Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:41
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700
Simulation Timestamp: 2023-10-16 08:41:35
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:35
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 985.43 | 471.43 | 471.43 |
Net Site Energy | 985.43 | 471.43 | 471.43 |
Total Source Energy | 3003.12 | 1436.68 | 1436.68 |
Net Source Energy | 3003.12 | 1436.68 | 1436.68 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 56.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 179.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 381.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 70.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 110.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 57.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 928.91 | 56.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 56.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 179.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 381.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 70.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 110.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 57.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 56.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 179.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 381.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 70.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 110.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 57.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 216.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 166.55 | 27.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 444.39 | 27.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 216.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 166.55 | 27.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 444.39 | 27.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 928.908 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 928.908 | 100.00 |
Total On-Site and Utility Electric Sources | 928.908 | 100.00 |
Total Electricity End Uses | 928.908 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 818.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:35
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:41 |
RunPeriod | RUNPERIOD 1 |
Weather File | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Latitude [deg] | 31.77 |
Longitude [deg] | -106.5 |
Elevation [m] | 1186.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.77 | 20.77 | 15.2453 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.38 | 10.38 | 17.9167 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 16.4411 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 16.4411 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 16.4411 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.72 | 20.72 | 10.0956 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 10.1826 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 10.1826 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 10.1826 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.36 | 10.36 | 10.1826 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 13.2210 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 13.2210 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 15.2453 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 17.9167 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 16.4411 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 16.4411 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 16.4411 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 10.0956 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 10.1826 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 10.1826 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 10.1826 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 10.1826 | 6.19 | 4.3000 | |
Total | 2090.32 | 13.2210 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 13.2210 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 13.2210 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:35
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 15-JUN-14:39 | 27-DEC-09:09 | - | - | - | - | - | - | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 132964.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 42694.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 23650.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7965.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 5433.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 87832.64 | 132964.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 132964.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 42694.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 23650.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 7965.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 5433.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:35
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 61.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 567.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1208.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 222.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 407.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 351.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 183.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2941.85 | 61.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 29.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 271.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 578.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 106.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 168.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 87.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1407.37 | 29.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 29.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 271.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 578.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 106.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 168.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 87.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1407.37 | 29.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:35
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 2.39 |
SMSTORE1 DIRECT AIR | 1.24 |
SMSTORE2 DIRECT AIR | 1.28 |
SMSTORE3 DIRECT AIR | 1.27 |
SMSTORE4 DIRECT AIR | 1.27 |
LGSTORE2 DIRECT AIR | 2.22 |
SMSTORE5 DIRECT AIR | 1.15 |
SMSTORE6 DIRECT AIR | 1.15 |
SMSTORE7 DIRECT AIR | 1.15 |
SMSTORE8 DIRECT AIR | 1.30 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.39 | 2.39 | 2.39 | 2.39 | 2.39 | 2.39 | 1.00 | 1.00 | 2.39 |
PSZ-AC_2:2 | 1.24 | 1.24 | 1.24 | 1.24 | 1.24 | 1.24 | 1.00 | 1.000000 | 1.24 |
PSZ-AC_3:3 | 1.28 | 1.28 | 1.28 | 1.28 | 1.28 | 1.28 | 1.00 | 1.00 | 1.28 |
PSZ-AC_4:4 | 1.27 | 1.27 | 1.27 | 1.27 | 1.27 | 1.27 | 1.00 | 1.000000 | 1.27 |
PSZ-AC_5:5 | 1.27 | 1.27 | 1.27 | 1.27 | 1.27 | 1.27 | 1.00 | 1.000000 | 1.27 |
PSZ-AC_6:6 | 2.22 | 2.22 | 2.22 | 2.22 | 2.22 | 2.22 | 1.00 | 1.000000 | 2.22 |
PSZ-AC_7:7 | 1.15 | 1.15 | 1.15 | 1.15 | 1.15 | 1.15 | 1.00 | 1.00 | 1.15 |
PSZ-AC_8:8 | 1.15 | 1.15 | 1.15 | 1.15 | 1.15 | 1.15 | 1.00 | 1.00 | 1.15 |
PSZ-AC_9:9 | 1.15 | 1.15 | 1.15 | 1.15 | 1.15 | 1.15 | 1.00 | 1.00 | 1.15 |
PSZ-AC_10:10 | 1.30 | 1.30 | 1.30 | 1.30 | 1.30 | 1.30 | 1.00 | 1.00 | 1.30 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.39 | 0.411479 |
PSZ-AC_2:2_OA_CONTROLLER | 1.24 | 0.205739 |
PSZ-AC_3:3_OA_CONTROLLER | 1.28 | 0.205739 |
PSZ-AC_4:4_OA_CONTROLLER | 1.27 | 0.205739 |
PSZ-AC_5:5_OA_CONTROLLER | 1.27 | 0.205739 |
PSZ-AC_6:6_OA_CONTROLLER | 2.22 | 0.411479 |
PSZ-AC_7:7_OA_CONTROLLER | 1.15 | 0.205739 |
PSZ-AC_8:8_OA_CONTROLLER | 1.15 | 0.205739 |
PSZ-AC_9:9_OA_CONTROLLER | 1.15 | 0.205739 |
PSZ-AC_10:10_OA_CONTROLLER | 1.30 | 0.205739 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.39 | 2556.55 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.24 | 1377.15 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.28 | 1415.48 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.27 | 1408.25 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.27 | 1410.88 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 2.22 | 2372.45 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 1.15 | 1276.42 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 1.15 | 1270.51 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 1.15 | 1274.04 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.30 | 1441.51 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.39 | 2.39 | 2.39 | 1.58 | 45206.36 | 58727.51 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.24 | 1.24 | 1.24 | 0.820949 | 23386.92 | 30340.44 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.28 | 1.28 | 1.28 | 0.843798 | 24024.38 | 31026.80 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.27 | 1.27 | 1.27 | 0.839484 | 23890.33 | 30897.21 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.27 | 1.27 | 1.27 | 0.841055 | 23956.89 | 30944.40 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 2.22 | 2.22 | 2.22 | 1.46 | 42466.09 | 55316.10 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 1.15 | 1.15 | 1.15 | 0.760900 | 21929.82 | 28536.62 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 1.15 | 1.15 | 1.15 | 0.757378 | 21844.09 | 28430.83 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 1.15 | 1.15 | 1.15 | 0.759480 | 21895.73 | 28493.97 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.30 | 1.30 | 1.30 | 0.859316 | 24023.27 | 31493.43 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 2.39 | 1.19 | 1.59 | 45206.36 | 22603.18 | 0.798650 | 0.798650 |
PSZ-AC_2:2 COOLING COIL | 1.24 | 0.621931 | 0.829240 | 23386.92 | 11693.46 | 0.800690 | 0.800690 |
PSZ-AC_3:3 COOLING COIL | 1.28 | 0.639241 | 0.852320 | 24024.38 | 12012.19 | 0.800870 | 0.800870 |
PSZ-AC_4:4 COOLING COIL | 1.27 | 0.635973 | 0.847967 | 23890.33 | 11945.17 | 0.800020 | 0.800020 |
PSZ-AC_5:5 COOLING COIL | 1.27 | 0.637163 | 0.849553 | 23956.89 | 11978.44 | 0.800730 | 0.800730 |
PSZ-AC_6:6 COOLING COIL | 2.22 | 1.11 | 1.48 | 42466.09 | 21233.04 | 0.793750 | 0.793750 |
PSZ-AC_7:7 COOLING COIL | 1.15 | 0.576439 | 0.768587 | 21929.82 | 10964.91 | 0.796950 | 0.796950 |
PSZ-AC_8:8 COOLING COIL | 1.15 | 0.573771 | 0.765027 | 21844.09 | 10922.05 | 0.796720 | 0.796720 |
PSZ-AC_9:9 COOLING COIL | 1.15 | 0.575364 | 0.767153 | 21895.73 | 10947.86 | 0.796850 | 0.796850 |
PSZ-AC_10:10 COOLING COIL | 1.30 | 0.650997 | 0.867993 | 24023.27 | 12011.64 | 0.800840 | 0.800840 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 58727.51 |
PSZ-AC_2:2 HEATING COIL | 30340.44 |
PSZ-AC_3:3 HEATING COIL | 31026.80 |
PSZ-AC_4:4 HEATING COIL | 30897.21 |
PSZ-AC_5:5 HEATING COIL | 30944.40 |
PSZ-AC_6:6 HEATING COIL | 55316.10 |
PSZ-AC_7:7 HEATING COIL | 28536.62 |
PSZ-AC_8:8 HEATING COIL | 28430.83 |
PSZ-AC_9:9 HEATING COIL | 28493.97 |
PSZ-AC_10:10 HEATING COIL | 31493.43 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:35
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:35
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:35
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.30 | 11.20 | 6.80 | 8.10 | 10.30 | 12.50 | 19.20 | 23.80 | 27.90 | 27.50 | 26.30 | 23.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | El Paso International Ap Ut TX USA TMY3 WMO#=722700 | 31.77 | -106.50 | -7.00 | 1186.00 | 87865 | 1.0443 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 17.94 | 21.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.74 | 20.77 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.66 | 10.38 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.41 | 20.72 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.12 | 10.36 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 15.245 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 19.545 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 17.917 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.217 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 16.441 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.741 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 16.441 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.741 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 16.441 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.741 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 10.096 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 14.396 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 10.183 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 14.483 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 10.183 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 14.483 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 10.183 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 14.483 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 10.183 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 14.483 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 3524.998 | 10.118 | 62.666 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3524.998 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 1786.253 | 5.127 | 31.755 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1786.253 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 1777.664 | 10.205 | 63.207 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1777.664 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1343.311 | 7.712 | 47.763 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1343.311 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 1773.748 | 10.183 | 63.068 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1773.748 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 1090.187 | 6.258 | 38.763 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1090.187 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 1773.748 | 10.183 | 63.068 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1773.748 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 1090.187 | 6.258 | 38.763 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1090.187 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 1773.748 | 10.183 | 63.068 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1773.748 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 1090.187 | 6.258 | 38.763 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1090.187 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 3517.169 | 10.096 | 62.527 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3517.169 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 1773.748 | 10.183 | 63.068 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1773.748 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 1773.748 | 10.183 | 63.068 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1773.748 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 1773.748 | 10.183 | 63.068 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1773.748 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 1773.748 | 10.183 | 63.068 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1773.748 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.6641 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1995 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2888 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.272 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.937 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.386 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
19 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
20 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
21 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
22 | 7 | -0.32972738E-12 | 0.11763143E-14 | -0.10490290E-12 | 0.10060316E-15 |
23 | 6 | 0.30001920E-07 | 0.18927851E-09 | 0.68616814E-08 | -0.14235861E-12 |
24 | 5 | -0.19683904E-03 | 0.16062604E-05 | -0.10115234E-03 | 0.67789156E-08 |
25 | 4 | 0.29998857 | 0.77587294E-03 | 0.10250533 | -0.34681058E-04 |
26 | 3 | -7.4215481 | 0.23875067E-01 | -2.3849775 | 0.29769922E-01 |
27 | 2 | 41.382972 | 0.84366340E-01 | 15.453844 | -0.33904133 |
28 | 1 | -80.937908 | 0.37867119E-01 | -29.310851 | 1.0869756 |
29 | 0 | 46.824336 | 0.75775345E-03 | 16.287225 | |
30 | 7 | -0.21163652E-08 | -0.68723841E-15 | 0.43910983E-14 | -0.57684426E-16 |
31 | 6 | 0.56109385E-05 | 0.38186281E-08 | 0.31898696E-02 | -0.26759299E-04 |
32 | 5 | -0.40164657E-03 | 0.22608617E-05 | -0.22372456 | 0.19561502E-02 |
33 | 4 | 0.92272104E-02 | 0.10289840E-03 | 4.8295456 | -0.45264980E-01 |
34 | 3 | -0.80993241E-01 | 0.81813938E-03 | -38.021416 | 0.39865375 |
35 | 2 | 0.28754352 | 0.13608947E-02 | 116.48395 | -1.4179393 |
36 | 1 | -0.41499682 | 0.41453381E-03 | -143.90731 | 2.0490399 |
37 | 0 | 0.20232414 | 0.10048102E-04 | 60.838472 | |
38 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
39 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
40 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
41 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
42 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
43 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
44 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
45 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
46 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
47 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
48 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
49 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
50 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
51 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
52 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
53 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
54 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
55 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
56 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
57 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
58 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
59 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
60 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
61 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
62 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
63 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
64 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
65 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
66 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
67 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
68 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
69 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
70 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
71 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
72 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
73 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
74 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
75 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
76 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
77 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
78 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
79 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
80 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
81 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
82 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
83 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
84 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
85 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
86 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
87 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
88 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
89 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
90 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
91 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
92 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
93 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
94 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479936E-14 | -0.41635794E-16 |
95 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
96 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
97 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
98 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
99 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
100 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
101 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
102 | 7 | -0.14484255E-08 | -0.22640907E-15 | 0.11860658E-13 | -0.17473455E-15 |
103 | 6 | 0.80640390E-05 | 0.55493782E-08 | 0.31828288E-02 | -0.26700235E-04 |
104 | 5 | -0.58275339E-03 | 0.32892043E-05 | -0.22332434 | 0.19526176E-02 |
105 | 4 | 0.13421983E-01 | 0.14977251E-03 | 4.8228790 | -0.45200897E-01 |
106 | 3 | -0.11791368 | 0.11914425E-02 | -37.983753 | 0.39823745 |
107 | 2 | 0.41875064 | 0.19825898E-02 | 116.41064 | -1.4169588 |
108 | 1 | -0.60444169 | 0.60433957E-03 | -143.86415 | 2.0483306 |
109 | 0 | 0.29470347 | 0.14596444E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.463_SHGC_0.25 | 35 | 1 | VerySmooth | 2.632 | 2.632 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.49960E-002 | 0.16139 | 0.61571 | 0.61571 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.11953 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.021 | 0.7435 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.021 | 0.7435 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.021 | 0.7435 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.021 | 0.7435 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.021 | 0.7435 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.021 | 0.7435 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.021 | 0.7435 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 0.157 | 4.517E-004 | 2.488E-004 | 0.314 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 3.813E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 8.993E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 4.692E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 0.112 | 6.453E-004 | 2.994E-004 | 0.448 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 3.583E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 23466.31440 | 28159.57728 | 1.99099 | 2.38919 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 38.10000 | 6.87148E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 18629.68766 | 22355.62519 | 0.92598 | 1.11118 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -5.20000 | 2.80840E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 12217.13759 | 14660.56511 | 1.03655 | 1.24386 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 37.99167 | 6.87130E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 8805.51779 | 10566.62134 | 0.43768 | 0.52521 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -5.20000 | 2.80840E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 12856.25119 | 15427.50143 | 1.06540 | 1.27848 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 30.95000 | 6.86012E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 8934.88174 | 10721.85809 | 0.44411 | 0.53293 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -5.20000 | 2.80840E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 12792.36710 | 15350.84052 | 1.05995 | 1.27195 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 30.95000 | 6.86012E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 9037.43491 | 10844.92190 | 0.44920 | 0.53904 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -5.20000 | 2.80840E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 12815.06644 | 15378.07972 | 1.06194 | 1.27433 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 30.95000 | 6.86012E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 9191.63655 | 11029.96386 | 0.45687 | 0.54824 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -5.20000 | 2.80840E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 21776.37545 | 26131.65054 | 1.84762 | 2.21714 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 37.88333 | 6.87114E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 17937.96522 | 21525.55826 | 0.89161 | 1.06993 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -5.20000 | 2.80840E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 11323.48028 | 13588.17634 | 0.96073 | 1.15288 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 37.88333 | 6.87114E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 9537.36910 | 11444.84292 | 0.47405 | 0.56886 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -5.20000 | 2.80840E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 11271.06877 | 13525.28253 | 0.95629 | 1.14754 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 37.88333 | 6.87114E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 9531.42803 | 11437.71364 | 0.47376 | 0.56851 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -5.20000 | 2.80840E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 11302.35070 | 13562.82085 | 0.95894 | 1.15073 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 37.88333 | 6.87114E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 9759.97716 | 11711.97260 | 0.48512 | 0.58214 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -5.20000 | 2.80840E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 12787.90579 | 15345.48695 | 1.08500 | 1.30199 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 37.45000 | 6.87043E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 11689.81253 | 14027.77503 | 0.58103 | 0.69723 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -5.20000 | 2.80840E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 33936.96 | 2.38919 | 2.38919 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 33389.82 | 1.11118 | 1.11118 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 17539.81 | 1.24386 | 1.24386 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 16092.64 | 0.52521 | 0.52521 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 17594.91 | 1.27848 | 1.27848 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 16245.61 | 0.53293 | 0.53293 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 17641.25 | 1.27195 | 1.27195 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 16366.88 | 0.53904 | 0.53904 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 17551.53 | 1.27433 | 1.27433 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 16549.23 | 0.54824 | 0.54824 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 31918.55 | 2.21714 | 2.21714 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 32571.94 | 1.06993 | 1.06993 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 16471.58 | 1.15288 | 1.15288 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 16958.07 | 0.56886 | 0.56886 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 16409.37 | 1.14754 | 1.14754 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 16951.04 | 0.56851 | 0.56851 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 16444.69 | 1.15073 | 1.15073 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 17221.31 | 0.58214 | 0.58214 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 18078.46 | 1.30199 | 1.30199 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 19503.29 | 0.69723 | 0.69723 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.38919 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.24386 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.27848 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.27195 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.27433 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.21714 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.15288 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.14754 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.15073 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.30199 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.38919 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.38919 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.38919 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.38919 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.38919 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.38919 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.24386 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.24386 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.24386 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.24386 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.24386 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.24386 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.27848 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.27848 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.27848 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.27848 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.27848 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.27848 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.27195 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.27195 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.27195 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.27195 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.27195 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.27195 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.27433 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.27433 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.27433 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.27433 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.27433 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.27433 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.21714 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.21714 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.21714 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.21714 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.21714 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 2.21714 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.15288 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.15288 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.15288 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.15288 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.15288 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 1.15288 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 1.00000 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.14754 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.14754 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.14754 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.14754 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.14754 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 1.14754 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 1.00000 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.15073 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.15073 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.15073 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.15073 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.15073 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 1.15073 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 1.00000 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.30199 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.30199 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.30199 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.30199 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.30199 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.30199 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.38919 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.24386 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.27848 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.27195 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.27433 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 2.21714 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 1.15288 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 1.14754 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 1.15073 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.30199 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.38919 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.38919 |
104 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2556.54717 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.38919 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.38919 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.38919 |
108 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.57687 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.38919 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.19460 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.59279 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 45206.36000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 22603.18000 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.79865 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.79865 |
116 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 45206.36000 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 58727.51376 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
120 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 58727.51376 |
121 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.24386 |
122 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
123 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.24386 |
124 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1377.15281 |
125 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.24386 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.24386 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.24386 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.82095 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.24386 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.62193 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.82924 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 23386.92000 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11693.46000 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80069 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80069 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23386.92000 |
137 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30340.44093 |
138 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
139 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
140 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 30340.44093 |
141 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.27848 |
142 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
143 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.27848 |
144 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1415.48219 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.27848 |
146 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.27848 |
147 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.27848 |
148 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.84380 |
149 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.27848 |
150 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.63924 |
151 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.85232 |
152 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 24024.38000 |
153 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 12012.19000 |
154 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80087 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80087 |
156 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 24024.38000 |
157 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31026.80361 |
158 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
159 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
160 | Coil:Heating:Fuel | PSZ-AC_3:3 HEATING COIL | Design Size Nominal Capacity [W] | 31026.80361 |
161 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.27195 |
162 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
163 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.27195 |
164 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1408.24532 |
165 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.27195 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.27195 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.27195 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.83948 |
169 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.27195 |
170 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.63597 |
171 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.84797 |
172 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 23890.33000 |
173 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11945.16500 |
174 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80002 |
175 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80002 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23890.33000 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30897.21499 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
179 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
180 | Coil:Heating:Fuel | PSZ-AC_4:4 HEATING COIL | Design Size Nominal Capacity [W] | 30897.21499 |
181 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.27433 |
182 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
183 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.27433 |
184 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1410.88036 |
185 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.27433 |
186 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.27433 |
187 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.27433 |
188 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.84105 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.27433 |
190 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.63716 |
191 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.84955 |
192 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 23956.89000 |
193 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11978.44500 |
194 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80073 |
195 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80073 |
196 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23956.89000 |
197 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30944.39742 |
198 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
200 | Coil:Heating:Fuel | PSZ-AC_5:5 HEATING COIL | Design Size Nominal Capacity [W] | 30944.39742 |
201 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.21714 |
202 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
203 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.21714 |
204 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2372.44759 |
205 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.21714 |
206 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.21714 |
207 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.21714 |
208 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.46331 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.21714 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.10857 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.47809 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 42466.09000 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 21233.04500 |
214 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.79375 |
215 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.79375 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 42466.09000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 55316.09879 |
218 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
219 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
220 | Coil:Heating:Fuel | PSZ-AC_6:6 HEATING COIL | Design Size Nominal Capacity [W] | 55316.09879 |
221 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.15288 |
222 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
223 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.15288 |
224 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1276.41969 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.15288 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.15288 |
227 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.15288 |
228 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.76090 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.15288 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.57644 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.76859 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 21929.82000 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10964.91000 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.79695 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.79695 |
236 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21929.82000 |
237 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28536.62003 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
240 | Coil:Heating:Fuel | PSZ-AC_7:7 HEATING COIL | Design Size Nominal Capacity [W] | 28536.62003 |
241 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.14754 |
242 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
243 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.14754 |
244 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1270.51178 |
245 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.14754 |
246 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.14754 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.14754 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.75738 |
249 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.14754 |
250 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.57377 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.76503 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 21844.09000 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10922.04500 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.79672 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.79672 |
256 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21844.09000 |
257 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28430.82707 |
258 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
259 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
260 | Coil:Heating:Fuel | PSZ-AC_8:8 HEATING COIL | Design Size Nominal Capacity [W] | 28430.82707 |
261 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.15073 |
262 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
263 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.15073 |
264 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1274.03783 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.15073 |
266 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.15073 |
267 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.15073 |
268 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.75948 |
269 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.15073 |
270 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.57536 |
271 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.76715 |
272 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 21895.73000 |
273 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10947.86500 |
274 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.79685 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.79685 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21895.73000 |
277 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28493.96913 |
278 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
279 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
280 | Coil:Heating:Fuel | PSZ-AC_9:9 HEATING COIL | Design Size Nominal Capacity [W] | 28493.96913 |
281 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.30199 |
282 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
283 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.30199 |
284 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1441.51451 |
285 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.30199 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.30199 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.30199 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.85932 |
289 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.30199 |
290 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.65100 |
291 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.86799 |
292 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 24023.27000 |
293 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 12011.63500 |
294 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80084 |
295 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80084 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 24023.27000 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31493.43077 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
299 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
300 | Coil:Heating:Fuel | PSZ-AC_10:10 HEATING COIL | Design Size Nominal Capacity [W] | 31493.43077 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 43330.4 | 11.25 | 11.25 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 22410.3 | 11.40 | 11.40 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | 23020.6 | 11.40 | 11.40 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | 22891.7 | 11.40 | 11.40 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | 22956.4 | 11.40 | 11.40 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | 40724.9 | 11.27 | 11.27 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | 21024.5 | 11.42 | 11.42 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | 20943.0 | 11.42 | 11.42 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | 20992.1 | 11.42 | 11.42 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | 23001.3 | 11.36 | 11.36 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 58.18 | 78.94 | 58.18 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.199 | 0.190 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.09 | 39.47 | 29.09 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 58.22 | 78.94 | 58.22 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.289 | 0.270 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 6.4103615625E-002 | 7.1123945970E-002 | Pass | Pass | 2.8501745470E-002 | 9.7534541658E-002 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 5.0090119700E-002 | 8.8852599308E-002 | Pass | Pass | 6.4038807866E-002 | 0.2049227098 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 5.9955796809E-002 | 8.2434127667E-002 | Pass | Pass | 2.6308142162E-002 | 0.1214554717 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 5.4428167117E-002 | 6.8687210746E-002 | Pass | Pass | 2.1212260098E-002 | 9.7293322109E-002 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 4.8884006270E-002 | 5.8867945379E-002 | Pass | Pass | 3.1825396138E-002 | 0.1272161681 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 4.9326404467E-002 | 5.7794238690E-002 | Pass | Pass | 2.3582088676E-002 | 9.7234336319E-002 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 4.7963381725E-002 | 5.4987945007E-002 | Pass | Pass | 3.9720286289E-002 | 0.1483210723 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 4.7073208637E-002 | 5.8139493639E-002 | Pass | Pass | 0.1361127330 | 1.0927846760 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 4.7085889785E-002 | 8.3569260221E-002 | Pass | Pass | 0.1532067377 | 0.7645565453 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 5.9479389515E-002 | 0.1758148903 | Pass | Pass | 9.3809516987E-002 | 0.3326883988 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:35
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3193.41 | 40.58 | 0.00 | 139.61 | 857.19 | 4230.82 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:35
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00 | -5.20 | Wetbulb [C] | 2.20 | 20.00 |
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 13.00 | 18.10 | Wetbulb [C] | 3.90 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 6 | |||
Feb | 3.00 | 4 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 18.00 | 7 | |||
Jul | 27.00 | 16 | |||
Aug | 41.00 | 15 | |||
Sep | 0.00 | 0 | |||
Oct | 23.00 | 18 | |||
Nov | 0.00 | 0 | |||
Dec | 7.00 | 7 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:35
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 78.94 | 58.18 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.193 | 0.199 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.09 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 78.94 | 58.22 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.276 | 0.289 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.632 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.632 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.632 | 0.251 | 0.251 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.632 | 0.251 | 0.251 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.632 | 0.251 | 0.251 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.632 | 0.251 | 0.251 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.632 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.632 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.632 | 0.251 | 0.251 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.632 | 0.251 | 0.251 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.632 | 0.251 | 0.251 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.632 | 0.251 | 0.251 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 124.40 | 2.632 | 0.251 | 0.251 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 124.40 | 2.632 | 0.251 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:35
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:35
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 10.1181 | 348.39 | 3525.00 | LightsWired | LTG_SCH_BASE_LPD1 | 84.21 | 168.00 | 84.19 | 0.0000 | Y | 55.71 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 5.1272 | 348.39 | 1786.25 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 168.00 | 97.48 | 0.0000 | Y | 32.69 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 10.2051 | 174.19 | 1777.66 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 85.70 | 168.00 | 85.69 | 0.0000 | Y | 28.59 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 7.7116 | 174.19 | 1343.31 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 168.00 | 97.48 | 0.0000 | Y | 24.58 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 10.1826 | 174.19 | 1773.75 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 22.71 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 6.2585 | 174.19 | 1090.19 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 15.95 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 10.1826 | 174.19 | 1773.75 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 22.71 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 6.2585 | 174.19 | 1090.19 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 15.95 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 10.1826 | 174.19 | 1773.75 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 22.71 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 6.2585 | 174.19 | 1090.19 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 15.95 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 10.0956 | 348.39 | 3517.17 | LightsWired | LTG_SCH_BASE_LPD2 | 62.11 | 168.00 | 61.60 | 0.0000 | Y | 40.67 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 10.1826 | 174.19 | 1773.75 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 20.88 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 10.1826 | 174.19 | 1773.75 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 20.88 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 10.1826 | 174.19 | 1773.75 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 20.88 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 10.1826 | 174.19 | 1773.75 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 20.88 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 6.6105 | 4180.64 | 27636.19 | 381.75 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 343.18 | AstronomicalClock | - | 41.77 | 41.77 | 2.69 | |
EXTERIOR_LIGHTS_B | 5060.12 | AstronomicalClock | - | 83.77 | 71.17 | 67.60 | |
Exterior Lighting Total | 5403.30 | 70.29 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:35
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 45206.36 | 36104.06 | 9102.30 | 0.80 | 3.73 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23386.92 | 18725.67 | 4661.25 | 0.80 | 3.80 | |||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 24024.38 | 19240.41 | 4783.97 | 0.80 | 3.80 | |||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23890.33 | 19112.74 | 4777.59 | 0.80 | 3.80 | |||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23956.89 | 19183.00 | 4773.89 | 0.80 | 3.80 | |||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 42466.09 | 33707.46 | 8758.63 | 0.79 | 3.73 | |||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 21929.82 | 17476.97 | 4452.85 | 0.80 | 3.80 | |||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 21844.09 | 17403.62 | 4440.47 | 0.80 | 3.80 | |||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 21895.73 | 17447.61 | 4448.12 | 0.80 | 3.80 | |||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 24023.27 | 19238.80 | 4784.47 | 0.80 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 43330.4 | 11.25 | 11.25 | ||||
PSZ-AC_2:2 COOLING COIL | 22410.3 | 11.40 | 11.40 | ||||
PSZ-AC_3:3 COOLING COIL | 23020.6 | 11.40 | 11.40 | ||||
PSZ-AC_4:4 COOLING COIL | 22891.7 | 11.40 | 11.40 | ||||
PSZ-AC_5:5 COOLING COIL | 22956.4 | 11.40 | 11.40 | ||||
PSZ-AC_6:6 COOLING COIL | 40724.9 | 11.27 | 11.27 | ||||
PSZ-AC_7:7 COOLING COIL | 21024.5 | 11.42 | 11.42 | ||||
PSZ-AC_8:8 COOLING COIL | 20943.0 | 11.42 | 11.42 | ||||
PSZ-AC_9:9 COOLING COIL | 20992.1 | 11.42 | 11.42 | ||||
PSZ-AC_10:10 COOLING COIL | 23001.3 | 11.36 | 11.36 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 58727.51 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 30340.44 | 0.80 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | 31026.80 | 0.80 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | 30897.21 | 0.80 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | 30944.40 | 0.80 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | 55316.10 | 0.80 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | 28536.62 | 0.80 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | 28430.83 | 0.80 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | 28493.97 | 0.80 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | 31493.43 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.39 | 2556.55 | 1070.05 | 1.00 | 1.29 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.24 | 1377.15 | 1107.16 | 1.00 | 1.35 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.28 | 1415.48 | 1107.16 | 1.00 | 1.35 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.27 | 1408.25 | 1107.16 | 1.00 | 1.35 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.27 | 1410.88 | 1107.16 | 1.00 | 1.35 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.22 | 2372.45 | 1070.05 | 1.00 | 1.30 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.15 | 1276.42 | 1107.16 | 1.00 | 1.37 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.15 | 1270.51 | 1107.16 | 1.00 | 1.37 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.15 | 1274.04 | 1107.16 | 1.00 | 1.37 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.30 | 1441.51 | 1107.16 | 1.00 | 1.34 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.74 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.74 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.74 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.74 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.74 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.74 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.74 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:35
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 23466.31 | 28159.58 | 80.83 | 1.991 | 2.389 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 23.89 | 23.89 | 0.00745 | 38.10 | 0.00687 | 0.411 | 0.00 |
SMSTORE1 | 12217.14 | 14660.57 | 84.16 | 1.037 | 1.244 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 23.89 | 23.89 | 0.00744 | 37.99 | 0.00687 | 0.206 | 0.00 |
SMSTORE2 | 12856.25 | 15427.50 | 88.57 | 1.065 | 1.278 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00771 | 30.95 | 0.00686 | 0.206 | 0.00 |
SMSTORE3 | 12792.37 | 15350.84 | 88.13 | 1.060 | 1.272 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00771 | 30.95 | 0.00686 | 0.206 | 0.00 |
SMSTORE4 | 12815.07 | 15378.08 | 88.28 | 1.062 | 1.274 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00772 | 30.95 | 0.00686 | 0.206 | 0.00 |
LGSTORE2 | 21776.38 | 26131.65 | 75.01 | 1.848 | 2.217 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.89 | 0.00749 | 37.88 | 0.00687 | 0.411 | 0.00 |
SMSTORE5 | 11323.48 | 13588.18 | 78.01 | 0.961 | 1.153 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.89 | 0.00747 | 37.88 | 0.00687 | 0.206 | 0.00 |
SMSTORE6 | 11271.07 | 13525.28 | 77.65 | 0.956 | 1.148 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.89 | 0.00747 | 37.88 | 0.00687 | 0.206 | 0.00 |
SMSTORE7 | 11302.35 | 13562.82 | 77.86 | 0.959 | 1.151 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.89 | 0.00747 | 37.88 | 0.00687 | 0.206 | 0.00 |
SMSTORE8 | 12787.91 | 15345.49 | 88.09 | 1.085 | 1.302 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 23.89 | 23.89 | 0.00741 | 37.45 | 0.00687 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 18629.69 | 22355.63 | 64.17 | 0.926 | 1.111 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00689 | -5.20 | 0.00281 | 0.411 | 0.00 |
SMSTORE1 | 8805.52 | 10566.62 | 60.66 | 0.438 | 0.525 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00679 | -5.20 | 0.00281 | 0.206 | 0.00 |
SMSTORE2 | 8934.88 | 10721.86 | 61.55 | 0.444 | 0.533 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00680 | -5.20 | 0.00281 | 0.206 | 0.00 |
SMSTORE3 | 9037.43 | 10844.92 | 62.26 | 0.449 | 0.539 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00681 | -5.20 | 0.00281 | 0.206 | 0.00 |
SMSTORE4 | 9191.64 | 11029.96 | 63.32 | 0.457 | 0.548 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00682 | -5.20 | 0.00281 | 0.206 | 0.00 |
LGSTORE2 | 17937.97 | 21525.56 | 61.79 | 0.892 | 1.070 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00690 | -5.20 | 0.00281 | 0.411 | 0.00 |
SMSTORE5 | 9537.37 | 11444.84 | 65.70 | 0.474 | 0.569 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00685 | -5.20 | 0.00281 | 0.206 | 0.00 |
SMSTORE6 | 9531.43 | 11437.71 | 65.66 | 0.474 | 0.569 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00685 | -5.20 | 0.00281 | 0.206 | 0.00 |
