Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:41
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880
Simulation Timestamp: 2023-10-16 08:41:29
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:29
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1114.87 | 533.35 | 533.35 |
Net Site Energy | 1114.87 | 533.35 | 533.35 |
Total Source Energy | 3491.95 | 1670.54 | 1670.54 |
Net Source Energy | 3491.95 | 1670.54 | 1670.54 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 18.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 355.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 381.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 70.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 104.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 56.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1096.22 | 18.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 18.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 355.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 381.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 70.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 104.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 56.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 18.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 355.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 381.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 70.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 104.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 56.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 216.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 246.62 | 8.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 524.43 | 8.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 216.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 246.62 | 8.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 524.43 | 8.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1096.224 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1096.224 | 100.00 |
Total On-Site and Utility Electric Sources | 1096.224 | 100.00 |
Total Electricity End Uses | 1096.224 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 10.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1974.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:29
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:41 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Latitude [deg] | 27.85 |
Longitude [deg] | -82.5 |
Elevation [m] | 8.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.77 | 20.77 | 15.2453 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.38 | 10.38 | 17.9167 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 16.4411 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 16.4411 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 16.4411 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.72 | 20.72 | 10.0956 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 10.1826 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 10.1826 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 10.1826 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.36 | 10.36 | 10.1826 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 13.2210 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 13.2210 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 15.2453 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 17.9167 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 16.4411 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 16.4411 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 16.4411 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 10.0956 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 10.1826 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 10.1826 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 10.1826 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 10.1826 | 6.19 | 4.3000 | |
Total | 2090.32 | 13.2210 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 13.2210 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 13.2210 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:29
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-SEP-12:30 | 05-FEB-10:09 | - | - | - | - | - | - | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 102580.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 72942.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 23650.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 11571.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 5414.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 121668.09 | 102580.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 102580.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 72942.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 23650.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 11571.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 5414.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:29
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 20.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1124.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1208.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 222.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 407.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 329.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 178.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3471.74 | 20.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 9.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 537.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 578.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 106.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 157.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 85.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1660.87 | 9.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 9.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 537.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 578.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 106.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 157.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 85.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1660.87 | 9.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:29
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 2.16 |
SMSTORE1 DIRECT AIR | 1.14 |
SMSTORE2 DIRECT AIR | 1.14 |
SMSTORE3 DIRECT AIR | 1.14 |
SMSTORE4 DIRECT AIR | 1.14 |
LGSTORE2 DIRECT AIR | 2.01 |
SMSTORE5 DIRECT AIR | 1.06 |
SMSTORE6 DIRECT AIR | 1.05 |
SMSTORE7 DIRECT AIR | 1.06 |
SMSTORE8 DIRECT AIR | 1.22 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.16 | 2.16 | 2.16 | 2.16 | 2.16 | 2.16 | 1.00 | 1.00 | 2.16 |
PSZ-AC_2:2 | 1.14 | 1.14 | 1.14 | 1.14 | 1.14 | 1.14 | 1.00 | 1.00 | 1.14 |
PSZ-AC_3:3 | 1.14 | 1.14 | 1.14 | 1.14 | 1.14 | 1.14 | 1.00 | 1.00 | 1.14 |
PSZ-AC_4:4 | 1.14 | 1.14 | 1.14 | 1.14 | 1.14 | 1.14 | 1.00 | 1.00 | 1.14 |
PSZ-AC_5:5 | 1.14 | 1.14 | 1.14 | 1.14 | 1.14 | 1.14 | 1.00 | 1.00 | 1.14 |
PSZ-AC_6:6 | 2.01 | 2.01 | 2.01 | 2.01 | 2.01 | 2.01 | 1.00 | 1.00 | 2.01 |
PSZ-AC_7:7 | 1.06 | 1.06 | 1.06 | 1.06 | 1.06 | 1.06 | 1.00 | 1.00 | 1.06 |
PSZ-AC_8:8 | 1.05 | 1.05 | 1.05 | 1.05 | 1.05 | 1.05 | 1.00 | 1.00 | 1.05 |
PSZ-AC_9:9 | 1.06 | 1.06 | 1.06 | 1.06 | 1.06 | 1.06 | 1.00 | 1.00 | 1.06 |
PSZ-AC_10:10 | 1.22 | 1.22 | 1.22 | 1.22 | 1.22 | 1.22 | 1.00 | 1.000000 | 1.22 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.16 | 0.411479 |
PSZ-AC_2:2_OA_CONTROLLER | 1.14 | 0.205739 |
PSZ-AC_3:3_OA_CONTROLLER | 1.14 | 0.205739 |
PSZ-AC_4:4_OA_CONTROLLER | 1.14 | 0.205739 |
PSZ-AC_5:5_OA_CONTROLLER | 1.14 | 0.205739 |
PSZ-AC_6:6_OA_CONTROLLER | 2.01 | 0.411479 |
PSZ-AC_7:7_OA_CONTROLLER | 1.06 | 0.205739 |
PSZ-AC_8:8_OA_CONTROLLER | 1.05 | 0.205739 |
PSZ-AC_9:9_OA_CONTROLLER | 1.06 | 0.205739 |
PSZ-AC_10:10_OA_CONTROLLER | 1.22 | 0.205739 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.16 | 2314.75 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.14 | 1257.30 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.14 | 1262.59 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.14 | 1266.68 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.14 | 1258.99 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 2.01 | 2153.43 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 1.06 | 1168.53 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 1.05 | 1163.62 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 1.06 | 1169.08 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.22 | 1347.74 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.16 | 2.16 | 2.16 | 1.43 | 53717.85 | 57621.40 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.14 | 1.14 | 1.14 | 0.749499 | 28199.78 | 30044.05 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.14 | 1.14 | 1.14 | 0.752654 | 28318.49 | 30153.24 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.14 | 1.14 | 1.14 | 0.755096 | 28410.34 | 30237.73 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.14 | 1.14 | 1.14 | 0.750511 | 28237.86 | 30079.07 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 2.01 | 2.01 | 2.01 | 1.33 | 49974.26 | 54177.89 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 1.06 | 1.06 | 1.06 | 0.696586 | 26208.93 | 28212.90 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 1.05 | 1.05 | 1.05 | 0.693660 | 26098.83 | 28111.62 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 1.06 | 1.06 | 1.06 | 0.696913 | 26221.23 | 28224.20 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.22 | 1.22 | 1.22 | 0.803414 | 29993.53 | 31910.12 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 2.16 | 1.08 | 1.44 | 53717.85 | 26858.92 | 0.701080 | 0.701080 |
PSZ-AC_2:2 COOLING COIL | 1.14 | 0.567803 | 0.757073 | 28199.78 | 14099.89 | 0.701080 | 0.701080 |
PSZ-AC_3:3 COOLING COIL | 1.14 | 0.570193 | 0.760260 | 28318.49 | 14159.25 | 0.701080 | 0.701080 |
PSZ-AC_4:4 COOLING COIL | 1.14 | 0.572042 | 0.762720 | 28410.34 | 14205.17 | 0.701080 | 0.701080 |
PSZ-AC_5:5 COOLING COIL | 1.14 | 0.568569 | 0.758093 | 28237.86 | 14118.93 | 0.701080 | 0.701080 |
PSZ-AC_6:6 COOLING COIL | 2.01 | 1.01 | 1.34 | 49974.26 | 24987.13 | 0.701080 | 0.701080 |
PSZ-AC_7:7 COOLING COIL | 1.06 | 0.527717 | 0.703620 | 26208.93 | 13104.47 | 0.701080 | 0.701080 |
PSZ-AC_8:8 COOLING COIL | 1.05 | 0.525500 | 0.700667 | 26098.83 | 13049.42 | 0.701080 | 0.701080 |
PSZ-AC_9:9 COOLING COIL | 1.06 | 0.527964 | 0.703953 | 26221.23 | 13110.61 | 0.701080 | 0.701080 |
PSZ-AC_10:10 COOLING COIL | 1.22 | 0.608647 | 0.811527 | 29993.53 | 14996.76 | 0.704000 | 0.704000 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 57621.40 |
PSZ-AC_2:2 HEATING COIL | 30044.05 |
PSZ-AC_3:3 HEATING COIL | 30153.24 |
PSZ-AC_4:4 HEATING COIL | 30237.73 |
PSZ-AC_5:5 HEATING COIL | 30079.07 |
PSZ-AC_6:6 HEATING COIL | 54177.89 |
PSZ-AC_7:7 HEATING COIL | 28212.90 |
PSZ-AC_8:8 HEATING COIL | 28111.62 |
PSZ-AC_9:9 HEATING COIL | 28224.20 |
PSZ-AC_10:10 HEATING COIL | 31910.12 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:29
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:29
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:29
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 24.20 | 18.90 | 15.70 | 13.60 | 15.50 | 17.10 | 21.20 | 26.90 | 27.60 | 27.90 | 27.40 | 26.20 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 | 27.85 | -82.52 | -5.00 | 8.00 | 101229 | 1.2032 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.85 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.74 | 20.77 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.66 | 10.38 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.41 | 20.72 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.12 | 10.36 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 15.245 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 19.545 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 17.917 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.217 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 16.441 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.741 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 16.441 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.741 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 16.441 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.741 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 10.096 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 14.396 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 10.183 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 14.483 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 10.183 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 14.483 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 10.183 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 14.483 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 10.183 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 14.483 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 3524.998 | 10.118 | 62.666 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3524.998 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 1786.253 | 5.127 | 31.755 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1786.253 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 1777.664 | 10.205 | 63.207 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1777.664 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1343.311 | 7.712 | 47.763 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1343.311 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 1773.748 | 10.183 | 63.068 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1773.748 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 1090.187 | 6.258 | 38.763 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1090.187 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 1773.748 | 10.183 | 63.068 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1773.748 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 1090.187 | 6.258 | 38.763 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1090.187 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 1773.748 | 10.183 | 63.068 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1773.748 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 1090.187 | 6.258 | 38.763 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1090.187 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 3517.169 | 10.096 | 62.527 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3517.169 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 1773.748 | 10.183 | 63.068 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1773.748 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 1773.748 | 10.183 | 63.068 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1773.748 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 1773.748 | 10.183 | 63.068 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1773.748 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 1773.748 | 10.183 | 63.068 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1773.748 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.7544 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1995 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2888 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.092 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.937 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.386 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
19 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
20 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
21 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
22 | 7 | -0.31526305E-12 | 0.65421067E-14 | -0.96995935E-13 | 0.16372101E-15 |
23 | 6 | 0.28934589E-07 | 0.21281465E-09 | 0.66261080E-08 | -0.13661131E-12 |
24 | 5 | -0.19144321E-03 | 0.18179002E-05 | -0.98452505E-04 | 0.65494719E-08 |
25 | 4 | 0.29370911 | 0.88327295E-03 | 0.10024532 | -0.33791493E-04 |
26 | 3 | -7.2972687 | 0.27321832E-01 | -2.3480939 | 0.29160644E-01 |
27 | 2 | 40.973187 | 0.96992104E-01 | 15.302757 | -0.33447687 |
28 | 1 | -80.623988 | 0.43709902E-01 | -29.175449 | 1.0802857 |
29 | 0 | 46.824338 | 0.87814252E-03 | 16.290426 | |
30 | 7 | -0.21163652E-08 | -0.68723841E-15 | 0.43910983E-14 | -0.57684426E-16 |
31 | 6 | 0.56109385E-05 | 0.38186281E-08 | 0.31898696E-02 | -0.26759299E-04 |
32 | 5 | -0.40164657E-03 | 0.22608617E-05 | -0.22372456 | 0.19561502E-02 |
33 | 4 | 0.92272104E-02 | 0.10289840E-03 | 4.8295456 | -0.45264980E-01 |
34 | 3 | -0.80993241E-01 | 0.81813938E-03 | -38.021416 | 0.39865375 |
35 | 2 | 0.28754352 | 0.13608947E-02 | 116.48395 | -1.4179393 |
36 | 1 | -0.41499682 | 0.41453381E-03 | -143.90731 | 2.0490399 |
37 | 0 | 0.20232414 | 0.10048102E-04 | 60.838472 | |
38 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
39 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
40 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
41 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
42 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
43 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
44 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
45 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
46 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
47 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
48 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
49 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
50 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
51 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
52 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
53 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
54 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
55 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
56 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
57 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
58 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
59 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
60 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
61 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
62 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
63 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
64 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
65 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
66 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
67 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
68 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
69 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
70 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
71 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
72 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
73 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
74 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
75 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
76 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
77 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
78 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
79 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
80 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
81 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
82 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
83 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
84 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
85 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
86 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
87 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
88 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
89 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
90 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
91 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
92 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
93 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
94 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479936E-14 | -0.41635794E-16 |
95 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
96 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
97 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
98 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
99 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
100 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
101 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
102 | 7 | -0.14484255E-08 | -0.22640907E-15 | 0.11860658E-13 | -0.17473455E-15 |
103 | 6 | 0.80640390E-05 | 0.55493782E-08 | 0.31828288E-02 | -0.26700235E-04 |
104 | 5 | -0.58275339E-03 | 0.32892043E-05 | -0.22332434 | 0.19526176E-02 |
105 | 4 | 0.13421983E-01 | 0.14977251E-03 | 4.8228790 | -0.45200897E-01 |
106 | 3 | -0.11791368 | 0.11914425E-02 | -37.983753 | 0.39823745 |
107 | 2 | 0.41875064 | 0.19825898E-02 | 116.41064 | -1.4169588 |
108 | 1 | -0.60444169 | 0.60433957E-03 | -143.86415 | 2.0483306 |
109 | 0 | 0.29470347 | 0.14596444E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 35 | 1 | VerySmooth | 2.861 | 2.861 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 1.93170E-002 | 0.16139 | 0.61074 | 0.61074 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10774 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.021 | 0.7435 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.021 | 0.7435 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.021 | 0.7435 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.021 | 0.7435 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.021 | 0.7435 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.021 | 0.7435 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.021 | 0.7435 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 0.157 | 4.517E-004 | 2.488E-004 | 0.314 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.389 | 1.116E-003 | 6.149E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.648E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 8.993E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.389 | 1.116E-003 | 7.565E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 0.112 | 6.453E-004 | 2.994E-004 | 0.448 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 5.921E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 24532.74509 | 29439.29410 | 1.80268 | 2.16322 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 33.90000 | 1.65364E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 16195.36703 | 19434.44044 | 0.69874 | 0.83848 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 12878.55359 | 15454.26431 | 0.94634 | 1.13561 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 33.90000 | 1.65364E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 8027.70262 | 9633.24315 | 0.34635 | 0.41562 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 12932.81524 | 15519.37828 | 0.95032 | 1.14039 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 33.83417 | 1.65363E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 8101.42664 | 9721.71197 | 0.34953 | 0.41944 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 12974.76318 | 15569.71581 | 0.95340 | 1.14408 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 33.83417 | 1.65363E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 8169.83286 | 9803.79943 | 0.35248 | 0.42298 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 12895.99664 | 15475.19596 | 0.94762 | 1.13714 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 33.83417 | 1.65363E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 8291.06872 | 9949.28247 | 0.35771 | 0.42925 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 22823.63190 | 27388.35828 | 1.67705 | 2.01246 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 33.83417 | 1.65363E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 15646.94966 | 18776.33959 | 0.67508 | 0.81010 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 11969.45691 | 14363.34830 | 0.87953 | 1.05543 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 33.83417 | 1.65363E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 8521.20626 | 10225.44752 | 0.36764 | 0.44117 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 11919.17548 | 14303.01058 | 0.87583 | 1.05100 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 33.83417 | 1.65363E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 8525.41723 | 10230.50068 | 0.36782 | 0.44139 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 11975.07673 | 14370.09208 | 0.87994 | 1.05593 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 33.83417 | 1.65363E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 8745.22786 | 10494.27344 | 0.37731 | 0.45277 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 13807.50470 | 16569.00564 | 1.01441 | 1.21729 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 33.50500 | 1.65356E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 10297.42960 | 12356.91552 | 0.44427 | 0.53312 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 33967.72 | 2.16322 | 2.16322 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 27363.91 | 0.83848 | 0.83848 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 17707.16 | 1.13561 | 1.13561 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 13599.19 | 0.41562 | 0.41562 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 17769.90 | 1.14039 | 1.14039 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 13686.37 | 0.41944 | 0.41944 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 17818.67 | 1.14408 | 1.14408 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 13767.26 | 0.42298 | 0.42298 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 17725.83 | 1.13714 | 1.13714 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 13910.62 | 0.42925 | 0.42925 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 31944.14 | 2.01246 | 2.01246 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 26715.44 | 0.81010 | 0.81010 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 16630.00 | 1.05543 | 1.05543 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 14182.76 | 0.44117 | 0.44117 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 16570.51 | 1.05100 | 1.05100 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 14187.74 | 0.44139 | 0.44139 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 16635.17 | 1.05593 | 1.05593 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 14447.68 | 0.45277 | 0.45277 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 18705.90 | 1.21729 | 1.21729 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 16283.13 | 0.53312 | 0.53312 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.16322 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.13561 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.14039 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.14408 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.13714 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.01246 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.05543 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.05100 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.05593 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.21729 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.16322 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.16322 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.16322 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.16322 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.16322 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.16322 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.13561 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.13561 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.13561 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.13561 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.13561 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.13561 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.14039 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.14039 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.14039 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.14039 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.14039 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.14039 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.14408 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.14408 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.14408 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.14408 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.14408 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.14408 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.13714 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.13714 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.13714 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.13714 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.13714 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.13714 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.01246 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.01246 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.01246 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.01246 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.01246 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 2.01246 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.05543 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.05543 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.05543 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.05543 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.05543 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 1.05543 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 1.00000 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.05100 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.05100 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.05100 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.05100 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.05100 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 1.05100 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 1.00000 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.05593 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.05593 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.05593 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.05593 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.05593 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 1.05593 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 1.00000 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.21729 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.21729 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.21729 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.21729 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.21729 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.21729 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.16322 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.13561 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.14039 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.14408 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.13714 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 2.01246 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 1.05543 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 1.05100 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 1.05593 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.21729 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.16322 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.16322 |
104 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2314.74547 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.16322 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.16322 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.16322 |
108 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.42772 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.16322 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.08161 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.44215 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 53717.85000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 26858.92500 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
116 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 53717.85000 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 57621.39834 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
120 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 57621.39834 |
121 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.13561 |
122 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
123 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.13561 |
124 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1257.29511 |
125 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.13561 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.13561 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.13561 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.74950 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.13561 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.56780 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.75707 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 28199.78000 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 14099.89000 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28199.78000 |
137 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30044.05022 |
138 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
139 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
140 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 30044.05022 |
141 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.14039 |
142 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
143 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.14039 |
144 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1262.58782 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.14039 |
146 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.14039 |
147 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.14039 |
148 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.75265 |
149 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.14039 |
150 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.57019 |
151 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.76026 |
152 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 28318.49000 |
153 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 14159.24500 |
154 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
156 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28318.49000 |
157 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30153.23952 |
158 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
159 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
160 | Coil:Heating:Fuel | PSZ-AC_3:3 HEATING COIL | Design Size Nominal Capacity [W] | 30153.23952 |
161 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.14408 |
162 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
163 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.14408 |
164 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1266.68319 |
165 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.14408 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.14408 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.14408 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.75510 |
169 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.14408 |
170 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.57204 |
171 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.76272 |
172 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 28410.34000 |
173 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 14205.17000 |
174 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
175 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28410.34000 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30237.72600 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
179 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
180 | Coil:Heating:Fuel | PSZ-AC_4:4 HEATING COIL | Design Size Nominal Capacity [W] | 30237.72600 |
181 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.13714 |
182 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
183 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.13714 |
184 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1258.99288 |
185 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.13714 |
186 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.13714 |
187 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.13714 |
188 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.75051 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.13714 |
190 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.56857 |
191 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.75809 |
192 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 28237.86000 |
193 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 14118.93000 |
194 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
195 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
196 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28237.86000 |
197 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30079.06962 |
198 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
200 | Coil:Heating:Fuel | PSZ-AC_5:5 HEATING COIL | Design Size Nominal Capacity [W] | 30079.06962 |
201 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.01246 |
202 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
203 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.01246 |
204 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2153.43085 |
205 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.01246 |
206 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.01246 |
207 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.01246 |
208 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.32823 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.01246 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.00623 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.34164 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 49974.26000 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 24987.13000 |
214 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
215 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 49974.26000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 54177.88587 |
218 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
219 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
220 | Coil:Heating:Fuel | PSZ-AC_6:6 HEATING COIL | Design Size Nominal Capacity [W] | 54177.88587 |
221 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.05543 |
222 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
223 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.05543 |
224 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1168.53255 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.05543 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.05543 |
227 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.05543 |
228 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.69659 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.05543 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52772 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.70362 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 26208.93000 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 13104.46500 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
236 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 26208.93000 |
237 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28212.89772 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
240 | Coil:Heating:Fuel | PSZ-AC_7:7 HEATING COIL | Design Size Nominal Capacity [W] | 28212.89772 |
241 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.05100 |
242 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
243 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.05100 |
244 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1163.62350 |
245 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.05100 |
246 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.05100 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.05100 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.69366 |
249 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.05100 |
250 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52550 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.70067 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 26098.83000 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 13049.41500 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
256 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 26098.83000 |
257 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28111.62369 |
258 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
259 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
260 | Coil:Heating:Fuel | PSZ-AC_8:8 HEATING COIL | Design Size Nominal Capacity [W] | 28111.62369 |
261 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.05593 |
262 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
263 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.05593 |
264 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1169.08084 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.05593 |
266 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.05593 |
267 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.05593 |
268 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.69691 |
269 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.05593 |
270 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52796 |
271 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.70395 |
272 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 26221.23000 |
273 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 13110.61500 |
274 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 26221.23000 |
277 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28224.20125 |
278 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
279 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
280 | Coil:Heating:Fuel | PSZ-AC_9:9 HEATING COIL | Design Size Nominal Capacity [W] | 28224.20125 |
281 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.21729 |
282 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
283 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.21729 |
284 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1347.73752 |
285 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.21729 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.21729 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.21729 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.80341 |
289 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.21729 |
290 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.60865 |
291 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.81153 |
292 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 29993.53000 |
293 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 14996.76500 |
294 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70400 |
295 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70400 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 29993.53000 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31910.12213 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
299 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
300 | Coil:Heating:Fuel | PSZ-AC_10:10 HEATING COIL | Design Size Nominal Capacity [W] | 31910.12213 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 52011.3 | 11.77 | 11.77 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 27303.9 | 11.95 | 11.95 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | 27418.8 | 11.95 | 11.95 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | 27507.8 | 11.95 | 11.95 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | 27340.8 | 11.95 | 11.95 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | 48386.6 | 11.77 | 11.77 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | 25376.3 | 11.95 | 11.95 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | 25269.7 | 11.95 | 11.95 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | 25388.2 | 11.95 | 11.95 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | 29033.3 | 11.93 | 11.93 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 58.18 | 78.94 | 58.18 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.199 | 0.190 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 29.09 | 39.47 | 29.09 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 58.22 | 78.94 | 58.22 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.289 | 0.270 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 1.6865756161E-002 | 6.8843671589E-002 | Pass | Pass | 3.4258246953E-002 | 8.8764166795E-002 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 2.3423712366E-002 | 0.1058519454 | Pass | Pass | 3.6238439335E-002 | 9.5559696733E-002 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 5.0048154372E-002 | 0.1784327973 | Pass | Pass | 0.1684306872 | 1.5064678564 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 5.0144916938E-002 | 0.1798370140 | Pass | Pass | 0.1695765612 | 1.5219935198 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 5.0072231442E-002 | 0.1777388723 | Pass | Pass | 0.1702162967 | 1.5404936505 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 4.8822524567E-002 | 0.1570599077 | Pass | Pass | 0.1463177724 | 1.2194608058 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 4.8737411936E-002 | 0.1581839931 | Pass | Pass | 0.1755024709 | 1.5535195311 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 4.8690450993E-002 | 0.1568496225 | Pass | Pass | 0.1777409564 | 1.5646090231 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 4.9514159543E-002 | 0.1577275202 | Pass | Pass | 0.1838012101 | 1.6113355784 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 5.2567017164E-002 | 0.1445447317 | Pass | Pass | 0.2234969421 | 2.0582500968 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:29
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3148.36 | -208.9 | 0.00 | -317.1 | 1823.93 | 4446.22 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:29
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60 | 0.00 | 4.60 | Wetbulb [C] | 2.50 | 10.00 |
TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 7.90 | 25.10 | Wetbulb [C] | 3.10 | 270.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 66.00 | 12 | |||
Feb | 66.00 | 22 | |||
Mar | 126.00 | 32 | |||
Apr | 206.00 | 19 | |||
May | 144.00 | 46 | |||
Jun | 99.00 | 30 | |||
Jul | 192.00 | 52 | |||
Aug | 240.00 | 34 | |||
Sep | 310.00 | 44 | |||
Oct | 34.00 | 10 | |||
Nov | 63.00 | 12 | |||
Dec | 35.00 | 24 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:29
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 78.94 | 58.18 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.193 | 0.199 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 29.09 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 78.94 | 58.22 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.276 | 0.289 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.861 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.861 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.861 | 0.251 | 0.251 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 124.40 | 2.861 | 0.251 | 0.251 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 124.40 | 2.861 | 0.251 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:29
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:29
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 10.1181 | 348.39 | 3525.00 | LightsWired | LTG_SCH_BASE_LPD1 | 84.21 | 168.00 | 84.19 | 0.0000 | Y | 55.71 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 5.1272 | 348.39 | 1786.25 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 168.00 | 97.48 | 0.0000 | Y | 32.69 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 10.2051 | 174.19 | 1777.66 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 85.70 | 168.00 | 85.69 | 0.0000 | Y | 28.59 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 7.7116 | 174.19 | 1343.31 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 168.00 | 97.48 | 0.0000 | Y | 24.58 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 10.1826 | 174.19 | 1773.75 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 22.71 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 6.2585 | 174.19 | 1090.19 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 15.95 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 10.1826 | 174.19 | 1773.75 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 22.71 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 6.2585 | 174.19 | 1090.19 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 15.95 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 10.1826 | 174.19 | 1773.75 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 22.71 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 6.2585 | 174.19 | 1090.19 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 15.95 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 10.0956 | 348.39 | 3517.17 | LightsWired | LTG_SCH_BASE_LPD2 | 62.11 | 168.00 | 61.60 | 0.0000 | Y | 40.67 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 10.1826 | 174.19 | 1773.75 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 20.88 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 10.1826 | 174.19 | 1773.75 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 20.88 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 10.1826 | 174.19 | 1773.75 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 20.88 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 10.1826 | 174.19 | 1773.75 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 20.88 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 6.6105 | 4180.64 | 27636.19 | 381.75 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 343.18 | AstronomicalClock | - | 41.73 | 41.73 | 2.69 | |
EXTERIOR_LIGHTS_B | 5060.12 | AstronomicalClock | - | 83.73 | 71.13 | 67.56 | |
Exterior Lighting Total | 5403.30 | 70.25 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:29
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 53717.85 | 37660.51 | 16057.34 | 0.70 | 3.73 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 28199.78 | 19770.30 | 8429.48 | 0.70 | 3.80 | |||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 28318.49 | 19853.53 | 8464.96 | 0.70 | 3.80 | |||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 28410.34 | 19917.92 | 8492.42 | 0.70 | 3.80 | |||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 28237.86 | 19797.00 | 8440.86 | 0.70 | 3.80 | |||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 49974.26 | 35035.95 | 14938.31 | 0.70 | 3.73 | |||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 26208.93 | 18374.56 | 7834.37 | 0.70 | 3.80 | |||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 26098.83 | 18297.37 | 7801.46 | 0.70 | 3.80 | |||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 26221.23 | 18383.18 | 7838.05 | 0.70 | 3.80 | |||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 29993.53 | 21115.45 | 8878.08 | 0.70 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 52011.3 | 11.77 | 11.77 | ||||
PSZ-AC_2:2 COOLING COIL | 27303.9 | 11.95 | 11.95 | ||||
PSZ-AC_3:3 COOLING COIL | 27418.8 | 11.95 | 11.95 | ||||
PSZ-AC_4:4 COOLING COIL | 27507.8 | 11.95 | 11.95 | ||||
PSZ-AC_5:5 COOLING COIL | 27340.8 | 11.95 | 11.95 | ||||
PSZ-AC_6:6 COOLING COIL | 48386.6 | 11.77 | 11.77 | ||||
PSZ-AC_7:7 COOLING COIL | 25376.3 | 11.95 | 11.95 | ||||
PSZ-AC_8:8 COOLING COIL | 25269.7 | 11.95 | 11.95 | ||||
PSZ-AC_9:9 COOLING COIL | 25388.2 | 11.95 | 11.95 | ||||
PSZ-AC_10:10 COOLING COIL | 29033.3 | 11.93 | 11.93 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 57621.40 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 30044.05 | 0.80 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | 30153.24 | 0.80 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | 30237.73 | 0.80 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | 30079.07 | 0.80 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | 54177.89 | 0.80 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | 28212.90 | 0.80 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | 28111.62 | 0.80 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | 28224.20 | 0.80 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | 31910.12 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.16 | 2314.75 | 1070.05 | 1.00 | 1.30 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.14 | 1257.30 | 1107.16 | 1.00 | 1.37 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.14 | 1262.59 | 1107.16 | 1.00 | 1.37 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.14 | 1266.68 | 1107.16 | 1.00 | 1.37 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.14 | 1258.99 | 1107.16 | 1.00 | 1.37 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.01 | 2153.43 | 1070.05 | 1.00 | 1.31 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.06 | 1168.53 | 1107.16 | 1.00 | 1.39 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.05 | 1163.62 | 1107.16 | 1.00 | 1.39 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.06 | 1169.08 | 1107.16 | 1.00 | 1.39 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.22 | 1347.74 | 1107.16 | 1.00 | 1.36 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.74 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.74 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.74 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.74 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.74 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.74 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.74 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:29
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 24532.75 | 29439.29 | 84.50 | 1.803 | 2.163 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 23.89 | 23.88 | 0.01035 | 33.90 | 0.01654 | 0.411 | 0.00 |
SMSTORE1 | 12878.55 | 15454.26 | 88.72 | 0.946 | 1.136 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 23.89 | 23.88 | 0.01038 | 33.90 | 0.01654 | 0.206 | 0.00 |
SMSTORE2 | 12932.82 | 15519.38 | 89.09 | 0.950 | 1.140 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.88 | 0.01038 | 33.83 | 0.01654 | 0.206 | 0.00 |
SMSTORE3 | 12974.76 | 15569.72 | 89.38 | 0.953 | 1.144 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.88 | 0.01037 | 33.83 | 0.01654 | 0.206 | 0.00 |
SMSTORE4 | 12896.00 | 15475.20 | 88.84 | 0.948 | 1.137 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.88 | 0.01038 | 33.83 | 0.01654 | 0.206 | 0.00 |
LGSTORE2 | 22823.63 | 27388.36 | 78.61 | 1.677 | 2.012 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.88 | 0.01042 | 33.83 | 0.01654 | 0.411 | 0.00 |
SMSTORE5 | 11969.46 | 14363.35 | 82.46 | 0.880 | 1.055 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.88 | 0.01050 | 33.83 | 0.01654 | 0.206 | 0.00 |
SMSTORE6 | 11919.18 | 14303.01 | 82.11 | 0.876 | 1.051 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.88 | 0.01050 | 33.83 | 0.01654 | 0.206 | 0.00 |
SMSTORE7 | 11975.08 | 14370.09 | 82.50 | 0.880 | 1.056 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.88 | 0.01050 | 33.83 | 0.01654 | 0.206 | 0.00 |
SMSTORE8 | 13807.50 | 16569.01 | 95.12 | 1.014 | 1.217 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 23.89 | 23.88 | 0.01034 | 33.50 | 0.01654 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 16195.37 | 19434.44 | 55.78 | 0.699 | 0.838 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00705 | 4.60 | 0.00526 | 0.411 | 0.00 |
SMSTORE1 | 8027.70 | 9633.24 | 55.30 | 0.346 | 0.416 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00697 | 4.60 | 0.00526 | 0.206 | 0.00 |
SMSTORE2 | 8101.43 | 9721.71 | 55.81 | 0.350 | 0.419 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00698 | 4.60 | 0.00526 | 0.206 | 0.00 |
SMSTORE3 | 8169.83 | 9803.80 | 56.28 | 0.352 | 0.423 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00698 | 4.60 | 0.00526 | 0.206 | 0.00 |
SMSTORE4 | 8291.07 | 9949.28 | 57.12 | 0.358 | 0.429 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00699 | 4.60 | 0.00526 | 0.206 | 0.00 |
LGSTORE2 | 15646.95 | 18776.34 | 53.90 | 0.675 | 0.810 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00705 | 4.60 | 0.00526 | 0.411 | 0.00 |
SMSTORE5 | 8521.21 | 10225.45 | 58.70 | 0.368 | 0.441 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00701 | 4.60 | 0.00526 | 0.206 | 0.00 |
SMSTORE6 | 8525.42 | 10230.50 | 58.73 | 0.368 | 0.441 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00701 | 4.60 | 0.00526 | 0.206 | 0.00 |
SMSTORE7 | 8745.23 | 10494.27 | 60.25 | 0.377 | 0.453 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00702 | 4.60 | 0.00526 | 0.206 | 0.00 |
SMSTORE8 | 10297.43 | 12356.92 | 70.94 | 0.444 | 0.533 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00707 | 4.60 | 0.00526 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.16 | 2.16 | 0.84 | 0.84 | 2.1632 | 2.1632 | 2.1632 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.14 | 1.14 | 0.42 | 0.42 | 1.1356 | 1.1356 | 1.1356 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 1.14 | 1.14 | 0.42 | 0.42 | 1.1404 | 1.1404 | 1.1404 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 1.14 | 1.14 | 0.42 | 0.42 | 1.1441 | 1.1441 | 1.1441 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.14 | 1.14 | 0.43 | 0.43 | 1.1371 | 1.1371 | 1.1371 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 2.01 | 2.01 | 0.81 | 0.81 | 2.0125 | 2.0125 | 2.0125 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 1.06 | 1.06 | 0.44 | 0.44 | 1.0554 | 1.0554 | 1.0554 | 1.0000 | 1.0000 |
PSZ-AC_8:8 | 1.05 | 1.05 | 0.44 | 0.44 | 1.0510 | 1.0510 | 1.0510 | 1.0000 | 1.0000 |
PSZ-AC_9:9 | 1.06 | 1.06 | 0.45 | 0.45 | 1.0559 | 1.0559 | 1.0559 | 1.0000 | 1.0000 |
