Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:41
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Simulation Timestamp: 2023-10-16 08:41:13
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1213.12 | 580.35 | 580.35 |
Net Site Energy | 1213.12 | 580.35 | 580.35 |
Total Source Energy | 3301.18 | 1579.27 | 1579.27 |
Net Source Energy | 3301.18 | 1579.27 | 1579.27 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 259.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 33.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 441.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 185.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 64.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 953.51 | 259.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 259.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 33.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 441.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 185.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 64.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 259.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 33.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 441.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 185.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 64.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 259.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 135.48 | 124.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 456.16 | 124.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 259.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 135.48 | 124.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 456.16 | 124.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 953.511 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 953.511 | 100.00 |
Total On-Site and Utility Electric Sources | 953.511 | 100.00 |
Total Electricity End Uses | 953.511 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1285.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:41 |
RunPeriod | RUNPERIOD 1 |
Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Latitude [deg] | 47.47 |
Longitude [deg] | -122.3 |
Elevation [m] | 122.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.77 | 20.77 | 17.8770 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.38 | 10.38 | 19.3382 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 17.3739 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 17.3739 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 17.3739 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.72 | 20.72 | 13.1675 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.3365 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.3365 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.3365 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.36 | 10.36 | 13.3365 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 15.5746 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 15.5746 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 17.8770 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 19.3382 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 17.3739 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 17.3739 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 17.3739 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 13.1675 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 13.3365 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 13.3365 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 13.3365 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 13.3365 | 6.19 | 4.3000 | |
Total | 2090.32 | 15.5746 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 15.5746 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 15.5746 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 29-AUG-15:50 | 26-DEC-09:09 | - | - | - | - | - | - | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 169226.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 27932.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 27522.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 11189.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 7554.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 82287.86 | 169226.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 169226.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 27932.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 27522.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 11189.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 7554.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 281.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 104.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1398.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 316.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 407.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 588.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 203.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3019.77 | 281.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 134.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 50.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 668.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 151.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 281.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 97.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1444.65 | 134.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 134.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 50.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 668.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 151.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 281.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 97.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1444.65 | 134.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 1.99 |
SMSTORE1 DIRECT AIR | 1.05 |
SMSTORE2 DIRECT AIR | 1.05 |
SMSTORE3 DIRECT AIR | 1.05 |
SMSTORE4 DIRECT AIR | 1.05 |
LGSTORE2 DIRECT AIR | 1.94 |
SMSTORE5 DIRECT AIR | 1.00 |
SMSTORE6 DIRECT AIR | 0.995952 |
SMSTORE7 DIRECT AIR | 0.988599 |
SMSTORE8 DIRECT AIR | 1.06 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 1.99 | 1.99 | 1.99 | 1.99 | 1.99 | 1.99 | 1.00 | 1.00 | 1.99 |
PSZ-AC_2:2 | 1.05 | 1.05 | 1.05 | 1.05 | 1.05 | 1.05 | 1.00 | 1.00 | 1.05 |
PSZ-AC_3:3 | 1.05 | 1.05 | 1.05 | 1.05 | 1.05 | 1.05 | 1.00 | 1.00 | 1.05 |
PSZ-AC_4:4 | 1.05 | 1.05 | 1.05 | 1.05 | 1.05 | 1.05 | 1.00 | 1.00 | 1.05 |
PSZ-AC_5:5 | 1.05 | 1.05 | 1.05 | 1.05 | 1.05 | 1.05 | 1.00 | 1.00 | 1.05 |
PSZ-AC_6:6 | 1.94 | 1.94 | 1.94 | 1.94 | 1.94 | 1.94 | 1.00 | 1.000000 | 1.94 |
PSZ-AC_7:7 | 1.00 | 1.00 | 1.00 | 1.00 | 1.01 | 1.01 | 1.00 | 0.994432 | 1.01 |
PSZ-AC_8:8 | 0.995952 | 0.995952 | 0.995952 | 0.995952 | 1.00 | 1.00 | 1.00 | 0.994062 | 1.00 |
PSZ-AC_9:9 | 0.988599 | 0.988599 | 0.988599 | 0.988599 | 0.995770 | 0.995770 | 1.00 | 0.992798 | 0.995770 |
PSZ-AC_10:10 | 1.06 | 1.06 | 1.06 | 1.06 | 1.07 | 1.07 | 1.00 | 0.985692 | 1.07 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 1.99 | 0.411479 |
PSZ-AC_2:2_OA_CONTROLLER | 1.05 | 0.205739 |
PSZ-AC_3:3_OA_CONTROLLER | 1.05 | 0.205739 |
PSZ-AC_4:4_OA_CONTROLLER | 1.05 | 0.205739 |
PSZ-AC_5:5_OA_CONTROLLER | 1.05 | 0.205739 |
PSZ-AC_6:6_OA_CONTROLLER | 1.94 | 0.411479 |
PSZ-AC_7:7_OA_CONTROLLER | 1.01 | 0.205739 |
PSZ-AC_8:8_OA_CONTROLLER | 1.00 | 0.205739 |
PSZ-AC_9:9_OA_CONTROLLER | 0.995770 | 0.205739 |
PSZ-AC_10:10_OA_CONTROLLER | 1.07 | 0.205739 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 1.99 | 2131.15 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.05 | 1166.10 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.05 | 1164.04 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.05 | 1167.69 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.05 | 1163.11 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 1.94 | 2074.70 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 1.01 | 1114.79 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 1.00 | 1109.26 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 0.995770 | 1102.48 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.07 | 1186.88 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 1.99 | 1.99 | 1.99 | 1.31 | 34604.53 | 57301.67 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.05 | 1.05 | 1.05 | 1.05 | 18184.09 | 29944.47 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.05 | 1.05 | 1.05 | 1.05 | 18155.51 | 29902.47 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.05 | 1.05 | 1.05 | 1.05 | 18206.34 | 29976.81 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.05 | 1.05 | 1.05 | 1.05 | 18142.80 | 29883.64 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 1.94 | 1.94 | 1.94 | 1.28 | 33800.80 | 56112.28 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 1.01 | 1.01 | 1.01 | 1.01 | 17475.04 | 28773.87 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 1.00 | 1.00 | 1.00 | 1.00 | 17399.68 | 28653.60 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 0.995770 | 0.995770 | 0.995770 | 0.995770 | 17300.61 | 28487.88 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.07 | 1.07 | 1.07 | 1.07 | 18314.20 | 30022.53 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 1.99 | 0.995819 | 1.33 | 34604.53 | 17302.26 | 0.800280 | 0.800280 |
PSZ-AC_2:2 COOLING COIL | 1.05 | 0.526618 | 0.702160 | 18184.09 | 9092.05 | 0.800510 | 0.800510 |
PSZ-AC_3:3 COOLING COIL | 1.05 | 0.525686 | 0.700913 | 18155.51 | 9077.75 | 0.800440 | 0.800440 |
PSZ-AC_4:4 COOLING COIL | 1.05 | 0.527336 | 0.703113 | 18206.34 | 9103.17 | 0.800550 | 0.800550 |
PSZ-AC_5:5 COOLING COIL | 1.05 | 0.525268 | 0.700360 | 18142.80 | 9071.40 | 0.800400 | 0.800400 |
PSZ-AC_6:6 COOLING COIL | 1.94 | 0.969445 | 1.29 | 33800.80 | 16900.40 | 0.800110 | 0.800110 |
PSZ-AC_7:7 COOLING COIL | 1.01 | 0.503448 | 0.671267 | 17475.04 | 8737.52 | 0.800670 | 0.800670 |
PSZ-AC_8:8 COOLING COIL | 1.00 | 0.500951 | 0.667933 | 17399.68 | 8699.84 | 0.800440 | 0.800440 |
PSZ-AC_9:9 COOLING COIL | 0.995770 | 0.497885 | 0.663847 | 17300.61 | 8650.31 | 0.800290 | 0.800290 |
PSZ-AC_10:10 COOLING COIL | 1.07 | 0.536002 | 0.714667 | 18314.20 | 9157.10 | 0.800240 | 0.800240 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 57301.67 |
PSZ-AC_2:2 HEATING COIL | 29944.47 |
PSZ-AC_3:3 HEATING COIL | 29902.47 |
PSZ-AC_4:4 HEATING COIL | 29976.81 |
PSZ-AC_5:5 HEATING COIL | 29883.64 |
PSZ-AC_6:6 HEATING COIL | 56112.28 |
PSZ-AC_7:7 HEATING COIL | 28773.87 |
PSZ-AC_8:8 HEATING COIL | 28653.60 |
PSZ-AC_9:9 HEATING COIL | 28487.88 |
PSZ-AC_10:10 HEATING COIL | 30022.53 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 11.40 | 8.10 | 5.40 | 4.50 | 5.80 | 8.30 | 10.90 | 13.00 | 15.60 | 17.70 | 18.80 | 15.10 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 | 47.47 | -122.32 | -8.00 | 122.00 | 99868 | 1.1870 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 11.22 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.74 | 20.77 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.66 | 10.38 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.41 | 20.72 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.12 | 10.36 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 17.877 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.177 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 19.338 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 23.638 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 17.374 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.674 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 17.374 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.674 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 17.374 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.674 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 13.168 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.468 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 13.336 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.636 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 13.336 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.636 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 13.336 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.636 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 13.336 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.636 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 4596.695 | 13.194 | 81.718 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4596.695 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 1631.408 | 4.683 | 29.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1631.408 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 2327.780 | 13.363 | 82.767 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2327.780 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1040.795 | 5.975 | 37.007 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1040.795 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 2323.122 | 13.336 | 82.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2323.122 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 703.295 | 4.037 | 25.007 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 703.295 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 2323.122 | 13.336 | 82.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2323.122 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 703.295 | 4.037 | 25.007 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 703.295 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 2323.122 | 13.336 | 82.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2323.122 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 703.295 | 4.037 | 25.007 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 703.295 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 4587.379 | 13.168 | 81.553 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4587.379 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 2323.122 | 13.336 | 82.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2323.122 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 2323.122 | 13.336 | 82.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2323.122 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 2323.122 | 13.336 | 82.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2323.122 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 2323.122 | 13.336 | 82.601 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2323.122 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.6641 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1464 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2111 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.272 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.756 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.659 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
19 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
20 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
21 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
22 | 7 | -0.32972738E-12 | 0.11763143E-14 | -0.10490290E-12 | 0.10060316E-15 |
23 | 6 | 0.30001920E-07 | 0.18927851E-09 | 0.68616814E-08 | -0.14235861E-12 |
24 | 5 | -0.19683904E-03 | 0.16062604E-05 | -0.10115234E-03 | 0.67789156E-08 |
25 | 4 | 0.29998857 | 0.77587294E-03 | 0.10250533 | -0.34681058E-04 |
26 | 3 | -7.4215481 | 0.23875067E-01 | -2.3849775 | 0.29769922E-01 |
27 | 2 | 41.382972 | 0.84366340E-01 | 15.453844 | -0.33904133 |
28 | 1 | -80.937908 | 0.37867119E-01 | -29.310851 | 1.0869756 |
29 | 0 | 46.824336 | 0.75775345E-03 | 16.287225 | |
30 | 7 | -0.28997596E-08 | -0.17578320E-14 | 0.22751757E-14 | -0.53829073E-16 |
31 | 6 | 0.41991781E-05 | 0.27986603E-08 | 0.31940183E-02 | -0.26794102E-04 |
32 | 5 | -0.29588474E-03 | 0.16552611E-05 | -0.22396035 | 0.19582313E-02 |
33 | 4 | 0.67666006E-02 | 0.75295852E-04 | 4.8334724 | -0.45302727E-01 |
34 | 3 | -0.59297736E-01 | 0.59838054E-03 | -38.043598 | 0.39889893 |
35 | 2 | 0.21038411 | 0.99492606E-03 | 116.52712 | -1.4185167 |
36 | 1 | -0.30354941 | 0.30287292E-03 | -143.93272 | 2.0494576 |
37 | 0 | 0.14796861 | 0.73483799E-05 | 60.838472 | |
38 | 7 | -0.51571905E-08 | -0.97500959E-14 | 0.15789915E-14 | -0.32998988E-16 |
39 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
40 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
41 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
42 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
43 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
44 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
45 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
46 | 7 | -0.51571905E-08 | -0.97500958E-14 | 0.15789913E-14 | -0.32998984E-16 |
47 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
48 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
49 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
50 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
51 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
52 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
53 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
54 | 7 | -0.51571905E-08 | -0.97500959E-14 | 0.15789911E-14 | -0.32998980E-16 |
55 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
56 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
57 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
58 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
59 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
60 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
61 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
62 | 7 | -0.51571905E-08 | -0.97500959E-14 | 0.15789915E-14 | -0.32998988E-16 |
63 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
64 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
65 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
66 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
67 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
68 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
69 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
70 | 7 | -0.51571905E-08 | -0.97500958E-14 | 0.15789913E-14 | -0.32998984E-16 |
71 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
72 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
73 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
74 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
75 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
76 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
77 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
78 | 7 | -0.51571905E-08 | -0.97500957E-14 | 0.15789917E-14 | -0.32998991E-16 |
79 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
80 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
81 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
82 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
83 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
84 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
85 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
86 | 7 | -0.51571905E-08 | -0.97500959E-14 | 0.15789915E-14 | -0.32998988E-16 |
87 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
88 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
89 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
90 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
91 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
92 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
93 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
94 | 7 | -0.51571905E-08 | -0.97500958E-14 | 0.15789913E-14 | -0.32998984E-16 |
95 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
96 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
97 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
98 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
99 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
100 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
101 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
102 | 7 | -0.19967951E-08 | -0.58252365E-15 | 0.72897552E-14 | -0.10630581E-15 |
103 | 6 | 0.59274927E-05 | 0.40433693E-08 | 0.31889525E-02 | -0.26751606E-04 |
104 | 5 | -0.42514865E-03 | 0.23948505E-05 | -0.22367243 | 0.19556901E-02 |
105 | 4 | 0.97725356E-02 | 0.10900143E-03 | 4.8286774 | -0.45256634E-01 |
106 | 3 | -0.85796444E-01 | 0.86675557E-03 | -38.016512 | 0.39859954 |
107 | 2 | 0.30461848 | 0.14417950E-02 | 116.47440 | -1.4178116 |
108 | 1 | -0.43965446 | 0.43929230E-03 | -143.90169 | 2.0489476 |
109 | 0 | 0.21434897 | 0.10616597E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 35 | 1 | VerySmooth | 2.168 | 2.168 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 3.44376E-002 | 0.31435 | 0.47922 | 0.47922 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11914 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 0.157 | 4.517E-004 | 2.488E-004 | 0.314 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 3.813E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 8.993E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 4.692E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 0.112 | 6.453E-004 | 2.994E-004 | 0.448 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 3.583E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 22294.65127 | 26753.58152 | 1.65970 | 1.99164 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 29.40000 | 8.82150E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 19691.83742 | 23630.20491 | 0.86111 | 1.03334 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 11790.13720 | 14148.16464 | 0.87770 | 1.05324 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 29.40000 | 8.82150E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 9073.31884 | 10887.98261 | 0.39678 | 0.47613 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 11769.27288 | 14123.12745 | 0.87614 | 1.05137 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 29.31333 | 8.82136E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 9177.82157 | 11013.38588 | 0.40135 | 0.48162 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 11806.20471 | 14167.44565 | 0.87889 | 1.05467 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 29.31333 | 8.82136E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 9276.81871 | 11132.18245 | 0.40568 | 0.48681 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 11759.92306 | 14111.90767 | 0.87545 | 1.05054 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 29.31333 | 8.82136E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 9453.41626 | 11344.09951 | 0.41340 | 0.49608 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 21704.16966 | 26045.00360 | 1.61574 | 1.93889 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 29.31333 | 8.82136E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 18363.00467 | 22035.60561 | 0.80302 | 0.96363 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 11539.98875 | 13847.98650 | 0.83441 | 1.00129 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 25.44800 | 8.81519E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 9764.33577 | 11717.20292 | 0.42700 | 0.51239 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 11479.95363 | 13775.94436 | 0.82996 | 0.99595 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 25.44800 | 8.81519E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 9765.67376 | 11718.80851 | 0.42705 | 0.51246 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 11397.01972 | 13676.42367 | 0.82383 | 0.98860 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 25.44800 | 8.81519E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 10050.94168 | 12061.13002 | 0.43953 | 0.52743 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 12160.43543 | 14592.52252 | 0.88056 | 1.05667 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 25.44800 | 8.81519E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 12473.86830 | 14968.64196 | 0.54546 | 0.65455 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 29045.17 | 1.99164 | 1.99164 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 35706.54 | 1.03334 | 1.03334 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 15282.01 | 1.05324 | 1.05324 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 16939.72 | 0.47613 | 0.47613 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 15257.02 | 1.05137 | 1.05137 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 17063.29 | 0.48162 | 0.48162 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 15299.88 | 1.05467 | 1.05467 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 17180.36 | 0.48681 | 0.48681 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 15245.13 | 1.05054 | 1.05054 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 17389.19 | 0.49608 | 0.49608 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 28336.65 | 1.93889 | 1.93889 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 34135.38 | 0.96363 | 0.96363 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 14641.91 | 1.00690 | 1.00690 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 17756.86 | 0.51239 | 0.51239 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 14565.23 | 1.00190 | 1.00190 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 17758.45 | 0.51246 | 0.51246 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 14515.08 | 0.99577 | 0.99577 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 18095.78 | 0.52743 | 0.52743 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 15318.85 | 1.07200 | 1.07200 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 20960.76 | 0.65455 | 0.65455 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.99164 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.05324 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.05137 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.05467 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.05054 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.93889 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.00129 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.99595 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.98860 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.05667 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.99164 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.99164 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.99164 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.99164 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.99164 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.99164 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.05324 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.05324 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.05324 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.05324 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.05324 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.05324 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.05137 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.05137 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.05137 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.05137 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.05137 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.05137 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.05467 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.05467 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.05467 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.05467 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.05467 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.05467 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.05054 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.05054 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.05054 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.05054 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.05054 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.05054 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.93889 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.93889 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.93889 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.93889 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.93889 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 1.93889 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.00129 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.00129 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.00129 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.00129 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.00690 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 1.00690 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 0.99443 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.99595 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.99595 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.99595 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.99595 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.00190 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 1.00190 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 0.99406 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.98860 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.98860 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.98860 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.98860 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.99577 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 0.99577 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 0.99280 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.05667 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.05667 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.05667 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.05667 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.07200 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.07200 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 0.98569 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 1.99164 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.05324 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.05137 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.05467 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.05054 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 1.93889 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 1.00690 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 1.00190 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 0.99577 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.07200 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.99164 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.99164 |
104 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2131.14584 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.99164 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.99164 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.99164 |
108 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.31448 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.99164 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.99582 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.32776 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 34604.53000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 17302.26500 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80028 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80028 |
116 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 34604.53000 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 57301.67032 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
120 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 57301.67032 |
121 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.05324 |
122 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
123 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.05324 |
124 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1166.09901 |
125 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.05324 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.05324 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.05324 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.05324 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.05324 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52662 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.70216 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 18184.09000 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 9092.04500 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80051 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80051 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18184.09000 |
137 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29944.47264 |
138 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
139 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
140 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 29944.47264 |
141 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.05137 |
142 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
143 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.05137 |
144 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1164.03566 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.05137 |
146 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.05137 |
147 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.05137 |
148 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.05137 |
149 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.05137 |
150 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52569 |
151 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.70091 |
152 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 18155.51000 |
153 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 9077.75500 |
154 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80044 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80044 |
156 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18155.51000 |
157 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29902.46816 |
158 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
159 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
160 | Coil:Heating:Fuel | PSZ-AC_3:3 HEATING COIL | Design Size Nominal Capacity [W] | 29902.46816 |
161 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.05467 |
162 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
163 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.05467 |
164 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1167.68837 |
165 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.05467 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.05467 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.05467 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.05467 |
169 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.05467 |
170 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52734 |
171 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.70311 |
172 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 18206.34000 |
173 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 9103.17000 |
174 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80055 |
175 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80055 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18206.34000 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29976.81279 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
179 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
180 | Coil:Heating:Fuel | PSZ-AC_4:4 HEATING COIL | Design Size Nominal Capacity [W] | 29976.81279 |
181 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.05054 |
182 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
183 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.05054 |
184 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1163.11080 |
185 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.05054 |
186 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.05054 |
187 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.05054 |
188 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.05054 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.05054 |
190 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52527 |
191 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.70036 |
192 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 18142.80000 |
193 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 9071.40000 |
194 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80040 |
195 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80040 |
196 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18142.80000 |
197 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29883.63500 |
198 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
200 | Coil:Heating:Fuel | PSZ-AC_5:5 HEATING COIL | Design Size Nominal Capacity [W] | 29883.63500 |
201 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.93889 |
202 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
203 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.93889 |
204 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2074.70409 |
205 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.93889 |
206 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.93889 |
207 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.93889 |
208 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.27967 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.93889 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.96945 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.29259 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 33800.80000 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 16900.40000 |
214 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80011 |
215 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80011 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 33800.80000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 56112.27527 |
218 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
219 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
220 | Coil:Heating:Fuel | PSZ-AC_6:6 HEATING COIL | Design Size Nominal Capacity [W] | 56112.27527 |
221 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.00690 |
222 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
223 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.00690 |
224 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1114.79313 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.00690 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.00690 |
227 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.00690 |
228 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.00690 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.00690 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.50345 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.67127 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 17475.04000 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 8737.52000 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80067 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80067 |
236 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 17475.04000 |
237 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28773.86511 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
240 | Coil:Heating:Fuel | PSZ-AC_7:7 HEATING COIL | Design Size Nominal Capacity [W] | 28773.86511 |
241 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.00190 |
242 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
243 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.00190 |
244 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1109.26409 |
245 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.00190 |
246 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.00190 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.00190 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.00190 |
249 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.00190 |
250 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.50095 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.66793 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 17399.68000 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 8699.84000 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80044 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80044 |
256 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 17399.68000 |
257 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28653.59979 |
258 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
259 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
260 | Coil:Heating:Fuel | PSZ-AC_8:8 HEATING COIL | Design Size Nominal Capacity [W] | 28653.59979 |
261 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.99577 |
262 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
263 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.99577 |
264 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1102.47554 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.99577 |
266 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.99577 |
267 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.99577 |
268 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.99577 |
269 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.99577 |
270 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.49789 |
271 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.66385 |
272 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 17300.61000 |
273 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 8650.30500 |
274 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80029 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80029 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 17300.61000 |
277 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28487.88358 |
278 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
279 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
280 | Coil:Heating:Fuel | PSZ-AC_9:9 HEATING COIL | Design Size Nominal Capacity [W] | 28487.88358 |
281 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.07200 |
282 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
283 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.07200 |
284 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1186.87938 |
285 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.07200 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.07200 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.07200 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.07200 |
289 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.07200 |
290 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.53600 |
291 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.71467 |
292 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 18314.20000 |
293 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 9157.10000 |
294 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80024 |
295 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80024 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18314.20000 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30022.52795 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
299 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
300 | Coil:Heating:Fuel | PSZ-AC_10:10 HEATING COIL | Design Size Nominal Capacity [W] | 30022.52795 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 33042.6 | 11.22 | 11.22 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 17358.2 | 11.95 | 11.95 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | 17331.1 | 11.95 | 11.95 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | 17379.3 | 11.95 | 11.95 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | 17319.0 | 11.95 | 11.95 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | 32280.2 | 11.23 | 11.23 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | 16685.4 | 11.96 | 11.96 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | 16614.0 | 11.96 | 11.96 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | 16519.7 | 11.96 | 11.96 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | 17473.7 | 11.92 | 11.92 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 58.18 | 78.94 | 58.18 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.146 | 0.141 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.09 | 39.47 | 29.09 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 58.22 | 78.94 | 58.22 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.211 | 0.201 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 3.1119753715E-002 | 0.1465308739 | Pass | Pass | 0.2247522812 | 1.3768452982 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 4.2588774073E-002 | 7.6984557884E-002 | Pass | Pass | 8.1078452657E-002 | 0.2124708931 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 3.3894030729E-002 | 0.1210920748 | Pass | Pass | 0.1503009587 | 0.5168805734 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 3.7936769021E-002 | 0.1499852958 | Pass | Pass | 8.9422622816E-002 | 0.3679152736 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 4.2328874900E-002 | 0.1764839144 | Pass | Pass | 7.4697641937E-002 | 0.3374059000 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 5.5334864275E-002 | 0.2390510700 | Pass | Pass | 7.8847375170E-002 | 0.3067067420 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 5.3269732232E-002 | 0.2221400850 | Pass | Pass | 0.1290181613 | 1.0021340301 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 5.5532309011E-002 | 0.2308341442 | Pass | Pass | 0.3103314187 | 3.1594911733 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 6.3698534732E-002 | 0.2629241559 | Pass | Pass | 7.4821884735E-002 | 0.3217979355 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 7.7208926530E-002 | 0.3164776336 | Pass | Pass | 5.1102901048E-002 | 0.2018229948 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3437.36 | 208.69 | 0.00 | 587.42 | 231.06 | 4464.54 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00 | -4.20 | Wetbulb [C] | 4.30 | 20.00 |
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 10.40 | 18.30 | Wetbulb [C] | 4.20 | 350.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 22.00 | 23 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 16.00 | 20 | |||
Jul | 0.00 | 0 | |||
Aug | 24.00 | 18 | |||
Sep | 12.00 | 15 | |||
Oct | 61.00 | 41 | |||
Nov | 0.00 | 0 | |||
Dec | 45.00 | 41 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 78.94 | 58.18 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.143 | 0.146 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.09 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.082 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.082 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.082 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.082 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 78.94 | 58.22 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.082 | 0.083 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.082 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.082 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.082 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.204 | 0.211 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.168 | 0.401 | 0.402 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.168 | 0.401 | 0.402 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.168 | 0.401 | 0.402 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.168 | 0.401 | 0.402 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.168 | 0.401 | 0.402 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.168 | 0.401 | 0.402 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.168 | 0.401 | 0.402 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.168 | 0.401 | 0.402 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.168 | 0.401 | 0.402 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.168 | 0.401 | 0.402 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.168 | 0.401 | 0.402 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.168 | 0.401 | 0.402 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 124.40 | 2.168 | 0.401 | 0.402 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 124.40 | 2.168 | 0.401 | 0.402 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 13.1942 | 348.39 | 4596.69 | LightsWired | LTG_SCH_BASE_LPD1 | 84.21 | 168.00 | 84.19 | 0.0000 | Y | 72.65 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 4.6828 | 348.39 | 1631.41 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 168.00 | 97.48 | 0.0000 | Y | 29.85 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 13.3632 | 174.19 | 2327.78 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 85.70 | 168.00 | 85.69 | 0.0000 | Y | 37.44 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 5.9749 | 174.19 | 1040.80 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 168.00 | 97.48 | 0.0000 | Y | 19.04 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 13.3365 | 174.19 | 2323.12 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 29.75 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 4.0374 | 174.19 | 703.30 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 10.29 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 13.3365 | 174.19 | 2323.12 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 29.75 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 4.0374 | 174.19 | 703.30 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 10.29 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 13.3365 | 174.19 | 2323.12 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 29.75 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 4.0374 | 174.19 | 703.30 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 10.29 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 13.1675 | 348.39 | 4587.38 | LightsWired | LTG_SCH_BASE_LPD2 | 62.11 | 168.00 | 61.60 | 0.0000 | Y | 53.05 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 13.3365 | 174.19 | 2323.12 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 27.34 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 13.3365 | 174.19 | 2323.12 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 27.34 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 13.3365 | 174.19 | 2323.12 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 27.34 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 13.3365 | 174.19 | 2323.12 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 27.34 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 7.7873 | 4180.64 | 32555.80 | 441.52 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 345.19 | AstronomicalClock | - | 42.59 | 42.59 | 2.76 | |
EXTERIOR_LIGHTS_B | 7274.32 | AstronomicalClock | - | 83.55 | 71.26 | 97.30 | |
Exterior Lighting Total | 7619.51 | 100.06 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 34604.53 | 27693.31 | 6911.22 | 0.80 | 3.80 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 18184.09 | 14556.55 | 3627.54 | 0.80 | 4.12 | |||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 18155.51 | 14532.40 | 3623.11 | 0.80 | 4.12 | |||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 18206.34 | 14575.09 | 3631.25 | 0.80 | 4.12 | |||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 18142.80 | 14521.50 | 3621.30 | 0.80 | 4.12 | |||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 33800.80 | 27044.36 | 6756.44 | 0.80 | 3.80 | |||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 17475.04 | 13991.74 | 3483.30 | 0.80 | 4.12 | |||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 17399.68 | 13927.40 | 3472.28 | 0.80 | 4.12 | |||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 17300.61 | 13845.51 | 3455.10 | 0.80 | 4.12 | |||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 18314.20 | 14655.76 | 3658.44 | 0.80 | 4.12 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 33042.6 | 11.22 | 11.22 | ||||
PSZ-AC_2:2 COOLING COIL | 17358.2 | 11.95 | 11.95 | ||||
PSZ-AC_3:3 COOLING COIL | 17331.1 | 11.95 | 11.95 | ||||
PSZ-AC_4:4 COOLING COIL | 17379.3 | 11.95 | 11.95 | ||||
PSZ-AC_5:5 COOLING COIL | 17319.0 | 11.95 | 11.95 | ||||
PSZ-AC_6:6 COOLING COIL | 32280.2 | 11.23 | 11.23 | ||||
PSZ-AC_7:7 COOLING COIL | 16685.4 | 11.96 | 11.96 | ||||
PSZ-AC_8:8 COOLING COIL | 16614.0 | 11.96 | 11.96 | ||||
PSZ-AC_9:9 COOLING COIL | 16519.7 | 11.96 | 11.96 | ||||
PSZ-AC_10:10 COOLING COIL | 17473.7 | 11.92 | 11.92 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 57301.67 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 29944.47 | 0.80 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | 29902.47 | 0.80 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | 29976.81 | 0.80 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | 29883.64 | 0.80 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | 56112.28 | 0.80 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | 28773.87 | 0.80 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | 28653.60 | 0.80 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | 28487.88 | 0.80 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | 30022.53 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.99 | 2131.15 | 1070.05 | 1.00 | 1.32 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.05 | 1166.10 | 1107.16 | 1.00 | 1.39 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.05 | 1164.04 | 1107.16 | 1.00 | 1.39 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.05 | 1167.69 | 1107.16 | 1.00 | 1.39 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.05 | 1163.11 | 1107.16 | 1.00 | 1.39 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.94 | 2074.70 | 1070.05 | 1.00 | 1.32 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.01 | 1114.79 | 1107.16 | 1.00 | 1.40 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.00 | 1109.26 | 1107.16 | 1.00 | 1.40 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.00 | 1102.48 | 1107.16 | 1.00 | 1.40 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.07 | 1186.88 | 1107.16 | 1.00 | 1.39 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 22294.65 | 26753.58 | 76.79 | 1.660 | 1.992 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 23.89 | 23.89 | 0.00903 | 29.40 | 0.00882 | 0.411 | 0.00 |
SMSTORE1 | 11790.14 | 14148.16 | 81.22 | 0.878 | 1.053 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 23.89 | 23.89 | 0.00900 | 29.40 | 0.00882 | 0.206 | 0.00 |
SMSTORE2 | 11769.27 | 14123.13 | 81.08 | 0.876 | 1.051 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.89 | 0.00900 | 29.31 | 0.00882 | 0.206 | 0.00 |
SMSTORE3 | 11806.20 | 14167.45 | 81.33 | 0.879 | 1.055 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.89 | 0.00900 | 29.31 | 0.00882 | 0.206 | 0.00 |
SMSTORE4 | 11759.92 | 14111.91 | 81.01 | 0.875 | 1.051 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.89 | 0.00900 | 29.31 | 0.00882 | 0.206 | 0.00 |
LGSTORE2 | 21704.17 | 26045.00 | 74.76 | 1.616 | 1.939 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.89 | 0.00904 | 29.31 | 0.00882 | 0.411 | 0.00 |
SMSTORE5 | 11539.99 | 13847.99 | 79.50 | 0.834 | 1.001 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00928 | 25.45 | 0.00882 | 0.206 | 0.00 |
SMSTORE6 | 11479.95 | 13775.94 | 79.08 | 0.830 | 0.996 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00929 | 25.45 | 0.00882 | 0.206 | 0.00 |
SMSTORE7 | 11397.02 | 13676.42 | 78.51 | 0.824 | 0.989 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00932 | 25.45 | 0.00882 | 0.206 | 0.00 |
SMSTORE8 | 12160.44 | 14592.52 | 83.77 | 0.881 | 1.057 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00923 | 25.45 | 0.00882 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 19691.84 | 23630.20 | 67.83 | 0.861 | 1.033 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00672 | -4.20 | 0.00269 | 0.411 | 0.00 |
SMSTORE1 | 9073.32 | 10887.98 | 62.51 | 0.397 | 0.476 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00663 | -4.20 | 0.00269 | 0.206 | 0.00 |
SMSTORE2 | 9177.82 | 11013.39 | 63.23 | 0.401 | 0.482 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00664 | -4.20 | 0.00269 | 0.206 | 0.00 |
SMSTORE3 | 9276.82 | 11132.18 | 63.91 | 0.406 | 0.487 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00665 | -4.20 | 0.00269 | 0.206 | 0.00 |
SMSTORE4 | 9453.42 | 11344.10 | 65.12 | 0.413 | 0.496 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00667 | -4.20 | 0.00269 | 0.206 | 0.00 |
LGSTORE2 | 18363.00 | 22035.61 | 63.25 | 0.803 | 0.964 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00675 | -4.20 | 0.00269 | 0.411 | 0.00 |
SMSTORE5 | 9764.34 | 11717.20 | 67.27 | 0.427 | 0.512 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00669 | -4.20 | 0.00269 | 0.206 | 0.00 |
SMSTORE6 | 9765.67 | 11718.81 | 67.27 | 0.427 | 0.512 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00669 | -4.20 | 0.00269 | 0.206 | 0.00 |
SMSTORE7 | 10050.94 | 12061.13 | 69.24 | 0.440 | 0.527 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00672 | -4.20 | 0.00269 | 0.206 | 0.00 |
SMSTORE8 | 12473.87 | 14968.64 | 85.93 | 0.545 | 0.655 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00675 | -4.20 | 0.00269 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 1.99 | 1.99 | 1.03 | 1.03 | 1.9916 | 1.9916 | 1.9916 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.05 | 1.05 | 0.48 | 0.48 | 1.0532 | 1.0532 | 1.0532 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 1.05 | 1.05 | 0.48 | 0.48 | 1.0514 | 1.0514 | 1.0514 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 1.05 | 1.05 | 0.49 | 0.49 | 1.0547 | 1.0547 | 1.0547 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.05 | 1.05 | 0.50 | 0.50 | 1.0505 | 1.0505 | 1.0505 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 1.94 | 1.94 | 0.96 | 0.96 | 1.9389 | 1.9389 | 1.9389 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 1.01 | 1.01 | 0.51 | 0.51 | 1.0069 | 1.0013 | 1.0069 | 0.9944 | 1.0000 |
