0.150398E+09 | 0.452334E+09 | 0.118628E+09 |
October | 0.257794E+09 | 0.150669E+09 | 0.107125E+09 | 0.292994E+09 | 0.144654E+09 |
November | 0.176880E+09 | 0.107600E+09 | 69279279.99 | 0.183716E+09 | 0.162945E+09 |
December | 0.144867E+09 | 92816685.57 | 52049860.74 | 0.144592E+09 | 0.206272E+09 |
Annual Sum or Average | 0.296062E+10 | 0.140448E+10 | 0.155614E+10 | 0.334563E+10 | 0.163362E+10 |
Minimum of Months | 0.144867E+09 | 46021543.82 | 52049860.74 | 0.139752E+09 | 88551899.81 |
Maximum of Months | 0.363119E+09 | 0.212721E+09 | 0.186113E+09 | 0.452334E+09 | 0.206272E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.250273E+09 | 0.162012E+09 | 88260973.07 | 0.258892E+09 | 0.216046E+09 |
February | 0.276082E+09 | 0.168469E+09 | 0.107613E+09 | 0.293033E+09 | 0.188442E+09 |
March | 0.188981E+09 | 55022658.43 | 0.133958E+09 | 0.167723E+09 | 0.174507E+09 |
April | 0.379775E+09 | 0.171654E+09 | 0.208121E+09 | 0.450346E+09 | 0.146757E+09 |
May | 0.324579E+09 | 0.105672E+09 | 0.218907E+09 | 0.359780E+09 | 0.132753E+09 |
June | 0.289361E+09 | 70042275.33 | 0.219319E+09 | 0.326044E+09 | 0.106025E+09 |
July | 0.323968E+09 | 0.101454E+09 | 0.222514E+09 | 0.387337E+09 | 0.104822E+09 |
August | 0.379619E+09 | 0.170767E+09 | 0.208853E+09 | 0.476660E+09 | 0.116120E+09 |
September | 0.434140E+09 | 0.254326E+09 | 0.179813E+09 | 0.540997E+09 | 0.140618E+09 |
October | 0.308214E+09 | 0.180137E+09 | 0.128077E+09 | 0.350604E+09 | 0.171323E+09 |
November | 0.211475E+09 | 0.128645E+09 | 82829254.37 | 0.220054E+09 | 0.192812E+09 |
December | 0.173200E+09 | 0.110970E+09 | 62230022.53 | 0.173274E+09 | 0.243745E+09 |
Annual Sum or Average | 0.353967E+10 | 0.167917E+10 | 0.186049E+10 | 0.400475E+10 | 0.193397E+10 |
Minimum of Months | 0.173200E+09 | 55022658.43 | 62230022.53 | 0.167723E+09 | 0.104822E+09 |
Maximum of Months | 0.434140E+09 | 0.254326E+09 | 0.222514E+09 | 0.540997E+09 | 0.243745E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.250273E+09 | 0.162012E+09 | 88260973.07 | 0.258892E+09 | 0.216046E+09 |
February | 0.276082E+09 | 0.168469E+09 | 0.107613E+09 | 0.293033E+09 | 0.188442E+09 |
March | 0.188981E+09 | 55022658.43 | 0.133958E+09 | 0.167723E+09 | 0.174507E+09 |
April | 0.379775E+09 | 0.171654E+09 | 0.208121E+09 | 0.450346E+09 | 0.146757E+09 |
May | 0.324579E+09 | 0.105672E+09 | 0.218907E+09 | 0.359780E+09 | 0.132753E+09 |
June | 0.289361E+09 | 70042275.33 | 0.219319E+09 | 0.326044E+09 | 0.106025E+09 |
July | 0.323968E+09 | 0.101454E+09 | 0.222514E+09 | 0.387337E+09 | 0.104822E+09 |
August | 0.379619E+09 | 0.170767E+09 | 0.208853E+09 | 0.476660E+09 | 0.116120E+09 |
September | 0.434140E+09 | 0.254326E+09 | 0.179813E+09 | 0.540997E+09 | 0.140618E+09 |
October | 0.308214E+09 | 0.180137E+09 | 0.128077E+09 | 0.350604E+09 | 0.171323E+09 |
November | 0.211475E+09 | 0.128645E+09 | 82829254.37 | 0.220054E+09 | 0.192812E+09 |
December | 0.173200E+09 | 0.110970E+09 | 62230022.53 | 0.173274E+09 | 0.243745E+09 |
Annual Sum or Average | 0.353967E+10 | 0.167917E+10 | 0.186049E+10 | 0.400475E+10 | 0.193397E+10 |
Minimum of Months | 0.173200E+09 | 55022658.43 | 62230022.53 | 0.167723E+09 | 0.104822E+09 |
Maximum of Months | 0.434140E+09 | 0.254326E+09 | 0.222514E+09 | 0.540997E+09 | 0.243745E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209331E+09 | 0.135509E+09 | 73822427.99 | 0.215602E+09 | 0.183045E+09 |
February | 0.230918E+09 | 0.140909E+09 | 90008705.79 | 0.244066E+09 | 0.159913E+09 |
March | 0.158065E+09 | 46021543.82 | 0.112044E+09 | 0.139156E+09 | 0.147678E+09 |
April | 0.317647E+09 | 0.143573E+09 | 0.174075E+09 | 0.375059E+09 | 0.124554E+09 |
May | 0.271481E+09 | 88385508.69 | 0.183096E+09 | 0.298710E+09 | 0.113262E+09 |
June | 0.242025E+09 | 58584113.08 | 0.183441E+09 | 0.270547E+09 | 90602408.07 |
July | 0.270970E+09 | 84857401.35 | 0.186113E+09 | 0.322669E+09 | 88889386.82 |
August | 0.317518E+09 | 0.142831E+09 | 0.174687E+09 | 0.398007E+09 | 97868114.85 |
September | 0.363119E+09 | 0.212721E+09 | 0.150398E+09 | 0.451050E+09 | 0.119450E+09 |
October | 0.257794E+09 | 0.150669E+09 | 0.107125E+09 | 0.291725E+09 | 0.145921E+09 |
November | 0.176880E+09 | 0.107600E+09 | 69279279.99 | 0.183246E+09 | 0.163594E+09 |
December | 0.144867E+09 | 92816685.57 | 52049860.74 | 0.144177E+09 | 0.207587E+09 |
Annual Sum or Average | 0.296062E+10 | 0.140448E+10 | 0.155614E+10 | 0.333401E+10 | 0.164236E+10 |
Minimum of Months | 0.144867E+09 | 46021543.82 | 52049860.74 | 0.139156E+09 | 88889386.82 |
Maximum of Months | 0.363119E+09 | 0.212721E+09 | 0.186113E+09 | 0.451050E+09 | 0.207587E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209331E+09 | 0.135509E+09 | 73822427.99 | 0.215602E+09 | 0.183045E+09 |
February | 0.230918E+09 | 0.140909E+09 | 90008705.79 | 0.244066E+09 | 0.159913E+09 |
March | 0.158065E+09 | 46021543.82 | 0.112044E+09 | 0.139156E+09 | 0.147678E+09 |
April | 0.317647E+09 | 0.143573E+09 | 0.174075E+09 | 0.375059E+09 | 0.124554E+09 |
May | 0.271481E+09 | 88385508.69 | 0.183096E+09 | 0.298710E+09 | 0.113262E+09 |
June | 0.242025E+09 | 58584113.08 | 0.183441E+09 | 0.270547E+09 | 90602408.07 |
July | 0.270970E+09 | 84857401.35 | 0.186113E+09 | 0.322669E+09 | 88889386.82 |
August | 0.317518E+09 | 0.142831E+09 | 0.174687E+09 | 0.398007E+09 | 97868114.85 |
September | 0.363119E+09 | 0.212721E+09 | 0.150398E+09 | 0.451050E+09 | 0.119450E+09 |
October | 0.257794E+09 | 0.150669E+09 | 0.107125E+09 | 0.291725E+09 | 0.145921E+09 |
November | 0.176880E+09 | 0.107600E+09 | 69279279.99 | 0.183246E+09 | 0.163594E+09 |
December | 0.144867E+09 | 92816685.57 | 52049860.74 | 0.144177E+09 | 0.207587E+09 |
Annual Sum or Average | 0.296062E+10 | 0.140448E+10 | 0.155614E+10 | 0.333401E+10 | 0.164236E+10 |
Minimum of Months | 0.144867E+09 | 46021543.82 | 52049860.74 | 0.139156E+09 | 88889386.82 |
Maximum of Months | 0.363119E+09 | 0.212721E+09 | 0.186113E+09 | 0.451050E+09 | 0.207587E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.250273E+09 | 0.162012E+09 | 88260973.07 | 0.258296E+09 | 0.216775E+09 |
February | 0.276082E+09 | 0.168469E+09 | 0.107613E+09 | 0.292396E+09 | 0.189106E+09 |
March | 0.188981E+09 | 55022658.43 | 0.133958E+09 | 0.167067E+09 | 0.174957E+09 |
April | 0.379775E+09 | 0.171654E+09 | 0.208121E+09 | 0.448851E+09 | 0.147590E+09 |
May | 0.324579E+09 | 0.105672E+09 | 0.218907E+09 | 0.357905E+09 | 0.133853E+09 |
June | 0.289361E+09 | 70042275.33 | 0.219319E+09 | 0.324063E+09 | 0.107142E+09 |
July | 0.323968E+09 | 0.101454E+09 | 0.222514E+09 | 0.386178E+09 | 0.105181E+09 |
August | 0.379619E+09 | 0.170767E+09 | 0.208853E+09 | 0.476029E+09 | 0.116034E+09 |
September | 0.434140E+09 | 0.254326E+09 | 0.179813E+09 | 0.539578E+09 | 0.141545E+09 |
October | 0.308214E+09 | 0.180137E+09 | 0.128077E+09 | 0.349174E+09 | 0.172760E+09 |
November | 0.211475E+09 | 0.128645E+09 | 82829254.37 | 0.219544E+09 | 0.193515E+09 |
December | 0.173200E+09 | 0.110970E+09 | 62230022.53 | 0.172820E+09 | 0.245203E+09 |
Annual Sum or Average | 0.353967E+10 | 0.167917E+10 | 0.186049E+10 | 0.399190E+10 | 0.194366E+10 |
Minimum of Months | 0.173200E+09 | 55022658.43 | 62230022.53 | 0.167067E+09 | 0.105181E+09 |
Maximum of Months | 0.434140E+09 | 0.254326E+09 | 0.222514E+09 | 0.539578E+09 | 0.245203E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209331E+09 | 0.135509E+09 | 73822427.99 | 0.215818E+09 | 0.182241E+09 |
February | 0.230918E+09 | 0.140909E+09 | 90008705.79 | 0.244311E+09 | 0.159165E+09 |
March | 0.158065E+09 | 46021543.82 | 0.112044E+09 | 0.139437E+09 | 0.146926E+09 |
April | 0.317647E+09 | 0.143573E+09 | 0.174075E+09 | 0.375498E+09 | 0.123885E+09 |
May | 0.271481E+09 | 88385508.69 | 0.183096E+09 | 0.299255E+09 | 0.112584E+09 |
June | 0.242025E+09 | 58584113.08 | 0.183441E+09 | 0.271044E+09 | 90083792.52 |
July | 0.270970E+09 | 84857401.35 | 0.186113E+09 | 0.323050E+09 | 88444999.80 |
August | 0.317518E+09 | 0.142831E+09 | 0.174687E+09 | 0.398282E+09 | 97453220.57 |
September | 0.363119E+09 | 0.212721E+09 | 0.150398E+09 | 0.451365E+09 | 0.118956E+09 |
October | 0.257794E+09 | 0.150669E+09 | 0.107125E+09 | 0.292098E+09 | 0.145052E+09 |
November | 0.176880E+09 | 0.107600E+09 | 69279279.99 | 0.183454E+09 | 0.162744E+09 |
December | 0.144867E+09 | 92816685.57 | 52049860.74 | 0.144306E+09 | 0.206829E+09 |
Annual Sum or Average | 0.296062E+10 | 0.140448E+10 | 0.155614E+10 | 0.333792E+10 | 0.163436E+10 |
Minimum of Months | 0.144867E+09 | 46021543.82 | 52049860.74 | 0.139437E+09 | 88444999.80 |
Maximum of Months | 0.363119E+09 | 0.212721E+09 | 0.186113E+09 | 0.451365E+09 | 0.206829E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209331E+09 | 0.135509E+09 | 73822427.99 | 0.215818E+09 | 0.182241E+09 |
February | 0.230918E+09 | 0.140909E+09 | 90008705.79 | 0.244311E+09 | 0.159165E+09 |
March | 0.158065E+09 | 46021543.82 | 0.112044E+09 | 0.139437E+09 | 0.146926E+09 |
April | 0.317647E+09 | 0.143573E+09 | 0.174075E+09 | 0.375498E+09 | 0.123885E+09 |
May | 0.271481E+09 | 88385508.69 | 0.183096E+09 | 0.299255E+09 | 0.112584E+09 |
June | 0.242025E+09 | 58584113.08 | 0.183441E+09 | 0.271044E+09 | 90083792.52 |
July | 0.270970E+09 | 84857401.35 | 0.186113E+09 | 0.323050E+09 | 88444999.80 |
August | 0.317518E+09 | 0.142831E+09 | 0.174687E+09 | 0.398282E+09 | 97453220.57 |
September | 0.363119E+09 | 0.212721E+09 | 0.150398E+09 | 0.451365E+09 | 0.118956E+09 |
October | 0.257794E+09 | 0.150669E+09 | 0.107125E+09 | 0.292098E+09 | 0.145052E+09 |
November | 0.176880E+09 | 0.107600E+09 | 69279279.99 | 0.183454E+09 | 0.162744E+09 |
December | 0.144867E+09 | 92816685.57 | 52049860.74 | 0.144306E+09 | 0.206829E+09 |
Annual Sum or Average | 0.296062E+10 | 0.140448E+10 | 0.155614E+10 | 0.333792E+10 | 0.163436E+10 |
Minimum of Months | 0.144867E+09 | 46021543.82 | 52049860.74 | 0.139437E+09 | 88444999.80 |
Maximum of Months | 0.363119E+09 | 0.212721E+09 | 0.186113E+09 | 0.451365E+09 | 0.206829E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.250273E+09 | 0.162012E+09 | 88260973.07 | 0.258557E+09 | 0.215816E+09 |
February | 0.276082E+09 | 0.168469E+09 | 0.107613E+09 | 0.292692E+09 | 0.188218E+09 |
March | 0.188981E+09 | 55022658.43 | 0.133958E+09 | 0.167405E+09 | 0.174062E+09 |
April | 0.379775E+09 | 0.171654E+09 | 0.208121E+09 | 0.449376E+09 | 0.146797E+09 |
May | 0.324579E+09 | 0.105672E+09 | 0.218907E+09 | 0.358557E+09 | 0.133056E+09 |
June | 0.289361E+09 | 70042275.33 | 0.219319E+09 | 0.324655E+09 | 0.106530E+09 |
July | 0.323968E+09 | 0.101454E+09 | 0.222514E+09 | 0.386634E+09 | 0.104656E+09 |
August | 0.379619E+09 | 0.170767E+09 | 0.208853E+09 | 0.476360E+09 | 0.115543E+09 |
September | 0.434140E+09 | 0.254326E+09 | 0.179813E+09 | 0.539955E+09 | 0.140962E+09 |
October | 0.308214E+09 | 0.180137E+09 | 0.128077E+09 | 0.349619E+09 | 0.171731E+09 |
November | 0.211475E+09 | 0.128645E+09 | 82829254.37 | 0.219794E+09 | 0.192504E+09 |
December | 0.173200E+09 | 0.110970E+09 | 62230022.53 | 0.172976E+09 | 0.244302E+09 |
Annual Sum or Average | 0.353967E+10 | 0.167917E+10 | 0.186049E+10 | 0.399658E+10 | 0.193418E+10 |
Minimum of Months | 0.173200E+09 | 55022658.43 | 62230022.53 | 0.167405E+09 | 0.104656E+09 |
Maximum of Months | 0.434140E+09 | 0.254326E+09 | 0.222514E+09 | 0.539955E+09 | 0.244302E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209331E+09 | 0.135509E+09 | 73822427.99 | 0.216662E+09 | 0.178904E+09 |
February | 0.230918E+09 | 0.140909E+09 | 90008705.79 | 0.245273E+09 | 0.156097E+09 |
March | 0.158065E+09 | 46021543.82 | 0.112044E+09 | 0.140562E+09 | 0.143776E+09 |
April | 0.317647E+09 | 0.143573E+09 | 0.174075E+09 | 0.377468E+09 | 0.120998E+09 |
May | 0.271481E+09 | 88385508.69 | 0.183096E+09 | 0.301753E+09 | 0.109570E+09 |
June | 0.242025E+09 | 58584113.08 | 0.183441E+09 | 0.273637E+09 | 87538724.72 |
July | 0.270970E+09 | 84857401.35 | 0.186113E+09 | 0.324937E+09 | 86527175.64 |
August | 0.317518E+09 | 0.142831E+09 | 0.174687E+09 | 0.399574E+09 | 95834948.33 |
September | 0.363119E+09 | 0.212721E+09 | 0.150398E+09 | 0.453186E+09 | 0.116503E+09 |
October | 0.257794E+09 | 0.150669E+09 | 0.107125E+09 | 0.293870E+09 | 0.141143E+09 |
November | 0.176880E+09 | 0.107600E+09 | 69279279.99 | 0.184335E+09 | 0.159341E+09 |
December | 0.144867E+09 | 92816685.57 | 52049860.74 | 0.144874E+09 | 0.203417E+09 |
Annual Sum or Average | 0.296062E+10 | 0.140448E+10 | 0.155614E+10 | 0.335613E+10 | 0.159965E+10 |
Minimum of Months | 0.144867E+09 | 46021543.82 | 52049860.74 | 0.140562E+09 | 86527175.64 |
Maximum of Months | 0.363119E+09 | 0.212721E+09 | 0.186113E+09 | 0.453186E+09 | 0.203417E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209331E+09 | 0.135509E+09 | 73822427.99 | 0.216662E+09 | 0.178904E+09 |
February | 0.230918E+09 | 0.140909E+09 | 90008705.79 | 0.245273E+09 | 0.156097E+09 |
March | 0.158065E+09 | 46021543.82 | 0.112044E+09 | 0.140562E+09 | 0.143776E+09 |
April | 0.317647E+09 | 0.143573E+09 | 0.174075E+09 | 0.377468E+09 | 0.120998E+09 |
May | 0.271481E+09 | 88385508.69 | 0.183096E+09 | 0.301753E+09 | 0.109570E+09 |
June | 0.242025E+09 | 58584113.08 | 0.183441E+09 | 0.273637E+09 | 87538724.72 |
July | 0.270970E+09 | 84857401.35 | 0.186113E+09 | 0.324937E+09 | 86527175.64 |
August | 0.317518E+09 | 0.142831E+09 | 0.174687E+09 | 0.399574E+09 | 95834948.33 |
September | 0.363119E+09 | 0.212721E+09 | 0.150398E+09 | 0.453186E+09 | 0.116503E+09 |
October | 0.257794E+09 | 0.150669E+09 | 0.107125E+09 | 0.293870E+09 | 0.141143E+09 |
November | 0.176880E+09 | 0.107600E+09 | 69279279.99 | 0.184335E+09 | 0.159341E+09 |
December | 0.144867E+09 | 92816685.57 | 52049860.74 | 0.144874E+09 | 0.203417E+09 |
Annual Sum or Average | 0.296062E+10 | 0.140448E+10 | 0.155614E+10 | 0.335613E+10 | 0.159965E+10 |
Minimum of Months | 0.144867E+09 | 46021543.82 | 52049860.74 | 0.140562E+09 | 86527175.64 |
Maximum of Months | 0.363119E+09 | 0.212721E+09 | 0.186113E+09 | 0.453186E+09 | 0.203417E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.250273E+09 | 0.162012E+09 | 88260973.07 | 0.259572E+09 | 0.211854E+09 |
February | 0.276082E+09 | 0.168469E+09 | 0.107613E+09 | 0.293849E+09 | 0.184583E+09 |
March | 0.188981E+09 | 55022658.43 | 0.133958E+09 | 0.168762E+09 | 0.170330E+09 |
April | 0.379775E+09 | 0.171654E+09 | 0.208121E+09 | 0.451720E+09 | 0.143380E+09 |
May | 0.324579E+09 | 0.105672E+09 | 0.218907E+09 | 0.361522E+09 | 0.129508E+09 |
June | 0.289361E+09 | 70042275.33 | 0.219319E+09 | 0.327725E+09 | 0.103530E+09 |
July | 0.323968E+09 | 0.101454E+09 | 0.222514E+09 | 0.388872E+09 | 0.102400E+09 |
August | 0.379619E+09 | 0.170767E+09 | 0.208853E+09 | 0.477894E+09 | 0.113637E+09 |
September | 0.434140E+09 | 0.254326E+09 | 0.179813E+09 | 0.542113E+09 | 0.138067E+09 |
October | 0.308214E+09 | 0.180137E+09 | 0.128077E+09 | 0.351728E+09 | 0.167113E+09 |
November | 0.211475E+09 | 0.128645E+09 | 82829254.37 | 0.220847E+09 | 0.188472E+09 |
December | 0.173200E+09 | 0.110970E+09 | 62230022.53 | 0.173659E+09 | 0.240259E+09 |
Annual Sum or Average | 0.353967E+10 | 0.167917E+10 | 0.186049E+10 | 0.401826E+10 | 0.189313E+10 |
Minimum of Months | 0.173200E+09 | 55022658.43 | 62230022.53 | 0.168762E+09 | 0.102400E+09 |
Maximum of Months | 0.434140E+09 | 0.254326E+09 | 0.222514E+09 | 0.542113E+09 | 0.240259E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209331E+09 | 0.135509E+09 | 73822427.99 | 0.218971E+09 | 0.167397E+09 |
February | 0.230918E+09 | 0.140909E+09 | 90008705.79 | 0.247887E+09 | 0.145267E+09 |
March | 0.158065E+09 | 46021543.82 | 0.112044E+09 | 0.143458E+09 | 0.133370E+09 |
April | 0.317647E+09 | 0.143573E+09 | 0.174075E+09 | 0.379918E+09 | 0.112657E+09 |
May | 0.271481E+09 | 88385508.69 | 0.183096E+09 | 0.305181E+09 | 0.100612E+09 |
June | 0.242025E+09 | 58584113.08 | 0.183441E+09 | 0.277129E+09 | 80289991.67 |
July | 0.270970E+09 | 84857401.35 | 0.186113E+09 | 0.327256E+09 | 80495923.46 |
August | 0.317518E+09 | 0.142831E+09 | 0.174687E+09 | 0.401162E+09 | 89998326.71 |
September | 0.363119E+09 | 0.212721E+09 | 0.150398E+09 | 0.455227E+09 | 0.109115E+09 |
October | 0.257794E+09 | 0.150669E+09 | 0.107125E+09 | 0.296404E+09 | 0.131240E+09 |
November | 0.176880E+09 | 0.107600E+09 | 69279279.99 | 0.186154E+09 | 0.148950E+09 |
December | 0.144867E+09 | 92816685.57 | 52049860.74 | 0.146446E+09 | 0.190751E+09 |
Annual Sum or Average | 0.296062E+10 | 0.140448E+10 | 0.155614E+10 | 0.338519E+10 | 0.149014E+10 |
Minimum of Months | 0.144867E+09 | 46021543.82 | 52049860.74 | 0.143458E+09 | 80289991.67 |
Maximum of Months | 0.363119E+09 | 0.212721E+09 | 0.186113E+09 | 0.455227E+09 | 0.190751E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209331E+09 | 0.135509E+09 | 73822427.99 | 0.218971E+09 | 0.167397E+09 |
February | 0.230918E+09 | 0.140909E+09 | 90008705.79 | 0.247887E+09 | 0.145267E+09 |
March | 0.158065E+09 | 46021543.82 | 0.112044E+09 | 0.143458E+09 | 0.133370E+09 |
April | 0.317647E+09 | 0.143573E+09 | 0.174075E+09 | 0.379918E+09 | 0.112657E+09 |
May | 0.271481E+09 | 88385508.69 | 0.183096E+09 | 0.305181E+09 | 0.100612E+09 |
June | 0.242025E+09 | 58584113.08 | 0.183441E+09 | 0.277129E+09 | 80289991.67 |
July | 0.270970E+09 | 84857401.35 | 0.186113E+09 | 0.327256E+09 | 80495923.46 |
August | 0.317518E+09 | 0.142831E+09 | 0.174687E+09 | 0.401162E+09 | 89998326.71 |
September | 0.363119E+09 | 0.212721E+09 | 0.150398E+09 | 0.455227E+09 | 0.109115E+09 |
October | 0.257794E+09 | 0.150669E+09 | 0.107125E+09 | 0.296404E+09 | 0.131240E+09 |
November | 0.176880E+09 | 0.107600E+09 | 69279279.99 | 0.186154E+09 | 0.148950E+09 |
December | 0.144867E+09 | 92816685.57 | 52049860.74 | 0.146446E+09 | 0.190751E+09 |
Annual Sum or Average | 0.296062E+10 | 0.140448E+10 | 0.155614E+10 | 0.338519E+10 | 0.149014E+10 |
Minimum of Months | 0.144867E+09 | 46021543.82 | 52049860.74 | 0.143458E+09 | 80289991.67 |
