Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:41
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Simulation Timestamp: 2023-10-16 08:41:13
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 981.11 | 469.36 | 469.36 |
Net Site Energy | 981.11 | 469.36 | 469.36 |
Total Source Energy | 3102.08 | 1484.02 | 1484.02 |
Net Source Energy | 3102.08 | 1484.02 | 1484.02 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 2.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 66.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 441.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 100.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 179.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 62.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 978.66 | 2.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 2.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 66.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 441.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 100.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 179.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 62.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 2.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 66.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 441.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 100.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 179.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 62.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 259.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 147.52 | 1.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 468.19 | 1.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 259.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 147.52 | 1.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 468.19 | 1.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 978.665 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 978.665 | 100.00 |
Total On-Site and Utility Electric Sources | 978.665 | 100.00 |
Total Electricity End Uses | 978.665 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 289.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:41 |
RunPeriod | RUNPERIOD 1 |
Weather File | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Latitude [deg] | 32.58 |
Longitude [deg] | -117.0 |
Elevation [m] | 159.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.77 | 20.77 | 17.8770 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.38 | 10.38 | 19.3382 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 17.3739 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 17.3739 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 17.3739 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.72 | 20.72 | 13.1675 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.3365 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.3365 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.3365 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.36 | 10.36 | 13.3365 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 15.5746 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 15.5746 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 17.8770 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 19.3382 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 17.3739 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 17.3739 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 17.3739 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 13.1675 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 13.3365 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 13.3365 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 13.3365 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 13.3365 | 6.19 | 4.3000 | |
Total | 2090.32 | 15.5746 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 15.5746 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 15.5746 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 16-OCT-11:30 | 30-MAR-08:09 | - | - | - | - | - | - | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 48795.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 37865.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 27522.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 11518.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4841.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 89836.85 | 48795.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 48795.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 37865.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 27522.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 11518.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 4841.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 2.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 211.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1398.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 316.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 407.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 567.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 197.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3099.43 | 2.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 101.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 668.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 151.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 271.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 94.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1482.76 | 1.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 101.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 668.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 151.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 271.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 94.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1482.76 | 1.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 1.92 |
SMSTORE1 DIRECT AIR | 0.994699 |
SMSTORE2 DIRECT AIR | 0.988142 |
SMSTORE3 DIRECT AIR | 0.981801 |
SMSTORE4 DIRECT AIR | 0.987082 |
LGSTORE2 DIRECT AIR | 1.79 |
SMSTORE5 DIRECT AIR | 0.971419 |
SMSTORE6 DIRECT AIR | 0.966527 |
SMSTORE7 DIRECT AIR | 0.961672 |
SMSTORE8 DIRECT AIR | 1.05 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 1.92 | 1.92 | 1.92 | 1.92 | 1.92 | 1.92 | 1.00 | 1.000000 | 1.92 |
PSZ-AC_2:2 | 0.994699 | 0.994699 | 0.994699 | 0.994699 | 1.01 | 1.01 | 1.00 | 0.987808 | 1.01 |
PSZ-AC_3:3 | 0.988142 | 0.988142 | 0.988142 | 0.988142 | 1.00 | 1.00 | 1.00 | 0.984141 | 1.00 |
PSZ-AC_4:4 | 0.981801 | 0.981801 | 0.981801 | 0.981801 | 1.01 | 1.01 | 1.00 | 0.974867 | 1.01 |
PSZ-AC_5:5 | 0.987082 | 0.987082 | 0.987082 | 0.987082 | 1.00 | 1.00 | 1.00 | 0.984573 | 1.00 |
PSZ-AC_6:6 | 1.79 | 1.79 | 1.79 | 1.79 | 1.84 | 1.84 | 1.00 | 0.971769 | 1.84 |
PSZ-AC_7:7 | 0.971419 | 0.971419 | 0.971419 | 0.971419 | 0.972843 | 0.972843 | 1.00 | 0.998537 | 0.972843 |
PSZ-AC_8:8 | 0.966527 | 0.966527 | 0.966527 | 0.966527 | 0.968306 | 0.968306 | 1.00 | 0.998162 | 0.968306 |
PSZ-AC_9:9 | 0.961672 | 0.961672 | 0.961672 | 0.961672 | 0.964333 | 0.964333 | 1.00 | 0.997241 | 0.964333 |
PSZ-AC_10:10 | 1.05 | 1.05 | 1.05 | 1.05 | 1.06 | 1.06 | 1.00 | 0.991644 | 1.06 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 1.92 | 0.411479 |
PSZ-AC_2:2_OA_CONTROLLER | 1.01 | 0.205739 |
PSZ-AC_3:3_OA_CONTROLLER | 1.00 | 0.205739 |
PSZ-AC_4:4_OA_CONTROLLER | 1.01 | 0.205739 |
PSZ-AC_5:5_OA_CONTROLLER | 1.00 | 0.205739 |
PSZ-AC_6:6_OA_CONTROLLER | 1.84 | 0.411479 |
PSZ-AC_7:7_OA_CONTROLLER | 0.972843 | 0.205739 |
PSZ-AC_8:8_OA_CONTROLLER | 0.968306 | 0.205739 |
PSZ-AC_9:9_OA_CONTROLLER | 0.964333 | 0.205739 |
PSZ-AC_10:10_OA_CONTROLLER | 1.06 | 0.205739 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 1.92 | 2050.05 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.01 | 1114.88 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.00 | 1111.66 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.01 | 1115.03 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.00 | 1109.98 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 1.84 | 1973.32 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 0.972843 | 1077.09 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 0.968306 | 1072.07 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 0.964333 | 1067.67 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.06 | 1174.29 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 1.92 | 1.92 | 1.92 | 1.26 | 33585.54 | 51437.64 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.01 | 1.01 | 1.01 | 1.01 | 17552.72 | 26543.71 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.00 | 1.00 | 1.00 | 1.00 | 17482.21 | 26396.60 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.01 | 1.01 | 1.01 | 1.01 | 17529.73 | 26254.35 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.00 | 1.00 | 1.00 | 1.00 | 17459.13 | 26372.81 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 1.84 | 1.84 | 1.84 | 1.22 | 32462.81 | 49109.54 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 0.972843 | 0.972843 | 0.972843 | 0.972843 | 17000.53 | 26221.97 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 0.968306 | 0.968306 | 0.968306 | 0.968306 | 16931.58 | 26111.28 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 0.964333 | 0.964333 | 0.964333 | 0.964333 | 16866.91 | 26005.19 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.06 | 1.06 | 1.06 | 1.06 | 18254.89 | 28006.44 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 1.92 | 0.957926 | 1.28 | 33585.54 | 16792.77 | 0.800170 | 0.800170 |
PSZ-AC_2:2 COOLING COIL | 1.01 | 0.503488 | 0.671320 | 17552.72 | 8776.36 | 0.800150 | 0.800150 |
PSZ-AC_3:3 COOLING COIL | 1.00 | 0.502033 | 0.669380 | 17482.21 | 8741.10 | 0.800540 | 0.800540 |
PSZ-AC_4:4 COOLING COIL | 1.01 | 0.503556 | 0.671407 | 17529.73 | 8764.86 | 0.800650 | 0.800650 |
PSZ-AC_5:5 COOLING COIL | 1.00 | 0.501274 | 0.668367 | 17459.13 | 8729.57 | 0.800470 | 0.800470 |
PSZ-AC_6:6 COOLING COIL | 1.84 | 0.922072 | 1.23 | 32462.81 | 16231.41 | 0.800730 | 0.800730 |
PSZ-AC_7:7 COOLING COIL | 0.972840 | 0.486421 | 0.648560 | 17000.53 | 8500.26 | 0.800270 | 0.800270 |
PSZ-AC_8:8 COOLING COIL | 0.968310 | 0.484153 | 0.645540 | 16931.58 | 8465.79 | 0.800050 | 0.800050 |
PSZ-AC_9:9 COOLING COIL | 0.964330 | 0.482166 | 0.642887 | 16866.91 | 8433.45 | 0.800960 | 0.800960 |
PSZ-AC_10:10 COOLING COIL | 1.06 | 0.530317 | 0.707087 | 18254.89 | 9127.44 | 0.800600 | 0.800600 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 51437.64 |
PSZ-AC_2:2 HEATING COIL | 26543.71 |
PSZ-AC_3:3 HEATING COIL | 26396.60 |
PSZ-AC_4:4 HEATING COIL | 26254.35 |
PSZ-AC_5:5 HEATING COIL | 26372.81 |
PSZ-AC_6:6 HEATING COIL | 49109.54 |
PSZ-AC_7:7 HEATING COIL | 26221.97 |
PSZ-AC_8:8 HEATING COIL | 26111.28 |
PSZ-AC_9:9 HEATING COIL | 26005.19 |
PSZ-AC_10:10 HEATING COIL | 28006.44 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.80 | 14.30 | 13.60 | 13.20 | 13.30 | 12.60 | 15.30 | 15.60 | 17.70 | 19.40 | 19.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 | 32.58 | -116.98 | -8.00 | 159.00 | 99429 | 1.1818 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.00 | 7.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.74 | 20.77 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.66 | 10.38 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.41 | 20.72 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.12 | 10.36 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 17.877 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.177 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 19.338 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 23.638 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 17.374 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.674 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 17.374 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.674 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 17.374 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.674 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 13.168 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.468 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 13.336 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.636 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 13.336 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.636 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 13.336 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.636 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 13.336 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.636 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 4596.695 | 13.194 | 81.718 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4596.695 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 1631.408 | 4.683 | 29.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1631.408 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 2327.780 | 13.363 | 82.767 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2327.780 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1040.795 | 5.975 | 37.007 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1040.795 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 2323.122 | 13.336 | 82.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2323.122 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 703.295 | 4.037 | 25.007 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 703.295 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 2323.122 | 13.336 | 82.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2323.122 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 703.295 | 4.037 | 25.007 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 703.295 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 2323.122 | 13.336 | 82.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2323.122 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 703.295 | 4.037 | 25.007 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 703.295 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 4587.379 | 13.168 | 81.553 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4587.379 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 2323.122 | 13.336 | 82.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2323.122 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 2323.122 | 13.336 | 82.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2323.122 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 2323.122 | 13.336 | 82.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2323.122 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 2323.122 | 13.336 | 82.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2323.122 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.6641 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1995 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2888 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.272 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.937 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.386 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
19 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
20 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
21 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
22 | 7 | -0.32972738E-12 | 0.11763143E-14 | -0.10490290E-12 | 0.10060316E-15 |
23 | 6 | 0.30001920E-07 | 0.18927851E-09 | 0.68616814E-08 | -0.14235861E-12 |
24 | 5 | -0.19683904E-03 | 0.16062604E-05 | -0.10115234E-03 | 0.67789156E-08 |
25 | 4 | 0.29998857 | 0.77587294E-03 | 0.10250533 | -0.34681058E-04 |
26 | 3 | -7.4215481 | 0.23875067E-01 | -2.3849775 | 0.29769922E-01 |
27 | 2 | 41.382972 | 0.84366340E-01 | 15.453844 | -0.33904133 |
28 | 1 | -80.937908 | 0.37867119E-01 | -29.310851 | 1.0869756 |
29 | 0 | 46.824336 | 0.75775345E-03 | 16.287225 | |
30 | 7 | -0.21163652E-08 | -0.68723841E-15 | 0.43910983E-14 | -0.57684426E-16 |
31 | 6 | 0.56109385E-05 | 0.38186281E-08 | 0.31898696E-02 | -0.26759299E-04 |
32 | 5 | -0.40164657E-03 | 0.22608617E-05 | -0.22372456 | 0.19561502E-02 |
33 | 4 | 0.92272104E-02 | 0.10289840E-03 | 4.8295456 | -0.45264980E-01 |
34 | 3 | -0.80993241E-01 | 0.81813938E-03 | -38.021416 | 0.39865375 |
35 | 2 | 0.28754352 | 0.13608947E-02 | 116.48395 | -1.4179393 |
36 | 1 | -0.41499682 | 0.41453381E-03 | -143.90731 | 2.0490399 |
37 | 0 | 0.20232414 | 0.10048102E-04 | 60.838472 | |
38 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
39 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
40 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
41 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
42 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
43 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
44 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
45 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
46 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
47 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
48 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
49 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
50 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
51 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
52 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
53 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
54 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
55 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
56 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
57 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
58 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
59 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
60 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
61 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
62 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
63 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
64 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
65 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
66 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
67 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
68 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
69 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
70 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
71 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
72 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
73 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
74 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
75 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
76 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
77 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
78 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
79 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
80 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
81 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
82 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
83 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
84 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
85 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
86 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
87 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
88 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
89 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
90 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
91 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
92 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
93 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
94 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479936E-14 | -0.41635794E-16 |
95 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
96 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
97 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
98 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
99 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
100 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
101 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
102 | 7 | -0.14484255E-08 | -0.22640907E-15 | 0.11860658E-13 | -0.17473455E-15 |
103 | 6 | 0.80640390E-05 | 0.55493782E-08 | 0.31828288E-02 | -0.26700235E-04 |
104 | 5 | -0.58275339E-03 | 0.32892043E-05 | -0.22332434 | 0.19526176E-02 |
105 | 4 | 0.13421983E-01 | 0.14977251E-03 | 4.8228790 | -0.45200897E-01 |
106 | 3 | -0.11791368 | 0.11914425E-02 | -37.983753 | 0.39823745 |
107 | 2 | 0.41875064 | 0.19825898E-02 | 116.41064 | -1.4169588 |
108 | 1 | -0.60444169 | 0.60433957E-03 | -143.86415 | 2.0483306 |
109 | 0 | 0.29470347 | 0.14596444E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.463_SHGC_0.25 | 35 | 1 | VerySmooth | 2.632 | 2.632 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.49960E-002 | 0.16139 | 0.61571 | 0.61571 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.11953 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 0.157 | 4.517E-004 | 2.488E-004 | 0.314 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 3.813E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 8.993E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 4.692E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 0.112 | 6.453E-004 | 2.994E-004 | 0.448 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 3.583E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 21352.71273 | 25623.25528 | 1.59654 | 1.91585 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 31.30000 | 8.23349E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 14026.15221 | 16831.38265 | 0.59900 | 0.71880 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 3.80000 | 5.05843E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 11416.77010 | 13700.12412 | 0.82892 | 0.99470 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 27.91800 | 8.22813E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 6432.29467 | 7718.75360 | 0.28255 | 0.33906 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 3.80000 | 5.05843E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 11346.02614 | 13615.23137 | 0.82345 | 0.98814 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 26.40500 | 8.22575E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 6504.21907 | 7805.06288 | 0.28571 | 0.34285 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 3.80000 | 5.05843E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 11275.49337 | 13530.59204 | 0.81817 | 0.98180 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 26.40500 | 8.22575E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 6577.26818 | 7892.72181 | 0.28892 | 0.34670 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 3.80000 | 5.05843E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 11334.23864 | 13601.08637 | 0.82257 | 0.98708 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 26.40500 | 8.22575E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 6728.13675 | 8073.76411 | 0.29554 | 0.35465 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 3.80000 | 5.05843E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 20630.11020 | 24756.13224 | 1.49340 | 1.79208 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 27.91800 | 8.22813E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 13484.92567 | 16181.91081 | 0.57531 | 0.69037 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 3.80000 | 5.05843E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 11155.85488 | 13387.02586 | 0.80952 | 0.97142 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 27.91800 | 8.22813E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 7269.81557 | 8723.77868 | 0.31076 | 0.37292 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 3.80000 | 5.05843E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 11101.08379 | 13321.30055 | 0.80544 | 0.96653 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 27.91800 | 8.22813E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 7299.91730 | 8759.90076 | 0.31209 | 0.37450 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 3.80000 | 5.05843E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 11046.57892 | 13255.89471 | 0.80139 | 0.96167 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 27.91800 | 8.22813E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 7689.83715 | 9227.80458 | 0.32918 | 0.39502 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 3.80000 | 5.05843E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 12053.05839 | 14463.67006 | 0.87648 | 1.05177 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 27.91800 | 8.22813E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 9765.81398 | 11718.97677 | 0.42009 | 0.50410 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 3.80000 | 5.05843E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 28848.70 | 1.91585 | 1.91585 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 24703.84 | 0.72418 | 0.72418 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 15031.36 | 1.00698 | 1.00698 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 11835.19 | 0.33906 | 0.33906 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 14981.51 | 1.00407 | 1.00407 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 11920.24 | 0.34285 | 0.34285 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 15019.42 | 1.00711 | 1.00711 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 12006.63 | 0.34670 | 0.34670 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 14958.59 | 1.00255 | 1.00255 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 12185.03 | 0.35465 | 0.35465 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 27786.53 | 1.84414 | 1.84414 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 24036.04 | 0.69037 | 0.69037 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 14377.81 | 0.97284 | 0.97284 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 12638.59 | 0.37292 | 0.37292 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 14309.54 | 0.96831 | 0.96831 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 12674.67 | 0.37450 | 0.37450 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 14277.74 | 0.96433 | 0.96433 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 13141.34 | 0.39502 | 0.39502 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 15326.14 | 1.06063 | 1.06063 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 15602.10 | 0.50410 | 0.50410 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.91585 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.99470 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.98814 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.98180 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.98708 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.79208 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.97142 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.96653 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.96167 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.05177 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.91585 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.91585 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.91585 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.91585 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.91585 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.91585 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.99470 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.99470 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.99470 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.99470 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.00698 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.00698 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 0.98781 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.98814 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.98814 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.98814 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.98814 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.00407 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.00407 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 0.98414 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.98180 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.98180 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.98180 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.98180 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.00711 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.00711 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 0.97487 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.98708 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.98708 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.98708 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.98708 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.00255 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.00255 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 0.98457 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.79208 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.79208 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.79208 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.79208 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.84414 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 1.84414 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 0.97177 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.97142 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.97142 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.97142 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.97142 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.97284 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 0.97284 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 0.99854 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.96653 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.96653 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.96653 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.96653 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.96831 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 0.96831 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 0.99816 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.96167 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.96167 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.96167 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.96167 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.96433 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 0.96433 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 0.99724 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.05177 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.05177 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.05177 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.05177 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.06063 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.06063 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 0.99164 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 1.91585 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.00698 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.00407 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.00711 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.00255 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 1.84414 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 0.97284 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 0.96831 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 0.96433 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.06063 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.91585 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.91585 |
104 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2050.05137 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.91585 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.91585 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.91585 |
108 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.26446 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.91585 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.95793 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.27723 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 33585.54000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 16792.77000 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80017 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80017 |
116 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 33585.54000 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 51437.63935 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
120 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 51437.63935 |
121 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.00698 |
122 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
123 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.00698 |
124 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1114.88263 |
125 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.00698 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.00698 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.00698 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.00698 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.00698 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.50349 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.67132 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 17552.72000 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 8776.36000 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80015 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80015 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 17552.72000 |
137 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26543.70624 |
138 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
139 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
140 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 26543.70624 |
141 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.00407 |
142 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
143 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.00407 |
144 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1111.65967 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.00407 |
146 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.00407 |
147 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.00407 |
148 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.00407 |
149 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.00407 |
150 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.50203 |
151 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.66938 |
152 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 17482.21000 |
153 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 8741.10500 |
154 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80054 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80054 |
156 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 17482.21000 |
157 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26396.60084 |
158 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
159 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
160 | Coil:Heating:Fuel | PSZ-AC_3:3 HEATING COIL | Design Size Nominal Capacity [W] | 26396.60084 |
161 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.00711 |
162 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
163 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.00711 |
164 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1115.03334 |
165 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.00711 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.00711 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.00711 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.00711 |
169 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.00711 |
170 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.50356 |
171 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.67141 |
172 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 17529.73000 |
173 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 8764.86500 |
174 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80065 |
175 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80065 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 17529.73000 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26254.35010 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
179 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
180 | Coil:Heating:Fuel | PSZ-AC_4:4 HEATING COIL | Design Size Nominal Capacity [W] | 26254.35010 |
181 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.00255 |
182 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
183 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.00255 |
184 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1109.97916 |
185 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.00255 |
186 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.00255 |
187 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.00255 |
188 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.00255 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.00255 |
190 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.50127 |
191 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.66837 |
192 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 17459.13000 |
193 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 8729.56500 |
194 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80047 |
195 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80047 |
196 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 17459.13000 |
197 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26372.81059 |
198 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
200 | Coil:Heating:Fuel | PSZ-AC_5:5 HEATING COIL | Design Size Nominal Capacity [W] | 26372.81059 |
201 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.84414 |
202 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
203 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.84414 |
204 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1973.32227 |
205 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.84414 |
206 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.84414 |
207 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.84414 |
208 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.21714 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.84414 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.92207 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.22943 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 32462.81000 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 16231.40500 |
214 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80073 |
215 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80073 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 32462.81000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 49109.53858 |
218 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
219 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
220 | Coil:Heating:Fuel | PSZ-AC_6:6 HEATING COIL | Design Size Nominal Capacity [W] | 49109.53858 |
221 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.97284 |
222 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
223 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.97284 |
224 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1077.09155 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.97284 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.97284 |
227 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.97284 |
228 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.97284 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.97284 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.48642 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.64856 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 17000.53000 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 8500.26500 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80027 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80027 |
236 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 17000.53000 |
237 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26221.97199 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
240 | Coil:Heating:Fuel | PSZ-AC_7:7 HEATING COIL | Design Size Nominal Capacity [W] | 26221.97199 |
241 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.96831 |
242 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
243 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.96831 |
244 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1072.06880 |
245 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.96831 |
246 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.96831 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.96831 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.96831 |
249 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.96831 |
250 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.48415 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.64554 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 16931.58000 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 8465.79000 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80005 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80005 |
256 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16931.58000 |
257 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26111.27594 |
258 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
259 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
260 | Coil:Heating:Fuel | PSZ-AC_8:8 HEATING COIL | Design Size Nominal Capacity [W] | 26111.27594 |
261 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.96433 |
262 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
263 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.96433 |
264 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1067.66946 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.96433 |
266 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.96433 |
267 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.96433 |
268 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.96433 |
269 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.96433 |
270 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.48217 |
271 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.64289 |
272 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 16866.91000 |
273 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 8433.45500 |
274 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80096 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80096 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16866.91000 |
277 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26005.19037 |
278 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
279 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
280 | Coil:Heating:Fuel | PSZ-AC_9:9 HEATING COIL | Design Size Nominal Capacity [W] | 26005.19037 |
281 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.06063 |
282 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
283 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.06063 |
284 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1174.29019 |
285 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.06063 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.06063 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.06063 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.06063 |
289 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.06063 |
290 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.53032 |
291 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.70709 |
292 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 18254.89000 |
293 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 9127.44500 |
294 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80060 |
295 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80060 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18254.89000 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28006.43744 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
299 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
300 | Coil:Heating:Fuel | PSZ-AC_10:10 HEATING COIL | Design Size Nominal Capacity [W] | 28006.43744 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 32082.9 | 11.24 | 11.24 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 16763.0 | 11.97 | 11.97 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | 16694.8 | 11.97 | 11.97 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | 16739.9 | 11.97 | 11.97 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | 16672.9 | 11.97 | 11.97 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | 31016.3 | 11.25 | 11.25 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | 16237.5 | 11.98 | 11.98 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | 16172.1 | 11.98 | 11.98 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | 16110.6 | 11.98 | 11.98 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | 17423.2 | 11.94 | 11.94 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 58.18 | 78.94 | 58.18 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.199 | 0.190 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.09 | 39.47 | 29.09 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 58.22 | 78.94 | 58.22 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.289 | 0.270 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 3.4204184323E-002 | 4.6198901748E-002 | Pass | Pass | 3.7680804016E-002 | 0.1378269835 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 5.7688682656E-002 | 0.1098687276 | Pass | Pass | 4.1407692049E-002 | 0.1434348323 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 4.0775925802E-002 | 6.3740177867E-002 | Pass | Pass | 3.1476217115E-002 | 0.1267144861 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 3.4415721510E-002 | 5.5037138280E-002 | Pass | Pass | 0.1680570150 | 1.5381514235 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 2.8128560070E-002 | 4.5193648546E-002 | Pass | Pass | 4.8925668857E-002 | 0.1482669377 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 1.9067405482E-002 | 2.8753365592E-002 | Pass | Pass | 0.1137107368 | 0.4148944986 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 2.5472342214E-002 | 4.9302992307E-002 | Pass | Pass | 0.2186058842 | 1.0932879140 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 2.4691600175E-002 | 4.7555288149E-002 | Pass | Pass | 0.1652848711 | 0.5455616907 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 2.4119582983E-002 | 4.6468962109E-002 | Pass | Pass | 0.5182942730 | 4.2660627841 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 3.8836922110E-002 | 6.9419579202E-002 | Pass | Pass | 0.3115888325 | 1.1078986597 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3514.57 | 96.66 | 0.00 | 426.02 | 363.12 | 4400.40 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00 | 3.80 | Wetbulb [C] | 3.00 | 120.00 |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 31.30 | 8.90 | 18.40 | Wetbulb [C] | 4.10 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.00 | 2 | |||
Feb | 59.00 | 53 | |||
Mar | 58.58 | 43 | |||
Apr | 46.42 | 14 | |||
May | 18.00 | 12 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 3.00 | 6 | |||
Oct | 0.00 | 0 | |||
Nov | 18.00 | 12 | |||
Dec | 4.00 | 4 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 78.94 | 58.18 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.193 | 0.199 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.09 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 78.94 | 58.22 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.276 | 0.289 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.632 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.632 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.632 | 0.251 | 0.251 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.632 | 0.251 | 0.251 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.632 | 0.251 | 0.251 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.632 | 0.251 | 0.251 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.632 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.632 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.632 | 0.251 | 0.251 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.632 | 0.251 | 0.251 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.632 | 0.251 | 0.251 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.632 | 0.251 | 0.251 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 124.40 | 2.632 | 0.251 | 0.251 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 124.40 | 2.632 | 0.251 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 13.1942 | 348.39 | 4596.69 | LightsWired | LTG_SCH_BASE_LPD1 | 84.21 | 168.00 | 84.19 | 0.0000 | Y | 72.65 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 4.6828 | 348.39 | 1631.41 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 168.00 | 97.48 | 0.0000 | Y | 29.85 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 13.3632 | 174.19 | 2327.78 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 85.70 | 168.00 | 85.69 | 0.0000 | Y | 37.44 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 5.9749 | 174.19 | 1040.80 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 168.00 | 97.48 | 0.0000 | Y | 19.04 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 13.3365 | 174.19 | 2323.12 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 29.75 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 4.0374 | 174.19 | 703.30 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 10.29 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 13.3365 | 174.19 | 2323.12 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 29.75 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 4.0374 | 174.19 | 703.30 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 10.29 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 13.3365 | 174.19 | 2323.12 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 29.75 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 4.0374 | 174.19 | 703.30 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 10.29 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 13.1675 | 348.39 | 4587.38 | LightsWired | LTG_SCH_BASE_LPD2 | 62.11 | 168.00 | 61.60 | 0.0000 | Y | 53.05 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 13.3365 | 174.19 | 2323.12 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 27.34 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 13.3365 | 174.19 | 2323.12 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 27.34 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 13.3365 | 174.19 | 2323.12 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 27.34 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 13.3365 | 174.19 | 2323.12 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 27.34 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 7.7873 | 4180.64 | 32555.80 | 441.52 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 345.19 | AstronomicalClock | - | 42.14 | 42.14 | 2.73 | |
EXTERIOR_LIGHTS_B | 7274.32 | AstronomicalClock | - | 83.75 | 71.27 | 97.32 | |
Exterior Lighting Total | 7619.51 | 100.05 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 33585.54 | 26874.14 | 6711.40 | 0.80 | 3.80 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 17552.72 | 14044.81 | 3507.91 | 0.80 | 4.12 | |||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 17482.21 | 13995.21 | 3487.00 | 0.80 | 4.12 | |||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 17529.73 | 14035.18 | 3494.55 | 0.80 | 4.12 | |||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 17459.13 | 13975.51 | 3483.62 | 0.80 | 4.12 | |||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 32462.81 | 25993.95 | 6468.86 | 0.80 | 3.80 | |||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 17000.53 | 13605.01 | 3395.52 | 0.80 | 4.12 | |||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 16931.58 | 13546.11 | 3385.47 | 0.80 | 4.12 | |||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 16866.91 | 13509.72 | 3357.19 | 0.80 | 4.12 | |||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 18254.89 | 14614.86 | 3640.03 | 0.80 | 4.12 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 32082.9 | 11.24 | 11.24 | ||||
PSZ-AC_2:2 COOLING COIL | 16763.0 | 11.97 | 11.97 | ||||
PSZ-AC_3:3 COOLING COIL | 16694.8 | 11.97 | 11.97 | ||||
PSZ-AC_4:4 COOLING COIL | 16739.9 | 11.97 | 11.97 | ||||
PSZ-AC_5:5 COOLING COIL | 16672.9 | 11.97 | 11.97 | ||||
PSZ-AC_6:6 COOLING COIL | 31016.3 | 11.25 | 11.25 | ||||
PSZ-AC_7:7 COOLING COIL | 16237.5 | 11.98 | 11.98 | ||||
PSZ-AC_8:8 COOLING COIL | 16172.1 | 11.98 | 11.98 | ||||
PSZ-AC_9:9 COOLING COIL | 16110.6 | 11.98 | 11.98 | ||||
PSZ-AC_10:10 COOLING COIL | 17423.2 | 11.94 | 11.94 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 51437.64 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 26543.71 | 0.80 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | 26396.60 | 0.80 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | 26254.35 | 0.80 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | 26372.81 | 0.80 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | 49109.54 | 0.80 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | 26221.97 | 0.80 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | 26111.28 | 0.80 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | 26005.19 | 0.80 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | 28006.44 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.92 | 2050.05 | 1070.05 | 1.00 | 1.32 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.01 | 1114.88 | 1107.16 | 1.00 | 1.40 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.00 | 1111.66 | 1107.16 | 1.00 | 1.40 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.01 | 1115.03 | 1107.16 | 1.00 | 1.40 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.00 | 1109.98 | 1107.16 | 1.00 | 1.40 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.84 | 1973.32 | 1070.05 | 1.00 | 1.33 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.97 | 1077.09 | 1107.16 | 1.00 | 1.41 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.97 | 1072.07 | 1107.16 | 1.00 | 1.41 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.96 | 1067.67 | 1107.16 | 1.00 | 1.41 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.06 | 1174.29 | 1107.16 | 1.00 | 1.39 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 21352.71 | 25623.26 | 73.55 | 1.597 | 1.916 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 23.89 | 23.89 | 0.00896 | 31.30 | 0.00823 | 0.411 | 0.00 |
SMSTORE1 | 11416.77 | 13700.12 | 78.65 | 0.829 | 0.995 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00922 | 27.92 | 0.00823 | 0.206 | 0.00 |
SMSTORE2 | 11346.03 | 13615.23 | 78.16 | 0.823 | 0.988 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.89 | 23.89 | 0.00944 | 26.41 | 0.00823 | 0.206 | 0.00 |
SMSTORE3 | 11275.49 | 13530.59 | 77.68 | 0.818 | 0.982 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.89 | 23.89 | 0.00942 | 26.41 | 0.00823 | 0.206 | 0.00 |
SMSTORE4 | 11334.24 | 13601.09 | 78.08 | 0.823 | 0.987 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.89 | 23.89 | 0.00944 | 26.41 | 0.00823 | 0.206 | 0.00 |
LGSTORE2 | 20630.11 | 24756.13 | 71.06 | 1.493 | 1.792 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00941 | 27.92 | 0.00823 | 0.411 | 0.00 |
SMSTORE5 | 11155.85 | 13387.03 | 76.85 | 0.810 | 0.971 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00930 | 27.92 | 0.00823 | 0.206 | 0.00 |
SMSTORE6 | 11101.08 | 13321.30 | 76.47 | 0.805 | 0.967 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00931 | 27.92 | 0.00823 | 0.206 | 0.00 |
SMSTORE7 | 11046.58 | 13255.89 | 76.10 | 0.801 | 0.962 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00934 | 27.92 | 0.00823 | 0.206 | 0.00 |
SMSTORE8 | 12053.06 | 14463.67 | 83.03 | 0.876 | 1.052 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00919 | 27.92 | 0.00823 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 14026.15 | 16831.38 | 48.31 | 0.599 | 0.719 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 21.11 | 21.11 | 0.00739 | 3.80 | 0.00506 | 0.411 | 0.00 |
SMSTORE1 | 6432.29 | 7718.75 | 44.31 | 0.283 | 0.339 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00714 | 3.80 | 0.00506 | 0.206 | 0.00 |
SMSTORE2 | 6504.22 | 7805.06 | 44.81 | 0.286 | 0.343 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00714 | 3.80 | 0.00506 | 0.206 | 0.00 |
SMSTORE3 | 6577.27 | 7892.72 | 45.31 | 0.289 | 0.347 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00715 | 3.80 | 0.00506 | 0.206 | 0.00 |
SMSTORE4 | 6728.14 | 8073.76 | 46.35 | 0.296 | 0.355 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00716 | 3.80 | 0.00506 | 0.206 | 0.00 |
LGSTORE2 | 13484.93 | 16181.91 | 46.45 | 0.575 | 0.690 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 21.11 | 21.11 | 0.00741 | 3.80 | 0.00506 | 0.411 | 0.00 |
SMSTORE5 | 7269.82 | 8723.78 | 50.08 | 0.311 | 0.373 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 21.11 | 21.11 | 0.00743 | 3.80 | 0.00506 | 0.206 | 0.00 |
SMSTORE6 | 7299.92 | 8759.90 | 50.29 | 0.312 | 0.375 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 21.11 | 21.11 | 0.00743 | 3.80 | 0.00506 | 0.206 | 0.00 |
SMSTORE7 | 7689.84 | 9227.80 | 52.97 | 0.329 | 0.395 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 21.11 | 21.11 | 0.00747 | 3.80 | 0.00506 | 0.206 | 0.00 |
SMSTORE8 | 9765.81 | 11718.98 | 67.28 | 0.420 | 0.504 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 21.11 | 21.11 | 0.00743 | 3.80 | 0.00506 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 1.92 | 1.92 | 0.72 | 0.72 | 1.9159 | 1.9159 | 1.9159 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.01 | 1.01 | 0.34 | 0.34 | 1.0070 | 0.9947 | 1.0070 | 0.9878 | 1.0000 |
PSZ-AC_3:3 | 1.00 | 1.00 | 0.34 | 0.34 | 1.0041 | 0.9881 | 1.0041 | 0.9841 | 1.0000 |
PSZ-AC_4:4 | 1.01 | 1.01 | 0.35 | 0.35 | 1.0071 | 0.9818 | 1.0071 | 0.9749 | 1.0000 |
PSZ-AC_5:5 | 1.00 | 1.00 | 0.35 | 0.35 | 1.0025 | 0.9871 | 1.0025 | 0.9846 | 1.0000 |
PSZ-AC_6:6 | 1.84 | 1.84 | 0.69 | 0.69 | 1.8441 | 1.7921 | 1.8441 | 0.9718 | 1.0000 |
PSZ-AC_7:7 | 0.97 | 0.97 | 0.37 | 0.37 | 0.9728 | 0.9714 | 0.9728 | 0.9985 | 1.0000 |
PSZ-AC_8:8 | 0.97 | 0.97 | 0.37 | 0.37 | 0.9683 | 0.9665 | 0.9683 | 0.9982 | 1.0000 |
PSZ-AC_9:9 | 0.96 | 0.96 | 0.40 | 0.40 | 0.9643 | 0.9617 | 0.9643 | 0.9972 | 1.0000 |