SMSTORE7 | 9759.98 | 11711.97 | 67.24 | 0.485 | 0.582 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00687 | -5.20 | 0.00281 | 0.206 | 0.00 |
SMSTORE8 | 11689.81 | 14027.78 | 80.53 | 0.581 | 0.697 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00692 | -5.20 | 0.00281 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.39 | 2.39 | 1.11 | 1.11 | 2.3892 | 2.3892 | 2.3892 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.24 | 1.24 | 0.53 | 0.53 | 1.2439 | 1.2439 | 1.2439 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 1.28 | 1.28 | 0.53 | 0.53 | 1.2785 | 1.2785 | 1.2785 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 1.27 | 1.27 | 0.54 | 0.54 | 1.2719 | 1.2719 | 1.2719 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.27 | 1.27 | 0.55 | 0.55 | 1.2743 | 1.2743 | 1.2743 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 2.22 | 2.22 | 1.07 | 1.07 | 2.2171 | 2.2171 | 2.2171 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 1.15 | 1.15 | 0.57 | 0.57 | 1.1529 | 1.1529 | 1.1529 | 1.0000 | 1.0000 |
PSZ-AC_8:8 | 1.15 | 1.15 | 0.57 | 0.57 | 1.1475 | 1.1475 | 1.1475 | 1.0000 | 1.0000 |
PSZ-AC_9:9 | 1.15 | 1.15 | 0.58 | 0.58 | 1.1507 | 1.1507 | 1.1507 | 1.0000 | 1.0000 |
PSZ-AC_10:10 | 1.30 | 1.30 | 0.70 | 0.70 | 1.3020 | 1.3020 | 1.3020 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 45206.360 | 36104.059 | 2.389190 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 22603.18 | 21674.06 | 1.592793 | 27.34 | 15.12 | 0.00735388 | 12.80 | 9.33 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 25.8338 | 23.89 | 0.00745425 | 35.0939 | 23466.31 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 58727.514 | 58727.514 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 58727.51 | 58727.51 | 2.389191 | 16.58 | 10.07 | 0.00618531 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 17.2225 | 21.11 | 0.00688790 | 38.4342 | 18629.69 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 23386.920 | 18725.673 | 1.243860 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 11693.46 | 11226.39 | 0.829240 | 27.28 | 15.09 | 0.00734245 | 12.80 | 9.33 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 24.8106 | 23.89 | 0.00743581 | 35.0079 | 12215.44 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 30340.441 | 30340.441 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 30340.44 | 30340.44 | 1.243862 | 16.76 | 10.09 | 0.00613290 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 16.5404 | 21.11 | 0.00679177 | 37.9035 | 8805.52 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 24024.380 | 19240.405 | 1.278480 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 12012.19 | 11533.33 | 0.852320 | 27.27 | 15.09 | 0.00734160 | 12.80 | 9.33 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 24.1388 | 23.89 | 0.00743437 | 35.0012 | 12261.95 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 31026.804 | 31026.804 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 31026.80 | 31026.80 | 1.278482 | 16.87 | 10.16 | 0.00615966 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 16.0925 | 21.11 | 0.00680239 | 37.9622 | 8934.88 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 23890.330 | 19112.742 | 1.271950 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 11945.17 | 11469.78 | 0.847967 | 27.26 | 15.08 | 0.00734088 | 12.80 | 9.33 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 24.2627 | 23.89 | 0.00743315 | 34.9956 | 12301.06 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 30897.215 | 30897.215 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 30897.21 | 30897.21 | 1.271945 | 16.85 | 10.16 | 0.00616330 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 16.1752 | 21.11 | 0.00681067 | 38.0079 | 9037.43 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 23956.890 | 19183.001 | 1.274330 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 11978.44 | 11500.16 | 0.849553 | 27.28 | 15.09 | 0.00734229 | 12.80 | 9.33 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 24.2174 | 23.89 | 0.00743552 | 35.0066 | 12225.33 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 30944.397 | 30944.397 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 30944.40 | 30944.40 | 1.274325 | 16.86 | 10.17 | 0.00617504 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 16.1450 | 21.11 | 0.00682323 | 38.0773 | 9191.64 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 42466.090 | 33707.459 | 2.217140 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 21233.04 | 20317.99 | 1.478093 | 27.53 | 15.20 | 0.00737518 | 12.80 | 9.33 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 27.8385 | 23.89 | 0.00749005 | 35.2605 | 21762.54 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 55316.099 | 55316.099 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 55316.10 | 55316.10 | 2.217143 | 16.23 | 9.89 | 0.00614469 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 18.5590 | 21.11 | 0.00690497 | 38.5279 | 17937.97 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 21929.820 | 17476.970 | 1.152880 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 10964.91 | 10509.26 | 0.768587 | 27.47 | 15.17 | 0.00736006 | 12.80 | 9.33 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 26.7685 | 23.89 | 0.00746630 | 35.1498 | 11313.73 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 28536.620 | 28536.620 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 28536.62 | 28536.62 | 1.152879 | 16.41 | 9.95 | 0.00612875 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 17.8457 | 21.11 | 0.00685000 | 38.2251 | 9537.37 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 21844.090 | 17403.623 | 1.147540 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 10922.05 | 10467.13 | 0.765027 | 27.48 | 15.17 | 0.00736113 | 12.80 | 9.33 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 26.8931 | 23.89 | 0.00746821 | 35.1587 | 11261.22 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 28430.827 | 28430.827 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 28430.83 | 28430.83 | 1.147543 | 16.39 | 9.93 | 0.00612506 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 17.9287 | 21.11 | 0.00684959 | 38.2228 | 9531.43 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 21895.730 | 17447.612 | 1.150730 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 10947.86 | 10492.47 | 0.767153 | 27.47 | 15.17 | 0.00736052 | 12.80 | 9.33 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 26.8186 | 23.89 | 0.00746713 | 35.1536 | 11291.04 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 28493.969 | 28493.969 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 28493.97 | 28493.97 | 1.150727 | 16.40 | 9.95 | 0.00614087 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 17.8791 | 21.11 | 0.00686640 | 38.3157 | 9759.98 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 24023.270 | 19238.796 | 1.301990 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 12011.64 | 11548.90 | 0.867993 | 27.09 | 15.01 | 0.00732684 | 12.80 | 9.33 | 0.00700000 | 37.56 | 0.00687061 | 18.01 | 23.7029 | 23.89 | 0.00741262 | 34.9000 | 12768.81 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 31493.431 | 31493.431 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 31493.43 | 31493.43 | 1.301994 | 16.95 | 10.31 | 0.00627358 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 15.8019 | 21.11 | 0.00692391 | 38.6341 | 11689.81 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:41:35
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 45206.360 | 36104.059 | 2.389190 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.5105 | 1004.8586 | 1.0443 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.389191 | 2.49510784 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 22603.18 | 21674.06 | 1.0000 | 1.66340462 | 1.592793 | 27.34 | 15.12 | 0.00735388 | 46239.4 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22603.18 | 38.10 | 0.00687148 | 18.17 | 0.41147883 | 25.8338 | 23.89 | 0.00745425 | 23.89 | 0.00745425 | 35.0939 | 23466.31 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 58727.514 | 58727.514 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.389191 | 2.49510784 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 58727.51 | 58727.51 | 1.0000 | 2.49510784 | 2.389191 | 16.58 | 10.07 | 0.00618531 | 32316.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 58727.51 | -5.20 | 0.00280840 | -5.20 | 0.41147883 | 17.2225 | 21.11 | 0.00688790 | 21.11 | 0.00688790 | 38.4342 | 18629.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23386.920 | 18725.673 | 1.243860 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.4892 | 1004.8586 | 1.0443 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.243862 | 1.29900468 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | Sensible | 11693.46 | 11226.39 | 1.0000 | 0.86600165 | 0.829240 | 27.28 | 15.09 | 0.00734245 | 46147.4 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11693.46 | 38.10 | 0.00687148 | 18.17 | 0.20573941 | 24.8106 | 23.89 | 0.00743581 | 23.89 | 0.00743581 | 35.0079 | 12215.44 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30340.441 | 30340.441 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.243862 | 1.29900468 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 30340.44 | 30340.44 | 1.0000 | 1.29900468 | 1.243862 | 16.76 | 10.09 | 0.00613290 | 32366.4 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30340.44 | -5.20 | 0.00280840 | -5.20 | 0.20573941 | 16.5404 | 21.11 | 0.00679177 | 21.11 | 0.00679177 | 37.9035 | 8805.52 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 24024.380 | 19240.405 | 1.278480 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.4877 | 1004.8586 | 1.0443 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.278482 | 1.33515902 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | Sensible | 12012.19 | 11533.33 | 1.0000 | 0.89010482 | 0.852320 | 27.27 | 15.09 | 0.00734160 | 46136.2 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12012.19 | 38.10 | 0.00687148 | 18.17 | 0.20573941 | 24.1388 | 23.89 | 0.00743437 | 23.89 | 0.00743437 | 35.0012 | 12261.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31026.804 | 31026.804 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.278482 | 1.33515902 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 31026.80 | 31026.80 | 1.0000 | 1.33515902 | 1.278482 | 16.87 | 10.16 | 0.00615966 | 32553.9 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31026.80 | -5.20 | 0.00280840 | -5.20 | 0.20573941 | 16.0925 | 21.11 | 0.00680239 | 21.11 | 0.00680239 | 37.9622 | 8934.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23890.330 | 19112.742 | 1.271950 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.4863 | 1004.8586 | 1.0443 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.271945 | 1.32833280 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | Sensible | 11945.17 | 11469.78 | 1.0000 | 0.88555850 | 0.847967 | 27.26 | 15.08 | 0.00734088 | 46126.8 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11945.17 | 38.10 | 0.00687148 | 18.17 | 0.20573941 | 24.2627 | 23.89 | 0.00743315 | 23.89 | 0.00743315 | 34.9956 | 12301.06 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30897.215 | 30897.215 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.271945 | 1.32833280 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 30897.21 | 30897.21 | 1.0000 | 1.32833280 | 1.271945 | 16.85 | 10.16 | 0.00616330 | 32541.0 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30897.21 | -5.20 | 0.00280840 | -5.20 | 0.20573941 | 16.1752 | 21.11 | 0.00681067 | 21.11 | 0.00681067 | 38.0079 | 9037.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23956.890 | 19183.001 | 1.274330 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.4889 | 1004.8586 | 1.0443 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.274325 | 1.33081832 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | Sensible | 11978.44 | 11500.16 | 1.0000 | 0.88721550 | 0.849553 | 27.28 | 15.09 | 0.00734229 | 46145.1 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11978.44 | 38.10 | 0.00687148 | 18.17 | 0.20573941 | 24.2174 | 23.89 | 0.00743552 | 23.89 | 0.00743552 | 35.0066 | 12225.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30944.397 | 30944.397 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.274325 | 1.33081832 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 30944.40 | 30944.40 | 1.0000 | 1.33081832 | 1.274325 | 16.86 | 10.17 | 0.00617504 | 32578.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30944.40 | -5.20 | 0.00280840 | -5.20 | 0.20573941 | 16.1450 | 21.11 | 0.00682323 | 21.11 | 0.00682323 | 38.0773 | 9191.64 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 42466.090 | 33707.459 | 2.217140 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.5501 | 1004.8586 | 1.0443 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.217143 | 2.31543257 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 21233.04 | 20317.99 | 1.0000 | 1.54361977 | 1.478093 | 27.53 | 15.20 | 0.00737518 | 46488.8 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21233.04 | 38.10 | 0.00687148 | 18.17 | 0.41147883 | 27.8385 | 23.89 | 0.00749005 | 23.89 | 0.00749005 | 35.2605 | 21762.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 55316.099 | 55316.099 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.217143 | 2.31543257 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 55316.10 | 55316.10 | 1.0000 | 2.31543257 | 2.217143 | 16.23 | 9.89 | 0.00614469 | 31856.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 55316.10 | -5.20 | 0.00280840 | -5.20 | 0.41147883 | 18.5590 | 21.11 | 0.00690497 | 21.11 | 0.00690497 | 38.5279 | 17937.97 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21929.820 | 17476.970 | 1.152880 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.5220 | 1004.8586 | 1.0443 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.152879 | 1.20398778 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 10964.91 | 10509.26 | 1.0000 | 0.80265944 | 0.768587 | 27.47 | 15.17 | 0.00736006 | 46383.2 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10964.91 | 38.10 | 0.00687148 | 18.17 | 0.20573941 | 26.7685 | 23.89 | 0.00746630 | 23.89 | 0.00746630 | 35.1498 | 11313.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28536.620 | 28536.620 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.152879 | 1.20398778 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 28536.62 | 28536.62 | 1.0000 | 1.20398778 | 1.152879 | 16.41 | 9.95 | 0.00612875 | 32006.9 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28536.62 | -5.20 | 0.00280840 | -5.20 | 0.20573941 | 17.8457 | 21.11 | 0.00685000 | 21.11 | 0.00685000 | 38.2251 | 9537.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21844.090 | 17403.623 | 1.147540 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.5240 | 1004.8586 | 1.0443 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.147543 | 1.19841512 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 10922.05 | 10467.13 | 1.0000 | 0.79894162 | 0.765027 | 27.48 | 15.17 | 0.00736113 | 46397.9 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10922.05 | 38.10 | 0.00687148 | 18.17 | 0.20573941 | 26.8931 | 23.89 | 0.00746821 | 23.89 | 0.00746821 | 35.1587 | 11261.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28430.827 | 28430.827 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.147543 | 1.19841512 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 28430.83 | 28430.83 | 1.0000 | 1.19841512 | 1.147543 | 16.39 | 9.93 | 0.00612506 | 31975.4 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28430.83 | -5.20 | 0.00280840 | -5.20 | 0.20573941 | 17.9287 | 21.11 | 0.00684959 | 21.11 | 0.00684959 | 38.2228 | 9531.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21895.730 | 17447.612 | 1.150730 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.5228 | 1004.8586 | 1.0443 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.150727 | 1.20174107 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 10947.86 | 10492.47 | 1.0000 | 0.80116257 | 0.767153 | 27.47 | 15.17 | 0.00736052 | 46389.5 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10947.86 | 38.10 | 0.00687148 | 18.17 | 0.20573941 | 26.8186 | 23.89 | 0.00746713 | 23.89 | 0.00746713 | 35.1536 | 11291.04 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28493.969 | 28493.969 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.150727 | 1.20174107 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 28493.97 | 28493.97 | 1.0000 | 1.20174107 | 1.150727 | 16.40 | 9.95 | 0.00614087 | 32028.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28493.97 | -5.20 | 0.00280840 | -5.20 | 0.20573941 | 17.8791 | 21.11 | 0.00686640 | 21.11 | 0.00686640 | 38.3157 | 9759.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 24023.270 | 19238.796 | 1.301990 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.4602 | 1004.8586 | 1.0443 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.301994 | 1.35971410 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | Sensible | 12011.64 | 11548.90 | 1.0000 | 0.90647298 | 0.867993 | 27.09 | 15.01 | 0.00732684 | 45916.4 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12011.64 | 37.56 | 0.00687061 | 18.01 | 0.20573941 | 23.7029 | 23.89 | 0.00741262 | 23.89 | 0.00741262 | 34.9000 | 12768.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31493.431 | 31493.431 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.301994 | 1.35971410 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 31493.43 | 31493.43 | 1.0000 | 1.35971410 | 1.301994 | 16.95 | 10.31 | 0.00627358 | 32919.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31493.43 | -5.20 | 0.00280840 | -5.20 | 0.20573941 | 15.8019 | 21.11 | 0.00692391 | 21.11 | 0.00692391 | 38.6341 | 11689.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:35
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 2.39 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.24 | - | |||
PSZ-AC_3:3_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.28 | - | |||
PSZ-AC_4:4_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.27 | - | |||
PSZ-AC_5:5_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.27 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 2.22 | - | |||
PSZ-AC_7:7_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.15 | - | |||
PSZ-AC_8:8_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.15 | - | |||
PSZ-AC_9:9_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.15 | - | |||
PSZ-AC_10:10_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.30 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 2405.17 | 2870.67 | 354.17 |
SMSTORE1 | 2168.00 | 2670.50 | 97.00 |
SMSTORE2 | 1778.00 | 2035.17 | 166.00 |
SMSTORE3 | 1793.00 | 2047.67 | 180.17 |
SMSTORE4 | 1795.50 | 2090.17 | 212.67 |
LGSTORE2 | 1650.17 | 2018.50 | 275.50 |
SMSTORE5 | 1610.67 | 2068.17 | 295.67 |
SMSTORE6 | 1620.33 | 2084.83 | 316.17 |
SMSTORE7 | 1680.50 | 2106.17 | 378.17 |
SMSTORE8 | 1952.67 | 2115.17 | 578.67 |
Facility | 2953.83 | 3263.17 | 818.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 0.67 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 0.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.67 | 0.00 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:35
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 1.043 | 0.224 | 0.000 | 0.000 |
SMSTORE1 | 8.47 | 28.12 | 902.60 | 0.906 | 0.239 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 1.103 | 0.312 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 1.095 | 0.312 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 1.082 | 0.312 | 0.000 | 0.000 |
LGSTORE2 | 24.75 | 56.25 | 1805.20 | 1.014 | 0.299 | 0.000 | 0.000 |
SMSTORE5 | 12.38 | 28.12 | 902.60 | 1.020 | 0.332 | 0.000 | 0.000 |
SMSTORE6 | 12.38 | 28.12 | 902.60 | 1.014 | 0.332 | 0.000 | 0.000 |
SMSTORE7 | 12.38 | 28.12 | 902.60 | 1.005 | 0.332 | 0.000 | 0.000 |
SMSTORE8 | 12.38 | 28.12 | 902.60 | 1.027 | 0.351 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.47 | 28.12 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 0.810 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 0.810 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 0.810 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.75 | 56.25 | 1805.20 | 0.809 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.38 | 28.12 | 902.60 | 0.809 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.38 | 28.12 | 902.60 | 0.808 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.38 | 28.12 | 902.60 | 0.807 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.38 | 28.12 | 902.60 | 0.807 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:41:35
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 16.93 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE1 | PSZ-AC_2:2 | 8.47 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE2 | PSZ-AC_3:3 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE3 | PSZ-AC_4:4 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE4 | PSZ-AC_5:5 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
LGSTORE2 | PSZ-AC_6:6 | 24.75 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE5 | PSZ-AC_7:7 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE6 | PSZ-AC_8:8 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE7 | PSZ-AC_9:9 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE8 | PSZ-AC_10:10 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
Total Facility | 120.88 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 2.469 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 10815468.32 | 0.00 | 10815468.32 | 2654475.14 | 13469943.46 | 12976396.34 | 3171.06 | 4311.24 | 1277.70 | 0.17 |
SMSTORE1 | 4696355.36 | 0.00 | 4696355.36 | 1335957.27 | 6032312.63 | 6488198.17 | 4393.63 | 3085.39 | 1280.97 | 0.33 |
SMSTORE2 | 4309280.99 | 0.00 | 4309280.99 | 1373148.37 | 5682429.36 | 6488198.17 | 4362.14 | 3429.13 | 968.73 | 7.53 |
SMSTORE3 | 4281661.48 | 0.00 | 4281661.48 | 1373148.37 | 5654809.85 | 6488198.17 | 4361.42 | 3453.28 | 945.30 | 12.25 |
SMSTORE4 | 4228620.18 | 0.00 | 4228620.18 | 1373148.37 | 5601768.56 | 6488198.17 | 4362.14 | 3505.81 | 892.05 | 6.72 |
LGSTORE2 | 7257323.72 | 0.00 | 7257323.72 | 2517694.69 | 9775018.41 | 12976396.34 | 4729.02 | 3316.68 | 714.30 | 1.81 |
SMSTORE5 | 3651066.46 | 0.00 | 3651066.46 | 1381417.89 | 5032484.36 | 6488198.17 | 4729.50 | 3333.73 | 696.77 | 1.17 |
SMSTORE6 | 3629816.76 | 0.00 | 3629816.76 | 1381417.89 | 5011234.65 | 6488198.17 | 4729.50 | 3353.19 | 677.31 | 0.83 |
SMSTORE7 | 3597910.42 | 0.00 | 3597910.42 | 1381417.89 | 4979328.31 | 6488198.17 | 4729.50 | 3396.96 | 633.54 | 0.83 |
SMSTORE8 | 3682824.94 | 0.00 | 3682824.94 | 1677310.53 | 5360135.46 | 6488198.17 | 4727.21 | 3430.62 | 602.17 | 4.21 |
Total Facility | 50150328.62 | 0.00 | 50150328.62 | 16449136.43 | 66599465.05 | 77858378.04 | 4729.67 | 4833.98 | 1607.28 | 17.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.5144 | 0.0000 | 0.5144 | 0.1106 | 0.6250 | 0.4115 | 251.06 | 4311.24 | 1277.70 |
SMSTORE1 | 0.2234 | 0.0000 | 0.2234 | 0.0589 | 0.2823 | 0.2057 | 1473.63 | 3085.39 | 1280.97 |
SMSTORE2 | 0.2719 | 0.0000 | 0.2719 | 0.0769 | 0.3488 | 0.2057 | 0.00 | 3429.13 | 965.87 |
SMSTORE3 | 0.2700 | 0.0000 | 0.2700 | 0.0769 | 0.3469 | 0.2057 | 0.00 | 3453.28 | 941.72 |
SMSTORE4 | 0.2669 | 0.0000 | 0.2669 | 0.0769 | 0.3437 | 0.2057 | 0.00 | 3505.64 | 889.36 |
LGSTORE2 | 0.5000 | 0.0000 | 0.5000 | 0.1476 | 0.6476 | 0.4115 | 0.00 | 3316.68 | 713.32 |
SMSTORE5 | 0.2516 | 0.0000 | 0.2516 | 0.0820 | 0.3336 | 0.2057 | 0.00 | 3333.73 | 696.27 |
SMSTORE6 | 0.2501 | 0.0000 | 0.2501 | 0.0820 | 0.3321 | 0.2057 | 0.00 | 3353.19 | 676.81 |
SMSTORE7 | 0.2479 | 0.0000 | 0.2479 | 0.0820 | 0.3299 | 0.2057 | 0.00 | 3396.96 | 633.04 |
SMSTORE8 | 0.2535 | 0.0000 | 0.2535 | 0.0865 | 0.3400 | 0.2057 | 0.00 | 3430.62 | 599.38 |
Total Facility | 3.0498 | 0.0000 | 3.0498 | 0.8803 | 3.9300 | 2.4689 | 1578.50 | 4833.82 | 1601.05 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 11795705.74 | 0.00 | 11795705.74 | 12976396.34 | 3170.48 | 0.00 | 5589.52 | 0.17 |
PSZ-AC_2:2 | 5121985.29 | 0.00 | 5121985.29 | 6488198.17 | 4375.60 | 4.00 | 4380.40 | 0.33 |
PSZ-AC_3:3 | 4699838.89 | 0.00 | 4699838.89 | 6488198.17 | 4362.14 | 0.00 | 4397.86 | 7.36 |
PSZ-AC_4:4 | 4669716.51 | 0.00 | 4669716.51 | 6488198.17 | 4360.92 | 0.00 | 4399.08 | 11.92 |
PSZ-AC_5:5 | 4611868.36 | 0.00 | 4611868.36 | 6488198.17 | 4362.14 | 0.00 | 4397.86 | 6.56 |
PSZ-AC_6:6 | 7915075.48 | 0.00 | 7915075.48 | 12976396.34 | 4728.85 | 0.00 | 4031.15 | 1.81 |
PSZ-AC_7:7 | 3981968.53 | 0.00 | 3981968.53 | 6488198.17 | 4729.50 | 0.00 | 4030.50 | 1.17 |
PSZ-AC_8:8 | 3958788.10 | 0.00 | 3958788.10 | 6488198.17 | 4729.50 | 0.00 | 4030.50 | 0.83 |
PSZ-AC_9:9 | 3923974.73 | 0.00 | 3923974.73 | 6488198.17 | 4729.50 | 0.00 | 4030.50 | 0.83 |
PSZ-AC_10:10 | 4016563.76 | 0.00 | 4016563.76 | 6488198.17 | 4727.04 | 0.00 | 4032.96 | 4.21 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.5611 | 0.0000 | 0.5611 | 0.4115 | 250.48 | 0.00 | 5589.52 |
PSZ-AC_2:2 | 0.2436 | 0.0000 | 0.2436 | 0.2057 | 1455.60 | 4.00 | 4380.40 |
PSZ-AC_3:3 | 0.2966 | 0.0000 | 0.2966 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_4:4 | 0.2945 | 0.0000 | 0.2945 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_5:5 | 0.2910 | 0.0000 | 0.2910 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_6:6 | 0.5453 | 0.0000 | 0.5453 | 0.4115 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_7:7 | 0.2744 | 0.0000 | 0.2744 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_8:8 | 0.2728 | 0.0000 | 0.2728 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_9:9 | 0.2704 | 0.0000 | 0.2704 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_10:10 | 0.2764 | 0.0000 | 0.2764 | 0.2057 | 0.00 | 0.00 | 4030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 5108.28 | 490.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 4376.13 | 867.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 4017.86 | 384.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 4032.53 | 374.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 4055.27 | 346.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 3781.07 | 250.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 3782.64 | 248.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 3792.85 | 237.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 3817.41 | 213.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 3815.03 | 219.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.5676 | 0.7703 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.2673 | 0.2921 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 0.2862 | 0.4076 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 0.2847 | 0.4038 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 0.2815 | 0.4059 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 0.5319 | 0.7513 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.2672 | 0.3862 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.2659 | 0.3843 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.2639 | 0.3886 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.2682 | 0.4239 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:35
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 759 |
Defaulted Fields | 823 |
Fields with Defaults | 2681 |
Autosized Fields | 184 |
Autosizable Fields | 458 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:41:35
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 928.91 | 2912.14 | 01-JAN-07:20 | 87832.64 | 15-JUN-14:40 |
Electricity:Building | 510.47 | 1694.14 | 01-JAN-00:10 | 31739.81 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 114.75 | 316.43 | 01-JAN-00:10 | 5937.46 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 510.47 | 1694.14 | 01-JAN-00:10 | 31739.81 | 01-JAN-11:10 |
InteriorLights:Electricity | 381.75 | 1244.72 | 01-JAN-00:10 | 23650.28 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 88.39 | 241.52 | 01-JAN-00:10 | 4589.20 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 381.75 | 1244.72 | 01-JAN-00:10 | 23650.28 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 381.75 | 1244.72 | 01-JAN-00:10 | 23650.28 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 88.39 | 241.52 | 01-JAN-00:10 | 4589.20 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 381.75 | 1244.72 | 01-JAN-00:10 | 23650.28 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 66.35 | 182.75 | 01-JAN-00:10 | 3434.71 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 53.17 | 145.29 | 01-JAN-00:10 | 2760.58 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 53.17 | 145.29 | 01-JAN-00:10 | 2760.58 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 49.13 | 169.56 | 01-JAN-00:10 | 3184.23 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 38.67 | 132.11 | 01-JAN-00:10 | 2510.11 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 38.67 | 132.11 | 01-JAN-00:10 | 2510.11 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 49.13 | 169.56 | 01-JAN-00:10 | 3184.23 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 38.67 | 132.11 | 01-JAN-00:10 | 2510.11 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 38.67 | 132.11 | 01-JAN-00:10 | 2510.11 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 49.13 | 169.56 | 01-JAN-00:10 | 3184.23 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 38.67 | 132.11 | 01-JAN-00:10 | 2510.11 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 38.67 | 132.11 | 01-JAN-00:10 | 2510.11 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 59.93 | 226.07 | 01-JAN-00:10 | 4220.73 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 40.67 | 151.17 | 01-JAN-00:10 | 2872.47 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 40.67 | 151.17 | 01-JAN-00:10 | 2872.47 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 30.51 | 115.05 | 01-JAN-00:10 | 2148.56 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 20.88 | 77.60 | 01-JAN-00:10 | 1474.43 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 20.88 | 77.60 | 01-JAN-00:10 | 1474.43 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 30.51 | 115.05 | 01-JAN-00:10 | 2148.56 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 20.88 | 77.60 | 01-JAN-00:10 | 1474.43 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 20.88 | 77.60 | 01-JAN-00:10 | 1474.43 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 30.51 | 115.05 | 01-JAN-00:10 | 2148.56 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 20.88 | 77.60 | 01-JAN-00:10 | 1474.43 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 20.88 | 77.60 | 01-JAN-00:10 | 1474.43 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 30.51 | 115.05 | 01-JAN-00:10 | 2148.56 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 20.88 | 77.60 | 01-JAN-00:10 | 1474.43 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 20.88 | 77.60 | 01-JAN-00:10 | 1474.43 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.36 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.36 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.18 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.18 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.26 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.26 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
ElectricityPurchased:Facility | 928.91 | 2912.14 | 01-JAN-07:20 | 87832.64 | 15-JUN-14:40 |
ElectricityPurchased:Plant | 928.91 | 2912.14 | 01-JAN-07:20 | 87832.64 | 15-JUN-14:40 |
Cogeneration:ElectricityPurchased | 928.91 | 2912.14 | 01-JAN-07:20 | 87832.64 | 15-JUN-14:40 |
General:Cogeneration:ElectricityPurchased | 928.91 | 2912.14 | 01-JAN-07:20 | 87832.64 | 15-JUN-14:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 928.91 | 2912.14 | 01-JAN-07:20 | 87832.64 | 15-JUN-14:40 |
ElectricityNet:Plant | 928.91 | 2912.14 | 01-JAN-07:20 | 87832.64 | 15-JUN-14:40 |
Cogeneration:ElectricityNet | 928.91 | 2912.14 | 01-JAN-07:20 | 87832.64 | 15-JUN-14:40 |
General:Cogeneration:ElectricityNet | 928.91 | 2912.14 | 01-JAN-07:20 | 87832.64 | 15-JUN-14:40 |
Electricity:HVAC | 290.21 | 0.00 | 01-JAN-00:10 | 51138.94 | 15-JUN-15:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 179.30 | 0.00 | 01-JAN-00:10 | 43107.59 | 15-JUN-15:00 |
General:Cooling:Electricity | 179.30 | 0.00 | 01-JAN-00:10 | 43107.59 | 15-JUN-15:00 |
Fans:Electricity | 110.91 | 0.00 | 01-JAN-00:10 | 9157.93 | 27-DEC-09:10 |
General:Fans:Electricity | 110.91 | 0.00 | 01-JAN-00:10 | 9157.93 | 27-DEC-09:10 |
ExteriorLights:Electricity | 70.29 | 0.00 | 01-JAN-07:20 | 5403.30 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 70.29 | 0.00 | 01-JAN-07:20 | 5403.30 | 01-JAN-06:10 |
Electricity:Plant | 57.94 | 1218.00 | 02-JAN-09:10 | 11249.83 | 09-JAN-18:40 |
WaterSystems:Electricity | 57.94 | 1218.00 | 02-JAN-09:10 | 11249.83 | 09-JAN-18:40 |
Water Heater:WaterSystems:Electricity | 57.94 | 1218.00 | 02-JAN-09:10 | 11249.83 | 09-JAN-18:40 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 56.52 | 0.00 | 01-JAN-00:10 | 132964.28 | 27-DEC-09:10 |
NaturalGas:HVAC | 56.52 | 0.00 | 01-JAN-00:10 | 132964.28 | 27-DEC-09:10 |
Heating:NaturalGas | 56.52 | 0.00 | 01-JAN-00:10 | 132964.28 | 27-DEC-09:10 |
General:Heating:NaturalGas | 56.52 | 0.00 | 01-JAN-00:10 | 132964.28 | 27-DEC-09:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1313.95 | 0.00 | 01-JAN-00:10 | 244279.99 | 03-JUL-14:10 |
EnergyTransfer:Building | 602.15 | 0.00 | 01-JAN-00:10 | 101205.14 | 03-JUL-13:00 |
EnergyTransfer:Zone:LGSTORE1 | 127.17 | 0.00 | 01-JAN-00:10 | 16901.80 | 07-AUG-16:10 |
Heating:EnergyTransfer | 16.58 | 0.00 | 01-JAN-00:10 | 64548.58 | 27-DEC-09:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 1.78 | 0.00 | 01-JAN-00:10 | 13475.49 | 03-FEB-09:10 |
General:Heating:EnergyTransfer | 16.58 | 0.00 | 01-JAN-00:10 | 64548.58 | 27-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 1.78 | 0.00 | 01-JAN-00:10 | 13475.49 | 03-FEB-09:10 |
Cooling:EnergyTransfer | 585.57 | 0.00 | 01-JAN-00:10 | 101205.14 | 03-JUL-13:00 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 125.39 | 0.00 | 01-JAN-00:10 | 16901.80 | 07-AUG-16:10 |
General:Cooling:EnergyTransfer | 585.57 | 0.00 | 01-JAN-00:10 | 101205.14 | 03-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 125.39 | 0.00 | 01-JAN-00:10 | 16901.80 | 07-AUG-16:10 |
EnergyTransfer:Zone:SMSTORE1 | 68.26 | 0.00 | 01-JAN-00:10 | 9351.54 | 20-APR-22:00 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 0.65 | 0.00 | 01-JAN-00:10 | 4078.13 | 03-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 0.65 | 0.00 | 01-JAN-00:10 | 4078.13 | 03-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 67.60 | 0.00 | 01-JAN-00:10 | 9351.54 | 20-APR-22:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 67.60 | 0.00 | 01-JAN-00:10 | 9351.54 | 20-APR-22:00 |
EnergyTransfer:Zone:SMSTORE2 | 52.23 | 0.00 | 01-JAN-00:10 | 8570.55 | 03-JUL-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 1.37 | 0.00 | 01-JAN-00:10 | 5823.09 | 27-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 1.37 | 0.00 | 01-JAN-00:10 | 5823.09 | 27-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 50.86 | 0.00 | 01-JAN-00:10 | 8570.55 | 03-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 50.86 | 0.00 | 01-JAN-00:10 | 8570.55 | 03-JUL-13:00 |
EnergyTransfer:Zone:SMSTORE3 | 51.83 | 0.00 | 01-JAN-00:10 | 8676.52 | 03-JUL-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 1.42 | 0.00 | 01-JAN-00:10 | 5853.23 | 03-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 1.42 | 0.00 | 01-JAN-00:10 | 5853.23 | 03-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 50.40 | 0.00 | 01-JAN-00:10 | 8676.52 | 03-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 50.40 | 0.00 | 01-JAN-00:10 | 8676.52 | 03-JUL-13:00 |
EnergyTransfer:Zone:SMSTORE4 | 49.91 | 0.00 | 01-JAN-00:10 | 8615.43 | 03-JUL-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 1.55 | 0.00 | 01-JAN-00:10 | 6748.69 | 28-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 1.55 | 0.00 | 01-JAN-00:10 | 6748.69 | 28-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 48.36 | 0.00 | 01-JAN-00:10 | 8615.43 | 03-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 48.36 | 0.00 | 01-JAN-00:10 | 8615.43 | 03-JUL-13:00 |
EnergyTransfer:Zone:LGSTORE2 | 82.89 | 0.00 | 01-JAN-00:10 | 16344.67 | 27-DEC-09:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 2.35 | 0.00 | 01-JAN-00:10 | 14151.68 | 27-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 2.35 | 0.00 | 01-JAN-00:10 | 14151.68 | 27-DEC-09:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 80.54 | 0.00 | 01-JAN-00:10 | 16061.02 | 03-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 80.54 | 0.00 | 01-JAN-00:10 | 16061.02 | 03-JUL-13:00 |
EnergyTransfer:Zone:SMSTORE5 | 42.15 | 0.00 | 01-JAN-00:10 | 8479.46 | 27-DEC-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 1.35 | 0.00 | 01-JAN-00:10 | 7391.66 | 27-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 1.35 | 0.00 | 01-JAN-00:10 | 7391.66 | 27-DEC-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 40.80 | 0.00 | 01-JAN-00:10 | 8423.74 | 03-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 40.80 | 0.00 | 01-JAN-00:10 | 8423.74 | 03-JUL-13:00 |
EnergyTransfer:Zone:SMSTORE6 | 41.56 | 0.00 | 01-JAN-00:10 | 8690.81 | 27-DEC-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 1.43 | 0.00 | 01-JAN-00:10 | 7603.04 | 27-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 1.43 | 0.00 | 01-JAN-00:10 | 7603.04 | 27-DEC-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 40.13 | 0.00 | 01-JAN-00:10 | 8392.11 | 03-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 40.13 | 0.00 | 01-JAN-00:10 | 8392.11 | 03-JUL-13:00 |
EnergyTransfer:Zone:SMSTORE7 | 40.81 | 0.00 | 01-JAN-00:10 | 8921.64 | 26-DEC-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 1.69 | 0.00 | 01-JAN-00:10 | 7966.21 | 26-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 1.69 | 0.00 | 01-JAN-00:10 | 7966.21 | 26-DEC-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 39.12 | 0.00 | 01-JAN-00:10 | 8482.20 | 03-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 39.12 | 0.00 | 01-JAN-00:10 | 8482.20 | 03-JUL-13:00 |
EnergyTransfer:Zone:SMSTORE8 | 45.34 | 0.00 | 01-JAN-00:10 | 10607.35 | 02-MAR-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 2.99 | 0.00 | 01-JAN-00:10 | 10080.47 | 02-MAR-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 2.99 | 0.00 | 01-JAN-00:10 | 10080.47 | 02-MAR-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 42.35 | 0.00 | 01-JAN-00:10 | 9976.87 | 03-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 42.35 | 0.00 | 01-JAN-00:10 | 9976.87 | 03-JUL-13:00 |
EnergyTransfer:HVAC | 711.81 | 0.00 | 01-JAN-00:10 | 145690.64 | 26-JUL-14:10 |
HeatingCoils:EnergyTransfer | 45.22 | 0.00 | 01-JAN-00:10 | 106371.43 | 27-DEC-09:10 |
CoolingCoils:EnergyTransfer | 666.59 | 0.00 | 01-JAN-00:10 | 145690.64 | 26-JUL-14:10 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:35
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 1.778 | -125.390 | 0.000 | 0.000 | 24.114 | 88.395 | 26.357 | 21.555 | 0.000 | 7.105 | 0.001 | 0.000 | -7.904 | 0.000 | -12.865 | -23.146 |
SMSTORE1 | 0.000 | 0.000 | 0.655 | -67.603 | 0.000 | 0.000 | 11.897 | 53.173 | 13.179 | 10.695 | 0.000 | 3.823 | 0.000 | 0.000 | -4.137 | 0.000 | -6.281 | -15.400 |
SMSTORE2 | 0.000 | 0.000 | 1.369 | -50.859 | 0.000 | 0.000 | 7.213 | 38.666 | 10.467 | 10.643 | 0.000 | 3.767 | 0.001 | 0.000 | -4.154 | 0.000 | -6.418 | -10.693 |
SMSTORE3 | 0.000 | 0.000 | 1.422 | -50.403 | 0.000 | 0.000 | 7.225 | 38.666 | 10.467 | 10.654 | 0.000 | 3.765 | 0.000 | 0.000 | -4.122 | 0.000 | -6.367 | -11.307 |
SMSTORE4 | 0.000 | 0.000 | 1.547 | -48.361 | 0.000 | 0.000 | 7.243 | 38.666 | 10.467 | 10.681 | 0.000 | 3.768 | 0.001 | 0.000 | -4.065 | 0.000 | -6.290 | -13.657 |
LGSTORE2 | 0.000 | 0.000 | 2.353 | -80.540 | 0.000 | 0.000 | 24.927 | 40.672 | 19.261 | 21.490 | 0.000 | 6.806 | 0.000 | 0.000 | -7.831 | 0.000 | -11.491 | -15.647 |
SMSTORE5 | 0.000 | 0.000 | 1.352 | -40.802 | 0.000 | 0.000 | 12.475 | 20.877 | 9.631 | 10.748 | 0.000 | 3.781 | 0.001 | 0.000 | -3.892 | 0.000 | -6.205 | -7.964 |
SMSTORE6 | 0.000 | 0.000 | 1.425 | -40.130 | 0.000 | 0.000 | 12.487 | 20.877 | 9.631 | 10.761 | 0.000 | 3.782 | 0.001 | 0.000 | -3.870 | 0.000 | -6.173 | -8.790 |
SMSTORE7 | 0.000 | 0.000 | 1.692 | -39.118 | 0.000 | 0.000 | 12.513 | 20.877 | 9.631 | 10.786 | 0.000 | 3.783 | 0.000 | 0.000 | -3.817 | 0.000 | -6.099 | -10.247 |
SMSTORE8 | 0.000 | 0.000 | 2.989 | -42.351 | 0.000 | 0.000 | 12.547 | 20.877 | 9.631 | 10.807 | 0.000 | 4.020 | 0.000 | 0.000 | -3.632 | 0.000 | -7.951 | -6.937 |
Total Facility | 0.000 | 0.000 | 16.582 | -585.558 | 0.000 | 0.000 | 132.642 | 381.746 | 128.721 | 128.819 | 0.000 | 44.400 | 0.007 | 0.000 | -47.423 | 0.000 | -76.140 | -123.789 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 11-SEP-08:62 | 0.00 | 0.00 | 0.00 | -44248.18 | 0.00 | 0.00 | 174.12 | 2415.36 | 749.03 | 724.51 | 0.00 | 0.00 | 40314.86 | 0.00 | -0.00 | 0.00 | -129.70 | 0.00 |
SMSTORE1 | 11-SEP-08:62 | 0.00 | 0.00 | 0.00 | -23097.86 | 0.00 | 0.00 | 85.29 | 1452.94 | 374.52 | 357.52 | 0.00 | 0.00 | 20894.32 | 0.00 | -0.00 | 0.00 | -66.72 | 0.00 |
SMSTORE2 | 11-SEP-07:02 | 0.00 | 0.00 | 0.00 | -25875.89 | 0.00 | 0.00 | 84.38 | 1321.11 | 374.52 | 0.00 | 0.00 | 0.00 | 24235.91 | 0.00 | -18.85 | 0.00 | -121.17 | 0.00 |
SMSTORE3 | 11-SEP-07:02 | 0.00 | 0.00 | 0.00 | -25802.93 | 0.00 | 0.00 | 83.79 | 1321.11 | 374.52 | 0.00 | 0.00 | 0.00 | 24167.07 | 0.00 | -20.63 | 0.00 | -122.93 | 0.00 |
SMSTORE4 | 11-SEP-07:02 | 0.00 | 0.00 | 0.00 | -25806.78 | 0.00 | 0.00 | 84.35 | 1321.11 | 374.52 | 0.00 | 0.00 | 0.00 | 24167.39 | 0.00 | -19.26 | 0.00 | -121.33 | 0.00 |
LGSTORE2 | 11-SEP-08:62 | 0.00 | 0.00 | 0.00 | -42242.57 | 0.00 | 0.00 | 374.41 | 1511.82 | 749.03 | 705.45 | 0.00 | 0.00 | 39029.09 | 0.00 | -0.00 | 0.00 | -127.23 | 0.00 |
SMSTORE5 | 11-SEP-08:62 | 0.00 | 0.00 | 0.00 | -21705.95 | 0.00 | 0.00 | 188.14 | 776.01 | 374.52 | 353.12 | 0.00 | 0.00 | 20081.84 | 0.00 | -0.00 | 0.00 | -67.68 | 0.00 |
SMSTORE6 | 11-SEP-08:62 | 0.00 | 0.00 | 0.00 | -21603.12 | 0.00 | 0.00 | 188.55 | 776.01 | 374.52 | 353.65 | 0.00 | 0.00 | 19977.62 | 0.00 | -0.00 | 0.00 | -67.23 | 0.00 |
SMSTORE7 | 11-SEP-08:62 | 0.00 | 0.00 | 0.00 | -21624.70 | 0.00 | 0.00 | 188.99 | 776.01 | 374.52 | 353.86 | 0.00 | 0.00 | 19997.84 | 0.00 | -0.00 | 0.00 | -66.52 | 0.00 |
SMSTORE8 | 11-SEP-08:62 | 0.00 | 0.00 | 0.00 | -23680.69 | 0.00 | 0.00 | 187.48 | 776.01 | 374.52 | 350.30 | 0.00 | 0.00 | 22075.62 | 0.00 | -0.00 | 0.00 | -83.23 | 0.00 |
Total Facility | 11-SEP-08:62 | 0.00 | 0.00 | 0.00 | -208336.46 | 0.00 | 0.00 | 1978.01 | 16014.49 | 5393.02 | 4315.05 | 0.00 | 0.00 | 181400.68 | 0.00 | 0.00 | 0.00 | -764.79 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 03-MAR-09:01 | 0.00 | 0.00 | 54058.46 | 0.00 | 0.00 | 0.00 | 245.56 | 2415.36 | 749.03 | 278.31 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -401.66 | -57345.06 |
SMSTORE1 | 03-FEB-09:01 | 0.00 | 0.00 | 26103.40 | 0.00 | 0.00 | 0.00 | 121.91 | 1452.94 | 374.52 | 1006.91 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -366.29 | -28693.39 |
SMSTORE2 | 27-DEC-08:62 | 0.00 | 0.00 | 25606.82 | 0.00 | 0.00 | 0.00 | 123.65 | 1321.11 | 374.52 | 152.85 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -540.35 | -27038.59 |
SMSTORE3 | 02-MAR-08:61 | 0.00 | 0.00 | 26221.20 | 0.00 | 0.00 | 0.00 | 122.80 | 1321.11 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -229.22 | 0.00 | -490.33 | -27320.07 |
SMSTORE4 | 02-MAR-08:61 | 0.00 | 0.00 | 26313.81 | 0.00 | 0.00 | 0.00 | 124.06 | 1321.11 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -224.12 | 0.00 | -485.09 | -27424.29 |
LGSTORE2 | 03-MAR-09:01 | 0.00 | 0.00 | 50828.26 | 0.00 | 0.00 | 0.00 | 540.92 | 1511.82 | 749.03 | 275.09 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -392.65 | -53512.47 |
SMSTORE5 | 03-MAR-09:01 | 0.00 | 0.00 | 26313.23 | 0.00 | 0.00 | 0.00 | 271.37 | 776.01 | 374.52 | 138.68 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -217.61 | -27656.20 |
SMSTORE6 | 03-MAR-09:01 | 0.00 | 0.00 | 26236.09 | 0.00 | 0.00 | 0.00 | 272.64 | 776.01 | 374.52 | 140.98 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -215.41 | -27584.84 |
SMSTORE7 | 03-MAR-09:01 | 0.00 | 0.00 | 26375.03 | 0.00 | 0.00 | 0.00 | 276.97 | 776.01 | 374.52 | 148.44 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -208.12 | -27742.85 |
SMSTORE8 | 02-MAR-08:61 | 0.00 | 0.00 | 31018.25 | 0.00 | 0.00 | 0.00 | 0.00 | 77.60 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -162.76 | 0.00 | -470.89 | -30499.65 |
Total Facility | 03-FEB-09:01 | 0.00 | 0.00 | 231203.14 | 0.00 | 0.00 | 0.00 | 2769.58 | 16014.49 | 5393.02 | 12274.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4069.36 | -263585.58 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:35
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.3892 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.3892 | 0.1722 | 1.0000 | Not calculated | 0.4115 | 0.1722 | ||
PSZ-AC_2:2 | 1.2439 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2439 | 0.1654 | 1.0000 | Not calculated | 0.2057 | 0.1654 | ||
PSZ-AC_3:3 | 1.2785 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2785 | 0.1609 | 1.0000 | Not calculated | 0.2057 | 0.1609 | ||
PSZ-AC_4:4 | 1.2719 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2719 | 0.1618 | 1.0000 | Not calculated | 0.2057 | 0.1618 | ||
PSZ-AC_5:5 | 1.2743 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2743 | 0.1614 | 1.0000 | Not calculated | 0.2057 | 0.1614 | ||
PSZ-AC_6:6 | 2.2171 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.2171 | 0.1856 | 1.0000 | Not calculated | 0.4115 | 0.1856 | ||
PSZ-AC_7:7 | 1.1529 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1529 | 0.1785 | 1.0000 | Not calculated | 0.2057 | 0.1785 | ||
PSZ-AC_8:8 | 1.1475 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1475 | 0.1793 | 1.0000 | Not calculated | 0.2057 | 0.1793 | ||
PSZ-AC_9:9 | 1.1507 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1507 | 0.1788 | 1.0000 | Not calculated | 0.2057 | 0.1788 | ||
PSZ-AC_10:10 | 1.3020 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3020 | 0.1580 | 1.0000 | Not calculated | 0.2057 | 0.1580 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.3892 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.3892 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.1722 | ||
PSZ-AC_2:2 | 1.2439 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2439 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1654 | ||
PSZ-AC_3:3 | 1.2785 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2785 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1609 | ||
PSZ-AC_4:4 | 1.2719 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2719 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1618 | ||
PSZ-AC_5:5 | 1.2743 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2743 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1614 | ||
PSZ-AC_6:6 | 2.2171 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.2171 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.1856 | ||
PSZ-AC_7:7 | 1.1529 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1529 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1785 | ||
PSZ-AC_8:8 | 1.1475 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1475 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1793 | ||
PSZ-AC_9:9 | 1.1507 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1507 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1788 | ||
PSZ-AC_10:10 | 1.3020 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3020 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1580 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.3892 | 2.3892 | 2.3892 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2439 | 1.2439 | 1.2439 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2785 | 1.2785 | 1.2785 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2719 | 1.2719 | 1.2719 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2743 | 1.2743 | 1.2743 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.2171 | 2.2171 | 2.2171 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1529 | 1.1529 | 1.1529 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1475 | 1.1475 | 1.1475 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1507 | 1.1507 | 1.1507 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3020 | 1.3020 | 1.3020 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.3892 | 2.3892 | 2.3892 | 2.3892 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.2439 | 1.2439 | 1.2439 | 1.2439 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.2785 | 1.2785 | 1.2785 | 1.2785 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.2719 | 1.2719 | 1.2719 | 1.2719 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.2743 | 1.2743 | 1.2743 | 1.2743 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.2171 | 2.2171 | 2.2171 | 2.2171 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.1529 | 1.1529 | 1.1529 | 1.1529 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.1475 | 1.1475 | 1.1475 | 1.1475 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.1507 | 1.1507 | 1.1507 | 1.1507 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.3020 | 1.3020 | 1.3020 | 1.3020 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.3892 | 2.3892 | 2.3892 | No | 0.4115 | 0.3703 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2439 | 1.2439 | 1.2439 | No | 0.2057 | 0.3917 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2785 | 1.2785 | 1.2785 | No | 0.2057 | 0.3861 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2719 | 1.2719 | 1.2719 | No | 0.2057 | 0.3817 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2743 | 1.2743 | 1.2743 | No | 0.2057 | 0.3753 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.2171 | 2.2171 | 2.2171 | No | 0.4115 | 0.3846 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1529 | 1.1529 | 1.1529 | No | 0.2057 | 0.3617 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1475 | 1.1475 | 1.1475 | No | 0.2057 | 0.3619 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1507 | 1.1507 | 1.1507 | No | 0.2057 | 0.3534 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3020 | 1.3020 | 1.3020 | No | 0.2057 | 0.2951 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.3892 | 2.3892 | 2.3892 | 2.3892 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.2439 | 1.2439 | 1.2439 | 1.2439 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.2785 | 1.2785 | 1.2785 | 1.2785 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.2719 | 1.2719 | 1.2719 | 1.2719 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.2743 | 1.2743 | 1.2743 | 1.2743 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.2171 | 2.2171 | 2.2171 | 2.2171 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.1529 | 1.1529 | 1.1529 | 1.1529 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.1475 | 1.1475 | 1.1475 | 1.1475 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.1507 | 1.1507 | 1.1507 | 1.1507 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.3020 | 1.3020 | 1.3020 | 1.3020 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:35
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 56.52 | 132964.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 179.30 | 43107.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 381.75 | 23650.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 70.29 | 5403.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.72 | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 110.91 | 9157.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 57.94 | 11249.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.72 | 928.91 |
Natural Gas | 0.00 | 56.52 |
Additional | 0.00 | 0.00 |
Total | 128.72 | 985.43 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 182.63 |
Space Heating | 0.00 |
Space Cooling | 85.78 |
Fans (All) | 53.06 |
Service Water Heating | 27.72 |
Receptacle Equipment | 61.58 |
Miscellaneous (All) | 444.39 |
Subtotal | 444.39 |
Natural Gas [MJ/m2] | |
Space Heating | 27.04 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 27.04 |
Subtotal | 27.04 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 38.74 |
Space Heating | 5.74 |
Space Cooling | 18.20 |
Fans (All) | 11.25 |
Service Water Heating | 5.88 |
Receptacle Equipment | 13.06 |
Miscellaneous | 7.13 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3238. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3296. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 4469. | 8760. |
LTG_SCH_BASE_LPD1 | 4391. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 3584. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4888. | 8760. |
TYPE2_EQUIP_SCH | 3911. | 8760. |
TYPE3_EQUIP_SCH | 3600. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:35
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8653.17 | 106.83 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8630.17 | 129.83 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8654.33 | 105.67 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8696.00 | 64.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8709.17 | 50.83 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8711.83 | 48.17 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8710.00 | 50.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8662.17 | 97.83 | 0.00 | 0.00 | 0.00 |
Min | 8630.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 129.83 | 0.00 | 0.00 | 0.00 |
Average | 8694.68 | 65.32 | 0.00 | 0.00 | 0.00 |
Sum | 86946.83 | 653.17 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25440.33 | 34.67 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25439.83 | 35.17 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25443.00 | 32.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93104.00 | 107.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45863.00 | 49.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45863.50 | 48.50 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45863.00 | 49.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45853.50 | 58.50 | 0.00 | 0.00 | 0.00 |
Min | 25439.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 93104.00 | 107.00 | 0.00 | 0.00 | 0.00 |
Average | 48568.82 | 41.38 | 0.00 | 0.00 | 0.00 |
Sum | 485688.17 | 413.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 8526.00 | 234.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8726.17 | 33.83 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8355.50 | 404.50 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8336.83 | 423.17 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8362.00 | 398.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8456.67 | 303.33 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8467.17 | 292.83 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8469.50 | 290.50 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8471.83 | 288.17 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8416.00 | 344.00 | 0.00 | 0.00 | 0.00 |
Min | 8336.83 | 33.83 | 0.00 | 0.00 | 0.00 |
Max | 8726.17 | 423.17 | 0.00 | 0.00 | 0.00 |
Average | 8458.77 | 301.23 | 0.00 | 0.00 | 0.00 |
Sum | 84587.67 | 3012.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 88915.50 | 125.50 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43750.67 | 26.33 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25418.67 | 56.33 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25421.67 | 53.33 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25419.00 | 56.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93001.17 | 209.83 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45802.50 | 109.50 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45801.00 | 111.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45795.50 | 116.50 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45776.67 | 135.33 | 0.00 | 0.00 | 0.00 |
Min | 25418.67 | 26.33 | 0.00 | 0.00 | 0.00 |
Max | 93001.17 | 209.83 | 0.00 | 0.00 | 0.00 |
Average | 48510.23 | 99.97 | 0.00 | 0.00 | 0.00 |
Sum | 485102.33 | 999.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:35
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:35
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
For: Environment
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
For: Environment
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
For: Environment
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.451868E+10 | 8984.14 | 27-JAN-09:04 | -1.2 | -5.7 | 0.114385E+10 | 1634.35 | 13-JAN-13:00 | -1.2 | -5.7 |
February | 0.415748E+10 | 8133.51 | 01-FEB-09:03 | 1.47 | -2.3 | 0.110802E+10 | 1685.85 | 19-FEB-17:00 | 21.10 | 7.61 |
March | 0.502297E+10 | 8292.31 | 02-MAR-09:04 | 0.47 | -3.7 | 0.130712E+10 | 1685.85 | 19-MAR-16:30 | 21.10 | 8.21 |
April | 0.876450E+10 | 18081.77 | 29-APR-08:62 | 21.28 | 13.80 | 0.135351E+10 | 1685.86 | 29-APR-12:00 | 27.80 | 15.20 |
May | 0.129523E+11 | 40732.21 | 15-MAY-08:62 | 23.40 | 11.89 | 0.140203E+10 | 1685.95 | 21-MAY-17:00 | 28.90 | 18.15 |
June | 0.163691E+11 | 40365.34 | 12-JUN-08:62 | 23.35 | 9.75 | 0.135630E+10 | 1685.95 | 23-JUN-12:09 | 27.57 | 16.83 |
July | 0.175826E+11 | 38379.75 | 03-JUL-08:61 | 29.18 | 17.25 | 0.141478E+10 | 1686.00 | 04-JUL-17:00 | 26.10 | 19.85 |
August | 0.172372E+11 | 41572.80 | 23-AUG-08:61 | 24.27 | 13.78 | 0.139611E+10 | 1685.99 | 18-AUG-12:20 | 24.27 | 13.78 |
September | 0.158067E+11 | 44255.07 | 11-SEP-08:62 | 21.57 | 11.25 | 0.136630E+10 | 1686.00 | 08-SEP-12:09 | 21.57 | 11.25 |
October | 0.118453E+11 | 40685.20 | 02-OCT-08:61 | 21.20 | 15.83 | 0.140818E+10 | 1686.02 | 08-OCT-17:00 | 23.90 | 16.81 |
November | 0.675063E+10 | 33448.30 | 10-NOV-09:02 | 18.48 | 11.84 | 0.127625E+10 | 1685.93 | 03-NOV-12:50 | 18.48 | 11.84 |
December | 0.438322E+10 | 8765.55 | 27-DEC-09:04 | -0.7 | -2.5 | 0.113040E+10 | 1669.67 | 10-DEC-13:00 | -0.7 | -2.5 |
Annual Sum or Average | 0.125391E+12 | 0.156629E+11 | ||||||||
Minimum of Months | 0.415748E+10 | 8133.51 | -1.2 | -5.7 | 0.110802E+10 | 1634.35 | -1.2 | -5.7 | ||
Maximum of Months | 0.175826E+11 | 44255.07 | 29.18 | 17.25 | 0.141478E+10 | 1686.02 | 28.90 | 19.85 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.215110E+10 | 4605.05 | 27-JAN-09:03 | -1.2 | -5.7 | 0.620701E+09 | 842.90 | 22-JAN-18:00 | -1.2 | -5.7 |
February | 0.226720E+10 | 16169.17 | 20-FEB-18:40 | 18.90 | 6.86 | 0.586444E+09 | 842.90 | 19-FEB-17:40 | 18.90 | 6.86 |
March | 0.293511E+10 | 16510.88 | 12-MAR-17:40 | 18.33 | 8.19 | 0.675747E+09 | 842.90 | 19-MAR-16:10 | 21.83 | 8.58 |
April | 0.527703E+10 | 16709.77 | 26-APR-21:43 | 18.77 | 9.00 | 0.675942E+09 | 843.15 | 16-APR-17:19 | 18.77 | 9.00 |
May | 0.724830E+10 | 22191.54 | 17-MAY-08:62 | 21.57 | 9.51 | 0.699171E+09 | 843.37 | 29-MAY-17:49 | 31.38 | 15.58 |
June | 0.875635E+10 | 21190.75 | 12-JUN-08:62 | 23.35 | 9.75 | 0.677754E+09 | 843.09 | 11-JUN-17:30 | 23.35 | 9.75 |