PSZ-AC_8:8 | 1.00 | 1.00 | 0.51 | 0.51 | 1.0019 | 0.9960 | 1.0019 | 0.9941 | 1.0000 |
PSZ-AC_9:9 | 1.00 | 1.00 | 0.53 | 0.53 | 0.9958 | 0.9886 | 0.9958 | 0.9928 | 1.0000 |
PSZ-AC_10:10 | 1.07 | 1.07 | 0.65 | 0.65 | 1.0720 | 1.0567 | 1.0720 | 0.9857 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 34604.530 | 27693.313 | 1.991640 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 17302.26 | 15972.50 | 1.327760 | 25.91 | 17.31 | 0.00898427 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 30.9905 | 23.89 | 0.00902665 | 48.1815 | 22294.65 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 57301.670 | 57301.670 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 57301.67 | 57301.67 | 1.991637 | 15.88 | 10.59 | 0.00588395 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 20.6603 | 21.11 | 0.00671558 | 42.6045 | 19691.84 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 18184.090 | 14556.546 | 1.053240 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 9092.05 | 8416.50 | 0.702160 | 25.88 | 17.28 | 0.00896588 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 29.3009 | 23.89 | 0.00900093 | 48.0460 | 11790.14 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 29944.473 | 29944.473 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 29944.47 | 29944.47 | 1.053236 | 16.16 | 10.69 | 0.00586120 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 19.5340 | 21.11 | 0.00663097 | 42.0729 | 9073.32 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 18155.510 | 14532.396 | 1.051370 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 9077.75 | 8402.59 | 0.700913 | 25.88 | 17.29 | 0.00896645 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 29.3530 | 23.89 | 0.00900172 | 48.0501 | 11768.99 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 29902.468 | 29902.468 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 29902.47 | 29902.47 | 1.051372 | 16.15 | 10.69 | 0.00586818 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 19.5687 | 21.11 | 0.00664134 | 42.1381 | 9177.82 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 18206.340 | 14575.085 | 1.054670 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 9103.17 | 8427.27 | 0.703113 | 25.88 | 17.28 | 0.00896549 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 29.2612 | 23.89 | 0.00900039 | 48.0431 | 11805.27 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 29976.813 | 29976.813 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 29976.81 | 29976.81 | 1.054671 | 16.17 | 10.71 | 0.00587786 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 19.5074 | 21.11 | 0.00665036 | 42.1947 | 9276.82 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 18142.800 | 14521.497 | 1.050540 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 9071.40 | 8396.39 | 0.700360 | 25.88 | 17.29 | 0.00896672 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 29.3762 | 23.89 | 0.00900209 | 48.0520 | 11758.92 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 29883.635 | 29883.635 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 29883.64 | 29883.64 | 1.050537 | 16.15 | 10.71 | 0.00588804 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 19.5842 | 21.11 | 0.00666681 | 42.2980 | 9453.42 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 33800.800 | 27044.358 | 1.938890 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 16900.40 | 15578.75 | 1.292593 | 25.94 | 17.33 | 0.00899454 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 31.8336 | 23.89 | 0.00904118 | 48.2579 | 21694.94 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 56112.275 | 56112.275 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 56112.28 | 56112.28 | 1.938890 | 15.74 | 10.53 | 0.00588620 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 21.2224 | 21.11 | 0.00674715 | 42.8016 | 18363.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 17475.040 | 13991.740 | 1.006900 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 8737.52 | 8071.48 | 0.671267 | 25.93 | 17.31 | 0.00898066 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 30.6494 | 23.89 | 0.00902163 | 48.1549 | 11248.34 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 28773.865 | 28773.865 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 28773.87 | 28773.87 | 1.006895 | 15.94 | 10.60 | 0.00587554 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 20.4330 | 21.11 | 0.00669351 | 42.4656 | 9764.34 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 17399.680 | 13927.400 | 1.001900 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 8699.84 | 8034.63 | 0.667933 | 25.94 | 17.32 | 0.00898248 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 30.8024 | 23.89 | 0.00902423 | 48.1685 | 11183.44 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 28653.600 | 28653.600 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 28653.60 | 28653.60 | 1.001902 | 15.91 | 10.59 | 0.00587161 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 20.5349 | 21.11 | 0.00669371 | 42.4668 | 9765.67 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 17300.610 | 13845.505 | 0.995770 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 8650.31 | 7987.54 | 0.663847 | 25.94 | 17.32 | 0.00898368 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 30.9920 | 23.89 | 0.00902594 | 48.1775 | 11140.99 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 28487.884 | 28487.884 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 28487.88 | 28487.88 | 0.995770 | 15.88 | 10.59 | 0.00588531 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 20.6613 | 21.11 | 0.00671735 | 42.6153 | 10050.94 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 18314.200 | 14655.755 | 1.072000 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 9157.10 | 8479.30 | 0.714667 | 25.76 | 17.24 | 0.00896040 | 12.80 | 11.97 | 0.00850000 | 28.88 | 0.00882066 | 18.17 | 28.7882 | 23.89 | 0.00899383 | 48.0085 | 11929.32 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 30022.528 | 30022.528 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 30022.53 | 30022.53 | 1.072005 | 16.25 | 10.84 | 0.00597145 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 19.1920 | 21.11 | 0.00675073 | 42.8269 | 12473.87 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 34604.530 | 27693.313 | 1.991640 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.5413 | 1004.8586 | 1.1870 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.991637 | 2.36405487 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | Sensible | 17302.26 | 15972.50 | 1.0000 | 1.57603888 | 1.327760 | 25.91 | 17.31 | 0.00898427 | 48936.5 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17302.26 | 29.40 | 0.00882150 | 18.34 | 0.41147883 | 30.9905 | 23.89 | 0.00902665 | 23.89 | 0.00902665 | 48.1815 | 22294.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 57301.670 | 57301.670 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.991637 | 2.36405487 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 57301.67 | 57301.67 | 1.0000 | 2.36405487 | 1.991637 | 15.88 | 10.59 | 0.00588395 | 30844.4 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 57301.67 | -4.20 | 0.00269032 | -4.20 | 0.41147883 | 20.6603 | 21.11 | 0.00671558 | 21.11 | 0.00671558 | 42.6045 | 19691.84 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 18184.090 | 14556.546 | 1.053240 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.5071 | 1004.8586 | 1.1870 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.053236 | 1.25018096 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | Sensible | 9092.05 | 8416.50 | 1.0000 | 0.83345745 | 0.702160 | 25.88 | 17.28 | 0.00896588 | 48857.5 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9092.05 | 29.40 | 0.00882150 | 18.34 | 0.20573941 | 29.3009 | 23.89 | 0.00900093 | 23.89 | 0.00900093 | 48.0460 | 11790.14 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29944.473 | 29944.473 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.053236 | 1.25018096 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 29944.47 | 29944.47 | 1.0000 | 1.25018096 | 1.053236 | 16.16 | 10.69 | 0.00586120 | 31076.6 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29944.47 | -4.20 | 0.00269032 | -4.20 | 0.20573941 | 19.5340 | 21.11 | 0.00663097 | 21.11 | 0.00663097 | 42.0729 | 9073.32 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 18155.510 | 14532.396 | 1.051370 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.5082 | 1004.8586 | 1.1870 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.051372 | 1.24796884 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 9077.75 | 8402.59 | 1.0000 | 0.83197767 | 0.700913 | 25.88 | 17.29 | 0.00896645 | 48861.0 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9077.75 | 29.40 | 0.00882150 | 18.34 | 0.20573941 | 29.3530 | 23.89 | 0.00900172 | 23.89 | 0.00900172 | 48.0501 | 11768.99 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29902.468 | 29902.468 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.051372 | 1.24796884 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 29902.47 | 29902.47 | 1.0000 | 1.24796884 | 1.051372 | 16.15 | 10.69 | 0.00586818 | 31085.3 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29902.47 | -4.20 | 0.00269032 | -4.20 | 0.20573941 | 19.5687 | 21.11 | 0.00664134 | 21.11 | 0.00664134 | 42.1381 | 9177.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 18206.340 | 14575.085 | 1.054670 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.5064 | 1004.8586 | 1.1870 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.054671 | 1.25188493 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 9103.17 | 8427.27 | 1.0000 | 0.83458905 | 0.703113 | 25.88 | 17.28 | 0.00896549 | 48855.1 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9103.17 | 29.40 | 0.00882150 | 18.34 | 0.20573941 | 29.2612 | 23.89 | 0.00900039 | 23.89 | 0.00900039 | 48.0431 | 11805.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29976.813 | 29976.813 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.054671 | 1.25188493 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 29976.81 | 29976.81 | 1.0000 | 1.25188493 | 1.054671 | 16.17 | 10.71 | 0.00587786 | 31125.6 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29976.81 | -4.20 | 0.00269032 | -4.20 | 0.20573941 | 19.5074 | 21.11 | 0.00665036 | 21.11 | 0.00665036 | 42.1947 | 9276.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 18142.800 | 14521.497 | 1.050540 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.5087 | 1004.8586 | 1.1870 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.050537 | 1.24697729 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 9071.40 | 8396.39 | 1.0000 | 0.83132087 | 0.700360 | 25.88 | 17.29 | 0.00896672 | 48862.6 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9071.40 | 29.40 | 0.00882150 | 18.34 | 0.20573941 | 29.3762 | 23.89 | 0.00900209 | 23.89 | 0.00900209 | 48.0520 | 11758.92 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29883.635 | 29883.635 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.050537 | 1.24697729 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 29883.64 | 29883.64 | 1.0000 | 1.24697729 | 1.050537 | 16.15 | 10.71 | 0.00588804 | 31131.6 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29883.64 | -4.20 | 0.00269032 | -4.20 | 0.20573941 | 19.5842 | 21.11 | 0.00666681 | 21.11 | 0.00666681 | 42.2980 | 9453.42 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 33800.800 | 27044.358 | 1.938890 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.5604 | 1004.8586 | 1.1870 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.938890 | 2.30144471 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 16900.40 | 15578.75 | 1.0000 | 1.53429637 | 1.292593 | 25.94 | 17.33 | 0.00899454 | 48994.8 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16900.40 | 29.40 | 0.00882150 | 18.34 | 0.41147883 | 31.8336 | 23.89 | 0.00904118 | 23.89 | 0.00904118 | 48.2579 | 21694.94 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 56112.275 | 56112.275 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.938890 | 2.30144471 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 56112.28 | 56112.28 | 1.0000 | 2.30144471 | 1.938890 | 15.74 | 10.53 | 0.00588620 | 30705.9 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 56112.28 | -4.20 | 0.00269032 | -4.20 | 0.41147883 | 21.2224 | 21.11 | 0.00674715 | 21.11 | 0.00674715 | 42.8016 | 18363.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 17475.040 | 13991.740 | 1.006900 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.5346 | 1004.8586 | 1.1870 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.006895 | 1.19517566 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | Sensible | 8737.52 | 8071.48 | 1.0000 | 0.79678735 | 0.671267 | 25.93 | 17.31 | 0.00898066 | 48948.2 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8737.52 | 29.40 | 0.00882150 | 18.34 | 0.20573941 | 30.6494 | 23.89 | 0.00902163 | 23.89 | 0.00902163 | 48.1549 | 11248.34 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28773.865 | 28773.865 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.006895 | 1.19517566 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 28773.87 | 28773.87 | 1.0000 | 1.19517566 | 1.006895 | 15.94 | 10.60 | 0.00587554 | 30881.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28773.87 | -4.20 | 0.00269032 | -4.20 | 0.20573941 | 20.4330 | 21.11 | 0.00669351 | 21.11 | 0.00669351 | 42.4656 | 9764.34 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 17399.680 | 13927.400 | 1.001900 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.5380 | 1004.8586 | 1.1870 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.001902 | 1.18924794 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | Sensible | 8699.84 | 8034.63 | 1.0000 | 0.79283071 | 0.667933 | 25.94 | 17.32 | 0.00898248 | 48959.5 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8699.84 | 29.40 | 0.00882150 | 18.34 | 0.20573941 | 30.8024 | 23.89 | 0.00902423 | 23.89 | 0.00902423 | 48.1685 | 11183.44 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28653.600 | 28653.600 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.001902 | 1.18924794 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 28653.60 | 28653.60 | 1.0000 | 1.18924794 | 1.001902 | 15.91 | 10.59 | 0.00587161 | 30845.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28653.60 | -4.20 | 0.00269032 | -4.20 | 0.20573941 | 20.5349 | 21.11 | 0.00669371 | 21.11 | 0.00669371 | 42.4668 | 9765.67 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 17300.610 | 13845.505 | 0.995770 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.5402 | 1004.8586 | 1.1870 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.995770 | 1.18196990 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | Sensible | 8650.31 | 7987.54 | 1.0000 | 0.78797987 | 0.663847 | 25.94 | 17.32 | 0.00898368 | 48967.0 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8650.31 | 29.40 | 0.00882150 | 18.34 | 0.20573941 | 30.9920 | 23.89 | 0.00902594 | 23.89 | 0.00902594 | 48.1775 | 11140.99 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28487.884 | 28487.884 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.995770 | 1.18196990 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 28487.88 | 28487.88 | 1.0000 | 1.18196990 | 0.995770 | 15.88 | 10.59 | 0.00588531 | 30847.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28487.88 | -4.20 | 0.00269032 | -4.20 | 0.20573941 | 20.6613 | 21.11 | 0.00671735 | 21.11 | 0.00671735 | 42.6153 | 10050.94 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 18314.200 | 14655.755 | 1.072000 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4969 | 1004.8586 | 1.1870 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.072005 | 1.27245971 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | Sensible | 9157.10 | 8479.30 | 1.0000 | 0.84830275 | 0.714667 | 25.76 | 17.24 | 0.00896040 | 48728.1 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9157.10 | 28.88 | 0.00882066 | 18.17 | 0.20573941 | 28.7882 | 23.89 | 0.00899383 | 23.89 | 0.00899383 | 48.0085 | 11929.32 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30022.528 | 30022.528 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.072005 | 1.27245971 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 30022.53 | 30022.53 | 1.0000 | 1.27245971 | 1.072005 | 16.25 | 10.84 | 0.00597145 | 31442.9 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30022.53 | -4.20 | 0.00269032 | -4.20 | 0.20573941 | 19.1920 | 21.11 | 0.00675073 | 21.11 | 0.00675073 | 42.8269 | 12473.87 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 1.99 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.05 | - | |||
PSZ-AC_3:3_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.05 | - | |||
PSZ-AC_4:4_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.05 | - | |||
PSZ-AC_5:5_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.05 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 1.94 | - | |||
PSZ-AC_7:7_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.01 | - | |||
PSZ-AC_8:8_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.00 | - | |||
PSZ-AC_9:9_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.00 | - | |||
PSZ-AC_10:10_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.07 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 1642.67 | 3836.67 | 481.17 |
SMSTORE1 | 1336.67 | 3285.00 | 71.33 |
SMSTORE2 | 1195.50 | 2584.83 | 155.50 |
SMSTORE3 | 1220.00 | 2623.33 | 198.17 |
SMSTORE4 | 1223.00 | 2703.33 | 258.67 |
LGSTORE2 | 1178.83 | 2664.17 | 379.50 |
SMSTORE5 | 1132.33 | 2564.67 | 374.00 |
SMSTORE6 | 1141.83 | 2585.33 | 402.33 |
SMSTORE7 | 1189.50 | 2683.50 | 504.33 |
SMSTORE8 | 1623.17 | 2868.00 | 1026.17 |
Facility | 2694.83 | 4181.67 | 1285.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 2.33 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 0.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 0.50 | 0.00 | 0.00 | 0.00 |
Facility | 2.83 | 0.00 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 1.006 | 0.230 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 1.126 | 0.245 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 1.264 | 0.320 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 1.259 | 0.320 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 1.239 | 0.320 | 0.000 | 0.000 |
LGSTORE2 | 24.77 | 56.25 | 1805.20 | 1.030 | 0.307 | 0.000 | 0.000 |
SMSTORE5 | 12.39 | 28.12 | 902.60 | 1.236 | 0.341 | 0.000 | 0.000 |
SMSTORE6 | 12.39 | 28.12 | 902.60 | 1.229 | 0.341 | 0.000 | 0.000 |
SMSTORE7 | 12.39 | 28.12 | 902.60 | 1.203 | 0.341 | 0.000 | 0.000 |
SMSTORE8 | 12.39 | 28.12 | 902.60 | 1.197 | 0.359 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 0.805 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 0.804 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 0.804 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.77 | 56.25 | 1805.20 | 0.802 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.39 | 28.12 | 902.60 | 0.803 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.39 | 28.12 | 902.60 | 0.803 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.39 | 28.12 | 902.60 | 0.802 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.39 | 28.12 | 902.60 | 0.802 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 16.93 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE1 | PSZ-AC_2:2 | 8.46 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE2 | PSZ-AC_3:3 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE3 | PSZ-AC_4:4 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE4 | PSZ-AC_5:5 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
LGSTORE2 | PSZ-AC_6:6 | 24.77 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE5 | PSZ-AC_7:7 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE6 | PSZ-AC_8:8 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE7 | PSZ-AC_9:9 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE8 | PSZ-AC_10:10 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
Total Facility | 120.95 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 2.469 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 10422969.23 | 0.00 | 10422969.23 | 2751627.34 | 13174596.57 | 12976396.34 | 3181.06 | 4041.65 | 1537.29 | 0.00 |
SMSTORE1 | 5817736.66 | 0.00 | 5817736.66 | 1379735.90 | 7197472.56 | 6488198.17 | 4120.52 | 2610.45 | 2029.03 | 0.00 |
SMSTORE2 | 4922317.92 | 0.00 | 4922317.92 | 1417116.89 | 6339434.82 | 6488198.17 | 4365.00 | 3038.06 | 1356.94 | 0.00 |
SMSTORE3 | 4904559.00 | 0.00 | 4904559.00 | 1417116.89 | 6321675.89 | 6488198.17 | 4365.00 | 3062.07 | 1332.93 | 0.00 |
SMSTORE4 | 4824180.25 | 0.00 | 4824180.25 | 1417116.89 | 6241297.14 | 6488198.17 | 4365.00 | 3138.90 | 1256.10 | 0.00 |
LGSTORE2 | 7366965.75 | 0.00 | 7366965.75 | 2601776.73 | 9968742.47 | 12976396.34 | 4730.00 | 3034.74 | 995.26 | 0.00 |
SMSTORE5 | 4415241.54 | 0.00 | 4415241.54 | 1426859.02 | 5842100.56 | 6488198.17 | 4730.00 | 2854.75 | 1175.25 | 0.00 |
SMSTORE6 | 4387325.53 | 0.00 | 4387325.53 | 1426859.02 | 5814184.56 | 6488198.17 | 4730.00 | 2873.49 | 1156.51 | 0.00 |
SMSTORE7 | 4295135.37 | 0.00 | 4295135.37 | 1426859.02 | 5721994.40 | 6488198.17 | 4730.00 | 2948.21 | 1081.79 | 0.00 |
SMSTORE8 | 4277628.52 | 0.00 | 4277628.52 | 1741640.55 | 6019269.07 | 6488198.17 | 4730.00 | 3056.78 | 973.22 | 0.00 |
Total Facility | 55634059.78 | 0.00 | 55634059.78 | 17006708.25 | 72640768.04 | 77858378.04 | 4730.00 | 4500.59 | 2200.64 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.4958 | 0.0000 | 0.4958 | 0.1134 | 0.6092 | 0.4115 | 261.06 | 4041.65 | 1537.29 |
SMSTORE1 | 0.2767 | 0.0000 | 0.2767 | 0.0605 | 0.3372 | 0.2057 | 1200.52 | 2610.45 | 2029.03 |
SMSTORE2 | 0.3111 | 0.0000 | 0.3111 | 0.0789 | 0.3900 | 0.2057 | 0.00 | 3038.06 | 1356.94 |
SMSTORE3 | 0.3100 | 0.0000 | 0.3100 | 0.0789 | 0.3889 | 0.2057 | 0.00 | 3062.07 | 1332.93 |
SMSTORE4 | 0.3049 | 0.0000 | 0.3049 | 0.0789 | 0.3838 | 0.2057 | 0.00 | 3138.90 | 1256.10 |
LGSTORE2 | 0.5078 | 0.0000 | 0.5078 | 0.1515 | 0.6593 | 0.4115 | 0.00 | 3034.74 | 995.26 |
SMSTORE5 | 0.3043 | 0.0000 | 0.3043 | 0.0842 | 0.3885 | 0.2057 | 0.00 | 2854.75 | 1175.25 |
SMSTORE6 | 0.3024 | 0.0000 | 0.3024 | 0.0842 | 0.3866 | 0.2057 | 0.00 | 2873.49 | 1156.51 |
SMSTORE7 | 0.2961 | 0.0000 | 0.2961 | 0.0842 | 0.3802 | 0.2057 | 0.00 | 2948.21 | 1081.79 |
SMSTORE8 | 0.2948 | 0.0000 | 0.2948 | 0.0886 | 0.3835 | 0.2057 | 0.00 | 3056.78 | 973.22 |
Total Facility | 3.4039 | 0.0000 | 3.4039 | 0.9032 | 4.3071 | 2.4689 | 1306.52 | 4500.59 | 2200.64 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 14685794.70 | 0.00 | 14685794.70 | 12976396.34 | 3180.22 | 0.33 | 5579.44 | 0.00 |
PSZ-AC_2:2 | 8196883.18 | 0.00 | 8196883.18 | 6488198.17 | 4103.71 | 2.38 | 4653.91 | 0.00 |
PSZ-AC_3:3 | 6935285.66 | 0.00 | 6935285.66 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 0.00 |
PSZ-AC_4:4 | 6910264.28 | 0.00 | 6910264.28 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 0.00 |
PSZ-AC_5:5 | 6797014.87 | 0.00 | 6797014.87 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 0.00 |
PSZ-AC_6:6 | 10379933.84 | 0.00 | 10379933.84 | 12976396.34 | 4730.00 | 0.00 | 4030.00 | 0.00 |
PSZ-AC_7:7 | 6220841.85 | 0.00 | 6220841.85 | 6488198.17 | 4730.00 | 0.00 | 4030.00 | 0.00 |
PSZ-AC_8:8 | 6181509.68 | 0.00 | 6181509.68 | 6488198.17 | 4730.00 | 0.00 | 4030.00 | 0.00 |
PSZ-AC_9:9 | 6051618.61 | 0.00 | 6051618.61 | 6488198.17 | 4730.00 | 0.00 | 4030.00 | 0.00 |
PSZ-AC_10:10 | 6026952.38 | 0.00 | 6026952.38 | 6488198.17 | 4730.00 | 0.00 | 4030.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.6985 | 0.0000 | 0.6985 | 0.4115 | 260.22 | 0.33 | 5579.44 |
PSZ-AC_2:2 | 0.3899 | 0.0000 | 0.3899 | 0.2057 | 1183.71 | 2.38 | 4653.91 |
PSZ-AC_3:3 | 0.4383 | 0.0000 | 0.4383 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_4:4 | 0.4368 | 0.0000 | 0.4368 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_5:5 | 0.4296 | 0.0000 | 0.4296 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_6:6 | 0.7155 | 0.0000 | 0.7155 | 0.4115 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_7:7 | 0.4288 | 0.0000 | 0.4288 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_8:8 | 0.4261 | 0.0000 | 0.4261 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_9:9 | 0.4171 | 0.0000 | 0.4171 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_10:10 | 0.4154 | 0.0000 | 0.4154 | 0.2057 | 0.00 | 0.00 | 4030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 4902.93 | 690.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 3363.94 | 1628.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 3589.06 | 805.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 3606.61 | 788.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 3665.95 | 729.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 3664.74 | 365.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 3380.55 | 649.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 3394.14 | 635.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 3443.10 | 586.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 3501.10 | 528.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.7066 | 0.8925 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.4349 | 0.5001 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 0.4051 | 0.5872 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 0.4038 | 0.5880 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 0.3978 | 0.5901 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 0.6980 | 0.8930 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.3997 | 0.5810 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.3972 | 0.5808 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.3894 | 0.5806 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.3873 | 0.6028 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 759 |
Defaulted Fields | 823 |
Fields with Defaults | 2681 |
Autosized Fields | 184 |
Autosizable Fields | 458 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 953.51 | 3115.94 | 15-JAN-08:00 | 82287.86 | 29-AUG-15:50 |
Electricity:Building | 570.24 | 1897.94 | 01-JAN-00:10 | 35612.10 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 128.86 | 354.96 | 01-JAN-00:10 | 6669.68 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 570.24 | 1897.94 | 01-JAN-00:10 | 35612.10 | 01-JAN-11:10 |
InteriorLights:Electricity | 441.52 | 1448.52 | 01-JAN-00:10 | 27522.57 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 102.50 | 280.06 | 01-JAN-00:10 | 5321.43 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 441.52 | 1448.52 | 01-JAN-00:10 | 27522.57 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 441.52 | 1448.52 | 01-JAN-00:10 | 27522.57 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 102.50 | 280.06 | 01-JAN-00:10 | 5321.43 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 441.52 | 1448.52 | 01-JAN-00:10 | 27522.57 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 69.66 | 191.80 | 01-JAN-00:10 | 3606.70 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 56.49 | 154.35 | 01-JAN-00:10 | 2932.57 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 56.49 | 154.35 | 01-JAN-00:10 | 2932.57 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 50.51 | 174.25 | 01-JAN-00:10 | 3273.35 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 40.04 | 136.80 | 01-JAN-00:10 | 2599.23 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 40.04 | 136.80 | 01-JAN-00:10 | 2599.23 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 50.51 | 174.25 | 01-JAN-00:10 | 3273.35 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 40.04 | 136.80 | 01-JAN-00:10 | 2599.23 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 40.04 | 136.80 | 01-JAN-00:10 | 2599.23 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 50.51 | 174.25 | 01-JAN-00:10 | 3273.35 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 40.04 | 136.80 | 01-JAN-00:10 | 2599.23 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 40.04 | 136.80 | 01-JAN-00:10 | 2599.23 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 72.31 | 272.07 | 01-JAN-00:10 | 5094.77 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 53.05 | 197.17 | 01-JAN-00:10 | 3746.51 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 53.05 | 197.17 | 01-JAN-00:10 | 3746.51 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 36.97 | 139.09 | 01-JAN-00:10 | 2605.22 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 36.97 | 139.09 | 01-JAN-00:10 | 2605.22 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 36.97 | 139.09 | 01-JAN-00:10 | 2605.22 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 36.97 | 139.09 | 01-JAN-00:10 | 2605.22 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 27.34 | 101.64 | 01-JAN-00:10 | 1931.10 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.36 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.36 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.18 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.18 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.26 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.26 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
ElectricityPurchased:Facility | 953.51 | 3115.94 | 15-JAN-08:00 | 82287.86 | 29-AUG-15:50 |
ElectricityPurchased:Plant | 953.51 | 3115.94 | 15-JAN-08:00 | 82287.86 | 29-AUG-15:50 |
Cogeneration:ElectricityPurchased | 953.51 | 3115.94 | 15-JAN-08:00 | 82287.86 | 29-AUG-15:50 |
General:Cogeneration:ElectricityPurchased | 953.51 | 3115.94 | 15-JAN-08:00 | 82287.86 | 29-AUG-15:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 953.51 | 3115.94 | 15-JAN-08:00 | 82287.86 | 29-AUG-15:50 |
ElectricityNet:Plant | 953.51 | 3115.94 | 15-JAN-08:00 | 82287.86 | 29-AUG-15:50 |
Cogeneration:ElectricityNet | 953.51 | 3115.94 | 15-JAN-08:00 | 82287.86 | 29-AUG-15:50 |
General:Cogeneration:ElectricityNet | 953.51 | 3115.94 | 15-JAN-08:00 | 82287.86 | 29-AUG-15:50 |
Electricity:HVAC | 218.81 | 0.00 | 01-JAN-00:10 | 40161.88 | 29-AUG-15:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 33.10 | 0.00 | 01-JAN-00:10 | 28884.73 | 29-AUG-15:00 |
General:Cooling:Electricity | 33.10 | 0.00 | 01-JAN-00:10 | 28884.73 | 29-AUG-15:00 |
Fans:Electricity | 185.70 | 0.00 | 01-JAN-00:10 | 11999.60 | 07-JAN-09:10 |
General:Fans:Electricity | 185.70 | 0.00 | 01-JAN-00:10 | 11999.60 | 07-JAN-09:10 |
ExteriorLights:Electricity | 100.06 | 0.00 | 01-JAN-08:10 | 7619.51 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 100.06 | 0.00 | 01-JAN-08:10 | 7619.51 | 01-JAN-06:10 |
Electricity:Plant | 64.39 | 1218.00 | 01-JAN-09:10 | 13622.60 | 17-JAN-14:30 |
WaterSystems:Electricity | 64.39 | 1218.00 | 01-JAN-09:10 | 13622.60 | 17-JAN-14:30 |
Water Heater:WaterSystems:Electricity | 64.39 | 1218.00 | 01-JAN-09:10 | 13622.60 | 17-JAN-14:30 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 259.60 | 0.00 | 01-JAN-00:10 | 169226.58 | 26-DEC-09:10 |
NaturalGas:HVAC | 259.60 | 0.00 | 01-JAN-00:10 | 169226.58 | 26-DEC-09:10 |
Heating:NaturalGas | 259.60 | 0.00 | 01-JAN-00:10 | 169226.58 | 26-DEC-09:10 |
General:Heating:NaturalGas | 259.60 | 0.00 | 01-JAN-00:10 | 169226.58 | 26-DEC-09:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 744.95 | 0.00 | 01-JAN-00:10 | 221264.05 | 26-DEC-09:10 |
EnergyTransfer:Building | 391.23 | 0.00 | 01-JAN-00:10 | 86083.46 | 10-AUG-16:10 |
EnergyTransfer:Zone:LGSTORE1 | 84.45 | 0.00 | 01-JAN-00:10 | 18122.79 | 15-JAN-09:10 |
Heating:EnergyTransfer | 60.28 | 0.00 | 01-JAN-00:10 | 82982.13 | 26-DEC-09:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 7.44 | 0.00 | 01-JAN-00:10 | 16918.79 | 15-JAN-09:10 |
General:Heating:EnergyTransfer | 60.28 | 0.00 | 01-JAN-00:10 | 82982.13 | 26-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 7.44 | 0.00 | 01-JAN-00:10 | 16918.79 | 15-JAN-09:10 |
Cooling:EnergyTransfer | 330.95 | 0.00 | 01-JAN-00:10 | 86083.46 | 10-AUG-16:10 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 77.01 | 0.00 | 01-JAN-00:10 | 14876.04 | 10-AUG-16:30 |
General:Cooling:EnergyTransfer | 330.95 | 0.00 | 01-JAN-00:10 | 86083.46 | 10-AUG-16:10 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 77.01 | 0.00 | 01-JAN-00:10 | 14876.04 | 10-AUG-16:30 |
EnergyTransfer:Zone:SMSTORE1 | 43.26 | 0.00 | 01-JAN-00:10 | 11633.95 | 08-AUG-22:00 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 2.46 | 0.00 | 01-JAN-00:10 | 4599.88 | 26-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 2.46 | 0.00 | 01-JAN-00:10 | 4599.88 | 26-DEC-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 40.80 | 0.00 | 01-JAN-00:10 | 11633.95 | 08-AUG-22:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 40.80 | 0.00 | 01-JAN-00:10 | 11633.95 | 08-AUG-22:00 |
EnergyTransfer:Zone:SMSTORE2 | 32.72 | 0.00 | 01-JAN-00:10 | 8066.24 | 16-JAN-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 3.63 | 0.00 | 01-JAN-00:10 | 7116.85 | 16-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 3.63 | 0.00 | 01-JAN-00:10 | 7116.85 | 16-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 29.08 | 0.00 | 01-JAN-00:10 | 7381.65 | 10-AUG-16:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 29.08 | 0.00 | 01-JAN-00:10 | 7381.65 | 10-AUG-16:10 |
EnergyTransfer:Zone:SMSTORE3 | 32.22 | 0.00 | 01-JAN-00:10 | 8636.13 | 19-FEB-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 4.12 | 0.00 | 01-JAN-00:10 | 7623.84 | 16-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 4.12 | 0.00 | 01-JAN-00:10 | 7623.84 | 16-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 28.10 | 0.00 | 01-JAN-00:10 | 7390.39 | 10-AUG-16:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 28.10 | 0.00 | 01-JAN-00:10 | 7390.39 | 10-AUG-16:10 |
EnergyTransfer:Zone:SMSTORE4 | 30.98 | 0.00 | 01-JAN-00:10 | 9456.05 | 26-DEC-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 4.83 | 0.00 | 01-JAN-00:10 | 8492.18 | 26-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 4.83 | 0.00 | 01-JAN-00:10 | 8492.18 | 26-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 26.14 | 0.00 | 01-JAN-00:10 | 7294.03 | 10-AUG-16:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 26.14 | 0.00 | 01-JAN-00:10 | 7294.03 | 10-AUG-16:10 |
EnergyTransfer:Zone:LGSTORE2 | 55.81 | 0.00 | 01-JAN-00:10 | 17154.04 | 22-DEC-09:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 7.64 | 0.00 | 01-JAN-00:10 | 16490.73 | 26-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 7.64 | 0.00 | 01-JAN-00:10 | 16490.73 | 26-DEC-09:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 48.17 | 0.00 | 01-JAN-00:10 | 13717.57 | 10-AUG-14:50 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 48.17 | 0.00 | 01-JAN-00:10 | 13717.57 | 10-AUG-14:50 |
EnergyTransfer:Zone:SMSTORE5 | 27.83 | 0.00 | 01-JAN-00:10 | 9039.32 | 20-FEB-10:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 5.11 | 0.00 | 01-JAN-00:10 | 8570.95 | 26-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 5.11 | 0.00 | 01-JAN-00:10 | 8570.95 | 26-DEC-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 22.72 | 0.00 | 01-JAN-00:10 | 7177.12 | 10-AUG-14:50 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 22.72 | 0.00 | 01-JAN-00:10 | 7177.12 | 10-AUG-14:50 |
EnergyTransfer:Zone:SMSTORE6 | 27.52 | 0.00 | 01-JAN-00:10 | 9748.80 | 26-DEC-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 5.34 | 0.00 | 01-JAN-00:10 | 9226.63 | 26-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 5.34 | 0.00 | 01-JAN-00:10 | 9226.63 | 26-DEC-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 22.18 | 0.00 | 01-JAN-00:10 | 7122.45 | 10-AUG-14:50 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 22.18 | 0.00 | 01-JAN-00:10 | 7122.45 | 10-AUG-14:50 |
EnergyTransfer:Zone:SMSTORE7 | 26.68 | 0.00 | 01-JAN-00:10 | 9454.25 | 26-DEC-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 6.58 | 0.00 | 01-JAN-00:10 | 9385.84 | 26-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 6.58 | 0.00 | 01-JAN-00:10 | 9385.84 | 26-DEC-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 20.10 | 0.00 | 01-JAN-00:10 | 7051.57 | 10-AUG-14:50 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 20.10 | 0.00 | 01-JAN-00:10 | 7051.57 | 10-AUG-14:50 |
EnergyTransfer:Zone:SMSTORE8 | 29.76 | 0.00 | 01-JAN-00:10 | 12441.96 | 16-JAN-10:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 13.12 | 0.00 | 01-JAN-00:10 | 12441.96 | 16-JAN-10:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 13.12 | 0.00 | 01-JAN-00:10 | 12441.96 | 16-JAN-10:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 16.63 | 0.00 | 01-JAN-00:10 | 7458.87 | 10-AUG-14:40 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 16.63 | 0.00 | 01-JAN-00:10 | 7458.87 | 10-AUG-14:40 |
EnergyTransfer:HVAC | 353.72 | 0.00 | 01-JAN-00:10 | 135381.26 | 26-DEC-09:10 |
HeatingCoils:EnergyTransfer | 207.68 | 0.00 | 01-JAN-00:10 | 135381.26 | 26-DEC-09:10 |
CoolingCoils:EnergyTransfer | 146.04 | 0.00 | 01-JAN-00:10 | 127405.33 | 29-AUG-14:50 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 7.438 | -77.014 | 0.000 | 0.000 | 25.353 | 102.498 | 26.357 | 21.159 | 0.000 | 0.453 | 0.000 | 0.000 | -9.314 | 0.000 | -31.511 | -65.420 |
SMSTORE1 | 0.000 | 0.000 | 2.456 | -40.804 | 0.000 | 0.000 | 12.338 | 56.486 | 13.179 | 10.439 | 0.000 | 0.246 | 0.000 | 0.000 | -4.977 | 0.000 | -16.029 | -33.333 |
SMSTORE2 | 0.000 | 0.000 | 3.631 | -29.085 | 0.000 | 0.000 | 7.529 | 40.039 | 10.467 | 10.429 | 0.000 | 0.240 | 0.002 | 0.000 | -4.907 | 0.000 | -16.421 | -21.922 |
SMSTORE3 | 0.000 | 0.000 | 4.124 | -28.098 | 0.000 | 0.000 | 7.544 | 40.039 | 10.467 | 10.445 | 0.000 | 0.240 | 0.000 | 0.000 | -4.846 | 0.000 | -16.332 | -23.583 |
SMSTORE4 | 0.000 | 0.000 | 4.833 | -26.144 | 0.000 | 0.000 | 7.568 | 40.039 | 10.467 | 10.471 | 0.000 | 0.240 | 0.002 | 0.000 | -4.780 | 0.000 | -16.211 | -26.484 |
LGSTORE2 | 0.000 | 0.000 | 7.644 | -48.166 | 0.000 | 0.000 | 26.204 | 53.048 | 19.261 | 21.099 | 0.000 | 0.433 | 0.005 | 0.000 | -9.248 | 0.000 | -29.321 | -40.956 |
SMSTORE5 | 0.000 | 0.000 | 5.112 | -22.721 | 0.000 | 0.000 | 13.010 | 27.343 | 9.631 | 10.509 | 0.000 | 0.241 | 0.000 | 0.000 | -4.657 | 0.000 | -16.211 | -22.257 |
SMSTORE6 | 0.000 | 0.000 | 5.343 | -22.181 | 0.000 | 0.000 | 13.019 | 27.343 | 9.631 | 10.518 | 0.000 | 0.241 | 0.001 | 0.000 | -4.635 | 0.000 | -16.180 | -23.097 |
SMSTORE7 | 0.000 | 0.000 | 6.576 | -20.104 | 0.000 | 0.000 | 13.064 | 27.343 | 9.631 | 10.558 | 0.000 | 0.241 | 0.002 | 0.000 | -4.539 | 0.000 | -16.022 | -26.747 |
SMSTORE8 | 0.000 | 0.000 | 13.124 | -16.632 | 0.000 | 0.000 | 13.145 | 27.343 | 9.631 | 10.663 | 0.000 | 0.251 | 0.001 | 0.000 | -4.196 | 0.000 | -19.567 | -33.760 |
Total Facility | 0.000 | 0.000 | 60.281 | -330.949 | 0.000 | 0.000 | 138.774 | 441.522 | 128.721 | 126.289 | 0.000 | 2.827 | 0.013 | 0.000 | -56.099 | 0.000 | -193.805 | -317.560 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 20-JUL-08:62 | 0.00 | 0.00 | 0.00 | -35896.10 | 0.00 | 0.00 | 183.66 | 2800.74 | 749.03 | 653.41 | 0.00 | 0.00 | 31812.19 | 0.00 | -0.00 | 0.00 | -302.92 | 0.00 |
SMSTORE1 | 06-JUL-08:62 | 0.00 | 0.00 | 0.00 | -21227.98 | 0.00 | 0.00 | 87.67 | 1543.46 | 374.52 | 375.25 | 0.00 | 0.00 | 19043.63 | 0.00 | -0.00 | 0.00 | -196.54 | 0.00 |
SMSTORE2 | 16-SEP-07:02 | 0.00 | 0.00 | 0.00 | -21287.06 | 0.00 | 0.00 | 87.18 | 1368.01 | 374.52 | 0.00 | 0.00 | 0.00 | 19939.16 | 0.00 | -160.42 | 0.00 | -321.39 | 0.00 |
SMSTORE3 | 01-AUG-07:02 | 0.00 | 0.00 | 0.00 | -21371.23 | 0.00 | 0.00 | 83.93 | 1368.01 | 374.52 | 15.28 | 0.00 | 0.00 | 19871.74 | 0.00 | -0.00 | 0.00 | -342.25 | 0.00 |
SMSTORE4 | 01-AUG-07:02 | 0.00 | 0.00 | 0.00 | -21180.98 | 0.00 | 0.00 | 84.72 | 1368.01 | 374.52 | 17.07 | 0.00 | 0.00 | 19676.33 | 0.00 | -0.00 | 0.00 | -339.67 | 0.00 |
LGSTORE2 | 15-AUG-08:62 | 0.00 | 0.00 | 0.00 | -35203.74 | 0.00 | 0.00 | 395.32 | 1971.84 | 749.03 | 331.48 | 0.00 | 0.00 | 32037.14 | 0.00 | -0.00 | 0.00 | -281.06 | 0.00 |
SMSTORE5 | 19-JUL-08:62 | 0.00 | 0.00 | 0.00 | -19690.73 | 0.00 | 0.00 | 197.20 | 1016.37 | 374.52 | 210.08 | 0.00 | 0.00 | 18085.34 | 0.00 | -0.00 | 0.00 | -192.77 | 0.00 |
SMSTORE6 | 19-JUL-08:62 | 0.00 | 0.00 | 0.00 | -19545.62 | 0.00 | 0.00 | 198.15 | 1016.37 | 374.52 | 211.16 | 0.00 | 0.00 | 17936.94 | 0.00 | -0.00 | 0.00 | -191.51 | 0.00 |
SMSTORE7 | 01-AUG-08:62 | 0.00 | 0.00 | 0.00 | -19242.14 | 0.00 | 0.00 | 197.02 | 1016.37 | 374.52 | 393.74 | 0.00 | 0.00 | 17569.91 | 0.00 | -0.00 | 0.00 | -309.42 | 0.00 |
SMSTORE8 | 23-JUL-09:02 | 0.00 | 0.00 | 0.00 | -18876.91 | 0.00 | 0.00 | 190.38 | 1016.37 | 374.52 | 712.71 | 0.00 | 0.00 | 16748.34 | 0.00 | -0.00 | 0.00 | -165.40 | 0.00 |
Total Facility | 20-JUL-08:62 | 0.00 | 0.00 | 0.00 | -170184.29 | 0.00 | 0.00 | 2053.46 | 18179.18 | 5393.02 | 3903.14 | 0.00 | 0.00 | 142544.08 | 0.00 | 0.00 | 0.00 | -1888.60 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 23-FEB-09:01 | 0.00 | 0.00 | 52494.95 | 0.00 | 0.00 | 0.00 | 246.23 | 2800.74 | 749.03 | 15.23 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -573.02 | -55733.16 |
SMSTORE1 | 17-JAN-09:01 | 0.00 | 0.00 | 25494.81 | 0.00 | 0.00 | 0.00 | 121.08 | 1543.46 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -121.25 | 0.00 | -479.81 | -26932.80 |
SMSTORE2 | 01-JAN-09:01 | 0.00 | 0.00 | 26705.43 | 0.00 | 0.00 | 0.00 | 122.96 | 1368.01 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -113.01 | 0.00 | -334.97 | -28122.95 |
SMSTORE3 | 01-JAN-09:01 | 0.00 | 0.00 | 26889.54 | 0.00 | 0.00 | 0.00 | 125.44 | 1368.01 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -103.76 | 0.00 | -323.01 | -28330.75 |
SMSTORE4 | 01-JAN-09:01 | 0.00 | 0.00 | 26883.15 | 0.00 | 0.00 | 0.00 | 127.21 | 1368.01 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -97.61 | 0.00 | -314.18 | -28341.09 |
LGSTORE2 | 16-JAN-09:01 | 0.00 | 0.00 | 56104.57 | 0.00 | 0.00 | 0.00 | 0.00 | 197.17 | 74.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -268.96 | 0.00 | -909.22 | -55198.46 |
SMSTORE5 | 16-JAN-09:01 | 0.00 | 0.00 | 28783.82 | 0.00 | 0.00 | 0.00 | 0.00 | 101.64 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -135.55 | 0.00 | -499.82 | -28287.53 |
SMSTORE6 | 16-JAN-09:01 | 0.00 | 0.00 | 28668.15 | 0.00 | 0.00 | 0.00 | 0.00 | 101.64 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -133.37 | 0.00 | -496.74 | -28177.12 |
SMSTORE7 | 17-JAN-08:61 | 0.00 | 0.00 | 28520.90 | 0.00 | 0.00 | 0.00 | 0.00 | 101.64 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -230.60 | 0.00 | -400.58 | -28028.80 |
SMSTORE8 | 17-JAN-08:61 | 0.00 | 0.00 | 30002.76 | 0.00 | 0.00 | 0.00 | 0.00 | 101.64 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -200.22 | 0.00 | -404.71 | -29536.91 |
Total Facility | 20-FEB-09:01 | 0.00 | 0.00 | 323591.96 | 0.00 | 0.00 | 0.00 | 760.07 | 9051.95 | 2471.80 | 1666.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5488.35 | -332054.33 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.9916 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.9916 | 0.2066 | 1.0000 | Not calculated | 0.4115 | 0.2066 | ||
PSZ-AC_2:2 | 1.0532 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0532 | 0.1953 | 1.0000 | Not calculated | 0.2057 | 0.1953 | ||
PSZ-AC_3:3 | 1.0514 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0514 | 0.1957 | 1.0000 | Not calculated | 0.2057 | 0.1957 | ||
PSZ-AC_4:4 | 1.0547 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0547 | 0.1951 | 1.0000 | Not calculated | 0.2057 | 0.1951 | ||
PSZ-AC_5:5 | 1.0505 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0505 | 0.1958 | 1.0000 | Not calculated | 0.2057 | 0.1958 | ||
PSZ-AC_6:6 | 1.9389 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.9389 | 0.2122 | 1.0000 | Not calculated | 0.4115 | 0.2122 | ||
PSZ-AC_7:7 | 1.0013 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0069 | 0.2043 | 1.0000 | Not calculated | 0.2057 | 0.2043 | ||
PSZ-AC_8:8 | 0.9960 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0019 | 0.2053 | 1.0000 | Not calculated | 0.2057 | 0.2053 | ||
PSZ-AC_9:9 | 0.9886 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9958 | 0.2066 | 1.0000 | Not calculated | 0.2057 | 0.2066 | ||
PSZ-AC_10:10 | 1.0567 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0720 | 0.1919 | 1.0000 | Not calculated | 0.2057 | 0.1919 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.9916 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.9916 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2066 | ||
PSZ-AC_2:2 | 1.0532 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0532 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1953 | ||
PSZ-AC_3:3 | 1.0514 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0514 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1957 | ||
PSZ-AC_4:4 | 1.0547 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0547 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1951 | ||
PSZ-AC_5:5 | 1.0505 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0505 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1958 | ||
PSZ-AC_6:6 | 1.9389 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.9389 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2122 | ||
PSZ-AC_7:7 | 1.0013 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0013 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2055 | ||
PSZ-AC_8:8 | 0.9960 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9960 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2066 | ||
PSZ-AC_9:9 | 0.9886 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9886 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2081 | ||
PSZ-AC_10:10 | 1.0567 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0567 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1947 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9916 | 1.9916 | 1.9916 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0532 | 1.0532 | 1.0532 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0514 | 1.0514 | 1.0514 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0547 | 1.0547 | 1.0547 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0505 | 1.0505 | 1.0505 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9389 | 1.9389 | 1.9389 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0013 | 1.0013 | 1.0013 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9960 | 0.9960 | 0.9960 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9886 | 0.9886 | 0.9886 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0567 | 1.0567 | 1.0567 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.9916 | 1.9916 | 1.9916 | 1.9916 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.0532 | 1.0532 | 1.0532 | 1.0532 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.0514 | 1.0514 | 1.0514 | 1.0514 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.0547 | 1.0547 | 1.0547 | 1.0547 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.0505 | 1.0505 | 1.0505 | 1.0505 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.9389 | 1.9389 | 1.9389 | 1.9389 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.0013 | 1.0069 | 1.0013 | 1.0013 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9960 | 1.0019 | 0.9960 | 0.9960 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.9886 | 0.9958 | 0.9886 | 0.9886 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.0567 | 1.0720 | 1.0567 | 1.0567 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9916 | 1.9916 | 1.9916 | No | 0.4115 | 0.3982 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0532 | 1.0532 | 1.0532 | No | 0.2057 | 0.4321 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0514 | 1.0514 | 1.0514 | No | 0.2057 | 0.4272 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0547 | 1.0547 | 1.0547 | No | 0.2057 | 0.4226 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0505 | 1.0505 | 1.0505 | No | 0.2057 | 0.4147 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9389 | 1.9389 | 1.9389 | No | 0.4115 | 0.4270 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0013 | 1.0013 | 1.0013 | No | 0.2057 | 0.4015 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9960 | 0.9960 | 0.9960 | No | 0.2057 | 0.4015 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9886 | 0.9886 | 0.9886 | No | 0.2057 | 0.3901 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0567 | 1.0567 | 1.0567 | No | 0.2057 | 0.3143 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.9916 | 1.9916 | 1.9916 | 1.9916 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.0532 | 1.0532 | 1.0532 | 1.0532 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.0514 | 1.0514 | 1.0514 | 1.0514 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.0547 | 1.0547 | 1.0547 | 1.0547 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.0505 | 1.0505 | 1.0505 | 1.0505 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.9389 | 1.9389 | 1.9389 | 1.9389 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.0013 | 1.0013 | 1.0013 | 1.0013 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9960 | 0.9960 | 0.9960 | 0.9960 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.9886 | 0.9886 | 0.9886 | 0.9886 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.0567 | 1.0567 | 1.0567 | 1.0567 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 259.60 | 169226.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 33.10 | 28884.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 441.52 | 27522.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 100.06 | 7619.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.72 | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 185.70 | 11999.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 64.39 | 13622.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.72 | 953.51 |
Natural Gas | 0.00 | 259.60 |
Additional | 0.00 | 0.00 |
Total | 128.72 | 1213.12 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 211.22 |
Space Heating | 0.00 |
Space Cooling | 15.84 |
Fans (All) | 88.84 |
Service Water Heating | 30.81 |
Receptacle Equipment | 61.58 |
Miscellaneous (All) | 456.16 |
Subtotal | 456.16 |
Natural Gas [MJ/m2] | |
Space Heating | 124.19 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 124.19 |
Subtotal | 124.19 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 36.40 |
Space Heating | 21.40 |
Space Cooling | 2.73 |
Fans (All) | 15.31 |
Service Water Heating | 5.31 |
Receptacle Equipment | 10.61 |
Miscellaneous | 8.25 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3238. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3296. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 4469. | 8760. |
LTG_SCH_BASE_LPD1 | 4391. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 3584. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4888. | 8760. |
TYPE2_EQUIP_SCH | 3911. | 8760. |
TYPE3_EQUIP_SCH | 3600. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8753.67 | 6.33 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8752.83 | 7.17 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8754.67 | 5.33 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8757.00 | 3.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8757.33 | 2.67 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8757.50 | 2.50 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8758.00 | 2.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8757.67 | 2.33 | 0.00 | 0.00 | 0.00 |
Min | 8752.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 7.17 | 0.00 | 0.00 | 0.00 |
Average | 8756.87 | 3.13 | 0.00 | 0.00 | 0.00 |
Sum | 87568.67 | 31.33 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25472.67 | 2.33 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25472.67 | 2.33 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25473.17 | 1.83 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93206.00 | 5.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45909.50 | 2.50 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45909.50 | 2.50 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45909.50 | 2.50 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45909.50 | 2.50 | 0.00 | 0.00 | 0.00 |
Min | 25472.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 93206.00 | 5.00 | 0.00 | 0.00 | 0.00 |
Average | 48608.05 | 2.15 | 0.00 | 0.00 | 0.00 |
Sum | 486080.50 | 21.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8726.33 | 33.67 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8724.17 | 35.83 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8730.67 | 29.33 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8744.33 | 15.67 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8742.50 | 17.50 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8743.17 | 16.83 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8745.67 | 14.33 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8749.33 | 10.67 | 0.00 | 0.00 | 0.00 |
Min | 8724.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 35.83 | 0.00 | 0.00 | 0.00 |
Average | 8742.62 | 17.38 | 0.00 | 0.00 | 0.00 |
Sum | 87426.17 | 173.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25468.67 | 6.33 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25468.67 | 6.33 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25468.83 | 6.17 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93201.00 | 10.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45903.50 | 8.50 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45904.00 | 8.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45904.00 | 8.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45904.00 | 8.00 | 0.00 | 0.00 | 0.00 |
Min | 25468.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 93201.00 | 10.00 | 0.00 | 0.00 | 0.00 |
Average | 48604.07 | 6.13 | 0.00 | 0.00 | 0.00 |
Sum | 486040.67 | 61.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:13
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Environment
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
For: Environment
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
For: Environment
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.138024E+10 | 10836.02 | 15-JAN-09:04 | -2.5 | -3.9 | 0.106359E+10 | 1275.40 | 08-JAN-18:00 | -2.5 | -3.9 |
February | 0.228021E+10 | 9571.47 | 17-FEB-09:04 | 1.02 | 0.16 | 0.972484E+09 | 1404.87 | 27-FEB-17:10 | 18.62 | 12.15 |
March | 0.444720E+10 | 8608.27 | 05-MAR-09:04 | 3.40 | 2.59 | 0.108688E+10 | 1539.85 | 18-MAR-12:00 | 17.20 | 10.94 |
April | 0.614460E+10 | 10289.01 | 27-APR-16:10 | 27.02 | 16.89 | 0.116089E+10 | 1685.91 | 29-APR-12:00 | 20.00 | 14.70 |
May | 0.799869E+10 | 10035.37 | 15-MAY-16:20 | 24.07 | 12.90 | 0.131187E+10 | 1685.96 | 07-MAY-12:00 | 24.07 | 12.90 |
June | 0.907212E+10 | 25401.06 | 28-JUN-08:62 | 17.98 | 13.05 | 0.133784E+10 | 1685.93 | 11-JUN-12:20 | 17.98 | 13.05 |
July | 0.118486E+11 | 35898.24 | 20-JUL-08:62 | 17.38 | 13.38 | 0.141110E+10 | 1685.98 | 15-JUL-12:00 | 17.38 | 13.38 |
August | 0.124090E+11 | 34566.18 | 09-AUG-08:62 | 21.72 | 14.33 | 0.139315E+10 | 1685.97 | 26-AUG-12:00 | 22.20 | 17.01 |
September | 0.929838E+10 | 30708.00 | 14-SEP-08:62 | 15.87 | 14.39 | 0.133549E+10 | 1685.98 | 23-SEP-12:30 | 21.10 | 16.82 |
October | 0.683576E+10 | 9156.89 | 04-OCT-16:10 | 21.02 | 11.40 | 0.122214E+10 | 1685.87 | 08-OCT-16:40 | 18.87 | 12.78 |
November | 0.334179E+10 | 9697.48 | 11-NOV-09:05 | 0.78 | 0.55 | 0.105902E+10 | 1685.88 | 04-NOV-12:00 | 0.78 | 0.55 |
December | 0.195765E+10 | 9997.06 | 25-DEC-09:04 | -0.1 | -0.7 | 0.106942E+10 | 1301.98 | 03-DEC-13:00 | -0.1 | -0.7 |
Annual Sum or Average | 0.770142E+11 | 0.144239E+11 | ||||||||
Minimum of Months | 0.138024E+10 | 8608.27 | -2.5 | -3.9 | 0.972484E+09 | 1275.40 | -2.5 | -3.9 | ||
Maximum of Months | 0.124090E+11 | 35898.24 | 27.02 | 16.89 | 0.141110E+10 | 1685.98 | 24.07 | 17.01 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.660811E+09 | 5150.26 | 07-JAN-09:03 | -3.1 | -3.3 | 0.553197E+09 | 779.64 | 29-JAN-18:00 | 9.40 | 5.55 |
February | 0.110957E+10 | 4497.07 | 18-FEB-09:03 | -0.3 | -1.0 | 0.517422E+09 | 842.90 | 26-FEB-18:00 | 10.00 | 7.75 |
March | 0.204588E+10 | 3136.91 | 01-MAR-09:02 | 4.37 | 0.91 | 0.602493E+09 | 842.90 | 19-MAR-17:00 | 10.00 | 6.56 |
April | 0.285881E+10 | 19586.71 | 02-APR-17:07 | 19.13 | 11.39 | 0.637044E+09 | 842.92 | 29-APR-12:00 | 20.00 | 14.70 |
May | 0.417196E+10 | 21044.53 | 14-MAY-19:33 | 17.40 | 10.65 | 0.690406E+09 | 842.94 | 07-MAY-12:00 | 17.40 | 10.65 |
June | 0.525249E+10 | 20108.65 | 24-JUN-18:50 | 17.98 | 11.71 | 0.675120E+09 | 842.93 | 11-JUN-12:09 | 17.98 | 11.71 |
July | 0.669991E+10 | 21229.45 | 06-JUL-08:62 | 16.10 | 11.33 | 0.703884E+09 | 842.95 | 15-JUL-12:00 | 20.60 | 16.71 |
August | 0.704626E+10 | 20819.59 | 01-AUG-08:62 | 11.85 | 11.55 | 0.694035E+09 | 842.95 | 26-AUG-12:20 | 22.20 | 17.39 |
September | 0.518866E+10 | 19829.21 | 11-SEP-08:62 | 15.28 | 12.74 | 0.679197E+09 | 842.95 | 23-SEP-12:30 | 21.10 | 16.82 |
October | 0.323263E+10 | 20061.84 | 04-OCT-20:01 | 16.65 | 10.41 | 0.667586E+09 | 842.90 | 08-OCT-16:40 | 18.87 | 12.78 |
November | 0.160026E+10 | 3588.40 | 04-NOV-14:00 | 21.10 | 15.94 | 0.568048E+09 | 842.92 | 04-NOV-12:00 | 21.10 | 15.94 |
December | 0.936896E+09 | 4631.69 | 26-DEC-09:03 | -0.9 | -0.9 | 0.561615E+09 | 832.05 | 03-DEC-18:00 | -0.9 | -0.9 |
Annual Sum or Average | 0.408041E+11 | 0.755005E+10 | ||||||||
Minimum of Months | 0.660811E+09 | 3136.91 | -3.1 | -3.3 | 0.517422E+09 | 779.64 | -0.9 | -0.9 | ||
Maximum of Months | 0.704626E+10 | 21229.45 | 21.10 | 15.94 | 0.703884E+09 | 842.95 | 22.20 | 17.39 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.366179E+09 | 5173.16 | 07-JAN-08:03 | -3.8 | -3.8 | 0.317515E+09 | 637.68 | 07-JAN-13:09 | 0.97 | 0.44 |
February | 0.754862E+09 | 5120.77 | 19-FEB-09:04 | -3.1 | -4.3 | 0.296141E+09 | 743.14 | 25-FEB-13:50 | 14.50 | 11.67 |
March | 0.169575E+10 | 3321.85 | 02-MAR-08:63 | 2.15 | 1.10 | 0.349717E+09 | 841.98 | 18-MAR-12:00 | 17.20 | 10.94 |
April | 0.217674E+10 | 15214.24 | 28-APR-07:03 | 11.28 | 10.34 | 0.367571E+09 | 842.92 | 29-APR-12:00 | 20.00 | 14.70 |
May | 0.294941E+10 | 17868.24 | 05-MAY-07:03 | 14.18 | 11.86 | 0.415028E+09 | 842.93 | 06-MAY-12:09 | 22.98 | 16.69 |