PSZ-AC_10:10 | 1.06 | 1.06 | 0.50 | 0.50 | 1.0606 | 1.0518 | 1.0606 | 0.9916 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 33585.540 | 26874.142 | 1.915850 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 16792.77 | 15981.70 | 1.277233 | 26.37 | 17.27 | 0.00880575 | 12.80 | 11.93 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 32.2164 | 23.89 | 0.00896227 | 47.6318 | 21352.71 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 51437.639 | 51437.639 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 51437.64 | 51437.64 | 1.915851 | 17.39 | 12.05 | 0.00673202 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 21.4776 | 21.11 | 0.00718978 | 45.3718 | 13738.57 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 17552.720 | 14044.809 | 1.006980 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 8776.36 | 8364.66 | 0.671320 | 26.32 | 17.25 | 0.00879570 | 12.80 | 11.93 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 30.6470 | 23.89 | 0.00894060 | 47.5180 | 11190.16 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 26543.706 | 26543.706 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 26543.71 | 26543.71 | 1.006976 | 17.57 | 12.11 | 0.00671405 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 20.4314 | 21.11 | 0.00713917 | 45.0559 | 6432.29 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 17482.210 | 13995.208 | 1.004070 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 8741.10 | 8330.13 | 0.669380 | 26.31 | 17.25 | 0.00879618 | 12.80 | 11.93 | 0.00850000 | 31.23 | 0.00823338 | 18.43 | 30.7358 | 23.89 | 0.00894166 | 47.5236 | 11163.30 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 26396.601 | 26396.601 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 26396.60 | 26396.60 | 1.004065 | 17.56 | 12.11 | 0.00671738 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 20.4906 | 21.11 | 0.00714491 | 45.0917 | 6504.22 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 17529.730 | 14035.178 | 1.007110 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 8764.86 | 8353.26 | 0.671407 | 26.31 | 17.25 | 0.00879573 | 12.80 | 11.93 | 0.00850000 | 31.23 | 0.00823338 | 18.43 | 30.6430 | 23.89 | 0.00894058 | 47.5179 | 11195.38 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 26254.350 | 26254.350 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 26254.35 | 26254.35 | 1.007112 | 17.57 | 12.12 | 0.00672296 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 20.4286 | 21.11 | 0.00715030 | 45.1254 | 6577.27 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 17459.130 | 13975.510 | 1.002550 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 8729.57 | 8318.84 | 0.668367 | 26.32 | 17.25 | 0.00879645 | 12.80 | 11.93 | 0.00850000 | 31.23 | 0.00823338 | 18.43 | 30.7824 | 23.89 | 0.00894233 | 47.5271 | 11143.90 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 26372.811 | 26372.811 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 26372.81 | 26372.81 | 1.002547 | 17.56 | 12.12 | 0.00673050 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 20.5217 | 21.11 | 0.00716224 | 45.1999 | 6728.14 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 32462.810 | 25993.946 | 1.844140 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 16231.41 | 15420.64 | 1.229427 | 26.42 | 17.30 | 0.00881781 | 12.80 | 11.93 | 0.00850000 | 31.23 | 0.00823338 | 18.43 | 33.4692 | 23.89 | 0.00898639 | 47.7582 | 20513.54 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 49109.539 | 49109.539 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 49109.54 | 49109.54 | 1.844145 | 17.03 | 12.06 | 0.00688465 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 22.3127 | 21.11 | 0.00740916 | 46.7381 | 13484.93 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 17000.530 | 13605.014 | 0.972840 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 8500.26 | 8092.71 | 0.648560 | 26.37 | 17.27 | 0.00880341 | 12.80 | 11.93 | 0.00850000 | 31.15 | 0.00823326 | 18.40 | 31.7225 | 23.89 | 0.00895952 | 47.6171 | 11155.85 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 26221.972 | 26221.972 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 26221.97 | 26221.97 | 0.972843 | 17.27 | 12.20 | 0.00692512 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 21.1483 | 21.11 | 0.00742578 | 46.8417 | 7269.82 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 16931.580 | 13546.111 | 0.968310 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 8465.79 | 8059.05 | 0.645540 | 26.38 | 17.27 | 0.00880424 | 12.80 | 11.93 | 0.00850000 | 31.15 | 0.00823326 | 18.40 | 31.8709 | 23.89 | 0.00896166 | 47.6284 | 11101.08 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 26111.276 | 26111.276 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 26111.28 | 26111.28 | 0.968306 | 17.26 | 12.19 | 0.00692500 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 21.2473 | 21.11 | 0.00742859 | 46.8593 | 7299.92 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 16866.910 | 13509.720 | 0.964330 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 8433.45 | 8027.88 | 0.642887 | 26.38 | 17.28 | 0.00880462 | 12.80 | 11.93 | 0.00850000 | 31.15 | 0.00823326 | 18.40 | 32.0024 | 23.89 | 0.00896267 | 47.6336 | 11046.58 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 26005.190 | 26005.190 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 26005.19 | 26005.19 | 0.964333 | 17.24 | 12.21 | 0.00695695 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 21.3349 | 21.11 | 0.00747186 | 47.1289 | 7689.84 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 18254.890 | 14614.865 | 1.060630 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 9127.44 | 8712.18 | 0.707087 | 26.19 | 17.20 | 0.00878384 | 12.80 | 11.93 | 0.00850000 | 30.86 | 0.00823278 | 18.30 | 29.0968 | 23.89 | 0.00892061 | 47.4132 | 12053.06 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 28006.437 | 28006.437 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 28006.44 | 28006.44 | 1.060634 | 17.60 | 12.37 | 0.00696613 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 19.3978 | 21.11 | 0.00742524 | 46.8400 | 9765.81 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 33585.540 | 26874.142 | 1.915850 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2094 | 1004.8586 | 1.1818 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.915851 | 2.26411210 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | Sensible | 16792.77 | 15981.70 | 1.0000 | 1.50940710 | 1.277233 | 26.37 | 17.27 | 0.00880575 | 48948.6 | 12.80 | 11.93 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16792.77 | 31.30 | 0.00823349 | 18.45 | 0.41147883 | 32.2164 | 23.89 | 0.00896227 | 23.89 | 0.00896227 | 47.6318 | 21352.71 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 51437.639 | 51437.639 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.915851 | 2.26411210 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 51437.64 | 51437.64 | 1.0000 | 2.26411210 | 1.915851 | 17.39 | 12.05 | 0.00673202 | 34529.4 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 51437.64 | 3.80 | 0.00505843 | 3.80 | 0.41147883 | 21.4776 | 21.11 | 0.00718978 | 21.11 | 0.00718978 | 45.3718 | 13738.57 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 17552.720 | 14044.809 | 1.006980 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1908 | 1004.8586 | 1.1818 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.006976 | 1.19002313 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | Sensible | 8776.36 | 8364.66 | 1.0000 | 0.79335165 | 0.671320 | 26.32 | 17.25 | 0.00879570 | 48879.9 | 12.80 | 11.93 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8776.36 | 31.30 | 0.00823349 | 18.45 | 0.20573941 | 30.6470 | 23.89 | 0.00894060 | 23.89 | 0.00894060 | 47.5180 | 11190.16 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26543.706 | 26543.706 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.006976 | 1.19002313 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 26543.71 | 26543.71 | 1.0000 | 1.19002313 | 1.006976 | 17.57 | 12.11 | 0.00671405 | 34668.1 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26543.71 | 3.80 | 0.00505843 | 3.80 | 0.20573941 | 20.4314 | 21.11 | 0.00713917 | 21.11 | 0.00713917 | 45.0559 | 6432.29 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 17482.210 | 13995.208 | 1.004070 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1917 | 1004.8586 | 1.1818 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.004065 | 1.18658295 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | Sensible | 8741.10 | 8330.13 | 1.0000 | 0.79105900 | 0.669380 | 26.31 | 17.25 | 0.00879618 | 48869.3 | 12.80 | 11.93 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8741.10 | 31.23 | 0.00823338 | 18.43 | 0.20573941 | 30.7358 | 23.89 | 0.00894166 | 23.89 | 0.00894166 | 47.5236 | 11163.30 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26396.601 | 26396.601 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.004065 | 1.18658295 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 26396.60 | 26396.60 | 1.0000 | 1.18658295 | 1.004065 | 17.56 | 12.11 | 0.00671738 | 34666.1 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26396.60 | 3.80 | 0.00505843 | 3.80 | 0.20573941 | 20.4906 | 21.11 | 0.00714491 | 21.11 | 0.00714491 | 45.0917 | 6504.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 17529.730 | 14035.178 | 1.007110 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1908 | 1004.8586 | 1.1818 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.007112 | 1.19018400 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | Sensible | 8764.86 | 8353.26 | 1.0000 | 0.79345407 | 0.671407 | 26.31 | 17.25 | 0.00879573 | 48863.7 | 12.80 | 11.93 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8764.86 | 31.23 | 0.00823338 | 18.43 | 0.20573941 | 30.6430 | 23.89 | 0.00894058 | 23.89 | 0.00894058 | 47.5179 | 11195.38 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26254.350 | 26254.350 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.007112 | 1.19018400 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 26254.35 | 26254.35 | 1.0000 | 1.19018400 | 1.007112 | 17.57 | 12.12 | 0.00672296 | 34691.2 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26254.35 | 3.80 | 0.00505843 | 3.80 | 0.20573941 | 20.4286 | 21.11 | 0.00715030 | 21.11 | 0.00715030 | 45.1254 | 6577.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 17459.130 | 13975.510 | 1.002550 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1922 | 1004.8586 | 1.1818 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.002547 | 1.18478918 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | Sensible | 8729.57 | 8318.84 | 1.0000 | 0.78986147 | 0.668367 | 26.32 | 17.25 | 0.00879645 | 48872.6 | 12.80 | 11.93 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8729.57 | 31.23 | 0.00823338 | 18.43 | 0.20573941 | 30.7824 | 23.89 | 0.00894233 | 23.89 | 0.00894233 | 47.5271 | 11143.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26372.811 | 26372.811 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.002547 | 1.18478918 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 26372.81 | 26372.81 | 1.0000 | 1.18478918 | 1.002547 | 17.56 | 12.12 | 0.00673050 | 34693.9 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26372.81 | 3.80 | 0.00505843 | 3.80 | 0.20573941 | 20.5217 | 21.11 | 0.00716224 | 21.11 | 0.00716224 | 45.1999 | 6728.14 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 32462.810 | 25993.946 | 1.844140 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2319 | 1004.8586 | 1.1818 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.844145 | 2.17937115 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | Sensible | 16231.41 | 15420.64 | 1.0000 | 1.45291020 | 1.229427 | 26.42 | 17.30 | 0.00881781 | 49031.3 | 12.80 | 11.93 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16231.41 | 31.23 | 0.00823338 | 18.43 | 0.41147883 | 33.4692 | 23.89 | 0.00898639 | 23.89 | 0.00898639 | 47.7582 | 20513.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 49109.539 | 49109.539 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.844145 | 2.17937115 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | Sensible | 49109.54 | 49109.54 | 1.0000 | 2.17937115 | 1.844145 | 17.03 | 12.06 | 0.00688465 | 34552.6 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 49109.54 | 3.80 | 0.00505843 | 3.80 | 0.41147883 | 22.3127 | 20.84 | 0.00740916 | 21.11 | 0.00740916 | 46.7381 | 13484.93 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 17000.530 | 13605.014 | 0.972840 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2051 | 1004.8586 | 1.1818 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.972843 | 1.14968501 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | Sensible | 8500.26 | 8092.71 | 1.0000 | 0.76645437 | 0.648560 | 26.37 | 17.27 | 0.00880341 | 48942.9 | 12.80 | 11.93 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8500.26 | 31.15 | 0.00823326 | 18.40 | 0.20573941 | 31.7225 | 23.89 | 0.00895952 | 23.89 | 0.00895952 | 47.6171 | 11155.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26221.972 | 26221.972 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.972843 | 1.14968501 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | Sensible | 26221.97 | 26221.97 | 1.0000 | 1.14968501 | 0.972843 | 17.27 | 12.20 | 0.00692512 | 34899.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26221.97 | 3.80 | 0.00505843 | 3.80 | 0.20573941 | 21.1483 | 20.89 | 0.00742578 | 21.11 | 0.00742578 | 46.8417 | 7269.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 16931.580 | 13546.111 | 0.968310 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2066 | 1004.8586 | 1.1818 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.968306 | 1.14432374 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | Sensible | 8465.79 | 8059.05 | 1.0000 | 0.76288540 | 0.645540 | 26.38 | 17.27 | 0.00880424 | 48953.7 | 12.80 | 11.93 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8465.79 | 31.15 | 0.00823326 | 18.40 | 0.20573941 | 31.8709 | 23.89 | 0.00896166 | 23.89 | 0.00896166 | 47.6284 | 11101.08 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26111.276 | 26111.276 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.968306 | 1.14432374 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | Sensible | 26111.28 | 26111.28 | 1.0000 | 1.14432374 | 0.968306 | 17.26 | 12.19 | 0.00692500 | 34881.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26111.28 | 3.80 | 0.00505843 | 3.80 | 0.20573941 | 21.2473 | 20.89 | 0.00742859 | 21.11 | 0.00742859 | 46.8593 | 7299.92 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 16866.910 | 13509.720 | 0.964330 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2074 | 1004.8586 | 1.1818 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.964333 | 1.13962790 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | Sensible | 8433.45 | 8027.88 | 1.0000 | 0.75974975 | 0.642887 | 26.38 | 17.28 | 0.00880462 | 48958.8 | 12.80 | 11.93 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8433.45 | 31.15 | 0.00823326 | 18.40 | 0.20573941 | 32.0024 | 23.89 | 0.00896267 | 23.89 | 0.00896267 | 47.6336 | 11046.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26005.190 | 26005.190 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.964333 | 1.13962790 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | Sensible | 26005.19 | 26005.19 | 1.0000 | 1.13962790 | 0.964333 | 17.24 | 12.21 | 0.00695695 | 34943.9 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26005.19 | 3.80 | 0.00505843 | 3.80 | 0.20573941 | 21.3349 | 20.88 | 0.00747186 | 21.11 | 0.00747186 | 47.1289 | 7689.84 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 18254.890 | 14614.865 | 1.060630 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1687 | 1004.8586 | 1.1818 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.060634 | 1.25343462 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | Sensible | 9127.44 | 8712.18 | 1.0000 | 0.83561994 | 0.707087 | 26.19 | 17.20 | 0.00878384 | 48713.2 | 12.80 | 11.93 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9127.44 | 30.86 | 0.00823278 | 18.30 | 0.20573941 | 29.0968 | 23.89 | 0.00892061 | 23.89 | 0.00892061 | 47.4132 | 12053.06 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28006.437 | 28006.437 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.060634 | 1.25343462 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | Sensible | 28006.44 | 28006.44 | 1.0000 | 1.25343462 | 1.060634 | 17.60 | 12.37 | 0.00696613 | 35340.0 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28006.44 | 3.80 | 0.00505843 | 3.80 | 0.20573941 | 19.3978 | 20.93 | 0.00742524 | 21.11 | 0.00742524 | 46.8400 | 9765.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 1.92 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.01 | - | |||
PSZ-AC_3:3_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.00 | - | |||
PSZ-AC_4:4_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.01 | - | |||
PSZ-AC_5:5_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.00 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 1.84 | - | |||
PSZ-AC_7:7_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.97 | - | |||
PSZ-AC_8:8_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.97 | - | |||
PSZ-AC_9:9_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.96 | - | |||
PSZ-AC_10:10_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.06 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 2879.67 | 1911.67 | 157.17 |
SMSTORE1 | 3164.00 | 1019.67 | 179.67 |
SMSTORE2 | 2301.17 | 946.67 | 125.83 |
SMSTORE3 | 2236.67 | 1024.17 | 127.67 |
SMSTORE4 | 2125.17 | 1178.17 | 134.17 |
LGSTORE2 | 1829.17 | 1394.17 | 90.83 |
SMSTORE5 | 1763.00 | 1261.17 | 139.50 |
SMSTORE6 | 1737.50 | 1295.50 | 142.00 |
SMSTORE7 | 1643.17 | 1457.50 | 148.33 |
SMSTORE8 | 1522.17 | 1750.83 | 158.83 |
Facility | 3246.17 | 2715.00 | 289.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 0.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.92 | 56.25 | 1805.20 | 1.226 | 0.221 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 1.703 | 0.239 | 0.000 | 0.000 |
SMSTORE2 | 7.09 | 28.12 | 902.60 | 1.811 | 0.313 | 0.000 | 0.000 |
SMSTORE3 | 7.09 | 28.12 | 902.60 | 1.796 | 0.313 | 0.000 | 0.000 |
SMSTORE4 | 7.09 | 28.12 | 902.60 | 1.751 | 0.313 | 0.000 | 0.000 |
LGSTORE2 | 24.79 | 56.25 | 1805.20 | 1.245 | 0.301 | 0.000 | 0.000 |
SMSTORE5 | 12.40 | 28.12 | 902.60 | 1.719 | 0.334 | 0.000 | 0.000 |
SMSTORE6 | 12.40 | 28.12 | 902.60 | 1.705 | 0.334 | 0.000 | 0.000 |
SMSTORE7 | 12.40 | 28.12 | 902.60 | 1.659 | 0.334 | 0.000 | 0.000 |
SMSTORE8 | 12.40 | 28.12 | 902.60 | 1.702 | 0.349 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.92 | 56.25 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.09 | 28.12 | 902.60 | 0.815 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.09 | 28.12 | 902.60 | 0.815 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.09 | 28.12 | 902.60 | 0.815 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.79 | 56.25 | 1805.20 | 0.815 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.40 | 28.12 | 902.60 | 0.815 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.40 | 28.12 | 902.60 | 0.815 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.40 | 28.12 | 902.60 | 0.815 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.40 | 28.12 | 902.60 | 0.814 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 16.92 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE1 | PSZ-AC_2:2 | 8.46 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE2 | PSZ-AC_3:3 | 7.09 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE3 | PSZ-AC_4:4 | 7.09 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE4 | PSZ-AC_5:5 | 7.09 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
LGSTORE2 | PSZ-AC_6:6 | 24.79 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE5 | PSZ-AC_7:7 | 12.40 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE6 | PSZ-AC_8:8 | 12.40 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE7 | PSZ-AC_9:9 | 12.40 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE8 | PSZ-AC_10:10 | 12.40 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
Total Facility | 121.02 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 2.469 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 12614983.11 | 0.00 | 12614983.11 | 2480010.94 | 15094994.05 | 12976396.34 | 3175.60 | 2295.38 | 3289.03 | 0.00 |
SMSTORE1 | 8755428.35 | 0.00 | 8755428.35 | 1288318.98 | 10043747.33 | 6488198.17 | 3613.21 | 852.60 | 4294.19 | 0.00 |
SMSTORE2 | 7011973.79 | 0.00 | 7011973.79 | 1304434.49 | 8316408.27 | 6488198.17 | 4365.00 | 1398.66 | 2996.34 | 0.00 |
SMSTORE3 | 6951936.84 | 0.00 | 6951936.84 | 1304434.49 | 8256371.33 | 6488198.17 | 4365.00 | 1450.44 | 2944.56 | 0.00 |
SMSTORE4 | 6776248.64 | 0.00 | 6776248.64 | 1304434.49 | 8080683.13 | 6488198.17 | 4365.00 | 1560.96 | 2834.04 | 0.00 |
LGSTORE2 | 8839663.22 | 0.00 | 8839663.22 | 2374603.37 | 11214266.59 | 12976396.34 | 4730.00 | 1822.78 | 2207.22 | 0.00 |
SMSTORE5 | 6099625.74 | 0.00 | 6099625.74 | 1310340.97 | 7409966.71 | 6488198.17 | 4730.00 | 1403.94 | 2626.06 | 0.00 |
SMSTORE6 | 6049032.70 | 0.00 | 6049032.70 | 1310340.97 | 7359373.67 | 6488198.17 | 4730.00 | 1429.67 | 2600.33 | 0.00 |
SMSTORE7 | 5884942.88 | 0.00 | 5884942.88 | 1310340.97 | 7195283.85 | 6488198.17 | 4730.00 | 1567.97 | 2462.03 | 0.00 |
SMSTORE8 | 6040428.64 | 0.00 | 6040428.64 | 1492825.49 | 7533254.13 | 6488198.17 | 4730.00 | 1731.05 | 2298.95 | 0.00 |
Total Facility | 75024263.92 | 0.00 | 75024263.92 | 15480085.15 | 90504349.07 | 77858378.04 | 4730.00 | 2935.53 | 4525.27 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.6000 | 0.0000 | 0.6000 | 0.1083 | 0.7083 | 0.4115 | 255.60 | 2295.38 | 3289.03 |
SMSTORE1 | 0.4164 | 0.0000 | 0.4164 | 0.0584 | 0.4748 | 0.2057 | 693.21 | 852.60 | 4294.19 |
SMSTORE2 | 0.4432 | 0.0000 | 0.4432 | 0.0766 | 0.5198 | 0.2057 | 0.00 | 1398.66 | 2996.34 |
SMSTORE3 | 0.4394 | 0.0000 | 0.4394 | 0.0766 | 0.5160 | 0.2057 | 0.00 | 1450.44 | 2944.56 |
SMSTORE4 | 0.4283 | 0.0000 | 0.4283 | 0.0766 | 0.5049 | 0.2057 | 0.00 | 1560.96 | 2834.04 |
LGSTORE2 | 0.6093 | 0.0000 | 0.6093 | 0.1471 | 0.7564 | 0.4115 | 0.00 | 1822.78 | 2207.22 |
SMSTORE5 | 0.4204 | 0.0000 | 0.4204 | 0.0818 | 0.5022 | 0.2057 | 0.00 | 1403.94 | 2626.06 |
SMSTORE6 | 0.4169 | 0.0000 | 0.4169 | 0.0818 | 0.4987 | 0.2057 | 0.00 | 1429.67 | 2600.33 |
SMSTORE7 | 0.4056 | 0.0000 | 0.4056 | 0.0818 | 0.4874 | 0.2057 | 0.00 | 1567.97 | 2462.03 |
SMSTORE8 | 0.4164 | 0.0000 | 0.4164 | 0.0855 | 0.5019 | 0.2057 | 0.00 | 1731.05 | 2298.95 |
Total Facility | 4.5960 | 0.0000 | 4.5960 | 0.8745 | 5.4704 | 2.4689 | 804.88 | 2935.53 | 4525.27 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 17618098.39 | 0.00 | 17618098.39 | 12976396.34 | 3172.43 | 0.33 | 5587.24 | 0.00 |
PSZ-AC_2:2 | 12227838.32 | 0.00 | 12227838.32 | 6488198.17 | 3565.86 | 7.32 | 5186.82 | 0.00 |
PSZ-AC_3:3 | 9792928.27 | 0.00 | 9792928.27 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 0.00 |
PSZ-AC_4:4 | 9709080.63 | 0.00 | 9709080.63 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 0.00 |
PSZ-AC_5:5 | 9463714.34 | 0.00 | 9463714.34 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 0.00 |
PSZ-AC_6:6 | 12345479.59 | 0.00 | 12345479.59 | 12976396.34 | 4730.00 | 0.00 | 4030.00 | 0.00 |
PSZ-AC_7:7 | 8518742.25 | 0.00 | 8518742.25 | 6488198.17 | 4730.00 | 0.00 | 4030.00 | 0.00 |
PSZ-AC_8:8 | 8448083.97 | 0.00 | 8448083.97 | 6488198.17 | 4730.00 | 0.00 | 4030.00 | 0.00 |
PSZ-AC_9:9 | 8218915.99 | 0.00 | 8218915.99 | 6488198.17 | 4730.00 | 0.00 | 4030.00 | 0.00 |
PSZ-AC_10:10 | 8436067.54 | 0.00 | 8436067.54 | 6488198.17 | 4730.00 | 0.00 | 4030.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.8380 | 0.0000 | 0.8380 | 0.4115 | 252.43 | 0.33 | 5587.24 |
PSZ-AC_2:2 | 0.5816 | 0.0000 | 0.5816 | 0.2057 | 645.86 | 7.32 | 5186.82 |
PSZ-AC_3:3 | 0.6189 | 0.0000 | 0.6189 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_4:4 | 0.6136 | 0.0000 | 0.6136 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_5:5 | 0.5981 | 0.0000 | 0.5981 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_6:6 | 0.8509 | 0.0000 | 0.8509 | 0.4115 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_7:7 | 0.5872 | 0.0000 | 0.5872 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_8:8 | 0.5823 | 0.0000 | 0.5823 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_9:9 | 0.5665 | 0.0000 | 0.5665 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_10:10 | 0.5815 | 0.0000 | 0.5815 | 0.2057 | 0.00 | 0.00 | 4030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 4200.28 | 1400.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 2511.78 | 3056.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 2829.90 | 1565.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 2853.34 | 1541.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 2921.47 | 1473.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 3276.78 | 753.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 2663.15 | 1366.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 2676.64 | 1353.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 2775.34 | 1254.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 2865.69 | 1164.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.8779 | 0.8621 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.7174 | 0.5220 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 0.6387 | 0.5837 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 0.6302 | 0.5834 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 0.6101 | 0.5749 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 0.8502 | 0.8553 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.6027 | 0.5573 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.5963 | 0.5551 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.5736 | 0.5512 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.5843 | 0.5749 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 759 |
Defaulted Fields | 823 |
Fields with Defaults | 2681 |
Autosized Fields | 184 |
Autosizable Fields | 458 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 978.66 | 3115.94 | 01-JAN-07:00 | 89836.85 | 16-OCT-11:30 |
Electricity:Building | 570.24 | 1897.94 | 01-JAN-00:10 | 35612.10 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 128.86 | 354.96 | 01-JAN-00:10 | 6669.68 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 570.24 | 1897.94 | 01-JAN-00:10 | 35612.10 | 01-JAN-11:10 |
InteriorLights:Electricity | 441.52 | 1448.52 | 01-JAN-00:10 | 27522.57 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 102.50 | 280.06 | 01-JAN-00:10 | 5321.43 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 441.52 | 1448.52 | 01-JAN-00:10 | 27522.57 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 441.52 | 1448.52 | 01-JAN-00:10 | 27522.57 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 102.50 | 280.06 | 01-JAN-00:10 | 5321.43 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 441.52 | 1448.52 | 01-JAN-00:10 | 27522.57 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 69.66 | 191.80 | 01-JAN-00:10 | 3606.70 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 56.49 | 154.35 | 01-JAN-00:10 | 2932.57 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 56.49 | 154.35 | 01-JAN-00:10 | 2932.57 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 50.51 | 174.25 | 01-JAN-00:10 | 3273.35 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 40.04 | 136.80 | 01-JAN-00:10 | 2599.23 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 40.04 | 136.80 | 01-JAN-00:10 | 2599.23 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 50.51 | 174.25 | 01-JAN-00:10 | 3273.35 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 40.04 | 136.80 | 01-JAN-00:10 | 2599.23 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 40.04 | 136.80 | 01-JAN-00:10 | 2599.23 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 50.51 | 174.25 | 01-JAN-00:10 | 3273.35 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 40.04 | 136.80 | 01-JAN-00:10 | 2599.23 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 40.04 | 136.80 | 01-JAN-00:10 | 2599.23 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 72.31 | 272.07 | 01-JAN-00:10 | 5094.77 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 53.05 | 197.17 | 01-JAN-00:10 | 3746.51 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 53.05 | 197.17 | 01-JAN-00:10 | 3746.51 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 36.97 | 139.09 | 01-JAN-00:10 | 2605.22 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 36.97 | 139.09 | 01-JAN-00:10 | 2605.22 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 36.97 | 139.09 | 01-JAN-00:10 | 2605.22 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 36.97 | 139.09 | 01-JAN-00:10 | 2605.22 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.36 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.36 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.18 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.18 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.26 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.26 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
ElectricityPurchased:Facility | 978.66 | 3115.94 | 01-JAN-07:00 | 89836.85 | 16-OCT-11:30 |
ElectricityPurchased:Plant | 978.66 | 3115.94 | 01-JAN-07:00 | 89836.85 | 16-OCT-11:30 |
Cogeneration:ElectricityPurchased | 978.66 | 3115.94 | 01-JAN-07:00 | 89836.85 | 16-OCT-11:30 |
General:Cogeneration:ElectricityPurchased | 978.66 | 3115.94 | 01-JAN-07:00 | 89836.85 | 16-OCT-11:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 978.66 | 3115.94 | 01-JAN-07:00 | 89836.85 | 16-OCT-11:30 |
ElectricityNet:Plant | 978.66 | 3115.94 | 01-JAN-07:00 | 89836.85 | 16-OCT-11:30 |
Cogeneration:ElectricityNet | 978.66 | 3115.94 | 01-JAN-07:00 | 89836.85 | 16-OCT-11:30 |
General:Cogeneration:ElectricityNet | 978.66 | 3115.94 | 01-JAN-07:00 | 89836.85 | 16-OCT-11:30 |
Electricity:HVAC | 246.08 | 0.00 | 01-JAN-00:10 | 49704.10 | 16-OCT-11:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 66.94 | 0.00 | 01-JAN-00:10 | 38180.95 | 16-OCT-11:10 |
General:Cooling:Electricity | 66.94 | 0.00 | 01-JAN-00:10 | 38180.95 | 16-OCT-11:10 |
Fans:Electricity | 179.14 | 0.00 | 01-JAN-00:10 | 11572.62 | 16-OCT-12:10 |
General:Fans:Electricity | 179.14 | 0.00 | 01-JAN-00:10 | 11572.62 | 16-OCT-12:10 |
ExteriorLights:Electricity | 100.05 | 0.00 | 01-JAN-07:00 | 7619.51 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 100.05 | 0.00 | 01-JAN-07:00 | 7619.51 | 01-JAN-06:10 |
Electricity:Plant | 62.29 | 1218.00 | 30-APR-17:10 | 11495.98 | 05-JAN-19:00 |
WaterSystems:Electricity | 62.29 | 1218.00 | 30-APR-17:10 | 11495.98 | 05-JAN-19:00 |
Water Heater:WaterSystems:Electricity | 62.29 | 1218.00 | 30-APR-17:10 | 11495.98 | 05-JAN-19:00 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 2.44 | 0.00 | 01-JAN-00:10 | 48795.34 | 30-MAR-08:10 |
NaturalGas:HVAC | 2.44 | 0.00 | 01-JAN-00:10 | 48795.34 | 30-MAR-08:10 |
Heating:NaturalGas | 2.44 | 0.00 | 01-JAN-00:10 | 48795.34 | 30-MAR-08:10 |
General:Heating:NaturalGas | 2.44 | 0.00 | 01-JAN-00:10 | 48795.34 | 30-MAR-08:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 781.61 | 0.00 | 01-JAN-00:10 | 235583.92 | 16-OCT-12:10 |
EnergyTransfer:Building | 483.96 | 0.00 | 01-JAN-00:10 | 94556.39 | 16-OCT-12:10 |
EnergyTransfer:Zone:LGSTORE1 | 107.46 | 0.00 | 01-JAN-00:10 | 15691.94 | 29-SEP-13:00 |
Heating:EnergyTransfer | 11.92 | 0.00 | 01-JAN-00:10 | 24513.95 | 30-MAR-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 0.89 | 0.00 | 01-JAN-00:10 | 6441.80 | 30-MAR-08:10 |
General:Heating:EnergyTransfer | 11.92 | 0.00 | 01-JAN-00:10 | 24513.95 | 30-MAR-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 0.89 | 0.00 | 01-JAN-00:10 | 6441.80 | 30-MAR-08:10 |
Cooling:EnergyTransfer | 472.04 | 0.00 | 01-JAN-00:10 | 94556.39 | 16-OCT-12:10 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 106.57 | 0.00 | 01-JAN-00:10 | 15691.94 | 29-SEP-13:00 |
General:Cooling:EnergyTransfer | 472.04 | 0.00 | 01-JAN-00:10 | 94556.39 | 16-OCT-12:10 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 106.57 | 0.00 | 01-JAN-00:10 | 15691.94 | 29-SEP-13:00 |
EnergyTransfer:Zone:SMSTORE1 | 58.94 | 0.00 | 01-JAN-00:10 | 10083.91 | 05-FEB-18:10 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 1.13 | 0.00 | 01-JAN-00:10 | 1080.39 | 25-FEB-09:00 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 1.13 | 0.00 | 01-JAN-00:10 | 1080.39 | 25-FEB-09:00 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 57.80 | 0.00 | 01-JAN-00:10 | 10083.91 | 05-FEB-18:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 57.80 | 0.00 | 01-JAN-00:10 | 10083.91 | 05-FEB-18:10 |
EnergyTransfer:Zone:SMSTORE2 | 41.85 | 0.00 | 01-JAN-00:10 | 8011.58 | 16-OCT-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 1.22 | 0.00 | 01-JAN-00:10 | 1702.97 | 15-OCT-16:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 1.22 | 0.00 | 01-JAN-00:10 | 1702.97 | 15-OCT-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 40.64 | 0.00 | 01-JAN-00:10 | 8011.58 | 16-OCT-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 40.64 | 0.00 | 01-JAN-00:10 | 8011.58 | 16-OCT-12:10 |
EnergyTransfer:Zone:SMSTORE3 | 40.77 | 0.00 | 01-JAN-00:10 | 8047.38 | 16-OCT-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 1.22 | 0.00 | 01-JAN-00:10 | 1706.13 | 15-OCT-16:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 1.22 | 0.00 | 01-JAN-00:10 | 1706.13 | 15-OCT-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 39.54 | 0.00 | 01-JAN-00:10 | 8047.38 | 16-OCT-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 39.54 | 0.00 | 01-JAN-00:10 | 8047.38 | 16-OCT-12:10 |
EnergyTransfer:Zone:SMSTORE4 | 38.38 | 0.00 | 01-JAN-00:10 | 7945.03 | 16-OCT-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 1.22 | 0.00 | 01-JAN-00:10 | 1713.38 | 15-OCT-16:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 1.22 | 0.00 | 01-JAN-00:10 | 1713.38 | 15-OCT-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 37.16 | 0.00 | 01-JAN-00:10 | 7945.03 | 16-OCT-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 37.16 | 0.00 | 01-JAN-00:10 | 7945.03 | 16-OCT-12:10 |
EnergyTransfer:Zone:LGSTORE2 | 68.14 | 0.00 | 01-JAN-00:10 | 15027.59 | 16-OCT-12:20 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 0.94 | 0.00 | 01-JAN-00:10 | 5901.14 | 30-MAR-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 0.94 | 0.00 | 01-JAN-00:10 | 5901.14 | 30-MAR-08:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 67.21 | 0.00 | 01-JAN-00:10 | 15027.59 | 16-OCT-12:20 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 67.21 | 0.00 | 01-JAN-00:10 | 15027.59 | 16-OCT-12:20 |
EnergyTransfer:Zone:SMSTORE5 | 33.98 | 0.00 | 01-JAN-00:10 | 7939.41 | 16-OCT-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 1.28 | 0.00 | 01-JAN-00:10 | 1722.34 | 15-OCT-16:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 1.28 | 0.00 | 01-JAN-00:10 | 1722.34 | 15-OCT-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 32.70 | 0.00 | 01-JAN-00:10 | 7939.41 | 16-OCT-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 32.70 | 0.00 | 01-JAN-00:10 | 7939.41 | 16-OCT-12:10 |
EnergyTransfer:Zone:SMSTORE6 | 33.43 | 0.00 | 01-JAN-00:10 | 7892.93 | 16-OCT-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 1.28 | 0.00 | 01-JAN-00:10 | 1725.28 | 02-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 1.28 | 0.00 | 01-JAN-00:10 | 1725.28 | 02-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 32.16 | 0.00 | 01-JAN-00:10 | 7892.93 | 16-OCT-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 32.16 | 0.00 | 01-JAN-00:10 | 7892.93 | 16-OCT-12:10 |
EnergyTransfer:Zone:SMSTORE7 | 31.27 | 0.00 | 01-JAN-00:10 | 7816.03 | 16-OCT-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 1.29 | 0.00 | 01-JAN-00:10 | 3243.16 | 30-MAR-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 1.29 | 0.00 | 01-JAN-00:10 | 3243.16 | 30-MAR-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 29.98 | 0.00 | 01-JAN-00:10 | 7816.03 | 16-OCT-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 29.98 | 0.00 | 01-JAN-00:10 | 7816.03 | 16-OCT-12:10 |
EnergyTransfer:Zone:SMSTORE8 | 29.73 | 0.00 | 01-JAN-00:10 | 8804.93 | 16-OCT-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 1.46 | 0.00 | 01-JAN-00:10 | 5931.74 | 30-MAR-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 1.46 | 0.00 | 01-JAN-00:10 | 5931.74 | 30-MAR-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 28.28 | 0.00 | 01-JAN-00:10 | 8804.93 | 16-OCT-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 28.28 | 0.00 | 01-JAN-00:10 | 8804.93 | 16-OCT-12:10 |
EnergyTransfer:HVAC | 297.65 | 0.00 | 01-JAN-00:10 | 141027.53 | 16-OCT-12:10 |
HeatingCoils:EnergyTransfer | 1.95 | 0.00 | 01-JAN-00:10 | 39036.27 | 30-MAR-08:10 |
CoolingCoils:EnergyTransfer | 295.70 | 0.00 | 01-JAN-00:10 | 141027.53 | 16-OCT-12:10 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 0.886 | -106.574 | 0.000 | 0.000 | 23.604 | 102.498 | 26.357 | 18.776 | 0.000 | 0.581 | 0.000 | 0.000 | -8.679 | 0.000 | -15.352 | -42.097 |
SMSTORE1 | 0.000 | 0.000 | 1.134 | -57.802 | 0.000 | 0.000 | 11.648 | 56.486 | 13.179 | 9.276 | 0.000 | 0.316 | 0.001 | 0.000 | -4.530 | 0.000 | -7.895 | -21.812 |
SMSTORE2 | 0.000 | 0.000 | 1.219 | -40.636 | 0.000 | 0.000 | 7.024 | 40.039 | 10.467 | 9.272 | 0.000 | 0.314 | 0.001 | 0.000 | -4.544 | 0.000 | -8.058 | -15.097 |
SMSTORE3 | 0.000 | 0.000 | 1.223 | -39.544 | 0.000 | 0.000 | 7.031 | 40.039 | 10.467 | 9.286 | 0.000 | 0.314 | 0.000 | 0.000 | -4.503 | 0.000 | -8.023 | -16.289 |
SMSTORE4 | 0.000 | 0.000 | 1.223 | -37.161 | 0.000 | 0.000 | 7.044 | 40.039 | 10.467 | 9.311 | 0.000 | 0.314 | 0.001 | 0.000 | -4.446 | 0.000 | -7.962 | -18.829 |
LGSTORE2 | 0.000 | 0.000 | 0.936 | -67.207 | 0.000 | 0.000 | 24.346 | 53.048 | 19.261 | 18.774 | 0.000 | 0.564 | 0.000 | 0.000 | -8.607 | 0.000 | -14.235 | -26.880 |
SMSTORE5 | 0.000 | 0.000 | 1.279 | -32.704 | 0.000 | 0.000 | 12.087 | 27.343 | 9.631 | 9.344 | 0.000 | 0.313 | 0.000 | 0.000 | -4.339 | 0.000 | -7.971 | -14.983 |
SMSTORE6 | 0.000 | 0.000 | 1.276 | -32.157 | 0.000 | 0.000 | 12.091 | 27.343 | 9.631 | 9.352 | 0.000 | 0.313 | 0.000 | 0.000 | -4.325 | 0.000 | -7.958 | -15.565 |
SMSTORE7 | 0.000 | 0.000 | 1.286 | -29.983 | 0.000 | 0.000 | 12.121 | 27.343 | 9.631 | 9.388 | 0.000 | 0.314 | 0.000 | 0.000 | -4.251 | 0.000 | -7.869 | -17.980 |
SMSTORE8 | 0.000 | 0.000 | 1.455 | -28.278 | 0.000 | 0.000 | 12.176 | 27.343 | 9.631 | 9.462 | 0.000 | 0.327 | 0.000 | 0.000 | -3.990 | 0.000 | -9.374 | -18.752 |
Total Facility | 0.000 | 0.000 | 11.917 | -472.046 | 0.000 | 0.000 | 129.172 | 441.522 | 128.721 | 112.242 | 0.000 | 3.669 | 0.005 | 0.000 | -52.215 | 0.000 | -94.696 | -208.285 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 10-JUL-08:62 | 0.00 | 0.00 | 0.00 | -30981.70 | 0.00 | 0.00 | 181.85 | 2800.74 | 749.03 | 280.94 | 0.00 | 0.00 | 27174.80 | 0.00 | -0.00 | 0.00 | -205.67 | 0.00 |
SMSTORE1 | 16-OCT-20:52 | 0.00 | 0.00 | 0.00 | -19720.66 | 0.00 | 0.00 | 591.09 | 2932.57 | 674.13 | 0.00 | 0.00 | 0.00 | 15730.96 | 0.00 | -201.08 | 0.00 | -7.01 | 0.00 |
SMSTORE2 | 18-OCT-07:02 | 0.00 | 0.00 | 0.00 | -20066.10 | 0.00 | 0.00 | 87.50 | 1368.01 | 374.52 | 227.49 | 0.00 | 0.00 | 18164.68 | 0.00 | -0.00 | 0.00 | -156.09 | 0.00 |
SMSTORE3 | 18-OCT-07:02 | 0.00 | 0.00 | 0.00 | -20119.70 | 0.00 | 0.00 | 87.49 | 1368.01 | 374.52 | 227.44 | 0.00 | 0.00 | 18218.27 | 0.00 | -0.00 | 0.00 | -156.03 | 0.00 |
SMSTORE4 | 18-OCT-07:02 | 0.00 | 0.00 | 0.00 | -19927.18 | 0.00 | 0.00 | 88.29 | 1368.01 | 374.52 | 229.34 | 0.00 | 0.00 | 18020.65 | 0.00 | -0.00 | 0.00 | -153.62 | 0.00 |
LGSTORE2 | 18-OCT-08:62 | 0.00 | 0.00 | 0.00 | -31839.12 | 0.00 | 0.00 | 404.17 | 1971.84 | 749.03 | 1668.48 | 0.00 | 0.00 | 27142.86 | 0.00 | -0.00 | 0.00 | -97.27 | 0.00 |
SMSTORE5 | 18-OCT-08:62 | 0.00 | 0.00 | 0.00 | -17249.17 | 0.00 | 0.00 | 195.19 | 1016.37 | 374.52 | 828.54 | 0.00 | 0.00 | 14896.63 | 0.00 | -0.00 | 0.00 | -62.08 | 0.00 |
SMSTORE6 | 18-OCT-08:62 | 0.00 | 0.00 | 0.00 | -17147.81 | 0.00 | 0.00 | 195.86 | 1016.37 | 374.52 | 829.46 | 0.00 | 0.00 | 14792.80 | 0.00 | -0.00 | 0.00 | -61.19 | 0.00 |
SMSTORE7 | 18-OCT-08:62 | 0.00 | 0.00 | 0.00 | -16947.86 | 0.00 | 0.00 | 198.52 | 1016.37 | 374.52 | 832.81 | 0.00 | 0.00 | 14583.05 | 0.00 | -0.00 | 0.00 | -57.40 | 0.00 |
SMSTORE8 | 30-SEP-08:61 | 0.00 | 0.00 | 0.00 | -16483.69 | 0.00 | 0.00 | 184.76 | 1016.37 | 374.52 | 975.04 | 0.00 | 2.04 | 13930.98 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 18-OCT-08:62 | 0.00 | 0.00 | 0.00 | -149990.26 | 0.00 | 0.00 | 2061.23 | 18179.18 | 5393.02 | 10035.60 | 0.00 | 0.00 | 114992.41 | 0.00 | 0.00 | 0.00 | -671.19 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 30-MAR-08:62 | 0.00 | 0.00 | 28029.18 | 0.00 | 0.00 | 0.00 | 240.90 | 2800.74 | 749.03 | 969.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -617.06 | -32171.78 |
SMSTORE1 | 16-OCT-08:06 | 0.00 | 0.00 | 2315.06 | 0.00 | 0.00 | 0.00 | 82.59 | 1543.46 | 374.52 | 1028.44 | 0.00 | 104.61 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5448.66 |
SMSTORE2 | 15-OCT-16:02 | 0.00 | 0.00 | 2011.95 | 0.00 | 0.00 | 0.00 | 98.50 | 1368.01 | 374.52 | 472.41 | 0.00 | 820.21 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5145.61 |
SMSTORE3 | 15-OCT-16:02 | 0.00 | 0.00 | 2014.84 | 0.00 | 0.00 | 0.00 | 98.50 | 1368.01 | 374.52 | 472.52 | 0.00 | 820.34 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5148.73 |
SMSTORE4 | 15-OCT-16:02 | 0.00 | 0.00 | 2018.38 | 0.00 | 0.00 | 0.00 | 98.50 | 1368.01 | 374.52 | 472.91 | 0.00 | 821.18 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5153.50 |
LGSTORE2 | 30-MAR-08:62 | 0.00 | 0.00 | 26769.23 | 0.00 | 0.00 | 0.00 | 529.33 | 1971.84 | 749.03 | 961.49 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -546.98 | -30433.94 |
SMSTORE5 | 30-MAR-08:62 | 0.00 | 0.00 | 5120.50 | 0.00 | 0.00 | 0.00 | 258.00 | 1016.37 | 374.52 | 472.79 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -300.35 | -6941.82 |
SMSTORE6 | 30-MAR-08:62 | 0.00 | 0.00 | 6347.79 | 0.00 | 0.00 | 0.00 | 258.92 | 1016.37 | 374.52 | 474.39 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -300.23 | -8171.75 |
SMSTORE7 | 30-MAR-08:62 | 0.00 | 0.00 | 12966.80 | 0.00 | 0.00 | 0.00 | 263.84 | 1016.37 | 374.52 | 482.66 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -299.59 | -14804.58 |
SMSTORE8 | 30-MAR-08:62 | 0.00 | 0.00 | 24965.05 | 0.00 | 0.00 | 0.00 | 276.22 | 1016.37 | 374.52 | 505.20 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -358.30 | -26779.05 |
Total Facility | 30-MAR-08:62 | -3810.49 | 3810.49 | 104198.55 | -3810.49 | 0.00 | 0.00 | 2631.66 | 18179.18 | 5393.02 | 5712.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3643.68 | -128660.25 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.9159 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.9159 | 0.2148 | 1.0000 | Not calculated | 0.4115 | 0.2148 | ||
PSZ-AC_2:2 | 0.9947 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0070 | 0.2043 | 1.0000 | Not calculated | 0.2057 | 0.2043 | ||
PSZ-AC_3:3 | 0.9881 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0041 | 0.2049 | 1.0000 | Not calculated | 0.2057 | 0.2049 | ||
PSZ-AC_4:4 | 0.9818 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0071 | 0.2043 | 1.0000 | Not calculated | 0.2057 | 0.2043 | ||
PSZ-AC_5:5 | 0.9871 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0025 | 0.2052 | 1.0000 | Not calculated | 0.2057 | 0.2052 | ||
PSZ-AC_6:6 | 1.7921 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.8441 | 0.2231 | 1.0000 | Not calculated | 0.4115 | 0.2231 | ||
PSZ-AC_7:7 | 0.9714 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9728 | 0.2115 | 1.0000 | Not calculated | 0.2057 | 0.2115 | ||
PSZ-AC_8:8 | 0.9665 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9683 | 0.2125 | 1.0000 | Not calculated | 0.2057 | 0.2125 | ||
PSZ-AC_9:9 | 0.9617 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9643 | 0.2133 | 1.0000 | Not calculated | 0.2057 | 0.2133 | ||
PSZ-AC_10:10 | 1.0518 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0606 | 0.1940 | 1.0000 | Not calculated | 0.2057 | 0.1940 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.9159 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.9159 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2148 | ||
PSZ-AC_2:2 | 0.9947 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9947 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2068 | ||
PSZ-AC_3:3 | 0.9881 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9881 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2082 | ||
PSZ-AC_4:4 | 0.9818 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9818 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2096 | ||
PSZ-AC_5:5 | 0.9871 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9871 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2084 | ||
PSZ-AC_6:6 | 1.7921 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.7921 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2296 | ||
PSZ-AC_7:7 | 0.9714 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9714 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2118 | ||
PSZ-AC_8:8 | 0.9665 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9665 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2129 | ||
PSZ-AC_9:9 | 0.9617 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9617 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2139 | ||
PSZ-AC_10:10 | 1.0518 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0518 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1956 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9159 | 1.9159 | 1.9159 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9947 | 0.9947 | 0.9947 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9881 | 0.9881 | 0.9881 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9818 | 0.9818 | 0.9818 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9871 | 0.9871 | 0.9871 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.7921 | 1.7921 | 1.7921 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9714 | 0.9714 | 0.9714 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9665 | 0.9665 | 0.9665 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9617 | 0.9617 | 0.9617 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0518 | 1.0518 | 1.0518 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.9159 | 1.9159 | 1.9159 | 1.9159 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 0.9947 | 1.0070 | 0.9947 | 0.9947 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 0.9881 | 1.0041 | 0.9881 | 0.9881 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 0.9818 | 1.0071 | 0.9818 | 0.9818 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 0.9871 | 1.0025 | 0.9871 | 0.9871 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.7921 | 1.8441 | 1.7921 | 1.7921 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.9714 | 0.9728 | 0.9714 | 0.9714 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9665 | 0.9683 | 0.9665 | 0.9665 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.9617 | 0.9643 | 0.9617 | 0.9617 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.0518 | 1.0606 | 1.0518 | 1.0518 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9159 | 1.9159 | 1.9159 | No | 0.4115 | 0.5725 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9947 | 0.9947 | 0.9947 | No | 0.2057 | 0.6068 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9881 | 0.9881 | 0.9881 | No | 0.2057 | 0.6001 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9818 | 0.9818 | 0.9818 | No | 0.2057 | 0.5934 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9871 | 0.9871 | 0.9871 | No | 0.2057 | 0.5801 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.7921 | 1.7921 | 1.7921 | No | 0.4115 | 0.5960 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9714 | 0.9714 | 0.9714 | No | 0.2057 | 0.5517 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9665 | 0.9665 | 0.9665 | No | 0.2057 | 0.5494 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9617 | 0.9617 | 0.9617 | No | 0.2057 | 0.5208 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0518 | 1.0518 | 1.0518 | No | 0.2057 | 0.4081 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.9159 | 1.9159 | 1.9159 | 1.9159 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 0.9947 | 0.9947 | 0.9947 | 0.9947 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 0.9881 | 0.9881 | 0.9881 | 0.9881 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 0.9818 | 0.9818 | 0.9818 | 0.9818 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 0.9871 | 0.9871 | 0.9871 | 0.9871 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.7921 | 1.7921 | 1.7921 | 1.7921 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.9714 | 0.9714 | 0.9714 | 0.9714 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9665 | 0.9665 | 0.9665 | 0.9665 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.9617 | 0.9617 | 0.9617 | 0.9617 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.0518 | 1.0518 | 1.0518 | 1.0518 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 2.44 | 48795.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 66.94 | 38180.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 441.52 | 27522.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 100.05 | 7619.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.72 | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 179.14 | 11572.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 62.29 | 11495.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.72 | 978.66 |
Natural Gas | 0.00 | 2.44 |
Additional | 0.00 | 0.00 |
Total | 128.72 | 981.11 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 211.22 |
Space Heating | 0.00 |
Space Cooling | 32.02 |
Fans (All) | 85.70 |
Service Water Heating | 29.80 |
Receptacle Equipment | 61.58 |
Miscellaneous (All) | 468.19 |
Subtotal | 468.19 |
Natural Gas [MJ/m2] | |
Space Heating | 1.17 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 1.17 |
Subtotal | 1.17 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 45.00 |
Space Heating | 0.25 |
Space Cooling | 6.82 |
Fans (All) | 18.26 |
Service Water Heating | 6.35 |
Receptacle Equipment | 13.12 |
Miscellaneous | 10.20 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3238. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3296. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 4469. | 8760. |
LTG_SCH_BASE_LPD1 | 4391. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 3584. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4888. | 8760. |
TYPE2_EQUIP_SCH | 3911. | 8760. |
TYPE3_EQUIP_SCH | 3600. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8759.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 0.17 | 0.00 | 0.00 | 0.00 |
Average | 8759.95 | 0.05 | 0.00 | 0.00 | 0.00 |
Sum | 87599.50 | 0.50 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25474.83 | 0.17 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25474.83 | 0.17 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25474.83 | 0.17 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93211.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45912.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45912.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45912.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45912.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 25474.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 93211.00 | 0.17 | 0.00 | 0.00 | 0.00 |
Average | 48610.15 | 0.05 | 0.00 | 0.00 | 0.00 |
Sum | 486101.50 | 0.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 8247.00 | 513.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8188.33 | 571.67 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 7917.17 | 842.83 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 7929.33 | 830.67 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 7956.83 | 803.17 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8047.83 | 712.17 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 7987.00 | 773.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8008.83 | 751.17 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8061.83 | 698.17 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8259.17 | 500.83 | 0.00 | 0.00 | 0.00 |
Min | 7917.17 | 500.83 | 0.00 | 0.00 | 0.00 |
Max | 8259.17 | 842.83 | 0.00 | 0.00 | 0.00 |
Average | 8060.33 | 699.67 | 0.00 | 0.00 | 0.00 |
Sum | 80603.33 | 6996.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 88153.33 | 887.67 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 42944.83 | 832.17 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25060.50 | 414.50 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25047.67 | 427.33 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25021.17 | 453.83 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 92362.67 | 848.33 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 44988.00 | 924.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 44972.67 | 939.33 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 44915.67 | 996.33 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 44838.00 | 1074.00 | 0.00 | 0.00 | 0.00 |
Min | 25021.17 | 414.50 | 0.00 | 0.00 | 0.00 |
Max | 92362.67 | 1074.00 | 0.00 | 0.00 | 0.00 |
Average | 47830.45 | 779.75 | 0.00 | 0.00 | 0.00 |
Sum | 478304.50 | 7797.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Environment
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
For: Environment
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
For: Environment
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.726085E+10 | 11105.80 | 21-JAN-09:02 | 14.33 | 13.47 | 0.133002E+10 | 1685.92 | 20-JAN-13:20 | 14.33 | 13.47 |
February | 0.606721E+10 | 7682.60 | 03-FEB-14:00 | 23.00 | 8.84 | 0.119017E+10 | 1685.86 | 18-FEB-13:00 | 19.00 | 13.20 |
March | 0.667540E+10 | 7758.01 | 23-MAR-17:10 | 18.67 | 15.66 | 0.127692E+10 | 1685.94 | 12-MAR-12:00 | 18.67 | 15.66 |
April | 0.784112E+10 | 21922.53 | 27-APR-08:62 | 17.33 | 15.22 | 0.134854E+10 | 1685.96 | 08-APR-12:39 | 17.33 | 15.22 |
May | 0.805537E+10 | 24673.61 | 03-MAY-08:62 | 19.00 | 15.78 | 0.139270E+10 | 1685.94 | 29-MAY-12:20 | 20.33 | 15.59 |
June | 0.935692E+10 | 30316.50 | 21-JUN-08:62 | 19.50 | 15.48 | 0.135409E+10 | 1685.98 | 18-JUN-17:10 | 19.50 | 15.48 |
July | 0.118645E+11 | 30988.53 | 10-JUL-08:62 | 19.33 | 14.88 | 0.141337E+10 | 1685.99 | 30-JUL-17:00 | 19.00 | 17.66 |
August | 0.120989E+11 | 28932.75 | 30-AUG-08:62 | 19.50 | 16.07 | 0.139472E+10 | 1685.99 | 27-AUG-16:00 | 19.50 | 16.07 |
September | 0.108065E+11 | 30418.19 | 28-SEP-08:62 | 17.33 | 15.31 | 0.136515E+10 | 1685.98 | 24-SEP-12:39 | 17.33 | 15.31 |
October | 0.113303E+11 | 29677.91 | 18-OCT-08:62 | 21.67 | 11.19 | 0.140949E+10 | 1685.98 | 01-OCT-12:39 | 21.67 | 11.19 |
November | 0.759066E+10 | 10807.20 | 28-NOV-09:02 | 20.17 | 7.85 | 0.134607E+10 | 1685.97 | 10-NOV-13:20 | 20.17 | 7.85 |
December | 0.762492E+10 | 23261.26 | 05-DEC-09:02 | 24.33 | 12.02 | 0.135156E+10 | 1685.85 | 25-DEC-13:50 | 22.00 | 9.80 |
Annual Sum or Average | 0.106573E+12 | 0.161728E+11 | ||||||||
Minimum of Months | 0.606721E+10 | 7682.60 | 14.33 | 7.85 | 0.119017E+10 | 1685.85 | 14.33 | 7.85 | ||
Maximum of Months | 0.120989E+11 | 30988.53 | 24.33 | 16.07 | 0.141337E+10 | 1685.99 | 22.00 | 17.66 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.374506E+10 | 18997.96 | 15-JAN-18:01 | 16.67 | 11.87 | 0.697203E+09 | 842.92 | 20-JAN-13:20 | 18.33 | 15.04 |
February | 0.306556E+10 | 17275.09 | 05-FEB-18:10 | 12.83 | 9.79 | 0.628162E+09 | 842.90 | 18-FEB-13:00 | 19.00 | 13.20 |
March | 0.316425E+10 | 8221.85 | 24-MAR-08:63 | 14.00 | 13.42 | 0.682953E+09 | 842.94 | 12-MAR-12:00 | 14.00 | 13.42 |
April | 0.439106E+10 | 16253.64 | 28-APR-08:62 | 15.33 | 12.80 | 0.680305E+09 | 842.94 | 08-APR-12:09 | 15.33 | 12.80 |
May | 0.452484E+10 | 18768.81 | 24-MAY-08:62 | 18.00 | 8.80 | 0.700797E+09 | 842.93 | 29-MAY-12:20 | 20.33 | 15.59 |
June | 0.523647E+10 | 17471.73 | 23-JUN-08:62 | 18.50 | 14.15 | 0.677455E+09 | 842.95 | 18-JUN-17:10 | 18.50 | 14.15 |
July | 0.641958E+10 | 16991.35 | 08-JUL-08:62 | 17.33 | 14.65 | 0.705262E+09 | 842.96 | 30-JUL-17:10 | 20.67 | 18.25 |
August | 0.658274E+10 | 17320.46 | 22-AUG-08:62 | 17.58 | 14.22 | 0.696595E+09 | 842.95 | 27-AUG-16:10 | 21.67 | 17.87 |
September | 0.597027E+10 | 18063.05 | 02-SEP-08:62 | 17.17 | 12.94 | 0.682158E+09 | 842.95 | 24-SEP-12:09 | 22.00 | 18.09 |
October | 0.637990E+10 | 19722.31 | 16-OCT-20:52 | 18.00 | 11.03 | 0.703199E+09 | 842.96 | 01-OCT-17:10 | 18.00 | 11.03 |
November | 0.430361E+10 | 18154.44 | 28-NOV-09:02 | 20.17 | 7.85 | 0.681607E+09 | 842.94 | 10-NOV-13:20 | 20.17 | 7.85 |
December | 0.401762E+10 | 18576.49 | 19-DEC-09:02 | 19.67 | 7.57 | 0.704142E+09 | 842.90 | 25-DEC-18:30 | 14.50 | 8.29 |
Annual Sum or Average | 0.578009E+11 | 0.823984E+10 | ||||||||
Minimum of Months | 0.306556E+10 | 8221.85 | 12.83 | 7.57 | 0.628162E+09 | 842.90 | 14.00 | 7.85 | ||
Maximum of Months | 0.658274E+10 | 19722.31 | 20.17 | 14.65 | 0.705262E+09 | 842.96 | 22.00 | 18.25 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.264983E+10 | 16108.29 | 21-JAN-08:62 | 13.17 | 13.07 | 0.410751E+09 | 842.90 | 14-JAN-13:39 | 13.17 | 13.07 |
February | 0.214465E+10 | 7254.05 | 02-FEB-08:63 | 12.50 | 10.66 | 0.372173E+09 | 842.90 | 18-FEB-13:00 | 19.00 | 13.20 |
March | 0.229772E+10 | 7748.04 | 24-MAR-07:03 | 13.17 | 13.07 | 0.413816E+09 | 842.90 | 11-MAR-13:20 | 13.17 | 13.07 |
April | 0.296693E+10 | 16071.77 | 27-APR-07:03 | 16.17 | 14.82 | 0.408740E+09 | 842.94 | 08-APR-12:09 | 16.17 | 14.82 |
May | 0.304397E+10 | 16760.95 | 04-MAY-07:03 | 18.17 | 14.03 | 0.424701E+09 | 842.90 | 27-MAY-12:20 | 19.00 | 13.73 |
June | 0.364795E+10 | 17534.08 | 23-JUN-07:02 | 17.17 | 13.94 | 0.416234E+09 | 842.94 | 24-JUN-12:20 | 22.33 | 16.50 |
July | 0.449444E+10 | 17078.43 | 10-JUL-07:02 | 18.17 | 14.44 | 0.419691E+09 | 842.95 | 29-JUL-12:09 | 23.00 | 19.54 |
August | 0.480522E+10 | 17627.62 | 22-AUG-07:02 | 16.22 | 13.67 | 0.431290E+09 | 842.94 | 26-AUG-12:09 | 24.33 | 19.43 |
September | 0.421896E+10 | 18225.86 | 02-SEP-07:03 | 16.17 | 12.63 | 0.410315E+09 | 842.95 | 23-SEP-12:09 | 22.00 | 17.98 |
October | 0.454773E+10 | 20076.94 | 18-OCT-07:02 | 17.67 | 10.06 | 0.419970E+09 | 842.92 | 21-OCT-12:50 | 20.83 | 15.02 |
November | 0.296072E+10 | 15754.75 | 19-NOV-09:02 | 24.33 | 12.78 | 0.404552E+09 | 842.90 | 18-NOV-13:09 | 24.33 | 12.78 |
December | 0.285729E+10 | 9810.81 | 19-DEC-08:63 | 17.33 | 6.12 | 0.413812E+09 | 842.90 | 16-DEC-13:39 | 17.33 | 6.12 |
Annual Sum or Average | 0.406354E+11 | 0.494605E+10 | ||||||||
Minimum of Months | 0.214465E+10 | 7254.05 | 12.50 | 6.12 | 0.372173E+09 | 842.90 | 13.17 | 6.12 | ||
Maximum of Months | 0.480522E+10 | 20076.94 | 24.33 | 14.82 | 0.431290E+09 | 842.95 | 24.33 | 19.54 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.250852E+10 | 15317.09 | 21-JAN-08:62 | 13.17 | 13.07 | 0.409108E+09 | 842.90 | 14-JAN-13:39 | 13.17 | 13.07 |
February | 0.203725E+10 | 6292.08 | 02-FEB-08:63 | 12.50 | 10.66 | 0.370837E+09 | 842.90 | 18-FEB-13:00 | 19.00 | 13.20 |
March | 0.217674E+10 | 7053.91 | 24-MAR-07:03 | 13.17 | 13.07 | 0.411404E+09 | 842.90 | 11-MAR-13:00 | 13.17 | 13.07 |
April | 0.285186E+10 | 16055.72 | 27-APR-07:03 | 16.17 | 14.82 | 0.408507E+09 | 842.94 | 08-APR-12:09 | 16.17 | 14.82 |
May | 0.294321E+10 | 16758.45 | 04-MAY-07:03 | 18.17 | 14.03 | 0.424598E+09 | 842.90 | 27-MAY-12:20 | 19.00 | 13.73 |
June | 0.357308E+10 | 17540.26 | 23-JUN-07:02 | 17.17 | 13.94 | 0.416207E+09 | 842.94 | 24-JUN-12:20 | 22.33 | 16.50 |
July | 0.444530E+10 | 17068.94 | 10-JUL-07:02 | 18.17 | 14.44 | 0.419676E+09 | 842.95 | 29-JUL-12:09 | 23.00 | 19.54 |
August | 0.475865E+10 | 17638.38 | 22-AUG-07:02 | 16.22 | 13.67 | 0.431276E+09 | 842.94 | 26-AUG-12:09 | 24.33 | 19.43 |
September | 0.415729E+10 | 17699.59 | 02-SEP-07:03 | 16.17 | 12.63 | 0.410294E+09 | 842.95 | 23-SEP-12:09 | 22.00 | 17.98 |
October | 0.450436E+10 | 20130.60 | 18-OCT-07:02 | 17.67 | 10.06 | 0.419952E+09 | 842.92 | 21-OCT-12:50 | 20.83 | 15.02 |
November | 0.285076E+10 | 15711.53 | 19-NOV-09:02 | 24.33 | 12.78 | 0.404372E+09 | 842.90 | 18-NOV-13:09 | 24.33 | 12.78 |
December | 0.273685E+10 | 8766.64 | 07-DEC-08:63 | 14.67 | 10.50 | 0.413008E+09 | 842.90 | 16-DEC-13:00 | 24.80 | 13.49 |
Annual Sum or Average | 0.395439E+11 | 0.493924E+10 | ||||||||
Minimum of Months | 0.203725E+10 | 6292.08 | 12.50 | 10.06 | 0.370837E+09 | 842.90 | 13.17 | 12.78 | ||
Maximum of Months | 0.475865E+10 | 20130.60 | 24.33 | 14.82 | 0.431276E+09 | 842.95 | 24.80 | 19.54 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.227751E+10 | 13522.46 | 21-JAN-08:62 | 13.17 | 13.07 | 0.406711E+09 | 842.90 | 14-JAN-13:09 | 13.17 | 13.07 |
February | 0.184341E+10 | 4263.54 | 02-FEB-08:63 | 12.50 | 10.66 | 0.367791E+09 | 842.90 | 04-FEB-13:50 | 20.17 | 9.01 |
March | 0.196115E+10 | 5410.91 | 24-MAR-07:03 | 13.17 | 13.07 | 0.406757E+09 | 842.90 | 11-MAR-13:09 | 13.17 | 13.07 |
April | 0.262975E+10 | 14683.11 | 27-APR-07:03 | 16.17 | 14.82 | 0.407954E+09 | 842.94 | 08-APR-12:09 | 16.17 | 14.82 |