PSZ-AC_10:10 | 1.22 | 1.22 | 0.53 | 0.53 | 1.2173 | 1.2173 | 1.2173 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 53717.850 | 37660.510 | 2.163220 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 26858.92 | 17882.93 | 1.442147 | 26.65 | 19.70 | 0.01152666 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 28.5324 | 23.88 | 0.01034989 | 55.8993 | 24532.75 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 57621.398 | 57621.398 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 57621.40 | 57621.40 | 2.163218 | 17.97 | 12.42 | 0.00670555 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 19.0216 | 21.11 | 0.00704578 | 45.2801 | 16195.37 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 28199.780 | 19770.302 | 1.135610 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 14099.89 | 9405.51 | 0.757073 | 26.59 | 19.66 | 0.01149766 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 27.1756 | 23.88 | 0.01038281 | 56.0748 | 12878.55 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 30044.050 | 30044.050 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 30044.05 | 30044.05 | 1.135605 | 18.12 | 12.44 | 0.00666254 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 18.1172 | 21.11 | 0.00697350 | 44.8210 | 8027.70 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 28318.490 | 19853.527 | 1.140390 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 14159.25 | 9453.71 | 0.760260 | 26.59 | 19.65 | 0.01148801 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 27.0617 | 23.88 | 0.01037661 | 56.0419 | 12931.66 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 30153.240 | 30153.240 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 30153.24 | 30153.24 | 1.140386 | 18.13 | 12.45 | 0.00666794 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 18.0412 | 21.11 | 0.00697850 | 44.8528 | 8101.43 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 28410.340 | 19917.921 | 1.144080 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 14205.17 | 9491.11 | 0.762720 | 26.58 | 19.65 | 0.01148050 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 26.9744 | 23.88 | 0.01037177 | 56.0162 | 12972.94 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 30237.726 | 30237.726 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 30237.73 | 30237.73 | 1.144085 | 18.14 | 12.46 | 0.00667280 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 17.9829 | 21.11 | 0.00698320 | 44.8827 | 8169.83 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 28237.860 | 19796.999 | 1.137140 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 14118.93 | 9420.70 | 0.758093 | 26.59 | 19.66 | 0.01149485 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 27.1391 | 23.88 | 0.01038105 | 56.0655 | 12894.36 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 30079.070 | 30079.070 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 30079.07 | 30079.07 | 1.137139 | 18.12 | 12.46 | 0.00667807 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 18.0927 | 21.11 | 0.00699194 | 44.9383 | 8291.07 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 49974.260 | 35035.954 | 2.012460 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 24987.13 | 16421.45 | 1.341640 | 26.80 | 19.86 | 0.01167487 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 30.6698 | 23.88 | 0.01042515 | 56.2985 | 22820.03 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 54177.886 | 54177.886 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 54177.89 | 54177.89 | 2.012463 | 17.73 | 12.31 | 0.00668514 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 20.4465 | 21.11 | 0.00705215 | 45.3203 | 15646.95 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 26208.930 | 18374.557 | 1.055430 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 13104.47 | 8599.16 | 0.703620 | 26.73 | 19.84 | 0.01167533 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 29.2401 | 23.88 | 0.01049799 | 56.6864 | 11966.84 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 28212.898 | 28212.898 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28212.90 | 28212.90 | 1.055434 | 17.89 | 12.35 | 0.00666515 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 19.4934 | 21.11 | 0.00700608 | 45.0282 | 8521.21 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 26098.830 | 18297.368 | 1.051000 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 13049.42 | 8554.97 | 0.700667 | 26.74 | 19.85 | 0.01168575 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 29.3634 | 23.88 | 0.01050476 | 56.7224 | 11916.48 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 28111.624 | 28111.624 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28111.62 | 28111.62 | 1.051000 | 17.88 | 12.34 | 0.00666401 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 19.5756 | 21.11 | 0.00700645 | 45.0305 | 8525.42 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 26221.230 | 18383.180 | 1.055930 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 13110.61 | 8603.87 | 0.703953 | 26.73 | 19.84 | 0.01167445 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 29.2263 | 23.88 | 0.01049743 | 56.6835 | 11971.21 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 28224.201 | 28224.201 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28224.20 | 28224.20 | 1.055929 | 17.89 | 12.36 | 0.00667718 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 19.4842 | 21.11 | 0.00702081 | 45.1219 | 8745.23 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 29993.530 | 21115.445 | 1.217290 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 14996.76 | 10088.76 | 0.811527 | 26.41 | 19.52 | 0.01138587 | 12.80 | 12.09 | 0.00850000 | 33.50 | 0.01653563 | 25.03 | 25.3521 | 23.88 | 0.01033847 | 55.8395 | 13807.50 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 31910.122 | 31910.122 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31910.12 | 31910.12 | 1.217294 | 18.32 | 12.62 | 0.00676238 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 16.9014 | 21.11 | 0.00706853 | 45.4259 | 10297.43 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:41:29
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 53717.850 | 37660.510 | 2.163220 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.2675 | 1004.8586 | 1.2032 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.163218 | 2.60271223 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | Sensible | 26858.92 | 17882.93 | 1.0000 | 1.73514313 | 1.442147 | 26.65 | 19.70 | 0.01152666 | 56182.0 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26858.92 | 33.90 | 0.01653638 | 25.13 | 0.41147883 | 28.5324 | 23.88 | 0.01034989 | 23.88 | 0.01034989 | 55.8993 | 24532.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 57621.398 | 57621.398 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.163218 | 2.60271223 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 57621.40 | 57621.40 | 1.0000 | 2.60271223 | 2.163218 | 17.97 | 12.42 | 0.00670555 | 35049.2 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 57621.40 | 4.60 | 0.00525715 | 4.60 | 0.41147883 | 19.0216 | 21.11 | 0.00704578 | 21.11 | 0.00704578 | 45.2801 | 16195.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28199.780 | 19770.302 | 1.135610 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.2136 | 1004.8586 | 1.2032 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.135605 | 1.36632247 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | Sensible | 14099.89 | 9405.51 | 1.0000 | 0.91088557 | 0.757073 | 26.59 | 19.66 | 0.01149766 | 56045.8 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14099.89 | 33.90 | 0.01653638 | 25.13 | 0.20573941 | 27.1756 | 23.88 | 0.01038281 | 23.88 | 0.01038281 | 56.0748 | 12878.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30044.050 | 30044.050 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.135605 | 1.36632247 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 30044.05 | 30044.05 | 1.0000 | 1.36632247 | 1.135605 | 18.12 | 12.44 | 0.00666254 | 35092.0 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30044.05 | 4.60 | 0.00525715 | 4.60 | 0.20573941 | 18.1172 | 21.11 | 0.00697350 | 21.11 | 0.00697350 | 44.8210 | 8027.70 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28318.490 | 19853.527 | 1.140390 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.1956 | 1004.8586 | 1.2032 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.140386 | 1.37207414 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 14159.25 | 9453.71 | 1.0000 | 0.91471966 | 0.760260 | 26.59 | 19.65 | 0.01148801 | 56013.6 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14159.25 | 33.90 | 0.01653638 | 25.13 | 0.20573941 | 27.0617 | 23.88 | 0.01037661 | 23.88 | 0.01037661 | 56.0419 | 12931.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30153.240 | 30153.240 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.140386 | 1.37207414 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 30153.24 | 30153.24 | 1.0000 | 1.37207414 | 1.140386 | 18.13 | 12.45 | 0.00666794 | 35118.5 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30153.24 | 4.60 | 0.00525715 | 4.60 | 0.20573941 | 18.0412 | 21.11 | 0.00697850 | 21.11 | 0.00697850 | 44.8528 | 8101.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28410.340 | 19917.921 | 1.144080 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.1817 | 1004.8586 | 1.2032 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.144085 | 1.37652464 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 14205.17 | 9491.11 | 1.0000 | 0.91767946 | 0.762720 | 26.58 | 19.65 | 0.01148050 | 55988.5 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14205.17 | 33.90 | 0.01653638 | 25.13 | 0.20573941 | 26.9744 | 23.88 | 0.01037177 | 23.88 | 0.01037177 | 56.0162 | 12972.94 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30237.726 | 30237.726 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.144085 | 1.37652464 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 30237.73 | 30237.73 | 1.0000 | 1.37652464 | 1.144085 | 18.14 | 12.46 | 0.00667280 | 35140.6 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30237.73 | 4.60 | 0.00525715 | 4.60 | 0.20573941 | 17.9829 | 21.11 | 0.00698320 | 21.11 | 0.00698320 | 44.8827 | 8169.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28237.860 | 19796.999 | 1.137140 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.2084 | 1004.8586 | 1.2032 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.137139 | 1.36816746 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 14118.93 | 9420.70 | 1.0000 | 0.91211280 | 0.758093 | 26.59 | 19.66 | 0.01149485 | 56036.4 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14118.93 | 33.90 | 0.01653638 | 25.13 | 0.20573941 | 27.1391 | 23.88 | 0.01038105 | 23.88 | 0.01038105 | 56.0655 | 12894.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30079.070 | 30079.070 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.137139 | 1.36816746 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 30079.07 | 30079.07 | 1.0000 | 1.36816746 | 1.137139 | 18.12 | 12.46 | 0.00667807 | 35135.5 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30079.07 | 4.60 | 0.00525715 | 4.60 | 0.20573941 | 18.0927 | 21.11 | 0.00699194 | 21.11 | 0.00699194 | 44.9383 | 8291.07 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 49974.260 | 35035.954 | 2.012460 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.5430 | 1004.8586 | 1.2032 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.012463 | 2.42132921 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 24987.13 | 16421.45 | 1.0000 | 1.61421684 | 1.341640 | 26.80 | 19.86 | 0.01167487 | 56706.8 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24987.13 | 33.90 | 0.01653638 | 25.13 | 0.41147883 | 30.6698 | 23.88 | 0.01042515 | 23.88 | 0.01042515 | 56.2985 | 22820.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 54177.886 | 54177.886 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.012463 | 2.42132921 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 54177.89 | 54177.89 | 1.0000 | 2.42132921 | 2.012463 | 17.73 | 12.31 | 0.00668514 | 34758.2 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 54177.89 | 4.60 | 0.00525715 | 4.60 | 0.41147883 | 20.4465 | 21.11 | 0.00705215 | 21.11 | 0.00705215 | 45.3203 | 15646.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 26208.930 | 18374.557 | 1.055430 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.5439 | 1004.8586 | 1.2032 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.055434 | 1.26986279 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 13104.47 | 8599.16 | 1.0000 | 0.84657229 | 0.703620 | 26.73 | 19.84 | 0.01167533 | 56640.7 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13104.47 | 33.90 | 0.01653638 | 25.13 | 0.20573941 | 29.2401 | 23.88 | 0.01049799 | 23.88 | 0.01049799 | 56.6864 | 11966.84 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28212.898 | 28212.898 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.055434 | 1.26986279 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 28212.90 | 28212.90 | 1.0000 | 1.26986279 | 1.055434 | 17.89 | 12.35 | 0.00666515 | 34867.5 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28212.90 | 4.60 | 0.00525715 | 4.60 | 0.20573941 | 19.4934 | 21.11 | 0.00700608 | 21.11 | 0.00700608 | 45.0282 | 8521.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 26098.830 | 18297.368 | 1.051000 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.5632 | 1004.8586 | 1.2032 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.051000 | 1.26452805 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 13049.42 | 8554.97 | 1.0000 | 0.84301894 | 0.700667 | 26.74 | 19.85 | 0.01168575 | 56675.7 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13049.42 | 33.90 | 0.01653638 | 25.13 | 0.20573941 | 29.3634 | 23.88 | 0.01050476 | 23.88 | 0.01050476 | 56.7224 | 11916.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28111.624 | 28111.624 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.051000 | 1.26452805 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 28111.62 | 28111.62 | 1.0000 | 1.26452805 | 1.051000 | 17.88 | 12.34 | 0.00666401 | 34850.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28111.62 | 4.60 | 0.00525715 | 4.60 | 0.20573941 | 19.5756 | 21.11 | 0.00700645 | 21.11 | 0.00700645 | 45.0305 | 8525.42 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 26221.230 | 18383.180 | 1.055930 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.5422 | 1004.8586 | 1.2032 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.055929 | 1.27045863 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 13110.61 | 8603.87 | 1.0000 | 0.84697335 | 0.703953 | 26.73 | 19.84 | 0.01167445 | 56637.7 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13110.61 | 33.90 | 0.01653638 | 25.13 | 0.20573941 | 29.2263 | 23.88 | 0.01049743 | 23.88 | 0.01049743 | 56.6835 | 11971.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28224.201 | 28224.201 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.055929 | 1.27045863 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 28224.20 | 28224.20 | 1.0000 | 1.27045863 | 1.055929 | 17.89 | 12.36 | 0.00667718 | 34899.6 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28224.20 | 4.60 | 0.00525715 | 4.60 | 0.20573941 | 19.4842 | 21.11 | 0.00702081 | 21.11 | 0.00702081 | 45.1219 | 8745.23 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 29993.530 | 21115.445 | 1.217290 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.0058 | 1004.8586 | 1.2032 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.217294 | 1.46460767 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | Sensible | 14996.76 | 10088.76 | 1.0000 | 0.97640202 | 0.811527 | 26.41 | 19.52 | 0.01138587 | 55569.2 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14996.76 | 33.50 | 0.01653563 | 25.03 | 0.20573941 | 25.3521 | 23.88 | 0.01033847 | 23.88 | 0.01033847 | 55.8395 | 13807.50 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31910.122 | 31910.122 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.217294 | 1.46460767 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 31910.12 | 31910.12 | 1.0000 | 1.46460767 | 1.217294 | 18.32 | 12.62 | 0.00676238 | 35549.1 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31910.12 | 4.60 | 0.00525715 | 4.60 | 0.20573941 | 16.9014 | 21.11 | 0.00706853 | 21.11 | 0.00706853 | 45.4259 | 10297.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:29
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialEnthalpy | 0.41 | 2.16 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.14 | - | |||
PSZ-AC_3:3_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.14 | - | |||
PSZ-AC_4:4_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.14 | - | |||
PSZ-AC_5:5_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.14 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialEnthalpy | 0.41 | 2.01 | - | |||
PSZ-AC_7:7_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.06 | - | |||
PSZ-AC_8:8_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.05 | - | |||
PSZ-AC_9:9_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.06 | - | |||
PSZ-AC_10:10_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.22 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 4391.67 | 2312.50 | 1300.67 |
SMSTORE1 | 4310.67 | 1552.83 | 708.00 |
SMSTORE2 | 3308.50 | 1829.83 | 1116.17 |
SMSTORE3 | 3294.00 | 1842.67 | 1104.67 |
SMSTORE4 | 3268.00 | 1946.17 | 1164.67 |
LGSTORE2 | 2950.83 | 2164.83 | 1373.00 |
SMSTORE5 | 2919.33 | 2227.33 | 1402.33 |
SMSTORE6 | 2912.00 | 2269.33 | 1427.00 |
SMSTORE7 | 2902.50 | 2302.83 | 1438.83 |
SMSTORE8 | 2935.67 | 2105.83 | 1248.33 |
Facility | 4574.50 | 3223.17 | 1974.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 0.00 | 1.00 | 0.00 | 1.00 |
SMSTORE1 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 0.00 | 3.50 | 0.00 | 3.50 |
SMSTORE3 | 0.00 | 3.17 | 0.00 | 3.17 |
SMSTORE4 | 0.00 | 3.33 | 0.00 | 3.33 |
LGSTORE2 | 0.00 | 6.33 | 0.00 | 6.33 |
SMSTORE5 | 0.00 | 5.33 | 0.00 | 5.33 |
SMSTORE6 | 0.00 | 5.00 | 0.00 | 5.00 |
SMSTORE7 | 0.00 | 4.67 | 0.00 | 4.67 |
SMSTORE8 | 0.00 | 4.00 | 0.00 | 4.00 |
Facility | 0.00 | 10.50 | 0.00 | 10.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:29
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.92 | 56.25 | 1805.20 | 0.926 | 0.345 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.802 | 0.384 | 0.000 | 0.000 |
SMSTORE2 | 7.09 | 28.12 | 902.60 | 0.973 | 0.504 | 0.000 | 0.000 |
SMSTORE3 | 7.09 | 28.12 | 902.60 | 0.971 | 0.504 | 0.000 | 0.000 |
SMSTORE4 | 7.09 | 28.12 | 902.60 | 0.964 | 0.504 | 0.000 | 0.000 |
LGSTORE2 | 24.81 | 56.25 | 1805.20 | 0.944 | 0.471 | 0.000 | 0.000 |
SMSTORE5 | 12.41 | 28.12 | 902.60 | 0.949 | 0.538 | 0.000 | 0.000 |
SMSTORE6 | 12.41 | 28.12 | 902.60 | 0.947 | 0.538 | 0.000 | 0.000 |
SMSTORE7 | 12.41 | 28.12 | 902.60 | 0.944 | 0.538 | 0.000 | 0.000 |
SMSTORE8 | 12.41 | 28.12 | 902.60 | 0.964 | 0.553 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.92 | 56.25 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.09 | 28.12 | 902.60 | 0.804 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.09 | 28.12 | 902.60 | 0.804 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.09 | 28.12 | 902.60 | 0.804 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.81 | 56.25 | 1805.20 | 0.803 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.41 | 28.12 | 902.60 | 0.802 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.41 | 28.12 | 902.60 | 0.802 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.41 | 28.12 | 902.60 | 0.801 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.41 | 28.12 | 902.60 | 0.799 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:41:29
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 16.92 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE1 | PSZ-AC_2:2 | 8.46 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE2 | PSZ-AC_3:3 | 7.09 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE3 | PSZ-AC_4:4 | 7.09 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE4 | PSZ-AC_5:5 | 7.09 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
LGSTORE2 | PSZ-AC_6:6 | 24.81 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE5 | PSZ-AC_7:7 | 12.41 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE6 | PSZ-AC_8:8 | 12.41 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE7 | PSZ-AC_9:9 | 12.41 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE8 | PSZ-AC_10:10 | 12.41 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
Total Facility | 121.09 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 2.469 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 9547422.66 | 0.00 | 9547422.66 | 3838649.30 | 13386071.96 | 12976396.34 | 3178.71 | 4739.65 | 841.64 | 0.00 |
SMSTORE1 | 4138162.00 | 0.00 | 4138162.00 | 2068521.06 | 6206683.06 | 6488198.17 | 4440.37 | 3476.11 | 843.51 | 0.00 |
SMSTORE2 | 3777357.04 | 0.00 | 3777357.04 | 2094113.03 | 5871470.07 | 6488198.17 | 4365.00 | 3812.45 | 582.55 | 0.67 |
SMSTORE3 | 3766732.99 | 0.00 | 3766732.99 | 2094113.03 | 5860846.02 | 6488198.17 | 4364.83 | 3828.11 | 567.06 | 1.50 |
SMSTORE4 | 3739801.84 | 0.00 | 3739801.84 | 2094113.03 | 5833914.87 | 6488198.17 | 4364.83 | 3858.93 | 536.24 | 1.17 |
LGSTORE2 | 6712362.55 | 0.00 | 6712362.55 | 3717029.21 | 10429391.76 | 12976396.34 | 4729.83 | 3536.71 | 493.46 | 0.17 |
SMSTORE5 | 3374207.20 | 0.00 | 3374207.20 | 2101897.61 | 5476104.81 | 6488198.17 | 4730.00 | 3547.76 | 482.24 | 0.17 |
SMSTORE6 | 3368993.41 | 0.00 | 3368993.41 | 2101897.61 | 5470891.02 | 6488198.17 | 4730.00 | 3550.65 | 479.35 | 0.00 |
SMSTORE7 | 3357491.61 | 0.00 | 3357491.61 | 2101897.61 | 5459389.22 | 6488198.17 | 4730.00 | 3567.82 | 462.18 | 0.00 |
SMSTORE8 | 3428914.81 | 0.00 | 3428914.81 | 2340335.64 | 5769250.45 | 6488198.17 | 4729.67 | 3577.91 | 452.42 | 0.33 |
Total Facility | 45211446.10 | 0.00 | 45211446.10 | 24552567.14 | 69764013.24 | 77858378.04 | 4730.00 | 5253.92 | 1111.84 | 1.83 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.4541 | 0.0000 | 0.4541 | 0.1689 | 0.6230 | 0.4115 | 258.71 | 4739.65 | 841.64 |
SMSTORE1 | 0.1968 | 0.0000 | 0.1968 | 0.0942 | 0.2910 | 0.2057 | 1520.37 | 3476.11 | 843.51 |
SMSTORE2 | 0.2387 | 0.0000 | 0.2387 | 0.1236 | 0.3623 | 0.2057 | 0.00 | 3812.45 | 582.55 |
SMSTORE3 | 0.2380 | 0.0000 | 0.2380 | 0.1236 | 0.3616 | 0.2057 | 0.00 | 3828.11 | 566.89 |
SMSTORE4 | 0.2363 | 0.0000 | 0.2363 | 0.1236 | 0.3599 | 0.2057 | 0.00 | 3858.93 | 536.07 |
LGSTORE2 | 0.4626 | 0.0000 | 0.4626 | 0.2310 | 0.6937 | 0.4115 | 0.00 | 3536.71 | 493.29 |
SMSTORE5 | 0.2326 | 0.0000 | 0.2326 | 0.1317 | 0.3643 | 0.2057 | 0.00 | 3547.76 | 482.24 |
SMSTORE6 | 0.2322 | 0.0000 | 0.2322 | 0.1317 | 0.3639 | 0.2057 | 0.00 | 3550.65 | 479.35 |
SMSTORE7 | 0.2314 | 0.0000 | 0.2314 | 0.1317 | 0.3631 | 0.2057 | 0.00 | 3567.82 | 462.18 |
SMSTORE8 | 0.2363 | 0.0000 | 0.2363 | 0.1354 | 0.3717 | 0.2057 | 0.00 | 3577.91 | 452.09 |
Total Facility | 2.7592 | 0.0000 | 2.7592 | 1.3954 | 4.1546 | 2.4689 | 1624.54 | 5253.92 | 1111.34 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 13820905.30 | 0.00 | 13820905.30 | 12976396.34 | 3177.55 | 0.00 | 5582.45 | 0.00 |
PSZ-AC_2:2 | 5990424.55 | 0.00 | 5990424.55 | 6488198.17 | 4375.15 | 1.08 | 4383.77 | 0.00 |
PSZ-AC_3:3 | 5468119.70 | 0.00 | 5468119.70 | 6488198.17 | 4364.83 | 0.00 | 4395.17 | 0.67 |
PSZ-AC_4:4 | 5452741.24 | 0.00 | 5452741.24 | 6488198.17 | 4364.67 | 0.00 | 4395.33 | 1.50 |
PSZ-AC_5:5 | 5413755.00 | 0.00 | 5413755.00 | 6488198.17 | 4364.67 | 0.00 | 4395.33 | 1.17 |
PSZ-AC_6:6 | 9716839.26 | 0.00 | 9716839.26 | 12976396.34 | 4729.83 | 0.00 | 4030.17 | 0.17 |
PSZ-AC_7:7 | 4884517.52 | 0.00 | 4884517.52 | 6488198.17 | 4730.00 | 0.00 | 4030.00 | 0.17 |
PSZ-AC_8:8 | 4876967.76 | 0.00 | 4876967.76 | 6488198.17 | 4730.00 | 0.00 | 4030.00 | 0.00 |
PSZ-AC_9:9 | 4860312.38 | 0.00 | 4860312.38 | 6488198.17 | 4730.00 | 0.00 | 4030.00 | 0.00 |
PSZ-AC_10:10 | 4963703.02 | 0.00 | 4963703.02 | 6488198.17 | 4729.67 | 0.00 | 4030.33 | 0.33 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.6574 | 0.0000 | 0.6574 | 0.4115 | 257.55 | 0.00 | 5582.45 |
PSZ-AC_2:2 | 0.2849 | 0.0000 | 0.2849 | 0.2057 | 1455.15 | 1.08 | 4383.77 |
PSZ-AC_3:3 | 0.3456 | 0.0000 | 0.3456 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_4:4 | 0.3446 | 0.0000 | 0.3446 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_5:5 | 0.3421 | 0.0000 | 0.3421 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_6:6 | 0.6697 | 0.0000 | 0.6697 | 0.4115 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_7:7 | 0.3367 | 0.0000 | 0.3367 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_8:8 | 0.3362 | 0.0000 | 0.3362 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_9:9 | 0.3350 | 0.0000 | 0.3350 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_10:10 | 0.3421 | 0.0000 | 0.3421 | 0.2057 | 0.00 | 0.00 | 4030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 5136.25 | 453.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 4843.39 | 646.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 4146.63 | 249.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 4156.40 | 240.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 4174.00 | 222.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 3842.44 | 187.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 3838.38 | 191.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 3841.43 | 188.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 3848.77 | 181.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 3836.36 | 193.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.6622 | 0.9666 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.2898 | 0.4034 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 0.3357 | 0.5129 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 0.3351 | 0.5118 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 0.3332 | 0.5142 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 0.6559 | 0.9571 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.3290 | 0.4929 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.3287 | 0.4906 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.3279 | 0.4886 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.3328 | 0.5279 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:29
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 759 |
Defaulted Fields | 823 |
Fields with Defaults | 2681 |
Autosized Fields | 184 |
Autosizable Fields | 458 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:41:29
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1096.22 | 2912.14 | 01-JAN-07:30 | 121668.09 | 10-SEP-12:30 |
Electricity:Building | 510.47 | 1694.14 | 01-JAN-00:10 | 31739.81 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 114.75 | 316.43 | 01-JAN-00:10 | 5937.46 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 510.47 | 1694.14 | 01-JAN-00:10 | 31739.81 | 01-JAN-11:10 |
InteriorLights:Electricity | 381.75 | 1244.72 | 01-JAN-00:10 | 23650.28 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 88.39 | 241.52 | 01-JAN-00:10 | 4589.20 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 381.75 | 1244.72 | 01-JAN-00:10 | 23650.28 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 381.75 | 1244.72 | 01-JAN-00:10 | 23650.28 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 88.39 | 241.52 | 01-JAN-00:10 | 4589.20 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 381.75 | 1244.72 | 01-JAN-00:10 | 23650.28 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 66.35 | 182.75 | 01-JAN-00:10 | 3434.71 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 53.17 | 145.29 | 01-JAN-00:10 | 2760.58 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 53.17 | 145.29 | 01-JAN-00:10 | 2760.58 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 49.13 | 169.56 | 01-JAN-00:10 | 3184.23 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 38.67 | 132.11 | 01-JAN-00:10 | 2510.11 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 38.67 | 132.11 | 01-JAN-00:10 | 2510.11 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 49.13 | 169.56 | 01-JAN-00:10 | 3184.23 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 38.67 | 132.11 | 01-JAN-00:10 | 2510.11 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 38.67 | 132.11 | 01-JAN-00:10 | 2510.11 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 49.13 | 169.56 | 01-JAN-00:10 | 3184.23 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 38.67 | 132.11 | 01-JAN-00:10 | 2510.11 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 38.67 | 132.11 | 01-JAN-00:10 | 2510.11 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 59.93 | 226.07 | 01-JAN-00:10 | 4220.73 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 40.67 | 151.17 | 01-JAN-00:10 | 2872.47 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 40.67 | 151.17 | 01-JAN-00:10 | 2872.47 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 30.51 | 115.05 | 01-JAN-00:10 | 2148.56 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 20.88 | 77.60 | 01-JAN-00:10 | 1474.43 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 20.88 | 77.60 | 01-JAN-00:10 | 1474.43 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 30.51 | 115.05 | 01-JAN-00:10 | 2148.56 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 20.88 | 77.60 | 01-JAN-00:10 | 1474.43 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 20.88 | 77.60 | 01-JAN-00:10 | 1474.43 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 30.51 | 115.05 | 01-JAN-00:10 | 2148.56 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 20.88 | 77.60 | 01-JAN-00:10 | 1474.43 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 20.88 | 77.60 | 01-JAN-00:10 | 1474.43 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 30.51 | 115.05 | 01-JAN-00:10 | 2148.56 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 20.88 | 77.60 | 01-JAN-00:10 | 1474.43 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 20.88 | 77.60 | 01-JAN-00:10 | 1474.43 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.36 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.36 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.18 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.18 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.26 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.26 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
ElectricityPurchased:Facility | 1096.22 | 2912.14 | 01-JAN-07:30 | 121668.09 | 10-SEP-12:30 |
ElectricityPurchased:Plant | 1096.22 | 2912.14 | 01-JAN-07:30 | 121668.09 | 10-SEP-12:30 |
Cogeneration:ElectricityPurchased | 1096.22 | 2912.14 | 01-JAN-07:30 | 121668.09 | 10-SEP-12:30 |
General:Cogeneration:ElectricityPurchased | 1096.22 | 2912.14 | 01-JAN-07:30 | 121668.09 | 10-SEP-12:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1096.22 | 2912.14 | 01-JAN-07:30 | 121668.09 | 10-SEP-12:30 |
ElectricityNet:Plant | 1096.22 | 2912.14 | 01-JAN-07:30 | 121668.09 | 10-SEP-12:30 |
Cogeneration:ElectricityNet | 1096.22 | 2912.14 | 01-JAN-07:30 | 121668.09 | 10-SEP-12:30 |
General:Cogeneration:ElectricityNet | 1096.22 | 2912.14 | 01-JAN-07:30 | 121668.09 | 10-SEP-12:30 |
Electricity:HVAC | 459.11 | 0.00 | 01-JAN-00:10 | 84587.90 | 10-SEP-12:50 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 355.06 | 0.00 | 01-JAN-00:10 | 72997.86 | 10-SEP-13:30 |
General:Cooling:Electricity | 355.06 | 0.00 | 01-JAN-00:10 | 72997.86 | 10-SEP-13:30 |
Fans:Electricity | 104.05 | 0.00 | 01-JAN-00:10 | 11597.37 | 10-SEP-13:00 |
General:Fans:Electricity | 104.05 | 0.00 | 01-JAN-00:10 | 11597.37 | 10-SEP-13:00 |
ExteriorLights:Electricity | 70.25 | 0.00 | 01-JAN-07:30 | 5403.30 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 70.25 | 0.00 | 01-JAN-07:30 | 5403.30 | 01-JAN-06:10 |
Electricity:Plant | 56.40 | 1218.00 | 05-JAN-09:10 | 9863.70 | 04-JAN-13:30 |
WaterSystems:Electricity | 56.40 | 1218.00 | 05-JAN-09:10 | 9863.70 | 04-JAN-13:30 |
Water Heater:WaterSystems:Electricity | 56.40 | 1218.00 | 05-JAN-09:10 | 9863.70 | 04-JAN-13:30 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 18.64 | 0.00 | 01-JAN-00:10 | 102580.99 | 05-FEB-10:10 |
NaturalGas:HVAC | 18.64 | 0.00 | 01-JAN-00:10 | 102580.99 | 05-FEB-10:10 |
Heating:NaturalGas | 18.64 | 0.00 | 01-JAN-00:10 | 102580.99 | 05-FEB-10:10 |
General:Heating:NaturalGas | 18.64 | 0.00 | 01-JAN-00:10 | 102580.99 | 05-FEB-10:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2261.28 | 0.00 | 01-JAN-00:10 | 411562.63 | 10-SEP-13:00 |
EnergyTransfer:Building | 781.22 | 0.00 | 01-JAN-00:10 | 121822.63 | 10-SEP-14:10 |
EnergyTransfer:Zone:LGSTORE1 | 161.47 | 0.00 | 01-JAN-00:10 | 19787.40 | 10-SEP-15:00 |
Heating:EnergyTransfer | 11.38 | 0.00 | 01-JAN-00:10 | 44452.64 | 06-FEB-09:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 1.33 | 0.00 | 01-JAN-00:10 | 12231.71 | 05-FEB-09:10 |
General:Heating:EnergyTransfer | 11.38 | 0.00 | 01-JAN-00:10 | 44452.64 | 06-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 1.33 | 0.00 | 01-JAN-00:10 | 12231.71 | 05-FEB-09:10 |
Cooling:EnergyTransfer | 769.84 | 0.00 | 01-JAN-00:10 | 121822.63 | 10-SEP-14:10 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 160.14 | 0.00 | 01-JAN-00:10 | 19787.40 | 10-SEP-15:00 |
General:Cooling:EnergyTransfer | 769.84 | 0.00 | 01-JAN-00:10 | 121822.63 | 10-SEP-14:10 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 160.14 | 0.00 | 01-JAN-00:10 | 19787.40 | 10-SEP-15:00 |
EnergyTransfer:Zone:SMSTORE1 | 86.33 | 0.00 | 01-JAN-00:10 | 10284.06 | 10-SEP-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 0.61 | 0.00 | 01-JAN-00:10 | 2744.21 | 05-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 0.61 | 0.00 | 01-JAN-00:10 | 2744.21 | 05-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 85.72 | 0.00 | 01-JAN-00:10 | 10284.06 | 10-SEP-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 85.72 | 0.00 | 01-JAN-00:10 | 10284.06 | 10-SEP-13:00 |
EnergyTransfer:Zone:SMSTORE2 | 66.46 | 0.00 | 01-JAN-00:10 | 10289.65 | 10-SEP-14:00 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 1.10 | 0.00 | 01-JAN-00:10 | 4784.54 | 05-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 1.10 | 0.00 | 01-JAN-00:10 | 4784.54 | 05-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 65.36 | 0.00 | 01-JAN-00:10 | 10289.65 | 10-SEP-14:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 65.36 | 0.00 | 01-JAN-00:10 | 10289.65 | 10-SEP-14:00 |
EnergyTransfer:Zone:SMSTORE3 | 66.27 | 0.00 | 01-JAN-00:10 | 10361.06 | 10-SEP-14:00 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 1.10 | 0.00 | 01-JAN-00:10 | 5382.00 | 05-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 1.10 | 0.00 | 01-JAN-00:10 | 5382.00 | 05-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 65.17 | 0.00 | 01-JAN-00:10 | 10361.06 | 10-SEP-14:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 65.17 | 0.00 | 01-JAN-00:10 | 10361.06 | 10-SEP-14:00 |
EnergyTransfer:Zone:SMSTORE4 | 64.52 | 0.00 | 01-JAN-00:10 | 10287.60 | 10-SEP-14:00 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 1.14 | 0.00 | 01-JAN-00:10 | 5354.92 | 05-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 1.14 | 0.00 | 01-JAN-00:10 | 5354.92 | 05-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 63.38 | 0.00 | 01-JAN-00:10 | 10287.60 | 10-SEP-14:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 63.38 | 0.00 | 01-JAN-00:10 | 10287.60 | 10-SEP-14:00 |
EnergyTransfer:Zone:LGSTORE2 | 108.79 | 0.00 | 01-JAN-00:10 | 19099.03 | 10-SEP-14:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 1.71 | 0.00 | 01-JAN-00:10 | 8822.47 | 06-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 1.71 | 0.00 | 01-JAN-00:10 | 8822.47 | 06-FEB-09:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 107.08 | 0.00 | 01-JAN-00:10 | 19099.03 | 10-SEP-14:10 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 107.08 | 0.00 | 01-JAN-00:10 | 19099.03 | 10-SEP-14:10 |
EnergyTransfer:Zone:SMSTORE5 | 56.05 | 0.00 | 01-JAN-00:10 | 10133.87 | 10-SEP-14:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 0.95 | 0.00 | 01-JAN-00:10 | 4846.54 | 06-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 0.95 | 0.00 | 01-JAN-00:10 | 4846.54 | 06-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 55.10 | 0.00 | 01-JAN-00:10 | 10133.87 | 10-SEP-14:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 55.10 | 0.00 | 01-JAN-00:10 | 10133.87 | 10-SEP-14:10 |
EnergyTransfer:Zone:SMSTORE6 | 55.44 | 0.00 | 01-JAN-00:10 | 10100.93 | 10-SEP-14:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 0.97 | 0.00 | 01-JAN-00:10 | 5290.76 | 06-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 0.97 | 0.00 | 01-JAN-00:10 | 5290.76 | 06-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 54.47 | 0.00 | 01-JAN-00:10 | 10100.93 | 10-SEP-14:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 54.47 | 0.00 | 01-JAN-00:10 | 10100.93 | 10-SEP-14:10 |
EnergyTransfer:Zone:SMSTORE7 | 54.92 | 0.00 | 01-JAN-00:10 | 10213.30 | 10-SEP-14:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 1.05 | 0.00 | 01-JAN-00:10 | 6574.08 | 06-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 1.05 | 0.00 | 01-JAN-00:10 | 6574.08 | 06-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 53.88 | 0.00 | 01-JAN-00:10 | 10213.30 | 10-SEP-14:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 53.88 | 0.00 | 01-JAN-00:10 | 10213.30 | 10-SEP-14:10 |
EnergyTransfer:Zone:SMSTORE8 | 60.97 | 0.00 | 01-JAN-00:10 | 11886.95 | 10-SEP-14:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 1.41 | 0.00 | 01-JAN-00:10 | 9261.38 | 21-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 1.41 | 0.00 | 01-JAN-00:10 | 9261.38 | 21-DEC-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 59.55 | 0.00 | 01-JAN-00:10 | 11886.95 | 10-SEP-14:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 59.55 | 0.00 | 01-JAN-00:10 | 11886.95 | 10-SEP-14:10 |
EnergyTransfer:HVAC | 1480.05 | 0.00 | 01-JAN-00:10 | 292048.15 | 10-SEP-13:00 |
HeatingCoils:EnergyTransfer | 14.91 | 0.00 | 01-JAN-00:10 | 82064.79 | 05-FEB-10:10 |
CoolingCoils:EnergyTransfer | 1465.14 | 0.00 | 01-JAN-00:10 | 292048.15 | 10-SEP-13:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:29
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 1.333 | -160.136 | 0.000 | 0.000 | 23.579 | 88.395 | 26.357 | 19.418 | 0.000 | 14.099 | 2.656 | 0.000 | -5.115 | 0.000 | -10.586 | -0.001 |
SMSTORE1 | 0.000 | 0.000 | 0.609 | -85.717 | 0.000 | 0.000 | 11.721 | 53.173 | 13.179 | 9.674 | 0.000 | 7.914 | 0.001 | 0.000 | -2.658 | 0.000 | -5.525 | -2.370 |
SMSTORE2 | 0.000 | 0.000 | 1.100 | -65.354 | 0.000 | 0.000 | 7.077 | 38.666 | 10.467 | 9.620 | 0.000 | 7.793 | 0.000 | 0.000 | -2.748 | 0.000 | -5.625 | -0.997 |
SMSTORE3 | 0.000 | 0.000 | 1.100 | -65.173 | 0.000 | 0.000 | 7.081 | 38.666 | 10.467 | 9.624 | 0.000 | 7.791 | 0.000 | 0.000 | -2.737 | 0.000 | -5.593 | -1.228 |
SMSTORE4 | 0.000 | 0.000 | 1.142 | -63.377 | 0.000 | 0.000 | 7.089 | 38.666 | 10.467 | 9.644 | 0.000 | 7.794 | 0.001 | 0.000 | -2.694 | 0.000 | -5.531 | -3.200 |
LGSTORE2 | 0.000 | 0.000 | 1.711 | -107.077 | 0.000 | 0.000 | 24.361 | 40.672 | 19.261 | 19.352 | 0.000 | 13.620 | 3.056 | 0.000 | -5.142 | 0.000 | -9.814 | -0.000 |
SMSTORE5 | 0.000 | 0.000 | 0.954 | -55.096 | 0.000 | 0.000 | 12.189 | 20.877 | 9.631 | 9.684 | 0.000 | 7.771 | 1.968 | 0.000 | -2.540 | 0.000 | -5.438 | -0.001 |
SMSTORE6 | 0.000 | 0.000 | 0.972 | -54.467 | 0.000 | 0.000 | 12.195 | 20.877 | 9.631 | 9.693 | 0.000 | 7.772 | 1.263 | 0.000 | -2.524 | 0.000 | -5.411 | -0.001 |
SMSTORE7 | 0.000 | 0.000 | 1.048 | -53.874 | 0.000 | 0.000 | 12.206 | 20.877 | 9.631 | 9.705 | 0.000 | 7.773 | 0.485 | 0.000 | -2.496 | 0.000 | -5.354 | -0.000 |
SMSTORE8 | 0.000 | 0.000 | 1.413 | -59.550 | 0.000 | 0.000 | 12.218 | 20.877 | 9.631 | 9.685 | 0.000 | 7.967 | 6.629 | 0.000 | -2.400 | 0.000 | -6.469 | -0.001 |
Total Facility | 0.000 | 0.000 | 11.381 | -769.822 | 0.000 | 0.000 | 129.716 | 381.746 | 128.721 | 116.101 | 0.000 | 90.294 | 16.060 | 0.000 | -31.054 | 0.000 | -65.346 | -7.798 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | -49223.15 | 0.00 | 0.00 | 167.07 | 2415.36 | 749.03 | 403.83 | 0.00 | 0.00 | 45810.28 | 0.00 | -0.00 | 0.00 | -322.42 | 0.00 |
SMSTORE1 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | -26440.48 | 0.00 | 0.00 | 82.70 | 1452.94 | 374.52 | 199.57 | 0.00 | 0.00 | 24499.77 | 0.00 | -0.00 | 0.00 | -169.02 | 0.00 |
SMSTORE2 | 17-OCT-07:02 | 0.00 | 0.00 | 0.00 | -28333.57 | 0.00 | 0.00 | 86.28 | 1321.11 | 374.52 | 0.00 | 0.00 | 0.00 | 27094.01 | 0.00 | -149.78 | 0.00 | -392.56 | 0.00 |
SMSTORE3 | 17-OCT-07:02 | 0.00 | 0.00 | 0.00 | -28471.29 | 0.00 | 0.00 | 85.96 | 1321.11 | 374.52 | 0.00 | 0.00 | 0.00 | 27234.71 | 0.00 | -150.86 | 0.00 | -394.15 | 0.00 |
SMSTORE4 | 17-OCT-07:02 | 0.00 | 0.00 | 0.00 | -28207.64 | 0.00 | 0.00 | 86.57 | 1321.11 | 374.52 | 0.00 | 0.00 | 0.00 | 26965.60 | 0.00 | -149.14 | 0.00 | -391.02 | 0.00 |
LGSTORE2 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | -45231.31 | 0.00 | 0.00 | 372.31 | 1511.82 | 749.03 | 404.50 | 0.00 | 0.00 | 42485.40 | 0.00 | -0.00 | 0.00 | -291.75 | 0.00 |
SMSTORE5 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | -23581.65 | 0.00 | 0.00 | 187.49 | 776.01 | 374.52 | 203.02 | 0.00 | 0.00 | 22199.67 | 0.00 | -0.00 | 0.00 | -159.06 | 0.00 |
SMSTORE6 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | -23455.23 | 0.00 | 0.00 | 187.91 | 776.01 | 374.52 | 203.63 | 0.00 | 0.00 | 22071.32 | 0.00 | -0.00 | 0.00 | -158.15 | 0.00 |
SMSTORE7 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | -23537.56 | 0.00 | 0.00 | 188.23 | 776.01 | 374.52 | 203.68 | 0.00 | 0.00 | 22152.17 | 0.00 | -0.00 | 0.00 | -157.06 | 0.00 |
SMSTORE8 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | -27208.80 | 0.00 | 0.00 | 187.97 | 776.01 | 374.52 | 203.35 | 0.00 | 0.00 | 25841.39 | 0.00 | -0.00 | 0.00 | -174.43 | 0.00 |
Total Facility | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | -229490.77 | 0.00 | 0.00 | 1964.70 | 16014.49 | 5393.02 | 2482.23 | 0.00 | 0.00 | 205421.46 | 0.00 | 0.00 | 0.00 | -1785.13 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 06-FEB-09:01 | 0.00 | 0.00 | 51376.49 | 0.00 | 0.00 | 0.00 | 245.60 | 2415.36 | 749.03 | 1311.20 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1142.50 | -54955.18 |
SMSTORE1 | 21-DEC-09:01 | 0.00 | 0.00 | 13480.88 | 0.00 | 0.00 | 0.00 | 118.43 | 1452.94 | 374.52 | 18.42 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -651.63 | -14793.55 |
SMSTORE2 | 05-FEB-09:02 | 0.00 | 0.00 | 21824.75 | 0.00 | 0.00 | 0.00 | 121.56 | 1321.11 | 374.52 | 597.85 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1017.42 | -23222.37 |
SMSTORE3 | 05-FEB-09:02 | 0.00 | 0.00 | 24874.45 | 0.00 | 0.00 | 0.00 | 122.45 | 1321.11 | 374.52 | 601.84 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1016.24 | -26278.13 |
SMSTORE4 | 05-FEB-09:02 | 0.00 | 0.00 | 24763.95 | 0.00 | 0.00 | 0.00 | 123.27 | 1321.11 | 374.52 | 605.03 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1008.63 | -26179.24 |
LGSTORE2 | 12-MAR-09:01 | 0.00 | 0.00 | 49704.18 | 0.00 | 0.00 | 0.00 | 542.53 | 1511.82 | 749.03 | 922.66 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -706.20 | -52724.02 |
SMSTORE5 | 12-MAR-09:01 | 0.00 | 0.00 | 25970.29 | 0.00 | 0.00 | 0.00 | 272.08 | 776.01 | 374.52 | 461.56 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -398.65 | -27455.82 |
SMSTORE6 | 12-MAR-09:01 | 0.00 | 0.00 | 25896.78 | 0.00 | 0.00 | 0.00 | 273.07 | 776.01 | 374.52 | 463.67 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -394.79 | -27389.25 |
SMSTORE7 | 12-MAR-09:01 | 0.00 | 0.00 | 26082.51 | 0.00 | 0.00 | 0.00 | 276.72 | 776.01 | 374.52 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -381.27 | -27599.39 |
SMSTORE8 | 05-FEB-09:02 | 0.00 | 0.00 | 31129.27 | 0.00 | 0.00 | 0.00 | 0.00 | 77.60 | 37.45 | 659.54 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1015.50 | -30888.36 |
Total Facility | 21-DEC-09:01 | 0.00 | 0.00 | 215832.98 | 0.00 | 0.00 | 0.00 | 2707.39 | 16014.49 | 5393.02 | 423.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7395.20 | -232975.89 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:29
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.1632 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.1632 | 0.1902 | 1.0000 | Not calculated | 0.4115 | 0.1902 | ||
PSZ-AC_2:2 | 1.1356 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1356 | 0.1812 | 1.0000 | Not calculated | 0.2057 | 0.1812 | ||
PSZ-AC_3:3 | 1.1404 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1404 | 0.1804 | 1.0000 | Not calculated | 0.2057 | 0.1804 | ||
PSZ-AC_4:4 | 1.1441 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1441 | 0.1798 | 1.0000 | Not calculated | 0.2057 | 0.1798 | ||
PSZ-AC_5:5 | 1.1371 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1371 | 0.1809 | 1.0000 | Not calculated | 0.2057 | 0.1809 | ||
PSZ-AC_6:6 | 2.0125 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.0125 | 0.2045 | 1.0000 | Not calculated | 0.4115 | 0.2045 | ||
PSZ-AC_7:7 | 1.0554 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0554 | 0.1949 | 1.0000 | Not calculated | 0.2057 | 0.1949 | ||
PSZ-AC_8:8 | 1.0510 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0510 | 0.1958 | 1.0000 | Not calculated | 0.2057 | 0.1958 | ||
PSZ-AC_9:9 | 1.0559 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0559 | 0.1948 | 1.0000 | Not calculated | 0.2057 | 0.1948 | ||
PSZ-AC_10:10 | 1.2173 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2173 | 0.1690 | 1.0000 | Not calculated | 0.2057 | 0.1690 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.1632 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.1632 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.1902 | ||
PSZ-AC_2:2 | 1.1356 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1356 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1812 | ||
PSZ-AC_3:3 | 1.1404 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1404 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1804 | ||
PSZ-AC_4:4 | 1.1441 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1441 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1798 | ||
PSZ-AC_5:5 | 1.1371 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1371 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1809 | ||
PSZ-AC_6:6 | 2.0125 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.0125 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2045 | ||
PSZ-AC_7:7 | 1.0554 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0554 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1949 | ||
PSZ-AC_8:8 | 1.0510 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0510 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1958 | ||
PSZ-AC_9:9 | 1.0559 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0559 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1948 | ||
PSZ-AC_10:10 | 1.2173 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2173 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1690 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.1632 | 2.1632 | 2.1632 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1356 | 1.1356 | 1.1356 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1404 | 1.1404 | 1.1404 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1441 | 1.1441 | 1.1441 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1371 | 1.1371 | 1.1371 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.0125 | 2.0125 | 2.0125 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0554 | 1.0554 | 1.0554 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0510 | 1.0510 | 1.0510 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0559 | 1.0559 | 1.0559 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2173 | 1.2173 | 1.2173 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.1632 | 2.1632 | 2.1632 | 2.1632 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.1356 | 1.1356 | 1.1356 | 1.1356 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.1404 | 1.1404 | 1.1404 | 1.1404 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.1441 | 1.1441 | 1.1441 | 1.1441 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.1371 | 1.1371 | 1.1371 | 1.1371 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.0125 | 2.0125 | 2.0125 | 2.0125 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.0554 | 1.0554 | 1.0554 | 1.0554 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.0510 | 1.0510 | 1.0510 | 1.0510 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.0559 | 1.0559 | 1.0559 | 1.0559 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.2173 | 1.2173 | 1.2173 | 1.2173 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.1632 | 2.1632 | 2.1632 | No | 0.4115 | 0.4907 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1356 | 1.1356 | 1.1356 | No | 0.2057 | 0.4950 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1404 | 1.1404 | 1.1404 | No | 0.2057 | 0.4905 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1441 | 1.1441 | 1.1441 | No | 0.2057 | 0.4864 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1371 | 1.1371 | 1.1371 | No | 0.2057 | 0.4793 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.0125 | 2.0125 | 2.0125 | No | 0.4115 | 0.5079 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0554 | 1.0554 | 1.0554 | No | 0.2057 | 0.4664 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0510 | 1.0510 | 1.0510 | No | 0.2057 | 0.4661 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0559 | 1.0559 | 1.0559 | No | 0.2057 | 0.4544 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2173 | 1.2173 | 1.2173 | No | 0.2057 | 0.3859 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.1632 | 2.1632 | 2.1632 | 2.1632 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.1356 | 1.1356 | 1.1356 | 1.1356 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.1404 | 1.1404 | 1.1404 | 1.1404 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.1441 | 1.1441 | 1.1441 | 1.1441 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.1371 | 1.1371 | 1.1371 | 1.1371 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.0125 | 2.0125 | 2.0125 | 2.0125 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.0554 | 1.0554 | 1.0554 | 1.0554 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.0510 | 1.0510 | 1.0510 | 1.0510 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.0559 | 1.0559 | 1.0559 | 1.0559 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.2173 | 1.2173 | 1.2173 | 1.2173 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:29
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 10.50 |
Number of hours not met | 10.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 18.64 | 102580.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 355.06 | 72997.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 381.75 | 23650.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 70.25 | 5403.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.72 | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 104.05 | 11597.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 56.40 | 9863.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.72 | 1096.22 |
Natural Gas | 0.00 | 18.64 |
Additional | 0.00 | 0.00 |
Total | 128.72 | 1114.87 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 182.63 |
Space Heating | 0.00 |
Space Cooling | 169.86 |
Fans (All) | 49.78 |
Service Water Heating | 26.98 |
Receptacle Equipment | 61.58 |
Miscellaneous (All) | 524.43 |
Subtotal | 524.43 |
Natural Gas [MJ/m2] | |
Space Heating | 8.92 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 8.92 |
Subtotal | 8.92 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 34.24 |
Space Heating | 1.67 |
Space Cooling | 31.85 |
Fans (All) | 9.33 |
Service Water Heating | 5.06 |
Receptacle Equipment | 11.55 |
Miscellaneous | 6.30 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3238. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3296. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 4469. | 8760. |
LTG_SCH_BASE_LPD1 | 4391. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 3584. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4888. | 8760. |
TYPE2_EQUIP_SCH | 3911. | 8760. |
TYPE3_EQUIP_SCH | 3600. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2505. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:29
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 8722.83 | 37.17 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8746.50 | 13.50 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 7819.50 | 940.33 | 0.17 | 0.00 | 0.00 |
SMSTORE3 | 7703.83 | 1056.00 | 0.17 | 0.00 | 0.00 |
SMSTORE4 | 7885.33 | 874.50 | 0.17 | 0.00 | 0.00 |
LGSTORE2 | 8240.50 | 519.33 | 0.17 | 0.00 | 0.00 |
SMSTORE5 | 8289.67 | 470.17 | 0.17 | 0.00 | 0.00 |
SMSTORE6 | 8305.00 | 454.83 | 0.17 | 0.00 | 0.00 |
SMSTORE7 | 8313.17 | 446.67 | 0.17 | 0.00 | 0.00 |
SMSTORE8 | 8207.00 | 552.67 | 0.33 | 0.00 | 0.00 |
Min | 7703.83 | 13.50 | 0.00 | 0.00 | 0.00 |
Max | 8746.50 | 1056.00 | 0.33 | 0.00 | 0.00 |
Average | 8223.33 | 536.52 | 0.15 | 0.00 | 0.00 |
Sum | 82233.33 | 5365.17 | 1.50 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 88993.33 | 47.67 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43770.33 | 6.67 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25403.67 | 71.17 | 0.17 | 0.00 | 0.00 |
SMSTORE3 | 25403.17 | 71.67 | 0.17 | 0.00 | 0.00 |
SMSTORE4 | 25406.50 | 68.33 | 0.17 | 0.00 | 0.00 |
LGSTORE2 | 93016.00 | 194.00 | 1.00 | 0.00 | 0.00 |
SMSTORE5 | 45816.50 | 95.00 | 0.50 | 0.00 | 0.00 |
SMSTORE6 | 45817.00 | 94.50 | 0.50 | 0.00 | 0.00 |
SMSTORE7 | 45817.50 | 94.00 | 0.50 | 0.00 | 0.00 |
SMSTORE8 | 45804.00 | 107.50 | 0.50 | 0.00 | 0.00 |
Min | 25403.17 | 6.67 | 0.00 | 0.00 | 0.00 |
Max | 93016.00 | 194.00 | 1.00 | 0.00 | 0.00 |
Average | 48524.80 | 85.05 | 0.35 | 0.00 | 0.00 |
Sum | 485248.00 | 850.50 | 3.50 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 5445.00 | 3315.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 7250.83 | 1509.17 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 4552.83 | 4207.17 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 4581.50 | 4178.50 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 4538.00 | 4222.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 4268.50 | 4491.50 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 4284.00 | 4476.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 4272.33 | 4487.67 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 4286.17 | 4473.83 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 4575.00 | 4185.00 | 0.00 | 0.00 | 0.00 |
Min | 4268.50 | 1509.17 | 0.00 | 0.00 | 0.00 |
Max | 7250.83 | 4491.50 | 0.00 | 0.00 | 0.00 |
Average | 4805.42 | 3954.58 | 0.00 | 0.00 | 0.00 |
Sum | 48054.17 | 39545.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 70968.83 | 18072.17 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 36128.00 | 7649.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 18964.67 | 6510.33 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 19005.00 | 6470.00 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 18680.00 | 6795.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 59757.50 | 33453.50 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 29071.00 | 16841.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 28832.67 | 17079.33 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 28817.00 | 17095.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 31802.50 | 14109.50 | 0.00 | 0.00 | 0.00 |
Min | 18680.00 | 6470.00 | 0.00 | 0.00 | 0.00 |
Max | 70968.83 | 33453.50 | 0.00 | 0.00 | 0.00 |
Average | 34202.72 | 14407.48 | 0.00 | 0.00 | 0.00 |
Sum | 342027.17 | 144074.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:29
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:41:29
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
For: Environment
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
For: Environment
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
For: Environment
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.737799E+10 | 29665.45 | 19-JAN-09:02 | 21.33 | 20.42 | 0.126885E+10 | 1685.92 | 15-JAN-17:10 | 21.33 | 20.42 |
February | 0.700909E+10 | 33532.48 | 28-FEB-09:02 | 20.08 | 18.60 | 0.119301E+10 | 1685.92 | 20-FEB-18:49 | 20.08 | 18.60 |
March | 0.812816E+10 | 28868.32 | 07-MAR-09:02 | 23.67 | 21.83 | 0.133034E+10 | 1686.00 | 26-MAR-12:00 | 29.40 | 20.20 |
April | 0.109379E+11 | 32415.66 | 22-APR-08:62 | 22.57 | 19.97 | 0.136044E+10 | 1686.03 | 22-APR-12:39 | 29.03 | 19.99 |
May | 0.167442E+11 | 34220.30 | 07-MAY-07:02 | 24.60 | 22.15 | 0.140356E+10 | 1686.07 | 28-MAY-12:39 | 32.03 | 23.83 |
June | 0.175627E+11 | 34927.87 | 11-JUN-07:02 | 23.58 | 20.40 | 0.135669E+10 | 1686.03 | 02-JUN-12:00 | 23.58 | 20.40 |
July | 0.185873E+11 | 34095.84 | 09-JUL-07:02 | 28.48 | 25.79 | 0.141507E+10 | 1686.08 | 08-JUL-12:09 | 28.48 | 25.79 |
August | 0.194323E+11 | 36056.74 | 20-AUG-07:02 | 24.17 | 22.66 | 0.139672E+10 | 1686.06 | 12-AUG-12:39 | 24.17 | 22.66 |
September | 0.173932E+11 | 33452.66 | 22-SEP-08:62 | 23.58 | 20.80 | 0.136721E+10 | 1686.04 | 04-SEP-12:50 | 23.58 | 20.80 |
October | 0.171919E+11 | 49245.21 | 26-OCT-08:61 | 21.18 | 12.94 | 0.141099E+10 | 1686.04 | 22-OCT-12:00 | 21.18 | 12.94 |
November | 0.109187E+11 | 36559.99 | 06-NOV-09:02 | 22.47 | 19.37 | 0.135615E+10 | 1686.04 | 05-NOV-16:10 | 22.47 | 19.37 |
December | 0.885566E+10 | 31803.05 | 11-DEC-09:02 | 21.33 | 20.54 | 0.133887E+10 | 1686.03 | 10-DEC-13:30 | 21.33 | 20.54 |
Annual Sum or Average | 0.160139E+12 | 0.161979E+11 | ||||||||
Minimum of Months | 0.700909E+10 | 28868.32 | 20.08 | 12.94 | 0.119301E+10 | 1685.92 | 20.08 | 12.94 | ||
Maximum of Months | 0.194323E+11 | 49245.21 | 28.48 | 25.79 | 0.141507E+10 | 1686.08 | 32.03 | 25.79 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.370950E+10 | 16312.86 | 19-JAN-09:02 | 21.33 | 20.42 | 0.661527E+09 | 842.99 | 01-JAN-13:00 | 21.33 | 20.42 |
February | 0.379229E+10 | 20177.13 | 28-FEB-09:02 | 20.08 | 18.60 | 0.611588E+09 | 842.99 | 24-FEB-13:39 | 20.08 | 18.60 |
March | 0.450657E+10 | 18201.99 | 30-MAR-08:62 | 21.78 | 19.48 | 0.677625E+09 | 842.99 | 26-MAR-12:39 | 21.78 | 19.48 |
April | 0.619094E+10 | 19907.09 | 24-APR-08:62 | 19.50 | 19.50 | 0.679648E+09 | 842.99 | 23-APR-16:49 | 19.50 | 19.50 |
May | 0.908459E+10 | 20935.18 | 07-MAY-07:02 | 24.60 | 22.15 | 0.701892E+09 | 843.02 | 07-MAY-12:00 | 32.80 | 23.11 |
June | 0.937784E+10 | 20597.50 | 11-JUN-07:02 | 23.58 | 20.40 | 0.678429E+09 | 843.01 | 02-JUN-12:00 | 23.58 | 20.40 |
July | 0.986801E+10 | 20929.24 | 09-JUL-07:02 | 28.48 | 25.79 | 0.707576E+09 | 843.00 | 02-JUL-16:10 | 28.48 | 25.79 |
August | 0.101239E+11 | 21453.13 | 20-AUG-07:02 | 24.17 | 22.66 | 0.698388E+09 | 843.01 | 12-AUG-12:39 | 24.17 | 22.66 |
September | 0.915612E+10 | 20304.29 | 03-SEP-07:02 | 26.78 | 24.09 | 0.683639E+09 | 842.99 | 08-SEP-12:00 | 28.30 | 25.04 |
October | 0.910934E+10 | 26449.40 | 26-OCT-08:61 | 21.18 | 12.94 | 0.705219E+09 | 843.01 | 09-OCT-12:09 | 21.18 | 12.94 |
November | 0.603710E+10 | 21550.15 | 06-NOV-09:02 | 22.47 | 19.37 | 0.679741E+09 | 843.00 | 03-NOV-12:39 | 22.47 | 19.37 |
December | 0.476249E+10 | 19243.89 | 11-DEC-09:02 | 21.33 | 20.54 | 0.682155E+09 | 842.99 | 10-DEC-13:09 | 21.33 | 20.54 |
Annual Sum or Average | 0.857187E+11 | 0.816743E+10 | ||||||||
Minimum of Months | 0.370950E+10 | 16312.86 | 19.50 | 12.94 | 0.611588E+09 | 842.99 | 19.50 | 12.94 | ||
Maximum of Months | 0.101239E+11 | 26449.40 | 28.48 | 25.79 | 0.707576E+09 | 843.02 | 32.80 | 25.79 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.285010E+10 | 22431.24 | 02-JAN-08:62 | 15.50 | 14.72 | 0.381645E+09 | 842.94 | 28-JAN-13:00 | 22.00 | 13.62 |
February | 0.282278E+10 | 18610.22 | 28-FEB-08:62 | 19.50 | 18.32 | 0.360373E+09 | 842.90 | 25-FEB-13:09 | 19.50 | 18.32 |
March | 0.335348E+10 | 17817.07 | 27-MAR-07:02 | 20.18 | 18.99 | 0.411829E+09 | 842.93 | 04-MAR-13:00 | 20.18 | 18.99 |
April | 0.450280E+10 | 18797.52 | 25-APR-07:02 | 20.27 | 17.95 | 0.410061E+09 | 842.99 | 22-APR-12:39 | 20.27 | 17.95 |
May | 0.702340E+10 | 18432.27 | 12-MAY-07:01 | 23.98 | 20.89 | 0.426651E+09 | 842.97 | 06-MAY-12:00 | 23.98 | 20.89 |
June | 0.734672E+10 | 18228.06 | 14-JUN-07:01 | 26.88 | 23.48 | 0.417647E+09 | 842.98 | 03-JUN-12:00 | 26.88 | 23.48 |
July | 0.756732E+10 | 16010.55 | 19-JUL-07:01 | 28.07 | 25.39 | 0.420816E+09 | 843.00 | 01-JUL-12:30 | 28.07 | 25.39 |
August | 0.796244E+10 | 18092.38 | 31-AUG-07:01 | 25.45 | 23.81 | 0.432372E+09 | 843.01 | 12-AUG-12:39 | 25.45 | 23.81 |
September | 0.699267E+10 | 17945.65 | 23-SEP-07:01 | 23.08 | 21.03 | 0.411423E+09 | 843.00 | 09-SEP-12:09 | 23.08 | 21.03 |
October | 0.695105E+10 | 28349.97 | 17-OCT-07:02 | 15.17 | 9.88 | 0.420743E+09 | 842.99 | 21-OCT-12:09 | 28.03 | 25.07 |
November | 0.445757E+10 | 19183.48 | 06-NOV-08:62 | 20.78 | 18.75 | 0.404041E+09 | 842.95 | 25-NOV-13:00 | 20.00 | 14.21 |
December | 0.352554E+10 | 22965.59 | 17-DEC-09:02 | 19.00 | 14.29 | 0.395836E+09 | 842.95 | 16-DEC-13:09 | 19.00 | 14.29 |
Annual Sum or Average | 0.653559E+11 | 0.489344E+10 | ||||||||
Minimum of Months | 0.282278E+10 | 16010.55 | 15.17 | 9.88 | 0.360373E+09 | 842.90 | 19.00 | 13.62 | ||
Maximum of Months | 0.796244E+10 | 28349.97 | 28.07 | 25.39 | 0.432372E+09 | 843.01 | 28.07 | 25.39 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.273707E+10 | 22503.61 | 02-JAN-08:62 | 15.50 | 14.72 | 0.379708E+09 | 842.93 | 28-JAN-13:00 | 22.00 | 13.62 |
February | 0.273098E+10 | 18633.14 | 28-FEB-08:62 | 19.50 | 18.32 | 0.359238E+09 | 842.90 | 25-FEB-13:09 | 19.50 | 18.32 |
March | 0.327192E+10 | 17840.66 | 27-MAR-07:02 | 20.18 | 18.99 | 0.411059E+09 | 842.93 | 04-MAR-13:00 | 20.18 | 18.99 |
April | 0.446958E+10 | 18866.22 | 25-APR-07:02 | 20.27 | 17.95 | 0.410015E+09 | 842.99 | 22-APR-12:39 | 20.27 | 17.95 |
May | 0.705604E+10 | 18540.12 | 12-MAY-07:01 | 23.98 | 20.89 | 0.426657E+09 | 842.97 | 27-MAY-12:00 | 26.70 | 23.11 |
June | 0.738949E+10 | 18364.45 | 12-JUN-07:01 | 25.18 | 21.23 | 0.417655E+09 | 842.97 | 03-JUN-12:00 | 25.18 | 21.23 |
July | 0.762610E+10 | 16096.47 | 19-JUL-07:01 | 28.07 | 25.39 | 0.420824E+09 | 843.00 | 01-JUL-12:30 | 28.07 | 25.39 |
August | 0.801169E+10 | 18186.87 | 31-AUG-07:01 | 25.45 | 23.81 | 0.432379E+09 | 843.01 | 12-AUG-12:39 | 25.45 | 23.81 |
September | 0.704074E+10 | 18041.38 | 23-SEP-07:01 | 23.08 | 21.03 | 0.411430E+09 | 843.00 | 09-SEP-12:09 | 23.08 | 21.03 |
October | 0.698658E+10 | 28487.80 | 17-OCT-07:02 | 15.17 | 9.88 | 0.420747E+09 | 842.99 | 21-OCT-12:09 | 28.03 | 25.07 |
November | 0.441103E+10 | 19290.18 | 06-NOV-08:62 | 20.78 | 18.75 | 0.403917E+09 | 842.95 | 25-NOV-13:00 | 20.00 | 14.21 |
December | 0.344377E+10 | 23054.59 | 17-DEC-09:02 | 19.00 | 14.29 | 0.394962E+09 | 842.95 | 16-DEC-13:09 | 19.00 | 14.29 |
Annual Sum or Average | 0.651750E+11 | 0.488859E+10 | ||||||||
Minimum of Months | 0.273098E+10 | 16096.47 | 15.17 | 9.88 | 0.359238E+09 | 842.90 | 19.00 | 13.62 | ||
Maximum of Months | 0.801169E+10 | 28487.80 | 28.07 | 25.39 | 0.432379E+09 | 843.01 | 28.07 | 25.39 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.256214E+10 | 22270.02 | 02-JAN-08:62 | 15.50 | 14.72 | 0.377014E+09 | 842.93 | 28-JAN-13:00 | 22.00 | 13.62 |