July | 0.926344E+10 | 20039.04 | 10-JUL-08:61 | 26.88 | 17.44 | 0.707311E+09 | 842.99 | 07-JUL-12:00 | 26.88 | 17.44 |
August | 0.907754E+10 | 21635.67 | 23-AUG-08:61 | 24.27 | 13.78 | 0.697535E+09 | 842.98 | 04-AUG-12:00 | 24.27 | 13.78 |
September | 0.835175E+10 | 23102.94 | 11-SEP-08:62 | 21.57 | 11.25 | 0.680483E+09 | 842.97 | 08-SEP-12:09 | 21.57 | 11.25 |
October | 0.658557E+10 | 22226.51 | 19-OCT-08:62 | 19.08 | 12.62 | 0.700970E+09 | 842.98 | 08-OCT-17:10 | 19.08 | 12.62 |
November | 0.365006E+10 | 22160.99 | 10-NOV-09:02 | 18.48 | 11.84 | 0.657006E+09 | 842.94 | 03-NOV-12:39 | 18.48 | 11.84 |
December | 0.204066E+10 | 4513.79 | 27-DEC-09:03 | -0.7 | -2.5 | 0.611996E+09 | 842.90 | 10-DEC-18:00 | -0.7 | -2.5 |
Annual Sum or Average | 0.676041E+11 | 0.799106E+10 | ||||||||
Minimum of Months | 0.204066E+10 | 4513.79 | -1.2 | -5.7 | 0.586444E+09 | 842.90 | -1.2 | -5.7 | ||
Maximum of Months | 0.926344E+10 | 23102.94 | 26.88 | 17.44 | 0.707311E+09 | 843.37 | 31.38 | 17.44 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.180966E+10 | 5052.70 | 27-JAN-08:03 | -3.5 | -7.2 | 0.349141E+09 | 709.91 | 07-JAN-13:00 | -3.5 | -7.2 |
February | 0.177397E+10 | 4793.13 | 03-FEB-08:03 | -2.0 | -5.0 | 0.336844E+09 | 842.87 | 11-FEB-13:00 | 18.90 | 6.65 |
March | 0.217762E+10 | 4506.50 | 02-MAR-08:03 | -0.9 | -4.7 | 0.407658E+09 | 842.88 | 25-MAR-12:39 | 19.23 | 8.73 |
April | 0.364395E+10 | 14760.07 | 20-APR-07:03 | 20.60 | 8.60 | 0.408633E+09 | 842.91 | 29-APR-12:09 | 27.30 | 15.21 |
May | 0.532186E+10 | 22988.20 | 15-MAY-07:02 | 21.97 | 11.12 | 0.426381E+09 | 842.90 | 27-MAY-12:09 | 30.10 | 16.35 |
June | 0.673893E+10 | 23404.08 | 14-JUN-07:01 | 22.12 | 9.77 | 0.417963E+09 | 842.92 | 03-JUN-12:09 | 22.12 | 9.77 |
July | 0.699490E+10 | 20848.45 | 11-JUL-07:01 | 24.45 | 16.28 | 0.421101E+09 | 842.96 | 08-JUL-12:09 | 24.45 | 16.28 |
August | 0.696638E+10 | 23939.36 | 23-AUG-07:01 | 22.07 | 13.03 | 0.432490E+09 | 842.94 | 12-AUG-12:09 | 22.07 | 13.03 |
September | 0.625393E+10 | 25880.68 | 11-SEP-07:02 | 18.77 | 10.73 | 0.411269E+09 | 842.94 | 09-SEP-12:09 | 18.77 | 10.73 |
October | 0.474272E+10 | 24091.87 | 06-OCT-07:02 | 12.70 | 10.09 | 0.419624E+09 | 842.94 | 28-OCT-12:30 | 21.40 | 13.50 |
November | 0.273902E+10 | 15126.33 | 10-NOV-08:62 | 17.88 | 11.42 | 0.383946E+09 | 842.90 | 18-NOV-13:00 | 19.40 | 6.83 |
December | 0.169661E+10 | 5138.97 | 27-DEC-08:03 | -3.4 | -4.3 | 0.342371E+09 | 842.89 | 09-DEC-13:00 | -3.4 | -4.3 |
Annual Sum or Average | 0.508595E+11 | 0.475742E+10 | ||||||||
Minimum of Months | 0.169661E+10 | 4506.50 | -3.5 | -7.2 | 0.336844E+09 | 709.91 | -3.5 | -7.2 | ||
Maximum of Months | 0.699490E+10 | 25880.68 | 24.45 | 16.28 | 0.432490E+09 | 842.96 | 30.10 | 16.35 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.166019E+10 | 5117.98 | 27-JAN-08:03 | -3.5 | -7.2 | 0.345444E+09 | 702.60 | 07-JAN-13:00 | -3.5 | -7.2 |
February | 0.165458E+10 | 4816.75 | 03-FEB-08:03 | -2.0 | -5.0 | 0.334209E+09 | 842.83 | 11-FEB-13:00 | 18.90 | 6.65 |
March | 0.204967E+10 | 4571.89 | 02-MAR-08:03 | -0.9 | -4.7 | 0.405937E+09 | 842.88 | 25-MAR-12:50 | 19.32 | 8.70 |
April | 0.359701E+10 | 14536.90 | 20-APR-07:03 | 20.60 | 8.60 | 0.408516E+09 | 842.91 | 29-APR-12:09 | 27.30 | 15.21 |
May | 0.534392E+10 | 22916.51 | 15-MAY-07:02 | 21.97 | 11.12 | 0.426385E+09 | 842.90 | 27-MAY-12:09 | 30.10 | 16.35 |
June | 0.679610E+10 | 23327.27 | 14-JUN-07:01 | 22.12 | 9.77 | 0.417975E+09 | 842.92 | 03-JUN-12:09 | 22.12 | 9.77 |
July | 0.705841E+10 | 20789.09 | 11-JUL-07:01 | 24.45 | 16.28 | 0.421112E+09 | 842.96 | 08-JUL-12:09 | 24.45 | 16.28 |
August | 0.702758E+10 | 23858.77 | 23-AUG-07:01 | 22.07 | 13.03 | 0.432500E+09 | 842.94 | 12-AUG-12:09 | 22.07 | 13.03 |
September | 0.629894E+10 | 25807.69 | 11-SEP-07:02 | 18.77 | 10.73 | 0.411278E+09 | 842.94 | 09-SEP-12:09 | 18.77 | 10.73 |
October | 0.472916E+10 | 24750.99 | 06-OCT-07:02 | 12.70 | 10.09 | 0.419590E+09 | 842.94 | 28-OCT-12:30 | 21.40 | 13.50 |
November | 0.262817E+10 | 14717.21 | 10-NOV-08:62 | 17.88 | 11.42 | 0.382830E+09 | 842.90 | 18-NOV-13:00 | 19.40 | 6.83 |
December | 0.156043E+10 | 5079.33 | 27-DEC-08:03 | -3.4 | -4.3 | 0.339140E+09 | 842.89 | 09-DEC-13:00 | -3.4 | -4.3 |
Annual Sum or Average | 0.504042E+11 | 0.474492E+10 | ||||||||
Minimum of Months | 0.156043E+10 | 4571.89 | -3.5 | -7.2 | 0.334209E+09 | 702.60 | -3.5 | -7.2 | ||
Maximum of Months | 0.705841E+10 | 25807.69 | 24.45 | 16.28 | 0.432500E+09 | 842.96 | 30.10 | 16.35 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.146441E+10 | 5124.52 | 27-JAN-08:03 | -3.5 | -7.2 | 0.340995E+09 | 702.41 | 03-JAN-17:10 | -3.5 | -7.2 |
February | 0.147151E+10 | 4779.44 | 03-FEB-08:03 | -2.0 | -5.0 | 0.330747E+09 | 841.88 | 11-FEB-13:00 | 18.90 | 6.65 |
March | 0.183683E+10 | 4526.22 | 02-MAR-08:03 | -0.9 | -4.7 | 0.402917E+09 | 842.88 | 25-MAR-12:00 | 19.40 | 8.67 |
April | 0.339865E+10 | 12767.91 | 20-APR-07:03 | 20.60 | 8.60 | 0.408091E+09 | 842.91 | 29-APR-12:09 | 27.30 | 15.21 |
May | 0.517350E+10 | 22888.51 | 15-MAY-07:02 | 21.97 | 11.12 | 0.426319E+09 | 842.90 | 27-MAY-12:09 | 30.10 | 16.35 |
June | 0.665399E+10 | 23278.70 | 14-JUN-07:01 | 22.12 | 9.77 | 0.417932E+09 | 842.92 | 03-JUN-12:09 | 22.12 | 9.77 |
July | 0.692871E+10 | 20750.61 | 11-JUL-07:01 | 24.45 | 16.28 | 0.421074E+09 | 842.96 | 08-JUL-12:09 | 24.45 | 16.28 |
August | 0.689178E+10 | 23815.95 | 23-AUG-07:01 | 22.07 | 13.03 | 0.432461E+09 | 842.95 | 12-AUG-12:09 | 22.07 | 13.03 |
September | 0.615834E+10 | 25811.55 | 11-SEP-07:02 | 18.77 | 10.73 | 0.411235E+09 | 842.94 | 09-SEP-12:09 | 18.77 | 10.73 |
October | 0.455996E+10 | 23386.86 | 06-OCT-07:02 | 12.70 | 10.09 | 0.419393E+09 | 842.94 | 28-OCT-12:30 | 21.40 | 13.50 |
November | 0.244588E+10 | 13189.26 | 10-NOV-08:62 | 17.88 | 11.42 | 0.380817E+09 | 842.90 | 18-NOV-13:00 | 19.40 | 6.83 |
December | 0.137779E+10 | 4689.79 | 28-DEC-08:04 | -1.0 | -2.3 | 0.335154E+09 | 839.19 | 09-DEC-13:00 | -1.0 | -2.3 |
Annual Sum or Average | 0.483614E+11 | 0.472713E+10 | ||||||||
Minimum of Months | 0.137779E+10 | 4526.22 | -3.5 | -7.2 | 0.330747E+09 | 702.41 | -3.5 | -7.2 | ||
Maximum of Months | 0.692871E+10 | 25811.55 | 24.45 | 16.28 | 0.432461E+09 | 842.96 | 30.10 | 16.35 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.222512E+10 | 9042.24 | 27-JAN-09:04 | -1.2 | -5.7 | 0.114523E+10 | 1994.90 | 03-JAN-17:10 | -1.2 | -5.7 |
February | 0.222768E+10 | 7907.24 | 02-FEB-09:04 | 1.38 | -2.7 | 0.112019E+10 | 2247.77 | 11-FEB-15:30 | 19.70 | 6.77 |
March | 0.281760E+10 | 8407.31 | 02-MAR-09:04 | 0.47 | -3.7 | 0.136583E+10 | 2247.80 | 25-MAR-14:00 | 21.10 | 8.87 |
April | 0.545391E+10 | 18277.93 | 29-APR-08:62 | 21.28 | 13.80 | 0.139952E+10 | 2247.80 | 29-APR-14:09 | 30.10 | 15.60 |
May | 0.867894E+10 | 38792.83 | 15-MAY-08:62 | 23.40 | 11.89 | 0.145856E+10 | 2247.80 | 27-MAY-14:09 | 30.68 | 15.94 |
June | 0.114229E+11 | 38846.05 | 12-JUN-08:62 | 23.35 | 9.75 | 0.143186E+10 | 2247.99 | 03-JUN-14:20 | 23.35 | 9.75 |
July | 0.118767E+11 | 36541.90 | 06-JUL-08:61 | 26.38 | 18.59 | 0.144077E+10 | 2248.12 | 01-JUL-14:20 | 26.38 | 18.59 |
August | 0.118612E+11 | 39240.03 | 28-AUG-08:61 | 23.58 | 15.64 | 0.148232E+10 | 2247.90 | 05-AUG-14:30 | 23.58 | 15.64 |
September | 0.105471E+11 | 42250.87 | 11-SEP-08:62 | 21.57 | 11.25 | 0.141117E+10 | 2247.90 | 23-SEP-14:00 | 28.30 | 18.50 |
October | 0.752999E+10 | 39604.53 | 01-OCT-09:02 | 22.57 | 12.91 | 0.143146E+10 | 2247.88 | 14-OCT-14:00 | 19.40 | 15.20 |
November | 0.384951E+10 | 31368.46 | 10-NOV-09:02 | 18.48 | 11.84 | 0.128556E+10 | 2247.80 | 18-NOV-15:00 | 19.40 | 6.83 |
December | 0.205068E+10 | 9220.28 | 27-DEC-09:04 | -0.7 | -2.5 | 0.113473E+10 | 2163.64 | 09-DEC-15:30 | -0.7 | -2.5 |
Annual Sum or Average | 0.805413E+11 | 0.161072E+11 | ||||||||
Minimum of Months | 0.205068E+10 | 7907.24 | -1.2 | -5.7 | 0.112019E+10 | 1994.90 | -1.2 | -5.7 | ||
Maximum of Months | 0.118767E+11 | 42250.87 | 26.38 | 18.59 | 0.148232E+10 | 2248.12 | 30.68 | 18.59 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.101775E+10 | 4491.38 | 27-JAN-09:04 | -1.2 | -5.7 | 0.570172E+09 | 997.43 | 03-JAN-17:10 | -1.2 | -5.7 |
February | 0.102824E+10 | 3936.97 | 02-FEB-09:04 | 1.38 | -2.7 | 0.557708E+09 | 1123.86 | 11-FEB-15:00 | 20.00 | 6.94 |
March | 0.131017E+10 | 4191.39 | 02-MAR-09:04 | 0.47 | -3.7 | 0.679881E+09 | 1123.86 | 25-MAR-14:00 | 21.10 | 8.87 |
April | 0.273454E+10 | 8157.95 | 29-APR-08:62 | 21.28 | 13.80 | 0.699282E+09 | 1123.87 | 29-APR-14:09 | 30.10 | 15.60 |
May | 0.445541E+10 | 19909.68 | 15-MAY-08:62 | 23.40 | 11.89 | 0.729218E+09 | 1123.87 | 27-MAY-14:09 | 30.68 | 15.94 |
June | 0.590676E+10 | 19932.16 | 12-JUN-08:62 | 23.35 | 9.75 | 0.715850E+09 | 1123.96 | 03-JUN-14:20 | 23.35 | 9.75 |
July | 0.614714E+10 | 18833.79 | 06-JUL-08:61 | 26.38 | 18.59 | 0.720293E+09 | 1124.03 | 01-JUL-14:20 | 26.38 | 18.59 |
August | 0.612765E+10 | 20232.57 | 28-AUG-08:61 | 23.58 | 15.64 | 0.741090E+09 | 1123.91 | 05-AUG-14:30 | 23.58 | 15.64 |
September | 0.543689E+10 | 21710.33 | 11-SEP-08:62 | 21.57 | 11.25 | 0.705527E+09 | 1123.92 | 23-SEP-14:00 | 28.30 | 18.50 |
October | 0.382660E+10 | 20318.08 | 01-OCT-09:02 | 22.57 | 12.91 | 0.715574E+09 | 1123.90 | 14-OCT-14:00 | 19.40 | 15.20 |
November | 0.186744E+10 | 14725.34 | 10-NOV-09:02 | 18.48 | 11.84 | 0.641489E+09 | 1123.87 | 18-NOV-15:39 | 19.40 | 6.83 |
December | 0.944329E+09 | 4591.89 | 27-DEC-09:04 | -0.7 | -2.5 | 0.565429E+09 | 1069.16 | 09-DEC-15:30 | -0.7 | -2.5 |
Annual Sum or Average | 0.408029E+11 | 0.804151E+10 | ||||||||
Minimum of Months | 0.944329E+09 | 3936.97 | -1.2 | -5.7 | 0.557708E+09 | 997.43 | -1.2 | -5.7 | ||
Maximum of Months | 0.614714E+10 | 21710.33 | 26.38 | 18.59 | 0.741090E+09 | 1124.03 | 30.68 | 18.59 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.960101E+09 | 4530.37 | 27-JAN-09:04 | -1.2 | -5.7 | 0.567891E+09 | 997.43 | 03-JAN-17:10 | -1.2 | -5.7 |
February | 0.970423E+09 | 3979.11 | 02-FEB-09:04 | 1.38 | -2.7 | 0.555533E+09 | 1123.84 | 11-FEB-15:00 | 20.00 | 6.94 |
March | 0.124013E+10 | 4240.26 | 02-MAR-09:04 | 0.47 | -3.7 | 0.677003E+09 | 1123.86 | 25-MAR-14:00 | 21.10 | 8.87 |
April | 0.266393E+10 | 7602.24 | 30-APR-09:03 | 20.37 | 12.82 | 0.698730E+09 | 1123.87 | 29-APR-14:09 | 20.37 | 12.82 |
May | 0.439636E+10 | 19802.44 | 15-MAY-08:62 | 23.40 | 11.89 | 0.729186E+09 | 1123.87 | 27-MAY-14:09 | 30.68 | 15.94 |
June | 0.585614E+10 | 19828.44 | 12-JUN-08:62 | 23.35 | 9.75 | 0.715839E+09 | 1123.96 | 03-JUN-14:20 | 23.35 | 9.75 |
July | 0.609983E+10 | 18730.25 | 06-JUL-08:61 | 26.38 | 18.59 | 0.720278E+09 | 1124.03 | 01-JUL-14:20 | 26.38 | 18.59 |
August | 0.608092E+10 | 20130.26 | 28-AUG-08:61 | 23.58 | 15.64 | 0.741073E+09 | 1123.91 | 05-AUG-14:30 | 23.58 | 15.64 |
September | 0.539163E+10 | 21607.47 | 11-SEP-08:62 | 21.57 | 11.25 | 0.705511E+09 | 1123.92 | 23-SEP-14:00 | 28.30 | 18.50 |
October | 0.376807E+10 | 20065.18 | 01-OCT-09:02 | 22.57 | 12.91 | 0.715340E+09 | 1123.90 | 14-OCT-14:00 | 19.40 | 15.20 |
November | 0.181042E+10 | 13938.08 | 10-NOV-09:02 | 18.48 | 11.84 | 0.639600E+09 | 1123.83 | 18-NOV-15:09 | 19.40 | 6.83 |
December | 0.892408E+09 | 4594.70 | 27-DEC-09:04 | -0.7 | -2.5 | 0.563744E+09 | 1061.99 | 09-DEC-15:30 | -0.7 | -2.5 |
Annual Sum or Average | 0.401304E+11 | 0.802973E+10 | ||||||||
Minimum of Months | 0.892408E+09 | 3979.11 | -1.2 | -5.7 | 0.555533E+09 | 997.43 | -1.2 | -5.7 | ||
Maximum of Months | 0.609983E+10 | 21607.47 | 26.38 | 18.59 | 0.741073E+09 | 1124.03 | 30.68 | 18.59 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.812283E+09 | 4639.52 | 27-JAN-09:04 | -1.2 | -5.7 | 0.563457E+09 | 991.69 | 03-JAN-17:30 | -1.2 | -5.7 |
February | 0.820321E+09 | 4102.56 | 02-FEB-09:04 | 1.38 | -2.7 | 0.550422E+09 | 1113.73 | 11-FEB-15:00 | 20.00 | 6.94 |
March | 0.107645E+10 | 4319.30 | 02-MAR-09:04 | 0.47 | -3.7 | 0.670180E+09 | 1123.85 | 25-MAR-14:20 | 20.37 | 8.78 |
April | 0.251307E+10 | 6283.34 | 30-APR-09:03 | 20.37 | 12.82 | 0.697255E+09 | 1123.87 | 29-APR-14:09 | 20.37 | 12.82 |
May | 0.430780E+10 | 19757.99 | 15-MAY-08:62 | 23.40 | 11.89 | 0.729079E+09 | 1123.87 | 27-MAY-14:09 | 30.68 | 15.94 |
June | 0.583997E+10 | 19789.68 | 12-JUN-08:62 | 23.35 | 9.75 | 0.715811E+09 | 1123.95 | 03-JUN-14:20 | 23.35 | 9.75 |
July | 0.611336E+10 | 18746.32 | 06-JUL-08:61 | 26.38 | 18.59 | 0.720268E+09 | 1124.03 | 01-JUL-14:20 | 26.38 | 18.59 |
August | 0.610227E+10 | 20173.29 | 28-AUG-08:61 | 23.58 | 15.64 | 0.741066E+09 | 1123.92 | 05-AUG-14:30 | 23.58 | 15.64 |
September | 0.539700E+10 | 21629.06 | 11-SEP-08:62 | 21.57 | 11.25 | 0.705501E+09 | 1123.92 | 23-SEP-14:00 | 28.30 | 18.50 |
October | 0.367664E+10 | 19768.34 | 02-OCT-08:61 | 21.20 | 15.83 | 0.714660E+09 | 1123.90 | 28-OCT-14:09 | 22.98 | 13.61 |
November | 0.169105E+10 | 11788.64 | 10-NOV-09:02 | 18.48 | 11.84 | 0.635356E+09 | 1123.83 | 18-NOV-15:09 | 19.40 | 6.83 |
December | 0.768448E+09 | 4571.09 | 27-DEC-09:04 | -0.7 | -2.5 | 0.560453E+09 | 1048.73 | 09-DEC-15:30 | -0.7 | -2.5 |
Annual Sum or Average | 0.391187E+11 | 0.800351E+10 | ||||||||
Minimum of Months | 0.768448E+09 | 4102.56 | -1.2 | -5.7 | 0.550422E+09 | 991.69 | -1.2 | -5.7 | ||
Maximum of Months | 0.611336E+10 | 21629.06 | 26.38 | 18.59 | 0.741066E+09 | 1124.03 | 30.68 | 18.59 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.515531E+09 | 4634.17 | 27-JAN-09:04 | -1.2 | -5.7 | 0.558098E+09 | 965.78 | 03-JAN-17:19 | -1.2 | -5.7 |
February | 0.510608E+09 | 4088.62 | 02-FEB-09:04 | 1.38 | -2.7 | 0.542827E+09 | 1080.26 | 18-FEB-15:00 | 20.00 | 8.60 |
March | 0.793071E+09 | 4215.02 | 02-MAR-09:04 | 0.47 | -3.7 | 0.660548E+09 | 1123.86 | 25-MAR-14:50 | 20.92 | 8.85 |
April | 0.254419E+10 | 7531.00 | 30-APR-09:03 | 20.37 | 12.82 | 0.695555E+09 | 1123.87 | 29-APR-14:09 | 20.37 | 12.82 |
May | 0.473827E+10 | 21454.23 | 15-MAY-08:62 | 23.40 | 11.89 | 0.729034E+09 | 1123.87 | 27-MAY-14:09 | 30.68 | 15.94 |
June | 0.670765E+10 | 21314.38 | 12-JUN-08:62 | 23.35 | 9.75 | 0.715907E+09 | 1123.96 | 03-JUN-14:20 | 23.35 | 9.75 |
July | 0.711300E+10 | 20349.01 | 03-JUL-08:61 | 29.18 | 17.25 | 0.720434E+09 | 1124.05 | 01-JUL-14:20 | 29.18 | 17.25 |
August | 0.714683E+10 | 22130.56 | 28-AUG-08:61 | 23.58 | 15.64 | 0.741213E+09 | 1123.96 | 05-AUG-14:20 | 23.58 | 15.64 |
September | 0.632501E+10 | 23685.09 | 11-SEP-08:62 | 21.57 | 11.25 | 0.705656E+09 | 1123.91 | 23-SEP-14:00 | 28.30 | 18.50 |
October | 0.392146E+10 | 21620.11 | 02-OCT-08:61 | 21.20 | 15.83 | 0.712683E+09 | 1123.89 | 28-OCT-14:09 | 22.98 | 13.61 |
November | 0.151983E+10 | 8675.23 | 10-NOV-09:02 | 18.48 | 11.84 | 0.630076E+09 | 1123.84 | 18-NOV-15:00 | 19.40 | 6.83 |
December | 0.516673E+09 | 4507.02 | 27-DEC-09:04 | -0.7 | -2.5 | 0.557228E+09 | 1037.99 | 09-DEC-15:30 | -0.7 | -2.5 |
Annual Sum or Average | 0.423521E+11 | 0.796926E+10 | ||||||||
Minimum of Months | 0.510608E+09 | 4088.62 | -1.2 | -5.7 | 0.542827E+09 | 965.78 | -1.2 | -5.7 | ||
Maximum of Months | 0.714683E+10 | 23685.09 | 29.18 | 17.25 | 0.741213E+09 | 1124.05 | 30.68 | 18.50 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.267446E+09 | 52392.34 | 09-JAN-09:01 | 5.47 |
February | 0.200439E+09 | 53133.21 | 04-FEB-09:01 | 7.25 |
March | 0.159589E+09 | 54058.60 | 03-MAR-09:01 | 9.68 |
April | 92479932.22 | 1026.24 | 22-APR-07:25 | 8.05 |
May | 0.100114E+09 | 3221.10 | 31-MAY-08:04 | 27.30 |
June | 0.104861E+09 | 3819.69 | 16-JUN-08:04 | 28.77 |
July | 88447713.35 | 3842.92 | 01-JUL-08:04 | 28.68 |
August | 99243229.00 | 3248.07 | 07-AUG-08:05 | 28.48 |
September | 94340448.39 | 1989.27 | 10-SEP-07:05 | 21.47 |
October | 83566345.86 | 1481.93 | 05-OCT-08:04 | 23.17 |
November | 0.113310E+09 | 51771.37 | 28-NOV-09:01 | 4.18 |
December | 0.374264E+09 | 52612.34 | 20-DEC-09:01 | 6.20 |
Annual Sum or Average | 0.177810E+10 | |||
Minimum of Months | 83566345.86 | 1026.24 | 4.18 | |
Maximum of Months | 0.374264E+09 | 54058.60 | 28.77 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 62985025.83 | 24161.75 | 28-JAN-09:01 | 2.07 |
February | 56453515.55 | 26103.88 | 03-FEB-09:01 | 2.95 |
March | 58547278.44 | 21843.97 | 02-MAR-09:01 | 0.47 |
April | 48472601.29 | 550.46 | 22-APR-07:25 | 8.05 |
May | 52690482.83 | 1702.54 | 31-MAY-08:04 | 27.30 |
June | 52717033.77 | 1940.25 | 16-JUN-08:04 | 28.77 |
July | 45223134.75 | 1989.49 | 01-JUL-08:04 | 28.68 |
August | 50737223.71 | 1383.02 | 26-AUG-08:05 | 26.88 |
September | 49402793.59 | 1103.06 | 10-SEP-07:05 | 21.47 |
October | 45361624.29 | 798.89 | 05-OCT-08:04 | 23.17 |
November | 49539838.64 | 5437.82 | 28-NOV-09:01 | 4.18 |
December | 82677500.41 | 23943.74 | 27-DEC-09:01 | -0.7 |
Annual Sum or Average | 0.654808E+09 | |||
Minimum of Months | 45223134.75 | 550.46 | -0.7 | |
Maximum of Months | 82677500.41 | 26103.88 | 28.77 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 92353338.65 | 23274.84 | 28-JAN-08:62 | -0.6 |
February | 70494049.28 | 24202.33 | 03-FEB-08:62 | -2.0 |
March | 65120758.52 | 22908.12 | 02-MAR-08:61 | -0.9 |
April | 87458633.44 | 1648.66 | 30-APR-16:02 | 30.50 |
May | 0.144650E+09 | 2251.41 | 21-MAY-16:02 | 33.57 |
June | 0.207857E+09 | 3066.92 | 18-JUN-16:01 | 37.20 |
July | 0.183352E+09 | 3278.97 | 02-JUL-16:01 | 38.22 |
August | 0.159329E+09 | 2837.60 | 06-AUG-16:01 | 36.10 |
September | 97025565.72 | 2085.45 | 17-SEP-16:02 | 32.62 |
October | 65874943.24 | 1837.11 | 01-OCT-16:02 | 31.60 |
November | 53854311.53 | 4791.04 | 28-NOV-08:63 | 2.48 |
December | 0.141677E+09 | 25607.27 | 27-DEC-08:62 | -3.4 |
Annual Sum or Average | 0.136905E+10 | |||
Minimum of Months | 53854311.53 | 1648.66 | -3.4 | |
Maximum of Months | 0.207857E+09 | 25607.27 | 38.22 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.112142E+09 | 25935.41 | 28-JAN-08:62 | -0.6 |
February | 80067103.49 | 25803.13 | 03-FEB-08:62 | -2.0 |
March | 68388910.76 | 26221.36 | 02-MAR-08:61 | -0.9 |
April | 87404331.30 | 1647.82 | 30-APR-16:02 | 30.50 |
May | 0.143827E+09 | 2249.90 | 21-MAY-16:02 | 33.57 |
June | 0.205201E+09 | 3064.29 | 18-JUN-16:01 | 37.20 |
July | 0.179928E+09 | 3276.87 | 02-JUL-16:01 | 38.22 |
August | 0.156614E+09 | 2834.79 | 06-AUG-16:01 | 36.10 |
September | 96221507.38 | 2083.25 | 17-SEP-16:02 | 32.62 |
October | 65331266.33 | 1836.35 | 01-OCT-16:02 | 31.60 |
November | 56733215.14 | 6479.40 | 28-NOV-08:63 | 2.48 |
December | 0.169951E+09 | 25545.89 | 27-DEC-08:62 | -3.4 |
Annual Sum or Average | 0.142181E+10 | |||
Minimum of Months | 56733215.14 | 1647.82 | -3.4 | |
Maximum of Months | 0.205201E+09 | 26221.36 | 38.22 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.147352E+09 | 26138.60 | 28-JAN-08:62 | -0.6 |
February | 96110650.74 | 25905.24 | 02-FEB-08:62 | -1.7 |
March | 74938165.62 | 26313.98 | 02-MAR-08:61 | -0.9 |
April | 88869188.21 | 1654.43 | 30-APR-16:02 | 30.50 |
May | 0.145896E+09 | 2255.56 | 21-MAY-16:02 | 33.57 |
June | 0.208371E+09 | 3067.81 | 18-JUN-16:01 | 37.20 |
July | 0.184043E+09 | 3280.51 | 02-JUL-16:01 | 38.22 |
August | 0.159895E+09 | 2838.02 | 06-AUG-16:01 | 36.10 |
September | 97632466.90 | 2087.57 | 17-SEP-16:02 | 32.62 |
October | 66072518.86 | 1842.12 | 01-OCT-16:02 | 31.60 |
November | 61926772.18 | 8134.27 | 28-NOV-08:63 | 2.48 |
December | 0.216165E+09 | 25735.15 | 28-DEC-08:62 | -1.0 |
Annual Sum or Average | 0.154727E+10 | |||
Minimum of Months | 61926772.18 | 1654.43 | -1.7 | |
Maximum of Months | 0.216165E+09 | 26313.98 | 38.22 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.304289E+09 | 49632.48 | 17-JAN-09:01 | 6.78 |
February | 0.180475E+09 | 49853.19 | 04-FEB-09:01 | 7.25 |
March | 0.140548E+09 | 50828.36 | 03-MAR-09:01 | 9.68 |
April | 0.136732E+09 | 3291.59 | 30-APR-16:02 | 30.50 |
May | 0.192063E+09 | 4515.84 | 21-MAY-16:02 | 33.57 |
June | 0.196136E+09 | 6116.64 | 18-JUN-16:01 | 37.20 |
July | 0.203977E+09 | 6549.04 | 02-JUL-16:01 | 38.22 |
August | 0.189880E+09 | 5655.96 | 06-AUG-16:01 | 36.10 |
September | 0.145019E+09 | 4157.07 | 17-SEP-16:02 | 32.62 |
October | 0.110321E+09 | 3683.02 | 01-OCT-16:02 | 31.60 |
November | 0.122716E+09 | 48586.26 | 28-NOV-09:01 | 4.18 |
December | 0.430920E+09 | 49442.84 | 20-DEC-09:01 | 6.20 |
Annual Sum or Average | 0.235308E+10 | |||
Minimum of Months | 0.110321E+09 | 3291.59 | 4.18 | |
Maximum of Months | 0.430920E+09 | 50828.36 | 38.22 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.192578E+09 | 25713.92 | 17-JAN-09:01 | 6.78 |
February | 0.110312E+09 | 25824.76 | 04-FEB-09:01 | 7.25 |
March | 82745346.53 | 26313.28 | 03-MAR-09:01 | 9.68 |
April | 73874915.23 | 1663.48 | 30-APR-16:02 | 30.50 |
May | 0.101463E+09 | 2270.93 | 21-MAY-16:02 | 33.57 |
June | 0.101861E+09 | 3071.88 | 18-JUN-16:01 | 37.20 |
July | 0.107771E+09 | 3286.74 | 02-JUL-16:01 | 38.22 |
August | 0.100833E+09 | 2841.57 | 06-AUG-16:01 | 36.10 |
September | 76554472.86 | 2093.50 | 17-SEP-16:02 | 32.62 |
October | 59761146.31 | 1855.32 | 01-OCT-16:02 | 31.60 |
November | 72037791.72 | 25186.68 | 28-NOV-09:01 | 4.18 |
December | 0.271934E+09 | 25613.55 | 20-DEC-09:01 | 6.20 |
Annual Sum or Average | 0.135173E+10 | |||
Minimum of Months | 59761146.31 | 1663.48 | 4.18 | |
Maximum of Months | 0.271934E+09 | 26313.28 | 38.22 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.217647E+09 | 25891.57 | 16-JAN-10:01 | 9.18 |
February | 0.122501E+09 | 25825.94 | 11-FEB-09:01 | 8.17 |
March | 91259331.02 | 26236.14 | 03-MAR-09:01 | 9.68 |
April | 74000172.64 | 1664.78 | 30-APR-16:02 | 30.50 |
May | 0.101587E+09 | 2272.26 | 21-MAY-16:02 | 33.57 |
June | 0.103373E+09 | 3072.45 | 18-JUN-16:01 | 37.20 |
July | 0.108658E+09 | 3287.40 | 02-JUL-16:01 | 38.22 |
August | 0.100252E+09 | 2842.01 | 06-AUG-16:01 | 36.10 |
September | 76475407.75 | 2094.06 | 17-SEP-16:02 | 32.62 |
October | 59617594.45 | 1856.54 | 01-OCT-16:02 | 31.60 |
November | 76880740.57 | 25105.53 | 28-NOV-09:01 | 4.18 |
December | 0.292951E+09 | 25532.55 | 20-DEC-09:01 | 6.20 |
Annual Sum or Average | 0.142520E+10 | |||
Minimum of Months | 59617594.45 | 1664.78 | 4.18 | |
Maximum of Months | 0.292951E+09 | 26236.14 | 38.22 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.298394E+09 | 26047.48 | 08-JAN-10:01 | 9.45 |
February | 0.167718E+09 | 26034.17 | 27-FEB-09:01 | 9.60 |
March | 0.128159E+09 | 26375.08 | 03-MAR-09:01 | 9.68 |
April | 75383711.87 | 1669.06 | 30-APR-16:02 | 30.50 |
May | 0.102467E+09 | 2274.38 | 21-MAY-16:02 | 33.57 |
June | 0.101751E+09 | 3072.37 | 18-JUN-16:01 | 37.20 |
July | 0.108230E+09 | 3286.81 | 02-JUL-16:01 | 38.22 |
August | 99632836.49 | 2840.43 | 06-AUG-16:01 | 36.10 |
September | 76560828.90 | 2093.26 | 17-SEP-16:02 | 32.62 |
October | 59973147.78 | 1857.83 | 01-OCT-16:02 | 31.60 |
November | 94221031.63 | 25241.57 | 28-NOV-09:01 | 4.18 |
December | 0.379357E+09 | 25666.44 | 20-DEC-09:01 | 6.20 |
Annual Sum or Average | 0.169185E+10 | |||
Minimum of Months | 59973147.78 | 1669.06 | 4.18 | |
Maximum of Months | 0.379357E+09 | 26375.08 | 38.22 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.692732E+09 | 30721.44 | 27-JAN-08:62 | -3.5 |
February | 0.415543E+09 | 30746.13 | 03-FEB-08:62 | -2.0 |
March | 0.320675E+09 | 31018.25 | 02-MAR-08:61 | -0.9 |
April | 84486810.11 | 6379.39 | 12-APR-08:63 | 11.15 |
May | 0.103964E+09 | 2268.08 | 21-MAY-16:02 | 33.57 |
June | 0.100424E+09 | 3065.24 | 18-JUN-16:01 | 37.20 |
July | 0.102536E+09 | 3268.33 | 02-JUL-16:01 | 38.22 |
August | 97122748.56 | 2821.24 | 06-AUG-16:01 | 36.10 |
September | 78509498.59 | 2077.83 | 17-SEP-16:02 | 32.62 |
October | 64833591.92 | 1846.08 | 01-OCT-16:02 | 31.60 |
November | 0.170823E+09 | 28443.46 | 30-NOV-09:02 | 8.17 |
December | 0.757343E+09 | 30730.34 | 27-DEC-08:62 | -3.4 |
Annual Sum or Average | 0.298899E+10 | |||
Minimum of Months | 64833591.92 | 1846.08 | -3.5 | |
Maximum of Months | 0.757343E+09 | 31018.25 | 38.22 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.750231E+10 | 4589.20 | 01-JAN-10:09 | 0.223514E+10 | 1348.26 | 01-JAN-10:09 |
February | 0.678234E+10 | 4589.20 | 01-FEB-10:09 | 0.202238E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.751014E+10 | 4589.20 | 01-MAR-10:09 | 0.224215E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.727015E+10 | 4589.20 | 01-APR-09:09 | 0.216638E+10 | 1348.26 | 01-APR-09:09 |
May | 0.750231E+10 | 4589.20 | 01-MAY-09:09 | 0.223514E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.727015E+10 | 4589.20 | 01-JUN-09:09 | 0.217123E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.751014E+10 | 4589.20 | 01-JUL-09:09 | 0.223729E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.750231E+10 | 4589.20 | 01-AUG-09:09 | 0.223756E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.727797E+10 | 4589.20 | 01-SEP-09:09 | 0.217096E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.750231E+10 | 4589.20 | 01-OCT-09:09 | 0.223514E+10 | 1348.26 | 01-OCT-09:09 |
November | 0.724667E+10 | 4589.20 | 01-NOV-09:09 | 0.215964E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.751797E+10 | 4589.20 | 01-DEC-10:09 | 0.224431E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.883948E+11 | 0.263573E+11 | ||||
Minimum of Months | 0.678234E+10 | 4589.20 | 0.202238E+10 | 1348.26 | ||
Maximum of Months | 0.751797E+10 | 4589.20 | 0.224431E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.451294E+10 | 2760.58 | 01-JAN-10:09 | 0.111757E+10 | 674.13 | 01-JAN-10:09 |
February | 0.407985E+10 | 2760.58 | 01-FEB-10:09 | 0.101119E+10 | 674.13 | 01-FEB-10:09 |
March | 0.451765E+10 | 2760.58 | 01-MAR-10:09 | 0.112107E+10 | 674.13 | 01-MAR-10:09 |
April | 0.437329E+10 | 2760.58 | 01-APR-09:09 | 0.108319E+10 | 674.13 | 01-APR-09:09 |
May | 0.451294E+10 | 2760.58 | 01-MAY-09:09 | 0.111757E+10 | 674.13 | 01-MAY-09:09 |
June | 0.437329E+10 | 2760.58 | 01-JUN-09:09 | 0.108562E+10 | 674.13 | 01-JUN-09:09 |
July | 0.451765E+10 | 2760.58 | 01-JUL-09:09 | 0.111865E+10 | 674.13 | 01-JUL-09:09 |
August | 0.451294E+10 | 2760.58 | 01-AUG-09:09 | 0.111878E+10 | 674.13 | 01-AUG-09:09 |
September | 0.437799E+10 | 2760.58 | 01-SEP-09:09 | 0.108548E+10 | 674.13 | 01-SEP-09:09 |
October | 0.451294E+10 | 2760.58 | 01-OCT-09:09 | 0.111757E+10 | 674.13 | 01-OCT-09:09 |
November | 0.435916E+10 | 2760.58 | 01-NOV-09:09 | 0.107982E+10 | 674.13 | 01-NOV-09:09 |
December | 0.452236E+10 | 2760.58 | 01-DEC-10:09 | 0.112215E+10 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.531730E+11 | 0.131787E+11 | ||||
Minimum of Months | 0.407985E+10 | 2760.58 | 0.101119E+10 | 674.13 | ||
Maximum of Months | 0.452236E+10 | 2760.58 | 0.112215E+10 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.326451E+10 | 2510.11 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.295632E+10 | 2510.11 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.333300E+10 | 2510.11 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.316749E+10 | 2510.11 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.329875E+10 | 2510.11 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.321885E+10 | 2510.11 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.324739E+10 | 2510.11 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.333300E+10 | 2510.11 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.316749E+10 | 2510.11 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.326451E+10 | 2510.11 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.316749E+10 | 2510.11 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.324739E+10 | 2510.11 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.386662E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.295632E+10 | 2510.11 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.333300E+10 | 2510.11 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.326451E+10 | 2510.11 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.295632E+10 | 2510.11 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.333300E+10 | 2510.11 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.316749E+10 | 2510.11 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.329875E+10 | 2510.11 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.321885E+10 | 2510.11 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.324739E+10 | 2510.11 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.333300E+10 | 2510.11 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.316749E+10 | 2510.11 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.326451E+10 | 2510.11 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.316749E+10 | 2510.11 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.324739E+10 | 2510.11 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.386662E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.295632E+10 | 2510.11 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.333300E+10 | 2510.11 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.326451E+10 | 2510.11 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.295632E+10 | 2510.11 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.333300E+10 | 2510.11 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.316749E+10 | 2510.11 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.329875E+10 | 2510.11 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.321885E+10 | 2510.11 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.324739E+10 | 2510.11 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.333300E+10 | 2510.11 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.316749E+10 | 2510.11 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.326451E+10 | 2510.11 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.316749E+10 | 2510.11 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.324739E+10 | 2510.11 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.386662E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.295632E+10 | 2510.11 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.333300E+10 | 2510.11 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.343207E+10 | 2872.47 | 01-JAN-11:09 | 0.162546E+10 | 1348.26 | 01-JAN-11:09 |
February | 0.310878E+10 | 2872.47 | 01-FEB-10:09 | 0.147229E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.351044E+10 | 2872.47 | 01-MAR-10:09 | 0.166213E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.333084E+10 | 2872.47 | 01-APR-09:09 | 0.157746E+10 | 1348.26 | 01-APR-09:09 |
May | 0.347125E+10 | 2872.47 | 01-MAY-09:09 | 0.164379E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.338962E+10 | 2872.47 | 01-JUN-09:09 | 0.160496E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.341247E+10 | 2872.47 | 01-JUL-09:09 | 0.161629E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.351044E+10 | 2872.47 | 01-AUG-09:09 | 0.166213E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.333084E+10 | 2872.47 | 01-SEP-09:09 | 0.157746E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.343207E+10 | 2872.47 | 01-OCT-10:09 | 0.162546E+10 | 1348.26 | 01-OCT-10:09 |
November | 0.333084E+10 | 2872.47 | 01-NOV-09:09 | 0.157746E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.341247E+10 | 2872.47 | 01-DEC-10:09 | 0.161629E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.406721E+11 | 0.192612E+11 | ||||
Minimum of Months | 0.310878E+10 | 2872.47 | 0.147229E+10 | 1348.26 | ||
Maximum of Months | 0.351044E+10 | 2872.47 | 0.166213E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.176168E+10 | 1474.43 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.159573E+10 | 1474.43 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.180191E+10 | 1474.43 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.170972E+10 | 1474.43 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.178179E+10 | 1474.43 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.173989E+10 | 1474.43 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.175162E+10 | 1474.43 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.180191E+10 | 1474.43 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.170972E+10 | 1474.43 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.176168E+10 | 1474.43 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.170972E+10 | 1474.43 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.175162E+10 | 1474.43 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.208770E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.159573E+10 | 1474.43 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.180191E+10 | 1474.43 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.176168E+10 | 1474.43 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.159573E+10 | 1474.43 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.180191E+10 | 1474.43 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.170972E+10 | 1474.43 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.178179E+10 | 1474.43 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.173989E+10 | 1474.43 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.175162E+10 | 1474.43 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.180191E+10 | 1474.43 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.170972E+10 | 1474.43 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.176168E+10 | 1474.43 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.170972E+10 | 1474.43 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.175162E+10 | 1474.43 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.208770E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.159573E+10 | 1474.43 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.180191E+10 | 1474.43 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.176168E+10 | 1474.43 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.159573E+10 | 1474.43 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.180191E+10 | 1474.43 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.170972E+10 | 1474.43 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.178179E+10 | 1474.43 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.173989E+10 | 1474.43 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.175162E+10 | 1474.43 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.180191E+10 | 1474.43 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.170972E+10 | 1474.43 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.176168E+10 | 1474.43 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.170972E+10 | 1474.43 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.175162E+10 | 1474.43 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.208770E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.159573E+10 | 1474.43 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.180191E+10 | 1474.43 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.176168E+10 | 1474.43 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.159573E+10 | 1474.43 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.180191E+10 | 1474.43 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.170972E+10 | 1474.43 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.178179E+10 | 1474.43 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.173989E+10 | 1474.43 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.175162E+10 | 1474.43 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.180191E+10 | 1474.43 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.170972E+10 | 1474.43 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.176168E+10 | 1474.43 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.170972E+10 | 1474.43 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.175162E+10 | 1474.43 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.208770E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.159573E+10 | 1474.43 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.180191E+10 | 1474.43 | 0.831065E+09 | 674.13 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.750231E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254788E+10 |
February | 0.305697E+10 | 0.678234E+10 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186510E+10 |
March | 0.335708E+10 | 0.751014E+10 | 0.224215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4486653.86 | 0.165840E+10 |
April | 0.327081E+10 | 0.727015E+10 | 0.216638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420080E+09 | 0.705795E+09 |
May | 0.336680E+10 | 0.750231E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100194E+10 | 0.257485E+09 |
June | 0.325380E+10 | 0.727015E+10 | 0.217123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168516E+10 | 85461678.99 |
July | 0.339353E+10 | 0.751014E+10 | 0.223729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153482E+10 | 60618430.34 |
August | 0.334857E+10 | 0.750231E+10 | 0.223756E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129832E+10 | 0.120182E+09 |
September | 0.327932E+10 | 0.727797E+10 | 0.217096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.934400E+09 | 0.139216E+09 |
October | 0.338624E+10 | 0.750231E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225897E+09 | 0.787048E+09 |
November | 0.327446E+10 | 0.724667E+10 | 0.215964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 925.13 | 0.199005E+10 |
December | 0.340325E+10 | 0.751797E+10 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264815E+10 |
Annual Sum or Average | 0.397770E+11 | 0.883948E+11 | 0.263573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.710510E+10 | 0.128654E+11 |
Minimum of Months | 0.305697E+10 | 0.678234E+10 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60618430.34 |
Maximum of Months | 0.340325E+10 | 0.751797E+10 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168516E+10 | 0.264815E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.451294E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129905E+10 |
February | 0.152844E+10 | 0.407985E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.928138E+09 |
March | 0.167849E+10 | 0.451765E+10 | 0.112107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2423445.28 | 0.803041E+09 |
April | 0.163536E+10 | 0.437329E+10 | 0.108319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225058E+09 | 0.308174E+09 |
May | 0.168335E+10 | 0.451294E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.534241E+09 | 93215896.50 |
June | 0.162685E+10 | 0.437329E+10 | 0.108562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.899800E+09 | 28914909.38 |
July | 0.169671E+10 | 0.451765E+10 | 0.111865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.825126E+09 | 20679204.80 |
August | 0.167424E+10 | 0.451294E+10 | 0.111878E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.700436E+09 | 44641317.00 |
September | 0.163961E+10 | 0.437799E+10 | 0.108548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512554E+09 | 50918461.65 |
October | 0.169307E+10 | 0.451294E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123251E+09 | 0.353557E+09 |
November | 0.163718E+10 | 0.435916E+10 | 0.107982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 503.07 | 0.980721E+09 |
December | 0.170157E+10 | 0.452236E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136957E+10 |
Annual Sum or Average | 0.198880E+11 | 0.531730E+11 | 0.131787E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382289E+10 | 0.628062E+10 |
Minimum of Months | 0.152844E+10 | 0.407985E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20679204.80 |
Maximum of Months | 0.170157E+10 | 0.452236E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.899800E+09 | 0.136957E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.326451E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130179E+10 |
February | 0.914877E+09 | 0.295632E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.942402E+09 |
March | 0.103395E+10 | 0.333300E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2423150.80 | 0.830617E+09 |
April | 0.984131E+09 | 0.316749E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218109E+09 | 0.327107E+09 |
May | 0.102058E+10 | 0.329875E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.524176E+09 | 0.102440E+09 |
June | 0.998711E+09 | 0.321885E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.894031E+09 | 31809446.91 |
July | 0.100600E+10 | 0.324739E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.813714E+09 | 25835230.21 |
August | 0.103395E+10 | 0.333300E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.691511E+09 | 46806864.04 |
September | 0.984131E+09 | 0.316749E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503577E+09 | 59172618.26 |
October | 0.100722E+10 | 0.326451E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119310E+09 | 0.375605E+09 |
November | 0.973196E+09 | 0.316749E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 503.07 | 0.100502E+10 |
December | 0.100600E+10 | 0.324739E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136953E+10 |
Annual Sum or Average | 0.119700E+11 | 0.386662E+11 | 0.104672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376685E+10 | 0.641813E+10 |
Minimum of Months | 0.914877E+09 | 0.295632E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25835230.21 |
Maximum of Months | 0.103395E+10 | 0.333300E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.894031E+09 | 0.136953E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.326451E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128636E+10 |
February | 0.914877E+09 | 0.295632E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.931395E+09 |
March | 0.103395E+10 | 0.333300E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2423150.80 | 0.822840E+09 |
April | 0.984131E+09 | 0.316749E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218144E+09 | 0.326133E+09 |
May | 0.102058E+10 | 0.329875E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.523968E+09 | 0.102760E+09 |
June | 0.998711E+09 | 0.321885E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.893472E+09 | 32436152.97 |
July | 0.100600E+10 | 0.324739E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.813096E+09 | 26492710.35 |
August | 0.103395E+10 | 0.333300E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.691073E+09 | 47414308.54 |
September | 0.984131E+09 | 0.316749E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503494E+09 | 59577146.04 |
October | 0.100722E+10 | 0.326451E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119265E+09 | 0.375441E+09 |
November | 0.973196E+09 | 0.316749E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 503.07 | 0.100016E+10 |
December | 0.100600E+10 | 0.324739E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135558E+10 |
Annual Sum or Average | 0.119700E+11 | 0.386662E+11 | 0.104672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376494E+10 | 0.636659E+10 |
Minimum of Months | 0.914877E+09 | 0.295632E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26492710.35 |
Maximum of Months | 0.103395E+10 | 0.333300E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.893472E+09 | 0.135558E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.326451E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126904E+10 |
February | 0.914877E+09 | 0.295632E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.917993E+09 |
March | 0.103395E+10 | 0.333300E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2423150.80 | 0.810981E+09 |
April | 0.984131E+09 | 0.316749E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218395E+09 | 0.322869E+09 |
May | 0.102058E+10 | 0.329875E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.524494E+09 | 0.101066E+09 |
June | 0.998711E+09 | 0.321885E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.894194E+09 | 31454386.16 |
July | 0.100600E+10 | 0.324739E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.813726E+09 | 25596296.21 |
August | 0.103395E+10 | 0.333300E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.691524E+09 | 46551793.06 |
September | 0.984131E+09 | 0.316749E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503606E+09 | 58803016.13 |
October | 0.100722E+10 | 0.326451E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119343E+09 | 0.373643E+09 |
November | 0.973196E+09 | 0.316749E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 503.07 | 0.992553E+09 |
December | 0.100600E+10 | 0.324739E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133954E+10 |
Annual Sum or Average | 0.119700E+11 | 0.386662E+11 | 0.104672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376770E+10 | 0.629009E+10 |
Minimum of Months | 0.914877E+09 | 0.295632E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25596296.21 |
Maximum of Months | 0.103395E+10 | 0.333300E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.894194E+09 | 0.133954E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.343207E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229471E+10 |
February | 0.313522E+10 | 0.310878E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166299E+10 |
March | 0.355148E+10 | 0.351044E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4361886.26 | 0.147313E+10 |
April | 0.338259E+10 | 0.333084E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395833E+09 | 0.601785E+09 |
May | 0.349753E+10 | 0.347125E+10 | 0.164379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.950613E+09 | 0.198081E+09 |
June | 0.343071E+10 | 0.338962E+10 | 0.160496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161730E+10 | 62838306.06 |
July | 0.344942E+10 | 0.341247E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146892E+10 | 52286523.34 |
August | 0.355148E+10 | 0.351044E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124823E+10 | 94735861.09 |
September | 0.338259E+10 | 0.333084E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.905863E+09 | 0.119217E+09 |
October | 0.344359E+10 | 0.343207E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215102E+09 | 0.700305E+09 |
November | 0.331698E+10 | 0.333084E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 894.61 | 0.181121E+10 |
December | 0.344942E+10 | 0.341247E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242011E+10 |
Annual Sum or Average | 0.410346E+11 | 0.406721E+11 | 0.192612E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.680623E+10 | 0.114914E+11 |
Minimum of Months | 0.313522E+10 | 0.310878E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52286523.34 |
Maximum of Months | 0.355148E+10 | 0.351044E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161730E+10 | 0.242011E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.176168E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124727E+10 |
February | 0.156756E+10 | 0.159573E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.898208E+09 |
March | 0.177569E+10 | 0.180191E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2423150.80 | 0.790407E+09 |
April | 0.169125E+10 | 0.170972E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219865E+09 | 0.319821E+09 |
May | 0.174872E+10 | 0.178179E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.527597E+09 | 0.101635E+09 |
June | 0.171530E+10 | 0.173989E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.897406E+09 | 31218911.48 |
July | 0.172466E+10 | 0.175162E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.816011E+09 | 25832258.00 |
August | 0.177569E+10 | 0.180191E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.693625E+09 | 48513980.36 |
September | 0.169125E+10 | 0.170972E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.504456E+09 | 61344142.96 |
October | 0.172174E+10 | 0.176168E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119718E+09 | 0.375882E+09 |
November | 0.165844E+10 | 0.170972E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 499.69 | 0.983462E+09 |
December | 0.172466E+10 | 0.175162E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132133E+10 |
Annual Sum or Average | 0.205167E+11 | 0.208770E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378110E+10 | 0.620493E+10 |
Minimum of Months | 0.156756E+10 | 0.159573E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25832258.00 |
Maximum of Months | 0.177569E+10 | 0.180191E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.897406E+09 | 0.132133E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.176168E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124140E+10 |
February | 0.156756E+10 | 0.159573E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.892689E+09 |
March | 0.177569E+10 | 0.180191E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2423150.80 | 0.783600E+09 |
April | 0.169125E+10 | 0.170972E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220015E+09 | 0.318026E+09 |
May | 0.174872E+10 | 0.178179E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.527787E+09 | 0.101027E+09 |
June | 0.171530E+10 | 0.173989E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.897621E+09 | 30911092.19 |
July | 0.172466E+10 | 0.175162E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.816218E+09 | 25562338.88 |
August | 0.177569E+10 | 0.180191E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.693759E+09 | 48264763.42 |
September | 0.169125E+10 | 0.170972E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.504504E+09 | 61085953.80 |
October | 0.172174E+10 | 0.176168E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119748E+09 | 0.374932E+09 |
November | 0.165844E+10 | 0.170972E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 499.59 | 0.979073E+09 |
December | 0.172466E+10 | 0.175162E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131690E+10 |
Annual Sum or Average | 0.205167E+11 | 0.208770E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378208E+10 | 0.617346E+10 |
Minimum of Months | 0.156756E+10 | 0.159573E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25562338.88 |
Maximum of Months | 0.177569E+10 | 0.180191E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.897621E+09 | 0.131690E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.176168E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122855E+10 |
February | 0.156756E+10 | 0.159573E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.878785E+09 |
March | 0.177569E+10 | 0.180191E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2423150.95 | 0.766598E+09 |
April | 0.169125E+10 | 0.170972E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220326E+09 | 0.312878E+09 |
May | 0.174872E+10 | 0.178179E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.528096E+09 | 99218092.11 |
June | 0.171530E+10 | 0.173989E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.897764E+09 | 30325715.56 |
July | 0.172466E+10 | 0.175162E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.816198E+09 | 25235727.13 |
August | 0.177569E+10 | 0.180191E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.693680E+09 | 48028332.93 |
September | 0.169125E+10 | 0.170972E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.504479E+09 | 60810343.42 |
October | 0.172174E+10 | 0.176168E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119770E+09 | 0.372447E+09 |
November | 0.165844E+10 | 0.170972E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 499.67 | 0.968631E+09 |
December | 0.172466E+10 | 0.175162E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130710E+10 |
Annual Sum or Average | 0.205167E+11 | 0.208770E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378274E+10 | 0.609861E+10 |
Minimum of Months | 0.156756E+10 | 0.159573E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25235727.13 |
Maximum of Months | 0.177569E+10 | 0.180191E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.897764E+09 | 0.130710E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.176168E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151827E+10 |
February | 0.156756E+10 | 0.159573E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112546E+10 |
March | 0.177569E+10 | 0.180191E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2547929.37 | 0.101137E+10 |
April | 0.169125E+10 | 0.170972E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236286E+09 | 0.460875E+09 |
May | 0.174872E+10 | 0.178179E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.570650E+09 | 0.182220E+09 |
June | 0.171530E+10 | 0.173989E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.968865E+09 | 62565468.84 |
July | 0.172466E+10 | 0.175162E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.868295E+09 | 53823305.84 |
August | 0.177569E+10 | 0.180191E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.733145E+09 | 90473636.24 |
September | 0.169125E+10 | 0.170972E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.516668E+09 | 0.115296E+09 |
October | 0.172174E+10 | 0.176168E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123897E+09 | 0.529485E+09 |
November | 0.165844E+10 | 0.170972E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 522.55 | 0.122605E+10 |
December | 0.172466E+10 | 0.175162E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157480E+10 |
Annual Sum or Average | 0.205167E+11 | 0.208770E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402036E+10 | 0.795069E+10 |
Minimum of Months | 0.156756E+10 | 0.159573E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53823305.84 |
Maximum of Months | 0.177569E+10 | 0.180191E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.968865E+09 | 0.157480E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 4589.20 | 01-JAN-10:09 | 1348.26 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4759.78 | 26-JAN-12:10 |
February | 4050.04 | 03-FEB-13:09 | 4589.20 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4405.18 | 08-FEB-18:00 |
March | 4050.04 | 03-MAR-13:09 | 4589.20 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 295.61 | 22-MAR-13:00 | 4306.07 | 01-MAR-18:00 |
April | 4050.04 | 01-APR-12:09 | 4589.20 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2329.01 | 21-APR-15:00 | 2875.97 | 06-APR-12:00 |
May | 4050.04 | 05-MAY-12:09 | 4589.20 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2978.24 | 19-MAY-14:00 | 1256.31 | 01-MAY-12:00 |
June | 4050.04 | 02-JUN-12:09 | 4589.20 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3756.84 | 02-JUN-16:00 | 769.58 | 28-JUN-02:00 |
July | 4050.04 | 01-JUL-12:09 | 4589.20 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3667.71 | 03-JUL-17:00 | 605.29 | 08-JUL-15:00 |
August | 4050.04 | 04-AUG-12:09 | 4589.20 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3392.40 | 07-AUG-16:00 | 810.91 | 14-AUG-11:10 |
September | 4050.04 | 01-SEP-12:09 | 4589.20 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2506.35 | 19-SEP-14:00 | 1642.25 | 23-SEP-17:00 |
October | 4050.04 | 01-OCT-12:09 | 4589.20 | 01-OCT-09:09 | 1348.26 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2302.69 | 01-OCT-15:00 | 2747.99 | 24-OCT-11:10 |
November | 4050.04 | 03-NOV-12:09 | 4589.20 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.77 | 03-NOV-16:00 | 4314.21 | 26-NOV-18:00 |
December | 4050.04 | 01-DEC-13:09 | 4589.20 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5586.01 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 4589.20 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 605.29 | |||||
Maximum of Months | 4050.04 | 4589.20 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 3756.84 | 5586.01 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 2760.58 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2613.89 | 26-JAN-12:10 |
February | 2024.96 | 03-FEB-13:09 | 2760.58 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2364.33 | 08-FEB-18:00 |
March | 2024.96 | 03-MAR-13:09 | 2760.58 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 158.50 | 22-MAR-13:00 | 2330.08 | 01-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 2760.58 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1213.30 | 21-APR-15:00 | 1592.41 | 11-APR-11:10 |
May | 2024.96 | 05-MAY-12:09 | 2760.58 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1582.04 | 19-MAY-14:00 | 668.82 | 01-MAY-12:00 |
June | 2024.96 | 02-JUN-12:09 | 2760.58 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.25 | 02-JUN-16:00 | 229.85 | 28-JUN-02:00 |
July | 2024.96 | 01-JUL-12:09 | 2760.58 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1980.07 | 03-JUL-17:00 | 325.28 | 08-JUL-15:00 |
August | 2024.96 | 04-AUG-12:09 | 2760.58 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1839.99 | 07-AUG-16:00 | 448.44 | 14-AUG-11:10 |
September | 2024.96 | 01-SEP-12:09 | 2760.58 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1376.39 | 19-SEP-14:00 | 892.82 | 23-SEP-17:00 |
October | 2024.96 | 01-OCT-12:09 | 2760.58 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1248.93 | 01-OCT-15:00 | 1583.08 | 24-OCT-11:10 |
November | 2024.96 | 03-NOV-12:09 | 2760.58 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 | 03-NOV-16:00 | 2329.09 | 26-NOV-18:00 |
December | 2024.96 | 01-DEC-13:09 | 2760.58 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3072.62 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2760.58 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.85 | |||||
Maximum of Months | 2024.96 | 2760.58 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.25 | 3072.62 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2510.11 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2613.89 | 26-JAN-12:10 |
February | 2024.96 | 04-FEB-13:09 | 2510.11 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2339.06 | 08-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2510.11 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 158.50 | 22-MAR-13:00 | 2330.08 | 01-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 2510.11 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1213.30 | 21-APR-15:00 | 1586.81 | 11-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 2510.11 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1582.04 | 19-MAY-14:00 | 668.82 | 01-MAY-12:00 |
June | 2024.96 | 03-JUN-12:09 | 2510.11 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.27 | 02-JUN-16:00 | 237.00 | 28-JUN-02:00 |
July | 2024.96 | 01-JUL-12:09 | 2510.11 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1980.08 | 03-JUL-17:00 | 325.28 | 08-JUL-15:00 |
August | 2024.96 | 05-AUG-12:09 | 2510.11 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1840.00 | 07-AUG-16:00 | 448.44 | 14-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 2510.11 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1376.39 | 19-SEP-14:00 | 892.78 | 23-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2510.11 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1248.93 | 01-OCT-15:00 | 1583.03 | 24-OCT-11:10 |
November | 2024.96 | 04-NOV-12:09 | 2510.11 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 | 03-NOV-16:00 | 2329.09 | 26-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2510.11 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3072.62 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2510.11 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.00 | |||||
Maximum of Months | 2024.96 | 2510.11 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.27 | 3072.62 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2510.11 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2613.89 | 26-JAN-12:10 |