May | 0.272823E+10 | 15528.61 | 05-MAY-07:03 | 17.17 | 15.06 | 0.424311E+09 | 842.90 | 13-MAY-12:09 | 18.00 | 13.19 |
June | 0.338687E+10 | 17345.80 | 23-JUN-07:02 | 17.17 | 13.94 | 0.416137E+09 | 842.94 | 24-JUN-12:20 | 22.33 | 16.50 |
July | 0.427635E+10 | 16866.79 | 10-JUL-07:02 | 18.17 | 14.44 | 0.419627E+09 | 842.95 | 29-JUL-12:09 | 23.00 | 19.54 |
August | 0.458816E+10 | 17449.01 | 22-AUG-07:02 | 16.22 | 13.67 | 0.431227E+09 | 842.94 | 26-AUG-12:09 | 24.33 | 19.43 |
September | 0.398297E+10 | 17051.51 | 30-SEP-07:01 | 23.92 | 14.07 | 0.410236E+09 | 842.95 | 23-SEP-12:09 | 23.92 | 14.07 |
October | 0.433339E+10 | 19937.96 | 18-OCT-07:02 | 17.67 | 10.06 | 0.419884E+09 | 842.92 | 21-OCT-12:50 | 20.83 | 15.02 |
November | 0.263511E+10 | 15505.28 | 19-NOV-09:02 | 24.33 | 12.78 | 0.403893E+09 | 842.90 | 18-NOV-13:39 | 24.33 | 12.78 |
December | 0.251777E+10 | 7334.24 | 07-DEC-08:63 | 14.67 | 10.50 | 0.411129E+09 | 842.90 | 30-DEC-13:30 | 19.50 | 9.97 |
Annual Sum or Average | 0.371607E+11 | 0.492566E+10 | ||||||||
Minimum of Months | 0.184341E+10 | 4263.54 | 12.50 | 10.06 | 0.367791E+09 | 842.90 | 13.17 | 9.01 | ||
Maximum of Months | 0.458816E+10 | 19937.96 | 24.33 | 15.06 | 0.431227E+09 | 842.95 | 24.33 | 19.54 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.437258E+10 | 11191.25 | 21-JAN-09:02 | 14.33 | 13.47 | 0.136306E+10 | 2247.80 | 14-JAN-15:50 | 14.33 | 13.47 |
February | 0.378549E+10 | 7033.91 | 03-FEB-14:00 | 23.00 | 8.84 | 0.121506E+10 | 2247.77 | 18-FEB-15:20 | 16.67 | 13.33 |
March | 0.412860E+10 | 7210.85 | 23-MAR-14:10 | 22.83 | 17.30 | 0.134135E+10 | 2247.80 | 11-MAR-15:09 | 22.83 | 17.30 |
April | 0.469938E+10 | 16379.63 | 27-APR-08:62 | 17.33 | 15.22 | 0.139312E+10 | 2247.93 | 08-APR-14:09 | 17.33 | 15.22 |
May | 0.483289E+10 | 21025.84 | 04-MAY-08:62 | 19.17 | 14.74 | 0.144619E+10 | 2247.90 | 06-MAY-14:00 | 20.00 | 15.11 |
June | 0.585239E+10 | 29076.97 | 21-JUN-08:62 | 19.50 | 15.48 | 0.142747E+10 | 2247.94 | 24-JUN-14:50 | 21.17 | 16.05 |
July | 0.745552E+10 | 28561.29 | 07-JUL-08:62 | 19.33 | 15.40 | 0.143719E+10 | 2247.97 | 15-JUL-14:00 | 22.00 | 18.09 |
August | 0.803081E+10 | 27842.05 | 30-AUG-08:62 | 19.50 | 16.07 | 0.147948E+10 | 2247.96 | 12-AUG-14:00 | 19.50 | 16.07 |
September | 0.695573E+10 | 29259.69 | 30-SEP-08:61 | 25.38 | 14.89 | 0.140798E+10 | 2247.97 | 23-SEP-14:20 | 25.38 | 14.89 |
October | 0.755546E+10 | 31853.35 | 18-OCT-08:62 | 21.67 | 11.19 | 0.143407E+10 | 2247.94 | 14-OCT-14:09 | 21.67 | 11.19 |
November | 0.475841E+10 | 27778.61 | 19-NOV-10:02 | 26.00 | 14.09 | 0.136271E+10 | 2247.81 | 18-NOV-15:09 | 26.00 | 14.09 |
December | 0.477883E+10 | 15463.17 | 05-DEC-09:02 | 24.33 | 12.02 | 0.138124E+10 | 2247.81 | 16-DEC-15:00 | 21.00 | 13.55 |
Annual Sum or Average | 0.672061E+11 | 0.166889E+11 | ||||||||
Minimum of Months | 0.378549E+10 | 7033.91 | 14.33 | 8.84 | 0.121506E+10 | 2247.77 | 14.33 | 11.19 | ||
Maximum of Months | 0.803081E+10 | 31853.35 | 26.00 | 17.30 | 0.147948E+10 | 2247.97 | 26.00 | 18.09 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.192296E+10 | 11784.28 | 21-JAN-09:02 | 14.33 | 13.47 | 0.695682E+09 | 1123.87 | 14-JAN-15:30 | 14.33 | 13.47 |
February | 0.155748E+10 | 3716.94 | 03-FEB-14:00 | 23.00 | 8.84 | 0.625585E+09 | 1123.87 | 11-FEB-15:00 | 18.00 | 13.88 |
March | 0.166394E+10 | 3807.82 | 23-MAR-14:10 | 22.83 | 17.30 | 0.692825E+09 | 1123.87 | 11-MAR-15:09 | 22.83 | 17.30 |
April | 0.225819E+10 | 15139.32 | 27-APR-08:62 | 17.33 | 15.22 | 0.701290E+09 | 1123.91 | 08-APR-14:20 | 17.33 | 15.22 |
May | 0.234857E+10 | 15727.44 | 04-MAY-08:62 | 19.17 | 14.74 | 0.726956E+09 | 1123.89 | 06-MAY-14:00 | 20.00 | 15.11 |
June | 0.299287E+10 | 16504.57 | 23-JUN-08:62 | 18.50 | 14.15 | 0.714415E+09 | 1123.91 | 24-JUN-14:30 | 21.50 | 16.19 |
July | 0.386898E+10 | 16021.06 | 08-JUL-08:62 | 17.33 | 14.65 | 0.718906E+09 | 1123.94 | 15-JUL-14:00 | 22.00 | 18.09 |
August | 0.417588E+10 | 16360.18 | 22-AUG-08:62 | 17.58 | 14.22 | 0.740019E+09 | 1123.93 | 12-AUG-14:00 | 17.58 | 14.22 |
September | 0.358437E+10 | 16230.83 | 27-SEP-08:62 | 16.17 | 14.19 | 0.704609E+09 | 1123.94 | 09-SEP-14:00 | 16.17 | 14.19 |
October | 0.392271E+10 | 17257.49 | 18-OCT-08:62 | 21.67 | 11.19 | 0.717435E+09 | 1123.90 | 21-OCT-14:00 | 20.00 | 15.11 |
November | 0.225124E+10 | 14621.44 | 19-NOV-10:02 | 26.00 | 14.09 | 0.688309E+09 | 1123.87 | 18-NOV-15:09 | 26.00 | 14.09 |
December | 0.215630E+10 | 14674.32 | 05-DEC-09:02 | 24.33 | 12.02 | 0.703720E+09 | 1123.87 | 16-DEC-15:09 | 22.75 | 13.56 |
Annual Sum or Average | 0.327035E+11 | 0.842975E+10 | ||||||||
Minimum of Months | 0.155748E+10 | 3716.94 | 14.33 | 8.84 | 0.625585E+09 | 1123.87 | 14.33 | 13.47 | ||
Maximum of Months | 0.417588E+10 | 17257.49 | 26.00 | 17.30 | 0.740019E+09 | 1123.94 | 26.00 | 18.09 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.188758E+10 | 11132.64 | 21-JAN-09:02 | 14.33 | 13.47 | 0.695044E+09 | 1123.87 | 14-JAN-15:39 | 14.33 | 13.47 |
February | 0.153176E+10 | 3666.98 | 03-FEB-14:00 | 23.00 | 8.84 | 0.624601E+09 | 1123.87 | 11-FEB-15:00 | 18.00 | 13.88 |
March | 0.164098E+10 | 3760.15 | 23-MAR-14:10 | 22.83 | 17.30 | 0.691623E+09 | 1123.87 | 11-MAR-15:39 | 22.83 | 17.30 |
April | 0.221406E+10 | 14770.49 | 27-APR-08:62 | 17.33 | 15.22 | 0.701106E+09 | 1123.91 | 08-APR-14:20 | 17.33 | 15.22 |
May | 0.229885E+10 | 15616.73 | 04-MAY-08:62 | 19.17 | 14.74 | 0.726836E+09 | 1123.89 | 06-MAY-14:00 | 20.00 | 15.11 |
June | 0.293458E+10 | 16388.48 | 23-JUN-08:62 | 18.50 | 14.15 | 0.714384E+09 | 1123.91 | 24-JUN-14:30 | 21.50 | 16.19 |
July | 0.381363E+10 | 15911.38 | 08-JUL-08:62 | 17.33 | 14.65 | 0.718883E+09 | 1123.94 | 15-JUL-14:00 | 22.00 | 18.09 |
August | 0.411866E+10 | 16250.03 | 22-AUG-08:62 | 17.58 | 14.22 | 0.740000E+09 | 1123.93 | 12-AUG-14:00 | 17.58 | 14.22 |
September | 0.352812E+10 | 16118.00 | 27-SEP-08:62 | 16.17 | 14.19 | 0.704578E+09 | 1123.94 | 09-SEP-14:00 | 16.17 | 14.19 |
October | 0.386438E+10 | 17156.05 | 18-OCT-08:62 | 21.67 | 11.19 | 0.717411E+09 | 1123.90 | 21-OCT-14:00 | 20.00 | 15.11 |
November | 0.220756E+10 | 14547.32 | 19-NOV-10:02 | 26.00 | 14.09 | 0.688101E+09 | 1123.87 | 18-NOV-15:20 | 26.00 | 14.09 |
December | 0.211656E+10 | 14309.84 | 05-DEC-09:02 | 24.33 | 12.02 | 0.703174E+09 | 1123.87 | 16-DEC-15:09 | 22.75 | 13.56 |
Annual Sum or Average | 0.321567E+11 | 0.842574E+10 | ||||||||
Minimum of Months | 0.153176E+10 | 3666.98 | 14.33 | 8.84 | 0.624601E+09 | 1123.87 | 14.33 | 13.47 | ||
Maximum of Months | 0.411866E+10 | 17156.05 | 26.00 | 17.30 | 0.740000E+09 | 1123.94 | 26.00 | 18.09 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.170285E+10 | 8040.92 | 21-JAN-09:02 | 14.33 | 13.47 | 0.690556E+09 | 1123.87 | 14-JAN-15:09 | 14.33 | 13.47 |
February | 0.137057E+10 | 3426.78 | 03-FEB-14:00 | 23.00 | 8.84 | 0.617173E+09 | 1123.85 | 18-FEB-15:20 | 16.67 | 13.33 |
March | 0.148611E+10 | 3551.13 | 23-MAR-14:10 | 22.83 | 17.30 | 0.682859E+09 | 1123.87 | 11-MAR-15:39 | 22.83 | 17.30 |
April | 0.201942E+10 | 11131.51 | 27-APR-08:62 | 17.33 | 15.22 | 0.699710E+09 | 1123.91 | 08-APR-14:20 | 17.33 | 15.22 |
May | 0.208898E+10 | 13669.18 | 04-MAY-08:62 | 19.17 | 14.74 | 0.725836E+09 | 1123.88 | 06-MAY-14:00 | 20.00 | 15.11 |
June | 0.273698E+10 | 15552.65 | 23-JUN-08:62 | 18.50 | 14.15 | 0.714212E+09 | 1123.91 | 24-JUN-14:20 | 21.67 | 16.27 |
July | 0.366827E+10 | 15677.13 | 08-JUL-08:62 | 17.33 | 14.65 | 0.718804E+09 | 1123.94 | 15-JUL-14:00 | 22.00 | 18.09 |
August | 0.397076E+10 | 15488.49 | 22-AUG-08:62 | 17.58 | 14.22 | 0.739926E+09 | 1123.93 | 12-AUG-14:00 | 17.58 | 14.22 |
September | 0.335067E+10 | 15346.95 | 28-SEP-08:62 | 17.33 | 15.31 | 0.704434E+09 | 1123.94 | 09-SEP-14:00 | 17.33 | 15.31 |
October | 0.368209E+10 | 16955.98 | 18-OCT-08:62 | 21.67 | 11.19 | 0.717324E+09 | 1123.89 | 21-OCT-14:00 | 20.00 | 15.11 |
November | 0.198954E+10 | 14402.21 | 19-NOV-10:02 | 26.00 | 14.09 | 0.686379E+09 | 1123.87 | 18-NOV-15:09 | 26.00 | 14.09 |
December | 0.191613E+10 | 9600.41 | 05-DEC-09:02 | 24.33 | 12.02 | 0.698581E+09 | 1123.87 | 16-DEC-15:39 | 21.70 | 13.58 |
Annual Sum or Average | 0.299824E+11 | 0.839579E+10 | ||||||||
Minimum of Months | 0.137057E+10 | 3426.78 | 14.33 | 8.84 | 0.617173E+09 | 1123.85 | 14.33 | 13.33 | ||
Maximum of Months | 0.397076E+10 | 16955.98 | 26.00 | 17.30 | 0.739926E+09 | 1123.94 | 26.00 | 18.09 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.140588E+10 | 4003.86 | 18-JAN-13:40 | 25.07 | 14.79 | 0.682731E+09 | 1123.87 | 14-JAN-15:20 | 25.07 | 14.79 |
February | 0.103923E+10 | 3207.17 | 01-FEB-13:10 | 23.17 | 14.41 | 0.603956E+09 | 1123.85 | 18-FEB-15:00 | 16.00 | 13.03 |
March | 0.119885E+10 | 3529.68 | 23-MAR-14:10 | 22.83 | 17.30 | 0.670590E+09 | 1123.87 | 11-MAR-15:39 | 22.83 | 17.30 |
April | 0.191162E+10 | 5309.74 | 30-APR-09:03 | 22.50 | 15.57 | 0.696562E+09 | 1123.91 | 08-APR-14:30 | 22.50 | 15.57 |
May | 0.190757E+10 | 7914.17 | 04-MAY-08:62 | 19.17 | 14.74 | 0.722946E+09 | 1123.86 | 27-MAY-14:09 | 19.83 | 14.00 |
June | 0.264134E+10 | 15730.09 | 21-JUN-08:62 | 19.50 | 15.48 | 0.713635E+09 | 1123.92 | 24-JUN-14:09 | 21.83 | 16.34 |
July | 0.388906E+10 | 16132.18 | 04-JUL-09:02 | 22.00 | 15.93 | 0.718768E+09 | 1123.94 | 15-JUL-14:00 | 22.00 | 18.09 |
August | 0.418661E+10 | 15491.38 | 30-AUG-08:62 | 19.50 | 16.07 | 0.739866E+09 | 1123.94 | 12-AUG-14:00 | 19.50 | 16.07 |
September | 0.328230E+10 | 16483.49 | 30-SEP-08:61 | 25.38 | 14.89 | 0.703957E+09 | 1123.95 | 09-SEP-14:00 | 25.38 | 14.89 |
October | 0.357694E+10 | 15285.47 | 17-OCT-08:62 | 26.50 | 12.89 | 0.717059E+09 | 1123.89 | 21-OCT-14:00 | 20.00 | 15.11 |
November | 0.165822E+10 | 15329.91 | 19-NOV-10:02 | 26.00 | 14.09 | 0.681492E+09 | 1123.87 | 18-NOV-15:20 | 26.00 | 14.09 |
December | 0.157949E+10 | 4155.16 | 19-DEC-13:10 | 25.50 | 11.30 | 0.689173E+09 | 1123.87 | 16-DEC-15:09 | 25.50 | 11.30 |
Annual Sum or Average | 0.282771E+11 | 0.834074E+10 | ||||||||
Minimum of Months | 0.103923E+10 | 3207.17 | 19.17 | 11.30 | 0.603956E+09 | 1123.85 | 16.00 | 11.30 | ||
Maximum of Months | 0.418661E+10 | 16483.49 | 26.50 | 17.30 | 0.739866E+09 | 1123.95 | 26.00 | 18.09 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 76437217.08 | 2666.21 | 03-JAN-09:02 | 11.33 |
February | 69918561.63 | 818.37 | 25-FEB-09:00 | 11.00 |
March | 89119378.59 | 28029.09 | 30-MAR-08:62 | 9.50 |
April | 77039192.93 | 834.68 | 01-APR-08:65 | 15.67 |
May | 76191783.48 | 799.88 | 06-MAY-08:00 | 14.00 |
June | 67664642.33 | 914.21 | 25-JUN-07:10 | 18.17 |
July | 68639611.99 | 1287.20 | 30-JUL-07:07 | 18.33 |
August | 73012571.31 | 1134.84 | 20-AUG-07:07 | 19.03 |
September | 69109160.73 | 3822.58 | 29-SEP-08:05 | 29.67 |
October | 72953663.97 | 3410.89 | 16-OCT-08:04 | 28.50 |
November | 69722876.57 | 799.56 | 01-NOV-07:13 | 11.33 |
December | 76085624.57 | 1460.06 | 05-DEC-09:04 | 24.33 |
Annual Sum or Average | 0.885894E+09 | |||
Minimum of Months | 67664642.33 | 799.56 | 9.50 | |
Maximum of Months | 89119378.59 | 28029.09 | 29.67 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 96233460.38 | 1097.93 | 24-JAN-09:05 | 21.33 |
February | 89155820.92 | 1143.45 | 01-FEB-09:07 | 22.33 |
March | 0.103854E+09 | 1073.40 | 28-MAR-07:13 | 10.33 |
April | 92808548.03 | 1178.80 | 26-APR-08:05 | 22.17 |
May | 92100498.13 | 1057.69 | 09-MAY-08:00 | 14.00 |
June | 93916463.24 | 1254.89 | 25-JUN-07:10 | 18.17 |
July | 96378944.44 | 1537.18 | 30-JUL-07:07 | 18.33 |
August | 0.101323E+09 | 1436.79 | 20-AUG-07:07 | 19.03 |
September | 91699391.27 | 1767.09 | 29-SEP-08:05 | 29.67 |
October | 92115365.86 | 2315.11 | 16-OCT-08:06 | 28.50 |
November | 87197888.80 | 1085.30 | 20-NOV-08:25 | 12.00 |
December | 97503529.17 | 1340.93 | 04-DEC-09:05 | 22.50 |
Annual Sum or Average | 0.113429E+10 | |||
Minimum of Months | 87197888.80 | 1057.69 | 10.33 | |
Maximum of Months | 0.103854E+09 | 2315.11 | 29.67 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.100956E+09 | 1060.31 | 15-JAN-09:07 | 22.50 |
February | 90785274.01 | 1057.87 | 12-FEB-09:00 | 15.00 |
March | 0.101633E+09 | 1037.26 | 28-MAR-07:00 | 11.00 |
April | 99045177.02 | 1033.58 | 05-APR-07:00 | 13.00 |
May | 0.100467E+09 | 1036.54 | 09-MAY-07:00 | 13.00 |
June | 98219344.18 | 1028.93 | 12-JUN-07:00 | 14.00 |
July | 0.105609E+09 | 1092.57 | 23-JUL-08:20 | 23.67 |
August | 0.107904E+09 | 1054.90 | 13-AUG-08:06 | 22.33 |
September | 0.105941E+09 | 1783.81 | 29-SEP-19:03 | 28.33 |
October | 0.111846E+09 | 2011.96 | 15-OCT-16:02 | 29.50 |
November | 96715605.98 | 1080.23 | 19-NOV-09:06 | 24.33 |
December | 99933743.79 | 1032.95 | 08-DEC-08:00 | 12.20 |
Annual Sum or Average | 0.121906E+10 | |||
Minimum of Months | 90785274.01 | 1028.93 | 11.00 | |
Maximum of Months | 0.111846E+09 | 2011.96 | 29.50 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.102472E+09 | 1064.00 | 03-JAN-08:10 | 7.67 |
February | 91002472.25 | 1060.20 | 12-FEB-09:00 | 15.00 |
March | 0.102039E+09 | 1038.18 | 28-MAR-07:00 | 11.00 |
April | 99495373.33 | 1034.88 | 05-APR-07:00 | 13.00 |
May | 0.100695E+09 | 1037.86 | 09-MAY-07:00 | 13.00 |
June | 98478451.08 | 1030.18 | 12-JUN-07:00 | 14.00 |
July | 0.105873E+09 | 1085.23 | 23-JUL-08:20 | 23.67 |
August | 0.108192E+09 | 1039.68 | 13-AUG-08:06 | 22.33 |
September | 0.106168E+09 | 1789.08 | 29-SEP-19:03 | 28.33 |
October | 0.111995E+09 | 2014.85 | 15-OCT-16:02 | 29.50 |
November | 96830910.79 | 1062.48 | 12-NOV-09:00 | 14.00 |
December | 0.100087E+09 | 1034.13 | 08-DEC-08:00 | 12.20 |
Annual Sum or Average | 0.122333E+10 | |||
Minimum of Months | 91002472.25 | 1030.18 | 7.67 | |
Maximum of Months | 0.111995E+09 | 2014.85 | 29.50 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.104138E+09 | 1029.87 | 31-JAN-08:00 | 13.00 |
February | 90815728.08 | 1056.48 | 12-FEB-09:00 | 15.00 |
March | 0.102832E+09 | 1036.53 | 28-MAR-07:00 | 11.00 |
April | 99764906.77 | 1031.87 | 05-APR-07:00 | 13.00 |
May | 0.100364E+09 | 1034.26 | 09-MAY-07:00 | 13.00 |
June | 98138485.34 | 1026.56 | 12-JUN-07:00 | 14.00 |
July | 0.105567E+09 | 1051.18 | 23-JUL-08:20 | 23.67 |
August | 0.107755E+09 | 1027.06 | 21-AUG-07:00 | 17.00 |
September | 0.105748E+09 | 1793.70 | 29-SEP-19:03 | 28.33 |
October | 0.111763E+09 | 2018.38 | 15-OCT-16:02 | 29.50 |
November | 96676611.76 | 1580.93 | 19-NOV-09:04 | 24.33 |
December | 99713934.49 | 1032.15 | 08-DEC-08:00 | 12.20 |
Annual Sum or Average | 0.122328E+10 | |||
Minimum of Months | 90815728.08 | 1026.56 | 11.00 | |
Maximum of Months | 0.111763E+09 | 2018.38 | 29.50 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 88051618.92 | 20622.06 | 02-JAN-09:02 | 13.00 |
February | 68240554.91 | 784.94 | 25-FEB-09:00 | 11.00 |
March | 85231880.59 | 26769.12 | 30-MAR-08:62 | 9.50 |
April | 75137035.18 | 773.69 | 06-APR-07:13 | 12.33 |
May | 77129837.30 | 768.18 | 06-MAY-08:00 | 14.00 |
June | 74926445.58 | 767.94 | 28-JUN-07:02 | 16.33 |
July | 77699395.88 | 1660.33 | 23-JUL-09:05 | 25.00 |
August | 79345200.64 | 1109.38 | 13-AUG-09:06 | 24.00 |
September | 76831836.74 | 3812.80 | 29-SEP-08:05 | 29.67 |
October | 86510661.71 | 5279.38 | 15-OCT-09:06 | 32.67 |
November | 72832393.64 | 773.63 | 01-NOV-07:13 | 11.33 |
December | 74077808.12 | 1240.60 | 05-DEC-09:04 | 24.33 |
Annual Sum or Average | 0.936015E+09 | |||
Minimum of Months | 68240554.91 | 767.94 | 9.50 | |
Maximum of Months | 88051618.92 | 26769.12 | 32.67 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.107846E+09 | 4365.77 | 02-JAN-09:02 | 13.00 |
February | 92703827.82 | 1039.98 | 25-FEB-09:00 | 11.00 |
March | 0.106789E+09 | 5120.48 | 30-MAR-08:62 | 9.50 |
April | 0.106071E+09 | 1046.32 | 30-APR-09:07 | 22.50 |
May | 0.104159E+09 | 1023.34 | 09-MAY-08:00 | 14.00 |
June | 0.104162E+09 | 1071.44 | 18-JUN-09:05 | 22.00 |
July | 0.113700E+09 | 1107.61 | 19-JUL-08:05 | 22.67 |
August | 0.116391E+09 | 1432.32 | 13-AUG-09:06 | 24.00 |
September | 0.107180E+09 | 2778.20 | 29-SEP-08:05 | 29.67 |
October | 0.116643E+09 | 2303.05 | 16-OCT-08:06 | 28.50 |
November | 0.100024E+09 | 1729.39 | 19-NOV-10:06 | 26.00 |
December | 0.103237E+09 | 1570.13 | 05-DEC-09:04 | 24.33 |
Annual Sum or Average | 0.127891E+10 | |||
Minimum of Months | 92703827.82 | 1023.34 | 9.50 | |
Maximum of Months | 0.116643E+09 | 5120.48 | 29.67 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.108457E+09 | 5500.19 | 02-JAN-09:02 | 13.00 |
February | 92354915.53 | 1035.92 | 25-FEB-09:00 | 11.00 |
March | 0.107040E+09 | 6347.76 | 30-MAR-08:62 | 9.50 |
April | 0.106014E+09 | 1031.55 | 06-APR-07:13 | 12.33 |
May | 0.103752E+09 | 1018.41 | 09-MAY-08:00 | 14.00 |
June | 0.103799E+09 | 1070.66 | 18-JUN-09:05 | 22.00 |
July | 0.113167E+09 | 1102.58 | 19-JUL-08:05 | 22.67 |
August | 0.115972E+09 | 1422.99 | 13-AUG-09:06 | 24.00 |
September | 0.106668E+09 | 2750.03 | 29-SEP-08:05 | 29.67 |
October | 0.116189E+09 | 2282.24 | 16-OCT-08:06 | 28.50 |
November | 99697551.58 | 1700.08 | 19-NOV-10:06 | 26.00 |
December | 0.102759E+09 | 1559.72 | 05-DEC-09:04 | 24.33 |
Annual Sum or Average | 0.127587E+10 | |||
Minimum of Months | 92354915.53 | 1018.41 | 9.50 | |
Maximum of Months | 0.116189E+09 | 6347.76 | 29.67 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.112478E+09 | 9756.49 | 02-JAN-09:02 | 13.00 |
February | 92587653.75 | 1033.34 | 25-FEB-09:00 | 11.00 |
March | 0.113906E+09 | 12966.75 | 30-MAR-08:62 | 9.50 |
April | 0.107075E+09 | 1028.12 | 06-APR-07:13 | 12.33 |
May | 0.103215E+09 | 1014.42 | 09-MAY-08:00 | 14.00 |
June | 0.103532E+09 | 1044.98 | 18-JUN-09:05 | 22.00 |
July | 0.112272E+09 | 1020.44 | 19-JUL-08:05 | 22.67 |
August | 0.115324E+09 | 1342.88 | 13-AUG-09:06 | 24.00 |
September | 0.106088E+09 | 2650.39 | 29-SEP-08:05 | 29.67 |
October | 0.115824E+09 | 2247.79 | 14-OCT-08:04 | 27.67 |
November | 99637974.37 | 1040.69 | 20-NOV-08:25 | 12.00 |
December | 0.103720E+09 | 1403.71 | 05-DEC-09:04 | 24.33 |
Annual Sum or Average | 0.128566E+10 | |||
Minimum of Months | 92587653.75 | 1014.42 | 9.50 | |
Maximum of Months | 0.115824E+09 | 12966.75 | 29.67 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.140822E+09 | 19944.23 | 02-JAN-09:02 | 13.00 |
February | 0.117034E+09 | 9405.36 | 27-FEB-09:03 | 12.00 |
March | 0.165158E+09 | 24964.80 | 30-MAR-08:62 | 9.50 |
April | 0.114598E+09 | 5229.70 | 01-APR-08:65 | 15.67 |
May | 0.108155E+09 | 1107.22 | 09-MAY-08:00 | 14.00 |
June | 0.109738E+09 | 1200.40 | 18-JUN-09:05 | 22.00 |
July | 0.119023E+09 | 1320.35 | 30-JUL-09:05 | 23.17 |
August | 0.120695E+09 | 1476.79 | 13-AUG-09:06 | 24.00 |
September | 0.113349E+09 | 1842.66 | 30-SEP-08:04 | 25.38 |
October | 0.122783E+09 | 2318.38 | 14-OCT-08:04 | 27.67 |
November | 0.106818E+09 | 2035.73 | 19-NOV-10:04 | 26.00 |
December | 0.116999E+09 | 1978.05 | 13-DEC-09:05 | 11.33 |
Annual Sum or Average | 0.145517E+10 | |||
Minimum of Months | 0.106818E+09 | 1107.22 | 9.50 | |
Maximum of Months | 0.165158E+09 | 24964.80 | 27.67 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.869933E+10 | 5321.43 | 01-JAN-10:09 | 0.223514E+10 | 1348.26 | 01-JAN-10:09 |
February | 0.786449E+10 | 5321.43 | 01-FEB-10:09 | 0.202238E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.870841E+10 | 5321.43 | 01-MAR-10:09 | 0.224215E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.843013E+10 | 5321.43 | 01-APR-09:09 | 0.216638E+10 | 1348.26 | 01-APR-09:09 |
May | 0.869933E+10 | 5321.43 | 01-MAY-09:09 | 0.223514E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.843013E+10 | 5321.43 | 01-JUN-09:09 | 0.217123E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.870841E+10 | 5321.43 | 01-JUL-09:09 | 0.223729E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.869933E+10 | 5321.43 | 01-AUG-09:09 | 0.223756E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.843920E+10 | 5321.43 | 01-SEP-09:09 | 0.217096E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.869933E+10 | 5321.43 | 01-OCT-09:09 | 0.223514E+10 | 1348.26 | 01-OCT-09:09 |
November | 0.840290E+10 | 5321.43 | 01-NOV-09:09 | 0.215964E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.871748E+10 | 5321.43 | 01-DEC-10:09 | 0.224431E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.102498E+12 | 0.263573E+11 | ||||
Minimum of Months | 0.786449E+10 | 5321.43 | 0.202238E+10 | 1348.26 | ||
Maximum of Months | 0.871748E+10 | 5321.43 | 0.224431E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.479410E+10 | 2932.57 | 01-JAN-10:09 | 0.111757E+10 | 674.13 | 01-JAN-10:09 |
February | 0.433403E+10 | 2932.57 | 01-FEB-10:09 | 0.101119E+10 | 674.13 | 01-FEB-10:09 |
March | 0.479910E+10 | 2932.57 | 01-MAR-10:09 | 0.112107E+10 | 674.13 | 01-MAR-10:09 |
April | 0.464574E+10 | 2932.57 | 01-APR-09:09 | 0.108319E+10 | 674.13 | 01-APR-09:09 |
May | 0.479410E+10 | 2932.57 | 01-MAY-09:09 | 0.111757E+10 | 674.13 | 01-MAY-09:09 |
June | 0.464574E+10 | 2932.57 | 01-JUN-09:09 | 0.108562E+10 | 674.13 | 01-JUN-09:09 |
July | 0.479910E+10 | 2932.57 | 01-JUL-09:09 | 0.111865E+10 | 674.13 | 01-JUL-09:09 |
August | 0.479410E+10 | 2932.57 | 01-AUG-09:09 | 0.111878E+10 | 674.13 | 01-AUG-09:09 |
September | 0.465074E+10 | 2932.57 | 01-SEP-09:09 | 0.108548E+10 | 674.13 | 01-SEP-09:09 |
October | 0.479410E+10 | 2932.57 | 01-OCT-09:09 | 0.111757E+10 | 674.13 | 01-OCT-09:09 |
November | 0.463074E+10 | 2932.57 | 01-NOV-09:09 | 0.107982E+10 | 674.13 | 01-NOV-09:09 |
December | 0.480410E+10 | 2932.57 | 01-DEC-10:09 | 0.112215E+10 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.564857E+11 | 0.131787E+11 | ||||
Minimum of Months | 0.433403E+10 | 2932.57 | 0.101119E+10 | 674.13 | ||
Maximum of Months | 0.480410E+10 | 2932.57 | 0.112215E+10 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.338042E+10 | 2599.23 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.306129E+10 | 2599.23 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.345133E+10 | 2599.23 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.327995E+10 | 2599.23 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.341588E+10 | 2599.23 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.333314E+10 | 2599.23 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.336269E+10 | 2599.23 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.345133E+10 | 2599.23 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.327995E+10 | 2599.23 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.338042E+10 | 2599.23 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.327995E+10 | 2599.23 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.336269E+10 | 2599.23 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.400390E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.306129E+10 | 2599.23 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.345133E+10 | 2599.23 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.338042E+10 | 2599.23 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.306129E+10 | 2599.23 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.345133E+10 | 2599.23 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.327995E+10 | 2599.23 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.341588E+10 | 2599.23 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.333314E+10 | 2599.23 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.336269E+10 | 2599.23 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.345133E+10 | 2599.23 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.327995E+10 | 2599.23 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.338042E+10 | 2599.23 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.327995E+10 | 2599.23 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.336269E+10 | 2599.23 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.400390E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.306129E+10 | 2599.23 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.345133E+10 | 2599.23 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.338042E+10 | 2599.23 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.306129E+10 | 2599.23 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.345133E+10 | 2599.23 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.327995E+10 | 2599.23 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.341588E+10 | 2599.23 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.333314E+10 | 2599.23 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.336269E+10 | 2599.23 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.345133E+10 | 2599.23 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.327995E+10 | 2599.23 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.338042E+10 | 2599.23 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.327995E+10 | 2599.23 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.336269E+10 | 2599.23 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.400390E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.306129E+10 | 2599.23 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.345133E+10 | 2599.23 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.447638E+10 | 3746.51 | 01-JAN-11:09 | 0.162546E+10 | 1348.26 | 01-JAN-11:09 |
February | 0.405472E+10 | 3746.51 | 01-FEB-10:09 | 0.147229E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.457860E+10 | 3746.51 | 01-MAR-10:09 | 0.166213E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.434435E+10 | 3746.51 | 01-APR-09:09 | 0.157746E+10 | 1348.26 | 01-APR-09:09 |
May | 0.452749E+10 | 3746.51 | 01-MAY-09:09 | 0.164379E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.442101E+10 | 3746.51 | 01-JUN-09:09 | 0.160496E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.445083E+10 | 3746.51 | 01-JUL-09:09 | 0.161629E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.457860E+10 | 3746.51 | 01-AUG-09:09 | 0.166213E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.434435E+10 | 3746.51 | 01-SEP-09:09 | 0.157746E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.447638E+10 | 3746.51 | 01-OCT-10:09 | 0.162546E+10 | 1348.26 | 01-OCT-10:09 |
November | 0.434435E+10 | 3746.51 | 01-NOV-09:09 | 0.157746E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.445083E+10 | 3746.51 | 01-DEC-10:09 | 0.161629E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.530479E+11 | 0.192612E+11 | ||||
Minimum of Months | 0.405472E+10 | 3746.51 | 0.147229E+10 | 1348.26 | ||
Maximum of Months | 0.457860E+10 | 3746.51 | 0.166213E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.230731E+10 | 1931.10 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.208997E+10 | 1931.10 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.236000E+10 | 1931.10 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.223926E+10 | 1931.10 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.233366E+10 | 1931.10 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.227877E+10 | 1931.10 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.229414E+10 | 1931.10 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.236000E+10 | 1931.10 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.223926E+10 | 1931.10 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.230731E+10 | 1931.10 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.223926E+10 | 1931.10 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.229414E+10 | 1931.10 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.273431E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.208997E+10 | 1931.10 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.236000E+10 | 1931.10 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.230731E+10 | 1931.10 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.208997E+10 | 1931.10 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.236000E+10 | 1931.10 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.223926E+10 | 1931.10 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.233366E+10 | 1931.10 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.227877E+10 | 1931.10 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.229414E+10 | 1931.10 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.236000E+10 | 1931.10 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.223926E+10 | 1931.10 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.230731E+10 | 1931.10 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.223926E+10 | 1931.10 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.229414E+10 | 1931.10 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.273431E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.208997E+10 | 1931.10 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.236000E+10 | 1931.10 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.230731E+10 | 1931.10 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.208997E+10 | 1931.10 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.236000E+10 | 1931.10 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.223926E+10 | 1931.10 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.233366E+10 | 1931.10 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.227877E+10 | 1931.10 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.229414E+10 | 1931.10 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.236000E+10 | 1931.10 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.223926E+10 | 1931.10 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.230731E+10 | 1931.10 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.223926E+10 | 1931.10 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.229414E+10 | 1931.10 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.273431E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.208997E+10 | 1931.10 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.236000E+10 | 1931.10 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.230731E+10 | 1931.10 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.208997E+10 | 1931.10 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.236000E+10 | 1931.10 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.223926E+10 | 1931.10 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.233366E+10 | 1931.10 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.227877E+10 | 1931.10 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.229414E+10 | 1931.10 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.236000E+10 | 1931.10 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.223926E+10 | 1931.10 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.230731E+10 | 1931.10 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.223926E+10 | 1931.10 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.229414E+10 | 1931.10 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.273431E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.208997E+10 | 1931.10 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.236000E+10 | 1931.10 | 0.831065E+09 | 674.13 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.869933E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12252689.35 | 0.186907E+10 |
February | 0.305697E+10 | 0.786449E+10 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1161972.39 | 0.191532E+10 |
March | 0.335708E+10 | 0.870841E+10 | 0.224215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 239551.68 | 0.205827E+10 |
April | 0.327081E+10 | 0.843013E+10 | 0.216638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11311541.57 | 0.130923E+10 |
May | 0.336680E+10 | 0.869933E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 146130.07 | 0.138627E+10 |
June | 0.325380E+10 | 0.843013E+10 | 0.217123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1329049.41 | 0.827591E+09 |
July | 0.339353E+10 | 0.870841E+10 | 0.223729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73299526.48 | 0.421833E+09 |
August | 0.334857E+10 | 0.869933E+10 | 0.223756E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83858008.97 | 0.422233E+09 |
September | 0.327932E+10 | 0.843920E+10 | 0.217096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128474E+09 | 0.766760E+09 |
October | 0.338624E+10 | 0.869933E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249071E+09 | 0.794557E+09 |
November | 0.327446E+10 | 0.840290E+10 | 0.215964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11953577.23 | 0.175026E+10 |
December | 0.340325E+10 | 0.871748E+10 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7580263.65 | 0.183061E+10 |
Annual Sum or Average | 0.397770E+11 | 0.102498E+12 | 0.263573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.580678E+09 | 0.153520E+11 |
Minimum of Months | 0.305697E+10 | 0.786449E+10 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 146130.07 | 0.421833E+09 |
Maximum of Months | 0.340325E+10 | 0.871748E+10 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249071E+09 | 0.205827E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.479410E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6701762.69 | 0.982108E+09 |
February | 0.152844E+10 | 0.433403E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 624619.33 | 0.101311E+10 |
March | 0.167849E+10 | 0.479910E+10 | 0.112107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 129950.11 | 0.110288E+10 |
April | 0.163536E+10 | 0.464574E+10 | 0.108319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6156467.73 | 0.668160E+09 |
May | 0.168335E+10 | 0.479410E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79966.17 | 0.694768E+09 |
June | 0.162685E+10 | 0.464574E+10 | 0.108562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 716802.10 | 0.421850E+09 |
July | 0.169671E+10 | 0.479910E+10 | 0.111865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39828612.29 | 0.209345E+09 |
August | 0.167424E+10 | 0.479410E+10 | 0.111878E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45648953.13 | 0.195848E+09 |
September | 0.163961E+10 | 0.465074E+10 | 0.108548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70104075.09 | 0.391451E+09 |
October | 0.169307E+10 | 0.479410E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134949E+09 | 0.373667E+09 |
November | 0.163718E+10 | 0.463074E+10 | 0.107982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6514881.75 | 0.887586E+09 |
December | 0.170157E+10 | 0.480410E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4116805.37 | 0.953751E+09 |
Annual Sum or Average | 0.198880E+11 | 0.564857E+11 | 0.131787E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315572E+09 | 0.789453E+10 |
Minimum of Months | 0.152844E+10 | 0.433403E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79966.17 | 0.195848E+09 |
Maximum of Months | 0.170157E+10 | 0.480410E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134949E+09 | 0.110288E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.338042E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6701762.56 | 0.986141E+09 |
February | 0.914877E+09 | 0.306129E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 624614.70 | 0.102462E+10 |
March | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 129950.11 | 0.111112E+10 |
April | 0.984131E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6156437.79 | 0.682903E+09 |
May | 0.102058E+10 | 0.341588E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 79966.07 | 0.712177E+09 |
June | 0.998711E+09 | 0.333314E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 716717.67 | 0.438387E+09 |
July | 0.100600E+10 | 0.336269E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39764155.64 | 0.229024E+09 |
August | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45647259.23 | 0.213854E+09 |
September | 0.984131E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 70222531.30 | 0.403777E+09 |
October | 0.100722E+10 | 0.338042E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133222E+09 | 0.389157E+09 |
November | 0.973196E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6512028.98 | 0.902088E+09 |
December | 0.100600E+10 | 0.336269E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4119695.14 | 0.964645E+09 |
Annual Sum or Average | 0.119700E+11 | 0.400390E+11 | 0.104672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313897E+09 | 0.805789E+10 |
Minimum of Months | 0.914877E+09 | 0.306129E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 79966.07 | 0.213854E+09 |
Maximum of Months | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133222E+09 | 0.111112E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.338042E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6701761.85 | 0.979157E+09 |
February | 0.914877E+09 | 0.306129E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 624614.70 | 0.101790E+10 |
March | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 129950.11 | 0.110123E+10 |
April | 0.984131E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6156421.36 | 0.681294E+09 |
May | 0.102058E+10 | 0.341588E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 79965.90 | 0.710964E+09 |
June | 0.998711E+09 | 0.333314E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 716685.71 | 0.437886E+09 |
July | 0.100600E+10 | 0.336269E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39763799.12 | 0.228754E+09 |
August | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45646841.53 | 0.213554E+09 |
September | 0.984131E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 70222496.24 | 0.403372E+09 |
October | 0.100722E+10 | 0.338042E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133222E+09 | 0.388651E+09 |
November | 0.973196E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6512068.66 | 0.900272E+09 |
December | 0.100600E+10 | 0.336269E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4119695.14 | 0.960377E+09 |
Annual Sum or Average | 0.119700E+11 | 0.400390E+11 | 0.104672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313897E+09 | 0.802341E+10 |
Minimum of Months | 0.914877E+09 | 0.306129E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 79965.90 | 0.213554E+09 |
Maximum of Months | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133222E+09 | 0.110123E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.338042E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6701761.33 | 0.969998E+09 |
February | 0.914877E+09 | 0.306129E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 624614.70 | 0.100494E+10 |
March | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 129950.11 | 0.108363E+10 |
April | 0.984131E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6156399.67 | 0.678524E+09 |
May | 0.102058E+10 | 0.341588E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 79965.60 | 0.708783E+09 |
June | 0.998711E+09 | 0.333314E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 716641.84 | 0.436928E+09 |
July | 0.100600E+10 | 0.336269E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39763233.65 | 0.227858E+09 |
August | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45646159.48 | 0.212518E+09 |
September | 0.984131E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 70222754.93 | 0.402455E+09 |
October | 0.100722E+10 | 0.338042E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133248E+09 | 0.387244E+09 |
November | 0.973196E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6512378.32 | 0.897108E+09 |
December | 0.100600E+10 | 0.336269E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4119695.14 | 0.952247E+09 |
Annual Sum or Average | 0.119700E+11 | 0.400390E+11 | 0.104672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313921E+09 | 0.796222E+10 |
Minimum of Months | 0.914877E+09 | 0.306129E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 79965.60 | 0.212518E+09 |
Maximum of Months | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133248E+09 | 0.108363E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.447638E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12048702.19 | 0.171446E+10 |
February | 0.313522E+10 | 0.405472E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1125023.37 | 0.176191E+10 |
March | 0.355148E+10 | 0.457860E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 233793.05 | 0.188463E+10 |
April | 0.338259E+10 | 0.434435E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11070305.86 | 0.122369E+10 |
May | 0.349753E+10 | 0.452749E+10 | 0.164379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 143496.59 | 0.128580E+10 |
June | 0.343071E+10 | 0.442101E+10 | 0.160496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1290131.87 | 0.796295E+09 |
July | 0.344942E+10 | 0.445083E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71453928.78 | 0.418475E+09 |
August | 0.355148E+10 | 0.457860E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82077927.79 | 0.396138E+09 |
September | 0.338259E+10 | 0.434435E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126038E+09 | 0.731700E+09 |
October | 0.344359E+10 | 0.447638E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239611E+09 | 0.717909E+09 |
November | 0.331698E+10 | 0.434435E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11589011.45 | 0.161638E+10 |
December | 0.344942E+10 | 0.445083E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7408179.01 | 0.168739E+10 |
Annual Sum or Average | 0.410346E+11 | 0.530479E+11 | 0.192612E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.564090E+09 | 0.142348E+11 |
Minimum of Months | 0.313522E+10 | 0.405472E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 143496.59 | 0.396138E+09 |
Maximum of Months | 0.355148E+10 | 0.457860E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239611E+09 | 0.188463E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6685448.04 | 0.968631E+09 |
February | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 624614.70 | 0.100105E+10 |
March | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 129950.12 | 0.107540E+10 |
April | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6156383.35 | 0.680168E+09 |
May | 0.174872E+10 | 0.233366E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 79948.41 | 0.711773E+09 |
June | 0.171530E+10 | 0.227877E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 716597.13 | 0.439468E+09 |
July | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39726027.68 | 0.230470E+09 |
August | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45644478.47 | 0.215585E+09 |
September | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 70091453.10 | 0.404540E+09 |
October | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132974E+09 | 0.391679E+09 |
November | 0.165844E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6417940.32 | 0.900215E+09 |
December | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4119446.33 | 0.951930E+09 |
Annual Sum or Average | 0.205167E+11 | 0.273431E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313367E+09 | 0.797091E+10 |
Minimum of Months | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 79948.41 | 0.215585E+09 |
Maximum of Months | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132974E+09 | 0.107540E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6687164.94 | 0.966855E+09 |
February | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 624614.69 | 0.998485E+09 |
March | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 129950.12 | 0.107256E+10 |
April | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6156363.53 | 0.679453E+09 |
May | 0.174872E+10 | 0.233366E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 79947.99 | 0.711085E+09 |
June | 0.171530E+10 | 0.227877E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 716584.36 | 0.439058E+09 |
July | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39725981.53 | 0.230101E+09 |
August | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45644472.99 | 0.215179E+09 |
September | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 70094494.94 | 0.404146E+09 |
October | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132998E+09 | 0.391137E+09 |
November | 0.165844E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6421148.19 | 0.899345E+09 |
December | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4119866.21 | 0.950225E+09 |
Annual Sum or Average | 0.205167E+11 | 0.273431E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313398E+09 | 0.795763E+10 |
Minimum of Months | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 79947.99 | 0.215179E+09 |
Maximum of Months | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132998E+09 | 0.107256E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6699757.28 | 0.955037E+09 |
February | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 624614.71 | 0.979502E+09 |
March | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 129950.14 | 0.105198E+10 |
April | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6156282.87 | 0.674732E+09 |
May | 0.174872E+10 | 0.233366E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 79950.69 | 0.706657E+09 |
June | 0.171530E+10 | 0.227877E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 716553.40 | 0.437100E+09 |
July | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39725889.69 | 0.228658E+09 |
August | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45643512.84 | 0.213530E+09 |
September | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 70106898.68 | 0.402431E+09 |
October | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133076E+09 | 0.388800E+09 |
November | 0.165844E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6445931.61 | 0.893054E+09 |
December | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4118763.64 | 0.937200E+09 |
Annual Sum or Average | 0.205167E+11 | 0.273431E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313524E+09 | 0.786868E+10 |
Minimum of Months | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 79950.69 | 0.213530E+09 |
Maximum of Months | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133076E+09 | 0.105198E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6973903.93 | 0.111303E+10 |
February | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 661592.84 | 0.114343E+10 |
March | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 135708.93 | 0.123743E+10 |
April | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6397273.89 | 0.795972E+09 |
May | 0.174872E+10 | 0.233366E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 82530.02 | 0.851813E+09 |
June | 0.171530E+10 | 0.227877E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 755650.00 | 0.517680E+09 |
July | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41388277.90 | 0.287603E+09 |
August | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47415627.00 | 0.293194E+09 |
September | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 72502751.84 | 0.469441E+09 |
October | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139306E+09 | 0.509939E+09 |
November | 0.165844E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6721584.38 | 0.105437E+10 |
December | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4288180.98 | 0.110019E+10 |
Annual Sum or Average | 0.205167E+11 | 0.273431E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326629E+09 | 0.937410E+10 |
Minimum of Months | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 82530.02 | 0.287603E+09 |
Maximum of Months | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139306E+09 | 0.123743E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 5321.43 | 01-JAN-10:09 | 1348.26 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 613.87 | 13-JAN-14:00 | 4097.10 | 06-JAN-18:00 |
February | 4050.04 | 03-FEB-13:09 | 5321.43 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 521.51 | 01-FEB-12:10 | 3529.19 | 25-FEB-13:00 |
March | 4050.04 | 03-MAR-13:09 | 5321.43 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.72 | 11-MAR-14:00 | 4088.43 | 29-MAR-11:10 |
April | 4050.04 | 01-APR-12:09 | 5321.43 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 907.67 | 26-APR-13:00 | 3525.28 | 17-APR-17:00 |
May | 4050.04 | 05-MAY-12:09 | 5321.43 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.46 | 03-MAY-13:00 | 3127.31 | 12-MAY-17:00 |
June | 4050.04 | 02-JUN-12:09 | 5321.43 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 277.58 | 29-JUN-11:10 | 2109.65 | 06-JUN-17:00 |
July | 4050.04 | 01-JUL-12:09 | 5321.43 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1207.02 | 31-JUL-13:00 | 1479.80 | 09-JUL-17:00 |
August | 4050.04 | 04-AUG-12:09 | 5321.43 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1197.34 | 17-AUG-14:00 | 1782.61 | 22-AUG-17:00 |
September | 4050.04 | 01-SEP-12:09 | 5321.43 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3428.48 | 29-SEP-13:00 | 2059.25 | 24-SEP-17:00 |
October | 4050.04 | 01-OCT-12:09 | 5321.43 | 01-OCT-09:09 | 1348.26 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3727.10 | 16-OCT-11:10 | 2131.49 | 23-OCT-15:00 |
November | 4050.04 | 03-NOV-12:09 | 5321.43 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 908.10 | 19-NOV-13:00 | 3331.54 | 26-NOV-18:00 |
December | 4050.04 | 01-DEC-13:09 | 5321.43 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 615.78 | 19-DEC-13:00 | 3646.29 | 24-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 5321.43 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 30.46 | 1479.80 | |||||
Maximum of Months | 4050.04 | 5321.43 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 3727.10 | 4097.10 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 2932.57 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 337.11 | 13-JAN-14:00 | 2396.21 | 06-JAN-18:00 |
February | 2024.96 | 03-FEB-13:09 | 2932.57 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 284.65 | 01-FEB-12:10 | 2115.56 | 25-FEB-13:00 |
March | 2024.96 | 03-MAR-13:09 | 2932.57 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.71 | 11-MAR-14:00 | 2267.39 | 29-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 2932.57 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 496.07 | 26-APR-13:00 | 2001.87 | 17-APR-17:00 |
May | 2024.96 | 05-MAY-12:09 | 2932.57 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 03-MAY-13:00 | 1816.45 | 12-MAY-17:00 |
June | 2024.96 | 02-JUN-12:09 | 2932.57 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 151.30 | 29-JUN-11:10 | 1147.49 | 06-JUN-17:00 |
July | 2024.96 | 01-JUL-12:09 | 2932.57 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 656.64 | 31-JUL-13:00 | 806.73 | 09-JUL-17:00 |
August | 2024.96 | 04-AUG-12:09 | 2932.57 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 654.51 | 17-AUG-14:00 | 974.14 | 22-AUG-17:00 |
September | 2024.96 | 01-SEP-12:09 | 2932.57 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1873.81 | 29-SEP-13:00 | 1133.64 | 24-SEP-17:00 |
October | 2024.96 | 01-OCT-12:09 | 2932.57 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2021.62 | 16-OCT-11:10 | 1153.39 | 23-OCT-15:00 |
November | 2024.96 | 03-NOV-12:09 | 2932.57 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 496.28 | 19-NOV-13:00 | 1943.20 | 26-NOV-18:00 |
December | 2024.96 | 01-DEC-13:09 | 2932.57 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 337.34 | 19-DEC-13:00 | 2171.04 | 24-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2932.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 806.73 | |||||
Maximum of Months | 2024.96 | 2932.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2021.62 | 2396.21 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2599.23 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 337.11 | 13-JAN-14:00 | 2370.01 | 06-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2599.23 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 284.65 | 01-FEB-12:10 | 2133.47 | 25-FEB-13:00 |
March | 2024.96 | 04-MAR-13:09 | 2599.23 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.71 | 11-MAR-14:00 | 2260.96 | 29-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 2599.23 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 496.06 | 26-APR-13:00 | 1973.60 | 17-APR-17:00 |
May | 2024.96 | 06-MAY-12:09 | 2599.23 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 03-MAY-13:00 | 1801.21 | 12-MAY-17:00 |
June | 2024.96 | 03-JUN-12:09 | 2599.23 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 151.30 | 29-JUN-11:10 | 1157.47 | 11-JUN-17:00 |
July | 2024.96 | 01-JUL-12:09 | 2599.23 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 656.64 | 31-JUL-13:00 | 1002.54 | 09-JUL-17:00 |
August | 2024.96 | 05-AUG-12:09 | 2599.23 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 654.52 | 17-AUG-14:00 | 974.14 | 22-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 2599.23 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1873.81 | 29-SEP-13:00 | 1219.40 | 24-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2599.23 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2021.62 | 16-OCT-11:10 | 1240.47 | 22-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2599.23 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 496.28 | 19-NOV-13:00 | 1821.81 | 25-NOV-16:00 |
December | 2024.96 | 02-DEC-13:09 | 2599.23 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 337.34 | 19-DEC-13:00 | 2045.31 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2599.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 974.14 | |||||
Maximum of Months | 2024.96 | 2599.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2021.62 | 2370.01 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2599.23 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 337.11 | 13-JAN-14:00 | 2354.09 | 06-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2599.23 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 284.65 | 01-FEB-12:10 | 2119.18 | 25-FEB-13:00 |
March | 2024.96 | 04-MAR-13:09 | 2599.23 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.71 | 11-MAR-14:00 | 2260.94 | 29-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 2599.23 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 496.06 | 26-APR-13:00 | 1963.04 | 17-APR-17:00 |
May | 2024.96 | 06-MAY-12:09 | 2599.23 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 03-MAY-13:00 | 1795.49 | 12-MAY-17:00 |
June | 2024.96 | 03-JUN-12:09 | 2599.23 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 151.30 | 29-JUN-11:10 | 1150.08 | 11-JUN-17:00 |
July | 2024.96 | 01-JUL-12:09 | 2599.23 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 656.64 | 31-JUL-13:00 | 998.39 | 09-JUL-17:00 |
August | 2024.96 | 05-AUG-12:09 | 2599.23 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 654.53 | 17-AUG-14:00 | 974.14 | 22-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 2599.23 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1873.81 | 29-SEP-13:00 | 1214.24 | 24-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2599.23 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2021.62 | 16-OCT-11:10 | 1235.46 | 22-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2599.23 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 496.28 | 19-NOV-13:00 | 1816.75 | 25-NOV-16:00 |
December | 2024.96 | 02-DEC-13:09 | 2599.23 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 337.34 | 19-DEC-13:00 | 2037.53 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2599.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 974.14 | |||||
Maximum of Months | 2024.96 | 2599.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2021.62 | 2354.09 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2599.23 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 337.11 | 13-JAN-14:00 | 2324.56 | 06-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2599.23 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 284.65 | 01-FEB-12:10 | 2080.07 | 25-FEB-13:00 |
March | 2024.96 | 04-MAR-13:09 | 2599.23 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.71 | 11-MAR-14:00 | 2260.94 | 29-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 2599.23 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 496.06 | 26-APR-13:00 | 1944.40 | 17-APR-17:00 |
May | 2024.96 | 06-MAY-12:09 | 2599.23 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 03-MAY-13:00 | 1779.00 | 12-MAY-17:00 |
June | 2024.96 | 03-JUN-12:09 | 2599.23 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 151.30 | 29-JUN-11:10 | 1147.49 | 06-JUN-17:00 |
July | 2024.96 | 01-JUL-12:09 | 2599.23 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 656.65 | 31-JUL-13:00 | 987.72 | 09-JUL-17:00 |
August | 2024.96 | 05-AUG-12:09 | 2599.23 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 654.53 | 17-AUG-14:00 | 974.14 | 22-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 2599.23 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1873.81 | 29-SEP-13:00 | 1203.51 | 24-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2599.23 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2021.62 | 16-OCT-11:10 | 1224.74 | 22-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2599.23 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 496.28 | 19-NOV-13:00 | 1802.01 | 25-NOV-16:00 |
December | 2024.96 | 02-DEC-13:09 | 2599.23 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 337.34 | 19-DEC-13:00 | 2018.61 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2599.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 974.14 | |||||
Maximum of Months | 2024.96 | 2599.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2021.62 | 2324.56 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 3746.51 | 01-JAN-11:09 | 1348.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 605.58 | 13-JAN-14:00 | 3942.93 | 06-JAN-18:00 |
February | 5400.05 | 04-FEB-15:09 | 3746.51 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 511.72 | 01-FEB-12:10 | 3516.18 | 25-FEB-13:00 |
March | 5400.05 | 04-MAR-15:09 | 3746.51 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.05 | 11-MAR-14:00 | 4058.02 | 29-MAR-11:10 |
April | 5400.05 | 01-APR-14:09 | 3746.51 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 891.61 | 26-APR-13:00 | 3323.20 | 17-APR-17:00 |
May | 5400.05 | 06-MAY-14:09 | 3746.51 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 29.91 | 03-MAY-13:00 | 3018.62 | 12-MAY-17:00 |
June | 5400.05 | 03-JUN-14:09 | 3746.51 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 272.00 | 29-JUN-11:10 | 2063.71 | 06-JUN-17:00 |
July | 5400.05 | 01-JUL-14:09 | 3746.51 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1180.99 | 31-JUL-13:00 | 1613.93 | 09-JUL-17:00 |
August | 5400.05 | 05-AUG-14:09 | 3746.51 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1176.35 | 17-AUG-14:00 | 1751.03 | 22-AUG-17:00 |
September | 5400.05 | 02-SEP-14:09 | 3746.51 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3368.03 | 29-SEP-13:00 | 2030.87 | 27-SEP-17:00 |
October | 5400.05 | 07-OCT-14:09 | 3746.51 | 01-OCT-10:09 | 1348.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3636.97 | 16-OCT-11:10 | 2075.64 | 23-OCT-15:00 |
November | 5400.05 | 04-NOV-14:09 | 3746.51 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 892.04 | 19-NOV-13:00 | 3128.85 | 25-NOV-16:00 |
December | 5400.05 | 02-DEC-15:09 | 3746.51 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 606.18 | 19-DEC-13:00 | 3440.60 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 3746.51 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 29.91 | 1613.93 | |||||
Maximum of Months | 5400.05 | 3746.51 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 3636.97 | 4058.02 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1931.10 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 337.11 | 13-JAN-14:00 | 2287.92 | 06-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1931.10 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 284.65 | 01-FEB-12:10 | 2049.31 | 25-FEB-13:00 |
March | 2699.95 | 04-MAR-15:09 | 1931.10 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.71 | 11-MAR-14:00 | 2260.94 | 29-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1931.10 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 496.06 | 26-APR-13:00 | 1920.73 | 17-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 1931.10 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.66 | 03-MAY-12:30 | 1757.66 | 12-MAY-17:00 |
June | 2699.95 | 03-JUN-14:09 | 1931.10 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 151.29 | 29-JUN-11:10 | 1147.48 | 06-JUN-17:00 |