February | 0.256536E+10 | 18375.23 | 28-FEB-08:62 | 19.50 | 18.32 | 0.357438E+09 | 842.90 | 25-FEB-13:09 | 19.50 | 18.32 |
March | 0.309156E+10 | 17571.29 | 27-MAR-07:02 | 20.18 | 18.99 | 0.409545E+09 | 842.93 | 04-MAR-13:09 | 20.18 | 18.99 |
April | 0.429296E+10 | 18616.63 | 25-APR-07:02 | 20.27 | 17.95 | 0.409866E+09 | 842.99 | 22-APR-12:39 | 20.27 | 17.95 |
May | 0.691510E+10 | 18306.99 | 12-MAY-07:01 | 23.98 | 20.89 | 0.426617E+09 | 842.97 | 27-MAY-12:00 | 26.70 | 23.11 |
June | 0.725771E+10 | 18219.81 | 12-JUN-07:01 | 25.18 | 21.23 | 0.417618E+09 | 842.97 | 03-JUN-12:00 | 25.18 | 21.23 |
July | 0.750950E+10 | 15921.70 | 19-JUL-07:01 | 28.07 | 25.39 | 0.420794E+09 | 843.00 | 01-JUL-12:39 | 28.07 | 25.39 |
August | 0.788666E+10 | 17969.05 | 31-AUG-07:01 | 25.45 | 23.81 | 0.432346E+09 | 843.00 | 12-AUG-12:39 | 25.45 | 23.81 |
September | 0.692153E+10 | 17812.53 | 23-SEP-07:01 | 23.08 | 21.03 | 0.411398E+09 | 842.99 | 09-SEP-12:09 | 23.08 | 21.03 |
October | 0.685601E+10 | 28223.96 | 17-OCT-07:02 | 15.17 | 9.88 | 0.420690E+09 | 842.98 | 21-OCT-12:09 | 28.03 | 25.07 |
November | 0.424576E+10 | 19073.59 | 06-NOV-08:62 | 20.78 | 18.75 | 0.403582E+09 | 842.95 | 25-NOV-13:50 | 20.08 | 14.24 |
December | 0.327510E+10 | 22805.65 | 17-DEC-09:02 | 19.00 | 14.29 | 0.393550E+09 | 842.95 | 16-DEC-13:09 | 19.00 | 14.29 |
Annual Sum or Average | 0.633794E+11 | 0.488046E+10 | ||||||||
Minimum of Months | 0.256214E+10 | 15921.70 | 15.17 | 9.88 | 0.357438E+09 | 842.90 | 19.00 | 13.62 | ||
Maximum of Months | 0.788666E+10 | 28223.96 | 28.07 | 25.39 | 0.432346E+09 | 843.00 | 28.07 | 25.39 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.416079E+10 | 37347.82 | 01-JAN-10:02 | 20.33 | 16.41 | 0.127859E+10 | 2247.89 | 28-JAN-15:39 | 23.00 | 14.05 |
February | 0.415921E+10 | 31723.25 | 28-FEB-09:02 | 20.08 | 18.60 | 0.121441E+10 | 2247.80 | 11-FEB-15:00 | 20.08 | 18.60 |
March | 0.500952E+10 | 26729.76 | 07-MAR-09:02 | 23.67 | 21.83 | 0.139619E+10 | 2247.88 | 04-MAR-15:00 | 23.67 | 21.83 |
April | 0.706724E+10 | 30788.49 | 22-APR-08:62 | 22.57 | 19.97 | 0.140733E+10 | 2247.99 | 15-APR-14:09 | 22.57 | 19.97 |
May | 0.117843E+11 | 31874.54 | 12-MAY-08:62 | 24.78 | 21.42 | 0.145944E+10 | 2248.05 | 06-MAY-14:20 | 24.78 | 21.42 |
June | 0.124577E+11 | 31692.15 | 14-JUN-08:61 | 28.07 | 23.96 | 0.143166E+10 | 2248.03 | 10-JUN-14:20 | 28.07 | 23.96 |
July | 0.128741E+11 | 28869.02 | 18-JUL-08:61 | 28.58 | 24.22 | 0.144044E+10 | 2248.02 | 15-JUL-14:20 | 28.58 | 24.22 |
August | 0.136262E+11 | 32058.41 | 31-AUG-08:61 | 27.88 | 24.10 | 0.148188E+10 | 2248.04 | 26-AUG-14:20 | 27.88 | 24.10 |
September | 0.118550E+11 | 30881.35 | 22-SEP-08:62 | 23.58 | 20.80 | 0.141214E+10 | 2247.81 | 16-SEP-14:09 | 23.58 | 20.80 |
October | 0.117594E+11 | 45252.38 | 26-OCT-08:61 | 21.18 | 12.94 | 0.143613E+10 | 2248.01 | 21-OCT-14:09 | 21.18 | 12.94 |
November | 0.696476E+10 | 33038.24 | 05-NOV-09:02 | 20.78 | 17.18 | 0.137375E+10 | 2248.04 | 04-NOV-14:50 | 20.78 | 17.18 |
December | 0.536211E+10 | 40960.49 | 17-DEC-10:02 | 19.17 | 14.29 | 0.134149E+10 | 2248.03 | 09-DEC-15:30 | 19.17 | 14.29 |
Annual Sum or Average | 0.107080E+12 | 0.166734E+11 | ||||||||
Minimum of Months | 0.415921E+10 | 26729.76 | 19.17 | 12.94 | 0.121441E+10 | 2247.80 | 19.17 | 12.94 | ||
Maximum of Months | 0.136262E+11 | 45252.38 | 28.58 | 24.22 | 0.148188E+10 | 2248.05 | 28.58 | 24.22 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.200929E+10 | 19439.59 | 01-JAN-10:02 | 20.33 | 16.41 | 0.636429E+09 | 1123.91 | 28-JAN-15:39 | 23.00 | 14.05 |
February | 0.203830E+10 | 16042.10 | 28-FEB-09:02 | 20.08 | 18.60 | 0.605151E+09 | 1123.87 | 11-FEB-15:00 | 20.08 | 18.60 |
March | 0.248243E+10 | 13913.44 | 07-MAR-09:02 | 23.67 | 21.83 | 0.696284E+09 | 1123.91 | 04-MAR-15:00 | 23.67 | 21.83 |
April | 0.360806E+10 | 16034.87 | 22-APR-08:62 | 22.57 | 19.97 | 0.703546E+09 | 1123.97 | 15-APR-14:09 | 22.57 | 19.97 |
May | 0.615474E+10 | 16593.89 | 12-MAY-08:62 | 24.78 | 21.42 | 0.729663E+09 | 1123.99 | 06-MAY-14:20 | 24.78 | 21.42 |
June | 0.651089E+10 | 16526.14 | 14-JUN-08:61 | 28.07 | 23.96 | 0.715766E+09 | 1123.98 | 10-JUN-14:30 | 28.07 | 23.96 |
July | 0.672869E+10 | 15059.68 | 18-JUL-08:61 | 28.58 | 24.22 | 0.720162E+09 | 1123.97 | 15-JUL-14:20 | 28.58 | 24.22 |
August | 0.711348E+10 | 16720.51 | 31-AUG-08:61 | 27.88 | 24.10 | 0.740884E+09 | 1124.01 | 26-AUG-14:30 | 27.88 | 24.10 |
September | 0.617022E+10 | 16077.44 | 22-SEP-08:62 | 23.58 | 20.80 | 0.706011E+09 | 1123.99 | 23-SEP-14:00 | 28.80 | 24.09 |
October | 0.609674E+10 | 23593.04 | 26-OCT-08:61 | 21.18 | 12.94 | 0.718012E+09 | 1123.97 | 21-OCT-14:09 | 21.18 | 12.94 |
November | 0.352866E+10 | 17060.82 | 06-NOV-09:02 | 22.47 | 19.37 | 0.686530E+09 | 1123.99 | 04-NOV-14:39 | 22.47 | 19.37 |
December | 0.265591E+10 | 21349.68 | 17-DEC-10:02 | 19.17 | 14.29 | 0.669298E+09 | 1123.97 | 16-DEC-15:00 | 19.17 | 14.29 |
Annual Sum or Average | 0.550974E+11 | 0.832774E+10 | ||||||||
Minimum of Months | 0.200929E+10 | 13913.44 | 19.17 | 12.94 | 0.605151E+09 | 1123.87 | 19.17 | 12.94 | ||
Maximum of Months | 0.711348E+10 | 23593.04 | 28.58 | 24.22 | 0.740884E+09 | 1124.01 | 28.80 | 24.22 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.194925E+10 | 19307.71 | 01-JAN-10:02 | 20.33 | 16.41 | 0.634765E+09 | 1123.91 | 28-JAN-15:39 | 23.00 | 14.05 |
February | 0.198277E+10 | 15251.18 | 28-FEB-09:02 | 20.08 | 18.60 | 0.603850E+09 | 1123.87 | 11-FEB-15:00 | 20.08 | 18.60 |
March | 0.242119E+10 | 13778.94 | 07-MAR-09:02 | 23.67 | 21.83 | 0.695163E+09 | 1123.91 | 04-MAR-15:00 | 23.67 | 21.83 |
April | 0.354847E+10 | 15926.41 | 22-APR-08:62 | 22.57 | 19.97 | 0.703422E+09 | 1123.97 | 15-APR-14:09 | 22.57 | 19.97 |
May | 0.610334E+10 | 16491.10 | 12-MAY-08:62 | 24.78 | 21.42 | 0.729647E+09 | 1123.99 | 06-MAY-14:20 | 24.78 | 21.42 |
June | 0.646246E+10 | 16420.07 | 14-JUN-08:61 | 28.07 | 23.96 | 0.715751E+09 | 1123.98 | 10-JUN-14:30 | 28.07 | 23.96 |
July | 0.668528E+10 | 14962.14 | 18-JUL-08:61 | 28.58 | 24.22 | 0.720150E+09 | 1123.97 | 15-JUL-14:20 | 28.58 | 24.22 |
August | 0.707005E+10 | 16613.03 | 31-AUG-08:61 | 27.88 | 24.10 | 0.740874E+09 | 1124.01 | 26-AUG-14:30 | 27.88 | 24.10 |
September | 0.612840E+10 | 15977.29 | 22-SEP-08:62 | 23.58 | 20.80 | 0.705999E+09 | 1123.99 | 23-SEP-14:00 | 28.80 | 24.09 |
October | 0.604681E+10 | 23466.54 | 26-OCT-08:61 | 21.18 | 12.94 | 0.717977E+09 | 1123.97 | 21-OCT-14:09 | 21.18 | 12.94 |
November | 0.347243E+10 | 16951.14 | 06-NOV-09:02 | 22.47 | 19.37 | 0.686251E+09 | 1123.99 | 04-NOV-14:30 | 22.47 | 19.37 |
December | 0.259836E+10 | 21225.06 | 17-DEC-10:02 | 19.17 | 14.29 | 0.668173E+09 | 1123.97 | 16-DEC-15:00 | 19.17 | 14.29 |
Annual Sum or Average | 0.544688E+11 | 0.832202E+10 | ||||||||
Minimum of Months | 0.194925E+10 | 13778.94 | 19.17 | 12.94 | 0.603850E+09 | 1123.87 | 19.17 | 12.94 | ||
Maximum of Months | 0.707005E+10 | 23466.54 | 28.58 | 24.22 | 0.740874E+09 | 1124.01 | 28.80 | 24.22 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.182963E+10 | 19236.54 | 01-JAN-10:02 | 20.33 | 16.41 | 0.631597E+09 | 1123.91 | 28-JAN-15:39 | 23.00 | 14.05 |
February | 0.187184E+10 | 12965.68 | 28-FEB-09:02 | 20.08 | 18.60 | 0.601187E+09 | 1123.87 | 11-FEB-15:00 | 20.08 | 18.60 |
March | 0.229833E+10 | 13650.18 | 07-MAR-09:02 | 23.67 | 21.83 | 0.692766E+09 | 1123.91 | 04-MAR-15:00 | 23.67 | 21.83 |
April | 0.343716E+10 | 15402.28 | 23-APR-09:02 | 24.68 | 20.67 | 0.703012E+09 | 1123.98 | 15-APR-14:09 | 24.68 | 20.67 |
May | 0.607881E+10 | 16517.41 | 12-MAY-08:62 | 24.78 | 21.42 | 0.729625E+09 | 1123.99 | 06-MAY-14:20 | 24.78 | 21.42 |
June | 0.646362E+10 | 16481.96 | 14-JUN-08:61 | 28.07 | 23.96 | 0.715738E+09 | 1124.01 | 03-JUN-14:09 | 28.07 | 23.96 |
July | 0.671636E+10 | 15035.86 | 07-JUL-08:61 | 29.08 | 24.94 | 0.720149E+09 | 1123.96 | 15-JUL-14:20 | 28.70 | 24.54 |
August | 0.711569E+10 | 16710.39 | 31-AUG-08:61 | 27.88 | 24.10 | 0.740876E+09 | 1124.00 | 26-AUG-14:30 | 27.88 | 24.10 |
September | 0.615166E+10 | 16019.96 | 22-SEP-08:62 | 23.58 | 20.80 | 0.705998E+09 | 1123.98 | 23-SEP-14:00 | 28.80 | 24.09 |
October | 0.603852E+10 | 23548.95 | 26-OCT-08:61 | 21.18 | 12.94 | 0.717902E+09 | 1123.98 | 21-OCT-14:09 | 21.18 | 12.94 |
November | 0.338507E+10 | 16935.26 | 06-NOV-09:02 | 22.47 | 19.37 | 0.685642E+09 | 1123.91 | 25-NOV-15:09 | 19.80 | 14.72 |
December | 0.248903E+10 | 21220.53 | 17-DEC-10:02 | 19.17 | 14.29 | 0.665768E+09 | 1123.97 | 16-DEC-15:00 | 19.17 | 14.29 |
Annual Sum or Average | 0.538757E+11 | 0.831026E+10 | ||||||||
Minimum of Months | 0.182963E+10 | 12965.68 | 19.17 | 12.94 | 0.601187E+09 | 1123.87 | 19.17 | 12.94 | ||
Maximum of Months | 0.711569E+10 | 23548.95 | 29.08 | 24.94 | 0.740876E+09 | 1124.01 | 28.80 | 24.54 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.168481E+10 | 17678.86 | 01-JAN-10:02 | 20.33 | 16.41 | 0.629763E+09 | 1123.91 | 28-JAN-15:39 | 23.00 | 14.05 |
February | 0.179147E+10 | 7225.39 | 28-FEB-09:02 | 20.08 | 18.60 | 0.597943E+09 | 1123.87 | 11-FEB-15:00 | 20.08 | 18.60 |
March | 0.230167E+10 | 9540.86 | 07-MAR-09:02 | 23.67 | 21.83 | 0.689922E+09 | 1123.91 | 04-MAR-15:00 | 23.67 | 21.83 |
April | 0.363474E+10 | 17605.60 | 23-APR-09:02 | 24.68 | 20.67 | 0.702399E+09 | 1123.96 | 22-APR-14:00 | 24.68 | 20.67 |
May | 0.681450E+10 | 17812.43 | 12-MAY-08:62 | 24.78 | 21.42 | 0.729690E+09 | 1124.01 | 27-MAY-14:00 | 32.20 | 25.37 |
June | 0.738833E+10 | 18724.07 | 11-JUN-09:01 | 28.07 | 20.81 | 0.715840E+09 | 1123.95 | 03-JUN-14:00 | 28.07 | 20.81 |
July | 0.777545E+10 | 16787.30 | 07-JUL-08:61 | 29.08 | 24.94 | 0.720311E+09 | 1123.99 | 29-JUL-14:00 | 27.20 | 25.59 |
August | 0.829022E+10 | 19600.27 | 31-AUG-08:61 | 27.88 | 24.10 | 0.741024E+09 | 1124.01 | 26-AUG-14:50 | 27.88 | 24.10 |
September | 0.706821E+10 | 17706.40 | 22-SEP-08:62 | 23.58 | 20.80 | 0.706157E+09 | 1124.02 | 23-SEP-14:20 | 29.93 | 24.10 |
October | 0.683449E+10 | 27221.50 | 26-OCT-08:61 | 21.18 | 12.94 | 0.717821E+09 | 1123.98 | 21-OCT-14:00 | 21.18 | 12.94 |
November | 0.356200E+10 | 19188.52 | 06-NOV-09:02 | 22.47 | 19.37 | 0.685081E+09 | 1123.89 | 25-NOV-15:09 | 19.80 | 14.72 |
December | 0.240653E+10 | 24245.06 | 17-DEC-10:02 | 19.17 | 14.29 | 0.663004E+09 | 1124.00 | 16-DEC-15:30 | 19.17 | 14.29 |
Annual Sum or Average | 0.595524E+11 | 0.829895E+10 | ||||||||
Minimum of Months | 0.168481E+10 | 7225.39 | 19.17 | 12.94 | 0.597943E+09 | 1123.87 | 19.17 | 12.94 | ||
Maximum of Months | 0.829022E+10 | 27221.50 | 29.08 | 24.94 | 0.741024E+09 | 1124.02 | 32.20 | 25.59 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.113151E+09 | 50218.37 | 10-JAN-09:01 | 5.33 |
February | 0.147163E+09 | 51376.94 | 06-FEB-09:01 | 7.47 |
March | 0.206885E+09 | 50458.22 | 11-MAR-09:01 | 6.52 |
April | 87141884.04 | 2469.50 | 29-APR-08:05 | 25.78 |
May | 0.101471E+09 | 3378.85 | 27-MAY-08:06 | 27.98 |
June | 98208058.50 | 3863.25 | 16-JUN-08:06 | 29.08 |
July | 92648967.36 | 3796.48 | 19-JUL-08:06 | 29.68 |
August | 96491406.29 | 3583.25 | 22-AUG-08:06 | 29.00 |
September | 92237324.67 | 3625.17 | 02-SEP-08:06 | 28.58 |
October | 89021379.50 | 2666.78 | 14-OCT-08:06 | 27.17 |
November | 84399939.35 | 1637.91 | 01-NOV-08:05 | 23.90 |
December | 0.123736E+09 | 50896.06 | 21-DEC-09:01 | 6.33 |
Annual Sum or Average | 0.133255E+10 | |||
Minimum of Months | 84399939.35 | 1637.91 | 5.33 | |
Maximum of Months | 0.206885E+09 | 51376.94 | 29.68 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 49244396.17 | 936.26 | 05-JAN-09:01 | 6.50 |
February | 50747555.82 | 13329.97 | 05-FEB-09:02 | -0.3 |
March | 71594759.92 | 3648.77 | 12-MAR-08:62 | 9.18 |
April | 47206014.34 | 1271.29 | 29-APR-08:05 | 25.78 |
May | 52016610.60 | 1830.04 | 16-MAY-08:04 | 27.98 |
June | 50225642.44 | 2265.19 | 17-JUN-08:05 | 30.00 |
July | 46373027.53 | 2203.85 | 08-JUL-08:05 | 29.68 |
August | 49054202.63 | 2027.35 | 22-AUG-08:05 | 29.00 |
September | 47672477.16 | 1682.73 | 08-SEP-08:04 | 27.47 |
October | 47142657.09 | 1549.01 | 14-OCT-08:05 | 27.17 |
November | 44301042.25 | 962.21 | 11-NOV-08:05 | 20.73 |
December | 52961627.69 | 13481.13 | 21-DEC-09:01 | 6.33 |
Annual Sum or Average | 0.608540E+09 | |||
Minimum of Months | 44301042.25 | 936.26 | -0.3 | |
Maximum of Months | 71594759.92 | 13481.13 | 30.00 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 55053211.03 | 2428.03 | 22-JAN-18:00 | 10.00 |
February | 65181969.11 | 21824.90 | 05-FEB-09:02 | -0.3 |
March | 82142650.13 | 10865.40 | 12-MAR-08:62 | 9.18 |
April | 58406537.70 | 1717.36 | 22-APR-17:03 | 30.13 |
May | 0.129173E+09 | 2528.21 | 28-MAY-16:02 | 33.43 |
June | 0.142894E+09 | 2348.22 | 25-JUN-16:02 | 32.70 |
July | 0.140632E+09 | 2838.06 | 22-JUL-17:02 | 34.63 |
August | 0.126783E+09 | 2567.01 | 27-AUG-16:02 | 33.67 |
September | 99488961.21 | 3276.02 | 09-SEP-17:02 | 36.18 |
October | 90013540.82 | 1849.30 | 08-OCT-16:02 | 30.67 |
November | 52177497.60 | 948.62 | 11-NOV-09:05 | 24.40 |
December | 57784861.10 | 3205.92 | 21-DEC-08:65 | 3.50 |
Annual Sum or Average | 0.109973E+10 | |||
Minimum of Months | 52177497.60 | 948.62 | -0.3 | |
Maximum of Months | 0.142894E+09 | 21824.90 | 36.18 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 57527054.62 | 4233.33 | 05-JAN-08:57 | 6.00 |
February | 70080764.04 | 24874.62 | 05-FEB-09:02 | -0.3 |
March | 88057748.27 | 13668.21 | 12-MAR-08:62 | 9.18 |
April | 58527614.43 | 1718.67 | 22-APR-17:03 | 30.13 |
May | 0.128422E+09 | 2528.49 | 28-MAY-16:02 | 33.43 |
June | 0.141047E+09 | 2347.78 | 25-JUN-16:02 | 32.70 |
July | 0.136013E+09 | 2838.00 | 22-JUL-17:02 | 34.63 |
August | 0.122679E+09 | 2565.82 | 27-AUG-16:02 | 33.67 |
September | 97011742.30 | 3276.51 | 09-SEP-17:02 | 36.18 |
October | 87608166.01 | 1848.03 | 08-OCT-16:02 | 30.67 |
November | 52291135.04 | 948.00 | 11-NOV-09:05 | 24.40 |
December | 60146856.08 | 3998.86 | 21-DEC-08:65 | 3.50 |
Annual Sum or Average | 0.109941E+10 | |||
Minimum of Months | 52291135.04 | 948.00 | -0.3 | |
Maximum of Months | 0.141047E+09 | 24874.62 | 36.18 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 60225969.71 | 4211.22 | 10-JAN-08:65 | 4.17 |
February | 78318638.02 | 24764.13 | 05-FEB-09:02 | -0.3 |
March | 96145946.57 | 16296.42 | 12-MAR-08:62 | 9.18 |
April | 58715231.98 | 1724.38 | 22-APR-17:03 | 30.13 |
May | 0.130252E+09 | 2531.67 | 28-MAY-16:02 | 33.43 |
June | 0.143562E+09 | 2350.75 | 25-JUN-16:02 | 32.70 |
July | 0.141554E+09 | 2841.90 | 22-JUL-17:02 | 34.63 |
August | 0.127974E+09 | 2568.55 | 27-AUG-16:02 | 33.67 |
September | 98841253.22 | 3279.46 | 09-SEP-17:02 | 36.18 |
October | 90085933.44 | 1850.23 | 08-OCT-16:02 | 30.67 |
November | 52411371.47 | 922.28 | 05-NOV-16:03 | 27.02 |
December | 63998012.18 | 5034.74 | 21-DEC-08:65 | 3.50 |
Annual Sum or Average | 0.114208E+10 | |||
Minimum of Months | 52411371.47 | 922.28 | -0.3 | |
Maximum of Months | 0.143562E+09 | 24764.13 | 36.18 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.119074E+09 | 47000.99 | 10-JAN-09:01 | 5.33 |
February | 0.150151E+09 | 48187.59 | 06-FEB-09:01 | 7.47 |
March | 0.182271E+09 | 49705.71 | 12-MAR-09:01 | 11.47 |
April | 0.107354E+09 | 3461.13 | 22-APR-17:03 | 30.13 |
May | 0.167085E+09 | 5076.65 | 28-MAY-16:02 | 33.43 |
June | 0.167104E+09 | 4712.46 | 25-JUN-16:02 | 32.70 |
July | 0.176178E+09 | 5693.26 | 22-JUL-17:02 | 34.63 |
August | 0.146031E+09 | 5154.22 | 27-AUG-16:02 | 33.67 |
September | 0.158114E+09 | 6550.72 | 09-SEP-17:02 | 36.18 |
October | 0.128320E+09 | 3703.00 | 08-OCT-16:02 | 30.67 |
November | 88196757.38 | 1863.84 | 05-NOV-16:03 | 27.02 |
December | 0.120658E+09 | 47529.38 | 21-DEC-09:01 | 6.33 |
Annual Sum or Average | 0.171054E+10 | |||
Minimum of Months | 88196757.38 | 1863.84 | 5.33 | |
Maximum of Months | 0.182271E+09 | 49705.71 | 36.18 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 73826574.08 | 24644.54 | 10-JAN-09:01 | 5.33 |
February | 96441110.85 | 25234.26 | 06-FEB-09:01 | 7.47 |
March | 0.110219E+09 | 25971.05 | 12-MAR-09:01 | 11.47 |
April | 58111312.68 | 1747.80 | 22-APR-17:03 | 30.13 |
May | 86475878.58 | 2544.86 | 28-MAY-16:02 | 33.43 |
June | 86623099.91 | 2363.56 | 25-JUN-16:02 | 32.70 |
July | 91784442.05 | 2861.47 | 22-JUL-17:02 | 34.63 |
August | 75421541.23 | 2582.16 | 27-AUG-16:02 | 33.67 |
September | 82923443.66 | 3291.95 | 09-SEP-17:02 | 36.18 |
October | 68013426.88 | 1860.95 | 08-OCT-16:02 | 30.67 |
November | 48569255.91 | 1001.27 | 11-NOV-10:05 | 24.68 |
December | 76006762.74 | 24901.26 | 21-DEC-09:01 | 6.33 |
Annual Sum or Average | 0.954416E+09 | |||
Minimum of Months | 48569255.91 | 1001.27 | 5.33 | |
Maximum of Months | 0.110219E+09 | 25971.05 | 36.18 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 77788214.95 | 24567.77 | 10-JAN-09:01 | 5.33 |
February | 0.102111E+09 | 25159.32 | 06-FEB-09:01 | 7.47 |
March | 0.112760E+09 | 25897.55 | 12-MAR-09:01 | 11.47 |
April | 57986144.42 | 1749.35 | 22-APR-17:03 | 30.13 |
May | 86802107.79 | 2545.94 | 28-MAY-16:02 | 33.43 |
June | 86920879.85 | 2364.57 | 25-JUN-16:02 | 32.70 |
July | 92038372.08 | 2862.63 | 22-JUL-17:02 | 34.63 |
August | 75743064.22 | 2583.08 | 27-AUG-16:02 | 33.67 |
September | 82979861.82 | 3292.72 | 09-SEP-17:02 | 36.18 |
October | 68104797.18 | 1861.86 | 08-OCT-16:02 | 30.67 |
November | 48471371.70 | 988.95 | 11-NOV-10:05 | 24.68 |
December | 79986529.69 | 24821.49 | 21-DEC-09:01 | 6.33 |
Annual Sum or Average | 0.971692E+09 | |||
Minimum of Months | 48471371.70 | 988.95 | 5.33 | |
Maximum of Months | 0.112760E+09 | 25897.55 | 36.18 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 97063419.03 | 24742.48 | 10-JAN-09:01 | 5.33 |
February | 0.123131E+09 | 25355.75 | 06-FEB-09:01 | 7.47 |
March | 0.130489E+09 | 26083.28 | 12-MAR-09:01 | 11.47 |
April | 58270817.72 | 1751.79 | 22-APR-17:03 | 30.13 |
May | 87772090.15 | 2546.69 | 28-MAY-16:02 | 33.43 |
June | 87077218.39 | 2364.71 | 25-JUN-16:02 | 32.70 |
July | 91710223.78 | 2861.43 | 22-JUL-17:02 | 34.63 |
August | 75639637.77 | 2581.70 | 27-AUG-16:02 | 33.67 |
September | 82648391.83 | 3292.23 | 09-SEP-17:02 | 36.18 |
October | 68419910.82 | 1860.81 | 08-OCT-16:02 | 30.67 |
November | 48853499.29 | 960.43 | 11-NOV-10:05 | 24.68 |
December | 96456826.08 | 25000.01 | 21-DEC-09:01 | 6.33 |
Annual Sum or Average | 0.104753E+10 | |||
Minimum of Months | 48853499.29 | 960.43 | 5.33 | |
Maximum of Months | 0.130489E+09 | 26083.28 | 36.18 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.185700E+09 | 28862.50 | 11-JAN-09:02 | 11.50 |
February | 0.212624E+09 | 31129.26 | 05-FEB-09:02 | -0.3 |
March | 0.228029E+09 | 29701.48 | 13-MAR-08:61 | 10.55 |
April | 62789475.00 | 1749.71 | 22-APR-17:03 | 30.13 |
May | 89930763.94 | 2534.00 | 28-MAY-16:02 | 33.43 |
June | 89123151.74 | 2348.42 | 25-JUN-16:02 | 32.70 |
July | 88608806.73 | 2826.43 | 22-JUL-17:02 | 34.63 |
August | 73428179.78 | 2550.48 | 27-AUG-16:02 | 33.67 |
September | 83264602.81 | 3268.90 | 09-SEP-17:02 | 36.18 |
October | 72132981.95 | 1838.03 | 08-OCT-16:02 | 30.67 |
November | 52810765.69 | 1122.58 | 11-NOV-10:05 | 24.68 |
December | 0.174951E+09 | 28763.06 | 21-DEC-09:01 | 6.33 |
Annual Sum or Average | 0.141339E+10 | |||
Minimum of Months | 52810765.69 | 1122.58 | -0.3 | |
Maximum of Months | 0.228029E+09 | 31129.26 | 36.18 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.750231E+10 | 4589.20 | 01-JAN-10:09 | 0.223514E+10 | 1348.26 | 01-JAN-10:09 |
February | 0.678234E+10 | 4589.20 | 01-FEB-10:09 | 0.202238E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.751014E+10 | 4589.20 | 01-MAR-10:09 | 0.224215E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.727015E+10 | 4589.20 | 01-APR-09:09 | 0.216638E+10 | 1348.26 | 01-APR-09:09 |
May | 0.750231E+10 | 4589.20 | 01-MAY-09:09 | 0.223514E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.727015E+10 | 4589.20 | 01-JUN-09:09 | 0.217123E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.751014E+10 | 4589.20 | 01-JUL-09:09 | 0.223729E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.750231E+10 | 4589.20 | 01-AUG-09:09 | 0.223756E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.727797E+10 | 4589.20 | 01-SEP-09:09 | 0.217096E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.750231E+10 | 4589.20 | 01-OCT-09:09 | 0.223514E+10 | 1348.26 | 01-OCT-09:09 |
November | 0.724667E+10 | 4589.20 | 01-NOV-09:09 | 0.215964E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.751797E+10 | 4589.20 | 01-DEC-10:09 | 0.224431E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.883948E+11 | 0.263573E+11 | ||||
Minimum of Months | 0.678234E+10 | 4589.20 | 0.202238E+10 | 1348.26 | ||
Maximum of Months | 0.751797E+10 | 4589.20 | 0.224431E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.451294E+10 | 2760.58 | 01-JAN-10:09 | 0.111757E+10 | 674.13 | 01-JAN-10:09 |
February | 0.407985E+10 | 2760.58 | 01-FEB-10:09 | 0.101119E+10 | 674.13 | 01-FEB-10:09 |
March | 0.451765E+10 | 2760.58 | 01-MAR-10:09 | 0.112107E+10 | 674.13 | 01-MAR-10:09 |
April | 0.437329E+10 | 2760.58 | 01-APR-09:09 | 0.108319E+10 | 674.13 | 01-APR-09:09 |
May | 0.451294E+10 | 2760.58 | 01-MAY-09:09 | 0.111757E+10 | 674.13 | 01-MAY-09:09 |
June | 0.437329E+10 | 2760.58 | 01-JUN-09:09 | 0.108562E+10 | 674.13 | 01-JUN-09:09 |
July | 0.451765E+10 | 2760.58 | 01-JUL-09:09 | 0.111865E+10 | 674.13 | 01-JUL-09:09 |
August | 0.451294E+10 | 2760.58 | 01-AUG-09:09 | 0.111878E+10 | 674.13 | 01-AUG-09:09 |
September | 0.437799E+10 | 2760.58 | 01-SEP-09:09 | 0.108548E+10 | 674.13 | 01-SEP-09:09 |
October | 0.451294E+10 | 2760.58 | 01-OCT-09:09 | 0.111757E+10 | 674.13 | 01-OCT-09:09 |
November | 0.435916E+10 | 2760.58 | 01-NOV-09:09 | 0.107982E+10 | 674.13 | 01-NOV-09:09 |
December | 0.452236E+10 | 2760.58 | 01-DEC-10:09 | 0.112215E+10 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.531730E+11 | 0.131787E+11 | ||||
Minimum of Months | 0.407985E+10 | 2760.58 | 0.101119E+10 | 674.13 | ||
Maximum of Months | 0.452236E+10 | 2760.58 | 0.112215E+10 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.326451E+10 | 2510.11 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.295632E+10 | 2510.11 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.333300E+10 | 2510.11 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.316749E+10 | 2510.11 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.329875E+10 | 2510.11 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.321885E+10 | 2510.11 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.324739E+10 | 2510.11 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.333300E+10 | 2510.11 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.316749E+10 | 2510.11 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.326451E+10 | 2510.11 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.316749E+10 | 2510.11 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.324739E+10 | 2510.11 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.386662E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.295632E+10 | 2510.11 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.333300E+10 | 2510.11 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.326451E+10 | 2510.11 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.295632E+10 | 2510.11 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.333300E+10 | 2510.11 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.316749E+10 | 2510.11 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.329875E+10 | 2510.11 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.321885E+10 | 2510.11 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.324739E+10 | 2510.11 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.333300E+10 | 2510.11 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.316749E+10 | 2510.11 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.326451E+10 | 2510.11 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.316749E+10 | 2510.11 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.324739E+10 | 2510.11 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.386662E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.295632E+10 | 2510.11 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.333300E+10 | 2510.11 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.326451E+10 | 2510.11 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.295632E+10 | 2510.11 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.333300E+10 | 2510.11 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.316749E+10 | 2510.11 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.329875E+10 | 2510.11 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.321885E+10 | 2510.11 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.324739E+10 | 2510.11 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.333300E+10 | 2510.11 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.316749E+10 | 2510.11 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.326451E+10 | 2510.11 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.316749E+10 | 2510.11 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.324739E+10 | 2510.11 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.386662E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.295632E+10 | 2510.11 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.333300E+10 | 2510.11 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.343207E+10 | 2872.47 | 01-JAN-11:09 | 0.162546E+10 | 1348.26 | 01-JAN-11:09 |
February | 0.310878E+10 | 2872.47 | 01-FEB-10:09 | 0.147229E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.351044E+10 | 2872.47 | 01-MAR-10:09 | 0.166213E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.333084E+10 | 2872.47 | 01-APR-09:09 | 0.157746E+10 | 1348.26 | 01-APR-09:09 |
May | 0.347125E+10 | 2872.47 | 01-MAY-09:09 | 0.164379E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.338962E+10 | 2872.47 | 01-JUN-09:09 | 0.160496E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.341247E+10 | 2872.47 | 01-JUL-09:09 | 0.161629E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.351044E+10 | 2872.47 | 01-AUG-09:09 | 0.166213E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.333084E+10 | 2872.47 | 01-SEP-09:09 | 0.157746E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.343207E+10 | 2872.47 | 01-OCT-10:09 | 0.162546E+10 | 1348.26 | 01-OCT-10:09 |
November | 0.333084E+10 | 2872.47 | 01-NOV-09:09 | 0.157746E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.341247E+10 | 2872.47 | 01-DEC-10:09 | 0.161629E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.406721E+11 | 0.192612E+11 | ||||
Minimum of Months | 0.310878E+10 | 2872.47 | 0.147229E+10 | 1348.26 | ||
Maximum of Months | 0.351044E+10 | 2872.47 | 0.166213E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.176168E+10 | 1474.43 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.159573E+10 | 1474.43 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.180191E+10 | 1474.43 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.170972E+10 | 1474.43 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.178179E+10 | 1474.43 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.173989E+10 | 1474.43 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.175162E+10 | 1474.43 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.180191E+10 | 1474.43 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.170972E+10 | 1474.43 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.176168E+10 | 1474.43 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.170972E+10 | 1474.43 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.175162E+10 | 1474.43 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.208770E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.159573E+10 | 1474.43 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.180191E+10 | 1474.43 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.176168E+10 | 1474.43 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.159573E+10 | 1474.43 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.180191E+10 | 1474.43 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.170972E+10 | 1474.43 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.178179E+10 | 1474.43 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.173989E+10 | 1474.43 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.175162E+10 | 1474.43 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.180191E+10 | 1474.43 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.170972E+10 | 1474.43 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.176168E+10 | 1474.43 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.170972E+10 | 1474.43 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.175162E+10 | 1474.43 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.208770E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.159573E+10 | 1474.43 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.180191E+10 | 1474.43 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.176168E+10 | 1474.43 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.159573E+10 | 1474.43 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.180191E+10 | 1474.43 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.170972E+10 | 1474.43 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.178179E+10 | 1474.43 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.173989E+10 | 1474.43 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.175162E+10 | 1474.43 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.180191E+10 | 1474.43 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.170972E+10 | 1474.43 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.176168E+10 | 1474.43 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.170972E+10 | 1474.43 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.175162E+10 | 1474.43 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.208770E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.159573E+10 | 1474.43 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.180191E+10 | 1474.43 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.176168E+10 | 1474.43 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.159573E+10 | 1474.43 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.180191E+10 | 1474.43 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.170972E+10 | 1474.43 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.178179E+10 | 1474.43 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.173989E+10 | 1474.43 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.175162E+10 | 1474.43 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.180191E+10 | 1474.43 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.170972E+10 | 1474.43 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.176168E+10 | 1474.43 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.170972E+10 | 1474.43 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.175162E+10 | 1474.43 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.208770E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.159573E+10 | 1474.43 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.180191E+10 | 1474.43 | 0.831065E+09 | 674.13 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.750231E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70559404.14 | 0.255328E+10 |
February | 0.305697E+10 | 0.678234E+10 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122072E+09 | 0.186291E+10 |
March | 0.335708E+10 | 0.751014E+10 | 0.224215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266935E+09 | 0.163714E+10 |
April | 0.327081E+10 | 0.727015E+10 | 0.216638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.755648E+09 | 0.586239E+09 |
May | 0.336680E+10 | 0.750231E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215910E+10 | 29162182.88 |
June | 0.325380E+10 | 0.727015E+10 | 0.217123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233501E+10 | 23429844.12 |
July | 0.339353E+10 | 0.751014E+10 | 0.223729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226651E+10 | 15567158.70 |
August | 0.334857E+10 | 0.750231E+10 | 0.223756E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232273E+10 | 37949654.62 |
September | 0.327932E+10 | 0.727797E+10 | 0.217096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165409E+10 | 76006757.01 |
October | 0.338624E+10 | 0.750231E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153145E+10 | 0.375350E+09 |
November | 0.327446E+10 | 0.724667E+10 | 0.215964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373085E+09 | 0.117674E+10 |
December | 0.340325E+10 | 0.751797E+10 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242261E+09 | 0.221255E+10 |
Annual Sum or Average | 0.397770E+11 | 0.883948E+11 | 0.263573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140994E+11 | 0.105863E+11 |
Minimum of Months | 0.305697E+10 | 0.678234E+10 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70559404.14 | 15567158.70 |
Maximum of Months | 0.340325E+10 | 0.751797E+10 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233501E+10 | 0.255328E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.451294E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39886527.21 | 0.137509E+10 |
February | 0.152844E+10 | 0.407985E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68878511.02 | 0.998203E+09 |
March | 0.167849E+10 | 0.451765E+10 | 0.112107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150067E+09 | 0.858173E+09 |
April | 0.163536E+10 | 0.437329E+10 | 0.108319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426366E+09 | 0.293434E+09 |
May | 0.168335E+10 | 0.451294E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121271E+10 | 11134837.52 |
June | 0.162685E+10 | 0.437329E+10 | 0.108562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131392E+10 | 8260100.16 |
July | 0.169671E+10 | 0.451765E+10 | 0.111865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127060E+10 | 6975689.81 |
August | 0.167424E+10 | 0.451294E+10 | 0.111878E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130209E+10 | 13268431.21 |
September | 0.163961E+10 | 0.437799E+10 | 0.108548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.925037E+09 | 31224050.99 |
October | 0.169307E+10 | 0.451294E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.856895E+09 | 0.165872E+09 |
November | 0.163718E+10 | 0.435916E+10 | 0.107982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210865E+09 | 0.601676E+09 |
December | 0.170157E+10 | 0.452236E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137009E+09 | 0.116188E+10 |
Annual Sum or Average | 0.198880E+11 | 0.531730E+11 | 0.131787E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.791432E+10 | 0.552519E+10 |
Minimum of Months | 0.152844E+10 | 0.407985E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39886527.21 | 6975689.81 |
Maximum of Months | 0.170157E+10 | 0.452236E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131392E+10 | 0.137509E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.326451E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887276.39 | 0.137502E+10 |
February | 0.914877E+09 | 0.295632E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68805973.26 | 0.100626E+10 |
March | 0.103395E+10 | 0.333300E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147778E+09 | 0.872552E+09 |
April | 0.984131E+09 | 0.316749E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421339E+09 | 0.307363E+09 |
May | 0.102058E+10 | 0.329875E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119398E+10 | 14234004.11 |
June | 0.998711E+09 | 0.321885E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129971E+10 | 11141506.69 |
July | 0.100600E+10 | 0.324739E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124720E+10 | 8379786.80 |
August | 0.103395E+10 | 0.333300E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129010E+10 | 20414825.67 |
September | 0.984131E+09 | 0.316749E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.902715E+09 | 38234243.81 |
October | 0.100722E+10 | 0.326451E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.837522E+09 | 0.180134E+09 |
November | 0.973196E+09 | 0.316749E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207876E+09 | 0.615228E+09 |
December | 0.100600E+10 | 0.324739E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136538E+09 | 0.117565E+10 |
Annual Sum or Average | 0.119700E+11 | 0.386662E+11 | 0.104672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.779346E+10 | 0.562461E+10 |
Minimum of Months | 0.914877E+09 | 0.295632E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887276.39 | 8379786.80 |
Maximum of Months | 0.103395E+10 | 0.333300E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129971E+10 | 0.137502E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.326451E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887463.76 | 0.136176E+10 |
February | 0.914877E+09 | 0.295632E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68805967.80 | 0.998126E+09 |
March | 0.103395E+10 | 0.333300E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147786E+09 | 0.866473E+09 |
April | 0.984131E+09 | 0.316749E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421332E+09 | 0.306843E+09 |
May | 0.102058E+10 | 0.329875E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119371E+10 | 14729202.89 |
June | 0.998711E+09 | 0.321885E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129940E+10 | 11576816.32 |
July | 0.100600E+10 | 0.324739E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124657E+10 | 8818278.51 |
August | 0.103395E+10 | 0.333300E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128971E+10 | 21078369.42 |
September | 0.984131E+09 | 0.316749E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.902266E+09 | 38965118.13 |
October | 0.100722E+10 | 0.326451E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.837400E+09 | 0.181035E+09 |
November | 0.973196E+09 | 0.316749E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207878E+09 | 0.614061E+09 |
December | 0.100600E+10 | 0.324739E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136539E+09 | 0.116916E+10 |
Annual Sum or Average | 0.119700E+11 | 0.386662E+11 | 0.104672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.779129E+10 | 0.559263E+10 |
Minimum of Months | 0.914877E+09 | 0.295632E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887463.76 | 8818278.51 |
Maximum of Months | 0.103395E+10 | 0.333300E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129940E+10 | 0.136176E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.326451E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887458.49 | 0.134436E+10 |
February | 0.914877E+09 | 0.295632E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68805960.73 | 0.986206E+09 |
March | 0.103395E+10 | 0.333300E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147807E+09 | 0.855480E+09 |
April | 0.984131E+09 | 0.316749E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421405E+09 | 0.304910E+09 |
May | 0.102058E+10 | 0.329875E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119418E+10 | 13588710.03 |
June | 0.998711E+09 | 0.321885E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129982E+10 | 10812669.33 |
July | 0.100600E+10 | 0.324739E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124723E+10 | 8254840.93 |
August | 0.103395E+10 | 0.333300E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129014E+10 | 20012254.24 |
September | 0.984131E+09 | 0.316749E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.902610E+09 | 37846385.44 |
October | 0.100722E+10 | 0.326451E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.837622E+09 | 0.179301E+09 |
November | 0.973196E+09 | 0.316749E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207892E+09 | 0.610906E+09 |
December | 0.100600E+10 | 0.324739E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136542E+09 | 0.115941E+10 |
Annual Sum or Average | 0.119700E+11 | 0.386662E+11 | 0.104672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.779394E+10 | 0.553109E+10 |
Minimum of Months | 0.914877E+09 | 0.295632E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887458.49 | 8254840.93 |
Maximum of Months | 0.103395E+10 | 0.333300E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129982E+10 | 0.134436E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.343207E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69893204.79 | 0.236497E+10 |
February | 0.313522E+10 | 0.310878E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120602E+09 | 0.173339E+10 |
March | 0.355148E+10 | 0.351044E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259374E+09 | 0.151152E+10 |
April | 0.338259E+10 | 0.333084E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.738670E+09 | 0.548788E+09 |
May | 0.349753E+10 | 0.347125E+10 | 0.164379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208568E+10 | 24777140.96 |
June | 0.343071E+10 | 0.338962E+10 | 0.160496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226915E+10 | 20222083.59 |
July | 0.344942E+10 | 0.341247E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217580E+10 | 14401199.36 |
August | 0.355148E+10 | 0.351044E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225254E+10 | 36727608.66 |
September | 0.338259E+10 | 0.333084E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157737E+10 | 74063052.14 |
October | 0.344359E+10 | 0.343207E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146725E+10 | 0.338969E+09 |
November | 0.331698E+10 | 0.333084E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364363E+09 | 0.109410E+10 |
December | 0.344942E+10 | 0.341247E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239250E+09 | 0.205197E+10 |
Annual Sum or Average | 0.410346E+11 | 0.406721E+11 | 0.192612E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136199E+11 | 0.981390E+10 |
Minimum of Months | 0.313522E+10 | 0.310878E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69893204.79 | 14401199.36 |
Maximum of Months | 0.355148E+10 | 0.351044E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226915E+10 | 0.236497E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.176168E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887454.96 | 0.131468E+10 |
February | 0.156756E+10 | 0.159573E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68807522.52 | 0.964390E+09 |
March | 0.177569E+10 | 0.180191E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147904E+09 | 0.835746E+09 |
April | 0.169125E+10 | 0.170972E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421593E+09 | 0.303730E+09 |
May | 0.174872E+10 | 0.178179E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119018E+10 | 11833508.93 |
June | 0.171530E+10 | 0.173989E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129515E+10 | 9675205.32 |
July | 0.172466E+10 | 0.175162E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124159E+10 | 7289083.90 |
August | 0.177569E+10 | 0.180191E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128475E+10 | 17878870.13 |
September | 0.169125E+10 | 0.170972E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.899502E+09 | 38037557.17 |
October | 0.172174E+10 | 0.176168E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.836716E+09 | 0.182363E+09 |
November | 0.165844E+10 | 0.170972E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207939E+09 | 0.608913E+09 |
December | 0.172466E+10 | 0.175162E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136546E+09 | 0.114312E+10 |
Annual Sum or Average | 0.205167E+11 | 0.208770E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.777056E+10 | 0.543766E+10 |
Minimum of Months | 0.156756E+10 | 0.159573E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887454.96 | 7289083.90 |
Maximum of Months | 0.177569E+10 | 0.180191E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129515E+10 | 0.131468E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.176168E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887453.10 | 0.130778E+10 |
February | 0.156756E+10 | 0.159573E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68807765.44 | 0.959053E+09 |
March | 0.177569E+10 | 0.180191E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147915E+09 | 0.830972E+09 |
April | 0.169125E+10 | 0.170972E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421625E+09 | 0.302649E+09 |
May | 0.174872E+10 | 0.178179E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119050E+10 | 11525911.50 |
June | 0.171530E+10 | 0.173989E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129542E+10 | 9476237.18 |
July | 0.172466E+10 | 0.175162E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124193E+10 | 7174005.31 |
August | 0.177569E+10 | 0.180191E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128494E+10 | 17620673.26 |
September | 0.169125E+10 | 0.170972E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.899674E+09 | 37722027.51 |
October | 0.172174E+10 | 0.176168E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.836829E+09 | 0.181684E+09 |
November | 0.165844E+10 | 0.170972E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207949E+09 | 0.607215E+09 |
December | 0.172466E+10 | 0.175162E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136547E+09 | 0.113829E+10 |
Annual Sum or Average | 0.205167E+11 | 0.208770E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.777202E+10 | 0.541116E+10 |
Minimum of Months | 0.156756E+10 | 0.159573E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887453.10 | 7174005.31 |
Maximum of Months | 0.177569E+10 | 0.180191E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129542E+10 | 0.130778E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.176168E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887447.90 | 0.129372E+10 |
February | 0.156756E+10 | 0.159573E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68808152.18 | 0.947326E+09 |
March | 0.177569E+10 | 0.180191E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147935E+09 | 0.820155E+09 |
April | 0.169125E+10 | 0.170972E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421658E+09 | 0.299396E+09 |
May | 0.174872E+10 | 0.178179E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119099E+10 | 10897185.42 |
June | 0.171530E+10 | 0.173989E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129568E+10 | 9154938.83 |
July | 0.172466E+10 | 0.175162E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124197E+10 | 7053054.13 |
August | 0.177569E+10 | 0.180191E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128485E+10 | 17557269.44 |
September | 0.169125E+10 | 0.170972E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.899520E+09 | 37483198.11 |
October | 0.172174E+10 | 0.176168E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.836804E+09 | 0.180654E+09 |
November | 0.165844E+10 | 0.170972E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207959E+09 | 0.603408E+09 |
December | 0.172466E+10 | 0.175162E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136548E+09 | 0.112756E+10 |
Annual Sum or Average | 0.205167E+11 | 0.208770E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.777260E+10 | 0.535436E+10 |
Minimum of Months | 0.156756E+10 | 0.159573E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887447.90 | 7053054.13 |
Maximum of Months | 0.177569E+10 | 0.180191E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129568E+10 | 0.129372E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.176168E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40553946.28 | 0.151799E+10 |
February | 0.156756E+10 | 0.159573E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 70151352.69 | 0.109637E+10 |
March | 0.177569E+10 | 0.180191E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151582E+09 | 0.990567E+09 |
April | 0.169125E+10 | 0.170972E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.429198E+09 | 0.369243E+09 |
May | 0.174872E+10 | 0.178179E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122124E+10 | 21034354.02 |
June | 0.171530E+10 | 0.173989E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132458E+10 | 19670737.59 |
July | 0.172466E+10 | 0.175162E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127392E+10 | 12158008.18 |
August | 0.177569E+10 | 0.180191E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131912E+10 | 39256391.82 |
September | 0.169125E+10 | 0.170972E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.925724E+09 | 68964388.24 |
October | 0.172174E+10 | 0.176168E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.860401E+09 | 0.272881E+09 |
November | 0.165844E+10 | 0.170972E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211385E+09 | 0.731671E+09 |
December | 0.172466E+10 | 0.175162E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138738E+09 | 0.132936E+10 |
Annual Sum or Average | 0.205167E+11 | 0.208770E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.796659E+10 | 0.646916E+10 |
Minimum of Months | 0.156756E+10 | 0.159573E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40553946.28 | 12158008.18 |
Maximum of Months | 0.177569E+10 | 0.180191E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132458E+10 | 0.151799E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 4589.20 | 01-JAN-10:09 | 1348.26 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1459.20 | 16-JAN-15:00 | 7668.65 | 04-JAN-18:00 |
February | 4050.04 | 03-FEB-13:09 | 4589.20 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2107.21 | 02-FEB-13:00 | 8462.73 | 04-FEB-18:00 |
March | 4050.04 | 03-MAR-13:09 | 4589.20 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2854.26 | 26-MAR-14:00 | 7632.19 | 11-MAR-12:10 |
April | 4050.04 | 01-APR-12:09 | 4589.20 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4371.37 | 28-APR-15:00 | 3398.57 | 02-APR-11:10 |
May | 4050.04 | 05-MAY-12:09 | 4589.20 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4660.72 | 07-MAY-14:00 | 524.52 | 31-MAY-13:00 |
June | 4050.04 | 02-JUN-12:09 | 4589.20 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5074.35 | 14-JUN-14:00 | 534.24 | 01-JUN-13:00 |
July | 4050.04 | 01-JUL-12:09 | 4589.20 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5552.73 | 22-JUL-16:00 | 529.81 | 12-JUL-15:00 |
August | 4050.04 | 04-AUG-12:09 | 4589.20 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5648.88 | 30-AUG-16:00 | 1008.29 | 16-AUG-17:00 |
September | 4050.04 | 01-SEP-12:09 | 4589.20 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5771.84 | 09-SEP-17:00 | 1979.94 | 07-SEP-17:00 |
October | 4050.04 | 01-OCT-12:09 | 4589.20 | 01-OCT-09:09 | 1348.26 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4643.30 | 05-OCT-15:00 | 3395.49 | 27-OCT-16:00 |
November | 4050.04 | 03-NOV-12:09 | 4589.20 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2838.15 | 01-NOV-14:00 | 6007.10 | 15-NOV-18:00 |
December | 4050.04 | 01-DEC-13:09 | 4589.20 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2866.47 | 13-DEC-15:00 | 8685.40 | 20-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 4589.20 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 1459.20 | 524.52 | |||||
Maximum of Months | 4050.04 | 4589.20 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 5771.84 | 8685.40 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 2760.58 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 16-JAN-15:00 | 4346.94 | 04-JAN-18:00 |
February | 2024.96 | 03-FEB-13:09 | 2760.58 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1179.68 | 02-FEB-13:00 | 4744.95 | 04-FEB-18:00 |
March | 2024.96 | 03-MAR-13:09 | 2760.58 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1615.89 | 26-MAR-14:00 | 4292.50 | 11-MAR-12:10 |
April | 2024.96 | 01-APR-12:09 | 2760.58 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2466.20 | 28-APR-15:00 | 1959.11 | 02-APR-11:10 |
May | 2024.96 | 05-MAY-12:09 | 2760.58 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2629.46 | 07-MAY-14:00 | 296.85 | 31-MAY-13:00 |
June | 2024.96 | 02-JUN-12:09 | 2760.58 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2880.95 | 14-JUN-14:00 | 299.45 | 01-JUN-13:00 |
July | 2024.96 | 01-JUL-12:09 | 2760.58 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3158.61 | 22-JUL-16:00 | 298.90 | 12-JUL-15:00 |
August | 2024.96 | 04-AUG-12:09 | 2760.58 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3204.08 | 30-AUG-16:00 | 570.82 | 16-AUG-17:00 |
September | 2024.96 | 01-SEP-12:09 | 2760.58 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 09-SEP-17:00 | 1121.25 | 07-SEP-17:00 |
October | 2024.96 | 01-OCT-12:09 | 2760.58 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2632.03 | 05-OCT-15:00 | 1915.64 | 27-OCT-16:00 |
November | 2024.96 | 03-NOV-12:09 | 2760.58 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1611.83 | 01-NOV-14:00 | 3464.27 | 15-NOV-18:00 |
December | 2024.96 | 01-DEC-13:09 | 2760.58 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1622.28 | 13-DEC-15:00 | 4940.59 | 20-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2760.58 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 296.85 | |||||
Maximum of Months | 2024.96 | 2760.58 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 4940.59 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2510.11 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 16-JAN-15:00 | 4346.94 | 04-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2510.11 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1179.68 | 02-FEB-13:00 | 4744.95 | 04-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2510.11 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1615.86 | 26-MAR-14:00 | 4292.50 | 11-MAR-12:10 |
April | 2024.96 | 01-APR-12:09 | 2510.11 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2466.27 | 28-APR-15:00 | 1950.47 | 02-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 2510.11 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2629.45 | 07-MAY-14:00 | 296.85 | 31-MAY-13:00 |
June | 2024.96 | 03-JUN-12:09 | 2510.11 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2880.95 | 14-JUN-14:00 | 299.45 | 01-JUN-13:00 |
July | 2024.96 | 01-JUL-12:09 | 2510.11 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3158.61 | 22-JUL-16:00 | 298.90 | 12-JUL-15:00 |
August | 2024.96 | 05-AUG-12:09 | 2510.11 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3204.08 | 30-AUG-16:00 | 570.82 | 16-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 2510.11 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 09-SEP-17:00 | 1121.25 | 07-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2510.11 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2632.03 | 05-OCT-15:00 | 1915.65 | 27-OCT-16:00 |
November | 2024.96 | 04-NOV-12:09 | 2510.11 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1611.96 | 01-NOV-14:00 | 3430.52 | 15-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2510.11 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1622.24 | 13-DEC-15:00 | 4940.59 | 20-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2510.11 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 296.85 | |||||
Maximum of Months | 2024.96 | 2510.11 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 4940.59 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2510.11 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 16-JAN-15:00 | 4346.94 | 04-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2510.11 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1179.68 | 02-FEB-13:00 | 4744.95 | 04-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2510.11 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1615.86 | 26-MAR-14:00 | 4292.50 | 11-MAR-12:10 |
April | 2024.96 | 01-APR-12:09 | 2510.11 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2466.28 | 28-APR-15:00 | 1946.34 | 02-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 2510.11 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2629.45 | 07-MAY-14:00 | 296.85 | 31-MAY-13:00 |
June | 2024.96 | 03-JUN-12:09 | 2510.11 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2880.95 | 14-JUN-14:00 | 299.45 | 01-JUN-13:00 |
July | 2024.96 | 01-JUL-12:09 | 2510.11 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3158.61 | 22-JUL-16:00 | 298.90 | 12-JUL-15:00 |
August | 2024.96 | 05-AUG-12:09 | 2510.11 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3204.08 | 30-AUG-16:00 | 570.82 | 16-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 2510.11 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 09-SEP-17:00 | 1121.25 | 07-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2510.11 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2632.03 | 05-OCT-15:00 | 1915.65 | 27-OCT-16:00 |
November | 2024.96 | 04-NOV-12:09 | 2510.11 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1611.99 | 01-NOV-14:00 | 3415.86 | 15-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2510.11 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1622.23 | 13-DEC-15:00 | 4940.59 | 20-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2510.11 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 296.85 | |||||
Maximum of Months | 2024.96 | 2510.11 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 4940.59 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2510.11 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 16-JAN-15:00 | 4346.94 | 04-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2510.11 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1179.68 | 02-FEB-13:00 | 4744.95 | 04-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2510.11 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1615.85 | 26-MAR-14:00 | 4292.50 | 11-MAR-12:10 |
April | 2024.96 | 01-APR-12:09 | 2510.11 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2466.30 | 28-APR-15:00 | 1935.39 | 02-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 2510.11 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2629.45 | 07-MAY-14:00 | 296.85 | 31-MAY-13:00 |
June | 2024.96 | 03-JUN-12:09 | 2510.11 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2880.95 | 14-JUN-14:00 | 299.45 | 01-JUN-13:00 |
July | 2024.96 | 01-JUL-12:09 | 2510.11 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3158.61 | 22-JUL-16:00 | 298.90 | 12-JUL-15:00 |
August | 2024.96 | 05-AUG-12:09 | 2510.11 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3204.08 | 30-AUG-16:00 | 570.82 | 16-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 2510.11 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 09-SEP-17:00 | 1121.25 | 07-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2510.11 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2632.03 | 05-OCT-15:00 | 1915.65 | 27-OCT-16:00 |
November | 2024.96 | 04-NOV-12:09 | 2510.11 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1612.02 | 01-NOV-14:00 | 3386.14 | 15-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2510.11 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1622.22 | 13-DEC-15:00 | 4940.59 | 20-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2510.11 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 296.85 | |||||
Maximum of Months | 2024.96 | 2510.11 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 4940.59 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 2872.47 | 01-JAN-11:09 | 1348.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1448.80 | 16-JAN-15:00 | 7613.97 | 04-JAN-18:00 |
February | 5400.05 | 04-FEB-15:09 | 2872.47 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2070.02 | 02-FEB-13:00 | 8324.27 | 04-FEB-18:00 |
March | 5400.05 | 04-MAR-15:09 | 2872.47 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2830.80 | 26-MAR-14:00 | 7527.14 | 11-MAR-12:10 |
April | 5400.05 | 01-APR-14:09 | 2872.47 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4323.08 | 28-APR-15:00 | 3272.85 | 01-APR-17:00 |
May | 5400.05 | 06-MAY-14:09 | 2872.47 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4608.83 | 07-MAY-14:00 | 520.08 | 31-MAY-13:00 |
June | 5400.05 | 03-JUN-14:09 | 2872.47 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5045.04 | 14-JUN-14:00 | 525.36 | 01-JUN-13:00 |
July | 5400.05 | 01-JUL-14:09 | 2872.47 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5529.73 | 22-JUL-16:00 | 523.91 | 12-JUL-15:00 |
August | 5400.05 | 05-AUG-14:09 | 2872.47 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5611.65 | 30-AUG-16:00 | 1000.01 | 16-AUG-17:00 |
September | 5400.05 | 02-SEP-14:09 | 2872.47 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5702.99 | 09-SEP-17:00 | 1964.22 | 07-SEP-17:00 |
October | 5400.05 | 07-OCT-14:09 | 2872.47 | 01-OCT-10:09 | 1348.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4610.19 | 05-OCT-15:00 | 3357.64 | 27-OCT-16:00 |
November | 5400.05 | 04-NOV-14:09 | 2872.47 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2822.66 | 01-NOV-14:00 | 5797.64 | 15-NOV-18:00 |