June | 0.364254E+10 | 21021.45 | 29-JUN-07:02 | 12.20 | 11.29 | 0.415340E+09 | 842.91 | 10-JUN-12:09 | 12.20 | 11.29 |
July | 0.463583E+10 | 21279.15 | 19-JUL-07:02 | 15.10 | 11.63 | 0.419799E+09 | 842.95 | 15-JUL-12:00 | 15.10 | 11.63 |
August | 0.510871E+10 | 21269.86 | 01-AUG-07:02 | 11.47 | 11.42 | 0.431483E+09 | 842.95 | 26-AUG-12:09 | 22.20 | 17.48 |
September | 0.358483E+10 | 21294.98 | 16-SEP-07:02 | 10.68 | 10.68 | 0.407493E+09 | 842.95 | 23-SEP-12:39 | 21.47 | 16.94 |
October | 0.244333E+10 | 9642.92 | 05-OCT-07:03 | 9.50 | 6.06 | 0.382885E+09 | 842.89 | 07-OCT-12:09 | 16.28 | 11.84 |
November | 0.113453E+10 | 3331.22 | 11-NOV-09:33 | 1.33 | 1.09 | 0.320363E+09 | 842.92 | 04-NOV-12:00 | 1.33 | 1.09 |
December | 0.591928E+09 | 4099.31 | 22-DEC-08:04 | 0.10 | -1.2 | 0.317852E+09 | 702.54 | 02-DEC-13:00 | 0.10 | -1.2 |
Annual Sum or Average | 0.290846E+11 | 0.444119E+10 | ||||||||
Minimum of Months | 0.366179E+09 | 3321.85 | -3.8 | -4.3 | 0.296141E+09 | 637.68 | 0.10 | -1.2 | ||
Maximum of Months | 0.510871E+10 | 21294.98 | 15.10 | 11.86 | 0.431483E+09 | 842.95 | 22.98 | 17.48 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.302677E+09 | 5282.57 | 07-JAN-08:03 | -3.8 | -3.8 | 0.317375E+09 | 637.68 | 14-JAN-13:00 | 5.00 | 1.73 |
February | 0.651841E+09 | 5223.16 | 19-FEB-09:04 | -3.1 | -4.3 | 0.295173E+09 | 732.23 | 25-FEB-13:50 | 14.50 | 11.67 |
March | 0.153521E+10 | 3265.25 | 05-MAR-09:04 | 3.40 | 2.59 | 0.346677E+09 | 840.00 | 18-MAR-12:00 | 17.20 | 10.94 |
April | 0.205467E+10 | 14425.62 | 28-APR-07:03 | 11.28 | 10.34 | 0.364020E+09 | 842.92 | 29-APR-12:00 | 20.00 | 14.70 |
May | 0.285770E+10 | 17715.46 | 07-MAY-08:62 | 17.52 | 14.34 | 0.413805E+09 | 842.93 | 06-MAY-12:09 | 17.52 | 14.34 |
June | 0.358784E+10 | 21078.52 | 29-JUN-07:02 | 12.20 | 11.29 | 0.415200E+09 | 842.91 | 10-JUN-12:09 | 12.20 | 11.29 |
July | 0.461683E+10 | 21309.53 | 19-JUL-07:02 | 15.10 | 11.63 | 0.419787E+09 | 842.95 | 15-JUL-12:00 | 15.10 | 11.63 |
August | 0.511035E+10 | 21377.68 | 01-AUG-07:02 | 11.47 | 11.42 | 0.431480E+09 | 842.95 | 26-AUG-12:09 | 22.20 | 17.48 |
September | 0.353031E+10 | 21359.17 | 16-SEP-07:02 | 10.68 | 10.68 | 0.407123E+09 | 842.95 | 23-SEP-12:39 | 21.47 | 16.94 |
October | 0.233908E+10 | 9187.83 | 05-OCT-07:03 | 9.50 | 6.06 | 0.379138E+09 | 842.89 | 07-OCT-12:09 | 16.28 | 11.84 |
November | 0.100935E+10 | 3725.11 | 24-NOV-08:04 | 1.97 | 1.45 | 0.318621E+09 | 842.91 | 04-NOV-12:00 | 1.97 | 1.45 |
December | 0.502010E+09 | 4533.29 | 26-DEC-08:04 | -1.1 | -1.2 | 0.317568E+09 | 695.88 | 02-DEC-13:00 | -1.1 | -1.2 |
Annual Sum or Average | 0.280979E+11 | 0.442597E+10 | ||||||||
Minimum of Months | 0.302677E+09 | 3265.25 | -3.8 | -4.3 | 0.295173E+09 | 637.68 | -1.1 | -1.2 | ||
Maximum of Months | 0.511035E+10 | 21377.68 | 17.52 | 14.34 | 0.431480E+09 | 842.95 | 22.20 | 17.48 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.226993E+09 | 5281.73 | 07-JAN-08:03 | -3.8 | -3.8 | 0.317269E+09 | 637.68 | 07-JAN-13:50 | 2.43 | 1.61 |
February | 0.538219E+09 | 5277.55 | 19-FEB-09:04 | -3.1 | -4.3 | 0.294005E+09 | 717.09 | 25-FEB-13:50 | 14.50 | 11.67 |
March | 0.133061E+10 | 3413.67 | 05-MAR-09:04 | 3.40 | 2.59 | 0.342857E+09 | 827.10 | 18-MAR-12:00 | 17.20 | 10.94 |
April | 0.187018E+10 | 11773.54 | 28-APR-07:03 | 11.28 | 10.34 | 0.358758E+09 | 842.92 | 29-APR-12:00 | 20.00 | 14.70 |
May | 0.265159E+10 | 17507.65 | 07-MAY-08:62 | 17.52 | 14.34 | 0.410464E+09 | 842.93 | 06-MAY-12:09 | 17.52 | 14.34 |
June | 0.338587E+10 | 20868.28 | 29-JUN-07:02 | 12.20 | 11.29 | 0.414562E+09 | 842.91 | 10-JUN-12:09 | 12.20 | 11.29 |
July | 0.444156E+10 | 21102.57 | 19-JUL-07:02 | 15.10 | 11.63 | 0.419700E+09 | 842.94 | 15-JUL-12:00 | 15.10 | 11.63 |
August | 0.493781E+10 | 21187.37 | 01-AUG-07:02 | 11.47 | 11.42 | 0.431401E+09 | 842.95 | 26-AUG-12:09 | 22.20 | 17.48 |
September | 0.334420E+10 | 21159.24 | 16-SEP-07:02 | 10.68 | 10.68 | 0.405811E+09 | 842.95 | 23-SEP-12:39 | 21.47 | 16.94 |
October | 0.215851E+10 | 7713.81 | 05-OCT-07:03 | 9.50 | 6.06 | 0.373627E+09 | 842.89 | 07-OCT-12:09 | 16.28 | 11.84 |
November | 0.859079E+09 | 3947.75 | 13-NOV-08:05 | 0.78 | 0.74 | 0.316409E+09 | 842.90 | 04-NOV-12:00 | 0.78 | 0.74 |
December | 0.399679E+09 | 4736.57 | 26-DEC-08:04 | -1.1 | -1.2 | 0.317232E+09 | 684.92 | 02-DEC-13:00 | -1.1 | -1.2 |
Annual Sum or Average | 0.261443E+11 | 0.440209E+10 | ||||||||
Minimum of Months | 0.226993E+09 | 3413.67 | -3.8 | -4.3 | 0.294005E+09 | 637.68 | -1.1 | -1.2 | ||
Maximum of Months | 0.493781E+10 | 21187.37 | 17.52 | 14.34 | 0.431401E+09 | 842.95 | 22.20 | 17.48 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.281266E+09 | 10656.41 | 21-JAN-09:04 | -1.0 | -1.1 | 0.108341E+10 | 1700.53 | 14-JAN-15:09 | -1.0 | -1.1 |
February | 0.946444E+09 | 9639.79 | 17-FEB-09:04 | 1.02 | 0.16 | 0.997804E+09 | 1941.62 | 27-FEB-17:10 | 18.62 | 12.15 |
March | 0.260251E+10 | 7790.29 | 05-MAR-10:04 | 3.98 | 2.65 | 0.114387E+10 | 2247.71 | 18-MAR-14:00 | 20.00 | 10.34 |
April | 0.379657E+10 | 9421.60 | 27-APR-14:50 | 27.02 | 17.21 | 0.118305E+10 | 2247.89 | 29-APR-14:09 | 21.28 | 14.86 |
May | 0.523729E+10 | 19435.46 | 07-MAY-09:02 | 16.38 | 13.91 | 0.135845E+10 | 2247.90 | 06-MAY-14:00 | 16.38 | 13.91 |
June | 0.611502E+10 | 29806.23 | 12-JUN-08:62 | 15.28 | 14.11 | 0.140831E+10 | 2247.85 | 03-JUN-14:09 | 15.28 | 14.11 |
July | 0.788893E+10 | 35160.85 | 20-JUL-08:62 | 17.38 | 13.38 | 0.143480E+10 | 2247.96 | 15-JUL-14:09 | 17.38 | 13.38 |
August | 0.877529E+10 | 35207.69 | 15-AUG-08:62 | 16.98 | 13.26 | 0.147808E+10 | 2247.96 | 26-AUG-14:30 | 20.35 | 16.60 |
September | 0.618924E+10 | 34555.59 | 10-SEP-09:02 | 16.28 | 13.48 | 0.136823E+10 | 2247.91 | 02-SEP-14:09 | 16.28 | 13.48 |
October | 0.422264E+10 | 8859.89 | 04-OCT-14:40 | 21.50 | 11.47 | 0.122657E+10 | 2247.83 | 07-OCT-14:00 | 18.30 | 12.37 |
November | 0.153452E+10 | 9172.74 | 11-NOV-10:03 | 1.97 | 1.65 | 0.106214E+10 | 2247.90 | 04-NOV-14:50 | 1.97 | 1.65 |
December | 0.576020E+09 | 9770.83 | 22-DEC-09:04 | 0.78 | -0.8 | 0.108544E+10 | 1700.53 | 02-DEC-15:09 | 0.78 | -0.8 |
Annual Sum or Average | 0.481658E+11 | 0.148301E+11 | ||||||||
Minimum of Months | 0.281266E+09 | 7790.29 | -1.0 | -1.1 | 0.997804E+09 | 1700.53 | -1.0 | -1.1 | ||
Maximum of Months | 0.877529E+10 | 35207.69 | 27.02 | 17.21 | 0.147808E+10 | 2247.96 | 21.28 | 16.60 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.119281E+09 | 5268.99 | 07-JAN-09:04 | -3.1 | -3.3 | 0.541960E+09 | 850.24 | 07-JAN-15:00 | 2.80 | 1.25 |
February | 0.388087E+09 | 5066.67 | 19-FEB-10:04 | -2.1 | -3.8 | 0.502066E+09 | 997.43 | 27-FEB-17:10 | 18.62 | 12.15 |
March | 0.107751E+10 | 3512.59 | 05-MAR-10:03 | 3.98 | 2.65 | 0.582945E+09 | 1123.85 | 18-MAR-14:09 | 20.00 | 10.47 |
April | 0.158169E+10 | 5015.21 | 27-APR-15:00 | 27.20 | 17.29 | 0.608180E+09 | 1123.89 | 29-APR-14:09 | 21.28 | 14.86 |
May | 0.228147E+10 | 15959.36 | 07-MAY-09:02 | 16.38 | 13.91 | 0.697967E+09 | 1123.90 | 06-MAY-14:00 | 16.38 | 13.91 |
June | 0.300269E+10 | 18770.08 | 21-JUN-08:62 | 14.68 | 12.63 | 0.710384E+09 | 1123.87 | 03-JUN-14:09 | 14.68 | 12.63 |
July | 0.404992E+10 | 19690.56 | 19-JUL-08:62 | 15.97 | 12.08 | 0.718592E+09 | 1123.93 | 15-JUL-14:09 | 15.97 | 12.08 |
August | 0.453361E+10 | 19689.37 | 01-AUG-08:62 | 11.85 | 11.55 | 0.739842E+09 | 1123.92 | 26-AUG-14:09 | 20.45 | 16.60 |
September | 0.297846E+10 | 18962.53 | 11-SEP-08:62 | 15.28 | 12.74 | 0.694338E+09 | 1123.91 | 23-SEP-14:09 | 23.30 | 17.84 |
October | 0.180694E+10 | 6847.77 | 04-OCT-08:62 | 14.18 | 9.87 | 0.630786E+09 | 1123.83 | 07-OCT-14:09 | 17.38 | 12.04 |
November | 0.647428E+09 | 3759.92 | 11-NOV-10:03 | 1.97 | 1.65 | 0.536036E+09 | 1123.90 | 04-NOV-14:50 | 1.97 | 1.65 |
December | 0.253877E+09 | 4602.87 | 25-DEC-10:04 | -0.3 | -0.3 | 0.543367E+09 | 890.21 | 02-DEC-15:09 | -0.3 | -0.3 |
Annual Sum or Average | 0.227210E+11 | 0.750646E+10 | ||||||||
Minimum of Months | 0.119281E+09 | 3512.59 | -3.1 | -3.8 | 0.502066E+09 | 850.24 | -0.3 | -0.3 | ||
Maximum of Months | 0.453361E+10 | 19690.56 | 27.20 | 17.29 | 0.739842E+09 | 1123.93 | 23.30 | 17.84 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.108812E+09 | 5273.16 | 07-JAN-09:04 | -3.1 | -3.3 | 0.541897E+09 | 850.24 | 07-JAN-15:39 | 2.97 | 1.40 |
February | 0.356675E+09 | 5038.63 | 19-FEB-10:04 | -2.1 | -3.8 | 0.501684E+09 | 997.43 | 27-FEB-17:10 | 18.62 | 12.15 |
March | 0.102690E+10 | 3521.37 | 24-MAR-08:02 | 4.08 | -0.6 | 0.581518E+09 | 1123.85 | 18-MAR-14:09 | 4.08 | -0.6 |
April | 0.153713E+10 | 4935.22 | 27-APR-15:00 | 27.20 | 17.29 | 0.606351E+09 | 1123.89 | 29-APR-14:09 | 21.28 | 14.86 |
May | 0.223647E+10 | 15017.01 | 07-MAY-09:02 | 16.38 | 13.91 | 0.696248E+09 | 1123.90 | 06-MAY-14:00 | 16.38 | 13.91 |
June | 0.293953E+10 | 18451.37 | 28-JUN-08:62 | 17.98 | 13.05 | 0.710001E+09 | 1123.87 | 03-JUN-14:09 | 17.98 | 13.05 |
July | 0.397763E+10 | 19545.46 | 19-JUL-08:62 | 15.97 | 12.08 | 0.718523E+09 | 1123.93 | 15-JUL-14:09 | 15.97 | 12.08 |
August | 0.446471E+10 | 19550.45 | 01-AUG-08:62 | 11.85 | 11.55 | 0.739795E+09 | 1123.92 | 26-AUG-14:09 | 20.45 | 16.60 |
September | 0.292900E+10 | 18819.94 | 11-SEP-08:62 | 15.28 | 12.74 | 0.693760E+09 | 1123.91 | 23-SEP-14:09 | 23.30 | 17.84 |
October | 0.176522E+10 | 5885.21 | 04-OCT-08:62 | 14.18 | 9.87 | 0.629287E+09 | 1123.83 | 07-OCT-14:09 | 17.38 | 12.04 |
November | 0.612790E+09 | 3811.73 | 11-NOV-10:03 | 1.97 | 1.65 | 0.535504E+09 | 1123.90 | 04-NOV-14:50 | 1.97 | 1.65 |
December | 0.226322E+09 | 4579.19 | 25-DEC-10:04 | -0.3 | -0.3 | 0.543261E+09 | 885.62 | 02-DEC-15:09 | -0.3 | -0.3 |
Annual Sum or Average | 0.221812E+11 | 0.749783E+10 | ||||||||
Minimum of Months | 0.108812E+09 | 3521.37 | -3.1 | -3.8 | 0.501684E+09 | 850.24 | -0.3 | -0.6 | ||
Maximum of Months | 0.446471E+10 | 19550.45 | 27.20 | 17.29 | 0.739795E+09 | 1123.93 | 23.30 | 17.84 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 61061966.85 | 4778.59 | 21-JAN-09:04 | -1.0 | -1.1 | 0.541713E+09 | 850.24 | 07-JAN-15:50 | -1.0 | -1.1 |
February | 0.255358E+09 | 4279.33 | 17-FEB-09:04 | 1.02 | 0.16 | 0.500153E+09 | 992.61 | 27-FEB-17:10 | 18.62 | 12.15 |
March | 0.822226E+09 | 3342.16 | 29-MAR-08:03 | 5.10 | 3.81 | 0.575817E+09 | 1123.85 | 18-MAR-14:00 | 5.10 | 3.81 |
April | 0.133267E+10 | 4664.55 | 27-APR-15:00 | 27.20 | 17.29 | 0.597975E+09 | 1123.89 | 29-APR-14:20 | 21.47 | 14.94 |
May | 0.202079E+10 | 11252.43 | 07-MAY-09:02 | 16.38 | 13.91 | 0.686075E+09 | 1123.90 | 06-MAY-14:00 | 16.38 | 13.91 |
June | 0.269895E+10 | 17541.39 | 28-JUN-08:62 | 17.98 | 13.05 | 0.707250E+09 | 1123.87 | 03-JUN-14:09 | 17.98 | 13.05 |
July | 0.374834E+10 | 18169.54 | 20-JUL-08:62 | 17.38 | 13.38 | 0.718141E+09 | 1123.93 | 15-JUL-14:09 | 17.38 | 13.38 |
August | 0.426403E+10 | 19248.43 | 01-AUG-08:62 | 11.85 | 11.55 | 0.739551E+09 | 1123.92 | 26-AUG-14:09 | 20.45 | 16.60 |
September | 0.272416E+10 | 17899.15 | 15-SEP-08:62 | 14.18 | 13.02 | 0.689203E+09 | 1123.91 | 23-SEP-14:09 | 23.30 | 17.84 |
October | 0.155179E+10 | 4367.92 | 04-OCT-15:00 | 21.70 | 11.49 | 0.620832E+09 | 1123.83 | 07-OCT-14:09 | 17.38 | 12.04 |
November | 0.482920E+09 | 4056.76 | 13-NOV-09:04 | 1.70 | 1.46 | 0.533095E+09 | 1123.89 | 04-NOV-14:00 | 1.70 | 1.46 |
December | 0.142109E+09 | 4352.39 | 22-DEC-09:04 | 0.78 | -0.8 | 0.542871E+09 | 866.28 | 02-DEC-15:09 | 0.78 | -0.8 |
Annual Sum or Average | 0.201044E+11 | 0.745268E+10 | ||||||||
Minimum of Months | 61061966.85 | 3342.16 | -1.0 | -1.1 | 0.500153E+09 | 850.24 | -1.0 | -1.1 | ||
Maximum of Months | 0.426403E+10 | 19248.43 | 27.20 | 17.29 | 0.739551E+09 | 1123.93 | 23.30 | 17.84 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5309226.13 | 3463.68 | 26-JAN-09:04 | 4.40 | 4.13 | 0.541594E+09 | 850.24 | 07-JAN-15:09 | 4.40 | 4.13 |
February | 73239372.69 | 4028.71 | 10-FEB-09:04 | 1.88 | 0.51 | 0.497678E+09 | 967.14 | 27-FEB-15:00 | 19.40 | 12.42 |
March | 0.360641E+09 | 3559.59 | 24-MAR-08:04 | 4.08 | -0.6 | 0.568117E+09 | 1123.87 | 18-MAR-14:00 | 4.08 | -0.6 |
April | 0.902773E+09 | 4595.69 | 27-APR-14:50 | 27.02 | 17.21 | 0.586101E+09 | 1123.89 | 29-APR-14:39 | 21.83 | 15.09 |
May | 0.158763E+10 | 4381.50 | 15-MAY-14:10 | 23.30 | 13.36 | 0.666939E+09 | 1123.91 | 06-MAY-14:00 | 23.30 | 13.36 |
June | 0.239433E+10 | 10442.37 | 28-JUN-08:62 | 17.98 | 13.05 | 0.699840E+09 | 1123.87 | 03-JUN-14:09 | 17.98 | 13.05 |
July | 0.350340E+10 | 18878.80 | 23-JUL-09:02 | 19.27 | 13.97 | 0.716341E+09 | 1123.93 | 15-JUL-14:30 | 19.27 | 13.97 |
August | 0.413050E+10 | 18170.40 | 09-AUG-08:62 | 21.72 | 14.33 | 0.738595E+09 | 1123.91 | 26-AUG-14:09 | 20.45 | 16.60 |
September | 0.240905E+10 | 17501.03 | 10-SEP-09:02 | 16.28 | 13.48 | 0.677494E+09 | 1123.92 | 23-SEP-14:09 | 23.30 | 17.84 |
October | 0.104570E+10 | 3900.44 | 04-OCT-15:00 | 21.70 | 11.49 | 0.606932E+09 | 1123.84 | 07-OCT-14:09 | 17.38 | 12.04 |
November | 0.195389E+09 | 3732.36 | 22-NOV-09:04 | 3.30 | 3.04 | 0.529999E+09 | 1123.89 | 04-NOV-14:00 | 3.30 | 3.04 |
December | 24029715.76 | 4207.59 | 06-DEC-09:04 | 1.12 | 1.00 | 0.542527E+09 | 850.24 | 02-DEC-15:09 | 1.12 | 1.00 |
Annual Sum or Average | 0.166320E+11 | 0.737216E+10 | ||||||||
Minimum of Months | 5309226.13 | 3463.68 | 1.12 | -0.6 | 0.497678E+09 | 850.24 | 1.12 | -0.6 | ||
Maximum of Months | 0.413050E+10 | 18878.80 | 27.02 | 17.21 | 0.738595E+09 | 1123.93 | 23.30 | 17.84 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.247593E+10 | 51133.56 | 01-JAN-09:01 | 7.80 |
February | 0.136337E+10 | 52493.42 | 23-FEB-09:01 | 11.20 |
March | 0.403045E+09 | 51010.59 | 06-MAR-09:01 | 7.30 |
April | 0.148847E+09 | 49371.47 | 18-APR-08:61 | 4.50 |
May | 81947088.36 | 1049.16 | 19-MAY-08:07 | 9.18 |
June | 75790315.45 | 848.32 | 01-JUN-07:25 | 11.65 |
July | 73519153.42 | 1026.73 | 23-JUL-07:07 | 16.38 |
August | 74239542.45 | 1206.61 | 13-AUG-07:07 | 18.17 |
September | 73619894.20 | 938.98 | 03-SEP-07:10 | 13.40 |
October | 97600843.72 | 15906.84 | 28-OCT-08:62 | 8.07 |
November | 0.719064E+09 | 50713.48 | 17-NOV-09:01 | 7.38 |
December | 0.185108E+10 | 52388.49 | 28-DEC-09:01 | 10.02 |
Annual Sum or Average | 0.743805E+10 | |||
Minimum of Months | 73519153.42 | 848.32 | 4.50 | |
Maximum of Months | 0.247593E+10 | 52493.42 | 18.17 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.623282E+09 | 25495.67 | 17-JAN-09:01 | 1.88 |
February | 0.356653E+09 | 25491.76 | 20-FEB-09:01 | 1.47 |
March | 0.121935E+09 | 2652.75 | 05-MAR-16:00 | 6.10 |
April | 0.106802E+09 | 1904.12 | 18-APR-08:06 | 4.50 |
May | 0.105862E+09 | 1162.62 | 18-MAY-07:25 | 6.10 |
June | 95169162.46 | 1171.79 | 11-JUN-07:10 | 12.98 |
July | 94126310.23 | 1459.24 | 23-JUL-07:07 | 16.38 |
August | 0.102616E+09 | 1542.70 | 13-AUG-07:07 | 18.17 |
September | 94042145.58 | 1297.28 | 03-SEP-07:10 | 13.40 |
October | 0.104346E+09 | 1158.99 | 12-OCT-07:25 | 6.95 |
November | 0.178100E+09 | 2746.01 | 23-NOV-17:30 | 5.85 |
December | 0.472863E+09 | 24847.23 | 26-DEC-09:01 | -0.9 |
Annual Sum or Average | 0.245580E+10 | |||
Minimum of Months | 94042145.58 | 1158.99 | -0.9 | |
Maximum of Months | 0.623282E+09 | 25495.67 | 18.17 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.104168E+10 | 26705.26 | 01-JAN-09:01 | 7.80 |
February | 0.545222E+09 | 25609.17 | 20-FEB-09:01 | 1.47 |
March | 0.149212E+09 | 4805.36 | 05-MAR-09:02 | 3.40 |
April | 0.109522E+09 | 1694.91 | 19-APR-07:07 | 4.18 |
May | 0.106889E+09 | 1078.55 | 17-MAY-07:00 | 8.90 |
June | 0.105435E+09 | 1073.53 | 11-JUN-08:00 | 13.90 |
July | 0.121901E+09 | 1640.65 | 23-JUL-16:12 | 27.43 |
August | 0.130801E+09 | 1952.13 | 10-AUG-19:03 | 29.18 |
September | 0.104363E+09 | 1087.48 | 17-SEP-08:00 | 11.10 |
October | 0.107354E+09 | 1102.84 | 15-OCT-08:00 | 8.30 |
November | 0.328643E+09 | 8919.02 | 24-NOV-08:62 | 1.97 |
December | 0.780037E+09 | 24928.95 | 25-DEC-09:01 | -0.1 |
Annual Sum or Average | 0.363106E+10 | |||
Minimum of Months | 0.104363E+09 | 1073.53 | -0.1 | |
Maximum of Months | 0.104168E+10 | 26705.26 | 29.18 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.121876E+10 | 26889.37 | 01-JAN-09:01 | 7.80 |
February | 0.626588E+09 | 25964.53 | 13-FEB-08:61 | 3.72 |
March | 0.174547E+09 | 9001.61 | 05-MAR-09:02 | 3.40 |
April | 0.112199E+09 | 1624.59 | 11-APR-07:07 | 5.60 |
May | 0.107197E+09 | 1079.71 | 17-MAY-07:00 | 8.90 |
June | 0.105788E+09 | 1073.00 | 11-JUN-08:00 | 13.90 |
July | 0.122130E+09 | 1644.81 | 23-JUL-16:12 | 27.43 |
August | 0.131134E+09 | 1954.18 | 10-AUG-19:03 | 29.18 |
September | 0.104616E+09 | 1089.25 | 17-SEP-08:00 | 11.10 |
October | 0.107947E+09 | 1106.66 | 15-OCT-08:00 | 8.30 |
November | 0.400476E+09 | 13728.85 | 24-NOV-08:62 | 1.97 |
December | 0.912131E+09 | 25081.31 | 25-DEC-09:01 | -0.1 |
Annual Sum or Average | 0.412351E+10 | |||
Minimum of Months | 0.104616E+09 | 1073.00 | -0.1 | |
Maximum of Months | 0.121876E+10 | 26889.37 | 29.18 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.146170E+10 | 26882.97 | 01-JAN-09:01 | 7.80 |
February | 0.757986E+09 | 25935.77 | 13-FEB-08:61 | 3.72 |
March | 0.217777E+09 | 13377.57 | 06-MAR-08:62 | 6.78 |
April | 0.119415E+09 | 2367.56 | 19-APR-07:03 | 4.18 |
May | 0.107180E+09 | 1077.13 | 17-MAY-07:00 | 8.90 |
June | 0.105851E+09 | 1070.44 | 11-JUN-08:00 | 13.90 |
July | 0.122315E+09 | 1645.67 | 23-JUL-16:12 | 27.43 |
August | 0.131528E+09 | 1959.42 | 10-AUG-19:03 | 29.18 |
September | 0.104461E+09 | 1086.68 | 17-SEP-08:00 | 11.10 |
October | 0.108504E+09 | 1104.64 | 15-OCT-08:00 | 8.30 |
November | 0.494962E+09 | 17944.25 | 24-NOV-08:62 | 1.97 |
December | 0.110167E+10 | 25566.30 | 27-DEC-08:62 | 4.50 |
Annual Sum or Average | 0.483335E+10 | |||
Minimum of Months | 0.104461E+09 | 1070.44 | 1.97 | |
Maximum of Months | 0.146170E+10 | 26882.97 | 29.18 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.259925E+10 | 56104.57 | 16-JAN-09:01 | -0.5 |
February | 0.129595E+10 | 56057.64 | 20-FEB-09:01 | 1.47 |
March | 0.368731E+09 | 50491.59 | 07-MAR-09:01 | 9.22 |
April | 0.134899E+09 | 48707.06 | 11-APR-08:61 | 5.68 |
May | 83451255.58 | 830.84 | 17-MAY-07:25 | 9.15 |
June | 79430603.06 | 822.17 | 19-JUN-07:25 | 13.35 |
July | 90612985.83 | 2128.27 | 23-JUL-16:03 | 27.62 |
August | 86965886.05 | 2300.80 | 13-AUG-16:03 | 28.08 |
September | 81009856.10 | 830.24 | 17-SEP-08:25 | 11.40 |
October | 0.104724E+09 | 19333.44 | 30-OCT-08:62 | 7.30 |
November | 0.814272E+09 | 51147.77 | 27-NOV-09:01 | 10.60 |
December | 0.190500E+10 | 51442.66 | 28-DEC-09:01 | 10.02 |
Annual Sum or Average | 0.764430E+10 | |||
Minimum of Months | 79430603.06 | 822.17 | -0.5 | |
Maximum of Months | 0.259925E+10 | 56104.57 | 28.08 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.155268E+10 | 28783.82 | 16-JAN-09:01 | -0.5 |
February | 0.805335E+09 | 28758.07 | 20-FEB-09:01 | 1.47 |
March | 0.254597E+09 | 25660.75 | 06-MAR-09:01 | 7.30 |
April | 0.128880E+09 | 16014.10 | 18-APR-08:61 | 4.50 |
May | 0.110538E+09 | 1110.52 | 18-MAY-07:25 | 6.10 |
June | 0.106406E+09 | 1096.91 | 01-JUN-07:25 | 11.65 |
July | 0.120143E+09 | 1620.83 | 23-JUL-16:12 | 27.43 |
August | 0.117767E+09 | 1718.92 | 13-AUG-16:12 | 27.97 |
September | 0.106586E+09 | 1108.69 | 17-SEP-08:25 | 11.40 |
October | 0.114185E+09 | 1227.58 | 28-OCT-08:04 | 8.07 |
November | 0.535613E+09 | 25217.05 | 26-NOV-10:01 | 5.18 |
December | 0.115946E+10 | 26352.09 | 28-DEC-09:01 | 10.02 |
Annual Sum or Average | 0.511219E+10 | |||
Minimum of Months | 0.106406E+09 | 1096.91 | -0.5 | |
Maximum of Months | 0.155268E+10 | 28783.82 | 27.97 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.162990E+10 | 28668.15 | 16-JAN-09:01 | -0.5 |
February | 0.851849E+09 | 28642.50 | 20-FEB-09:01 | 1.47 |
March | 0.274793E+09 | 25575.77 | 06-MAR-09:01 | 7.30 |
April | 0.132144E+09 | 18448.78 | 18-APR-08:61 | 4.50 |
May | 0.110189E+09 | 1106.26 | 18-MAY-07:25 | 6.10 |
June | 0.106037E+09 | 1092.39 | 01-JUN-07:25 | 11.65 |
July | 0.119756E+09 | 1619.20 | 23-JUL-16:12 | 27.43 |
August | 0.117298E+09 | 1716.95 | 13-AUG-16:12 | 27.97 |
September | 0.106198E+09 | 1103.70 | 17-SEP-08:25 | 11.40 |
October | 0.114602E+09 | 2861.19 | 30-OCT-08:62 | 7.30 |
November | 0.565025E+09 | 25126.31 | 26-NOV-10:01 | 5.18 |
December | 0.121477E+10 | 26253.88 | 28-DEC-09:01 | 10.02 |
Annual Sum or Average | 0.534257E+10 | |||
Minimum of Months | 0.106037E+09 | 1092.39 | -0.5 | |
Maximum of Months | 0.162990E+10 | 28668.15 | 27.97 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.198882E+10 | 28520.89 | 17-JAN-08:61 | 1.70 |
February | 0.109640E+10 | 28484.52 | 20-FEB-09:01 | 1.47 |
March | 0.402606E+09 | 25742.18 | 07-MAR-09:01 | 9.22 |
April | 0.163999E+09 | 24852.26 | 11-APR-08:61 | 5.68 |
May | 0.110374E+09 | 1099.83 | 17-MAY-07:25 | 9.15 |
June | 0.105869E+09 | 1087.23 | 19-JUN-07:25 | 13.35 |
July | 0.119698E+09 | 1619.76 | 23-JUL-16:12 | 27.43 |
August | 0.117108E+09 | 1715.64 | 13-AUG-16:12 | 27.97 |
September | 0.105958E+09 | 1099.03 | 17-SEP-08:25 | 11.40 |
October | 0.130419E+09 | 10181.57 | 30-OCT-08:62 | 7.30 |
November | 0.732049E+09 | 26051.81 | 27-NOV-09:01 | 10.60 |
December | 0.150288E+10 | 28395.02 | 26-DEC-08:61 | -1.1 |
Annual Sum or Average | 0.657618E+10 | |||
Minimum of Months | 0.105869E+09 | 1087.23 | -1.1 | |
Maximum of Months | 0.198882E+10 | 28520.89 | 27.97 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.380002E+10 | 30002.75 | 17-JAN-08:61 | 1.70 |
February | 0.234754E+10 | 29954.74 | 20-FEB-09:01 | 1.47 |
March | 0.111702E+10 | 29073.67 | 05-MAR-09:02 | 3.40 |
April | 0.409888E+09 | 27680.95 | 01-APR-08:62 | 11.57 |
May | 0.141901E+09 | 10675.79 | 18-MAY-08:63 | 6.28 |
June | 0.109818E+09 | 1158.84 | 01-JUN-07:25 | 11.65 |
July | 0.124597E+09 | 1682.47 | 23-JUL-16:12 | 27.43 |
August | 0.121667E+09 | 1773.32 | 13-AUG-16:12 | 27.97 |
September | 0.111696E+09 | 1181.98 | 17-SEP-08:25 | 11.40 |
October | 0.298022E+09 | 26472.42 | 28-OCT-08:62 | 8.07 |
November | 0.154499E+10 | 27724.00 | 27-NOV-09:01 | 10.60 |
December | 0.299623E+10 | 29859.53 | 26-DEC-08:61 | -1.1 |
Annual Sum or Average | 0.131234E+11 | |||
Minimum of Months | 0.109818E+09 | 1158.84 | -1.1 | |
Maximum of Months | 0.380002E+10 | 30002.75 | 27.97 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.869933E+10 | 5321.43 | 01-JAN-10:09 | 0.223514E+10 | 1348.26 | 01-JAN-10:09 |
February | 0.786449E+10 | 5321.43 | 01-FEB-10:09 | 0.202238E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.870841E+10 | 5321.43 | 01-MAR-10:09 | 0.224215E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.843013E+10 | 5321.43 | 01-APR-09:09 | 0.216638E+10 | 1348.26 | 01-APR-09:09 |
May | 0.869933E+10 | 5321.43 | 01-MAY-09:09 | 0.223514E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.843013E+10 | 5321.43 | 01-JUN-09:09 | 0.217123E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.870841E+10 | 5321.43 | 01-JUL-09:09 | 0.223729E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.869933E+10 | 5321.43 | 01-AUG-09:09 | 0.223756E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.843920E+10 | 5321.43 | 01-SEP-09:09 | 0.217096E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.869933E+10 | 5321.43 | 01-OCT-09:09 | 0.223514E+10 | 1348.26 | 01-OCT-09:09 |
November | 0.840290E+10 | 5321.43 | 01-NOV-09:09 | 0.215964E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.871748E+10 | 5321.43 | 01-DEC-10:09 | 0.224431E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.102498E+12 | 0.263573E+11 | ||||
Minimum of Months | 0.786449E+10 | 5321.43 | 0.202238E+10 | 1348.26 | ||
Maximum of Months | 0.871748E+10 | 5321.43 | 0.224431E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.479410E+10 | 2932.57 | 01-JAN-10:09 | 0.111757E+10 | 674.13 | 01-JAN-10:09 |
February | 0.433403E+10 | 2932.57 | 01-FEB-10:09 | 0.101119E+10 | 674.13 | 01-FEB-10:09 |
March | 0.479910E+10 | 2932.57 | 01-MAR-10:09 | 0.112107E+10 | 674.13 | 01-MAR-10:09 |
April | 0.464574E+10 | 2932.57 | 01-APR-09:09 | 0.108319E+10 | 674.13 | 01-APR-09:09 |
May | 0.479410E+10 | 2932.57 | 01-MAY-09:09 | 0.111757E+10 | 674.13 | 01-MAY-09:09 |
June | 0.464574E+10 | 2932.57 | 01-JUN-09:09 | 0.108562E+10 | 674.13 | 01-JUN-09:09 |
July | 0.479910E+10 | 2932.57 | 01-JUL-09:09 | 0.111865E+10 | 674.13 | 01-JUL-09:09 |
August | 0.479410E+10 | 2932.57 | 01-AUG-09:09 | 0.111878E+10 | 674.13 | 01-AUG-09:09 |
September | 0.465074E+10 | 2932.57 | 01-SEP-09:09 | 0.108548E+10 | 674.13 | 01-SEP-09:09 |
October | 0.479410E+10 | 2932.57 | 01-OCT-09:09 | 0.111757E+10 | 674.13 | 01-OCT-09:09 |
November | 0.463074E+10 | 2932.57 | 01-NOV-09:09 | 0.107982E+10 | 674.13 | 01-NOV-09:09 |
December | 0.480410E+10 | 2932.57 | 01-DEC-10:09 | 0.112215E+10 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.564857E+11 | 0.131787E+11 | ||||
Minimum of Months | 0.433403E+10 | 2932.57 | 0.101119E+10 | 674.13 | ||
Maximum of Months | 0.480410E+10 | 2932.57 | 0.112215E+10 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.338042E+10 | 2599.23 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.306129E+10 | 2599.23 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.345133E+10 | 2599.23 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.327995E+10 | 2599.23 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.341588E+10 | 2599.23 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.333314E+10 | 2599.23 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.336269E+10 | 2599.23 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.345133E+10 | 2599.23 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.327995E+10 | 2599.23 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.338042E+10 | 2599.23 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.327995E+10 | 2599.23 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.336269E+10 | 2599.23 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.400390E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.306129E+10 | 2599.23 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.345133E+10 | 2599.23 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.338042E+10 | 2599.23 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.306129E+10 | 2599.23 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.345133E+10 | 2599.23 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.327995E+10 | 2599.23 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.341588E+10 | 2599.23 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.333314E+10 | 2599.23 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.336269E+10 | 2599.23 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.345133E+10 | 2599.23 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.327995E+10 | 2599.23 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.338042E+10 | 2599.23 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.327995E+10 | 2599.23 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.336269E+10 | 2599.23 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.400390E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.306129E+10 | 2599.23 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.345133E+10 | 2599.23 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.338042E+10 | 2599.23 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.306129E+10 | 2599.23 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.345133E+10 | 2599.23 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.327995E+10 | 2599.23 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.341588E+10 | 2599.23 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.333314E+10 | 2599.23 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.336269E+10 | 2599.23 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.345133E+10 | 2599.23 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.327995E+10 | 2599.23 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.338042E+10 | 2599.23 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.327995E+10 | 2599.23 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.336269E+10 | 2599.23 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.400390E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.306129E+10 | 2599.23 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.345133E+10 | 2599.23 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.447638E+10 | 3746.51 | 01-JAN-11:09 | 0.162546E+10 | 1348.26 | 01-JAN-11:09 |
February | 0.405472E+10 | 3746.51 | 01-FEB-10:09 | 0.147229E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.457860E+10 | 3746.51 | 01-MAR-10:09 | 0.166213E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.434435E+10 | 3746.51 | 01-APR-09:09 | 0.157746E+10 | 1348.26 | 01-APR-09:09 |
May | 0.452749E+10 | 3746.51 | 01-MAY-09:09 | 0.164379E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.442101E+10 | 3746.51 | 01-JUN-09:09 | 0.160496E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.445083E+10 | 3746.51 | 01-JUL-09:09 | 0.161629E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.457860E+10 | 3746.51 | 01-AUG-09:09 | 0.166213E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.434435E+10 | 3746.51 | 01-SEP-09:09 | 0.157746E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.447638E+10 | 3746.51 | 01-OCT-10:09 | 0.162546E+10 | 1348.26 | 01-OCT-10:09 |
November | 0.434435E+10 | 3746.51 | 01-NOV-09:09 | 0.157746E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.445083E+10 | 3746.51 | 01-DEC-10:09 | 0.161629E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.530479E+11 | 0.192612E+11 | ||||
Minimum of Months | 0.405472E+10 | 3746.51 | 0.147229E+10 | 1348.26 | ||
Maximum of Months | 0.457860E+10 | 3746.51 | 0.166213E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.230731E+10 | 1931.10 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.208997E+10 | 1931.10 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.236000E+10 | 1931.10 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.223926E+10 | 1931.10 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.233366E+10 | 1931.10 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.227877E+10 | 1931.10 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.229414E+10 | 1931.10 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.236000E+10 | 1931.10 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.223926E+10 | 1931.10 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.230731E+10 | 1931.10 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.223926E+10 | 1931.10 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.229414E+10 | 1931.10 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.273431E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.208997E+10 | 1931.10 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.236000E+10 | 1931.10 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.230731E+10 | 1931.10 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.208997E+10 | 1931.10 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.236000E+10 | 1931.10 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.223926E+10 | 1931.10 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.233366E+10 | 1931.10 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.227877E+10 | 1931.10 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.229414E+10 | 1931.10 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.236000E+10 | 1931.10 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.223926E+10 | 1931.10 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.230731E+10 | 1931.10 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.223926E+10 | 1931.10 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.229414E+10 | 1931.10 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.273431E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.208997E+10 | 1931.10 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.236000E+10 | 1931.10 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.230731E+10 | 1931.10 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.208997E+10 | 1931.10 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.236000E+10 | 1931.10 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.223926E+10 | 1931.10 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.233366E+10 | 1931.10 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.227877E+10 | 1931.10 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.229414E+10 | 1931.10 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.236000E+10 | 1931.10 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.223926E+10 | 1931.10 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.230731E+10 | 1931.10 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.223926E+10 | 1931.10 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.229414E+10 | 1931.10 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.273431E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.208997E+10 | 1931.10 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.236000E+10 | 1931.10 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.230731E+10 | 1931.10 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.208997E+10 | 1931.10 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.236000E+10 | 1931.10 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.223926E+10 | 1931.10 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.233366E+10 | 1931.10 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.227877E+10 | 1931.10 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.229414E+10 | 1931.10 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.236000E+10 | 1931.10 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.223926E+10 | 1931.10 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.230731E+10 | 1931.10 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.223926E+10 | 1931.10 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.229414E+10 | 1931.10 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.273431E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.208997E+10 | 1931.10 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.236000E+10 | 1931.10 | 0.831065E+09 | 674.13 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.869933E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.448076E+10 |
February | 0.305697E+10 | 0.786449E+10 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357740E+10 |
March | 0.335708E+10 | 0.870841E+10 | 0.224215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322687E+10 |
April | 0.327081E+10 | 0.843013E+10 | 0.216638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24395190.27 | 0.253860E+10 |
May | 0.336680E+10 | 0.869933E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2651653.33 | 0.218801E+10 |
June | 0.325380E+10 | 0.843013E+10 | 0.217123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13746167.66 | 0.165177E+10 |
July | 0.339353E+10 | 0.870841E+10 | 0.223729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130180E+09 | 0.114165E+10 |
August | 0.334857E+10 | 0.869933E+10 | 0.223756E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278918E+09 | 0.945909E+09 |
September | 0.327932E+10 | 0.843920E+10 | 0.217096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3240947.60 | 0.155391E+10 |
October | 0.338624E+10 | 0.869933E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261374E+10 |
November | 0.327446E+10 | 0.840290E+10 | 0.215964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349754E+10 |
December | 0.340325E+10 | 0.871748E+10 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.409488E+10 |
Annual Sum or Average | 0.397770E+11 | 0.102498E+12 | 0.263573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453132E+09 | 0.315110E+11 |
Minimum of Months | 0.305697E+10 | 0.786449E+10 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.945909E+09 |
Maximum of Months | 0.340325E+10 | 0.871748E+10 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278918E+09 | 0.448076E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.479410E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226054E+10 |
February | 0.152844E+10 | 0.433403E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181128E+10 |
March | 0.167849E+10 | 0.479910E+10 | 0.112107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166981E+10 |
April | 0.163536E+10 | 0.464574E+10 | 0.108319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13270063.37 | 0.132566E+10 |
May | 0.168335E+10 | 0.479410E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1458710.14 | 0.113168E+10 |
June | 0.162685E+10 | 0.464574E+10 | 0.108562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7466795.06 | 0.794759E+09 |
July | 0.169671E+10 | 0.479910E+10 | 0.111865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70592254.19 | 0.524257E+09 |
August | 0.167424E+10 | 0.479410E+10 | 0.111878E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151709E+09 | 0.423317E+09 |
September | 0.163961E+10 | 0.465074E+10 | 0.108548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1785849.06 | 0.818697E+09 |
October | 0.169307E+10 | 0.479410E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138281E+10 |
November | 0.163718E+10 | 0.463074E+10 | 0.107982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179084E+10 |
December | 0.170157E+10 | 0.480410E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209532E+10 |
Annual Sum or Average | 0.198880E+11 | 0.564857E+11 | 0.131787E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246283E+09 | 0.160290E+11 |
Minimum of Months | 0.152844E+10 | 0.433403E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423317E+09 |
Maximum of Months | 0.170157E+10 | 0.480410E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151709E+09 | 0.226054E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.338042E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231760E+10 |
February | 0.914877E+09 | 0.306129E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185231E+10 |
March | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168891E+10 |
April | 0.984131E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13086801.63 | 0.135106E+10 |
May | 0.102058E+10 | 0.341588E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1456092.85 | 0.116926E+10 |
June | 0.998711E+09 | 0.333314E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7466662.08 | 0.830235E+09 |
July | 0.100600E+10 | 0.336269E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 67035633.82 | 0.561175E+09 |
August | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149613E+09 | 0.453935E+09 |
September | 0.984131E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1785802.28 | 0.842057E+09 |
October | 0.100722E+10 | 0.338042E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139903E+10 |
November | 0.973196E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181318E+10 |
December | 0.100600E+10 | 0.336269E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214222E+10 |
Annual Sum or Average | 0.119700E+11 | 0.400390E+11 | 0.104672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240444E+09 | 0.164210E+11 |
Minimum of Months | 0.914877E+09 | 0.306129E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453935E+09 |
Maximum of Months | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149613E+09 | 0.231760E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.338042E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231176E+10 |
February | 0.914877E+09 | 0.306129E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184468E+10 |
March | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167383E+10 |
April | 0.984131E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13090655.04 | 0.133406E+10 |
May | 0.102058E+10 | 0.341588E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1456086.89 | 0.116285E+10 |
June | 0.998711E+09 | 0.333314E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7466663.24 | 0.828948E+09 |
July | 0.100600E+10 | 0.336269E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 67036598.56 | 0.560935E+09 |
August | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149611E+09 | 0.453988E+09 |
September | 0.984131E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1785791.43 | 0.840185E+09 |
October | 0.100722E+10 | 0.338042E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138155E+10 |
November | 0.973196E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180255E+10 |
December | 0.100600E+10 | 0.336269E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213708E+10 |
Annual Sum or Average | 0.119700E+11 | 0.400390E+11 | 0.104672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240446E+09 | 0.163324E+11 |
Minimum of Months | 0.914877E+09 | 0.306129E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453988E+09 |
Maximum of Months | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149611E+09 | 0.231176E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.338042E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230728E+10 |
February | 0.914877E+09 | 0.306129E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183743E+10 |
March | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165716E+10 |
April | 0.984131E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13096138.02 | 0.131087E+10 |
May | 0.102058E+10 | 0.341588E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1456066.51 | 0.114764E+10 |
June | 0.998711E+09 | 0.333314E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7466660.80 | 0.824343E+09 |
July | 0.100600E+10 | 0.336269E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 67058654.45 | 0.558672E+09 |
August | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149624E+09 | 0.451958E+09 |
September | 0.984131E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1785762.02 | 0.834274E+09 |
October | 0.100722E+10 | 0.338042E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135740E+10 |
November | 0.973196E+09 | 0.327995E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179092E+10 |
December | 0.100600E+10 | 0.336269E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213265E+10 |
Annual Sum or Average | 0.119700E+11 | 0.400390E+11 | 0.104672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240487E+09 | 0.162106E+11 |
Minimum of Months | 0.914877E+09 | 0.306129E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451958E+09 |
Maximum of Months | 0.103395E+10 | 0.345133E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149624E+09 | 0.230728E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.447638E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420920E+10 |
February | 0.313522E+10 | 0.405472E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334477E+10 |
March | 0.355148E+10 | 0.457860E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298856E+10 |
April | 0.338259E+10 | 0.434435E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23661439.70 | 0.232913E+10 |
May | 0.349753E+10 | 0.452749E+10 | 0.164379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2614482.47 | 0.203025E+10 |
June | 0.343071E+10 | 0.442101E+10 | 0.160496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13430087.21 | 0.150938E+10 |
July | 0.344942E+10 | 0.445083E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121091E+09 | 0.103953E+10 |
August | 0.355148E+10 | 0.457860E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269481E+09 | 0.847870E+09 |
September | 0.338259E+10 | 0.434435E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3205613.91 | 0.148276E+10 |
October | 0.344359E+10 | 0.447638E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241204E+10 |
November | 0.331698E+10 | 0.434435E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324648E+10 |
December | 0.344942E+10 | 0.445083E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388070E+10 |
Annual Sum or Average | 0.410346E+11 | 0.530479E+11 | 0.192612E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.433483E+09 | 0.293207E+11 |
Minimum of Months | 0.313522E+10 | 0.405472E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.847870E+09 |
Maximum of Months | 0.355148E+10 | 0.457860E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269481E+09 | 0.420920E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230964E+10 |
February | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183843E+10 |
March | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165567E+10 |
April | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13121162.19 | 0.130253E+10 |
May | 0.174872E+10 | 0.233366E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1455984.68 | 0.114300E+10 |
June | 0.171530E+10 | 0.227877E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7466729.41 | 0.830779E+09 |
July | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 67140416.45 | 0.563699E+09 |
August | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149710E+09 | 0.457621E+09 |
September | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1785724.92 | 0.833934E+09 |
October | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135218E+10 |
November | 0.165844E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179022E+10 |
December | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213347E+10 |
Annual Sum or Average | 0.205167E+11 | 0.273431E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240680E+09 | 0.162112E+11 |
Minimum of Months | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.457621E+09 |
Maximum of Months | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149710E+09 | 0.230964E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230801E+10 |
February | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183627E+10 |
March | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165124E+10 |
April | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13126916.08 | 0.129737E+10 |
May | 0.174872E+10 | 0.233366E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1455976.60 | 0.113850E+10 |
June | 0.171530E+10 | 0.227877E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7466727.87 | 0.829093E+09 |
July | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 67153817.01 | 0.562658E+09 |
August | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149719E+09 | 0.456760E+09 |
September | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1785713.58 | 0.832306E+09 |
October | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134812E+10 |
November | 0.165844E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178774E+10 |
December | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213193E+10 |
Annual Sum or Average | 0.205167E+11 | 0.273431E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240708E+09 | 0.161800E+11 |
Minimum of Months | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456760E+09 |
Maximum of Months | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149719E+09 | 0.230801E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230041E+10 |
February | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182682E+10 |
March | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163214E+10 |
April | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13150544.83 | 0.127277E+10 |
May | 0.174872E+10 | 0.233366E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1455946.28 | 0.111224E+10 |
June | 0.171530E+10 | 0.227877E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7466725.24 | 0.819276E+09 |
July | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 67191240.26 | 0.558232E+09 |
August | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149742E+09 | 0.453243E+09 |
September | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1785677.32 | 0.820869E+09 |
October | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132520E+10 |
November | 0.165844E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177606E+10 |
December | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212487E+10 |
Annual Sum or Average | 0.205167E+11 | 0.273431E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240792E+09 | 0.160221E+11 |
Minimum of Months | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453243E+09 |
Maximum of Months | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149742E+09 | 0.230041E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274688E+10 |
February | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220247E+10 |
March | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198887E+10 |
April | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13765197.76 | 0.159552E+10 |
May | 0.174872E+10 | 0.233366E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1492781.54 | 0.137221E+10 |
June | 0.171530E+10 | 0.227877E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7782221.73 | 0.106792E+10 |
July | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 70033780.43 | 0.768113E+09 |
August | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155691E+09 | 0.645996E+09 |
September | 0.169125E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1820508.29 | 0.946580E+09 |
October | 0.172174E+10 | 0.230731E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161558E+10 |
November | 0.165844E+10 | 0.223926E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211986E+10 |
December | 0.172466E+10 | 0.229414E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249747E+10 |
Annual Sum or Average | 0.205167E+11 | 0.273431E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250585E+09 | 0.195675E+11 |
Minimum of Months | 0.156756E+10 | 0.208997E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.645996E+09 |
Maximum of Months | 0.177569E+10 | 0.236000E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155691E+09 | 0.274688E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 5321.43 | 01-JAN-10:09 | 1348.26 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 6851.57 | 07-JAN-12:10 |
February | 4050.04 | 03-FEB-13:09 | 5321.43 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 7078.81 | 18-FEB-18:00 |
March | 4050.04 | 03-MAR-13:09 | 5321.43 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 5122.21 | 22-MAR-11:10 |
April | 4050.04 | 01-APR-12:09 | 5321.43 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 996.74 | 01-APR-16:00 | 4438.64 | 18-APR-17:00 |
May | 4050.04 | 05-MAY-12:09 | 5321.43 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 321.47 | 05-MAY-16:00 | 4145.59 | 23-MAY-17:00 |
June | 4050.04 | 02-JUN-12:09 | 5321.43 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 818.14 | 28-JUN-17:00 | 3620.21 | 13-JUN-14:00 |
July | 4050.04 | 01-JUL-12:09 | 5321.43 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1923.97 | 24-JUL-15:00 | 3054.49 | 09-JUL-13:00 |
August | 4050.04 | 04-AUG-12:09 | 5321.43 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2236.67 | 10-AUG-17:00 | 3106.92 | 01-AUG-11:10 |
September | 4050.04 | 01-SEP-12:09 | 5321.43 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 323.76 | 14-SEP-17:00 | 3387.11 | 16-SEP-11:10 |
October | 4050.04 | 01-OCT-12:09 | 5321.43 | 01-OCT-09:09 | 1348.26 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3842.84 | 31-OCT-17:00 |
November | 4050.04 | 03-NOV-12:09 | 5321.43 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5652.45 | 12-NOV-17:00 |
December | 4050.04 | 01-DEC-13:09 | 5321.43 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6746.90 | 26-DEC-13:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 5321.43 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3054.49 | |||||
Maximum of Months | 4050.04 | 5321.43 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 2236.67 | 7078.81 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 2932.57 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3788.98 | 07-JAN-12:10 |
February | 2024.96 | 03-FEB-13:09 | 2932.57 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3839.40 | 18-FEB-18:00 |
March | 2024.96 | 03-MAR-13:09 | 2932.57 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2779.27 | 22-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 2932.57 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 536.87 | 01-APR-16:00 | 2413.10 | 18-APR-17:00 |
May | 2024.96 | 05-MAY-12:09 | 2932.57 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.00 | 05-MAY-16:00 | 2457.05 | 23-MAY-17:00 |
June | 2024.96 | 02-JUN-12:09 | 2932.57 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 449.30 | 28-JUN-17:00 | 2117.01 | 13-JUN-14:00 |
July | 2024.96 | 01-JUL-12:09 | 2932.57 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.67 | 24-JUL-15:00 | 1677.41 | 09-JUL-13:00 |
August | 2024.96 | 04-AUG-12:09 | 2932.57 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.30 | 10-AUG-17:00 | 1742.22 | 01-AUG-11:10 |
September | 2024.96 | 01-SEP-12:09 | 2932.57 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.81 | 14-SEP-17:00 | 2012.04 | 16-SEP-11:10 |
October | 2024.96 | 01-OCT-12:09 | 2932.57 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2105.79 | 29-OCT-11:10 |
November | 2024.96 | 03-NOV-12:09 | 2932.57 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3111.71 | 12-NOV-17:00 |
December | 2024.96 | 01-DEC-13:09 | 2932.57 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3697.90 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2932.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1677.41 | |||||
Maximum of Months | 2024.96 | 2932.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.30 | 3839.40 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2599.23 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3788.98 | 07-JAN-12:10 |
February | 2024.96 | 04-FEB-13:09 | 2599.23 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3839.40 | 18-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2599.23 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2779.27 | 22-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 2599.23 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 536.87 | 01-APR-16:00 | 2413.10 | 18-APR-17:00 |
May | 2024.96 | 06-MAY-12:09 | 2599.23 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.00 | 05-MAY-16:00 | 2441.05 | 23-MAY-17:00 |
June | 2024.96 | 03-JUN-12:09 | 2599.23 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 449.30 | 28-JUN-17:00 | 2100.86 | 13-JUN-14:00 |
July | 2024.96 | 01-JUL-12:09 | 2599.23 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.67 | 24-JUL-15:00 | 1677.43 | 09-JUL-13:00 |
August | 2024.96 | 05-AUG-12:09 | 2599.23 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.30 | 10-AUG-17:00 | 1742.22 | 01-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 2599.23 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.81 | 14-SEP-17:00 | 2022.63 | 16-SEP-11:10 |
October | 2024.96 | 07-OCT-12:09 | 2599.23 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2060.04 | 27-OCT-16:00 |
November | 2024.96 | 04-NOV-12:09 | 2599.23 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3111.71 | 12-NOV-17:00 |
December | 2024.96 | 02-DEC-13:09 | 2599.23 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3697.90 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2599.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1677.43 | |||||
Maximum of Months | 2024.96 | 2599.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.30 | 3839.40 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2599.23 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3788.98 | 07-JAN-12:10 |
February | 2024.96 | 04-FEB-13:09 | 2599.23 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3839.40 | 18-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2599.23 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2779.27 | 22-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 2599.23 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 536.87 | 01-APR-16:00 | 2413.10 | 18-APR-17:00 |
May | 2024.96 | 06-MAY-12:09 | 2599.23 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.00 | 05-MAY-16:00 | 2426.22 | 23-MAY-17:00 |
June | 2024.96 | 03-JUN-12:09 | 2599.23 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 449.30 | 28-JUN-17:00 | 2096.51 | 13-JUN-14:00 |
July | 2024.96 | 01-JUL-12:09 | 2599.23 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.67 | 24-JUL-15:00 | 1677.43 | 09-JUL-13:00 |
August | 2024.96 | 05-AUG-12:09 | 2599.23 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.30 | 10-AUG-17:00 | 1742.22 | 01-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 2599.23 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.81 | 14-SEP-17:00 | 2022.76 | 16-SEP-11:10 |
October | 2024.96 | 07-OCT-12:09 | 2599.23 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2041.32 | 31-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2599.23 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3111.71 | 12-NOV-17:00 |
December | 2024.96 | 02-DEC-13:09 | 2599.23 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3697.90 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2599.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1677.43 | |||||
Maximum of Months | 2024.96 | 2599.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.30 | 3839.40 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2599.23 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3788.98 | 07-JAN-12:10 |
February | 2024.96 | 04-FEB-13:09 | 2599.23 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3839.40 | 18-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2599.23 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2779.27 | 22-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 2599.23 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 536.87 | 01-APR-16:00 | 2413.10 | 18-APR-17:00 |
May | 2024.96 | 06-MAY-12:09 | 2599.23 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.00 | 05-MAY-16:00 | 2391.62 | 23-MAY-17:00 |
June | 2024.96 | 03-JUN-12:09 | 2599.23 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 449.30 | 28-JUN-17:00 | 2075.94 | 13-JUN-14:00 |
July | 2024.96 | 01-JUL-12:09 | 2599.23 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.67 | 24-JUL-15:00 | 1677.43 | 09-JUL-13:00 |
August | 2024.96 | 05-AUG-12:09 | 2599.23 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.30 | 10-AUG-17:00 | 1742.22 | 01-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 2599.23 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.80 | 14-SEP-17:00 | 2017.07 | 16-SEP-11:10 |