July | 2699.95 | 01-JUL-14:09 | 1931.10 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 656.64 | 31-JUL-13:00 | 963.22 | 09-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1931.10 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 654.53 | 17-AUG-14:00 | 974.13 | 22-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1931.10 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1873.81 | 29-SEP-13:00 | 1176.49 | 24-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1931.10 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2021.62 | 16-OCT-11:10 | 1198.30 | 22-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1931.10 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 496.28 | 19-NOV-13:00 | 1814.14 | 25-NOV-16:00 |
December | 2699.95 | 02-DEC-15:09 | 1931.10 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 337.34 | 19-DEC-13:00 | 1994.79 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 16.66 | 963.22 | |||||
Maximum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2021.62 | 2287.92 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1931.10 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 337.11 | 13-JAN-14:00 | 2284.41 | 06-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1931.10 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 284.65 | 01-FEB-12:10 | 2044.17 | 25-FEB-13:00 |
March | 2699.95 | 04-MAR-15:09 | 1931.10 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.71 | 11-MAR-14:00 | 2260.94 | 29-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1931.10 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 496.06 | 26-APR-13:00 | 1915.88 | 17-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 1931.10 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.66 | 03-MAY-12:30 | 1754.84 | 12-MAY-17:00 |
June | 2699.95 | 03-JUN-14:09 | 1931.10 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 151.29 | 29-JUN-11:10 | 1147.49 | 06-JUN-17:00 |
July | 2699.95 | 01-JUL-14:09 | 1931.10 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 656.64 | 31-JUL-13:00 | 959.63 | 09-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1931.10 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 654.53 | 17-AUG-14:00 | 974.13 | 22-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1931.10 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1873.81 | 29-SEP-13:00 | 1172.73 | 24-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1931.10 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2021.62 | 16-OCT-11:10 | 1194.25 | 22-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1931.10 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 496.28 | 19-NOV-13:00 | 1810.64 | 25-NOV-16:00 |
December | 2699.95 | 02-DEC-15:09 | 1931.10 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 337.34 | 19-DEC-13:00 | 1990.66 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 16.66 | 959.63 | |||||
Maximum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2021.62 | 2284.41 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1931.10 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 337.11 | 13-JAN-14:00 | 2258.44 | 06-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1931.10 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 284.65 | 01-FEB-12:10 | 1995.37 | 25-FEB-13:00 |
March | 2699.95 | 04-MAR-15:09 | 1931.10 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.71 | 11-MAR-14:00 | 2260.94 | 29-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1931.10 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 496.06 | 26-APR-13:00 | 1890.52 | 17-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 1931.10 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.66 | 03-MAY-12:30 | 1731.30 | 12-MAY-17:00 |
June | 2699.95 | 03-JUN-14:09 | 1931.10 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 151.29 | 29-JUN-11:10 | 1147.49 | 06-JUN-17:00 |
July | 2699.95 | 01-JUL-14:09 | 1931.10 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 656.64 | 31-JUL-13:00 | 948.42 | 09-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1931.10 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 654.52 | 17-AUG-14:00 | 974.13 | 22-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1931.10 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1873.81 | 29-SEP-13:00 | 1160.64 | 24-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1931.10 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2021.62 | 16-OCT-11:10 | 1181.02 | 22-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1931.10 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 496.28 | 19-NOV-13:00 | 1788.33 | 25-NOV-16:00 |
December | 2699.95 | 02-DEC-15:09 | 1931.10 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 337.34 | 19-DEC-13:00 | 1965.42 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 16.66 | 948.42 | |||||
Maximum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2021.62 | 2260.94 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1931.10 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 345.40 | 13-JAN-14:00 | 2246.01 | 06-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1931.10 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 294.44 | 01-FEB-12:10 | 2005.73 | 25-FEB-13:00 |
March | 2699.95 | 04-MAR-15:09 | 1931.10 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.38 | 11-MAR-14:00 | 2291.35 | 29-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1931.10 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 512.10 | 26-APR-13:00 | 1960.93 | 17-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 1931.10 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.20 | 03-MAY-12:30 | 1757.39 | 12-MAY-17:00 |
June | 2699.95 | 03-JUN-14:09 | 1931.10 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 156.86 | 29-JUN-11:10 | 1193.42 | 06-JUN-17:00 |
July | 2699.95 | 01-JUL-14:09 | 1931.10 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 682.92 | 31-JUL-13:00 | 985.69 | 09-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1931.10 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 675.69 | 17-AUG-14:00 | 1005.64 | 22-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1931.10 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1934.42 | 29-SEP-13:00 | 1173.00 | 24-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1931.10 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2111.76 | 16-OCT-11:10 | 1209.18 | 23-OCT-15:00 |
November | 2699.95 | 04-NOV-14:09 | 1931.10 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 512.34 | 19-NOV-13:00 | 1801.85 | 25-NOV-16:00 |
December | 2699.95 | 02-DEC-15:09 | 1931.10 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 346.95 | 19-DEC-13:00 | 1921.52 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 17.20 | 985.69 | |||||
Maximum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2111.76 | 2291.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11105.80 | 21-JAN-09:02 | 1350.01 | 11202.96 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 432.13 |
February | 7682.60 | 03-FEB-14:00 | 4050.04 | 5321.43 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.64 |
March | 7758.01 | 23-MAR-17:10 | 3375.03 | 5321.43 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 273.15 |
April | 21922.53 | 27-APR-08:62 | 1687.52 | 14003.70 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 283.26 |
May | 24673.61 | 03-MAY-08:62 | 1687.52 | 14003.70 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.59 |
June | 30316.50 | 21-JUN-08:62 | 2025.02 | 16804.44 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.38 |
July | 30988.53 | 10-JUL-08:62 | 1687.52 | 14003.70 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.67 |
August | 28932.75 | 30-AUG-08:62 | 2025.02 | 16804.44 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.04 |
September | 30418.19 | 28-SEP-08:62 | 2025.02 | 16804.44 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.42 |
October | 29677.91 | 18-OCT-08:62 | 1687.52 | 14003.70 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.61 |
November | 10807.20 | 28-NOV-09:02 | 1350.01 | 11202.96 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.13 |
December | 23261.26 | 05-DEC-09:02 | 1687.52 | 14003.70 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 21.12 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7682.60 | 1350.01 | 5321.43 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30988.53 | 4050.04 | 16804.44 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 21.12 | 432.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18997.96 | 15-JAN-18:01 | 20249.61 | 29325.68 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.55 |
February | 17275.09 | 05-FEB-18:10 | 4049.92 | 5865.14 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.33 |
March | 8221.85 | 24-MAR-08:63 | 506.24 | 4630.37 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.11 |
April | 16253.64 | 28-APR-08:62 | 674.99 | 6173.83 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.09 |
May | 18768.81 | 24-MAY-08:62 | 674.99 | 6173.83 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.63 |
June | 17471.73 | 23-JUN-08:62 | 843.73 | 7717.28 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.99 |
July | 16991.35 | 08-JUL-08:62 | 843.73 | 7717.28 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.97 |
August | 17320.46 | 22-AUG-08:62 | 843.73 | 7717.28 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.89 |
September | 18063.05 | 02-SEP-08:62 | 674.99 | 6173.83 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.87 |
October | 19722.31 | 16-OCT-20:52 | 9112.33 | 26393.11 | 6067.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.01 |
November | 18154.44 | 28-NOV-09:02 | 674.99 | 6173.83 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.06 |
December | 18576.49 | 19-DEC-09:02 | 674.99 | 6173.83 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8221.85 | 506.24 | 4630.37 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.01 | |
Maximum of Months | 19722.31 | 20249.61 | 29325.68 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16108.29 | 21-JAN-08:62 | 674.99 | 5472.06 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.27 |
February | 7254.05 | 02-FEB-08:63 | 506.24 | 4104.04 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 276.29 |
March | 7748.04 | 24-MAR-07:03 | 506.24 | 4104.04 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 252.19 |
April | 16071.77 | 27-APR-07:03 | 674.99 | 5472.06 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.79 |
May | 16760.95 | 04-MAY-07:03 | 674.99 | 5472.06 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.91 |
June | 17534.08 | 23-JUN-07:02 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.78 |
July | 17078.43 | 10-JUL-07:02 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.27 |
August | 17627.62 | 22-AUG-07:02 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.07 |
September | 18225.86 | 02-SEP-07:03 | 674.99 | 5472.06 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.56 |
October | 20076.94 | 18-OCT-07:02 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.09 |
November | 15754.75 | 19-NOV-09:02 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 |
December | 9810.81 | 19-DEC-08:63 | 506.24 | 4104.04 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7254.05 | 506.24 | 4104.04 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | |
Maximum of Months | 20076.94 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 276.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15317.09 | 21-JAN-08:62 | 674.99 | 5472.06 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.16 |
February | 6292.08 | 02-FEB-08:63 | 506.24 | 4104.04 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 276.05 |
March | 7053.91 | 24-MAR-07:03 | 506.24 | 4104.04 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 252.03 |
April | 16055.72 | 27-APR-07:03 | 674.99 | 5472.06 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.50 |
May | 16758.45 | 04-MAY-07:03 | 674.99 | 5472.06 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.79 |
June | 17540.26 | 23-JUN-07:02 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.82 |
July | 17068.94 | 10-JUL-07:02 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.98 |
August | 17638.38 | 22-AUG-07:02 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.22 |
September | 17699.59 | 02-SEP-07:03 | 674.99 | 5472.06 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.49 |
October | 20130.60 | 18-OCT-07:02 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.03 |
November | 15711.53 | 19-NOV-09:02 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 |
December | 8766.64 | 07-DEC-08:63 | 506.24 | 4104.04 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6292.08 | 506.24 | 4104.04 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | |
Maximum of Months | 20130.60 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 276.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13522.46 | 21-JAN-08:62 | 674.99 | 5472.06 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.89 |
February | 4263.54 | 02-FEB-08:63 | 506.24 | 4104.04 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 275.55 |
March | 5410.91 | 24-MAR-07:03 | 506.24 | 4104.04 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.63 |
April | 14683.11 | 27-APR-07:03 | 674.99 | 5472.06 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.41 |
May | 15528.61 | 05-MAY-07:03 | 674.99 | 5472.06 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.36 |
June | 17345.80 | 23-JUN-07:02 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.18 |
July | 16866.79 | 10-JUL-07:02 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.08 |
August | 17449.01 | 22-AUG-07:02 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.74 |
September | 17051.51 | 30-SEP-07:01 | 1181.23 | 9576.10 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.10 |
October | 19937.96 | 18-OCT-07:02 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.62 |
November | 15505.28 | 19-NOV-09:02 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1.36 | 0.00 |
December | 7334.24 | 07-DEC-08:63 | 506.24 | 4104.04 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4263.54 | 506.24 | 4104.04 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19937.96 | 1181.23 | 9576.10 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 1.36 | 275.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11191.25 | 21-JAN-09:02 | 2970.03 | 7887.36 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 405.45 |
February | 7033.91 | 03-FEB-14:00 | 4792.55 | 3746.51 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.38 |
March | 7210.85 | 23-MAR-14:10 | 4657.54 | 3746.51 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 310.59 |
April | 16379.63 | 27-APR-08:62 | 3712.53 | 9859.20 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.89 |
May | 21025.84 | 04-MAY-08:62 | 3712.53 | 9859.20 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.68 |
June | 29076.97 | 21-JUN-08:62 | 4455.04 | 11831.03 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.01 |
July | 28561.29 | 07-JUL-08:62 | 3712.53 | 9859.20 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.22 |
August | 27842.05 | 30-AUG-08:62 | 4455.04 | 11831.03 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.77 |
September | 29259.69 | 30-SEP-08:61 | 5197.55 | 13802.87 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 8.81 | 0.00 |
October | 31853.35 | 18-OCT-08:62 | 3712.53 | 9859.20 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.27 |
November | 27778.61 | 19-NOV-10:02 | 3712.53 | 9859.20 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 68.66 | 0.00 |
December | 15463.17 | 05-DEC-09:02 | 3712.53 | 9859.20 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 19.31 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7033.91 | 2970.03 | 3746.51 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31853.35 | 5197.55 | 13802.87 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 68.66 | 405.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11784.28 | 21-JAN-09:02 | 1484.97 | 4065.46 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.26 |
February | 3716.94 | 03-FEB-14:00 | 2396.20 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.93 |
March | 3807.82 | 23-MAR-14:10 | 2328.71 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.76 |
April | 15139.32 | 27-APR-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.42 |
May | 15727.44 | 04-MAY-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.33 |
June | 16504.57 | 23-JUN-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.16 |
July | 16021.06 | 08-JUL-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.16 |
August | 16360.18 | 22-AUG-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.62 |
September | 16230.83 | 27-SEP-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.85 |
October | 17257.49 | 18-OCT-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.08 |
November | 14621.44 | 19-NOV-10:02 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 28.65 | 0.00 |
December | 14674.32 | 05-DEC-09:02 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3716.94 | 1484.97 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17257.49 | 2396.20 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 28.65 | 225.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11132.64 | 21-JAN-09:02 | 1484.97 | 4065.46 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.17 |
February | 3666.98 | 03-FEB-14:00 | 2396.20 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.93 |
March | 3760.15 | 23-MAR-14:10 | 2328.71 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.76 |
April | 14770.49 | 27-APR-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.77 |
May | 15616.73 | 04-MAY-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.40 |
June | 16388.48 | 23-JUN-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.13 |
July | 15911.38 | 08-JUL-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.27 |
August | 16250.03 | 22-AUG-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.73 |
September | 16118.00 | 27-SEP-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.93 |
October | 17156.05 | 18-OCT-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.19 |
November | 14547.32 | 19-NOV-10:02 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 29.75 | 0.00 |
December | 14309.84 | 05-DEC-09:02 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 9.64 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3666.98 | 1484.97 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17156.05 | 2396.20 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 29.75 | 225.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8040.92 | 21-JAN-09:02 | 1484.97 | 4065.46 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.74 |
February | 3426.78 | 03-FEB-14:00 | 2396.20 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.93 |
March | 3551.13 | 23-MAR-14:10 | 2328.71 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.76 |
April | 11131.51 | 27-APR-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.44 |
May | 13669.18 | 04-MAY-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.26 |
June | 15552.65 | 23-JUN-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.62 |
July | 15677.13 | 08-JUL-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.24 |
August | 15488.49 | 22-AUG-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.07 |
September | 15346.95 | 28-SEP-08:62 | 2227.46 | 6098.20 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.04 |
October | 16955.98 | 18-OCT-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.40 |
November | 14402.21 | 19-NOV-10:02 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 35.55 | 0.00 |
December | 9600.41 | 05-DEC-09:02 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 10.10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3426.78 | 1484.97 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16955.98 | 2396.20 | 6098.20 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 35.55 | 224.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4003.86 | 18-JAN-13:40 | 2396.20 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 193.52 | 0.00 |
February | 3207.17 | 01-FEB-13:10 | 2396.20 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.14 |
March | 3529.68 | 23-MAR-14:10 | 2328.71 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.36 |
April | 5309.74 | 30-APR-09:03 | 1113.73 | 3049.10 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.79 |
May | 7914.17 | 04-MAY-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.57 |
June | 15730.09 | 21-JUN-08:62 | 2227.46 | 6098.20 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.19 |
July | 16132.18 | 04-JUL-09:02 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.80 |
August | 15491.38 | 30-AUG-08:62 | 2227.46 | 6098.20 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.99 |
September | 16483.49 | 30-SEP-08:61 | 2598.70 | 7114.56 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 2.04 | 0.00 |
October | 15285.47 | 17-OCT-08:62 | 2227.46 | 6098.20 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 49.83 | 0.00 |
November | 15329.91 | 19-NOV-10:02 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 46.82 | 0.00 |
December | 4155.16 | 19-DEC-13:10 | 2396.20 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 265.18 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3207.17 | 1113.73 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16483.49 | 2598.70 | 7114.56 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 265.18 | 178.36 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.803543E+11 | 67432.91 | 14-JAN-12:30 | 0.676891E+09 | 29406.25 | 03-JAN-09:09 |
February | 0.710486E+11 | 64214.85 | 03-FEB-13:50 | 0.306491E+09 | 11837.67 | 28-FEB-09:30 |
March | 0.790311E+11 | 64321.83 | 22-MAR-12:50 | 0.139148E+10 | 48795.34 | 30-MAR-08:09 |
April | 0.768308E+11 | 70321.57 | 26-APR-11:50 | 6869475.17 | 7972.55 | 01-APR-08:09 |
May | 0.783242E+11 | 66125.14 | 04-MAY-12:20 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.803803E+11 | 70221.58 | 28-JUN-11:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.891420E+11 | 77906.75 | 19-JUL-14:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.924095E+11 | 76313.24 | 18-AUG-14:20 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.837123E+11 | 89131.59 | 29-SEP-12:09 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.889766E+11 | 89836.85 | 16-OCT-11:30 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.776600E+11 | 69019.12 | 19-NOV-12:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.807950E+11 | 67645.94 | 05-DEC-14:20 | 59309223.59 | 4500.18 | 13-DEC-09:20 |
Annual Sum or Average | 0.978665E+12 | 0.244104E+10 | ||||
Minimum of Months | 0.710486E+11 | 64214.85 | 0.00 | 0.00 | ||
Maximum of Months | 0.924095E+11 | 89836.85 | 0.139148E+10 | 48795.34 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.373403E+11 | 0.101117E+11 | 0.108804E+11 | 0.00 | 0.150277E+11 | 0.00 | 0.00 | 0.164995E+10 | 0.00 | 0.00 | 0.00 | 0.534423E+10 | 0.00 |
February | 0.337970E+11 | 0.856113E+10 | 0.985143E+10 | 0.00 | 0.135941E+11 | 0.00 | 0.00 | 0.405985E+09 | 0.00 | 0.00 | 0.00 | 0.483900E+10 | 0.00 |
March | 0.378801E+11 | 0.864879E+10 | 0.110560E+11 | 0.00 | 0.152587E+11 | 0.00 | 0.00 | 0.802543E+09 | 0.00 | 0.00 | 0.00 | 0.538499E+10 | 0.00 |
April | 0.362171E+11 | 0.755589E+10 | 0.105544E+11 | 0.00 | 0.147199E+11 | 0.00 | 0.00 | 0.264248E+10 | 0.00 | 0.00 | 0.00 | 0.514106E+10 | 0.00 |
May | 0.376032E+11 | 0.713683E+10 | 0.109629E+11 | 0.00 | 0.153101E+11 | 0.00 | 0.00 | 0.202997E+10 | 0.00 | 0.00 | 0.00 | 0.528118E+10 | 0.00 |
June | 0.366114E+11 | 0.659082E+10 | 0.106855E+11 | 0.00 | 0.149827E+11 | 0.00 | 0.00 | 0.641646E+10 | 0.00 | 0.00 | 0.00 | 0.509346E+10 | 0.00 |
July | 0.372230E+11 | 0.691743E+10 | 0.108424E+11 | 0.00 | 0.151403E+11 | 0.00 | 0.00 | 0.138147E+11 | 0.00 | 0.00 | 0.00 | 0.520427E+10 | 0.00 |
August | 0.378660E+11 | 0.748301E+10 | 0.110491E+11 | 0.00 | 0.154762E+11 | 0.00 | 0.00 | 0.152912E+11 | 0.00 | 0.00 | 0.00 | 0.524391E+10 | 0.00 |
September | 0.362312E+11 | 0.802220E+10 | 0.105613E+11 | 0.00 | 0.147793E+11 | 0.00 | 0.00 | 0.905422E+10 | 0.00 | 0.00 | 0.00 | 0.506416E+10 | 0.00 |
October | 0.373403E+11 | 0.913340E+10 | 0.108804E+11 | 0.00 | 0.151995E+11 | 0.00 | 0.00 | 0.111737E+11 | 0.00 | 0.00 | 0.00 | 0.524929E+10 | 0.00 |
November | 0.361749E+11 | 0.957658E+10 | 0.105443E+11 | 0.00 | 0.146728E+11 | 0.00 | 0.00 | 0.156959E+10 | 0.00 | 0.00 | 0.00 | 0.512179E+10 | 0.00 |
December | 0.372370E+11 | 0.103129E+11 | 0.108529E+11 | 0.00 | 0.149810E+11 | 0.00 | 0.00 | 0.208772E+10 | 0.00 | 0.00 | 0.00 | 0.532352E+10 | 0.00 |
Annual Sum or Average | 0.441522E+12 | 0.100051E+12 | 0.128721E+12 | 0.00 | 0.179142E+12 | 0.00 | 0.00 | 0.669385E+11 | 0.00 | 0.00 | 0.00 | 0.622909E+11 | 0.00 |
Minimum of Months | 0.337970E+11 | 0.659082E+10 | 0.985143E+10 | 0.00 | 0.135941E+11 | 0.00 | 0.00 | 0.405985E+09 | 0.00 | 0.00 | 0.00 | 0.483900E+10 | 0.00 |
Maximum of Months | 0.378801E+11 | 0.103129E+11 | 0.110560E+11 | 0.00 | 0.154762E+11 | 0.00 | 0.00 | 0.152912E+11 | 0.00 | 0.00 | 0.00 | 0.538499E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.676891E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.306491E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.139148E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 6869475.17 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 59309223.59 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.244104E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.139148E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 27522.57 | 01-JAN-11:09 | 7619.51 | 01-JAN-06:10 | 8089.53 | 01-JAN-11:09 | 0.00 | 10702.50 | 03-JAN-09:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 27522.57 | 01-FEB-10:09 | 7619.51 | 01-FEB-06:10 | 8089.53 | 01-FEB-10:09 | 0.00 | 10567.99 | 28-FEB-09:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 27522.57 | 01-MAR-10:09 | 7619.51 | 01-MAR-06:10 | 8089.53 | 01-MAR-10:09 | 0.00 | 10889.52 | 30-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 27522.57 | 01-APR-09:09 | 7619.51 | 01-APR-05:10 | 8089.53 | 01-APR-09:09 | 0.00 | 10563.65 | 27-APR-08:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 27522.57 | 01-MAY-09:09 | 7619.51 | 01-MAY-18:30 | 8089.53 | 01-MAY-09:09 | 0.00 | 10723.61 | 03-MAY-08:09 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 27522.57 | 01-JUN-09:09 | 7619.51 | 01-JUN-18:49 | 8089.53 | 01-JUN-09:09 | 0.00 | 10934.83 | 26-JUN-08:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 27522.57 | 01-JUL-09:09 | 7619.51 | 01-JUL-18:00 | 8089.53 | 01-JUL-09:09 | 0.00 | 10934.83 | 21-JUL-08:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 27522.57 | 01-AUG-09:09 | 7619.51 | 01-AUG-18:49 | 8089.53 | 01-AUG-09:09 | 0.00 | 11041.78 | 07-AUG-08:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 27522.57 | 01-SEP-09:09 | 7619.51 | 01-SEP-05:10 | 8089.53 | 01-SEP-09:09 | 0.00 | 11550.11 | 29-SEP-12:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 27522.57 | 01-OCT-10:09 | 7619.51 | 01-OCT-05:10 | 8089.53 | 01-OCT-10:09 | 0.00 | 11572.62 | 16-OCT-12:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 27522.57 | 01-NOV-09:09 | 7619.51 | 01-NOV-05:10 | 8089.53 | 01-NOV-09:09 | 0.00 | 10688.82 | 19-NOV-10:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 27522.57 | 01-DEC-10:09 | 7619.51 | 01-DEC-06:10 | 8089.53 | 01-DEC-10:09 | 0.00 | 10624.34 | 05-DEC-09:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 27522.57 | 7619.51 | 8089.53 | 0.00 | 10563.65 | 0.00 | 0.00 | |||||
Maximum of Months | 27522.57 | 7619.51 | 8089.53 | 0.00 | 11572.62 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 15852.51 | 14-JAN-14:00 | 0.00 | 0.00 | 0.00 | 11495.98 | 05-JAN-18:00 | 0.00 |
February | 13359.20 | 01-FEB-12:09 | 0.00 | 0.00 | 0.00 | 9710.93 | 27-FEB-13:39 | 0.00 |
March | 13404.18 | 23-MAR-13:00 | 0.00 | 0.00 | 0.00 | 9745.47 | 29-MAR-14:20 | 0.00 |
April | 18570.06 | 26-APR-12:00 | 0.00 | 0.00 | 0.00 | 9705.74 | 04-APR-12:39 | 0.00 |
May | 14756.36 | 04-MAY-12:09 | 0.00 | 0.00 | 0.00 | 9699.66 | 25-MAY-12:30 | 0.00 |
June | 18006.05 | 28-JUN-12:09 | 0.00 | 0.00 | 0.00 | 10997.45 | 08-JUN-15:09 | 0.00 |
July | 25288.75 | 31-JUL-12:00 | 0.00 | 0.00 | 0.00 | 9487.72 | 05-JUL-10:50 | 0.00 |
August | 24588.23 | 17-AUG-13:00 | 0.00 | 0.00 | 0.00 | 9662.09 | 02-AUG-16:49 | 0.00 |
September | 37221.57 | 29-SEP-12:00 | 0.00 | 0.00 | 0.00 | 8496.00 | 28-SEP-13:50 | 0.00 |
October | 38180.95 | 16-OCT-11:09 | 0.00 | 0.00 | 0.00 | 9701.01 | 25-OCT-12:09 | 0.00 |
November | 17660.14 | 19-NOV-12:00 | 0.00 | 0.00 | 0.00 | 7611.94 | 21-NOV-14:39 | 0.00 |
December | 15934.40 | 19-DEC-13:09 | 0.00 | 0.00 | 0.00 | 9706.03 | 06-DEC-13:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 13359.20 | 0.00 | 0.00 | 0.00 | 7611.94 | 0.00 | ||
Maximum of Months | 38180.95 | 0.00 | 0.00 | 0.00 | 11495.98 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 67432.91 | 14-JAN-12:30 | 27522.57 | 8089.53 | 0.00 | 0.00 | 10452.02 | 0.00 | 0.00 | 13797.08 | 0.00 |
February | 64214.85 | 03-FEB-13:50 | 27522.57 | 8089.53 | 0.00 | 0.00 | 10452.02 | 0.00 | 0.00 | 10560.64 | 0.00 |
March | 64321.83 | 22-MAR-12:50 | 27522.57 | 8089.53 | 0.00 | 0.00 | 10452.02 | 0.00 | 0.00 | 10673.00 | 0.00 |
April | 70321.57 | 26-APR-11:50 | 27522.57 | 8089.53 | 0.00 | 0.00 | 10452.02 | 0.00 | 0.00 | 16399.56 | 0.00 |
May | 66125.14 | 04-MAY-12:20 | 27522.57 | 8089.53 | 0.00 | 0.00 | 10452.02 | 0.00 | 0.00 | 14600.97 | 0.00 |
June | 70221.58 | 28-JUN-11:00 | 27522.57 | 8089.53 | 0.00 | 0.00 | 10452.02 | 0.00 | 0.00 | 16597.87 | 0.00 |
July | 77906.75 | 19-JUL-14:09 | 27522.57 | 8089.53 | 0.00 | 0.00 | 10452.02 | 0.00 | 0.00 | 22599.46 | 0.00 |
August | 76313.24 | 18-AUG-14:20 | 27522.57 | 8089.53 | 0.00 | 0.00 | 10452.02 | 0.00 | 0.00 | 22429.89 | 0.00 |
September | 89131.59 | 29-SEP-12:09 | 27522.57 | 8089.53 | 0.00 | 0.00 | 11475.35 | 0.00 | 0.00 | 36582.76 | 0.00 |
October | 89836.85 | 16-OCT-11:30 | 27522.57 | 8089.53 | 0.00 | 0.00 | 11518.51 | 0.00 | 0.00 | 37865.19 | 0.00 |
November | 69019.12 | 19-NOV-12:00 | 27522.57 | 8089.53 | 0.00 | 0.00 | 10452.02 | 0.00 | 0.00 | 17660.14 | 0.00 |
December | 67645.94 | 05-DEC-14:20 | 27522.57 | 8089.53 | 0.00 | 0.00 | 10452.02 | 0.00 | 0.00 | 14000.11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 64214.85 | 27522.57 | 8089.53 | 0.00 | 0.00 | 10452.02 | 0.00 | 0.00 | 10560.64 | 0.00 | |
Maximum of Months | 89836.85 | 27522.57 | 8089.53 | 0.00 | 0.00 | 11518.51 | 0.00 | 0.00 | 37865.19 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 29406.25 | 03-JAN-09:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 11837.67 | 28-FEB-09:30 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 48795.34 | 30-MAR-08:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 7972.55 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 4500.18 | 13-DEC-09:20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 48795.34 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 296.33 | 22.64 | 66.50 | 22.86 | 0.67 | 22.86 |
February | 301.00 | 22.64 | 42.67 | 22.79 | 0.83 | 22.79 |
March | 356.17 | 22.31 | 66.50 | 22.54 | 2.17 | 22.52 |
April | 126.17 | 23.15 | 216.67 | 23.62 | 0.00 | 23.62 |
May | 102.00 | 23.22 | 228.00 | 23.69 | 0.00 | 23.69 |
June | 17.67 | 23.50 | 394.67 | 23.89 | 1.33 | 23.89 |
July | 44.33 | 24.00 | 484.50 | 23.92 | 44.33 | 23.93 |
August | 48.33 | 24.03 | 492.50 | 23.93 | 48.33 | 23.94 |
September | 30.83 | 23.83 | 429.00 | 23.90 | 25.17 | 23.90 |
October | 75.17 | 23.83 | 306.50 | 23.89 | 34.33 | 23.91 |
November | 179.17 | 23.34 | 129.17 | 23.56 | 0.00 | 23.56 |
December | 334.50 | 22.99 | 23.00 | 23.04 | 0.00 | 23.04 |
Annual Sum or Average | 1911.67 | 22.91 | 2879.67 | 23.50 | 157.17 | 23.52 |
Minimum of Months | 17.67 | 22.31 | 23.00 | 22.54 | 0.00 | 22.52 |
Maximum of Months | 356.17 | 24.03 | 492.50 | 23.93 | 48.33 | 23.94 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 167.00 | 23.51 | 100.17 | 23.66 | 0.00 | 23.66 |
February | 139.50 | 23.43 | 79.67 | 23.60 | 0.00 | 23.60 |
March | 183.50 | 23.16 | 108.17 | 23.43 | 0.00 | 23.43 |
April | 41.33 | 23.72 | 253.83 | 23.88 | 0.00 | 23.88 |
May | 20.50 | 23.78 | 254.00 | 23.91 | 0.00 | 23.91 |
June | 1.83 | 23.84 | 417.83 | 23.93 | 1.67 | 23.93 |
July | 59.67 | 24.03 | 489.50 | 23.94 | 59.67 | 23.95 |
August | 58.33 | 24.09 | 496.50 | 23.95 | 58.33 | 23.97 |
September | 24.17 | 23.89 | 441.67 | 23.92 | 24.17 | 23.92 |
October | 67.33 | 23.82 | 306.00 | 23.91 | 35.83 | 23.91 |
November | 81.00 | 23.88 | 161.67 | 23.90 | 0.00 | 23.90 |
December | 175.50 | 23.74 | 55.00 | 23.78 | 0.00 | 23.78 |
Annual Sum or Average | 1019.67 | 23.61 | 3164.00 | 23.85 | 179.67 | 23.85 |
Minimum of Months | 1.83 | 23.16 | 55.00 | 23.43 | 0.00 | 23.43 |
Maximum of Months | 183.50 | 24.09 | 496.50 | 23.95 | 59.67 | 23.97 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 153.00 | 23.13 | 61.50 | 23.36 | 0.00 | 23.36 |
February | 132.17 | 23.11 | 56.33 | 23.35 | 0.67 | 23.35 |
March | 177.33 | 22.79 | 75.50 | 23.12 | 0.00 | 23.12 |
April | 50.00 | 23.43 | 177.33 | 23.82 | 0.00 | 23.82 |
May | 33.50 | 23.57 | 187.67 | 23.88 | 0.00 | 23.88 |
June | 4.33 | 23.71 | 305.50 | 23.95 | 1.00 | 23.95 |
July | 33.83 | 24.18 | 363.83 | 24.00 | 33.83 | 24.02 |
August | 36.17 | 24.17 | 376.17 | 24.00 | 36.17 | 24.01 |
September | 16.67 | 24.00 | 330.17 | 23.97 | 15.33 | 23.97 |
October | 59.00 | 23.97 | 229.17 | 24.00 | 38.83 | 24.01 |
November | 82.67 | 23.71 | 105.00 | 23.82 | 0.00 | 23.82 |
December | 168.00 | 23.52 | 33.00 | 23.58 | 0.00 | 23.58 |
Annual Sum or Average | 946.67 | 23.36 | 2301.17 | 23.79 | 125.83 | 23.80 |
Minimum of Months | 4.33 | 22.79 | 33.00 | 23.12 | 0.00 | 23.12 |
Maximum of Months | 177.33 | 24.18 | 376.17 | 24.00 | 38.83 | 24.02 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 163.67 | 23.06 | 53.00 | 23.27 | 0.00 | 23.27 |
February | 144.67 | 23.07 | 47.67 | 23.27 | 0.67 | 23.27 |
March | 195.00 | 22.74 | 70.00 | 23.05 | 0.00 | 23.05 |
April | 55.83 | 23.41 | 166.50 | 23.79 | 0.00 | 23.79 |
May | 37.67 | 23.55 | 178.50 | 23.87 | 0.00 | 23.87 |
June | 5.33 | 23.69 | 302.83 | 23.95 | 1.00 | 23.95 |
July | 35.00 | 24.18 | 362.83 | 24.00 | 35.00 | 24.02 |
August | 36.67 | 24.17 | 375.83 | 24.00 | 36.67 | 24.01 |
September | 16.83 | 23.99 | 327.33 | 23.97 | 15.33 | 23.97 |
October | 59.83 | 23.97 | 226.50 | 24.00 | 39.00 | 24.01 |
November | 90.50 | 23.69 | 95.83 | 23.80 | 0.00 | 23.80 |
December | 183.17 | 23.49 | 29.83 | 23.55 | 0.00 | 23.55 |
Annual Sum or Average | 1024.17 | 23.32 | 2236.67 | 23.76 | 127.67 | 23.77 |
Minimum of Months | 5.33 | 22.74 | 29.83 | 23.05 | 0.00 | 23.05 |
Maximum of Months | 195.00 | 24.18 | 375.83 | 24.00 | 39.00 | 24.02 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 183.00 | 22.99 | 44.17 | 23.17 | 0.00 | 23.17 |
February | 178.50 | 23.02 | 32.33 | 23.15 | 0.50 | 23.15 |
March | 224.67 | 22.65 | 58.50 | 22.91 | 0.00 | 22.91 |
April | 66.33 | 23.35 | 152.33 | 23.75 | 0.00 | 23.75 |
May | 47.67 | 23.51 | 159.67 | 23.83 | 0.00 | 23.83 |
June | 7.17 | 23.67 | 294.50 | 23.94 | 1.00 | 23.94 |
July | 36.33 | 24.17 | 359.83 | 24.00 | 36.33 | 24.01 |
August | 39.83 | 24.15 | 374.67 | 23.99 | 39.83 | 24.01 |
September | 17.67 | 23.97 | 321.83 | 23.96 | 15.83 | 23.96 |
October | 65.17 | 23.95 | 222.17 | 23.99 | 40.67 | 24.00 |
November | 104.67 | 23.64 | 81.67 | 23.76 | 0.00 | 23.76 |
December | 207.17 | 23.42 | 23.50 | 23.47 | 0.00 | 23.47 |
Annual Sum or Average | 1178.17 | 23.25 | 2125.17 | 23.71 | 134.17 | 23.72 |
Minimum of Months | 7.17 | 22.65 | 23.50 | 22.91 | 0.00 | 22.91 |
Maximum of Months | 224.67 | 24.17 | 374.67 | 24.00 | 40.67 | 24.01 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 213.83 | 22.71 | 24.83 | 22.83 | 0.00 | 22.83 |
February | 230.17 | 22.65 | 15.83 | 22.73 | 2.00 | 22.73 |
March | 268.83 | 22.30 | 42.33 | 22.52 | 0.00 | 22.52 |
April | 93.33 | 23.09 | 124.00 | 23.55 | 0.00 | 23.55 |
May | 74.83 | 23.20 | 122.00 | 23.63 | 0.00 | 23.63 |
June | 13.00 | 23.45 | 258.33 | 23.88 | 0.83 | 23.88 |
July | 23.83 | 23.94 | 329.50 | 23.92 | 23.83 | 23.92 |
August | 23.17 | 23.98 | 343.67 | 23.92 | 23.17 | 23.92 |
September | 21.67 | 23.77 | 291.67 | 23.90 | 15.33 | 23.90 |
October | 49.33 | 23.85 | 205.67 | 23.91 | 25.67 | 23.91 |
November | 140.33 | 23.37 | 57.17 | 23.52 | 0.00 | 23.52 |
December | 241.83 | 23.10 | 14.17 | 23.14 | 0.00 | 23.14 |
Annual Sum or Average | 1394.17 | 22.91 | 1829.17 | 23.48 | 90.83 | 23.49 |
Minimum of Months | 13.00 | 22.30 | 14.17 | 22.52 | 0.00 | 22.52 |
Maximum of Months | 268.83 | 23.98 | 343.67 | 23.92 | 25.67 | 23.92 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 190.17 | 23.03 | 22.67 | 23.12 | 0.00 | 23.12 |
February | 205.17 | 23.04 | 13.17 | 23.10 | 1.83 | 23.10 |
March | 236.50 | 22.64 | 44.50 | 22.84 | 0.00 | 22.84 |
April | 69.83 | 23.45 | 115.17 | 23.74 | 0.00 | 23.74 |
May | 53.17 | 23.59 | 96.17 | 23.79 | 0.00 | 23.79 |
June | 8.83 | 23.74 | 246.67 | 23.91 | 1.00 | 23.91 |
July | 35.83 | 23.97 | 327.33 | 23.94 | 35.83 | 23.94 |
August | 39.33 | 23.97 | 343.50 | 23.93 | 39.33 | 23.93 |
September | 19.33 | 23.93 | 288.50 | 23.92 | 17.83 | 23.92 |
October | 66.83 | 23.90 | 189.83 | 23.93 | 43.67 | 23.93 |
November | 109.50 | 23.70 | 60.67 | 23.77 | 0.00 | 23.77 |
December | 226.67 | 23.43 | 14.83 | 23.46 | 0.00 | 23.46 |
Annual Sum or Average | 1261.17 | 23.26 | 1763.00 | 23.64 | 139.50 | 23.66 |
Minimum of Months | 8.83 | 22.64 | 13.17 | 22.84 | 0.00 | 22.84 |
Maximum of Months | 236.50 | 23.97 | 343.50 | 23.94 | 43.67 | 23.94 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 194.17 | 23.03 | 21.83 | 23.11 | 0.00 | 23.11 |
February | 209.33 | 23.03 | 11.83 | 23.08 | 1.83 | 23.08 |
March | 242.17 | 22.64 | 43.83 | 22.83 | 0.00 | 22.83 |
April | 73.17 | 23.44 | 111.00 | 23.73 | 0.00 | 23.73 |
May | 56.17 | 23.58 | 91.83 | 23.78 | 0.00 | 23.78 |
June | 9.83 | 23.73 | 242.50 | 23.91 | 1.00 | 23.91 |
July | 36.33 | 23.97 | 326.33 | 23.93 | 36.33 | 23.94 |
August | 40.67 | 23.97 | 342.50 | 23.93 | 40.67 | 23.93 |
September | 20.50 | 23.92 | 286.33 | 23.92 | 18.00 | 23.92 |
October | 68.83 | 23.90 | 187.00 | 23.93 | 44.17 | 23.93 |
November | 112.83 | 23.69 | 57.83 | 23.76 | 0.00 | 23.76 |
December | 231.50 | 23.42 | 14.67 | 23.45 | 0.00 | 23.45 |
Annual Sum or Average | 1295.50 | 23.25 | 1737.50 | 23.63 | 142.00 | 23.65 |
Minimum of Months | 9.83 | 22.64 | 11.83 | 22.83 | 0.00 | 22.83 |
Maximum of Months | 242.17 | 23.97 | 342.50 | 23.93 | 44.17 | 23.94 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 216.83 | 22.97 | 18.83 | 23.04 | 0.33 | 23.04 |
February | 230.00 | 22.90 | 7.83 | 22.93 | 1.83 | 22.93 |
March | 263.50 | 22.53 | 36.00 | 22.69 | 0.50 | 22.69 |
April | 92.67 | 23.37 | 96.50 | 23.65 | 0.00 | 23.65 |
May | 72.50 | 23.50 | 76.67 | 23.70 | 0.00 | 23.70 |
June | 14.50 | 23.69 | 228.67 | 23.90 | 1.17 | 23.90 |
July | 37.67 | 23.97 | 323.67 | 23.93 | 37.67 | 23.94 |
August | 42.83 | 23.96 | 340.33 | 23.92 | 42.83 | 23.93 |
September | 24.17 | 23.87 | 280.00 | 23.91 | 18.17 | 23.92 |
October | 74.67 | 23.89 | 180.33 | 23.93 | 45.83 | 23.93 |
November | 132.17 | 23.61 | 42.33 | 23.68 | 0.00 | 23.68 |
December | 256.00 | 23.34 | 12.00 | 23.36 | 0.00 | 23.36 |
Annual Sum or Average | 1457.50 | 23.18 | 1643.17 | 23.57 | 148.33 | 23.59 |
Minimum of Months | 14.50 | 22.53 | 7.83 | 22.69 | 0.00 | 22.69 |
Maximum of Months | 263.50 | 23.97 | 340.33 | 23.93 | 45.83 | 23.94 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 256.17 | 22.88 | 18.67 | 22.92 | 2.67 | 22.90 |
February | 261.17 | 22.68 | 5.50 | 22.70 | 2.17 | 22.70 |
March | 285.17 | 22.36 | 28.33 | 22.47 | 3.33 | 22.45 |
April | 118.33 | 23.22 | 86.00 | 23.51 | 0.17 | 23.51 |
May | 111.00 | 23.37 | 53.33 | 23.54 | 0.00 | 23.54 |
June | 30.50 | 23.53 | 202.00 | 23.87 | 1.33 | 23.87 |
July | 41.33 | 23.96 | 320.83 | 23.93 | 39.67 | 23.94 |
August | 43.50 | 23.96 | 336.50 | 23.92 | 43.00 | 23.93 |
September | 35.33 | 23.72 | 268.33 | 23.90 | 18.50 | 23.90 |
October | 90.67 | 23.86 | 176.50 | 23.91 | 48.00 | 23.91 |
November | 182.83 | 23.42 | 20.67 | 23.47 | 0.00 | 23.47 |
December | 294.83 | 23.17 | 5.50 | 23.18 | 0.00 | 23.18 |
Annual Sum or Average | 1750.83 | 23.06 | 1522.17 | 23.45 | 158.83 | 23.47 |
Minimum of Months | 30.50 | 22.36 | 5.50 | 22.47 | 0.00 | 22.45 |
Maximum of Months | 294.83 | 23.96 | 336.50 | 23.93 | 48.00 | 23.94 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 23.11529 | 39.17989 | 0.16644 | 6.83722 |
February | 448.00000 | 23.01843 | 42.21878 | 0.15787 | 6.47276 |
March | 497.00000 | 22.73014 | 45.56399 | 0.10833 | 6.69053 |
April | 479.00000 | 23.66461 | 46.88432 | 0.36442 | 8.17995 |
May | 496.00000 | 23.73430 | 46.19235 | -0.5358 | 11.50077 |
June | 481.00000 | 23.87592 | 51.52010 | -0.4209 | 8.88389 |
July | 495.00000 | 23.91402 | 56.65884 | -0.3323 | 7.39709 |
August | 497.00000 | 23.91766 | 58.35032 | -0.3174 | 7.18751 |
September | 479.00000 | 23.89256 | 53.72866 | -0.3725 | 8.05548 |
October | 496.00000 | 23.88668 | 44.88137 | 0.44389 | 9.39836 |
November | 480.00000 | 23.65471 | 39.28418 | 0.30983 | 7.45196 |
December | 496.00000 | 23.25181 | 34.27156 | 0.17100 | 6.29293 |
Annual Sum or Average | 5840.00000 | 23.55654 | 46.58240 | -0.0229 | 7.87057 |
Minimum of Months | 448.00000 | 22.73014 | 34.27156 | -0.5358 | 6.29293 |
Maximum of Months | 497.00000 | 23.91766 | 58.35032 | 0.44389 | 11.50077 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 23.76584 | 38.28593 | 0.31218 | 7.40392 |
February | 448.00000 | 23.74493 | 40.63513 | 0.31714 | 7.38433 |
March | 497.00000 | 23.60716 | 43.87676 | 0.29806 | 7.47159 |
April | 479.00000 | 23.88622 | 46.04696 | 0.41465 | 8.72342 |
May | 496.00000 | 23.90913 | 45.46291 | -0.4800 | 9.93686 |
June | 481.00000 | 23.92651 | 51.44379 | -0.4044 | 8.51508 |
July | 495.00000 | 23.92347 | 57.13897 | -0.3351 | 7.44644 |
August | 497.00000 | 23.93741 | 58.95219 | -0.3150 | 7.15976 |
September | 479.00000 | 23.91805 | 53.83239 | -0.3662 | 7.91700 |
October | 496.00000 | 23.90274 | 44.76412 | 0.44794 | 9.43776 |
November | 480.00000 | 23.90661 | 38.36513 | 0.36757 | 8.02563 |
December | 496.00000 | 23.83231 | 33.15503 | 0.30069 | 7.09142 |
Annual Sum or Average | 5840.00000 | 23.85530 | 46.02459 | 0.04469 | 8.04525 |
Minimum of Months | 448.00000 | 23.60716 | 33.15503 | -0.4800 | 7.09142 |
Maximum of Months | 497.00000 | 23.93741 | 58.95219 | 0.44794 | 9.93686 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 23.57611 | 36.84923 | 0.26547 | 7.21860 |
February | 336.00000 | 23.56827 | 39.87619 | 0.27867 | 7.09828 |
March | 379.00000 | 23.35705 | 43.58737 | 0.24709 | 7.24304 |
April | 360.00000 | 23.84030 | 45.38405 | 0.39902 | 8.55214 |
May | 375.00000 | 23.88298 | 44.77892 | -0.4943 | 10.30272 |
June | 366.00000 | 23.94063 | 50.82777 | -0.4064 | 8.58668 |
July | 369.00000 | 23.98518 | 56.69188 | -0.3187 | 7.26854 |
August | 379.00000 | 23.97906 | 58.47367 | -0.3021 | 7.02702 |
September | 360.00000 | 23.95797 | 53.29461 | -0.3568 | 7.82066 |
October | 371.00000 | 23.96347 | 43.94441 | 0.45773 | 9.66919 |
November | 360.00000 | 23.84669 | 37.49121 | 0.35150 | 7.82227 |
December | 369.00000 | 23.70931 | 32.13698 | 0.27322 | 6.84315 |
Annual Sum or Average | 4395.00000 | 23.80122 | 45.33516 | 0.03002 | 7.95960 |
Minimum of Months | 336.00000 | 23.35705 | 32.13698 | -0.4943 | 6.84315 |
Maximum of Months | 379.00000 | 23.98518 | 58.47367 | 0.45773 | 10.30272 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 23.52225 | 36.97410 | 0.24669 | 7.16019 |
February | 336.00000 | 23.51890 | 40.02857 | 0.26225 | 6.98051 |
March | 379.00000 | 23.28377 | 43.78161 | 0.22474 | 7.11671 |
April | 360.00000 | 23.82620 | 45.45235 | 0.39106 | 8.44512 |
May | 375.00000 | 23.87536 | 44.82735 | -0.5023 | 10.48500 |
June | 366.00000 | 23.93803 | 50.86607 | -0.4111 | 8.67001 |
July | 369.00000 | 23.98368 | 56.73323 | -0.3215 | 7.30480 |
August | 379.00000 | 23.97765 | 58.51718 | -0.3046 | 7.05737 |
September | 360.00000 | 23.95592 | 53.33411 | -0.3606 | 7.87794 |
October | 371.00000 | 23.96162 | 43.96657 | 0.45581 | 9.63427 |
November | 360.00000 | 23.83682 | 37.54544 | 0.34499 | 7.73676 |
December | 369.00000 | 23.67992 | 32.21952 | 0.26148 | 6.74087 |
Annual Sum or Average | 4395.00000 | 23.78071 | 45.41072 | 0.02108 | 7.94031 |
Minimum of Months | 336.00000 | 23.28377 | 32.21952 | -0.5023 | 6.74087 |
Maximum of Months | 379.00000 | 23.98368 | 58.51718 | 0.45581 | 10.48500 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 23.44138 | 37.17302 | 0.22002 | 7.04770 |
February | 336.00000 | 23.40909 | 40.36713 | 0.23004 | 6.76340 |
March | 379.00000 | 23.14193 | 44.16736 | 0.18460 | 6.91030 |
April | 360.00000 | 23.79516 | 45.59932 | 0.37706 | 8.26852 |
May | 375.00000 | 23.85562 | 44.94195 | -0.5174 | 10.85418 |
June | 366.00000 | 23.93166 | 50.95452 | -0.4200 | 8.83289 |
July | 369.00000 | 23.97893 | 56.85447 | -0.3282 | 7.39384 |
August | 379.00000 | 23.97307 | 58.64854 | -0.3110 | 7.13818 |
September | 360.00000 | 23.95041 | 53.42903 | -0.3684 | 8.00116 |
October | 371.00000 | 23.95521 | 44.05732 | 0.45062 | 9.54069 |
November | 360.00000 | 23.81288 | 37.67247 | 0.33331 | 7.59274 |
December | 369.00000 | 23.61277 | 32.39937 | 0.23904 | 6.56718 |
Annual Sum or Average | 4395.00000 | 23.73911 | 45.57829 | 0.00470 | 7.91727 |
Minimum of Months | 336.00000 | 23.14193 | 32.39937 | -0.5174 | 6.56718 |
Maximum of Months | 379.00000 | 23.97893 | 58.64854 | 0.45062 | 10.85418 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.12259 | 39.70538 | 0.15591 | 6.74318 |
February | 308.00000 | 22.94501 | 43.36655 | 0.13798 | 6.27557 |
March | 348.00000 | 22.64605 | 46.97864 | 0.08327 | 6.56405 |
April | 330.00000 | 23.64440 | 47.34558 | 0.34495 | 7.88213 |
May | 344.00000 | 23.72248 | 46.63119 | -0.5617 | 12.02678 |
June | 336.00000 | 23.86780 | 51.88503 | -0.4457 | 9.30999 |
July | 338.00000 | 23.91574 | 57.18547 | -0.3517 | 7.67288 |
August | 348.00000 | 23.90918 | 58.74104 | -0.3353 | 7.42627 |
September | 330.00000 | 23.88332 | 54.10612 | -0.3915 | 8.35499 |
October | 340.00000 | 23.89871 | 45.27689 | 0.44155 | 9.30075 |
November | 330.00000 | 23.63091 | 39.83543 | 0.29822 | 7.18980 |
December | 338.00000 | 23.30091 | 35.00473 | 0.17804 | 6.19504 |
Annual Sum or Average | 4030.00000 | 23.54273 | 47.22106 | -0.0399 | 7.92557 |
Minimum of Months | 308.00000 | 22.64605 | 35.00473 | -0.5617 | 6.19504 |
Maximum of Months | 348.00000 | 23.91574 | 58.74104 | 0.44155 | 12.02678 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.40123 | 38.79124 | 0.19814 | 6.84691 |
February | 308.00000 | 23.31829 | 42.12137 | 0.19746 | 6.52614 |
March | 348.00000 | 23.02721 | 45.82977 | 0.14458 | 6.71732 |
April | 330.00000 | 23.79688 | 46.63272 | 0.36294 | 8.00387 |
May | 344.00000 | 23.84602 | 45.93973 | -0.5432 | 11.38703 |
June | 336.00000 | 23.90105 | 51.80745 | -0.4495 | 9.34679 |
July | 338.00000 | 23.92877 | 57.80658 | -0.3594 | 7.80055 |
August | 348.00000 | 23.91998 | 59.50520 | -0.3431 | 7.54327 |
September | 330.00000 | 23.91125 | 54.35172 | -0.3965 | 8.41467 |
October | 340.00000 | 23.91761 | 45.28444 | 0.43552 | 9.20589 |
November | 330.00000 | 23.81398 | 38.93860 | 0.32192 | 7.40489 |
December | 338.00000 | 23.56832 | 33.99122 | 0.21803 | 6.36055 |
Annual Sum or Average | 4030.00000 | 23.69681 | 46.80608 | -0.0207 | 7.97433 |
Minimum of Months | 308.00000 | 23.02721 | 33.99122 | -0.5432 | 6.36055 |
Maximum of Months | 348.00000 | 23.92877 | 59.50520 | 0.43552 | 11.38703 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.38855 | 38.83074 | 0.19331 | 6.82451 |
February | 308.00000 | 23.29728 | 42.18710 | 0.19108 | 6.49251 |
March | 348.00000 | 23.00616 | 45.88944 | 0.13840 | 6.70032 |
April | 330.00000 | 23.79040 | 46.67248 | 0.35933 | 7.95765 |
May | 344.00000 | 23.84149 | 45.97747 | -0.5479 | 11.50378 |
June | 336.00000 | 23.89989 | 51.84056 | -0.4534 | 9.42313 |
July | 338.00000 | 23.92802 | 57.84695 | -0.3626 | 7.84993 |
August | 348.00000 | 23.91940 | 59.54793 | -0.3463 | 7.58892 |
September | 330.00000 | 23.91009 | 54.38490 | -0.4001 | 8.47632 |
October | 340.00000 | 23.91686 | 45.31367 | 0.43306 | 9.16149 |
November | 330.00000 | 23.80849 | 38.97921 | 0.31871 | 7.36463 |
December | 338.00000 | 23.55674 | 34.03061 | 0.21338 | 6.32637 |
Annual Sum or Average | 4030.00000 | 23.68961 | 46.84772 | -0.0248 | 7.98416 |
Minimum of Months | 308.00000 | 23.00616 | 34.03061 | -0.5479 | 6.32637 |
Maximum of Months | 348.00000 | 23.92802 | 59.54793 | 0.43306 | 11.50378 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.29405 | 39.09385 | 0.16368 | 6.70815 |
February | 308.00000 | 23.14189 | 42.65389 | 0.14756 | 6.30898 |
March | 348.00000 | 22.85395 | 46.31196 | 0.09654 | 6.60217 |
April | 330.00000 | 23.74447 | 46.89459 | 0.34138 | 7.76328 |
May | 344.00000 | 23.80777 | 46.17747 | -0.5697 | 12.10210 |
June | 336.00000 | 23.89322 | 51.97095 | -0.4648 | 9.66398 |
July | 338.00000 | 23.92586 | 57.97767 | -0.3680 | 7.93765 |
August | 348.00000 | 23.91755 | 59.68840 | -0.3514 | 7.66862 |
September | 330.00000 | 23.90480 | 54.51119 | -0.4091 | 8.64516 |
October | 340.00000 | 23.91461 | 45.42890 | 0.42751 | 9.06815 |
November | 330.00000 | 23.76046 | 39.21789 | 0.29968 | 7.15366 |
December | 338.00000 | 23.45960 | 34.31560 | 0.18265 | 6.15859 |
Annual Sum or Average | 4030.00000 | 23.63638 | 47.07481 | -0.0448 | 7.99592 |
Minimum of Months | 308.00000 | 22.85395 | 34.31560 | -0.5697 | 6.15859 |
Maximum of Months | 348.00000 | 23.92586 | 59.68840 | 0.42751 | 12.10210 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.12316 | 39.22356 | 0.10264 | 6.58343 |
February | 308.00000 | 22.86465 | 43.09588 | 0.05608 | 6.20470 |
March | 348.00000 | 22.63370 | 46.70923 | 0.02306 | 6.67623 |
April | 330.00000 | 23.65063 | 47.07265 | 0.30854 | 7.50440 |
May | 344.00000 | 23.72504 | 46.36501 | -0.6168 | 13.57171 |
June | 336.00000 | 23.87041 | 52.04996 | -0.4852 | 10.21180 |
July | 338.00000 | 23.92764 | 57.80592 | -0.3587 | 7.82385 |
August | 348.00000 | 23.91818 | 59.52034 | -0.3428 | 7.57919 |
September | 330.00000 | 23.88960 | 54.59809 | -0.4215 | 8.97622 |
October | 340.00000 | 23.90601 | 45.39095 | 0.41824 | 8.94211 |
November | 330.00000 | 23.62453 | 39.40026 | 0.24729 | 6.68846 |
December | 338.00000 | 23.25639 | 34.52312 | 0.11227 | 5.95002 |
Annual Sum or Average | 4030.00000 | 23.53517 | 47.19835 | -0.0821 | 8.07737 |
Minimum of Months | 308.00000 | 22.63370 | 34.52312 | -0.6168 | 5.95002 |
Maximum of Months | 348.00000 | 23.92764 | 59.52034 | 0.41824 | 13.57171 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.115912E+10 | 0.302564E+09 | 76.56 | 0.108427E+10 | 74845386.16 | 0.00 | 0.72 | 18-JAN-13:10 | 0.00 | 01-JAN-00:10 | 10611.04 | 18-JAN-13:10 | 10611.04 | 18-JAN-13:10 | 1580.27 | 17-JAN-13:40 | 2683.46 | 18-JAN-13:10 | 0.00 | 01-JAN-00:10 |
February | 0.284439E+09 | 75442844.18 | 38.44 | 0.272304E+09 | 12134738.35 | 0.00 | 0.58 | 01-FEB-12:10 | 0.00 | 01-FEB-00:10 | 8236.29 | 01-FEB-12:10 | 8236.29 | 01-FEB-12:10 | 897.62 | 01-FEB-13:50 | 2166.49 | 01-FEB-12:10 | 0.00 | 01-FEB-00:10 |
March | 0.601357E+09 | 0.156967E+09 | 48.83 | 0.490535E+09 | 0.110823E+09 | 0.00 | 0.64 | 23-MAR-14:00 | 0.00 | 01-MAR-00:10 | 9906.97 | 23-MAR-14:00 | 8127.82 | 11-MAR-14:00 | 2533.29 | 23-MAR-15:00 | 2411.27 | 23-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.218486E+10 | 0.561312E+09 | 151.33 | 0.177415E+10 | 0.410713E+09 | 0.00 | 1.00 | 27-APR-08:62 | 0.00 | 01-APR-00:10 | 24111.28 | 27-APR-08:62 | 14961.29 | 27-APR-08:62 | 9149.99 | 27-APR-08:62 | 5131.14 | 27-APR-08:62 | 0.00 | 01-APR-00:10 |
May | 0.184849E+10 | 0.482744E+09 | 162.61 | 0.150163E+10 | 0.346858E+09 | 0.00 | 1.00 | 03-MAY-08:62 | 0.00 | 01-MAY-00:10 | 28846.65 | 03-MAY-08:62 | 19562.21 | 03-MAY-08:62 | 9284.45 | 03-MAY-08:62 | 6132.73 | 03-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.537833E+10 | 0.134326E+10 | 262.37 | 0.392163E+10 | 0.145670E+10 | 0.00 | 1.00 | 17-JUN-08:62 | 0.00 | 01-JUN-00:10 | 35036.85 | 30-JUN-08:62 | 25080.18 | 21-JUN-08:62 | 16155.93 | 28-JUN-08:62 | 7408.49 | 30-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.118412E+11 | 0.283621E+10 | 385.48 | 0.802966E+10 | 0.381154E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-00:10 | 35885.67 | 19-JUL-08:62 | 25874.08 | 10-JUL-08:62 | 16942.91 | 20-JUL-08:62 | 7641.49 | 19-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.129082E+11 | 0.306090E+10 | 387.65 | 0.858150E+10 | 0.432672E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 36154.53 | 14-AUG-08:62 | 23567.33 | 30-AUG-08:62 | 16483.95 | 25-AUG-08:62 | 7720.68 | 14-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.770036E+10 | 0.192165E+10 | 308.33 | 0.567110E+10 | 0.202926E+10 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-00:10 | 36345.85 | 22-SEP-08:62 | 33067.25 | 30-SEP-08:61 | 17976.84 | 22-SEP-08:62 | 8104.67 | 29-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.894533E+10 | 0.224454E+10 | 333.12 | 0.732390E+10 | 0.162142E+10 | 0.00 | 1.00 | 01-OCT-07:03 | 0.00 | 01-OCT-00:10 | 35894.94 | 01-OCT-07:03 | 32343.65 | 17-OCT-08:62 | 18511.93 | 01-OCT-07:03 | 7880.56 | 16-OCT-08:61 | 0.00 | 01-OCT-00:10 |
November | 0.116331E+10 | 0.301296E+09 | 90.92 | 0.110309E+10 | 60217626.19 | 0.00 | 0.83 | 19-NOV-13:10 | 0.00 | 01-NOV-00:10 | 12752.35 | 19-NOV-13:10 | 12752.35 | 19-NOV-13:10 | 2207.22 | 10-NOV-09:02 | 3162.04 | 19-NOV-13:10 | 0.00 | 01-NOV-00:10 |
December | 0.144033E+10 | 0.375840E+09 | 109.78 | 0.142434E+10 | 15992888.39 | 0.00 | 1.00 | 05-DEC-09:02 | 0.00 | 01-DEC-00:10 | 25755.74 | 05-DEC-09:02 | 25755.74 | 05-DEC-09:02 | 1398.34 | 07-DEC-13:50 | 5795.26 | 05-DEC-09:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.554553E+11 | 0.136627E+11 | 2355.43 | 0.411781E+11 | 0.142772E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.284439E+09 | 75442844.18 | 38.44 | 0.272304E+09 | 12134738.35 | 0.00 | 0.58 | 0.00 | 8236.29 | 8127.82 | 897.62 | 2166.49 | 0.00 | |||||||
Maximum of Months | 0.129082E+11 | 0.306090E+10 | 387.65 | 0.858150E+10 | 0.432672E+10 | 0.00 | 1.00 | 0.00 | 36345.85 | 33067.25 | 18511.93 | 8104.67 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.798982E+09 | 0.178367E+09 | 87.42 | 0.764891E+09 | 34090635.17 | 0.00 | 1.00 | 15-JAN-18:01 | 0.00 | 01-JAN-00:10 | 17398.61 | 20-JAN-09:02 | 16190.24 | 15-JAN-18:01 | 6596.35 | 21-JAN-09:02 | 3418.70 | 20-JAN-09:02 | 0.00 | 01-JAN-00:10 |
February | 0.218442E+09 | 49318322.63 | 46.99 | 0.212460E+09 | 5982924.69 | 0.00 | 1.00 | 01-FEB-09:03 | 0.00 | 01-FEB-00:10 | 16642.51 | 05-FEB-18:10 | 16471.12 | 05-FEB-18:10 | 1795.49 | 16-FEB-09:03 | 3256.20 | 05-FEB-18:10 | 0.00 | 01-FEB-00:10 |
March | 0.407820E+09 | 91666731.68 | 54.67 | 0.353500E+09 | 54319204.64 | 0.00 | 0.68 | 23-MAR-14:00 | 0.00 | 01-MAR-00:10 | 6062.90 | 23-MAR-14:00 | 5686.23 | 11-MAR-14:00 | 1273.42 | 22-MAR-13:00 | 1271.53 | 23-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.124789E+10 | 0.276831E+09 | 133.80 | 0.107823E+10 | 0.169657E+09 | 0.00 | 1.00 | 26-APR-08:62 | 0.00 | 01-APR-00:10 | 17965.00 | 26-APR-08:62 | 14539.40 | 30-APR-17:07 | 6415.82 | 27-APR-08:62 | 3566.57 | 26-APR-08:62 | 0.00 | 01-APR-00:10 |
May | 0.944974E+09 | 0.213337E+09 | 139.58 | 0.815627E+09 | 0.129347E+09 | 0.00 | 1.00 | 01-MAY-08:62 | 0.00 | 01-MAY-00:10 | 17904.28 | 03-MAY-08:62 | 15211.45 | 24-MAY-08:62 | 5492.21 | 03-MAY-08:62 | 3510.16 | 03-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.281787E+10 | 0.610275E+09 | 226.89 | 0.217590E+10 | 0.641973E+09 | 0.00 | 1.00 | 02-JUN-08:62 | 0.00 | 01-JUN-00:10 | 18346.27 | 30-JUN-08:62 | 13802.61 | 23-JUN-08:62 | 8254.92 | 28-JUN-08:62 | 3577.42 | 30-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.644672E+10 | 0.134236E+10 | 332.32 | 0.462089E+10 | 0.182584E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-00:10 | 18773.27 | 19-JUL-08:62 | 13701.73 | 10-JUL-08:62 | 9653.09 | 19-JUL-20:34 | 3705.39 | 23-JUL-17:03 | 0.00 | 01-JUL-00:10 |
August | 0.700308E+10 | 0.144304E+10 | 330.09 | 0.493366E+10 | 0.206942E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 18921.75 | 14-AUG-08:62 | 13573.30 | 19-AUG-18:10 | 8924.93 | 06-AUG-19:12 | 3725.13 | 14-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.400270E+10 | 0.868648E+09 | 257.87 | 0.308417E+10 | 0.918525E+09 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-00:10 | 18849.38 | 22-SEP-08:62 | 17369.73 | 29-SEP-08:62 | 9451.53 | 21-SEP-20:02 | 3926.99 | 29-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.514867E+10 | 0.111684E+10 | 287.24 | 0.434819E+10 | 0.800484E+09 | 0.00 | 1.00 | 01-OCT-07:03 | 0.00 | 01-OCT-00:10 | 18748.95 | 04-OCT-20:02 | 17086.71 | 17-OCT-08:62 | 9506.56 | 01-OCT-07:03 | 3828.46 | 16-OCT-08:61 | 0.00 | 01-OCT-00:10 |
November | 0.762803E+09 | 0.169125E+09 | 89.33 | 0.737114E+09 | 25688556.71 | 0.00 | 1.00 | 01-NOV-08:62 | 0.00 | 01-NOV-00:10 | 17667.97 | 10-NOV-09:02 | 16518.20 | 28-NOV-09:02 | 5007.00 | 10-NOV-09:02 | 3469.26 | 10-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 0.103371E+10 | 0.230797E+09 | 118.38 | 0.102544E+10 | 8267972.70 | 0.00 | 1.00 | 04-DEC-09:02 | 0.00 | 01-DEC-00:10 | 16877.31 | 05-DEC-09:02 | 16877.31 | 05-DEC-09:02 | 1122.22 | 08-DEC-09:03 | 3502.97 | 05-DEC-09:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.308337E+11 | 0.659061E+10 | 2104.57 | 0.241501E+11 | 0.668359E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.218442E+09 | 49318322.63 | 46.99 | 0.212460E+09 | 5982924.69 | 0.00 | 0.68 | 0.00 | 6062.90 | 5686.23 | 1122.22 | 1271.53 | 0.00 | |||||||
Maximum of Months | 0.700308E+10 | 0.144304E+10 | 332.32 | 0.493366E+10 | 0.206942E+10 | 0.00 | 1.00 | 0.00 | 18921.75 | 17369.73 | 9653.09 | 3926.99 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.698388E+09 | 0.157052E+09 | 76.64 | 0.673027E+09 | 25360899.66 | 0.00 | 1.00 | 21-JAN-08:62 | 0.00 | 01-JAN-00:10 | 14282.02 | 21-JAN-08:62 | 8421.42 | 21-JAN-08:62 | 5860.60 | 21-JAN-08:62 | 2769.23 | 21-JAN-08:62 | 0.00 | 01-JAN-00:10 |
February | 0.167331E+09 | 37997197.74 | 39.89 | 0.166047E+09 | 1283980.43 | 0.00 | 0.66 | 01-FEB-12:10 | 0.00 | 01-FEB-00:10 | 5497.30 | 01-FEB-12:10 | 5497.30 | 01-FEB-12:10 | 362.08 | 01-FEB-13:40 | 1230.94 | 01-FEB-12:10 | 0.00 | 01-FEB-00:10 |
March | 0.338941E+09 | 76427353.68 | 45.75 | 0.296753E+09 | 42188270.47 | 0.00 | 0.65 | 11-MAR-14:00 | 0.00 | 01-MAR-00:10 | 5580.53 | 23-MAR-14:00 | 5441.21 | 11-MAR-14:00 | 1194.24 | 22-MAR-13:00 | 1185.67 | 23-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.102751E+10 | 0.230094E+09 | 113.39 | 0.893719E+09 | 0.133787E+09 | 0.00 | 1.00 | 27-APR-07:03 | 0.00 | 01-APR-00:10 | 17622.13 | 27-APR-07:03 | 10823.87 | 27-APR-07:03 | 6798.26 | 27-APR-07:03 | 3459.84 | 27-APR-07:03 | 0.00 | 01-APR-00:10 |
May | 0.752767E+09 | 0.170972E+09 | 119.86 | 0.652850E+09 | 99916875.74 | 0.00 | 1.00 | 01-MAY-07:03 | 0.00 | 01-MAY-00:10 | 17696.32 | 03-MAY-07:03 | 13244.10 | 04-MAY-07:03 | 6210.05 | 03-MAY-07:03 | 3472.92 | 03-MAY-07:03 | 0.00 | 01-MAY-00:10 |
June | 0.249811E+10 | 0.545477E+09 | 216.31 | 0.193328E+10 | 0.564826E+09 | 0.00 | 1.00 | 03-JUN-07:03 | 0.00 | 01-JUN-00:10 | 18133.31 | 30-JUN-07:02 | 13223.90 | 25-JUN-08:62 | 8521.54 | 29-JUN-07:02 | 3543.20 | 30-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.545236E+10 | 0.114623E+10 | 307.93 | 0.395348E+10 | 0.149887E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:10 | 18680.97 | 23-JUL-08:62 | 13367.76 | 04-JUL-08:62 | 9066.09 | 20-JUL-07:03 | 3696.60 | 23-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.616166E+10 | 0.128057E+10 | 310.13 | 0.437926E+10 | 0.178240E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 18669.30 | 19-AUG-07:02 | 12483.71 | 06-AUG-08:62 | 9222.05 | 18-AUG-07:02 | 3636.72 | 13-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.339181E+10 | 0.744534E+09 | 242.16 | 0.264089E+10 | 0.750915E+09 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:10 | 18600.98 | 22-SEP-07:02 | 17326.62 | 29-SEP-07:02 | 8854.69 | 22-SEP-07:02 | 3604.69 | 22-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 0.423917E+10 | 0.935160E+09 | 260.58 | 0.364029E+10 | 0.598879E+09 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 18696.71 | 05-OCT-07:02 | 16881.50 | 16-OCT-07:03 | 8688.93 | 05-OCT-07:03 | 3890.95 | 15-OCT-08:62 | 0.00 | 01-OCT-00:10 |