February | 2024.96 | 04-FEB-13:09 | 2510.11 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2317.77 | 08-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2510.11 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 158.50 | 22-MAR-13:00 | 2330.08 | 01-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 2510.11 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1213.30 | 21-APR-15:00 | 1578.75 | 11-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 2510.11 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1582.04 | 19-MAY-14:00 | 668.82 | 01-MAY-12:00 |
June | 2024.96 | 03-JUN-12:09 | 2510.11 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.26 | 02-JUN-16:00 | 238.65 | 28-JUN-02:00 |
July | 2024.96 | 01-JUL-12:09 | 2510.11 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1980.07 | 03-JUL-17:00 | 325.28 | 08-JUL-15:00 |
August | 2024.96 | 05-AUG-12:09 | 2510.11 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1839.99 | 07-AUG-16:00 | 448.44 | 14-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 2510.11 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1376.39 | 19-SEP-14:00 | 892.79 | 23-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2510.11 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1248.93 | 01-OCT-15:00 | 1582.55 | 24-OCT-11:10 |
November | 2024.96 | 04-NOV-12:09 | 2510.11 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 | 03-NOV-16:00 | 2329.09 | 26-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2510.11 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3072.62 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2510.11 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.65 | |||||
Maximum of Months | 2024.96 | 2510.11 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.26 | 3072.62 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2510.11 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2613.89 | 26-JAN-12:10 |
February | 2024.96 | 04-FEB-13:09 | 2510.11 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2283.77 | 08-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2510.11 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 158.50 | 22-MAR-13:00 | 2330.08 | 01-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 2510.11 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1213.30 | 21-APR-15:00 | 1557.67 | 11-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 2510.11 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1582.04 | 19-MAY-14:00 | 668.82 | 01-MAY-12:00 |
June | 2024.96 | 03-JUN-12:09 | 2510.11 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.27 | 02-JUN-16:00 | 235.63 | 28-JUN-02:00 |
July | 2024.96 | 01-JUL-12:09 | 2510.11 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1980.07 | 03-JUL-17:00 | 325.28 | 08-JUL-15:00 |
August | 2024.96 | 05-AUG-12:09 | 2510.11 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1840.00 | 07-AUG-16:00 | 448.44 | 14-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 2510.11 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1376.39 | 19-SEP-14:00 | 892.77 | 23-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2510.11 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1248.93 | 01-OCT-15:00 | 1567.43 | 24-OCT-11:10 |
November | 2024.96 | 04-NOV-12:09 | 2510.11 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 | 03-NOV-16:00 | 2329.09 | 26-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2510.11 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3072.62 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2510.11 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.63 | |||||
Maximum of Months | 2024.96 | 2510.11 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.27 | 3072.62 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 2872.47 | 01-JAN-11:09 | 1348.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4695.52 | 26-JAN-12:10 |
February | 5400.05 | 04-FEB-15:09 | 2872.47 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4040.79 | 08-FEB-18:00 |
March | 5400.05 | 04-MAR-15:09 | 2872.47 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 285.58 | 22-MAR-13:00 | 4193.35 | 01-MAR-18:00 |
April | 5400.05 | 01-APR-14:09 | 2872.47 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2194.06 | 21-APR-15:00 | 2733.05 | 11-APR-11:10 |
May | 5400.05 | 06-MAY-14:09 | 2872.47 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2853.75 | 19-MAY-14:00 | 1206.11 | 01-MAY-12:00 |
June | 5400.05 | 03-JUN-14:09 | 2872.47 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3682.72 | 02-JUN-16:00 | 450.25 | 28-JUN-02:00 |
July | 5400.05 | 01-JUL-14:09 | 2872.47 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3564.46 | 03-JUL-17:00 | 585.90 | 08-JUL-15:00 |
August | 5400.05 | 05-AUG-14:09 | 2872.47 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3310.34 | 07-AUG-16:00 | 804.87 | 14-AUG-11:10 |
September | 5400.05 | 02-SEP-14:09 | 2872.47 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2472.51 | 19-SEP-14:00 | 1605.74 | 23-SEP-17:00 |
October | 5400.05 | 07-OCT-14:09 | 2872.47 | 01-OCT-10:09 | 1348.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2247.00 | 01-OCT-15:00 | 2750.17 | 24-OCT-11:10 |
November | 5400.05 | 04-NOV-14:09 | 2872.47 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.75 | 08-NOV-15:00 | 4192.77 | 26-NOV-18:00 |
December | 5400.05 | 02-DEC-15:09 | 2872.47 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5518.47 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 2872.47 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 450.25 | |||||
Maximum of Months | 5400.05 | 2872.47 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 3682.72 | 5518.47 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1474.43 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2613.89 | 26-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1474.43 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2231.45 | 08-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1474.43 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 158.50 | 22-MAR-13:00 | 2330.08 | 01-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1474.43 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1213.30 | 21-APR-15:00 | 1510.58 | 11-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1474.43 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1582.04 | 19-MAY-14:00 | 668.82 | 01-MAY-12:00 |
June | 2699.95 | 03-JUN-14:09 | 1474.43 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.25 | 02-JUN-16:00 | 223.15 | 28-JUN-02:00 |
July | 2699.95 | 01-JUL-14:09 | 1474.43 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1980.06 | 03-JUL-17:00 | 325.28 | 08-JUL-15:00 |
August | 2699.95 | 05-AUG-14:09 | 1474.43 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1839.96 | 07-AUG-16:00 | 448.44 | 14-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1474.43 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1376.39 | 19-SEP-14:00 | 892.75 | 23-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1474.43 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1248.93 | 01-OCT-15:00 | 1526.28 | 24-OCT-11:10 |
November | 2699.95 | 04-NOV-14:09 | 1474.43 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 | 08-NOV-15:00 | 2329.09 | 26-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1474.43 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3072.62 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1474.43 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.15 | |||||
Maximum of Months | 2699.95 | 1474.43 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.25 | 3072.62 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1474.43 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2613.89 | 26-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1474.43 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2231.40 | 08-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1474.43 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 158.50 | 22-MAR-13:00 | 2330.08 | 01-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1474.43 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1213.30 | 21-APR-15:00 | 1500.85 | 11-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1474.43 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1582.04 | 19-MAY-14:00 | 668.82 | 01-MAY-12:00 |
June | 2699.95 | 03-JUN-14:09 | 1474.43 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.25 | 02-JUN-16:00 | 222.33 | 28-JUN-02:00 |
July | 2699.95 | 01-JUL-14:09 | 1474.43 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1980.06 | 03-JUL-17:00 | 325.28 | 08-JUL-15:00 |
August | 2699.95 | 05-AUG-14:09 | 1474.43 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1839.96 | 07-AUG-16:00 | 448.44 | 14-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1474.43 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1376.39 | 19-SEP-14:00 | 892.75 | 23-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1474.43 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1248.93 | 01-OCT-15:00 | 1519.75 | 24-OCT-11:10 |
November | 2699.95 | 04-NOV-14:09 | 1474.43 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 | 08-NOV-15:00 | 2329.09 | 26-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1474.43 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3072.62 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1474.43 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.33 | |||||
Maximum of Months | 2699.95 | 1474.43 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.25 | 3072.62 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1474.43 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2613.89 | 26-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1474.43 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2231.40 | 08-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1474.43 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 158.50 | 22-MAR-13:00 | 2330.08 | 01-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1474.43 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1213.30 | 21-APR-15:00 | 1474.76 | 11-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1474.43 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1582.04 | 19-MAY-14:00 | 668.82 | 01-MAY-12:00 |
June | 2699.95 | 03-JUN-14:09 | 1474.43 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.26 | 02-JUN-16:00 | 221.06 | 28-JUN-02:00 |
July | 2699.95 | 01-JUL-14:09 | 1474.43 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1980.05 | 03-JUL-17:00 | 325.28 | 08-JUL-15:00 |
August | 2699.95 | 05-AUG-14:09 | 1474.43 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1839.95 | 07-AUG-16:00 | 448.44 | 14-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1474.43 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1376.39 | 19-SEP-14:00 | 892.75 | 23-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1474.43 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1248.93 | 01-OCT-15:00 | 1500.28 | 24-OCT-11:10 |
November | 2699.95 | 04-NOV-14:09 | 1474.43 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 | 08-NOV-15:00 | 2329.09 | 26-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1474.43 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3072.62 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1474.43 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.06 | |||||
Maximum of Months | 2699.95 | 1474.43 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.26 | 3072.62 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1474.43 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2678.15 | 26-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1474.43 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2519.17 | 08-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1474.43 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 168.54 | 22-MAR-13:00 | 2442.80 | 01-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1474.43 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1348.25 | 21-APR-15:00 | 1635.11 | 06-APR-12:00 |
May | 2699.95 | 06-MAY-14:09 | 1474.43 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1706.53 | 19-MAY-14:00 | 719.02 | 01-MAY-12:00 |
June | 2699.95 | 03-JUN-14:09 | 1474.43 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2122.39 | 02-JUN-16:00 | 518.53 | 28-JUN-02:00 |
July | 2699.95 | 01-JUL-14:09 | 1474.43 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2083.27 | 03-JUL-17:00 | 344.67 | 08-JUL-15:00 |
August | 2699.95 | 05-AUG-14:09 | 1474.43 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1921.92 | 07-AUG-16:00 | 476.63 | 14-AUG-01:00 |
September | 2699.95 | 02-SEP-14:09 | 1474.43 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1410.22 | 19-SEP-14:00 | 929.18 | 23-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1474.43 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1304.62 | 01-OCT-15:00 | 1465.63 | 24-OCT-11:10 |
November | 2699.95 | 04-NOV-14:09 | 1474.43 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 | 03-NOV-16:00 | 2450.53 | 26-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1474.43 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3140.15 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1474.43 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 344.67 | |||||
Maximum of Months | 2699.95 | 1474.43 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2122.39 | 3140.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8984.14 | 27-JAN-09:04 | 2700.03 | 19322.89 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1050.96 |
February | 8133.51 | 01-FEB-09:03 | 2700.03 | 19322.89 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1104.46 |
March | 8292.31 | 02-MAR-09:04 | 2700.03 | 19322.89 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 788.18 |
April | 18081.77 | 29-APR-08:62 | 1350.01 | 9661.45 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.51 |
May | 40732.21 | 15-MAY-08:62 | 2025.02 | 14492.17 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.65 |
June | 40365.34 | 12-JUN-08:62 | 2025.02 | 14492.17 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.94 |
July | 38379.75 | 03-JUL-08:61 | 2700.03 | 19322.89 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 128.71 | 0.00 |
August | 41572.80 | 23-AUG-08:61 | 2362.52 | 16907.53 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.75 |
September | 44255.07 | 11-SEP-08:62 | 2025.02 | 14492.17 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.70 |
October | 40685.20 | 02-OCT-08:61 | 2362.52 | 16907.53 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.63 |
November | 33448.30 | 10-NOV-09:02 | 1687.52 | 12076.81 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 322.38 |
December | 8765.55 | 27-DEC-09:04 | 2700.03 | 19322.89 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 809.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8133.51 | 1350.01 | 9661.45 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 44255.07 | 2700.03 | 19322.89 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 128.71 | 1104.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4605.05 | 27-JAN-09:03 | 1349.97 | 11623.51 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 524.80 |
February | 16169.17 | 20-FEB-18:40 | 8099.84 | 11042.33 | 2696.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.23 |
March | 16510.88 | 12-MAR-17:40 | 8099.84 | 11042.33 | 2696.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.56 |
April | 16709.77 | 26-APR-21:43 | 9112.33 | 24845.25 | 6067.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.58 |
May | 22191.54 | 17-MAY-08:62 | 843.73 | 7264.69 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.42 |
June | 21190.75 | 12-JUN-08:62 | 1012.48 | 8717.63 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.19 |
July | 20039.04 | 10-JUL-08:61 | 1349.97 | 11623.51 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 23.13 | 0.00 |
August | 21635.67 | 23-AUG-08:61 | 1181.23 | 10170.57 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.29 |
September | 23102.94 | 11-SEP-08:62 | 1012.48 | 8717.63 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.72 |
October | 22226.51 | 19-OCT-08:62 | 843.73 | 7264.69 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.60 |
November | 22160.99 | 10-NOV-09:02 | 843.73 | 7264.69 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.17 |
December | 4513.79 | 27-DEC-09:03 | 1349.97 | 11623.51 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 450.85 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4513.79 | 843.73 | 7264.69 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23102.94 | 9112.33 | 24845.25 | 6067.15 | 0.00 | 0.00 | 0.00 | 0.00 | 23.13 | 524.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5052.70 | 27-JAN-08:03 | 1012.48 | 7926.65 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 578.46 |
February | 4793.13 | 03-FEB-08:03 | 1012.48 | 7926.65 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 471.20 |
March | 4506.50 | 02-MAR-08:03 | 1181.23 | 9247.76 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 499.24 |
April | 14760.07 | 20-APR-07:03 | 674.99 | 5284.43 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.58 |
May | 22988.20 | 15-MAY-07:02 | 1012.48 | 7926.65 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.55 |
June | 23404.08 | 14-JUN-07:01 | 1181.23 | 9247.76 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.25 |
July | 20848.45 | 11-JUL-07:01 | 1349.97 | 10568.86 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.23 |
August | 23939.36 | 23-AUG-07:01 | 1181.23 | 9247.76 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.06 |
September | 25880.68 | 11-SEP-07:02 | 1012.48 | 7926.65 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.17 |
October | 24091.87 | 06-OCT-07:02 | 843.73 | 6605.54 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.34 |
November | 15126.33 | 10-NOV-08:62 | 674.99 | 5284.43 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.91 |
December | 5138.97 | 27-DEC-08:03 | 1012.48 | 7926.65 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 550.27 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4506.50 | 674.99 | 5284.43 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.23 | |
Maximum of Months | 25880.68 | 1349.97 | 10568.86 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 578.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5117.98 | 27-JAN-08:03 | 1012.48 | 7926.65 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 579.92 |
February | 4816.75 | 03-FEB-08:03 | 1012.48 | 7926.65 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 470.46 |
March | 4571.89 | 02-MAR-08:03 | 1181.23 | 9247.76 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 500.14 |
April | 14536.90 | 20-APR-07:03 | 674.99 | 5284.43 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.53 |
May | 22916.51 | 15-MAY-07:02 | 1012.48 | 7926.65 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.85 |
June | 23327.27 | 14-JUN-07:01 | 1181.23 | 9247.76 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.30 |
July | 20789.09 | 11-JUL-07:01 | 1349.97 | 10568.86 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.66 |
August | 23858.77 | 23-AUG-07:01 | 1181.23 | 9247.76 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.19 |
September | 25807.69 | 11-SEP-07:02 | 1012.48 | 7926.65 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.93 |
October | 24750.99 | 06-OCT-07:02 | 843.73 | 6605.54 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.50 |
November | 14717.21 | 10-NOV-08:62 | 674.99 | 5284.43 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.78 |
December | 5079.33 | 27-DEC-08:03 | 1012.48 | 7926.65 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 544.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4571.89 | 674.99 | 5284.43 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.66 | |
Maximum of Months | 25807.69 | 1349.97 | 10568.86 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 579.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5124.52 | 27-JAN-08:03 | 1012.48 | 7926.65 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 577.94 |
February | 4779.44 | 03-FEB-08:03 | 1012.48 | 7926.65 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 466.39 |
March | 4526.22 | 02-MAR-08:03 | 1181.23 | 9247.76 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 495.04 |
April | 12767.91 | 20-APR-07:03 | 674.99 | 5284.43 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.17 |
May | 22888.51 | 15-MAY-07:02 | 1012.48 | 7926.65 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.68 |
June | 23278.70 | 14-JUN-07:01 | 1181.23 | 9247.76 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.00 |
July | 20750.61 | 11-JUL-07:01 | 1349.97 | 10568.86 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.63 |
August | 23815.95 | 23-AUG-07:01 | 1181.23 | 9247.76 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.88 |
September | 25811.55 | 11-SEP-07:02 | 1012.48 | 7926.65 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.33 |
October | 23386.86 | 06-OCT-07:02 | 843.73 | 6605.54 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.18 |
November | 13189.26 | 10-NOV-08:62 | 674.99 | 5284.43 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.33 |
December | 4689.79 | 28-DEC-08:04 | 843.73 | 6605.54 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 452.35 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4526.22 | 674.99 | 5284.43 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.63 | |
Maximum of Months | 25811.55 | 1349.97 | 10568.86 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 577.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9042.24 | 27-JAN-09:04 | 5940.06 | 12094.56 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 948.80 |
February | 7907.24 | 02-FEB-09:04 | 5940.06 | 12094.56 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 794.52 |
March | 8407.31 | 02-MAR-09:04 | 5940.06 | 12094.56 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 774.39 |
April | 18277.93 | 29-APR-08:62 | 2970.03 | 6047.28 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.14 |
May | 38792.83 | 15-MAY-08:62 | 4455.04 | 9070.92 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.55 |
June | 38846.05 | 12-JUN-08:62 | 4455.04 | 9070.92 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.43 |
July | 36541.90 | 06-JUL-08:61 | 5197.55 | 10582.74 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 31.10 | 0.00 |
August | 39240.03 | 28-AUG-08:61 | 5940.06 | 12094.56 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.20 |
September | 42250.87 | 11-SEP-08:62 | 4455.04 | 9070.92 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.23 |
October | 39604.53 | 01-OCT-09:02 | 3712.53 | 7559.10 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.76 |
November | 31368.46 | 10-NOV-09:02 | 3712.53 | 7559.10 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.35 |
December | 9220.28 | 27-DEC-09:04 | 5940.06 | 12094.56 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 811.58 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7907.24 | 2970.03 | 6047.28 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 42250.87 | 5940.06 | 12094.56 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 31.10 | 948.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4491.38 | 27-JAN-09:04 | 2969.94 | 6208.12 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 521.22 |
February | 3936.97 | 02-FEB-09:04 | 2969.94 | 6208.12 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 438.85 |
March | 4191.39 | 02-MAR-09:04 | 2969.94 | 6208.12 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 431.03 |
April | 8157.95 | 29-APR-08:62 | 1484.97 | 3104.06 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.09 |
May | 19909.68 | 15-MAY-08:62 | 2227.46 | 4656.09 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.55 |
June | 19932.16 | 12-JUN-08:62 | 2227.46 | 4656.09 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.16 |
July | 18833.79 | 06-JUL-08:61 | 2598.70 | 5432.10 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 19.82 | 0.00 |
August | 20232.57 | 28-AUG-08:61 | 2969.94 | 6208.12 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.73 |
September | 21710.33 | 11-SEP-08:62 | 2227.46 | 4656.09 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.68 |
October | 20318.08 | 01-OCT-09:02 | 1856.21 | 3880.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.93 |
November | 14725.34 | 10-NOV-09:02 | 1856.21 | 3880.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.58 |
December | 4591.89 | 27-DEC-09:04 | 2969.94 | 6208.12 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 452.15 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3936.97 | 1484.97 | 3104.06 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21710.33 | 2969.94 | 6208.12 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 19.82 | 521.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4530.37 | 27-JAN-09:04 | 2969.94 | 6208.12 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 522.23 |
February | 3979.11 | 02-FEB-09:04 | 2969.94 | 6208.12 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 439.89 |
March | 4240.26 | 02-MAR-09:04 | 2969.94 | 6208.12 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 432.15 |
April | 7602.24 | 30-APR-09:03 | 1113.73 | 2328.04 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.33 |
May | 19802.44 | 15-MAY-08:62 | 2227.46 | 4656.09 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.80 |
June | 19828.44 | 12-JUN-08:62 | 2227.46 | 4656.09 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.61 |
July | 18730.25 | 06-JUL-08:61 | 2598.70 | 5432.10 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 20.31 | 0.00 |
August | 20130.26 | 28-AUG-08:61 | 2969.94 | 6208.12 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.41 |
September | 21607.47 | 11-SEP-08:62 | 2227.46 | 4656.09 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.23 |
October | 20065.18 | 01-OCT-09:02 | 1856.21 | 3880.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.52 |
November | 13938.08 | 10-NOV-09:02 | 1856.21 | 3880.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.44 |
December | 4594.70 | 27-DEC-09:04 | 2969.94 | 6208.12 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 451.56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3979.11 | 1113.73 | 2328.04 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21607.47 | 2969.94 | 6208.12 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 20.31 | 522.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4639.52 | 27-JAN-09:04 | 2969.94 | 6208.12 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 525.11 |
February | 4102.56 | 02-FEB-09:04 | 2969.94 | 6208.12 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 442.99 |
March | 4319.30 | 02-MAR-09:04 | 2969.94 | 6208.12 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 432.70 |
April | 6283.34 | 30-APR-09:03 | 1113.73 | 2328.04 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.10 |
May | 19757.99 | 15-MAY-08:62 | 2227.46 | 4656.09 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.59 |
June | 19789.68 | 12-JUN-08:62 | 2227.46 | 4656.09 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.83 |
July | 18746.32 | 06-JUL-08:61 | 2598.70 | 5432.10 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 21.02 | 0.00 |
August | 20173.29 | 28-AUG-08:61 | 2969.94 | 6208.12 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.27 |
September | 21629.06 | 11-SEP-08:62 | 2227.46 | 4656.09 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.52 |
October | 19768.34 | 02-OCT-08:61 | 2598.70 | 5432.10 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.67 |
November | 11788.64 | 10-NOV-09:02 | 1856.21 | 3880.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.10 |
December | 4571.09 | 27-DEC-09:04 | 2969.94 | 6208.12 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 449.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4102.56 | 1113.73 | 2328.04 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21629.06 | 2969.94 | 6208.12 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 21.02 | 525.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4634.17 | 27-JAN-09:04 | 2969.94 | 6208.12 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 628.59 |
February | 4088.62 | 02-FEB-09:04 | 2969.94 | 6208.12 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 502.72 |
March | 4215.02 | 02-MAR-09:04 | 2969.94 | 6208.12 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 446.20 |
April | 7531.00 | 30-APR-09:03 | 1113.73 | 2328.04 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.63 |
May | 21454.23 | 15-MAY-08:62 | 2227.46 | 4656.09 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.89 |
June | 21314.38 | 12-JUN-08:62 | 2227.46 | 4656.09 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.01 |
July | 20349.01 | 03-JUL-08:61 | 2969.94 | 6208.12 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 74.81 | 0.00 |
August | 22130.56 | 28-AUG-08:61 | 2969.94 | 6208.12 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.85 |
September | 23685.09 | 11-SEP-08:62 | 2227.46 | 4656.09 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.23 |
October | 21620.11 | 02-OCT-08:61 | 2598.70 | 5432.10 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.09 |
November | 8675.23 | 10-NOV-09:02 | 1856.21 | 3880.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.94 |
December | 4507.02 | 27-DEC-09:04 | 2969.94 | 6208.12 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 456.58 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4088.62 | 1113.73 | 2328.04 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23685.09 | 2969.94 | 6208.12 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 74.81 | 628.59 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.649014E+11 | 54792.68 | 09-JAN-18:40 | 0.166515E+11 | 126251.35 | 27-JAN-09:09 |
February | 0.586721E+11 | 51665.88 | 20-FEB-15:30 | 0.879136E+10 | 116707.96 | 03-FEB-09:09 |
March | 0.658281E+11 | 55332.23 | 14-MAR-15:39 | 0.453622E+10 | 124563.91 | 02-MAR-09:09 |
April | 0.720467E+11 | 71208.10 | 21-APR-12:50 | 65447725.11 | 14583.39 | 11-APR-08:30 |
May | 0.852440E+11 | 75822.82 | 21-MAY-13:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.940754E+11 | 87832.64 | 15-JUN-14:39 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.985408E+11 | 85883.98 | 03-JUL-16:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.959694E+11 | 85595.57 | 07-AUG-15:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.886681E+11 | 76734.06 | 15-SEP-12:30 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.764846E+11 | 77291.70 | 03-OCT-14:20 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.635317E+11 | 59641.75 | 09-NOV-17:10 | 0.414432E+10 | 86131.13 | 28-NOV-09:09 |
December | 0.649458E+11 | 51268.54 | 27-DEC-19:10 | 0.223323E+11 | 132964.28 | 27-DEC-09:09 |
Annual Sum or Average | 0.928908E+12 | 0.565211E+11 | ||||
Minimum of Months | 0.586721E+11 | 51268.54 | 0.00 | 0.00 | ||
Maximum of Months | 0.985408E+11 | 87832.64 | 0.223323E+11 | 132964.28 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.322876E+11 | 0.709859E+10 | 0.108804E+11 | 0.00 | 0.950759E+10 | 0.00 | 0.00 | 4264570.17 | 0.00 | 0.00 | 0.00 | 0.512302E+10 | 0.00 |
February | 0.292229E+11 | 0.601318E+10 | 0.985143E+10 | 0.00 | 0.853220E+10 | 0.00 | 0.00 | 0.420808E+09 | 0.00 | 0.00 | 0.00 | 0.463160E+10 | 0.00 |
March | 0.327448E+11 | 0.609033E+10 | 0.110560E+11 | 0.00 | 0.951379E+10 | 0.00 | 0.00 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.510105E+10 | 0.00 |
April | 0.313156E+11 | 0.532328E+10 | 0.105544E+11 | 0.00 | 0.898130E+10 | 0.00 | 0.00 | 0.110651E+11 | 0.00 | 0.00 | 0.00 | 0.480707E+10 | 0.00 |
May | 0.325099E+11 | 0.501075E+10 | 0.109629E+11 | 0.00 | 0.932625E+10 | 0.00 | 0.00 | 0.225699E+11 | 0.00 | 0.00 | 0.00 | 0.486422E+10 | 0.00 |
June | 0.316492E+11 | 0.460356E+10 | 0.106855E+11 | 0.00 | 0.922590E+10 | 0.00 | 0.00 | 0.332809E+11 | 0.00 | 0.00 | 0.00 | 0.463047E+10 | 0.00 |
July | 0.321889E+11 | 0.486486E+10 | 0.108424E+11 | 0.00 | 0.935977E+10 | 0.00 | 0.00 | 0.365855E+11 | 0.00 | 0.00 | 0.00 | 0.469940E+10 | 0.00 |
August | 0.327323E+11 | 0.528308E+10 | 0.110491E+11 | 0.00 | 0.948113E+10 | 0.00 | 0.00 | 0.326887E+11 | 0.00 | 0.00 | 0.00 | 0.473507E+10 | 0.00 |
September | 0.313281E+11 | 0.564099E+10 | 0.105613E+11 | 0.00 | 0.900822E+10 | 0.00 | 0.00 | 0.275143E+11 | 0.00 | 0.00 | 0.00 | 0.461520E+10 | 0.00 |
October | 0.322876E+11 | 0.642425E+10 | 0.108804E+11 | 0.00 | 0.930284E+10 | 0.00 | 0.00 | 0.127393E+11 | 0.00 | 0.00 | 0.00 | 0.485021E+10 | 0.00 |
November | 0.312780E+11 | 0.671409E+10 | 0.105443E+11 | 0.00 | 0.907493E+10 | 0.00 | 0.00 | 0.110963E+10 | 0.00 | 0.00 | 0.00 | 0.481078E+10 | 0.00 |
December | 0.322014E+11 | 0.722178E+10 | 0.108529E+11 | 0.00 | 0.959557E+10 | 0.00 | 0.00 | 1358745.42 | 0.00 | 0.00 | 0.00 | 0.507272E+10 | 0.00 |
Annual Sum or Average | 0.381746E+12 | 0.702887E+11 | 0.128721E+12 | 0.00 | 0.110910E+12 | 0.00 | 0.00 | 0.179302E+12 | 0.00 | 0.00 | 0.00 | 0.579408E+11 | 0.00 |
Minimum of Months | 0.292229E+11 | 0.460356E+10 | 0.985143E+10 | 0.00 | 0.853220E+10 | 0.00 | 0.00 | 1358745.42 | 0.00 | 0.00 | 0.00 | 0.461520E+10 | 0.00 |
Maximum of Months | 0.327448E+11 | 0.722178E+10 | 0.110560E+11 | 0.00 | 0.959557E+10 | 0.00 | 0.00 | 0.365855E+11 | 0.00 | 0.00 | 0.00 | 0.512302E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.166515E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.879136E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.453622E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 65447725.11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.414432E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.223323E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.565211E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.223323E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 23650.28 | 01-JAN-11:09 | 5403.30 | 01-JAN-06:10 | 8089.53 | 01-JAN-11:09 | 0.00 | 9015.04 | 27-JAN-09:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 23650.28 | 01-FEB-10:09 | 5403.30 | 01-FEB-06:10 | 8089.53 | 01-FEB-10:09 | 0.00 | 8810.49 | 03-FEB-09:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 23650.28 | 01-MAR-10:09 | 5403.30 | 01-MAR-06:10 | 8089.53 | 01-MAR-10:09 | 0.00 | 8979.50 | 02-MAR-09:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 23650.28 | 01-APR-09:09 | 5403.30 | 01-APR-05:10 | 8089.53 | 01-APR-09:09 | 0.00 | 6631.09 | 11-APR-08:30 | 0.00 | 0.00 | 01-APR-00:10 |
May | 23650.28 | 01-MAY-09:09 | 5403.30 | 01-MAY-05:10 | 8089.53 | 01-MAY-09:09 | 0.00 | 8018.60 | 31-MAY-08:09 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 23650.28 | 01-JUN-09:09 | 5403.30 | 01-JUN-19:10 | 8089.53 | 01-JUN-09:09 | 0.00 | 8304.49 | 16-JUN-08:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 23650.28 | 01-JUL-09:09 | 5403.30 | 01-JUL-19:19 | 8089.53 | 01-JUL-09:09 | 0.00 | 8523.20 | 17-JUL-08:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 23650.28 | 01-AUG-09:09 | 5403.30 | 01-AUG-05:10 | 8089.53 | 01-AUG-09:09 | 0.00 | 8483.36 | 05-AUG-08:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 23650.28 | 01-SEP-09:09 | 5403.30 | 01-SEP-05:10 | 8089.53 | 01-SEP-09:09 | 0.00 | 8304.49 | 22-SEP-08:09 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 23650.28 | 01-OCT-10:09 | 5403.30 | 01-OCT-05:10 | 8089.53 | 01-OCT-10:09 | 0.00 | 8148.98 | 02-OCT-08:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 23650.28 | 01-NOV-09:09 | 5403.30 | 01-NOV-05:10 | 8089.53 | 01-NOV-09:09 | 0.00 | 8159.96 | 28-NOV-09:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 23650.28 | 01-DEC-10:09 | 5403.30 | 01-DEC-06:10 | 8089.53 | 01-DEC-10:09 | 0.00 | 9157.93 | 27-DEC-09:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 23650.28 | 5403.30 | 8089.53 | 0.00 | 6631.09 | 0.00 | 0.00 | |||||
Maximum of Months | 23650.28 | 5403.30 | 8089.53 | 0.00 | 9157.93 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 604.88 | 03-JAN-14:00 | 0.00 | 0.00 | 0.00 | 11249.83 | 09-JAN-18:40 | 0.00 |
February | 8178.37 | 20-FEB-15:30 | 0.00 | 0.00 | 0.00 | 7584.29 | 08-FEB-13:30 | 0.00 |
March | 11696.45 | 22-MAR-12:00 | 0.00 | 0.00 | 0.00 | 7579.34 | 14-MAR-12:20 | 0.00 |
April | 27071.85 | 21-APR-14:30 | 0.00 | 0.00 | 0.00 | 9688.66 | 07-APR-13:50 | 0.00 |
May | 32545.55 | 19-MAY-16:10 | 0.00 | 0.00 | 0.00 | 7547.54 | 10-MAY-11:00 | 0.00 |
June | 43107.59 | 15-JUN-14:00 | 0.00 | 0.00 | 0.00 | 7552.07 | 19-JUN-13:50 | 0.00 |
July | 42952.19 | 03-JUL-16:10 | 0.00 | 0.00 | 0.00 | 7550.15 | 17-JUL-12:09 | 0.00 |
August | 41885.78 | 07-AUG-16:10 | 0.00 | 0.00 | 0.00 | 7897.27 | 04-AUG-16:30 | 0.00 |
September | 34082.16 | 15-SEP-12:00 | 0.00 | 0.00 | 0.00 | 7557.23 | 27-SEP-12:09 | 0.00 |
October | 34270.62 | 03-OCT-13:00 | 0.00 | 0.00 | 0.00 | 7562.78 | 17-OCT-12:30 | 0.00 |
November | 14055.39 | 09-NOV-13:00 | 0.00 | 0.00 | 0.00 | 7543.37 | 16-NOV-19:49 | 0.00 |
December | 350.30 | 10-DEC-18:10 | 0.00 | 0.00 | 0.00 | 7581.36 | 15-DEC-13:39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 350.30 | 0.00 | 0.00 | 0.00 | 7543.37 | 0.00 | ||
Maximum of Months | 43107.59 | 0.00 | 0.00 | 0.00 | 11249.83 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 54792.68 | 09-JAN-18:40 | 23650.28 | 8089.53 | 5403.30 | 0.00 | 6399.73 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 51665.88 | 20-FEB-15:30 | 23650.28 | 8089.53 | 0.00 | 0.00 | 6321.30 | 0.00 | 0.00 | 8178.37 | 0.00 |
March | 55332.23 | 14-MAR-15:39 | 23650.28 | 8089.53 | 0.00 | 0.00 | 6321.30 | 0.00 | 0.00 | 9723.11 | 0.00 |
April | 71208.10 | 21-APR-12:50 | 23650.28 | 8089.53 | 0.00 | 0.00 | 6321.30 | 0.00 | 0.00 | 25834.23 | 0.00 |
May | 75822.82 | 21-MAY-13:00 | 23650.28 | 8089.53 | 0.00 | 0.00 | 6321.30 | 0.00 | 0.00 | 32342.81 | 0.00 |
June | 87832.64 | 15-JUN-14:39 | 23650.28 | 8089.53 | 0.00 | 0.00 | 7965.03 | 0.00 | 0.00 | 42694.43 | 0.00 |
July | 85883.98 | 03-JUL-16:10 | 23650.28 | 8089.53 | 0.00 | 0.00 | 7870.17 | 0.00 | 0.00 | 42952.19 | 0.00 |
August | 85595.57 | 07-AUG-15:00 | 23650.28 | 8089.53 | 0.00 | 0.00 | 7515.97 | 0.00 | 0.00 | 40916.03 | 0.00 |
September | 76734.06 | 15-SEP-12:30 | 23650.28 | 8089.53 | 0.00 | 0.00 | 6350.62 | 0.00 | 0.00 | 33579.04 | 0.00 |
October | 77291.70 | 03-OCT-14:20 | 23650.28 | 8089.53 | 0.00 | 0.00 | 6337.71 | 0.00 | 0.00 | 33781.06 | 0.00 |
November | 59641.75 | 09-NOV-17:10 | 23650.28 | 8089.53 | 5403.30 | 0.00 | 6321.30 | 0.00 | 0.00 | 10740.72 | 0.00 |
December | 51268.54 | 27-DEC-19:10 | 23650.28 | 8089.53 | 5403.30 | 0.00 | 7023.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 51268.54 | 23650.28 | 8089.53 | 0.00 | 0.00 | 6321.30 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 87832.64 | 23650.28 | 8089.53 | 5403.30 | 0.00 | 7965.03 | 0.00 | 0.00 | 42952.19 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 126251.35 | 27-JAN-09:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 116707.96 | 03-FEB-09:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 124563.91 | 02-MAR-09:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 14583.39 | 11-APR-08:30 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 86131.13 | 28-NOV-09:09 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 132964.28 | 27-DEC-09:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 132964.28 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.50 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
Annual Sum or Average | 0.67 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.55 | 59.67 | 21.46 | 59.67 | 21.38 |
February | 448.00 | 22.14 | 44.33 | 22.01 | 44.33 | 21.90 |
March | 497.00 | 22.78 | 26.83 | 22.68 | 26.83 | 22.59 |
April | 272.33 | 23.59 | 12.00 | 23.60 | 0.00 | 23.60 |
May | 71.83 | 23.84 | 183.17 | 23.90 | 0.00 | 23.90 |
June | 3.83 | 23.87 | 346.00 | 23.97 | 0.00 | 23.97 |
July | 67.00 | 24.03 | 495.00 | 23.97 | 67.00 | 23.97 |
August | 31.00 | 24.16 | 486.50 | 23.98 | 31.00 | 23.99 |
September | 38.00 | 23.96 | 410.17 | 23.93 | 33.83 | 23.94 |
October | 66.67 | 23.62 | 244.00 | 23.86 | 13.33 | 23.87 |
November | 383.00 | 22.73 | 26.67 | 22.75 | 7.33 | 22.71 |
December | 496.00 | 21.42 | 70.83 | 21.32 | 70.83 | 21.25 |
Annual Sum or Average | 2870.67 | 22.41 | 2405.17 | 22.98 | 354.17 | 22.93 |
Minimum of Months | 3.83 | 21.42 | 12.00 | 21.32 | 0.00 | 21.25 |
Maximum of Months | 497.00 | 24.16 | 495.00 | 23.98 | 70.83 | 23.99 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 486.83 | 22.41 | 6.50 | 22.39 | 6.50 | 22.38 |
February | 445.17 | 22.86 | 4.67 | 22.84 | 4.67 | 22.82 |
March | 484.67 | 23.32 | 3.17 | 23.30 | 3.17 | 23.29 |
April | 229.00 | 23.67 | 14.50 | 23.68 | 0.00 | 23.68 |
May | 60.67 | 23.67 | 169.17 | 23.88 | 0.00 | 23.88 |
June | 2.00 | 23.26 | 332.17 | 23.99 | 0.00 | 23.99 |
July | 35.67 | 23.97 | 495.00 | 23.96 | 35.67 | 23.96 |
August | 14.33 | 23.87 | 480.50 | 23.96 | 13.50 | 23.96 |
September | 26.00 | 23.55 | 395.33 | 23.90 | 16.67 | 23.90 |
October | 52.00 | 23.62 | 234.33 | 23.87 | 6.00 | 23.87 |
November | 338.17 | 23.22 | 22.67 | 23.26 | 0.83 | 23.25 |
December | 496.00 | 22.26 | 10.00 | 22.23 | 10.00 | 22.20 |
Annual Sum or Average | 2670.50 | 22.92 | 2168.00 | 23.37 | 97.00 | 23.37 |
Minimum of Months | 2.00 | 22.26 | 3.17 | 22.23 | 0.00 | 22.20 |
Maximum of Months | 496.00 | 23.97 | 495.00 | 23.99 | 35.67 | 23.99 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.83 | 19.00 | 21.80 | 19.00 | 21.77 |
February | 334.50 | 22.39 | 12.83 | 22.35 | 12.83 | 22.30 |
March | 375.33 | 23.03 | 5.33 | 23.01 | 5.33 | 22.98 |
April | 155.83 | 23.60 | 25.67 | 23.79 | 0.00 | 23.79 |
May | 34.50 | 23.89 | 144.83 | 24.24 | 0.83 | 24.26 |
June | 2.33 | 28.52 | 267.17 | 24.25 | 2.33 | 24.29 |
July | 58.17 | 24.71 | 368.67 | 24.21 | 58.17 | 24.27 |
August | 20.33 | 24.98 | 375.00 | 24.15 | 20.33 | 24.19 |
September | 17.17 | 24.33 | 320.83 | 24.10 | 13.67 | 24.12 |
October | 37.00 | 23.51 | 193.83 | 23.97 | 6.33 | 23.97 |
November | 260.00 | 22.89 | 19.67 | 22.94 | 2.00 | 22.93 |
December | 369.00 | 21.69 | 25.17 | 21.65 | 25.17 | 21.62 |
Annual Sum or Average | 2035.17 | 22.60 | 1778.00 | 23.27 | 166.00 | 23.27 |
Minimum of Months | 2.33 | 21.69 | 5.33 | 21.65 | 0.00 | 21.62 |
Maximum of Months | 375.33 | 28.52 | 375.00 | 24.25 | 58.17 | 24.29 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.74 | 24.17 | 21.70 | 24.17 | 21.67 |
February | 336.00 | 22.32 | 15.00 | 22.27 | 15.00 | 22.22 |
March | 376.83 | 22.98 | 6.67 | 22.95 | 6.67 | 22.92 |
April | 160.67 | 23.60 | 24.67 | 23.78 | 0.00 | 23.78 |
May | 34.67 | 23.90 | 144.83 | 24.24 | 0.83 | 24.26 |
June | 2.33 | 28.55 | 269.17 | 24.25 | 2.33 | 24.29 |
July | 58.00 | 24.75 | 368.67 | 24.22 | 58.00 | 24.28 |
August | 19.83 | 25.04 | 375.50 | 24.15 | 19.83 | 24.20 |
September | 16.83 | 24.35 | 321.83 | 24.10 | 13.50 | 24.12 |
October | 37.17 | 23.50 | 192.67 | 23.97 | 6.17 | 23.97 |
November | 265.33 | 22.85 | 18.67 | 22.90 | 2.50 | 22.88 |
December | 369.00 | 21.61 | 31.17 | 21.57 | 31.17 | 21.54 |
Annual Sum or Average | 2047.67 | 22.55 | 1793.00 | 23.23 | 180.17 | 23.23 |
Minimum of Months | 2.33 | 21.61 | 6.67 | 21.57 | 0.00 | 21.54 |
Maximum of Months | 376.83 | 28.55 | 375.50 | 24.25 | 58.00 | 24.29 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.64 | 32.33 | 21.59 | 32.33 | 21.56 |
February | 336.00 | 22.22 | 21.00 | 22.16 | 21.00 | 22.10 |
March | 379.00 | 22.90 | 11.00 | 22.85 | 11.00 | 22.80 |
April | 177.67 | 23.58 | 18.67 | 23.73 | 0.00 | 23.73 |
May | 39.33 | 23.88 | 140.00 | 24.23 | 0.83 | 24.25 |
June | 2.17 | 28.53 | 264.83 | 24.25 | 2.17 | 24.28 |
July | 58.83 | 24.64 | 368.50 | 24.20 | 58.83 | 24.26 |
August | 20.33 | 24.91 | 374.50 | 24.14 | 20.33 | 24.18 |
September | 18.17 | 24.30 | 319.17 | 24.10 | 14.17 | 24.12 |
October | 42.33 | 23.48 | 187.50 | 23.94 | 6.50 | 23.95 |
November | 276.33 | 22.80 | 16.17 | 22.83 | 3.67 | 22.81 |
December | 369.00 | 21.51 | 41.83 | 21.47 | 41.83 | 21.44 |
Annual Sum or Average | 2090.17 | 22.48 | 1795.50 | 23.17 | 212.67 | 23.15 |
Minimum of Months | 2.17 | 21.51 | 11.00 | 21.47 | 0.00 | 21.44 |
Maximum of Months | 379.00 | 28.53 | 374.50 | 24.25 | 58.83 | 24.28 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.49 | 45.17 | 21.45 | 45.17 | 21.41 |
February | 308.00 | 22.10 | 31.83 | 22.01 | 31.83 | 21.93 |
March | 348.00 | 22.80 | 17.00 | 22.72 | 17.00 | 22.65 |
April | 200.33 | 23.62 | 9.67 | 23.68 | 0.00 | 23.68 |
May | 47.67 | 23.88 | 114.50 | 24.04 | 0.67 | 24.05 |
June | 1.67 | 28.44 | 228.33 | 24.04 | 1.67 | 24.07 |
July | 70.50 | 24.25 | 336.83 | 24.04 | 70.50 | 24.07 |
August | 15.50 | 24.66 | 340.17 | 24.00 | 15.50 | 24.03 |
September | 15.00 | 24.34 | 285.50 | 23.99 | 11.83 | 24.01 |
October | 53.17 | 23.55 | 163.17 | 23.87 | 8.67 | 23.87 |
November | 280.67 | 22.76 | 10.83 | 22.75 | 5.50 | 22.72 |
December | 338.00 | 21.39 | 67.17 | 21.35 | 67.17 | 21.31 |
Annual Sum or Average | 2018.50 | 22.44 | 1650.17 | 23.01 | 275.50 | 22.97 |
Minimum of Months | 1.67 | 21.39 | 9.67 | 21.35 | 0.00 | 21.31 |
Maximum of Months | 348.00 | 28.44 | 340.17 | 24.04 | 70.50 | 24.07 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.47 | 51.67 | 21.42 | 51.67 | 21.38 |
February | 308.00 | 22.07 | 37.00 | 21.97 | 37.00 | 21.89 |
March | 348.00 | 22.76 | 19.67 | 22.67 | 19.67 | 22.59 |
April | 221.33 | 23.64 | 7.17 | 23.68 | 0.00 | 23.68 |
May | 63.17 | 23.86 | 102.83 | 24.02 | 0.33 | 24.03 |
June | 2.17 | 26.36 | 210.67 | 24.03 | 1.17 | 24.06 |
July | 69.83 | 24.18 | 335.83 | 24.03 | 69.83 | 24.05 |
August | 15.17 | 24.57 | 337.50 | 24.00 | 15.17 | 24.02 |
September | 14.83 | 24.13 | 274.17 | 23.98 | 11.33 | 23.99 |
October | 60.83 | 23.59 | 153.33 | 23.87 | 8.67 | 23.87 |
November | 286.83 | 22.77 | 6.00 | 22.74 | 6.00 | 22.71 |
December | 338.00 | 21.37 | 74.83 | 21.32 | 74.83 | 21.29 |
Annual Sum or Average | 2068.17 | 22.45 | 1610.67 | 22.98 | 295.67 | 22.92 |
Minimum of Months | 2.17 | 21.37 | 6.00 | 21.32 | 0.00 | 21.29 |
Maximum of Months | 348.00 | 26.36 | 337.50 | 24.03 | 74.83 | 24.06 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.43 | 56.67 | 21.39 | 56.67 | 21.35 |
February | 308.00 | 22.04 | 41.33 | 21.93 | 41.33 | 21.84 |
March | 348.00 | 22.72 | 23.83 | 22.61 | 23.83 | 22.52 |
April | 227.50 | 23.63 | 7.00 | 23.67 | 0.00 | 23.67 |
May | 66.17 | 23.85 | 100.83 | 24.01 | 0.17 | 24.02 |
June | 2.33 | 26.17 | 207.17 | 24.04 | 1.17 | 24.06 |
July | 70.50 | 24.18 | 335.83 | 24.03 | 70.50 | 24.05 |
August | 15.33 | 24.56 | 337.00 | 24.00 | 15.33 | 24.02 |
September | 15.67 | 24.11 | 273.00 | 23.98 | 11.50 | 23.99 |
October | 65.33 | 23.59 | 150.83 | 23.86 | 8.83 | 23.86 |
November | 288.00 | 22.73 | 6.67 | 22.70 | 6.67 | 22.66 |
December | 338.00 | 21.35 | 80.17 | 21.30 | 80.17 | 21.27 |
Annual Sum or Average | 2084.83 | 22.43 | 1620.33 | 22.95 | 316.17 | 22.89 |
Minimum of Months | 2.33 | 21.35 | 6.67 | 21.30 | 0.00 | 21.27 |
Maximum of Months | 348.00 | 26.17 | 337.00 | 24.04 | 80.17 | 24.06 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.38 | 72.50 | 21.33 | 72.50 | 21.30 |
February | 308.00 | 21.95 | 55.17 | 21.82 | 55.17 | 21.73 |
March | 348.00 | 22.61 | 35.00 | 22.47 | 35.00 | 22.36 |
April | 234.33 | 23.58 | 7.33 | 23.62 | 0.50 | 23.61 |
May | 70.33 | 23.84 | 100.17 | 24.00 | 0.17 | 24.01 |
June | 2.33 | 26.17 | 209.67 | 24.03 | 1.17 | 24.06 |
July | 70.83 | 24.18 | 335.83 | 24.03 | 70.83 | 24.05 |
August | 16.17 | 24.52 | 337.67 | 24.00 | 16.17 | 24.02 |
September | 16.17 | 24.15 | 273.33 | 23.98 | 11.83 | 24.00 |
October | 71.17 | 23.55 | 148.00 | 23.83 | 9.00 | 23.84 |
November | 290.83 | 22.65 | 8.17 | 22.61 | 8.17 | 22.57 |
December | 338.00 | 21.31 | 97.67 | 21.26 | 97.67 | 21.23 |
Annual Sum or Average | 2106.17 | 22.38 | 1680.50 | 22.89 | 378.17 | 22.81 |
Minimum of Months | 2.33 | 21.31 | 7.33 | 21.26 | 0.17 | 21.23 |
Maximum of Months | 348.00 | 26.17 | 337.67 | 24.03 | 97.67 | 24.06 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.31 | 130.67 | 21.25 | 130.67 | 21.22 |
February | 308.00 | 21.84 | 99.50 | 21.66 | 99.50 | 21.55 |
March | 348.00 | 22.46 | 61.67 | 22.26 | 61.67 | 22.11 |
April | 240.17 | 23.52 | 10.83 | 23.53 | 3.17 | 23.50 |
May | 65.83 | 23.85 | 112.83 | 24.01 | 0.67 | 24.02 |
June | 2.50 | 27.54 | 242.17 | 24.04 | 2.17 | 24.07 |
July | 62.83 | 24.36 | 337.67 | 24.06 | 62.83 | 24.10 |
August | 21.50 | 24.70 | 344.33 | 24.02 | 21.50 | 24.06 |
September | 16.50 | 24.57 | 291.17 | 24.01 | 13.00 | 24.04 |
October | 78.00 | 23.39 | 147.83 | 23.78 | 9.50 | 23.78 |
November | 293.83 | 22.55 | 22.50 | 22.45 | 22.50 | 22.36 |
December | 338.00 | 21.27 | 151.50 | 21.22 | 151.50 | 21.19 |
Annual Sum or Average | 2115.17 | 22.31 | 1952.67 | 22.79 | 578.67 | 22.66 |
Minimum of Months | 2.50 | 21.27 | 10.83 | 21.22 | 0.67 | 21.19 |
Maximum of Months | 348.00 | 27.54 | 344.33 | 24.06 | 151.50 | 24.10 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.55092 | 22.98991 | -0.3566 | 8.60472 |
February | 448.00000 | 22.13932 | 18.96125 | -0.2511 | 7.79565 |
March | 497.00000 | 22.78289 | 17.64313 | -0.1025 | 6.65626 |
April | 479.00000 | 23.71761 | 20.05041 | 0.19366 | 6.31036 |
May | 496.00000 | 23.90991 | 29.36551 | -0.5218 | 11.04634 |
June | 481.00000 | 23.95375 | 33.93998 | -0.4083 | 8.65075 |
July | 495.00000 | 23.96074 | 49.38711 | -0.2812 | 6.77773 |
August | 497.00000 | 23.96427 | 44.68616 | -0.3167 | 7.25604 |
September | 479.00000 | 23.93037 | 42.65504 | -0.3532 | 7.83452 |
October | 496.00000 | 23.86299 | 36.41773 | 0.38895 | 8.45639 |
November | 480.00000 | 22.96516 | 23.10395 | 0.02216 | 6.52637 |
December | 496.00000 | 21.42080 | 19.92484 | -0.4085 | 9.18529 |
Annual Sum or Average | 5840.00000 | 23.18323 | 30.01439 | -0.1999 | 7.93289 |
Minimum of Months | 448.00000 | 21.42080 | 17.64313 | -0.5218 | 6.31036 |
Maximum of Months | 497.00000 | 23.96427 | 49.38711 | 0.38895 | 11.04634 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 22.43510 | 24.34717 | -0.1456 | 6.50568 |
February | 448.00000 | 22.86233 | 19.24908 | -0.0734 | 6.17555 |
March | 497.00000 | 23.33206 | 17.63884 | 0.03848 | 5.91251 |
April | 479.00000 | 23.78068 | 20.62722 | 0.22602 | 6.33868 |
May | 496.00000 | 23.88634 | 30.15782 | -0.5211 | 10.96897 |
June | 481.00000 | 23.95107 | 34.18476 | -0.4207 | 8.87989 |
July | 495.00000 | 23.96242 | 47.94829 | -0.3100 | 7.15103 |
August | 497.00000 | 23.95213 | 44.06708 | -0.3442 | 7.65820 |
September | 479.00000 | 23.88729 | 41.77298 | -0.3907 | 8.45737 |
October | 496.00000 | 23.85309 | 36.11525 | 0.38441 | 8.31369 |
November | 480.00000 | 23.41717 | 23.18349 | 0.12844 | 6.27767 |
December | 496.00000 | 22.26125 | 21.49277 | -0.2073 | 6.82307 |
Annual Sum or Average | 5840.00000 | 23.46674 | 30.15317 | -0.1371 | 7.46543 |
Minimum of Months | 448.00000 | 22.26125 | 17.63884 | -0.5211 | 5.91251 |
Maximum of Months | 497.00000 | 23.96242 | 47.94829 | 0.38441 | 10.96897 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.83491 | 21.37597 | -0.2786 | 7.54296 |
February | 336.00000 | 22.40047 | 17.94643 | -0.1711 | 6.87431 |
March | 379.00000 | 23.04347 | 16.57168 | -0.0262 | 6.24610 |
April | 360.00000 | 23.87261 | 20.01849 | 0.23794 | 6.68515 |
May | 375.00000 | 24.05933 | 28.83854 | -0.4789 | 10.41703 |
June | 366.00000 | 24.12641 | 33.04783 | -0.3715 | 8.52386 |
July | 369.00000 | 24.13446 | 48.69056 | -0.2474 | 6.87253 |
August | 379.00000 | 24.10327 | 44.45206 | -0.2897 | 7.24151 |
September | 360.00000 | 24.06705 | 42.02211 | -0.3273 | 7.68656 |
October | 371.00000 | 23.94868 | 35.35236 | 0.40360 | 8.73718 |
November | 360.00000 | 23.16332 | 22.38874 | 0.07801 | 6.48374 |
December | 369.00000 | 21.68689 | 18.74476 | -0.3331 | 7.99790 |
Annual Sum or Average | 4395.00000 | 23.37623 | 29.21328 | -0.1512 | 7.61838 |
Minimum of Months | 336.00000 | 21.68689 | 16.57168 | -0.4789 | 6.24610 |
Maximum of Months | 379.00000 | 24.13446 | 48.69056 | 0.40360 | 10.41703 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.74376 | 21.48297 | -0.3082 | 7.83351 |
February | 336.00000 | 22.32300 | 18.05066 | -0.1961 | 7.06503 |
March | 379.00000 | 22.98927 | 16.64821 | -0.0450 | 6.30894 |
April | 360.00000 | 23.86488 | 20.02878 | 0.23414 | 6.66628 |
May | 375.00000 | 24.05954 | 28.82748 | -0.4777 | 10.39462 |
June | 366.00000 | 24.12725 | 33.03142 | -0.3685 | 8.47930 |
July | 369.00000 | 24.13537 | 48.62043 | -0.2445 | 6.84792 |
August | 379.00000 | 24.10406 | 44.39882 | -0.2870 | 7.21189 |
September | 360.00000 | 24.06765 | 41.96665 | -0.3252 | 7.65870 |
October | 371.00000 | 23.94615 | 35.35249 | 0.40247 | 8.72052 |
November | 360.00000 | 23.12184 | 22.45892 | 0.06363 | 6.49791 |
December | 369.00000 | 21.60757 | 18.82713 | -0.3595 | 8.31675 |
Annual Sum or Average | 4395.00000 | 23.34732 | 29.23307 | -0.1601 | 7.67536 |
Minimum of Months | 336.00000 | 21.60757 | 16.64821 | -0.4777 | 6.30894 |
Maximum of Months | 379.00000 | 24.13537 | 48.62043 | 0.40247 | 10.39462 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.63595 | 21.60663 | -0.3432 | 8.21607 |
February | 336.00000 | 22.22263 | 18.18096 | -0.2288 | 7.34714 |
March | 379.00000 | 22.89765 | 16.77600 | -0.0753 | 6.42786 |
April | 360.00000 | 23.83804 | 20.06753 | 0.22092 | 6.58406 |
May | 375.00000 | 24.05386 | 28.85951 | -0.4866 | 10.57370 |
June | 366.00000 | 24.12341 | 33.06762 | -0.3750 | 8.56419 |
July | 369.00000 | 24.13172 | 48.73272 | -0.2497 | 6.88289 |
August | 379.00000 | 24.10049 | 44.48735 | -0.2924 | 7.26458 |
September | 360.00000 | 24.06359 | 42.05961 | -0.3314 | 7.73714 |
October | 371.00000 | 23.93302 | 35.42725 | 0.39483 | 8.60559 |
November | 360.00000 | 23.05135 | 22.57880 | 0.04078 | 6.50350 |
December | 369.00000 | 21.51204 | 18.92281 | -0.3915 | 8.73142 |
Annual Sum or Average | 4395.00000 | 23.30379 | 29.32225 | -0.1771 | 7.79456 |
Minimum of Months | 336.00000 | 21.51204 | 16.77600 | -0.4866 | 6.42786 |
Maximum of Months | 379.00000 | 24.13172 | 48.73272 | 0.39483 | 10.57370 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.49392 | 23.12734 | -0.3983 | 8.91826 |
February | 308.00000 | 22.10422 | 19.56342 | -0.2798 | 7.80198 |
March | 348.00000 | 22.79910 | 18.14308 | -0.1203 | 6.52205 |
April | 330.00000 | 23.77614 | 21.56408 | 0.19659 | 6.31878 |
May | 344.00000 | 23.95047 | 30.49719 | -0.5225 | 11.18419 |
June | 336.00000 | 23.96815 | 34.53445 | -0.4168 | 8.97047 |
July | 338.00000 | 23.99719 | 50.02653 | -0.2864 | 7.05830 |
August | 348.00000 | 23.96971 | 45.59760 | -0.3297 | 7.56616 |
September | 330.00000 | 23.95901 | 42.97995 | -0.3633 | 8.09753 |
October | 340.00000 | 23.86852 | 36.52784 | 0.37517 | 8.25117 |
November | 330.00000 | 22.93159 | 24.13066 | 0.00017 | 6.47725 |
December | 338.00000 | 21.39188 | 20.49220 | -0.4426 | 9.50352 |
Annual Sum or Average | 4030.00000 | 23.19123 | 30.69048 | -0.2163 | 8.06390 |
Minimum of Months | 308.00000 | 21.39188 | 18.14308 | -0.5225 | 6.31878 |
Maximum of Months | 348.00000 | 23.99719 | 50.02653 | 0.37517 | 11.18419 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.46530 | 23.06407 | -0.4133 | 9.13409 |
February | 308.00000 | 22.07270 | 19.51375 | -0.2953 | 7.97254 |
March | 348.00000 | 22.76273 | 18.11830 | -0.1381 | 6.61846 |
April | 330.00000 | 23.76823 | 21.48078 | 0.18233 | 6.20838 |
May | 344.00000 | 23.94916 | 30.42314 | -0.5434 | 11.63373 |
June | 336.00000 | 23.96636 | 34.46741 | -0.4421 | 9.41391 |
July | 338.00000 | 23.99433 | 50.03356 | -0.3119 | 7.35788 |
August | 348.00000 | 23.96816 | 45.59609 | -0.3546 | 7.90252 |
September | 330.00000 | 23.95816 | 42.98525 | -0.3873 | 8.45502 |
October | 340.00000 | 23.86802 | 36.48409 | 0.36149 | 8.02975 |
November | 330.00000 | 22.91768 | 24.07058 | -0.0134 | 6.46639 |
December | 338.00000 | 21.37039 | 20.40859 | -0.4548 | 9.69989 |
Annual Sum or Average | 4030.00000 | 23.17893 | 30.64575 | -0.2349 | 8.25012 |
Minimum of Months | 308.00000 | 21.37039 | 18.11830 | -0.5434 | 6.20838 |
Maximum of Months | 348.00000 | 23.99433 | 50.03356 | 0.36149 | 11.63373 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.43475 | 23.10217 | -0.4257 | 9.31956 |
February | 308.00000 | 22.03628 | 19.56140 | -0.3088 | 8.12829 |
March | 348.00000 | 22.71689 | 18.19024 | -0.1537 | 6.72263 |
April | 330.00000 | 23.75418 | 21.50771 | 0.17526 | 6.18183 |
May | 344.00000 | 23.94805 | 30.43279 | -0.5473 | 11.72704 |
June | 336.00000 | 23.96618 | 34.47493 | -0.4451 | 9.46616 |
July | 338.00000 | 23.99385 | 50.07262 | -0.3144 | 7.38771 |
August | 348.00000 | 23.96767 | 45.61880 | -0.3570 | 7.93770 |
September | 330.00000 | 23.95770 | 43.00558 | -0.3899 | 8.49672 |
October | 340.00000 | 23.86223 | 36.51849 | 0.35779 | 7.98079 |
November | 330.00000 | 22.88081 | 24.13810 | -0.0254 | 6.49623 |
December | 338.00000 | 21.34924 | 20.42600 | -0.4644 | 9.86301 |
Annual Sum or Average | 4030.00000 | 23.16295 | 30.67926 | -0.2422 | 8.31776 |
Minimum of Months | 308.00000 | 21.34924 | 18.19024 | -0.5473 | 6.18183 |
Maximum of Months | 348.00000 | 23.99385 | 50.07262 | 0.35779 | 11.72704 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.37693 | 23.16929 | -0.4515 | 9.74635 |
February | 308.00000 | 21.95273 | 19.65803 | -0.3400 | 8.52827 |
March | 348.00000 | 22.61014 | 18.34685 | -0.1894 | 7.01165 |
April | 330.00000 | 23.71558 | 21.57056 | 0.15943 | 6.15380 |
May | 344.00000 | 23.94417 | 30.45049 | -0.5521 | 11.86285 |
June | 336.00000 | 23.96552 | 34.48429 | -0.4443 | 9.45293 |
July | 338.00000 | 23.99371 | 50.08295 | -0.3119 | 7.35649 |
August | 348.00000 | 23.96768 | 45.62282 | -0.3542 | 7.89985 |
September | 330.00000 | 23.95778 | 43.00250 | -0.3879 | 8.47108 |
October | 340.00000 | 23.84551 | 36.58578 | 0.35143 | 7.91579 |
November | 330.00000 | 22.79748 | 24.27909 | -0.0511 | 6.59957 |
December | 338.00000 | 21.30856 | 20.45763 | -0.4849 | 10.24428 |
Annual Sum or Average | 4030.00000 | 23.12727 | 30.73411 | -0.2553 | 8.44446 |
Minimum of Months | 308.00000 | 21.30856 | 18.34685 | -0.5521 | 6.15380 |
Maximum of Months | 348.00000 | 23.99371 | 50.08295 | 0.35143 | 11.86285 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.30921 | 23.06586 | -0.5050 | 10.80404 |
February | 308.00000 | 21.83610 | 19.72665 | -0.4012 | 9.52656 |
March | 348.00000 | 22.45677 | 18.42780 | -0.2536 | 7.73291 |
April | 330.00000 | 23.66420 | 21.53578 | 0.14030 | 6.20732 |
May | 344.00000 | 23.94426 | 30.21811 | -0.5360 | 11.59015 |
June | 336.00000 | 23.96976 | 34.39139 | -0.4019 | 8.72422 |
July | 338.00000 | 24.00116 | 49.74810 | -0.2632 | 6.82320 |
August | 348.00000 | 23.97387 | 45.41870 | -0.3037 | 7.27750 |
September | 330.00000 | 23.96613 | 42.71120 | -0.3387 | 7.79463 |
October | 340.00000 | 23.80318 | 36.57841 | 0.34973 | 8.03980 |
November | 330.00000 | 22.69548 | 24.28118 | -0.0902 | 6.90230 |
December | 338.00000 | 21.27049 | 20.32629 | -0.5271 | 11.17075 |
Annual Sum or Average | 4030.00000 | 23.08228 | 30.62616 | -0.2611 | 8.55172 |
Minimum of Months | 308.00000 | 21.27049 | 18.42780 | -0.5360 | 6.20732 |
Maximum of Months | 348.00000 | 24.00116 | 49.74810 | 0.34973 | 11.59015 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 487581.23 | 139528.55 | 0.50 | 487581.23 | -0.0 | 0.00 | 0.03 | 03-JAN-15:00 | 0.00 | 01-JAN-00:05 | 439.35 | 03-JAN-15:00 | 439.35 | 03-JAN-15:00 | 0.00 | 01-JAN-00:05 | 125.54 | 03-JAN-15:00 | 0.00 | 01-JAN-00:05 |