December | 5400.05 | 02-DEC-15:09 | 2872.47 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2842.13 | 13-DEC-15:00 | 8649.42 | 20-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 2872.47 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 1448.80 | 520.08 | |||||
Maximum of Months | 5400.05 | 2872.47 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 5702.99 | 8649.42 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1474.43 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 16-JAN-15:00 | 4346.94 | 04-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1474.43 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1179.68 | 02-FEB-13:00 | 4744.95 | 04-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1474.43 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1615.85 | 26-MAR-14:00 | 4292.50 | 11-MAR-12:10 |
April | 2699.95 | 01-APR-14:09 | 1474.43 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2466.43 | 28-APR-15:00 | 1863.16 | 01-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 1474.43 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2629.46 | 07-MAY-14:00 | 296.85 | 31-MAY-13:00 |
June | 2699.95 | 03-JUN-14:09 | 1474.43 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2880.95 | 14-JUN-14:00 | 299.45 | 01-JUN-13:00 |
July | 2699.95 | 01-JUL-14:09 | 1474.43 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3158.61 | 22-JUL-16:00 | 298.90 | 12-JUL-15:00 |
August | 2699.95 | 05-AUG-14:09 | 1474.43 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3204.08 | 30-AUG-16:00 | 570.82 | 16-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1474.43 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 09-SEP-17:00 | 1121.25 | 07-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1474.43 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2632.03 | 05-OCT-15:00 | 1915.63 | 27-OCT-16:00 |
November | 2699.95 | 04-NOV-14:09 | 1474.43 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1611.94 | 01-NOV-14:00 | 3291.13 | 15-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1474.43 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1622.24 | 13-DEC-15:00 | 4940.59 | 20-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1474.43 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 296.85 | |||||
Maximum of Months | 2699.95 | 1474.43 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 4940.59 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1474.43 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 16-JAN-15:00 | 4346.94 | 04-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1474.43 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1179.68 | 02-FEB-13:00 | 4744.95 | 04-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1474.43 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1615.85 | 26-MAR-14:00 | 4292.50 | 11-MAR-12:10 |
April | 2699.95 | 01-APR-14:09 | 1474.43 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2466.43 | 28-APR-15:00 | 1861.05 | 01-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 1474.43 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2629.46 | 07-MAY-14:00 | 296.85 | 31-MAY-13:00 |
June | 2699.95 | 03-JUN-14:09 | 1474.43 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2880.95 | 14-JUN-14:00 | 299.45 | 01-JUN-13:00 |
July | 2699.95 | 01-JUL-14:09 | 1474.43 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3158.61 | 22-JUL-16:00 | 298.90 | 12-JUL-15:00 |
August | 2699.95 | 05-AUG-14:09 | 1474.43 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3204.08 | 30-AUG-16:00 | 570.82 | 16-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1474.43 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 09-SEP-17:00 | 1121.25 | 07-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1474.43 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2632.03 | 05-OCT-15:00 | 1915.64 | 27-OCT-16:00 |
November | 2699.95 | 04-NOV-14:09 | 1474.43 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1611.94 | 01-NOV-14:00 | 3275.99 | 15-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1474.43 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1622.24 | 13-DEC-15:00 | 4940.59 | 20-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1474.43 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 296.85 | |||||
Maximum of Months | 2699.95 | 1474.43 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 4940.59 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1474.43 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 16-JAN-15:00 | 4346.94 | 04-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1474.43 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1179.68 | 02-FEB-13:00 | 4744.95 | 04-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1474.43 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1615.88 | 26-MAR-14:00 | 4292.50 | 11-MAR-12:10 |
April | 2699.95 | 01-APR-14:09 | 1474.43 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2466.39 | 28-APR-15:00 | 1855.11 | 01-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 1474.43 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2629.46 | 07-MAY-14:00 | 296.85 | 31-MAY-13:00 |
June | 2699.95 | 03-JUN-14:09 | 1474.43 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2880.95 | 14-JUN-14:00 | 299.45 | 01-JUN-13:00 |
July | 2699.95 | 01-JUL-14:09 | 1474.43 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3158.61 | 22-JUL-16:00 | 298.90 | 12-JUL-15:00 |
August | 2699.95 | 05-AUG-14:09 | 1474.43 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3204.08 | 30-AUG-16:00 | 570.82 | 16-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1474.43 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 09-SEP-17:00 | 1121.25 | 07-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1474.43 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2632.03 | 05-OCT-15:00 | 1915.64 | 27-OCT-16:00 |
November | 2699.95 | 04-NOV-14:09 | 1474.43 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1611.98 | 01-NOV-14:00 | 3248.20 | 15-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1474.43 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1622.23 | 13-DEC-15:00 | 4940.59 | 20-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1474.43 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 296.85 | |||||
Maximum of Months | 2699.95 | 1474.43 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 4940.59 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1474.43 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 837.55 | 16-JAN-15:00 | 4401.62 | 04-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1474.43 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1216.86 | 02-FEB-13:00 | 4883.41 | 04-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1474.43 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1639.54 | 26-MAR-14:00 | 4397.55 | 11-MAR-12:10 |
April | 2699.95 | 01-APR-14:09 | 1474.43 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2515.01 | 28-APR-15:00 | 1910.28 | 01-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 1474.43 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2680.96 | 07-MAY-14:00 | 301.30 | 31-MAY-13:00 |
June | 2699.95 | 03-JUN-14:09 | 1474.43 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2910.27 | 14-JUN-14:00 | 308.33 | 01-JUN-13:00 |
July | 2699.95 | 01-JUL-14:09 | 1474.43 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3181.61 | 22-JUL-16:00 | 304.80 | 12-JUL-15:00 |
August | 2699.95 | 05-AUG-14:09 | 1474.43 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3241.30 | 30-AUG-16:00 | 579.09 | 16-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1474.43 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3322.12 | 09-SEP-17:00 | 1136.97 | 07-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1474.43 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2665.14 | 05-OCT-15:00 | 1953.45 | 27-OCT-16:00 |
November | 2699.95 | 04-NOV-14:09 | 1474.43 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.70 | 01-NOV-14:00 | 3216.58 | 15-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1474.43 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1646.38 | 13-DEC-15:00 | 4976.57 | 20-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1474.43 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 837.55 | 301.30 | |||||
Maximum of Months | 2699.95 | 1474.43 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3322.12 | 4976.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 29665.45 | 19-JAN-09:02 | 1687.52 | 12076.81 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.22 |
February | 33532.48 | 28-FEB-09:02 | 1687.52 | 12076.81 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 292.58 |
March | 28868.32 | 07-MAR-09:02 | 1687.52 | 12076.81 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.30 |
April | 32415.66 | 22-APR-08:62 | 1687.52 | 12076.81 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.17 |
May | 34220.30 | 07-MAY-07:02 | 1687.52 | 1207.61 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 35.25 | 0.00 |
June | 34927.87 | 11-JUN-07:02 | 1687.52 | 1207.61 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.70 |
July | 34095.84 | 09-JUL-07:02 | 2025.02 | 1449.13 | 449.42 | 0.00 | 0.00 | 0.00 | 0.00 | 225.81 | 0.00 |
August | 36056.74 | 20-AUG-07:02 | 2025.02 | 1449.13 | 449.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.43 |
September | 33452.66 | 22-SEP-08:62 | 2025.02 | 14492.17 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.12 |
October | 49245.21 | 26-OCT-08:61 | 2362.52 | 16907.53 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 322.42 |
November | 36559.99 | 06-NOV-09:02 | 2025.02 | 14492.17 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.93 |
December | 31803.05 | 11-DEC-09:02 | 1687.52 | 12076.81 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 28868.32 | 1687.52 | 1207.61 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 49245.21 | 2362.52 | 16907.53 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 225.81 | 322.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16312.86 | 19-JAN-09:02 | 843.73 | 7264.69 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.90 |
February | 20177.13 | 28-FEB-09:02 | 843.73 | 7264.69 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.97 |
March | 18201.99 | 30-MAR-08:62 | 674.99 | 5811.75 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.54 |
April | 19907.09 | 24-APR-08:62 | 843.73 | 7264.69 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.12 |
May | 20935.18 | 07-MAY-07:02 | 843.73 | 726.47 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 17.26 | 0.00 |
June | 20597.50 | 11-JUN-07:02 | 843.73 | 726.47 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.76 |
July | 20929.24 | 09-JUL-07:02 | 1012.48 | 871.76 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 130.05 | 0.00 |
August | 21453.13 | 20-AUG-07:02 | 1012.48 | 871.76 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.40 |
September | 20304.29 | 03-SEP-07:02 | 1012.48 | 871.76 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 72.88 | 0.00 |
October | 26449.40 | 26-OCT-08:61 | 1181.23 | 10170.57 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.02 |
November | 21550.15 | 06-NOV-09:02 | 1012.48 | 8717.63 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.93 |
December | 19243.89 | 11-DEC-09:02 | 843.73 | 7264.69 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.78 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16312.86 | 674.99 | 726.47 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26449.40 | 1181.23 | 10170.57 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 130.05 | 194.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 22431.24 | 02-JAN-08:62 | 843.73 | 6605.54 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 365.79 |
February | 18610.22 | 28-FEB-08:62 | 843.73 | 6605.54 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.67 |
March | 17817.07 | 27-MAR-07:02 | 843.73 | 6605.54 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.70 |
April | 18797.52 | 25-APR-07:02 | 843.73 | 6605.54 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.96 |
May | 18432.27 | 12-MAY-07:01 | 1181.23 | 9247.76 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.78 |
June | 18228.06 | 14-JUN-07:01 | 1349.97 | 10568.86 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 35.27 | 0.00 |
July | 16010.55 | 19-JUL-07:01 | 1349.97 | 10568.86 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 79.42 | 0.00 |
August | 18092.38 | 31-AUG-07:01 | 1349.97 | 10568.86 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.70 |
September | 17945.65 | 23-SEP-07:01 | 1181.23 | 9247.76 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.64 |
October | 28349.97 | 17-OCT-07:02 | 1012.48 | 7926.65 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 392.56 |
November | 19183.48 | 06-NOV-08:62 | 1012.48 | 7926.65 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.92 |
December | 22965.59 | 17-DEC-09:02 | 1012.48 | 7926.65 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 260.91 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16010.55 | 843.73 | 6605.54 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28349.97 | 1349.97 | 10568.86 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 79.42 | 392.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 22503.61 | 02-JAN-08:62 | 843.73 | 6605.54 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 365.80 |
February | 18633.14 | 28-FEB-08:62 | 843.73 | 6605.54 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.58 |
March | 17840.66 | 27-MAR-07:02 | 843.73 | 6605.54 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.59 |
April | 18866.22 | 25-APR-07:02 | 843.73 | 6605.54 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.22 |
May | 18540.12 | 12-MAY-07:01 | 1181.23 | 9247.76 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.74 |
June | 18364.45 | 12-JUN-07:01 | 1349.97 | 10568.86 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.28 |
July | 16096.47 | 19-JUL-07:01 | 1349.97 | 10568.86 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 79.51 | 0.00 |
August | 18186.87 | 31-AUG-07:01 | 1349.97 | 10568.86 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.55 |
September | 18041.38 | 23-SEP-07:01 | 1181.23 | 9247.76 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.21 |
October | 28487.80 | 17-OCT-07:02 | 1012.48 | 7926.65 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 394.15 |
November | 19290.18 | 06-NOV-08:62 | 1012.48 | 7926.65 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.46 |
December | 23054.59 | 17-DEC-09:02 | 1012.48 | 7926.65 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261.49 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16096.47 | 843.73 | 6605.54 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28487.80 | 1349.97 | 10568.86 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 79.51 | 394.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 22270.02 | 02-JAN-08:62 | 843.73 | 6605.54 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 362.43 |
February | 18375.23 | 28-FEB-08:62 | 843.73 | 6605.54 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.27 |
March | 17571.29 | 27-MAR-07:02 | 843.73 | 6605.54 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.19 |
April | 18616.63 | 25-APR-07:02 | 843.73 | 6605.54 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.16 |
May | 18306.99 | 12-MAY-07:01 | 1181.23 | 9247.76 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.29 |
June | 18219.81 | 12-JUN-07:01 | 1349.97 | 10568.86 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.66 |
July | 15921.70 | 19-JUL-07:01 | 1349.97 | 10568.86 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 79.36 | 0.00 |
August | 17969.05 | 31-AUG-07:01 | 1349.97 | 10568.86 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.63 |
September | 17812.53 | 23-SEP-07:01 | 1181.23 | 9247.76 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.72 |
October | 28223.96 | 17-OCT-07:02 | 1012.48 | 7926.65 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 391.02 |
November | 19073.59 | 06-NOV-08:62 | 1012.48 | 7926.65 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.07 |
December | 22805.65 | 17-DEC-09:02 | 1012.48 | 7926.65 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 15921.70 | 843.73 | 6605.54 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28223.96 | 1349.97 | 10568.86 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 79.36 | 391.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 37347.82 | 01-JAN-10:02 | 3712.53 | 7559.10 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 303.60 |
February | 31723.25 | 28-FEB-09:02 | 3712.53 | 7559.10 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 278.30 |
March | 26729.76 | 07-MAR-09:02 | 3712.53 | 7559.10 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.23 |
April | 30788.49 | 22-APR-08:62 | 3712.53 | 7559.10 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.58 |
May | 31874.54 | 12-MAY-08:62 | 4455.04 | 9070.92 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.83 |
June | 31692.15 | 14-JUN-08:61 | 5940.06 | 12094.56 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 151.97 | 0.00 |
July | 28869.02 | 18-JUL-08:61 | 5940.06 | 12094.56 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 184.50 | 0.00 |
August | 32058.41 | 31-AUG-08:61 | 5940.06 | 12094.56 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 142.12 | 0.00 |
September | 30881.35 | 22-SEP-08:62 | 4455.04 | 9070.92 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.43 |
October | 45252.38 | 26-OCT-08:61 | 5197.55 | 10582.74 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 291.75 |
November | 33038.24 | 05-NOV-09:02 | 2970.03 | 6047.28 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.26 |
December | 40960.49 | 17-DEC-10:02 | 4455.04 | 9070.92 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 448.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 26729.76 | 2970.03 | 6047.28 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 45252.38 | 5940.06 | 12094.56 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 184.50 | 448.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19439.59 | 01-JAN-10:02 | 1856.21 | 3880.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.85 |
February | 16042.10 | 28-FEB-09:02 | 1856.21 | 3880.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.04 |
March | 13913.44 | 07-MAR-09:02 | 1856.21 | 3880.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.39 |
April | 16034.87 | 22-APR-08:62 | 1856.21 | 3880.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.88 |
May | 16593.89 | 12-MAY-08:62 | 2227.46 | 4656.09 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.11 |
June | 16526.14 | 14-JUN-08:61 | 2969.94 | 6208.12 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 91.39 | 0.00 |
July | 15059.68 | 18-JUL-08:61 | 2969.94 | 6208.12 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 109.27 | 0.00 |
August | 16720.51 | 31-AUG-08:61 | 2969.94 | 6208.12 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 85.95 | 0.00 |
September | 16077.44 | 22-SEP-08:62 | 2227.46 | 4656.09 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.38 |
October | 23593.04 | 26-OCT-08:61 | 2598.70 | 5432.10 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.06 |
November | 17060.82 | 06-NOV-09:02 | 2227.46 | 4656.09 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.71 |
December | 21349.68 | 17-DEC-10:02 | 2227.46 | 4656.09 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13913.44 | 1856.21 | 3880.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23593.04 | 2969.94 | 6208.12 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 109.27 | 246.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19307.71 | 01-JAN-10:02 | 1856.21 | 3880.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.96 |
February | 15251.18 | 28-FEB-09:02 | 1856.21 | 3880.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.83 |
March | 13778.94 | 07-MAR-09:02 | 1856.21 | 3880.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.36 |
April | 15926.41 | 22-APR-08:62 | 1856.21 | 3880.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.41 |
May | 16491.10 | 12-MAY-08:62 | 2227.46 | 4656.09 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 |
June | 16420.07 | 14-JUN-08:61 | 2969.94 | 6208.12 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 92.45 | 0.00 |
July | 14962.14 | 18-JUL-08:61 | 2969.94 | 6208.12 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 110.12 | 0.00 |
August | 16613.03 | 31-AUG-08:61 | 2969.94 | 6208.12 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 86.84 | 0.00 |
September | 15977.29 | 22-SEP-08:62 | 2227.46 | 4656.09 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.41 |
October | 23466.54 | 26-OCT-08:61 | 2598.70 | 5432.10 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.15 |
November | 16951.14 | 06-NOV-09:02 | 2227.46 | 4656.09 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.31 |
December | 21225.06 | 17-DEC-10:02 | 2227.46 | 4656.09 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13778.94 | 1856.21 | 3880.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23466.54 | 2969.94 | 6208.12 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 110.12 | 245.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19236.54 | 01-JAN-10:02 | 1856.21 | 3880.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.97 |
February | 12965.68 | 28-FEB-09:02 | 1856.21 | 3880.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.24 |
March | 13650.18 | 07-MAR-09:02 | 1856.21 | 3880.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.28 |
April | 15402.28 | 23-APR-09:02 | 1856.21 | 3880.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 10.71 | 0.00 |
May | 16517.41 | 12-MAY-08:62 | 2227.46 | 4656.09 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.57 |
June | 16481.96 | 14-JUN-08:61 | 2969.94 | 6208.12 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 93.56 | 0.00 |
July | 15035.86 | 07-JUL-08:61 | 2969.94 | 6208.12 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 118.98 | 0.00 |
August | 16710.39 | 31-AUG-08:61 | 2969.94 | 6208.12 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 86.85 | 0.00 |
September | 16019.96 | 22-SEP-08:62 | 2227.46 | 4656.09 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.86 |
October | 23548.95 | 26-OCT-08:61 | 2598.70 | 5432.10 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.06 |
November | 16935.26 | 06-NOV-09:02 | 2227.46 | 4656.09 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.83 |
December | 21220.53 | 17-DEC-10:02 | 2227.46 | 4656.09 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12965.68 | 1856.21 | 3880.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23548.95 | 2969.94 | 6208.12 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 118.98 | 241.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17678.86 | 01-JAN-10:02 | 1856.21 | 3880.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.36 |
February | 7225.39 | 28-FEB-09:02 | 1856.21 | 3880.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.76 |
March | 9540.86 | 07-MAR-09:02 | 1856.21 | 3880.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.78 |
April | 17605.60 | 23-APR-09:02 | 1856.21 | 3880.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 8.79 | 0.00 |
May | 17812.43 | 12-MAY-08:62 | 2227.46 | 4656.09 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.99 | 0.00 |
June | 18724.07 | 11-JUN-09:01 | 2969.94 | 6208.12 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 101.61 | 0.00 |
July | 16787.30 | 07-JUL-08:61 | 2969.94 | 6208.12 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 127.55 | 0.00 |
August | 19600.27 | 31-AUG-08:61 | 2969.94 | 6208.12 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 89.65 | 0.00 |
September | 17706.40 | 22-SEP-08:62 | 2227.46 | 4656.09 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.73 |
October | 27221.50 | 26-OCT-08:61 | 2598.70 | 5432.10 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.43 |
November | 19188.52 | 06-NOV-09:02 | 2227.46 | 4656.09 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.70 |
December | 24245.06 | 17-DEC-10:02 | 2227.46 | 4656.09 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 276.71 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7225.39 | 1856.21 | 3880.07 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27221.50 | 2969.94 | 6208.12 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 127.55 | 276.71 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.690705E+11 | 76614.38 | 19-JAN-13:50 | 0.517273E+10 | 90550.88 | 10-JAN-09:09 |
February | 0.648928E+11 | 74148.38 | 02-FEB-13:39 | 0.517454E+10 | 102580.99 | 05-FEB-10:09 |
March | 0.745463E+11 | 76097.67 | 30-MAR-12:50 | 0.370012E+10 | 88523.31 | 11-MAR-12:09 |
April | 0.808319E+11 | 90517.72 | 28-APR-16:19 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.106965E+12 | 96931.42 | 24-MAY-12:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.108483E+12 | 105546.88 | 28-JUN-13:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.114819E+12 | 110224.00 | 22-JUL-15:50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.116409E+12 | 103293.78 | 03-AUG-14:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.106360E+12 | 121668.09 | 10-SEP-12:30 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.102739E+12 | 110554.64 | 07-OCT-12:50 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.773849E+11 | 89091.05 | 02-NOV-13:39 | 980824.19 | 434.26 | 15-NOV-20:00 |
December | 0.737239E+11 | 81861.51 | 15-DEC-13:00 | 0.459536E+10 | 96566.73 | 21-DEC-09:09 |
Annual Sum or Average | 0.109622E+13 | 0.186437E+11 | ||||
Minimum of Months | 0.648928E+11 | 74148.38 | 0.00 | 0.00 | ||
Maximum of Months | 0.116409E+12 | 121668.09 | 0.517454E+10 | 102580.99 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.322876E+11 | 0.691055E+10 | 0.108804E+11 | 0.00 | 0.847794E+10 | 0.00 | 0.00 | 0.557312E+10 | 0.00 | 0.00 | 0.00 | 0.494091E+10 | 0.00 |
February | 0.292229E+11 | 0.591916E+10 | 0.985143E+10 | 0.00 | 0.771890E+10 | 0.00 | 0.00 | 0.772195E+10 | 0.00 | 0.00 | 0.00 | 0.445849E+10 | 0.00 |
March | 0.327448E+11 | 0.606764E+10 | 0.110560E+11 | 0.00 | 0.861986E+10 | 0.00 | 0.00 | 0.111379E+11 | 0.00 | 0.00 | 0.00 | 0.492009E+10 | 0.00 |
April | 0.313156E+11 | 0.540109E+10 | 0.105544E+11 | 0.00 | 0.819735E+10 | 0.00 | 0.00 | 0.207087E+11 | 0.00 | 0.00 | 0.00 | 0.465472E+10 | 0.00 |
May | 0.325099E+11 | 0.515664E+10 | 0.109629E+11 | 0.00 | 0.873122E+10 | 0.00 | 0.00 | 0.448701E+11 | 0.00 | 0.00 | 0.00 | 0.473384E+10 | 0.00 |
June | 0.316492E+11 | 0.475918E+10 | 0.106855E+11 | 0.00 | 0.881152E+10 | 0.00 | 0.00 | 0.480476E+11 | 0.00 | 0.00 | 0.00 | 0.452968E+10 | 0.00 |
July | 0.321889E+11 | 0.503993E+10 | 0.108424E+11 | 0.00 | 0.943965E+10 | 0.00 | 0.00 | 0.526863E+11 | 0.00 | 0.00 | 0.00 | 0.462161E+10 | 0.00 |
August | 0.327323E+11 | 0.538358E+10 | 0.110491E+11 | 0.00 | 0.955093E+10 | 0.00 | 0.00 | 0.530318E+11 | 0.00 | 0.00 | 0.00 | 0.466103E+10 | 0.00 |
September | 0.313281E+11 | 0.567341E+10 | 0.105613E+11 | 0.00 | 0.882376E+10 | 0.00 | 0.00 | 0.454347E+11 | 0.00 | 0.00 | 0.00 | 0.453866E+10 | 0.00 |
October | 0.322876E+11 | 0.635617E+10 | 0.108804E+11 | 0.00 | 0.895217E+10 | 0.00 | 0.00 | 0.395094E+11 | 0.00 | 0.00 | 0.00 | 0.475300E+10 | 0.00 |
November | 0.312780E+11 | 0.656172E+10 | 0.105443E+11 | 0.00 | 0.823075E+10 | 0.00 | 0.00 | 0.160898E+11 | 0.00 | 0.00 | 0.00 | 0.468027E+10 | 0.00 |
December | 0.322014E+11 | 0.701754E+10 | 0.108529E+11 | 0.00 | 0.850067E+10 | 0.00 | 0.00 | 0.102479E+11 | 0.00 | 0.00 | 0.00 | 0.490336E+10 | 0.00 |
Annual Sum or Average | 0.381746E+12 | 0.702466E+11 | 0.128721E+12 | 0.00 | 0.104055E+12 | 0.00 | 0.00 | 0.355059E+12 | 0.00 | 0.00 | 0.00 | 0.563957E+11 | 0.00 |
Minimum of Months | 0.292229E+11 | 0.475918E+10 | 0.985143E+10 | 0.00 | 0.771890E+10 | 0.00 | 0.00 | 0.557312E+10 | 0.00 | 0.00 | 0.00 | 0.445849E+10 | 0.00 |
Maximum of Months | 0.327448E+11 | 0.701754E+10 | 0.110560E+11 | 0.00 | 0.955093E+10 | 0.00 | 0.00 | 0.530318E+11 | 0.00 | 0.00 | 0.00 | 0.494091E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.517273E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.517454E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.370012E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 980824.19 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.459536E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.186437E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.517454E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 23650.28 | 01-JAN-11:09 | 5403.30 | 01-JAN-06:10 | 8089.53 | 01-JAN-11:09 | 0.00 | 7531.46 | 10-JAN-09:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 23650.28 | 01-FEB-10:09 | 5403.30 | 01-FEB-06:10 | 8089.53 | 01-FEB-10:09 | 0.00 | 7771.18 | 05-FEB-10:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 23650.28 | 01-MAR-10:09 | 5403.30 | 01-MAR-06:10 | 8089.53 | 01-MAR-10:09 | 0.00 | 7494.19 | 11-MAR-12:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 23650.28 | 01-APR-09:09 | 5403.30 | 01-APR-05:10 | 8089.53 | 01-APR-09:09 | 0.00 | 7491.12 | 29-APR-08:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 23650.28 | 01-MAY-09:09 | 5403.30 | 01-MAY-05:10 | 8089.53 | 01-MAY-09:09 | 0.00 | 8314.68 | 22-MAY-08:09 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 23650.28 | 01-JUN-09:09 | 5403.30 | 01-JUN-05:10 | 8089.53 | 01-JUN-09:09 | 0.00 | 8913.78 | 19-JUN-08:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 23650.28 | 01-JUL-09:09 | 5403.30 | 01-JUL-05:10 | 8089.53 | 01-JUL-09:09 | 0.00 | 10045.04 | 22-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 23650.28 | 01-AUG-09:09 | 5403.30 | 01-AUG-05:10 | 8089.53 | 01-AUG-09:09 | 0.00 | 9203.55 | 14-AUG-08:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 23650.28 | 01-SEP-09:09 | 5403.30 | 01-SEP-05:10 | 8089.53 | 01-SEP-09:09 | 0.00 | 11597.37 | 10-SEP-12:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 23650.28 | 01-OCT-10:09 | 5403.30 | 01-OCT-05:10 | 8089.53 | 01-OCT-10:09 | 0.00 | 10313.28 | 07-OCT-12:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 23650.28 | 01-NOV-09:09 | 5403.30 | 01-NOV-05:10 | 8089.53 | 01-NOV-09:09 | 0.00 | 7555.84 | 02-NOV-08:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 23650.28 | 01-DEC-10:09 | 5403.30 | 01-DEC-06:10 | 8089.53 | 01-DEC-10:09 | 0.00 | 7649.63 | 21-DEC-09:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 23650.28 | 5403.30 | 8089.53 | 0.00 | 7491.12 | 0.00 | 0.00 | |||||
Maximum of Months | 23650.28 | 5403.30 | 8089.53 | 0.00 | 11597.37 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 30065.65 | 19-JAN-13:00 | 0.00 | 0.00 | 0.00 | 9863.70 | 04-JAN-13:30 | 0.00 |
February | 32280.54 | 24-FEB-13:09 | 0.00 | 0.00 | 0.00 | 9689.86 | 03-FEB-13:50 | 0.00 |
March | 35711.17 | 30-MAR-12:00 | 0.00 | 0.00 | 0.00 | 9653.42 | 13-MAR-11:39 | 0.00 |
April | 48577.63 | 28-APR-16:10 | 0.00 | 0.00 | 0.00 | 7557.61 | 17-APR-12:30 | 0.00 |
May | 52190.38 | 30-MAY-12:00 | 0.00 | 0.00 | 0.00 | 7553.49 | 06-MAY-12:00 | 0.00 |
June | 58348.78 | 28-JUN-13:00 | 0.00 | 0.00 | 0.00 | 7546.41 | 13-JUN-12:39 | 0.00 |
July | 66121.51 | 22-JUL-15:00 | 0.00 | 0.00 | 0.00 | 7544.27 | 01-JUL-12:00 | 0.00 |
August | 58714.66 | 28-AUG-12:00 | 0.00 | 0.00 | 0.00 | 7545.67 | 30-AUG-12:20 | 0.00 |
September | 72997.86 | 10-SEP-13:30 | 0.00 | 0.00 | 0.00 | 8078.37 | 23-SEP-11:00 | 0.00 |
October | 64778.47 | 07-OCT-12:00 | 0.00 | 0.00 | 0.00 | 7557.16 | 28-OCT-12:30 | 0.00 |
November | 46454.35 | 02-NOV-12:00 | 0.00 | 0.00 | 0.00 | 8133.30 | 18-NOV-14:20 | 0.00 |
December | 38926.41 | 15-DEC-13:00 | 0.00 | 0.00 | 0.00 | 7552.33 | 09-DEC-13:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 30065.65 | 0.00 | 0.00 | 0.00 | 7544.27 | 0.00 | ||
Maximum of Months | 72997.86 | 0.00 | 0.00 | 0.00 | 9863.70 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 76614.38 | 19-JAN-13:50 | 23650.28 | 8089.53 | 0.00 | 0.00 | 5745.08 | 0.00 | 0.00 | 29951.31 | 0.00 |
February | 74148.38 | 02-FEB-13:39 | 23650.28 | 8089.53 | 0.00 | 0.00 | 5745.08 | 0.00 | 0.00 | 31211.62 | 0.00 |
March | 76097.67 | 30-MAR-12:50 | 23650.28 | 8089.53 | 0.00 | 0.00 | 5745.08 | 0.00 | 0.00 | 35280.22 | 0.00 |
April | 90517.72 | 28-APR-16:19 | 23650.28 | 8089.53 | 0.00 | 0.00 | 7118.00 | 0.00 | 0.00 | 48335.30 | 0.00 |
May | 96931.42 | 24-MAY-12:00 | 23650.28 | 8089.53 | 0.00 | 0.00 | 7744.33 | 0.00 | 0.00 | 52008.08 | 0.00 |
June | 105546.88 | 28-JUN-13:00 | 23650.28 | 8089.53 | 0.00 | 0.00 | 8865.92 | 0.00 | 0.00 | 58348.78 | 0.00 |
July | 110224.00 | 22-JUL-15:50 | 23650.28 | 8089.53 | 0.00 | 0.00 | 9907.45 | 0.00 | 0.00 | 65256.15 | 0.00 |
August | 103293.78 | 03-AUG-14:00 | 23650.28 | 8089.53 | 0.00 | 0.00 | 8780.49 | 0.00 | 0.00 | 58705.61 | 0.00 |
September | 121668.09 | 10-SEP-12:30 | 23650.28 | 8089.53 | 0.00 | 0.00 | 11571.19 | 0.00 | 0.00 | 72942.30 | 0.00 |
October | 110554.64 | 07-OCT-12:50 | 23650.28 | 8089.53 | 0.00 | 0.00 | 10069.50 | 0.00 | 0.00 | 63305.72 | 0.00 |
November | 89091.05 | 02-NOV-13:39 | 23650.28 | 8089.53 | 0.00 | 0.00 | 6736.35 | 0.00 | 0.00 | 45171.05 | 0.00 |
December | 81861.51 | 15-DEC-13:00 | 23650.28 | 8089.53 | 0.00 | 0.00 | 5745.08 | 0.00 | 0.00 | 38926.41 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 74148.38 | 23650.28 | 8089.53 | 0.00 | 0.00 | 5745.08 | 0.00 | 0.00 | 29951.31 | 0.00 | |
Maximum of Months | 121668.09 | 23650.28 | 8089.53 | 0.00 | 0.00 | 11571.19 | 0.00 | 0.00 | 72942.30 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 90550.88 | 10-JAN-09:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 102580.99 | 05-FEB-10:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 88523.31 | 11-MAR-12:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 434.26 | 15-NOV-20:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 96566.73 | 21-DEC-09:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 102580.99 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.46 | 0.17 | 24.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.46 | 0.33 | 24.46 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.49 | 0.17 | 24.49 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.52 | 0.33 | 24.52 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.00 | 24.48 | 1.00 | 24.48 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.52 | 0.33 | 24.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.45 | 0.17 | 24.45 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.49 | 1.33 | 24.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.50 | 0.83 | 24.50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.49 | 0.67 | 24.49 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.46 | 0.50 | 24.46 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.50 | 24.49 | 3.50 | 24.49 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.50 | 1.33 | 24.50 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.48 | 0.17 | 24.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.49 | 1.50 | 24.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.49 | 0.83 | 24.49 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.54 | 0.33 | 24.54 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.46 | 0.33 | 24.46 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.17 | 24.49 | 3.17 | 24.49 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.54 | 1.50 | 24.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.45 | 0.17 | 24.45 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.49 | 1.50 | 24.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.51 | 0.67 | 24.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.49 | 0.67 | 24.49 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.46 | 0.33 | 24.46 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.33 | 24.49 | 3.33 | 24.49 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.51 | 1.50 | 24.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.49 | 0.17 | 24.49 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.52 | 0.83 | 24.52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.58 | 2.00 | 24.58 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.58 | 1.17 | 24.58 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.56 | 1.50 | 24.56 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.53 | 0.67 | 24.53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 6.33 | 24.56 | 6.33 | 24.56 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.58 | 2.00 | 24.58 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.45 | 0.17 | 24.45 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.50 | 0.50 | 24.50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.56 | 2.00 | 24.56 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.58 | 1.00 | 24.58 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.53 | 1.33 | 24.53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.54 | 0.33 | 24.54 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 5.33 | 24.54 | 5.33 | 24.54 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.58 | 2.00 | 24.58 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.45 | 0.17 | 24.45 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.49 | 0.50 | 24.49 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.57 | 1.83 | 24.57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.58 | 1.00 | 24.58 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.54 | 1.17 | 24.54 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.53 | 0.33 | 24.53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 5.00 | 24.55 | 5.00 | 24.55 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.58 | 1.83 | 24.58 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.48 | 0.33 | 24.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.56 | 1.83 | 24.56 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.57 | 1.00 | 24.57 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.54 | 1.17 | 24.54 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.53 | 0.33 | 24.53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.67 | 24.55 | 4.67 | 24.55 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.57 | 1.83 | 24.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.51 | 1.83 | 24.51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.54 | 0.67 | 24.54 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.51 | 1.00 | 24.51 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.48 | 0.50 | 24.48 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.00 | 24.51 | 4.00 | 24.51 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.54 | 1.83 | 24.54 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 346.17 | 22.07 | 159.67 | 22.58 | 46.00 | 22.63 |
February | 275.17 | 22.59 | 223.83 | 23.10 | 80.00 | 23.15 |
March | 256.50 | 22.61 | 219.50 | 23.15 | 57.33 | 23.19 |
April | 95.50 | 23.73 | 361.50 | 23.87 | 58.83 | 23.87 |
May | 135.17 | 24.10 | 496.00 | 23.99 | 135.17 | 24.01 |
June | 131.50 | 24.11 | 481.00 | 24.00 | 131.50 | 24.02 |
July | 248.17 | 24.05 | 495.00 | 24.00 | 248.17 | 24.01 |
August | 156.33 | 24.18 | 497.00 | 24.03 | 156.33 | 24.06 |
September | 181.50 | 24.08 | 479.00 | 23.99 | 181.50 | 24.01 |
October | 124.17 | 23.98 | 449.33 | 23.96 | 114.33 | 23.97 |
November | 113.83 | 23.52 | 312.67 | 23.82 | 47.33 | 23.84 |
December | 248.50 | 22.43 | 217.17 | 23.09 | 44.17 | 23.15 |
Annual Sum or Average | 2312.50 | 23.22 | 4391.67 | 23.68 | 1300.67 | 23.73 |
Minimum of Months | 95.50 | 22.07 | 159.67 | 22.58 | 44.17 | 22.63 |
Maximum of Months | 346.17 | 24.18 | 497.00 | 24.03 | 248.17 | 24.06 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 292.83 | 22.67 | 150.00 | 23.08 | 20.67 | 23.12 |
February | 200.33 | 22.89 | 213.50 | 23.40 | 36.83 | 23.43 |
March | 182.00 | 22.86 | 208.00 | 23.42 | 12.67 | 23.44 |
April | 38.00 | 23.73 | 336.83 | 23.89 | 15.67 | 23.89 |
May | 65.83 | 23.94 | 492.83 | 23.97 | 65.83 | 23.96 |
June | 65.17 | 23.89 | 479.17 | 23.96 | 65.17 | 23.96 |
July | 154.83 | 23.92 | 494.83 | 23.96 | 154.83 | 23.95 |
August | 91.50 | 23.96 | 496.00 | 23.98 | 91.50 | 23.98 |
September | 116.67 | 23.93 | 476.67 | 23.96 | 116.67 | 23.95 |
October | 86.17 | 23.87 | 436.33 | 23.95 | 77.50 | 23.94 |
November | 69.17 | 23.67 | 307.83 | 23.89 | 27.17 | 23.89 |
December | 190.33 | 22.73 | 218.67 | 23.36 | 23.50 | 23.38 |
Annual Sum or Average | 1552.83 | 23.27 | 4310.67 | 23.77 | 708.00 | 23.78 |
Minimum of Months | 38.00 | 22.67 | 150.00 | 23.08 | 12.67 | 23.12 |
Maximum of Months | 292.83 | 23.96 | 496.00 | 23.98 | 154.83 | 23.98 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 249.83 | 22.23 | 118.00 | 22.76 | 27.67 | 22.82 |
February | 176.67 | 22.61 | 165.50 | 23.22 | 38.50 | 23.27 |
March | 171.00 | 22.66 | 162.33 | 23.30 | 26.50 | 23.36 |
April | 69.17 | 23.89 | 274.33 | 23.99 | 47.83 | 24.00 |
May | 114.67 | 24.30 | 375.00 | 24.13 | 114.67 | 24.16 |
June | 122.33 | 24.36 | 366.00 | 24.16 | 122.33 | 24.20 |
July | 220.83 | 24.22 | 369.00 | 24.15 | 220.83 | 24.17 |
August | 149.67 | 24.28 | 379.00 | 24.15 | 149.67 | 24.18 |
September | 178.00 | 24.22 | 360.00 | 24.13 | 178.00 | 24.15 |
October | 110.50 | 24.18 | 335.00 | 24.10 | 104.67 | 24.13 |
November | 81.67 | 23.71 | 240.83 | 23.92 | 45.17 | 23.94 |
December | 185.50 | 22.54 | 163.50 | 23.20 | 40.33 | 23.28 |
Annual Sum or Average | 1829.83 | 23.46 | 3308.50 | 23.84 | 1116.17 | 23.90 |
Minimum of Months | 69.17 | 22.23 | 118.00 | 22.76 | 26.50 | 22.82 |
Maximum of Months | 249.83 | 24.36 | 379.00 | 24.16 | 220.83 | 24.20 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 254.67 | 22.19 | 116.83 | 22.71 | 29.33 | 22.77 |
February | 183.50 | 22.58 | 165.33 | 23.19 | 39.83 | 23.23 |
March | 177.67 | 22.65 | 159.67 | 23.28 | 27.67 | 23.33 |
April | 70.17 | 23.88 | 272.50 | 23.99 | 47.83 | 24.00 |
May | 113.00 | 24.31 | 375.00 | 24.13 | 113.00 | 24.17 |
June | 120.33 | 24.37 | 366.00 | 24.16 | 120.33 | 24.20 |
July | 216.33 | 24.23 | 369.00 | 24.15 | 216.33 | 24.17 |
August | 146.33 | 24.29 | 379.00 | 24.15 | 146.33 | 24.18 |
September | 174.00 | 24.22 | 360.00 | 24.13 | 174.00 | 24.15 |
October | 110.00 | 24.19 | 335.33 | 24.11 | 104.00 | 24.13 |
November | 84.33 | 23.69 | 235.17 | 23.91 | 45.50 | 23.94 |
December | 192.33 | 22.54 | 160.17 | 23.17 | 40.50 | 23.25 |
Annual Sum or Average | 1842.67 | 23.43 | 3294.00 | 23.82 | 1104.67 | 23.89 |
Minimum of Months | 70.17 | 22.19 | 116.83 | 22.71 | 27.67 | 22.77 |
Maximum of Months | 254.67 | 24.37 | 379.00 | 24.16 | 216.33 | 24.20 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 268.67 | 22.17 | 115.17 | 22.66 | 35.33 | 22.74 |
February | 193.50 | 22.54 | 164.83 | 23.13 | 43.50 | 23.18 |
March | 191.17 | 22.64 | 152.67 | 23.22 | 31.00 | 23.28 |
April | 78.33 | 23.86 | 270.17 | 23.97 | 51.33 | 23.99 |
May | 119.00 | 24.28 | 375.00 | 24.13 | 119.00 | 24.16 |
June | 127.17 | 24.34 | 366.00 | 24.15 | 127.17 | 24.19 |
July | 224.00 | 24.21 | 369.00 | 24.14 | 224.00 | 24.16 |
August | 152.33 | 24.27 | 379.00 | 24.14 | 152.33 | 24.17 |
September | 183.33 | 24.21 | 360.00 | 24.12 | 183.33 | 24.14 |
October | 112.50 | 24.16 | 334.00 | 24.10 | 106.00 | 24.12 |
November | 92.50 | 23.65 | 225.33 | 23.89 | 48.83 | 23.92 |
December | 203.67 | 22.53 | 156.83 | 23.14 | 42.83 | 23.22 |
Annual Sum or Average | 1946.17 | 23.41 | 3268.00 | 23.80 | 1164.67 | 23.87 |
Minimum of Months | 78.33 | 22.17 | 115.17 | 22.66 | 31.00 | 22.74 |
Maximum of Months | 268.67 | 24.34 | 379.00 | 24.15 | 224.00 | 24.19 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 266.83 | 22.16 | 96.33 | 22.58 | 43.17 | 22.68 |
February | 195.50 | 22.51 | 149.00 | 23.05 | 48.67 | 23.09 |
March | 213.83 | 22.73 | 132.00 | 23.17 | 46.33 | 23.24 |
April | 95.50 | 23.81 | 239.17 | 23.90 | 59.67 | 23.91 |
May | 124.50 | 24.06 | 344.00 | 23.99 | 124.50 | 24.00 |
June | 152.17 | 24.03 | 336.00 | 23.99 | 152.17 | 24.00 |
July | 249.33 | 24.03 | 338.00 | 24.01 | 249.33 | 24.01 |
August | 193.33 | 24.00 | 348.00 | 23.97 | 193.33 | 23.98 |
September | 229.83 | 24.02 | 330.00 | 24.00 | 229.83 | 24.01 |
October | 123.00 | 24.01 | 304.83 | 23.98 | 115.67 | 24.00 |
November | 112.67 | 23.60 | 195.50 | 23.80 | 61.00 | 23.83 |
December | 208.33 | 22.53 | 138.00 | 23.06 | 49.33 | 23.15 |
Annual Sum or Average | 2164.83 | 23.35 | 2950.83 | 23.69 | 1373.00 | 23.75 |
Minimum of Months | 95.50 | 22.16 | 96.33 | 22.58 | 43.17 | 22.68 |
Maximum of Months | 266.83 | 24.06 | 348.00 | 24.01 | 249.33 | 24.01 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 274.33 | 22.17 | 93.00 | 22.56 | 45.67 | 22.66 |
February | 199.50 | 22.49 | 149.17 | 23.02 | 51.83 | 23.06 |
March | 223.67 | 22.74 | 130.67 | 23.15 | 50.83 | 23.23 |
April | 102.67 | 23.81 | 235.17 | 23.89 | 61.50 | 23.91 |
May | 124.33 | 24.06 | 344.00 | 23.99 | 124.33 | 24.00 |
June | 154.50 | 24.03 | 336.00 | 23.98 | 154.50 | 23.99 |
July | 251.83 | 24.02 | 338.00 | 24.00 | 251.83 | 24.01 |
August | 198.00 | 23.99 | 348.00 | 23.97 | 198.00 | 23.98 |
September | 234.83 | 24.02 | 330.00 | 24.00 | 234.83 | 24.00 |
October | 125.67 | 24.01 | 300.17 | 23.98 | 116.17 | 24.00 |
November | 121.83 | 23.61 | 181.33 | 23.80 | 62.50 | 23.82 |
December | 216.17 | 22.55 | 133.83 | 23.05 | 50.33 | 23.13 |
Annual Sum or Average | 2227.33 | 23.35 | 2919.33 | 23.68 | 1402.33 | 23.74 |
Minimum of Months | 102.67 | 22.17 | 93.00 | 22.56 | 45.67 | 22.66 |
Maximum of Months | 274.33 | 24.06 | 348.00 | 24.00 | 251.83 | 24.01 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 278.00 | 22.16 | 92.50 | 22.54 | 47.83 | 22.65 |
February | 203.33 | 22.48 | 148.50 | 23.00 | 54.50 | 23.04 |
March | 228.67 | 22.73 | 130.17 | 23.14 | 53.17 | 23.22 |
April | 105.33 | 23.80 | 234.50 | 23.89 | 62.50 | 23.90 |
May | 127.83 | 24.05 | 344.00 | 23.99 | 127.83 | 24.00 |
June | 156.83 | 24.02 | 336.00 | 23.98 | 156.83 | 23.99 |
July | 252.83 | 24.02 | 338.00 | 24.00 | 252.83 | 24.01 |
August | 203.17 | 23.99 | 348.00 | 23.97 | 203.17 | 23.97 |
September | 237.67 | 24.01 | 330.00 | 23.99 | 237.67 | 24.00 |
October | 126.33 | 24.00 | 299.67 | 23.98 | 116.17 | 23.99 |
November | 126.17 | 23.60 | 178.17 | 23.79 | 63.33 | 23.81 |
December | 223.17 | 22.55 | 132.50 | 23.03 | 51.17 | 23.12 |
Annual Sum or Average | 2269.33 | 23.34 | 2912.00 | 23.67 | 1427.00 | 23.73 |
Minimum of Months | 105.33 | 22.16 | 92.50 | 22.54 | 47.83 | 22.65 |
Maximum of Months | 278.00 | 24.05 | 348.00 | 24.00 | 252.83 | 24.01 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 282.67 | 22.13 | 92.67 | 22.51 | 50.67 | 22.61 |
February | 209.50 | 22.44 | 148.83 | 22.94 | 60.00 | 22.99 |
March | 236.17 | 22.70 | 130.00 | 23.10 | 58.17 | 23.18 |
April | 112.67 | 23.77 | 232.33 | 23.87 | 65.67 | 23.89 |
May | 129.00 | 24.05 | 344.00 | 23.99 | 129.00 | 24.00 |
June | 156.83 | 24.02 | 336.00 | 23.98 | 156.83 | 23.99 |
July | 251.67 | 24.02 | 338.00 | 24.00 | 251.67 | 24.01 |
August | 197.83 | 23.99 | 348.00 | 23.97 | 197.83 | 23.98 |
September | 236.33 | 24.02 | 330.00 | 24.00 | 236.33 | 24.00 |
October | 127.83 | 24.00 | 299.17 | 23.98 | 116.17 | 23.99 |
November | 130.50 | 23.57 | 173.33 | 23.77 | 63.67 | 23.80 |
December | 231.83 | 22.53 | 130.17 | 23.00 | 52.83 | 23.08 |
Annual Sum or Average | 2302.83 | 23.32 | 2902.50 | 23.66 | 1438.83 | 23.72 |
Minimum of Months | 112.67 | 22.13 | 92.67 | 22.51 | 50.67 | 22.61 |
Maximum of Months | 282.67 | 24.05 | 348.00 | 24.00 | 251.67 | 24.01 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 282.33 | 22.08 | 99.67 | 22.44 | 54.83 | 22.53 |
February | 216.17 | 22.37 | 155.83 | 22.85 | 70.33 | 22.87 |
March | 233.00 | 22.59 | 140.17 | 22.99 | 61.00 | 23.03 |
April | 116.00 | 23.69 | 228.33 | 23.85 | 66.00 | 23.86 |
May | 119.67 | 24.07 | 344.00 | 23.99 | 119.67 | 24.01 |
June | 121.33 | 24.08 | 336.00 | 24.00 | 121.33 | 24.01 |
July | 202.17 | 24.07 | 338.00 | 24.02 | 202.17 | 24.03 |
August | 147.33 | 24.04 | 348.00 | 23.99 | 147.33 | 24.00 |
September | 188.17 | 24.06 | 330.00 | 24.01 | 188.17 | 24.03 |
October | 117.50 | 24.00 | 300.67 | 23.98 | 105.33 | 24.00 |
November | 126.67 | 23.50 | 178.67 | 23.75 | 55.83 | 23.78 |
December | 235.50 | 22.46 | 136.33 | 22.92 | 56.33 | 22.98 |
Annual Sum or Average | 2105.83 | 23.22 | 2935.67 | 23.62 | 1248.33 | 23.67 |
Minimum of Months | 116.00 | 22.08 | 99.67 | 22.44 | 54.83 | 22.53 |
Maximum of Months | 282.33 | 24.08 | 348.00 | 24.02 | 202.17 | 24.03 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 22.61637 | 44.24007 | 0.09301 | 8.00224 |
February | 448.00000 | 23.08280 | 48.04056 | 0.23216 | 9.04558 |
March | 497.00000 | 23.22371 | 46.57477 | 0.25277 | 8.81782 |
April | 479.00000 | 23.85844 | 53.31409 | 0.48900 | 10.35402 |
May | 496.00000 | 23.96009 | 61.46874 | -0.2293 | 6.22074 |
June | 481.00000 | 23.96761 | 61.25145 | -0.2058 | 6.05497 |
July | 495.00000 | 23.97149 | 64.95973 | -0.1666 | 5.77793 |
August | 497.00000 | 23.98584 | 62.88748 | -0.1628 | 5.78140 |
September | 479.00000 | 23.96218 | 63.75267 | -0.1803 | 5.88065 |
October | 496.00000 | 23.93934 | 56.25240 | 0.60008 | 12.90846 |
November | 480.00000 | 23.80919 | 48.18299 | 0.45276 | 9.93696 |
December | 496.00000 | 23.14815 | 46.11953 | 0.25220 | 8.85882 |
Annual Sum or Average | 5840.00000 | 23.62849 | 54.78644 | 0.11774 | 8.12980 |
Minimum of Months | 448.00000 | 22.61637 | 44.24007 | -0.2293 | 5.77793 |
Maximum of Months | 497.00000 | 23.98584 | 64.95973 | 0.60008 | 12.90846 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 23.16680 | 42.94038 | 0.20923 | 7.66882 |
February | 448.00000 | 23.43414 | 46.49943 | 0.30658 | 8.76916 |
March | 497.00000 | 23.51158 | 44.46520 | 0.31149 | 8.46935 |
April | 479.00000 | 23.88407 | 50.11911 | 0.47700 | 10.00089 |
May | 496.00000 | 23.96806 | 57.47348 | -0.2648 | 6.62954 |
June | 481.00000 | 23.97374 | 57.57664 | -0.2464 | 6.47333 |
July | 495.00000 | 23.97439 | 61.16861 | -0.2114 | 6.15922 |
August | 497.00000 | 23.98792 | 59.55344 | -0.2120 | 6.18758 |
September | 479.00000 | 23.96514 | 60.05029 | -0.2263 | 6.30471 |
October | 496.00000 | 23.94528 | 53.23321 | 0.56780 | 12.06912 |
November | 480.00000 | 23.87921 | 46.36535 | 0.45689 | 9.75268 |
December | 496.00000 | 23.45198 | 44.64957 | 0.31261 | 8.64225 |
Annual Sum or Average | 5840.00000 | 23.76270 | 52.03484 | 0.12194 | 8.08768 |
Minimum of Months | 448.00000 | 23.16680 | 42.94038 | -0.2648 | 6.15922 |
Maximum of Months | 497.00000 | 23.98792 | 61.16861 | 0.56780 | 12.06912 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 22.77809 | 42.24201 | 0.13101 | 7.84159 |
February | 336.00000 | 23.22533 | 46.79834 | 0.27159 | 9.04972 |
March | 379.00000 | 23.34668 | 45.14460 | 0.28464 | 8.84812 |
April | 360.00000 | 23.95138 | 52.46061 | 0.50905 | 10.84339 |
May | 375.00000 | 24.07937 | 61.33576 | -0.1977 | 6.22698 |
June | 366.00000 | 24.09419 | 61.54353 | -0.1743 | 6.13645 |
July | 369.00000 | 24.10599 | 65.63371 | -0.1314 | 5.90825 |
August | 379.00000 | 24.09220 | 63.75170 | -0.1415 | 5.88473 |
September | 360.00000 | 24.08012 | 64.51700 | -0.1519 | 5.96906 |
October | 371.00000 | 24.05013 | 56.25163 | 0.61988 | 13.57854 |
November | 360.00000 | 23.87975 | 47.52847 | 0.47145 | 10.24881 |
December | 369.00000 | 23.22627 | 45.27065 | 0.27640 | 8.97442 |
Annual Sum or Average | 4395.00000 | 23.74476 | 54.42749 | 0.14515 | 8.27899 |
Minimum of Months | 336.00000 | 22.77809 | 42.24201 | -0.1977 | 5.88473 |
Maximum of Months | 379.00000 | 24.10599 | 65.63371 | 0.61988 | 13.57854 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 22.72355 | 42.42690 | 0.11369 | 7.83276 |
February | 336.00000 | 23.18634 | 46.96454 | 0.25829 | 8.98790 |
March | 379.00000 | 23.32120 | 45.24835 | 0.27522 | 8.82096 |
April | 360.00000 | 23.94792 | 52.48810 | 0.50707 | 10.81269 |
May | 375.00000 | 24.07975 | 61.27467 | -0.1964 | 6.21894 |
June | 366.00000 | 24.09482 | 61.46317 | -0.1726 | 6.12764 |
July | 369.00000 | 24.10673 | 65.50942 | -0.1292 | 5.90258 |
August | 379.00000 | 24.09278 | 63.65372 | -0.1397 | 5.87829 |
September | 360.00000 | 24.08070 | 64.41491 | -0.1502 | 5.96378 |
October | 371.00000 | 24.05038 | 56.18537 | 0.62071 | 13.60411 |
November | 360.00000 | 23.87327 | 47.57615 | 0.46840 | 10.20933 |
December | 369.00000 | 23.19565 | 45.36028 | 0.26595 | 8.94067 |
Annual Sum or Average | 4395.00000 | 23.73186 | 54.43369 | 0.14139 | 8.26187 |
Minimum of Months | 336.00000 | 22.72355 | 42.42690 | -0.1964 | 5.87829 |
Maximum of Months | 379.00000 | 24.10673 | 65.50942 | 0.62071 | 13.60411 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 22.64828 | 42.76876 | 0.09100 | 7.82760 |
February | 336.00000 | 23.12379 | 47.29120 | 0.23810 | 8.88075 |
March | 379.00000 | 23.27124 | 45.52128 | 0.25811 | 8.74077 |
April | 360.00000 | 23.93676 | 52.74745 | 0.50048 | 10.69411 |
May | 375.00000 | 24.07605 | 61.52587 | -0.2011 | 6.24344 |
June | 366.00000 | 24.09128 | 61.69604 | -0.1770 | 6.14345 |
July | 369.00000 | 24.10369 | 65.74470 | -0.1327 | 5.90532 |
August | 379.00000 | 24.08956 | 63.88578 | -0.1434 | 5.88421 |
September | 360.00000 | 24.07744 | 64.65955 | -0.1538 | 5.97512 |
October | 371.00000 | 24.04557 | 56.38227 | 0.61752 | 13.52409 |
November | 360.00000 | 23.85615 | 47.78223 | 0.46062 | 10.09759 |
December | 369.00000 | 23.14614 | 45.59103 | 0.24964 | 8.86919 |
Annual Sum or Average | 4395.00000 | 23.70812 | 54.68581 | 0.13194 | 8.21978 |
Minimum of Months | 336.00000 | 22.64828 | 42.76876 | -0.2011 | 5.88421 |
Maximum of Months | 379.00000 | 24.10369 | 65.74470 | 0.61752 | 13.52409 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.53476 | 44.38070 | 0.05401 | 7.77445 |
February | 308.00000 | 23.01634 | 48.88916 | 0.20253 | 8.59952 |
March | 348.00000 | 23.17966 | 47.12100 | 0.22598 | 8.50619 |
April | 330.00000 | 23.87568 | 53.97835 | 0.47944 | 10.23228 |
May | 344.00000 | 23.96262 | 63.05643 | -0.2352 | 6.38413 |
June | 336.00000 | 23.96403 | 63.12348 | -0.2130 | 6.21723 |
July | 338.00000 | 23.99066 | 67.28096 | -0.1626 | 5.91201 |
August | 348.00000 | 23.95852 | 65.35031 | -0.1772 | 5.89114 |
September | 330.00000 | 23.98203 | 66.31969 | -0.1786 | 6.05983 |
October | 340.00000 | 23.94815 | 57.81258 | 0.60101 | 13.02811 |
November | 330.00000 | 23.79741 | 49.10250 | 0.44169 | 9.73243 |
December | 338.00000 | 23.04718 | 47.07689 | 0.21858 | 8.66729 |
Annual Sum or Average | 4030.00000 | 23.60728 | 56.17857 | 0.10261 | 8.07266 |
Minimum of Months | 308.00000 | 22.53476 | 44.38070 | -0.2352 | 5.89114 |
Maximum of Months | 348.00000 | 23.99066 | 67.28096 | 0.60101 | 13.02811 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.50054 | 44.43240 | 0.03596 | 7.76527 |
February | 308.00000 | 22.98657 | 48.96248 | 0.18501 | 8.50118 |
March | 348.00000 | 23.15789 | 47.16587 | 0.21029 | 8.38973 |
April | 330.00000 | 23.87333 | 54.02393 | 0.46660 | 9.97495 |
May | 344.00000 | 23.96134 | 63.13385 | -0.2575 | 6.60909 |
June | 336.00000 | 23.96224 | 63.21793 | -0.2369 | 6.43457 |
July | 338.00000 | 23.98899 | 67.44447 | -0.1864 | 6.07789 |
August | 348.00000 | 23.95715 | 65.49332 | -0.2020 | 6.08210 |
September | 330.00000 | 23.98050 | 66.50500 | -0.2017 | 6.23122 |
October | 340.00000 | 23.94718 | 57.91536 | 0.58437 | 12.60105 |
November | 330.00000 | 23.79329 | 49.13994 | 0.42834 | 9.49267 |
December | 338.00000 | 23.02854 | 47.08871 | 0.20299 | 8.53833 |
Annual Sum or Average | 4030.00000 | 23.59742 | 56.26459 | 0.08361 | 8.04852 |
Minimum of Months | 308.00000 | 22.50054 | 44.43240 | -0.2575 | 6.07789 |
Maximum of Months | 348.00000 | 23.98899 | 67.44447 | 0.58437 | 12.60105 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.47549 | 44.53602 | 0.02688 | 7.78273 |
February | 308.00000 | 22.96106 | 49.10760 | 0.17592 | 8.48346 |
March | 348.00000 | 23.13841 | 47.27658 | 0.20277 | 8.36780 |
April | 330.00000 | 23.86899 | 54.13387 | 0.46343 | 9.92588 |
May | 344.00000 | 23.96089 | 63.23435 | -0.2598 | 6.63158 |
June | 336.00000 | 23.96183 | 63.31044 | -0.2391 | 6.45395 |
July | 338.00000 | 23.98858 | 67.53643 | -0.1883 | 6.08963 |
August | 348.00000 | 23.95685 | 65.57653 | -0.2038 | 6.09541 |
September | 330.00000 | 23.98010 | 66.59685 | -0.2036 | 6.24436 |
October | 340.00000 | 23.94592 | 57.99628 | 0.58269 | 12.56286 |
November | 330.00000 | 23.78602 | 49.23156 | 0.42461 | 9.44764 |
December | 338.00000 | 23.00673 | 47.19221 | 0.19522 | 8.51594 |
Annual Sum or Average | 4030.00000 | 23.58862 | 56.36471 | 0.07931 | 8.04069 |
Minimum of Months | 308.00000 | 22.47549 | 44.53602 | -0.2598 | 6.08963 |
Maximum of Months | 348.00000 | 23.98858 | 67.53643 | 0.58269 | 12.56286 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.42713 | 44.72880 | 0.01010 | 7.85155 |
February | 308.00000 | 22.90700 | 49.39532 | 0.15789 | 8.48883 |
March | 348.00000 | 23.09511 | 47.49391 | 0.18745 | 8.36433 |
April | 330.00000 | 23.85510 | 54.34564 | 0.45726 | 9.85252 |
May | 344.00000 | 23.96038 | 63.30144 | -0.2591 | 6.62295 |
June | 336.00000 | 23.96159 | 63.31983 | -0.2372 | 6.43692 |
July | 338.00000 | 23.98867 | 67.48854 | -0.1851 | 6.06882 |
August | 348.00000 | 23.95700 | 65.50066 | -0.2001 | 6.06783 |
September | 330.00000 | 23.98026 | 66.56221 | -0.2007 | 6.22676 |
October | 340.00000 | 23.94342 | 58.00634 | 0.58299 | 12.58777 |
November | 330.00000 | 23.76869 | 49.36107 | 0.41848 | 9.39925 |
December | 338.00000 | 22.95873 | 47.38967 | 0.17982 | 8.51550 |
Annual Sum or Average | 4030.00000 | 23.56985 | 56.46019 | 0.07394 | 8.03098 |
Minimum of Months | 308.00000 | 22.42713 | 44.72880 | -0.2591 | 6.06783 |
Maximum of Months | 348.00000 | 23.98867 | 67.48854 | 0.58299 | 12.58777 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.39206 | 44.65073 | -0.0108 | 8.12479 |
February | 308.00000 | 22.83181 | 49.49496 | 0.12900 | 8.66806 |
March | 348.00000 | 23.03323 | 47.42381 | 0.16386 | 8.58386 |
April | 330.00000 | 23.82705 | 54.36063 | 0.45429 | 9.93130 |
May | 344.00000 | 23.96374 | 62.73327 | -0.2261 | 6.32051 |
June | 336.00000 | 23.96602 | 62.37002 | -0.1963 | 6.10973 |
July | 338.00000 | 23.99606 | 66.26130 | -0.1392 | 5.83484 |
August | 348.00000 | 23.96331 | 64.30727 | -0.1504 | 5.76322 |
September | 330.00000 | 23.98781 | 65.54377 | -0.1589 | 6.00599 |
October | 340.00000 | 23.94074 | 57.28374 | 0.60501 | 13.26135 |
November | 330.00000 | 23.74740 | 49.10068 | 0.41793 | 9.55077 |
December | 338.00000 | 22.89826 | 47.43858 | 0.15684 | 8.73420 |
Annual Sum or Average | 4030.00000 | 23.54890 | 55.96114 | 0.08537 | 8.06361 |
Minimum of Months | 308.00000 | 22.39206 | 44.65073 | -0.2261 | 5.76322 |
Maximum of Months | 348.00000 | 23.99606 | 66.26130 | 0.60501 | 13.26135 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.445858E+10 | 0.113734E+10 | 124.84 | 0.279324E+10 | 0.166534E+10 | 0.00 | 1.00 | 02-JAN-09:02 | 0.00 | 01-JAN-00:05 | 58713.27 | 19-JAN-09:02 | 32139.41 | 19-JAN-09:02 | 26573.86 | 19-JAN-09:02 | 12407.97 | 19-JAN-09:02 | 0.00 | 01-JAN-00:05 |
February | 0.581438E+10 | 0.147694E+10 | 158.17 | 0.363365E+10 | 0.218073E+10 | 0.00 | 1.00 | 27-FEB-09:02 | 0.00 | 01-FEB-00:05 | 57433.10 | 28-FEB-09:02 | 28738.85 | 28-FEB-09:02 | 28694.26 | 28-FEB-09:02 | 12252.82 | 28-FEB-09:02 | 0.00 | 01-FEB-00:05 |
March | 0.848433E+10 | 0.217307E+10 | 228.69 | 0.547401E+10 | 0.301032E+10 | 0.00 | 1.00 | 06-MAR-09:02 | 0.00 | 01-MAR-00:05 | 59072.45 | 07-MAR-09:02 | 32350.85 | 07-MAR-09:02 | 26721.61 | 07-MAR-09:02 | 12697.50 | 07-MAR-09:02 | 0.00 | 01-MAR-00:05 |
April | 0.161535E+11 | 0.412679E+10 | 364.22 | 0.105463E+11 | 0.560713E+10 | 0.00 | 1.00 | 01-APR-08:62 | 0.00 | 01-APR-00:05 | 59757.25 | 29-APR-08:62 | 35759.13 | 22-APR-08:62 | 31638.39 | 24-APR-08:62 | 12992.01 | 29-APR-08:62 | 0.00 | 01-APR-00:05 |
May | 0.364957E+11 | 0.906395E+10 | 475.24 | 0.221322E+11 | 0.143634E+11 | 0.00 | 1.00 | 01-MAY-08:62 | 0.00 | 01-MAY-00:10 | 60831.89 | 24-MAY-08:61 | 38979.19 | 07-MAY-07:02 | 31205.80 | 24-MAY-08:03 | 13302.27 | 27-MAY-08:04 | 0.00 | 01-MAY-00:10 |
June | 0.390742E+11 | 0.963789E+10 | 462.16 | 0.234960E+11 | 0.155782E+11 | 0.00 | 1.00 | 01-JUN-08:62 | 0.00 | 01-JUN-00:10 | 60704.32 | 19-JUN-08:61 | 39759.10 | 11-JUN-07:02 | 30350.15 | 19-JUN-08:04 | 13623.18 | 17-JUN-08:02 | 0.00 | 01-JUN-00:10 |
July | 0.444826E+11 | 0.107688E+11 | 478.74 | 0.248085E+11 | 0.196741E+11 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 60942.91 | 03-JUL-08:61 | 38459.50 | 09-JUL-07:02 | 31260.96 | 31-JUL-08:04 | 13571.07 | 08-JUL-08:02 | 0.00 | 01-JUL-00:05 |
August | 0.438970E+11 | 0.106504E+11 | 479.18 | 0.253642E+11 | 0.185328E+11 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 61068.65 | 07-AUG-08:61 | 40536.42 | 20-AUG-07:02 | 30936.59 | 07-AUG-08:05 | 13460.64 | 22-AUG-08:02 | 0.00 | 01-AUG-00:10 |