November | 0.644741E+09 | 0.143909E+09 | 79.93 | 0.629596E+09 | 15145154.26 | 0.00 | 1.00 | 01-NOV-07:03 | 0.00 | 01-NOV-00:10 | 16992.10 | 19-NOV-09:02 | 16992.10 | 19-NOV-09:02 | 5951.29 | 10-NOV-08:62 | 3525.61 | 19-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 0.910243E+09 | 0.205028E+09 | 112.58 | 0.904999E+09 | 5244173.06 | 0.00 | 0.89 | 05-DEC-08:63 | 0.00 | 01-DEC-00:10 | 7684.20 | 05-DEC-08:63 | 7684.20 | 05-DEC-08:63 | 778.46 | 10-DEC-09:03 | 1474.06 | 05-DEC-08:63 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.262830E+11 | 0.567345E+10 | 1925.16 | 0.207642E+11 | 0.551881E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.167331E+09 | 37997197.74 | 39.89 | 0.166047E+09 | 1283980.43 | 0.00 | 0.65 | 0.00 | 5497.30 | 5441.21 | 362.08 | 1185.67 | 0.00 | |||||||
Maximum of Months | 0.616166E+10 | 0.128057E+10 | 310.13 | 0.437926E+10 | 0.178240E+10 | 0.00 | 1.00 | 0.00 | 18696.71 | 17326.62 | 9222.05 | 3890.95 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.669906E+09 | 0.151179E+09 | 71.99 | 0.646421E+09 | 23485261.26 | 0.00 | 1.00 | 21-JAN-08:62 | 0.00 | 01-JAN-00:10 | 12868.26 | 21-JAN-08:62 | 7596.29 | 21-JAN-08:62 | 5271.97 | 21-JAN-08:62 | 2472.97 | 21-JAN-08:62 | 0.00 | 01-JAN-00:10 |
February | 0.158926E+09 | 36155607.89 | 37.33 | 0.157972E+09 | 953906.80 | 0.00 | 0.65 | 01-FEB-12:10 | 0.00 | 01-FEB-00:10 | 5375.76 | 01-FEB-12:10 | 5375.76 | 01-FEB-12:10 | 340.43 | 01-FEB-13:40 | 1208.68 | 01-FEB-12:10 | 0.00 | 01-FEB-00:10 |
March | 0.318795E+09 | 72121754.05 | 43.50 | 0.279329E+09 | 39466625.29 | 0.00 | 0.64 | 11-MAR-14:00 | 0.00 | 01-MAR-00:10 | 5473.85 | 23-MAR-14:00 | 5296.11 | 11-MAR-14:00 | 1156.71 | 22-MAR-13:00 | 1167.04 | 23-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.978378E+09 | 0.219645E+09 | 111.42 | 0.851224E+09 | 0.127154E+09 | 0.00 | 1.00 | 27-APR-07:03 | 0.00 | 01-APR-00:10 | 17667.67 | 27-APR-07:03 | 10842.26 | 27-APR-07:03 | 6825.40 | 27-APR-07:03 | 3468.81 | 27-APR-07:03 | 0.00 | 01-APR-00:10 |
May | 0.711514E+09 | 0.161870E+09 | 115.47 | 0.617804E+09 | 93709808.41 | 0.00 | 1.00 | 01-MAY-07:03 | 0.00 | 01-MAY-00:10 | 17742.68 | 03-MAY-07:03 | 13271.67 | 04-MAY-07:03 | 6236.14 | 03-MAY-07:03 | 3482.05 | 03-MAY-07:03 | 0.00 | 01-MAY-00:10 |
June | 0.244016E+10 | 0.533770E+09 | 213.65 | 0.188779E+10 | 0.552365E+09 | 0.00 | 1.00 | 03-JUN-07:03 | 0.00 | 01-JUN-00:10 | 18182.24 | 30-JUN-07:02 | 13249.35 | 25-JUN-08:62 | 8551.17 | 29-JUN-07:02 | 3552.77 | 30-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.539416E+10 | 0.113563E+10 | 306.64 | 0.391056E+10 | 0.148360E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:10 | 18731.56 | 23-JUL-08:62 | 13398.50 | 04-JUL-08:62 | 9096.13 | 20-JUL-07:03 | 3706.63 | 23-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.610566E+10 | 0.127087E+10 | 309.32 | 0.433940E+10 | 0.176626E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 18720.14 | 19-AUG-07:02 | 12509.77 | 06-AUG-08:62 | 9250.99 | 18-AUG-07:02 | 3646.51 | 13-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.333344E+10 | 0.732919E+09 | 240.00 | 0.259798E+10 | 0.735452E+09 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:10 | 18650.64 | 22-SEP-07:02 | 17372.89 | 29-SEP-07:02 | 8882.62 | 22-SEP-07:02 | 3614.39 | 22-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 0.420427E+10 | 0.928398E+09 | 259.84 | 0.361073E+10 | 0.593539E+09 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 18748.09 | 05-OCT-07:02 | 16936.12 | 16-OCT-07:03 | 8713.25 | 05-OCT-07:03 | 3902.00 | 15-OCT-08:62 | 0.00 | 01-OCT-00:10 |
November | 0.619839E+09 | 0.138764E+09 | 75.83 | 0.606227E+09 | 13612171.76 | 0.00 | 1.00 | 10-NOV-08:62 | 0.00 | 01-NOV-00:10 | 17032.87 | 19-NOV-09:02 | 17032.87 | 19-NOV-09:02 | 5390.02 | 10-NOV-08:62 | 3534.11 | 19-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 0.863947E+09 | 0.195375E+09 | 111.69 | 0.859006E+09 | 4940899.99 | 0.00 | 0.78 | 05-DEC-08:63 | 0.00 | 01-DEC-00:10 | 6544.75 | 05-DEC-08:63 | 6544.75 | 05-DEC-08:63 | 563.10 | 07-DEC-13:40 | 1385.79 | 19-DEC-13:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.257990E+11 | 0.557670E+10 | 1896.69 | 0.203645E+11 | 0.543454E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.158926E+09 | 36155607.89 | 37.33 | 0.157972E+09 | 953906.80 | 0.00 | 0.64 | 0.00 | 5375.76 | 5296.11 | 340.43 | 1167.04 | 0.00 | |||||||
Maximum of Months | 0.610566E+10 | 0.127087E+10 | 309.32 | 0.433940E+10 | 0.176626E+10 | 0.00 | 1.00 | 0.00 | 18748.09 | 17372.89 | 9250.99 | 3902.00 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.616653E+09 | 0.140016E+09 | 67.22 | 0.596055E+09 | 20598285.13 | 0.00 | 1.00 | 21-JAN-08:62 | 0.00 | 01-JAN-00:10 | 9805.17 | 21-JAN-08:62 | 6078.96 | 18-JAN-13:10 | 3994.14 | 21-JAN-08:62 | 1833.25 | 21-JAN-08:62 | 0.00 | 01-JAN-00:10 |
February | 0.142966E+09 | 32669319.31 | 31.08 | 0.142384E+09 | 581923.13 | 0.00 | 0.62 | 01-FEB-12:10 | 0.00 | 01-FEB-00:10 | 5105.38 | 01-FEB-12:10 | 5105.38 | 01-FEB-12:10 | 299.98 | 01-FEB-13:40 | 1156.59 | 01-FEB-12:10 | 0.00 | 01-FEB-00:10 |
March | 0.280945E+09 | 63927641.47 | 40.33 | 0.246337E+09 | 34607979.18 | 0.00 | 0.61 | 11-MAR-14:00 | 0.00 | 01-MAR-00:10 | 5239.35 | 23-MAR-14:00 | 5002.69 | 11-MAR-14:00 | 1080.05 | 22-MAR-13:00 | 1123.87 | 23-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.894922E+09 | 0.201670E+09 | 106.78 | 0.779020E+09 | 0.115903E+09 | 0.00 | 1.00 | 27-APR-07:03 | 0.00 | 01-APR-00:10 | 15490.90 | 27-APR-07:03 | 9511.82 | 27-APR-07:03 | 5979.08 | 27-APR-07:03 | 3014.91 | 27-APR-07:03 | 0.00 | 01-APR-00:10 |
May | 0.639619E+09 | 0.145948E+09 | 106.67 | 0.556237E+09 | 83382552.68 | 0.00 | 1.00 | 03-MAY-07:03 | 0.00 | 01-MAY-00:10 | 17513.77 | 03-MAY-07:03 | 12068.96 | 04-MAY-07:03 | 6181.09 | 03-MAY-07:03 | 3435.29 | 03-MAY-07:03 | 0.00 | 01-MAY-00:10 |
June | 0.230758E+10 | 0.506430E+09 | 208.54 | 0.178350E+10 | 0.524076E+09 | 0.00 | 1.00 | 03-JUN-07:03 | 0.00 | 01-JUN-00:10 | 18105.79 | 30-JUN-07:02 | 13165.63 | 25-JUN-08:62 | 8539.88 | 29-JUN-07:02 | 3537.99 | 30-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.520259E+10 | 0.109859E+10 | 302.38 | 0.376865E+10 | 0.143394E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:10 | 18652.80 | 23-JUL-08:62 | 13315.74 | 04-JUL-08:62 | 9017.83 | 20-JUL-07:02 | 3691.41 | 23-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.590681E+10 | 0.123347E+10 | 306.92 | 0.419612E+10 | 0.171068E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 18641.99 | 19-AUG-07:02 | 12427.70 | 06-AUG-08:62 | 9241.91 | 18-AUG-07:02 | 3631.44 | 13-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.318582E+10 | 0.702784E+09 | 236.09 | 0.248804E+10 | 0.697779E+09 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:10 | 18571.02 | 22-SEP-07:02 | 17298.91 | 29-SEP-07:02 | 8872.88 | 22-SEP-07:02 | 3599.31 | 22-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 0.405862E+10 | 0.898788E+09 | 256.30 | 0.348998E+10 | 0.568639E+09 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 18670.02 | 05-OCT-07:02 | 16853.17 | 16-OCT-07:03 | 8705.57 | 05-OCT-07:03 | 3883.02 | 15-OCT-08:62 | 0.00 | 01-OCT-00:10 |
November | 0.575455E+09 | 0.129444E+09 | 71.42 | 0.564169E+09 | 11285793.84 | 0.00 | 1.00 | 10-NOV-08:62 | 0.00 | 01-NOV-00:10 | 16953.87 | 19-NOV-09:02 | 16953.87 | 19-NOV-09:02 | 4142.94 | 10-NOV-08:62 | 3517.81 | 19-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 0.783736E+09 | 0.178278E+09 | 105.22 | 0.779341E+09 | 4394817.67 | 0.00 | 0.75 | 19-DEC-13:10 | 0.00 | 01-DEC-00:10 | 6177.04 | 19-DEC-13:10 | 6177.04 | 19-DEC-13:10 | 531.16 | 07-DEC-13:50 | 1347.08 | 19-DEC-13:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.245957E+11 | 0.533201E+10 | 1838.96 | 0.193898E+11 | 0.520587E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.142966E+09 | 32669319.31 | 31.08 | 0.142384E+09 | 581923.13 | 0.00 | 0.61 | 0.00 | 5105.38 | 5002.69 | 299.98 | 1123.87 | 0.00 | |||||||
Maximum of Months | 0.590681E+10 | 0.123347E+10 | 306.92 | 0.419612E+10 | 0.171068E+10 | 0.00 | 1.00 | 0.00 | 18670.02 | 17298.91 | 9241.91 | 3883.02 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.960330E+09 | 0.251713E+09 | 57.83 | 0.902157E+09 | 58173033.18 | 0.00 | 0.70 | 18-JAN-13:10 | 0.00 | 01-JAN-00:10 | 9923.86 | 18-JAN-13:10 | 9923.86 | 18-JAN-13:10 | 1936.54 | 20-JAN-09:02 | 2523.19 | 18-JAN-13:10 | 0.00 | 01-JAN-00:10 |
February | 0.257013E+09 | 68142522.05 | 29.33 | 0.249962E+09 | 7051815.40 | 0.00 | 0.57 | 01-FEB-12:10 | 0.00 | 01-FEB-00:10 | 7739.81 | 01-FEB-12:10 | 7739.81 | 01-FEB-12:10 | 807.66 | 01-FEB-13:40 | 2043.45 | 01-FEB-12:10 | 0.00 | 01-FEB-00:10 |
March | 0.494112E+09 | 0.128990E+09 | 38.83 | 0.408462E+09 | 85650029.91 | 0.00 | 0.62 | 23-MAR-14:10 | 0.00 | 01-MAR-00:10 | 9230.19 | 23-MAR-14:10 | 7261.78 | 11-MAR-14:00 | 2493.57 | 23-MAR-15:00 | 2254.27 | 23-MAR-14:10 | 0.00 | 01-MAR-00:10 |
April | 0.167854E+10 | 0.433727E+09 | 116.88 | 0.137046E+10 | 0.308082E+09 | 0.00 | 1.00 | 27-APR-08:62 | 0.00 | 01-APR-00:10 | 16927.26 | 27-APR-08:62 | 11221.17 | 26-APR-13:00 | 6446.24 | 27-APR-08:62 | 3606.03 | 27-APR-08:62 | 0.00 | 01-APR-00:10 |
May | 0.136195E+10 | 0.355935E+09 | 128.16 | 0.111526E+10 | 0.246694E+09 | 0.00 | 1.00 | 03-MAY-08:62 | 0.00 | 01-MAY-00:10 | 23620.29 | 03-MAY-08:62 | 16687.10 | 04-MAY-08:62 | 7719.28 | 03-MAY-08:62 | 5023.56 | 03-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.424864E+10 | 0.106505E+10 | 211.29 | 0.311668E+10 | 0.113197E+10 | 0.00 | 1.00 | 17-JUN-08:62 | 0.00 | 01-JUN-00:10 | 33721.74 | 30-JUN-08:62 | 26416.56 | 25-JUN-09:02 | 14622.25 | 29-JUN-08:62 | 7148.68 | 25-JUN-09:02 | 0.00 | 01-JUN-00:10 |
July | 0.913406E+10 | 0.219408E+10 | 297.19 | 0.625352E+10 | 0.288054E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-00:10 | 34980.70 | 30-JUL-09:02 | 26784.63 | 04-JUL-09:02 | 16389.36 | 20-JUL-08:62 | 7590.97 | 23-JUL-09:02 | 0.00 | 01-JUL-00:10 |
August | 0.102679E+11 | 0.243757E+10 | 301.49 | 0.690433E+10 | 0.336354E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 34941.38 | 14-AUG-08:62 | 23529.01 | 13-AUG-09:02 | 16168.15 | 25-AUG-08:62 | 7494.25 | 13-AUG-09:02 | 0.00 | 01-AUG-00:10 |
September | 0.608288E+10 | 0.152041E+10 | 238.83 | 0.453181E+10 | 0.155107E+10 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-00:10 | 34972.64 | 22-SEP-08:62 | 32009.78 | 30-SEP-08:61 | 16663.41 | 22-SEP-08:62 | 7884.00 | 29-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.717591E+10 | 0.180647E+10 | 257.31 | 0.597187E+10 | 0.120404E+10 | 0.00 | 1.00 | 01-OCT-09:02 | 0.00 | 01-OCT-00:10 | 34735.44 | 01-OCT-09:02 | 31636.37 | 17-OCT-08:62 | 16031.80 | 05-OCT-08:62 | 8250.11 | 15-OCT-09:01 | 0.00 | 01-OCT-00:10 |
November | 0.971888E+09 | 0.252699E+09 | 68.92 | 0.929127E+09 | 42761733.37 | 0.00 | 1.00 | 19-NOV-10:02 | 0.00 | 01-NOV-00:10 | 31935.35 | 19-NOV-10:02 | 31935.35 | 19-NOV-10:02 | 1850.78 | 10-NOV-13:10 | 7372.88 | 19-NOV-10:02 | 0.00 | 01-NOV-00:10 |
December | 0.124740E+10 | 0.327807E+09 | 95.14 | 0.123234E+10 | 15063542.58 | 0.00 | 1.00 | 05-DEC-09:02 | 0.00 | 01-DEC-00:10 | 16999.67 | 05-DEC-09:02 | 16999.67 | 05-DEC-09:02 | 1410.61 | 07-DEC-13:40 | 3828.02 | 05-DEC-09:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.438806E+11 | 0.108426E+11 | 1841.21 | 0.329860E+11 | 0.108946E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.257013E+09 | 68142522.05 | 29.33 | 0.249962E+09 | 7051815.40 | 0.00 | 0.57 | 0.00 | 7739.81 | 7261.78 | 807.66 | 2043.45 | 0.00 | |||||||
Maximum of Months | 0.102679E+11 | 0.243757E+10 | 301.49 | 0.690433E+10 | 0.336354E+10 | 0.00 | 1.00 | 0.00 | 34980.70 | 32009.78 | 16663.41 | 8250.11 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.555145E+09 | 0.126102E+09 | 56.01 | 0.536136E+09 | 19009351.96 | 0.00 | 1.00 | 20-JAN-09:02 | 0.00 | 01-JAN-00:10 | 9339.10 | 20-JAN-09:02 | 7013.50 | 20-JAN-09:02 | 3167.86 | 21-JAN-09:02 | 1739.93 | 20-JAN-09:02 | 0.00 | 01-JAN-00:10 |
February | 0.127930E+09 | 29311983.47 | 20.78 | 0.127394E+09 | 536170.16 | 0.00 | 0.60 | 01-FEB-12:10 | 0.00 | 01-FEB-00:10 | 4790.38 | 01-FEB-12:10 | 4790.38 | 01-FEB-12:10 | 287.59 | 01-FEB-13:40 | 1091.01 | 01-FEB-12:10 | 0.00 | 01-FEB-00:10 |
March | 0.249501E+09 | 56758525.42 | 31.75 | 0.217761E+09 | 31740265.17 | 0.00 | 0.60 | 23-MAR-14:10 | 0.00 | 01-MAR-00:10 | 5101.94 | 23-MAR-14:10 | 4494.32 | 11-MAR-14:00 | 1162.48 | 23-MAR-15:00 | 1091.79 | 23-MAR-14:10 | 0.00 | 01-MAR-00:10 |
April | 0.833944E+09 | 0.187834E+09 | 95.83 | 0.721171E+09 | 0.112773E+09 | 0.00 | 1.00 | 26-APR-08:62 | 0.00 | 01-APR-00:10 | 17209.95 | 27-APR-08:62 | 11010.06 | 27-APR-08:62 | 6199.88 | 27-APR-08:62 | 3377.44 | 27-APR-08:62 | 0.00 | 01-APR-00:10 |
May | 0.588868E+09 | 0.134199E+09 | 96.30 | 0.511146E+09 | 77721851.88 | 0.00 | 1.00 | 03-MAY-08:62 | 0.00 | 01-MAY-00:10 | 17324.07 | 03-MAY-08:62 | 13040.40 | 04-MAY-08:62 | 5416.62 | 03-MAY-08:62 | 3396.91 | 03-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.214331E+10 | 0.469733E+09 | 189.30 | 0.165092E+10 | 0.492388E+09 | 0.00 | 1.00 | 03-JUN-08:62 | 0.00 | 01-JUN-00:10 | 17677.91 | 30-JUN-08:62 | 13936.97 | 25-JUN-09:02 | 8068.69 | 28-JUN-08:62 | 3459.37 | 18-JUN-09:02 | 0.00 | 01-JUN-00:10 |
July | 0.486490E+10 | 0.102365E+10 | 283.98 | 0.350115E+10 | 0.136375E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-00:10 | 18347.01 | 30-JUL-09:02 | 14144.73 | 04-JUL-09:02 | 8593.53 | 20-JUL-08:62 | 3669.80 | 23-JUL-09:02 | 0.00 | 01-JUL-00:10 |
August | 0.551650E+10 | 0.114768E+10 | 284.11 | 0.390187E+10 | 0.161463E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 18317.01 | 14-AUG-08:62 | 12696.04 | 23-AUG-08:62 | 8363.94 | 25-AUG-08:62 | 3623.18 | 13-AUG-09:02 | 0.00 | 01-AUG-00:10 |
September | 0.300743E+10 | 0.662556E+09 | 216.42 | 0.234462E+10 | 0.662810E+09 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-00:10 | 18338.56 | 22-SEP-08:62 | 16791.22 | 30-SEP-08:61 | 8663.29 | 22-SEP-08:62 | 3813.07 | 29-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.377156E+10 | 0.834185E+09 | 237.89 | 0.324329E+10 | 0.528271E+09 | 0.00 | 1.00 | 01-OCT-09:02 | 0.00 | 01-OCT-00:10 | 18211.75 | 01-OCT-09:02 | 16629.24 | 17-OCT-08:62 | 8470.33 | 05-OCT-08:03 | 3995.41 | 15-OCT-09:01 | 0.00 | 01-OCT-00:10 |
November | 0.518536E+09 | 0.116781E+09 | 55.59 | 0.508556E+09 | 9980104.34 | 0.00 | 1.00 | 19-NOV-10:02 | 0.00 | 01-NOV-00:10 | 16793.11 | 19-NOV-10:02 | 16793.11 | 19-NOV-10:02 | 2440.98 | 10-NOV-09:02 | 3574.53 | 19-NOV-10:02 | 0.00 | 01-NOV-00:10 |
December | 0.694052E+09 | 0.158204E+09 | 90.82 | 0.689893E+09 | 4158360.57 | 0.00 | 1.00 | 05-DEC-09:02 | 0.00 | 01-DEC-00:10 | 16313.54 | 05-DEC-09:02 | 16313.54 | 05-DEC-09:02 | 528.56 | 07-DEC-13:50 | 3385.89 | 05-DEC-09:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.228717E+11 | 0.494699E+10 | 1658.78 | 0.179539E+11 | 0.491777E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.127930E+09 | 29311983.47 | 20.78 | 0.127394E+09 | 536170.16 | 0.00 | 0.60 | 0.00 | 4790.38 | 4494.32 | 287.59 | 1091.01 | 0.00 | |||||||
Maximum of Months | 0.551650E+10 | 0.114768E+10 | 284.11 | 0.390187E+10 | 0.161463E+10 | 0.00 | 1.00 | 0.00 | 18347.01 | 16793.11 | 8663.29 | 3995.41 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.543384E+09 | 0.123610E+09 | 56.22 | 0.525111E+09 | 18273539.83 | 0.00 | 0.94 | 20-JAN-09:02 | 0.00 | 01-JAN-00:10 | 8397.35 | 20-JAN-09:02 | 6304.98 | 20-JAN-09:02 | 2793.92 | 21-JAN-09:02 | 1594.05 | 20-JAN-09:02 | 0.00 | 01-JAN-00:10 |
February | 0.125053E+09 | 28679300.91 | 20.44 | 0.124540E+09 | 512658.71 | 0.00 | 0.60 | 01-FEB-12:10 | 0.00 | 01-FEB-00:10 | 4736.88 | 01-FEB-12:10 | 4736.88 | 01-FEB-12:10 | 280.58 | 01-FEB-13:40 | 1079.99 | 01-FEB-12:10 | 0.00 | 01-FEB-00:10 |
March | 0.243903E+09 | 55538061.99 | 31.00 | 0.212930E+09 | 30973119.32 | 0.00 | 0.60 | 23-MAR-14:10 | 0.00 | 01-MAR-00:10 | 5041.49 | 23-MAR-14:10 | 4442.19 | 11-MAR-14:00 | 1146.68 | 23-MAR-15:00 | 1080.13 | 23-MAR-14:10 | 0.00 | 01-MAR-00:10 |
April | 0.815828E+09 | 0.183930E+09 | 94.94 | 0.705466E+09 | 0.110361E+09 | 0.00 | 1.00 | 27-APR-08:62 | 0.00 | 01-APR-00:10 | 16698.06 | 27-APR-08:62 | 10678.78 | 27-APR-08:62 | 6019.28 | 27-APR-08:62 | 3271.44 | 27-APR-08:62 | 0.00 | 01-APR-00:10 |
May | 0.571308E+09 | 0.130310E+09 | 93.30 | 0.495981E+09 | 75326382.97 | 0.00 | 1.00 | 03-MAY-08:62 | 0.00 | 01-MAY-00:10 | 17252.32 | 03-MAY-08:62 | 12974.13 | 04-MAY-08:62 | 5406.86 | 03-MAY-08:62 | 3382.89 | 03-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.210069E+10 | 0.460927E+09 | 187.28 | 0.161731E+10 | 0.483383E+09 | 0.00 | 1.00 | 03-JUN-08:62 | 0.00 | 01-JUN-00:10 | 17605.23 | 30-JUN-08:62 | 13866.35 | 25-JUN-09:02 | 8046.48 | 28-JUN-08:62 | 3445.09 | 18-JUN-09:02 | 0.00 | 01-JUN-00:10 |
July | 0.480074E+10 | 0.101099E+10 | 282.67 | 0.345315E+10 | 0.134760E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-00:10 | 18271.48 | 30-JUL-09:02 | 14073.23 | 04-JUL-09:02 | 8567.43 | 20-JUL-08:62 | 3654.83 | 23-JUL-09:02 | 0.00 | 01-JUL-00:10 |
August | 0.544983E+10 | 0.113480E+10 | 283.73 | 0.385296E+10 | 0.159686E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 18241.60 | 14-AUG-08:62 | 12631.59 | 23-AUG-08:62 | 8340.05 | 25-AUG-08:62 | 3608.38 | 13-AUG-09:02 | 0.00 | 01-AUG-00:10 |
September | 0.295894E+10 | 0.652548E+09 | 214.80 | 0.230804E+10 | 0.650902E+09 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-00:10 | 18262.33 | 22-SEP-08:62 | 16720.24 | 30-SEP-08:61 | 8636.07 | 22-SEP-08:62 | 3797.22 | 29-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.372157E+10 | 0.823864E+09 | 236.37 | 0.320150E+10 | 0.520078E+09 | 0.00 | 1.00 | 01-OCT-09:02 | 0.00 | 01-OCT-00:10 | 18136.71 | 01-OCT-09:02 | 16555.45 | 17-OCT-08:62 | 8447.10 | 05-OCT-08:03 | 3978.10 | 15-OCT-09:01 | 0.00 | 01-OCT-00:10 |
November | 0.507801E+09 | 0.114505E+09 | 54.76 | 0.498375E+09 | 9425690.72 | 0.00 | 1.00 | 19-NOV-10:02 | 0.00 | 01-NOV-00:10 | 16716.71 | 19-NOV-10:02 | 16716.71 | 19-NOV-10:02 | 2212.05 | 10-NOV-09:02 | 3558.59 | 19-NOV-10:02 | 0.00 | 01-NOV-00:10 |
December | 0.676079E+09 | 0.154304E+09 | 90.93 | 0.672062E+09 | 4017362.88 | 0.00 | 1.00 | 05-DEC-09:02 | 0.00 | 01-DEC-00:10 | 15965.18 | 05-DEC-09:02 | 15965.18 | 05-DEC-09:02 | 518.48 | 07-DEC-13:50 | 3309.81 | 05-DEC-09:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.225151E+11 | 0.487400E+10 | 1646.45 | 0.176674E+11 | 0.484771E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.125053E+09 | 28679300.91 | 20.44 | 0.124540E+09 | 512658.71 | 0.00 | 0.60 | 0.00 | 4736.88 | 4442.19 | 280.58 | 1079.99 | 0.00 | |||||||
Maximum of Months | 0.544983E+10 | 0.113480E+10 | 283.73 | 0.385296E+10 | 0.159686E+10 | 0.00 | 1.00 | 0.00 | 18271.48 | 16720.24 | 8636.07 | 3978.10 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.492733E+09 | 0.112881E+09 | 53.58 | 0.477599E+09 | 15133898.29 | 0.00 | 0.69 | 14-JAN-15:00 | 0.00 | 01-JAN-00:10 | 5583.53 | 14-JAN-15:00 | 5583.53 | 14-JAN-15:00 | 993.46 | 20-JAN-09:02 | 1248.06 | 14-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.110064E+09 | 25394938.56 | 18.72 | 0.109688E+09 | 375744.53 | 0.00 | 0.57 | 01-FEB-12:10 | 0.00 | 01-FEB-00:10 | 4473.10 | 01-FEB-12:10 | 4473.10 | 01-FEB-12:10 | 232.87 | 01-FEB-13:40 | 1027.88 | 01-FEB-12:10 | 0.00 | 01-FEB-00:10 |
March | 0.217012E+09 | 49703307.77 | 29.08 | 0.190070E+09 | 26942062.25 | 0.00 | 0.57 | 23-MAR-14:10 | 0.00 | 01-MAR-00:10 | 4770.03 | 23-MAR-14:10 | 4228.00 | 11-MAR-14:00 | 1072.62 | 23-MAR-14:50 | 1029.70 | 23-MAR-14:10 | 0.00 | 01-MAR-00:10 |
April | 0.744733E+09 | 0.168651E+09 | 89.71 | 0.645197E+09 | 99535741.53 | 0.00 | 1.00 | 27-APR-08:62 | 0.00 | 01-APR-00:10 | 10858.34 | 27-APR-08:62 | 7019.45 | 27-APR-08:62 | 3838.90 | 27-APR-08:62 | 2052.45 | 27-APR-08:62 | 0.00 | 01-APR-00:10 |
May | 0.506818E+09 | 0.115947E+09 | 87.29 | 0.441473E+09 | 65345483.28 | 0.00 | 1.00 | 03-MAY-08:62 | 0.00 | 01-MAY-00:10 | 15390.81 | 03-MAY-08:62 | 11087.67 | 04-MAY-08:62 | 4816.73 | 03-MAY-08:62 | 2995.39 | 03-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.196452E+10 | 0.432780E+09 | 182.18 | 0.151296E+10 | 0.451562E+09 | 0.00 | 1.00 | 17-JUN-08:62 | 0.00 | 01-JUN-00:10 | 17533.99 | 30-JUN-08:62 | 13790.69 | 25-JUN-09:02 | 8047.47 | 28-JUN-08:62 | 3429.11 | 25-JUN-09:02 | 0.00 | 01-JUN-00:10 |
July | 0.463047E+10 | 0.977669E+09 | 280.00 | 0.333228E+10 | 0.129819E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-00:10 | 18197.36 | 30-JUL-09:02 | 14000.48 | 04-JUL-09:02 | 8557.81 | 20-JUL-08:62 | 3640.64 | 23-JUL-09:02 | 0.00 | 01-JUL-00:10 |
August | 0.527716E+10 | 0.110192E+10 | 281.40 | 0.373356E+10 | 0.154361E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 18167.25 | 14-AUG-08:62 | 12553.79 | 23-AUG-08:62 | 8337.00 | 25-AUG-08:62 | 3594.23 | 13-AUG-09:02 | 0.00 | 01-AUG-00:10 |
September | 0.280700E+10 | 0.621399E+09 | 208.90 | 0.219818E+10 | 0.608824E+09 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-00:10 | 18185.46 | 22-SEP-08:62 | 16651.89 | 30-SEP-08:61 | 8622.52 | 22-SEP-08:62 | 3781.40 | 29-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.356796E+10 | 0.792533E+09 | 234.54 | 0.307645E+10 | 0.491507E+09 | 0.00 | 1.00 | 01-OCT-09:02 | 0.00 | 01-OCT-00:10 | 18063.63 | 01-OCT-09:02 | 16471.92 | 17-OCT-08:62 | 8442.94 | 05-OCT-08:03 | 3959.76 | 15-OCT-09:01 | 0.00 | 01-OCT-00:10 |
November | 0.461105E+09 | 0.104663E+09 | 52.46 | 0.453705E+09 | 7399579.19 | 0.00 | 1.00 | 19-NOV-10:02 | 0.00 | 01-NOV-00:10 | 16617.45 | 19-NOV-10:02 | 16617.45 | 19-NOV-10:02 | 959.19 | 10-NOV-09:02 | 3538.91 | 19-NOV-10:02 | 0.00 | 01-NOV-00:10 |
December | 0.599325E+09 | 0.137663E+09 | 85.02 | 0.595873E+09 | 3452760.71 | 0.00 | 1.00 | 05-DEC-09:02 | 0.00 | 01-DEC-00:10 | 11176.55 | 05-DEC-09:02 | 11176.55 | 05-DEC-09:02 | 476.43 | 07-DEC-13:50 | 2252.27 | 05-DEC-09:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.213789E+11 | 0.464121E+10 | 1602.90 | 0.167670E+11 | 0.461187E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.110064E+09 | 25394938.56 | 18.72 | 0.109688E+09 | 375744.53 | 0.00 | 0.57 | 0.00 | 4473.10 | 4228.00 | 232.87 | 1027.88 | 0.00 | |||||||
Maximum of Months | 0.527716E+10 | 0.110192E+10 | 281.40 | 0.373356E+10 | 0.154361E+10 | 0.00 | 1.00 | 0.00 | 18197.36 | 16651.89 | 8622.52 | 3959.76 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.460797E+09 | 0.106465E+09 | 49.83 | 0.448054E+09 | 12742973.70 | 0.00 | 0.65 | 18-JAN-13:10 | 0.00 | 01-JAN-00:10 | 5593.44 | 18-JAN-13:10 | 5593.44 | 18-JAN-13:10 | 642.01 | 17-JAN-14:00 | 1259.50 | 18-JAN-13:10 | 0.00 | 01-JAN-00:10 |
February | 98315933.15 | 22872786.05 | 16.50 | 98028196.74 | 287736.41 | 0.00 | 0.56 | 01-FEB-12:10 | 0.00 | 01-FEB-00:10 | 4679.08 | 01-FEB-12:10 | 4679.08 | 01-FEB-12:10 | 200.37 | 01-FEB-13:40 | 1080.31 | 01-FEB-12:10 | 0.00 | 01-FEB-00:10 |
March | 0.219541E+09 | 50443063.51 | 27.83 | 0.192738E+09 | 26802924.88 | 0.00 | 0.54 | 23-MAR-14:10 | 0.00 | 01-MAR-00:10 | 4781.63 | 23-MAR-14:10 | 4339.29 | 11-MAR-13:50 | 1046.84 | 23-MAR-14:30 | 1043.25 | 23-MAR-14:10 | 0.00 | 01-MAR-00:10 |
April | 0.789225E+09 | 0.178784E+09 | 88.86 | 0.684871E+09 | 0.104354E+09 | 0.00 | 0.79 | 26-APR-13:00 | 0.00 | 01-APR-00:10 | 7348.23 | 26-APR-13:00 | 6817.30 | 26-APR-13:00 | 1038.03 | 25-APR-13:00 | 1594.41 | 26-APR-13:00 | 0.00 | 01-APR-00:10 |
May | 0.518317E+09 | 0.118710E+09 | 81.23 | 0.452207E+09 | 66109169.74 | 0.00 | 0.70 | 04-MAY-08:62 | 0.00 | 01-MAY-00:10 | 6382.56 | 04-MAY-08:62 | 5419.39 | 04-MAY-12:10 | 1455.94 | 03-MAY-08:62 | 1303.53 | 04-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.203496E+10 | 0.448768E+09 | 175.93 | 0.157060E+10 | 0.464357E+09 | 0.00 | 1.00 | 18-JUN-09:02 | 0.00 | 01-JUN-00:10 | 18974.86 | 30-JUN-08:62 | 14960.30 | 25-JUN-09:02 | 6532.24 | 30-JUN-08:62 | 3710.95 | 25-JUN-09:02 | 0.00 | 01-JUN-00:10 |
July | 0.497359E+10 | 0.104927E+10 | 273.20 | 0.359684E+10 | 0.137675E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-00:10 | 19687.48 | 30-JUL-09:02 | 15204.88 | 04-JUL-09:02 | 9330.36 | 20-JUL-08:62 | 3941.03 | 23-JUL-09:02 | 0.00 | 01-JUL-00:10 |
August | 0.566140E+10 | 0.118041E+10 | 278.39 | 0.402404E+10 | 0.163736E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 19656.43 | 14-AUG-08:62 | 13315.26 | 13-AUG-09:02 | 8820.10 | 08-AUG-08:62 | 3890.22 | 13-AUG-09:02 | 0.00 | 01-AUG-00:10 |
September | 0.281852E+10 | 0.626773E+09 | 196.33 | 0.222615E+10 | 0.592378E+09 | 0.00 | 1.00 | 03-SEP-09:02 | 0.00 | 01-SEP-00:10 | 19678.51 | 22-SEP-08:62 | 18016.37 | 30-SEP-08:61 | 9423.75 | 22-SEP-08:62 | 4075.61 | 29-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.354293E+10 | 0.792898E+09 | 221.13 | 0.309021E+10 | 0.452720E+09 | 0.00 | 1.00 | 01-OCT-09:02 | 0.00 | 01-OCT-00:10 | 19544.52 | 01-OCT-09:02 | 17689.73 | 17-OCT-08:62 | 9191.50 | 05-OCT-08:62 | 4281.83 | 15-OCT-09:01 | 0.00 | 01-OCT-00:10 |
November | 0.429915E+09 | 98407623.13 | 49.80 | 0.425336E+09 | 4578440.56 | 0.00 | 1.00 | 19-NOV-10:02 | 0.00 | 01-NOV-00:10 | 17860.04 | 19-NOV-10:02 | 17860.04 | 19-NOV-10:02 | 533.68 | 10-NOV-13:10 | 3813.10 | 19-NOV-10:02 | 0.00 | 01-NOV-00:10 |
December | 0.537070E+09 | 0.124429E+09 | 72.17 | 0.534387E+09 | 2682603.10 | 0.00 | 0.68 | 19-DEC-13:10 | 0.00 | 01-DEC-00:10 | 5723.97 | 19-DEC-13:10 | 5723.97 | 19-DEC-13:10 | 411.23 | 07-DEC-14:00 | 1275.85 | 19-DEC-13:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.220846E+11 | 0.479823E+10 | 1531.22 | 0.173435E+11 | 0.474113E+10 | 0.00 | ||||||||||||||
Minimum of Months | 98315933.15 | 22872786.05 | 16.50 | 98028196.74 | 287736.41 | 0.00 | 0.54 | 0.00 | 4679.08 | 4339.29 | 200.37 | 1043.25 | 0.00 | |||||||
Maximum of Months | 0.566140E+10 | 0.118041E+10 | 278.39 | 0.402404E+10 | 0.163736E+10 | 0.00 | 1.00 | 0.00 | 19687.48 | 18016.37 | 9423.75 | 4281.83 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.21 | 70.58 | 25.64 | 143.95 | 55.61 | 0.00 | 0.00 | 0.00 |
February | 75.62 | 46.58 | 29.04 | 106.80 | 51.38 | 0.00 | 0.00 | 0.00 |
March | 60.28 | 29.12 | 31.16 | 84.72 | 52.49 | 0.00 | 0.00 | 0.00 |
April | 50.37 | 19.21 | 31.16 | 74.49 | 45.40 | 0.00 | 0.00 | 0.00 |
May | 35.87 | 4.41 | 31.45 | 42.38 | 41.89 | 0.00 | 0.00 | 0.00 |
June | 31.46 | 1.90 | 29.56 | 37.10 | 32.61 | 0.00 | 0.00 | 0.00 |
July | 33.33 | 3.75 | 29.58 | 46.26 | 28.60 | 0.00 | 0.00 | 0.00 |
August | 42.82 | 13.51 | 29.31 | 68.97 | 29.72 | 0.00 | 0.00 | 0.00 |
September | 59.58 | 30.19 | 29.39 | 96.43 | 34.68 | 0.00 | 0.00 | 0.00 |
October | 75.77 | 50.66 | 25.12 | 123.30 | 37.43 | 0.00 | 0.00 | 0.00 |
November | 92.10 | 65.02 | 27.08 | 136.72 | 52.33 | 0.00 | 0.00 | 0.00 |
December | 102.78 | 78.23 | 24.55 | 154.50 | 55.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.96 | 34.39 | 28.58 | 92.93 | 43.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.46 | 1.90 | 24.55 | 37.10 | 28.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.78 | 78.23 | 31.45 | 154.50 | 55.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.21 | 70.58 | 25.64 | 143.95 | 55.61 | 0.00 | 0.00 | 0.00 |
February | 75.62 | 46.58 | 29.04 | 106.80 | 51.38 | 0.00 | 0.00 | 0.00 |
March | 60.28 | 29.12 | 31.16 | 84.72 | 52.49 | 0.00 | 0.00 | 0.00 |
April | 50.37 | 19.21 | 31.16 | 74.49 | 45.40 | 0.00 | 0.00 | 0.00 |
May | 35.87 | 4.41 | 31.45 | 42.38 | 41.89 | 0.00 | 0.00 | 0.00 |
June | 31.46 | 1.90 | 29.56 | 37.10 | 32.61 | 0.00 | 0.00 | 0.00 |
July | 33.33 | 3.75 | 29.58 | 46.26 | 28.60 | 0.00 | 0.00 | 0.00 |
August | 42.82 | 13.51 | 29.31 | 68.97 | 29.72 | 0.00 | 0.00 | 0.00 |
September | 59.58 | 30.19 | 29.39 | 96.43 | 34.68 | 0.00 | 0.00 | 0.00 |
October | 75.77 | 50.66 | 25.12 | 123.30 | 37.43 | 0.00 | 0.00 | 0.00 |
November | 92.10 | 65.02 | 27.08 | 136.72 | 52.33 | 0.00 | 0.00 | 0.00 |
December | 102.78 | 78.23 | 24.55 | 154.50 | 55.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.96 | 34.39 | 28.58 | 92.93 | 43.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.46 | 1.90 | 24.55 | 37.10 | 28.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.78 | 78.23 | 31.45 | 154.50 | 55.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.21 | 70.58 | 25.64 | 143.95 | 55.61 | 0.00 | 0.00 | 0.00 |
February | 75.62 | 46.58 | 29.04 | 106.80 | 51.38 | 0.00 | 0.00 | 0.00 |
March | 60.28 | 29.12 | 31.16 | 84.72 | 52.49 | 0.00 | 0.00 | 0.00 |
April | 50.37 | 19.21 | 31.16 | 74.49 | 45.40 | 0.00 | 0.00 | 0.00 |
May | 35.87 | 4.41 | 31.45 | 42.38 | 41.89 | 0.00 | 0.00 | 0.00 |
June | 31.46 | 1.90 | 29.56 | 37.10 | 32.61 | 0.00 | 0.00 | 0.00 |
July | 33.33 | 3.75 | 29.58 | 46.26 | 28.60 | 0.00 | 0.00 | 0.00 |
August | 42.82 | 13.51 | 29.31 | 68.97 | 29.72 | 0.00 | 0.00 | 0.00 |
September | 59.58 | 30.19 | 29.39 | 96.43 | 34.68 | 0.00 | 0.00 | 0.00 |
October | 75.77 | 50.66 | 25.12 | 123.30 | 37.43 | 0.00 | 0.00 | 0.00 |
November | 92.10 | 65.02 | 27.08 | 136.72 | 52.33 | 0.00 | 0.00 | 0.00 |
December | 102.78 | 78.23 | 24.55 | 154.50 | 55.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.96 | 34.39 | 28.58 | 92.93 | 43.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.46 | 1.90 | 24.55 | 37.10 | 28.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.78 | 78.23 | 31.45 | 154.50 | 55.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.21 | 70.58 | 25.64 | 143.95 | 55.61 | 0.00 | 0.00 | 0.00 |
February | 75.62 | 46.58 | 29.04 | 106.80 | 51.38 | 0.00 | 0.00 | 0.00 |
March | 60.28 | 29.12 | 31.16 | 84.72 | 52.49 | 0.00 | 0.00 | 0.00 |
April | 50.37 | 19.21 | 31.16 | 74.49 | 45.40 | 0.00 | 0.00 | 0.00 |
May | 35.87 | 4.41 | 31.45 | 42.38 | 41.89 | 0.00 | 0.00 | 0.00 |
June | 31.46 | 1.90 | 29.56 | 37.10 | 32.61 | 0.00 | 0.00 | 0.00 |
July | 33.33 | 3.75 | 29.58 | 46.26 | 28.60 | 0.00 | 0.00 | 0.00 |
August | 42.82 | 13.51 | 29.31 | 68.97 | 29.72 | 0.00 | 0.00 | 0.00 |
September | 59.58 | 30.19 | 29.39 | 96.43 | 34.68 | 0.00 | 0.00 | 0.00 |
October | 75.77 | 50.66 | 25.12 | 123.30 | 37.43 | 0.00 | 0.00 | 0.00 |
November | 92.10 | 65.02 | 27.08 | 136.72 | 52.33 | 0.00 | 0.00 | 0.00 |
December | 102.78 | 78.23 | 24.55 | 154.50 | 55.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.96 | 34.39 | 28.58 | 92.93 | 43.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.46 | 1.90 | 24.55 | 37.10 | 28.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.78 | 78.23 | 31.45 | 154.50 | 55.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 115.66 | 84.84 | 30.82 | 173.10 | 66.21 | 0.00 | 0.00 | 0.00 |
February | 90.90 | 55.99 | 34.91 | 128.71 | 61.09 | 0.00 | 0.00 | 0.00 |
March | 72.47 | 35.01 | 37.46 | 102.11 | 62.35 | 0.00 | 0.00 | 0.00 |
April | 60.55 | 23.09 | 37.46 | 89.70 | 54.04 | 0.00 | 0.00 | 0.00 |
May | 43.12 | 5.31 | 37.81 | 51.19 | 49.79 | 0.00 | 0.00 | 0.00 |
June | 37.83 | 2.28 | 35.54 | 44.73 | 38.84 | 0.00 | 0.00 | 0.00 |
July | 40.07 | 4.51 | 35.56 | 55.61 | 34.12 | 0.00 | 0.00 | 0.00 |
August | 51.47 | 16.24 | 35.24 | 82.89 | 35.43 | 0.00 | 0.00 | 0.00 |
September | 71.63 | 36.30 | 35.33 | 115.93 | 41.37 | 0.00 | 0.00 | 0.00 |
October | 91.09 | 60.90 | 30.19 | 148.21 | 44.62 | 0.00 | 0.00 | 0.00 |
November | 110.71 | 78.16 | 32.55 | 164.53 | 62.30 | 0.00 | 0.00 | 0.00 |
December | 123.56 | 94.05 | 29.52 | 185.83 | 66.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 75.69 | 41.34 | 34.35 | 111.83 | 51.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 37.83 | 2.28 | 29.52 | 44.73 | 34.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 123.56 | 94.05 | 37.81 | 185.83 | 66.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 115.66 | 84.84 | 30.82 | 173.10 | 66.21 | 0.00 | 0.00 | 0.00 |
February | 90.90 | 55.99 | 34.91 | 128.71 | 61.09 | 0.00 | 0.00 | 0.00 |
March | 72.47 | 35.01 | 37.46 | 102.11 | 62.35 | 0.00 | 0.00 | 0.00 |
April | 60.55 | 23.09 | 37.46 | 89.70 | 54.04 | 0.00 | 0.00 | 0.00 |
May | 43.12 | 5.31 | 37.81 | 51.19 | 49.79 | 0.00 | 0.00 | 0.00 |
June | 37.83 | 2.28 | 35.54 | 44.73 | 38.84 | 0.00 | 0.00 | 0.00 |
July | 40.07 | 4.51 | 35.56 | 55.61 | 34.12 | 0.00 | 0.00 | 0.00 |
August | 51.47 | 16.24 | 35.24 | 82.89 | 35.43 | 0.00 | 0.00 | 0.00 |
September | 71.63 | 36.30 | 35.33 | 115.93 | 41.37 | 0.00 | 0.00 | 0.00 |
October | 91.09 | 60.90 | 30.19 | 148.21 | 44.62 | 0.00 | 0.00 | 0.00 |
November | 110.71 | 78.16 | 32.55 | 164.53 | 62.30 | 0.00 | 0.00 | 0.00 |
December | 123.56 | 94.05 | 29.52 | 185.83 | 66.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 75.69 | 41.34 | 34.35 | 111.83 | 51.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 37.83 | 2.28 | 29.52 | 44.73 | 34.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 123.56 | 94.05 | 37.81 | 185.83 | 66.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.21 | 70.58 | 25.64 | 142.05 | 59.13 | 0.00 | 0.00 | 0.00 |
February | 75.62 | 46.58 | 29.04 | 104.69 | 55.22 | 0.00 | 0.00 | 0.00 |
March | 60.28 | 29.12 | 31.16 | 82.43 | 56.89 | 0.00 | 0.00 | 0.00 |
April | 50.37 | 19.21 | 31.16 | 73.44 | 47.19 | 0.00 | 0.00 | 0.00 |
May | 35.87 | 4.41 | 31.45 | 41.46 | 43.40 | 0.00 | 0.00 | 0.00 |
June | 31.46 | 1.90 | 29.56 | 36.57 | 33.37 | 0.00 | 0.00 | 0.00 |
July | 33.33 | 3.75 | 29.58 | 45.99 | 28.92 | 0.00 | 0.00 | 0.00 |
August | 42.82 | 13.51 | 29.31 | 68.65 | 30.15 | 0.00 | 0.00 | 0.00 |
September | 59.58 | 30.19 | 29.39 | 95.97 | 35.26 | 0.00 | 0.00 | 0.00 |
October | 75.77 | 50.66 | 25.12 | 122.73 | 38.08 | 0.00 | 0.00 | 0.00 |
November | 92.10 | 65.02 | 27.08 | 135.47 | 54.24 | 0.00 | 0.00 | 0.00 |
December | 102.78 | 78.23 | 24.55 | 152.64 | 59.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.96 | 34.39 | 28.58 | 91.81 | 45.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.46 | 1.90 | 24.55 | 36.57 | 28.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.78 | 78.23 | 31.45 | 152.64 | 59.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.21 | 70.58 | 25.64 | 142.05 | 59.13 | 0.00 | 0.00 | 0.00 |
February | 75.62 | 46.58 | 29.04 | 104.69 | 55.22 | 0.00 | 0.00 | 0.00 |
March | 60.28 | 29.12 | 31.16 | 82.43 | 56.89 | 0.00 | 0.00 | 0.00 |
April | 50.37 | 19.21 | 31.16 | 73.44 | 47.19 | 0.00 | 0.00 | 0.00 |
May | 35.87 | 4.41 | 31.45 | 41.46 | 43.40 | 0.00 | 0.00 | 0.00 |
June | 31.46 | 1.90 | 29.56 | 36.57 | 33.37 | 0.00 | 0.00 | 0.00 |
July | 33.33 | 3.75 | 29.58 | 45.99 | 28.92 | 0.00 | 0.00 | 0.00 |
August | 42.82 | 13.51 | 29.31 | 68.65 | 30.15 | 0.00 | 0.00 | 0.00 |
September | 59.58 | 30.19 | 29.39 | 95.97 | 35.26 | 0.00 | 0.00 | 0.00 |
October | 75.77 | 50.66 | 25.12 | 122.73 | 38.08 | 0.00 | 0.00 | 0.00 |
November | 92.10 | 65.02 | 27.08 | 135.47 | 54.24 | 0.00 | 0.00 | 0.00 |
December | 102.78 | 78.23 | 24.55 | 152.64 | 59.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.96 | 34.39 | 28.58 | 91.81 | 45.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.46 | 1.90 | 24.55 | 36.57 | 28.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.78 | 78.23 | 31.45 | 152.64 | 59.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 115.66 | 84.84 | 30.82 | 170.88 | 70.33 | 0.00 | 0.00 | 0.00 |
February | 90.90 | 55.99 | 34.91 | 126.26 | 65.59 | 0.00 | 0.00 | 0.00 |
March | 72.47 | 35.01 | 37.46 | 99.42 | 67.51 | 0.00 | 0.00 | 0.00 |
April | 60.55 | 23.09 | 37.46 | 88.48 | 56.15 | 0.00 | 0.00 | 0.00 |
May | 43.12 | 5.31 | 37.81 | 50.13 | 51.56 | 0.00 | 0.00 | 0.00 |
June | 37.83 | 2.28 | 35.54 | 44.11 | 39.73 | 0.00 | 0.00 | 0.00 |
July | 40.07 | 4.51 | 35.56 | 55.30 | 34.50 | 0.00 | 0.00 | 0.00 |
August | 51.47 | 16.24 | 35.24 | 82.52 | 35.92 | 0.00 | 0.00 | 0.00 |
September | 71.63 | 36.30 | 35.33 | 115.42 | 42.04 | 0.00 | 0.00 | 0.00 |
October | 91.09 | 60.90 | 30.19 | 147.57 | 45.38 | 0.00 | 0.00 | 0.00 |
November | 110.71 | 78.16 | 32.55 | 163.08 | 64.54 | 0.00 | 0.00 | 0.00 |
December | 123.56 | 94.05 | 29.52 | 183.66 | 70.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 75.69 | 41.34 | 34.35 | 110.53 | 53.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 37.83 | 2.28 | 29.52 | 44.11 | 34.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 123.56 | 94.05 | 37.81 | 183.66 | 70.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.21 | 70.58 | 25.64 | 142.43 | 58.49 | 0.00 | 0.00 | 0.00 |
February | 75.62 | 46.58 | 29.04 | 104.95 | 54.67 | 0.00 | 0.00 | 0.00 |
March | 60.28 | 29.12 | 31.16 | 82.71 | 56.16 | 0.00 | 0.00 | 0.00 |
April | 50.37 | 19.21 | 31.16 | 73.61 | 47.24 | 0.00 | 0.00 | 0.00 |
May | 35.87 | 4.41 | 31.45 | 41.59 | 43.58 | 0.00 | 0.00 | 0.00 |
June | 31.46 | 1.90 | 29.56 | 36.64 | 33.97 | 0.00 | 0.00 | 0.00 |
July | 33.33 | 3.75 | 29.58 | 45.97 | 30.02 | 0.00 | 0.00 | 0.00 |
August | 42.82 | 13.51 | 29.31 | 68.68 | 31.22 | 0.00 | 0.00 | 0.00 |
September | 59.58 | 30.19 | 29.39 | 96.04 | 36.16 | 0.00 | 0.00 | 0.00 |
October | 75.77 | 50.66 | 25.12 | 122.73 | 39.17 | 0.00 | 0.00 | 0.00 |
November | 92.10 | 65.02 | 27.08 | 135.67 | 54.27 | 0.00 | 0.00 | 0.00 |
December | 102.78 | 78.23 | 24.55 | 152.88 | 58.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.96 | 34.39 | 28.58 | 91.96 | 45.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.46 | 1.90 | 24.55 | 36.64 | 30.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.78 | 78.23 | 31.45 | 152.88 | 58.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.21 | 70.58 | 25.64 | 142.43 | 58.49 | 0.00 | 0.00 | 0.00 |
February | 75.62 | 46.58 | 29.04 | 104.95 | 54.67 | 0.00 | 0.00 | 0.00 |
March | 60.28 | 29.12 | 31.16 | 82.71 | 56.16 | 0.00 | 0.00 | 0.00 |
April | 50.37 | 19.21 | 31.16 | 73.61 | 47.24 | 0.00 | 0.00 | 0.00 |
May | 35.87 | 4.41 | 31.45 | 41.59 | 43.58 | 0.00 | 0.00 | 0.00 |
June | 31.46 | 1.90 | 29.56 | 36.64 | 33.97 | 0.00 | 0.00 | 0.00 |
July | 33.33 | 3.75 | 29.58 | 45.97 | 30.02 | 0.00 | 0.00 | 0.00 |
August | 42.82 | 13.51 | 29.31 | 68.68 | 31.22 | 0.00 | 0.00 | 0.00 |
September | 59.58 | 30.19 | 29.39 | 96.04 | 36.16 | 0.00 | 0.00 | 0.00 |
October | 75.77 | 50.66 | 25.12 | 122.73 | 39.17 | 0.00 | 0.00 | 0.00 |
November | 92.10 | 65.02 | 27.08 | 135.67 | 54.27 | 0.00 | 0.00 | 0.00 |
December | 102.78 | 78.23 | 24.55 | 152.88 | 58.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.96 | 34.39 | 28.58 | 91.96 | 45.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.46 | 1.90 | 24.55 | 36.64 | 30.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.78 | 78.23 | 31.45 | 152.88 | 58.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 115.03 | 84.38 | 30.65 | 170.40 | 69.19 | 0.00 | 0.00 | 0.00 |
February | 90.41 | 55.69 | 34.72 | 125.87 | 64.58 | 0.00 | 0.00 | 0.00 |
March | 72.07 | 34.82 | 37.26 | 99.21 | 66.28 | 0.00 | 0.00 | 0.00 |
April | 60.22 | 22.96 | 37.26 | 88.19 | 55.87 | 0.00 | 0.00 | 0.00 |
May | 42.88 | 5.28 | 37.60 | 50.01 | 51.46 | 0.00 | 0.00 | 0.00 |
June | 37.62 | 2.27 | 35.35 | 43.96 | 40.20 | 0.00 | 0.00 | 0.00 |
July | 39.85 | 4.49 | 35.36 | 54.98 | 35.58 | 0.00 | 0.00 | 0.00 |
August | 51.19 | 16.15 | 35.05 | 82.11 | 36.96 | 0.00 | 0.00 | 0.00 |
September | 71.24 | 36.10 | 35.14 | 114.87 | 42.84 | 0.00 | 0.00 | 0.00 |
October | 90.59 | 60.56 | 30.03 | 146.75 | 46.39 | 0.00 | 0.00 | 0.00 |
November | 110.11 | 77.73 | 32.37 | 162.44 | 64.21 | 0.00 | 0.00 | 0.00 |
December | 122.89 | 93.53 | 29.35 | 182.94 | 69.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 75.28 | 41.11 | 34.16 | 110.10 | 53.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 37.62 | 2.27 | 29.35 | 43.96 | 35.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.89 | 93.53 | 37.60 | 182.94 | 69.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.21 | 70.58 | 25.64 | 142.72 | 57.73 | 0.00 | 0.00 | 0.00 |
February | 75.62 | 46.58 | 29.04 | 105.20 | 53.97 | 0.00 | 0.00 | 0.00 |
March | 60.28 | 29.12 | 31.16 | 83.01 | 55.33 | 0.00 | 0.00 | 0.00 |
April | 50.37 | 19.21 | 31.16 | 73.75 | 46.77 | 0.00 | 0.00 | 0.00 |
May | 35.87 | 4.41 | 31.45 | 41.71 | 43.21 | 0.00 | 0.00 | 0.00 |
June | 31.46 | 1.90 | 29.56 | 36.72 | 33.73 | 0.00 | 0.00 | 0.00 |
July | 33.33 | 3.75 | 29.58 | 46.02 | 29.90 | 0.00 | 0.00 | 0.00 |
August | 42.82 | 13.51 | 29.31 | 68.72 | 31.09 | 0.00 | 0.00 | 0.00 |
September | 59.58 | 30.19 | 29.39 | 96.09 | 35.96 | 0.00 | 0.00 | 0.00 |
October | 75.77 | 50.66 | 25.12 | 122.77 | 39.04 | 0.00 | 0.00 | 0.00 |
November | 92.10 | 65.02 | 27.08 | 135.81 | 53.86 | 0.00 | 0.00 | 0.00 |
December | 102.78 | 78.23 | 24.55 | 153.08 | 58.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.96 | 34.39 | 28.58 | 92.10 | 44.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.46 | 1.90 | 24.55 | 36.72 | 29.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.78 | 78.23 | 31.45 | 153.08 | 58.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.21 | 70.58 | 25.64 | 142.72 | 57.73 | 0.00 | 0.00 | 0.00 |
February | 75.62 | 46.58 | 29.04 | 105.20 | 53.97 | 0.00 | 0.00 | 0.00 |
March | 60.28 | 29.12 | 31.16 | 83.01 | 55.33 | 0.00 | 0.00 | 0.00 |
April | 50.37 | 19.21 | 31.16 | 73.75 | 46.77 | 0.00 | 0.00 | 0.00 |
May | 35.87 | 4.41 | 31.45 | 41.71 | 43.21 | 0.00 | 0.00 | 0.00 |
June | 31.46 | 1.90 | 29.56 | 36.72 | 33.73 | 0.00 | 0.00 | 0.00 |
July | 33.33 | 3.75 | 29.58 | 46.02 | 29.90 | 0.00 | 0.00 | 0.00 |
August | 42.82 | 13.51 | 29.31 | 68.72 | 31.09 | 0.00 | 0.00 | 0.00 |
September | 59.58 | 30.19 | 29.39 | 96.09 | 35.96 | 0.00 | 0.00 | 0.00 |
October | 75.77 | 50.66 | 25.12 | 122.77 | 39.04 | 0.00 | 0.00 | 0.00 |
November | 92.10 | 65.02 | 27.08 | 135.81 | 53.86 | 0.00 | 0.00 | 0.00 |
December | 102.78 | 78.23 | 24.55 | 153.08 | 58.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.96 | 34.39 | 28.58 | 92.10 | 44.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.46 | 1.90 | 24.55 | 36.72 | 29.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.78 | 78.23 | 31.45 | 153.08 | 58.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 115.03 | 84.38 | 30.65 | 170.75 | 68.29 | 0.00 | 0.00 | 0.00 |
February | 90.41 | 55.69 | 34.72 | 126.17 | 63.75 | 0.00 | 0.00 | 0.00 |
March | 72.07 | 34.82 | 37.26 | 99.57 | 65.30 | 0.00 | 0.00 | 0.00 |
April | 60.22 | 22.96 | 37.26 | 88.37 | 55.32 | 0.00 | 0.00 | 0.00 |
May | 42.88 | 5.28 | 37.60 | 50.14 | 51.03 | 0.00 | 0.00 | 0.00 |
June | 37.62 | 2.27 | 35.35 | 44.05 | 39.92 | 0.00 | 0.00 | 0.00 |
July | 39.85 | 4.49 | 35.36 | 55.04 | 35.43 | 0.00 | 0.00 | 0.00 |
August | 51.19 | 16.15 | 35.05 | 82.15 | 36.81 | 0.00 | 0.00 | 0.00 |
September | 71.24 | 36.10 | 35.14 | 114.93 | 42.61 | 0.00 | 0.00 | 0.00 |
October | 90.59 | 60.56 | 30.03 | 146.80 | 46.23 | 0.00 | 0.00 | 0.00 |
November | 110.11 | 77.73 | 32.37 | 162.60 | 63.72 | 0.00 | 0.00 | 0.00 |
December | 122.89 | 93.53 | 29.35 | 183.18 | 69.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 75.28 | 41.11 | 34.16 | 110.27 | 53.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 37.62 | 2.27 | 29.35 | 44.05 | 35.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.89 | 93.53 | 37.60 | 183.18 | 69.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.21 | 70.58 | 25.64 | 143.12 | 56.88 | 0.00 | 0.00 | 0.00 |
February | 75.62 | 46.58 | 29.04 | 105.63 | 53.00 | 0.00 | 0.00 | 0.00 |
March | 60.28 | 29.12 | 31.16 | 83.54 | 54.21 | 0.00 | 0.00 | 0.00 |
April | 50.37 | 19.21 | 31.16 | 73.99 | 46.18 | 0.00 | 0.00 | 0.00 |
May | 35.87 | 4.41 | 31.45 | 41.92 | 42.73 | 0.00 | 0.00 | 0.00 |
June | 31.46 | 1.90 | 29.56 | 36.87 | 33.38 | 0.00 | 0.00 | 0.00 |
July | 33.33 | 3.75 | 29.58 | 46.14 | 29.60 | 0.00 | 0.00 | 0.00 |
August | 42.82 | 13.51 | 29.31 | 68.82 | 30.79 | 0.00 | 0.00 | 0.00 |
September | 59.58 | 30.19 | 29.39 | 96.20 | 35.62 | 0.00 | 0.00 | 0.00 |
October | 75.77 | 50.66 | 25.12 | 122.88 | 38.71 | 0.00 | 0.00 | 0.00 |
November | 92.10 | 65.02 | 27.08 | 136.04 | 53.34 | 0.00 | 0.00 | 0.00 |
December | 102.78 | 78.23 | 24.55 | 153.42 | 57.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.96 | 34.39 | 28.58 | 92.34 | 44.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.46 | 1.90 | 24.55 | 36.87 | 29.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.78 | 78.23 | 31.45 | 153.42 | 57.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.21 | 70.58 | 25.64 | 143.12 | 56.88 | 0.00 | 0.00 | 0.00 |
February | 75.62 | 46.58 | 29.04 | 105.63 | 53.00 | 0.00 | 0.00 | 0.00 |
March | 60.28 | 29.12 | 31.16 | 83.54 | 54.21 | 0.00 | 0.00 | 0.00 |
April | 50.37 | 19.21 | 31.16 | 73.99 | 46.18 | 0.00 | 0.00 | 0.00 |
May | 35.87 | 4.41 | 31.45 | 41.92 | 42.73 | 0.00 | 0.00 | 0.00 |
June | 31.46 | 1.90 | 29.56 | 36.87 | 33.38 | 0.00 | 0.00 | 0.00 |
July | 33.33 | 3.75 | 29.58 | 46.14 | 29.60 | 0.00 | 0.00 | 0.00 |
August | 42.82 | 13.51 | 29.31 | 68.82 | 30.79 | 0.00 | 0.00 | 0.00 |
September | 59.58 | 30.19 | 29.39 | 96.20 | 35.62 | 0.00 | 0.00 | 0.00 |
October | 75.77 | 50.66 | 25.12 | 122.88 | 38.71 | 0.00 | 0.00 | 0.00 |
November | 92.10 | 65.02 | 27.08 | 136.04 | 53.34 | 0.00 | 0.00 | 0.00 |
December | 102.78 | 78.23 | 24.55 | 153.42 | 57.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.96 | 34.39 | 28.58 | 92.34 | 44.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.46 | 1.90 | 24.55 | 36.87 | 29.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.78 | 78.23 | 31.45 | 153.42 | 57.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 115.03 | 84.38 | 30.65 | 171.21 | 67.29 | 0.00 | 0.00 | 0.00 |
February | 90.41 | 55.69 | 34.72 | 126.69 | 62.61 | 0.00 | 0.00 | 0.00 |
March | 72.07 | 34.82 | 37.26 | 100.20 | 63.99 | 0.00 | 0.00 | 0.00 |
April | 60.22 | 22.96 | 37.26 | 88.65 | 54.62 | 0.00 | 0.00 | 0.00 |
May | 42.88 | 5.28 | 37.60 | 50.39 | 50.47 | 0.00 | 0.00 | 0.00 |
June | 37.62 | 2.27 | 35.35 | 44.23 | 39.50 | 0.00 | 0.00 | 0.00 |
July | 39.85 | 4.49 | 35.36 | 55.18 | 35.07 | 0.00 | 0.00 | 0.00 |
August | 51.19 | 16.15 | 35.05 | 82.28 | 36.46 | 0.00 | 0.00 | 0.00 |
September | 71.24 | 36.10 | 35.14 | 115.07 | 42.21 | 0.00 | 0.00 | 0.00 |
October | 90.59 | 60.56 | 30.03 | 146.94 | 45.85 | 0.00 | 0.00 | 0.00 |
November | 110.11 | 77.73 | 32.37 | 162.87 | 63.10 | 0.00 | 0.00 | 0.00 |
December | 122.89 | 93.53 | 29.35 | 183.58 | 68.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 75.28 | 41.11 | 34.16 | 110.56 | 52.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 37.62 | 2.27 | 29.35 | 44.23 | 35.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.89 | 93.53 | 37.60 | 183.58 | 68.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.21 | 70.58 | 25.64 | 144.26 | 54.90 | 0.00 | 0.00 | 0.00 |
February | 75.62 | 46.58 | 29.04 | 107.07 | 50.61 | 0.00 | 0.00 | 0.00 |
March | 60.28 | 29.12 | 31.16 | 85.05 | 51.66 | 0.00 | 0.00 | 0.00 |
April | 50.37 | 19.21 | 31.16 | 74.78 | 44.70 | 0.00 | 0.00 | 0.00 |
May | 35.87 | 4.41 | 31.45 | 42.65 | 41.46 | 0.00 | 0.00 | 0.00 |
June | 31.46 | 1.90 | 29.56 | 37.30 | 32.50 | 0.00 | 0.00 | 0.00 |
July | 33.33 | 3.75 | 29.58 | 46.36 | 28.82 | 0.00 | 0.00 | 0.00 |
August | 42.82 | 13.51 | 29.31 | 69.05 | 29.97 | 0.00 | 0.00 | 0.00 |
September | 59.58 | 30.19 | 29.39 | 96.57 | 34.77 | 0.00 | 0.00 | 0.00 |
October | 75.77 | 50.66 | 25.12 | 123.27 | 37.85 | 0.00 | 0.00 | 0.00 |
November | 92.10 | 65.02 | 27.08 | 136.89 | 51.88 | 0.00 | 0.00 | 0.00 |
December | 102.78 | 78.23 | 24.55 | 154.55 | 55.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.96 | 34.39 | 28.58 | 93.11 | 42.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.46 | 1.90 | 24.55 | 37.30 | 28.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.78 | 78.23 | 31.45 | 154.55 | 55.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.21 | 70.58 | 25.64 | 144.26 | 54.90 | 0.00 | 0.00 | 0.00 |
February | 75.62 | 46.58 | 29.04 | 107.07 | 50.61 | 0.00 | 0.00 | 0.00 |
March | 60.28 | 29.12 | 31.16 | 85.05 | 51.66 | 0.00 | 0.00 | 0.00 |
April | 50.37 | 19.21 | 31.16 | 74.78 | 44.70 | 0.00 | 0.00 | 0.00 |
May | 35.87 | 4.41 | 31.45 | 42.65 | 41.46 | 0.00 | 0.00 | 0.00 |
June | 31.46 | 1.90 | 29.56 | 37.30 | 32.50 | 0.00 | 0.00 | 0.00 |
July | 33.33 | 3.75 | 29.58 | 46.36 | 28.82 | 0.00 | 0.00 | 0.00 |
August | 42.82 | 13.51 | 29.31 | 69.05 | 29.97 | 0.00 | 0.00 | 0.00 |
September | 59.58 | 30.19 | 29.39 | 96.57 | 34.77 | 0.00 | 0.00 | 0.00 |
October | 75.77 | 50.66 | 25.12 | 123.27 | 37.85 | 0.00 | 0.00 | 0.00 |
November | 92.10 | 65.02 | 27.08 | 136.89 | 51.88 | 0.00 | 0.00 | 0.00 |
December | 102.78 | 78.23 | 24.55 | 154.55 | 55.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.96 | 34.39 | 28.58 | 93.11 | 42.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.46 | 1.90 | 24.55 | 37.30 | 28.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.78 | 78.23 | 31.45 | 154.55 | 55.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.21 | 70.58 | 25.64 | 144.26 | 54.90 | 0.00 | 0.00 | 0.00 |
February | 75.62 | 46.58 | 29.04 | 107.07 | 50.61 | 0.00 | 0.00 | 0.00 |
March | 60.28 | 29.12 | 31.16 | 85.05 | 51.66 | 0.00 | 0.00 | 0.00 |
April | 50.37 | 19.21 | 31.16 | 74.78 | 44.70 | 0.00 | 0.00 | 0.00 |
May | 35.87 | 4.41 | 31.45 | 42.65 | 41.46 | 0.00 | 0.00 | 0.00 |
June | 31.46 | 1.90 | 29.56 | 37.30 | 32.50 | 0.00 | 0.00 | 0.00 |
July | 33.33 | 3.75 | 29.58 | 46.36 | 28.82 | 0.00 | 0.00 | 0.00 |
August | 42.82 | 13.51 | 29.31 | 69.05 | 29.97 | 0.00 | 0.00 | 0.00 |
September | 59.58 | 30.19 | 29.39 | 96.57 | 34.77 | 0.00 | 0.00 | 0.00 |
October | 75.77 | 50.66 | 25.12 | 123.27 | 37.85 | 0.00 | 0.00 | 0.00 |
November | 92.10 | 65.02 | 27.08 | 136.89 | 51.88 | 0.00 | 0.00 | 0.00 |
December | 102.78 | 78.23 | 24.55 | 154.55 | 55.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.96 | 34.39 | 28.58 | 93.11 | 42.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.46 | 1.90 | 24.55 | 37.30 | 28.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.78 | 78.23 | 31.45 | 154.55 | 55.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.21 | 70.58 | 25.64 | 144.26 | 54.90 | 0.00 | 0.00 | 0.00 |
February | 75.62 | 46.58 | 29.04 | 107.07 | 50.61 | 0.00 | 0.00 | 0.00 |
March | 60.28 | 29.12 | 31.16 | 85.05 | 51.66 | 0.00 | 0.00 | 0.00 |
April | 50.37 | 19.21 | 31.16 | 74.78 | 44.70 | 0.00 | 0.00 | 0.00 |
May | 35.87 | 4.41 | 31.45 | 42.65 | 41.46 | 0.00 | 0.00 | 0.00 |
June | 31.46 | 1.90 | 29.56 | 37.30 | 32.50 | 0.00 | 0.00 | 0.00 |
July | 33.33 | 3.75 | 29.58 | 46.36 | 28.82 | 0.00 | 0.00 | 0.00 |
August | 42.82 | 13.51 | 29.31 | 69.05 | 29.97 | 0.00 | 0.00 | 0.00 |
September | 59.58 | 30.19 | 29.39 | 96.57 | 34.77 | 0.00 | 0.00 | 0.00 |
October | 75.77 | 50.66 | 25.12 | 123.27 | 37.85 | 0.00 | 0.00 | 0.00 |
November | 92.10 | 65.02 | 27.08 | 136.89 | 51.88 | 0.00 | 0.00 | 0.00 |
December | 102.78 | 78.23 | 24.55 | 154.55 | 55.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.96 | 34.39 | 28.58 | 93.11 | 42.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.46 | 1.90 | 24.55 | 37.30 | 28.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.78 | 78.23 | 31.45 | 154.55 | 55.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 115.03 | 84.38 | 30.65 | 172.53 | 64.99 | 0.00 | 0.00 | 0.00 |
February | 90.41 | 55.69 | 34.72 | 128.34 | 59.83 | 0.00 | 0.00 | 0.00 |
March | 72.07 | 34.82 | 37.26 | 101.96 | 61.02 | 0.00 | 0.00 | 0.00 |
April | 60.22 | 22.96 | 37.26 | 89.56 | 52.90 | 0.00 | 0.00 | 0.00 |
May | 42.88 | 5.28 | 37.60 | 51.24 | 48.99 | 0.00 | 0.00 | 0.00 |
June | 37.62 | 2.27 | 35.35 | 44.73 | 38.48 | 0.00 | 0.00 | 0.00 |
July | 39.85 | 4.49 | 35.36 | 55.44 | 34.17 | 0.00 | 0.00 | 0.00 |
August | 51.19 | 16.15 | 35.05 | 82.54 | 35.50 | 0.00 | 0.00 | 0.00 |
September | 71.24 | 36.10 | 35.14 | 115.48 | 41.21 | 0.00 | 0.00 | 0.00 |
October | 90.59 | 60.56 | 30.03 | 147.37 | 44.85 | 0.00 | 0.00 | 0.00 |
November | 110.11 | 77.73 | 32.37 | 163.84 | 61.41 | 0.00 | 0.00 | 0.00 |
December | 122.89 | 93.53 | 29.35 | 184.88 | 66.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 75.28 | 41.11 | 34.16 | 111.44 | 50.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 37.62 | 2.27 | 29.35 | 44.73 | 34.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.89 | 93.53 | 37.60 | 184.88 | 66.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 115.03 | 84.38 | 30.65 | 172.53 | 64.99 | 0.00 | 0.00 | 0.00 |
February | 90.41 | 55.69 | 34.72 | 128.34 | 59.83 | 0.00 | 0.00 | 0.00 |
March | 72.07 | 34.82 | 37.26 | 101.96 | 61.02 | 0.00 | 0.00 | 0.00 |
April | 60.22 | 22.96 | 37.26 | 89.56 | 52.90 | 0.00 | 0.00 | 0.00 |
May | 42.88 | 5.28 | 37.60 | 51.24 | 48.99 | 0.00 | 0.00 | 0.00 |
June | 37.62 | 2.27 | 35.35 | 44.73 | 38.48 | 0.00 | 0.00 | 0.00 |
July | 39.85 | 4.49 | 35.36 | 55.44 | 34.17 | 0.00 | 0.00 | 0.00 |
August | 51.19 | 16.15 | 35.05 | 82.54 | 35.50 | 0.00 | 0.00 | 0.00 |
September | 71.24 | 36.10 | 35.14 | 115.48 | 41.21 | 0.00 | 0.00 | 0.00 |
October | 90.59 | 60.56 | 30.03 | 147.37 | 44.85 | 0.00 | 0.00 | 0.00 |
November | 110.11 | 77.73 | 32.37 | 163.84 | 61.41 | 0.00 | 0.00 | 0.00 |
December | 122.89 | 93.53 | 29.35 | 184.88 | 66.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 75.28 | 41.11 | 34.16 | 111.44 | 50.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 37.62 | 2.27 | 29.35 | 44.73 | 34.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.89 | 93.53 | 37.60 | 184.88 | 66.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.21 | 70.58 | 25.64 | 143.60 | 55.59 | 0.00 | 0.00 | 0.00 |
February | 75.62 | 46.58 | 29.04 | 106.20 | 51.56 | 0.00 | 0.00 | 0.00 |
March | 60.28 | 29.12 | 31.16 | 84.22 | 52.58 | 0.00 | 0.00 | 0.00 |
April | 50.37 | 19.21 | 31.16 | 74.33 | 45.11 | 0.00 | 0.00 | 0.00 |
May | 35.87 | 4.41 | 31.45 | 42.26 | 41.79 | 0.00 | 0.00 | 0.00 |
June | 31.46 | 1.90 | 29.56 | 37.13 | 32.53 | 0.00 | 0.00 | 0.00 |
July | 33.33 | 3.75 | 29.58 | 46.29 | 28.73 | 0.00 | 0.00 | 0.00 |
August | 42.82 | 13.51 | 29.31 | 68.93 | 29.88 | 0.00 | 0.00 | 0.00 |
September | 59.58 | 30.19 | 29.39 | 96.34 | 34.74 | 0.00 | 0.00 | 0.00 |
October | 75.77 | 50.66 | 25.12 | 123.01 | 37.84 | 0.00 | 0.00 | 0.00 |
November | 92.10 | 65.02 | 27.08 | 136.31 | 52.44 | 0.00 | 0.00 | 0.00 |
December | 102.78 | 78.23 | 24.55 | 153.85 | 56.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.96 | 34.39 | 28.58 | 92.67 | 43.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.46 | 1.90 | 24.55 | 37.13 | 28.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.78 | 78.23 | 31.45 | 153.85 | 56.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.21 | 70.58 | 25.64 | 143.60 | 55.59 | 0.00 | 0.00 | 0.00 |
February | 75.62 | 46.58 | 29.04 | 106.20 | 51.56 | 0.00 | 0.00 | 0.00 |
March | 60.28 | 29.12 | 31.16 | 84.22 | 52.58 | 0.00 | 0.00 | 0.00 |
April | 50.37 | 19.21 | 31.16 | 74.33 | 45.11 | 0.00 | 0.00 | 0.00 |
May | 35.87 | 4.41 | 31.45 | 42.26 | 41.79 | 0.00 | 0.00 | 0.00 |
June | 31.46 | 1.90 | 29.56 | 37.13 | 32.53 | 0.00 | 0.00 | 0.00 |
July | 33.33 | 3.75 | 29.58 | 46.29 | 28.73 | 0.00 | 0.00 | 0.00 |
August | 42.82 | 13.51 | 29.31 | 68.93 | 29.88 | 0.00 | 0.00 | 0.00 |
September | 59.58 | 30.19 | 29.39 | 96.34 | 34.74 | 0.00 | 0.00 | 0.00 |
October | 75.77 | 50.66 | 25.12 | 123.01 | 37.84 | 0.00 | 0.00 | 0.00 |
November | 92.10 | 65.02 | 27.08 | 136.31 | 52.44 | 0.00 | 0.00 | 0.00 |
December | 102.78 | 78.23 | 24.55 | 153.85 | 56.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.96 | 34.39 | 28.58 | 92.67 | 43.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.46 | 1.90 | 24.55 | 37.13 | 28.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.78 | 78.23 | 31.45 | 153.85 | 56.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 115.03 | 84.38 | 30.65 | 171.79 | 65.77 | 0.00 | 0.00 | 0.00 |
February | 90.41 | 55.69 | 34.72 | 127.37 | 60.92 | 0.00 | 0.00 | 0.00 |
March | 72.07 | 34.82 | 37.26 | 101.02 | 62.07 | 0.00 | 0.00 | 0.00 |
April | 60.22 | 22.96 | 37.26 | 89.06 | 53.36 | 0.00 | 0.00 | 0.00 |
May | 42.88 | 5.28 | 37.60 | 50.82 | 49.35 | 0.00 | 0.00 | 0.00 |
June | 37.62 | 2.27 | 35.35 | 44.55 | 38.50 | 0.00 | 0.00 | 0.00 |
July | 39.85 | 4.49 | 35.36 | 55.37 | 34.06 | 0.00 | 0.00 | 0.00 |
August | 51.19 | 16.15 | 35.05 | 82.43 | 35.39 | 0.00 | 0.00 | 0.00 |
September | 71.24 | 36.10 | 35.14 | 115.24 | 41.17 | 0.00 | 0.00 | 0.00 |
October | 90.59 | 60.56 | 30.03 | 147.10 | 44.82 | 0.00 | 0.00 | 0.00 |
November | 110.11 | 77.73 | 32.37 | 163.21 | 62.04 | 0.00 | 0.00 | 0.00 |
December | 122.89 | 93.53 | 29.35 | 184.11 | 66.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 75.28 | 41.11 | 34.16 | 110.96 | 51.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 37.62 | 2.27 | 29.35 | 44.55 | 34.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.89 | 93.53 | 37.60 | 184.11 | 66.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.21 | 70.58 | 25.64 | 143.69 | 55.44 | 0.00 | 0.00 | 0.00 |
February | 75.62 | 46.58 | 29.04 | 106.31 | 51.39 | 0.00 | 0.00 | 0.00 |
March | 60.28 | 29.12 | 31.16 | 84.32 | 52.41 | 0.00 | 0.00 | 0.00 |
April | 50.37 | 19.21 | 31.16 | 74.40 | 44.98 | 0.00 | 0.00 | 0.00 |
May | 35.87 | 4.41 | 31.45 | 42.34 | 41.66 | 0.00 | 0.00 | 0.00 |
June | 31.46 | 1.90 | 29.56 | 37.21 | 32.41 | 0.00 | 0.00 | 0.00 |
July | 33.33 | 3.75 | 29.58 | 46.35 | 28.62 | 0.00 | 0.00 | 0.00 |
August | 42.82 | 13.51 | 29.31 | 68.99 | 29.77 | 0.00 | 0.00 | 0.00 |
September | 59.58 | 30.19 | 29.39 | 96.40 | 34.61 | 0.00 | 0.00 | 0.00 |
October | 75.77 | 50.66 | 25.12 | 123.07 | 37.71 | 0.00 | 0.00 | 0.00 |
November | 92.10 | 65.02 | 27.08 | 136.39 | 52.32 | 0.00 | 0.00 | 0.00 |
December | 102.78 | 78.23 | 24.55 | 153.94 | 56.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.96 | 34.39 | 28.58 | 92.75 | 43.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.46 | 1.90 | 24.55 | 37.21 | 28.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.78 | 78.23 | 31.45 | 153.94 | 56.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.21 | 70.58 | 25.64 | 143.69 | 55.44 | 0.00 | 0.00 | 0.00 |
February | 75.62 | 46.58 | 29.04 | 106.31 | 51.39 | 0.00 | 0.00 | 0.00 |
March | 60.28 | 29.12 | 31.16 | 84.32 | 52.41 | 0.00 | 0.00 | 0.00 |
April | 50.37 | 19.21 | 31.16 | 74.40 | 44.98 | 0.00 | 0.00 | 0.00 |
May | 35.87 | 4.41 | 31.45 | 42.34 | 41.66 | 0.00 | 0.00 | 0.00 |
June | 31.46 | 1.90 | 29.56 | 37.21 | 32.41 | 0.00 | 0.00 | 0.00 |
July | 33.33 | 3.75 | 29.58 | 46.35 | 28.62 | 0.00 | 0.00 | 0.00 |
August | 42.82 | 13.51 | 29.31 | 68.99 | 29.77 | 0.00 | 0.00 | 0.00 |
September | 59.58 | 30.19 | 29.39 | 96.40 | 34.61 | 0.00 | 0.00 | 0.00 |
October | 75.77 | 50.66 | 25.12 | 123.07 | 37.71 | 0.00 | 0.00 | 0.00 |
November | 92.10 | 65.02 | 27.08 | 136.39 | 52.32 | 0.00 | 0.00 | 0.00 |
December | 102.78 | 78.23 | 24.55 | 153.94 | 56.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.96 | 34.39 | 28.58 | 92.75 | 43.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.46 | 1.90 | 24.55 | 37.21 | 28.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.78 | 78.23 | 31.45 | 153.94 | 56.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 115.03 | 84.38 | 30.65 | 171.91 | 65.59 | 0.00 | 0.00 | 0.00 |
February | 90.41 | 55.69 | 34.72 | 127.50 | 60.71 | 0.00 | 0.00 | 0.00 |
March | 72.07 | 34.82 | 37.26 | 101.13 | 61.87 | 0.00 | 0.00 | 0.00 |
April | 60.22 | 22.96 | 37.26 | 89.15 | 53.20 | 0.00 | 0.00 | 0.00 |
May | 42.88 | 5.28 | 37.60 | 50.91 | 49.20 | 0.00 | 0.00 | 0.00 |
June | 37.62 | 2.27 | 35.35 | 44.64 | 38.35 | 0.00 | 0.00 | 0.00 |
July | 39.85 | 4.49 | 35.36 | 55.45 | 33.93 | 0.00 | 0.00 | 0.00 |
August | 51.19 | 16.15 | 35.05 | 82.50 | 35.26 | 0.00 | 0.00 | 0.00 |
September | 71.24 | 36.10 | 35.14 | 115.31 | 41.02 | 0.00 | 0.00 | 0.00 |
October | 90.59 | 60.56 | 30.03 | 147.18 | 44.67 | 0.00 | 0.00 | 0.00 |
November | 110.11 | 77.73 | 32.37 | 163.30 | 61.89 | 0.00 | 0.00 | 0.00 |
December | 122.89 | 93.53 | 29.35 | 184.22 | 66.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 75.28 | 41.11 | 34.16 | 111.05 | 50.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 37.62 | 2.27 | 29.35 | 44.64 | 33.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.89 | 93.53 | 37.60 | 184.22 | 66.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.21 | 70.58 | 25.64 | 144.19 | 54.46 | 0.00 | 0.00 | 0.00 |
February | 75.62 | 46.58 | 29.04 | 106.96 | 50.07 | 0.00 | 0.00 | 0.00 |
March | 60.28 | 29.12 | 31.16 | 84.92 | 51.19 | 0.00 | 0.00 | 0.00 |
April | 50.37 | 19.21 | 31.16 | 74.75 | 44.17 | 0.00 | 0.00 | 0.00 |
May | 35.87 | 4.41 | 31.45 | 42.69 | 40.93 | 0.00 | 0.00 | 0.00 |
June | 31.46 | 1.90 | 29.56 | 37.47 | 31.89 | 0.00 | 0.00 | 0.00 |
July | 33.33 | 3.75 | 29.58 | 46.51 | 28.27 | 0.00 | 0.00 | 0.00 |
August | 42.82 | 13.51 | 29.31 | 69.14 | 29.42 | 0.00 | 0.00 | 0.00 |