Maximum of Months | 0.363119E+09 | 0.212721E+09 | 0.186113E+09 | 0.455227E+09 | 0.190751E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.250273E+09 | 0.162012E+09 | 88260973.07 | 0.262381E+09 | 0.198171E+09 |
February | 0.276082E+09 | 0.168469E+09 | 0.107613E+09 | 0.297019E+09 | 0.171739E+09 |
March | 0.188981E+09 | 55022658.43 | 0.133958E+09 | 0.172278E+09 | 0.157961E+09 |
April | 0.379775E+09 | 0.171654E+09 | 0.208121E+09 | 0.454686E+09 | 0.133505E+09 |
May | 0.324579E+09 | 0.105672E+09 | 0.218907E+09 | 0.365646E+09 | 0.118967E+09 |
June | 0.289361E+09 | 70042275.33 | 0.219319E+09 | 0.331905E+09 | 95001475.10 |
July | 0.323968E+09 | 0.101454E+09 | 0.222514E+09 | 0.391660E+09 | 95310363.67 |
August | 0.379619E+09 | 0.170767E+09 | 0.208853E+09 | 0.479810E+09 | 0.106761E+09 |
September | 0.434140E+09 | 0.254326E+09 | 0.179813E+09 | 0.544565E+09 | 0.129357E+09 |
October | 0.308214E+09 | 0.180137E+09 | 0.128077E+09 | 0.354782E+09 | 0.155392E+09 |
November | 0.211475E+09 | 0.128645E+09 | 82829254.37 | 0.223053E+09 | 0.176148E+09 |
December | 0.173200E+09 | 0.110970E+09 | 62230022.53 | 0.175566E+09 | 0.225246E+09 |
Annual Sum or Average | 0.353967E+10 | 0.167917E+10 | 0.186049E+10 | 0.405335E+10 | 0.176356E+10 |
Minimum of Months | 0.173200E+09 | 55022658.43 | 62230022.53 | 0.172278E+09 | 95001475.10 |
Maximum of Months | 0.434140E+09 | 0.254326E+09 | 0.222514E+09 | 0.544565E+09 | 0.225246E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 516.08 | 442.44 | 500.53 | 324.01 | 176.52 | 0.00 | 0.00 |
February | 647.62 | 425.50 | 611.31 | 373.03 | 238.28 | 0.00 | 0.00 |
March | 334.26 | 354.84 | 377.95 | 110.04 | 267.91 | 0.00 | 0.00 |
April | 931.02 | 304.87 | 784.84 | 354.74 | 430.10 | 0.00 | 0.00 |
May | 719.63 | 266.52 | 649.14 | 211.34 | 437.80 | 0.00 | 0.00 |
June | 674.64 | 218.48 | 597.99 | 144.75 | 453.25 | 0.00 | 0.00 |
July | 776.35 | 207.55 | 647.92 | 202.90 | 445.01 | 0.00 | 0.00 |
August | 955.18 | 228.85 | 759.22 | 341.52 | 417.69 | 0.00 | 0.00 |
September | 1119.89 | 287.84 | 897.19 | 525.59 | 371.60 | 0.00 | 0.00 |
October | 701.61 | 344.78 | 616.41 | 360.26 | 256.15 | 0.00 | 0.00 |
November | 453.54 | 407.50 | 437.03 | 265.86 | 171.18 | 0.00 | 0.00 |
December | 345.10 | 500.12 | 346.39 | 221.93 | 124.46 | 0.00 | 0.00 |
Annual Sum or Average | 680.27 | 331.98 | 601.24 | 285.22 | 316.02 | 0.00 | 0.00 |
Minimum of Months | 334.26 | 207.55 | 346.39 | 110.04 | 124.46 | 0.00 | 0.00 |
Maximum of Months | 1119.89 | 500.12 | 897.19 | 525.59 | 453.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 254.80 | 234.26 | 250.27 | 162.01 | 88.26 | 0.00 | 0.00 |
February | 319.97 | 225.89 | 305.65 | 186.51 | 119.14 | 0.00 | 0.00 |
March | 163.16 | 189.97 | 188.97 | 55.02 | 133.95 | 0.00 | 0.00 |
April | 457.76 | 166.09 | 392.42 | 177.37 | 215.05 | 0.00 | 0.00 |
May | 351.46 | 145.91 | 324.57 | 105.67 | 218.90 | 0.00 | 0.00 |
June | 330.92 | 116.10 | 299.00 | 72.37 | 226.62 | 0.00 | 0.00 |
July | 384.37 | 107.99 | 323.96 | 101.45 | 222.51 | 0.00 | 0.00 |
August | 475.14 | 117.68 | 379.61 | 170.76 | 208.85 | 0.00 | 0.00 |
September | 555.73 | 150.22 | 448.60 | 262.80 | 185.80 | 0.00 | 0.00 |
October | 345.02 | 188.28 | 308.20 | 180.13 | 128.07 | 0.00 | 0.00 |
November | 223.89 | 217.49 | 218.52 | 132.93 | 85.59 | 0.00 | 0.00 |
December | 170.27 | 264.87 | 173.19 | 110.97 | 62.23 | 0.00 | 0.00 |
Annual Sum or Average | 335.56 | 176.82 | 300.62 | 142.61 | 158.01 | 0.00 | 0.00 |
Minimum of Months | 163.16 | 107.99 | 173.19 | 55.02 | 62.23 | 0.00 | 0.00 |
Maximum of Months | 555.73 | 264.87 | 448.60 | 262.80 | 226.62 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 255.00 | 227.30 | 249.75 | 161.67 | 88.08 | 0.00 | 0.00 |
February | 320.02 | 219.35 | 305.03 | 186.13 | 118.89 | 0.00 | 0.00 |
March | 163.54 | 183.96 | 188.59 | 54.91 | 133.68 | 0.00 | 0.00 |
April | 458.19 | 162.10 | 391.62 | 177.01 | 214.61 | 0.00 | 0.00 |
May | 352.09 | 142.71 | 323.90 | 105.45 | 218.45 | 0.00 | 0.00 |
June | 330.19 | 117.05 | 298.38 | 72.23 | 226.16 | 0.00 | 0.00 |
July | 383.13 | 110.02 | 323.29 | 101.24 | 222.05 | 0.00 | 0.00 |
August | 473.92 | 120.19 | 378.83 | 170.41 | 208.42 | 0.00 | 0.00 |
September | 554.67 | 151.63 | 447.68 | 262.26 | 185.42 | 0.00 | 0.00 |
October | 345.32 | 183.18 | 307.57 | 179.76 | 127.81 | 0.00 | 0.00 |
November | 224.20 | 210.12 | 218.07 | 132.66 | 85.41 | 0.00 | 0.00 |
December | 170.39 | 257.52 | 172.84 | 110.74 | 62.10 | 0.00 | 0.00 |
Annual Sum or Average | 335.41 | 173.54 | 300.00 | 142.32 | 157.69 | 0.00 | 0.00 |
Minimum of Months | 163.54 | 110.02 | 172.84 | 54.91 | 62.10 | 0.00 | 0.00 |
Maximum of Months | 554.67 | 257.52 | 447.68 | 262.26 | 226.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 255.51 | 224.34 | 249.75 | 161.67 | 88.08 | 0.00 | 0.00 |
February | 320.55 | 216.69 | 305.03 | 186.13 | 118.89 | 0.00 | 0.00 |
March | 164.11 | 181.48 | 188.59 | 54.91 | 133.68 | 0.00 | 0.00 |
April | 459.38 | 159.44 | 391.62 | 177.01 | 214.61 | 0.00 | 0.00 |
May | 353.31 | 140.37 | 323.90 | 105.45 | 218.45 | 0.00 | 0.00 |
June | 330.80 | 115.98 | 298.38 | 72.23 | 226.16 | 0.00 | 0.00 |
July | 383.43 | 109.38 | 323.29 | 101.24 | 222.05 | 0.00 | 0.00 |
August | 474.06 | 119.75 | 378.83 | 170.41 | 208.42 | 0.00 | 0.00 |
September | 554.95 | 150.75 | 447.68 | 262.26 | 185.42 | 0.00 | 0.00 |
October | 346.06 | 180.30 | 307.57 | 179.76 | 127.81 | 0.00 | 0.00 |
November | 224.65 | 207.19 | 218.07 | 132.66 | 85.41 | 0.00 | 0.00 |
December | 170.73 | 254.40 | 172.84 | 110.74 | 62.10 | 0.00 | 0.00 |
Annual Sum or Average | 335.98 | 171.45 | 300.00 | 142.32 | 157.69 | 0.00 | 0.00 |
Minimum of Months | 164.11 | 109.38 | 172.84 | 54.91 | 62.10 | 0.00 | 0.00 |
Maximum of Months | 554.95 | 254.40 | 447.68 | 262.26 | 226.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 256.02 | 222.11 | 249.75 | 161.67 | 88.08 | 0.00 | 0.00 |
February | 321.12 | 214.66 | 305.03 | 186.13 | 118.89 | 0.00 | 0.00 |
March | 164.72 | 179.56 | 188.59 | 54.91 | 133.68 | 0.00 | 0.00 |
April | 460.85 | 156.90 | 391.62 | 177.01 | 214.61 | 0.00 | 0.00 |
May | 354.91 | 137.99 | 323.90 | 105.45 | 218.45 | 0.00 | 0.00 |
June | 332.14 | 114.23 | 298.38 | 72.23 | 226.16 | 0.00 | 0.00 |
July | 384.19 | 108.18 | 323.29 | 101.24 | 222.05 | 0.00 | 0.00 |
August | 474.45 | 118.85 | 378.83 | 170.41 | 208.42 | 0.00 | 0.00 |
September | 555.59 | 149.36 | 447.68 | 262.26 | 185.42 | 0.00 | 0.00 |
October | 347.04 | 177.54 | 307.57 | 179.76 | 127.81 | 0.00 | 0.00 |
November | 225.08 | 205.07 | 218.07 | 132.66 | 85.41 | 0.00 | 0.00 |
December | 171.11 | 251.85 | 172.84 | 110.74 | 62.10 | 0.00 | 0.00 |
Annual Sum or Average | 336.79 | 169.47 | 300.00 | 142.32 | 157.69 | 0.00 | 0.00 |
Minimum of Months | 164.72 | 108.18 | 172.84 | 54.91 | 62.10 | 0.00 | 0.00 |
Maximum of Months | 555.59 | 251.85 | 447.68 | 262.26 | 226.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 516.12 | 433.70 | 499.50 | 323.35 | 176.15 | 0.00 | 0.00 |
February | 646.78 | 419.17 | 610.05 | 372.26 | 237.79 | 0.00 | 0.00 |
March | 333.95 | 350.24 | 377.17 | 109.82 | 267.36 | 0.00 | 0.00 |
April | 928.36 | 304.31 | 783.23 | 354.01 | 429.22 | 0.00 | 0.00 |
May | 717.26 | 266.80 | 647.81 | 210.90 | 436.90 | 0.00 | 0.00 |
June | 671.80 | 220.11 | 596.77 | 144.45 | 452.32 | 0.00 | 0.00 |
July | 772.70 | 210.52 | 646.59 | 202.49 | 444.10 | 0.00 | 0.00 |
August | 951.23 | 232.94 | 757.66 | 340.82 | 416.84 | 0.00 | 0.00 |
September | 1115.48 | 291.57 | 895.35 | 524.51 | 370.84 | 0.00 | 0.00 |
October | 699.37 | 343.96 | 615.14 | 359.52 | 255.62 | 0.00 | 0.00 |
November | 453.31 | 400.23 | 436.14 | 265.31 | 170.82 | 0.00 | 0.00 |
December | 345.32 | 490.06 | 345.68 | 221.48 | 124.20 | 0.00 | 0.00 |
Annual Sum or Average | 678.34 | 329.86 | 600.01 | 284.64 | 315.37 | 0.00 | 0.00 |
Minimum of Months | 333.95 | 210.52 | 345.68 | 109.82 | 124.20 | 0.00 | 0.00 |
Maximum of Months | 1115.48 | 490.06 | 895.35 | 524.51 | 452.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 257.43 | 217.62 | 249.75 | 161.67 | 88.08 | 0.00 | 0.00 |
February | 322.64 | 210.37 | 305.03 | 186.13 | 118.89 | 0.00 | 0.00 |
March | 166.29 | 175.60 | 188.59 | 54.91 | 133.68 | 0.00 | 0.00 |
April | 462.56 | 153.05 | 391.62 | 177.01 | 214.61 | 0.00 | 0.00 |
May | 356.68 | 134.55 | 323.90 | 105.45 | 218.45 | 0.00 | 0.00 |
June | 333.78 | 111.24 | 298.38 | 72.23 | 226.16 | 0.00 | 0.00 |
July | 385.12 | 105.65 | 323.29 | 101.24 | 222.05 | 0.00 | 0.00 |
August | 474.93 | 116.40 | 378.83 | 170.41 | 208.42 | 0.00 | 0.00 |
September | 556.20 | 146.78 | 447.68 | 262.26 | 185.42 | 0.00 | 0.00 |
October | 348.20 | 173.46 | 307.57 | 179.76 | 127.81 | 0.00 | 0.00 |
November | 226.09 | 200.89 | 218.07 | 132.66 | 85.41 | 0.00 | 0.00 |
December | 172.18 | 246.56 | 172.84 | 110.74 | 62.10 | 0.00 | 0.00 |
Annual Sum or Average | 338.02 | 165.79 | 300.00 | 142.32 | 157.69 | 0.00 | 0.00 |
Minimum of Months | 166.29 | 105.65 | 172.84 | 54.91 | 62.10 | 0.00 | 0.00 |
Maximum of Months | 556.20 | 246.56 | 447.68 | 262.26 | 226.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 257.69 | 216.66 | 249.75 | 161.67 | 88.08 | 0.00 | 0.00 |
February | 322.96 | 209.39 | 305.03 | 186.13 | 118.89 | 0.00 | 0.00 |
March | 166.62 | 174.70 | 188.59 | 54.91 | 133.68 | 0.00 | 0.00 |
April | 463.11 | 152.23 | 391.62 | 177.01 | 214.61 | 0.00 | 0.00 |
May | 357.33 | 133.74 | 323.90 | 105.45 | 218.45 | 0.00 | 0.00 |
June | 334.39 | 110.61 | 298.38 | 72.23 | 226.16 | 0.00 | 0.00 |
July | 385.58 | 105.12 | 323.29 | 101.24 | 222.05 | 0.00 | 0.00 |
August | 475.26 | 115.91 | 378.83 | 170.41 | 208.42 | 0.00 | 0.00 |
September | 556.59 | 146.17 | 447.68 | 262.26 | 185.42 | 0.00 | 0.00 |
October | 348.65 | 172.43 | 307.57 | 179.76 | 127.81 | 0.00 | 0.00 |
November | 226.35 | 199.84 | 218.07 | 132.66 | 85.41 | 0.00 | 0.00 |
December | 172.34 | 245.65 | 172.84 | 110.74 | 62.10 | 0.00 | 0.00 |
Annual Sum or Average | 338.42 | 164.98 | 300.00 | 142.32 | 157.69 | 0.00 | 0.00 |
Minimum of Months | 166.62 | 105.12 | 172.84 | 54.91 | 62.10 | 0.00 | 0.00 |
Maximum of Months | 556.59 | 245.65 | 447.68 | 262.26 | 226.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 258.70 | 212.69 | 249.75 | 161.67 | 88.08 | 0.00 | 0.00 |
February | 324.24 | 205.35 | 305.03 | 186.13 | 118.89 | 0.00 | 0.00 |
March | 167.97 | 170.95 | 188.59 | 54.91 | 133.68 | 0.00 | 0.00 |
April | 465.53 | 148.68 | 391.62 | 177.01 | 214.61 | 0.00 | 0.00 |
May | 360.30 | 130.17 | 323.90 | 105.45 | 218.45 | 0.00 | 0.00 |
June | 337.58 | 107.49 | 298.38 | 72.23 | 226.16 | 0.00 | 0.00 |
July | 387.82 | 102.84 | 323.29 | 101.24 | 222.05 | 0.00 | 0.00 |
August | 476.79 | 113.99 | 378.83 | 170.41 | 208.42 | 0.00 | 0.00 |
September | 558.83 | 143.16 | 447.68 | 262.26 | 185.42 | 0.00 | 0.00 |
October | 350.76 | 167.79 | 307.57 | 179.76 | 127.81 | 0.00 | 0.00 |
November | 227.44 | 195.66 | 218.07 | 132.66 | 85.41 | 0.00 | 0.00 |
December | 173.02 | 241.60 | 172.84 | 110.74 | 62.10 | 0.00 | 0.00 |
Annual Sum or Average | 340.26 | 161.48 | 300.00 | 142.32 | 157.69 | 0.00 | 0.00 |
Minimum of Months | 167.97 | 102.84 | 172.84 | 54.91 | 62.10 | 0.00 | 0.00 |
Maximum of Months | 558.83 | 241.60 | 447.68 | 262.26 | 226.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 261.47 | 198.99 | 249.75 | 161.67 | 88.08 | 0.00 | 0.00 |
February | 327.71 | 191.09 | 305.03 | 186.13 | 118.89 | 0.00 | 0.00 |
March | 171.44 | 158.57 | 188.59 | 54.91 | 133.68 | 0.00 | 0.00 |
April | 468.57 | 138.43 | 391.62 | 177.01 | 214.61 | 0.00 | 0.00 |
May | 364.40 | 119.55 | 323.90 | 105.45 | 218.45 | 0.00 | 0.00 |
June | 341.88 | 98.60 | 298.38 | 72.23 | 226.16 | 0.00 | 0.00 |
July | 390.60 | 95.69 | 323.29 | 101.24 | 222.05 | 0.00 | 0.00 |
August | 478.69 | 107.06 | 378.83 | 170.41 | 208.42 | 0.00 | 0.00 |
September | 561.35 | 134.10 | 447.68 | 262.26 | 185.42 | 0.00 | 0.00 |
October | 353.79 | 156.02 | 307.57 | 179.76 | 127.81 | 0.00 | 0.00 |
November | 229.69 | 182.89 | 218.07 | 132.66 | 85.41 | 0.00 | 0.00 |
December | 174.90 | 226.53 | 172.84 | 110.74 | 62.10 | 0.00 | 0.00 |
Annual Sum or Average | 343.22 | 150.43 | 300.00 | 142.32 | 157.69 | 0.00 | 0.00 |
Minimum of Months | 171.44 | 95.69 | 172.84 | 54.91 | 62.10 | 0.00 | 0.00 |
Maximum of Months | 561.35 | 226.53 | 447.68 | 262.26 | 226.16 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.138227E+10 | 0.118503E+10 | 0.134062E+10 | 0.867838E+09 | 0.472782E+09 | 0.00 | 0.00 |
February | 0.156671E+10 | 0.102936E+10 | 0.147887E+10 | 0.902427E+09 | 0.576443E+09 | 0.00 | 0.00 |
March | 0.895275E+09 | 0.950399E+09 | 0.101230E+10 | 0.294736E+09 | 0.717563E+09 | 0.00 | 0.00 |
April | 0.241320E+10 | 0.790220E+09 | 0.203431E+10 | 0.919485E+09 | 0.111483E+10 | 0.00 | 0.00 |
May | 0.192744E+10 | 0.713841E+09 | 0.173865E+10 | 0.566048E+09 | 0.117260E+10 | 0.00 | 0.00 |
June | 0.174867E+10 | 0.566307E+09 | 0.155000E+10 | 0.375191E+09 | 0.117481E+10 | 0.00 | 0.00 |
July | 0.207939E+10 | 0.555901E+09 | 0.173538E+10 | 0.543453E+09 | 0.119192E+10 | 0.00 | 0.00 |
August | 0.255835E+10 | 0.612940E+09 | 0.203348E+10 | 0.914736E+09 | 0.111875E+10 | 0.00 | 0.00 |
September | 0.290274E+10 | 0.746068E+09 | 0.232553E+10 | 0.136233E+10 | 0.963194E+09 | 0.00 | 0.00 |
October | 0.187918E+10 | 0.923464E+09 | 0.165099E+10 | 0.964930E+09 | 0.686061E+09 | 0.00 | 0.00 |
November | 0.117558E+10 | 0.105624E+10 | 0.113279E+10 | 0.689106E+09 | 0.443686E+09 | 0.00 | 0.00 |
December | 0.924303E+09 | 0.133952E+10 | 0.927770E+09 | 0.594427E+09 | 0.333343E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.214531E+11 | 0.104693E+11 | 0.189607E+11 | 0.899471E+10 | 0.996599E+10 | 0.00 | 0.00 |
Minimum of Months | 0.895275E+09 | 0.555901E+09 | 0.927770E+09 | 0.294736E+09 | 0.333343E+09 | 0.00 | 0.00 |
Maximum of Months | 0.290274E+10 | 0.133952E+10 | 0.232553E+10 | 0.136233E+10 | 0.119192E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.682468E+09 | 0.627448E+09 | 0.670310E+09 | 0.433919E+09 | 0.236391E+09 | 0.00 | 0.00 |
February | 0.774077E+09 | 0.546473E+09 | 0.739435E+09 | 0.451213E+09 | 0.288222E+09 | 0.00 | 0.00 |
March | 0.436994E+09 | 0.508825E+09 | 0.506150E+09 | 0.147368E+09 | 0.358782E+09 | 0.00 | 0.00 |
April | 0.118652E+10 | 0.430506E+09 | 0.101716E+10 | 0.459743E+09 | 0.557414E+09 | 0.00 | 0.00 |
May | 0.941344E+09 | 0.390796E+09 | 0.869325E+09 | 0.283024E+09 | 0.586301E+09 | 0.00 | 0.00 |
June | 0.857739E+09 | 0.300932E+09 | 0.775001E+09 | 0.187595E+09 | 0.587406E+09 | 0.00 | 0.00 |
July | 0.102949E+10 | 0.289234E+09 | 0.867689E+09 | 0.271726E+09 | 0.595962E+09 | 0.00 | 0.00 |
August | 0.127261E+10 | 0.315206E+09 | 0.101674E+10 | 0.457368E+09 | 0.559373E+09 | 0.00 | 0.00 |
September | 0.144045E+10 | 0.389377E+09 | 0.116276E+10 | 0.681166E+09 | 0.481597E+09 | 0.00 | 0.00 |
October | 0.924111E+09 | 0.504295E+09 | 0.825496E+09 | 0.482465E+09 | 0.343031E+09 | 0.00 | 0.00 |
November | 0.580335E+09 | 0.563746E+09 | 0.566396E+09 | 0.344553E+09 | 0.221843E+09 | 0.00 | 0.00 |
December | 0.456040E+09 | 0.709438E+09 | 0.463885E+09 | 0.297213E+09 | 0.166672E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.105822E+11 | 0.557628E+10 | 0.948035E+10 | 0.449735E+10 | 0.498299E+10 | 0.00 | 0.00 |
Minimum of Months | 0.436994E+09 | 0.289234E+09 | 0.463885E+09 | 0.147368E+09 | 0.166672E+09 | 0.00 | 0.00 |
Maximum of Months | 0.144045E+10 | 0.709438E+09 | 0.116276E+10 | 0.681166E+09 | 0.595962E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.682986E+09 | 0.608810E+09 | 0.668935E+09 | 0.433029E+09 | 0.235906E+09 | 0.00 | 0.00 |
February | 0.774196E+09 | 0.530654E+09 | 0.737918E+09 | 0.450288E+09 | 0.287630E+09 | 0.00 | 0.00 |
March | 0.438038E+09 | 0.492729E+09 | 0.505111E+09 | 0.147066E+09 | 0.358046E+09 | 0.00 | 0.00 |
April | 0.118763E+10 | 0.420161E+09 | 0.101507E+10 | 0.458800E+09 | 0.556270E+09 | 0.00 | 0.00 |
May | 0.943045E+09 | 0.382227E+09 | 0.867542E+09 | 0.282443E+09 | 0.585099E+09 | 0.00 | 0.00 |
June | 0.855853E+09 | 0.303385E+09 | 0.773411E+09 | 0.187211E+09 | 0.586201E+09 | 0.00 | 0.00 |
July | 0.102618E+10 | 0.294689E+09 | 0.865909E+09 | 0.271169E+09 | 0.594740E+09 | 0.00 | 0.00 |
August | 0.126935E+10 | 0.321925E+09 | 0.101466E+10 | 0.456430E+09 | 0.558226E+09 | 0.00 | 0.00 |
September | 0.143769E+10 | 0.393033E+09 | 0.116038E+10 | 0.679769E+09 | 0.480609E+09 | 0.00 | 0.00 |
October | 0.924895E+09 | 0.490630E+09 | 0.823802E+09 | 0.481475E+09 | 0.342327E+09 | 0.00 | 0.00 |
November | 0.581124E+09 | 0.544631E+09 | 0.565234E+09 | 0.343846E+09 | 0.221388E+09 | 0.00 | 0.00 |
December | 0.456363E+09 | 0.689738E+09 | 0.462933E+09 | 0.296604E+09 | 0.166330E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.105774E+11 | 0.547261E+10 | 0.946090E+10 | 0.448813E+10 | 0.497277E+10 | 0.00 | 0.00 |
Minimum of Months | 0.438038E+09 | 0.294689E+09 | 0.462933E+09 | 0.147066E+09 | 0.166330E+09 | 0.00 | 0.00 |
Maximum of Months | 0.143769E+10 | 0.689738E+09 | 0.116038E+10 | 0.679769E+09 | 0.594740E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.684363E+09 | 0.600879E+09 | 0.668935E+09 | 0.433029E+09 | 0.235906E+09 | 0.00 | 0.00 |
February | 0.775486E+09 | 0.524212E+09 | 0.737918E+09 | 0.450288E+09 | 0.287630E+09 | 0.00 | 0.00 |
March | 0.439540E+09 | 0.486073E+09 | 0.505111E+09 | 0.147066E+09 | 0.358046E+09 | 0.00 | 0.00 |
April | 0.119072E+10 | 0.413276E+09 | 0.101507E+10 | 0.458800E+09 | 0.556270E+09 | 0.00 | 0.00 |
May | 0.946317E+09 | 0.375980E+09 | 0.867542E+09 | 0.282443E+09 | 0.585099E+09 | 0.00 | 0.00 |
June | 0.857422E+09 | 0.300629E+09 | 0.773411E+09 | 0.187211E+09 | 0.586201E+09 | 0.00 | 0.00 |
July | 0.102699E+10 | 0.292971E+09 | 0.865909E+09 | 0.271169E+09 | 0.594740E+09 | 0.00 | 0.00 |
August | 0.126973E+10 | 0.320741E+09 | 0.101466E+10 | 0.456430E+09 | 0.558226E+09 | 0.00 | 0.00 |
September | 0.143843E+10 | 0.390732E+09 | 0.116038E+10 | 0.679769E+09 | 0.480609E+09 | 0.00 | 0.00 |