October | 2024.96 | 07-OCT-12:09 | 2599.23 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2041.32 | 31-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2599.23 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3111.71 | 12-NOV-17:00 |
December | 2024.96 | 02-DEC-13:09 | 2599.23 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3697.90 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2599.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1677.43 | |||||
Maximum of Months | 2024.96 | 2599.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.30 | 3839.40 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 3746.51 | 01-JAN-11:09 | 1348.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 6800.61 | 07-JAN-12:10 |
February | 5400.05 | 04-FEB-15:09 | 3746.51 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 6907.61 | 18-FEB-18:00 |
March | 5400.05 | 04-MAR-15:09 | 3746.51 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 5000.04 | 22-MAR-11:10 |
April | 5400.05 | 01-APR-14:09 | 3746.51 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 966.74 | 01-APR-16:00 | 4340.23 | 18-APR-17:00 |
May | 5400.05 | 06-MAY-14:09 | 3746.51 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 317.80 | 05-MAY-16:00 | 4062.98 | 23-MAY-17:00 |
June | 5400.05 | 03-JUN-14:09 | 3746.51 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 807.08 | 28-JUN-17:00 | 3543.74 | 13-JUN-14:00 |
July | 5400.05 | 01-JUL-14:09 | 3746.51 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1897.85 | 24-JUL-15:00 | 2994.36 | 09-JUL-13:00 |
August | 5400.05 | 05-AUG-14:09 | 3746.51 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2210.88 | 10-AUG-17:00 | 3087.87 | 01-AUG-11:10 |
September | 5400.05 | 02-SEP-14:09 | 3746.51 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 319.37 | 14-SEP-17:00 | 3485.38 | 16-SEP-11:10 |
October | 5400.05 | 07-OCT-14:09 | 3746.51 | 01-OCT-10:09 | 1348.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3682.21 | 31-OCT-17:00 |
November | 5400.05 | 04-NOV-14:09 | 3746.51 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5588.12 | 12-NOV-17:00 |
December | 5400.05 | 02-DEC-15:09 | 3746.51 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6644.20 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 3746.51 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2994.36 | |||||
Maximum of Months | 5400.05 | 3746.51 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 2210.88 | 6907.61 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1931.10 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3788.98 | 07-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1931.10 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3839.40 | 18-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1931.10 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2779.27 | 22-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1931.10 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 536.87 | 01-APR-16:00 | 2413.10 | 18-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 1931.10 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.00 | 05-MAY-16:00 | 2352.72 | 23-MAY-17:00 |
June | 2699.95 | 03-JUN-14:09 | 1931.10 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 449.30 | 28-JUN-17:00 | 2045.73 | 13-JUN-14:00 |
July | 2699.95 | 01-JUL-14:09 | 1931.10 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.66 | 24-JUL-15:00 | 1677.43 | 09-JUL-13:00 |
August | 2699.95 | 05-AUG-14:09 | 1931.10 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.30 | 10-AUG-17:00 | 1738.25 | 01-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1931.10 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.80 | 14-SEP-17:00 | 2009.08 | 16-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 1931.10 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2041.32 | 31-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1931.10 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3111.71 | 12-NOV-17:00 |
December | 2699.95 | 02-DEC-15:09 | 1931.10 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3697.90 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1677.43 | |||||
Maximum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.30 | 3839.40 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1931.10 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3788.98 | 07-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1931.10 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3839.40 | 18-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1931.10 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2779.27 | 22-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1931.10 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 536.87 | 01-APR-16:00 | 2413.10 | 18-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 1931.10 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.00 | 05-MAY-16:00 | 2344.98 | 23-MAY-17:00 |
June | 2699.95 | 03-JUN-14:09 | 1931.10 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 449.30 | 28-JUN-17:00 | 2039.88 | 13-JUN-14:00 |
July | 2699.95 | 01-JUL-14:09 | 1931.10 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.66 | 24-JUL-15:00 | 1677.43 | 09-JUL-13:00 |
August | 2699.95 | 05-AUG-14:09 | 1931.10 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.30 | 10-AUG-17:00 | 1736.74 | 01-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1931.10 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.80 | 14-SEP-17:00 | 2007.16 | 16-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 1931.10 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2041.32 | 31-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1931.10 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3111.71 | 12-NOV-17:00 |
December | 2699.95 | 02-DEC-15:09 | 1931.10 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3697.90 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1677.43 | |||||
Maximum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.30 | 3839.40 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1931.10 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3788.98 | 07-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1931.10 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3839.40 | 18-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1931.10 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2779.27 | 22-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1931.10 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 536.87 | 01-APR-16:00 | 2413.10 | 18-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 1931.10 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 176.99 | 05-MAY-16:00 | 2296.81 | 23-MAY-17:00 |
June | 2699.95 | 03-JUN-14:09 | 1931.10 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 449.30 | 28-JUN-17:00 | 2004.98 | 13-JUN-14:00 |
July | 2699.95 | 01-JUL-14:09 | 1931.10 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.66 | 24-JUL-15:00 | 1677.43 | 09-JUL-13:00 |
August | 2699.95 | 05-AUG-14:09 | 1931.10 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.30 | 10-AUG-17:00 | 1731.32 | 01-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1931.10 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.80 | 14-SEP-17:00 | 1985.28 | 16-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 1931.10 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2041.32 | 31-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1931.10 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3111.71 | 12-NOV-17:00 |
December | 2699.95 | 02-DEC-15:09 | 1931.10 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3697.90 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1677.43 | |||||
Maximum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.30 | 3839.40 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1931.10 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3839.94 | 07-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1931.10 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4010.60 | 18-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1931.10 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2901.44 | 22-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1931.10 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 566.87 | 01-APR-16:00 | 2511.52 | 18-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 1931.10 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 180.65 | 05-MAY-16:00 | 2260.42 | 23-MAY-17:00 |
June | 2699.95 | 03-JUN-14:09 | 1931.10 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 460.34 | 28-JUN-17:00 | 2006.80 | 13-JUN-14:00 |
July | 2699.95 | 01-JUL-14:09 | 1931.10 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1082.64 | 24-JUL-15:00 | 1679.50 | 09-JUL-13:00 |
August | 2699.95 | 05-AUG-14:09 | 1931.10 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1256.75 | 10-AUG-17:00 | 1790.76 | 01-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1931.10 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 182.17 | 14-SEP-17:00 | 1941.11 | 16-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 1931.10 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2201.94 | 31-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1931.10 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3176.04 | 12-NOV-17:00 |
December | 2699.95 | 02-DEC-15:09 | 1931.10 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3817.59 | 26-DEC-13:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1679.50 | |||||
Maximum of Months | 2699.95 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1256.75 | 4010.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10836.02 | 15-JAN-09:04 | 3037.53 | 25206.67 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1210.89 |
February | 9571.47 | 17-FEB-09:04 | 2700.03 | 22405.92 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 963.70 |
March | 8608.27 | 05-MAR-09:04 | 1687.52 | 14003.70 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 950.23 |
April | 10289.01 | 27-APR-16:10 | 3375.03 | 5321.43 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 911.82 | 0.00 |
May | 10035.37 | 15-MAY-16:20 | 3375.03 | 5321.43 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 49.62 | 0.00 |
June | 25401.06 | 28-JUN-08:62 | 1687.52 | 14003.70 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.78 |
July | 35898.24 | 20-JUL-08:62 | 2025.02 | 16804.44 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 302.92 |
August | 34566.18 | 09-AUG-08:62 | 2025.02 | 16804.44 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.17 |
September | 30708.00 | 14-SEP-08:62 | 1687.52 | 14003.70 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 318.11 |
October | 9156.89 | 04-OCT-16:10 | 3375.03 | 5321.43 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 864.62 |
November | 9697.48 | 11-NOV-09:05 | 1350.01 | 11202.96 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 976.16 |
December | 9997.06 | 25-DEC-09:04 | 2362.52 | 19605.18 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1000.77 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8608.27 | 1350.01 | 5321.43 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35898.24 | 3375.03 | 25206.67 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 911.82 | 1210.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5150.26 | 07-JAN-09:03 | 1349.97 | 12347.66 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 621.02 |
February | 4497.07 | 18-FEB-09:03 | 1349.97 | 12347.66 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 541.60 |
March | 3136.91 | 01-MAR-09:02 | 1012.48 | 9260.74 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 443.02 |
April | 19586.71 | 02-APR-17:07 | 20249.61 | 29325.68 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.97 |
May | 21044.53 | 14-MAY-19:33 | 12149.77 | 26393.11 | 6067.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.27 |
June | 20108.65 | 24-JUN-18:50 | 13499.74 | 23460.55 | 5393.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.15 |
July | 21229.45 | 06-JUL-08:62 | 843.73 | 7717.28 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.54 |
August | 20819.59 | 01-AUG-08:62 | 843.73 | 7717.28 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 318.70 |
September | 19829.21 | 11-SEP-08:62 | 843.73 | 7717.28 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.85 |
October | 20061.84 | 04-OCT-20:01 | 10124.81 | 29325.68 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.09 |
November | 3588.40 | 04-NOV-14:00 | 1349.97 | 2932.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 450.07 |
December | 4631.69 | 26-DEC-09:03 | 1349.97 | 12347.66 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 576.61 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3136.91 | 843.73 | 2932.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.09 | |
Maximum of Months | 21229.45 | 20249.61 | 29325.68 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 621.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5173.16 | 07-JAN-08:03 | 1012.48 | 8208.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 631.71 |
February | 5120.77 | 19-FEB-09:04 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 676.16 |
March | 3321.85 | 02-MAR-08:63 | 506.24 | 4104.04 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 491.32 |
April | 15214.24 | 28-APR-07:03 | 674.99 | 5472.06 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.82 |
May | 17868.24 | 05-MAY-07:03 | 674.99 | 5472.06 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.58 |
June | 21021.45 | 29-JUN-07:02 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294.39 |
July | 21279.15 | 19-JUL-07:02 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.83 |
August | 21269.86 | 01-AUG-07:02 | 1012.48 | 8208.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 341.20 |
September | 21294.98 | 16-SEP-07:02 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 321.39 |
October | 9642.92 | 05-OCT-07:03 | 506.24 | 4104.04 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 353.77 |
November | 3331.22 | 11-NOV-09:33 | 506.24 | 4104.04 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 478.05 |
December | 4099.31 | 22-DEC-08:04 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 534.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3321.85 | 506.24 | 4104.04 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.83 | |
Maximum of Months | 21294.98 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 676.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5282.57 | 07-JAN-08:03 | 1012.48 | 8208.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 633.73 |
February | 5223.16 | 19-FEB-09:04 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 678.29 |
March | 3265.25 | 05-MAR-09:04 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 458.83 |
April | 14425.62 | 28-APR-07:03 | 674.99 | 5472.06 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.70 |
May | 17715.46 | 07-MAY-08:62 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.03 |
June | 21078.52 | 29-JUN-07:02 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294.28 |
July | 21309.53 | 19-JUL-07:02 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.10 |
August | 21377.68 | 01-AUG-07:02 | 1012.48 | 8208.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 342.25 |
September | 21359.17 | 16-SEP-07:02 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 321.42 |
October | 9187.83 | 05-OCT-07:03 | 506.24 | 4104.04 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 353.66 |
November | 3725.11 | 24-NOV-08:04 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 488.25 |
December | 4533.29 | 26-DEC-08:04 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 579.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3265.25 | 506.24 | 4104.04 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.03 | |
Maximum of Months | 21377.68 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 678.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5281.73 | 07-JAN-08:03 | 1012.48 | 8208.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 630.04 |
February | 5277.55 | 19-FEB-09:04 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 677.81 |
March | 3413.67 | 05-MAR-09:04 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 461.42 |
April | 11773.54 | 28-APR-07:03 | 674.99 | 5472.06 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.27 |
May | 17507.65 | 07-MAY-08:62 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.88 |
June | 20868.28 | 29-JUN-07:02 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 291.31 |
July | 21102.57 | 19-JUL-07:02 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.21 |
August | 21187.37 | 01-AUG-07:02 | 1012.48 | 8208.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 339.67 |
September | 21159.24 | 16-SEP-07:02 | 843.73 | 6840.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 318.81 |
October | 7713.81 | 05-OCT-07:03 | 506.24 | 4104.04 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 353.26 |
November | 3947.75 | 13-NOV-08:05 | 674.99 | 5472.06 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 474.97 |
December | 4736.57 | 26-DEC-08:04 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 582.96 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3413.67 | 506.24 | 4104.04 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.88 | |
Maximum of Months | 21187.37 | 1349.97 | 10944.11 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 677.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10656.41 | 21-JAN-09:04 | 5940.06 | 15774.71 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 938.65 |
February | 9639.79 | 17-FEB-09:04 | 5940.06 | 15774.71 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 899.72 |
March | 7790.29 | 05-MAR-10:04 | 5940.06 | 15774.71 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 806.55 |
April | 9421.60 | 27-APR-14:50 | 4657.54 | 3746.51 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 897.01 | 0.00 |
May | 19435.46 | 07-MAY-09:02 | 2970.03 | 7887.36 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 343.64 |
June | 29806.23 | 12-JUN-08:62 | 3712.53 | 9859.20 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 387.77 |
July | 35160.85 | 20-JUL-08:62 | 4455.04 | 11831.03 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 283.76 |
August | 35207.69 | 15-AUG-08:62 | 3712.53 | 9859.20 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281.06 |
September | 34555.59 | 10-SEP-09:02 | 3712.53 | 9859.20 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 323.52 |
October | 8859.89 | 04-OCT-14:40 | 4657.54 | 3746.51 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 704.06 |
November | 9172.74 | 11-NOV-10:03 | 4455.04 | 11831.03 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 862.51 |
December | 9770.83 | 22-DEC-09:04 | 5940.06 | 15774.71 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 959.42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7790.29 | 2970.03 | 3746.51 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35207.69 | 5940.06 | 15774.71 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 897.01 | 959.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5268.99 | 07-JAN-09:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 625.20 |
February | 5066.67 | 19-FEB-10:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 656.98 |
March | 3512.59 | 05-MAR-10:03 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 443.31 |
April | 5015.21 | 27-APR-15:00 | 2328.71 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 528.76 | 0.00 |
May | 15959.36 | 07-MAY-09:02 | 1484.97 | 4065.46 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.08 |
June | 18770.08 | 21-JUN-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.46 |
July | 19690.56 | 19-JUL-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.77 |
August | 19689.37 | 01-AUG-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 315.13 |
September | 18962.53 | 11-SEP-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.59 |
October | 6847.77 | 04-OCT-08:62 | 1484.97 | 4065.46 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.37 |
November | 3759.92 | 11-NOV-10:03 | 2227.46 | 6098.20 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 471.35 |
December | 4602.87 | 25-DEC-10:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 549.73 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3512.59 | 1484.97 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19690.56 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 528.76 | 656.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5273.16 | 07-JAN-09:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 623.85 |
February | 5038.63 | 19-FEB-10:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 654.09 |
March | 3521.37 | 24-MAR-08:02 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 503.28 |
April | 4935.22 | 27-APR-15:00 | 2328.71 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 528.76 | 0.00 |
May | 15017.01 | 07-MAY-09:02 | 1484.97 | 4065.46 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.93 |
June | 18451.37 | 28-JUN-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.91 |
July | 19545.46 | 19-JUL-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.51 |
August | 19550.45 | 01-AUG-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 313.97 |
September | 18819.94 | 11-SEP-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.28 |
October | 5885.21 | 04-OCT-08:62 | 1484.97 | 4065.46 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.22 |
November | 3811.73 | 11-NOV-10:03 | 2227.46 | 6098.20 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 472.22 |
December | 4579.19 | 25-DEC-10:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 547.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3521.37 | 1484.97 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19550.45 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 528.76 | 654.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4778.59 | 21-JAN-09:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 521.23 |
February | 4279.33 | 17-FEB-09:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 495.56 |
March | 3342.16 | 29-MAR-08:03 | 2598.70 | 7114.56 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 470.94 |
April | 4664.55 | 27-APR-15:00 | 2328.71 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 528.76 | 0.00 |
May | 11252.43 | 07-MAY-09:02 | 1484.97 | 4065.46 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.34 |
June | 17541.39 | 28-JUN-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.46 |
July | 18169.54 | 20-JUL-08:62 | 2227.46 | 6098.20 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.65 |
August | 19248.43 | 01-AUG-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 309.42 |
September | 17899.15 | 15-SEP-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.71 |
October | 4367.92 | 04-OCT-15:00 | 2328.71 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 359.31 |
November | 4056.76 | 13-NOV-09:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 506.44 |
December | 4352.39 | 22-DEC-09:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 527.91 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3342.16 | 1484.97 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19248.43 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 528.76 | 527.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3463.68 | 26-JAN-09:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 462.22 |
February | 4028.71 | 10-FEB-09:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 548.24 |
March | 3559.59 | 24-MAR-08:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 672.21 |
April | 4595.69 | 27-APR-14:50 | 2328.71 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 514.32 | 0.00 |
May | 4381.50 | 15-MAY-14:10 | 2328.71 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.78 |
June | 10442.37 | 28-JUN-08:62 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.44 |
July | 18878.80 | 23-JUL-09:02 | 2227.46 | 6098.20 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.40 |
August | 18170.40 | 09-AUG-08:62 | 2227.46 | 6098.20 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.62 |
September | 17501.03 | 10-SEP-09:02 | 1856.21 | 5081.83 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.22 |
October | 3900.44 | 04-OCT-15:00 | 2328.71 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 373.96 |
November | 3732.36 | 22-NOV-09:04 | 2598.70 | 7114.56 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 568.82 |
December | 4207.59 | 06-DEC-09:04 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 515.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3463.68 | 1856.21 | 1931.10 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18878.80 | 2969.94 | 8130.93 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 514.32 | 672.21 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.809512E+11 | 64684.56 | 04-JAN-17:49 | 0.768213E+11 | 160915.29 | 07-JAN-09:09 |
February | 0.721203E+11 | 64010.14 | 10-FEB-19:40 | 0.490935E+11 | 152355.57 | 18-FEB-09:09 |
March | 0.791332E+11 | 63882.01 | 03-MAR-19:30 | 0.221382E+11 | 91880.37 | 24-MAR-08:09 |
April | 0.752975E+11 | 70770.78 | 27-APR-14:50 | 0.661378E+10 | 83621.82 | 18-APR-08:09 |
May | 0.780997E+11 | 68783.98 | 06-MAY-13:00 | 0.478217E+09 | 24095.08 | 18-MAY-08:20 |
June | 0.773039E+11 | 72396.24 | 28-JUN-14:00 | 1338675.61 | 750.49 | 15-JUN-08:30 |
July | 0.841613E+11 | 78768.90 | 31-JUL-13:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.896149E+11 | 82287.86 | 29-AUG-15:50 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.790358E+11 | 72845.91 | 12-SEP-14:50 | 16868755.62 | 5408.66 | 28-SEP-08:30 |
October | 0.790086E+11 | 62537.67 | 04-OCT-14:20 | 0.391643E+10 | 48621.88 | 30-OCT-08:09 |
November | 0.778109E+11 | 65484.01 | 14-NOV-17:40 | 0.366324E+11 | 112098.52 | 13-NOV-09:09 |
December | 0.809734E+11 | 64194.24 | 23-DEC-17:49 | 0.638925E+11 | 169226.58 | 26-DEC-09:09 |
Annual Sum or Average | 0.953511E+12 | 0.259605E+12 | ||||
Minimum of Months | 0.721203E+11 | 62537.67 | 0.00 | 0.00 | ||
Maximum of Months | 0.896149E+11 | 82287.86 | 0.768213E+11 | 169226.58 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.373403E+11 | 0.113004E+11 | 0.108804E+11 | 0.00 | 0.158402E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.558983E+10 | 0.00 |
February | 0.337970E+11 | 0.918288E+10 | 0.985143E+10 | 0.00 | 0.142233E+11 | 0.00 | 0.00 | 321437.97 | 0.00 | 0.00 | 0.00 | 0.506538E+10 | 0.00 |
March | 0.378801E+11 | 0.876309E+10 | 0.110560E+11 | 0.00 | 0.158167E+11 | 0.00 | 0.00 | 1723336.01 | 0.00 | 0.00 | 0.00 | 0.561556E+10 | 0.00 |
April | 0.362171E+11 | 0.707129E+10 | 0.105544E+11 | 0.00 | 0.150717E+11 | 0.00 | 0.00 | 0.104114E+10 | 0.00 | 0.00 | 0.00 | 0.534186E+10 | 0.00 |
May | 0.376032E+11 | 0.616727E+10 | 0.109629E+11 | 0.00 | 0.157988E+11 | 0.00 | 0.00 | 0.211513E+10 | 0.00 | 0.00 | 0.00 | 0.545234E+10 | 0.00 |
June | 0.366114E+11 | 0.538632E+10 | 0.106855E+11 | 0.00 | 0.154870E+11 | 0.00 | 0.00 | 0.390648E+10 | 0.00 | 0.00 | 0.00 | 0.522725E+10 | 0.00 |
July | 0.372230E+11 | 0.579839E+10 | 0.108424E+11 | 0.00 | 0.156995E+11 | 0.00 | 0.00 | 0.928429E+10 | 0.00 | 0.00 | 0.00 | 0.531379E+10 | 0.00 |
August | 0.378660E+11 | 0.675301E+10 | 0.110491E+11 | 0.00 | 0.159973E+11 | 0.00 | 0.00 | 0.126012E+11 | 0.00 | 0.00 | 0.00 | 0.534820E+10 | 0.00 |
September | 0.362312E+11 | 0.786677E+10 | 0.105613E+11 | 0.00 | 0.153138E+11 | 0.00 | 0.00 | 0.389036E+10 | 0.00 | 0.00 | 0.00 | 0.517237E+10 | 0.00 |
October | 0.373403E+11 | 0.958599E+10 | 0.108804E+11 | 0.00 | 0.155801E+11 | 0.00 | 0.00 | 0.217438E+09 | 0.00 | 0.00 | 0.00 | 0.540434E+10 | 0.00 |
November | 0.361749E+11 | 0.105549E+11 | 0.105443E+11 | 0.00 | 0.151793E+11 | 0.00 | 0.00 | 45689381.53 | 0.00 | 0.00 | 0.00 | 0.531182E+10 | 0.00 |
December | 0.372370E+11 | 0.116341E+11 | 0.108529E+11 | 0.00 | 0.156972E+11 | 0.00 | 0.00 | 36020.10 | 0.00 | 0.00 | 0.00 | 0.555214E+10 | 0.00 |
Annual Sum or Average | 0.441522E+12 | 0.100064E+12 | 0.128721E+12 | 0.00 | 0.185705E+12 | 0.00 | 0.00 | 0.331039E+11 | 0.00 | 0.00 | 0.00 | 0.643949E+11 | 0.00 |
Minimum of Months | 0.337970E+11 | 0.538632E+10 | 0.985143E+10 | 0.00 | 0.142233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.506538E+10 | 0.00 |
Maximum of Months | 0.378801E+11 | 0.116341E+11 | 0.110560E+11 | 0.00 | 0.159973E+11 | 0.00 | 0.00 | 0.126012E+11 | 0.00 | 0.00 | 0.00 | 0.561556E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.768213E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.490935E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.221382E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.661378E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.478217E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 1338675.61 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 16868755.62 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.391643E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.366324E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.638925E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.259605E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.768213E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 27522.57 | 01-JAN-11:09 | 7619.51 | 01-JAN-06:10 | 8089.53 | 01-JAN-11:09 | 0.00 | 11999.60 | 07-JAN-09:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 27522.57 | 01-FEB-10:09 | 7619.51 | 01-FEB-06:10 | 8089.53 | 01-FEB-10:09 | 0.00 | 11931.24 | 18-FEB-09:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 27522.57 | 01-MAR-10:09 | 7619.51 | 01-MAR-06:10 | 8089.53 | 01-MAR-10:09 | 0.00 | 11546.46 | 24-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 27522.57 | 01-APR-09:09 | 7619.51 | 01-APR-05:10 | 8089.53 | 01-APR-09:09 | 0.00 | 11465.56 | 18-APR-08:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 27522.57 | 01-MAY-09:09 | 7619.51 | 01-MAY-19:19 | 8089.53 | 01-MAY-09:09 | 0.00 | 11078.95 | 18-MAY-08:20 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 27522.57 | 01-JUN-09:09 | 7619.51 | 01-JUN-19:00 | 8089.53 | 01-JUN-09:09 | 0.00 | 11144.85 | 12-JUN-08:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 27522.57 | 01-JUL-09:09 | 7619.51 | 01-JUL-20:10 | 8089.53 | 01-JUL-09:09 | 0.00 | 11497.77 | 24-JUL-08:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 27522.57 | 01-AUG-09:09 | 7619.51 | 01-AUG-19:40 | 8089.53 | 01-AUG-09:09 | 0.00 | 11554.11 | 10-AUG-08:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 27522.57 | 01-SEP-09:09 | 7619.51 | 01-SEP-05:10 | 8089.53 | 01-SEP-09:09 | 0.00 | 11319.97 | 14-SEP-08:09 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 27522.57 | 01-OCT-10:09 | 7619.51 | 01-OCT-05:10 | 8089.53 | 01-OCT-10:09 | 0.00 | 11209.32 | 30-OCT-08:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 27522.57 | 01-NOV-09:09 | 7619.51 | 01-NOV-05:10 | 8089.53 | 01-NOV-09:09 | 0.00 | 11620.33 | 13-NOV-09:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 27522.57 | 01-DEC-10:09 | 7619.51 | 01-DEC-06:10 | 8089.53 | 01-DEC-10:09 | 0.00 | 11984.13 | 26-DEC-09:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 27522.57 | 7619.51 | 8089.53 | 0.00 | 11078.95 | 0.00 | 0.00 | |||||
Maximum of Months | 27522.57 | 7619.51 | 8089.53 | 0.00 | 11999.60 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 13622.60 | 17-JAN-14:30 | 0.00 |
February | 341.71 | 27-FEB-21:10 | 0.00 | 0.00 | 0.00 | 11041.65 | 21-FEB-14:39 | 0.00 |
March | 314.95 | 18-MAR-21:30 | 0.00 | 0.00 | 0.00 | 9697.49 | 03-MAR-12:09 | 0.00 |
April | 19022.44 | 27-APR-14:00 | 0.00 | 0.00 | 0.00 | 9679.98 | 13-APR-15:00 | 0.00 |
May | 17193.64 | 06-MAY-12:00 | 0.00 | 0.00 | 0.00 | 9718.34 | 03-MAY-13:09 | 0.00 |
June | 19075.50 | 28-JUN-16:00 | 0.00 | 0.00 | 0.00 | 9681.97 | 13-JUN-11:39 | 0.00 |
July | 26421.21 | 24-JUL-14:00 | 0.00 | 0.00 | 0.00 | 11465.16 | 29-JUL-13:00 | 0.00 |
August | 28884.73 | 29-AUG-14:00 | 0.00 | 0.00 | 0.00 | 11756.14 | 07-AUG-10:00 | 0.00 |
September | 19746.64 | 14-SEP-14:09 | 0.00 | 0.00 | 0.00 | 9708.66 | 06-SEP-12:20 | 0.00 |
October | 10320.48 | 04-OCT-14:00 | 0.00 | 0.00 | 0.00 | 11756.91 | 15-OCT-13:50 | 0.00 |
November | 5045.27 | 04-NOV-14:39 | 0.00 | 0.00 | 0.00 | 11848.57 | 14-NOV-13:09 | 0.00 |
December | 60.03 | 03-DEC-20:19 | 0.00 | 0.00 | 0.00 | 10089.63 | 02-DEC-12:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9679.98 | 0.00 | ||
Maximum of Months | 28884.73 | 0.00 | 0.00 | 0.00 | 13622.60 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 64684.56 | 04-JAN-17:49 | 27522.57 | 8089.53 | 7619.51 | 0.00 | 11198.10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 64010.14 | 10-FEB-19:40 | 27522.57 | 8089.53 | 7619.51 | 0.00 | 11096.55 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 63882.01 | 03-MAR-19:30 | 27522.57 | 8089.53 | 7619.51 | 0.00 | 10965.64 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 70770.78 | 27-APR-14:50 | 27522.57 | 8089.53 | 0.00 | 0.00 | 10856.69 | 0.00 | 0.00 | 18847.40 | 0.00 |
May | 68783.98 | 06-MAY-13:00 | 27522.57 | 8089.53 | 0.00 | 0.00 | 10856.69 | 0.00 | 0.00 | 16848.26 | 0.00 |
June | 72396.24 | 28-JUN-14:00 | 27522.57 | 8089.53 | 0.00 | 0.00 | 10856.69 | 0.00 | 0.00 | 18358.80 | 0.00 |
July | 78768.90 | 31-JUL-13:00 | 27522.57 | 8089.53 | 0.00 | 0.00 | 10969.11 | 0.00 | 0.00 | 24868.90 | 0.00 |
August | 82287.86 | 29-AUG-15:50 | 27522.57 | 8089.53 | 0.00 | 0.00 | 11189.02 | 0.00 | 0.00 | 27932.15 | 0.00 |
September | 72845.91 | 12-SEP-14:50 | 27522.57 | 8089.53 | 0.00 | 0.00 | 10856.69 | 0.00 | 0.00 | 18809.86 | 0.00 |
October | 62537.67 | 04-OCT-14:20 | 27522.57 | 8089.53 | 0.00 | 0.00 | 10856.69 | 0.00 | 0.00 | 9434.68 | 0.00 |
November | 65484.01 | 14-NOV-17:40 | 27522.57 | 8089.53 | 7619.51 | 0.00 | 11225.02 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 64194.24 | 23-DEC-17:49 | 27522.57 | 8089.53 | 7619.51 | 0.00 | 11271.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 62537.67 | 27522.57 | 8089.53 | 0.00 | 0.00 | 10856.69 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 82287.86 | 27522.57 | 8089.53 | 7619.51 | 0.00 | 11271.35 | 0.00 | 0.00 | 27932.15 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 160915.29 | 07-JAN-09:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 152355.57 | 18-FEB-09:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 91880.37 | 24-MAR-08:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 83621.82 | 18-APR-08:09 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 24095.08 | 18-MAY-08:20 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 750.49 | 15-JUN-08:30 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 5408.66 | 28-SEP-08:30 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 48621.88 | 30-OCT-08:09 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 112098.52 | 13-NOV-09:09 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 169226.58 | 26-DEC-09:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 169226.58 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.33 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
February | 0.33 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
Annual Sum or Average | 2.33 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.33 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.50 | 14.97 | 0.00 | 14.97 | 0.00 | 14.97 | 0.00 | 14.97 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 14.97 | 0.00 | 14.97 | 0.00 | 14.97 | 0.00 | 14.97 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 14.97 | 0.00 | 14.97 | 0.00 | 14.97 | 0.00 | 14.97 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 20.98 | 166.67 | 20.91 | 166.67 | 20.88 |
February | 448.00 | 21.09 | 119.67 | 21.01 | 119.67 | 20.96 |
March | 497.00 | 21.24 | 43.50 | 21.17 | 43.50 | 21.12 |
April | 423.50 | 21.76 | 29.17 | 21.81 | 10.83 | 21.78 |
May | 309.17 | 22.43 | 62.50 | 22.68 | 0.00 | 22.68 |
June | 119.00 | 23.01 | 137.83 | 23.48 | 0.00 | 23.48 |
July | 36.17 | 23.47 | 322.33 | 23.86 | 0.00 | 23.86 |
August | 25.50 | 23.39 | 387.83 | 23.88 | 0.00 | 23.88 |
September | 133.00 | 22.81 | 215.33 | 23.48 | 0.00 | 23.48 |
October | 390.17 | 21.80 | 13.83 | 21.87 | 0.83 | 21.86 |
November | 463.17 | 21.18 | 38.67 | 21.15 | 34.33 | 21.10 |
December | 496.00 | 21.00 | 105.33 | 20.93 | 105.33 | 20.88 |
Annual Sum or Average | 3836.67 | 21.50 | 1642.67 | 21.94 | 481.17 | 21.83 |
Minimum of Months | 25.50 | 20.98 | 13.83 | 20.91 | 0.00 | 20.88 |
Maximum of Months | 497.00 | 23.47 | 387.83 | 23.88 | 166.67 | 23.88 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.45 | 33.17 | 21.41 | 33.17 | 21.37 |
February | 438.50 | 21.72 | 20.83 | 21.67 | 20.83 | 21.63 |
March | 492.50 | 22.28 | 0.50 | 22.28 | 0.50 | 22.28 |
April | 372.50 | 22.85 | 27.17 | 22.92 | 0.00 | 22.92 |
May | 155.50 | 23.32 | 70.00 | 23.49 | 0.00 | 23.49 |
June | 31.17 | 23.53 | 162.17 | 23.87 | 0.00 | 23.87 |
July | 7.17 | 23.50 | 321.50 | 23.92 | 0.00 | 23.92 |
August | 3.17 | 22.82 | 382.83 | 23.93 | 0.00 | 23.93 |
September | 33.67 | 23.38 | 264.00 | 23.85 | 0.00 | 23.85 |
October | 314.83 | 22.91 | 25.00 | 22.98 | 0.00 | 22.98 |
November | 444.00 | 21.90 | 14.33 | 21.95 | 1.67 | 21.94 |
December | 496.00 | 21.56 | 15.17 | 21.53 | 15.17 | 21.51 |
Annual Sum or Average | 3285.00 | 22.12 | 1336.67 | 22.59 | 71.33 | 22.56 |
Minimum of Months | 3.17 | 21.45 | 0.50 | 21.41 | 0.00 | 21.37 |
Maximum of Months | 496.00 | 23.53 | 382.83 | 23.93 | 33.17 | 23.93 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.12 | 68.17 | 21.12 | 68.17 | 21.12 |
February | 336.00 | 21.32 | 37.83 | 21.30 | 37.83 | 21.28 |
March | 379.00 | 21.65 | 4.83 | 21.64 | 4.83 | 21.64 |
April | 296.17 | 22.30 | 22.33 | 22.42 | 0.00 | 22.42 |
May | 138.00 | 22.98 | 64.17 | 23.33 | 0.00 | 23.33 |
June | 35.17 | 23.42 | 134.50 | 23.94 | 0.00 | 23.94 |
July | 6.17 | 23.81 | 266.00 | 24.04 | 0.17 | 24.04 |
August | 4.00 | 23.87 | 328.17 | 24.03 | 0.33 | 24.03 |
September | 49.67 | 23.23 | 200.00 | 23.84 | 0.00 | 23.84 |
October | 254.50 | 22.33 | 17.00 | 22.44 | 0.00 | 22.44 |
November | 346.17 | 21.40 | 14.83 | 21.45 | 6.50 | 21.45 |
December | 369.00 | 21.13 | 37.67 | 21.13 | 37.67 | 21.13 |
Annual Sum or Average | 2584.83 | 21.70 | 1195.50 | 22.32 | 155.50 | 22.27 |
Minimum of Months | 4.00 | 21.12 | 4.83 | 21.12 | 0.00 | 21.12 |
Maximum of Months | 379.00 | 23.87 | 328.17 | 24.04 | 68.17 | 24.04 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.12 | 82.33 | 21.12 | 82.33 | 21.11 |
February | 336.00 | 21.29 | 45.67 | 21.27 | 45.67 | 21.25 |
March | 379.00 | 21.57 | 8.33 | 21.56 | 8.33 | 21.55 |
April | 301.83 | 22.21 | 20.17 | 22.32 | 0.17 | 22.32 |
May | 148.67 | 22.95 | 62.33 | 23.28 | 0.00 | 23.28 |
June | 37.33 | 23.41 | 131.00 | 23.93 | 0.00 | 23.93 |
July | 7.00 | 23.80 | 265.50 | 24.04 | 0.17 | 24.04 |
August | 4.00 | 23.87 | 327.33 | 24.03 | 0.33 | 24.03 |
September | 54.83 | 23.21 | 195.83 | 23.82 | 0.00 | 23.82 |
October | 266.67 | 22.25 | 14.50 | 22.34 | 0.00 | 22.34 |
November | 348.00 | 21.36 | 17.83 | 21.39 | 12.00 | 21.38 |
December | 369.00 | 21.12 | 49.17 | 21.12 | 49.17 | 21.12 |
Annual Sum or Average | 2623.33 | 21.67 | 1220.00 | 22.27 | 198.17 | 22.21 |
Minimum of Months | 4.00 | 21.12 | 8.33 | 21.12 | 0.00 | 21.11 |
Maximum of Months | 379.00 | 23.87 | 327.33 | 24.04 | 82.33 | 24.04 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 104.67 | 21.11 | 104.67 | 21.11 |
February | 336.00 | 21.26 | 58.83 | 21.23 | 58.83 | 21.22 |
March | 379.00 | 21.48 | 14.33 | 21.47 | 14.33 | 21.46 |
April | 310.33 | 22.09 | 19.33 | 22.19 | 1.00 | 22.19 |
May | 179.50 | 22.87 | 56.50 | 23.16 | 0.00 | 23.16 |
June | 47.67 | 23.34 | 118.17 | 23.87 | 0.00 | 23.87 |
July | 8.67 | 23.69 | 256.33 | 24.03 | 0.00 | 24.03 |
August | 6.83 | 23.75 | 320.67 | 24.02 | 0.33 | 24.02 |
September | 68.50 | 23.12 | 177.83 | 23.75 | 0.00 | 23.75 |
October | 276.83 | 22.10 | 12.67 | 22.18 | 0.00 | 22.18 |
November | 350.00 | 21.31 | 21.00 | 21.33 | 16.83 | 21.32 |
December | 369.00 | 21.12 | 62.67 | 21.12 | 62.67 | 21.12 |
Annual Sum or Average | 2703.33 | 21.64 | 1223.00 | 22.20 | 258.67 | 22.13 |
Minimum of Months | 6.83 | 21.11 | 12.67 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 379.00 | 23.75 | 320.67 | 24.03 | 104.67 | 24.03 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 144.50 | 21.11 | 144.50 | 21.11 |
February | 308.00 | 21.19 | 102.50 | 21.17 | 102.50 | 21.15 |
March | 348.00 | 21.27 | 18.33 | 21.26 | 18.33 | 21.25 |
April | 298.33 | 21.76 | 17.83 | 21.85 | 2.67 | 21.85 |
May | 224.17 | 22.51 | 43.17 | 22.74 | 0.00 | 22.74 |
June | 80.50 | 23.03 | 92.50 | 23.52 | 0.00 | 23.52 |
July | 18.00 | 23.39 | 223.33 | 23.90 | 0.00 | 23.90 |
August | 13.67 | 23.29 | 278.83 | 23.89 | 0.00 | 23.89 |
September | 99.67 | 22.71 | 138.17 | 23.41 | 0.00 | 23.41 |
October | 271.33 | 21.73 | 8.17 | 21.79 | 0.00 | 21.79 |
November | 324.50 | 21.19 | 21.50 | 21.18 | 21.50 | 21.18 |
December | 338.00 | 21.11 | 90.00 | 21.11 | 90.00 | 21.11 |
Annual Sum or Average | 2664.17 | 21.54 | 1178.83 | 22.00 | 379.50 | 21.92 |
Minimum of Months | 13.67 | 21.11 | 8.17 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 348.00 | 23.39 | 278.83 | 23.90 | 144.50 | 23.90 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 139.33 | 21.11 | 139.33 | 21.11 |
February | 308.00 | 21.23 | 101.33 | 21.20 | 101.33 | 21.18 |
March | 348.00 | 21.42 | 19.67 | 21.40 | 19.67 | 21.39 |
April | 296.17 | 22.04 | 17.00 | 22.12 | 2.67 | 22.11 |
May | 202.17 | 22.91 | 38.00 | 23.08 | 0.00 | 23.08 |
June | 54.50 | 23.37 | 79.00 | 23.73 | 0.00 | 23.73 |
July | 12.17 | 23.66 | 214.00 | 23.94 | 0.00 | 23.94 |
August | 7.67 | 23.63 | 265.67 | 23.93 | 0.17 | 23.93 |
September | 74.17 | 23.07 | 139.83 | 23.64 | 0.00 | 23.64 |
October | 261.33 | 22.02 | 6.00 | 22.06 | 0.00 | 22.06 |
November | 322.50 | 21.26 | 23.83 | 21.26 | 22.17 | 21.25 |
December | 338.00 | 21.11 | 88.67 | 21.11 | 88.67 | 21.11 |
Annual Sum or Average | 2564.67 | 21.65 | 1132.33 | 22.07 | 374.00 | 21.98 |
Minimum of Months | 7.67 | 21.11 | 6.00 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 348.00 | 23.66 | 265.67 | 23.94 | 139.33 | 23.94 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 149.83 | 21.11 | 149.83 | 21.11 |
February | 308.00 | 21.23 | 107.67 | 21.20 | 107.67 | 21.18 |
March | 348.00 | 21.40 | 22.50 | 21.38 | 22.50 | 21.37 |
April | 297.33 | 22.01 | 17.17 | 22.09 | 3.33 | 22.08 |
May | 209.33 | 22.89 | 36.67 | 23.05 | 0.00 | 23.05 |
June | 60.00 | 23.37 | 75.17 | 23.71 | 0.00 | 23.71 |
July | 13.33 | 23.65 | 210.50 | 23.93 | 0.00 | 23.93 |
August | 8.67 | 23.63 | 262.33 | 23.92 | 0.17 | 23.93 |
September | 76.17 | 23.05 | 135.83 | 23.62 | 0.00 | 23.62 |
October | 263.67 | 22.00 | 5.33 | 22.04 | 0.00 | 22.04 |
November | 322.83 | 21.25 | 24.33 | 21.24 | 24.33 | 21.23 |
December | 338.00 | 21.11 | 94.50 | 21.11 | 94.50 | 21.11 |
Annual Sum or Average | 2585.33 | 21.65 | 1141.83 | 22.05 | 402.33 | 21.96 |
Minimum of Months | 8.67 | 21.11 | 5.33 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 348.00 | 23.65 | 262.33 | 23.93 | 149.83 | 23.93 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 178.33 | 21.11 | 178.33 | 21.11 |
February | 308.00 | 21.21 | 121.67 | 21.18 | 121.67 | 21.16 |
March | 348.00 | 21.32 | 37.50 | 21.30 | 37.50 | 21.28 |
April | 300.33 | 21.89 | 18.67 | 21.95 | 6.50 | 21.94 |
May | 234.33 | 22.74 | 32.33 | 22.89 | 0.00 | 22.89 |
June | 86.50 | 23.30 | 64.33 | 23.59 | 0.00 | 23.59 |
July | 21.17 | 23.61 | 199.67 | 23.92 | 0.00 | 23.92 |
August | 13.83 | 23.49 | 250.50 | 23.91 | 0.00 | 23.91 |
September | 94.67 | 22.93 | 122.83 | 23.50 | 0.00 | 23.50 |
October | 274.33 | 21.90 | 3.83 | 21.93 | 0.50 | 21.93 |
November | 324.33 | 21.22 | 35.17 | 21.21 | 35.17 | 21.20 |
December | 338.00 | 21.11 | 124.67 | 21.11 | 124.67 | 21.11 |
Annual Sum or Average | 2683.50 | 21.64 | 1189.50 | 21.98 | 504.33 | 21.88 |
Minimum of Months | 13.83 | 21.11 | 3.83 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 348.00 | 23.61 | 250.50 | 23.92 | 178.33 | 23.92 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 311.17 | 21.11 | 311.17 | 21.11 |
February | 308.00 | 21.17 | 182.33 | 21.15 | 182.33 | 21.13 |
March | 348.00 | 21.22 | 100.17 | 21.19 | 100.17 | 21.18 |
April | 304.83 | 21.71 | 35.33 | 21.71 | 28.00 | 21.67 |
May | 260.33 | 22.42 | 24.17 | 22.54 | 1.33 | 22.53 |
June | 136.50 | 23.13 | 55.83 | 23.38 | 0.00 | 23.38 |
July | 46.67 | 23.40 | 179.00 | 23.84 | 0.00 | 23.84 |
August | 26.67 | 23.31 | 226.83 | 23.87 | 0.17 | 23.87 |
September | 140.17 | 22.70 | 105.33 | 23.23 | 0.00 | 23.23 |
October | 293.50 | 21.76 | 9.00 | 21.74 | 9.00 | 21.72 |
November | 325.33 | 21.17 | 135.00 | 21.15 | 135.00 | 21.14 |
December | 338.00 | 21.11 | 259.00 | 21.11 | 259.00 | 21.11 |
Annual Sum or Average | 2868.00 | 21.62 | 1623.17 | 21.81 | 1026.17 | 21.68 |
Minimum of Months | 26.67 | 21.11 | 9.00 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 348.00 | 23.40 | 311.17 | 23.87 | 311.17 | 23.87 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 20.97950 | 30.57231 | -0.5285 | 11.21560 |
February | 448.00000 | 21.08880 | 32.30809 | -0.4553 | 10.08511 |
March | 497.00000 | 21.23675 | 33.52071 | -0.3634 | 8.30819 |
April | 479.00000 | 21.99968 | 36.73974 | -0.1276 | 6.95705 |
May | 496.00000 | 22.97235 | 39.80013 | -0.8274 | 21.57034 |
June | 481.00000 | 23.65903 | 40.58809 | -0.5653 | 12.41987 |
July | 495.00000 | 23.86197 | 44.11697 | -0.4296 | 9.16982 |
August | 497.00000 | 23.87525 | 47.14538 | -0.4010 | 8.64462 |
September | 479.00000 | 23.55993 | 46.37317 | -0.5559 | 12.61654 |
October | 496.00000 | 22.23987 | 40.76754 | -0.0342 | 6.60964 |
November | 480.00000 | 21.26772 | 39.18835 | -0.3400 | 8.39348 |
December | 496.00000 | 21.00058 | 32.79028 | -0.4907 | 10.32015 |
Annual Sum or Average | 5840.00000 | 22.31833 | 38.68780 | -0.4267 | 10.53430 |
Minimum of Months | 448.00000 | 20.97950 | 30.57231 | -0.8274 | 6.60964 |
Maximum of Months | 497.00000 | 23.87525 | 47.14538 | -0.0342 | 21.57034 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.45419 | 32.77163 | -0.3711 | 8.30532 |
February | 448.00000 | 21.76449 | 33.62069 | -0.2705 | 7.64413 |
March | 497.00000 | 22.29484 | 33.59366 | -0.1170 | 6.20654 |
April | 479.00000 | 23.07274 | 35.57709 | 0.10906 | 6.28386 |
May | 496.00000 | 23.70098 | 38.18746 | -0.6020 | 13.21563 |
June | 481.00000 | 23.87686 | 39.77799 | -0.4905 | 10.20282 |
July | 495.00000 | 23.89243 | 44.03603 | -0.4197 | 8.87154 |
August | 497.00000 | 23.88902 | 47.08776 | -0.3957 | 8.47733 |
September | 479.00000 | 23.84904 | 45.44087 | -0.4635 | 9.79109 |
October | 496.00000 | 23.27084 | 39.10500 | 0.18888 | 6.47880 |
November | 480.00000 | 22.04469 | 39.95064 | -0.1463 | 6.82283 |
December | 496.00000 | 21.55825 | 34.85973 | -0.3237 | 7.68940 |
Annual Sum or Average | 5840.00000 | 22.89462 | 38.69142 | -0.2755 | 8.33872 |
Minimum of Months | 448.00000 | 21.45419 | 32.77163 | -0.6020 | 6.20654 |
Maximum of Months | 497.00000 | 23.89243 | 47.08776 | 0.18888 | 13.21563 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.11964 | 30.28367 | -0.4678 | 9.69784 |
February | 336.00000 | 21.32025 | 31.49999 | -0.3789 | 8.71142 |
March | 379.00000 | 21.64896 | 32.03854 | -0.2528 | 7.04685 |
April | 360.00000 | 22.58982 | 34.82831 | 0.00817 | 6.43378 |
May | 375.00000 | 23.57419 | 37.99693 | -0.6339 | 14.51174 |
June | 366.00000 | 23.91340 | 39.06979 | -0.4831 | 10.19808 |
July | 369.00000 | 24.00126 | 43.89469 | -0.3856 | 8.43312 |
August | 379.00000 | 24.00379 | 47.17497 | -0.3558 | 7.95631 |
September | 360.00000 | 23.84177 | 45.06637 | -0.4648 | 10.06187 |
October | 371.00000 | 22.82731 | 38.39082 | 0.09744 | 6.34683 |
November | 360.00000 | 21.49384 | 38.10608 | -0.2738 | 7.62117 |
December | 369.00000 | 21.13040 | 32.10609 | -0.4363 | 9.08562 |
Annual Sum or Average | 4395.00000 | 22.63246 | 37.57841 | -0.3359 | 8.84794 |
Minimum of Months | 336.00000 | 21.11964 | 30.28367 | -0.6339 | 6.34683 |
Maximum of Months | 379.00000 | 24.00379 | 47.17497 | 0.09744 | 14.51174 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.11704 | 30.28907 | -0.4818 | 9.98111 |
February | 336.00000 | 21.29084 | 31.57453 | -0.3964 | 8.93214 |
March | 379.00000 | 21.57422 | 32.17973 | -0.2785 | 7.27528 |
April | 360.00000 | 22.48816 | 35.03680 | -0.0212 | 6.50914 |
May | 375.00000 | 23.53297 | 38.10608 | -0.6527 | 15.12364 |
June | 366.00000 | 23.90710 | 39.09351 | -0.4881 | 10.31297 |
July | 369.00000 | 24.00019 | 43.90247 | -0.3870 | 8.45809 |
August | 379.00000 | 24.00329 | 47.18251 | -0.3559 | 7.95892 |
September | 360.00000 | 23.82781 | 45.11759 | -0.4723 | 10.25724 |
October | 371.00000 | 22.72067 | 38.64499 | 0.06823 | 6.38554 |
November | 360.00000 | 21.44314 | 38.24219 | -0.2954 | 7.79194 |
December | 369.00000 | 21.12477 | 32.11359 | -0.4494 | 9.32922 |
Annual Sum or Average | 4395.00000 | 22.59628 | 37.66384 | -0.3511 | 9.03240 |
Minimum of Months | 336.00000 | 21.11704 | 30.28907 | -0.6527 | 6.38554 |
Maximum of Months | 379.00000 | 24.00329 | 47.18251 | 0.06823 | 15.12364 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.11430 | 30.29538 | -0.4964 | 10.28626 |
February | 336.00000 | 21.25588 | 31.66404 | -0.4156 | 9.18991 |
March | 379.00000 | 21.48211 | 32.36009 | -0.3088 | 7.56103 |
April | 360.00000 | 22.33956 | 35.34721 | -0.0622 | 6.61959 |
May | 375.00000 | 23.42313 | 38.38685 | -0.6972 | 16.61954 |
June | 366.00000 | 23.87899 | 39.18725 | -0.5051 | 10.72783 |
July | 369.00000 | 23.99326 | 43.94145 | -0.3953 | 8.60359 |
August | 379.00000 | 23.99681 | 47.22725 | -0.3636 | 8.07993 |
September | 360.00000 | 23.78016 | 45.28125 | -0.4950 | 10.86148 |
October | 371.00000 | 22.56168 | 39.03101 | 0.02604 | 6.45222 |
November | 360.00000 | 21.37752 | 38.42263 | -0.3205 | 7.98634 |
December | 369.00000 | 21.11835 | 32.12287 | -0.4634 | 9.59907 |
Annual Sum or Average | 4395.00000 | 22.53717 | 37.81264 | -0.3750 | 9.39010 |
Minimum of Months | 336.00000 | 21.11430 | 30.29538 | -0.6972 | 6.45222 |
Maximum of Months | 379.00000 | 23.99681 | 47.22725 | 0.02604 | 16.61954 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10724 | 31.83007 | -0.5263 | 10.92001 |
February | 308.00000 | 21.18551 | 33.34007 | -0.4505 | 9.68524 |
March | 348.00000 | 21.26585 | 34.28415 | -0.3635 | 8.12195 |
April | 330.00000 | 21.96156 | 37.52431 | -0.1410 | 6.88726 |
May | 344.00000 | 22.99207 | 40.76413 | -0.8201 | 21.10079 |
June | 336.00000 | 23.68363 | 40.76507 | -0.5618 | 12.21964 |
July | 338.00000 | 23.88060 | 44.92735 | -0.4248 | 9.08417 |
August | 348.00000 | 23.88152 | 47.92764 | -0.3955 | 8.54049 |
September | 330.00000 | 23.51169 | 47.06754 | -0.5716 | 13.13813 |
October | 340.00000 | 22.15818 | 41.38401 | -0.0583 | 6.63285 |
November | 330.00000 | 21.23018 | 40.31856 | -0.3685 | 8.43155 |
December | 338.00000 | 21.10832 | 33.64490 | -0.4915 | 10.15940 |
Annual Sum or Average | 4030.00000 | 22.34045 | 39.52085 | -0.4315 | 10.42411 |
Minimum of Months | 308.00000 | 21.10724 | 31.83007 | -0.8201 | 6.63285 |
Maximum of Months | 348.00000 | 23.88152 | 47.92764 | -0.0583 | 21.10079 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.11035 | 31.70847 | -0.5237 | 10.86345 |
February | 308.00000 | 21.23380 | 33.09800 | -0.4438 | 9.65260 |
March | 348.00000 | 21.41737 | 33.88020 | -0.3418 | 7.94339 |
April | 330.00000 | 22.23313 | 36.81990 | -0.1014 | 6.73190 |
May | 344.00000 | 23.32261 | 39.78121 | -0.7496 | 18.29866 |
June | 336.00000 | 23.81903 | 40.13859 | -0.5430 | 11.51703 |
July | 338.00000 | 23.91976 | 44.91694 | -0.4318 | 9.15831 |
August | 348.00000 | 23.91272 | 48.10117 | -0.4034 | 8.62447 |
September | 330.00000 | 23.70974 | 46.44510 | -0.5341 | 11.76996 |
October | 340.00000 | 22.45139 | 40.50064 | -0.0127 | 6.53857 |
November | 330.00000 | 21.31868 | 39.94291 | -0.3552 | 8.37446 |
December | 338.00000 | 21.11465 | 33.51972 | -0.4894 | 10.11647 |
Annual Sum or Average | 4030.00000 | 22.47394 | 39.11075 | -0.4112 | 9.97614 |
Minimum of Months | 308.00000 | 21.11035 | 31.70847 | -0.7496 | 6.53857 |
Maximum of Months | 348.00000 | 23.91976 | 48.10117 | -0.0127 | 18.29866 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10929 | 31.71095 | -0.5288 | 10.97708 |
February | 308.00000 | 21.22832 | 33.11237 | -0.4502 | 9.76661 |
March | 348.00000 | 21.39873 | 33.91490 | -0.3505 | 8.05614 |
April | 330.00000 | 22.20415 | 36.88191 | -0.1110 | 6.78272 |
May | 344.00000 | 23.29258 | 39.86201 | -0.7625 | 18.76492 |
June | 336.00000 | 23.81059 | 40.17581 | -0.5496 | 11.68492 |
July | 338.00000 | 23.91758 | 44.94092 | -0.4366 | 9.25038 |
August | 348.00000 | 23.91103 | 48.12647 | -0.4076 | 8.69929 |
September | 330.00000 | 23.69864 | 46.49257 | -0.5407 | 11.94427 |
October | 340.00000 | 22.42710 | 40.56397 | -0.0204 | 6.55663 |
November | 330.00000 | 21.31032 | 39.96744 | -0.3616 | 8.46267 |
December | 338.00000 | 21.11371 | 33.52056 | -0.4947 | 10.22673 |
Annual Sum or Average | 4030.00000 | 22.46213 | 39.14563 | -0.4182 | 10.10858 |
Minimum of Months | 308.00000 | 21.10929 | 31.71095 | -0.7625 | 6.55663 |
Maximum of Months | 348.00000 | 23.91758 | 48.12647 | -0.0204 | 18.76492 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10708 | 31.71544 | -0.5479 | 11.41658 |
February | 308.00000 | 21.20525 | 33.17111 | -0.4742 | 10.19721 |
March | 348.00000 | 21.32213 | 34.06181 | -0.3850 | 8.52839 |
April | 330.00000 | 22.07152 | 37.16128 | -0.1530 | 7.02861 |
May | 344.00000 | 23.11725 | 40.30672 | -0.8322 | 21.44165 |
June | 336.00000 | 23.75347 | 40.37407 | -0.5802 | 12.56984 |
July | 338.00000 | 23.90623 | 45.03237 | -0.4504 | 9.54624 |
August | 348.00000 | 23.90205 | 48.20874 | -0.4185 | 8.92164 |
September | 330.00000 | 23.61451 | 46.78787 | -0.5782 | 13.11012 |
October | 340.00000 | 22.28850 | 40.91094 | -0.0619 | 6.67051 |
November | 330.00000 | 21.26836 | 40.08767 | -0.3873 | 8.80873 |
December | 338.00000 | 21.10991 | 33.52537 | -0.5142 | 10.64386 |
Annual Sum or Average | 4030.00000 | 22.39892 | 39.31903 | -0.4490 | 10.75416 |
Minimum of Months | 308.00000 | 21.10708 | 31.71544 | -0.8322 | 6.67051 |
Maximum of Months | 348.00000 | 23.90623 | 48.20874 | -0.0619 | 21.44165 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10541 | 31.54377 | -0.6210 | 13.25504 |
February | 308.00000 | 21.16983 | 33.08285 | -0.5523 | 11.87992 |
March | 348.00000 | 21.22103 | 34.12622 | -0.4719 | 10.05643 |
April | 330.00000 | 21.87997 | 37.43894 | -0.2384 | 7.81131 |
May | 344.00000 | 22.78648 | 40.95713 | -0.9794 | 27.69763 |
June | 336.00000 | 23.59940 | 40.72066 | -0.6551 | 15.12299 |
July | 338.00000 | 23.85679 | 45.11929 | -0.4845 | 10.47297 |
August | 348.00000 | 23.86981 | 48.25044 | -0.4400 | 9.53478 |
September | 330.00000 | 23.39642 | 47.37780 | -0.6742 | 16.59712 |
October | 340.00000 | 22.05096 | 41.34810 | -0.1541 | 7.19700 |
November | 330.00000 | 21.21309 | 40.03355 | -0.4597 | 10.08269 |
December | 338.00000 | 21.10616 | 33.36102 | -0.5853 | 12.32162 |
Annual Sum or Average | 4030.00000 | 22.28090 | 39.48838 | -0.5267 | 12.68645 |
Minimum of Months | 308.00000 | 21.10541 | 31.54377 | -0.9794 | 7.19700 |
Maximum of Months | 348.00000 | 23.86981 | 48.25044 | -0.1541 | 27.69763 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 96970.27 | 27319.98 | 0.17 | 96970.27 | 0.00 | 0.00 | 0.01 | 18-MAR-16:10 | 0.00 | 01-MAR-00:10 | 161.62 | 18-MAR-16:10 | 161.62 | 18-MAR-16:10 | 0.00 | 18-MAR-16:10 | 45.53 | 18-MAR-16:10 | 0.00 | 01-MAR-00:10 |
April | 0.779497E+09 | 0.201989E+09 | 37.92 | 0.745006E+09 | 34491276.67 | 0.00 | 0.82 | 27-APR-16:10 | 0.00 | 01-APR-00:10 | 13255.78 | 27-APR-16:10 | 12694.89 | 27-APR-16:10 | 911.19 | 29-APR-17:10 | 3283.98 | 27-APR-16:10 | 0.00 | 01-APR-00:10 |
May | 0.177811E+10 | 0.448546E+09 | 93.71 | 0.157430E+10 | 0.203807E+09 | 0.00 | 0.75 | 06-MAY-13:00 | 0.00 | 01-MAY-00:10 | 12256.30 | 06-MAY-13:00 | 11066.78 | 15-MAY-17:00 | 2476.80 | 06-MAY-12:50 | 2925.89 | 06-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.327704E+10 | 0.829226E+09 | 184.66 | 0.306161E+10 | 0.215426E+09 | 0.00 | 1.00 | 12-JUN-08:62 | 0.00 | 01-JUN-00:10 | 23747.71 | 12-JUN-08:62 | 19265.88 | 28-JUN-08:62 | 8825.28 | 12-JUN-08:62 | 5060.25 | 12-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.806766E+10 | 0.198569E+10 | 314.28 | 0.693788E+10 | 0.112978E+10 | 0.00 | 1.00 | 08-JUL-08:62 | 0.00 | 01-JUL-00:10 | 35521.20 | 31-JUL-08:62 | 29685.47 | 24-JUL-08:61 | 9197.63 | 25-JUL-08:62 | 7554.87 | 31-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.105353E+11 | 0.258056E+10 | 344.86 | 0.907739E+10 | 0.145790E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 35655.04 | 29-AUG-08:62 | 32627.03 | 09-AUG-08:62 | 14720.35 | 30-AUG-08:62 | 7564.53 | 10-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.338027E+10 | 0.827720E+09 | 154.20 | 0.275327E+10 | 0.627002E+09 | 0.00 | 1.00 | 11-SEP-08:62 | 0.00 | 01-SEP-00:10 | 31643.46 | 14-SEP-08:62 | 20264.49 | 14-SEP-08:62 | 11378.96 | 14-SEP-08:62 | 6739.05 | 14-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.193742E+09 | 50150916.06 | 19.15 | 0.189934E+09 | 3808604.48 | 0.00 | 0.52 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 7321.94 | 04-OCT-15:00 | 7321.94 | 04-OCT-15:00 | 568.56 | 08-OCT-14:00 | 1819.14 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 32318846.39 | 8745398.89 | 4.00 | 24106228.82 | 8212617.57 | 0.00 | 0.24 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 3387.90 | 04-NOV-14:00 | 2564.64 | 04-NOV-14:00 | 823.26 | 04-NOV-14:00 | 903.63 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.280440E+11 | 0.693266E+10 | 1152.94 | 0.243636E+11 | 0.368043E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.105353E+11 | 0.258056E+10 | 344.86 | 0.907739E+10 | 0.145790E+10 | 0.00 | 1.00 | 0.00 | 35655.04 | 32627.03 | 14720.35 | 7564.53 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 1337707.27 | 320549.34 | 1.42 | 1265340.40 | 72366.87 | 0.00 | 0.19 | 27-FEB-21:10 | 0.00 | 01-FEB-00:10 | 1446.85 | 27-FEB-21:10 | 1376.11 | 27-FEB-21:10 | 70.74 | 27-FEB-21:10 | 341.71 | 27-FEB-21:10 | 0.00 | 01-FEB-00:10 |