September | 0.388431E+11 | 0.934574E+10 | 461.55 | 0.217768E+11 | 0.170663E+11 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:05 | 61379.09 | 05-SEP-08:61 | 37119.01 | 03-SEP-07:02 | 33552.89 | 05-SEP-08:04 | 13866.12 | 10-SEP-07:04 | 0.00 | 01-SEP-00:05 |
October | 0.330470E+11 | 0.803144E+10 | 441.24 | 0.199499E+11 | 0.130971E+11 | 0.00 | 1.00 | 01-OCT-07:03 | 0.00 | 01-OCT-00:10 | 61502.37 | 06-OCT-08:61 | 44876.22 | 26-OCT-08:61 | 32891.12 | 06-OCT-08:05 | 13497.15 | 07-OCT-08:13 | 0.00 | 01-OCT-00:10 |
November | 0.128170E+11 | 0.318569E+10 | 289.98 | 0.801880E+10 | 0.479820E+10 | 0.00 | 1.00 | 01-NOV-08:62 | 0.00 | 01-NOV-00:10 | 59577.53 | 02-NOV-08:61 | 39409.69 | 06-NOV-09:02 | 29134.42 | 04-NOV-08:62 | 12780.13 | 02-NOV-08:61 | 0.00 | 01-NOV-00:10 |
December | 0.821480E+10 | 0.204904E+10 | 184.57 | 0.510624E+10 | 0.310856E+10 | 0.00 | 1.00 | 09-DEC-09:02 | 0.00 | 01-DEC-00:10 | 59352.87 | 15-DEC-09:02 | 34257.72 | 11-DEC-09:02 | 27572.19 | 15-DEC-09:02 | 12558.43 | 15-DEC-09:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.291782E+12 | 0.716471E+11 | 4148.57 | 0.173100E+12 | 0.118682E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.445858E+10 | 0.113734E+10 | 124.84 | 0.279324E+10 | 0.166534E+10 | 0.00 | 1.00 | 0.00 | 57433.10 | 28738.85 | 26573.86 | 12252.82 | 0.00 | |||||||
Maximum of Months | 0.444826E+11 | 0.107688E+11 | 479.18 | 0.253642E+11 | 0.196741E+11 | 0.00 | 1.00 | 0.00 | 61502.37 | 44876.22 | 33552.89 | 13866.12 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.275141E+10 | 0.683826E+09 | 136.31 | 0.177600E+10 | 0.975414E+09 | 0.00 | 1.00 | 01-JAN-18:02 | 0.00 | 01-JAN-00:05 | 30673.53 | 19-JAN-09:02 | 19113.22 | 29-JAN-18:07 | 13539.93 | 01-JAN-18:02 | 6386.70 | 19-JAN-09:02 | 0.00 | 01-JAN-00:05 |
February | 0.359292E+10 | 0.893347E+09 | 177.82 | 0.229973E+10 | 0.129318E+10 | 0.00 | 1.00 | 02-FEB-09:03 | 0.00 | 01-FEB-00:05 | 29808.87 | 28-FEB-21:20 | 21637.96 | 28-FEB-09:02 | 15562.49 | 28-FEB-21:20 | 6276.40 | 28-FEB-21:20 | 0.00 | 01-FEB-00:05 |
March | 0.514955E+10 | 0.128813E+10 | 241.18 | 0.343493E+10 | 0.171462E+10 | 0.00 | 1.00 | 04-MAR-19:01 | 0.00 | 01-MAR-00:05 | 30150.71 | 07-MAR-09:02 | 23729.21 | 04-MAR-19:01 | 14724.95 | 07-MAR-21:02 | 6487.85 | 07-MAR-09:02 | 0.00 | 01-MAR-00:05 |
April | 0.913440E+10 | 0.228681E+10 | 376.19 | 0.616655E+10 | 0.296785E+10 | 0.00 | 1.00 | 01-APR-08:62 | 0.00 | 01-APR-00:05 | 30244.18 | 29-APR-08:62 | 24584.72 | 17-APR-20:01 | 15428.55 | 15-APR-18:10 | 6655.90 | 29-APR-08:62 | 0.00 | 01-APR-00:05 |
May | 0.184404E+11 | 0.453912E+10 | 476.31 | 0.115963E+11 | 0.684410E+10 | 0.00 | 1.00 | 01-MAY-08:62 | 0.00 | 01-MAY-00:10 | 30906.03 | 24-MAY-08:61 | 23822.79 | 07-MAY-07:02 | 12465.16 | 24-MAY-08:03 | 6853.17 | 27-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.195105E+11 | 0.478036E+10 | 463.17 | 0.121326E+11 | 0.737789E+10 | 0.00 | 1.00 | 01-JUN-08:62 | 0.00 | 01-JUN-00:10 | 30645.36 | 19-JUN-08:61 | 23460.29 | 11-JUN-07:02 | 11358.15 | 19-JUN-08:03 | 7005.52 | 17-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.219685E+11 | 0.529782E+10 | 480.67 | 0.127189E+11 | 0.924965E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 31039.81 | 03-JUL-08:61 | 23551.84 | 09-JUL-07:02 | 12855.79 | 03-JUL-08:04 | 6988.24 | 19-JUL-08:61 | 0.00 | 01-JUL-00:05 |
August | 0.216319E+11 | 0.522207E+10 | 479.87 | 0.129013E+11 | 0.873053E+10 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 31142.09 | 16-AUG-08:61 | 24115.16 | 20-AUG-07:02 | 13230.60 | 16-AUG-08:03 | 6930.40 | 22-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.192916E+11 | 0.461077E+10 | 463.01 | 0.112133E+11 | 0.807825E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:05 | 31390.19 | 05-SEP-08:61 | 22871.73 | 03-SEP-07:02 | 14455.72 | 05-SEP-08:04 | 7148.17 | 10-SEP-07:01 | 0.00 | 01-SEP-00:05 |
October | 0.167613E+11 | 0.403876E+10 | 444.39 | 0.104937E+11 | 0.626766E+10 | 0.00 | 1.00 | 01-OCT-07:03 | 0.00 | 01-OCT-00:10 | 31139.54 | 06-OCT-08:61 | 24616.93 | 26-OCT-20:01 | 13239.71 | 06-OCT-08:04 | 6956.19 | 07-OCT-08:61 | 0.00 | 01-OCT-00:10 |
November | 0.711883E+10 | 0.173846E+10 | 300.99 | 0.460437E+10 | 0.251445E+10 | 0.00 | 1.00 | 01-NOV-08:62 | 0.00 | 01-NOV-00:10 | 30359.25 | 02-NOV-08:61 | 23322.12 | 06-NOV-09:02 | 15353.63 | 29-NOV-21:02 | 6541.37 | 02-NOV-08:61 | 0.00 | 01-NOV-00:10 |
December | 0.454458E+10 | 0.111521E+10 | 199.95 | 0.293355E+10 | 0.161103E+10 | 0.00 | 1.00 | 08-DEC-21:02 | 0.00 | 01-DEC-00:10 | 30200.54 | 13-DEC-09:02 | 20868.43 | 11-DEC-09:02 | 14015.54 | 08-DEC-22:05 | 6388.43 | 15-DEC-09:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.149896E+12 | 0.364947E+11 | 4239.84 | 0.922712E+11 | 0.576246E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.275141E+10 | 0.683826E+09 | 136.31 | 0.177600E+10 | 0.975414E+09 | 0.00 | 1.00 | 0.00 | 29808.87 | 19113.22 | 11358.15 | 6276.40 | 0.00 | |||||||
Maximum of Months | 0.219685E+11 | 0.529782E+10 | 480.67 | 0.129013E+11 | 0.924965E+10 | 0.00 | 1.00 | 0.00 | 31390.19 | 24616.93 | 15562.49 | 7148.17 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.203272E+10 | 0.510465E+09 | 102.24 | 0.129959E+10 | 0.733136E+09 | 0.00 | 1.00 | 01-JAN-09:02 | 0.00 | 01-JAN-00:05 | 29665.52 | 20-JAN-08:62 | 18077.73 | 01-JAN-09:02 | 15858.72 | 20-JAN-08:62 | 6265.07 | 20-JAN-08:62 | 0.00 | 01-JAN-00:05 |
February | 0.281209E+10 | 0.702068E+09 | 140.05 | 0.177811E+10 | 0.103399E+10 | 0.00 | 1.00 | 01-FEB-08:62 | 0.00 | 01-FEB-00:05 | 30039.89 | 28-FEB-08:62 | 15445.85 | 28-FEB-08:62 | 14594.05 | 28-FEB-08:62 | 6316.74 | 28-FEB-08:62 | 0.00 | 01-FEB-00:05 |
March | 0.391835E+10 | 0.985017E+09 | 181.71 | 0.256419E+10 | 0.135416E+10 | 0.00 | 1.00 | 01-MAR-08:62 | 0.00 | 01-MAR-00:05 | 30800.61 | 07-MAR-08:62 | 15799.19 | 18-MAR-07:03 | 15849.65 | 07-MAR-08:62 | 6420.80 | 07-MAR-08:62 | 0.00 | 01-MAR-00:05 |
April | 0.698510E+10 | 0.175421E+10 | 284.06 | 0.465364E+10 | 0.233146E+10 | 0.00 | 1.00 | 01-APR-07:03 | 0.00 | 01-APR-00:05 | 31513.69 | 29-APR-07:02 | 18505.90 | 27-APR-07:02 | 17543.78 | 24-APR-07:02 | 6617.14 | 29-APR-07:02 | 0.00 | 01-APR-00:05 |
May | 0.151643E+11 | 0.368473E+10 | 342.99 | 0.927554E+10 | 0.588872E+10 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 32280.48 | 24-MAY-07:01 | 20127.60 | 12-MAY-07:01 | 17160.95 | 24-MAY-07:04 | 6851.29 | 28-MAY-08:04 | 0.00 | 01-MAY-00:10 |
June | 0.162736E+11 | 0.392955E+10 | 335.92 | 0.982039E+10 | 0.645325E+10 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 32580.35 | 19-JUN-07:01 | 20411.88 | 14-JUN-07:01 | 18625.66 | 19-JUN-07:04 | 6937.91 | 17-JUN-07:04 | 0.00 | 01-JUN-00:10 |
July | 0.180309E+11 | 0.427345E+10 | 347.82 | 0.100597E+11 | 0.797120E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:05 | 32666.10 | 03-JUL-07:01 | 18356.90 | 19-JUL-07:01 | 18831.92 | 02-JUL-08:04 | 7016.95 | 09-JUL-08:04 | 0.00 | 01-JUL-00:05 |
August | 0.181371E+11 | 0.431391E+10 | 355.68 | 0.104521E+11 | 0.768499E+10 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 32631.38 | 14-AUG-07:03 | 19910.71 | 31-AUG-07:01 | 18902.23 | 14-AUG-07:04 | 6899.12 | 06-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.157349E+11 | 0.369638E+10 | 333.62 | 0.877710E+10 | 0.695778E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:05 | 32676.76 | 05-SEP-07:01 | 19375.09 | 23-SEP-07:01 | 18614.37 | 05-SEP-07:02 | 7282.41 | 10-SEP-08:13 | 0.00 | 01-SEP-00:05 |
October | 0.134711E+11 | 0.320575E+10 | 318.93 | 0.816152E+10 | 0.530957E+10 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 | 32612.02 | 25-OCT-07:01 | 23239.58 | 26-OCT-07:01 | 18169.68 | 25-OCT-07:05 | 6815.86 | 14-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.565002E+10 | 0.138127E+10 | 243.56 | 0.359652E+10 | 0.205350E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 31488.60 | 02-NOV-07:02 | 19509.15 | 07-NOV-08:62 | 16485.99 | 04-NOV-07:02 | 6599.81 | 11-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 0.360899E+10 | 0.883683E+09 | 152.44 | 0.227300E+10 | 0.133599E+10 | 0.00 | 1.00 | 09-DEC-08:62 | 0.00 | 01-DEC-00:10 | 31297.65 | 15-DEC-08:62 | 18787.89 | 17-DEC-09:02 | 17361.54 | 14-DEC-08:62 | 6486.59 | 15-DEC-08:62 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.121819E+12 | 0.293205E+11 | 3139.01 | 0.727114E+11 | 0.491077E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.203272E+10 | 0.510465E+09 | 102.24 | 0.129959E+10 | 0.733136E+09 | 0.00 | 1.00 | 0.00 | 29665.52 | 15445.85 | 14594.05 | 6265.07 | 0.00 | |||||||
Maximum of Months | 0.181371E+11 | 0.431391E+10 | 355.68 | 0.104521E+11 | 0.797120E+10 | 0.00 | 1.00 | 0.00 | 32676.76 | 23239.58 | 18902.23 | 7282.41 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.197263E+10 | 0.496447E+09 | 100.10 | 0.125763E+10 | 0.715000E+09 | 0.00 | 1.00 | 01-JAN-09:02 | 0.00 | 01-JAN-00:05 | 29762.11 | 20-JAN-08:62 | 18137.96 | 01-JAN-09:02 | 15920.29 | 20-JAN-08:62 | 6285.44 | 20-JAN-08:62 | 0.00 | 01-JAN-00:05 |
February | 0.274584E+10 | 0.686783E+09 | 137.83 | 0.173254E+10 | 0.101330E+10 | 0.00 | 1.00 | 01-FEB-08:62 | 0.00 | 01-FEB-00:05 | 30137.15 | 28-FEB-08:62 | 15485.63 | 28-FEB-08:62 | 14651.51 | 28-FEB-08:62 | 6337.20 | 28-FEB-08:62 | 0.00 | 01-FEB-00:05 |
March | 0.385791E+10 | 0.971144E+09 | 179.87 | 0.251847E+10 | 0.133944E+10 | 0.00 | 1.00 | 01-MAR-08:62 | 0.00 | 01-MAR-00:05 | 30899.86 | 07-MAR-08:62 | 15762.11 | 30-MAR-07:02 | 15916.00 | 07-MAR-08:62 | 6441.57 | 07-MAR-08:62 | 0.00 | 01-MAR-00:05 |
April | 0.695323E+10 | 0.174751E+10 | 283.48 | 0.462898E+10 | 0.232424E+10 | 0.00 | 1.00 | 01-APR-07:03 | 0.00 | 01-APR-00:05 | 31618.15 | 29-APR-07:02 | 18564.57 | 27-APR-07:02 | 17592.52 | 24-APR-07:02 | 6638.66 | 29-APR-07:02 | 0.00 | 01-APR-00:05 |
May | 0.152134E+11 | 0.369716E+10 | 343.61 | 0.931106E+10 | 0.590239E+10 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 32387.41 | 24-MAY-07:01 | 20235.99 | 12-MAY-07:01 | 17205.76 | 24-MAY-07:04 | 6873.49 | 28-MAY-08:04 | 0.00 | 01-MAY-00:10 |
June | 0.163380E+11 | 0.394547E+10 | 337.78 | 0.986739E+10 | 0.647064E+10 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 32686.08 | 19-JUN-07:01 | 20502.27 | 14-JUN-07:01 | 18638.41 | 19-JUN-07:04 | 6960.41 | 17-JUN-07:04 | 0.00 | 01-JUN-00:10 |
July | 0.181243E+11 | 0.429618E+10 | 350.76 | 0.101263E+11 | 0.799801E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:05 | 32765.66 | 31-JUL-07:01 | 18452.81 | 19-JUL-07:01 | 18834.32 | 02-JUL-08:04 | 7040.37 | 09-JUL-08:04 | 0.00 | 01-JUL-00:05 |
August | 0.182149E+11 | 0.433308E+10 | 358.31 | 0.105083E+11 | 0.770656E+10 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 32737.28 | 14-AUG-07:01 | 20007.49 | 31-AUG-07:01 | 18816.99 | 14-AUG-07:04 | 6922.56 | 06-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.158110E+11 | 0.371480E+10 | 335.54 | 0.883056E+10 | 0.698048E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:05 | 32743.14 | 05-SEP-07:01 | 19473.29 | 23-SEP-07:01 | 18521.21 | 05-SEP-07:04 | 7307.55 | 10-SEP-08:13 | 0.00 | 01-SEP-00:05 |
October | 0.135223E+11 | 0.321825E+10 | 320.84 | 0.819959E+10 | 0.532271E+10 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 | 32707.33 | 25-OCT-07:01 | 23323.40 | 26-OCT-07:01 | 18189.90 | 25-OCT-07:05 | 6838.01 | 14-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.560555E+10 | 0.137102E+10 | 241.97 | 0.356301E+10 | 0.204255E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 31593.06 | 02-NOV-07:02 | 19594.13 | 07-NOV-08:62 | 16535.35 | 04-NOV-07:02 | 6621.21 | 11-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 0.357275E+10 | 0.875310E+09 | 151.10 | 0.224607E+10 | 0.132667E+10 | 0.00 | 1.00 | 09-DEC-08:62 | 0.00 | 01-DEC-00:10 | 31401.13 | 15-DEC-08:62 | 18853.17 | 17-DEC-09:02 | 17636.08 | 16-DEC-08:62 | 6507.74 | 15-DEC-08:62 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.121932E+12 | 0.293532E+11 | 3141.19 | 0.727899E+11 | 0.491420E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.197263E+10 | 0.496447E+09 | 100.10 | 0.125763E+10 | 0.715000E+09 | 0.00 | 1.00 | 0.00 | 29762.11 | 15485.63 | 14651.51 | 6285.44 | 0.00 | |||||||
Maximum of Months | 0.182149E+11 | 0.433308E+10 | 358.31 | 0.105083E+11 | 0.799801E+10 | 0.00 | 1.00 | 0.00 | 32765.66 | 23323.40 | 18834.32 | 7307.55 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.185561E+10 | 0.468243E+09 | 96.66 | 0.117707E+10 | 0.678542E+09 | 0.00 | 1.00 | 01-JAN-09:02 | 0.00 | 01-JAN-00:05 | 29578.20 | 20-JAN-08:62 | 18002.92 | 01-JAN-09:02 | 15866.89 | 20-JAN-08:62 | 6246.81 | 20-JAN-08:62 | 0.00 | 01-JAN-00:05 |
February | 0.260772E+10 | 0.653974E+09 | 133.19 | 0.163846E+10 | 0.969258E+09 | 0.00 | 1.00 | 01-FEB-08:62 | 0.00 | 01-FEB-00:05 | 29952.10 | 28-FEB-08:62 | 15346.27 | 28-FEB-08:62 | 14605.83 | 28-FEB-08:62 | 6298.46 | 28-FEB-08:62 | 0.00 | 01-FEB-00:05 |
March | 0.369586E+10 | 0.932615E+09 | 177.27 | 0.240000E+10 | 0.129586E+10 | 0.00 | 1.00 | 07-MAR-08:62 | 0.00 | 01-MAR-00:05 | 30709.39 | 07-MAR-08:62 | 15619.21 | 30-MAR-07:02 | 15866.68 | 07-MAR-08:62 | 6402.21 | 07-MAR-08:62 | 0.00 | 01-MAR-00:05 |
April | 0.674264E+10 | 0.169736E+10 | 279.74 | 0.447700E+10 | 0.226564E+10 | 0.00 | 1.00 | 01-APR-07:03 | 0.00 | 01-APR-00:05 | 31421.33 | 29-APR-07:02 | 18324.72 | 27-APR-07:02 | 17511.64 | 24-APR-07:02 | 6598.22 | 29-APR-07:02 | 0.00 | 01-APR-00:05 |
May | 0.150089E+11 | 0.365001E+10 | 342.99 | 0.916411E+10 | 0.584480E+10 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 32186.00 | 24-MAY-07:01 | 20005.50 | 12-MAY-07:01 | 17139.23 | 24-MAY-07:03 | 6831.80 | 28-MAY-08:04 | 0.00 | 01-MAY-00:10 |
June | 0.161473E+11 | 0.390051E+10 | 335.69 | 0.972824E+10 | 0.641910E+10 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 32487.61 | 19-JUN-07:03 | 20300.20 | 14-JUN-07:01 | 18581.93 | 19-JUN-07:04 | 6918.15 | 17-JUN-07:04 | 0.00 | 01-JUN-00:10 |
July | 0.179431E+11 | 0.425269E+10 | 346.72 | 0.999882E+10 | 0.794425E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:05 | 32566.70 | 31-JUL-07:01 | 18259.51 | 19-JUL-07:01 | 18804.06 | 02-JUL-08:04 | 6997.01 | 09-JUL-08:04 | 0.00 | 01-JUL-00:05 |
August | 0.180251E+11 | 0.428769E+10 | 354.41 | 0.103723E+11 | 0.765272E+10 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 32538.49 | 14-AUG-07:01 | 19789.76 | 31-AUG-07:01 | 18812.91 | 14-AUG-07:04 | 6879.18 | 06-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.156306E+11 | 0.367342E+10 | 334.02 | 0.870514E+10 | 0.692545E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:05 | 32559.24 | 05-SEP-07:01 | 19247.06 | 23-SEP-07:01 | 18469.62 | 05-SEP-07:04 | 7262.09 | 10-SEP-08:13 | 0.00 | 01-SEP-00:05 |
October | 0.133531E+11 | 0.317863E+10 | 317.05 | 0.807481E+10 | 0.527828E+10 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 | 32529.43 | 25-OCT-07:01 | 23144.78 | 26-OCT-07:01 | 18190.98 | 25-OCT-07:04 | 6796.45 | 14-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.543748E+10 | 0.133099E+10 | 237.64 | 0.343990E+10 | 0.199758E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 31396.02 | 02-NOV-07:02 | 19378.34 | 07-NOV-08:62 | 16478.71 | 04-NOV-07:02 | 6580.43 | 11-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 0.345941E+10 | 0.848556E+09 | 145.99 | 0.216445E+10 | 0.129496E+10 | 0.00 | 1.00 | 09-DEC-08:62 | 0.00 | 01-DEC-00:10 | 31205.20 | 15-DEC-08:62 | 18710.70 | 17-DEC-09:02 | 17356.36 | 14-DEC-08:62 | 6467.92 | 15-DEC-08:62 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.119907E+12 | 0.288747E+11 | 3101.36 | 0.713403E+11 | 0.485664E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.185561E+10 | 0.468243E+09 | 96.66 | 0.117707E+10 | 0.678542E+09 | 0.00 | 1.00 | 0.00 | 29578.20 | 15346.27 | 14605.83 | 6246.81 | 0.00 | |||||||
Maximum of Months | 0.180251E+11 | 0.428769E+10 | 354.41 | 0.103723E+11 | 0.794425E+10 | 0.00 | 1.00 | 0.00 | 32566.70 | 23144.78 | 18812.91 | 7262.09 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.301783E+10 | 0.773434E+09 | 90.91 | 0.187911E+10 | 0.113872E+10 | 0.00 | 1.00 | 01-JAN-10:02 | 0.00 | 01-JAN-00:05 | 54575.39 | 19-JAN-09:02 | 33106.48 | 01-JAN-10:02 | 25348.25 | 19-JAN-09:02 | 11539.36 | 19-JAN-09:02 | 0.00 | 01-JAN-00:05 |
February | 0.440620E+10 | 0.112122E+10 | 122.27 | 0.271080E+10 | 0.169540E+10 | 0.00 | 1.00 | 26-FEB-10:03 | 0.00 | 01-FEB-00:05 | 53143.67 | 28-FEB-09:02 | 27482.79 | 28-FEB-09:02 | 25660.88 | 28-FEB-09:02 | 11363.28 | 28-FEB-09:02 | 0.00 | 01-FEB-00:05 |
March | 0.626015E+10 | 0.160098E+10 | 168.29 | 0.397940E+10 | 0.228075E+10 | 0.00 | 1.00 | 07-MAR-09:02 | 0.00 | 01-MAR-00:05 | 54828.73 | 07-MAR-09:02 | 29885.19 | 07-MAR-09:02 | 24943.54 | 07-MAR-09:02 | 11805.90 | 07-MAR-09:02 | 0.00 | 01-MAR-00:05 |
April | 0.118086E+11 | 0.301324E+10 | 268.74 | 0.771464E+10 | 0.409392E+10 | 0.00 | 1.00 | 01-APR-08:62 | 0.00 | 01-APR-00:05 | 55300.80 | 29-APR-08:62 | 33715.18 | 22-APR-08:62 | 31591.90 | 30-APR-09:02 | 12081.58 | 29-APR-08:62 | 0.00 | 01-APR-00:05 |
May | 0.266940E+11 | 0.656520E+10 | 334.35 | 0.160780E+11 | 0.106160E+11 | 0.00 | 1.00 | 01-MAY-08:62 | 0.00 | 01-MAY-00:10 | 56987.71 | 21-MAY-09:01 | 35243.94 | 12-MAY-08:62 | 30261.76 | 21-MAY-09:04 | 12521.82 | 28-MAY-09:04 | 0.00 | 01-MAY-00:10 |
June | 0.289312E+11 | 0.707193E+10 | 327.77 | 0.172060E+11 | 0.117252E+11 | 0.00 | 1.00 | 01-JUN-08:62 | 0.00 | 01-JUN-00:10 | 57367.26 | 19-JUN-08:61 | 36194.64 | 10-JUN-08:61 | 33076.45 | 19-JUN-08:04 | 12673.84 | 17-JUN-08:02 | 0.00 | 01-JUN-00:10 |
July | 0.320332E+11 | 0.768101E+10 | 332.98 | 0.175785E+11 | 0.144547E+11 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 57624.77 | 31-JUL-08:61 | 33612.76 | 19-JUL-08:61 | 32886.53 | 31-JUL-08:03 | 12781.96 | 09-JUL-09:13 | 0.00 | 01-JUL-00:05 |
August | 0.324222E+11 | 0.780958E+10 | 343.04 | 0.184050E+11 | 0.140171E+11 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 57446.79 | 07-AUG-08:61 | 36324.91 | 31-AUG-08:61 | 33460.06 | 14-AUG-08:05 | 12550.44 | 13-AUG-09:13 | 0.00 | 01-AUG-00:10 |
September | 0.277502E+11 | 0.659029E+10 | 322.12 | 0.151564E+11 | 0.125938E+11 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:05 | 57683.53 | 05-SEP-08:61 | 34222.41 | 23-SEP-08:62 | 33261.08 | 05-SEP-08:02 | 13261.33 | 10-SEP-09:13 | 0.00 | 01-SEP-00:05 |
October | 0.239866E+11 | 0.578112E+10 | 308.26 | 0.142859E+11 | 0.970071E+10 | 0.00 | 1.00 | 01-OCT-09:02 | 0.00 | 01-OCT-00:10 | 57505.40 | 08-OCT-09:01 | 41194.27 | 26-OCT-08:61 | 31807.92 | 22-OCT-09:04 | 12553.69 | 07-OCT-08:13 | 0.00 | 01-OCT-00:10 |
November | 0.948435E+10 | 0.234633E+10 | 218.56 | 0.587665E+10 | 0.360770E+10 | 0.00 | 1.00 | 01-NOV-08:62 | 0.00 | 01-NOV-00:10 | 55327.39 | 02-NOV-08:61 | 34497.25 | 07-NOV-09:01 | 27384.89 | 04-NOV-08:62 | 11894.24 | 11-NOV-10:02 | 0.00 | 01-NOV-00:10 |
December | 0.600218E+10 | 0.148717E+10 | 133.71 | 0.368202E+10 | 0.232016E+10 | 0.00 | 1.00 | 09-DEC-09:02 | 0.00 | 01-DEC-00:10 | 55059.74 | 15-DEC-09:02 | 35250.35 | 10-DEC-10:02 | 25345.31 | 15-DEC-09:02 | 11794.27 | 10-DEC-10:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.212797E+12 | 0.518415E+11 | 2971.01 | 0.124552E+12 | 0.882442E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.301783E+10 | 0.773434E+09 | 90.91 | 0.187911E+10 | 0.113872E+10 | 0.00 | 1.00 | 0.00 | 53143.67 | 27482.79 | 24943.54 | 11363.28 | 0.00 | |||||||
Maximum of Months | 0.324222E+11 | 0.780958E+10 | 343.04 | 0.184050E+11 | 0.144547E+11 | 0.00 | 1.00 | 0.00 | 57683.53 | 41194.27 | 33460.06 | 13261.33 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.152277E+10 | 0.384209E+09 | 88.58 | 0.948424E+09 | 0.574342E+09 | 0.00 | 1.00 | 01-JAN-10:02 | 0.00 | 01-JAN-00:05 | 27060.86 | 01-JAN-10:02 | 17369.31 | 01-JAN-10:02 | 12074.41 | 19-JAN-09:02 | 5736.80 | 01-JAN-10:02 | 0.00 | 01-JAN-00:05 |
February | 0.223619E+10 | 0.560224E+09 | 118.99 | 0.137551E+10 | 0.860674E+09 | 0.00 | 1.00 | 27-FEB-09:02 | 0.00 | 01-FEB-00:05 | 27009.10 | 28-FEB-09:02 | 13966.81 | 28-FEB-09:02 | 13042.29 | 28-FEB-09:02 | 5674.44 | 28-FEB-09:02 | 0.00 | 01-FEB-00:05 |
March | 0.319245E+10 | 0.803889E+09 | 166.75 | 0.202637E+10 | 0.116608E+10 | 0.00 | 1.00 | 07-MAR-09:02 | 0.00 | 01-MAR-00:05 | 28737.87 | 07-MAR-09:02 | 15682.78 | 07-MAR-09:02 | 13055.09 | 07-MAR-09:02 | 6082.14 | 07-MAR-09:02 | 0.00 | 01-MAR-00:05 |
April | 0.607227E+10 | 0.152532E+10 | 266.46 | 0.396919E+10 | 0.210309E+10 | 0.00 | 1.00 | 01-APR-08:62 | 0.00 | 01-APR-00:05 | 28985.77 | 29-APR-08:62 | 17698.95 | 22-APR-08:62 | 16567.79 | 30-APR-09:02 | 6224.74 | 29-APR-08:62 | 0.00 | 01-APR-00:05 |
May | 0.138489E+11 | 0.335507E+10 | 334.39 | 0.834873E+10 | 0.550014E+10 | 0.00 | 1.00 | 01-MAY-08:62 | 0.00 | 01-MAY-00:10 | 29888.06 | 21-MAY-09:01 | 18474.11 | 12-MAY-08:62 | 15913.74 | 21-MAY-09:04 | 6452.29 | 28-MAY-09:04 | 0.00 | 01-MAY-00:10 |
June | 0.150089E+11 | 0.361397E+10 | 327.36 | 0.893226E+10 | 0.607665E+10 | 0.00 | 1.00 | 01-JUN-08:62 | 0.00 | 01-JUN-00:10 | 30086.19 | 19-JUN-08:61 | 18942.01 | 10-JUN-08:61 | 17436.13 | 19-JUN-08:04 | 6530.29 | 17-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.166225E+11 | 0.392657E+10 | 331.98 | 0.913034E+10 | 0.749218E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 30221.24 | 31-JUL-08:61 | 17621.92 | 19-JUL-08:61 | 17338.29 | 31-JUL-08:03 | 6585.73 | 09-JUL-09:13 | 0.00 | 01-JUL-00:05 |
August | 0.168171E+11 | 0.399064E+10 | 342.68 | 0.955429E+10 | 0.726277E+10 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 30127.90 | 07-AUG-08:61 | 19033.47 | 31-AUG-08:61 | 17653.74 | 14-AUG-08:05 | 6466.90 | 13-AUG-09:13 | 0.00 | 01-AUG-00:10 |
September | 0.143829E+11 | 0.336394E+10 | 321.80 | 0.786428E+10 | 0.651867E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:05 | 30252.06 | 05-SEP-08:61 | 17947.86 | 23-SEP-08:62 | 17474.91 | 05-SEP-08:02 | 6834.00 | 10-SEP-09:13 | 0.00 | 01-SEP-00:05 |
October | 0.124231E+11 | 0.294795E+10 | 307.34 | 0.740270E+10 | 0.502040E+10 | 0.00 | 1.00 | 01-OCT-09:02 | 0.00 | 01-OCT-00:10 | 30158.63 | 08-OCT-09:01 | 21631.34 | 26-OCT-08:61 | 16748.91 | 22-OCT-09:04 | 6469.31 | 07-OCT-08:13 | 0.00 | 01-OCT-00:10 |
November | 0.486412E+10 | 0.118392E+10 | 214.52 | 0.301067E+10 | 0.185345E+10 | 0.00 | 1.00 | 01-NOV-08:62 | 0.00 | 01-NOV-00:10 | 29001.74 | 02-NOV-08:61 | 18097.48 | 07-NOV-09:01 | 14352.73 | 04-NOV-08:62 | 6128.33 | 11-NOV-10:02 | 0.00 | 01-NOV-00:10 |
December | 0.308176E+10 | 0.751307E+09 | 130.26 | 0.188918E+10 | 0.119258E+10 | 0.00 | 1.00 | 09-DEC-09:02 | 0.00 | 01-DEC-00:10 | 28864.31 | 15-DEC-09:02 | 18461.65 | 10-DEC-10:02 | 13262.52 | 15-DEC-09:02 | 6076.84 | 10-DEC-10:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.110073E+12 | 0.264070E+11 | 2951.12 | 0.644519E+11 | 0.456210E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.152277E+10 | 0.384209E+09 | 88.58 | 0.948424E+09 | 0.574342E+09 | 0.00 | 1.00 | 0.00 | 27009.10 | 13966.81 | 12074.41 | 5674.44 | 0.00 | |||||||
Maximum of Months | 0.168171E+11 | 0.399064E+10 | 342.68 | 0.955429E+10 | 0.749218E+10 | 0.00 | 1.00 | 0.00 | 30252.06 | 21631.34 | 17653.74 | 6834.00 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.148757E+10 | 0.375664E+09 | 87.36 | 0.925100E+09 | 0.562471E+09 | 0.00 | 1.00 | 01-JAN-10:02 | 0.00 | 01-JAN-00:05 | 26944.71 | 01-JAN-10:02 | 17282.96 | 01-JAN-10:02 | 11430.76 | 19-JAN-09:02 | 5712.30 | 01-JAN-10:02 | 0.00 | 01-JAN-00:05 |
February | 0.218607E+10 | 0.548151E+09 | 117.41 | 0.134236E+10 | 0.843711E+09 | 0.00 | 1.00 | 27-FEB-09:02 | 0.00 | 01-FEB-00:05 | 25752.16 | 28-FEB-09:02 | 13204.53 | 28-FEB-09:02 | 12547.63 | 28-FEB-09:02 | 5409.15 | 28-FEB-09:02 | 0.00 | 01-FEB-00:05 |
March | 0.313506E+10 | 0.790049E+09 | 165.50 | 0.198510E+10 | 0.114995E+10 | 0.00 | 1.00 | 07-MAR-09:02 | 0.00 | 01-MAR-00:05 | 28620.96 | 07-MAR-09:02 | 15543.49 | 07-MAR-09:02 | 13077.46 | 07-MAR-09:02 | 6056.80 | 07-MAR-09:02 | 0.00 | 01-MAR-00:05 |
April | 0.599684E+10 | 0.150697E+10 | 264.93 | 0.391489E+10 | 0.208195E+10 | 0.00 | 1.00 | 01-APR-08:62 | 0.00 | 01-APR-00:05 | 28866.31 | 29-APR-08:62 | 17582.75 | 22-APR-08:62 | 16507.71 | 30-APR-09:02 | 6198.64 | 29-APR-08:62 | 0.00 | 01-APR-00:05 |
May | 0.137713E+11 | 0.333629E+10 | 334.36 | 0.829428E+10 | 0.547705E+10 | 0.00 | 1.00 | 01-MAY-08:62 | 0.00 | 01-MAY-00:10 | 29758.78 | 21-MAY-09:01 | 18363.77 | 12-MAY-08:62 | 15869.31 | 21-MAY-09:04 | 6425.19 | 28-MAY-09:04 | 0.00 | 01-MAY-00:10 |
June | 0.149370E+11 | 0.359619E+10 | 327.29 | 0.888089E+10 | 0.605610E+10 | 0.00 | 1.00 | 01-JUN-08:62 | 0.00 | 01-JUN-00:10 | 29959.78 | 19-JUN-08:03 | 18832.09 | 10-JUN-08:61 | 17385.26 | 19-JUN-08:04 | 6502.85 | 17-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.165553E+11 | 0.390987E+10 | 331.33 | 0.908407E+10 | 0.747122E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 30094.26 | 31-JUL-08:61 | 17514.24 | 19-JUL-08:61 | 17283.63 | 31-JUL-08:03 | 6557.83 | 09-JUL-09:13 | 0.00 | 01-JUL-00:05 |
August | 0.167510E+11 | 0.397415E+10 | 342.66 | 0.950790E+10 | 0.724310E+10 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 30001.31 | 07-AUG-08:02 | 18919.45 | 31-AUG-08:61 | 17595.28 | 14-AUG-08:05 | 6439.59 | 13-AUG-09:13 | 0.00 | 01-AUG-00:10 |
September | 0.143179E+11 | 0.334831E+10 | 321.75 | 0.782009E+10 | 0.649781E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:05 | 30124.95 | 05-SEP-08:61 | 17841.85 | 23-SEP-08:62 | 17415.13 | 05-SEP-08:02 | 6804.87 | 10-SEP-09:13 | 0.00 | 01-SEP-00:05 |
October | 0.123556E+11 | 0.293160E+10 | 307.01 | 0.735392E+10 | 0.500170E+10 | 0.00 | 1.00 | 01-OCT-09:02 | 0.00 | 01-OCT-00:10 | 30031.92 | 08-OCT-09:01 | 21529.42 | 26-OCT-08:61 | 16700.69 | 22-OCT-09:04 | 6441.87 | 07-OCT-08:13 | 0.00 | 01-OCT-00:10 |
November | 0.480317E+10 | 0.116908E+10 | 213.05 | 0.296554E+10 | 0.183763E+10 | 0.00 | 1.00 | 01-NOV-08:62 | 0.00 | 01-NOV-00:10 | 28882.96 | 02-NOV-08:61 | 17982.42 | 07-NOV-09:01 | 14310.36 | 04-NOV-08:62 | 6102.57 | 11-NOV-10:02 | 0.00 | 01-NOV-00:10 |
December | 0.304091E+10 | 0.741575E+09 | 127.88 | 0.186023E+10 | 0.118068E+10 | 0.00 | 1.00 | 10-DEC-10:02 | 0.00 | 01-DEC-00:10 | 28745.14 | 15-DEC-09:02 | 18340.25 | 10-DEC-10:02 | 13259.48 | 15-DEC-09:02 | 6050.86 | 10-DEC-10:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.109338E+12 | 0.262279E+11 | 2940.54 | 0.639344E+11 | 0.454034E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.148757E+10 | 0.375664E+09 | 87.36 | 0.925100E+09 | 0.562471E+09 | 0.00 | 1.00 | 0.00 | 25752.16 | 13204.53 | 11430.76 | 5409.15 | 0.00 | |||||||
Maximum of Months | 0.167510E+11 | 0.397415E+10 | 342.66 | 0.950790E+10 | 0.747122E+10 | 0.00 | 1.00 | 0.00 | 30124.95 | 21529.42 | 17595.28 | 6804.87 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.142932E+10 | 0.361791E+09 | 86.03 | 0.887203E+09 | 0.542120E+09 | 0.00 | 1.00 | 01-JAN-10:02 | 0.00 | 01-JAN-00:05 | 27063.94 | 01-JAN-10:02 | 17329.31 | 01-JAN-10:02 | 9734.63 | 01-JAN-10:02 | 5737.91 | 01-JAN-10:02 | 0.00 | 01-JAN-00:05 |
February | 0.209986E+10 | 0.528039E+09 | 115.16 | 0.128652E+10 | 0.813331E+09 | 0.00 | 1.00 | 28-FEB-09:02 | 0.00 | 01-FEB-00:05 | 21868.48 | 28-FEB-09:02 | 10999.69 | 28-FEB-09:02 | 10868.79 | 28-FEB-09:02 | 4592.80 | 28-FEB-09:02 | 0.00 | 01-FEB-00:05 |
March | 0.303795E+10 | 0.767568E+09 | 164.34 | 0.191593E+10 | 0.112201E+10 | 0.00 | 1.00 | 07-MAR-09:02 | 0.00 | 01-MAR-00:05 | 28754.51 | 07-MAR-09:02 | 15454.97 | 07-MAR-09:02 | 13299.54 | 07-MAR-09:02 | 6085.16 | 07-MAR-09:02 | 0.00 | 01-MAR-00:05 |
April | 0.586639E+10 | 0.147710E+10 | 261.18 | 0.382357E+10 | 0.204282E+10 | 0.00 | 1.00 | 15-APR-08:62 | 0.00 | 01-APR-00:05 | 28993.58 | 29-APR-08:62 | 17462.66 | 23-APR-09:02 | 16606.75 | 30-APR-09:02 | 6227.54 | 29-APR-08:62 | 0.00 | 01-APR-00:05 |
May | 0.137339E+11 | 0.333058E+10 | 334.07 | 0.827015E+10 | 0.546379E+10 | 0.00 | 1.00 | 01-MAY-08:62 | 0.00 | 01-MAY-00:10 | 29889.24 | 21-MAY-09:01 | 18416.68 | 12-MAY-08:62 | 15989.98 | 21-MAY-09:03 | 6455.58 | 28-MAY-09:04 | 0.00 | 01-MAY-00:10 |
June | 0.149392E+11 | 0.359908E+10 | 327.30 | 0.888338E+10 | 0.605580E+10 | 0.00 | 1.00 | 01-JUN-08:62 | 0.00 | 01-JUN-00:10 | 30100.28 | 19-JUN-08:61 | 18890.05 | 10-JUN-08:61 | 17504.40 | 19-JUN-08:04 | 6533.37 | 17-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.166013E+11 | 0.392282E+10 | 331.32 | 0.911801E+10 | 0.748334E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 30235.40 | 31-JUL-08:61 | 17616.07 | 19-JUL-08:61 | 17377.97 | 31-JUL-08:03 | 6588.69 | 09-JUL-09:13 | 0.00 | 01-JUL-00:05 |
August | 0.168184E+11 | 0.399150E+10 | 342.45 | 0.955654E+10 | 0.726183E+10 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 30142.01 | 07-AUG-08:61 | 19030.07 | 31-AUG-08:61 | 17671.26 | 14-AUG-08:05 | 6469.92 | 13-AUG-09:13 | 0.00 | 01-AUG-00:10 |
September | 0.143536E+11 | 0.335846E+10 | 321.87 | 0.784613E+10 | 0.650745E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:05 | 30266.22 | 05-SEP-08:61 | 17916.08 | 23-SEP-08:62 | 17491.07 | 05-SEP-08:02 | 6838.02 | 10-SEP-09:13 | 0.00 | 01-SEP-00:05 |
October | 0.123541E+11 | 0.293275E+10 | 306.22 | 0.735355E+10 | 0.500056E+10 | 0.00 | 1.00 | 01-OCT-09:02 | 0.00 | 01-OCT-00:10 | 30172.76 | 08-OCT-09:01 | 21627.64 | 26-OCT-08:61 | 16794.50 | 22-OCT-09:03 | 6472.32 | 07-OCT-08:13 | 0.00 | 01-OCT-00:10 |
November | 0.472164E+10 | 0.115020E+10 | 208.85 | 0.290587E+10 | 0.181577E+10 | 0.00 | 1.00 | 01-NOV-08:62 | 0.00 | 01-NOV-00:10 | 29015.44 | 02-NOV-08:61 | 18017.06 | 07-NOV-09:01 | 14393.40 | 04-NOV-08:62 | 6130.88 | 11-NOV-10:02 | 0.00 | 01-NOV-00:10 |
December | 0.297905E+10 | 0.727812E+09 | 125.69 | 0.181674E+10 | 0.116231E+10 | 0.00 | 1.00 | 10-DEC-10:02 | 0.00 | 01-DEC-00:10 | 28875.66 | 15-DEC-09:02 | 18339.58 | 10-DEC-10:02 | 13398.59 | 15-DEC-09:02 | 6077.90 | 10-DEC-10:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.108935E+12 | 0.261477E+11 | 2924.47 | 0.636636E+11 | 0.452711E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.142932E+10 | 0.361791E+09 | 86.03 | 0.887203E+09 | 0.542120E+09 | 0.00 | 1.00 | 0.00 | 21868.48 | 10999.69 | 9734.63 | 4592.80 | 0.00 | |||||||
Maximum of Months | 0.168184E+11 | 0.399150E+10 | 342.45 | 0.955654E+10 | 0.748334E+10 | 0.00 | 1.00 | 0.00 | 30266.22 | 21627.64 | 17671.26 | 6838.02 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.149374E+10 | 0.381702E+09 | 83.89 | 0.937971E+09 | 0.555765E+09 | 0.00 | 1.00 | 01-JAN-10:02 | 0.00 | 01-JAN-00:05 | 24423.38 | 01-JAN-10:02 | 15717.28 | 01-JAN-10:02 | 8706.10 | 01-JAN-10:02 | 5183.08 | 01-JAN-10:02 | 0.00 | 01-JAN-00:05 |
February | 0.216685E+10 | 0.551197E+09 | 111.74 | 0.134307E+10 | 0.823787E+09 | 0.00 | 0.78 | 24-FEB-13:10 | 0.00 | 01-FEB-00:05 | 11448.97 | 24-FEB-13:10 | 7219.68 | 02-FEB-13:10 | 5426.59 | 28-FEB-09:02 | 2800.85 | 24-FEB-13:10 | 0.00 | 01-FEB-00:05 |
March | 0.323501E+10 | 0.825408E+09 | 160.65 | 0.206314E+10 | 0.117187E+10 | 0.00 | 1.00 | 07-MAR-09:02 | 0.00 | 01-MAR-00:05 | 21426.75 | 07-MAR-09:02 | 10672.86 | 07-MAR-09:02 | 10753.88 | 07-MAR-09:02 | 4520.17 | 07-MAR-09:02 | 0.00 | 01-MAR-00:05 |
April | 0.618047E+10 | 0.157341E+10 | 255.36 | 0.407982E+10 | 0.210065E+10 | 0.00 | 1.00 | 22-APR-08:62 | 0.00 | 01-APR-00:05 | 33411.24 | 29-APR-08:62 | 20129.54 | 23-APR-09:02 | 19050.01 | 30-APR-09:02 | 7127.51 | 29-APR-08:62 | 0.00 | 01-APR-00:05 |
May | 0.148762E+11 | 0.364799E+10 | 334.92 | 0.908577E+10 | 0.579046E+10 | 0.00 | 1.00 | 01-MAY-08:62 | 0.00 | 01-MAY-00:10 | 34315.00 | 24-MAY-08:61 | 20530.99 | 31-MAY-08:61 | 19214.49 | 23-MAY-08:62 | 7377.14 | 28-MAY-09:04 | 0.00 | 01-MAY-00:10 |
June | 0.163351E+11 | 0.397269E+10 | 327.95 | 0.988559E+10 | 0.644956E+10 | 0.00 | 1.00 | 01-JUN-08:62 | 0.00 | 01-JUN-00:10 | 34446.19 | 05-JUN-08:61 | 21330.31 | 11-JUN-09:01 | 20219.76 | 19-JUN-08:04 | 7473.09 | 17-JUN-08:02 | 0.00 | 01-JUN-00:10 |
July | 0.182580E+11 | 0.435708E+10 | 334.61 | 0.102667E+11 | 0.799135E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 34585.22 | 31-JUL-08:61 | 19717.21 | 19-JUL-08:61 | 20394.29 | 02-JUL-09:06 | 7538.77 | 09-JUL-09:13 | 0.00 | 01-JUL-00:05 |
August | 0.186380E+11 | 0.445878E+10 | 345.93 | 0.108230E+11 | 0.781504E+10 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 34478.40 | 07-AUG-08:61 | 22342.84 | 31-AUG-08:61 | 20197.50 | 06-AUG-09:06 | 7402.17 | 13-AUG-09:13 | 0.00 | 01-AUG-00:10 |
September | 0.158068E+11 | 0.373257E+10 | 323.75 | 0.884449E+10 | 0.696229E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:05 | 34620.49 | 05-SEP-08:02 | 20488.67 | 01-SEP-08:61 | 20150.53 | 05-SEP-08:04 | 7829.47 | 10-SEP-09:13 | 0.00 | 01-SEP-00:05 |
October | 0.135597E+11 | 0.324312E+10 | 304.12 | 0.821608E+10 | 0.534366E+10 | 0.00 | 1.00 | 01-OCT-09:02 | 0.00 | 01-OCT-00:10 | 34584.43 | 25-OCT-08:61 | 25253.40 | 26-OCT-08:61 | 19695.13 | 22-OCT-09:03 | 7391.66 | 07-OCT-08:13 | 0.00 | 01-OCT-00:10 |
November | 0.501133E+10 | 0.123286E+10 | 202.97 | 0.312446E+10 | 0.188687E+10 | 0.00 | 1.00 | 01-NOV-08:62 | 0.00 | 01-NOV-00:10 | 33451.78 | 02-NOV-08:61 | 19959.86 | 11-NOV-10:02 | 16653.64 | 04-NOV-08:62 | 7025.96 | 11-NOV-10:02 | 0.00 | 01-NOV-00:10 |
December | 0.309934E+10 | 0.768279E+09 | 123.58 | 0.190979E+10 | 0.118955E+10 | 0.00 | 1.00 | 10-DEC-10:02 | 0.00 | 01-DEC-00:10 | 33256.21 | 15-DEC-09:02 | 20964.12 | 10-DEC-10:02 | 17996.46 | 11-DEC-09:02 | 6954.37 | 10-DEC-10:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.118661E+12 | 0.287451E+11 | 2909.48 | 0.705799E+11 | 0.480808E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.149374E+10 | 0.381702E+09 | 83.89 | 0.937971E+09 | 0.555765E+09 | 0.00 | 0.78 | 0.00 | 11448.97 | 7219.68 | 5426.59 | 2800.85 | 0.00 | |||||||
Maximum of Months | 0.186380E+11 | 0.445878E+10 | 345.93 | 0.108230E+11 | 0.799135E+10 | 0.00 | 1.00 | 0.00 | 34620.49 | 25253.40 | 20394.29 | 7829.47 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 133.98 | 53.77 | 0.00 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 123.39 | 46.92 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 81.22 | 41.54 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 66.03 | 27.44 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.84 | 6.92 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 63.63 | 6.06 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 66.60 | 3.97 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 77.98 | 6.55 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 86.66 | 9.36 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 123.55 | 17.33 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.22 | 37.64 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 134.76 | 48.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 96.19 | 25.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.84 | 3.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.22 | 53.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 133.98 | 53.77 | 0.00 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 123.39 | 46.92 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 81.22 | 41.54 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 66.03 | 27.44 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.84 | 6.92 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 63.63 | 6.06 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 66.60 | 3.97 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 77.98 | 6.55 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 86.66 | 9.36 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 123.55 | 17.33 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.22 | 37.64 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 134.76 | 48.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 96.19 | 25.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.84 | 3.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.22 | 53.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 133.98 | 53.77 | 0.00 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 123.39 | 46.92 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 81.22 | 41.54 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 66.03 | 27.44 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.84 | 6.92 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 63.63 | 6.06 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 66.60 | 3.97 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 77.98 | 6.55 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 86.66 | 9.36 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 123.55 | 17.33 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.22 | 37.64 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 134.76 | 48.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 96.19 | 25.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.84 | 3.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.22 | 53.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 133.98 | 53.77 | 0.00 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 123.39 | 46.92 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 81.22 | 41.54 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 66.03 | 27.44 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.84 | 6.92 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 63.63 | 6.06 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 66.60 | 3.97 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 77.98 | 6.55 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 86.66 | 9.36 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 123.55 | 17.33 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.22 | 37.64 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 134.76 | 48.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 96.19 | 25.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.84 | 3.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.22 | 53.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 108.04 | 77.05 | 30.99 | 161.30 | 63.93 | 0.00 | 0.00 | 0.00 |
February | 97.98 | 63.42 | 34.56 | 148.53 | 55.83 | 0.00 | 0.00 | 0.00 |
March | 62.56 | 28.23 | 34.32 | 97.78 | 49.41 | 0.00 | 0.00 | 0.00 |
April | 46.36 | 10.86 | 35.50 | 79.33 | 32.74 | 0.00 | 0.00 | 0.00 |
May | 35.43 | 1.51 | 33.92 | 75.18 | 8.33 | 0.00 | 0.00 | 0.00 |
June | 35.00 | 0.33 | 34.67 | 76.05 | 7.30 | 0.00 | 0.00 | 0.00 |
July | 36.63 | 0.67 | 35.96 | 79.59 | 4.80 | 0.00 | 0.00 | 0.00 |
August | 43.10 | 5.17 | 37.93 | 93.32 | 7.88 | 0.00 | 0.00 | 0.00 |
September | 51.71 | 13.63 | 38.08 | 103.86 | 11.26 | 0.00 | 0.00 | 0.00 |
October | 80.23 | 41.79 | 38.44 | 148.30 | 20.73 | 0.00 | 0.00 | 0.00 |
November | 102.10 | 70.29 | 31.80 | 162.53 | 44.87 | 0.00 | 0.00 | 0.00 |
December | 105.57 | 75.81 | 29.75 | 162.10 | 58.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.89 | 32.24 | 34.66 | 115.50 | 30.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 35.00 | 0.33 | 29.75 | 75.18 | 4.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 108.04 | 77.05 | 38.44 | 162.53 | 63.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 108.04 | 77.05 | 30.99 | 161.30 | 63.93 | 0.00 | 0.00 | 0.00 |
February | 97.98 | 63.42 | 34.56 | 148.53 | 55.83 | 0.00 | 0.00 | 0.00 |
March | 62.56 | 28.23 | 34.32 | 97.78 | 49.41 | 0.00 | 0.00 | 0.00 |
April | 46.36 | 10.86 | 35.50 | 79.33 | 32.74 | 0.00 | 0.00 | 0.00 |
May | 35.43 | 1.51 | 33.92 | 75.18 | 8.33 | 0.00 | 0.00 | 0.00 |
June | 35.00 | 0.33 | 34.67 | 76.05 | 7.30 | 0.00 | 0.00 | 0.00 |
July | 36.63 | 0.67 | 35.96 | 79.59 | 4.80 | 0.00 | 0.00 | 0.00 |
August | 43.10 | 5.17 | 37.93 | 93.32 | 7.88 | 0.00 | 0.00 | 0.00 |
September | 51.71 | 13.63 | 38.08 | 103.86 | 11.26 | 0.00 | 0.00 | 0.00 |
October | 80.23 | 41.79 | 38.44 | 148.30 | 20.73 | 0.00 | 0.00 | 0.00 |
November | 102.10 | 70.29 | 31.80 | 162.53 | 44.87 | 0.00 | 0.00 | 0.00 |
December | 105.57 | 75.81 | 29.75 | 162.10 | 58.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.89 | 32.24 | 34.66 | 115.50 | 30.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 35.00 | 0.33 | 29.75 | 75.18 | 4.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 108.04 | 77.05 | 38.44 | 162.53 | 63.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 132.37 | 57.04 | 0.00 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 122.06 | 49.37 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 80.21 | 43.89 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 65.64 | 28.21 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.95 | 7.14 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 63.91 | 6.19 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 67.00 | 4.01 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 78.46 | 6.46 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 86.95 | 9.31 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 123.60 | 17.43 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 134.63 | 38.40 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 133.75 | 50.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 95.84 | 26.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.95 | 4.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 134.63 | 57.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 132.37 | 57.04 | 0.00 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 122.06 | 49.37 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 80.21 | 43.89 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 65.64 | 28.21 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.95 | 7.14 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 63.91 | 6.19 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 67.00 | 4.01 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 78.46 | 6.46 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 86.95 | 9.31 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 123.60 | 17.43 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 134.63 | 38.40 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 133.75 | 50.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 95.84 | 26.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.95 | 4.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 134.63 | 57.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 108.04 | 77.05 | 30.99 | 159.45 | 67.75 | 0.00 | 0.00 | 0.00 |
February | 97.98 | 63.42 | 34.56 | 146.99 | 58.70 | 0.00 | 0.00 | 0.00 |
March | 62.56 | 28.23 | 34.32 | 96.61 | 52.16 | 0.00 | 0.00 | 0.00 |
April | 46.36 | 10.86 | 35.50 | 78.89 | 33.64 | 0.00 | 0.00 | 0.00 |
May | 35.43 | 1.51 | 33.92 | 75.31 | 8.59 | 0.00 | 0.00 | 0.00 |
June | 35.00 | 0.33 | 34.67 | 76.39 | 7.46 | 0.00 | 0.00 | 0.00 |
July | 36.63 | 0.67 | 35.96 | 80.06 | 4.86 | 0.00 | 0.00 | 0.00 |
August | 43.10 | 5.17 | 37.93 | 93.91 | 7.78 | 0.00 | 0.00 | 0.00 |
September | 51.71 | 13.63 | 38.08 | 104.22 | 11.20 | 0.00 | 0.00 | 0.00 |
October | 80.23 | 41.79 | 38.44 | 148.40 | 20.84 | 0.00 | 0.00 | 0.00 |
November | 102.10 | 70.29 | 31.80 | 161.87 | 45.77 | 0.00 | 0.00 | 0.00 |
December | 105.57 | 75.81 | 29.75 | 160.95 | 60.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.89 | 32.24 | 34.66 | 115.10 | 31.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 35.00 | 0.33 | 29.75 | 75.31 | 4.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 108.04 | 77.05 | 38.44 | 161.87 | 67.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 132.83 | 55.99 | 1.33 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 122.39 | 48.83 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 80.36 | 43.76 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 65.51 | 29.31 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.22 | 8.88 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 63.12 | 8.10 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 65.41 | 5.58 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 77.45 | 8.28 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 86.25 | 11.43 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 123.19 | 19.56 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 134.70 | 39.33 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 134.01 | 50.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 95.49 | 27.37 | 1.33 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.22 | 5.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 134.70 | 55.99 | 1.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 132.83 | 55.99 | 1.33 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 122.39 | 48.83 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 80.36 | 43.76 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 65.51 | 29.31 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.22 | 8.88 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 63.12 | 8.10 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 65.41 | 5.58 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 77.45 | 8.28 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 86.25 | 11.43 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 123.19 | 19.56 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 134.70 | 39.33 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 134.01 | 50.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 95.49 | 27.37 | 1.33 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.22 | 5.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 134.70 | 55.99 | 1.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.45 | 76.63 | 30.82 | 159.12 | 66.15 | 1.33 | 0.00 | 0.00 |
February | 97.45 | 63.08 | 34.37 | 146.58 | 57.74 | 0.00 | 0.00 | 0.00 |
March | 62.21 | 28.08 | 34.14 | 96.26 | 51.71 | 0.00 | 0.00 | 0.00 |
April | 46.11 | 10.81 | 35.31 | 78.30 | 34.73 | 0.00 | 0.00 | 0.00 |
May | 35.23 | 1.50 | 33.74 | 74.05 | 10.59 | 0.00 | 0.00 | 0.00 |
June | 34.80 | 0.32 | 34.48 | 75.06 | 9.65 | 0.00 | 0.00 | 0.00 |
July | 36.43 | 0.67 | 35.76 | 77.79 | 6.69 | 0.00 | 0.00 | 0.00 |
August | 42.86 | 5.14 | 37.72 | 92.23 | 9.88 | 0.00 | 0.00 | 0.00 |
September | 51.43 | 13.55 | 37.87 | 102.85 | 13.62 | 0.00 | 0.00 | 0.00 |
October | 79.79 | 41.56 | 38.23 | 147.10 | 23.20 | 0.00 | 0.00 | 0.00 |
November | 101.54 | 69.91 | 31.63 | 161.07 | 46.60 | 0.00 | 0.00 | 0.00 |
December | 104.99 | 75.40 | 29.59 | 160.38 | 60.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.53 | 32.06 | 34.47 | 114.08 | 32.41 | 1.33 | 0.00 | 0.00 |
Minimum of Months | 34.80 | 0.32 | 29.59 | 74.05 | 6.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.45 | 76.63 | 38.23 | 161.07 | 66.15 | 1.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 133.12 | 55.24 | 1.50 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 122.63 | 48.22 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 80.51 | 43.29 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 65.54 | 29.19 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.17 | 9.04 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 63.06 | 8.29 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 65.29 | 5.80 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 77.38 | 8.50 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 86.18 | 11.64 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 123.15 | 19.72 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 134.76 | 39.16 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 134.17 | 50.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 95.53 | 27.25 | 1.50 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.17 | 5.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 134.76 | 55.24 | 1.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 133.12 | 55.24 | 1.50 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 122.63 | 48.22 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 80.51 | 43.29 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 65.54 | 29.19 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.17 | 9.04 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 63.06 | 8.29 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 65.29 | 5.80 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 77.38 | 8.50 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 86.18 | 11.64 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 123.15 | 19.72 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 134.76 | 39.16 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 134.17 | 50.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 95.53 | 27.25 | 1.50 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.17 | 5.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 134.76 | 55.24 | 1.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.45 | 76.63 | 30.82 | 159.46 | 65.27 | 1.50 | 0.00 | 0.00 |
February | 97.45 | 63.08 | 34.37 | 146.87 | 57.02 | 0.00 | 0.00 | 0.00 |
March | 62.21 | 28.08 | 34.14 | 96.44 | 51.16 | 0.00 | 0.00 | 0.00 |
April | 46.11 | 10.81 | 35.31 | 78.34 | 34.59 | 0.00 | 0.00 | 0.00 |
May | 35.23 | 1.50 | 33.74 | 73.99 | 10.77 | 0.00 | 0.00 | 0.00 |
June | 34.80 | 0.32 | 34.48 | 74.98 | 9.88 | 0.00 | 0.00 | 0.00 |
July | 36.43 | 0.67 | 35.76 | 77.66 | 6.95 | 0.00 | 0.00 | 0.00 |
August | 42.86 | 5.14 | 37.72 | 92.14 | 10.14 | 0.00 | 0.00 | 0.00 |
September | 51.43 | 13.55 | 37.87 | 102.77 | 13.86 | 0.00 | 0.00 | 0.00 |
October | 79.79 | 41.56 | 38.23 | 147.06 | 23.40 | 0.00 | 0.00 | 0.00 |
November | 101.54 | 69.91 | 31.63 | 161.14 | 46.39 | 0.00 | 0.00 | 0.00 |
December | 104.99 | 75.40 | 29.59 | 160.57 | 59.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.53 | 32.06 | 34.47 | 114.13 | 32.27 | 1.50 | 0.00 | 0.00 |
Minimum of Months | 34.80 | 0.32 | 29.59 | 73.99 | 6.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.45 | 76.63 | 38.23 | 161.14 | 65.27 | 1.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 133.49 | 54.47 | 1.50 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 122.98 | 47.51 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 80.79 | 42.64 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 65.70 | 28.79 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.30 | 8.76 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 63.18 | 8.03 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 65.42 | 5.58 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 77.49 | 8.25 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 86.27 | 11.39 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 123.24 | 19.44 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 134.93 | 38.77 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 134.43 | 49.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 95.72 | 26.83 | 1.50 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.30 | 5.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 134.93 | 54.47 | 1.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 133.49 | 54.47 | 1.50 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 122.98 | 47.51 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 80.79 | 42.64 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 65.70 | 28.79 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.30 | 8.76 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 63.18 | 8.03 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 65.42 | 5.58 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 77.49 | 8.25 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 86.27 | 11.39 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 123.24 | 19.44 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 134.93 | 38.77 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 134.43 | 49.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 95.72 | 26.83 | 1.50 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.30 | 5.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 134.93 | 54.47 | 1.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.45 | 76.63 | 30.82 | 159.90 | 64.36 | 1.50 | 0.00 | 0.00 |
February | 97.45 | 63.08 | 34.37 | 147.29 | 56.19 | 0.00 | 0.00 | 0.00 |
March | 62.21 | 28.08 | 34.14 | 96.78 | 50.39 | 0.00 | 0.00 | 0.00 |
April | 46.11 | 10.81 | 35.31 | 78.54 | 34.11 | 0.00 | 0.00 | 0.00 |
May | 35.23 | 1.50 | 33.74 | 74.15 | 10.45 | 0.00 | 0.00 | 0.00 |
June | 34.80 | 0.32 | 34.48 | 75.13 | 9.57 | 0.00 | 0.00 | 0.00 |
July | 36.43 | 0.67 | 35.76 | 77.81 | 6.69 | 0.00 | 0.00 | 0.00 |
August | 42.86 | 5.14 | 37.72 | 92.27 | 9.84 | 0.00 | 0.00 | 0.00 |
September | 51.43 | 13.55 | 37.87 | 102.88 | 13.57 | 0.00 | 0.00 | 0.00 |
October | 79.79 | 41.56 | 38.23 | 147.17 | 23.07 | 0.00 | 0.00 | 0.00 |
November | 101.54 | 69.91 | 31.63 | 161.35 | 45.93 | 0.00 | 0.00 | 0.00 |
December | 104.99 | 75.40 | 29.59 | 160.88 | 58.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.53 | 32.06 | 34.47 | 114.35 | 31.78 | 1.50 | 0.00 | 0.00 |
Minimum of Months | 34.80 | 0.32 | 29.59 | 74.15 | 6.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.45 | 76.63 | 38.23 | 161.35 | 64.36 | 1.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 134.48 | 52.68 | 1.67 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 123.97 | 45.81 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 81.56 | 40.90 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 66.10 | 27.52 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.30 | 7.82 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 63.10 | 7.06 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 65.38 | 4.84 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 77.42 | 7.32 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 86.11 | 10.43 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 123.30 | 18.44 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.39 | 37.59 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 135.12 | 48.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 96.05 | 25.60 | 1.67 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.30 | 4.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.39 | 52.68 | 1.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 134.48 | 52.68 | 1.67 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 123.97 | 45.81 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 81.56 | 40.90 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 66.10 | 27.52 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.30 | 7.82 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 63.10 | 7.06 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 65.38 | 4.84 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 77.42 | 7.32 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 86.11 | 10.43 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 123.30 | 18.44 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.39 | 37.59 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 135.12 | 48.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 96.05 | 25.60 | 1.67 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.30 | 4.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.39 | 52.68 | 1.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 134.48 | 52.68 | 1.67 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 123.97 | 45.81 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 81.56 | 40.90 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 66.10 | 27.52 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.30 | 7.82 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 63.10 | 7.06 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 65.38 | 4.84 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 77.42 | 7.32 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 86.11 | 10.43 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 123.30 | 18.44 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.39 | 37.59 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 135.12 | 48.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 96.05 | 25.60 | 1.67 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.30 | 4.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.39 | 52.68 | 1.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 134.48 | 52.68 | 1.67 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 123.97 | 45.81 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 81.56 | 40.90 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 66.10 | 27.52 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.30 | 7.82 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 63.10 | 7.06 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 65.38 | 4.84 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 77.42 | 7.32 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 86.11 | 10.43 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 123.30 | 18.44 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.39 | 37.59 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 135.12 | 48.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 96.05 | 25.60 | 1.67 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.30 | 4.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.39 | 52.68 | 1.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.45 | 76.63 | 30.82 | 161.03 | 62.27 | 1.67 | 0.00 | 0.00 |
February | 97.45 | 63.08 | 34.37 | 148.42 | 54.19 | 0.00 | 0.00 | 0.00 |
March | 62.21 | 28.08 | 34.14 | 97.65 | 48.36 | 0.00 | 0.00 | 0.00 |
April | 46.11 | 10.81 | 35.31 | 78.99 | 32.63 | 0.00 | 0.00 | 0.00 |
May | 35.23 | 1.50 | 33.74 | 74.16 | 9.33 | 0.00 | 0.00 | 0.00 |
June | 34.80 | 0.32 | 34.48 | 75.05 | 8.42 | 0.00 | 0.00 | 0.00 |
July | 36.43 | 0.67 | 35.76 | 77.78 | 5.81 | 0.00 | 0.00 | 0.00 |
August | 42.86 | 5.14 | 37.72 | 92.19 | 8.73 | 0.00 | 0.00 | 0.00 |
September | 51.43 | 13.55 | 37.87 | 102.69 | 12.44 | 0.00 | 0.00 | 0.00 |
October | 79.79 | 41.56 | 38.23 | 147.21 | 21.89 | 0.00 | 0.00 | 0.00 |
November | 101.54 | 69.91 | 31.63 | 161.86 | 44.55 | 0.00 | 0.00 | 0.00 |
December | 104.99 | 75.40 | 29.59 | 161.65 | 56.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.53 | 32.06 | 34.47 | 114.73 | 30.33 | 1.67 | 0.00 | 0.00 |
Minimum of Months | 34.80 | 0.32 | 29.59 | 74.16 | 5.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.45 | 76.63 | 38.23 | 161.86 | 62.27 | 1.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.45 | 76.63 | 30.82 | 161.03 | 62.27 | 1.67 | 0.00 | 0.00 |
February | 97.45 | 63.08 | 34.37 | 148.42 | 54.19 | 0.00 | 0.00 | 0.00 |
March | 62.21 | 28.08 | 34.14 | 97.65 | 48.36 | 0.00 | 0.00 | 0.00 |
April | 46.11 | 10.81 | 35.31 | 78.99 | 32.63 | 0.00 | 0.00 | 0.00 |
May | 35.23 | 1.50 | 33.74 | 74.16 | 9.33 | 0.00 | 0.00 | 0.00 |
June | 34.80 | 0.32 | 34.48 | 75.05 | 8.42 | 0.00 | 0.00 | 0.00 |
July | 36.43 | 0.67 | 35.76 | 77.78 | 5.81 | 0.00 | 0.00 | 0.00 |
August | 42.86 | 5.14 | 37.72 | 92.19 | 8.73 | 0.00 | 0.00 | 0.00 |
September | 51.43 | 13.55 | 37.87 | 102.69 | 12.44 | 0.00 | 0.00 | 0.00 |
October | 79.79 | 41.56 | 38.23 | 147.21 | 21.89 | 0.00 | 0.00 | 0.00 |
November | 101.54 | 69.91 | 31.63 | 161.86 | 44.55 | 0.00 | 0.00 | 0.00 |
December | 104.99 | 75.40 | 29.59 | 161.65 | 56.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.53 | 32.06 | 34.47 | 114.73 | 30.33 | 1.67 | 0.00 | 0.00 |
Minimum of Months | 34.80 | 0.32 | 29.59 | 74.16 | 5.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.45 | 76.63 | 38.23 | 161.86 | 62.27 | 1.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 134.32 | 52.45 | 1.67 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 123.84 | 45.55 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 81.48 | 40.66 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 66.11 | 27.26 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.56 | 7.47 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 63.41 | 6.70 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 65.76 | 4.51 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 77.70 | 6.93 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 86.26 | 10.02 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 123.32 | 18.07 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.27 | 37.34 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 134.96 | 47.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 96.12 | 25.29 | 1.67 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.56 | 4.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.27 | 52.45 | 1.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 134.32 | 52.45 | 1.67 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 123.84 | 45.55 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 81.48 | 40.66 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 66.11 | 27.26 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.56 | 7.47 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 63.41 | 6.70 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 65.76 | 4.51 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 77.70 | 6.93 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 86.26 | 10.02 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 123.32 | 18.07 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.27 | 37.34 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 134.96 | 47.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 96.12 | 25.29 | 1.67 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.56 | 4.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.27 | 52.45 | 1.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.45 | 76.63 | 30.82 | 160.89 | 61.98 | 1.67 | 0.00 | 0.00 |