October | 0.926890E+09 | 0.482913E+09 | 0.823802E+09 | 0.481475E+09 | 0.342327E+09 | 0.00 | 0.00 |
November | 0.582291E+09 | 0.537041E+09 | 0.565234E+09 | 0.343846E+09 | 0.221388E+09 | 0.00 | 0.00 |
December | 0.457287E+09 | 0.681390E+09 | 0.462933E+09 | 0.296604E+09 | 0.166330E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.105955E+11 | 0.540684E+10 | 0.946090E+10 | 0.448813E+10 | 0.497277E+10 | 0.00 | 0.00 |
Minimum of Months | 0.439540E+09 | 0.292971E+09 | 0.462933E+09 | 0.147066E+09 | 0.166330E+09 | 0.00 | 0.00 |
Maximum of Months | 0.143843E+10 | 0.681390E+09 | 0.116038E+10 | 0.679769E+09 | 0.594740E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.685731E+09 | 0.594900E+09 | 0.668935E+09 | 0.433029E+09 | 0.235906E+09 | 0.00 | 0.00 |
February | 0.776849E+09 | 0.519294E+09 | 0.737918E+09 | 0.450288E+09 | 0.287630E+09 | 0.00 | 0.00 |
March | 0.441193E+09 | 0.480940E+09 | 0.505111E+09 | 0.147066E+09 | 0.358046E+09 | 0.00 | 0.00 |
April | 0.119452E+10 | 0.406691E+09 | 0.101507E+10 | 0.458800E+09 | 0.556270E+09 | 0.00 | 0.00 |
May | 0.950592E+09 | 0.369603E+09 | 0.867542E+09 | 0.282443E+09 | 0.585099E+09 | 0.00 | 0.00 |
June | 0.860912E+09 | 0.296084E+09 | 0.773411E+09 | 0.187211E+09 | 0.586201E+09 | 0.00 | 0.00 |
July | 0.102902E+10 | 0.289762E+09 | 0.865909E+09 | 0.271169E+09 | 0.594740E+09 | 0.00 | 0.00 |
August | 0.127078E+10 | 0.318323E+09 | 0.101466E+10 | 0.456430E+09 | 0.558226E+09 | 0.00 | 0.00 |
September | 0.144008E+10 | 0.387136E+09 | 0.116038E+10 | 0.679769E+09 | 0.480609E+09 | 0.00 | 0.00 |
October | 0.929523E+09 | 0.475524E+09 | 0.823802E+09 | 0.481475E+09 | 0.342327E+09 | 0.00 | 0.00 |
November | 0.583414E+09 | 0.531545E+09 | 0.565234E+09 | 0.343846E+09 | 0.221388E+09 | 0.00 | 0.00 |
December | 0.458297E+09 | 0.674563E+09 | 0.462933E+09 | 0.296604E+09 | 0.166330E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.106209E+11 | 0.534437E+10 | 0.946090E+10 | 0.448813E+10 | 0.497277E+10 | 0.00 | 0.00 |
Minimum of Months | 0.441193E+09 | 0.289762E+09 | 0.462933E+09 | 0.147066E+09 | 0.166330E+09 | 0.00 | 0.00 |
Maximum of Months | 0.144008E+10 | 0.674563E+09 | 0.116038E+10 | 0.679769E+09 | 0.594740E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.138237E+10 | 0.116163E+10 | 0.133787E+10 | 0.866058E+09 | 0.471812E+09 | 0.00 | 0.00 |
February | 0.156468E+10 | 0.101406E+10 | 0.147584E+10 | 0.900576E+09 | 0.575261E+09 | 0.00 | 0.00 |
March | 0.894453E+09 | 0.938073E+09 | 0.101022E+10 | 0.294131E+09 | 0.716091E+09 | 0.00 | 0.00 |
April | 0.240631E+10 | 0.788778E+09 | 0.203014E+10 | 0.917599E+09 | 0.111254E+10 | 0.00 | 0.00 |
May | 0.192111E+10 | 0.714603E+09 | 0.173508E+10 | 0.564887E+09 | 0.117020E+10 | 0.00 | 0.00 |
June | 0.174131E+10 | 0.570514E+09 | 0.154682E+10 | 0.374421E+09 | 0.117240E+10 | 0.00 | 0.00 |
July | 0.206959E+10 | 0.563851E+09 | 0.173182E+10 | 0.542338E+09 | 0.118948E+10 | 0.00 | 0.00 |
August | 0.254779E+10 | 0.623909E+09 | 0.202931E+10 | 0.912859E+09 | 0.111645E+10 | 0.00 | 0.00 |
September | 0.289133E+10 | 0.755746E+09 | 0.232076E+10 | 0.135954E+10 | 0.961219E+09 | 0.00 | 0.00 |
October | 0.187318E+10 | 0.921261E+09 | 0.164760E+10 | 0.962950E+09 | 0.684654E+09 | 0.00 | 0.00 |
November | 0.117497E+10 | 0.103740E+10 | 0.113047E+10 | 0.687693E+09 | 0.442776E+09 | 0.00 | 0.00 |
December | 0.924913E+09 | 0.131258E+10 | 0.925867E+09 | 0.593207E+09 | 0.332659E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.213920E+11 | 0.104024E+11 | 0.189218E+11 | 0.897626E+10 | 0.994554E+10 | 0.00 | 0.00 |
Minimum of Months | 0.894453E+09 | 0.563851E+09 | 0.925867E+09 | 0.294131E+09 | 0.332659E+09 | 0.00 | 0.00 |
Maximum of Months | 0.289133E+10 | 0.131258E+10 | 0.232076E+10 | 0.135954E+10 | 0.118948E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.689499E+09 | 0.582865E+09 | 0.668935E+09 | 0.433029E+09 | 0.235906E+09 | 0.00 | 0.00 |
February | 0.780528E+09 | 0.508932E+09 | 0.737918E+09 | 0.450288E+09 | 0.287630E+09 | 0.00 | 0.00 |
March | 0.445379E+09 | 0.470314E+09 | 0.505111E+09 | 0.147066E+09 | 0.358046E+09 | 0.00 | 0.00 |
April | 0.119897E+10 | 0.396699E+09 | 0.101507E+10 | 0.458800E+09 | 0.556270E+09 | 0.00 | 0.00 |
May | 0.955324E+09 | 0.360375E+09 | 0.867542E+09 | 0.282443E+09 | 0.585099E+09 | 0.00 | 0.00 |
June | 0.865157E+09 | 0.288346E+09 | 0.773411E+09 | 0.187211E+09 | 0.586201E+09 | 0.00 | 0.00 |
July | 0.103152E+10 | 0.282960E+09 | 0.865909E+09 | 0.271169E+09 | 0.594740E+09 | 0.00 | 0.00 |
August | 0.127204E+10 | 0.311770E+09 | 0.101466E+10 | 0.456430E+09 | 0.558226E+09 | 0.00 | 0.00 |
September | 0.144168E+10 | 0.380445E+09 | 0.116038E+10 | 0.679769E+09 | 0.480609E+09 | 0.00 | 0.00 |
October | 0.932623E+09 | 0.464602E+09 | 0.823802E+09 | 0.481475E+09 | 0.342327E+09 | 0.00 | 0.00 |
November | 0.586037E+09 | 0.520702E+09 | 0.565234E+09 | 0.343846E+09 | 0.221388E+09 | 0.00 | 0.00 |
December | 0.461174E+09 | 0.660377E+09 | 0.462933E+09 | 0.296604E+09 | 0.166330E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.106599E+11 | 0.522839E+10 | 0.946090E+10 | 0.448813E+10 | 0.497277E+10 | 0.00 | 0.00 |
Minimum of Months | 0.445379E+09 | 0.282960E+09 | 0.462933E+09 | 0.147066E+09 | 0.166330E+09 | 0.00 | 0.00 |
Maximum of Months | 0.144168E+10 | 0.660377E+09 | 0.116038E+10 | 0.679769E+09 | 0.594740E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.690193E+09 | 0.580298E+09 | 0.668935E+09 | 0.433029E+09 | 0.235906E+09 | 0.00 | 0.00 |
February | 0.781312E+09 | 0.506545E+09 | 0.737918E+09 | 0.450288E+09 | 0.287630E+09 | 0.00 | 0.00 |
March | 0.446278E+09 | 0.467914E+09 | 0.505111E+09 | 0.147066E+09 | 0.358046E+09 | 0.00 | 0.00 |
April | 0.120037E+10 | 0.394567E+09 | 0.101507E+10 | 0.458800E+09 | 0.556270E+09 | 0.00 | 0.00 |
May | 0.957065E+09 | 0.358222E+09 | 0.867542E+09 | 0.282443E+09 | 0.585099E+09 | 0.00 | 0.00 |
June | 0.866742E+09 | 0.286697E+09 | 0.773411E+09 | 0.187211E+09 | 0.586201E+09 | 0.00 | 0.00 |
July | 0.103273E+10 | 0.281546E+09 | 0.865909E+09 | 0.271169E+09 | 0.594740E+09 | 0.00 | 0.00 |
August | 0.127292E+10 | 0.310449E+09 | 0.101466E+10 | 0.456430E+09 | 0.558226E+09 | 0.00 | 0.00 |
September | 0.144268E+10 | 0.378874E+09 | 0.116038E+10 | 0.679769E+09 | 0.480609E+09 | 0.00 | 0.00 |
October | 0.933815E+09 | 0.461835E+09 | 0.823802E+09 | 0.481475E+09 | 0.342327E+09 | 0.00 | 0.00 |
November | 0.586702E+09 | 0.517992E+09 | 0.565234E+09 | 0.343846E+09 | 0.221388E+09 | 0.00 | 0.00 |
December | 0.461587E+09 | 0.657960E+09 | 0.462933E+09 | 0.296604E+09 | 0.166330E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.106724E+11 | 0.520290E+10 | 0.946090E+10 | 0.448813E+10 | 0.497277E+10 | 0.00 | 0.00 |
Minimum of Months | 0.446278E+09 | 0.281546E+09 | 0.462933E+09 | 0.147066E+09 | 0.166330E+09 | 0.00 | 0.00 |
Maximum of Months | 0.144268E+10 | 0.657960E+09 | 0.116038E+10 | 0.679769E+09 | 0.594740E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.692896E+09 | 0.569661E+09 | 0.668935E+09 | 0.433029E+09 | 0.235906E+09 | 0.00 | 0.00 |
February | 0.784393E+09 | 0.496776E+09 | 0.737918E+09 | 0.450288E+09 | 0.287630E+09 | 0.00 | 0.00 |
March | 0.449884E+09 | 0.457880E+09 | 0.505111E+09 | 0.147066E+09 | 0.358046E+09 | 0.00 | 0.00 |
April | 0.120666E+10 | 0.385376E+09 | 0.101507E+10 | 0.458800E+09 | 0.556270E+09 | 0.00 | 0.00 |
May | 0.965026E+09 | 0.348647E+09 | 0.867542E+09 | 0.282443E+09 | 0.585099E+09 | 0.00 | 0.00 |
June | 0.874998E+09 | 0.278608E+09 | 0.773411E+09 | 0.187211E+09 | 0.586201E+09 | 0.00 | 0.00 |
July | 0.103875E+10 | 0.275454E+09 | 0.865909E+09 | 0.271169E+09 | 0.594740E+09 | 0.00 | 0.00 |
August | 0.127704E+10 | 0.305306E+09 | 0.101466E+10 | 0.456430E+09 | 0.558226E+09 | 0.00 | 0.00 |
September | 0.144848E+10 | 0.371073E+09 | 0.116038E+10 | 0.679769E+09 | 0.480609E+09 | 0.00 | 0.00 |
October | 0.939467E+09 | 0.449398E+09 | 0.823802E+09 | 0.481475E+09 | 0.342327E+09 | 0.00 | 0.00 |
November | 0.589515E+09 | 0.507154E+09 | 0.565234E+09 | 0.343846E+09 | 0.221388E+09 | 0.00 | 0.00 |
December | 0.463406E+09 | 0.647091E+09 | 0.462933E+09 | 0.296604E+09 | 0.166330E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.107305E+11 | 0.509242E+10 | 0.946090E+10 | 0.448813E+10 | 0.497277E+10 | 0.00 | 0.00 |
Minimum of Months | 0.449884E+09 | 0.275454E+09 | 0.462933E+09 | 0.147066E+09 | 0.166330E+09 | 0.00 | 0.00 |
Maximum of Months | 0.144848E+10 | 0.647091E+09 | 0.116038E+10 | 0.679769E+09 | 0.594740E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.700322E+09 | 0.532963E+09 | 0.668935E+09 | 0.433029E+09 | 0.235906E+09 | 0.00 | 0.00 |
February | 0.792792E+09 | 0.462274E+09 | 0.737918E+09 | 0.450288E+09 | 0.287630E+09 | 0.00 | 0.00 |
March | 0.459193E+09 | 0.424701E+09 | 0.505111E+09 | 0.147066E+09 | 0.358046E+09 | 0.00 | 0.00 |
April | 0.121452E+10 | 0.358818E+09 | 0.101507E+10 | 0.458800E+09 | 0.556270E+09 | 0.00 | 0.00 |
May | 0.976009E+09 | 0.320190E+09 | 0.867542E+09 | 0.282443E+09 | 0.585099E+09 | 0.00 | 0.00 |
June | 0.886162E+09 | 0.255581E+09 | 0.773411E+09 | 0.187211E+09 | 0.586201E+09 | 0.00 | 0.00 |
July | 0.104617E+10 | 0.256302E+09 | 0.865909E+09 | 0.271169E+09 | 0.594740E+09 | 0.00 | 0.00 |
August | 0.128214E+10 | 0.286758E+09 | 0.101466E+10 | 0.456430E+09 | 0.558226E+09 | 0.00 | 0.00 |
September | 0.145502E+10 | 0.347586E+09 | 0.116038E+10 | 0.679769E+09 | 0.480609E+09 | 0.00 | 0.00 |
October | 0.947588E+09 | 0.417871E+09 | 0.823802E+09 | 0.481475E+09 | 0.342327E+09 | 0.00 | 0.00 |
November | 0.595360E+09 | 0.474049E+09 | 0.565234E+09 | 0.343846E+09 | 0.221388E+09 | 0.00 | 0.00 |
December | 0.468458E+09 | 0.606747E+09 | 0.462933E+09 | 0.296604E+09 | 0.166330E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.108237E+11 | 0.474384E+10 | 0.946090E+10 | 0.448813E+10 | 0.497277E+10 | 0.00 | 0.00 |
Minimum of Months | 0.459193E+09 | 0.255581E+09 | 0.462933E+09 | 0.147066E+09 | 0.166330E+09 | 0.00 | 0.00 |
Maximum of Months | 0.145502E+10 | 0.606747E+09 | 0.116038E+10 | 0.679769E+09 | 0.594740E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.18 | 3.23 | 2.03 | 1.05 | -4.0 | 28.28 | 62.93 | 0.00 |
February | 4.25 | 3.55 | 2.74 | 1.60 | -5.0 | 43.80 | 86.73 | 0.02 |
March | 5.90 | 4.45 | 2.76 | 1.18 | -1.9 | 68.95 | 35.00 | 0.00 |
April | 8.96 | 6.24 | 3.38 | 1.56 | -0.7 | 96.13 | 186.12 | 0.00 |
May | 9.99 | 8.07 | 6.28 | 3.35 | -0.9 | 110.92 | 199.68 | 0.02 |
June | 13.31 | 11.27 | 9.70 | 3.33 | 3.35 | 121.69 | 199.28 | 0.00 |
July | 15.02 | 12.39 | 10.49 | 3.21 | 4.49 | 111.91 | 220.83 | 0.00 |
August | 15.65 | 12.75 | 10.65 | 2.92 | 3.95 | 91.47 | 211.91 | 0.00 |
September | 13.43 | 11.01 | 9.10 | 2.64 | 1.43 | 68.72 | 198.32 | 0.01 |
October | 9.33 | 8.03 | 6.81 | 1.97 | -1.0 | 48.92 | 91.86 | 0.04 |
November | 6.66 | 5.66 | 4.54 | 2.05 | -2.3 | 30.27 | 53.24 | 0.04 |
December | 4.10 | 3.14 | 1.95 | 2.36 | -5.1 | 20.52 | 40.74 | 0.04 |
Annual Sum or Average | 9.26 | 7.50 | 5.89 | 2.27 | -0.6 | 70.25 | 132.30 | 0.02 |
Minimum of Months | 4.10 | 3.14 | 1.95 | 1.05 | -5.1 | 20.52 | 35.00 | 0.00 |
Maximum of Months | 15.65 | 12.75 | 10.65 | 3.35 | 4.49 | 121.69 | 220.83 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 29-JAN-05:00 | 9.37 | 5.00 | 3.60 | 8.35 | 0.00 | 0.00 |
February | 11.00 | 07-FEB-14:00 | 9.86 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 14.00 | 25-MAR-12:00 | 11.22 | 9.00 | 2.60 | 7.35 | 287.00 | 93.00 |
April | 24.00 | 30-APR-14:00 | 13.13 | 4.00 | 1.50 | 7.75 | 167.50 | 716.00 |
May | 24.00 | 22-MAY-14:00 | 16.08 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 27.00 | 13-JUN-16:00 | 17.53 | 12.00 | 3.10 | 12.41 | 141.50 | 652.50 |
July | 30.00 | 22-JUL-17:00 | 16.80 | 8.00 | 0.00 | 14.28 | 122.00 | 407.00 |
August | 27.00 | 14-AUG-17:19 | 14.18 | 3.33 | 2.60 | 10.37 | 133.00 | 358.83 |
September | 23.00 | 11-SEP-16:00 | 16.22 | 12.00 | 2.60 | 8.74 | 108.00 | 325.50 |
October | 19.00 | 07-OCT-14:00 | 10.10 | 1.00 | 1.50 | 2.22 | 131.00 | 540.50 |
November | 16.00 | 24-NOV-11:00 | 12.01 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 13.00 | 23-DEC-10:00 | 7.64 | 2.00 | 7.70 | 6.75 | 70.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.00 | 7.64 | 1.00 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 17.53 | 12.00 | 7.70 | 14.28 | 287.00 | 769.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.0 | 10-JAN-07:00 | -7.0 | -9.0 | 0.00 | -20.0 | 0.00 | 0.00 |
February | -4.0 | 17-FEB-06:00 | -4.0 | -4.0 | 0.00 | -20.5 | 0.00 | 0.00 |
March | -1.0 | 08-MAR-06:00 | -1.4 | -2.0 | 0.00 | -14.4 | 17.50 | 184.50 |
April | 0.00 | 08-APR-04:00 | -0.9 | -2.0 | 0.00 | -12.7 | 0.00 | 0.00 |
May | 2.00 | 06-MAY-04:00 | 1.57 | 1.00 | 3.60 | -13.7 | 12.50 | 117.00 |
June | 6.00 | 01-JUN-03:00 | 5.05 | 4.00 | 0.00 | -9.2 | 0.00 | 0.00 |
July | 7.00 | 05-JUL-04:00 | 6.47 | 6.00 | 3.10 | -7.8 | 28.00 | 155.00 |
August | 8.00 | 20-AUG-04:00 | 7.45 | 7.00 | 0.00 | -6.6 | 0.00 | 0.00 |
September | 5.00 | 20-SEP-03:00 | 5.00 | 5.00 | 2.60 | -10.0 | 0.00 | 0.00 |
October | 2.00 | 07-OCT-03:00 | 2.00 | 2.00 | 0.00 | -13.4 | 0.00 | 0.00 |
November | -2.0 | 29-NOV-01:00 | -2.0 | -2.0 | 3.10 | -10.7 | 0.00 | 0.00 |
December | -3.0 | 29-DEC-20:00 | -4.5 | -7.0 | 3.60 | -20.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -6.0 | -7.0 | -9.0 | 0.00 | -20.5 | 0.00 | 0.00 | |
Maximum of Months | 8.00 | 7.45 | 7.00 | 3.60 | -6.6 | 28.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.44 | 29-JAN-04:00 | 13.00 | 12.00 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.86 | 07-FEB-14:00 | 11.00 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.39 | 28-APR-07:00 | 16.00 | 15.00 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 16.08 | 22-MAY-14:00 | 24.00 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 19.93 | 25-JUN-17:00 | 22.00 | 19.00 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 17.31 | 22-JUL-09:00 | 26.00 | 12.00 | 4.60 | 11.46 | 224.50 | 619.50 |
August | 17.06 | 14-AUG-12:00 | 24.00 | 13.00 | 2.60 | 9.91 | 205.50 | 669.50 |
September | 16.54 | 10-SEP-15:00 | 21.00 | 14.00 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.58 | 17-OCT-14:00 | 16.00 | 12.00 | 0.00 | 12.03 | 144.00 | 44.50 |
November | 12.01 | 24-NOV-11:00 | 16.00 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 7.93 | 02-DEC-12:00 | 9.00 | 7.00 | 0.00 | 2.01 | 135.50 | 84.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.93 | 9.00 | 7.00 | 0.00 | 2.01 | 0.00 | 0.00 | |
Maximum of Months | 19.93 | 26.00 | 19.00 | 4.60 | 15.94 | 224.50 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 29-JAN-04:00 | 13.00 | 12.44 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.00 | 07-FEB-14:00 | 11.00 | 9.86 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.00 | 28-APR-07:00 | 16.00 | 15.39 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 12.00 | 23-MAY-07:00 | 17.00 | 13.95 | 3.10 | 5.13 | 112.00 | 719.50 |
June | 19.00 | 25-JUN-17:00 | 22.00 | 19.93 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 14.00 | 17-JUL-17:00 | 18.00 | 15.45 | 3.60 | 9.91 | 120.00 | 0.00 |
August | 16.00 | 08-AUG-12:00 | 18.00 | 16.70 | 1.50 | 11.46 | 154.00 | 0.00 |
September | 14.00 | 10-SEP-15:00 | 21.00 | 16.54 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.00 | 17-OCT-18:00 | 13.00 | 13.00 | 2.60 | 9.33 | 0.00 | 0.00 |
November | 12.00 | 08-NOV-14:00 | 12.00 | 12.00 | 0.00 | 8.15 | 93.00 | 106.00 |
December | 7.00 | 02-DEC-11:00 | 8.00 | 7.45 | 3.10 | 1.16 | 144.50 | 146.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.00 | 8.00 | 7.45 | 0.00 | 1.16 | 0.00 | 0.00 | |
Maximum of Months | 19.00 | 22.00 | 19.93 | 3.60 | 15.94 | 160.50 | 719.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.33 | 8.85 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.00 | 14.79 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.33 | 17.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 11.26 | 40.86 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.54 | 47.73 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 13.82 | 50.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 14.77 | 51.67 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 15.12 | 44.67 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 14.78 | 34.25 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.84 | 17.71 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.55 | 9.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 11.27 | 6.14 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.57 | 28.73 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.00 | 6.14 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 15.12 | 51.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.363015E+09 | -238921553.3 | 0.00 | 0.00 | 744.00 | 0.00 | -124093686.1 | 58.99 | 0.00 | 0.00 |
February | 0.330643E+09 | -218406059.4 | 0.00 | 0.00 | 672.00 | 0.00 | -112237414.0 | 58.99 | 0.00 | 0.00 |
March | 0.368032E+09 | -244121707.8 | 0.00 | 0.00 | 744.00 | 0.00 | -123909809.9 | 58.99 | 0.00 | 0.00 |
April | 0.345994E+09 | -228768972.9 | 0.00 | 0.00 | 720.00 | 0.00 | -117225451.1 | 58.99 | 0.00 | 0.00 |
May | 0.350593E+09 | -230441315.1 | 0.00 | 0.00 | 744.00 | 0.00 | -120151762.0 | 58.99 | 0.00 | 0.00 |
June | 0.331080E+09 | -219059679.5 | 0.00 | 0.00 | 720.00 | 0.00 | -112020205.8 | 58.99 | 0.00 | 0.00 |
July | 0.331306E+09 | -217093749.3 | 0.00 | 0.00 | 744.00 | 0.00 | -114212305.7 | 58.99 | 0.00 | 0.00 |
August | 0.333537E+09 | -219928957.1 | 0.00 | 0.00 | 744.00 | 0.00 | -113608027.1 | 58.99 | 0.00 | 0.00 |
September | 0.323229E+09 | -212078239.2 | 0.00 | 0.00 | 720.00 | 0.00 | -111150876.9 | 58.99 | 0.00 | 0.00 |
October | 0.342994E+09 | -221708101.6 | 0.00 | 0.00 | 744.00 | 0.00 | -121286020.3 | 58.99 | 0.00 | 0.00 |
November | 0.339575E+09 | -220047616.0 | 0.00 | 0.00 | 720.00 | 0.00 | -119527860.7 | 58.99 | 0.00 | 0.00 |