March | 6766749.09 | 1624532.20 | 5.67 | 6565911.19 | 200837.91 | 0.00 | 0.18 | 18-MAR-21:30 | 0.00 | 01-MAR-00:10 | 1338.58 | 18-MAR-21:30 | 1338.58 | 18-MAR-21:30 | 198.88 | 09-MAR-21:20 | 314.95 | 18-MAR-21:30 | 0.00 | 01-MAR-00:10 |
April | 0.551041E+09 | 0.121648E+09 | 42.21 | 0.536808E+09 | 14232993.16 | 0.00 | 1.00 | 01-APR-18:31 | 0.00 | 01-APR-00:10 | 17783.22 | 29-APR-18:01 | 17293.02 | 01-APR-18:39 | 3425.07 | 29-APR-18:01 | 3546.63 | 01-APR-18:39 | 0.00 | 01-APR-00:10 |
May | 0.112610E+10 | 0.243279E+09 | 91.11 | 0.102754E+10 | 98560568.80 | 0.00 | 1.00 | 04-MAY-20:01 | 0.00 | 01-MAY-00:10 | 18470.41 | 07-MAY-17:02 | 17347.01 | 14-MAY-18:00 | 5685.10 | 06-MAY-18:57 | 3645.95 | 07-MAY-17:02 | 0.00 | 01-MAY-00:10 |
June | 0.196768E+10 | 0.426263E+09 | 163.22 | 0.188483E+10 | 82842438.58 | 0.00 | 1.00 | 02-JUN-20:04 | 0.00 | 01-JUN-00:10 | 18206.87 | 11-JUN-18:00 | 17592.12 | 25-JUN-17:47 | 6335.19 | 12-JUN-08:62 | 3622.61 | 10-JUN-18:07 | 0.00 | 01-JUN-00:10 |
July | 0.459153E+10 | 0.974906E+09 | 264.75 | 0.408578E+10 | 0.505751E+09 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-00:10 | 18918.98 | 15-JUL-18:02 | 17345.98 | 23-JUL-19:17 | 7039.99 | 11-JUL-08:62 | 3758.49 | 15-JUL-18:02 | 0.00 | 01-JUL-00:10 |
August | 0.617965E+10 | 0.130627E+10 | 297.25 | 0.550455E+10 | 0.675096E+09 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 18797.27 | 26-AUG-18:02 | 17745.42 | 08-AUG-22:00 | 7323.78 | 30-AUG-08:62 | 3790.00 | 24-AUG-20:52 | 0.00 | 01-AUG-00:10 |
September | 0.186224E+10 | 0.393233E+09 | 134.26 | 0.158269E+10 | 0.279553E+09 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-00:10 | 18648.32 | 23-SEP-18:02 | 17367.35 | 10-SEP-17:01 | 6824.65 | 23-SEP-08:62 | 3652.73 | 23-SEP-18:02 | 0.00 | 01-SEP-00:10 |
October | 0.116531E+09 | 26335487.26 | 24.41 | 0.114575E+09 | 1956123.49 | 0.00 | 1.00 | 04-OCT-20:01 | 0.00 | 01-OCT-00:10 | 17112.36 | 04-OCT-20:01 | 17112.36 | 04-OCT-20:01 | 417.10 | 04-OCT-08:62 | 3342.89 | 04-OCT-20:01 | 0.00 | 01-OCT-00:10 |
November | 32241094.12 | 7467111.56 | 6.33 | 25577445.00 | 6663649.12 | 0.00 | 0.34 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 2823.54 | 04-NOV-14:00 | 2256.98 | 04-NOV-14:00 | 566.56 | 04-NOV-14:00 | 639.13 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 147431.66 | 36020.10 | 0.17 | 147431.66 | 0.00 | 0.00 | 0.03 | 03-DEC-20:20 | 0.00 | 01-DEC-00:03 | 245.72 | 03-DEC-20:20 | 245.72 | 03-DEC-20:20 | 0.00 | 01-DEC-00:03 | 60.03 | 03-DEC-20:20 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.164353E+11 | 0.350139E+10 | 1030.78 | 0.147703E+11 | 0.166493E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.617965E+10 | 0.130627E+10 | 297.25 | 0.550455E+10 | 0.675096E+09 | 0.00 | 1.00 | 0.00 | 18918.98 | 17745.42 | 7323.78 | 3790.00 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 27.15 | 6.72 | 0.33 | 27.15 | 0.00 | 0.00 | 0.00 | 27-FEB-13:20 | 0.00 | 01-FEB-00:10 | 0.03 | 27-FEB-13:20 | 0.03 | 27-FEB-13:20 | 0.00 | 27-FEB-16:50 | 0.01 | 27-FEB-13:20 | 0.00 | 01-FEB-00:10 |
March | 41633.12 | 10235.65 | 0.67 | 41633.12 | -0.0 | 0.00 | 0.01 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 | 69.30 | 18-MAR-16:00 | 69.30 | 18-MAR-16:00 | 0.00 | 14-MAR-15:40 | 17.04 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 |
April | 0.406576E+09 | 90756598.88 | 29.57 | 0.398068E+09 | 8508085.19 | 0.00 | 0.86 | 28-APR-07:03 | 0.00 | 01-APR-00:10 | 7676.07 | 28-APR-07:03 | 7342.80 | 27-APR-16:10 | 2187.97 | 28-APR-07:03 | 1620.85 | 27-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.827107E+09 | 0.181648E+09 | 78.87 | 0.759466E+09 | 67640445.79 | 0.00 | 1.00 | 05-MAY-07:03 | 0.00 | 01-MAY-00:10 | 18122.04 | 07-MAY-08:62 | 13051.87 | 07-MAY-08:62 | 5070.17 | 07-MAY-08:62 | 3560.27 | 07-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.143186E+10 | 0.315281E+09 | 142.03 | 0.138561E+10 | 46243875.55 | 0.00 | 1.00 | 03-JUN-07:03 | 0.00 | 01-JUN-00:10 | 17907.96 | 12-JUN-07:02 | 14825.40 | 10-JUN-07:02 | 5605.51 | 12-JUN-07:02 | 3518.69 | 12-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.336366E+10 | 0.724441E+09 | 225.89 | 0.303115E+10 | 0.332510E+09 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:10 | 18459.59 | 31-JUL-07:01 | 14987.70 | 20-JUL-07:02 | 6661.52 | 11-JUL-07:02 | 3620.72 | 31-JUL-07:01 | 0.00 | 01-JUL-00:10 |
August | 0.460041E+10 | 0.984056E+09 | 255.67 | 0.413498E+10 | 0.465436E+09 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 18553.65 | 30-AUG-07:02 | 15224.61 | 09-AUG-07:01 | 7706.37 | 30-AUG-07:02 | 3636.40 | 30-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.145795E+10 | 0.310772E+09 | 116.81 | 0.124450E+10 | 0.213448E+09 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:10 | 17930.15 | 01-SEP-07:02 | 13071.66 | 11-SEP-07:02 | 6986.46 | 24-SEP-08:62 | 3523.11 | 01-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 77582926.46 | 17439298.12 | 15.50 | 76811438.32 | 771488.14 | 0.00 | 0.50 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 3998.88 | 04-OCT-15:00 | 3998.88 | 04-OCT-15:00 | 1148.28 | 01-OCT-08:63 | 872.54 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 21528381.83 | 5014087.69 | 3.92 | 16940096.76 | 4588285.08 | 0.00 | 0.29 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 2350.93 | 04-NOV-14:00 | 1876.59 | 04-NOV-14:00 | 474.34 | 04-NOV-14:00 | 539.81 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.121867E+11 | 0.262942E+10 | 869.25 | 0.110476E+11 | 0.113915E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.460041E+10 | 0.984056E+09 | 255.67 | 0.413498E+10 | 0.465436E+09 | 0.00 | 1.00 | 0.00 | 18553.65 | 15224.61 | 7706.37 | 3636.40 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 18.37 | 4.55 | 0.33 | 18.37 | 0.00 | 0.00 | 0.00 | 27-FEB-17:00 | 0.00 | 01-FEB-00:10 | 0.02 | 27-FEB-17:00 | 0.02 | 27-FEB-17:00 | 0.00 | 27-FEB-17:00 | 0.01 | 27-FEB-17:00 | 0.00 | 01-FEB-00:10 |
March | 20.26 | 5.01 | 0.17 | 20.26 | 0.00 | 0.00 | 0.00 | 14-MAR-16:10 | 0.00 | 01-MAR-00:10 | 0.03 | 14-MAR-16:10 | 0.03 | 14-MAR-16:10 | 0.00 | 14-MAR-16:10 | 0.01 | 14-MAR-16:10 | 0.00 | 01-MAR-00:10 |
April | 0.392551E+09 | 87973199.28 | 29.65 | 0.384474E+09 | 8077291.76 | 0.00 | 0.79 | 27-APR-15:00 | 0.00 | 01-APR-00:10 | 7328.91 | 27-APR-15:00 | 7226.08 | 27-APR-16:10 | 1859.54 | 28-APR-07:03 | 1599.52 | 27-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.805418E+09 | 0.177198E+09 | 77.62 | 0.739929E+09 | 65489456.10 | 0.00 | 1.00 | 05-MAY-07:03 | 0.00 | 01-MAY-00:10 | 18171.80 | 07-MAY-08:62 | 13083.06 | 07-MAY-08:62 | 5088.74 | 07-MAY-08:62 | 3570.05 | 07-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.140990E+10 | 0.310746E+09 | 140.96 | 0.136491E+10 | 44982596.26 | 0.00 | 1.00 | 03-JUN-07:03 | 0.00 | 01-JUN-00:10 | 17958.02 | 12-JUN-07:02 | 14862.64 | 10-JUN-07:02 | 5620.83 | 12-JUN-07:02 | 3528.52 | 12-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.335055E+10 | 0.721951E+09 | 224.88 | 0.302009E+10 | 0.330462E+09 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:10 | 18513.75 | 31-JUL-07:01 | 15028.01 | 20-JUL-07:02 | 6680.93 | 11-JUL-07:02 | 3631.27 | 31-JUL-07:01 | 0.00 | 01-JUL-00:10 |
August | 0.459937E+10 | 0.984050E+09 | 254.76 | 0.413529E+10 | 0.464083E+09 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 18606.95 | 30-AUG-07:02 | 15279.16 | 09-AUG-07:01 | 7852.13 | 30-AUG-07:03 | 3646.80 | 30-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.144222E+10 | 0.307687E+09 | 115.63 | 0.123186E+10 | 0.210357E+09 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:10 | 17980.27 | 01-SEP-07:02 | 13112.20 | 11-SEP-07:02 | 6831.52 | 24-SEP-08:62 | 3532.96 | 01-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 73139931.76 | 16454569.72 | 14.50 | 72554882.28 | 585049.48 | 0.00 | 0.49 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 3921.50 | 04-OCT-15:00 | 3921.50 | 04-OCT-15:00 | 619.16 | 01-OCT-08:63 | 858.01 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 17592269.78 | 4130281.24 | 3.75 | 13867318.90 | 3724950.88 | 0.00 | 0.25 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 2041.19 | 04-NOV-14:00 | 1629.08 | 04-NOV-14:00 | 412.10 | 04-NOV-14:00 | 473.27 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.120907E+11 | 0.261019E+10 | 862.25 | 0.109630E+11 | 0.112776E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.459937E+10 | 0.984050E+09 | 254.76 | 0.413529E+10 | 0.464083E+09 | 0.00 | 1.00 | 0.00 | 18606.95 | 15279.16 | 7852.13 | 3646.80 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 97.70 | 24.15 | 0.50 | 97.70 | -0.0 | 0.00 | 0.00 | 18-MAR-13:30 | 0.00 | 01-MAR-00:10 | 0.06 | 18-MAR-13:30 | 0.06 | 18-MAR-13:30 | 0.00 | 01-MAR-00:10 | 0.01 | 18-MAR-13:30 | 0.00 | 01-MAR-00:10 |
April | 0.367860E+09 | 82956522.73 | 29.15 | 0.360455E+09 | 7404893.28 | 0.00 | 0.78 | 27-APR-16:10 | 0.00 | 01-APR-00:10 | 7084.56 | 27-APR-16:10 | 6992.98 | 27-APR-16:10 | 804.65 | 28-APR-07:03 | 1554.49 | 27-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.753043E+09 | 0.166296E+09 | 74.82 | 0.692212E+09 | 60831605.34 | 0.00 | 1.00 | 05-MAY-07:03 | 0.00 | 01-MAY-00:10 | 18103.34 | 07-MAY-08:62 | 13004.88 | 07-MAY-08:62 | 5098.46 | 07-MAY-08:62 | 3556.64 | 07-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.134252E+10 | 0.296588E+09 | 132.78 | 0.130034E+10 | 42176821.04 | 0.00 | 1.00 | 10-JUN-07:02 | 0.00 | 01-JUN-00:10 | 17890.37 | 12-JUN-07:02 | 14777.84 | 10-JUN-07:02 | 5624.63 | 12-JUN-07:02 | 3515.22 | 12-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.325077E+10 | 0.701943E+09 | 220.35 | 0.292994E+10 | 0.320831E+09 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:10 | 18445.67 | 31-JUL-07:01 | 14946.82 | 20-JUL-07:02 | 6681.75 | 11-JUL-07:02 | 3618.01 | 31-JUL-07:01 | 0.00 | 01-JUL-00:10 |
August | 0.447908E+10 | 0.960008E+09 | 250.07 | 0.402893E+10 | 0.450148E+09 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 18537.54 | 30-AUG-07:02 | 15198.98 | 09-AUG-07:01 | 7720.24 | 30-AUG-07:02 | 3633.34 | 30-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.138573E+10 | 0.296248E+09 | 112.82 | 0.118406E+10 | 0.201669E+09 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:10 | 17912.86 | 01-SEP-07:02 | 13041.16 | 11-SEP-07:02 | 6628.72 | 14-SEP-07:02 | 3519.70 | 01-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 66013474.66 | 14869688.95 | 12.50 | 65675884.81 | 337589.84 | 0.00 | 0.47 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 3760.72 | 04-OCT-15:00 | 3760.72 | 04-OCT-15:00 | 141.56 | 08-OCT-14:00 | 826.60 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 12798923.20 | 3035380.93 | 3.33 | 10103132.42 | 2695790.78 | 0.00 | 0.21 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 1645.36 | 04-NOV-14:00 | 1311.14 | 04-NOV-14:00 | 334.22 | 04-NOV-14:00 | 386.15 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.116578E+11 | 0.252194E+10 | 836.34 | 0.105717E+11 | 0.108609E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.447908E+10 | 0.960008E+09 | 250.07 | 0.402893E+10 | 0.450148E+09 | 0.00 | 1.00 | 0.00 | 18537.54 | 15198.98 | 7720.24 | 3633.34 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 216840.39 | 61032.05 | 0.33 | 216840.39 | 0.00 | 0.00 | 0.02 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 | 246.40 | 18-MAR-16:00 | 246.40 | 18-MAR-16:00 | 0.00 | 18-MAR-15:50 | 69.29 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 |
April | 0.614455E+09 | 0.159654E+09 | 28.25 | 0.582239E+09 | 32216259.44 | 0.00 | 0.81 | 27-APR-15:00 | 0.00 | 01-APR-00:10 | 12816.91 | 27-APR-15:00 | 11894.66 | 27-APR-15:00 | 1065.43 | 29-APR-14:40 | 3186.66 | 27-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.132606E+10 | 0.336457E+09 | 70.00 | 0.117288E+10 | 0.153176E+09 | 0.00 | 1.00 | 07-MAY-09:02 | 0.00 | 01-MAY-00:10 | 18060.12 | 07-MAY-09:02 | 12115.14 | 07-MAY-09:02 | 5944.98 | 07-MAY-09:02 | 3850.40 | 07-MAY-09:02 | 0.00 | 01-MAY-00:10 |
June | 0.256971E+10 | 0.653529E+09 | 145.92 | 0.240144E+10 | 0.168270E+09 | 0.00 | 1.00 | 10-JUN-08:62 | 0.00 | 01-JUN-00:10 | 29337.46 | 12-JUN-08:62 | 22859.31 | 28-JUN-08:62 | 10311.18 | 12-JUN-08:62 | 6248.69 | 12-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.621235E+10 | 0.153436E+10 | 239.52 | 0.532507E+10 | 0.887286E+09 | 0.00 | 1.00 | 07-JUL-08:62 | 0.00 | 01-JUL-00:10 | 34709.35 | 31-JUL-08:62 | 29481.54 | 24-JUL-08:61 | 10763.70 | 25-JUL-08:62 | 7381.64 | 31-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.839383E+10 | 0.205872E+10 | 264.29 | 0.719375E+10 | 0.120009E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 34785.00 | 30-AUG-08:62 | 31767.73 | 09-AUG-08:62 | 14340.32 | 30-AUG-08:62 | 7387.57 | 10-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.274830E+10 | 0.670631E+09 | 119.58 | 0.222424E+10 | 0.524051E+09 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-00:10 | 33679.17 | 14-SEP-08:62 | 24601.53 | 10-SEP-09:02 | 12137.41 | 14-SEP-08:62 | 7171.49 | 14-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.163874E+09 | 42457875.11 | 16.33 | 0.160722E+09 | 3152512.37 | 0.00 | 0.53 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 7314.05 | 04-OCT-15:00 | 7314.05 | 04-OCT-15:00 | 498.01 | 08-OCT-14:10 | 1812.05 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 29885288.12 | 8040855.17 | 3.33 | 22177697.80 | 7707590.32 | 0.00 | 0.26 | 04-NOV-14:40 | 0.00 | 01-NOV-00:10 | 3507.95 | 04-NOV-14:40 | 2645.48 | 04-NOV-14:40 | 862.47 | 04-NOV-14:40 | 932.23 | 04-NOV-14:40 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.220587E+11 | 0.546391E+10 | 887.56 | 0.190827E+11 | 0.297595E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.839383E+10 | 0.205872E+10 | 264.29 | 0.719375E+10 | 0.120009E+10 | 0.00 | 1.00 | 0.00 | 34785.00 | 31767.73 | 14340.32 | 7387.57 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.98 | 0.24 | 0.17 | 0.98 | 0.00 | 0.00 | 0.00 | 27-FEB-14:30 | 0.00 | 01-FEB-00:10 | 0.00 | 27-FEB-14:30 | 0.00 | 27-FEB-14:30 | 0.00 | 01-FEB-00:10 | 0.00 | 27-FEB-14:30 | 0.00 | 01-FEB-00:10 |
March | 10.43 | 2.58 | 0.17 | 10.43 | 0.00 | 0.00 | 0.00 | 18-MAR-13:30 | 0.00 | 01-MAR-00:10 | 0.02 | 18-MAR-13:30 | 0.02 | 18-MAR-13:30 | 0.00 | 01-MAR-00:10 | 0.00 | 18-MAR-13:30 | 0.00 | 01-MAR-00:10 |
April | 0.348945E+09 | 78762637.44 | 26.69 | 0.339823E+09 | 9122302.01 | 0.00 | 0.81 | 27-APR-15:00 | 0.00 | 01-APR-00:10 | 7252.67 | 27-APR-15:00 | 6953.07 | 27-APR-15:00 | 350.83 | 29-APR-14:30 | 1571.19 | 27-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.692597E+09 | 0.152898E+09 | 65.93 | 0.635385E+09 | 57212905.01 | 0.00 | 1.00 | 06-MAY-08:62 | 0.00 | 01-MAY-00:10 | 15835.99 | 07-MAY-09:02 | 10954.80 | 07-MAY-09:02 | 4881.19 | 07-MAY-09:02 | 3092.61 | 07-MAY-09:02 | 0.00 | 01-MAY-00:10 |
June | 0.128974E+10 | 0.285557E+09 | 126.91 | 0.124911E+10 | 40631139.17 | 0.00 | 1.00 | 10-JUN-08:62 | 0.00 | 01-JUN-00:10 | 17287.13 | 12-JUN-08:62 | 14798.95 | 28-JUN-08:62 | 5918.98 | 12-JUN-08:62 | 3396.81 | 12-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.317124E+10 | 0.684425E+09 | 212.45 | 0.284128E+10 | 0.329955E+09 | 0.00 | 1.00 | 06-JUL-08:62 | 0.00 | 01-JUL-00:10 | 17967.27 | 31-JUL-08:62 | 15362.05 | 24-JUL-08:61 | 6541.20 | 11-JUL-08:62 | 3524.78 | 31-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.443530E+10 | 0.950334E+09 | 242.74 | 0.396106E+10 | 0.474244E+09 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 18010.17 | 30-AUG-08:62 | 16509.48 | 09-AUG-08:62 | 7343.68 | 30-AUG-08:62 | 3528.38 | 10-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.132898E+10 | 0.283582E+09 | 103.00 | 0.113245E+10 | 0.196527E+09 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-00:10 | 17446.45 | 14-SEP-08:62 | 13102.02 | 04-SEP-09:02 | 6241.99 | 14-SEP-08:62 | 3427.51 | 14-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 64370739.68 | 14482392.46 | 11.26 | 63975248.02 | 395491.66 | 0.00 | 0.51 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 3955.35 | 04-OCT-15:00 | 3955.35 | 04-OCT-15:00 | 125.04 | 08-OCT-14:10 | 860.20 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 13133366.09 | 3099945.20 | 3.00 | 10330048.95 | 2803317.14 | 0.00 | 0.23 | 04-NOV-14:50 | 0.00 | 01-NOV-00:10 | 1753.11 | 04-NOV-14:50 | 1397.03 | 04-NOV-14:50 | 356.44 | 04-NOV-14:40 | 409.19 | 04-NOV-14:50 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.113443E+11 | 0.245314E+10 | 792.33 | 0.102334E+11 | 0.111089E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.443530E+10 | 0.950334E+09 | 242.74 | 0.396106E+10 | 0.474244E+09 | 0.00 | 1.00 | 0.00 | 18010.17 | 16509.48 | 7343.68 | 3528.38 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 3.65 | 0.90 | 0.17 | 3.65 | -0.0 | 0.00 | 0.00 | 27-FEB-14:30 | 0.00 | 01-FEB-00:10 | 0.01 | 27-FEB-14:30 | 0.01 | 27-FEB-14:30 | 0.00 | 01-FEB-00:10 | 0.00 | 27-FEB-14:30 | 0.00 | 01-FEB-00:10 |
March | 64.63 | 15.98 | 0.17 | 64.63 | 0.00 | 0.00 | 0.00 | 18-MAR-13:30 | 0.00 | 01-MAR-00:10 | 0.11 | 18-MAR-13:30 | 0.11 | 18-MAR-13:30 | 0.00 | 01-MAR-00:10 | 0.03 | 18-MAR-13:30 | 0.00 | 01-MAR-00:10 |
April | 0.341917E+09 | 77291897.31 | 26.31 | 0.332978E+09 | 8938859.21 | 0.00 | 0.80 | 27-APR-15:00 | 0.00 | 01-APR-00:10 | 7164.63 | 27-APR-15:00 | 6867.57 | 27-APR-15:00 | 344.78 | 29-APR-14:30 | 1554.57 | 27-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.674830E+09 | 0.149174E+09 | 65.26 | 0.619170E+09 | 55660636.81 | 0.00 | 1.00 | 07-MAY-09:02 | 0.00 | 01-MAY-00:10 | 14472.34 | 07-MAY-09:02 | 10023.75 | 07-MAY-09:02 | 4448.59 | 07-MAY-09:02 | 2808.35 | 07-MAY-09:02 | 0.00 | 01-MAY-00:10 |
June | 0.126184E+10 | 0.279681E+09 | 125.62 | 0.122252E+10 | 39311115.73 | 0.00 | 1.00 | 10-JUN-08:62 | 0.00 | 01-JUN-00:10 | 17210.31 | 12-JUN-08:62 | 14719.25 | 28-JUN-08:62 | 5905.84 | 12-JUN-08:62 | 3381.71 | 12-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.312264E+10 | 0.674525E+09 | 211.14 | 0.279775E+10 | 0.324889E+09 | 0.00 | 1.00 | 06-JUL-08:62 | 0.00 | 01-JUL-00:10 | 17887.91 | 31-JUL-08:62 | 15280.53 | 24-JUL-08:61 | 6524.57 | 11-JUL-08:62 | 3509.29 | 31-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.438027E+10 | 0.939147E+09 | 241.52 | 0.391215E+10 | 0.468122E+09 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 17931.06 | 30-AUG-08:62 | 16423.39 | 09-AUG-08:62 | 7323.94 | 30-AUG-08:62 | 3512.95 | 10-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.130622E+10 | 0.278970E+09 | 102.91 | 0.111316E+10 | 0.193061E+09 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-00:10 | 17369.27 | 14-SEP-08:62 | 12809.24 | 11-SEP-08:62 | 6225.83 | 14-SEP-08:62 | 3412.36 | 14-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 61962724.52 | 13951793.86 | 10.85 | 61603604.58 | 359119.94 | 0.00 | 0.50 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 3885.98 | 04-OCT-15:00 | 3885.98 | 04-OCT-15:00 | 118.26 | 08-OCT-14:10 | 846.53 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 12390727.59 | 2928988.83 | 3.00 | 9748182.72 | 2642544.88 | 0.00 | 0.22 | 04-NOV-14:40 | 0.00 | 01-NOV-00:10 | 1692.07 | 04-NOV-14:40 | 1347.50 | 04-NOV-14:40 | 344.57 | 04-NOV-14:40 | 395.63 | 04-NOV-14:40 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.111621E+11 | 0.241567E+10 | 786.94 | 0.100691E+11 | 0.109298E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.438027E+10 | 0.939147E+09 | 241.52 | 0.391215E+10 | 0.468122E+09 | 0.00 | 1.00 | 0.00 | 17931.06 | 16423.39 | 7323.94 | 3512.95 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 3539.00 | 876.22 | 0.33 | 3539.00 | 0.00 | 0.00 | 0.00 | 27-FEB-14:50 | 0.00 | 01-FEB-00:10 | 5.83 | 27-FEB-14:50 | 5.83 | 27-FEB-14:50 | 0.00 | 27-FEB-14:50 | 1.44 | 27-FEB-14:50 | 0.00 | 01-FEB-00:10 |
March | 181.97 | 44.99 | 0.33 | 181.97 | -0.0 | 0.00 | 0.00 | 18-MAR-13:40 | 0.00 | 01-MAR-00:10 | 0.25 | 18-MAR-13:40 | 0.25 | 18-MAR-13:40 | 0.00 | 01-MAR-00:10 | 0.06 | 18-MAR-13:40 | 0.00 | 01-MAR-00:10 |
April | 0.316328E+09 | 71998036.28 | 24.92 | 0.308162E+09 | 8165621.44 | 0.00 | 0.78 | 27-APR-15:00 | 0.00 | 01-APR-00:10 | 6877.58 | 27-APR-15:00 | 6590.21 | 27-APR-15:00 | 319.92 | 29-APR-14:40 | 1502.69 | 27-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.611734E+09 | 0.135938E+09 | 60.29 | 0.561434E+09 | 50299871.81 | 0.00 | 0.96 | 07-MAY-09:02 | 0.00 | 01-MAY-00:10 | 8893.62 | 07-MAY-09:02 | 6232.33 | 07-MAY-09:02 | 2661.28 | 07-MAY-09:02 | 1674.25 | 07-MAY-09:02 | 0.00 | 01-MAY-00:10 |
June | 0.117492E+10 | 0.261357E+09 | 117.67 | 0.114010E+10 | 34819202.00 | 0.00 | 1.00 | 10-JUN-08:62 | 0.00 | 01-JUN-00:10 | 17102.67 | 12-JUN-08:62 | 13970.59 | 28-JUN-08:62 | 5916.73 | 12-JUN-08:62 | 3360.55 | 12-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.298506E+10 | 0.646559E+09 | 203.12 | 0.267678E+10 | 0.308276E+09 | 0.00 | 1.00 | 07-JUL-08:62 | 0.00 | 01-JUL-00:10 | 17779.46 | 31-JUL-08:62 | 15151.80 | 24-JUL-08:61 | 5584.01 | 26-JUL-08:62 | 3488.28 | 31-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.424134E+10 | 0.910825E+09 | 235.84 | 0.379082E+10 | 0.450514E+09 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 17823.38 | 30-AUG-08:62 | 16292.86 | 09-AUG-08:62 | 7317.91 | 30-AUG-08:62 | 3492.27 | 10-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.123630E+10 | 0.264658E+09 | 99.15 | 0.105448E+10 | 0.181821E+09 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-00:10 | 17263.35 | 14-SEP-08:62 | 12661.52 | 10-SEP-09:02 | 6224.16 | 14-SEP-08:62 | 3391.61 | 14-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 53268704.49 | 12036458.97 | 8.71 | 53078680.60 | 190023.89 | 0.00 | 0.47 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 3632.26 | 04-OCT-15:00 | 3632.26 | 04-OCT-15:00 | 82.75 | 08-OCT-14:10 | 797.25 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 9035111.65 | 2152765.07 | 2.67 | 7120946.95 | 1914164.71 | 0.00 | 0.18 | 04-NOV-14:50 | 0.00 | 01-NOV-00:10 | 1379.07 | 04-NOV-14:50 | 1097.64 | 04-NOV-14:50 | 281.65 | 04-NOV-14:40 | 325.69 | 04-NOV-14:50 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.106280E+11 | 0.230553E+10 | 753.03 | 0.959198E+10 | 0.103600E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.424134E+10 | 0.910825E+09 | 235.84 | 0.379082E+10 | 0.450514E+09 | 0.00 | 1.00 | 0.00 | 17823.38 | 16292.86 | 7317.91 | 3492.27 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 499.83 | 123.40 | 1.17 | 499.83 | 0.00 | 0.00 | 0.00 | 18-MAR-14:10 | 0.00 | 01-MAR-00:10 | 0.52 | 18-MAR-14:10 | 0.52 | 18-MAR-14:10 | 0.00 | 18-MAR-14:10 | 0.13 | 18-MAR-14:10 | 0.00 | 01-MAR-00:10 |
April | 0.296268E+09 | 68111489.80 | 24.83 | 0.288832E+09 | 7435244.23 | 0.00 | 0.75 | 27-APR-15:00 | 0.00 | 01-APR-00:10 | 6908.75 | 27-APR-15:00 | 6600.04 | 27-APR-15:00 | 327.66 | 27-APR-17:00 | 1524.99 | 27-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.551403E+09 | 0.123699E+09 | 56.08 | 0.506599E+09 | 44804721.86 | 0.00 | 0.70 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 | 6546.18 | 06-MAY-13:30 | 5501.10 | 06-MAY-13:40 | 1064.94 | 06-MAY-13:10 | 1381.46 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 |
June | 0.110804E+10 | 0.248254E+09 | 106.50 | 0.107610E+10 | 31933568.53 | 0.00 | 0.81 | 28-JUN-08:62 | 0.00 | 01-JUN-00:10 | 7311.75 | 28-JUN-08:62 | 6988.73 | 28-JUN-15:00 | 842.30 | 28-JUN-08:62 | 1520.07 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.292202E+10 | 0.635491E+09 | 191.62 | 0.262568E+10 | 0.296346E+09 | 0.00 | 1.00 | 20-JUL-08:62 | 0.00 | 01-JUL-00:10 | 18815.18 | 31-JUL-08:62 | 15914.48 | 24-JUL-08:61 | 4502.15 | 31-JUL-08:62 | 3691.72 | 31-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.431761E+10 | 0.927267E+09 | 219.30 | 0.386077E+10 | 0.456837E+09 | 0.00 | 1.00 | 08-AUG-08:62 | 0.00 | 01-AUG-00:10 | 18860.87 | 30-AUG-08:62 | 17192.63 | 09-AUG-08:62 | 7922.54 | 30-AUG-08:62 | 3696.74 | 10-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.119154E+10 | 0.256864E+09 | 90.69 | 0.101420E+10 | 0.177336E+09 | 0.00 | 1.00 | 10-SEP-09:02 | 0.00 | 01-SEP-00:10 | 16174.60 | 10-SEP-09:02 | 12083.52 | 10-SEP-09:02 | 4091.08 | 10-SEP-09:02 | 3155.05 | 10-SEP-09:02 | 0.00 | 01-SEP-00:10 |
October | 40327504.11 | 9259881.25 | 6.83 | 40326955.87 | 548.24 | 0.00 | 0.39 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 3109.06 | 04-OCT-15:00 | 3109.06 | 04-OCT-15:00 | 0.60 | 09-OCT-13:00 | 698.25 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 4443922.43 | 1074566.95 | 2.00 | 3508755.09 | 935167.34 | 0.00 | 0.11 | 04-NOV-14:40 | 0.00 | 01-NOV-00:10 | 855.80 | 04-NOV-14:40 | 678.96 | 04-NOV-14:40 | 176.84 | 04-NOV-14:40 | 206.01 | 04-NOV-14:40 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.104316E+11 | 0.227002E+10 | 699.03 | 0.941602E+10 | 0.101563E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.431761E+10 | 0.927267E+09 | 219.30 | 0.386077E+10 | 0.456837E+09 | 0.00 | 1.00 | 0.00 | 18860.87 | 17192.63 | 7922.54 | 3696.74 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 56.05 | 68.74 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 98.09 | 60.17 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 110.78 | 50.75 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 123.47 | 42.85 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 112.94 | 37.36 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 104.35 | 30.31 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 123.99 | 27.63 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 136.83 | 27.00 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 142.96 | 37.67 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 120.42 | 47.51 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 61.08 | 56.56 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 65.08 | 69.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 104.69 | 46.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 56.05 | 27.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 142.96 | 69.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 56.05 | 68.74 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 98.09 | 60.17 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 110.78 | 50.75 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 123.47 | 42.85 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 112.94 | 37.36 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 104.35 | 30.31 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 123.99 | 27.63 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 136.83 | 27.00 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 142.96 | 37.67 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 120.42 | 47.51 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 61.08 | 56.56 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 65.08 | 69.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 104.69 | 46.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 56.05 | 27.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 142.96 | 69.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 56.05 | 68.74 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 98.09 | 60.17 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 110.78 | 50.75 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 123.47 | 42.85 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 112.94 | 37.36 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 104.35 | 30.31 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 123.99 | 27.63 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 136.83 | 27.00 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 142.96 | 37.67 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 120.42 | 47.51 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 61.08 | 56.56 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 65.08 | 69.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 104.69 | 46.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 56.05 | 27.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 142.96 | 69.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 56.05 | 68.74 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 98.09 | 60.17 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 110.78 | 50.75 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 123.47 | 42.85 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 112.94 | 37.36 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 104.35 | 30.31 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 123.99 | 27.63 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 136.83 | 27.00 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 142.96 | 37.67 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 120.42 | 47.51 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 61.08 | 56.56 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 65.08 | 69.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 104.69 | 46.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 56.05 | 27.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 142.96 | 69.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.22 | 43.48 | 29.74 | 67.70 | 81.53 | 0.00 | 0.00 | 0.00 |
February | 112.60 | 69.70 | 42.90 | 118.28 | 71.46 | 0.00 | 0.00 | 0.00 |
March | 121.13 | 64.60 | 56.53 | 133.49 | 60.29 | 0.00 | 0.00 | 0.00 |
April | 127.89 | 55.53 | 72.36 | 148.76 | 50.91 | 0.00 | 0.00 | 0.00 |
May | 116.94 | 34.84 | 82.10 | 136.08 | 44.43 | 0.00 | 0.00 | 0.00 |
June | 106.99 | 28.72 | 78.26 | 125.71 | 36.06 | 0.00 | 0.00 | 0.00 |
July | 116.67 | 42.73 | 73.94 | 149.18 | 32.92 | 0.00 | 0.00 | 0.00 |
August | 125.35 | 58.45 | 66.90 | 164.54 | 32.21 | 0.00 | 0.00 | 0.00 |
September | 138.88 | 76.70 | 62.19 | 171.93 | 44.94 | 0.00 | 0.00 | 0.00 |
October | 125.80 | 77.67 | 48.13 | 145.03 | 56.53 | 0.00 | 0.00 | 0.00 |
November | 74.38 | 42.63 | 31.75 | 73.67 | 67.14 | 0.00 | 0.00 | 0.00 |
December | 77.82 | 50.36 | 27.46 | 78.46 | 83.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 109.76 | 53.68 | 56.07 | 126.09 | 55.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 73.22 | 28.72 | 27.46 | 67.70 | 32.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.88 | 77.67 | 82.10 | 171.93 | 83.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.22 | 43.48 | 29.74 | 67.70 | 81.53 | 0.00 | 0.00 | 0.00 |
February | 112.60 | 69.70 | 42.90 | 118.28 | 71.46 | 0.00 | 0.00 | 0.00 |
March | 121.13 | 64.60 | 56.53 | 133.49 | 60.29 | 0.00 | 0.00 | 0.00 |
April | 127.89 | 55.53 | 72.36 | 148.76 | 50.91 | 0.00 | 0.00 | 0.00 |
May | 116.94 | 34.84 | 82.10 | 136.08 | 44.43 | 0.00 | 0.00 | 0.00 |
June | 106.99 | 28.72 | 78.26 | 125.71 | 36.06 | 0.00 | 0.00 | 0.00 |
July | 116.67 | 42.73 | 73.94 | 149.18 | 32.92 | 0.00 | 0.00 | 0.00 |
August | 125.35 | 58.45 | 66.90 | 164.54 | 32.21 | 0.00 | 0.00 | 0.00 |
September | 138.88 | 76.70 | 62.19 | 171.93 | 44.94 | 0.00 | 0.00 | 0.00 |
October | 125.80 | 77.67 | 48.13 | 145.03 | 56.53 | 0.00 | 0.00 | 0.00 |
November | 74.38 | 42.63 | 31.75 | 73.67 | 67.14 | 0.00 | 0.00 | 0.00 |
December | 77.82 | 50.36 | 27.46 | 78.46 | 83.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 109.76 | 53.68 | 56.07 | 126.09 | 55.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 73.22 | 28.72 | 27.46 | 67.70 | 32.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.88 | 77.67 | 82.10 | 171.93 | 83.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 55.05 | 73.23 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 96.58 | 64.51 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 108.82 | 55.98 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 120.94 | 47.26 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 110.69 | 40.25 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 103.09 | 31.63 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 123.34 | 28.21 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 136.27 | 27.48 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 141.88 | 39.08 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 118.46 | 51.91 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 59.87 | 61.00 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 64.16 | 74.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 103.28 | 49.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 55.05 | 27.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 141.88 | 74.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 55.05 | 73.23 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 96.58 | 64.51 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 108.82 | 55.98 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 120.94 | 47.26 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 110.69 | 40.25 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 103.09 | 31.63 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 123.34 | 28.21 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 136.27 | 27.48 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 141.88 | 39.08 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 118.46 | 51.91 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 59.87 | 61.00 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 64.16 | 74.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 103.28 | 49.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 55.05 | 27.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 141.88 | 74.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.22 | 43.48 | 29.74 | 66.51 | 86.81 | 0.00 | 0.00 | 0.00 |
February | 112.60 | 69.70 | 42.90 | 116.50 | 76.56 | 0.00 | 0.00 | 0.00 |
March | 121.13 | 64.60 | 56.53 | 131.17 | 66.43 | 0.00 | 0.00 | 0.00 |
April | 127.89 | 55.53 | 72.36 | 145.80 | 56.08 | 0.00 | 0.00 | 0.00 |
May | 116.94 | 34.84 | 82.10 | 133.44 | 47.81 | 0.00 | 0.00 | 0.00 |
June | 106.99 | 28.72 | 78.26 | 124.23 | 37.62 | 0.00 | 0.00 | 0.00 |
July | 116.67 | 42.73 | 73.94 | 148.44 | 33.60 | 0.00 | 0.00 | 0.00 |
August | 125.35 | 58.45 | 66.90 | 163.90 | 32.77 | 0.00 | 0.00 | 0.00 |
September | 138.88 | 76.70 | 62.19 | 170.66 | 46.60 | 0.00 | 0.00 | 0.00 |
October | 125.80 | 77.67 | 48.13 | 142.73 | 61.69 | 0.00 | 0.00 | 0.00 |
November | 74.38 | 42.63 | 31.75 | 72.24 | 72.35 | 0.00 | 0.00 | 0.00 |
December | 77.82 | 50.36 | 27.46 | 77.36 | 88.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 109.76 | 53.68 | 56.07 | 124.44 | 58.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 73.22 | 28.72 | 27.46 | 66.51 | 32.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.88 | 77.67 | 82.10 | 170.66 | 88.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 55.23 | 70.86 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 96.91 | 62.44 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 109.20 | 54.13 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 121.30 | 46.28 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 110.71 | 40.52 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 102.94 | 32.53 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 123.09 | 29.56 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 136.06 | 29.01 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 141.82 | 39.96 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 118.73 | 51.12 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 60.18 | 59.06 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 64.38 | 72.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 103.40 | 48.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 55.23 | 29.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 141.82 | 72.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 55.23 | 70.86 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 96.91 | 62.44 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 109.20 | 54.13 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 121.30 | 46.28 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 110.71 | 40.52 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 102.94 | 32.53 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 123.09 | 29.56 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 136.06 | 29.01 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 141.82 | 39.96 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 118.73 | 51.12 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 60.18 | 59.06 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 64.38 | 72.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 103.40 | 48.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 55.23 | 29.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 141.82 | 72.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.82 | 43.24 | 29.58 | 66.36 | 83.56 | 0.00 | 0.00 | 0.00 |
February | 111.99 | 69.32 | 42.67 | 116.26 | 73.72 | 0.00 | 0.00 | 0.00 |
March | 120.46 | 64.24 | 56.22 | 130.91 | 63.91 | 0.00 | 0.00 | 0.00 |
April | 127.19 | 55.22 | 71.96 | 145.42 | 54.63 | 0.00 | 0.00 | 0.00 |
May | 116.30 | 34.65 | 81.65 | 132.73 | 47.86 | 0.00 | 0.00 | 0.00 |
June | 106.40 | 28.57 | 77.83 | 123.37 | 38.45 | 0.00 | 0.00 | 0.00 |
July | 116.03 | 42.50 | 73.54 | 147.33 | 34.98 | 0.00 | 0.00 | 0.00 |
August | 124.66 | 58.13 | 66.53 | 162.76 | 34.37 | 0.00 | 0.00 | 0.00 |
September | 138.12 | 76.28 | 61.85 | 169.66 | 47.37 | 0.00 | 0.00 | 0.00 |
October | 125.12 | 77.25 | 47.87 | 142.27 | 60.42 | 0.00 | 0.00 | 0.00 |
November | 73.97 | 42.39 | 31.58 | 72.22 | 69.69 | 0.00 | 0.00 | 0.00 |
December | 77.40 | 50.09 | 27.31 | 77.20 | 85.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 109.16 | 53.39 | 55.77 | 123.90 | 57.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.82 | 28.57 | 27.31 | 66.36 | 34.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.12 | 77.25 | 81.65 | 169.66 | 85.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 55.37 | 69.81 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 97.14 | 61.52 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 109.48 | 53.15 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 121.66 | 45.44 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 110.91 | 40.12 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 103.00 | 32.38 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 123.11 | 29.52 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 136.06 | 29.02 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 141.89 | 39.77 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 119.00 | 50.26 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 60.39 | 58.08 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 64.51 | 71.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 103.56 | 48.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 55.37 | 29.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 141.89 | 71.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 55.37 | 69.81 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 97.14 | 61.52 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 109.48 | 53.15 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 121.66 | 45.44 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 110.91 | 40.12 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 103.00 | 32.38 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 123.11 | 29.52 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 136.06 | 29.02 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 141.89 | 39.77 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 119.00 | 50.26 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 60.39 | 58.08 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 64.51 | 71.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 103.56 | 48.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 55.37 | 29.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 141.89 | 71.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.82 | 43.24 | 29.58 | 66.53 | 82.32 | 0.00 | 0.00 | 0.00 |
February | 111.99 | 69.32 | 42.67 | 116.54 | 72.63 | 0.00 | 0.00 | 0.00 |
March | 120.46 | 64.24 | 56.22 | 131.25 | 62.75 | 0.00 | 0.00 | 0.00 |
April | 127.19 | 55.22 | 71.96 | 145.85 | 53.64 | 0.00 | 0.00 | 0.00 |
May | 116.30 | 34.65 | 81.65 | 132.97 | 47.38 | 0.00 | 0.00 | 0.00 |
June | 106.40 | 28.57 | 77.83 | 123.45 | 38.27 | 0.00 | 0.00 | 0.00 |
July | 116.03 | 42.50 | 73.54 | 147.35 | 34.94 | 0.00 | 0.00 | 0.00 |
August | 124.66 | 58.13 | 66.53 | 162.76 | 34.38 | 0.00 | 0.00 | 0.00 |
September | 138.12 | 76.28 | 61.85 | 169.74 | 47.13 | 0.00 | 0.00 | 0.00 |
October | 125.12 | 77.25 | 47.87 | 142.60 | 59.42 | 0.00 | 0.00 | 0.00 |
November | 73.97 | 42.39 | 31.58 | 72.47 | 68.53 | 0.00 | 0.00 | 0.00 |
December | 77.40 | 50.09 | 27.31 | 77.36 | 84.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 109.16 | 53.39 | 55.77 | 124.09 | 57.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.82 | 28.57 | 27.31 | 66.53 | 34.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.12 | 77.25 | 81.65 | 169.74 | 84.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 55.52 | 69.01 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 97.39 | 60.81 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 109.81 | 52.27 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 122.15 | 44.53 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 111.35 | 39.45 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 103.22 | 32.01 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 123.23 | 29.25 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 136.16 | 28.76 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 142.09 | 39.32 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 119.40 | 49.26 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 60.64 | 57.25 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 64.65 | 70.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 103.82 | 47.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 55.52 | 28.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 142.09 | 70.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 55.52 | 69.01 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 97.39 | 60.81 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 109.81 | 52.27 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 122.15 | 44.53 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 111.35 | 39.45 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 103.22 | 32.01 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 123.23 | 29.25 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 136.16 | 28.76 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 142.09 | 39.32 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 119.40 | 49.26 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 60.64 | 57.25 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 64.65 | 70.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 103.82 | 47.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 55.52 | 28.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 142.09 | 70.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.82 | 43.24 | 29.58 | 66.72 | 81.37 | 0.00 | 0.00 | 0.00 |
February | 111.99 | 69.32 | 42.67 | 116.83 | 71.79 | 0.00 | 0.00 | 0.00 |
March | 120.46 | 64.24 | 56.22 | 131.64 | 61.71 | 0.00 | 0.00 | 0.00 |
April | 127.19 | 55.22 | 71.96 | 146.43 | 52.58 | 0.00 | 0.00 | 0.00 |
May | 116.30 | 34.65 | 81.65 | 133.49 | 46.60 | 0.00 | 0.00 | 0.00 |
June | 106.40 | 28.57 | 77.83 | 123.71 | 37.83 | 0.00 | 0.00 | 0.00 |
July | 116.03 | 42.50 | 73.54 | 147.50 | 34.61 | 0.00 | 0.00 | 0.00 |
August | 124.66 | 58.13 | 66.53 | 162.88 | 34.07 | 0.00 | 0.00 | 0.00 |
September | 138.12 | 76.28 | 61.85 | 169.98 | 46.61 | 0.00 | 0.00 | 0.00 |
October | 125.12 | 77.25 | 47.87 | 143.07 | 58.24 | 0.00 | 0.00 | 0.00 |
November | 73.97 | 42.39 | 31.58 | 72.76 | 67.55 | 0.00 | 0.00 | 0.00 |
December | 77.40 | 50.09 | 27.31 | 77.54 | 83.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 109.16 | 53.39 | 55.77 | 124.40 | 56.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.82 | 28.57 | 27.31 | 66.72 | 34.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.12 | 77.25 | 81.65 | 169.98 | 83.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 56.20 | 66.90 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 98.29 | 59.08 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 110.76 | 50.46 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 123.41 | 42.70 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 112.64 | 37.84 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 103.96 | 30.96 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 123.63 | 28.41 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 136.48 | 27.88 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 142.77 | 38.18 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 120.43 | 47.30 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 61.32 | 55.39 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 65.22 | 68.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 104.61 | 46.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 56.20 | 27.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 142.77 | 68.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 56.20 | 66.90 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 98.29 | 59.08 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 110.76 | 50.46 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 123.41 | 42.70 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 112.64 | 37.84 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 103.96 | 30.96 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 123.63 | 28.41 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 136.48 | 27.88 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 142.77 | 38.18 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 120.43 | 47.30 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 61.32 | 55.39 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 65.22 | 68.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 104.61 | 46.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 56.20 | 27.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 142.77 | 68.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 56.20 | 66.90 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 98.29 | 59.08 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 110.76 | 50.46 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 123.41 | 42.70 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 112.64 | 37.84 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 103.96 | 30.96 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 123.63 | 28.41 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 136.48 | 27.88 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 142.77 | 38.18 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 120.43 | 47.30 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 61.32 | 55.39 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 65.22 | 68.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 104.61 | 46.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 56.20 | 27.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 142.77 | 68.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 56.20 | 66.90 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 98.29 | 59.08 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 110.76 | 50.46 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 123.41 | 42.70 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 112.64 | 37.84 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 103.96 | 30.96 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 123.63 | 28.41 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 136.48 | 27.88 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 142.77 | 38.18 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 120.43 | 47.30 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 61.32 | 55.39 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 65.22 | 68.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 104.61 | 46.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 56.20 | 27.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 142.77 | 68.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.82 | 43.24 | 29.58 | 67.51 | 78.93 | 0.00 | 0.00 | 0.00 |
February | 111.99 | 69.32 | 42.67 | 117.87 | 69.78 | 0.00 | 0.00 | 0.00 |
March | 120.46 | 64.24 | 56.22 | 132.74 | 59.61 | 0.00 | 0.00 | 0.00 |
April | 127.19 | 55.22 | 71.96 | 147.89 | 50.44 | 0.00 | 0.00 | 0.00 |
May | 116.30 | 34.65 | 81.65 | 134.99 | 44.73 | 0.00 | 0.00 | 0.00 |
June | 106.40 | 28.57 | 77.83 | 124.56 | 36.62 | 0.00 | 0.00 | 0.00 |
July | 116.03 | 42.50 | 73.54 | 147.95 | 33.64 | 0.00 | 0.00 | 0.00 |
August | 124.66 | 58.13 | 66.53 | 163.24 | 33.05 | 0.00 | 0.00 | 0.00 |
September | 138.12 | 76.28 | 61.85 | 170.76 | 45.27 | 0.00 | 0.00 | 0.00 |
October | 125.12 | 77.25 | 47.87 | 144.26 | 55.95 | 0.00 | 0.00 | 0.00 |
November | 73.97 | 42.39 | 31.58 | 73.56 | 65.39 | 0.00 | 0.00 | 0.00 |
December | 77.40 | 50.09 | 27.31 | 78.19 | 80.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 109.16 | 53.39 | 55.77 | 125.31 | 54.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.82 | 28.57 | 27.31 | 67.51 | 33.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.12 | 77.25 | 81.65 | 170.76 | 80.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.82 | 43.24 | 29.58 | 67.51 | 78.93 | 0.00 | 0.00 | 0.00 |
February | 111.99 | 69.32 | 42.67 | 117.87 | 69.78 | 0.00 | 0.00 | 0.00 |
March | 120.46 | 64.24 | 56.22 | 132.74 | 59.61 | 0.00 | 0.00 | 0.00 |
April | 127.19 | 55.22 | 71.96 | 147.89 | 50.44 | 0.00 | 0.00 | 0.00 |
May | 116.30 | 34.65 | 81.65 | 134.99 | 44.73 | 0.00 | 0.00 | 0.00 |
June | 106.40 | 28.57 | 77.83 | 124.56 | 36.62 | 0.00 | 0.00 | 0.00 |
July | 116.03 | 42.50 | 73.54 | 147.95 | 33.64 | 0.00 | 0.00 | 0.00 |
August | 124.66 | 58.13 | 66.53 | 163.24 | 33.05 | 0.00 | 0.00 | 0.00 |
September | 138.12 | 76.28 | 61.85 | 170.76 | 45.27 | 0.00 | 0.00 | 0.00 |
October | 125.12 | 77.25 | 47.87 | 144.26 | 55.95 | 0.00 | 0.00 | 0.00 |
November | 73.97 | 42.39 | 31.58 | 73.56 | 65.39 | 0.00 | 0.00 | 0.00 |
December | 77.40 | 50.09 | 27.31 | 78.19 | 80.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 109.16 | 53.39 | 55.77 | 125.31 | 54.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.82 | 28.57 | 27.31 | 67.51 | 33.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.12 | 77.25 | 81.65 | 170.76 | 80.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 55.94 | 67.39 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 97.93 | 59.43 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 110.29 | 50.89 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 122.74 | 43.17 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 111.87 | 38.35 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 103.51 | 31.11 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 123.38 | 28.35 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 136.27 | 27.78 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 142.31 | 38.42 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 119.81 | 47.93 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 61.03 | 55.84 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 65.00 | 69.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 104.19 | 46.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 55.94 | 27.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 142.31 | 69.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 55.94 | 67.39 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 97.93 | 59.43 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 110.29 | 50.89 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 122.74 | 43.17 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 111.87 | 38.35 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 103.51 | 31.11 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 123.38 | 28.35 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 136.27 | 27.78 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 142.31 | 38.42 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 119.81 | 47.93 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 61.03 | 55.84 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 65.00 | 69.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 104.19 | 46.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 55.94 | 27.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 142.31 | 69.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.82 | 43.24 | 29.58 | 67.22 | 79.47 | 0.00 | 0.00 | 0.00 |
February | 111.99 | 69.32 | 42.67 | 117.48 | 70.17 | 0.00 | 0.00 | 0.00 |
March | 120.46 | 64.24 | 56.22 | 132.23 | 60.09 | 0.00 | 0.00 | 0.00 |
April | 127.19 | 55.22 | 71.96 | 147.14 | 50.98 | 0.00 | 0.00 | 0.00 |
May | 116.30 | 34.65 | 81.65 | 134.12 | 45.31 | 0.00 | 0.00 | 0.00 |
June | 106.40 | 28.57 | 77.83 | 124.06 | 36.78 | 0.00 | 0.00 | 0.00 |
July | 116.03 | 42.50 | 73.54 | 147.70 | 33.56 | 0.00 | 0.00 | 0.00 |
August | 124.66 | 58.13 | 66.53 | 163.02 | 32.92 | 0.00 | 0.00 | 0.00 |
September | 138.12 | 76.28 | 61.85 | 170.25 | 45.54 | 0.00 | 0.00 | 0.00 |
October | 125.12 | 77.25 | 47.87 | 143.57 | 56.67 | 0.00 | 0.00 | 0.00 |
November | 73.97 | 42.39 | 31.58 | 73.24 | 65.89 | 0.00 | 0.00 | 0.00 |
December | 77.40 | 50.09 | 27.31 | 77.96 | 81.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 109.16 | 53.39 | 55.77 | 124.85 | 54.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.82 | 28.57 | 27.31 | 67.22 | 32.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.12 | 77.25 | 81.65 | 170.25 | 81.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 56.00 | 67.12 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 98.03 | 59.16 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 110.41 | 50.61 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 122.88 | 42.94 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 112.01 | 38.15 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 103.61 | 30.97 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 123.47 | 28.23 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 136.34 | 27.66 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 142.39 | 38.28 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 119.91 | 47.72 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 61.11 | 55.57 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 65.07 | 68.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 104.28 | 46.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 56.00 | 27.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 142.39 | 68.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 56.00 | 67.12 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 98.03 | 59.16 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 110.41 | 50.61 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 122.88 | 42.94 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 112.01 | 38.15 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 103.61 | 30.97 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 123.47 | 28.23 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 136.34 | 27.66 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 142.39 | 38.28 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 119.91 | 47.72 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 61.11 | 55.57 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 65.07 | 68.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 104.28 | 46.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 56.00 | 27.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 142.39 | 68.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.82 | 43.24 | 29.58 | 67.29 | 79.14 | 0.00 | 0.00 | 0.00 |
February | 111.99 | 69.32 | 42.67 | 117.61 | 69.84 | 0.00 | 0.00 | 0.00 |
March | 120.46 | 64.24 | 56.22 | 132.37 | 59.75 | 0.00 | 0.00 | 0.00 |
April | 127.19 | 55.22 | 71.96 | 147.31 | 50.70 | 0.00 | 0.00 | 0.00 |
May | 116.30 | 34.65 | 81.65 | 134.29 | 45.08 | 0.00 | 0.00 | 0.00 |
June | 106.40 | 28.57 | 77.83 | 124.18 | 36.62 | 0.00 | 0.00 | 0.00 |
July | 116.03 | 42.50 | 73.54 | 147.80 | 33.41 | 0.00 | 0.00 | 0.00 |
August | 124.66 | 58.13 | 66.53 | 163.10 | 32.78 | 0.00 | 0.00 | 0.00 |
September | 138.12 | 76.28 | 61.85 | 170.34 | 45.38 | 0.00 | 0.00 | 0.00 |
October | 125.12 | 77.25 | 47.87 | 143.68 | 56.42 | 0.00 | 0.00 | 0.00 |
November | 73.97 | 42.39 | 31.58 | 73.33 | 65.57 | 0.00 | 0.00 | 0.00 |
December | 77.40 | 50.09 | 27.31 | 78.04 | 81.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 109.16 | 53.39 | 55.77 | 124.96 | 54.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.82 | 28.57 | 27.31 | 67.29 | 32.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.12 | 77.25 | 81.65 | 170.34 | 81.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 56.23 | 65.89 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 98.41 | 57.98 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 110.89 | 49.34 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 123.48 | 41.79 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 112.74 | 37.08 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 104.04 | 30.34 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 123.73 | 27.77 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 136.54 | 27.28 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 142.75 | 37.56 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 120.38 | 46.55 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 61.42 | 54.43 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 65.30 | 67.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 104.67 | 45.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 56.23 | 27.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 142.75 | 67.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 56.23 | 65.89 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 98.41 | 57.98 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 110.89 | 49.34 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 123.48 | 41.79 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 112.74 | 37.08 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 104.04 | 30.34 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 123.73 | 27.77 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 136.54 | 27.28 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 142.75 | 37.56 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 120.38 | 46.55 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 61.42 | 54.43 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 65.30 | 67.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 104.67 | 45.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 56.23 | 27.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 142.75 | 67.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.82 | 43.24 | 29.58 | 67.58 | 77.69 | 0.00 | 0.00 | 0.00 |