February | 0.330464E+09 | 91911818.05 | 34.83 | 0.330464E+09 | -0.0 | 0.00 | 0.35 | 20-FEB-16:00 | 0.00 | 01-FEB-00:10 | 6075.74 | 20-FEB-16:00 | 6075.74 | 20-FEB-16:00 | 0.00 | 20-FEB-16:30 | 1659.83 | 20-FEB-16:00 | 0.00 | 01-FEB-00:10 |
March | 0.920474E+09 | 0.255961E+09 | 85.92 | 0.920474E+09 | -0.0 | 0.00 | 0.42 | 14-MAR-16:30 | 0.00 | 01-MAR-00:10 | 7416.49 | 14-MAR-16:30 | 7416.49 | 14-MAR-16:30 | 0.00 | 21-MAR-18:00 | 2033.57 | 21-MAR-16:10 | 0.00 | 01-MAR-00:10 |
April | 0.825938E+10 | 0.229839E+10 | 313.53 | 0.823517E+10 | 24216410.16 | 0.00 | 0.87 | 29-APR-08:62 | 0.00 | 01-APR-00:10 | 18292.63 | 29-APR-08:62 | 16356.80 | 29-APR-08:62 | 1935.83 | 29-APR-08:62 | 4562.16 | 21-APR-14:00 | 0.00 | 01-APR-00:10 |
May | 0.165586E+11 | 0.461468E+10 | 443.11 | 0.160903E+11 | 0.468335E+09 | 0.00 | 1.00 | 09-MAY-08:62 | 0.00 | 01-MAY-00:10 | 45804.10 | 23-MAY-08:62 | 43020.10 | 30-MAY-08:61 | 8796.32 | 23-MAY-08:62 | 10459.08 | 31-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.236863E+11 | 0.678971E+10 | 460.29 | 0.228665E+11 | 0.819813E+09 | 0.00 | 1.00 | 01-JUN-08:62 | 0.00 | 01-JUN-00:10 | 46414.65 | 30-JUN-08:62 | 44450.98 | 09-JUN-08:61 | 17200.18 | 29-JUN-08:62 | 10866.44 | 07-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.284991E+11 | 0.761272E+10 | 478.04 | 0.236645E+11 | 0.483455E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 49926.50 | 19-JUL-08:62 | 44092.31 | 03-JUL-08:61 | 24049.33 | 19-JUL-08:03 | 11045.24 | 26-JUL-08:61 | 0.00 | 01-JUL-00:05 |
August | 0.249035E+11 | 0.671719E+10 | 470.42 | 0.221035E+11 | 0.279996E+10 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 48920.61 | 02-AUG-08:61 | 43993.97 | 26-AUG-08:62 | 20239.60 | 14-AUG-08:61 | 10932.46 | 07-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.209333E+11 | 0.551127E+10 | 447.42 | 0.182537E+11 | 0.267965E+10 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-00:03 | 48240.42 | 22-SEP-08:61 | 42731.73 | 11-SEP-08:62 | 20190.94 | 14-SEP-08:62 | 10644.34 | 15-SEP-08:62 | 0.00 | 01-SEP-00:03 |
October | 0.970449E+10 | 0.254542E+10 | 329.49 | 0.869960E+10 | 0.100490E+10 | 0.00 | 1.00 | 02-OCT-08:61 | 0.00 | 01-OCT-00:10 | 47352.62 | 04-OCT-08:62 | 36654.18 | 02-OCT-08:61 | 18124.57 | 04-OCT-08:62 | 10290.54 | 05-OCT-08:61 | 0.00 | 01-OCT-00:10 |
November | 0.796828E+09 | 0.214848E+09 | 64.71 | 0.788120E+09 | 8707660.04 | 0.00 | 1.00 | 10-NOV-09:02 | 0.00 | 01-NOV-00:10 | 30311.15 | 10-NOV-09:02 | 27963.11 | 10-NOV-09:02 | 2348.04 | 10-NOV-09:02 | 6535.43 | 10-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.134593E+12 | 0.366522E+11 | 3128.25 | 0.121953E+12 | 0.126401E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.284991E+11 | 0.761272E+10 | 478.04 | 0.236645E+11 | 0.483455E+10 | 0.00 | 1.00 | 0.00 | 49926.50 | 44450.98 | 24049.33 | 11045.24 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 13202528.32 | 3645010.45 | 8.69 | 13170912.06 | 31616.25 | 0.00 | 0.31 | 01-JAN-18:10 | 0.00 | 01-JAN-00:05 | 2752.20 | 01-JAN-18:10 | 2752.20 | 01-JAN-18:10 | 17.48 | 01-JAN-23:10 | 717.98 | 01-JAN-18:10 | 0.00 | 01-JAN-00:05 |
February | 0.305614E+09 | 80033540.57 | 47.51 | 0.305572E+09 | 41660.07 | 0.00 | 1.00 | 12-FEB-18:01 | 0.00 | 01-FEB-00:10 | 22008.57 | 19-FEB-18:08 | 22008.57 | 12-FEB-18:09 | 65.28 | 13-FEB-21:40 | 4659.60 | 12-FEB-18:09 | 0.00 | 01-FEB-00:10 |
March | 0.778004E+09 | 0.204971E+09 | 111.35 | 0.777888E+09 | 115307.52 | 0.00 | 1.00 | 12-MAR-17:01 | 0.00 | 01-MAR-00:10 | 22008.57 | 12-MAR-17:09 | 22008.57 | 15-MAR-21:00 | 192.03 | 10-MAR-23:10 | 4749.17 | 26-MAR-17:01 | 0.00 | 01-MAR-00:10 |
April | 0.528582E+10 | 0.138551E+10 | 304.27 | 0.526545E+10 | 20373626.64 | 0.00 | 1.00 | 01-APR-21:01 | 0.00 | 01-APR-00:10 | 22776.24 | 18-APR-20:56 | 22260.01 | 29-APR-20:40 | 2499.98 | 18-APR-21:25 | 4941.44 | 29-APR-20:17 | 0.00 | 01-APR-00:10 |
May | 0.929292E+10 | 0.249407E+10 | 428.06 | 0.899420E+10 | 0.298722E+09 | 0.00 | 1.00 | 02-MAY-20:01 | 0.00 | 01-MAY-00:10 | 23772.51 | 27-MAY-21:00 | 22544.68 | 30-MAY-08:61 | 7723.00 | 24-MAY-22:10 | 5357.14 | 31-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.122120E+11 | 0.342944E+10 | 454.66 | 0.117690E+11 | 0.443035E+09 | 0.00 | 1.00 | 01-JUN-08:62 | 0.00 | 01-JUN-00:10 | 23925.81 | 30-JUN-08:62 | 23032.63 | 21-JUN-08:61 | 8357.13 | 29-JUN-08:62 | 5547.70 | 07-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.144647E+11 | 0.380384E+10 | 474.67 | 0.120953E+11 | 0.236939E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 25170.42 | 19-JUL-08:62 | 22992.19 | 01-JUL-08:61 | 13884.07 | 18-JUL-20:53 | 5609.08 | 26-JUL-08:61 | 0.00 | 01-JUL-00:05 |
August | 0.129367E+11 | 0.341259E+10 | 460.87 | 0.114386E+11 | 0.149809E+10 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 24902.98 | 03-AUG-08:61 | 22955.21 | 07-AUG-08:61 | 11748.17 | 16-AUG-20:35 | 5543.64 | 07-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.115553E+11 | 0.293742E+10 | 415.82 | 0.100893E+11 | 0.146608E+10 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-00:03 | 24822.38 | 22-SEP-08:61 | 22456.68 | 12-SEP-08:62 | 12646.42 | 23-SEP-18:02 | 5388.98 | 15-SEP-08:62 | 0.00 | 01-SEP-00:03 |
October | 0.602137E+10 | 0.149981E+10 | 311.26 | 0.537197E+10 | 0.649405E+09 | 0.00 | 1.00 | 02-OCT-08:61 | 0.00 | 01-OCT-00:10 | 24622.50 | 03-OCT-20:03 | 22008.57 | 09-OCT-19:15 | 10681.16 | 03-OCT-22:10 | 5295.98 | 03-OCT-20:03 | 0.00 | 01-OCT-00:10 |
November | 0.587149E+09 | 0.152787E+09 | 83.41 | 0.580873E+09 | 6275458.14 | 0.00 | 1.00 | 08-NOV-21:01 | 0.00 | 01-NOV-00:10 | 22008.57 | 09-NOV-21:44 | 22008.57 | 09-NOV-21:01 | 1210.08 | 10-NOV-09:02 | 4659.60 | 08-NOV-21:20 | 0.00 | 01-NOV-00:10 |
December | 4957521.50 | 1358745.42 | 2.92 | 4955677.64 | 1843.86 | 0.00 | 0.30 | 10-DEC-18:10 | 0.00 | 01-DEC-00:10 | 2680.18 | 10-DEC-18:10 | 2680.18 | 10-DEC-18:10 | 2.02 | 25-DEC-21:10 | 700.61 | 10-DEC-18:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.734578E+11 | 0.194055E+11 | 3103.50 | 0.667063E+11 | 0.675155E+10 | 0.00 | ||||||||||||||
Minimum of Months | 4957521.50 | 1358745.42 | 2.92 | 4955677.64 | 1843.86 | 0.00 | 0.30 | 0.00 | 2680.18 | 2680.18 | 2.02 | 700.61 | 0.00 | |||||||
Maximum of Months | 0.144647E+11 | 0.380384E+10 | 474.67 | 0.120953E+11 | 0.236939E+10 | 0.00 | 1.00 | 0.00 | 25170.42 | 23032.63 | 13884.07 | 5609.08 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 1431675.45 | 400976.19 | 2.00 | 1431675.45 | 0.00 | 0.00 | 0.06 | 03-JAN-15:00 | 0.00 | 01-JAN-00:05 | 480.72 | 03-JAN-15:00 | 480.72 | 03-JAN-15:00 | 0.00 | 03-JAN-15:00 | 133.98 | 03-JAN-15:00 | 0.00 | 01-JAN-00:05 |
February | 0.175435E+09 | 47932772.13 | 35.83 | 0.175435E+09 | 0.00 | 0.00 | 0.33 | 20-FEB-15:00 | 0.00 | 01-FEB-00:10 | 3025.56 | 20-FEB-15:00 | 3025.56 | 20-FEB-15:00 | 0.00 | 21-FEB-15:20 | 816.58 | 20-FEB-15:00 | 0.00 | 01-FEB-00:10 |
March | 0.533569E+09 | 0.145129E+09 | 86.08 | 0.533569E+09 | 33.62 | 0.00 | 0.45 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 | 4208.79 | 22-MAR-13:00 | 4208.79 | 22-MAR-13:00 | 0.02 | 10-MAR-19:00 | 1136.87 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.341114E+10 | 0.931407E+09 | 230.79 | 0.340095E+10 | 10190819.34 | 0.00 | 1.00 | 20-APR-07:03 | 0.00 | 01-APR-00:10 | 13496.74 | 20-APR-07:03 | 13496.74 | 20-APR-07:03 | 1211.46 | 29-APR-07:03 | 2860.08 | 20-APR-07:03 | 0.00 | 01-APR-00:10 |
May | 0.674796E+10 | 0.184768E+10 | 320.62 | 0.657114E+10 | 0.176821E+09 | 0.00 | 1.00 | 09-MAY-07:02 | 0.00 | 01-MAY-00:10 | 24457.87 | 28-MAY-08:62 | 22981.91 | 31-MAY-07:01 | 5784.46 | 24-MAY-07:03 | 5313.79 | 30-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.954069E+10 | 0.268810E+10 | 332.69 | 0.922132E+10 | 0.319369E+09 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 24672.42 | 04-JUN-08:61 | 23649.94 | 18-JUN-08:61 | 8669.75 | 29-JUN-07:02 | 5521.30 | 18-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.112458E+11 | 0.294830E+10 | 339.16 | 0.935229E+10 | 0.189355E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:05 | 26112.44 | 19-JUL-07:02 | 23473.00 | 03-JUL-07:01 | 14838.83 | 19-JUL-07:03 | 5706.67 | 02-JUL-08:61 | 0.00 | 01-JUL-00:05 |
August | 0.996316E+10 | 0.263207E+10 | 344.76 | 0.878238E+10 | 0.118078E+10 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 25963.52 | 03-AUG-07:01 | 23189.48 | 27-AUG-08:61 | 10774.41 | 14-AUG-07:03 | 5626.93 | 06-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.861176E+10 | 0.224039E+10 | 321.60 | 0.756782E+10 | 0.104393E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:03 | 25436.46 | 23-SEP-07:01 | 22365.21 | 11-SEP-07:02 | 11434.49 | 14-SEP-07:03 | 5460.16 | 10-SEP-08:61 | 0.00 | 01-SEP-00:03 |
October | 0.411173E+10 | 0.106137E+10 | 252.48 | 0.372206E+10 | 0.389668E+09 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 | 24837.41 | 04-OCT-07:02 | 21447.34 | 02-OCT-07:01 | 9543.26 | 04-OCT-07:02 | 5263.91 | 04-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.430919E+09 | 0.114206E+09 | 67.01 | 0.426286E+09 | 4633148.48 | 0.00 | 1.00 | 10-NOV-08:62 | 0.00 | 01-NOV-00:10 | 13085.18 | 10-NOV-08:62 | 12041.11 | 10-NOV-08:62 | 1044.06 | 10-NOV-08:62 | 2773.06 | 10-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.547736E+11 | 0.146570E+11 | 2333.03 | 0.497547E+11 | 0.501895E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.112458E+11 | 0.294830E+10 | 344.76 | 0.935229E+10 | 0.189355E+10 | 0.00 | 1.00 | 0.00 | 26112.44 | 23649.94 | 14838.83 | 5706.67 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 281107.82 | 79054.97 | 0.67 | 281107.82 | -0.0 | 0.00 | 0.03 | 03-JAN-15:00 | 0.00 | 01-JAN-00:05 | 219.12 | 03-JAN-15:00 | 219.12 | 03-JAN-15:00 | 0.00 | 01-JAN-00:05 | 61.54 | 03-JAN-15:00 | 0.00 | 01-JAN-00:05 |
February | 0.152353E+09 | 41802079.07 | 33.00 | 0.152353E+09 | 0.00 | 0.00 | 0.31 | 20-FEB-15:00 | 0.00 | 01-FEB-00:10 | 2807.01 | 20-FEB-15:00 | 2807.01 | 20-FEB-15:00 | 0.00 | 23-FEB-13:50 | 761.83 | 20-FEB-15:00 | 0.00 | 01-FEB-00:10 |
March | 0.492492E+09 | 0.134314E+09 | 83.17 | 0.492492E+09 | 25.19 | 0.00 | 0.44 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 | 4071.78 | 22-MAR-13:00 | 4071.78 | 22-MAR-13:00 | 0.02 | 10-MAR-19:00 | 1103.23 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.337421E+10 | 0.921717E+09 | 230.04 | 0.336385E+10 | 10364919.77 | 0.00 | 1.00 | 20-APR-07:03 | 0.00 | 01-APR-00:10 | 13277.56 | 20-APR-07:03 | 13277.56 | 20-APR-07:03 | 1227.10 | 29-APR-07:03 | 2813.70 | 20-APR-07:03 | 0.00 | 01-APR-00:10 |
May | 0.676898E+10 | 0.185094E+10 | 321.02 | 0.658950E+10 | 0.179478E+09 | 0.00 | 1.00 | 09-MAY-07:02 | 0.00 | 01-MAY-00:10 | 24323.29 | 28-MAY-08:62 | 22853.25 | 31-MAY-07:01 | 5867.92 | 24-MAY-07:03 | 5284.64 | 30-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.960228E+10 | 0.270001E+10 | 333.18 | 0.927683E+10 | 0.325454E+09 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 24537.35 | 04-JUN-08:61 | 23447.22 | 18-JUN-08:02 | 8628.50 | 29-JUN-07:02 | 5496.57 | 18-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.113264E+11 | 0.296261E+10 | 339.50 | 0.941398E+10 | 0.191242E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:05 | 25967.71 | 19-JUL-07:02 | 23338.83 | 03-JUL-07:01 | 14750.69 | 19-JUL-07:03 | 5680.02 | 02-JUL-08:61 | 0.00 | 01-JUL-00:05 |
August | 0.100394E+11 | 0.264623E+10 | 345.09 | 0.884168E+10 | 0.119775E+10 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 25819.70 | 03-AUG-07:01 | 23074.37 | 27-AUG-08:61 | 10698.15 | 14-AUG-07:03 | 5598.97 | 06-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.866567E+10 | 0.224976E+10 | 322.10 | 0.760930E+10 | 0.105637E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:03 | 25296.11 | 23-SEP-07:01 | 22229.93 | 11-SEP-07:02 | 11373.13 | 14-SEP-07:03 | 5429.96 | 10-SEP-08:61 | 0.00 | 01-SEP-00:03 |
October | 0.410503E+10 | 0.105888E+10 | 252.31 | 0.371412E+10 | 0.390904E+09 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 | 24699.84 | 04-OCT-07:02 | 21270.57 | 02-OCT-07:01 | 9495.37 | 04-OCT-07:02 | 5234.71 | 04-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.407353E+09 | 0.108058E+09 | 64.18 | 0.402768E+09 | 4584963.76 | 0.00 | 1.00 | 10-NOV-08:62 | 0.00 | 01-NOV-00:10 | 12710.28 | 10-NOV-08:62 | 11666.45 | 10-NOV-08:62 | 1043.83 | 10-NOV-08:62 | 2693.76 | 10-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.549345E+11 | 0.146744E+11 | 2324.26 | 0.498571E+11 | 0.507733E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.113264E+11 | 0.296261E+10 | 345.09 | 0.941398E+10 | 0.191242E+10 | 0.00 | 1.00 | 0.00 | 25967.71 | 23447.22 | 14750.69 | 5680.02 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.122739E+09 | 33886860.87 | 29.67 | 0.122739E+09 | -0.0 | 0.00 | 0.28 | 20-FEB-15:00 | 0.00 | 01-FEB-00:10 | 2528.08 | 20-FEB-15:00 | 2528.08 | 20-FEB-15:00 | 0.00 | 20-FEB-15:20 | 691.60 | 20-FEB-15:00 | 0.00 | 01-FEB-00:10 |
March | 0.425068E+09 | 0.116563E+09 | 75.75 | 0.425068E+09 | -0.0 | 0.00 | 0.42 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 | 3842.39 | 22-MAR-13:00 | 3842.39 | 22-MAR-13:00 | 0.00 | 14-MAR-16:40 | 1047.87 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.322767E+10 | 0.886223E+09 | 224.24 | 0.321824E+10 | 9437367.92 | 0.00 | 1.00 | 20-APR-07:03 | 0.00 | 01-APR-00:10 | 11493.83 | 20-APR-07:03 | 11493.83 | 20-APR-07:03 | 1121.04 | 29-APR-07:03 | 2436.58 | 20-APR-07:03 | 0.00 | 01-APR-00:10 |
May | 0.660483E+10 | 0.181319E+10 | 319.06 | 0.643106E+10 | 0.173774E+09 | 0.00 | 1.00 | 09-MAY-07:02 | 0.00 | 01-MAY-00:10 | 24386.05 | 28-MAY-08:62 | 22911.96 | 31-MAY-07:01 | 5600.52 | 28-MAY-08:62 | 5298.66 | 30-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.945048E+10 | 0.266560E+10 | 332.62 | 0.913455E+10 | 0.315937E+09 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 24601.92 | 04-JUN-08:61 | 23542.44 | 18-JUN-08:61 | 8668.47 | 29-JUN-07:02 | 5507.62 | 18-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.111655E+11 | 0.292976E+10 | 338.57 | 0.928395E+10 | 0.188156E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:05 | 26037.37 | 19-JUL-07:02 | 23406.79 | 03-JUL-07:01 | 14815.98 | 19-JUL-07:03 | 5688.11 | 02-JUL-08:61 | 0.00 | 01-JUL-00:05 |
August | 0.987906E+10 | 0.261246E+10 | 344.65 | 0.870746E+10 | 0.117159E+10 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 25888.83 | 03-AUG-07:01 | 23122.71 | 27-AUG-08:61 | 10733.12 | 03-AUG-07:03 | 5613.13 | 06-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.850828E+10 | 0.221664E+10 | 321.47 | 0.747425E+10 | 0.103404E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:03 | 25363.00 | 23-SEP-07:01 | 22299.05 | 11-SEP-07:02 | 11263.05 | 14-SEP-07:01 | 5444.71 | 10-SEP-08:61 | 0.00 | 01-SEP-00:03 |
October | 0.397082E+10 | 0.102806E+10 | 245.95 | 0.359537E+10 | 0.375454E+09 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 | 24765.55 | 04-OCT-07:02 | 21386.72 | 02-OCT-07:01 | 9538.43 | 04-OCT-07:02 | 5248.78 | 04-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.360730E+09 | 96008511.81 | 58.60 | 0.356766E+09 | 3964519.64 | 0.00 | 1.00 | 10-NOV-08:62 | 0.00 | 01-NOV-00:10 | 11214.02 | 10-NOV-08:62 | 10235.96 | 10-NOV-08:62 | 978.06 | 10-NOV-08:62 | 2379.26 | 10-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.537152E+11 | 0.143984E+11 | 2290.58 | 0.487495E+11 | 0.496576E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.111655E+11 | 0.292976E+10 | 344.65 | 0.928395E+10 | 0.188156E+10 | 0.00 | 1.00 | 0.00 | 26037.37 | 23542.44 | 14815.98 | 5688.11 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.185414E+09 | 52271306.24 | 26.17 | 0.185414E+09 | 0.00 | 0.00 | 0.28 | 20-FEB-15:30 | 0.00 | 01-FEB-00:10 | 4399.62 | 20-FEB-15:30 | 4399.62 | 20-FEB-15:30 | 0.00 | 21-FEB-15:00 | 1226.64 | 20-FEB-15:30 | 0.00 | 01-FEB-00:10 |
March | 0.650428E+09 | 0.182385E+09 | 68.75 | 0.650428E+09 | -0.0 | 0.00 | 0.41 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 | 6661.07 | 22-MAR-13:00 | 6661.07 | 22-MAR-13:00 | 0.00 | 14-MAR-15:20 | 1853.22 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.558272E+10 | 0.156698E+10 | 220.50 | 0.556288E+10 | 19836133.31 | 0.00 | 0.93 | 29-APR-08:62 | 0.00 | 01-APR-00:10 | 18428.97 | 29-APR-08:62 | 16703.07 | 29-APR-08:62 | 1725.90 | 29-APR-08:62 | 4352.16 | 21-APR-14:20 | 0.00 | 01-APR-00:10 |
May | 0.117208E+11 | 0.327805E+10 | 315.04 | 0.113933E+11 | 0.327435E+09 | 0.00 | 1.00 | 09-MAY-08:62 | 0.00 | 01-MAY-00:10 | 43343.96 | 28-MAY-09:02 | 40767.14 | 30-MAY-08:61 | 9125.29 | 28-MAY-09:02 | 9854.75 | 31-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.170271E+11 | 0.489328E+10 | 325.59 | 0.164362E+11 | 0.590994E+09 | 0.00 | 1.00 | 01-JUN-08:62 | 0.00 | 01-JUN-00:10 | 43972.99 | 04-JUN-09:01 | 41666.19 | 21-JUN-08:61 | 15789.12 | 29-JUN-08:62 | 10241.34 | 18-JUN-09:01 | 0.00 | 01-JUN-00:10 |
July | 0.199416E+11 | 0.530840E+10 | 328.32 | 0.164919E+11 | 0.344968E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 45990.79 | 17-JUL-08:61 | 41376.40 | 03-JUL-08:61 | 21623.36 | 17-JUL-08:03 | 10494.32 | 02-JUL-09:01 | 0.00 | 01-JUL-00:05 |
August | 0.177423E+11 | 0.476197E+10 | 337.02 | 0.155740E+11 | 0.216827E+10 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 44946.29 | 09-AUG-08:61 | 41736.66 | 20-AUG-09:01 | 18906.04 | 14-AUG-08:03 | 10335.60 | 27-AUG-09:01 | 0.00 | 01-AUG-00:10 |
September | 0.151928E+11 | 0.401261E+10 | 312.60 | 0.133153E+11 | 0.187749E+10 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-00:03 | 45105.70 | 22-SEP-08:61 | 40644.24 | 12-SEP-08:62 | 18375.04 | 14-SEP-08:62 | 10028.39 | 10-SEP-09:01 | 0.00 | 01-SEP-00:03 |
October | 0.698825E+10 | 0.183782E+10 | 237.10 | 0.625862E+10 | 0.729624E+09 | 0.00 | 1.00 | 01-OCT-09:02 | 0.00 | 01-OCT-00:10 | 44391.52 | 04-OCT-08:62 | 40401.28 | 01-OCT-09:02 | 16778.06 | 04-OCT-08:62 | 9658.55 | 05-OCT-08:61 | 0.00 | 01-OCT-00:10 |
November | 0.567788E+09 | 0.154028E+09 | 52.55 | 0.559945E+09 | 7842350.03 | 0.00 | 1.00 | 10-NOV-09:02 | 0.00 | 01-NOV-00:10 | 28562.85 | 10-NOV-09:02 | 26244.33 | 10-NOV-09:02 | 2318.53 | 10-NOV-09:02 | 6158.44 | 10-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.955993E+11 | 0.260478E+11 | 2223.64 | 0.864281E+11 | 0.917117E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.199416E+11 | 0.530840E+10 | 337.02 | 0.164919E+11 | 0.344968E+10 | 0.00 | 1.00 | 0.00 | 45990.79 | 41736.66 | 21623.36 | 10494.32 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 84207973.08 | 23385595.07 | 23.33 | 84207973.08 | 0.00 | 0.00 | 0.27 | 20-FEB-15:40 | 0.00 | 01-FEB-00:10 | 2172.78 | 20-FEB-15:40 | 2172.78 | 20-FEB-15:40 | 0.00 | 22-FEB-15:40 | 596.97 | 20-FEB-15:40 | 0.00 | 01-FEB-00:10 |
March | 0.306579E+09 | 84661934.14 | 64.00 | 0.306579E+09 | -0.0 | 0.00 | 0.39 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 | 3313.16 | 22-MAR-13:00 | 3313.16 | 22-MAR-13:00 | 0.00 | 22-MAR-12:30 | 909.04 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.284022E+10 | 0.784242E+09 | 217.08 | 0.283108E+10 | 9141734.83 | 0.00 | 0.83 | 21-APR-14:20 | 0.00 | 01-APR-00:10 | 8064.12 | 29-APR-08:62 | 7816.76 | 21-APR-14:40 | 726.94 | 29-APR-08:62 | 2204.88 | 21-APR-14:30 | 0.00 | 01-APR-00:10 |
May | 0.601383E+10 | 0.165401E+10 | 315.02 | 0.585114E+10 | 0.162688E+09 | 0.00 | 1.00 | 09-MAY-08:62 | 0.00 | 01-MAY-00:10 | 22384.74 | 28-MAY-09:02 | 21049.99 | 30-MAY-08:61 | 4646.76 | 28-MAY-09:02 | 4999.37 | 31-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.875233E+10 | 0.247388E+10 | 326.20 | 0.845765E+10 | 0.294681E+09 | 0.00 | 1.00 | 01-JUN-08:62 | 0.00 | 01-JUN-00:10 | 22702.10 | 04-JUN-09:01 | 21506.81 | 09-JUN-08:61 | 8114.03 | 29-JUN-08:62 | 5199.16 | 18-JUN-09:01 | 0.00 | 01-JUN-00:10 |
July | 0.102462E+11 | 0.268311E+10 | 327.23 | 0.849814E+10 | 0.174808E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 23754.00 | 17-JUL-08:61 | 21389.39 | 03-JUL-08:61 | 11140.11 | 17-JUL-08:03 | 5324.57 | 02-JUL-09:01 | 0.00 | 01-JUL-00:05 |
August | 0.911495E+10 | 0.240614E+10 | 336.83 | 0.802191E+10 | 0.109304E+10 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 23211.76 | 09-AUG-08:61 | 21595.41 | 07-AUG-08:61 | 9727.25 | 14-AUG-08:03 | 5242.93 | 27-AUG-09:01 | 0.00 | 01-AUG-00:10 |
September | 0.780613E+10 | 0.202757E+10 | 312.87 | 0.685911E+10 | 0.947025E+09 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-00:03 | 23295.31 | 22-SEP-08:61 | 20780.82 | 11-SEP-08:62 | 9459.33 | 14-SEP-08:62 | 5088.10 | 10-SEP-09:01 | 0.00 | 01-SEP-00:03 |
October | 0.357449E+10 | 0.924309E+09 | 234.47 | 0.321024E+10 | 0.364250E+09 | 0.00 | 1.00 | 01-OCT-09:02 | 0.00 | 01-OCT-00:10 | 22926.88 | 04-OCT-08:62 | 20874.52 | 01-OCT-09:02 | 8623.55 | 04-OCT-08:62 | 4900.46 | 05-OCT-08:61 | 0.00 | 01-OCT-00:10 |
November | 0.278598E+09 | 74297616.41 | 49.21 | 0.275169E+09 | 3428701.41 | 0.00 | 1.00 | 10-NOV-09:02 | 0.00 | 01-NOV-00:10 | 13251.19 | 10-NOV-09:02 | 12175.30 | 10-NOV-09:02 | 1075.89 | 10-NOV-09:02 | 2807.60 | 10-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.490176E+11 | 0.131356E+11 | 2206.25 | 0.443952E+11 | 0.462233E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.102462E+11 | 0.268311E+10 | 336.83 | 0.849814E+10 | 0.174808E+10 | 0.00 | 1.00 | 0.00 | 23754.00 | 21595.41 | 11140.11 | 5324.57 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 76568644.61 | 21311876.16 | 22.83 | 76568644.61 | -0.0 | 0.00 | 0.26 | 20-FEB-15:40 | 0.00 | 01-FEB-00:10 | 2076.34 | 20-FEB-15:40 | 2076.34 | 20-FEB-15:40 | 0.00 | 21-FEB-16:40 | 572.02 | 20-FEB-15:40 | 0.00 | 01-FEB-00:10 |
March | 0.283859E+09 | 78573740.43 | 61.83 | 0.283859E+09 | 0.00 | 0.00 | 0.38 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 | 3202.00 | 22-MAR-13:00 | 3202.00 | 22-MAR-13:00 | 0.00 | 14-MAR-15:10 | 881.12 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.278343E+10 | 0.769787E+09 | 215.56 | 0.277455E+10 | 8883134.38 | 0.00 | 0.82 | 21-APR-14:20 | 0.00 | 01-APR-00:10 | 7754.94 | 21-APR-14:40 | 7754.94 | 21-APR-14:40 | 667.85 | 29-APR-08:62 | 2189.19 | 21-APR-14:30 | 0.00 | 01-APR-00:10 |
May | 0.595348E+10 | 0.163871E+10 | 314.22 | 0.579237E+10 | 0.161116E+09 | 0.00 | 1.00 | 09-MAY-08:62 | 0.00 | 01-MAY-00:10 | 22295.28 | 28-MAY-09:02 | 20958.67 | 30-MAY-08:61 | 4643.03 | 28-MAY-09:02 | 4978.05 | 31-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.869519E+10 | 0.245868E+10 | 325.81 | 0.840285E+10 | 0.292337E+09 | 0.00 | 1.00 | 01-JUN-08:62 | 0.00 | 01-JUN-00:10 | 22608.96 | 04-JUN-09:01 | 21417.27 | 21-JUN-08:61 | 8095.32 | 29-JUN-08:62 | 5178.66 | 18-JUN-09:01 | 0.00 | 01-JUN-00:10 |
July | 0.101866E+11 | 0.266818E+10 | 327.03 | 0.844700E+10 | 0.173963E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 23660.24 | 17-JUL-08:61 | 21305.77 | 03-JUL-08:61 | 11105.74 | 17-JUL-08:03 | 5303.91 | 02-JUL-09:01 | 0.00 | 01-JUL-00:05 |
August | 0.906062E+10 | 0.239255E+10 | 336.79 | 0.797396E+10 | 0.108666E+10 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 23120.47 | 09-AUG-08:61 | 21504.30 | 07-AUG-08:61 | 9695.99 | 14-AUG-08:03 | 5221.36 | 27-AUG-09:01 | 0.00 | 01-AUG-00:10 |
September | 0.775421E+10 | 0.201481E+10 | 312.98 | 0.681231E+10 | 0.941902E+09 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-00:03 | 23203.39 | 22-SEP-08:61 | 20697.27 | 11-SEP-08:62 | 9434.23 | 14-SEP-08:62 | 5068.11 | 10-SEP-09:01 | 0.00 | 01-SEP-00:03 |
October | 0.352673E+10 | 0.912681E+09 | 232.66 | 0.316712E+10 | 0.359607E+09 | 0.00 | 1.00 | 01-OCT-09:02 | 0.00 | 01-OCT-00:10 | 22836.15 | 04-OCT-08:62 | 20623.08 | 01-OCT-09:02 | 8601.71 | 04-OCT-08:62 | 4881.19 | 05-OCT-08:61 | 0.00 | 01-OCT-00:10 |
November | 0.264057E+09 | 70509491.12 | 47.21 | 0.260781E+09 | 3275358.57 | 0.00 | 1.00 | 10-NOV-09:02 | 0.00 | 01-NOV-00:10 | 12485.83 | 10-NOV-09:02 | 11437.72 | 10-NOV-09:02 | 1048.11 | 10-NOV-09:02 | 2645.76 | 10-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.485848E+11 | 0.130258E+11 | 2196.93 | 0.439914E+11 | 0.459341E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.101866E+11 | 0.266818E+10 | 336.79 | 0.844700E+10 | 0.173963E+10 | 0.00 | 1.00 | 0.00 | 23660.24 | 21504.30 | 11105.74 | 5303.91 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 60232296.13 | 16848386.91 | 21.33 | 60232296.13 | 0.00 | 0.00 | 0.23 | 20-FEB-15:30 | 0.00 | 01-FEB-00:10 | 1896.55 | 20-FEB-15:30 | 1896.55 | 20-FEB-15:30 | 0.00 | 22-FEB-16:00 | 525.46 | 20-FEB-15:30 | 0.00 | 01-FEB-00:10 |
March | 0.236374E+09 | 65805504.24 | 55.00 | 0.236374E+09 | 0.00 | 0.00 | 0.36 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 | 2968.18 | 22-MAR-13:00 | 2968.18 | 22-MAR-13:00 | 0.00 | 14-MAR-16:10 | 822.72 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.267192E+10 | 0.742091E+09 | 210.69 | 0.266371E+10 | 8212502.38 | 0.00 | 0.81 | 21-APR-14:20 | 0.00 | 01-APR-00:10 | 7661.16 | 21-APR-14:40 | 7661.16 | 21-APR-14:40 | 473.08 | 29-APR-08:62 | 2169.06 | 21-APR-14:30 | 0.00 | 01-APR-00:10 |
May | 0.586834E+10 | 0.161886E+10 | 313.24 | 0.571014E+10 | 0.158202E+09 | 0.00 | 1.00 | 09-MAY-08:62 | 0.00 | 01-MAY-00:10 | 22343.65 | 28-MAY-09:02 | 20988.85 | 30-MAY-08:61 | 4671.47 | 28-MAY-09:02 | 4986.62 | 31-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.868001E+10 | 0.245629E+10 | 326.05 | 0.839036E+10 | 0.289652E+09 | 0.00 | 1.00 | 01-JUN-08:62 | 0.00 | 01-JUN-00:10 | 22655.94 | 04-JUN-09:01 | 21459.43 | 21-JUN-08:61 | 7448.43 | 28-JUN-08:62 | 5190.76 | 18-JUN-09:01 | 0.00 | 01-JUN-00:10 |
July | 0.102005E+11 | 0.267267E+10 | 327.18 | 0.846253E+10 | 0.173793E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 23714.45 | 17-JUL-08:61 | 21356.09 | 03-JUL-08:61 | 11139.76 | 17-JUL-08:03 | 5316.41 | 02-JUL-09:01 | 0.00 | 01-JUL-00:05 |
August | 0.908337E+10 | 0.239855E+10 | 336.68 | 0.799866E+10 | 0.108472E+10 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 23173.85 | 09-AUG-08:61 | 21559.16 | 07-AUG-08:61 | 9715.83 | 14-AUG-08:03 | 5233.80 | 27-AUG-09:01 | 0.00 | 01-AUG-00:10 |
September | 0.776232E+10 | 0.201708E+10 | 312.84 | 0.682037E+10 | 0.941954E+09 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-00:03 | 23257.20 | 22-SEP-08:61 | 20744.68 | 11-SEP-08:62 | 9465.07 | 14-SEP-08:62 | 5079.97 | 10-SEP-09:01 | 0.00 | 01-SEP-00:03 |
October | 0.346079E+10 | 0.897101E+09 | 229.27 | 0.310900E+10 | 0.351797E+09 | 0.00 | 1.00 | 01-OCT-09:02 | 0.00 | 01-OCT-00:10 | 22887.54 | 04-OCT-08:62 | 19242.64 | 01-OCT-09:02 | 8637.08 | 04-OCT-08:62 | 4892.45 | 05-OCT-08:61 | 0.00 | 01-OCT-00:10 |
November | 0.237427E+09 | 63562176.01 | 43.78 | 0.234486E+09 | 2940373.70 | 0.00 | 1.00 | 10-NOV-09:02 | 0.00 | 01-NOV-00:10 | 10359.71 | 10-NOV-09:02 | 9402.86 | 10-NOV-09:02 | 956.86 | 10-NOV-09:02 | 2196.24 | 10-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.482613E+11 | 0.129489E+11 | 2176.06 | 0.436858E+11 | 0.457540E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.102005E+11 | 0.267267E+10 | 336.68 | 0.846253E+10 | 0.173793E+10 | 0.00 | 1.00 | 0.00 | 23714.45 | 21559.16 | 11139.76 | 5316.41 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 40521247.79 | 11423277.58 | 16.50 | 40521247.79 | 0.00 | 0.00 | 0.20 | 20-FEB-15:30 | 0.00 | 01-FEB-00:10 | 1728.42 | 20-FEB-15:30 | 1728.42 | 20-FEB-15:30 | 0.00 | 21-FEB-14:50 | 483.67 | 20-FEB-15:30 | 0.00 | 01-FEB-00:10 |
March | 0.191182E+09 | 53759205.96 | 42.33 | 0.191182E+09 | -0.0 | 0.00 | 0.33 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 | 2935.16 | 22-MAR-13:00 | 2935.16 | 22-MAR-13:00 | 0.00 | 14-MAR-15:40 | 820.81 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.279044E+10 | 0.778738E+09 | 203.68 | 0.278297E+10 | 7463197.20 | 0.00 | 0.80 | 21-APR-14:10 | 0.00 | 01-APR-00:10 | 8117.12 | 21-APR-14:20 | 8117.12 | 21-APR-14:20 | 340.95 | 30-APR-09:03 | 2316.15 | 21-APR-14:10 | 0.00 | 01-APR-00:10 |
May | 0.636613E+10 | 0.175976E+10 | 314.62 | 0.619809E+10 | 0.168033E+09 | 0.00 | 1.00 | 09-MAY-08:62 | 0.00 | 01-MAY-00:10 | 24625.26 | 28-MAY-09:02 | 22921.68 | 30-MAY-08:61 | 5435.70 | 28-MAY-09:02 | 5451.41 | 31-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.965457E+10 | 0.272589E+10 | 326.10 | 0.934101E+10 | 0.313558E+09 | 0.00 | 1.00 | 01-JUN-08:62 | 0.00 | 01-JUN-00:10 | 24656.77 | 04-JUN-09:03 | 23622.29 | 09-JUN-08:61 | 8040.40 | 28-JUN-08:62 | 5705.40 | 18-JUN-09:01 | 0.00 | 01-JUN-00:10 |
July | 0.114545E+11 | 0.299589E+10 | 330.60 | 0.955138E+10 | 0.190309E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 26263.94 | 19-JUL-08:62 | 23437.91 | 03-JUL-08:61 | 12649.89 | 17-JUL-08:03 | 5847.05 | 02-JUL-09:01 | 0.00 | 01-JUL-00:05 |
August | 0.103116E+11 | 0.270895E+10 | 336.99 | 0.911948E+10 | 0.119217E+10 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 25817.15 | 03-AUG-08:61 | 23522.56 | 07-AUG-08:61 | 10967.21 | 14-AUG-08:61 | 5750.86 | 27-AUG-09:01 | 0.00 | 01-AUG-00:10 |
September | 0.885762E+10 | 0.228672E+10 | 312.93 | 0.780865E+10 | 0.104897E+10 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-00:03 | 25632.92 | 22-SEP-08:61 | 22755.03 | 11-SEP-08:62 | 10565.59 | 14-SEP-08:62 | 5579.61 | 10-SEP-09:01 | 0.00 | 01-SEP-00:03 |
October | 0.375628E+10 | 0.973864E+09 | 223.77 | 0.338727E+10 | 0.369016E+09 | 0.00 | 1.00 | 01-OCT-09:02 | 0.00 | 01-OCT-00:10 | 25121.59 | 04-OCT-08:62 | 19559.93 | 02-OCT-08:61 | 9580.19 | 04-OCT-08:62 | 5370.29 | 05-OCT-08:61 | 0.00 | 01-OCT-00:10 |
November | 0.228524E+09 | 61322631.62 | 38.03 | 0.225914E+09 | 2609876.56 | 0.00 | 0.65 | 10-NOV-09:02 | 0.00 | 01-NOV-00:10 | 6548.81 | 10-NOV-09:02 | 5929.32 | 10-NOV-09:02 | 619.49 | 10-NOV-09:02 | 1551.00 | 10-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.536514E+11 | 0.143563E+11 | 2145.55 | 0.486465E+11 | 0.500491E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.114545E+11 | 0.299589E+10 | 336.99 | 0.955138E+10 | 0.190309E+10 | 0.00 | 1.00 | 0.00 | 26263.94 | 23622.29 | 12649.89 | 5847.05 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 137.81 | 68.21 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 130.25 | 61.26 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 109.08 | 55.08 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 82.63 | 35.13 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.67 | 20.89 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 68.66 | 10.48 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 69.58 | 8.56 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 82.78 | 12.56 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 117.10 | 24.49 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.91 | 39.47 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 146.13 | 62.19 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 138.21 | 74.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 106.74 | 39.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.67 | 8.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 146.13 | 74.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 137.81 | 68.21 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 130.25 | 61.26 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 109.08 | 55.08 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 82.63 | 35.13 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.67 | 20.89 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 68.66 | 10.48 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 69.58 | 8.56 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 82.78 | 12.56 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 117.10 | 24.49 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.91 | 39.47 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 146.13 | 62.19 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 138.21 | 74.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 106.74 | 39.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.67 | 8.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 146.13 | 74.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 137.81 | 68.21 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 130.25 | 61.26 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 109.08 | 55.08 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 82.63 | 35.13 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.67 | 20.89 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 68.66 | 10.48 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 69.58 | 8.56 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 82.78 | 12.56 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 117.10 | 24.49 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.91 | 39.47 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 146.13 | 62.19 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 138.21 | 74.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 106.74 | 39.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.67 | 8.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 146.13 | 74.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 137.81 | 68.21 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 130.25 | 61.26 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 109.08 | 55.08 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 82.63 | 35.13 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.67 | 20.89 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 68.66 | 10.48 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 69.58 | 8.56 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 82.78 | 12.56 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 117.10 | 24.49 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.91 | 39.47 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 146.13 | 62.19 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 138.21 | 74.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 106.74 | 39.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.67 | 8.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 146.13 | 74.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 118.27 | 89.61 | 28.67 | 166.02 | 81.10 | 0.00 | 0.00 | 0.00 |
February | 109.71 | 77.35 | 32.37 | 156.91 | 72.86 | 0.00 | 0.00 | 0.00 |
March | 89.16 | 51.41 | 37.75 | 131.49 | 65.58 | 0.00 | 0.00 | 0.00 |
April | 60.45 | 22.56 | 37.90 | 99.36 | 41.97 | 0.00 | 0.00 | 0.00 |
May | 42.72 | 5.98 | 36.74 | 77.44 | 25.10 | 0.00 | 0.00 | 0.00 |
June | 36.86 | 2.34 | 34.52 | 81.83 | 12.63 | 0.00 | 0.00 | 0.00 |
July | 37.57 | 3.48 | 34.09 | 83.11 | 10.30 | 0.00 | 0.00 | 0.00 |
August | 47.89 | 12.68 | 35.22 | 99.07 | 15.07 | 0.00 | 0.00 | 0.00 |
September | 74.76 | 38.84 | 35.92 | 140.52 | 29.31 | 0.00 | 0.00 | 0.00 |
October | 101.57 | 68.67 | 32.90 | 163.41 | 47.08 | 0.00 | 0.00 | 0.00 |
November | 122.24 | 93.19 | 29.05 | 175.89 | 74.05 | 0.00 | 0.00 | 0.00 |
December | 121.14 | 90.93 | 30.21 | 166.41 | 88.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 80.03 | 46.24 | 33.78 | 128.26 | 46.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.86 | 2.34 | 28.67 | 77.44 | 10.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.24 | 93.19 | 37.90 | 175.89 | 88.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 118.27 | 89.61 | 28.67 | 166.02 | 81.10 | 0.00 | 0.00 | 0.00 |
February | 109.71 | 77.35 | 32.37 | 156.91 | 72.86 | 0.00 | 0.00 | 0.00 |
March | 89.16 | 51.41 | 37.75 | 131.49 | 65.58 | 0.00 | 0.00 | 0.00 |
April | 60.45 | 22.56 | 37.90 | 99.36 | 41.97 | 0.00 | 0.00 | 0.00 |
May | 42.72 | 5.98 | 36.74 | 77.44 | 25.10 | 0.00 | 0.00 | 0.00 |
June | 36.86 | 2.34 | 34.52 | 81.83 | 12.63 | 0.00 | 0.00 | 0.00 |
July | 37.57 | 3.48 | 34.09 | 83.11 | 10.30 | 0.00 | 0.00 | 0.00 |
August | 47.89 | 12.68 | 35.22 | 99.07 | 15.07 | 0.00 | 0.00 | 0.00 |
September | 74.76 | 38.84 | 35.92 | 140.52 | 29.31 | 0.00 | 0.00 | 0.00 |
October | 101.57 | 68.67 | 32.90 | 163.41 | 47.08 | 0.00 | 0.00 | 0.00 |
November | 122.24 | 93.19 | 29.05 | 175.89 | 74.05 | 0.00 | 0.00 | 0.00 |
December | 121.14 | 90.93 | 30.21 | 166.41 | 88.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 80.03 | 46.24 | 33.78 | 128.26 | 46.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.86 | 2.34 | 28.67 | 77.44 | 10.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.24 | 93.19 | 37.90 | 175.89 | 88.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 135.74 | 73.18 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 128.06 | 65.68 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 106.96 | 58.69 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 81.78 | 36.33 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.54 | 21.25 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 68.99 | 10.66 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 70.00 | 8.65 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 83.15 | 12.57 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 117.22 | 24.30 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.50 | 39.82 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 144.62 | 64.85 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 136.22 | 78.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 105.92 | 41.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.54 | 8.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 144.62 | 78.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 135.74 | 73.18 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 128.06 | 65.68 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 106.96 | 58.69 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 81.78 | 36.33 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.54 | 21.25 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 68.99 | 10.66 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 70.00 | 8.65 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 83.15 | 12.57 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 117.22 | 24.30 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.50 | 39.82 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 144.62 | 64.85 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 136.22 | 78.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 105.92 | 41.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.54 | 8.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 144.62 | 78.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 118.27 | 89.61 | 28.67 | 163.59 | 86.93 | 0.00 | 0.00 | 0.00 |
February | 109.71 | 77.35 | 32.37 | 154.34 | 78.06 | 0.00 | 0.00 | 0.00 |
March | 89.16 | 51.41 | 37.75 | 129.01 | 69.83 | 0.00 | 0.00 | 0.00 |
April | 60.45 | 22.56 | 37.90 | 98.37 | 43.39 | 0.00 | 0.00 | 0.00 |
May | 42.72 | 5.98 | 36.74 | 77.28 | 25.53 | 0.00 | 0.00 | 0.00 |
June | 36.86 | 2.34 | 34.52 | 82.21 | 12.84 | 0.00 | 0.00 | 0.00 |
July | 37.57 | 3.48 | 34.09 | 83.60 | 10.41 | 0.00 | 0.00 | 0.00 |
August | 47.89 | 12.68 | 35.22 | 99.51 | 15.09 | 0.00 | 0.00 | 0.00 |
September | 74.76 | 38.84 | 35.92 | 140.68 | 29.09 | 0.00 | 0.00 | 0.00 |
October | 101.57 | 68.67 | 32.90 | 162.96 | 47.48 | 0.00 | 0.00 | 0.00 |
November | 122.24 | 93.19 | 29.05 | 174.15 | 77.17 | 0.00 | 0.00 | 0.00 |
December | 121.14 | 90.93 | 30.21 | 164.08 | 93.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 80.03 | 46.24 | 33.78 | 127.30 | 48.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.86 | 2.34 | 28.67 | 77.28 | 10.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.24 | 93.19 | 37.90 | 174.15 | 93.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 136.30 | 70.79 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 128.50 | 64.01 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 107.28 | 57.78 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 81.57 | 37.26 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 63.90 | 22.88 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 67.40 | 12.08 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 68.35 | 10.18 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 81.93 | 14.28 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.88 | 26.61 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.31 | 41.20 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 144.98 | 64.23 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 136.76 | 76.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 105.61 | 41.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 63.90 | 10.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 144.98 | 76.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 136.30 | 70.79 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 128.50 | 64.01 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 107.28 | 57.78 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 81.57 | 37.26 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 63.90 | 22.88 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 67.40 | 12.08 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 68.35 | 10.18 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 81.93 | 14.28 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.88 | 26.61 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.31 | 41.20 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 144.98 | 64.23 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 136.76 | 76.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 105.61 | 41.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 63.90 | 10.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 144.98 | 76.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.63 | 89.12 | 28.51 | 163.37 | 83.67 | 0.00 | 0.00 | 0.00 |
February | 109.11 | 76.92 | 32.19 | 154.03 | 75.67 | 0.00 | 0.00 | 0.00 |
March | 88.68 | 51.13 | 37.55 | 128.69 | 68.37 | 0.00 | 0.00 | 0.00 |
April | 60.12 | 22.43 | 37.69 | 97.59 | 44.24 | 0.00 | 0.00 | 0.00 |
May | 42.49 | 5.95 | 36.54 | 76.12 | 27.30 | 0.00 | 0.00 | 0.00 |
June | 36.66 | 2.33 | 34.33 | 79.94 | 14.46 | 0.00 | 0.00 | 0.00 |
July | 37.37 | 3.46 | 33.90 | 81.24 | 12.15 | 0.00 | 0.00 | 0.00 |
August | 47.63 | 12.61 | 35.02 | 97.56 | 17.02 | 0.00 | 0.00 | 0.00 |
September | 74.35 | 38.63 | 35.72 | 139.51 | 31.62 | 0.00 | 0.00 | 0.00 |
October | 101.02 | 68.30 | 32.72 | 161.84 | 48.83 | 0.00 | 0.00 | 0.00 |
November | 121.57 | 92.68 | 28.89 | 173.61 | 76.01 | 0.00 | 0.00 | 0.00 |
December | 120.48 | 90.44 | 30.04 | 163.82 | 90.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.59 | 45.99 | 33.60 | 126.26 | 49.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.66 | 2.33 | 28.51 | 76.12 | 12.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 121.57 | 92.68 | 37.69 | 173.61 | 90.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 136.71 | 69.59 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 128.86 | 63.02 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 107.58 | 57.03 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 81.63 | 37.09 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 63.86 | 22.97 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 67.29 | 12.27 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 68.23 | 10.38 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 81.83 | 14.49 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.83 | 26.79 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.32 | 41.16 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 145.22 | 63.64 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 137.13 | 75.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 105.72 | 41.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 63.86 | 10.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 145.22 | 75.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 136.71 | 69.59 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 128.86 | 63.02 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 107.58 | 57.03 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 81.63 | 37.09 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 63.86 | 22.97 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 67.29 | 12.27 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 68.23 | 10.38 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 81.83 | 14.49 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.83 | 26.79 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.32 | 41.16 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 145.22 | 63.64 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 137.13 | 75.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 105.72 | 41.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 63.86 | 10.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 145.22 | 75.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.63 | 89.12 | 28.51 | 163.85 | 82.25 | 0.00 | 0.00 | 0.00 |
February | 109.11 | 76.92 | 32.19 | 154.46 | 74.51 | 0.00 | 0.00 | 0.00 |
March | 88.68 | 51.13 | 37.55 | 129.05 | 67.49 | 0.00 | 0.00 | 0.00 |
April | 60.12 | 22.43 | 37.69 | 97.67 | 44.03 | 0.00 | 0.00 | 0.00 |
May | 42.49 | 5.95 | 36.54 | 76.08 | 27.41 | 0.00 | 0.00 | 0.00 |
June | 36.66 | 2.33 | 34.33 | 79.81 | 14.70 | 0.00 | 0.00 | 0.00 |
July | 37.37 | 3.46 | 33.90 | 81.10 | 12.40 | 0.00 | 0.00 | 0.00 |
August | 47.63 | 12.61 | 35.02 | 97.45 | 17.27 | 0.00 | 0.00 | 0.00 |
September | 74.35 | 38.63 | 35.72 | 139.45 | 31.83 | 0.00 | 0.00 | 0.00 |
October | 101.02 | 68.30 | 32.72 | 161.86 | 48.78 | 0.00 | 0.00 | 0.00 |
November | 121.57 | 92.68 | 28.89 | 173.90 | 75.31 | 0.00 | 0.00 | 0.00 |
December | 120.48 | 90.44 | 30.04 | 164.27 | 89.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.59 | 45.99 | 33.60 | 126.39 | 48.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.66 | 2.33 | 28.51 | 76.08 | 12.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 121.57 | 92.68 | 37.69 | 173.90 | 89.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 137.17 | 68.51 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 129.33 | 62.02 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 108.06 | 56.13 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 81.88 | 36.58 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.02 | 22.65 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 67.46 | 12.04 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 68.37 | 10.16 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 81.95 | 14.25 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.93 | 26.51 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.46 | 40.81 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 145.57 | 62.96 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 137.58 | 74.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 105.99 | 40.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.02 | 10.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 145.57 | 74.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 137.17 | 68.51 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 129.33 | 62.02 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 108.06 | 56.13 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 81.88 | 36.58 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.02 | 22.65 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 67.46 | 12.04 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 68.37 | 10.16 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 81.95 | 14.25 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.93 | 26.51 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.46 | 40.81 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 145.57 | 62.96 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 137.58 | 74.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 105.99 | 40.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.02 | 10.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 145.57 | 74.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.63 | 89.12 | 28.51 | 164.41 | 80.97 | 0.00 | 0.00 | 0.00 |
February | 109.11 | 76.92 | 32.19 | 155.01 | 73.33 | 0.00 | 0.00 | 0.00 |
March | 88.68 | 51.13 | 37.55 | 129.61 | 66.43 | 0.00 | 0.00 | 0.00 |
April | 60.12 | 22.43 | 37.69 | 97.96 | 43.43 | 0.00 | 0.00 | 0.00 |
May | 42.49 | 5.95 | 36.54 | 76.27 | 27.03 | 0.00 | 0.00 | 0.00 |
June | 36.66 | 2.33 | 34.33 | 80.01 | 14.42 | 0.00 | 0.00 | 0.00 |
July | 37.37 | 3.46 | 33.90 | 81.27 | 12.14 | 0.00 | 0.00 | 0.00 |
August | 47.63 | 12.61 | 35.02 | 97.59 | 16.99 | 0.00 | 0.00 | 0.00 |
September | 74.35 | 38.63 | 35.72 | 139.57 | 31.51 | 0.00 | 0.00 | 0.00 |
October | 101.02 | 68.30 | 32.72 | 162.03 | 48.36 | 0.00 | 0.00 | 0.00 |
November | 121.57 | 92.68 | 28.89 | 174.32 | 74.51 | 0.00 | 0.00 | 0.00 |
December | 120.48 | 90.44 | 30.04 | 164.81 | 87.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.59 | 45.99 | 33.60 | 126.72 | 47.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.66 | 2.33 | 28.51 | 76.27 | 12.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 121.57 | 92.68 | 37.69 | 174.32 | 87.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 138.47 | 66.17 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 130.62 | 59.76 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 109.34 | 53.97 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 82.55 | 35.10 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.24 | 21.54 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 67.66 | 11.26 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 68.43 | 9.41 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 81.98 | 13.35 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.94 | 25.40 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.89 | 39.66 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 146.52 | 61.23 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 138.84 | 72.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 106.63 | 38.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.24 | 9.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 146.52 | 72.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 138.47 | 66.17 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 130.62 | 59.76 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 109.34 | 53.97 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 82.55 | 35.10 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.24 | 21.54 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 67.66 | 11.26 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 68.43 | 9.41 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 81.98 | 13.35 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.94 | 25.40 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.89 | 39.66 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 146.52 | 61.23 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 138.84 | 72.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 106.63 | 38.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.24 | 9.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 146.52 | 72.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 138.47 | 66.17 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 130.62 | 59.76 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 109.34 | 53.97 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 82.55 | 35.10 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.24 | 21.54 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 67.66 | 11.26 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 68.43 | 9.41 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 81.98 | 13.35 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.94 | 25.40 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.89 | 39.66 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 146.52 | 61.23 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 138.84 | 72.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 106.63 | 38.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.24 | 9.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 146.52 | 72.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 138.47 | 66.17 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 130.62 | 59.76 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 109.34 | 53.97 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 82.55 | 35.10 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.24 | 21.54 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 67.66 | 11.26 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 68.43 | 9.41 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 81.98 | 13.35 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.94 | 25.40 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.89 | 39.66 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 146.52 | 61.23 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 138.84 | 72.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 106.63 | 38.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.24 | 9.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 146.52 | 72.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.63 | 89.12 | 28.51 | 165.89 | 78.24 | 0.00 | 0.00 | 0.00 |
February | 109.11 | 76.92 | 32.19 | 156.49 | 70.68 | 0.00 | 0.00 | 0.00 |
March | 88.68 | 51.13 | 37.55 | 131.09 | 63.90 | 0.00 | 0.00 | 0.00 |
April | 60.12 | 22.43 | 37.69 | 98.74 | 41.69 | 0.00 | 0.00 | 0.00 |
May | 42.49 | 5.95 | 36.54 | 76.53 | 25.71 | 0.00 | 0.00 | 0.00 |
June | 36.66 | 2.33 | 34.33 | 80.27 | 13.48 | 0.00 | 0.00 | 0.00 |
July | 37.37 | 3.46 | 33.90 | 81.35 | 11.25 | 0.00 | 0.00 | 0.00 |
August | 47.63 | 12.61 | 35.02 | 97.63 | 15.91 | 0.00 | 0.00 | 0.00 |
September | 74.35 | 38.63 | 35.72 | 139.58 | 30.20 | 0.00 | 0.00 | 0.00 |
October | 101.02 | 68.30 | 32.72 | 162.51 | 47.02 | 0.00 | 0.00 | 0.00 |
November | 121.57 | 92.68 | 28.89 | 175.41 | 72.49 | 0.00 | 0.00 | 0.00 |
December | 120.48 | 90.44 | 30.04 | 166.26 | 85.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.59 | 45.99 | 33.60 | 127.46 | 46.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.66 | 2.33 | 28.51 | 76.53 | 11.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 121.57 | 92.68 | 37.69 | 175.41 | 85.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.63 | 89.12 | 28.51 | 165.89 | 78.24 | 0.00 | 0.00 | 0.00 |
February | 109.11 | 76.92 | 32.19 | 156.49 | 70.68 | 0.00 | 0.00 | 0.00 |
March | 88.68 | 51.13 | 37.55 | 131.09 | 63.90 | 0.00 | 0.00 | 0.00 |
April | 60.12 | 22.43 | 37.69 | 98.74 | 41.69 | 0.00 | 0.00 | 0.00 |
May | 42.49 | 5.95 | 36.54 | 76.53 | 25.71 | 0.00 | 0.00 | 0.00 |
June | 36.66 | 2.33 | 34.33 | 80.27 | 13.48 | 0.00 | 0.00 | 0.00 |
July | 37.37 | 3.46 | 33.90 | 81.35 | 11.25 | 0.00 | 0.00 | 0.00 |
August | 47.63 | 12.61 | 35.02 | 97.63 | 15.91 | 0.00 | 0.00 | 0.00 |
September | 74.35 | 38.63 | 35.72 | 139.58 | 30.20 | 0.00 | 0.00 | 0.00 |
October | 101.02 | 68.30 | 32.72 | 162.51 | 47.02 | 0.00 | 0.00 | 0.00 |
November | 121.57 | 92.68 | 28.89 | 175.41 | 72.49 | 0.00 | 0.00 | 0.00 |
December | 120.48 | 90.44 | 30.04 | 166.26 | 85.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.59 | 45.99 | 33.60 | 127.46 | 46.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.66 | 2.33 | 28.51 | 76.53 | 11.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 121.57 | 92.68 | 37.69 | 175.41 | 85.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 138.23 | 66.04 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 130.42 | 59.63 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 109.18 | 53.78 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 82.52 | 34.85 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.44 | 21.22 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 68.15 | 10.94 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 68.83 | 9.11 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 82.25 | 13.01 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.99 | 25.05 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.75 | 39.44 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 146.33 | 61.10 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 138.63 | 72.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 106.65 | 38.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.44 | 9.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 146.33 | 72.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 138.23 | 66.04 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 130.42 | 59.63 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 109.18 | 53.78 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 82.52 | 34.85 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.44 | 21.22 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 68.15 | 10.94 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 68.83 | 9.11 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 82.25 | 13.01 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.99 | 25.05 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.75 | 39.44 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 146.33 | 61.10 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 138.63 | 72.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 106.65 | 38.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.44 | 9.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 146.33 | 72.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.63 | 89.12 | 28.51 | 165.68 | 78.06 | 0.00 | 0.00 | 0.00 |
February | 109.11 | 76.92 | 32.19 | 156.31 | 70.52 | 0.00 | 0.00 | 0.00 |
March | 88.68 | 51.13 | 37.55 | 130.95 | 63.66 | 0.00 | 0.00 | 0.00 |
April | 60.12 | 22.43 | 37.69 | 98.73 | 41.40 | 0.00 | 0.00 | 0.00 |
May | 42.49 | 5.95 | 36.54 | 76.76 | 25.35 | 0.00 | 0.00 | 0.00 |
June | 36.66 | 2.33 | 34.33 | 80.83 | 13.12 | 0.00 | 0.00 | 0.00 |
July | 37.37 | 3.46 | 33.90 | 81.80 | 10.88 | 0.00 | 0.00 | 0.00 |
August | 47.63 | 12.61 | 35.02 | 97.95 | 15.51 | 0.00 | 0.00 | 0.00 |
September | 74.35 | 38.63 | 35.72 | 139.66 | 29.79 | 0.00 | 0.00 | 0.00 |
October | 101.02 | 68.30 | 32.72 | 162.39 | 46.75 | 0.00 | 0.00 | 0.00 |
November | 121.57 | 92.68 | 28.89 | 175.24 | 72.32 | 0.00 | 0.00 | 0.00 |
December | 120.48 | 90.44 | 30.04 | 166.06 | 85.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.59 | 45.99 | 33.60 | 127.51 | 45.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.66 | 2.33 | 28.51 | 76.76 | 10.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 121.57 | 92.68 | 37.69 | 175.24 | 85.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 138.43 | 65.63 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 130.64 | 59.22 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 109.44 | 53.34 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 82.66 | 34.62 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.52 | 21.11 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 68.23 | 10.87 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 68.90 | 9.04 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 82.31 | 12.94 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 117.03 | 24.97 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.83 | 39.30 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 146.53 | 60.78 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 138.79 | 71.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 106.78 | 38.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.52 | 9.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 146.53 | 71.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 138.43 | 65.63 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 130.64 | 59.22 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 109.44 | 53.34 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 82.66 | 34.62 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.52 | 21.11 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 68.23 | 10.87 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 68.90 | 9.04 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 82.31 | 12.94 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 117.03 | 24.97 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.83 | 39.30 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 146.53 | 60.78 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 138.79 | 71.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 106.78 | 38.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.52 | 9.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 146.53 | 71.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.63 | 89.12 | 28.51 | 165.91 | 77.57 | 0.00 | 0.00 | 0.00 |