December | 0.359090E+09 | -234599638.6 | 0.00 | 0.00 | 744.00 | 0.00 | -124490518.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.411909E+10 | -0.270518E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.141391E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.323229E+09 | -244121707.8 | 0.00 | 0.00 | 672.00 | 0.00 | -124490518.3 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.368032E+09 | -212078239.2 | 0.00 | 0.00 | 744.00 | 0.00 | -111150876.9 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.360758E+09 | -238920383.8 | 0.00 | 0.00 | 744.00 | 0.00 | -121837164.7 | 58.99 | 0.00 | 0.00 |
February | 0.328538E+09 | -218406655.9 | 0.00 | 0.00 | 672.00 | 0.00 | -110131352.1 | 58.99 | 0.00 | 0.00 |
March | 0.365591E+09 | -244118605.2 | 0.00 | 0.00 | 744.00 | 0.00 | -121472097.0 | 58.99 | 0.00 | 0.00 |
April | 0.342270E+09 | -228767813.3 | 0.00 | 0.00 | 720.00 | 0.00 | -113501800.3 | 58.99 | 0.00 | 0.00 |
May | 0.346863E+09 | -230440862.9 | 0.00 | 0.00 | 744.00 | 0.00 | -116422457.6 | 58.99 | 0.00 | 0.00 |
June | 0.328909E+09 | -219058922.6 | 0.00 | 0.00 | 720.00 | 0.00 | -109849754.0 | 58.99 | 0.00 | 0.00 |
July | 0.330067E+09 | -217090370.9 | 0.00 | 0.00 | 744.00 | 0.00 | -112976778.8 | 58.99 | 0.00 | 0.00 |
August | 0.332768E+09 | -219932261.2 | 0.00 | 0.00 | 744.00 | 0.00 | -112835283.7 | 58.99 | 0.00 | 0.00 |
September | 0.321662E+09 | -212063849.1 | 0.00 | 0.00 | 720.00 | 0.00 | -109597653.5 | 58.99 | 0.00 | 0.00 |
October | 0.339156E+09 | -221711180.7 | 0.00 | 0.00 | 744.00 | 0.00 | -117445134.1 | 58.99 | 0.00 | 0.00 |
November | 0.337110E+09 | -220050505.8 | 0.00 | 0.00 | 720.00 | 0.00 | -117059872.6 | 58.99 | 0.00 | 0.00 |
December | 0.356927E+09 | -234597435.1 | 0.00 | 0.00 | 744.00 | 0.00 | -122329120.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.409062E+10 | -0.270516E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.138546E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.321662E+09 | -244118605.2 | 0.00 | 0.00 | 672.00 | 0.00 | -122329120.2 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.365591E+09 | -212063849.1 | 0.00 | 0.00 | 744.00 | 0.00 | -109597653.5 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.333677E+09 | -210106145.0 | 0.00 | 0.00 | 744.00 | 0.00 | -123570916.7 | 58.99 | 0.00 | 0.00 |
February | 0.303824E+09 | -192214705.7 | 0.00 | 0.00 | 672.00 | 0.00 | -111609581.6 | 58.99 | 0.00 | 0.00 |
March | 0.340967E+09 | -217889884.4 | 0.00 | 0.00 | 744.00 | 0.00 | -123077138.0 | 58.99 | 0.00 | 0.00 |
April | 0.316017E+09 | -201192315.3 | 0.00 | 0.00 | 720.00 | 0.00 | -114824197.4 | 58.99 | 0.00 | 0.00 |
May | 0.321965E+09 | -204362425.7 | 0.00 | 0.00 | 744.00 | 0.00 | -117602205.9 | 58.99 | 0.00 | 0.00 |
June | 0.304810E+09 | -195107047.4 | 0.00 | 0.00 | 720.00 | 0.00 | -109702854.5 | 58.99 | 0.00 | 0.00 |
July | 0.302223E+09 | -189798735.5 | 0.00 | 0.00 | 744.00 | 0.00 | -112423940.5 | 58.99 | 0.00 | 0.00 |
August | 0.308651E+09 | -196437706.0 | 0.00 | 0.00 | 744.00 | 0.00 | -112213042.2 | 58.99 | 0.00 | 0.00 |
September | 0.295719E+09 | -186384734.4 | 0.00 | 0.00 | 720.00 | 0.00 | -109333782.5 | 58.99 | 0.00 | 0.00 |
October | 0.313977E+09 | -194971765.0 | 0.00 | 0.00 | 744.00 | 0.00 | -119005627.4 | 59.00 | 0.00 | 0.00 |
November | 0.313128E+09 | -194294651.2 | 0.00 | 0.00 | 720.00 | 0.00 | -118833765.9 | 58.99 | 0.00 | 0.00 |
December | 0.328821E+09 | -204816089.9 | 0.00 | 0.00 | 744.00 | 0.00 | -124005047.1 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.378378E+10 | -0.238758E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.139620E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.295719E+09 | -217889884.4 | 0.00 | 0.00 | 672.00 | 0.00 | -124005047.1 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.340967E+09 | -186384734.4 | 0.00 | 0.00 | 744.00 | 0.00 | -109333782.5 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.334111E+09 | -210110041.8 | 0.00 | 0.00 | 744.00 | 0.00 | -124001248.0 | 58.99 | 0.00 | 0.00 |
February | 0.304184E+09 | -192209080.0 | 0.00 | 0.00 | 672.00 | 0.00 | -111974596.3 | 58.99 | 0.00 | 0.00 |
March | 0.341363E+09 | -217879027.3 | 0.00 | 0.00 | 744.00 | 0.00 | -123484289.5 | 58.99 | 0.00 | 0.00 |
April | 0.316573E+09 | -201207610.8 | 0.00 | 0.00 | 720.00 | 0.00 | -115365115.8 | 58.99 | 0.00 | 0.00 |
May | 0.322485E+09 | -204371115.0 | 0.00 | 0.00 | 744.00 | 0.00 | -118113485.7 | 58.99 | 0.00 | 0.00 |
June | 0.305042E+09 | -195099871.9 | 0.00 | 0.00 | 720.00 | 0.00 | -109942025.6 | 58.99 | 0.00 | 0.00 |
July | 0.302352E+09 | -189798902.7 | 0.00 | 0.00 | 744.00 | 0.00 | -112552714.3 | 58.99 | 0.00 | 0.00 |
August | 0.308726E+09 | -196440176.9 | 0.00 | 0.00 | 744.00 | 0.00 | -112285818.0 | 58.99 | 0.00 | 0.00 |
September | 0.295877E+09 | -186381991.5 | 0.00 | 0.00 | 720.00 | 0.00 | -109494670.3 | 58.99 | 0.00 | 0.00 |
October | 0.314484E+09 | -194980176.5 | 0.00 | 0.00 | 744.00 | 0.00 | -119503606.2 | 58.99 | 0.00 | 0.00 |
November | 0.313544E+09 | -194291116.5 | 0.00 | 0.00 | 720.00 | 0.00 | -119252435.2 | 58.99 | 0.00 | 0.00 |
December | 0.329244E+09 | -204797876.9 | 0.00 | 0.00 | 744.00 | 0.00 | -124446069.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.378798E+10 | -0.238757E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.140042E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.295877E+09 | -217879027.3 | 0.00 | 0.00 | 672.00 | 0.00 | -124446069.9 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.341363E+09 | -186381991.5 | 0.00 | 0.00 | 744.00 | 0.00 | -109494670.3 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.323873E+09 | -198581315.2 | 0.00 | 0.00 | 744.00 | 0.00 | -125291238.5 | 58.99 | 0.00 | 0.00 |
February | 0.294856E+09 | -181764081.0 | 0.00 | 0.00 | 672.00 | 0.00 | -113092182.0 | 59.00 | 0.00 | 0.00 |
March | 0.330816E+09 | -206149844.9 | 0.00 | 0.00 | 744.00 | 0.00 | -124666613.6 | 59.00 | 0.00 | 0.00 |
April | 0.307670E+09 | -190388215.7 | 0.00 | 0.00 | 720.00 | 0.00 | -117281641.5 | 58.99 | 0.00 | 0.00 |
May | 0.313362E+09 | -193263199.1 | 0.00 | 0.00 | 744.00 | 0.00 | -120098783.0 | 58.99 | 0.00 | 0.00 |
June | 0.296349E+09 | -184612561.1 | 0.00 | 0.00 | 720.00 | 0.00 | -111736383.1 | 58.99 | 0.00 | 0.00 |
July | 0.293178E+09 | -179488913.8 | 0.00 | 0.00 | 744.00 | 0.00 | -113688840.4 | 59.00 | 0.00 | 0.00 |
August | 0.298913E+09 | -185823973.0 | 0.00 | 0.00 | 744.00 | 0.00 | -113088834.7 | 59.01 | 0.00 | 0.00 |
September | 0.287067E+09 | -176374035.0 | 0.00 | 0.00 | 720.00 | 0.00 | -110693427.2 | 58.99 | 0.00 | 0.00 |
October | 0.305640E+09 | -184276904.7 | 0.00 | 0.00 | 744.00 | 0.00 | -121363410.9 | 58.99 | 0.00 | 0.00 |
November | 0.303844E+09 | -183507183.9 | 0.00 | 0.00 | 720.00 | 0.00 | -120336349.9 | 58.99 | 0.00 | 0.00 |
December | 0.319515E+09 | -193676962.6 | 0.00 | 0.00 | 744.00 | 0.00 | -125838425.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.367508E+10 | -0.225791E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.141718E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.287067E+09 | -206149844.9 | 0.00 | 0.00 | 672.00 | 0.00 | -125838425.5 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.330816E+09 | -176374035.0 | 0.00 | 0.00 | 744.00 | 0.00 | -110693427.2 | 59.01 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.323796E+09 | -198583347.5 | 0.00 | 0.00 | 744.00 | 0.00 | -125213021.7 | 58.99 | 0.00 | 0.00 |
February | 0.294793E+09 | -181739706.6 | 0.00 | 0.00 | 672.00 | 0.00 | -113053769.7 | 59.00 | 0.00 | 0.00 |
March | 0.330739E+09 | -206148910.9 | 0.00 | 0.00 | 744.00 | 0.00 | -124589738.6 | 59.00 | 0.00 | 0.00 |
April | 0.307208E+09 | -190392066.3 | 0.00 | 0.00 | 720.00 | 0.00 | -116816216.8 | 58.99 | 0.00 | 0.00 |
May | 0.312786E+09 | -193259174.8 | 0.00 | 0.00 | 744.00 | 0.00 | -119526908.0 | 58.99 | 0.00 | 0.00 |
June | 0.295679E+09 | -184613162.1 | 0.00 | 0.00 | 720.00 | 0.00 | -111065691.8 | 58.99 | 0.00 | 0.00 |
July | 0.292873E+09 | -179488771.0 | 0.00 | 0.00 | 744.00 | 0.00 | -113383767.0 | 59.00 | 0.00 | 0.00 |
August | 0.298791E+09 | -185885616.3 | 0.00 | 0.00 | 744.00 | 0.00 | -112905362.8 | 58.99 | 0.00 | 0.00 |
September | 0.286619E+09 | -176372421.6 | 0.00 | 0.00 | 720.00 | 0.00 | -110246688.9 | 58.99 | 0.00 | 0.00 |
October | 0.305120E+09 | -184280557.4 | 0.00 | 0.00 | 744.00 | 0.00 | -120839820.8 | 58.99 | 0.00 | 0.00 |
November | 0.303763E+09 | -183506223.7 | 0.00 | 0.00 | 720.00 | 0.00 | -120256923.7 | 58.99 | 0.00 | 0.00 |
December | 0.319393E+09 | -193689076.2 | 0.00 | 0.00 | 744.00 | 0.00 | -125704069.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.367156E+10 | -0.225796E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.141360E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.286619E+09 | -206148910.9 | 0.00 | 0.00 | 672.00 | 0.00 | -125704069.2 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.330739E+09 | -176372421.6 | 0.00 | 0.00 | 744.00 | 0.00 | -110246688.9 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.323932E+09 | -198579409.9 | 0.00 | 0.00 | 744.00 | 0.00 | -125352704.8 | 58.99 | 0.00 | 0.00 |
February | 0.294918E+09 | -181784535.7 | 0.00 | 0.00 | 672.00 | 0.00 | -113133466.5 | 58.99 | 0.00 | 0.00 |
March | 0.330871E+09 | -206153971.8 | 0.00 | 0.00 | 744.00 | 0.00 | -124716586.6 | 58.99 | 0.00 | 0.00 |
April | 0.307393E+09 | -190393773.2 | 0.00 | 0.00 | 720.00 | 0.00 | -116998935.5 | 58.99 | 0.00 | 0.00 |
May | 0.312976E+09 | -193262643.8 | 0.00 | 0.00 | 744.00 | 0.00 | -119713334.6 | 58.99 | 0.00 | 0.00 |
June | 0.295859E+09 | -184607442.8 | 0.00 | 0.00 | 720.00 | 0.00 | -111251620.2 | 58.99 | 0.00 | 0.00 |
July | 0.292995E+09 | -179484351.8 | 0.00 | 0.00 | 744.00 | 0.00 | -113510692.5 | 59.00 | 0.00 | 0.00 |
August | 0.298897E+09 | -185843901.5 | 0.00 | 0.00 | 744.00 | 0.00 | -113052868.4 | 59.00 | 0.00 | 0.00 |
September | 0.286741E+09 | -176371890.7 | 0.00 | 0.00 | 720.00 | 0.00 | -110369120.6 | 58.99 | 0.00 | 0.00 |
October | 0.305315E+09 | -184280666.9 | 0.00 | 0.00 | 744.00 | 0.00 | -121034366.0 | 58.99 | 0.00 | 0.00 |
November | 0.303899E+09 | -183499452.0 | 0.00 | 0.00 | 720.00 | 0.00 | -120399980.0 | 58.99 | 0.00 | 0.00 |
December | 0.319523E+09 | -193680386.8 | 0.00 | 0.00 | 744.00 | 0.00 | -125842863.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.367332E+10 | -0.225794E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.141538E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.286741E+09 | -206153971.8 | 0.00 | 0.00 | 672.00 | 0.00 | -125842863.1 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.330871E+09 | -176371890.7 | 0.00 | 0.00 | 744.00 | 0.00 | -110369120.6 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 195.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 217.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 215.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 359.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 417.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 410.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 429.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 396.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 337.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 234.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 171.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 131.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3515.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 131.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 429.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.122923E+11 | 53805.54 | 01-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.102323E+11 | 53805.54 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.922519E+10 | 53805.54 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.211927E+10 | 53805.54 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.134102E+10 | 51697.99 | 06-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 26785763.19 | 5280.40 | 08-JUN-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 654360.37 | 657.79 | 08-SEP-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.250019E+10 | 53805.54 | 21-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.796055E+10 | 53805.54 | 03-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135176E+11 | 53805.54 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.592158E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.135176E+11 | 53805.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.297356E+10 | 28392.67 | 09-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.220414E+10 | 28392.67 | 17-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.178828E+10 | 18900.92 | 16-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.116285E+09 | 7118.68 | 01-APR-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15303236.12 | 1406.91 | 06-MAY-08:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.127292E+09 | 3218.44 | 28-OCT-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.141598E+10 | 24777.94 | 29-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.346104E+10 | 28392.67 | 28-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.121019E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.346104E+10 | 28392.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.400882E+10 | 27915.81 | 09-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.311879E+10 | 27915.81 | 13-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.268417E+10 | 20720.13 | 05-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.312502E+09 | 5571.40 | 08-APR-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 80030622.34 | 3003.08 | 17-MAY-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.396278E+09 | 5749.70 | 23-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.225602E+10 | 21887.82 | 29-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.446543E+10 | 27915.81 | 17-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173220E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.446543E+10 | 27915.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.424047E+10 | 27788.59 | 01-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.331415E+10 | 27788.59 | 13-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.289029E+10 | 25833.79 | 05-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.395423E+09 | 7117.10 | 08-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.124373E+09 | 3759.32 | 06-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.506986E+09 | 5192.27 | 23-OCT-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.247518E+10 | 26119.46 | 29-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.467498E+10 | 27788.59 | 03-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186219E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.467498E+10 | 27788.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.455258E+10 | 27903.42 | 01-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.358680E+10 | 27903.42 | 12-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.318729E+10 | 27903.42 | 05-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.511755E+09 | 6962.11 | 01-APR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.204147E+09 | 3547.16 | 17-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.654559E+09 | 8040.41 | 23-OCT-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.275165E+10 | 27903.42 | 28-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.498912E+10 | 27903.42 | 03-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.204379E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.498912E+10 | 27903.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.993317E+10 | 52471.63 | 01-JAN-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.800618E+10 | 52471.63 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.749348E+10 | 52471.63 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.174932E+10 | 52471.63 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.108613E+10 | 38925.95 | 17-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 19674479.84 | 3264.71 | 08-JUN-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.225278E+10 | 52471.63 | 19-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.667650E+10 | 52471.63 | 01-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.106967E+11 | 52471.63 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.479140E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.106967E+11 | 52471.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.442055E+10 | 27913.33 | 01-JAN-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.347581E+10 | 27913.33 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.311961E+10 | 27913.33 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.517495E+09 | 26607.91 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.245498E+09 | 5388.18 | 17-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1984.07 | 3.31 | 08-JUN-08:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.694828E+09 | 25942.01 | 23-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.272122E+10 | 27913.33 | 03-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.483295E+10 | 27913.33 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.200280E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.483295E+10 | 27913.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.453073E+10 | 27786.67 | 01-JAN-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.357986E+10 | 27786.67 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.322778E+10 | 27786.67 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.570612E+09 | 27786.67 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.284864E+09 | 8568.98 | 17-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 594981.93 | 316.62 | 08-JUN-08:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.755348E+09 | 27786.67 | 23-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.282624E+10 | 27786.67 | 03-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.492821E+10 | 27786.67 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.207042E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.492821E+10 | 27786.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.530671E+10 | 27539.63 | 01-JAN-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.426955E+10 | 27539.63 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.390560E+10 | 27539.63 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.886507E+09 | 27539.63 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.547588E+09 | 27539.63 | 04-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 14706297.47 | 16424.66 | 08-JUN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 485338.54 | 1617.80 | 05-JUL-08:65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.110182E+10 | 27539.63 | 11-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.341115E+10 | 27539.63 | 01-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.571046E+10 | 27539.63 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.251546E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.571046E+10 | 27539.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.657291E+10 | 28261.94 | 01-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.538289E+10 | 28261.94 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.503282E+10 | 28261.94 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.124721E+10 | 28261.94 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.886736E+09 | 28261.94 | 05-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 40341550.51 | 4722.05 | 08-JUN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 288110.83 | 377.16 | 05-JUL-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4164383.78 | 1016.18 | 08-SEP-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.164824E+10 | 28261.94 | 14-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.438844E+10 | 28261.94 | 01-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.707143E+10 | 28261.94 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.322755E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.707143E+10 | 28261.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.403401E+09 | 0.399666E+09 | 11317.60 | 30-APR-16:03 | 11317.60 | 0.00 |