February | 97.45 | 63.08 | 34.37 | 148.32 | 53.87 | 0.00 | 0.00 | 0.00 |
March | 62.21 | 28.08 | 34.14 | 97.61 | 48.06 | 0.00 | 0.00 | 0.00 |
April | 46.11 | 10.81 | 35.31 | 79.03 | 32.31 | 0.00 | 0.00 | 0.00 |
May | 35.23 | 1.50 | 33.74 | 74.47 | 8.93 | 0.00 | 0.00 | 0.00 |
June | 34.80 | 0.32 | 34.48 | 75.42 | 8.00 | 0.00 | 0.00 | 0.00 |
July | 36.43 | 0.67 | 35.76 | 78.22 | 5.43 | 0.00 | 0.00 | 0.00 |
August | 42.86 | 5.14 | 37.72 | 92.53 | 8.28 | 0.00 | 0.00 | 0.00 |
September | 51.43 | 13.55 | 37.87 | 102.88 | 11.96 | 0.00 | 0.00 | 0.00 |
October | 79.79 | 41.56 | 38.23 | 147.28 | 21.45 | 0.00 | 0.00 | 0.00 |
November | 101.54 | 69.91 | 31.63 | 161.77 | 44.24 | 0.00 | 0.00 | 0.00 |
December | 104.99 | 75.40 | 29.59 | 161.53 | 56.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.53 | 32.06 | 34.47 | 114.83 | 29.96 | 1.67 | 0.00 | 0.00 |
Minimum of Months | 34.80 | 0.32 | 29.59 | 74.47 | 5.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.45 | 76.63 | 38.23 | 161.77 | 61.98 | 1.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 134.49 | 52.16 | 1.67 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 124.02 | 45.25 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 81.62 | 40.38 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 66.20 | 27.09 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.63 | 7.39 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 63.48 | 6.62 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 65.83 | 4.46 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 77.75 | 6.87 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 86.31 | 9.95 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 123.38 | 17.97 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.36 | 37.18 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 135.10 | 47.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 96.21 | 25.13 | 1.67 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.63 | 4.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.36 | 52.16 | 1.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 134.49 | 52.16 | 1.67 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 124.02 | 45.25 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 81.62 | 40.38 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 66.20 | 27.09 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.63 | 7.39 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 63.48 | 6.62 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 65.83 | 4.46 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 77.75 | 6.87 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 86.31 | 9.95 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 123.38 | 17.97 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.36 | 37.18 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 135.10 | 47.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 96.21 | 25.13 | 1.67 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.63 | 4.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.36 | 52.16 | 1.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.45 | 76.63 | 30.82 | 161.09 | 61.63 | 1.67 | 0.00 | 0.00 |
February | 97.45 | 63.08 | 34.37 | 148.53 | 53.52 | 0.00 | 0.00 | 0.00 |
March | 62.21 | 28.08 | 34.14 | 97.77 | 47.74 | 0.00 | 0.00 | 0.00 |
April | 46.11 | 10.81 | 35.31 | 79.13 | 32.12 | 0.00 | 0.00 | 0.00 |
May | 35.23 | 1.50 | 33.74 | 74.56 | 8.83 | 0.00 | 0.00 | 0.00 |
June | 34.80 | 0.32 | 34.48 | 75.50 | 7.91 | 0.00 | 0.00 | 0.00 |
July | 36.43 | 0.67 | 35.76 | 78.31 | 5.36 | 0.00 | 0.00 | 0.00 |
August | 42.86 | 5.14 | 37.72 | 92.60 | 8.21 | 0.00 | 0.00 | 0.00 |
September | 51.43 | 13.55 | 37.87 | 102.94 | 11.87 | 0.00 | 0.00 | 0.00 |
October | 79.79 | 41.56 | 38.23 | 147.35 | 21.34 | 0.00 | 0.00 | 0.00 |
November | 101.54 | 69.91 | 31.63 | 161.88 | 44.06 | 0.00 | 0.00 | 0.00 |
December | 104.99 | 75.40 | 29.59 | 161.68 | 56.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.53 | 32.06 | 34.47 | 114.95 | 29.77 | 1.67 | 0.00 | 0.00 |
Minimum of Months | 34.80 | 0.32 | 29.59 | 74.56 | 5.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.45 | 76.63 | 38.23 | 161.88 | 61.63 | 1.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 134.84 | 51.48 | 1.67 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 124.40 | 44.53 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 81.90 | 39.69 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 66.37 | 26.69 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.66 | 7.31 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 63.47 | 6.60 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 65.76 | 4.49 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 77.67 | 6.94 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 86.25 | 9.99 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 123.37 | 17.92 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.54 | 36.86 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 135.38 | 46.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 96.33 | 24.85 | 1.67 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.66 | 4.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.54 | 51.48 | 1.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 134.84 | 51.48 | 1.67 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 124.40 | 44.53 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 81.90 | 39.69 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 66.37 | 26.69 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.66 | 7.31 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 63.47 | 6.60 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 65.76 | 4.49 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 77.67 | 6.94 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 86.25 | 9.99 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 123.37 | 17.92 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.54 | 36.86 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 135.38 | 46.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 96.33 | 24.85 | 1.67 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.66 | 4.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.54 | 51.48 | 1.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.45 | 76.63 | 30.82 | 161.51 | 60.83 | 1.67 | 0.00 | 0.00 |
February | 97.45 | 63.08 | 34.37 | 148.99 | 52.67 | 0.00 | 0.00 | 0.00 |
March | 62.21 | 28.08 | 34.14 | 98.11 | 46.92 | 0.00 | 0.00 | 0.00 |
April | 46.11 | 10.81 | 35.31 | 79.34 | 31.65 | 0.00 | 0.00 | 0.00 |
May | 35.23 | 1.50 | 33.74 | 74.59 | 8.74 | 0.00 | 0.00 | 0.00 |
June | 34.80 | 0.32 | 34.48 | 75.49 | 7.88 | 0.00 | 0.00 | 0.00 |
July | 36.43 | 0.67 | 35.76 | 78.22 | 5.40 | 0.00 | 0.00 | 0.00 |
August | 42.86 | 5.14 | 37.72 | 92.49 | 8.29 | 0.00 | 0.00 | 0.00 |
September | 51.43 | 13.55 | 37.87 | 102.87 | 11.92 | 0.00 | 0.00 | 0.00 |
October | 79.79 | 41.56 | 38.23 | 147.35 | 21.28 | 0.00 | 0.00 | 0.00 |
November | 101.54 | 69.91 | 31.63 | 162.09 | 43.68 | 0.00 | 0.00 | 0.00 |
December | 104.99 | 75.40 | 29.59 | 162.02 | 55.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.53 | 32.06 | 34.47 | 115.09 | 29.44 | 1.67 | 0.00 | 0.00 |
Minimum of Months | 34.80 | 0.32 | 29.59 | 74.59 | 5.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.45 | 76.63 | 38.23 | 162.09 | 60.83 | 1.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 135.45 | 49.06 | 0.00 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 125.13 | 41.97 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 82.29 | 37.11 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 66.51 | 25.08 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.15 | 7.11 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 62.72 | 6.61 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 64.71 | 4.78 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 76.58 | 7.48 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 85.40 | 10.37 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 122.81 | 17.87 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.69 | 35.69 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 135.89 | 44.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 96.14 | 23.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.15 | 4.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.89 | 49.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 135.45 | 49.06 | 0.00 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 125.13 | 41.97 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 82.29 | 37.11 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 66.51 | 25.08 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.15 | 7.11 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 62.72 | 6.61 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 64.71 | 4.78 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 76.58 | 7.48 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 85.40 | 10.37 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 122.81 | 17.87 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.69 | 35.69 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 135.89 | 44.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 96.14 | 23.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.15 | 4.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.89 | 49.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.45 | 76.63 | 30.82 | 162.24 | 57.98 | 0.00 | 0.00 | 0.00 |
February | 97.45 | 63.08 | 34.37 | 149.86 | 49.66 | 0.00 | 0.00 | 0.00 |
March | 62.21 | 28.08 | 34.14 | 98.57 | 43.89 | 0.00 | 0.00 | 0.00 |
April | 46.11 | 10.81 | 35.31 | 79.51 | 29.75 | 0.00 | 0.00 | 0.00 |
May | 35.23 | 1.50 | 33.74 | 73.98 | 8.49 | 0.00 | 0.00 | 0.00 |
June | 34.80 | 0.32 | 34.48 | 74.59 | 7.89 | 0.00 | 0.00 | 0.00 |
July | 36.43 | 0.67 | 35.76 | 76.97 | 5.75 | 0.00 | 0.00 | 0.00 |
August | 42.86 | 5.14 | 37.72 | 91.20 | 8.94 | 0.00 | 0.00 | 0.00 |
September | 51.43 | 13.55 | 37.87 | 101.85 | 12.38 | 0.00 | 0.00 | 0.00 |
October | 79.79 | 41.56 | 38.23 | 146.66 | 21.23 | 0.00 | 0.00 | 0.00 |
November | 101.54 | 69.91 | 31.63 | 162.27 | 42.30 | 0.00 | 0.00 | 0.00 |
December | 104.99 | 75.40 | 29.59 | 162.63 | 52.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.53 | 32.06 | 34.47 | 114.85 | 28.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.80 | 0.32 | 29.59 | 73.98 | 5.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.45 | 76.63 | 38.23 | 162.63 | 57.98 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.358848E+09 | 0.144021E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.298493E+09 | 0.113512E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.217535E+09 | 0.111269E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.171140E+09 | 71118051.92 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.168321E+09 | 18536026.74 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.164918E+09 | 15705866.50 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.178382E+09 | 10620837.66 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.208861E+09 | 17532781.61 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.224622E+09 | 24269683.83 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.330912E+09 | 46420904.31 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.350484E+09 | 97552120.41 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.360943E+09 | 0.130678E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.303346E+10 | 0.801236E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.164918E+09 | 10620837.66 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.360943E+09 | 0.144021E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.358848E+09 | 0.144021E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.298493E+09 | 0.113512E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.217535E+09 | 0.111269E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.171140E+09 | 71118051.92 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.168321E+09 | 18536026.74 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.164918E+09 | 15705866.50 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.178382E+09 | 10620837.66 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.208861E+09 | 17532781.61 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.224622E+09 | 24269683.83 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.330912E+09 | 46420904.31 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.350484E+09 | 97552120.41 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.360943E+09 | 0.130678E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.303346E+10 | 0.801236E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.164918E+09 | 10620837.66 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.360943E+09 | 0.144021E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.358848E+09 | 0.144021E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.298493E+09 | 0.113512E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.217535E+09 | 0.111269E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.171140E+09 | 71118051.92 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.168321E+09 | 18536026.74 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.164918E+09 | 15705866.50 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.178382E+09 | 10620837.66 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.208861E+09 | 17532781.61 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.224622E+09 | 24269683.83 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.330912E+09 | 46420904.31 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.350484E+09 | 97552120.41 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.360943E+09 | 0.130678E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.303346E+10 | 0.801236E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.164918E+09 | 10620837.66 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.360943E+09 | 0.144021E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.358848E+09 | 0.144021E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.298493E+09 | 0.113512E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.217535E+09 | 0.111269E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.171140E+09 | 71118051.92 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.168321E+09 | 18536026.74 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.164918E+09 | 15705866.50 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.178382E+09 | 10620837.66 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.208861E+09 | 17532781.61 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.224622E+09 | 24269683.83 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.330912E+09 | 46420904.31 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.350484E+09 | 97552120.41 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.360943E+09 | 0.130678E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.303346E+10 | 0.801236E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.164918E+09 | 10620837.66 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.360943E+09 | 0.144021E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.289368E+09 | 0.206369E+09 | 82998250.47 | 0.432026E+09 | 0.171230E+09 |
February | 0.237043E+09 | 0.153434E+09 | 83608932.79 | 0.359314E+09 | 0.135068E+09 |
March | 0.167547E+09 | 75614314.65 | 91933022.62 | 0.261892E+09 | 0.132343E+09 |
April | 0.120178E+09 | 28160696.70 | 92017377.45 | 0.205616E+09 | 84852968.00 |
May | 94885545.44 | 4032502.60 | 90853042.84 | 0.201361E+09 | 22311773.37 |
June | 90707111.54 | 845477.76 | 89861633.79 | 0.197125E+09 | 18912939.98 |
July | 98120832.69 | 1803450.40 | 96317382.29 | 0.213170E+09 | 12859998.89 |
August | 0.115434E+09 | 13855553.09 | 0.101578E+09 | 0.249942E+09 | 21102786.69 |
September | 0.134034E+09 | 35323541.73 | 98710078.52 | 0.269213E+09 | 29194110.01 |
October | 0.214886E+09 | 0.111935E+09 | 0.102951E+09 | 0.397200E+09 | 55515088.34 |
November | 0.264635E+09 | 0.182204E+09 | 82431092.21 | 0.421281E+09 | 0.116316E+09 |
December | 0.282747E+09 | 0.203054E+09 | 79693274.94 | 0.434182E+09 | 0.155477E+09 |
Annual Sum or Average | 0.210959E+10 | 0.101663E+10 | 0.109295E+10 | 0.364232E+10 | 0.955184E+09 |
Minimum of Months | 90707111.54 | 845477.76 | 79693274.94 | 0.197125E+09 | 12859998.89 |
Maximum of Months | 0.289368E+09 | 0.206369E+09 | 0.102951E+09 | 0.434182E+09 | 0.171230E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.289368E+09 | 0.206369E+09 | 82998250.47 | 0.432026E+09 | 0.171230E+09 |
February | 0.237043E+09 | 0.153434E+09 | 83608932.79 | 0.359314E+09 | 0.135068E+09 |
March | 0.167547E+09 | 75614314.65 | 91933022.62 | 0.261892E+09 | 0.132343E+09 |
April | 0.120178E+09 | 28160696.70 | 92017377.45 | 0.205616E+09 | 84852968.00 |
May | 94885545.44 | 4032502.60 | 90853042.84 | 0.201361E+09 | 22311773.37 |
June | 90707111.54 | 845477.76 | 89861633.79 | 0.197125E+09 | 18912939.98 |
July | 98120832.69 | 1803450.40 | 96317382.29 | 0.213170E+09 | 12859998.89 |
August | 0.115434E+09 | 13855553.09 | 0.101578E+09 | 0.249942E+09 | 21102786.69 |
September | 0.134034E+09 | 35323541.73 | 98710078.52 | 0.269213E+09 | 29194110.01 |
October | 0.214886E+09 | 0.111935E+09 | 0.102951E+09 | 0.397200E+09 | 55515088.34 |
November | 0.264635E+09 | 0.182204E+09 | 82431092.21 | 0.421281E+09 | 0.116316E+09 |
December | 0.282747E+09 | 0.203054E+09 | 79693274.94 | 0.434182E+09 | 0.155477E+09 |
Annual Sum or Average | 0.210959E+10 | 0.101663E+10 | 0.109295E+10 | 0.364232E+10 | 0.955184E+09 |
Minimum of Months | 90707111.54 | 845477.76 | 79693274.94 | 0.197125E+09 | 12859998.89 |
Maximum of Months | 0.289368E+09 | 0.206369E+09 | 0.102951E+09 | 0.434182E+09 | 0.171230E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.354551E+09 | 0.152768E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.295283E+09 | 0.119444E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.214842E+09 | 0.117543E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.170148E+09 | 73107425.01 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.168603E+09 | 19123920.22 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.165663E+09 | 16052162.94 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.179449E+09 | 10753604.61 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.210157E+09 | 17301059.57 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.225363E+09 | 24137822.11 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.331061E+09 | 46688269.22 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.348949E+09 | 99537577.59 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.358227E+09 | 0.136447E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.302230E+10 | 0.832904E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.165663E+09 | 10753604.61 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.358227E+09 | 0.152768E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.354551E+09 | 0.152768E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.295283E+09 | 0.119444E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.214842E+09 | 0.117543E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.170148E+09 | 73107425.01 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.168603E+09 | 19123920.22 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.165663E+09 | 16052162.94 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.179449E+09 | 10753604.61 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.210157E+09 | 17301059.57 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.225363E+09 | 24137822.11 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.331061E+09 | 46688269.22 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.348949E+09 | 99537577.59 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.358227E+09 | 0.136447E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.302230E+10 | 0.832904E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.165663E+09 | 10753604.61 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.358227E+09 | 0.152768E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.289368E+09 | 0.206369E+09 | 82998250.47 | 0.427061E+09 | 0.181466E+09 |
February | 0.237043E+09 | 0.153434E+09 | 83608932.79 | 0.355605E+09 | 0.142016E+09 |
March | 0.167547E+09 | 75614314.65 | 91933022.62 | 0.258767E+09 | 0.139706E+09 |
April | 0.120178E+09 | 28160696.70 | 92017377.45 | 0.204478E+09 | 87192429.16 |
May | 94885545.44 | 4032502.60 | 90853042.84 | 0.201704E+09 | 23017432.15 |
June | 90707111.54 | 845477.76 | 89861633.79 | 0.198008E+09 | 19331301.92 |
July | 98120832.69 | 1803450.40 | 96317382.29 | 0.214441E+09 | 13026558.52 |
August | 0.115434E+09 | 13855553.09 | 0.101578E+09 | 0.251516E+09 | 20826986.94 |
September | 0.134034E+09 | 35323541.73 | 98710078.52 | 0.270148E+09 | 29038559.33 |
October | 0.214886E+09 | 0.111935E+09 | 0.102951E+09 | 0.397474E+09 | 55814174.32 |
November | 0.264635E+09 | 0.182204E+09 | 82431092.21 | 0.419567E+09 | 0.118638E+09 |
December | 0.282747E+09 | 0.203054E+09 | 79693274.94 | 0.431077E+09 | 0.162223E+09 |
Annual Sum or Average | 0.210959E+10 | 0.101663E+10 | 0.109295E+10 | 0.362985E+10 | 0.992297E+09 |
Minimum of Months | 90707111.54 | 845477.76 | 79693274.94 | 0.198008E+09 | 13026558.52 |
Maximum of Months | 0.289368E+09 | 0.206369E+09 | 0.102951E+09 | 0.431077E+09 | 0.181466E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.355780E+09 | 0.149962E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.296085E+09 | 0.118127E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.215237E+09 | 0.117194E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.169800E+09 | 75976520.74 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.166650E+09 | 23794860.67 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.163617E+09 | 20990681.72 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.175182E+09 | 14934104.64 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.207443E+09 | 22188411.11 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.223573E+09 | 29627465.44 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.329940E+09 | 52379677.43 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.349131E+09 | 0.101956E+09 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.358934E+09 | 0.135998E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.301137E+10 | 0.863128E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.163617E+09 | 14934104.64 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.358934E+09 | 0.149962E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.355780E+09 | 0.149962E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.296085E+09 | 0.118127E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.215237E+09 | 0.117194E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.169800E+09 | 75976520.74 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.166650E+09 | 23794860.67 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.163617E+09 | 20990681.72 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.175182E+09 | 14934104.64 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.207443E+09 | 22188411.11 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.223573E+09 | 29627465.44 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.329940E+09 | 52379677.43 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.349131E+09 | 0.101956E+09 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.358934E+09 | 0.135998E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.301137E+10 | 0.863128E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.163617E+09 | 14934104.64 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.358934E+09 | 0.149962E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287786E+09 | 0.205242E+09 | 82544708.12 | 0.426184E+09 | 0.177169E+09 |
February | 0.235747E+09 | 0.152595E+09 | 83152053.37 | 0.354611E+09 | 0.139673E+09 |
March | 0.166632E+09 | 75201121.67 | 91430656.38 | 0.257821E+09 | 0.138499E+09 |
April | 0.119521E+09 | 28006813.11 | 91514550.25 | 0.202955E+09 | 90029720.12 |
May | 94367045.19 | 4010467.07 | 90356578.12 | 0.198345E+09 | 28362490.39 |
June | 90211444.27 | 840857.66 | 89370586.61 | 0.194561E+09 | 25016331.01 |
July | 97584653.27 | 1793595.48 | 95791057.80 | 0.208361E+09 | 17905126.38 |
August | 0.114803E+09 | 13779839.69 | 0.101023E+09 | 0.247018E+09 | 26458397.30 |
September | 0.133301E+09 | 35130516.91 | 98170679.18 | 0.266596E+09 | 35294182.95 |
October | 0.213712E+09 | 0.111324E+09 | 0.102388E+09 | 0.394004E+09 | 62149769.39 |
November | 0.263189E+09 | 0.181208E+09 | 81980649.09 | 0.417484E+09 | 0.120775E+09 |
December | 0.281202E+09 | 0.201944E+09 | 79257792.56 | 0.429557E+09 | 0.160776E+09 |
Annual Sum or Average | 0.209806E+10 | 0.101108E+10 | 0.108698E+10 | 0.359750E+10 | 0.102211E+10 |
Minimum of Months | 90211444.27 | 840857.66 | 79257792.56 | 0.194561E+09 | 17905126.38 |
Maximum of Months | 0.287786E+09 | 0.205242E+09 | 0.102388E+09 | 0.429557E+09 | 0.177169E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.356547E+09 | 0.147963E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.296664E+09 | 0.116654E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.215648E+09 | 0.115952E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.169889E+09 | 75670007.24 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.166515E+09 | 24200881.48 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.163441E+09 | 21491247.90 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.174873E+09 | 15524859.31 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.207245E+09 | 22779203.70 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.223386E+09 | 30158991.12 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.329833E+09 | 52825912.02 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.349292E+09 | 0.101515E+09 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.359368E+09 | 0.134684E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.301270E+10 | 0.859418E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.163441E+09 | 15524859.31 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.359368E+09 | 0.147963E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.356547E+09 | 0.147963E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.296664E+09 | 0.116654E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.215648E+09 | 0.115952E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.169889E+09 | 75670007.24 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.166515E+09 | 24200881.48 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.163441E+09 | 21491247.90 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.174873E+09 | 15524859.31 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.207245E+09 | 22779203.70 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.223386E+09 | 30158991.12 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.329833E+09 | 52825912.02 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.349292E+09 | 0.101515E+09 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.359368E+09 | 0.134684E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.301270E+10 | 0.859418E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.163441E+09 | 15524859.31 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.359368E+09 | 0.147963E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287786E+09 | 0.205242E+09 | 82544708.12 | 0.427097E+09 | 0.174811E+09 |
February | 0.235747E+09 | 0.152595E+09 | 83152053.37 | 0.355303E+09 | 0.137938E+09 |
March | 0.166632E+09 | 75201121.67 | 91430656.38 | 0.258311E+09 | 0.137033E+09 |
April | 0.119521E+09 | 28006813.11 | 91514550.25 | 0.203062E+09 | 89668050.06 |
May | 94367045.19 | 4010467.07 | 90356578.12 | 0.198183E+09 | 28841784.79 |
June | 90211444.27 | 840857.66 | 89370586.61 | 0.194352E+09 | 25608488.23 |
July | 97584653.27 | 1793595.48 | 95791057.80 | 0.207998E+09 | 18606073.26 |
August | 0.114803E+09 | 13779839.69 | 0.101023E+09 | 0.246781E+09 | 27155807.31 |
September | 0.133301E+09 | 35130516.91 | 98170679.18 | 0.266374E+09 | 35922402.94 |
October | 0.213712E+09 | 0.111324E+09 | 0.102388E+09 | 0.393875E+09 | 62674769.57 |
November | 0.263189E+09 | 0.181208E+09 | 81980649.09 | 0.417677E+09 | 0.120253E+09 |
December | 0.281202E+09 | 0.201944E+09 | 79257792.56 | 0.430077E+09 | 0.159226E+09 |
Annual Sum or Average | 0.209806E+10 | 0.101108E+10 | 0.108698E+10 | 0.359909E+10 | 0.101774E+10 |
Minimum of Months | 90211444.27 | 840857.66 | 79257792.56 | 0.194352E+09 | 18606073.26 |
Maximum of Months | 0.287786E+09 | 0.205242E+09 | 0.102388E+09 | 0.430077E+09 | 0.174811E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.357535E+09 | 0.145903E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.297520E+09 | 0.114948E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.216399E+09 | 0.114197E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.170306E+09 | 74613481.72 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.166867E+09 | 23475339.81 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.163770E+09 | 20814500.11 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.175220E+09 | 14950136.46 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.207540E+09 | 22102921.83 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.223622E+09 | 29512638.68 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.330085E+09 | 52076884.35 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.349751E+09 | 0.100489E+09 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.360054E+09 | 0.133033E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.301867E+10 | 0.846116E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.163770E+09 | 14950136.46 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.360054E+09 | 0.145903E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.357535E+09 | 0.145903E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.297520E+09 | 0.114948E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.216399E+09 | 0.114197E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.170306E+09 | 74613481.72 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.166867E+09 | 23475339.81 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.163770E+09 | 20814500.11 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.175220E+09 | 14950136.46 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.207540E+09 | 22102921.83 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.223622E+09 | 29512638.68 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.330085E+09 | 52076884.35 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.349751E+09 | 0.100489E+09 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.360054E+09 | 0.133033E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.301867E+10 | 0.846116E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.163770E+09 | 14950136.46 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.360054E+09 | 0.145903E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287786E+09 | 0.205242E+09 | 82544708.12 | 0.428274E+09 | 0.172384E+09 |
February | 0.235747E+09 | 0.152595E+09 | 83152053.37 | 0.356326E+09 | 0.135931E+09 |
March | 0.166632E+09 | 75201121.67 | 91430656.38 | 0.259210E+09 | 0.134968E+09 |
April | 0.119521E+09 | 28006813.11 | 91514550.25 | 0.203564E+09 | 88424823.82 |
May | 94367045.19 | 4010467.07 | 90356578.12 | 0.198603E+09 | 27989247.02 |
June | 90211444.27 | 840857.66 | 89370586.61 | 0.194744E+09 | 24812564.17 |
July | 97584653.27 | 1793595.48 | 95791057.80 | 0.208411E+09 | 17929688.97 |
August | 0.114803E+09 | 13779839.69 | 0.101023E+09 | 0.247134E+09 | 26361251.03 |
September | 0.133301E+09 | 35130516.91 | 98170679.18 | 0.266656E+09 | 35162322.57 |
October | 0.213712E+09 | 0.111324E+09 | 0.102388E+09 | 0.394179E+09 | 61795885.74 |
November | 0.263189E+09 | 0.181208E+09 | 81980649.09 | 0.418227E+09 | 0.119045E+09 |
December | 0.281202E+09 | 0.201944E+09 | 79257792.56 | 0.430896E+09 | 0.157282E+09 |
Annual Sum or Average | 0.209806E+10 | 0.101108E+10 | 0.108698E+10 | 0.360622E+10 | 0.100209E+10 |
Minimum of Months | 90211444.27 | 840857.66 | 79257792.56 | 0.194744E+09 | 17929688.97 |
Maximum of Months | 0.287786E+09 | 0.205242E+09 | 0.102388E+09 | 0.430896E+09 | 0.172384E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.360198E+09 | 0.141105E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.299907E+09 | 0.110816E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.218437E+09 | 0.109549E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.171330E+09 | 71344785.49 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.166874E+09 | 20952483.13 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.163544E+09 | 18288612.85 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.175125E+09 | 12974574.08 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.207355E+09 | 19593441.58 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.223204E+09 | 27038190.37 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.330240E+09 | 49390518.46 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.350920E+09 | 97440341.92 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.361901E+09 | 0.128767E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.302904E+10 | 0.807260E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.163544E+09 | 12974574.08 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.361901E+09 | 0.141105E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.360198E+09 | 0.141105E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.299907E+09 | 0.110816E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.218437E+09 | 0.109549E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.171330E+09 | 71344785.49 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.166874E+09 | 20952483.13 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.163544E+09 | 18288612.85 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.175125E+09 | 12974574.08 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.207355E+09 | 19593441.58 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.223204E+09 | 27038190.37 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.330240E+09 | 49390518.46 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.350920E+09 | 97440341.92 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.361901E+09 | 0.128767E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.302904E+10 | 0.807260E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.163544E+09 | 12974574.08 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.361901E+09 | 0.141105E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.360198E+09 | 0.141105E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.299907E+09 | 0.110816E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.218437E+09 | 0.109549E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.171330E+09 | 71344785.49 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.166874E+09 | 20952483.13 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.163544E+09 | 18288612.85 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.175125E+09 | 12974574.08 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.207355E+09 | 19593441.58 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.223204E+09 | 27038190.37 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.330240E+09 | 49390518.46 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.350920E+09 | 97440341.92 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.361901E+09 | 0.128767E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.302904E+10 | 0.807260E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.163544E+09 | 12974574.08 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.361901E+09 | 0.141105E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.360198E+09 | 0.141105E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.299907E+09 | 0.110816E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.218437E+09 | 0.109549E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.171330E+09 | 71344785.49 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.166874E+09 | 20952483.13 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.163544E+09 | 18288612.85 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.175125E+09 | 12974574.08 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.207355E+09 | 19593441.58 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.223204E+09 | 27038190.37 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.330240E+09 | 49390518.46 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.350920E+09 | 97440341.92 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.361901E+09 | 0.128767E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.302904E+10 | 0.807260E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.163544E+09 | 12974574.08 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.361901E+09 | 0.141105E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287786E+09 | 0.205242E+09 | 82544708.12 | 0.431297E+09 | 0.166794E+09 |
February | 0.235747E+09 | 0.152595E+09 | 83152053.37 | 0.359053E+09 | 0.131103E+09 |
March | 0.166632E+09 | 75201121.67 | 91430656.38 | 0.261557E+09 | 0.129534E+09 |
April | 0.119521E+09 | 28006813.11 | 91514550.25 | 0.204750E+09 | 84588523.51 |
May | 94367045.19 | 4010467.07 | 90356578.12 | 0.198643E+09 | 24997674.17 |
June | 90211444.27 | 840857.66 | 89370586.61 | 0.194520E+09 | 21813539.25 |
July | 97584653.27 | 1793595.48 | 95791057.80 | 0.208332E+09 | 15570478.81 |
August | 0.114803E+09 | 13779839.69 | 0.101023E+09 | 0.246929E+09 | 23389842.94 |
September | 0.133301E+09 | 35130516.91 | 98170679.18 | 0.266164E+09 | 32239023.07 |
October | 0.213712E+09 | 0.111324E+09 | 0.102388E+09 | 0.394300E+09 | 58635154.42 |
November | 0.263189E+09 | 0.181208E+09 | 81980649.09 | 0.419533E+09 | 0.115473E+09 |
December | 0.281202E+09 | 0.201944E+09 | 79257792.56 | 0.432973E+09 | 0.152302E+09 |
Annual Sum or Average | 0.209806E+10 | 0.101108E+10 | 0.108698E+10 | 0.361805E+10 | 0.956441E+09 |
Minimum of Months | 90211444.27 | 840857.66 | 79257792.56 | 0.194520E+09 | 15570478.81 |
Maximum of Months | 0.287786E+09 | 0.205242E+09 | 0.102388E+09 | 0.432973E+09 | 0.166794E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287786E+09 | 0.205242E+09 | 82544708.12 | 0.431297E+09 | 0.166794E+09 |
February | 0.235747E+09 | 0.152595E+09 | 83152053.37 | 0.359053E+09 | 0.131103E+09 |
March | 0.166632E+09 | 75201121.67 | 91430656.38 | 0.261557E+09 | 0.129534E+09 |
April | 0.119521E+09 | 28006813.11 | 91514550.25 | 0.204750E+09 | 84588523.51 |
May | 94367045.19 | 4010467.07 | 90356578.12 | 0.198643E+09 | 24997674.17 |
June | 90211444.27 | 840857.66 | 89370586.61 | 0.194520E+09 | 21813539.25 |
July | 97584653.27 | 1793595.48 | 95791057.80 | 0.208332E+09 | 15570478.81 |
August | 0.114803E+09 | 13779839.69 | 0.101023E+09 | 0.246929E+09 | 23389842.94 |
September | 0.133301E+09 | 35130516.91 | 98170679.18 | 0.266164E+09 | 32239023.07 |
October | 0.213712E+09 | 0.111324E+09 | 0.102388E+09 | 0.394300E+09 | 58635154.42 |
November | 0.263189E+09 | 0.181208E+09 | 81980649.09 | 0.419533E+09 | 0.115473E+09 |
December | 0.281202E+09 | 0.201944E+09 | 79257792.56 | 0.432973E+09 | 0.152302E+09 |
Annual Sum or Average | 0.209806E+10 | 0.101108E+10 | 0.108698E+10 | 0.361805E+10 | 0.956441E+09 |
Minimum of Months | 90211444.27 | 840857.66 | 79257792.56 | 0.194520E+09 | 15570478.81 |
Maximum of Months | 0.287786E+09 | 0.205242E+09 | 0.102388E+09 | 0.432973E+09 | 0.166794E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.359753E+09 | 0.140489E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.299593E+09 | 0.110194E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.218238E+09 | 0.108909E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.171355E+09 | 70646865.89 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.167560E+09 | 20020331.53 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.164363E+09 | 17366626.72 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.176135E+09 | 12092910.67 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.208105E+09 | 18567448.82 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.223593E+09 | 25979172.83 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.330299E+09 | 48390013.85 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.350620E+09 | 96792071.83 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.361490E+09 | 0.128134E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.303110E+10 | 0.797581E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.164363E+09 | 12092910.67 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.361490E+09 | 0.140489E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.359753E+09 | 0.140489E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.299593E+09 | 0.110194E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.218238E+09 | 0.108909E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.171355E+09 | 70646865.89 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.167560E+09 | 20020331.53 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.164363E+09 | 17366626.72 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.176135E+09 | 12092910.67 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.208105E+09 | 18567448.82 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.223593E+09 | 25979172.83 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.330299E+09 | 48390013.85 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.350620E+09 | 96792071.83 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.361490E+09 | 0.128134E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.303110E+10 | 0.797581E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.164363E+09 | 12092910.67 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.361490E+09 | 0.140489E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287786E+09 | 0.205242E+09 | 82544708.12 | 0.430935E+09 | 0.166003E+09 |
February | 0.235747E+09 | 0.152595E+09 | 83152053.37 | 0.358816E+09 | 0.130328E+09 |
March | 0.166632E+09 | 75201121.67 | 91430656.38 | 0.261427E+09 | 0.128735E+09 |
April | 0.119521E+09 | 28006813.11 | 91514550.25 | 0.204845E+09 | 83754192.00 |
May | 94367045.19 | 4010467.07 | 90356578.12 | 0.199461E+09 | 23908404.74 |
June | 90211444.27 | 840857.66 | 89370586.61 | 0.195489E+09 | 20731915.42 |
July | 97584653.27 | 1793595.48 | 95791057.80 | 0.209517E+09 | 14533780.87 |
August | 0.114803E+09 | 13779839.69 | 0.101023E+09 | 0.247840E+09 | 22186105.82 |
September | 0.133301E+09 | 35130516.91 | 98170679.18 | 0.266674E+09 | 30999265.46 |
October | 0.213712E+09 | 0.111324E+09 | 0.102388E+09 | 0.394472E+09 | 57452800.68 |
November | 0.263189E+09 | 0.181208E+09 | 81980649.09 | 0.419303E+09 | 0.114681E+09 |
December | 0.281202E+09 | 0.201944E+09 | 79257792.56 | 0.432633E+09 | 0.151499E+09 |
Annual Sum or Average | 0.209806E+10 | 0.101108E+10 | 0.108698E+10 | 0.362141E+10 | 0.944812E+09 |
Minimum of Months | 90211444.27 | 840857.66 | 79257792.56 | 0.195489E+09 | 14533780.87 |
Maximum of Months | 0.287786E+09 | 0.205242E+09 | 0.102388E+09 | 0.432633E+09 | 0.166003E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.360206E+09 | 0.139695E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.300024E+09 | 0.109469E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.218605E+09 | 0.108166E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.171581E+09 | 70226592.23 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.167754E+09 | 19791384.46 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.164542E+09 | 17167896.46 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.176322E+09 | 11935997.62 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.208255E+09 | 18397226.08 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.223721E+09 | 25785349.38 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.330451E+09 | 48129104.25 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.350865E+09 | 96381696.21 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.361842E+09 | 0.127420E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.303417E+10 | 0.792566E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.164542E+09 | 11935997.62 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.361842E+09 | 0.139695E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.360206E+09 | 0.139695E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.300024E+09 | 0.109469E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.218605E+09 | 0.108166E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.171581E+09 | 70226592.23 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.167754E+09 | 19791384.46 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.164542E+09 | 17167896.46 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.176322E+09 | 11935997.62 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.208255E+09 | 18397226.08 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.223721E+09 | 25785349.38 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.330451E+09 | 48129104.25 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.350865E+09 | 96381696.21 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.361842E+09 | 0.127420E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.303417E+10 | 0.792566E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.164542E+09 | 11935997.62 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.361842E+09 | 0.139695E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287786E+09 | 0.205242E+09 | 82544708.12 | 0.431476E+09 | 0.165065E+09 |
February | 0.235747E+09 | 0.152595E+09 | 83152053.37 | 0.359331E+09 | 0.129474E+09 |
March | 0.166632E+09 | 75201121.67 | 91430656.38 | 0.261866E+09 | 0.127859E+09 |
April | 0.119521E+09 | 28006813.11 | 91514550.25 | 0.205117E+09 | 83258653.56 |
May | 94367045.19 | 4010467.07 | 90356578.12 | 0.199693E+09 | 23637471.43 |
June | 90211444.27 | 840857.66 | 89370586.61 | 0.195704E+09 | 20496408.70 |
July | 97584653.27 | 1793595.48 | 95791057.80 | 0.209739E+09 | 14346500.46 |
August | 0.114803E+09 | 13779839.69 | 0.101023E+09 | 0.248019E+09 | 21984396.61 |
September | 0.133301E+09 | 35130516.91 | 98170679.18 | 0.266828E+09 | 30770423.42 |
October | 0.213712E+09 | 0.111324E+09 | 0.102388E+09 | 0.394655E+09 | 57144293.64 |
November | 0.263189E+09 | 0.181208E+09 | 81980649.09 | 0.419595E+09 | 0.114194E+09 |
December | 0.281202E+09 | 0.201944E+09 | 79257792.56 | 0.433054E+09 | 0.150657E+09 |
Annual Sum or Average | 0.209806E+10 | 0.101108E+10 | 0.108698E+10 | 0.362508E+10 | 0.938888E+09 |
Minimum of Months | 90211444.27 | 840857.66 | 79257792.56 | 0.195704E+09 | 14346500.46 |
Maximum of Months | 0.287786E+09 | 0.205242E+09 | 0.102388E+09 | 0.433054E+09 | 0.165065E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.361144E+09 | 0.137884E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.300952E+09 | 0.107722E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.219361E+09 | 0.106309E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.172024E+09 | 69189178.18 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.167831E+09 | 19587712.29 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.164510E+09 | 17098756.18 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.176123E+09 | 12024137.50 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.208019E+09 | 18588726.71 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.223569E+09 | 25886565.51 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.330447E+09 | 47996479.30 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.351320E+09 | 95544329.75 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.362591E+09 | 0.125776E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.303789E+10 | 0.783607E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.164510E+09 | 12024137.50 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.362591E+09 | 0.137884E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.361144E+09 | 0.137884E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.300952E+09 | 0.107722E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.219361E+09 | 0.106309E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.172024E+09 | 69189178.18 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.167831E+09 | 19587712.29 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.164510E+09 | 17098756.18 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.176123E+09 | 12024137.50 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.208019E+09 | 18588726.71 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.223569E+09 | 25886565.51 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.330447E+09 | 47996479.30 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.351320E+09 | 95544329.75 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.362591E+09 | 0.125776E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.303789E+10 | 0.783607E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.164510E+09 | 12024137.50 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.362591E+09 | 0.137884E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287786E+09 | 0.205242E+09 | 82544708.12 | 0.432593E+09 | 0.162933E+09 |
February | 0.235747E+09 | 0.152595E+09 | 83152053.37 | 0.360435E+09 | 0.127416E+09 |
March | 0.166632E+09 | 75201121.67 | 91430656.38 | 0.262770E+09 | 0.125673E+09 |
April | 0.119521E+09 | 28006813.11 | 91514550.25 | 0.205646E+09 | 82040075.28 |
May | 94367045.19 | 4010467.07 | 90356578.12 | 0.199782E+09 | 23401676.36 |
June | 90211444.27 | 840857.66 | 89370586.61 | 0.195663E+09 | 20419563.11 |
July | 97584653.27 | 1793595.48 | 95791057.80 | 0.209499E+09 | 14455918.42 |
August | 0.114803E+09 | 13779839.69 | 0.101023E+09 | 0.247736E+09 | 22216839.47 |
September | 0.133301E+09 | 35130516.91 | 98170679.18 | 0.266646E+09 | 30895895.18 |
October | 0.213712E+09 | 0.111324E+09 | 0.102388E+09 | 0.394649E+09 | 56993075.63 |
November | 0.263189E+09 | 0.181208E+09 | 81980649.09 | 0.420136E+09 | 0.113209E+09 |
December | 0.281202E+09 | 0.201944E+09 | 79257792.56 | 0.433945E+09 | 0.148720E+09 |
Annual Sum or Average | 0.209806E+10 | 0.101108E+10 | 0.108698E+10 | 0.362950E+10 | 0.928375E+09 |
Minimum of Months | 90211444.27 | 840857.66 | 79257792.56 | 0.195663E+09 | 14455918.42 |
Maximum of Months | 0.287786E+09 | 0.205242E+09 | 0.102388E+09 | 0.433945E+09 | 0.162933E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.362778E+09 | 0.131393E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.302714E+09 | 0.101523E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.220395E+09 | 99401490.09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.172404E+09 | 65012460.39 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.166465E+09 | 19034588.61 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.162571E+09 | 17123400.39 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.173315E+09 | 12799824.44 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.205117E+09 | 20039183.97 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.221351E+09 | 26882103.72 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.328926E+09 | 47874057.42 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.351720E+09 | 92500607.48 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.363966E+09 | 0.119974E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.303172E+10 | 0.753557E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.162571E+09 | 12799824.44 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.363966E+09 | 0.131393E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.362778E+09 | 0.131393E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.302714E+09 | 0.101523E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.220395E+09 | 99401490.09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.172404E+09 | 65012460.39 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.166465E+09 | 19034588.61 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.162571E+09 | 17123400.39 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.173315E+09 | 12799824.44 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.205117E+09 | 20039183.97 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.221351E+09 | 26882103.72 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.328926E+09 | 47874057.42 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.351720E+09 | 92500607.48 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.363966E+09 | 0.119974E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.303172E+10 | 0.753557E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.162571E+09 | 12799824.44 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.363966E+09 | 0.131393E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287786E+09 | 0.205242E+09 | 82544708.12 | 0.434539E+09 | 0.155291E+09 |
February | 0.235747E+09 | 0.152595E+09 | 83152053.37 | 0.362537E+09 | 0.120127E+09 |
March | 0.166632E+09 | 75201121.67 | 91430656.38 | 0.264007E+09 | 0.117546E+09 |
April | 0.119521E+09 | 28006813.11 | 91514550.25 | 0.206093E+09 | 77124199.11 |
May | 94367045.19 | 4010467.07 | 90356578.12 | 0.198136E+09 | 22751967.69 |
June | 90211444.27 | 840857.66 | 89370586.61 | 0.193328E+09 | 20454476.40 |
July | 97584653.27 | 1793595.48 | 95791057.80 | 0.206151E+09 | 15390547.92 |
August | 0.114803E+09 | 13779839.69 | 0.101023E+09 | 0.244257E+09 | 23938605.49 |
September | 0.133301E+09 | 35130516.91 | 98170679.18 | 0.263983E+09 | 32080229.30 |
October | 0.213712E+09 | 0.111324E+09 | 0.102388E+09 | 0.392816E+09 | 56863286.61 |
November | 0.263189E+09 | 0.181208E+09 | 81980649.09 | 0.420599E+09 | 0.109630E+09 |
December | 0.281202E+09 | 0.201944E+09 | 79257792.56 | 0.435581E+09 | 0.141890E+09 |
Annual Sum or Average | 0.209806E+10 | 0.101108E+10 | 0.108698E+10 | 0.362203E+10 | 0.893088E+09 |
Minimum of Months | 90211444.27 | 840857.66 | 79257792.56 | 0.193328E+09 | 15390547.92 |
Maximum of Months | 0.287786E+09 | 0.205242E+09 | 0.102388E+09 | 0.435581E+09 | 0.155291E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 858.51 | 342.94 | 575.55 | 410.47 | 165.08 | 0.00 | 0.00 |
February | 790.59 | 299.35 | 522.00 | 337.88 | 184.12 | 0.00 | 0.00 |
March | 520.43 | 264.99 | 333.25 | 150.40 | 182.86 | 0.00 | 0.00 |
April | 422.76 | 175.22 | 247.00 | 57.88 | 189.12 | 0.00 | 0.00 |
May | 401.73 | 44.34 | 188.73 | 8.02 | 180.71 | 0.00 | 0.00 |
June | 406.60 | 38.83 | 186.43 | 1.74 | 184.69 | 0.00 | 0.00 |
July | 425.58 | 25.46 | 195.16 | 3.59 | 191.58 | 0.00 | 0.00 |
August | 498.55 | 41.94 | 229.60 | 27.56 | 202.04 | 0.00 | 0.00 |
September | 554.36 | 59.98 | 275.48 | 72.60 | 202.88 | 0.00 | 0.00 |
October | 790.79 | 110.78 | 427.41 | 222.64 | 204.77 | 0.00 | 0.00 |
November | 865.93 | 240.29 | 543.91 | 374.49 | 169.42 | 0.00 | 0.00 |
December | 863.25 | 311.26 | 562.39 | 403.88 | 158.51 | 0.00 | 0.00 |
Annual Sum or Average | 615.76 | 162.21 | 356.37 | 171.74 | 184.63 | 0.00 | 0.00 |
Minimum of Months | 401.73 | 25.46 | 186.43 | 1.74 | 158.51 | 0.00 | 0.00 |
Maximum of Months | 865.93 | 342.94 | 575.55 | 410.47 | 204.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 424.19 | 181.83 | 287.78 | 205.24 | 82.54 | 0.00 | 0.00 |
February | 391.11 | 157.45 | 261.00 | 168.94 | 92.06 | 0.00 | 0.00 |
March | 257.04 | 139.93 | 166.63 | 75.20 | 91.43 | 0.00 | 0.00 |
April | 210.18 | 90.05 | 123.50 | 28.94 | 94.56 | 0.00 | 0.00 |
May | 201.21 | 22.87 | 94.36 | 4.01 | 90.35 | 0.00 | 0.00 |
June | 204.22 | 19.84 | 93.22 | 0.87 | 92.35 | 0.00 | 0.00 |
July | 214.06 | 12.89 | 97.58 | 1.79 | 95.79 | 0.00 | 0.00 |
August | 250.83 | 20.69 | 114.80 | 13.78 | 101.02 | 0.00 | 0.00 |
September | 278.11 | 29.83 | 137.74 | 36.30 | 101.44 | 0.00 | 0.00 |
October | 395.61 | 55.70 | 213.71 | 111.32 | 102.39 | 0.00 | 0.00 |
November | 431.12 | 122.57 | 271.95 | 187.24 | 84.71 | 0.00 | 0.00 |
December | 428.44 | 162.45 | 281.19 | 201.94 | 79.26 | 0.00 | 0.00 |
Annual Sum or Average | 306.77 | 84.29 | 178.19 | 85.87 | 92.32 | 0.00 | 0.00 |
Minimum of Months | 201.21 | 12.89 | 93.22 | 0.87 | 79.26 | 0.00 | 0.00 |
Maximum of Months | 431.12 | 181.83 | 287.78 | 205.24 | 102.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 424.78 | 178.13 | 287.19 | 204.81 | 82.37 | 0.00 | 0.00 |
February | 391.36 | 155.39 | 260.46 | 168.59 | 91.87 | 0.00 | 0.00 |
March | 256.98 | 139.22 | 166.28 | 75.04 | 91.24 | 0.00 | 0.00 |
April | 209.32 | 93.36 | 123.25 | 28.88 | 94.37 | 0.00 | 0.00 |
May | 198.49 | 28.36 | 94.17 | 4.00 | 90.17 | 0.00 | 0.00 |
June | 201.31 | 25.85 | 93.02 | 0.87 | 92.16 | 0.00 | 0.00 |
July | 208.60 | 17.84 | 97.38 | 1.79 | 95.59 | 0.00 | 0.00 |
August | 247.13 | 26.45 | 114.56 | 13.75 | 100.81 | 0.00 | 0.00 |
September | 275.36 | 36.48 | 137.46 | 36.23 | 101.23 | 0.00 | 0.00 |
October | 393.48 | 62.32 | 213.27 | 111.09 | 102.17 | 0.00 | 0.00 |
November | 430.46 | 125.26 | 271.40 | 186.86 | 84.54 | 0.00 | 0.00 |
December | 428.40 | 161.58 | 280.62 | 201.52 | 79.09 | 0.00 | 0.00 |
Annual Sum or Average | 305.06 | 87.15 | 177.82 | 85.69 | 92.13 | 0.00 | 0.00 |
Minimum of Months | 198.49 | 17.84 | 93.02 | 0.87 | 79.09 | 0.00 | 0.00 |
Maximum of Months | 430.46 | 178.13 | 287.19 | 204.81 | 102.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 425.70 | 175.75 | 287.19 | 204.81 | 82.37 | 0.00 | 0.00 |
February | 392.13 | 153.46 | 260.46 | 168.59 | 91.87 | 0.00 | 0.00 |
March | 257.47 | 137.74 | 166.28 | 75.04 | 91.24 | 0.00 | 0.00 |
April | 209.43 | 92.98 | 123.25 | 28.88 | 94.37 | 0.00 | 0.00 |
May | 198.33 | 28.84 | 94.17 | 4.00 | 90.17 | 0.00 | 0.00 |
June | 201.09 | 26.46 | 93.02 | 0.87 | 92.16 | 0.00 | 0.00 |
July | 208.24 | 18.54 | 97.38 | 1.79 | 95.59 | 0.00 | 0.00 |
August | 246.89 | 27.15 | 114.56 | 13.75 | 100.81 | 0.00 | 0.00 |
September | 275.13 | 37.13 | 137.46 | 36.23 | 101.23 | 0.00 | 0.00 |
October | 393.35 | 62.85 | 213.27 | 111.09 | 102.17 | 0.00 | 0.00 |
November | 430.66 | 124.72 | 271.40 | 186.86 | 84.54 | 0.00 | 0.00 |
December | 428.92 | 160.02 | 280.62 | 201.52 | 79.09 | 0.00 | 0.00 |
Annual Sum or Average | 305.19 | 86.78 | 177.82 | 85.69 | 92.13 | 0.00 | 0.00 |
Minimum of Months | 198.33 | 18.54 | 93.02 | 0.87 | 79.09 | 0.00 | 0.00 |
Maximum of Months | 430.66 | 175.75 | 287.19 | 204.81 | 102.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 426.88 | 173.31 | 287.19 | 204.81 | 82.37 | 0.00 | 0.00 |
February | 393.26 | 151.22 | 260.46 | 168.59 | 91.87 | 0.00 | 0.00 |
March | 258.37 | 135.66 | 166.28 | 75.04 | 91.24 | 0.00 | 0.00 |
April | 209.94 | 91.69 | 123.25 | 28.88 | 94.37 | 0.00 | 0.00 |
May | 198.75 | 27.98 | 94.17 | 4.00 | 90.17 | 0.00 | 0.00 |
June | 201.50 | 25.63 | 93.02 | 0.87 | 92.16 | 0.00 | 0.00 |
July | 208.65 | 17.86 | 97.38 | 1.79 | 95.59 | 0.00 | 0.00 |
August | 247.24 | 26.35 | 114.56 | 13.75 | 100.81 | 0.00 | 0.00 |
September | 275.42 | 36.34 | 137.46 | 36.23 | 101.23 | 0.00 | 0.00 |
October | 393.65 | 61.96 | 213.27 | 111.09 | 102.17 | 0.00 | 0.00 |
November | 431.22 | 123.47 | 271.40 | 186.86 | 84.54 | 0.00 | 0.00 |
December | 429.74 | 158.06 | 280.62 | 201.52 | 79.09 | 0.00 | 0.00 |
Annual Sum or Average | 305.80 | 85.44 | 177.82 | 85.69 | 92.13 | 0.00 | 0.00 |
Minimum of Months | 198.75 | 17.86 | 93.02 | 0.87 | 79.09 | 0.00 | 0.00 |
Maximum of Months | 431.22 | 173.31 | 287.19 | 204.81 | 102.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 859.99 | 335.28 | 574.37 | 409.63 | 164.75 | 0.00 | 0.00 |
February | 792.71 | 291.61 | 520.92 | 337.19 | 183.74 | 0.00 | 0.00 |
March | 521.53 | 260.33 | 332.57 | 150.09 | 182.48 | 0.00 | 0.00 |
April | 422.38 | 175.37 | 246.50 | 57.76 | 188.74 | 0.00 | 0.00 |
May | 397.54 | 49.96 | 188.34 | 8.00 | 180.34 | 0.00 | 0.00 |
June | 402.48 | 45.05 | 186.05 | 1.73 | 184.31 | 0.00 | 0.00 |
July | 417.10 | 31.00 | 194.76 | 3.58 | 191.18 | 0.00 | 0.00 |
August | 494.05 | 46.73 | 229.13 | 27.50 | 201.63 | 0.00 | 0.00 |
September | 549.82 | 66.60 | 274.92 | 72.45 | 202.46 | 0.00 | 0.00 |
October | 787.62 | 117.54 | 426.53 | 222.18 | 204.35 | 0.00 | 0.00 |
November | 865.26 | 239.47 | 542.79 | 373.72 | 169.07 | 0.00 | 0.00 |
December | 863.78 | 306.03 | 561.23 | 403.05 | 158.19 | 0.00 | 0.00 |
Annual Sum or Average | 613.66 | 163.05 | 355.64 | 171.39 | 184.25 | 0.00 | 0.00 |
Minimum of Months | 397.54 | 31.00 | 186.05 | 1.73 | 158.19 | 0.00 | 0.00 |
Maximum of Months | 865.26 | 335.28 | 574.37 | 409.63 | 204.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 429.53 | 166.88 | 287.19 | 204.81 | 82.37 | 0.00 | 0.00 |
February | 396.00 | 144.97 | 260.46 | 168.59 | 91.87 | 0.00 | 0.00 |
March | 260.57 | 129.39 | 166.28 | 75.04 | 91.24 | 0.00 | 0.00 |
April | 211.25 | 86.82 | 123.25 | 28.88 | 94.37 | 0.00 | 0.00 |
May | 199.59 | 23.88 | 94.17 | 4.00 | 90.17 | 0.00 | 0.00 |
June | 202.24 | 21.40 | 93.02 | 0.87 | 92.16 | 0.00 | 0.00 |