September | 59.58 | 30.19 | 29.39 | 96.58 | 34.15 | 0.00 | 0.00 | 0.00 |
October | 75.77 | 50.66 | 25.12 | 123.26 | 37.27 | 0.00 | 0.00 | 0.00 |
November | 92.10 | 65.02 | 27.08 | 136.80 | 51.50 | 0.00 | 0.00 | 0.00 |
December | 102.78 | 78.23 | 24.55 | 154.49 | 55.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.96 | 34.39 | 28.58 | 93.11 | 42.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.46 | 1.90 | 24.55 | 37.47 | 28.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.78 | 78.23 | 31.45 | 154.49 | 55.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.21 | 70.58 | 25.64 | 144.19 | 54.46 | 0.00 | 0.00 | 0.00 |
February | 75.62 | 46.58 | 29.04 | 106.96 | 50.07 | 0.00 | 0.00 | 0.00 |
March | 60.28 | 29.12 | 31.16 | 84.92 | 51.19 | 0.00 | 0.00 | 0.00 |
April | 50.37 | 19.21 | 31.16 | 74.75 | 44.17 | 0.00 | 0.00 | 0.00 |
May | 35.87 | 4.41 | 31.45 | 42.69 | 40.93 | 0.00 | 0.00 | 0.00 |
June | 31.46 | 1.90 | 29.56 | 37.47 | 31.89 | 0.00 | 0.00 | 0.00 |
July | 33.33 | 3.75 | 29.58 | 46.51 | 28.27 | 0.00 | 0.00 | 0.00 |
August | 42.82 | 13.51 | 29.31 | 69.14 | 29.42 | 0.00 | 0.00 | 0.00 |
September | 59.58 | 30.19 | 29.39 | 96.58 | 34.15 | 0.00 | 0.00 | 0.00 |
October | 75.77 | 50.66 | 25.12 | 123.26 | 37.27 | 0.00 | 0.00 | 0.00 |
November | 92.10 | 65.02 | 27.08 | 136.80 | 51.50 | 0.00 | 0.00 | 0.00 |
December | 102.78 | 78.23 | 24.55 | 154.49 | 55.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.96 | 34.39 | 28.58 | 93.11 | 42.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.46 | 1.90 | 24.55 | 37.47 | 28.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.78 | 78.23 | 31.45 | 154.49 | 55.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 115.03 | 84.38 | 30.65 | 172.51 | 64.44 | 0.00 | 0.00 | 0.00 |
February | 90.41 | 55.69 | 34.72 | 128.27 | 59.17 | 0.00 | 0.00 | 0.00 |
March | 72.07 | 34.82 | 37.26 | 101.85 | 60.43 | 0.00 | 0.00 | 0.00 |
April | 60.22 | 22.96 | 37.26 | 89.57 | 52.25 | 0.00 | 0.00 | 0.00 |
May | 42.88 | 5.28 | 37.60 | 51.33 | 48.35 | 0.00 | 0.00 | 0.00 |
June | 37.62 | 2.27 | 35.35 | 44.95 | 37.75 | 0.00 | 0.00 | 0.00 |
July | 39.85 | 4.49 | 35.36 | 55.64 | 33.52 | 0.00 | 0.00 | 0.00 |
August | 51.19 | 16.15 | 35.05 | 82.67 | 34.84 | 0.00 | 0.00 | 0.00 |
September | 71.24 | 36.10 | 35.14 | 115.52 | 40.47 | 0.00 | 0.00 | 0.00 |
October | 90.59 | 60.56 | 30.03 | 147.40 | 44.15 | 0.00 | 0.00 | 0.00 |
November | 110.11 | 77.73 | 32.37 | 163.79 | 60.93 | 0.00 | 0.00 | 0.00 |
December | 122.89 | 93.53 | 29.35 | 184.86 | 65.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 75.28 | 41.11 | 34.16 | 111.48 | 50.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 37.62 | 2.27 | 29.35 | 44.95 | 33.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.89 | 93.53 | 37.60 | 184.86 | 65.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.21 | 70.58 | 25.64 | 145.35 | 51.27 | 0.00 | 0.00 | 0.00 |
February | 75.62 | 46.58 | 29.04 | 108.46 | 46.05 | 0.00 | 0.00 | 0.00 |
March | 60.28 | 29.12 | 31.16 | 86.12 | 47.42 | 0.00 | 0.00 | 0.00 |
April | 50.37 | 19.21 | 31.16 | 75.37 | 41.29 | 0.00 | 0.00 | 0.00 |
May | 35.87 | 4.41 | 31.45 | 43.43 | 38.22 | 0.00 | 0.00 | 0.00 |
June | 31.46 | 1.90 | 29.56 | 37.98 | 29.88 | 0.00 | 0.00 | 0.00 |
July | 33.33 | 3.75 | 29.58 | 46.57 | 26.91 | 0.00 | 0.00 | 0.00 |
August | 42.82 | 13.51 | 29.31 | 69.16 | 27.98 | 0.00 | 0.00 | 0.00 |
September | 59.58 | 30.19 | 29.39 | 96.87 | 32.38 | 0.00 | 0.00 | 0.00 |
October | 75.77 | 50.66 | 25.12 | 123.66 | 35.50 | 0.00 | 0.00 | 0.00 |
November | 92.10 | 65.02 | 27.08 | 137.88 | 48.53 | 0.00 | 0.00 | 0.00 |
December | 102.78 | 78.23 | 24.55 | 155.81 | 51.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.96 | 34.39 | 28.58 | 93.85 | 39.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.46 | 1.90 | 24.55 | 37.98 | 26.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.78 | 78.23 | 31.45 | 155.81 | 51.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.21 | 70.58 | 25.64 | 145.35 | 51.27 | 0.00 | 0.00 | 0.00 |
February | 75.62 | 46.58 | 29.04 | 108.46 | 46.05 | 0.00 | 0.00 | 0.00 |
March | 60.28 | 29.12 | 31.16 | 86.12 | 47.42 | 0.00 | 0.00 | 0.00 |
April | 50.37 | 19.21 | 31.16 | 75.37 | 41.29 | 0.00 | 0.00 | 0.00 |
May | 35.87 | 4.41 | 31.45 | 43.43 | 38.22 | 0.00 | 0.00 | 0.00 |
June | 31.46 | 1.90 | 29.56 | 37.98 | 29.88 | 0.00 | 0.00 | 0.00 |
July | 33.33 | 3.75 | 29.58 | 46.57 | 26.91 | 0.00 | 0.00 | 0.00 |
August | 42.82 | 13.51 | 29.31 | 69.16 | 27.98 | 0.00 | 0.00 | 0.00 |
September | 59.58 | 30.19 | 29.39 | 96.87 | 32.38 | 0.00 | 0.00 | 0.00 |
October | 75.77 | 50.66 | 25.12 | 123.66 | 35.50 | 0.00 | 0.00 | 0.00 |
November | 92.10 | 65.02 | 27.08 | 137.88 | 48.53 | 0.00 | 0.00 | 0.00 |
December | 102.78 | 78.23 | 24.55 | 155.81 | 51.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.96 | 34.39 | 28.58 | 93.85 | 39.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.46 | 1.90 | 24.55 | 37.98 | 26.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.78 | 78.23 | 31.45 | 155.81 | 51.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 115.03 | 84.38 | 30.65 | 173.88 | 60.68 | 0.00 | 0.00 | 0.00 |
February | 90.41 | 55.69 | 34.72 | 130.06 | 54.43 | 0.00 | 0.00 | 0.00 |
March | 72.07 | 34.82 | 37.26 | 103.29 | 56.00 | 0.00 | 0.00 | 0.00 |
April | 60.22 | 22.96 | 37.26 | 90.31 | 48.85 | 0.00 | 0.00 | 0.00 |
May | 42.88 | 5.28 | 37.60 | 52.21 | 45.16 | 0.00 | 0.00 | 0.00 |
June | 37.62 | 2.27 | 35.35 | 45.57 | 35.37 | 0.00 | 0.00 | 0.00 |
July | 39.85 | 4.49 | 35.36 | 55.71 | 31.91 | 0.00 | 0.00 | 0.00 |
August | 51.19 | 16.15 | 35.05 | 82.70 | 33.15 | 0.00 | 0.00 | 0.00 |
September | 71.24 | 36.10 | 35.14 | 115.88 | 38.38 | 0.00 | 0.00 | 0.00 |
October | 90.59 | 60.56 | 30.03 | 147.87 | 42.07 | 0.00 | 0.00 | 0.00 |
November | 110.11 | 77.73 | 32.37 | 165.08 | 57.44 | 0.00 | 0.00 | 0.00 |
December | 122.89 | 93.53 | 29.35 | 186.44 | 61.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 75.28 | 41.11 | 34.16 | 112.36 | 47.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 37.62 | 2.27 | 29.35 | 45.57 | 31.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.89 | 93.53 | 37.60 | 186.44 | 61.47 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257692E+09 | 0.189029E+09 | 68662961.73 | 0.385544E+09 | 0.148954E+09 |
February | 0.182932E+09 | 0.112676E+09 | 70255471.66 | 0.258364E+09 | 0.124307E+09 |
March | 0.161465E+09 | 77995209.48 | 83469784.12 | 0.226915E+09 | 0.140581E+09 |
April | 0.130556E+09 | 49782315.15 | 80773802.02 | 0.193081E+09 | 0.117669E+09 |
May | 96064863.77 | 11822097.95 | 84242765.81 | 0.113504E+09 | 0.112199E+09 |
June | 81555873.29 | 4924049.82 | 76631823.47 | 96169208.28 | 84518752.45 |
July | 89269746.81 | 10049224.57 | 79220522.24 | 0.123908E+09 | 76601723.95 |
August | 0.114685E+09 | 36175194.33 | 78509647.06 | 0.184738E+09 | 79593250.24 |
September | 0.154436E+09 | 78258129.89 | 76177968.73 | 0.249941E+09 | 89899955.13 |
October | 0.202954E+09 | 0.135680E+09 | 67273430.23 | 0.330250E+09 | 0.100259E+09 |
November | 0.238712E+09 | 0.168527E+09 | 70185095.75 | 0.354388E+09 | 0.135635E+09 |
December | 0.275297E+09 | 0.209537E+09 | 65760100.01 | 0.413808E+09 | 0.149941E+09 |
Annual Sum or Average | 0.198562E+10 | 0.108446E+10 | 0.901163E+09 | 0.293061E+10 | 0.136016E+10 |
Minimum of Months | 81555873.29 | 4924049.82 | 65760100.01 | 96169208.28 | 76601723.95 |
Maximum of Months | 0.275297E+09 | 0.209537E+09 | 84242765.81 | 0.413808E+09 | 0.149941E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257692E+09 | 0.189029E+09 | 68662961.73 | 0.385544E+09 | 0.148954E+09 |
February | 0.182932E+09 | 0.112676E+09 | 70255471.66 | 0.258364E+09 | 0.124307E+09 |
March | 0.161465E+09 | 77995209.48 | 83469784.12 | 0.226915E+09 | 0.140581E+09 |
April | 0.130556E+09 | 49782315.15 | 80773802.02 | 0.193081E+09 | 0.117669E+09 |
May | 96064863.77 | 11822097.95 | 84242765.81 | 0.113504E+09 | 0.112199E+09 |
June | 81555873.29 | 4924049.82 | 76631823.47 | 96169208.28 | 84518752.45 |
July | 89269746.81 | 10049224.57 | 79220522.24 | 0.123908E+09 | 76601723.95 |
August | 0.114685E+09 | 36175194.33 | 78509647.06 | 0.184738E+09 | 79593250.24 |
September | 0.154436E+09 | 78258129.89 | 76177968.73 | 0.249941E+09 | 89899955.13 |
October | 0.202954E+09 | 0.135680E+09 | 67273430.23 | 0.330250E+09 | 0.100259E+09 |
November | 0.238712E+09 | 0.168527E+09 | 70185095.75 | 0.354388E+09 | 0.135635E+09 |
December | 0.275297E+09 | 0.209537E+09 | 65760100.01 | 0.413808E+09 | 0.149941E+09 |
Annual Sum or Average | 0.198562E+10 | 0.108446E+10 | 0.901163E+09 | 0.293061E+10 | 0.136016E+10 |
Minimum of Months | 81555873.29 | 4924049.82 | 65760100.01 | 96169208.28 | 76601723.95 |
Maximum of Months | 0.275297E+09 | 0.209537E+09 | 84242765.81 | 0.413808E+09 | 0.149941E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257692E+09 | 0.189029E+09 | 68662961.73 | 0.385544E+09 | 0.148954E+09 |
February | 0.182932E+09 | 0.112676E+09 | 70255471.66 | 0.258364E+09 | 0.124307E+09 |
March | 0.161465E+09 | 77995209.48 | 83469784.12 | 0.226915E+09 | 0.140581E+09 |
April | 0.130556E+09 | 49782315.15 | 80773802.02 | 0.193081E+09 | 0.117669E+09 |
May | 96064863.77 | 11822097.95 | 84242765.81 | 0.113504E+09 | 0.112199E+09 |
June | 81555873.29 | 4924049.82 | 76631823.47 | 96169208.28 | 84518752.45 |
July | 89269746.81 | 10049224.57 | 79220522.24 | 0.123908E+09 | 76601723.95 |
August | 0.114685E+09 | 36175194.33 | 78509647.06 | 0.184738E+09 | 79593250.24 |
September | 0.154436E+09 | 78258129.89 | 76177968.73 | 0.249941E+09 | 89899955.13 |
October | 0.202954E+09 | 0.135680E+09 | 67273430.23 | 0.330250E+09 | 0.100259E+09 |
November | 0.238712E+09 | 0.168527E+09 | 70185095.75 | 0.354388E+09 | 0.135635E+09 |
December | 0.275297E+09 | 0.209537E+09 | 65760100.01 | 0.413808E+09 | 0.149941E+09 |
Annual Sum or Average | 0.198562E+10 | 0.108446E+10 | 0.901163E+09 | 0.293061E+10 | 0.136016E+10 |
Minimum of Months | 81555873.29 | 4924049.82 | 65760100.01 | 96169208.28 | 76601723.95 |
Maximum of Months | 0.275297E+09 | 0.209537E+09 | 84242765.81 | 0.413808E+09 | 0.149941E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257692E+09 | 0.189029E+09 | 68662961.73 | 0.385544E+09 | 0.148954E+09 |
February | 0.182932E+09 | 0.112676E+09 | 70255471.66 | 0.258364E+09 | 0.124307E+09 |
March | 0.161465E+09 | 77995209.48 | 83469784.12 | 0.226915E+09 | 0.140581E+09 |
April | 0.130556E+09 | 49782315.15 | 80773802.02 | 0.193081E+09 | 0.117669E+09 |
May | 96064863.77 | 11822097.95 | 84242765.81 | 0.113504E+09 | 0.112199E+09 |
June | 81555873.29 | 4924049.82 | 76631823.47 | 96169208.28 | 84518752.45 |
July | 89269746.81 | 10049224.57 | 79220522.24 | 0.123908E+09 | 76601723.95 |
August | 0.114685E+09 | 36175194.33 | 78509647.06 | 0.184738E+09 | 79593250.24 |
September | 0.154436E+09 | 78258129.89 | 76177968.73 | 0.249941E+09 | 89899955.13 |
October | 0.202954E+09 | 0.135680E+09 | 67273430.23 | 0.330250E+09 | 0.100259E+09 |
November | 0.238712E+09 | 0.168527E+09 | 70185095.75 | 0.354388E+09 | 0.135635E+09 |
December | 0.275297E+09 | 0.209537E+09 | 65760100.01 | 0.413808E+09 | 0.149941E+09 |
Annual Sum or Average | 0.198562E+10 | 0.108446E+10 | 0.901163E+09 | 0.293061E+10 | 0.136016E+10 |
Minimum of Months | 81555873.29 | 4924049.82 | 65760100.01 | 96169208.28 | 76601723.95 |
Maximum of Months | 0.275297E+09 | 0.209537E+09 | 84242765.81 | 0.413808E+09 | 0.149941E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.309785E+09 | 0.227241E+09 | 82543450.73 | 0.463619E+09 | 0.177332E+09 |
February | 0.219912E+09 | 0.135454E+09 | 84457892.83 | 0.311387E+09 | 0.147790E+09 |
March | 0.194106E+09 | 93762249.22 | 0.100344E+09 | 0.273498E+09 | 0.167006E+09 |
April | 0.156949E+09 | 59846006.84 | 97102545.23 | 0.232499E+09 | 0.140068E+09 |
May | 0.115485E+09 | 14211981.76 | 0.101273E+09 | 0.137114E+09 | 0.133363E+09 |
June | 98042715.30 | 5919465.95 | 92123249.35 | 0.115936E+09 | 0.100683E+09 |
July | 0.107316E+09 | 12080715.02 | 95235263.81 | 0.148952E+09 | 91396631.83 |
August | 0.137869E+09 | 43488152.79 | 94380682.40 | 0.222010E+09 | 94885900.13 |
September | 0.185656E+09 | 94078320.04 | 91577646.08 | 0.300495E+09 | 0.107225E+09 |
October | 0.243981E+09 | 0.163108E+09 | 80873019.95 | 0.396959E+09 | 0.119515E+09 |
November | 0.286969E+09 | 0.202596E+09 | 84373290.15 | 0.426469E+09 | 0.161477E+09 |
December | 0.330949E+09 | 0.251896E+09 | 79053764.04 | 0.497719E+09 | 0.178620E+09 |
Annual Sum or Average | 0.238702E+10 | 0.130368E+10 | 0.108334E+10 | 0.352666E+10 | 0.161936E+10 |
Minimum of Months | 98042715.30 | 5919465.95 | 79053764.04 | 0.115936E+09 | 91396631.83 |
Maximum of Months | 0.330949E+09 | 0.251896E+09 | 0.101273E+09 | 0.497719E+09 | 0.178620E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.309785E+09 | 0.227241E+09 | 82543450.73 | 0.463619E+09 | 0.177332E+09 |
February | 0.219912E+09 | 0.135454E+09 | 84457892.83 | 0.311387E+09 | 0.147790E+09 |
March | 0.194106E+09 | 93762249.22 | 0.100344E+09 | 0.273498E+09 | 0.167006E+09 |
April | 0.156949E+09 | 59846006.84 | 97102545.23 | 0.232499E+09 | 0.140068E+09 |
May | 0.115485E+09 | 14211981.76 | 0.101273E+09 | 0.137114E+09 | 0.133363E+09 |
June | 98042715.30 | 5919465.95 | 92123249.35 | 0.115936E+09 | 0.100683E+09 |
July | 0.107316E+09 | 12080715.02 | 95235263.81 | 0.148952E+09 | 91396631.83 |
August | 0.137869E+09 | 43488152.79 | 94380682.40 | 0.222010E+09 | 94885900.13 |
September | 0.185656E+09 | 94078320.04 | 91577646.08 | 0.300495E+09 | 0.107225E+09 |
October | 0.243981E+09 | 0.163108E+09 | 80873019.95 | 0.396959E+09 | 0.119515E+09 |
November | 0.286969E+09 | 0.202596E+09 | 84373290.15 | 0.426469E+09 | 0.161477E+09 |
December | 0.330949E+09 | 0.251896E+09 | 79053764.04 | 0.497719E+09 | 0.178620E+09 |
Annual Sum or Average | 0.238702E+10 | 0.130368E+10 | 0.108334E+10 | 0.352666E+10 | 0.161936E+10 |
Minimum of Months | 98042715.30 | 5919465.95 | 79053764.04 | 0.115936E+09 | 91396631.83 |
Maximum of Months | 0.330949E+09 | 0.251896E+09 | 0.101273E+09 | 0.497719E+09 | 0.178620E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257692E+09 | 0.189029E+09 | 68662961.73 | 0.380461E+09 | 0.158361E+09 |
February | 0.182932E+09 | 0.112676E+09 | 70255471.66 | 0.253275E+09 | 0.133588E+09 |
March | 0.161465E+09 | 77995209.48 | 83469784.12 | 0.220789E+09 | 0.152366E+09 |
April | 0.130556E+09 | 49782315.15 | 80773802.02 | 0.190361E+09 | 0.122329E+09 |
May | 96064863.77 | 11822097.95 | 84242765.81 | 0.111058E+09 | 0.116250E+09 |
June | 81555873.29 | 4924049.82 | 76631823.47 | 94783344.95 | 86485996.47 |
July | 89269746.81 | 10049224.57 | 79220522.24 | 0.123178E+09 | 77462201.16 |
August | 0.114685E+09 | 36175194.33 | 78509647.06 | 0.183859E+09 | 80741518.48 |
September | 0.154436E+09 | 78258129.89 | 76177968.73 | 0.248764E+09 | 91388766.42 |
October | 0.202954E+09 | 0.135680E+09 | 67273430.23 | 0.328727E+09 | 0.102006E+09 |
November | 0.238712E+09 | 0.168527E+09 | 70185095.75 | 0.351134E+09 | 0.140600E+09 |
December | 0.275297E+09 | 0.209537E+09 | 65760100.01 | 0.408827E+09 | 0.158523E+09 |
Annual Sum or Average | 0.198562E+10 | 0.108446E+10 | 0.901163E+09 | 0.289522E+10 | 0.142010E+10 |
Minimum of Months | 81555873.29 | 4924049.82 | 65760100.01 | 94783344.95 | 77462201.16 |
Maximum of Months | 0.275297E+09 | 0.209537E+09 | 84242765.81 | 0.408827E+09 | 0.158523E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257692E+09 | 0.189029E+09 | 68662961.73 | 0.380461E+09 | 0.158361E+09 |
February | 0.182932E+09 | 0.112676E+09 | 70255471.66 | 0.253275E+09 | 0.133588E+09 |
March | 0.161465E+09 | 77995209.48 | 83469784.12 | 0.220789E+09 | 0.152366E+09 |
April | 0.130556E+09 | 49782315.15 | 80773802.02 | 0.190361E+09 | 0.122329E+09 |
May | 96064863.77 | 11822097.95 | 84242765.81 | 0.111058E+09 | 0.116250E+09 |
June | 81555873.29 | 4924049.82 | 76631823.47 | 94783344.95 | 86485996.47 |
July | 89269746.81 | 10049224.57 | 79220522.24 | 0.123178E+09 | 77462201.16 |
August | 0.114685E+09 | 36175194.33 | 78509647.06 | 0.183859E+09 | 80741518.48 |
September | 0.154436E+09 | 78258129.89 | 76177968.73 | 0.248764E+09 | 91388766.42 |
October | 0.202954E+09 | 0.135680E+09 | 67273430.23 | 0.328727E+09 | 0.102006E+09 |
November | 0.238712E+09 | 0.168527E+09 | 70185095.75 | 0.351134E+09 | 0.140600E+09 |
December | 0.275297E+09 | 0.209537E+09 | 65760100.01 | 0.408827E+09 | 0.158523E+09 |
Annual Sum or Average | 0.198562E+10 | 0.108446E+10 | 0.901163E+09 | 0.289522E+10 | 0.142010E+10 |
Minimum of Months | 81555873.29 | 4924049.82 | 65760100.01 | 94783344.95 | 77462201.16 |
Maximum of Months | 0.275297E+09 | 0.209537E+09 | 84242765.81 | 0.408827E+09 | 0.158523E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.309785E+09 | 0.227241E+09 | 82543450.73 | 0.457673E+09 | 0.188380E+09 |
February | 0.219912E+09 | 0.135454E+09 | 84457892.83 | 0.305443E+09 | 0.158673E+09 |
March | 0.194106E+09 | 93762249.22 | 0.100344E+09 | 0.266298E+09 | 0.180814E+09 |
April | 0.156949E+09 | 59846006.84 | 97102545.23 | 0.229335E+09 | 0.145538E+09 |
May | 0.115485E+09 | 14211981.76 | 0.101273E+09 | 0.134260E+09 | 0.138086E+09 |
June | 98042715.30 | 5919465.95 | 92123249.35 | 0.114326E+09 | 0.102985E+09 |
July | 0.107316E+09 | 12080715.02 | 95235263.81 | 0.148124E+09 | 92398295.25 |
August | 0.137869E+09 | 43488152.79 | 94380682.40 | 0.221024E+09 | 96210791.69 |
September | 0.185656E+09 | 94078320.04 | 91577646.08 | 0.299174E+09 | 0.108963E+09 |
October | 0.243981E+09 | 0.163108E+09 | 80873019.95 | 0.395241E+09 | 0.121548E+09 |
November | 0.286969E+09 | 0.202596E+09 | 84373290.15 | 0.422711E+09 | 0.167292E+09 |
December | 0.330949E+09 | 0.251896E+09 | 79053764.04 | 0.491910E+09 | 0.188703E+09 |
Annual Sum or Average | 0.238702E+10 | 0.130368E+10 | 0.108334E+10 | 0.348552E+10 | 0.168959E+10 |
Minimum of Months | 98042715.30 | 5919465.95 | 79053764.04 | 0.114326E+09 | 92398295.25 |
Maximum of Months | 0.330949E+09 | 0.251896E+09 | 0.101273E+09 | 0.491910E+09 | 0.188703E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257692E+09 | 0.189029E+09 | 68662961.73 | 0.381494E+09 | 0.156661E+09 |
February | 0.182932E+09 | 0.112676E+09 | 70255471.66 | 0.253894E+09 | 0.132257E+09 |
March | 0.161465E+09 | 77995209.48 | 83469784.12 | 0.221532E+09 | 0.150424E+09 |
April | 0.130556E+09 | 49782315.15 | 80773802.02 | 0.190798E+09 | 0.122441E+09 |
May | 96064863.77 | 11822097.95 | 84242765.81 | 0.111405E+09 | 0.116726E+09 |
June | 81555873.29 | 4924049.82 | 76631823.47 | 94979900.42 | 88040323.19 |
July | 89269746.81 | 10049224.57 | 79220522.24 | 0.123132E+09 | 80418510.05 |
August | 0.114685E+09 | 36175194.33 | 78509647.06 | 0.183946E+09 | 83609146.25 |
September | 0.154436E+09 | 78258129.89 | 76177968.73 | 0.248942E+09 | 93720356.08 |
October | 0.202954E+09 | 0.135680E+09 | 67273430.23 | 0.328711E+09 | 0.104925E+09 |
November | 0.238712E+09 | 0.168527E+09 | 70185095.75 | 0.351668E+09 | 0.140676E+09 |
December | 0.275297E+09 | 0.209537E+09 | 65760100.01 | 0.409464E+09 | 0.157851E+09 |
Annual Sum or Average | 0.198562E+10 | 0.108446E+10 | 0.901163E+09 | 0.289997E+10 | 0.142775E+10 |
Minimum of Months | 81555873.29 | 4924049.82 | 65760100.01 | 94979900.42 | 80418510.05 |
Maximum of Months | 0.275297E+09 | 0.209537E+09 | 84242765.81 | 0.409464E+09 | 0.157851E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257692E+09 | 0.189029E+09 | 68662961.73 | 0.381494E+09 | 0.156661E+09 |
February | 0.182932E+09 | 0.112676E+09 | 70255471.66 | 0.253894E+09 | 0.132257E+09 |
March | 0.161465E+09 | 77995209.48 | 83469784.12 | 0.221532E+09 | 0.150424E+09 |
April | 0.130556E+09 | 49782315.15 | 80773802.02 | 0.190798E+09 | 0.122441E+09 |
May | 96064863.77 | 11822097.95 | 84242765.81 | 0.111405E+09 | 0.116726E+09 |
June | 81555873.29 | 4924049.82 | 76631823.47 | 94979900.42 | 88040323.19 |
July | 89269746.81 | 10049224.57 | 79220522.24 | 0.123132E+09 | 80418510.05 |
August | 0.114685E+09 | 36175194.33 | 78509647.06 | 0.183946E+09 | 83609146.25 |
September | 0.154436E+09 | 78258129.89 | 76177968.73 | 0.248942E+09 | 93720356.08 |
October | 0.202954E+09 | 0.135680E+09 | 67273430.23 | 0.328711E+09 | 0.104925E+09 |
November | 0.238712E+09 | 0.168527E+09 | 70185095.75 | 0.351668E+09 | 0.140676E+09 |
December | 0.275297E+09 | 0.209537E+09 | 65760100.01 | 0.409464E+09 | 0.157851E+09 |
Annual Sum or Average | 0.198562E+10 | 0.108446E+10 | 0.901163E+09 | 0.289997E+10 | 0.142775E+10 |
Minimum of Months | 81555873.29 | 4924049.82 | 65760100.01 | 94979900.42 | 80418510.05 |
Maximum of Months | 0.275297E+09 | 0.209537E+09 | 84242765.81 | 0.409464E+09 | 0.157851E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.308092E+09 | 0.226000E+09 | 82092393.62 | 0.456397E+09 | 0.185327E+09 |
February | 0.218711E+09 | 0.134714E+09 | 83996374.29 | 0.304510E+09 | 0.156228E+09 |
March | 0.193045E+09 | 93249887.21 | 99795205.46 | 0.265724E+09 | 0.177536E+09 |
April | 0.156091E+09 | 59518979.48 | 96571930.22 | 0.228601E+09 | 0.144818E+09 |
May | 0.114854E+09 | 14134320.66 | 0.100719E+09 | 0.133938E+09 | 0.137840E+09 |
June | 97506962.76 | 5887119.14 | 91619843.62 | 0.113935E+09 | 0.104190E+09 |
July | 0.106730E+09 | 12014700.18 | 94714852.53 | 0.147260E+09 | 95301643.31 |
August | 0.137115E+09 | 43250512.61 | 93864940.96 | 0.219915E+09 | 98992880.35 |
September | 0.184641E+09 | 93564230.86 | 91077221.78 | 0.297749E+09 | 0.111046E+09 |
October | 0.242648E+09 | 0.162217E+09 | 80431090.87 | 0.393062E+09 | 0.124252E+09 |
November | 0.285401E+09 | 0.201489E+09 | 83912233.92 | 0.421038E+09 | 0.166427E+09 |
December | 0.329141E+09 | 0.250519E+09 | 78621776.26 | 0.489980E+09 | 0.186858E+09 |
Annual Sum or Average | 0.237398E+10 | 0.129656E+10 | 0.107742E+10 | 0.347211E+10 | 0.168882E+10 |
Minimum of Months | 97506962.76 | 5887119.14 | 78621776.26 | 0.113935E+09 | 95301643.31 |
Maximum of Months | 0.329141E+09 | 0.250519E+09 | 0.100719E+09 | 0.489980E+09 | 0.186858E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257692E+09 | 0.189029E+09 | 68662961.73 | 0.382275E+09 | 0.154615E+09 |
February | 0.182932E+09 | 0.112676E+09 | 70255471.66 | 0.254488E+09 | 0.130555E+09 |
March | 0.161465E+09 | 77995209.48 | 83469784.12 | 0.222344E+09 | 0.148194E+09 |
April | 0.130556E+09 | 49782315.15 | 80773802.02 | 0.191167E+09 | 0.121228E+09 |
May | 96064863.77 | 11822097.95 | 84242765.81 | 0.111711E+09 | 0.115737E+09 |
June | 81555873.29 | 4924049.82 | 76631823.47 | 95182352.39 | 87424699.91 |
July | 89269746.81 | 10049224.57 | 79220522.24 | 0.123258E+09 | 80073468.63 |
August | 0.114685E+09 | 36175194.33 | 78509647.06 | 0.184050E+09 | 83278358.88 |
September | 0.154436E+09 | 78258129.89 | 76177968.73 | 0.249073E+09 | 93213773.79 |
October | 0.202954E+09 | 0.135680E+09 | 67273430.23 | 0.328815E+09 | 0.104554E+09 |
November | 0.238712E+09 | 0.168527E+09 | 70185095.75 | 0.352025E+09 | 0.139595E+09 |
December | 0.275297E+09 | 0.209537E+09 | 65760100.01 | 0.410002E+09 | 0.156331E+09 |
Annual Sum or Average | 0.198562E+10 | 0.108446E+10 | 0.901163E+09 | 0.290439E+10 | 0.141480E+10 |
Minimum of Months | 81555873.29 | 4924049.82 | 65760100.01 | 95182352.39 | 80073468.63 |
Maximum of Months | 0.275297E+09 | 0.209537E+09 | 84242765.81 | 0.410002E+09 | 0.156331E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257692E+09 | 0.189029E+09 | 68662961.73 | 0.382275E+09 | 0.154615E+09 |
February | 0.182932E+09 | 0.112676E+09 | 70255471.66 | 0.254488E+09 | 0.130555E+09 |
March | 0.161465E+09 | 77995209.48 | 83469784.12 | 0.222344E+09 | 0.148194E+09 |
April | 0.130556E+09 | 49782315.15 | 80773802.02 | 0.191167E+09 | 0.121228E+09 |
May | 96064863.77 | 11822097.95 | 84242765.81 | 0.111711E+09 | 0.115737E+09 |
June | 81555873.29 | 4924049.82 | 76631823.47 | 95182352.39 | 87424699.91 |
July | 89269746.81 | 10049224.57 | 79220522.24 | 0.123258E+09 | 80073468.63 |
August | 0.114685E+09 | 36175194.33 | 78509647.06 | 0.184050E+09 | 83278358.88 |
September | 0.154436E+09 | 78258129.89 | 76177968.73 | 0.249073E+09 | 93213773.79 |
October | 0.202954E+09 | 0.135680E+09 | 67273430.23 | 0.328815E+09 | 0.104554E+09 |
November | 0.238712E+09 | 0.168527E+09 | 70185095.75 | 0.352025E+09 | 0.139595E+09 |
December | 0.275297E+09 | 0.209537E+09 | 65760100.01 | 0.410002E+09 | 0.156331E+09 |
Annual Sum or Average | 0.198562E+10 | 0.108446E+10 | 0.901163E+09 | 0.290439E+10 | 0.141480E+10 |
Minimum of Months | 81555873.29 | 4924049.82 | 65760100.01 | 95182352.39 | 80073468.63 |
Maximum of Months | 0.275297E+09 | 0.209537E+09 | 84242765.81 | 0.410002E+09 | 0.156331E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.308092E+09 | 0.226000E+09 | 82092393.62 | 0.457329E+09 | 0.182912E+09 |
February | 0.218711E+09 | 0.134714E+09 | 83996374.29 | 0.305222E+09 | 0.154224E+09 |
March | 0.193045E+09 | 93249887.21 | 99795205.46 | 0.266695E+09 | 0.174908E+09 |
April | 0.156091E+09 | 59518979.48 | 96571930.22 | 0.229044E+09 | 0.143385E+09 |
May | 0.114854E+09 | 14134320.66 | 0.100719E+09 | 0.134307E+09 | 0.136673E+09 |
June | 97506962.76 | 5887119.14 | 91619843.62 | 0.114179E+09 | 0.103461E+09 |
July | 0.106730E+09 | 12014700.18 | 94714852.53 | 0.147412E+09 | 94891939.26 |
August | 0.137115E+09 | 43250512.61 | 93864940.96 | 0.220041E+09 | 98601602.73 |
September | 0.184641E+09 | 93564230.86 | 91077221.78 | 0.297908E+09 | 0.110446E+09 |
October | 0.242648E+09 | 0.162217E+09 | 80431090.87 | 0.393187E+09 | 0.123816E+09 |
November | 0.285401E+09 | 0.201489E+09 | 83912233.92 | 0.421465E+09 | 0.165150E+09 |
December | 0.329141E+09 | 0.250519E+09 | 78621776.26 | 0.490623E+09 | 0.185063E+09 |
Annual Sum or Average | 0.237398E+10 | 0.129656E+10 | 0.107742E+10 | 0.347741E+10 | 0.167353E+10 |
Minimum of Months | 97506962.76 | 5887119.14 | 78621776.26 | 0.114179E+09 | 94891939.26 |
Maximum of Months | 0.329141E+09 | 0.250519E+09 | 0.100719E+09 | 0.490623E+09 | 0.185063E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257692E+09 | 0.189029E+09 | 68662961.73 | 0.383323E+09 | 0.152338E+09 |
February | 0.182932E+09 | 0.112676E+09 | 70255471.66 | 0.255545E+09 | 0.128219E+09 |
March | 0.161465E+09 | 77995209.48 | 83469784.12 | 0.223744E+09 | 0.145193E+09 |
April | 0.130556E+09 | 49782315.15 | 80773802.02 | 0.191787E+09 | 0.119698E+09 |
May | 96064863.77 | 11822097.95 | 84242765.81 | 0.112266E+09 | 0.114454E+09 |
June | 81555873.29 | 4924049.82 | 76631823.47 | 95568567.63 | 86516811.45 |
July | 89269746.81 | 10049224.57 | 79220522.24 | 0.123580E+09 | 79267341.31 |
August | 0.114685E+09 | 36175194.33 | 78509647.06 | 0.184336E+09 | 82469975.53 |
September | 0.154436E+09 | 78258129.89 | 76177968.73 | 0.249361E+09 | 92328278.22 |
October | 0.202954E+09 | 0.135680E+09 | 67273430.23 | 0.329119E+09 | 0.103686E+09 |
November | 0.238712E+09 | 0.168527E+09 | 70185095.75 | 0.352612E+09 | 0.138250E+09 |
December | 0.275297E+09 | 0.209537E+09 | 65760100.01 | 0.410916E+09 | 0.154350E+09 |
Annual Sum or Average | 0.198562E+10 | 0.108446E+10 | 0.901163E+09 | 0.291216E+10 | 0.139677E+10 |
Minimum of Months | 81555873.29 | 4924049.82 | 65760100.01 | 95568567.63 | 79267341.31 |
Maximum of Months | 0.275297E+09 | 0.209537E+09 | 84242765.81 | 0.410916E+09 | 0.154350E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257692E+09 | 0.189029E+09 | 68662961.73 | 0.383323E+09 | 0.152338E+09 |
February | 0.182932E+09 | 0.112676E+09 | 70255471.66 | 0.255545E+09 | 0.128219E+09 |
March | 0.161465E+09 | 77995209.48 | 83469784.12 | 0.223744E+09 | 0.145193E+09 |
April | 0.130556E+09 | 49782315.15 | 80773802.02 | 0.191787E+09 | 0.119698E+09 |
May | 96064863.77 | 11822097.95 | 84242765.81 | 0.112266E+09 | 0.114454E+09 |
June | 81555873.29 | 4924049.82 | 76631823.47 | 95568567.63 | 86516811.45 |
July | 89269746.81 | 10049224.57 | 79220522.24 | 0.123580E+09 | 79267341.31 |
August | 0.114685E+09 | 36175194.33 | 78509647.06 | 0.184336E+09 | 82469975.53 |
September | 0.154436E+09 | 78258129.89 | 76177968.73 | 0.249361E+09 | 92328278.22 |
October | 0.202954E+09 | 0.135680E+09 | 67273430.23 | 0.329119E+09 | 0.103686E+09 |
November | 0.238712E+09 | 0.168527E+09 | 70185095.75 | 0.352612E+09 | 0.138250E+09 |
December | 0.275297E+09 | 0.209537E+09 | 65760100.01 | 0.410916E+09 | 0.154350E+09 |
Annual Sum or Average | 0.198562E+10 | 0.108446E+10 | 0.901163E+09 | 0.291216E+10 | 0.139677E+10 |
Minimum of Months | 81555873.29 | 4924049.82 | 65760100.01 | 95568567.63 | 79267341.31 |
Maximum of Months | 0.275297E+09 | 0.209537E+09 | 84242765.81 | 0.410916E+09 | 0.154350E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.308092E+09 | 0.226000E+09 | 82092393.62 | 0.458582E+09 | 0.180230E+09 |
February | 0.218711E+09 | 0.134714E+09 | 83996374.29 | 0.306483E+09 | 0.151477E+09 |
March | 0.193045E+09 | 93249887.21 | 99795205.46 | 0.268366E+09 | 0.171379E+09 |
April | 0.156091E+09 | 59518979.48 | 96571930.22 | 0.229788E+09 | 0.141583E+09 |
May | 0.114854E+09 | 14134320.66 | 0.100719E+09 | 0.134974E+09 | 0.135168E+09 |
June | 97506962.76 | 5887119.14 | 91619843.62 | 0.114643E+09 | 0.102393E+09 |
July | 0.106730E+09 | 12014700.18 | 94714852.53 | 0.147798E+09 | 93943542.57 |
August | 0.137115E+09 | 43250512.61 | 93864940.96 | 0.220387E+09 | 97654898.48 |
September | 0.184641E+09 | 93564230.86 | 91077221.78 | 0.298254E+09 | 0.109404E+09 |
October | 0.242648E+09 | 0.162217E+09 | 80431090.87 | 0.393554E+09 | 0.122798E+09 |
November | 0.285401E+09 | 0.201489E+09 | 83912233.92 | 0.422167E+09 | 0.163566E+09 |
December | 0.329141E+09 | 0.250519E+09 | 78621776.26 | 0.491712E+09 | 0.182730E+09 |
Annual Sum or Average | 0.237398E+10 | 0.129656E+10 | 0.107742E+10 | 0.348671E+10 | 0.165233E+10 |
Minimum of Months | 97506962.76 | 5887119.14 | 78621776.26 | 0.114643E+09 | 93943542.57 |
Maximum of Months | 0.329141E+09 | 0.250519E+09 | 0.100719E+09 | 0.491712E+09 | 0.182730E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257692E+09 | 0.189029E+09 | 68662961.73 | 0.386391E+09 | 0.147057E+09 |
February | 0.182932E+09 | 0.112676E+09 | 70255471.66 | 0.259014E+09 | 0.122444E+09 |
March | 0.161465E+09 | 77995209.48 | 83469784.12 | 0.227810E+09 | 0.138373E+09 |
April | 0.130556E+09 | 49782315.15 | 80773802.02 | 0.193821E+09 | 0.115873E+09 |
May | 96064863.77 | 11822097.95 | 84242765.81 | 0.114230E+09 | 0.111035E+09 |
June | 81555873.29 | 4924049.82 | 76631823.47 | 96682339.70 | 84246521.03 |
July | 89269746.81 | 10049224.57 | 79220522.24 | 0.124169E+09 | 77195437.04 |
August | 0.114685E+09 | 36175194.33 | 78509647.06 | 0.184953E+09 | 80267827.45 |
September | 0.154436E+09 | 78258129.89 | 76177968.73 | 0.250311E+09 | 90114755.22 |
October | 0.202954E+09 | 0.135680E+09 | 67273430.23 | 0.330171E+09 | 0.101391E+09 |
November | 0.238712E+09 | 0.168527E+09 | 70185095.75 | 0.354825E+09 | 0.134477E+09 |
December | 0.275297E+09 | 0.209537E+09 | 65760100.01 | 0.413958E+09 | 0.149361E+09 |
Annual Sum or Average | 0.198562E+10 | 0.108446E+10 | 0.901163E+09 | 0.293633E+10 | 0.135183E+10 |
Minimum of Months | 81555873.29 | 4924049.82 | 65760100.01 | 96682339.70 | 77195437.04 |
Maximum of Months | 0.275297E+09 | 0.209537E+09 | 84242765.81 | 0.413958E+09 | 0.149361E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257692E+09 | 0.189029E+09 | 68662961.73 | 0.386391E+09 | 0.147057E+09 |
February | 0.182932E+09 | 0.112676E+09 | 70255471.66 | 0.259014E+09 | 0.122444E+09 |
March | 0.161465E+09 | 77995209.48 | 83469784.12 | 0.227810E+09 | 0.138373E+09 |
April | 0.130556E+09 | 49782315.15 | 80773802.02 | 0.193821E+09 | 0.115873E+09 |
May | 96064863.77 | 11822097.95 | 84242765.81 | 0.114230E+09 | 0.111035E+09 |
June | 81555873.29 | 4924049.82 | 76631823.47 | 96682339.70 | 84246521.03 |
July | 89269746.81 | 10049224.57 | 79220522.24 | 0.124169E+09 | 77195437.04 |
August | 0.114685E+09 | 36175194.33 | 78509647.06 | 0.184953E+09 | 80267827.45 |
September | 0.154436E+09 | 78258129.89 | 76177968.73 | 0.250311E+09 | 90114755.22 |
October | 0.202954E+09 | 0.135680E+09 | 67273430.23 | 0.330171E+09 | 0.101391E+09 |
November | 0.238712E+09 | 0.168527E+09 | 70185095.75 | 0.354825E+09 | 0.134477E+09 |
December | 0.275297E+09 | 0.209537E+09 | 65760100.01 | 0.413958E+09 | 0.149361E+09 |
Annual Sum or Average | 0.198562E+10 | 0.108446E+10 | 0.901163E+09 | 0.293633E+10 | 0.135183E+10 |
Minimum of Months | 81555873.29 | 4924049.82 | 65760100.01 | 96682339.70 | 77195437.04 |
Maximum of Months | 0.275297E+09 | 0.209537E+09 | 84242765.81 | 0.413958E+09 | 0.149361E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257692E+09 | 0.189029E+09 | 68662961.73 | 0.386391E+09 | 0.147057E+09 |
February | 0.182932E+09 | 0.112676E+09 | 70255471.66 | 0.259014E+09 | 0.122444E+09 |
March | 0.161465E+09 | 77995209.48 | 83469784.12 | 0.227810E+09 | 0.138373E+09 |
April | 0.130556E+09 | 49782315.15 | 80773802.02 | 0.193821E+09 | 0.115873E+09 |
May | 96064863.77 | 11822097.95 | 84242765.81 | 0.114230E+09 | 0.111035E+09 |
June | 81555873.29 | 4924049.82 | 76631823.47 | 96682339.70 | 84246521.03 |
July | 89269746.81 | 10049224.57 | 79220522.24 | 0.124169E+09 | 77195437.04 |
August | 0.114685E+09 | 36175194.33 | 78509647.06 | 0.184953E+09 | 80267827.45 |
September | 0.154436E+09 | 78258129.89 | 76177968.73 | 0.250311E+09 | 90114755.22 |
October | 0.202954E+09 | 0.135680E+09 | 67273430.23 | 0.330171E+09 | 0.101391E+09 |
November | 0.238712E+09 | 0.168527E+09 | 70185095.75 | 0.354825E+09 | 0.134477E+09 |
December | 0.275297E+09 | 0.209537E+09 | 65760100.01 | 0.413958E+09 | 0.149361E+09 |
Annual Sum or Average | 0.198562E+10 | 0.108446E+10 | 0.901163E+09 | 0.293633E+10 | 0.135183E+10 |
Minimum of Months | 81555873.29 | 4924049.82 | 65760100.01 | 96682339.70 | 77195437.04 |
Maximum of Months | 0.275297E+09 | 0.209537E+09 | 84242765.81 | 0.413958E+09 | 0.149361E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257692E+09 | 0.189029E+09 | 68662961.73 | 0.386391E+09 | 0.147057E+09 |
February | 0.182932E+09 | 0.112676E+09 | 70255471.66 | 0.259014E+09 | 0.122444E+09 |
March | 0.161465E+09 | 77995209.48 | 83469784.12 | 0.227810E+09 | 0.138373E+09 |
April | 0.130556E+09 | 49782315.15 | 80773802.02 | 0.193821E+09 | 0.115873E+09 |
May | 96064863.77 | 11822097.95 | 84242765.81 | 0.114230E+09 | 0.111035E+09 |
June | 81555873.29 | 4924049.82 | 76631823.47 | 96682339.70 | 84246521.03 |
July | 89269746.81 | 10049224.57 | 79220522.24 | 0.124169E+09 | 77195437.04 |
August | 0.114685E+09 | 36175194.33 | 78509647.06 | 0.184953E+09 | 80267827.45 |
September | 0.154436E+09 | 78258129.89 | 76177968.73 | 0.250311E+09 | 90114755.22 |
October | 0.202954E+09 | 0.135680E+09 | 67273430.23 | 0.330171E+09 | 0.101391E+09 |
November | 0.238712E+09 | 0.168527E+09 | 70185095.75 | 0.354825E+09 | 0.134477E+09 |
December | 0.275297E+09 | 0.209537E+09 | 65760100.01 | 0.413958E+09 | 0.149361E+09 |
Annual Sum or Average | 0.198562E+10 | 0.108446E+10 | 0.901163E+09 | 0.293633E+10 | 0.135183E+10 |
Minimum of Months | 81555873.29 | 4924049.82 | 65760100.01 | 96682339.70 | 77195437.04 |
Maximum of Months | 0.275297E+09 | 0.209537E+09 | 84242765.81 | 0.413958E+09 | 0.149361E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.308092E+09 | 0.226000E+09 | 82092393.62 | 0.462111E+09 | 0.174062E+09 |
February | 0.218711E+09 | 0.134714E+09 | 83996374.29 | 0.310471E+09 | 0.144742E+09 |
March | 0.193045E+09 | 93249887.21 | 99795205.46 | 0.273082E+09 | 0.163440E+09 |
April | 0.156091E+09 | 59518979.48 | 96571930.22 | 0.232133E+09 | 0.137118E+09 |
May | 0.114854E+09 | 14134320.66 | 0.100719E+09 | 0.137248E+09 | 0.131203E+09 |
June | 97506962.76 | 5887119.14 | 91619843.62 | 0.115932E+09 | 99745438.22 |
July | 0.106730E+09 | 12014700.18 | 94714852.53 | 0.148482E+09 | 91521449.38 |
August | 0.137115E+09 | 43250512.61 | 93864940.96 | 0.221084E+09 | 95093888.81 |
September | 0.184641E+09 | 93564230.86 | 91077221.78 | 0.299317E+09 | 0.106816E+09 |
October | 0.242648E+09 | 0.162217E+09 | 80431090.87 | 0.394721E+09 | 0.120124E+09 |
November | 0.285401E+09 | 0.201489E+09 | 83912233.92 | 0.424677E+09 | 0.159170E+09 |
December | 0.329141E+09 | 0.250519E+09 | 78621776.26 | 0.495195E+09 | 0.176899E+09 |
Annual Sum or Average | 0.237398E+10 | 0.129656E+10 | 0.107742E+10 | 0.351445E+10 | 0.159994E+10 |
Minimum of Months | 97506962.76 | 5887119.14 | 78621776.26 | 0.115932E+09 | 91521449.38 |
Maximum of Months | 0.329141E+09 | 0.250519E+09 | 0.100719E+09 | 0.495195E+09 | 0.176899E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.308092E+09 | 0.226000E+09 | 82092393.62 | 0.462111E+09 | 0.174062E+09 |
February | 0.218711E+09 | 0.134714E+09 | 83996374.29 | 0.310471E+09 | 0.144742E+09 |
March | 0.193045E+09 | 93249887.21 | 99795205.46 | 0.273082E+09 | 0.163440E+09 |
April | 0.156091E+09 | 59518979.48 | 96571930.22 | 0.232133E+09 | 0.137118E+09 |
May | 0.114854E+09 | 14134320.66 | 0.100719E+09 | 0.137248E+09 | 0.131203E+09 |
June | 97506962.76 | 5887119.14 | 91619843.62 | 0.115932E+09 | 99745438.22 |
July | 0.106730E+09 | 12014700.18 | 94714852.53 | 0.148482E+09 | 91521449.38 |
August | 0.137115E+09 | 43250512.61 | 93864940.96 | 0.221084E+09 | 95093888.81 |
September | 0.184641E+09 | 93564230.86 | 91077221.78 | 0.299317E+09 | 0.106816E+09 |
October | 0.242648E+09 | 0.162217E+09 | 80431090.87 | 0.394721E+09 | 0.120124E+09 |
November | 0.285401E+09 | 0.201489E+09 | 83912233.92 | 0.424677E+09 | 0.159170E+09 |
December | 0.329141E+09 | 0.250519E+09 | 78621776.26 | 0.495195E+09 | 0.176899E+09 |
Annual Sum or Average | 0.237398E+10 | 0.129656E+10 | 0.107742E+10 | 0.351445E+10 | 0.159994E+10 |
Minimum of Months | 97506962.76 | 5887119.14 | 78621776.26 | 0.115932E+09 | 91521449.38 |
Maximum of Months | 0.329141E+09 | 0.250519E+09 | 0.100719E+09 | 0.495195E+09 | 0.176899E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257692E+09 | 0.189029E+09 | 68662961.73 | 0.384605E+09 | 0.148900E+09 |
February | 0.182932E+09 | 0.112676E+09 | 70255471.66 | 0.256923E+09 | 0.124745E+09 |
March | 0.161465E+09 | 77995209.48 | 83469784.12 | 0.225569E+09 | 0.140831E+09 |
April | 0.130556E+09 | 49782315.15 | 80773802.02 | 0.192655E+09 | 0.116937E+09 |
May | 96064863.77 | 11822097.95 | 84242765.81 | 0.113202E+09 | 0.111930E+09 |
June | 81555873.29 | 4924049.82 | 76631823.47 | 96248538.73 | 84323031.22 |
July | 89269746.81 | 10049224.57 | 79220522.24 | 0.123970E+09 | 76953322.64 |
August | 0.114685E+09 | 36175194.33 | 78509647.06 | 0.184628E+09 | 80032121.05 |
September | 0.154436E+09 | 78258129.89 | 76177968.73 | 0.249713E+09 | 90049245.86 |
October | 0.202954E+09 | 0.135680E+09 | 67273430.23 | 0.329464E+09 | 0.101348E+09 |
November | 0.238712E+09 | 0.168527E+09 | 70185095.75 | 0.353326E+09 | 0.135922E+09 |
December | 0.275297E+09 | 0.209537E+09 | 65760100.01 | 0.412075E+09 | 0.151252E+09 |
Annual Sum or Average | 0.198562E+10 | 0.108446E+10 | 0.901163E+09 | 0.292238E+10 | 0.136322E+10 |
Minimum of Months | 81555873.29 | 4924049.82 | 65760100.01 | 96248538.73 | 76953322.64 |
Maximum of Months | 0.275297E+09 | 0.209537E+09 | 84242765.81 | 0.412075E+09 | 0.151252E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257692E+09 | 0.189029E+09 | 68662961.73 | 0.384605E+09 | 0.148900E+09 |
February | 0.182932E+09 | 0.112676E+09 | 70255471.66 | 0.256923E+09 | 0.124745E+09 |
March | 0.161465E+09 | 77995209.48 | 83469784.12 | 0.225569E+09 | 0.140831E+09 |
April | 0.130556E+09 | 49782315.15 | 80773802.02 | 0.192655E+09 | 0.116937E+09 |
May | 96064863.77 | 11822097.95 | 84242765.81 | 0.113202E+09 | 0.111930E+09 |
June | 81555873.29 | 4924049.82 | 76631823.47 | 96248538.73 | 84323031.22 |
July | 89269746.81 | 10049224.57 | 79220522.24 | 0.123970E+09 | 76953322.64 |
August | 0.114685E+09 | 36175194.33 | 78509647.06 | 0.184628E+09 | 80032121.05 |
September | 0.154436E+09 | 78258129.89 | 76177968.73 | 0.249713E+09 | 90049245.86 |
October | 0.202954E+09 | 0.135680E+09 | 67273430.23 | 0.329464E+09 | 0.101348E+09 |
November | 0.238712E+09 | 0.168527E+09 | 70185095.75 | 0.353326E+09 | 0.135922E+09 |
December | 0.275297E+09 | 0.209537E+09 | 65760100.01 | 0.412075E+09 | 0.151252E+09 |
Annual Sum or Average | 0.198562E+10 | 0.108446E+10 | 0.901163E+09 | 0.292238E+10 | 0.136322E+10 |
Minimum of Months | 81555873.29 | 4924049.82 | 65760100.01 | 96248538.73 | 76953322.64 |
Maximum of Months | 0.275297E+09 | 0.209537E+09 | 84242765.81 | 0.412075E+09 | 0.151252E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.308092E+09 | 0.226000E+09 | 82092393.62 | 0.460135E+09 | 0.176165E+09 |
February | 0.218711E+09 | 0.134714E+09 | 83996374.29 | 0.308139E+09 | 0.147376E+09 |
March | 0.193045E+09 | 93249887.21 | 99795205.46 | 0.270563E+09 | 0.166239E+09 |
April | 0.156091E+09 | 59518979.48 | 96571930.22 | 0.230850E+09 | 0.138318E+09 |
May | 0.114854E+09 | 14134320.66 | 0.100719E+09 | 0.136112E+09 | 0.132190E+09 |
June | 97506962.76 | 5887119.14 | 91619843.62 | 0.115476E+09 | 99801601.51 |
July | 0.106730E+09 | 12014700.18 | 94714852.53 | 0.148295E+09 | 91215199.95 |
August | 0.137115E+09 | 43250512.61 | 93864940.96 | 0.220770E+09 | 94786571.54 |
September | 0.184641E+09 | 93564230.86 | 91077221.78 | 0.298705E+09 | 0.106710E+09 |
October | 0.242648E+09 | 0.162217E+09 | 80431090.87 | 0.393995E+09 | 0.120039E+09 |
November | 0.285401E+09 | 0.201489E+09 | 83912233.92 | 0.423041E+09 | 0.160810E+09 |
December | 0.329141E+09 | 0.250519E+09 | 78621776.26 | 0.493116E+09 | 0.179066E+09 |
Annual Sum or Average | 0.237398E+10 | 0.129656E+10 | 0.107742E+10 | 0.349920E+10 | 0.161272E+10 |
Minimum of Months | 97506962.76 | 5887119.14 | 78621776.26 | 0.115476E+09 | 91215199.95 |
Maximum of Months | 0.329141E+09 | 0.250519E+09 | 0.100719E+09 | 0.493116E+09 | 0.179066E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257692E+09 | 0.189029E+09 | 68662961.73 | 0.384854E+09 | 0.148491E+09 |
February | 0.182932E+09 | 0.112676E+09 | 70255471.66 | 0.257182E+09 | 0.124312E+09 |
March | 0.161465E+09 | 77995209.48 | 83469784.12 | 0.225834E+09 | 0.140385E+09 |
April | 0.130556E+09 | 49782315.15 | 80773802.02 | 0.192847E+09 | 0.116575E+09 |
May | 96064863.77 | 11822097.95 | 84242765.81 | 0.113411E+09 | 0.111570E+09 |
June | 81555873.29 | 4924049.82 | 76631823.47 | 96450254.13 | 83994648.30 |
July | 89269746.81 | 10049224.57 | 79220522.24 | 0.124151E+09 | 76665933.02 |
August | 0.114685E+09 | 36175194.33 | 78509647.06 | 0.184793E+09 | 79736437.96 |
September | 0.154436E+09 | 78258129.89 | 76177968.73 | 0.249869E+09 | 89719774.79 |
October | 0.202954E+09 | 0.135680E+09 | 67273430.23 | 0.329632E+09 | 0.101014E+09 |
November | 0.238712E+09 | 0.168527E+09 | 70185095.75 | 0.353521E+09 | 0.135601E+09 |
December | 0.275297E+09 | 0.209537E+09 | 65760100.01 | 0.412323E+09 | 0.150857E+09 |
Annual Sum or Average | 0.198562E+10 | 0.108446E+10 | 0.901163E+09 | 0.292487E+10 | 0.135892E+10 |
Minimum of Months | 81555873.29 | 4924049.82 | 65760100.01 | 96450254.13 | 76665933.02 |
Maximum of Months | 0.275297E+09 | 0.209537E+09 | 84242765.81 | 0.412323E+09 | 0.150857E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257692E+09 | 0.189029E+09 | 68662961.73 | 0.384854E+09 | 0.148491E+09 |
February | 0.182932E+09 | 0.112676E+09 | 70255471.66 | 0.257182E+09 | 0.124312E+09 |
March | 0.161465E+09 | 77995209.48 | 83469784.12 | 0.225834E+09 | 0.140385E+09 |
April | 0.130556E+09 | 49782315.15 | 80773802.02 | 0.192847E+09 | 0.116575E+09 |
May | 96064863.77 | 11822097.95 | 84242765.81 | 0.113411E+09 | 0.111570E+09 |
June | 81555873.29 | 4924049.82 | 76631823.47 | 96450254.13 | 83994648.30 |
July | 89269746.81 | 10049224.57 | 79220522.24 | 0.124151E+09 | 76665933.02 |
August | 0.114685E+09 | 36175194.33 | 78509647.06 | 0.184793E+09 | 79736437.96 |
September | 0.154436E+09 | 78258129.89 | 76177968.73 | 0.249869E+09 | 89719774.79 |
October | 0.202954E+09 | 0.135680E+09 | 67273430.23 | 0.329632E+09 | 0.101014E+09 |
November | 0.238712E+09 | 0.168527E+09 | 70185095.75 | 0.353521E+09 | 0.135601E+09 |
December | 0.275297E+09 | 0.209537E+09 | 65760100.01 | 0.412323E+09 | 0.150857E+09 |
Annual Sum or Average | 0.198562E+10 | 0.108446E+10 | 0.901163E+09 | 0.292487E+10 | 0.135892E+10 |
Minimum of Months | 81555873.29 | 4924049.82 | 65760100.01 | 96450254.13 | 76665933.02 |
Maximum of Months | 0.275297E+09 | 0.209537E+09 | 84242765.81 | 0.412323E+09 | 0.150857E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.308092E+09 | 0.226000E+09 | 82092393.62 | 0.460432E+09 | 0.175683E+09 |
February | 0.218711E+09 | 0.134714E+09 | 83996374.29 | 0.308449E+09 | 0.146867E+09 |
March | 0.193045E+09 | 93249887.21 | 99795205.46 | 0.270880E+09 | 0.165715E+09 |
April | 0.156091E+09 | 59518979.48 | 96571930.22 | 0.231082E+09 | 0.137891E+09 |
May | 0.114854E+09 | 14134320.66 | 0.100719E+09 | 0.136364E+09 | 0.131765E+09 |
June | 97506962.76 | 5887119.14 | 91619843.62 | 0.115719E+09 | 99413246.68 |
July | 0.106730E+09 | 12014700.18 | 94714852.53 | 0.148513E+09 | 90874944.62 |
August | 0.137115E+09 | 43250512.61 | 93864940.96 | 0.220970E+09 | 94437471.39 |
September | 0.184641E+09 | 93564230.86 | 91077221.78 | 0.298894E+09 | 0.106320E+09 |
October | 0.242648E+09 | 0.162217E+09 | 80431090.87 | 0.394197E+09 | 0.119644E+09 |
November | 0.285401E+09 | 0.201489E+09 | 83912233.92 | 0.423275E+09 | 0.160430E+09 |
December | 0.329141E+09 | 0.250519E+09 | 78621776.26 | 0.493412E+09 | 0.178599E+09 |
Annual Sum or Average | 0.237398E+10 | 0.129656E+10 | 0.107742E+10 | 0.350218E+10 | 0.160764E+10 |
Minimum of Months | 97506962.76 | 5887119.14 | 78621776.26 | 0.115719E+09 | 90874944.62 |
Maximum of Months | 0.329141E+09 | 0.250519E+09 | 0.100719E+09 | 0.493412E+09 | 0.178599E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257692E+09 | 0.189029E+09 | 68662961.73 | 0.386208E+09 | 0.145864E+09 |
February | 0.182932E+09 | 0.112676E+09 | 70255471.66 | 0.258757E+09 | 0.121138E+09 |
March | 0.161465E+09 | 77995209.48 | 83469784.12 | 0.227448E+09 | 0.137111E+09 |
April | 0.130556E+09 | 49782315.15 | 80773802.02 | 0.193750E+09 | 0.114482E+09 |
May | 96064863.77 | 11822097.95 | 84242765.81 | 0.114341E+09 | 0.109633E+09 |
June | 81555873.29 | 4924049.82 | 76631823.47 | 97111289.78 | 82664144.35 |
July | 89269746.81 | 10049224.57 | 79220522.24 | 0.124584E+09 | 75728518.55 |
August | 0.114685E+09 | 36175194.33 | 78509647.06 | 0.185181E+09 | 78787775.65 |
September | 0.154436E+09 | 78258129.89 | 76177968.73 | 0.250324E+09 | 88513466.92 |
October | 0.202954E+09 | 0.135680E+09 | 67273430.23 | 0.330138E+09 | 99819685.38 |
November | 0.238712E+09 | 0.168527E+09 | 70185095.75 | 0.354587E+09 | 0.133486E+09 |
December | 0.275297E+09 | 0.209537E+09 | 65760100.01 | 0.413774E+09 | 0.148119E+09 |
Annual Sum or Average | 0.198562E+10 | 0.108446E+10 | 0.901163E+09 | 0.293620E+10 | 0.133535E+10 |
Minimum of Months | 81555873.29 | 4924049.82 | 65760100.01 | 97111289.78 | 75728518.55 |
Maximum of Months | 0.275297E+09 | 0.209537E+09 | 84242765.81 | 0.413774E+09 | 0.148119E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257692E+09 | 0.189029E+09 | 68662961.73 | 0.386208E+09 | 0.145864E+09 |
February | 0.182932E+09 | 0.112676E+09 | 70255471.66 | 0.258757E+09 | 0.121138E+09 |
March | 0.161465E+09 | 77995209.48 | 83469784.12 | 0.227448E+09 | 0.137111E+09 |
April | 0.130556E+09 | 49782315.15 | 80773802.02 | 0.193750E+09 | 0.114482E+09 |
May | 96064863.77 | 11822097.95 | 84242765.81 | 0.114341E+09 | 0.109633E+09 |
June | 81555873.29 | 4924049.82 | 76631823.47 | 97111289.78 | 82664144.35 |
July | 89269746.81 | 10049224.57 | 79220522.24 | 0.124584E+09 | 75728518.55 |
August | 0.114685E+09 | 36175194.33 | 78509647.06 | 0.185181E+09 | 78787775.65 |
September | 0.154436E+09 | 78258129.89 | 76177968.73 | 0.250324E+09 | 88513466.92 |
October | 0.202954E+09 | 0.135680E+09 | 67273430.23 | 0.330138E+09 | 99819685.38 |
November | 0.238712E+09 | 0.168527E+09 | 70185095.75 | 0.354587E+09 | 0.133486E+09 |
December | 0.275297E+09 | 0.209537E+09 | 65760100.01 | 0.413774E+09 | 0.148119E+09 |
Annual Sum or Average | 0.198562E+10 | 0.108446E+10 | 0.901163E+09 | 0.293620E+10 | 0.133535E+10 |
Minimum of Months | 81555873.29 | 4924049.82 | 65760100.01 | 97111289.78 | 75728518.55 |
Maximum of Months | 0.275297E+09 | 0.209537E+09 | 84242765.81 | 0.413774E+09 | 0.148119E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.308092E+09 | 0.226000E+09 | 82092393.62 | 0.462043E+09 | 0.172588E+09 |
February | 0.218711E+09 | 0.134714E+09 | 83996374.29 | 0.310321E+09 | 0.143133E+09 |
March | 0.193045E+09 | 93249887.21 | 99795205.46 | 0.272803E+09 | 0.161865E+09 |
April | 0.156091E+09 | 59518979.48 | 96571930.22 | 0.232164E+09 | 0.135425E+09 |
May | 0.114854E+09 | 14134320.66 | 0.100719E+09 | 0.137478E+09 | 0.129490E+09 |
June | 97506962.76 | 5887119.14 | 91619843.62 | 0.116513E+09 | 97847418.77 |
July | 0.106730E+09 | 12014700.18 | 94714852.53 | 0.149033E+09 | 89772520.28 |
August | 0.137115E+09 | 43250512.61 | 93864940.96 | 0.221434E+09 | 93323491.63 |
September | 0.184641E+09 | 93564230.86 | 91077221.78 | 0.299441E+09 | 0.104899E+09 |
October | 0.242648E+09 | 0.162217E+09 | 80431090.87 | 0.394805E+09 | 0.118241E+09 |
November | 0.285401E+09 | 0.201489E+09 | 83912233.92 | 0.424548E+09 | 0.157942E+09 |
December | 0.329141E+09 | 0.250519E+09 | 78621776.26 | 0.495140E+09 | 0.175374E+09 |
Annual Sum or Average | 0.237398E+10 | 0.129656E+10 | 0.107742E+10 | 0.351572E+10 | 0.157990E+10 |
Minimum of Months | 97506962.76 | 5887119.14 | 78621776.26 | 0.116513E+09 | 89772520.28 |
Maximum of Months | 0.329141E+09 | 0.250519E+09 | 0.100719E+09 | 0.495140E+09 | 0.175374E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257692E+09 | 0.189029E+09 | 68662961.73 | 0.389298E+09 | 0.137321E+09 |
February | 0.182932E+09 | 0.112676E+09 | 70255471.66 | 0.262389E+09 | 0.111400E+09 |
March | 0.161465E+09 | 77995209.48 | 83469784.12 | 0.230676E+09 | 0.127006E+09 |
April | 0.130556E+09 | 49782315.15 | 80773802.02 | 0.195358E+09 | 0.107026E+09 |
May | 96064863.77 | 11822097.95 | 84242765.81 | 0.116319E+09 | 0.102374E+09 |
June | 81555873.29 | 4924049.82 | 76631823.47 | 98455295.68 | 77445151.12 |
July | 89269746.81 | 10049224.57 | 79220522.24 | 0.124746E+09 | 72079522.86 |
August | 0.114685E+09 | 36175194.33 | 78509647.06 | 0.185248E+09 | 74937534.45 |
September | 0.154436E+09 | 78258129.89 | 76177968.73 | 0.251088E+09 | 83936672.52 |
October | 0.202954E+09 | 0.135680E+09 | 67273430.23 | 0.331200E+09 | 95095490.30 |
November | 0.238712E+09 | 0.168527E+09 | 70185095.75 | 0.357396E+09 | 0.125787E+09 |
December | 0.275297E+09 | 0.209537E+09 | 65760100.01 | 0.417330E+09 | 0.139023E+09 |
Annual Sum or Average | 0.198562E+10 | 0.108446E+10 | 0.901163E+09 | 0.295950E+10 | 0.125343E+10 |
Minimum of Months | 81555873.29 | 4924049.82 | 65760100.01 | 98455295.68 | 72079522.86 |
Maximum of Months | 0.275297E+09 | 0.209537E+09 | 84242765.81 | 0.417330E+09 | 0.139023E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257692E+09 | 0.189029E+09 | 68662961.73 | 0.389298E+09 | 0.137321E+09 |
February | 0.182932E+09 | 0.112676E+09 | 70255471.66 | 0.262389E+09 | 0.111400E+09 |
March | 0.161465E+09 | 77995209.48 | 83469784.12 | 0.230676E+09 | 0.127006E+09 |
April | 0.130556E+09 | 49782315.15 | 80773802.02 | 0.195358E+09 | 0.107026E+09 |
May | 96064863.77 | 11822097.95 | 84242765.81 | 0.116319E+09 | 0.102374E+09 |
June | 81555873.29 | 4924049.82 | 76631823.47 | 98455295.68 | 77445151.12 |
July | 89269746.81 | 10049224.57 | 79220522.24 | 0.124746E+09 | 72079522.86 |
August | 0.114685E+09 | 36175194.33 | 78509647.06 | 0.185248E+09 | 74937534.45 |
September | 0.154436E+09 | 78258129.89 | 76177968.73 | 0.251088E+09 | 83936672.52 |
October | 0.202954E+09 | 0.135680E+09 | 67273430.23 | 0.331200E+09 | 95095490.30 |
November | 0.238712E+09 | 0.168527E+09 | 70185095.75 | 0.357396E+09 | 0.125787E+09 |
December | 0.275297E+09 | 0.209537E+09 | 65760100.01 | 0.417330E+09 | 0.139023E+09 |
Annual Sum or Average | 0.198562E+10 | 0.108446E+10 | 0.901163E+09 | 0.295950E+10 | 0.125343E+10 |
Minimum of Months | 81555873.29 | 4924049.82 | 65760100.01 | 98455295.68 | 72079522.86 |
Maximum of Months | 0.275297E+09 | 0.209537E+09 | 84242765.81 | 0.417330E+09 | 0.139023E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.308092E+09 | 0.226000E+09 | 82092393.62 | 0.465721E+09 | 0.162524E+09 |
February | 0.218711E+09 | 0.134714E+09 | 83996374.29 | 0.314640E+09 | 0.131669E+09 |
March | 0.193045E+09 | 93249887.21 | 99795205.46 | 0.276655E+09 | 0.149977E+09 |
April | 0.156091E+09 | 59518979.48 | 96571930.22 | 0.234083E+09 | 0.126632E+09 |
May | 0.114854E+09 | 14134320.66 | 0.100719E+09 | 0.139843E+09 | 0.120948E+09 |
June | 97506962.76 | 5887119.14 | 91619843.62 | 0.118121E+09 | 91684359.94 |
July | 0.106730E+09 | 12014700.18 | 94714852.53 | 0.149218E+09 | 85460554.54 |
August | 0.137115E+09 | 43250512.61 | 93864940.96 | 0.221505E+09 | 88787364.68 |
September | 0.184641E+09 | 93564230.86 | 91077221.78 | 0.300356E+09 | 99489887.39 |
October | 0.242648E+09 | 0.162217E+09 | 80431090.87 | 0.396068E+09 | 0.112680E+09 |
November | 0.285401E+09 | 0.201489E+09 | 83912233.92 | 0.427893E+09 | 0.148873E+09 |
December | 0.329141E+09 | 0.250519E+09 | 78621776.26 | 0.499367E+09 | 0.164654E+09 |
Annual Sum or Average | 0.237398E+10 | 0.129656E+10 | 0.107742E+10 | 0.354347E+10 | 0.148338E+10 |
Minimum of Months | 97506962.76 | 5887119.14 | 78621776.26 | 0.118121E+09 | 85460554.54 |
Maximum of Months | 0.329141E+09 | 0.250519E+09 | 0.100719E+09 | 0.499367E+09 | 0.164654E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 921.97 | 354.87 | 616.16 | 451.99 | 164.18 | 0.00 | 0.00 |
February | 684.62 | 327.71 | 484.27 | 298.29 | 185.99 | 0.00 | 0.00 |
March | 543.11 | 334.65 | 386.08 | 186.49 | 199.58 | 0.00 | 0.00 |
April | 477.36 | 289.66 | 322.58 | 123.00 | 199.58 | 0.00 | 0.00 |
May | 271.90 | 267.15 | 229.70 | 28.27 | 201.43 | 0.00 | 0.00 |
June | 237.87 | 208.12 | 201.51 | 12.17 | 189.34 | 0.00 | 0.00 |
July | 296.27 | 182.65 | 213.45 | 24.03 | 189.42 | 0.00 | 0.00 |
August | 441.67 | 189.72 | 274.22 | 86.50 | 187.72 | 0.00 | 0.00 |
September | 617.58 | 221.47 | 381.58 | 193.36 | 188.22 | 0.00 | 0.00 |
October | 789.62 | 238.97 | 485.28 | 324.42 | 160.86 | 0.00 | 0.00 |
November | 875.96 | 333.91 | 589.81 | 416.40 | 173.41 | 0.00 | 0.00 |
December | 989.65 | 357.30 | 658.26 | 501.02 | 157.24 | 0.00 | 0.00 |
Annual Sum or Average | 595.37 | 275.22 | 403.24 | 220.23 | 183.01 | 0.00 | 0.00 |
Minimum of Months | 237.87 | 182.65 | 201.51 | 12.17 | 157.24 | 0.00 | 0.00 |
Maximum of Months | 989.65 | 357.30 | 658.26 | 501.02 | 201.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 454.97 | 188.58 | 308.08 | 225.99 | 82.09 | 0.00 | 0.00 |
February | 335.64 | 176.03 | 242.14 | 149.14 | 92.99 | 0.00 | 0.00 |
March | 264.29 | 181.28 | 193.04 | 93.25 | 99.79 | 0.00 | 0.00 |
April | 235.36 | 150.54 | 161.29 | 61.50 | 99.79 | 0.00 | 0.00 |
May | 133.06 | 138.36 | 114.85 | 14.13 | 100.72 | 0.00 | 0.00 |
June | 117.24 | 106.46 | 100.75 | 6.08 | 94.67 | 0.00 | 0.00 |
July | 147.28 | 92.34 | 106.73 | 12.01 | 94.71 | 0.00 | 0.00 |
August | 219.81 | 96.21 | 137.11 | 43.25 | 93.86 | 0.00 | 0.00 |
September | 307.37 | 112.55 | 190.79 | 96.68 | 94.11 | 0.00 | 0.00 |
October | 393.03 | 121.55 | 242.64 | 162.21 | 80.43 | 0.00 | 0.00 |
November | 434.02 | 173.03 | 294.91 | 208.20 | 86.71 | 0.00 | 0.00 |
December | 488.93 | 188.82 | 329.13 | 250.51 | 78.62 | 0.00 | 0.00 |
Annual Sum or Average | 294.14 | 143.64 | 201.62 | 110.12 | 91.50 | 0.00 | 0.00 |
Minimum of Months | 117.24 | 92.34 | 100.75 | 6.08 | 78.62 | 0.00 | 0.00 |
Maximum of Months | 488.93 | 188.82 | 329.13 | 250.51 | 100.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 455.27 | 186.17 | 307.45 | 225.53 | 81.92 | 0.00 | 0.00 |
February | 335.77 | 173.92 | 241.64 | 148.84 | 92.80 | 0.00 | 0.00 |
March | 264.63 | 178.61 | 192.64 | 93.06 | 99.59 | 0.00 | 0.00 |
April | 235.42 | 150.35 | 160.96 | 61.37 | 99.58 | 0.00 | 0.00 |
May | 133.19 | 138.62 | 114.61 | 14.10 | 100.51 | 0.00 | 0.00 |
June | 117.24 | 108.13 | 100.55 | 6.07 | 94.48 | 0.00 | 0.00 |
July | 146.93 | 95.63 | 106.51 | 11.99 | 94.52 | 0.00 | 0.00 |
August | 219.46 | 99.39 | 136.83 | 43.16 | 93.67 | 0.00 | 0.00 |
September | 306.96 | 115.16 | 190.40 | 96.48 | 93.92 | 0.00 | 0.00 |
October | 392.21 | 124.74 | 242.14 | 161.88 | 80.26 | 0.00 | 0.00 |
November | 433.79 | 172.75 | 294.30 | 207.77 | 86.53 | 0.00 | 0.00 |
December | 488.69 | 187.63 | 328.46 | 250.00 | 78.46 | 0.00 | 0.00 |
Annual Sum or Average | 294.01 | 144.10 | 201.21 | 109.89 | 91.32 | 0.00 | 0.00 |
Minimum of Months | 117.24 | 95.63 | 100.55 | 6.07 | 78.46 | 0.00 | 0.00 |
Maximum of Months | 488.69 | 187.63 | 328.46 | 250.00 | 100.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 456.20 | 183.74 | 307.45 | 225.53 | 81.92 | 0.00 | 0.00 |
February | 336.56 | 171.68 | 241.64 | 148.84 | 92.80 | 0.00 | 0.00 |
March | 265.60 | 175.96 | 192.64 | 93.06 | 99.59 | 0.00 | 0.00 |
April | 235.87 | 148.86 | 160.96 | 61.37 | 99.58 | 0.00 | 0.00 |
May | 133.56 | 137.45 | 114.61 | 14.10 | 100.51 | 0.00 | 0.00 |
June | 117.49 | 107.37 | 100.55 | 6.07 | 94.48 | 0.00 | 0.00 |
July | 147.08 | 95.22 | 106.51 | 11.99 | 94.52 | 0.00 | 0.00 |
August | 219.59 | 99.00 | 136.83 | 43.16 | 93.67 | 0.00 | 0.00 |
September | 307.12 | 114.53 | 190.40 | 96.48 | 93.92 | 0.00 | 0.00 |
October | 392.33 | 124.30 | 242.14 | 161.88 | 80.26 | 0.00 | 0.00 |
November | 434.23 | 171.43 | 294.30 | 207.77 | 86.53 | 0.00 | 0.00 |
December | 489.33 | 185.83 | 328.46 | 250.00 | 78.46 | 0.00 | 0.00 |
Annual Sum or Average | 294.46 | 142.79 | 201.21 | 109.89 | 91.32 | 0.00 | 0.00 |
Minimum of Months | 117.49 | 95.22 | 100.55 | 6.07 | 78.46 | 0.00 | 0.00 |
Maximum of Months | 489.33 | 185.83 | 328.46 | 250.00 | 100.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 457.45 | 181.04 | 307.45 | 225.53 | 81.92 | 0.00 | 0.00 |
February | 337.95 | 168.62 | 241.64 | 148.84 | 92.80 | 0.00 | 0.00 |
March | 267.27 | 172.40 | 192.64 | 93.06 | 99.59 | 0.00 | 0.00 |
April | 236.64 | 146.98 | 160.96 | 61.37 | 99.58 | 0.00 | 0.00 |
May | 134.22 | 135.93 | 114.61 | 14.10 | 100.51 | 0.00 | 0.00 |
June | 117.97 | 106.26 | 100.55 | 6.07 | 94.48 | 0.00 | 0.00 |
July | 147.46 | 94.26 | 106.51 | 11.99 | 94.52 | 0.00 | 0.00 |
August | 219.93 | 98.04 | 136.83 | 43.16 | 93.67 | 0.00 | 0.00 |
September | 307.48 | 113.45 | 190.40 | 96.48 | 93.92 | 0.00 | 0.00 |
October | 392.69 | 123.27 | 242.14 | 161.88 | 80.26 | 0.00 | 0.00 |
November | 434.95 | 169.78 | 294.30 | 207.77 | 86.53 | 0.00 | 0.00 |
December | 490.42 | 183.48 | 328.46 | 250.00 | 78.46 | 0.00 | 0.00 |
Annual Sum or Average | 295.25 | 140.98 | 201.21 | 109.89 | 91.32 | 0.00 | 0.00 |
Minimum of Months | 117.97 | 94.26 | 100.55 | 6.07 | 78.46 | 0.00 | 0.00 |
Maximum of Months | 490.42 | 183.48 | 328.46 | 250.00 | 100.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 922.11 | 349.59 | 614.90 | 451.06 | 163.84 | 0.00 | 0.00 |
February | 684.93 | 322.11 | 483.28 | 297.67 | 185.60 | 0.00 | 0.00 |
March | 544.13 | 328.69 | 385.29 | 186.11 | 199.17 | 0.00 | 0.00 |
April | 478.22 | 284.62 | 321.92 | 122.75 | 199.17 | 0.00 | 0.00 |
May | 273.08 | 263.79 | 229.23 | 28.21 | 201.02 | 0.00 | 0.00 |
June | 238.66 | 206.97 | 201.09 | 12.14 | 188.95 | 0.00 | 0.00 |
July | 296.31 | 183.63 | 213.01 | 23.98 | 189.04 | 0.00 | 0.00 |
August | 441.30 | 190.88 | 273.66 | 86.32 | 187.34 | 0.00 | 0.00 |
September | 617.24 | 221.49 | 380.80 | 192.96 | 187.83 | 0.00 | 0.00 |
October | 787.83 | 241.12 | 484.29 | 323.76 | 160.53 | 0.00 | 0.00 |
November | 875.25 | 330.34 | 588.60 | 415.54 | 173.06 | 0.00 | 0.00 |
December | 987.99 | 355.15 | 656.91 | 499.99 | 156.92 | 0.00 | 0.00 |
Annual Sum or Average | 595.33 | 272.93 | 402.41 | 219.78 | 182.63 | 0.00 | 0.00 |
Minimum of Months | 238.66 | 183.63 | 201.09 | 12.14 | 156.92 | 0.00 | 0.00 |
Maximum of Months | 987.99 | 355.15 | 656.91 | 499.99 | 201.02 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 458.98 | 176.96 | 307.45 | 225.53 | 81.92 | 0.00 | 0.00 |
February | 339.78 | 164.05 | 241.64 | 148.84 | 92.80 | 0.00 | 0.00 |
March | 269.45 | 167.23 | 192.64 | 93.06 | 99.59 | 0.00 | 0.00 |
April | 237.72 | 143.59 | 160.96 | 61.37 | 99.58 | 0.00 | 0.00 |
May | 135.35 | 132.93 | 114.61 | 14.10 | 100.51 | 0.00 | 0.00 |
June | 118.82 | 103.57 | 100.55 | 6.07 | 94.48 | 0.00 | 0.00 |
July | 147.94 | 91.52 | 106.51 | 11.99 | 94.52 | 0.00 | 0.00 |
August | 220.29 | 95.15 | 136.83 | 43.16 | 93.67 | 0.00 | 0.00 |
September | 307.92 | 110.65 | 190.40 | 96.48 | 93.92 | 0.00 | 0.00 |