May | 0.00 | 0.00 | 0.260421E+09 | 0.220324E+09 | 9103.42 | 22-MAY-15:00 | 8264.61 | 0.00 |
June | 0.00 | 0.00 | 0.170446E+10 | 0.140119E+10 | 30424.26 | 13-JUN-08:62 | 25185.14 | 0.00 |
July | 0.00 | 0.00 | 0.316561E+10 | 0.265539E+10 | 30581.87 | 18-JUL-08:62 | 20472.93 | 0.00 |
August | 0.00 | 0.00 | 0.314642E+10 | 0.255829E+10 | 19999.86 | 17-AUG-08:62 | 11541.19 | 0.00 |
September | 0.00 | 0.00 | 0.164188E+10 | 0.136596E+10 | 11771.93 | 13-SEP-16:10 | 10073.06 | 0.00 |
October | 0.00 | 0.00 | 6505.57 | 6505.57 | 10.84 | 07-OCT-15:00 | 10.84 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.103222E+11 | 0.860083E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.316561E+10 | 0.265539E+10 | 30581.87 | 25185.14 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 42502.68 | 33968.26 | 39.11 | 25-MAR-20:00 | 33.00 | 0.00 |
April | 0.00 | 0.00 | 0.256369E+09 | 0.255633E+09 | 15843.46 | 30-APR-19:07 | 15843.46 | 0.00 |
May | 0.00 | 0.00 | 0.166609E+09 | 0.152731E+09 | 15848.43 | 21-MAY-19:00 | 14346.77 | 0.00 |
June | 0.00 | 0.00 | 0.963523E+09 | 0.830701E+09 | 17464.33 | 25-JUN-18:00 | 10405.38 | 0.00 |
July | 0.00 | 0.00 | 0.159301E+10 | 0.140366E+10 | 16802.89 | 23-JUL-17:02 | 12221.96 | 0.00 |
August | 0.00 | 0.00 | 0.151830E+10 | 0.130418E+10 | 16676.21 | 17-AUG-08:62 | 9970.97 | 0.00 |
September | 0.00 | 0.00 | 0.896889E+09 | 0.780181E+09 | 16691.92 | 10-SEP-17:02 | 11196.88 | 0.00 |
October | 0.00 | 0.00 | 10714559.63 | 10026421.49 | 2639.40 | 03-OCT-20:10 | 2639.40 | 0.00 |
November | 0.00 | 0.00 | 115176.38 | 99683.97 | 94.81 | 05-NOV-19:20 | 87.38 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.540556E+10 | 0.473725E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.159301E+10 | 0.140366E+10 | 17464.33 | 15843.46 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.131766E+09 | 0.131349E+09 | 7030.22 | 30-APR-08:63 | 6530.14 | 0.00 |
May | 0.00 | 0.00 | 89581997.95 | 81627887.56 | 5286.83 | 22-MAY-15:00 | 5016.52 | 0.00 |
June | 0.00 | 0.00 | 0.757012E+09 | 0.658996E+09 | 16341.75 | 27-JUN-07:02 | 9073.17 | 0.00 |
July | 0.00 | 0.00 | 0.114407E+10 | 0.102241E+10 | 16339.98 | 18-JUL-07:02 | 10666.77 | 0.00 |
August | 0.00 | 0.00 | 0.116225E+10 | 0.100050E+10 | 16237.30 | 17-AUG-07:02 | 9555.96 | 0.00 |
September | 0.00 | 0.00 | 0.719243E+09 | 0.632302E+09 | 16036.16 | 16-SEP-07:03 | 9591.95 | 0.00 |
October | 0.00 | 0.00 | 358844.26 | 356941.86 | 317.33 | 07-OCT-15:00 | 317.33 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.400427E+10 | 0.352754E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.116225E+10 | 0.102241E+10 | 16341.75 | 10666.77 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.125641E+09 | 0.125273E+09 | 6216.69 | 30-APR-08:63 | 5769.85 | 0.00 |
May | 0.00 | 0.00 | 78944714.37 | 72349132.37 | 5062.97 | 22-MAY-15:00 | 4802.29 | 0.00 |
June | 0.00 | 0.00 | 0.738281E+09 | 0.642818E+09 | 16393.61 | 27-JUN-07:02 | 9096.85 | 0.00 |
July | 0.00 | 0.00 | 0.112243E+10 | 0.100395E+10 | 16391.39 | 18-JUL-07:02 | 10693.65 | 0.00 |
August | 0.00 | 0.00 | 0.113187E+10 | 0.975381E+09 | 16288.86 | 17-AUG-07:02 | 9582.24 | 0.00 |
September | 0.00 | 0.00 | 0.695411E+09 | 0.612071E+09 | 15371.75 | 16-SEP-07:03 | 9193.85 | 0.00 |
October | 0.00 | 0.00 | 316205.64 | 315851.89 | 187.43 | 07-OCT-15:00 | 187.43 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.389289E+10 | 0.343216E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.113187E+10 | 0.100395E+10 | 16393.61 | 10693.65 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.113533E+09 | 0.113259E+09 | 5891.51 | 30-APR-15:00 | 5891.51 | 0.00 |
May | 0.00 | 0.00 | 66033176.56 | 61023229.43 | 4760.61 | 22-MAY-15:00 | 4513.30 | 0.00 |
June | 0.00 | 0.00 | 0.696259E+09 | 0.606643E+09 | 16316.70 | 27-JUN-07:02 | 9031.44 | 0.00 |
July | 0.00 | 0.00 | 0.105838E+10 | 0.949690E+09 | 16314.28 | 18-JUL-07:02 | 10620.11 | 0.00 |
August | 0.00 | 0.00 | 0.105493E+10 | 0.911878E+09 | 16212.30 | 17-AUG-07:02 | 9514.20 | 0.00 |
September | 0.00 | 0.00 | 0.643008E+09 | 0.567474E+09 | 12511.82 | 16-SEP-07:03 | 7492.77 | 0.00 |
October | 0.00 | 0.00 | 83604.57 | 83574.70 | 37.01 | 11-OCT-15:20 | 37.01 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.363222E+10 | 0.321005E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.105838E+10 | 0.949690E+09 | 16316.70 | 10620.11 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.217909E+09 | 0.214584E+09 | 10168.83 | 30-APR-15:00 | 10168.83 | 0.00 |
May | 0.00 | 0.00 | 0.136000E+09 | 0.116410E+09 | 8367.49 | 22-MAY-15:00 | 7457.47 | 0.00 |
June | 0.00 | 0.00 | 0.128862E+10 | 0.106860E+10 | 29769.95 | 13-JUN-08:62 | 23802.27 | 0.00 |
July | 0.00 | 0.00 | 0.223968E+10 | 0.188747E+10 | 30289.85 | 18-JUL-08:62 | 20190.09 | 0.00 |
August | 0.00 | 0.00 | 0.258112E+10 | 0.209881E+10 | 25719.87 | 18-AUG-08:62 | 18907.02 | 0.00 |
September | 0.00 | 0.00 | 0.137887E+10 | 0.115784E+10 | 11362.16 | 13-SEP-14:20 | 9547.77 | 0.00 |
October | 0.00 | 0.00 | 3322516.03 | 3322516.03 | 1414.99 | 07-OCT-15:00 | 1414.99 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.784553E+10 | 0.654703E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.258112E+10 | 0.209881E+10 | 30289.85 | 23802.27 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.102641E+09 | 0.102418E+09 | 6018.90 | 30-APR-09:03 | 5961.61 | 0.00 |
May | 0.00 | 0.00 | 57947410.30 | 53701520.11 | 4932.95 | 22-MAY-15:00 | 4599.26 | 0.00 |
June | 0.00 | 0.00 | 0.651513E+09 | 0.564685E+09 | 16207.70 | 13-JUN-08:62 | 13026.64 | 0.00 |
July | 0.00 | 0.00 | 0.964650E+09 | 0.864487E+09 | 16199.28 | 18-JUL-08:62 | 10901.97 | 0.00 |
August | 0.00 | 0.00 | 0.986646E+09 | 0.853353E+09 | 16228.21 | 17-AUG-08:62 | 9670.28 | 0.00 |
September | 0.00 | 0.00 | 0.594499E+09 | 0.525043E+09 | 9568.57 | 13-SEP-08:62 | 6496.95 | 0.00 |
October | 0.00 | 0.00 | 80706.33 | 80706.33 | 134.51 | 07-OCT-15:00 | 134.51 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.335798E+10 | 0.296377E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.986646E+09 | 0.864487E+09 | 16228.21 | 13026.64 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 98852842.76 | 98649552.71 | 5908.91 | 30-APR-15:00 | 5908.91 | 0.00 |
May | 0.00 | 0.00 | 55034815.06 | 51102925.61 | 4835.77 | 22-MAY-15:00 | 4507.74 | 0.00 |
June | 0.00 | 0.00 | 0.632864E+09 | 0.548706E+09 | 16117.22 | 13-JUN-08:62 | 12936.77 | 0.00 |
July | 0.00 | 0.00 | 0.936246E+09 | 0.840418E+09 | 16109.10 | 18-JUL-08:62 | 10827.04 | 0.00 |
August | 0.00 | 0.00 | 0.948844E+09 | 0.822012E+09 | 16138.10 | 17-AUG-08:62 | 9602.92 | 0.00 |
September | 0.00 | 0.00 | 0.572917E+09 | 0.506495E+09 | 8016.69 | 13-SEP-08:62 | 5454.45 | 0.00 |
October | 0.00 | 0.00 | 27792.77 | 27792.77 | 46.32 | 07-OCT-15:00 | 46.32 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.324479E+10 | 0.286741E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.948844E+09 | 0.840418E+09 | 16138.10 | 12936.77 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.237015E+09 | 0.236998E+09 | 5609.40 | 30-APR-15:00 | 5609.40 | 0.00 |
May | 0.00 | 0.00 | 0.229711E+09 | 0.204695E+09 | 4561.58 | 22-MAY-15:00 | 4210.78 | 0.00 |
June | 0.00 | 0.00 | 0.108436E+10 | 0.959449E+09 | 7353.88 | 13-JUN-15:00 | 6480.62 | 0.00 |
July | 0.00 | 0.00 | 0.231275E+10 | 0.203565E+10 | 16003.76 | 23-JUL-09:01 | 14186.06 | 0.00 |
August | 0.00 | 0.00 | 0.292192E+10 | 0.255808E+10 | 6768.71 | 14-AUG-14:50 | 6233.87 | 0.00 |
September | 0.00 | 0.00 | 0.147908E+10 | 0.132252E+10 | 6273.55 | 13-SEP-14:40 | 5553.10 | 0.00 |
October | 0.00 | 0.00 | 28270758.26 | 28270758.26 | 2338.51 | 07-OCT-15:00 | 2338.51 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.829311E+10 | 0.734567E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.292192E+10 | 0.255808E+10 | 16003.76 | 14186.06 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 77404207.28 | 77331491.36 | 5419.73 | 30-APR-15:00 | 5419.73 | 0.00 |
May | 0.00 | 0.00 | 48039066.62 | 44634479.34 | 4409.35 | 22-MAY-15:00 | 4108.32 | 0.00 |
June | 0.00 | 0.00 | 0.563384E+09 | 0.490082E+09 | 7354.69 | 13-JUN-15:00 | 6479.19 | 0.00 |
July | 0.00 | 0.00 | 0.824063E+09 | 0.752798E+09 | 16589.40 | 22-JUL-08:62 | 15199.84 | 0.00 |
August | 0.00 | 0.00 | 0.754924E+09 | 0.660144E+09 | 6735.39 | 14-AUG-13:00 | 5791.26 | 0.00 |
September | 0.00 | 0.00 | 0.444062E+09 | 0.393716E+09 | 5668.34 | 13-SEP-14:20 | 4977.12 | 0.00 |
October | 0.00 | 0.00 | 7914.70 | 7914.70 | 13.19 | 07-OCT-16:30 | 13.19 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.271188E+10 | 0.241871E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.824063E+09 | 0.752798E+09 | 16589.40 | 15199.84 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.168636E+10 | 0.41 | 1953.47 | 01-JAN-09:02 | 0.89 |
February | 0.150615E+10 | 0.41 | 1953.47 | 01-FEB-09:01 | 0.88 |
March | 0.162481E+10 | 0.40 | 1953.47 | 01-MAR-09:01 | 0.89 |
April | 0.141890E+10 | 0.37 | 1953.47 | 01-APR-08:61 | 0.89 |
May | 0.144696E+10 | 0.37 | 1907.56 | 06-MAY-08:61 | 0.88 |
June | 0.137925E+10 | 0.36 | 1953.47 | 13-JUN-08:62 | 0.88 |
July | 0.141967E+10 | 0.36 | 1953.47 | 18-JUL-08:62 | 0.88 |
August | 0.142064E+10 | 0.36 | 1142.07 | 17-AUG-08:62 | 0.67 |
September | 0.137557E+10 | 0.36 | 795.72 | 08-SEP-09:00 | 0.54 |
October | 0.147221E+10 | 0.37 | 1953.47 | 21-OCT-08:61 | 0.89 |
November | 0.154362E+10 | 0.39 | 1953.47 | 03-NOV-08:61 | 0.89 |
December | 0.171877E+10 | 0.41 | 1953.47 | 01-DEC-09:01 | 0.89 |
Annual Sum or Average | 0.180129E+11 | 0.38 | |||
Minimum of Months | 0.137557E+10 | 0.36 | 795.72 | 0.54 | |
Maximum of Months | 0.171877E+10 | 0.41 | 1953.47 | 0.89 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.148882E+10 | 0.46 | 1096.86 | 01-JAN-09:08 | 0.91 |
February | 0.134651E+10 | 0.46 | 1096.86 | 01-FEB-09:06 | 0.91 |
March | 0.151244E+10 | 0.47 | 1096.86 | 12-MAR-13:30 | 0.92 |
April | 0.153641E+10 | 0.58 | 1096.86 | 01-APR-08:09 | 0.92 |
May | 0.164308E+10 | 0.59 | 1096.86 | 04-MAY-15:00 | 0.91 |
June | 0.179571E+10 | 0.62 | 1096.86 | 06-JUN-17:10 | 0.91 |
July | 0.190062E+10 | 0.61 | 1096.86 | 06-JUL-08:40 | 0.91 |
August | 0.193457E+10 | 0.61 | 1096.86 | 01-AUG-10:00 | 0.91 |
September | 0.181696E+10 | 0.62 | 1096.86 | 01-SEP-08:63 | 0.91 |
October | 0.155184E+10 | 0.56 | 1096.86 | 02-OCT-16:50 | 0.91 |
November | 0.144543E+10 | 0.47 | 1096.86 | 01-NOV-08:08 | 0.92 |
December | 0.148077E+10 | 0.46 | 1096.86 | 01-DEC-09:01 | 0.91 |
Annual Sum or Average | 0.194531E+11 | 0.54 | |||
Minimum of Months | 0.134651E+10 | 0.46 | 1096.86 | 0.91 | |
Maximum of Months | 0.193457E+10 | 0.62 | 1096.86 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.156391E+10 | 0.50 | 1080.64 | 01-JAN-12:10 | 0.92 |
February | 0.141608E+10 | 0.50 | 1080.64 | 01-FEB-08:10 | 0.92 |
March | 0.159503E+10 | 0.50 | 1080.64 | 01-MAR-09:50 | 0.92 |
April | 0.151722E+10 | 0.50 | 1080.64 | 02-APR-08:15 | 0.92 |
May | 0.157947E+10 | 0.50 | 1080.64 | 04-MAY-08:00 | 0.91 |
June | 0.154057E+10 | 0.50 | 1080.64 | 08-JUN-15:30 | 0.91 |
July | 0.155613E+10 | 0.49 | 1080.64 | 06-JUL-12:10 | 0.91 |
August | 0.159503E+10 | 0.50 | 1080.64 | 01-AUG-09:20 | 0.91 |
September | 0.151722E+10 | 0.49 | 1080.64 | 01-SEP-08:40 | 0.91 |
October | 0.156391E+10 | 0.49 | 1080.64 | 15-OCT-09:06 | 0.91 |
November | 0.151722E+10 | 0.50 | 1080.64 | 01-NOV-08:61 | 0.92 |
December | 0.155613E+10 | 0.49 | 1080.64 | 01-DEC-08:10 | 0.92 |
Annual Sum or Average | 0.185179E+11 | 0.50 | |||
Minimum of Months | 0.141608E+10 | 0.49 | 1080.64 | 0.91 | |
Maximum of Months | 0.159503E+10 | 0.50 | 1080.64 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.156894E+10 | 0.50 | 1084.12 | 01-JAN-12:00 | 0.92 |
February | 0.142063E+10 | 0.50 | 1084.12 | 01-FEB-13:00 | 0.91 |
March | 0.160016E+10 | 0.50 | 1084.12 | 02-MAR-10:03 | 0.92 |
April | 0.152210E+10 | 0.50 | 1084.12 | 01-APR-08:40 | 0.92 |
May | 0.158455E+10 | 0.50 | 1084.12 | 04-MAY-13:00 | 0.91 |
June | 0.154552E+10 | 0.50 | 1084.12 | 12-JUN-08:00 | 0.91 |
July | 0.156113E+10 | 0.49 | 1084.12 | 09-JUL-10:20 | 0.91 |
August | 0.160016E+10 | 0.50 | 1084.12 | 01-AUG-07:40 | 0.91 |
September | 0.152210E+10 | 0.49 | 1084.12 | 05-SEP-10:40 | 0.91 |
October | 0.156894E+10 | 0.49 | 1084.12 | 01-OCT-15:10 | 0.91 |
November | 0.152210E+10 | 0.50 | 1084.12 | 01-NOV-17:00 | 0.91 |
December | 0.156113E+10 | 0.49 | 1084.12 | 01-DEC-09:50 | 0.92 |
Annual Sum or Average | 0.185774E+11 | 0.50 | |||
Minimum of Months | 0.142063E+10 | 0.49 | 1084.12 | 0.91 | |
Maximum of Months | 0.160016E+10 | 0.50 | 1084.12 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.156195E+10 | 0.50 | 1079.29 | 01-JAN-10:40 | 0.92 |
February | 0.141431E+10 | 0.50 | 1079.29 | 01-FEB-09:06 | 0.91 |
March | 0.159304E+10 | 0.50 | 1079.29 | 01-MAR-09:00 | 0.92 |
April | 0.151533E+10 | 0.50 | 1079.29 | 01-APR-08:08 | 0.92 |
May | 0.157750E+10 | 0.50 | 1079.29 | 03-MAY-11:20 | 0.91 |
June | 0.153864E+10 | 0.50 | 1079.29 | 09-JUN-17:20 | 0.91 |
July | 0.155418E+10 | 0.49 | 1079.29 | 06-JUL-10:10 | 0.91 |
August | 0.159304E+10 | 0.50 | 1079.29 | 01-AUG-08:07 | 0.91 |
September | 0.151533E+10 | 0.49 | 1079.29 | 03-SEP-13:50 | 0.91 |
October | 0.156195E+10 | 0.49 | 1079.29 | 01-OCT-14:10 | 0.91 |
November | 0.151533E+10 | 0.50 | 1079.29 | 01-NOV-12:55 | 0.91 |
December | 0.155418E+10 | 0.49 | 1079.29 | 01-DEC-13:30 | 0.92 |
Annual Sum or Average | 0.184948E+11 | 0.50 | |||
Minimum of Months | 0.141431E+10 | 0.49 | 1079.29 | 0.91 | |
Maximum of Months | 0.159304E+10 | 0.50 | 1079.29 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.125273E+10 | 0.30 | 1933.76 | 01-JAN-10:01 | 0.89 |
February | 0.111266E+10 | 0.30 | 1933.76 | 01-FEB-09:01 | 0.88 |
March | 0.122106E+10 | 0.30 | 1933.76 | 01-MAR-09:01 | 0.89 |
April | 0.104114E+10 | 0.27 | 1933.76 | 01-APR-08:61 | 0.89 |
May | 0.106824E+10 | 0.27 | 1634.23 | 17-MAY-08:61 | 0.82 |
June | 0.101996E+10 | 0.27 | 1933.76 | 26-JUN-08:62 | 0.88 |
July | 0.102912E+10 | 0.26 | 1933.76 | 18-JUL-08:62 | 0.88 |
August | 0.105565E+10 | 0.27 | 1599.28 | 18-AUG-08:62 | 0.81 |
September | 0.100246E+10 | 0.27 | 773.50 | 23-SEP-09:40 | 0.53 |
October | 0.108290E+10 | 0.27 | 1933.76 | 19-OCT-08:61 | 0.88 |
November | 0.115009E+10 | 0.29 | 1933.76 | 01-NOV-08:61 | 0.89 |
December | 0.126405E+10 | 0.30 | 1933.76 | 01-DEC-09:01 | 0.89 |
Annual Sum or Average | 0.133001E+11 | 0.28 | |||
Minimum of Months | 0.100246E+10 | 0.26 | 773.50 | 0.53 | |
Maximum of Months | 0.126405E+10 | 0.30 | 1933.76 | 0.89 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.142770E+10 | 0.46 | 1068.96 | 01-JAN-10:50 | 0.92 |
February | 0.129301E+10 | 0.46 | 1068.96 | 01-FEB-09:04 | 0.92 |
March | 0.145849E+10 | 0.47 | 1068.96 | 01-MAR-09:04 | 0.92 |
April | 0.138537E+10 | 0.46 | 1068.96 | 01-APR-09:50 | 0.92 |
May | 0.144309E+10 | 0.46 | 1068.96 | 03-MAY-08:40 | 0.91 |
June | 0.140846E+10 | 0.46 | 1068.96 | 01-JUN-18:30 | 0.91 |
July | 0.142001E+10 | 0.45 | 1068.96 | 02-JUL-15:10 | 0.91 |
August | 0.145849E+10 | 0.46 | 1068.96 | 01-AUG-08:40 | 0.91 |
September | 0.138537E+10 | 0.46 | 1068.96 | 01-SEP-09:50 | 0.91 |
October | 0.142770E+10 | 0.46 | 1068.96 | 18-OCT-19:40 | 0.91 |
November | 0.138537E+10 | 0.46 | 1068.96 | 01-NOV-08:06 | 0.92 |
December | 0.142001E+10 | 0.45 | 1068.96 | 01-DEC-09:03 | 0.92 |
Annual Sum or Average | 0.169131E+11 | 0.46 | |||
Minimum of Months | 0.129301E+10 | 0.45 | 1068.96 | 0.91 | |