February | 109.11 | 76.92 | 32.19 | 156.57 | 70.03 | 0.00 | 0.00 | 0.00 |
March | 88.68 | 51.13 | 37.55 | 131.26 | 63.14 | 0.00 | 0.00 | 0.00 |
April | 60.12 | 22.43 | 37.69 | 98.90 | 41.12 | 0.00 | 0.00 | 0.00 |
May | 42.49 | 5.95 | 36.54 | 76.86 | 25.22 | 0.00 | 0.00 | 0.00 |
June | 36.66 | 2.33 | 34.33 | 80.92 | 13.03 | 0.00 | 0.00 | 0.00 |
July | 37.37 | 3.46 | 33.90 | 81.89 | 10.81 | 0.00 | 0.00 | 0.00 |
August | 47.63 | 12.61 | 35.02 | 98.02 | 15.44 | 0.00 | 0.00 | 0.00 |
September | 74.35 | 38.63 | 35.72 | 139.72 | 29.69 | 0.00 | 0.00 | 0.00 |
October | 101.02 | 68.30 | 32.72 | 162.48 | 46.58 | 0.00 | 0.00 | 0.00 |
November | 121.57 | 92.68 | 28.89 | 175.47 | 71.94 | 0.00 | 0.00 | 0.00 |
December | 120.48 | 90.44 | 30.04 | 166.26 | 84.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.59 | 45.99 | 33.60 | 127.66 | 45.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.66 | 2.33 | 28.51 | 76.86 | 10.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 121.57 | 92.68 | 37.69 | 175.47 | 84.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 138.88 | 64.55 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 131.18 | 58.08 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 110.05 | 52.15 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 82.98 | 33.99 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.64 | 20.87 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 68.24 | 10.82 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 68.86 | 9.03 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 82.26 | 12.95 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 117.02 | 24.95 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.97 | 39.00 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 146.98 | 59.96 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 139.21 | 70.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 107.03 | 38.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.64 | 9.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 146.98 | 70.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 138.88 | 64.55 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 131.18 | 58.08 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 110.05 | 52.15 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 82.98 | 33.99 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.64 | 20.87 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 68.24 | 10.82 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 68.86 | 9.03 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 82.26 | 12.95 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 117.02 | 24.95 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.97 | 39.00 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 146.98 | 59.96 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 139.21 | 70.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 107.03 | 38.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.64 | 9.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 146.98 | 70.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.63 | 89.12 | 28.51 | 166.45 | 76.29 | 0.00 | 0.00 | 0.00 |
February | 109.11 | 76.92 | 32.19 | 157.22 | 68.68 | 0.00 | 0.00 | 0.00 |
March | 88.68 | 51.13 | 37.55 | 131.99 | 61.74 | 0.00 | 0.00 | 0.00 |
April | 60.12 | 22.43 | 37.69 | 99.28 | 40.38 | 0.00 | 0.00 | 0.00 |
May | 42.49 | 5.95 | 36.54 | 77.01 | 24.93 | 0.00 | 0.00 | 0.00 |
June | 36.66 | 2.33 | 34.33 | 80.93 | 12.96 | 0.00 | 0.00 | 0.00 |
July | 37.37 | 3.46 | 33.90 | 81.84 | 10.80 | 0.00 | 0.00 | 0.00 |
August | 47.63 | 12.61 | 35.02 | 97.96 | 15.45 | 0.00 | 0.00 | 0.00 |
September | 74.35 | 38.63 | 35.72 | 139.70 | 29.67 | 0.00 | 0.00 | 0.00 |
October | 101.02 | 68.30 | 32.72 | 162.65 | 46.23 | 0.00 | 0.00 | 0.00 |
November | 121.57 | 92.68 | 28.89 | 176.01 | 70.97 | 0.00 | 0.00 | 0.00 |
December | 120.48 | 90.44 | 30.04 | 166.75 | 83.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.59 | 45.99 | 33.60 | 127.96 | 45.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.66 | 2.33 | 28.51 | 77.01 | 10.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 121.57 | 92.68 | 37.69 | 176.01 | 83.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 139.95 | 60.81 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 132.43 | 54.13 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 111.28 | 48.16 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 83.41 | 31.57 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.53 | 19.79 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 67.56 | 10.53 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 67.92 | 9.07 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 81.34 | 13.09 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.33 | 25.00 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 136.06 | 37.86 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 147.84 | 57.23 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 140.22 | 67.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 107.24 | 36.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.53 | 9.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 147.84 | 67.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 139.95 | 60.81 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 132.43 | 54.13 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 111.28 | 48.16 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 83.41 | 31.57 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.53 | 19.79 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 67.56 | 10.53 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 67.92 | 9.07 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 81.34 | 13.09 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.33 | 25.00 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 136.06 | 37.86 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 147.84 | 57.23 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 140.22 | 67.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 107.24 | 36.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.53 | 9.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 147.84 | 67.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.63 | 89.12 | 28.51 | 167.73 | 71.89 | 0.00 | 0.00 | 0.00 |
February | 109.11 | 76.92 | 32.19 | 158.71 | 64.04 | 0.00 | 0.00 | 0.00 |
March | 88.68 | 51.13 | 37.55 | 133.45 | 57.04 | 0.00 | 0.00 | 0.00 |
April | 60.12 | 22.43 | 37.69 | 99.79 | 37.53 | 0.00 | 0.00 | 0.00 |
May | 42.49 | 5.95 | 36.54 | 76.87 | 23.66 | 0.00 | 0.00 | 0.00 |
June | 36.66 | 2.33 | 34.33 | 80.12 | 12.64 | 0.00 | 0.00 | 0.00 |
July | 37.37 | 3.46 | 33.90 | 80.73 | 10.85 | 0.00 | 0.00 | 0.00 |
August | 47.63 | 12.61 | 35.02 | 96.86 | 15.62 | 0.00 | 0.00 | 0.00 |
September | 74.35 | 38.63 | 35.72 | 138.86 | 29.73 | 0.00 | 0.00 | 0.00 |
October | 101.02 | 68.30 | 32.72 | 162.75 | 44.89 | 0.00 | 0.00 | 0.00 |
November | 121.57 | 92.68 | 28.89 | 177.03 | 67.76 | 0.00 | 0.00 | 0.00 |
December | 120.48 | 90.44 | 30.04 | 167.96 | 80.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.59 | 45.99 | 33.60 | 128.20 | 42.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.66 | 2.33 | 28.51 | 76.87 | 10.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 121.57 | 92.68 | 37.69 | 177.03 | 80.01 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.369114E+09 | 0.182696E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.315104E+09 | 0.148191E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.292152E+09 | 0.147534E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.214166E+09 | 91063261.75 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.173208E+09 | 55954291.12 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.177954E+09 | 27155853.34 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.186376E+09 | 22932056.29 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.221719E+09 | 33633867.02 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.303521E+09 | 63466582.96 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.364022E+09 | 0.105714E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.378761E+09 | 0.161202E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.370177E+09 | 0.198432E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.336627E+10 | 0.123798E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.173208E+09 | 22932056.29 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.378761E+09 | 0.198432E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.369114E+09 | 0.182696E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.315104E+09 | 0.148191E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.292152E+09 | 0.147534E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.214166E+09 | 91063261.75 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.173208E+09 | 55954291.12 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.177954E+09 | 27155853.34 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.186376E+09 | 22932056.29 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.221719E+09 | 33633867.02 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.303521E+09 | 63466582.96 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.364022E+09 | 0.105714E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.378761E+09 | 0.161202E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.370177E+09 | 0.198432E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.336627E+10 | 0.123798E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.173208E+09 | 22932056.29 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.378761E+09 | 0.198432E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.369114E+09 | 0.182696E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.315104E+09 | 0.148191E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.292152E+09 | 0.147534E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.214166E+09 | 91063261.75 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.173208E+09 | 55954291.12 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.177954E+09 | 27155853.34 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.186376E+09 | 22932056.29 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.221719E+09 | 33633867.02 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.303521E+09 | 63466582.96 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.364022E+09 | 0.105714E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.378761E+09 | 0.161202E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.370177E+09 | 0.198432E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.336627E+10 | 0.123798E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.173208E+09 | 22932056.29 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.378761E+09 | 0.198432E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.369114E+09 | 0.182696E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.315104E+09 | 0.148191E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.292152E+09 | 0.147534E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.214166E+09 | 91063261.75 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.173208E+09 | 55954291.12 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.177954E+09 | 27155853.34 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.186376E+09 | 22932056.29 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.221719E+09 | 33633867.02 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.303521E+09 | 63466582.96 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.364022E+09 | 0.105714E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.378761E+09 | 0.161202E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.370177E+09 | 0.198432E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.336627E+10 | 0.123798E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.173208E+09 | 22932056.29 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.378761E+09 | 0.198432E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316787E+09 | 0.239999E+09 | 76787787.94 | 0.444658E+09 | 0.217228E+09 |
February | 0.265418E+09 | 0.187115E+09 | 78302345.55 | 0.379591E+09 | 0.176260E+09 |
March | 0.238818E+09 | 0.137702E+09 | 0.101116E+09 | 0.352185E+09 | 0.175651E+09 |
April | 0.156695E+09 | 58466780.93 | 98228034.59 | 0.257548E+09 | 0.108795E+09 |
May | 0.114426E+09 | 16015840.86 | 98409804.77 | 0.207410E+09 | 67227446.58 |
June | 95535986.37 | 6061786.34 | 89474200.03 | 0.212113E+09 | 32724957.64 |
July | 0.100635E+09 | 9329009.15 | 91305690.16 | 0.222598E+09 | 27587623.11 |
August | 0.128281E+09 | 33956884.46 | 94324609.58 | 0.265344E+09 | 40360371.90 |
September | 0.193774E+09 | 0.100672E+09 | 93101553.68 | 0.364218E+09 | 75969519.14 |
October | 0.272058E+09 | 0.183929E+09 | 88128496.15 | 0.437668E+09 | 0.126093E+09 |
November | 0.316835E+09 | 0.241548E+09 | 75287263.97 | 0.455902E+09 | 0.191946E+09 |
December | 0.324462E+09 | 0.243556E+09 | 80906164.45 | 0.445718E+09 | 0.236136E+09 |
Annual Sum or Average | 0.252372E+10 | 0.145835E+10 | 0.106537E+10 | 0.404496E+10 | 0.147598E+10 |
Minimum of Months | 95535986.37 | 6061786.34 | 75287263.97 | 0.207410E+09 | 27587623.11 |
Maximum of Months | 0.324462E+09 | 0.243556E+09 | 0.101116E+09 | 0.455902E+09 | 0.236136E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316787E+09 | 0.239999E+09 | 76787787.94 | 0.444658E+09 | 0.217228E+09 |
February | 0.265418E+09 | 0.187115E+09 | 78302345.55 | 0.379591E+09 | 0.176260E+09 |
March | 0.238818E+09 | 0.137702E+09 | 0.101116E+09 | 0.352185E+09 | 0.175651E+09 |
April | 0.156695E+09 | 58466780.93 | 98228034.59 | 0.257548E+09 | 0.108795E+09 |
May | 0.114426E+09 | 16015840.86 | 98409804.77 | 0.207410E+09 | 67227446.58 |
June | 95535986.37 | 6061786.34 | 89474200.03 | 0.212113E+09 | 32724957.64 |
July | 0.100635E+09 | 9329009.15 | 91305690.16 | 0.222598E+09 | 27587623.11 |
August | 0.128281E+09 | 33956884.46 | 94324609.58 | 0.265344E+09 | 40360371.90 |
September | 0.193774E+09 | 0.100672E+09 | 93101553.68 | 0.364218E+09 | 75969519.14 |
October | 0.272058E+09 | 0.183929E+09 | 88128496.15 | 0.437668E+09 | 0.126093E+09 |
November | 0.316835E+09 | 0.241548E+09 | 75287263.97 | 0.455902E+09 | 0.191946E+09 |
December | 0.324462E+09 | 0.243556E+09 | 80906164.45 | 0.445718E+09 | 0.236136E+09 |
Annual Sum or Average | 0.252372E+10 | 0.145835E+10 | 0.106537E+10 | 0.404496E+10 | 0.147598E+10 |
Minimum of Months | 95535986.37 | 6061786.34 | 75287263.97 | 0.207410E+09 | 27587623.11 |
Maximum of Months | 0.324462E+09 | 0.243556E+09 | 0.101116E+09 | 0.455902E+09 | 0.236136E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.363555E+09 | 0.196004E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.309798E+09 | 0.158900E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.286476E+09 | 0.157208E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.211963E+09 | 94157697.52 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.172863E+09 | 56912425.77 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.178824E+09 | 27618424.59 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.187494E+09 | 23165449.77 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.222703E+09 | 33680780.89 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.303830E+09 | 62985845.05 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.362934E+09 | 0.106647E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.374865E+09 | 0.168083E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.364840E+09 | 0.210774E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.334014E+10 | 0.129614E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.172863E+09 | 23165449.77 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.374865E+09 | 0.210774E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.363555E+09 | 0.196004E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.309798E+09 | 0.158900E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.286476E+09 | 0.157208E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.211963E+09 | 94157697.52 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.172863E+09 | 56912425.77 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.178824E+09 | 27618424.59 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.187494E+09 | 23165449.77 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.222703E+09 | 33680780.89 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.303830E+09 | 62985845.05 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.362934E+09 | 0.106647E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.374865E+09 | 0.168083E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.364840E+09 | 0.210774E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.334014E+10 | 0.129614E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.172863E+09 | 23165449.77 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.374865E+09 | 0.210774E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316787E+09 | 0.239999E+09 | 76787787.94 | 0.438170E+09 | 0.232840E+09 |
February | 0.265418E+09 | 0.187115E+09 | 78302345.55 | 0.373379E+09 | 0.188839E+09 |
March | 0.238818E+09 | 0.137702E+09 | 0.101116E+09 | 0.345547E+09 | 0.187034E+09 |
April | 0.156695E+09 | 58466780.93 | 98228034.59 | 0.254969E+09 | 0.112455E+09 |
May | 0.114426E+09 | 16015840.86 | 98409804.77 | 0.206978E+09 | 68375541.85 |
June | 95535986.37 | 6061786.34 | 89474200.03 | 0.213091E+09 | 33288706.13 |
July | 0.100635E+09 | 9329009.15 | 91305690.16 | 0.223906E+09 | 27870014.75 |
August | 0.128281E+09 | 33956884.46 | 94324609.58 | 0.266525E+09 | 40419509.45 |
September | 0.193774E+09 | 0.100672E+09 | 93101553.68 | 0.364650E+09 | 75388631.84 |
October | 0.272058E+09 | 0.183929E+09 | 88128496.15 | 0.436484E+09 | 0.127170E+09 |
November | 0.316835E+09 | 0.241548E+09 | 75287263.97 | 0.451385E+09 | 0.200013E+09 |
December | 0.324462E+09 | 0.243556E+09 | 80906164.45 | 0.439468E+09 | 0.250630E+09 |
Annual Sum or Average | 0.252372E+10 | 0.145835E+10 | 0.106537E+10 | 0.401455E+10 | 0.154432E+10 |
Minimum of Months | 95535986.37 | 6061786.34 | 75287263.97 | 0.206978E+09 | 27870014.75 |
Maximum of Months | 0.324462E+09 | 0.243556E+09 | 0.101116E+09 | 0.451385E+09 | 0.250630E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.365074E+09 | 0.189611E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.310877E+09 | 0.154846E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.287329E+09 | 0.154752E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.211422E+09 | 96590708.54 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.171149E+09 | 61279951.23 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.174696E+09 | 31306108.14 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.183076E+09 | 27254054.44 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.219430E+09 | 38249852.64 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.302942E+09 | 68974411.90 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.362409E+09 | 0.110359E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.375783E+09 | 0.166478E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.366287E+09 | 0.204701E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.333048E+10 | 0.130440E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.171149E+09 | 27254054.44 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.375783E+09 | 0.204701E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.365074E+09 | 0.189611E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.310877E+09 | 0.154846E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.287329E+09 | 0.154752E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.211422E+09 | 96590708.54 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.171149E+09 | 61279951.23 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.174696E+09 | 31306108.14 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.183076E+09 | 27254054.44 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.219430E+09 | 38249852.64 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.302942E+09 | 68974411.90 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.362409E+09 | 0.110359E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.375783E+09 | 0.166478E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.366287E+09 | 0.204701E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.333048E+10 | 0.130440E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.171149E+09 | 27254054.44 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.375783E+09 | 0.204701E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.315056E+09 | 0.238688E+09 | 76368182.54 | 0.437577E+09 | 0.224089E+09 |
February | 0.263967E+09 | 0.186093E+09 | 77874463.88 | 0.372622E+09 | 0.183071E+09 |
March | 0.237513E+09 | 0.136950E+09 | 0.100564E+09 | 0.344671E+09 | 0.183132E+09 |
April | 0.155839E+09 | 58147290.33 | 97691269.37 | 0.252953E+09 | 0.114669E+09 |
May | 0.113800E+09 | 15928322.61 | 97872046.28 | 0.203886E+09 | 73125600.02 |
June | 95013931.80 | 6028661.83 | 88985269.98 | 0.207199E+09 | 37492620.97 |
July | 0.100085E+09 | 9278030.96 | 90806751.97 | 0.217602E+09 | 32553916.80 |
August | 0.127581E+09 | 33771327.72 | 93809174.56 | 0.261307E+09 | 45588454.72 |
September | 0.192715E+09 | 0.100122E+09 | 92592802.02 | 0.361611E+09 | 81963698.54 |
October | 0.270571E+09 | 0.182924E+09 | 87646919.67 | 0.433482E+09 | 0.130782E+09 |
November | 0.315104E+09 | 0.240228E+09 | 74875858.16 | 0.450006E+09 | 0.197018E+09 |
December | 0.322689E+09 | 0.242225E+09 | 80464054.26 | 0.438787E+09 | 0.242150E+09 |
Annual Sum or Average | 0.250993E+10 | 0.145038E+10 | 0.105955E+10 | 0.398170E+10 | 0.154564E+10 |
Minimum of Months | 95013931.80 | 6028661.83 | 74875858.16 | 0.203886E+09 | 32553916.80 |
Maximum of Months | 0.322689E+09 | 0.242225E+09 | 0.100564E+09 | 0.450006E+09 | 0.242150E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.366153E+09 | 0.186389E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.311748E+09 | 0.152449E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.288152E+09 | 0.152743E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.211596E+09 | 96131980.00 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.171053E+09 | 61519718.50 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.174404E+09 | 31811087.59 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.182743E+09 | 27797342.27 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.219178E+09 | 38814692.56 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.302819E+09 | 69439725.61 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.362437E+09 | 0.110251E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.376398E+09 | 0.164948E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.367296E+09 | 0.201755E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.333398E+10 | 0.129405E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.171053E+09 | 27797342.27 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.376398E+09 | 0.201755E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.366153E+09 | 0.186389E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.311748E+09 | 0.152449E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.288152E+09 | 0.152743E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.211596E+09 | 96131980.00 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.171053E+09 | 61519718.50 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.174404E+09 | 31811087.59 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.182743E+09 | 27797342.27 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.219178E+09 | 38814692.56 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.302819E+09 | 69439725.61 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.362437E+09 | 0.110251E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.376398E+09 | 0.164948E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.367296E+09 | 0.201755E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.333398E+10 | 0.129405E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.171053E+09 | 27797342.27 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.376398E+09 | 0.201755E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.315056E+09 | 0.238688E+09 | 76368182.54 | 0.438862E+09 | 0.220285E+09 |
February | 0.263967E+09 | 0.186093E+09 | 77874463.88 | 0.373659E+09 | 0.180245E+09 |
March | 0.237513E+09 | 0.136950E+09 | 0.100564E+09 | 0.345649E+09 | 0.180761E+09 |
April | 0.155839E+09 | 58147290.33 | 97691269.37 | 0.253161E+09 | 0.114128E+09 |
May | 0.113800E+09 | 15928322.61 | 97872046.28 | 0.203774E+09 | 73410146.10 |
June | 95013931.80 | 6028661.83 | 88985269.98 | 0.206855E+09 | 38092063.05 |
July | 0.100085E+09 | 9278030.96 | 90806751.97 | 0.217210E+09 | 33199985.37 |
August | 0.127581E+09 | 33771327.72 | 93809174.56 | 0.261010E+09 | 46259287.53 |
September | 0.192715E+09 | 0.100122E+09 | 92592802.02 | 0.361463E+09 | 82513296.39 |
October | 0.270571E+09 | 0.182924E+09 | 87646919.67 | 0.433515E+09 | 0.130654E+09 |
November | 0.315104E+09 | 0.240228E+09 | 74875858.16 | 0.450740E+09 | 0.195211E+09 |
December | 0.322689E+09 | 0.242225E+09 | 80464054.26 | 0.439991E+09 | 0.238670E+09 |
Annual Sum or Average | 0.250993E+10 | 0.145038E+10 | 0.105955E+10 | 0.398589E+10 | 0.153343E+10 |
Minimum of Months | 95013931.80 | 6028661.83 | 74875858.16 | 0.203774E+09 | 33199985.37 |
Maximum of Months | 0.322689E+09 | 0.242225E+09 | 0.100564E+09 | 0.450740E+09 | 0.238670E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.367402E+09 | 0.183488E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.312883E+09 | 0.150036E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.289422E+09 | 0.150340E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.212223E+09 | 94809661.94 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.171481E+09 | 60664154.14 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.174859E+09 | 31206056.06 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.183131E+09 | 27217578.77 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.219503E+09 | 38170241.14 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.303079E+09 | 68714884.35 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.362827E+09 | 0.109300E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.377310E+09 | 0.163182E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.368497E+09 | 0.199105E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.334262E+10 | 0.127623E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.171481E+09 | 27217578.77 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.377310E+09 | 0.199105E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.367402E+09 | 0.183488E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.312883E+09 | 0.150036E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.289422E+09 | 0.150340E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.212223E+09 | 94809661.94 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.171481E+09 | 60664154.14 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.174859E+09 | 31206056.06 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.183131E+09 | 27217578.77 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.219503E+09 | 38170241.14 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.303079E+09 | 68714884.35 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.362827E+09 | 0.109300E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.377310E+09 | 0.163182E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.368497E+09 | 0.199105E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.334262E+10 | 0.127623E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.171481E+09 | 27217578.77 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.377310E+09 | 0.199105E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.315056E+09 | 0.238688E+09 | 76368182.54 | 0.440351E+09 | 0.216863E+09 |
February | 0.263967E+09 | 0.186093E+09 | 77874463.88 | 0.375011E+09 | 0.177404E+09 |
March | 0.237513E+09 | 0.136950E+09 | 0.100564E+09 | 0.347160E+09 | 0.177930E+09 |
April | 0.155839E+09 | 58147290.33 | 97691269.37 | 0.253910E+09 | 0.112572E+09 |
May | 0.113800E+09 | 15928322.61 | 97872046.28 | 0.204282E+09 | 72401997.94 |
June | 95013931.80 | 6028661.83 | 88985269.98 | 0.207392E+09 | 37375604.07 |
July | 0.100085E+09 | 9278030.96 | 90806751.97 | 0.217669E+09 | 32514299.33 |
August | 0.127581E+09 | 33771327.72 | 93809174.56 | 0.261395E+09 | 45497784.11 |
September | 0.192715E+09 | 0.100122E+09 | 92592802.02 | 0.361776E+09 | 81661503.29 |
October | 0.270571E+09 | 0.182924E+09 | 87646919.67 | 0.433984E+09 | 0.129535E+09 |
November | 0.315104E+09 | 0.240228E+09 | 74875858.16 | 0.451830E+09 | 0.193130E+09 |
December | 0.322689E+09 | 0.242225E+09 | 80464054.26 | 0.441425E+09 | 0.235542E+09 |
Annual Sum or Average | 0.250993E+10 | 0.145038E+10 | 0.105955E+10 | 0.399618E+10 | 0.151243E+10 |
Minimum of Months | 95013931.80 | 6028661.83 | 74875858.16 | 0.204282E+09 | 32514299.33 |
Maximum of Months | 0.322689E+09 | 0.242225E+09 | 0.100564E+09 | 0.451830E+09 | 0.235542E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.370869E+09 | 0.177221E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.315996E+09 | 0.144560E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.292864E+09 | 0.144543E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.213971E+09 | 90983251.02 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.172063E+09 | 57681684.84 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.175383E+09 | 29175683.89 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.183284E+09 | 25214473.02 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.219582E+09 | 35746411.85 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.303112E+09 | 65847647.20 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.363979E+09 | 0.106219E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.379785E+09 | 0.158703E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.371873E+09 | 0.193259E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.336276E+10 | 0.122915E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.172063E+09 | 25214473.02 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.379785E+09 | 0.193259E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.370869E+09 | 0.177221E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.315996E+09 | 0.144560E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.292864E+09 | 0.144543E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.213971E+09 | 90983251.02 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.172063E+09 | 57681684.84 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.175383E+09 | 29175683.89 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.183284E+09 | 25214473.02 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.219582E+09 | 35746411.85 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.303112E+09 | 65847647.20 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.363979E+09 | 0.106219E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.379785E+09 | 0.158703E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.371873E+09 | 0.193259E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.336276E+10 | 0.122915E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.172063E+09 | 25214473.02 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.379785E+09 | 0.193259E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.370869E+09 | 0.177221E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.315996E+09 | 0.144560E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.292864E+09 | 0.144543E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.213971E+09 | 90983251.02 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.172063E+09 | 57681684.84 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.175383E+09 | 29175683.89 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.183284E+09 | 25214473.02 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.219582E+09 | 35746411.85 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.303112E+09 | 65847647.20 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.363979E+09 | 0.106219E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.379785E+09 | 0.158703E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.371873E+09 | 0.193259E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.336276E+10 | 0.122915E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.172063E+09 | 25214473.02 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.379785E+09 | 0.193259E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.370869E+09 | 0.177221E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.315996E+09 | 0.144560E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.292864E+09 | 0.144543E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.213971E+09 | 90983251.02 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.172063E+09 | 57681684.84 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.175383E+09 | 29175683.89 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.183284E+09 | 25214473.02 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.219582E+09 | 35746411.85 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.303112E+09 | 65847647.20 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.363979E+09 | 0.106219E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.379785E+09 | 0.158703E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.371873E+09 | 0.193259E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.336276E+10 | 0.122915E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.172063E+09 | 25214473.02 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.379785E+09 | 0.193259E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.315056E+09 | 0.238688E+09 | 76368182.54 | 0.444331E+09 | 0.209546E+09 |
February | 0.263967E+09 | 0.186093E+09 | 77874463.88 | 0.378592E+09 | 0.171001E+09 |
March | 0.237513E+09 | 0.136950E+09 | 0.100564E+09 | 0.351124E+09 | 0.171147E+09 |
April | 0.155839E+09 | 58147290.33 | 97691269.37 | 0.255940E+09 | 0.108065E+09 |
May | 0.113800E+09 | 15928322.61 | 97872046.28 | 0.204988E+09 | 68861019.96 |
June | 95013931.80 | 6028661.83 | 88985269.98 | 0.208061E+09 | 34938160.69 |
July | 0.100085E+09 | 9278030.96 | 90806751.97 | 0.217878E+09 | 30121465.31 |
August | 0.127581E+09 | 33771327.72 | 93809174.56 | 0.261492E+09 | 42614573.69 |
September | 0.192715E+09 | 0.100122E+09 | 92592802.02 | 0.361794E+09 | 78287198.04 |
October | 0.270571E+09 | 0.182924E+09 | 87646919.67 | 0.435265E+09 | 0.125929E+09 |
November | 0.315104E+09 | 0.240228E+09 | 74875858.16 | 0.454650E+09 | 0.187896E+09 |
December | 0.322689E+09 | 0.242225E+09 | 80464054.26 | 0.445318E+09 | 0.228700E+09 |
Annual Sum or Average | 0.250993E+10 | 0.145038E+10 | 0.105955E+10 | 0.401944E+10 | 0.145711E+10 |
Minimum of Months | 95013931.80 | 6028661.83 | 74875858.16 | 0.204988E+09 | 30121465.31 |
Maximum of Months | 0.322689E+09 | 0.242225E+09 | 0.100564E+09 | 0.454650E+09 | 0.228700E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.315056E+09 | 0.238688E+09 | 76368182.54 | 0.444331E+09 | 0.209546E+09 |
February | 0.263967E+09 | 0.186093E+09 | 77874463.88 | 0.378592E+09 | 0.171001E+09 |
March | 0.237513E+09 | 0.136950E+09 | 0.100564E+09 | 0.351124E+09 | 0.171147E+09 |
April | 0.155839E+09 | 58147290.33 | 97691269.37 | 0.255940E+09 | 0.108065E+09 |
May | 0.113800E+09 | 15928322.61 | 97872046.28 | 0.204988E+09 | 68861019.96 |
June | 95013931.80 | 6028661.83 | 88985269.98 | 0.208061E+09 | 34938160.69 |
July | 0.100085E+09 | 9278030.96 | 90806751.97 | 0.217878E+09 | 30121465.31 |
August | 0.127581E+09 | 33771327.72 | 93809174.56 | 0.261492E+09 | 42614573.69 |
September | 0.192715E+09 | 0.100122E+09 | 92592802.02 | 0.361794E+09 | 78287198.04 |
October | 0.270571E+09 | 0.182924E+09 | 87646919.67 | 0.435265E+09 | 0.125929E+09 |
November | 0.315104E+09 | 0.240228E+09 | 74875858.16 | 0.454650E+09 | 0.187896E+09 |
December | 0.322689E+09 | 0.242225E+09 | 80464054.26 | 0.445318E+09 | 0.228700E+09 |
Annual Sum or Average | 0.250993E+10 | 0.145038E+10 | 0.105955E+10 | 0.401944E+10 | 0.145711E+10 |
Minimum of Months | 95013931.80 | 6028661.83 | 74875858.16 | 0.204988E+09 | 30121465.31 |
Maximum of Months | 0.322689E+09 | 0.242225E+09 | 0.100564E+09 | 0.454650E+09 | 0.228700E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.370238E+09 | 0.176886E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.315507E+09 | 0.144265E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.292425E+09 | 0.144043E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.213887E+09 | 90340929.96 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.172587E+09 | 56846310.81 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.176649E+09 | 28367805.24 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.184342E+09 | 24387728.59 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.220306E+09 | 34842372.81 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.303228E+09 | 64929151.07 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.363596E+09 | 0.105633E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.379295E+09 | 0.158381E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.371304E+09 | 0.193088E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.336336E+10 | 0.122201E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.172587E+09 | 24387728.59 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.379295E+09 | 0.193088E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.370238E+09 | 0.176886E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.315507E+09 | 0.144265E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.292425E+09 | 0.144043E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.213887E+09 | 90340929.96 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.172587E+09 | 56846310.81 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.176649E+09 | 28367805.24 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.184342E+09 | 24387728.59 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.220306E+09 | 34842372.81 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.303228E+09 | 64929151.07 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.363596E+09 | 0.105633E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.379295E+09 | 0.158381E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.371304E+09 | 0.193088E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.336336E+10 | 0.122201E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.172587E+09 | 24387728.59 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.379295E+09 | 0.193088E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.315056E+09 | 0.238688E+09 | 76368182.54 | 0.443746E+09 | 0.209074E+09 |
February | 0.263967E+09 | 0.186093E+09 | 77874463.88 | 0.378144E+09 | 0.170599E+09 |
March | 0.237513E+09 | 0.136950E+09 | 0.100564E+09 | 0.350745E+09 | 0.170512E+09 |
April | 0.155839E+09 | 58147290.33 | 97691269.37 | 0.255908E+09 | 0.107305E+09 |
May | 0.113800E+09 | 15928322.61 | 97872046.28 | 0.205602E+09 | 67893799.10 |
June | 95013931.80 | 6028661.83 | 88985269.98 | 0.209499E+09 | 33997092.16 |
July | 0.100085E+09 | 9278030.96 | 90806751.97 | 0.219104E+09 | 29152746.62 |
August | 0.127581E+09 | 33771327.72 | 93809174.56 | 0.262357E+09 | 41554186.03 |
September | 0.192715E+09 | 0.100122E+09 | 92592802.02 | 0.362000E+09 | 77203338.26 |
October | 0.270571E+09 | 0.182924E+09 | 87646919.67 | 0.434935E+09 | 0.125211E+09 |
November | 0.315104E+09 | 0.240228E+09 | 74875858.16 | 0.454214E+09 | 0.187458E+09 |
December | 0.322689E+09 | 0.242225E+09 | 80464054.26 | 0.444783E+09 | 0.228428E+09 |
Annual Sum or Average | 0.250993E+10 | 0.145038E+10 | 0.105955E+10 | 0.402104E+10 | 0.144839E+10 |
Minimum of Months | 95013931.80 | 6028661.83 | 74875858.16 | 0.205602E+09 | 29152746.62 |
Maximum of Months | 0.322689E+09 | 0.242225E+09 | 0.100564E+09 | 0.454214E+09 | 0.228428E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.370758E+09 | 0.175776E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.316034E+09 | 0.143257E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.293119E+09 | 0.142853E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.214257E+09 | 89735475.37 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.172809E+09 | 56550399.22 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.176857E+09 | 28185074.93 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.184533E+09 | 24213824.66 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.220460E+09 | 34664166.04 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.303354E+09 | 64713781.19 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.363808E+09 | 0.105253E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.379807E+09 | 0.157532E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.371746E+09 | 0.192224E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.336754E+10 | 0.121496E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.172809E+09 | 24213824.66 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.379807E+09 | 0.192224E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.370758E+09 | 0.175776E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.316034E+09 | 0.143257E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.293119E+09 | 0.142853E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.214257E+09 | 89735475.37 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.172809E+09 | 56550399.22 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.176857E+09 | 28185074.93 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.184533E+09 | 24213824.66 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.220460E+09 | 34664166.04 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.303354E+09 | 64713781.19 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.363808E+09 | 0.105253E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.379807E+09 | 0.157532E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.371746E+09 | 0.192224E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.336754E+10 | 0.121496E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.172809E+09 | 24213824.66 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.379807E+09 | 0.192224E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.315056E+09 | 0.238688E+09 | 76368182.54 | 0.444365E+09 | 0.207761E+09 |
February | 0.263967E+09 | 0.186093E+09 | 77874463.88 | 0.378772E+09 | 0.169409E+09 |
March | 0.237513E+09 | 0.136950E+09 | 0.100564E+09 | 0.351571E+09 | 0.169107E+09 |
April | 0.155839E+09 | 58147290.33 | 97691269.37 | 0.256349E+09 | 0.106590E+09 |
May | 0.113800E+09 | 15928322.61 | 97872046.28 | 0.205867E+09 | 67543859.87 |
June | 95013931.80 | 6028661.83 | 88985269.98 | 0.209747E+09 | 33780170.50 |
July | 0.100085E+09 | 9278030.96 | 90806751.97 | 0.219332E+09 | 28946962.79 |
August | 0.127581E+09 | 33771327.72 | 93809174.56 | 0.262542E+09 | 41342570.14 |
September | 0.192715E+09 | 0.100122E+09 | 92592802.02 | 0.362152E+09 | 76948628.95 |
October | 0.270571E+09 | 0.182924E+09 | 87646919.67 | 0.435189E+09 | 0.124761E+09 |
November | 0.315104E+09 | 0.240228E+09 | 74875858.16 | 0.454824E+09 | 0.186457E+09 |
December | 0.322689E+09 | 0.242225E+09 | 80464054.26 | 0.445311E+09 | 0.227407E+09 |
Annual Sum or Average | 0.250993E+10 | 0.145038E+10 | 0.105955E+10 | 0.402602E+10 | 0.144006E+10 |
Minimum of Months | 95013931.80 | 6028661.83 | 74875858.16 | 0.205867E+09 | 28946962.79 |
Maximum of Months | 0.322689E+09 | 0.242225E+09 | 0.100564E+09 | 0.454824E+09 | 0.227407E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.371975E+09 | 0.172886E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.317356E+09 | 0.140499E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.294756E+09 | 0.139678E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.215092E+09 | 88092529.32 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.173142E+09 | 55903892.34 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.176890E+09 | 28033002.00 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.184423E+09 | 24192403.44 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.220317E+09 | 34696864.32 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.303312E+09 | 64672542.56 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.364185E+09 | 0.104451E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.380981E+09 | 0.155408E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.372851E+09 | 0.189845E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.337528E+10 | 0.119836E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.173142E+09 | 24192403.44 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.380981E+09 | 0.189845E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.371975E+09 | 0.172886E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.317356E+09 | 0.140499E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.294756E+09 | 0.139678E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.215092E+09 | 88092529.32 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.173142E+09 | 55903892.34 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.176890E+09 | 28033002.00 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.184423E+09 | 24192403.44 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.220317E+09 | 34696864.32 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.303312E+09 | 64672542.56 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.364185E+09 | 0.104451E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.380981E+09 | 0.155408E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.372851E+09 | 0.189845E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.337528E+10 | 0.119836E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.173142E+09 | 24192403.44 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.380981E+09 | 0.189845E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.315056E+09 | 0.238688E+09 | 76368182.54 | 0.445819E+09 | 0.204348E+09 |
February | 0.263967E+09 | 0.186093E+09 | 77874463.88 | 0.380346E+09 | 0.166158E+09 |
March | 0.237513E+09 | 0.136950E+09 | 0.100564E+09 | 0.353519E+09 | 0.165369E+09 |
April | 0.155839E+09 | 58147290.33 | 97691269.37 | 0.257341E+09 | 0.104656E+09 |
May | 0.113800E+09 | 15928322.61 | 97872046.28 | 0.206263E+09 | 66783932.73 |
June | 95013931.80 | 6028661.83 | 88985269.98 | 0.209782E+09 | 33604335.32 |
July | 0.100085E+09 | 9278030.96 | 90806751.97 | 0.219198E+09 | 28925283.98 |
August | 0.127581E+09 | 33771327.72 | 93809174.56 | 0.262371E+09 | 41385762.51 |
September | 0.192715E+09 | 0.100122E+09 | 92592802.02 | 0.362101E+09 | 76903819.12 |
October | 0.270571E+09 | 0.182924E+09 | 87646919.67 | 0.435639E+09 | 0.123820E+09 |
November | 0.315104E+09 | 0.240228E+09 | 74875858.16 | 0.456219E+09 | 0.183949E+09 |
December | 0.322689E+09 | 0.242225E+09 | 80464054.26 | 0.446628E+09 | 0.224594E+09 |
Annual Sum or Average | 0.250993E+10 | 0.145038E+10 | 0.105955E+10 | 0.403523E+10 | 0.142050E+10 |
Minimum of Months | 95013931.80 | 6028661.83 | 74875858.16 | 0.206263E+09 | 28925283.98 |
Maximum of Months | 0.322689E+09 | 0.242225E+09 | 0.100564E+09 | 0.456219E+09 | 0.224594E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.374840E+09 | 0.162876E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.320379E+09 | 0.130956E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.298041E+09 | 0.128979E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.216199E+09 | 81831753.32 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.172828E+09 | 53000365.07 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.175118E+09 | 27306643.45 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.181923E+09 | 24283565.15 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.217855E+09 | 35054691.45 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.301515E+09 | 64795419.81 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.364412E+09 | 0.101401E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.383196E+09 | 0.148341E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.375564E+09 | 0.181115E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.338187E+10 | 0.113994E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.172828E+09 | 24283565.15 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.383196E+09 | 0.181115E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.374840E+09 | 0.162876E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.320379E+09 | 0.130956E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.298041E+09 | 0.128979E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.216199E+09 | 81831753.32 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.172828E+09 | 53000365.07 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.175118E+09 | 27306643.45 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.181923E+09 | 24283565.15 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.217855E+09 | 35054691.45 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.301515E+09 | 64795419.81 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.364412E+09 | 0.101401E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.383196E+09 | 0.148341E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.375564E+09 | 0.181115E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.338187E+10 | 0.113994E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.172828E+09 | 24283565.15 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.383196E+09 | 0.181115E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.315056E+09 | 0.238688E+09 | 76368182.54 | 0.449248E+09 | 0.192541E+09 |
February | 0.263967E+09 | 0.186093E+09 | 77874463.88 | 0.383959E+09 | 0.154926E+09 |
March | 0.237513E+09 | 0.136950E+09 | 0.100564E+09 | 0.357443E+09 | 0.152784E+09 |
April | 0.155839E+09 | 58147290.33 | 97691269.37 | 0.258658E+09 | 97288085.65 |
May | 0.113800E+09 | 15928322.61 | 97872046.28 | 0.205880E+09 | 63370287.13 |
June | 95013931.80 | 6028661.83 | 88985269.98 | 0.207662E+09 | 32756591.38 |
July | 0.100085E+09 | 9278030.96 | 90806751.97 | 0.216215E+09 | 29048720.88 |
August | 0.127581E+09 | 33771327.72 | 93809174.56 | 0.259424E+09 | 41827551.82 |
September | 0.192715E+09 | 0.100122E+09 | 92592802.02 | 0.359935E+09 | 77060109.79 |
October | 0.270571E+09 | 0.182924E+09 | 87646919.67 | 0.435899E+09 | 0.120237E+09 |
November | 0.315104E+09 | 0.240228E+09 | 74875858.16 | 0.458856E+09 | 0.175623E+09 |
December | 0.322689E+09 | 0.242225E+09 | 80464054.26 | 0.449874E+09 | 0.214289E+09 |
Annual Sum or Average | 0.250993E+10 | 0.145038E+10 | 0.105955E+10 | 0.404305E+10 | 0.135175E+10 |
Minimum of Months | 95013931.80 | 6028661.83 | 74875858.16 | 0.205880E+09 | 29048720.88 |
Maximum of Months | 0.322689E+09 | 0.242225E+09 | 0.100564E+09 | 0.458856E+09 | 0.214289E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 883.28 | 435.05 | 630.09 | 477.36 | 152.73 | 0.00 | 0.00 |
February | 834.82 | 390.74 | 584.48 | 412.05 | 172.43 | 0.00 | 0.00 |
March | 699.29 | 351.49 | 475.01 | 273.89 | 201.12 | 0.00 | 0.00 |
April | 529.23 | 224.48 | 322.06 | 120.17 | 201.89 | 0.00 | 0.00 |
May | 413.55 | 133.76 | 227.59 | 31.86 | 195.74 | 0.00 | 0.00 |
June | 438.29 | 67.16 | 196.36 | 12.46 | 183.90 | 0.00 | 0.00 |
July | 444.56 | 54.85 | 200.16 | 18.56 | 181.61 | 0.00 | 0.00 |
August | 529.26 | 80.37 | 255.15 | 67.54 | 187.61 | 0.00 | 0.00 |
September | 749.43 | 156.56 | 398.26 | 206.91 | 191.35 | 0.00 | 0.00 |
October | 870.45 | 252.03 | 541.12 | 365.84 | 175.29 | 0.00 | 0.00 |
November | 936.28 | 396.87 | 651.19 | 496.46 | 154.74 | 0.00 | 0.00 |
December | 885.66 | 472.67 | 645.36 | 484.44 | 160.92 | 0.00 | 0.00 |
Annual Sum or Average | 683.50 | 250.63 | 426.33 | 246.36 | 179.97 | 0.00 | 0.00 |
Minimum of Months | 413.55 | 54.85 | 196.36 | 12.46 | 152.73 | 0.00 | 0.00 |
Maximum of Months | 936.28 | 472.67 | 651.19 | 496.46 | 201.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 435.07 | 233.29 | 315.05 | 238.68 | 76.37 | 0.00 | 0.00 |
February | 410.46 | 209.42 | 292.24 | 206.02 | 86.22 | 0.00 | 0.00 |
March | 342.93 | 187.22 | 237.51 | 136.95 | 100.56 | 0.00 | 0.00 |
April | 261.92 | 116.04 | 161.03 | 60.08 | 100.94 | 0.00 | 0.00 |
May | 206.36 | 68.03 | 113.80 | 15.93 | 97.87 | 0.00 | 0.00 |
June | 220.19 | 34.15 | 98.18 | 6.23 | 91.95 | 0.00 | 0.00 |
July | 223.60 | 27.70 | 100.08 | 9.28 | 90.80 | 0.00 | 0.00 |
August | 265.80 | 40.24 | 127.58 | 33.77 | 93.81 | 0.00 | 0.00 |
September | 375.12 | 77.69 | 199.13 | 103.46 | 95.68 | 0.00 | 0.00 |
October | 433.97 | 127.11 | 270.56 | 182.92 | 87.64 | 0.00 | 0.00 |
November | 463.39 | 206.86 | 325.60 | 248.23 | 77.37 | 0.00 | 0.00 |
December | 436.51 | 250.96 | 322.68 | 242.22 | 80.46 | 0.00 | 0.00 |
Annual Sum or Average | 339.13 | 131.17 | 213.17 | 123.18 | 89.99 | 0.00 | 0.00 |
Minimum of Months | 206.36 | 27.70 | 98.18 | 6.23 | 76.37 | 0.00 | 0.00 |
Maximum of Months | 463.39 | 250.96 | 325.60 | 248.23 | 100.94 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 435.98 | 225.25 | 314.40 | 238.19 | 76.21 | 0.00 | 0.00 |
February | 411.04 | 203.69 | 291.64 | 205.60 | 86.04 | 0.00 | 0.00 |
March | 343.24 | 183.93 | 237.02 | 136.66 | 100.35 | 0.00 | 0.00 |
April | 260.72 | 118.77 | 160.70 | 59.96 | 100.74 | 0.00 | 0.00 |
May | 203.92 | 73.06 | 113.56 | 15.90 | 97.67 | 0.00 | 0.00 |
June | 214.73 | 38.62 | 97.98 | 6.22 | 91.76 | 0.00 | 0.00 |
July | 217.95 | 32.50 | 99.88 | 9.26 | 90.62 | 0.00 | 0.00 |
August | 261.41 | 45.58 | 127.31 | 33.70 | 93.61 | 0.00 | 0.00 |
September | 373.26 | 84.84 | 198.72 | 103.24 | 95.48 | 0.00 | 0.00 |
October | 432.46 | 131.24 | 270.01 | 182.54 | 87.46 | 0.00 | 0.00 |
November | 463.57 | 204.46 | 324.93 | 247.72 | 77.21 | 0.00 | 0.00 |
December | 437.34 | 243.26 | 322.02 | 241.72 | 80.30 | 0.00 | 0.00 |
Annual Sum or Average | 337.48 | 131.74 | 212.73 | 122.93 | 89.80 | 0.00 | 0.00 |
Minimum of Months | 203.92 | 32.50 | 97.98 | 6.22 | 76.21 | 0.00 | 0.00 |
Maximum of Months | 463.57 | 243.26 | 324.93 | 247.72 | 100.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 437.26 | 221.42 | 314.40 | 238.19 | 76.21 | 0.00 | 0.00 |
February | 412.18 | 200.54 | 291.64 | 205.60 | 86.04 | 0.00 | 0.00 |
March | 344.22 | 181.54 | 237.02 | 136.66 | 100.35 | 0.00 | 0.00 |
April | 260.94 | 118.21 | 160.70 | 59.96 | 100.74 | 0.00 | 0.00 |
May | 203.81 | 73.35 | 113.56 | 15.90 | 97.67 | 0.00 | 0.00 |
June | 214.38 | 39.24 | 97.98 | 6.22 | 91.76 | 0.00 | 0.00 |
July | 217.55 | 33.15 | 99.88 | 9.26 | 90.62 | 0.00 | 0.00 |
August | 261.11 | 46.25 | 127.31 | 33.70 | 93.61 | 0.00 | 0.00 |
September | 373.11 | 85.41 | 198.72 | 103.24 | 95.48 | 0.00 | 0.00 |
October | 432.49 | 131.11 | 270.01 | 182.54 | 87.46 | 0.00 | 0.00 |
November | 464.33 | 202.59 | 324.93 | 247.72 | 77.21 | 0.00 | 0.00 |
December | 438.54 | 239.76 | 322.02 | 241.72 | 80.30 | 0.00 | 0.00 |
Annual Sum or Average | 337.83 | 130.69 | 212.73 | 122.93 | 89.80 | 0.00 | 0.00 |
Minimum of Months | 203.81 | 33.15 | 97.98 | 6.22 | 76.21 | 0.00 | 0.00 |
Maximum of Months | 464.33 | 239.76 | 324.93 | 247.72 | 100.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 438.75 | 217.98 | 314.40 | 238.19 | 76.21 | 0.00 | 0.00 |
February | 413.68 | 197.37 | 291.64 | 205.60 | 86.04 | 0.00 | 0.00 |
March | 345.73 | 178.69 | 237.02 | 136.66 | 100.35 | 0.00 | 0.00 |
April | 261.71 | 116.59 | 160.70 | 59.96 | 100.74 | 0.00 | 0.00 |
May | 204.32 | 72.33 | 113.56 | 15.90 | 97.67 | 0.00 | 0.00 |
June | 214.93 | 38.50 | 97.98 | 6.22 | 91.76 | 0.00 | 0.00 |
July | 218.01 | 32.46 | 99.88 | 9.26 | 90.62 | 0.00 | 0.00 |
August | 261.50 | 45.49 | 127.31 | 33.70 | 93.61 | 0.00 | 0.00 |
September | 373.43 | 84.53 | 198.72 | 103.24 | 95.48 | 0.00 | 0.00 |
October | 432.96 | 129.98 | 270.01 | 182.54 | 87.46 | 0.00 | 0.00 |
November | 465.45 | 200.42 | 324.93 | 247.72 | 77.21 | 0.00 | 0.00 |
December | 439.97 | 236.62 | 322.02 | 241.72 | 80.30 | 0.00 | 0.00 |
Annual Sum or Average | 338.71 | 128.90 | 212.73 | 122.93 | 89.80 | 0.00 | 0.00 |
Minimum of Months | 204.32 | 32.46 | 97.98 | 6.22 | 76.21 | 0.00 | 0.00 |
Maximum of Months | 465.45 | 236.62 | 324.93 | 247.72 | 100.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 885.66 | 421.14 | 628.80 | 476.38 | 152.42 | 0.00 | 0.00 |
February | 835.47 | 380.39 | 583.28 | 411.20 | 172.08 | 0.00 | 0.00 |
March | 699.56 | 343.66 | 474.04 | 273.33 | 200.71 | 0.00 | 0.00 |
April | 527.69 | 223.79 | 321.40 | 119.92 | 201.47 | 0.00 | 0.00 |
May | 410.03 | 137.56 | 227.13 | 31.79 | 195.34 | 0.00 | 0.00 |
June | 431.19 | 71.98 | 195.95 | 12.43 | 183.52 | 0.00 | 0.00 |
July | 436.41 | 60.15 | 199.75 | 18.52 | 181.24 | 0.00 | 0.00 |
August | 523.19 | 85.20 | 254.63 | 67.40 | 187.23 | 0.00 | 0.00 |
September | 746.93 | 162.02 | 397.45 | 206.49 | 190.96 | 0.00 | 0.00 |
October | 868.60 | 252.66 | 540.01 | 365.09 | 174.93 | 0.00 | 0.00 |
November | 936.90 | 389.89 | 649.86 | 495.44 | 154.42 | 0.00 | 0.00 |
December | 887.89 | 459.39 | 644.03 | 483.44 | 160.59 | 0.00 | 0.00 |
Annual Sum or Average | 681.44 | 248.31 | 425.46 | 245.85 | 179.60 | 0.00 | 0.00 |
Minimum of Months | 410.03 | 60.15 | 195.95 | 12.43 | 152.42 | 0.00 | 0.00 |
Maximum of Months | 936.90 | 459.39 | 649.86 | 495.44 | 201.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 442.14 | 210.14 | 314.40 | 238.19 | 76.21 | 0.00 | 0.00 |
February | 417.15 | 189.79 | 291.64 | 205.60 | 86.04 | 0.00 | 0.00 |
March | 349.31 | 171.22 | 237.02 | 136.66 | 100.35 | 0.00 | 0.00 |
April | 263.77 | 111.11 | 160.70 | 59.96 | 100.74 | 0.00 | 0.00 |
May | 205.64 | 67.80 | 113.56 | 15.90 | 97.67 | 0.00 | 0.00 |
June | 217.13 | 35.00 | 97.98 | 6.22 | 91.76 | 0.00 | 0.00 |
July | 219.45 | 29.09 | 99.88 | 9.26 | 90.62 | 0.00 | 0.00 |
August | 262.46 | 41.53 | 127.31 | 33.70 | 93.61 | 0.00 | 0.00 |
September | 373.63 | 79.88 | 198.72 | 103.24 | 95.48 | 0.00 | 0.00 |
October | 433.89 | 125.63 | 270.01 | 182.54 | 87.46 | 0.00 | 0.00 |
November | 467.90 | 194.53 | 324.93 | 247.72 | 77.21 | 0.00 | 0.00 |
December | 443.32 | 229.47 | 322.02 | 241.72 | 80.30 | 0.00 | 0.00 |
Annual Sum or Average | 340.81 | 123.43 | 212.73 | 122.93 | 89.80 | 0.00 | 0.00 |
Minimum of Months | 205.64 | 29.09 | 97.98 | 6.22 | 76.21 | 0.00 | 0.00 |
Maximum of Months | 467.90 | 229.47 | 324.93 | 247.72 | 100.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 442.76 | 208.82 | 314.40 | 238.19 | 76.21 | 0.00 | 0.00 |