October | 393.12 | 120.50 | 242.14 | 161.88 | 80.26 | 0.00 | 0.00 |
November | 435.84 | 166.92 | 294.30 | 207.77 | 86.53 | 0.00 | 0.00 |
December | 491.81 | 179.80 | 328.46 | 250.00 | 78.46 | 0.00 | 0.00 |
Annual Sum or Average | 296.29 | 137.59 | 201.21 | 109.89 | 91.32 | 0.00 | 0.00 |
Minimum of Months | 118.82 | 91.52 | 100.55 | 6.07 | 78.46 | 0.00 | 0.00 |
Maximum of Months | 491.81 | 179.80 | 328.46 | 250.00 | 100.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 459.28 | 176.47 | 307.45 | 225.53 | 81.92 | 0.00 | 0.00 |
February | 340.12 | 163.48 | 241.64 | 148.84 | 92.80 | 0.00 | 0.00 |
March | 269.77 | 166.70 | 192.64 | 93.06 | 99.59 | 0.00 | 0.00 |
April | 237.95 | 143.15 | 160.96 | 61.37 | 99.58 | 0.00 | 0.00 |
May | 135.60 | 132.51 | 114.61 | 14.10 | 100.51 | 0.00 | 0.00 |
June | 119.07 | 103.16 | 100.55 | 6.07 | 94.48 | 0.00 | 0.00 |
July | 148.15 | 91.18 | 106.51 | 11.99 | 94.52 | 0.00 | 0.00 |
August | 220.49 | 94.80 | 136.83 | 43.16 | 93.67 | 0.00 | 0.00 |
September | 308.11 | 110.25 | 190.40 | 96.48 | 93.92 | 0.00 | 0.00 |
October | 393.32 | 120.10 | 242.14 | 161.88 | 80.26 | 0.00 | 0.00 |
November | 436.08 | 166.52 | 294.30 | 207.77 | 86.53 | 0.00 | 0.00 |
December | 492.11 | 179.33 | 328.46 | 250.00 | 78.46 | 0.00 | 0.00 |
Annual Sum or Average | 296.55 | 137.16 | 201.21 | 109.89 | 91.32 | 0.00 | 0.00 |
Minimum of Months | 119.07 | 91.18 | 100.55 | 6.07 | 78.46 | 0.00 | 0.00 |
Maximum of Months | 492.11 | 179.33 | 328.46 | 250.00 | 100.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 460.89 | 173.36 | 307.45 | 225.53 | 81.92 | 0.00 | 0.00 |
February | 342.19 | 159.31 | 241.64 | 148.84 | 92.80 | 0.00 | 0.00 |
March | 271.69 | 162.82 | 192.64 | 93.06 | 99.59 | 0.00 | 0.00 |
April | 239.07 | 140.58 | 160.96 | 61.37 | 99.58 | 0.00 | 0.00 |
May | 136.71 | 130.21 | 114.61 | 14.10 | 100.51 | 0.00 | 0.00 |
June | 119.88 | 101.53 | 100.55 | 6.07 | 94.48 | 0.00 | 0.00 |
July | 148.67 | 90.06 | 106.51 | 11.99 | 94.52 | 0.00 | 0.00 |
August | 220.95 | 93.67 | 136.83 | 43.16 | 93.67 | 0.00 | 0.00 |
September | 308.68 | 108.77 | 190.40 | 96.48 | 93.92 | 0.00 | 0.00 |
October | 393.92 | 118.68 | 242.14 | 161.88 | 80.26 | 0.00 | 0.00 |
November | 437.39 | 163.93 | 294.30 | 207.77 | 86.53 | 0.00 | 0.00 |
December | 493.84 | 176.08 | 328.46 | 250.00 | 78.46 | 0.00 | 0.00 |
Annual Sum or Average | 297.70 | 134.79 | 201.21 | 109.89 | 91.32 | 0.00 | 0.00 |
Minimum of Months | 119.88 | 90.06 | 100.55 | 6.07 | 78.46 | 0.00 | 0.00 |
Maximum of Months | 493.84 | 176.08 | 328.46 | 250.00 | 100.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 464.57 | 163.22 | 307.45 | 225.53 | 81.92 | 0.00 | 0.00 |
February | 346.98 | 146.52 | 241.64 | 148.84 | 92.80 | 0.00 | 0.00 |
March | 275.54 | 150.83 | 192.64 | 93.06 | 99.59 | 0.00 | 0.00 |
April | 241.05 | 131.44 | 160.96 | 61.37 | 99.58 | 0.00 | 0.00 |
May | 139.07 | 121.60 | 114.61 | 14.10 | 100.51 | 0.00 | 0.00 |
June | 121.54 | 95.13 | 100.55 | 6.07 | 94.48 | 0.00 | 0.00 |
July | 148.86 | 85.73 | 106.51 | 11.99 | 94.52 | 0.00 | 0.00 |
August | 221.03 | 89.11 | 136.83 | 43.16 | 93.67 | 0.00 | 0.00 |
September | 309.62 | 103.15 | 190.40 | 96.48 | 93.92 | 0.00 | 0.00 |
October | 395.19 | 113.08 | 242.14 | 161.88 | 80.26 | 0.00 | 0.00 |
November | 440.85 | 154.49 | 294.30 | 207.77 | 86.53 | 0.00 | 0.00 |
December | 498.07 | 165.29 | 328.46 | 250.00 | 78.46 | 0.00 | 0.00 |
Annual Sum or Average | 300.05 | 126.53 | 201.21 | 109.89 | 91.32 | 0.00 | 0.00 |
Minimum of Months | 121.54 | 85.73 | 100.55 | 6.07 | 78.46 | 0.00 | 0.00 |
Maximum of Months | 498.07 | 165.29 | 328.46 | 250.00 | 100.51 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.246941E+10 | 0.950479E+09 | 0.165034E+10 | 0.121060E+10 | 0.439739E+09 | 0.00 | 0.00 |
February | 0.165623E+10 | 0.792805E+09 | 0.117155E+10 | 0.721614E+09 | 0.449938E+09 | 0.00 | 0.00 |
March | 0.145465E+10 | 0.896332E+09 | 0.103407E+10 | 0.499505E+09 | 0.534566E+09 | 0.00 | 0.00 |
April | 0.123732E+10 | 0.750811E+09 | 0.836122E+09 | 0.318821E+09 | 0.517300E+09 | 0.00 | 0.00 |
May | 0.728245E+09 | 0.715522E+09 | 0.615229E+09 | 75712355.33 | 0.539517E+09 | 0.00 | 0.00 |
June | 0.616548E+09 | 0.539441E+09 | 0.522309E+09 | 31535131.19 | 0.490774E+09 | 0.00 | 0.00 |
July | 0.793534E+09 | 0.489199E+09 | 0.571711E+09 | 64358328.32 | 0.507353E+09 | 0.00 | 0.00 |
August | 0.118297E+10 | 0.508144E+09 | 0.734477E+09 | 0.231677E+09 | 0.502800E+09 | 0.00 | 0.00 |
September | 0.160075E+10 | 0.574049E+09 | 0.989056E+09 | 0.501189E+09 | 0.487867E+09 | 0.00 | 0.00 |
October | 0.211492E+10 | 0.640066E+09 | 0.129978E+10 | 0.868937E+09 | 0.430840E+09 | 0.00 | 0.00 |
November | 0.227049E+10 | 0.865490E+09 | 0.152879E+10 | 0.107930E+10 | 0.449487E+09 | 0.00 | 0.00 |
December | 0.265067E+10 | 0.957004E+09 | 0.176309E+10 | 0.134194E+10 | 0.421148E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.187757E+11 | 0.867934E+10 | 0.127165E+11 | 0.694519E+10 | 0.577133E+10 | 0.00 | 0.00 |
Minimum of Months | 0.616548E+09 | 0.489199E+09 | 0.522309E+09 | 31535131.19 | 0.421148E+09 | 0.00 | 0.00 |
Maximum of Months | 0.265067E+10 | 0.957004E+09 | 0.176309E+10 | 0.134194E+10 | 0.539517E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.121859E+10 | 0.505102E+09 | 0.825168E+09 | 0.605299E+09 | 0.219869E+09 | 0.00 | 0.00 |
February | 0.811992E+09 | 0.425846E+09 | 0.585776E+09 | 0.360807E+09 | 0.224969E+09 | 0.00 | 0.00 |
March | 0.707873E+09 | 0.485544E+09 | 0.517036E+09 | 0.249753E+09 | 0.267283E+09 | 0.00 | 0.00 |
April | 0.610057E+09 | 0.390196E+09 | 0.418061E+09 | 0.159411E+09 | 0.258650E+09 | 0.00 | 0.00 |
May | 0.356375E+09 | 0.370584E+09 | 0.307614E+09 | 37856177.66 | 0.269758E+09 | 0.00 | 0.00 |
June | 0.303892E+09 | 0.275957E+09 | 0.261154E+09 | 15767565.59 | 0.245387E+09 | 0.00 | 0.00 |
July | 0.394480E+09 | 0.247323E+09 | 0.285855E+09 | 32179164.16 | 0.253676E+09 | 0.00 | 0.00 |
August | 0.588742E+09 | 0.257694E+09 | 0.367239E+09 | 0.115839E+09 | 0.251400E+09 | 0.00 | 0.00 |
September | 0.796702E+09 | 0.291741E+09 | 0.494528E+09 | 0.250595E+09 | 0.243934E+09 | 0.00 | 0.00 |
October | 0.105269E+10 | 0.325560E+09 | 0.649889E+09 | 0.434469E+09 | 0.215420E+09 | 0.00 | 0.00 |
November | 0.112498E+10 | 0.448490E+09 | 0.764394E+09 | 0.539650E+09 | 0.224743E+09 | 0.00 | 0.00 |
December | 0.130956E+10 | 0.505748E+09 | 0.881544E+09 | 0.670970E+09 | 0.210574E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.927594E+10 | 0.452978E+10 | 0.635826E+10 | 0.347259E+10 | 0.288566E+10 | 0.00 | 0.00 |
Minimum of Months | 0.303892E+09 | 0.247323E+09 | 0.261154E+09 | 15767565.59 | 0.210574E+09 | 0.00 | 0.00 |
Maximum of Months | 0.130956E+10 | 0.505748E+09 | 0.881544E+09 | 0.670970E+09 | 0.269758E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.121939E+10 | 0.498650E+09 | 0.823475E+09 | 0.604057E+09 | 0.219418E+09 | 0.00 | 0.00 |
February | 0.812296E+09 | 0.420739E+09 | 0.584574E+09 | 0.360067E+09 | 0.224507E+09 | 0.00 | 0.00 |
March | 0.708786E+09 | 0.478382E+09 | 0.515975E+09 | 0.249240E+09 | 0.266735E+09 | 0.00 | 0.00 |
April | 0.610198E+09 | 0.389701E+09 | 0.417203E+09 | 0.159084E+09 | 0.258120E+09 | 0.00 | 0.00 |
May | 0.356747E+09 | 0.371289E+09 | 0.306983E+09 | 37778516.56 | 0.269205E+09 | 0.00 | 0.00 |
June | 0.303894E+09 | 0.280269E+09 | 0.260619E+09 | 15735218.78 | 0.244883E+09 | 0.00 | 0.00 |
July | 0.393524E+09 | 0.256139E+09 | 0.285269E+09 | 32113149.32 | 0.253156E+09 | 0.00 | 0.00 |
August | 0.587806E+09 | 0.266211E+09 | 0.366485E+09 | 0.115601E+09 | 0.250884E+09 | 0.00 | 0.00 |
September | 0.795633E+09 | 0.298487E+09 | 0.493514E+09 | 0.250080E+09 | 0.243433E+09 | 0.00 | 0.00 |
October | 0.105048E+10 | 0.334102E+09 | 0.648555E+09 | 0.433577E+09 | 0.214978E+09 | 0.00 | 0.00 |
November | 0.112437E+10 | 0.447780E+09 | 0.762826E+09 | 0.538543E+09 | 0.224282E+09 | 0.00 | 0.00 |
December | 0.130891E+10 | 0.502560E+09 | 0.879735E+09 | 0.669593E+09 | 0.210142E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.927204E+10 | 0.454431E+10 | 0.634521E+10 | 0.346547E+10 | 0.287974E+10 | 0.00 | 0.00 |
Minimum of Months | 0.303894E+09 | 0.256139E+09 | 0.260619E+09 | 15735218.78 | 0.210142E+09 | 0.00 | 0.00 |
Maximum of Months | 0.130891E+10 | 0.502560E+09 | 0.879735E+09 | 0.669593E+09 | 0.269205E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.122188E+10 | 0.492142E+09 | 0.823475E+09 | 0.604057E+09 | 0.219418E+09 | 0.00 | 0.00 |
February | 0.814196E+09 | 0.415331E+09 | 0.584574E+09 | 0.360067E+09 | 0.224507E+09 | 0.00 | 0.00 |
March | 0.711380E+09 | 0.471294E+09 | 0.515975E+09 | 0.249240E+09 | 0.266735E+09 | 0.00 | 0.00 |
April | 0.611379E+09 | 0.385840E+09 | 0.417203E+09 | 0.159084E+09 | 0.258120E+09 | 0.00 | 0.00 |
May | 0.357728E+09 | 0.368145E+09 | 0.306983E+09 | 37778516.56 | 0.269205E+09 | 0.00 | 0.00 |
June | 0.304543E+09 | 0.278310E+09 | 0.260619E+09 | 15735218.78 | 0.244883E+09 | 0.00 | 0.00 |
July | 0.393927E+09 | 0.255038E+09 | 0.285269E+09 | 32113149.32 | 0.253156E+09 | 0.00 | 0.00 |
August | 0.588140E+09 | 0.265158E+09 | 0.366485E+09 | 0.115601E+09 | 0.250884E+09 | 0.00 | 0.00 |
September | 0.796055E+09 | 0.296873E+09 | 0.493514E+09 | 0.250080E+09 | 0.243433E+09 | 0.00 | 0.00 |
October | 0.105082E+10 | 0.332924E+09 | 0.648555E+09 | 0.433577E+09 | 0.214978E+09 | 0.00 | 0.00 |
November | 0.112551E+10 | 0.444340E+09 | 0.762826E+09 | 0.538543E+09 | 0.224282E+09 | 0.00 | 0.00 |
December | 0.131063E+10 | 0.497724E+09 | 0.879735E+09 | 0.669593E+09 | 0.210142E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.928618E+10 | 0.450312E+10 | 0.634521E+10 | 0.346547E+10 | 0.287974E+10 | 0.00 | 0.00 |
Minimum of Months | 0.304543E+09 | 0.255038E+09 | 0.260619E+09 | 15735218.78 | 0.210142E+09 | 0.00 | 0.00 |
Maximum of Months | 0.131063E+10 | 0.497724E+09 | 0.879735E+09 | 0.669593E+09 | 0.269205E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.122523E+10 | 0.484905E+09 | 0.823475E+09 | 0.604057E+09 | 0.219418E+09 | 0.00 | 0.00 |
February | 0.817572E+09 | 0.407915E+09 | 0.584574E+09 | 0.360067E+09 | 0.224507E+09 | 0.00 | 0.00 |
March | 0.715852E+09 | 0.461764E+09 | 0.515975E+09 | 0.249240E+09 | 0.266735E+09 | 0.00 | 0.00 |
April | 0.613362E+09 | 0.380979E+09 | 0.417203E+09 | 0.159084E+09 | 0.258120E+09 | 0.00 | 0.00 |
May | 0.359504E+09 | 0.364073E+09 | 0.306983E+09 | 37778516.56 | 0.269205E+09 | 0.00 | 0.00 |
June | 0.305780E+09 | 0.275427E+09 | 0.260619E+09 | 15735218.78 | 0.244883E+09 | 0.00 | 0.00 |
July | 0.394958E+09 | 0.252478E+09 | 0.285269E+09 | 32113149.32 | 0.253156E+09 | 0.00 | 0.00 |
August | 0.589058E+09 | 0.262595E+09 | 0.366485E+09 | 0.115601E+09 | 0.250884E+09 | 0.00 | 0.00 |
September | 0.796975E+09 | 0.294060E+09 | 0.493514E+09 | 0.250080E+09 | 0.243433E+09 | 0.00 | 0.00 |
October | 0.105179E+10 | 0.330170E+09 | 0.648555E+09 | 0.433577E+09 | 0.214978E+09 | 0.00 | 0.00 |
November | 0.112739E+10 | 0.440065E+09 | 0.762826E+09 | 0.538543E+09 | 0.224282E+09 | 0.00 | 0.00 |
December | 0.131354E+10 | 0.491430E+09 | 0.879735E+09 | 0.669593E+09 | 0.210142E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.931102E+10 | 0.444586E+10 | 0.634521E+10 | 0.346547E+10 | 0.287974E+10 | 0.00 | 0.00 |
Minimum of Months | 0.305780E+09 | 0.252478E+09 | 0.260619E+09 | 15735218.78 | 0.210142E+09 | 0.00 | 0.00 |
Maximum of Months | 0.131354E+10 | 0.491430E+09 | 0.879735E+09 | 0.669593E+09 | 0.269205E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.246979E+10 | 0.936350E+09 | 0.164695E+10 | 0.120811E+10 | 0.438837E+09 | 0.00 | 0.00 |
February | 0.165699E+10 | 0.779258E+09 | 0.116915E+10 | 0.720134E+09 | 0.449015E+09 | 0.00 | 0.00 |
March | 0.145740E+10 | 0.880368E+09 | 0.103195E+10 | 0.498481E+09 | 0.533470E+09 | 0.00 | 0.00 |
April | 0.123955E+10 | 0.737726E+09 | 0.834406E+09 | 0.318167E+09 | 0.516239E+09 | 0.00 | 0.00 |
May | 0.731415E+09 | 0.706546E+09 | 0.613967E+09 | 75557033.12 | 0.538410E+09 | 0.00 | 0.00 |
June | 0.618594E+09 | 0.536476E+09 | 0.521237E+09 | 31470437.57 | 0.489767E+09 | 0.00 | 0.00 |
July | 0.793638E+09 | 0.491823E+09 | 0.570538E+09 | 64226298.64 | 0.506312E+09 | 0.00 | 0.00 |
August | 0.118198E+10 | 0.511259E+09 | 0.732970E+09 | 0.231202E+09 | 0.501768E+09 | 0.00 | 0.00 |
September | 0.159988E+10 | 0.574092E+09 | 0.987027E+09 | 0.500161E+09 | 0.486866E+09 | 0.00 | 0.00 |
October | 0.211012E+10 | 0.645810E+09 | 0.129711E+10 | 0.867155E+09 | 0.429956E+09 | 0.00 | 0.00 |
November | 0.226865E+10 | 0.856248E+09 | 0.152565E+10 | 0.107709E+10 | 0.448565E+09 | 0.00 | 0.00 |
December | 0.264622E+10 | 0.951241E+09 | 0.175947E+10 | 0.133919E+10 | 0.420284E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.187742E+11 | 0.860719E+10 | 0.126904E+11 | 0.693094E+10 | 0.575949E+10 | 0.00 | 0.00 |
Minimum of Months | 0.618594E+09 | 0.491823E+09 | 0.521237E+09 | 31470437.57 | 0.420284E+09 | 0.00 | 0.00 |
Maximum of Months | 0.264622E+10 | 0.951241E+09 | 0.175947E+10 | 0.133919E+10 | 0.538410E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.122934E+10 | 0.473964E+09 | 0.823475E+09 | 0.604057E+09 | 0.219418E+09 | 0.00 | 0.00 |
February | 0.821984E+09 | 0.396865E+09 | 0.584574E+09 | 0.360067E+09 | 0.224507E+09 | 0.00 | 0.00 |
March | 0.721697E+09 | 0.447897E+09 | 0.515975E+09 | 0.249240E+09 | 0.266735E+09 | 0.00 | 0.00 |
April | 0.616159E+09 | 0.372192E+09 | 0.417203E+09 | 0.159084E+09 | 0.258120E+09 | 0.00 | 0.00 |
May | 0.362514E+09 | 0.356050E+09 | 0.306983E+09 | 37778516.56 | 0.269205E+09 | 0.00 | 0.00 |
June | 0.307972E+09 | 0.268446E+09 | 0.260619E+09 | 15735218.78 | 0.244883E+09 | 0.00 | 0.00 |
July | 0.396235E+09 | 0.245121E+09 | 0.285269E+09 | 32113149.32 | 0.253156E+09 | 0.00 | 0.00 |
August | 0.590025E+09 | 0.254850E+09 | 0.366485E+09 | 0.115601E+09 | 0.250884E+09 | 0.00 | 0.00 |
September | 0.798130E+09 | 0.286808E+09 | 0.493514E+09 | 0.250080E+09 | 0.243433E+09 | 0.00 | 0.00 |
October | 0.105292E+10 | 0.322736E+09 | 0.648555E+09 | 0.433577E+09 | 0.214978E+09 | 0.00 | 0.00 |
November | 0.112969E+10 | 0.432653E+09 | 0.762826E+09 | 0.538543E+09 | 0.224282E+09 | 0.00 | 0.00 |
December | 0.131727E+10 | 0.481569E+09 | 0.879735E+09 | 0.669593E+09 | 0.210142E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.934394E+10 | 0.433915E+10 | 0.634521E+10 | 0.346547E+10 | 0.287974E+10 | 0.00 | 0.00 |
Minimum of Months | 0.307972E+09 | 0.245121E+09 | 0.260619E+09 | 15735218.78 | 0.210142E+09 | 0.00 | 0.00 |
Maximum of Months | 0.131727E+10 | 0.481569E+09 | 0.879735E+09 | 0.669593E+09 | 0.269205E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.123014E+10 | 0.472665E+09 | 0.823475E+09 | 0.604057E+09 | 0.219418E+09 | 0.00 | 0.00 |
February | 0.822813E+09 | 0.395490E+09 | 0.584574E+09 | 0.360067E+09 | 0.224507E+09 | 0.00 | 0.00 |
March | 0.722545E+09 | 0.446484E+09 | 0.515975E+09 | 0.249240E+09 | 0.266735E+09 | 0.00 | 0.00 |
April | 0.616775E+09 | 0.371041E+09 | 0.417203E+09 | 0.159084E+09 | 0.258120E+09 | 0.00 | 0.00 |
May | 0.363185E+09 | 0.354903E+09 | 0.306983E+09 | 37778516.56 | 0.269205E+09 | 0.00 | 0.00 |
June | 0.308618E+09 | 0.267401E+09 | 0.260619E+09 | 15735218.78 | 0.244883E+09 | 0.00 | 0.00 |
July | 0.396814E+09 | 0.244207E+09 | 0.285269E+09 | 32113149.32 | 0.253156E+09 | 0.00 | 0.00 |
August | 0.590556E+09 | 0.253910E+09 | 0.366485E+09 | 0.115601E+09 | 0.250884E+09 | 0.00 | 0.00 |
September | 0.798632E+09 | 0.285759E+09 | 0.493514E+09 | 0.250080E+09 | 0.243433E+09 | 0.00 | 0.00 |
October | 0.105346E+10 | 0.321672E+09 | 0.648555E+09 | 0.433577E+09 | 0.214978E+09 | 0.00 | 0.00 |
November | 0.113032E+10 | 0.431631E+09 | 0.762826E+09 | 0.538543E+09 | 0.224282E+09 | 0.00 | 0.00 |
December | 0.131806E+10 | 0.480313E+09 | 0.879735E+09 | 0.669593E+09 | 0.210142E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.935191E+10 | 0.432548E+10 | 0.634521E+10 | 0.346547E+10 | 0.287974E+10 | 0.00 | 0.00 |
Minimum of Months | 0.308618E+09 | 0.244207E+09 | 0.260619E+09 | 15735218.78 | 0.210142E+09 | 0.00 | 0.00 |
Maximum of Months | 0.131806E+10 | 0.480313E+09 | 0.879735E+09 | 0.669593E+09 | 0.269205E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.123446E+10 | 0.464315E+09 | 0.823475E+09 | 0.604057E+09 | 0.219418E+09 | 0.00 | 0.00 |
February | 0.827834E+09 | 0.385410E+09 | 0.584574E+09 | 0.360067E+09 | 0.224507E+09 | 0.00 | 0.00 |
March | 0.727699E+09 | 0.436086E+09 | 0.515975E+09 | 0.249240E+09 | 0.266735E+09 | 0.00 | 0.00 |
April | 0.619663E+09 | 0.364389E+09 | 0.417203E+09 | 0.159084E+09 | 0.258120E+09 | 0.00 | 0.00 |
May | 0.366159E+09 | 0.348754E+09 | 0.306983E+09 | 37778516.56 | 0.269205E+09 | 0.00 | 0.00 |
June | 0.310735E+09 | 0.263175E+09 | 0.260619E+09 | 15735218.78 | 0.244883E+09 | 0.00 | 0.00 |
July | 0.398200E+09 | 0.241229E+09 | 0.285269E+09 | 32113149.32 | 0.253156E+09 | 0.00 | 0.00 |
August | 0.591796E+09 | 0.250899E+09 | 0.366485E+09 | 0.115601E+09 | 0.250884E+09 | 0.00 | 0.00 |
September | 0.800088E+09 | 0.281926E+09 | 0.493514E+09 | 0.250080E+09 | 0.243433E+09 | 0.00 | 0.00 |
October | 0.105508E+10 | 0.317880E+09 | 0.648555E+09 | 0.433577E+09 | 0.214978E+09 | 0.00 | 0.00 |
November | 0.113372E+10 | 0.424913E+09 | 0.762826E+09 | 0.538543E+09 | 0.224282E+09 | 0.00 | 0.00 |
December | 0.132269E+10 | 0.471610E+09 | 0.879735E+09 | 0.669593E+09 | 0.210142E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.938812E+10 | 0.425059E+10 | 0.634521E+10 | 0.346547E+10 | 0.287974E+10 | 0.00 | 0.00 |
Minimum of Months | 0.310735E+09 | 0.241229E+09 | 0.260619E+09 | 15735218.78 | 0.210142E+09 | 0.00 | 0.00 |
Maximum of Months | 0.132269E+10 | 0.471610E+09 | 0.879735E+09 | 0.669593E+09 | 0.269205E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.124432E+10 | 0.437166E+09 | 0.823475E+09 | 0.604057E+09 | 0.219418E+09 | 0.00 | 0.00 |
February | 0.839418E+09 | 0.354468E+09 | 0.584574E+09 | 0.360067E+09 | 0.224507E+09 | 0.00 | 0.00 |
March | 0.738004E+09 | 0.403987E+09 | 0.515975E+09 | 0.249240E+09 | 0.266735E+09 | 0.00 | 0.00 |
April | 0.624799E+09 | 0.340684E+09 | 0.417203E+09 | 0.159084E+09 | 0.258120E+09 | 0.00 | 0.00 |
May | 0.372479E+09 | 0.325694E+09 | 0.306983E+09 | 37778516.56 | 0.269205E+09 | 0.00 | 0.00 |
June | 0.315030E+09 | 0.246574E+09 | 0.260619E+09 | 15735218.78 | 0.244883E+09 | 0.00 | 0.00 |
July | 0.398711E+09 | 0.229619E+09 | 0.285269E+09 | 32113149.32 | 0.253156E+09 | 0.00 | 0.00 |
August | 0.592001E+09 | 0.238662E+09 | 0.366485E+09 | 0.115601E+09 | 0.250884E+09 | 0.00 | 0.00 |
September | 0.802533E+09 | 0.267363E+09 | 0.493514E+09 | 0.250080E+09 | 0.243433E+09 | 0.00 | 0.00 |
October | 0.105847E+10 | 0.302871E+09 | 0.648555E+09 | 0.433577E+09 | 0.214978E+09 | 0.00 | 0.00 |
November | 0.114268E+10 | 0.400447E+09 | 0.762826E+09 | 0.538543E+09 | 0.224282E+09 | 0.00 | 0.00 |
December | 0.133403E+10 | 0.442701E+09 | 0.879735E+09 | 0.669593E+09 | 0.210142E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.946247E+10 | 0.399023E+10 | 0.634521E+10 | 0.346547E+10 | 0.287974E+10 | 0.00 | 0.00 |
Minimum of Months | 0.315030E+09 | 0.229619E+09 | 0.260619E+09 | 15735218.78 | 0.210142E+09 | 0.00 | 0.00 |
Maximum of Months | 0.133403E+10 | 0.442701E+09 | 0.879735E+09 | 0.669593E+09 | 0.269205E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.22 | 9.61 | 5.99 | 2.23 | 0.81 | 45.19 | 208.20 | 0.00 |
February | 13.28 | 10.20 | 7.03 | 3.12 | 2.96 | 66.07 | 175.60 | 0.04 |
March | 12.64 | 10.61 | 8.97 | 2.93 | 3.55 | 84.90 | 179.28 | 0.03 |
April | 15.30 | 12.62 | 10.61 | 2.62 | 4.76 | 81.20 | 282.81 | 0.02 |
May | 15.56 | 12.65 | 10.56 | 2.92 | 6.17 | 105.80 | 234.18 | 0.01 |
June | 17.67 | 14.80 | 13.02 | 2.53 | 9.03 | 98.05 | 261.27 | 0.00 |
July | 19.43 | 16.76 | 15.28 | 2.35 | 9.62 | 86.54 | 312.15 | 0.00 |
August | 19.66 | 17.23 | 15.95 | 2.55 | 9.62 | 74.58 | 307.55 | 0.00 |
September | 18.47 | 15.50 | 13.65 | 2.19 | 8.99 | 70.75 | 240.05 | 0.00 |
October | 18.77 | 13.72 | 9.60 | 2.71 | 7.74 | 53.88 | 216.36 | 0.00 |
November | 14.32 | 10.43 | 6.22 | 2.47 | 2.41 | 50.75 | 207.87 | 0.01 |
December | 13.59 | 8.82 | 3.19 | 2.50 | 0.05 | 39.49 | 221.83 | 0.00 |
Annual Sum or Average | 16.01 | 12.76 | 10.02 | 2.59 | 5.49 | 71.44 | 237.65 | 0.01 |
Minimum of Months | 12.64 | 8.82 | 3.19 | 2.19 | 0.05 | 39.49 | 175.60 | 0.00 |
Maximum of Months | 19.66 | 17.23 | 15.95 | 3.12 | 9.62 | 105.80 | 312.15 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 26.00 | 13-JAN-13:00 | 15.46 | 8.00 | 3.10 | 11.84 | 120.00 | 725.00 |
February | 26.00 | 01-FEB-11:00 | 14.67 | 6.00 | 4.10 | 10.11 | 166.00 | 715.50 |
March | 24.00 | 11-MAR-10:00 | 13.82 | 6.00 | 2.60 | 8.15 | 120.00 | 907.00 |
April | 27.00 | 26-APR-12:00 | 17.13 | 11.00 | 4.10 | 12.22 | 159.00 | 884.00 |
May | 24.00 | 03-MAY-11:00 | 15.05 | 9.00 | 4.10 | 12.98 | 187.00 | 842.50 |
June | 25.00 | 29-JUN-10:00 | 19.59 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 28.00 | 19-JUL-10:00 | 20.49 | 17.00 | 3.60 | 14.65 | 173.00 | 813.00 |
August | 28.00 | 14-AUG-10:00 | 21.19 | 18.00 | 3.60 | 14.84 | 148.00 | 840.00 |
September | 36.00 | 29-SEP-10:00 | 17.91 | 5.00 | 3.60 | 19.35 | 159.50 | 790.00 |
October | 37.00 | 16-OCT-10:00 | 17.87 | 4.00 | 5.70 | 20.05 | 122.00 | 871.50 |
November | 27.00 | 19-NOV-12:00 | 14.96 | 6.00 | 4.10 | 11.07 | 128.50 | 796.00 |
December | 26.00 | 05-DEC-09:00 | 13.09 | 1.00 | 3.60 | 8.94 | 75.50 | 857.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.00 | 13.09 | 1.00 | 2.60 | 8.15 | 75.50 | 715.50 | |
Maximum of Months | 37.00 | 21.19 | 18.00 | 5.70 | 20.05 | 187.00 | 907.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.00 | 08-JAN-06:00 | -0.3 | -2.0 | 3.10 | -15.5 | 11.50 | 193.50 |
February | 5.00 | 04-FEB-05:00 | 0.22 | -8.0 | 4.10 | -10.9 | 0.00 | 0.00 |
March | 4.00 | 07-MAR-04:00 | 3.53 | 3.00 | 0.00 | -11.4 | 0.00 | 0.00 |
April | 7.00 | 01-APR-05:00 | 4.33 | 1.00 | 4.10 | -9.0 | 23.50 | 211.00 |
May | 8.00 | 14-MAY-03:00 | 7.45 | 7.00 | 1.50 | -6.6 | 0.00 | 0.00 |
June | 11.00 | 13-JUN-03:00 | 9.85 | 9.00 | 2.10 | -3.4 | 0.00 | 0.00 |
July | 13.00 | 06-JUL-00:00 | 13.00 | 13.00 | 0.00 | -0.6 | 0.00 | 0.00 |
August | 14.00 | 24-AUG-01:00 | 14.00 | 14.00 | 0.00 | 0.51 | 0.00 | 0.00 |
September | 11.00 | 20-SEP-02:00 | 9.85 | 9.00 | 1.50 | -3.4 | 0.00 | 0.00 |
October | 9.00 | 12-OCT-04:00 | 6.56 | 4.00 | 3.10 | -6.4 | 0.00 | 0.00 |
November | 7.00 | 05-NOV-01:00 | 5.54 | 4.00 | 3.10 | -8.3 | 0.00 | 0.00 |
December | 5.00 | 03-DEC-00:00 | 5.00 | 5.00 | 2.10 | -0.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | -0.3 | -8.0 | 0.00 | -15.5 | 0.00 | 0.00 | |
Maximum of Months | 14.00 | 14.00 | 14.00 | 4.10 | 0.51 | 23.50 | 211.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 17.04 | 17-JAN-11:00 | 24.00 | 13.00 | 3.10 | 12.79 | 223.50 | 9.00 |
February | 16.80 | 11-FEB-13:00 | 18.00 | 16.20 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 17.41 | 22-MAR-12:00 | 22.00 | 15.00 | 3.10 | 8.35 | 145.50 | 876.00 |
April | 18.33 | 26-APR-10:00 | 26.00 | 14.00 | 4.10 | 12.03 | 141.50 | 915.50 |
May | 16.69 | 05-MAY-14:00 | 18.00 | 16.00 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 19.59 | 29-JUN-10:00 | 25.00 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 21.19 | 19-JUL-11:00 | 28.00 | 18.00 | 4.60 | 14.84 | 182.50 | 808.00 |
August | 21.20 | 18-AUG-11:00 | 28.00 | 18.00 | 3.60 | 17.21 | 244.00 | 667.50 |
September | 21.85 | 22-SEP-11:00 | 26.00 | 20.00 | 2.60 | 20.05 | 284.00 | 21.00 |
October | 21.09 | 01-OCT-11:00 | 26.00 | 19.00 | 3.60 | 13.16 | 102.00 | 899.50 |
November | 16.52 | 10-NOV-12:00 | 21.00 | 14.00 | 5.10 | 7.15 | 131.00 | 808.50 |
December | 15.64 | 07-DEC-12:00 | 20.00 | 13.00 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.64 | 18.00 | 13.00 | 1.10 | 5.94 | 89.00 | 9.00 | |
Maximum of Months | 21.85 | 28.00 | 20.00 | 5.10 | 20.05 | 303.50 | 915.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 17-JAN-12:00 | 22.00 | 16.85 | 2.10 | 11.65 | 241.50 | 67.50 |
February | 16.20 | 11-FEB-13:00 | 18.00 | 16.80 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 15.00 | 23-MAR-15:20 | 21.67 | 17.34 | 3.77 | 8.02 | 112.00 | 809.83 |
April | 15.00 | 26-APR-21:19 | 16.00 | 15.39 | 2.23 | 6.15 | 0.00 | 0.00 |
May | 16.00 | 05-MAY-14:00 | 18.00 | 16.69 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 17.00 | 28-JUN-08:00 | 19.00 | 17.66 | 1.50 | 16.12 | 285.00 | 428.50 |
July | 18.00 | 18-JUL-10:00 | 26.00 | 20.47 | 4.60 | 12.79 | 169.00 | 819.00 |
August | 18.10 | 14-AUG-09:00 | 26.90 | 20.93 | 3.40 | 13.73 | 139.00 | 817.00 |
September | 20.00 | 22-SEP-09:00 | 22.00 | 20.55 | 1.50 | 16.30 | 296.00 | 18.00 |
October | 19.00 | 01-OCT-07:10 | 19.17 | 19.06 | 0.25 | 16.82 | 53.33 | 0.00 |
November | 15.00 | 10-NOV-17:19 | 16.67 | 15.62 | 2.77 | 3.34 | 0.00 | 0.00 |
December | 13.00 | 07-DEC-12:00 | 20.00 | 15.64 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.00 | 16.00 | 15.39 | 0.25 | 3.34 | 0.00 | 0.00 | |
Maximum of Months | 20.00 | 26.90 | 20.93 | 5.10 | 16.82 | 303.50 | 868.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 17.43 | 27.46 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 17.38 | 30.87 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 17.83 | 38.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 18.69 | 55.75 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 19.73 | 55.13 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.65 | 58.21 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.22 | 63.49 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 21.28 | 59.02 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.81 | 46.26 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.94 | 34.64 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.91 | 29.25 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 17.99 | 26.27 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.33 | 43.77 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 17.38 | 26.27 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 21.28 | 63.49 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.320603E+09 | -204060083.2 | 0.00 | 0.00 | 744.00 | 0.00 | -116542485.0 | 58.99 | 0.00 | 0.00 |
February | 0.290883E+09 | -185517194.3 | 0.00 | 0.00 | 672.00 | 0.00 | -105365778.4 | 58.99 | 0.00 | 0.00 |
March | 0.324223E+09 | -206490883.6 | 0.00 | 0.00 | 744.00 | 0.00 | -117732132.4 | 58.99 | 0.00 | 0.00 |
April | 0.303937E+09 | -193128853.6 | 0.00 | 0.00 | 720.00 | 0.00 | -110808446.2 | 58.99 | 0.00 | 0.00 |
May | 0.308905E+09 | -194775041.6 | 0.00 | 0.00 | 744.00 | 0.00 | -114130023.0 | 58.99 | 0.00 | 0.00 |
June | 0.295480E+09 | -185932851.2 | 0.00 | 0.00 | 720.00 | 0.00 | -109547351.2 | 58.99 | 0.00 | 0.00 |
July | 0.298077E+09 | -185412557.2 | 0.00 | 0.00 | 744.00 | 0.00 | -112664526.3 | 58.99 | 0.00 | 0.00 |
August | 0.301728E+09 | -189052209.9 | 0.00 | 0.00 | 744.00 | 0.00 | -112675923.5 | 58.99 | 0.00 | 0.00 |
September | 0.292379E+09 | -183139648.5 | 0.00 | 0.00 | 720.00 | 0.00 | -109239734.8 | 58.99 | 0.00 | 0.00 |
October | 0.304766E+09 | -191726736.7 | 0.00 | 0.00 | 744.00 | 0.00 | -113039105.7 | 58.99 | 0.00 | 0.00 |
November | 0.300745E+09 | -189927655.0 | 0.00 | 0.00 | 720.00 | 0.00 | -110817015.1 | 58.99 | 0.00 | 0.00 |
December | 0.317582E+09 | -201588997.3 | 0.00 | 0.00 | 744.00 | 0.00 | -115993134.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.365931E+10 | -0.231075E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.134856E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.290883E+09 | -206490883.6 | 0.00 | 0.00 | 672.00 | 0.00 | -117732132.4 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.324223E+09 | -183139648.5 | 0.00 | 0.00 | 744.00 | 0.00 | -105365778.4 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.318169E+09 | -204064442.5 | 0.00 | 0.00 | 744.00 | 0.00 | -114104973.0 | 58.99 | 0.00 | 0.00 |
February | 0.288529E+09 | -185515821.6 | 0.00 | 0.00 | 672.00 | 0.00 | -103013370.6 | 58.99 | 0.00 | 0.00 |
March | 0.321151E+09 | -206483931.9 | 0.00 | 0.00 | 744.00 | 0.00 | -114666590.7 | 58.99 | 0.00 | 0.00 |
April | 0.302816E+09 | -193125949.6 | 0.00 | 0.00 | 720.00 | 0.00 | -109690478.0 | 58.99 | 0.00 | 0.00 |
May | 0.307947E+09 | -194771643.7 | 0.00 | 0.00 | 744.00 | 0.00 | -113175123.1 | 58.99 | 0.00 | 0.00 |
June | 0.295007E+09 | -185932473.8 | 0.00 | 0.00 | 720.00 | 0.00 | -109074858.6 | 58.99 | 0.00 | 0.00 |
July | 0.297804E+09 | -185410655.1 | 0.00 | 0.00 | 744.00 | 0.00 | -112392898.0 | 58.99 | 0.00 | 0.00 |
August | 0.301410E+09 | -189052170.0 | 0.00 | 0.00 | 744.00 | 0.00 | -112358157.6 | 58.99 | 0.00 | 0.00 |
September | 0.292025E+09 | -183137534.2 | 0.00 | 0.00 | 720.00 | 0.00 | -108887680.3 | 58.99 | 0.00 | 0.00 |
October | 0.304390E+09 | -191721754.2 | 0.00 | 0.00 | 744.00 | 0.00 | -112667801.3 | 58.99 | 0.00 | 0.00 |
November | 0.299556E+09 | -189933257.7 | 0.00 | 0.00 | 720.00 | 0.00 | -109623012.7 | 58.99 | 0.00 | 0.00 |
December | 0.315357E+09 | -201583283.7 | 0.00 | 0.00 | 744.00 | 0.00 | -113773393.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.364416E+10 | -0.231073E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.133343E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.288529E+09 | -206483931.9 | 0.00 | 0.00 | 672.00 | 0.00 | -114666590.7 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.321151E+09 | -183137534.2 | 0.00 | 0.00 | 744.00 | 0.00 | -103013370.6 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.294153E+09 | -179429947.4 | 0.00 | 0.00 | 744.00 | 0.00 | -114723472.9 | 59.00 | 0.00 | 0.00 |
February | 0.266746E+09 | -163269906.4 | 0.00 | 0.00 | 672.00 | 0.00 | -103475858.8 | 58.99 | 0.00 | 0.00 |
March | 0.299622E+09 | -184257981.4 | 0.00 | 0.00 | 744.00 | 0.00 | -115364247.7 | 59.00 | 0.00 | 0.00 |
April | 0.279547E+09 | -169862266.8 | 0.00 | 0.00 | 720.00 | 0.00 | -109685020.3 | 58.99 | 0.00 | 0.00 |
May | 0.285801E+09 | -172724472.1 | 0.00 | 0.00 | 744.00 | 0.00 | -113076111.4 | 58.99 | 0.00 | 0.00 |
June | 0.274248E+09 | -165608430.0 | 0.00 | 0.00 | 720.00 | 0.00 | -108639706.1 | 58.99 | 0.00 | 0.00 |
July | 0.273659E+09 | -162112657.0 | 0.00 | 0.00 | 744.00 | 0.00 | -111546267.6 | 58.99 | 0.00 | 0.00 |
August | 0.280461E+09 | -168874191.3 | 0.00 | 0.00 | 744.00 | 0.00 | -111586772.6 | 58.99 | 0.00 | 0.00 |
September | 0.269208E+09 | -160960086.4 | 0.00 | 0.00 | 720.00 | 0.00 | -108247866.4 | 58.99 | 0.00 | 0.00 |
October | 0.280478E+09 | -168605049.0 | 0.00 | 0.00 | 744.00 | 0.00 | -111872478.8 | 58.99 | 0.00 | 0.00 |
November | 0.277403E+09 | -167674587.5 | 0.00 | 0.00 | 720.00 | 0.00 | -109728872.1 | 59.00 | 0.00 | 0.00 |
December | 0.290065E+09 | -175988597.6 | 0.00 | 0.00 | 744.00 | 0.00 | -114076251.4 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.337139E+10 | -0.203937E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.133202E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.266746E+09 | -184257981.4 | 0.00 | 0.00 | 672.00 | 0.00 | -115364247.7 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.299622E+09 | -160960086.4 | 0.00 | 0.00 | 744.00 | 0.00 | -103475858.8 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.294550E+09 | -179462988.0 | 0.00 | 0.00 | 744.00 | 0.00 | -115087138.2 | 58.99 | 0.00 | 0.00 |
February | 0.267077E+09 | -163262774.7 | 0.00 | 0.00 | 672.00 | 0.00 | -103814310.1 | 59.00 | 0.00 | 0.00 |
March | 0.300057E+09 | -184259984.0 | 0.00 | 0.00 | 744.00 | 0.00 | -115797271.7 | 59.00 | 0.00 | 0.00 |
April | 0.279765E+09 | -169871516.5 | 0.00 | 0.00 | 720.00 | 0.00 | -109893327.6 | 58.99 | 0.00 | 0.00 |
May | 0.285967E+09 | -172723005.3 | 0.00 | 0.00 | 744.00 | 0.00 | -113243675.6 | 58.99 | 0.00 | 0.00 |
June | 0.274349E+09 | -165600413.5 | 0.00 | 0.00 | 720.00 | 0.00 | -108749059.3 | 58.99 | 0.00 | 0.00 |
July | 0.273726E+09 | -162099801.7 | 0.00 | 0.00 | 744.00 | 0.00 | -111626398.5 | 58.99 | 0.00 | 0.00 |
August | 0.280516E+09 | -168845368.7 | 0.00 | 0.00 | 744.00 | 0.00 | -111670428.8 | 58.99 | 0.00 | 0.00 |
September | 0.269303E+09 | -160946356.5 | 0.00 | 0.00 | 720.00 | 0.00 | -108356400.2 | 59.00 | 0.00 | 0.00 |
October | 0.280540E+09 | -168618387.6 | 0.00 | 0.00 | 744.00 | 0.00 | -111921933.2 | 58.99 | 0.00 | 0.00 |
November | 0.277590E+09 | -167681732.4 | 0.00 | 0.00 | 720.00 | 0.00 | -109908065.4 | 59.00 | 0.00 | 0.00 |
December | 0.290363E+09 | -175975847.3 | 0.00 | 0.00 | 744.00 | 0.00 | -114387256.4 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.337380E+10 | -0.203935E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.133446E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.267077E+09 | -184259984.0 | 0.00 | 0.00 | 672.00 | 0.00 | -115797271.7 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.300057E+09 | -160946356.5 | 0.00 | 0.00 | 744.00 | 0.00 | -103814310.1 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.286562E+09 | -169621564.2 | 0.00 | 0.00 | 744.00 | 0.00 | -116939974.3 | 58.99 | 0.00 | 0.00 |
February | 0.260198E+09 | -154399130.3 | 0.00 | 0.00 | 672.00 | 0.00 | -105799359.7 | 58.99 | 0.00 | 0.00 |
March | 0.292600E+09 | -174392313.0 | 0.00 | 0.00 | 744.00 | 0.00 | -118207965.0 | 58.98 | 0.00 | 0.00 |
April | 0.271854E+09 | -160743881.9 | 0.00 | 0.00 | 720.00 | 0.00 | -111109985.8 | 58.99 | 0.00 | 0.00 |
May | 0.277639E+09 | -163357195.4 | 0.00 | 0.00 | 744.00 | 0.00 | -114281775.2 | 58.99 | 0.00 | 0.00 |
June | 0.266136E+09 | -156702186.5 | 0.00 | 0.00 | 720.00 | 0.00 | -109433557.4 | 58.99 | 0.00 | 0.00 |
July | 0.265550E+09 | -153314961.0 | 0.00 | 0.00 | 744.00 | 0.00 | -112235285.2 | 58.99 | 0.00 | 0.00 |
August | 0.272040E+09 | -159781730.7 | 0.00 | 0.00 | 744.00 | 0.00 | -112257987.7 | 58.99 | 0.00 | 0.00 |
September | 0.261301E+09 | -152322534.0 | 0.00 | 0.00 | 720.00 | 0.00 | -108978182.9 | 58.99 | 0.00 | 0.00 |
October | 0.271940E+09 | -159364374.5 | 0.00 | 0.00 | 744.00 | 0.00 | -112575397.5 | 58.99 | 0.00 | 0.00 |
November | 0.269441E+09 | -158380042.1 | 0.00 | 0.00 | 720.00 | 0.00 | -111060982.2 | 59.00 | 0.00 | 0.00 |
December | 0.282543E+09 | -166414877.6 | 0.00 | 0.00 | 744.00 | 0.00 | -116128380.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.327780E+10 | -0.192879E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.134901E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.260198E+09 | -174392313.0 | 0.00 | 0.00 | 672.00 | 0.00 | -118207965.0 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.292600E+09 | -152322534.0 | 0.00 | 0.00 | 744.00 | 0.00 | -105799359.7 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.285924E+09 | -169578304.4 | 0.00 | 0.00 | 744.00 | 0.00 | -116345910.4 | 59.00 | 0.00 | 0.00 |
February | 0.259413E+09 | -154415076.4 | 0.00 | 0.00 | 672.00 | 0.00 | -104998109.2 | 58.98 | 0.00 | 0.00 |
March | 0.291730E+09 | -174359164.1 | 0.00 | 0.00 | 744.00 | 0.00 | -117370906.0 | 59.00 | 0.00 | 0.00 |
April | 0.271451E+09 | -160728605.1 | 0.00 | 0.00 | 720.00 | 0.00 | -110722843.3 | 58.99 | 0.00 | 0.00 |
May | 0.277301E+09 | -163350479.8 | 0.00 | 0.00 | 744.00 | 0.00 | -113950250.8 | 58.99 | 0.00 | 0.00 |
June | 0.266042E+09 | -156692320.1 | 0.00 | 0.00 | 720.00 | 0.00 | -109349880.6 | 58.99 | 0.00 | 0.00 |
July | 0.265501E+09 | -153311291.7 | 0.00 | 0.00 | 744.00 | 0.00 | -112189845.7 | 58.99 | 0.00 | 0.00 |
August | 0.272023E+09 | -159773309.2 | 0.00 | 0.00 | 744.00 | 0.00 | -112249359.7 | 58.99 | 0.00 | 0.00 |
September | 0.261227E+09 | -152308500.2 | 0.00 | 0.00 | 720.00 | 0.00 | -108918265.2 | 58.99 | 0.00 | 0.00 |
October | 0.271876E+09 | -159370967.1 | 0.00 | 0.00 | 744.00 | 0.00 | -112504836.3 | 58.99 | 0.00 | 0.00 |
November | 0.268972E+09 | -158380288.4 | 0.00 | 0.00 | 720.00 | 0.00 | -110592074.1 | 58.99 | 0.00 | 0.00 |
December | 0.281899E+09 | -166415457.9 | 0.00 | 0.00 | 744.00 | 0.00 | -115483735.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.327336E+10 | -0.192868E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.134468E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.259413E+09 | -174359164.1 | 0.00 | 0.00 | 672.00 | 0.00 | -117370906.0 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.291730E+09 | -152308500.2 | 0.00 | 0.00 | 744.00 | 0.00 | -104998109.2 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.286014E+09 | -169583124.4 | 0.00 | 0.00 | 744.00 | 0.00 | -116430481.4 | 59.00 | 0.00 | 0.00 |
February | 0.259510E+09 | -154401326.1 | 0.00 | 0.00 | 672.00 | 0.00 | -105108947.6 | 58.99 | 0.00 | 0.00 |
March | 0.291830E+09 | -174388018.4 | 0.00 | 0.00 | 744.00 | 0.00 | -117442067.7 | 58.99 | 0.00 | 0.00 |
April | 0.271522E+09 | -160732881.2 | 0.00 | 0.00 | 720.00 | 0.00 | -110789489.6 | 58.99 | 0.00 | 0.00 |
May | 0.277370E+09 | -163346144.4 | 0.00 | 0.00 | 744.00 | 0.00 | -114023914.6 | 58.99 | 0.00 | 0.00 |
June | 0.266095E+09 | -156704922.6 | 0.00 | 0.00 | 720.00 | 0.00 | -109390482.1 | 58.99 | 0.00 | 0.00 |
July | 0.265569E+09 | -153316673.4 | 0.00 | 0.00 | 744.00 | 0.00 | -112251890.8 | 58.99 | 0.00 | 0.00 |
August | 0.272069E+09 | -159778813.5 | 0.00 | 0.00 | 744.00 | 0.00 | -112290589.2 | 58.99 | 0.00 | 0.00 |
September | 0.261287E+09 | -152319270.6 | 0.00 | 0.00 | 720.00 | 0.00 | -108968211.3 | 58.99 | 0.00 | 0.00 |
October | 0.271932E+09 | -159357374.6 | 0.00 | 0.00 | 744.00 | 0.00 | -112574386.4 | 58.99 | 0.00 | 0.00 |
November | 0.269035E+09 | -158398648.7 | 0.00 | 0.00 | 720.00 | 0.00 | -110636183.6 | 58.99 | 0.00 | 0.00 |
December | 0.281987E+09 | -166437579.2 | 0.00 | 0.00 | 744.00 | 0.00 | -115549050.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.327422E+10 | -0.192876E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.134546E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.259510E+09 | -174388018.4 | 0.00 | 0.00 | 672.00 | 0.00 | -117442067.7 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.291830E+09 | -152319270.6 | 0.00 | 0.00 | 744.00 | 0.00 | -105108947.6 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 293.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 279.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 338.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 358.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 393.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 381.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 408.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 390.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 328.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 296.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 300.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 297.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4065.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 279.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 408.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 83355927.46 | 6618.38 | 03-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 55115621.84 | 3386.02 | 10-FEB-09:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.292429E+09 | 33363.93 | 30-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1429403.95 | 2710.26 | 01-APR-08:65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17886741.31 | 2567.08 | 13-DEC-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.450217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.292429E+09 | 33363.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2829215.10 | 1113.06 | 29-MAR-11:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2829215.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2829215.10 | 1113.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 8228666.11 | 1878.57 | 03-JAN-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 18798616.72 | 3233.34 | 30-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 27027282.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18798616.72 | 3233.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 17972289.06 | 3218.98 | 03-JAN-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 28209054.45 | 3169.13 | 30-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 46181343.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28209054.45 | 3218.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 29735886.51 | 2667.99 | 03-JAN-08:65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 47911327.74 | 3161.99 | 30-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 660549.06 | 737.70 | 01-APR-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 78307763.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 47911327.74 | 3161.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.163905E+09 | 24235.54 | 02-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 71893646.43 | 3464.57 | 28-FEB-09:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.287893E+09 | 32065.33 | 30-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1368660.47 | 2519.30 | 01-APR-08:65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11911008.68 | 1920.93 | 13-DEC-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.536972E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.287893E+09 | 32065.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 39206176.13 | 5545.46 | 02-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3155283.20 | 808.70 | 28-FEB-09:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 53378961.14 | 7155.14 | 30-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95740420.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 53378961.14 | 7155.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 43086386.91 | 6754.56 | 02-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4309308.65 | 957.99 | 28-FEB-09:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 58597605.38 | 8448.94 | 30-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105993E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 58597605.38 | 8448.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 58034463.11 | 11278.44 | 02-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 15163398.20 | 1604.13 | 27-FEB-09:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 95693067.09 | 15407.30 | 30-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 224822.07 | 332.42 | 01-APR-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 206223.18 | 308.78 | 13-DEC-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169322E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 95693067.09 | 15407.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 97988069.35 | 22141.29 | 02-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 95555747.69 | 11309.12 | 27-FEB-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.227444E+09 | 28006.44 | 30-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1812144.59 | 6040.48 | 01-APR-08:65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17443405.70 | 3438.05 | 13-DEC-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.440243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.227444E+09 | 28006.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.115912E+10 | 0.108427E+10 | 10611.04 | 18-JAN-13:10 | 10611.04 | 0.00 |
February | 0.00 | 0.00 | 0.284439E+09 | 0.272304E+09 | 8236.29 | 01-FEB-12:10 | 8236.29 | 0.00 |
March | 0.00 | 0.00 | 0.601357E+09 | 0.490535E+09 | 9906.97 | 23-MAR-14:00 | 7529.08 | 0.00 |
April | 0.00 | 0.00 | 0.218486E+10 | 0.177415E+10 | 24111.28 | 27-APR-08:62 | 14961.29 | 0.00 |
May | 0.00 | 0.00 | 0.184849E+10 | 0.150163E+10 | 28846.65 | 03-MAY-08:62 | 19562.21 | 0.00 |
June | 0.00 | 0.00 | 0.537833E+10 | 0.392163E+10 | 35036.85 | 30-JUN-08:62 | 22419.97 | 0.00 |
July | 0.00 | 0.00 | 0.118412E+11 | 0.802966E+10 | 35885.67 | 19-JUL-08:62 | 22546.30 | 0.00 |
August | 0.00 | 0.00 | 0.129082E+11 | 0.858150E+10 | 36154.53 | 14-AUG-08:62 | 22385.60 | 0.00 |
September | 0.00 | 0.00 | 0.770036E+10 | 0.567110E+10 | 36345.85 | 22-SEP-08:62 | 18369.02 | 0.00 |
October | 0.00 | 0.00 | 0.894533E+10 | 0.732390E+10 | 35894.94 | 01-OCT-07:03 | 17383.01 | 0.00 |
November | 0.00 | 0.00 | 0.116331E+10 | 0.110309E+10 | 12752.35 | 19-NOV-13:10 | 12752.35 | 0.00 |
December | 0.00 | 0.00 | 0.144033E+10 | 0.142434E+10 | 25755.74 | 05-DEC-09:02 | 25755.74 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.554553E+11 | 0.411781E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.284439E+09 | 0.272304E+09 | 8236.29 | 7529.08 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.129082E+11 | 0.858150E+10 | 36345.85 | 25755.74 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.798982E+09 | 0.764891E+09 | 17398.61 | 20-JAN-09:02 | 12888.59 | 0.00 |
February | 0.00 | 0.00 | 0.218442E+09 | 0.212460E+09 | 16642.51 | 05-FEB-18:10 | 16471.12 | 0.00 |
March | 0.00 | 0.00 | 0.407820E+09 | 0.353500E+09 | 6062.90 | 23-MAR-14:00 | 4845.36 | 0.00 |
April | 0.00 | 0.00 | 0.124789E+10 | 0.107823E+10 | 17965.00 | 26-APR-08:62 | 14382.34 | 0.00 |
May | 0.00 | 0.00 | 0.944974E+09 | 0.815627E+09 | 17904.28 | 03-MAY-08:62 | 12412.07 | 0.00 |
June | 0.00 | 0.00 | 0.281787E+10 | 0.217590E+10 | 18346.27 | 30-JUN-08:62 | 11895.66 | 0.00 |
July | 0.00 | 0.00 | 0.644672E+10 | 0.462089E+10 | 18773.27 | 19-JUL-08:62 | 12010.05 | 0.00 |
August | 0.00 | 0.00 | 0.700308E+10 | 0.493366E+10 | 18921.75 | 14-AUG-08:62 | 11898.41 | 0.00 |
September | 0.00 | 0.00 | 0.400270E+10 | 0.308417E+10 | 18849.38 | 22-SEP-08:62 | 10449.69 | 0.00 |
October | 0.00 | 0.00 | 0.514867E+10 | 0.434819E+10 | 18748.95 | 04-OCT-20:02 | 10223.43 | 0.00 |
November | 0.00 | 0.00 | 0.762803E+09 | 0.737114E+09 | 17667.97 | 10-NOV-09:02 | 12660.97 | 0.00 |
December | 0.00 | 0.00 | 0.103371E+10 | 0.102544E+10 | 16877.31 | 05-DEC-09:02 | 16877.31 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.308337E+11 | 0.241501E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.218442E+09 | 0.212460E+09 | 6062.90 | 4845.36 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.700308E+10 | 0.493366E+10 | 18921.75 | 16877.31 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.698388E+09 | 0.673027E+09 | 14282.02 | 21-JAN-08:62 | 8421.42 | 0.00 |
February | 0.00 | 0.00 | 0.167331E+09 | 0.166047E+09 | 5497.30 | 01-FEB-12:10 | 5497.30 | 0.00 |
March | 0.00 | 0.00 | 0.338941E+09 | 0.296753E+09 | 5580.53 | 23-MAR-14:00 | 4463.62 | 0.00 |
April | 0.00 | 0.00 | 0.102751E+10 | 0.893719E+09 | 17622.13 | 27-APR-07:03 | 10823.87 | 0.00 |
May | 0.00 | 0.00 | 0.752767E+09 | 0.652850E+09 | 17696.32 | 03-MAY-07:03 | 11486.26 | 0.00 |
June | 0.00 | 0.00 | 0.249811E+10 | 0.193328E+10 | 18133.31 | 30-JUN-07:02 | 10759.22 | 0.00 |
July | 0.00 | 0.00 | 0.545236E+10 | 0.395348E+10 | 18680.97 | 23-JUL-08:62 | 12492.19 | 0.00 |
August | 0.00 | 0.00 | 0.616166E+10 | 0.437926E+10 | 18669.30 | 19-AUG-07:02 | 10295.72 | 0.00 |
September | 0.00 | 0.00 | 0.339181E+10 | 0.264089E+10 | 18600.98 | 22-SEP-07:02 | 9746.29 | 0.00 |
October | 0.00 | 0.00 | 0.423917E+10 | 0.364029E+10 | 18696.71 | 05-OCT-07:02 | 10080.13 | 0.00 |
November | 0.00 | 0.00 | 0.644741E+09 | 0.629596E+09 | 16992.10 | 19-NOV-09:02 | 16992.10 | 0.00 |
December | 0.00 | 0.00 | 0.910243E+09 | 0.904999E+09 | 7684.20 | 05-DEC-08:63 | 7684.20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.262830E+11 | 0.207642E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.167331E+09 | 0.166047E+09 | 5497.30 | 4463.62 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.616166E+10 | 0.437926E+10 | 18696.71 | 16992.10 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.669906E+09 | 0.646421E+09 | 12868.26 | 21-JAN-08:62 | 7596.29 | 0.00 |
February | 0.00 | 0.00 | 0.158926E+09 | 0.157972E+09 | 5375.76 | 01-FEB-12:10 | 5375.76 | 0.00 |
March | 0.00 | 0.00 | 0.318795E+09 | 0.279329E+09 | 5473.85 | 23-MAR-14:00 | 4377.51 | 0.00 |
April | 0.00 | 0.00 | 0.978378E+09 | 0.851224E+09 | 17667.67 | 27-APR-07:03 | 10842.26 | 0.00 |
May | 0.00 | 0.00 | 0.711514E+09 | 0.617804E+09 | 17742.68 | 03-MAY-07:03 | 11506.54 | 0.00 |
June | 0.00 | 0.00 | 0.244016E+10 | 0.188779E+10 | 18182.24 | 30-JUN-07:02 | 10780.56 | 0.00 |
July | 0.00 | 0.00 | 0.539416E+10 | 0.391056E+10 | 18731.56 | 23-JUL-08:62 | 12522.62 | 0.00 |
August | 0.00 | 0.00 | 0.610566E+10 | 0.433940E+10 | 18720.14 | 19-AUG-07:02 | 10319.95 | 0.00 |
September | 0.00 | 0.00 | 0.333344E+10 | 0.259798E+10 | 18650.64 | 22-SEP-07:02 | 9768.02 | 0.00 |
October | 0.00 | 0.00 | 0.420427E+10 | 0.361073E+10 | 18748.09 | 05-OCT-07:02 | 10107.52 | 0.00 |
November | 0.00 | 0.00 | 0.619839E+09 | 0.606227E+09 | 17032.87 | 19-NOV-09:02 | 17032.87 | 0.00 |
December | 0.00 | 0.00 | 0.863947E+09 | 0.859006E+09 | 6544.75 | 05-DEC-08:63 | 6544.75 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.257990E+11 | 0.203645E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.158926E+09 | 0.157972E+09 | 5375.76 | 4377.51 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.610566E+10 | 0.433940E+10 | 18748.09 | 17032.87 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.616653E+09 | 0.596055E+09 | 9805.17 | 21-JAN-08:62 | 5811.03 | 0.00 |
February | 0.00 | 0.00 | 0.142966E+09 | 0.142384E+09 | 5105.38 | 01-FEB-12:10 | 5105.38 | 0.00 |
March | 0.00 | 0.00 | 0.280945E+09 | 0.246337E+09 | 5239.35 | 23-MAR-14:00 | 4187.42 | 0.00 |
April | 0.00 | 0.00 | 0.894922E+09 | 0.779020E+09 | 15490.90 | 27-APR-07:03 | 9511.82 | 0.00 |
May | 0.00 | 0.00 | 0.639619E+09 | 0.556237E+09 | 17513.77 | 03-MAY-07:03 | 11332.67 | 0.00 |
June | 0.00 | 0.00 | 0.230758E+10 | 0.178350E+10 | 18105.79 | 30-JUN-07:02 | 10704.80 | 0.00 |
July | 0.00 | 0.00 | 0.520259E+10 | 0.376865E+10 | 18652.80 | 23-JUL-08:62 | 12440.78 | 0.00 |
August | 0.00 | 0.00 | 0.590681E+10 | 0.419612E+10 | 18641.99 | 19-AUG-07:02 | 10245.77 | 0.00 |
September | 0.00 | 0.00 | 0.318582E+10 | 0.248804E+10 | 18571.02 | 22-SEP-07:02 | 9698.14 | 0.00 |
October | 0.00 | 0.00 | 0.405862E+10 | 0.348998E+10 | 18670.02 | 05-OCT-07:02 | 10034.91 | 0.00 |
November | 0.00 | 0.00 | 0.575455E+09 | 0.564169E+09 | 16953.87 | 19-NOV-09:02 | 16953.87 | 0.00 |
December | 0.00 | 0.00 | 0.783736E+09 | 0.779341E+09 | 6177.04 | 19-DEC-13:10 | 6177.04 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.245957E+11 | 0.193898E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.142966E+09 | 0.142384E+09 | 5105.38 | 4187.42 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.590681E+10 | 0.419612E+10 | 18670.02 | 16953.87 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.960330E+09 | 0.902157E+09 | 9923.86 | 18-JAN-13:10 | 9923.86 | 0.00 |
February | 0.00 | 0.00 | 0.257013E+09 | 0.249962E+09 | 7739.81 | 01-FEB-12:10 | 7739.81 | 0.00 |
March | 0.00 | 0.00 | 0.494112E+09 | 0.408462E+09 | 9230.19 | 23-MAR-14:10 | 6905.08 | 0.00 |
April | 0.00 | 0.00 | 0.167854E+10 | 0.137046E+10 | 16927.26 | 27-APR-08:62 | 10481.02 | 0.00 |
May | 0.00 | 0.00 | 0.136195E+10 | 0.111526E+10 | 23620.29 | 03-MAY-08:62 | 15901.01 | 0.00 |
June | 0.00 | 0.00 | 0.424864E+10 | 0.311668E+10 | 33721.74 | 30-JUN-08:62 | 22194.95 | 0.00 |
July | 0.00 | 0.00 | 0.913406E+10 | 0.625352E+10 | 34980.70 | 30-JUL-09:02 | 21540.10 | 0.00 |
August | 0.00 | 0.00 | 0.102679E+11 | 0.690433E+10 | 34941.38 | 14-AUG-08:62 | 21621.83 | 0.00 |
September | 0.00 | 0.00 | 0.608288E+10 | 0.453181E+10 | 34972.64 | 22-SEP-08:62 | 18309.24 | 0.00 |
October | 0.00 | 0.00 | 0.717591E+10 | 0.597187E+10 | 34735.44 | 01-OCT-09:02 | 20126.97 | 0.00 |
November | 0.00 | 0.00 | 0.971888E+09 | 0.929127E+09 | 31935.35 | 19-NOV-10:02 | 31935.35 | 0.00 |
December | 0.00 | 0.00 | 0.124740E+10 | 0.123234E+10 | 16999.67 | 05-DEC-09:02 | 16999.67 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.438806E+11 | 0.329860E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.257013E+09 | 0.249962E+09 | 7739.81 | 6905.08 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.102679E+11 | 0.690433E+10 | 34980.70 | 31935.35 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.555145E+09 | 0.536136E+09 | 9339.10 | 20-JAN-09:02 | 7013.50 | 0.00 |
February | 0.00 | 0.00 | 0.127930E+09 | 0.127394E+09 | 4790.38 | 01-FEB-12:10 | 4790.38 | 0.00 |
March | 0.00 | 0.00 | 0.249501E+09 | 0.217761E+09 | 5101.94 | 23-MAR-14:10 | 4012.20 | 0.00 |
April | 0.00 | 0.00 | 0.833944E+09 | 0.721171E+09 | 17209.95 | 27-APR-08:62 | 11010.06 | 0.00 |
May | 0.00 | 0.00 | 0.588868E+09 | 0.511146E+09 | 17324.07 | 03-MAY-08:62 | 11907.45 | 0.00 |
June | 0.00 | 0.00 | 0.214331E+10 | 0.165092E+10 | 17677.91 | 30-JUN-08:62 | 11727.32 | 0.00 |
July | 0.00 | 0.00 | 0.486490E+10 | 0.350115E+10 | 18347.01 | 30-JUL-09:02 | 11356.27 | 0.00 |
August | 0.00 | 0.00 | 0.551650E+10 | 0.390187E+10 | 18317.01 | 14-AUG-08:62 | 11435.25 | 0.00 |
September | 0.00 | 0.00 | 0.300743E+10 | 0.234462E+10 | 18338.56 | 22-SEP-08:62 | 9675.27 | 0.00 |
October | 0.00 | 0.00 | 0.377156E+10 | 0.324329E+10 | 18211.75 | 01-OCT-09:02 | 10635.04 | 0.00 |
November | 0.00 | 0.00 | 0.518536E+09 | 0.508556E+09 | 16793.11 | 19-NOV-10:02 | 16793.11 | 0.00 |
December | 0.00 | 0.00 | 0.694052E+09 | 0.689893E+09 | 16313.54 | 05-DEC-09:02 | 16313.54 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.228717E+11 | 0.179539E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.127930E+09 | 0.127394E+09 | 4790.38 | 4012.20 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.551650E+10 | 0.390187E+10 | 18347.01 | 16793.11 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.543384E+09 | 0.525111E+09 | 8397.35 | 20-JAN-09:02 | 6304.98 | 0.00 |
February | 0.00 | 0.00 | 0.125053E+09 | 0.124540E+09 | 4736.88 | 01-FEB-12:10 | 4736.88 | 0.00 |
March | 0.00 | 0.00 | 0.243903E+09 | 0.212930E+09 | 5041.49 | 23-MAR-14:10 | 3963.59 | 0.00 |
April | 0.00 | 0.00 | 0.815828E+09 | 0.705466E+09 | 16698.06 | 27-APR-08:62 | 10678.78 | 0.00 |
May | 0.00 | 0.00 | 0.571308E+09 | 0.495981E+09 | 17252.32 | 03-MAY-08:62 | 11845.46 | 0.00 |
June | 0.00 | 0.00 | 0.210069E+10 | 0.161731E+10 | 17605.23 | 30-JUN-08:62 | 11664.56 | 0.00 |
July | 0.00 | 0.00 | 0.480074E+10 | 0.345315E+10 | 18271.48 | 30-JUL-09:02 | 11297.26 | 0.00 |
August | 0.00 | 0.00 | 0.544983E+10 | 0.385296E+10 | 18241.60 | 14-AUG-08:62 | 11375.86 | 0.00 |
September | 0.00 | 0.00 | 0.295894E+10 | 0.230804E+10 | 18262.33 | 22-SEP-08:62 | 9626.26 | 0.00 |
October | 0.00 | 0.00 | 0.372157E+10 | 0.320150E+10 | 18136.71 | 01-OCT-09:02 | 10580.74 | 0.00 |
November | 0.00 | 0.00 | 0.507801E+09 | 0.498375E+09 | 16716.71 | 19-NOV-10:02 | 16716.71 | 0.00 |
December | 0.00 | 0.00 | 0.676079E+09 | 0.672062E+09 | 15965.18 | 05-DEC-09:02 | 15965.18 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.225151E+11 | 0.176674E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.125053E+09 | 0.124540E+09 | 4736.88 | 3963.59 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.544983E+10 | 0.385296E+10 | 18271.48 | 16716.71 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.492733E+09 | 0.477599E+09 | 5583.53 | 14-JAN-15:00 | 5583.53 | 0.00 |
February | 0.00 | 0.00 | 0.110064E+09 | 0.109688E+09 | 4473.10 | 01-FEB-12:10 | 4473.10 | 0.00 |
March | 0.00 | 0.00 | 0.217012E+09 | 0.190070E+09 | 4770.03 | 23-MAR-14:10 | 3753.83 | 0.00 |
April | 0.00 | 0.00 | 0.744733E+09 | 0.645197E+09 | 10858.34 | 27-APR-08:62 | 7019.45 | 0.00 |
May | 0.00 | 0.00 | 0.506818E+09 | 0.441473E+09 | 15390.81 | 03-MAY-08:62 | 10574.07 | 0.00 |
June | 0.00 | 0.00 | 0.196452E+10 | 0.151296E+10 | 17533.99 | 30-JUN-08:62 | 11583.30 | 0.00 |
July | 0.00 | 0.00 | 0.463047E+10 | 0.333228E+10 | 18197.36 | 30-JUL-09:02 | 11225.50 | 0.00 |
August | 0.00 | 0.00 | 0.527716E+10 | 0.373356E+10 | 18167.25 | 14-AUG-08:62 | 11301.68 | 0.00 |
September | 0.00 | 0.00 | 0.280700E+10 | 0.219818E+10 | 18185.46 | 22-SEP-08:62 | 9562.94 | 0.00 |
October | 0.00 | 0.00 | 0.356796E+10 | 0.307645E+10 | 18063.63 | 01-OCT-09:02 | 10517.44 | 0.00 |
November | 0.00 | 0.00 | 0.461105E+09 | 0.453705E+09 | 16617.45 | 19-NOV-10:02 | 16617.45 | 0.00 |
December | 0.00 | 0.00 | 0.599325E+09 | 0.595873E+09 | 11176.55 | 05-DEC-09:02 | 11176.55 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.213789E+11 | 0.167670E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.110064E+09 | 0.109688E+09 | 4473.10 | 3753.83 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.527716E+10 | 0.373356E+10 | 18197.36 | 16617.45 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.460797E+09 | 0.448054E+09 | 5593.44 | 18-JAN-13:10 | 5593.44 | 0.00 |
February | 0.00 | 0.00 | 98315933.15 | 98028196.74 | 4679.08 | 01-FEB-12:10 | 4679.08 | 0.00 |
March | 0.00 | 0.00 | 0.219541E+09 | 0.192738E+09 | 4781.63 | 23-MAR-14:10 | 3752.93 | 0.00 |
April | 0.00 | 0.00 | 0.789225E+09 | 0.684871E+09 | 7348.23 | 26-APR-13:00 | 6817.30 | 0.00 |
May | 0.00 | 0.00 | 0.518317E+09 | 0.452207E+09 | 6382.56 | 04-MAY-08:62 | 4996.38 | 0.00 |
June | 0.00 | 0.00 | 0.203496E+10 | 0.157060E+10 | 18974.86 | 30-JUN-08:62 | 12442.62 | 0.00 |
July | 0.00 | 0.00 | 0.497359E+10 | 0.359684E+10 | 19687.48 | 30-JUL-09:02 | 12120.54 | 0.00 |
August | 0.00 | 0.00 | 0.566140E+10 | 0.402404E+10 | 19656.43 | 14-AUG-08:62 | 12192.25 | 0.00 |
September | 0.00 | 0.00 | 0.281852E+10 | 0.222615E+10 | 19678.51 | 22-SEP-08:62 | 10254.76 | 0.00 |
October | 0.00 | 0.00 | 0.354293E+10 | 0.309021E+10 | 19544.52 | 01-OCT-09:02 | 11280.31 | 0.00 |
November | 0.00 | 0.00 | 0.429915E+09 | 0.425336E+09 | 17860.04 | 19-NOV-10:02 | 17860.04 | 0.00 |
December | 0.00 | 0.00 | 0.537070E+09 | 0.534387E+09 | 5723.97 | 19-DEC-13:10 | 5723.97 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.220846E+11 | 0.173435E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 98315933.15 | 98028196.74 | 4679.08 | 3752.93 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.566140E+10 | 0.402404E+10 | 19687.48 | 17860.04 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.148984E+10 | 0.37 | 978.29 | 03-JAN-09:02 | 0.61 |
February | 0.134746E+10 | 0.37 | 900.99 | 10-FEB-09:15 | 0.57 |
March | 0.150074E+10 | 0.37 | 1617.85 | 30-MAR-08:62 | 0.80 |
April | 0.144071E+10 | 0.36 | 1336.12 | 27-APR-08:62 | 0.72 |
May | 0.148802E+10 | 0.36 | 1666.62 | 03-MAY-08:62 | 0.80 |
June | 0.144792E+10 | 0.37 | 2050.05 | 19-JUN-08:62 | 0.88 |
July | 0.149153E+10 | 0.36 | 2050.05 | 01-JUL-08:62 | 0.88 |
August | 0.149489E+10 | 0.36 | 2050.05 | 01-AUG-08:62 | 0.88 |
September | 0.145723E+10 | 0.37 | 2050.05 | 06-SEP-08:62 | 0.88 |
October | 0.150624E+10 | 0.37 | 2050.05 | 01-OCT-07:03 | 0.88 |
November | 0.143766E+10 | 0.36 | 820.02 | 09-NOV-14:10 | 0.54 |
December | 0.149427E+10 | 0.37 | 1563.50 | 05-DEC-09:02 | 0.79 |
Annual Sum or Average | 0.175965E+11 | 0.37 | |||
Minimum of Months | 0.134746E+10 | 0.36 | 820.02 | 0.54 | |
Maximum of Months | 0.150624E+10 | 0.37 | 2050.05 | 0.88 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.178602E+10 | 0.62 | 1114.88 | 07-JAN-11:30 | 0.93 |
February | 0.160622E+10 | 0.62 | 1114.88 | 01-FEB-08:65 | 0.92 |
March | 0.175788E+10 | 0.61 | 1114.88 | 01-MAR-08:65 | 0.92 |
April | 0.188057E+10 | 0.62 | 1114.88 | 01-APR-07:05 | 0.92 |
May | 0.195152E+10 | 0.62 | 1114.88 | 01-MAY-07:03 | 0.91 |
June | 0.195077E+10 | 0.62 | 1114.88 | 01-JUN-07:03 | 0.92 |
July | 0.195799E+10 | 0.61 | 1114.88 | 01-JUL-07:02 | 0.91 |
August | 0.198395E+10 | 0.61 | 1114.88 | 01-AUG-07:02 | 0.91 |
September | 0.191152E+10 | 0.62 | 1114.88 | 01-SEP-07:03 | 0.91 |
October | 0.192889E+10 | 0.61 | 1114.88 | 01-OCT-07:03 | 0.91 |
November | 0.183649E+10 | 0.62 | 1114.88 | 01-NOV-07:03 | 0.92 |
December | 0.179987E+10 | 0.63 | 1114.88 | 01-DEC-08:65 | 0.92 |
Annual Sum or Average | 0.223517E+11 | 0.62 | |||
Minimum of Months | 0.160622E+10 | 0.61 | 1114.88 | 0.91 | |
Maximum of Months | 0.198395E+10 | 0.63 | 1114.88 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.160879E+10 | 0.50 | 1111.66 | 02-JAN-21:00 | 0.92 |
February | 0.145672E+10 | 0.50 | 1111.66 | 01-FEB-09:07 | 0.92 |
March | 0.164081E+10 | 0.51 | 1111.66 | 01-MAR-12:00 | 0.92 |
April | 0.156077E+10 | 0.50 | 1111.66 | 01-APR-11:30 | 0.92 |
May | 0.162480E+10 | 0.50 | 1111.66 | 01-MAY-10:30 | 0.92 |
June | 0.158478E+10 | 0.50 | 1111.66 | 01-JUN-07:03 | 0.92 |
July | 0.160079E+10 | 0.49 | 1111.66 | 01-JUL-09:10 | 0.91 |
August | 0.164081E+10 | 0.50 | 1111.66 | 01-AUG-09:20 | 0.92 |
September | 0.156077E+10 | 0.50 | 1111.66 | 01-SEP-10:10 | 0.92 |
October | 0.160879E+10 | 0.50 | 1111.66 | 01-OCT-10:40 | 0.91 |
November | 0.156077E+10 | 0.50 | 1111.66 | 06-NOV-11:30 | 0.92 |
December | 0.160079E+10 | 0.50 | 1111.66 | 04-DEC-08:20 | 0.92 |
Annual Sum or Average | 0.190494E+11 | 0.50 | |||
Minimum of Months | 0.145672E+10 | 0.49 | 1111.66 | 0.91 | |
Maximum of Months | 0.164081E+10 | 0.51 | 1111.66 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.161368E+10 | 0.50 | 1115.03 | 01-JAN-09:25 | 0.92 |