February | 111.99 | 69.32 | 42.67 | 118.07 | 68.45 | 0.00 | 0.00 | 0.00 |
March | 120.46 | 64.24 | 56.22 | 132.94 | 58.26 | 0.00 | 0.00 | 0.00 |
April | 127.19 | 55.22 | 71.96 | 148.02 | 49.35 | 0.00 | 0.00 | 0.00 |
May | 116.30 | 34.65 | 81.65 | 135.16 | 43.82 | 0.00 | 0.00 | 0.00 |
June | 106.40 | 28.57 | 77.83 | 124.70 | 35.87 | 0.00 | 0.00 | 0.00 |
July | 116.03 | 42.50 | 73.54 | 148.11 | 32.88 | 0.00 | 0.00 | 0.00 |
August | 124.66 | 58.13 | 66.53 | 163.34 | 32.33 | 0.00 | 0.00 | 0.00 |
September | 138.12 | 76.28 | 61.85 | 170.78 | 44.53 | 0.00 | 0.00 | 0.00 |
October | 125.12 | 77.25 | 47.87 | 144.25 | 55.04 | 0.00 | 0.00 | 0.00 |
November | 73.97 | 42.39 | 31.58 | 73.70 | 64.23 | 0.00 | 0.00 | 0.00 |
December | 77.40 | 50.09 | 27.31 | 78.32 | 79.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 109.16 | 53.39 | 55.77 | 125.43 | 53.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.82 | 28.57 | 27.31 | 67.58 | 32.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.12 | 77.25 | 81.65 | 170.78 | 79.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 57.06 | 61.14 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 99.64 | 53.52 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 112.22 | 44.95 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 124.91 | 38.02 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 114.46 | 33.68 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 105.16 | 27.96 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 124.40 | 25.95 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 136.98 | 25.69 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 143.71 | 35.07 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 121.57 | 42.91 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 62.31 | 50.55 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 66.08 | 63.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 105.72 | 41.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 57.06 | 25.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 143.71 | 63.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 57.06 | 61.14 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 99.64 | 53.52 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 112.22 | 44.95 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 124.91 | 38.02 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 114.46 | 33.68 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 105.16 | 27.96 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 124.40 | 25.95 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 136.98 | 25.69 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 143.71 | 35.07 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 121.57 | 42.91 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 62.31 | 50.55 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 66.08 | 63.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 105.72 | 41.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 57.06 | 25.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 143.71 | 63.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.82 | 43.24 | 29.58 | 68.58 | 72.08 | 0.00 | 0.00 | 0.00 |
February | 111.99 | 69.32 | 42.67 | 119.55 | 63.19 | 0.00 | 0.00 | 0.00 |
March | 120.46 | 64.24 | 56.22 | 134.55 | 53.09 | 0.00 | 0.00 | 0.00 |
April | 127.19 | 55.22 | 71.96 | 149.74 | 44.91 | 0.00 | 0.00 | 0.00 |
May | 116.30 | 34.65 | 81.65 | 137.21 | 39.82 | 0.00 | 0.00 | 0.00 |
June | 106.40 | 28.57 | 77.83 | 126.04 | 33.08 | 0.00 | 0.00 | 0.00 |
July | 116.03 | 42.50 | 73.54 | 148.92 | 30.74 | 0.00 | 0.00 | 0.00 |
August | 124.66 | 58.13 | 66.53 | 163.88 | 30.46 | 0.00 | 0.00 | 0.00 |
September | 138.12 | 76.28 | 61.85 | 171.92 | 41.59 | 0.00 | 0.00 | 0.00 |
October | 125.12 | 77.25 | 47.87 | 145.67 | 50.76 | 0.00 | 0.00 | 0.00 |
November | 73.97 | 42.39 | 31.58 | 74.78 | 59.65 | 0.00 | 0.00 | 0.00 |
December | 77.40 | 50.09 | 27.31 | 79.26 | 74.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 109.16 | 53.39 | 55.77 | 126.69 | 49.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.82 | 28.57 | 27.31 | 68.58 | 30.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.12 | 77.25 | 81.65 | 171.92 | 74.36 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.150134E+09 | 0.184108E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.237306E+09 | 0.145554E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.296722E+09 | 0.135926E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.320023E+09 | 0.111072E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.302501E+09 | 0.100078E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.270480E+09 | 78552316.23 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.332085E+09 | 73996980.51 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.366473E+09 | 72323907.26 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.370564E+09 | 97652494.14 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.322529E+09 | 0.127261E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.158322E+09 | 0.146591E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.174322E+09 | 0.187310E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.330146E+10 | 0.146043E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.150134E+09 | 72323907.26 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.370564E+09 | 0.187310E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.150134E+09 | 0.184108E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.237306E+09 | 0.145554E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.296722E+09 | 0.135926E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.320023E+09 | 0.111072E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.302501E+09 | 0.100078E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.270480E+09 | 78552316.23 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.332085E+09 | 73996980.51 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.366473E+09 | 72323907.26 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.370564E+09 | 97652494.14 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.322529E+09 | 0.127261E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.158322E+09 | 0.146591E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.174322E+09 | 0.187310E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.330146E+10 | 0.146043E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.150134E+09 | 72323907.26 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.370564E+09 | 0.187310E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.150134E+09 | 0.184108E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.237306E+09 | 0.145554E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.296722E+09 | 0.135926E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.320023E+09 | 0.111072E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.302501E+09 | 0.100078E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.270480E+09 | 78552316.23 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.332085E+09 | 73996980.51 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.366473E+09 | 72323907.26 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.370564E+09 | 97652494.14 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.322529E+09 | 0.127261E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.158322E+09 | 0.146591E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.174322E+09 | 0.187310E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.330146E+10 | 0.146043E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.150134E+09 | 72323907.26 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.370564E+09 | 0.187310E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.150134E+09 | 0.184108E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.237306E+09 | 0.145554E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.296722E+09 | 0.135926E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.320023E+09 | 0.111072E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.302501E+09 | 0.100078E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.270480E+09 | 78552316.23 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.332085E+09 | 73996980.51 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.366473E+09 | 72323907.26 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.370564E+09 | 97652494.14 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.322529E+09 | 0.127261E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.158322E+09 | 0.146591E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.174322E+09 | 0.187310E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.330146E+10 | 0.146043E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.150134E+09 | 72323907.26 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.370564E+09 | 0.187310E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.196113E+09 | 0.116453E+09 | 79660284.81 | 0.181323E+09 | 0.218382E+09 |
February | 0.272406E+09 | 0.168623E+09 | 0.103783E+09 | 0.286148E+09 | 0.172867E+09 |
March | 0.324426E+09 | 0.173013E+09 | 0.151413E+09 | 0.357549E+09 | 0.161480E+09 |
April | 0.331483E+09 | 0.143928E+09 | 0.187555E+09 | 0.385596E+09 | 0.131967E+09 |
May | 0.313202E+09 | 93305917.62 | 0.219896E+09 | 0.364484E+09 | 0.119000E+09 |
June | 0.277305E+09 | 74452992.86 | 0.202852E+09 | 0.325829E+09 | 93468704.01 |
July | 0.312494E+09 | 0.114452E+09 | 0.198042E+09 | 0.399566E+09 | 88167086.03 |
August | 0.335735E+09 | 0.156559E+09 | 0.179176E+09 | 0.440697E+09 | 86273672.90 |
September | 0.359982E+09 | 0.198794E+09 | 0.161188E+09 | 0.445631E+09 | 0.116489E+09 |
October | 0.336952E+09 | 0.208043E+09 | 0.128909E+09 | 0.388460E+09 | 0.151400E+09 |
November | 0.192791E+09 | 0.110485E+09 | 82305443.16 | 0.190955E+09 | 0.174033E+09 |
December | 0.208438E+09 | 0.134889E+09 | 73549600.79 | 0.210144E+09 | 0.222402E+09 |
Annual Sum or Average | 0.346133E+10 | 0.169300E+10 | 0.176833E+10 | 0.397638E+10 | 0.173593E+10 |
Minimum of Months | 0.192791E+09 | 74452992.86 | 73549600.79 | 0.181323E+09 | 86273672.90 |
Maximum of Months | 0.359982E+09 | 0.208043E+09 | 0.219896E+09 | 0.445631E+09 | 0.222402E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.196113E+09 | 0.116453E+09 | 79660284.81 | 0.181323E+09 | 0.218382E+09 |
February | 0.272406E+09 | 0.168623E+09 | 0.103783E+09 | 0.286148E+09 | 0.172867E+09 |
March | 0.324426E+09 | 0.173013E+09 | 0.151413E+09 | 0.357549E+09 | 0.161480E+09 |
April | 0.331483E+09 | 0.143928E+09 | 0.187555E+09 | 0.385596E+09 | 0.131967E+09 |
May | 0.313202E+09 | 93305917.62 | 0.219896E+09 | 0.364484E+09 | 0.119000E+09 |
June | 0.277305E+09 | 74452992.86 | 0.202852E+09 | 0.325829E+09 | 93468704.01 |
July | 0.312494E+09 | 0.114452E+09 | 0.198042E+09 | 0.399566E+09 | 88167086.03 |
August | 0.335735E+09 | 0.156559E+09 | 0.179176E+09 | 0.440697E+09 | 86273672.90 |
September | 0.359982E+09 | 0.198794E+09 | 0.161188E+09 | 0.445631E+09 | 0.116489E+09 |
October | 0.336952E+09 | 0.208043E+09 | 0.128909E+09 | 0.388460E+09 | 0.151400E+09 |
November | 0.192791E+09 | 0.110485E+09 | 82305443.16 | 0.190955E+09 | 0.174033E+09 |
December | 0.208438E+09 | 0.134889E+09 | 73549600.79 | 0.210144E+09 | 0.222402E+09 |
Annual Sum or Average | 0.346133E+10 | 0.169300E+10 | 0.176833E+10 | 0.397638E+10 | 0.173593E+10 |
Minimum of Months | 0.192791E+09 | 74452992.86 | 73549600.79 | 0.181323E+09 | 86273672.90 |
Maximum of Months | 0.359982E+09 | 0.208043E+09 | 0.219896E+09 | 0.445631E+09 | 0.222402E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.147459E+09 | 0.196128E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.233653E+09 | 0.156059E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.291463E+09 | 0.149935E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.313486E+09 | 0.122492E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.296472E+09 | 0.107804E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.267203E+09 | 81997088.93 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.330358E+09 | 75566684.92 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.364980E+09 | 73609786.00 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.367751E+09 | 0.101298E+09 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.317270E+09 | 0.139025E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.155182E+09 | 0.158109E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.171847E+09 | 0.199385E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.325712E+10 | 0.156141E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.147459E+09 | 73609786.00 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.367751E+09 | 0.199385E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.147459E+09 | 0.196128E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.233653E+09 | 0.156059E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.291463E+09 | 0.149935E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.313486E+09 | 0.122492E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.296472E+09 | 0.107804E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.267203E+09 | 81997088.93 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.330358E+09 | 75566684.92 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.364980E+09 | 73609786.00 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.367751E+09 | 0.101298E+09 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.317270E+09 | 0.139025E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.155182E+09 | 0.158109E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.171847E+09 | 0.199385E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.325712E+10 | 0.156141E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.147459E+09 | 73609786.00 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.367751E+09 | 0.199385E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.196113E+09 | 0.116453E+09 | 79660284.81 | 0.178141E+09 | 0.232502E+09 |
February | 0.272406E+09 | 0.168623E+09 | 0.103783E+09 | 0.281832E+09 | 0.185203E+09 |
March | 0.324426E+09 | 0.173013E+09 | 0.151413E+09 | 0.351326E+09 | 0.177917E+09 |
April | 0.331483E+09 | 0.143928E+09 | 0.187555E+09 | 0.377902E+09 | 0.145361E+09 |
May | 0.313202E+09 | 93305917.62 | 0.219896E+09 | 0.357397E+09 | 0.128062E+09 |
June | 0.277305E+09 | 74452992.86 | 0.202852E+09 | 0.322004E+09 | 97501385.84 |
July | 0.312494E+09 | 0.114452E+09 | 0.198042E+09 | 0.397592E+09 | 89993606.58 |
August | 0.335735E+09 | 0.156559E+09 | 0.179176E+09 | 0.438992E+09 | 87772059.03 |
September | 0.359982E+09 | 0.198794E+09 | 0.161188E+09 | 0.442343E+09 | 0.120782E+09 |
October | 0.336952E+09 | 0.208043E+09 | 0.128909E+09 | 0.382287E+09 | 0.165221E+09 |
November | 0.192791E+09 | 0.110485E+09 | 82305443.16 | 0.187240E+09 | 0.187544E+09 |
December | 0.208438E+09 | 0.134889E+09 | 73549600.79 | 0.207214E+09 | 0.236620E+09 |
Annual Sum or Average | 0.346133E+10 | 0.169300E+10 | 0.176833E+10 | 0.392427E+10 | 0.185448E+10 |
Minimum of Months | 0.192791E+09 | 74452992.86 | 73549600.79 | 0.178141E+09 | 87772059.03 |
Maximum of Months | 0.359982E+09 | 0.208043E+09 | 0.219896E+09 | 0.442343E+09 | 0.236620E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.147927E+09 | 0.189780E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.234451E+09 | 0.151059E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.292479E+09 | 0.144981E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.314415E+09 | 0.119959E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.296532E+09 | 0.108522E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.266816E+09 | 84319167.77 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.329682E+09 | 79167278.85 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.364430E+09 | 77698298.31 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.367607E+09 | 0.103588E+09 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.317997E+09 | 0.136913E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.155991E+09 | 0.153079E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.172422E+09 | 0.193483E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.326075E+10 | 0.154255E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.147927E+09 | 77698298.31 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.367607E+09 | 0.193483E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.147927E+09 | 0.189780E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.234451E+09 | 0.151059E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.292479E+09 | 0.144981E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.314415E+09 | 0.119959E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.296532E+09 | 0.108522E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.266816E+09 | 84319167.77 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.329682E+09 | 79167278.85 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.364430E+09 | 77698298.31 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.367607E+09 | 0.103588E+09 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.317997E+09 | 0.136913E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.155991E+09 | 0.153079E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.172422E+09 | 0.193483E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.326075E+10 | 0.154255E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.147927E+09 | 77698298.31 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.367607E+09 | 0.193483E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195041E+09 | 0.115817E+09 | 79224982.71 | 0.177740E+09 | 0.223796E+09 |
February | 0.270917E+09 | 0.167701E+09 | 0.103216E+09 | 0.281252E+09 | 0.178341E+09 |
March | 0.322653E+09 | 0.172067E+09 | 0.150586E+09 | 0.350621E+09 | 0.171167E+09 |
April | 0.329671E+09 | 0.143141E+09 | 0.186530E+09 | 0.376936E+09 | 0.141606E+09 |
May | 0.311490E+09 | 92796049.21 | 0.218694E+09 | 0.355510E+09 | 0.128183E+09 |
June | 0.275790E+09 | 74046145.90 | 0.201744E+09 | 0.319783E+09 | 99655168.15 |
July | 0.310786E+09 | 0.113827E+09 | 0.196960E+09 | 0.394616E+09 | 93683320.78 |
August | 0.333901E+09 | 0.155704E+09 | 0.178197E+09 | 0.435936E+09 | 92045980.58 |
September | 0.358015E+09 | 0.197708E+09 | 0.160307E+09 | 0.439753E+09 | 0.122775E+09 |
October | 0.335111E+09 | 0.206906E+09 | 0.128205E+09 | 0.381055E+09 | 0.161840E+09 |
November | 0.191737E+09 | 0.109882E+09 | 81855686.64 | 0.187188E+09 | 0.180637E+09 |
December | 0.207299E+09 | 0.134152E+09 | 73147690.40 | 0.206776E+09 | 0.228406E+09 |
Annual Sum or Average | 0.344241E+10 | 0.168375E+10 | 0.175867E+10 | 0.390717E+10 | 0.182214E+10 |
Minimum of Months | 0.191737E+09 | 74046145.90 | 73147690.40 | 0.177740E+09 | 92045980.58 |
Maximum of Months | 0.358015E+09 | 0.206906E+09 | 0.218694E+09 | 0.439753E+09 | 0.228406E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.148303E+09 | 0.186971E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.235012E+09 | 0.148830E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.293244E+09 | 0.142359E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.315345E+09 | 0.117781E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.297066E+09 | 0.107446E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.266985E+09 | 83927722.10 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.329725E+09 | 79075869.44 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.364423E+09 | 77739648.44 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.367782E+09 | 0.103071E+09 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.318739E+09 | 0.134625E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.156543E+09 | 0.150537E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.172785E+09 | 0.190932E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.326595E+10 | 0.152330E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.148303E+09 | 77739648.44 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.367782E+09 | 0.190932E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.148303E+09 | 0.186971E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.235012E+09 | 0.148830E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.293244E+09 | 0.142359E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.315345E+09 | 0.117781E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.297066E+09 | 0.107446E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.266985E+09 | 83927722.10 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.329725E+09 | 79075869.44 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.364423E+09 | 77739648.44 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.367782E+09 | 0.103071E+09 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.318739E+09 | 0.134625E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.156543E+09 | 0.150537E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.172785E+09 | 0.190932E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.326595E+10 | 0.152330E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.148303E+09 | 77739648.44 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.367782E+09 | 0.190932E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195041E+09 | 0.115817E+09 | 79224982.71 | 0.178200E+09 | 0.220477E+09 |
February | 0.270917E+09 | 0.167701E+09 | 0.103216E+09 | 0.281929E+09 | 0.175707E+09 |
March | 0.322653E+09 | 0.172067E+09 | 0.150586E+09 | 0.351538E+09 | 0.168073E+09 |
April | 0.329671E+09 | 0.143141E+09 | 0.186530E+09 | 0.378044E+09 | 0.139040E+09 |
May | 0.311490E+09 | 92796049.21 | 0.218694E+09 | 0.356148E+09 | 0.126915E+09 |
June | 0.275790E+09 | 74046145.90 | 0.201744E+09 | 0.319986E+09 | 99193375.52 |
July | 0.310786E+09 | 0.113827E+09 | 0.196960E+09 | 0.394667E+09 | 93575609.72 |
August | 0.333901E+09 | 0.155704E+09 | 0.178197E+09 | 0.435926E+09 | 92095548.55 |
September | 0.358015E+09 | 0.197708E+09 | 0.160307E+09 | 0.439963E+09 | 0.122163E+09 |
October | 0.335111E+09 | 0.206906E+09 | 0.128205E+09 | 0.381938E+09 | 0.159143E+09 |
November | 0.191737E+09 | 0.109882E+09 | 81855686.64 | 0.187849E+09 | 0.177632E+09 |
December | 0.207299E+09 | 0.134152E+09 | 73147690.40 | 0.207214E+09 | 0.225384E+09 |
Annual Sum or Average | 0.344241E+10 | 0.168375E+10 | 0.175867E+10 | 0.391340E+10 | 0.179940E+10 |
Minimum of Months | 0.191737E+09 | 74046145.90 | 73147690.40 | 0.178200E+09 | 92095548.55 |
Maximum of Months | 0.358015E+09 | 0.206906E+09 | 0.218694E+09 | 0.439963E+09 | 0.225384E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.148717E+09 | 0.184829E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.235606E+09 | 0.147107E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.294110E+09 | 0.139998E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.316612E+09 | 0.115431E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.298234E+09 | 0.105661E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.267538E+09 | 82962726.33 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.330047E+09 | 78338152.57 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.364698E+09 | 77018046.75 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.368306E+09 | 0.101923E+09 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.319803E+09 | 0.131936E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.157166E+09 | 0.148386E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.173169E+09 | 0.188955E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.327401E+10 | 0.150255E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.148717E+09 | 77018046.75 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.368306E+09 | 0.188955E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.148717E+09 | 0.184829E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.235606E+09 | 0.147107E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.294110E+09 | 0.139998E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.316612E+09 | 0.115431E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.298234E+09 | 0.105661E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.267538E+09 | 82962726.33 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.330047E+09 | 78338152.57 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.364698E+09 | 77018046.75 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.368306E+09 | 0.101923E+09 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.319803E+09 | 0.131936E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.157166E+09 | 0.148386E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.173169E+09 | 0.188955E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.327401E+10 | 0.150255E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.148717E+09 | 77018046.75 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.368306E+09 | 0.188955E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195041E+09 | 0.115817E+09 | 79224982.71 | 0.178704E+09 | 0.217946E+09 |
February | 0.270917E+09 | 0.167701E+09 | 0.103216E+09 | 0.282643E+09 | 0.173676E+09 |
March | 0.322653E+09 | 0.172067E+09 | 0.150586E+09 | 0.352575E+09 | 0.165291E+09 |
April | 0.329671E+09 | 0.143141E+09 | 0.186530E+09 | 0.379553E+09 | 0.136275E+09 |
May | 0.311490E+09 | 92796049.21 | 0.218694E+09 | 0.357544E+09 | 0.124821E+09 |
June | 0.275790E+09 | 74046145.90 | 0.201744E+09 | 0.320647E+09 | 98060924.74 |
July | 0.310786E+09 | 0.113827E+09 | 0.196960E+09 | 0.395056E+09 | 92711010.31 |
August | 0.333901E+09 | 0.155704E+09 | 0.178197E+09 | 0.436258E+09 | 91248396.30 |
September | 0.358015E+09 | 0.197708E+09 | 0.160307E+09 | 0.440591E+09 | 0.120810E+09 |
October | 0.335111E+09 | 0.206906E+09 | 0.128205E+09 | 0.383205E+09 | 0.155977E+09 |
November | 0.191737E+09 | 0.109882E+09 | 81855686.64 | 0.188596E+09 | 0.175096E+09 |
December | 0.207299E+09 | 0.134152E+09 | 73147690.40 | 0.207678E+09 | 0.223043E+09 |
Annual Sum or Average | 0.344241E+10 | 0.168375E+10 | 0.175867E+10 | 0.392305E+10 | 0.177496E+10 |
Minimum of Months | 0.191737E+09 | 74046145.90 | 73147690.40 | 0.178704E+09 | 91248396.30 |
Maximum of Months | 0.358015E+09 | 0.206906E+09 | 0.218694E+09 | 0.440591E+09 | 0.223043E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.150526E+09 | 0.179191E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.237772E+09 | 0.142926E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.296650E+09 | 0.135149E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.319876E+09 | 0.110671E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.301704E+09 | 0.101348E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.269473E+09 | 80248258.54 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.331131E+09 | 76102139.47 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.365558E+09 | 74681986.46 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.370059E+09 | 98958927.69 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.322565E+09 | 0.126680E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.158940E+09 | 0.143564E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.174681E+09 | 0.183688E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.329894E+10 | 0.145321E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.150526E+09 | 74681986.46 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.370059E+09 | 0.183688E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.150526E+09 | 0.179191E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.237772E+09 | 0.142926E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.296650E+09 | 0.135149E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.319876E+09 | 0.110671E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.301704E+09 | 0.101348E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.269473E+09 | 80248258.54 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.331131E+09 | 76102139.47 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.365558E+09 | 74681986.46 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.370059E+09 | 98958927.69 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.322565E+09 | 0.126680E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.158940E+09 | 0.143564E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.174681E+09 | 0.183688E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.329894E+10 | 0.145321E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.150526E+09 | 74681986.46 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.370059E+09 | 0.183688E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.150526E+09 | 0.179191E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.237772E+09 | 0.142926E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.296650E+09 | 0.135149E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.319876E+09 | 0.110671E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.301704E+09 | 0.101348E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.269473E+09 | 80248258.54 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.331131E+09 | 76102139.47 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.365558E+09 | 74681986.46 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.370059E+09 | 98958927.69 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.322565E+09 | 0.126680E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.158940E+09 | 0.143564E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.174681E+09 | 0.183688E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.329894E+10 | 0.145321E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.150526E+09 | 74681986.46 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.370059E+09 | 0.183688E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.150526E+09 | 0.179191E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.237772E+09 | 0.142926E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.296650E+09 | 0.135149E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.319876E+09 | 0.110671E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.301704E+09 | 0.101348E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.269473E+09 | 80248258.54 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.331131E+09 | 76102139.47 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.365558E+09 | 74681986.46 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.370059E+09 | 98958927.69 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.322565E+09 | 0.126680E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.158940E+09 | 0.143564E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.174681E+09 | 0.183688E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.329894E+10 | 0.145321E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.150526E+09 | 74681986.46 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.370059E+09 | 0.183688E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195041E+09 | 0.115817E+09 | 79224982.71 | 0.180814E+09 | 0.211399E+09 |
February | 0.270917E+09 | 0.167701E+09 | 0.103216E+09 | 0.285152E+09 | 0.168821E+09 |
March | 0.322653E+09 | 0.172067E+09 | 0.150586E+09 | 0.355520E+09 | 0.159659E+09 |
April | 0.329671E+09 | 0.143141E+09 | 0.186530E+09 | 0.383325E+09 | 0.130741E+09 |
May | 0.311490E+09 | 92796049.21 | 0.218694E+09 | 0.361556E+09 | 0.119801E+09 |
June | 0.275790E+09 | 74046145.90 | 0.201744E+09 | 0.322864E+09 | 94908056.66 |
July | 0.310786E+09 | 0.113827E+09 | 0.196960E+09 | 0.396272E+09 | 90111627.00 |
August | 0.333901E+09 | 0.155704E+09 | 0.178197E+09 | 0.437220E+09 | 88529267.71 |
September | 0.358015E+09 | 0.197708E+09 | 0.160307E+09 | 0.442610E+09 | 0.117339E+09 |
October | 0.335111E+09 | 0.206906E+09 | 0.128205E+09 | 0.386393E+09 | 0.149847E+09 |
November | 0.191737E+09 | 0.109882E+09 | 81855686.64 | 0.190661E+09 | 0.169491E+09 |
December | 0.207299E+09 | 0.134152E+09 | 73147690.40 | 0.209432E+09 | 0.216901E+09 |
Annual Sum or Average | 0.344241E+10 | 0.168375E+10 | 0.175867E+10 | 0.395182E+10 | 0.171755E+10 |
Minimum of Months | 0.191737E+09 | 74046145.90 | 73147690.40 | 0.180814E+09 | 88529267.71 |
Maximum of Months | 0.358015E+09 | 0.206906E+09 | 0.218694E+09 | 0.442610E+09 | 0.216901E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195041E+09 | 0.115817E+09 | 79224982.71 | 0.180814E+09 | 0.211399E+09 |
February | 0.270917E+09 | 0.167701E+09 | 0.103216E+09 | 0.285152E+09 | 0.168821E+09 |
March | 0.322653E+09 | 0.172067E+09 | 0.150586E+09 | 0.355520E+09 | 0.159659E+09 |
April | 0.329671E+09 | 0.143141E+09 | 0.186530E+09 | 0.383325E+09 | 0.130741E+09 |
May | 0.311490E+09 | 92796049.21 | 0.218694E+09 | 0.361556E+09 | 0.119801E+09 |
June | 0.275790E+09 | 74046145.90 | 0.201744E+09 | 0.322864E+09 | 94908056.66 |
July | 0.310786E+09 | 0.113827E+09 | 0.196960E+09 | 0.396272E+09 | 90111627.00 |
August | 0.333901E+09 | 0.155704E+09 | 0.178197E+09 | 0.437220E+09 | 88529267.71 |
September | 0.358015E+09 | 0.197708E+09 | 0.160307E+09 | 0.442610E+09 | 0.117339E+09 |
October | 0.335111E+09 | 0.206906E+09 | 0.128205E+09 | 0.386393E+09 | 0.149847E+09 |
November | 0.191737E+09 | 0.109882E+09 | 81855686.64 | 0.190661E+09 | 0.169491E+09 |
December | 0.207299E+09 | 0.134152E+09 | 73147690.40 | 0.209432E+09 | 0.216901E+09 |
Annual Sum or Average | 0.344241E+10 | 0.168375E+10 | 0.175867E+10 | 0.395182E+10 | 0.171755E+10 |
Minimum of Months | 0.191737E+09 | 74046145.90 | 73147690.40 | 0.180814E+09 | 88529267.71 |
Maximum of Months | 0.358015E+09 | 0.206906E+09 | 0.218694E+09 | 0.442610E+09 | 0.216901E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.149828E+09 | 0.180505E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.236912E+09 | 0.143783E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.295414E+09 | 0.136306E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.318143E+09 | 0.111909E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.299627E+09 | 0.102713E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.268290E+09 | 80639527.06 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.330472E+09 | 75943498.35 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.364985E+09 | 74403573.22 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.368875E+09 | 99585277.55 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.320908E+09 | 0.128373E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.158188E+09 | 0.144728E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.174107E+09 | 0.184867E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.328575E+10 | 0.146376E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.149828E+09 | 74403573.22 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.368875E+09 | 0.184867E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.149828E+09 | 0.180505E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.236912E+09 | 0.143783E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.295414E+09 | 0.136306E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.318143E+09 | 0.111909E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.299627E+09 | 0.102713E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.268290E+09 | 80639527.06 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.330472E+09 | 75943498.35 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.364985E+09 | 74403573.22 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.368875E+09 | 99585277.55 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.320908E+09 | 0.128373E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.158188E+09 | 0.144728E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.174107E+09 | 0.184867E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.328575E+10 | 0.146376E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.149828E+09 | 74403573.22 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.368875E+09 | 0.184867E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195041E+09 | 0.115817E+09 | 79224982.71 | 0.180047E+09 | 0.212840E+09 |
February | 0.270917E+09 | 0.167701E+09 | 0.103216E+09 | 0.284216E+09 | 0.169749E+09 |
March | 0.322653E+09 | 0.172067E+09 | 0.150586E+09 | 0.354154E+09 | 0.160937E+09 |
April | 0.329671E+09 | 0.143141E+09 | 0.186530E+09 | 0.381396E+09 | 0.132128E+09 |
May | 0.311490E+09 | 92796049.21 | 0.218694E+09 | 0.359224E+09 | 0.121346E+09 |
June | 0.275790E+09 | 74046145.90 | 0.201744E+09 | 0.321570E+09 | 95328408.66 |
July | 0.310786E+09 | 0.113827E+09 | 0.196960E+09 | 0.395592E+09 | 89896196.18 |
August | 0.333901E+09 | 0.155704E+09 | 0.178197E+09 | 0.436634E+09 | 88178580.59 |
September | 0.358015E+09 | 0.197708E+09 | 0.160307E+09 | 0.441296E+09 | 0.118043E+09 |
October | 0.335111E+09 | 0.206906E+09 | 0.128205E+09 | 0.384538E+09 | 0.151772E+09 |
November | 0.191737E+09 | 0.109882E+09 | 81855686.64 | 0.189832E+09 | 0.170774E+09 |
December | 0.207299E+09 | 0.134152E+09 | 73147690.40 | 0.208805E+09 | 0.218194E+09 |
Annual Sum or Average | 0.344241E+10 | 0.168375E+10 | 0.175867E+10 | 0.393730E+10 | 0.172919E+10 |
Minimum of Months | 0.191737E+09 | 74046145.90 | 73147690.40 | 0.180047E+09 | 88178580.59 |
Maximum of Months | 0.358015E+09 | 0.206906E+09 | 0.218694E+09 | 0.441296E+09 | 0.218194E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.149988E+09 | 0.179767E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.237157E+09 | 0.143109E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.295731E+09 | 0.135547E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.318504E+09 | 0.111298E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.300015E+09 | 0.102193E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.268552E+09 | 80286006.83 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.330694E+09 | 75603424.31 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.365171E+09 | 74091475.42 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.369064E+09 | 99226102.58 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.321160E+09 | 0.127813E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.158390E+09 | 0.144038E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.174276E+09 | 0.184111E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.328870E+10 | 0.145708E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.149988E+09 | 74091475.42 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.369064E+09 | 0.184111E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.149988E+09 | 0.179767E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.237157E+09 | 0.143109E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.295731E+09 | 0.135547E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.318504E+09 | 0.111298E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.300015E+09 | 0.102193E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.268552E+09 | 80286006.83 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.330694E+09 | 75603424.31 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.365171E+09 | 74091475.42 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.369064E+09 | 99226102.58 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.321160E+09 | 0.127813E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.158390E+09 | 0.144038E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.174276E+09 | 0.184111E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.328870E+10 | 0.145708E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.149988E+09 | 74091475.42 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.369064E+09 | 0.184111E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195041E+09 | 0.115817E+09 | 79224982.71 | 0.180240E+09 | 0.211966E+09 |
February | 0.270917E+09 | 0.167701E+09 | 0.103216E+09 | 0.284512E+09 | 0.168952E+09 |
March | 0.322653E+09 | 0.172067E+09 | 0.150586E+09 | 0.354537E+09 | 0.160043E+09 |
April | 0.329671E+09 | 0.143141E+09 | 0.186530E+09 | 0.381827E+09 | 0.131410E+09 |
May | 0.311490E+09 | 92796049.21 | 0.218694E+09 | 0.359687E+09 | 0.120734E+09 |
June | 0.275790E+09 | 74046145.90 | 0.201744E+09 | 0.321883E+09 | 94911725.16 |
July | 0.310786E+09 | 0.113827E+09 | 0.196960E+09 | 0.395858E+09 | 89494495.33 |
August | 0.333901E+09 | 0.155704E+09 | 0.178197E+09 | 0.436857E+09 | 87809969.86 |
September | 0.358015E+09 | 0.197708E+09 | 0.160307E+09 | 0.441522E+09 | 0.117618E+09 |
October | 0.335111E+09 | 0.206906E+09 | 0.128205E+09 | 0.384839E+09 | 0.151111E+09 |
November | 0.191737E+09 | 0.109882E+09 | 81855686.64 | 0.190074E+09 | 0.169958E+09 |
December | 0.207299E+09 | 0.134152E+09 | 73147690.40 | 0.209009E+09 | 0.217298E+09 |
Annual Sum or Average | 0.344241E+10 | 0.168375E+10 | 0.175867E+10 | 0.394085E+10 | 0.172131E+10 |
Minimum of Months | 0.191737E+09 | 74046145.90 | 73147690.40 | 0.180240E+09 | 87809969.86 |
Maximum of Months | 0.358015E+09 | 0.206906E+09 | 0.218694E+09 | 0.441522E+09 | 0.217298E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.150610E+09 | 0.176486E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.238084E+09 | 0.140261E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.296997E+09 | 0.132158E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.320057E+09 | 0.108331E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.301973E+09 | 99326981.29 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.269674E+09 | 78639725.69 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.331385E+09 | 74392133.10 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.365700E+09 | 73055320.04 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.370011E+09 | 97360037.86 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.322428E+09 | 0.124679E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.159189E+09 | 0.141093E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.174911E+09 | 0.180896E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.330102E+10 | 0.142668E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.150610E+09 | 73055320.04 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.370011E+09 | 0.180896E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.150610E+09 | 0.176486E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.238084E+09 | 0.140261E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.296997E+09 | 0.132158E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.320057E+09 | 0.108331E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.301973E+09 | 99326981.29 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.269674E+09 | 78639725.69 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.331385E+09 | 74392133.10 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.365700E+09 | 73055320.04 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.370011E+09 | 97360037.86 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.322428E+09 | 0.124679E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.159189E+09 | 0.141093E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.174911E+09 | 0.180896E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.330102E+10 | 0.142668E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.150610E+09 | 73055320.04 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.370011E+09 | 0.180896E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195041E+09 | 0.115817E+09 | 79224982.71 | 0.180993E+09 | 0.208086E+09 |
February | 0.270917E+09 | 0.167701E+09 | 0.103216E+09 | 0.285625E+09 | 0.165587E+09 |
March | 0.322653E+09 | 0.172067E+09 | 0.150586E+09 | 0.356060E+09 | 0.156049E+09 |
April | 0.329671E+09 | 0.143141E+09 | 0.186530E+09 | 0.383681E+09 | 0.127918E+09 |
May | 0.311490E+09 | 92796049.21 | 0.218694E+09 | 0.362016E+09 | 0.117360E+09 |
June | 0.275790E+09 | 74046145.90 | 0.201744E+09 | 0.323224E+09 | 92977503.09 |
July | 0.310786E+09 | 0.113827E+09 | 0.196960E+09 | 0.396686E+09 | 88070401.42 |
August | 0.333901E+09 | 0.155704E+09 | 0.178197E+09 | 0.437491E+09 | 86591638.41 |
September | 0.358015E+09 | 0.197708E+09 | 0.160307E+09 | 0.442654E+09 | 0.115416E+09 |
October | 0.335111E+09 | 0.206906E+09 | 0.128205E+09 | 0.386352E+09 | 0.147420E+09 |
November | 0.191737E+09 | 0.109882E+09 | 81855686.64 | 0.191032E+09 | 0.166481E+09 |
December | 0.207299E+09 | 0.134152E+09 | 73147690.40 | 0.209773E+09 | 0.213491E+09 |
Annual Sum or Average | 0.344241E+10 | 0.168375E+10 | 0.175867E+10 | 0.395559E+10 | 0.168545E+10 |
Minimum of Months | 0.191737E+09 | 74046145.90 | 73147690.40 | 0.180993E+09 | 86591638.41 |
Maximum of Months | 0.358015E+09 | 0.206906E+09 | 0.218694E+09 | 0.442654E+09 | 0.213491E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.152825E+09 | 0.163759E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.241049E+09 | 0.129484E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.300577E+09 | 0.120394E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.323771E+09 | 98542088.10 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.306567E+09 | 90220042.96 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.272577E+09 | 72474270.59 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.333205E+09 | 69503748.14 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.366900E+09 | 68797811.64 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.372488E+09 | 90913326.10 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.325614E+09 | 0.114932E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.161507E+09 | 0.131034E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.176984E+09 | 0.168779E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.333406E+10 | 0.131883E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.152825E+09 | 68797811.64 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.372488E+09 | 0.168779E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.152825E+09 | 0.163759E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.241049E+09 | 0.129484E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.300577E+09 | 0.120394E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.323771E+09 | 98542088.10 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.306567E+09 | 90220042.96 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.272577E+09 | 72474270.59 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.333205E+09 | 69503748.14 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.366900E+09 | 68797811.64 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.372488E+09 | 90913326.10 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.325614E+09 | 0.114932E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.161507E+09 | 0.131034E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.176984E+09 | 0.168779E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.333406E+10 | 0.131883E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.152825E+09 | 68797811.64 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.372488E+09 | 0.168779E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195041E+09 | 0.115817E+09 | 79224982.71 | 0.183689E+09 | 0.193062E+09 |
February | 0.270917E+09 | 0.167701E+09 | 0.103216E+09 | 0.289209E+09 | 0.152873E+09 |
March | 0.322653E+09 | 0.172067E+09 | 0.150586E+09 | 0.360374E+09 | 0.142190E+09 |
April | 0.329671E+09 | 0.143141E+09 | 0.186530E+09 | 0.388131E+09 | 0.116415E+09 |
May | 0.311490E+09 | 92796049.21 | 0.218694E+09 | 0.367498E+09 | 0.106656E+09 |
June | 0.275790E+09 | 74046145.90 | 0.201744E+09 | 0.326686E+09 | 85741218.85 |
July | 0.310786E+09 | 0.113827E+09 | 0.196960E+09 | 0.398858E+09 | 82325279.57 |
August | 0.333901E+09 | 0.155704E+09 | 0.178197E+09 | 0.438923E+09 | 81587654.08 |
September | 0.358015E+09 | 0.197708E+09 | 0.160307E+09 | 0.445612E+09 | 0.107804E+09 |
October | 0.335111E+09 | 0.206906E+09 | 0.128205E+09 | 0.390164E+09 | 0.135946E+09 |
November | 0.191737E+09 | 0.109882E+09 | 81855686.64 | 0.193833E+09 | 0.154620E+09 |
December | 0.207299E+09 | 0.134152E+09 | 73147690.40 | 0.212280E+09 | 0.199159E+09 |
Annual Sum or Average | 0.344241E+10 | 0.168375E+10 | 0.175867E+10 | 0.399526E+10 | 0.155838E+10 |
Minimum of Months | 0.191737E+09 | 74046145.90 | 73147690.40 | 0.183689E+09 | 81587654.08 |
Maximum of Months | 0.358015E+09 | 0.206906E+09 | 0.218694E+09 | 0.445612E+09 | 0.199159E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 359.61 | 438.02 | 390.07 | 231.63 | 158.44 | 0.00 | 0.00 |
February | 628.94 | 383.58 | 599.87 | 371.33 | 228.54 | 0.00 | 0.00 |
March | 710.12 | 323.57 | 645.29 | 344.12 | 301.16 | 0.00 | 0.00 |
April | 791.39 | 273.23 | 681.30 | 295.82 | 385.48 | 0.00 | 0.00 |
May | 723.93 | 238.32 | 622.96 | 185.59 | 437.37 | 0.00 | 0.00 |
June | 668.82 | 193.34 | 569.95 | 153.02 | 416.92 | 0.00 | 0.00 |
July | 794.31 | 176.34 | 621.55 | 227.65 | 393.91 | 0.00 | 0.00 |
August | 876.38 | 172.43 | 667.78 | 311.40 | 356.38 | 0.00 | 0.00 |
September | 915.71 | 240.58 | 739.87 | 408.58 | 331.29 | 0.00 | 0.00 |
October | 771.74 | 303.11 | 670.20 | 413.80 | 256.40 | 0.00 | 0.00 |
November | 391.67 | 360.50 | 396.24 | 227.08 | 169.16 | 0.00 | 0.00 |
December | 417.25 | 445.80 | 414.59 | 268.29 | 146.29 | 0.00 | 0.00 |
Annual Sum or Average | 670.93 | 295.33 | 584.72 | 286.00 | 298.72 | 0.00 | 0.00 |
Minimum of Months | 359.61 | 172.43 | 390.07 | 153.02 | 146.29 | 0.00 | 0.00 |
Maximum of Months | 915.71 | 445.80 | 739.87 | 413.80 | 437.37 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 176.62 | 233.26 | 195.04 | 115.81 | 79.22 | 0.00 | 0.00 |
February | 309.66 | 205.57 | 299.93 | 185.66 | 114.27 | 0.00 | 0.00 |
March | 348.81 | 178.38 | 322.64 | 172.06 | 150.58 | 0.00 | 0.00 |
April | 387.68 | 150.60 | 340.65 | 147.91 | 192.74 | 0.00 | 0.00 |
May | 354.82 | 128.31 | 311.48 | 92.79 | 218.69 | 0.00 | 0.00 |
June | 330.40 | 100.89 | 284.97 | 76.51 | 208.46 | 0.00 | 0.00 |
July | 395.13 | 90.03 | 310.78 | 113.82 | 196.95 | 0.00 | 0.00 |
August | 436.44 | 87.74 | 333.89 | 155.70 | 178.19 | 0.00 | 0.00 |
September | 454.42 | 124.76 | 369.94 | 204.29 | 165.65 | 0.00 | 0.00 |
October | 379.64 | 165.50 | 335.10 | 206.90 | 128.20 | 0.00 | 0.00 |
November | 191.98 | 194.35 | 198.12 | 113.54 | 84.58 | 0.00 | 0.00 |
December | 205.69 | 237.23 | 207.29 | 134.15 | 73.15 | 0.00 | 0.00 |
Annual Sum or Average | 331.00 | 157.83 | 292.36 | 143.00 | 149.36 | 0.00 | 0.00 |
Minimum of Months | 176.62 | 87.74 | 195.04 | 76.51 | 73.15 | 0.00 | 0.00 |
Maximum of Months | 454.42 | 237.23 | 369.94 | 206.90 | 218.69 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 176.82 | 225.27 | 194.64 | 115.58 | 79.06 | 0.00 | 0.00 |
February | 310.08 | 198.60 | 299.32 | 185.28 | 114.04 | 0.00 | 0.00 |
March | 349.30 | 172.17 | 321.98 | 171.71 | 150.27 | 0.00 | 0.00 |
April | 388.03 | 147.19 | 339.95 | 147.60 | 192.35 | 0.00 | 0.00 |
May | 354.16 | 128.89 | 310.84 | 92.60 | 218.24 | 0.00 | 0.00 |
June | 329.25 | 103.51 | 284.39 | 76.35 | 208.03 | 0.00 | 0.00 |
July | 393.51 | 94.09 | 310.14 | 113.59 | 196.55 | 0.00 | 0.00 |
August | 434.88 | 92.38 | 333.21 | 155.38 | 177.83 | 0.00 | 0.00 |
September | 453.31 | 127.30 | 369.18 | 203.87 | 165.31 | 0.00 | 0.00 |
October | 379.72 | 162.66 | 334.41 | 206.48 | 127.94 | 0.00 | 0.00 |
November | 192.58 | 187.81 | 197.72 | 113.31 | 84.41 | 0.00 | 0.00 |
December | 205.95 | 229.75 | 206.87 | 133.87 | 73.00 | 0.00 | 0.00 |
Annual Sum or Average | 330.69 | 155.61 | 291.76 | 142.71 | 149.06 | 0.00 | 0.00 |
Minimum of Months | 176.82 | 92.38 | 194.64 | 76.35 | 73.00 | 0.00 | 0.00 |
Maximum of Months | 453.31 | 229.75 | 369.18 | 206.48 | 218.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 177.27 | 221.93 | 194.64 | 115.58 | 79.06 | 0.00 | 0.00 |
February | 310.83 | 195.67 | 299.32 | 185.28 | 114.04 | 0.00 | 0.00 |
March | 350.22 | 169.05 | 321.98 | 171.71 | 150.27 | 0.00 | 0.00 |
April | 389.17 | 144.52 | 339.95 | 147.60 | 192.35 | 0.00 | 0.00 |
May | 354.79 | 127.62 | 310.84 | 92.60 | 218.24 | 0.00 | 0.00 |
June | 329.46 | 103.03 | 284.39 | 76.35 | 208.03 | 0.00 | 0.00 |
July | 393.56 | 93.98 | 310.14 | 113.59 | 196.55 | 0.00 | 0.00 |
August | 434.88 | 92.43 | 333.21 | 155.38 | 177.83 | 0.00 | 0.00 |
September | 453.52 | 126.66 | 369.18 | 203.87 | 165.31 | 0.00 | 0.00 |
October | 380.61 | 159.94 | 334.41 | 206.48 | 127.94 | 0.00 | 0.00 |
November | 193.26 | 184.69 | 197.72 | 113.31 | 84.41 | 0.00 | 0.00 |
December | 206.39 | 226.72 | 206.87 | 133.87 | 73.00 | 0.00 | 0.00 |
Annual Sum or Average | 331.22 | 153.67 | 291.76 | 142.71 | 149.06 | 0.00 | 0.00 |
Minimum of Months | 177.27 | 92.43 | 194.64 | 76.35 | 73.00 | 0.00 | 0.00 |
Maximum of Months | 453.52 | 226.72 | 369.18 | 206.48 | 218.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 177.77 | 219.38 | 194.64 | 115.58 | 79.06 | 0.00 | 0.00 |
February | 311.61 | 193.41 | 299.32 | 185.28 | 114.04 | 0.00 | 0.00 |
March | 351.25 | 166.25 | 321.98 | 171.71 | 150.27 | 0.00 | 0.00 |
April | 390.73 | 141.64 | 339.95 | 147.60 | 192.35 | 0.00 | 0.00 |
May | 356.19 | 125.50 | 310.84 | 92.60 | 218.24 | 0.00 | 0.00 |
June | 330.14 | 101.85 | 284.39 | 76.35 | 208.03 | 0.00 | 0.00 |
July | 393.95 | 93.11 | 310.14 | 113.59 | 196.55 | 0.00 | 0.00 |
August | 435.21 | 91.58 | 333.21 | 155.38 | 177.83 | 0.00 | 0.00 |
September | 454.17 | 125.25 | 369.18 | 203.87 | 165.31 | 0.00 | 0.00 |
October | 381.87 | 156.75 | 334.41 | 206.48 | 127.94 | 0.00 | 0.00 |
November | 194.03 | 182.05 | 197.72 | 113.31 | 84.41 | 0.00 | 0.00 |
December | 206.85 | 224.37 | 206.87 | 133.87 | 73.00 | 0.00 | 0.00 |
Annual Sum or Average | 332.03 | 151.57 | 291.76 | 142.71 | 149.06 | 0.00 | 0.00 |
Minimum of Months | 177.77 | 91.58 | 194.64 | 76.35 | 73.00 | 0.00 | 0.00 |
Maximum of Months | 454.17 | 224.37 | 369.18 | 206.48 | 218.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 359.82 | 425.46 | 389.27 | 231.15 | 158.12 | 0.00 | 0.00 |
February | 628.88 | 375.89 | 598.64 | 370.57 | 228.07 | 0.00 | 0.00 |
March | 708.50 | 321.05 | 643.96 | 343.42 | 300.54 | 0.00 | 0.00 |
April | 789.41 | 271.67 | 679.90 | 295.21 | 384.69 | 0.00 | 0.00 |
May | 720.55 | 240.81 | 621.68 | 185.21 | 436.48 | 0.00 | 0.00 |
June | 664.98 | 197.07 | 568.78 | 152.71 | 416.07 | 0.00 | 0.00 |
July | 790.42 | 180.94 | 620.28 | 227.18 | 393.10 | 0.00 | 0.00 |
August | 872.41 | 177.64 | 666.41 | 310.76 | 355.65 | 0.00 | 0.00 |
September | 912.60 | 243.25 | 738.36 | 407.74 | 330.61 | 0.00 | 0.00 |
October | 770.25 | 301.08 | 668.83 | 412.95 | 255.88 | 0.00 | 0.00 |
November | 392.39 | 352.33 | 395.43 | 226.62 | 168.82 | 0.00 | 0.00 |
December | 417.26 | 436.29 | 413.73 | 267.74 | 145.99 | 0.00 | 0.00 |
Annual Sum or Average | 669.06 | 293.25 | 583.52 | 285.41 | 298.11 | 0.00 | 0.00 |
Minimum of Months | 359.82 | 177.64 | 389.27 | 152.71 | 145.99 | 0.00 | 0.00 |
Maximum of Months | 912.60 | 436.29 | 738.36 | 412.95 | 436.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 179.10 | 214.25 | 194.64 | 115.58 | 79.06 | 0.00 | 0.00 |
February | 313.34 | 189.04 | 299.32 | 185.28 | 114.04 | 0.00 | 0.00 |
March | 352.81 | 161.87 | 321.98 | 171.71 | 150.27 | 0.00 | 0.00 |
April | 392.62 | 137.32 | 339.95 | 147.60 | 192.35 | 0.00 | 0.00 |
May | 357.85 | 122.00 | 310.84 | 92.60 | 218.24 | 0.00 | 0.00 |
June | 331.08 | 99.00 | 284.39 | 76.35 | 208.03 | 0.00 | 0.00 |
July | 394.47 | 90.27 | 310.14 | 113.59 | 196.55 | 0.00 | 0.00 |
August | 435.56 | 88.48 | 333.21 | 155.38 | 177.83 | 0.00 | 0.00 |
September | 454.88 | 122.38 | 369.18 | 203.87 | 165.31 | 0.00 | 0.00 |
October | 383.20 | 152.52 | 334.41 | 206.48 | 127.94 | 0.00 | 0.00 |
November | 195.30 | 177.56 | 197.72 | 113.31 | 84.41 | 0.00 | 0.00 |
December | 207.97 | 219.51 | 206.87 | 133.87 | 73.00 | 0.00 | 0.00 |
Annual Sum or Average | 333.23 | 147.66 | 291.76 | 142.71 | 149.06 | 0.00 | 0.00 |
Minimum of Months | 179.10 | 88.48 | 194.64 | 76.35 | 73.00 | 0.00 | 0.00 |
Maximum of Months | 454.88 | 219.51 | 369.18 | 206.48 | 218.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 179.29 | 213.37 | 194.64 | 115.58 | 79.06 | 0.00 | 0.00 |
February | 313.67 | 188.15 | 299.32 | 185.28 | 114.04 | 0.00 | 0.00 |
March | 353.19 | 160.97 | 321.98 | 171.71 | 150.27 | 0.00 | 0.00 |
April | 393.07 | 136.58 | 339.95 | 147.60 | 192.35 | 0.00 | 0.00 |
May | 358.32 | 121.39 | 310.84 | 92.60 | 218.24 | 0.00 | 0.00 |
June | 331.40 | 98.57 | 284.39 | 76.35 | 208.03 | 0.00 | 0.00 |
July | 394.73 | 89.87 | 310.14 | 113.59 | 196.55 | 0.00 | 0.00 |
August | 435.78 | 88.11 | 333.21 | 155.38 | 177.83 | 0.00 | 0.00 |
September | 455.11 | 121.94 | 369.18 | 203.87 | 165.31 | 0.00 | 0.00 |
October | 383.50 | 151.86 | 334.41 | 206.48 | 127.94 | 0.00 | 0.00 |
November | 195.55 | 176.71 | 197.72 | 113.31 | 84.41 | 0.00 | 0.00 |
December | 208.17 | 218.61 | 206.87 | 133.87 | 73.00 | 0.00 | 0.00 |
Annual Sum or Average | 333.53 | 146.99 | 291.76 | 142.71 | 149.06 | 0.00 | 0.00 |
Minimum of Months | 179.29 | 88.11 | 194.64 | 76.35 | 73.00 | 0.00 | 0.00 |
Maximum of Months | 455.11 | 218.61 | 369.18 | 206.48 | 218.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 180.04 | 209.47 | 194.64 | 115.58 | 79.06 | 0.00 | 0.00 |
February | 314.89 | 184.40 | 299.32 | 185.28 | 114.04 | 0.00 | 0.00 |
March | 354.71 | 156.95 | 321.98 | 171.71 | 150.27 | 0.00 | 0.00 |
April | 394.98 | 132.94 | 339.95 | 147.60 | 192.35 | 0.00 | 0.00 |
May | 360.65 | 117.99 | 310.84 | 92.60 | 218.24 | 0.00 | 0.00 |
June | 332.78 | 96.55 | 284.39 | 76.35 | 208.03 | 0.00 | 0.00 |
July | 395.56 | 88.43 | 310.14 | 113.59 | 196.55 | 0.00 | 0.00 |
August | 436.41 | 86.88 | 333.21 | 155.38 | 177.83 | 0.00 | 0.00 |
September | 456.28 | 119.65 | 369.18 | 203.87 | 165.31 | 0.00 | 0.00 |
October | 385.01 | 148.14 | 334.41 | 206.48 | 127.94 | 0.00 | 0.00 |
November | 196.53 | 173.10 | 197.72 | 113.31 | 84.41 | 0.00 | 0.00 |
December | 208.93 | 214.79 | 206.87 | 133.87 | 73.00 | 0.00 | 0.00 |
Annual Sum or Average | 334.78 | 143.92 | 291.76 | 142.71 | 149.06 | 0.00 | 0.00 |
Minimum of Months | 180.04 | 86.88 | 194.64 | 76.35 | 73.00 | 0.00 | 0.00 |
Maximum of Months | 456.28 | 214.79 | 369.18 | 206.48 | 218.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 182.70 | 194.36 | 194.64 | 115.58 | 79.06 | 0.00 | 0.00 |