July | 209.75 | 14.46 | 97.38 | 1.79 | 95.59 | 0.00 | 0.00 |
August | 247.93 | 22.15 | 114.56 | 13.75 | 100.81 | 0.00 | 0.00 |
September | 275.41 | 32.01 | 137.46 | 36.23 | 101.23 | 0.00 | 0.00 |
October | 393.92 | 57.58 | 213.27 | 111.09 | 102.17 | 0.00 | 0.00 |
November | 432.31 | 118.93 | 271.40 | 186.86 | 84.54 | 0.00 | 0.00 |
December | 431.46 | 152.24 | 280.62 | 201.52 | 79.09 | 0.00 | 0.00 |
Annual Sum or Average | 307.07 | 80.54 | 177.82 | 85.69 | 92.13 | 0.00 | 0.00 |
Minimum of Months | 199.59 | 14.46 | 93.02 | 0.87 | 79.09 | 0.00 | 0.00 |
Maximum of Months | 432.31 | 166.88 | 287.19 | 204.81 | 102.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 430.07 | 165.94 | 287.19 | 204.81 | 82.37 | 0.00 | 0.00 |
February | 396.57 | 144.02 | 260.46 | 168.59 | 91.87 | 0.00 | 0.00 |
March | 261.00 | 128.51 | 166.28 | 75.04 | 91.24 | 0.00 | 0.00 |
April | 211.53 | 86.31 | 123.25 | 28.88 | 94.37 | 0.00 | 0.00 |
May | 199.82 | 23.60 | 94.17 | 4.00 | 90.17 | 0.00 | 0.00 |
June | 202.46 | 21.15 | 93.02 | 0.87 | 92.16 | 0.00 | 0.00 |
July | 209.97 | 14.27 | 97.38 | 1.79 | 95.59 | 0.00 | 0.00 |
August | 248.11 | 21.95 | 114.56 | 13.75 | 100.81 | 0.00 | 0.00 |
September | 275.57 | 31.77 | 137.46 | 36.23 | 101.23 | 0.00 | 0.00 |
October | 394.10 | 57.27 | 213.27 | 111.09 | 102.17 | 0.00 | 0.00 |
November | 432.61 | 118.42 | 271.40 | 186.86 | 84.54 | 0.00 | 0.00 |
December | 431.88 | 151.40 | 280.62 | 201.52 | 79.09 | 0.00 | 0.00 |
Annual Sum or Average | 307.38 | 80.04 | 177.82 | 85.69 | 92.13 | 0.00 | 0.00 |
Minimum of Months | 199.82 | 14.27 | 93.02 | 0.87 | 79.09 | 0.00 | 0.00 |
Maximum of Months | 432.61 | 165.94 | 287.19 | 204.81 | 102.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 431.18 | 163.79 | 287.19 | 204.81 | 82.37 | 0.00 | 0.00 |
February | 397.79 | 141.72 | 260.46 | 168.59 | 91.87 | 0.00 | 0.00 |
March | 261.91 | 126.30 | 166.28 | 75.04 | 91.24 | 0.00 | 0.00 |
April | 212.07 | 85.04 | 123.25 | 28.88 | 94.37 | 0.00 | 0.00 |
May | 199.91 | 23.36 | 94.17 | 4.00 | 90.17 | 0.00 | 0.00 |
June | 202.42 | 21.07 | 93.02 | 0.87 | 92.16 | 0.00 | 0.00 |
July | 209.73 | 14.38 | 97.38 | 1.79 | 95.59 | 0.00 | 0.00 |
August | 247.83 | 22.18 | 114.56 | 13.75 | 100.81 | 0.00 | 0.00 |
September | 275.38 | 31.89 | 137.46 | 36.23 | 101.23 | 0.00 | 0.00 |
October | 394.09 | 57.12 | 213.27 | 111.09 | 102.17 | 0.00 | 0.00 |
November | 433.17 | 117.40 | 271.40 | 186.86 | 84.54 | 0.00 | 0.00 |
December | 432.77 | 149.44 | 280.62 | 201.52 | 79.09 | 0.00 | 0.00 |
Annual Sum or Average | 307.75 | 79.13 | 177.82 | 85.69 | 92.13 | 0.00 | 0.00 |
Minimum of Months | 199.91 | 14.38 | 93.02 | 0.87 | 79.09 | 0.00 | 0.00 |
Maximum of Months | 433.17 | 163.79 | 287.19 | 204.81 | 102.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 433.13 | 156.09 | 287.19 | 204.81 | 82.37 | 0.00 | 0.00 |
February | 400.12 | 133.59 | 260.46 | 168.59 | 91.87 | 0.00 | 0.00 |
March | 263.14 | 118.11 | 166.28 | 75.04 | 91.24 | 0.00 | 0.00 |
April | 212.54 | 79.92 | 123.25 | 28.88 | 94.37 | 0.00 | 0.00 |
May | 198.28 | 22.71 | 94.17 | 4.00 | 90.17 | 0.00 | 0.00 |
June | 200.03 | 21.10 | 93.02 | 0.87 | 92.16 | 0.00 | 0.00 |
July | 206.39 | 15.30 | 97.38 | 1.79 | 95.59 | 0.00 | 0.00 |
August | 244.36 | 23.90 | 114.56 | 13.75 | 100.81 | 0.00 | 0.00 |
September | 272.64 | 33.12 | 137.46 | 36.23 | 101.23 | 0.00 | 0.00 |
October | 392.27 | 56.98 | 213.27 | 111.09 | 102.17 | 0.00 | 0.00 |
November | 433.66 | 113.67 | 271.40 | 186.86 | 84.54 | 0.00 | 0.00 |
December | 434.41 | 142.56 | 280.62 | 201.52 | 79.09 | 0.00 | 0.00 |
Annual Sum or Average | 307.12 | 76.11 | 177.82 | 85.69 | 92.13 | 0.00 | 0.00 |
Minimum of Months | 198.28 | 15.30 | 93.02 | 0.87 | 79.09 | 0.00 | 0.00 |
Maximum of Months | 434.41 | 156.09 | 287.19 | 204.81 | 102.17 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.229944E+10 | 0.918542E+09 | 0.154157E+10 | 0.109940E+10 | 0.442162E+09 | 0.00 | 0.00 |
February | 0.191260E+10 | 0.724184E+09 | 0.126281E+10 | 0.817396E+09 | 0.445415E+09 | 0.00 | 0.00 |
March | 0.139392E+10 | 0.709761E+09 | 0.892585E+09 | 0.402825E+09 | 0.489760E+09 | 0.00 | 0.00 |
April | 0.109579E+10 | 0.454177E+09 | 0.640232E+09 | 0.150022E+09 | 0.490210E+09 | 0.00 | 0.00 |
May | 0.107601E+10 | 0.118766E+09 | 0.505490E+09 | 21482596.50 | 0.484007E+09 | 0.00 | 0.00 |
June | 0.105392E+10 | 0.100647E+09 | 0.483230E+09 | 4504165.10 | 0.478725E+09 | 0.00 | 0.00 |
July | 0.113987E+10 | 68200073.08 | 0.522725E+09 | 9607631.05 | 0.513117E+09 | 0.00 | 0.00 |
August | 0.133532E+10 | 0.112334E+09 | 0.614958E+09 | 73813531.21 | 0.541145E+09 | 0.00 | 0.00 |
September | 0.143691E+10 | 0.155466E+09 | 0.714045E+09 | 0.188181E+09 | 0.525864E+09 | 0.00 | 0.00 |
October | 0.211805E+10 | 0.296712E+09 | 0.114478E+10 | 0.596320E+09 | 0.548456E+09 | 0.00 | 0.00 |
November | 0.224450E+10 | 0.622840E+09 | 0.140981E+10 | 0.970667E+09 | 0.439140E+09 | 0.00 | 0.00 |
December | 0.231214E+10 | 0.833667E+09 | 0.150630E+10 | 0.108174E+10 | 0.424555E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.194185E+11 | 0.511530E+10 | 0.112385E+11 | 0.541597E+10 | 0.582256E+10 | 0.00 | 0.00 |
Minimum of Months | 0.105392E+10 | 68200073.08 | 0.483230E+09 | 4504165.10 | 0.424555E+09 | 0.00 | 0.00 |
Maximum of Months | 0.231214E+10 | 0.918542E+09 | 0.154157E+10 | 0.109940E+10 | 0.548456E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.113616E+10 | 0.487001E+09 | 0.770783E+09 | 0.549702E+09 | 0.221081E+09 | 0.00 | 0.00 |
February | 0.946171E+09 | 0.380905E+09 | 0.631406E+09 | 0.408698E+09 | 0.222707E+09 | 0.00 | 0.00 |
March | 0.688450E+09 | 0.374792E+09 | 0.446293E+09 | 0.201412E+09 | 0.244880E+09 | 0.00 | 0.00 |
April | 0.544774E+09 | 0.233407E+09 | 0.320116E+09 | 75011096.64 | 0.245105E+09 | 0.00 | 0.00 |
May | 0.538910E+09 | 61264928.14 | 0.252745E+09 | 10741298.25 | 0.242003E+09 | 0.00 | 0.00 |
June | 0.529333E+09 | 51434397.80 | 0.241615E+09 | 2252082.55 | 0.239363E+09 | 0.00 | 0.00 |
July | 0.573338E+09 | 34532928.09 | 0.261363E+09 | 4803815.53 | 0.256559E+09 | 0.00 | 0.00 |
August | 0.671830E+09 | 55428668.26 | 0.307479E+09 | 36906765.60 | 0.270572E+09 | 0.00 | 0.00 |
September | 0.720873E+09 | 77313107.48 | 0.357023E+09 | 94090626.76 | 0.262932E+09 | 0.00 | 0.00 |
October | 0.105959E+10 | 0.149189E+09 | 0.572388E+09 | 0.298160E+09 | 0.274228E+09 | 0.00 | 0.00 |
November | 0.111746E+10 | 0.317713E+09 | 0.704904E+09 | 0.485334E+09 | 0.219570E+09 | 0.00 | 0.00 |
December | 0.114753E+10 | 0.435116E+09 | 0.753148E+09 | 0.540871E+09 | 0.212277E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.967443E+10 | 0.265810E+10 | 0.561926E+10 | 0.270798E+10 | 0.291128E+10 | 0.00 | 0.00 |
Minimum of Months | 0.529333E+09 | 34532928.09 | 0.241615E+09 | 2252082.55 | 0.212277E+09 | 0.00 | 0.00 |
Maximum of Months | 0.114753E+10 | 0.487001E+09 | 0.770783E+09 | 0.549702E+09 | 0.274228E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.113774E+10 | 0.477093E+09 | 0.769201E+09 | 0.548574E+09 | 0.220627E+09 | 0.00 | 0.00 |
February | 0.946780E+09 | 0.375927E+09 | 0.630110E+09 | 0.407860E+09 | 0.222251E+09 | 0.00 | 0.00 |
March | 0.688294E+09 | 0.372887E+09 | 0.445377E+09 | 0.200999E+09 | 0.244378E+09 | 0.00 | 0.00 |
April | 0.542556E+09 | 0.241983E+09 | 0.319459E+09 | 74857213.05 | 0.244602E+09 | 0.00 | 0.00 |
May | 0.531645E+09 | 75952115.92 | 0.252226E+09 | 10719262.72 | 0.241507E+09 | 0.00 | 0.00 |
June | 0.521796E+09 | 66997694.46 | 0.241119E+09 | 2247462.45 | 0.238872E+09 | 0.00 | 0.00 |
July | 0.558724E+09 | 47771342.70 | 0.260826E+09 | 4793960.61 | 0.256032E+09 | 0.00 | 0.00 |
August | 0.661904E+09 | 70835025.87 | 0.306848E+09 | 36831052.20 | 0.270017E+09 | 0.00 | 0.00 |
September | 0.713741E+09 | 94548818.32 | 0.356290E+09 | 93897601.94 | 0.262393E+09 | 0.00 | 0.00 |
October | 0.105388E+10 | 0.166909E+09 | 0.571214E+09 | 0.297548E+09 | 0.273665E+09 | 0.00 | 0.00 |
November | 0.111575E+10 | 0.324686E+09 | 0.703458E+09 | 0.484338E+09 | 0.219120E+09 | 0.00 | 0.00 |
December | 0.114742E+10 | 0.432771E+09 | 0.751603E+09 | 0.539761E+09 | 0.211842E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.962024E+10 | 0.274836E+10 | 0.560773E+10 | 0.270243E+10 | 0.290531E+10 | 0.00 | 0.00 |
Minimum of Months | 0.521796E+09 | 47771342.70 | 0.241119E+09 | 2247462.45 | 0.211842E+09 | 0.00 | 0.00 |
Maximum of Months | 0.114742E+10 | 0.477093E+09 | 0.769201E+09 | 0.548574E+09 | 0.273665E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.114019E+10 | 0.470736E+09 | 0.769201E+09 | 0.548574E+09 | 0.220627E+09 | 0.00 | 0.00 |
February | 0.948631E+09 | 0.371245E+09 | 0.630110E+09 | 0.407860E+09 | 0.222251E+09 | 0.00 | 0.00 |
March | 0.689607E+09 | 0.368935E+09 | 0.445377E+09 | 0.200999E+09 | 0.244378E+09 | 0.00 | 0.00 |
April | 0.542841E+09 | 0.241008E+09 | 0.319459E+09 | 74857213.05 | 0.244602E+09 | 0.00 | 0.00 |
May | 0.531212E+09 | 77243375.00 | 0.252226E+09 | 10719262.72 | 0.241507E+09 | 0.00 | 0.00 |
June | 0.521235E+09 | 68590845.07 | 0.241119E+09 | 2247462.45 | 0.238872E+09 | 0.00 | 0.00 |
July | 0.557743E+09 | 49655443.52 | 0.260826E+09 | 4793960.61 | 0.256032E+09 | 0.00 | 0.00 |
August | 0.661270E+09 | 72713844.05 | 0.306848E+09 | 36831052.20 | 0.270017E+09 | 0.00 | 0.00 |
September | 0.713147E+09 | 96240103.69 | 0.356290E+09 | 93897601.94 | 0.262393E+09 | 0.00 | 0.00 |
October | 0.105354E+10 | 0.168326E+09 | 0.571214E+09 | 0.297548E+09 | 0.273665E+09 | 0.00 | 0.00 |
November | 0.111626E+10 | 0.323283E+09 | 0.703458E+09 | 0.484338E+09 | 0.219120E+09 | 0.00 | 0.00 |
December | 0.114881E+10 | 0.428593E+09 | 0.751603E+09 | 0.539761E+09 | 0.211842E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.962449E+10 | 0.273657E+10 | 0.560773E+10 | 0.270243E+10 | 0.290531E+10 | 0.00 | 0.00 |
Minimum of Months | 0.521235E+09 | 49655443.52 | 0.241119E+09 | 2247462.45 | 0.211842E+09 | 0.00 | 0.00 |
Maximum of Months | 0.114881E+10 | 0.470736E+09 | 0.769201E+09 | 0.548574E+09 | 0.273665E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.114334E+10 | 0.464189E+09 | 0.769201E+09 | 0.548574E+09 | 0.220627E+09 | 0.00 | 0.00 |
February | 0.951366E+09 | 0.365827E+09 | 0.630110E+09 | 0.407860E+09 | 0.222251E+09 | 0.00 | 0.00 |
March | 0.692007E+09 | 0.363361E+09 | 0.445377E+09 | 0.200999E+09 | 0.244378E+09 | 0.00 | 0.00 |
April | 0.544175E+09 | 0.237652E+09 | 0.319459E+09 | 74857213.05 | 0.244602E+09 | 0.00 | 0.00 |
May | 0.532337E+09 | 74939827.60 | 0.252226E+09 | 10719262.72 | 0.241507E+09 | 0.00 | 0.00 |
June | 0.522283E+09 | 66441383.33 | 0.241119E+09 | 2247462.45 | 0.238872E+09 | 0.00 | 0.00 |
July | 0.558850E+09 | 47829020.34 | 0.260826E+09 | 4793960.61 | 0.256032E+09 | 0.00 | 0.00 |
August | 0.662215E+09 | 70566840.30 | 0.306848E+09 | 36831052.20 | 0.270017E+09 | 0.00 | 0.00 |
September | 0.713900E+09 | 94187389.44 | 0.356290E+09 | 93897601.94 | 0.262393E+09 | 0.00 | 0.00 |
October | 0.105435E+10 | 0.165949E+09 | 0.571214E+09 | 0.297548E+09 | 0.273665E+09 | 0.00 | 0.00 |
November | 0.111773E+10 | 0.320022E+09 | 0.703458E+09 | 0.484338E+09 | 0.219120E+09 | 0.00 | 0.00 |
December | 0.115100E+10 | 0.423349E+09 | 0.751603E+09 | 0.539761E+09 | 0.211842E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.964356E+10 | 0.269431E+10 | 0.560773E+10 | 0.270243E+10 | 0.290531E+10 | 0.00 | 0.00 |
Minimum of Months | 0.522283E+09 | 47829020.34 | 0.241119E+09 | 2247462.45 | 0.211842E+09 | 0.00 | 0.00 |
Maximum of Months | 0.115100E+10 | 0.464189E+09 | 0.769201E+09 | 0.548574E+09 | 0.273665E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.230339E+10 | 0.898006E+09 | 0.153840E+10 | 0.109715E+10 | 0.441255E+09 | 0.00 | 0.00 |
February | 0.191773E+10 | 0.705468E+09 | 0.126022E+10 | 0.815720E+09 | 0.444501E+09 | 0.00 | 0.00 |
March | 0.139686E+10 | 0.697265E+09 | 0.890754E+09 | 0.401998E+09 | 0.488756E+09 | 0.00 | 0.00 |
April | 0.109482E+10 | 0.454555E+09 | 0.638919E+09 | 0.149714E+09 | 0.489204E+09 | 0.00 | 0.00 |
May | 0.106478E+10 | 0.133805E+09 | 0.504453E+09 | 21438525.43 | 0.483014E+09 | 0.00 | 0.00 |
June | 0.104322E+10 | 0.116781E+09 | 0.482238E+09 | 4494924.91 | 0.477743E+09 | 0.00 | 0.00 |
July | 0.111716E+10 | 83037219.85 | 0.521653E+09 | 9587921.21 | 0.512065E+09 | 0.00 | 0.00 |
August | 0.132328E+10 | 0.125153E+09 | 0.613697E+09 | 73662104.40 | 0.540035E+09 | 0.00 | 0.00 |
September | 0.142514E+10 | 0.172630E+09 | 0.712581E+09 | 0.187795E+09 | 0.524785E+09 | 0.00 | 0.00 |
October | 0.210956E+10 | 0.314832E+09 | 0.114243E+10 | 0.595097E+09 | 0.547331E+09 | 0.00 | 0.00 |
November | 0.224275E+10 | 0.620706E+09 | 0.140692E+10 | 0.968676E+09 | 0.438239E+09 | 0.00 | 0.00 |
December | 0.231355E+10 | 0.819672E+09 | 0.150321E+10 | 0.107952E+10 | 0.423684E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.193522E+11 | 0.514191E+10 | 0.112155E+11 | 0.540485E+10 | 0.581061E+10 | 0.00 | 0.00 |
Minimum of Months | 0.104322E+10 | 83037219.85 | 0.482238E+09 | 4494924.91 | 0.423684E+09 | 0.00 | 0.00 |
Maximum of Months | 0.231355E+10 | 0.898006E+09 | 0.153840E+10 | 0.109715E+10 | 0.547331E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.115044E+10 | 0.446981E+09 | 0.769201E+09 | 0.548574E+09 | 0.220627E+09 | 0.00 | 0.00 |
February | 0.958001E+09 | 0.350714E+09 | 0.630110E+09 | 0.407860E+09 | 0.222251E+09 | 0.00 | 0.00 |
March | 0.697903E+09 | 0.346552E+09 | 0.445377E+09 | 0.200999E+09 | 0.244378E+09 | 0.00 | 0.00 |
April | 0.547554E+09 | 0.225048E+09 | 0.319459E+09 | 74857213.05 | 0.244602E+09 | 0.00 | 0.00 |
May | 0.534580E+09 | 63948916.41 | 0.252226E+09 | 10719262.72 | 0.241507E+09 | 0.00 | 0.00 |
June | 0.524214E+09 | 55464807.35 | 0.241119E+09 | 2247462.45 | 0.238872E+09 | 0.00 | 0.00 |
July | 0.561785E+09 | 38718203.77 | 0.260826E+09 | 4793960.61 | 0.256032E+09 | 0.00 | 0.00 |
August | 0.664049E+09 | 59320526.44 | 0.306848E+09 | 36831052.20 | 0.270017E+09 | 0.00 | 0.00 |
September | 0.713859E+09 | 82957154.28 | 0.356290E+09 | 93897601.94 | 0.262393E+09 | 0.00 | 0.00 |
October | 0.105507E+10 | 0.154233E+09 | 0.571214E+09 | 0.297548E+09 | 0.273665E+09 | 0.00 | 0.00 |
November | 0.112054E+10 | 0.308265E+09 | 0.703458E+09 | 0.484338E+09 | 0.219120E+09 | 0.00 | 0.00 |
December | 0.115561E+10 | 0.407767E+09 | 0.751603E+09 | 0.539761E+09 | 0.211842E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.968361E+10 | 0.253997E+10 | 0.560773E+10 | 0.270243E+10 | 0.290531E+10 | 0.00 | 0.00 |
Minimum of Months | 0.524214E+09 | 38718203.77 | 0.241119E+09 | 2247462.45 | 0.211842E+09 | 0.00 | 0.00 |
Maximum of Months | 0.115561E+10 | 0.446981E+09 | 0.769201E+09 | 0.548574E+09 | 0.273665E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.115189E+10 | 0.444455E+09 | 0.769201E+09 | 0.548574E+09 | 0.220627E+09 | 0.00 | 0.00 |
February | 0.959380E+09 | 0.348413E+09 | 0.630110E+09 | 0.407860E+09 | 0.222251E+09 | 0.00 | 0.00 |
March | 0.699074E+09 | 0.344190E+09 | 0.445377E+09 | 0.200999E+09 | 0.244378E+09 | 0.00 | 0.00 |
April | 0.548280E+09 | 0.223712E+09 | 0.319459E+09 | 74857213.05 | 0.244602E+09 | 0.00 | 0.00 |
May | 0.535201E+09 | 63219906.84 | 0.252226E+09 | 10719262.72 | 0.241507E+09 | 0.00 | 0.00 |
June | 0.524787E+09 | 54832141.73 | 0.241119E+09 | 2247462.45 | 0.238872E+09 | 0.00 | 0.00 |
July | 0.562382E+09 | 38217700.35 | 0.260826E+09 | 4793960.61 | 0.256032E+09 | 0.00 | 0.00 |
August | 0.664529E+09 | 58778206.69 | 0.306848E+09 | 36831052.20 | 0.270017E+09 | 0.00 | 0.00 |
September | 0.714270E+09 | 82340871.67 | 0.356290E+09 | 93897601.94 | 0.262393E+09 | 0.00 | 0.00 |
October | 0.105556E+10 | 0.153402E+09 | 0.571214E+09 | 0.297548E+09 | 0.273665E+09 | 0.00 | 0.00 |
November | 0.112132E+10 | 0.306957E+09 | 0.703458E+09 | 0.484338E+09 | 0.219120E+09 | 0.00 | 0.00 |
December | 0.115674E+10 | 0.405497E+09 | 0.751603E+09 | 0.539761E+09 | 0.211842E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.969341E+10 | 0.252401E+10 | 0.560773E+10 | 0.270243E+10 | 0.290531E+10 | 0.00 | 0.00 |
Minimum of Months | 0.524787E+09 | 38217700.35 | 0.241119E+09 | 2247462.45 | 0.211842E+09 | 0.00 | 0.00 |
Maximum of Months | 0.115674E+10 | 0.444455E+09 | 0.769201E+09 | 0.548574E+09 | 0.273665E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.115488E+10 | 0.438700E+09 | 0.769201E+09 | 0.548574E+09 | 0.220627E+09 | 0.00 | 0.00 |
February | 0.962338E+09 | 0.342860E+09 | 0.630110E+09 | 0.407860E+09 | 0.222251E+09 | 0.00 | 0.00 |
March | 0.701492E+09 | 0.338291E+09 | 0.445377E+09 | 0.200999E+09 | 0.244378E+09 | 0.00 | 0.00 |
April | 0.549694E+09 | 0.220418E+09 | 0.319459E+09 | 74857213.05 | 0.244602E+09 | 0.00 | 0.00 |
May | 0.535443E+09 | 62576773.25 | 0.252226E+09 | 10719262.72 | 0.241507E+09 | 0.00 | 0.00 |
June | 0.524682E+09 | 54616842.78 | 0.241119E+09 | 2247462.45 | 0.238872E+09 | 0.00 | 0.00 |
July | 0.561743E+09 | 38502505.53 | 0.260826E+09 | 4793960.61 | 0.256032E+09 | 0.00 | 0.00 |
August | 0.663775E+09 | 59394003.36 | 0.306848E+09 | 36831052.20 | 0.270017E+09 | 0.00 | 0.00 |
September | 0.713784E+09 | 82668572.87 | 0.356290E+09 | 93897601.94 | 0.262393E+09 | 0.00 | 0.00 |
October | 0.105554E+10 | 0.152986E+09 | 0.571214E+09 | 0.297548E+09 | 0.273665E+09 | 0.00 | 0.00 |
November | 0.112278E+10 | 0.304297E+09 | 0.703458E+09 | 0.484338E+09 | 0.219120E+09 | 0.00 | 0.00 |
December | 0.115913E+10 | 0.400272E+09 | 0.751603E+09 | 0.539761E+09 | 0.211842E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.970528E+10 | 0.249558E+10 | 0.560773E+10 | 0.270243E+10 | 0.290531E+10 | 0.00 | 0.00 |
Minimum of Months | 0.524682E+09 | 38502505.53 | 0.241119E+09 | 2247462.45 | 0.211842E+09 | 0.00 | 0.00 |
Maximum of Months | 0.115913E+10 | 0.438700E+09 | 0.769201E+09 | 0.548574E+09 | 0.273665E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.116010E+10 | 0.418076E+09 | 0.769201E+09 | 0.548574E+09 | 0.220627E+09 | 0.00 | 0.00 |
February | 0.967964E+09 | 0.323174E+09 | 0.630110E+09 | 0.407860E+09 | 0.222251E+09 | 0.00 | 0.00 |
March | 0.704797E+09 | 0.316349E+09 | 0.445377E+09 | 0.200999E+09 | 0.244378E+09 | 0.00 | 0.00 |
April | 0.550901E+09 | 0.207149E+09 | 0.319459E+09 | 74857213.05 | 0.244602E+09 | 0.00 | 0.00 |
May | 0.531066E+09 | 60820846.09 | 0.252226E+09 | 10719262.72 | 0.241507E+09 | 0.00 | 0.00 |
June | 0.518470E+09 | 54700932.86 | 0.241119E+09 | 2247462.45 | 0.238872E+09 | 0.00 | 0.00 |
July | 0.552782E+09 | 40989506.55 | 0.260826E+09 | 4793960.61 | 0.256032E+09 | 0.00 | 0.00 |
August | 0.654491E+09 | 64016505.77 | 0.306848E+09 | 36831052.20 | 0.270017E+09 | 0.00 | 0.00 |
September | 0.706686E+09 | 85844284.84 | 0.356290E+09 | 93897601.94 | 0.262393E+09 | 0.00 | 0.00 |
October | 0.105067E+10 | 0.152611E+09 | 0.571214E+09 | 0.297548E+09 | 0.273665E+09 | 0.00 | 0.00 |
November | 0.112404E+10 | 0.294631E+09 | 0.703458E+09 | 0.484338E+09 | 0.219120E+09 | 0.00 | 0.00 |
December | 0.116351E+10 | 0.381837E+09 | 0.751603E+09 | 0.539761E+09 | 0.211842E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.968547E+10 | 0.240020E+10 | 0.560773E+10 | 0.270243E+10 | 0.290531E+10 | 0.00 | 0.00 |
Minimum of Months | 0.518470E+09 | 40989506.55 | 0.241119E+09 | 2247462.45 | 0.211842E+09 | 0.00 | 0.00 |
Maximum of Months | 0.116351E+10 | 0.418076E+09 | 0.769201E+09 | 0.548574E+09 | 0.273665E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.57 | 11.02 | 8.64 | 3.24 | 3.13 | 48.31 | 209.17 | 0.01 |
February | 15.49 | 12.82 | 10.40 | 2.82 | 4.36 | 58.07 | 218.23 | 0.02 |
March | 17.07 | 13.58 | 10.72 | 3.68 | 7.24 | 76.61 | 186.08 | 0.03 |
April | 21.23 | 17.54 | 15.23 | 2.65 | 11.47 | 90.28 | 216.86 | 0.02 |
May | 26.90 | 22.82 | 21.10 | 3.11 | 19.64 | 106.10 | 173.47 | 0.04 |
June | 27.61 | 23.37 | 21.62 | 2.44 | 19.77 | 115.40 | 187.69 | 0.03 |
July | 27.94 | 24.58 | 23.34 | 2.53 | 20.70 | 123.49 | 154.05 | 0.05 |
August | 27.43 | 23.90 | 22.52 | 3.20 | 20.40 | 118.51 | 145.78 | 0.03 |
September | 26.23 | 23.37 | 22.24 | 3.39 | 19.02 | 101.73 | 135.58 | 0.05 |
October | 24.23 | 20.47 | 18.40 | 4.11 | 16.60 | 78.24 | 178.15 | 0.01 |
November | 18.91 | 15.31 | 12.62 | 2.63 | 7.99 | 49.56 | 205.43 | 0.01 |
December | 15.68 | 12.88 | 10.53 | 3.17 | 6.01 | 45.08 | 191.18 | 0.02 |
Annual Sum or Average | 21.89 | 18.50 | 16.48 | 3.09 | 13.08 | 84.44 | 183.16 | 0.03 |
Minimum of Months | 13.57 | 11.02 | 8.64 | 2.44 | 3.13 | 45.08 | 135.58 | 0.01 |
Maximum of Months | 27.94 | 24.58 | 23.34 | 4.11 | 20.70 | 123.49 | 218.23 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 27.00 | 02-JAN-14:00 | 18.67 | 14.00 | 1.50 | 17.75 | 146.50 | 0.00 |
February | 28.30 | 02-FEB-12:00 | 20.78 | 17.20 | 6.60 | 17.93 | 127.50 | 748.50 |
March | 30.00 | 26-MAR-13:00 | 19.88 | 14.40 | 3.00 | 19.52 | 288.50 | 548.00 |
April | 33.30 | 28-APR-14:00 | 23.06 | 18.80 | 4.10 | 23.15 | 150.50 | 762.50 |
May | 33.90 | 07-MAY-13:00 | 23.76 | 19.40 | 4.10 | 23.15 | 287.50 | 507.50 |
June | 35.00 | 14-JUN-13:00 | 23.95 | 19.40 | 2.10 | 24.16 | 194.50 | 712.50 |
July | 36.10 | 21-JUL-15:00 | 25.96 | 22.20 | 1.50 | 26.65 | 216.00 | 245.00 |
August | 36.30 | 30-AUG-15:00 | 23.74 | 18.50 | 2.40 | 25.33 | 116.00 | 698.50 |
September | 36.40 | 09-SEP-16:00 | 26.65 | 23.40 | 4.40 | 26.48 | 114.00 | 401.50 |
October | 34.00 | 05-OCT-14:00 | 24.05 | 20.00 | 2.60 | 29.55 | 169.50 | 606.00 |
November | 30.00 | 01-NOV-13:00 | 25.01 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 30.00 | 13-DEC-14:00 | 21.84 | 18.00 | 3.10 | 20.92 | 101.50 | 682.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 27.00 | 18.67 | 14.00 | 1.50 | 17.75 | 101.50 | 0.00 | |
Maximum of Months | 36.40 | 26.65 | 23.40 | 6.60 | 29.55 | 288.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.00 | 05-JAN-05:00 | -0.0 | -0.0 | 2.10 | -16.0 | 0.00 | 0.00 |
February | -3.4 | 05-FEB-07:10 | -5.4 | -9.4 | 4.68 | -21.3 | 0.00 | 0.00 |
March | 1.10 | 09-MAR-05:00 | -2.1 | -7.3 | 3.60 | -14.4 | 0.00 | 0.00 |
April | 8.30 | 11-APR-05:00 | 6.95 | 5.50 | 0.00 | -6.9 | 0.00 | 0.00 |
May | 21.10 | 07-MAY-00:00 | 19.58 | 18.90 | 0.00 | 11.46 | 0.00 | 0.00 |
June | 20.60 | 07-JUN-01:00 | 18.00 | 16.70 | 3.60 | 10.50 | 0.00 | 0.00 |
July | 22.20 | 11-JUL-19:00 | 21.37 | 21.10 | 2.10 | 20.22 | 0.00 | 0.00 |
August | 20.20 | 25-AUG-23:00 | 20.20 | 20.20 | 5.30 | 11.84 | 0.00 | 0.00 |
September | 19.20 | 07-SEP-17:00 | 19.20 | 19.20 | 2.50 | 16.85 | 35.00 | 7.00 |
October | 10.00 | 28-OCT-04:00 | 5.56 | 0.00 | 3.60 | -0.1 | 0.00 | 0.00 |
November | 7.20 | 12-NOV-07:49 | 4.12 | 0.18 | 4.60 | -9.0 | 36.00 | 517.00 |
December | 0.00 | 21-DEC-04:00 | -0.9 | -2.0 | 2.10 | -16.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.4 | -5.4 | -9.4 | 0.00 | -21.3 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 21.37 | 21.10 | 5.30 | 20.22 | 36.00 | 517.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 22.11 | 31-JAN-12:00 | 25.00 | 21.00 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 21.49 | 24-FEB-12:00 | 27.70 | 18.80 | 4.10 | 17.75 | 165.00 | 746.50 |
March | 22.77 | 30-MAR-12:00 | 29.40 | 20.00 | 2.50 | 27.14 | 340.00 | 0.00 |
April | 25.55 | 28-APR-15:00 | 32.20 | 23.30 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 25.84 | 27-MAY-13:00 | 31.70 | 23.90 | 3.10 | 22.13 | 168.50 | 735.50 |
June | 26.52 | 29-JUN-16:00 | 29.40 | 25.60 | 1.50 | 26.32 | 164.00 | 36.00 |
July | 27.17 | 22-JUL-10:00 | 32.20 | 25.60 | 2.10 | 21.96 | 191.00 | 719.50 |
August | 27.24 | 07-AUG-12:00 | 31.00 | 26.00 | 3.10 | 27.95 | 473.00 | 200.00 |
September | 27.79 | 10-SEP-12:00 | 35.00 | 25.50 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.18 | 07-OCT-07:00 | 29.00 | 28.00 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 25.01 | 01-NOV-13:00 | 30.00 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 24.12 | 12-DEC-13:00 | 27.00 | 23.00 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.49 | 25.00 | 18.80 | 1.50 | 17.75 | 95.00 | 0.00 | |
Maximum of Months | 28.18 | 35.00 | 28.00 | 5.70 | 27.95 | 473.00 | 746.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 31-JAN-12:00 | 25.00 | 22.11 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 20.20 | 02-FEB-22:00 | 21.50 | 20.56 | 4.80 | 14.65 | 0.00 | 0.00 |
March | 21.10 | 07-MAR-08:00 | 23.30 | 21.69 | 2.00 | 13.91 | 126.00 | 566.50 |
April | 23.30 | 28-APR-15:00 | 32.20 | 25.55 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 24.40 | 26-MAY-08:20 | 27.07 | 25.09 | 3.10 | 23.71 | 252.67 | 47.33 |
June | 25.60 | 29-JUN-14:00 | 27.20 | 26.00 | 5.10 | 24.16 | 335.00 | 238.00 |
July | 25.60 | 02-JUL-05:00 | 26.10 | 25.71 | 2.60 | 19.52 | 30.50 | 8.50 |
August | 26.60 | 09-AUG-18:00 | 26.60 | 26.60 | 1.90 | 19.52 | 26.00 | 23.00 |
September | 25.50 | 10-SEP-12:00 | 35.00 | 27.79 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.00 | 07-OCT-07:00 | 29.00 | 28.18 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 23.80 | 01-NOV-10:00 | 26.10 | 24.39 | 2.00 | 22.64 | 228.50 | 113.00 |
December | 23.00 | 12-DEC-13:00 | 27.00 | 24.12 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.20 | 21.50 | 20.56 | 1.90 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 28.00 | 35.00 | 28.18 | 5.70 | 24.66 | 336.50 | 662.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.46 | 29.60 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 20.78 | 36.65 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 22.23 | 38.94 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.49 | 49.11 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 26.95 | 46.95 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 28.93 | 51.71 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 29.89 | 48.43 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 29.58 | 45.50 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.08 | 39.22 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.80 | 37.51 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 23.35 | 31.26 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 21.40 | 27.18 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 25.18 | 40.17 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.46 | 27.18 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 29.89 | 51.71 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.260804E+09 | -189182204.7 | 0.00 | 0.00 | 744.00 | 0.00 | -71622088.5 | 59.00 | 0.00 | 0.00 |
February | 0.234194E+09 | -170339543.8 | 0.00 | 0.00 | 672.00 | 0.00 | -63854343.0 | 59.01 | 0.00 | 0.00 |
March | 0.254739E+09 | -184429116.7 | 0.00 | 0.00 | 744.00 | 0.00 | -70310105.5 | 58.99 | 0.00 | 0.00 |
April | 0.231808E+09 | -165334979.0 | 0.00 | 0.00 | 720.00 | 0.00 | -66473170.0 | 58.99 | 0.00 | 0.00 |
May | 0.226876E+09 | -159017712.0 | 0.00 | 0.00 | 744.00 | 0.00 | -67858703.2 | 58.98 | 0.00 | 0.00 |
June | 0.211388E+09 | -145799074.0 | 0.00 | 0.00 | 720.00 | 0.00 | -65588645.1 | 58.99 | 0.00 | 0.00 |
July | 0.210438E+09 | -142841415.0 | 0.00 | 0.00 | 744.00 | 0.00 | -67596880.7 | 58.98 | 0.00 | 0.00 |
August | 0.214997E+09 | -147434673.2 | 0.00 | 0.00 | 744.00 | 0.00 | -67562071.6 | 58.99 | 0.00 | 0.00 |
September | 0.213792E+09 | -148328153.7 | 0.00 | 0.00 | 720.00 | 0.00 | -65463650.2 | 58.98 | 0.00 | 0.00 |
October | 0.230925E+09 | -163031390.1 | 0.00 | 0.00 | 744.00 | 0.00 | -67894032.6 | 58.98 | 0.00 | 0.00 |
November | 0.235439E+09 | -168882000.5 | 0.00 | 0.00 | 720.00 | 0.00 | -66557031.8 | 58.99 | 0.00 | 0.00 |
December | 0.255137E+09 | -184815091.1 | 0.00 | 0.00 | 744.00 | 0.00 | -70322395.4 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.278054E+10 | -0.196944E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -811103117.5 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.210438E+09 | -189182204.7 | 0.00 | 0.00 | 672.00 | 0.00 | -71622088.5 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.260804E+09 | -142841415.0 | 0.00 | 0.00 | 744.00 | 0.00 | -63854343.0 | 59.01 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.259538E+09 | -189171548.1 | 0.00 | 0.00 | 744.00 | 0.00 | -70366068.2 | 59.00 | 0.00 | 0.00 |
February | 0.233366E+09 | -170387362.7 | 0.00 | 0.00 | 672.00 | 0.00 | -62978915.8 | 58.98 | 0.00 | 0.00 |
March | 0.253939E+09 | -184436052.9 | 0.00 | 0.00 | 744.00 | 0.00 | -69502459.4 | 58.99 | 0.00 | 0.00 |
April | 0.231556E+09 | -165326368.6 | 0.00 | 0.00 | 720.00 | 0.00 | -66229380.0 | 58.99 | 0.00 | 0.00 |
May | 0.226756E+09 | -158980883.2 | 0.00 | 0.00 | 744.00 | 0.00 | -67775034.4 | 59.00 | 0.00 | 0.00 |
June | 0.211298E+09 | -145798596.8 | 0.00 | 0.00 | 720.00 | 0.00 | -65498955.4 | 58.99 | 0.00 | 0.00 |
July | 0.210387E+09 | -142830477.6 | 0.00 | 0.00 | 744.00 | 0.00 | -67556368.0 | 58.99 | 0.00 | 0.00 |
August | 0.214962E+09 | -147434794.0 | 0.00 | 0.00 | 744.00 | 0.00 | -67527562.8 | 58.99 | 0.00 | 0.00 |
September | 0.213754E+09 | -148327917.6 | 0.00 | 0.00 | 720.00 | 0.00 | -65426397.0 | 58.99 | 0.00 | 0.00 |
October | 0.230836E+09 | -163022749.2 | 0.00 | 0.00 | 744.00 | 0.00 | -67813054.6 | 58.98 | 0.00 | 0.00 |
November | 0.235140E+09 | -168881283.2 | 0.00 | 0.00 | 720.00 | 0.00 | -66258797.0 | 58.99 | 0.00 | 0.00 |
December | 0.254356E+09 | -184807373.5 | 0.00 | 0.00 | 744.00 | 0.00 | -69548529.6 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.277589E+10 | -0.196941E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -806481522.1 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.210387E+09 | -189171548.1 | 0.00 | 0.00 | 672.00 | 0.00 | -70366068.2 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.259538E+09 | -142830477.6 | 0.00 | 0.00 | 744.00 | 0.00 | -62978915.8 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.237204E+09 | -166365229.0 | 0.00 | 0.00 | 744.00 | 0.00 | -70839111.9 | 58.99 | 0.00 | 0.00 |
February | 0.213171E+09 | -149955629.0 | 0.00 | 0.00 | 672.00 | 0.00 | -63215103.0 | 58.99 | 0.00 | 0.00 |
March | 0.234157E+09 | -164606618.3 | 0.00 | 0.00 | 744.00 | 0.00 | -69550625.5 | 58.99 | 0.00 | 0.00 |
April | 0.211100E+09 | -145391303.2 | 0.00 | 0.00 | 720.00 | 0.00 | -65708563.6 | 59.00 | 0.00 | 0.00 |
May | 0.207716E+09 | -141047953.9 | 0.00 | 0.00 | 744.00 | 0.00 | -66668417.7 | 58.98 | 0.00 | 0.00 |
June | 0.194225E+09 | -129838928.1 | 0.00 | 0.00 | 720.00 | 0.00 | -64386014.6 | 59.00 | 0.00 | 0.00 |
July | 0.191098E+09 | -124860994.6 | 0.00 | 0.00 | 744.00 | 0.00 | -66237324.9 | 58.99 | 0.00 | 0.00 |
August | 0.198021E+09 | -131695608.5 | 0.00 | 0.00 | 744.00 | 0.00 | -66324957.8 | 58.99 | 0.00 | 0.00 |
September | 0.194662E+09 | -130374993.5 | 0.00 | 0.00 | 720.00 | 0.00 | -64287078.8 | 58.99 | 0.00 | 0.00 |
October | 0.210125E+09 | -143401607.7 | 0.00 | 0.00 | 744.00 | 0.00 | -66723653.1 | 58.98 | 0.00 | 0.00 |
November | 0.214985E+09 | -149111799.6 | 0.00 | 0.00 | 720.00 | 0.00 | -65873161.3 | 58.99 | 0.00 | 0.00 |
December | 0.230962E+09 | -161331176.8 | 0.00 | 0.00 | 744.00 | 0.00 | -69631251.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.253743E+10 | -0.173798E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -799445263.3 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.191098E+09 | -166365229.0 | 0.00 | 0.00 | 672.00 | 0.00 | -70839111.9 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.237204E+09 | -124860994.6 | 0.00 | 0.00 | 744.00 | 0.00 | -63215103.0 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.237439E+09 | -166362343.8 | 0.00 | 0.00 | 744.00 | 0.00 | -71076409.2 | 59.00 | 0.00 | 0.00 |
February | 0.213339E+09 | -149952662.8 | 0.00 | 0.00 | 672.00 | 0.00 | -63386681.5 | 58.99 | 0.00 | 0.00 |
March | 0.234277E+09 | -164583553.7 | 0.00 | 0.00 | 744.00 | 0.00 | -69693032.1 | 58.99 | 0.00 | 0.00 |
April | 0.211145E+09 | -145411064.2 | 0.00 | 0.00 | 720.00 | 0.00 | -65733828.4 | 59.00 | 0.00 | 0.00 |
May | 0.207671E+09 | -141030932.2 | 0.00 | 0.00 | 744.00 | 0.00 | -66639720.3 | 58.99 | 0.00 | 0.00 |
June | 0.194159E+09 | -129851804.4 | 0.00 | 0.00 | 720.00 | 0.00 | -64306985.1 | 58.99 | 0.00 | 0.00 |
July | 0.191026E+09 | -124887288.6 | 0.00 | 0.00 | 744.00 | 0.00 | -66138774.1 | 58.98 | 0.00 | 0.00 |
August | 0.197947E+09 | -131697536.4 | 0.00 | 0.00 | 744.00 | 0.00 | -66249843.4 | 58.99 | 0.00 | 0.00 |
September | 0.194607E+09 | -130366909.8 | 0.00 | 0.00 | 720.00 | 0.00 | -64240142.2 | 58.99 | 0.00 | 0.00 |
October | 0.210074E+09 | -143386793.8 | 0.00 | 0.00 | 744.00 | 0.00 | -66686749.3 | 58.98 | 0.00 | 0.00 |
November | 0.215033E+09 | -149101209.0 | 0.00 | 0.00 | 720.00 | 0.00 | -65931864.8 | 59.00 | 0.00 | 0.00 |
December | 0.231102E+09 | -161325539.9 | 0.00 | 0.00 | 744.00 | 0.00 | -69776895.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.253782E+10 | -0.173796E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -799860925.2 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.191026E+09 | -166362343.8 | 0.00 | 0.00 | 672.00 | 0.00 | -71076409.2 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.237439E+09 | -124887288.6 | 0.00 | 0.00 | 744.00 | 0.00 | -63386681.5 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.229137E+09 | -157235577.3 | 0.00 | 0.00 | 744.00 | 0.00 | -71901478.9 | 59.00 | 0.00 | 0.00 |
February | 0.205908E+09 | -141800508.2 | 0.00 | 0.00 | 672.00 | 0.00 | -64107373.4 | 58.99 | 0.00 | 0.00 |
March | 0.226160E+09 | -155746806.3 | 0.00 | 0.00 | 744.00 | 0.00 | -70413519.6 | 58.99 | 0.00 | 0.00 |
April | 0.203822E+09 | -137589599.7 | 0.00 | 0.00 | 720.00 | 0.00 | -66231965.0 | 59.00 | 0.00 | 0.00 |
May | 0.200412E+09 | -133388314.0 | 0.00 | 0.00 | 744.00 | 0.00 | -67023313.9 | 58.98 | 0.00 | 0.00 |
June | 0.187585E+09 | -122866683.2 | 0.00 | 0.00 | 720.00 | 0.00 | -64718299.5 | 58.99 | 0.00 | 0.00 |
July | 0.184601E+09 | -118094116.9 | 0.00 | 0.00 | 744.00 | 0.00 | -66506815.2 | 59.00 | 0.00 | 0.00 |
August | 0.191258E+09 | -124609373.4 | 0.00 | 0.00 | 744.00 | 0.00 | -66648860.4 | 58.99 | 0.00 | 0.00 |
September | 0.187903E+09 | -123381356.1 | 0.00 | 0.00 | 720.00 | 0.00 | -64521758.0 | 58.99 | 0.00 | 0.00 |
October | 0.202593E+09 | -135518396.2 | 0.00 | 0.00 | 744.00 | 0.00 | -67074339.0 | 58.99 | 0.00 | 0.00 |
November | 0.207198E+09 | -140821959.9 | 0.00 | 0.00 | 720.00 | 0.00 | -66376313.0 | 58.99 | 0.00 | 0.00 |
December | 0.223017E+09 | -152570675.4 | 0.00 | 0.00 | 744.00 | 0.00 | -70446256.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.244959E+10 | -0.164362E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -805970292.5 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.184601E+09 | -157235577.3 | 0.00 | 0.00 | 672.00 | 0.00 | -71901478.9 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.229137E+09 | -118094116.9 | 0.00 | 0.00 | 744.00 | 0.00 | -64107373.4 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.229243E+09 | -157243539.3 | 0.00 | 0.00 | 744.00 | 0.00 | -71999549.8 | 58.99 | 0.00 | 0.00 |
February | 0.205997E+09 | -141800597.7 | 0.00 | 0.00 | 672.00 | 0.00 | -64196802.4 | 58.99 | 0.00 | 0.00 |
March | 0.226252E+09 | -155739939.5 | 0.00 | 0.00 | 744.00 | 0.00 | -70512128.2 | 59.00 | 0.00 | 0.00 |
April | 0.203877E+09 | -137596819.6 | 0.00 | 0.00 | 720.00 | 0.00 | -66280025.9 | 58.99 | 0.00 | 0.00 |
May | 0.200508E+09 | -133376141.6 | 0.00 | 0.00 | 744.00 | 0.00 | -67131631.3 | 58.99 | 0.00 | 0.00 |
June | 0.187680E+09 | -122870931.4 | 0.00 | 0.00 | 720.00 | 0.00 | -64809519.7 | 58.99 | 0.00 | 0.00 |
July | 0.184690E+09 | -118104137.0 | 0.00 | 0.00 | 744.00 | 0.00 | -66585882.7 | 58.98 | 0.00 | 0.00 |
August | 0.191361E+09 | -124600495.1 | 0.00 | 0.00 | 744.00 | 0.00 | -66760867.3 | 58.99 | 0.00 | 0.00 |
September | 0.188004E+09 | -123374589.1 | 0.00 | 0.00 | 720.00 | 0.00 | -64629411.0 | 58.99 | 0.00 | 0.00 |
October | 0.202680E+09 | -135518384.5 | 0.00 | 0.00 | 744.00 | 0.00 | -67161476.3 | 58.99 | 0.00 | 0.00 |
November | 0.207267E+09 | -140841722.4 | 0.00 | 0.00 | 720.00 | 0.00 | -66425716.9 | 58.98 | 0.00 | 0.00 |
December | 0.223106E+09 | -152558187.9 | 0.00 | 0.00 | 744.00 | 0.00 | -70547472.9 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.245067E+10 | -0.164363E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -807040484.3 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.184690E+09 | -157243539.3 | 0.00 | 0.00 | 672.00 | 0.00 | -71999549.8 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.229243E+09 | -118104137.0 | 0.00 | 0.00 | 744.00 | 0.00 | -64196802.4 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.229338E+09 | -157247081.1 | 0.00 | 0.00 | 744.00 | 0.00 | -72090558.9 | 58.99 | 0.00 | 0.00 |
February | 0.206090E+09 | -141800581.3 | 0.00 | 0.00 | 672.00 | 0.00 | -64289884.2 | 58.99 | 0.00 | 0.00 |
March | 0.226336E+09 | -155743162.2 | 0.00 | 0.00 | 744.00 | 0.00 | -70592475.6 | 58.99 | 0.00 | 0.00 |
April | 0.203927E+09 | -137606702.0 | 0.00 | 0.00 | 720.00 | 0.00 | -66320432.4 | 58.99 | 0.00 | 0.00 |
May | 0.200532E+09 | -133378877.8 | 0.00 | 0.00 | 744.00 | 0.00 | -67153071.3 | 58.99 | 0.00 | 0.00 |
June | 0.187704E+09 | -122872859.1 | 0.00 | 0.00 | 720.00 | 0.00 | -64831537.9 | 58.99 | 0.00 | 0.00 |
July | 0.184720E+09 | -118093878.9 | 0.00 | 0.00 | 744.00 | 0.00 | -66625751.5 | 58.99 | 0.00 | 0.00 |
August | 0.191382E+09 | -124615668.2 | 0.00 | 0.00 | 744.00 | 0.00 | -66766393.5 | 58.99 | 0.00 | 0.00 |
September | 0.188014E+09 | -123382195.6 | 0.00 | 0.00 | 720.00 | 0.00 | -64631865.0 | 58.98 | 0.00 | 0.00 |
October | 0.202711E+09 | -135510301.7 | 0.00 | 0.00 | 744.00 | 0.00 | -67200856.6 | 58.99 | 0.00 | 0.00 |
November | 0.207322E+09 | -140824078.3 | 0.00 | 0.00 | 720.00 | 0.00 | -66497769.8 | 59.00 | 0.00 | 0.00 |
December | 0.223185E+09 | -152584927.1 | 0.00 | 0.00 | 744.00 | 0.00 | -70599722.3 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.245126E+10 | -0.164366E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -807600319.1 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.184720E+09 | -157247081.1 | 0.00 | 0.00 | 672.00 | 0.00 | -72090558.9 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.229338E+09 | -118093878.9 | 0.00 | 0.00 | 744.00 | 0.00 | -64289884.2 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 307.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 295.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 296.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 347.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 353.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 394.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 390.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 380.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 342.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 330.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 308.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 282.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4027.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 282.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 394.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.665037E+09 | 57621.40 | 10-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.792458E+09 | 57621.40 | 05-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.525156E+09 | 57621.40 | 11-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.605356E+09 | 57621.40 | 21-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.258801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.792458E+09 | 57621.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 64446953.98 | 4030.14 | 05-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.156652E+09 | 18280.66 | 05-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.128765E+09 | 6154.83 | 12-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.131572E+09 | 16689.62 | 21-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.481437E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.156652E+09 | 18280.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.208443E+09 | 5463.82 | 04-JAN-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.256033E+09 | 27063.80 | 05-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.185211E+09 | 13642.93 | 12-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.213153E+09 | 7172.73 | 21-DEC-08:65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.862840E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.256033E+09 | 27063.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.249084E+09 | 7523.13 | 05-JAN-08:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.280495E+09 | 30237.73 | 05-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.201962E+09 | 16581.56 | 12-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.233862E+09 | 8025.45 | 21-DEC-08:65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.965403E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.280495E+09 | 30237.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.310915E+09 | 8085.22 | 10-JAN-08:65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.319377E+09 | 30079.07 | 05-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.230478E+09 | 19346.93 | 12-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271783E+09 | 9145.57 | 21-DEC-08:65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.113255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.319377E+09 | 30079.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.686863E+09 | 54177.89 | 10-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.636426E+09 | 54177.89 | 05-FEB-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.439297E+09 | 54177.89 | 12-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.591810E+09 | 54177.89 | 21-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.235440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.686863E+09 | 54177.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.379630E+09 | 28212.90 | 10-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.351744E+09 | 28212.90 | 05-FEB-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.243408E+09 | 28212.90 | 11-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.328338E+09 | 28212.90 | 21-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.130312E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.379630E+09 | 28212.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.409400E+09 | 28111.62 | 10-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.369993E+09 | 28111.62 | 05-FEB-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.257139E+09 | 28111.62 | 11-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.347020E+09 | 28111.62 | 21-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.138355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.409400E+09 | 28111.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.485599E+09 | 28224.20 | 05-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.418617E+09 | 28224.20 | 05-FEB-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.302328E+09 | 28224.20 | 11-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.396103E+09 | 28224.20 | 20-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.485599E+09 | 28224.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.678766E+09 | 31910.12 | 05-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.557837E+09 | 31910.12 | 05-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.446352E+09 | 31910.12 | 10-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 784659.35 | 347.41 | 15-NOV-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.557290E+09 | 31910.12 | 20-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.224103E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.678766E+09 | 31910.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.445858E+10 | 0.279324E+10 | 58713.27 | 19-JAN-09:02 | 32139.41 | 0.00 |
February | 0.00 | 0.00 | 0.581438E+10 | 0.363365E+10 | 57433.10 | 28-FEB-09:02 | 28738.85 | 0.00 |
March | 0.00 | 0.00 | 0.848433E+10 | 0.547401E+10 | 59072.45 | 07-MAR-09:02 | 32350.85 | 0.00 |
April | 0.00 | 0.00 | 0.161535E+11 | 0.105463E+11 | 59757.25 | 29-APR-08:62 | 31665.69 | 0.00 |
May | 0.00 | 0.00 | 0.364957E+11 | 0.221322E+11 | 60831.89 | 24-MAY-08:61 | 29774.33 | 0.00 |
June | 0.00 | 0.00 | 0.390742E+11 | 0.234960E+11 | 60704.32 | 19-JUN-08:61 | 30868.11 | 0.00 |
July | 0.00 | 0.00 | 0.444826E+11 | 0.248085E+11 | 60942.91 | 03-JUL-08:61 | 30549.29 | 0.00 |
August | 0.00 | 0.00 | 0.438970E+11 | 0.253642E+11 | 61068.65 | 07-AUG-08:61 | 30814.20 | 0.00 |
September | 0.00 | 0.00 | 0.388431E+11 | 0.217768E+11 | 61379.09 | 05-SEP-08:61 | 28009.58 | 0.00 |
October | 0.00 | 0.00 | 0.330470E+11 | 0.199499E+11 | 61502.37 | 06-OCT-08:61 | 29270.87 | 0.00 |
November | 0.00 | 0.00 | 0.128170E+11 | 0.801880E+10 | 59577.53 | 02-NOV-08:61 | 32701.88 | 0.00 |
December | 0.00 | 0.00 | 0.821480E+10 | 0.510624E+10 | 59352.87 | 15-DEC-09:02 | 31780.68 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.291782E+12 | 0.173100E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.445858E+10 | 0.279324E+10 | 57433.10 | 28009.58 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.444826E+11 | 0.253642E+11 | 61502.37 | 32701.88 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.275141E+10 | 0.177600E+10 | 30673.53 | 19-JAN-09:02 | 17746.38 | 0.00 |
February | 0.00 | 0.00 | 0.359292E+10 | 0.229973E+10 | 29808.87 | 28-FEB-21:20 | 14246.38 | 0.00 |
March | 0.00 | 0.00 | 0.514955E+10 | 0.343493E+10 | 30150.71 | 07-MAR-09:02 | 19843.64 | 0.00 |
April | 0.00 | 0.00 | 0.913440E+10 | 0.616655E+10 | 30244.18 | 29-APR-08:62 | 20038.60 | 0.00 |
May | 0.00 | 0.00 | 0.184404E+11 | 0.115963E+11 | 30906.03 | 24-MAY-08:61 | 18686.20 | 0.00 |
June | 0.00 | 0.00 | 0.195105E+11 | 0.121326E+11 | 30645.36 | 19-JUN-08:61 | 19595.92 | 0.00 |
July | 0.00 | 0.00 | 0.219685E+11 | 0.127189E+11 | 31039.81 | 03-JUL-08:61 | 18731.92 | 0.00 |
August | 0.00 | 0.00 | 0.216319E+11 | 0.129013E+11 | 31142.09 | 16-AUG-08:61 | 18117.37 | 0.00 |
September | 0.00 | 0.00 | 0.192916E+11 | 0.112133E+11 | 31390.19 | 05-SEP-08:61 | 17350.09 | 0.00 |
October | 0.00 | 0.00 | 0.167613E+11 | 0.104937E+11 | 31139.54 | 06-OCT-08:61 | 18539.20 | 0.00 |
November | 0.00 | 0.00 | 0.711883E+10 | 0.460437E+10 | 30359.25 | 02-NOV-08:61 | 19989.87 | 0.00 |
December | 0.00 | 0.00 | 0.454458E+10 | 0.293355E+10 | 30200.54 | 13-DEC-09:02 | 19534.19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.149896E+12 | 0.922712E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.275141E+10 | 0.177600E+10 | 29808.87 | 14246.38 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.219685E+11 | 0.129013E+11 | 31390.19 | 20038.60 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.203272E+10 | 0.129959E+10 | 29665.52 | 20-JAN-08:62 | 13806.79 | 0.00 |
February | 0.00 | 0.00 | 0.281209E+10 | 0.177811E+10 | 30039.89 | 28-FEB-08:62 | 15445.85 | 0.00 |
March | 0.00 | 0.00 | 0.391835E+10 | 0.256419E+10 | 30800.61 | 07-MAR-08:62 | 14950.96 | 0.00 |
April | 0.00 | 0.00 | 0.698510E+10 | 0.465364E+10 | 31513.69 | 29-APR-07:02 | 16867.13 | 0.00 |
May | 0.00 | 0.00 | 0.151643E+11 | 0.927554E+10 | 32280.48 | 24-MAY-07:01 | 15257.03 | 0.00 |
June | 0.00 | 0.00 | 0.162736E+11 | 0.982039E+10 | 32580.35 | 19-JUN-07:01 | 14100.89 | 0.00 |
July | 0.00 | 0.00 | 0.180309E+11 | 0.100597E+11 | 32666.10 | 03-JUL-07:01 | 14508.21 | 0.00 |
August | 0.00 | 0.00 | 0.181371E+11 | 0.104521E+11 | 32631.38 | 14-AUG-07:03 | 13804.81 | 0.00 |
September | 0.00 | 0.00 | 0.157349E+11 | 0.877710E+10 | 32676.76 | 05-SEP-07:01 | 14081.81 | 0.00 |
October | 0.00 | 0.00 | 0.134711E+11 | 0.816152E+10 | 32612.02 | 25-OCT-07:01 | 14541.38 | 0.00 |
November | 0.00 | 0.00 | 0.565002E+10 | 0.359652E+10 | 31488.60 | 02-NOV-07:02 | 16962.48 | 0.00 |
December | 0.00 | 0.00 | 0.360899E+10 | 0.227300E+10 | 31297.65 | 15-DEC-08:62 | 17053.41 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.121819E+12 | 0.727114E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.203272E+10 | 0.129959E+10 | 29665.52 | 13804.81 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.181371E+11 | 0.104521E+11 | 32676.76 | 17053.41 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.197263E+10 | 0.125763E+10 | 29762.11 | 20-JAN-08:62 | 13841.82 | 0.00 |
February | 0.00 | 0.00 | 0.274584E+10 | 0.173254E+10 | 30137.15 | 28-FEB-08:62 | 15485.63 | 0.00 |
March | 0.00 | 0.00 | 0.385791E+10 | 0.251847E+10 | 30899.86 | 07-MAR-08:62 | 14983.86 | 0.00 |
April | 0.00 | 0.00 | 0.695323E+10 | 0.462898E+10 | 31618.15 | 29-APR-07:02 | 16929.64 | 0.00 |
May | 0.00 | 0.00 | 0.152134E+11 | 0.931106E+10 | 32387.41 | 24-MAY-07:01 | 15321.76 | 0.00 |
June | 0.00 | 0.00 | 0.163380E+11 | 0.986739E+10 | 32686.08 | 19-JUN-07:01 | 14209.00 | 0.00 |
July | 0.00 | 0.00 | 0.181243E+11 | 0.101263E+11 | 32765.66 | 31-JUL-07:01 | 14410.04 | 0.00 |
August | 0.00 | 0.00 | 0.182149E+11 | 0.105083E+11 | 32737.28 | 14-AUG-07:01 | 14097.60 | 0.00 |
September | 0.00 | 0.00 | 0.158110E+11 | 0.883056E+10 | 32743.14 | 05-SEP-07:01 | 14250.82 | 0.00 |
October | 0.00 | 0.00 | 0.135223E+11 | 0.819959E+10 | 32707.33 | 25-OCT-07:01 | 14622.32 | 0.00 |
November | 0.00 | 0.00 | 0.560555E+10 | 0.356301E+10 | 31593.06 | 02-NOV-07:02 | 17016.20 | 0.00 |
December | 0.00 | 0.00 | 0.357275E+10 | 0.224607E+10 | 31401.13 | 15-DEC-08:62 | 17111.42 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.121932E+12 | 0.727899E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.197263E+10 | 0.125763E+10 | 29762.11 | 13841.82 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.182149E+11 | 0.105083E+11 | 32765.66 | 17111.42 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.185561E+10 | 0.117707E+10 | 29578.20 | 20-JAN-08:62 | 13711.31 | 0.00 |
February | 0.00 | 0.00 | 0.260772E+10 | 0.163846E+10 | 29952.10 | 28-FEB-08:62 | 15346.27 | 0.00 |
March | 0.00 | 0.00 | 0.369586E+10 | 0.240000E+10 | 30709.39 | 07-MAR-08:62 | 14842.71 | 0.00 |
April | 0.00 | 0.00 | 0.674264E+10 | 0.447700E+10 | 31421.33 | 29-APR-07:02 | 16702.35 | 0.00 |
May | 0.00 | 0.00 | 0.150089E+11 | 0.916411E+10 | 32186.00 | 24-MAY-07:01 | 15111.31 | 0.00 |
June | 0.00 | 0.00 | 0.161473E+11 | 0.972824E+10 | 32487.61 | 19-JUN-07:03 | 13940.94 | 0.00 |
July | 0.00 | 0.00 | 0.179431E+11 | 0.999882E+10 | 32566.70 | 31-JUL-07:01 | 14263.60 | 0.00 |
August | 0.00 | 0.00 | 0.180251E+11 | 0.103723E+11 | 32538.49 | 14-AUG-07:01 | 13912.03 | 0.00 |
September | 0.00 | 0.00 | 0.156306E+11 | 0.870514E+10 | 32559.24 | 05-SEP-07:01 | 14113.54 | 0.00 |
October | 0.00 | 0.00 | 0.133531E+11 | 0.807481E+10 | 32529.43 | 25-OCT-07:01 | 14428.15 | 0.00 |
November | 0.00 | 0.00 | 0.543748E+10 | 0.343990E+10 | 31396.02 | 02-NOV-07:02 | 16778.78 | 0.00 |
December | 0.00 | 0.00 | 0.345941E+10 | 0.216445E+10 | 31205.20 | 15-DEC-08:62 | 16883.32 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.119907E+12 | 0.713403E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.185561E+10 | 0.117707E+10 | 29578.20 | 13711.31 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.180251E+11 | 0.103723E+11 | 32566.70 | 16883.32 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.301783E+10 | 0.187911E+10 | 54575.39 | 19-JAN-09:02 | 29227.14 | 0.00 |
February | 0.00 | 0.00 | 0.440620E+10 | 0.271080E+10 | 53143.67 | 28-FEB-09:02 | 27482.79 | 0.00 |
March | 0.00 | 0.00 | 0.626015E+10 | 0.397940E+10 | 54828.73 | 07-MAR-09:02 | 29885.19 | 0.00 |
April | 0.00 | 0.00 | 0.118086E+11 | 0.771464E+10 | 55300.80 | 29-APR-08:62 | 30203.21 | 0.00 |
May | 0.00 | 0.00 | 0.266940E+11 | 0.160780E+11 | 56987.71 | 21-MAY-09:01 | 26803.92 | 0.00 |
June | 0.00 | 0.00 | 0.289312E+11 | 0.172060E+11 | 57367.26 | 19-JUN-08:61 | 24672.97 | 0.00 |
July | 0.00 | 0.00 | 0.320332E+11 | 0.175785E+11 | 57624.77 | 31-JUL-08:61 | 24849.26 | 0.00 |
August | 0.00 | 0.00 | 0.324222E+11 | 0.184050E+11 | 57446.79 | 07-AUG-08:61 | 26134.53 | 0.00 |
September | 0.00 | 0.00 | 0.277502E+11 | 0.151564E+11 | 57683.53 | 05-SEP-08:61 | 24561.85 | 0.00 |
October | 0.00 | 0.00 | 0.239866E+11 | 0.142859E+11 | 57505.40 | 08-OCT-09:01 | 26245.91 | 0.00 |
November | 0.00 | 0.00 | 0.948435E+10 | 0.587665E+10 | 55327.39 | 02-NOV-08:61 | 30088.83 | 0.00 |
December | 0.00 | 0.00 | 0.600218E+10 | 0.368202E+10 | 55059.74 | 15-DEC-09:02 | 29714.43 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.212797E+12 | 0.124552E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.301783E+10 | 0.187911E+10 | 53143.67 | 24561.85 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.324222E+11 | 0.184050E+11 | 57683.53 | 30203.21 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.152277E+10 | 0.948424E+09 | 27060.86 | 01-JAN-10:02 | 17369.31 | 0.00 |
February | 0.00 | 0.00 | 0.223619E+10 | 0.137551E+10 | 27009.10 | 28-FEB-09:02 | 13966.81 | 0.00 |
March | 0.00 | 0.00 | 0.319245E+10 | 0.202637E+10 | 28737.87 | 07-MAR-09:02 | 15682.78 | 0.00 |
April | 0.00 | 0.00 | 0.607227E+10 | 0.396919E+10 | 28985.77 | 29-APR-08:62 | 15830.88 | 0.00 |
May | 0.00 | 0.00 | 0.138489E+11 | 0.834873E+10 | 29888.06 | 21-MAY-09:01 | 14001.38 | 0.00 |
June | 0.00 | 0.00 | 0.150089E+11 | 0.893226E+10 | 30086.19 | 19-JUN-08:61 | 12841.19 | 0.00 |
July | 0.00 | 0.00 | 0.166225E+11 | 0.913034E+10 | 30221.24 | 31-JUL-08:61 | 12948.90 | 0.00 |
August | 0.00 | 0.00 | 0.168171E+11 | 0.955429E+10 | 30127.90 | 07-AUG-08:61 | 13613.85 | 0.00 |
September | 0.00 | 0.00 | 0.143829E+11 | 0.786428E+10 | 30252.06 | 05-SEP-08:61 | 12858.39 | 0.00 |
October | 0.00 | 0.00 | 0.124231E+11 | 0.740270E+10 | 30158.63 | 08-OCT-09:01 | 13711.04 | 0.00 |
November | 0.00 | 0.00 | 0.486412E+10 | 0.301067E+10 | 29001.74 | 02-NOV-08:61 | 15795.18 | 0.00 |
December | 0.00 | 0.00 | 0.308176E+10 | 0.188918E+10 | 28864.31 | 15-DEC-09:02 | 15601.80 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.110073E+12 | 0.644519E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.152277E+10 | 0.948424E+09 | 27009.10 | 12841.19 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.168171E+11 | 0.955429E+10 | 30252.06 | 17369.31 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.148757E+10 | 0.925100E+09 | 26944.71 | 01-JAN-10:02 | 17282.96 | 0.00 |
February | 0.00 | 0.00 | 0.218607E+10 | 0.134236E+10 | 25752.16 | 28-FEB-09:02 | 13204.53 | 0.00 |
March | 0.00 | 0.00 | 0.313506E+10 | 0.198510E+10 | 28620.96 | 07-MAR-09:02 | 15543.49 | 0.00 |
April | 0.00 | 0.00 | 0.599684E+10 | 0.391489E+10 | 28866.31 | 29-APR-08:62 | 15717.24 | 0.00 |
May | 0.00 | 0.00 | 0.137713E+11 | 0.829428E+10 | 29758.78 | 21-MAY-09:01 | 13912.23 | 0.00 |
June | 0.00 | 0.00 | 0.149370E+11 | 0.888089E+10 | 29959.78 | 19-JUN-08:03 | 12675.28 | 0.00 |
July | 0.00 | 0.00 | 0.165553E+11 | 0.908407E+10 | 30094.26 | 31-JUL-08:61 | 12873.76 | 0.00 |
August | 0.00 | 0.00 | 0.167510E+11 | 0.950790E+10 | 30001.31 | 07-AUG-08:02 | 13433.35 | 0.00 |
September | 0.00 | 0.00 | 0.143179E+11 | 0.782009E+10 | 30124.95 | 05-SEP-08:61 | 12788.97 | 0.00 |
October | 0.00 | 0.00 | 0.123556E+11 | 0.735392E+10 | 30031.92 | 08-OCT-09:01 | 13634.24 | 0.00 |
November | 0.00 | 0.00 | 0.480317E+10 | 0.296554E+10 | 28882.96 | 02-NOV-08:61 | 15683.91 | 0.00 |
December | 0.00 | 0.00 | 0.304091E+10 | 0.186023E+10 | 28745.14 | 15-DEC-09:02 | 15485.66 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.109338E+12 | 0.639344E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.148757E+10 | 0.925100E+09 | 25752.16 | 12675.28 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.167510E+11 | 0.950790E+10 | 30124.95 | 17282.96 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.142932E+10 | 0.887203E+09 | 27063.94 | 01-JAN-10:02 | 17329.31 | 0.00 |
February | 0.00 | 0.00 | 0.209986E+10 | 0.128652E+10 | 21868.48 | 28-FEB-09:02 | 10999.69 | 0.00 |
March | 0.00 | 0.00 | 0.303795E+10 | 0.191593E+10 | 28754.51 | 07-MAR-09:02 | 15454.97 | 0.00 |
April | 0.00 | 0.00 | 0.586639E+10 | 0.382357E+10 | 28993.58 | 29-APR-08:62 | 15709.83 | 0.00 |
May | 0.00 | 0.00 | 0.137339E+11 | 0.827015E+10 | 29889.24 | 21-MAY-09:01 | 13918.98 | 0.00 |
June | 0.00 | 0.00 | 0.149392E+11 | 0.888338E+10 | 30100.28 | 19-JUN-08:61 | 12777.47 | 0.00 |
July | 0.00 | 0.00 | 0.166013E+11 | 0.911801E+10 | 30235.40 | 31-JUL-08:61 | 12917.45 | 0.00 |
August | 0.00 | 0.00 | 0.168184E+11 | 0.955654E+10 | 30142.01 | 07-AUG-08:61 | 13618.88 | 0.00 |
September | 0.00 | 0.00 | 0.143536E+11 | 0.784613E+10 | 30266.22 | 05-SEP-08:61 | 12854.67 | 0.00 |
October | 0.00 | 0.00 | 0.123541E+11 | 0.735355E+10 | 30172.76 | 08-OCT-09:01 | 13703.08 | 0.00 |
November | 0.00 | 0.00 | 0.472164E+10 | 0.290587E+10 | 29015.44 | 02-NOV-08:61 | 15713.15 | 0.00 |
December | 0.00 | 0.00 | 0.297905E+10 | 0.181674E+10 | 28875.66 | 15-DEC-09:02 | 15477.07 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.108935E+12 | 0.636636E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.142932E+10 | 0.887203E+09 | 21868.48 | 10999.69 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.168184E+11 | 0.955654E+10 | 30266.22 | 17329.31 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.149374E+10 | 0.937971E+09 | 24423.38 | 01-JAN-10:02 | 15717.28 | 0.00 |
February | 0.00 | 0.00 | 0.216685E+10 | 0.134307E+10 | 11448.97 | 24-FEB-13:10 | 7146.18 | 0.00 |
March | 0.00 | 0.00 | 0.323501E+10 | 0.206314E+10 | 21426.75 | 07-MAR-09:02 | 10672.86 | 0.00 |
April | 0.00 | 0.00 | 0.618047E+10 | 0.407982E+10 | 33411.24 | 29-APR-08:62 | 16978.06 | 0.00 |
May | 0.00 | 0.00 | 0.148762E+11 | 0.908577E+10 | 34315.00 | 24-MAY-08:61 | 15160.43 | 0.00 |
June | 0.00 | 0.00 | 0.163351E+11 | 0.988559E+10 | 34446.19 | 05-JUN-08:61 | 15593.89 | 0.00 |
July | 0.00 | 0.00 | 0.182580E+11 | 0.102667E+11 | 34585.22 | 31-JUL-08:61 | 14615.19 | 0.00 |
August | 0.00 | 0.00 | 0.186380E+11 | 0.108230E+11 | 34478.40 | 07-AUG-08:61 | 15121.04 | 0.00 |
September | 0.00 | 0.00 | 0.158068E+11 | 0.884449E+10 | 34620.49 | 05-SEP-08:02 | 14478.08 | 0.00 |
October | 0.00 | 0.00 | 0.135597E+11 | 0.821608E+10 | 34584.43 | 25-OCT-08:61 | 15036.16 | 0.00 |
November | 0.00 | 0.00 | 0.501133E+10 | 0.312446E+10 | 33451.78 | 02-NOV-08:61 | 17324.04 | 0.00 |
December | 0.00 | 0.00 | 0.309934E+10 | 0.190979E+10 | 33256.21 | 15-DEC-09:02 | 16942.96 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.118661E+12 | 0.705799E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.149374E+10 | 0.937971E+09 | 11448.97 | 7146.18 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.186380E+11 | 0.108230E+11 | 34620.49 | 17324.04 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.169628E+10 | 0.36 | 2314.75 | 10-JAN-09:01 | 0.88 |
February | 0.153931E+10 | 0.36 | 2314.75 | 05-FEB-09:02 | 0.88 |
March | 0.169989E+10 | 0.36 | 2314.75 | 07-MAR-09:02 | 0.86 |
April | 0.163077E+10 | 0.36 | 2314.75 | 22-APR-08:62 | 0.87 |
May | 0.171541E+10 | 0.36 | 2314.75 | 01-MAY-08:62 | 0.86 |
June | 0.171290E+10 | 0.37 | 2314.75 | 01-JUN-08:62 | 0.86 |
July | 0.183967E+10 | 0.37 | 2314.75 | 01-JUL-08:61 | 0.86 |
August | 0.184046E+10 | 0.37 | 2314.75 | 01-AUG-08:61 | 0.86 |
September | 0.173415E+10 | 0.37 | 2314.75 | 01-SEP-08:61 | 0.86 |
October | 0.176277E+10 | 0.37 | 2314.75 | 02-OCT-08:62 | 0.87 |
November | 0.162924E+10 | 0.36 | 2314.75 | 01-NOV-08:62 | 0.86 |
December | 0.170255E+10 | 0.36 | 2314.75 | 11-DEC-09:02 | 0.86 |
Annual Sum or Average | 0.205034E+11 | 0.36 | |||
Minimum of Months | 0.153931E+10 | 0.36 | 2314.75 | 0.86 | |
Maximum of Months | 0.184046E+10 | 0.37 | 2314.75 | 0.88 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.761048E+09 | 0.35 | 1257.30 | 19-JAN-09:02 | 0.89 |
February | 0.725603E+09 | 0.36 | 1257.30 | 28-FEB-09:02 | 0.90 |
March | 0.802132E+09 | 0.37 | 1257.30 | 07-MAR-09:02 | 0.90 |
April | 0.788044E+09 | 0.38 | 1257.30 | 22-APR-08:62 | 0.90 |
May | 0.825343E+09 | 0.39 | 1257.30 | 01-MAY-08:62 | 0.90 |
June | 0.831357E+09 | 0.39 | 1257.30 | 01-JUN-08:62 | 0.90 |
July | 0.902745E+09 | 0.40 | 1257.30 | 01-JUL-08:61 | 0.90 |
August | 0.899999E+09 | 0.40 | 1257.30 | 01-AUG-08:61 | 0.90 |
September | 0.838649E+09 | 0.39 | 1257.30 | 01-SEP-08:61 | 0.90 |
October | 0.852505E+09 | 0.39 | 1257.30 | 02-OCT-08:62 | 0.90 |
November | 0.816973E+09 | 0.37 | 1257.30 | 01-NOV-08:62 | 0.90 |
December | 0.815680E+09 | 0.37 | 1257.30 | 11-DEC-09:02 | 0.90 |
Annual Sum or Average | 0.986008E+10 | 0.38 | |||
Minimum of Months | 0.725603E+09 | 0.35 | 1257.30 | 0.89 | |
Maximum of Months | 0.902745E+09 | 0.40 | 1257.30 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.736580E+09 | 0.30 | 1262.59 | 01-JAN-09:02 | 0.90 |
February | 0.668499E+09 | 0.30 | 1262.59 | 28-FEB-08:62 | 0.90 |
March | 0.750600E+09 | 0.30 | 1262.59 | 07-MAR-08:62 | 0.89 |
April | 0.711591E+09 | 0.30 | 1262.59 | 01-APR-07:03 | 0.89 |
May | 0.756041E+09 | 0.30 | 1262.59 | 01-MAY-07:02 | 0.89 |
June | 0.760554E+09 | 0.31 | 1262.59 | 01-JUN-07:02 | 0.89 |
July | 0.806988E+09 | 0.31 | 1262.59 | 01-JUL-07:01 | 0.89 |
August | 0.820300E+09 | 0.32 | 1262.59 | 01-AUG-07:01 | 0.89 |
September | 0.757434E+09 | 0.30 | 1262.59 | 01-SEP-07:01 | 0.89 |
October | 0.770411E+09 | 0.30 | 1262.59 | 01-OCT-08:62 | 0.90 |
November | 0.711930E+09 | 0.30 | 1262.59 | 01-NOV-07:02 | 0.89 |
December | 0.733523E+09 | 0.30 | 1262.59 | 10-DEC-09:02 | 0.90 |
Annual Sum or Average | 0.898445E+10 | 0.30 | |||
Minimum of Months | 0.668499E+09 | 0.30 | 1262.59 | 0.89 | |
Maximum of Months | 0.820300E+09 | 0.32 | 1262.59 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.739947E+09 | 0.30 | 1266.68 | 01-JAN-09:02 | 0.90 |