Maximum of Months | 0.145849E+10 | 0.47 | 1068.96 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.141997E+10 | 0.46 | 1063.17 | 04-JAN-09:06 | 0.92 |
February | 0.128601E+10 | 0.46 | 1063.17 | 01-FEB-10:30 | 0.91 |
March | 0.145059E+10 | 0.47 | 1063.17 | 01-MAR-14:20 | 0.91 |
April | 0.137787E+10 | 0.46 | 1063.17 | 01-APR-17:00 | 0.92 |
May | 0.143528E+10 | 0.46 | 1063.17 | 03-MAY-12:30 | 0.91 |
June | 0.140083E+10 | 0.46 | 1063.17 | 21-JUN-14:10 | 0.91 |
July | 0.141231E+10 | 0.45 | 1063.17 | 10-JUL-19:20 | 0.91 |
August | 0.145059E+10 | 0.46 | 1063.17 | 01-AUG-08:40 | 0.91 |
September | 0.137787E+10 | 0.46 | 1063.17 | 11-SEP-14:10 | 0.91 |
October | 0.141997E+10 | 0.46 | 1063.17 | 13-OCT-08:50 | 0.91 |
November | 0.137787E+10 | 0.46 | 1063.17 | 01-NOV-19:20 | 0.91 |
December | 0.141231E+10 | 0.45 | 1063.17 | 02-DEC-14:00 | 0.91 |
Annual Sum or Average | 0.168214E+11 | 0.46 | |||
Minimum of Months | 0.128601E+10 | 0.45 | 1063.17 | 0.91 | |
Maximum of Months | 0.145059E+10 | 0.47 | 1063.17 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.140603E+10 | 0.46 | 1052.74 | 16-JAN-13:00 | 0.92 |
February | 0.127339E+10 | 0.46 | 1052.74 | 07-FEB-16:30 | 0.91 |
March | 0.143635E+10 | 0.47 | 1052.74 | 09-MAR-10:30 | 0.92 |
April | 0.136435E+10 | 0.46 | 1052.74 | 04-APR-14:20 | 0.92 |
May | 0.142119E+10 | 0.46 | 1052.74 | 04-MAY-10:50 | 0.91 |
June | 0.138709E+10 | 0.46 | 1052.74 | 02-JUN-17:20 | 0.91 |
July | 0.139845E+10 | 0.45 | 1052.74 | 14-JUL-11:10 | 0.91 |
August | 0.143635E+10 | 0.46 | 1052.74 | 08-AUG-11:10 | 0.91 |
September | 0.136435E+10 | 0.46 | 1052.74 | 18-SEP-16:00 | 0.91 |
October | 0.140603E+10 | 0.46 | 1052.74 | 06-OCT-08:40 | 0.92 |
November | 0.136435E+10 | 0.46 | 1052.74 | 01-NOV-08:00 | 0.92 |
December | 0.139845E+10 | 0.45 | 1052.74 | 01-DEC-11:50 | 0.92 |
Annual Sum or Average | 0.166564E+11 | 0.46 | |||
Minimum of Months | 0.127339E+10 | 0.45 | 1052.74 | 0.91 | |
Maximum of Months | 0.143635E+10 | 0.47 | 1052.74 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.146785E+10 | 0.46 | 1099.02 | 02-JAN-12:30 | 0.92 |
February | 0.132937E+10 | 0.46 | 1099.02 | 01-FEB-09:20 | 0.92 |
March | 0.149950E+10 | 0.47 | 1099.02 | 01-MAR-18:20 | 0.92 |
April | 0.142433E+10 | 0.46 | 1099.02 | 01-APR-12:50 | 0.92 |
May | 0.148368E+10 | 0.46 | 1099.02 | 01-MAY-08:50 | 0.92 |
June | 0.144807E+10 | 0.46 | 1099.02 | 07-JUN-10:40 | 0.92 |
July | 0.145994E+10 | 0.45 | 1099.02 | 06-JUL-16:00 | 0.91 |
August | 0.149950E+10 | 0.46 | 1099.02 | 03-AUG-12:50 | 0.91 |
September | 0.142433E+10 | 0.46 | 1099.02 | 09-SEP-14:40 | 0.91 |
October | 0.146785E+10 | 0.46 | 1099.02 | 02-OCT-08:10 | 0.92 |
November | 0.142433E+10 | 0.46 | 1099.02 | 01-NOV-10:40 | 0.92 |
December | 0.145994E+10 | 0.45 | 1099.02 | 01-DEC-08:30 | 0.92 |
Annual Sum or Average | 0.173887E+11 | 0.46 | |||
Minimum of Months | 0.132937E+10 | 0.45 | 1099.02 | 0.91 | |
Maximum of Months | 0.149950E+10 | 0.47 | 1099.02 | 0.92 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.168636E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.150615E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.162481E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.151943E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.151468E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.179262E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.220743E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.221578E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.178500E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.147221E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.154362E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.171877E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.205869E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.147221E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.221578E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.148882E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.134651E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.151245E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.159172E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.167967E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.199965E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.224273E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.226406E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.201132E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.155437E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.144545E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.148077E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.206175E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.134651E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.226406E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.156391E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.141608E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.159503E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.154623E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.159962E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.170215E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.180485E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.185031E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.167451E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.156400E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.151722E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.155613E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.193900E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.141608E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.185031E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.156894E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.142063E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.160016E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.154982E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.160236E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.170343E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.180528E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.184901E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.167447E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.156901E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.152210E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.156113E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.194263E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.142063E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.184901E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.156195E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.141431E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.159304E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.154046E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.159243E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.168806E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.178484E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.182542E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.165666E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.156197E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.151533E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.155418E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.192887E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.141431E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.182542E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.125273E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.111266E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.122106E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.109653E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.110378E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.133745E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.158903E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.170744E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.134829E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.108382E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.115009E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.126405E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.152669E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.108382E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.170744E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.142770E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.129301E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.145849E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.140810E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.145616E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.154879E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.163035E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.167591E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.151620E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.142772E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.138537E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.142001E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.176478E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.129301E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.167591E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.141997E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.128601E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.145059E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.139980E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.144770E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.153738E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.161664E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.165995E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.150421E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.141997E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.137787E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.141231E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.175324E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.128601E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.165995E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.140603E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.127339E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.143635E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.141749E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.147386E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.162544E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.190732E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.207981E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.169068E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.141264E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.136435E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.139845E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.184858E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.127339E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.207981E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.146785E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.132937E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.149950E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.144166E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.149468E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.157120E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.163971E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.166799E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.152382E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.146785E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.142433E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.145994E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.179879E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.132937E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.166799E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.168636E+10 | 0.00 | 0.122923E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150615E+10 | 0.00 | 0.102323E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.162481E+10 | 0.00 | 0.922519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.141890E+10 | 0.403401E+09 | 0.211927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144696E+10 | 0.260421E+09 | 0.134102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.137925E+10 | 0.170446E+10 | 26785763.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.141967E+10 | 0.316561E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.142064E+10 | 0.314642E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.137557E+10 | 0.164188E+10 | 654360.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147221E+10 | 6505.57 | 0.250019E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.154362E+10 | 0.00 | 0.796055E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.171877E+10 | 0.00 | 0.135176E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.180129E+11 | 0.103222E+11 | 0.592158E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.137557E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.171877E+10 | 0.316561E+10 | 0.135176E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.148882E+10 | 0.00 | 0.297356E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134651E+10 | 0.00 | 0.220414E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.151244E+10 | 42502.68 | 0.178828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153641E+10 | 0.256369E+09 | 0.116285E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.164308E+10 | 0.166609E+09 | 15303236.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.179571E+10 | 0.963523E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.190062E+10 | 0.159301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.193457E+10 | 0.151830E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.181696E+10 | 0.896889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.155184E+10 | 10714559.63 | 0.127292E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144543E+10 | 115176.38 | 0.141598E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.148077E+10 | 0.00 | 0.346104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.194531E+11 | 0.540556E+10 | 0.121019E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.134651E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.193457E+10 | 0.159301E+10 | 0.346104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.156391E+10 | 0.00 | 0.400882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.141608E+10 | 0.00 | 0.311879E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159503E+10 | 0.00 | 0.268417E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.151722E+10 | 0.131766E+09 | 0.312502E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.157947E+10 | 89581997.95 | 80030622.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.154057E+10 | 0.757012E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.155613E+10 | 0.114407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.159503E+10 | 0.116225E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.151722E+10 | 0.719243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156391E+10 | 358844.26 | 0.396278E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.151722E+10 | 0.00 | 0.225602E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.155613E+10 | 0.00 | 0.446543E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.185179E+11 | 0.400427E+10 | 0.173220E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.141608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.159503E+10 | 0.116225E+10 | 0.446543E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.156894E+10 | 0.00 | 0.424047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142063E+10 | 0.00 | 0.331415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160016E+10 | 0.00 | 0.289029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152210E+10 | 0.125641E+09 | 0.395423E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.158455E+10 | 78944714.37 | 0.124373E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.154552E+10 | 0.738281E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.156113E+10 | 0.112243E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.160016E+10 | 0.113187E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152210E+10 | 0.695411E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156894E+10 | 316205.64 | 0.506986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152210E+10 | 0.00 | 0.247518E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.156113E+10 | 0.00 | 0.467498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.185774E+11 | 0.389289E+10 | 0.186219E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.142063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.160016E+10 | 0.113187E+10 | 0.467498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.156195E+10 | 0.00 | 0.455258E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.141431E+10 | 0.00 | 0.358680E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159304E+10 | 0.00 | 0.318729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.151533E+10 | 0.113533E+09 | 0.511755E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.157750E+10 | 66033176.56 | 0.204147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.153864E+10 | 0.696259E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.155418E+10 | 0.105838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.159304E+10 | 0.105493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.151533E+10 | 0.643008E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156195E+10 | 83604.57 | 0.654559E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.151533E+10 | 0.00 | 0.275165E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.155418E+10 | 0.00 | 0.498912E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.184948E+11 | 0.363222E+10 | 0.204379E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.141431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.159304E+10 | 0.105838E+10 | 0.498912E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.125273E+10 | 0.00 | 0.993317E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.111266E+10 | 0.00 | 0.800618E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.122106E+10 | 0.00 | 0.749348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.104114E+10 | 0.217909E+09 | 0.174932E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.106824E+10 | 0.136000E+09 | 0.108613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.101996E+10 | 0.128862E+10 | 19674479.