February | 318.83 | 170.24 | 299.32 | 185.28 | 114.04 | 0.00 | 0.00 |
March | 358.99 | 142.99 | 321.98 | 171.71 | 150.27 | 0.00 | 0.00 |
April | 399.56 | 120.95 | 339.95 | 147.60 | 192.35 | 0.00 | 0.00 |
May | 366.13 | 107.19 | 310.84 | 92.60 | 218.24 | 0.00 | 0.00 |
June | 336.36 | 89.00 | 284.39 | 76.35 | 208.03 | 0.00 | 0.00 |
July | 397.72 | 82.64 | 310.14 | 113.59 | 196.55 | 0.00 | 0.00 |
August | 437.84 | 81.83 | 333.21 | 155.38 | 177.83 | 0.00 | 0.00 |
September | 459.33 | 111.74 | 369.18 | 203.87 | 165.31 | 0.00 | 0.00 |
October | 388.81 | 136.58 | 334.41 | 206.48 | 127.94 | 0.00 | 0.00 |
November | 199.40 | 160.76 | 197.72 | 113.31 | 84.41 | 0.00 | 0.00 |
December | 211.41 | 200.39 | 206.87 | 133.87 | 73.00 | 0.00 | 0.00 |
Annual Sum or Average | 338.13 | 133.06 | 291.76 | 142.71 | 149.06 | 0.00 | 0.00 |
Minimum of Months | 182.70 | 81.83 | 194.64 | 76.35 | 73.00 | 0.00 | 0.00 |
Maximum of Months | 459.33 | 200.39 | 369.18 | 206.48 | 218.24 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.963182E+09 | 0.117319E+10 | 0.104477E+10 | 0.620386E+09 | 0.424379E+09 | 0.00 | 0.00 |
February | 0.152152E+10 | 0.927951E+09 | 0.145120E+10 | 0.898314E+09 | 0.552889E+09 | 0.00 | 0.00 |
March | 0.190198E+10 | 0.866658E+09 | 0.172833E+10 | 0.921701E+09 | 0.806632E+09 | 0.00 | 0.00 |
April | 0.205128E+10 | 0.708221E+09 | 0.176593E+10 | 0.766756E+09 | 0.999171E+09 | 0.00 | 0.00 |
May | 0.193897E+10 | 0.638313E+09 | 0.166854E+10 | 0.497074E+09 | 0.117146E+10 | 0.00 | 0.00 |
June | 0.173357E+10 | 0.501144E+09 | 0.147731E+10 | 0.396638E+09 | 0.108067E+10 | 0.00 | 0.00 |
July | 0.212747E+10 | 0.472321E+09 | 0.166477E+10 | 0.609727E+09 | 0.105504E+10 | 0.00 | 0.00 |
August | 0.234728E+10 | 0.461842E+09 | 0.178858E+10 | 0.834046E+09 | 0.954537E+09 | 0.00 | 0.00 |
September | 0.237352E+10 | 0.623587E+09 | 0.191775E+10 | 0.105905E+10 | 0.858706E+09 | 0.00 | 0.00 |
October | 0.206703E+10 | 0.811841E+09 | 0.179506E+10 | 0.110832E+10 | 0.686745E+09 | 0.00 | 0.00 |
November | 0.101520E+10 | 0.934428E+09 | 0.102707E+10 | 0.588595E+09 | 0.438471E+09 | 0.00 | 0.00 |
December | 0.111758E+10 | 0.119404E+10 | 0.111043E+10 | 0.718600E+09 | 0.391825E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.211586E+11 | 0.931354E+10 | 0.184397E+11 | 0.901920E+10 | 0.942053E+10 | 0.00 | 0.00 |
Minimum of Months | 0.963182E+09 | 0.461842E+09 | 0.102707E+10 | 0.396638E+09 | 0.391825E+09 | 0.00 | 0.00 |
Maximum of Months | 0.237352E+10 | 0.119404E+10 | 0.191775E+10 | 0.110832E+10 | 0.117146E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.473057E+09 | 0.624757E+09 | 0.522383E+09 | 0.310193E+09 | 0.212190E+09 | 0.00 | 0.00 |
February | 0.749137E+09 | 0.497321E+09 | 0.725601E+09 | 0.449157E+09 | 0.276444E+09 | 0.00 | 0.00 |
March | 0.934251E+09 | 0.477785E+09 | 0.864166E+09 | 0.460850E+09 | 0.403316E+09 | 0.00 | 0.00 |
April | 0.100487E+10 | 0.390343E+09 | 0.882964E+09 | 0.383378E+09 | 0.499586E+09 | 0.00 | 0.00 |
May | 0.950340E+09 | 0.343669E+09 | 0.834269E+09 | 0.248537E+09 | 0.585732E+09 | 0.00 | 0.00 |
June | 0.856410E+09 | 0.261495E+09 | 0.738653E+09 | 0.198319E+09 | 0.540334E+09 | 0.00 | 0.00 |
July | 0.105831E+10 | 0.241126E+09 | 0.832384E+09 | 0.304863E+09 | 0.527521E+09 | 0.00 | 0.00 |
August | 0.116895E+10 | 0.234991E+09 | 0.894292E+09 | 0.417023E+09 | 0.477269E+09 | 0.00 | 0.00 |
September | 0.117784E+10 | 0.323378E+09 | 0.958876E+09 | 0.529523E+09 | 0.429353E+09 | 0.00 | 0.00 |
October | 0.101683E+10 | 0.443270E+09 | 0.897532E+09 | 0.554160E+09 | 0.343372E+09 | 0.00 | 0.00 |
November | 0.497603E+09 | 0.503760E+09 | 0.513533E+09 | 0.294298E+09 | 0.219235E+09 | 0.00 | 0.00 |
December | 0.550908E+09 | 0.635390E+09 | 0.555213E+09 | 0.359300E+09 | 0.195913E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.104385E+11 | 0.497728E+10 | 0.921987E+10 | 0.450960E+10 | 0.471026E+10 | 0.00 | 0.00 |
Minimum of Months | 0.473057E+09 | 0.234991E+09 | 0.513533E+09 | 0.198319E+09 | 0.195913E+09 | 0.00 | 0.00 |
Maximum of Months | 0.117784E+10 | 0.635390E+09 | 0.958876E+09 | 0.554160E+09 | 0.585732E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.473590E+09 | 0.603352E+09 | 0.521311E+09 | 0.309557E+09 | 0.211754E+09 | 0.00 | 0.00 |
February | 0.750153E+09 | 0.480458E+09 | 0.724113E+09 | 0.448236E+09 | 0.275877E+09 | 0.00 | 0.00 |
March | 0.935577E+09 | 0.461127E+09 | 0.862394E+09 | 0.459905E+09 | 0.402488E+09 | 0.00 | 0.00 |
April | 0.100576E+10 | 0.381522E+09 | 0.881152E+09 | 0.382591E+09 | 0.498561E+09 | 0.00 | 0.00 |
May | 0.948572E+09 | 0.345226E+09 | 0.832557E+09 | 0.248027E+09 | 0.584530E+09 | 0.00 | 0.00 |
June | 0.853415E+09 | 0.268293E+09 | 0.737138E+09 | 0.197912E+09 | 0.539225E+09 | 0.00 | 0.00 |
July | 0.105398E+10 | 0.252017E+09 | 0.830677E+09 | 0.304238E+09 | 0.526439E+09 | 0.00 | 0.00 |
August | 0.116480E+10 | 0.247442E+09 | 0.892457E+09 | 0.416168E+09 | 0.476290E+09 | 0.00 | 0.00 |
September | 0.117497E+10 | 0.329951E+09 | 0.956909E+09 | 0.528437E+09 | 0.428472E+09 | 0.00 | 0.00 |
October | 0.101705E+10 | 0.435665E+09 | 0.895691E+09 | 0.553023E+09 | 0.342668E+09 | 0.00 | 0.00 |
November | 0.499170E+09 | 0.486795E+09 | 0.512480E+09 | 0.293694E+09 | 0.218786E+09 | 0.00 | 0.00 |
December | 0.551620E+09 | 0.615371E+09 | 0.554074E+09 | 0.358563E+09 | 0.195511E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.104287E+11 | 0.490722E+10 | 0.920095E+10 | 0.450035E+10 | 0.470060E+10 | 0.00 | 0.00 |
Minimum of Months | 0.473590E+09 | 0.247442E+09 | 0.512480E+09 | 0.197912E+09 | 0.195511E+09 | 0.00 | 0.00 |
Maximum of Months | 0.117497E+10 | 0.615371E+09 | 0.956909E+09 | 0.553023E+09 | 0.584530E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.474802E+09 | 0.594416E+09 | 0.521311E+09 | 0.309557E+09 | 0.211754E+09 | 0.00 | 0.00 |
February | 0.751953E+09 | 0.473367E+09 | 0.724113E+09 | 0.448236E+09 | 0.275877E+09 | 0.00 | 0.00 |
March | 0.938024E+09 | 0.452790E+09 | 0.862394E+09 | 0.459905E+09 | 0.402488E+09 | 0.00 | 0.00 |
April | 0.100873E+10 | 0.374602E+09 | 0.881152E+09 | 0.382591E+09 | 0.498561E+09 | 0.00 | 0.00 |
May | 0.950278E+09 | 0.341806E+09 | 0.832557E+09 | 0.248027E+09 | 0.584530E+09 | 0.00 | 0.00 |
June | 0.853955E+09 | 0.267049E+09 | 0.737138E+09 | 0.197912E+09 | 0.539225E+09 | 0.00 | 0.00 |
July | 0.105412E+10 | 0.251727E+09 | 0.830677E+09 | 0.304238E+09 | 0.526439E+09 | 0.00 | 0.00 |
August | 0.116477E+10 | 0.247574E+09 | 0.892457E+09 | 0.416168E+09 | 0.476290E+09 | 0.00 | 0.00 |
September | 0.117553E+10 | 0.328305E+09 | 0.956909E+09 | 0.528437E+09 | 0.428472E+09 | 0.00 | 0.00 |
October | 0.101941E+10 | 0.428392E+09 | 0.895691E+09 | 0.553023E+09 | 0.342668E+09 | 0.00 | 0.00 |
November | 0.500934E+09 | 0.478705E+09 | 0.512480E+09 | 0.293694E+09 | 0.218786E+09 | 0.00 | 0.00 |
December | 0.552783E+09 | 0.607248E+09 | 0.554074E+09 | 0.358563E+09 | 0.195511E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.104453E+11 | 0.484598E+10 | 0.920095E+10 | 0.450035E+10 | 0.470060E+10 | 0.00 | 0.00 |
Minimum of Months | 0.474802E+09 | 0.247574E+09 | 0.512480E+09 | 0.197912E+09 | 0.195511E+09 | 0.00 | 0.00 |
Maximum of Months | 0.117553E+10 | 0.607248E+09 | 0.956909E+09 | 0.553023E+09 | 0.584530E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.476134E+09 | 0.587601E+09 | 0.521311E+09 | 0.309557E+09 | 0.211754E+09 | 0.00 | 0.00 |
February | 0.753852E+09 | 0.467888E+09 | 0.724113E+09 | 0.448236E+09 | 0.275877E+09 | 0.00 | 0.00 |
March | 0.940793E+09 | 0.445285E+09 | 0.862394E+09 | 0.459905E+09 | 0.402488E+09 | 0.00 | 0.00 |
April | 0.101278E+10 | 0.367136E+09 | 0.881152E+09 | 0.382591E+09 | 0.498561E+09 | 0.00 | 0.00 |
May | 0.954010E+09 | 0.336143E+09 | 0.832557E+09 | 0.248027E+09 | 0.584530E+09 | 0.00 | 0.00 |
June | 0.855723E+09 | 0.263985E+09 | 0.737138E+09 | 0.197912E+09 | 0.539225E+09 | 0.00 | 0.00 |
July | 0.105515E+10 | 0.249387E+09 | 0.830677E+09 | 0.304238E+09 | 0.526439E+09 | 0.00 | 0.00 |
August | 0.116565E+10 | 0.245284E+09 | 0.892457E+09 | 0.416168E+09 | 0.476290E+09 | 0.00 | 0.00 |
September | 0.117720E+10 | 0.324655E+09 | 0.956909E+09 | 0.528437E+09 | 0.428472E+09 | 0.00 | 0.00 |
October | 0.102281E+10 | 0.419849E+09 | 0.895691E+09 | 0.553023E+09 | 0.342668E+09 | 0.00 | 0.00 |
November | 0.502927E+09 | 0.471866E+09 | 0.512480E+09 | 0.293694E+09 | 0.218786E+09 | 0.00 | 0.00 |
December | 0.554016E+09 | 0.600953E+09 | 0.554074E+09 | 0.358563E+09 | 0.195511E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.104710E+11 | 0.478003E+10 | 0.920095E+10 | 0.450035E+10 | 0.470060E+10 | 0.00 | 0.00 |
Minimum of Months | 0.476134E+09 | 0.245284E+09 | 0.512480E+09 | 0.197912E+09 | 0.195511E+09 | 0.00 | 0.00 |
Maximum of Months | 0.117720E+10 | 0.600953E+09 | 0.956909E+09 | 0.553023E+09 | 0.584530E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.963730E+09 | 0.113956E+10 | 0.104262E+10 | 0.619114E+09 | 0.423508E+09 | 0.00 | 0.00 |
February | 0.152139E+10 | 0.909346E+09 | 0.144823E+10 | 0.896471E+09 | 0.551754E+09 | 0.00 | 0.00 |
March | 0.189764E+10 | 0.859909E+09 | 0.172479E+10 | 0.919810E+09 | 0.804977E+09 | 0.00 | 0.00 |
April | 0.204615E+10 | 0.704166E+09 | 0.176230E+10 | 0.765183E+09 | 0.997122E+09 | 0.00 | 0.00 |
May | 0.192993E+10 | 0.644989E+09 | 0.166511E+10 | 0.496055E+09 | 0.116906E+10 | 0.00 | 0.00 |
June | 0.172362E+10 | 0.510808E+09 | 0.147428E+10 | 0.395824E+09 | 0.107845E+10 | 0.00 | 0.00 |
July | 0.211707E+10 | 0.484632E+09 | 0.166135E+10 | 0.608476E+09 | 0.105288E+10 | 0.00 | 0.00 |
August | 0.233667E+10 | 0.475786E+09 | 0.178491E+10 | 0.832335E+09 | 0.952579E+09 | 0.00 | 0.00 |
September | 0.236545E+10 | 0.630514E+09 | 0.191382E+10 | 0.105687E+10 | 0.856945E+09 | 0.00 | 0.00 |
October | 0.206305E+10 | 0.806412E+09 | 0.179138E+10 | 0.110605E+10 | 0.685336E+09 | 0.00 | 0.00 |
November | 0.101708E+10 | 0.913238E+09 | 0.102496E+10 | 0.587388E+09 | 0.437571E+09 | 0.00 | 0.00 |
December | 0.111759E+10 | 0.116855E+10 | 0.110815E+10 | 0.717126E+09 | 0.391021E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.210994E+11 | 0.924791E+10 | 0.184019E+11 | 0.900070E+10 | 0.940120E+10 | 0.00 | 0.00 |
Minimum of Months | 0.963730E+09 | 0.475786E+09 | 0.102496E+10 | 0.395824E+09 | 0.391021E+09 | 0.00 | 0.00 |
Maximum of Months | 0.236545E+10 | 0.116855E+10 | 0.191382E+10 | 0.110605E+10 | 0.116906E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.479701E+09 | 0.573847E+09 | 0.521311E+09 | 0.309557E+09 | 0.211754E+09 | 0.00 | 0.00 |
February | 0.758038E+09 | 0.457314E+09 | 0.724113E+09 | 0.448236E+09 | 0.275877E+09 | 0.00 | 0.00 |
March | 0.944979E+09 | 0.433547E+09 | 0.862394E+09 | 0.459905E+09 | 0.402488E+09 | 0.00 | 0.00 |
April | 0.101768E+10 | 0.355944E+09 | 0.881152E+09 | 0.382591E+09 | 0.498561E+09 | 0.00 | 0.00 |
May | 0.958477E+09 | 0.326770E+09 | 0.832557E+09 | 0.248027E+09 | 0.584530E+09 | 0.00 | 0.00 |
June | 0.858149E+09 | 0.256607E+09 | 0.737138E+09 | 0.197912E+09 | 0.539225E+09 | 0.00 | 0.00 |
July | 0.105654E+10 | 0.241783E+09 | 0.830677E+09 | 0.304238E+09 | 0.526439E+09 | 0.00 | 0.00 |
August | 0.116660E+10 | 0.236985E+09 | 0.892457E+09 | 0.416168E+09 | 0.476290E+09 | 0.00 | 0.00 |
September | 0.117905E+10 | 0.317213E+09 | 0.956909E+09 | 0.528437E+09 | 0.428472E+09 | 0.00 | 0.00 |
October | 0.102635E+10 | 0.408518E+09 | 0.895691E+09 | 0.553023E+09 | 0.342668E+09 | 0.00 | 0.00 |
November | 0.506206E+09 | 0.460228E+09 | 0.512480E+09 | 0.293694E+09 | 0.218786E+09 | 0.00 | 0.00 |
December | 0.557019E+09 | 0.587928E+09 | 0.554074E+09 | 0.358563E+09 | 0.195511E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.105088E+11 | 0.465668E+10 | 0.920095E+10 | 0.450035E+10 | 0.470060E+10 | 0.00 | 0.00 |
Minimum of Months | 0.479701E+09 | 0.236985E+09 | 0.512480E+09 | 0.197912E+09 | 0.195511E+09 | 0.00 | 0.00 |
Maximum of Months | 0.117905E+10 | 0.587928E+09 | 0.956909E+09 | 0.553023E+09 | 0.584530E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.480215E+09 | 0.571499E+09 | 0.521311E+09 | 0.309557E+09 | 0.211754E+09 | 0.00 | 0.00 |
February | 0.758825E+09 | 0.455170E+09 | 0.724113E+09 | 0.448236E+09 | 0.275877E+09 | 0.00 | 0.00 |
March | 0.945996E+09 | 0.431134E+09 | 0.862394E+09 | 0.459905E+09 | 0.402488E+09 | 0.00 | 0.00 |
April | 0.101883E+10 | 0.354005E+09 | 0.881152E+09 | 0.382591E+09 | 0.498561E+09 | 0.00 | 0.00 |
May | 0.959716E+09 | 0.325119E+09 | 0.832557E+09 | 0.248027E+09 | 0.584530E+09 | 0.00 | 0.00 |
June | 0.858985E+09 | 0.255482E+09 | 0.737138E+09 | 0.197912E+09 | 0.539225E+09 | 0.00 | 0.00 |
July | 0.105724E+10 | 0.240701E+09 | 0.830677E+09 | 0.304238E+09 | 0.526439E+09 | 0.00 | 0.00 |
August | 0.116720E+10 | 0.235993E+09 | 0.892457E+09 | 0.416168E+09 | 0.476290E+09 | 0.00 | 0.00 |
September | 0.117965E+10 | 0.316070E+09 | 0.956909E+09 | 0.528437E+09 | 0.428472E+09 | 0.00 | 0.00 |
October | 0.102716E+10 | 0.406737E+09 | 0.895691E+09 | 0.553023E+09 | 0.342668E+09 | 0.00 | 0.00 |
November | 0.506854E+09 | 0.458033E+09 | 0.512480E+09 | 0.293694E+09 | 0.218786E+09 | 0.00 | 0.00 |
December | 0.557559E+09 | 0.585518E+09 | 0.554074E+09 | 0.358563E+09 | 0.195511E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.105182E+11 | 0.463546E+10 | 0.920095E+10 | 0.450035E+10 | 0.470060E+10 | 0.00 | 0.00 |
Minimum of Months | 0.480215E+09 | 0.235993E+09 | 0.512480E+09 | 0.197912E+09 | 0.195511E+09 | 0.00 | 0.00 |
Maximum of Months | 0.117965E+10 | 0.585518E+09 | 0.956909E+09 | 0.553023E+09 | 0.584530E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.482212E+09 | 0.561057E+09 | 0.521311E+09 | 0.309557E+09 | 0.211754E+09 | 0.00 | 0.00 |
February | 0.761793E+09 | 0.446107E+09 | 0.724113E+09 | 0.448236E+09 | 0.275877E+09 | 0.00 | 0.00 |
March | 0.950053E+09 | 0.420363E+09 | 0.862394E+09 | 0.459905E+09 | 0.402488E+09 | 0.00 | 0.00 |
April | 0.102379E+10 | 0.344578E+09 | 0.881152E+09 | 0.382591E+09 | 0.498561E+09 | 0.00 | 0.00 |
May | 0.965962E+09 | 0.316014E+09 | 0.832557E+09 | 0.248027E+09 | 0.584530E+09 | 0.00 | 0.00 |
June | 0.862570E+09 | 0.250256E+09 | 0.737138E+09 | 0.197912E+09 | 0.539225E+09 | 0.00 | 0.00 |
July | 0.105946E+10 | 0.236854E+09 | 0.830677E+09 | 0.304238E+09 | 0.526439E+09 | 0.00 | 0.00 |
August | 0.116889E+10 | 0.232702E+09 | 0.892457E+09 | 0.416168E+09 | 0.476290E+09 | 0.00 | 0.00 |
September | 0.118268E+10 | 0.310136E+09 | 0.956909E+09 | 0.528437E+09 | 0.428472E+09 | 0.00 | 0.00 |
October | 0.103121E+10 | 0.396777E+09 | 0.895691E+09 | 0.553023E+09 | 0.342668E+09 | 0.00 | 0.00 |
November | 0.509407E+09 | 0.448665E+09 | 0.512480E+09 | 0.293694E+09 | 0.218786E+09 | 0.00 | 0.00 |
December | 0.559594E+09 | 0.575283E+09 | 0.554074E+09 | 0.358563E+09 | 0.195511E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.105576E+11 | 0.453879E+10 | 0.920095E+10 | 0.450035E+10 | 0.470060E+10 | 0.00 | 0.00 |
Minimum of Months | 0.482212E+09 | 0.232702E+09 | 0.512480E+09 | 0.197912E+09 | 0.195511E+09 | 0.00 | 0.00 |
Maximum of Months | 0.118268E+10 | 0.575283E+09 | 0.956909E+09 | 0.553023E+09 | 0.584530E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.489337E+09 | 0.520577E+09 | 0.521311E+09 | 0.309557E+09 | 0.211754E+09 | 0.00 | 0.00 |
February | 0.771305E+09 | 0.411838E+09 | 0.724113E+09 | 0.448236E+09 | 0.275877E+09 | 0.00 | 0.00 |
March | 0.961525E+09 | 0.382974E+09 | 0.862394E+09 | 0.459905E+09 | 0.402488E+09 | 0.00 | 0.00 |
April | 0.103567E+10 | 0.313498E+09 | 0.881152E+09 | 0.382591E+09 | 0.498561E+09 | 0.00 | 0.00 |
May | 0.980632E+09 | 0.287095E+09 | 0.832557E+09 | 0.248027E+09 | 0.584530E+09 | 0.00 | 0.00 |
June | 0.871839E+09 | 0.230689E+09 | 0.737138E+09 | 0.197912E+09 | 0.539225E+09 | 0.00 | 0.00 |
July | 0.106527E+10 | 0.221332E+09 | 0.830677E+09 | 0.304238E+09 | 0.526439E+09 | 0.00 | 0.00 |
August | 0.117272E+10 | 0.219183E+09 | 0.892457E+09 | 0.416168E+09 | 0.476290E+09 | 0.00 | 0.00 |
September | 0.119059E+10 | 0.289630E+09 | 0.956909E+09 | 0.528437E+09 | 0.428472E+09 | 0.00 | 0.00 |
October | 0.104139E+10 | 0.365809E+09 | 0.895691E+09 | 0.553023E+09 | 0.342668E+09 | 0.00 | 0.00 |
November | 0.516843E+09 | 0.416684E+09 | 0.512480E+09 | 0.293694E+09 | 0.218786E+09 | 0.00 | 0.00 |
December | 0.566247E+09 | 0.536716E+09 | 0.554074E+09 | 0.358563E+09 | 0.195511E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.106634E+11 | 0.419602E+10 | 0.920095E+10 | 0.450035E+10 | 0.470060E+10 | 0.00 | 0.00 |
Minimum of Months | 0.489337E+09 | 0.219183E+09 | 0.512480E+09 | 0.197912E+09 | 0.195511E+09 | 0.00 | 0.00 |
Maximum of Months | 0.119059E+10 | 0.536716E+09 | 0.956909E+09 | 0.553023E+09 | 0.584530E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.50 | 3.10 | 1.22 | 3.91 | -4.2 | 29.50 | 44.23 | 0.00 |
February | 5.82 | 4.07 | 1.77 | 3.94 | -3.8 | 43.80 | 82.64 | 0.00 |
March | 8.33 | 5.86 | 2.94 | 3.85 | -1.4 | 65.55 | 100.60 | 0.02 |
April | 10.85 | 8.04 | 5.25 | 4.23 | 1.22 | 89.73 | 150.02 | 0.00 |
May | 12.97 | 10.02 | 7.49 | 3.85 | 3.75 | 114.98 | 168.60 | 0.00 |
June | 15.59 | 11.80 | 8.88 | 4.02 | 5.93 | 107.53 | 199.74 | 0.01 |
July | 17.66 | 13.41 | 10.38 | 3.76 | 8.02 | 92.25 | 247.81 | 0.00 |
August | 18.80 | 14.57 | 11.86 | 3.84 | 8.90 | 79.20 | 215.47 | 0.01 |
September | 15.09 | 12.55 | 10.74 | 2.23 | 5.47 | 68.06 | 162.11 | 0.01 |
October | 11.43 | 9.19 | 7.19 | 4.02 | 2.10 | 48.18 | 106.36 | 0.04 |
November | 8.07 | 6.72 | 5.29 | 3.86 | 0.13 | 33.26 | 46.10 | 0.00 |
December | 5.42 | 4.09 | 2.46 | 3.51 | -3.8 | 24.03 | 50.49 | 0.04 |
Annual Sum or Average | 11.24 | 8.64 | 6.31 | 3.75 | 1.89 | 66.43 | 131.49 | 0.01 |
Minimum of Months | 4.50 | 3.10 | 1.22 | 2.23 | -4.2 | 24.03 | 44.23 | 0.00 |
Maximum of Months | 18.80 | 14.57 | 11.86 | 4.23 | 8.90 | 114.98 | 247.81 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.40 | 11-JAN-14:20 | 10.49 | 7.20 | 8.40 | 3.89 | 99.17 | 130.33 |
February | 20.00 | 27-FEB-14:00 | 12.17 | 5.60 | 2.60 | 5.54 | 87.00 | 691.00 |
March | 20.60 | 18-MAR-15:00 | 10.43 | 0.00 | 6.20 | 6.55 | 111.50 | 465.50 |
April | 27.20 | 27-APR-15:09 | 17.22 | 11.02 | 4.10 | 12.63 | 151.33 | 598.33 |
May | 25.00 | 05-MAY-15:00 | 17.36 | 12.80 | 2.60 | 18.99 | 208.50 | 29.50 |
June | 26.70 | 28-JUN-16:00 | 16.74 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 30.60 | 24-JUL-14:00 | 18.78 | 12.20 | 3.10 | 20.75 | 267.00 | 383.50 |
August | 31.80 | 10-AUG-16:00 | 18.70 | 11.10 | 2.60 | 16.85 | 50.50 | 750.50 |
September | 25.00 | 14-SEP-16:00 | 16.69 | 11.70 | 3.10 | 13.54 | 100.50 | 235.00 |
October | 21.70 | 04-OCT-14:00 | 11.49 | 1.70 | 5.20 | 4.92 | 56.50 | 783.50 |
November | 21.10 | 04-NOV-13:00 | 15.94 | 12.80 | 0.00 | 6.95 | 52.50 | 729.00 |
December | 13.30 | 14-DEC-11:00 | 8.44 | 3.60 | 13.90 | 5.33 | 127.50 | 85.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 8.44 | 0.00 | 0.00 | 3.89 | 50.50 | 29.50 | |
Maximum of Months | 31.80 | 18.78 | 12.80 | 13.90 | 20.75 | 267.00 | 783.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -3.9 | 07-JAN-07:00 | -3.9 | -3.9 | 2.10 | -14.4 | 0.00 | 0.00 |
February | -5.6 | 19-FEB-05:10 | -6.1 | -7.3 | 3.77 | -22.8 | 0.00 | 0.00 |
March | -0.6 | 01-MAR-06:00 | -2.0 | -3.9 | 1.50 | -17.3 | 16.50 | 102.00 |
April | 1.70 | 19-APR-04:00 | 1.21 | 0.60 | 3.10 | -11.9 | 0.00 | 0.00 |
May | 4.40 | 11-MAY-02:00 | 3.92 | 3.30 | 3.10 | -10.9 | 0.00 | 0.00 |
June | 8.30 | 15-JUN-02:00 | 7.50 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
July | 11.10 | 03-JUL-03:00 | 8.19 | 5.00 | 2.60 | 5.54 | 0.00 | 0.00 |
August | 11.00 | 06-AUG-04:00 | 10.57 | 10.20 | 2.60 | -3.2 | 11.00 | 135.50 |
September | 7.20 | 27-SEP-04:49 | 6.72 | 6.20 | 0.25 | -4.0 | 0.00 | 0.00 |
October | 5.60 | 13-OCT-04:00 | 4.51 | 3.30 | 2.10 | -8.5 | 0.00 | 0.00 |
November | 0.00 | 11-NOV-06:00 | -0.2 | -0.6 | 2.10 | -16.0 | 0.00 | 0.00 |
December | -1.7 | 26-DEC-06:00 | -1.7 | -1.7 | 2.10 | -15.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -6.1 | -7.3 | 0.25 | -22.8 | 0.00 | 0.00 | |
Maximum of Months | 11.10 | 10.57 | 10.20 | 3.77 | 5.54 | 16.50 | 135.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.49 | 11-JAN-13:00 | 14.40 | 7.20 | 8.20 | 2.85 | 105.50 | 249.00 |
February | 12.42 | 27-FEB-15:00 | 19.40 | 6.70 | 2.60 | 6.35 | 88.00 | 342.50 |
March | 12.45 | 09-MAR-11:00 | 17.20 | 8.90 | 2.10 | 12.41 | 178.00 | 40.00 |
April | 17.29 | 27-APR-14:00 | 27.20 | 11.10 | 4.10 | 12.41 | 147.50 | 646.00 |
May | 17.58 | 06-MAY-12:00 | 23.90 | 13.90 | 5.20 | 15.57 | 365.50 | 282.50 |
June | 16.74 | 28-JUN-16:00 | 26.70 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 19.18 | 31-JUL-15:00 | 28.90 | 13.90 | 4.10 | 14.65 | 45.00 | 848.50 |
August | 20.13 | 29-AUG-12:00 | 28.90 | 15.70 | 2.60 | 17.39 | 136.50 | 655.00 |
September | 17.97 | 23-SEP-13:00 | 23.30 | 15.00 | 2.10 | 9.72 | 148.00 | 670.50 |
October | 15.15 | 01-OCT-11:00 | 17.20 | 13.90 | 4.60 | 13.73 | 236.50 | 63.50 |
November | 16.05 | 04-NOV-12:00 | 20.60 | 13.30 | 0.00 | 7.95 | 62.00 | 746.50 |
December | 10.71 | 16-DEC-11:00 | 11.70 | 10.00 | 6.70 | 7.35 | 89.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.49 | 11.70 | 6.70 | 0.00 | 2.85 | 45.00 | 0.00 | |
Maximum of Months | 20.13 | 28.90 | 15.70 | 8.20 | 17.39 | 365.50 | 848.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.00 | 11-JAN-21:00 | 11.10 | 10.49 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 11.70 | 24-FEB-00:00 | 12.80 | 12.15 | 4.10 | 8.74 | 0.00 | 0.00 |
March | 11.70 | 09-MAR-16:00 | 12.80 | 12.15 | 2.10 | 8.74 | 37.50 | 0.00 |
April | 12.80 | 28-APR-12:00 | 16.70 | 14.35 | 4.10 | 8.35 | 265.50 | 596.00 |
May | 13.90 | 05-MAY-16:00 | 22.80 | 17.10 | 2.60 | 19.17 | 111.50 | 27.50 |
June | 13.90 | 12-JUN-12:00 | 16.70 | 15.00 | 3.60 | 13.16 | 263.50 | 0.00 |
July | 15.00 | 11-JUL-09:20 | 16.13 | 15.49 | 4.60 | 12.91 | 204.17 | 28.17 |
August | 16.40 | 30-AUG-07:00 | 17.40 | 16.77 | 5.20 | 12.41 | 168.50 | 34.50 |
September | 15.00 | 14-SEP-11:20 | 20.37 | 16.93 | 2.10 | 6.89 | 152.83 | 748.17 |
October | 13.90 | 01-OCT-10:00 | 16.70 | 15.01 | 4.10 | 13.16 | 184.50 | 0.00 |
November | 13.90 | 03-NOV-19:00 | 15.00 | 14.31 | 4.60 | 11.46 | 0.00 | 0.00 |
December | 10.00 | 16-DEC-10:00 | 11.10 | 10.48 | 7.70 | 6.75 | 81.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 11.10 | 10.48 | 2.10 | 6.75 | 0.00 | 0.00 | |
Maximum of Months | 16.40 | 22.80 | 17.10 | 7.70 | 19.17 | 265.50 | 748.17 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.48 | 8.35 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 11.14 | 14.81 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 11.69 | 23.26 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 12.99 | 36.00 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 14.72 | 45.46 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.40 | 49.26 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.58 | 51.50 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 17.95 | 42.11 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.39 | 30.76 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 16.06 | 18.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 14.32 | 9.65 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.65 | 7.39 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 14.55 | 28.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 11.14 | 7.39 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 17.95 | 51.50 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.357790E+09 | -233292547.1 | 0.00 | 0.00 | 744.00 | 0.00 | -124496995.7 | 58.99 | 0.00 | 0.00 |
February | 0.325209E+09 | -213320233.7 | 0.00 | 0.00 | 672.00 | 0.00 | -111888915.6 | 58.99 | 0.00 | 0.00 |
March | 0.360171E+09 | -237334404.6 | 0.00 | 0.00 | 744.00 | 0.00 | -122836534.6 | 58.99 | 0.00 | 0.00 |
April | 0.336811E+09 | -220454043.8 | 0.00 | 0.00 | 720.00 | 0.00 | -116357016.0 | 59.00 | 0.00 | 0.00 |
May | 0.336326E+09 | -219628056.3 | 0.00 | 0.00 | 744.00 | 0.00 | -116697886.8 | 58.99 | 0.00 | 0.00 |
June | 0.317039E+09 | -206542790.4 | 0.00 | 0.00 | 720.00 | 0.00 | -110496582.4 | 58.99 | 0.00 | 0.00 |
July | 0.316368E+09 | -203268797.8 | 0.00 | 0.00 | 744.00 | 0.00 | -113098752.0 | 58.99 | 0.00 | 0.00 |
August | 0.318667E+09 | -205768620.5 | 0.00 | 0.00 | 744.00 | 0.00 | -112898480.7 | 58.99 | 0.00 | 0.00 |
September | 0.310053E+09 | -199578770.7 | 0.00 | 0.00 | 720.00 | 0.00 | -110473900.7 | 58.99 | 0.00 | 0.00 |
October | 0.329663E+09 | -210824539.2 | 0.00 | 0.00 | 744.00 | 0.00 | -118838390.5 | 58.99 | 0.00 | 0.00 |
November | 0.330278E+09 | -211652896.2 | 0.00 | 0.00 | 720.00 | 0.00 | -118625595.7 | 58.99 | 0.00 | 0.00 |
December | 0.351926E+09 | -227815095.8 | 0.00 | 0.00 | 744.00 | 0.00 | -124111357.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.399030E+10 | -0.258948E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.140082E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.310053E+09 | -237334404.6 | 0.00 | 0.00 | 672.00 | 0.00 | -124496995.7 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.360171E+09 | -199578770.7 | 0.00 | 0.00 | 744.00 | 0.00 | -110473900.7 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.355559E+09 | -233294084.0 | 0.00 | 0.00 | 744.00 | 0.00 | -122264685.0 | 58.99 | 0.00 | 0.00 |
February | 0.322764E+09 | -213320820.7 | 0.00 | 0.00 | 672.00 | 0.00 | -109443088.4 | 58.99 | 0.00 | 0.00 |
March | 0.356384E+09 | -237335750.0 | 0.00 | 0.00 | 744.00 | 0.00 | -119048385.4 | 58.99 | 0.00 | 0.00 |
April | 0.333173E+09 | -220454202.3 | 0.00 | 0.00 | 720.00 | 0.00 | -112718402.4 | 58.99 | 0.00 | 0.00 |
May | 0.333639E+09 | -219624694.8 | 0.00 | 0.00 | 744.00 | 0.00 | -114013911.6 | 58.99 | 0.00 | 0.00 |
June | 0.315914E+09 | -206543316.4 | 0.00 | 0.00 | 720.00 | 0.00 | -109370595.6 | 58.99 | 0.00 | 0.00 |
July | 0.315857E+09 | -203268883.3 | 0.00 | 0.00 | 744.00 | 0.00 | -112588563.2 | 58.99 | 0.00 | 0.00 |
August | 0.318270E+09 | -205769524.0 | 0.00 | 0.00 | 744.00 | 0.00 | -112500412.1 | 58.99 | 0.00 | 0.00 |
September | 0.308870E+09 | -199579381.7 | 0.00 | 0.00 | 720.00 | 0.00 | -109290647.0 | 58.99 | 0.00 | 0.00 |
October | 0.326191E+09 | -210818429.7 | 0.00 | 0.00 | 744.00 | 0.00 | -115372252.1 | 58.99 | 0.00 | 0.00 |
November | 0.327501E+09 | -211652430.7 | 0.00 | 0.00 | 720.00 | 0.00 | -115848241.4 | 58.99 | 0.00 | 0.00 |
December | 0.349551E+09 | -227816340.1 | 0.00 | 0.00 | 744.00 | 0.00 | -121734875.6 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.396367E+10 | -0.258948E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.137419E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.308870E+09 | -237335750.0 | 0.00 | 0.00 | 672.00 | 0.00 | -122264685.0 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.356384E+09 | -199579381.7 | 0.00 | 0.00 | 744.00 | 0.00 | -109290647.0 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.329226E+09 | -205145689.6 | 0.00 | 0.00 | 744.00 | 0.00 | -124080669.9 | 59.00 | 0.00 | 0.00 |
February | 0.298826E+09 | -187766579.4 | 0.00 | 0.00 | 672.00 | 0.00 | -111059561.4 | 58.98 | 0.00 | 0.00 |
March | 0.332677E+09 | -211844823.5 | 0.00 | 0.00 | 744.00 | 0.00 | -120832494.1 | 58.98 | 0.00 | 0.00 |
April | 0.307695E+09 | -193895037.7 | 0.00 | 0.00 | 720.00 | 0.00 | -113800303.6 | 58.99 | 0.00 | 0.00 |
May | 0.308762E+09 | -194783005.7 | 0.00 | 0.00 | 744.00 | 0.00 | -113978499.3 | 58.99 | 0.00 | 0.00 |
June | 0.292643E+09 | -183961284.7 | 0.00 | 0.00 | 720.00 | 0.00 | -108681578.0 | 58.99 | 0.00 | 0.00 |
July | 0.289122E+09 | -177695301.7 | 0.00 | 0.00 | 744.00 | 0.00 | -111426274.9 | 59.00 | 0.00 | 0.00 |
August | 0.295029E+09 | -183778052.8 | 0.00 | 0.00 | 744.00 | 0.00 | -111250576.0 | 59.00 | 0.00 | 0.00 |
September | 0.284134E+09 | -175397529.8 | 0.00 | 0.00 | 720.00 | 0.00 | -108736337.7 | 59.00 | 0.00 | 0.00 |
October | 0.301720E+09 | -185403340.4 | 0.00 | 0.00 | 744.00 | 0.00 | -116316851.3 | 58.99 | 0.00 | 0.00 |
November | 0.304401E+09 | -186875589.5 | 0.00 | 0.00 | 720.00 | 0.00 | -117525167.2 | 58.99 | 0.00 | 0.00 |
December | 0.322417E+09 | -198834759.5 | 0.00 | 0.00 | 744.00 | 0.00 | -123581757.8 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.366665E+10 | -0.228538E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.138127E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.284134E+09 | -211844823.5 | 0.00 | 0.00 | 672.00 | 0.00 | -124080669.9 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.332677E+09 | -175397529.8 | 0.00 | 0.00 | 744.00 | 0.00 | -108681578.0 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.329691E+09 | -205162623.1 | 0.00 | 0.00 | 744.00 | 0.00 | -124527979.6 | 58.99 | 0.00 | 0.00 |
February | 0.299270E+09 | -187717928.5 | 0.00 | 0.00 | 672.00 | 0.00 | -111552226.8 | 59.00 | 0.00 | 0.00 |
March | 0.333226E+09 | -211877793.3 | 0.00 | 0.00 | 744.00 | 0.00 | -121347987.1 | 58.97 | 0.00 | 0.00 |
April | 0.308250E+09 | -193885327.6 | 0.00 | 0.00 | 720.00 | 0.00 | -114364224.9 | 59.00 | 0.00 | 0.00 |
May | 0.309030E+09 | -194789130.1 | 0.00 | 0.00 | 744.00 | 0.00 | -114240406.4 | 58.99 | 0.00 | 0.00 |
June | 0.292725E+09 | -183964028.9 | 0.00 | 0.00 | 720.00 | 0.00 | -108760684.1 | 58.99 | 0.00 | 0.00 |
July | 0.289138E+09 | -177697725.9 | 0.00 | 0.00 | 744.00 | 0.00 | -111440198.7 | 58.99 | 0.00 | 0.00 |
August | 0.295022E+09 | -183791804.1 | 0.00 | 0.00 | 744.00 | 0.00 | -111230629.4 | 58.99 | 0.00 | 0.00 |
September | 0.284250E+09 | -175377258.9 | 0.00 | 0.00 | 720.00 | 0.00 | -108872281.1 | 59.00 | 0.00 | 0.00 |
October | 0.302255E+09 | -185400572.1 | 0.00 | 0.00 | 744.00 | 0.00 | -116854336.4 | 58.99 | 0.00 | 0.00 |
November | 0.304893E+09 | -186891803.4 | 0.00 | 0.00 | 720.00 | 0.00 | -118001478.7 | 58.99 | 0.00 | 0.00 |
December | 0.322839E+09 | -198837690.4 | 0.00 | 0.00 | 744.00 | 0.00 | -124001701.8 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.367059E+10 | -0.228539E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.138519E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.284250E+09 | -211877793.3 | 0.00 | 0.00 | 672.00 | 0.00 | -124527979.6 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.333226E+09 | -175377258.9 | 0.00 | 0.00 | 744.00 | 0.00 | -108760684.1 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.319850E+09 | -193896292.8 | 0.00 | 0.00 | 744.00 | 0.00 | -125954180.5 | 59.00 | 0.00 | 0.00 |
February | 0.290373E+09 | -177537577.8 | 0.00 | 0.00 | 672.00 | 0.00 | -112835604.1 | 58.99 | 0.00 | 0.00 |
March | 0.323646E+09 | -200431684.7 | 0.00 | 0.00 | 744.00 | 0.00 | -123214589.0 | 58.99 | 0.00 | 0.00 |
April | 0.299993E+09 | -183474948.1 | 0.00 | 0.00 | 720.00 | 0.00 | -116517921.9 | 58.99 | 0.00 | 0.00 |
May | 0.300537E+09 | -184207790.6 | 0.00 | 0.00 | 744.00 | 0.00 | -116329138.3 | 58.99 | 0.00 | 0.00 |
June | 0.283960E+09 | -174033306.4 | 0.00 | 0.00 | 720.00 | 0.00 | -109926698.1 | 59.00 | 0.00 | 0.00 |
July | 0.280316E+09 | -168097666.0 | 0.00 | 0.00 | 744.00 | 0.00 | -112218726.6 | 58.98 | 0.00 | 0.00 |
August | 0.285950E+09 | -173912381.1 | 0.00 | 0.00 | 744.00 | 0.00 | -112037386.8 | 58.99 | 0.00 | 0.00 |
September | 0.276097E+09 | -165964582.0 | 0.00 | 0.00 | 720.00 | 0.00 | -110132460.6 | 59.00 | 0.00 | 0.00 |
October | 0.294269E+09 | -175219124.0 | 0.00 | 0.00 | 744.00 | 0.00 | -119049697.0 | 59.00 | 0.00 | 0.00 |
November | 0.296019E+09 | -176511180.4 | 0.00 | 0.00 | 720.00 | 0.00 | -119507526.5 | 58.99 | 0.00 | 0.00 |
December | 0.313336E+09 | -188083355.5 | 0.00 | 0.00 | 744.00 | 0.00 | -125252549.4 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.356435E+10 | -0.216137E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.140298E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.276097E+09 | -200431684.7 | 0.00 | 0.00 | 672.00 | 0.00 | -125954180.5 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.323646E+09 | -165964582.0 | 0.00 | 0.00 | 744.00 | 0.00 | -109926698.1 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.319732E+09 | -193898394.9 | 0.00 | 0.00 | 744.00 | 0.00 | -125833370.5 | 59.00 | 0.00 | 0.00 |
February | 0.290222E+09 | -177538601.3 | 0.00 | 0.00 | 672.00 | 0.00 | -112683756.0 | 58.99 | 0.00 | 0.00 |
March | 0.323265E+09 | -200431902.8 | 0.00 | 0.00 | 744.00 | 0.00 | -122833583.6 | 58.99 | 0.00 | 0.00 |
April | 0.299413E+09 | -183472243.1 | 0.00 | 0.00 | 720.00 | 0.00 | -115941032.7 | 59.00 | 0.00 | 0.00 |
May | 0.299794E+09 | -184207458.8 | 0.00 | 0.00 | 744.00 | 0.00 | -115586387.4 | 58.99 | 0.00 | 0.00 |
June | 0.283656E+09 | -174036705.5 | 0.00 | 0.00 | 720.00 | 0.00 | -109619122.4 | 59.00 | 0.00 | 0.00 |
July | 0.280240E+09 | -168093781.6 | 0.00 | 0.00 | 744.00 | 0.00 | -112146406.2 | 58.98 | 0.00 | 0.00 |
August | 0.285898E+09 | -173912596.7 | 0.00 | 0.00 | 744.00 | 0.00 | -111985848.6 | 58.99 | 0.00 | 0.00 |
September | 0.275674E+09 | -165991586.9 | 0.00 | 0.00 | 720.00 | 0.00 | -109682578.9 | 58.99 | 0.00 | 0.00 |
October | 0.293601E+09 | -175236636.7 | 0.00 | 0.00 | 744.00 | 0.00 | -118364112.5 | 58.99 | 0.00 | 0.00 |
November | 0.295771E+09 | -176513649.3 | 0.00 | 0.00 | 720.00 | 0.00 | -119257597.2 | 58.99 | 0.00 | 0.00 |
December | 0.313229E+09 | -188073927.5 | 0.00 | 0.00 | 744.00 | 0.00 | -125154949.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.356050E+10 | -0.216141E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.139909E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.275674E+09 | -200431902.8 | 0.00 | 0.00 | 672.00 | 0.00 | -125833370.5 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.323265E+09 | -165991586.9 | 0.00 | 0.00 | 744.00 | 0.00 | -109619122.4 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.319848E+09 | -193896471.8 | 0.00 | 0.00 | 744.00 | 0.00 | -125951906.3 | 59.00 | 0.00 | 0.00 |
February | 0.290345E+09 | -177537348.9 | 0.00 | 0.00 | 672.00 | 0.00 | -112807728.0 | 58.99 | 0.00 | 0.00 |
March | 0.323435E+09 | -200427582.2 | 0.00 | 0.00 | 744.00 | 0.00 | -123007742.5 | 59.00 | 0.00 | 0.00 |
April | 0.299562E+09 | -183483498.4 | 0.00 | 0.00 | 720.00 | 0.00 | -116078378.6 | 58.99 | 0.00 | 0.00 |
May | 0.299953E+09 | -184197465.8 | 0.00 | 0.00 | 744.00 | 0.00 | -115755313.1 | 59.00 | 0.00 | 0.00 |
June | 0.283746E+09 | -174045429.6 | 0.00 | 0.00 | 720.00 | 0.00 | -109700912.0 | 59.00 | 0.00 | 0.00 |
July | 0.280320E+09 | -168098020.3 | 0.00 | 0.00 | 744.00 | 0.00 | -112221978.0 | 58.98 | 0.00 | 0.00 |
August | 0.285965E+09 | -173906979.5 | 0.00 | 0.00 | 744.00 | 0.00 | -112057760.6 | 58.99 | 0.00 | 0.00 |
September | 0.275758E+09 | -165997973.6 | 0.00 | 0.00 | 720.00 | 0.00 | -109759711.1 | 58.99 | 0.00 | 0.00 |
October | 0.293734E+09 | -175242634.1 | 0.00 | 0.00 | 744.00 | 0.00 | -118491618.8 | 58.99 | 0.00 | 0.00 |
November | 0.295896E+09 | -176514137.6 | 0.00 | 0.00 | 720.00 | 0.00 | -119382076.2 | 58.99 | 0.00 | 0.00 |
December | 0.313347E+09 | -188085588.6 | 0.00 | 0.00 | 744.00 | 0.00 | -125260983.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.356191E+10 | -0.216143E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.140048E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.275758E+09 | -200427582.2 | 0.00 | 0.00 | 672.00 | 0.00 | -125951906.3 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.323435E+09 | -165997973.6 | 0.00 | 0.00 | 744.00 | 0.00 | -109700912.0 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 237.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 259.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 247.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 379.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 427.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 375.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 471.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 366.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 301.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 245.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 242.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 160.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3714.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 160.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 471.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.127272E+11 | 57301.67 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.854034E+10 | 57301.67 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.424438E+10 | 57301.67 | 05-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137086E+10 | 57301.67 | 18-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 97741755.11 | 6714.09 | 18-MAY-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2281726.59 | 1827.88 | 28-SEP-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.775364E+09 | 21671.50 | 28-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.627576E+10 | 57301.67 | 13-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.108313E+11 | 57301.67 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.448652E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.127272E+11 | 57301.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.322348E+10 | 29944.47 | 06-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.184916E+10 | 29944.47 | 18-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.391097E+09 | 5431.71 | 05-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 43019629.92 | 4834.34 | 18-APR-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 845243.82 | 761.68 | 30-OCT-08:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.116279E+10 | 5594.67 | 23-NOV-17:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.249436E+10 | 29944.47 | 26-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.916474E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.322348E+10 | 29944.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.422706E+10 | 29902.47 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.255382E+10 | 29902.47 | 18-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.789837E+09 | 8264.87 | 05-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137871E+09 | 4690.71 | 19-APR-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 514473.55 | 638.40 | 18-MAY-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 24431292.71 | 2111.83 | 30-OCT-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.176578E+10 | 12933.41 | 24-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.340887E+10 | 29902.47 | 25-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.129082E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.422706E+10 | 29902.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.446267E+10 | 29976.81 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.271922E+10 | 29976.81 | 13-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.941108E+09 | 12699.58 | 05-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.188167E+09 | 4349.46 | 18-APR-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 894848.76 | 709.81 | 18-MAY-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 50804046.73 | 2817.45 | 30-OCT-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.193502E+10 | 18008.54 | 24-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.362514E+10 | 29976.81 | 25-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.139230E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.446267E+10 | 29976.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.478773E+10 | 29883.64 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.295421E+10 | 29883.64 | 12-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.115853E+10 | 17082.46 | 05-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.274913E+09 | 5524.43 | 19-APR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3085396.44 | 1192.46 | 18-MAY-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.104076E+09 | 3072.75 | 29-OCT-08:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.215542E+10 | 22456.93 | 24-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.392237E+10 | 29883.64 | 18-DEC-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.153603E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.478773E+10 | 29883.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.104365E+11 | 56112.28 | 01-JAN-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.680373E+10 | 56112.28 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.351149E+10 | 56112.28 | 05-MAR-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.117419E+10 | 56112.28 | 11-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 72354128.37 | 6971.45 | 18-MAY-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1263915.80 | 1422.72 | 28-SEP-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.831984E+09 | 25572.47 | 30-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.547869E+10 | 56112.28 | 12-NOV-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.887465E+10 | 56112.28 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.371849E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.104365E+11 | 56112.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.468147E+10 | 28773.87 | 01-JAN-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.290014E+10 | 28773.87 | 05-FEB-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.120170E+10 | 28773.87 | 05-MAR-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.304640E+09 | 19619.66 | 18-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7575175.98 | 2116.54 | 18-MAY-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.163618E+09 | 3570.24 | 30-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.219511E+10 | 28773.87 | 13-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.385753E+10 | 28773.87 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.153118E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.468147E+10 | 28773.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.477585E+10 | 28653.60 | 01-JAN-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.298212E+10 | 28653.60 | 02-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.127316E+10 | 28653.60 | 05-MAR-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.336205E+09 | 22150.91 | 18-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 9258235.41 | 2117.77 | 18-MAY-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.184843E+09 | 5305.08 | 30-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.226248E+10 | 28653.60 | 12-NOV-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.394732E+10 | 28653.60 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.157712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.477585E+10 | 28653.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.518954E+10 | 28487.88 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.332595E+10 | 28487.88 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.158692E+10 | 28487.88 | 05-MAR-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.489907E+09 | 28487.88 | 11-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 25869532.79 | 3465.36 | 18-MAY-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.300548E+09 | 13019.91 | 30-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.255052E+10 | 28487.88 | 12-NOV-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.432740E+10 | 28487.88 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.177966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.518954E+10 | 28487.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.694557E+10 | 30022.53 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.464610E+10 | 30022.53 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.261234E+10 | 30022.53 | 01-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.971250E+09 | 30022.53 | 01-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.165280E+09 | 14101.75 | 18-MAY-08:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1070940.49 | 630.84 | 15-JUN-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 9949362.11 | 2362.62 | 27-SEP-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.696629E+09 | 30022.53 | 28-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.352438E+10 | 30022.53 | 10-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.582509E+10 | 30022.53 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.253977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.694557E+10 | 30022.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 96970.27 | 96970.27 | 161.62 | 18-MAR-16:10 | 161.62 | 0.00 |
April | 0.00 | 0.00 | 0.779497E+09 | 0.745006E+09 | 13255.78 | 27-APR-16:10 | 12694.89 | 0.00 |
May | 0.00 | 0.00 | 0.177811E+10 | 0.157430E+10 | 12256.30 | 06-MAY-13:00 | 9868.57 | 0.00 |
June | 0.00 | 0.00 | 0.327704E+10 | 0.306161E+10 | 23747.71 | 12-JUN-08:62 | 14922.43 | 0.00 |
July | 0.00 | 0.00 | 0.806766E+10 | 0.693788E+10 | 35521.20 | 31-JUL-08:62 | 26846.50 | 0.00 |
August | 0.00 | 0.00 | 0.105353E+11 | 0.907739E+10 | 35655.04 | 29-AUG-08:62 | 25636.99 | 0.00 |
September | 0.00 | 0.00 | 0.338027E+10 | 0.275327E+10 | 31643.46 | 14-SEP-08:62 | 20264.49 | 0.00 |
October | 0.00 | 0.00 | 0.193742E+09 | 0.189934E+09 | 7321.94 | 04-OCT-15:00 | 7321.94 | 0.00 |
November | 0.00 | 0.00 | 32318846.39 | 24106228.82 | 3387.90 | 04-NOV-14:00 | 2564.64 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.280440E+11 | 0.243636E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.105353E+11 | 0.907739E+10 | 35655.04 | 26846.50 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 1337707.27 | 1265340.40 | 1446.85 | 27-FEB-21:10 | 1376.11 | 0.00 |
March | 0.00 | 0.00 | 6766749.09 | 6565911.19 | 1338.58 | 18-MAR-21:30 | 1338.58 | 0.00 |
April | 0.00 | 0.00 | 0.551041E+09 | 0.536808E+09 | 17783.22 | 29-APR-18:01 | 14358.14 | 0.00 |
May | 0.00 | 0.00 | 0.112610E+10 | 0.102754E+10 | 18470.41 | 07-MAY-17:02 | 14657.19 | 0.00 |
June | 0.00 | 0.00 | 0.196768E+10 | 0.188483E+10 | 18206.87 | 11-JUN-18:00 | 15271.05 | 0.00 |
July | 0.00 | 0.00 | 0.459153E+10 | 0.408578E+10 | 18918.98 | 15-JUL-18:02 | 13678.16 | 0.00 |
August | 0.00 | 0.00 | 0.617965E+10 | 0.550455E+10 | 18797.27 | 26-AUG-18:02 | 12471.27 | 0.00 |
September | 0.00 | 0.00 | 0.186224E+10 | 0.158269E+10 | 18648.32 | 23-SEP-18:02 | 13050.97 | 0.00 |
October | 0.00 | 0.00 | 0.116531E+09 | 0.114575E+09 | 17112.36 | 04-OCT-20:01 | 17112.36 | 0.00 |
November | 0.00 | 0.00 | 32241094.12 | 25577445.00 | 2823.54 | 04-NOV-14:00 | 2256.98 | 0.00 |
December | 0.00 | 0.00 | 147431.66 | 147431.66 | 245.72 | 03-DEC-20:20 | 245.72 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.164353E+11 | 0.147703E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.617965E+10 | 0.550455E+10 | 18918.98 | 17112.36 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 27.15 | 27.15 | 0.03 | 27-FEB-13:20 | 0.03 | 0.00 |
March | 0.00 | 0.00 | 41633.12 | 41633.12 | 69.30 | 18-MAR-16:00 | 69.30 | 0.00 |
April | 0.00 | 0.00 | 0.406576E+09 | 0.398068E+09 | 7676.07 | 28-APR-07:03 | 5488.10 | 0.00 |
May | 0.00 | 0.00 | 0.827107E+09 | 0.759466E+09 | 18122.04 | 07-MAY-08:62 | 13051.87 | 0.00 |
June | 0.00 | 0.00 | 0.143186E+10 | 0.138561E+10 | 17907.96 | 12-JUN-07:02 | 12302.45 | 0.00 |
July | 0.00 | 0.00 | 0.336366E+10 | 0.303115E+10 | 18459.59 | 31-JUL-07:01 | 13815.78 | 0.00 |
August | 0.00 | 0.00 | 0.460041E+10 | 0.413498E+10 | 18553.65 | 30-AUG-07:02 | 10847.27 | 0.00 |
September | 0.00 | 0.00 | 0.145795E+10 | 0.124450E+10 | 17930.15 | 01-SEP-07:02 | 11941.90 | 0.00 |
October | 0.00 | 0.00 | 77582926.46 | 76811438.32 | 3998.88 | 04-OCT-15:00 | 3998.88 | 0.00 |
November | 0.00 | 0.00 | 21528381.83 | 16940096.76 | 2350.93 | 04-NOV-14:00 | 1876.59 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.121867E+11 | 0.110476E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.460041E+10 | 0.413498E+10 | 18553.65 | 13815.78 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 18.37 | 18.37 | 0.02 | 27-FEB-17:00 | 0.02 | 0.00 |
March | 0.00 | 0.00 | 20.26 | 20.26 | 0.03 | 14-MAR-16:10 | 0.03 | 0.00 |
April | 0.00 | 0.00 | 0.392551E+09 | 0.384474E+09 | 7328.91 | 27-APR-15:00 | 7203.77 | 0.00 |
May | 0.00 | 0.00 | 0.805418E+09 | 0.739929E+09 | 18171.80 | 07-MAY-08:62 | 13083.06 | 0.00 |
June | 0.00 | 0.00 | 0.140990E+10 | 0.136491E+10 | 17958.02 | 12-JUN-07:02 | 12337.20 | 0.00 |
July | 0.00 | 0.00 | 0.335055E+10 | 0.302009E+10 | 18513.75 | 31-JUL-07:01 | 13869.94 | 0.00 |
August | 0.00 | 0.00 | 0.459937E+10 | 0.413529E+10 | 18606.95 | 30-AUG-07:02 | 10884.71 | 0.00 |
September | 0.00 | 0.00 | 0.144222E+10 | 0.123186E+10 | 17980.27 | 01-SEP-07:02 | 11975.51 | 0.00 |
October | 0.00 | 0.00 | 73139931.76 | 72554882.28 | 3921.50 | 04-OCT-15:00 | 3921.50 | 0.00 |
November | 0.00 | 0.00 | 17592269.78 | 13867318.90 | 2041.19 | 04-NOV-14:00 | 1629.08 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.120907E+11 | 0.109630E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.459937E+10 | 0.413529E+10 | 18606.95 | 13869.94 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 97.70 | 97.70 | 0.06 | 18-MAR-13:30 | 0.06 | 0.00 |
April | 0.00 | 0.00 | 0.367860E+09 | 0.360455E+09 | 7084.56 | 27-APR-16:10 | 6992.98 | 0.00 |
May | 0.00 | 0.00 | 0.753043E+09 | 0.692212E+09 | 18103.34 | 07-MAY-08:62 | 13004.88 | 0.00 |
June | 0.00 | 0.00 | 0.134252E+10 | 0.130034E+10 | 17890.37 | 12-JUN-07:02 | 12265.74 | 0.00 |
July | 0.00 | 0.00 | 0.325077E+10 | 0.292994E+10 | 18445.67 | 31-JUL-07:01 | 13798.83 | 0.00 |
August | 0.00 | 0.00 | 0.447908E+10 | 0.402893E+10 | 18537.54 | 30-AUG-07:02 | 10817.30 | 0.00 |
September | 0.00 | 0.00 | 0.138573E+10 | 0.118406E+10 | 17912.86 | 01-SEP-07:02 | 11905.98 | 0.00 |
October | 0.00 | 0.00 | 66013474.66 | 65675884.81 | 3760.72 | 04-OCT-15:00 | 3760.72 | 0.00 |
November | 0.00 | 0.00 | 12798923.20 | 10103132.42 | 1645.36 | 04-NOV-14:00 | 1311.14 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.116578E+11 | 0.105717E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.447908E+10 | 0.402893E+10 | 18537.54 | 13798.83 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 216840.39 | 216840.39 | 246.40 | 18-MAR-16:00 | 246.40 | 0.00 |
April | 0.00 | 0.00 | 0.614455E+09 | 0.582239E+09 | 12816.91 | 27-APR-15:00 | 11894.66 | 0.00 |
May | 0.00 | 0.00 | 0.132606E+10 | 0.117288E+10 | 18060.12 | 07-MAY-09:02 | 12115.14 | 0.00 |
June | 0.00 | 0.00 | 0.256971E+10 | 0.240144E+10 | 29337.46 | 12-JUN-08:62 | 19026.28 | 0.00 |
July | 0.00 | 0.00 | 0.621235E+10 | 0.532507E+10 | 34709.35 | 31-JUL-08:62 | 26373.53 | 0.00 |
August | 0.00 | 0.00 | 0.839383E+10 | 0.719375E+10 | 34785.00 | 30-AUG-08:62 | 20444.68 | 0.00 |
September | 0.00 | 0.00 | 0.274830E+10 | 0.222424E+10 | 33679.17 | 14-SEP-08:62 | 21541.76 | 0.00 |
October | 0.00 | 0.00 | 0.163874E+09 | 0.160722E+09 | 7314.05 | 04-OCT-15:00 | 7314.05 | 0.00 |
November | 0.00 | 0.00 | 29885288.12 | 22177697.80 | 3507.95 | 04-NOV-14:40 | 2645.48 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.220587E+11 | 0.190827E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.839383E+10 | 0.719375E+10 | 34785.00 | 26373.53 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.98 | 0.98 | 0.00 | 27-FEB-14:30 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 10.43 | 10.43 | 0.02 | 18-MAR-13:30 | 0.02 | 0.00 |
April | 0.00 | 0.00 | 0.348945E+09 | 0.339823E+09 | 7252.67 | 27-APR-15:00 | 6953.07 | 0.00 |
May | 0.00 | 0.00 | 0.692597E+09 | 0.635385E+09 | 15835.99 | 07-MAY-09:02 | 10954.80 | 0.00 |
June | 0.00 | 0.00 | 0.128974E+10 | 0.124911E+10 | 17287.13 | 12-JUN-08:62 | 11368.15 | 0.00 |
July | 0.00 | 0.00 | 0.317124E+10 | 0.284128E+10 | 17967.27 | 31-JUL-08:62 | 13757.66 | 0.00 |
August | 0.00 | 0.00 | 0.443530E+10 | 0.396106E+10 | 18010.17 | 30-AUG-08:62 | 10666.49 | 0.00 |
September | 0.00 | 0.00 | 0.132898E+10 | 0.113245E+10 | 17446.45 | 14-SEP-08:62 | 11204.46 | 0.00 |
October | 0.00 | 0.00 | 64370739.68 | 63975248.02 | 3955.35 | 04-OCT-15:00 | 3955.35 | 0.00 |
November | 0.00 | 0.00 | 13133366.09 | 10330048.95 | 1753.11 | 04-NOV-14:50 | 1397.03 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.113443E+11 | 0.102334E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.443530E+10 | 0.396106E+10 | 18010.17 | 13757.66 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 3.65 | 3.65 | 0.01 | 27-FEB-14:30 | 0.01 | 0.00 |
March | 0.00 | 0.00 | 64.63 | 64.63 | 0.11 | 18-MAR-13:30 | 0.11 | 0.00 |
April | 0.00 | 0.00 | 0.341917E+09 | 0.332978E+09 | 7164.63 | 27-APR-15:00 | 6867.57 | 0.00 |
May | 0.00 | 0.00 | 0.674830E+09 | 0.619170E+09 | 14472.34 | 07-MAY-09:02 | 10023.75 | 0.00 |
June | 0.00 | 0.00 | 0.126184E+10 | 0.122252E+10 | 17210.31 | 12-JUN-08:62 | 11304.47 | 0.00 |
July | 0.00 | 0.00 | 0.312264E+10 | 0.279775E+10 | 17887.91 | 31-JUL-08:62 | 13682.97 | 0.00 |
August | 0.00 | 0.00 | 0.438027E+10 | 0.391215E+10 | 17931.06 | 30-AUG-08:62 | 10607.13 | 0.00 |
September | 0.00 | 0.00 | 0.130622E+10 | 0.111316E+10 | 17369.27 | 14-SEP-08:62 | 11143.45 | 0.00 |
October | 0.00 | 0.00 | 61962724.52 | 61603604.58 | 3885.98 | 04-OCT-15:00 | 3885.98 | 0.00 |
November | 0.00 | 0.00 | 12390727.59 | 9748182.72 | 1692.07 | 04-NOV-14:40 | 1347.50 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.111621E+11 | 0.100691E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.438027E+10 | 0.391215E+10 | 17931.06 | 13682.97 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 3539.00 | 3539.00 | 5.83 | 27-FEB-14:50 | 5.83 | 0.00 |
March | 0.00 | 0.00 | 181.97 | 181.97 | 0.25 | 18-MAR-13:40 | 0.25 | 0.00 |
April | 0.00 | 0.00 | 0.316328E+09 | 0.308162E+09 | 6877.58 | 27-APR-15:00 | 6590.21 | 0.00 |
May | 0.00 | 0.00 | 0.611734E+09 | 0.561434E+09 | 8893.62 | 07-MAY-09:02 | 6232.33 | 0.00 |
June | 0.00 | 0.00 | 0.117492E+10 | 0.114010E+10 | 17102.67 | 12-JUN-08:62 | 11185.94 | 0.00 |
July | 0.00 | 0.00 | 0.298506E+10 | 0.267678E+10 | 17779.46 | 31-JUL-08:62 | 13561.39 | 0.00 |
August | 0.00 | 0.00 | 0.424134E+10 | 0.379082E+10 | 17823.38 | 30-AUG-08:62 | 10505.48 | 0.00 |
September | 0.00 | 0.00 | 0.123630E+10 | 0.105448E+10 | 17263.35 | 14-SEP-08:62 | 11039.19 | 0.00 |
October | 0.00 | 0.00 | 53268704.49 | 53078680.60 | 3632.26 | 04-OCT-15:00 | 3632.26 | 0.00 |
November | 0.00 | 0.00 | 9035111.65 | 7120946.95 | 1379.07 | 04-NOV-14:50 | 1097.64 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.106280E+11 | 0.959198E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.424134E+10 | 0.379082E+10 | 17823.38 | 13561.39 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 499.83 | 499.83 | 0.52 | 18-MAR-14:10 | 0.52 | 0.00 |
April | 0.00 | 0.00 | 0.296268E+09 | 0.288832E+09 | 6908.75 | 27-APR-15:00 | 6600.04 | 0.00 |
May | 0.00 | 0.00 | 0.551403E+09 | 0.506599E+09 | 6546.18 | 06-MAY-13:30 | 5497.07 | 0.00 |
June | 0.00 | 0.00 | 0.110804E+10 | 0.107610E+10 | 7311.75 | 28-JUN-08:62 | 6469.45 | 0.00 |
July | 0.00 | 0.00 | 0.292202E+10 | 0.262568E+10 | 18815.18 | 31-JUL-08:62 | 14313.03 | 0.00 |
August | 0.00 | 0.00 | 0.431761E+10 | 0.386077E+10 | 18860.87 | 30-AUG-08:62 | 10938.33 | 0.00 |
September | 0.00 | 0.00 | 0.119154E+10 | 0.101420E+10 | 16174.60 | 10-SEP-09:02 | 12083.52 | 0.00 |
October | 0.00 | 0.00 | 40327504.11 | 40326955.87 | 3109.06 | 04-OCT-15:00 | 3109.06 | 0.00 |
November | 0.00 | 0.00 | 4443922.43 | 3508755.09 | 855.80 | 04-NOV-14:40 | 678.96 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.104316E+11 | 0.941602E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.431761E+10 | 0.386077E+10 | 18860.87 | 14313.03 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.183163E+10 | 0.41 | 2131.15 | 01-JAN-09:01 | 0.89 |
February | 0.159075E+10 | 0.40 | 2131.15 | 01-FEB-09:01 | 0.89 |
March | 0.164767E+10 | 0.38 | 2131.15 | 05-MAR-09:02 | 0.89 |
April | 0.152822E+10 | 0.37 | 2131.15 | 18-APR-08:61 | 0.89 |
May | 0.154888E+10 | 0.36 | 1002.28 | 18-MAY-08:07 | 0.60 |
June | 0.150385E+10 | 0.37 | 1349.10 | 12-JUN-08:62 | 0.70 |
July | 0.154854E+10 | 0.36 | 2131.15 | 20-JUL-08:62 | 0.88 |
August | 0.156169E+10 | 0.36 | 2131.15 | 08-AUG-08:62 | 0.88 |
September | 0.150103E+10 | 0.36 | 1924.07 | 14-SEP-08:62 | 0.84 |
October | 0.156400E+10 | 0.37 | 1336.06 | 28-OCT-08:62 | 0.71 |
November | 0.163479E+10 | 0.39 | 2131.15 | 13-NOV-09:01 | 0.89 |
December | 0.179526E+10 | 0.40 | 2131.15 | 01-DEC-09:01 | 0.89 |
Annual Sum or Average | 0.192563E+11 | 0.38 | |||
Minimum of Months | 0.150103E+10 | 0.36 | 1002.28 | 0.60 | |
Maximum of Months | 0.183163E+10 | 0.41 | 2131.15 | 0.89 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.158263E+10 | 0.47 | 1166.10 | 01-JAN-09:01 | 0.92 |
February | 0.143812E+10 | 0.49 | 1166.10 | 01-FEB-09:04 | 0.92 |
March | 0.164239E+10 | 0.54 | 1166.10 | 03-MAR-09:50 | 0.92 |
April | 0.168574E+10 | 0.60 | 1166.10 | 01-APR-12:30 | 0.92 |
May | 0.192684E+10 | 0.62 | 1166.10 | 03-MAY-10:30 | 0.91 |
June | 0.196033E+10 | 0.61 | 1166.10 | 01-JUN-08:63 | 0.92 |
July | 0.201705E+10 | 0.60 | 1166.10 | 01-JUL-13:10 | 0.92 |
August | 0.197650E+10 | 0.59 | 1166.10 | 01-AUG-16:00 | 0.91 |
September | 0.198027E+10 | 0.61 | 1166.10 | 01-SEP-11:10 | 0.91 |
October | 0.180338E+10 | 0.61 | 1166.10 | 01-OCT-09:20 | 0.91 |
November | 0.159128E+10 | 0.51 | 1166.10 | 04-NOV-16:20 | 0.91 |
December | 0.157443E+10 | 0.47 | 1166.10 | 01-DEC-09:09 | 0.92 |
Annual Sum or Average | 0.211790E+11 | 0.56 | |||
Minimum of Months | 0.143812E+10 | 0.47 | 1166.10 | 0.91 | |
Maximum of Months | 0.201705E+10 | 0.62 | 1166.10 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.168459E+10 | 0.50 | 1164.04 | 06-JAN-14:20 | 0.92 |
February | 0.152535E+10 | 0.50 | 1164.04 | 04-FEB-16:50 | 0.92 |
March | 0.171812E+10 | 0.51 | 1164.04 | 06-MAR-20:10 | 0.92 |
April | 0.163431E+10 | 0.50 | 1164.04 | 01-APR-07:20 | 0.92 |
May | 0.170135E+10 | 0.50 | 1164.04 | 03-MAY-10:15 | 0.92 |
June | 0.165945E+10 | 0.50 | 1164.04 | 16-JUN-15:50 | 0.92 |
July | 0.167621E+10 | 0.49 | 1164.04 | 05-JUL-08:62 | 0.92 |
August | 0.171812E+10 | 0.50 | 1164.04 | 01-AUG-14:50 | 0.91 |
September | 0.163431E+10 | 0.50 | 1164.04 | 01-SEP-07:15 | 0.91 |
October | 0.168459E+10 | 0.50 | 1164.04 | 03-OCT-14:50 | 0.92 |
November | 0.163431E+10 | 0.50 | 1164.04 | 15-NOV-08:50 | 0.92 |
December | 0.167621E+10 | 0.49 | 1164.04 | 01-DEC-15:20 | 0.92 |
Annual Sum or Average | 0.199469E+11 | 0.50 | |||
Minimum of Months | 0.152535E+10 | 0.49 | 1164.04 | 0.91 | |
Maximum of Months | 0.171812E+10 | 0.51 | 1164.04 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.168988E+10 | 0.50 | 1167.69 | 04-JAN-18:40 | 0.92 |
February | 0.153014E+10 | 0.50 | 1167.69 | 05-FEB-13:40 | 0.92 |
March | 0.172351E+10 | 0.51 | 1167.69 | 07-MAR-12:20 | 0.92 |
April | 0.163943E+10 | 0.50 | 1167.69 | 11-APR-08:10 | 0.92 |
May | 0.170669E+10 | 0.50 | 1167.69 | 15-MAY-08:50 | 0.92 |