February | 0.671246E+09 | 0.30 | 1266.68 | 05-FEB-09:02 | 0.91 |
March | 0.753419E+09 | 0.30 | 1266.68 | 07-MAR-08:62 | 0.89 |
April | 0.713799E+09 | 0.30 | 1266.68 | 01-APR-07:03 | 0.89 |
May | 0.758326E+09 | 0.30 | 1266.68 | 01-MAY-07:02 | 0.89 |
June | 0.762955E+09 | 0.31 | 1266.68 | 01-JUN-07:02 | 0.89 |
July | 0.809881E+09 | 0.31 | 1266.68 | 01-JUL-07:01 | 0.89 |
August | 0.822860E+09 | 0.32 | 1266.68 | 01-AUG-07:01 | 0.89 |
September | 0.760232E+09 | 0.30 | 1266.68 | 01-SEP-07:01 | 0.89 |
October | 0.772879E+09 | 0.30 | 1266.68 | 01-OCT-08:62 | 0.90 |
November | 0.714113E+09 | 0.30 | 1266.68 | 01-NOV-07:02 | 0.89 |
December | 0.736397E+09 | 0.30 | 1266.68 | 10-DEC-09:02 | 0.90 |
Annual Sum or Average | 0.901605E+10 | 0.30 | |||
Minimum of Months | 0.671246E+09 | 0.30 | 1266.68 | 0.89 | |
Maximum of Months | 0.822860E+09 | 0.32 | 1266.68 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.736981E+09 | 0.30 | 1258.99 | 01-JAN-09:02 | 0.90 |
February | 0.668121E+09 | 0.30 | 1258.99 | 05-FEB-09:02 | 0.91 |
March | 0.749511E+09 | 0.30 | 1258.99 | 07-MAR-08:62 | 0.89 |
April | 0.709203E+09 | 0.30 | 1258.99 | 22-APR-07:02 | 0.89 |
May | 0.752629E+09 | 0.30 | 1258.99 | 01-MAY-07:02 | 0.89 |
June | 0.756925E+09 | 0.31 | 1258.99 | 01-JUN-07:02 | 0.89 |
July | 0.803948E+09 | 0.31 | 1258.99 | 01-JUL-07:01 | 0.89 |
August | 0.816492E+09 | 0.32 | 1258.99 | 01-AUG-07:01 | 0.89 |
September | 0.754751E+09 | 0.30 | 1258.99 | 01-SEP-07:01 | 0.89 |
October | 0.767416E+09 | 0.30 | 1258.99 | 01-OCT-08:62 | 0.90 |
November | 0.709460E+09 | 0.30 | 1258.99 | 01-NOV-07:02 | 0.89 |
December | 0.732835E+09 | 0.30 | 1258.99 | 10-DEC-09:02 | 0.90 |
Annual Sum or Average | 0.895827E+10 | 0.30 | |||
Minimum of Months | 0.668121E+09 | 0.30 | 1258.99 | 0.89 | |
Maximum of Months | 0.816492E+09 | 0.32 | 1258.99 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116721E+10 | 0.27 | 2153.43 | 01-JAN-10:02 | 0.87 |
February | 0.105731E+10 | 0.27 | 2153.43 | 05-FEB-10:01 | 0.88 |
March | 0.118617E+10 | 0.27 | 2153.43 | 07-MAR-09:02 | 0.86 |
April | 0.112167E+10 | 0.26 | 2153.43 | 22-APR-08:62 | 0.87 |
May | 0.121266E+10 | 0.27 | 2153.43 | 01-MAY-08:62 | 0.86 |
June | 0.123397E+10 | 0.28 | 2153.43 | 01-JUN-08:62 | 0.86 |
July | 0.132277E+10 | 0.28 | 2153.43 | 01-JUL-08:61 | 0.86 |
August | 0.134565E+10 | 0.29 | 2153.43 | 01-AUG-08:61 | 0.86 |
September | 0.122939E+10 | 0.28 | 2153.43 | 01-SEP-08:61 | 0.86 |
October | 0.124466E+10 | 0.27 | 2153.43 | 01-OCT-09:02 | 0.87 |
November | 0.112329E+10 | 0.26 | 2153.43 | 01-NOV-08:62 | 0.86 |
December | 0.115975E+10 | 0.26 | 2153.43 | 10-DEC-10:02 | 0.87 |
Annual Sum or Average | 0.144045E+11 | 0.27 | |||
Minimum of Months | 0.105731E+10 | 0.26 | 2153.43 | 0.86 | |
Maximum of Months | 0.134565E+10 | 0.29 | 2153.43 | 0.88 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.633885E+09 | 0.28 | 1168.53 | 01-JAN-10:02 | 0.90 |
February | 0.574215E+09 | 0.28 | 1168.53 | 05-FEB-10:01 | 0.91 |
March | 0.643971E+09 | 0.28 | 1168.53 | 07-MAR-09:02 | 0.89 |
April | 0.608467E+09 | 0.27 | 1168.53 | 22-APR-08:62 | 0.90 |
May | 0.657255E+09 | 0.28 | 1168.53 | 01-MAY-08:62 | 0.89 |
June | 0.668250E+09 | 0.29 | 1168.53 | 01-JUN-08:62 | 0.89 |
July | 0.716023E+09 | 0.29 | 1168.53 | 01-JUL-08:61 | 0.89 |
August | 0.728179E+09 | 0.30 | 1168.53 | 01-AUG-08:61 | 0.89 |
September | 0.665303E+09 | 0.29 | 1168.53 | 01-SEP-08:61 | 0.89 |
October | 0.673535E+09 | 0.28 | 1168.53 | 01-OCT-09:02 | 0.90 |
November | 0.609236E+09 | 0.27 | 1168.53 | 01-NOV-08:62 | 0.89 |
December | 0.629751E+09 | 0.27 | 1168.53 | 10-DEC-10:02 | 0.90 |
Annual Sum or Average | 0.780807E+10 | 0.28 | |||
Minimum of Months | 0.574215E+09 | 0.27 | 1168.53 | 0.89 | |
Maximum of Months | 0.728179E+09 | 0.30 | 1168.53 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.631980E+09 | 0.28 | 1163.62 | 01-JAN-10:02 | 0.90 |
February | 0.572271E+09 | 0.28 | 1163.62 | 05-FEB-10:01 | 0.91 |
March | 0.641613E+09 | 0.28 | 1163.62 | 07-MAR-09:02 | 0.89 |
April | 0.605864E+09 | 0.27 | 1163.62 | 22-APR-08:62 | 0.90 |
May | 0.654370E+09 | 0.28 | 1163.62 | 01-MAY-08:62 | 0.89 |
June | 0.665461E+09 | 0.29 | 1163.62 | 01-JUN-08:62 | 0.89 |
July | 0.713336E+09 | 0.29 | 1163.62 | 01-JUL-08:61 | 0.89 |
August | 0.725471E+09 | 0.30 | 1163.62 | 01-AUG-08:61 | 0.89 |
September | 0.662707E+09 | 0.29 | 1163.62 | 01-SEP-08:61 | 0.89 |
October | 0.670756E+09 | 0.28 | 1163.62 | 01-OCT-09:02 | 0.90 |
November | 0.606624E+09 | 0.27 | 1163.62 | 01-NOV-08:62 | 0.89 |
December | 0.627579E+09 | 0.27 | 1163.62 | 10-DEC-10:02 | 0.90 |
Annual Sum or Average | 0.777803E+10 | 0.28 | |||
Minimum of Months | 0.572271E+09 | 0.27 | 1163.62 | 0.89 | |
Maximum of Months | 0.725471E+09 | 0.30 | 1163.62 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.636755E+09 | 0.28 | 1169.08 | 01-JAN-10:02 | 0.90 |
February | 0.576100E+09 | 0.28 | 1169.08 | 05-FEB-10:01 | 0.91 |
March | 0.645670E+09 | 0.28 | 1169.08 | 07-MAR-09:02 | 0.89 |
April | 0.608422E+09 | 0.27 | 1169.08 | 23-APR-09:02 | 0.90 |
May | 0.655992E+09 | 0.28 | 1169.08 | 01-MAY-08:62 | 0.89 |
June | 0.667311E+09 | 0.29 | 1169.08 | 01-JUN-08:62 | 0.89 |
July | 0.716301E+09 | 0.29 | 1169.08 | 01-JUL-08:61 | 0.89 |
August | 0.728721E+09 | 0.30 | 1169.08 | 01-AUG-08:61 | 0.89 |
September | 0.665580E+09 | 0.29 | 1169.08 | 01-SEP-08:61 | 0.89 |
October | 0.673356E+09 | 0.28 | 1169.08 | 01-OCT-09:02 | 0.90 |
November | 0.609195E+09 | 0.27 | 1169.08 | 01-NOV-08:62 | 0.89 |
December | 0.631684E+09 | 0.27 | 1169.08 | 10-DEC-10:02 | 0.90 |
Annual Sum or Average | 0.781509E+10 | 0.28 | |||
Minimum of Months | 0.576100E+09 | 0.27 | 1169.08 | 0.89 | |
Maximum of Months | 0.728721E+09 | 0.30 | 1169.08 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.737273E+09 | 0.28 | 1347.74 | 05-JAN-09:01 | 0.91 |
February | 0.666226E+09 | 0.28 | 1347.74 | 05-FEB-09:02 | 0.91 |
March | 0.746881E+09 | 0.28 | 1347.74 | 10-MAR-09:02 | 0.91 |
April | 0.699517E+09 | 0.27 | 1347.74 | 23-APR-09:02 | 0.90 |
May | 0.743189E+09 | 0.28 | 1347.74 | 01-MAY-08:62 | 0.89 |
June | 0.751834E+09 | 0.28 | 1347.74 | 01-JUN-08:62 | 0.89 |
July | 0.807992E+09 | 0.29 | 1347.74 | 01-JUL-08:61 | 0.89 |
August | 0.822797E+09 | 0.29 | 1347.74 | 01-AUG-08:61 | 0.89 |
September | 0.755569E+09 | 0.28 | 1347.74 | 01-SEP-08:61 | 0.89 |
October | 0.763890E+09 | 0.28 | 1347.74 | 01-OCT-09:02 | 0.90 |
November | 0.700685E+09 | 0.27 | 1347.74 | 01-NOV-08:62 | 0.89 |
December | 0.730917E+09 | 0.27 | 1347.74 | 10-DEC-10:02 | 0.90 |
Annual Sum or Average | 0.892677E+10 | 0.28 | |||
Minimum of Months | 0.666226E+09 | 0.27 | 1347.74 | 0.89 | |
Maximum of Months | 0.822797E+09 | 0.29 | 1347.74 | 0.91 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.283362E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.301625E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.387296E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.575756E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.107794E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.113508E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.126085E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.124908E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.110799E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.979421E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.481494E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.375159E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.921505E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.283362E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.126085E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.144487E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.161895E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.209026E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.307486E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.536446E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.561172E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.620057E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.612206E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.544942E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.489126E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.255543E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.193089E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.463548E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.144487E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.620057E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.124704E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.137057E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.173562E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.246580E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.444077E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.469010E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.508044E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.513421E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.445382E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.397616E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.209320E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.161721E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.383049E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.124704E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.513421E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.123639E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.135803E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.172456E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.246131E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.445548E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.470843E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.510607E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.515594E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.447503E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.399113E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.208513E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.161171E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.383692E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.123639E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.515594E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.120522E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.132209E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.168213E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.240656E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.440264E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.465743E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.505664E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.510418E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.442817E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.394605E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.204045E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.158139E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.378330E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.120522E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.510418E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.194065E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.217853E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.278715E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.413492E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.777786E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.830590E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.900378E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.915523E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.781968E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.702578E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.346963E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.264692E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.662460E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.194065E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.915523E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.101809E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.113444E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.144786E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.213379E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.401233E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.428222E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.464259E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.471882E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.402925E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.362148E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.179316E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.138106E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.342151E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.101809E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.471882E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.100764E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.112042E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.143166E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.211284E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.399066E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.426165E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.462320E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.469962E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.401102E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.360236E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.177571E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.136915E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.340059E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.100764E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.469962E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.998546E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.110414E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.141324E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.208552E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.398657E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.426639E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.463912E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.472022E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.402404E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.360610E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.175939E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.135950E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.339628E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.998546E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.472022E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.111897E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.121742E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.157229E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.227293E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.439118E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.472452E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.516507E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.528157E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.448814E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.400701E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.193355E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.149920E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.376719E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.111897E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.528157E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.169628E+10 | 0.445858E+10 | 0.665037E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.153931E+10 | 0.581438E+10 | 0.792458E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.169989E+10 | 0.848433E+10 | 0.525156E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.163077E+10 | 0.161535E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.171541E+10 | 0.364957E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.171290E+10 | 0.390742E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.183967E+10 | 0.444826E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.184046E+10 | 0.438970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.173415E+10 | 0.388431E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.176277E+10 | 0.330470E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.162924E+10 | 0.128170E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.170255E+10 | 0.821480E+10 | 0.605356E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.205034E+11 | 0.291782E+12 | 0.258801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.153931E+10 | 0.445858E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.184046E+10 | 0.444826E+11 | 0.792458E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.761048E+09 | 0.272824E+10 | 64446953.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.725603E+09 | 0.358344E+10 | 0.156652E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.802132E+09 | 0.512196E+10 | 0.128765E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.788044E+09 | 0.905881E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.825343E+09 | 0.184404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.831357E+09 | 0.195105E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.902745E+09 | 0.219685E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.899999E+09 | 0.216319E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.838649E+09 | 0.192916E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.852505E+09 | 0.167267E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.816973E+09 | 0.706082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.815680E+09 | 0.452998E+10 | 0.131572E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.986008E+10 | 0.149653E+12 | 0.481437E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.725603E+09 | 0.272824E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.902745E+09 | 0.219685E+11 | 0.156652E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.736580E+09 | 0.203272E+10 | 0.208443E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.668499E+09 | 0.281209E+10 | 0.256033E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.750600E+09 | 0.391835E+10 | 0.185211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.711591E+09 | 0.698510E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.756041E+09 | 0.151643E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.760554E+09 | 0.162736E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.806988E+09 | 0.180309E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.820300E+09 | 0.181371E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.757434E+09 | 0.157349E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.770411E+09 | 0.134711E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.711930E+09 | 0.565002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.733523E+09 | 0.360899E+10 | 0.213153E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.898445E+10 | 0.121819E+12 | 0.862840E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.668499E+09 | 0.203272E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.820300E+09 | 0.181371E+11 | 0.256033E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.739947E+09 | 0.197263E+10 | 0.249084E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.671246E+09 | 0.274584E+10 | 0.280495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.753419E+09 | 0.385791E+10 | 0.201962E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.713799E+09 | 0.695323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.758326E+09 | 0.152134E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.762955E+09 | 0.163380E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.809881E+09 | 0.181243E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.822860E+09 | 0.182149E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.760232E+09 | 0.158110E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.772879E+09 | 0.135223E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.714113E+09 | 0.560555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.736397E+09 | 0.357275E+10 | 0.233862E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.901605E+10 | 0.121932E+12 | 0.965403E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.671246E+09 | 0.197263E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.822860E+09 | 0.182149E+11 | 0.280495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.736981E+09 | 0.185561E+10 | 0.310915E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.668121E+09 | 0.260772E+10 | 0.319377E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.749511E+09 | 0.369586E+10 | 0.230478E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.709203E+09 | 0.674264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.752629E+09 | 0.150089E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.756925E+09 | 0.161473E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.803948E+09 | 0.179431E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.816492E+09 | 0.180251E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.754751E+09 | 0.156306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.767416E+09 | 0.133531E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.709460E+09 | 0.543748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.732835E+09 | 0.345941E+10 | 0.271783E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.895827E+10 | 0.119907E+12 | 0.113255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.668121E+09 | 0.185561E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.816492E+09 | 0.180251E+11 | 0.319377E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.116721E+10 | 0.301783E+10 | 0.686863E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.105731E+10 | 0.440620E+10 | 0.636426E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.118617E+10 | 0.626015E+10 | 0.439297E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.112167E+10 | 0.118086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.121266E+10 | 0.266940E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.123397E+10 | 0.289312E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.132277E+10 | 0.320332E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.134565E+10 | 0.324222E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.122939E+10 | 0.277502E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.124466E+10 | 0.239866E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112329E+10 | 0.948435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.115975E+10 | 0.600218E+10 | 0.591810E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144045E+11 | 0.212797E+12 | 0.235440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.105731E+10 | 0.301783E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.134565E+10 | 0.324222E+11 | 0.686863E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.633885E+09 | 0.152277E+10 | 0.379630E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.574215E+09 | 0.223619E+10 | 0.351744E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.643971E+09 | 0.319245E+10 | 0.243408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.608467E+09 | 0.607227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.657255E+09 | 0.138489E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.668250E+09 | 0.150089E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.716023E+09 | 0.166225E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.728179E+09 | 0.168171E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.665303E+09 | 0.143829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.673535E+09 | 0.124231E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.609236E+09 | 0.486412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.629751E+09 | 0.308176E+10 | 0.328338E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.780807E+10 | 0.110073E+12 | 0.130312E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.574215E+09 | 0.152277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.728179E+09 | 0.168171E+11 | 0.379630E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.631980E+09 | 0.148757E+10 | 0.409400E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.572271E+09 | 0.218607E+10 | 0.369993E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.641613E+09 | 0.313506E+10 | 0.257139E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.605864E+09 | 0.599684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.654370E+09 | 0.137713E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.665461E+09 | 0.149370E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.713336E+09 | 0.165553E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.725471E+09 | 0.167510E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.662707E+09 | 0.143179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.670756E+09 | 0.123556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.606624E+09 | 0.480317E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.627579E+09 | 0.304091E+10 | 0.347020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.777803E+10 | 0.109338E+12 | 0.138355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.572271E+09 | 0.148757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.725471E+09 | 0.167510E+11 | 0.409400E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.636755E+09 | 0.142932E+10 | 0.485599E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.576100E+09 | 0.209986E+10 | 0.418617E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.645670E+09 | 0.303795E+10 | 0.302328E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.608422E+09 | 0.586639E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.655992E+09 | 0.137339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.667311E+09 | 0.149392E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.716301E+09 | 0.166013E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.728721E+09 | 0.168184E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.665580E+09 | 0.143536E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.673356E+09 | 0.123541E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.609195E+09 | 0.472164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.631684E+09 | 0.297905E+10 | 0.396103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.781509E+10 | 0.108935E+12 | 0.160265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.576100E+09 | 0.142932E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.728721E+09 | 0.168184E+11 | 0.485599E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.737273E+09 | 0.149374E+10 | 0.678766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.666226E+09 | 0.216685E+10 | 0.557837E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.746881E+09 | 0.323501E+10 | 0.446352E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.699517E+09 | 0.618047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.743189E+09 | 0.148762E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.751834E+09 | 0.163351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.807992E+09 | 0.182580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.822797E+09 | 0.186380E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.755569E+09 | 0.158068E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.763890E+09 | 0.135597E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.700685E+09 | 0.501133E+10 | 784659.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.730917E+09 | 0.309934E+10 | 0.557290E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.892677E+10 | 0.118661E+12 | 0.224103E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.666226E+09 | 0.149374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.822797E+09 | 0.186380E+11 | 0.678766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.169628E+10 | 0.00 | 0.00 | 0.00 | 0.113734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.153931E+10 | 0.00 | 0.00 | 0.00 | 0.147694E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.169989E+10 | 0.00 | 0.00 | 0.00 | 0.217307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.163077E+10 | 0.00 | 0.00 | 0.00 | 0.412679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.171541E+10 | 0.00 | 0.00 | 0.00 | 0.906395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.171290E+10 | 0.00 | 0.00 | 0.00 | 0.963789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.183967E+10 | 0.00 | 0.00 | 0.00 | 0.107688E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.184046E+10 | 0.00 | 0.00 | 0.00 | 0.106504E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.173415E+10 | 0.00 | 0.00 | 0.00 | 0.934574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.176277E+10 | 0.00 | 0.00 | 0.00 | 0.803144E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.162924E+10 | 0.00 | 0.00 | 0.00 | 0.318569E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.170255E+10 | 0.00 | 0.00 | 0.00 | 0.204904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.205034E+11 | 0.00 | 0.00 | 0.00 | 0.716471E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.153931E+10 | 0.00 | 0.00 | 0.00 | 0.113734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.184046E+10 | 0.00 | 0.00 | 0.00 | 0.107688E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.761048E+09 | 0.00 | 0.00 | 0.00 | 0.683826E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.725603E+09 | 0.00 | 0.00 | 0.00 | 0.893347E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.802132E+09 | 0.00 | 0.00 | 0.00 | 0.128813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.788044E+09 | 0.00 | 0.00 | 0.00 | 0.228681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.825343E+09 | 0.00 | 0.00 | 0.00 | 0.453912E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.831357E+09 | 0.00 | 0.00 | 0.00 | 0.478036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.902745E+09 | 0.00 | 0.00 | 0.00 | 0.529782E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.899999E+09 | 0.00 | 0.00 | 0.00 | 0.522207E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.838649E+09 | 0.00 | 0.00 | 0.00 | 0.461077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.852505E+09 | 0.00 | 0.00 | 0.00 | 0.403876E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.816973E+09 | 0.00 | 0.00 | 0.00 | 0.173846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.815680E+09 | 0.00 | 0.00 | 0.00 | 0.111521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.986008E+10 | 0.00 | 0.00 | 0.00 | 0.364947E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.725603E+09 | 0.00 | 0.00 | 0.00 | 0.683826E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.902745E+09 | 0.00 | 0.00 | 0.00 | 0.529782E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.736580E+09 | 0.00 | 0.00 | 0.00 | 0.510465E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.668499E+09 | 0.00 | 0.00 | 0.00 | 0.702068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.750600E+09 | 0.00 | 0.00 | 0.00 | 0.985017E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.711591E+09 | 0.00 | 0.00 | 0.00 | 0.175421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.756041E+09 | 0.00 | 0.00 | 0.00 | 0.368473E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.760554E+09 | 0.00 | 0.00 | 0.00 | 0.392955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.806988E+09 | 0.00 | 0.00 | 0.00 | 0.427345E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.820300E+09 | 0.00 | 0.00 | 0.00 | 0.431391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.757434E+09 | 0.00 | 0.00 | 0.00 | 0.369638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.770411E+09 | 0.00 | 0.00 | 0.00 | 0.320575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.711930E+09 | 0.00 | 0.00 | 0.00 | 0.138127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.733523E+09 | 0.00 | 0.00 | 0.00 | 0.883683E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.898445E+10 | 0.00 | 0.00 | 0.00 | 0.293205E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.668499E+09 | 0.00 | 0.00 | 0.00 | 0.510465E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.820300E+09 | 0.00 | 0.00 | 0.00 | 0.431391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.739947E+09 | 0.00 | 0.00 | 0.00 | 0.496447E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.671246E+09 | 0.00 | 0.00 | 0.00 | 0.686783E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.753419E+09 | 0.00 | 0.00 | 0.00 | 0.971144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.713799E+09 | 0.00 | 0.00 | 0.00 | 0.174751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.758326E+09 | 0.00 | 0.00 | 0.00 | 0.369716E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.762955E+09 | 0.00 | 0.00 | 0.00 | 0.394547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.809881E+09 | 0.00 | 0.00 | 0.00 | 0.429618E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.822860E+09 | 0.00 | 0.00 | 0.00 | 0.433308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.760232E+09 | 0.00 | 0.00 | 0.00 | 0.371480E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.772879E+09 | 0.00 | 0.00 | 0.00 | 0.321825E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.714113E+09 | 0.00 | 0.00 | 0.00 | 0.137102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.736397E+09 | 0.00 | 0.00 | 0.00 | 0.875310E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.901605E+10 | 0.00 | 0.00 | 0.00 | 0.293532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.671246E+09 | 0.00 | 0.00 | 0.00 | 0.496447E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.822860E+09 | 0.00 | 0.00 | 0.00 | 0.433308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.736981E+09 | 0.00 | 0.00 | 0.00 | 0.468243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.668121E+09 | 0.00 | 0.00 | 0.00 | 0.653974E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.749511E+09 | 0.00 | 0.00 | 0.00 | 0.932615E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.709203E+09 | 0.00 | 0.00 | 0.00 | 0.169736E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.752629E+09 | 0.00 | 0.00 | 0.00 | 0.365001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.756925E+09 | 0.00 | 0.00 | 0.00 | 0.390051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.803948E+09 | 0.00 | 0.00 | 0.00 | 0.425269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.816492E+09 | 0.00 | 0.00 | 0.00 | 0.428769E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.754751E+09 | 0.00 | 0.00 | 0.00 | 0.367342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.767416E+09 | 0.00 | 0.00 | 0.00 | 0.317863E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.709460E+09 | 0.00 | 0.00 | 0.00 | 0.133099E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.732835E+09 | 0.00 | 0.00 | 0.00 | 0.848556E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.895827E+10 | 0.00 | 0.00 | 0.00 | 0.288747E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.668121E+09 | 0.00 | 0.00 | 0.00 | 0.468243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.816492E+09 | 0.00 | 0.00 | 0.00 | 0.428769E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.116721E+10 | 0.00 | 0.00 | 0.00 | 0.773434E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.105731E+10 | 0.00 | 0.00 | 0.00 | 0.112122E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.118617E+10 | 0.00 | 0.00 | 0.00 | 0.160098E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.112167E+10 | 0.00 | 0.00 | 0.00 | 0.301324E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.121266E+10 | 0.00 | 0.00 | 0.00 | 0.656520E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.123397E+10 | 0.00 | 0.00 | 0.00 | 0.707193E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.132277E+10 | 0.00 | 0.00 | 0.00 | 0.768101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.134565E+10 | 0.00 | 0.00 | 0.00 | 0.780958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.122939E+10 | 0.00 | 0.00 | 0.00 | 0.659029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.124466E+10 | 0.00 | 0.00 | 0.00 | 0.578112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112329E+10 | 0.00 | 0.00 | 0.00 | 0.234633E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.115975E+10 | 0.00 | 0.00 | 0.00 | 0.148717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144045E+11 | 0.00 | 0.00 | 0.00 | 0.518415E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.105731E+10 | 0.00 | 0.00 | 0.00 | 0.773434E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.134565E+10 | 0.00 | 0.00 | 0.00 | 0.780958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.633885E+09 | 0.00 | 0.00 | 0.00 | 0.384209E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.574215E+09 | 0.00 | 0.00 | 0.00 | 0.560224E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.643971E+09 | 0.00 | 0.00 | 0.00 | 0.803889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.608467E+09 | 0.00 | 0.00 | 0.00 | 0.152532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.657255E+09 | 0.00 | 0.00 | 0.00 | 0.335507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.668250E+09 | 0.00 | 0.00 | 0.00 | 0.361397E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.716023E+09 | 0.00 | 0.00 | 0.00 | 0.392657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.728179E+09 | 0.00 | 0.00 | 0.00 | 0.399064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.665303E+09 | 0.00 | 0.00 | 0.00 | 0.336394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.673535E+09 | 0.00 | 0.00 | 0.00 | 0.294795E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.609236E+09 | 0.00 | 0.00 | 0.00 | 0.118392E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.629751E+09 | 0.00 | 0.00 | 0.00 | 0.751307E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.780807E+10 | 0.00 | 0.00 | 0.00 | 0.264070E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.574215E+09 | 0.00 | 0.00 | 0.00 | 0.384209E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.728179E+09 | 0.00 | 0.00 | 0.00 | 0.399064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.631980E+09 | 0.00 | 0.00 | 0.00 | 0.375664E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.572271E+09 | 0.00 | 0.00 | 0.00 | 0.548151E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.641613E+09 | 0.00 | 0.00 | 0.00 | 0.790049E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.605864E+09 | 0.00 | 0.00 | 0.00 | 0.150697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.654370E+09 | 0.00 | 0.00 | 0.00 | 0.333629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.665461E+09 | 0.00 | 0.00 | 0.00 | 0.359619E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.713336E+09 | 0.00 | 0.00 | 0.00 | 0.390987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.725471E+09 | 0.00 | 0.00 | 0.00 | 0.397415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.662707E+09 | 0.00 | 0.00 | 0.00 | 0.334831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.670756E+09 | 0.00 | 0.00 | 0.00 | 0.293160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.606624E+09 | 0.00 | 0.00 | 0.00 | 0.116908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.627579E+09 | 0.00 | 0.00 | 0.00 | 0.741575E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.777803E+10 | 0.00 | 0.00 | 0.00 | 0.262279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.572271E+09 | 0.00 | 0.00 | 0.00 | 0.375664E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.725471E+09 | 0.00 | 0.00 | 0.00 | 0.397415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.636755E+09 | 0.00 | 0.00 | 0.00 | 0.361791E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.576100E+09 | 0.00 | 0.00 | 0.00 | 0.528039E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.645670E+09 | 0.00 | 0.00 | 0.00 | 0.767568E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.608422E+09 | 0.00 | 0.00 | 0.00 | 0.147710E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.655992E+09 | 0.00 | 0.00 | 0.00 | 0.333058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.667311E+09 | 0.00 | 0.00 | 0.00 | 0.359908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.716301E+09 | 0.00 | 0.00 | 0.00 | 0.392282E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.728721E+09 | 0.00 | 0.00 | 0.00 | 0.399150E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.665580E+09 | 0.00 | 0.00 | 0.00 | 0.335846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.673356E+09 | 0.00 | 0.00 | 0.00 | 0.293275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.609195E+09 | 0.00 | 0.00 | 0.00 | 0.115020E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.631684E+09 | 0.00 | 0.00 | 0.00 | 0.727812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.781509E+10 | 0.00 | 0.00 | 0.00 | 0.261477E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.576100E+09 | 0.00 | 0.00 | 0.00 | 0.361791E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.728721E+09 | 0.00 | 0.00 | 0.00 | 0.399150E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.737273E+09 | 0.00 | 0.00 | 0.00 | 0.381702E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.666226E+09 | 0.00 | 0.00 | 0.00 | 0.551197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.746881E+09 | 0.00 | 0.00 | 0.00 | 0.825408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.699517E+09 | 0.00 | 0.00 | 0.00 | 0.157341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.743189E+09 | 0.00 | 0.00 | 0.00 | 0.364799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.751834E+09 | 0.00 | 0.00 | 0.00 | 0.397269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.807992E+09 | 0.00 | 0.00 | 0.00 | 0.435708E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.822797E+09 | 0.00 | 0.00 | 0.00 | 0.445878E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.755569E+09 | 0.00 | 0.00 | 0.00 | 0.373257E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.763890E+09 | 0.00 | 0.00 | 0.00 | 0.324312E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.700685E+09 | 0.00 | 0.00 | 0.00 | 0.123286E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.730917E+09 | 0.00 | 0.00 | 0.00 | 0.768279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.892677E+10 | 0.00 | 0.00 | 0.00 | 0.287451E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.666226E+09 | 0.00 | 0.00 | 0.00 | 0.381702E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.822797E+09 | 0.00 | 0.00 | 0.00 | 0.445878E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.579138E+10 | 0.667777E+09 | 0.00 | 3103531.34 | 6681456.68 | 70209996.44 | 0.138773E+10 | 0.00 | 0.62 |
February | 0.349948E+10 | 0.863454E+09 | 0.00 | 3961970.77 | 1295616.16 | 0.269210E+09 | 0.204321E+10 | 0.00 | 0.67 |
March | 0.266971E+10 | 0.158872E+10 | 0.00 | 4385213.18 | 12167954.24 | 0.263067E+09 | 0.219153E+10 | 0.00 | 0.67 |
April | 0.264888E+09 | 0.383339E+10 | 0.00 | 5856331.89 | 25754199.39 | 0.00 | 0.253968E+10 | 0.00 | 0.72 |
May | 0.00 | 0.128900E+11 | 0.00 | 0.00 | 91060168.44 | 0.00 | 0.00 | 0.00 | 0.54 |
June | 0.00 | 0.144485E+11 | 0.00 | 0.00 | 87558194.06 | 0.00 | 0.00 | 0.00 | 0.54 |
July | 0.00 | 0.173458E+11 | 0.00 | 0.00 | 84886721.15 | 0.00 | 0.00 | 0.00 | 0.54 |
August | 0.00 | 0.161448E+11 | 0.00 | 0.00 | 85358032.25 | 0.00 | 0.00 | 0.00 | 0.54 |
September | 0.00 | 0.135523E+11 | 0.00 | 0.00 | 72555440.76 | 0.00 | 0.00 | 0.00 | 0.54 |
October | 0.105402E+09 | 0.103914E+11 | 0.00 | 3754288.64 | 38194913.85 | 0.00 | 0.114516E+10 | 0.00 | 0.62 |
November | 0.860303E+09 | 0.300488E+10 | 0.00 | 8530513.09 | 29004275.00 | 0.00 | 0.428467E+10 | 0.00 | 0.78 |
December | 0.348230E+10 | 0.179194E+10 | 0.00 | 3980353.63 | 22250315.78 | 0.158451E+09 | 0.293813E+10 | 0.00 | 0.65 |
Annual Sum or Average | 0.166735E+11 | 0.965229E+11 | 0.00 | 33572202.54 | 0.556767E+09 | 0.760938E+09 | 0.165301E+11 | 0.00 | 0.62 |
Minimum of Months | 0.00 | 0.667777E+09 | 0.00 | 0.00 | 1295616.16 | 0.00 | 0.00 | 0.00 | 0.54 |
Maximum of Months | 0.579138E+10 | 0.173458E+11 | 0.00 | 8530513.09 | 91060168.44 | 0.269210E+09 | 0.428467E+10 | 0.00 | 0.78 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.193862E+10 | 0.357697E+09 | 0.00 | 1860423.45 | 4344810.77 | 1222641.31 | 0.938260E+09 | 0.00 | 0.53 |
February | 0.104735E+10 | 0.487691E+09 | 0.00 | 2306690.01 | 5087596.76 | 53054031.57 | 0.129325E+10 | 0.00 | 0.60 |
March | 0.848346E+09 | 0.862969E+09 | 0.00 | 2374902.22 | 16280272.44 | 66565855.63 | 0.125804E+10 | 0.00 | 0.58 |
April | 62879972.72 | 0.184676E+10 | 0.00 | 2648518.85 | 35457717.48 | 0.00 | 0.116676E+10 | 0.00 | 0.63 |
May | 0.00 | 0.569891E+10 | 0.00 | 0.00 | 61344015.63 | 0.00 | 0.00 | 0.00 | 0.44 |
June | 0.00 | 0.636849E+10 | 0.00 | 0.00 | 60526296.27 | 0.00 | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.754039E+10 | 0.00 | 0.00 | 59211882.15 | 0.00 | 0.00 | 0.00 | 0.44 |
August | 0.00 | 0.709635E+10 | 0.00 | 0.00 | 57410065.06 | 0.00 | 0.00 | 0.00 | 0.45 |
September | 0.00 | 0.595596E+10 | 0.00 | 0.00 | 52967908.19 | 0.00 | 0.00 | 0.00 | 0.44 |
October | 26958329.51 | 0.460199E+10 | 0.00 | 1583090.25 | 34775396.35 | 0.00 | 0.508837E+09 | 0.00 | 0.52 |
November | 0.223233E+09 | 0.141009E+10 | 0.00 | 4664504.92 | 21472544.58 | 0.00 | 0.229557E+10 | 0.00 | 0.75 |
December | 0.108382E+10 | 0.880156E+09 | 0.00 | 2895241.09 | 14312889.44 | 34066021.08 | 0.195109E+10 | 0.00 | 0.61 |
Annual Sum or Average | 0.523121E+10 | 0.431075E+11 | 0.00 | 18333370.78 | 0.423191E+09 | 0.154909E+09 | 0.941182E+10 | 0.00 | 0.53 |
Minimum of Months | 0.00 | 0.357697E+09 | 0.00 | 0.00 | 4344810.77 | 0.00 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 0.193862E+10 | 0.754039E+10 | 0.00 | 4664504.92 | 61344015.63 | 66565855.63 | 0.229557E+10 | 0.00 | 0.75 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.210225E+10 | 0.297730E+09 | 0.00 | 825822.06 | 9480084.33 | 47105771.87 | 0.374646E+09 | 0.00 | 0.48 |
February | 0.125268E+10 | 0.408280E+09 | 0.00 | 1190747.09 | 6147444.77 | 97075017.93 | 0.559281E+09 | 0.00 | 0.52 |
March | 0.105977E+10 | 0.743642E+09 | 0.00 | 1329065.53 | 18262254.98 | 0.102255E+09 | 0.647770E+09 | 0.00 | 0.53 |
April | 0.166613E+09 | 0.150764E+10 | 0.00 | 1838578.62 | 82816335.38 | 0.00 | 0.696589E+09 | 0.00 | 0.57 |
May | 0.00 | 0.480425E+10 | 0.00 | 0.00 | 0.340766E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.540704E+10 | 0.00 | 102164.99 | 0.393088E+09 | 0.00 | 239519.79 | 0.00 | 0.43 |
July | 0.00 | 0.623409E+10 | 0.00 | 52061.56 | 0.440278E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
August | 0.00 | 0.604566E+10 | 0.00 | 0.00 | 0.386620E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
September | 712081.07 | 0.493469E+10 | 0.00 | 203014.87 | 0.309986E+09 | 0.00 | 62874.36 | 0.00 | 0.42 |
October | 73941112.85 | 0.386008E+10 | 0.00 | 1865541.71 | 0.238122E+09 | 0.00 | 0.432684E+09 | 0.00 | 0.49 |
November | 0.413921E+09 | 0.119361E+10 | 0.00 | 2907730.76 | 73016069.83 | 0.00 | 0.133818E+10 | 0.00 | 0.63 |
December | 0.137314E+10 | 0.750854E+09 | 0.00 | 1592356.67 | 33930601.46 | 64907465.64 | 0.886095E+09 | 0.00 | 0.52 |
Annual Sum or Average | 0.644303E+10 | 0.361876E+11 | 0.00 | 11907083.87 | 0.233251E+10 | 0.311343E+09 | 0.493555E+10 | 0.00 | 0.49 |
Minimum of Months | 0.00 | 0.297730E+09 | 0.00 | 0.00 | 6147444.77 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.210225E+10 | 0.623409E+10 | 0.00 | 2907730.76 | 0.440278E+09 | 0.102255E+09 | 0.133818E+10 | 0.00 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.208210E+10 | 0.290660E+09 | 0.00 | 774278.22 | 9729507.48 | 65159014.06 | 0.349175E+09 | 0.00 | 0.48 |
February | 0.125280E+10 | 0.401978E+09 | 0.00 | 1114234.71 | 6075120.45 | 0.109511E+09 | 0.528960E+09 | 0.00 | 0.52 |
March | 0.106928E+10 | 0.738356E+09 | 0.00 | 1239554.00 | 17977934.30 | 0.105166E+09 | 0.616225E+09 | 0.00 | 0.53 |
April | 0.175539E+09 | 0.150659E+10 | 0.00 | 1809729.79 | 82658216.65 | 0.00 | 0.684424E+09 | 0.00 | 0.57 |
May | 0.00 | 0.481546E+10 | 0.00 | 0.00 | 0.339095E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.541934E+10 | 0.00 | 105532.34 | 0.392977E+09 | 0.00 | 245228.70 | 0.00 | 0.43 |
July | 0.00 | 0.625412E+10 | 0.00 | 39604.71 | 0.439668E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
August | 0.00 | 0.606400E+10 | 0.00 | 0.00 | 0.383974E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
September | 708777.43 | 0.495177E+10 | 0.00 | 187366.89 | 0.308460E+09 | 0.00 | 65904.79 | 0.00 | 0.42 |
October | 74580508.25 | 0.387057E+10 | 0.00 | 1879213.65 | 0.237518E+09 | 0.00 | 0.435155E+09 | 0.00 | 0.49 |
November | 0.432748E+09 | 0.119135E+10 | 0.00 | 2846313.86 | 72999610.37 | 0.00 | 0.131351E+10 | 0.00 | 0.63 |
December | 0.138452E+10 | 0.749188E+09 | 0.00 | 1482102.51 | 34284714.06 | 74987030.36 | 0.834802E+09 | 0.00 | 0.52 |
Annual Sum or Average | 0.647227E+10 | 0.362534E+11 | 0.00 | 11477930.69 | 0.232542E+10 | 0.354823E+09 | 0.476256E+10 | 0.00 | 0.49 |
Minimum of Months | 0.00 | 0.290660E+09 | 0.00 | 0.00 | 6075120.45 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.208210E+10 | 0.625412E+10 | 0.00 | 2846313.86 | 0.439668E+09 | 0.109511E+09 | 0.131351E+10 | 0.00 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.205610E+10 | 0.271614E+09 | 0.00 | 705612.00 | 10258819.32 | 95051946.72 | 0.309073E+09 | 0.00 | 0.47 |
February | 0.126400E+10 | 0.386864E+09 | 0.00 | 969930.03 | 5839633.20 | 0.133306E+09 | 0.462309E+09 | 0.00 | 0.51 |
March | 0.112800E+10 | 0.718911E+09 | 0.00 | 1059272.04 | 17199540.50 | 0.115363E+09 | 0.509530E+09 | 0.00 | 0.52 |
April | 0.182667E+09 | 0.147979E+10 | 0.00 | 1667056.07 | 81732345.80 | 0.00 | 0.661208E+09 | 0.00 | 0.56 |
May | 0.00 | 0.477598E+10 | 0.00 | 0.00 | 0.341282E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.538692E+10 | 0.00 | 92427.02 | 0.391651E+09 | 0.00 | 230720.00 | 0.00 | 0.43 |
July | 0.00 | 0.622044E+10 | 0.00 | 48328.33 | 0.438356E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
August | 0.00 | 0.602837E+10 | 0.00 | 0.00 | 0.384432E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
September | 734455.68 | 0.491971E+10 | 0.00 | 191838.63 | 0.305300E+09 | 0.00 | 63192.10 | 0.00 | 0.42 |
October | 76431081.61 | 0.384519E+10 | 0.00 | 1806119.38 | 0.236495E+09 | 0.00 | 0.422389E+09 | 0.00 | 0.49 |
November | 0.472045E+09 | 0.117445E+10 | 0.00 | 2630773.94 | 72560346.17 | 0.00 | 0.124277E+10 | 0.00 | 0.62 |
December | 0.140271E+10 | 0.735676E+09 | 0.00 | 1287619.71 | 34166285.53 | 98808070.03 | 0.742626E+09 | 0.00 | 0.51 |
Annual Sum or Average | 0.658269E+10 | 0.359439E+11 | 0.00 | 10458977.15 | 0.231927E+10 | 0.442529E+09 | 0.435020E+10 | 0.00 | 0.48 |
Minimum of Months | 0.00 | 0.271614E+09 | 0.00 | 0.00 | 5839633.20 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.205610E+10 | 0.622044E+10 | 0.00 | 2630773.94 | 0.438356E+09 | 0.133306E+09 | 0.124277E+10 | 0.00 | 0.62 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.380928E+10 | 0.438483E+09 | 0.00 | 1101535.86 | 23063813.08 | 0.131083E+09 | 0.577347E+09 | 0.00 | 0.43 |
February | 0.238356E+10 | 0.645241E+09 | 0.00 | 1404513.13 | 13612354.01 | 0.249315E+09 | 0.701470E+09 | 0.00 | 0.46 |
March | 0.209120E+10 | 0.121408E+10 | 0.00 | 1406335.09 | 30055381.94 | 0.229621E+09 | 0.787460E+09 | 0.00 | 0.46 |
April | 0.282775E+09 | 0.266848E+10 | 0.00 | 2336529.88 | 90467816.31 | 0.00 | 0.110294E+10 | 0.00 | 0.49 |
May | 0.00 | 0.890427E+10 | 0.00 | 0.00 | 0.258054E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
June | 0.00 | 0.101911E+11 | 0.00 | 0.00 | 0.255757E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
July | 0.00 | 0.116076E+11 | 0.00 | 0.00 | 0.362294E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.113715E+11 | 0.00 | 0.00 | 0.247301E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
September | 0.00 | 0.906517E+10 | 0.00 | 156053.95 | 0.285896E+09 | 0.00 | 31510207.13 | 0.00 | 0.39 |
October | 85327570.39 | 0.724079E+10 | 0.00 | 2414504.17 | 0.166070E+09 | 0.00 | 0.683632E+09 | 0.00 | 0.44 |
November | 0.696059E+09 | 0.216256E+10 | 0.00 | 4122699.36 | 61593597.43 | 0.00 | 0.222469E+10 | 0.00 | 0.54 |
December | 0.268760E+10 | 0.129575E+10 | 0.00 | 1705360.03 | 48816696.15 | 0.170722E+09 | 0.112896E+10 | 0.00 | 0.44 |
Annual Sum or Average | 0.120358E+11 | 0.668050E+11 | 0.00 | 14647531.48 | 0.184298E+10 | 0.780741E+09 | 0.723801E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.438483E+09 | 0.00 | 0.00 | 13612354.01 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.380928E+10 | 0.116076E+11 | 0.00 | 4122699.36 | 0.362294E+09 | 0.249315E+09 | 0.222469E+10 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.187543E+10 | 0.213410E+09 | 0.00 | 522271.15 | 12809042.72 | 93124540.03 | 0.271962E+09 | 0.00 | 0.44 |
February | 0.114068E+10 | 0.316138E+09 | 0.00 | 670828.91 | 6588643.32 | 0.166684E+09 | 0.349477E+09 | 0.00 | 0.46 |
March | 0.104748E+10 | 0.599274E+09 | 0.00 | 650534.35 | 14385084.97 | 0.123372E+09 | 0.368681E+09 | 0.00 | 0.47 |
April | 0.143940E+09 | 0.132904E+10 | 0.00 | 1128821.38 | 44855895.27 | 0.00 | 0.555578E+09 | 0.00 | 0.49 |
May | 0.00 | 0.444458E+10 | 0.00 | 0.00 | 0.125826E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
June | 0.00 | 0.508401E+10 | 0.00 | 0.00 | 0.126919E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
July | 0.00 | 0.578477E+10 | 0.00 | 0.00 | 0.177372E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.566917E+10 | 0.00 | 0.00 | 0.119708E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
September | 0.00 | 0.451318E+10 | 0.00 | 84477.94 | 0.137992E+09 | 0.00 | 18852425.22 | 0.00 | 0.39 |
October | 42322498.52 | 0.360544E+10 | 0.00 | 1184687.29 | 82447142.77 | 0.00 | 0.345153E+09 | 0.00 | 0.44 |
November | 0.358753E+09 | 0.107364E+10 | 0.00 | 2022355.82 | 30519083.66 | 0.00 | 0.111513E+10 | 0.00 | 0.55 |
December | 0.133295E+10 | 0.643093E+09 | 0.00 | 791336.62 | 24299328.43 | 0.118740E+09 | 0.525042E+09 | 0.00 | 0.44 |
Annual Sum or Average | 0.594155E+10 | 0.332757E+11 | 0.00 | 7055313.45 | 0.903721E+09 | 0.501920E+09 | 0.354987E+10 | 0.00 | 0.44 |
Minimum of Months | 0.00 | 0.213410E+09 | 0.00 | 0.00 | 6588643.32 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.187543E+10 | 0.578477E+10 | 0.00 | 2022355.82 | 0.177372E+09 | 0.166684E+09 | 0.111513E+10 | 0.00 | 0.55 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.185509E+10 | 0.208649E+09 | 0.00 | 495281.43 | 13783398.27 | 0.112155E+09 | 0.262960E+09 | 0.00 | 0.43 |
February | 0.112606E+10 | 0.309892E+09 | 0.00 | 647693.78 | 7030035.69 | 0.181845E+09 | 0.340668E+09 | 0.00 | 0.46 |
March | 0.105931E+10 | 0.591916E+09 | 0.00 | 616767.55 | 14269011.96 | 0.123085E+09 | 0.348213E+09 | 0.00 | 0.47 |
April | 0.149440E+09 | 0.131799E+10 | 0.00 | 1111919.87 | 44788444.20 | 0.00 | 0.544209E+09 | 0.00 | 0.49 |
May | 0.00 | 0.442975E+10 | 0.00 | 0.00 | 0.126248E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
June | 0.00 | 0.507165E+10 | 0.00 | 0.00 | 0.126309E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
July | 0.00 | 0.577187E+10 | 0.00 | 0.00 | 0.177261E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.565726E+10 | 0.00 | 0.00 | 0.119489E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
September | 0.00 | 0.450092E+10 | 0.00 | 85021.73 | 0.137712E+09 | 0.00 | 19054704.05 | 0.00 | 0.39 |
October | 46463420.86 | 0.359547E+10 | 0.00 | 1159275.89 | 81987818.11 | 0.00 | 0.338068E+09 | 0.00 | 0.44 |
November | 0.367552E+09 | 0.106675E+10 | 0.00 | 1999937.83 | 30419315.99 | 0.00 | 0.109530E+10 | 0.00 | 0.55 |
December | 0.133241E+10 | 0.637116E+09 | 0.00 | 748150.38 | 24724787.05 | 0.131181E+09 | 0.498014E+09 | 0.00 | 0.44 |
Annual Sum or Average | 0.593632E+10 | 0.331592E+11 | 0.00 | 6864048.46 | 0.904023E+09 | 0.548266E+09 | 0.344648E+10 | 0.00 | 0.44 |
Minimum of Months | 0.00 | 0.208649E+09 | 0.00 | 0.00 | 7030035.69 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.185509E+10 | 0.577187E+10 | 0.00 | 1999937.83 | 0.177261E+09 | 0.181845E+09 | 0.109530E+10 | 0.00 | 0.55 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.181222E+10 | 0.201456E+09 | 0.00 | 448526.76 | 15333986.81 | 0.162834E+09 | 0.238767E+09 | 0.00 | 0.43 |
February | 0.107822E+10 | 0.299438E+09 | 0.00 | 590378.75 | 7384161.65 | 0.230282E+09 | 0.323735E+09 | 0.00 | 0.46 |
March | 0.103881E+10 | 0.578811E+09 | 0.00 | 549900.21 | 14078424.19 | 0.152511E+09 | 0.319792E+09 | 0.00 | 0.46 |
April | 0.169026E+09 | 0.129968E+10 | 0.00 | 1014535.83 | 45493683.69 | 0.00 | 0.514205E+09 | 0.00 | 0.49 |
May | 0.00 | 0.441962E+10 | 0.00 | 0.00 | 0.126859E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
June | 0.00 | 0.507022E+10 | 0.00 | 0.00 | 0.126526E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
July | 0.00 | 0.577975E+10 | 0.00 | 0.00 | 0.176206E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.566770E+10 | 0.00 | 0.00 | 0.120154E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
September | 0.00 | 0.450596E+10 | 0.00 | 85094.69 | 0.137405E+09 | 0.00 | 19066840.71 | 0.00 | 0.39 |
October | 52396217.88 | 0.359502E+10 | 0.00 | 1118674.55 | 82604088.36 | 0.00 | 0.327806E+09 | 0.00 | 0.44 |
November | 0.392421E+09 | 0.105916E+10 | 0.00 | 1880732.43 | 30718106.35 | 0.00 | 0.105103E+10 | 0.00 | 0.54 |
December | 0.131234E+10 | 0.627597E+09 | 0.00 | 668148.13 | 26242660.70 | 0.177732E+09 | 0.443313E+09 | 0.00 | 0.44 |
Annual Sum or Average | 0.585543E+10 | 0.331044E+11 | 0.00 | 6355991.35 | 0.909006E+09 | 0.723359E+09 | 0.323771E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.201456E+09 | 0.00 | 0.00 | 7384161.65 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.181222E+10 | 0.577975E+10 | 0.00 | 1880732.43 | 0.176206E+09 | 0.230282E+09 | 0.105103E+10 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.165814E+10 | 0.206085E+09 | 0.00 | 431826.17 | 13681778.58 | 0.283562E+09 | 0.253302E+09 | 0.00 | 0.44 |
February | 0.928822E+09 | 0.303726E+09 | 0.00 | 570444.35 | 8621463.30 | 0.357238E+09 | 0.332648E+09 | 1349.55 | 0.47 |
March | 0.904113E+09 | 0.588125E+09 | 57049.39 | 553808.33 | 13018209.52 | 0.247784E+09 | 0.334581E+09 | 103.60 | 0.48 |
April | 0.176241E+09 | 0.131058E+10 | 0.00 | 967695.21 | 41840473.87 | 0.00 | 0.533916E+09 | 0.00 | 0.51 |
May | 0.00 | 0.450162E+10 | 0.00 | 0.00 | 0.117145E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
June | 28919.69 | 0.520013E+10 | 0.00 | 0.00 | 0.122119E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
July | 0.00 | 0.594940E+10 | 0.00 | 0.00 | 0.169748E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.583873E+10 | 0.00 | 0.00 | 0.110085E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
September | 0.00 | 0.463747E+10 | 0.00 | 120977.65 | 0.135029E+09 | 0.00 | 19178027.80 | 0.00 | 0.39 |
October | 57042690.73 | 0.368767E+10 | 0.00 | 1127012.85 | 77989465.81 | 0.00 | 0.327923E+09 | 0.00 | 0.45 |
November | 0.396999E+09 | 0.108472E+10 | 0.00 | 1849976.85 | 27422578.05 | 0.00 | 0.106961E+10 | 0.00 | 0.57 |
December | 0.110233E+10 | 0.623699E+09 | 558954.37 | 687191.34 | 21877862.06 | 0.379830E+09 | 0.430617E+09 | 3222.62 | 0.45 |
Annual Sum or Average | 0.522371E+10 | 0.339320E+11 | 616003.76 | 6308932.76 | 0.858577E+09 | 0.126841E+10 | 0.330177E+10 | 4675.78 | 0.44 |
Minimum of Months | 0.00 | 0.206085E+09 | 0.00 | 0.00 | 8621463.30 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.165814E+10 | 0.594940E+10 | 558954.37 | 1849976.85 | 0.169748E+09 | 0.379830E+09 | 0.106961E+10 | 3222.62 | 0.57 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:41:29
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.205617E+12 | 0.148033E+11 | 0.00 | 0.281937E+11 | 0.286299E+11 |
February | 0.229504E+12 | 0.859180E+10 | 0.00 | 0.196716E+11 | 0.394250E+11 |
March | 0.262546E+12 | 0.509786E+10 | 0.00 | 0.137025E+11 | 0.558445E+11 |
April | 0.308234E+12 | -0.885801E+10 | 0.00 | -0.786603E+10 | 0.102602E+12 |
May | 0.314650E+12 | -0.364669E+11 | 0.00 | -0.616121E+11 | 0.228117E+12 |
June | 0.316953E+12 | -0.396791E+11 | 0.00 | -0.697297E+11 | 0.245543E+12 |
July | 0.325986E+12 | -0.465181E+11 | 0.00 | -0.810133E+11 | 0.273306E+12 |
August | 0.301867E+12 | -0.455396E+11 | 0.00 | -0.775980E+11 | 0.274384E+12 |
September | 0.253658E+12 | -0.387170E+11 | 0.00 | -0.633094E+11 | 0.237357E+12 |
October | 0.255536E+12 | -0.287434E+11 | 0.00 | -0.439326E+11 | 0.204343E+12 |
November | 0.187669E+12 | -0.161430E+10 | 0.00 | 0.682017E+10 | 0.816035E+11 |
December | 0.186140E+12 | 0.869842E+10 | 0.00 | 0.195262E+11 | 0.527708E+11 |
Annual Sum or Average | 0.314836E+13 | -0.208945E+12 | 0.00 | -0.317147E+12 | 0.182393E+13 |
Minimum of Months | 0.186140E+12 | -0.465181E+11 | 0.00 | -0.810133E+11 | 0.286299E+11 |
Maximum of Months | 0.325986E+12 | 0.148033E+11 | 0.00 | 0.281937E+11 | 0.274384E+12 |