February | 417.84 | 188.46 | 291.64 | 205.60 | 86.04 | 0.00 | 0.00 |
March | 350.14 | 169.81 | 237.02 | 136.66 | 100.35 | 0.00 | 0.00 |
April | 264.22 | 110.36 | 160.70 | 59.96 | 100.74 | 0.00 | 0.00 |
May | 205.90 | 67.44 | 113.56 | 15.90 | 97.67 | 0.00 | 0.00 |
June | 217.38 | 34.78 | 97.98 | 6.22 | 91.76 | 0.00 | 0.00 |
July | 219.68 | 28.89 | 99.88 | 9.26 | 90.62 | 0.00 | 0.00 |
August | 262.64 | 41.32 | 127.31 | 33.70 | 93.61 | 0.00 | 0.00 |
September | 373.79 | 79.62 | 198.72 | 103.24 | 95.48 | 0.00 | 0.00 |
October | 434.14 | 125.17 | 270.01 | 182.54 | 87.46 | 0.00 | 0.00 |
November | 468.53 | 193.49 | 324.93 | 247.72 | 77.21 | 0.00 | 0.00 |
December | 443.85 | 228.44 | 322.02 | 241.72 | 80.30 | 0.00 | 0.00 |
Annual Sum or Average | 341.23 | 122.72 | 212.73 | 122.93 | 89.80 | 0.00 | 0.00 |
Minimum of Months | 205.90 | 28.89 | 97.98 | 6.22 | 76.21 | 0.00 | 0.00 |
Maximum of Months | 468.53 | 228.44 | 324.93 | 247.72 | 100.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 444.21 | 205.39 | 314.40 | 238.19 | 76.21 | 0.00 | 0.00 |
February | 419.58 | 184.84 | 291.64 | 205.60 | 86.04 | 0.00 | 0.00 |
March | 352.09 | 166.04 | 237.02 | 136.66 | 100.35 | 0.00 | 0.00 |
April | 265.25 | 108.35 | 160.70 | 59.96 | 100.74 | 0.00 | 0.00 |
May | 206.30 | 66.68 | 113.56 | 15.90 | 97.67 | 0.00 | 0.00 |
June | 217.42 | 34.59 | 97.98 | 6.22 | 91.76 | 0.00 | 0.00 |
July | 219.55 | 28.86 | 99.88 | 9.26 | 90.62 | 0.00 | 0.00 |
August | 262.47 | 41.36 | 127.31 | 33.70 | 93.61 | 0.00 | 0.00 |
September | 373.74 | 79.57 | 198.72 | 103.24 | 95.48 | 0.00 | 0.00 |
October | 434.59 | 124.22 | 270.01 | 182.54 | 87.46 | 0.00 | 0.00 |
November | 469.98 | 190.88 | 324.93 | 247.72 | 77.21 | 0.00 | 0.00 |
December | 445.17 | 225.61 | 322.02 | 241.72 | 80.30 | 0.00 | 0.00 |
Annual Sum or Average | 342.01 | 121.04 | 212.73 | 122.93 | 89.80 | 0.00 | 0.00 |
Minimum of Months | 206.30 | 28.86 | 97.98 | 6.22 | 76.21 | 0.00 | 0.00 |
Maximum of Months | 469.98 | 225.61 | 324.93 | 247.72 | 100.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 447.63 | 193.51 | 314.40 | 238.19 | 76.21 | 0.00 | 0.00 |
February | 423.58 | 172.30 | 291.64 | 205.60 | 86.04 | 0.00 | 0.00 |
March | 356.01 | 153.35 | 237.02 | 136.66 | 100.35 | 0.00 | 0.00 |
April | 266.61 | 100.68 | 160.70 | 59.96 | 100.74 | 0.00 | 0.00 |
May | 205.92 | 63.24 | 113.56 | 15.90 | 97.67 | 0.00 | 0.00 |
June | 215.24 | 33.71 | 97.98 | 6.22 | 91.76 | 0.00 | 0.00 |
July | 216.57 | 28.98 | 99.88 | 9.26 | 90.62 | 0.00 | 0.00 |
August | 259.53 | 41.79 | 127.31 | 33.70 | 93.61 | 0.00 | 0.00 |
September | 371.51 | 79.73 | 198.72 | 103.24 | 95.48 | 0.00 | 0.00 |
October | 434.86 | 120.61 | 270.01 | 182.54 | 87.46 | 0.00 | 0.00 |
November | 472.70 | 182.22 | 324.93 | 247.72 | 77.21 | 0.00 | 0.00 |
December | 448.40 | 215.25 | 322.02 | 241.72 | 80.30 | 0.00 | 0.00 |
Annual Sum or Average | 342.68 | 115.16 | 212.73 | 122.93 | 89.80 | 0.00 | 0.00 |
Minimum of Months | 205.92 | 28.98 | 97.98 | 6.22 | 76.21 | 0.00 | 0.00 |
Maximum of Months | 472.70 | 215.25 | 324.93 | 247.72 | 100.74 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.236577E+10 | 0.116524E+10 | 0.168764E+10 | 0.127856E+10 | 0.409076E+09 | 0.00 | 0.00 |
February | 0.201960E+10 | 0.945283E+09 | 0.141398E+10 | 0.996831E+09 | 0.417145E+09 | 0.00 | 0.00 |
March | 0.187298E+10 | 0.941437E+09 | 0.127227E+10 | 0.733588E+09 | 0.538684E+09 | 0.00 | 0.00 |
April | 0.137176E+10 | 0.581841E+09 | 0.834770E+09 | 0.311474E+09 | 0.523296E+09 | 0.00 | 0.00 |
May | 0.110764E+10 | 0.358265E+09 | 0.609587E+09 | 85322163.70 | 0.524265E+09 | 0.00 | 0.00 |
June | 0.113604E+10 | 0.174068E+09 | 0.508955E+09 | 32293323.27 | 0.476661E+09 | 0.00 | 0.00 |
July | 0.119070E+10 | 0.146901E+09 | 0.536117E+09 | 49698998.17 | 0.486418E+09 | 0.00 | 0.00 |
August | 0.141756E+10 | 0.215253E+09 | 0.683402E+09 | 0.180901E+09 | 0.502501E+09 | 0.00 | 0.00 |
September | 0.194252E+10 | 0.405805E+09 | 0.103230E+10 | 0.536317E+09 | 0.495986E+09 | 0.00 | 0.00 |
October | 0.233142E+10 | 0.675042E+09 | 0.144935E+10 | 0.979857E+09 | 0.469492E+09 | 0.00 | 0.00 |
November | 0.242685E+10 | 0.102870E+10 | 0.168790E+10 | 0.128681E+10 | 0.401082E+09 | 0.00 | 0.00 |
December | 0.237214E+10 | 0.126600E+10 | 0.172853E+10 | 0.129751E+10 | 0.431016E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.215550E+11 | 0.790383E+10 | 0.134448E+11 | 0.776917E+10 | 0.567562E+10 | 0.00 | 0.00 |
Minimum of Months | 0.110764E+10 | 0.146901E+09 | 0.508955E+09 | 32293323.27 | 0.401082E+09 | 0.00 | 0.00 |
Maximum of Months | 0.242685E+10 | 0.126600E+10 | 0.172853E+10 | 0.129751E+10 | 0.538684E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.116528E+10 | 0.624847E+09 | 0.843820E+09 | 0.639281E+09 | 0.204538E+09 | 0.00 | 0.00 |
February | 0.992976E+09 | 0.506639E+09 | 0.706988E+09 | 0.498416E+09 | 0.208572E+09 | 0.00 | 0.00 |
March | 0.918499E+09 | 0.501450E+09 | 0.636136E+09 | 0.366794E+09 | 0.269342E+09 | 0.00 | 0.00 |
April | 0.678895E+09 | 0.300769E+09 | 0.417385E+09 | 0.155737E+09 | 0.261648E+09 | 0.00 | 0.00 |
May | 0.552702E+09 | 0.182198E+09 | 0.304793E+09 | 42661081.85 | 0.262132E+09 | 0.00 | 0.00 |
June | 0.570738E+09 | 88523475.10 | 0.254477E+09 | 16146661.64 | 0.238331E+09 | 0.00 | 0.00 |
July | 0.598892E+09 | 74199845.93 | 0.268059E+09 | 24849499.09 | 0.243209E+09 | 0.00 | 0.00 |
August | 0.711929E+09 | 0.107780E+09 | 0.341701E+09 | 90450288.55 | 0.251251E+09 | 0.00 | 0.00 |
September | 0.972309E+09 | 0.201360E+09 | 0.516151E+09 | 0.268159E+09 | 0.247993E+09 | 0.00 | 0.00 |
October | 0.116235E+10 | 0.340463E+09 | 0.724674E+09 | 0.489928E+09 | 0.234746E+09 | 0.00 | 0.00 |
November | 0.120111E+10 | 0.536178E+09 | 0.843948E+09 | 0.643407E+09 | 0.200541E+09 | 0.00 | 0.00 |
December | 0.116915E+10 | 0.672178E+09 | 0.864264E+09 | 0.648756E+09 | 0.215508E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.106948E+11 | 0.413659E+10 | 0.672240E+10 | 0.388458E+10 | 0.283781E+10 | 0.00 | 0.00 |
Minimum of Months | 0.552702E+09 | 74199845.93 | 0.254477E+09 | 16146661.64 | 0.200541E+09 | 0.00 | 0.00 |
Maximum of Months | 0.120111E+10 | 0.672178E+09 | 0.864264E+09 | 0.648756E+09 | 0.269342E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.116772E+10 | 0.603311E+09 | 0.842088E+09 | 0.637970E+09 | 0.204119E+09 | 0.00 | 0.00 |
February | 0.994377E+09 | 0.492762E+09 | 0.705538E+09 | 0.497393E+09 | 0.208145E+09 | 0.00 | 0.00 |
March | 0.919330E+09 | 0.492636E+09 | 0.634831E+09 | 0.366042E+09 | 0.268789E+09 | 0.00 | 0.00 |
April | 0.675797E+09 | 0.307850E+09 | 0.416529E+09 | 0.155417E+09 | 0.261111E+09 | 0.00 | 0.00 |
May | 0.546183E+09 | 0.195684E+09 | 0.304168E+09 | 42573563.60 | 0.261595E+09 | 0.00 | 0.00 |
June | 0.556589E+09 | 0.100103E+09 | 0.253955E+09 | 16113537.12 | 0.237842E+09 | 0.00 | 0.00 |
July | 0.583753E+09 | 87060733.05 | 0.267509E+09 | 24798520.89 | 0.242710E+09 | 0.00 | 0.00 |
August | 0.700165E+09 | 0.122086E+09 | 0.341000E+09 | 90264731.81 | 0.250735E+09 | 0.00 | 0.00 |
September | 0.967496E+09 | 0.219912E+09 | 0.515092E+09 | 0.267608E+09 | 0.247484E+09 | 0.00 | 0.00 |
October | 0.115830E+10 | 0.351501E+09 | 0.723188E+09 | 0.488923E+09 | 0.234265E+09 | 0.00 | 0.00 |
November | 0.120157E+10 | 0.529972E+09 | 0.842216E+09 | 0.642087E+09 | 0.200130E+09 | 0.00 | 0.00 |
December | 0.117136E+10 | 0.651552E+09 | 0.862491E+09 | 0.647425E+09 | 0.215066E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.106426E+11 | 0.415443E+10 | 0.670861E+10 | 0.387662E+10 | 0.283199E+10 | 0.00 | 0.00 |
Minimum of Months | 0.546183E+09 | 87060733.05 | 0.253955E+09 | 16113537.12 | 0.200130E+09 | 0.00 | 0.00 |
Maximum of Months | 0.120157E+10 | 0.651552E+09 | 0.862491E+09 | 0.647425E+09 | 0.268789E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.117117E+10 | 0.593062E+09 | 0.842088E+09 | 0.637970E+09 | 0.204119E+09 | 0.00 | 0.00 |
February | 0.997155E+09 | 0.485142E+09 | 0.705538E+09 | 0.497393E+09 | 0.208145E+09 | 0.00 | 0.00 |
March | 0.921953E+09 | 0.486247E+09 | 0.634831E+09 | 0.366042E+09 | 0.268789E+09 | 0.00 | 0.00 |
April | 0.676351E+09 | 0.306391E+09 | 0.416529E+09 | 0.155417E+09 | 0.261111E+09 | 0.00 | 0.00 |
May | 0.545878E+09 | 0.196448E+09 | 0.304168E+09 | 42573563.60 | 0.261595E+09 | 0.00 | 0.00 |
June | 0.555661E+09 | 0.101712E+09 | 0.253955E+09 | 16113537.12 | 0.237842E+09 | 0.00 | 0.00 |
July | 0.582696E+09 | 88793871.65 | 0.267509E+09 | 24798520.89 | 0.242710E+09 | 0.00 | 0.00 |
August | 0.699364E+09 | 0.123888E+09 | 0.341000E+09 | 90264731.81 | 0.250735E+09 | 0.00 | 0.00 |
September | 0.967101E+09 | 0.221393E+09 | 0.515092E+09 | 0.267608E+09 | 0.247484E+09 | 0.00 | 0.00 |
October | 0.115839E+10 | 0.351155E+09 | 0.723188E+09 | 0.488923E+09 | 0.234265E+09 | 0.00 | 0.00 |
November | 0.120353E+10 | 0.525106E+09 | 0.842216E+09 | 0.642087E+09 | 0.200130E+09 | 0.00 | 0.00 |
December | 0.117458E+10 | 0.642180E+09 | 0.862491E+09 | 0.647425E+09 | 0.215066E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.106538E+11 | 0.412152E+10 | 0.670861E+10 | 0.387662E+10 | 0.283199E+10 | 0.00 | 0.00 |
Minimum of Months | 0.545878E+09 | 88793871.65 | 0.253955E+09 | 16113537.12 | 0.200130E+09 | 0.00 | 0.00 |
Maximum of Months | 0.120353E+10 | 0.642180E+09 | 0.862491E+09 | 0.647425E+09 | 0.268789E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.117515E+10 | 0.583839E+09 | 0.842088E+09 | 0.637970E+09 | 0.204119E+09 | 0.00 | 0.00 |
February | 0.100078E+10 | 0.477476E+09 | 0.705538E+09 | 0.497393E+09 | 0.208145E+09 | 0.00 | 0.00 |
March | 0.926003E+09 | 0.478609E+09 | 0.634831E+09 | 0.366042E+09 | 0.268789E+09 | 0.00 | 0.00 |
April | 0.678355E+09 | 0.302190E+09 | 0.416529E+09 | 0.155417E+09 | 0.261111E+09 | 0.00 | 0.00 |
May | 0.547241E+09 | 0.193728E+09 | 0.304168E+09 | 42573563.60 | 0.261595E+09 | 0.00 | 0.00 |
June | 0.557109E+09 | 99785948.08 | 0.253955E+09 | 16113537.12 | 0.237842E+09 | 0.00 | 0.00 |
July | 0.583928E+09 | 86947873.50 | 0.267509E+09 | 24798520.89 | 0.242710E+09 | 0.00 | 0.00 |
August | 0.700400E+09 | 0.121837E+09 | 0.341000E+09 | 90264731.81 | 0.250735E+09 | 0.00 | 0.00 |
September | 0.967934E+09 | 0.219091E+09 | 0.515092E+09 | 0.267608E+09 | 0.247484E+09 | 0.00 | 0.00 |
October | 0.115964E+10 | 0.348134E+09 | 0.723188E+09 | 0.488923E+09 | 0.234265E+09 | 0.00 | 0.00 |
November | 0.120645E+10 | 0.519493E+09 | 0.842216E+09 | 0.642087E+09 | 0.200130E+09 | 0.00 | 0.00 |
December | 0.117842E+10 | 0.633752E+09 | 0.862491E+09 | 0.647425E+09 | 0.215066E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.106814E+11 | 0.406488E+10 | 0.670861E+10 | 0.387662E+10 | 0.283199E+10 | 0.00 | 0.00 |
Minimum of Months | 0.547241E+09 | 86947873.50 | 0.253955E+09 | 16113537.12 | 0.200130E+09 | 0.00 | 0.00 |
Maximum of Months | 0.120645E+10 | 0.633752E+09 | 0.862491E+09 | 0.647425E+09 | 0.268789E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.237214E+10 | 0.112797E+10 | 0.168418E+10 | 0.127594E+10 | 0.408237E+09 | 0.00 | 0.00 |
February | 0.202117E+10 | 0.920242E+09 | 0.141108E+10 | 0.994786E+09 | 0.416289E+09 | 0.00 | 0.00 |
March | 0.187370E+10 | 0.920464E+09 | 0.126966E+10 | 0.732083E+09 | 0.537578E+09 | 0.00 | 0.00 |
April | 0.136777E+10 | 0.580062E+09 | 0.833057E+09 | 0.310835E+09 | 0.522223E+09 | 0.00 | 0.00 |
May | 0.109823E+10 | 0.368445E+09 | 0.608336E+09 | 85147127.19 | 0.523189E+09 | 0.00 | 0.00 |
June | 0.111765E+10 | 0.186577E+09 | 0.507911E+09 | 32227074.24 | 0.475683E+09 | 0.00 | 0.00 |
July | 0.116889E+10 | 0.161099E+09 | 0.535018E+09 | 49597041.79 | 0.485420E+09 | 0.00 | 0.00 |
August | 0.140131E+10 | 0.228212E+09 | 0.682000E+09 | 0.180529E+09 | 0.501470E+09 | 0.00 | 0.00 |
September | 0.193604E+10 | 0.419964E+09 | 0.103018E+10 | 0.535217E+09 | 0.494968E+09 | 0.00 | 0.00 |
October | 0.232645E+10 | 0.676734E+09 | 0.144638E+10 | 0.977846E+09 | 0.468529E+09 | 0.00 | 0.00 |
November | 0.242844E+10 | 0.101060E+10 | 0.168443E+10 | 0.128417E+10 | 0.400260E+09 | 0.00 | 0.00 |
December | 0.237813E+10 | 0.123044E+10 | 0.172498E+10 | 0.129485E+10 | 0.430132E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.214899E+11 | 0.783081E+10 | 0.134172E+11 | 0.775323E+10 | 0.566398E+10 | 0.00 | 0.00 |
Minimum of Months | 0.109823E+10 | 0.161099E+09 | 0.507911E+09 | 32227074.24 | 0.400260E+09 | 0.00 | 0.00 |
Maximum of Months | 0.242844E+10 | 0.123044E+10 | 0.172498E+10 | 0.129485E+10 | 0.537578E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.118422E+10 | 0.562845E+09 | 0.842088E+09 | 0.637970E+09 | 0.204119E+09 | 0.00 | 0.00 |
February | 0.100916E+10 | 0.459130E+09 | 0.705538E+09 | 0.497393E+09 | 0.208145E+09 | 0.00 | 0.00 |
March | 0.935594E+09 | 0.458598E+09 | 0.634831E+09 | 0.366042E+09 | 0.268789E+09 | 0.00 | 0.00 |
April | 0.683681E+09 | 0.287986E+09 | 0.416529E+09 | 0.155417E+09 | 0.261111E+09 | 0.00 | 0.00 |
May | 0.550773E+09 | 0.181584E+09 | 0.304168E+09 | 42573563.60 | 0.261595E+09 | 0.00 | 0.00 |
June | 0.562795E+09 | 90730394.70 | 0.253955E+09 | 16113537.12 | 0.237842E+09 | 0.00 | 0.00 |
July | 0.587787E+09 | 77927164.03 | 0.267509E+09 | 24798520.89 | 0.242710E+09 | 0.00 | 0.00 |
August | 0.702967E+09 | 0.111237E+09 | 0.341000E+09 | 90264731.81 | 0.250735E+09 | 0.00 | 0.00 |
September | 0.968454E+09 | 0.207061E+09 | 0.515092E+09 | 0.267608E+09 | 0.247484E+09 | 0.00 | 0.00 |
October | 0.116213E+10 | 0.336476E+09 | 0.723188E+09 | 0.488923E+09 | 0.234265E+09 | 0.00 | 0.00 |
November | 0.121280E+10 | 0.504219E+09 | 0.842216E+09 | 0.642087E+09 | 0.200130E+09 | 0.00 | 0.00 |
December | 0.118739E+10 | 0.614603E+09 | 0.862491E+09 | 0.647425E+09 | 0.215066E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.107477E+11 | 0.389240E+10 | 0.670861E+10 | 0.387662E+10 | 0.283199E+10 | 0.00 | 0.00 |
Minimum of Months | 0.550773E+09 | 77927164.03 | 0.253955E+09 | 16113537.12 | 0.200130E+09 | 0.00 | 0.00 |
Maximum of Months | 0.121280E+10 | 0.614603E+09 | 0.862491E+09 | 0.647425E+09 | 0.268789E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.118588E+10 | 0.559313E+09 | 0.842088E+09 | 0.637970E+09 | 0.204119E+09 | 0.00 | 0.00 |
February | 0.101084E+10 | 0.455923E+09 | 0.705538E+09 | 0.497393E+09 | 0.208145E+09 | 0.00 | 0.00 |
March | 0.937808E+09 | 0.454812E+09 | 0.634831E+09 | 0.366042E+09 | 0.268789E+09 | 0.00 | 0.00 |
April | 0.684862E+09 | 0.286060E+09 | 0.416529E+09 | 0.155417E+09 | 0.261111E+09 | 0.00 | 0.00 |
May | 0.551482E+09 | 0.180642E+09 | 0.304168E+09 | 42573563.60 | 0.261595E+09 | 0.00 | 0.00 |
June | 0.563460E+09 | 90148460.46 | 0.253955E+09 | 16113537.12 | 0.237842E+09 | 0.00 | 0.00 |
July | 0.588398E+09 | 77374137.88 | 0.267509E+09 | 24798520.89 | 0.242710E+09 | 0.00 | 0.00 |
August | 0.703462E+09 | 0.110670E+09 | 0.341000E+09 | 90264731.81 | 0.250735E+09 | 0.00 | 0.00 |
September | 0.968861E+09 | 0.206376E+09 | 0.515092E+09 | 0.267608E+09 | 0.247484E+09 | 0.00 | 0.00 |
October | 0.116281E+10 | 0.335266E+09 | 0.723188E+09 | 0.488923E+09 | 0.234265E+09 | 0.00 | 0.00 |
November | 0.121444E+10 | 0.501521E+09 | 0.842216E+09 | 0.642087E+09 | 0.200130E+09 | 0.00 | 0.00 |
December | 0.118880E+10 | 0.611854E+09 | 0.862491E+09 | 0.647425E+09 | 0.215066E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.107611E+11 | 0.386996E+10 | 0.670861E+10 | 0.387662E+10 | 0.283199E+10 | 0.00 | 0.00 |
Minimum of Months | 0.551482E+09 | 77374137.88 | 0.253955E+09 | 16113537.12 | 0.200130E+09 | 0.00 | 0.00 |
Maximum of Months | 0.121444E+10 | 0.611854E+09 | 0.862491E+09 | 0.647425E+09 | 0.268789E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.118977E+10 | 0.550118E+09 | 0.842088E+09 | 0.637970E+09 | 0.204119E+09 | 0.00 | 0.00 |
February | 0.101506E+10 | 0.447156E+09 | 0.705538E+09 | 0.497393E+09 | 0.208145E+09 | 0.00 | 0.00 |
March | 0.943030E+09 | 0.444723E+09 | 0.634831E+09 | 0.366042E+09 | 0.268789E+09 | 0.00 | 0.00 |
April | 0.687524E+09 | 0.280840E+09 | 0.416529E+09 | 0.155417E+09 | 0.261111E+09 | 0.00 | 0.00 |
May | 0.552545E+09 | 0.178589E+09 | 0.304168E+09 | 42573563.60 | 0.261595E+09 | 0.00 | 0.00 |
June | 0.563559E+09 | 89668122.78 | 0.253955E+09 | 16113537.12 | 0.237842E+09 | 0.00 | 0.00 |
July | 0.588042E+09 | 77309194.12 | 0.267509E+09 | 24798520.89 | 0.242710E+09 | 0.00 | 0.00 |
August | 0.703003E+09 | 0.110777E+09 | 0.341000E+09 | 90264731.81 | 0.250735E+09 | 0.00 | 0.00 |
September | 0.968725E+09 | 0.206249E+09 | 0.515092E+09 | 0.267608E+09 | 0.247484E+09 | 0.00 | 0.00 |
October | 0.116401E+10 | 0.332721E+09 | 0.723188E+09 | 0.488923E+09 | 0.234265E+09 | 0.00 | 0.00 |
November | 0.121818E+10 | 0.494764E+09 | 0.842216E+09 | 0.642087E+09 | 0.200130E+09 | 0.00 | 0.00 |
December | 0.119233E+10 | 0.604284E+09 | 0.862491E+09 | 0.647425E+09 | 0.215066E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.107858E+11 | 0.381720E+10 | 0.670861E+10 | 0.387662E+10 | 0.283199E+10 | 0.00 | 0.00 |
Minimum of Months | 0.552545E+09 | 77309194.12 | 0.253955E+09 | 16113537.12 | 0.200130E+09 | 0.00 | 0.00 |
Maximum of Months | 0.121818E+10 | 0.604284E+09 | 0.862491E+09 | 0.647425E+09 | 0.268789E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.119893E+10 | 0.518292E+09 | 0.842088E+09 | 0.637970E+09 | 0.204119E+09 | 0.00 | 0.00 |
February | 0.102472E+10 | 0.416838E+09 | 0.705538E+09 | 0.497393E+09 | 0.208145E+09 | 0.00 | 0.00 |
March | 0.953525E+09 | 0.410742E+09 | 0.634831E+09 | 0.366042E+09 | 0.268789E+09 | 0.00 | 0.00 |
April | 0.691055E+09 | 0.260951E+09 | 0.416529E+09 | 0.155417E+09 | 0.261111E+09 | 0.00 | 0.00 |
May | 0.551534E+09 | 0.169369E+09 | 0.304168E+09 | 42573563.60 | 0.261595E+09 | 0.00 | 0.00 |
June | 0.557896E+09 | 87368444.93 | 0.253955E+09 | 16113537.12 | 0.237842E+09 | 0.00 | 0.00 |
July | 0.580059E+09 | 77614969.49 | 0.267509E+09 | 24798520.89 | 0.242710E+09 | 0.00 | 0.00 |
August | 0.695133E+09 | 0.111936E+09 | 0.341000E+09 | 90264731.81 | 0.250735E+09 | 0.00 | 0.00 |
September | 0.962964E+09 | 0.206650E+09 | 0.515092E+09 | 0.267608E+09 | 0.247484E+09 | 0.00 | 0.00 |
October | 0.116472E+10 | 0.323038E+09 | 0.723188E+09 | 0.488923E+09 | 0.234265E+09 | 0.00 | 0.00 |
November | 0.122525E+10 | 0.472304E+09 | 0.842216E+09 | 0.642087E+09 | 0.200130E+09 | 0.00 | 0.00 |
December | 0.120100E+10 | 0.576519E+09 | 0.862491E+09 | 0.647425E+09 | 0.215066E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.108068E+11 | 0.363162E+10 | 0.670861E+10 | 0.387662E+10 | 0.283199E+10 | 0.00 | 0.00 |
Minimum of Months | 0.551534E+09 | 77614969.49 | 0.253955E+09 | 16113537.12 | 0.200130E+09 | 0.00 | 0.00 |
Maximum of Months | 0.122525E+10 | 0.576519E+09 | 0.862491E+09 | 0.647425E+09 | 0.268789E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 8.14 | 3.28 | -3.0 | 3.49 | -5.4 | 41.12 | 223.64 | 0.00 |
February | 10.27 | 3.71 | -4.6 | 3.82 | -5.0 | 51.61 | 245.22 | 0.00 |
March | 12.55 | 4.68 | -5.5 | 4.62 | -3.1 | 72.41 | 273.25 | 0.00 |
April | 19.23 | 8.50 | -2.7 | 4.72 | 3.38 | 79.21 | 314.56 | 0.00 |
May | 23.84 | 12.23 | 2.64 | 5.25 | 8.38 | 86.83 | 326.20 | 0.00 |
June | 27.86 | 15.03 | 5.88 | 4.15 | 14.09 | 80.19 | 344.14 | 0.01 |
July | 27.54 | 18.92 | 14.64 | 3.53 | 17.44 | 86.25 | 283.04 | 0.01 |
August | 26.28 | 17.11 | 12.00 | 3.28 | 15.48 | 80.55 | 269.68 | 0.02 |
September | 23.38 | 15.82 | 11.20 | 2.23 | 11.29 | 66.71 | 294.09 | 0.00 |
October | 18.30 | 12.02 | 7.27 | 3.24 | 6.21 | 54.59 | 257.93 | 0.01 |
November | 11.18 | 5.22 | -1.5 | 3.40 | -3.3 | 40.23 | 258.80 | 0.00 |
December | 6.79 | 1.84 | -4.8 | 2.82 | -8.9 | 42.65 | 217.21 | 0.00 |
Annual Sum or Average | 17.98 | 9.90 | 2.67 | 3.71 | 4.26 | 65.29 | 275.60 | 0.00 |
Minimum of Months | 6.79 | 1.84 | -5.5 | 2.23 | -8.9 | 40.23 | 217.21 | 0.00 |
Maximum of Months | 27.86 | 18.92 | 14.64 | 5.25 | 17.44 | 86.83 | 344.14 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.60 | 03-JAN-14:00 | 8.39 | -5.0 | 9.80 | 2.22 | 118.50 | 530.50 |
February | 23.30 | 20-FEB-14:00 | 8.88 | -7.8 | 4.10 | 4.10 | 55.00 | 955.00 |
March | 25.00 | 21-MAR-15:00 | 9.53 | -8.3 | 6.20 | 5.54 | 50.00 | 873.00 |
April | 32.20 | 21-APR-13:00 | 15.21 | 2.80 | 13.90 | 18.28 | 265.50 | 638.50 |
May | 35.00 | 19-MAY-13:00 | 17.23 | 6.10 | 10.30 | 21.78 | 145.00 | 874.50 |
June | 38.90 | 02-JUN-15:00 | 16.22 | -1.1 | 4.60 | 20.40 | 234.50 | 284.00 |
July | 38.30 | 01-JUL-16:00 | 19.19 | 8.90 | 3.60 | 26.81 | 165.50 | 256.50 |
August | 37.20 | 07-AUG-15:00 | 17.89 | 6.70 | 5.70 | 24.66 | 143.50 | 615.00 |
September | 33.90 | 19-SEP-13:00 | 16.85 | 6.70 | 3.10 | 17.75 | 113.00 | 912.00 |
October | 32.80 | 01-OCT-14:00 | 15.90 | 4.40 | 5.70 | 16.12 | 127.50 | 736.50 |
November | 23.90 | 03-NOV-15:00 | 13.45 | 6.10 | 5.70 | 12.22 | 48.50 | 648.50 |
December | 18.30 | 10-DEC-14:00 | 7.97 | -2.8 | 7.20 | 4.10 | 123.00 | 52.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.30 | 7.97 | -8.3 | 3.10 | 2.22 | 48.50 | 52.50 | |
Maximum of Months | 38.90 | 19.19 | 8.90 | 13.90 | 26.81 | 265.50 | 955.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 27-JAN-06:00 | -7.5 | -15.0 | 3.60 | -23.6 | 0.00 | 0.00 |
February | -5.6 | 03-FEB-06:00 | -7.5 | -11.7 | 1.50 | -23.9 | 0.00 | 0.00 |
March | -3.9 | 02-MAR-04:00 | -6.5 | -12.8 | 1.50 | -21.3 | 0.00 | 0.00 |
April | 3.30 | 12-APR-05:00 | -1.8 | -9.4 | 2.10 | -14.9 | 37.00 | 217.50 |
May | 9.40 | 02-MAY-05:00 | 3.98 | -2.2 | 3.60 | -7.6 | 51.00 | 277.50 |
June | 15.00 | 13-JUN-04:00 | 4.43 | -10.6 | 2.10 | -4.3 | 0.00 | 0.00 |
July | 17.80 | 05-JUL-05:00 | 15.98 | 15.00 | 4.10 | 4.31 | 39.00 | 249.00 |
August | 16.70 | 31-AUG-05:00 | 13.89 | 12.20 | 4.10 | 2.64 | 36.00 | 126.50 |
September | 8.30 | 30-SEP-05:00 | 5.77 | 3.30 | 1.50 | -7.3 | 0.00 | 0.00 |
October | 6.70 | 11-OCT-05:00 | 5.82 | 5.00 | 1.50 | -5.5 | 0.00 | 0.00 |
November | -0.6 | 17-NOV-03:00 | -3.1 | -6.7 | 1.50 | -18.1 | 0.00 | 0.00 |
December | -4.4 | 27-DEC-06:00 | -5.1 | -6.1 | 2.10 | -18.6 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -7.5 | -15.0 | 1.50 | -23.9 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 15.98 | 15.00 | 4.10 | 4.31 | 51.00 | 277.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.18 | 12-JAN-15:00 | 18.90 | 2.80 | 3.60 | 6.15 | 70.50 | 491.50 |
February | 11.42 | 13-FEB-16:00 | 12.80 | 10.60 | 4.10 | 6.55 | 34.00 | 18.50 |
March | 10.75 | 10-MAR-18:00 | 13.30 | 8.90 | 1.50 | 8.54 | 0.00 | 0.00 |
April | 15.74 | 29-APR-13:00 | 30.00 | 6.70 | 4.10 | 18.28 | 336.50 | 432.50 |
May | 19.12 | 24-MAY-12:00 | 27.80 | 15.00 | 5.20 | 17.57 | 188.50 | 862.00 |
June | 20.21 | 03-JUN-14:00 | 33.90 | 13.90 | 8.80 | 23.66 | 264.50 | 316.00 |
July | 22.88 | 20-JUL-15:39 | 25.53 | 21.87 | 2.93 | 18.99 | 184.00 | 15.83 |
August | 21.18 | 02-AUG-11:00 | 30.60 | 17.20 | 3.60 | 20.75 | 154.50 | 850.00 |
September | 20.65 | 14-SEP-09:00 | 25.00 | 18.90 | 2.10 | 14.47 | 126.50 | 835.50 |
October | 19.64 | 03-OCT-13:00 | 32.80 | 13.30 | 2.60 | 21.44 | 224.50 | 577.50 |
November | 13.57 | 03-NOV-14:00 | 23.30 | 7.20 | 0.00 | 10.88 | 72.50 | 802.00 |
December | 8.30 | 10-DEC-12:00 | 17.20 | -0.6 | 5.70 | 1.58 | 198.50 | 507.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.30 | 12.80 | -0.6 | 0.00 | 1.58 | 0.00 | 0.00 | |
Maximum of Months | 22.88 | 33.90 | 21.87 | 8.80 | 23.66 | 336.50 | 862.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.00 | 16-JAN-01:00 | 9.00 | 9.00 | 2.10 | 4.51 | 0.00 | 0.00 |
February | 10.60 | 13-FEB-13:09 | 12.20 | 11.24 | 5.53 | 5.71 | 147.33 | 0.00 |
March | 10.00 | 11-MAR-00:00 | 10.60 | 10.24 | 2.10 | 6.15 | 0.00 | 0.00 |
April | 10.60 | 17-APR-01:00 | 17.80 | 13.38 | 7.20 | 3.48 | 0.00 | 0.00 |
May | 15.00 | 24-MAY-10:00 | 25.60 | 18.41 | 7.20 | 15.39 | 171.00 | 872.50 |
June | 17.20 | 19-JUN-17:00 | 23.90 | 19.20 | 3.60 | 15.39 | 86.00 | 324.00 |
July | 22.20 | 20-JUL-14:00 | 24.40 | 22.82 | 4.60 | 17.93 | 283.00 | 59.50 |
August | 18.90 | 01-AUG-20:00 | 22.20 | 19.91 | 4.60 | 17.75 | 0.00 | 0.00 |
September | 19.40 | 22-SEP-01:00 | 20.60 | 19.76 | 1.50 | 16.30 | 0.00 | 0.00 |
October | 17.20 | 03-OCT-19:00 | 23.30 | 19.11 | 4.60 | 18.46 | 0.00 | 0.00 |
November | 10.00 | 01-NOV-09:00 | 13.30 | 11.28 | 3.10 | 8.94 | 123.50 | 0.00 |
December | 6.10 | 13-DEC-00:00 | 8.30 | 7.10 | 7.70 | 3.06 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 8.30 | 7.10 | 1.50 | 3.06 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 25.60 | 22.82 | 7.70 | 18.46 | 283.00 | 872.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 15.16 | 28.38 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 15.21 | 35.58 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 16.80 | 47.71 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 19.62 | 58.45 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 22.88 | 63.58 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 25.71 | 66.73 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 27.35 | 58.19 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 27.33 | 54.44 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 25.68 | 50.89 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 22.83 | 39.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 19.57 | 32.11 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 16.77 | 26.90 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 21.28 | 46.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 15.16 | 26.90 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 27.35 | 66.73 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.289424E+09 | -215184018.4 | 0.00 | 0.00 | 744.00 | 0.00 | -74240458.4 | 59.00 | 0.00 | 0.00 |
February | 0.261360E+09 | -195223984.9 | 0.00 | 0.00 | 672.00 | 0.00 | -66135759.3 | 58.99 | 0.00 | 0.00 |
March | 0.283582E+09 | -211652637.0 | 0.00 | 0.00 | 744.00 | 0.00 | -71928908.9 | 58.99 | 0.00 | 0.00 |
April | 0.255939E+09 | -188721615.9 | 0.00 | 0.00 | 720.00 | 0.00 | -67217083.5 | 58.98 | 0.00 | 0.00 |
May | 0.247742E+09 | -179194222.5 | 0.00 | 0.00 | 744.00 | 0.00 | -68548069.5 | 58.99 | 0.00 | 0.00 |
June | 0.227165E+09 | -161374248.5 | 0.00 | 0.00 | 720.00 | 0.00 | -65790463.5 | 58.99 | 0.00 | 0.00 |
July | 0.223106E+09 | -155326073.9 | 0.00 | 0.00 | 744.00 | 0.00 | -67780026.4 | 58.99 | 0.00 | 0.00 |
August | 0.226538E+09 | -158740942.9 | 0.00 | 0.00 | 744.00 | 0.00 | -67797287.2 | 58.98 | 0.00 | 0.00 |
September | 0.225741E+09 | -159883452.0 | 0.00 | 0.00 | 720.00 | 0.00 | -65857101.3 | 58.97 | 0.00 | 0.00 |
October | 0.246254E+09 | -177581364.5 | 0.00 | 0.00 | 744.00 | 0.00 | -68672878.3 | 58.99 | 0.00 | 0.00 |
November | 0.255603E+09 | -186815574.5 | 0.00 | 0.00 | 720.00 | 0.00 | -68787249.0 | 58.98 | 0.00 | 0.00 |
December | 0.282081E+09 | -207564777.3 | 0.00 | 0.00 | 744.00 | 0.00 | -74516179.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.302453E+10 | -0.219726E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -827271465.1 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.223106E+09 | -215184018.4 | 0.00 | 0.00 | 672.00 | 0.00 | -74516179.7 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.289424E+09 | -155326073.9 | 0.00 | 0.00 | 744.00 | 0.00 | -65790463.5 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.287476E+09 | -215195049.0 | 0.00 | 0.00 | 744.00 | 0.00 | -72280584.3 | 58.99 | 0.00 | 0.00 |
February | 0.259788E+09 | -195228230.8 | 0.00 | 0.00 | 672.00 | 0.00 | -64559501.1 | 58.98 | 0.00 | 0.00 |
March | 0.282140E+09 | -211660956.8 | 0.00 | 0.00 | 744.00 | 0.00 | -70478886.4 | 58.99 | 0.00 | 0.00 |
April | 0.255504E+09 | -188716298.3 | 0.00 | 0.00 | 720.00 | 0.00 | -66787374.2 | 58.98 | 0.00 | 0.00 |
May | 0.247589E+09 | -179181868.4 | 0.00 | 0.00 | 744.00 | 0.00 | -68406947.5 | 59.00 | 0.00 | 0.00 |
June | 0.227047E+09 | -161373566.0 | 0.00 | 0.00 | 720.00 | 0.00 | -65673166.6 | 58.99 | 0.00 | 0.00 |
July | 0.223026E+09 | -155344348.7 | 0.00 | 0.00 | 744.00 | 0.00 | -67681463.3 | 58.98 | 0.00 | 0.00 |
August | 0.226501E+09 | -158698959.0 | 0.00 | 0.00 | 744.00 | 0.00 | -67801707.1 | 59.00 | 0.00 | 0.00 |
September | 0.225753E+09 | -159821120.4 | 0.00 | 0.00 | 720.00 | 0.00 | -65931623.6 | 59.01 | 0.00 | 0.00 |
October | 0.246114E+09 | -177584761.0 | 0.00 | 0.00 | 744.00 | 0.00 | -68528999.3 | 58.99 | 0.00 | 0.00 |
November | 0.254516E+09 | -186784449.7 | 0.00 | 0.00 | 720.00 | 0.00 | -67731686.4 | 58.99 | 0.00 | 0.00 |
December | 0.280240E+09 | -207554898.2 | 0.00 | 0.00 | 744.00 | 0.00 | -72684795.4 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.301569E+10 | -0.219714E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -818546735.2 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.223026E+09 | -215195049.0 | 0.00 | 0.00 | 672.00 | 0.00 | -72684795.4 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.287476E+09 | -155344348.7 | 0.00 | 0.00 | 744.00 | 0.00 | -64559501.1 | 59.01 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.262663E+09 | -189229736.4 | 0.00 | 0.00 | 744.00 | 0.00 | -73432971.6 | 58.99 | 0.00 | 0.00 |
February | 0.237151E+09 | -171810841.7 | 0.00 | 0.00 | 672.00 | 0.00 | -65339758.5 | 59.00 | 0.00 | 0.00 |
March | 0.259866E+09 | -188888013.8 | 0.00 | 0.00 | 744.00 | 0.00 | -70977829.6 | 58.99 | 0.00 | 0.00 |
April | 0.232265E+09 | -165960610.2 | 0.00 | 0.00 | 720.00 | 0.00 | -66304395.3 | 59.00 | 0.00 | 0.00 |
May | 0.226366E+09 | -158965157.1 | 0.00 | 0.00 | 744.00 | 0.00 | -67400404.6 | 58.99 | 0.00 | 0.00 |
June | 0.208133E+09 | -143730509.8 | 0.00 | 0.00 | 720.00 | 0.00 | -64402336.3 | 58.98 | 0.00 | 0.00 |
July | 0.202117E+09 | -135782980.7 | 0.00 | 0.00 | 744.00 | 0.00 | -66333719.6 | 59.00 | 0.00 | 0.00 |
August | 0.208286E+09 | -141760523.9 | 0.00 | 0.00 | 744.00 | 0.00 | -66525250.7 | 58.99 | 0.00 | 0.00 |
September | 0.205302E+09 | -140500259.3 | 0.00 | 0.00 | 720.00 | 0.00 | -64801319.4 | 59.00 | 0.00 | 0.00 |
October | 0.224053E+09 | -156197346.8 | 0.00 | 0.00 | 744.00 | 0.00 | -67855733.6 | 58.99 | 0.00 | 0.00 |
November | 0.233008E+09 | -164926257.4 | 0.00 | 0.00 | 720.00 | 0.00 | -68081352.1 | 58.98 | 0.00 | 0.00 |
December | 0.254959E+09 | -181164030.3 | 0.00 | 0.00 | 744.00 | 0.00 | -73794661.0 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.275417E+10 | -0.193892E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -815249732.2 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.202117E+09 | -189229736.4 | 0.00 | 0.00 | 672.00 | 0.00 | -73794661.0 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.262663E+09 | -135782980.7 | 0.00 | 0.00 | 744.00 | 0.00 | -64402336.3 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.263044E+09 | -189228063.8 | 0.00 | 0.00 | 744.00 | 0.00 | -73815874.5 | 59.00 | 0.00 | 0.00 |
February | 0.237435E+09 | -171810810.2 | 0.00 | 0.00 | 672.00 | 0.00 | -65623980.2 | 58.99 | 0.00 | 0.00 |
March | 0.260120E+09 | -188890118.6 | 0.00 | 0.00 | 744.00 | 0.00 | -71229759.8 | 58.99 | 0.00 | 0.00 |
April | 0.232312E+09 | -165962834.6 | 0.00 | 0.00 | 720.00 | 0.00 | -66349306.3 | 58.99 | 0.00 | 0.00 |
May | 0.226343E+09 | -158947808.5 | 0.00 | 0.00 | 744.00 | 0.00 | -67394947.7 | 59.00 | 0.00 | 0.00 |
June | 0.208067E+09 | -143725865.3 | 0.00 | 0.00 | 720.00 | 0.00 | -64341228.4 | 58.98 | 0.00 | 0.00 |
July | 0.202025E+09 | -135779627.9 | 0.00 | 0.00 | 744.00 | 0.00 | -66245764.1 | 58.99 | 0.00 | 0.00 |
August | 0.208224E+09 | -141769656.1 | 0.00 | 0.00 | 744.00 | 0.00 | -66453928.6 | 58.99 | 0.00 | 0.00 |
September | 0.205247E+09 | -140530716.4 | 0.00 | 0.00 | 720.00 | 0.00 | -64715822.3 | 58.98 | 0.00 | 0.00 |
October | 0.224059E+09 | -156203823.9 | 0.00 | 0.00 | 744.00 | 0.00 | -67855356.7 | 58.99 | 0.00 | 0.00 |
November | 0.233209E+09 | -164916213.0 | 0.00 | 0.00 | 720.00 | 0.00 | -68292925.2 | 59.00 | 0.00 | 0.00 |
December | 0.255305E+09 | -181173849.5 | 0.00 | 0.00 | 744.00 | 0.00 | -74131532.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.275539E+10 | -0.193894E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -816450426.6 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.202025E+09 | -189228063.8 | 0.00 | 0.00 | 672.00 | 0.00 | -74131532.9 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.263044E+09 | -135779627.9 | 0.00 | 0.00 | 744.00 | 0.00 | -64341228.4 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.253833E+09 | -178858762.5 | 0.00 | 0.00 | 744.00 | 0.00 | -74974197.5 | 58.99 | 0.00 | 0.00 |
February | 0.229127E+09 | -162480222.6 | 0.00 | 0.00 | 672.00 | 0.00 | -66647228.1 | 58.99 | 0.00 | 0.00 |
March | 0.251054E+09 | -178726865.7 | 0.00 | 0.00 | 744.00 | 0.00 | -72327069.0 | 58.99 | 0.00 | 0.00 |
April | 0.224101E+09 | -157044242.9 | 0.00 | 0.00 | 720.00 | 0.00 | -67056734.0 | 59.00 | 0.00 | 0.00 |
May | 0.218255E+09 | -150332220.4 | 0.00 | 0.00 | 744.00 | 0.00 | -67922503.4 | 58.99 | 0.00 | 0.00 |
June | 0.200845E+09 | -135990963.2 | 0.00 | 0.00 | 720.00 | 0.00 | -64853686.3 | 58.98 | 0.00 | 0.00 |
July | 0.195096E+09 | -128423999.4 | 0.00 | 0.00 | 744.00 | 0.00 | -66671753.3 | 58.99 | 0.00 | 0.00 |
August | 0.201033E+09 | -134128190.3 | 0.00 | 0.00 | 744.00 | 0.00 | -66905010.5 | 59.00 | 0.00 | 0.00 |
September | 0.198138E+09 | -132988099.1 | 0.00 | 0.00 | 720.00 | 0.00 | -65149889.5 | 58.99 | 0.00 | 0.00 |
October | 0.215980E+09 | -147632946.5 | 0.00 | 0.00 | 744.00 | 0.00 | -68347048.6 | 58.99 | 0.00 | 0.00 |
November | 0.224877E+09 | -155746920.7 | 0.00 | 0.00 | 720.00 | 0.00 | -69129638.7 | 59.00 | 0.00 | 0.00 |
December | 0.246592E+09 | -171340535.6 | 0.00 | 0.00 | 744.00 | 0.00 | -75251089.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.265893E+10 | -0.183369E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -825235848.0 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.195096E+09 | -178858762.5 | 0.00 | 0.00 | 672.00 | 0.00 | -75251089.1 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.253833E+09 | -128423999.4 | 0.00 | 0.00 | 744.00 | 0.00 | -64853686.3 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.253923E+09 | -178858093.9 | 0.00 | 0.00 | 744.00 | 0.00 | -75064778.7 | 58.99 | 0.00 | 0.00 |
February | 0.229207E+09 | -162482994.0 | 0.00 | 0.00 | 672.00 | 0.00 | -66724322.1 | 58.99 | 0.00 | 0.00 |
March | 0.251142E+09 | -178733383.3 | 0.00 | 0.00 | 744.00 | 0.00 | -72408313.2 | 58.99 | 0.00 | 0.00 |
April | 0.224160E+09 | -157046857.6 | 0.00 | 0.00 | 720.00 | 0.00 | -67113084.7 | 59.00 | 0.00 | 0.00 |
May | 0.218315E+09 | -150345549.5 | 0.00 | 0.00 | 744.00 | 0.00 | -67969116.7 | 58.98 | 0.00 | 0.00 |
June | 0.200943E+09 | -135985789.9 | 0.00 | 0.00 | 720.00 | 0.00 | -64957323.9 | 58.99 | 0.00 | 0.00 |
July | 0.195199E+09 | -128411995.6 | 0.00 | 0.00 | 744.00 | 0.00 | -66787185.1 | 59.00 | 0.00 | 0.00 |
August | 0.201120E+09 | -134141635.3 | 0.00 | 0.00 | 744.00 | 0.00 | -66978588.2 | 58.99 | 0.00 | 0.00 |
September | 0.198231E+09 | -132972804.1 | 0.00 | 0.00 | 720.00 | 0.00 | -65258439.6 | 59.00 | 0.00 | 0.00 |
October | 0.216049E+09 | -147649226.1 | 0.00 | 0.00 | 744.00 | 0.00 | -68399582.5 | 58.98 | 0.00 | 0.00 |
November | 0.224934E+09 | -155776925.8 | 0.00 | 0.00 | 720.00 | 0.00 | -69157400.2 | 58.98 | 0.00 | 0.00 |
December | 0.246660E+09 | -171333818.9 | 0.00 | 0.00 | 744.00 | 0.00 | -75325985.3 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.265988E+10 | -0.183374E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -826144120.2 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.195199E+09 | -178858093.9 | 0.00 | 0.00 | 672.00 | 0.00 | -75325985.3 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.253923E+09 | -128411995.6 | 0.00 | 0.00 | 744.00 | 0.00 | -64957323.9 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.254054E+09 | -178854664.4 | 0.00 | 0.00 | 744.00 | 0.00 | -75199469.8 | 58.99 | 0.00 | 0.00 |
February | 0.229335E+09 | -162487688.1 | 0.00 | 0.00 | 672.00 | 0.00 | -66847764.0 | 58.99 | 0.00 | 0.00 |
March | 0.251306E+09 | -178722633.4 | 0.00 | 0.00 | 744.00 | 0.00 | -72582985.0 | 58.99 | 0.00 | 0.00 |
April | 0.224224E+09 | -157061013.5 | 0.00 | 0.00 | 720.00 | 0.00 | -67163462.8 | 58.99 | 0.00 | 0.00 |
May | 0.218361E+09 | -150303302.3 | 0.00 | 0.00 | 744.00 | 0.00 | -68057350.3 | 59.01 | 0.00 | 0.00 |
June | 0.200969E+09 | -135992051.4 | 0.00 | 0.00 | 720.00 | 0.00 | -64977310.0 | 58.99 | 0.00 | 0.00 |
July | 0.195223E+09 | -128424747.4 | 0.00 | 0.00 | 744.00 | 0.00 | -66798304.5 | 58.99 | 0.00 | 0.00 |
August | 0.201154E+09 | -134138024.1 | 0.00 | 0.00 | 744.00 | 0.00 | -67016057.3 | 58.99 | 0.00 | 0.00 |
September | 0.198243E+09 | -132989419.8 | 0.00 | 0.00 | 720.00 | 0.00 | -65253681.4 | 58.98 | 0.00 | 0.00 |
October | 0.216099E+09 | -147621062.4 | 0.00 | 0.00 | 744.00 | 0.00 | -68478433.2 | 59.00 | 0.00 | 0.00 |
November | 0.225057E+09 | -155761961.0 | 0.00 | 0.00 | 720.00 | 0.00 | -69295407.4 | 58.99 | 0.00 | 0.00 |
December | 0.246752E+09 | -171342623.6 | 0.00 | 0.00 | 744.00 | 0.00 | -75409511.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.266078E+10 | -0.183370E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -827079737.4 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.195223E+09 | -178854664.4 | 0.00 | 0.00 | 672.00 | 0.00 | -75409511.9 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.254054E+09 | -128424747.4 | 0.00 | 0.00 | 744.00 | 0.00 | -64977310.0 | 59.01 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 276.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 268.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 351.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 373.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 408.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 398.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 400.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 377.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 365.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 318.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 295.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 289.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4125.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 268.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 408.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.226424E+10 | 58727.51 | 06-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127834E+10 | 58727.51 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.629237E+09 | 58727.51 | 02-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8162900.92 | 3396.04 | 11-APR-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.578887E+09 | 58727.51 | 28-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.326799E+10 | 58727.51 | 04-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.802686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.326799E+10 | 58727.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.329266E+09 | 28434.92 | 27-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.140001E+09 | 29823.41 | 03-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 73410220.08 | 25955.37 | 02-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 88787835.13 | 8503.11 | 28-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.584666E+09 | 28383.41 | 27-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.121613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.584666E+09 | 29823.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.715746E+09 | 27980.69 | 28-JAN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.336107E+09 | 29234.29 | 03-FEB-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.177936E+09 | 27463.83 | 02-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 187039.32 | 311.73 | 12-APR-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.185457E+09 | 8394.10 | 28-NOV-08:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.106698E+10 | 31026.80 | 27-DEC-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.248241E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.106698E+10 | 31026.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.844729E+09 | 30773.80 | 28-JAN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.399574E+09 | 30897.21 | 03-FEB-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.213138E+09 | 30897.21 | 02-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 428756.59 | 649.05 | 12-APR-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.212635E+09 | 10183.15 | 28-NOV-08:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.120661E+10 | 30897.21 | 27-DEC-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.287712E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.120661E+10 | 30897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.102372E+10 | 30944.40 | 27-JAN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.505556E+09 | 30944.40 | 02-FEB-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271839E+09 | 30944.40 | 02-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1360791.33 | 1117.86 | 12-APR-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.248604E+09 | 11943.91 | 28-NOV-08:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140101E+10 | 30944.40 | 27-DEC-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.345209E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.140101E+10 | 30944.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.221792E+10 | 55316.10 | 06-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.112791E+10 | 55316.10 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.549090E+09 | 55316.10 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 4839534.93 | 2646.47 | 11-APR-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.555267E+09 | 55316.10 | 28-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.296821E+10 | 55316.10 | 03-DEC-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.742323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.296821E+10 | 55316.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.118174E+10 | 28536.62 | 06-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.601672E+09 | 28536.62 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.297146E+09 | 28536.62 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2175853.31 | 1249.13 | 11-APR-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.291523E+09 | 28536.62 | 28-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.156440E+10 | 28536.62 | 03-DEC-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.393866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.156440E+10 | 28536.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.125527E+10 | 28430.83 | 06-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.648478E+09 | 28430.83 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.325413E+09 | 28430.83 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2742643.31 | 1980.85 | 11-APR-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.306737E+09 | 28430.83 | 28-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.163313E+10 | 28430.83 | 03-DEC-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.417177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.163313E+10 | 28430.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.145881E+10 | 28493.97 | 02-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.788376E+09 | 28493.97 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.411940E+09 | 28493.97 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7274332.56 | 2668.29 | 11-APR-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.352433E+09 | 28493.97 | 27-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.182603E+10 | 28493.97 | 03-DEC-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.484486E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.182603E+10 | 28493.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.202979E+10 | 31493.43 | 02-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120707E+10 | 31493.43 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.679827E+09 | 31493.43 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 25186327.83 | 8277.18 | 12-APR-08:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.495125E+09 | 31493.43 | 27-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.234679E+10 | 31493.43 | 02-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.678378E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.234679E+10 | 31493.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 487581.23 | 487581.23 | 439.35 | 03-JAN-15:00 | 439.35 | 0.00 |
February | 0.00 | 0.00 | 0.330464E+09 | 0.330464E+09 | 6075.74 | 20-FEB-16:00 | 6075.74 | 0.00 |
March | 0.00 | 0.00 | 0.920474E+09 | 0.920474E+09 | 7416.49 | 14-MAR-16:30 | 7416.49 | 0.00 |
April | 0.00 | 0.00 | 0.825938E+10 | 0.823517E+10 | 18292.63 | 29-APR-08:62 | 16356.80 | 0.00 |
May | 0.00 | 0.00 | 0.165586E+11 | 0.160903E+11 | 45804.10 | 23-MAY-08:62 | 37007.77 | 0.00 |
June | 0.00 | 0.00 | 0.236863E+11 | 0.228665E+11 | 46414.65 | 30-JUN-08:62 | 33813.28 | 0.00 |
July | 0.00 | 0.00 | 0.284991E+11 | 0.236645E+11 | 49926.50 | 19-JUL-08:62 | 26267.41 | 0.00 |
August | 0.00 | 0.00 | 0.249035E+11 | 0.221035E+11 | 48920.61 | 02-AUG-08:61 | 31885.18 | 0.00 |
September | 0.00 | 0.00 | 0.209333E+11 | 0.182537E+11 | 48240.42 | 22-SEP-08:61 | 29494.71 | 0.00 |
October | 0.00 | 0.00 | 0.970449E+10 | 0.869960E+10 | 47352.62 | 04-OCT-08:62 | 29228.05 | 0.00 |
November | 0.00 | 0.00 | 0.796828E+09 | 0.788120E+09 | 30311.15 | 10-NOV-09:02 | 27963.11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.134593E+12 | 0.121953E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.284991E+11 | 0.236645E+11 | 49926.50 | 37007.77 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 13202528.32 | 13170912.06 | 2752.20 | 01-JAN-18:10 | 2752.20 | 0.00 |
February | 0.00 | 0.00 | 0.305614E+09 | 0.305572E+09 | 22008.57 | 19-FEB-18:08 | 22008.57 | 0.00 |
March | 0.00 | 0.00 | 0.778004E+09 | 0.777888E+09 | 22008.57 | 12-MAR-17:09 | 22008.57 | 0.00 |
April | 0.00 | 0.00 | 0.528582E+10 | 0.526545E+10 | 22776.24 | 18-APR-20:56 | 20306.29 | 0.00 |
May | 0.00 | 0.00 | 0.929292E+10 | 0.899420E+10 | 23772.51 | 27-MAY-21:00 | 17845.23 | 0.00 |
June | 0.00 | 0.00 | 0.122120E+11 | 0.117690E+11 | 23925.81 | 30-JUN-08:62 | 17976.10 | 0.00 |
July | 0.00 | 0.00 | 0.144647E+11 | 0.120953E+11 | 25170.42 | 19-JUL-08:62 | 16257.49 | 0.00 |
August | 0.00 | 0.00 | 0.129367E+11 | 0.114386E+11 | 24902.98 | 03-AUG-08:61 | 17973.52 | 0.00 |
September | 0.00 | 0.00 | 0.115553E+11 | 0.100893E+11 | 24822.38 | 22-SEP-08:61 | 15812.33 | 0.00 |
October | 0.00 | 0.00 | 0.602137E+10 | 0.537197E+10 | 24622.50 | 03-OCT-20:03 | 14824.27 | 0.00 |
November | 0.00 | 0.00 | 0.587149E+09 | 0.580873E+09 | 22008.57 | 09-NOV-21:44 | 21519.66 | 0.00 |
December | 0.00 | 0.00 | 4957521.50 | 4955677.64 | 2680.18 | 10-DEC-18:10 | 2680.18 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.734578E+11 | 0.667063E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4957521.50 | 4955677.64 | 2680.18 | 2680.18 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.144647E+11 | 0.120953E+11 | 25170.42 | 22008.57 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1431675.45 | 1431675.45 | 480.72 | 03-JAN-15:00 | 480.72 | 0.00 |
February | 0.00 | 0.00 | 0.175435E+09 | 0.175435E+09 | 3025.56 | 20-FEB-15:00 | 3025.56 | 0.00 |
March | 0.00 | 0.00 | 0.533569E+09 | 0.533569E+09 | 4208.79 | 22-MAR-13:00 | 4208.79 | 0.00 |
April | 0.00 | 0.00 | 0.341114E+10 | 0.340095E+10 | 13496.74 | 20-APR-07:03 | 13496.74 | 0.00 |
May | 0.00 | 0.00 | 0.674796E+10 | 0.657114E+10 | 24457.87 | 28-MAY-08:62 | 18859.67 | 0.00 |
June | 0.00 | 0.00 | 0.954069E+10 | 0.922132E+10 | 24672.42 | 04-JUN-08:61 | 19762.40 | 0.00 |
July | 0.00 | 0.00 | 0.112458E+11 | 0.935229E+10 | 26112.44 | 19-JUL-07:02 | 11400.37 | 0.00 |
August | 0.00 | 0.00 | 0.996316E+10 | 0.878238E+10 | 25963.52 | 03-AUG-07:01 | 15367.21 | 0.00 |
September | 0.00 | 0.00 | 0.861176E+10 | 0.756782E+10 | 25436.46 | 23-SEP-07:01 | 15580.14 | 0.00 |
October | 0.00 | 0.00 | 0.411173E+10 | 0.372206E+10 | 24837.41 | 04-OCT-07:02 | 15294.15 | 0.00 |
November | 0.00 | 0.00 | 0.430919E+09 | 0.426286E+09 | 13085.18 | 10-NOV-08:62 | 12041.11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.547736E+11 | 0.497547E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.112458E+11 | 0.935229E+10 | 26112.44 | 19762.40 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 281107.82 | 281107.82 | 219.12 | 03-JAN-15:00 | 219.12 | 0.00 |
February | 0.00 | 0.00 | 0.152353E+09 | 0.152353E+09 | 2807.01 | 20-FEB-15:00 | 2807.01 | 0.00 |
March | 0.00 | 0.00 | 0.492492E+09 | 0.492492E+09 | 4071.78 | 22-MAR-13:00 | 4071.78 | 0.00 |
April | 0.00 | 0.00 | 0.337421E+10 | 0.336385E+10 | 13277.56 | 20-APR-07:03 | 13277.56 | 0.00 |
May | 0.00 | 0.00 | 0.676898E+10 | 0.658950E+10 | 24323.29 | 28-MAY-08:62 | 18742.30 | 0.00 |
June | 0.00 | 0.00 | 0.960228E+10 | 0.927683E+10 | 24537.35 | 04-JUN-08:61 | 19644.40 | 0.00 |
July | 0.00 | 0.00 | 0.113264E+11 | 0.941398E+10 | 25967.71 | 19-JUL-07:02 | 11342.68 | 0.00 |
August | 0.00 | 0.00 | 0.100394E+11 | 0.884168E+10 | 25819.70 | 03-AUG-07:01 | 15277.78 | 0.00 |
September | 0.00 | 0.00 | 0.866567E+10 | 0.760930E+10 | 25296.11 | 23-SEP-07:01 | 15491.79 | 0.00 |
October | 0.00 | 0.00 | 0.410503E+10 | 0.371412E+10 | 24699.84 | 04-OCT-07:02 | 15204.47 | 0.00 |
November | 0.00 | 0.00 | 0.407353E+09 | 0.402768E+09 | 12710.28 | 10-NOV-08:62 | 11666.45 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.549345E+11 | 0.498571E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.113264E+11 | 0.941398E+10 | 25967.71 | 19644.40 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.122739E+09 | 0.122739E+09 | 2528.08 | 20-FEB-15:00 | 2528.08 | 0.00 |
March | 0.00 | 0.00 | 0.425068E+09 | 0.425068E+09 | 3842.39 | 22-MAR-13:00 | 3842.39 | 0.00 |
April | 0.00 | 0.00 | 0.322767E+10 | 0.321824E+10 | 11493.83 | 20-APR-07:03 | 11493.83 | 0.00 |
May | 0.00 | 0.00 | 0.660483E+10 | 0.643106E+10 | 24386.05 | 28-MAY-08:62 | 18785.53 | 0.00 |
June | 0.00 | 0.00 | 0.945048E+10 | 0.913455E+10 | 24601.92 | 04-JUN-08:61 | 19692.11 | 0.00 |
July | 0.00 | 0.00 | 0.111655E+11 | 0.928395E+10 | 26037.37 | 19-JUL-07:02 | 11345.98 | 0.00 |
August | 0.00 | 0.00 | 0.987906E+10 | 0.870746E+10 | 25888.83 | 03-AUG-07:01 | 15297.65 | 0.00 |
September | 0.00 | 0.00 | 0.850828E+10 | 0.747425E+10 | 25363.00 | 23-SEP-07:01 | 15514.22 | 0.00 |
October | 0.00 | 0.00 | 0.397082E+10 | 0.359537E+10 | 24765.55 | 04-OCT-07:02 | 15227.11 | 0.00 |
November | 0.00 | 0.00 | 0.360730E+09 | 0.356766E+09 | 11214.02 | 10-NOV-08:62 | 10235.96 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.537152E+11 | 0.487495E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.111655E+11 | 0.928395E+10 | 26037.37 | 19692.11 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.185414E+09 | 0.185414E+09 | 4399.62 | 20-FEB-15:30 | 4399.62 | 0.00 |
March | 0.00 | 0.00 | 0.650428E+09 | 0.650428E+09 | 6661.07 | 22-MAR-13:00 | 6661.07 | 0.00 |
April | 0.00 | 0.00 | 0.558272E+10 | 0.556288E+10 | 18428.97 | 29-APR-08:62 | 16703.07 | 0.00 |
May | 0.00 | 0.00 | 0.117208E+11 | 0.113933E+11 | 43343.96 | 28-MAY-09:02 | 34218.67 | 0.00 |
June | 0.00 | 0.00 | 0.170271E+11 | 0.164362E+11 | 43972.99 | 04-JUN-09:01 | 35776.69 | 0.00 |
July | 0.00 | 0.00 | 0.199416E+11 | 0.164919E+11 | 45990.79 | 17-JUL-08:61 | 24583.49 | 0.00 |
August | 0.00 | 0.00 | 0.177423E+11 | 0.155740E+11 | 44946.29 | 09-AUG-08:61 | 32817.20 | 0.00 |
September | 0.00 | 0.00 | 0.151928E+11 | 0.133153E+11 | 45105.70 | 22-SEP-08:61 | 28213.41 | 0.00 |
October | 0.00 | 0.00 | 0.698825E+10 | 0.625862E+10 | 44391.52 | 04-OCT-08:62 | 27613.46 | 0.00 |
November | 0.00 | 0.00 | 0.567788E+09 | 0.559945E+09 | 28562.85 | 10-NOV-09:02 | 26244.33 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.955993E+11 | 0.864281E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.199416E+11 | 0.164919E+11 | 45990.79 | 35776.69 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 84207973.08 | 84207973.08 | 2172.78 | 20-FEB-15:40 | 2172.78 | 0.00 |
March | 0.00 | 0.00 | 0.306579E+09 | 0.306579E+09 | 3313.16 | 22-MAR-13:00 | 3313.16 | 0.00 |
April | 0.00 | 0.00 | 0.284022E+10 | 0.283108E+10 | 8064.12 | 29-APR-08:62 | 7337.18 | 0.00 |
May | 0.00 | 0.00 | 0.601383E+10 | 0.585114E+10 | 22384.74 | 28-MAY-09:02 | 17737.97 | 0.00 |
June | 0.00 | 0.00 | 0.875233E+10 | 0.845765E+10 | 22702.10 | 04-JUN-09:01 | 18493.49 | 0.00 |
July | 0.00 | 0.00 | 0.102462E+11 | 0.849814E+10 | 23754.00 | 17-JUL-08:61 | 12728.94 | 0.00 |
August | 0.00 | 0.00 | 0.911495E+10 | 0.802191E+10 | 23211.76 | 09-AUG-08:61 | 17009.34 | 0.00 |
September | 0.00 | 0.00 | 0.780613E+10 | 0.685911E+10 | 23295.31 | 22-SEP-08:61 | 14610.62 | 0.00 |
October | 0.00 | 0.00 | 0.357449E+10 | 0.321024E+10 | 22926.88 | 04-OCT-08:62 | 14303.32 | 0.00 |
November | 0.00 | 0.00 | 0.278598E+09 | 0.275169E+09 | 13251.19 | 10-NOV-09:02 | 12175.30 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.490176E+11 | 0.443952E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.102462E+11 | 0.849814E+10 | 23754.00 | 18493.49 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 76568644.61 | 76568644.61 | 2076.34 | 20-FEB-15:40 | 2076.34 | 0.00 |
March | 0.00 | 0.00 | 0.283859E+09 | 0.283859E+09 | 3202.00 | 22-MAR-13:00 | 3202.00 | 0.00 |
April | 0.00 | 0.00 | 0.278343E+10 | 0.277455E+10 | 7754.94 | 21-APR-14:40 | 7754.94 | 0.00 |
May | 0.00 | 0.00 | 0.595348E+10 | 0.579237E+10 | 22295.28 | 28-MAY-09:02 | 17652.25 | 0.00 |
June | 0.00 | 0.00 | 0.869519E+10 | 0.840285E+10 | 22608.96 | 04-JUN-09:01 | 18388.01 | 0.00 |
July | 0.00 | 0.00 | 0.101866E+11 | 0.844700E+10 | 23660.24 | 17-JUL-08:61 | 12668.03 | 0.00 |
August | 0.00 | 0.00 | 0.906062E+10 | 0.797396E+10 | 23120.47 | 09-AUG-08:61 | 16928.96 | 0.00 |
September | 0.00 | 0.00 | 0.775421E+10 | 0.681231E+10 | 23203.39 | 22-SEP-08:61 | 14541.76 | 0.00 |
October | 0.00 | 0.00 | 0.352673E+10 | 0.316712E+10 | 22836.15 | 04-OCT-08:62 | 14234.45 | 0.00 |
November | 0.00 | 0.00 | 0.264057E+09 | 0.260781E+09 | 12485.83 | 10-NOV-09:02 | 11437.72 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.485848E+11 | 0.439914E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.101866E+11 | 0.844700E+10 | 23660.24 | 18388.01 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 60232296.13 | 60232296.13 | 1896.55 | 20-FEB-15:30 | 1896.55 | 0.00 |
March | 0.00 | 0.00 | 0.236374E+09 | 0.236374E+09 | 2968.18 | 22-MAR-13:00 | 2968.18 | 0.00 |
April | 0.00 | 0.00 | 0.267192E+10 | 0.266371E+10 | 7661.16 | 21-APR-14:40 | 7661.16 | 0.00 |
May | 0.00 | 0.00 | 0.586834E+10 | 0.571014E+10 | 22343.65 | 28-MAY-09:02 | 17672.18 | 0.00 |
June | 0.00 | 0.00 | 0.868001E+10 | 0.839036E+10 | 22655.94 | 04-JUN-09:01 | 18395.38 | 0.00 |
July | 0.00 | 0.00 | 0.102005E+11 | 0.846253E+10 | 23714.45 | 17-JUL-08:61 | 12688.38 | 0.00 |
August | 0.00 | 0.00 | 0.908337E+10 | 0.799866E+10 | 23173.85 | 09-AUG-08:61 | 16969.25 | 0.00 |
September | 0.00 | 0.00 | 0.776232E+10 | 0.682037E+10 | 23257.20 | 22-SEP-08:61 | 14572.88 | 0.00 |
October | 0.00 | 0.00 | 0.346079E+10 | 0.310900E+10 | 22887.54 | 04-OCT-08:62 | 14250.46 | 0.00 |
November | 0.00 | 0.00 | 0.237427E+09 | 0.234486E+09 | 10359.71 | 10-NOV-09:02 | 9402.86 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.482613E+11 | 0.436858E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.102005E+11 | 0.846253E+10 | 23714.45 | 18395.38 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 40521247.79 | 40521247.79 | 1728.42 | 20-FEB-15:30 | 1728.42 | 0.00 |
March | 0.00 | 0.00 | 0.191182E+09 | 0.191182E+09 | 2935.16 | 22-MAR-13:00 | 2935.16 | 0.00 |
April | 0.00 | 0.00 | 0.279044E+10 | 0.278297E+10 | 8117.12 | 21-APR-14:20 | 8117.12 | 0.00 |
May | 0.00 | 0.00 | 0.636613E+10 | 0.619809E+10 | 24625.26 | 28-MAY-09:02 | 19189.56 | 0.00 |
June | 0.00 | 0.00 | 0.965457E+10 | 0.934101E+10 | 24656.77 | 04-JUN-09:03 | 20239.71 | 0.00 |
July | 0.00 | 0.00 | 0.114545E+11 | 0.955138E+10 | 26263.94 | 19-JUL-08:62 | 14430.14 | 0.00 |
August | 0.00 | 0.00 | 0.103116E+11 | 0.911948E+10 | 25817.15 | 03-AUG-08:61 | 17670.59 | 0.00 |
September | 0.00 | 0.00 | 0.885762E+10 | 0.780865E+10 | 25632.92 | 22-SEP-08:61 | 15682.62 | 0.00 |
October | 0.00 | 0.00 | 0.375628E+10 | 0.338727E+10 | 25121.59 | 04-OCT-08:62 | 15541.39 | 0.00 |
November | 0.00 | 0.00 | 0.228524E+09 | 0.225914E+09 | 6548.81 | 10-NOV-09:02 | 5929.32 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.536514E+11 | 0.486465E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.114545E+11 | 0.955138E+10 | 26263.94 | 20239.71 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.191471E+10 | 0.42 | 2556.55 | 06-JAN-09:01 | 1.02 |
February | 0.171223E+10 | 0.42 | 2556.55 | 01-FEB-09:01 | 1.01 |
March | 0.187932E+10 | 0.42 | 2556.55 | 02-MAR-09:01 | 1.02 |
April | 0.179675E+10 | 0.42 | 1111.32 | 11-APR-08:13 | 0.65 |
May | 0.185743E+10 | 0.41 | 2556.55 | 09-MAY-08:62 | 1.01 |
June | 0.182825E+10 | 0.42 | 2556.55 | 01-JUN-08:62 | 1.01 |
July | 0.187455E+10 | 0.41 | 2556.55 | 01-JUL-08:61 | 1.00 |
August | 0.187097E+10 | 0.41 | 2556.55 | 01-AUG-08:61 | 1.00 |
September | 0.180475E+10 | 0.41 | 2556.55 | 01-SEP-08:62 | 1.00 |
October | 0.185644E+10 | 0.41 | 2556.55 | 02-OCT-08:61 | 1.00 |
November | 0.180805E+10 | 0.42 | 2556.55 | 28-NOV-09:01 | 1.01 |
December | 0.194848E+10 | 0.43 | 2556.55 | 04-DEC-09:01 | 1.01 |
Annual Sum or Average | 0.221519E+11 | 0.42 | |||
Minimum of Months | 0.171223E+10 | 0.41 | 1111.32 | 0.65 | |
Maximum of Months | 0.194848E+10 | 0.43 | 2556.55 | 1.02 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.774639E+09 | 0.37 | 1325.26 | 27-JAN-09:01 | 1.03 |
February | 0.755460E+09 | 0.39 | 1363.07 | 03-FEB-09:01 | 1.04 |
March | 0.888829E+09 | 0.42 | 1257.73 | 02-MAR-09:01 | 1.01 |
April | 0.847162E+09 | 0.41 | 736.69 | 29-APR-08:62 | 0.76 |
May | 0.857422E+09 | 0.41 | 1377.15 | 09-MAY-08:62 | 1.05 |
June | 0.856418E+09 | 0.43 | 1377.15 | 01-JUN-08:62 | 1.05 |
July | 0.888329E+09 | 0.43 | 1377.15 | 01-JUL-08:61 | 1.04 |
August | 0.883878E+09 | 0.42 | 1377.15 | 01-AUG-08:61 | 1.03 |
September | 0.844213E+09 | 0.41 | 1377.15 | 01-SEP-08:62 | 1.03 |
October | 0.910996E+09 | 0.41 | 1377.15 | 02-OCT-08:61 | 1.04 |
November | 0.859535E+09 | 0.42 | 1250.85 | 10-NOV-09:02 | 1.00 |
December | 0.774943E+09 | 0.36 | 1323.85 | 27-DEC-09:01 | 1.03 |
Annual Sum or Average | 0.101418E+11 | 0.41 | |||
Minimum of Months | 0.755460E+09 | 0.36 | 736.69 | 0.76 | |
Maximum of Months | 0.910996E+09 | 0.43 | 1377.15 | 1.05 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.838986E+09 | 0.35 | 1332.10 | 28-JAN-08:62 | 1.02 |
February | 0.751139E+09 | 0.35 | 1366.42 | 03-FEB-08:62 | 1.04 |
March | 0.840571E+09 | 0.35 | 1317.95 | 02-MAR-08:61 | 1.02 |
April | 0.794980E+09 | 0.34 | 732.33 | 20-APR-07:03 | 0.75 |
May | 0.829270E+09 | 0.35 | 1415.48 | 09-MAY-07:02 | 1.05 |
June | 0.816129E+09 | 0.35 | 1415.48 | 01-JUN-07:02 | 1.05 |
July | 0.822483E+09 | 0.34 | 1415.48 | 01-JUL-07:01 | 1.04 |
August | 0.839916E+09 | 0.35 | 1415.48 | 01-AUG-07:01 | 1.03 |
September | 0.797566E+09 | 0.34 | 1415.48 | 01-SEP-07:02 | 1.03 |
October | 0.820047E+09 | 0.34 | 1415.48 | 02-OCT-07:01 | 1.04 |
November | 0.800032E+09 | 0.34 | 795.96 | 28-NOV-08:63 | 0.78 |
December | 0.844524E+09 | 0.35 | 1415.48 | 27-DEC-08:62 | 1.05 |
Annual Sum or Average | 0.979564E+10 | 0.35 | |||
Minimum of Months | 0.751139E+09 | 0.34 | 732.33 | 0.75 | |
Maximum of Months | 0.844524E+09 | 0.35 | 1415.48 | 1.05 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.838306E+09 | 0.35 | 1404.87 | 28-JAN-08:62 | 1.05 |