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.102912E+10 | 0.223968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.105565E+10 | 0.258112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.100246E+10 | 0.137887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.108290E+10 | 3322516.03 | 0.225278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.115009E+10 | 0.00 | 0.667650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.126405E+10 | 0.00 | 0.106967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.133001E+11 | 0.784553E+10 | 0.479140E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.100246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.126405E+10 | 0.258112E+10 | 0.106967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.142770E+10 | 0.00 | 0.442055E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129301E+10 | 0.00 | 0.347581E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145849E+10 | 0.00 | 0.311961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138537E+10 | 0.102641E+09 | 0.517495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144309E+10 | 57947410.30 | 0.245498E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140846E+10 | 0.651513E+09 | 1984.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.142001E+10 | 0.964650E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145849E+10 | 0.986646E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138537E+10 | 0.594499E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.142770E+10 | 80706.33 | 0.694828E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138537E+10 | 0.00 | 0.272122E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142001E+10 | 0.00 | 0.483295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169131E+11 | 0.335798E+10 | 0.200280E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145849E+10 | 0.986646E+09 | 0.483295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.141997E+10 | 0.00 | 0.453073E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128601E+10 | 0.00 | 0.357986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145059E+10 | 0.00 | 0.322778E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137787E+10 | 98852842.76 | 0.570612E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.143528E+10 | 55034815.06 | 0.284864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140083E+10 | 0.632864E+09 | 594981.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.141231E+10 | 0.936246E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145059E+10 | 0.948844E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.137787E+10 | 0.572917E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.141997E+10 | 27792.77 | 0.755348E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137787E+10 | 0.00 | 0.282624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141231E+10 | 0.00 | 0.492821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168214E+11 | 0.324479E+10 | 0.207042E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.128601E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145059E+10 | 0.948844E+09 | 0.492821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.140603E+10 | 0.00 | 0.530671E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127339E+10 | 0.00 | 0.426955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143635E+10 | 0.00 | 0.390560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136435E+10 | 0.237015E+09 | 0.886507E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.142119E+10 | 0.229711E+09 | 0.547588E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.138709E+10 | 0.108436E+10 | 14706297.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.139845E+10 | 0.231275E+10 | 485338.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.143635E+10 | 0.292192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136435E+10 | 0.147908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140603E+10 | 28270758.26 | 0.110182E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136435E+10 | 0.00 | 0.341115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139845E+10 | 0.00 | 0.571046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.166564E+11 | 0.829311E+10 | 0.251546E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.143635E+10 | 0.292192E+10 | 0.571046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.146785E+10 | 0.00 | 0.657291E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.132937E+10 | 0.00 | 0.538289E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149950E+10 | 0.00 | 0.503282E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142433E+10 | 77404207.28 | 0.124721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.148368E+10 | 48039066.62 | 0.886736E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.144807E+10 | 0.563384E+09 | 40341550.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.145994E+10 | 0.824063E+09 | 288110.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.149950E+10 | 0.754924E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.142433E+10 | 0.444062E+09 | 4164383.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.146785E+10 | 7914.70 | 0.164824E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142433E+10 | 0.00 | 0.438844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.145994E+10 | 0.00 | 0.707143E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173887E+11 | 0.271188E+10 | 0.322755E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.132937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149950E+10 | 0.824063E+09 | 0.707143E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.168636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.162481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.141890E+10 | 0.00 | 0.00 | 0.00 | 0.100521E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144696E+10 | 0.00 | 0.00 | 0.00 | 67725267.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.137925E+10 | 0.00 | 0.00 | 0.00 | 0.413373E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.141967E+10 | 0.00 | 0.00 | 0.00 | 0.787756E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.142064E+10 | 0.00 | 0.00 | 0.00 | 0.795134E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.137557E+10 | 0.00 | 0.00 | 0.00 | 0.409430E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147221E+10 | 0.00 | 0.00 | 0.00 | 1838.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.154362E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.171877E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.180129E+11 | 0.00 | 0.00 | 0.00 | 0.257394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.137557E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.171877E+10 | 0.00 | 0.00 | 0.00 | 0.795134E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.148882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134651E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.151244E+10 | 0.00 | 0.00 | 0.00 | 10513.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153641E+10 | 0.00 | 0.00 | 0.00 | 55304296.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.164308E+10 | 0.00 | 0.00 | 0.00 | 36586446.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.179571E+10 | 0.00 | 0.00 | 0.00 | 0.203944E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.190062E+10 | 0.00 | 0.00 | 0.00 | 0.342114E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.193457E+10 | 0.00 | 0.00 | 0.00 | 0.329490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.181696E+10 | 0.00 | 0.00 | 0.00 | 0.194364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.155184E+10 | 0.00 | 0.00 | 0.00 | 2530982.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144543E+10 | 0.00 | 0.00 | 0.00 | 28448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.148077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.194531E+11 | 0.00 | 0.00 | 0.00 | 0.116437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.134651E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.193457E+10 | 0.00 | 0.00 | 0.00 | 0.342114E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.156391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.141608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.151722E+10 | 0.00 | 0.00 | 0.00 | 29004441.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.157947E+10 | 0.00 | 0.00 | 0.00 | 20150136.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.154057E+10 | 0.00 | 0.00 | 0.00 | 0.161580E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.155613E+10 | 0.00 | 0.00 | 0.00 | 0.248720E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.159503E+10 | 0.00 | 0.00 | 0.00 | 0.255281E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.151722E+10 | 0.00 | 0.00 | 0.00 | 0.157288E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156391E+10 | 0.00 | 0.00 | 0.00 | 87820.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.151722E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.155613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.185179E+11 | 0.00 | 0.00 | 0.00 | 0.872112E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.141608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.159503E+10 | 0.00 | 0.00 | 0.00 | 0.255281E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.156894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160016E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152210E+10 | 0.00 | 0.00 | 0.00 | 27718280.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.158455E+10 | 0.00 | 0.00 | 0.00 | 17812087.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.154552E+10 | 0.00 | 0.00 | 0.00 | 0.157907E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.156113E+10 | 0.00 | 0.00 | 0.00 | 0.244154E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.160016E+10 | 0.00 | 0.00 | 0.00 | 0.248856E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152210E+10 | 0.00 | 0.00 | 0.00 | 0.152371E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156894E+10 | 0.00 | 0.00 | 0.00 | 77761.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152210E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.156113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.185774E+11 | 0.00 | 0.00 | 0.00 | 0.848897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.142063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.160016E+10 | 0.00 | 0.00 | 0.00 | 0.248856E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.156195E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.141431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159304E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.151533E+10 | 0.00 | 0.00 | 0.00 | 25128870.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.157750E+10 | 0.00 | 0.00 | 0.00 | 14939613.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.153864E+10 | 0.00 | 0.00 | 0.00 | 0.149419E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.155418E+10 | 0.00 | 0.00 | 0.00 | 0.230657E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.159304E+10 | 0.00 | 0.00 | 0.00 | 0.232386E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.151533E+10 | 0.00 | 0.00 | 0.00 | 0.141336E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156195E+10 | 0.00 | 0.00 | 0.00 | 20665.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.151533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.155418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.184948E+11 | 0.00 | 0.00 | 0.00 | 0.793887E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.141431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.159304E+10 | 0.00 | 0.00 | 0.00 | 0.232386E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.125273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.111266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.122106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.104114E+10 | 0.00 | 0.00 | 0.00 | 55393926.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.106824E+10 | 0.00 | 0.00 | 0.00 | 35539220.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.101996E+10 | 0.00 | 0.00 | 0.00 | 0.317493E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.102912E+10 | 0.00 | 0.00 | 0.00 | 0.559911E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.105565E+10 | 0.00 | 0.00 | 0.00 | 0.651786E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.100246E+10 | 0.00 | 0.00 | 0.00 | 0.345833E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.108290E+10 | 0.00 | 0.00 | 0.00 | 918918.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.115009E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.126405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.133001E+11 | 0.00 | 0.00 | 0.00 | 0.196688E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.100246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.126405E+10 | 0.00 | 0.00 | 0.00 | 0.651786E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.142770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138537E+10 | 0.00 | 0.00 | 0.00 | 22729177.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144309E+10 | 0.00 | 0.00 | 0.00 | 13066957.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140846E+10 | 0.00 | 0.00 | 0.00 | 0.140330E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.142001E+10 | 0.00 | 0.00 | 0.00 | 0.210348E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145849E+10 | 0.00 | 0.00 | 0.00 | 0.217418E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138537E+10 | 0.00 | 0.00 | 0.00 | 0.130829E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.142770E+10 | 0.00 | 0.00 | 0.00 | 19782.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169131E+11 | 0.00 | 0.00 | 0.00 | 0.734741E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145849E+10 | 0.00 | 0.00 | 0.00 | 0.217418E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.141997E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128601E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137787E+10 | 0.00 | 0.00 | 0.00 | 21929495.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.143528E+10 | 0.00 | 0.00 | 0.00 | 12417869.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140083E+10 | 0.00 | 0.00 | 0.00 | 0.136547E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.141231E+10 | 0.00 | 0.00 | 0.00 | 0.204326E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145059E+10 | 0.00 | 0.00 | 0.00 | 0.209360E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.137787E+10 | 0.00 | 0.00 | 0.00 | 0.126343E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.141997E+10 | 0.00 | 0.00 | 0.00 | 6836.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137787E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168214E+11 | 0.00 | 0.00 | 0.00 | 0.710931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.128601E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145059E+10 | 0.00 | 0.00 | 0.00 | 0.209360E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.140603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143635E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136435E+10 | 0.00 | 0.00 | 0.00 | 53140802.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.142119E+10 | 0.00 | 0.00 | 0.00 | 52670499.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.138709E+10 | 0.00 | 0.00 | 0.00 | 0.238351E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.139845E+10 | 0.00 | 0.00 | 0.00 | 0.508864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.143635E+10 | 0.00 | 0.00 | 0.00 | 0.643457E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136435E+10 | 0.00 | 0.00 | 0.00 | 0.326333E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140603E+10 | 0.00 | 0.00 | 0.00 | 6609508.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139845E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.166564E+11 | 0.00 | 0.00 | 0.00 | 0.182943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.143635E+10 | 0.00 | 0.00 | 0.00 | 0.643457E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.146785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.132937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149950E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142433E+10 | 0.00 | 0.00 | 0.00 | 17327469.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.148368E+10 | 0.00 | 0.00 | 0.00 | 11000985.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.144807E+10 | 0.00 | 0.00 | 0.00 | 0.123128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.145994E+10 | 0.00 | 0.00 | 0.00 | 0.179778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.149950E+10 | 0.00 | 0.00 | 0.00 | 0.168484E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.142433E+10 | 0.00 | 0.00 | 0.00 | 99495160.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.146785E+10 | 0.00 | 0.00 | 0.00 | 1949.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142433E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.145994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173887E+11 | 0.00 | 0.00 | 0.00 | 0.599216E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.132937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149950E+10 | 0.00 | 0.00 | 0.00 | 0.179778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.841388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.622440E+10 | 0.00 | 0.00 | 0.52 |