February | 0.146114E+10 | 0.50 | 1115.03 | 01-FEB-08:40 | 0.92 |
March | 0.164579E+10 | 0.51 | 1115.03 | 10-MAR-13:40 | 0.92 |
April | 0.156551E+10 | 0.50 | 1115.03 | 01-APR-10:10 | 0.92 |
May | 0.162973E+10 | 0.50 | 1115.03 | 01-MAY-12:40 | 0.92 |
June | 0.158959E+10 | 0.50 | 1115.03 | 01-JUN-10:40 | 0.92 |
July | 0.160565E+10 | 0.49 | 1115.03 | 01-JUL-08:07 | 0.91 |
August | 0.164579E+10 | 0.50 | 1115.03 | 01-AUG-07:04 | 0.91 |
September | 0.156551E+10 | 0.50 | 1115.03 | 01-SEP-16:50 | 0.92 |
October | 0.161368E+10 | 0.50 | 1115.03 | 01-OCT-08:40 | 0.91 |
November | 0.156551E+10 | 0.50 | 1115.03 | 01-NOV-07:03 | 0.92 |
December | 0.160565E+10 | 0.50 | 1115.03 | 01-DEC-10:40 | 0.92 |
Annual Sum or Average | 0.191072E+11 | 0.50 | |||
Minimum of Months | 0.146114E+10 | 0.49 | 1115.03 | 0.91 | |
Maximum of Months | 0.164579E+10 | 0.51 | 1115.03 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.160636E+10 | 0.50 | 1109.98 | 01-JAN-09:40 | 0.92 |
February | 0.145452E+10 | 0.50 | 1109.98 | 01-FEB-08:30 | 0.92 |
March | 0.163833E+10 | 0.51 | 1109.98 | 03-MAR-14:20 | 0.92 |
April | 0.155841E+10 | 0.50 | 1109.98 | 01-APR-10:20 | 0.92 |
May | 0.162235E+10 | 0.50 | 1109.98 | 30-MAY-15:10 | 0.92 |
June | 0.158239E+10 | 0.50 | 1109.98 | 01-JUN-09:50 | 0.92 |
July | 0.159837E+10 | 0.49 | 1109.98 | 01-JUL-07:10 | 0.91 |
August | 0.163833E+10 | 0.50 | 1109.98 | 01-AUG-09:20 | 0.92 |
September | 0.155841E+10 | 0.50 | 1109.98 | 01-SEP-09:30 | 0.92 |
October | 0.160636E+10 | 0.50 | 1109.98 | 01-OCT-08:09 | 0.91 |
November | 0.155841E+10 | 0.50 | 1109.98 | 03-NOV-17:00 | 0.92 |
December | 0.159837E+10 | 0.50 | 1109.98 | 01-DEC-11:30 | 0.92 |
Annual Sum or Average | 0.190206E+11 | 0.50 | |||
Minimum of Months | 0.145452E+10 | 0.49 | 1109.98 | 0.91 | |
Maximum of Months | 0.163833E+10 | 0.51 | 1109.98 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.105818E+10 | 0.27 | 1373.63 | 02-JAN-09:02 | 0.75 |
February | 0.956506E+09 | 0.27 | 872.86 | 28-FEB-09:10 | 0.58 |
March | 0.108390E+10 | 0.28 | 1562.40 | 30-MAR-08:62 | 0.80 |
April | 0.102301E+10 | 0.27 | 850.07 | 01-APR-08:65 | 0.57 |
May | 0.106571E+10 | 0.27 | 1300.67 | 03-MAY-08:62 | 0.72 |
June | 0.104150E+10 | 0.27 | 1973.32 | 21-JUN-08:62 | 0.89 |
July | 0.105278E+10 | 0.27 | 1973.32 | 01-JUL-08:62 | 0.88 |
August | 0.108119E+10 | 0.27 | 1973.32 | 01-AUG-08:62 | 0.88 |
September | 0.103496E+10 | 0.27 | 1973.32 | 06-SEP-08:62 | 0.88 |
October | 0.107079E+10 | 0.27 | 1973.32 | 01-OCT-09:02 | 0.88 |
November | 0.102311E+10 | 0.27 | 1973.32 | 19-NOV-10:02 | 0.89 |
December | 0.104885E+10 | 0.27 | 907.44 | 05-DEC-09:02 | 0.59 |
Annual Sum or Average | 0.125405E+11 | 0.27 | |||
Minimum of Months | 0.956506E+09 | 0.27 | 850.07 | 0.57 | |
Maximum of Months | 0.108390E+10 | 0.28 | 1973.32 | 0.89 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.143856E+10 | 0.46 | 1077.09 | 01-JAN-10:10 | 0.92 |
February | 0.130285E+10 | 0.46 | 1077.09 | 01-FEB-09:03 | 0.92 |
March | 0.146958E+10 | 0.47 | 1077.09 | 07-MAR-09:30 | 0.92 |
April | 0.139591E+10 | 0.46 | 1077.09 | 01-APR-10:15 | 0.92 |
May | 0.145407E+10 | 0.46 | 1077.09 | 01-MAY-10:40 | 0.92 |
June | 0.141918E+10 | 0.47 | 1077.09 | 24-JUN-09:00 | 0.92 |
July | 0.143081E+10 | 0.45 | 1077.09 | 11-JUL-17:20 | 0.91 |
August | 0.146958E+10 | 0.47 | 1077.09 | 01-AUG-08:30 | 0.91 |
September | 0.139591E+10 | 0.46 | 1077.09 | 01-SEP-08:30 | 0.92 |
October | 0.143856E+10 | 0.46 | 1077.09 | 01-OCT-09:07 | 0.91 |
November | 0.139591E+10 | 0.46 | 1077.09 | 01-NOV-08:62 | 0.92 |
December | 0.143081E+10 | 0.46 | 1077.09 | 04-DEC-09:02 | 0.92 |
Annual Sum or Average | 0.170417E+11 | 0.46 | |||
Minimum of Months | 0.130285E+10 | 0.45 | 1077.09 | 0.91 | |
Maximum of Months | 0.146958E+10 | 0.47 | 1077.09 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.143186E+10 | 0.46 | 1072.07 | 01-JAN-09:05 | 0.92 |
February | 0.129677E+10 | 0.46 | 1072.07 | 02-FEB-12:40 | 0.92 |
March | 0.146273E+10 | 0.47 | 1072.07 | 30-MAR-19:50 | 0.92 |
April | 0.138940E+10 | 0.46 | 1072.07 | 01-APR-11:40 | 0.92 |
May | 0.144729E+10 | 0.46 | 1072.07 | 03-MAY-14:10 | 0.92 |
June | 0.141256E+10 | 0.47 | 1072.07 | 02-JUN-13:10 | 0.92 |
July | 0.142414E+10 | 0.45 | 1072.07 | 01-JUL-16:00 | 0.91 |
August | 0.146273E+10 | 0.47 | 1072.07 | 26-AUG-16:20 | 0.91 |
September | 0.138940E+10 | 0.46 | 1072.07 | 03-SEP-13:10 | 0.92 |
October | 0.143186E+10 | 0.46 | 1072.07 | 04-OCT-17:50 | 0.91 |
November | 0.138940E+10 | 0.46 | 1072.07 | 02-NOV-10:00 | 0.92 |
December | 0.142414E+10 | 0.46 | 1072.07 | 30-DEC-12:20 | 0.92 |
Annual Sum or Average | 0.169623E+11 | 0.46 | |||
Minimum of Months | 0.129677E+10 | 0.45 | 1072.07 | 0.91 | |
Maximum of Months | 0.146273E+10 | 0.47 | 1072.07 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.142598E+10 | 0.46 | 1067.67 | 01-JAN-16:00 | 0.92 |
February | 0.129145E+10 | 0.46 | 1067.67 | 03-FEB-10:00 | 0.93 |
March | 0.145673E+10 | 0.47 | 1067.67 | 08-MAR-09:40 | 0.92 |
April | 0.138370E+10 | 0.46 | 1067.67 | 03-APR-13:20 | 0.92 |
May | 0.144135E+10 | 0.46 | 1067.67 | 01-MAY-12:10 | 0.92 |
June | 0.140676E+10 | 0.47 | 1067.67 | 15-JUN-17:20 | 0.92 |
July | 0.141829E+10 | 0.45 | 1067.67 | 07-JUL-08:30 | 0.92 |
August | 0.145673E+10 | 0.47 | 1067.67 | 03-AUG-09:10 | 0.91 |
September | 0.138370E+10 | 0.46 | 1067.67 | 09-SEP-10:20 | 0.91 |
October | 0.142598E+10 | 0.46 | 1067.67 | 12-OCT-10:50 | 0.93 |
November | 0.138370E+10 | 0.46 | 1067.67 | 10-NOV-12:10 | 0.92 |
December | 0.141829E+10 | 0.46 | 1067.67 | 07-DEC-13:30 | 0.92 |
Annual Sum or Average | 0.168927E+11 | 0.46 | |||
Minimum of Months | 0.129145E+10 | 0.45 | 1067.67 | 0.91 | |
Maximum of Months | 0.145673E+10 | 0.47 | 1067.67 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.156838E+10 | 0.46 | 1174.29 | 01-JAN-11:00 | 0.92 |
February | 0.142042E+10 | 0.46 | 1174.29 | 01-FEB-09:50 | 0.92 |
March | 0.160220E+10 | 0.47 | 1174.29 | 02-MAR-09:20 | 0.92 |
April | 0.152188E+10 | 0.46 | 1174.29 | 01-APR-10:30 | 0.92 |
May | 0.158529E+10 | 0.46 | 1174.29 | 01-MAY-11:50 | 0.92 |
June | 0.154724E+10 | 0.47 | 1174.29 | 01-JUN-10:50 | 0.92 |
July | 0.155993E+10 | 0.45 | 1174.29 | 01-JUL-09:00 | 0.91 |
August | 0.160220E+10 | 0.47 | 1174.29 | 01-AUG-09:40 | 0.91 |
September | 0.152188E+10 | 0.46 | 1174.29 | 01-SEP-08:30 | 0.92 |
October | 0.156838E+10 | 0.46 | 1174.29 | 30-OCT-16:50 | 0.92 |
November | 0.152188E+10 | 0.46 | 1174.29 | 07-NOV-13:50 | 0.92 |
December | 0.155993E+10 | 0.46 | 1174.29 | 04-DEC-09:40 | 0.92 |
Annual Sum or Average | 0.185796E+11 | 0.46 | |||
Minimum of Months | 0.142042E+10 | 0.45 | 1174.29 | 0.91 | |
Maximum of Months | 0.160220E+10 | 0.47 | 1174.29 | 0.92 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.179240E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.142291E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.165771E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.200202E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.197076E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.279118E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.432774E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.455579E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.337888E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.375079E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.173896E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.187011E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.312592E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.142291E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.455579E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.196439E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.165554E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.184955E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.215740E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.216486E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.256105E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.330036E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.342700E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.278017E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.304572E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.200562E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.203066E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.289423E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.165554E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.342700E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.176585E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.149472E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.171724E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.179086E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.179577E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.213026E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.274702E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.292138E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.230530E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.254395E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.170468E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.180582E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.247229E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.149472E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.292138E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.176485E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.149730E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.171791E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.178515E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.179160E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.212336E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.274128E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.291666E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.229843E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.254207E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.170427E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.180102E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.246839E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.149730E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.291666E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.174638E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.148719E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.170226E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.176008E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.176829E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.208882E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.269696E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.287180E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.226119E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.250515E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.168785E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.177665E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.243526E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.148719E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.287180E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.130989E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.102465E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.121289E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.145674E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.142164E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.210654E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.324686E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.351876E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.255537E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.287726E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.127581E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.137665E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.233831E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.102465E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.351876E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.156467E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.133216E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.152634E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.158374E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.158827E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.188891E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.245446E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.261726E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.205847E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.227275E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.151269E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.158901E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.219887E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.133216E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.261726E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.155546E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.132545E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.151827E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.157333E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.157760E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.187349E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.243512E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.259753E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.204195E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.225572E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.150391E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.157844E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.218363E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.132545E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.259753E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.153886E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.131685E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.150643E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.155235E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.155730E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.183954E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.239596E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.255865E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.200510E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.221851E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.148836E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.155596E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.215339E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.131685E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.255865E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.167485E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.144329E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.165264E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.170066E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.170400E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.199601E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.260920E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.278261E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.214865E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.236128E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.162029E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.168436E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.233779E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.144329E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.278261E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.148984E+10 | 0.115912E+10 | 83355927.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134746E+10 | 0.284439E+09 | 55115621.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.150074E+10 | 0.601357E+09 | 0.292429E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144071E+10 | 0.218486E+10 | 1429403.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.148802E+10 | 0.184849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.144792E+10 | 0.537833E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149153E+10 | 0.118412E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.149489E+10 | 0.129082E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.145723E+10 | 0.770036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.150624E+10 | 0.894533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.143766E+10 | 0.116331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149427E+10 | 0.144033E+10 | 17886741.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175965E+11 | 0.554553E+11 | 0.450217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.134746E+10 | 0.284439E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.150624E+10 | 0.129082E+11 | 0.292429E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.178602E+10 | 0.798982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.160622E+10 | 0.218442E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.175788E+10 | 0.407820E+09 | 2829215.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.188057E+10 | 0.124789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.195152E+10 | 0.944974E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.195077E+10 | 0.281787E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195799E+10 | 0.644672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.198395E+10 | 0.700308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.191152E+10 | 0.400270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.192889E+10 | 0.514867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.183649E+10 | 0.762803E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.179987E+10 | 0.103371E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.223517E+11 | 0.308337E+11 | 2829215.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.160622E+10 | 0.218442E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.198395E+10 | 0.700308E+10 | 2829215.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.160879E+10 | 0.698388E+09 | 8228666.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.145672E+10 | 0.167331E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.164081E+10 | 0.338941E+09 | 18798616.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.156077E+10 | 0.102751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.162480E+10 | 0.752767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.158478E+10 | 0.249811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.160079E+10 | 0.545236E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.164081E+10 | 0.616166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.156077E+10 | 0.339181E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.160879E+10 | 0.423917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.156077E+10 | 0.644741E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.160079E+10 | 0.910243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.190494E+11 | 0.262830E+11 | 27027282.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.145672E+10 | 0.167331E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.164081E+10 | 0.616166E+10 | 18798616.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.161368E+10 | 0.669906E+09 | 17972289.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.146114E+10 | 0.158926E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.164579E+10 | 0.318795E+09 | 28209054.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.156551E+10 | 0.978378E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.162973E+10 | 0.711514E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.158959E+10 | 0.244016E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.160565E+10 | 0.539416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.164579E+10 | 0.610566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.156551E+10 | 0.333344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.161368E+10 | 0.420427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.156551E+10 | 0.619839E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.160565E+10 | 0.863947E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.191072E+11 | 0.257990E+11 | 46181343.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.146114E+10 | 0.158926E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.164579E+10 | 0.610566E+10 | 28209054.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.160636E+10 | 0.616653E+09 | 29735886.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.145452E+10 | 0.142966E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.163833E+10 | 0.280945E+09 | 47911327.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.155841E+10 | 0.894922E+09 | 660549.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.162235E+10 | 0.639619E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.158239E+10 | 0.230758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.159837E+10 | 0.520259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.163833E+10 | 0.590681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.155841E+10 | 0.318582E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.160636E+10 | 0.405862E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.155841E+10 | 0.575455E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.159837E+10 | 0.783736E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.190206E+11 | 0.245957E+11 | 78307763.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.145452E+10 | 0.142966E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.163833E+10 | 0.590681E+10 | 47911327.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.105818E+10 | 0.960330E+09 | 0.163905E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.956506E+09 | 0.257013E+09 | 71893646.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.108390E+10 | 0.494112E+09 | 0.287893E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.102301E+10 | 0.167854E+10 | 1368660.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.106571E+10 | 0.136195E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.104150E+10 | 0.424864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.105278E+10 | 0.913406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.108119E+10 | 0.102679E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.103496E+10 | 0.608288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.107079E+10 | 0.717591E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.102311E+10 | 0.971888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.104885E+10 | 0.124740E+10 | 11911008.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.125405E+11 | 0.438806E+11 | 0.536972E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.956506E+09 | 0.257013E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.108390E+10 | 0.102679E+11 | 0.287893E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.143856E+10 | 0.555145E+09 | 39206176.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130285E+10 | 0.127930E+09 | 3155283.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146958E+10 | 0.249501E+09 | 53378961.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139591E+10 | 0.833944E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.145407E+10 | 0.588868E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.141918E+10 | 0.214331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.143081E+10 | 0.486490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.146958E+10 | 0.551650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.139591E+10 | 0.300743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143856E+10 | 0.377156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.139591E+10 | 0.518536E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143081E+10 | 0.694052E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170417E+11 | 0.228717E+11 | 95740420.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130285E+10 | 0.127930E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.146958E+10 | 0.551650E+10 | 53378961.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.143186E+10 | 0.543384E+09 | 43086386.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129677E+10 | 0.125053E+09 | 4309308.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146273E+10 | 0.243903E+09 | 58597605.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138940E+10 | 0.815828E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144729E+10 | 0.571308E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.141256E+10 | 0.210069E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.142414E+10 | 0.480074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.146273E+10 | 0.544983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138940E+10 | 0.295894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143186E+10 | 0.372157E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138940E+10 | 0.507801E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142414E+10 | 0.676079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169623E+11 | 0.225151E+11 | 0.105993E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129677E+10 | 0.125053E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.146273E+10 | 0.544983E+10 | 58597605.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.142598E+10 | 0.492733E+09 | 58034463.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129145E+10 | 0.110064E+09 | 15163398.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145673E+10 | 0.217012E+09 | 95693067.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138370E+10 | 0.744733E+09 | 224822.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144135E+10 | 0.506818E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140676E+10 | 0.196452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.141829E+10 | 0.463047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145673E+10 | 0.527716E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138370E+10 | 0.280700E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.142598E+10 | 0.356796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138370E+10 | 0.461105E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141829E+10 | 0.599325E+09 | 206223.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168927E+11 | 0.213789E+11 | 0.169322E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129145E+10 | 0.110064E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145673E+10 | 0.527716E+10 | 95693067.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.156838E+10 | 0.460797E+09 | 97988069.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142042E+10 | 98315933.15 | 95555747.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160220E+10 | 0.219541E+09 | 0.227444E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152188E+10 | 0.789225E+09 | 1812144.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.158529E+10 | 0.518317E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.154724E+10 | 0.203496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.155993E+10 | 0.497359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.160220E+10 | 0.566140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152188E+10 | 0.281852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156838E+10 | 0.354293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152188E+10 | 0.429915E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.155993E+10 | 0.537070E+09 | 17443405.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.185796E+11 | 0.220846E+11 | 0.440243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.142042E+10 | 98315933.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.160220E+10 | 0.566140E+10 | 0.227444E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.148984E+10 | 0.00 | 0.00 | 0.00 | 0.302564E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134746E+10 | 0.00 | 0.00 | 0.00 | 75442844.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.150074E+10 | 0.00 | 0.00 | 0.00 | 0.156967E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144071E+10 | 0.00 | 0.00 | 0.00 | 0.561312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.148802E+10 | 0.00 | 0.00 | 0.00 | 0.482744E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.144792E+10 | 0.00 | 0.00 | 0.00 | 0.134326E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149153E+10 | 0.00 | 0.00 | 0.00 | 0.283621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.149489E+10 | 0.00 | 0.00 | 0.00 | 0.306090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.145723E+10 | 0.00 | 0.00 | 0.00 | 0.192165E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.150624E+10 | 0.00 | 0.00 | 0.00 | 0.224454E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.143766E+10 | 0.00 | 0.00 | 0.00 | 0.301296E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149427E+10 | 0.00 | 0.00 | 0.00 | 0.375840E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175965E+11 | 0.00 | 0.00 | 0.00 | 0.136627E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.134746E+10 | 0.00 | 0.00 | 0.00 | 75442844.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.150624E+10 | 0.00 | 0.00 | 0.00 | 0.306090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.178602E+10 | 0.00 | 0.00 | 0.00 | 0.178367E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.160622E+10 | 0.00 | 0.00 | 0.00 | 49318322.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.175788E+10 | 0.00 | 0.00 | 0.00 | 91666731.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.188057E+10 | 0.00 | 0.00 | 0.00 | 0.276831E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.195152E+10 | 0.00 | 0.00 | 0.00 | 0.213337E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.195077E+10 | 0.00 | 0.00 | 0.00 | 0.610275E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195799E+10 | 0.00 | 0.00 | 0.00 | 0.134236E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.198395E+10 | 0.00 | 0.00 | 0.00 | 0.144304E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.191152E+10 | 0.00 | 0.00 | 0.00 | 0.868648E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.111684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.183649E+10 | 0.00 | 0.00 | 0.00 | 0.169125E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.179987E+10 | 0.00 | 0.00 | 0.00 | 0.230797E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.223517E+11 | 0.00 | 0.00 | 0.00 | 0.659061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.160622E+10 | 0.00 | 0.00 | 0.00 | 49318322.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.198395E+10 | 0.00 | 0.00 | 0.00 | 0.144304E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.160879E+10 | 0.00 | 0.00 | 0.00 | 0.157052E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.145672E+10 | 0.00 | 0.00 | 0.00 | 37997197.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.164081E+10 | 0.00 | 0.00 | 0.00 | 76427353.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.156077E+10 | 0.00 | 0.00 | 0.00 | 0.230094E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.162480E+10 | 0.00 | 0.00 | 0.00 | 0.170972E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.158478E+10 | 0.00 | 0.00 | 0.00 | 0.545477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.160079E+10 | 0.00 | 0.00 | 0.00 | 0.114623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.164081E+10 | 0.00 | 0.00 | 0.00 | 0.128057E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.156077E+10 | 0.00 | 0.00 | 0.00 | 0.744534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.160879E+10 | 0.00 | 0.00 | 0.00 | 0.935160E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.156077E+10 | 0.00 | 0.00 | 0.00 | 0.143909E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.160079E+10 | 0.00 | 0.00 | 0.00 | 0.205028E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.190494E+11 | 0.00 | 0.00 | 0.00 | 0.567345E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.145672E+10 | 0.00 | 0.00 | 0.00 | 37997197.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.164081E+10 | 0.00 | 0.00 | 0.00 | 0.128057E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.161368E+10 | 0.00 | 0.00 | 0.00 | 0.151179E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.146114E+10 | 0.00 | 0.00 | 0.00 | 36155607.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.164579E+10 | 0.00 | 0.00 | 0.00 | 72121754.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.156551E+10 | 0.00 | 0.00 | 0.00 | 0.219645E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.162973E+10 | 0.00 | 0.00 | 0.00 | 0.161870E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.158959E+10 | 0.00 | 0.00 | 0.00 | 0.533770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.160565E+10 | 0.00 | 0.00 | 0.00 | 0.113563E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.164579E+10 | 0.00 | 0.00 | 0.00 | 0.127087E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.156551E+10 | 0.00 | 0.00 | 0.00 | 0.732919E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.161368E+10 | 0.00 | 0.00 | 0.00 | 0.928398E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.156551E+10 | 0.00 | 0.00 | 0.00 | 0.138764E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.160565E+10 | 0.00 | 0.00 | 0.00 | 0.195375E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.191072E+11 | 0.00 | 0.00 | 0.00 | 0.557670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.146114E+10 | 0.00 | 0.00 | 0.00 | 36155607.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.164579E+10 | 0.00 | 0.00 | 0.00 | 0.127087E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.160636E+10 | 0.00 | 0.00 | 0.00 | 0.140016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.145452E+10 | 0.00 | 0.00 | 0.00 | 32669319.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.163833E+10 | 0.00 | 0.00 | 0.00 | 63927641.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.155841E+10 | 0.00 | 0.00 | 0.00 | 0.201670E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.162235E+10 | 0.00 | 0.00 | 0.00 | 0.145948E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.158239E+10 | 0.00 | 0.00 | 0.00 | 0.506430E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.159837E+10 | 0.00 | 0.00 | 0.00 | 0.109859E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.163833E+10 | 0.00 | 0.00 | 0.00 | 0.123347E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.155841E+10 | 0.00 | 0.00 | 0.00 | 0.702784E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.160636E+10 | 0.00 | 0.00 | 0.00 | 0.898788E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.155841E+10 | 0.00 | 0.00 | 0.00 | 0.129444E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.159837E+10 | 0.00 | 0.00 | 0.00 | 0.178278E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.190206E+11 | 0.00 | 0.00 | 0.00 | 0.533201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.145452E+10 | 0.00 | 0.00 | 0.00 | 32669319.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.163833E+10 | 0.00 | 0.00 | 0.00 | 0.123347E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.105818E+10 | 0.00 | 0.00 | 0.00 | 0.251713E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.956506E+09 | 0.00 | 0.00 | 0.00 | 68142522.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.108390E+10 | 0.00 | 0.00 | 0.00 | 0.128990E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.102301E+10 | 0.00 | 0.00 | 0.00 | 0.433727E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.106571E+10 | 0.00 | 0.00 | 0.00 | 0.355935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.104150E+10 | 0.00 | 0.00 | 0.00 | 0.106505E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.105278E+10 | 0.00 | 0.00 | 0.00 | 0.219408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.108119E+10 | 0.00 | 0.00 | 0.00 | 0.243757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.103496E+10 | 0.00 | 0.00 | 0.00 | 0.152041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.107079E+10 | 0.00 | 0.00 | 0.00 | 0.180647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.102311E+10 | 0.00 | 0.00 | 0.00 | 0.252699E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.104885E+10 | 0.00 | 0.00 | 0.00 | 0.327807E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.125405E+11 | 0.00 | 0.00 | 0.00 | 0.108426E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.956506E+09 | 0.00 | 0.00 | 0.00 | 68142522.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.108390E+10 | 0.00 | 0.00 | 0.00 | 0.243757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.143856E+10 | 0.00 | 0.00 | 0.00 | 0.126102E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130285E+10 | 0.00 | 0.00 | 0.00 | 29311983.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146958E+10 | 0.00 | 0.00 | 0.00 | 56758525.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139591E+10 | 0.00 | 0.00 | 0.00 | 0.187834E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.145407E+10 | 0.00 | 0.00 | 0.00 | 0.134199E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.141918E+10 | 0.00 | 0.00 | 0.00 | 0.469733E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.143081E+10 | 0.00 | 0.00 | 0.00 | 0.102365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.146958E+10 | 0.00 | 0.00 | 0.00 | 0.114768E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.139591E+10 | 0.00 | 0.00 | 0.00 | 0.662556E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143856E+10 | 0.00 | 0.00 | 0.00 | 0.834185E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.139591E+10 | 0.00 | 0.00 | 0.00 | 0.116781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143081E+10 | 0.00 | 0.00 | 0.00 | 0.158204E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170417E+11 | 0.00 | 0.00 | 0.00 | 0.494699E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130285E+10 | 0.00 | 0.00 | 0.00 | 29311983.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.146958E+10 | 0.00 | 0.00 | 0.00 | 0.114768E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.143186E+10 | 0.00 | 0.00 | 0.00 | 0.123610E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129677E+10 | 0.00 | 0.00 | 0.00 | 28679300.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146273E+10 | 0.00 | 0.00 | 0.00 | 55538061.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138940E+10 | 0.00 | 0.00 | 0.00 | 0.183930E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144729E+10 | 0.00 | 0.00 | 0.00 | 0.130310E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.141256E+10 | 0.00 | 0.00 | 0.00 | 0.460927E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.142414E+10 | 0.00 | 0.00 | 0.00 | 0.101099E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.146273E+10 | 0.00 | 0.00 | 0.00 | 0.113480E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138940E+10 | 0.00 | 0.00 | 0.00 | 0.652548E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143186E+10 | 0.00 | 0.00 | 0.00 | 0.823864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138940E+10 | 0.00 | 0.00 | 0.00 | 0.114505E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142414E+10 | 0.00 | 0.00 | 0.00 | 0.154304E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169623E+11 | 0.00 | 0.00 | 0.00 | 0.487400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129677E+10 | 0.00 | 0.00 | 0.00 | 28679300.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.146273E+10 | 0.00 | 0.00 | 0.00 | 0.113480E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.142598E+10 | 0.00 | 0.00 | 0.00 | 0.112881E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129145E+10 | 0.00 | 0.00 | 0.00 | 25394938.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145673E+10 | 0.00 | 0.00 | 0.00 | 49703307.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138370E+10 | 0.00 | 0.00 | 0.00 | 0.168651E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144135E+10 | 0.00 | 0.00 | 0.00 | 0.115947E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140676E+10 | 0.00 | 0.00 | 0.00 | 0.432780E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.141829E+10 | 0.00 | 0.00 | 0.00 | 0.977669E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145673E+10 | 0.00 | 0.00 | 0.00 | 0.110192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138370E+10 | 0.00 | 0.00 | 0.00 | 0.621399E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.142598E+10 | 0.00 | 0.00 | 0.00 | 0.792533E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138370E+10 | 0.00 | 0.00 | 0.00 | 0.104663E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141829E+10 | 0.00 | 0.00 | 0.00 | 0.137663E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168927E+11 | 0.00 | 0.00 | 0.00 | 0.464121E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129145E+10 | 0.00 | 0.00 | 0.00 | 25394938.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145673E+10 | 0.00 | 0.00 | 0.00 | 0.110192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.156838E+10 | 0.00 | 0.00 | 0.00 | 0.106465E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142042E+10 | 0.00 | 0.00 | 0.00 | 22872786.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160220E+10 | 0.00 | 0.00 | 0.00 | 50443063.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152188E+10 | 0.00 | 0.00 | 0.00 | 0.178784E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.158529E+10 | 0.00 | 0.00 | 0.00 | 0.118710E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.154724E+10 | 0.00 | 0.00 | 0.00 | 0.448768E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.155993E+10 | 0.00 | 0.00 | 0.00 | 0.104927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.160220E+10 | 0.00 | 0.00 | 0.00 | 0.118041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152188E+10 | 0.00 | 0.00 | 0.00 | 0.626773E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156838E+10 | 0.00 | 0.00 | 0.00 | 0.792898E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152188E+10 | 0.00 | 0.00 | 0.00 | 98407623.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.155993E+10 | 0.00 | 0.00 | 0.00 | 0.124429E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.185796E+11 | 0.00 | 0.00 | 0.00 | 0.479823E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.142042E+10 | 0.00 | 0.00 | 0.00 | 22872786.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.160220E+10 | 0.00 | 0.00 | 0.00 | 0.118041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.481549E+10 | 33993999.21 | 0.00 | 5173338.07 | 0.00 | 1667278.00 | 0.392192E+10 | 0.00 | 0.64 |
February | 0.478156E+10 | 10478687.36 | 0.00 | 3601749.33 | 0.00 | 0.00 | 0.330649E+10 | 0.00 | 0.61 |
March | 0.627427E+10 | 1064623.63 | 0.00 | 3306001.58 | 0.00 | 33275562.24 | 0.250280E+10 | 0.00 | 0.61 |
April | 0.160696E+10 | 46995797.66 | 0.00 | 10155958.09 | 0.00 | 1468865.20 | 0.662699E+10 | 0.00 | 0.80 |
May | 0.136773E+10 | 13846411.87 | 0.00 | 11395183.41 | 0.00 | 0.00 | 0.748790E+10 | 0.00 | 0.83 |
June | 0.277731E+09 | 0.187328E+09 | 0.00 | 14153354.06 | 0.00 | 0.00 | 0.665243E+10 | 0.00 | 0.98 |
July | 37119068.84 | 0.116762E+10 | 0.00 | 16483810.56 | 88976.69 | 0.00 | 0.442892E+10 | 0.00 | 1.00 |
August | 36664611.58 | 0.146123E+10 | 0.00 | 13228771.98 | 1702380.01 | 0.00 | 0.398730E+10 | 0.00 | 0.99 |
September | 0.153976E+09 | 0.459845E+09 | 0.00 | 16094577.38 | 599694.44 | 0.00 | 0.628484E+10 | 0.00 | 1.00 |
October | 0.252621E+09 | 0.947212E+09 | 0.00 | 17333357.76 | 3238878.39 | 0.00 | 0.600122E+10 | 0.00 | 0.94 |
November | 0.206127E+10 | 33094548.82 | 0.00 | 8691487.59 | 0.00 | 0.00 | 0.692825E+10 | 0.00 | 0.71 |
December | 0.479603E+10 | 18559298.88 | 0.00 | 5914859.40 | 0.00 | 0.00 | 0.395968E+10 | 0.00 | 0.68 |
Annual Sum or Average | 0.264614E+11 | 0.438127E+10 | 0.00 | 0.125532E+09 | 5629929.53 | 36411705.44 | 0.620887E+11 | 0.00 | 0.82 |
Minimum of Months | 36664611.58 | 1064623.63 | 0.00 | 3306001.58 | 0.00 | 0.00 | 0.250280E+10 | 0.00 | 0.61 |
Maximum of Months | 0.627427E+10 | 0.146123E+10 | 0.00 | 17333357.76 | 3238878.39 | 33275562.24 | 0.748790E+10 | 0.00 | 1.00 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.629702E+09 | 21478424.92 | 0.00 | 5526042.44 | 0.00 | 0.00 | 0.458527E+10 | 0.00 | 0.84 |
February | 0.673670E+09 | 6369986.62 | 0.00 | 4565541.73 | 0.00 | 0.00 | 0.417147E+10 | 0.00 | 0.76 |
March | 0.121428E+10 | 0.00 | 0.00 | 4201712.56 | 0.00 | 0.00 | 0.372551E+10 | 0.00 | 0.72 |
April | 0.167551E+09 | 24227503.10 | 0.00 | 7150151.81 | 0.00 | 0.00 | 0.536896E+10 | 0.00 | 1.14 |
May | 77962656.14 | 7073369.11 | 0.00 | 7773223.36 | 0.00 | 0.00 | 0.598039E+10 | 0.00 | 1.21 |
June | 28131882.51 | 83253381.37 | 0.00 | 8674453.00 | 0.00 | 0.00 | 0.499658E+10 | 0.00 | 1.46 |
July | 11940219.72 | 0.553296E+09 | 0.00 | 9106514.81 | 74829.09 | 0.00 | 0.325083E+10 | 0.00 | 1.42 |
August | 12028520.54 | 0.700295E+09 | 0.00 | 7876884.40 | 987583.40 | 0.00 | 0.305671E+10 | 0.00 | 1.42 |
September | 25020359.45 | 0.228833E+09 | 0.00 | 9396025.92 | 1002354.35 | 0.00 | 0.469256E+10 | 0.00 | 1.45 |
October | 35354137.12 | 0.499274E+09 | 0.00 | 8504612.04 | 1549383.20 | 0.00 | 0.425273E+10 | 0.00 | 1.30 |
November | 90215378.04 | 21069858.79 | 0.00 | 7110628.32 | 0.00 | 0.00 | 0.580424E+10 | 0.00 | 0.99 |
December | 0.515064E+09 | 10301496.55 | 0.00 | 6230513.59 | 0.00 | 0.00 | 0.472742E+10 | 0.00 | 0.90 |
Annual Sum or Average | 0.348092E+10 | 0.215547E+10 | 0.00 | 86116303.97 | 3614150.03 | 0.00 | 0.546127E+11 | 0.00 | 1.14 |
Minimum of Months | 11940219.72 | 0.00 | 0.00 | 4201712.56 | 0.00 | 0.00 | 0.305671E+10 | 0.00 | 0.72 |
Maximum of Months | 0.121428E+10 | 0.700295E+09 | 0.00 | 9396025.92 | 1549383.20 | 0.00 | 0.598039E+10 | 0.00 | 1.46 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.121602E+10 | 20839117.56 | 0.00 | 3161048.34 | 0.00 | 0.00 | 0.257542E+10 | 0.00 | 0.69 |
February | 0.114273E+10 | 7512977.11 | 0.00 | 2499871.71 | 0.00 | 0.00 | 0.245603E+10 | 0.00 | 0.63 |
March | 0.179294E+10 | 0.00 | 0.00 | 2231916.32 | 0.00 | 1105702.65 | 0.200691E+10 | 0.00 | 0.62 |
April | 0.581687E+09 | 26221835.31 | 0.00 | 4284340.36 | 0.00 | 0.00 | 0.316933E+10 | 0.00 | 0.92 |
May | 0.466445E+09 | 7484299.61 | 0.00 | 4885530.97 | 0.00 | 0.00 | 0.369490E+10 | 0.00 | 0.98 |
June | 0.264334E+09 | 80834374.46 | 0.00 | 5747582.59 | 0.00 | 0.00 | 0.285143E+10 | 0.00 | 1.17 |
July | 0.178380E+09 | 0.528927E+09 | 0.00 | 5462811.84 | 875637.57 | 0.00 | 0.146625E+10 | 0.00 | 1.09 |
August | 0.188780E+09 | 0.655074E+09 | 0.00 | 4811897.25 | 2670941.05 | 0.00 | 0.128984E+10 | 0.00 | 1.09 |
September | 0.238453E+09 | 0.202932E+09 | 0.00 | 6325804.76 | 478548.08 | 0.00 | 0.267870E+10 | 0.00 | 1.13 |
October | 0.278247E+09 | 0.489434E+09 | 0.00 | 5318712.88 | 2735090.43 | 0.00 | 0.241215E+10 | 0.00 | 1.03 |
November | 0.573765E+09 | 16782438.15 | 0.00 | 4346953.46 | 0.00 | 0.00 | 0.354443E+10 | 0.00 | 0.80 |
December | 0.108167E+10 | 11500608.47 | 0.00 | 3648279.94 | 0.00 | 0.00 | 0.265571E+10 | 0.00 | 0.76 |
Annual Sum or Average | 0.800345E+10 | 0.204754E+10 | 0.00 | 52724750.43 | 6760217.13 | 1105702.65 | 0.308011E+11 | 0.00 | 0.91 |
Minimum of Months | 0.178380E+09 | 0.00 | 0.00 | 2231916.32 | 0.00 | 0.00 | 0.128984E+10 | 0.00 | 0.62 |
Maximum of Months | 0.179294E+10 | 0.655074E+09 | 0.00 | 6325804.76 | 2735090.43 | 1105702.65 | 0.369490E+10 | 0.00 | 1.17 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.126989E+10 | 20682524.02 | 0.00 | 2902985.62 | 0.00 | 11422313.45 | 0.240769E+10 | 0.00 | 0.67 |
February | 0.123628E+10 | 7476452.74 | 0.00 | 2278121.67 | 0.00 | 0.00 | 0.226509E+10 | 0.00 | 0.61 |
March | 0.190199E+10 | 0.00 | 0.00 | 1992055.59 | 0.00 | 3222283.20 | 0.180510E+10 | 0.00 | 0.61 |
April | 0.616332E+09 | 25844030.16 | 0.00 | 4073031.71 | 0.00 | 0.00 | 0.307038E+10 | 0.00 | 0.90 |
May | 0.486151E+09 | 7446600.36 | 0.00 | 4681649.92 | 0.00 | 0.00 | 0.361873E+10 | 0.00 | 0.97 |
June | 0.266353E+09 | 78903630.78 | 0.00 | 5600196.19 | 0.00 | 0.00 | 0.283341E+10 | 0.00 | 1.16 |
July | 0.179444E+09 | 0.524545E+09 | 0.00 | 5378610.81 | 876023.68 | 0.00 | 0.147219E+10 | 0.00 | 1.09 |
August | 0.189375E+09 | 0.648785E+09 | 0.00 | 4753773.16 | 2652100.34 | 0.00 | 0.129467E+10 | 0.00 | 1.10 |
September | 0.241578E+09 | 0.201300E+09 | 0.00 | 6211263.34 | 480025.43 | 0.00 | 0.267294E+10 | 0.00 | 1.13 |
October | 0.282731E+09 | 0.489191E+09 | 0.00 | 5245326.03 | 2739661.40 | 0.00 | 0.240261E+10 | 0.00 | 1.03 |
November | 0.597491E+09 | 16809750.47 | 0.00 | 4129093.40 | 0.00 | 0.00 | 0.343889E+10 | 0.00 | 0.78 |
December | 0.113009E+10 | 11440594.68 | 0.00 | 3402674.35 | 0.00 | 0.00 | 0.253682E+10 | 0.00 | 0.75 |
Annual Sum or Average | 0.839771E+10 | 0.203242E+10 | 0.00 | 50648781.78 | 6747810.85 | 14644596.65 | 0.298185E+11 | 0.00 | 0.90 |
Minimum of Months | 0.179444E+09 | 0.00 | 0.00 | 1992055.59 | 0.00 | 0.00 | 0.129467E+10 | 0.00 | 0.61 |
Maximum of Months | 0.190199E+10 | 0.648785E+09 | 0.00 | 6211263.34 | 2739661.40 | 11422313.45 | 0.361873E+10 | 0.00 | 1.16 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.138184E+10 | 20304475.97 | 0.00 | 2453103.42 | 0.00 | 23182787.27 | 0.210653E+10 | 0.00 | 0.64 |
February | 0.139150E+10 | 7353230.89 | 0.00 | 1841236.45 | 0.00 | 0.00 | 0.192104E+10 | 0.00 | 0.58 |
March | 0.206789E+10 | 0.00 | 0.00 | 1578282.15 | 0.00 | 15919694.82 | 0.145416E+10 | 0.00 | 0.58 |
April | 0.677531E+09 | 25112041.58 | 0.00 | 3662320.91 | 0.00 | 0.00 | 0.285903E+10 | 0.00 | 0.87 |
May | 0.544043E+09 | 7332439.73 | 0.00 | 4239848.29 | 0.00 | 0.00 | 0.340755E+10 | 0.00 | 0.93 |
June | 0.275894E+09 | 73889886.28 | 0.00 | 5243325.88 | 0.00 | 0.00 | 0.275555E+10 | 0.00 | 1.14 |
July | 0.181547E+09 | 0.508252E+09 | 0.00 | 5079922.45 | 941310.99 | 0.00 | 0.146457E+10 | 0.00 | 1.08 |
August | 0.189028E+09 | 0.625847E+09 | 0.00 | 4524429.73 | 2649003.03 | 0.00 | 0.128810E+10 | 0.00 | 1.09 |
September | 0.246894E+09 | 0.196232E+09 | 0.00 | 5862468.59 | 483773.49 | 0.00 | 0.262570E+10 | 0.00 | 1.12 |
October | 0.298883E+09 | 0.483076E+09 | 0.00 | 4955319.73 | 2754631.88 | 0.00 | 0.234638E+10 | 0.00 | 1.01 |
November | 0.648859E+09 | 16546893.76 | 0.00 | 3691196.31 | 0.00 | 0.00 | 0.320704E+10 | 0.00 | 0.75 |
December | 0.125281E+10 | 11250901.17 | 0.00 | 2949254.47 | 0.00 | 0.00 | 0.226698E+10 | 0.00 | 0.72 |
Annual Sum or Average | 0.915672E+10 | 0.197520E+10 | 0.00 | 46080708.40 | 6828719.39 | 39102482.09 | 0.277026E+11 | 0.00 | 0.88 |
Minimum of Months | 0.181547E+09 | 0.00 | 0.00 | 1578282.15 | 0.00 | 0.00 | 0.128810E+10 | 0.00 | 0.58 |
Maximum of Months | 0.206789E+10 | 0.625847E+09 | 0.00 | 5862468.59 | 2754631.88 | 23182787.27 | 0.340755E+10 | 0.00 | 1.14 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.325225E+10 | 13145948.96 | 0.00 | 3228645.45 | 0.00 | 31737888.95 | 0.226797E+10 | 0.00 | 0.46 |
February | 0.352068E+10 | 5600071.33 | 0.00 | 2011385.61 | 0.00 | 1233552.70 | 0.180001E+10 | 0.00 | 0.44 |
March | 0.457435E+10 | 738328.05 | 0.00 | 1877559.43 | 127851.33 | 27357720.31 | 0.126855E+10 | 0.00 | 0.45 |
April | 0.136994E+10 | 35299395.24 | 0.00 | 5598275.58 | 394311.68 | 1440638.59 | 0.373427E+10 | 0.00 | 0.57 |
May | 0.115597E+10 | 7027172.65 | 0.00 | 6417583.74 | 0.00 | 0.00 | 0.445885E+10 | 0.00 | 0.60 |
June | 0.319287E+09 | 0.104623E+09 | 0.00 | 8255884.98 | 0.00 | 0.00 | 0.368900E+10 | 0.00 | 0.69 |
July | 0.108066E+09 | 0.838644E+09 | 0.00 | 7441320.99 | 2802318.40 | 0.00 | 0.173673E+10 | 0.00 | 0.66 |
August | 79571088.96 | 0.103789E+10 | 0.00 | 6207141.90 | 9357486.22 | 0.00 | 0.159683E+10 | 0.00 | 0.67 |
September | 0.293268E+09 | 0.326170E+09 | 0.00 | 9146029.37 | 1479694.11 | 0.00 | 0.328516E+10 | 0.00 | 0.68 |
October | 0.240224E+09 | 0.749955E+09 | 0.00 | 7973477.54 | 6979445.80 | 0.00 | 0.318717E+10 | 0.00 | 0.64 |
November | 0.186555E+10 | 13781446.65 | 0.00 | 5104056.66 | 0.00 | 0.00 | 0.392836E+10 | 0.00 | 0.51 |
December | 0.297196E+10 | 9166774.86 | 0.00 | 4080793.78 | 0.00 | 0.00 | 0.251282E+10 | 0.00 | 0.49 |
Annual Sum or Average | 0.197511E+11 | 0.314204E+10 | 0.00 | 67342155.03 | 21141107.54 | 61769800.54 | 0.334657E+11 | 0.00 | 0.57 |
Minimum of Months | 79571088.96 | 738328.05 | 0.00 | 1877559.43 | 0.00 | 0.00 | 0.126855E+10 | 0.00 | 0.44 |
Maximum of Months | 0.457435E+10 | 0.103789E+10 | 0.00 | 9146029.37 | 9357486.22 | 31737888.95 | 0.445885E+10 | 0.00 | 0.69 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.127730E+10 | 10394120.58 | 0.00 | 2072332.40 | 0.00 | 15628053.13 | 0.194894E+10 | 0.00 | 0.57 |
February | 0.144573E+10 | 4219266.56 | 0.00 | 1392988.04 | 0.00 | 0.00 | 0.161405E+10 | 0.00 | 0.52 |
March | 0.205994E+10 | 21651.18 | 0.00 | 1212076.27 | 0.00 | 11294341.46 | 0.123101E+10 | 0.00 | 0.52 |
April | 0.473335E+09 | 18795191.45 | 0.00 | 3250798.69 | 0.00 | 0.00 | 0.280224E+10 | 0.00 | 0.78 |
May | 0.327507E+09 | 3780668.83 | 0.00 | 3728704.60 | 0.00 | 0.00 | 0.335824E+10 | 0.00 | 0.84 |
June | 92509478.30 | 43580892.77 | 0.00 | 4899321.84 | 0.00 | 0.00 | 0.276089E+10 | 0.00 | 1.03 |
July | 56290772.62 | 0.385281E+09 | 0.00 | 4619231.33 | 1031620.81 | 0.00 | 0.146437E+10 | 0.00 | 0.98 |
August | 39198731.24 | 0.473915E+09 | 0.00 | 4230680.88 | 5373693.22 | 0.00 | 0.134276E+10 | 0.00 | 0.99 |
September | 93176502.96 | 0.148954E+09 | 0.00 | 5330447.98 | 700872.04 | 0.00 | 0.259187E+10 | 0.00 | 1.01 |
October | 93915826.38 | 0.384295E+09 | 0.00 | 4496895.72 | 2679962.38 | 0.00 | 0.238289E+10 | 0.00 | 0.92 |
November | 0.405582E+09 | 8942360.42 | 0.00 | 3293237.41 | 0.00 | 0.00 | 0.315392E+10 | 0.00 | 0.66 |
December | 0.118489E+10 | 5863997.21 | 0.00 | 2499780.46 | 0.00 | 0.00 | 0.208895E+10 | 0.00 | 0.65 |
Annual Sum or Average | 0.754939E+10 | 0.148804E+10 | 0.00 | 41026495.63 | 9786148.45 | 26922394.59 | 0.267401E+11 | 0.00 | 0.79 |
Minimum of Months | 39198731.24 | 21651.18 | 0.00 | 1212076.27 | 0.00 | 0.00 | 0.123101E+10 | 0.00 | 0.52 |
Maximum of Months | 0.205994E+10 | 0.473915E+09 | 0.00 | 5330447.98 | 5373693.22 | 15628053.13 | 0.335824E+10 | 0.00 | 1.03 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.129159E+10 | 10287602.08 | 0.00 | 1997996.87 | 0.00 | 19367481.18 | 0.190221E+10 | 0.00 | 0.57 |
February | 0.148874E+10 | 4236969.87 | 0.00 | 1332125.12 | 0.00 | 0.00 | 0.154190E+10 | 0.00 | 0.51 |
March | 0.208430E+10 | 29589.79 | 0.00 | 1170218.32 | 0.00 | 13595990.95 | 0.118325E+10 | 0.00 | 0.52 |
April | 0.489950E+09 | 18766672.97 | 0.00 | 3162645.84 | 0.00 | 0.00 | 0.275154E+10 | 0.00 | 0.77 |
May | 0.342955E+09 | 3741562.96 | 0.00 | 3623004.26 | 0.00 | 0.00 | 0.330268E+10 | 0.00 | 0.83 |
June | 97267267.15 | 42424126.81 | 0.00 | 4786119.63 | 0.00 | 0.00 | 0.273159E+10 | 0.00 | 1.02 |
July | 56556778.11 | 0.380200E+09 | 0.00 | 4564190.39 | 1067913.49 | 0.00 | 0.145984E+10 | 0.00 | 0.97 |
August | 39366520.77 | 0.466914E+09 | 0.00 | 4158662.63 | 5303820.73 | 0.00 | 0.133665E+10 | 0.00 | 0.98 |
September | 97062966.14 | 0.147750E+09 | 0.00 | 5212925.55 | 694316.44 | 0.00 | 0.257154E+10 | 0.00 | 1.00 |
October | 94960411.53 | 0.382145E+09 | 0.00 | 4409864.73 | 2749467.88 | 0.00 | 0.236420E+10 | 0.00 | 0.92 |
November | 0.435815E+09 | 8912257.65 | 0.00 | 3186707.90 | 0.00 | 0.00 | 0.308346E+10 | 0.00 | 0.66 |
December | 0.120708E+10 | 5828870.29 | 0.00 | 2410977.95 | 0.00 | 0.00 | 0.203766E+10 | 0.00 | 0.64 |
Annual Sum or Average | 0.772565E+10 | 0.147124E+10 | 0.00 | 40015439.19 | 9815518.53 | 32963472.13 | 0.262665E+11 | 0.00 | 0.78 |
Minimum of Months | 39366520.77 | 29589.79 | 0.00 | 1170218.32 | 0.00 | 0.00 | 0.118325E+10 | 0.00 | 0.51 |
Maximum of Months | 0.208430E+10 | 0.466914E+09 | 0.00 | 5212925.55 | 5303820.73 | 19367481.18 | 0.330268E+10 | 0.00 | 1.02 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.145474E+10 | 9862703.76 | 0.00 | 1599318.47 | 0.00 | 36220222.56 | 0.158426E+10 | 0.00 | 0.55 |
February | 0.166410E+10 | 4077067.54 | 0.00 | 1020567.42 | 0.00 | 1634773.29 | 0.121385E+10 | 0.00 | 0.49 |
March | 0.219718E+10 | 247452.26 | 0.00 | 938465.23 | 34280.61 | 33693720.35 | 0.935482E+09 | 0.00 | 0.51 |
April | 0.573085E+09 | 18422943.62 | 0.00 | 2768672.44 | 294597.50 | 1979976.45 | 0.252797E+10 | 0.00 | 0.74 |
May | 0.451171E+09 | 3575900.65 | 0.00 | 3170286.88 | 0.00 | 0.00 | 0.303475E+10 | 0.00 | 0.79 |
June | 0.118932E+09 | 38601553.83 | 0.00 | 4366996.78 | 0.00 | 0.00 | 0.263283E+10 | 0.00 | 1.00 |
July | 57726004.84 | 0.365908E+09 | 0.00 | 4314109.49 | 891522.36 | 0.00 | 0.145755E+10 | 0.00 | 0.96 |
August | 41698851.34 | 0.445347E+09 | 0.00 | 3943395.57 | 5019995.53 | 0.00 | 0.132491E+10 | 0.00 | 0.97 |
September | 0.118729E+09 | 0.143711E+09 | 0.00 | 4831403.08 | 562017.68 | 0.00 | 0.250879E+10 | 0.00 | 0.99 |
October | 0.107187E+09 | 0.375915E+09 | 0.00 | 4090004.98 | 2676032.77 | 0.00 | 0.230809E+10 | 0.00 | 0.90 |
November | 0.661981E+09 | 8841595.92 | 0.00 | 2621717.42 | 0.00 | 0.00 | 0.267273E+10 | 0.00 | 0.62 |
December | 0.137544E+10 | 5685196.69 | 0.00 | 1988331.06 | 0.00 | 0.00 | 0.173112E+10 | 0.00 | 0.62 |
Annual Sum or Average | 0.882197E+10 | 0.142020E+10 | 0.00 | 35653268.84 | 9478446.43 | 73528692.65 | 0.239323E+11 | 0.00 | 0.76 |
Minimum of Months | 41698851.34 | 247452.26 | 0.00 | 938465.23 | 0.00 | 0.00 | 0.935482E+09 | 0.00 | 0.49 |
Maximum of Months | 0.219718E+10 | 0.445347E+09 | 0.00 | 4831403.08 | 5019995.53 | 36220222.56 | 0.303475E+10 | 0.00 | 1.00 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.161158E+10 | 10371597.34 | 0.00 | 1184464.39 | 105457.02 | 88222495.12 | 0.118882E+10 | 0.00 | 0.54 |
February | 0.171443E+10 | 3926309.75 | 0.00 | 695679.24 | 0.00 | 64594800.91 | 0.888795E+09 | 0.00 | 0.48 |
March | 0.211767E+10 | 708223.18 | 0.00 | 810420.53 | 806159.06 | 0.160335E+09 | 0.767063E+09 | 0.00 | 0.51 |
April | 0.685420E+09 | 20771847.36 | 0.00 | 2512470.56 | 40683.96 | 1355122.53 | 0.235901E+10 | 0.00 | 0.76 |
May | 0.618053E+09 | 4209969.50 | 0.00 | 2788749.46 | 0.00 | 0.00 | 0.276997E+10 | 0.00 | 0.80 |
June | 0.187144E+09 | 46231213.72 | 0.00 | 3950257.15 | 0.00 | 0.00 | 0.252176E+10 | 0.00 | 1.04 |
July | 64235509.19 | 0.408975E+09 | 0.00 | 4096397.04 | 1406124.93 | 0.00 | 0.151174E+10 | 0.00 | 1.03 |
August | 45716503.39 | 0.503773E+09 | 0.00 | 3620817.22 | 5197763.97 | 0.00 | 0.136073E+10 | 0.00 | 1.04 |
September | 0.176777E+09 | 0.150405E+09 | 0.00 | 4405014.14 | 711050.60 | 0.00 | 0.248237E+10 | 0.00 | 1.03 |
October | 0.142898E+09 | 0.386199E+09 | 0.00 | 3560126.55 | 3196420.61 | 0.00 | 0.226953E+10 | 0.00 | 0.94 |
November | 0.107435E+10 | 11237602.25 | 0.00 | 1897221.89 | 49823.44 | 0.00 | 0.201827E+10 | 0.00 | 0.60 |
December | 0.155217E+10 | 6717084.83 | 0.00 | 1473828.72 | 0.00 | 2016660.82 | 0.133836E+10 | 0.00 | 0.61 |
Annual Sum or Average | 0.999044E+10 | 0.155353E+10 | 0.00 | 30995446.89 | 11513483.59 | 0.316524E+09 | 0.214764E+11 | 0.00 | 0.78 |
Minimum of Months | 45716503.39 | 708223.18 | 0.00 | 695679.24 | 0.00 | 0.00 | 0.767063E+09 | 0.00 | 0.48 |
Maximum of Months | 0.211767E+10 | 0.503773E+09 | 0.00 | 4405014.14 | 5197763.97 | 0.160335E+09 | 0.276997E+10 | 0.00 | 1.04 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.163178E+12 | 0.129373E+11 | 0.00 | 0.428543E+11 | 0.874076E+10 |
February | 0.200984E+12 | 0.135801E+11 | 0.00 | 0.403009E+11 | 0.215776E+10 |
March | 0.284078E+12 | 0.146020E+11 | 0.00 | 0.436409E+11 | 0.445277E+10 |
April | 0.382874E+12 | 0.910456E+10 | 0.00 | 0.423046E+11 | 0.138397E+11 |
May | 0.401926E+12 | 0.971028E+10 | 0.00 | 0.469406E+11 | 0.104746E+11 |
June | 0.403904E+12 | 0.525531E+10 | 0.00 | 0.356420E+11 | 0.343506E+11 |
July | 0.434403E+12 | 29834666.01 | 0.00 | 0.150567E+11 | 0.765555E+11 |
August | 0.397853E+12 | -679180582.8 | 0.00 | 0.117433E+11 | 0.855494E+11 |
September | 0.311868E+12 | 0.363978E+10 | 0.00 | 0.319370E+11 | 0.483431E+11 |
October | 0.211133E+12 | 0.333778E+10 | 0.00 | 0.266357E+11 | 0.595497E+11 |
November | 0.179019E+12 | 0.122225E+11 | 0.00 | 0.460825E+11 | 0.822498E+10 |
December | 0.143351E+12 | 0.129213E+11 | 0.00 | 0.428833E+11 | 0.108855E+11 |
Annual Sum or Average | 0.351457E+13 | 0.966616E+11 | 0.00 | 0.426022E+12 | 0.363124E+12 |
Minimum of Months | 0.143351E+12 | -679180582.8 | 0.00 | 0.117433E+11 | 0.215776E+10 |
Maximum of Months | 0.434403E+12 | 0.146020E+11 | 0.00 | 0.469406E+11 | 0.855494E+11 |