February | 0.749073E+09 | 0.35 | 1408.25 | 03-FEB-08:62 | 1.05 |
March | 0.837257E+09 | 0.35 | 1408.25 | 02-MAR-08:61 | 1.05 |
April | 0.790926E+09 | 0.34 | 717.79 | 20-APR-07:03 | 0.74 |
May | 0.825079E+09 | 0.35 | 1408.25 | 09-MAY-07:02 | 1.05 |
June | 0.813116E+09 | 0.35 | 1408.25 | 01-JUN-07:02 | 1.05 |
July | 0.819221E+09 | 0.34 | 1408.25 | 01-JUL-07:01 | 1.04 |
August | 0.836083E+09 | 0.35 | 1408.25 | 01-AUG-07:01 | 1.03 |
September | 0.793553E+09 | 0.34 | 1408.25 | 01-SEP-07:02 | 1.03 |
October | 0.815876E+09 | 0.34 | 1408.25 | 02-OCT-07:01 | 1.04 |
November | 0.796702E+09 | 0.35 | 841.78 | 28-NOV-08:63 | 0.81 |
December | 0.844147E+09 | 0.35 | 1408.25 | 27-DEC-08:62 | 1.05 |
Annual Sum or Average | 0.975934E+10 | 0.35 | |||
Minimum of Months | 0.749073E+09 | 0.34 | 717.79 | 0.74 | |
Maximum of Months | 0.844147E+09 | 0.35 | 1408.25 | 1.05 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.844736E+09 | 0.35 | 1410.88 | 27-JAN-08:62 | 1.05 |
February | 0.753357E+09 | 0.35 | 1410.88 | 02-FEB-08:62 | 1.05 |
March | 0.840420E+09 | 0.35 | 1410.88 | 02-MAR-08:61 | 1.05 |
April | 0.792390E+09 | 0.34 | 594.93 | 12-APR-07:30 | 0.66 |
May | 0.826438E+09 | 0.35 | 1410.88 | 09-MAY-07:02 | 1.05 |
June | 0.812912E+09 | 0.35 | 1410.88 | 01-JUN-07:02 | 1.05 |
July | 0.819713E+09 | 0.34 | 1410.88 | 01-JUL-07:01 | 1.04 |
August | 0.837172E+09 | 0.35 | 1410.88 | 01-AUG-07:01 | 1.03 |
September | 0.794930E+09 | 0.34 | 1410.88 | 01-SEP-07:02 | 1.03 |
October | 0.817325E+09 | 0.34 | 1410.88 | 02-OCT-07:01 | 1.04 |
November | 0.799151E+09 | 0.35 | 891.09 | 28-NOV-08:63 | 0.84 |
December | 0.850994E+09 | 0.35 | 1410.88 | 27-DEC-08:62 | 1.05 |
Annual Sum or Average | 0.978954E+10 | 0.35 | |||
Minimum of Months | 0.753357E+09 | 0.34 | 594.93 | 0.66 | |
Maximum of Months | 0.850994E+09 | 0.35 | 1410.88 | 1.05 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.132453E+10 | 0.31 | 2372.45 | 06-JAN-09:01 | 1.02 |
February | 0.117691E+10 | 0.31 | 2372.45 | 01-FEB-09:01 | 1.01 |
March | 0.130892E+10 | 0.32 | 2372.45 | 01-MAR-09:01 | 1.01 |
April | 0.123000E+10 | 0.31 | 1017.08 | 11-APR-08:30 | 0.64 |
May | 0.128398E+10 | 0.31 | 2372.45 | 09-MAY-08:62 | 1.01 |
June | 0.127392E+10 | 0.31 | 2372.45 | 01-JUN-08:62 | 1.01 |
July | 0.128444E+10 | 0.30 | 2372.45 | 01-JUL-08:61 | 1.01 |
August | 0.130819E+10 | 0.31 | 2372.45 | 01-AUG-08:61 | 1.00 |
September | 0.123498E+10 | 0.30 | 2372.45 | 01-SEP-08:62 | 1.00 |
October | 0.126866E+10 | 0.30 | 2372.45 | 01-OCT-09:02 | 1.01 |
November | 0.124424E+10 | 0.31 | 2372.45 | 28-NOV-09:01 | 1.01 |
December | 0.133701E+10 | 0.32 | 2372.45 | 03-DEC-10:01 | 1.01 |
Annual Sum or Average | 0.152758E+11 | 0.31 | |||
Minimum of Months | 0.117691E+10 | 0.30 | 1017.08 | 0.64 | |
Maximum of Months | 0.133701E+10 | 0.32 | 2372.45 | 1.02 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.713629E+09 | 0.33 | 1276.42 | 06-JAN-09:01 | 1.05 |
February | 0.633730E+09 | 0.32 | 1276.42 | 01-FEB-09:01 | 1.05 |
March | 0.704593E+09 | 0.33 | 1276.42 | 01-MAR-09:01 | 1.05 |
April | 0.661754E+09 | 0.32 | 544.09 | 11-APR-08:13 | 0.66 |
May | 0.690628E+09 | 0.32 | 1276.42 | 09-MAY-08:62 | 1.05 |
June | 0.685429E+09 | 0.32 | 1276.42 | 01-JUN-08:62 | 1.05 |
July | 0.690743E+09 | 0.31 | 1276.42 | 01-JUL-08:61 | 1.04 |
August | 0.703588E+09 | 0.32 | 1276.42 | 01-AUG-08:61 | 1.03 |
September | 0.664163E+09 | 0.31 | 1276.42 | 01-SEP-08:62 | 1.03 |
October | 0.682492E+09 | 0.31 | 1276.42 | 01-OCT-09:02 | 1.04 |
November | 0.669546E+09 | 0.32 | 1276.42 | 28-NOV-09:01 | 1.05 |
December | 0.720223E+09 | 0.33 | 1276.42 | 03-DEC-10:01 | 1.05 |
Annual Sum or Average | 0.822052E+10 | 0.32 | |||
Minimum of Months | 0.633730E+09 | 0.31 | 544.09 | 0.66 | |
Maximum of Months | 0.720223E+09 | 0.33 | 1276.42 | 1.05 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.712415E+09 | 0.33 | 1270.51 | 06-JAN-09:01 | 1.05 |
February | 0.632112E+09 | 0.32 | 1270.51 | 01-FEB-09:01 | 1.05 |
March | 0.702120E+09 | 0.33 | 1270.51 | 01-MAR-09:01 | 1.05 |
April | 0.658707E+09 | 0.32 | 561.32 | 11-APR-08:13 | 0.68 |
May | 0.687380E+09 | 0.32 | 1270.51 | 09-MAY-08:62 | 1.05 |
June | 0.682131E+09 | 0.32 | 1270.51 | 01-JUN-08:62 | 1.05 |
July | 0.687431E+09 | 0.31 | 1270.51 | 01-JUL-08:61 | 1.04 |
August | 0.700288E+09 | 0.32 | 1270.51 | 01-AUG-08:61 | 1.03 |
September | 0.661046E+09 | 0.31 | 1270.51 | 01-SEP-08:62 | 1.03 |
October | 0.679313E+09 | 0.31 | 1270.51 | 02-OCT-08:61 | 1.04 |
November | 0.666878E+09 | 0.32 | 1270.51 | 28-NOV-09:01 | 1.05 |
December | 0.718888E+09 | 0.33 | 1270.51 | 03-DEC-10:01 | 1.05 |
Annual Sum or Average | 0.818871E+10 | 0.32 | |||
Minimum of Months | 0.632112E+09 | 0.31 | 561.32 | 0.68 | |
Maximum of Months | 0.718888E+09 | 0.33 | 1270.51 | 1.05 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.719778E+09 | 0.33 | 1274.04 | 02-JAN-09:01 | 1.04 |
February | 0.637581E+09 | 0.32 | 1274.04 | 01-FEB-09:01 | 1.05 |
March | 0.706370E+09 | 0.33 | 1274.04 | 01-MAR-09:01 | 1.05 |
April | 0.660656E+09 | 0.32 | 581.20 | 11-APR-08:10 | 0.69 |
May | 0.689160E+09 | 0.32 | 1274.04 | 09-MAY-08:62 | 1.05 |
June | 0.683774E+09 | 0.32 | 1274.04 | 01-JUN-08:62 | 1.05 |
July | 0.689413E+09 | 0.31 | 1274.04 | 01-JUL-08:61 | 1.04 |
August | 0.702517E+09 | 0.32 | 1274.04 | 01-AUG-08:61 | 1.03 |
September | 0.662820E+09 | 0.31 | 1274.04 | 01-SEP-08:62 | 1.03 |
October | 0.681143E+09 | 0.31 | 1274.04 | 02-OCT-08:61 | 1.04 |
November | 0.669917E+09 | 0.32 | 1274.04 | 27-NOV-09:01 | 1.05 |
December | 0.725961E+09 | 0.33 | 1274.04 | 03-DEC-10:01 | 1.05 |
Annual Sum or Average | 0.822909E+10 | 0.32 | |||
Minimum of Months | 0.637581E+09 | 0.31 | 581.20 | 0.69 | |
Maximum of Months | 0.725961E+09 | 0.33 | 1274.04 | 1.05 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.825859E+09 | 0.33 | 1441.51 | 02-JAN-09:01 | 1.04 |
February | 0.730612E+09 | 0.33 | 1441.51 | 01-FEB-09:01 | 1.05 |
March | 0.805391E+09 | 0.33 | 1441.51 | 01-MAR-09:01 | 1.05 |
April | 0.747973E+09 | 0.32 | 803.92 | 12-APR-08:63 | 0.78 |
May | 0.779471E+09 | 0.32 | 1441.51 | 09-MAY-08:62 | 1.05 |
June | 0.773816E+09 | 0.32 | 1441.51 | 01-JUN-08:62 | 1.05 |
July | 0.783447E+09 | 0.31 | 1441.51 | 01-JUL-08:61 | 1.04 |
August | 0.798535E+09 | 0.32 | 1441.51 | 01-AUG-08:61 | 1.03 |
September | 0.750193E+09 | 0.31 | 1441.51 | 01-SEP-08:62 | 1.03 |
October | 0.770553E+09 | 0.31 | 1441.51 | 02-OCT-08:61 | 1.04 |
November | 0.760879E+09 | 0.32 | 1441.51 | 27-NOV-09:01 | 1.05 |
December | 0.830414E+09 | 0.33 | 1441.51 | 02-DEC-09:02 | 1.05 |
Annual Sum or Average | 0.935714E+10 | 0.32 | |||
Minimum of Months | 0.730612E+09 | 0.31 | 803.92 | 0.78 | |
Maximum of Months | 0.830414E+09 | 0.33 | 1441.51 | 1.05 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.191485E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.180414E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.213529E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.409514E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.647210E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.861797E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.948727E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.858815E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.731603E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.440186E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.202290E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.194848E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.588042E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.180414E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.948727E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.778284E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.835494E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.109380E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.223268E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.335149E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.428586E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.469217E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.429646E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.378163E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.241081E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.101232E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.776301E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.295473E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.776301E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.469217E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.839387E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.799072E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.985700E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.172639E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.267695E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.350423E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.377079E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.347199E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.303795E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.188142E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.914238E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.844524E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.244526E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.799072E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.377079E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.838385E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.790875E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.971571E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.171264E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.267602E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.351312E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.378183E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.348232E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.304332E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.187475E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.904761E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.844147E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.244337E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.790875E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.378183E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.844736E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.787244E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.956983E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.167861E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.263963E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.347851E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.374947E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.344963E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.301157E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.184539E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.895160E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.850994E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.241879E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.787244E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.374947E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.132453E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.122918E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.149130E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.279698E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.456202E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.616720E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.659284E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.607015E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.524760E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.310648E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.139827E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.133701E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.413236E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.122918E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.659284E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.713629E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.657116E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.789255E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.144600E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.234464E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.315931E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.337385E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.310973E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.269173E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.160680E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.743844E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.720223E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.213561E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.657116E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.337385E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.712415E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.653424E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.780693E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.142849E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.232609E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.314081E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.335561E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.309283E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.267586E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.159199E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.737387E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.718888E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.212145E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.653424E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.335561E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.719778E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.654429E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.772176E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.140275E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.230802E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.314006E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.336208E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.310107E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.267990E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.157824E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.733479E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.725961E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.211779E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.654429E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.336208E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.825859E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.742035E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.859150E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.152671E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.253923E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.349971E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.377934E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.350749E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.303691E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.174442E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.822201E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.830414E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.237135E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.742035E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.377934E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.191471E+10 | 487581.23 | 0.226424E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.171223E+10 | 0.330464E+09 | 0.127834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.187932E+10 | 0.920474E+09 | 0.629237E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.179675E+10 | 0.825938E+10 | 8162900.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.185743E+10 | 0.165586E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.182825E+10 | 0.236863E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.187455E+10 | 0.284991E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.187097E+10 | 0.249035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.180475E+10 | 0.209333E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.185644E+10 | 0.970449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.180805E+10 | 0.796828E+09 | 0.578887E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.194848E+10 | 0.00 | 0.326799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.221519E+11 | 0.134593E+12 | 0.802686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.171223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.194848E+10 | 0.284991E+11 | 0.326799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.774639E+09 | 13202528.32 | 0.329266E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.755460E+09 | 0.293143E+09 | 0.140001E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.888829E+09 | 0.752989E+09 | 73410220.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.847162E+09 | 0.499477E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.857422E+09 | 0.902713E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.856418E+09 | 0.121145E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.888329E+09 | 0.143864E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.883878E+09 | 0.127406E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.844213E+09 | 0.111104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.910996E+09 | 0.568166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.859535E+09 | 0.576797E+09 | 88787835.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.774943E+09 | 4957521.50 | 0.584666E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.101418E+11 | 0.716966E+11 | 0.121613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.755460E+09 | 4957521.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.910996E+09 | 0.143864E+11 | 0.584666E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.838986E+09 | 1431675.45 | 0.715746E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.751139E+09 | 0.175435E+09 | 0.336107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.840571E+09 | 0.533569E+09 | 0.177936E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.794980E+09 | 0.341114E+10 | 187039.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.829270E+09 | 0.674796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.816129E+09 | 0.954069E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.822483E+09 | 0.112458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.839916E+09 | 0.996316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.797566E+09 | 0.861176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.820047E+09 | 0.411173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.800032E+09 | 0.430919E+09 | 0.185457E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.844524E+09 | 0.00 | 0.106698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.979564E+10 | 0.547736E+11 | 0.248241E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.751139E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.844524E+09 | 0.112458E+11 | 0.106698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.838306E+09 | 281107.82 | 0.844729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.749073E+09 | 0.152353E+09 | 0.399574E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.837257E+09 | 0.492492E+09 | 0.213138E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.790926E+09 | 0.337421E+10 | 428756.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.825079E+09 | 0.676898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.813116E+09 | 0.960228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.819221E+09 | 0.113264E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.836083E+09 | 0.100394E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.793553E+09 | 0.866567E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.815876E+09 | 0.410503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.796702E+09 | 0.407353E+09 | 0.212635E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.844147E+09 | 0.00 | 0.120661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.975934E+10 | 0.549345E+11 | 0.287712E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.749073E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.844147E+09 | 0.113264E+11 | 0.120661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.844736E+09 | 0.00 | 0.102372E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.753357E+09 | 0.122739E+09 | 0.505556E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.840420E+09 | 0.425068E+09 | 0.271839E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.792390E+09 | 0.322767E+10 | 1360791.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.826438E+09 | 0.660483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.812912E+09 | 0.945048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.819713E+09 | 0.111655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.837172E+09 | 0.987906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.794930E+09 | 0.850828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.817325E+09 | 0.397082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.799151E+09 | 0.360730E+09 | 0.248604E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.850994E+09 | 0.00 | 0.140101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.978954E+10 | 0.537152E+11 | 0.345209E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.753357E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.850994E+09 | 0.111655E+11 | 0.140101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.132453E+10 | 0.00 | 0.221792E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117691E+10 | 0.185414E+09 | 0.112791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130892E+10 | 0.650428E+09 | 0.549090E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.123000E+10 | 0.558272E+10 | 4839534.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.128398E+10 | 0.117208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.127392E+10 | 0.170271E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.128444E+10 | 0.199416E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130819E+10 | 0.177423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.123498E+10 | 0.151928E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.126866E+10 | 0.698825E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.124424E+10 | 0.567788E+09 | 0.555267E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133701E+10 | 0.00 | 0.296821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.152758E+11 | 0.955993E+11 | 0.742323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.117691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.133701E+10 | 0.199416E+11 | 0.296821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.713629E+09 | 0.00 | 0.118174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.633730E+09 | 84207973.08 | 0.601672E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.704593E+09 | 0.306579E+09 | 0.297146E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.661754E+09 | 0.284022E+10 | 2175853.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.690628E+09 | 0.601383E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.685429E+09 | 0.875233E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.690743E+09 | 0.102462E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.703588E+09 | 0.911495E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.664163E+09 | 0.780613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.682492E+09 | 0.357449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.669546E+09 | 0.278598E+09 | 0.291523E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.720223E+09 | 0.00 | 0.156440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.822052E+10 | 0.490176E+11 | 0.393866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.633730E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.720223E+09 | 0.102462E+11 | 0.156440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.712415E+09 | 0.00 | 0.125527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.632112E+09 | 76568644.61 | 0.648478E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.702120E+09 | 0.283859E+09 | 0.325413E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.658707E+09 | 0.278343E+10 | 2742643.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.687380E+09 | 0.595348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.682131E+09 | 0.869519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.687431E+09 | 0.101866E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.700288E+09 | 0.906062E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.661046E+09 | 0.775421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.679313E+09 | 0.352673E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.666878E+09 | 0.264057E+09 | 0.306737E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.718888E+09 | 0.00 | 0.163313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.818871E+10 | 0.485848E+11 | 0.417177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.632112E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.718888E+09 | 0.101866E+11 | 0.163313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.719778E+09 | 0.00 | 0.145881E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.637581E+09 | 60232296.13 | 0.788376E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.706370E+09 | 0.236374E+09 | 0.411940E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.660656E+09 | 0.267192E+10 | 7274332.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.689160E+09 | 0.586834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.683774E+09 | 0.868001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.689413E+09 | 0.102005E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.702517E+09 | 0.908337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.662820E+09 | 0.776232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.681143E+09 | 0.346079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.669917E+09 | 0.237427E+09 | 0.352433E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.725961E+09 | 0.00 | 0.182603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.822909E+10 | 0.482613E+11 | 0.484486E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.637581E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.725961E+09 | 0.102005E+11 | 0.182603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.825859E+09 | 0.00 | 0.202979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.730612E+09 | 40521247.79 | 0.120707E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.805391E+09 | 0.191182E+09 | 0.679827E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.747973E+09 | 0.279044E+10 | 25186327.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.779471E+09 | 0.636613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.773816E+09 | 0.965457E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.783447E+09 | 0.114545E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.798535E+09 | 0.103116E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.750193E+09 | 0.885762E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.770553E+09 | 0.375628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.760879E+09 | 0.228524E+09 | 0.495125E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.830414E+09 | 0.00 | 0.234679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.935714E+10 | 0.536514E+11 | 0.678378E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.730612E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.830414E+09 | 0.114545E+11 | 0.234679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.191471E+10 | 0.00 | 0.00 | 0.00 | 139528.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.171223E+10 | 0.00 | 0.00 | 0.00 | 91911818.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.187932E+10 | 0.00 | 0.00 | 0.00 | 0.255961E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.179675E+10 | 0.00 | 0.00 | 0.00 | 0.229839E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.185743E+10 | 0.00 | 0.00 | 0.00 | 0.461468E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.182825E+10 | 0.00 | 0.00 | 0.00 | 0.678971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.187455E+10 | 0.00 | 0.00 | 0.00 | 0.761272E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.187097E+10 | 0.00 | 0.00 | 0.00 | 0.671719E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.180475E+10 | 0.00 | 0.00 | 0.00 | 0.551127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.185644E+10 | 0.00 | 0.00 | 0.00 | 0.254542E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.180805E+10 | 0.00 | 0.00 | 0.00 | 0.214848E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.194848E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.221519E+11 | 0.00 | 0.00 | 0.00 | 0.366522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.171223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.194848E+10 | 0.00 | 0.00 | 0.00 | 0.761272E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.774639E+09 | 0.00 | 0.00 | 0.00 | 3645010.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.755460E+09 | 0.00 | 0.00 | 0.00 | 80033540.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.888829E+09 | 0.00 | 0.00 | 0.00 | 0.204971E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.847162E+09 | 0.00 | 0.00 | 0.00 | 0.138551E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.857422E+09 | 0.00 | 0.00 | 0.00 | 0.249407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.856418E+09 | 0.00 | 0.00 | 0.00 | 0.342944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.888329E+09 | 0.00 | 0.00 | 0.00 | 0.380384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.883878E+09 | 0.00 | 0.00 | 0.00 | 0.341259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.844213E+09 | 0.00 | 0.00 | 0.00 | 0.293742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.910996E+09 | 0.00 | 0.00 | 0.00 | 0.149981E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.859535E+09 | 0.00 | 0.00 | 0.00 | 0.152787E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.774943E+09 | 0.00 | 0.00 | 0.00 | 1358745.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.101418E+11 | 0.00 | 0.00 | 0.00 | 0.194055E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.755460E+09 | 0.00 | 0.00 | 0.00 | 1358745.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.910996E+09 | 0.00 | 0.00 | 0.00 | 0.380384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.838986E+09 | 0.00 | 0.00 | 0.00 | 400976.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.751139E+09 | 0.00 | 0.00 | 0.00 | 47932772.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.840571E+09 | 0.00 | 0.00 | 0.00 | 0.145129E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.794980E+09 | 0.00 | 0.00 | 0.00 | 0.931407E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.829270E+09 | 0.00 | 0.00 | 0.00 | 0.184768E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.816129E+09 | 0.00 | 0.00 | 0.00 | 0.268810E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.822483E+09 | 0.00 | 0.00 | 0.00 | 0.294830E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.839916E+09 | 0.00 | 0.00 | 0.00 | 0.263207E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.797566E+09 | 0.00 | 0.00 | 0.00 | 0.224039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.820047E+09 | 0.00 | 0.00 | 0.00 | 0.106137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.800032E+09 | 0.00 | 0.00 | 0.00 | 0.114206E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.844524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.979564E+10 | 0.00 | 0.00 | 0.00 | 0.146570E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.751139E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.844524E+09 | 0.00 | 0.00 | 0.00 | 0.294830E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.838306E+09 | 0.00 | 0.00 | 0.00 | 79054.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.749073E+09 | 0.00 | 0.00 | 0.00 | 41802079.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.837257E+09 | 0.00 | 0.00 | 0.00 | 0.134314E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.790926E+09 | 0.00 | 0.00 | 0.00 | 0.921717E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.825079E+09 | 0.00 | 0.00 | 0.00 | 0.185094E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.813116E+09 | 0.00 | 0.00 | 0.00 | 0.270001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.819221E+09 | 0.00 | 0.00 | 0.00 | 0.296261E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.836083E+09 | 0.00 | 0.00 | 0.00 | 0.264623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.793553E+09 | 0.00 | 0.00 | 0.00 | 0.224976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.815876E+09 | 0.00 | 0.00 | 0.00 | 0.105888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.796702E+09 | 0.00 | 0.00 | 0.00 | 0.108058E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.844147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.975934E+10 | 0.00 | 0.00 | 0.00 | 0.146744E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.749073E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.844147E+09 | 0.00 | 0.00 | 0.00 | 0.296261E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.844736E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.753357E+09 | 0.00 | 0.00 | 0.00 | 33886860.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.840420E+09 | 0.00 | 0.00 | 0.00 | 0.116563E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.792390E+09 | 0.00 | 0.00 | 0.00 | 0.886223E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.826438E+09 | 0.00 | 0.00 | 0.00 | 0.181319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.812912E+09 | 0.00 | 0.00 | 0.00 | 0.266560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.819713E+09 | 0.00 | 0.00 | 0.00 | 0.292976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.837172E+09 | 0.00 | 0.00 | 0.00 | 0.261246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.794930E+09 | 0.00 | 0.00 | 0.00 | 0.221664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.817325E+09 | 0.00 | 0.00 | 0.00 | 0.102806E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.799151E+09 | 0.00 | 0.00 | 0.00 | 96008511.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.850994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.978954E+10 | 0.00 | 0.00 | 0.00 | 0.143984E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.753357E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.850994E+09 | 0.00 | 0.00 | 0.00 | 0.292976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.132453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117691E+10 | 0.00 | 0.00 | 0.00 | 52271306.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130892E+10 | 0.00 | 0.00 | 0.00 | 0.182385E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.123000E+10 | 0.00 | 0.00 | 0.00 | 0.156698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.128398E+10 | 0.00 | 0.00 | 0.00 | 0.327805E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.127392E+10 | 0.00 | 0.00 | 0.00 | 0.489328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.128444E+10 | 0.00 | 0.00 | 0.00 | 0.530840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130819E+10 | 0.00 | 0.00 | 0.00 | 0.476197E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.123498E+10 | 0.00 | 0.00 | 0.00 | 0.401261E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.126866E+10 | 0.00 | 0.00 | 0.00 | 0.183782E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.124424E+10 | 0.00 | 0.00 | 0.00 | 0.154028E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.152758E+11 | 0.00 | 0.00 | 0.00 | 0.260478E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.117691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.133701E+10 | 0.00 | 0.00 | 0.00 | 0.530840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.713629E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.633730E+09 | 0.00 | 0.00 | 0.00 | 23385595.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.704593E+09 | 0.00 | 0.00 | 0.00 | 84661934.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.661754E+09 | 0.00 | 0.00 | 0.00 | 0.784242E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.690628E+09 | 0.00 | 0.00 | 0.00 | 0.165401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.685429E+09 | 0.00 | 0.00 | 0.00 | 0.247388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.690743E+09 | 0.00 | 0.00 | 0.00 | 0.268311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.703588E+09 | 0.00 | 0.00 | 0.00 | 0.240614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.664163E+09 | 0.00 | 0.00 | 0.00 | 0.202757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.682492E+09 | 0.00 | 0.00 | 0.00 | 0.924309E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.669546E+09 | 0.00 | 0.00 | 0.00 | 74297616.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.720223E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.822052E+10 | 0.00 | 0.00 | 0.00 | 0.131356E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.633730E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.720223E+09 | 0.00 | 0.00 | 0.00 | 0.268311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.712415E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.632112E+09 | 0.00 | 0.00 | 0.00 | 21311876.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.702120E+09 | 0.00 | 0.00 | 0.00 | 78573740.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.658707E+09 | 0.00 | 0.00 | 0.00 | 0.769787E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.687380E+09 | 0.00 | 0.00 | 0.00 | 0.163871E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.682131E+09 | 0.00 | 0.00 | 0.00 | 0.245868E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.687431E+09 | 0.00 | 0.00 | 0.00 | 0.266818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.700288E+09 | 0.00 | 0.00 | 0.00 | 0.239255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.661046E+09 | 0.00 | 0.00 | 0.00 | 0.201481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.679313E+09 | 0.00 | 0.00 | 0.00 | 0.912681E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.666878E+09 | 0.00 | 0.00 | 0.00 | 70509491.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.718888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.818871E+10 | 0.00 | 0.00 | 0.00 | 0.130258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.632112E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.718888E+09 | 0.00 | 0.00 | 0.00 | 0.266818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.719778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.637581E+09 | 0.00 | 0.00 | 0.00 | 16848386.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.706370E+09 | 0.00 | 0.00 | 0.00 | 65805504.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.660656E+09 | 0.00 | 0.00 | 0.00 | 0.742091E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.689160E+09 | 0.00 | 0.00 | 0.00 | 0.161886E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.683774E+09 | 0.00 | 0.00 | 0.00 | 0.245629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.689413E+09 | 0.00 | 0.00 | 0.00 | 0.267267E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.702517E+09 | 0.00 | 0.00 | 0.00 | 0.239855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.662820E+09 | 0.00 | 0.00 | 0.00 | 0.201708E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.681143E+09 | 0.00 | 0.00 | 0.00 | 0.897101E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.669917E+09 | 0.00 | 0.00 | 0.00 | 63562176.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.725961E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.822909E+10 | 0.00 | 0.00 | 0.00 | 0.129489E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.637581E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.725961E+09 | 0.00 | 0.00 | 0.00 | 0.267267E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.825859E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.730612E+09 | 0.00 | 0.00 | 0.00 | 11423277.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.805391E+09 | 0.00 | 0.00 | 0.00 | 53759205.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.747973E+09 | 0.00 | 0.00 | 0.00 | 0.778738E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.779471E+09 | 0.00 | 0.00 | 0.00 | 0.175976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.773816E+09 | 0.00 | 0.00 | 0.00 | 0.272589E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.783447E+09 | 0.00 | 0.00 | 0.00 | 0.299589E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.798535E+09 | 0.00 | 0.00 | 0.00 | 0.270895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.750193E+09 | 0.00 | 0.00 | 0.00 | 0.228672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.770553E+09 | 0.00 | 0.00 | 0.00 | 0.973864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.760879E+09 | 0.00 | 0.00 | 0.00 | 61322631.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.830414E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.935714E+10 | 0.00 | 0.00 | 0.00 | 0.143563E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.730612E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.830414E+09 | 0.00 | 0.00 | 0.00 | 0.299589E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.840207E+10 | 0.00 | 0.00 | 247431.00 | 0.00 | 0.547852E+09 | 0.351104E+09 | 0.00 | 0.54 |
February | 0.577738E+10 | 0.00 | 0.00 | 1966620.71 | 0.00 | 0.305877E+09 | 0.139351E+10 | 0.00 | 0.63 |
March | 0.444947E+10 | 223236.99 | 0.00 | 4214060.73 | 0.00 | 0.175302E+09 | 0.287149E+10 | 0.00 | 0.73 |
April | 0.811905E+09 | 0.492772E+09 | 0.00 | 12126375.72 | 1172285.00 | 0.00 | 0.300792E+10 | 0.00 | 0.83 |
May | 61521532.22 | 0.202615E+10 | 0.00 | 9665888.81 | 15070321.46 | 0.00 | 0.133791E+10 | 0.00 | 0.73 |
June | 2108874.65 | 0.445763E+10 | 0.00 | 2366264.78 | 22209267.18 | 0.00 | 0.108931E+09 | 0.00 | 0.60 |
July | 3611.20 | 0.702854E+10 | 0.00 | 590419.68 | 36435421.15 | 0.00 | 14377054.81 | 0.00 | 0.57 |
August | 4578569.84 | 0.459245E+10 | 0.00 | 2694358.68 | 23087608.67 | 0.00 | 0.322466E+09 | 0.00 | 0.67 |
September | 16557618.43 | 0.315821E+10 | 0.00 | 10323231.78 | 21879584.84 | 0.00 | 0.124202E+10 | 0.00 | 0.78 |
October | 0.417424E+09 | 0.746958E+09 | 0.00 | 19277311.08 | 1973715.66 | 0.00 | 0.552605E+10 | 0.00 | 1.00 |
November | 0.465808E+10 | 0.00 | 0.00 | 6234972.23 | 0.00 | 97555207.76 | 0.449388E+10 | 0.00 | 0.74 |
December | 0.910533E+10 | 0.00 | 0.00 | 8531.82 | 0.00 | 0.952522E+09 | 31778042.23 | 0.00 | 0.53 |
Annual Sum or Average | 0.337064E+11 | 0.225029E+11 | 0.00 | 69715467.03 | 0.121828E+09 | 0.207911E+10 | 0.207014E+11 | 0.00 | 0.70 |
Minimum of Months | 3611.20 | 0.00 | 0.00 | 8531.82 | 0.00 | 0.00 | 14377054.81 | 0.00 | 0.53 |
Maximum of Months | 0.910533E+10 | 0.702854E+10 | 0.00 | 19277311.08 | 36435421.15 | 0.952522E+09 | 0.552605E+10 | 0.00 | 1.00 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.304295E+10 | 0.00 | 0.00 | 572440.27 | 0.00 | 43142379.07 | 0.537577E+09 | 0.00 | 0.42 |
February | 0.200861E+10 | 0.00 | 0.00 | 1702629.17 | 0.00 | 25597623.51 | 0.121216E+10 | 0.00 | 0.59 |
March | 0.123124E+10 | 132607.66 | 0.00 | 3591627.49 | 0.00 | 19153004.70 | 0.236119E+10 | 0.00 | 0.74 |
April | 0.185817E+09 | 0.235609E+09 | 0.00 | 5641684.95 | 355569.89 | 0.00 | 0.169234E+10 | 0.00 | 0.73 |
May | 20919702.65 | 0.952107E+09 | 0.00 | 4328021.51 | 5376188.06 | 0.00 | 0.561404E+09 | 0.00 | 0.59 |
June | 1546217.64 | 0.197720E+10 | 0.00 | 1005823.22 | 8452517.20 | 0.00 | 34023393.32 | 0.00 | 0.48 |
July | 0.00 | 0.318412E+10 | 0.00 | 0.00 | 26436523.81 | 0.00 | 0.00 | 0.00 | 0.47 |
August | 670558.96 | 0.208979E+10 | 0.00 | 1126926.22 | 14222211.12 | 0.00 | 0.105471E+09 | 0.00 | 0.55 |
September | 5270058.04 | 0.156811E+10 | 0.00 | 3297446.78 | 20373593.05 | 0.00 | 0.427683E+09 | 0.00 | 0.61 |
October | 97775118.49 | 0.378854E+09 | 0.00 | 8552425.08 | 2217617.95 | 0.00 | 0.273504E+10 | 0.00 | 0.93 |
November | 0.116164E+10 | 0.00 | 0.00 | 4822521.78 | 0.00 | 5240611.71 | 0.331379E+10 | 0.00 | 0.75 |
December | 0.328524E+10 | 0.00 | 0.00 | 269563.37 | 0.00 | 0.184612E+09 | 0.280305E+09 | 0.00 | 0.40 |
Annual Sum or Average | 0.110417E+11 | 0.103859E+11 | 0.00 | 34911109.83 | 77434221.09 | 0.277745E+09 | 0.132610E+11 | 0.00 | 0.60 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 |
Maximum of Months | 0.328524E+10 | 0.318412E+10 | 0.00 | 8552425.08 | 26436523.81 | 0.184612E+09 | 0.331379E+10 | 0.00 | 0.93 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.306297E+10 | 0.00 | 0.00 | 191194.68 | 0.00 | 0.214626E+09 | 0.226044E+09 | 0.00 | 0.43 |
February | 0.217453E+10 | 0.00 | 0.00 | 777922.47 | 0.00 | 97004223.86 | 0.571619E+09 | 0.00 | 0.53 |
March | 0.163980E+10 | 281389.06 | 0.00 | 1843008.89 | 0.00 | 46300397.18 | 0.120007E+10 | 0.00 | 0.64 |
April | 0.389572E+09 | 0.230142E+09 | 0.00 | 2523269.10 | 8042984.15 | 0.00 | 0.105539E+10 | 0.00 | 0.64 |
May | 63961464.55 | 0.890411E+09 | 0.00 | 1971199.58 | 41719728.96 | 0.00 | 0.409281E+09 | 0.00 | 0.56 |
June | 5251966.42 | 0.179302E+10 | 0.00 | 1132768.25 | 0.112191E+09 | 0.00 | 55513595.51 | 0.00 | 0.48 |
July | 176563.63 | 0.269547E+10 | 0.00 | 399478.11 | 0.196245E+09 | 0.00 | 1602663.78 | 0.00 | 0.45 |
August | 8927973.95 | 0.181733E+10 | 0.00 | 1297512.72 | 0.108820E+09 | 0.00 | 0.136155E+09 | 0.00 | 0.55 |
September | 37985197.52 | 0.137036E+10 | 0.00 | 1572042.74 | 46769737.35 | 0.00 | 0.215370E+09 | 0.00 | 0.55 |
October | 0.275843E+09 | 0.314083E+09 | 0.00 | 5257631.69 | 13668352.82 | 0.00 | 0.182187E+10 | 0.00 | 0.77 |
November | 0.159241E+10 | 0.00 | 0.00 | 2814326.51 | 0.00 | 36344614.55 | 0.187802E+10 | 0.00 | 0.65 |
December | 0.327515E+10 | 0.00 | 0.00 | 36205.32 | 0.00 | 0.365618E+09 | 55675722.81 | 0.00 | 0.41 |
Annual Sum or Average | 0.125266E+11 | 0.911110E+10 | 0.00 | 19816560.07 | 0.527457E+09 | 0.759893E+09 | 0.762662E+10 | 0.00 | 0.55 |
Minimum of Months | 176563.63 | 0.00 | 0.00 | 36205.32 | 0.00 | 0.00 | 1602663.78 | 0.00 | 0.41 |
Maximum of Months | 0.327515E+10 | 0.269547E+10 | 0.00 | 5257631.69 | 0.196245E+09 | 0.365618E+09 | 0.187802E+10 | 0.00 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.304270E+10 | 0.00 | 0.00 | 136512.33 | 0.00 | 0.251325E+09 | 0.165770E+09 | 0.00 | 0.42 |
February | 0.216273E+10 | 0.00 | 0.00 | 680329.00 | 0.00 | 0.122382E+09 | 0.510058E+09 | 0.00 | 0.52 |
March | 0.165459E+10 | 279614.75 | 0.00 | 1665005.14 | 0.00 | 65611231.46 | 0.110449E+10 | 0.00 | 0.63 |
April | 0.390716E+09 | 0.230185E+09 | 0.00 | 2471213.21 | 8119589.52 | 0.00 | 0.104021E+10 | 0.00 | 0.63 |
May | 63694419.13 | 0.891889E+09 | 0.00 | 1999779.33 | 41743804.16 | 0.00 | 0.409586E+09 | 0.00 | 0.56 |
June | 5062002.53 | 0.179583E+10 | 0.00 | 1188817.04 | 0.113624E+09 | 0.00 | 55393028.92 | 0.00 | 0.48 |
July | 424075.11 | 0.270720E+10 | 0.00 | 424702.72 | 0.197513E+09 | 0.00 | 1594525.33 | 0.00 | 0.45 |
August | 9089286.29 | 0.182732E+10 | 0.00 | 1325262.02 | 0.107122E+09 | 0.00 | 0.131253E+09 | 0.00 | 0.55 |
September | 37487640.75 | 0.137937E+10 | 0.00 | 1599343.23 | 46842108.53 | 0.00 | 0.214715E+09 | 0.00 | 0.55 |
October | 0.277117E+09 | 0.315649E+09 | 0.00 | 5233896.85 | 13313642.81 | 0.00 | 0.181140E+10 | 0.00 | 0.77 |
November | 0.161875E+10 | 0.00 | 0.00 | 2634462.48 | 0.00 | 54380860.44 | 0.176480E+10 | 0.00 | 0.64 |
December | 0.319582E+10 | 0.00 | 0.00 | 19931.92 | 0.00 | 0.435488E+09 | 36601084.53 | 0.00 | 0.41 |
Annual Sum or Average | 0.124582E+11 | 0.914772E+10 | 0.00 | 19379255.27 | 0.528279E+09 | 0.929187E+09 | 0.724588E+10 | 0.00 | 0.55 |
Minimum of Months | 424075.11 | 0.00 | 0.00 | 19931.92 | 0.00 | 0.00 | 1594525.33 | 0.00 | 0.41 |
Maximum of Months | 0.319582E+10 | 0.270720E+10 | 0.00 | 5233896.85 | 0.197513E+09 | 0.435488E+09 | 0.181140E+10 | 0.00 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.295327E+10 | 0.00 | 0.00 | 78396.11 | 0.00 | 0.347410E+09 | 0.109178E+09 | 0.00 | 0.42 |
February | 0.212434E+10 | 0.00 | 0.00 | 556518.01 | 0.00 | 0.163980E+09 | 0.443128E+09 | 0.00 | 0.51 |
March | 0.169167E+10 | 279501.24 | 0.00 | 1382259.87 | 0.00 | 86628561.62 | 0.951275E+09 | 0.00 | 0.61 |
April | 0.414001E+09 | 0.230017E+09 | 0.00 | 2219207.88 | 8326266.38 | 0.00 | 0.964505E+09 | 0.00 | 0.62 |
May | 65833525.19 | 0.888922E+09 | 0.00 | 1844397.61 | 42099647.69 | 0.00 | 0.396924E+09 | 0.00 | 0.56 |
June | 4970842.39 | 0.179042E+10 | 0.00 | 1068058.36 | 0.113523E+09 | 0.00 | 56011142.33 | 0.00 | 0.48 |
July | 179738.57 | 0.269009E+10 | 0.00 | 401867.11 | 0.193577E+09 | 0.00 | 1606988.68 | 0.00 | 0.45 |
August | 9025504.50 | 0.181354E+10 | 0.00 | 1280036.08 | 0.107562E+09 | 0.00 | 0.136137E+09 | 0.00 | 0.55 |
September | 37964914.58 | 0.136282E+10 | 0.00 | 1522562.57 | 48388645.53 | 0.00 | 0.213170E+09 | 0.00 | 0.54 |
October | 0.301577E+09 | 0.309868E+09 | 0.00 | 4938724.51 | 13686699.69 | 0.00 | 0.174451E+10 | 0.00 | 0.76 |
November | 0.165563E+10 | 0.00 | 0.00 | 2304451.79 | 0.00 | 71476519.29 | 0.160455E+10 | 0.00 | 0.62 |
December | 0.305162E+10 | 0.00 | 0.00 | 3686.58 | 0.00 | 0.572624E+09 | 12212524.37 | 0.00 | 0.41 |
Annual Sum or Average | 0.123101E+11 | 0.908597E+10 | 0.00 | 17600166.48 | 0.527164E+09 | 0.124212E+10 | 0.663321E+10 | 0.00 | 0.54 |
Minimum of Months | 179738.57 | 0.00 | 0.00 | 3686.58 | 0.00 | 0.00 | 1606988.68 | 0.00 | 0.41 |
Maximum of Months | 0.305162E+10 | 0.269009E+10 | 0.00 | 4938724.51 | 0.193577E+09 | 0.572624E+09 | 0.174451E+10 | 0.00 | 0.76 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.539133E+10 | 0.00 | 0.00 | 68329.10 | 0.00 | 0.701277E+09 | 0.127075E+09 | 0.00 | 0.38 |
February | 0.397650E+10 | 0.00 | 0.00 | 732910.99 | 0.00 | 0.246989E+09 | 0.718928E+09 | 0.00 | 0.44 |
March | 0.310890E+10 | 0.00 | 0.00 | 1971831.47 | 0.00 | 0.136068E+09 | 0.161540E+10 | 0.00 | 0.52 |
April | 0.632227E+09 | 0.276828E+09 | 0.00 | 4227644.82 | 9477628.81 | 0.00 | 0.160091E+10 | 0.00 | 0.52 |
May | 65090267.97 | 0.147096E+10 | 0.00 | 2995883.32 | 62143464.19 | 0.00 | 0.567718E+09 | 0.00 | 0.47 |
June | 2770845.32 | 0.331204E+10 | 0.00 | 1285435.13 | 87686830.16 | 0.00 | 40437701.15 | 0.00 | 0.41 |
July | 0.00 | 0.492303E+10 | 0.00 | 513512.26 | 0.161370E+09 | 0.00 | 313063.10 | 0.00 | 0.39 |
August | 4211612.71 | 0.330532E+10 | 0.00 | 1482087.69 | 83662261.45 | 0.00 | 0.190980E+09 | 0.00 | 0.46 |
September | 34643802.56 | 0.235973E+10 | 0.00 | 2996598.58 | 65430296.75 | 0.00 | 0.303730E+09 | 0.00 | 0.46 |
October | 0.398439E+09 | 0.559571E+09 | 0.00 | 8021669.62 | 11341563.30 | 0.00 | 0.310809E+10 | 0.00 | 0.64 |
November | 0.321060E+10 | 0.00 | 0.00 | 3233361.32 | 0.00 | 0.153848E+09 | 0.250440E+10 | 0.00 | 0.52 |
December | 0.546517E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121165E+10 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.222899E+11 | 0.162075E+11 | 0.00 | 27529264.31 | 0.481112E+09 | 0.244983E+10 | 0.107780E+11 | 0.00 | 0.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.546517E+10 | 0.492303E+10 | 0.00 | 8021669.62 | 0.161370E+09 | 0.121165E+10 | 0.310809E+10 | 0.00 | 0.64 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.258897E+10 | 0.00 | 0.00 | 21654.98 | 0.00 | 0.449401E+09 | 45144419.31 | 0.00 | 0.38 |
February | 0.194528E+10 | 0.00 | 0.00 | 319505.95 | 0.00 | 0.166531E+09 | 0.330343E+09 | 0.00 | 0.44 |
March | 0.157124E+10 | 0.00 | 0.00 | 884259.41 | 0.00 | 91346748.70 | 0.730414E+09 | 0.00 | 0.52 |
April | 0.332708E+09 | 0.144425E+09 | 0.00 | 2021437.41 | 5107450.62 | 0.00 | 0.774816E+09 | 0.00 | 0.53 |
May | 34063000.71 | 0.743924E+09 | 0.00 | 1467555.76 | 31934242.34 | 0.00 | 0.285545E+09 | 0.00 | 0.47 |
June | 1176537.12 | 0.166900E+10 | 0.00 | 602979.04 | 41180290.42 | 0.00 | 21267881.56 | 0.00 | 0.42 |
July | 0.00 | 0.246630E+10 | 0.00 | 243500.68 | 77608088.99 | 0.00 | 162145.95 | 0.00 | 0.39 |
August | 1733656.60 | 0.165891E+10 | 0.00 | 730911.94 | 40491766.49 | 0.00 | 0.101020E+09 | 0.00 | 0.47 |
September | 16912022.42 | 0.118003E+10 | 0.00 | 1475456.59 | 36667136.96 | 0.00 | 0.154960E+09 | 0.00 | 0.46 |
October | 0.204951E+09 | 0.280007E+09 | 0.00 | 4039499.55 | 5839890.24 | 0.00 | 0.156677E+10 | 0.00 | 0.66 |
November | 0.158178E+10 | 0.00 | 0.00 | 1553324.55 | 0.00 | 0.120421E+09 | 0.121685E+10 | 0.00 | 0.52 |
December | 0.257709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.742109E+09 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.108559E+11 | 0.814260E+10 | 0.00 | 13360085.84 | 0.238829E+09 | 0.156981E+10 | 0.522730E+10 | 0.00 | 0.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.258897E+10 | 0.246630E+10 | 0.00 | 4039499.55 | 77608088.99 | 0.742109E+09 | 0.156677E+10 | 0.00 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.251800E+10 | 0.00 | 0.00 | 15392.14 | 0.00 | 0.517236E+09 | 35541808.69 | 0.00 | 0.38 |
February | 0.193331E+10 | 0.00 | 0.00 | 285399.35 | 0.00 | 0.191807E+09 | 0.297404E+09 | 0.00 | 0.44 |
March | 0.156829E+10 | 0.00 | 0.00 | 799227.14 | 0.00 | 0.117538E+09 | 0.673584E+09 | 0.00 | 0.51 |
April | 0.346466E+09 | 0.144296E+09 | 0.00 | 1932290.12 | 5166918.71 | 0.00 | 0.743128E+09 | 0.00 | 0.52 |
May | 34453454.16 | 0.743022E+09 | 0.00 | 1422313.39 | 31943884.74 | 0.00 | 0.281827E+09 | 0.00 | 0.47 |
June | 1176322.75 | 0.166652E+10 | 0.00 | 587453.27 | 42284245.31 | 0.00 | 21219990.04 | 0.00 | 0.42 |
July | 0.00 | 0.245870E+10 | 0.00 | 239657.23 | 79228932.62 | 0.00 | 158722.68 | 0.00 | 0.39 |
August | 1776493.25 | 0.165370E+10 | 0.00 | 716736.15 | 42167894.97 | 0.00 | 0.101186E+09 | 0.00 | 0.47 |
September | 16926460.82 | 0.117593E+10 | 0.00 | 1452186.58 | 37379028.77 | 0.00 | 0.154124E+09 | 0.00 | 0.46 |
October | 0.211946E+09 | 0.278321E+09 | 0.00 | 3947040.74 | 5854373.07 | 0.00 | 0.154275E+10 | 0.00 | 0.65 |
November | 0.158606E+10 | 0.00 | 0.00 | 1451038.93 | 0.00 | 0.141890E+09 | 0.115309E+10 | 0.00 | 0.51 |
December | 0.250464E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.807828E+09 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.107231E+11 | 0.812049E+10 | 0.00 | 12848735.06 | 0.244025E+09 | 0.177630E+10 | 0.500401E+10 | 0.00 | 0.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.251800E+10 | 0.245870E+10 | 0.00 | 3947040.74 | 79228932.62 | 0.807828E+09 | 0.154275E+10 | 0.00 | 0.65 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.229967E+10 | 0.00 | 0.00 | 3729.16 | 0.00 | 0.736536E+09 | 12691837.26 | 0.00 | 0.38 |
February | 0.185665E+10 | 0.00 | 0.00 | 216223.14 | 0.00 | 0.292045E+09 | 0.234567E+09 | 0.00 | 0.43 |
March | 0.152968E+10 | 0.00 | 0.00 | 632725.70 | 0.00 | 0.197693E+09 | 0.561749E+09 | 0.00 | 0.50 |
April | 0.383085E+09 | 0.144056E+09 | 0.00 | 1742344.46 | 5344606.59 | 1028467.03 | 0.666161E+09 | 0.00 | 0.51 |
May | 39456657.54 | 0.741192E+09 | 0.00 | 1318346.20 | 32154919.88 | 0.00 | 0.271364E+09 | 0.00 | 0.47 |
June | 1179407.57 | 0.166660E+10 | 0.00 | 552081.78 | 41318832.25 | 0.00 | 21699599.11 | 0.00 | 0.42 |
July | 0.00 | 0.245786E+10 | 0.00 | 233872.16 | 78471352.53 | 0.00 | 153663.81 | 0.00 | 0.39 |
August | 1850608.88 | 0.165614E+10 | 0.00 | 691655.14 | 39674098.10 | 0.00 | 0.102461E+09 | 0.00 | 0.47 |
September | 17153909.05 | 0.117321E+10 | 0.00 | 1427202.32 | 40308481.70 | 0.00 | 0.153257E+09 | 0.00 | 0.46 |
October | 0.247175E+09 | 0.276390E+09 | 0.00 | 3765037.84 | 5889244.72 | 0.00 | 0.147850E+10 | 0.00 | 0.65 |
November | 0.157442E+10 | 0.00 | 0.00 | 1258775.72 | 0.00 | 0.205426E+09 | 0.103289E+10 | 0.00 | 0.50 |
December | 0.230201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.997336E+09 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.102523E+11 | 0.811545E+10 | 0.00 | 11841993.61 | 0.243162E+09 | 0.243006E+10 | 0.453550E+10 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.230201E+10 | 0.245786E+10 | 0.00 | 3765037.84 | 78471352.53 | 0.997336E+09 | 0.147850E+10 | 0.00 | 0.65 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.160606E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139822E+10 | 0.00 | 0.00 | 0.38 |
February | 0.138738E+10 | 0.00 | 0.00 | 152794.93 | 0.00 | 0.756974E+09 | 0.196782E+09 | 0.00 | 0.43 |
March | 0.131677E+10 | 0.00 | 0.00 | 438169.74 | 0.00 | 0.442938E+09 | 0.430044E+09 | 0.00 | 0.49 |
April | 0.407481E+09 | 0.147216E+09 | 0.00 | 1666017.40 | 5029992.14 | 8046135.65 | 0.616447E+09 | 0.00 | 0.53 |
May | 34631814.27 | 0.759390E+09 | 0.00 | 1256439.02 | 31497209.12 | 0.00 | 0.277854E+09 | 0.00 | 0.49 |
June | 1408259.30 | 0.168296E+10 | 0.00 | 580002.21 | 36456062.35 | 0.00 | 28314504.68 | 0.00 | 0.42 |
July | 705169.79 | 0.250752E+10 | 0.00 | 311167.20 | 65529171.62 | 0.00 | 1560643.55 | 0.00 | 0.40 |
August | 3428290.37 | 0.169770E+10 | 0.00 | 781572.11 | 31616231.36 | 0.00 | 0.124971E+09 | 0.00 | 0.48 |
September | 15976287.70 | 0.121955E+10 | 0.00 | 1683960.95 | 26481189.09 | 0.00 | 0.170441E+09 | 0.00 | 0.48 |
October | 0.326530E+09 | 0.285515E+09 | 0.00 | 3840409.83 | 4608630.33 | 0.00 | 0.144199E+10 | 0.00 | 0.69 |
November | 0.146492E+10 | 0.00 | 0.00 | 1156042.36 | 0.00 | 0.367528E+09 | 0.943026E+09 | 0.00 | 0.52 |
December | 0.168019E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158640E+10 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.824548E+10 | 0.829986E+10 | 0.00 | 11866575.75 | 0.201218E+09 | 0.456010E+10 | 0.423143E+10 | 0.00 | 0.47 |
Minimum of Months | 705169.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.168019E+10 | 0.250752E+10 | 0.00 | 3840409.83 | 65529171.62 | 0.158640E+10 | 0.144199E+10 | 0.00 | 0.69 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:41:35
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.177474E+12 | 0.171987E+11 | 0.00 | 0.428905E+11 | 0.334997E+10 |
February | 0.189068E+12 | 0.126505E+11 | 0.00 | 0.342648E+11 | 0.371263E+10 |
March | 0.293479E+12 | 0.114928E+11 | 0.00 | 0.339067E+11 | 0.704740E+10 |
April | 0.321130E+12 | 0.338808E+10 | 0.00 | 0.142622E+11 | 0.513051E+11 |
May | 0.348078E+12 | -0.312318E+10 | 0.00 | -0.507983E+10 | 0.104466E+12 |
June | 0.348339E+12 | -0.890817E+10 | 0.00 | -0.219574E+11 | 0.150582E+12 |
July | 0.344234E+12 | -0.130218E+11 | 0.00 | -0.342282E+11 | 0.175316E+12 |
August | 0.313738E+12 | -0.859407E+10 | 0.00 | -0.212371E+11 | 0.155723E+12 |
September | 0.283594E+12 | -0.589811E+10 | 0.00 | -0.128415E+11 | 0.133162E+12 |
October | 0.246109E+12 | 0.389253E+10 | 0.00 | 0.218311E+11 | 0.619593E+11 |
November | 0.184020E+12 | 0.135822E+11 | 0.00 | 0.415595E+11 | 0.609787E+10 |
December | 0.144144E+12 | 0.179250E+11 | 0.00 | 0.462346E+11 | 0.447277E+10 |
Annual Sum or Average | 0.319341E+13 | 0.405845E+11 | 0.00 | 0.139605E+12 | 0.857194E+12 |
Minimum of Months | 0.144144E+12 | -0.130218E+11 | 0.00 | -0.342282E+11 | 0.334997E+10 |
Maximum of Months | 0.348339E+12 | 0.179250E+11 | 0.00 | 0.462346E+11 | 0.175316E+12 |