February | 0.800847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.495886E+10 | 0.00 | 0.00 | 0.53 |
March | 0.839172E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450159E+10 | 0.00 | 0.00 | 0.53 |
April | 0.872728E+10 | 0.00 | 0.00 | 2091154.97 | 2029961.44 | 0.424528E+09 | 0.104858E+10 | 0.00 | 0.56 |
May | 0.860138E+10 | 114223.13 | 0.00 | 2235191.10 | 0.00 | 0.118443E+09 | 0.157339E+10 | 0.00 | 0.57 |
June | 0.456214E+10 | 67405207.80 | 0.00 | 6745478.38 | 1368286.09 | 626659.34 | 0.440361E+10 | 0.00 | 0.65 |
July | 0.194883E+10 | 92848389.77 | 0.00 | 13866682.75 | 1003636.24 | 0.00 | 0.723110E+10 | 0.00 | 0.78 |
August | 0.720615E+09 | 1289269.17 | 0.00 | 16805868.68 | 0.00 | 0.00 | 0.860534E+10 | 0.00 | 0.88 |
September | 0.300280E+10 | 0.00 | 0.00 | 9873631.61 | 0.00 | 0.00 | 0.622882E+10 | 0.00 | 0.71 |
October | 0.938620E+10 | 0.00 | 0.00 | 274764.34 | 0.00 | 0.557244E+09 | 0.368583E+09 | 0.00 | 0.53 |
November | 0.842411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363346E+10 | 0.00 | 0.00 | 0.52 |
December | 0.709319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.766524E+10 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 0.772806E+11 | 0.161657E+09 | 0.00 | 51892771.84 | 4401883.77 | 0.280844E+11 | 0.294594E+11 | 0.00 | 0.61 |
Minimum of Months | 0.720615E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.938620E+10 | 92848389.77 | 0.00 | 16805868.68 | 2029961.44 | 0.766524E+10 | 0.860534E+10 | 0.00 | 0.88 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.331243E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205712E+10 | 0.00 | 0.00 | 0.38 |
February | 0.346735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119577E+10 | 0.00 | 0.00 | 0.39 |
March | 0.377773E+10 | 0.00 | 0.00 | 1286.80 | 0.00 | 0.991110E+09 | 1232283.48 | 0.00 | 0.39 |
April | 0.302034E+10 | 176313.19 | 0.00 | 2089012.92 | 0.00 | 20695741.38 | 0.155744E+10 | 0.00 | 0.52 |
May | 0.281061E+10 | 9110.02 | 0.00 | 2518635.54 | 0.00 | 0.00 | 0.218071E+10 | 0.00 | 0.56 |
June | 0.568852E+09 | 26440046.99 | 0.00 | 6529310.86 | 362406.84 | 0.00 | 0.505142E+10 | 0.00 | 0.84 |
July | 0.134939E+09 | 41685414.40 | 0.00 | 9106577.79 | 500992.89 | 0.00 | 0.618641E+10 | 0.00 | 1.09 |
August | 36148705.97 | 196626.89 | 0.00 | 10451513.02 | 0.00 | 0.00 | 0.670319E+10 | 0.00 | 1.31 |
September | 0.237299E+09 | 0.00 | 0.00 | 8114305.19 | 0.00 | 0.00 | 0.592524E+10 | 0.00 | 1.00 |
October | 0.292770E+10 | 0.00 | 0.00 | 1622381.39 | 0.00 | 4844206.37 | 0.158716E+10 | 0.00 | 0.45 |
November | 0.388870E+10 | 0.00 | 0.00 | 2413.39 | 0.00 | 0.562397E+09 | 2092930.04 | 0.00 | 0.38 |
December | 0.252895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276158E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.267111E+11 | 68507511.48 | 0.00 | 40435436.90 | 863399.73 | 0.759353E+10 | 0.291949E+11 | 0.00 | 0.65 |
Minimum of Months | 36148705.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.388870E+10 | 41685414.40 | 0.00 | 10451513.02 | 500992.89 | 0.276158E+10 | 0.670319E+10 | 0.00 | 1.31 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.272264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279406E+10 | 0.00 | 0.00 | 0.41 |
February | 0.279757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201186E+10 | 0.00 | 0.00 | 0.41 |
March | 0.310866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179907E+10 | 0.00 | 0.00 | 0.42 |
April | 0.317986E+10 | 0.00 | 0.00 | 933299.05 | 490357.82 | 0.114914E+09 | 0.758920E+09 | 0.00 | 0.49 |
May | 0.318612E+10 | 15193.61 | 0.00 | 1132598.49 | 0.00 | 4461979.54 | 0.101711E+10 | 0.00 | 0.51 |
June | 0.107919E+10 | 16612968.70 | 0.00 | 3785574.99 | 0.00 | 0.00 | 0.294362E+10 | 0.00 | 0.67 |
July | 0.521507E+09 | 33315343.13 | 0.00 | 5754253.82 | 1853883.61 | 0.00 | 0.387508E+10 | 0.00 | 0.85 |
August | 0.336589E+09 | 199025.20 | 0.00 | 7044723.77 | 0.00 | 0.00 | 0.443767E+10 | 0.00 | 1.05 |
September | 0.715106E+09 | 0.00 | 0.00 | 5050972.05 | 0.00 | 0.00 | 0.362332E+10 | 0.00 | 0.80 |
October | 0.316709E+10 | 0.00 | 0.00 | 749516.97 | 0.00 | 57168996.00 | 0.838105E+09 | 0.00 | 0.44 |
November | 0.313199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141217E+10 | 0.00 | 0.00 | 0.41 |
December | 0.201545E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346685E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.259618E+11 | 50142530.63 | 0.00 | 24450939.13 | 2344241.43 | 0.116606E+11 | 0.174938E+11 | 0.00 | 0.57 |
Minimum of Months | 0.336589E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.318612E+10 | 33315343.13 | 0.00 | 7044723.77 | 1853883.61 | 0.346685E+10 | 0.443767E+10 | 0.00 | 1.05 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.245538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306037E+10 | 0.00 | 0.00 | 0.41 |
February | 0.251351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229542E+10 | 0.00 | 0.00 | 0.41 |
March | 0.280425E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210158E+10 | 0.00 | 0.00 | 0.42 |
April | 0.313588E+10 | 0.00 | 0.00 | 841022.44 | 526689.57 | 0.184351E+09 | 0.676366E+09 | 0.00 | 0.49 |
May | 0.317785E+10 | 13091.78 | 0.00 | 1042573.17 | 0.00 | 5438851.38 | 0.961089E+09 | 0.00 | 0.50 |
June | 0.116359E+10 | 16389328.18 | 0.00 | 3565111.57 | 0.00 | 0.00 | 0.279211E+10 | 0.00 | 0.66 |
July | 0.557857E+09 | 33262716.24 | 0.00 | 5614085.20 | 1870678.47 | 0.00 | 0.379855E+10 | 0.00 | 0.85 |
August | 0.341515E+09 | 186808.02 | 0.00 | 6936225.01 | 0.00 | 0.00 | 0.441398E+10 | 0.00 | 1.05 |
September | 0.737729E+09 | 0.00 | 0.00 | 4879820.11 | 0.00 | 0.00 | 0.354635E+10 | 0.00 | 0.79 |
October | 0.307806E+10 | 0.00 | 0.00 | 662155.28 | 0.00 | 0.161245E+09 | 0.769668E+09 | 0.00 | 0.44 |
November | 0.284932E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169081E+10 | 0.00 | 0.00 | 0.41 |
December | 0.180680E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367506E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.246218E+11 | 49851944.22 | 0.00 | 23540992.78 | 2397368.04 | 0.131743E+11 | 0.169581E+11 | 0.00 | 0.57 |
Minimum of Months | 0.341515E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.317785E+10 | 33262716.24 | 0.00 | 6936225.01 | 1870678.47 | 0.367506E+10 | 0.441398E+10 | 0.00 | 1.05 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.207643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343906E+10 | 0.00 | 0.00 | 0.41 |
February | 0.210507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270354E+10 | 0.00 | 0.00 | 0.41 |
March | 0.251554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238853E+10 | 0.00 | 0.00 | 0.42 |
April | 0.309499E+10 | 0.00 | 0.00 | 692327.90 | 611049.78 | 0.257638E+09 | 0.558601E+09 | 0.00 | 0.48 |
May | 0.316307E+10 | 10322.18 | 0.00 | 880135.96 | 0.00 | 32194680.38 | 0.843692E+09 | 0.00 | 0.49 |
June | 0.139861E+10 | 15889709.80 | 0.00 | 3026671.97 | 0.00 | 0.00 | 0.238238E+10 | 0.00 | 0.64 |
July | 0.656563E+09 | 33003198.62 | 0.00 | 5141893.53 | 1901010.61 | 0.00 | 0.355781E+10 | 0.00 | 0.83 |
August | 0.365471E+09 | 156622.40 | 0.00 | 6535899.76 | 0.00 | 0.00 | 0.427133E+10 | 0.00 | 1.03 |
September | 0.808916E+09 | 0.00 | 0.00 | 4425547.81 | 0.00 | 0.00 | 0.331564E+10 | 0.00 | 0.77 |
October | 0.298401E+10 | 0.00 | 0.00 | 477275.87 | 0.00 | 0.320293E+09 | 0.617109E+09 | 0.00 | 0.43 |
November | 0.256600E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197087E+10 | 0.00 | 0.00 | 0.41 |
December | 0.146970E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.401186E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.232044E+11 | 49059853.00 | 0.00 | 21179752.80 | 2512060.39 | 0.151240E+11 | 0.155466E+11 | 0.00 | 0.56 |
Minimum of Months | 0.365471E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.316307E+10 | 33003198.62 | 0.00 | 6535899.76 | 1901010.61 | 0.401186E+10 | 0.427133E+10 | 0.00 | 1.03 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.337169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.696804E+10 | 0.00 | 0.00 | 0.38 |
February | 0.376018E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.526175E+10 | 0.00 | 0.00 | 0.38 |
March | 0.469463E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453958E+10 | 0.00 | 0.00 | 0.39 |
April | 0.586582E+10 | 0.00 | 0.00 | 998563.79 | 1219043.71 | 0.402196E+09 | 0.666374E+09 | 0.00 | 0.41 |
May | 0.595558E+10 | 0.00 | 0.00 | 1180885.85 | 0.00 | 74664888.25 | 0.106244E+10 | 0.00 | 0.41 |
June | 0.345236E+10 | 23628574.39 | 0.00 | 3780170.68 | 0.00 | 0.00 | 0.257964E+10 | 0.00 | 0.47 |
July | 0.132198E+10 | 43615293.93 | 0.00 | 7979472.12 | 3063228.00 | 0.00 | 0.478979E+10 | 0.00 | 0.56 |
August | 0.435279E+09 | 40980.29 | 0.00 | 10882156.02 | 28673.88 | 0.00 | 0.595816E+10 | 0.00 | 0.66 |
September | 0.196678E+10 | 0.00 | 0.00 | 6357651.44 | 0.00 | 0.00 | 0.419633E+10 | 0.00 | 0.52 |
October | 0.614141E+10 | 0.00 | 0.00 | 243045.59 | 0.00 | 0.604012E+09 | 0.337582E+09 | 0.00 | 0.38 |
November | 0.469540E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383514E+10 | 0.00 | 0.00 | 0.38 |
December | 0.202888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.824314E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.436900E+11 | 67284848.61 | 0.00 | 31421945.49 | 4310945.59 | 0.299285E+11 | 0.195903E+11 | 0.00 | 0.44 |
Minimum of Months | 0.435279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.614141E+10 | 43615293.93 | 0.00 | 10882156.02 | 3063228.00 | 0.824314E+10 | 0.595816E+10 | 0.00 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.154826E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360957E+10 | 0.00 | 0.00 | 0.38 |
February | 0.173149E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276795E+10 | 0.00 | 0.00 | 0.38 |
March | 0.214723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245896E+10 | 0.00 | 0.00 | 0.39 |
April | 0.288110E+10 | 0.00 | 0.00 | 566059.30 | 509307.62 | 0.272209E+09 | 0.487574E+09 | 0.00 | 0.44 |
May | 0.291834E+10 | 0.00 | 0.00 | 744023.38 | 0.00 | 45336732.88 | 0.812259E+09 | 0.00 | 0.44 |
June | 0.130898E+10 | 10078376.80 | 0.00 | 2601257.77 | 0.00 | 0.00 | 0.220369E+10 | 0.00 | 0.58 |
July | 0.468875E+09 | 19591588.30 | 0.00 | 4641478.23 | 1273045.51 | 0.00 | 0.350626E+10 | 0.00 | 0.75 |
August | 0.112785E+09 | 0.00 | 0.00 | 5984707.09 | 13368.87 | 0.00 | 0.429934E+10 | 0.00 | 0.94 |
September | 0.565714E+09 | 0.00 | 0.00 | 3901942.76 | 0.00 | 0.00 | 0.327811E+10 | 0.00 | 0.70 |
October | 0.279071E+10 | 0.00 | 0.00 | 315340.88 | 0.00 | 0.356926E+09 | 0.505244E+09 | 0.00 | 0.39 |
November | 0.222286E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203123E+10 | 0.00 | 0.00 | 0.38 |
December | 0.913933E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420847E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.196103E+11 | 29669965.10 | 0.00 | 18754809.42 | 1795722.00 | 0.157507E+11 | 0.150925E+11 | 0.00 | 0.51 |
Minimum of Months | 0.112785E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.291834E+10 | 19591588.30 | 0.00 | 5984707.09 | 1273045.51 | 0.420847E+10 | 0.429934E+10 | 0.00 | 0.94 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.141013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374737E+10 | 0.00 | 0.00 | 0.38 |
February | 0.160402E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289494E+10 | 0.00 | 0.00 | 0.38 |
March | 0.201375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259185E+10 | 0.00 | 0.00 | 0.39 |
April | 0.285841E+10 | 0.00 | 0.00 | 540835.62 | 536221.51 | 0.292948E+09 | 0.469641E+09 | 0.00 | 0.43 |
May | 0.290970E+10 | 0.00 | 0.00 | 695919.62 | 0.00 | 62126358.77 | 0.772288E+09 | 0.00 | 0.44 |
June | 0.138587E+10 | 9934063.70 | 0.00 | 2437094.35 | 0.00 | 0.00 | 0.207289E+10 | 0.00 | 0.57 |
July | 0.499225E+09 | 19488566.21 | 0.00 | 4448832.91 | 1287058.69 | 0.00 | 0.341065E+10 | 0.00 | 0.74 |
August | 0.133237E+09 | 0.00 | 0.00 | 5781214.66 | 17987.53 | 0.00 | 0.421101E+10 | 0.00 | 0.93 |
September | 0.606359E+09 | 0.00 | 0.00 | 3708948.46 | 0.00 | 0.00 | 0.317204E+10 | 0.00 | 0.68 |
October | 0.278679E+10 | 0.00 | 0.00 | 260060.09 | 0.00 | 0.414913E+09 | 0.430096E+09 | 0.00 | 0.39 |
November | 0.208409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216933E+10 | 0.00 | 0.00 | 0.38 |
December | 0.809105E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431313E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.191007E+11 | 29422629.91 | 0.00 | 17872905.71 | 1841267.73 | 0.164866E+11 | 0.145386E+11 | 0.00 | 0.51 |
Minimum of Months | 0.133237E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.290970E+10 | 19488566.21 | 0.00 | 5781214.66 | 1287058.69 | 0.431313E+10 | 0.421101E+10 | 0.00 | 0.93 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.112038E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.445874E+10 | 0.00 | 0.00 | 0.41 |
February | 0.122601E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363990E+10 | 0.00 | 0.00 | 0.41 |
March | 0.175828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321358E+10 | 0.00 | 0.00 | 0.42 |
April | 0.301736E+10 | 0.00 | 0.00 | 442969.60 | 1087598.18 | 0.412521E+09 | 0.238299E+09 | 0.00 | 0.41 |
May | 0.310446E+10 | 0.00 | 0.00 | 535643.95 | 0.00 | 0.174199E+09 | 0.434996E+09 | 0.00 | 0.42 |
June | 0.190003E+10 | 9660096.87 | 0.00 | 1715654.57 | 0.00 | 2998542.44 | 0.104723E+10 | 0.00 | 0.42 |
July | 0.885136E+09 | 18569606.80 | 0.00 | 3534256.33 | 1777508.90 | 655337.57 | 0.151038E+10 | 0.00 | 0.41 |
August | 0.451802E+09 | 0.00 | 0.00 | 4843550.91 | 0.00 | 0.00 | 0.172025E+10 | 0.00 | 0.43 |
September | 0.117501E+10 | 0.00 | 0.00 | 2881279.02 | 0.00 | 0.00 | 0.157953E+10 | 0.00 | 0.42 |
October | 0.296091E+10 | 0.00 | 0.00 | 108527.99 | 0.00 | 0.729303E+09 | 0.141145E+09 | 0.00 | 0.41 |
November | 0.184734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274527E+10 | 0.00 | 0.00 | 0.41 |
December | 0.545701E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.499569E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.199924E+11 | 28229703.67 | 0.00 | 14061882.36 | 2865107.08 | 0.203729E+11 | 0.667184E+10 | 0.00 | 0.42 |
Minimum of Months | 0.451802E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.310446E+10 | 18569606.80 | 0.00 | 4843550.91 | 1777508.90 | 0.499569E+10 | 0.172025E+10 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 76845574.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507113E+10 | 0.00 | 0.00 | 0.38 |
February | 84282490.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.439774E+10 | 0.00 | 0.00 | 0.38 |
March | 0.298823E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.429126E+10 | 0.00 | 0.00 | 0.39 |
April | 0.226542E+10 | 0.00 | 0.00 | 408612.64 | 875251.65 | 0.836354E+09 | 0.391043E+09 | 0.00 | 0.43 |
May | 0.241255E+10 | 0.00 | 0.00 | 379782.09 | 0.00 | 0.629260E+09 | 0.470753E+09 | 0.00 | 0.42 |
June | 0.197289E+10 | 9552575.20 | 0.00 | 1412544.48 | 34764.58 | 10838210.56 | 0.109292E+10 | 0.00 | 0.54 |
July | 0.781111E+09 | 20544882.28 | 0.00 | 3116683.07 | 1311270.24 | 0.00 | 0.267986E+10 | 0.00 | 0.68 |
August | 0.316766E+09 | 0.00 | 0.00 | 4354843.02 | 0.00 | 0.00 | 0.358706E+10 | 0.00 | 0.85 |
September | 0.122852E+10 | 0.00 | 0.00 | 2312972.90 | 0.00 | 0.00 | 0.208574E+10 | 0.00 | 0.63 |
October | 0.193863E+10 | 0.00 | 0.00 | 44323.26 | 0.00 | 0.144094E+10 | 79135373.53 | 0.00 | 0.38 |
November | 0.466907E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375958E+10 | 0.00 | 0.00 | 0.38 |
December | 13630929.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.508195E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.118564E+11 | 30097457.48 | 0.00 | 12029761.46 | 2221286.47 | 0.255191E+11 | 0.103865E+11 | 0.00 | 0.49 |
Minimum of Months | 13630929.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.241255E+10 | 20544882.28 | 0.00 | 4354843.02 | 1311270.24 | 0.508195E+10 | 0.358706E+10 | 0.00 | 0.85 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:41:10
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.735701E+11 | 0.256671E+11 | 0.00 | 0.763744E+11 | 0.147079E+11 |
February | 0.125230E+12 | 0.229781E+11 | 0.00 | 0.672504E+11 | 0.117926E+11 |
March | 0.165085E+12 | 0.222071E+11 | 0.00 | 0.682298E+11 | 0.106387E+11 |
April | 0.453457E+12 | 0.167129E+11 | 0.00 | 0.539445E+11 | 0.427932E+10 |
May | 0.549412E+12 | 0.194944E+11 | 0.00 | 0.547118E+11 | 0.267416E+10 |
June | 0.563754E+12 | 0.148460E+11 | 0.00 | 0.493833E+11 | 0.111479E+11 |
July | 0.573267E+12 | 0.123872E+11 | 0.00 | 0.520158E+11 | 0.188777E+11 |
August | 0.468224E+12 | 0.101320E+11 | 0.00 | 0.554640E+11 | 0.199589E+11 |
September | 0.339845E+12 | 0.131829E+11 | 0.00 | 0.528768E+11 | 0.111507E+11 |
October | 0.142656E+12 | 0.185156E+11 | 0.00 | 0.544162E+11 | 0.271304E+10 |
November | 0.471562E+11 | 0.229554E+11 | 0.00 | 0.631607E+11 | 0.922087E+10 |
December | 0.567633E+10 | 0.281943E+11 | 0.00 | 0.761256E+11 | 0.160870E+11 |
Annual Sum or Average | 0.350733E+13 | 0.227273E+12 | 0.00 | 0.723953E+12 | 0.133249E+12 |
Minimum of Months | 0.567633E+10 | 0.101320E+11 | 0.00 | 0.493833E+11 | 0.267416E+10 |
Maximum of Months | 0.573267E+12 | 0.281943E+11 | 0.00 | 0.763744E+11 | 0.199589E+11 |