June | 0.166466E+10 | 0.50 | 1167.69 | 17-JUN-09:30 | 0.91 |
July | 0.168147E+10 | 0.49 | 1167.69 | 01-JUL-06:10 | 0.91 |
August | 0.172351E+10 | 0.50 | 1167.69 | 10-AUG-17:00 | 0.91 |
September | 0.163943E+10 | 0.50 | 1167.69 | 01-SEP-06:10 | 0.91 |
October | 0.168988E+10 | 0.50 | 1167.69 | 01-OCT-07:10 | 0.91 |
November | 0.163943E+10 | 0.50 | 1167.69 | 11-NOV-10:40 | 0.92 |
December | 0.168147E+10 | 0.49 | 1167.69 | 01-DEC-09:30 | 0.92 |
Annual Sum or Average | 0.200095E+11 | 0.50 | |||
Minimum of Months | 0.153014E+10 | 0.49 | 1167.69 | 0.91 | |
Maximum of Months | 0.172351E+10 | 0.51 | 1167.69 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.168325E+10 | 0.50 | 1163.11 | 01-JAN-11:05 | 0.92 |
February | 0.152414E+10 | 0.50 | 1163.11 | 01-FEB-10:50 | 0.92 |
March | 0.171675E+10 | 0.51 | 1163.11 | 01-MAR-08:15 | 0.92 |
April | 0.163301E+10 | 0.50 | 1163.11 | 04-APR-08:00 | 0.92 |
May | 0.170000E+10 | 0.50 | 1163.11 | 03-MAY-16:30 | 0.92 |
June | 0.165813E+10 | 0.50 | 1163.11 | 02-JUN-13:10 | 0.92 |
July | 0.167488E+10 | 0.49 | 1163.11 | 01-JUL-14:40 | 0.91 |
August | 0.171675E+10 | 0.50 | 1163.11 | 02-AUG-11:10 | 0.91 |
September | 0.163301E+10 | 0.50 | 1163.11 | 01-SEP-07:30 | 0.91 |
October | 0.168325E+10 | 0.50 | 1163.11 | 04-OCT-11:00 | 0.92 |
November | 0.163301E+10 | 0.50 | 1163.11 | 02-NOV-08:05 | 0.92 |
December | 0.167488E+10 | 0.49 | 1163.11 | 01-DEC-09:01 | 0.92 |
Annual Sum or Average | 0.199311E+11 | 0.50 | |||
Minimum of Months | 0.152414E+10 | 0.49 | 1163.11 | 0.91 | |
Maximum of Months | 0.171675E+10 | 0.51 | 1163.11 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.133992E+10 | 0.30 | 2074.70 | 01-JAN-10:01 | 0.89 |
February | 0.115476E+10 | 0.29 | 2074.70 | 01-FEB-09:01 | 0.89 |
March | 0.121019E+10 | 0.29 | 2074.70 | 05-MAR-10:01 | 0.89 |
April | 0.110158E+10 | 0.27 | 2074.70 | 11-APR-08:61 | 0.89 |
May | 0.112196E+10 | 0.27 | 984.54 | 18-MAY-08:10 | 0.60 |
June | 0.109370E+10 | 0.27 | 1774.06 | 12-JUN-08:62 | 0.82 |
July | 0.110574E+10 | 0.27 | 2074.70 | 20-JUL-08:62 | 0.88 |
August | 0.114268E+10 | 0.27 | 2074.70 | 07-AUG-08:62 | 0.88 |
September | 0.107637E+10 | 0.27 | 2074.70 | 10-SEP-09:02 | 0.88 |
October | 0.112685E+10 | 0.27 | 1397.19 | 30-OCT-08:62 | 0.73 |
November | 0.119707E+10 | 0.29 | 2074.70 | 12-NOV-10:01 | 0.89 |
December | 0.129929E+10 | 0.30 | 2074.70 | 01-DEC-09:01 | 0.89 |
Annual Sum or Average | 0.139701E+11 | 0.28 | |||
Minimum of Months | 0.107637E+10 | 0.27 | 984.54 | 0.60 | |
Maximum of Months | 0.133992E+10 | 0.30 | 2074.70 | 0.89 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.148892E+10 | 0.46 | 1114.79 | 01-JAN-10:20 | 0.92 |
February | 0.134845E+10 | 0.46 | 1114.79 | 01-FEB-09:20 | 0.92 |
March | 0.152102E+10 | 0.47 | 1114.79 | 01-MAR-10:40 | 0.92 |
April | 0.144477E+10 | 0.46 | 1114.79 | 01-APR-12:30 | 0.92 |
May | 0.150497E+10 | 0.46 | 1114.79 | 03-MAY-14:00 | 0.92 |
June | 0.146885E+10 | 0.47 | 1114.79 | 02-JUN-08:63 | 0.92 |
July | 0.148089E+10 | 0.45 | 1114.79 | 04-JUL-11:10 | 0.92 |
August | 0.152102E+10 | 0.47 | 1114.79 | 01-AUG-14:20 | 0.91 |
September | 0.144477E+10 | 0.46 | 1114.79 | 02-SEP-17:00 | 0.92 |
October | 0.148892E+10 | 0.46 | 1114.79 | 01-OCT-09:15 | 0.91 |
November | 0.144477E+10 | 0.46 | 1114.79 | 01-NOV-08:50 | 0.92 |
December | 0.148089E+10 | 0.46 | 1114.79 | 01-DEC-11:10 | 0.92 |
Annual Sum or Average | 0.176383E+11 | 0.46 | |||
Minimum of Months | 0.134845E+10 | 0.45 | 1114.79 | 0.91 | |
Maximum of Months | 0.152102E+10 | 0.47 | 1114.79 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.148153E+10 | 0.46 | 1109.26 | 09-JAN-11:50 | 0.92 |
February | 0.134177E+10 | 0.46 | 1109.26 | 01-FEB-17:20 | 0.92 |
March | 0.151348E+10 | 0.47 | 1109.26 | 17-MAR-11:10 | 0.92 |
April | 0.143761E+10 | 0.46 | 1109.26 | 17-APR-10:30 | 0.92 |
May | 0.149751E+10 | 0.46 | 1109.26 | 01-MAY-07:05 | 0.92 |
June | 0.146157E+10 | 0.47 | 1109.26 | 01-JUN-07:03 | 0.91 |
July | 0.147355E+10 | 0.45 | 1109.26 | 03-JUL-13:50 | 0.92 |
August | 0.151348E+10 | 0.47 | 1109.26 | 13-AUG-09:10 | 0.91 |
September | 0.143761E+10 | 0.46 | 1109.26 | 23-SEP-10:00 | 0.91 |
October | 0.148153E+10 | 0.46 | 1109.26 | 03-OCT-14:40 | 0.92 |
November | 0.143761E+10 | 0.46 | 1109.26 | 12-NOV-15:30 | 0.92 |
December | 0.147355E+10 | 0.46 | 1109.26 | 03-DEC-12:50 | 0.92 |
Annual Sum or Average | 0.175508E+11 | 0.46 | |||
Minimum of Months | 0.134177E+10 | 0.45 | 1109.26 | 0.91 | |
Maximum of Months | 0.151348E+10 | 0.47 | 1109.26 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.147247E+10 | 0.46 | 1102.48 | 01-JAN-10:05 | 0.92 |
February | 0.133355E+10 | 0.46 | 1102.48 | 01-FEB-11:50 | 0.92 |
March | 0.150422E+10 | 0.47 | 1102.48 | 23-MAR-12:20 | 0.92 |
April | 0.142881E+10 | 0.46 | 1102.48 | 11-APR-16:10 | 0.92 |
May | 0.148834E+10 | 0.46 | 1102.48 | 03-MAY-14:50 | 0.92 |
June | 0.145262E+10 | 0.47 | 1102.48 | 02-JUN-15:00 | 0.92 |
July | 0.146453E+10 | 0.45 | 1102.48 | 01-JUL-13:20 | 0.92 |
August | 0.150422E+10 | 0.47 | 1102.48 | 01-AUG-14:30 | 0.91 |
September | 0.142881E+10 | 0.46 | 1102.48 | 01-SEP-08:40 | 0.91 |
October | 0.147247E+10 | 0.46 | 1102.48 | 03-OCT-15:00 | 0.92 |
November | 0.142881E+10 | 0.46 | 1102.48 | 01-NOV-08:15 | 0.92 |
December | 0.146453E+10 | 0.46 | 1102.48 | 01-DEC-09:05 | 0.92 |
Annual Sum or Average | 0.174434E+11 | 0.46 | |||
Minimum of Months | 0.133355E+10 | 0.45 | 1102.48 | 0.91 | |
Maximum of Months | 0.150422E+10 | 0.47 | 1102.48 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.158541E+10 | 0.46 | 1186.88 | 11-JAN-17:10 | 0.92 |
February | 0.143626E+10 | 0.46 | 1186.88 | 01-FEB-09:20 | 0.92 |
March | 0.161938E+10 | 0.47 | 1186.88 | 02-MAR-19:30 | 0.92 |
April | 0.153820E+10 | 0.46 | 1186.88 | 08-APR-14:10 | 0.92 |
May | 0.160229E+10 | 0.46 | 1186.88 | 02-MAY-09:50 | 0.92 |
June | 0.156383E+10 | 0.47 | 1186.88 | 03-JUN-16:50 | 0.92 |
July | 0.157665E+10 | 0.45 | 1186.88 | 01-JUL-13:10 | 0.92 |
August | 0.161938E+10 | 0.47 | 1186.88 | 22-AUG-19:17 | 0.92 |
September | 0.153820E+10 | 0.46 | 1186.88 | 01-SEP-19:10 | 0.91 |
October | 0.158520E+10 | 0.46 | 1186.88 | 13-OCT-19:50 | 0.92 |
November | 0.153820E+10 | 0.46 | 1186.88 | 06-NOV-16:20 | 0.91 |
December | 0.157665E+10 | 0.46 | 1186.88 | 06-DEC-13:20 | 0.92 |
Annual Sum or Average | 0.187796E+11 | 0.46 | |||
Minimum of Months | 0.143626E+10 | 0.45 | 1186.88 | 0.91 | |
Maximum of Months | 0.161938E+10 | 0.47 | 1186.88 | 0.92 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.183163E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.159075E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.164769E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.173021E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.199743E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.233308E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.353423E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.414225E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.232875E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.161415E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.164354E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.179526E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.261890E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.159075E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.414225E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.158263E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.143844E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.164402E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.180739E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.217012E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.238659E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.299196E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.328277E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.237350E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.182972E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.159875E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.157447E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.246803E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.143844E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.328277E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.168459E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.152535E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.171813E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.172506E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.188300E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.197473E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.240065E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.270217E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.194508E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.170203E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.163932E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.167621E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.225763E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.152535E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.270217E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.168988E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.153014E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.172351E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.172741E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.188389E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.197540E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.240342E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.270756E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.194712E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.170633E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.164356E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.168147E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.226197E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.153014E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.270756E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.168325E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.152414E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.171675E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.171596E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.186630E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.195472E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.237682E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.267676E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.192926E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.169812E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.163604E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.167488E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.224530E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.152414E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.267676E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.133992E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.115476E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.121025E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.126123E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.145842E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.174723E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.264009E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.320140E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.174700E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.116930E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.120511E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.129929E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.194340E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.115476E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.320140E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.148892E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.134845E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.152102E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.152353E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.165787E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.175441E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.216532E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.247136E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.172835E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.150340E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.144787E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.148089E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.200914E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.134845E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.247136E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.148153E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.134177E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.151348E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.151490E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.164668E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.174125E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.214807E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.245263E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.171658E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.149548E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.144054E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.147355E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.199664E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.134177E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.245263E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.147247E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.133356E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.150422E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.150081E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.162428E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.171398E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.211109E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.241504E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.169347E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.148450E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.143096E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.146453E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.197489E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.133356E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.241504E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.158541E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.143626E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.161938E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.160631E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.172599E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.181209E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.221214E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.254665E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.179506E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.159446E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.153927E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.157665E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.210497E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.143626E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.254665E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.183163E+10 | 0.00 | 0.127272E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.159075E+10 | 0.00 | 0.854034E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.164767E+10 | 96970.27 | 0.424438E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152822E+10 | 0.779497E+09 | 0.137086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.154888E+10 | 0.177811E+10 | 97741755.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.150385E+10 | 0.327704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.154854E+10 | 0.806766E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.156169E+10 | 0.105353E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.150103E+10 | 0.338027E+10 | 2281726.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156400E+10 | 0.193742E+09 | 0.775364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163479E+10 | 32318846.39 | 0.627576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.179526E+10 | 0.00 | 0.108313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.192563E+11 | 0.280440E+11 | 0.448652E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.150103E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.183163E+10 | 0.105353E+11 | 0.127272E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.158263E+10 | 0.00 | 0.322348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143812E+10 | 1337707.27 | 0.184916E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.164239E+10 | 6766749.09 | 0.391097E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.168574E+10 | 0.551041E+09 | 43019629.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.192684E+10 | 0.112610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.196033E+10 | 0.196768E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.201705E+10 | 0.459153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.197650E+10 | 0.617965E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.198027E+10 | 0.186224E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.180338E+10 | 0.116531E+09 | 845243.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.159128E+10 | 32241094.12 | 0.116279E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157443E+10 | 147431.66 | 0.249436E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.211790E+11 | 0.164353E+11 | 0.916474E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.143812E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.201705E+10 | 0.617965E+10 | 0.322348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.168459E+10 | 0.00 | 0.422706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152535E+10 | 27.15 | 0.255382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.171812E+10 | 41633.12 | 0.789837E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.163431E+10 | 0.406576E+09 | 0.137871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.170135E+10 | 0.827107E+09 | 514473.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.165945E+10 | 0.143186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.167621E+10 | 0.336366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.171812E+10 | 0.460041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.163431E+10 | 0.145795E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.168459E+10 | 77582926.46 | 24431292.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163431E+10 | 21528381.83 | 0.176578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167621E+10 | 0.00 | 0.340887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.199469E+11 | 0.121867E+11 | 0.129082E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.152535E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.171812E+10 | 0.460041E+10 | 0.422706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.168988E+10 | 0.00 | 0.446267E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.153014E+10 | 18.37 | 0.271922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.172351E+10 | 20.26 | 0.941108E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.163943E+10 | 0.392551E+09 | 0.188167E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.170669E+10 | 0.805418E+09 | 894848.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.166466E+10 | 0.140990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168147E+10 | 0.335055E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.172351E+10 | 0.459937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.163943E+10 | 0.144222E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.168988E+10 | 73139931.76 | 50804046.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163943E+10 | 17592269.78 | 0.193502E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168147E+10 | 0.00 | 0.362514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.200095E+11 | 0.120907E+11 | 0.139230E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.153014E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.172351E+10 | 0.459937E+10 | 0.446267E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.168325E+10 | 0.00 | 0.478773E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152414E+10 | 0.00 | 0.295421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.171675E+10 | 97.70 | 0.115853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.163301E+10 | 0.367860E+09 | 0.274913E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.170000E+10 | 0.753043E+09 | 3085396.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.165813E+10 | 0.134252E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.167488E+10 | 0.325077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.171675E+10 | 0.447908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.163301E+10 | 0.138573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.168325E+10 | 66013474.66 | 0.104076E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163301E+10 | 12798923.20 | 0.215542E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167488E+10 | 0.00 | 0.392237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.199311E+11 | 0.116578E+11 | 0.153603E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.152414E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.171675E+10 | 0.447908E+10 | 0.478773E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.133992E+10 | 0.00 | 0.104365E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.115476E+10 | 0.00 | 0.680373E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.121019E+10 | 216840.39 | 0.351149E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.110158E+10 | 0.614455E+09 | 0.117419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.112196E+10 | 0.132606E+10 | 72354128.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.109370E+10 | 0.256971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.110574E+10 | 0.621235E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.114268E+10 | 0.839383E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.107637E+10 | 0.274830E+10 | 1263915.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.112685E+10 | 0.163874E+09 | 0.831984E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119707E+10 | 29885288.12 | 0.547869E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129929E+10 | 0.00 | 0.887465E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.139701E+11 | 0.220587E+11 | 0.371849E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.107637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.133992E+10 | 0.839383E+10 | 0.104365E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.148892E+10 | 0.00 | 0.468147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134845E+10 | 0.98 | 0.290014E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152102E+10 | 10.43 | 0.120170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144477E+10 | 0.348945E+09 | 0.304640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.150497E+10 | 0.692597E+09 | 7575175.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.146885E+10 | 0.128974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.148089E+10 | 0.317124E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.152102E+10 | 0.443530E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144477E+10 | 0.132898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.148892E+10 | 64370739.68 | 0.163618E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144477E+10 | 13133366.09 | 0.219511E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.148089E+10 | 0.00 | 0.385753E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.176383E+11 | 0.113443E+11 | 0.153118E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.134845E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.152102E+10 | 0.443530E+10 | 0.468147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.148153E+10 | 0.00 | 0.477585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134177E+10 | 3.65 | 0.298212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.151348E+10 | 64.63 | 0.127316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.143761E+10 | 0.341917E+09 | 0.336205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.149751E+10 | 0.674830E+09 | 9258235.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.146157E+10 | 0.126184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147355E+10 | 0.312264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.151348E+10 | 0.438027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.143761E+10 | 0.130622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.148153E+10 | 61962724.52 | 0.184843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.143761E+10 | 12390727.59 | 0.226248E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147355E+10 | 0.00 | 0.394732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175508E+11 | 0.111621E+11 | 0.157712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.134177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.151348E+10 | 0.438027E+10 | 0.477585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.147247E+10 | 0.00 | 0.518954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133355E+10 | 3539.00 | 0.332595E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.150422E+10 | 181.97 | 0.158692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142881E+10 | 0.316328E+09 | 0.489907E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.148834E+10 | 0.611734E+09 | 25869532.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.145262E+10 | 0.117492E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.146453E+10 | 0.298506E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.150422E+10 | 0.424134E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.142881E+10 | 0.123630E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147247E+10 | 53268704.49 | 0.300548E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142881E+10 | 9035111.65 | 0.255052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.146453E+10 | 0.00 | 0.432740E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.174434E+11 | 0.106280E+11 | 0.177966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.150422E+10 | 0.424134E+10 | 0.518954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.158541E+10 | 0.00 | 0.694557E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143626E+10 | 0.00 | 0.464610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161938E+10 | 499.83 | 0.261234E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153820E+10 | 0.296268E+09 | 0.971250E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.160229E+10 | 0.551403E+09 | 0.165280E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.156383E+10 | 0.110804E+10 | 1070940.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.157665E+10 | 0.292202E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.161938E+10 | 0.431761E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.153820E+10 | 0.119154E+10 | 9949362.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.158520E+10 | 40327504.11 | 0.696629E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.153820E+10 | 4443922.43 | 0.352438E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157665E+10 | 0.00 | 0.582509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.187796E+11 | 0.104316E+11 | 0.253977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.143626E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.161938E+10 | 0.431761E+10 | 0.694557E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.183163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.159075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.164767E+10 | 0.00 | 0.00 | 0.00 | 27319.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152822E+10 | 0.00 | 0.00 | 0.00 | 0.201989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.154888E+10 | 0.00 | 0.00 | 0.00 | 0.448546E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.150385E+10 | 0.00 | 0.00 | 0.00 | 0.829226E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.154854E+10 | 0.00 | 0.00 | 0.00 | 0.198569E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.156169E+10 | 0.00 | 0.00 | 0.00 | 0.258056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.150103E+10 | 0.00 | 0.00 | 0.00 | 0.827720E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156400E+10 | 0.00 | 0.00 | 0.00 | 50150916.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163479E+10 | 0.00 | 0.00 | 0.00 | 8745398.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.179526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.192563E+11 | 0.00 | 0.00 | 0.00 | 0.693266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.150103E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.183163E+10 | 0.00 | 0.00 | 0.00 | 0.258056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.158263E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143812E+10 | 0.00 | 0.00 | 0.00 | 320549.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.164239E+10 | 0.00 | 0.00 | 0.00 | 1624532.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.168574E+10 | 0.00 | 0.00 | 0.00 | 0.121648E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.192684E+10 | 0.00 | 0.00 | 0.00 | 0.243279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.196033E+10 | 0.00 | 0.00 | 0.00 | 0.426263E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.201705E+10 | 0.00 | 0.00 | 0.00 | 0.974906E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.197650E+10 | 0.00 | 0.00 | 0.00 | 0.130627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.198027E+10 | 0.00 | 0.00 | 0.00 | 0.393233E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.180338E+10 | 0.00 | 0.00 | 0.00 | 26335487.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.159128E+10 | 0.00 | 0.00 | 0.00 | 7467111.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157443E+10 | 0.00 | 0.00 | 0.00 | 36020.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.211790E+11 | 0.00 | 0.00 | 0.00 | 0.350139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.143812E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.201705E+10 | 0.00 | 0.00 | 0.00 | 0.130627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.168459E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152535E+10 | 0.00 | 0.00 | 0.00 | 6.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.171812E+10 | 0.00 | 0.00 | 0.00 | 10235.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.163431E+10 | 0.00 | 0.00 | 0.00 | 90756598.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.170135E+10 | 0.00 | 0.00 | 0.00 | 0.181648E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.165945E+10 | 0.00 | 0.00 | 0.00 | 0.315281E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.167621E+10 | 0.00 | 0.00 | 0.00 | 0.724441E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.171812E+10 | 0.00 | 0.00 | 0.00 | 0.984056E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.163431E+10 | 0.00 | 0.00 | 0.00 | 0.310772E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.168459E+10 | 0.00 | 0.00 | 0.00 | 17439298.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163431E+10 | 0.00 | 0.00 | 0.00 | 5014087.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.199469E+11 | 0.00 | 0.00 | 0.00 | 0.262942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.152535E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.171812E+10 | 0.00 | 0.00 | 0.00 | 0.984056E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.168988E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.153014E+10 | 0.00 | 0.00 | 0.00 | 4.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.172351E+10 | 0.00 | 0.00 | 0.00 | 5.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.163943E+10 | 0.00 | 0.00 | 0.00 | 87973199.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.170669E+10 | 0.00 | 0.00 | 0.00 | 0.177198E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.166466E+10 | 0.00 | 0.00 | 0.00 | 0.310746E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168147E+10 | 0.00 | 0.00 | 0.00 | 0.721951E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.172351E+10 | 0.00 | 0.00 | 0.00 | 0.984050E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.163943E+10 | 0.00 | 0.00 | 0.00 | 0.307687E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.168988E+10 | 0.00 | 0.00 | 0.00 | 16454569.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163943E+10 | 0.00 | 0.00 | 0.00 | 4130281.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.200095E+11 | 0.00 | 0.00 | 0.00 | 0.261019E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.153014E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.172351E+10 | 0.00 | 0.00 | 0.00 | 0.984050E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.168325E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152414E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.171675E+10 | 0.00 | 0.00 | 0.00 | 24.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.163301E+10 | 0.00 | 0.00 | 0.00 | 82956522.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.170000E+10 | 0.00 | 0.00 | 0.00 | 0.166296E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.165813E+10 | 0.00 | 0.00 | 0.00 | 0.296588E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.167488E+10 | 0.00 | 0.00 | 0.00 | 0.701943E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.171675E+10 | 0.00 | 0.00 | 0.00 | 0.960008E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.163301E+10 | 0.00 | 0.00 | 0.00 | 0.296248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.168325E+10 | 0.00 | 0.00 | 0.00 | 14869688.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163301E+10 | 0.00 | 0.00 | 0.00 | 3035380.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167488E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.199311E+11 | 0.00 | 0.00 | 0.00 | 0.252194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.152414E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.171675E+10 | 0.00 | 0.00 | 0.00 | 0.960008E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.133992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.115476E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.121019E+10 | 0.00 | 0.00 | 0.00 | 61032.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.110158E+10 | 0.00 | 0.00 | 0.00 | 0.159654E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.112196E+10 | 0.00 | 0.00 | 0.00 | 0.336457E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.109370E+10 | 0.00 | 0.00 | 0.00 | 0.653529E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.110574E+10 | 0.00 | 0.00 | 0.00 | 0.153436E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.114268E+10 | 0.00 | 0.00 | 0.00 | 0.205872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.107637E+10 | 0.00 | 0.00 | 0.00 | 0.670631E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.112685E+10 | 0.00 | 0.00 | 0.00 | 42457875.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119707E+10 | 0.00 | 0.00 | 0.00 | 8040855.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.139701E+11 | 0.00 | 0.00 | 0.00 | 0.546391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.107637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.133992E+10 | 0.00 | 0.00 | 0.00 | 0.205872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.148892E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134845E+10 | 0.00 | 0.00 | 0.00 | 0.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152102E+10 | 0.00 | 0.00 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144477E+10 | 0.00 | 0.00 | 0.00 | 78762637.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.150497E+10 | 0.00 | 0.00 | 0.00 | 0.152898E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.146885E+10 | 0.00 | 0.00 | 0.00 | 0.285557E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.148089E+10 | 0.00 | 0.00 | 0.00 | 0.684425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.152102E+10 | 0.00 | 0.00 | 0.00 | 0.950334E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144477E+10 | 0.00 | 0.00 | 0.00 | 0.283582E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.148892E+10 | 0.00 | 0.00 | 0.00 | 14482392.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144477E+10 | 0.00 | 0.00 | 0.00 | 3099945.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.148089E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.176383E+11 | 0.00 | 0.00 | 0.00 | 0.245314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.134845E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.152102E+10 | 0.00 | 0.00 | 0.00 | 0.950334E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.148153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134177E+10 | 0.00 | 0.00 | 0.00 | 0.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.151348E+10 | 0.00 | 0.00 | 0.00 | 15.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.143761E+10 | 0.00 | 0.00 | 0.00 | 77291897.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.149751E+10 | 0.00 | 0.00 | 0.00 | 0.149174E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.146157E+10 | 0.00 | 0.00 | 0.00 | 0.279681E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147355E+10 | 0.00 | 0.00 | 0.00 | 0.674525E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.151348E+10 | 0.00 | 0.00 | 0.00 | 0.939147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.143761E+10 | 0.00 | 0.00 | 0.00 | 0.278970E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.148153E+10 | 0.00 | 0.00 | 0.00 | 13951793.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.143761E+10 | 0.00 | 0.00 | 0.00 | 2928988.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175508E+11 | 0.00 | 0.00 | 0.00 | 0.241567E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.134177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.151348E+10 | 0.00 | 0.00 | 0.00 | 0.939147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.147247E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133355E+10 | 0.00 | 0.00 | 0.00 | 876.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.150422E+10 | 0.00 | 0.00 | 0.00 | 44.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142881E+10 | 0.00 | 0.00 | 0.00 | 71998036.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.148834E+10 | 0.00 | 0.00 | 0.00 | 0.135938E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.145262E+10 | 0.00 | 0.00 | 0.00 | 0.261357E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.146453E+10 | 0.00 | 0.00 | 0.00 | 0.646559E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.150422E+10 | 0.00 | 0.00 | 0.00 | 0.910825E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.142881E+10 | 0.00 | 0.00 | 0.00 | 0.264658E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147247E+10 | 0.00 | 0.00 | 0.00 | 12036458.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142881E+10 | 0.00 | 0.00 | 0.00 | 2152765.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.146453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.174434E+11 | 0.00 | 0.00 | 0.00 | 0.230553E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.150422E+10 | 0.00 | 0.00 | 0.00 | 0.910825E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.158541E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143626E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161938E+10 | 0.00 | 0.00 | 0.00 | 123.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153820E+10 | 0.00 | 0.00 | 0.00 | 68111489.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.160229E+10 | 0.00 | 0.00 | 0.00 | 0.123699E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.156383E+10 | 0.00 | 0.00 | 0.00 | 0.248254E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.157665E+10 | 0.00 | 0.00 | 0.00 | 0.635491E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.161938E+10 | 0.00 | 0.00 | 0.00 | 0.927267E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.153820E+10 | 0.00 | 0.00 | 0.00 | 0.256864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.158520E+10 | 0.00 | 0.00 | 0.00 | 9259881.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.153820E+10 | 0.00 | 0.00 | 0.00 | 1074566.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157665E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.187796E+11 | 0.00 | 0.00 | 0.00 | 0.227002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.143626E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.161938E+10 | 0.00 | 0.00 | 0.00 | 0.927267E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.674581E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.753797E+10 | 0.00 | 0.00 | 0.53 |
February | 0.743204E+10 | 0.00 | 0.00 | 61462.84 | 0.00 | 0.427119E+10 | 71152114.77 | 0.00 | 0.53 |
March | 0.920463E+10 | 0.00 | 0.00 | 121925.48 | 0.00 | 0.140624E+10 | 0.151751E+09 | 0.00 | 0.53 |
April | 0.756582E+10 | 27224359.58 | 0.00 | 2509655.61 | 0.00 | 0.208066E+09 | 0.125252E+10 | 0.00 | 0.58 |
May | 0.525355E+10 | 17051979.27 | 0.00 | 7445304.90 | 0.00 | 2701844.75 | 0.360670E+10 | 0.00 | 0.68 |
June | 0.181457E+10 | 23627031.62 | 0.00 | 15343754.87 | 0.00 | 0.00 | 0.651856E+10 | 0.00 | 0.85 |
July | 0.449413E+09 | 0.371561E+09 | 0.00 | 19939927.64 | 359080.97 | 0.00 | 0.649790E+10 | 0.00 | 0.95 |
August | 0.385068E+09 | 0.820047E+09 | 0.00 | 19516595.00 | 165090.88 | 0.00 | 0.519161E+10 | 0.00 | 0.91 |
September | 0.235087E+10 | 43840871.31 | 0.00 | 13355996.50 | 0.00 | 0.00 | 0.621914E+10 | 0.00 | 0.82 |
October | 0.712952E+10 | 0.00 | 0.00 | 3290173.97 | 0.00 | 46617487.52 | 0.266601E+10 | 0.00 | 0.59 |
November | 0.809494E+10 | 0.00 | 0.00 | 286062.37 | 0.00 | 0.294678E+10 | 0.273784E+09 | 0.00 | 0.53 |
December | 0.768430E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.586649E+10 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 0.641105E+11 | 0.130335E+10 | 0.00 | 81870859.17 | 524171.85 | 0.222860E+11 | 0.324491E+11 | 0.00 | 0.67 |
Minimum of Months | 0.385068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.920463E+10 | 0.820047E+09 | 0.00 | 19939927.64 | 359080.97 | 0.753797E+10 | 0.651856E+10 | 0.00 | 0.95 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.256524E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266923E+10 | 0.00 | 0.00 | 0.39 |
February | 0.307508E+10 | 0.00 | 0.00 | 155173.56 | 0.00 | 0.116784E+10 | 0.151280E+09 | 0.00 | 0.40 |
March | 0.390128E+10 | 0.00 | 0.00 | 356236.77 | 0.00 | 0.109690E+09 | 0.358910E+09 | 0.00 | 0.42 |
April | 0.246750E+10 | 12665440.26 | 0.00 | 2393213.92 | 0.00 | 9108882.39 | 0.191501E+10 | 0.00 | 0.57 |
May | 0.995145E+09 | 7249907.19 | 0.00 | 6172202.12 | 0.00 | 0.00 | 0.443371E+10 | 0.00 | 0.87 |
June | 0.186850E+09 | 11050318.45 | 0.00 | 9512006.35 | 0.00 | 0.00 | 0.554717E+10 | 0.00 | 1.21 |
July | 40617627.14 | 0.159390E+09 | 0.00 | 10553164.49 | 182057.45 | 0.00 | 0.484138E+10 | 0.00 | 1.32 |
August | 27542719.90 | 0.371364E+09 | 0.00 | 9664349.79 | 320178.72 | 0.00 | 0.382288E+10 | 0.00 | 1.18 |
September | 0.381002E+09 | 13823786.19 | 0.00 | 8769692.28 | 0.00 | 0.00 | 0.544907E+10 | 0.00 | 1.15 |
October | 0.222534E+10 | 0.00 | 0.00 | 3444724.50 | 0.00 | 0.00 | 0.309167E+10 | 0.00 | 0.64 |
November | 0.345327E+10 | 0.00 | 0.00 | 464569.58 | 0.00 | 0.642503E+09 | 0.455555E+09 | 0.00 | 0.43 |
December | 0.288009E+10 | 0.00 | 0.00 | 1880.81 | 0.00 | 0.204805E+10 | 1638438.35 | 0.00 | 0.38 |
Annual Sum or Average | 0.221989E+11 | 0.575543E+09 | 0.00 | 51487214.17 | 502236.17 | 0.664642E+10 | 0.300683E+11 | 0.00 | 0.75 |
Minimum of Months | 27542719.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.390128E+10 | 0.371364E+09 | 0.00 | 10553164.49 | 320178.72 | 0.266923E+10 | 0.554717E+10 | 0.00 | 1.32 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.196322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345869E+10 | 0.00 | 0.00 | 0.41 |
February | 0.267016E+10 | 0.00 | 0.00 | 49820.51 | 0.00 | 0.172388E+10 | 62730441.16 | 0.00 | 0.42 |
March | 0.389845E+10 | 0.00 | 0.00 | 69626.25 | 0.00 | 0.282035E+09 | 99662168.92 | 0.00 | 0.43 |
April | 0.285675E+10 | 13185720.61 | 0.00 | 927554.63 | 0.00 | 26183884.88 | 0.775937E+09 | 0.00 | 0.49 |
May | 0.153971E+10 | 7246642.44 | 0.00 | 3364291.37 | 0.00 | 0.00 | 0.246685E+10 | 0.00 | 0.69 |
June | 0.475619E+09 | 12094340.64 | 0.00 | 5891089.98 | 19504.49 | 0.00 | 0.360262E+10 | 0.00 | 0.94 |
July | 0.195703E+09 | 0.149656E+09 | 0.00 | 6930605.71 | 2803969.21 | 0.00 | 0.311799E+10 | 0.00 | 1.02 |
August | 0.183532E+09 | 0.351120E+09 | 0.00 | 6358843.32 | 5353500.75 | 0.00 | 0.266001E+10 | 0.00 | 0.95 |
September | 0.737012E+09 | 14485966.23 | 0.00 | 5362234.28 | 0.00 | 0.00 | 0.324479E+10 | 0.00 | 0.86 |
October | 0.266137E+10 | 0.00 | 0.00 | 1719362.01 | 0.00 | 0.00 | 0.157086E+10 | 0.00 | 0.54 |
November | 0.302952E+10 | 0.00 | 0.00 | 126338.82 | 0.00 | 0.123358E+10 | 0.119883E+09 | 0.00 | 0.43 |
December | 0.247269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261101E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.226837E+11 | 0.547789E+09 | 0.00 | 30799766.87 | 8176974.45 | 0.933538E+10 | 0.177213E+11 | 0.00 | 0.63 |
Minimum of Months | 0.183532E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.389845E+10 | 0.351120E+09 | 0.00 | 6930605.71 | 5353500.75 | 0.345869E+10 | 0.360262E+10 | 0.00 | 1.02 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.176253E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365816E+10 | 0.00 | 0.00 | 0.41 |
February | 0.246103E+10 | 0.00 | 0.00 | 36726.80 | 0.00 | 0.192439E+10 | 55200740.84 | 0.00 | 0.42 |
March | 0.375449E+10 | 0.00 | 0.00 | 57629.63 | 0.00 | 0.404600E+09 | 88118596.12 | 0.00 | 0.43 |
April | 0.286992E+10 | 13163889.32 | 0.00 | 832135.22 | 0.00 | 63462523.95 | 0.665429E+09 | 0.00 | 0.49 |
May | 0.162663E+10 | 7155539.02 | 0.00 | 3157226.29 | 0.00 | 0.00 | 0.231209E+10 | 0.00 | 0.68 |
June | 0.490282E+09 | 12090682.03 | 0.00 | 5767170.68 | 19395.45 | 0.00 | 0.355927E+10 | 0.00 | 0.93 |
July | 0.198708E+09 | 0.149450E+09 | 0.00 | 6901241.31 | 2782647.57 | 0.00 | 0.311322E+10 | 0.00 | 1.02 |
August | 0.183055E+09 | 0.350624E+09 | 0.00 | 6388917.23 | 5328572.47 | 0.00 | 0.266702E+10 | 0.00 | 0.96 |
September | 0.766247E+09 | 14238881.91 | 0.00 | 5247142.03 | 0.00 | 0.00 | 0.317999E+10 | 0.00 | 0.86 |
October | 0.270165E+10 | 0.00 | 0.00 | 1603278.21 | 0.00 | 1868497.28 | 0.145576E+10 | 0.00 | 0.53 |
November | 0.281390E+10 | 0.00 | 0.00 | 104899.19 | 0.00 | 0.144822E+10 | 98696276.61 | 0.00 | 0.43 |
December | 0.226349E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281788E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.218919E+11 | 0.546723E+09 | 0.00 | 30096366.59 | 8130615.50 | 0.103186E+11 | 0.171948E+11 | 0.00 | 0.63 |
Minimum of Months | 0.183055E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.375449E+10 | 0.350624E+09 | 0.00 | 6901241.31 | 5328572.47 | 0.365816E+10 | 0.355927E+10 | 0.00 | 1.02 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.147573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394374E+10 | 0.00 | 0.00 | 0.41 |
February | 0.212279E+10 | 0.00 | 0.00 | 23128.25 | 0.00 | 0.225797E+10 | 42200194.91 | 0.00 | 0.42 |
March | 0.350016E+10 | 0.00 | 0.00 | 41547.63 | 0.00 | 0.633195E+09 | 73150958.79 | 0.00 | 0.43 |
April | 0.289292E+10 | 13157299.88 | 0.00 | 679853.56 | 0.00 | 86302184.32 | 0.527526E+09 | 0.00 | 0.48 |
May | 0.182663E+10 | 6954463.49 | 0.00 | 2658726.09 | 0.00 | 0.00 | 0.194757E+10 | 0.00 | 0.66 |
June | 0.603362E+09 | 12074900.66 | 0.00 | 5253872.62 | 20093.41 | 0.00 | 0.330309E+10 | 0.00 | 0.91 |
July | 0.214062E+09 | 0.148684E+09 | 0.00 | 6511600.43 | 2820459.24 | 0.00 | 0.301394E+10 | 0.00 | 1.00 |
August | 0.200964E+09 | 0.348914E+09 | 0.00 | 6004881.19 | 5377551.27 | 0.00 | 0.258692E+10 | 0.00 | 0.94 |
September | 0.908062E+09 | 13806030.57 | 0.00 | 4783765.61 | 0.00 | 0.00 | 0.289863E+10 | 0.00 | 0.84 |
October | 0.272034E+10 | 0.00 | 0.00 | 1386157.74 | 0.00 | 9844801.94 | 0.129601E+10 | 0.00 | 0.52 |
November | 0.258754E+10 | 0.00 | 0.00 | 80793.89 | 0.00 | 0.166265E+10 | 81331668.32 | 0.00 | 0.43 |
December | 0.196335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311542E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.210159E+11 | 0.543590E+09 | 0.00 | 27424327.01 | 8218103.92 | 0.117091E+11 | 0.157704E+11 | 0.00 | 0.62 |
Minimum of Months | 0.200964E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.350016E+10 | 0.348914E+09 | 0.00 | 6511600.43 | 5377551.27 | 0.394374E+10 | 0.330309E+10 | 0.00 | 1.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.220859E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.794528E+10 | 0.00 | 0.00 | 0.38 |
February | 0.386936E+10 | 0.00 | 0.00 | 14796.45 | 0.00 | 0.435042E+10 | 20007561.33 | 0.00 | 0.38 |
March | 0.638660E+10 | 0.00 | 0.00 | 54037.72 | 0.00 | 0.126124E+10 | 74136770.44 | 0.00 | 0.39 |
April | 0.542066E+10 | 17147838.30 | 0.00 | 1029390.77 | 0.00 | 0.161944E+09 | 0.530736E+09 | 0.00 | 0.41 |
May | 0.398608E+10 | 7018168.46 | 0.00 | 3550510.93 | 0.00 | 2782858.15 | 0.201158E+10 | 0.00 | 0.48 |
June | 0.150684E+10 | 13621269.41 | 0.00 | 8136905.09 | 16401.47 | 0.00 | 0.414461E+10 | 0.00 | 0.61 |
July | 0.380180E+09 | 0.285626E+09 | 0.00 | 10042127.30 | 4405927.16 | 0.00 | 0.384419E+10 | 0.00 | 0.65 |
August | 0.291602E+09 | 0.679157E+09 | 0.00 | 8627748.72 | 4528504.48 | 0.00 | 0.322009E+10 | 0.00 | 0.62 |
September | 0.211883E+10 | 16171976.72 | 0.00 | 7185329.23 | 0.00 | 0.00 | 0.342729E+10 | 0.00 | 0.57 |
October | 0.518579E+10 | 0.00 | 0.00 | 1845171.89 | 0.00 | 81007558.95 | 0.150009E+10 | 0.00 | 0.42 |
November | 0.467633E+10 | 0.00 | 0.00 | 119380.18 | 0.00 | 0.329188E+10 | 92080915.80 | 0.00 | 0.39 |
December | 0.334974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.619516E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.393806E+11 | 0.101874E+10 | 0.00 | 40605398.27 | 8950833.12 | 0.232897E+11 | 0.188648E+11 | 0.00 | 0.47 |
Minimum of Months | 0.291602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.638660E+10 | 0.679157E+09 | 0.00 | 10042127.30 | 4528504.48 | 0.794528E+10 | 0.414461E+10 | 0.00 | 0.65 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.105969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.400474E+10 | 0.00 | 0.00 | 0.38 |
February | 0.176814E+10 | 0.00 | 0.00 | 12534.11 | 0.00 | 0.233180E+10 | 28396686.61 | 0.00 | 0.38 |
March | 0.312722E+10 | 0.00 | 0.00 | 29962.56 | 0.00 | 0.729768E+09 | 57144674.86 | 0.00 | 0.39 |
April | 0.265399E+10 | 7906435.33 | 0.00 | 618804.38 | 0.00 | 0.112298E+09 | 0.467605E+09 | 0.00 | 0.44 |
May | 0.173035E+10 | 2646052.86 | 0.00 | 2231020.41 | 0.00 | 0.00 | 0.174609E+10 | 0.00 | 0.60 |
June | 0.462878E+09 | 5922970.21 | 0.00 | 4716919.49 | 0.00 | 0.00 | 0.315942E+10 | 0.00 | 0.84 |
July | 0.125134E+09 | 0.124840E+09 | 0.00 | 5709491.10 | 1644736.52 | 0.00 | 0.283523E+10 | 0.00 | 0.92 |
August | 90440504.96 | 0.304570E+09 | 0.00 | 5207469.31 | 1649357.11 | 0.00 | 0.238673E+10 | 0.00 | 0.86 |
September | 0.818755E+09 | 4420285.98 | 0.00 | 4353937.66 | 0.00 | 0.00 | 0.270933E+10 | 0.00 | 0.77 |
October | 0.247500E+10 | 0.00 | 0.00 | 1158330.08 | 0.00 | 37488769.97 | 0.119318E+10 | 0.00 | 0.47 |
November | 0.222945E+10 | 0.00 | 0.00 | 70966.75 | 0.00 | 0.175975E+10 | 77876109.56 | 0.00 | 0.39 |
December | 0.157796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318289E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.181190E+11 | 0.450306E+09 | 0.00 | 24109435.85 | 3294093.63 | 0.121587E+11 | 0.146610E+11 | 0.00 | 0.57 |
Minimum of Months | 90440504.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.312722E+10 | 0.304570E+09 | 0.00 | 5709491.10 | 1649357.11 | 0.400474E+10 | 0.315942E+10 | 0.00 | 0.92 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.935746E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412829E+10 | 0.00 | 0.00 | 0.38 |
February | 0.169323E+10 | 0.00 | 0.00 | 10682.55 | 0.00 | 0.240713E+10 | 25155906.50 | 0.00 | 0.38 |
March | 0.302803E+10 | 0.00 | 0.00 | 27613.61 | 0.00 | 0.825273E+09 | 52804118.76 | 0.00 | 0.39 |
April | 0.263441E+10 | 7885778.91 | 0.00 | 592507.09 | 0.00 | 0.133645E+09 | 0.447594E+09 | 0.00 | 0.44 |
May | 0.177290E+10 | 2575627.73 | 0.00 | 2129954.75 | 0.00 | 0.00 | 0.166788E+10 | 0.00 | 0.59 |
June | 0.499026E+09 | 5897828.41 | 0.00 | 4566412.64 | 0.00 | 0.00 | 0.307929E+10 | 0.00 | 0.83 |
July | 0.131086E+09 | 0.124319E+09 | 0.00 | 5568536.13 | 1541389.63 | 0.00 | 0.279657E+10 | 0.00 | 0.91 |
August | 96247921.05 | 0.303260E+09 | 0.00 | 5080396.71 | 1644363.50 | 0.00 | 0.235725E+10 | 0.00 | 0.85 |
September | 0.834791E+09 | 4295138.48 | 0.00 | 4235869.80 | 0.00 | 0.00 | 0.265782E+10 | 0.00 | 0.76 |
October | 0.249864E+10 | 0.00 | 0.00 | 1106896.93 | 0.00 | 44187643.60 | 0.113497E+10 | 0.00 | 0.47 |
November | 0.216080E+10 | 0.00 | 0.00 | 67805.41 | 0.00 | 0.182561E+10 | 76917767.72 | 0.00 | 0.39 |
December | 0.149922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326126E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.177841E+11 | 0.448233E+09 | 0.00 | 23386675.62 | 3185753.13 | 0.126254E+11 | 0.142962E+11 | 0.00 | 0.57 |
Minimum of Months | 96247921.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.302803E+10 | 0.303260E+09 | 0.00 | 5568536.13 | 1644363.50 | 0.412829E+10 | 0.307929E+10 | 0.00 | 0.91 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.576598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.448638E+10 | 0.00 | 0.00 | 0.38 |
February | 0.126533E+10 | 0.00 | 0.00 | 4351.33 | 0.00 | 0.283646E+10 | 12654898.15 | 0.00 | 0.38 |
March | 0.267638E+10 | 0.00 | 0.00 | 20256.28 | 0.00 | 0.115358E+10 | 43458516.94 | 0.00 | 0.39 |
April | 0.254063E+10 | 7829661.33 | 0.00 | 476175.80 | 0.00 | 0.230965E+09 | 0.370586E+09 | 0.00 | 0.43 |
May | 0.196737E+10 | 2368657.74 | 0.00 | 1726230.12 | 0.00 | 1454358.36 | 0.131155E+10 | 0.00 | 0.57 |
June | 0.687445E+09 | 5851993.83 | 0.00 | 3974956.76 | 0.00 | 0.00 | 0.271992E+10 | 0.00 | 0.80 |
July | 0.168794E+09 | 0.122727E+09 | 0.00 | 5071376.28 | 1654804.33 | 0.00 | 0.265151E+10 | 0.00 | 0.89 |
August | 0.138346E+09 | 0.300124E+09 | 0.00 | 4632976.43 | 1614037.26 | 0.00 | 0.223632E+10 | 0.00 | 0.83 |
September | 0.991620E+09 | 3945113.46 | 0.00 | 3743066.41 | 0.00 | 0.00 | 0.234730E+10 | 0.00 | 0.73 |
October | 0.247355E+10 | 0.00 | 0.00 | 886296.14 | 0.00 | 0.132444E+09 | 0.947831E+09 | 0.00 | 0.45 |
November | 0.186326E+10 | 0.00 | 0.00 | 55704.10 | 0.00 | 0.211873E+10 | 64233234.24 | 0.00 | 0.39 |
December | 0.105885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370001E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.164082E+11 | 0.442846E+09 | 0.00 | 20591389.66 | 3268841.59 | 0.146600E+11 | 0.127054E+11 | 0.00 | 0.55 |
Minimum of Months | 0.138346E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.267638E+10 | 0.300124E+09 | 0.00 | 5071376.28 | 1654804.33 | 0.448638E+10 | 0.271992E+10 | 0.00 | 0.89 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 32883574.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.500694E+10 | 0.00 | 0.00 | 0.38 |
February | 0.407454E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367185E+10 | 0.00 | 0.00 | 0.38 |
March | 0.155201E+10 | 0.00 | 0.00 | 5377.47 | 0.00 | 0.222904E+10 | 26661125.52 | 0.00 | 0.39 |
April | 0.200545E+10 | 8158760.17 | 0.00 | 364685.13 | 0.00 | 0.751188E+09 | 0.283138E+09 | 0.00 | 0.43 |
May | 0.195051E+10 | 2416746.97 | 0.00 | 1307412.63 | 0.00 | 0.116480E+09 | 0.100647E+10 | 0.00 | 0.57 |
June | 0.871430E+09 | 6354067.81 | 0.00 | 3304956.68 | 0.00 | 0.00 | 0.237479E+10 | 0.00 | 0.79 |
July | 0.316339E+09 | 0.126568E+09 | 0.00 | 4305117.38 | 1776490.27 | 0.00 | 0.239999E+10 | 0.00 | 0.90 |
August | 0.208504E+09 | 0.313173E+09 | 0.00 | 3881707.37 | 1601744.56 | 0.00 | 0.206963E+10 | 0.00 | 0.83 |
September | 0.115339E+10 | 4081187.01 | 0.00 | 3144293.93 | 0.00 | 1560195.83 | 0.198841E+10 | 0.00 | 0.73 |
October | 0.204262E+10 | 0.00 | 0.00 | 592894.18 | 0.00 | 0.606638E+09 | 0.705831E+09 | 0.00 | 0.44 |
November | 0.819473E+09 | 0.00 | 0.00 | 44611.00 | 0.00 | 0.311971E+10 | 60423773.80 | 0.00 | 0.39 |
December | 0.139617E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459588E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.114997E+11 | 0.460752E+09 | 0.00 | 16951055.76 | 3378234.83 | 0.200993E+11 | 0.109153E+11 | 0.00 | 0.55 |
Minimum of Months | 32883574.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.204262E+10 | 0.313173E+09 | 0.00 | 4305117.38 | 1776490.27 | 0.500694E+10 | 0.239999E+10 | 0.00 | 0.90 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:41:13
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.443801E+11 | 0.293887E+11 | 0.00 | 0.687144E+11 | 0.153643E+11 |
February | 0.119928E+12 | 0.237048E+11 | 0.00 | 0.561268E+11 | 0.982036E+10 |
March | 0.235446E+12 | 0.216361E+11 | 0.00 | 0.523379E+11 | 0.443649E+10 |
April | 0.390345E+12 | 0.174150E+11 | 0.00 | 0.431642E+11 | 0.677933E+10 |
May | 0.528720E+12 | 0.152776E+11 | 0.00 | 0.452910E+11 | 0.113572E+11 |
June | 0.538940E+12 | 0.112452E+11 | 0.00 | 0.455928E+11 | 0.207400E+11 |
July | 0.573531E+12 | 0.665434E+10 | 0.00 | 0.356657E+11 | 0.503218E+11 |
August | 0.443072E+12 | 0.403567E+10 | 0.00 | 0.269415E+11 | 0.687634E+11 |
September | 0.302616E+12 | 0.108854E+11 | 0.00 | 0.451314E+11 | 0.212335E+11 |
October | 0.174599E+12 | 0.180478E+11 | 0.00 | 0.488376E+11 | 0.191154E+10 |
November | 0.597111E+11 | 0.231953E+11 | 0.00 | 0.548262E+11 | 0.755754E+10 |
December | 0.260775E+11 | 0.272005E+11 | 0.00 | 0.647908E+11 | 0.127787E+11 |
Annual Sum or Average | 0.343736E+13 | 0.208686E+12 | 0.00 | 0.587420E+12 | 0.231064E+12 |
Minimum of Months | 0.260775E+11 | 0.403567E+10 | 0.00 | 0.269415E+11 | 0.191154E+10 |
Maximum of Months | 0.573531E+12 | 0.293887E+11 | 0.00 | 0.687144E+11 | 0.687634E+11 |